Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

PDU

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

MINI-LINK BAS 6-6

6.3 PDU
The Power Distribution Unit is an optional unit required if “high
Ohmic” -48V distribution is not available.
The PDU branches one incoming -48V distribution cable into 5 or 10
outgoing cables and converts a possibly “low Ohmic” electrical
interface to a “High Ohmic” interface.
There are two types of PDU:
• with 5 outputs (Figure 6-3) and;
• with 10 outputs (Figure 6-4).
Every single output provide 5A normally but each output is protected
by a 10AMAX automatic circuit breaker.

Product Power Current for each


PDU Type
Number consumption Output Line

BMG 663 011/1 5 output 1200 W 5A


BMG 663 011/2 10 output 2400 W 5A

164 (140) mm

50 mm

535 (485) mm

Figure 6-3 Dimensions and mechanical structure.

164 (140) mm

75 mm

535 (485) mm

Figure 6-4 Dimensions and mechanical structure.

Product Catalogue EN/LZB 111 0616 R1


6-7 MINI-LINK BAS

PDU is normally used in redundant version, this to ensure the


completely redundancy of the power supply to the subrack located
cabinet.
The following table and figures supplies the different accessories
associated to the PDUs.

Product Number Order Object

BMG 663 011/1 PDU, 5 Fuses


BMG 663 011/2 PDU, 10 Fuses
NTM 501 09/1 Mounting kit, 5 fuses, BYB 311
NTM 501 10/1 Mounting kit, 5 fuses, BYB 501 metric hole pattern
NTM 501 16/1 Mounting kit, 5 fuses, (BYB 501) 19" st. height
mounting pitch
NTM 501 17/1 PDU Mounting kit, 5 fuses, 23"
NTM 501 11/1 Mounting kit, 10 fuses, BYB 311
NTM 501 12/1 Mounting kit, 10 fuses, BYB 501 metric hole pattern

50 mm
50 mm

for BYB 501 for BYB 311

Figure 6-5 Mounting Kit for PDU with 5 fuses.

75 mm
75 mm

for BYB 501 for BYB 311

Figure 6-6 Mounting Kit for PDU with 10 fuses.

EN/LZB 111 0616 R1 Product Catalogue