Distance Protection
Distance Protection
Distance Protection
Some numerical relays measure the absolute fault impedance and then
determine whether operation is required according to impedance boundaries
defined on the R/X diagram. Traditional distance relays and numerical relays
that emulate the impedance elements of traditional relays do not measure
absolute impedance.
Please note that this technical article is not about the basics of distance
protection. But, just in case, let’s say a few introduction words:
The basic principle of distance protection involves the division of the voltage at
the relaying point by the measured current. The apparent impedance so
calculated is compared with the reach point impedance. If the measured
impedance is less than the reach point impedance, it is assumed that a
fault exists on the line between the relay and the reach point.
At each stage of distance relay design evolution, the development of
impedance operating characteristic shapes and sophistication has been
governed by the technology available and the acceptable cost.
Since many traditional relays are still in service and since some numerical
relays emulate the techniques of the traditional relays, a brief review
of impedance comparators is justified.
Contents:
1. Amplitude and phase comparison
2. Plain impedance characteristic
3. Self-polarised Mho relay
4. Offset Mho/Lenticular characteristics
5. Fully Cross-Polarised Mho characteristic
6. Partially Cross-Polarised Mho characteristic
7. Quadrilateral characteristic
8. Protection against power swings
<="" ins="" data-adsbygoogle-status="done" style="box-sizing: border-box;
height: 280px; width: 336px; display: block;">
characteristic centred at the origin of the R/X diagram. If the sum and difference of V and I
Go back to contents ↑
Operation occurs for all impedance values less than the setting, that is, for all
points within the circle.
Vector AB represents the impedance in front of the relay between the relaying
point A and the end of line AB. Vector AC represents the impedance of
line AC behind the relaying point.
AL represents the reach of instantaneous Zone 1 protection, set to cover 80%
to 85% of the protected line.
1. It is non-directional. It will see faults both in front of and behind the relaying
point, and therefore requires a directional element to give it correct
discrimination.
2. It has non-uniform fault resistance coverage
3. It is susceptible to power swings and heavy loading of a long line because of
the large area covered by the impedance circle.
Directional control is an essential discrimination quality for a distance
relay, to make the relay non-responsive to faults outside the protected line. This
can be obtained by the addition of a separate directional control element.
The impedance characteristic of a directional control element is a straight line
on the R/X diagram, so the combined characteristic of the directional and
impedance relays is the semi-circle APLQ shown in Figure 2.
Figure 2 – Combined
directional and impedance relays
If a fault occurs at F close to C on the parallel line CD, the directional unit
RD at A will restrain due to current IF1. At the same time, the impedance unit is
prevented from operating by the inhibiting output of unit RD. If this control is not
provided, the under impedance element could operate prior to circuit breaker
C opening.
Reversal of current through the relay from IF1 to IF2 when C opens could then
result in incorrect tripping of the healthy line if the directional unit RD operates
before the impedance unit resets.
Go back to contents ↑
S2 = V-IZn
S1 = V
where:
The impedance reach varies with fault angle. As the line to be protected is
made up of resistance and inductance, its fault angle will be dependent upon
the relative values of R and X at the system operating frequency.
However, when setting the relay, the difference between the line angle θ and
the relay characteristic angle Ø must be known. The resulting characteristic is
shown in Figure 3 where GL corresponds to the length of the line to be
protected.
With Ø set less than θ, the actual amount of line protected, AB, would be equal
to the relay setting value AQ multiplied by cosine (θ−Ø).
AQ = AB / cos(θ−Ø)
Due to the physical nature of an arc, there is a non-linear relationship between
arc voltage and arc current, which results in a non-linear resistance. Using the
empirical formula derived by A.R. van C. Warrington, the approximate value of
arc resistance can be assessed as:
Ra = L × 28,710 / I1.4
where:
In the latter case, the earth fault resistance reduces the effective earth-fault
reach of a ‘mho’ Zone 1 element to such an extent that the majority of faults are
detected in Zone 2 time.
Go back to contents ↑
To avoid this, a shaped type of characteristic may be used, where the resistive
coverage is restricted.
Go back to contents ↑
percentage of voltage from the healthy phase(s) to the main polarising voltage as a substitute
phase reference. This technique is called cross-polarising, and it has the advantage of
preserving and indeed enhancing the directional properties of the mho characteristic.
By the use of a phase voltage memory system, that provides several cycles
of pre-fault voltage reference during a fault, the cross-polarisation technique
is also effective for close-up three-phase faults. For this type of fault, no
healthy phase voltage reference is available.
One additional benefit of applying cross-polarisation to a mho impedance element is that its
This effect is illustrated in Figure 6, for the case where a mho element has
100% cross-polarisation. With cross-polarisation from the healthy phase(s) or
from a memory system, the mho resistive expansion will occur during
a balanced three-phase fault as well as for unbalanced faults.
The expansion will not occur under load conditions, when there is no phase
shift between the measured voltage and the polarising voltage. The degree of
resistive reach enhancement depends on the ratio of source impedance to
relay reach (impedance) setting as can be deduced by reference to Figure 6.
Figure 6 – Fully cross-
polarised mho relay characteristic with variations of ZS/ZL ratio
It must be emphasised that the apparent extension of a fully cross-polarised
impedance characteristic into the negative reactance quadrants of Figure 7
does not imply that there would be operation for reverse faults.
For reverse faults, the effect is to exclude the origin of the impedance
diagram, thereby ensuring proper directional responses for close-up forward or
reverse faults.
Figure 7 – Illustration of
improvement in relay resistive coverage for fully cross-polarised characteristic
Fully cross-polarised characteristics have now largely been superseded, due to
the tendency of comparators connected to healthy phases to operate under
heavy fault conditions on another phase.
three earth-fault and three phase-fault loops. For these types of relay, mal-operation of
healthy phases is undesirable, especially when single-pole tripping is required for single-
phase faults.
Go back to contents ↑
Go back to contents ↑
7. Quadrilateral Characteristic
This form of polygonal impedance characteristic is shown in Figure 9. The
characteristic is provided with forward reach and resistive reach settings that
are independently adjustable. It therefore provides better resistive coverage
than any mho-type characteristic for short lines.
This is especially true for earth fault impedance measurement, where the
arc resistances and fault resistance to earth contribute to the highest values of
fault resistance.
maximum resistive reach in terms of the zone impedance reach. Recommendations in this
Figure 9 –
Quadrilateral characteristic
Quadrilateral elements with plain reactance reach lines can introduce reach
error problems for resistive earth faults where the angle of total fault current
differs from the angle of the current measured by the relay. This will be the case
where the local and remote source voltage vectors are phase shifted
with respect to each other due to pre-fault power flow.
This can be overcome by selecting an alternative to use of a phase current for
polarisation of the reactance reach line.
Go back to contents ↑
When the impedance enters the third zone the trip sequence is completed and
the circuit breaker trip coil can be energized at a favourable angle between
system sources for arc interruption with little risk of restriking.
Only an unstable power swing condition can cause the impedance vector to
move successively through the three zones.
Therefore, other types of system disturbance, such as power system fault conditions, will not