Directional or Non-Directional Earth-Fault Relay REJ 527: Technical Reference Manual
Directional or Non-Directional Earth-Fault Relay REJ 527: Technical Reference Manual
Directional or Non-Directional Earth-Fault Relay REJ 527: Technical Reference Manual
Earth-Fault Relay
REJ 527
Technical Reference Manual
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
Issued: 07.07.1999
Version: C/14.11.2005
Contents
1. About this manual .....................................................................5
1.1. Copyrights .....................................................................................5
1.2. Trademarks ...................................................................................5
1.3. Guarantee .....................................................................................5
1.4. General .........................................................................................5
1.5. Use of symbols ..............................................................................6
1.6. Terminology ..................................................................................6
1.7. Related documents .......................................................................6
1.8. Document revisions .......................................................................6
2. Safety Information .....................................................................7
3. Introduction ...............................................................................9
3.1. Use of the relay .............................................................................9
3.2. Features ........................................................................................9
4. Instructions ..............................................................................11
4.1. Application ...................................................................................11
4.2. Requirements ..............................................................................11
4.3. Configuration ...............................................................................11
5. Technical description .............................................................13
5.1. Functional description .................................................................13
5.1.1. Product functions .............................................................13
5.1.1.1. Schema of product functions ............................13
5.1.1.2. Earth-fault current, zero-sequence voltage and
intermittent earth-faults ......................................13
5.1.1.3. Inputs ...............................................................14
5.1.1.4. Outputs .............................................................14
5.1.1.5. Circuit-breaker failure protection unit ...............14
5.1.1.6. Disturbance recorder ........................................14
5.1.1.7. HMI module ......................................................14
5.1.1.8. Non-volatile memory ........................................15
5.1.1.9. Self-supervision ................................................15
5.1.2. Measurements .................................................................15
5.1.3. Configuration ....................................................................16
5.1.4. Protection .........................................................................17
5.1.4.1. Block diagram ..................................................17
5.1.4.2. Directional or non-directional earth-fault
current unit .........................................................17
5.1.4.3. Zero-sequence voltage unit ..............................21
5.1.4.4. Protection against intermittent earth-faults .......22
5.1.4.5. Time/current characteristics .............................23
3
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
4
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
1.1. Copyrights
The information in this document is subject to change without notice and should not
be construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for
any errors that may appear in this document.
In no event shall ABB Oy be liable for direct, indirect, special, incidental or
consequential damages of any nature or kind arising from the use of this document,
nor shall ABB Oy be liable for incidental or consequential damages arising from
use of any software or hardware described in this document.
This document and parts thereof must not be reproduced or copied without written
permission from ABB Oy, and the contents thereof must not be imparted to a third
party nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license
and may be used, copied, or disclosed only in accordance with the terms of such
license.
Copyright © 2005 ABB Oy
All rights reserved.
1.2. Trademarks
ABB is a registered trademark of ABB Group.
All other brand or product names mentioned in this document may be trademarks or
registered trademarks of their respective holders.
1.3. Guarantee
Please inquire about the terms of guarantee from your nearest ABB representative.
1.4. General
The purpose of this manual is to provide the user with thorough information on the
protection relay REJ 527 and its applications, focusing on giving a technical
description of the relay.
Refer to the Operator’s Manual for instructions on how to use the
Human-Machine Interface (HMI) of the relay, also known as the Man-Machine
Interface (MMI), and to the Installation Manual for installation of the relay.
5
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
Although warning hazards are related to personal injury, and caution hazards are
associated with equipment or property damage, it should be understood that
operation of damaged equipment could, under certain operational conditions, result
in degraded process performance leading to personal injury or death. Therefore,
comply fully with all warning and caution notices.
1.6. Terminology
The following is a list of terms that you should be familiar with. The list contains
terms that are unique to ABB or have a usage or definition that is different from
standard industry usage.
Term Description
IEC_103 IEC 60870-5-103, a communication protocol standardized by the
International Electrotechnical Commission
SPA A data communication protocol developed by ABB
6
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
2. Safety Information
Dangerous voltages can occur on the connectors, even though the
auxiliary voltage has been disconnected.
Non-observance can result in death, personal injury or substantial
property damage.
Only a competent electrician is allowed to carry out the electrical
installation.
National and local electrical safety regulations must always be
followed.
The frame of the device has to be carefully earthed.
The device contains components which are sensitive to electrostatic
discharge. Unnecessary touching of electronic components must
therefore be avoided.
Breaking the sealing tape on the rear panel of the device will result
in loss of warranty and proper operation will no longer be
guaranteed.
7
8
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
3. Introduction
3.2. Features
• Directional or non-directional low-set earth-fault current stage with
definite-time or inverse definite minimum time (IDMT) characteristic
• Directional or non-directional high-set earth-fault current stage with definite-time
characteristic
• Deblocking zero-sequence voltage stage with definite-time characteristic
• The two earth-fault current stages can be configured to operate alternatively as
two voltage stages: three-stage voltage monitoring operation possible
• Intermittent earth-fault protection
• Circuit-breaker failure protection (CBFP)
• Disturbance recorder
• recording time up to 19 seconds
• triggering by a start or a trip signal from any protection stage and/or by a binary
input signal
• records two analogue channels and seven digital channels
• adjustable sampling rate
• Non-volatile memory for
• up to 60 event codes
• setting values
• disturbance recorder data
• recorded data of the five last events with time stamp
• number of starts for each stage
• alarm indication messages and LEDs showing the status at the moment of
power failure
• Two accurate measuring inputs
• Galvanically isolated binary input with a wide input voltage range
9
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
10
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
4. Instructions
4.1. Application
The directional or non-directional earth-fault relay REJ 527 is a secondary relay
which is connected to the voltage and current transformers of the object to be
protected. The earth-fault current and the zero-sequence voltage unit continuously
measure the zero-sequence voltage, earth-fault current and phase angle of the object.
On detection of a fault, the relay will start, trip the circuit breaker, provide alarms,
record fault data, etc., in accordance with the application and the configured relay
functions.
The voltage unit includes low-set stage U0b> and the earth-fault current unit low-set
stage I0> and high-set stage I0>>. The earth-fault stages can be replaced by two
additional voltage stages, low-set stage U0> and high-set stage U0>>.
The protection functions are independent of each other and have their own setting
groups and data recordings. The voltage and current functions use conventional
transformer measurement.
An output contact matrix allows start or trip signals from the protection stages to be
routed to the desired output contact.
4.2. Requirements
When the REJ 527 is operating under the conditions specified below (see also
“Technical data”), it will be practically maintenance-free. The relay includes no
parts or components subject to abnormal physical or electrical wear under normal
operating conditions.
Environmental conditions
4.3. Configuration
Setting and connection example
The appropriate configuration of the output contact matrix enables the use of the
signals from the earth-fault current and the voltage unit as contact functions. The
start signals can be used for blocking co-operating protection relays, signalling and
initiating autoreclosing.
Figure 4.3.-1 represents the REJ 527 with the default configuration: all trips are
routed to trip the circuit breaker.
11
12
REJ 527
L1
L2
L3
-
0
A
N
-
dn I
da PC
S1 P1
I O
Earth-Fault Relay
S2 + Tx Rx
P2 +
RER 103
Uaux ~ +
+ + +
100V
* ~
Spa Bus
+ -
Optical
PC-interface
IRF
SGR1 X X 2 1
Uob> START
5 SGB1 SGR2 4 3 X X
*REJ527B 418BAA: 2=5A Blocking of stage Uob> TRIP
3=1A
SGR3 X X 2 1
Io> START
REJ527B 411BAA: 2=1A 6
SGB1 SGR4 4 3 X X
3 = 0.2 A Blocking of stage Io> TRIP
SGR5 X X 2 1
Io>> START
7 SGB1 SGR6 4 3 X X
Blocking of stage Io>> TRIP
X=Default value
1 SGB1 I/O
INDICATIONS CLEARED
A0501420
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
5. Technical description
PO2
SO2
IRF
Optical pc-
interface
Serial communication
A0501421
13
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
5.1.1.3. Inputs
The REJ 527 includes two energizing inputs and one external binary input controlled
by an external voltage. For details, refer to section Input/output connections and
tables 5.1.4.6-7, 5.2.1-1 and 5.2.1-5. The function of the binary input is determined
using the SGB switches.
5.1.1.4. Outputs
The REJ 527 is provided with two power outputs (PO1 and PO2) and two signal
outputs (SO1 and SO2). Switchgroups SGR1...6 are used for routing start and trip
signals from the protection stages to the desired signal or power output. PO1 and
PO2 can be configured to be latched and the minimum pulse length to 40 or 80 ms.
14
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
5.1.1.9. Self-supervision
The self-supervision system of the REJ 527 manages run-time fault situations and
informs the user about an existing fault. When the self-supervision system detects a
permanent internal relay fault, the READY indicator LED will start to blink. At the
same time the self-supervision alarm relay (also referred to as the IRF relay), which
is normally picked up, will drop off and a fault code will appear on the LCD. The
fault code is numerical and identifies the fault type. For fault codes, refer to section
Internal fault in the Operator’s Manual.
INTERNAL FAULT
FAULT CODE :56
A501289
5.1.2. Measurements
The table below presents the measured values which can be accessed through the
HMI. The measured voltage is shown as a percentage of the rated voltage, Un, and
the measured currents of the rated current, In, of the energizing input. The phase
angle is shown in degrees and can be selected to be shown either as the angle
between the voltage and the current or as the angle between the basic angle and the
current with switch SGF3/8. If the measured current and voltage values are too low,
i.e. lower than 0.50 percent, dashes will be shown on the LCD.
15
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
5.1.3. Configuration
The figure below illustrates how the start, trip and binary input signals can be
configured to obtain the required protection functionality.
BI IRF SO2 SO1 PO2 PO1
X2.1 17 18 13 14 15 10 11 12 7 8 9 5 6 3 4
+ + +
IRF
Uo SGR1 4 3 2 1
Uob> START
Io 5 SGB1 SGR2 4 3 2 1
Blocking of stage Uob> TRIP START
SGR3 4 3 2 1
START TRIP
Io>
6 SGB1 SGR4 START 4 3 2 1
Blocking of stage Io> TRIP
SGR5 TRIP
START 4 3 2 1
Io>>
7 SGB1 SGR6 START 4 3 2 1
Blocking of stage Io>> TRIP
1 SGB1 TRIP
INDICATIONS CLEARED
SGF1...SGF5
A0501422
16
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
5.1.4. Protection
SGF2/8 tb>
SGR2/x 1 1 PO1
Uo>
SGB1/5
SGF3/1 SGR3/x
&
0.50% x Un 70 ms
Io> SGF1/5 0.1 ... 1s
to>,k
SGR4/x
SGF2/7
&
5s C
0.48% x In jb/Ij SGB1/6
SGF1/2
Uo>>
PO2
SGR5/x 1
2
60 ms 1
j
SGF3/3
& SGF2/3
to>>
SGR6/x 3 SO1
4 SO2
SGB1/7
Io>>
Io
Uob> START
SGF2/1 Io>
1
0.12 * Io>
2 * Io>> Io>>
C
60 ms
Fig. 5.1.4.1.-1 Block diagram of the directional earth-fault relay REJ 527
17
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
When an earth-fault stage starts, a start signal will be generated and a start indication
shown on the HMI. If the above mentioned criteria remain fulfilled until the set
operate time elapses, the stage will deliver a trip signal and a trip indication will be
shown on the HMI. The trip indication will remain active although the protection
stage is reset. The direction of the fault spot is determined by means of the angle
between the voltage and the current. Basic angle ϕb can be set between -90° and 0°.
When basic angle ϕb is 0-°, the negative quadrant of the operation sector can be
extended with ϕa (see Fig. 5.1.4.2.-1). Extended operation sector ϕa can be set
between 0 and 90°.
Figures 5.1.4.2.-1, 5.1.4.2.-2 and 5.1.4.2.-3 show examples of the basic angle
characteristic.
Io
In jb=0°
ja=40° Dj=80°
6
OPERATION OPERATION
AREA 4 AREA
Negative Positive
quadrant quadrant
3
1
Io>
-140° -120° -100° -80° -60° -40° -20° 0° 20° 40° 60° 80° 100°
NON-OPERATION AREA
A0501424
LEAD LAG
Uo
Io
OPERATION SECTOR
jb=0°
j Dj=80°
Dj
Io>
ja=40°
A0501425
18
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
LEAD LAG
Uo
Io
Io>
Dj
OPERATION SECTOR
jb=-90°
Dj=80°
A0501426
19
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
jc=2..7°
Uo
Io
Io>(>)
jc=2..7°
A0501427
Uo
Io
j
jc=2..7° jc=2..7°
Io>(>)
A0501428
20
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
When the earth-fault current exceeds the set start value of high-set stage I0>>, the
earth-fault unit will start to deliver a start signal after a ~ 60 ms’ start time. When
the set operate time elapses, the earth-fault unit will deliver a trip signal.
It is possible to block the start and the tripping of an earth-fault stage by applying an
external binary input signal to the relay.
The inverse-time function of stage I0> can be set to be inhibited when stage I0>>
starts with a switch of switchgroup SGF2. In this case the operate time will be
determined by stage I0>>.
The high-set stage can be set out of operation. This state will be indicated by dashes
on the LCD and by “999” when the set start value is read via serial communication.
The set start value of stage I0>> can be automatically doubled in a start situation,
e.g. when the object to be protected is connected to a distribution network. Thus a
set start value below the connection inrush current level can be selected for stage
I0>>. A start situation is defined as a situation where the earth-fault current rises
from a value below 12% x I0> to a value above 150% x I0> in less than 60 ms. The
start situation ends when the current falls below 125% x I0>.
21
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
Instantaneous
peak value of
Instantaneous neutral current Io
value of neutral
voltage Uo
Fundamental
amplitude of Io
A0501429
Set value
³100ms ³100ms
Trip level
A0501430
22
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
The resetting time can be set to 80, 100, 500 or 1000 ms in SGF5. When the resetting
time is set to 100 ms or above, earth-fault stage I0> will operate as an intermittent
earth-fault stage.
k×β
t [ s ] = --------------------------
Io- α
-------- –1
Io>
where
t = operate time
k = time multiplier
I0 = earth-fault current value
I0> = set start value
23
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
According to the standard, the normal current range is 2...20 times the setting value
at normal inverse, very inverse or extremely inverse characteristic. The relay is to
start before the current exceeds the setting value by 1.3 times. At long-time inverse
characteristic, the normal current range is specified to be 2...7 times the setting
value, and the relay is to start before the current exceeds the setting value by 1.1
times.
Within the normal current range the inverse-time stage fulfils the tolerance
requirements of class 5 at all degrees of inversity.
The time/current characteristics according to the IEC and BS standards are
illustrated in Fig. 5.1.4.5.-1...Fig. 5.1.4.5.-4.
If the ratio between the current and the set start value is higher than
20, the operate time will be the same as when the ratio is 20.
RI-type characteristic
The RI-type characteristic is a special characteristic which is principally used for
obtaining time grading with mechanical relays. The characteristic can be expressed
mathematically as follows:
k
t [ s ] = -------------------------------------------------
Io>
0.339 – 0.236 × ---------
Io
where
t = operate time
k = time multiplier
I0 = earth-fault current value
I0> = set start value
The RI-type characteristic is illustrated in Fig. 5.1.4.5.-5.
24
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
RD-type characteristic
The RD-type characteristic is a special characteristic which is principally used in
earth-fault protection and which requires a high degree of selectivity even at high
resistance faults. The protection can operate in a selective way even if it is not
directional. Mathematically the time/current characteristic can be expressed as
follows:
Io
t [ s ] = 5.8 – 1.35 × log e ------------------
k × Io>
where
t = operate time
k = time multiplier
I0 = earth-fault value
I0> = set start value
The RD-type characteristic is illustrated in Fig. 5.1.4.5.-6.
25
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
t/s
70
60
50
40
30
20
10
9
8
7
6
5
4
3 k
1.0
2 0.9
0.8
0.7
0.6
0.5
1
0.9 0.4
0.8
0.7 0.3
0.6
0.5
0.2
0.4
0.3
0.1
0.2
0.05
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
1 2 3 4 5 6 7 8 9 10 20 Io/Io>
A0501292
26
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
t/s
70
60
50
40
30
20
10
9
8
7
6
5
4
1
0.9
0.8 k
0.7 1.0
0.6 0.9
0.8
0.5 0.7
0.6
0.4
0.5
0.3 0.4
0.3
0.2
0.2
0.1
0.09 0.1
0.08
0.07
0.06
0.05
0.05
0.04
0.03
0.02
1 2 3 4 5 6 7 8 9 10 20 Io/Io>
A0501293
27
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
t/s
70
60
50
40
30
20
10
9
8
7
6
5
4
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
k
1.0
0.2 0.9
0.8
0.7
0.6
0.5
0.1 0.4
0.09
0.08 0.3
0.07
0.2
0.06
0.05
0.1
0.04
0.05
0.03
0.02
1 2 3 4 5 6 7 8 9 10 20 Io/Io>
A0501294
28
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
t/s
700
600
500
400
300
200
100
90
80
70
60
50
40
30
20
10
9
8 k
7
1.0
6 0.9
5 0.8
0.7
4
0.6
3 0.5
0.4
2
0.3
0.2
1
0.9
0.8
0.7
0.6 0.1
0.5
0.4
0.05
0.3
0.2
1 2 3 4 5 6 7 8 9 10 20 Io/Io>
A0501295
29
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
t/s
70
60
50
40
30
20
10
9
8
7
6
5
4
k
3 1.0
0.9
0.8
0.7
2 0.6
0.5
0.4
1
0.9 0.3
0.8
0.7
0.6 0.2
0.5
0.4
0.3 0.1
0.2
0.05
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
1 2 3 4 5 6 7 8 9 10 20 Io/Io>
A0501296
30
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
t/s
70
60
50
40
30
20
10
9
8
7
6
5
4
1 k
0.9
0.8 1.0
0.7 0.9
0.6
0.8
0.5
0.4
0.7
0.3
0.2
0.6
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.05 0.1 0.2 0.3 0.4 0.5
0.03
0.02
1 2 3 4 5 6 7 8 9 10 20 30 40 I o / I o >
A0501297
31
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
5.1.4.6. Settings
There are two alternative setting groups available, setting groups 1 and 2. Either of
these setting groups can be used as the actual settings, one at a time. Both groups
have their related registers. By switching between the setting groups a whole group
of settings can be changed at the same time. This can be done in any of the following
ways:
Group configuration:
• via the HMI
• entering parameter V150 via serial communication
Group selection:
• switching between Group1 and Group2 is accomplished by means of the external
binary input
The setting values can be altered via the HMI or with a personal computer provided
with the Relay Setting Tool.
Before the relay is connected to a system it must be assured that the relay has been
given the correct settings. If there is any doubt, the setting values should be read with
the relay trip circuits disconnected or tested with current injection, refer to section
Check lists for additional information.
32
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
Checksum SG_ ∑ = 85
33
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
SGF1...SGF5
Switchgroups SGF1...SGF5 are used for configuring the desired function as
follows.
34
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
35
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
36
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
If the resetting time ≥100 ms, stage I0> will operate as an intermittent earth-fault
stage.
37
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
SGB1
Table 5.1.4.6-7 SGB1 Resetting/blocking with BI
Default
Switch Function
setting
SGB1/1 • 0 = indications are not cleared by the binary input signal 0
• 1 = indications are cleared by the binary input signal
SGB1/2 • 0 = indications are not cleared and latched output contacts are 0
not unlatched by the binary input signal
• 1 = indications are cleared and latched output contacts are
unlatched by the binary input signal
SGB1/3 • 0 = indications and memorized values are not cleared and 0
latched output contacts are not unlatched by the binary input
signal
• 1 = indications and memorized values are cleared and latched
output contacts are unlatched by the binary input signal
SGB1/4 Switching between setting groups 1 and 2 using the external 0
binary input
• 0 = the setting group cannot be changed using the external
binary input
• 1 = the currently used setting group is determined by the binary
input. When the binary input is energized, setting group 2 will be
activated.
Note!
When SGB1/4 is set to 1, it is important that the switch has the
same setting in both setting groups.
SGB1/5 Blocking of stage tb> by the binary input signal 0
SGB1/6 Blocking of stage t0> by the binary input signal 0
SGB1/7 Blocking of stage t0>> by the binary input signal 0
• When SGB1/5...7 = 0, tripping of the stage will not be blocked by
the external binary input signal.
• When SGB1/5...7 = 1, tripping of the stage will be blocked by the
external binary input signal.
SGB1/8 Set the basic angle 0°/-90° or cos(ϕ)/sin(ϕ) using the binary input 0
• 0 = the binary input signal does not affect the basic angle
• 1 = the basic angle is -90° or sin(ϕ) when the external binary
input signal is not energized. When the input is energized, the
basic angle is 0° or cos(ϕ).
Σ SGB1 0
SGR1...SGR6
The start and trip signals from the protection stages are connected to the output
contacts with the switches of switchgroups SGR1...SGR6.
The matrix below can be of help when making the desired selections. The start and
trip signals from the different protection stages are combined with the output
contacts by encircling the desired intersection point. Each intersection point is
marked with a switch number, and the corresponding weighting factor of the switch
is shown on the bottom line of the matrix. The switchgroup checksum is obtained by
horizontally adding the weighting factors of all the selected switches of the
switchgroup.
38
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
PO1 PO2 SO1 SO2 Not in use Not in use Not in use Not in use
Checksum
(factory setting)
SGR2 1 2 3 4 5 6 7 8 å SGR2=
tb>
(3)
SGR4 1 2 3 4 5 6 7 8 å SGR4=
to>
(3)
SGR5 Io>>/
Uo>> 1 2 3 4 5 6 7 8 å SGR5=
(12)
SGR6 1 2 3 4 5 6 7 8 å SGR6=
to>>
(3)
A0501431
39
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
40
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
41
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
In addition, in case of an alarm from a protection stage, a text message will appear
on the LCD.
The messages on the LCD have a certain priority order. If different types of
indications are activated simultaneously, the message with the highest priority will
appear on the LCD.
The priority order of the messages:
1. CBFP
2. TRIP
3. START
5.1.7.1. Function
The REJ 527 features an integrated disturbance recorder for recording monitored
quantities. The recorder continuously captures the curve forms of the current and
voltage as well as the status of both the internal signals and the external binary input
signal and stores these in the memory.
Triggering of the recorder will generate an event code. After the recorder has been
triggered, it will continue to record data for a pre-defined post-triggering time. An
asterisk will be shown on the LCD on completion of the recording. The status of the
recording can also be viewed using a SPA parameter.
As soon as the recorder has been triggered and the recording has finished, the
recording can be uploaded and analyzed by means of a PC provided with a special
program.
42
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
The recording length varies according to the selected sampling frequency. The RMS
curve is recorded by selecting the sampling frequency to be the same as the nominal
frequency of the relay. The sampling frequency is selected with parameter M15; see
the table below for details.
Recording length:
Cycles
[ s ] = -----------------------------------------------------------------
Nominal frequency [ Hz ]
Changing the setting values of parameters M15 is allowed only when the recorder
has not been triggered.
The post-triggering recording length defines the time during which the recorder
continues to store data after it has been triggered. The length can be changed with
parameter V240. If the post-triggering recording length has been defined to be the
same as the total recording length, no data stored prior to the triggering will be
retained in the memory. By the time the post-triggering recording finishes, a
complete recording will have been created.
Triggering of the recorder immediately after it has been cleared or the auxiliary
voltage connected may result in a shortened total recording length. Disconnection of
the auxiliary voltage after the recorder has been triggered but before the recording
has finished, on the other hand, may result in a shortened post-triggering recording
length. This, however, will not affect the total recording length.
At a power reset, triggered recorder data will be retained in the memory provided
that it has been defined non-volatile.
43
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
Writing the value 1 to parameter M2 will clear the recorder memory, restart the
storing of new data and enable the triggering of the recorder. Recorder data can be
cleared by performing a master reset. Writing the value 2 to parameter V246 will
restart the unloading process by setting the time stamp and the first data ready to be
read.
5.1.7.4. Triggering
The user can select the start or trip signal from any protection stage and/or the
external binary input signal to trigger the disturbance recorder, either on the rising
or falling edge of the signal(s). Triggering on the rising edge means that the
post-triggering recording sequence will start when the signal is activated.
Correspondingly, triggering on the falling edge means that the post-triggering
recording sequence will start when the active signal is reset. The trigger signal(s)
and the edge are selected with parameters V241...V244; see tables 5.1.9.4-5 and
5.1.9.4-6. The recorder can also be triggered manually using parameter M1.
Triggering of the disturbance recorder is only possible if the recorder has not already
been triggered.
44
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
The REJ 527 will start to collect data from all the stages when a protection function
starts. When each stage has dropped off, the collected data and the time stamp will
be stored in the first event register and the four previously stored events will move
one step forward. When a sixth event is stored, the oldest event will be cleared.
45
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
- ABB -
A0501299
Relay data, such as events, setting values and all input data and memorized values
can be read via the optical PC-interface.
When setting values are altered via the optical PC-interface, the relay will check that
the entered parameter values are within the permitted setting range. If an entered
value is too high or too low, the setting value will remain unchanged.
The REJ 525 has an internal counter which can be accessed via
“COMMUNICATION” under “CONFIGURATION” in the HMI menu. The
counter value is set to 0 when the relay receives a valid message.
46
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
IEC 60870-5-103 star coupler RER 125 is required. The RER 125 is used to set the
line-idle state “light off” to the relay and “light on” to the master. However, the RER
125 is not required if the master is compatible with the line-idle state “light off”.
Master
system
light on
RER 125
IEC_103 star-coupler
REJ 521
light off
ABB
Order
Article
Serial
No: REJ521B 416BAA
No: 1MRS091416
No: 123456
Uaux = 110-240 Vac
Uaux = 48-220 Vdc In = 1/5 A (Io)
fn = 50/60 Hz RER 103
A0501300
47
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
identification
Information
Event code
Standard description of
Function
Relative
Event reason the information number
number
(IEC 60870-5-103)
Type
type
time
GI
I0> Start E5/ 160 67 start/pick-up N X E5 2
Activated/Reset E6
identification
Rated value
Information
Standard description of
Normalize
Function
(IEC 60870-5-103)
Type
type
Voltage U0 2.40 Un
Standard description of
Function
Relative
(IEC 80870-5-103)
Type
time
type
GI
48
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
identification
Information
Event code
Standard description of
Function
Relative
Event reason the information number
number
(IEC 80870-5-103)
Type
time
type
GI
I0> Trip E7/ 163 1) 92 - - E5 2
Activated/Reset E8 (160) (trip IN>)
identification
Rated value
Information
Standard description of
Normalize
Function
(IEC 60870-5-103)
Type
type
Current I0 2.40 In
Current Iϕ 2.40 In
49
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
identification
Information
Event code
Standard description of
Function
Relative
Event reason the information number
number
(IEC 80870-5-103)
Type
type
time
GI
U0b> Start E1/ 170 84 - X E1 2
Activated/Reset E2
Information
Standard description of
Normalize
Function
(IEC 60870-5-103)
Type
type
Current I0 2.40 In
Current Iϕ 2.40 In
50
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
51
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
Events E50 and E51 are always included in the event reporting.
52
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
• S = setting values
• V = recorded data/parameter
• M = disturbance recorder parameter
• O = output data
Settings
Table 5.1.9.4-1 Settings
Actual Group 1 Group 2
Variable Setting range
settings (R) (R, W, P) (R, W, P)
Set start value of stage I0> S1 S41 S81 1.0...100% x In
Set start value of stage U0> S2 1) S42 S82 2.0...80.0% x Un
Operate time of stage I0>/U0> S3 1) S43 S83 0.10...300 s
Time multiplier k of stage I0> S4 1) S44 S84 0.05...1.00 2)
Set start value of stage I0>> S5 1) S45 S85 5.0...400% x In
Set start value of stage U0>> S6 1) S46 S86 2.0...80.0% x Un
Operate time of stage I0>>/U0>> S7 S47 S87 0.10...300 s
Set start value of stage U0b> S8 S48 S88 2.0...80.0% x Un
Operate time of stage U0b> S9 S49 S89 0.10...300 s
Additional angle (ϕa) of stage I0>/ S10 1) S50 S90 0...90°
I0>> with the basic angle
Basic angle (ϕb) of stage I0>/I0>> S11 1) S51 S91 -90...0°
Angle correction (ϕc) of stage I0>/ S12 1) S52 S92 2...7°
I0>> with the Iϕ characteristic
Checksum, SGF1 S13 S53 S93 0...31
Checksum, SGF2 S14 S54 S94 0...255
Checksum, SGF3 S15 S55 S95 0...255
Checksum, SGF4 S16 S56 S96 0...32
Checksum, SGF5 S17 S57 S97 0...4
Checksum, SGB1 S18 S58 S98 0...255
Checksum, SGR1 S19 S59 S99 0...15
Checksum, SGR2 S20 S60 S100 0...15
Checksum, SGR3 S21 S61 S101 0...15
Checksum, SGR4 S22 S62 S102 0...15
Checksum, SGR5 S23 S63 S103 0...15
Checksum, SGR6 S24 S64 S104 0...15
Operate time of CBFP - S121 S121 0.10...1.00 s
Time setting for disabling new trip - S122 S122 0...999 min
indications on the LCD
1) If
the protection stage has been set out of operation, the number indicating the currently used value
will be displaced by “999” when parameters are read via the SPA bus and by dashes on the LCD.
2) Values above 1 equal 1.
53
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
Recorded data
Parameters V1…V3 show the number of starts of the protection stages and
parameter V4 the trip indication code.
The last five recorded values can be read with parameters V11...V99. Event n
denotes the last recorded value, n-1 the next one, and so forth.
54
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
Disturbance recorder
Table 5.1.9.4-4 Parameters for the disturbance recorder
Description Parameter R, W Value/Note
Manual triggering M1 1) W 1
Clear recorder memory M2 W 1
Sampling rate M15 2) R, W 800/960 Hz
400/480 Hz
50/60 Hz
Station identification/unit number M18 R, W 0…9999
Rated frequency M19 R 50 or 60 Hz
Station name M20 R, W Max 16 characters
Digital channel texts M40...46 R
Analogue channel texts M60...61 R
Analogue channel: rated voltage M80 3) R, W Factor 0.00...600, unit (V, kV),
and unit of primary voltage e.g. 20.0,kV)
transformer
Analogue channel: conversion M81 3) R, W Factor 0...65535, unit (A, kA),
factor and unit, I0 e.g. 10.0,kA
Post-triggering recording length V240 R, W 0...100%
Internal trigger signals’ checksum V241 R,W 0...63, see table 5.1.9.4-5
Internal trigger signal’s edge V242 R,W 0...63; 0 = rising, 1 = falling
External trigger signal (BI) V243 R,W 0/1, see table 5.1.9.4-6
External trigger signal’s edge V244 R,W 0/1; 0 = rising, 1 = falling
Triggering state, clearing and V246 R,W R:
restart 0 = recorder not triggered
1 = recorder triggered and
recording stored in the
memory
W:
0 = clear recorder memory
2 = download restart; sets the
first information and the time
stamp for triggering ready to
be read
4 = manual triggering
1)
M1 can be used for broadcast triggering by using the unit address “900”.
2)Parameters can be written when the recorder has not been triggered.
3) The disturbance recorder requires this parameter to be set. The conversion factor is the
transformation ratio multiplied by the rated current of the relay. If this parameter has been given the
default value 0, dashes will be shown on the LCD instead of the primary values and the recorded
data will be redundant.
55
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
Control parameters
Table 5.1.9.4-7 Control parameters
Description Parameter R, W Value
Unlatching output contacts V101 W 1 = unlatch
Clearing registers and unlatching V102 W 1 = clear and unlatch
output contacts
Rated frequency V133 R,W (P) 50=50 Hz
60=60 Hz
Nominal voltage V134 R,W (P) 100, 110, 115, 120 (V)
Remote control of settings V150 R,W 0 = setting group 1
1 = setting group 2
Non-volatile memory settings V152 R, W 0...31
Event mask for I0>, U0> and U0b> V155 R,W 0...255, see Event codes
Event mask for I0>> and U0>> V156 R,W 0...15, see Event codes
Event mask for output contacts’ V157 R,W 0...255, see Event codes
events
Event mask for the disturbance V158 R,W 0...7, see Event codes
recorder and the HMI password
56
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
57
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
Each protection stage has its internal output signal. These signals can be read (R)
with parameters O1...O6. The state of the output contacts can be read (R) or changed
(W) with parameters O7...O10. When the value of any of parameters O1...O10 is
changed from 0 to 1, it will be recorded in the corresponding parameter O21...O30.
58
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
59
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
The binary input X2.1/17-18 can be used to generate an external blocking signal, to
unlatch the output contacts or for remote control of relay settings. The requested
function is selected in SGB. The binary input can also be used as a trigger signal for
the disturbance recorder; this function is selected with SPA parameter V243.
The auxiliary voltage of the relay is connected to terminals X2.1/1-2. At DC supply,
the positive lead is connected to terminal X2.1/1. For details, refer to the description
of the auxiliary voltage. The permitted auxiliary voltage range of the relay is marked
on the front panel of the relay.
Output contacts PO1 and PO2 are heavy-duty trip contacts capable of controlling
most circuit breakers. The trip signals from the different protection stages are routed
to the output contacts with switches 1 and 2 of SGR1...SGR6. On delivery from the
factory, the trip signals from all the protection stages are routed to both PO1 and
PO2.
Output contacts SO1 and SO2 can be used for signalling on start and tripping of the
relay. The signals to be routed to output contacts SO1 and SO2 are selected with
switches 3 and 4 of SGR1...SGR6. On delivery from the factory, the start signals
from all the protection stages are routed to both SO1 and SO2.
Output contact IRF functions as an output contact for the self-supervision system of
the protection relay. The IRF relay is energized under normal operating conditions
and contact gap X2.1/13-15 is closed. When a fault is detected by the
self-supervision system or the auxiliary voltage is disconnected, the output contact
will drop off and contact X2.1/13-14 will close.
The following picture presents a rear view of the REJ 527, showing three connecting
sockets: one for measuring transformers, one for power supply and one for serial
communication.
60
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
A0501432
61
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
62
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
63
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
Table 5.2.3-6 Signal outputs (SO1, SO2) and self-supervision (IRF) output
Rated voltage 250 V AC/DC
Continuous carry 5A
Make and carry for 3.0 s 8A
Make and carry for 0.5 s 10 A
Breaking capacity when the control circuit time-constant L/R 1 A/0.25 A/0.15 A
< 40 ms, at 48/110/220 V DC
Minimum contact load 100 mA at 24 V AC/DC
64
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
65
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
Auxiliary voltage
The REJ 527 requires a secured auxiliary voltage supply to operate. The internal
power supply of the relay forms the voltages required by the relay electronics. The
power supply is a galvanically isolated (flyback-type) DC/DC converter. When the
auxiliary voltage is connected, the READY indicator LED on the front panel will be
on. For detailed information on power supply, refer to table 5.2.3-2.
The primary side of the power supply is protected with a fuse located on the PCB of
the relay. The fuse size is 3.15 A (slow).
66
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
6. Ordering information
Order number (I0 inputs 0.2 A/1 A) REJ527B 411BAA
(Article nr:1MRS091411-BAA)
Order number (I0 inputs 1 A/5 A) REJ527B 418BAA
(Article nr:1MRS091418-BAA)
Protective cover for rear connectors 1MRS060132
Flush mounting kit 1MRS050209
Semi-flush mounting kit 1MRS050253
Wall mounting kit 1MRS050240
Side-by-side mounting kit 1MRS050241
19” Rack mounting kit 1MRS050257
Optic bus connection module 1MRS090701 (RER 103)
Opto-cable 1MKC950001-2
67
68
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
7. Abbreviations
ϕa Additional angle
ϕb Basic angle
ϕc Angle correction factor
BI Binary input
CBFP Circuit-breaker failure protection
CPU Central processing unit
CT Current transformer
IDMT Inverse definite minimum time characteristic
IEC_103 Standard IEC 60870-5-103
IRF Internal relay fault
I 0> Low-set earth-fault current stage
I0>> High-set earth-fault current stage
LCD Liquid Crystal Display
LED Light-emitting diode
LSG
LON /SPA Gateway, SPA-ZC 102
HMI Human-Machine Interface
PCB Printed Circuit Board
PO1, PO2 Power outputs
SGB Switchgroup for binary input
SGF Switchgroups for functions
SGR Switchgroups for output contacts
SO1, SO2 Signal outputs
U0b> Zero-sequence voltage stage
U0> Low-set zero-sequence voltage stage
U0>> High-set zero-sequence voltage stage
VT Voltage transformer
69
70
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
8. Check lists
Table 8.-1 Setting group 1
Group 1 Default Customer’s
Variable Setting range
(R, W, P) setting setting
Set start value of stage I0> S41 1.0...100% x In 1.0% x In
Set start value of stage U0> S42 2.0...80.0% x Un 2.0% x Un
Operate time of stage I0>/U0> S43 0.10...300 s 0.10 s
Time multiplier k of stage I0> S44 0.05...1.00 0.05
Set start value of stage I0>> S45 5.0...400% x In 5.0% x In
Set start value of stage U0>> S46 2.0...80.0% x Un 2.0% x Un
Operate time of stage I0>>/ S47 0.10...300 s 0.10 s
U0>>
Set start value of stage U0b> S48 2.0...80.0% x Un 2.0% x Un
Operate time of stage U0b> S49 0.10...300 s 0.10 s
Additional angle (ϕa) of stage S50 0...90° 0°
I0>/I0>> with the basic angle
Basic angle (ϕb) of stage I0>/ S51 -90...0° -90°
I0>>
Angle correction (ϕc) of stage S52 2...7° 2°
I0>/ I0>> with the Iϕ
characteristic
Checksum, SGF1 S53 0...31 0
Checksum, SGF2 S54 0...255 0
Checksum, SGF3 S55 0...255 0
Checksum, SGF4 S56 0...32 0
Checksum, SGF5 S57 0...4 0
Checksum, SGB1 S58 0...255 0
Checksum, SGR1 S59 0...15 12
Checksum, SGR2 S60 0...15 3
Checksum, SGR3 S61 0...15 12
Checksum, SGR4 S62 0...15 3
Checksum, SGR5 S63 0...15 12
Checksum, SGR6 S64 0...15 3
71
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
72
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
73
74
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
9. Service
When the protection relay is used under the conditions specified in Section 5.2.3.
Technical data, it is practically maintenance-free. The protection relay electronics
include no parts or components subject to abnormal physical or electrical wear under
normal operating conditions.
If the relay fails in operation or if the operating values considerably differ from those
mentioned in the protection relay specifications, the relay should be overhauled. All
repairs are to be taken by the manufacturer. Please contact the manufacturer or its
nearest representative for further information about checking, overhaul and
recalibration of the relay.
75
76
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
10. Index
A
Application ............................................................................................... 11
Auxiliary voltage .......................................................................... 61, 63, 66
B
Basic angle .................................................................. 17, 33, 36, 38, 41, 53
Binary input ........................................................................................ 62, 64
Binary input test ....................................................................................... 42
Block diagram .......................................................................................... 17
C
CBFP ........................................................................................................ 14
Check lists ................................................................................................ 71
Checksum calculation ............................................................................... 33
Communication ports ............................................................................... 45
Communication protocol .......................................................................... 46
Comtrade .................................................................................................. 44
Configuration ............................................................................................ 16
Connection diagram .................................................................................. 12
Control parameters ............................................................................. 56, 73
Cos(j) characteristics .............................................................. 17, 19, 36, 38
Counter ..................................................................................................... 46
D
Data communication ................................................................................. 66
Design description .................................................................................... 59
Dimensions ............................................................................................... 63
Directional earth-fault current .................................................................. 17
Directional element .................................................................................. 41
Disturbance recorder .................................................................... 14, 42, 55
Disturbance recorder data ......................................................................... 42
E
Earth-fault current ........................................................................ 17, 19, 20
Electromagnetic compatibility tests ......................................................... 64
Energizing inputs ...................................................................................... 63
Environmental conditions ......................................................................... 11
Environmental tests .................................................................................. 64
Event codes ................................................................................... 44, 51, 52
External parameterization ......................................................................... 59
F
Fault code ........................................................................................... 15, 59
Features ....................................................................................................... 9
Function test ............................................................................................. 42
77
REJ 527 Directional or Non-Directional 1MRS750616-MUM
Earth-Fault Relay
H
HMI .................................................................................................... 14, 32
I
IEC 60255 standard .................................................................................. 23
IEC 60870-5-103 ...................................................................................... 46
Indication messages ............................................................................ 41, 59
Input/output connections .......................................................................... 59
Input/output signals .................................................................................. 58
Inputs .................................................................................................. 14, 58
Intermittent earth-fault ....................................................................... 22, 37
Internal relay fault ........................................................................ 15, 59, 62
L
Latching feature ........................................................................................ 34
LCD .................................................................................................... 14, 59
LED .............................................................................................. 15, 41, 59
LED test ................................................................................................... 42
Local parameterization ............................................................................. 59
LON bus ................................................................................................... 45
M
Master reset .............................................................................................. 44
Measurements ........................................................................................... 15
Measuring range ....................................................................................... 63
N
New trip indication ................................................................................... 39
Non-directional earth-fault current ........................................................... 17
Non-volatile memory ......................................................................... 15, 39
O
Operation direction ............................................................................. 20, 40
Ordering information ................................................................................ 67
Output signals ........................................................................................... 58
P
Parameterization ....................................................................................... 59
Parameters for the disturbance recorder ............................................. 55, 73
Password ............................................................................................ 14, 52
Power outputs (PO1, PO2) ........................................................... 14, 62, 64
Power supply ............................................................................................ 63
Product functions ..................................................................................... 13
78
1MRS750616-MUM Directional or Non-Directional REJ 527
Earth-Fault Relay
R
RD-type characteristic .............................................................................. 25
Recorded data ..................................................................................... 44, 54
Requirements ............................................................................................ 11
RI-type characteristic ................................................................................ 24
S
Self-supervision .................................................................................. 15, 59
Serial communication ......................................................................... 45, 62
Setting groups ............................................................................... 32, 71, 72
Settings ............................................................................................... 32, 53
SGB1 ........................................................................................................ 38
SGF1...SGF5 ............................................................................................ 34
SGR1...SGR6 ...................................................................................... 38, 60
Signal diagram .......................................................................................... 16
Signal outputs (SO1, SO2) ........................................................... 14, 62, 64
Sin(j) characteristics ..................................................................... 17, 36, 38
SPA bus communication protocol ............................................................ 45
Switchgroups ............................................................................................ 33
T
Technical data ........................................................................................... 63
Technical data on protection functions ..................................................... 40
Time/current characteristics ..................................................................... 23
W
Weighting factor ....................................................................................... 33
Z
Zero-sequence voltage ........................................................................ 17, 21
79
1MRS750616-MUM EN 11.2005
ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 Vaasa
FINLAND
Tel. +358 10 22 11
Fax. +358 10 224 1094
www.abb.com/substationautomation