Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

A2-10 Metal Roofs

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 23

NPQS

A2-10 Metal Roofs

National Productivity and Quality Specifications (NPQS)

A2-10 Metal Roofs

1
Version 1.0
NPQS
A2-10 Metal Roofs

CONTENTS
Page

1. GENERAL 3
1.1 Scope 3
1.2 Related Sections 3
1.3 Standards 3
1.4 Trade Preambles 4
1.5 Abbreviations / Definitions 5

2. PERFORMANCE REQUIREMENTS 7
2.1 Contractor’s Brief 7

3. MATERIALS AND COMPONENTS 9


3.1 Metal Roof System 9
3.2 General Material Requirements 10
3.3 Metal Sheeting 10
3.4 Roof Deck (Liner) 11
3.5 Skylights 11
3.6 Accessories 11
3.7 Purlins 12
3.8 Underlayment and Insulation System 12
3.9 Rainwater Goods 13
3.10 Safety and Maintenance 14

4. WORKMANSHIP 15
4.1 General Workmanship Requirements 15
4.2 Supporting Members 15
4.3 Underlayment and Insulation System 16
4.4 Installation of Metal Roof Sheeting 16
4.5 Skylights 18
4.6 Installation of Rainwater Goods 18
4.7 Protection 18

5. VERIFICATION AND SUBMISSION 19


5.1 Submissions 19
5.2 Samples and Mock-ups 20
5.3 Inspection and Tests 21

2
Version 1.0
NPQS
A2-10 Metal Roofs

1. GENERAL
Read with the General Requirements section, and all other contract documents.
This Document is supplementary to Section A2-10 Metal Roofs of the NPQS, which
sets out Project Specific Data (PSD), in the same clause headings as in the NPQS.
All modifications and additions noted in this document take precedence over clauses
noted in the NPQS.

1.1 Scope
This section covers the requirements for the construction of common metal roofing
systems including metal sheets, finishes and insulation. The following types of metal
sheets are covered:
a. Profiled Metal Sheets
b. Standing Seams
c. Composite Panels

1.2 Related Sections


Read this work section in conjunction with the relevant requirements of the other work
sections including the following:
a. A2-40 Skylights

1.3 Standards
Unless otherwise agreed by the SO, ensure all of the Works comply with the relevant
requirements of the Standards and Codes listed below or referenced in the body of
the Specification. Alternative Standards and Codes may be submitted to the SO,
provided it can be demonstrated that the alternative Standards and Codes comply
with the requirements of the standards specified. All Standards and Codes quoted
are the current version, unless specific year references are noted.
Singapore Standards
SS CP 1 Use of Timber in Buildings
SS CP 7 Structural Use of Timber
SS CP 26 Drainage of Roofs
SS CP 33 Lightning Protection
SS CP 89 The Design and Installation of Metal Roofing
SS 72 Treatment of Timber and Plywood with Copper/Chrome/Arsenic
Wood Preservatives
SS 141 Unplasticized PVC pipe for cold water services and industrial uses
SS 370 Specification for Metal Roofing
Other Standards

3
Version 1.0
NPQS
A2-10 Metal Roofs

BS EN 363 Personal protective equipment against falls from a height – Fall


Arrest Systems.
BS EN 1316 Thermal Insulation Products for Buildings – Factory Made Mineral
Wool (MW) Products - Specifications
BS EN 10088 Stainless Steels
BS CP 3 Code of basic data for the design of buildings: Chapter V Loading
BS 460 Cast iron for rainwater goods

1.4 Trade Preambles

1.4.1 Contractor’s Submissions


The intended design of the metal roofing system(s) for the project is indicated in the
drawings and this specification. Base on the information available, engage qualified
personnel to carry out and submit the following items to the SO:

1.4.1.1 Design development


Develop all necessary details including connections and interfaces etc. for the
construction of the metal roofing system(s).

1.4.1.2 Construction Methods


Submit suitable methods to carry out the works including fabrication, setting out,
installation, fixing and waterproofing etc. Take into account of the performance
requirements as set out in clause 2.1 and submit to the SO.

1.4.1.3 Temporary Supports


Plan, design and supervise any temporary supports (including support of personnel
working on the roof and roof loading resulting from the installation process), to ensure
the roof installation is stable throughout the construction. Submit all calculations with
PE endorsement to the SO.

1.4.1.4 Manufacturer and products


Submit manufacturer and products to the SO, to meet with specified requirements
when called for.

1.4.2 Shop Drawings


Prepare coordinated shop drawings incorporating all developed details.

1.4.3 Co-ordination with other Works


Co-ordinate the roofing works particularly the interfacing with the following trades:
a. Main Structural Roofing Works
b. External Masonry and Cladding
c. Lightning Protection
d. Plumbing Works

4
Version 1.0
NPQS
A2-10 Metal Roofs

e. Mechanical Services
f. Electrical Services
g. Internal Masonry and Partitions
h. Ceilings
i. External Painting and Coating

1.4.4 Provide Spare Materials


Deliver to site in strong protective packages marked for identification, and store
where directed, components and materials for future replacement and repair. Refer
to PSD for list.
Provide spare materials as listed below:
Spare Material Description (Size, Quantity Due Date
Type, etc)

a. All spare materials shall be delivered and stored in an area agreed by the SO.
b. The Dates listed are provisional, subject to final agreement with the SO.

1.4.5 Warranty
Refer to the PSD for warranty requirements.
The period of warranty required for the roof shall be [      years]

1.4.6 Maintenance Manual


Prepare and submit a maintenance / replacement manual covering all components
and accessories. Refer to the General Requirements section, clause 1.4.8 for details.

1.4.7 Quality Control Plan


Prepare and submit a quality control plan to the SO.

1.5 Abbreviations / Definitions


a. BMT Base Metal Thickness
b. OTTV Overall Thermal Transfer Value
c. PVF2 Polyvinylidene Fluoride, also known as XPD
d. RWDP Rainwater Down Pipe
e. U-value Thermal Transmittance
f. XRW Polyester Paint

5
Version 1.0
NPQS
A2-10 Metal Roofs

6
Version 1.0
NPQS
A2-10 Metal Roofs

2. PERFORMANCE REQUIREMENTS

2.1 Contractor’s Brief


When carrying out the proposals as set out in clause 1.4.1, take account of the
following requirements:

2.1.1 Structural

2.1.1.1 Dead Loads


The self weight and other associated dead loads of the complete metal roofing
system shall not exceed the assumed design value as indicated in the PSD.
The self weight and other associated dead loads of the complete roof system shall
not exceed [     KN/m2]

The loads shall be supported and transferred to the main building structure at the
appropriate locations as indicated in the drawings.

2.1.1.2 Live Loads


Unless otherwise specified, account for the Live Loads as stipulated in the Building
Control Regulations, and additional requirements of other statutory authorities having
jurisdiction over the works if any.

2.1.1.3 Wind Loads


Account for wind loads computed based on BS CP 3 with a basic wind speed of 35
m/s, and the design recommendations of SS CP 89.

2.1.1.4 Thermal Stress and Structural Movement


Account for all thermal stress and other structural movement.

2.1.1.5 Structural Fixing


Structural fixings to be able to resist the worst combination of the applied loads, as
well as foreseeable vibration transmitted to the roofing system.

2.1.1.6 Maintenance Loads


For accessible areas allow for maintenance loadings, including loadings from
personnel, plant and equipment. Include the dynamic effects of such plants and
equipments. Account for maintenance loading requirements as indicated in the PSD.
Account for maintenance loading requirements of      KN/m2

2.1.1.7 Secondary Building Movements


Take into account, movements from secondary support structures, including vibration
and thermal movement from M&E equipment and related works.

7
Version 1.0
NPQS
A2-10 Metal Roofs

2.1.2 Fire Resistance


Comply with the requirements of the FSSD and additional requirements of other
statutory authorities having jurisdiction over the works if any.

2.1.3 Functional

2.1.3.1 Air Infiltration


The metal roofing system shall be sufficiently air tight such as to prevent undesirable
noise resulting from wind movements.

2.1.3.2 Invasion of Pests


Gaps and openings shall be sealed off for bird-proofing and disallow the invasion of
undesirable pests.

2.1.4 Environmental

2.1.4.1 Thermal Performance


Comply with the applicable OTTV or U-value referred to in the PSD.
The OTTV of the roof shall be [     W/m2]
The U-value of the roof shall be [     W/m2°K]

2.1.4.2 Rainwater Drainage


Take into account, compliance with the requirements of SS CP 26 for roof drainage,
and that of other statutory authorities having jurisdiction over the works if any.

2.1.4.3 Watertightness
The completed roof shall be in-penetrable to water and not give rise to any
observable dampness on visible surfaces under the normal environmental conditions
expected.

2.1.5 Maintenance

2.1.5.1 The roof system shall be maintainable and replaceable in parts or whole from
the outside.

2.1.5.2 Allow routine cleaning to be conducted with minimal disruption to the building
occupants.

8
Version 1.0
NPQS
A2-10 Metal Roofs

3. MATERIALS AND COMPONENTS

3.1 Metal Roof System


The metal roofing system(s) for the project may consist of varying combination of
different components as set out below. Refer to the PSD for the requirements of
different types of system(s).
Select suitable manufacturer and product to comply with the following requirements:
Metal Roof System Type: MR
Items Requirements Clause ref.
Purlins: 3.7
Type of Section
Material / protection
Size and spacing Contractor to propose
Roof Pitch: 3.3.5
Metal Sheeting:
Form of Sheeting 3.3.1
Metallic Coating 3.3.2
Base Metal Thickness 3.3.3
Min End Lap width
Paint Coating 3.3.4
Exposed side 3.3.4.1 &
3.3.4.2
Exposed side colour 3.3.4.3
Reversed side 3.3.4.1 &
3.3.4.2
Reversed side colour 3.3.4.3
Roof Deck (Liner) 3.4
Fixings and Fasteners Contractor to propose 3.6.1
Profile fillers/ Rib End Stops Contractor to propose 3.6.2
Sealants Contractor to propose 3.6.3
Acoustic Treatment: 3.6.4
Underlayment and Insulation 3.8
System:
Waterproof Underlayment 3.8.1
Vapour Barrier 3.8.2
Thermal Insulation 3.8.3
Wire Mesh Support Contractor to propose 3.8.4
Rainwater Goods: 3.10
Gutter Material and Profile 3.10.2
Gutter Support Material 3.10.2
Gutter Covering Material 3.10.3
RWD Material & Profile 3.10.4
Holder Bat Material 3.10.5
Miscellaneous Components:
Component(s) 3.2.1

9
Version 1.0
NPQS
A2-10 Metal Roofs

The roofing system may be assembled on site with the individual components, or
supplied and installed as a composite system incorporating one or more components.

3.2 General Material Requirements

3.2.1 Ancillary Products and Accessories


Where ancillary products and accessories and miscellaneous components are not
specified, they are to be types recommended for the intended purpose, by the metal
sheeting manufacturer.

3.2.2 Length of Components


Components, particularly metal sheeting, gutters, down pipes, capping, and flashing
shall be in the longest lengths as practical to minimise lapping, joints and wastage.

3.2.3 Compatibility of Materials and Separation


Take into account, the following requirements for different materials used in the
system:
a. Compatibility of materials used for the roofing system.
b. Prevent contact between incompatible materials / components, particularly
contact between incompatible metals, and metals with alloys.
c. Materials use for separation of dissimilar materials / components, shall comply
with the have the following quality.

I. Non-conducting, non-compressible and non-water absorbing.


II. Compatible with elements, with which it comes into contact.

3.3 Metal Sheeting

3.3.1 Form of Sheeting


Acceptable forms are:
a. Corrugated sheet in Sinusoidal or Trapezoidal profiles
b. Standing Seams

3.3.2 Materials of Sheeting and Metallic Coating


Mild steel sheet complying with SS 370 and SS CP 89, supplied with one of the
following metallic coating:
a. Zinc aluminium alloy
b. Aluminium
c. Zinc (Galvanised)

10
Version 1.0
NPQS
A2-10 Metal Roofs

3.3.3 Base Metal Thickness


Comply with SS 370 and SS CP 89.

3.3.4 Paint Coating


Unless otherwise specified, use the following paint coatings and comply with SS 370
and SS CP 89.

3.3.4.1 PVF2
a. XPD
b. XPD Pearlescent Steel

3.3.4.2 Polyester
a. XRW
b. XRW Ultra

3.3.4.3 Colour of Metal Sheeting


Refer to clause 3.1 for selected colour of metal sheeting.

3.3.5 Pitch Capacity


The pitching capacity of metal roof sheets shall comply with the minimum roof pitch
recommendations of SS CP 89 for different profiles.

3.4 Roof Deck (Liner)


Use proprietary metal sheeting recommended by the roofing manufacturer. Submit
suitable product and manufacturer for to the SO.

3.5 Skylights
Refer to section A2-40 for general requirement of materials for skylights.

3.6 Accessories

3.6.1 Fixings, Brackets, Screws and Washers


To roof sheeting manufacturer’s recommendations and shall comply with SS CP 89.

3.6.2 Profile Fillers and Rib End Stops


To manufacturer’s recommendations and shall match the profile of metal sheeting
selected.

3.6.3 Weather Seals and Air Seals


Sealants shall be to manufacturer’s recommendation and shall be non-staining and
compatible with the other components.

11
Version 1.0
NPQS
A2-10 Metal Roofs

Sealant geometry (and cross sections) shall be designed to accommodate the


anticipated substrate movements.
Unless otherwise agreed non-structural sealants shall be either:
a. low modulus silicone (exposed or concealed); or
b. polyurethane (concealed).
Do not use acrylic sealants for frame seals or smoke flashings.
Do not use Acid curing sealants.
Backing rods shall not adhere to the sealant and shall be compatible with the
substrate.
The colour of all visible sealants shall be approved by the S.O.

3.6.4 Acoustic Treatment


Refer to clause 3.1 for acoustic treatment material, if any.

3.7 Purlins
Use the following materials:
a. Galvanised steel sections in accordance with structural specifications.
b. Structural timber in accordance with SS CP 1, SS CP 7 and SS 72.

3.8 Underlayment and Insulation System

3.8.1 Waterproof Underlayment


Waterproof underlayment may be one of the following materials or similar impervious
sheet materials of adequate puncture resistance. Submit suitable product and
manufacturer to the SO.
a. Double-sided Reflective Foil Laminates
b. Waterproofing Felts

3.8.2 Vapour Barrier


Vapour barrier may be one of the following materials or similar impervious sheet
materials of adequate puncture resistance. Submit suitable product and
manufacturer to the SO.
a. Double-sided Reflective Foil Laminates
b. Waterproofing Felts

12
Version 1.0
NPQS
A2-10 Metal Roofs

3.8.3 Thermal Insulation

3.8.3.1 Double-sided Reflective Foil Laminates


Submit suitable product and manufacturer to the SO.
Where double-sided reflective foil laminate is expected to perform as a waterproof
underlayment (or vapour barrier) as well, it shall also be subjected to the requirement
of these items.

3.8.3.2 Mineral Wool


Comply with BS EN 13162.

3.8.3.3 Other Types of Insulations


Other types of insulations shall comply with the following requirements:
a. Shall not contain organic components which may be subject to volatilisation and
condensation
b. Non-combustible
c. Rot and vermin resistant
d. Does not degrade in moisture
Submit suitable product and manufacturer to the SO.

3.8.4 Wire Mesh Support


Where required, wire mesh support shall be expanded metal wire mesh, complying to
the following requirements.
a. Galvanised
b. Does not sag when stretched between supports
c. Rigidly connected at junction without weld joints
d. Does not unravel or fray
Submit suitable product and manufacturer to the SO.

3.9 Rainwater Goods


Rainwater goods shall comply with SS CP 26, SS CP 89 and in accordance with
manufacturer’s recommendations.

3.9.1 Flashing
All flashings and capping shall have a minimum BMT of 0.55 mm, with the same
coating system and profile as the selected metal sheeting, and comply with SS CP
89.

3.9.2 Gutters and Gutter Support


Use:
a. Stainless steel grade 1.4401 (formerly 316), comply with BS EN 10088

13
Version 1.0
NPQS
A2-10 Metal Roofs

b. Galvanised mild steel in accordance with structural specifications.

3.9.3 Wire Mesh Gutter Covering


Comply with the requirements of ENV. Use:
a. Stainless steel grade 1.4401 (formerly 316), comply with BS EN 10088
b. Galvanised mild steel in accordance with structural specifications.

3.9.4 Rainwater Down Pipes


Ductile Iron Pipes and fittings to BS 460.
uPVC pipes and fittings to SS 141.

3.9.5 Holder Bats


Use:
a. Stainless steel grade 1.4401 (formerly 316), comply with BS EN 10088
b. Galvanised mild steel in accordance with structural specifications.

3.10 Safety and Maintenance

3.10.1 Maintenance Walkways


Provide maintenance walkway where shown on drawings. Submit materials to
comply with performance requirements of maintenance loads, to the SO.

3.10.2 Fall Arrest System


Where shown in drawings, provide a support system for the purpose of carrying out
periodical maintenance and cleaning, capable of taking the load of two number
operatives and comply with the requirements of BS EN 363.

14
Version 1.0
NPQS
A2-10 Metal Roofs

4. WORKMANSHIP

4.1 General Workmanship Requirements

4.1.1 Method of Works


Carry out the works in accordance with the method of works, as submitted to the SO.
Ensure construction will achieve the design as set out in the approved shop
drawings.

4.1.2 Co-ordination and Setting Out


Co-ordinate the roofing works with all interfacing works packages and trades to
ensure correct setting out and positioning of all penetrations, attachments, and other
constituent materials and elements.

4.1.3 Handling and Hoisting


Handle and hoist assemblies carefully, at all stages to ensure that sections and
finishes are not damaged, and in accordance with manufacturer’s recommendations.

4.1.4 Finished Tolerances of Systems

4.1.4.1 Fabrication
Linear dimensions ±2mm
Squareness (diagonal) ±3mm
Flatness ±0.5mm in 300mm
Joint widths shall not vary by more than 2mm or 10%. Adjacent “flush” surfaces
separated by “hair line” joints shall not step by more than 0.5mm.

4.1.4.2 Installation
Linear dimensions ±2mm
Level ±2mm
Position at floor or ceiling ±2mm from grid
Verticality ±H/500 or < 5mm between floors and ceiling
Steps in plane ±2mm
Steps out of plane ±1mm

4.2 Supporting Members


Install supporting members in accordance with structural specifications, comply with
SS CP 89, and take into account, the following:
a. The spacing of supporting members is within tolerances recommended by the
sheeting manufacturer.
b. Any vertical or horizontal misalignment at the abutting ends does not exceed
2mm.

15
Version 1.0
NPQS
A2-10 Metal Roofs

c. The top of the supporting members is substantially in a plane parallel to the


specified roof pitch.

4.3 Underlayment and Insulation System

4.3.1 Waterproof Underlayment


Locate and lay waterproof underlayment to comply with SS CP 89, in accordance
with manufacturer’s recommendations, and take into account, any water built-up is
shed and drain to gutter area, without penetrating into the roofing space.

4.3.2 Vapour Barrier


Locate and lay vapour barrier to comply with SS CP 89, in accordance with
manufacturer’s recommendations, and prevent interstitial condensation on visible
surfaces. Where condensation is expected, ensure adequate drainage provision is
made.

4.3.3 Thermal Insulation and Wire Mesh Support


Locate and lay thermal insulation and wire mesh support to comply with SS CP 89
and in accordance with manufacturer’s recommendations.

4.4 Installation of Metal Roof Sheeting


Carry out the installation of metal roof sheeting, including any roof deck (liner)
materials, to comply with SS CP 89, in accordance manufacturer’s recommendations,
and the following requirements.

4.4.1 Laying the Sheeting


Support sheets as near to their ends as practicable, notwithstanding that the sheet
end shall always positively overhang the full width of the supporting surface to
prevent water intrusion by capillary action. Ensure compliance with manufacturer’s
recommended maximum and minimum unsupported end overhang for the sheet.

4.4.2 Fixing of Metal Roof Sheeting


Fix sheeting to manufacturer’s recommendation.
Unless otherwise agreed, install fasteners normal to the plane of the roof and
adequately seal all fasteners which pierce the cladding to prevent leakage.
Pay particular attention to combinations of internal and external wind pressures and
frictional drag.
Where non-returnable movement is allowed to take place during fixing, make
provision for anchoring of the sheets.
Give consideration to the anchoring of roofing against movement down the slope due
to vibration and thermal movements.

16
Version 1.0
NPQS
A2-10 Metal Roofs

4.4.3 Projections
Provide adequate flashings to accepted detail for any projections through roofs such
as pipes, ducts and conduits.

4.4.4 Vibration Proofing of Fixings


Vibration proof all fixings subject to vibrating loads by the use of locking nuts, locking
washers or other accepted methods.

4.4.5 Prevention of Bi-Metallic Corrosion


Prevent corrosion of dissimilar metal in contact from galvanic action by:
a. separating or isolating the dissimilar metals with separator and
b. Appropriate detailing of the overlapping of metal sheets to avoid crevice
corrosion.

4.4.6 Drilling, Piercing and Cutting


Remove swarf, nails, screws, other metallic particles, etc, immediately after drilling,
piercing and cutting of metal roof sheeting.
Do not punch holes, unless it can be done without causing local distortions to the
metal roof sheeting.

4.4.7 End and Side Laps

4.4.7.1 Planning
Plan and lay metal roof sheeting to minimise end and side laps. Avoid formation of
laps at roof protrusions and attachments.

4.4.7.2 End Laps


Provide two strips of manufacturer’s recommended profile fillers and sealant, one at
the low end of the lap to prevent capillary and the other at the high end to prevent
condensation from entering the lap. Mechanically fasten when recommended by the
manufacturer.

4.4.7.3 Side Laps


For pierced fastened roof sheeting form side laps with the lap cavity on top of the
sheet with profile filler or sealant such that any moisture build up in this cavity can be
drained down the roof slope unobstructed by the filler or sealant.

4.4.8 Sealant Jointing


Apply sealant and jointing in accordance with manufacturer’s recommendations.
Pay particular attention to:
a. Clean and prepare joint surfaces before application and ensure that joints are free
from dust, grease and other contaminants.
b. Apply jointing material so that joints subject to ingress of water are made
watertight and are in accordance with details on the approved shop drawings.
Ensure backing rods when needed are installed at the correct depths.

17
Version 1.0
NPQS
A2-10 Metal Roofs

4.5 Skylights
Install skylight(s) in accordance with section A2-40, clause 4.0 and comply with SS
CP 89.

4.6 Installation of Rainwater Goods


Provide and install rainwater goods to comply with SS CP 26, SS CP 89, in
accordance with manufacturer’s recommendations, the requirements of ENV and any
other statutory authorities having jurisdiction over the works.

4.6.1 Flashing
Flash and cap all parts of the roof to prevent water penetration and dampness into
the inner parts of the building, including areas around vent pipes, skylights, ducts,
and other penetrations, ridges, verges, and along roof slopes that abuts walls.

4.6.2 Gutters
a. Install to required fall, space gutter support at 600 mm centres
b. Box gutters to be continuously supported
c. Fix stop ends to match gutters profile and colour
d. Lap all gutters in the direction of flow and seal all joints

4.6.3 Down Pipes


Space all down pipes at required centres, fit to gutters and fix securely to walls or
columns with holder bats spaced at 1200 mm centres. Seal all joints.

4.7 Protection
Ensure that from completion of the roof until Practical Completion:
a. The roof is not used as a working platform unless fully protected to the
satisfaction of the SO.
b. Do not allow solvents or other harmful chemical to come into contact with the roof
surface.
c. Protect the finished roof areas from damage by subsequent building operations.

4.7.1 Wet Weather


Provide temporary covers and drainage as required to keep unfinished areas of the
roof dry.
Suspend work in severe or continuously wet weather unless an effective temporary
roof is provided over the working area.
If unavoidable wetting of the construction does occur, take prompt action to minimise
and make good any damage.

18
Version 1.0
NPQS
A2-10 Metal Roofs

19
Version 1.0
NPQS
A2-10 Metal Roofs

5. VERIFICATION AND SUBMISSION

5.1 Submissions

5.1.1 Submissions
Include in construction program, event for submission of the following information:
a. Name of the metal roof manufacturer and inclusion of copies of technical data
relating to system proposal.
b. Composition of the roof system and associated components.
c. Name of Sub-Contractor – (if sub-contracted).
d. Information of current or completed similar jobs during the previous 5 years and
details of Quality Control Procedures adopted.

5.1.2 Computation Submissions


Where only performance values are specified, submit computations as follows:
Structural calculations for fixing system
a. Thermal performance calculation
b. Temporary support system calculation (if necessary)

5.1.3 Method Statements


Prior to commencing construction work, submit a detailed method statement to the
SO. Include at least the following information:
a. Sequence of Construction
b. Fixing and installation of the roof system
c. Method of forming laps, joints and penetrations, and application of sealant and
fillers.
d. Accommodation of lightning protection systems

5.1.4 Shop Drawings


Where specified, prepare shop drawings, particularly include:
a. Typical and non-typical details of roof system and associated components
including interfaces and flashings with adjacent structure and / or other cladding
elements.
b. End and side lap details and details at 1:5 scale of, ridge, eaves, gutters, valley,
hips and any changes in roof pitch.
c. Provision and supports for insulation, underlayment and vapour barriers.

20
Version 1.0
NPQS
A2-10 Metal Roofs

d. Waterproofing of penetration through roof, including lightning protection points


and vent pipes etc.
e. Details of drainage system
f. Penetrations to roof
Do not commence fabrication until shop drawings have been reviewed and
permission to proceed has been obtained from the SO.

5.1.5 Certification of Materials


Provide the SO with certification from the manufacturers of the following materials /
components, certifying that the respective materials are of the correct grade,
strength, size, finish, etc, and is in accordance with the relevant codes and standards
specified.
a. Roof Sheeting and coatings
b. Bolts, Screws, Fixings
c. Sealants, fillers and bi-metallic separators
d. Rain water goods
e. Insulation
f. Vapour barrier

5.1.6 Maintenance Manual


Submit maintenance/ replacement manual at the completion of the construction.
Include the following information in the maintenance manual and logbook.
a. An outline description of the completed roof system
b. A detailed description of specific materials and components with product names,
types, serial numbers, etc
c. Cleaning methods for roof surface, roof and gutters to be cleaned every six
months.
d. Roof fixings, flashings and sealant to be inspected every two years.

5.1.7 Warranty
Submit the warranty upon completion of the works.

5.1.8 Quality Control Plan Submission


Prepare and submit the quality control plan to the SO prior to starting work.

5.2 Samples and Mock-ups

5.2.1 Samples
For each system type specified provide samples of each component to permit
approval of material quality, thickness, finishes and profile.

21
Version 1.0
NPQS
A2-10 Metal Roofs

5.2.2 Mock-Ups
Within timeframe as directed, provide mock-up panel of sufficient size to permit
approval of the intended construction. Also include the following elements where
applicable:
a. Eaves
b. Ridge
c. Edge/gutter
d. Upstand
e. Vent pipes / other building services protrusions
If approved, this sample mock-up panel may form part of the works.
Refer to the PSD for additional requirements of mock-up panels if any.
Provide additional mock-ups as follows:
Mock-up Additional Requirements Due Date

5.3 Inspection and Tests

5.3.1 On Site Water Test


Carry out on site water tests, upon completion of a part of the works, in accordance
with the following procedure:
a. Spray with a continuous water jet from a water hose with normal tap pressure.
Hold the hose at 1.2 m away from the roof surface. Place the hose at the level of
horizontal joints so that the jet cone scatter will cover the joints.
b. The test is deemed as passed if there is no water seepage or dampness
observed from the underside of the roof.
c. Any areas showing water seepage or other defeats shall be made good after a
method statement for reinstatement has been accepted by the SO.
d. Use tested areas as a site quality standard for the remainder of the project.
Refer to PSD for area and frequency of test.
Carry out on site water test at the following area and frequency:
Area of Test Frequency of Test

22
Version 1.0
NPQS
A2-10 Metal Roofs

5.3.2 On Site Drainage Test


Upon completion of the roofing works and installation of rain water goods, carry out
on site drainage test to verify proper functioning and performance of the roof drainage
system, in accordance with SS CP 26.

23
Version 1.0

You might also like