STATEMENT OF TECHNICAL REQUIREMENTS
380V/415V/440V 50HZ/60HZ 3 PH PRIMARY
AND 230V 50HZ/60HZ 3PH 4 WIRE SECONDARY
CENTRE TAPPED NEUTRAL EARTHED TRANSFORMER
EED5016
NOV 2006
i
ii
380V/415V/440V 50HZ/60HZ 3 PH PRIMARY
AND 230V 50HZ/60HZ 3PH 4 WIRE SECONDARY
CENTRE TAPPED NEUTRAL EARTHED TRANSFORMER
EED5016
3. Input Power Supply. The transformers should be designed to meet
the characteristics of the following input voltage for the rated load and duty
cycle:
3.1 440V, 60Hz, 3Ph
Load range Tolerance Average
Max. Unbalance 2%
Max. Modulation 2%
Transients (Excluding Spikes)
(Average line to line value for
3phase system)
1
a. Frequent Transients
High limit +6%
Recovery Time 0.5 Sec
Low Limit 10%
Recovery Time 0.5 Sec
b. Infrequent Transients
High limit ± 10%
Recovery Time 1 Sec
Low Limit 16%
Recovery Time 1 Sec
(b) Waveform Max. Individual Harmonic 3%
Max. total Harmonic content 5%
(c) Frequency Nominal Frequency 60 Hz
Load range Tolerance ± 2.5%
Constant Load Tolerance ± 0.5%
Modulation 0.25%
Infrequent Transients
High limit + 3.75%
Recovery Time 2 Seconds
Low Limit 3.75%
Recovery Time 2 Seconds
3.2 415V, 50Hz, 3Ph
Load range Tolerance Average
2
phase of 3phase system ± 6%
Max. Unbalance
2%
Max. Modulation
2%
Transients (Excluding Spikes)
(Average line to line value for
3phase system)
a. Frequent Transients
High limit
+6%
Recovery Time
0.5 Sec
Low Limit
10%
Recovery Time
0.5 Sec
b. Infrequent Transients
High limit
Recovery Time + 10%
Low Limit 1 Sec
Recovery Time 16%
1 Sec
(b) Waveform Max. Individual Harmonic 3%
Max. total Harmonic content 5%
(c) Frequency Nominal Frequency 50Hz
Load range Tolerance ± 2.5%
Constant Load Tolerance ± 0.5%
Modulation 0.25%
Infrequent Transients
High limit + 3.75%
Recovery Time 2 Seconds
Low Limit 3.75%
Recovery Time 2 Seconds
3.3 380V, 50Hz, 3 Ph
3
S No Characteristic Description Value
(a) Voltage Nominal Voltage 380V
Load range Tolerance Average
Max. Unbalance 2%
Max. Modulation 2%
Transients (Excluding Spikes)
(Average line to line value for
3phase system)
a. Frequent Transients
High limit +6%
Recovery Time 0.5 Sec
Low Limit 10%
Recovery Time 0.5 Sec
b. Infrequent Transients
High limit + 10%
Recovery Time 1 Sec
Low Limit 16%
Recovery Time 1 Sec
(b) Waveform Max. Individual Harmonic 3%
Max. total Harmonic content 5%
Load range Tolerance ± 2.5%
Constant Load Tolerance ± 0.5%
Modulation ±0.25%
Infrequent Transients
4
High limit + 3.75%
Recovery Time 2 Seconds
Low Limit 3.75%
Recovery Time 2 Seconds
Load range Tolerance Average
Max. Unbalance 2%
Max. Modulation 2%
Transients (Excluding Spikes)
(Average line to line value for
3phase system)
a. Frequent Transients
High limit +6%
Recovery Time 0.5 Sec
Low Limit 10%
Recovery Time 0.5 Sec
b. Infrequent Transients
High limit +10%
Recovery Time 1 Sec
Low Limit 16%
5
Recovery Time 1 Sec
(b) Waveform Max. Individual Harmonic 3%
Max. total Harmonic content 5%
(c) Frequency Nominal Frequency 50Hz/60Hz
Load range Tolerance ± 2.5%
Constant Load Tolerance ± 0.5%
Modulation 0.25%
Infrequent Transients
High limit + 3.75%
Recovery Time 2 Seconds
Low Limit 3.75%
Recovery Time 2 Seconds
5. Scope of supply. The following ratings of transformers will comprise the
scope of supply for one ship:
6. Design Requirements.
6.1.1 Primary Voltage : 380V/415V/440V, 50Hz/60Hz, 3 Ph.
6.1.2 Rating : 5KVA to 20 KVA
6
6.1.3 Primary Winding : Delta connected.
6.1.4 Secondary Winding : Star connected three phase terminal output. Centre
point of secondary centre tapped as neutral (two leads). Five connections should
be brought out i.e. one each for three phases and two neutral lines.
6.1.5 Secondary Voltage: The output Voltage between any one of the three
phases and neutral line should be 230V, 50Hz/60Hz.
7.0 Permissible Temperature Rise.
8 Regulation. The regulation at 0.8 P.F should not be more than 3.3%.
9 Inrush Current. The saturated reactance of the primary winding of a
transformer is not to be less than 4.2 Fp /K Ohm per phase. The Primary winding
factor Fp=3 for a Delta connected Primary winding and K is the total KVA rating
of a transformer as specified. In the TSPs. The saturated reactance is to be
calculated as follows:
80 f N2A
Xt = X 10 10 Ohm/ Phase
Where LN : no. of turns in Primary Winding
7
A : Mean cross sectional area of the coil formed by the Primary
winding (mm2)
L : Length of the Winding (mm)
F : Supply Frequency (Hz)
10. Technical Requirements
11 Construction.
8
11.2 Insulation. The design of the Transformer should be “F” class. The
insulation material of winding is to include a minimum thickness of 0.5 mm of
mica or micanite or other approved insulation appropriate to the insulation class
between one winding and any one of the following parts:
(a) Core
(b) Another winding
(c) Earthed screen
11.5.1 Vacuum/pressure impregnation and bake, plus one dip and bake.
11.5.2 Hot dip and bake –three times.
11.5.3 A smooth even finish of the windings is essential and an air drying
finishing varnish may be applied after the impregnation process to achieve this
finish.
14. Cable Glands. The cable glands of mild steel for body and naval brass
for nut for incoming and outgoing cable should conform to specifications
9
mentioned in DGS/EED/VI/1535/R6 and NES 514. The glands for incoming &
outgoing cables are to be fitted on opposite ends and do not pass each other
across the terminal board. The size of the cable gland shall be indicted at the
time of approval of binding drawings.
21. Efficiency. During the final stages of the temp. rise tests for the
equipment, when temperatures are study, the output and input powers are to be
measured(by wattmeter) to enable the equipment efficiency to be calculated. The
efficiency is to be calculated during full load trials of the transformer in
accordance with BS 3399. The efficiency shall be 97% and above.
10
(a) Vibration JSS 55555Test 28 533 Hz
(b) High Temperature JSS 55555Test 17 550 C for 16 Hrs.
Procedure 5, Test
Condition ’G’
(c) Damp Heat JSS 55555Test 10 400 C – 95% RH for 16
Hrs.
(d) Drip proof JSS 55555Test 11 Vertical Water drip 1 mtr
height for 15 min.
(e) Mould Growth JSS 55555Test 21 290 C 90% RH mould
growth chamber for 28
days.
(f) Bump JSS 55555Test 5 1000 bumps40G,
6m/sec
(g) Shock/Impact As per BR 3021, As per laid down
NSS II grade. specifications
(h) Inclination/Tilt AS per NES
1004(Data sheet:36)
(j) EMI/EMC MIL STD 461C/E
23.1 Ship Motion:
11
Operating 0 to 550 C
(b) Relative Humidity Up to 100%
at 38 deg C
(c) Time Continuous Up to 48 hours.
24. Painting. Powder coating as per IS 5 code 632 grey colour.
25. Tally & Diagram Plate.
25.1 All tally and diagram plate shall be of aluminum oxidized .
25.3 Size of tally plate, diagram plate, danger plate etc. and their letters shall
conform to NES 723.
25.4 The information mentioned below are to be indicated on the tally plate:
(a) Rating in KVA
(b) No load voltage (HV & LV)
(c) Current in Amps(HV & LV)
(d) Percentage Impedance
(e) Total weight
(f) Frequency
(g) Class of Insulation
(h) Temperature rise C deg
(j) Type of cooling
(k) Purchase order and date
(l) Year of manufacturing
(m) Makers serial number
(n) Terminal plate indicating various output voltages
(p) Earth Terminal
(q) Danger tally voltage (RED)
(r) Connection diagram plate
12
28. Information to be supplied while Tendering. The manufacture should
furnish the under mentioned details of transformer at the time of tendering:
(b) Voltage ratio at noload.
(c) Noload current
(d) Fullload losses(fixed, copper and total)
(e) Efficiency (at full load UPF and halfload UPF)
(f) Regulation (at UPF and 0.8 PF lagging)
(g) Method of voltage control to meet any special requirements for
regulation which cannot be obtained by the inherent regulation of the
transformer.
(h) Maximum allowable temperature rise in deg C.
(j) Output at abnormal ambient temperature, if applicable.
(k) Class of insulation.
29. A brief specification of the equipment offered is to be submitted, together
with confirmation that all the transformers will conform in all respects to the
Procurement Specifications and relevant specifications or details of all proposed
departures from the requirements of these documents.
31. Binding Drawings and Documents. The format and content of
documentation being provided should be as per JSS 025101 and EEDS048.
In addition to the hard copy the documents be also supplied in the form of CD
ROM. Documentation shall be presented as per the table below.
(e) As fitted drawings
(i) Velographs 02 “
13
(ii) Paper Prints 13 “
31.1 Binding Drawings. Following binding drawings are to be submitted to the
designated authorities for approval:
(a) Overall dimension of the equipment
(b) Mounting arrangement
(c) CG of the equipment
(d) Terminal connection details
(e) Circuit diagram details as per clause 1002 of NES 535.
(f) Part list indicating description, qty, part number, material and
makers name etc.
(g) List of tally plates.
(h) Details of S/V mounts.
(j) Details of Design Specifications.
(k) Details of windings (Gauge, no. of turns, weight, insulating material
etc.)
32. Product Support. The manufacturer should submit product support
certificate for a period of 15 years.
33. On Board and Base & Depot spares.
(a) All spares required for exploitation up to 2 years.
(b) One set of generalpurpose maintenance tools.
(c) One set of special tools required for disassembling /assembling of
components to carry out repair by replacement.
14
(c) EED/DGS/1535/R6 Cable Glands
(d) IS 5 Powder coating painting
(e) NES 723 Tally Plate
(f) DEF STAN 08107 Earthing
(g) MIL STD 461 C/E EMI/EMC
(h) DEF STAN 07224 Material & finishes
(j) DEF STAN 07226 Electrical Testing
(k) NES 581 Electronic components Practice.
(l) NES 539 Guide to design the supply systems for
Portable equipment
(m) NES 535 Requirements for transformers for power
Services.
(n) NES 537 Requirements for testing of the transformers.
(p) NES 501 General requirements for the design of
electrotechnical equipment.
(q) NES 511 Requirements of electrical testing of equipt.
(r) BS 3399 Specification for transformers for use in ships.
(s) BS 5629 Insulating varnish containing solvent.
(t) IS Equipment Enclosure.
(u) EEDS048/ Preparation of documents and drawings.
JSS025101