DE28 Differential Pressure Transmitter: Block Schematic Diagram
DE28 Differential Pressure Transmitter: Block Schematic Diagram
DE28 Differential Pressure Transmitter: Block Schematic Diagram
com)
Email: india.eke@gmail.com
Mob: +91-9680966000
Application
Measuring Transmitter for overpressu-
re, partial vacuum and differential pres-
sure of liquid and aerial media. Ranges:
0-0.4 up to 0-6 bar. This series of trans-
mitter is suitable for various measuring
applications in the field of industrial and
sanitary techniques.
Typical applications:
Measurement of differential pres-
sure between forward and return
flow in heating systems
Monitoring of filters, blowers and
compressors
Specifications
General
Measuring ranges 0-0.4 0-0.6 0-1 0-1.6 0-2.5 0-4 0-6 bar
Nominal pressure 16 bar
Max. pressure load one-sided overpressure protected up to nominal pressure,
on (+) and (-) side of diaphragm, partial vacuum protected
Permissible ambient temperature 0 up to +70 C
Max. storage temperature 70 C
Protection class IP54 per DIN EN 60529
Linearity 2% FS
Hysteresis 1% FS
Electrical
Electrical connection 3-wire
Operating voltage 24 V DC / AC 24 V DC / AC
range 15...30 V DC range 15...30 V DC
20...30 V AC 20...28 V AC
Output signal 0...20 mA 0...10 V
4...20 mA
Load 380 for all 2K
operating voltages
Connections
Pressure connection female thread G 1/8
cutting ring connection (brass) for 6mm tube
cutting ring connection (brass) for 8mm tube
Electrical connection fixed numbered cable, prewired
Materials
Case material polycarbonate
Pressure chamber brass
Electrical Connection
7MKREP
Contact: EK Engineering (www.ekeindia.com)
Email: india.eke@gmail.com
Mob: +91-9680966000
Ordering Code
Measuring Range
0 ... 400 mbar ....................................................................> 8 3
0 ... 0.6 bar ....................................................................> 0 1
0 ... 1 bar ....................................................................> 0 2
0 ... 1.6 bar ....................................................................> 0 3
0 ... 2.5 bar ....................................................................> 0 4
0 ... 4 bar ....................................................................> 0 5
0 ... 6 bar ....................................................................> 0 6
Pressure Connection
Female thread G 1/8 ............................................................................... > 0 0
Cutting ring connection (brass) for 6mm tube ......................................... > 2 8
Cutting ring connection (brass) for 8mm tube ......................................... > 2 9
Electrical Connection
Numbered cable, 1m, prewired ................................................................................ > 1
Numbered cable, 2.5m, prewired ............................................................................. > 2
Numbered cable, 5m, prewired ................................................................................ > 5
Output Signal
0 - 20 mA linear, 3-wire connection.................................................................................. > A
4 - 20 mA linear, 3-wire connection.................................................................................. > P
0 - 10 V DC linear, 3-wire connection............................................................................... > C
Power supply
24 V DC / AC........................................................................................................................... > L
Technische Änderungen vorbehalten Subject to change without notice Changements techniques sous réserve
Fischer Mess- und Regeltechnik GmbH Bielefelder Str. 37a D-32107 Bad Salzuflen Tel. +49 5222 9740 Fax +49 5222 7170 eMail: info@fischermesstechnik.de www.fischermesstechnik.de