L-PRO 4000: Transmission Line Protection Relay
L-PRO 4000: Transmission Line Protection Relay
L-PRO 4000: Transmission Line Protection Relay
User Manual
Version 2.3 Rev 0
Preface
Information in this document is subject to change without notice.
© 2013 ERLPhase Power Technologies Ltd. All rights reserved.
Reproduction in any manner whatsoever without the written permission of
ERLPhase Power Technologies Ltd. is strictly forbidden.
This manual is part of a complete set of product documentation that includes
detailed drawings and operation. Users should evaluate the information in the
context of the complete set of product documentation and their particular
applications. ERLPhase assumes no liability for any incidental, indirect or
consequential damages arising from the use of this documentation.
While all information presented is believed to be reliable and in accordance
with accepted engineering practices, ERLPhase makes no warranties as to the
completeness of the information.
All trademarks used in association with B-PRO, F-PRO, L-PRO, ProLogic,
T-PRO, TESLA, TESLA Control Panel, Relay Control Panel, RecordGraph
and RecordBase are trademarks of ERLPhase Power Technologies Ltd.
Windows® is a registered trademark of the Microsoft Corporation.
Procomm® is a registered trademark of Symantec.
HyperTerminal® is a registered trademark of Hilgraeve.
Modbus® is a registered trademark of Modicon.
Contact Information
ERLPhase Power Technologies Ltd.
Website: www.erlphase.com
Email: info@erlphase.com
Technical Support
Email: support@erlphase.com
Tel: 1-204-477-0591
Example Describes
Text boxes similar to this one Relate important notes and information.
Indicates a warning.
TT - Transfer Trip
TUI - Terminal User Interface
UI - User Interface
VI - Virtual Input
WI - Weak Infeed
L-PRO Setting
Compatible Offliner Settings ICD File Version
Firmware Version
Operating System
The following software must be installed and functional prior to installing the
applications:
• Microsoft Windows XP Professional Service Pack 3 or
• Microsoft Windows 7 Professional Service Pack 1 32-bit or 64-bit
Relay Control Panel requires Windows XP SP3 (it will not work on earlier ver-
sions of Windows).
Software Installation
The CD-ROM contains software and the User Manual for the L-PRO Trans-
mission Line Protection Relay.
Software is installed directly from the CD-ROM to a Windows PC. Alterna-
tively, create installation diskettes to install software on computers without a
CD-ROM drive.
The CD-ROM contains the following:
• L-PRO Offliner Settings: Offliner settings program for the relay
• L-PRO Firmware: Firmware and installation instructions
• L-PRO User Manual: L-PRO manual in PDF format
• L-PRO Function Logic Diagram: diagram in PDF format
• Relay Control Panel: software
• Relay Control Panel User Manual: manual in PDF format
• USB Driver
To install the software on the computer, click the desired item on the screen.
The installation program launches automatically. Installation may take a few
minutes to start.
To view the L-PRO User Manual the user must have Adobe Acrobat on the
computer. If a copy is needed, download a copy at www.adobe.com.
Anti-virus/Anti-spyware Software
If an anti-virus/anti-spyware software on your local system identifies any of
the ERLPhase applications as a “potential threat”, it will be necessary to con-
figure your anti-virus/anti-software to classify it as “safe” for its proper oper-
ation. Please consult the appropriate anti-virus/anti-spyware software
documentation to determine the relevant procedure.
by programming the output matrix and allowing any internal relay function or
any external input or any GOOSE messaging input to initiate recording.
Bus 2 Bus 1
50 50 Rec.
LS 79-1,3
CT BF
PT
Σ 21P 21N 68 50/67 51/67 50N/
67
51N/
67
46/50
/67
46/51
/67
5050N
/67
Rec.
1 2
IRIG-B FUNCTIONAL
SERVICE REQUIRED
ALARM
TEST MODE
(119) (150)
100BASE-T USB
1 2
IRIG-B FUNCTIONAL
SERVICE REQUIRED
ALARM
TEST MODE
(119) (150)
100BASE-T USB
9 10 11 12 13
121
7 External
Inputs
48 125 250
1
V 48 125 250
2
V 48 125 250
3
V 48 125 250
4
V 48 125 250
5
V 48 125 250
6
V 48 125 250
7
V 48 125 250
8
V 48 125 250
9
V 118 TX 119 RX TX 120 RX 122 123
8 Output NO NC
Contacts RELAY
INOPERATIVE
NO NC
1
NO NC
2
NO
3
NO
4
NO
5
NO
6
NO
7
NO
8
Output
Contacts
NO
9
NO
10
NO
11
NO
12
NO
13
NO
14
Unused
8
200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235
Input
1A 5A 50Hz 60Hz
Main AC Line Currents Aux. AC Line Currents AC Current Inputs (Record Only) Aux. AC Volts Unused Main AC Volts Unused
15 I 1A I 1B I 1C I 2A I 2B I 2C I 3A I 3B I 3C I 4A I 4B I 4C VA VB VC N VA VB VC N
300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 Power Supply
±10%
48 to 250 Vdc
100 to 240 Vac
Made in Canada 336 337
14 14 16 17 18
8 9 10 11 12
V V V V V V V V V 121
External 48 125 250 48 125 250 48 125 250 48 125 250 48 125 250 48 125 250 48 125 250 48 125 250 48 125 250
118 TX 119 RX TX 120 RX 122 123
Inputs 1 2 3 4 5 6 7 8 9
7
Modem 100BASE- T FX 100BASE- T FX
100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117
1000BASE- TX LX 1000BASE- TX LX IRIG-B SCADA COM
48 V 48 V 48 V 48 V 48 V
125 V 125 V 125 V 125 V 125 V
V V V V V V NO NO NO NO NC NO NC NO NC NO NC
7 External External
250 V 250 V 48 125 250 48 125 250 250 V 48 125 250 48 125 250 250 V 250 V 48 125 250 48 125 250 Output
Inputs 10 11 12 13 14 15 16 17 18 Inputs 19 20 15 16 17 18 19 20 21 Contacts
400 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435
13 Output
Contacts
NO NC
RELAY
INOPERATIVE
NO NC
1
NO NC
2
NO
3
NO
4
NO
5
NO
6
NO
7
NO
8
Output
Contacts
NO
9 10
NO NO
11
NO
12
NO
13
NO
14
Unused
200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235
Input
1A 5A 50Hz 60Hz
Main AC Line Currents Aux. AC Line Currents AC Current Inputs (Record Only) Aux. AC Volts Unused Main AC Volts Unused
I 1A I 1B I 1C I 2A I 2B I 2C I 3A I 3B I 3C I 4A I 4B I 4C VA VB VC N VA VB VC N
300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 Power Supply
±10%
48 to 250 Vdc
100 to 240 Vac
Made in Canada 336 337
19 14 15 16 17 18 20
AC Current and The relay is provided with terminal blocks for up to 12 ac currents and 6 phase-
Voltage Inputs to-neutral voltages.
Each of the current input circuits has polarity (•) marks.
A complete schematic of current and voltage circuits is shown, for details see
“AC Schematic Drawings” in Appendix I and “DC Schematic Drawings”
in Appendix J.
External Inputs The relay contains 9 (3U) or 20 (4U) programmable external inputs.
Output Relay The relay has 14 (3U) or 21 (4U) programmable relay contacts.
Contacts
Relay If the relay is in self check program or becomes inoperative, then the Relay In-
Inoperative operative Alarm output contact closes and all tripping functions are blocked.
Alarm Output
Case Ground the relay to the station ground using the case-grounding terminal at the
Grounding back of the relay, for details see Figure 1.5: L-PRO Relay Rear View (4U) on
page 1-5.
WARNING!
Laptop PC
In Windows XP or Windows 7
Connect a USB port of the PC to Port 150 (USB front) of the LPRO-4000.
The LPRO-4000 was already powered on.
In the window
“Welcome to the Found New Hardware Wizard”
“Can Windows connect to Windows Update to search for software?”
Check the option “No, not this time”.
In the window
“This wizard helps you install software for:”
“ERLPhase 4000 Series Device”
“What do you want the wizard to do?”
Check the option “Install from a list or specific location (Advanced)”.
In the window
“Please choose your search and installation options”
“Search for the best driver in these locations”
In the window
“Hardware Installation”
“The software you are installing for this hardware”
“ERLPhase 4000 Series Device”
“has not passed Windows Logo testing to verify its compatibility with
Windows XP” or “Windows can’t verify the publisher”
Hit Continue Anyway.
In the window
“Completing the Found New Hardware Wizard”
“The wizard has finished installing the software for”
“ERLPhase 4000 Series Device”
Hit Finish.
To verify the installation was successful, and to which comm port is the ERL-
Phase 4000 Series Device configured, do the following:
In Windows XP
Start > Control Panel->Performance and Maintenance->System >Hard-
ware > Device Manager > Ports
or (if using Control Panel’s Classic View)
Start > Control Panel > System > Hardware >Device Manager >Ports
In Windows 7 ‘small icons’ view, go to
Start>Control Panel>Device Manager>Ports.
Look for the port number associated to this device.
“ERLPhase 4000 Series Device”
Look for a COM#, where “#” can be 1, 2, 3, etc. Leave the default settings
for this port.
It is recommended to restart the PC after the USB driver installation.
The default baud rate for the relay USB Port 150 is 115200, however to double
check it login to the relay display and go to:
Main Menu > System > Relay Comm Setup
TCP/IP
Network Port 119 - RJ-45
Network
Access both the relay’s user interface and DNP3 SCADA services simultane-
ously with the Ethernet TCP/IP LAN link through the network ports Port 119
and Port 120. The rear Port 119 and 120 are either 100BASE-T copper inter-
face with an RJ-45 connector or 100BASE-FX optical interface with an ST
style connector. Each port is factory configurable as a copper or optical inter-
face. The front Port 119 is 100BASE-T copper interface with an RJ-45 connec-
tor.
DNP3 SCADA services can also be accessed over the LAN, for details see
“Communication Port Details” on page 2-15.
Connect to the Ethernet LAN using a Cat 5 cable with an RJ-45 connector or
100BASE-FX 1300 nm, multimode optical fiber with an ST style connector.
By default, the Port 119 is assigned with an IP address of 192.168.100.80 Port
120 is assigned with an IP address of 192.168.101.80. If this address is not suit-
able, it may be modified using the relay’s Maintenance Menu. For details see
“Using HyperTerminal to Access the Relay’s Maintenance Menu” on page 2-
9.
Laptop PC
To create a serial link between the relay and the computer, connect the com-
puter’s serial port and Port 123 on the relay’s rear panel provided the port is
not configured for modem use.
The serial ports are configured as EIR RS-232 Data Communications Equip-
ment (DCE) devices with female DB9 connectors. This allows them to be con-
nected directly to a PC serial port with standard straight-through male-to
female serial cable, for pin-out details see “Communication Port Details” on
page 2-15. Rear Port 122 is for SCADA and Port 123 can be used for direct se-
rial access and external modem.
Ensure the relay port and the PC’s port have the same baud rate and
communications parameter, see “Maintenance Menu Commands”
on page 2-11.
Analog Analog
Port 123 - RJ-11 modem Telephone Telephone
Line Telephone Line
System
Desktop Computer
Using an external modem, access the relay’s user interface through a telephone
link between the relay and the computer.
Connect the serial port on the external modem to the Port 123 on the relay’s
rear panel. Both devices are configured as RS-232 DCE devices with female
connectors, so the cable between the relay and the modem requires a crossover
and a gender change. Alternatively, use the ERLPhase modem port adapter
provided with the relay to make Port 123 appear the same as a PC’s serial port.
A standard modem-to-PC serial cable can then be used to connect the modem
and the relay. For pin-out details see “Communication Port Details” on page 2-
15.
Connect the modem to an analog telephone line or switch using a standard RJ-
11 connector.
Configure the relay’s Port 123 to work with a modem. Log into the relay
through Relay Control Panel, go to Utilities>Communication and select port
123. Set the Baud Rate as high as possible – most modems handle 57,600 bps.
The Initialize setting allows the user to set the control codes sent to the modem
at the start of each connection session. The factory defaults are:
“M0S0=0&B1” for an external modem and “M0S0=0” for an internal modem.
Internal
Analog Analog
Port 118 - RJ-11 modem Telephone Telephone
Line Telephone Line
System
Desktop Computer
Access the relay’s user interface through a telephone link between the relay
and the computer using an optional internal modem. If the modem has been in-
stalled, Port 118 on the rear panel is labelled “INTERNAL MODEM.”
Connect the relay’s Port 118 to an analog telephone line or switch using a stan-
dard RJ-11 connector.
When an internal modem is installed, the relay’s Port 118 is used to interface
to the modem internally. Appropriate Port 118 settings are configured at the
factory when the internal modem is installed. The factory defaults are:
“M0S0=0&B1” for an external modem and “M0S0=0” for an internal modem.
Baud rate Default fixed baud rate 115,200 N81 (no parity, 8 data bits, 1 stop bit).
Data bits 8
Parity None
Stop bits 1
Emulation VT100
Font Use a font that supports line drawing (e.g. Terminal or MS Line Draw).
If the menu appears outlined in odd characters, the font selected is not
supporting line drawing characters.
“What area code (or city code) are you are in now?”
Enter “306”
“If you need to specify a carrier code, what is it?”
Enter “”, i.e. leave blank
“If you dial a number to access an outside line, what is it?”
Enter “”.
“The phone system at this location uses:”
Choose “Tone dialing”.
Hit OK.
First time use of HyperTerminal will show “Phone and Modem Options”.
Hit Cancel.
Maintenance
Menu Commands 1, 4, 5, 6 and 7 are Port 150 access only.
Commands
Modify IP address Modifies the LAN IP addresses, network mask, default gateway
and IEC61850 network port assignment.
Retrieve system diagnos- Automatically packages up the internal status log plus setting
tics and setup information and downloads it in compressed form to
the computer. This file can then be sent to our customer support
to help diagnose a problem.
Restore settings (com- Use these commands to force the system back to default
mands 4, 5 and 6) values, if a problem is suspected due to the unit's settings,
calibration and/or setup parameters.
Force hardware reset Manually initiates a hardware reset. Note that the
communication link is immediately lost and cannot be
reestablished until the unit completes its start-up.
Exit network utilities Exit network utilities menu and return to Maintenance Menu
Commands
The firmware update is used to update the relay’s software with maintenance
or enhancement releases. Please see the L-PRO Firmware Update Procedure
documentation that comes with the firmware update for instructions on how to
update the firmware on the relay.
The baud rate is available on the LCD screen from the top level menu
selecting System then Relay Comm Setup.
Direct Serial For a direct serial connection, both the relay and the computer must be set to
Link the same baud rate.
To change the baud rate of a relay serial port:
1. The user needs to log into the relay as Change (any port) or Service (USB
port only) using RCP.
2. Then choose Utilities>Communication tab.
Modem Link Unlike a direct serial link, the baud rates for a modem link do not have to be
the same on the computer and on the relay. The modems automatically nego-
tiate an optimal baud rate for their communication.
The baud rate set on the relay only affects the rate at which the relay commu-
nicates with the modem. Similarly, the baud rate set in HyperTerminal only af-
fects the rate at which the computer communicates with its modem. Details on
how to set these respective baud rates are described above, except that the user
modifies the Port 123 baud rate on the relay and the properties of the modem
in HyperTerminal.
Protocol To select the desired SCADA protocol go to L-PRO 4000 Offliner SCADA
Selection communications section. Select the protocol and set the corresponding param-
eters.
Communication Port 122’s communication parameters are set in the L-PRO 4000 Offliner
Parameters SCADA communications section Both the baud rate and the parity bit can be
configured. The number of data bits and stop bits are determined automatically
by the selected SCADA protocol. Modbus ASCII uses 7 data bits. Modbus
RTU and DNP Serial use 8 data bits. All protocols use 1 stop bit except in the
case where either Modbus protocol is used with no parity; this uses 2 stop bits,
as defined in the Modbus standard.
Diagnostics Protocol monitor utilities are available to assist in resolving SCADA commu-
nication difficulties such as incompatible baud rate or addressing. The utilities
can be accessed through the Maintenance Menu Commands, see “Maintenance
Menu Commands” on page 2-11
Front Panel 150 USB-B receptacle, High speed USB 2.0 interface
Used for user interface access
Default fixed baud rate 115,200 N81 (no parity, 8 data bits, 1 stop
bit).
Rear Panel 119 Rear panel, RJ-45 receptacle or ST type optical receptacle (fac-
tory configured). 100BASE-T or 100BASE-FX (1300nm, multi-
mode) Ethernet interface. Same subnet as front panel port 119.
Used for user interface access or IEC61850/DNP SCADA access
through Ethernet LAN.
Rear Panel 120 ST type optical receptacle. 100BASE-FX (1300 nm, multimode)
Ethernet interface.
Used for user interface access or IEC61850/DNP SCADA access
through Ethernet LAN
DCD 1
RxD 2
TxD 3
DTR 4
Common 5
DSR 6
RTS 7
CTS 8
No connection 9
Notes:
Relay is DCE, PC is DTE.
Pins 1 and 6 are tied together internal to the relay.
Male DB-9 Cable End for Relay Port Female DB-9 Cable End for Computer Port
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
2 Setup and Communications
Signal Name Direction Modem <-> Relay Pin # on the Modem Adapter
DCD 1
RxD 2
TxD 3
DTR 4
Common 5
DSR 6
RTS 7
CTS 8
No connection 9
Notes:
Relay (with modem adapter) is DTE, modem is DCE.
Pins 1 and 6 are tied together internal to the relay.
TEST MODE — red LED off within 20 seconds after power applied
When the Relay Functional LED comes on, it indicates that the DSP is actively
protecting the system.
When the test mode LED goes off, the relay is capable of recording and com-
municating with the user.
The display, the 16 LED lights and the 6 push buttons, provide selective infor-
mation about the relay.
LED Lights
Relay Functional Indicates when the relay is functional. When the Relay Functional
green LED goes on, the rear Relay Inoperative contact changes to
an open and the protective functions become functional.
IRIG-B Functional Indicates the presence of a valid IRIG-B time signal where the LED
is on.
Service Required Indicates the relay needs service. This LED can be the same state
as the Relay Functional LED or can be of the opposite state
depending on the nature of the problem.
The following items bring up this LED:
• DSP failure - protection difficulties within the relay.
• Communication failure within the relay.
• Internal relay problems.
Test Mode Occurs when the relay output contacts are intentionally blocked.
Possible reasons are:
• Relay initialization on startup
• User interface processor has reset and is being tested.
The user cannot communicate with the relay through the ports until
the front display becomes active and the TEST MODE LED goes
out. Normally, the red Target LED remains off after this start-up
unless the relay had unviewed target messages.
1 Any device 21P trip operation (phase distance - 21P1, 21P2, 21P3,
21P4)
9 ProLogic 1 - 8
10 ProLogic 9 - 16
11 ProLogic 17 - 24
Target LED assignments are the default values but are configurable
by the user through the Offliner settings (output matrix configuration).
Push Buttons
Up, Down, Right, Left, Enter, Escape Used to navigate the front panel screens.
Display The basic menu structure for navigation of the LCD screen is given below:
Main Screen
Enter Password
System (V)
Settings
System Parameters
Record Length
Setting Group 1
Setting Group 2
Setting Group 3
Setting Group 4
Setting Group 5
Setting Group 6
Setting Group 7
Setting Group 8
Metering (V)
Analog (V)
Logic (V)
ProLogic (V)
Records (V)
Swing Recording
Event Recording
Fault Log
Fault List
Event List
Utilities (V)
Setup (V)
Timeouts (V)
Maintenance (V)
Erase (C,S)
Network (V)
Ping (V)
Logout (V)
Where the access levels required to access each are indicated by:
V: view
C: change
S: service
To login into the LCD menu structure, follow these steps:
2012Oct24
12:17
LPRO-4000-101224-01
View
Change - read/write
Service - full access
****
1 2 3 4 5 6 7 8 9 0 - + =
a b c d e f g h i j k l m n o
Sp p q r s t u v w x y z , .
back select view
select view
Please refer to the Relay Control Panel User Manual for details.
4. Run Relay Control Panel.
Go to:
Start > All Programs > ERLPhase > Relay Control Panel > Relay Control
Panel
First time RCP is run.
Hit Add New.
“Add New Relay”
Choose Communication > Direct Serial Link.
Hit Get Information From Relay.
Then RCP will communicate with the LPRO-4000 and retrieve in-
formation to fill required fields.
When this is done, hit Save Relay.
If the window “Relay already exists...” pops up, you may need to re-
name the relay changing the “Relay Name” in the “Relay Definition”
category, before saving.
After first time, in “Select Relay”, choose relay and hit Connect.
In “Relay Password Prompt”
Choose desired access level, enter appropriate password
Note: Default passwords are listed below (remove the quotation
marks)
View Access “view”
Change Access “change”
Service Access “service”
The basic structure of the Relay Control Panel information, including basic
actions available, is given below:
Metering
Analog
Line
External
Logic 1
Logic 2
ProLogic
Outputs
Group Logic
Virtual
Utilities
Unit Identification
Communication
Time
External Input
Configuration
Notice that some options are not available (N/A) depending on the access level.
21P Phase/21N The relay 21P contains 5 zones of phase distance elements; all 5 zones of 21P
Ground can be set to either Mho or Quadrilateral type. Note that only one type can be
used at a time. The 21P can contain a mixture of Mho and Quadrilateral shapes,
Distance
for example the 21P1 and 21P2 can be set to a Mho characteristic and the 21P3,
21P4 and 21P5 could be set to a Quadrilateral characteristic.
The relay 21N contains 5 zones of ground distance elements; all 5 zones of 21N
can be set to either Mho or Quadrilateral type. Note that only one type can be
used at a time. The 21N can contain a mixture of Mho and Quadrilateral
shapes, for example the 21N1 and 21N2 can be set to a Mho characteristic and
the 21N3, 21N4 and 21N5 could be set to a Quadrilateral characteristic.
The Quadrilateral shape is parallel to the positive sequence line angle setting.
The user-defined Mho Characteristic Angle is not selectable when a Quadrilat-
eral characteristic for that particular zone is defined. All other settings are se-
lectable and user-definable.
Zones 3, 4 and 5 reach can be set in either forward direction or reverse direction
or offset as required. All the distance functions are set in secondary ohms. The
available range of impedance settings is based on the nominal current specified
when the relay was ordered. The impedance reach ranges are given in “21P
Phase/21N Ground Distance” on page 4-2.
Zone 5
Zone 3
Zone 2
Line Z1
Characteristic Angle
Zone 1
Line Angle
R
Zone 4
Figure 4.1: Phase and Ground distance protection Mho relay characteristic
The shape of the phase and ground distance relays is adjustable. For the circu-
lar Mho characteristic shape, the characteristic angle is 90 degrees. Determine
this angle by drawing 2 lines from any point on the impedance locus to the di-
ameter of the characteristic. Produce a tomato-shaped characteristic by select-
ing an angle less than 90 degrees or a lens-shaped characteristic with angles
greater than 90 degrees.
Zone 5
Zone 3
Zone 2
Zone 1
Line Z1
Forward
Line Angle
R
Directional Element
Zone 4
Reverse
The shape of the Mho characteristic means that significant extensions are made
to the relay characteristics in the R region of the R-X plane for ground faults.
Restrict the reach in the R region for the phase distance relays where load en-
croachment is an issue. The shaped Mho characteristic provides the best fit for
the application keeping the number of relay settings at a minimum and pro-
vides the benefits associated with the Mho characteristic.
The Mho characteristic used by the relay is developed by the classical ap-
proach using the measurement of the angle between 2 vectors.
These vectors are defined as:
A = I Z set – V (1)
B = V ref (2)
I phase + K o 3I 0 (3)
where
V is the actual line voltage for ground distance relays or the actual line to
line voltage for the phase distance relay.
I is defined as above for ground distance relays or the line to line current for
phase distance relays.
Zset is the setting reach and Vref is a positive sequence memory voltage
stored within the relay.
Vref is the polarizing quantity for the Mho elements, and is more completely
described in “Relay Method of Memory Polarization” on page 4-8.
To make the reach of the ground distance relay relate to the line positive se-
quence impedance the classical Ko factor is used.
This factor is defined as
Z0 – Z1 (4)
K 0 = -----------------
-
3Z 1
The relay includes a directional element to supervise the phase (21P) and
ground (21N) Mho elements, for all five Zones (21P1 to 21P5 and 21N1 to
21N5). The directional element improves security of the Mho elements for re-
verse faults such as: bus faults, phase-phase faults during high load conditions.
The directional element does not supervise Zone 3, Zone 4 and Zone 5 ele-
ments if these zones are set as offset characteristic. The directional element is
described in “Directional Element” on page 4-10.
Load The load impedance may enter into the protection zones permanently or tem-
Encroachment porarily due to system condition. This is observed in very long lines or heavily
loaded medium lines will have issue. This is a normal load conditions and it is
(LE)
not an abnormal/fault conditions. Therefore, the relay should not initiate any
trip command during this condition. The relay should identify properly wheth-
er the impedance entered into the protection zone is normal load condition or
fault condition.
This is distinguished by monitoring all phase-to-phase impedance values (i.e.
Zab, Zbc & Zca).If all the three phase impedances enter into the protection
zones with the limited load angle area, it is declared as a loading condition and
21P function is blocked. If only one of the phase-to-phase impedance enters
into the protection zones with the limited load angle area then this can be de-
clared as fault condition.
Generally, the three phase fault will not have any additional resistance compo-
nent other than the conductor resistance. Therefore, three phase fault will al-
ways have the fault angle as close to line angle only and it will not enter into
the loading area.
Figure 4.4: Load Encroachment (LE) Logic on page 4-5 shows how the LE
function works. Phase-to-phase current monitoring has been added to the logic
to ensure stable operation.
Enable/ Disa- Enable/ Disa- Enable/ Disa- Enable/ Disa- Enable/ Disa-
ble ble ble ble ble
Characteristic Type Mho / Quadri- Mho / Quadri- Mho / Quadri- Mho / Quadri- Mho / Quadri-
lateral lateral lateral lateral lateral
Forward Impedance 0.00 to 66.00 0.00 to 66.00 0.00 to 66.00 0.00 to 66.00 0.00 to 66.00 Both
Reach (Ohms secondary) (5A) (5A) (5A) (5A) (5A)
0.00 to 0.00 to 0.00 to 0.00 to 0.00 to
330.00 (1A) 330.00 (1A) 330.00 (1A) 330.00 (1A) 330.00 (1A)
Forward Reactance 0.00 to 66.00 0.00 to 66.00 0.00 to 66.00 0.00 to 66.00 0.00 to 66.00 Quadrilateral
Reach (Ohms secondary) (5A) (5A) (5A) (5A) (5A)
0.00 to 0.00 to 0.00 to 0.00 to 0.00 to
330.00 (1A) 330.00 (1A) 330.00 (1A) 330.00 (1A) 330.00 (1A)
Left Reach (R1) (Ohms 0.05 to 66.00 0.05 to 66.00 0.05 to 66.00 0.05 to 66.00 0.05 to 66.00 Quadrilateral
secondary) (5A) (5A) (5A) (5A) (5A)
0.25 to 0.25 to 0.25 to 0.25 to 0.25 to
330.00 (1A) 330.00 (1A) 330.00 (1A) 330.00 (1A) 330.00 (1A)
Right Reach (R2) (Ohms 0.05 to 66.00 0.05 to 66.00 0.05 to 66.00 0.05 to 66.00 0.05 to 66.00 Quadrilateral
secondary) (5A) (5A) (5A) (5A) (5A)
0.25 to 0.25 to 0.25 to 0.25 to 0.25 to
330.00 (1A) 330.00 (1A) 330.00 (1A) 330.00 (1A) 330.00 (1A)
Mho Characteristic Angle 70.0 to 140.0 70.0 to 140.0 70.0 to 140.0 70.0 to 140.0 70.0 to 140.0 Mho
(degrees)
Pickup Delay (seconds) 0.00 to 99.00 0.00 to 99.00 0.00 to 99.00 0.00 to 99.00 0.00 to 99.00 Both
Id Supervision (A second- 0.2 to 50.0 0.2 to 50.0 0.2 to 50.0 0.2 to 50.0 0.2 to 50.0 Both
ary) (5A) 0.04 to (5A) 0.04 to (5A) 0.04 to (5A) 0.04 to (5A) 0.04 to
10.00 (1A) 10.00 (1A) 10.00 (1A) 10.00 (1A) 10.00 (1A)
LHS
RHS
Enable/ Disa- Enable/ Disa- Enable/ Disa- Enable/ Disa- Enable/ Disa-
ble ble ble ble ble
Characteristic Type Mho / Quadri- Mho / Quadri- Mho / Quadri- Mho / Quadri- Mho / Quadri-
lateral lateral lateral lateral lateral
Forward Impedance 0.00 to 66.00 0.00 to 66.00 0.00 to 66.00 0.00 to 66.00 0.00 to 66.00 Both
Reach (Ohms secondary) (5A) (5A) (5A) (5A) (5A)
0.00 to 0.00 to 0.00 to 0.00 to 0.00 to
330.00 (1A) 330.00 (1A) 330.00 (1A) 330.00 (1A) 330.00 (1A)
Forward Reactance 0.00 to 66.00 0.00 to 66.00 0.00 to 66.00 0.00 to 66.00 0.00 to 66.00 Quadrilateral
Reach (Ohms secondary) (5A) (5A) (5A) (5A) (5A)
0.00 to 0.00 to 0.00 to 0.00 to 0.00 to
330.00 (1A) 330.00 (1A) 330.00 (1A) 330.00 (1A) 330.00 (1A)
Left Reach (R1) (Ohms 0.05 to 66.00 0.05 to 66.00 0.05 to 66.00 0.05 to 66.00 0.05 to 66.00 Quadrilateral
secondary) (5A) (5A) (5A) (5A) (5A)
0.25 to 0.25 to 0.25 to 0.25 to 0.25 to
330.00 (1A) 330.00 (1A) 330.00 (1A) 330.00 (1A) 330.00 (1A)
Right Reach (R2) (Ohms 0.05 to 66.00 0.05 to 66.00 0.05 to 66.00 0.05 to 66.00 0.05 to 66.00 Quadrilateral
secondary) (5A) (5A) (5A) (5A) (5A)
0.25 to 0.25 to 0.25 to 0.25 to 0.25 to
330.00 (1A) 330.00 (1A) 330.00 (1A) 330.00 (1A) 330.00 (1A)
Mho Characteristic Angle 70.0 to 140.0 70.0 to 140.0 70.0 to 140.0 70.0 to 140.0 70.0 to 140.0 Mho
(degrees)
Pickup Delay (seconds) 0.00 to 99.00 0.00 to 99.00 0.00 to 99.00 0.00 to 99.00 0.00 to 99.00 Both
Id Supervision (A second- 0.2 to 50.0 0.2 to 50.0 0.2 to 50.0 0.2 to 50.0 0.2 to 50.0 Both
ary) (5A) 0.04 to (5A) 0.04 to (5A) 0.04 to (5A) 0.04 to (5A) 0.04 to
10.00 (1A) 10.00 (1A) 10.00 (1A) 10.00 (1A) 10.00 (1A)
3I0 Supervision (A sec- 0.2 to 50.0 0.2 to 50.0 0.2 to 50.0 0.2 to 50.0 0.2 to 50.0 Both
ondary) (5A) 0.04 to (5A) 0.04 to (5A) 0.04 to (5A) 0.04 to (5A) 0.04 to
10.00 (1A) 10.00 (1A) 10.00 (1A) 10.00 (1A) 10.00 (1A)
Relay Method of The 21P and 21N Mho/Quad elements use positive-sequence voltage, derived
Memory from a memory voltage, as the polarizing quantity. No user settings are re-
quired for the memory polarization functionality. Sufficient positive-sequence
Polarization
voltage should be available during all fault events. However, during certain
fault events, especially 3-phase bolted faults near the line VT location, the pos-
itive-sequence voltage may be insufficient for correct operation. To ensure ad-
equate positive-sequence voltage exists for all fault conditions, the relay uses
a ring filter, implemented in software, to provide memory voltage as the source
for the positive-sequence voltage. This memory voltage lasts for approximate-
ly 150 cycles, even if all voltage inputs from the line VTs go to zero. A practi-
cal effect of using a memorized voltage is to expand the Mho characteristic by
the magnitude of the source impedance see “Effect of using Memorized Volt-
age on a 3-phase forward fault condition” on page 4-8. This expansion of the
characteristic ensures correct operation for zero voltage faults at the relay lo-
cation, and for forward capacitive faults.
.
X
No Memory
Voltage
Line Z
Full
Memory
Voltage
R
Z
rce
Sou
Figure 4.5: Effect of using Memorized Voltage on a 3-phase forward fault condition
Ring Filter The voltage memory in the relay uses a ring filter implemented in software.
The ring filter is a high-Q bandpass filter, with the frequency response centered
on the nominal system frequency. The effect of the ring filter is to retain some
voltage information for approximately 150 cycles, even if the measured system
voltage is severely depressed by a fault.
VA Ring Filter
Sequence
VB Ring Filter Component Vpos_mem
Filter
VC Ring Filter Vpos_mem
correct? Vpolarizing
Sequence
Component Vpos
Filter
Fault
Ring Filter
Memory Voltage
The ring filter is designed to adjust the center of the frequency response to ac-
count for small variations of the power system frequency. When the measured
voltage drops below 0.5 Vsec, the ring filter explicitly uses the nominal system
frequency as the center point of the bandpass filter. During this condition, or
when the system frequency varies widely or rapidly, as during out-of-step con-
ditions, the ring filter could provide an incorrect output. During these condi-
tions, the 21P and 21N Mho/Quad elements use the positive-sequence voltage
derived from the system voltage directly from the line VTs until the voltage
output of the ring filter is correct. If the measured positive sequence voltage is
below 1 Vsec, then the Mho/Quad elements use the positive sequence voltage
derived from the memory voltage
Directional The relay includes a directional element that directly supervises the Zone 1 to
Element Zone 5 phase and ground distance elements, the 50/51/67, 50N/51N/67N, 46-
50/51/67 overcurrent elements, and the 50N/67F and 50N/67R elements in the
Communications Aided Tripping schemes. The directional element considers
negative-sequence impedance, zero-sequence impedance, or positive-se-
quence impedance, depending on relay settings and system conditions at the
time of the fault. The element declares a forward fault when the impedance de-
termined by the directional element is within 90° of the line impedance.
jX
Forward
Line Impedance
90.0
Line Z Angle
R
Reverse
The directional element in the relay is always enabled. The directional element
actually consists of 3 separate internal elements: a negative-sequence element,
a zero-sequence element, and a positive-sequence element. The negative-se-
quence and zero-sequence elements use directly measured currents and voltag-
es. The positive-sequence element uses directly measured current, and a
memory voltage from the ring filter. The sensitivity for the negative- and zero-
sequence elements may be set by the user, to correctly account for load condi-
tions and system configuration. Both of these elements may be disabled as
well. The positive-sequence element is always active.
Y
3P Fault
N Minimum Sensitivity
Threshold
Z2 Y V2 Y Y
ON I2 Forward
N N
Y Y Y Directional
Z0 3V0 Forward
ON 3I0 Element
Asserted
N N
Y Y
V1 (mem) Forward
I1
Directional
Element
Valid
For 3-phase faults, the directional element will only use the positive-sequence
element. For all other faults, the directional element will consider, in order, the
negative-sequence calculation, the zero-sequence calculation, and the positive-
sequence calculation. The directional element will only move from one calcu-
lation to the next calculation if insufficient sequence voltages and currents ex-
ist to make a valid calculation.
The negative-sequence calculation determines the angle between the measured
negative-sequence impedance, and the positive-sequence line impedance angle
entered in settings. To perform this calculation, the default minimum amount
of negative-sequence voltage required is 0.5 V secondary, and the default min-
imum amount of negative-sequence current required is 0.2 A secondary.
The zero-sequence calculation determines the angle between the measured
zero-sequence impedance the zero-sequence line impedance angle entered in
settings. To perform this calculation, the default minimum amount of zero-se-
quence voltage (3V0) required is 1.0 V secondary, and the default minimum
amount of zero-sequence current (3I0) required is 0.2 A secondary.
Directional The output of the directional element asserts when the direction is determined
Element to be “forward”. This output is used internally by protection functions directly
supervised by the element, and is also available as the “Directional Element”
Outputs
indication in ProLogic equations. The directional element also provides the
“Directional Valid” output for use in ProLogic equations. This output asserts
when any one of the active sequence impedance calculations has sufficient in-
put quantities to make a valid direction determination, regardless of the actual
direction. The “Directional Valid” output will always be asserted, except in the
rare case where system voltage has gone to 0 for more than 30 cycles, as pre-
viously described. The 2 outputs can be combined in a ProLogic equation to e
a secure reverse directional output from the relay, for example.
Directional Element
Reverse Fault
Directional Valid
Directional The default setting of the directional element in the relay should be correct for
Element most applications. The default settings enable both the negative-sequence and
zero-sequence calculations, with the minimum sensitivities as described. There
Settings
are some applications where it may be advisable to change the sensitivity
thresholds for the negative-sequence or zero-sequence calculations, or it may
be desirable to disable one or both of these elements.
Selecting “Directional Element Override Enabled” allows user settings for the
negative-sequence and zero-sequence directional elements.
Negative-Sequence Enable/Disable
21P and 21N The phase selector algorithm for the relay ensures that:
Phase Selector • 21N only trips on single-phase-to-ground fault, so as to prevent 21N from
false tripping for phase-to-phase-to-ground faults with arc resistance
• Supervise 21P for low Source Impedance Ratio (SIR) ratios and single-
phase-to-ground faults at 20% of line reach or below.
Algorithm Details
The phase selector uses a combination of positive, negative and zero sequence
current phasors to correctly determine the faulty phase. No user settings are re-
quired for the phase selector functionality. An OR function with angle checks
between I1 and I2 as well as the angle between I2 and I0. The OR function al-
lows the algorithm to adapt to various fault conditions and provide the correct
fault type. When energizing a line with a T-tapped load, the user may have sys-
tem conditions where no pre-trigger load current is available. Using positive
and negative sequence currents alone may cause an incorrect fault determina-
tion if the load current is significantly large enough to affect the total positive
sequence current, which includes both load and fault current. Our algorithm
overcomes this problem.
Table 4.5: Angular difference between negative and zero sequence currents
for various faults
Capacitance When a fault occurs, especially on a line with high source to impedance ratio
Coupled (SIR), the CCVT secondary voltage can become quite different from the actual
system voltage varying in both magnitude and phase due to the transient re-
Voltage (CCVT)
sponse of the CCVT. This transient response can cause device 21 overreach
Transformer on significantly. A special CCVT transient compensation algorithm (Patent Pend-
21 Devices ing) has been included in L-PRO 4000 relay to address this issue.
The CCVT transient compensation algorithm uses a combination of techniques
with digital filters, vector averages and other means to rebuild the correct volt-
age from the transient distorted voltage waveforms. This combination of tech-
niques provides a secure method for detecting and correcting CCVT transient
phenomena. On one hand, it improves the reach accuracy of 21 devices dra-
matically during the period of the CCVT subsidence transient. On the other
hand, it will not sacrifice the relay operation speed very much. It does not add
any additional delay when the SIR is low (<1.2). In the worst case, it adds about
one cycle delay when the SIR is high (>15). For the operation time details, refer
to “IED Specifications” in Appendix A.
68 Power Swing The Power Swing function can be used as a tripping or blocking function. This
function consists of 2 sets of inner and outer impedance Zones on the R-X
plane, for details see If the user selects Device 68 to block for Power Swing
conditions, the relay energizes the front panel alarm LED when the 68 ele-
ments are blocking. If the user selects the 68 to trip for Power Swing conditions
the relay energizes the front panel target light. on page 4-17. Set the Power
swing zones to different values and to have the Power Swing function operate
for different system conditions. The Power swing zones are quadrilateral char-
acteristic and the reactance lines with the same angle as the angle chosen for
the line positive sequence impedance. Outputs from the outer and the inner
power swing zones are available on the output matrix for use with other types
of Power Swing schemes or for monitoring.
X4
X3
Zone 5
Zone 3
R2 R1 R3 R4
Zone 2
Line Z1
Zone 1
Line Angle
R
Zone 4
X2
X1
The basic Power Swing scheme looks at the positive sequence impedance of
the line with respect to the line loading. If the line loading causes the imped-
ance to cross the outer Zone, an Power Swing timer is started. If the impedance
does not cross the inner zone before this timer times out, the function produces
an output (either a block or trip whichever is set) when the impedance crosses
the inner Zone. The entire activity is supervised by an overcurrent function to
prevent undesired operations for impedances far from the origin.
The logic has a timeout feature that prevents the blocking function from oper-
ating for an indefinite amount of time. Device 68 functions as either a blocking
device or tripping device. The 68 Power Swing (68 Trip or 68 Block), 68 Inner
and 68 Outer Zone logic points are available in the output matrix. These logic
points are also logged as event messages in the event log, “Event Messages”
in Appendix D In addition, the outputs from the inner and outer Zones are
available for use with ProLogic to create any application scheme required.
If the user selects Device 68 to block for Power Swing conditions, the relay en-
ergizes the front panel alarm LED when the 68 elements are blocking. If the
user selects the 68 to trip for Power Swing conditions the relay energizes the
front panel target light.
Zone Blocking
Top Blinder
Bottom Blinder
Line
Energization Vpos - VposOld > 10 volts
The Logic shown in “Line Energization Supervision Logic” on page 4-19 has
been introduced in order to prevent potentially erroneous operations of the 21
upon energizing of T-tapped transmission lines that have transformers connect-
ed and the PT connected on the line side of the breaker. This logic does not re-
quire any user setting.
In this logic, the present positive sequence voltage is compared with the posi-
tive sequence voltage of 2 cycles previously. In an energization situation, the
VposOld would be near zero V and the present Vpos would be approximately
the nominal. As time goes by the old Vpos gets updated with the nominal volt-
age and would eventually equal the present. When it gets within 10 V second-
ary the top input to the AND gate would reset, go to zero, and reset the blocking
function.
The second input is the previous 2 cycle positive sequence voltage and has an
undervoltage setting of 30 V. This input goes high to block the distance relays
only if the positive sequence voltage from 2 cycles back was less than 30 V
(approximately 50% nominal), so, for a line that has been previously energized
and now experiences a fault, no distance relay blocking takes place.
The third input (the bottom one) produces an output only if the positive se-
quence line current is less than 4% nominal or 4.0% of 5 A secondary = 0.20
A secondary. If this current has been that low for the 1 second pickup time de-
lay this input to the AND gate would go high. For a de-energized line this input
would normally be high to allow the blocking scheme to operate if the other
two inputs are high. This input along with input two are present to help prevent
any distance relay blocking for a line that is in service and is now experiencing
a line fault.
Switch On To When energizing a line that has been out of service, the line may have a fault
Fault (SOTF) on it. If the line potential is derived from bus PTs, the distance relay function
acts normal and operates for any fault that exists when the line is energized. If
the line uses line PTs, the output of these line PTs is zero before energizing.
Because there is no memory voltage, operation of the line distance functions
may be undefined. To provide protection to detect faults when a line is first en-
ergized, the Switch On To Fault function (SOTF) is involved.
The logic diagram, Figure 4.14: Switch On To Fault (SOTF) on page 4-20,
shows how the circuit actually works. The SOTF function has options as Close
Command or Status Monitoring.
Close Command
This method can be applied where the relay can get the Breaker Close com-
mand from control panel manual close switch (TNC) or SCADA Close com-
mand. This Close command should reach the relay as an External Input or a
Virtual Input or ProLogics to initiate SOTF logic.
This method ensures that all the poles or any one pole are in dead condition for
more than the A1 timer by checking the current level (i.e. lower than 4% of
nominal), then it will enable the SOTF function.
Status Monitoring
This method can be applied where the relay can get Breaker status (52A). This
Breaker Status Monitoring signal should reach the relay as an External Input
or a Virtual Input to initiate SOTF logic.
This method will monitor all the pole statuses as well as each pole load current.
The SOTF function is enabled whenever current value is changing from 0 to
more than 4% of nominal or any pole Breaker status is changing from open to
close.
Both options have a common Pick-up delay (i.e. timer B1), which will allow
to extend the SOTF function enabled up-to the desired settable duration. Typ-
ically, this timer value shall be equal to Zone 2 time delay setting.
During SOTF Enabled condition, if any 50 Trip or 50N Trip or Zone 2 (21N2
or 21P2) alarm picked up condition happens, then the relay will go for an in-
stantaneous 3-pole SOTF Trip.
In addition to the above options, the SOTF function has a second harmonic re-
straint logic which allows the line to be more easily energized if the line is T-
tapped with an online reactor or transformer. Energization of the line with the
T-tapped device results in second harmonics that allows the line to be ener-
gized. If a fault exists that exceeds the line high set overcurrent devices, the line
is allowed to trip.
Close Pulse EI1 to EI 20, PL1 to PL24, VI1 to VI30 (This setting shall
be enabled when the Breaker signal setting is selected
as Close Command)
Pole Dead Pick-up Timer (A1, 0.0 to 999.9 Seconds (This setting shall be enabled
Pick-up timer) when the Breaker signal setting is selected as Close
Command)
Main Breaker Status EI1 to EI 20, PL1 to PL24, VI1 to VI30 (This setting shall
be enabled when the Breaker signal setting is selected
as Status Monitoring)
Aux Breaker Status EI1 to EI 20, PL1 to PL24, VI1 to VI30 (This setting shall
be enabled when the Breaker signal setting selected as
Status Monitoring & ring bus configuration is enabled)
Weak Infeed Weak Infeed provides tripping if fault levels are too low to activate the distance
(WI) units. If enabled, this function sends a permissive trip signal even if the fault
level seen by the relay is very low as when the line breaker is open. The posi-
tive sequence and zero sequence voltage detectors allow the relay to echo back
a permissive signal to allow the end with fault current to trip quickly without
the need for an auxiliary b contact.
25/27/59 Sync The relay can bring in voltages from both line and bus PTs. The Line Sync
Check Check function, if enabled, looks at the voltage steady state angle between the
line and bus PT voltage. If this angle is within a plus/minus specified value, (+/
- 1 to 50 degree magnitude range of setting available), the function enables a
definite time delay pickup (user-selectable 0 to 10 seconds) after which time
an output is produced.
The line sync reference voltage is taken from a bus source. The relay can bring
one single phase-to-neutral voltage. Logic within the relay allows the single-
phase quantity to be either A, B or C phase. All unused single-phase inputs
must be grounded for proper operation.
The Dead Main Live Auxiliary (DMLA), Live Main Dead Auxiliary (LMDA)
and Dead Main Dead Auxiliary (DMDA) logic functions use fixed values of
main and auxiliary positive sequence secondary voltages to determine the Sync
Check condition. The voltage is fixed at 20 V secondary, voltages below 20 V
are declared a dead state and voltages above 20 V are declared a live state.
When enabled, this function checks that the voltage angle between the line PT
and bus PT are within a specified value. Use this function to ensure that closing
a line to a system will result in acceptable power flow. The function uses pos-
itive sequence voltage, and therefore, can accommodate single-phase sources
as well as 3-phase sources. If a single-phase source is used, it must be connect-
ed to the corresponding phase designation on the relay input. For example: If
only a B-phase bus PT is available, it should be connected to the relay input B-
phase terminals. In this example, the voltage and angle limit is 20 degrees with
no pickup or drop out delay.
The Dead Main Live Auxiliary, Live Main Dead Auxiliary and Dead Main
Dead Auxiliary logic functions use fixed values of main and auxiliary positive
sequence secondary voltages to determine the sync check condition. The volt-
age is fixed at 20 V secondary. Voltages below 20 V are declared a dead state
and voltages above 20 V are declared a live state.
Main/Aux
79 Recloser The relay provides single-phase tripping and reclosing and 3-phase tripping
and reclosing on the 4000 hardware platform.
The schemes available are user-programmable and consist of the following
user setting options:
• 3-Phase Trip and Reclose Scheme
• 1-Phase/3-Phase Trip and Reclose Scheme
Please note that the user can select only one scheme at a time, although the user
can change the scheme selected by using the setting groups within the setting
software.
Lockout Indication
Lockout indication is provided for the lead and follower breaker. The lead and
follower lockout indication is set for a fixed time delay pickup of the close sig-
nal time (TP) plus 1.0 second. When the recloser goes to the lead lockout con-
dition, the breaker out of service timers are set to zero seconds and
automatically pick up. If the recloser is in the lead lockout state, the logic re-
mains in that state for setting (TD) seconds after the main or auxiliary breaker
is manually closed. The follower lockout condition occurs when the follower
breaker receives a close signal and the breaker remains open. If the recloser is
in the follower lockout state, the logic remains in that state for setting (TD) sec-
onds after the follower breaker is manually closed.
79 Recloser Enable/Disable
Number of Shots 1 to 4
The recloser provides flexibility with lead and follower breaker options. The
lead breaker is in the main or auxiliary position. This allows the user to control
the lead circuit breaker with complete Dead Main Live Auxiliary, Live Main
Dead Auxiliary, Dead Main Dead Auxiliary or Live Main Live Auxiliary su-
pervision (angle limit and voltage limit). The user also has the ability to control
the 79 remotely or locally with external or virtual inputs. The 79 recloser mon-
itors the breaker contact “a” status and automatically moves the follower
breaker into the lead position when the lead breaker is removed from service,
Sync Control
The flexibility provided with device 79 allows the user to control 1 or 2 circuit
breakers with complete Dead Main Live Auxiliary, Live Main Dead Auxiliary,
Dead Main Dead Auxiliary or Live Main Live Auxiliary supervision (slip fre-
quency). Sync control is provided on the lead breaker only, because the follow-
er breaker always recloses after the lead breaker has successfully closed.
ProLogic can be used to supervise follower breaker closing attempts if an ex-
ternal input is used to signal that the follower breaker has a valid sync check
signal from an external device (e.g. PLC).
Operation of the Relay with the Single-Phase Trip and Reclose Scheme
Setting
This setting allows the relay to trip only the faulted phase if the fault is single
phase in nature, then initiate a reclose of that phase after a line dead time. The
reason for this is that many faults are transient in nature, such as those caused
by lightening. The trip of the faulted phase, and that the trip of the faulted phase
then reclosing it some time later, should in many cases allow the line to return
into service. The benefit of this scheme is that approximately one half of the
power flow on the line (before the fault occurs) can be sent down the line dur-
ing the open phase condition, promoting system stability and eliminating the
need to resynchronize the line.
It should be noted that employing this scheme means that the high voltage line
breakers must be capable of opening and reclosing in a single phase mode and
that additional equipment such as line and neutral reactors must be installed on
the line in order to allow the scheme to work correctly. A thorough systems
study on the line and surrounding equipment must be performed in order that
appropriate scheme settings be determined to obtain satisfactory performance
of this scheme.
In operation, the Single-Phase Trip Setting blocks 79-3 from any attempts to
reclose on a 3 Phase basis. If a single phase fault occurs on the line, the faulted
phase is identified and only that phase is opened. After a period of time as de-
fined by the pickup time of timer T1 in the single phase recloser 79-1, that
phase will be reclosed. If the fault starts as a single phase fault and then evolves
into a multiphase fault, or commutates to a different phase while the first phase
is open, the line will 3 phase trip and reclosing will be inhibited. If the first sin-
gle phase fault is detected, then reclosed upon, and if the fault persists, the line
will 3-phase trip and lockout. Timer TD5 dropout time determines how soon a
subsequent single line to ground fault can occur after the first one in order for
the line to attempt another single phase trip and reclosure. If a single phase
fault is detected and that phase opens but fails to reclose before timer TM times
out, the line will 3-phase trip and lockout. It is important therefore that timer
TM be set longer in duration than the single phase recloser time. Only one sin-
gle phase reclose is attempted. If upon reclosure the fault persists, before timer
TD5 has had a chance to dropout, the line will 3-phase trip and lockout. To get
the line out of a locked out state, the line must be manually reclosed and stay
in service for longer than the single phase lockout timer TD reset.
Protection functions that can initiate a single phase trip and reclose are defined
by the user in the output matrix setting screen. The user has full control to dic-
tate which protection functions should initiate the recloser logic. Time delayed
trips for instance may be considered backup functions where recloser initiation
is undesired. In this case these types of operations can be set to block any at-
tempted reclosures in any of the chosen reclosure schemes. These protection
functions can also be set to initiate transient fault or dynamic swing recordings
and breaker failure initiations on the output matrix as well.
During the single pole open condition while in the single pole tripping mode,
unbalanced line load current will create negative and zero sequence line quan-
tities. In order to override these unbalances, provisions have been made in the
relay logic to allow the user to apply modified protective relay settings to the
line protections that will be automatically applied while the line is in a phase
open condition. These settings can be determined through load flow and fault
study cases for the protected line. Once the line phase recloses, the protective
settings that have been modified will return to their original settings. In this
way, protection security can be maintained while the line goes through a single
phase trip and reclose operation.
The drawing for the single phase reclosing logic is shown on the L-PRO 4000
Function Logic Diagram.
59 Main/ The relay provides overvoltage protection from both the bus and line PTs.
Auxiliary These functions are definite time delay functions.
Overvoltage
Gate Switch (Setting)
59 Va Main
59 Vb Main
T
59 Vc Main
0
The definite time delay main overvoltage function, similar to the undervoltage
function, looks at all 3 phase-to-neutral voltages. This function uses the RMS
voltages to make this determination of overvoltage and is settable to an AND
or OR logic.
The auxiliary overvoltage function operates exactly the same way as the main
overvoltage function except that it uses the voltages from the auxiliary PT in-
puts.
Main Enable/Disable
Auxiliary Enable/Disable
59N Zero The relay provides Zero sequence overvoltage protection from line side PT.
Sequence The element operates on the residual voltage quantity 3V0. The element has
one DTL and one Inverse Time stage
Overvoltage
The device 59N Inverse Time provides three IEC inverse time curve types,
three IEEE inverse time types of Zero sequence overvoltage protection and one
user defined curve .The equation and the parameters of device 59N are listed
below
Pickup
T (3V0) =TMS (B+ (A/ ((3V0/3V0pickup) p -1)))
Reset
T (3V0) =TMS (TR/ ((3V0/3V0pickup) 2 -1))
NO Curve Type A B P
Table 4.13: Table 4.13: 59N Zero Sequence Overvoltage setting functions
A 0.0010 to 1000.0
B 0.0000 to 10.0
p 0.01 to 10.0
TR 0.10 to 100.0
27 Main/ The relay provides undervoltage protection from both the bus and line PTs.
Auxiliary These functions are definite time delay functions.
Undervoltage The definite time main undervoltage function looks at the phase-to-neutral
voltage of all 3 phases to determine an undervoltage condition. The fundamen-
tal RMS voltage is used for this calculation. If any of the phase-to-neutral volt-
ages is below the set value, the function starts the definite time delay timer. The
user can set this function to be an AND or OR logic.
The auxiliary undervoltage function operates exactly the same way as the main
undervoltage function except that it uses the voltages from the auxiliary PT in-
puts.
60 Loss of
Potential (LOP) 27 VLa (0.75 pu fixed)
27 VLb (0.75 pu fixed) 168
27 VLc (0.75 pu fixed)
59 VLa (0.1 pu fixed)
59 VLb (0.1 pu fixed) 175 171
59 VLc (0.1 pu fixed)
176 0
dVpos/dt > 3V/cycle 173 174
17ms
dVpos/dt < -3V/cycle
0 5ms
ABS | dIpos/dt | > 0.1A/cycle 169
20ms
12ms
50 Ipos
167
50 3I0
The relay distance elements (21P and 21N) are supervised by both instanta-
neous non-directional overcurrent and the loss of potential (LOP) logic to pre-
vent false trip due to the loss of potential, where the phase distance elements
are supervised by the delta current (i.e. Ia-Ib, Ib-Ic and Ic-Ia), and the ground
distance elements are supervised by both the phase current and the zero se-
quence (3I0) current.
The loss of potential (LOP) function uses rate of change values for the positive
sequence voltage and current signal along with voltage and current supervision
to detect loss of potential conditions. This function operates very fast and been
field proven to block the distance elements during potential transferring be-
tween buses.
The function looks for a negative rate of change on the positive sequence volt-
age while determining if the positive sequence current is changing. A loss of
potential in itself should result in only a loss of voltage or a negative rate of
change of voltage. A fault results in a high rate of change of current as well. In
some rare cases there is a negative rate of change of fault current, therefore we
use an absolute rate of change of current. When the loss of potential condition
is detected, it is latched until all the 3-phase voltages are above 75% or a pos-
itive rate of change of voltage is detected. So the circuit detects a loss of poten-
tial that results in a voltage of less than 75%. Select positive and zero sequence
current blocking functions above the maximum load current, this ensures that
LOP does not pick up on fault.
A dropout timer has been added on the di/dt signal (in front of gate 169) to en-
sure that the di/dt signal will not reset earlier than the dv/dt signal. This change
improves the security of the algorithm in some particular fault situations.
Note that the positive and zero sequence current blocking level
should be set above the maximum line current. This function is fast
enough to provide blocking of the distance functions for schemes that
use bus potential inputs that are sometimes transferred without the
need for any external blocking inputs.
Logic Description (for details see Figure 4.17: Loss of Potential Logic on page 4-
Gate # 31)
167 When 50Ipos or 503I0 exceed their set point and go HIGH (1) it will invert and
block logic element 169.
168 When one of the phase-to-ground potentials falls below 0.75 pu, the logic ele-
ment’s output is HIGH.
169 To declare a LOP, this element must have a negative rate of change of positive
sequence voltage below or less than 3 V/cycle - AND - an absolute value of rate
of change of positive sequence current below or less than 0.1 A/cycle - AND -not
have a positive sequence load current (50 Ipos) above the setting.- OR - not
have 3 times zero sequence fault current (3Io) above the setting of 3Io.
170 LOP is declared by this logic element (logic HIGH) when any of the phase cur-
rents are above 0.2 A.
171 Has an output when o/p from 168 is HIGH - AND - o/p from logic 173 is HIGH -
AND - “NOT” logic 176 HIGH. (Positive sequence rate of change voltage is not
greater than 3 V/cycle and not 3 phase voltage greater than 0.1 pu).
172 Has an output when o/p from 170 is HIGH - AND - positive sequence rate of
change voltage is not greater than 3 V/cycle.
173 Has an output when o/p from 171 is HIGH - OR - timed o/p from logic 169 is
HIGH.
174 Has a Loss of Potential (LOP) output when o/p from 168 is HIGH - AND - o/p
from logic 172 is HIGH - AND - o/p from logic 173 is HIGH. The output is timed on
drop out. This output is sent to other elements of the relay to give indication and
block voltage elements, such as impedance from tripping falsely from loss of
potential condition.
175 Phase voltage AØ and BØ and CØ less that 0.1pu will have output HIGH.
176 Logic element 175 HIGH and positive sequence rate of change voltage is not
greater than 3 V/cycle - output HIGH, will invert into element 171 to Block tuning
171 off.
60 CT The relay provides CT secondary circuit supervision function for both main
Supervision and auxiliary CT’s. The element operates on presence of negative sequence
current Inps on main CT above the set vale and the absence of negative se-
quence voltage Vnps (below the set value, line PT) principle.
The auxiliary CT Supervision function operates exactly the same way as the
main CT Supervision function except that it uses the Inps current from the aux-
iliary CT in-puts.
Main Enable/Disable
Auxiliary Enable/Disable
81 Frequency The relay has 4 frequency devices available. Each frequency element can be
set to operate either at a fixed level of under-frequency, a fixed level of over-
frequency, or at a rate of change level (df/dt). The df/dt function can be set to
operate for a positive rate of change or a negative rate of change. Each frequen-
cy element has a definite time delay setting to create a time delayed output. A
fixed level of positive sequence voltage of 0.25 pu provides an undervoltage
inhibit on each element
T
Frequency (Hz)
O
T
df/dt (Hz/s)
O
Four frequency elements are provided with adjustable definite time delays.
Frequency is determined from the main voltage input (3 phase voltage).
50LS The relay takes in currents from main, auxiliary CTs and 2 additional CT in-
Overcurrent puts, 50LS Input 3 and 50LS Input 4. These individual overcurrent devices can
be used with ProLogic to create logic. 50LS Input 3 and 50LS Input 4 are not
available in the Output Matrix.
Input 3 Enable/Disable
Input 4 Enable/Disable
50BF Breaker The Breaker Failure (BF) protection function detects breaker failures. There
Failure are 2 sets of breaker failure protection functions, 50BF Main and 50BF Auxil-
iary, one for each breaker. When breaker failure is initiated by a trip or other
internal logic (user-settable through the output matrix) and the breaker current
still exists, 2 timers (T1 and T2, user-settable) are started. When these timers
are timed out and if the current still exists (which indicates breaker failure), the
output of this function is set high. Use the 2 outputs of this function to trip an-
other trip coil or the next level of breakers, such as bus breakers.
Main Enable/Disable
Auxiliary Enable/Disable
Main
Auxiliary
The L-PRO breaker failure protection can be initiated by any protection func-
tion located within the L-PRO relay by initiating the BFI column in the Output
Matrix screen. When the breaker failure function is initiated this way several
modes of operation may occur.
1. If the 3 Pole tripping option for the relay is selected, initiation of the BFI
column in the Output matrix will result in 3 pole breaker failure initiation.
Output of the breaker failure function will then be a three pole output. The
3 pole BF initiation will occur regardless of the type of fault detected, sin-
gle phase or multi-phase fault.
2. If the 1 Pole (single pole) tripping option for the relay is selected, initiation
of the BFI column in the Output matrix will result in a 1 pole breaker fail-
ure initiation if a single phase trip by a protection function operates. If a
multi phase fault occurs, a multi-phase protection function will be initiated
and the BF initiation will be a 3 pole breaker failure. For this case all three
poles of the breaker will be checked to see if they open correctly. Breaker
failure operation will result in 3 pole backup breaker tripping just like the
single pole BF initiation.
3. If the 1/3 Pole Scheme tripping option for the relay is selected, the breaker
failure initiation will be a combination of (1) and (2) above, with single or
three pole BF initiation as required by the fault detection.
The breaker failure function can also be initiated by an input to one of the ex-
ternal inputs from an outside protective relay or by a ProLogic input. This input
can be a phase segregated input that can come from a single pole trip from an
external relay and is shown on the Scheme Selector screen.
The breaker failure logic uses a current detector that is user settable in the 50BF
Setting screen to determine whether a pole is open or closed in the range of 0.1
- 50 A secondary. There are two (2) breaker failure functions available per line
breaker with adjustable pickup definite time delays from 0.01 to 99.9 seconds.
In any case, the output of the Breaker Failure function must be set to close out-
put contacts to perform its function. This is done by mapping the BF output to
the appropriate output contact in the Output Matrix screen.
50/51/67 Phase Phase Overcurrent provides backup protection to the line. The user can define
Overcurrent directional or non directional control on either 50 or 51 functions.
Device 51 provides 3 IEC inverse time curve types, 3 IEEE inverse time types
of overcurrent protection and one user-defined curve. The equation and the pa-
rameters of Device 50/51/67 are listed below.
No Curve Type A B p TR
50 Enable/Disable
51 Enable/Disable
Curve Type For details see Table 4.21: IEC and IEEE Curves on page
38.
A 0.0010 to 1000.0000
B 0.0000 to 10.0000
p 0.01 to 10.00
TR 0.10 to 100.00
50N/51N/67 Neutral overcurrent provides backup protection for line to ground faults. The
Neutral user can define directional or non directional control on either 50N or 51N
functions. 51N can also be configured for use in the communication scheme.
Overcurrent
All the curve definitions are the same as the phase overcurrent except that this
function uses 3I0 rather than phase current. The equation is:
All parameters for Equations 5 and 6 are defined in Table 4.23: 50N/51N/67
Neutral Overcurrent Settings on page 40.
50N Enable/Disable
51N Enable/Disable
Curve Type For details see Table 4.21: IEC and IEEE Curves on page 38.
A 0.0010 to 1000.0000
B 0.0000 to 10.0000
p 0.01 to 10.00
TR 0.10 to 100.00
46-50/46-51/67 Negative Sequence Overcurrent provides further backup protection for any un-
Negative balanced faults. The user can define directional or non directionall control on
either 46-50 or 46-51 functions. All the curve definitions are the same as the
Sequence
Phase Overcurrent. The only difference is that this function uses the negative
Overcurrent sequence current (I2) rather than phase current. The equation is:
46-50 Enable/Disable
46-51 Enable/Disable
Curve Type For details see Table 4.21: IEC and IEEE Curves on page
38.
A 0.0010 to 1000.0000
B 0.0000 to 10.0000
p 0.01 to 10.00
TR 0.10 to 100.00
Adaptive The relay provides an adaptive additional time delay (maximum 16 ms) re-
Additional sponse to the 50 O/C elements to prevent operation during RFI testing with
minimal pickup set points and operation near pickup.
Delay for 50 O/C
Elements This adaptive delay is applied to: 50LS-1, 50LS-2, 50LS-3, 50LS-4, 50, 50N,
46/50.
If the Pickup Delay setting (Tp) < 20ms AND Pickup Level setting <Inominal
(nominal current), an extra 8 ms delay is added. After this 8 ms timer expires,
if I < threshold, the second 8ms extra delay will be added in addition to the
original Tp. If I > threshold after the first 8ms timer expires, only Tp is used
for the delay. (Note Tp is the setting which is less than 20ms, could be 0ms).
The threshold is equal to 2*PickupLevel if pickup is between 40%*Inominal and
Inominal (i.e. between 2 A and 5 A for 5 ACT). The threshold is equal to
40%*Inominal if 2*PickupLevel < 40%*Inominal. The threshold is equal to Inom-
inal if 2*PickupLevel>Inominal
Z Circle Trigger
X
The Impedance Circle Trigger (Z Circle Trigger) triggers the relay to record on
a dynamic swing disturbance — only used to trigger a recording. This trigger
is usually set outside the last protection zone used and blocked during LOP
conditions.
Fault Locator Whenever a fault occurs and the line trips, the fault locator calculates the fault
type and the distance to the fault. This information is available from the front
display of the relay or through Port 150, 123 or the SCADA port or through
Relay Control Panel software. Fault locator information can also be captured
optionally in event records. Fault locator can be enabled/disabled through set-
tings (system parameters).
The fault locator is initiated by the following logic:
• 21 Trip
• 50N Trip
• 51N Trip
• Scheme Trip
• 21 Alarm (configurable)
The relay fault locator uses the Takagi method of fault location. The imped-
ance calculated for a fault initiated by any of the above functions will be cal-
culated and compared with the line impedance to calculate distance to fault.
Mutual Compensation
The fault locator has the ability to take into account mutual compensation for
up to two lines in parallel with the protected line where the relay is applied.
The currents from the parallel line (s) is brought into the relay via spare current
inputs IA3 and IA4. The currents from up to two parallel lines can be added to
determine the parallel line 3I0 current. There are two possible ways to get the
parallel line 3I0 currents.
1. Connect all 3 phases of the first parallel line into the IA3 inputs. The currents
are recorded by the relay if a recording initiation occurs and are added by
the relay to obtain 3 I01 to be used in the line impedance to fault calcula-
tion. Alternatively, the neutral current from line 1 CTs can be connected to
IA3. This quantity is added with the other line 1 phase current inputs (which
are IB3 = IC3 = 0 since no connection is made) to obtain line 1 residual 3I0
current. If this is done, the individual line 1 phase currents is not recorded
by the relay.
2. Connect the currents from the second parallel line (if present) in a similar
way to that of line 1.
Op 1 Op 2
A
B Op 3
C Op 4
D Op 5
T
E O
The setting group can be changed using the Relay Control Panel, with either
Change or Service access level, using the following path:
Relay Control Panel > Utilities > Settings Group
In this tab, choose desired setting group number and hit Save.
The setting group can also be changed using the relay display interface, after
login in with the Change or Service access level, using the following path:
Main Menu > Utilities > Maintenance > Settings Group Control
In this screen, highlight the group number, and then hit Edit. Choose the de-
sired setting group number, and then hit Enter with the cursor in the return
character (bottom right).
change, the interface processor uses the new setting group ancillary setting in-
formation at the same time as the protection processor switches to the new set-
ting group. An event is logged to show when the new setting group is in
service.
50/51N OC The carrier start logic is traditionally initiated by the Zone 2 distance elements,
Carrier Start but the relay provides 2 directional neutral overcurrent elements that can be
used in addition to the Zone 2 distance elements. The device 51N time over-
and Block Logic
current element, and the 50N/67F instantaneous overcurrent if enabled can be
configured to drive the carrier start logic. The 51N is configured in the 50N/
51N screen, while the 50N/67F is configured in the scheme selector screen,
both elements are forward directional elements.
The carrier block logic is traditionally initiated by the Zone 4 distance ele-
ments, but the relay provides one directional neutral overcurrent element that
can be used in addition to the Zone 4 distance elements. The device 50N/67R,
if enabled, can be configured to drive the carrier block logic. The 50N/67R is
configured in the scheme selector screen and is a reverse directional element.
The scheme selector can also be configured to enable the 50N/67F and 50N/
67R directional overcurrent elements as inputs to ProLogic statements. The
Basic Logic The basic selection does not provide any communication-aided logic for local
or remote protections.
101
Receiver #1
Receiver #2 102 103
PUTT SCHEME (+)
21-2
50N-67R
104 21-4 R 105
Receiver #1 0
Receiver #2 106
(If DCB shceme is TD2
107
selected, Zone 4 must TL2
be set reverse) 0
DCB SCHEME
6ms
108
TWD1
60 110 0
3ms 111
TWD3
TWD2
20ms
0 112
27 V1
113
59 V0 Weak Infeed Enable
WEAK INFEED LOGIC Switch
Receiver #1
120
Receiver #2
(+)
51NAlarm 115
117
TL1
116
TD1
50N-67F 119 DCB PUTT DCB PUTT
114 21-2 118
21P2 POTT BASIC POTT BASIC
21N2
TL3
Send
TD3
TL3, TD3 range: 0-1s
SCHEME SELECTOR
POTT SCHEME
Trip
3I0 > Pickup
TCS
Forward 121
0
Non-directional 21N4
21P4
(+) 21N2
21P2
3I0 > Pickup TCB 21N1
Reverse 122 21P1
0
POTT Logic The POTT logic is used for tripping schemes where the local end over-reaches
the remote end for forward fault conditions, for details see Figure 4.27: Com-
munication-aided Scheme on page 4-48. The local end sends a permissive trip
signal to the remote end when one of the forward directional elements operates.
The scheme send signal (permissive transfer trip send) is time delayed by timer
setting TL3; the local end is required to sense a forward fault for durations
greater than TL3. The local end does not produce a scheme trip output unless
the remote has detected a forward directional fault and sends the similar per-
missive trip signal to the local end. The local end senses a permissive trip re-
ceive signal and the scheme trip closes the output contacts and removes the
fault contribution from the local end. The remote end acts in a similar fashion
and the fault contribution is removed from the remote end.
Current reversal logic guards against incorrect permissive tripping for installa-
tions with parallel lines where one end of the un-faulted line is contributing
fault current and the other end of the un-faulted line is over-reaching and send-
ing a permissive trip signal. The local reverse directional elements are used
with the permissive receive signal from the remote end to form the blocking
logic. The blocking logic is time delayed by timer setting TL1; the local end is
required to sense reverse faults while receiving the remote permissive trip for
durations greater than TL1. The blocking logic continues to block the scheme
send and scheme trip signals when the reverse fault detection or permissive trip
receive signals go low. Timer setting TD1 determines the current reversal
block extension time.
For line terminals with a weak source, fault conditions could occur on the pro-
tected line where no elements operate at the weak source. Weak infeed (WI)
logic enables the relay to protect lines where one end of the line has no source
or has a very weak source. The WI scheme can only be enabled if the user has
selected the POTT scheme otherwise it is disabled. If enabled, the WI feature
enhances the POTT tripping logic.
WI enables the POTT scheme to quickly isolate line faults where one end of
the line has a high source of impedance.
During fault conditions where no weak source elements pick up the WI logic
echoes back the permissive transfer trip signal received by the weak source. If
a permissive transfer trip is received from the remote line end, AND 110, AND
111 and OR 115 echo a POTT signal back to the remote end. The permissive
transfer trip signal is required to last for durations greater than 20 ms. A 3 ms
time delay pickup and time delay dropout timer TWD2 determine the amount
of time between permissive transfer trip receive signals that the scheme echoes
back. If the permissive transfer trip receive signal is constantly high the WI
logic only echoes back for a time equal to TWD3 plus 3ms. If the PT signal
being received resets then starts up again, after timer setting TWD2, a new per-
missive transfer trip signal echoes back.
The WI logic blocks when forward or reverse faults are detected, the logic is
also blocked for a loss of potential condition. During a reverse or a forward
fault condition, the Zone 2, Zone 4, 51N, or 50N/67 elements could pick up. If
any of these functions pick up, they block the WI scheme by putting a high in-
put into inverted input of AND 110. The blocking condition is required last for
DCB Logic The DCB logic is used for tripping schemes where the local end over-reaches
the remote end for forward fault conditions, for details see Figure 4.27: Com-
munication-aided Scheme on page 4-48. Typically DCB is used when the com-
munications link may be disrupted during fault conditions, for example power
line carrier. The local end sends a block trip signal to the remote end when one
of the enabled reverse directional elements operates. The scheme send signal
(block trip send) is time delayed by timer setting TL3, the local end is required
to sense a reverse fault for durations greater than TL3. If one of the forward
directional elements operates the blocking logic does not operate. For forward
directional fault conditions the DCB logic is time delayed by timer setting TL2.
The forward fault condition has to last for durations greater than TL2. The local
end does not produce a scheme trip output if the remote has detected a reverse
directional fault and sends the similar block trip signal to the local end. The lo-
cal end senses a block trip receive signal and the scheme trip logic is disabled
with no intentional delay. Current reversal logic guards against incorrect local
tripping for installations with parallel lines where one end of the un-faulted line
is contributing fault current and the other end of the un-faulted line is reverse-
reaching and sending a block trip signal. The local forward directional ele-
ments are supervised by the block receive signal from the remote end to form
the blocking logic. The blocking logic reset is time delayed by timer setting
TD2; the local end is required to receive the remote block trip for durations
greater than 0 ms. The blocking logic continues to block the scheme trip signals
when the block trip receive signal goes low. Typically the block reset timer
TD2 is set longer than the forward directional elements reset time.
4 Protection Functions and Specifications
PUTT Logic The PUTT logic is used for tripping schemes where the local end under-reach
the remote end for close in forward fault conditions, for details see Figure 4.27:
Communication-aided Scheme on page 4-48. The local end sends a permissive
trip signal to the remote end when one of the forward directional elements op-
erates (Zone 1 distance elements). The scheme send signal (permissive transfer
trip send) is time delayed by timer setting TL3, the local end is required to
sense a forward fault for durations greater than TL3. The remote end does not
produce a scheme trip output unless a forward directional fault is detected and
the local end has sent the permissive trip signal. The remote end senses a per-
missive trip receive signal and the scheme trip closes the output contacts and
removes the fault contribution from the remote end. The remote end can act
quicker for fault conditions where the Zone 2 faults would be time delayed un-
less the close in fault condition was not transferred by the scheme send.
Fault Recording The relay provides DFR-quality fault recording, capturing input signal wave-
forms and external input states at a rate of 96 samples per cycle. Each record
also contains the timing of the internal logic produced by the relay (e.g. Device
51 trip). Obtain this information by uploading the records from the relay via
the Relay Control Panel file transfer process and view them with RecordBase
View software.
The quantities recorded are:
• 18 analog channels (6 voltages and 12 currents) @ 96 samples/cycle which
captures up to the 25th harmonic
• External inputs @ 1 ms resolution
• Protection element output signals @ 8 samples/cycle
• ProLogic signals @ 8 samples/cycle
• Active setting group
Swing The relay records dynamic system responses allowing the user to analyze sys-
Recording tem stability and to provide a larger context for fault analysis. Swing records
contain positive sequence phasor measurements and system frequency calcu-
lated at a rate of 1 phasor per cycle. Swing records can extend to 2 minutes in
duration.
The quantities recorded are:
• Positive sequence impedance (magnitude)
• Positive sequence voltage (magnitude)
• Positive sequence current (magnitude)
• 3-Phase Reactive Power (Vars)
• 3-Phase Real Power (Watts)
Event The event recording provides permanent storage for the event log. The user can
Recording create an event record automatically or manually. When the event auto save is
enabled, an event record is created approximately every 250 events.
The user can initiate an event manually through the Relay Control Panel.
Record Recording can be initiated automatically by the relay when a fault or abnormal
Initiation condition is detected. Set the relay to initiate a fault record on activation of any
of its trip or alarm functions or on assertion of any external digital inputs.
The assignment of fault record initiation to the various relay functions is done
through the relay’s Output Matrix settings.
A recording can also be initiated manually through the Relay Control Panel.
The commands Trigger Fault, Trigger Swing and Trigger Event are available
under the following path:
Relay Control Panel > Records
Also the relay display provides the option to initiate Fault Recording, under the
following path:
Main Menu > Records > Fault Recording
Record The length of each record is determined by the Record Length setting. Tran-
Duration and sient record lengths can be set between 0.2 and 10.0 seconds; swing record
lengths can be set between 60 and 120 seconds. Pre-trigger times are configu-
Extension
rable between 0.10 to 2.00 seconds for transient records and fixed at 30 sec-
onds for swing records and are included as part of the normal record length.
The relay automatically extends a record as required to capture consecutive
triggers that are close together. If a trigger occurs while a recording is in prog-
ress, the record is extended to include the full post-trigger time of subsequent
triggers, up to a maximum length —12.0 seconds for transient records; 180
seconds for swing records. If a trigger occurs before the end of a record caused
by a previous trigger, but too late to allow sufficient post-trigger time in a max-
imum extended record, a new overlapping record is created.
The normal record length settings are accessible under the Record Length
heading of the relay settings, and can be set with the Offliner Settings software.
Record Storage The relay compresses records on the fly, achieving a typical lossless compres-
sion rate of 4:1. As a result, the relay can store up to 75 x 2 second transient
records, or up to 75 x 120 seconds swing records, or a combination of 75 tran-
sient, swing and optionally event records. If the storage is full, new records au-
tomatically overwrite the oldest, ensuring that the recording function is always
available.
Record A listing of stored records is available through the Relay Control Panel under
Retrieval and the Records > List menu. The listing transfers records to a connected PC and
deletes them from storage.
Deletion
Front Panel The front panel display shows events in abbreviated form (Trip
and Alarm events only).
Relay Control Panel The full event log is available through the Main Menu->Events of
the Relay Control Panel
SCADA The protocols included in the relay allow all the SCADA master
access to the event data from the relay (Trip and Alarm events
only).
• 61850 SCADA protocol included in the L-PRO allow the SCADA client
access to Trip event data
DNP Protocol The relay supports a DNP3 (Level 2) SCADA connection. DNP3 is available
via a direct serial link or an Ethernet LAN connection using either TCP or
UDP.
Serial DNP communications can be utilized exclusively via serial Port 122.
Port 122 is an RS-232 DCE DB9F port located on the back of the relay. An ex-
ternal RS-232 to RS-485 converter can be used to connect the relay to an RS-
485 network. For details on connecting to serial Port, see “Communicating
with the Relay Intelligent Electronic Device (IED)” on page 2-2 and “Commu-
nication Port Details” on page 2-15.
Network DNP communications can be utilized via physical LAN Port 119 or
Port 120. Port 119 is available as a RJ-45 port on the front of the relay and as
an RJ-45 or ST fiber optic port on the rear. Port 120 located on the rear of the
relay is available as an RJ-45 or ST fiber optic port. DNP communications can
be used with multiple masters when it is utilized with TCP. For details on con-
necting to the Ethernet LAN, see “Network Link” on page 2-5.
The data points available for DNP SCADA interface are user configurable.
Complete details regarding the DNP3 protocol emulation and data point lists
can be found in “DNP3 Device Profile” in Appendix F
SCADA The parameters for SCADA communications may be defined using L-PRO
Configuration 4000 Offliner.
and Settings If DNP3 LAN/WAN communications were chosen, the relay’s network pa-
rameters need to be defined. This is done via the Maintenance interface. Note
that this effort may already have been completed as part of the steps taken to
establish a network maintenance connection to the relay.
1. Establish a TUI session with the relay and login as maintenance. The fol-
lowing screen appears.
2. Select the first option by entering the number 1 followed by Enter. The fol-
lowing screen appears.
Figure 5.2: Change the network parameters as needed for the particular application
Offliner SCADA Details on using the Offliner software are available in “To Install Software on
Configuration the Computer” on page -xiii. Details on downloading a completed settings file
to the relay are available in “Sending a New Setting File to the Relay” on
page 6-6.
Open the Offliner application according to the instructions found in the indi-
cated section and highlight the SCADA Communication selection. The screen
appears as follows.
Implementation The L-PRO 4000 conforms to IEC 61850-8-1, commonly referred to as Station
Details Bus Protocol. Implementation includes the following documents (“IEC61850
Implementation” in Appendix N’ on page Appendix N-1):
• Protocol Implementation Conformance Statement
• Model Implementation Conformance Statement
• Tissues Conformance Statement
All configurable IEC61850 parameters are available via the Maintenance in-
terface. Note that this effort may already have been completed as part of the
steps taken to establish a network maintenance connection to the relay.
1. Establish a TUI session with the relay and login as maintenance. The fol-
lowing screen appears.
2. Select the first option by entering the number 1 followed by <Enter>. The
following screen appears.
Figure 5.7: Change the network parameters as needed for the particular application
Note that unit’s IP address can be used on the IEC61850 client side for unique
unit identification instead of a physical device “PD Name”. The publisher con-
figuration is fixed and defined in the ICD file and available for reading to any
IEC61850 client. Subscriber functionality is also fixed and supported for the
Virtual Inputs only.
Toolbar
Copy Setting Copy values from one Setting Brings up the Copy Inputs dialog box
Group Group to another.
Ctrl+N Opens up a default setting file of the most recent setting version
Ctrl+Z Undo
Ctrl+X Cut
Ctrl+C Copy
Ctrl+V Paste
Ctrl+F6 Switches to the next open Offliner setting file, if more than one setting file is being
edited
Refresh
This button will manually refresh the graph if it has been zoomed.
Print Graph
To print a particular graph, click the Print Graph button.
Zoom on Graphs
Graphs can be zoomed to bring portions of the traces into clearer display. Left-
click on any graph and drag to form a small box around the graph area. When
the user releases the mouse, the trace assumes a new zoom position determined
by the area of the zoom coordinates.
Displaying Co-ordinates
At any time the user may right-click on the graph to display the co-ordinates of
the point the user selected.
Sending a New 1. Make sure the settings version and the serial number of the relay in the set-
Setting File to ting file match. The relay will reject the setting file if either the serial
number or the settings version do not match.
the Relay
2. Check the serial number and the settings version of the relay. The Device
Serial Number and Required Settings Version on the Identification screen
indicate the serial number and the settings version of the relay.
Creating a 1. Offliner Settings displays a default setting file on start up showing the set-
Setting File tings version in the bottom status bar. As an example L-PRO Offliner is
shipped with a set of default sample files of older settings versions. These
from an Older
sample files are “v1 sample.lps”, “v2 sample.lps”, “v3 sample.lps”, etc.
Version Each sample file contains default values of an older settings version. For a
new installation these sample files are placed in the default directory
C:\Program Files\ERLPhase\L-PRO Offliner Settings, or the user can
choose the path during the Offliner software installation. If an older ver-
sion of L-PRO Offliner was previously installed on the PC, then the default
directory may be C:\Program Files\APT\L-PRO Offliner Settings. Open a
sample file of the desired version. Use File/Save As to save the sample file
to a new file name. Then edit the setting file and the serial number, save it
and load it into the relay.
Use RecordBase View and RecordGraph to analyze the records from a relay.
1. Set the receive directory on the terminal program to point to a convenient
directory on the PC’s hard disk or network. For example with HyperTer-
minal, select Transfer>Receive File to set the receive directory.
2. Select one or more records on the relay using the List function in the Ter-
minal Mode’s Records menu.
3. Initiate transfer of the selected records by selecting R on the keyboard.
4. Start the RecordBase View program and use the File>Open menu command
to open the downloaded record files located in the receive directory spec-
ified in step 1.
Standard I/O
Optional I/O
In the LHS Menu Tree there are a series of menu headings that may have sub
menus associated with them. Clicking on an item in the left hand side tree view
will display its corresponding menu in the RHS view. Similarly, the user can
use the arrow keys to scroll through the menu tree.
The serial number of the relay must match the one in the setting file,
or the setting will be rejected by the relay. This feature ensures that
the correct setting file is applied to the right relay.
The user can choose to ignore the serial number enforcement in the
identification screen. The relay only checks for proper relay type and
setting version if the ignore serial number has been chosen.
Identification The first screen presents all the menu items in the left menu tree. Access the
menu items by clicking the tabs at the top of the screen or the item on the left
menu tree.
Identification
Nominal CT Format 5 A or 1 A
Setting Software
Station
Important Note
Nominal CT Secondary Current can be set to either 1 A or 5 A.
Nominal System Frequency can be set to either 50 Hz or 60 Hz.
Ensure setting selection matches that of target the relay.
The serial number of the relay must match the one in the setting file,
or the setting will be rejected by the relay. This feature ensures that
the correct setting file is applied to the right relay.
Analog Inputs
Analog Input Names screen identifies all the ac voltage and current inputs to
the relay. These names appear in any fault disturbance records the relay pro-
duces.
External Inputs
External Input Names screen allows the user to define meaningful names for 9
external digital inputs. Meaningful names may include terms such as T.T.
(Transfer Trip) and P.T. (Permissive Trip).
1 to 20 User-defined
Output Contacts
The Output Contacts are also identified during the setting procedure using
meaningful names. The dropout delay time settings are made here.
Outputs 1 to 21 User-defined
Virtual Inputs
The relay can control its internal functions and connected devices both
locally and remotely. Thirty general purpose logic points are accessible
via DNP3 and the TUI. The 30 virtual inputs are individually controlled
and include a set, reset and pulse function. The latch state is retained
during setting changes and relay power down conditions. The 30 virtual
inputs conform to DNP3 standards. Use the DNP3 functions such as
SBO (select before operate), Direct Operate, or Direct Operate with no
acknowledge to control virtual inputs.
Use virtual inputs to:
• control circuit breakers
• enable or disable reclosing
• enable or disable under-frequency load shedding
Setting Groups
System
Parameters
System Parameters
CT Turns Ratio
PT Turns Ratio
Line
Target Latching On
This option specifies whether the front Target LED is latched or not. Target
Latching on means that the target LED remains on after a trip until it is reset
through the front by Human Machine Interface (HMI). If the Target Latching
is set off the target light comes on during a relay trip and will reset.
Base MVA
The base MVA is used for recording purposes.
cases where voltage for line protection is obtained from bus PTs, the bus PTs
are connected to the main voltage inputs.
SCADA
Communication
The relay has configurable SCADA communication parameters for both Serial
and Ethernet (TCP and UDP). For DNP3 Level 2 (TCP) up to 3 independent
Masters are supported.
DNP
Configuration -
Point Map
The relay has configurable DNP point mapping. On the Point Map screen, any
of the configurable points may be added or removed from the Point List by
clicking (or using the cursor keys and space bar on the keyboard) on the asso-
ciated check box. A green 'X' denotes that the item will be mapped to the Point
List.
The list contains separate sections for Binary Inputs, Binary Outputs, and An-
alog Inputs. The list is scrollable by using the scroll control on the right hand
side.
DNP
Configuration -
Class Data
Class data for each DNP point can be assigned on the Class Data screen. Only
Points which were mapped in the Point Map screen will appear here. Sections
for Binary Inputs and Analog Inputs appear here; Binary Outputs cannot be as-
signed a Class. The list is scrollable by using the scroll control on the right hand
side.
In addition to assigning a Change Event Class to each mapped point, most An-
alog Inputs can also be assigned a Deadband and Scaling factor.
SCADA
Settings
Summary
This screen provides a summary of the current SCADA settings as set in the
working setting file. This includes SCADA Communication parameters and (if
the SCADA mode is set to DNP) Binary Input, Binary Output, and Analog In-
put information including Deadband and Scaling factors.
This SCADA Summary screen is scrollable and can be printed.
Record Length
Fault
Swing
The relay has recording and logging functions to analyze faults and dynamic
swing, and to review the operation of the overall protection scheme.
This screen displays the record length for each of the two types of recordings
provided: fault and swing. Pre-trigger times are configurable between 0.10 to
2.00 seconds for fault records and fixed at 30 seconds for swing records and
are included as part of the record length.
Setting Groups
The relay has 8 setting groups (SG). The user can change all relay setting pa-
rameters except the physical connections such as input or output parameters in
each setting group. Use any one of the 16 available Group Logic Statements
per setting group to perform Setting Group changes. The Group Logic state-
ments are similar to the ProLogic statements with the following exceptions, the
sole function is to activate one of the 8 setting groups and the processing is in
a slower half second cycle. Group Logic inputs statements can be driven from
ProLogic or any external input or virtual input or from previous Group Logic
statements. Each Group Logic statement includes 5 inputs (with Boolean state-
ments), one latch state and one pickup delay timer. View the active setting
group (ASG) from the Terminal Mode, from the front panel or from a record
stored by the relay (the active setting group is stored with the record).
Line Parameters
Line
Sequence Impedance
K0
K0 Override Enable/Disable
Mutual Compensation
KM1
KM2
Line Parameter Settings permit a parameter entry related to the line voltage,
CT ratio, PT ratio, line length, line secondary positive and zero sequence im-
pedance.
The K0 factor used is a default factor based on the line parameters (K0 = [Z0 -
Z1] / 3Z1). The user can specify by selecting K0 Override Enable.
Scheme Selector
Distance Scheme
DEF Scheme
Direction Forward
Direction Reverse
Directional Element
Protection Functions
ProLogic
and set a pickup and dropout delay. Start with input A by selecting any of the
relay functions using the list for up to 5 possible inputs. Put these inputs into
AND, NAND, OR, NOR, XOR, NXOR and LATCH logics by clicking on the
gate. Invert the input by clicking on the input line.
The output of ProLogic 1 can be nested into ProLogic 2 and so forth. If de-
scribed, the user can illuminate the front target LED on operation of this func-
tion by enabling this feature. The operation of the ProLogic statements are
recorded in the events logs.
The above is an example of a ProLogic application where an output is
produced if either of the line breakers is slow to open following a line
fault.
In this example current through the main and aux line breaker is present
as measured by the 50LS Main and the 50LS Aux functions after a
protection line trip as by Output Contact 14 and after the 0.50 ms (3
cycles) ProLogic 1 pickup time delay.
Group Logic
The 16 Group Logic statements reside in a slower processing thread within the
relay protection algorithms. The processing cycle happens once every half sec-
ond (0.5 s). When using ProLogic statements the user must keep in mind that
a latch or dropout timer should be used if the initiating condition does not last
at least 0.5 seconds.
Output Matrix
The output contact matrix determines which function initiates which output re-
lay. All output relays have an individual user-selectable stretch time, except
those outputs identified as communication initiation outputs. They can have
their time delay characteristics changed. Functions also initiate recording as re-
quired.
Print the entire output matrix by selecting Print under the File menu. This print-
out is produced on 2 pages.
Select Settings Summary to view and print the relay settings in text form, for
details see “IED Settings and Ranges” in Appendix B.
6 Offliner Settings Software
The electronics in the relay contain static sensitive devices and are
not user-serviceable. If the front of the relay is opened for any reason
exposing the electronics, take extreme care to ensure that the user
and the relay are solidly grounded.
Generally an analog metering check, as well as testing the I/O (External Inputs
and Output Contacts) is sufficient to ensure the functionality of the relay. Fur-
ther tests can be performed on delivery and acceptance of the purchaser’s op-
tion according to the published relay specifications in “IED Settings and
Ranges” in Appendix B.
Calibration The relay is calibrated before it leaves the factory; but if component changes
are made within the relay, the user may need to do a re-calibration.
To perform a calibration, the user must be logged into the relay using Relay
Control Panel at the Service access level to the front USB Port. Proceed to the
Utilities>Analog Input Calibrate. The Calibrate menu leads the user through
every analog input and prompts the user to apply the appropriate quantity.
For example, when selecting channel 16 to calibrate Main VA, the Applied
Signal check box will indicate the desired calibration of the relay. If a 69 V
phase-to-neutral quantity is applied to the back VA terminals, 69.0 V would be
indicated as the desired calibration. If a 69 V phase-to-neutral quantity is ap-
plied to the to the back VA terminals, 69.0 V would be indicated as the desired
calibration.
In a similar way, the user needs to go through all 18 ac analog quantities and
provide the information about the injected calibration quantities. The user must
have a test source to perform this function. Only the magnitude of the analog
input requires calibration, not the angle.
When an analog input channel is calibrated, verify the quantity measured by
selecting the Metering menu and the Analog Quantity submenu. VA of the ac
voltage input is used as a reference quantity by the relay. Therefore, if it is ab-
sent, there is not a locked, valid relationship among all of the analog quantities.
Testing the To test the external inputs connect the relay using Relay Control Panel, Meter-
External Inputs ing>External. This screen displays the status of the Input and Output Contacts.
Placing a voltage of 125 Vdcnominal, (150 Vmaximum), to each of the external
inputs in turn causes the input to change from Low to High status. These inputs
are polarity sensitive and this screen has a 0.5 second update rate.
Testing the Test the output relays to verify their integrity using the Utilities>Toggle Out-
Output Relay puts. The output contacts are toggled from open to closed by pressing the
Closed button. Verify the output contact status using an ohmmeter. When ex-
Contacts
iting this sub-menu, each contact status reverts to the open position.
About the The acceptance test setting file provided is not necessarily configured to a pro-
Acceptance vide a realistic setting example. Its configuration is intended to demonstrate
simple test methods for each relay element. Tests are organized to prevent in-
Test Setting File
terference of one protection element on the next within the relay for ease of
testing without using multiple setting files and minimizing the number of test
connection changes. All contacts in the relay will be tested if all elements in
this procedure are tested as written.
Testing all the elements is accommodated by using of the relay Setting Groups
(3 groups are used).
Setting Group 1 tests elements: 21P, 21N, 68, 60, Switch On To Fault, Weak
Infeed
Setting Group 2 tests elements: 46-50/46-51, 50/51, 50N/51N, 27, 59, 50LS,
50BF
Setting Group 3 tests elements: 25/27/59 (Sync Check), 79, 81
The file demonstrates all types of impedance characteristics available in the re-
lay: circle, tomato, lens, Quadrilateral.
Virtual Inputs are used to perform some input functions and demonstrate their
use.
In addition to, or exclusive of these tests, the user may wish to perform dynam-
ic simulation tests on the relay to verify the relay operates as per protection
scheme design using the settings that are applied for the particular line on
which the relay will be installed.
Reactive (x)
Forward
Characteristic
Angle = 90 degrees
Line
Angle
Resistive (R)
Directional
Reverse
Supervision
Figure 7.4: MHO Circle (Characteristic Angle = 90) Available for 21P and 21N
Reactive (x)
Forward
Characteristic
Angle = 90 degrees
Line
Angle
Resistive (R)
Reverse
Directional
Supervision
Figure 7.5: MHO Tomato (Characteristic Angle < 90) Available for 21P and 21N
Reactive (x)
Forward
Characteristic
Angle = 90 degrees
Line
Angle
Resistive (R)
Reverse Directional
Supervision
Figure 7.6: MHO Lens (Characteristic Angle > 90) Available for 21P and 21N
Reactive (x)
Forward
Line
Angle
R1
Resistive (R)
Reverse Directional
Supervision
kV 230kV (2)
Nominal secondary phase-to-phase voltage = ---------------------- = ---------------- = 115V
PTRatio 2000
where
kV - Nominal Primary Voltage
PT Ratio - Potential Transformer Ratio
Zero Sequence Impedance calculations for phase-to-ground impedance ele-
ment tests (using secondary Positive and Zero Sequence Line Impedances):
Z0 – Z1
K 0 = ------------------
3 Z1
4.41 – 1.03 + j15.38 – j5.81
= -----------------------------------------------------------------------------------
-
3 5.9 80
3.38 + j9.57 10.15 70.52 (6)
= ------------------------------ = ---------------------------------- = 0.57 – 9.5
17.7 80 17.7 80
where
Z1 - Positive Sequence Impedance
Z2 - Negative Sequence Impedance
K0 - Factor
1 + K0 = (1 + 0.57-9.5)
= (1 + 0.562 – j0.094)
= (1.562 – j0.094) = 1.5693.5
(7)
The pure resistive component 9.41 cos – 3.5 = 9.39 0 (11)
OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 OUT 9 OUT OUT OUT OUT OUT
10 11 12 13 14
21 21P2 21P3 21P4 21N2 21N3 21N4 46-50 DLPU S Trip Send 68 68 IN 27/59
50BF- 60 50BF- 50BF- 50LS 50N 51N 81-1 46-51 25C 51 OUTER 27/59 Main
Main1 68 Aux1 Aux 2 81-2 81-3 50 PL1 Aux
PL2
50BF- 81-4
Main2
L-PRO 4000 SIMPLIFIED REAR VIEW
Main Line Currents Auxilliary Line Currents
Auxilliary Voltages Main Voltages Power
301 303 305 307 309 311
Supply
300 302 304 306 308 310 324 325 326 327 330 331 332 333 334 335
For Prot./Sync./Rec.
Where each test specifies Metering/Protection, view the following screen un-
der Metering>Protection in Relay Control Panel.
60 Loss of Settings
Potential (LOP) • Voltage = 0.75 per unit phase-to-neutral fixed (In this case minimum op-
Test erate = 0.75 per unit = 0.75 * Vnominal = 0.75 * 66.4 V = 49.8 V)
• I1 Blocking = 10.0 A (positive sequence current that blocks LOP if
exceeded)
• 3I0 Blocking = 1.0 A (zero sequence current that blocks LOP if exceeded)
60 Test Procedure:
1. In Relay Control Panel access relay Metering>Logic>Protection.
Monitor: 60 Alarm
2. Apply balanced 3-phase nominal voltages (66.4 V) to the relay terminals:
Ph A: 330, 66.4 V 0
Ph B: 331, 66.4 V -120
Ph C: 332, 66.4 V +120
Ph N: 333
3. Connect 3-phase current sources (0.5 A) to the relay terminals (must be
greater than 0.2 A (4% Inominal) to enable due to low set supervision, for
details see Figure 7.10: Loss of Potential Logic (60) on page 7-12).
Ph A: 300 – 301, 0.5 A 0
Ph B: 302 – 303, 0.5 A -120
Ph C: 303 – 304, 0.5 A +120
Observe: 60 Alarm = Low
4. Instantaneously reduce single-phase voltage to 48 V or less.
60 Alarm = High
Contact 2 Closed
21P1 Phase (Zone 1 Single-Phase Under Impedance Test tested as 3-phase fault)
Distance Test
Settings
• Positive Sequence Secondary Line Impedance (100% of line)= 5.9
• Positive Sequence Line Angle = 80
• 21P1 = 4.72 (Maximum Reach = 80% of line at maximum torque angle
of 80)
• Time Delay = 0 (expect 1.3 cycles, 22 ms or less)
• Delta Current Supervision = 7.0 A (minimum phasor difference between
any 2 phases to allow 21P Trip)
Preliminary Calculations
Since this is a balanced 3-phase test, there is no Zero Sequence Current, so Z
is calculated as:
V Phase (17)
Z = ----------------
-
I Phase
where
Z - Phase Impedance
VPhase - Phase Voltage
IPhase - Phase Current
Determine the voltage and current quantities required to perform this test.
1. Determine the minimum current required (as per Idelta supervision setting).
2. Determine an appropriate fault voltage to use for the test.
3. Determine the 3-phase voltage phasors required to create the fault voltage.
2. Use the minimum test current to determine what voltage would be appro-
priate for this test.
V FaultMin (21)
Z = ----------------------------
-
2 I TestMin
where
VFaultMin - Minimum Fault Voltage
ITestMin - Minimum Fault Test Current
C
120 deg
HEALTHY
VOLTS
FAULT N A
VOLTS
0 deg
-120 deg
B
The following tables show the voltages to inject for a variety of fault voltage
levels using 115 V secondary phase-to-phase nominal (66.4 V phase-to-neutral
nominal).
A-B Fault
(C-phase voltage = 66.4 V +120) The resultant angle of A-B voltage always = +30
% Reduction 10% 20% 30% 40% 50% 60% 70% 80% 90%
Fault V 103.5 V 92.0 V 80.5 V 69.0 V 57.5 V 46.0 V 34.5 V 23.0 V 11.5 V
Fault Volt Angle 30 30 30 30 30 30 30 30 30
Voltage A=B 61.5 V 56.7 V 52.2 V 47.9 V 43.9 V 40.4 V 37.4 V 35.1 V 33.7 V
A Angle -2.7 -5.8 -9.5 -13.9 -19.1 -25.3 -32.5 -40.9 -50.2
B Angle -117.3 -114.2v -110.5 -106.1 -100.9 -94.7 -87.5 -79.1 -69.8
B-C Fault
(A phase voltage = 66.4 V) The resultant angle of B-C voltage always = -90
% Reduction 10% 20% 30% 40% 50% 60% 70% 80% 90%
Fault V 103.5 V 92.0 V 80.5 V 69.0 V 57.5 V 46.0 V 34.5 V 23.0 V 11.5 V
Fault Volt Angle -90 -90 -90 -90 -90 -90 -90 -90 -90
Voltage B=C 61.5 V 56.7 V 52.2 V 47.9 V 43.9 V 40.4 V 37.4 V 35.1 V 33.7 V
B Angle -122.7 -125.8 -129.5 -133.9 -139.1 -145.3 -152.5 -160.9 -170.2
C Angle 122.7 125.8 129.5 133.9 139.1 145.3 152.5 160.9 170.2
C-A Fault
(B phase voltage = 66.4 V -120) The resultant angle of C-A voltage always = +150
% Reduction 10% 20% 30% 40% 50% 60% 70% 80% 90%
Fault V 103.5 V 92.0 V 80.5 V 69.0 V 57.5 V 46.0 V 34.5 V 23.0 V 11.5 V
Fault Volt Angle 150 150 150 150 150 150 150 150 150
Voltage C=A 61.5 V 56.7 V 52.2 V 47.9 V 43.9 V 40.4 V 37.4 V 35.1 V 33.7 V
C Angle 117.3 114.2 110.5 106.1 100.9 94.7 87.5 79.1 69.8
A Angle 2.7 5.8 9.5 13.9 19.1 25.3 32.5 40.9 50.2
For this B-C test a minimum fault voltage of 23.6 V is required as calculated
in “B-C Fault Voltage Injections, for details see Table 7.15: B-C Fault Voltage
Injections on page 7-19. Select the next highest voltage. In this case 34.5 V
(70% reduction) is used.
The following formulae were used to calculate the voltages for the tables (they
may be used for any other desired fault voltage):
2 2 (24)
Test voltage magnitude = V Fault V Nominal
- + ----------------------
--------------- -
2 2
where
VFault - phase-to-phase fault voltage
VNominal - phase-to-neutral nominal voltage
V Fault (25)
60 – atan ----------------------
-
V
Nominal
Example of this calculation using the 70% voltage reduction from the B-C
fault, for details see Table 7.15: B-C Fault Voltage Injections on page 7-19:
Phase B-C voltage angle = -90 with respect to A-N voltage phasor.
Fault Voltage = 70% reduction of phase-to-phase nominal
2 2
Faulted Test Voltage Magnitudes = 34.5 66.4
---------- + ---------- = 1399.8 = 37.4V (27)
2 2
34.5
Faulted Phase Angle = 60 – atan ---------- = 60 – 27.5 = 32.5 (28)
66.4
For B-C fault adjust Phase B angle toward Phase C angle and adjust Phase C
angle toward Phase B angle:
B Phase Angle = -120 - 32.5 = -152.5
C Phase Angle = +120 +32.5 = 152.5
So,
A Phase Phasor = Unfaulted = 66.4 V 0
B Phase Phasor = Faulted = 37.4 V -152.5
C Phase Phasor = Faulted = 37.4 V +152.5
AC Current AC Voltages
+
+
+
+ +
A B C L-PRO A B C N
Main Current Inputs Main Voltage Inputs
21N# - Zan
50 Ia
138
50N 3IO
Directional Element N - Zone #
21N# - Zbn
50 Ib
139 141 0 TN#
50N 3IO 142 Out 1
Directional Element 60 4ms 0
21N# - Zcn
21N
50 Ic Generic Phase Distance
140 Logic (# = any zone)
50N 3IO
Directional Element
Preliminary calculations
Since this is a single-phase test, use the compensated impedance value calcu-
lated above; the calculated fault impedance Zfault is:
V fault (29)
Z fault = --------------
-
I fault
(30)
IMin = (Greater of Iphase and 3Io Supervision)x105% = 1.5x1.05 = 1.58A
Load Load Encroachment function operates based on the fact that all phase-to-phase
Encroachment impedances (Zab, Zbc and Zca) are within the limited load angle area.
Test
Load Encroachment Test Procedure
1. Use the following load encroachment settings together with above 21P set-
ting.
3. Apply the following 3-phase currents to the relay main ac current terminals:
Ph A: 300 – 301, 5.3 A <-30
Ph B: 302 – 303, 5.3 A <210
Ph C: 304 – 305, 5.3 A <90
4. Observe target Load Encroachment.
5. Disable Load Encroachment, repeat steps 2-3.
6. Observe 21P3 Alarm/Trip.
End of Load Encroachment test.
21-2 6ms
108
21-4R TWD1
60 110 0
111
3ms TWD3
TWD2
20ms
Receiver
0 112
Weak
27 V1 Infeed
113 Enable
59 V0
Switch
Scheme Scheme
Trip Send
For this test apply 0 voltage and 0 current to the relay with no prefault. This
causes the first 3 conditions to be met: (27V1, NOT (Zone 2 OR Zone 4R),
NOT Loss of Potential).
In this case a Virtual Input is set up to simulate the Permissive Trip Receive
contact via ProLogic.
1. Objective of this test is to observe the basic operation of the logic. The user
may disable 50, 50N, 21P2 and 21N2 functions.
2. Instantaneously, step single-phase current from 0 to 1.05 A to:
Ph-A: 300 – 301, 1.05 A<Any
AND
External Input- 1 from Low to High.
Both inputs shall be changed at the same time. Analog input can be delayed by
1 – 3 cycles to simulate the delay in circuit breaker operation.
3. Observe target Switch On To Fault on A.
End of Switch On To Fault Close Command test.
1. Objective of this test is to observe the basic operation of the logic. The user
may disable 50, 50N, 21P2 and 21N2 functions.
2. During this test, the Main Breaker Status input (connected to EI-1) is used
activate the SOTF logic. Ring bus configuration shall be disabled to disa-
ble the Aux Breaker Status input.
3. Instantaneously, step single-phase current from 0 to 1.05 A to:
Ph-A: 300 – 301, 1.05 A<Any
AND
External Input 1 from Low to High.
Both inputs shall be changed at the same time. Analog input can be delayed by
1 – 3 cycles to simulate the delay in circuit breaker operation.
4. Observe target Switch On To Fault on A.
End of Switch On To Fault Status Monitoring test.
Settings
• Outer Right Blinder = 17 ohm
• Outer Left Blinder = -17 ohm
• Inner Right Blinder = 13 ohm
• Inner Left Blinder = -13 ohm
• Top Outer Blinder = 27 ohm
• Top Inner Blinder = 18 ohm
• Bottom Inner Blinder = -18 ohm
• Bottom Outer Blinder = - 27 ohm
• Swing timer = 1.0 second
• I1 Supervision (positive sequence current) = 3.0 A
• 3I0 Supervision = 1.0 A
Note: Out of Step Blinders are Positive Sequence Impedance Quantities.
165 Out 2
68 Trip
60
Preliminary Calculations
Because this is a Positive Sequence Impedance, perform this test as balanced
3-phase, since this is the easiest way to obtain positive sequence. The calculat-
ed Z is:
V Phase (31)
Z = ----------------
-
I Phase
where
Z - Fault Impedance
VPhase - Phase Voltage
IPhase - Phase Current
The minimum 3-phase current required must be greater than the I1Supervision
Setting (3.0 A). Add 5% to ensure that the supervision is met:
(32)
IMin = I1Supervision x 105% = 3.0 x 1.05 = 3.15A
where
IMin - Minimum Current
I1Supervision - Positive Sequence Supervision current setting
3. Connect 3-phase current sources (3.15 A 180 from voltages) to the relay
terminals.
Ph A: 300 –301, 3.15 A 180
Ph B: 302 –303, 3.15 A +60
Ph C: 303 –304, 3.15 A -60
Observe 68 InnBlinder Alarm = Low
Contact 13 = Open
4. Simultaneously increase (ramp up) 3-phase currents.
At 4.86 to 5.36 A (expect 5.11 A):
68 InnBlinder Alarm = High
Contact 13 = Closed
Change Setting For the next group of tests using the Acceptance Test file change to Setting
Group Group 2.
1. In Relay Control Panel access Utilities>Virtual Inputs.
2. Select corresponding virtual input for “Switch to SG2”.
3. Click on Pulse On button to execute the command.
4. The Active Setting Group will become Group 2.
27 Settings
Undervoltage • Main: AND (3-Phase Undervoltage)
Test • Auxiliary: AND (Single-Phase Undervoltage; Only 1 phase is connected)
• Main and Aux Pickup: 30 V
• Time Delay: 0.01 second
27 Va main RMS
27 Vb main RMS 300
T
27 Vc main RMS Out 14
27 Main Undervoltage 0
301
3 Phases Connected
27 Va aux RMS
27 Vb aux RMS 302
27 Vc aux RMS
T
Out 13
27 Aux Undervoltage 0
303
1 Phase Connected
27 Test Procedure
1. In Relay Control Panel access relay Metering>Protection.
Monitor:
27 Main U/V
27 Aux U/V
Monitor Output Contacts:
13 (27 Aux Trip)
14 (27 Main Trip)
2. Apply balanced 3-phase nominal voltages (66.4 V) to the relay terminals.
Ph A: 324 and 330, 66.4 V 0
Ph B: 331, 66.4 V -120
Ph C: 332, 66.4 V +120
Ph N: 327 and 333
Observe:
27 Main U/V = Low
27 Aux U/V = Low
3. Reduce A Phase voltage.
At 31.0 to 29.0 V (expect 30 V):
27 Aux U/V = High
Contact 13 closed
27 Main U/V remains Low
Contact 14 open
4. With A Phase voltage still reduced, reduce B and C phase V:
At 31 to 29 V (expect 30 V):
27 Aux U/V = High
27 Main U/V = High
Contact 14 closed
End of 27 test.
59 Overvoltage Settings
Test • Main: AND (3-Phase Overvoltage)
• Auxiliary: OR (Single-Phase Overvoltage – 1 phase connected)
• Main and Aux Pickup: 72 V
• Time Delay: 0.05 second
59 Va main MS
59 Vb main RMS 296
T
59 Vc main RMS Out 14
59 Main Undervoltage 0
297
3 Phases Connected
59 Va aux RMS
59 Vb aux RMS 298
59 Vc aux RMS
T
Out 13
59 Aux Undervoltage 0
299
1 Phase Connected
59 Test Procedure
1. In Relay Control Panel access relay Metering>Protection.
Monitor:
59 Main O/V
59 Aux O/V
Monitor contacts:
Output 13 (59 Aux Trip)
Output 14 (59 Main Trip)
2. Apply balanced 3-phase nominal voltages (66.4 V) to the relay terminals.
Ph A: 324 & 330, 66.4 V 0
Ph B: 331, 66.4 V -120
Ph C: 332, 66.4 V +120
Ph N: 327 and 333
Observe:
59 Main O/V = Low
59 Aux O/V = Low
5ms
Alarm
0
Timer is active, only if it's directional or combined
Timing Test
1. Monitor (Timer Stop) on Output Contact 7.
2. Set timer start from single-phase 0.0 A to 4.00 A transition (this equates to
4x pickup).
where
TMS -
IMultiple -
3. Inject fault.
Observe Relay Target: “51N Trip”
End of 50N/51N test.
285 Out 11
51P Directional Control
51 Timing Test
1. Monitor (Timer Stop) on Output Contact 11.
2. Set timer start from single-phase 0.0 A to 6.00 A transition (this equates to
4x pickup).
3. Inject fault.
Time Delay A
= TMS B + ------------------------------------
-
p
I multiple – 1
51 Directional Test
Settings
• 51 Settings as above
• Line Angle = 80 (i.e. current lags voltage by 80)
Note: Operating Range = ± 90 from line angle
51P Forward
266
51P Reverse
278 51P directional control
267
Non-directional
50P Forward
268
279 50P directional control
50P Reverse
269
Non-directional
46-50 Reverse
283 46-50 directional control
277
Non-directional
46-50/46-51 Settings
Negative • Directional
Sequence • 46-51 Pickup = 1.0 A
Overcurrent • Time Curve = IEEE Extremely Inverse
Test
A = 5.64
B = 0.02434
p=2
TMS = 3.0
5ms
Alarm
0
Timer is active, only if it's directional or combined
Figure 7.28: Negative Sequence Instantaneous and Time OverCurrent Logic (46-50/
46-51)
2 (35)
I A + aI B + a I C
I 1 = --------------------------------------- where a = 1 120
3
2 (36)
I A + a I B + aI C
- where a = 1 120
I 2 = ---------------------------------------
3
3I o = I A + I B + I C (37)
where
IA - Phase A Current
IB - Phase B Current
IC - Phase C Current
Using Equation 6 notice that there is a need to triple the pickup setting current
on one phase to obtain the pickup value of negative sequence current.
For example injecting 1.0 A on Phase A only (Phase B = Phase C = 0), and with
no voltage applied, the 46-51 element becomes non-directional even though
the setting is directional:
2 (38)
1 + a 0 + a0 1
I 2 = ------------------------------- = --- = 0.33 A
3 3
Time Delay A
= TMS B + -------------------------------------
-
p
I Multiple – 1
3. Inject fault.
Observe Relay Target: “46-51 Trip”
End of 46-51 test.
Directional (see OR 265, for details see Figure 7.27: Directional Element Logic on page 7-
Element 38)
Positive
Settings
Sequence
• Directional
Current
Supervision • 50ILpos (Positive Sequence (I1) Low Set = 0.2 A fixed)
Threshold • 46-50 Pickup = 5.0 A
(50ILpos) Test
46-50 Directional Control If Directional or combined, T must be greater than
T
288 0
Out 8
50 I2
5ms
Alarm
0
Timer is active, only if it's directional or com
Figure 7.29: Negative Sequence Instantaneous and Time OverCurrent Logic (46-50/
46-51)
Test Calculations
The relay directional element has a fixed positive sequence current setting of
4% of Inominal that is used to supervise the directional control. If the positive
sequence current falls below 4% of Inominal, the directional control becomes
non-directional. So, for directional control of the 46 element, the following is
required:
Negative Sequence Current (I2) greater than pickup AND Positive Se-
quence Current (I1) greater than or equal to 0.2 A (4% Inominal).
For this test inject a Reverse Negative Sequence fault:
With the I1 Directional Supervision threshold not exceeded, the directional
unit is disabled, therefore the directional element will be non-directional.
This means that the 46 element is able to operate in the reverse direction as
well as in the forward direction.
When the I1 Directional Supervision is exceeded, the 46 drops out as it has
now become Directional (forward) only.
Testing is accomplished by applying 3-phase balanced I2 quantities sufficient
to pickup the 46 element and then increasing the magnitude of any single-
phase.
For example, for our 46-50 pickup of 5.0 A, use I2 of 5.1 A. This is sufficient
I2 magnitude to solidly pickup the 46-50 element at the line angle. Note, that
the line angle is the Positive Sequence Forward Direction but is the Negative
Sequence Reverse Direction:
IA = 5.1 A -80
IB = 5.1 A +40
IC = 5.1 A +160
The symmetrical components using Equations 5 to 7:
I1 = 0
I2 = 5.1 A -80
3I0 = 0
Now vary single-phase current to obtain sufficient I1 to enable the directional
element (0.2 A).
Vary Phase A for this test.
Use the I1 formula to calculate Inew because we know the required value of I1
(0.2 A).
where
Iold - 5.1 A (I2 pickup plus margin)
I1 - |Inew - Iold|/3
0.2 - |Inew - Iold|/3
Inew = 0.6 + 5.1
Inew = 5.7 A
Auxiliary:
• 50LS Pickup: 1.0 A
• Time Delay: 0.00 seconds
• 50BF Time Delay 1: 5.0 seconds
• 50BF Time Delay 2: 10.0 seconds
Input 3:
• 50LS Pickup: 0.3 A
• Time Delay: 1.00 second
(50LS used with Virtual Input 3 to make Breaker Fail for Breaker 3)
Input 4:
• 50LS Pickup: 0.3 A
• Time Delay: 1.00 second
(50LS used with Virtual Input 4 to make Breaker Fail for Breaker 4)
Main and Aux. Breaker Fails are set to be initiated via the Output Matrix from
50LS Pickup (1.0 A Main and Aux and 0 time delay). Note: Requires a mini-
mum of 0.2 A on any phase to arm Breaker Fail.
AND gate. The initiate in this case is provided by Virtual Input 3 which will
latch until the current drops below the 50LS threshold.
Note: ProLogic 2 (not shown) is for 52-4 (Input 4).
For the next group of tests using the Acceptance Test file, change to Setting
Group 3.
1. In Relay Control Panel access Utilities>Virtual Inputs.
2. In the drop down list of virtual inputs, select the corresponding virtual input
to “Switch to SG3”.
3. Cursor over to Action and select Pulse On.
4. Click on Pulse On to execute this command, the Active Setting Group is
Group 3 now.
81 Settings
Overfrequency • 81-1 Pickup = 60.5 Hz Fixed Rate (50.5 Hz for 50 Hz Relay)
and • 81-1 Time Delay = 0.5 second
Underfrequency • 81-2 Pickup = 59.5 Hz Fixed Rate (49.5 Hz for 50 Hz Relay)
Test
• 81-2 Time Delay = 0.5 second
• 81-3 Pickup = +1.0 Hz/second
• 81-3 Time Delay = 0.2 second
• 81-4 Pickup = -1.0 Hz/second
• 81-4 Time Delay = 0.2 second
Requires minimum of 0.25 per unit positive sequence voltage (fixed setting) to
enable the 81 element.
81-4 Frequency T
200 ms 307 Out 9
Vpos. > 0.25 PU 0
0
81-2 = Low
Contact 8 = Closed
4. Ramp down the voltage frequency.
At 59.501 to 59.499 Hz (49.501 to 49.499 Hz for 50 Hz Relay):
81-1 = Low
81-2 = High
Contact 8 = Closed
5. Turn voltage source off.
25/27/59 Sync Note: Three or four voltage sources are required for this test.
Check Test The relay will create the positive sequence sync check voltage out of the sin-
gle-phase auxiliary voltage input depending on which phase is injected.
Settings
• Maximum voltage: 70 V sec. (Maximum Positive Sequence voltage)
• Minimum voltage: 40 V sec. (Minimum Positive Sequence voltage)
• Angle Difference: 20 degrees
• Time Delay: 200 milliseconds
• Dead Main Live Aux. (DMLA): Enable
• Live Main Dead Aux. (LMDA): Enable
• Dead Main Dead Aux. (DMDA): Enable
Contact 10 = Open
8. Slowly ramp up the auxiliary voltage magnitude.
At 69.0 to 71.0 V (expect 70 V):
25/27/59 = Low
Contact 10 = Open
8. Turn all voltage sources off.
End of Sync Check test.
79 Recloser Settings
Test • Number of Shots: 4
• First Reclose (T1): 2.0 seconds
• Second Reclose (T2): 4.0 seconds
• Third Reclose (T3): 6.0 seconds
• Fourth Reclose (T4): 8.0 seconds
• Close time (Tp): 0.3 second
• Lockout Reset (TD): 12 seconds
• Initiate Reset (TDI): 1.0 second
• Sync Control: Enable
• Mode: Main then Aux.
• Block Reset (TDB): 1.0 seconds
• Follower Time (TF): 8.0 seconds
• Breaker Out Of Service (TC): 200 seconds
• Follower Sequencer: Close after Recloser Follower Time
• Main Breaker: EI1 [Breaker Status a]
• Aux Breaker: EI2 [Breaker Status a]
The following procedure allows the user to test the Main and Auxiliary 4-shot
reclosers, ending in 79 lockout.
The only test equipment required for this test is a 125 Vdc supply.
Output Contact 5 of the relay is used to simulate the Main Breaker “a” Contact
and Output Contact 6 is used to simulate the Aux Breaker “a” Contact.
The Main Breaker Status is monitored by External Input 1; and Auxiliary
Breaker Status is monitored by External Input 2.
Output 7 is used to simulate a protection operation. It supplies a trip command
via External Input 3 and initiates the 79 operation.
Connect a 125 Vdc supply to the relay output and input terminals as shown, for
details see Figure 7.34: Test Connections for 4-Shot Recloser Test on page 7-
53.
+
OUT 5 210 OUT 6 212 OUT 7 214
ProLogic equations are used to activate and supervise the 79 test functions.
Normally each of these ProLogic equations would not be set to target, but for
this type of acceptance testing, it is convenient for seeing operations as they
happen.
Figure 7.35: Simulating Main Breaker Close Command using Virtual Input in ProLogic
ProLogic 2: This equation is used to reset the Main Breaker Status via ProLog-
ic 3 (Opens Out 5).
Figure 7.36: Breaker Status Reset using ProLogic (Ext. Input 3 via Output Contact 5)
ProLogic 3: This equation is set from ProLogic 1 (Main Breaker Close Com-
mand) OR ProLogic 9 (Main Breaker Reclose). (Note that ProLogic 9 is
mapped to Out 14, so Out 14 is used to indirectly provide ProLogic 9 availabil-
ity to ProLogic 1 through 8.) ProLogic 9 changes the Main Breaker Status con-
tact (Out 5) and apply a trip signal via ProLogic 4. Reset occurs when ProLogic
2 (Breaker Status Reset) is activated.
ProLogic 4: This equation applies the External Trip (Closes Out 7), 10 seconds
after the Breaker Status (ProLogic 3) goes high (i.e. Main Breaker Status =
Closed).
Figure 7.38: Using ProLogic to give Trip Command via External Input
ProLogic 5: This equation provides indication via the relay HMI display, that
the Recloser has locked out.
ProLogic 6: This equation resets the 79 Lockout. It uses Virtual Input 1 “SCA-
DA Reset 79" to simulate a SCADA Lockout Reset command. In this case, this
is done by closing the Main Breaker Status (Out 5), then Auxiliary Breaker Sta-
tus (Out 6) to simulate main and auxiliary breaker closed status. This latching
function resets when the 79 Lead Lockout goes low.
ProLogic 7: This equation is intended only for giving indication of when the
79 Lockout is reset.
This indication, along with ProLogic 6, proves the 79 Reset timer (TD).
ProLogic 9: This equation closes Out 5 to simulate Main Breaker “a” contact,
and also closes Out 14 to provide feedback into Main Breaker Status ProLogic
3. This latching function resets when an external trip is received.
79 Test Procedure:
1. Access Utilities>Virtual Inputs.
2. Select Virtual Input 2 (“SCADA Close Breaker 1&2”).
3. Pulse On (This simulates a SCADA Breaker Close command.)
Observe the relay actions on the relay HMI:
Main Breaker Close and Aux Breaker Close
After 10 Seconds: External Trip (Time delay of ProLogic4)
After 2 Seconds: Main Breaker Reclose (Shot 1, T1)
After 8 Seconds: Auxiliary Breaker Close (Shot 1, TF)
After 2 Seconds: External Trip (PL4 – TF)
After 4 Seconds: Main Breaker Reclose (Shot 2, T2)
After 8 Seconds: Aux Breaker Close (Shot 2, TF)
After 2 Seconds: External Trip (PL4 – TF)
After 6 Seconds: Main Breaker Reclose (Shot 3, T3)
After 8 Seconds: Aux Breaker Close (Shot 3, TF)
After 2 Seconds: External Trip (PL4 – TF)
After 8 Seconds: Main Breaker Reclose (Shot 4, T4)
After 8 Seconds: Aux Breaker Close (Shot 4, TF)
After 2 Seconds: External Trip (PL4 – TF)
After 1.3 Seconds: Recloser Lockout (1.0 seconds + Tp)
4. For detail of shot numbers, etc. observe the sequence of events by viewing
Main Menu>Events
5. To perform this test again, reset the Lockout as per 79 Reset Procedure
above, then repeat the 79 test procedure.
End of 79 test.
4U The relay is 4 rack units or 7.0 inches high and approximately 12.25 inches
deep. The relay is designed for a 19-inch rack. A complete mechanical drawing
is shown, for details see “Mechanical Drawings” in Appendix G.
To install the relay the following is needed:
• 19 inch rack
• 4 - #10 screws
RJ-45 There is one front 100BASE-T Ethernet Port 119 with RJ-45 receptacle. Use
CAT5 or CAT5e straight. The rear Ethernet Ports 119 and 120 may also be
configured as 100BASE-T Ethernet Ports.
Optical ST Port 119 and port 120 in the rear panel may be configured with ST style optical
connectors if desired. These are 1300 nm 100BASE-FX optical Ethernet ports.
The transmit and receive connections are indicated on the rear panel. Use stan-
dard multi-mode cables with ST connectors for this interface.
USB There is a standard USB-B connector on the front panel. This is a USB 2.0 Full
Speed interface and can be connected to a PC with a standard USB peripheral
cable (A style to B style).
RJ-11 The relay may have an optional internal modem. Connection to this is via the
relay’s Port 118 RJ-11 receptacle. A standard telephone extension cable is to
be used.
IRIG-B Wiring The relay accepts both modulated and unmodulated IRIG-B standard time sig-
nals with or without the IEEE 1344 extensions. The IRIG-B connector on the
back of the relay is BNC type.
General:
Nominal Frequency 50 or 60 Hz
Operate Time 1.0 to 1.3 cycles at 80% reach Including output relay operation
Memory Settings and records are stored in non-volatile Records are stored in a circular buffer
memory
Protection Functions:
IEEE Dev. 21P-1, 2, 3, 4,5, 21N-1, 2, 2 x 3-phase voltage inputs for synchronizing Suitable for ring bus configurations and
3, 4,5, 27, 50BF, 50LS, 50/51/67, during reclosing integrated HV breaker auto-recloser
50N/ 51N/67, 46/50//51/67, 59,59N, 2 x3-phase current inputs for protection
60, 68, 79-1, 3, Sync Check, 81, Extra 6 currents used for recording and Pro-
Switch On To Fault, 60CTS, Weak Logic input
Infeed, Mutual compensation, vir-
tual inputs
Group Logic 8 (16 group logic statements per setting group) 5 inputs per group logic statement
Recording:
Transient (Fault) 96 s/c oscillography of all analog and external User-configurable 0.2 to 10.0 seconds
input channels Record length and 0.1 to 2 seconds
prefault length
Dynamic Swing 1 s/c phasor measurements of line positive User-configurable 60 – 120 seconds.
sequence V and I plus frequency Pre trigger time fixed at 30secs
Events 250 events circular log with 1ms resolution When event auto save is enabled, a
compressed event record is created
every 250 events.
External Inputs 9 isolated inputs (3U chassis) Optional 48, 110/125 or 220/250 Vdc
20 isolated inputs (4U chassis) nominal, externally wetted
Output Relays (contacts) 14 programmable outputs (3U chassis) and 1 Externally wetted
relay inoperative contact (N.C.) Make: 30 A as per IEEE C37.90
21 programmable outputs (4U chassis) and 1 Carry: 8 A
relay inoperative contact (N.C.) Break: 0.9 A at 125 Vdc resistive
0.35 A at 250 Vdc resistive
Front Panel Indicators 16 LEDs: 11 programmable, 5 fixed Fixed: Relay Functional, IRIG-B Func-
tional, Service Required, Test Mode,
Alarm Target (11 programmable)
Default assignments: Ground Distance,
Phase Distance, Phase Overcurrent,
Breaker Failure, Over/Under-Fre-
quency, Switch On To Fault, Communi-
cation Trip, Power Swing Trip, ProLogic
1 - 8, ProLogic 9 - 16, ProLogic 17 - 24
Front User Interface USB port and 100BASE-T Ethernet port Full Speed USB 2.0, RJ-45
Rear User Interface LAN Port 1: 100BASE Copper or Optical Copper: RJ-45, 100BASE-T
1300nm Optical: 100BASE-FX, Multimode ST
LAN Port 2: 100BASE Copper or Optical style connector
Two Serial RS-232 ports to 115 kbd modem Com port can support external modem
Environmental:
Ambient Temperature Range -40°C to 85°C for 16 hours IEC 60068-2-1/IEC 60068-2-2
-40°C to 70°C continuous LCD contrast impaired for temperatures
below -20°C and above 70° C
Insulation Test (Hi-Pot) Power supply, analog inputs, external inputs, IEC 60255-5, ANSI/IEEE C37.90
output contacts – 2 kVrms, 50/60 Hz, 1 minute
Electrical Fast Transient Tested to level 4 - 4.0 kV 2.5/5 kHz on ANSI/IEEE C37.90.1, IEC/EN 60255-
Power and I/O lines 22-4, IEC 61000-4-4
RFI Susceptibility 10 V/m modulated, 35 V/m unmodulated ANSI/IEEE C37.90.2, IEC 60255-22-3,
IEC 61000-4-3 Level 3
Conducted RF Immunity 150 kHz to 80 MHz IEC 60255-22-6 / IEC 61000-4-6 Level
3
Sinusoidal Vibration 10 Hz to 150 Hz, 1.0 octave/min, 40 sweeps IEC/EN 60255-21-1, IEC/EN 60068-26,
Class 1
Physical:
Dimensions 3U chassis: 13.2 cm height x 48.26 cm width 5.2 height x 19 width rack mount x 12.9
rack mount x 32.8 cm depth depth
4U chassis 17.7 cm x 48.3 cm x 32.8 cm 6.93" x 19 x 12.9
External Time Source Synchronized using IRIG-B input (modulated In the absence of an external time
or unmodulated) auto detect source, the relay maintains time with a
maximum 90 seconds drift per year at a
constant temperature of 25C. The relay
can detect loss of re-establishment of
external time source and automatically
switch between internal and external
time.
Impedance ±5.0% or 5 m of set value from 0.05 to 66.00 ohms secondary (0.25 to 330.00 ohms sec-
ondary, 1 A nominal)
Directional Phase Angle ±2.0° of set value of Positive Sequence Line Angle value from 25.0° to 89.0°
±0.05 Hz (df/dt)
Frequency Timer ±2.5% of set value plus 1.25 cycles to 1.75 cycles of inherent delay (fixed level)
at 2x pickup, error <40 ms (df/dt)
at 0.1 Hz/s above pickup, error <100 ms
Description
Test Test Level
Type Test Test Points
IEC/EN 61000-3-2 Power line harmonics ac power port Class D: max.1.08, 2.3, 0.431.14, 0.3,
0.77, 0.23 A.... for 2nd to nth har-
monic
IEC/EN 61000-3-3 Power line fluctuations ac power port THD/ 3%; Pst <1., Plt < 0.65
IEC/EN 60255-22-3
IEC/EN 61000-4-4 Burst (fast transient) Signal ports +/- 4 kV @2.5 kHz
IEC/EN 61000-4-6 Induced (conducted) RFI Signal ports 10 Vrms: 0.150 - 80 MHz
IEC/EN 60255-22-7 Power frequency Binary input ports: Class A Differential = 150 Vrms
IEC/EN 61000-4-8 Magnetic leld Enclosure ports 40 A/m continuous, 1000 A/m for 1 s
IEC/EN 61000-4-11 Voltage dips & interrupts ac power port 30% for 1 period, 60% for 50 periods
IEC 60255-11 Voltage dips & interrupts dc power port 100% reduction for up to 200 ms
IEC/EN 61000-4-16 Mains frequency voltage Signal ports 30 V continuous, 300 V for 1s
Note:The L-PRO 4000 is available with 5 or 1 amp current input. All current specifications change accordingly.
1.6
1.4
1.2
1 SIR 30
Time (cycles)
SIR 10
0.8
SIR 1
0.6 SIR 0.1
0.4
0.2
0
0% 20% 40% 60% 80% 100%
Fault Location (%of Z1 Reach)
1.6
1.4
1.2
1 SIR 30
Time (cycles) SIR 10
0.8
SIR 1
0.6 SIR 0.1
0.4
0.2
0
0% 20% 40% 60% 80% 100%
Fault Location (%of Z1 Reach)
Figure A.2: Ground Mho Operating Times Single Line -to-Ground Faults
1.6
1.4
1.2
1 SIR 30
Time (cycles)
SIR 10
0.8
SIR 1
0.6 SIR 0.1
0.4
0.2
0
0% 20% 40% 60% 80% 100%
Fault Location (%of Z1 Reach)
195
180
165
150
135
120
Delay error (ms)
75
60
45
30
15
0
0 1 2 3 4 5 6 7 8 9 10 11
Hz/s Pickup Multiple
195
180
165
150
135
120
Time Delay Error (ms)
75
60
45
30
15
0
0 1 2 3 4 5 6 7 8 9 10 11
Multiple of Hz/s Pickup
195
180
165
150
135
120
75
60
45
30
15
0
0 1 2 3 4 5 6 7 8 9 10 11
Multiple of Hz/s Pickup
4 0.694 ms 1.215 ms
5 0.868 ms 1.563 ms
6 1.042 ms 1.909 ms
7 1.215 ms 2.257 ms
8 1.389 ms 2.604 ms
9 1.563 ms 2.951 ms
10 1.736 ms 3.299 ms
11 1.909 ms 3.645 ms
12 2.083 ms 3.993 ms
For a setting of 6, it will take between 1.042 and 1.909 ms for an External Input
to be declared as high. The default setting is 4.
Relay Identification
Unit ID UnitID
Comments Comments
Station Number 1
Location Location
Line D245
IA3 Current 3 A
IB3 Current 3 B
IC3 Current 3 C
IA4 Current 4 A
IB4 Current 4 B
IC4 Current 4 C
1 EI Spare 1
2 EI Spare 2
3 EI Spare 3
4 EI Spare 4
5 EI Spare 5
6 EI Spare 6
7 EI Spare 7
8 EI Spare 8
9 EI Spare 9
VI 1 Virtual Input 1
VI 2 Virtual Input 2
VI 3 Virtual Input 3
VI 4 Virtual Input 4
VI 5 Virtual Input 5
VI 6 Virtual Input 6
VI 7 Virtual Input 7
VI 8 Virtual Input 8
VI 9 Virtual Input 9
VI 10 Virtual Input 10
VI 11 Virtual Input 11
VI 12 Virtual Input 12
VI 13 Virtual Input 13
VI 14 Virtual Input 14
VI 15 Virtual Input 15
VI 16 Virtual Input 16
VI 17 Virtual Input 17
VI 18 Virtual Input 18
VI 19 Virtual Input 19
VI 20 Virtual Input 20
VI 21 Virtual Input 21
VI 22 Virtual Input 22
VI 23 Virtual Input 23
VI 24 Virtual Input 24
VI 25 Virtual Input 25
VI 26 Virtual Input 26
VI 27 Virtual Input 27
VI 28 Virtual Input 28
VI 29 Virtual Input 29
VI 30 Virtual Input 30
System Parameters
Record Length
Line Parameters
K0 Override Disabled
Scheme Selector
1Ph/3Ph for 3Ph Dropout Delay (TD4) 25.000 seconds s 0.100 to 999.000
1Ph/3Ph for 1Ph Pickup Delay (TL5) 0.100 seconds s 0.100 to 5.000
1Ph/3Ph for 1Ph Dropout Delay (TD5) 25.000 seconds s 0.100 to 999.000
POTT Current Reversal Pickup Delay (TL1) 0.000 seconds s 0.000 to 0.500
POTT Current Reversal Dropout Delay (TD1) 0.100 seconds s 0.000 to 0.500
DCB Scheme Zone 2 Pickup Delay (TL2) 0.050 seconds s 0.005 to 0.500
DCB Scheme Receiver Dropout Delay (TD2) 0.100 seconds s 0.000 to 0.500
Action <diabled>
Direction Forward
Action <diabled>
Direction Reverse
52 - Breaker Status
Directional Element
Protection Summary
Type Quadrilateral
Type Quadrilateral
Type Quadrilateral
Type Quadrilateral
Type Quadrilateral
Type Quadrilateral
Type Quadrilateral
Type Quadrilateral
Type Quadrilateral
Type Quadrilateral
68 Off
50 Pickup 2.5 A
59 3V0 5.0 V
59 Main Disabled
Default Gate OR
59 Aux Disabled
Default Gate OR
27 Main Disabled
27 Aux Disabled
60 Disabled
I1 Blocking 7.5 A
81-1 Disabled
81-2 Disabled
81-3 Disabled
81-4 Disabled
50 Disabled
51 Disabled
50N Disabled
51N Disabled
46-50 Disabled
46-51 Disabled
Type Quadrilateral
Type Quadrilateral
Type Quadrilateral
Type Quadrilateral
Type Quadrilateral
Type Quadrilateral
Type Quadrilateral
Type Quadrilateral
Type Quadrilateral
Type Quadrilateral
Mode Off
79-3Ph - Recloser
79-3Ph Disabled
Number of Shots 1
79-1Ph - Recloser
79-1Ph Disabled
Number of Shots 1
59 - Overvoltage
59 Main Disabled
Gate Switch OR
59 Auxiliary Disabled
Gate Switch OR
A 0.14 - -
B 0 - -
p 0.02 - -
TR 13.5 - -
27 - Undervoltage
27 Main Disabled
27 Auxiliary Disabled
60 Disabled
60 CT Supervision
81-1 Disabled
81-2 Disabled
81-3 Disabled
81-4 Disabled
50 Disabled
51 Disabled
A 0.14 - -
B 0 - -
p 0.02 - -
TR 13.5 - -
50N Disabled
51N Disabled
A 0.14 - -
B 0 - -
p 0.02 - -
TR 13.5 - -
46-50 Disabled
46-51 Disabled
A 0.14 - -
B 0 - -
p 0.02 - -
TR 13.5 - -
Z Circle Trigger
ProLogic 1 [ProLogic 1]
[ProLogic 1] Disabled
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
ProLogic 2 [ProLogic 2]
[ProLogic 2] Disabled
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
ProLogic 3 [ProLogic 3]
[ProLogic 3] Disabled
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
ProLogic 4 [ProLogic 4]
[ProLogic 4] Disabled
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
ProLogic 5 [ProLogic 5]
[ProLogic 5] Disabled
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
ProLogic 6 [ProLogic 6]
[ProLogic 6] Disabled
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
ProLogic 7 [ProLogic 7]
[ProLogic 7] Disabled
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
ProLogic 8 [ProLogic 8]
[ProLogic 8] Disabled
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
ProLogic 9 [ProLogic 9]
[ProLogic 9] Disabled
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Operator 1
Operator 2
Operator 3
Operator 4
Operator 5
Main Processor The MPB has two processor sub-systems which control the operation of the en-
Board (MPB) tire relay: the DSP processor and the control processor. The DSP sub-system
interfaces to the RAIB, the DIB and the OCB and manages the protection fea-
tures of the relay. The control processor manages the user interface and system
control features of the relay. Both subsystems operate independently of each
other and will continue to function even if the other sub-system fails.
The MPB provides the following functionality:
• DSP processor subsystem which interfaces to the RAIB, the DIB and the
OCB and manages the protection features of the relay, with:
• The floating point DSP to provide fast capture and manipulation of
data.
• RAM and reprogrammable non-volatile Flash memory. Allows oper-
ation independent of the control processor and supports field software
updates.
• A control processor subsystem which manages the user interface and sys-
tem control features of the relay, with
• RAM and reprogrammable non-volatile Flash memory. Allows oper-
ation independent of the DSP processor and supports field software
upgrades.
• Settings and recordings stored in non-volatile memory.
• Runs a Real Time Operating System (RTOS).
• Provides Ethernet ports and RS-232 ports for modem, SCADA, COM
and USB interfaces.
• A time synchronism processor with automatic detection of modulated and
un-modulated IRIG-B
• A high speed link is provided between the DSP and control processor sub-
systems.
• Sophisticated fault detection and “watchdog” recovery hardware
• The MPB also provides the power supply for the entire unit. The power
supply operating range is 48-250 Vdc, 100-240 Vac, +/-10%, 50/60 Hz.
This wide operating range provides easier installation by eliminating pow-
er supply ordering options
Digital Input This board provides 9 digital input channels. Inputs are optically isolated, ex-
Board (DIB) ternally wetted, and factory preset to the customer’s requested voltage level of
48, 110/125 or 220/250 Vdc. This board interfaces to the MPB.
Rear Panel The RPCB provides the relay with two RS-232 ports (Ports 122 and 123,
Comm Board DB9F), IRIG-B time synchronization input (Port 121, male BNC), internal
(RPCB) modem connection (Port 118, RJ-11) and two Ethernet ports (Ports 119 and
120, RJ-45 or 100BASE-FX MM 1300nm ST, depending upon order specifi-
cation). The RPCB interfaces to the MPB. Port 119 is the exception in that it
interfaces to the GFPCB where it shares an internal switch with the front panel
LAN port. The switch then interfaces to the MPB.
Output Contact The LOCB provides 14 normally open contact outputs for relaying, alarms and
Board (LOCB) control. It also provides one normally closed output contact for relay inopera-
tive indication. This board interfaces to the MPB.
Digital Input/ The DIGIO provides 11 digital input channels. Inputs are optically isolated, ex-
Output Board ternally wetted, and factory preset to the customer's requested voltage level of
(DIGIO) 48, 110/125 or 220/250 Vdc. The DIGIO also provide 7 normally open contact
outputs for relaying, alarms and control. This board interfaces to the MPB.
Relay AC Each relay has 3 RASBs. Two RASBs have 3 voltage transformer inputs and
Analog Sensor 3 current transformer inputs while the third RASB has 6 current transformer
Boards (RASB) inputs. These boards provide 12 current and 6 voltage ac analog measurement
inputs. The RASBs interface to the RAIB.
Relay AC The RAIB provides the analog to digital conversion of the 12 ac analog current
Analog Input inputs and the 6 ac analog voltage inputs. The sample rate is fixed at 96 sam-
Board (RAIB) ples/cycle. Each channel is simultaneously sampled using 16-bit analog to dig-
ital converters. The digitized data is sent to the MPB for processing and
implementation of the protection algorithms.
• A time synchronism processor with automatic detection of modulated and
un-modulated IRIG-B
• A high speed link is provided between the DSP and control processor sub-
systems.
• Sophisticated fault detection and “watchdog” recovery hardware
• The MPB also provides the power supply for the entire unit. The power
supply operating range is 48-250 Vdc, 100-240 Vac, +/-10%, 50/60 Hz.
This wide operating range provides easier installation by eliminating pow-
er supply ordering options
Graphics Front The GFPCB provides the front panel USB and Ethernet ports, the front panel
Panel Comm status LEDs and interfaces the MPB to the FPDB. The MPB controls the state
Board (GFPCB) of the LEDs.
Graphics Front The GFPDB provides the 240x128 monochrome graphics front panel display
Panel Display and the keypad. The keypad is used to navigate the menus on the display to
Board (GFPDB) control relay operation by a local user.
21P1 ABC 12.3km:Trip The possible phase information for 21P1–21P5 will be:
21P2 ABC 12.3km:Trip • AB
21P3 ABC 12.3km:Trip • BC
21P4 ABC 12.3km:Trip • CA
21P5 ABC 12.3km:Trip • AB, BC
• AB, CA
• CA, BC
• ABC
• ABG
• BCG
• CAG
• ABGBC
• BCGCA
• CAGAB
• ABCG
21N1 AG 12.3km:Trip The possible phase information for 21N1–N5 will be:
21N2 AG 12.3km:Trip • AG
21N3 AG 12.3km:Trip • BG
21N4 AG 12.3km:Trip • CG
21N5 AG 12.3km:Trip • ABG
• BCG
• CAG
• ABCG
21P2 ABC 12.3km:Alarm The possible phase information for 21P2–21P5 will be:
21P3 ABC 12.3km:Alarm • AB
21P4 ABC 12.3km:Alarm • BC
21P5 ABC 12.3km:Alarm • CA
• AB, BC
• AB, CA
• CA, BC
• ABC
• ABG
• BCG
• CAG
• ABGBC
• BCGCA
• CAGAB
• ABCG
21N2 AG 12.3km:Alarm The possible phase information for 21N2–N5 and 50N/51N will be:
21N3 AG 12.3km:Alarm • AG
21N4 AG 12.3km:Alarm • BG
21N5 AG 12.3km:Alarm • CG
51N AG 12.3km:Trip • ABG
50N AG 12.3km:Trip • BCG
• CAG
• ABCG
46-51: Trip
46-50: Trip
51N: Alarm
46-51: Alarm
POTT (WI) 12.3 km: Trip Weak Infeed (WI) is not available unless POTT is selected.
PUTT: Send
POTT: Send
POTT: Send (WI) Weak Infeed (WI) is not available unless POTT is selected.
DCB: Send
Extern Input Name: EIn: High External input names are user assigned
Extern Input Name: EIn: Low External input names are user assigned
Output Contacts: EIn: High Output Contact Names are user assigned
Output Contacts: EIn: High Output Contacts names are user assigned
Com-Aided (Z2,Wi): Send Scheme types: WI, Z2, Z2 & WI, Z2 is Zone 2 POTT and WI is
Weak Infeed
81-1: Trip
81-2: Trip
81-3: Trip
81-4: Trip
79 Lead Lockout: High Recloser shot count has expired and reclosing attempts are
blocked.
79 Main Reclose: shot n Recloser Main circuit breaker close attempt where n equals the
shot count.
79 Follow Reclose: shot n Recloser Aux. circuit breaker close attempt where n equals the
shot count.
Self Check: DC Ch.n: O/P Block Continuous dc level on Ch. n, where n = 1 to 18. Relay is blocked.
Manual Settings Load request, activate SGn Manual or user-initiated settings change.
Changed Active Group from x to y This happens when relay changes setting group. Automatic group
Logic n logic initiated setting group change
User changed Active Group from x to y This happens when the relay changes setting group. User initiated
setting group change
Unit Recalibrated
Unit restarted
User logged In
Note: For either of the above cases the DSP controller functions con-
tinue with normal auxiliary relay outputs provided that DSP failure or
Self Check Fail: Block has not occurred.
Self Check Fail The DSP has an algorithm that detects continuous dc levels on the analog in-
due to DC puts and initiates alarms and relay output contact blocking when the measured
Offset Detector dc level exceeds the Alarm or Block level. The Alarm level is intended to pro-
vide an early indication of a problem. The Block level blocks the relay from
false-tripping by preventing any output contact from closing. The Relay Func-
tional LED turns off, but the protection functions will operate normally, with
the exception that the output contacts will not be allowed to close. The Relay
Inoperative contact will close for a Block condition. The following table de-
scribes all the Alarm/Block indication functions
Action Condition
Alarm Block
The Self Check Fail signal, which is available in the Output Matrix, TUI me-
tering and SCADA, can be used to signal an alarm. Note that if this signal is
mapped to an output contact, the contact which it is mapped to will only be
closed for an alarm condition. If the relay is in the Block condition, the Relay
Inoperative contact must be used to signal an alarm.
The status of the Self Check Fail is available through the SCADA services pro-
vided by the relay. The digital signal Self Check Fail will indicate that DSP has
detected a continuous dc level and the analog metering value Self Check Fail
Parameter is used to indicate which condition, Alarm or Block. The failure
types and which analog values they are associated with are described in the ta-
ble below. Both signals are available in DNP and Modbus.
0 Normal
1 Alarm
2 Block
The Alarm condition is allowed to reset if the continuous dc level drops below
the pickup level. The Block condition has no reset level. If power is cycled to
the relay it will go into its normal state until the continuous dc level is detected
again.
Self Check Fail appears as “Aux. Failure Alarm” in the settings ver-
sions before V 10.
L-PRO Clock Time (UTC). Read all in same query to ensure consistent time reading data
Time of Acquisition (UTC). Read all in same query to ensure consistent time reading data
P 40306 MW 10
Q 40307 Mvar 10
Only the “hold readings” coil can be forced. When active, this coil locks all coil, input and holding register readings simultaneously
at their present values. When inactive, coil, input and holding register values will read their most recently available state.
Return Query Data (Subfunction 00) This provides an echo of the submitted message.
Restart Comm. Option (Subfunction 01) This restarts the Modbus communications process.
Force Listen Only Mode (Subfunction 04) No response is returned. IED enters “Listen Only” mode. This
mode can only be exited by the “Restart Comm. Option” com-
mand.
A fixed response is returned by the IED, including system model, version and issue numbers.
All L-PRO detector event messages displayed in the Event Log are available via Modbus. This includes fault location information.
The following controls are available.
Refresh Event List (Function Code 6, address 40513): Fetches the latest events from the relay's event log and
makes them available for Modbus access. The most recent event becomes the current
event available for reading.
Acknowledge Current Event and (Function Code 6, address 40514): Clears the current event from the read registers and
Get Next Event places the next event into them. An acknowledged event is no longer available for reading.
Get Next Event (Function Code 6, address 40515): Places the next event in the read registers without
acknowledging the current event. The current event will reappear in the list when Refresh
Event List is used.
Size of Current Event Message (Function Code 3, address 40516): Indicates the number of 16 bit registers used to contain
the current event. Event data is stored with 2 characters per register. A reading of zero indi-
cates that there are no unacknowledged events available in the current set. (NB. The
Refresh Event List function can be used to check for new events that have occurred since
the last Refresh Event List.)
Fault Location Event (Function Code 3, address 40517): Identifies fault location events. These events are identi-
fied by “FL” in this register. Non-fault location events contain “” in this location.
Read Event Message (Function Code 3, addresses 40518 – 40570): Contains the current message. Two.
ASCII characters are packed into each 16 bit register. All unused registers in the set are set
to 0.
Fault Information – Type (Function Code 3, address 40571): If the current event is a fault location event, this register
contains the type of fault.
The following type bitmap:
0x0001 – Phase A
0x0002 – Phase B
0x0004 – Phase C
0x0008 – Ground
Any number of the flags may be set for a given fault. If the relay could not determine the
fault type, then the register will not have any flags set and will read 0x0000.
Fault Information – Fault Dis- (Function Code 3, address 40572): If the current event is a fault location event, this register
tance contains the distance to the fault. It is scaled up by a factor of 10. The units are the same as
the units set in the relay configuration.
Fault Information – Time of Fault (Function Code 3, addresses 40573 to 40576): If the current event is a fault location event,
these registers contain the time of the fault in seconds since 1970. Each of these 16-bit reg-
isters contains an 8-bit portion of a 32-bit time value. Register 40573 contains the upper
most 8 bits, and register 40576 contains the lowest 8 bits.
If configurable,
1.1 Device Identification Capabilities Current Value
list methods
1.1.9 Notable Additions: • Start-stop (qualifier codes 0x00 and 0x01), limited
quantity (qualifier codes 0x07 and 0x08) and indi-
ces (qualifier codes 0x17 and 0x28) for Binary In-
puts, Binary Outputs and Analog Inputs (object
groups 1, 10 and 30)
• 32-bit and 16-bit Analog Inputs with and without
flag (variations 1, 2, 3 and 4)
• Analog Input events with time (variations 3 and 4)
• Fault Location information as analog readings
• Event Log messages as Object groups 110 and
111
If configurable,
1.1 Device Identification Capabilities Current Value
list methods
If configurable,
1.2 Serial Connections Capabilities Current Value
list methods
1.2.2 Serial Connection Asynchronous - 8 Data Bits, 1 Start Bit, 1 Stop Not configured L-PRO Offliner
Parameters: Bit, No Parity for DNP
Other, explain - Asynchronous with selectable
parity
If configurable,
1.2 Serial Connections Capabilities Current Value
list methods
If configurable,
1.3 IP Networking Capabilities Current Value
list methods
1.3.2 Type of End Point: TCP Initiating (Master Only) Not configured L-PRO Offliner
TCP Listening (Outstation Only) for DNP
TCP Dual (required for Masters)
UDP Datagram (required)
1.3.6 Accepts TCP Allows all (show as *.*.*.* in 1.3.7) Limits based on L-PRO Offliner
Connections or UDP Limits based on an IP address an IP address
Datagrams from: Limits based on list of IP addresses
Limits based on a wildcard IP address
Limits based on list of wildcard IP addresses
Other validation, explain_________________
1.3.8 TCP Listen Port Not Applicable (Master w/o dual end point) 20,000 L-PRO Offliner
Number: Fixed at 20,000
Configurable, range 1025 to 32737
Configurable, selectable from ____,____,____
Configurable, other, describe______________
1.3.9 TCP Listen Port Not Applicable (Outstation w/o dual end point) NA
Number of remote Fixed at 20,000
device: Configurable, range _______ to _______
Configurable, selectable from ____,____,____
Configurable, other, describe______________
If configurable,
1.3 IP Networking Capabilities Current Value
list methods
1.3.14 Multiple master Supports multiple masters (Outstations only) Method 1 (based L-PRO Offliner
connections If supported, the following methods may be on IP address)
(Outstations Only): used:
Method 1 (based on IP address) - required
Method 2 (based on IP port number) -
recommended
Method 3 (browsing for static data) - optional
If configurable,
1.4 Link Layer Capabilities Current Value
list methods
If configurable,
1.5 Application Layer Capabilities Current Value
list methods
1.5.8 Supports mixing object Not applicable - controls are not supported Analog Outputs
groups (AOBs, CROBs Yes not supported
and Data Sets) in the No
same control request:
1.6.6 Event Buffer • Single buffer for the Object Groups 2 and 32, size
Organization: 200.
• Separate buffer for the Object Group 111, size
100.
• Separate buffer for the Fault Locator events, size
100.
If configurable,
1.8 Outstation Performance Capabilities Current Value
list methods
Capabilities and The following tables identify the capabilities and current settings for each
Current DNP3 data type. Each data type also provides a table defining the data points
Settings for available in the device, default point lists configuration and a description of
Device how this information can be obtained in case of customized point configura-
Database tion.
2.1.5 Definition of Binary Fixed, list shown in table below Complete list is L-PRO Offliner
Input Point List: Configurable shown in the
Other, explain_____________________ table below;
points excluded
from the default
configuration are
marked with ‘*’
2. Binary Input data points are user selectable; the data points avail-
Notes
able in the device for any given Binary Input point selection can be
obtained through the L-PRO Offliner software (see SCADA Setting
Summary).
2.2.1 Minimum pulse time Fixed at 0,000 ms (hardware may limit this
allowed with Trip, further)
Close, and Pulse On Based on point Index (add column to table
commands: below)
2.2.2 Maximum pulse time Fixed at 0,000 ms (hardware may limit this
allowed with Trip, further)
Close, and Pulse On Based on point Index (add column to table
commands: below)
2.2.5 Event Variation Variation 1 - without time Not supported L-PRO Offliner
reported when variation Variation 2 - with absolute time (See Note 2
0 requested: Based on point Index (add column to table below)
below)
2.2.6 Command Event Variation 1 - without time Not supported L-PRO Offliner
Variation reported when Variation 2 - with absolute time (See Note 2
variation 0 requested: Based on point Index (add column to table below)
below)
2.2.7 Event reporting mode: Only most recent Not supported L-PRO Offliner
All events (See Note 2
below)
2.2.10 Definition of Binary Fixed, list shown in table below Complete list is L-PRO Offliner
Output Status/Control Configurable shown in the
relay output block Other, explain_____________________ table below;
(CROB) Point List: points excluded
from the default
configuration are
marked with ‘*’
2. Events are not supported for Binary Outputs (group 10), but most of Binary
Output points can be mapped to Binary Inputs (group 2) with full Event and Class
Data support. See L-PRO Offliner/DNP Configuration/Point Map screen for com-
plete point lists and configuration options.
NOTES
3. Virtual Inputs (default Binary Output points 94-123) can be used to control re-
lay output contacts. See L-PRO Offliner/Setting Group X/Output Matrix screen
for configuration options.
4. Binary Output data points are user selectable; the data points available in the
device for any given Binary Output point selection can be obtained through the
L-PRO Offliner software (see SCADA Setting Summary).
Default Class
Supported Control Operations Assigned to Events
(1, 2, 3 or none)
Cancel Currently Running Operation
Direct Operate - No Ack
Latch On / NUL
Select/Operate
Direct Operate
Point Index
Count > 1
Pulse Off
Close
Trip
Default Class
Supported Control Operations Assigned to Events
(1, 2, 3 or none)
Latch On / NUL
Select/Operate
Direct Operate
Point Index
Count > 1
Pulse Off
Close
Trip
19 Virtual Input 6 Y Y Y Y - Y Y - - - - Inactive Active None None Pulse duration fixed
at 1 s
44 Get Next Fault Y Y Y Y - Y - - - - - Inactive Active None None Pulse duration fixed
Event at 1 s
Default Class
Supported Control Operations Assigned to Events
(1, 2, 3 or none)
Latch On / NUL
Select/Operate
Direct Operate
Point Index
Count > 1
Pulse Off
Close
Trip
46* Output Contact 16 - - - - - - - - - - - Inactive Active None None
2.3.7 Definition of Analog Fixed, list shown in table below Complete list is L-PRO Offliner
Input Point List: Configurable shown in the
Other, explain_____________________ table below;
points excluded
from the default
configuration are
marked with ‘*’
2. Nominal values in calculations for the following table are based on 69V sec-
ondary voltage * PT ratio for voltage channels, and either 1 A or 5A secondary
current * CT ratio for current channels dependent upon the format of CT installed
in the L-PRO.
3. Analog Input data points are user selectable; the data points available in the
device for any given Analog Input point selection can be obtained through the L-
PRO Offliner software (see SCADA Setting Summary).
4. When a fault location event is available, Binary Input Fault Information Avail-
able (default point index 39) is asserted while there are still fault location events
in the buffer (size 100). When a Pulse or Latch is received for the Binary Output
Get Next Fault Event (default point index 44, previous state is not important),
NOTES fault event information is put into the Analog Inputs. If there is no fault location
event available when the Binary Output is pulsed, the fault type is set to zero.
Not all fault location events are reported trough DNP. In a burst of fault locations
from a fault, only the first processed event is available through DNP, all other
events within the following 100 ms interval are ignored. Outside 100 ms from the
processed fault location event, the system accepts another fault location event
and performs the same filtering. In addition, only fault location events generated
by trip elements are available.
The following bitmap id used for the fault information Type points:
0x0001 Phase A
0x0002 Phase B
0x0004 Phase C
0x0008 Ground
Default Class
Assigned to Multiplier Resolutionc
Name
Events
Minimum Maximumd (default/ (range))
Offset Units (default/ Description
(1, 2, 3 or none) maximal)
1 Line Va Angle 2 -18,000 18,000 0.1 / (0.01 - 1.0) 0.0 Degrees 0.1 / 0.01
3 Line Vb Angle 2 -18,000 18,000 0.1 / (0.01 - 1.0) 0.0 Degrees 0.1 / 0.01
5 Line Vc Angle 2 -18,000 18,000 0.1 / (0.01 - 1.0) 0.0 Degrees 0.1 / 0.01
7 Line Ia Angle 2 -18,000 18,000 0.1 / (0.01 - 1.0) 0.0 Degrees 0.1 / 0.01
9 Line Ib Angle 2 -18,000 18,000 0.1 / (0.01 - 1.0) 0.0 Degrees 0.1 / 0.01
Default Class
Assigned to Multiplier Resolutionc
Name
Events
Minimum Maximumd (default/ (range))
Offset Units (default/ Description
(1, 2, 3 or none) maximal)
11 Line Ic Angle 2 -18,000 18,000 0.1 / (0.01 - 1.0) 0.0 Degrees 0.1 / 0.01
13 I2a Angle 2 -18,000 18,000 0.1 / (0.01 - 1.0) 0.0 Degrees 0.1 / 0.01
15 I2b Angle 2 -18,000 18,000 0.1 / (0.01 - 1.0) 0.0 Degrees 0.1 / 0.01
17 I2c Angle 2 -18,000 18,000 0.1 / (0.01 - 1.0) 0.0 Degrees 0.1 / 0.01
19 I3a Angle 2 -18,000 18,000 0.1 / (0.01 - 1.0) 0.0 Degrees 0.1 / 0.01
21 I3b Angle 2 -18,000 18,000 0.1 / (0.01 - 1.0) 0.0 Degrees 0.1 / 0.01
23 I3c Angle 2 -18,000 18,000 0.1 / (0.01 - 1.0) 0.0 Degrees 0.1 / 0.01
27 I4b Angle 2 -18,000 18,000 0.1 / (0.01 - 1.0) 0.0 Degrees 0.1 / 0.01
29 I4c Angle 2 -18,000 18,000 0.1 / (0.01 - 1.0) 0.0 Degrees 0.1 / 0.01
31 Bus Va Angle 2 -18,000 18,000 0.1 / (0.01 - 1.0) 0.0 Degrees 0.1 / 0.01
33 Bus Vb Angle 2 -18,000 18,000 0.1 / (0.01 - 1.0) 0.0 Degrees 0.1 / 0.01
35 Bus Vc Angle 2 -18,000 18,000 0.1 / (0.01 - 1.0) 0.0 Degrees 0.1 / 0.01
36 Pos Seq Fre- 2 0 Configurable 0.01 / (0.001 - 1.0) 0.0 Hz 0.01 / 0.001
quency
39 Pos Seq Voltage 2 0 Configurable 0.1 / (0.00001- 1.0) 0.0 kV 0.1 / 0.00001
40 Pos Seq Current 2 0 Configurable 1.0 / (0.01 - 1000) 0.0 A 1.0 / 0.01
41* Line Za Magnitude 2 0 Configurable 1.0 / (0.01 - 1000) 0.0 Om 1.0 / 0.01
42* Line Za Angle 2 -18,000 18,000 0.1 / (0.01 - 1.0) 0.0 degrees 0.1 / 0.01
43* Line Zb Magnitude 2 0 Configurable 1.0 / (0.01 - 1000) 0.0 Om 1.0 / 0.01
44* Line Zb Angle 2 -18,000 18,000 0.1 / (0.01 - 1.0) 0.0 degrees 0.1 / 0.01
45* Line Zc Magnitude 2 0 Configurable 1.0 / (0.01 - 1000) 0.0 Om 1.0 / 0.01
46* Line Zc Angle 2 -18,000 18,000 0.1 / (0.01 - 1.0) 0.0 degrees 0.1 / 0.01
Default Class
Assigned to Multiplier Resolutionc
Name
Events
Minimum Maximumd (default/ (range))
Offset Units (default/ Description
(1, 2, 3 or none) maximal)
54 Fault Information - none 0 65,535 1.0 0.0 NA 1.0 See description below on
DNP Time (High 16 how to access Fault Informa-
bits) tion.
60 Ia Summated 2 -18,000 18,000 0.1 / (0.01 - 1.0) 0.0 Degrees 0.1 / 0.01
Angle
64 Ic Summated 2 -18,000 18,000 0.1 / (0.01 - 1.0) 0.0 Degrees 0.1 / 0.01
Angle
a. The minimum and maximum transmitted values are the lowest and highest values that the outstation will report in DNP analog input
objects. These values are integers if the outstation transmits only integers. If the outstation is capable of transmitting both integers
and floating-point, then integer and floating-point values are required for the minimums and maximums.
For example, a pressure sensor is able to measure 0 to 500 kPa. The outstation provides a linear conversion of the sensor's output
signal to integers in the range of 0 to 25000 or floating-point values of 0 to 500.000. The sensor and outstation are used in an ap-
plication where the maximum possible pressure is 380 kPa. For this input, the minimum transmitted value would be stated as 0 /
0.0 and the maximum transmitted value would be stated as 19000 / 380.000.
b. The scaling information for each point specifies how data transmitted in integer variations (16 bit and 32 bit) is converted to engi-
neering units when received by the Master (i.e. scaled according to the equation: scaled value = multiplier * raw + offset). Scaling
is not applied to Floating point variations since they are already transmitted in engineering units.
c. Resolution is the smallest change that may be detected in the value due to quantization errors and is given in the units shown in the
previous column. This parameter does not represent the accuracy of the measurement.
d. Maximal values are calculated as (2 * Configured Nominal / Multiplier) for voltage channels and as (40 * Configured Nominal /
Multiplier) for current channels (see Note 2 above for the nominal definitions).
* Object 110 and 111 are Octet String Object used to provide access to the
Event Log text of the relay. Object 110 always contains the most recent event
in the relay. Object 111 is the corresponding change event object.
As stated in the DNP specifications, the variation of the response object repre-
sents the length of the string. The string represents the ASCII values of the
event text. The first two characters in the string can be used to quickly identify
fault location events. Fault locator events begin with the characters "FL"
(0x46, 0x4C hex). The following example shows a fault distance event re-
turned through either of the octet string objects:
Event Message:
0x69 0x70
Implementation The following implementation table identifies which object groups and varia-
Table tions, function codes and qualifiers the device supports in both requests and re-
sponses. The Request columns identify all requests that may be sent by a
Master, or all requests that must be parsed by an Outstation. The Response col-
umns identify all responses that must be parsed by a Master, or all responses
that may be sent by an Outstation.
The implementation table must list all functionality required by the device wheth-
er Master or Outstation as defined within the DNP3 IED Conformance Test Pro-
cedures. Any functionality beyond the highest subset level supported is
NOTE
indicated by highlighted rows. Any Object Groups not provided by an outstation
or not processed by a Master are indicated by strikethrough (note these Object
Groups will still be parsed).
Request Response
DNP Object Group & Variation
Outstation parses Outstation can issue
1 0 Binary Input - Any Variation 1 (read) 06 (no range, or all) 129 (response) 00, 01 (start-stop)
00, 01 (start-stop)
07, 08 (limited qty)
17, 28 (index)
1 1 Binary Input - Packed format 1 (read) 06 (no range, or all) 129 (response) 00, 01 (start-stop)
00, 01 (start-stop)
07, 08 (limited qty)
17, 28 (index)
1 2 Binary Input - With flags 1 (read) 06 (no range, or all) 129 (response) 00, 01 (start-stop)
00, 01 (start-stop)
07, 08 (limited qty)
17, 28 (index)
2 0 Binary Input Event - Any Variation 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty)
2 1 Binary Input Event - Without time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty) 130 (unsol. resp)
2 2 Binary Input Event - With absolute 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
time 07, 08 (limited qty) 130 (unsol. resp)
2 3 Binary Input Event - With relative 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
time 07, 08 (limited qty) 130 (unsol. resp)
10 0 Binary Output - Any Variation 1 (read) 06 (no range, or all) 129 (response) 00, 01 (start-stop)
00, 01 (start-stop)
07, 08 (limited qty)
17, 28 (index)
10 2 Binary Output - Output Status with 1 (read) 06 (no range, or all) 129 (response) 00, 01 (start-stop)
flag 00, 01 (start-stop)
07, 08 (limited qty)
17, 28 (index)
12 1 Binary Command - Control relay 3 (select) 17, 28 (index) 129 (response) Echo of request
output block (CROB) 4 (operate)
5 (direct op)
6 (dir. op, no ack)
Request Response
DNP Object Group & Variation
Outstation parses Outstation can issue
30 0 Analog Input - Any Variation 1 (read) 06 (no range, or all) 129 (response) 00, 01 (start-stop)
00, 01 (start-stop)
07, 08 (limited qty)
17, 28 (index)
30 1 Analog Input - 32-bit with flag 1 (read) 06 (no range, or all) 129 (response) 00, 01 (start-stop)
00, 01 (start-stop)
07, 08 (limited qty)
17, 28 (index)
30 2 Analog Input - 16-bit with flag 1 (read) 06 (no range, or all) 129 (response) 00, 01 (start-stop)
00, 01 (start-stop)
07, 08 (limited qty)
17, 28 (index)
30 3 Analog Input - 32-bit without flag 1 (read) 06 (no range, or all) 129 (response) 00, 01 (start-stop)
00, 01 (start-stop)
07, 08 (limited qty)
17, 28 (index)
30 4 Analog Input - 16-bit without flag 1 (read) 06 (no range, or all) 129 (response) 00, 01 (start-stop)
00, 01 (start-stop)
07, 08 (limited qty)
17, 28 (index)
32 0 Analog Input Event - Any Variation 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty)
32 1 Analog Input Event - 32-bit without 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
time 07, 08 (limited qty) 130 (unsol. resp)
32 2 Analog Input Event - 16-bit without 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
time 07, 08 (limited qty) 130 (unsol. resp)
32 3 Analog Input Event - 32-bit with time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty)
32 4 Analog Input Event - 16-bit with time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty)
40 0 Analog Output Status - Any Varia- 1 (read) 06 (no range, or all) 129 (response)
tion
Request Response
DNP Object Group & Variation
Outstation parses Outstation can issue
41 2 Analog Output - 16-bit 3 (select) 17, 28 (index) 129 (response) Echo of request
4 (operate)
5 (direct op)
6 (dir. op, no ack)
50 1 Time and Date - Absolute time 2 (write) 07 (limited qty = 1) 129 (response)
51 1 Time and Date CTO - Absolute time, 129 (response) 07 (limited qty)
synchronized 130 (unsol. resp) (qty = 1)
51 2 Time and Date CTO - Absolute time, 129 (response) 07 (limited qty)
unsynchronized 130 (unsol. resp) (qty = 1)
60 1 Class Objects - Class 0 data 1 (read) 06 (no range, or all) 129 (response) 00, 01 (start-stop)
60 2 Class Objects - Class 1 data 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
60 3 Class Objects - Class 2 data 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
60 4 Class Objects - Class 3 data 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
110 0 Octet string 1 (read) 06 (no range, or all) 129 (response) 07 (limited qty)
111 0 Octet string event 1 (read) 06 (no range, or all) 129 (response) 07 (limited qty)
12.742
12.062
.326
17.953 .215
1.250
L-PRO LINE PROTECTION RELAY RELAY FUNCTIONAL
(typ)
IRIG-B FUNCTIONAL
SERVICE REQUIRED
ALARM
TEST MODE
2.250
5.180
(119) (150) (typ)
100BASE-T USB
Appendix G Mechanical Drawings
4.750
X (typ)
Appendix G-1
17.410
Appendix G-2
Appendix G Mechanical Drawings
12.742
12.062
.326
18.547 .212
.215
17.953
1.250
(typ)
IRIG-B FUNCTIONAL
SERVICE REQUIRED
ALARM
4.000
TEST MODE 6.930
(119) (150) (typ)
100BASE-T USB
X 6.500
(typ)
D02706R02.30
D02706R02.30
48 125 250 V 48 125 250 V 48 125 250 V 48 125 250 V 48 125 250 V 48 125 250 V 48 125 250 V 48 125 250 V 48 125 250 V 121
External 118 TX 119 RX TX 120 RX 122 123
Inputs 1 2 3 4 5 6 7 8 9
200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235
Input
1A 5A 50Hz 60Hz
Main AC Line Currents Aux. AC Line Currents AC Current Inputs (Record Only) Aux. AC Volts Unused Main AC Volts Unused
I 1A I 1B I 1C I 2A I 2B I 2C I 3A I 3B I 3C I 4A I 4B I 4C VA VB VC N VA VB VC N
300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 Power Supply
±10%
48 to 250 Vdc
100 to 240 Vac
Made in Canada 336 337
Appendix H Rear Panel Drawings
Appendix H-1
Appendix H-2
Appendix H Rear Panel Drawings
48 125 250 V 48 125 250 V 48 125 250 V 48 125 250 V 48 125 250 V 48 125 250 V 48 125 250 V 48 125 250 V 48 125 250 V 121
External 118 TX 119 RX TX 120 RX 122 123
Inputs 1 2 3 4 5 6 7 8 9
200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235
Input
1A 5A 50Hz 60Hz
Main AC Line Currents Aux. AC Line Currents AC Current Inputs (Record Only) Aux. AC Volts Unused Main AC Volts Unused
I 1A I 1B I 1C I 2A I 2B I 2C I 3A I 3B I 3C I 4A I 4B I 4C VA VB VC N VA VB VC N
300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 Power Supply
±10%
48 to 250 Vdc
100 to 240 Vac
Made in Canada 336 337
D02706R02.30
D02706R02.30
Bus A
Line Breaker
A Line CTs Protected Line
A
B 52-1 B
C C
Line Breaker
Aux AC
Notes:
1. CT inputs 1 to be used for protection and for recording of the protected line.
2. CT inputs 2 can be used for second set of line currents for ring bus applications.
3. CT inputs 3 and 4 can be used for mutual compensation, recording other AC currents.
Appendix I-1
4. AC Aux Voltage inputs used for line sync and over/under protection, main AC voltage inputs used for line protection.
Appendix J DC Schematic Drawings
5A
+Supply
200 202 204 206 208 210 212 214 216 218 220 222 224 226 228
NC Out1 Out2 Out3 Out4 Out5 Out6 Out7 Out8 Out9 Out10 Out11 Out12 Out13 Out14
+ 336
201 203 205 207 209 211 213 215 217 219 221 223 225 227 229
Power
Supply
Alarm
Optional Output Relay Contacts (4U Chassis)
- 337
5A
-Supply
1 2 3 4 5 6 7 8 9
- 101 - 103 - 105 - 107 - 109 - 111 - 113 - 115 - 117
+ 400 + 402 + 404 + 406 + 408 + 410 + 412 + 414 + 416 + 418 + 420
10 11 12 13 14 15 16 17 18 19 20
- 401 - 403 - 405 - 407 - 409 - 411 - 413 - 415 - 417 - 419 - 421
Notes:
1. IRIG-B and comm ports shown separately on L-PRO rear panel layout drawing.
2. All output relays can be programmed to operate on any relay function.
3. All outputs are rated tripping duty, interrupting via breaker aux "a" contact
Latch Status The relay does not reset any ProLogic, Group Logic or Virtual Input latch func-
tions during the setting save or active group change. Retaining latch status al-
lows the relay continuous access to specific latched logic states. This is useful
when the relay has ProLogic, Group Logic or Virtual Input functions used to
block protection or ancillary functions for specific operating conditions.
Event Status The relay resets all the events that are currently high and reports states of all
Reset the events that remain high after a setting change.
Viewing Active To view the active setting group and status of the group logic functions in real
Setting Group time via the TUI, enter the Metering/Logic/Setting Group menu choice. To
view a snapshot of the group logic data, enter the Settings/Active Group menu
choice.
Front Panel The front panel display along with the front panel control buttons allow the
Active Setting user to access metering and setting functions within the relay.
Group The front display also allows the user to reset the LED target lights that will
occur if a relay trip occurs. The front display will go dark and reset if no user
interaction has taken place for a period of time. Pressing any of the front panel
control buttons brings the front panel to life.
Using One Use one external input connected to a SCADA output contact to toggle be-
External Input tween 2 or more setting groups. In this example we connect external input one
to Toggle (EI 1) to the SCADA control output contact and switch between group 1 and
Setting Group group 2. If the user wanted to switch through all setting groups, group logic 2
would switch to setting group 3, and so forth. If the contact input to switch set-
ting groups becomes welded shut or the SCADA system has a problem, the re-
lay will only switch to the new logic and stay in that logic until the input has
been de-energized for the ProLogic pickup delay, which was set to 10 seconds.
Prologic 10 has no intentional delay and becomes high for the combined drop-
out time of ProLogic 9 and 10 equalling 0.52 seconds.
Group Logic 1 is used to switch to the new setting group; there is no intentional
delay. The user can also provide 4 additional logic inputs to be used to provide
qualifiers before switching setting groups. The example uses a ProLogic state-
ment and an external input as qualifiers, see example “Using ProLogic to Qual-
ify Group Logic Statements” in Appendix L’ on page Appendix L-8.
Prologic 10 has no intentional delay and becomes high for the combined drop-
out time of ProLogic 9 and 10 equalling 0.52 seconds.
Group Logic 1 is used to switch to the new setting group; there is no intentional
delay.
Using Three Three external inputs connected to an 8 position selector switch. The output
External Inputs contact is used to build a truth table to toggle between 8 setting groups. In this
to Toggle example we connect EI 1, EI 2, and EI 3 to the selector switch output contacts.
Setting Group
Selector
Input States Setting Group to Activate
Switch
EI 3 EI 2 EI 1
1 0 0 0 Setting Group 1
2 0 0 1 Setting Group 2
3 0 1 0 Setting Group 3
4 0 1 1 Setting Group 4
5 1 0 0 Setting Group 5
6 1 0 1 Setting Group 6
7 1 1 0 Setting Group 7
8 1 1 1 Setting Group 8
Using ProLogic Select from any available ProLogic inputs to make specific blocking logic to
to Qualify be used as a qualifier for any group logic decisions. In this example we use ei-
Group Logic ther the zone 1 or zone 2 phase distance elements or the communications trip
Statements or the communications send or the Power Swing outer blinder alarm to drive
the Block Group Logic statement. There is no intentional pickup delay and 0.5
second drop-out delay to hold the block on after the block condition has reset.
79 Recloser
Settings
Most protection schemes require the ability to block the 79 when certain events
happen. In our example we are using Virtual Input 7 (VI 7) to block. The 79
blocking is set to last for an additional time of 1.0 seconds (TDB).
79 initiation is done by simply setting the desired function in the output matrix.
The 79 can also automatically move the follow breaker into the lead position
if the lead breaker has been out of service for an extended period of time. The
out of service indication is also used to prevent reclosing attempts to the main
or auxiliary breaker. In our example a breaker has to be opened and stay open
for a time of 120.0 seconds (TC).
The 79 can also be configured with the follow breaker switch setting. In this
example we are using the TF follow time of 5.0 seconds for the 2nd breaker
open interval. The user can use the recloser reset time of TD by selecting the
“close after recloser reset time” setting.
52 - Breaker Status can use any external input or ProLogic statement. The re-
closer does not have to be enabled for this logic to work. The 2 circuit breakers
cannot share the same input.
Test Examples to test the 79 functions using Virtual Inputs and ProLogic to simu-
Configuration late the reclose initiation and breaker contact “a” status are shown below.
Virtual Inputs are multi-use logic points that are accessed remotely via SCA-
DA control and/or locally via the Terminal User Interface (TUI).
We will set up 6 virtual inputs to trip and close each breaker and to initiate the
79. External inputs to provide the breaker “a”, trip, close, and initiate signals
can be used, but using virtual inputs and ProLogic testing is quicker and does
not require an external dc supply or relays to simulate the circuit breakers.
Virtual Inputs The Virtual Input (VI) names are used for descriptive purposes. This name will
appear in the event log when the logic point becomes active. The relay supports
2 circuit breakers and in this example we will name the main circuit breaker
52-1 and the auxiliary circuit breaker 52-2. Virtual Inputs 1, 2, 3, and 4 will be
used as Control Switches (CS) for tripping and closing while Virtual Input 7
will be used to enable or disable the 79. Virtual Input 5 is used to trip circuit
breakers 52-1 and 52-2, and to provide recloser initiation. Virtual Input 6 is
used to provide recloser initiation without any tripping (used to help test logic)
Main and ProLogic statement 1 and 3 are used to provide a common tripping logic point
Auxiliary Circuit for the circuit breaker this is analogous to creating a dc trip bus to gather the
Breaker Trip trip and no reclose or trip and reclose signals. VI2 and VI4 are (VI2 for main
Logic and VI4 for auxiliary) the trip and no reclose while VI5 is the trip and reclose
(common to main and auxiliary) signal.
Circuit Breaker ProLogic statement 2 and 4 are used to provide a simulated logic point for the
Simulator Logic circuit breaker contact “a” status. The output of this logic is used as the input
for the 52 - Breaker Status (see 79 Recloser Settings). The 79 Main Reclose
logic point and VI1 provide the close signal ProLogic 1 provides the trip signal.
The pickup and dropout time delays are used to simulate breaker tripping and
closing times.
Figure L.29: ProLogic status for 52-1 and 52-2 are low
7 Check the metering screen for Protection. All 79 logic points should be low.
8 Go to the Control Virtual Inputs and “close” 52-1 and 52-2 using the Pulse
On action for the Virtual Input 1 and Virtual Input 2. This will activate Pro-
Logic 2 and 4.
Figure L.31: Control Virtual Input '52-1 Close 52-CS' to 'Pulse On'
9 Check the event log for VI1 and VI3 along with PL2 and PL4.
10 Go to the Control Virtual Inputs and select “Manual 79 I” using the Pulse
On action for the Virtual Input 6. This will initiate the recloser but no action
will be taken because the circuit breakers remain closed.
11 Check the event log and confirm there was no reclosure action.
12 Go to the Control Virtual Inputs and select “52-1, 52-2 Trip&79I” using
the Pulse On action for the Virtual Input 5. This will trip both breakers and
initiate the reclosing sequence.
Figure L.35: select 52-1, 52-2 Trip&79I using the Pulse On action
13 Check the event log and confirm that 52-1was the first breaker and 52-2
was the second breaker. Check open interval time and follower time, the
close pulse can be measured from the time between PL9 and PL10 going
high.
• T1 - Open interval time equals time from 79 Initiate event to 79 Main
Reclose (shot 1) event.
• TP - Close pulse time equals time from TP start: PL9 event to TP end:
PL10 event.
• TF - Follow breaker time equals time from 52-1 “a” status: PL2 event
to 79 Au Auxiliary Reclose (shot 1) event.
14 Go to the Control Virtual Inputs and select “52-1 Trip 52-CS” using the
Pulse On action for the virtual inputs. This will trip breaker 52-1 and after
timer TC, 52-2 (follow breaker) will move into the lead position.
15 Go to the Control Virtual Inputs and select “52-1, 52-2 Trip&79I” using
the Pulse On action for the virtual inputs. This will trip breaker 52-2 and in-
itiate the reclosing sequence.
16 Check the event log and confirm that only 52-2 breaker reclosed and was
in the lead position. Confirm that 52-1 breaker did not receive any reclose
attempts.
Figure L.37: Only 52-2 breaker reclosed and was in the lead position
17 Go to the Control Virtual Inputs and select “52-1 Close 52-CS” using the
Pulse On action for the virtual inputs. This will close breaker 52-1 and after
a fixed delay of 10.0 seconds breaker 52-1 will move back into the lead po-
sition and 52-2 (follow breaker) will move back into the follow position.
18 Go to the Control Virtual Inputs and select “52-1, 52-2 Trip&79I” using
the Pulse On action for the virtual inputs. This will trip both breakers and
initiate the reclosing sequence.
19 After 52-1 closes and before 52-2 closes select “52-1, 52-2 Trip&79I” us-
ing the Pulse On action for the virtual inputs. This will trip breaker 52-1 and
cause a lockout alarm to be generated and block the follow breaker reclose
attempt.
20 Check the event log and confirm the 79 Lead Lockout event and that there
was no follow breaker reclose attempt.
• 79 Lead Lockout - The time equals time from 79 Initiate event to 79
Lead Lockout event (approx. TP + 1.0s).
21 Go to the Control Virtual Inputs and select “52-1 Close 52-CS” using the
Pulse On action for the virtual inputs. This will close breaker 52-1 and after
a fixed delay of TD seconds the recloser will reset.
Communication
-aided Tripping
L-PRO #1 L-PRO #2
Schemes
1 2
3 4
F
Current The relays are installed and provide line protection by the tripping Breaker #1
Reversal Logic and Breaker #2 respectively. A ground fault occurs at location F in the parallel
Example line. Initially, 21N2 of L-PRO #2 picks up and sends a permissive transfer trip
signal to L-PRO #1. Since L-PRO #1 detects a reverse fault (21N4 picks up),
it neither trips the breaker nor sends a permissive transfer trip signal. When
breaker #3 opens due to a zone 1 trip, the current reversal condition occurs on
L-PRO #1. If the 21P2 on L-PRO #1 operates, and if the received permissive
transfer trip signal from L-PRO #2 still exists the POTT scheme on L-PRO #1
will trip breaker #1. To prevent this unwanted tripping on the parallel line, the
relay has current reversal logic. The relay current reversal logic prevents the
false trip during this current reversal condition. Gate #116 of the functional
logic diagram and timer TL1 and TD1 stretch the zone 4 logic and block the
POTT scheme from tripping the breaker or sending the transfer trip signal to
the remote end.
Communication The basic selection does not provide any communication-aided logic for local
-aided Tripping or remote protections.
Scheme Timer
Considerations
101
Receiver #1
Receiver #2 102 103
PUTT SCHEME (+)
21-2
50N-67R
104 21-4 R 105
Receiver #1 0
Receiver #2 106
(If DCB shceme is TD2
107
selected, Zone 4 must TL2
be set reverse) 0
DCB SCHEME
6ms
108
TWD1
60 110 0
3ms 111
TWD3
TWD2
20ms
0 112
27 V1
113
59 V0 Weak Infeed Enable
WEAK INFEED LOGIC Switch
Receiver #1
120
Receiver #2
(+)
51NAlarm 115
117
TL1
116
TD1
50N-67F 119 DCB PUTT DCB PUTT
114 21-2 118
21P2 POTT BASIC POTT BASIC
21N2
TL3
S
TD3
TL3, TD3 range: 0-1s
SCHEME SELECTOR
POTT SCHEME
Trip
3I0 > Pickup
TCS
Forward 121
0
Non-directional 21N4
(+) 21P4
21N2
21P2
3I0 > Pickup TCB 21N1
Reverse 122 21P1
0
Timer Considerations
TD2 Upon receipt of a Blocking Signal at the local end from the remote end, TD2
extends the Blocking Signal to prevent a Scheme Trip.
The Blocking Signal should be extended by:
Time for the local 21-2 to de-assert (~1 cycle) – Blocking Signal Channel
Reset Time (i.e. the time for the removal of the Block to propagate from the
remote end to the local end) + Security Margin*.
TL2 Delays the local 21-2 from producing a Scheme Trip for at least as long as it
would take a Blocking Signal to arrive from the remote end.
Should be set longer than the remote end 21-4R (OR 50-67R) detection
time (~1 cycle) + Blocking Channel Time + Security Margin*.
Timer Considerations
Timer Considerations
TL3 Local fault duration must be greater than this time in order to produce a
Scheme Send.
POTT and PUTT = Permissive Trip
DCB = Block Signal (derived from 21-4R (OR 50N-67R) AND NOT 21-2)
TD3 Stretches the Scheme Send signal to ensure that it's received by the
remote end relay. Set longer than the channel pickup delay.
Notes:
* Security Margin = 0.5 to 1 cycle or a percentage of total expected time to account for errors in
scheme timing assumptions.
** Parallel Line applications: fault contribution can come from unfaulted line appearing as a Zone
2 fault at one end and zone 4 reverse fault at the other end. Depending on the location of the fault
on the faulted line and which breaker clears first, the current may change direction and the 2 ter-
minals on the unfaulted line may change state from forward to reverse and reverse to forward.
The unfaulted line contribution may come either end on a networked system.
Relay
User
Inputs DSP MPC
Laptop or Remote
Digital Signal Micro-
Connection
Processor Processor
Outputs
Watchdog Watchdog
A B C D E
DSP DSP DSP.MPC MPC MPC
System Self- Comm Self- System
Fail check Fail check Fail
Fail Fail
M.1 Actions
A - DSP System Failure
The Relay Functional LED changes from green to off. The Master Relay is de-
energized. Two of its contacts open, disconnecting power to the other auxiliary
relays. A separate contact labeled “Relay Inoperative” on the rear panel closes
to activate a remote alarm.
The watch-dog repeatedly attempts to re-start the DSP for diagnostic purposes.
The Relay Functional LED stays off and the relays remain de-energized, even
for a successful re-start. Only a power-down/power-up cycle will reset the
LED to green and re-energize the relays.
er calibration. Alarm just drives the optional output contact but Block causes
the Relay Functional LED to go out and the relay to be unable to drive any out-
put contact.
Server/Publisher Remarks
SCSMs supported
Server/
Remarks
Publisher
M3 Data c4 YES
M5 Substitution O YES
Reporting
M7-10 GI YES
M8-7 GI YES
Logging O NO
M9 Log control O NO
M9-1 IntgPd NO
M10 Log O NO
M11 Control M NO
M12-1 EntryID
M12-2 DataReflnc
Server (Clause 6)
S1 ServerDirectory TP M YES
S2 Associate M YES
S3 Abort M YES
S4 Release M YES
S6 LogicalNodeDirectory TP M YES
S7 GetAllDataValues TP M YES
S8 GetDataValues TP M YES
S9 SetDataValues TP O YES
S13 SetDataSetValues TP O NO
S14 CreateDataSet TP O NO
S15 DeleteDataSet TP O NO
S18 SelectActive SG TP O NO
S19 SelectEdit SG TP O NO
S20 SetSGvalues TP O NO
S21 ConfirmEditSGvalues TP O NO
S22 GetSGvalues TP O NO
S23 GetSGCBvalues TP O NO
S24-2 qchg-change(qchg) NO
S24-3 Data-update(dupd) NO
S27-2 qchg-change(qchg) NO
S27-3 Data-update(dupd) NO
S30 GetLCBValues TP M NO
S31 SetLCBValues TP M NO
Log
S32 QueryLogByTime TP M NO
S33 QueryLogAfter TP M NO
S34 GetLogStatusValues TP M NO
c7- shall declare support for at least one(query log by time or Query LogAfter)
S36 GetGOReference TP c9
S37 GetGOOSEElementNumber TP c9
S40 SendGSSEMessage MC C8 NO
S41 GetGsReference TP C9 NO
S42 GetGSSEElementNumber TP C9 NO
S43 GetGsCBValues TP O NO
S44 SetGsCBValues TP O NO
c8- shall declare support for at least one(Send GOOSE Message or Send GSSE Message)
c9- shall declare support if TP association is available
Multicast SVC
S46 GetMSVCBValues TP O NO
S47 SetMSVCBValues TP O NO
Unicast SVC
S49 GetUSVCBValues TP O NO
S50 SetUSVCBValues TP O NO
C10- shall declare support for at least one(Send MSV Message or Send USV Message)
S51 Select TP O NO
S53 Cancel TP O NO
S54 Operate TP M NO
S55 Command-Termination TP O NO
T1
T2
T3
T4
T5
Objective
To provide comprehensive details of the standard data object model elements
supported by the device. The MICS is conformant to the devices associated
ICD (Substation Configuration Language) file, according to part 6 of the IEC
61850 standards. The layout of the presented tables within this document is
conformant to the part 7 series of the IEC 61850 standard specifications with
the following exceptions:
• The "Trigger Options" field is not presented
• The "M/O" field is not present as the definitions are as deployed within the
model
• An additional column "X" is used to signify custom attributes
Protection
1 LLN0 LLN0
2 LPHD1 LPHD1
3 PDIS1 PDIS1
4 PDIS2 PDIS1
5 PDIS3 PDIS1
6 PDIS4 PDIS1
7 PDIS5 PDIS1
8 PDIS6 PDIS1
9 PDIS7 PDIS1
10 PDIS8 PDIS1
11 RSYN1 RSYN1
12 RREC1 RREC1
13 RREC2 RREC1
14 PTOV1 PTOV1
15 PTOV2 PTOV1
16 PTOV3 PTOV1
17 PTOV4 PTOV1
18 PTOV5 PTOV1
19 PTOV6 PTOV1
20 PTUV1 PTUV1
21 PTUV2 PTUV1
22 PTUV3 PTUV1
23 PTUV4 PTUV1
24 PTUV5 PTUV1
25 PTUV6 PTUV1
26 PTOF1 PTOF1
27 PTOF2 PTOF1
28 PTOF3 PTOF1
29 PTOF4 PTOF1
30 PTUF1 PTUF1
31 PTUF2 PTUF1
32 PTUF3 PTUF1
33 PTUF4 PTUF1
34 PFRC1 PFRC1
35 PFRC2 PFRC1
36 PFRC3 PFRC1
37 PFRC4 PFRC1
38 PIOC1 PIOC1
39 PIOC2 PIOC1
40 PIOC3 PIOC1
41 PIOC4 PIOC1
42 PIOC5 PIOC1
43 PIOC6 PIOC1
44 RBRF1 RBRF1
45 RBRF2 RBRF1
46 RBRF3 RBRF1
47 RBRF4 RBRF1
48 PTOC1 PTOC1
49 PTOC2 PTOC1
50 PTOC3 PTOC1
51 PTOC4 PTOC1
52 PTOC5 PTOC1
53 PTOC6 PTOC1
Measurements
1 LLN0 LLN0
2 LPHD1 LPHD1
3 MMXU1 MMXU1
System
1 LLN0 LLN0
2 LPHD1 LPHD1
3 GGIO1 GGIO1
4 GGIO2 GGIO2
5 GGIO3 GGIO3
6 GGIO4 GGIO4
Records
1 LLN0 LLN0
2 LPHD1 LPHD1
3 RDRE1 RDRE1
VirtualElements
1 LLN0 LLN0
2 LPHD1 LPHD1
3 GGIO1 GGIO5
4 GGIO2 GGIO5
5 GGIO3 GGIO5
Hz MV_1_TotW Frequency
Str ACD_1_Str
Op ACT_1_Op
PoRch ASG_1_PoRch
PhStr ASG_1_PoRch
GndStr ASG_1_PoRch
DirMod ING_1_DirMod
PctRch ASG_1_PoRch
Ofs ASG_1_PoRch
PctOfs ASG_1_PoRch
RisLod ASG_1_PoRch
AngLod ASG_1_PoRch
TmDlMod SPG_1_TmDlMod
OpDlTmms ING_1_OpDlTmms
PhDlMod SPG_1_TmDlMod
PhDlTmms ING_1_OpDlTmms
GndDlMod SPG_1_TmDlMod
GndDlTmms ING_1_OpDlTmms
X1 ASG_1_PoRch
LinAng ASG_1_PoRch
RisGndRch ASG_1_PoRch
RisPhRch ASG_1_PoRch
K0Fact ASG_1_PoRch
K0FactAng ASG_1_PoRch
RsDlTmms ING_1_OpDlTmms
Rel SPS_1_Proxy
VInd SPS_1_Proxy
AngInd SPS_1_Proxy
HzInd SPS_1_Proxy
SynPrg SPS_1_Proxy
DifVClc MV_1_TotW
DifHzClc MV_1_TotW
DifAngClc MV_1_TotW
DifV ASG_1_PoRch
DifHz ASG_1_PoRch
DifAng ASG_1_PoRch
LivDeaMod ING_1_OpDlTmms
DeaLinVal ASG_1_PoRch
LivLinVal ASG_1_PoRch
DeaBusVal ASG_1_PoRch
LivBusVal ASG_1_PoRch
PlsTmms ING_1_OpDlTmms
BkrTmms ING_1_OpDlTmms
Auto SPS_1_Proxy
Op ACT_1_Op
AutoRecSt INS_1_PhyHealth
Op ACT_1_Op Operate
Op ACT_1_Op Operate
Op ACT_1_Op Operate
Op ACT_1_Op Operate
Op ACT_1_Op Operate
Op ACT_1_Op Operate
Ind1 SPS_1_Proxy
Ind2 SPS_1_Proxy
Ind3 SPS_1_Proxy
Ind4 SPS_1_Proxy
Ind5 SPS_1_Proxy
Ind6 SPS_1_Proxy
Ind7 SPS_1_Proxy
Ind8 SPS_1_Proxy
Ind9 SPS_1_Proxy
Ind10 SPS_1_Proxy
Ind11 SPS_1_Proxy
Ind12 SPS_1_Proxy
Ind13 SPS_1_Proxy
Ind14 SPS_1_Proxy
Ind15 SPS_1_Proxy
Ind16 SPS_1_Proxy
Ind17 SPS_1_Proxy
Ind18 SPS_1_Proxy
Ind19 SPS_1_Proxy
Ind20 SPS_1_Proxy
Ind21 SPS_1_Proxy
Ind22 SPS_1_Proxy
Ind23 SPS_1_Proxy
Ind24 SPS_1_Proxy
Ind1 SPS_1_Proxy
Ind2 SPS_1_Proxy
Ind3 SPS_1_Proxy
Ind4 SPS_1_Proxy
Ind5 SPS_1_Proxy
Ind6 SPS_1_Proxy
Ind7 SPS_1_Proxy
Ind8 SPS_1_Proxy
Ind9 SPS_1_Proxy
Ind10 SPS_1_Proxy
Ind11 SPS_1_Proxy
Ind12 SPS_1_Proxy
Ind13 SPS_1_Proxy
Ind14 SPS_1_Proxy
Ind15 SPS_1_Proxy
Ind16 SPS_1_Proxy
Ind1 SPS_1_Proxy
Ind2 SPS_1_Proxy
Ind3 SPS_1_Proxy
Ind4 SPS_1_Proxy
Ind5 SPS_1_Proxy
Ind6 SPS_1_Proxy
Ind7 SPS_1_Proxy
Ind8 SPS_1_Proxy
Ind9 SPS_1_Proxy
Ind10 SPS_1_Proxy
Ind11 SPS_1_Proxy
Ind12 SPS_1_Proxy
Ind13 SPS_1_Proxy
Ind14 SPS_1_Proxy
Ind15 SPS_1_Proxy
Ind16 SPS_1_Proxy
Ind17 SPS_1_Proxy
Ind18 SPS_1_Proxy
Ind19 SPS_1_Proxy
Ind20 SPS_1_Proxy
Ind1 SPS_1_Proxy
Ind2 SPS_1_Proxy
Ind3 SPS_1_Proxy
Ind4 SPS_1_Proxy
Ind5 SPS_1_Proxy
Ind6 SPS_1_Proxy
Ind7 SPS_1_Proxy
Ind8 SPS_1_Proxy
Ind9 SPS_1_Proxy
Ind10 SPS_1_Proxy
Ind11 SPS_1_Proxy
Ind12 SPS_1_Proxy
Ind13 SPS_1_Proxy
Ind14 SPS_1_Proxy
Ind15 SPS_1_Proxy
Ind16 SPS_1_Proxy
Ind17 SPS_1_Proxy
Ind18 SPS_1_Proxy
Ind19 SPS_1_Proxy
Ind20 SPS_1_Proxy
Ind21 SPS_1_Proxy
Ind1 SPS_1_Proxy
Ind2 SPS_1_Proxy
Ind3 SPS_1_Proxy
Ind4 SPS_1_Proxy
Ind5 SPS_1_Proxy
Ind6 SPS_1_Proxy
Ind7 SPS_1_Proxy
Ind8 SPS_1_Proxy
Ind9 SPS_1_Proxy
Ind10 SPS_1_Proxy
Ind11 SPS_1_Proxy
Ind12 SPS_1_Proxy
Ind13 SPS_1_Proxy
Ind14 SPS_1_Proxy
Ind15 SPS_1_Proxy
Ind16 SPS_1_Proxy
Ind17 SPS_1_Proxy
Ind18 SPS_1_Proxy
Ind19 SPS_1_Proxy
Ind20 SPS_1_Proxy
Ind21 SPS_1_Proxy
Ind22 SPS_1_Proxy
Ind23 SPS_1_Proxy
Ind24 SPS_1_Proxy
Ind25 SPS_1_Proxy
Ind26 SPS_1_Proxy
Ind27 SPS_1_Proxy
Ind28 SPS_1_Proxy
Ind29 SPS_1_Proxy
Ind30 SPS_1_Proxy
RcdTrg SPC_1_RcdTrg
RcdMade SPS_1_Proxy
FltNum INS_1_IntIn
RcdStr SPS_1_Proxy
Vendor VisString255 DC
hwRev VisString255 DC
swRev VisString255 DC
serNum VisString255 DC
Model VisString255 DC
q Quality ST
t Timestamp ST
subEna BOOLEAN SV
subQ Quality SV
subID VisString64 SV
stVal BOOLEAN ST
q Quality ST
t Timestamp ST
subEna BOOLEAN SV
subVal BOOLEAN SV
subQ Quality SV
subID VisString64 SV
Q Quality ST
T Timestamp ST
subEna BOOLEAN SV
subQ Quality SV
subID VisString64 SV
Q Quality ST
T Timestamp ST
subEna BOOLEAN SV
subQ Quality SV
subID VisString64 SV
Vendor VisString255 DC
swRev VisString255 DC
d VisString255 DC
configRev VisString255 DC
ldNs VisString255 DC
Vendor VisString255 DC
hwRev VisString255 DC
d VisString255 DC
mag AnalogueValue_1 MX
Q Quality MX
T Timestamp MX
subEna BOOLEAN SV
subVal AnalogueValue_1 SV
subQ Quality SV
subID VisString64 SV
cVal Vector_1 MX
Q Quality MX
T Timestamp MX
ctlModel ctlModelEnum CF
subEna Enum SV
subVal Vector_1 SV
subQ Quality SV
subID VisString64 SV
phsAB CMV_1_phsAB
phsBC CMV_1_phsAB
phsCA CMV_1_phsAB
phsA CMV_1_phsAB
phsB CMV_1_phsAB
phsC CMV_1_phsAB
neut CMV_1_phsAB
phsA CMV_1_phsAB
phsB CMV_1_phsAB
phsC CMV_1_phsAB
general BOOLEAN ST
q Quality ST
t Timestamp ST
general BOOLEAN ST
q Quality ST
t Timestamp ST
setMag AnalogueValue_1 SG
setVal BOOLEAN SG
setVal INT32 SG
stVal INT32 ST
Q Quality ST
T Timestamp ST
subEna BOOLEAN SV
subVal INT32 SV
subQ Quality SV
subID VisString64 SV
stVal BOOLEAN ST
Q Quality ST
T Timestamp ST
Oper SPCOperate_1 CO
subEna BOOLEAN SV
subVal BOOLEAN SV
subQ Quality SV
subID VisString64 SV
Component: Vector_1
Comment: Complex Vector (w.r.t. Floating Point Magnitude and Angle val-
ues)
Parent Type: Vector
Component: AnalogueValue_1
Comment: General Analogue Value (w.r.t. Floating Point Value)
Parent Type: AnalogueValue
Component: Originator
Comment: Originator Value
Parent Type: Originator
orIdent Octet64
Component: SPCOperate_1
Comment:
ctlVal BOOLEAN
Origin Originator
CtlNum INT8U
T Timestamp
Test BOOLEAN
Check Dbpos
Ordinal Semantic
1 Ready
2 InProgress
3 Successful
Ordinal Semantic
1 on
2 blocked
3 test
4 test/blocked
5 off
Ordinal Semantic
1 on
2 blocked
3 test
4 test/blocked
5 off
Ordinal Semantic
1 Ok
2 Warning
3 Alarm
Ordinal Semantic
0 unknown
1 forward
2 backward
3 both
Ordinal Semantic
0 status-only
1 direct-with-normal-security
2 sbo-with-normal-security
3 direct-with-enhanced-security
4 sbo-with-enhanced-security
Ordinal Semantic
0 not-supported
1 bay-control
2 station-control
3 remote-control
4 Automatic-bay
5 Automatic-station
6 automatic-remote
7 maintenance
8 process
Ordinal Semantic
1 NonDirectional
2 Forward
3 Inverse
L-PRO
LN Spec
LD Name LN Name LN Description Protection Comments
Reference
Function
LPROProtection PTOF1 Overfrequency Dev 81-1 Dev 81-1 can operate as PTOF PTOF1
or PTUF or PFRC (one type of
protection at a time)
LPROProtection PTOF2 Overfrequency Dev 81-2 Dev 81-2 can operate as PTOF PTUF2
or PTUF or PFRC (one type of
protection at a time)
LPROProtection PTOF3 Overfrequency Dev 81-3 Dev 81-3 can operate as PTOF PTUF3
or PTUF or PFRC (one type of
protection at a time)
LPROProtection PTOF4 Overfrequency Dev 81-4 Dev 81-4 can operate as PTOF PTOF4
or PTUF or PFRC (one type of
protection at a time)
LPROProtection PTUF1 Underfrequency Dev 81-1 Dev 81-1 can operate as PTOF PTUF1
or PTUF or PFRC (one type of
protection at a time)
LPROProtection PTUF2 Underfrequency Dev 81-2 Dev 81-2 can operate as PTOF PTUF2
or PTUF or PFRC (one type of
protection at a time)
LPROProtection PTUF3 Underfrequency Dev 81-3 Dev 81-3 can operate as PTOF PTUF3
or PTUF or PFRC (one type of
protection at a time)
LPROProtection PTUF4 Underfrequency Dev 81-4 Dev 81-4 can operate as PTOF PTUF4
or PTUF or PFRC (one type of
protection at a time)
LPROProtection PFRC1 Rate of change of Dev 81-1 Dev 81-1 can operate as PTOF PFRC1
frequency or PTUF or PFRC (one type of
protection at a time)
LPROProtection PFRC2 Rate of change of Dev 81-2 Dev 81-2 can operate as PTOF PFRC2
frequency or PTUF or PFRC (one type of
protection at a time)
LPROProtection PFRC3 Rate of change of Dev 81-3 Dev 81-3 can operate as PTOF PFRC3
frequency or PTUF or PFRC (one type of
protection at a time)
LPROProtection PFRC4 Rate of change of Dev 81-4 Dev 81-4 can operate as PTOF PFRC4
frequency or PTUF or PFRC (one type of
protection at a time)
LPROProtection PTOC5 Time overcurrent Dev 46-50/67 Negative sequence overcurrent PTOC5
LPROProtection PTOC6 Time overcurrent Dev 46-50/67 Negative sequence overcurrent PTOC6
LPROSystem GGIO1 General process I/O ProLogic1-24 Prologic status under GGIO1
LPROSystem GGIO2 General process I/O Group Logic1- Group Logic status GGIO2
16
LPROSystem GGIO3 General process I/O External input 1 External input status GGIO3
-20
LPROSystem GGIO4 General process I/O Output contact Output contact status GGIO4
1-21
LPROVirtualEle- GGIO1 General process I/O Virtual inputs 1- Virtual input status GGIO1
ments 30
LPROVirtualEle- GGIO2 General Process I/O Virtual Inputs 1 Virtual input incoming controls GGIO2
ments – 30
LPROVirtualEle- GGIO3 General Process I/O Virtual Inputs 1 Virtual input outgoing controls GGIO3
ments – 30 (Currently not support)
MMXU1.MX.Hz.mag.f Frequency
PDIS2
This section defines logical node data for the logical node PDIS3 of the L-PRO
logical device LPROProtection.
PDIS3
This section defines logical node data for the logical node PDIS3 of the L-PRO
logical device LPROProtection.
PDIS4
This section defines logical node data for the logical node PDIS4 of the L-PRO
logical device LPROProtection.
PDIS5
This section defines logical node data for the logical node PDIS5 of the L-PRO
logical device LPROProtection.
PDIS6
This section defines logical node data for the logical node PDIS6 of the L-PRO
logical device LPROProtection.
PDIS7
This section defines logical node data for the logical node PDIS7 of the L-PRO
logical device LPROProtection.
PDIS8
This section defines logical node data for the logical node PDIS8 of the L-PRO
logical device LPROProtection.
RSYN1
This section defines logical node data for the logical node RSYN1 of the L-
PRO logical device LPROProtection.
RREC1
This section defines logical node data for the logical node RREC1of the L-
PRO logical device LPROProtection.
RREC2
This section defines logical node data for the logical node RREC2of the L-
PRO logical device LPROProtection.
PTOV1
This section defines logical node data for the logical node PTOV1of the L-
PRO logical device LPROProtection.
PTOV2
This section defines logical node data for the logical node PTOV2 of the L-
PRO logical device LPROProtection.
PTOV3
This section defines logical node data for the logical node PTOV3of the L-
PRO logical device LPROProtection.
PTOV4
This section defines logical node data for the logical node PTOV4of the L-
PRO logical device LPROProtection.
PTOV5
This section defines logical node data for the logical node PTOV5of the L-
PRO logical device LPROProtection.
PTOV6
This section defines logical node data for the logical node PTOV6 of the L-
PRO logical device LPROProtection.
PTUV1
This section defines logical node data for the logical node PTUV1of the L-
PRO logical device LPROProtection.
PTUV2
This section defines logical node data for the logical node PTUV2 of the L-
PRO logical device LPROProtection.
PTUV3
This section defines logical node data for the logical node PTUV3of the L-
PRO logical device LPROProtection.
PTUV4
This section defines logical node data for the logical node PTUV4of the L-
PRO logical device LPROProtection.
PTUV5
This section defines logical node data for the logical node PTUV5of the L-
PRO logical device LPROProtection.
PTUV6
This section defines logical node data for the logical node PTUV6 of the L-
PRO logical device LPROProtection.
PTOF1
This section defines logical node data for the logical node PTOF1 of the L-
PRO logical device LPROProtection.
PTOF2
This section defines logical node data for the logical node PTOF2 of the L-
PRO logical device LPROProtection.
PTOF3
This section defines logical node data for the logical node PTOF3 of the L-
PRO logical device LPROProtection.
PTOF4
This section defines logical node data for the logical node PTOF4 of the L-
PRO logical device LPROProtection.
PTUF1
This section defines logical node data for the logical node PTUF1 of the L-
PRO logical device LPROProtection.
PTUF2
This section defines logical node data for the logical node PTUF2 of the L-
PRO logical device LPROProtection.
PTUF3
This section defines logical node data for the logical node PTUF3 of the L-
PRO logical device LPROProtection.
PTUF4
This section defines logical node data for the logical node PTUF4 of the L-
PRO logical device LPROProtection.
PFRC1
This section defines logical node data for the logical node PFRC1 of the L-
PRO logical device LPROProtection.
PFRC2
This section defines logical node data for the logical node PFRC2 of the L-
PRO logical device LPROProtection.
PFRC3
This section defines logical node data for the logical node PFRC3 of the L-
PRO logical device LPROProtection.
PFRC4
This section defines logical node data for the logical node PFRC4 of the L-
PRO logical device LPROProtection.
PIOC1
This section defines logical node data for the logical node PIOC1 of the L-PRO
logical device LPROProtection.
PIOC2
This section defines logical node data for the logical node PIOC2 of the L-PRO
logical device LPROProtection.
PIOC3
This section defines logical node data for the logical node PIOC3 of the L-PRO
logical device LPROProtection.
PIOC4
This section defines logical node data for the logical node PIOC4 of the L-PRO
logical device LPROProtection.
PIOC5
This section defines logical node data for the logical node PIOC5 of the L-PRO
logical device LPROProtection.
PIOC6
This section defines logical node data for the logical node PIOC6 of the L-PRO
logical device LPROProtection.
RBRF1
This section defines logical node data for the logical node RBRF1 of the L-
PRO logical device LPROProtection.
RBRF2
This section defines logical node data for the logical node RBRF2 of the L-
PRO logical device LPROProtection.
RBRF3
This section defines logical node data for the logical node RBRF3 of the L-
PRO logical device LPROProtection.
RBRF4
This section defines logical node data for the logical node RBRF4 of the L-
PRO logical device LPROProtection.
PTOC1
This section defines logical node data for the logical node PTOC1 of the L-
PRO logical device LPROProtection.
PTOC2
This section defines logical node data for the logical node PTOC1 of the L-
PRO logical device LPROProtection.
PTOC3
This section defines logical node data for the logical node PTOC3 of the L-
PRO logical device LPROProtection.
PTOC4
This section defines logical node data for the logical node PTOC4 of the L-
PRO logical device LPROProtection.
PTOC5
This section defines logical node data for the logical node PTOC5 of the L-
PRO logical device LPROProtection.
PTOC6
This section defines logical node data for the logical node PTOC6 of the L-
PRO logical device LPROProtection.
GGIO2
This section defines logical node data for the logical node GGIO2 of the L-
PRO logical device LPROSystem. This logical node presents L-PRO Active
Setting Group Number.
GGIO3
This section defines logical node data for the logical node GGIO3 of the L-
PRO logical device LPROSystem. This logical node presents L-PRO External
Inputs.
GGIO4
This section defines logical node data for the logical node GGIO4 of the L-
PRO logical device LPROSystem. This logical node presents L-PRO Output
Contacts.
GGIO2
This section defines logical node data for the logical node GGIO2 of the L-
PRO logical device LPROVirtualElements. This logical node presents L-PRO
Virtual Inputs Control.
This Logical Node is used for the L-PRO GOOSE Subscription configuration.
The L-PRO will subscribe for the data mapped to the Logical Node GGIO2 of
the Logical Device LPROVirtualElements as defined in the current CID file;
the stVal changes of the subscribed data will initiate actions as defined in the
Output Matrix configuration for the L-PRO Virtual Inputs and will modify the
ProLogic function states in case mapped Virtual Inputs are used as ProLogic
inputs.
GGIO3
This section defines logical node data for the logical node GGIO3 of the L-
PRO logical device LPROVirtualElements. This logical node presents L-PRO
Virtual Outputs Control.
Index
Numerics F
21P phase distance 4-2 fault locator 4-43
25/27/59 sync check 4-36 Front display 3-1
46/50/51/67 negative sequence front display 3-2, 3-4
overcurrent 4-41 Front view 3-1
50/51/67 phase overcurrent 4-38
50BF breaker failure 4-36
G
grounding 2-1
50LS low set overcurrent 4-38
group logic 4-45, 6-26, L-8
50N/51N/67 neutral overcurrent 4-40,
6-25 H
59 overvoltage 4-28 HyperTerminal 2-9
60 loss of potential 4-43, 6-25
68 out of step 4-43 I
79 recloser 4-24 identification 6-10
81 frequency 4-34 inputs
81 over/under frequency 6-25 external 1-5
IRIG-B time 2-1
A IRIG-B 3-2
ac and dc wiring 8-1 IRIG-B time input 2-1
Alarm 3-2
analog input 6-11
L
LED lights 3-2
B line parameters 6-21
backward compatibility 6-6
Base MVA 6-15
M
maintenance 2-17
Baud rate
direct serial link 2-13 maintenance menu 2-17
modem link 2-13 mho
characteristic shapes 4-3, 7-6
C phase and ground 4-3
calibrate 7-2 modem link 2-13
calibration 7-2
circuit breaker simulator L-13
O
Offliner settings 3-1, 6-1
communication
direct serial link 2-6 output contact 6-12
modem link - external 2-7 output matrix 6-27
modem link - internal 2-8 output relay contacts 1-5
network link 2-9
P
relay 2-2
parameters
communication-aided scheme 4-47,
line 6-21
L-22
system 6-14
creating a setting file from an older physical mounting 8-1
version 6-7 POTT logic L-24
CT turns ratio 6-15 power supply 2-1
D ProLogic 6-25
DCB logic 4-50 protection functions 4-2, 6-25
dead line pickup 4-20 graphing 6-25
display 3-4 PT turns ratio 6-15
PUTT logic 4-51
E PUTT scheme 6-24
external input 6-12
T
Test mode 3-1, 3-2
testing
21N2 ground distance 7-22
21P1 phase distance 7-14
21P2 phase distanc 7-16
25/27/59 sync check 7-50
27 undervoltage 7-33
46-50/46-51 negative sequence
overcurrent 7-40
50/51 phase overcurrent 7-37
50BF breaker fail 7-44
50LS low set overcurrent 7-44
50N/51N neutral overcurrent 7-35
59 overvoltage 7-34
60 loss of potential 7-12
79 recloser 7-52
81 overfrequency 7-47
81 underfrequency 7-47
dead line pickup 7-27
directional element 7-42
external inputs 7-3
output relay contacts 7-3
weak infeed 7-25
tool bar 6-2
V
version descriptions 2-xi