Review of IS 9012:1978 Recommended Practice For Shotcreting: Recommendations For Inclusion and Amendment
Review of IS 9012:1978 Recommended Practice For Shotcreting: Recommendations For Inclusion and Amendment
Review of IS 9012:1978 Recommended Practice For Shotcreting: Recommendations For Inclusion and Amendment
Fine aggregate ACI 506.5R suggests a typical range from 7 to 10% (Max
15%) for the replacement of cement by silica fume. It also
The use of finer sand will generally result in greater drying mentions that addition of fly ash and slag is acceptable only if
shrinkage and coarser sand in more rebound. The Indian all shotcrete performance requirements can be demonstrated
standard suggests that sand for shotcrete shall grade evenly from during preconstruction testing. EFNARC has given max
fine to coarse as per Zone II and Zone III grading of IS 383-1970 percentage of silica fume as 15% of Portland cement. It has also
[7]. given that max percentage of fly ash and GGBS each as 30% of
The fine aggregate grading limits specified by IS 9012 and Portland cement. Thus it is proposed that the Indian standard
ACI 506R are in similar lines. The grading zone for fine should recommend an appropriate percentage of pozzolanic
aggregate suggested by IS 9012 as per IS 383 can be adopted. materials for the replacement of cement in shotcrete. Although
slag, fly ash and silica fume are used for durability requirement
Coarse aggregate and cost effectiveness, codes and literatures generally specify
Indian standard suggests that coarse aggregate shall conform silica fume with shotcrete instead of fly ash and slag. This may
to one of the grading with nominal maximum aggregate size of be due to the fact that silica fume increases early compressive
10, 12.5 and 20 mm as illustrated in Table I of IS 9012. and flexural strength of shotcrete considerably than fly ash and
slag. As noted earlier, even ACI has suggested the usage of fly
ACI 506R suggests the combined aggregates (fine and ash and slag only after preconstruction testing. Thus, it is
coarse) conform to either grading #1 or grading #2 with recommended to incorporate maximum percentage of silica
maximum aggregate size of 4.75 or 10 mm respectively. fume as 15% of Portland cement. The dosage of fly ash and slag
In practice, it has been observed that a coarse aggregate with shall be as per the design requirement of the project but the
maximum size of 10mm will promote an in-place shotcrete maximum replacement shall not exceed 30%.
274
v.Reinforcement and welded wire fabric as reinforcement in shotcrete whereas
Broad classification of reinforcement types used in shotcrete fibers are extensively used in current practice. In underground
is illustrated in Fig. 1. Indian standard mentions reinforcing bars and tunnel construction, it has become more common to use
fiber reinforcement instead of steel-mesh reinforcement.
. Fibers eliminate the need for conventional reinforcing steel and
welded wire mesh by imparting toughness or energy absorption
capability to hardened shotcrete. Additionally, fiber reinforced
shotcrete has high ductility, provides homogeneous fibre
reinforcement and strong bond to the surface [11].
Indian standard has not specified fibers for shotcrete
reinforcement. Other international standards such as ACI apart
from suggesting reinforcing bars and wire mesh have
extensively dealt with fibers also.
Typical length and diameter for different types of fiber as per
ACI is presented in Table. II. Both ACI and EN discuss the
dimensions and tolerances of steel fibers. As per both the codes
permissible deviation of the nominal/declared value from the
specified value shall not more than 10% for length and diameter
and 15% for aspect ratio respectively. In addition, EN also
specifies deviation of the average value relative to the declared
value.
A typical range of minimum and maximum dosages of
different types of fiber used in shotcrete as per three ACI codes
are depicted in Fig. 2. ACI reports specific dosages for both steel
and synthetic fibers whereas, EN although elaborates
extensively on fibres it has not included dosage for fibres. As
seen from the graph there is a variation in dosage of steel fibers
within ACI codes.
The dosage and type of fiber shall be selected based on the
Fig 1 - Reinforcement in Shotcrete design requirement of the project.
275
iii. Bond strength
III.STRENGTH PROPERTIES
Strength developed between the substrate and shotcrete layer
A. Indian codal provisions can be termed as bond strength. Inference from both ASTM and
The physical properties of sound shotcrete in place are EN is if the failure occurs in the bond zone then it is reported as
comparable to those of conventional mortar or concrete of the bond strength between the two materials whereas if the failure
same composition. Most reported values for 28 days occurs in any individual material then it is reported as tensile
compressive strength are in the range of 20 to 50 N/mm2. It is strength of that material. Bond strength reported in ACI is
suggested that strength higher than 25 N/mm2 be specified only illustrated in Fig. 3.
for the most carefully executed shotcrete jobs.
B. Commentary and Recommendations
Indian standard does not mention minimum requirement for
the strength properties such as flexural strength, bond strength
and toughness of shotcrete to be achieved. Provisions mentioned
in other International standards are elucidated below
i. Compressive strength
IS 9012 mentioned that the compressive strength of 28 days
shotcrete are in the range of 20 to 50 MPa. Whereas, ACI 506R
reports that the strength of wet mix shotcrete is generally
between 30 to 50 MPa and strengths over 100 MPa have been
reported. ACI 506.5R specifies the minimum compressive
strength as 30 MPa whereas for some special application such as
permanent tunnel lining, compressive strength of 40 MPa or Fig 3 - Bond Strength (ACI)
more is specified. Bond strength mentioned in ACI 506.1 & 506.5 is between
EFNARC states that compressive strength classes of sprayed shotcrete and rock whereas in ACI 506, it is not clearly
concrete vary from C24/30 to C48/60. The minimum mentioned. As depicted above there is a variation in the range of
compressive strength of C24/30 and C48/60 are 20.5 MPa and bond strength specified within ACI codes.
41 MPa respectively as per the in-situ strength requirement. EN Minimum bond strength required as per EFNARC is
refers to EN 206-1 for the compressive strength classes of demonstrated in Fig. 4.
sprayed concrete. EN 206-1 lists compressive strength class
from C8/10 to C 100/115.
Compressive strength of shotcrete depends on improving
density of the material, maximizing hydration of cement and
minimizing porosity. Modern specifications typically require
compressive strengths of 20 MPa (for temporary sprayed
concrete) to 40 MPa or higher (for permanent sprayed concrete)
at 28 days [12]. Thus current minimum compressive strength of
20 MPa in IS 9012 should suffice for the Indian conditions.
ii. Flexural Strength
Flexural strength is usually specified for fiber reinforced
shotcrete. Load deflection curve obtained by testing a simply
supported beam under third-point loading is used for the
evaluation of flexural strength. Minimum flexural strength as Fig 4 - Bond Strength (EFNARC)
per ACI & EFNARC is presented in Table III. Typical value of 0.5 to 1.5 MPa is recommended for bond
TABLE III - MINIMUM FLEXURAL STRENGTH strength between shotcrete and rock. These values might vary
depending on the fiber content.
Minimum Flexural Strength (MPa)
iv. Toughness
EFNARC
ACI 506.5 As per ACI 506.1R toughness energy is quoted as “ability of
C 24/30 C 36/45 C 44/55
4 to 4.5 3.4 4.2 4.6
the shotcrete specimen to absorb energy before and after
cracking” [13]. Energy absorption as per ACI & EFNARC is
It is a well-known fact that the flexural strength increases in illustrated in below
accordance with compressive strength. Dosage of fiber also
influences flexural strength of shotcrete. For a typical M40 grade The energy absorption of the shotcrete panel depends on
shotcrete, flexural strength from 4 to 4.5 MPa is recommended, centrally loaded round panel or square panel test method. Thus
whereas up to 6 MPa can also be achieved. a minimum energy absorption value of 280 joule (Upto 40 mm
deflection) and 500 joule (Upto 25 mm deflection) is
276
recommended for round panel and square panel test ii. Permeability
respectively. EFNARC suggests a maximum value of water penetration in
TABLE IV – ENERGY ABSORPTION accordance with EN 7031 as 50mm and the mean average value
shall be less than 20mm. Also it states that sprayed concrete is
Energy Absorption (Joule) considered water-tight when the coefficient of water
ACI 506.5 EFNARC & EN permeability is less than 10-12 m/s. Similarly EN suggests
resistance to water penetration in accordance with EN 12390-8
for deflection upto 40mm for deflection upto 25mm
as 50mm [15]. Latest test procedure as per EN can be
a b c incorporated in the Indian Standard to measure permeability.
280
500 700 1000
iii. Air content
IV.DURABILITY PROPERTIES Air content (%) and spacing factor are related to the freezing
and thawing resistance of shotcrete. The term "spacing factor"
A. Indian codal provisions refers to the distance between air bubbles in hardened shotcrete.
Indian standard specifies a drying shrinkage range of 0.06% ACI 506R recommends an entrained air-void system with in
to 0.1% for the shotcrete. As far as durability is concerned Indian place air content in the range of 4 to 6% with a maximum air
standard has a brief mention that durability of shotcrete in void spacing factor of 0.3mm to resist freezing and thawing
laboratory tests and under field exposure has generally been cycles. Further it states that total air content in concrete before
good. shooting as 6 to 10%.
B. Commentary and Recommendations ACI 506.5R suggests air content as shot: 4 ± 1% and Air
content immediately before the pump as 7 to 10%. Further it
Permeability and porosity are the two important factors for a
states a maximum spacing factor of 0.3mm for as shot. A
durable shotcrete and they in turn affect the other parameters
minimum air content of 7 ± 1% before shooting and 4 ± 1% as
such as strength and ability to resist deterioration mechanism.
shot is recommended where freezing and thawing resistance is
Codal provisions pertaining to above discussed parameters in the
of interest.
other international standards have been elaborated below
EFNARC and EN does not discuss the concept of air content.
i. Absorption and volume of permeable voids EN has noted that current available test methods for the
Boiled Water Absorption (BWA) and Maximum Volume of measurement of air content do not give reliable data results for
Permeable voids (VPV) are related in the sense they both fresh sprayed concrete.
measure porosity due to capillary action in the sample, but
express differently. BWA represents mass ratio whereas the V.TESTING
VPV represents the volumetric ratio of water absorbed. ACI
A. Indian codal provisions
506R recommends acceptable values of permeable void volume
in the range of 14 to 17% and typical boiled absorption values in Indian standard focuses on the compressive strength from
the range 6 to 9%. Similarly, ACI 506.5R specifies maximum preconstruction testing. The code suggests that the cubes or
volume of permeable voids at 7 days as 17% and maximum cores shall be taken from the panel of size 75 x 75 cm with
boiled absorption at 7 days as 8%. thickness same as in the structure but not less than 7.5cm. It also
specifies the core shall have a minimum diameter of 7.5 cm and
Test method as per ASTM C642 can be incorporated in the a length-diameter ratio of at least 1.
Indian standard to find BWA and VPV. Morgan et al (1987)
have published quality indicators based on ASTM C 642 results, B. Commentary and Recommendations
as shown in the table below [14]. Compressive, flexural and energy absorption tests are widely
TABLE V – VPV AND BWA adopted to evaluate shotcrete quality. Similarly, bond strength is
adopted to examine the strength developed between the
Shotcrete Permeable void Boiled water absorption shotcrete layer and substrate such as rock or concrete.
quality volume (%) (%)
Brief description of the test method specifications mentioned
Excellent < 14 <6 in international standards has been discussed below. As the
Indian standard does not include any of the below mentioned
Good 14 to 17 6 to 8
tests, it is recommended to incorporate these test methods.
Fair 17 to 19 8 to 9
i. Flexural strength Test
Marginal > 19 >9 ACI refers ASTM C1609 for the testing of flexural strength
of shotcrete. The code recommends Third-point loading test
EFNARC and EN does not include the concept of BWA and with deflection controlled machine. This test method utilizes
VPV. Although table suggested by Morgan are being used as a two preferred specimen sizes of 100 x 100 x 350mm tested on a
quality indicator, further research is underway to establish clear 300 mm span (or) 150 x 150 x 500 mm tested on a 450mm span
relationship between BWA and compressive strength and also as presented in Fig 5. ACI suggests an increase in rate of
between BWA and durability of shotcrete. deflection as illustrated in Table VI.
277
TABLE VI – RATE OF INCREASE IN NET DEFLECTION
278
together with a portion of the substrate rock/concrete and then Larger aggregates and fibers show a significant rebound in
tested as depicted in Fig 9 shotcrete. Lower aggregate density and the addition of fine
particles reduce aggregate rebound. Synthetic fibers display
lower rebound than steel fibers. Also advanced application
techniques have evolved in recent times which reduce rebound.
Hence aggregate size, fiber type and application technique plays
a key role in the percentage of rebound in shotcrete. Considering
the aforementioned factors and surface of application, the values
for percentage of rebound is recommended as proposed in Table
VII. EN and EFNARC have not included the criteria for
percentage of rebound.
TABLE VII – PERCENTAGE OF REBOUND
Fig 8 - Direct tension test (Pull-off method) – ACI
% of Rebound
.EFNARC specifies a specimen with core diameter of 50 to Surface
60 mm. The code suggests the rate of loading shall be 1 to 3 MPa IS 9012 ACI 506R Proposed
per minute. EN specifies a specimen with core diameter of 50 to
Floors or Slabs 5 to 15 0 to 10 0 to 5
100mm and length not less than 2d. The code suggests the rate
of loading shall be 0.05 ± 0.01 MPa per second. Sloping &
15 to 30 10 to 30 10 to 30
vertical walls
Overhead
25 to 50 10 to 30 15 to 30
work
279
[3] European Standard for Sprayed concrete (Part 1 - Definitions, specifications,
and conformity), BS EN 14487-1-2005, British Standards Institution.
[4] European specification for sprayed concrete, EFNARC-1996, European
Standards.
[5] European Standards for Concrete - Specification, performance, production and
conformity, BS EN 206-2013, British Standards Institution.
[6] Indian standard code of practice for Plain and Reinforced Concrete, IS 456-
2000, Bureau of Indian Standards, New Delhi.
[7] Indian standard code for Specification for Coarse and fine aggregates from
Natural sources for concrete, IS 383-1970, Bureau of Indian Standards, New
Delhi.
[8] Simon Reny and Marc Jolin, Improve Your Shotcrete: Use Coarse Aggregates,
Technical tip, Shotcrete - Winter 2011.
[9] American Standard code for Guide to Specifying Underground Shotcrete, ACI
506.5R-09, American Concrete Institute.
[10] V.M Malhotra and P. Kumar Mehta, Pozzolanic and Cementitious Materials,
Advances in Concrete Technology, Volume 1, 1996.
[11] O. Cengiz, L. Turanli, Comparative evaluation of steel mesh, steel fibre and
high-performance polypropylene fibre reinforced shotcrete in panel test,
Cement and Concrete Research, 2004.
[12] Alun thomas, Sprayed concrete lined tunnels - An introduction, Taylor &
Francis group, London & New york, 2009.
[13] American Standard code for Guide to Fiber-Reinforced Shotcrete, ACI 506.1R-
08, American Concrete Institute.
[14] Louis-Samuel Bolduc and Marc Jolin, Shotcrete Boiled Water Absorption,
Shotcrete - Winter 2010.
[15] European Standard for Testing hardened concrete. Depth of penetration of
water under pressure, BS EN 12390-8-2009, British Standards Institution.
[16] European Standard for Testing sprayed concrete, BS EN 14488-2006 (Part 1 to
7), British Standards Institution.
[17] Bernard, E.S. Correlations in the behavior of fibre reinforced shotcrete beam
and panel specimens, Materials and Structures, RILEM, 2002
[18] Josef Kaufmann, Rebound and orientation of fibers in wet sprayed concrete
applications, Construction and Building Materials, 2013.
[19] Standard Test Method for Density, Absorption, and Voids in Hardened
Concrete, ASTM C642-06, American Society for Testing and Materials.
[20] European Standard for Testing concrete - Determination of the depth of
penetration of water under pressure, EN 7031, British Standards Institution.
[21] Standard Test Method for Flexural Performance of Fiber-Reinforced Concrete
(Using Beam With Third-Point Loading), ASTM C1609-12, American Society
for Testing and Materials.
[22] Standard Test Method for Flexural Toughness of Fiber Reinforced Concrete
(Using Centrally Loaded Round Panel), ASTM C1150-12, American Society
for Testing and Materials.
[23] Standard Test Method for Tensile Strength of Concrete Surfaces and the Bond
Strength or Tensile Strength of Concrete Repair and Overlay Materials by
Direct Tension (Pull-off Method), ASTM C1583- 13, American Society for
Testing and Materials
280