Load Calculation
Load Calculation
LPMTI
Load
I
C.B. Size
C.B. Size
11375
VA 100%
= 29.85
== 5337.3
/ 0.8 Amps
= 66
= 53
50 /A0.8 = 66
3ph
Cable
= 44x16
X 25mm2
mm, 16 10mm2
mm G G
L
15
VD/A/L
FOR 4X10mm2
3.35
VD
3.35X25.22X15
VD%
3.35X25.22X15
1.267=0.5%
LPMT2
Lighting Load
= 8500 VA
Other Load
= 36220 VA
1st.10,000 100%
Remaining:26220x0.4= 10488
10448VA
VA
_ _ _ _ _ _ _ _ _ (1)
Total Demand
I
C.B. Size
= 6900 VA 100%
= VA /3 V
=
18.1 Amps
= 53
30 /A0.8 = 66 3ph
Cable
= 44x6
X 25
mm2
mm, 16 6mm2
mm GG
L
15
VD/A/L
FOR 4X6mm2
3.35
VD
3.35X25.22X15
VD%
3.35X25.22X15
1.267=0.5%
_ _ _ _ _ _ _ _ _ (1)
PP1
Total outlet Load
1st.10,000 100%
Remaining 0.4
Total Demand
I
C.B. Size
Cable
= 36000 VA
= 10000 VA
= 10400 VA
= 20400 VA
= 30.9 Amps
= 50 A
== 4 x4 16mm
x 16mm , 10mm G
_ _ _ _ _ _ _ _ _ (1)
_ _ _ _ _ _ _ _ _ (2)
LPG
Lighting Load
Other Load
= 13700 VA 100%
= 8160 VA 100%
Total Demand
I
C.B. Size
Cable
21860 VA
= 33.2 Amp
= 33.2/0.8 = 41
=
50 A 3 Ph
= 4 x 16 mm, 10 mm G
LPM
Lighting Load
Other Load
1st.10,000 100%
Remaining x 0.4
= 18900 VA 100%
= 33000
=
10000 VA
=
9200 VA
Total Demand
= 1+2+3
= 18900+10000+9200
= 33184
57.88 Amps
C.B. Size
80 Amps
Cable
= 4 x 25 mm, 16 mm G
PPIV
= 121050
121090
= 183.9
_ _ _ _ _ _ _ _ _ (1)
_ _ _ _ _ _ _ _ _ (2)
_ _ _ _ _ _ _ _ _ (3)
C.B. Size
= 183.9/08
=
229
= 250 A 3 Ph
Cable
= 4 X 150 mm, 70 mm G
PP2V
= 50400
1
50400
C.B. Size
Cable
= 4 X 35 mm, 16 mm G
765 Amps
100 A
PPS
= 145970
1
145970
C.B. Size
Cable
= 4 X 240 mm, 70 mm G
221 Amps
300 A
LPS
Lighting Load
A/C Load
Other Load
Total Demand
= 22271 VA 100%
= 7000 VA 100%
=
2460 VA 100%
= 31720 VA
48 Amps
C.B. Size
80 A 3 Ph
Cable
= 4 X 25mm, 10 mm G
Voltage Drop
PPS --- LPS
I = 48 Amps
L
=
5 ms
Cable
4.16 mm
VDKM/A =
2.11
VD
0.45
VD% =
0.11%
1, 3, 5 --------- LPS
L
=
Cable
140ms
4.74 Amps
4 x 6 mm
3.64 V
0.90%
311ms
5.69 Amps
_ _ _ _ _ _ _ _ _ (1)
_ _ _ _ _ _ _ _ _ (2)
_ _ _ _ _ _ _ _ _ (3)
Cable
4 x 6 mm
9.72 V
2.5%
13, 15, 17
5.69 Amps
L
=
138 ms
Cable
4 x 6 mm
VDKM/A =
5.49
VD
7V
VD% =
19, 21, 23
I = 9.25 Amps
L
=
148 ms
VDKM/A = (4.10mm)
3.32
VD =
3.32 x 148/100 x 9.25
=
4.54011
VD% =
1.196
2, 4, 6
L
VD =
VD% =
130ms
VD/KM/I (4x6mm) = 5.49
3.41 Amps
3.41 x 130/1000 x 5.49 = 2.43
0.6%
8, 10, 12
L
VD =
VD% =
155ms
VD/KM/I (4x6mm) = 5.49
4.33 Amps
4.33 x 155/1000 x 5.49 = 3.68
0.96%
PPA/C
Total Connected Load
ACCU Load
=
AHU Fan Load
= 276000
160800 VA ---------(1)
3.75 KW X 4
Total Demand
C.B. Size
18750 VA ---------(2)
=
1+2
= 179550 VA
= 272.8 Amps
= 272.8/08 = 341
= 400 A
Bus Bar # 1
15 + 25 + 180 + 260 + 12
+ 34 + 8 + 40
= 574 KW
Demand Factor
Total Demand
= 344.4 KW
= 430.5 KW
= 654 A
C.B. Size
= 800 A
Cable
0.6
Bus Bar # 2
Demand Load
= 269.1 KW
= 336.375 KVA
= 511 A
I
Main C.B. Size
Cable
0.6
= 800 A
= 2 [4 X 300 mm, 120 mm G]
BB4
Demand Load
I
C.B. Size
Cable
0.6
312.75 KVA
= 475 A
= 800 A
= 2 [4 X 300 mm, 120 mm G]
BB5
Total Load
= 30 KW
=
=
37.5 KVA
56.9 Amps
= 100 A
= 4 x 35 mm, 16 mm G]
MDP1
Total Load
I
C.B. Size
= 136.7 Amps
= 1600 A
Transformer - 1
= 1000 KVA
= 34.5 KV - 380/220V
Primary Feeder
Fuse
1000000/34500 x 3
16.7 Amps
85 A
Cable
4 x 70mm, 25mm G
Secondary Feeder
= 1519.3 Amps
C.B. Size
Cable
1600 A
7 x 1C x 630mm, 120mm G
MDP2
Total Load
I
C.B. Size
= 1392 Amps
= 1600 A
Transformer - 2
= 1000 KVA
= 34.5 KV - 380/220V
Primary Feeder
=
1000,000/34.5 x 3
16.7 Amps
Fuse
85 A
Cable
4 x 70mm, 25mm G
Secondary Feeder
I
C.B. Size
Cable
= 1519.3 Amps
=
1600 A
7 x 1 x 630mm, 120mm G