Power System Protection Lecture Notes
Power System Protection Lecture Notes
Mohammed Tawfeeq
Power System
Protection
Lecture Notes
Mohammed T. Lazim
Alzuhairi
1
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
In this course the power system is considered as all the plant and
equipment necessary to generate, transmit, distribute and utilize
the electric power.
2
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
Auto control for voltage, frequency, reactive power compensation, power flow,
network configuration and stability
Local manual control (plant status, voltage level reactive power support,
network configuration)
Communications infrastructure
3
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
Abnormalities:
4
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
Types of Faults
5
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
Faults in Windings
6
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
Single-Phase-Ground: 70 – 80 %
Phase-Phase-Ground: 17 – 10 %
Phase-Phase: 10 – 8 %
Three-Phase: 3 – 2 %
Poles collapsing
Conductors breaking
Vehicle impact
Etc
7
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
8
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
Should be affordable
9
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
PR Protection Relay
CB Circuit Breaker
Equip Protected Item
CT Current Transformer
VT Voltage Transformer
DC Aux DC Auxiliary supply
HMI Man-machine interface
PCL Communications Link
Tr CB trip coil
11
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
1 4
2.1
5
2 A D
2.2
2.4 P
F.A.
2.3
3
1 – CT or VT , 2- Relay 3- TC 4- CB 5- DC supply
11
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
2.1
2 A D
12
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
2 Circuit breakers
isolate the fault by
interrupting the
current.
Tripping power, as
well as power 1 4
required by the
relays, is usually
provided by the
station battery
because is safer 2.1
than the ac faulted
system.
2 A D
5
2.2
2.4 P
F.A.
2.3
3
13
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
What is a Relay?
Device which receives a signal from the power system and
determines whether conditions are "normal" or "abnormal"
(measuring function)-
The purpose of the protective relaying systems is to isolate only the faulty
component of power system.
Relaying equipments are classified into two groups:
1. Primary relaying equipment.
2. Back-up relaying equipment.
Primary relaying is - the first line of defense for protecting the equipments.
Back-up protection relaying works only when the primary relaying
equipment fails (they are slow in action).
14
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
15
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
■ Security
* Relay should not cause circuit breaker to open during
normal conditions
■ Dependability
* Relay should cause circuit breaker to open
during abnormal conditions
■ Sensitivity
Ability of a relay to detect all faults for the expected
limiting system and fault conditions
■ Selectivity
Ability of a relay system to discriminate between
16
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
17
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
Classification of Relays
Protection relays can be classified in accordance with the function which they
carry out, their construction, the incoming signal and the type of protection.
1. General function:
Auxiliary.
Protection.
Monitoring.
Control.
2. Construction:
Electromagnetic.
Solid state.
Microprocessor.
Computerized.
Nonelectric (thermal, pressure ......etc.).
3. Incoming signal:
Current.
Voltage.
Frequency.
Temperature.
Pressure.
Velocity.
Others.
4. Type of protection
Over current.
Directional over current.
Distance.
Over voltage.
Differential.
Reverse power.
Other.
18
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
Definitions:
■ Normally open contact ( N/O): is one which is open when the relay is not
energized.
■ Normally closed contact (N/C): is one which is closed when the relay is not
energized.
■ Operating force or torque: that which tends to close the contacts of the relay.
■ Restrain force or torque: that which opposes the operating force or torque
and tend to prevent the closure of the relay contacts.
■ Pick-up level: the value of the actuating quantity (current or voltage), which is
on the border above which the relay operates.
■ Drop-out or reset level: the value of current or voltage below which a relay
opens its contacts and comes to original position..
■ Operating time: the time which elapses between the instant when the
actuating quantity exceeds the pick-up value to the instant when the relay
contacts close.
■ Reset time: the time which elapses between the instant when the actuating
quantity becomes less than the reset value to the instant when the relay contact
returns to its normal position.
■ Primary relays: the relays which are connected directly in the circuit to be
protected.
■ Secondary relays: the relays which are connected in the circuit to be
protected through CTs and V.Ts.
■ Auxiliary relays: relays which operate in response to the opening or closing of
its operating circuit to assist another relay in the performance of its function. This
relay may be instantaneous or may have a time delay.
■ Reach: a distance relay operates whenever the impedance seen by the relay
is less than a prescribed value, this impedance or rt]ic corresponding distance is
known as the reach of the relay.
■ Instantaneous relay: One which has no intentional time-delay and operates in
less than 0.1 second.
■ Blocking: preventing the protective relay from tripping cither due to its own
characteristics or to an additional relay.
19
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
Types of Relay
Others:
Temperature
Pressure
Attracted Plunger
Armature Type
21
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
1. Electromagnetic relays
Electromechanical Relays
� Research Began at the End of the 19th
Century
� The Relay Family Was Completed in
the 1930’s
� They Are Still in Use
These relays were the earliest forms of relay used for the protection of power
systems, and they date back nearly 100 years. They work on the principle of
a mechanical force causing operation of a relay contact in response to a
stimulus. The mechanical force is generated through current flow in one or
more windings on a magnetic core or cores, hence the term
electromechanical relay. The principle advantage of such relays is that they
provide galvanic isolation between the inputs and outputs in a simple, cheap
and reliable form – therefore for simple on/off switching functions where the
output contacts have to carry substantial currents, they are still used.
Electromechanical relays can be classified into several different types as
follows:
21
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
(a) (b)
(c)
22
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
1.1.2 Plunger type relay: The other type is the piston or solenoid relay,
illustrated in Figure 2, in which α bar or piston is attracted axially within the
field of the solenoid. In this case, the piston also carries the operating
contacts. This called plunger type relay.
It can be shown that the force of attraction is equal to K 1I2 - K2, where
Κ1 depends upon the number of turns on the operating solenoid, the
air gap, the effective area and the reluctance of the magnetic circuit,
among other factors. K2 is the restraining force, usually produced by a
spring. When the relay is balanced, the resultant force is zero and
therefore Κ112 = K2, so that :
I K 2 / K1 constant.
23
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
Hence F (t ) k
2
Where k is constant
N 2i 2 N2
k 2 k1i 2 , k1 k l 2
lg g
I = RMS value of i
24
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
In order to control the value at which the relay starts to operate, the
restraining tension of the spring or the resistance of the solenoid
circuit can be varied, thus modifying the restricting force. Attraction
relays effectively have no time delay and, for that reason, are widely
used when instantaneous operations are required.
Example :
An electromagnetic relay of attracted armature type has constants
k1 0.6 and k 2 10 find whether the relay will operate or not
when:
(a) A current of 4A flows through the relay winding.
(b) A current of 5A flows through the relay winding.
(c) Find the minimum current required to operate the relay.
Solution:
(a) For 4A current:
Fn (t ) k1 I 2 k 2 0.6(4) 2 10 0.4 N
Fn (t ) k1 I 2 k 2 0.6(5) 2 10 15 10 5N
25
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
k2 10
or I 4.08 A
k1 0.6
The two magnets of the induction type relay produce two alternating
magnetic fields 1 & 2 :
26
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
1 1m sin t
2 2m sin(t )
where 2 leads 1 by an angle .
1 & 2 produce eddy currents in the rotating disc which are i φ1 and iφ2
d 1
i 1
dt
d 2
i 2
dt
or
i11m cos t
i 22m cos(t )
27
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
T FrF
or
T K11m 2 m sin
T1 2 sin
In terms of currents:
TI 1 I 2 sin
or
T K t I 1 I 2 sin
28
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
Plug settings
The operation is similar to the induction disc; here, two fluxes at right angles
induce eddy currents in a bell-shaped cup which rotates and carries the
moving contacts. A four-pole relay is shown in Figure 7.
29
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
Note that the main coils has TAPS, this means that the
number of turns is actually adjustable.
In the electromagnetic induction principle, the relay element has a non-
magnetic rotor (an aluminum or copper disc or cylinder) in which coils
create magnetic fluxes that induce circulating currents. The interaction
between the fluxes and the circulating currents generates torque. This is the
operation principle of induction motors.
If the current is sinusoidal and the iron core is assumed to have a linear
behavior, the magnetic field and the magnetic flux in the iron core are
sinusoidal too. Note that the flux is divided in two parts. One flows through
the normal (‘pole”) and the other flows through the shaded pole. These two
fluxes are similar in magnitude but different in angle.
Features of the Induction Principle
� Suitable for AC Systems
� The Torque Does Not Vary With Time: No Vibration
� Inherent Rejection of DC Offset: Low Overreach
31
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
Fig.9 . Small overcurrent relay and the circuit board for a simple static relay.
31
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
R
Relay
CT
Rectifier
C
Fig.1
32
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
3. Computerized Relay
3.1. Digital relays
� Research Began in the 1960’s
� Basic Developments: Early 1970’s
� A Technical and Economic Solution:
the Microprocessor
� Commercial Relays: Early 1980
A digital protective relay is a microcomputer controlled relay. The data
acquisition system collects the transducers information and converts it to the
proper form for use by the microcomputer. Information from CT and PT and
other systems is amplified and sampled at several kHz. The sampled signals
are digitized with A/D converter and fed to registers in microprocessor
system. The microprocessor may use some kind of counting technique, or
use the Discrete Fourier Transform (DFT) to compare the information with
preset limits for overcurrent , over/under voltage…etc, and then send
command through D/A converter to alarm or trip signals to the circuit
breakers.
33
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
Operation :
Fig.11
34
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
After the currents and voltages are reduced to acceptable levels by the
instrument transformers, the signals are filtered with an analog filter
The signal then digitized and re-filtered with a digital filter.
Numerical operating quantities are then calculated from the processed
waveforms.
Fig.12
35
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
36
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
37
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
38
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
39
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
Other Features :
The relay has some form of advanced event recording. The event
recording would include some means for the user to see the timing of
key logic decisions, relay I/O (input/output) changes, and see in an
oscillographic fashion at least the fundamental frequency component
of the incoming AC waveform.
The relay has an extensive collection of settings, beyond what can be
entered via front panel knobs and dials, and these settings are
transferred to the relay via an interface with a PC (personal computer),
and this same PC interface is used to collect event reports from the
relay.
The more modern versions of the digital relay will contain advanced
metering and communication protocol ports, allowing the relay to
become a focal point in a SCADA system.
41
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
� Low Cost
� Multifunctionality
� Protection and control
� Measurement
� Fault recording
� Communications capability
� Compatibility with Digital Integrated Systems
� High Reliability
� Relays (integration, self-testing)
� Protection system (supervised by the relays)
� Sensitivity and Selectivity
� New Protection Principles
� New Relay Operating Characteristics
� Maintenance-Free
� Reduced Burden on CTs and VTs
� Adaptive Protection
41
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
The distinction between digital and numerical relay rests on points of fine
technical detail, and is rarely found in areas other than Protection. They can
be viewed as natural developments of digital relays as a result of advances in
technology. Typically, they use a specialized digital signal processor (DSP)
as the computational hardware, together with the associated software tools.
I1 U
1 numerically the measurement
value is converted into a
D
000101001001
A logical digit and then
compared with another digit
setting value stored 000101001011
in EEPROM stored in a memory
meas. current 1,05 A
no pick-up
setting value 1,10 A
42
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
Mode of operation
Analog Inputs
Analog-Digital-Conversion
What did the current and voltage signals look like (CT
saturation) ?
43
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
Electromagnetic vs Computerized
44
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
45
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
52 - AC Circuit Breaker
53 - Exciter or DC Generator Relay
54 - High-Speed DC Circuit Breaker
55 - Power Factor Relay
56 - Field Application Relay
59 - Overvoltage Relay
60 - Voltage or Current Balance Relay
61 - Machine Split Phase Current Balance
62 - Time-Delay Stopping or Opening Relay
63 - Pressure Switch
64 - Ground Detector Relay
65 - Governor
66 - Starts per Hour
67 - AC Directional Overcurrent Relay
68 - Blocking Relay
69 - Permissive Control Device
71 - Level Switch
72 - DC Circuit Breaker
74 - Alarm Relay
75 - Position Changing Mechanism
76 - DC Overcurrent Relay
78 - Phase-Angle Measuring or Out-of-Step Protective Relay
79 - AC-Reclosing Relay
81 - Frequency Relay
83 - Automatic Selective Control or Transfer Relay
84 - Operating Mechanism
85 - Carrier or Pilot-Wire Receiver Relay
86 - Lockout Relay
87 - Differential Protective Relay
89 - Line Switch
90 - Regulating Device
91 - Voltage Directional Relay
92 - Voltage and Power Directional Relay
94 - Tripping or Trip-Free Relay
95 - Reluctance Torque Synchrocheck
96 - Autoloading Relay
46
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq
protection
Impedance protection
protection
protection
underfrequency protection
47