Digsilent Powerfactory: Technical Reference Documentation
Digsilent Powerfactory: Technical Reference Documentation
MV Load
ElmLodmv, TypDistrf
DIgSILENT GmbH
Heinrich-Hertz-Str. 9
72810 - Gomaringen
Germany
http://www.digsilent.de
info@digsilent.de
Version: 2016
Edition: 1
Copyright © 2016, DIgSILENT GmbH. Copyright of this document belongs to DIgSILENT GmbH.
No part of this document may be reproduced, copied, or transmitted in any form, by any means
electronic or mechanical, without the prior written permission of DIgSILENT GmbH.
Contents
1 General Description 4
2 Load-Flow Analysis 4
2.2.1 3PH-D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2.3 3PH-’YN’ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3 Short-Circuit 14
3.1 Complete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4 RMS Simulation 17
4.2.3 3PH-D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.2.5 3PH-’YN’ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5 EMT Simulation 22
6 Harmonics 22
List of Figures 25
1 General Description
The Medium-Voltage Load represents an aggregation of general loads and static generation.
Optionally, they can be connected through a MV-LV transformer. In this case, the specification
and measurement of electric quantities is done on the MV side of the transformer.
Representations of the MV load model (with and without distribution transformer) are provided
in Figure 1.1.
Note: The MV load element in PowerFactory may be used in conjunction with the Distribution
Transformer Type. The load element contains all of the operational data associated with
the particular load being modelled, and the type contains the non-specific data required
for the modelling of that particular class of power system equipment, in addition with the
MV-LV transformer. The terms ’element’ and ’type’ used throughout this document refer to
these PowerFactory objects.
2 Load-Flow Analysis
The Load Flow tab available in the MV load element’s dialogue allows the user to specify
whether the load is balanced or unbalanced. Additionally, on the Load Flow tab the user can
specify the input parameters for the load by using the Input Mode drop-down menu. Based on
the load data available to the user, the appropriate combination of parameters can be selected
from the following:
• P,cosphi: Enter active power and power factor for the load and for the generation parts
• S,cosphi: Enter apparent power and power factor for the load and for the generation parts
• E,cosphi: Enter yearly energy consumption, power factor, and consumption profile for the
load part, and active power and power factor for the generation part
For load flow analysis, it suffices to only specify the electrical consumption and generation of
the MV load on the MV side.
Other data characterizing a MV load, such as the number of phases, are defined in the distri-
bution transformer type. If no Type is specified on the Basic Data tab of the MV load element,
a technology configuration is assumed based on the technology of the bus to which the load is
connected.
Figure 2.1 shows the load model used for balanced load flow analysis.
All loads specified as 2-phase or 1-phase loads are only considered in unbalanced load flow
calculations. They are ignored when a balanced load flow is performed.
The total active power of the MV load is the substraction of the generation active power (Pgen )
from the consumption active power (Pload ):
With
Where
With
( √
slini · 1 − coslini2 · scale0 · zonescale · scLoadF ac, if load is inductive
Qload = √
−slini · 1 − coslini2 · scale0 · zonescale · scLoadF ac, if load is capacitive.
( p
sgini · 1 − cosgini2 · gscale · scGenF ac, if generation is inductive
Qgen = p
2
−sgini · 1 − cosgini · gscale · scGenF ac, if generation is capacitive.
Where
Depending on the tap position of the transformer defined in the load flow, the actual voltage on
the LV side is calculated as follows:
z trf = r1 + x1
imv
imv0 =
dutap
1+ · (nntap − nnenutral)
100
dutap
umv0 = umv · 1 + · (nntap − nneutral)
100
z trf
P fe
· umv0 − imv0 ·
iP f e = 1000 · Snom 2
0, if |i
P f e | > |imv 0 |
ilv0 = imv0 − iP f e
z trf
ulv = tratio · umv0 − · (imv0 + ilv0 )
2
Where
n z trf o
Gmload = < i∗P f e · umv0 − imv0 · · 1000 in kW
2
z trf Gmload
Losses = · |imv0 |2 − |ilv0 |2 + in MW/Mvar
2 1000
The total per-phase active power of the MV load is the substraction of the generation active
power per phase from the consumption active power per phase:
Pr = Ploadr − Pgenr
Ps = Ploads − Pgens
Pt = Ploadt − Pgent
With
Where
• slinir, slinis, and slinit are the specified load apparent power per phase
• coslinir, coslinis, and coslinit are the specified load power factor per phase
• scale0 is the load scaling factor
• zonescale is the zone scaling factor, if available
• scLoadF ac is the load scaling factor of the load flow analysis command
• sginir, sginis, and sginit are the specified generation apparent power per phase
• coslinir, coslinis, and coslinit are the specified generation power factor per phase
• gscale is the generation scaling factor
• scGenF ac is the generation scaling factor of the load flow analysis command
The corresponding total per-phase reactive power values are calculated as follows:
Qr = Qloadr − Qgenr
Qs = Qloads − Qgens
Qt = Qloadt − Qgent
With
( √
slinir · 1 − coslinir2 · scale0 · zonescale · scLoadF ac, if load is inductive
Qloadr = √
−slinir · 1 − coslinir2 · scale0 · zonescale · scLoadF ac, if load is capacitive.
( √
slinis · 1 − coslinis2 · scale0 · zonescale · scLoadF ac, if load is inductive
Qloads = √
2
−slinis · 1 − coslinis · scale0 · zonescale · scLoadF ac, if load is capacitive.
( √
slinit · 1 − coslinit2 · scale0 · zonescale · scLoadF ac, if load is inductive
Qloadt = √
2
−slinit · 1 − coslinit · scale0 · zonescale · scLoadF ac, if load is capacitive.
( p
sginir · 1 − cosginir2 · gscale · scGenF ac, if generation is inductive
Qgenr = p
2
−sginir · 1 − cosginir · gscale · scGenF ac, if generation is capacitive.
( p
sginis · 1 − cosginis2 · gscale · scGenF ac, if generation is inductive
Qgens = p
2
−sginis · 1 − cosginis · gscale · scGenF ac, if generation is capacitive.
( p
sginit · 1 − cosginit2 · gscale · scGenF ac, if generation is inductive
Qgent = p
−sginit · 1 − cosginit2 · gscale · scGenF ac, if generation is capacitive.
Where
• slinir, slinis, and slinit are the specified load apparent power values per phase
• coslinir, coslinis, and coslinit are the specified load power factors per phase
• scale0 is the load scaling factor
• coslinir, coslinis, and coslinit are the specified generation power factors per phase
• gscale is the generation scaling factor
• scGenF ac is the generation scaling factor of the load flow analysis command
2.2.1 3PH-D
Figure 2.2: Load model used for unbalanced 3-phase Delta connection
ur = ua − ub
us = ub − uc
ut = uc − ua
Figure 2.3: Load model used for unbalanced 3-phase PH-E connection
ur = ua
us = ub
ut = uc
If the load has a distribution transformer type assigned, then the voltages are:
ur = ua − u0
us = ub − u0
ut = uc − u0
2.2.3 3PH-’YN’
ur = ua − un
us = ub − un
ut = uc − un
If the load has a distribution transformer type assigned, then the voltages are:
ur = ua − un − u0
ub − un − u03PH ‘YN’ load model diagram
us =Technology
Figure 7: 3-phase,
ut = uc − un − u0
The 1PH PH-PH load model can be used for representing single-phase loads connected be-
tween two phases (see Figure 2.7).
The 1PH PH-N load model can be used for a load connected between one phase and the neutral
phase (see Figure 2.8).
DC-loads are always “single-phase”, as shown in Figure 10. For load flow analysis, the
the active power flow P. Inductive effects are only considered in transient simulations.
2 Load-Flow Analysis
Depending on the tap position of the transformer defined in the load flow, the actual voltage on
the LV side is calculated as follows:
z trf = r1 + x1
ir(mv)
ir(mv)0 =
dutap
1+ · (nntap − nnenutral)
100
is(mv)
is(mv)0 =
dutap
1+ · (nntap − nnenutral)
100
it(mv)
it(mv)0 =
dutap
1+ · (nntap − nnenutral)
100
dutap
ur(mv)0 = ur(mv) · 1 + · (nntap − nneutral)
100
dutap
us(mv)0 = us(mv) · 1 + · (nntap − nneutral)
100
dutap
ut(mv)0 = ut(mv) · 1 + · (nntap − nneutral)
100
i00 ir(mv)0
i10 = A−1 is(mv)0
i20 it(mv)0
u00 ur(mv)0
u10 = A−1 us(mv)0
u20 ut(mv)0
z trf
Pf e
· u10 − i10 ·
i1(P f e) = 1000 · Snom 2
0, if |i
1(P f e) | > |i10 |
z trf
Pf e
· u20 − i20 ·
i2(P f e) = 1000 · Snom 2
0, if |i
2(P f e) | > |i20 |
Where
nh z trf z trf i o
Gmload = < i∗1(P f e) · u1(mv)0 − i1(mv)0 · + i∗2(P f e) · u2(mv)0 − i2(mv)0 · · 1000 in kW
2 2
z trf h i Gmload
Losses = · |i1(mv)0 |2 − |i1(lv)0 |2 + |i2(mv)0 |2 − |i2(lv)0 |2 + in MW/Mvar
2 1000
3 Short-Circuit
3.1 Complete
The MV Load model for the ”complete” short-circuit calculation is the following:
Where
00 U 00 − Uldf
Ishc = U 00 · Iload + Iload − Igen + 00
Zshc
0 U 0 − Uldf
Ishc = U 0 · Iload + Iload − Igen + 0
Zshc
For the X/R ratio (X/R ratio break) calculation only the short-circuit contribution is considered,
the load impedance and load current are ignored.
00 1
Zshc = 00 · S 00
Sk,l l,ini · cosphil,ini · scale · zonescale + Sk,g · Sg,ini · cosphig,ini · zonescale + Skssf ix
00
00 Zshc
={Zshc }= p
1 + (R/X)2
00 00
<{Zshc } = R/X · ={Zshc }
Where
00
• Zshc is the subtransient short-circuit contribution
00
• Sk,l is the subtransient short-circuit level for load in MVA/MW
00
• Sk,g is the subtransient short-circuit level for generation in MVA/MW
• Skssf ix is the fixed subtransient short-circuit level in MVA
0 1
Zshc = 0 ·S 0
Sk,l l,ini · cosphil,ini · scale · zonescale + Sk,g · Sg,ini · cosphig,ini · zonescale + Sksf ix
0
0 R Zshc
={Zshc }= ·p
X 1 + (R/X)2
q
0 0 )2 − (<{Z 0 })2
<{Zshc } = (Zshc shc
Where
0
• Zshc is the transient short-circuit contribution
0
• Sk,l is the transient short-circuit level for load in MVA/MW
0
• Sk,g is the transient short-circuit level for generation in MVA/MW
• Sksf ix is the fixed transient short-circuit level in MVA
• Sl,ini is the load apparent power operating point
• cosphil,ini is the load power factor
• Sg,ini is the generation apparent power operating point
• cosphig,ini is the generation power factor
• scale is the scaling factor
• zonescale is the zone scaling factor
• R/X is the R to X” ratio
2
Ildf Sgini
Yload = −
Uldf (Uldf )2
Iload = 0
and
Sgini
Igen = when Sgini > 0
Uldf
Yload = 0
4 RMS Simulation
ildf
y load =
uldf
If generation is available, the load part is modelled as a constant admittance, while the gener-
ation part is modelled as a current source, with a magnitude of current injection (igen ) and the
angle with respect to the load-flow voltage (phiuigen ).
ildf
y load =
uldf
igen = −ildf + y load · uldf
If no generation is available, the load is modelled as a constant admittance. The initialization for
this model is thus:
ir,ldf
y r,load =
ur,ldf
is,ldf
y s,load =
us,ldf
it,ldf
y t,load =
ut,ldf
Initialization:
ir,ldf sr,gen
y r,load = − 2
ur,ldf ur,ldf
is,ldf ss,gen
y s,load = − 2
us,ldf us,ldf
it,ldf st,gen
y t,load = − 2
ut,ldf ut,ldf
ir,gen = −ir,ldf + y r,load · ur,ldf
is,gen = −is,ldf + y s,load · us,ldf
it,gen = −it,ldf + y t,load · ut,ldf
Equations:
ir,rms = (y r,load · ur,rms ) − |ir,gen | · cos(angle(ur,rms ) − phiuir,gen ) + sin(angle(ur,rms ) − phiuir,gen )
is,rms = (y s,load · us,rms ) − |is,gen | · cos(angle(us,rms ) − phiuis,gen ) + sin(angle(us,rms ) − phiuis,gen )
it,rms = (y t,load · ut,rms ) − |it,gen | · cos(angle(ut,rms ) − phiuit,gen ) + sin(angle(ut,rms ) − phiuit,gen )
4.2.3 3PH-D
Figure 4.3: Load model used for unbalanced 3-phase Delta connection
ur = ua − ub
us = ub − uc
ut = uc − ua
ir = ia − ib
is = ib − ic
it = ic − ia
Figure 4.4: Load model used for unbalanced 3-phase PH-E connection
ur = ua
us = ub
ut = uc
ir = ia
is = ib
it = ic
If the load has a distribution transformer type assigned, then the voltages are:
ur = ua − u0
us = ub − u0
ut = uc − u0
ir = ia − i0
is = ib − i0
it = ic − i0
4.2.5 3PH-’YN’
ur = ua − un
us = ub − un
ut = uc − un
ir = ia
is = ib
it = ic
If the load has a distribution transformer type assigned, then the voltages are:
ur = ua − un − u0
us = ub − un − u0
ut = uc − un − u0
ir = ia − i0
is = ib − i0
it = ic − i0
5 EMT Simulation
6 Harmonics
The load admittance is calculated from the load flow analysis results:
ildf sgen
y load = − 2
uldf uldf
If the imaginary part of y load is negative, the load is modelled as an inductive load:
with:
( )
1
rload = <
y load
( )
1
=
y load
lload =
2πfnom
If the imaginary part of y load is positive, the load is modelled as a capacitive load:
with:
( )
1
rload = <
y load
n o
= y load
cload =
2πfnom
with:
n o
= y load
cload =
(1 − ppgrd) · 2πfnom
1
z rea =
={y load } · ppgrd
<{y load } −
1 − ppgrd
rload = <{z rea }
={z rea }
lload =
2pifnom
Initialization:
i1 = ildf − uldf · y 1
Equation:
i = y 1 · u + i1
List of Figures