DB3 Range - SOUNDERS - Up To 118 DB (A) : Exd (E), Weatherproof
DB3 Range - SOUNDERS - Up To 118 DB (A) : Exd (E), Weatherproof
DB3 Range - SOUNDERS - Up To 118 DB (A) : Exd (E), Weatherproof
Exd(e), Weatherproof
Features
ᔢ Zone 1, Zone 2 and non-Ex use.
ᔢ Ex de IIC T4/T5.
ᔢ ATEX approved, EEx II 2GD.
ᔢ Optional Exe terminal chamber.
ᔢ IECEx certified Gb, Db.
ᔢ UL Listed for USA and Canada
– Hazardous locations:
Class I, Div 2, Groups A-D.
Class II, Div 2, Groups F & G
Class I, Zones 1 & 2, AExd IIC T4.
– Ordinary locations: Audible-Signal Device.
ᔢ GOST ‘R’ & ‘K’ certified.
ᔢ Chinese (CQST) certified.
ᔢ Brazilian (Inmetro) certified.
ᔢ IP66 and IP67.
ᔢ SIL 1 Certified.
ᔢ Designed in accordance with EN54-3
ᔢ *Certified temperature: –55°C to +70°C.
ᔢ All GRP corrosion free flamepaths.
ᔢ Up to 118dB(A) output.
ᔢ Integral volume control.
ᔢ 27 tones, user selectable.
Introduction ᔢ Tones comply with UKOOA/PFEER guidelines.
ᔢ Two tones may be switched via the external
This range of light weight all GRP, flameproof sounders is intended for use in voltage supply – now available in a.c. and d.c.
potentially explosive gas and dust atmospheres and has been designed versions.
with high ingress protection to cope with the harsh environmental conditions ᔢ Tones may be programmed to customer
found offshore and onshore in the oil, gas and petrochemical industries. specification.
The flamepaths, flare and the body, are manufactured completely from a UV ᔢ d.c. version accepts any voltage between
12V d.c. and 48V d.c.
stable glass reinforced polyester.
ᔢ End of line resistor option.
Stainless steel screws and sinter are incorporated thus ensuring a corrosion
ᔢ Sounder/Beacon Combination Unit available.
free product. A tapered flamepath is used to overcome the problems of
assembly of parallel spigot flamepaths. *Depending on version.
Sales Enq. UK: +44 (0)1773 864 100 Sales Enq. USA: +1 (713) 937- 9772 E-Mail: medc.sales@cooperindustries.com Web: www.coopermedc.com
6DS094/S
Specification ALL DIMENSIONS
ALL DIMENSIONS IN IN MILLIMETRES
MILLIMETRES
322±3
271±3 WITHOUT Exe CHAMBER
Model Details Certification Code Voltage Code Label Code Entries Code Finish Code
DB3 Standard unit Uncertified W 12V - 48V d.c. 048 Duty D* 1 x M20 (Exd) 1B Natural Black N
DB3P Two stage Exd D 110V a.c. 110 Tag T* 2 x M20 (Exd/Exde) 2B Red R
DB3L*† Low temp. Exde E 120V a.c. 120 None N 1 x 1/2" NPT (UL only) 1C Special S*
standard unit IECEx Exd DJ 220V a.c. 220 2 x 1/2" NPT (UL only) 2C
IECEx Exe EJ * Please specify wording * Please specify.
DB3LP*† Low temp. UL Listed UL* 230V a.c. 230
To specify certified
two stage UL (Ordinary Locations) UW 240V a.c. 240 plug, suffix appropriate
ATEX/UL Dual Listed AU 254V a.c. 254 code with 'P', e.g. 2BP Option Code
* Available unpainted only.
GOST ‘R’ Exd DG is 2 x M20 entries with None N
† Min IECEx temp - 40ºC.
GOST ‘R’ Exde EG one certified plug. End of line E*
GOST ‘K’ Exd DK resistor
Gost 'K' Exe EK Special tone S
Chinese (CQST) Q
Inmetro Exd DM * State value.
Inmetro Exde EM * Not all options are available UL listed
All the above specifications, dimensions, weights and tolerances are nominal (typical) and Cooper MEDC reserve the right to vary all data without prior notice. No liability is accepted for any consequence of use.
02/12