MDR & Test Sheets PDF
MDR & Test Sheets PDF
MDR & Test Sheets PDF
7 Sabre Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Due to W.Lucy’s policy of continuous research and development, W.Lucy reserves the right to change the design and
specification of it’s products without prior notice.
Safety
Sabre VRN6a
Rated Voltage 12kV(15.5kV)
Impulse Withstand Voltage 75kV(95kV)
Normal Current Ring Switches 630A
Tee-Off Circuit Breaker 630A
Short Circuit Peak Making Current Ring Switches 50kA
Tee-Off Circuit Breaker 50kA
Short Circuit Breaking Current Tee-Off Circuit Breaker 20kA RMS
3 Second Short Time Current Ring Switches 20kA
Tee-Off Circuit Breaker 20kA
Earth Switch Peak Making Current Ring Switches 50kA
Tee-Off Circuit Breaker 50kA
Internal Arc Rating Freestanding 20kA 1 sec
Optional Cable Boxes Internal Arc Rating Standard Type 12.5kA 1 sec
Gas pressure Min Operating Pressure 0 Bar G
IP Rating Up to IP54
Weight 350kg
Testing standards BS EN 60265-1
BS EN 60129
BS EN 60694
BS EN 60298
IEC 60056
ENA TS 41-36
IEC 62271-102
IEC 62271-100
IEC 62271-103
* The weight stated is nominal and includes two ring switch cable boxes.
=Sabre VRN6a - IOM July 2009 LIOM01-006 - Issue 5 4
2.1 Sabre VRN6a Dimensions (Including Cabling Boxes)
Dimensions in millimetres
OQ
N
OP
O
P
OO
Q
S
ON
T
OM
U
NV
NU
NT
V
NS
NM
NR
NN
NQ
NP NO
4.3 Housing
The housing of the Sabre VRN6a is fully treated; using zinc coated steel and electrostatically applied oven cured paint, to resist
weather and pollution attacks. All units are provided with a hinged, weatherproof and lockable door. The external support legs can
provide a Tee-Off bushing height of 1402mm, 1320mm or 1100mm.
4.6 Operation
All operating positions and instructions are indicated on the main panel at the front of the unit. Operation is by means of manually
independent mechanisms, which are mounted externally to the gas enclosure.
The tee-off vacuum circuit breaker has two operating positions, 'ON' or 'OFF', with an off-load interlocked disconnector allowing
isolation & earthing of the tee-off circuit.
A single, "Y"-bar type operating handle is stored at the front door. Symbols located on the end of the operating handle indicate
direction of operation.
4.8 Interlocks
Positive safety interlocks are incorporated on all switch and circuit breaker positions.
4.9 Padlocks
The door has a quarter-turn handle that can be padlocked. The handle has a padlock hasp
hole size 8mm diameter.
All switch and selector positions can be padlocked. The padlock hasp hole size is 8.5mm
diameter.
Ring Switch
Bushings Profile “C”
Bolted Separable
Insulating Bushing Boot
Heat Shrink
Insulating Bushing Boot
5.6 Earthing
The Sabre VRN6a unit should be earthed at either of the primary
earth points. These earth points are located at the rear of the unit,
either side of the Cable Test Access Cover as shown.
Dimensions in mm
5.8 Marshalling Box
The marshalling box located on the left hand side of the unit and houses the terminals for all
customer options including ring switch actuators, pressure switch and EFI CT’s.
Circuit Resistance
Value
(microhms)
Any readings which are above these maximum values should be reported to appropriate supervising personal for review.
6.2.1 1 kV test.
• oÉãçîÉ=íÜÉ=É~êíÜ=äáåâ=EëÉÉ=ÄÉäçïFK
• Where units are not fitted with a removable earth link, ensure all earths are
removed from the unit, both internally and externally.
• If protection relays are fitted remove the relay from its housing on the front of the
unit before commencing test.
• Attach the black (negative) lead of the test set to the unit at any point where a
bolted connection is present (nut etc.).
• Using the red (positive) lead as a probe, test each of the connections located on
the terminal block in the Marshalling box for approx 2 seconds.
• Any indication of continuity should be investigated and rectified.
Position of earth link 2. Lift link with finger. 3. Rotate the link completely
away from the terminal.
Test Schedule
Test RH Ring LH Ring Disconnector CB Switch Apply Test Voltage To: Earth
Switch Switch
4 Open Open Service Closed U1, V1, W1, U2, V2, W2 U3, V3, W3
pÜçêíáåÖ= `áêÅìáí=_êÉ~âÉê=
qÉëí=mÜ~ëÉ `q=o~íáç qêáé=iÉîÉä
iáåâ ^Åíáçå
pÜçêíáåÖ= `áêÅìáí=_êÉ~âÉê=
qÉëí=mÜ~ëÉ `q=o~íáç qêáé=iÉîÉä
iáåâ ^Åíáçå
6.5.3 Relay Secondary Injection Tests - Overcurrent and Earth Fault Test
Consult the appropriate relay technical documentation for recommended secondary injection procedure, commissioning checks and
any necessary equipment required.
Check the pressure indicator on the front panel, behind main door.
Ensure the pointer is in the green zone before any switching
operations are carried out.
! Note: Ensure the 'Disconnector Padlock Flap' is in the 'CB AND DISCONNECTOR FREE' position before operation (Section
’7.3.1 Padlocking to prevent operation Remove padlock for operation’ on page 25).
! Note: Ensure the 'Disconnector Padlock Flap' is in the 'CB AND DISCONNECTOR FREE' position before operation (Section
’7.3.1 Padlocking to prevent operation Remove padlock for operation’ on page 25).
3. Firmly pull the operating handle down from the 'OFF’ &
‘RESET' to 'ON' position.
! Note: Ensure the 'Disconnector Padlock Flap' is in the 'CB AND DISCONNECTOR FREE' position before operation (Section
’7.3.1 Padlocking to prevent operation Remove padlock for operation’ on page 25).
! Note: Ensure the 'Disconnector Padlock Flap' is in the 'CB AND DISCONNECTOR FREE' position before operation (Section
’7.3.1 Padlocking to prevent operation Remove padlock for operation’ on page 25).
! Note: Ensure the 'Disconnector Padlock Flap' is in the 'CB AND DISCONNECTOR FREE' position before operation (Section
’7.3.1 Padlocking to prevent operation Remove padlock for operation’ on page 25).
3. Firmly pull the operating handle down from the 'OFF &
RESET' to 'ON' position.
! Note: Ensure the 'Disconnector Padlock Flap' is in the 'CB AND DISCONNECTOR FREE' position before operation (Section
’7.3.1 Padlocking to prevent operation Remove padlock for operation’ on page 25).
3. Rotate the operating handle from the 'MAIN ON' to the 'OFF'
position as shown. Note the arrow directions on the handle.
3. Rotate the operating handle from the 'OFF' to the 'MAIN ON'
position as shown. Note the arrow directions on the handle.
The 'Ring Switch' indicator will now show 'MAIN ON' as shown:
1. Open cable test access cover by holding the test box, pulling 2. Move the interlock flap out of the way of the required ring
the access knob forward, and then lower the test access switch test bushings.
cover.
3. Insert the operating handle into the star point earth bar and 4. When the star point earth bar is clear from all the bushings,
pull down away from the bushings. remove the operating handle and allow to pivot down into the
access cover as shown.
The ring switch can now be operated 'EARTH ON' to 'OFF' (see Section ’7.4.5 Switch from EARTH ON' to 'OFF'’ on page 34).
To allow access to a star point earth bar, remove the padlock on the side of the
required earth bar, then slide the padlock flap clear.
1. Slide the ‘Disconnector Padlock Flap’ to the right. 2. Push the CB cable test access cover knob in and rotate
clockwise 60°.
3. Rotate the handle anti-clockwise on top of the access cover 4. Rotate the handle access flap up.
and lift up the cover.
5. Insert the handle into the end of the removable star point 6. Lift the handle up removing the star point earth bar from the
earth bar. bushings.
11. Rotate the handle clockwise to lock the access cover. 11. To fully interlock the cover, turn the CB cable test access
cover knob anti-clockwise 60° and allow the to spring out.
Conditions
Housing Exterior:
Indoor and Outdoor Units:
• Check that all external fixings are present and tight
• Check that all labels are present
• Check that all earth connections are present
• Clean the unit thoroughly
• Touch up paint-work as necessary
If a unit has not been operated for a considerable time, and if it is practicable to do so, operate it a few times to ensure that
switch is functioning correctly.
The unit should be filled to the recommended pressure using either a temperature compensated gauge on the regulator head of the
SF6 supply or, where such a gauge is unavailable, compensating for temperature using a graph.
Before filling the switchgear, all pipes and fittings must be purged using SF6 to avoid any impurities inadvertently entering the unit or
contaminating the filling valve (Hansen valve B2H16-BS) on the unit. SF6 gas to IEC 60376 must always be used.
Note: Ensure all SF6 gas handling equipment is in good condition and moisture free.
LH Actuator
RH Actuator
3. Attach the switch labels as shown. 4. For connecting the Gemini umbilical cable into the
marshalling box terminals, please refer to Lucy document
no:-
DOC00041 - Gemini V1.2 To Lucy RMU Actuator
Wiring Schedule..
3. Ensure the actuator unit’s location collar has the slot in the 4. Locate the actuator unit into the ring switch aperture and
same orientation as the ring switch. The collar can be screw in the two location studs by hand.
adjusted to the correct position by pulling out and rotating.
5. Using a suitable screwdriver, tighten the location studs as 6. Secure the actuator unit with the two M12 nuts and washers,
shown. using the box spanner supplied.
Note: For the actuator to operate remotely the following conditions must apply:-
6. Insert into the remote actuator unit the operating handle and
rotate from the ‘OFF’ to ‘EARTH ON’ position.
i) the disconnector is in the ‘SERVICE’ position (see section 7.3.6 Operate CB/T-Off
from 'ISOLATE' to 'ON' on page 29).
ii) the circuit breaker and disconnector operation shutters are closed (See Section 7.3.1
Padlocking to prevent operation on page 26 and see section 7.3.7 Close CB to
’SERVICE’ on page 30).
If a power failure occurs during a circuit breaker ON’ to ‘OFF & RESET’ remote operation, it can be
continued manually by:
1. Open the remote actuator unit cover by undoing the captive 2. Firmly push in the actuator boss to disengage the actuator
screw. gearbox.
Captive Screw
2 TB WIP1 03.99 E
1 General 2 Characteristics and Features
The WIP1 is a self powered time overcurrent relay with •Auxiliary voltage supply is not required
multi-characteristics. Definite time and inverse time trip- •User-friendly setting procedure with wide setting
ping characteristics can be selected. The WIP1-1 does ranges
not require any aux. voltage supply, consequently it •Digital filtering of measured quantities by using dis-
can also be used for switchboards without built-in bat- crete Fourier analysis to suppress high frequency
teries. It takes its power supply energy from the C.T. harmonics and transient DC components induced by
circuits and provides the tripping pulse energy to the faults or system operations
circuit breaker. Due to its wide setting ranges, the trip- •Two-element overcurrent and short circuit relay
ping characteristic can be selected to protect a wide •Selectable protection functions between:
variety of different equipment. definite time overcurrent and
Optionally the WIP1 is available with earth fault ele- inverse time overcurrent
ment (option IE) and negative sequence element (option •Selectable inverse time characteristics acc. to
IS). IEC 255-4 :
normal inverse (type A)
The relay is buffered by a battery for feeding the LC very inverse (type B)
display as well as for memorizing fault values and reset extremely inverse (type C)
of the trip relay. Failure of the battery has no effect on special characteristics
the protective functions of the relay. The battery has a •Reset mode for inverse time characteristics selectable
service life of more than 10 years. •High-set overcurrent element with instantaneous or
definite time function
•Two-stage earth fault supervision (Option IE) with
tripping and/or alarm function
•Two-stage load unbalance supervision (Option IS)
•Redundant power supply unit for external voltage
supply (Option WIP1-2)
•Serial interface for connection to SCADA Systems
(Option WIP1-3)
•Phase and earth current measuring during normal
operation
•Five fault memories
•High-accuracy components and over-rating guaran-
tee precision, reliablity and a long service life
•High operating reliability through internal self-
supervision (watchdog); internal faults are indicated
by an alarm relay
•Remote tripping via external voltage
•High-capacity electro pulse output for direct trigger-
ing the circuit breaker
•Trip indication via external flag indicator with me-
chanical reset
•Two potential free alarm contacts, latched type (bi-
stable relay)
•Relay with one potential free contact; tripping func-
tion selectable
•Trip value indication via LCD display, battery-
buffered
•Compact construction
•Insensitive to extreme environmental conditions
•In accordance with the specified technical data, it
complies with the requirement of VDE regulation
0435-303, IEC255, VDE 0843
TB WIP1 03.99 E 3
3 Design
3.1 Connections
Important Information!
It is essential that the WIP1 is earthed via terminal .
Please note!
In this circuit we recommend earthing the current the earthing connection on WIP1 must be re-
transformers via the relay connection. *1: If the moved. Otherwise the measuring transformer for
current transformers have to be earthed directly, earth fault measuring is short circuited.
4 TB WIP1 03.99 E
Figure 3.3: Blockdiagram WIP1-I1 (only phase current measuring)
TB WIP1 03.99 E 5
Figure 3.4: Blockdiagram WIP1-I1-E1 with earth fault detection via C.T. cable type
6 TB WIP1 03.99 E
Figure 3.5: Connection example with relay tripping
The protection unit WIP1 receives the analog input Instantaneous means, a trip is initiated as soon as the
signals of the phase currents IL1 (1S1 - 1S2), minimum current is available (lowest power supply
IL2 (2S1 - 2S2) and IL3 (3S1 - 3S2) for phase current, value adjustable).
earth current and negative sequence measuring. The
measured current values are analogously filtered and After activation means, the high-speed tripping func-
fed to the analog/digital converter. tion only is activated if one of the phase currents ex-
ceeds the set value.
3.1.2 Control inputs The fast trip input can be applied for e.g. arcing fault
detectors.
Input remote tripping
The remote tripping input (terminals 20 and 22) en- Reset
ables tripping by an external voltage pulse, e.g. from a After a trip event the alarm relay is reset and the LED
thermal overcurrent tripping device, Buchholz protec- extinguishes when voltage is applied (see also chapter
tion or other external trip commands. By bypassing the 5.9).
measuring circuits, this input (230 V AC max. 5 min)
has a direct effect on the trip circuit. The input terminals
are galvanically decoupled from the relay electronics. 3.1.3 Operation outputs
TB WIP1 03.99 E 7
•Potential free contacts (auto-reset) 4 Working Principle
terminals (34, 35, 36)
For applications where a higher trip output energy is
4.1 Analog circuits
required, a relay with one potential free changeover
contact is provided in the trip circuit. This Relay can be
The alternating currents induced by the main current
assigned to any function (see 5.7).
transformers provide the WIP1's supply energy and
form the measuring value.
Example:
The measuring currents are galvanically isolated via the
When using DC coils it has be observed that the
input transformers, decoupled from high-frequency inter-
breaking capacity of the output contacts is not unlim-
ferences by analog RC-filters and then converted into
ited (see chapter 7).
current proportional voltages.
In case the coil burden is higher than the contact
The noise signals caused by inductive and capacitive
breaking capacity, the following circuit arrangement
coupling are supressed by an analog R-C filter circuit.
can be used:
The analog voltage signals are fed to the A/D-
converter of the microprocessor and transformed to
digital signals through Sample- and Hold-circuits. The
analog signals are sampled at 50 Hz (60 Hz) with a
sampling frequency of 800 Hz (960 Hz), namely, a
sampling rate of 1.25 ms (1.04 ms) for every measur-
ing quantity. (16 samples per periode).
@*OUFSOBM@'BVMU@
@@@@@@@@@@@@@@@@
8 TB WIP1 03.99 E
4.3 Battery buffer 4.4.3 LED
The relay is provided with a battery fed clock IC so The trip status is indicated by the LED at the front. If the
that the actual relay settings cannot be lost or parame- relay has tripped, the LED flashes and can be switched
ters can be set, even if the power supply is interrupted. off by pressing any push button.
An empty or missing battery does not impair the proper
working order of the relay.
4.5 Function push buttons
4.4 Indicating and operating elements The following four function push buttons are arranged
at the front of the relay:
4.4.1 Front plate
<SELECT/RESET> "Select" = Selection of function
There are the following indicating and operating ele- displayed (short pressing of the
ments at the front of the relay: push button)
•Two-line LC display with 16 characters per line "Reset" = Reset of trip functions
•Push buttons for adjustment and operation (long pressing of the push
•LED for trip indication button, for 3s)
<+> and <-> Selection of parameters
<ENTER> Storing parameters
4.4.2 Display <DISPLAY ON> Switching the relay on. If no
key is pressed longer than
All setting and measuring values as well as fault data 1 min. the relay switches off.
are shown in the LC display.
The push buttons <SELECT/RESET>, <+>, <-> and
<DISPLAY ON> can be activated without removing the
transparent cover by simply using a pin or screw
driver.
TB WIP1 03.99 E 9
4.6 Opening the front cover 4.7.1 Determining the maximum coil
resistance
For adjustment of the unit the transparent cover has to
be opened as illustrated. Do not use force! The trans-
parent cover has two inserts for labels.
10 TB WIP1 03.99 E
4.7.2 Characteristics of the current transformers
Figure 4.6: Circuit diagram of the secondary C.T. side and magnetizing curve
During normal operation the load of the current trans- For tripping in case of a single-phase fault:
former is only the WIP impedance and the impedances ISp
of the connection cables. In case of tripping, the trip- IL = eq. 1
0.9
ping coil also affects the transformer. Under any cir-
cumstances it must be prevented that this load has the for tripping in case of a 3-phase fault:
effect that the transformer gets into saturation to such an ISp
extent that the current flowing through the coil becomes IL = eq. 2
2
too low to ensure definite tripping.
The secondary transformer current Isec is proportional to The voltage UL where the flux reaches the value φs is
the primary transformer current and is a function of the called Umax in the following. Up to this point the trans-
transformation ratio. This current is divided into the former is still working in its precision class and the cur-
magnetization current of the transformer and a current IL rent IL is nearly as high as current Isec.
which flows through the current paths of the overcurrent
protection system. The voltage Umax can be calculated as follows:
The flux φ is proportional to the voltage UL and linked to
the magnetization current Iµ via the magnetization Umax = IL x ZLmax eq. 3
curve. As from the value φs the transformer moves into
saturation. As a result the magnetization current grows
overproportionally and the load current decreases at The impedance ZLmax results from the WIP impedance,
the same rate. So when the transformers are dimen- the cable impedances and the resistance of the trip-
sioned it must be taken into account that with a known ping coil during tripping of the WIP1.
resistance ZL the current IL is still sufficient for tripping the
coil. For this reason, the rated current of the tripping ZLmax = ZWIP + ZLeit + RSp eq. 4
coil must be inserted for ISp in the calculation below. As
the coil current ISp is a direct current, it must be con-
verted into an effective AC value by means of eq. 1 or
eq. 2. The result is, at the same time, the lowest switch-
ing point for possible tripping.
TB WIP1 03.99 E 11
The impedance of WIP1 for the respective pickup
value can be found in diagram 1 or diagram 2.
The resistance of the tripping coil can be determined
by measuring, or calculated from the rated data of the
coil.
If a transformer is loaded with its rated impedance ZN,
the max. power of the C.T. can be determined as fol-
lows:
First of all an explanation for the definition of the C.T.
data:
Class: 10P20;
Class 10 P 20
Tolerance 10%
Protection transformer (P)
ü (overcurrent factor)
The equation
Smax = Z N x (IN x ü)2 eq. 6
Smax
ZN = eq. 7
(ü x IN )2
2
SN = Z N x IN eq. 8
CAUTION:
With a setting value ≥ 12 x IN the resistance of the
tripping coil must not be smaller than 17 Ω.
12 TB WIP1 03.99 E
[Ζ /W]
[Ι/Ιν ]
[Ζ/Ω]
[Ι/Ιν]
Smax = SN x ü2 eq. 9
This means the result for Smax must not be higher than
1000 VA.
TB WIP1 03.99 E 13
4.7.4 Dimensioning example
For switching off a C.B. a tripping coil with a power of The rated impedance of the transformer is calculated in
PN = 10 W and a rated current IN = 0.45 A is used. acc. with eq. 7.
Zmax = 57.9 Ω.
14 TB WIP1 03.99 E
Figure 4.7:WIP1 - power consumption
TB WIP1 03.99 E 15
5 Operations and settings
)DXOWPHPRU\
)DXOWPHPRU\
)DXOWPHPRU\
)DXOWPHPRU\
\HV $FWLYDWHGE\
)DXOWPHPRU\ 7ULS"
'LVSOD\2Q
QR
0HDVXUHPHQWV ,6(*
,!,PLQ :,3
3URWHFWLRQ $FWLYDWHGE\
6HWWLQJV WUDQVIRUPHUFXUUHQW
.LQGRI7ULSSLQJ
5HOD\$VVLJQPHQW
6\VWHP
6HWWLQJV
6LJQDO,QSXW
)DVW7ULS
6LJQDO,QSXW
%ORFNLQJ
16 TB WIP1 03.99 E
5.1 Function of push buttons 5.1.1 Measuring value and fault
indication
The push buttons are used for calling parameters, se-
lecting the measuring quantities to be displayed and Display when the relay is de-energized:
for changing and saving of parameters. The relay is only activated after the <DISPLAY ON>
push button has been pressed. When the battery volt-
The different menus can be selected by pressing push age is too low (<3 V), the following is displayed:
button <+> or <-> and then called up by the
<SELECT/RESET> push button. If this push button is #BUUFSZ@7PMUBHF@
pressed for longer than 3 s, the display is reset. @@@UP@MPX@@@@@@@
By push button <ENTER>, the set and displayed values If the battery voltage is within the permissible range,
are saved in the internal parameter memory. Incidental the following is displayed:
or unothorized changing of parameters is prevented by
an obligatory password (see chapter 5.1.4). 1305&$5*0/
4&55*/(4
Push button <DISPLAY ON> is to activate fault indica-
In this mode measuring values cannot be read because
tion or for setting modes. Should no push button be ac-
the measuring mode is only activated if C.T. current is
tuated for 60 s, the relay switches off automatically.
available.
By pressing push buttons <SELECT/RESET>, <+> and
<-> simultaniuously and then activation of the relay by
If supply is present via C.T.s the following is indicated
the <DISPLAY ON> push button, the default settings of
on display:
the relay are saved in the parameter memory.
*4&(@@@@
%&'"6-54&55*/(4 8*1@@
@@@@"$5*7"5&%@@@
This display is referred to as ‘Main Menu’ and can be
entered from any menu point by pressing the
<SELECT/RESET> push button for about 3 s. This is the
push button all fault stores and parameter blocks can
be selected with.
Note!
If supplied via C.T.s a faulty battery or battery voltage
to low will be indicated too.
'"6-5
.FNPSZ@
TB WIP1 03.99 E 17
5.1.2 Display
The menu of the data displayed can be subdivided For the password any combination of the following four
into five groups : push buttons can be used:
1BSBNFUFS
1BTTXPSE@YYYY@@
1BSBNFUFS
TUPSF@WBMVF@@@@
18 TB WIP1 03.99 E
5.2 Display of measuring values The following faults can be displayed:
I> Overcurrent
.&"463&.&/54 I>> Short circuit
IE> Earth fault current
IE>> Earth fault
Measuring values can be displayed during operation FAST Fast trip
only. The C.T. current should sufficiently be rated to en- EXT External trip
sure power supply for the relay.
-@-@
-@-@ -@@&@
-@@&@
Here the current values at the trip instant are displayed
The measuring values (secondary C.T. currents) are in ampere.
direct shown in ampere.
These values are not displayed if the event is of ener-
These values are not displayed if the event is of ener- gizing nature only.
gizing nature only.
A peak value measured at the C.T. during the pick-up
A peak value is measured as well: phase is displayed.
-?@-?@ -?@-?@
-?@@&@ -?@@&?@
This value is saved in the fault memory when below the From the energizing time displayed can be concluded
pick-up value or in case of tripping. For an inverse time whether trippings have occured.
characteristic the pick-up time during the pick-up phase
is stored. 1JDLVQ@5JNF
U@U&
1JDLVQ@5JNF
U@@@@@@@@ %BUF@@@@
5JNF@@@@
5.3 Displaying the pickup phase The exact time the trip occured is also recorded. After
pressing the <SELECT/RESET> push button, message
If a pickup value is exceeded, the display will show the „Fault memory 1“ is displayed again.
pickup time.
If the pickup value drops below the treshold before Example: When selecting an inverse time characteristic
tripping takes place, the measuring values are dis- a reset time of 300 s is set and the following informa-
played. tion can be gathered in failure cases:
•Number of energizing events
•Max. current during each of the energizing events
5.4 Display of tripping values •Duration of the individual energizing events
•Time intervall between two energizing events
'"6-5 •Intervall between the energizing phases
.&.03:@ •Tripping time
•Tripping value at the instant of shut-down
The fault memory provided in the WIP1-1 can save up
to five trip events. The individual registers are selected
by push buttons <+> and <->. Configuration of all reg-
isters is identical.
53*1
*@@@-@YY@YY@Y@
TB WIP1 03.99 E 19
5.5 Protection parameters
5SJQQJOH@5JNF
5.5.1 Pickup value for phase U*@@@T@@@@
overcurrent element
When the „Definite time“ characteristic has been cho-
sen, the respective time displayed is to be understood
The pickup value for the phase overcurrent element I> is
in seconds which can gradually be changed by push
displayed as secondary C.T. current in ampere.
buttons <+> and <->.
0WFSDVSSFOU
*@@@@@"@@@
5.5.4 Reset mode for inverse
If this pickup value is set to "EXIT", the overcurrent trip is time tripping characteristics for
blocked. phase overcurrent element
3FTFU.PEVT
5.5.2 Time current characteristics for U@@T@@@@@@@@@
phase overcurrent element
To ensure tripping, even with recurring fault pulses
$IBSBDUFSJTUJD (packing faults) shorter than the set trip delay, the reset
/PSNBM@*OWFSTF@@ mode for inverse time tripping characteristics can be
switched over. For adjustment t = 60 s or 300 s, the
By setting this parameter one of the following nine mes- tripping time is maintained accordingly and only reset
sages appears on the display: after 60 s or 300 s faultless condition. This function is
off if t is set to 0. With breaking fault current, the trip
Definite_time protection: delay is reset immediately and started again at recur-
Definite_time ring fault current.
Inverse_time protection:
Normal_Inverse 5.5.5 Minimal time
Very_Inverse
Extremely Inverse This function is active with all inverse time tripping
RI-Inverse characteristics. It ensures that the trip delay is not faster
Long Time Inverse than the set value.
X^2_Time
X^2.5_Time .JOJNBM@UJNF
X^3_Time UMNJO@@@T
X^3.5_Time
Note: The minimum time cannot be set lower than the
X^4_Time
shortest trip delay of a tripping characteristic.
The latter depends on the multiplier of a tripping char-
The text displayed can be changed by <+> <-> push
acteristic.
buttons. By the <ENTER> push button the required
Example: selected characteristic x^4-time
characteristic is selected.
Faxtor: 0.8
The lowest adjustable minimum time then amounts to
0.16 s. This value is automatically increased if the mul-
5.5.3 Trip delay or time multiplier for tiplier of the characteristic is increased.
phase overcurrent element
After the characteristic is changed, usually the time de- 5.5.6 Current setting for high set
lay or time multiplier should be changed accordingly. element
5JNF'BDUPS The pickup value for the high set element appearing on
U*@@@@@@@@ the display is related to the secondary C.T. current
given in ampere.
When the “Inverse time” characteristic has been cho-
sen, the time factor tI> is displayed; this also can
gradually be changed by push buttons < +> and <->.
20 TB WIP1 03.99 E
5.5.10 Trip delay or time multiplier for
4IPSU@$JSDVJU earth fault overcurrent element
*@@@"@@@@@
(refer to 5.4.3)
When this pickup value is set to infinity (on the display
appears „EXIT“), the high set element of the relay is
blocked.
5.5.11 Reset mode for normal inverse
time tripping characteristics for
5.5.7 Trip delay for high set element
earth fault element
Irrespectively on the trip characteristic chosen for I>, the
(refer to 5.4.4)
high set element I>> has always a definite time trip-
ping characteristic. The indication value is displayed
as seconds.
5.5.12 Minimum tripping time (earth fault
element)
5SJQQJOH@5JNF
U*@@@T@@@@
(refer to 5.4.5)
5.5.8 Pickup value for earth fault
current element
5.5.13 Current setting for earth fault
The pickup value for the earth fault current element IE> high set element
is given in ampere as secondary C.T. current.
(refer to 5.4.6)
&BSUI@'BVMU
*&@@"@@@@@@
5.5.14 Trip delay for earth fault high set
If this pickup value is set to EXIT, the earth fault current element
element is blocked.
At WIP1-1 the earth fault current element is only ac- (refer to 5.4.7)
tivated if the current flowing in at least one of the
phases is higher than the lowest adjustable treshold
of the phase overcurrent element (0,5 A). 5.6 System parameters
At WIP1-2 the external power supply must be in opera-
tion. 5.6.1 Selection of the language
Definite time characteristics The language can be chosen by push buttons <+>
Definite time earth fault current protection and <->.
TB WIP1 03.99 E 21
This inquiry is acknowledged by push button 5.6.4 Time setting
<ENTER>. By pressing push button <SELECT/RESET>
this procedure is stopped and the next parameter is in- The same procedure applies for setting the time.
dicated.
1BSBNFUFS
/BNF@PME@@@@@@@@ 5JNF@@@@
1BTTXPSE@@YYYY@
To activate a new password, the existing one has to 5.6.5 Rated frequency setting
be entered first.
The adapted FFT algarithm requires the rated frequency
@TU@JOQVU@@@@@@ of the object to be protected as a parameter for exact
@1BTTXPSE@YYYY@ digital sampling and filtering of the input currents. Dis-
played is either "fN = 50 Hz" or „fN = 60 Hz“.
The new password can be entered by push buttons
<SELECT/RESET>, <ENTER>, <+> and <->. The place
3BUFE@'SFRVFODZ@
for entering the information is marked by the letter „x“ G/@@)[@@@@@@@@
on the display.
The rated frequency required can be adjusted by <+>
@OE@'FFE@@@@@@@ or <-> and then saved by <ENTER>.
@1BTTXPSE@YYYY@
1BSBNFUFS
*ODPSSFDU@*OQVU@
/FX@QBTTXPSE@@@@
JT@BDUJWF@@@@@@
1BSBNUFS
%BUF@@
22 TB WIP1 03.99 E
5.6.6 Adjustment of the slave address 5.7 Tripping method/Relay matrix
(WIP1-2-R)
5.7.1 Tripping method
4MBWF@"ESFTT
/P@@@@@@@@@@@@ This is to determine wether the C.B. is activated direct
via the electro pulse output or if to be switched via an
By pressing keys <+> or <-> the slave address can be interposing C.T. circuit (see figure 3.2 and 3.3).
set within a range from 1 - 32.
,JOE@PG@5SJQQJOH
&MFDUSP@1VMTF@@@
5.6.7 Baud Rate setting (WI1-2-R)
Note:
#BVE@3BUF If parameter is set on electro-pulse the output relay will
@@@@@@@@@@@@ also operate in case of tripping.
If parameter is set on relay the electro impulse output
The baud rate can be set by keys <+> and <-> and doesn’t connect with a trip coil.
then be saved by pressing <ENTER>.
5.7.2 Earth fault overcurrent
5.6.8 Setting of parity The trip relay can be assigned to the different trip ele-
ments and it can be defined wether the earth fault
1BSJUZ@$IFDL overcurrent function IE> should result in tripping.
&WFO@1BSJUZ@@@@@
&BSUI'BVMU@*&@
The following three parity settings are possible:
"MBSN@@@@@@@@@@@
&WFO, 0%%, /0 (no parity check) In this case alarm means that tripping of the latched re-
lay at the elctro impulse output and activation of the
The setting can be changed by push buttons <+> and LED are prevented. Exceeding of the pickup value
<-> and saved by pressing <ENTER>. incl. expiring of the tripping time is here regarded as
activation only.
(*) @*@@"MBSN@/P@@
@*@@5SJQ@@:FT@
(*) @*@"MBSN@/P@@
@*@5SJQ@@:FT@
(*) *&@@"MBSN@/P@@
*&@@5SJQ@@:FT@
(*) *&@"MBSN@/P@@
*&@5SJQ@@:FT@
TB WIP1 03.99 E 23
5.8 Signal inputs 5.9 Reset
5.8.1 Fast trip There are three possibilities to reset both the message
displayed at the WIP1 as well as the output relay:
By this operating input a fast trip can be initiated if a
specific minimum current flows via the measuring C.T.s. Manual Reset
Adjustable are two kinds of fast tripping: If the display is on by pressing the <SELECT/RESET>
push button for some time (about 3 s). Reset are: the
'"45@53*1 display, LED and signal relay.
*NNFEJBUFMZ@@@@@
External reset
Here a trip occurs when the C.T. current in at least one Applying voltage resets the signal relay and extin-
phase is sufficient to supply the relay. guishes the LED. The Display reads:
'BTU@5SJQ &YUFSOBM@3FTFU
"GUFS@1JDLVQ@@@@ BDUJWBUFE
Here a trip occurs when the current flowing is higher The display is maintained as long as the voltage signal
than the set treshold. is applied.
Note:
The voltage signal puts the battery under load.
5.8.2 Blocking the protection functions For this reason it should be kept as short as possible.
The blocking function of the WIP1 can be set acc. to Software Reset (optionally)
requirement. By applying the aux. voltage to terminals Resetting of a displayed message, of the LED and also
14 and 17 the functions chosen by the user are of the output relay can be realized via RS485 inter-
blocked. face. The effect of the Software Reset and the Manual
Reset is the same.
#MPDL@'VODUJPO@
*@/P@@@@@@@@@@@
For the "Yes" or "No" entry, push buttons <+> or <-> 5.10 Clearing the fault memory
are to be used. This applies for the overcurrent element,
short circuit element and if available earth fault overcur- Pressing push buttons <-> and <SELECT/RESET> (ap-
rent and high set element. prox. 3 s) at the same time results in clearing the fault
memory.
24 TB WIP1 03.99 E
6 Relay testing and
commissioning
TB WIP1 03.99 E 25
6.2.2 Example of test circuit
2 3 4
2S1
A
1
1S1
2S2
1S2
2S1
23
5
Start Timer Stop
28
24
25
1 = Variable voltage source
27
2 = Switching device
26
3 = Inductance 6
4 = Ammeter
5 = Timer
26 TB WIP1 03.99 E
6.2.4 Checking the tripping circuits
1305&$5*0/ Should the test current be so low that the coil fails to
4&55*/(4 trip, the test will be stopped.
After entering the correct password, the trip mode starts 5FTU@TUPQQFE
upon the following inputs. BSSFTU@DVSSFOU
5&45@$633&/5
4&5@50"NQ
3FMBZ@5FTU
JT@SVOOJOH
Break of 1s
Break of 1s
TB WIP1 03.99 E 27
6.2.5 Checking the input circuits and 6.2.7 Checking the high set element
measured values of the relay
Inject a current, which is less than the relay pickup cur- The high set element of the WIP1 is checked in the
rent set values, in phase 1 (terminals 1S1-1S2), and same manner. It is important, however, that the se-
check the measured current on the display by pressing lected test current is not too high because of trip delay
the push button <SELECT/RESET>. The current can be at inverse time characteristics may become shorter than
also injected into the other current input circuits the high set setting. The reason is that both tripping
(Phase 2: terminals 2S1-2S2, Phase 3: terminals signals operate the same tripping relay or the same
3S1-3S2. Compare the displayed current value with electro impulse output.
the reading of the ammeter. The deviation must not ex-
ceed 5% In. By using an RMS-metering instrument, a Note !
greater deviation may be observed if the test current Where test currents >2,5 x IN are used, the thermal
contains harmonics. Because the WIP1 relay measures withstand capability of the current paths has to be con-
only the fundamental component of the input signals, sidered (see technical data, chapter 7).
the harmonics will be rejected by the internal DFFT-
digital filter. Whereas the RMS-metering instrument
measures the RMS-value of the input signals. 6.2.8 Checking the external blocking
To check the relay operating time, a timer must be For this purpose the parameter "Blocking Function" in
connected to the trip output relay contact. The timer the menu "Signal input blocking" for the high set ele-
should be started simultaneously with the current injec- ment must be set to "Yes". Then the terminals 14 and
tion in the current input circuit and stopped by the trip 17 are supplied with auxiliary voltage
relay contact. Set the current to a value corresponding (e.g. 110 V DC).
to twice the operating value and inject the current in-
stantaneously. The operating time measured by the The time delay tI> should be set to EXIT for this test. In-
timer should have a deviation of less than 3% of the set ject a test current which could cause a high set (I>>)
value or ±10 ms (DEFT). Accuracy for inverse time tripping. Observe that there is no trip and alarm for the
characteristics refer to IEC 255-3. high set element.
Repeat the test on the other phases or with the inverse
time characteristics in the similar manner. Remove the auxiliary supply voltage from the blocking
In case of inverse time characteristics the injected cur- input. Inject a test current to trip the relay (message
rent should be selected according to the characteristic „TRIP“ on the display). Interrupt the test current.
curve, e.g. two times IS. The tripping time may be red
from the characteristic curve diagram or calculated
with the equations given under "technical data". 6.2.9 Checking the input "Fast trip"
Please observe that during the secondary injection test
the test current must be very stable, not deviating more The "Fast trip" function allows the unit to be tripped
than 1%. Otherwise the test results may be wrong. within the shortest possible time. A prerequisite for
correct tripping is the correct setting of the parameters.
In the menu "Signal input - fast trip" the setting should
be "instantaneously“. If a current is now injected which
is greater than the lowest adjustable overcurrent
threshold and an auxiliary voltage (110 V DC) is
supplied to the terminals 32 and 33, tripping takes
place instantaneously (tl>=50 ms ±10 ms).
28 TB WIP1 03.99 E
6.2.10 Remote trip
Checking the input "Remote trip" does not require any When the relay is switched on, the following informa-
test current. The terminals 20 and 22 are provided tion can be displayed by means of the CT current or by
with supply voltage (230 V AC ±20%). This leads to pressing the key „Display On“.
tripping within 200 ms.
Display of time and date begins with induction of the
Caution! CT current.
These terminals may only be supplied with voltage for
a maximum of 2 min. *4&(@@@@
8*1@@@@
-PTT@PG@%BUB
1SFTT@3FTFU
6.2.12 Checking the battery
The information will be indicated until the key
The battery test is carried out by pressing the key <SELECT/RESET> has been pressed for 3s; thereafter
<DISPLAY ON>. If the display indicates "Protection pa- the following is displayed:
rameter", the battery is ok.
'BVMUNFNPSZ
Note: DMFBSFE
Relays which have been out of order for more than one
month might show "Battery voltage too low" on the dis- If during this process the CT current exceeds a value of
play when the key <DISPLAY ON> is first pressed. The 0.5A in one phase, the self-supervising relay energizes
reasons for this are that, on the one hand, the capaci- for 1s.
tors are completely discharged and, on the other hand,
the long storage time of the battery. Data is read or processed permanently via the I2 C bus
of the processor. Should this communication be disrup-
But before replacing the battery the power supply has ted, the following is displayed:
switched off and the <DISPLAY ON> key is pressed
again. If "Battery voltage too low" is indicated again, *OUFSOBM@'BVMU
the battery does need replacing. 1SFTT@3FTFU
TB WIP1 03.99 E 29
6.3 Primary injection test
6.4 Maintenance
30 TB WIP1 03.99 E
7 Technical data
Measuring input
Signal inputs
Flag indicator
Mains part
TB WIP1 03.99 E 31
Battery:
Rated voltage: 3.6 V
Signal battery voltage
too low at: 2.7 V
Min. operating voltage: 2.5 V
Lifespan storage: 10 years
Operation: > = 5 years
Accuracy
Basic accuracy: ±5% related to the actual current measuring value
Frequency effect In the range of ±5% of the rated frequency, the current deviation is
0.5% per Hz.
Dropout to pickup ratio: >97%
Temperature effect At -20°C .... +55°C = ±1.5%
Climatic withstand
Storage: -40°C ... +85°C
Output relays
The output relays and watchdog relays have the following characteristics:
32 TB WIP1 03.99 E
7.1 System data
Design standard:
Generic standard: EN 50082-2, EN 50081-1
Product standard: EN 60255-6, IEC 255-4, BS 142
TB WIP1 03.99 E 33
Mechanical tests:
tI> 0.06 - 300 s 0.01; 0.02; 0.1; 0.2; 0.5; 1.0; 2.0; 5.0; 10; 20 ±3% or ±20 ms*
(definite time) s
0.05 - 10 ±5% for NINV
(inverse time) 0.01; 0.02; 0.05; 0.1; 0.2; 0.5 ±7,5% for VINV and EINV
X^2 - X^4
tmin 0.06...2 s ±3% or ±10 ms
0.01; 0.02; 0.05 s
I>> 1...35 (EXIT) 0.02; 0.05; 0.1; 0.2; 0.5; 1.0 A ±3% of setting value or
min. ±1% In
tI>> 0.06...2 s 0.01 s; 0.02 s; 0.05 s ±3% or ±10 ms
* Currents in the range from 0.5 to 1.5 A lead to trippings with increased trip delays (up to 50 ms).
If a C.T. current >0.5 A was present before tripping, the trip delay decreases (about 20 ms).
Annotation to WIP1-1:
The earth fault current element is only activated if the current flowing in at least one of the phases is higher than the
lowest adjustable treshold of the phase overcurrent element (0,5 A).
34 TB WIP1 03.99 E
7.3 Inverse time tripping characteristics
Tripping characteristics acc. to IEC 255-4 for phase and earth current element
0.14
Normal Inverse (Type A) t= 0.02
⋅ tI >
I
−1
Is
13.5
Very Inverse (Type B) t= ⋅ tI >
I
− 1
Is
80
Extremly Inverse (Type C) t= ⋅t
2 I>
I
−1
Is
120
Long Time Inverse t= t I > [s]
I
1
Is
1
RI-Inverse Time t= tI > [s]
0.236
0.339 −
I
I
S
100
X^2- Tripping delay: t= ⋅t
2 I>
I
IS
100
X^2.5- Tripping delay: t= ⋅t
2.5 I>
I
IS
100
X^3- Tripping delay: t= ⋅t
3 I>
I
IS
100
X^3.5- Tripping delay: t= ⋅t
3.5 I>
I
IS
100
X^4- Tripping delay: t= ⋅t
4 I>
I
IS
TB WIP1 03.99 E 35
7.3.1 Tripping characteristics
10000
1000
1000
100 tI>=
100
10.0
t[s] 8.0
t[s] tI>=
6.0 10
10 4.0
3.0
2.0 10.0
8.0
1.4 6.0
1.0
1 4.0
0.8 3.0
0.6 2.0
0.5 1.4
1 0.4 1.0
0.3 0.8
0.6
0.2
0.1 0.5
0.4
0.05 0.1 0.2 0.3
0.1
0.05 0.01
0.1
1 2 3 4 5 6 7 8 9 10 20 1 2 3 4 5 6 7 8 9 10 20
I/IS I/IS
Figure 7.1: Normal inverse tripping characteristic Figure 7.3: Extremely inverse tripping characteristic
100
1000
tI>=
10.0
8.0
7.0
6.0
5.0
100
4.0
tI>= 10 3.0
2.0
t[s] 10 t[s]
1.0
10.0
8.0 0.8
6.0 0.7
0.6
4.0 0.5
3.0
0.4
2.0 1 0.3
1 1.4
1.0
0.8 0.2
0.6
0.5
0.4
0.3
0.1
0.2
0.1
0.1
0.05 0.05
0.1
1 2 3 4 5 6 7 8 9 10 20 1 2 3 4 5 6 7 8 9 10 20
I/IS I/IS
36 TB WIP1 03.99 E
10000 1000
1000 100
tI>=
100 10
t[s] 10.0
8.0 t[s]
6.0
5.0
4.0 10
3.0 8.0
2.0 6.0
10 1 4.0
1.0 3.0
0.8 2.0
0.6
0.5 1.4
0.4
1.0
0.3 0.8
0.2 0.6
1 0.1 0.4
0.1 0.3
0.2
0.1
0.05
0.1 0.01
1 2 3 4 5 6 7 8 9 10 20
1 2 3 4 5 6 7 8 9 10 20
I/IS I/IS
Figure 7.5: Long Time Inverse Figure 7.7: x^2- tripping characteristic
1000
100
100
I>
0.5 2.5
10
10
t[s]
t[s] 300
tI> 10
1 8.0
6.0
1
0.06 4.0
3.0
I>>
1.0 35 2.0
2.0 1.4
tI>> 1.0
0.8
0.1 0.6
0.1
0.4
0.3
0.06 0.1 0.2
0.01 0.01
1 10 1 2 3 4 5 6 7 8 9 10 20
I/IN I/IS
Figure 7.6: Definite time tripping characteristic Figure 7.8: x^2.5- tripping characteristic
TB WIP1 03.99 E 37
1000 1000
100 100
10 10
t[s] t[s]
10 10
8.0 8.0
6.0 6.0
1 1
4.0 4.0
3.0 3.0
2.0 2.0
1.4 1.4
1.0 1.0
0.8 0.8
0.6 0.6
0.1 0.1
0.4 0.4
0.3 0.3
0.1 0.2 0.1 0.2
0.01 0.01
1 2 3 4 5 6 7 8 9 10 20 1 2 3 4 5 6 7 8 9 10 20
I/IS I/IS
Figure 7.9: x^3- tripping characteristic Figure 7.11: x^4- tripping characteristic
1000
100
100
I>
0.5 2.5
10
10
t[s] t[s] 2
tI >
10 1
8.0
6.0
1 0.06
4.0
3.0 I>>
1.0 35
2.0 2.0
1.4
1.0 tI>>
0.8 0.1
0.6
0.1
0.4
0.3 0.06
0.1 0.2
0.01
0.01 1 10
1 2 3 4 5 6 7 8 9 10 20
I/IS I/IN
38 TB WIP1 03.99 E
Figure 7.13: Trip example
TB WIP1 03.99 E 39
7.4 Relay case
Connection terminals
The connection of up to a maximum of 2 x 2.5 mm2 cross-section conductors is possible. For this the transparent
cover of the unit has to be removed (see para. 4).
40 TB WIP1 03.99 E
7.5 Flag indicators
■ panel cut-out: 31 x 20 mm
TB WIP1 03.99 E 41
8 Order form
* The additional power supply does not deliver the trip energy when using the impulse output!
WIP-BAT
Spare battery for WIP1 yes no
42 TB WIP1 03.99 E
Setting list WIP1-1
Note !
All settings must be checked at site and should the occasion arise, adjusted to the object/item to be protected.
Date:
System parameters
Protection parameters
Kind of tripping
* When using a tripping coil the parameter has to be set to „Electro pulse“.
TB WIP1 03.99 E 43
Relay matrix
Signal inputs
44 TB WIP1 03.99 E
Switchgear Test Certificate
Ring Main Unit
Details
Customer ADAPT
Customer Ref No. 117-00040 Lucy Ref No. 317-00423
Serial Number. SF00135812 Date. 14.05.2017
Equipment Rating
System Level rating 12 kV
Impulse Level 95 kV
Max Current(Ring/T-Off/Other) 630A / 630A
Designation VRN 6a
Confirmation of Compliance
The following tests have been completed successfully on the above mentioned equipment(s) and values/levels
achieved are within stated requirements in accordance with the respective standards & specifications:
Primary Tests (completed on all equipment relative to rating) IEC/BS Other Ref:
Standard
(x)
Ref
Dielectric Power Frequency Test on main circuit 60694(7.1) &
28kV AC applied for 1 minute - Passed (Withstood successfully) 62271-1(7.1)
Supplementary Tests
Main circuit resistance tested including earth circuit & values observed below 60694(7.3) &
maximum permissible values. 62271-1(7.3)
Test Circuits (Applicable as per the unit) Max. Permissible Values in
Micro-Ohms
T-Off to Earth 1200
L.H & R.H Ring Switch to Earth 500
L.H Ring Switch to R.H. Ring Switch 240
L.H. & R.H. Ring Switch to T-Off 250
L.H. & R.H. Ring Switch to L.H & R.H. Extn n/a
T-Off to L.H. & R.H. Extensible n/a
60694(7.2) &
1kV DC Insulation resistance check on aux wiring circuits - Passed
62271-1(7.2)
Internal
2kV AC Power Frequency check for one minute on aux wiring circuits - Passed standard
60694 &
Verification of correct wiring (including protection) - Passed
62271-1
60694(7.5) &
Visual inspection checks - Passed 62271-1(7.5)
Mechanical operation Checks (including interlocks, earthing points & 60694(7.2) &
switch/breaker operation as applicable) - Passed 62271-1(7.2)
60694(7.2) &
Aux Electrical device Checks - Passed
62271-1(7.2)
60694(7.4)
Gas Tightness test - Passed
61958
Confirmation of operation of VPIS - Passed
(x) Lucy Electric reserves the right to reference other appropriate test standards as required.
Quality Department
Lucy Electric Doc. No.: LGL-QUA-PRO-F-21, Issue 4
M.I.P.
800 Amp Series
Aluminium Body Size D – 11000V
Bolted Adaptor n
Select complete Adaptor from Table 1
Ordering
o Select Phase Thimble from Table 2
Procedure
pSelect Accessories from Table 3
B804TPA
Table 1 Table 2
Part No. Description Colour Phase Thimble – c/w item 1
B804TPA 800A / 11kv Bolted Adaptor Red Part No. Cable CSA mm 2 ID mm Utilux Die No.
NB: Adaptor supplied with Pilot Thimble F-201-432 25 8.0 38-92 Cu
F-201-302 35 9.5 38-115 Cu
F-201-303 50 10.5 38-115 Cu
F-201-303-1 70 13.0 38-142 Cu
F-201-304-1 95 14.0 38-165 Cu
F-201-305-1 120 16.0 38-165 Cu
F-201-306-1 150 18.0 38-183 Cu
F-201-307-1 185 21.8 SOLDER ONLY
F-201-326-1 240 24.2 SOLDER ONLY
F-3641 300 26.3 40-281 Cu
F-3641-1 240 24.2 40-281 Cu
F-3641-2 185 21.2 38-231 Cu
Table 3
Accessories
Part No. Description
F-800 800A Phase Pin
800-150A Phase
F-810
13 Transition Pin
F-829 800A Pilot Pin
1 800-300A Phase
F-830
Transition Pin
12 2 800-425A Phase See Aluminium Body Size
F-840
Transition Pin D Accessories
F-029 Pilot Socket
3
8516-2 Blanking Cover
4 N-862 Blanking Cover with
11 Pilot Diode
4534 Socket Extraction Tool
5
Spare Parts
Item Part No. Description
1 AH009868 Screw ¼” x 2¼” skt head
10 2 AI018994 O-ring ID 184.0 x Sect 5.0
3 4468 Phase Pin
9 6 Interior
4 F-804-1 c/w items 6, 12 & O-ring AI019021
8 5 See table 2 Phase Thimble
7
6 F-4466 Phase Insulator
c/w O-ring AI019020
7 F-3517-804 11kv Adaptor Body
c/w items 2, 7, 8, 9, 10 & 13
8 AH113111 Earth Screw M10 x 16 hex head
9 AH151011 Spring Washer M10
Weight: 16.0kg 10 AH150011 Washer M10
Dimensions: L 250mm W 250mm H 290mm 11 8505 Pilot Socket & Thimble
Compliance: Non Hazardous Area only, Dimesions to AS1300 12 AH007225 Screw ¼” x 5⁄8” csk head
Materials: Aluminium / Polyester 13 3378 Guide Pin
Accessories Ordering
Procedure n
Select complete Accessory from
Table 1
Table 1
Accessories
Part No. Description
F-800 800A Phase Socket
3
Parts List
Item Part No. Description
1 F-800 Phase Socket
2A F-810 800-150A Phase Transition Pin
2B F830 800-300A Phase Transition Pin
2C F-840 800-425A Phase Transition Pin
3 F-829 Pilot Pin
7
4 4480 Blanking Cover Shroud
4 5 AH113116S Screw M10 x 50 hex. head
6 6 AH120011 Nut M10
7 4534 Socket Extraction Tool
This is to certify that the following transformer has passed the High Voltage and other routine tests as detailed in the standard AS-2374.1.2 and
AS/NZS-60076 and are within the tolerances specified in part 1.
Serial Number 17568-2
Rating 1500kVA Voltage Ratio (No Load) 11000 / 1000-577
Vector Group Dyn 11 Mounting Type Groundmount
Phases 3 Oil Quantity 980 ℓ
Frequency 50 Total Mass 4600 kg
HV Separate Source Test Voltage (50Hz–1min) 28 kV HV Induced Withstand Test Voltage 22000 V
LV Separate Source Test Voltage (50 Hz–1 min) 10 kV LV Induced Withstand Test Voltage 2000 V
HV Tap Voltages (Nominal Tap Underlined) HV-Earth Minimum Insulation Resistance3 >2 GΩ
1 11275 V LV-Earth Minimum Insulation Resistance3 >2 GΩ
N 2 11000 V HV-LV Minimum Insulation Resistance3 >2 GΩ
3 10725 V
4 10450 V
5 10175 V
6 9900 V
NOTES:
1 Values at reference temperature of 75°C.
2 Values at reference temperature of 75°C, unity power factor and full load.
3 Values at reference temperature of 20°C.
550 Rosebank Road, Auckland | PO Box 15121, New Lynn, 0640 | p +64 9 820 6110 | etel@eteltransformers.co.nz | www.eteltransformers.co.nz
©ETEL LTD. All rights reserved. No part of this document shall be transmitted to a third party or copied in any form without prior permission in writing from ETEL LTD.
7/09/2005 ABB
Setting of Electronic OCR relays
Time current curve LLL
1E4s
1E3s I1
100s
L
t1
10s
I2
1s S t=k
I2t=k
t2
0.1s 2
I I3
1E-2s
MCCB Time Current curves are generally as shown above. Blue for Electronic and Red for
Thermal Magnetic circuit breakers. Electronic MCCB’s have greater adjustment
possibilities.
Generally used in Power Distribution. Select either S(I2) or I(I3) function – not both.
7/09/2005 ABB
Generally used in higher level applications where more advanced setting are required.
Isomax MCCB’s use trip units as below:
There is also a time setting t1 used to adjust the length of time required the MCCB will
accept a current as adjusted for I1. Generally this setting is made according to the
requirements of the load eg a motor requires a longer time. For power distribution setting is
generally 12 - 18 sec.
When adjusting a Tmax MCCB the setting follows In x (0.4 + 0.04, 0.05, 0.16, 0.32).
Isomax follows a direct In x dip switch indication.
When adjusting a Tmax MCCB the setting follows In x sum of (1 +1.5 +2+5.5). Isomax
follows a direct In x dip switch indication.
In some cases you can exclude this function in favour of the I2 or S function. In particular
when discrimination is required.
When adjusting a Tmax MCCB the setting follows In x sum of (0.2 +0.25 +0.55). Isomax
follows a direct In x dip switch indication.
1E3s
G
I4
100s
10s
1s
0.1s t4
This information has been provided as a guide only. No responsibility is taken by ABB
in regards to the choice of settings made. Each application should be carefully assessed
before settings are chosen.
ELRC-1
EARTH LEAKAGE RELAY
“COMPACT” VERSION WITH BUILT-IN TOROIDAL TRANSFORMER
GENERALITY
MODELS
ELRC-1/35 ELRC-1/60
110Vac/dc-230-400 Vac
ELRC-1/80 ELRC-1/110
ELRC-1/35 ELRC-1/60
24 - 48 Vac/dc
ELRC-1/80 ELRC-1/110
OPTIONS
F built-in filter for 3rd harmonic
Double output contact NO-C-NC
2
(in such a case the relay is renamed as ELRC-2/...)
T tropicalisation
The ELRC-1 have the particularity that they are manufactured with the Such a feature allows to easily choose the tripping current value, in the
buit-in Toroidal Transformers. way that the voltage values are maintained below 50V, in compliance
They are specially conceived for those applications, in which the space with the CEI Standards.
saving is an advantage (for example, in MOTOR CONTROL CEN- It allows also to perform a tripping selectivity, whenever there are more
TERS, BATTERIES OF DISTRIBUTION, etc.). ELR’s or RCD’s in the same line.
Although its reduced dimensions , the relay has as wide setting ranges Other important feature is its insensitivity to external disturbances and
as the other ELR’s series. pulse currents with dc components (presents in the line), due to the filters
built on the input circuits, as pe rthe VDE Standards.
LEGEND
1 Potentiometer for tripping time setting.
16 2 Potentiometer for tripping current setting.
5 4 1 2 Microswitches for constant selection:
• time:
K = 1 with micro (a) in position 0;
K=10 with micro (a) in position 1;
3
• current:
K=0,1 with micros (b-c) in position 0;
K= 1 with micro(b) in position 1and (c) in position 0;
K=10 with micros (c-b) in position 1
a
b
c 4 Test push button.
d
1 0
5 Manual reset push button.
6 Signalling lamp for Aux. Supply presence (green LED).
7 Signalling lamp for relay tripped (red LED).
6 7 3
ELRC-1
EARTH LEAKAGE RELAY
“COMPACT” VERSION WITH BUILT-IN TOROIDAL TRANSFORMER
ELECTRICAL CHARACTERISTICS
Auxiliary Voltage supply 24-48V ac/dc / 110 Vac/dc - 230 - 400 Vac ± 20% (standard)
Frequency 50 ÷ 60 Hz
Maximum consumption 3 VA
Current tripping ajustment range I∆N 0,025÷0,25A K=0,1 - 0,25÷2,5A K=1 - 2,5÷25A K=10
Tripping time setting range 0,02 ÷ 0,5 sec. K=1 - 0,2 ÷ 5 sec. K=10
Output: 2 change over contacts 5A 250V
Working Temperature -10 + 60°C
Storing Temperature -20 + 80°C
Relative Humidity 90%
Insulation Test 2,5 kV 60 sec.
CEI 41-1/IEC 255/VDE 0664/IEC 755/CEI 64.8/ EN 61008-1(1999-11)/EN 62020 (1999-09) /
Standards
EN 61543 (1996-09) /EN61326-1(1998-04) / EN 61326/A1 (1999-05)-IEC 60947-2 ANNEX M
Wiring method Screw terminals for cross section wire 2,5 mm2
Terminals protection according with DIN 40050 IP20
WIRING DIAGRAM
SUPPLY Vaux
N L1 L2 L3 BA
Earth
LEGEND
------------------------------------------
BA 0-1 = 110 V ac/dc
0-3 = 230 V ac
0-5 = 400 V ac
--------------------------------------
6 5 4 3 2 1 0
0-1 = 24 V ac/dc
Vaux 0-2 = 48 V ac/dc
--------------------------------------
TRIP
17
LOAD
DIMENSIONS
H
DIMENSIONS (mm)
D type
A A B C D E F G H
E ELRC-1/35 35 100 60 110 47 70 60 50
ELRC-1/60 60 100 60 110 47 70 60 50
Ø5
ELRC-1/80 80 150 110 160 70 70 60 50
C G
B F ELRC-1/110 110 150 110 160 70 70 60 50
N24 DIGITAL PANEL METERS
• Destined for measurement of d.c. voltage or d.c. current,
temperature through Pt100 resistance thermometers,
J, K thermocouples, a.c. voltage and a.c. current.
FeATUReS: • 4 LED digit displays with 20 mm digit high.
• Parameters programmable by PD14 programmer:
– precision of displayed results (decimal point),
– measurement averaging time,
– recounting of indications (individual characteristic),
– automatic or manual compensation: cold junction
temperature for measurement with thermocouples
or wire resistance for measurement with Pt100 (N24T).
Example of application
INPUTS:
Measurement and display:
Supplying
N24 output 24 V d.c. - temperature
digital - analog signals
meter
- d.c. current and voltage
PD14 - rms current and voltage.
programmer
Current
60 mV
PC Computer
Programming using
LPConfig program
a.c. current
shunt transformer
Temperature
Pt100 probe
Inputs
Type Measuring ranges Parameters Overloads Errors
-11 mV...-10 mV...60 mV...66 mV
-66 mV...-60 mV...60 mV...66 mV Short duration overload (1s):
Input resistance >1 MΩ Basic error:
-0.5 V...0 V...10 V...11 V - voltage input: 10 Un ± (0.2% of range + 1 digit)
oUTPUTS: N24S
-11 V...-10 V...10 V...11 V
- current input: 5 In
Sustained overload:
Additional error from ambient temperature
changes: ± (50% of basic error/10K)
-1 mA...0 mA...20 mA...22 mA Input resistance 10 Ω ±1% 110% Un, 110% In
3.6 mA...4 mA...20 mA...22 mA Input resistance 10 Ω ±1%
Current flowing through the
-50˚C...150˚C sensor: < 300 µA.
Resistance of wires connecting Basic error:
RTD with the meter: ± (0.2% of range + 1 digit)
Pt100
- max 5 Ω (per wire) for automatic
Short duration Additional errors:
-50˚C...400˚C compensation
N24T overload (1s) • compensation of cold junction temperatu-
- max 10 Ω (per wire) for manual
compensation Input of sensors: 30 V re changes: ± 0.2% of range,
GAlVANIC Thermo- • from ambient temperature changes:
ISolATIoN: couple J
-50˚C...1200˚C ± (50% of basic error/10K).
Thermo-
-50˚C...1370˚C
couple K
1...100...120 V a.c.
2.5...250...300 V a.c. Short term overload (1s): Basic error:
voltage input: 2 Un (< 1000V), • voltage and current: ± (0.5% of range
4...400..600 V a.c. Input resistance > 2 MΩ current input: 10 In
+ 1 digit) in frequency range 20...500 Hz
N24Z 20...500 Hz Sustained overload: • frequency: ± (0.02% of range + 1 digit)
(in voltage range: 24...480 V) 150% Un (for 400 V input),
120% (for remaining inputs), Additional error from ambient temperature
0.01...1...1.2 A a.c. Input resistance 10 mΩ ±10% 120% In changes: ± (50% of basic error/10K)
0.05...5...6 A a.c. Input resistance 2 mΩ ±10%
Export department: 0...100...110 V d.c.
+48 68 45 75 139/276/ 0...250...275 V d.c. Short term overload (1s):
305/ 386 voltage input: 2 Un (< 1000V),
-120...-100...100...120 V d.c. Input resistance > 2 MΩ Basic error:
Fax: +48 68 32 54 091 current input: 10 In
± (0.2% of range + 1 digit)
e-mail: export@lumel.com.pl N24H -300...-250...250...300 V d.c. Sustained overload:
Additional error from ambient temperature
-600...-400...400...600 V d.c. 150% Un (for ± 400 V input),
120% (for remaining inputs), changes: ± (50% of basic error/10K)
-1.2...-1...1...1.2 A d.c. Input resistance 10 mΩ ±10% 120% In
„LUMEL” S.A. -6...-5...5...6 A d.c. Input resistance 2 mΩ ±10%
ul. Słubicka 1
65-127 Zielona Góra
POLAND
Outputs
WWW.LUMEL.COM.PL For N24S and N24T Output for supply external transducers 24 V ± 5%, 30 mA
N24 digital panel meters
External features
Weight < 0.25 kg
Overall dimensions 96 x 48 x 64 mm (with terminals)
Protection grade (acc. to EN 60529) ensured by the housing: IP65 from the terminal side: IP 20 See Also:
Display 4-digit LED display, 20 mm high, red colour indication range: -1999...9999
Resistance Resistance
thermometer in a thermometer in a Fig. 4. Electrical connections of N24Z and N24H meters for
Fig. 1. Electrical connections of the N24S meter two-wire system three-wire system
with manual with automatic the measurement of voltage (and frequency only in N24Z)
compensation compensation
Ordering
OUR OFFER
Table 1. Ordering codes: Table 2. INPUT SIGNALS
N24 - X X X XX XX X X Nr N24S N24T N24Z N24H
Input kind: 1 0...20 mA Pt100: -50...150°C 100 V a.c. ±100 V d.c.
2 4...20 mA Pt100: -50...400°C 250 V a.c. ±250 V d.c.
standard: voltage, current S 3 0...60 mV Thermocouple J 400 V a.c. ±400 V d.c.
temperature: thermocouples, 4 0...10 V Thermocouple K 1 A a.c. ±1 A d.c.
T
resistance thermometers 5 ± 60 mV 5 A a.c. ±5 A d.c.
a.c. signals Z 6 ± 10 V 20...500 Hz 0...100 V d.c.
d.c. signals: high voltage and high current H 7 0...250 V d.c.
Input:
Table 3. codes of printed units:
see table 2 X www.lumel.com.pl
Supply: Code Unit Code Unit Code Unit
00 without unit 06 mA 12 bar
230 V a.c. 1 01 ˚C 07 kA 13 kPa For more information
110 V a.c. 2 02 % 08 kV 14 MPa about LUMEL’s
24 V a.c. 3 03 A 09 Hz products please visit
85...253 V a.c./d.c. with supply output 24 V/30 mA* 4 04 V 10 turns XX on order our website:
05 mV 11 rpm
20...40 V a.c./d.c. with supply output 24 V/30 mA* 5 www.lumel.com.pl
Unit: Table 4. Example of non-standard settings:
see table 3 XX Parameter Range/Value
Version: Decimal point 000,0 for I, U
standard 00 Averaging time 1s
non-standard settings NS Upper measurement overflow 9999
Lower measurement overflow -1999 Export department:
custom-made** XX Individual characteristic enabled +48 68 45 75 139/276/
Language: Parameter a of the individual characteristic 5 305/ 386
Polish P Parameter b of the individual characteristic 0 Fax: +48 68 32 54 091
English E Order example 1 : Order example 2 : e-mail: export@lumel.com.pl
other** X The code N24Z-2 1 04 00 E 0 means The code N24S-1 4 02 NS E 1 means:
Acceptance tests: N24Z - digital meter for a.c. signals N24S - digital meter for d.c. signals
without extra requirements 0 2 - input: 250 V a.c. 1 - input: 0...20mA
1 - supply: 230 V a.c. 4 - supply: 85...253 V a.c. wiht supply output: „LUMEL” S.A.
with an extra quality inspection certificate 1
04 - unit: V 24V/30mA
acc. to customer’s request** X ul. Słubicka 1
00 - standard version 02 - unit: %
* -The output is only in N24S and N24T meters NS - non-standard settings, display range:
65-127 Zielona Góra
E - English language
** - After agreeing with the manufacturer 0 - without extra requirements 0...100.0 POLAND
E - English language WWW.LUMEL.COM.PL
1 - with an extra quality inspection certificate
N24-19A/1