Circuit breakers must be connected serially to BAT+, PHASE-L1, PHASE-L2 and PHASE-
L3 terminals, in close proximity of the unit.
Fuses must be of fast type with a maximum rating of 6A.
Disconnect all power before working on equipment .
When the genset is running, do not touch terminals.
Do not try to clean the device with solvent or the like. Only clean with a dump cloth.
Verify correct terminal connections when wiring.
Electrical equipment should be serviced only by competent service personnel. No
responsibility is assured by the manufacturer or any of its subsidiaries for any
consequences arising out of the use of this material.
Only for front panel mounting.
CONNECTION DIAGRAM
DKG-116 User Manual V-03 (30.03.2011)
PROGRAMMING
N 3- Press MENU button for saving the Low AC Voltage limit and
MENU displaying the next program parameter.
N
5- Press MENU button for saving the parameter and displaying
MENU the next parameter.
6- Repeat steps 4 and 5 as required.
7- Any time on settings, press MENU button for 3 sec. to exit from
RUN STOP
program mode.
N
DKG-116 User Manual V-03 (30.03.2011)
44mm
DC Supply Range: 9.0 to 16.0 V-DC
Cranking dropouts: survives 0 V for 100ms.
Typical Standby Current: 12mA-DC (display off)
Maximum Operating Current: 130 mA-DC
Fuel and Crank outputs: 10A @ 12V-DC
Auxiliary Output: 1A @ 12V-DC (negative pulling
protected semiconductor output)
92mm
Magnetic pickup Input: 1.5 to 30Vpp
Operating temp.: -40°C (-40°F) to 80 °C (176°F).
Maximum humidity: 95% non-condensing. PACKAGING INFORMATION
Dimensions: 102 x 55 x 40 mm (WxHxD)
Pieces per Package: 24
Packed weight: 140 g
Package Size: 280 x 170 x 215mm (LxWxH)
Case Material: High Temp. ABS/PC (UL94-V0)
Package Weight: 3.6 kg
IP Protection: IP65 (front panel), IP30 (rear)
Conformity (EU directives)
-2006/95/EC (low voltage)
-2004/108/EC (EMC)
Norms of reference:
EN 61010 (safety requirements)
EN 61326 (EMC requirements)