0: DC-DC CONVERTER
()
Cl)
w
Q 48 VOLTS OUTPUT
PROPRIETARYINFORMATION
This document contains proprietary information developed by and for exclusive use of Saudi
2as
Electricity Company. Your acceptance of the document is an acknowledgement that it must be used
Q
for the identified purpose/application and during the period indicated. It cannot be used or copied for
any other purposes nor released to others without prior written authorization of Saudi Electricity
Company. Saudi Electricity Company will not be responsible for misuse and/or misapplication, and
ci N (") any harm resulting therefrom. Saudi Electricity Company also reserves the right to take any
Z
necessary actions to protect its interest against unauthorized use.
<t..
Engr. Ahmed M. AI-Zahrani Engr. Abdullah M. AI-Garni Engr. Saleh N. AI-Sohaibani
Division Manager (A), Department Manager, Executive Director,
Transmission Substation Transmission Standards & Engineering &Projects
Specifications Specifications
Date of Approval: April 29, 2009
TABLE OF CONTENTS
1.0 SCOPE
4.1 General
4.2 Performance Characteristics and Ratings
4.3 Controls and Protection
4.4 Static Indications, Alarms and Instrumentation
4.5 Construction
4.6 Wiring
4.7 Nameplate(s)
5.0 TESTS
1.0 SCOPE
This SEC Transmission Material Standard Specification (TMSS) specifies the minimum
technical requirements for design, engineering, manufacture, inspection, testing and
performance of 48 Volt output DC-DC Converter intended to be used in the
telecommunication system of the Saudi Electricity Company, Saudi Arabia.
This Material Standard Specification shall always be read in conjunction with SEC General
Specification No. 01-TMSS-01, titled "General Requirements for All Equipment/Materials",
which shall be considered as an integral part of this TMSS.
This TMSS shall also be read in conjunction with SEC Purchase Order or Contract
Schedules for project, as applicable.
The latest revision of the following Codes and Standards shall be applicable for the
equipment/material covered in this TMSS. In case of conflict, the vendor/manufacturer may
propose equipment/material conforming to one group of Industry Codes and Standards
quoted hereunder without jeopardizing the requirements of this TMSS.
3.6 ANSI C63.4 Measurement of Radio Noise Emission from low Voltage
Electrical and Electronic Equipment in the Range of 9 kHz to
40 GHz.
3.8 NEMA 250 Enclosures for Electrical Equipment (1000 Volts max.)
4.1 General
4.1.1 The DC-DC converter shall be switched mode type suitable for application in
the 48 Vdc power supply system for communication installation. Typical
installations include telecommunication, fiber optic transmission systems,
PABX telephone systems, radio, paging systems etc.
4.1.2 The DC-DC converter shall be suitably designed for the utility
telecommunication system having positive terminal grounded.
4.1.4 The converter circuitry shall be of modular design. The printed circuit cards
shall have plug-in or slide-in type construction. All printed circuit boards
shall be coated with a solderable polyurethane varnish.
4.1.5 It shall be ensured that harmonics due to switching and commutations are not
reflected in the input and the output of the converter.
4.1.6 The DC-DC converter shall be, normally, either operated in parallel with an
AC-DC converter i.e. rectifier (without any 48 V telecommunication battery)
or operated in parallel with DC-DC converter on the equal current sharing
basis. The load sharing mismatch shall not exceed 5% of the actual load
current. However, when the mode of operation is other than the parallel one,
it shall be specified in the Data Schedule, SEC Purchase Order or Contract
Schedules for project, as applicable.
4.2.1 The nominal output DC voltage of the converter system shall be 48 volts. The
range of D.C. voltage (voltage window) permitted for operation of
telecommunication system shall be 42 to 56 volts.
4.2.2 The DC-DC converter shall be fed from the substation D.C. distribution
board having 125 +10%, -20% VDC or 110 +15%, -10% unless otherwise
specified in the Data Schedules, SEC Purchase Order or Contract Schedules
for project, as applicable.
4.2.3 The rated output current of DC-DC converter shall be selected on the basis of
the total continuous load of the telecommunication system. However, the
rated output current of the converter shall not be less than 30 A upto 132 kV
substations and 50 A upto 380 kV substations unless otherwise specified in
the Data Schedule, SEC Purchase Order or Contract Schedules for project, as
applicable.
The power supply shall be capable of continuous operation without derating
at the maximum ambient operating temperature based on the maximum
4.2.4 The output D.C. voltage shall be adjustable from 80 % to 120 % of the rated
output voltage with 1 % resolution.
4.2.5 The output voltage shall be automatically and continuously held constant to
within ±0.5% of the voltage setting at any load from no-load to full rated load
(0 to 100%), with simultaneous D.C. input voltage variation specified in the
Data Schedule and under the specified ambient temperature conditions given
in 01-TMSS-01.
4.2.6 The maximum voltage transient shall remain within ±5% of initial steady
state voltage for sudden load changes (application or removal) from 10 % to
100 % of the rated output. Recovery to steady state regulation of ±0.5% shall
take place within 50 milliseconds.
4.2.7 The output ripple and switching noise including spikes shall not exceed 30
mVrms over a bandwidth of 30 MHz.
4.2.8 The temperature coefficient, i.e. change in output voltage against temperature
variation, shall not exceed 0.02 %/ºC.
4.2.9 The converter start-up time for the output voltage to enter the specified
permissible band shall be within 2-5 seconds.
4.2.11 The output of the converter shall not change its polarity at any time.
4.2.13 The converter shall meet the safety requirements as per IEC 61204-7 and IEC
60950 or equivalent standard.
4.2.14 The maximum acoustic noise shall not exceed 60 dBA (A-weighting)
measured as per clause 5 of IEC 61204 Edition 1.1.
4.2.16 Input transient withstand voltage shall be 2 kV minimum. (also refers to Para
4.3.3).
4.3.2 Both the power supply units i.e. DC-DC converter and AC-DC
converter/DC-DC converter shall be arranged in such a way that the unit
which has been tripped due to input supply failure will automatically resume
the operation on restoration of the input voltage.
4.3.3 The converter shall be protected against voltage or current transients by the
use of appropriate surge equipment.
4.3.5 The converter shall be furnished with a current walk-in control circuitry to
limit the input inrush current upon application of input voltage.
4.3.6 The converter shall be protected against input and output polarity inversion.
4.3.7 Thermal protection for high temperature shutdown shall be provided. It shall
protect the unit from excessive ambient operating temperature.
4.3.8 The over-voltage protection shall be provided. The setting range of this
protection shall be 110 % to 120 % of the rated output voltage.
4.3.11 Protection of converter against current fed back into the power supply by the
load i.e. to prevent reverse flow of current during parallel operation shall be
provided.
4.3.12 When specified in Data Schedule, the converter shall also be provided with
remote programming (remote control) facility.
4.3.13 When specified in Data Schedule, remote sensing provision shall be made for
the output in terms of maximum total voltage drop of 500 mV per D.C.
output line.
4.4.1 General
a. The alarm signals shall be triggered via a set of Form 'C' dry contacts
which shall be used to light LED indicators on the converter panel,
give a remote alarm (through a common Form 'C' dry contact rated
continuous current of 2 A min. i.e. class 2 as per IEC 62271-1)
indication or operate a remote audible alarm as applicable. Audible
alarm on the converter panel shall be provided if specified in the Data
Schedule.
b. All the status and alarm indicators mentioned hereunder shall be high
intensity LEDs.
The following alarm indicators shall be provided. All alarm indicators shall
be connected to a separate relay card with an individual relay for each alarm.
All indications shall be in Red.
e. Over-current trip
f. High ripple
g. High temperature
Alarms in items c, d and e above shall be provided with time delay to allow
for any transient as per manufacturer's recommendation.
The converter shall have the following components mounted on the front
panel. Each component shall be labeled for identification:
h. Any other device such as manual resetting device for alarm indication
when provided.
4.5 Construction
4.5.2 Unless otherwise specified, the degree of protection for the converter
enclosure shall be as per 01-TMSS-01.
4.5.3 The terminals shall be adequately marked and identified. All the markings
shall be permanent.
4.5.4 The converter shall be adequately ventilated for self-cooling by natural air
convection. Forced cooling by integral fan shall be subject to prior approval
by SEC. The loss of forced cooling, if required, shall be detected by a
thermostat or air flow switch to provide alarm indication (also refers to Para
4.3.7, 4.4.3.g and 4.4.3.h).
4.5.5 Provision shall be made for grounding of the panel and a bolted connector
shall be provided to accommodate 35 mm² copper grounding conductor. All
bolted parts shall use suitable washer to ensure electrical continuity of the
structure.
4.5.7 Panel shall be provided with door-switch controlled illumination lamp, one
single-phase, 3-pin receptacles and thermostat controlled anti-condensation
heater with overriding manual switch rated for A.C. voltage specified in the
Data Schedule.
4.6 Wiring
4.6.1 All wirings within the converter shall be installed and tested at the factory
unless otherwise specified. The wiring shall be 600/1000V insulated, tinned,
annealed, stranded copper conductor of minimum size 2.5 mm2. The cable
insulation shall be heat resistant and flame retardant, rated 90 °C maximum
operating temperature, type SIS as listed in ANSI/NFPA 70 or approved
equivalent. Electronic and low signal wiring shall be of manufacturer's
standard.
4.6.2 The supply circuit terminals shall be fitted with non-flammable, transparent
plastic covers to prevent accidental human contact with live parts and/or
short circuits. The insulation shall be rated for 600 V and 105 °C minimum.
4.7 Nameplate(s)
4.7.1 The converter shall bear a nameplate fixed on the front side of the panel. The
plate shall be marked in English and Arabic with the following minimum
information:
l. 46-TMSS-07, Rev.0
5.0 TESTS
All test results shall be provided for review and acceptance by SEC.
All type (design) tests prescribed in the relevant IEC or equivalent ANSI/IEEE
standard shall be performed on the representative unit or on the first unit of every
new design or rating to be supplied to SEC.
In lieu of the actual type (design) tests, certified test reports of type (design) tests
performed on an identical unit may be submitted to SEC for review and approval
during bidding stage.
Any special/optional tests specified in Data Schedule shall be performed as per the
applicable standards.
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Installation
Free standing or wall mounted
4.1 General
Type of converter
Switched mode(SM)/Conventional SM
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.1 (Continued)
Rated output DC
a Voltage (V) 48
b Current (A) *
c Power at 50 ºC (W) *
Input DC supply
a Voltage (V)
b Voltage tolerance (± %)
c Current (A) *
d Peak inrush current (A) *
Source current harmonics distortion
e *
factor (THD) (%)
f Efficiency (%) *
Regulation
a Source regulation (%) *
b Load regulation (%) *
c Load change for 'b' (%) 0 - 100
d Total regulation (%) ± 0.5
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.2 (Continued)
Requirements of safety
a Protection class *
b Over-voltage category *
c Pollution degree *
Acoustic noise:
a Sound level, max. (dBA) 60
b Frequency (Hz) *
Galvanic isolation
a Input/output (Vac) *
b Input/ground (Vac) *
c Output/ground (Vac) *
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.2 (Continued)
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.3 (Continued)
Auxiliary contact
Rated continuous current (A) *
Class *
4.5 Construction
Enclosure material
Steel/aluminum alloy/zinc alloy *
Weight (kg) *
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.5 (Continued)
Official Seal/Stamp
of the Company &
Date