[ Application note ] How to get communication working between the

relay and VAMPSET

How to get communication working between the relay


and VAMPSET

There are few things which should be checked if there are any problems in
communication between relay and PC (VAMPSET).

1. VAMPSET version

- Download latest version of VAMPSET-tool from our website.

Figure 1.Your current VAMPSET version can be checked from-> Help->About..

Link to latest VAMPSET:

http://www.vamp.fi/In English/Products/Softwares/VAMPSET setting and configuration


tool/Default.aspx

1 ANCOM.EN0010_A
How to get communication working between the [ Application note ]
relay and VAMPSET

2. VAMPSET and relay settings

2.1 Communication speed

- Communication speed should be same in VAMPSET and in relay

- Communication speed can be changed in VAMPSET->Settings->Communication


settings as shown in picture 2.

Figure 2. Setting the communication speed in VAMPSET.

- Relays default communication speed is 38400bps.

- Communication speed can be changed in relays HMI or if connection is already


working between VAMPSET and relay then from: Mimic->local panel display->CONF.

ANCOM.EN0010_A 2
[ Application note ] How to get communication working between the
relay and VAMPSET

Figure 3. Changing relays communication speed

If you haven’t set the configurators password following text will appear:

3 ANCOM.EN0010_A
How to get communication working between the [ Application note ]
relay and VAMPSET

In case shown above:

- Press info button: and then enter

- Set configurators password by using arrow buttons(default is 0002):

- Press enter again

2.2 Communication port

- VAMPSET’s communication port can be set in ->Settings-> Communication settings

- If there is lots of options and you don’t know which is the right one, you could
disconnect the cable from PC and open the Communication settings again and check

ANCOM.EN0010_A 4
[ Application note ] How to get communication working between the
relay and VAMPSET

which COM-port disappeared from the menu or you could go windows ->Control
panel-> System-> Hardware -> Device manager-> Ports (COM&LPT) as shown in
picture 4. If computer gives a very high com-port number for you then you may have
the change it manually to some lower because VAMPSET doesn’t support COM-port
numbers above 25. Changing COM-port number is shown in picture 5.

Figure 4. Communication port settings.

Figure 5. How to change communication port number.

3. Connection cable and adapters

- There is special RS-232 serial cable between PC and relay: VX-003. (connection
diagram in picture 6.)
- VAMP 50-series uses standard: USB A-B cable.

5 ANCOM.EN0010_A
How to get communication working between the [ Application note ]
relay and VAMPSET

Figure 6. The cable between PC and VAMP relay (200 series)

- If USB-Serial adapter is used, there are only 2 adapters which are tested and proven
good by VAMP Ltd.
1. FTDI CHIP ES-U-1001-R100/ US232R-100

2.ATEN USB-to-Serial (RS-232) Converter Model: UC-232A

- USB-Serial adapters driver should also be up to date. Driver can be updated


according picture 7 and 8 if you have internet connection available.

ANCOM.EN0010_A 6
[ Application note ] How to get communication working between the
relay and VAMPSET

Figure 7. How to update USB-Serial adapters driver.

Figure 8. After clicking “Next>”, the updating should begin.

7 ANCOM.EN0010_A
How to get communication working between the [ Application note ]
relay and VAMPSET

4. Connection is working but password isn’t accepted


- Sometimes might happen that connection is successful but for some reason
VAMPSET isn’t accepting any password:

->Try to restart VAMPSET and connect to relay again.

->Try to boot relay (if incorrect password is tried three times-> relay locks itself and
you will have to wait 30 min or boot the relay).

5. “File is incompatible with the device. Cannot connect...”- message on screen


1. Device type is different. For example a file from VAMP260 cannot be sent to
VAMP265. If VAMP260 file is open, VAMPSET cannot connect to VAMP265.

2. The major version number is different. For example V6.21 file cannot be sent to
device, which has V10.55 firmware, because the major version numbers are different
(6<-->10). Version number can be checked from the DEVICE INFO view.

3. The minor version number of the file is greater than the version on device. For
example V6.46 file cannot be sent to device, which has V6.21 firmware, because the
minor version of the file is greater (46 > 21).

Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE © 2018 Schneider Electric Industries SAS - All rights reserved.
Electrical equipment should be installed, operated, serviced,
Phone: +33 (0) 1 41 29 70 00 and maintained only by qualified personnel. No responsibility
Fax: +33 (0) 1 41 29 71 00 is assumed by Schneider Electric for any consequences
www.schneider-electric.com arising out of the use of this material.

Publishing: 09/2018

ANCOM.EN0010_A 8

You might also like