HAT600 Series HAT600/HAT600I/HAT600B/HAT600BI Ats Controller User Manual
HAT600 Series HAT600/HAT600I/HAT600B/HAT600BI Ats Controller User Manual
HAT600 Series HAT600/HAT600I/HAT600B/HAT600BI Ats Controller User Manual
HAT600/HAT600I/HAT600B/HAT600BI
ATS CONTROLLER
USER MANUAL
CONTENT
1 OVERVIEW .................................................................................................... 5
2 PERFORMANCE AND CHARACTERISTICS................................................. 6
3 SPECIFICATION ............................................................................................ 8
4 OPERATING .................................................................................................. 9
4.1 OPERATION PANEL ...................................................................................... 9
4.2 KEY FUNCTION DESCRIPTION ............................................................ 10
5 LCD DISPLAY .............................................................................................. 11
5.1 MAIN SCREEN .................................................................................... 11
5.2 MAIN MENU INTERFACE ...................................................................... 14
6 COMMISSIONING ........................................................................................ 15
7 PARAMETERS CONFIGURATION .............................................................. 16
7.1 PARAMETERS TABLE .................................................................................17
7.2 INPUT/OUTPUT FUNCTION DESCRIPTION ........................................ 21
8 EVENT LOG ................................................................................................. 23
9 TIMING START ............................................................................................ 24
10 DATE AND TIME SETTING ...................................................................... 25
11 LANGUAGE SETTING .............................................................................. 26
12 CONTROLLER INFORMATION ................................................................ 27
13 ATS OPERATION ..................................................................................... 28
13.1 MANUAL OPERATION ............................................................................. 28
13.2 AUTOMATIC OPERATION ....................................................................... 28
13.3 ATS POWER SUPPLY ..................................................................................29
14 COMMUNICATION CONFIGURATION .................................................... 30
15 DESCRIPTION OF CONNECTING TERMINALS ...................................... 31
16 TYPICAL WIRING DIAGRAM .................................................................... 33
17 INSTALLATION ......................................................................................... 37
18 FAULT FINDING ....................................................................................... 38
1 OVERVIEW
◙ Measure and display active power, apparent power, power factor and 3
phase current;
◙ Over current alarm;
◙ Over/under voltage, loss of phase, reverse phase sequence, over/under
frequency protection.
◙ Automatic/Manual mode. In manual mode, can force switch to close or open;
◙ All parameters can be set on site. With Two different passwords which
ensures authorized staff operation only.
◙ During genset testing ATS controller can be set either on On-load or Off-load
mode.
◙ ATS Controller has function of automatic Re-closing.
◙ Closing output signal can be set as on intervals or as continuous output.
◙ Applicable for ATS of one neutral position, two neutral position and change
over.
◙ Applicable for 2 isolated neutral line for Generator and Mains.
◙ Real-time clock (RTC).
◙ Event log can record 99 items circularly.
◙ Timely schedule can be set on monthly or weekly basis and trial can be set
as with on- load or off -load.
◙ Can control two generators to work in a cycle, even the genset running time
and crank rest time can be set.
◙ Widely range of DC power supply (8V to 35V). Max.80V DC input can be
endured in an instant, or be supplied via HWS560 module (input AC
85V~560V, output DC 12V).
HAT600 √ × ×
HAT600I √ × √
HAT600B √ √ (LN220V) ×
HAT600BI √ √ (LN220V) √
3 SPECIFICATION
4 OPERATING
5 LCD DISPLAY
In the screen, press key, can enter the main menu interface.
1. Parameters set
2. History record
3. Time start Press key to choose parameters
4. Date & Time Set (the current line was highlighted with
black) and then press key to
3. Time start confirm, can enter the corresponding
4. Date & Time Set display screen.
5. Language
6. Information
6 COMMISSIONING
On the main screen press to enter into the operation interface, the screen will
show as following:
1 Exit
2 Stop to Test
3 Test Off-Load
4 Test On-Load
5 Cyc start
generator only when mains is abnormal. After mains return normal, the ATS will
transfer the load to mains. Here the start generator signal output will keep.
TEST ON-LOAD: It will send out a start generator signal immediately. After
generator voltage is normal, the ATS will transfer the load to mains immediately
regardless whether the main is normal or not.
STOP TO TEST: The start generator signal will turn off after pressing this key
immediately.
CYCLE START: When this mode is active, generator start-signal will cyclic output
according to mains status. The cyclic time can be set by users. If generator fault
occurs, start-signal won’t be send out anymore by controller. If in manual mode,
controller will keep the current status and cancel cycle start function.
Conditions and procedures for cycle start mode:
1. In automatic mode.
2. Output setting: 1# engine start output (N/O Output) and 2 # engine start output
(N/O Output).
3. Input setting: 1# generator fault input, 2# generator fault input and remote start
input.
4. Option of <Cycle run times> and <Cycle shutdown times> should be
programmed and run.
5. Set the system type as 1# Gens & 2# Gens.
6. Set the proper <generator start delay> time.
Note: In manual mode, after choosing commissioning stage, generator will output
start-signal immediately, but the ATS will not transfer to load automatically except
for operation manually by pressing key on the front panel.
7 PARAMETERS CONFIGURATION
In the main interface, press key, choose 1.Parameters setting and then
press key, to enter the password interface.
Input password value 0-9 by key, and to shift Right by key. Press the
again to confirm the password when Four number is OK. If password correct and
enter into the parameter mains interface. While error, directly exit and return to
main interface. Factory Default Password is 1234. to shift to next
position and set the parameters. While setting the current configuration
parameters according to press key. Then enter current parameter model,
and the current value of the first line screen display was highlighted with black.
Press key to change the value while press key to shift position, and
press key again to confirm the password when Four number is OK. If the
value number is within the setting range, the value will be saved into the internal
memory of the controller; If it is beyond the range, then the parameters setting will
not be saved. Long time press will back to the main display screen.
8 EVENT LOG
On the main screen press key and select 2 Event log, and then pressing
key, the screen will show the event log
1# Shut interface as follow:
1# Volt normal
2# Below Volt
2010-02-18 21:15:07 1/99
Press key to select the corresponding record, and press key to enter into
detailed information interface.
In the detailed information interface, press key can display the record
information circularly. The detailed information include specific status of voltage,
current, frequency and time-to-event. Press will exit the current interface,
Event log include:Record type, 1# power supply status, 2# power supply status,
1# 3-phase voltage, 2# 3-phase voltage, 3-phase current, 1# frequency, 2#
frequency and time-to-event.
Event log type:
NO. Type Description
1 1# Shut 1# close signal output
2 2# Shut 2# close signal output
3 1# Fail to Shut 1# power supply can not connect to
load.
4 2# Fail to Shut 2# power supply can not connect to
load.
5 1# Fail to Break off 1# power supply can not disconnect to
load.
6 2# Fail to Break off 2# power supply can not disconnect to
load.
7 Trip alarm The input is active.
8 Breaking compulsorily Breaking compulsorily input is active.
9 TIMING START
On the main screen press key and select 3 Time start, and then pressing
key, the screen will show the time start interface as follow:
1 Exit
2 Time start cyc
3 Load set
4 Start time
5 Continue time
Time start cycle: Include inhibit start; single time, weekly or monthly.
Load set: Starting generator with load or without load.
Start time: Generator start date and time.
Continue time: Generator continuously run time can be set on the duration of
maximum time for 99 hours 59 minutes.
Press key according to the corresponding bit input values 0-9, pressing
key to carry through the right of bit shift; pressing key when right shift to the
end, can update the date and time.
Date and time format set: year-month-date (week) and hour: minute.
On the main screen press key and select 5 Language, press again to
enter into language setting interface and the screen will show the language
interface as follow:
1.Simplified Chinese
2.English
Information
One OFF Position
1# Priority
Ver1.0 2009-10-11
Display content includes off positions setting and
switching priority choice and controller version, date.
Long pressing key will exit and return to main screen.
Press key and manual operation indicator light, and the manual mode is
active.
● Press , 1# close relay outputs immediately, if 1# closing input is active, its
indicator lights, and the 1# source connect to load.
● Press , 2# close relay outputs immediately, if 2# closing input is active, its
indicator lights, and the 2# source connect to load.
Press and the automatic LED will light, enter AUTO mode and controller ca n
automatically switch load to 1# or 2#.
The power of ATS is supplied by controller, as long as one power is normal, this
can ensures ATS voltage power supply normally and can be transferred properly.
Users should select power supply voltage (phase voltage or line voltage) based
on ATS type. If choose phase voltage, connect the phase voltage (A1) to normally
close (Pin5) and normally open (Pin7) contact of auxiliary output 1; connect N
phase (A1) to normally close (Pin8) and normally open (Pin10) contact of auxiliary
output 2. And then connect the common output of auxiliary output1&2 to ATS
power supplies. When controller power is ON, parameters can be set and also set
the configurable output1 as "ATS power L1". If the ATS power supplied by Line
Voltage, setting way is same as above, but need to change phase N to phase B.
Wiring diagrams are shown as following:
ATS L-N voltage power supply ATS L-L voltage power supply
Note: Normally Close (N/C) input voltage must come from 1# voltage.
14COMMUNICATION CONFIGURATION
HAT600 series controller has RS485 serial port, can connect the local area
network openly. It uses Modbus protocol via PC or system software, it can also be
applicable to dual power switching management to factories, telecom, industrial
and civil buildings, which achieves “remote control, remote measuring, remote
communication” functions.
More information of Communication Protocol, refer to “HAT600 Communication
Protocol”.
Communication parameters,
Module address 1 (range: 1-254, User can set it)
Baud rate 9600 bps
Data bit 8bit
Parity bit None
Stop bit 1 bit or 2-bits(set via PC)
1 1# close 250V16A(relay
2 Volt-free relay contact output
output capacity)
3 2# close 250V16A(relay
Volt-free relay contact output
4 output capacity)
5 NC Default: ATS Volt-free relay
6 Aux. output 1 Common power of L1 contact output:
7 NO output. 250V16A
8 NC Default: ATS Volt-free relay
9 Aux. output 2 Common power of N contact output:
10 NO output. 250V16A
11 A1
For single phase,
12 B1 1# AC 3-phase 4 wire voltage
only connect A1,
13 C1 input
N1
14 N1
15 A2
For single phase,
16 B2 2# AC 3-phase 4 wire voltage
only connect A2,
17 C2 input
N2
18 N2
35 RS485 GND
36 IA Input Sensing from Secondary
37 IA Output phase A current
NOTE: All above are application diagrams of HAT600 series ATS controllers.
However, HAT600 and HAT600B have no sample current input, please skip over
the current part of the diagram.
17INSTALLATION
18FAULT FINDING