Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Tape Wound, Split Core and Ebony Current Transformers

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

Tape Wound, Split Core and Ebony

Current Transformers
Current Transformers

Contents Page

Tape Wound Measuring


and Protection Current Transformers 2–6

Split Core Current Transformers 7–9

3-in-1 Current Transformers 10 - 11

Ebony Moulded Case


Current Transformers 12 - 20

Moulded Case Overview 21 - 22

www.crompton-instruments.com
Customer service 0870 870 7500
(Fax 0870 240 5287)

For orders via email cromptonorders@te.com

For general enquiries crompton.info@te.com

For technical enquiries cromptontechnical@te.com

1
Tape Wound Measuring and
Protection Current Transformers

2
MR Series Measuring Range
A comprehensive range of measuring ring current
transformers for installation where reliability, accuracy
and quality are required.

Construction
High grade silicon iron cores are carefully selected, then insulated and protected
by a polypropylene covering on which the secondary winding is toroidally wound
by precision winding machines. Multi layers of polyester and PVC are then applied
to provide a tough moisture resistant coating.

Specifications

System voltage: 720V maximum


Test voltage: 3kV for 1 minute
System frequency: 50/60Hz
Overload withstand: 1.2 x rated current continuously
Short circuit thermal 60 x rated primary current for 1 second
Features current (Ith)*:
• Available in a wide range of Dynamic current (Idyn)*: = 2.55 x Ith
transformer ratings Service temperature: -20°C to 70°C
• Accuracy up to Class 0.5 Secondary current: 5A or 1A
• Measuring or protective types Complies with: IEC60044-1, BSEN60044-1
Saturation coefficient: <6
Humidity: Up to 95% RH (non condensing)
Benefits Insulation class: BSEN60085 Class Y
• Long product life Mounting hardware: Foot mounted

Applications
• Switchgear Loss in copper wires between instrument and CT for 5A secondary
• Control panels Wire section Loss in VA (for both wires)
• Overload protection in mm2 1m 2m 4m 6m 8m 10m
• Control devices 1.5 0.60 1.19 2.38 3.57 4.76 5.95
2.5 0.36 0.71 1.43 2.14 2.86 3.57
4 0.22 0.45 0.89 1.34 1.79 2.23
Dimensions 6 0.15 0.30 0.60 1.89 1.19 1.49
10 0.09 0.18 0.36 0.54 0.71 0.89

Loss in copper wires between instrument and CT for 1A secondary


Wire section Loss in VA (for both wires)
in mm2 10m 20m 40m 60m 80m 100m
1 0.36 0.71 1.43 2.14 2.86 3.57
1.5 0.24 0.48 0.95 1.43 1.90 2.38
2.5 0.14 0.29 0.57 0.86 1.14 1.43
4 0.09 0.18 0.36 0.54 0.71 0.89
6 0.06 0.12 0.24 0.36 0.48 0.60
10 0.04 0.07 0.14 0.21 0.29 0.36

* Thermal current (Ith) & dynamic


current (ldyn).
lth is the highest primary current
(effective value), the ldyn is the highest
primary current (peak value) that the
CT can support for 1 second without
damage, owing to excessive overloads
with secondary short circuits.

3
MR Series Measuring Range
MR transformers are used to accurately measure high
alternating primary currents, converting the primary current
into a proportional secondary current as required for
measurement and instrumentation. They are available in
5 amp or 1 amp secondary versions.

Part number Ratio range Class 3 Class 1 Class 0.5 A B C D Approx. weight
MR-28-40/5A 40/5 1.5 - - 28 70 40 77.5 0.5
MR-28-50/5A 50/5 2 - - 28 70 40 77.5 0.5
MR-28-60/5A 60/5 2.5 - - 28 70 40 77.5 0.5

MR-28-40/1A 40/1 1.5 - - 22 60 50 70 0.5


MR-28-50/1A 50/1 2 - - 22 60 40 70 0.5
MR-28-60/1A 60/1 2.5 - - 22 60 40 70 0.5

MR-42-80/5A 80/5 1.5 - - 42 80 30 86 0.5


MR-42-100/5A 100/5 3.75 1.25 - 42 80 30 86 0.5
MR-42-150/5A 150/5 5 2.5 1 42 80 30 86 0.5
MR-42-200/5A 200/5 7.5 5 2.5 42 80 30 86 0.5
MR-42-250/5A 250/5 10 5 2.5 42 80 30 86 0.5

MR-42-80/1A 80/1 1.5 - - 40 72 26 70 0.5


MR-42-100/1A 100/1 5 1.5 - 40 72 45 70 0.5
MR-42-150/1A 150/1 5 3 - 40 72 40 70 0.5
MR-42-200/1A 200/1 7.5 5 3 40 72 40 70 0.5
MR-42-250/1A 250/1 10 7.5 2.5 40 72 40 70 0.5

MR-45-300/5A 300/5 10 7.5 3.75 45 80 30 86 0.5


MR-45-400/5A 400/5 15 7.5 5 45 80 30 86 0.5

MR-45-300/1A 300/1 10 10 5 45 83 32 100 0.5


MR-45-400/1A 400/1 15 10 5 45 83 32 100 0.5

MR-60-400/5A 400/5 15 7.5 5 60 100 30 86 0.5


MR-60-500/5A 500/5 15 10 5 60 100 30 86 0.5
MR-60-600/5A 600/5 20 10 7.5 60 100 30 86 0.5

MR-60-400/1A 400/1 15 7.5 5 58 100 30 100 0.5


MR-60-500/1A 500/1 20 15 5 58 100 32 100 0.5
MR-60-600/1A 600/1 20 15 10 58 100 32 100 0.5

MR-85-800/5A 800/5 20 10 7.5 85 124 30 86 0.5


MR-85-1000/5A 1000/5 30 15 10 85 124 30 86 1
MR-85-1200/5A 1200/5 30 15 10 85 124 30 86 1
MR-85-1500/5A 1500/5 30 15 10 85 124 30 86 1
MR-85-1600/5A 1600/5 30 15 10 85 124 30 86 1

MR-85-800/1A 800/1 20 15 10 84 122 30 100 0.5


MR-85-1000/1A 1000/1 25 20 15 94 135 30 100 1
MR-85-1200/1A 1200/1 25 20 15 94 135 30 100 1
MR-85-1500/1A 1500/1 25 20 15 94 135 30 100 1
MR-85-1600/1A 1600/1 25 20 15 94 135 30 100 1

MR-125-2000/5A 2000/5 30 20 15 125 160 30 86 1


MR-125-2500/5A 2500/5 30 20 15 125 160 30 861 -
MR-125-3000/5A 3000/5 30 20 15 125 160 30 86 1
MR-125-4000/5A 4000/5 30 20 15 125 160 30 86 1

MR-125-2000/1A 2000/1 25 20 15 132 175 30 150 1.5


MR-125-2500/1A 2500/1 25 20 15 132 175 30 150 1.5
MR-125-3000/1A 3000/1 25 20 15 125 180 32 150 1.5
MR-125-4000/1A 4000/1 25 20 15 140 215 45 150 4.5

4
PR Series Protection Range
IEC60044-1/BSEN60044-1 commonly define protection
current transformers in terms of composite error at an
accuracy limit factor. In simple terms this means how
accurate the current transformer will remain when the
primary current flowing is many times higher than in normal
conditions i.e. in a fault situation.
The classification of protection current transformers follows the following
simple formula:
“10 P 10”

Number before letter Number after letter indicates


indicates composite factor of primary current up
error achieved in to which composite error
percentage terms will be achieved

‘P’ for Protection

Manufacturers of protection devices will normally specify the classification for the
protection current transformer intended to operate the particular protection
device concerned.

In addition the classification of protection current transformers indicates


accuracy class:
5P – current transformer will have a ratio error of 1% and phase error not
exceeding 60 minutes.
10P – current transformer will have a ratio error of 3% (no level of phase
error specified).

The PR series is a range of two of the most popular classifications of protection


current transformers, 5P10 and 10P10. Other classifications are possible (such as 5P20
or 10P20). Please consult factory for a quotation should you require an alternative
classification or a current transformer with dimensions different to those set out below.

Part number Ratio range VA burden Accuracy class A B C D Approx. weight

PR-35-100/5A-2.5 100/5 2.5 10P10 35 98 60 100 2


PR-35-100/5A-5 100/5 5 10P10 35 98 90 100 3
PR-35-120/5A-2.5 120/5 2.5 10P10 35 98 55 100 2
PR-35-120/5A-5 120/5 5 10P10 35 98 85 100 3
PR-35-150/5A-2.5 150/5 2.5 5P10 & 10P10 35 98 50 100 1.5
PR-35-150/5A-5 150/5 5 5P10 & 10P10 35 98 70 100 2.5
PR-35-200/5A-2.5 200/5 2.5 5P10 & 10P10 35 98 40 100 1
PR-35-200/5A-5 200/5 5 5P10 & 10P10 35 98 60 100 2
PR-35-250/5A-2.5 250/5 2.5 5P10 & 10P10 35 98 35 100 1
PR-35-250/5A-5 250/5 5 5P10 & 10P10 35 98 55 100 1.5

PR-55-300/5A-5 300/5 5 5P10 & 10P10 55 98 75 100 1.5


PR-55-300/5A-15 300/5 15 5P10 & 10P10 55 125 90 100 4
PR-55-400/5A-5 400/5 5 5P10 & 10P10 55 98 60 100 1.5
PR-55-400/5A-15 400/5 15 5P10 & 10P10 55 125 65 100 3
PR-55-500/5A-5 500/5 5 5P10 & 10P10 55 98 55 100 1
PR-55-500/5A-15 500/5 15 5P10 & 10P10 55 125 60 100 2.5
PR-55-600/5A-5 600/5 5 5P10 & 10P10 55 98 50 100 1
PR-55-600/5A-15 600/5 15 5P10 & 10P10 55 125 55 100 2.5

PR-65-800/5A-5 800/5 5 5P10 & 10P10 65 110 40 100 1


PR-65-800/5A-15 800/5 15 5P10 & 10P10 65 110 80 100 3

PR-80-1000/5A-15 1000/5 15 5P10 & 10P10 80 125 70 100 2


PR-80-1200/5A-15 1200/5 15 5P10 & 10P10 80 125 65 100 2.5

PR-90-1500/5A-15 1500/5 15 5P10 & 10P10 90 140 55 100 2.5


PR-90-1600/5A-15 1600/5 15 5P10 & 10P10 90 140 55 100 2.5

PR-100-2000/5A-15 2000/5 15 5P10 & 10P10 100 155 55 100 3


PR-110-2500/5A-15 2500/5 15 5P10 & 10P10 110 165 45 100 3
PR-120-3000/5A-15 3000/5 15 5P10 & 10P10 120 180 45 150 3
Consult factory for availability and lead time on 1A secondary for protection range.
1A current transformer dimensions may vary by up to 10%.

5
Class PX Current Transformers
In some balanced protection systems where sensitivity and
stability levels required are high, classes 5P10 or 10P10 may
not be adequate. In these situations a Class PX current
transformer will usually be specified. Class PX as defined in
IEC60044-1/BSEN60044-1 allows the manufacturer of a
protection device to detail more specific requirements of the
current transformer so as to achieve a more sensitive
protection scheme. Typically this will involve specifying the
following information for the current transformer:
1) Turns ratio 4) Maximum excitation current at the
2) Minimum kneepoint voltage rated minimum kneepoint voltage
3) Maximum secondary resistance

To enquire about Class PX current transformers consult the factory with the above
information together with any physical limiting dimensions and the aperture size
required. If not all the above information is available, details of relay type, lead run from
current transformer to relay and the fault current expected to flow through the zone
protected by the current transformers will be required in order to provide a quotation.

Miniature Current Transformers


A range of Wedding ring Miniature Tape wound Current
transformers whose size permits PCB mounting. Designed to
convert high currents to low level electronic signals.
Available in tape wound with ring or foot mounting versions
or in a moulded case.
Specifications
Ring type (P) Foot mounting
Primary current range: 10A-100A option (F)
Secondary output: 10mA-100mA
VA output: 0.015VA-0.15VA
System frequency: 50/60Hz
Service temperature: 0°C to + 80°C
Insulation class: BSEN60085 Class Y
Operating voltage: 720V AC
Test voltage: 2kV DC
Accuracy
20-80%: 1.5%
81-120%: 1%

Part number Ratio range Type


773-01-P-FL 10A-100A/10mA-100mA Ring type, flexible lead 150mm
773-02-P-FL 10A-100A/10mA-100mA Ring type, flexible lead 450mm
773-01-F-FL 10A-100A/10mA-100mA Ring type, foot mounting, flexible lead 150mm

Moulded Case (MC)


Dimensions
Specifications A = 16mm transformer ratings
Service temperature: -20°C to + 85°C Fixing centres 30mm x 30mm
Insulation class: BSEN60085 Class Y M3.5 terminal screw and clamp

Part number Ratio range Type


773-01-MC 10A-100A/10mA-100mA Moulded case

6
Split Core Current Transformers

7
SC Series Split Core Current
Transformers
A range of split core current transformers that offers a
cost effective and efficient method by which the current
can be measured without the need to break the
conductor, thereby reducing installation and
commissioning time.

Specifications

System voltage: 720V (0.72kV) maximum


Test voltage: 3kV for 1 minute
System frequency: 50/60Hz
Insulation class: E Features
Overload withstand: 1.2 times rated current continuously • High quality comprehensive
Short circuit thermal: 100 x rated primary for 1 second measurements
• Available in a wide range of
Operating temperature: -20˚C to +70˚C transformer ratings
Relative humidity: 0-90% (non condensing) • Accuracy up to Class 0.5
Compliant with: IEC/EN60044-1, BS7626 • Foot or busbar mounted

Accuracy: Class 3, 1 & 0.5


Benefits
Mounting hardware: Plug-in metal feet for wall or base mounting
• Faster installation
or moulded busbar mounting
• Cost effective
Rated dynamic current: = 2.55 x lht • Long product life
Enclosure: Flame retardant grade classified UL 94V-O
Applications
• Switchgear
• Distribution systems
• Generator sets
• Control panels

Model Case 1 Case 2 Case 3 Case 4 Case 5


A 20 50 80 80 80
B 30 80 80 120 160
C 51 78 108 108 120
D 89 114 144 144 184
E 111 145 145 185 245
F 34 32 32 32 52
G 47 32 32 32 52
H 40 32 32 32 52
I 32 33 33 33 38
Weight (Kg) 0.75 0.90 1.05 1.25 4.30

8
Product Codes
Part number Ratio Burden VA against class index Aperture (mm)
0.5 1 3
SC1-100/5A 100/5A - - 1.5 20 x 30
SC1-150/5A 150/5A - - 2 20 x 30
Case 1

SC1-200/5A 200/5A - 1.5 2.5 20 x 30


SC1-250/5A 250/5A - 2 4 20 x 30
SC1-300/5A 300/5A 1.5 4 6 20 x 30
SC1-400/5A 400/5A 2.5 6 10 20 x 30
SC2-250/5A 250/5A 1 2 4 50 x 80
SC2-300/5A 300/5A 1.5 3 6 50 x 80
SC2-400/5A 400/5A 1.5 3 10 50 x 80
Case 2

SC2-500/5A 500/5A 2.5 5 15 50 x 80


SC2-600/5A 600/5A 2.5 5 15 50 x 80
SC2-750/5A 750/5A 3 6 20 50 x 80
SC2-800/5A 800/5A 3 7.5 20 50 x 80
SC2-1000/5A 1000/5A 5 10 20 50 x 80
SC3-250/5A 250/5A 1 2 4 80 x 80
SC3-300/5A 300/5A 1.5 3 6 80 x 80
SC3-400/5A 400/5A 1.5 3 10 80 x 80
Case 3

SC3-500/5A 500/5A 2.5 5 15 80 x 80


SC3-600/5A 600/5A 2.5 5 15 80 x 80
SC3-750/5A 750/5A 3 6 20 80 x 80
SC3-800/5A 800/5A 3 7.5 20 80 x 80
SC3-1000/5A 1000/5A 5 10 20 80 x 80
SC4-500/5A 500/5A - 4 12.5 80 x 120
SC4-600/5A 600/5A - 5 15 80 x 120
SC4-750/5A 750/5A 2.5 6 17.5 80 x 120
SC4-800/5A 800/5A 3 7.5 20 80 x 120
Case 4

SC4-1000/5A 1000/5A 5 10 20 80 x 120


SC4-1200/5A 1200/5A 6 12.5 25 80 x 120
SC4-1250/5A 1250/5A 7.5 15 30 80 x 120
SC4-1500/5A 1500/5A 8 17 30 80 x 120
SC4-1600/5A 1600/5A 8 17 30 80 x 120
SC5-1000/5A 1000/5A 10 15 20 80 x 160
SC5-1250/5A 1250/5A 10 15 20 80 x 160
SC5-1500/5A 1500/5A 15 20 25 80 x 160
SC5-2000/5A 2000/5A 15 20 25 80 x 160
Case 5

SC5-2500/5A 2500/5A 15 20 25 80 x 160


SC5-3000/5A 3000/5A 20 25 30 80 x 160
SC5-4000/5A 4000/5A 20 25 30 80 x 160
SC5-5000/5A 5000/5A 20 25 30 80 x 160
SC5-6000/5A 6000/5A 20 25 30 80 x 160

9
3-in-1 Current Transformers

10
3-in-1 Current Transformers
A range of 3-in-1 current transformers combine three traditional
current transformers in one moulded case. 3-in-1 current
transformers can be directly installed next to a three-phase
moulded case circuit breaker, thus saving installation time where
fitting three standard individual current transformers would be
required. The M3N1 range of current transformers offers primary
currents between 60-630A with 5A secondaries with up to Class
0.5 accuracy performance.

Specifications

System voltage: 720V maximum


Test voltage: 3kV for 1 minute
System frequency: 50Hz or 60Hz
Primary ratings: 60A to 630A
Short circuit thermal current: 60 x rated primary current (lth): for 1 sec
Features
Overload withstand: 1.2 x rated current continuously
• Cost effective three-phase
Rated dynamic current: = 2.55 x Ith
moulded case
Secondary terminals: M4 screw terminals
• Ratio’s ranging from 60/5
to 630/5 Enclosure: Flame retardant grade classified UL 94V-O
• Integrated wire sealable Aperture holes centres: 25, 35, 45mm
terminal cover Operating temperature: -20°C to +85°C
• Busbar, DIN-rail and metal feet Accuracy: Class 0.5, 1, 3
mounting hardware supplied Mounting hardware: Plug-in metal feet for wall or base mounting
• Combined M4 posi/slot screw Busbar and DIN-rail mounting
Compliant with: IEC/EN60044-1
Benefits
• Isolated output for safety
• Faster installation Part number Ratio Burden VA against Aperture
• Compact size class index (mm)
• Ex-stock delivery Class Class Class
0.5 1 3
Applications
M3N1-25-60/5 60/5 - 1 2 3@15 x 25mm
• Switchgear
M3N1-25-100/5 100/5 - 1.5 2.5 3@15 x 25mm
• Distribution systems
M3N1-25-125/5 125/5 - 1.5 2.5 3@15 x 25mm
• Generator sets
M3N1-25-150/5 150/5 1.5 1.5 2.5 3@15 x 25mm
• Control panels
M3N1-25-160/5 160/5 1.5 1.5 2.5 3@15 x 25mm

M3N1-35-100/5 100/5 - 1.5 2 3@21 x 25mm


M3N1-35-125/5 125/5 - 1.5 2.5 3@21 x 25mm
M3N1-35-150/5 150/5 - 1.5 2.5 3@21 x 25mm
M3N1-35-160/5 160/5 1.5 1.5 2.5 3@21 x 25mm
M3N1-35-200/5 200/5 1.5 1.5 2.5 3@21 x 25mm
M3N1-35-250/5 250/5 1.5 1.5 2.5 3@21 x 25mm

M3N1-45-250/5 250/5 1.5 1.5 2.5 3@31 x 31mm


M3N1-45-300/5 300/5 2.5 2.5 3.75 3@31 x 31mm
M3N1-45-400/5 400/5 2.5 2.5 3.75 3@31 x 31mm
M3N1-45-500/5 500/5 2.5 2.5 3.75 3@31 x 31mm
M3N1-45-600/5 600/5 2.5 2.5 3.75 3@31 x 31mm
M3N1-45-630/5 630/5 2.5 2.5 3.75 3@31 x 31mm

M3N1-25 M3N1-35 M3N1-45

11
Ebony Moulded Case Current
Transformers

12
Ebony Series Current Transformers
The range of Crompton Instruments Ebony current
transformers offers wide system current ratings,
apertures, busbar and case sizes to suit every
application. Manufactured to meet EN60044
the range benefits include ratio rating from 1/5 to
6000/5, accuracy up to Class 0.5, integral terminal
cover for safety and multiple mounting options.

Construction
The toroidal core and secondary winding is encapsulated by a self-extinguishing
polycarbonate moulded case cover providing excellent mechanical strength and
electrical insulation. The material is halogen free thus reducing risk of halogen
emissions in case of fire. The integral covered secondary terminals offer protection to
IP20B and the enclosure is protected to IP40.
Features
• CT ratios from 1A to 6000A with
Installation Options
5A and 1A secondaries
• Plug-in metal feet for wall or base mounting
• Accuracy up to Class 0.5 • Plastic DIN-rail clips for DIN-rail mounting
• Integral terminal cover • Moulded busbar mounting
• Primary copper busbar mounting
• High impact, flame retardant
• Multi busbar mounting for two busbars
moulded case
• Busbar, DIN-rail or foot
mounting options Specifications

System voltage: 720V maximum


Benefits Test voltage: 3kV for 1 minute
• Wide range of apertures and System frequency: 50/60Hz
case sizes Short circuit thermal 60 x rated primary current for 1 second
• Reduction of high currents for current (Ith)*:
ease of metering Overload withstand: 1.2 x rated current continuously
Dynamic current (Idyn)*: = 2.55 x Ith
• Long product life Saturation coefficient: <5 for through aperture models
<10 for wound primary
Approvals Service temperature: -20°C to 85°C
• BSEN61010-1 Insulation class: Class E BS2757 IEC85
• EN60044-1 Enclosure code: IP40
Integral terminal cover: IP20B
• UL Recognized file no: E257877
Complies with: IEC60044-1:2003
Humidity: Up to 95% RH (non condensing)
Secondary terminals Up to 10mm2 cable
screw clamp:
* Thermal current (Ith) & dynamic
‘Fast On’: 6.3mm type
current (ldyn)
lth is the highest primary current
(effective value), the ldyn is the highest
Loss in copper wires between instrument and CT for 5A secondary
primary current (Peak Value) that the
CT can support for 1 second without Wire section Loss in VA (for both wires)
damage, owing to excessive overloads in mm2 1m 2m 4m 6m 8m 10m
with secondary short circuits. 1.5 0.60 1.19 2.38 3.57 4.76 5.95
2.5 0.36 0.71 1.43 2.14 2.86 3.57
4 0.22 0.45 0.89 1.34 1.79 2.23
6 0.15 0.30 0.60 1.89 1.19 1.49
10 0.09 0.18 0.36 0.54 0.71 0.89

Loss in copper wires between instrument and CT for 1A secondary


Wire section Loss in VA (for both wires)
in mm2 10m 20m 40m 60m 80m 100m
1 0.36 0.71 1.43 2.14 2.86 3.57
1.5 0.24 0.48 0.95 1.43 1.90 2.38
2.5 0.14 0.29 0.57 0.86 1.14 1.43
4 0.09 0.18 0.36 0.54 0.71 0.89
6 0.06 0.12 0.24 0.36 0.48 0.60
10 0.04 0.07 0.14 0.21 0.29 0.36

13
M53Q Range
Case Size: 45mm wide x 30mm deep x 65mm high
1.8" wide x 1.2" deep x 2.5" high
Aperture: 20 x 6mm and 21mm diameter
0.8" x 0.2" and 0.8" diameter
Weight: 0.25Kg

Model type Primary current VA at Class 3 VA at Class 1

M53Q-50/5 50 1 -
M53Q-60/5 60 1.25 -
M53Q-75/5 75 1.5 -
M53Q-80/5 80 1.25 -
M53Q-100/5 100 2.5 1.5
M53Q-125/5 125 3 2.5
M53Q-150/5 150 3.75 2.5
M53Q-200/5 200 5 3.75
M53Q-250/5 250 - 5
M53Q-300/5 300 7.5 5

Ordering Codes
As above Change end suffix to depict required secondary.
For example: M53Q-50/1
M30-DINCLIP DIN-rail mounting clip for DIN-rail mounting option
(2 required)
• Mounting feet centres
26mm x 51mm

M55E Range
Case Size: 50mm wide x 50mm deep x 80mm high
2" wide x 2" deep x 3.1" high
Aperture: 15 x 5mm and 16 diameter
0.6" x 0.2" diameter
Weight: 0.4Kg

Model type Primary current VA at Class 3 VA at Class 1


M55E-30/5 30 1.25 -
M55E-40/5 40 2.5 -
M55E-50/5 50 2.5 -
M55E-60/5 60 3.75 2.5
M55E-75/5 75 5 3.75
M55E-80/5 80 5 3.75
M55E-100/5 100 7.5 5

Ordering Codes
As above Change end suffix to depict required secondary.
For example: M55E-50/1
M50-DINCLIP (2 required)

• Mounting feet centres


33mm x 71mm

Consult factory for availability and lead time on 1A secondary. 14


M53J Range
Case Size: 50mm wide x 30mm deep x 80mm high
2" wide x 1.2" deep x 3.1" high
Aperture: 30 x 10mm, 25 x 15mm and 20 x 20mm and 25mm diameter
1.2" x 0.4", 1" x 0.6" and 0.8" x 0.8" and 1.0" diameter
Weight: 0.22Kg

Model type Primary current VA at Class 3 VA at Class 1


M53J-100/5 100 1.25 -
M53J-125/5 125 1.25 -
M53J-150/5 150 2.5 -
M53J-160/5 160 2.5 -
M53J-200/5 200 2.5 2.5
M53J-250/5 250 3.75 2.5
M53J-300/5 300 5 3.75
M53J-400/5 400 7.5 3.75

Ordering Codes
As above Change end suffix to depict required secondary.
For example: M53J-150/1
M30-DINCLIP DIN-rail mounting clip for DIN-rail mounting option
(2 required)

• Mounting feet centres


33mm x 51mm

M65F Range
Case Size: 60mm wide x 50mm deep x 94mm high
2.4" wide x 2" deep x 3.7" high
Aperture: 20 x 10mm and 23mm diameter
0.8" x 0.4", 0.9" diameter
Weight: 0.4Kg

Model type Primary current VA at VA at VA at


Class 3 Class 1 Class 0.5
M65F-30/5 30 1.25 - -
M65F-40/5 40 2.5 - -
M65F-50/5 50 2.5 - -
M65F-60/5 60 3.75 - -
M65F-75/5 75 5 2.5 -
M65F-80/5 80 5 2.5 -
M65F-100/5 100 7.5 5 2.5
M65F-125/5 125 7.5 5 2.5
M65F-150/5 150 15 10 5
M65F-200/5 200 20 15 7.5
M65F-250/5 250 20 20 10
M65F-300/5 300 30 30 10

Ordering Codes
As above Change end suffix to depict required secondary.
For example: M65F-150/1
• Mounting feet centres M50-DINCLIP DIN-rail mounting clip for DIN-rail mounting option
42mm x 71mm (2 required)

15 Consult factory for availability and lead time on 1A secondary.


M63N Range
Case Size: 60mm wide x 30mm deep x 94mm high
2.3" wide x 1.2" deep x 3.7" high
Aperture: 40 x 10mm and 32mm diameter
1.5" x 0.4" and 1.2" diameter
Weight: 0.3Kg

Model type Primary current VA at VA at VA at


Class 3 Class 1 Class 0.5
M63N-200/5 200 2.5 - -
M63N-250/5 250 3.75 2.5 -
M63N-300/5 300 5 3.75 -
M63N-400/5 400 7.5 5 -
M63N-500/5 500 10 7.5 3.75
M63N-600/5 600 10 7.5 5
M63N-750/5 750 15 10 7.5
M63N-800/5 800 15 10 7.5

Ordering Codes
As above Change end suffix to depict required secondary.
For example: M53J-150/1
M30-DINCLIP DIN-rail mounting clip for DIN-rail mounting option
(2 required)

• Mounting feet centres


42mm x 51mm

MA5G Range
Case Size: 77mm wide x 50mm deep x 116mm high
3" wide x 2" deep x 4.5" high
Aperture: 40 x 10mm, 30 x 30mm and 36mm diameter
1.6" x 0.4", 1.2" x 1.2" and 1.4" diameter
Weight: 0.6Kg

Model type Primary current VA at VA at VA at


Class 3 Class 1 Class 0.5
MA5G-100/5 100 2.5 - -
MA5G-125/5 125 5 2.5 -
MA5G-150/5 150 5 3.75 -
MA5G-200/5 200 10 5 2.5
MA5G-250/5 250 10 7.5 5
MA5G-300/5 300 10 7.5 5
MA5G-400/5 400 10 7.5 5
MA5G-500/5 500 10 7.5 5
MA5G-600/5 600 10 10 7.5 116

MA5G-750/5 750 15 10 10
MA5G-800/5 800 15 10 10
MA5G-1000/5 1000 20 15 15

71
Ordering Codes
As above Change end suffix to depict required secondary.
For example: MA5G-150/1 • Mounting feet centres
M50-DINCLIP DIN-rail mounting clip for DIN-rail mounting option 58.5mm x 71mm
(2 required)

Consult factory for availability and lead time on 1A secondary. 16


MA5Y Range
Case Size: 77mm wide x 50mm deep x 116mm high
3" wide x 2" deep x 4.5" high
Fixing: M8 stud primary bar
Weight: 0.45Kg

Model type Primary current VA at Class 3 VA at Class 1


MA5Y-1/5 1 7.5 5
MA5Y-5/5 5 7.5 5
MA5Y-10/5 10 7.5 5
MA5Y-15/5 15 7.5 5
MA5Y-20/5 20 7.5 5
MA5Y-30/5 30 7.5 5
MA5Y-40/5 40 7.5 5

• Mounting feet
Ordering Codes
centres As above Change end suffix to depict required secondary.
58.5mm x 71mm For example: MA5Y-1/1
M50-DINCLIP DIN-rail mounting clip for DIN-rail mounting option (2 required)

M93L Range
Case Size: 90mm wide x 30mm deep x 131mm high
3.5" wide x 1.2" deep x 5.1" high
Aperture: 50 x 10mm, 40 x 30mm and 42mm diameter
2" x 0.4", 1.5" x 1.2" and 1.6" diameter
Weight: 0.45Kg

Model type Primary current VA at Class 3 VA at Class 1 VA at Class 0.5


M93L-400/5 400 15 7.5 3.75
M93L-500/5 500 20 15 5
M93L-600/5 600 30 20 10
M93L-750/5 750 20 15 7.5
• Mounting feet M93L-800/5 800 20 15 10
centres M93L-1000/5 1000 20 20 15
71.5mm x 51mm M93L-1200/5 1200 30 30 20
M93L-1250/5 1250 30 30 20
M93L-1500/5 1500 30 30 20
M93L-1600/5 1600 30 30 20

Ordering Codes
As above Change end suffix to depict required secondary.
For example: M93L-1000/1
M30-DINCLIP DIN-rail mounting clip for DIN-rail mounting option (2 required)

M93R Range
Case Size: 90mm wide x 30mm deep x 131mm high
3.5" wide x 1.2" deep x 5.1" high
Aperture: 64 x 12.6mm, 60 x 30mm
2.5" x 0.5", 2.4" x 1.2"
Weight: 0.6Kg

Model type Primary current VA at Class 3 VA at Class 1 VA at Class 0.5


M93R 800/5 10 10 5
M93R 1000/5 10 10 7.5
M93R 1200/5 10 15 10
M93R 1250/5 10 15 10
• Mounting feet M93R 1500/5 10 20 15
centres M93R 1600/5 10 20 15
71.5mm x 51mm M93R 2000/5 10 20 20

Ordering Codes
As above Change end suffix to depict required secondary.
For example: M93R-1000/1
17 M30-DINCLIP DIN-rail mounting clip for DIN-rail mounting option (2 required)
M93S Range
Case Size: 90mm wide x 30mm deep x 131mm high
3.5" wide x 1.2" deep x 5.1" high
Aperture: 76.5 x 19mm, 60 x 30mm
3.0" x 0.7", 2.4" x 1.2"
Weight: 0.7Kg

Model type Primary current VA at Class 3 VA at Class 1 VA at Class 0.5


M93S-800/5A 800 10 10 5
M93S-1000/5A 1000 150 10 7.5
M93S-1200/5A 1200 20 15 10
M93S-1250/5A 1250 20 20 15
M93S-1500/5A 1500 20 20 15 • Mounting feet
M93S-1600/5A 1600 30 20 15 centres
M93S-2000/5 2000 30 20 15 71.5mm x 51mm

Ordering Codes
As above Change end suffix to depict required secondary.
For example: M93S-1000/1
M30-DINCLIP DIN-rail mounting clip for DIN-rail mounting option (2 required)

S95P Range
Case Size: 90mm wide x 50mm deep x 144mm high
3.5" wide x 2" deep x 5.7" high
Weight: 0.9Kg - 1.11Kg

Model type Primary current VA at Class 1


S95P-5/5 5+5=5 5
S95P-5/5/5 5+5+5=5 5

Ordering Codes
As above Change end suffix to depict required secondary.
For example: S95P-1/1
M50-DINCLIP DIN-rail mounting clip for DIN-rail mounting option (2 required)
• Mounting feet
centres
71.5mm x 71mm

S97P Range
Case Size: 90mm wide x 50mm deep x 144mm high
3.5" wide x 2" deep x 5.7" high
Weight: 0.9Kg - 1.11Kg

Model type Primary current VA at Class 1


S97P-5/5/5/5 5+5+5+5=5 5
S97P-5/5/5/5/5 5+5+5+5+5=5 5
S97P-5/5/5/5/5/5 5+5+5+5+5+5=5 5

Ordering Codes
As above Change end suffix to depict required secondary. • Mounting feet
For example: S95P-1/1
centres
71.5mm x 91mm

Consult factory for availability and lead time on 1A secondary. 18


MB5D Range
Case Size: 134mm wide x 50mm deep x 156mm high
5.2" wide x 2" deep x 6.1" high
Aperture: 80 x 30mm, 60 x 30mm, 50 X 50mm and 63mm diameter
3.1" x 1.2", 2.3" x 1.2", 2 x 2" and 2.4" diameter
Weight: 0.5Kg

Model type Primary VA at VA at VA at


current Class 3 Class 1 Class 0.5
MB5D-400/5 400 15 10 7.5
MB5D-500/5 500 20 15 10
MB5D-600/5 600 15 10 5
MB5D-750/5 750 15 10 5
MB5D-800/5 800 20 15 7.5
MB5D-1000/5 1000 22.5 20 10
MB5D-1200/5 1200 30 20 15
MB5D-1250/5 1250 30 20 15
MB5D-1500/5 1500 30 20 15
MB5D-1600/5 1600 40 30 20
MB5D-2000/5 2000 50 40 30

Ordering Codes
As above Change end suffix to depict required secondary.
For example: MB5D-1600/1

• Mounting feet centres


105mm x 71mm
• Mounting hole centres
110mm x 6.6mm

MB5Z Range
Case Size: 134mm wide x 50mm deep x 156mm high
5.2" wide x 2" deep x 6.1" high
Aperture: 104 x 35mm, 35mm diameter
4" x 1.3" and 1.3" diameter
Weight: 0.7Kg

Model type Primary VA at VA at VA at


current Class 3 Class 1 Class 0.5
MB5Z-750/5 750 15 7.5 2.5
MB5Z-800/5 800 20 10 2.5
MB5Z-1000/5 1000 22.5 15 7.5
MB5Z-1200/5 1200 30 20 10
MB5Z-1250/5 1250 30 20 15
MB5Z-1500/5 1500 30 20 15
MB5Z-1600/5 1600 30 20 15
MB5Z-2000/5 2000 30 20 15
MB5Z-2400/5 2400 30 20 15
MB5Z-2500/5 2500 30 20 15
MB5Z-3000/5 3000 30 20 15
MB5Z-4000/5 4000 30 20 15

Ordering Codes
As above Change end suffix to depict required secondary.
For example: MB5Z-1600/1
• Mounting feet centres
105mm x 71mm
• Mounting hole centres
110mm x 6.6mm

19 Consult factory for availability and lead time on 1A secondary.


MC5T Range
Case Size: 140mm wide x 50mm deep x 238mm high
5.5" wide x 2" deep x 9.3" high
Aperture: 160 x 50mm
6.3" x 2"
Weight: +/-1.5Kg

Model type Primary VA at VA at VA at


current Class 3 Class 1 Class 0.5
MC5T-1600/5 1600 45 30 20
MC5T-2000/5 2000 45 30 20
MC5T-2500/5 2500 60 45 30
MC5T-3000/5 3000 60 45 30
MC5T-3200/5 3200 60 45 30
MC5T-4000/5 4000 60 45 30
MC5T-5000/5 5000 60 45 30
MC5T-6000/5 6000 60 45 30

Ordering Codes
As above Change end suffix to depict required secondary.
For example: MC5T-1600/1

• Hole for M6 diameter screws or


busbar mounting

MD5T Range
Case Size: 213mm wide x 50mm deep x 165mm high
8.3" wide x 2" deep x 6.5" high
Aperture: 160 x 50mm
6.3" x 2"
Weight: +/-1.5Kg

Model type Primary VA at VA at VA at


current Class 3 Class 1 Class 0.5
MD5T-1600/5 1600 45 30 20
MD5T-2000/5 2000 45 30 20
MD5T-2500/5 2500 60 45 30
MD5T-3000/5 3000 60 45 30
MD5T-3200/5 3200 60 45 30
MD5T-4000/5 4000 60 45 30
MD5T-5000/5 5000 60 45 30
MD5T-6000/5 6000 60 45 30

Ordering Codes
As above Change end suffix to depict required secondary.
For example: MD5T-1600/1

• Hole for M6 diameter screws or


busbar mounting

Consult factory for availability and lead time on 1A secondary. 20


Moulded Case Overview Range
Type MA5Y M53Q M55E M53J M65F M63N MA5G M93L

Inside diameter (mm) 21 16.2 25 23 32 36 32


Busbar M8 Stud 20x6 15x5 30x10 20x10 40x10 40x10 50x10
25x15 30x30 40x30
20x20
Dimensions (mm)
Height 116 65 80 80 94 94 116 131
Width 77 45 50 50 60 60 77 90
Depth 50 30 50 50 50 30 50 30
DIN-rail mounting X X X X X X X X X X X X X X X X
Foot mounting X X X X X X X X X X X X X X X X
Integrated terminal cover X X X X X X X X X X X X X X X X
Secondary 5 1 5 1 5 1 5 1 5 1 5 1 5 1 5 1
Primary current
1 X X
5 X X
10 X X
15 X X
20 X X X X
30 X X X X X X
40 X X X X X X
50 X X X X X X
60 X X X X X X
75 X X X X X X
80 X X X X X
100 X X X X X X X X X
125 X X X X X X X
150 X X X X X X X
160 X
200 X X X X X X X X X
250 X X X X X X X X X
300 X X X X X X X X X
400 X X X X X X
500 X X X X X
600 X X X X X
750 X X X X X
800 X X X X X
1000 X X X
1200 X
1250
1500 X
1600 X
2000
2500
3000
3200
4000
5000
6000
5+5=5
5+5+5=5
5+5+5+5=5
5+5+5+5+5=5
5+5+5+5+5+5=5
1+1=1
1+1+1=1
1+1+1+1=1
1+1+1+1+1=1
1+1+1+1+1+1=1

21 Consult factory for availability and lead time on 1A secondary.


Moulded Case Overview Range
Type M93S M93R MB5D MB5Z MC5T MD5T S95 S97

Inside diameter (mm) 63 35


Busbar 60x30 60x30 80x30 104x35 50x160 160x50
76.5x19 64x12.6 60x30
50x50
Dimensions (mm)
Height 131 131 156 156 238 165 144 144
Width 90 90 134 134 140 213 90 90
Depth 30 30 50 50 50 50 50 70
DIN-rail mounting X X X X X X
Foot mounting X X X X X X X X X X X X
Integrated terminal cover X X X X X X X X X X X
Secondary 5 1 5 1 5 1 5 1 5 1 5 1 5 1 5 1
Primary current
5
10
15
20
25
30
40
50
60
75
80
100
125
150
160
200
250
300
400 X X
500 X X
600 X X
750 X X X X
800 X X X X X X X X
1000 X X X X X X X X
1200 X X X X X X X X
1250 X X X X X X X X
1500 X X X X X X X X
1600 X X X X X X X X X X X X
2000 X X X X X X X X X X X X
2500 X X X X X X
3000 X X X X X X
4000 X X X X X X
5000 X X
6000 X X
5+5=5 X
5+5+5=5 X
5+5+5+5=5 X
5+5+5+5+5=5 X
5+5+5+5+5+5=5 X
1+1=1 X
1+1+1=1 X
1+1+1+1=1 X
1+1+1+1+1=1 X
1+1+1+1+1+1=1 X

Consult factory for availability and lead time on 1A secondary. 22


About TE Connectivity

TE Connectivity is a global, $12.1 billion company that designs and manufactures


over 500,000 products that connect and protect the flow of power and data inside
the products that touch every aspect of our lives. Our nearly 100,000 employees
partner with customers in virtually every industry – from consumer electronics,
energy and healthcare, to automotive, aerospace and communication networks –
enabling smarter, faster, better technologies to connect products to possibilities.

While TE Connectivity (TE) has made every reasonable effort to ensure the accuracy of the information in this catalogue, TE does not guarantee that it is error-free, nor does TE make any
Tyco Electronics UK Ltd CI-EPP-TAPE WOUND CT-10/11

other representation, warranty or guarantee that the information is accurate, correct, reliable or current. TE reserves the right to make any adjustments to the information contained herein at
any time without notice. TE expressly disclaims all implied warranties regarding the information contained herein, including, but not limited to, any implied warranties of merchantability or
fitness for a particular purpose. The dimensions in this catalogue are for reference purposes only and are subject to change without notice. Specifications are subject to change without notice.
Consult TE for the latest dimensions and design specifications. TE Connectivity and TE connectivity (logo) are trademarks. CROMPTON is a trademark of Crompton Parkinson Limited and is
used under licence. Other trademarks are property of their respective owners.

TE Energy – innovative and economical solutions for the electrical power industry: cable accessories, connectors & fittings,
insulators & insulation, surge arresters, switching equipment, street lighting, power measurement and control.

Tyco Electronics UK Ltd Registered office:


TE Energy Faraday Road, Dorcan
Freebournes Road Swindon, SN3 5HH
Witham, Essex CM8 3AH Reg. no. 550 926

Phone: +44 (0)870 870 7500


Fax: +44 (0)870 240 5287
Email: crompton.info@te.com

http://energy.te.com
www.crompton-instruments.com

You might also like