Power System Protection Schemes
Power System Protection Schemes
POWER SYSTEM
PROTECTION SCHEMES
Afroz Alam
Assistant Professor
Department of Electrical Engineering
AMU, Aligarh
Generator Protection
Components of a Power Plant
Introduction
In a generating station, the generator and transformer are
the most expensive equipments.
It is desirable to employ a protective system to isolate the
faulty equipment as quickly as possible to keep the
healthy section in normal operation and to ensure
uninterrupted power supply.
The basic electrical quantities which are likely to
change during abnormal fault conditions are current,
voltage, phase angle and frequency .
Protective relays utilizes one or more of these quantities
to detect abnormal conditions in a power system.
Stator protection
Stator faults include the following:
Phase-to-earth faults
Phase-to-phase faults
Inter-turn faults
Phase faults and inter-turn faults are less common.
These usually develop into an earth fault. This causes,
• Arcing to core
• Damage of conductor and insulation
Differential Protection of Generator
Differential Protection of Generator (Contd.)
CTs are provided at each end of the generator
winding which is to be protected.
When there is no any fault, the differential current
(I1-I2) through the relay is zero. So the relay will
not operate.
When the fault occurs, the balance is disturbed and
differential current (I1-I2) flows through the
operating coil of the relay causing relay operation
and the trip circuit of the circuit breaker is closed.
Biased Differential Protection
Due to the difference in the magnetising currents of the
CTs on the two sides of the generator, the current through
the operating coil will not be zero even under normal
operating conditions or during external fault conditions.
To provide stability on external faults, bias coils
(restraining coils) are provided.
The relay is set to operate, not at a definite current but at
a certain percentage of the through current.
To obtain the required amount of biasing, a suitable ratio
of the restraining coil turns to operating coil turns is
provided.
Biased Differential Protection (Contd.)
Modified Differential Protection
Generally, protection is made for 80 to 85% of the
winding.
If any fault occurs near the neutral point then the fault
current is very small and relay does not operate.
Modified differential protection scheme is used to
overcome this.
Two phase elements (PC and PA) and balancing
resistor (BR) is connected in star and the earth
relay (ER) is connected between the star point and
neutral pilot wire.
Modified Differential Protection (Contd.)
Restricted or Balanced Earth Fault
Protection
In case of small size generators, star point is not
available because it is made inside the generator
and grounded through some low resistance, then
percentage differential relay for ground fault is
provided and is known as restricted earth fault
protection.
This scheme can be used only for ground faults but
not for phase faults.
Restricted or Balanced Earth Fault
Protection (Contd.)
Stator Inter-turn Fault Protection
Inter-turn fault on the same phase of the stator
winding cannot be detected by differential
protection as it does not disturb the balance
between the currents in neutral and high voltage
CTs.
For protection against inter-turn faults, the
following protection schemes are used.
(1) Cross differential protection.
(2) Residual voltage protection.
Cross Differential Protection
Cross Differential Protection
(Contd.)
Used in case of hydroelectric generator having
double winding armature.
As shown in figure on the previous slide, relay Rc
provides protection against phase to ground and
phase to phase fault.
The relay R1 provides protection against inter-turn
faults.
Residual voltage protection
Residual voltage protection (Contd.)
This method is used in case of alternators not
having parallel stator windings.
During normal operations,
VRES=VRN+VBN+VYN = 0.
In case of fault, VRES is not equal to zero and this
residual voltage operates the relay.
Rotor faults
Faults in the rotor circuit may be either earth faults
or between the turns of the field winding .
Field circuits are normally operated un-earthed. So
a single earth fault will not affect its operation. But
when a second fault arises then field winding is
short circuited and produces unsymmetrical field
system which leads to unbalanced forces on rotor
and results in excess pressure and bearing and shaft
distortion.
Rotor Earth Fault Protection
The rotor earth fault protection is done by “dc
injection method or ac injection method”.
The dc or ac voltage is impressed between the field
circuit and ground through a sensitive overvoltage
relay and current limiting resistor or capacitor(in
case of ac).
But dc source is generally used as over-current
relay in case of dc which is more sensitive than ac.
A single earth fault in rotor circuit will complete
the path and the fault is sensed by the relay.
Rotor Earth Fault Protection
(Contd.)
Rotor Temperature Alarm
Rotor Temperature Alarm (Contd.)
It is provided in large generators.
It indicates the level of temperature.
The relay measures the temperature by measuring
the resistance.(as shown in the figure of the
previous slide)
Loss of Excitation Protection
When the excitation of generator is lost it operate
as an Induction generator.
It derives excitation from the system and supply
power at leading power factor, which may cause:
(1) A fall in voltage & so loss of synchronism &
system instability.
(2) Over heating of rotor due to induction current
on it.
A protection having MHO characteristic is used to
detect loss of field.
Over Voltage Protection
Over voltage may be caused due to ;
(1) Transient over voltage in the transmission line due to
lightening.
(2) Defective operation of the voltage regulator.
(3) Sudden loss of load due to line tripping.
The protection is provided with an over voltage relay. It
is usually of induction pattern with an IDMT
Characteristic.
Overload Protection
Overloading of the machine causes overheating in
the stator winding.
This can be prevented by using over-current relay
with time delay adjustment.
Overheating not only depends on over-current but
also on the failure of the cooling system in the
generator.
So, temperature detector coils such as thermistors
or thermocouples are used at various points in
stator winding for indication of the temperature.
Reverse Power Protection
When prime-mover fails machine starts motoring
and draws electrical power from the system and
this is known as inverted operation .
The generator can be protected from inverted
operation by using single-element directional
power relay (reverse power relay) which senses the
direction of power flow.
Negative Phase Sequence Protection
Unbalance may cause due to single phase fault or
unbalanced loading and it gives rise to negative
sequence current .
This current in rotor causes rotor overheating and
damage to the rotor.
This can be protected by negative sequence current
filter with over current relay.
Negative Phase Sequence
Protection (Contd.)
Protection of Power
Transformer
Differential Protection Scheme
Φ = K E/f
Where
Φ = flux E = applied voltage
f = frequency K is a constant.
In case of radially fed 220 kV substations, having more than one bus, it
is desirable to have bus bar protection but is not a must.
Differential Relay Principle
Bus bar protection relays work on the differential principle i.e.
comparing the currents entering and leaving a protected object.
If those currents matches, the protected object is assumed to be in
healthy condition and relay remains stable (non operating) . If there is a
difference in magnitude of currents, it is assumed that there is some
internal fault and the differential relay operates.
C.T C.T
Protected object
Differential
Relay
Differential Protection of Bus Bar
Differential Protection of Bus Bar (Contd.)
The bus bar is fed by a generator and supplies load
to two lines.
Secondaries of CT in the generator lead, in line 1 &
2 are all connected in parallel.
The protective relay is connected across this
parallel connection.
When a fault occurs, the fault current upsets the
balance and produces a differential current to
operate the relay.
Differential Protection of Bus Bar (Contd.)
Simple Current Differential Circuit with Bus Fault
Simple Current Differential Circuit with Close in Line Fault
Typical Instantaneous Over-current Relay
Single Bus Bar Protection (Healthy condition)
Current
entering
the bus
S P2
2 BUSBAR
ZONE
S P1
1
87 Busbar
S P1
1
P2
S P2
2 BUSBAR
ZONE
S P1
1
Busbar
87
S P1
1
P2
S
2
K
BUSBAR
ZONE
Relay
(R) 87
B C
A D
Here, in the figure above we assume that at normal condition feed, A, B, C & D carry
currents IA, IB, IC and ID . Now, according to Kirchhoff's current law, at node K, IA +
IB+ IC+ID = 0
So, it is clear that under normal condition there is no current flowing through the bus
bar protection tripping relay.
Now, say fault is occurred at any of the feeders, outside the protected zone. In that
case, the faulty current will pass through primary of the CT of that feeder. This fault
current is contributed by all other feeders connected to the bus. So, contributed part of
fault current flows through the corresponding CT of respective feeder. Hence at that
faulty condition, if we apply KCL at node K, we will still get, iR = 0.
Single Bus Bar Protection Scheme (Contd.)
Double bus system consists of two number of buses (Bus1 & Bus2 ) separated
by a bus coupler.
Double Bus Bar Protection Scheme
(explained step-by-step)
Bus #1 Bus #2
87-1
87-2
Bus
Coupler
Bus bar Bus bar
Protection Open Protection
Relay Bus-1 Relay Bus-2
100 A 100 A
T/F #1 T/F #2
Two number of bus bar protection relays are required for protection of the double bus system,
one for each bus. The relays will remain stable as long as the bus coupler CB is open.
Bus coupler closed condition
Feeder #1 200 A Feeder #2
Feeder #2 CB
open
Bus #1 Bus #2
87-1
87-2
100 A Bus
Coupler
Bus bar closed Bus bar
Protection Protection
Relay Bus-1 Relay Bus-2
100 A
100 A
T/F #1 T/F #2
When bus coupler CB is closed and feeder #2 is in switched-off condition, all the load current is
coming through feeder #1. There will be unbalance current in the relays and both relays will
operate. Hence, the bus coupler shall also be included in the protection scheme.
Bus Coupler CTs
Feeder #1 200 A Feeder #2
Feeder #2 CB
open
T/F #1 T/F #2
When the bus coupler bay is included in the bus bar protection scheme, the
relays will remain stable during normal condition and external fault.
Fault at bus coupler
Feeder #1 Feeder #2
Bus bar
Bus bar
Protection
Protection
Relay fault Relay
100 A Bus-2
Bus-1
T/F #1 T/F #2
In case of a fault in bus bar, heavy fault current flows but bus coupler CB is not covered by any bus bar
protection zones. So the bus bar protection relays will not operate. So the scheme needs modification.
Overlapping of Zones
Feeder #1 Feeder #2
Bus
Bus #1 Coupler Bus #2
87-1
87-2
T/F #2
T/F #1
Now the protection zones of Bus-1 and Bus-2 overlaps to include the bus
coupler CB, So both relays operates for a fault in the bus coupler bay.
Check Zone Relay
Check Relay
Protection Zone
Bus #1 Bus #2
87- 87-1 87-2
CH Bus
Coupler
The figure above shows double bus bar protection scheme with a check zone relay.
Check Zone Relay (Contd.)
For a double bus bar arrangement, two different high
impedance units are required. In this case, the current must be
switched between the two different measuring units by
connecting auxiliary switches to the bus bar isolator contacts.
In some cases the auxiliary switches do not operate correctly.
This causes the bus bar protection to trip the bus bar. For this
reason, a safety precaution is introduced.
Check zone is a safety precaution to avoid tripping of bus bars
due to defective CT switching relays.
Unit schemes
Non-unit schemes
Unit Type Protection Schemes
Unit Type Protection Schemes
Unit type schemes protect a specific area of the system,
i.e., a transformer, transmission line, generator or busbar.
The most obvious example of unit protection schemes is
based on Kirchhoff's current law – the sum of the
currents entering an area of the system must be zero.
Any deviation from this must indicate an abnormal
current path.
In these schemes, the effects of any disturbance or
abnormal operating condition outside the area of interest
are totally ignored and the protection must be designed
to be stable above the maximum possible fault current
that could flow through the protected area.
Non Unit Type Protection Schemes
Non Unit Type Protection Schemes
The non-unit schemes are also intended to protect
specific areas but have no fixed boundaries.
Apart from protecting their own designated areas, the
protective zones can overlap into other areas.
While this can be very beneficial for backup purposes,
there can be a tendency for too great area to be isolated if
a fault is detected by different non unit schemes.
The most simple of these schemes measures current and
incorporates an inverse time characteristic into the
protection operation to allow protection nearer to the
fault to operate first.
Non Unit Type Protection Schemes (Contd.)
The non unit type protection system includes the
following schemes:
- Time graded over current protection
- Current graded over current protection
- Distance or Impedance Protection
Time Graded Protection
This is a scheme of over current protection in
which time discrimination is incorporated. In other
words, the time setting of the relays is so graded
that minimum possible part of system is isolated in
the event of fault.
We will discuss the application of the time graded
protection on
- Radial feeder
- Parallel feeder
- Ring main feeder
Protection Of Radial Feeder
The main characteristic of the radial feeder is that
power can flow in one direction only from
generator to supply end of the load line.
In radial feeder, number of feeders can be
connected in series and it is desired that smallest
part of the system should be off in the event of
fault.
This is achieved by time graded protection.
In this system, time setting of a relay is so adjusted
that farther the relay from the generating system,
lesser the time of operation.
Time Graded Protection Of Radial Feeder
Drawbacks Of Time Graded Protection On Radial Feeder
Basic Principle
The basic principle of distance protection involves the
division of the voltage at the relaying point by the
measured current.
The apparent impedance so calculated is compared with
the reach point impedance.
If the measured impedance is less than the reach point
impedance, it is assumed that a fault exists on the line
between the relay and the reach point.
Basic Principle Of Operation Of Impedance Relay
Balanced Beam Principle Of Impedance Relay