Tape Wound, Split Core and Ebony Current Transformers
Tape Wound, Split Core and Ebony Current Transformers
Tape Wound, Split Core and Ebony Current Transformers
Current Transformers
Current Transformers
Contents Page
www.crompton-instruments.com
Customer service 0870 870 7500
(Fax 0870 240 5287)
1
Tape Wound Measuring and
Protection Current Transformers
2
MR Series Measuring Range
A comprehensive range of measuring ring current
transformers for installation where reliability, accuracy
and quality are required.
Construction
High grade silicon iron cores are carefully selected, then insulated and protected
by a polypropylene covering on which the secondary winding is toroidally wound
by precision winding machines. Multi layers of polyester and PVC are then applied
to provide a tough moisture resistant coating.
Specifications
Applications
• Switchgear Loss in copper wires between instrument and CT for 5A secondary
• Control panels Wire section Loss in VA (for both wires)
• Overload protection in mm2 1m 2m 4m 6m 8m 10m
• Control devices 1.5 0.60 1.19 2.38 3.57 4.76 5.95
2.5 0.36 0.71 1.43 2.14 2.86 3.57
4 0.22 0.45 0.89 1.34 1.79 2.23
Dimensions 6 0.15 0.30 0.60 1.89 1.19 1.49
10 0.09 0.18 0.36 0.54 0.71 0.89
3
MR Series Measuring Range
MR transformers are used to accurately measure high
alternating primary currents, converting the primary current
into a proportional secondary current as required for
measurement and instrumentation. They are available in
5 amp or 1 amp secondary versions.
Part number Ratio range Class 3 Class 1 Class 0.5 A B C D Approx. weight
MR-28-40/5A 40/5 1.5 - - 28 70 40 77.5 0.5
MR-28-50/5A 50/5 2 - - 28 70 40 77.5 0.5
MR-28-60/5A 60/5 2.5 - - 28 70 40 77.5 0.5
4
PR Series Protection Range
IEC60044-1/BSEN60044-1 commonly define protection
current transformers in terms of composite error at an
accuracy limit factor. In simple terms this means how
accurate the current transformer will remain when the
primary current flowing is many times higher than in normal
conditions i.e. in a fault situation.
The classification of protection current transformers follows the following
simple formula:
“10 P 10”
Manufacturers of protection devices will normally specify the classification for the
protection current transformer intended to operate the particular protection
device concerned.
5
Class PX Current Transformers
In some balanced protection systems where sensitivity and
stability levels required are high, classes 5P10 or 10P10 may
not be adequate. In these situations a Class PX current
transformer will usually be specified. Class PX as defined in
IEC60044-1/BSEN60044-1 allows the manufacturer of a
protection device to detail more specific requirements of the
current transformer so as to achieve a more sensitive
protection scheme. Typically this will involve specifying the
following information for the current transformer:
1) Turns ratio 4) Maximum excitation current at the
2) Minimum kneepoint voltage rated minimum kneepoint voltage
3) Maximum secondary resistance
To enquire about Class PX current transformers consult the factory with the above
information together with any physical limiting dimensions and the aperture size
required. If not all the above information is available, details of relay type, lead run from
current transformer to relay and the fault current expected to flow through the zone
protected by the current transformers will be required in order to provide a quotation.
6
Split Core Current Transformers
7
SC Series Split Core Current
Transformers
A range of split core current transformers that offers a
cost effective and efficient method by which the current
can be measured without the need to break the
conductor, thereby reducing installation and
commissioning time.
Specifications
8
Product Codes
Part number Ratio Burden VA against class index Aperture (mm)
0.5 1 3
SC1-100/5A 100/5A - - 1.5 20 x 30
SC1-150/5A 150/5A - - 2 20 x 30
Case 1
9
3-in-1 Current Transformers
10
3-in-1 Current Transformers
A range of 3-in-1 current transformers combine three traditional
current transformers in one moulded case. 3-in-1 current
transformers can be directly installed next to a three-phase
moulded case circuit breaker, thus saving installation time where
fitting three standard individual current transformers would be
required. The M3N1 range of current transformers offers primary
currents between 60-630A with 5A secondaries with up to Class
0.5 accuracy performance.
Specifications
11
Ebony Moulded Case Current
Transformers
12
Ebony Series Current Transformers
The range of Crompton Instruments Ebony current
transformers offers wide system current ratings,
apertures, busbar and case sizes to suit every
application. Manufactured to meet EN60044
the range benefits include ratio rating from 1/5 to
6000/5, accuracy up to Class 0.5, integral terminal
cover for safety and multiple mounting options.
Construction
The toroidal core and secondary winding is encapsulated by a self-extinguishing
polycarbonate moulded case cover providing excellent mechanical strength and
electrical insulation. The material is halogen free thus reducing risk of halogen
emissions in case of fire. The integral covered secondary terminals offer protection to
IP20B and the enclosure is protected to IP40.
Features
• CT ratios from 1A to 6000A with
Installation Options
5A and 1A secondaries
• Plug-in metal feet for wall or base mounting
• Accuracy up to Class 0.5 • Plastic DIN-rail clips for DIN-rail mounting
• Integral terminal cover • Moulded busbar mounting
• Primary copper busbar mounting
• High impact, flame retardant
• Multi busbar mounting for two busbars
moulded case
• Busbar, DIN-rail or foot
mounting options Specifications
13
M53Q Range
Case Size: 45mm wide x 30mm deep x 65mm high
1.8" wide x 1.2" deep x 2.5" high
Aperture: 20 x 6mm and 21mm diameter
0.8" x 0.2" and 0.8" diameter
Weight: 0.25Kg
M53Q-50/5 50 1 -
M53Q-60/5 60 1.25 -
M53Q-75/5 75 1.5 -
M53Q-80/5 80 1.25 -
M53Q-100/5 100 2.5 1.5
M53Q-125/5 125 3 2.5
M53Q-150/5 150 3.75 2.5
M53Q-200/5 200 5 3.75
M53Q-250/5 250 - 5
M53Q-300/5 300 7.5 5
Ordering Codes
As above Change end suffix to depict required secondary.
For example: M53Q-50/1
M30-DINCLIP DIN-rail mounting clip for DIN-rail mounting option
(2 required)
• Mounting feet centres
26mm x 51mm
M55E Range
Case Size: 50mm wide x 50mm deep x 80mm high
2" wide x 2" deep x 3.1" high
Aperture: 15 x 5mm and 16 diameter
0.6" x 0.2" diameter
Weight: 0.4Kg
Ordering Codes
As above Change end suffix to depict required secondary.
For example: M55E-50/1
M50-DINCLIP (2 required)
Ordering Codes
As above Change end suffix to depict required secondary.
For example: M53J-150/1
M30-DINCLIP DIN-rail mounting clip for DIN-rail mounting option
(2 required)
M65F Range
Case Size: 60mm wide x 50mm deep x 94mm high
2.4" wide x 2" deep x 3.7" high
Aperture: 20 x 10mm and 23mm diameter
0.8" x 0.4", 0.9" diameter
Weight: 0.4Kg
Ordering Codes
As above Change end suffix to depict required secondary.
For example: M65F-150/1
• Mounting feet centres M50-DINCLIP DIN-rail mounting clip for DIN-rail mounting option
42mm x 71mm (2 required)
Ordering Codes
As above Change end suffix to depict required secondary.
For example: M53J-150/1
M30-DINCLIP DIN-rail mounting clip for DIN-rail mounting option
(2 required)
MA5G Range
Case Size: 77mm wide x 50mm deep x 116mm high
3" wide x 2" deep x 4.5" high
Aperture: 40 x 10mm, 30 x 30mm and 36mm diameter
1.6" x 0.4", 1.2" x 1.2" and 1.4" diameter
Weight: 0.6Kg
MA5G-750/5 750 15 10 10
MA5G-800/5 800 15 10 10
MA5G-1000/5 1000 20 15 15
71
Ordering Codes
As above Change end suffix to depict required secondary.
For example: MA5G-150/1 • Mounting feet centres
M50-DINCLIP DIN-rail mounting clip for DIN-rail mounting option 58.5mm x 71mm
(2 required)
• Mounting feet
Ordering Codes
centres As above Change end suffix to depict required secondary.
58.5mm x 71mm For example: MA5Y-1/1
M50-DINCLIP DIN-rail mounting clip for DIN-rail mounting option (2 required)
M93L Range
Case Size: 90mm wide x 30mm deep x 131mm high
3.5" wide x 1.2" deep x 5.1" high
Aperture: 50 x 10mm, 40 x 30mm and 42mm diameter
2" x 0.4", 1.5" x 1.2" and 1.6" diameter
Weight: 0.45Kg
Ordering Codes
As above Change end suffix to depict required secondary.
For example: M93L-1000/1
M30-DINCLIP DIN-rail mounting clip for DIN-rail mounting option (2 required)
M93R Range
Case Size: 90mm wide x 30mm deep x 131mm high
3.5" wide x 1.2" deep x 5.1" high
Aperture: 64 x 12.6mm, 60 x 30mm
2.5" x 0.5", 2.4" x 1.2"
Weight: 0.6Kg
Ordering Codes
As above Change end suffix to depict required secondary.
For example: M93R-1000/1
17 M30-DINCLIP DIN-rail mounting clip for DIN-rail mounting option (2 required)
M93S Range
Case Size: 90mm wide x 30mm deep x 131mm high
3.5" wide x 1.2" deep x 5.1" high
Aperture: 76.5 x 19mm, 60 x 30mm
3.0" x 0.7", 2.4" x 1.2"
Weight: 0.7Kg
Ordering Codes
As above Change end suffix to depict required secondary.
For example: M93S-1000/1
M30-DINCLIP DIN-rail mounting clip for DIN-rail mounting option (2 required)
S95P Range
Case Size: 90mm wide x 50mm deep x 144mm high
3.5" wide x 2" deep x 5.7" high
Weight: 0.9Kg - 1.11Kg
Ordering Codes
As above Change end suffix to depict required secondary.
For example: S95P-1/1
M50-DINCLIP DIN-rail mounting clip for DIN-rail mounting option (2 required)
• Mounting feet
centres
71.5mm x 71mm
S97P Range
Case Size: 90mm wide x 50mm deep x 144mm high
3.5" wide x 2" deep x 5.7" high
Weight: 0.9Kg - 1.11Kg
Ordering Codes
As above Change end suffix to depict required secondary. • Mounting feet
For example: S95P-1/1
centres
71.5mm x 91mm
Ordering Codes
As above Change end suffix to depict required secondary.
For example: MB5D-1600/1
MB5Z Range
Case Size: 134mm wide x 50mm deep x 156mm high
5.2" wide x 2" deep x 6.1" high
Aperture: 104 x 35mm, 35mm diameter
4" x 1.3" and 1.3" diameter
Weight: 0.7Kg
Ordering Codes
As above Change end suffix to depict required secondary.
For example: MB5Z-1600/1
• Mounting feet centres
105mm x 71mm
• Mounting hole centres
110mm x 6.6mm
Ordering Codes
As above Change end suffix to depict required secondary.
For example: MC5T-1600/1
MD5T Range
Case Size: 213mm wide x 50mm deep x 165mm high
8.3" wide x 2" deep x 6.5" high
Aperture: 160 x 50mm
6.3" x 2"
Weight: +/-1.5Kg
Ordering Codes
As above Change end suffix to depict required secondary.
For example: MD5T-1600/1
While TE Connectivity (TE) has made every reasonable effort to ensure the accuracy of the information in this catalogue, TE does not guarantee that it is error-free, nor does TE make any
Tyco Electronics UK Ltd CI-EPP-TAPE WOUND CT-10/11
other representation, warranty or guarantee that the information is accurate, correct, reliable or current. TE reserves the right to make any adjustments to the information contained herein at
any time without notice. TE expressly disclaims all implied warranties regarding the information contained herein, including, but not limited to, any implied warranties of merchantability or
fitness for a particular purpose. The dimensions in this catalogue are for reference purposes only and are subject to change without notice. Specifications are subject to change without notice.
Consult TE for the latest dimensions and design specifications. TE Connectivity and TE connectivity (logo) are trademarks. CROMPTON is a trademark of Crompton Parkinson Limited and is
used under licence. Other trademarks are property of their respective owners.
TE Energy – innovative and economical solutions for the electrical power industry: cable accessories, connectors & fittings,
insulators & insulation, surge arresters, switching equipment, street lighting, power measurement and control.
http://energy.te.com
www.crompton-instruments.com