Thrust Block Calculation For ф (90 DEGREE)
Thrust Block Calculation For ф (90 DEGREE)
Thrust Block Calculation For ф (90 DEGREE)
Where;
inputs:
Working Pressure P KN/m2
Angle of pipe bent ϴ degrees
area of 160 mm dia pipe a m2
allowable bearing pressure q 98.1 KN/m2
Thrust force T (2PaSin(ϴ/2)) 70 KN
NOTE : 1- Thrust block weight and soil friction are considered to be null wich is safer
2-Thrust block must totally backfilled
THRUST BLOCK CALCULATION FOR
110 mm ф PIPE (90 DEGREE)
(NEGLECTING THE FRICTION FORCES RESISTANCE)
Where;
inputs:
Working Pressure P 1650 KN/m2
Angle of pipe bent ϴ 90 degrees
area of 110 mm dia pipe a 0.0095 m2
allowable bearing pressure q 98.1 KN/m2
Thrust force T (2PaSin(ϴ/2)) 22.1677975902 KN
NOTE : 1- Thrust block weight and soil friction are considered to be null wich is safer
2-Thrust block must totally backfilled
THRUST BLOCK CALCULATION FOR
75 mm ф PIPE (90 DEGREE)
(NEGLECTING THE FRICTION FORCES RESISTANCE)
Where;
inputs:
Working Pressure P 1650 KN/m2
Angle of pipe bent ϴ 90 degrees
area of 75 mm dia pipe a 0.004417 m2
allowable bearing pressure q 98.1 KN/m2
Thrust force T (2PaSin(ϴ/2)) 10.3068591533 KN
NOTE : 1- Thrust block weight and soil friction are considered to be null wich is safer
2-Thrust block must totally backfilled
THRUST BLOCK CALCULATION FOR
160 mm ф (90 DEGREE)
(NEGLECTING THE FRICTION FORCES RESISTANCE)
Where;
inputs:
Working Pressure P 1650 KN/m2
Angle of pipe bent ϴ 90 degrees
area of 160 mm dia pipe a 0.0201 m2
allowable bearing pressure q 98.1 KN/m2
Thrust force T (2PaSin(ϴ/2)) 46.9023927961 KN
NOTE : 1- Thrust block weight and soil friction are considered to be null wich is safer
2-Thrust block must totally backfilled
THRUST BLOCK CALCULATION FOR
160 + 2x110 mm ф (90 DEGREE)
(NEGLECTING THE FRICTION FORCES RESISTANCE)
Where;
inputs:
Working Pressure P KN/m2
Angle of pipe bent ϴ degrees
area of 160 mm dia pipe a m2
allowable bearing pressure q 98.1 KN/m2
Thrust force T (2PaSin(ϴ/2)) 92 KN
NOTE : 1- Thrust block weight and soil friction are considered to be null wich is safer
2-Thrust block must totally backfilled