Protection Coordination Report: Siemens India LTD
Protection Coordination Report: Siemens India LTD
Protection Coordination Report: Siemens India LTD
INS VALSURA
The short circuit currents at various busbars are calculated based on the above
assumptions. Calculated Short circuit currents are tabulated in the report and
also shown in the SLD.
Selectivity of relays and circuit breakers were worked out based on the cable size
and flow of short circuit currents.
Time current characterstic curves are generated for every path and verified .
Conclusion
Settings for each device,short circuit currents at every busbars,detailed
calculations for the settings are given in the following pages. No deviation is
observed and the interuupting capacities of the devices are above the calculated
short circuit currents .
Reference Documents/Drawings
Sl.No File ref Drawing title Drawing No
1 INS Valsura _cable sch MV&LV Power Cable Schedule G71101-H0825-P0001
2 MV LAB SLD - RZ OSLD SINGLE LINE DIAGRAM (2) G71001-H0825-S0001-Z
3 M-10-MCC PANEL_03_27.02.18 SITE CHANGES. 415 V SwitchBoard SSCSPL/2014-15/SPN046-1
4 Synch Panel SINGLE LINE DIAGRAM SYNC PANEL FOR 2 X 2500 kVA 6.6kV DG S301-10572
sets
5 RATING & DAIGRAM PLATE-R1 RATING & DIAGRAM PLATE 32RD1025
6 GTP-ADA2309014-R1 GUARANTEED TECHNICAL PARTICULARS ADA2309014
7 1502579_00_Technical Data and Drawings_REV_A_EN MACHINE DATA A5E39491727A-AF
8 1.6 tdps-2500kVA,6.6kV,ACG DATASHEET Alternator Data sheet TDM-25-0209
9 1.1 DATA SHEET-2000 KVA 6.6 KV RAD Genset Data Sheet
Device Details
2-Winding Transformers
Details of Equipment kVA rating High Low Percentag Low High Grounding Mode Vector Type of Supply Variation on Primary side
Voltage voltage e winding winding Group Cooling
side side Impedanc
DISTRIBUTION 500 6600 433 5.00 Star Delta DIRECT Dyn11 AN -5% to +5% tapping range
TRANSFORMER
CONVERTOR 1250 6600 3300 16.00 Delta Delta NA Dd AN -5% to +5% tapping range
TRANSFORMER
Gen1 Diesel 2.000 6.600 1500 80.00 122.8% 15.8% 11.9% 16.3% Wye
Gen2 Diesel 2.000 6.600 1500 80.00 122.8% 15.8% 11.9% 16.3% Wye
Cable Details
Cable Id Cable Material Length in met Size in Sq.mm No of runs per phase
C:ACO ENCL FAN1 DG1 Copper 20.0 2.5 1
C:ACO ENCL FAN1 DG2 Copper 20.0 2.5 1
C:ACO ENCL FAN2 DG1 Copper 20.0 2.5 1
C:ACO ENCL FAN2 DG2 Copper 20.0 2.5 1
C:ACO ENCL FAN3 DG1 Copper 20.0 2.5 1
C:ACO ENCL FAN3 DG2 Copper 20.0 2.5 1
C:ACO ENCL FAN4 DG1 Copper 20.0 2.5 1
C:ACO ENCL FAN4 DG2 Copper 20.0 2.5 1
C:CONVERT TRAFO Aluminum 15.0 240 1
C:CONVERT TRAFO LT Aluminum 55.0 240 2
C:COOLING FAN 1 _MTR1 Copper 45.0 2.5 1
C:COOLING FAN 1 _MTR2 Copper 50.0 2.5 1
C:COOLING FAN 2 _MTR1 Copper 45.0 2.5 1
C:COOLING FAN 2 _MTR2 Copper 50.0 2.5 1
C:COOLING UNIT FDR Aluminum 45.0 6 1
C:DC MTR PULLY LD Aluminum 30.0 6 1
C:DG AIR COMPRESSOR Aluminum 65.0 25 1
C:DIST TRAFO Aluminum 20.0 240 1
C:DIST TRAFO AUX SUPPLY Aluminum 40.0 6 1
C:DW PUMP Copper 50.0 2.5 1
C:EXT.PRE C FDR Aluminum 45.0 6 1
C:F W COOLING PUMP Copper 40.0 2.5 1
C:FAN FOR CT Copper 40.0 2.5 1
C:FAN1 FOR LOAD BANK Copper 45.0 6 1
C:FAN2 FOR LOAD BANK Copper 45.0 6 1
C:FAN3 FOR LOAD BANK Copper 45.0 6 1
C:FAN4 FOR LOAD BANK Aluminum 45.0 6 1
C:FAN5 FOR LOAD BANK Aluminum 45.0 6 1
C:FAN6 FOR LOAD BANK Aluminum 45.0 6 1
C:FUEL SUPP PUMP 1 TO BF Copper 40.0 2.5 1
C:FUEL SUPP PUMP 2 TO BF Copper 40.0 2.5 1
C:FUEL SUPPLY PUMP 1 Copper 55.0 2.5 1
C:FUEL SUPPLY PUMP 2 Copper 55.0 2.5 1
C:GEN1 Aluminum 20.0 240 1
C:GEN2 Aluminum 20.0 240 1
C:IND MTR PULLY LD Aluminum 30.0 6 1
C:JO PUMP DE _MTR1 Copper 45.0 2.5 1
C:JO PUMP DE _MTR2 Copper 50.0 2.5 1
C:JO PUMP NDE _MTR1 Copper 45.0 2.5 1
C:JO PUMP NDE _MTR2 Copper 50.0 2.5 1
C:LIGHTING Copper 10.0 2.5 1
C:LOAD BANK 1 Aluminum 30.0 35 1
C:LOAD BANK 2 Aluminum 30.0 35 1
C:LOAD BANK 3 Aluminum 30.0 35 1
C:LOAD BANK 4 Aluminum 30.0 35 1
C:LOAD BANK 5 Aluminum 30.0 35 1
C:LOAD BANK 6 Aluminum 30.0 35 1
C:MTR1 Aluminum 15.0 240 4
C:MTR2 Aluminum 20.0 240 1
C:NORMAL WATER PUMP1 Copper 45.0 2.5 1
C:P&V 1 Aluminum 40.0 6 1
Cable Details
Cable Id Cable Material Length in met Size in Sq.mm No of runs per phase
C:P&V 2 Aluminum 40.0 6 1
C:PDB F.FLOOR Aluminum 80.0 10 1
C:PDB G.FLOOR Aluminum 70.0 10 1
C:PDB SHED AREA Copper 40.0 2.5 1
C:PUMP FOR FNTN Copper 50.0 2.5 1
C:SH Copper 10.0 2.5 1
C:SYNC MTR PULLY LD Aluminum 30.0 6 1
C:T11 LT Aluminum 15.0 240 4
Motor Load Data
Description Load Rating in kW Voltage in PF in %
kV
Mtr1 Motor 5000.00 3.300 93.15
Mtr2 Motor 5000.00 3.300 93.15
ACO ENCL FAN1 DG1 Motor 2.20 0.415 83.63
ACO ENCL FAN1 DG2 Motor 2.20 0.415 83.63
ACO ENCL FAN2 DG1 Motor 2.20 0.415 83.63
ACO ENCL FAN2 DG2 Motor 2.20 0.415 83.63
ACO ENCL FAN3 DG1 Motor 2.20 0.415 83.63
ACO ENCL FAN3 DG2 Motor 2.20 0.415 83.63
ACO ENCL FAN4 DG1 Motor 2.20 0.415 83.63
ACO ENCL FAN4 DG2 Motor 2.20 0.415 83.63
COOLING FAN 1 _MTR1 Motor 3.00 0.415 84.37
COOLING FAN 1 _MTR2 Motor 3.00 0.415 84.37
COOLING FAN 2 _MTR1 Motor 3.00 0.415 84.37
COOLING FAN 2 _MTR2 Motor 3.00 0.415 84.37
F W COOLING PUMP Motor 5.50 0.415 85.82
FAN FOR CT Motor 3.70 0.415 84.87
FAN1 FOR LOAD BANK Motor 0.37 0.415 79.37
FAN2 FOR LOAD BANK Motor 3.70 0.415 84.87
FAN3 FOR LOAD BANK Motor 3.70 0.415 84.87
FAN4 FOR LOAD BANK Motor 11.00 0.415 87.47
FAN5 FOR LOAD BANK Motor 11.00 0.415 87.47
FAN6 FOR LOAD BANK Motor 11.00 0.415 87.47
FUEL SUPPLY PUMP 1 TO BF Motor 1.50 0.415 82.71
FUEL SUPPLY PUMP 2 TO BF Motor 1.50 0.415 82.71
FUEL SUPPLY PUMP 1 TO HSD Motor 0.37 0.415 79.37
FUEL SUPPLY PUMP 2 TO HSD Motor 0.37 0.415 79.37
JO PUMP DE _MTR1 Motor 0.75 0.415 81.06
JO PUMP DE _MTR2 Motor 0.75 0.415 81.06
JO PUMP NDE _MTR1 Motor 0.75 0.415 81.06
JO PUMP NDE _MTR2 Motor 0.75 0.415 81.06
NORMAL WATER PUMP1 Motor 3.70 0.415 84.87
P&V 1 Motor 11.00 0.415 87.47
P&V 2 Motor 3.00 0.415 84.37
Lumped Load Details
Description Load Rating in kVA Voltage in Load Current in
kV Amps
COOLING UNIT FDR Lumped Load 10.5 0.415 14.61
DC MTR PULLY LD Lumped Load 15.0 0.415 20.87
DG AIR COMPRESSOR Lumped Load 15.0 0.415 20.87
DIST TRAFO AUX SUPPLY Lumped Load 10.0 0.415 13.91
DW PUMP Lumped Load 5.0 0.415 6.96
EXT.PRE CHARGING FDR Lumped Load 9.0 0.415 12.52
IND MTR PULLY LD Lumped Load 15.0 0.415 20.87
PDB F.FLOOR Lumped Load 10.0 0.415 13.91
PDB G.FLOOR Lumped Load 10.0 0.415 13.91
PDB SHED AREA Lumped Load 10.0 0.415 13.91
PUMP FOR FOUNTAIN Lumped Load 3.0 0.415 4.17
SYNC MTR PULLY LD Lumped Load 15.0 0.415 20.87
SIEMENS INDIA LTD
INS VALSURA
N:GEN 1
N:GEN 2
C:GEN2
C:GEN1
LO5-MVSB_IC1 LO9-MVSB_IC2
R
R
MVSB-RHS
LO7-MVSB_BC
MVSB-LHS 6.6 kV
L13-MVSB-F8
6.6 kV CB6
L10-MVSB-F5 L12-MVSB-F7
L11-MVSB-F6
Open
LO3-MVSB-F3 LO4-MVSB-F4
LO2-MVSB-F2
LO1-MVSB-F1 CONT-F8
CONT-F7
CONT-F2 CONT-F3 CONT-F4 CONT-F6
R R
N:SPARE
N:T12 HT
N:T11 HT N:LOAD BANK 1 N:LOAD BANK 2 N:LOAD BANK 3 N:LOAD BANK 4 N:LOAD BANK 5 N:LOAD BANK 6
T12
DIST TRAFO T11
1250 kVA
500 kVA
LOAD BANK 1 LOAD BANK 2 LOAD BANK 3 LOAD BANK 5 LOAD BANK 6
LOAD BANK 4
N:T12 LT
N:T11 LT 200 kVA 500 kVA 500 kVA 200 kVA 100 kVA
500 kVA
C:T11 LT
N:COS
COS
LT SB-F32-1 LT SB-F33-1
Bus13-1
CONTROL CKTS
Bus13
C:COOLING FAN 2 _MTR1 C:COOLING FAN 1 _MTR2 C:COOLING FAN 2 _MTR2 C:JO PUMP DE _MTR1 C:JO PUMP NDE _MTR1 C:JO PUMP DE _MTR2 C:JO PUMP NDE _MTR2 C:ACO ENCL FAN1 DG1 C:ACO ENCL FAN2 DG1 C:ACO ENCL FAN3 DG1 C:ACO ENCL FAN4 DG1 C:ACO ENCL FAN1 DG2 C:ACO ENCL FAN2 DG2 C:ACO ENCL FAN3 DG2 C:ACO ENCL FAN4 DG2 C:FUEL SUPPLY PUMP 1 C:FUEL SUPPLY PUMP 2 C:FUEL SUPP PUMP 1 TO BF C:FUEL SUPP PUMP 2 TO BF C:NORMAL WATER PUMP1 C:FAN1 FOR LOAD BANK C:FAN2 FOR LOAD BANK C:FAN4 FOR LOAD BANK C:FAN5 FOR LOAD BANK C:FAN6 FOR LOAD BANK C:P&V 1 C:P&V 2 C:F W COOLING PUMP C:FAN FOR CT
C:FAN3 FOR LOAD BANK C:COOLING UNIT FDR C:DW PUMP C:DG AIR COMPRESSOR C:SYNC MTR PULLY LD C:DC MTR PULLY LD C:IND MTR PULLY LD C:PUMP FOR FNTN C:PDB SHED AREA C:PDB G.FLOOR C:PDB F.FLOOR C:DIST TRAFO AUX SUPPLY
C:COOLING FAN 1 _MTR1 C:EXT.PRE C FDR
C:SH C:LIGHTING
SYNC MTR PULLY LD IND MTR PULLY LD PUMP FOR FOUNTAIN PDB SHED AREA PDB F.FLOOR DIST TRAFO AUX SUPPLY
DW PUMP DG AIR COMPRESSOR DC MTR PULLY LD PDB G.FLOOR
COOLING FAN 1 _MTR2 COOLING FAN 2 _MTR2 JO PUMP DE _MTR1 JO PUMP NDE _MTR1 JO PUMP DE _MTR2 JO PUMP NDE _MTR2 ACO ENCL FAN1 DG1 ACO ENCL FAN2 DG1 ACO ENCL FAN3 DG1 ACO ENCL FAN4 DG1 ACO ENCL FAN2 DG2 ACO ENCL FAN3 DG2 ACO ENCL FAN4 DG2 FUEL SUPPLY PUMP 1 TO HSD FUEL SUPPLY PUMP 2 TO HSD FUEL SUPPLY PUMP 1 TO BF NORMAL WATER PUMP1 FAN1 FOR LOAD BANK FAN2 FOR LOAD BANK FAN5 FOR LOAD BANK FAN6 FOR LOAD BANK P&V 1 P&V 2 F W COOLING PUMP FAN FOR CT
COOLING FAN 2 _MTR1 ACO ENCL FAN1 DG2 FUEL SUPPLY PUMP 2 TO BF FAN3 FOR LOAD BANK FAN4 FOR LOAD BANK SPACE HEATERS LIGHTING EXT.PRE CHARGING FDR COOLING UNIT FDR 15 kVA 15 kVA 3 kVA 10 kVA 10 kVA 10 kVA
15 kVA 15 kVA 10 kVA
COOLING FAN 1 _MTR1 3 kW 3 kW 0.75 kW 0.75 kW 0.75 kW 0.75 kW 2.2 kW 2.2 kW 2.2 kW 2.2 kW 2.2 kW 2.2 kW 2.2 kW 0.37 kW 0.37 kW 1.5 kW 3.7 kW 0.37 kW 3.7 kW 11 kW 11 kW 11 kW 3 kW 5.5 kW 3.7 kW 5 kVA
3 kW 2.2 kW 1.5 kW 3.7 kW 11 kW 0 MVA 0 MVA 9 kVA 10.5 kVA
3 kW
C:CONVERT TRAFO LT
Bus12
Charger1
DC BUS
Inv1 Inv2
N:INV1 N:INV2
C:MTR1 C:MTR2
N:MTR2
N:MTR1
Mtr1 Mtr2
5000 kW 5000 kW
6.6 kV 0.433kV
CTHV:50/1 ACB LV:1000 A
0.5 MVA
Transformer capacity PT 500 kVA
Primary Voltage Vp 6.6 kV
Secondary Voltage Vs 0.433 kV
Transformer HV side CT details CTHV 50/1
Turns Ratio CTR1 50
Transformer LV ACB rating 1000
Percentage Impedance of Transformer Z 5.00%
Fault Current at 6.6 kV Bus 369 A
Fault current at 0.415 kV Bus as per report 4762.00 A
Transformer Full Load HV side Primary Current at 0% tapping Ipfl 500X 1000 )/ (1.732 Amps
X6.6x1000x1)
Transformer Full Load HV side Primary Current at -0% tapping 43.74 Amps
43.74 Amps
Transformer HV side CT Secondary Full Load Current Isfl 0.87
Measuring Tolerence 10.00 %
Relay reset tolerance 5.00 %
Transformer HV side Primary current setting 43.74x 1.10/0.95 Amps
IDMT setting at 33 kV side 50.65
CT secondary Current to the above 1.01
Setting proposed Ip 1
Curve Extreme Inverse
Transformer Full Load LV side Primary Current Ipfl 500 X 1000 )/ (1.732 Amps
X0.433x1000)
666.71 Amps
Measuring Tolerence 10.00 %
Relay reset tolerance 5.00 %
Transformer LV side Primary current setting 275.56*1.10/0.95 Amps
771.98
Setting proposed Ip 0.8
Fault current at 0.415 kV Bus as per report 4762.00 Amps
HV side current due to fault at 6.6 kV bus 312.42 Amps
HV side CT Secondary current due to fault at 0.415 kV bus 6.25 Amps
HV side CT current due to fault at Transformer HV side 7.38 Amps
Setting REQUIRED for high set on HV side 8.12 X In
Setting proposed on HV side relay I>> 8.00 X In
Setting proposed on LV side relay I>> 4 x In
Setting Calculation for CONVERTOR Transformer
6.6 kV 3.3kV
CTHV:120/1
1.25 MVA
Transformer capacity PT 1250 kVA
Primary Voltage Vp 6.6 kV
Secondary Voltage Vs 3.3 kV
Transformer HV side CT details CTHV 120/1
Turns Ratio CTR1 120
Percentage Impedance of Transformer Z 6.25%
Fault Current at 6.6 kV Bus 369 A
Transformer Full Load HV side Primary Current at 0% tapping Ipfl 1250X 1000 )/ (1.732 Amps
X6.6x1000x1)
Transformer Full Load HV side Primary Current at -0% tapping 109.35 Amps
Relay reset ratio 0.95
Measuring Tolerence 10.00 %
Transformer HV side Primary current setting 109.35x 1.10/0.95 Amps
IDMT setting at 6.6 kV side 126.62
CT secondary Current to the above 1.06
Setting proposed Ip 1.05
Curve Extreme Inverse
Transformer Full Load LV side Primary Current Ipfl 1250 X 1000 )/ (1.732 Amps
X3.3
218.70 Amps
Relay reset ratio 0.95
Measuring Tolerence 10.00 %
Transformer LV side Primary current setting 218*1.10/0.95 Amps
253.23
Setting proposed on HV side relay I>> 2.50 X In
SIEMENS INDIA LTD
INS VALSURA
100 100
50 LT SB_IC 50
30 30
Gen1
10 10
5 5
Seconds
Seconds
3 3
1 1
.5 .5
.3 .3
.1 .1
DIST TRAFO T11
Inrush
.05 1600 kW
Gen1
.05
C:GEN1
1-3/C 240
LO5-MVSB_IC1
.03 .03
±
MVSB-LHS R:LO5-MVSB-IC1
LO2-MVSB-F2 LO3-MVSB-F3
LO1-MVSB-F1
±
CONT-F2 CONT-F3
R
R:LO1-MVSB-F1
C:T11 LT
4-3/C 240
COS
.01 LT SB_IC
LT SWITCH BOARD
.01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Amps X 10 MVSB-LHS (Nom. kV=6.6, Plot Ref. kV=6.6) ETAP Star 18.0.0C
100 100
50 50
30 30
R:LO5-MVSB-IC1 - N
OC1
10 10
5 LT SB_IC 5
Seconds
Seconds
3 R:LO1-MVSB-F1 - N 3
OC1
1 1
.5 .5
.3 .3
.1 .1
.05 1600 kW
Gen1
.05
C:GEN1
1-3/C 240
LO5-MVSB_IC1
.03 .03
±
MVSB-LHS R:LO5-MVSB-IC1
LO2-MVSB-F2 LO3-MVSB-F3
LO1-MVSB-F1
±
CONT-F2 CONT-F3
R
R:LO1-MVSB-F1
C:T11 LT
4-3/C 240
COS
.01 LT SB_IC
LT SWITCH BOARD
.01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Amps X 10 MVSB-LHS (Nom. kV=6.6, Plot Ref. kV=6.6) ETAP Star 18.0.0C
100 100
50 50
30 30
R:LO9-MVSB-IC2 - P
OC1
10 10
5 R:LO10-MVSB-F5 - P 5
Seconds
OC1
3 3
T12
1 1
.5 .5
.3 .3
.1 .1
1600 kW
Gen2
R
MVSB-RHS
.03
R:LO9-MVSB-IC2
L10-MVSB-F5
R:LO10-MVSB-F5
C:CONVERT TRAFO
1-3/C 240
T12
1250 kVA
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
100 100
50 50
30 30
10 10
5 5
Seconds
Seconds
3 3
R:LO9-MVSB-IC2 - N
1
OC1 1
.5 .5
.3 .3
.1
R:LO10-MVSB-F5 - N .1
OC1
1600 kW
Gen2
.05 .05
.03 ±
R
MVSB-RHS
.03
R:LO9-MVSB-IC2
L10-MVSB-F5
R:LO10-MVSB-F5
C:CONVERT TRAFO
1-3/C 240
T12
1250 kVA
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Amps X 10 MVSB-RHS (Nom. kV=6.6, Plot Ref. kV=6.6) ETAP Star 18.0.0C