Davidson Fire Station 2 Plumbing Bound Int4

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

PLUMBING SYMBOLS GENERAL PLUMBING NOTES GENERAL NOTES

1.) THE ENTIRE PLUMBING SYSTEM SHALL BE IN ACCORDANCE WITH THE A. DO NOT SHUT DOWN ANY PLUMBING, FIRE PROTECTION, NATURAL GAS,
COMPRESSED AIR QUICK LATEST EDITION OF THE PLUMBING CODE OF NORTH CAROLINA AND OR RELATED SYSTEMS WITHOUT BUILDING OWNER'S PRIOR WRITTEN 455 South Main Street Engineering
W WATER SERVICE (DOMESTIC OR COMBINED) CHECK VALVE DISCONNECT W/ CHECK LOCAL PLUMBING INSPECTOR. APPROVAL. FOLLOW ALL OWNER REQUIREMENTS AND SHUT DOWN Davidson, NC 28036 Architecture
F WATER SERVICE (FIRE PROTECTION ONLY) PROCEDURES AS WELL AS ALL REQUIREMENTS OF THIS PROJECT.
BALANCING VALVE COMPRESSED AIR QUICK P: (704) 439-2931 Environmental
2.) THE EXISTING PIPING INDICATED ON THESE PLANS SHALL BE B.
DOMESTIC COLD WATER DISCONNECT W/O CHECK IF REQUIRED, PROVIDE SHUT DOWNS AND TIE-INS DURING OFF HOURS Planning
VERIFIED IN THE FIELD FOR EXACT LOCATIONS, QUANTITY, AND PIPE
DOMESTIC HOT WATER SUPPLY ANGLE VALVE TO AVOID DISRUPTION OF BUILDING SYSTEMS. COORDINATE ALL SHUT
COMPRESSED AIR SIZES.
DOWN REQUIREMENTS PRIOR TO SUBMITTING BID (INCLUDE ALL
DOMESTIC HOT WATER RECIRCULATION FILTER/WATER SEPARATOR REQUIRED DURING OFF HOURS IN BID). www.labellapc.com
PRESSURE REDUCING VALVE 3.) THE PIPING INDICATED ON THESE PLANS ARE DIAGRAMMATIC. ALL WORK
SAN SANITARY DRAIN/SEWER (ABOVE GRADE) SHALL BE COORDINATED WITH ALL OTHER TRADES PRIOR TO C. PROVIDE ALL WORK IN COMPLIANCE WITH ALL LOCAL, STATE AND FEDERAL
STEAM TRAP INSTALLATION. CONTRACTOR SHALL COORDINATE ROUTING OF ALL CODES. OBTAIN ALL REQUIRED PERMITS.
SAN SANITARY DRAIN/SEWER (BELOW GRADE)
PNEUMATIC VALVE PIPING WITH EXISTING CONDITIONS AND SHALL PROVIDE ANY
ST D. PROVIDE ALL REQUIRED EXCAVATION, BACKFILL AND COMPACTION FOR
STORM DRAIN SEWAGE (ABOVE GRADE) NECESSARY OFFSETS, REROUTING, TEES, ELBOWS, ETC. REQUIRED FOR
PNEUMATIC CONTROL VALVE (3 WAY) PUMP (SCHEMATIC) ALL UNDERGROUND WORK.
ST STORM DRAIN SEWAGE (BELOW GRADE) A COMPLETE AND COORDINATED INSTALLATION.
E. FIELD VERIFY EXACT LOCATION, DEPTH, COMPOSITION AND CONDITION OF
SST SECONDARY STORM DRAIN SEWAGE (ABOVE GRADE) 4.) ALL PIPING, VALVES AND SYSTEMS AS REQUIRED FOR WORK OF THE
SOLENOID OR MOTORIZED VALVE THE CONTRACTOR SHALL OBTAIN AND PAY ALL FEES RELATED TO
IN-LINE PUMP (PLAN) PERMITTING, INSPECTIONS, TAP-ON FEES, ETC. CONTRACT.
SST SECONDARY STORM DRAIN SEWAGE (BELOW GRADE)
SOLENOID OR MOTORIZED CONTROL VALVE (3 WAY) F. PROVIDE CUTTING, CORING AND PATCHING OF ALL WALLS, SLABS AND
V SANITARY VENT PIPING 5.) CONTRACTOR SHALL COORDINATE ANY PLUMBING OR PIPING SYSTEM DECKS AS REQUIRED FOR WORK SHOWN. COORDINATE ALL WORK WITH
FLEX CONNECTION SHUTDOWN WITH THE OWNER 48 HOURS IN ADVANCE. OWNER AND GENERAL CONTRACTOR AND ALL TRADES.
GW GREASE WASTE (BELOW GRADE) TRIPLE DUTY VALVE
EXPANSION JOINT WITH 6.) CONTRACTOR SHALL COORDINATE AND PROVIDE ALL NECESSARY PIPING
G. PROVIDE SCHEDULE 40 BLACK STEEL PIPE SLEEVES FOR ALL
(E) EXISTING PIPING TO REMAIN GUIDES UNDERGROUND PIPING PASSING THROUGH OR UNDER FOOTINGS, WALLS,
RELIEF VALVE & PLUMBING FITTINGS, PIPING, MISCELLANEOUS ITEMS REQUIRED FOR
FOUNDATION WALLS, SLABS FLOORS AND/OR UNDERGROUND
SYMBOL(E) EXISTING PIPING TO BE REMOVED A COMPLETE INSTALLATION OF ALL PLUMBING RELATED ITEMS.
PIPE ANCHOR STRUCTURES. REFER TO THE PROJECT SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS.
PIPE TURNED UP TEMPERATURE & PRESSURE RELIEF VALVE PIPE GUIDE 7.) ALL WORK SHALL BE COORDINATED WITH THE EQUIPMENT VENDORS.
H. WHERE PIPING IS LOCATED OVER FOOTINGS AND/OR OTHER
UNDERGROUND STRUCTURES, ROLL DOWN AS REQUIRED TO CONNECT
PIPE TURNED DOWN
HOSE BIBB OR DRAIN VALVE FLOOR DRAIN OR FLOOR SINK 8.) THE CONTRACTOR SHALL COORDINATE THE INSTALLATION OF ALL TO SYSTEMS NOTED. PROVIDE ALL REQUIRED OFFSETS, FITTINGS AND
NC LICENSE NO. C-0430
FD UNDER SLAB PIPING WITH EXISTING STRUCTURAL FOUNDATIONS.
BRANCH OFF BOTTOM OF PIPE CONNECTIONS.
CWS WALL HYDRANT UNDERGROUND UTILITY LOCATIONS SHALL BE VERIFIED PRIOR TO ANY AS S O CI AT
FLOOR/DECK PLATE CLEAN OUT I. PITCH ALL SANITARY, WASTE, AND STORM PIPING AS FOLLOWS: PIPING H C ARO L LA ES
BRANCH OFF TOP OF PIPE FCO/DPCO WORK BEING PERFORMED. CONTRACTOR SHALL REPAIR OR REPLACE ALL RT I EL CH
I TE C TUR A
(PLAN VIEW) 3" AND SMALLER, PITCH AT 2 PERCENT (14" PER FOOT) MINIMUM, PIPING O L

B
AR
E S S IO N

NA

P.
C
PIPING NOT IN PROPER WORKING ORDER OR DAMAGED DURING

LA
CWS & HWS WALL HYDRANT OF

C.
N

OR
ED
INSTALLATION OF THE NEW UNDERSLAB PIPING. 4" AND LARGER, PITCH AT 1 PERCENT (18" PER FOOT) MINIMUM.

PO
R E GI S TE R
AL
PR
VALVE ON VERTICAL CLEAN OUT

R A TI ON
CO SEAL CERT. NO.
J. CONNECT TO SITE PIPING OUTSIDE BUILDING AS SHOWN. PROVIDE ALL
NON-FREEZE CWS WALL HYDRANT IN BOX 030515 52904
9.) ALL PLUMBING & PIPING SYSTEMS SHALL BE SUPPORTED AS REQUIRED REQUIRED OFFSETS, FITTINGS AND CONNECTIONS. FIELD VERIFY EXACT
VALVE(S) IN VERTICAL PIPE EN
BY THE STATE AND LOCAL CODE REQUIREMENTS AND PER MANUFACTURER'S LOCATION, DEPTH AND COMPOSITION OF SITE SERVICES AND G INEER
NON-FREEZE CWS & HWS WALL HYDRANT IN BOX EQUIPMENT TO BE REMOVED NO

CR

E
NA
RECOMMENDATIONS. COORDINATE ALL WORK WITH SITE CONTRACTOR. AI RT
H CAROLI

H
CH
REDUCER G S. BL YT C

.
AR
K. COORDINATE ALL VENT TERMINATIONS ABOVE ROOF WITH HVAC L OT TE , N .
NON-FREEZE ROOF HYDRANT 10.) ALL PIPING PENETRATIONS THROUGH NEW, EXISTING WALL, OR FLOOR
PIPE BREAK PIPE CONTINUATION CONTRACTOR. ALL VENT TERMINATIONS ABOVE ROOF SHALL BE A
SHALL BE SEALED TO EQUAL THE RATING OF THE NEW, EXISTING MINIMUM 25'-0" AWAY FROM ANY HVAC OUTSIDE AIR INTAKE (ROOFTOP
BALL VALVE STRAINER WALL OR FLOOR. UNIT, LOUVER, ETC.). 9/9/2016
UNION NEW CONNECTION TO EXIST. 11.) THE PLUMBING SYSTEM SHALL BE TESTED AS REQUIRED BY STATE AND LOCAL L. PROVIDE SINGLE HOSE BIBB WITH VACUUM BREAKER (HB) UNDER
BUTTERFLY VALVE LAVATORY(S) IN ALL TOILET ROOMS WITH FLOOR DRAINS. ONE REQUIRED
CODE OR BY THE REQUIREMENTS OF THE LOCAL PLUMBING INSPECTOR. © 2016 LaBella Associates
FLANGE PER ROOM.
GATE VALVE - NRS REMOVE TO THIS POINT 12.) THE ENTIRE DOMESTIC WATER SYSTEM (EXISTING/NEW) SHALL BE M. PROVIDE BARRIER TYPE SEAL DEVICE ON ALL FLOOR DRAINS.

GATE VALVE - OS&Y PRESSURE GAUGE


X KEYNOTE
DISINFECTED IN ACCORDANCE TO THE LOCAL CODE & HEALTH
DEPARTMENT REQUIREMENTS. N. REFER TO ARCHITECTURAL DRAWINGS AND THE PROJECT SPECIFICATIONS
FOR ANY PROJECT PHASING REQUIREMENTS.
TOWN OF DAVIDSON
13.) THE BACKFLOW PREVENTION DEVICE SHALL BE INSTALLED PER STATE AND 216 South Main Street,
GLOBE VALVE THERMOMETER
X DEMOLITION KEYNOTE
LOCAL CODE & PER AUTHORITY HAVING JURISDICTION REQUIREMENTS. Davidson, NC 28036
WHA
PLUG VALVE 1 3 14.) THE CONTRACTOR SHALL NOT SCALE THESE DRAWINGS.
WATER HAMMER ARRESTER WB
SHUT-OFF VALVE (GATE, BALL,
WASHER BOX
OR BUTTERFLY - REFER TO SPECS) P-TRAP

ABBREVIATIONS PLUMBING SPECIFICATION NOTES


AFF ABOVE FINISHED FLOOR (N) NEW 1. SCOPE OF WORK 5. SANITARY/STORM DRAINAGE AND VENT PIPING 7. B. BELOW GRADE
AP ACCESS PANEL NC NORMALLY CLOSED
- - NH NO HUB EARTH SHALL BE EXCAVATED TO A MINIMUM DEPTH WITH AN
BFP BACK FLOW PREVENTER No NUMBER A. THE CONTRACTOR IS RESPONSIBLE FOR ALL WORK, MATERIALS, A. ABOVE GRADE: EVEN SURFACE TO INSURE SOLID BEARING OF PIPE FOR ITS
BLDG BUILDING NO NORMALLY OPEN
BSMT BASEMENT NTS NOT TO SCALE AND LABOR TO SATISFY A COMPLETE WORKING SYSTEM -2" AND BELOW: SCH. 40 GALV. STL. PIPE WITH SCREWED ENTIRE LENGTH.
- - - - WHETHER SPECIFIED OR IMPLIED. ENDS OR SCH. 40 PVC WITH SOLVENT -INTERIOR: THE PIPE SHALL BE INSTALLED (UNLESS OTHER-
CA COMPRESSED AIR OD OUTSIDE DIMENSION
CFH CUBIC FEET PER HOUR ODWH ON DEMAND WATER HEATER JOINTS OR DWV COPPER WITH SOLDER WISE SPECIFIED) A MINIMUM OF 4 INCHES BELOW
CI CAST IRON OPG OPENING B. ALL WORK IS TO BE PERFORMED IN STRICT COMPLIANCE JOINTS. ALL SOLDER TO BE "NO LEAD" THE BOTTOM OF THE SLAB AND SHALL NOT BE
℄ CENTER LINE OS OPEN SITE
WITH THE NATIONAL STANDARD PLUMBING CODE (LATEST TYPE. IN ANY DIRECT CONTACT WITH THE CONCRETE
CLG CEILING OT OFF TOP
CO CLEAN OUT OZ OUNCE EDITION), ALL LOCAL CODES, AND ALL OTHER REGULATIONS AT ANY POINT.
CONN CONNECTION - -
CWS COLD WATER SUPPLY PART PARTIAL GOVERNING WORK OF THIS NATURE. -3" AND ABOVE: SCH. 40 PVC WITH SOLVENT JOINTS. -EXTERIOR: THE WATER PIPE SHALL HAVE A MINIMUM OF
COND CONDUCTOR PDR PLENUM DRAIN 42" OF COVER AND THE SANITARY WASTE PIPE
- - PERF PERFORATED
DB DRAIN BOX PH PHASE C. THE CONTRACTOR SHALL, BEFORE SUBMITTING ANY PROPOSAL, SHALL HAVE A MINIMUM OF 24" OF COVER.
DEG DEGREE PIV POST INDICATOR VALVE EXAMINE THE PROPOSED SITE AND SHALL DETERMINE FOR
DF DRINKING FOUNTAIN POS POSITIVE
DIA DIAMETER PRESS PRESSURE HIMSELF THE CONDITIONS THAT MAY EFFECT THE WORK. NO B. BELOW GRADE: SERVICE WT. CAST IRON WITH BELL AND FIRE STATION #2
DN DOWN PS PRESSURE SWITCH ALLOWANCE SHALL BE MADE IF THE CONTRACTOR FAILS TO SPIGOT JOINTS OR SCH. 40 PVC WITH 8. MISCELLANEOUS
DPCO DECK PLATE CLEAN OUT PSI POUNDS PER SQUARE INCH 19436 DAVIDSON CONCORD ROAD,
MAKE SUCH EXAMINATIONS. SOLVENT JOINTS.
DRS
DW
DARK ROOM DOUBLE BOWL SINK
DOMESTIC WATER
PSIG POUNDS PER SQUARE
INCH GAUGE A. COORDINATE INSTALLATION OF ALL ROOF FLASHING AT
DAVIDSON, NC 28036
DWG DRAWING PSIA POUNDS PER SQUARE
DWH DOMESTIC WATER HEATER INCH ABSOLUTE D. ALL EQUIPMENT AND MATERIALS SHALL BE AS SPECIFIED OR C. PVC PIPING SHALL NOT BE USED IN AIR PLENUM CEILINGS ROOF PENETRATION.
- - PT PRESSURE TRANSMITTER "APPROVED EQUAL" BY ENGINEER OR ARCHITECT. AND SHALL NOT CROSS FIRE RATED WALLS, CEILINGS,
(E) EXISTING PV PLUG VALVE
EA EACH PVC POLYVINYL CHLORIDE OR FLOORS. B. DO NOT SCALE THIS DRAWING FOR EXACT DIMENSIONS.
ELEV ELEVATION PVS POLYVINYL COATED STEEL 2. PERMITS VERIFY ALL FIGURES, CONDITIONS, AND DIMENSIONS
ENT ENTERING - -
EQ EQUAL QUAN QUANTITY D. DRAINAGE PIPING SHALL BE RUN AS STRAIGHT AS POSSIBLE AT THE JOB SITE.
EQUIP EQUIPMENT - - A. THE CONTRACTOR SHALL SECURE ALL PERMITS OR APPLICA- AND SHALL HAVE LONG TURN FITTINGS.
EQUIV EQUIVALENT RD ROOF DRAIN
ETR EXISTING TO REMAIN REL RELIEF TIONS AND PAY ANY AND ALL FEES. C. THE PLUMBING PLANS ARE INTENDED TO BE DIAGRAMMATIC
- - REQD REQUIRED E. DRAINAGE PIPING 3" SIZE AND SMALLER SHALL RUN AT A MATIC AND ARE BASED ON ONE MANUFACTURE'S EQUIP-
°F DEGREES FAHRENHEIT RL RAIN LEADER 3 09/07/16 PERMITTING COMMENTS
FAI FRESH AIR INTAKE RM ROOM UNIFORM GRADE OF AT LEAST 1/4" PER FOOT, AND PIPING MEANT. THEY ARE NOT INTENDED TO SHOW EVERY ITEM
FCO FLOOR CLEANOUT RP RECIRCULATION PUMP 3. SHOP DRAWINGS LARGER THAN 3" SHALL BE RUN AT A GRADE OF NO LESS IN ITS EXACT LOCATION, THE EXACT DIMENSIONS, OR ALL 2 08/15/16 ADDENDUM 2
FD FLOOR DRAIN RPM REVOLUTIONS PER MINUTE
FIN FINISHED - - THAN 1/8" PER FOOT. THE DETAILS OF THE EQUIPMENT. THE CONTRACTOR 1 08/10/16 PERMITTING COMMENTS
FL FLOOR SA SHOCK ABSORBER A. SUBMIT MATERIAL LIST AND SHOP DRAWINGS FOR MAJOR SHALL VERIFY THE ACTUAL DIMENSIONS OF THE EQUIP- NO: DATE: DESCRIPTION:
FLA FULL LOAD AMPS SCH SCHEDULE
FPWH FREEZE PROOF WALL HYDRANT SCHEM SCHEMATIC EQUIPMENT/FIXTURES TO THE ARCHITECT OR ENGINEER F. ALL VENT PIPING SHALL BE SLOPED TO DRAIN BACK TO MEANT PROPOSED TO ENSURE THAT THE EQUIPMENT WILL REVISIONS
FT FEET SK STAINLESS STEEL SINK FOR APPROVAL. THE CONTRACTOR SHALL SUBMIT THREE FIXTURES. FIT IN THE AVAILABLE SPACE.
- - SPEC SPECIFICATION PROJECT NUMBER:
SETS OF SHOP DRAWINGS AND THEY SHALL BE CLEARLY
GA
GALV
GAUGE
GALVANIZED
SPS
SQ
SUMP PUMP SYSTEM
SQUARE
2151374
LABELED. G. CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER
GC GENERAL CONTRACTOR S/S SERVICE SINK
GPD GALLONS PER DAY SS STAINLESS STEEL FLASHING OF THE VENT PIPING RUN THROUGH THE ROOF. 9. TESTING DRAWN BY:
GPH GALLONS PER HOUR ST STORM PAV/DWM
GPM GALLONS PER MINUTE SST SECONDARY STORM REVIEWED BY:
GW GREASE WASTE STD STANDARD 4. DOMESTIC WATER SUPPLY PIPING A. PLUMBING SYSTEMS SHALL BE FLOW AND PRESSURE
TESTED IN ACCORDANCE WITH STANDARD PRACTICE AND
BB
- - STL STEEL 6. ALL STUB-INS AND/OR SLAB OR WALL PENETRATION TO BE
HT HEIGHT STR STRUCTURAL THE NATIONAL STANDARD PLUMBING CODE. CONTRACTOR
HB HOSE BIBB SUP SUPPLY A. UNDERGROUND: PROVIDE TYPE "K" SOFT DRAWN COPPER PER NATIONAL STANDARD PLUMBING CODE. ALL PIPING ISSUED FOR:
HD HEAD (SEE SCHEDULES) SYS SYSTEM TUBING WITH BRAZED CONNECTIONS. PENETRATIONS OF BUILDING FOUNDATIONS OR FOOTINGS
SHALL SCOPE NEW LINES AND PROVIDE REPORT WITH CONSTRUCTION
HP HORSE POWER S/SHO SAFETY SHOWER VIDEO.
HR HOSE REEL - - SHALL BE SLEEVED.
HTR HEATER TYP TYPICAL DATE:
B. ABOVE GROUND: PROVIDE TYPE "L" HARD DRAWN COPPER
HWS HOT WATER SUPPLY - -
TUBING WITH 125 PSI SOLDER JOINTS, 10. GUARANTEE
07.25.16
HWR HOT WATER RETURN UR URINAL
- - - - COPPER OR BRASS FITTINGS. ALL SOLDER 7. PIPE SUPPORTS
ID INTERNAL DIAMETER VB VACUUM BREAKER DRAWING NAME:
INCL INCLUDING VS VIVARIUM SINK TO BE "NO LEAD" TYPE. A. MATERIALS, EQUIPMENT AND INSTALLATION SHALL BE
INV INVERT VTR VENT THRU ROOF A. ABOVE GRADE GUARANTEED FOR A PERIOD OF ONE(1) YEAR FROM DATE
- - - -
K TYPE OF COPPER TUBING W WIDTH CONTRACTOR MAY SUBMIT OPTIONAL CODE APPROVED ALL PIPE SHALL BE SUPPORTED FROM THE BUILDING OF ACCEPTANCE. DEFECTS WHICH APPEAR DURING THAT
KW KILOWATT W/ WITH MATERIAL AND FITTINGS AS LISTED IN 'TABLE 605.4 - WATER STRUCTURE IN A NEAT AND WORKMANLIKE MANNER. PERIOD SHALL BE CORRECTED AT THIS CONTRACTOR'S
- - WHA WATER HAMMER ARRESTER
DISTRIBUTION PIPE' , AND 'TABLE 605.5 PIPE FITTINGS' THE USE OF WIRE AND PERFORMED METAL TO SUPPORT EXPENSE.
LAV
-
MC
LAVATORY
-
MECHANICAL CONTRACTOR
W/O
WC
WM
WITHOUT
WATER CLOSET
WATER METER
OF THE PLUMBING CODE OF NEW YORK STATE. PIPES WILL NOT BE PERMITTED. SPACING OF PIPE SUPPORTS PLUMBING SYMBOLS AND
MED
MFR
MISC
MEDIUM
MANUFACTURER
MISCELLANEOUS
-
YCO
-
YARD CLEAN OUT C. ALL HOT WATER PIPING TO BE INSULATED WITH 1"
SHALL BE AS SPECIFIED IN CHAPTER 8 OF THE NATIONAL
STANDARD PLUMBING CODE.
B. FOR THE SAME PERIOD, THE PLUMBING CONTRACTOR
SHALL BE RESPONSIBLE FOR ANY DAMAGE TO PREMISES ABBREVIATIONS
MIN MINIMUM FIBERGLASS INSULATION. CAUSED BY DEFECTS IN WORKMANSHIP OR IN THE WORK
MSS MOP SERVICE SINK OR EQUIPMENT FURNISHED AND/OR INSTALLED BY HIM.
MTD MOUNTED
D. ALL COLD WATER PIPING TO BE INSULATED WITH 1/2"
FOAM INSULATION.

DRAWING NUMBER:
E. COMPLY WITH NSF 14 FOR PLASTIC, POTABLE DOMESTIC WATER
MECKLENBURG
PIPING AND COMPONENTS. COUNTY
INCLUDING MARKING "NSF-pw" ON PIPING.
CODE ENFORCEMENT

P-001
F. The
COMPLY WITH NSF
Design 61 FOR POTABLE
In These DOMESTIC WATER
Construction
Documents Have Been Reviewed For
PIPING AND COMPONENTS.
Compliance With The State Building
Code. It Is The Responsibility Of The
Contractor To Construct This Project
With Good Engineering Practice And
In Compliance With The North
Carolina State Building Code.
DECONTAMINATION

1-1/4"G
114 5
KEY NOTES: 455 South Main Street Engineering
Davidson, NC 28036 Architecture
3 SS-1 17 1 PROVIDE 4" SAN PIPE UP TO WC. P: (704) 439-2931 Environmental

3"SAN
10 STORAGE Planning
M 2 PROVIDE 4" SAN PIPE UP TO CO.
115
4 SH-1 4
3 3 PROVIDE 4" SANITARY W/ DEEP SEAL P-TRAP UP TO FD/TD
FD BEDROOM www.labellapc.com
4"SAN 3
FD 111

4"SAN
EXERCISE

3"SAN
4 PROVIDE 2"V PIPE UP.

N
SA
112

4"SAN
4

4"
3"SAN LOCKER ROOM
5 L-1 5 PROVIDE 3"SAN PIPE UP.
113 2
16 2"V 4"SAN 6 PROVIDE TD-1 AND CONNECT TO CB-1.
4"SAN 4"SAN 4"SAN 4"SAN 4"SAN
FCO
7 PROVIDE CB-1 AND CONNECT TO 4"WASTE PIPE.
4"OW 4"OW 4"OW
19
MSB-1 4

4"SAN
2 8 PROVIDE OI-1 AND ALL ASSOCIATED ACCESSORIES. CONNECT TO 4"SAN
PIPE TO OUTLET, 4"OW PIPE TO INLET, AND 2"V PIPE IN SLAB.

LI-1
FD 4 17 BEDROOM
5 3 110
9 PROVIDE OI-2 AND ALL ASSOCIATED ACCESSORIES. CONNECT TO 4"SAN
2"V
WB AND 2"V PIPES IN SLAB.
VESTIBULE
LAUNDRY 117

4"SAN
13 10 PROVIDE 1-1/4" G PIPE UP. REFER TO P101 AND CIVIL DRAWINGS FOR
116
CONTINUATION.

11 PROVIDE 2" CWS PIPE UP. REFER TO P101 DRAWING FOR CONTINUATION.
NC LICENSE NO. C-0430

4"OW
12 PROVIDE 4"FP PIPE UP. REFER TO FP101 DRAWING FOR CONTINUATION.
4
ASSOCI AT
CORRIDOR 13 PROVIDE 4"SAN UP. T H CARO L LA ES
I EL
OR
I TE C TU R A
CH L
108

B
AR
ES S IO N

NA

P.
C

LA
OF

C.
N

OR
ED
14 PROVIDE 4" FIRE SUPPRESSION UNDERGROUND PIPE. REFER TO CIVIL

PO
R E GI S TE R
AL
PR

R A TI ON
SEAL CERT. NO.
DRAWINGS FOR CONTINUATION.
030515 52904
BEDROOM
15 PROVIDE 2" CWS UNDERGROUND PIPE. REFER TO CIVIL DRAWINGS FOR EN
109 G INEER NO

CR

E
NA
CONTINUATION. AI RT
H CAROLI

H
CH
G S. BLYT AR
LOT TE , N .
C
.

16 PROVIDE 4" SAN PIPE. REFER TO CIVIL DRAWINGS FOR CONTINUATION.

17 PROVIDE 3" DEEPSEAL P-TRAP AT SD/MSB.


9/16/2016
9/9/2016
1
5 18 PROVIDE 4" SAN PIPE UP TO WALL CO.
© 2016 LaBella Associates
19 EXTEND 4" OW PIPING TO EXTERIOR OIL SEPARATOR, SEE CIVIL
DRAWINGS FOR PIPE CONTINUATION.
P-1
2"V TOWN OF DAVIDSON

4"OW

3"SAN

4"SAN
L-1
6 6 MEN 216 South Main Street,
107 4
TD-1 TD-1 Davidson, NC 28036
4"SAN

2
2"V

3"
SAN
5
17
4
KITCHEN
SH-1 105 SK-1
SH-1

2"V
17 2
FCO
FCO 4"SAN
WOMEN 4
106

4"SAN
3"SAN
2 L-1
P-1
1

5
LINEN PANTRY
103 104
4"OW

7
4 7 4
4"OW 4"OW 4"OW 4"OW FIRE STATION #2
4"OW 4"OW
WCO CB-1
CB-1
WCO 19436 DAVIDSON CONCORD ROAD,
DAVIDSON, NC 28036
2

BAY 1 BAY 2
118 119

5 9/16/16 INTERACTIVE REVIEW COMMENTS


4 9/14/16 INTERACTIVE REVIEW COMMENTS
3 09/07/16 PERMITTING COMMENTS
6 6
2 08/15/16 ADDENDUM 2
TD-1 TD-1
1 08/10/16 PERMITTING COMMENTS
NO: DATE: DESCRIPTION:
REVISIONS
PROJECT NUMBER:

LIVING
2151374
102 DRAWN BY:
PAV/DWM
REVIEWED BY:
BB
ISSUED FOR:
CONSTRUCTION
DATE:
07.25.16
DRAWING NAME:

ENTRY OFFICE
100 101

11
UNDER SLAB PLUMBING
12
2" SPRINKLER
CLOSET
101A
FLOOR PLAN
455 South Main Street Engineering
Davidson, NC 28036 Architecture
P: (704) 439-2931 Environmental
Planning

www.labellapc.com

4"
NC LICENSE NO. C-0430
A
O
S
S

CAR
I
C

T
H

A
L L

T L
O

E S
R

T C U
E
C H

A
I
I

R
NO

R
P
L A

A
L

E S S ON
N

C
F

O
D
I

O
R O

R
E E

P
A

L
RP

E G IS T

N I A R

SEAL CERT. NO.


T O

030515 52904
R

E
G R N
L E
CRA

I NE
E

N
A
I
H

R
YT

A R
O
T
H
C

.
C

H C
R

S B
.
IG

LO T N
E
.

,
T

9/16/2016
9/9/2016
© 2016 LaBella Associates

TOWN OF DAVIDSON
216 South Main Street,
Davidson, NC 28036

FIRE STATION #2
19436 DAVIDSON CONCORD ROAD,
DAVIDSON, NC 28036

5 9/16/16 INTERACTIVE REVIEW COMMENTS


4 9/14/16 INTERACTIVE REVIEW COMMENTS
3 09/07/16 PERMITTING COMMENTS
2 08/15/16 ADDENDUM 2
1 08/10/16 PERMITTING COMMENTS
NO: DATE: DESCRIPTION:
REVISIONS
PROJECT NUMBER:
2151374
DRAWN BY:

REVIEWED BY:

ISSUED FOR:
CONSTRUCTION

DATE:
07.25.16
DRAWING NAME:

DRAWING NUMBER:

15 DRAWING NUMBER:
MECKLENBURG COUNTY
14
CODE ENFORCEMENT
4"
00/00/0000 00:00AM

2"
UNDERSLAB PLUMBING FLOOR PLAN
P-100
1 The Design In These Construction
Documents Have Been Reviewed For
P100 1/4" = 1'-0" Compliance With The State Building
Code. It Is The Responsibility Of The
FLPTH

N Contractor To Construct This Project


With Good Engineering Practice And
In Compliance With The North
Carolina State Building Code.
TOTAL GAS LOAD = 580 MBH
TOTAL DEVELOPED LENGTH = 150'
GAS PRESSURE = <2.0 PSI
GAS METER BY GAS CO.
11
GAS PIPING SIZED PER TABLE 402.4(2) OF THE
NCSBC: FUEL GAS CODE 2012 SS-1 KEY NOTES:
2 1 PROVIDE WC-1 AND ALL ASSOCIATED ACCESSORIES. CONNECT TO 1/2"CW PIPE IN WALL AND 4"SAN PIPE IN
17 4
SLAB.
FCO
M
13 2 PROVIDE 4" FCO.
16
FD-1
FD-1
12 FD-1 12 2V" 3 1"CW, 3/4" HW AND 2"V PIPES UP.
1"G TO
GENERATOR 6
12 2
2"G UP 5 L-1 4 PROVIDE SH-1 (ADA) AND ALL ASSOCIATED ACCESSORIES. CONNECT 1/2"CW AND HW PIPEING IN WALL TO
2V" 2V" 2V" FCO
SHOWER CONTROLS. CONNECT SHOWER TRENCH DRAIN TO 4"SAN PIPE IN SLAB.

6 6 5 PROVIDE L-1, 1-1/2" P-TRAP, FAUCET, AND ALL ASSOCIATED ACCESSORIES. CONNECT 1/2"CW AND HW PIPES
IN WALL TO FAUCET. CONNECT P-TRAP TO 4" SAN PIPE IN FLOOR AND CONNECT 1-1/2" V PIPE DOWN.

2V"
28 MSB-1
24 6 PROVIDE 2"V PIPE DN AND CONNECT TO 2"V PIPE IN SLAB.
LI-1

12 FD-1 6
2V" 7 PROVIDE DOUBLE BOWL SINK 'SK-1', 1-1/2" P-TRAP, FAUCET, SINK DISPOSAL 'SD-1', AND ALL ASSOCIATED
ED-1 ACCESSORIES. CONNECT 1/2"CW AND HW PIPES IN WALL TO FAUCET. CONNECT P-TRAP TO 4" SAN PIPE IN
W/D 29 FLOOR AND CONNECT 1-1/2" V PIPE DOWN.

2V"
15 STACKED
NFWHB-1 19 1/2"TW 8 2" CWS MAIN PIPE UP TO ATTIC SPACE. PROVIDE SHUT OFF AT BASE.

NC LICENSE NO. C-0430


18 9 PROVIDE 2"V PIPE DN AND CONNECT TO 2"V PIPE IN SLAB. CONNECT 2"V NEAR FLOOR TO 2"V PIPE AS SHOWN
23 EW-1 AND THEN RUN UP ALONG WALL TO APPROX. 12' AFF. TERMINATE WITH AIR ADMITTANCE VALVE INSIDE
6 14
H C ARO L
ASS O CI AT
OX-BOX MOUNTED TO INTERIOR WALL. T LA ES
SSH-1 I EL
OR
I TE C TU R A
CH L
E S S IO N AR

B
C

NA

P.
OF

LA

C.
N

O
PROVIDE 1/2" HW PIPE AND CONNECT TO DISHWASHER. PROVIDE WASTE HOSE AND CONNECT FROM

ED
10

RP
R E GI S TE R
AL
PR

OR A
DISHWASHER TO SD-1 DISHWASHER TYE-IN POINT. SEAL CERT. NO.

TI ON
030515 52904
11 PROVIDE SS-1, 1-1/2" P-TRAP, FAUCET, AND ALL ASSOCIATED ACCESSORIES. CONNECT 1/2"CW AND HW PIPES EN
G INEER NO
IN WALL TO FAUCET. CONNECT P-TRAP TO 4" SAN PIPE IN FLOOR AND CONNECT 1-1/2" V PIPE DOWN.

CR

E
NA
AI RT
H CAROLI
G S. BLYT
CH

H
AR C

.
LOT TE , N .
12 PROVIDE FD-1 AND CONNECT TO 4"SAN PIPE IN SLAB.

21
13 PROVIDE 2" SAN W/ DEEP SEAL P-TRAP UP TO DRAIN PAN ON MEZZAININE/ATTIC. ROUTE PIPING TO EXTERIOR 9/20/2016
9/9/2016
WALL DOWN TO SPLASH BLOCK. PROVIDE AIR GAP PER CODE.
13 1 6 3 © 2016 LaBella Associates
WC-1 14 PROVIDE SAFETY SHOWER SSH-1, TEMPERED WATER MIXING VALVE, AND ALL ASSOCIATED ACCESSORIES.
PROVIDE AND CONNECT 1/2" CW AND HW PIPING TO MIXING VALVE. PROVIDE AND CONNECT 1/2" TEMPERED

1-1/2"V 2"V
WATER PIPING TO MIXING VALVE AND SHOWER.
TOWN OF DAVIDSON
15 PROVIDE NFWHB-1 AND ALL ASSOCIATED ACCESSORIES. CONNECT TO IN WALL 1/2" CW AND HW PIPING.
5 3/4"HW
L-1 3/4"CW
13 2"V 16 PROVIDE 2"V PIPE UP TO MEZANINE/ATTIC.
20
2
1/2" 1/2"HW
FCO 17 PROVIDE NATURAL GAS PRESSURE REGULATOR, METER, AND ALL ASSOCIATED ACCESSORIES. CONNECT
1/2" 1/2"CW 1-1/2"V 1-1/4"G PIPE TO INLET OF REGULATOR. PROVIDE AND CONNECT 2"G PIPE TO REGULATOR AND METER.
30
CONNECT 2"G PIPE TO METER OUTLET AND UP SIDE OF BUILDING.
4 SD-1 NFWHB-2
6

2"V
18 PROVIDE WASH MACHINE CONNECTION BOX, WITH TWO 3/4" VALVES WITH WATER HAMMER ARRESTERS EA
SH-1 1/2"HW SD-1 FOR CW AND HW HOSE CONNECTIONS, 3/4"CW AND HW PIPES UP IN WALL, 2" WASTE CONNECTION, AND ALL
SH-1
2"V 1/2"CW ASSOCIATED ACCESSORIES. SEE DETAIL 1 ON DRAWING P502 FOR MORE INFORMATION.

2"V
2
2 19 PROVIDE WASH MACHINE CONNECTION BOX, WITH TWO 1/2" VALVES WITH WATER HAMMER ARRESTERS EA
FCO 7 FOR CW AND HW HOSE CONNECTIONS, 1/2"CW AND HW PIPES UP IN WALL, 2" WASTE CONNECTION DN, AND
25 25 SK-1 ALL ASSOCIATED ACCESSORIES. CONNECT 2" WASTE PIPE TO 4" WASTE PIPE IN SLAB. CONNECT 1-1/2"V PIPE
FCO 1/2" DN TO WASTE PIPE. SEE DETAIL 1 ON DRAWING P502 FOR MORE INFORMATION.
5 1 10
20 PROVIDE 3/4" GAS SUPPLY PIPE DN AND CONNECT TO STOVE AND TO MAIN IN MEZZANAINE/ATTIC.
L-1 WC-1
1-1/2"V 2"V
1/2" 21 PROVIDE SIOUX CHIEF ICE MAKER OUTLET BOX WITH 1/2" CW SUPPLY QUARTER -TURN BALL VALVE AND A
6
1/2" X 1/4" OD COMPRESSION OUTLET. PROVIDE OUTLET BOX WITH FRAME AND STAINLESS STEEL HOSE FOR
CONNECTION TO REFRIGERATOR ICE MAKER.

22 4"FP PIPE UP. REFER TO FP101 DRAWING FOR CONTINUATION. 4 6

23 PROVIDE VALVE CONNECTION BOX, WITH TWO 1/2" VALVES WITH WATER HAMMER ARRESTERS EA FOR CW
AND HW HOSE CONNECTIONS, 1/2"CW AND HW PIPES UP IN WALL. SEE DETAIL 1 ON DRAWING P502 FOR MORE
26 26
INFORMATION. FIRE STATION #2
CB-1 CB-1 CB-1 CB-1
24 PROVIDE LINT INTERCEPTOR LI-1. SEE P-100 FOR ADDITIONAL INFORMATION.
9 9

25 PROVIDE TD-1 AND ALL ASSOCIATED ACCESSORIES. SEE P-100 FOR ADDITIONAL INFORMATION.
2
FCO 26 PROVIDE CB-1 AND ALL ASSOCIATED ACCESSORIES. SEE P-100 FOR ADDITIONAL INFORMATION.

6 9/20/16 INTERACTIVE REVIEW COMMENTS


27 1-1/2" CWS TRUCK FILL LINE MOUNT 36" AFF. EXTEND 1-1/2" CWS UP TO ATTIC SPACE CONTINUE ON P-102. 5 9/16/16 INTERACTIVE REVIEW COMMENTS
COORDINATE CONNECTION WITH FIRE DEPARTMENT AHJ.
4 9/14/16 INTERACTIVE REVIEW COMMENTS
28 PROVIDE MOP SERVICE BASIN MSB-1, DRAIN, WALL MOUNTED FAUCET, WITH PAIL HOOK AND ALL 3 09/07/16 PERMITTING COMMENTS
ASSOCIATED ACCESSORIES. 2 08/15/16 ADDENDUM 2
1 08/10/16 PERMITTING COMMENTS
29 PROVIDE 4" WASTE AND CONNECT TWO 2" WASTE FROM WASHER BOXES. EXTEND 2" VENT UP VENT SYSTEM IN
CEILING. NO: DATE: DESCRIPTION:
REVISIONS
30 PROVIDE NFWHB-2 AND ALL ASSOCIATED ACCESSORIES. CONNECT TO IN WALL 1/2" CW PIPING.
PROJECT NUMBER:
25 25

DRAWN BY:
PAV/DWM
REVIEWED BY:
BB
ISSUED FOR:

DATE:

DRAWING NAME:

FIRE TRUCK FILL


8
CONNECTION

15 27
22
NFWHB-1

DRAWING NUMBER:
MECKLENBURG COUNTY
CODE ENFORCEMENT

P-101
00/00/0000 00:00AM

The Design In These Construction


Documents Have Been Reviewed For
Compliance With The State Building
Code. It Is The Responsibility Of The
FLPTH

Contractor To Construct This Project


With Good Engineering Practice And
In Compliance With The North
Carolina State Building Code.
11 27 14 KEY NOTES:
WH-2 455 South Main Street Engineering
1 PROVIDE 2" GAS RISER UP FROM GAS REGULATOR. SUPPORT PIPING FROM WALL.. PAINT EXTERIOR PIPING. Davidson, NC 28036 Architecture
21 P: (704) 439-2931 Environmental
2"V HWCP-2 2 ROUTE GAS PIPING AS SHOWN IN ATTIC SPACES. PROVIDE HANGERS AND GAS SHUT OFF VALVES AS INDICATED
Planning
AND REQUIRED BY CODE.
7

1" CD
www.labellapc.com
3 PROVIDE 1" GAS DN TO GF-1 WITH DRIP LEG, SHUT OFF VALVE AND REGULATOR. FINAL CONNECTION BY
1 6 15 EQUIPMENT INSTALLER.
1"
1"
2"G UP

(130 CFH)
16 4 PROVIDE 3/4" GAS DN TO RADIANT HEAT BURNERS, IRH-1 THRU 4 WITH DRIP LEG, SHUT OFF VALVE AND
(580 CFH) 13

1"G
REGULATOR. FINAL CONNECTION BY EQUIPMENT INSTALLER.

2"V
5 PROVIDE 3/4" GAS DN TO GAS STOVE IN KITCHEN WITH DRIP LEG, SHUT OFF VALVE AND REGULATOR. FINAL
MEZZANINE

(580 CFH)
28 CONNECTION BY EQUIPMENT INSTALLER.
---

2"G
HP-2
17 1/2" 6 PROVIDE 2"V PIPE DN
2 2
1" 1"

3"V
7 PROVIDE 1" GAS DN TO WH-1 AND WH-2. CONNECT TO WG WITH DRIP LEG AND GAS SHUT OFF VALVE. RUN GAS
2"G 1"G PIPING ON MEZZANINE WALL.
1/2" (580 CFH) (210 CFH)
1/2" 8 PROVIDE 4" VENT UP THRU ROOF. COORDINATE ROOF PENETRATION AND FLASHING WITH ROOFING INSTALLER.
1"
23 1"
2"V
9 PROVIDE 1/2" CW AND 1/2" HW DN TO DOMESTIC HOSE CONNECTION BOX. PROVIDE ALL ASSOCIATED
ACCESSORIES. NC LICENSE NO. C-0430
19

(160 CFH)
9 18 10 PROVIDE 2"V PIPE DN AND CONNECT TO 2"V PIPE IN SLAB.

1-1/2"G
20 ASS O CI AT
8 10 T H C ARO L LA ES
I EL
OR
I TE C TU R A
CH L

B
AR
E S S IO N

NA

P.
C

LA
OF

C.
N

O
ED

RP
11 PROVIDE 1/2"CW AND 1/2" HW PIPES DN IN WALL TO FAUCET ON SS-1. DROP 1-1/2" V PIPE DOWN AND

R E GI S TE R
AL
PR

OR A
SEAL CERT. NO.
CONNECT TO WASTE PIPING.

TI ON
030515 52904
1" EN
12 PROVIDE WH-1 AND CONNECT TO 1" CW AND 1" HW PIPING. PROVIDE MIXING VALVE, T&P RELIEF VALVE, DRAIN
G INEER NO

CR

E
NA
PAN AND ALL ASSOCIATED ACCESSORIES PER WATER HEATER DETAIL AND SPECS. AI RT
H CAROLI

H
CH
2 G S. BLYT C

.
2 AR
LOT TE , N .
13 PROVIDE EXPANSION TANK SIZED FOR WATER HEATER AND INSTALL PER WATER HEATER DETAIL AND SPECS.

(210 CFH)
14 PROVIDE WH-2 AND CONNECT TO 1" CW AND 1" HW PIPING. PROVIDE MIXING VALVE, T&P RELIEF VALVE, DRAIN 9/14/2016
9/9/2016

1"G
8 5 PAN AND ALL ASSOCIATED ACCESSORIES PER WATER HEATER DETAIL AND SPECS
15 6 13 22
© 2016 LaBella Associates
2"V 15 PROVIDE DRAIN PAN W/ 2" DRAIN FOR WH. CONNECT 2" DRAIN TO 2" P-TRAP BELOW MEZZANAINE FLOOR AND
ROUTE TO EXTERIOR WALL. PROVIDE SPLASH BLOCK. PIPING BY EQUIPMENT INSTALLER. MAINTAIN AIR GAP

12
1"
7
1"
PER CODE.
TOWN OF DAVIDSON
16 PROVIDE 1/2" CW AND 1/2" HW, 1-1/2" WASTE PIPE DN TO L-1. RUN BRANCH PIPING IN ATTIC AS SHOWN.
WH-1 3/4"
216 South Main Street,
1"G
1" G
3/4"G
Davidson, NC 28036
17 PROVIDE 3/4" CW AND 3/2" HW, 2" WASTE PIPE DN TO MSB-1. RUN BRANCH PIPING IN ATTIC AS SHOWN.
(210 CFH) (80 CFH)

28 29
18 PROVIDE 3/4" CW AND 3/4" HW DN TO EQUIPMENT WASH MACHINE CONNECTION BOX. PROVIDE ALL
1/2" HWCP-1 ASSOCIATED ACCESSORIES. SEE WASH MACHINE CONNECTION BOX DETAIL FOR MORE INFORMATION.
2
MECHANICAL PLATFORM 19 PROVIDE 1/2" CW AND 1/2" HW DN TO DOMESTIC WASH MACHINE CONNECTION BOX. PROVIDE ALL
--- ASSOCIATED ACCESSORIES. SEE WASH MACHINE CONNECTION BOX DETAIL FOR MORE INFORMATION.

20 PROVIDE 1/2"CW AND 1/2" HW DROPS DOWN TO TEMPERED WATER MIXING VALVE SERVING SSH-1.

1" CD 21 PROVIDE HWCP-2, 1/2" CHECK VALVE, AND ALL ASSOCIATED ACCESSORIES. CONNECT TO 1/2" HWR PIPING.
SEE DETAIL 12/P501 FOR MORE INFORMATION.
(160 CFH)
1-1/2"G

22 PROVIDE 1" CW AND 3/4" HW DROPS DN TO PLUMBING EQUIPMENT IN KITCHEN AND MENS AND WOMENS
HP-1 SHOWER ROOMS.

23 PROVIDE 1/2' CW AND 1/2" HW DN AND CONNECT TO NFHB-1.

24 2" CW UP FROM WATER SUPPLY CLOSET. 4

25 4"FP PIPE UP. REFER TO FP101 DRAWING FOR CONTINUATION

26 PROVIDE 1-1/2" DROP DN TO TRUCK FILL CONNECTION. PROVIDE DOUBLE CHECK VALVE ASSEMBLY ON PIPE
4
3/4"G
(40 CFH) 3/4"G DROP. FIRE STATION #2
(40 CFH)
27 PROVIDE 1/2" CW AND 1/2" HW DROPS DN AND CONNECT TO SH-1 IN LOCKER ROOM.
19436 DAVIDSON CONCORD ROAD,
DAVIDSON, NC 28036
4 28 PROVIDE 1/2" BALANCE VALVE, CHECK VALVE, SHUT-OFF VALVE AND ALL ASSOCIATED ACCESSORIES.
CONNECT TO 1/2" HW AND HWR PIPING.

29 PROVIDE HWCP-1, 1/2" CHECK VALVE, AND ALL ASSOCIATED ACCESSORIES. CONNECT TO 1/2" HWR PIPING.
SEE DETAIL 12/P501 FOR MORE INFORMATION.

30 PROVIDE CONDENSATE DRAIN LINE TO 1" P-TRAP BELOW MEZZANINE FLOOR AND ROUTE TO EXTERIOR WALL.
PROVIDE SPLASH BLOCK. CONDENSATE DRAIN LINE BY EQUIPMENT INSTALLER. MAINTAIN AIR GAP PER CODE. 4 9/14/16 INTERACTIVE REVIEW COMMENTS
3 09/07/16 PERMITTING COMMENTS
(80 CFH)

2 08/15/16 ADDENDUM 2
1"G

1 08/10/16 PERMITTING COMMENTS


2" CW
NO: DATE: DESCRIPTION:
REVISIONS
PROJECT NUMBER:
2151374
DRAWN BY:
PAV/DWM
REVIEWED BY:
1/2" BB
ISSUED FOR:
CONSTRUCTION
DATE:
07.25.16
DRAWING NAME:

4 3/4"G
(40CFH)
3/4"G
(40CFH)
24 PLUMBING
4
1-1/2" CWS
MEZZANINE PLAN
1/2"
1/2" CW
1-1/2"

23 26 25 DRAWING NUMBER:
MECKLENBURG COUNTY
CODE ENFORCEMENT
00/00/0000 00:00AM

1 PLUMBING MEZZANINE PLAN


P-102
The Design In These Construction
P102 1/4" = 1'-0" Documents Have Been Reviewed For
Compliance With The State Building
Code. It Is The Responsibility Of The
FLPTH

N Contractor To Construct This Project


With Good Engineering Practice And
In Compliance With The North
Carolina State Building Code.
455 South Main Street Engineering
Davidson, NC 28036 Architecture
P: (704) 439-2931 Environmental
Planning

www.labellapc.com

NC LICENSE NO. C-0430


ASS O CI AT
H CARO L LA ES
RT I EL CH
I TE C TU R A
O L

B
AR
E S S IO N

NA

P.
C

LA
OF

C.
N

O
ED

RP
R E GI S TE R
AL
PR

OR A
SEAL CERT. NO.

TI ON
030515 52904
EN
G I N EER NO

CR

E
RT NA
AI H CAROLI

H
CH
G S. BLYT C

.
AR
L OT TE , N .

9/16/2016
9/9/2016

© 2016 LaBella Associates

TOWN OF DAVIDSON
216 South Main Street,
Davidson, NC 28036

FIRE STATION #2
19436 DAVIDSON CONCORD ROAD,
DAVIDSON, NC 28036

5 9/16/16 INTERACTIVE REVIEW COMMENTS


4 9/14/16 INTERACTIVE REVIEW COMMENTS
3 09/07/16 PERMITTING COMMENTS
2 08/15/16 ADDENDUM 2
1 08/10/16 PERMITTING COMMENTS
NO: DATE: DESCRIPTION:
REVISIONS
PROJECT NUMBER:
2151374
DRAWN BY:
PAV/DWM
REVIEWED BY:
BB
ISSUED FOR:
CONSTRUCTION
DATE:
07.25.16
DRAWING NAME:
3 1

PLUMBING RISER DIAGRAM

DRAWING NUMBER:
MECKLENBURG COUNTY
CODE ENFORCEMENT
00/00/0000 00:00AM

P-401
The Design In These Construction
Documents Have Been Reviewed For
Compliance With The State Building
Code. It Is The Responsibility Of The
FLPTH

Contractor To Construct This Project


With Good Engineering Practice And
In Compliance With The North
Carolina State Building Code.
INSTALL WATER HAMMER GALVANIZED OR STAINLESS
ARRESTOR JUST BEFORE LAST 3/4"HW 3/4"CW 455 South Main Street Engineering
STEEL TO MATCH SAFETY
FIXTURE ON BRANCH LINE SHOWER EQUIPMENT Davidson, NC 28036 Architecture
INSTALL WATER HAMMER P: (704) 439-2931 Environmental
MEMBRANE CLAMPING ARRESTOR ON ALL LOCKABLE BALL VALVE
Planning
COLLAR AND SEEPAGE PAN FIXTURES WITH QUICK
CLOSING VALVES.
PROVIDE CLEANOUT TEE WITH SCREWED INSTALL AN ADDITIONAL WATER www.labellapc.com
COUNTERSUNK ABS PLASTIC PLUG. CLEANOUT HAMMER ARRESTOR IF THE BRANCH
CONCRETE FLOOR
FACE SHALL BE WITHIN 4" OF WALL SURFACE. SINGLE OR LINE IS GREATER THAN 20' LONG.
PROVE EXTENSION IF REQUIRED DOUBLE FIXTURE
MULTIPLE FIXTURES
PROVIDE A ROUND 18 GAUGE REDUCING TRAP
STAINLESS STEEL COVER FOR
CONSEALED CLEANOUTS PDI PIPE FIXTURE WATER SUPPLY FIXTURE UNIT (WSFU)
SIZE SIZE UNIT LOAD FIXTURE COLD HOT
MAXIMUM TAILPIECE 1" TW
HUB AT FLOOR MAXIMUM 12' WHERE A 1/2" 1-11 VALVE WATER CLOSET 5 --
LENGTH IS 2 FEET PULL-ROD HANDLE
ENLARGED 4" WASTE LINE IS
SLOPE WASTE AT TWO AT 69" A.F.F.
USED AS A COMBINATION B 3/4" 12-32 URINAL 4 -- CHECK
PERCENT
WASTE AND VENT SYSTEM EMERGENCY FACE VALVES
C 1" 33-60 LAVATORY/SINK 1.5 1.5 WASH/EYE
PROVIDE TRAP PRIMER IF REQUIRED BY
LOCAL AUTHORITIES OTHERWISE MAXIMUM 8' ON 2" D 1-1/4" 61-113 JANITOR'S SINK 3 3
LONG SWEEP AT END OF LINE DEEP-SEAL P-TRAP WASTE OR 10' ON 3".
TMV - NAVIGATOR
OR COMBINATION WYE COMMENTS:
E 1-1/2" 114-154 NC LICENSE NO. C-0430

33" - 45" A.F.F.


EFX S19-2100 WITH

42" AFF
1. LOCATE FLOOR DRAIN/SINK WHERE SHOWN ON DIMENSIONED FLOOR PLAN. IF SITUATION IS F 2" 154-330 CABINET
COMBINATION DRENCH ASSOCI AT
FLOOR SLAB ON GRADE, SET DRAIN BODY IN PLACE, PROVIDE BACKFILL, AND POUR T H CARO L LA ES
EL
OR
I TE C TU R A
AROUND IT. RECESS TOP OF FLOOR DRAINS 1/2" BELOW FLOOR DATUM AND SLOPE FLOOR SHOWER AND CH L

IN

B
AR
E S S IO N

P.
C

LA
COMMENTS: OF

C.
N

OR
EYE/EYE-FACE WASH

ED
TO IT. DO NOT RECESS FLOOR SINKS.

PO
R E GI S TE R
AL
PR
1. WATER HAMMER ARRESTERS SHALL BE HAVE PISTON AND 0-RING CONSTRUCTION WITH

R A TI ON
COMMENTS: 2. OTHER VENTING METHODS MAY BE USED, IF APPROVED BY LOCAL CODE AND/OR LOCAL BRADLEY MODEL S19-310 SEAL CERT. NO.
PDI #WH-201, ASSE # 1010 AND ANSI # A112.26.1M CERTIFICATION. INSTALL IN HORIZONTAL 030515 52904
PROVIDE WALL CLEANOUT (WCO) WHERE SHOWN AUTHORITIES. OR VERTICAL POSITION, BUT NEVER UPSIDE DOWN. SIZE THE UNITS AS SHOWN PER THE
ON PLAN AND ON SANITARY WASTE BRANCHES FLOOR LINE EN
TABLES SHOWN ABOVE. G INEER NO

CR

E
RT NA
NOT SERVED WITH A FLOOR CLEANOUT. AI H CAROLI

H
CH
G S. BLYT AR
L OT TE , N .
C
.

1 WALL CLEANOUT 2 FLOOR DRAIN AND SINK DETAIL 3 WATER HAMMER ARRESTER DETAIL 4 SAFETY SHOWER AND EYEWASH DETAIL 9/9/2016
NONE NONE NONE NONE
© 2016 LaBella Associates

ALL-THREAD ROD.
LENGTH AS REQ'D FOR
TOWN OF DAVIDSON
WALL PIPE SLOPE. 216 South Main Street,
Davidson, NC 28036
WATER CLOSET STORM COLLAR

2'-0" MIN.
TOP BEAM C-CLAMP KHW 140°F (IN) CW (IN)
IF STEEL BAR JOIST. PROVIDE COPPER OR STEEL DECK
VENT SEAT ADJUSTABLE BAND NON-METALLIC SEAL ALL AROUND
HANGER FOR COATING WHERE
CHASE PIPING FOUR INCH HANGERS CONTACT FLASHING SKIRT
OR LESS. BARE COPPER PIPE. CLEVIS HANGER FOR PIPE
BALL VALVE
OVER FOUR INCH. FLASHING BY ROOFING
NOTES: (TYP.)
C.W. SUPPLY
CONTRACTOR
PLAN VIEW 1. FOR CONTINUATION OF PIPING SEE PLANS. ANCHOR PIPE TO ROOF DECK OR JOISTS WITH
2. MINIMUM CHASE SPACE SHOWN MUST BE CLEAR SPACE. U-BOLT AROUND PIPE AND ANGLE IRON
DO NOT HANG PIPE LARGER THAN 4" PROVIDE GALVANIZED STEEL SADDLE FOR ALL WELD- ED OR SCREWED TO DECK OR JOIST
ROOF
FROM BOTTOM OF JOISTS, AND HANG INSULATED PIPE 1" AND LARGER. VERIFY
ONLY AT PANEL POINT. INSULATION THICKNESS WHEN SIZING HANGERS. H C
OPENING IN ROOF
DO NOT SUSPEND OTHER ITEMS FROM PIPE. HUBLESS PIPE CONNECTORS
PROVIDE PIPE INCREASER ON CAST IRON PIPE.
M WATTS MMV ASSE 1070
WHERE REQUIRED TO MAKE
VENT MINIMUM 3" VENT THRU ROOF MIXING VALVE WITH
FLUSH VALVE TEMPERATURE ADJUSTMENT
SEAT COMMENTS:
1. PROVIDE UPPER ATTACHMENT AS REQUIRED FOR CASES NOT SHOWN HERE. DO NOT INSTALL COMMENTS:
HANGER INSIDE INSULATION OR OTHERWISE PENETRATE VAPOR BARRIER. DO NOT HANG ONE PIPE UNION (TYP.)
1. REFER TO PLANS FOR VTR PIPE SIZES AND LOCATIONS.
WATER CLOSET FROM ANOTHER EXCEPT IN CHASES. TRAPEZE HANGERS MAY BE USED FOR MULTIPLE PARALLEL
HOLDRITE BRACING PIPES. SLOPE ALL WATER PIPING SLIGHTLY TOWARD DRAINABLE LOCATIONS. HANGER SPACING FOR 2. LOCATE VTR MINIMUM THREE FEET FROM PROPERTY LINE, OR TEN FEET
FINISHED FLOOR PIPE SIZE: COPPER: 2"=9' 1 1 2 "=8' 1 1 4 "=7' 1"=6' 3 4 "=6' 3 4 "=5'. CAST IRON: 10' AND ONE HORIZONTAL OR THREE FEET VERTICAL ABOVE ANY BUILDING OPENING OR
NEAR ALL JOINTS. STEEL: 3"=12' 2 1 2 "=11' 2"=10' 1 1 2 "=9' 1"=7' 3 4 "=6' 1 2 "=5'. LOCATE
CONCRETE SLAB
HANGERS AS CLOSE AS POSSIBLE TO TURNS AND TEES OF PIPE. PROVIDE SUPPLEMENTARY STEEL
FRESH AIR INTAKE, OR ONE FOOT FROM ANY VERTICAL SURFACE.
FIRE STATION #2
TW 110°F (OUT) 19436 DAVIDSON CONCORD ROAD,
STRUTS BETWEEN JOISTS IF REQUIRED. LOCATE HANGERS TO TAKE LOAD OFF OF EQUIPMENT 3. LOCATE VTR MINIMUM 18" FROM PARAPET, EXPANSION JOINT, EQUIPMENT
WATER CLOSET FLOOR FLANGE CONNECTIONS. ANCHOR WATER PIPE AGAINST SWAYING DUE TO CHANGES IN WATER VELOCITY. CURB, ETC. OFFSET IN CEILING SPACE WHERE REQUIRED TO MEET THESE DAVIDSON, NC 28036
ESCUTCHEON PROVIDE SEISMIC BRACING AS REQUIRED BY LOCAL AUTHORITIES. CHAINS OR PERFORATED STRAP CONDITIONS.
4" SAN TO NEAREST MAIN
IRON OR STEEL IS NOT ACCEPTABLE. DO NOT SUSPEND PIPE FROM JOIST BRACING MEMBERS.
4" SAN
REFER TO CODES AND SPECIFICATIONS FOR FURTHER INFORMATION.
ELEVATION

5 FL MTD TANK TYPE WATER CLOSET DETAIL 6 PIPE HANGER DETAIL 7 VENT THRU ROOF (VTR) DETAIL 8 THEMOSTATIC MIXING VALVE
NONE NONE NONE NONE

3 09/07/16 PERMITTING COMMENTS


GAS BRANCH TO EQUIPMENT PIPING HANGER SUPPORTS
2 08/15/16 ADDENDUM 2
CONNECT VENT SYSTEM EXTEND 1/2" HW, 1/2" CW AND G 1 08/10/16 PERMITTING COMMENTS
ABOVE CEILING 1-1/2" VENT ABOVE CEILING AND NO: DATE: DESCRIPTION:
HOT WATER RECIRCULATING PUMP
CONNECT TO NEAREST ACTIVE MAIN. REVISIONS
1-1/2" PIPE BALANCING VALVE (TYPICAL) PROJECT NUMBER:
THERMOMETER (TYPICAL)
PROVIDE CONNECTION
2151374
WALL WALL PIPE INSULATION PIPE SLEEVE 1/2" HW
1/2" CW TO DOMESTIC
(WHERE REQ'D) 1-1/2" DRAWN BY:
HOT & COLD WATER AND PAV/DWM
1/2" CW HOT WATER RECIRCULATION T & P VALVE REVIEWED BY:
1/2" HW CONTINUOUSLY WELDED WATER BB
V

PIPING.
LAVATORY SUPPORT WATERPROOF CAULK STOP & ANCHOR COLLAR,
WATERPROOF FLOORS ONLY. MIN. SHUT OFF VALVE (TYPICAL) ISSUED FOR:
FOR CONCEALED ARM
1" ALL OTHERS TO HAVE ANCHOR CABINET VENT LINE CONSTRUCTION
LUGS (MIN. 3 REQ'D). FROM SINK UNION (TYPICAL)
LAVATORY EXPANSION DATE:
SINK
TANK 07.25.16
6"

CUT OPENING IN EXISTING


WASTE LINE

G
1-1/2" P-TRAP FROM SINK DRAWING NAME:
STOP
1-1/2" VALVE TYP. MANUAL SHUT-OFF VALVE ( GAS COCK) WITH AN 1/8"
N.P.T. PLUGGED TAPPING ACCESSIBLE FOR TEST WH-1
1-1/4" GAGE CONNECTION TO BE INSTALLED UPSTREAM OF
WASTE THE GAS SUPPLY CONNECTION TO THE APPLIANCE
STOP VALVE TYP. CONCRETE FLOOR SLAB LATERIAL DRAIN VALVE 3 1
METAL DECK
CUT OPENING IN EXISTING
PRESSURE INJECT EPOXY GROUT
TO COMPLETELY FILL ANNULAR
6" DRIP LEG
WITH CAP DRAIN PAN
PLUMBING DETAILS
PRESSURE INJECT EPOXY SPACE BETWEEN PIPE AND WALL . EXTEND 1/2" HW, 1/2" CW AND
P-TRAP W/CO SEE SPECIFICATION 030130 1-1/2" VENT ABOVE CEILING
GROUT TO COMPLETELY FILL ROUTE TO
MAINTENANCE OF CONCRETE. AND CONNECT TO NEAREST MEZZANINE FLOOR 2" WASTE
1-1/2" ANNULAR SPACE BETWEEN EXTERIOR WALL
PIPE AND WALL . SEE ACTIVE MAIN. GROUND JOINT UNION
FLOOR P-TRAP
SPECIFICATION 030130 FIRE RESISTANT
MAINTENANCE OF CONCRETE. SILICONE FOAM SEALER
COMMENTS: DRAWING NUMBER:
MECKLENBURG COUNTY 1. PIPING SHOWN IS SCHEMATIC. PROVIDE CLEARANCES RECOMMENDED BY
CONNECT WASTE PIPING TO CODE ENFORCEMENT MANUFACTURER. PROVIDE SEISMIC STRAPPING AS REQUIRED.
00/00/0000 00:00AM

SANITARY MAIN BELOW FLOOR 2. SET THERMOSTAT AT 130°F.

P-501
The Design In These Construction
Documents Have Been Reviewed For
9 LAVATORY DETAIL 10 TYPICAL PIPE SLEEVE THROUGH FLOOR DETAIL 11 COUNTERTOP SINK DETAIL
Compliance With The State Building 12 WATER HEATER DETAIL
Code. It Is The Responsibility Of The
FLPTH

NONE NONE NONE NONE


Contractor To Construct This Project
With Good Engineering Practice And
In Compliance With The North
Carolina State Building Code.
WASHING MACHINE
BOX (WMF-X)

455 South Main Street Engineering


Davidson, NC 28036 Architecture
WATER HAMMER P: (704) 439-2931 Environmental
2 2
ARRESTOR (WHA-X) Planning
NOTES: EXTENSION UP

HW(125)
TO GRADE
1 " TEMPERED(T) WATER FROM
SHOWER SH-1(ADA). EXTEND www.labellapc.com

CW
1 2
MIXING VALVE TO SHOWER HAND HELD SPRAY SYSTEM WITH CAPPED TEST TEE 4"
INLET
HOSE VALVE VACUUM BREAKER AND 60" HOSE. RUN PIPING IN WALL
CONNECTION 1-1/2" VENT CHASE AND ABOVE CEILING.
4 GENERATOR SHUT-OFF VALVE, LABELED IN
2 DROP12" H&C WATER DN TO TEMPERATURE CONTROL ACCORDANCE WITH NFPA 110
C.O.
PRESSURE REGULATOR INLET
MIXING VALVE. RUN PIPING IN WALL CHASE.
1/2" 3 THERMOSTATIC TEMPERING VALVE SERVING SHOWER 3" NG GAS TO GAS PRESSURE OIL SEPARATOR
1/2"
1 " TEMPERED WATER TO HAND HELD
SH-2(ADA). CONNECT BOOSTER SYSTEM
2
1 SHOWER AND TO DIVERTER VALVE AND SHOWER HEAD. 3" NG TO BUILDING
UNION (TYPICAL)
1/2" 4 SHOWER HEAD. EXTEND 1/2" CW FROM DIVERTER VALVE EQUIPMENT PAD
CWS HWS
TO SHOWER HEAD PIPING TO BE CONCEALED IN WALL 12" MIN. DIRT LEG 4" SEE DETAIL
CHASE.
3

72"
GAS METER
1/2" 5 SHOWER FLOOR DRAIN. MAIN SHUT-OFF VALVE OUTLET 3"
GRADE

48"
6 2" VENT PIPE RUN TO NEAREST WALL AND UP TO VENT 3"
SEPARATOR VENT
SYSTEM IN CEILING.
GAS MAIN BY GAS
OIL STORAGE VENT
COMPANY
7 3" WASTE PIPING. EXTEND PIPING TO NEAREST MAIN. PITCH TO
2" TRAP AND 2" WASTE 5 DRAIN MIN 1/8" PER FT. G NOTE:
NC LICENSE NO. C-0430
42" AFF WASTE PIPE RUN VENTS BELOW GRADE TO BUILDING
WALL. EXTEND UP WALL TO ABOVE ROOF
AND ANCHOR VENTS SECURELY TO WALL. ASSOCI AT
T H CARO L LA ES
I EL
OR
6 2" VENT PIPE NOTES: RC
H I TE C TU R A
L

B
E S S IO N

NA

P.
A C

LA
OF

C.
N

OR
ED
GAS METER AND REGULATOR SHALL

PO
R E GI S T E R
AL
PR
7 3" SANITARY PIPE BE BY THE LOCAL GAS COMPANY.

R ATI ON
SEAL CERT. NO.
FINISHED FLOOR 030515 52904
3" P-TRAP
EN
G INEER NO

CR

E
RT NA
AI H CAROLI

H
CH
G S. BL YT AR
L OT T E , N .
C
.

1 WASHING MACHINE BOX DETAIL 2 ADA SHOWER DETAIL 3 GAS METER DETAIL 4 OIL SEPARATOR DETAIL 07/25/16
NONE NONE NONE NONE
© 2016 LaBella Associates

P&G CHEMICAL
TOWN OF DAVIDSON
DISPENSER 216 South Main Street,
Davidson, NC 28036
MEMBRANE CLAMP FLOOR SLAB ON GRADE HW AND CW ISOLATION VALVES P&G
CHEMICAL BOTTLE

HW AND CW PIPING
SAME SIZE AS SEWER UP TO 4" (RUN BESIDE EACH OTHER IN WALL) FAUCET AND VALVES
AS REQUIRED FOR MAXIMUM.
DEPTH OF SEWER
JANITOR'S SINK
LONG SWEEP ELBOW AT END OR
HUB AND SPIGOT
TURN OF RUN.
CAST IRON PIPE
BELOW FLOOR. FIAT FAUCETS
COMBINATION WYE AND EIGHTH MODEL 830-AA
SANITARY SEWER BEND IN RUN. ENTER TOP OF
LINE PIPE. FINISHED FLOOR

DIRECTION OF
FLOW COMMENTS:
1. EACH CHEMICAL DISPENSER MUST HAVE A DEDICATED WATER SUPPLY, LOCATED WITHIN 4 FEET OF
MOP SINK MS-1 THE DISPENSER. IT MUST PROVIDE TEMPERED WATER (ADJUSTABLE FROM 60-120F) WITH A FLOW
COMMENTS:
1. LOCATE AT BUILDING EXIT, AT ENDS OF RUNS, AT TURNS OF PIPE GREATER RATE OF 4 GPM AT 40 PSI DYNAMIC/FLOWING PRESSURE (35 PSID MIN.). THE HOT AND COLD
THAN 45 DEGREES, AT 50' INTERVALS ON STRAIGHT RUNS, AND/OR WHERE WATER SUPPLY LINES MUST HAVE CHECK VALVES TO PREVENT HOT/COLD WATER CROSSOVER, IF
SHOWN ON PLANS. PROVIDE BACKFILL PER ARCHITECTURAL SPECIFICATIONS. THE TEMPERING VALVE DOES NOT INCLUDE THEM. IT MUST INCLUDE A SHUTOFF VALVE TERMINATING
LOCATE CLEANOUTS WHERE THERE IS 18" CLEAR AROUND. CONSULT LOCAL FINISHED FLOOR IN A 43 " GARDEN HOSE MALE FITTING.
CODES FOR OTHER FCO REQUIREMENTS.
TO VENT MAIN.
2" VENT PIPING 2. THE DEDICATED WATER SUPPLY SHOULD NOT HAVE ANY BACKFLOW PREVENTION (E.G. NO FIRE STATION #2
2. ROUND SECURED GASKETED NICKEL BRONZE ADJUSTABLE TOP WITH "CO" ATMOSPHERIC VACUUM BREAKER, ETC.), UNLESS REQUIRED BY THE LOCAL PLUMBING CODE OR
CAST IN COVER. PROVIDE CLEANOUT TOP WITH VARIATIONS SUITABLE FOR 3" SANITARY PIPING
TO SANITARY MAIN.
UTILITY- EACH CHEMICAL DISPENSER INCLUDES AN INTEGRAL BACKFLOW PREVENTOR ASSE 1055)
19436 DAVIDSON CONCORD ROAD,
FLOOR COVERING (CARPET MARKER, RECESSED FOR TILE, SCORIATED FOR DAVIDSON, NC 28036
UNFINISHED FLOORS). PROVIDE GASKETED PLASTIC PLUG IN CAST IRON BODY.
USE TEFLON JOINT COMPOUND ON PLUG THREADS. CLEAN THE TOP OF
EXPOSED FCO AFTER INSTALLATION.

5 6 FLOOR CLEANOUT DETAIL 7 MOP SINK DETAIL 8 CHEMICAL SYSTEM AT JANITOR'S SINK
NONE NONE NONE NONE

PAVEMENT
SEE NOTE 4 EXPANSION JOINT TO PER
ENGINEER'S DETAILS -- -- --
DESIGN
SEE NOTE 3 DOCUMENTS NO: DATE: DESCRIPTION:
REVISIONS
PACK ANNULAR SPACE SOLID STUD AND GYPSUM WALLBOARD WALL
WITH FIBERGLASS INSULATION PROJECT NUMBER:
CONSTRUCTION: PROVIDE GALVANIZED
3 THICKNESS 2151374
(FOR ACOUSTICS). STEEL PIPE OR MINIMUM 18 GA 4"
CW OPTIONAL WATER
GALVANIZED SHEET METAL SLEEVE. FEED FROM ABOVE
DRAWN BY:
CAULK OR GROUT SLEEVE IN PLACE AS BUILDING EXTERIOR PAV/DWM
10" 10"
REQUIRED. REVIEWED BY:
OPERATING ROD AND CASING BB
LENGTH = WALL DEPTH + 2"
FLEXIBLE SAFETY VALVE ISSUED FOR:
CONSTRUCTION

10"
PIPE OR CONDUIT ACCESS PANEL CONNECTION
LOCATION BASED PRESSURE RELIEF VALVE UNION
ON PIPE FEED WALL BOX DATE:
SET FOR 50 P.S.I. COMPRESSOR
3 07.25.16
UNINSULATED PIPE UNION 4"
HOSE W/PRESSURE GAUGE AND TANK
SHUTOFF VALVE CONNECTION
DRAWING NAME:

INSULATED PIPE
NOTES: TO COMPRESSED
WALL BOX 1. IT IS NECESSARY TO ENSURE MINIMUM DIMENSIONS SHOWN ARE SUITABLE FOR EXISTING AIR LOOP VIBRATION
GROUND CONDITIONS. ENGINEERING ADVICE MAY BE REQUIRED. ISOLATORS (TYP.
BUILDING INTERIOR
EXPOSED PIPE SHALL HAVE 2. MINIMUM CONCRETE STRENGTH OF 4,000 PSI IS RECOMMENDED. CONCRETE SHOULD BE
FOR 4)
MIN

WALL CONSTRUCTION:
24"

PRE-CAST, POURED IN
PLACE OR MASONRY
ESCUTCHEON TO COVER
PENETRATION. 3.
VIBRATED TO ELIMINATE AIR POCKETS.
EXPANSION AND CONTRACTION CONTROL JOINTS AND REINFORCEMENT ARE RECOMMENDED TO
MOISTURE AND OIL
SEPARATOR FINISHED FLOOR PLUMBING DETAILS
3
PROTECT CHANNEL AND CONCRETE SURROUND. ENGINEERING ADVICE MAY BE REQUIRED.
BLOCK 4"
CW OPTIONAL WATER GRADE 4. THE FINISHED LEVEL OF THE CONCRETE SURROUND MUST BE APPROX. 1/8" [3mm] ABOVE THE
PROVIDE GALVANIZED STEEL PIPE DRAIN TO OUTSIDE OF BLDG. GATE VALVE
FEED FROM ABOVE TOP OF THE CHANNEL EDGE.
SLEEVE GROUTED INTO WALL.
5. CONCRETE BASE THICKNESS SHOULD MATCH SLAB THICKNESS. ENGINEERING ADVICE MAY BE
REQUIRED TO DETERMINE PROPER LOAD CLASS.
3 6. REFER TO ACO'S LATEST INSTALLATION INSTRUCTIONS FOR FURTHER DETAILS.
4" I.P.S. 7. S200k - POWER DRAIN - LOAD CLASS: E
COMMENTS: DRAWING NUMBER:
1. CENTER PIPE ALONG WITH THE INSULATION IN SLEEVE. CONTINUE THE MECKLENBURG COUNTY
INSULATION THRU THE SLEEVE. CODE ENFORCEMENT
00/00/0000 00:00AM

P-502
The Design In These Construction
Documents Have Been Reviewed For
9 PIPE PENETRATION (NON-RATED WALL) 10 FREEZE PROOF WALL HYDRANT DETAIL 11 TRENCH DRAIN DETAIL S200K POWERDRAIN
Compliance With The State Building
Code. It Is The Responsibility Of The
12 AIR COMPRESSOR DETAIL
FLPTH

NONE NONE NONE NONE


Contractor To Construct This Project
With Good Engineering Practice And
In Compliance With The North
Carolina State Building Code.
PLUMBING FIXTURE SCHEDULE 455 South Main Street Engineering
Davidson, NC 28036 Architecture
FAUCET/VALVE DRAIN PIPING CONNECTIONS P: (704) 439-2931 Environmental
OR APPROVED EQUAL BY ONE OF THE
FIXTURE DESCRIPTION ACCESSIBLE DESIGN MANUFACTURER & MODEL TYPE MATERIAL STYLE SUPPLIES & STOPS MOUNTING REMARKS Planning
FOLLOWING MANUFACTURERS MANUFACTURER
SPOUT HANDLES CENTERS TYPE SIZE VENT C.W. H.W.
MODEL NO.
AMERICAN STANDARD TWO PIECE, K-4199 ELONGATED BOWL, K-4467-RZ TOILET FLUSH TANK, K-4731-C TOILET SEAT, 3/8" NPT
P-1 WATER CLOSET YES
KOHLER HIGHLINE K-3999-RZ-0
GERBER FLUSH TANK VITREOUS CHINA
HANDICAP
- - - - FLOOR MTD 4" 2 1/2" - KOHLER K-7637-CP FLOOR ANGLE SUPPLY WITH STOP AND ANNEALED VERTICLE TUBEBATTERIES. HIGH EFFICIENCY TOILET 1.28 GPF. ADA
www.labellapc.com
FLOOR MTD TANK TYPE ELONGATED
ZURN COMPLIANT
AMERICAN STANDARD
KOHLER LEDENA K-2215 UNDER- RECTANGULAR KOHLER DM FAUCET KOHLER K-8998 P-TRAP, 0.5 GPM MAXIMUM FLOW-RATE, INCLUDES TWO AAA BATTERIES. PROVIDE 1139288 SPRAY AERATED. ADA
L-1 LAVATORY YES GERBER VITREOUS CHINA STANDARD SENSOR SINGLE-HOLE GRID 1-1/2" 1-1/2" 1/2" 1/2" DROP-IN
ADA 21" X 116-1/4" COUNTER BASIN K-13467 K-7129 DRAIN COMPLIANT, PROVIDE WITH TRUEBRO LAV GUARD UNDERSINK PIPING COVER MODEL #102 E-Z
ZURN
ADVANCE TABCO
SINK - COUNTER KOHLER CORALAIS ADA COMPLIANT, DOUBLE COMPARTMENT, INCLUDES INSTALLATION HARDWARE, TOP - MOUNT. PROVIDE
SK-1 YES KOHLER TOCCATA K-3346-4 ELKAY DOUBLE COMPT. STAINLESS 6" DEEP 2-HOLE GOOSENECK DOUBLE LEVER 8" GRID 1-1/2" 1-1/2" 1/2" 1/2" MCGUIRE 175LK & PW8090 COUNTER TOP
TOP DROP-IN K-15889-K K-15850-4M LEVER HANDLES WITH 1030920 SIDE SPRAY. SEE SD-1 ON SCHEDULE FOR DSPOSAL
JUST
INTERGRAL
K-10825-4 K-10591 REINFORCED POLYESTER RESIN SURROUND SHOWER ENCLOSURE AND BASE WITH GEL COAT, INTEGRAL FRONT
AQUA BATH SURROUND FIBERGLASS HANDICAP SINGLE LEVER WALL-MOUNT FRONT
COMFORT DESIGNS MODEL# XST DEVONSHIRE MULTIFUNCTI KOHLER K-304-CS VALE TRENCH DRAIN AND GRATE, HDPE FOLD-UP SEAT CURTAIN ROD, HORIZONTAL AND VERTICAL GRAB BARS,
SH-1 SHOWER YES
3838 TR RRF .75 L-BAR-I
AQUARIUS BATHWARE ENCLOSURE W./SANITARY SHOWER
SHOWERING ON SHOWER
K-304/K-P304 WITH SLIDE TRENCH 3" 2" 1/2" 1/2"
WITH STOPS
WALL
KOHLER ADA SHOWER SYSTEM WITH HAND HELD SHOWER ASSEMBLY W/SLIDE ABR, VACUUM BREAKER &60"
BEST BATH SYSTEMS W/BASE GELCOAT PACKAGE SERIES VALVE BAR & HOSE DRAIN W/.75
PACKAGE HEAD HOSE. (ADA/ANSI). INSTALL PER OWNER RECOMMENDATIONS.
l-BAR-I GRATE
JAY R. SMITH
FD FLOOR DRAIN - JOSAM WADE-TYLER ROUND TOP CAST IRON BRASS TOP - - - - CAST IRON SEE PLAN - - - - FLOOR PROVIDE: SEDIMENT BUCKET, TRAP PRIMER CONNECTION & VALVE
ZURN
JAY R. SMITH
WCO WALL CLEAN-OUT - JOSAM WADE-TYLER - CAST IRON - - - - - - 4" - - - - WALL -
ZURN
ACORN TERRAZZO WARE
MSB-1 MOP SINK YES
FIAT TERRAZZO MOP SERVICE BASIN
MUSTEE MOP SINK TERRAZZO
FLOOR MOUNTED
FIAT 830-AA FAUCET
WITH PAIL
FOUR ARM 8" GRID 3" 2 1/2" 1/2" - FLOOR
INCLUDES STRAINER AND PLUG, CSA APPROVED. PROVIDE WITH 832-AA HOSE BRACKET, 889-CC MOP HANGER NC LICENSE NO. C-0430
TSBC6010 MOP BASIN HOOK AND E-77-A GUARD.
SWAN STONE
ASSOCI AT
FIAT MODEL LTD II WALL HUNG
ACORN TERRAZZO WARE
DOUBLE BOWL
WALL HUNG
CP BLADE T H CARO L LA ES
I EL
OR
I TE C TU R A
SS-1 UTILITY SINK YES MUSTEE MOLDED STONE CABINET FIAT A1 4" FAUCET SWING SPOUT 4" GRID 2" - 1/2" 1/2" - FLOOR WALL MOUNTED STYLE - CABINET MOUNTED WITH , INCLUDES STRAINERS AND PLUGS. RC
H L

B
E S S IO N

NA

P.
SERV-A-SINK LAUNDRY SINK HANDLES A C

LA
OF

C.
N
SWANSTONE MOUNTED

OR
ED

PO
R E GI S T E R
AL
PR
JAY R. SMITH

R ATI ON
FLOOR CLEAN SEAL CERT. NO.
FCO
OUT
YES JOSAM 57000 WADE-TYLER ROUND TOP CAST IRON BRONZE PLUG - - - - CAST IRON 4" - - - - FLOOR PROVIDE WITH WATER TIGHT ABS PLUG 030515 52904
ZURN EN
JAY R. SMITH KEY G INEER NO

CR

E
FROST PROOF RT NA
AI H CAROLI

H
FPHB YES WOODFORD MB65-K WADE-TYLER - CHROME - - CYLINDER - - - - - 1/2 " - - WALL ASSE 1011 SINGLE CHECK ANTI-SIPHON VACUUM BREAKER, MODULAR BOX SYSTEM G S. BL YT
CH
C
.
HOSE BIB AR
L OT T E , N .
ZURN LOCK
JAY R. SMITH
PISTON OPERATED, WILL PRIME 1 TO 4 FLOOR DRAINS, DISTRIBUTION UNIT DU-4/DU-U, INSTALL PER
TP-1 TRAP PRIMER YES PRECISION P1-500 WADE-TYLER - BRASS - - - - - - - - 1/2 " - - -
MANUFACTURERS RECOMMENDATIONS.
ZURN 07/25/16
ACORN SAFETY SHOWERS
FLOOR EYE/FACE STANDARD DRAIN HEIGHT, 316 STAINLESS STEEL HANDLE, ANTI-FREEZE VALVE, HALO EYE/FACE WASH,
EYE WASH EYE WASH YES BRADLEY S19314 SERIES JAY R. SMITH - - - - - 4" 2 1 - - - FLOOR
MOUNTED WASHDOWN PROVIDE NAVIGATOR S19-2100 EFX25 EMERGENCY THERMOSTATIC MIXING VALVE FOR TEPID WATER. © 2016 LaBella Associates
GUARDIAN EQUIPMENT
JAY R. SMITH POLYESTER PROVIDE CLOSING CAP PART NUMBER 96823, IRON SLOTTED LONGITUDINAL GRATE ADA COMPLIANT, SECURED
TRENCH DRAIN RECESSED IN RECESSED IN
TD-1 YES ACO DRAIN S200K, SK2-1:SK2-11 ABT INC POLYMER POWER DRAIN - - - - TRENCH 4" 2 - - - POWER LOK LOCKING OR APPROVED EQUAL. INSTALL TRENCH DRAIN SYSTEM PER MANUFACTURERS
SYSTEM
MCNICHOLS INDUSTRIES
JAY R. SMITH
FLOOR

RECESSED IN
CONCRETE
POLYESTER
FLOOR
RECOMMENDATIONS.
RECESSED IN PROVIDE GRATE, FOUL AIR TRAP, DEBRIS STRAINER, INSTALLATION DEVICE, GRATE REMOVAL TOOL, GRATE
TOWN OF DAVIDSON
CB-1 CATCH BASIN ---- ACO DRAIN CATCH BASIN SK2-621D ABT INC POLYMER POWER DRAIN - - - - CATCH BASIN 4" 2 - - PROVIDE FOUL AIR TRAP
MCNICHOLS INDUSTRIES
FLOOR
CONCRETE
FLOOR SHALL BE IRON SLOTTED LONGITUDINAL, MODEL 72263 LOAD CLASS: E 216 South Main Street,
JAY R. SMITH
INFLOOR
STEEL w/ACID Davidson, NC 28036
LINT RECESSED IN PROVIDE JOSAM 61806 SERIES LINT INTERCEPTOR W/ACID RESISTANT COATING, NON-SKID COVER, GALVANIZED
LI-1 ---- JOSAM MODEL 61806 WADE-TYLER RESISTANT GRAVITY DRAIN - - - - - 4" 3" (2 REQ.) - - -
INTERCEPTOR W/EXTENSION FLOOR- STEEL BUCKET W/SS SCREENS. PROVIDE WITH EXTENSION AS NEEDED.
ZURN COATING
SINK
GENERAL ELECTRIC MOUNTED FOOD WASTE DISPOSER SHALL BE INSINKERATOR MODEL PRO EXCEL W/MULTIGRIND PLUS AND SOUNDSEAL
SD-1 SINK DISPOSAL --- INSINKERATOR PR5O XL KITCHEN AID UNDER SINK STAINLESS MULTI GRIND - - - - W/DISH 1-1/2" 1-1/2" - - 1-1/2" TRAP UNDER SINK PLUS TECHNOLOGIES, 1.0 HP MOTOR, AUTO-REVERSE GRIND SYSTEM FEATURE, STAINLESS STEEL GRIND
WASTE KING WASHER CHAMBER AND COMPONENTS. 1.0 HP/120V/60 HZ
DRAIN

GAS HOT WATER HEATER SCHEDULE LIVING AREA TANK WATER HEATER FLOW CALCULATIONS SHOCK ABSORBER SCHEDULE
WATER GAS INPUT GPH DELIVERED @ FIXTURE QTY. SIZE GPH TAG MANUFACTURER MODEL FIXTURE UNITS INLET SIZE
TAG LOCATION MANUFACTURER AND MODEL THERM. EFF. COMMENTS
CONNECTIONS (BTUH) 90 DEG F RISE
KITCHEN SINK 1 5 GPH 5
INSTALL PER MANUFACTURER'S MOP SINK 1 10 GPH 10 SA-1 JAY R. SMITH HYDROTOLS - 5005 1-11 3/4"
WH-1 MECHANICAL PLATFORM RHEEM GHE80ES-130(A) 2" 130,000 95% 170
RECOMMENDATIONS
SHOWER 2 30 GPH 60
INSTALL PER MANUFACTURER'S SA-2 JAY R. SMITH HYDROTOLS - 5010 12-32 1"
WH-2 TRUCK MEZZANINE RHEEM GHE80ES-130(A) 2" 130,000 95% 170 LAVATORY 2 5 GPH 10
RECOMMENDATIONS
SA-3 JAY R. SMITH HYDROTOLS - 5020 33-60 1"
TOTAL REQUIRED FLOW AT 70°F TEMPERATURE RISE = 85
SA-4 JAY R. SMITH HYDROTOLS - 5030 61-113 1"

SA-5 JAY R. SMITH HYDROTOLS - 5040 114-154 1"

PUMP SCHEDULE SA-6 JAY R. SMITH HYDROTOLS - 5050 155-330 1" FIRE STATION #2
TRUCK BAY TANK WATER HEATER FLOW CALCULATIONS 19436 DAVIDSON CONCORD ROAD,
TAG SERVICE LOCATION MANUFACTURER/MODEL HOUSING MATERIAL
MAX GPM @
VOLTS/PHASE/HZ HP COMMENTS FIXTURE QTY. SIZE GPH DAVIDSON, NC 28036
HEAD
SERVICE SINK 1 5 GPH 5
INSTALL PER
MECHANICAL MOP SINK 1 10 GPH 10
HWCP-1 DOM HW RECIRCULATION TACO 4PC80/0012-F4-1 BRONZE -LEAD FREE 48 115/1/60 1/8 MANUFACTURER'S
PLATFORM
RECOMMENDATIONS SHOWER 1 30 GPH 30
INSTALL PER
HWCP-2 DOM HW RECIRCULATION MEZZANINE TACO 4PC8/0012-F4-1 BRONZE-LEAD FREE 48 115/1/60 1/8 MANUFACTURERS DOMESTIC WASHER 1 30 GPH 30
RECOMMENDATIONS EQUIPMENT WASHER 1 30 GPH 30
LAVATORY 1 5 GPH 5

TOTAL REQUIRED FLOW AT 70°F TEMPERATURE RISE = 110

-- -- --
NO: DATE: DESCRIPTION:
REVISIONS
PROJECT NUMBER:
2151374
DRAWN BY:
PAV/DWM
REVIEWED BY:
BB
ISSUED FOR:
CONSTRUCTION
DATE:
07.25.16
DRAWING NAME:

PLUMBING SCHEDULES

DRAWING NUMBER:
MECKLENBURG COUNTY
CODE ENFORCEMENT
00/00/0000 00:00AM

P-601
The Design In These Construction
Documents Have Been Reviewed For
Compliance With The State Building
Code. It Is The Responsibility Of The
FLPTH

Contractor To Construct This Project


With Good Engineering Practice And
In Compliance With The North
Carolina State Building Code.