46TMSS07R0 DC-DC Convertors

Download as pdf or txt
Download as pdf or txt
You are on page 1of 18

u

-
1
Q
il.. ~~~~~~t4S~1
a..
« Saudi Electricity Company
I--

W
()

Q
b
0:
0

..11-11
Cl)
z
0
ReVIsionno. 0
en

0::
Z
0
i=
a..
0: DC-DC CONVERTER
()
Cl)
w
Q 48 VOLTS OUTPUT

PROPRIETARYINFORMATION

This document contains proprietary information developed by and for exclusive use of Saudi
2as
Electricity Company. Your acceptance of the document is an acknowledgement that it must be used
Q
for the identified purpose/application and during the period indicated. It cannot be used or copied for
any other purposes nor released to others without prior written authorization of Saudi Electricity
Company. Saudi Electricity Company will not be responsible for misuse and/or misapplication, and
ci N (") any harm resulting therefrom. Saudi Electricity Company also reserves the right to take any
Z
necessary actions to protect its interest against unauthorized use.

ORIGINATED BY CERTIFIED BY APPROVED BY

<t..
Engr. Ahmed M. AI-Zahrani Engr. Abdullah M. AI-Garni Engr. Saleh N. AI-Sohaibani
Division Manager (A), Department Manager, Executive Director,
Transmission Substation Transmission Standards & Engineering &Projects
Specifications Specifications
Date of Approval: April 29, 2009

46TMSS07RO/ASD PAGE NO. 1 OF 18


TRANSMISSION MATERIALS STANDARD SPECIFICATION 46-TMSS-07, Rev. 0

TABLE OF CONTENTS

1.0 SCOPE

2.0 CROSS REFERENCES

3.0 APPLICABLE CODES AND STANDARDS

4.0 DESIGN AND CONSTRUCTION REQUIREMENTS

4.1 General
4.2 Performance Characteristics and Ratings
4.3 Controls and Protection
4.4 Static Indications, Alarms and Instrumentation
4.5 Construction
4.6 Wiring
4.7 Nameplate(s)

5.0 TESTS

6.0 DATA SCHEDULE

46TMSS07R0/ASD Date of Approval: April 29, 2009 PAGE NO. 2 OF 18


TRANSMISSION MATERIALS STANDARD SPECIFICATION 46-TMSS-07, Rev. 0

1.0 SCOPE

This SEC Transmission Material Standard Specification (TMSS) specifies the minimum
technical requirements for design, engineering, manufacture, inspection, testing and
performance of 48 Volt output DC-DC Converter intended to be used in the
telecommunication system of the Saudi Electricity Company, Saudi Arabia.

2.0 CROSS REFERENCES

This Material Standard Specification shall always be read in conjunction with SEC General
Specification No. 01-TMSS-01, titled "General Requirements for All Equipment/Materials",
which shall be considered as an integral part of this TMSS.

This TMSS shall also be read in conjunction with SEC Purchase Order or Contract
Schedules for project, as applicable.

3.0 APPLICABLE CODES AND STANDARDS

The latest revision of the following Codes and Standards shall be applicable for the
equipment/material covered in this TMSS. In case of conflict, the vendor/manufacturer may
propose equipment/material conforming to one group of Industry Codes and Standards
quoted hereunder without jeopardizing the requirements of this TMSS.

3.1 IEC 60146 Semi-Conductor Converters – General Requirements and Line


(All Parts) Commutated Converters

3.2 IEC 60478 Stabilized Power Supplies, DC Output


(All Parts)

3.3 IEC 60529 Degrees of Protection Provided by Enclosure (IP Codes)

3.4 IEC 60950 Information Technology Equipment Safety


(All Parts)

3.5 IEC 61204 Low-voltage Power Supplies, DC Output


(All Parts)

3.6 ANSI C63.4 Measurement of Radio Noise Emission from low Voltage
Electrical and Electronic Equipment in the Range of 9 kHz to
40 GHz.

3.7 ANSI/ Communication Type Battery Charger


NEMA PE7

3.8 NEMA 250 Enclosures for Electrical Equipment (1000 Volts max.)

3.9 NFPA 70 National Electrical Code (NEC)

46TMSS07R0/ASD Date of Approval: April 29, 2009 PAGE NO. 3 OF 18


TRANSMISSION MATERIALS STANDARD SPECIFICATION 46-TMSS-07, Rev. 0

4.0 DESIGN AND CONSTRUCTION REQUIREMENTS

4.1 General

4.1.1 The DC-DC converter shall be switched mode type suitable for application in
the 48 Vdc power supply system for communication installation. Typical
installations include telecommunication, fiber optic transmission systems,
PABX telephone systems, radio, paging systems etc.

4.1.2 The DC-DC converter shall be suitably designed for the utility
telecommunication system having positive terminal grounded.

4.1.3 The converter system shall be capable of supplying maximum continuous


D.C. load of the communication system.

4.1.4 The converter circuitry shall be of modular design. The printed circuit cards
shall have plug-in or slide-in type construction. All printed circuit boards
shall be coated with a solderable polyurethane varnish.

4.1.5 It shall be ensured that harmonics due to switching and commutations are not
reflected in the input and the output of the converter.

4.1.6 The DC-DC converter shall be, normally, either operated in parallel with an
AC-DC converter i.e. rectifier (without any 48 V telecommunication battery)
or operated in parallel with DC-DC converter on the equal current sharing
basis. The load sharing mismatch shall not exceed 5% of the actual load
current. However, when the mode of operation is other than the parallel one,
it shall be specified in the Data Schedule, SEC Purchase Order or Contract
Schedules for project, as applicable.

4.2 Performance Characteristics and Ratings

4.2.1 The nominal output DC voltage of the converter system shall be 48 volts. The
range of D.C. voltage (voltage window) permitted for operation of
telecommunication system shall be 42 to 56 volts.

4.2.2 The DC-DC converter shall be fed from the substation D.C. distribution
board having 125 +10%, -20% VDC or 110 +15%, -10% unless otherwise
specified in the Data Schedules, SEC Purchase Order or Contract Schedules
for project, as applicable.

4.2.3 The rated output current of DC-DC converter shall be selected on the basis of
the total continuous load of the telecommunication system. However, the
rated output current of the converter shall not be less than 30 A upto 132 kV
substations and 50 A upto 380 kV substations unless otherwise specified in
the Data Schedule, SEC Purchase Order or Contract Schedules for project, as
applicable.
The power supply shall be capable of continuous operation without derating
at the maximum ambient operating temperature based on the maximum

46TMSS07R0/ASD Date of Approval: April 29, 2009 PAGE NO. 4 OF 18


TRANSMISSION MATERIALS STANDARD SPECIFICATION 46-TMSS-07, Rev. 0

ambient temperature stated in 01-TMSS-01, at maximum power output under


least favorable conditions in the convection cooled environment.

4.2.4 The output D.C. voltage shall be adjustable from 80 % to 120 % of the rated
output voltage with 1 % resolution.

4.2.5 The output voltage shall be automatically and continuously held constant to
within ±0.5% of the voltage setting at any load from no-load to full rated load
(0 to 100%), with simultaneous D.C. input voltage variation specified in the
Data Schedule and under the specified ambient temperature conditions given
in 01-TMSS-01.

4.2.6 The maximum voltage transient shall remain within ±5% of initial steady
state voltage for sudden load changes (application or removal) from 10 % to
100 % of the rated output. Recovery to steady state regulation of ±0.5% shall
take place within 50 milliseconds.

4.2.7 The output ripple and switching noise including spikes shall not exceed 30
mVrms over a bandwidth of 30 MHz.

4.2.8 The temperature coefficient, i.e. change in output voltage against temperature
variation, shall not exceed 0.02 %/ºC.

4.2.9 The converter start-up time for the output voltage to enter the specified
permissible band shall be within 2-5 seconds.

4.2.10 No overshoot of output shall occur at switch-on and switch-off of the


converter. No over-voltage condition shall happen at any load and any source
voltage between zero and maximum.

4.2.11 The output of the converter shall not change its polarity at any time.

4.2.12 The converter shall meet the requirements of electro-magnetic compatibility


(EMC) as per IEC 61204-3 or equivalent standard.

4.2.13 The converter shall meet the safety requirements as per IEC 61204-7 and IEC
60950 or equivalent standard.

4.2.14 The maximum acoustic noise shall not exceed 60 dBA (A-weighting)
measured as per clause 5 of IEC 61204 Edition 1.1.

4.2.15 Input, output and ground shall be galvanically isolated.

4.2.16 Input transient withstand voltage shall be 2 kV minimum. (also refers to Para
4.3.3).

46TMSS07R0/ASD Date of Approval: April 29, 2009 PAGE NO. 5 OF 18


TRANSMISSION MATERIALS STANDARD SPECIFICATION 46-TMSS-07, Rev. 0

4.3 Controls and Protection

4.3.1 The converter shall be adequately protected against short circuits by


automatic circuit breakers provided at both input and output circuits. The
circuit breakers shall be fitted with thermo-magnetic releases and auxiliary
contacts for remote alarm initiation.

4.3.2 Both the power supply units i.e. DC-DC converter and AC-DC
converter/DC-DC converter shall be arranged in such a way that the unit
which has been tripped due to input supply failure will automatically resume
the operation on restoration of the input voltage.

4.3.3 The converter shall be protected against voltage or current transients by the
use of appropriate surge equipment.

4.3.4 An automatic and adjustable current limiting device shall be provided to


protect the converter against continuous overloads and direct short circuits
without tripping it out of circuit for limited time duration. The minimum
setting range shall be from 90% to 110% of the rated D.C. current of the
converter. Constant voltage characteristics shall be restored automatically at
the end of overloads/short circuits. The current limiting stability shall be
within ±1 %.

4.3.5 The converter shall be furnished with a current walk-in control circuitry to
limit the input inrush current upon application of input voltage.

4.3.6 The converter shall be protected against input and output polarity inversion.

4.3.7 Thermal protection for high temperature shutdown shall be provided. It shall
protect the unit from excessive ambient operating temperature.

4.3.8 The over-voltage protection shall be provided. The setting range of this
protection shall be 110 % to 120 % of the rated output voltage.

4.3.9 Output over-current protection shall be provided in accordance with clause


4.3.4 here above.

4.3.10 Protection of power supply and/or connected equipment against excessively


low output voltage shall be provided.

4.3.11 Protection of converter against current fed back into the power supply by the
load i.e. to prevent reverse flow of current during parallel operation shall be
provided.

4.3.12 When specified in Data Schedule, the converter shall also be provided with
remote programming (remote control) facility.

46TMSS07R0/ASD Date of Approval: April 29, 2009 PAGE NO. 6 OF 18


TRANSMISSION MATERIALS STANDARD SPECIFICATION 46-TMSS-07, Rev. 0

4.3.13 When specified in Data Schedule, remote sensing provision shall be made for
the output in terms of maximum total voltage drop of 500 mV per D.C.
output line.

4.4 Status Indications, Alarms and Instrumentations

4.4.1 General

a. The alarm signals shall be triggered via a set of Form 'C' dry contacts
which shall be used to light LED indicators on the converter panel,
give a remote alarm (through a common Form 'C' dry contact rated
continuous current of 2 A min. i.e. class 2 as per IEC 62271-1)
indication or operate a remote audible alarm as applicable. Audible
alarm on the converter panel shall be provided if specified in the Data
Schedule.

b. All the status and alarm indicators mentioned hereunder shall be high
intensity LEDs.

c. All alarm relays shall be self-reset unless otherwise specified or


required operationally.

4.4.2 Status Indications

The following status indicators shall be provided

a. Mains D.C. Power On (Green)

b. D.C output available (Green)

c. Current limit (Amber)

4.4.3 Alarm Indications

The following alarm indicators shall be provided. All alarm indicators shall
be connected to a separate relay card with an individual relay for each alarm.
All indications shall be in Red.

a. Main D.C. supply fail

b. D.C. output circuit breaker trip

c. Low output D.C. voltage

d. High output D.C. voltage

e. Over-current trip

f. High ripple

46TMSS07R0/ASD Date of Approval: April 29, 2009 PAGE NO. 7 OF 18


TRANSMISSION MATERIALS STANDARD SPECIFICATION 46-TMSS-07, Rev. 0

g. High temperature

h. Loss of forced cooling fan (if forced cooling is accepted by SEC)

Alarms in items c, d and e above shall be provided with time delay to allow
for any transient as per manufacturer's recommendation.

4.4.4 Panel Mounted Equipment/Instruments

The converter shall have the following components mounted on the front
panel. Each component shall be labeled for identification:

a. Input and output circuit breakers as per clause 4.3.1

b. Analog or digital (3 digit), 96 x 96 mm, D.C. ammeter with ±2% full-


scale accuracy and of range 0-150% of maximum rated output
current.

c. Analog or digital (3 digit), 96 x 96 mm, D.C. voltmeter with ±2%


full-scale accuracy, and of range consistent with the maximum output
DC voltage plus 20 %.

d. Controls for the following functions:

i. Current limit adjust (90-110%)


ii. Over-voltage trip adjust (110-120 %)
iii. Low voltage trip adjust (80-100 %)
iv. High ripple alarm adjust (>30 mV)

e. Test push button

f. Status indicators as per clause 4.4.2

g. Alarm indicators as per clause 4.4.3

h. Any other device such as manual resetting device for alarm indication
when provided.

i. Any additional accessory requirements specified in Data Schedule.

4.5 Construction

4.5.1 The converter shall be designed as a free standing or wall mounted


equipment as specified in Data Schedule. The enclosure shall be fabricated
from minimum of 2 mm thick steel or alloy of aluminum or zinc, suitably
braced & supported. Suitable stiffeners shall be provided for all weight
bearing members. The execution and dimensions of the enclosure shall be
subject to SEC approval.

46TMSS07R0/ASD Date of Approval: April 29, 2009 PAGE NO. 8 OF 18


TRANSMISSION MATERIALS STANDARD SPECIFICATION 46-TMSS-07, Rev. 0

4.5.2 Unless otherwise specified, the degree of protection for the converter
enclosure shall be as per 01-TMSS-01.

4.5.3 The terminals shall be adequately marked and identified. All the markings
shall be permanent.

4.5.4 The converter shall be adequately ventilated for self-cooling by natural air
convection. Forced cooling by integral fan shall be subject to prior approval
by SEC. The loss of forced cooling, if required, shall be detected by a
thermostat or air flow switch to provide alarm indication (also refers to Para
4.3.7, 4.4.3.g and 4.4.3.h).

4.5.5 Provision shall be made for grounding of the panel and a bolted connector
shall be provided to accommodate 35 mm² copper grounding conductor. All
bolted parts shall use suitable washer to ensure electrical continuity of the
structure.

4.5.6 SEC approved schematic diagram of the converter identifying various


components and referring to the appropriate drawings and erection
instructions shall be affixed to the inside of the cabinet/enclosure access door.
The diagram shall be marked on durable non-fading material suitable for the
specified climatic conditions.

4.5.7 Panel shall be provided with door-switch controlled illumination lamp, one
single-phase, 3-pin receptacles and thermostat controlled anti-condensation
heater with overriding manual switch rated for A.C. voltage specified in the
Data Schedule.

4.5.8 Appropriate identification in the form of a nameplate(s) shall be provided on


each converter/component where it is safe and reasonably feasible. These
nameplates shall be clearly visible, engraved type, of appropriate size and
attached to the panel by stainless steel screws or rivets.

4.6 Wiring

4.6.1 All wirings within the converter shall be installed and tested at the factory
unless otherwise specified. The wiring shall be 600/1000V insulated, tinned,
annealed, stranded copper conductor of minimum size 2.5 mm2. The cable
insulation shall be heat resistant and flame retardant, rated 90 °C maximum
operating temperature, type SIS as listed in ANSI/NFPA 70 or approved
equivalent. Electronic and low signal wiring shall be of manufacturer's
standard.

4.6.2 The supply circuit terminals shall be fitted with non-flammable, transparent
plastic covers to prevent accidental human contact with live parts and/or
short circuits. The insulation shall be rated for 600 V and 105 °C minimum.

46TMSS07R0/ASD Date of Approval: April 29, 2009 PAGE NO. 9 OF 18


TRANSMISSION MATERIALS STANDARD SPECIFICATION 46-TMSS-07, Rev. 0

4.7 Nameplate(s)

4.7.1 The converter shall bear a nameplate fixed on the front side of the panel. The
plate shall be marked in English and Arabic with the following minimum
information:

a. The words "DC-DC CONVERTER"

b. Model Number and Type

c. Manufacturer's Name/Country and Trade Mark

d. Year of Manufacture (month and year)

e. Manufacturer's Serial Number

f. Rated DC Input Voltage

g. Rated DC Input Current

h. Rated DC Output Voltage

i. Rated DC Output Current

j. Range of Adjustments for Current Limiter

k. SEC Purchase Order Number/Contract No./Job Order No.

l. 46-TMSS-07, Rev.0

4.7.2 The nameplate material shall be stainless steel or other non-corrodible


material, but shall not include plastic or aluminum and shall be fastened to
the equipment by stainless steel screws or rivets. The markings shall be
imprinted or etched in black and shall be non-fading.

5.0 TESTS

All test results shall be provided for review and acceptance by SEC.

5.1 Type (Design) Tests

All type (design) tests prescribed in the relevant IEC or equivalent ANSI/IEEE
standard shall be performed on the representative unit or on the first unit of every
new design or rating to be supplied to SEC.

46TMSS07R0/ASD Date of Approval: April 29, 2009 PAGE NO. 10 OF 18


TRANSMISSION MATERIALS STANDARD SPECIFICATION 46-TMSS-07, Rev. 0

In lieu of the actual type (design) tests, certified test reports of type (design) tests
performed on an identical unit may be submitted to SEC for review and approval
during bidding stage.

5.2 Routine (Production) Tests

All routine (production) tests prescribed in the relevant IEC or equivalent


ANSI/IEEE standard shall be performed on all the equipment covered in this TMSS.

5.3 Special/Optional Tests

Any special/optional tests specified in Data Schedule shall be performed as per the
applicable standards.

46TMSS07R0/ASD Date of Approval: April 29, 2009 PAGE NO. 11 OF 18


TRANSMISSION MATERIALS STANDARD SPECIFICATION 46-TMSS-07, Rev. 0

6.0 DATA SCHEDULE

DC-DC CONVERTER, 48 VOLTS OUTPUT

SEC Enquiry No. Date:

SEC Purchase Order Date:


No.
or Contract No.

SEC PTS No./Project Title with J.O. No.

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

3.0 APPLICABLE CODES AND STANDARDS

Applicable industry standards *

4.0 DESIGN AND CONSTRUCTION REQUIREMENTS

Type designation of converter *

Converter installation within


Air conditioned/
Non-air conditioned area

Application (telecommunication/ Fiber


optic/ PABX/ radio/ paging)

Installation
Free standing or wall mounted

4.1 General

Type of converter
Switched mode(SM)/Conventional SM

Second power supply system


AC-DC converter (rectifier)/ DC-DC
Converter

Voltage window for telecom system (V) 42-56

'A'- SEC SPECIFIED DATA/PARAMETER.


'B'- BIDDER/SUPPLIER/VENDOR/CONTRACTOR PROPOSED DATA/PARAMETERS.
'C'- REMARKS SUPPORTING THE PROPOSED DEVIATION IN COLUMN 'B'.
(*)- DATA/PARAMETER TO BE PROVIDED/PROPOSED BY THE BIDDER/SUPPLIER/
VENDOR/CONTRACTOR IN COLUMN 'B'.
46TMSS07R0/ASD Date of Approval: April 29, 2009 PAGE NO. 12 OF 18
TRANSMISSION MATERIALS STANDARD SPECIFICATION 46-TMSS-07, Rev. 0

6.0 DATA SCHEDULE

DC-DC CONVERTER, 48 VOLTS OUTPUT

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

4.1 (Continued)

Mode of operation with second supply


a Parallel/standby/independent Parallel
b Load sharing basis in parallel operation Equal

4.2 Performance Characteristics and Ratings

Rated output DC
a Voltage (V) 48
b Current (A) *
c Power at 50 ºC (W) *

Ambient operating temperature


a Low (ºC) *
b High without derating (ºC) *
c High with derating (ºC) *
d Derating rate (%/ºC) *

Temperature coefficient (%/ºC) 0.02

Storage & transit


a Ambient temperature range (ºC-ºC) *
b Relative humidity (%) *

Input DC supply
a Voltage (V)
b Voltage tolerance (± %)
c Current (A) *
d Peak inrush current (A) *
Source current harmonics distortion
e *
factor (THD) (%)
f Efficiency (%) *

Regulation
a Source regulation (%) *
b Load regulation (%) *
c Load change for 'b' (%) 0 - 100
d Total regulation (%) ± 0.5

46TMSS07R0/ASD Date of Approval: April 29, 2009 PAGE NO. 13 OF 18


TRANSMISSION MATERIALS STANDARD SPECIFICATION 46-TMSS-07, Rev. 0

6.0 DATA SCHEDULE

DC-DC CONVERTER, 48 VOLTS OUTPUT

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

4.2 (Continued)

Adjustability of voltage output


a Span (%) 80 - 120
b Resolution (%) 1

Ripple and switching noise including spikes


30
(mVrms)

Cross regulation, if applicable


a Cross regulation (%) *
b Load change (%) *

Hold-up time (ms) *

Start-up time (s) 2-5

Turn-on/turn-off overshoot (%) None

Transient response to load current changes


a Voltage deviation (%) ±5
b Recovery time (ms) 50
c Load change (%) 10 - 100

Mean-time between failures (Hrs) *

Requirements of safety
a Protection class *
b Over-voltage category *
c Pollution degree *

Acoustic noise:
a Sound level, max. (dBA) 60
b Frequency (Hz) *

Input transient withstand voltage, min. (kV) 2

Galvanic isolation
a Input/output (Vac) *
b Input/ground (Vac) *
c Output/ground (Vac) *

46TMSS07R0/ASD Date of Approval: April 29, 2009 PAGE NO. 14 OF 18


TRANSMISSION MATERIALS STANDARD SPECIFICATION 46-TMSS-07, Rev. 0

6.0 DATA SCHEDULE

DC-DC CONVERTER, 48 VOLTS OUTPUT

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

4.2 (Continued)

Electromagnetic Compatibility (EMC)


Applied standard IEC 61204-3

4.3 Control and Protection

Short circuit rating of input


*
circuit breaker (kA)

Short circuit rating of output


*
circuit breaker (kA)

Surge suppression eqpt. provided? YES

Current limiting feature


Range (%) 90 - 110
Stability (%) 1

Are the following features provided?

a Over-current protection YES

b Output over-voltage protection YES

c Output under-voltage protection YES

Reverse polarity protection for input &


d YES
output

e Reverse current protection YES

f Thermal protection YES

g Current walk-in control circuitry YES

Remote programming type, if required Yes/No


a Resistance programming (ohm/V) *
b Voltage programming (V/V) *
c Digital programming *
Type of interface & communication
d
protocol for 'c' *
46TMSS07R0/ASD Date of Approval: April 29, 2009 PAGE NO. 15 OF 18
TRANSMISSION MATERIALS STANDARD SPECIFICATION 46-TMSS-07, Rev. 0

6.0 DATA SCHEDULE

DC-DC CONVERTER, 48 VOLTS OUTPUT

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

4.3 (Continued)

Remote sensing, if required Yes/No


Max. total voltage drop (mV) 500

4.4 Status indications, alarms and


YES
instrumentations provided as per clause 4.4?
(List out the devices, range set points
and reset feature provided)

Alarm point reset (Self/Manual)

Audible alarm on converter panel required? YES/NO

Auxiliary contact
Rated continuous current (A) *
Class *

4.5 Construction

Converter panel type


(free standing/ wall mounted/rack mounted)

Type of cooling (natural/forced) Natural

Cable entry to panel (top/bottom)

Rated voltage of panel accessories:


- illumination lamp
- receptacle
- heater

Overall dimension (W × H × D) (mm) *

Enclosure material
Steel/aluminum alloy/zinc alloy *

Thickness of sheet metal, min. (mm) *

Weight (kg) *

46TMSS07R0/ASD Date of Approval: April 29, 2009 PAGE NO. 16 OF 18


TRANSMISSION MATERIALS STANDARD SPECIFICATION 46-TMSS-07, Rev. 0

6.0 DATA SCHEDULE

DC-DC CONVERTER, 48 VOLTS OUTPUT

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

4.5 (Continued)

Color shade RAL 7038

5.3 Special/optional Tests

46TMSS07R0/ASD Date of Approval: April 29, 2009 PAGE NO. 17 OF 18


TRANSMISSION MATERIALS STANDARD SPECIFICATION 46-TMSS-07, Rev. 0

6.0 DATA SCHEDULE

DC-DC CONVERTER, 48 VOLTS OUTPUT

A. ADDITIONAL TECHNICAL INFORMATION OR FEATURES TO BE FURNISHED BY


SEC:

B. ADDITIONAL SUPPLEMENTARY DATA OR FEATURES PROPOSED BY


BIDDER/VENDOR/SUPPLIER/CONTRACTOR:

B. OTHER PARTICULARS TO BE FILLED UP BY BIDDER/VENDOR/SUPPLIER/


CONTRACTOR:

Actual Manufacturer Vendor/Supplier/


of Equipment/Material Contractor

Name of the Company


Location and address

Name and Signature of


authorized
representative
and date

Official Seal/Stamp
of the Company &
Date

46TMSS07R0/ASD Date of Approval: April 29, 2009 PAGE NO. 18 OF 18