Caterpillar XQ20 Towable Diesel Generator Set
Caterpillar XQ20 Towable Diesel Generator Set
Caterpillar XQ20 Towable Diesel Generator Set
STANDBY 20 kW
PRIME 18 kW
60 Hz
Standby Prime
Voltage kW (kVA) kW (kVA)
208/120V 3 PH 20 (25) 18 (22.5)
480/277V 3 PH 20 (25) 18 (22.5)
240/120V 1 PH 17 (17) 16 (16)
FEATURES
EPA TIER 4 AND CARB CERTIFIED FOR MULTI-VOLTAGE DISTRIBUTION PANEL
NON-ROAD MOBILE APPLICATIONS. ● Switchable voltage output:
LEHE5041-06
XQ20
STANDBY 20 kW
PRIME 18 kW
60 Hz
LEHE5041-06 2
XQ20
STANDBY 20 kW
PRIME 18 kW
60 Hz
SPECIFICATIONS
GENERATOR ENGINE
Voltage Regulation . . . . . . . . . . . . . . ± 0.5% 3 Phase at steady state Manufacturer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Caterpillar®
from no load to full load Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C2.2
Frequency Regulation . . . . . . . . . ± 0.85% for constant load from Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-Cycle
no load to 100% load Aspiration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NA
Waveform Distortion . . . . . . . . . . . . . . . . . THD <4.0%, at no load Cylinder Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . In-line 4
Radio Interference . . . . . . . . . . . . . . Compliance with EN61000-6 Displacement — L (in3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.2 (135)
Telephone Interference . . . . . . . . . . . . . . . . . . . . TIF <50, THF <2% Bore — mm (in) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 (3.3)
Overspeed Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2250 rpm Stroke — mm (in) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 (3.9)
Insulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Class H Compression ratio. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23.3
Temperature Rise. . . . . . . . . . . . . . . . . . . . . . Within Class H limits Governor
Available Voltages. . . . . . . . . . . . . . . . . . . . . 480/277 Volt 3 phase, Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mechanical
208/120 Volt 3 phase, Class. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Class A1
240/120 Volt single phase Air cleaner type . . . . . . . . . . . . . Dry, replaceable paper element,
Deration . . . . . . . . . . . . . . . Consult factory for available outputs type with restriction indicator
Ratings . . . . . . . . . . . . . . . . . . . . . . At 25° C (77° F), 100 m (328 ft), Piston speed — m/sec (ft/sec) . . . . . . . . . . . . . . . . . . . . . 6.0 (19.7)
30% humidity, 0.8 pf (3-Phase), 1.0 pf (1-Phase) Engine speed — rpm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1800
Maximum power at rated rpm — kW (hp)
Standby . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24.3 (33)
Prime . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 (30)
BMEP — kPa (psi)
Standby . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 731 (106)
Prime. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 658 (96)
LEHE5041-06 3
XQ20
STANDBY 20 kW
PRIME 18 kW
60 Hz
G C F H
CONTROL PANEL I
A NEMA 1 steel enclosure with hinged lockable door
and viewing window. A
B Off/auto/run switch.
C Panel light ON/OFF switch. M J
D Pre-heat pushbutton.
E Red emergency stop pushbutton. L E
F Voltage adjust potentiometer.
G Voltmeter and ammeter. N D
H Frequency meter.
I Battery voltage indicator. O B
J Fuel, level display with momentary activation
pushbutton. K
K Hours run meter. 6
L 7 position voltmeter phase selector switch. 1
M 4 position ammeter phase selector switch. 5
N Oil pressure gauge. 2
O Water temperature gauge. 7
OTHER FEATURES 3
● Shutdowns: high coolant temperature/low coolant 4
level, low oil pressure, overcrank, overspeed.
● Low fuel level/fuel tank leak alarm. 3 Main bus connection studs for 1 phase and 3 phase
● Printed circuit board control logic. enclosed with hinged transparent cover. Includes
● Autostart standard. safety lockout feature to keep unit from operating
● Cycle cranking with 3 adjustable time with the door open.
crank/rest periods. 4 2 — Single phase — California style Twistlocks,
● Battery charger, 5 Amp constant voltage, UL listed 50 Amps @ 208 Volt phase to phase, 120 Volt phase
(optional). to neutral (adjustable to 240/139) or 240/120 single
phase when operating in single phase voltage
DISTRIBUTION PANEL position.
1 3 pole, 100 Amp molded case circuit breaker (M5) 5 2 — Single phase — GFCI Duplex receptacles,
with solid neutral UL/CSA listed with shunt trip. 20 Amps @ 120 Volts.***
Provides thermal and magnetic overload protection 6 Remote start contact terminals.
when using receptacles. 7 Individual circuit breaker protection for receptacles,
2 3 Pole, 100 Amp MCCB with solid neutral, UL/CSA also act as on/off switches.
listed with shunt trip. Integral trip unit for thermal
and magnetic overload protection when using main
bus connections. *** Receptacles not for use with unit operating at 480/277V or
240/139V 3 phase.
LEHE5041-06 4
XQ20
STANDBY 20 kW
PRIME 18 kW
60 Hz
Weight
With Lube Oil With Fuel, Lube
Length Width Height & Coolant Oil & Coolant
Model mm (in) mm (in) mm (in) kg (lb) kg (lb)
XQ20 1980 (78) 820 (32.3) 1555 (61.2) 1020 (2,248) 1166 (2,571)
XQ20 with trailer 3429 (135) 1596 (62.8) 1822 (71.7) 1253 (2,761) 1399 (3,084)
RATING DEFINITIONS
Standby — Applicable for supplying continuous Prime — Applicable for supplying continuous electrical
electrical power (at variable load) in the event of power (at variable load) in lieu of commercially
a utility power failure. No overload is permitted on purchased power. There is no limitation to the annual
these ratings. The generator on the generator set hours of operation and the generator set can supply
is peak prime rated (as defined in ISO8528-3) at 86° F. 10% overload power for 1 hour in 12 hours.