CENTRIFUGAL PUMPS 1 OF 3
Revision A B
Issue IDC Implementation Issue
Date 3/14/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client
LIQUID Water
VISCOSITY cSt @ 5oC 1 S G @ 5oC 1 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA
Edge of B'plate
9755-DAT-ME-021
Equipment Data Sheet
CENTRIFUGAL PUMPS 2 OF 3
TYPE NOTE 4
SupplierR STA TYPE STA
DRIVER
DRIVER
REMARKS
REMARKS
SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS
WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT
9755-DAT-ME-021
Equipment Data Sheet
CENTRIFUGAL PUMPS 3 OF 3
QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA
SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE
HYDROTEST ü
PERFORMANCE ü
NPSH ü
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST
TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER Engine operation and
control panel operation
Note 1 The pumps shown on this Data Sheet will be used as the main diesel engine driven pumps to supply a firewater system.
The maximum flow will be 150% of the rated flow in accordance with the requirements of NFPA 20. The pump shall be capable
of operating at zero flow for a period of 2 hours. The driver shall be rated accordingly.
Note 2 The rotation shall be to suit the application. The suction flange shall be on the right side and the discharge flange shall be
NOTES
9755-DAT-ME-021
Equipment Data Sheet
CENTRIFUGAL PUMPS 1 OF 3
Revision A B
Issue IDC Implementation Issue
Date 3/14/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client
LIQUID Water
VISCOSITY cSt @ 5oC 1 S G @ 5oC 1 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA
Edge of B'plate
9755-DAT-ME-020
Equipment Data Sheet
CENTRIFUGAL PUMPS 2 OF 3
TYPE NOTE 4
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 4 PHASE HERTZ ENCLOSURE NOTE 4
kW RATING STA VERTICAL HORIZONTAL
DRIVER
REMARKS
SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS
WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT
9755-DAT-ME-020
Equipment Data Sheet
CENTRIFUGAL PUMPS 3 OF 3
QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA
SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE
HYDROTEST ü
PERFORMANCE ü
NPSH ü
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST
TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER
Note 1 The pump shown on this Data Sheet will be used as the electrically driven pump to supply a firewater system. The maximum flow
will be 150% of the rated flow in accordance with the requirements of NFPA 20. The pump shall be capable of operating
at zero flow for a period of 2 hours. The driver shall be rated accordingly.
Note 2 The rotation shall be to suit the application. The suction flange shall be on the right side and the discharge flange shall
NOTES
9755-DAT-ME-020
Equipment Data Sheet
CENTRIFUGAL PUMPS 1 OF 3
Revision A B
Issue IDC Implementation Issue
Date 3/14/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client
LIQUID Water
VISCOSITY cSt @ 5oC 1 S G @ 5oC 1 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA
Edge of B'plate
9755-DAT-ME-019
Equipment Data Sheet
CENTRIFUGAL PUMPS 2 OF 3
TYPE NOTE 4
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 4 PHASE HERTZ ENCLOSURE NOTE 4
kW RATING STA VERTICAL HORIZONTAL
DRIVER
REMARKS
SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS
WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT
9755-DAT-ME-019
Equipment Data Sheet
CENTRIFUGAL PUMPS 3 OF 3
QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA
SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE
HYDROTEST ü
PERFORMANCE ü
NPSH ü
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST
TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER
Note 1 The pump shown on this Data Sheet will be used as a jockey pump to maintain the pressure in a wet fire hydrant system.
The pump flow will reduce to zero as the hydrant pressure builds up to its set pressure.
Note 2 The rotation shall be to suit the application. The suction flange shall be on the end and the discharge flange shall be on the top
when viewed from the driver end.
NOTES
REMARKS
9755-DAT-ME-019
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 1 OF 3
Revision A B
Issue IDC Implementation Issue
Date 3/10/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client
LIQUID Jet A1
VISCOSITY cSt @ 5oC 2.2 S G @ 5oC 0.8 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA
9755-DAT-ME-018
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 2 OF 3
Supplier'S STANDARD ü
NOTE 3 BEARING HOUSING STA
MATERIALS
TYPE NOTE 4
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 4 PHASE HERTZ ENCLOSURE NOTE 4
kW RATING STA VERTICAL HORIZONTAL
DRIVER
REMARKS
SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS
WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT
9755-DAT-ME-018
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 3 OF 3
QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA
SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE
HYDROTEST ü
PERFORMANCE ü
NPSH ü
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST
TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER
Note 1 The pump shown on this Data Sheet will be used to transfer recovered JetA1 fuel from a horizontal separator tank to a horizontal
storage tank at the road offloading area. Add 1.7 bar to the discharge pressure (to allow for the internal relief valve) when sizing the
motor.
Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 Do not use zinc, copper, cadmium and their alloys for parts in contact with the fuel.
NOTES
REMARKS
9755-DAT-ME-018
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 1 OF 3
Revision A B
Issue IDC Implementation Issue
Date 3/10/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client
LIQUID Jet A1
VISCOSITY cSt @ 5oC 2.2 S G @ 5oC 0.8 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA
CAPACITY (NOTE 1) m3/hr 250 NPSH REQUIRED - RATED CAP m H20 STA
SUCTION PRESSURE BARG - 0.11 SUCTION SPECIFIC SPEED STA
DISCHARGE PRESS. BARG + 6.95 MAX SOUND PRESS. LEVEL dBA 85
DIFFERENTIAL PRESS BAR 7.06 DIFFERENTIAL HEAD m 90
DESIGN
9755-DAT-ME-017
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 2 OF 3
Supplier'S STANDARD ü
NOTE 3 BEARING HOUSING STA
MATERIALS
TYPE NOTE 4
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 4 PHASE HERTZ ENCLOSURE NOTE 4
kW RATING NOTE 1 STA VERTICAL HORIZONTAL
DRIVER
REMARKS
SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS
WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT
9755-DAT-ME-017
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 3 OF 3
QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA
SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 7 OBSERVE
HYDROTEST ü
PERFORMANCE ü
NPSH ü
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST
TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER
Note 1 The pumps shown on this Data Sheet will be used to transfer JetA1 fuel from two horizontal storage tanks at the road offload area to
the main depot storage tanks. Add 1.7 bar to the discharge pressure (to allow for the internal relief valve) when sizing the motor. They
will be used independently or with two simultaneously in a parallel arrangement.
Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 Do not use zinc, copper, cadmium and their alloys for parts in contact with the fuel.
NOTES
REMARKS
9755-DAT-ME-017
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 1 OF 3
Revision A B
Issue IDC Implementation Issue
Date 3/10/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client
LIQUID Jet A1
VISCOSITY cSt @ 5oC 2.2 S G @ 5oC 0.8 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA
9755-DAT-ME-016
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 2 OF 3
Supplier'S STANDARD ü
NOTE 3 BEARING HOUSING STA
MATERIALS
TYPE NOTE 4
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 4 PHASE HERTZ ENCLOSURE NOTE 4
kW RATING NOTE 1 STA VERTICAL HORIZONTAL
DRIVER
REMARKS
SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS
WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT
9755-DAT-ME-016
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 3 OF 3
QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA
SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE
HYDROTEST ü
PERFORMANCE ü
NPSH ü
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST
TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER
Note 1 The pump shown on this Data Sheet will be used to transfer recovered JetA1 fuel from a horizontal separator tank to the the main
depot storage tanks. Add 1.7 bar to the discharge pressure (to allow for the internal relief valve) when sizing the motor.
Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 Do not use zinc, copper, cadmium and their alloys for parts in contact with the fuel.
NOTES
REMARKS
9755-DAT-ME-016
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 1 OF 3
Revision A B
Issue IDC Implementation Issue
Date 3/10/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client
LIQUID Jet A1
VISCOSITY cSt @ 5oC 2.2 S G @ 5oC 0.8 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA
CAPACITY (NOTE 1) m3/hr 250 NPSH REQUIRED - RATED CAP m H20 STA
SUCTION PRESSURE BARG + 0.02 SUCTION SPECIFIC SPEED STA
DISCHARGE PRESS. BARG + 2.37 MAX SOUND PRESS. LEVEL dBA 85
DIFFERENTIAL PRESS BAR 2.35 DIFFERENTIAL HEAD m 30
DESIGN
9755-DAT-ME-015
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 2 OF 3
Supplier'S STANDARD ü
NOTE 3 BEARING HOUSING STA
MATERIALS
TYPE NOTE 4
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 4 PHASE HERTZ ENCLOSURE NOTE 4
kW RATING NOTE 1 STA VERTICAL HORIZONTAL
DRIVER
REMARKS
SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS
WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT
9755-DAT-ME-015
Equipment Data Sheet
ROTARY POSITIVE DISPLACEMENT PUMPS 3 OF 3
QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA
SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE
HYDROTEST ü
PERFORMANCE ü
NPSH ü
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST
TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER
Note 1 The pump shown on this Data Sheet will be used to transfer JetA1 fuel from tank to tank. Add 1.7 bar to the discharge pressure (to
allow for the internal relief valve) when sizing the motor.
Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 Do not use zinc, copper, cadmium and their alloys for parts in contact with the fuel.
NOTES
REMARKS
9755-DAT-ME-015
Equipment Data Sheet
CENTRIFUGAL PUMPS 1 OF 3
Revision A B
Issue IDC Implementation Issue
Date 3/13/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client
9755-DAT-ME-014
Equipment Data Sheet
CENTRIFUGAL PUMPS 2 OF 3
TYPE NOTE 3
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 3 PHASE HERTZ ENCLOSURE NOTE 3
kW RATING STA VERTICAL HORIZONTAL
DRIVER
SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS
WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT
9755-DAT-ME-014
Equipment Data Sheet
CENTRIFUGAL PUMPS 3 OF 3
QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA
SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE
HYDROTEST ü
PERFORMANCE ü
NPSH
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST
TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER
Note 1 The pump shown on this Data Sheet will be used to transfer water from a slab drain sump to an open drain.
There could be Jet fuel in the sump occasionally.
Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 See Data Sheet 9755-DAT-EL-003
NOTES
Note 4 Pumpsets to be prepared and painted in accordance with project specification 9755-SPC-CP-007.
Note 5 Mounting plate to be suitable for galvanised open mesh flooring of drain sump. Sump depth = 0.5m.
Note 6 Tests on one pump of each type to be witnessed by the Purchaser.
Note 7 STA = Supplier to add details.
REMARKS
9755-DAT-ME-014
Equipment Data Sheet
CENTRIFUGAL PUMPS 1 OF 3
Revision A B
Issue IDC Implementation Issue
Date 3/13/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client
LIQUID Water
VISCOSITY cSt @ 5oC 1 S G @ 5oC 1 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA
9755-DAT-ME-013
Equipment Data Sheet
CENTRIFUGAL PUMPS 2 OF 3
TYPE NOTE 3
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 3 PHASE HERTZ ENCLOSURE NOTE 3
kW RATING STA VERTICAL HORIZONTAL
DRIVER
SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS
WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT
9755-DAT-ME-013
Equipment Data Sheet
CENTRIFUGAL PUMPS 3 OF 3
QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA
SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE
HYDROTEST ü
PERFORMANCE ü
NPSH
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST
TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER
Note 1 The pump shown on this Data Sheet will be used to transfer water from a separator water sump to an open drain sump.
Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 See Data Sheet 9755-DAT-EL-003
Note 4 Pumpsets to be prepared and painted in accordance with project specification 9755-SPC-CP-007.
NOTES
Note 5 See drawing 9755/CI/2/4534. Mounting plate to be suitable for galvanised open mesh flooring of intercepter.
Note 6 Tests on one pump of each type to be witnessed by the Purchaser.
Note 7 STA = Supplier to add details.
REMARKS
9755-DAT-ME-013
Equipment Data Sheet
CENTRIFUGAL PUMPS 1 OF 3
Revision A B
Issue IDC Implementation Issue
Date 3/13/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client
9755-DAT-ME-012
Equipment Data Sheet
CENTRIFUGAL PUMPS 2 OF 3
TYPE NOTE 3
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 3 PHASE HERTZ ENCLOSURE NOTE 3
kW RATING STA VERTICAL HORIZONTAL
DRIVER
SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS
WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT
9755-DAT-ME-012
Equipment Data Sheet
CENTRIFUGAL PUMPS 3 OF 3
QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA
SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE
HYDROTEST ü
PERFORMANCE ü
NPSH
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST
TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER
Note 1 The pump shown on this Data Sheet will be used to transfer fuel from an oil separator oil sump to a hose line.
Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 See Data Sheet 9755-DAT-EL-003
Note 4 Pumpsets to be prepared and painted in accordance with project specification 9755-SPC-CP-007.
NOTES
Note 5 See drawing 9755/CI/2/4534. Mounting plate to be suitable for galvanised open mesh flooring of intercepter.
Note 6 Tests on one pump of each type to be witnessed by the Purchaser.
Note 7 STA = Supplier to add details.
REMARKS
9755-DAT-ME-012
Equipment Data Sheet
CENTRIFUGAL PUMPS 1 OF 3
Revision A B
Issue IDC Implementation Issue
Date 3/13/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client
9755-DAT-ME-011
Equipment Data Sheet
CENTRIFUGAL PUMPS 2 OF 3
TYPE NOTE 3
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 3 PHASE HERTZ ENCLOSURE NOTE 3
kW RATING STA VERTICAL HORIZONTAL
DRIVER
VERTICAL PUMPS UP DOWN SEPARATE MOUNTING PLATE 24" Diameter, ANSI 150
PUMP THRUST N DRIVER ALIGNMENT SCREWS Required
AT MIN FLOW N PIT OR SUMP DEPTH m NOTE 5
AT DESIGN FLOW N PUMP LENGTH m NOTE 5
VERTICAL PUMPS
SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS
WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT
9755-DAT-ME-011
Equipment Data Sheet
CENTRIFUGAL PUMPS 3 OF 3
QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA
SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE
HYDROTEST ü
PERFORMANCE ü
NPSH
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST
TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER
Note 1 The pump shown on this Data Sheet will be used to transfer fuel and water slops from a buried tank to a separator tank.
Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 See Data Sheet 9755-DAT-EL-004
Note 4 Pumpsets to be prepared and painted in accordance with project specification 9755-SPC-CP-007.
NOTES
REMARKS
9755-DAT-ME-011
Equipment Data Sheet
CENTRIFUGAL PUMPS 1 OF 3
Revision A B
Issue IDC Implementation Issue
Date 3/13/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client
LIQUID Water
VISCOSITY cSt @ 5oC 1 S G @ 5oC 1 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA
9755-DAT-ME-010
Equipment Data Sheet
CENTRIFUGAL PUMPS 2 OF 3
TYPE NOTE 3
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 3 PHASE HERTZ ENCLOSURE NOTE 3
kW RATING STA VERTICAL HORIZONTAL
DRIVER
SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS
WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT
9755-DAT-ME-010
Equipment Data Sheet
CENTRIFUGAL PUMPS 3 OF 3
QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA
SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE
HYDROTEST ü
PERFORMANCE ü
NPSH
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST
TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER
Note 1 The pump shown on this Data Sheet will be used to transfer water from a pipe trench drain sump to an oily water drainage system.
Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 See Data Sheet 9755-DAT-EL-003
Note 4 Pumpsets to be prepared and painted in accordance with project specification 9755-SPC-CP-007.
NOTES
Note 5 Mounting plate to be suitable for galvanised open mesh platform affixed level with top of wall at +1.3m AOD.
Sump depth = - 1.7m AOD.
Note 6 Tests on one pump of each type to be witnessed by the Purchaser.
Note 7 STA = Supplier to add details.
REMARKS
9755-DAT-ME-010
Equipment Data Sheet
CENTRIFUGAL PUMPS 1 OF 3
Revision A B
Issue IDC Implementation Issue
Date 3/13/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client
9755-DAT-ME-009
Equipment Data Sheet
CENTRIFUGAL PUMPS 2 OF 3
TYPE NOTE 3
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 3 PHASE HERTZ ENCLOSURE NOTE 3
kW RATING STA VERTICAL HORIZONTAL
DRIVER
SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS
WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT
9755-DAT-ME-009
Equipment Data Sheet
CENTRIFUGAL PUMPS 3 OF 3
QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA
SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE
HYDROTEST ü
PERFORMANCE ü
NPSH
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST
TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER
Note 1 The pump shown on this Data Sheet will be used to transfer water from a slab drain sump to an oily water system.
There could be Jet fuel in the sump occasionally.
Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 See Data Sheet 9755-DAT-EL-003
NOTES
Note 4 Pumpsets to be prepared and painted in accordance with project specification 9755-SPC-CP-007.
Note 5 Mounting plate to be suitable for galvanised open mesh flooring of drain sump. Sump depth = 0.5m.
Note 6 Tests on one pump of each type to be witnessed by the Purchaser.
Note 7 STA = Supplier to add details.
REMARKS
9755-DAT-ME-009
Equipment Data Sheet
CENTRIFUGAL PUMPS 1 OF 3
Revision A B
Issue IDC Implementation Issue
Date 3/13/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client
LIQUID Water
VISCOSITY cSt @ 5oC 1 S G @ 5oC 1 SP. HEAT (kJ/kg deg C) N/A
PROCESS
DATA
9755-DAT-ME-008
Equipment Data Sheet
CENTRIFUGAL PUMPS 2 OF 3
TYPE NOTE 3
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 3 PHASE HERTZ ENCLOSURE NOTE 3
kW RATING STA VERTICAL HORIZONTAL
DRIVER
SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS
WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT
9755-DAT-ME-008
Equipment Data Sheet
CENTRIFUGAL PUMPS 3 OF 3
QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA
SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE
HYDROTEST ü
PERFORMANCE ü
NPSH
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST
TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER
Note 1 The pump shown on this Data Sheet will be used to transfer water from a separator water sump to an open drain sump.
Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 See Data Sheet 9755-DAT-EL-003
Note 4 Pumpsets to be prepared and painted in accordance with project specification 9755-SPC-CP-007.
NOTES
Note 5 See drawing 9755/CI/2/4530. Mounting plate to be suitable for galvanised open mesh flooring of intercepter.
Note 6 Tests on one pump of each type to be witnessed by the Purchaser.
Note 7 STA = Supplier to add details.
REMARKS
9755-DAT-ME-008
Equipment Data Sheet
CENTRIFUGAL PUMPS 1 OF 3
Revision A B
Issue IDC Implementation Issue
Date 3/13/2003 3/21/2003
By PEIT
Checked AB (18/03/03)
Approved
Client
9755-DAT-ME-007
Equipment Data Sheet
CENTRIFUGAL PUMPS 2 OF 3
TYPE NOTE 3
Supplier STA TYPE STA FRAME STA
VOLTS NOTE 3 PHASE HERTZ ENCLOSURE NOTE 3
kW RATING STA VERTICAL HORIZONTAL
DRIVER
SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS
WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT
9755-DAT-ME-007
Equipment Data Sheet
CENTRIFUGAL PUMPS 3 OF 3
QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA
SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 6 OBSERVE
HYDROTEST ü
PERFORMANCE ü
NPSH
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST
DISMANTLE & INSPECT AFTER
TEST
TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER
Note 1 The pump shown on this Data Sheet will be used to transfer fuel from a separator oil sump to a hose line.
Note 2 See project design base memorandum and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 3 See Data Sheet 9755-DAT-EL-003
Note 4 Pumpsets to be prepared and painted in accordance with project specification 9755-SPC-CP-007.
NOTES
Note 5 See drawing 9755/CI/2/4530. Mounting plate to be suitable for galvanised open mesh flooring of intercepter.
Note 6 Tests on one pump of each type to be witnessed by the Purchaser.
Note 7 STA = Supplier to add details.
REMARKS
9755-DAT-ME-007
Equipment Data Sheet
CENTRIFUGAL PUMPS
Revision A 0
Issue Preliminary Issue Approved for Design
Date 2/22/2006 2/24/2006
By NMC NMC
Checked DWA DWA
Approved AJG AJG
Client
LIQUID Diesel
VISCOSITY cSt @ 59oF 2.1 S G @ 59oF 0.84 SP. HEAT (kJ/kg deg C) 1.8
PROCESS
DATA
680212557.xls
Equipment Data Sheet
CENTRIFUGAL PUMPS
TYPE NOTE 3
SUPPLIER STA TYPE STA FRAME STA
VOLTS NOTE 4 PHASE HERTZ ENCLOSURE NOTE 3
kW RATING STA VERTICAL HORIZONTAL
SPEED rev / min STA EFFICIENCY %
MINIMUM STARTING VOLTAGE INSULATION NOTE 4
DRIVER
REMARKS
SURFACE PREPARATION
PRIMER COATS
FINISH COATS
REMARKS
WEIGHTS
TOTAL WEIGHT kg STA WEIGHT OF PUMP kg STA
WEIGHT
680212557.xls
Equipment Data Sheet
CENTRIFUGAL PUMPS
QA & TEST
REVIEW VENDOR QA PROGRM. DATE COMMENTS
QA
SHOP INSPECTION
TEST NON WITNESS WITNESS NOTE 7/9 OBSERVE
HYDROTEST ü
PERFORMANCE ü
NPSH ü
STRING TEST (CONTRACT MTR) ü
SOUND LEVEL TEST ü
DISMANTLE & INSPECT AFTER ü
TEST
TEST
CLEANLINESS PRIOR TO FINAL ü
TEST
PIPELOAD TEST
OTHER
Note 1 The pump shown on this Data Sheet will be used to transfer fuel from Tank 22-T-2220.
Note 2 Pumps are to be equipped with hydraulically balanced mechanical seals with dry running standby seals for enhanced safety.
Note 3 See project specification 22-SP-R-003 and P&ID drawings for full details of pump monitoring and control instrumentation.
Note 4 Pumpsets to be in accordance with Project Specification 22-SP-R-003
NOTES
Note 5 Pumpsets to be prepared and painted in accordance with Project Specification 22-SP-C-001
Note 6 Manufacturer's standard material quality control procedures to apply
Note 7 Tests on all pumps to be witnessed by the Owner at Supplier's works.
Note 8 STA = Supplier to Advise.
Note 9 Supplier to undertake 4 hour test with contract motor for vibration and bearing temperature measurement. Owner to witness
Note 10 Data Sheet to be completed in API format by Supplier/Manufacturer/Contractor as appropriate.
REMARKS
680212557.xls