PLC Lab Manual
PLC Lab Manual
PLC Lab Manual
APPLICATIONS
(BE - 2008 Course)
INDEX
Practical
Title of Experiment Page No.
No.
01 (a) Interfacing of lamp and button with PLC for ON/OFF 3-6
operation.
04 15-16
PLC based thermal ON/OFF control
PLC interfaced with SCADA and Status read
05 17-19
/command transfer operation.
Title: Interfacing of lamp and button with PLC for ON/OFF operation.
Aim: To study interfacing of lamp and button with PLC for ON/OFF operation.
Equipments used: -
Theory:
Introduction to plc:
Advantages of PLC:-
3) Speed of operation: Relay takes more time to operation. Speed of PLC is very fast
i.e scan time is very less.
1) Switches:
There are two fundamental uses for switches. First , switches are used for
operator input to send instructions to the control circuit. Second, switches may be
installed on the moving parts of machine to provide automatic to the control system.
2) Push button:
3) Selector switches:
4) Limit Switches:
Normally these switches are not operator accessible. They are activated
by moving parts on the machine. They are usually mechanical switches but can also be
light activated or magnetically operated (such as magnetic by stores and home security
system that sense windows have been opened).
5) Indicator Lamps:
All the control panels include lamps. They tell the operator when
power is applied to the machine and indicate the present operating status of the
machine. The light bulbs used in indicators are generally white; they are usually
colored with lenses. the colors are usually red, green etc, but the other colors are also
available. Red lamps are reserved for safety critical indicators. Green usually indicates
safe conditions and red usually indicate dangerous conditions. The other colors
indicate information not critical to the safe operation of the machine. In this case we
usually flash the lamp continuously on and off
PROCEDURE:
Ladder diagram:
Conclusion:
Experiment no.(1B)
Equipments used: -
Theory:
Follows:
1] ON Delay Timer
3] Retentive Timer
1] On delay timer -
It is used to program a time to begin after the input goes false for
example external cooling fan or a motor which has to run all the time and it is expected
to turn off the fan or motor after 5 min when input is sensed by them. The 5 min is
nothing but OFF Delay Time.
3] Retentive timer –
TON Timer
Table of status bit for TON timer
Procedure :-
Ladder diagram:-
Conclusion:-
Experiment no.2 (A)
Title: Multiple push button operation with delayed lamp for ON/OFF operation
Aim: To study multiple push button operation with delayed lamp for ON/OFF
operation.
Theory:
Push button:
Conclusion:
Experiment no.2 (B)
Title :- Combination of counter & timer for lamp ON/OFF operation.
Aim: To study combination of counter & timer for lamp ON/OFF operation.
Equipments used: -
Theory :-
PLC Counter
1. Up Counter
2. Down Counter
1.Up Counter
Use the count-up instruction if you want a counter to increment one decimal value
each time it register a rung transition from false to true.
PROCEDURE:
Theory/Explanation:-
When the auto button (I: 0.0/6) i.e. (B3:0/6) is selected and set point is given from
screen which is stored in N7:5 temp. Sensed by RTD is given to I/P and it is stored in
N7:1. Here we compare both the set point value and RTD value. When RTD value is
greater than set point heater (O: 0.0/7) is automatically become OFF and if the
temperature goes low heating automatically starts.
When manual button (I: 0.0/7) i.e. (B3:0/6) is selected there is no need to set point
value and heater will turn ON and OFF with the help of manual button only.
SCADA SCREEN:-
Ladder Diagram:-
Conclusion:-
Experiment No:-4
Theory/Explanation:-
In this experiment I/P value (O:0./0.5) i.e. (B3:10/5) is ON when the temperature
Is less than or equal to 25 and the level is less than or equal to 10 at that time O/P value
(O:0/0.6) i.e. (B3:10/6) is OFF.
If level goes high that is greater than or equal to 75 but the temperature is less than
output value is ON but I/P value is still ON it will become OFF when temperature
become greater than or equal to 50.
SCADA SCREEN:-
Ladder Diagram:-
Conclusion:-
Experiment No:-5
Title: - PLC interfaced with SCADA and Status read /command transfer operation.
Aim: - To study PLC interfaced with SCADA and Status read /command transfer
operation.
v) SCADA software:-visualization
(Tm-600)
Theory/Explanation:-
When the button for the input (I:0.0/4) is pressed status of that corresponding I/P will
change to green colour and command for the same i.e. (I:0.0/4) “ON” is also visible.
If it is OFF status of that corresponding I/P will change to red colour and commend for
the same (I:0.0/4) “OFF” is also visible.
SCADA SCREEN:-
Ladder Diagram:-
Conclusion:-
Experiment No:-6
v) SCADA software:-visualization
(Tm-600)
Theory/Explanation:-
In this screen here we are able to read the parameter of PLC i.e. the value of the analog
input (I:1.0) and (I:1.1). These analog input are scaled and the scaled values are stored
in (N7:0) and (N7:1) which indicates the value of TT 101 and LT 101.
SCADA SCREEN:-
Ladder Diagram:-
Conclusion:-
Experiment No:-7
v) SCADA software:-visualization
(Tm-600)
Theory:-
One of the most important implementation of SCADA is alarm. The alarm has just two
digital status point with values alarm or normal. When the requirements of the alarm
are met they are activated. For example and a light glows. The attention of the SCADA
operation is drawn to the system which required to attention by the alarm. To alert the
SCADA operators along with the managers the text messages and Email are sending
along with the alarm activation.
When some of the variables in power station or substation are out of limit, the operator
gets corresponding alarm message. The operator receives alarm signal. By virtue of
fast experience and human reasoning, the control room operator determined cause of
trouble and takes appropriate follow-up action to ensure system security.
The knowledge of single alarm by themselves is often insufficient, and the operators
must be able to draw conclusions from knowing the status and the values of many
other variables. In the case of breaker status values, the operator are provided with
one-line display diagrams have graphic indications of breakers, bus bar, switches,
transformers etc. further, the breaker positions are shown so that a quick accurate
assessment of a switching action can be obtained by looking at the display.
To sound an alarm or to close the trip circuit of circuit-breaker so as to disconnect a
component during an abnormal condition in the component, which include over-load,
under-voltage, temperature rise, unbalanced load, reserve power, under-frequency,
short circuits etc.
Explanation:-
When water level goes low or high or temperature goes low or high the alarm will be
generated and the hooter i.e. (O: 0/11) should turn ON the alarm will be acknowledge
with the button Ack Alarm (B3:6/0)
SCADA SCREEN:-
Ladder Diagram:-
Conclusion:-
Experiment No:-8
v) SCADA software:-visualization
(Tm-600)
Theory/Explanation:-
Trend display is the distributed control system equivalent of chart records. They are a
profile of a process variable showing changes that have been takes place over a period
of time.
The trend display information is valuable to the operator to observe the resent pattern
of operating history. It is valuable to the operator after an upset has occurred, allowing
him to determine which several inter-related variable was the 1st to be affected by the
changing conditions treads over larger periods (over a week or more) can be saved on
floppy disk, storage & displayed when required. The fig. show trend for the
temperature and level. When we touch on any of the temperature indicator block then
this trends window will pop up. In some displays, several trend graphs can be
displayed at once allowing comprising of the history of several variables.
SCADA SCREEN:-
Ladder Diagram:-
Conclusion:-