Shutdown Valve: B224 323 HPCL Rajasthan Refinery Limited Rajasthan Refinery Project Offsites

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Document No.

SHUTDOWN VALVE B224-323-79-DS-24411


PROCESS DATA SHEET Rev. No. A
Page 1 of 1
PROJECT RAJASTHAN REFINERY PROJECT CLIENT HPCL RAJASTHAN REFINERY LIMITED
UNIT OFFSITES JOB NO. B224 UNIT NO. 323
TAG NO. 323-ROSOV-41101
SERVICE HEXANE FEED T-1048
LOCATION 4"-P-323-41102-A41A
FLUID HYDROCARBON
FLUID STATE LIQUID
OPERATING CONDITIONS
INLET TEMPERATURE DEG C AMBIENT
INLET PRESSURE KG/CM2 G 0-2
FLOW RATE LPH
NORMAL KG/HR M3/HR
MINIMUM M3/HR M3/HR
MAXIMUM NM3/HR 55 M3/HR
PRESSURE DROP LPM
@ NORMAL FLOW KG/CM2
@ MINIMUM FLOW KG/CM2
@ MAXIMUM FLOW KG/CM2
LIQUID PROPERTIES @ P & T
DENSITY KG/M3 640-670
VISCOSITY CP 0.4-0.5
GAS / VAPOUR PROPERTIES @ P & T
MOLECULAR WEIGHT
COMPRESSIBILITY FACTOR
CP/CV
DESIGN CONDITIONS
DESIGN TEMPERATURE DEG C 65
DIFF. PRESSURE @ SHUT-OFF KG/CM2 19.0
PARAMETERS IF FLASHING LIQUID OR TWO PHASE
LIQ. VAP. PRESS. @ OP. TEMP. KG/CM2 A
CRITICAL PRESSURE KG/CM2 A
WT % VAPOR AT INTLET IF TWO PHASE
WT % VAP. AT OUTLET IF FLASHING LIQ./ TWO PHASE
FOR SELF ACTUATED PR. REG. VALVES
CONTROLLED SIDE
SET POINT KG/CM2 G
TSO REQUIRED YES
FIRE SAFE REQUIRED YES
HAND WHEEL REQUIRED YES
QUICK CLOSING REQUIRED YES NO
QUICK OPENING REQUIRED NO NO
LIMIT SWITCH REQUIREMENT
FULL OPEN FO YES
FULL CLOSED FC YES
FAILURE POSITION FL FC
IBR CERTIFICATE REQUIRED NO
NOTE NO. 1,2,3,4,5,6
NOTES:
1. REFER P&ID NO. B224-79-41-323-11411.
2. REFER DETAIL-B OF P&ID B224-79-41-323-1193 FOR TANK BODY REMOTE OPERATED SHUT-OFF VALVE.
3. VALVE TO BE FULL BORE LINE SIZE ON/OFF VALVE. IT SHALL BE TRIPLE OFFSET BUTTERFLY TYPE VALVE.
4. ROSOV SHALL BE FIRE SAFE. THE ACTUATOR AND ACCESSORIES SHALL ALSO BE FIRE SAFE.
5. ROSOV SHALL HAVE OPEN/CLOSE PROVISION FROM FIELD AND ONLY CLOSE PROVISION FROM CONTROL ROOM.
ONE EMERGENCY CLOSE BUTTON (ECB) SHALL BE PROVIDED OUTSIDE THE DYKE FOR ACTUATING CLOSURE OF THE ROSOV
OVERRIDING ALL THE CONTROLS AND LOGIC.
6. ROSOV OPEN/CLOSE INDICATION SHALL BE AVAILABLE IN CONTROL ROOM.

A 05.09.2019 ISSUED FOR TENDER AC PD VRK


Prepared Reviewed Approved
Rev.No. Date Purpose
By By By

Format No,3-0411-1061 Rev. 0 Copyrights EIL - all rights reserved

Page 575 of 2375