SECTION 10: page 3

10: LUMENEX EMERGENCY LIGHTING

by Honeywell
8W Luminaire
 Suitable for a wide range
of interior and exterior
applications
 Cost effective with an optically
efficient and durable lens
design
 Maintained /non-maintained
versions
 Weatherproof (fit seal
supplied if an IP65 rating is
required)
 Snap-fit construction with
hinged gear tray
 Simple to install with screw
terminal block and a BESA
box mounting facility
8W Luminaire
 Stylish, slim profile design
with a range of optional
TECHNICAL SPECIFICATION
pictograms
Emergency Duration 3 hours
Emergency Lamp O/P 105 lumens
Maintained Lamp O/P 185 lumens (LUM8/M)
3 part self-extinguishing unit incorporating a polycarbonate lens, ABS/PC alloy
Construction
base and metal geartray. Colour: White
Length 343mm
Dimensions Height 78mm
Depth 101mm
Weight 1.0kg (LUM8/NM) 1.2kg (LUM8/M)
Cable Entry Drill guides on sides and one end. BESA in rear of fitting
Supply Voltage 230Vac +/- 10% 50Hz
Power Consumption 8VA (LUM8/NM) 15VA (LUM8/M)
Recharge Period 24 hours for full 3 hour duration
Battery NiCad 2.4V 4Ah
Light Source 300mm 8 Watt T5 fluorescent
Monitor High intensity red LED monitoring charger output and battery connection
Operating Temperature 0 to +25oC
Ingress Protection IP40 (IP65 when seal fitted)
Warranty 1 year
Certification CE - Ref. BS 4533 / EN 60598-2-22

ORDER CODES
8W Luminaire, IP65, LUM8/NM
Non-maintained
8W Luminaire, IP65, Maintained LUM8/M
Semi-recessing Bezel for LUM8/RB
8W Luminaire, White
Pictogram, Arrow Down LUM8/PAD
Pictogram, Arrow Left LUM8/PAL
Pictogram, Arrow Right LUM8/PAR
SECTION 10: page 4

10: LUMENEX EMERGENCY LIGHTING

by Honeywell
Unilux Emergency Luminaire
 A flexible high light output
luminaire
 A separate mounting bracket
and battery compartment
makes the Unilux easy to
install and maintain
 Elegant and functional design

Unilux Luminaire

TECHNICAL SPECIFICATION
Emergency Duration 3 hours
Emergency Lamp O/P 180 lumens
Maintained Lamp O/P 220 lumens (UNIHI8/M and UNIHI8/M/ST)
3 part self-extinguishing unit incorporating a polycarbonate lens, ABS/PC alloy
Construction
base and metal geartray. Colour: White
Length 363mm
Dimensions Height 83mm
Width 149mm
Weight 1.16kg
16/20mm knockouts on side/end of fitting
Cable Entry
Provision for rear BESA box mountings
6VA Non maintained
Power Consumption
26VA Maintained
Recharge Period 24 hours for full 3 hour duration
Battery NiCad 3.6V 4Ah
Light Source 8 Watt T5 fluorescent
Indicators Green LED / Manual Test Switch
Self-test Indicator Green, Amber, Red LED / Auto test
Operating Temperature 0 to +35oC
Ingress Protection IP20
Certification CE

ORDER CODES
High Light Output 8W UNIHI8/NM
Luminaire, IP20, Non-maintained
High Light Output 8W UNIHI8/M
Luminaire, IP20, Maintained
Self-test High Light Output 8W UNIHI8/NM/ST
Luminaire, IP20, Non-maintained
Self-test High Light Output 8W UNIHI8/M/ST
Luminaire, IP20, Maintained
Pictogram, Arrow Down LUM8/PAD
Pictogram, Arrow Left LUM8/PAL
Pictogram, Arrow Right LUM8/PAR
SECTION 10: page 5

10: LUMENEX EMERGENCY LIGHTING

by Honeywell
High Light 8W Luminaire
 Cost effective lighting solution
for both interior and exterior
applications
 Designed to minimise panic
and assist finding the escape
routes
 Energy efficient illumination
provided by a 28W 2D
fluorescent lamp
 Maintained/non-maintained
versions
 Weatherproof (IP65 rating)
 Snap-fit construction
 Simple to install with 20mm
gland rear entry and drill
points
High Light 8W Luminaire
 Strong, neutral coloured
polycarbonate base and
TECHNICAL SPECIFICATION
PMMA diffuser
Emergency Duration 3 hours
Emergency Lamp O/P 180 lumens  Clean, simple styling with
Maintained Lamp O/P 220 lumens (LUMHIGH/M and LUMHIGH/M/ST) rugged durability
3 part self-extinguishing unit incorporating a polycarbonate lens, ABS/PC alloy
Construction
base and steel geartray. Colour: White
Length 370mm
Dimensions Height 87mm (with recess bezel 44mm)
Depth 140mm
1.8kg (LUMHIGH/NM) 2.1kg (LUMHIGH/M)
Weight
1.9kg (LUMHIGH/NM/ST) 2.2kg (LUMHIGH/M/ST)
Cable Entry Gland entry points in end walls of base. BESA in rear of fitting
Supply Voltage 230Vac +/- 10% 50Hz
9VA (LUMHIGH/NM) 19VA (LUMHIGH/M)
Power Consumption
10VA (LUMHIGH/NM/ST) 21VA (LUMHIGH/M/ST)
Recharge Period 24 hours for full 3 hour duration
Battery NiCad 3.6V 4Ah
Light Source 300mm 8 Watt T5 fluorescent
Monitor High intensity red LED monitoring charger output and battery connection
Self-test Monitor High intensity red and green LED monitoring luminaire status
Operating Temperature 0 to +25oC
Ingress protection IP65
Warranty 1 year
Certification CE - Ref. BS 4533 / EN 60598-2-22
ORDER CODES
High Light Output 8W LUMHIGH/NM
Luminaire, IP65, Non-maintained
High Light Output 8W LUMHIGH/M
Luminaire, IP65, Maintained
Self-test High Light Output LUMHIGH/NM/ST
8W Luminaire, IP65, Non-maintained
Self-test High Light Output 8W LUMHIGH/M/ST
Luminaire, IP65, Maintained
Pictogram, Arrow Down LUM8/PAD
Pictogram, Arrow Left LUM8/PAL
Pictogram, Arrow Right LUM8/PAR
SECTION 10: page 6

10: LUMENEX EMERGENCY LIGHTING

by Honeywell
28W Antipanic Luminaire
 Cost effective lighting solution
for both interior and exterior
applications
 Designed to minimise panic
and assist finding the escape
routes
 Energy efficient illumination
provided by a 28W 2D
fluorescent lamp
 Maintained/non-maintained
versions
 Weatherproof (IP65 rating)
 Snap-fit construction
 Simple to install with 20mm
gland rear entry and drill
points
Circular 28W Luminaire
 Strong, neutral coloured
polycarbonate base and TECHNICAL SPECIFICATION
PMMA diffuser Emergency Duration 3 hours
 Clean, simple styling with Emergency Lamp O/P 380 lumens
rugged durability Maintained Lamp O/P 2000 lumens (LUMCIRC28/M)
Circular unit incorporating a polycarbonate base, PMMA diffuser and removable
Construction
steel geartray. Colour: White
Diameter 360mm
Dimensions
Height 90mm
Weight 2.7kg (LUMCIRC28/NM) 3.3kg (LUMCIRC28/M)
Cable Entry 20mm gland entry points in rear of fitting
Supply Voltage 230Vac +/- 10% 50Hz
Power Consumption 9VA (LUMCIRC28/NM) 63VA (LUMCIRC28/M)
Recharge Period 24 hours for full 3 hour duration
Battery NiCad 4.8V 4Ah
Light Source 28 Watt 2D fluorescent
Monitor High intensity red LED monitoring charger output and battery connection
Operating Temperature 0 to +25oC
Ingress Protection IP65
Warranty 1 year
Certification CE - Ref. BS 4533 / EN 60598-2-22

ORDER CODES
Circular 28W Luminaire, LUMCIRC28/NM
IP65, Non-maintained
Circular 28W Luminaire, LUMCIRC28/M
IP65, Maintained
SECTION 10: page 7

10: LUMENEX EMERGENCY LIGHTING

by Honeywell
Rectangular 8W Exit Sign
 Cost effective lighting solution
for interior applications
 Suitable for mounting on
emergency escape routes as
defined by BS 5266
 Maintained/non-maintained
versions
 Single-sided low profile unit
with pictogram accessible
from bottom entry
 Integral threshold down-
lighter
 Robust construction for
simple surface-mounted
installation
 Range of self-adhesive
Rectangular Exit Sign
pictogram options

TECHNICAL SPECIFICATION
Emergency Duration 3 hours
Emergency Lamp O/P 105 lumens
Maintained Lamp O/P 185 lumens (LUMRECT/M)
Rectangular sheet steel housing, incorporating self-extinguishing opal exit
Construction
screen and down-lighter. Colour: White
Length 425mm (pictogram 395mm)
Dimensions Height 190mm (pictogram 160mm)
Depth 60mm
Weight 2.3kg (LUMRECT/NM) 2.4kg (LUMRECT/M)
Cable Entry 20mm knockouts in side, top and rear. Rear BESA box mounting provision
Supply Voltage 230Vac +/- 10% 50Hz
Power Consumption 8VA (LUMRECT/NM) 15VA (LUMRECT/M)
Recharge Period 24 hours for full 3 hour duration
Battery NiCad 2.4V 4Ah
Light Source 300mm 8 Watt T5 fluorescent
Monitor High intensity red LED monitoring charger output and battery connection
Operating Temperature 0 to +25oC
Ingress Protection IP20
Warranty 1 year
Certification CE - Ref. BS 4533 / EN 60598-2-22

ORDER CODES
Rectangular 8W Exit Sign, LUMRECT/NM
IP20, Non-maintained
Rectangular 8W Exit Sign, LUMRECT/M
IP20, Maintained
Pictogram for Rectangular LUMRECT/PAD
Exit Sign, Arrow Down
Pictogram for Rectangular LUMRECT/PAL
Exit Sign, Arrow Left
Pictogram for Rectangular LUMRECT/PAR
Exit Sign, Arrow Right
SECTION 10: page 8

10: LUMENEX EMERGENCY LIGHTING

by Honeywell
LED Exit Sign
 Cost effective lighting solution
for interior applications
 Stylish surface - mounted
unit requiring ultra-low
maintenance/running cost
 Maintained (or non-
maintained via link)
 Housing constructed from
sheet steel and white PC/ABS

 Simple to install:
 (1) Steel back box can be
“first-fixed” to the wall
 (2) Steel gear tray is
then assembled and the
terminal block wired up LED Exit Sign with pictogram
 (3) Plastic cover is then
snapped in position over TECHNICAL SPECIFICATION
the whole assembly Emergency Duration 3 hours
 Two pre-punched 20mm holes Emergency Lamp O/P N/A
in the rear of the back box Maintained Lamp O/P N/A
PC/ABS cover, sheet steel rear housing and geartray Clear dot-printed LED
 20mm conduit entry in the Construction
blade. Colour: White
top of the housing allows for
Length 308.5mm (pictogram 316mm)
surface wiring
Dimensions Height 255mm (pictogram 170.5mm)
 Self-test facility option (for Depth 53.5mm
testing to BS 5266) Weight 1.3kg (LUMLED/W) 1.4kg (LUMLED/W/ST)
 Supplied with single-sided Cable Entry 20mm in rear or top of fitting Provision for BESA box entry
pictogram already fitted Supply Voltage 230Vac +/- 10% 50Hz
Power Consumption 5VA (LUMLED/W) 6VA (LUMLED/W/ST)
(LUMLED/PAD)
Recharge Period 24 hours for full 3 hour duration
 Uniform LED lit surface with a NiCad 2.4V 1.2Ah (LUMLED/W)
range of optional pictograms Battery
Nickel metal hydride 3.6V (LUMLED/W/ST)
Light Source In moulded LED blade
Monitor High intensity red LED monitoring charger output and battery connection
Self-test Monitor High intensity red and green LED monitoring luminaire status
ORDER CODES Operating Temperature 0 to +25oC
Ingress Protection IP20
Exit Sign, IP20, Maintained LUMLED/W
Warranty 1 year
(or non-maintained via link) Certification CE - Ref. BS 4533 / EN 60598-2-22
Self-test LED Exit Sign, LUMLED/W/ST
IP20, Maintained (or non-maintained via link)
Pictogram for LED Exit Sign, LUMLED/PAD
Arrow Down
Pictogram for LED Exit Sign, LUMLED/PAD/DS
Arrow Down, Double Sided
Pictogram for LED Exit Sign, LUMLED/PAL
Arrow Left
Pictogram for LED Exit Sign, LUMLED/PAL/DS
Arrow Left, Double Sided
Pictogram for LED Exit Sign, LUMLED/PAR
Arrow Right
Pictogram for LED Exit Sign, LUMLED/PAR/DS
Arrow Right, Double Sided
SECTION 10: page 9

10: LUMENEX EMERGENCY LIGHTING

by Honeywell
Hanging LED Exit Sign – Brass Effect
 Effective and flexible design
for high profile interior
applications
 Chain mounting system
allows unit to blend in with
decorative lighting
 Maintained (or non-
maintained via link)
 Attractively styled unit
requiring ultra-low
maintenance/running cost
 Housing constructed from
anodised extruded aluminium
 Upper steel top box is used
for termination
 Unit supplied ready assembled
Hanging LED Exit Sign with Pictogram
with a one metre long supply
cable
TECHNICAL SPECIFICATION
 No need to open the
Emergency Duration 3 hours
Emergency Lamp O/P N/A
housing unless an alternative
Maintained Lamp O/P N/A pictogram is required
Aluminium housing with sheet steel top box. Clear dot-printed LED blade.  Supplied with single-sided
Construction
Colour: Brass Effect pictogram already fitted
Length 300mm Height top box 32mm (LUMLED/PAD)
Height sign 260mm (pictogram 173mm)
Dimensions  Uniform LED lit surface with a
Chain height variable
Depth top box 70mm Depth sign 47mm
range of optional pictograms
Weight 2.0kg
Cable Entry 20mm hole in top box. Provision for BESA box entry
Supply Voltage 230Vac +/- 10% 50Hz
Power Consumption 5VA
Recharge Period 24 hours for full 3 hour duration
Battery NiCad 2.4V 1.2Ah
Light Source In moulded LED blade
Monitor High intensity red LED monitoring charger output and battery connection
Operating Temperature 0 to +25oC
Ingress Protection IP20
Warranty 1 year
Certification CE - Ref. BS 4533 / EN 60598-2-22
ORDER CODES
Hanging LED Exit Sign, LUMEXIT/B
IP20, Brass Effect, Maintained
(or non-maintained via link)
Pictogram for LED Exit Sign, LUMLED/PAD
Arrow Down
Pictogram for LED Exit Sign, LUMLED/PAD/DS
Arrow Down, Double Sided
Pictogram for LED Exit Sign, LUMLED/PAL
Arrow Left
Pictogram for LED Exit Sign, LUMLED/PAL/DS
Arrow Left, Double Sided
Pictogram for LED Exit Sign, LUMLED/PAR
Arrow Right
Pictogram for LED Exit Sign, LUMLED/PAR/DS
Arrow Right, Double Sided
SECTION 10: page 10

10: LUMENEX EMERGENCY LIGHTING

by Honeywell
Hanging LED Exit Sign – White
 Effective and flexible design
for high profile interior
applications
 Chain mounting system
allows unit to blend in with
decorative lighting
 Maintained (or non-
maintained via link)
 Attractively styled slimline
unit requiring ultra-low
maintenance/running cost
 Housing constructed from
powder coated extruded
aluminium
 Upper steel top box is used
for termination
Hanging LED Exit Sign with Pictogram
 Unit supplied ready assembled
with a one metre long supply
TECHNICAL SPECIFICATION
cable
Emergency Duration 3 hours
 Self-test facility option (for Emergency Lamp O/P N/A
testing to BS 5266) Maintained Lamp O/P N/A
 No need to open the Aluminium housing with sheet steel top box. Clear dot-printed LED blade.
Construction
housing unless an alternative Colour: White
pictogram is required Length 300mm (pictogram 316mm)
Height top box 46mm Height sign 232mm (pictogram 172mm)
 Supplied with single-sided Dimensions
Chain height variable
pictogram already fitted Depth top box 70mm Depth sign 32mm
(LUMLED/PAD) Weight 2.1kg (LUMEXIT/W) 2.2kg (LUMEXIT/W/ST)
 Uniform LED lit surface with a Cable Entry 20mm hole in top box. Provision for BESA box entry
range of optional pictograms Supply Voltage 230Vac +/- 10% 50Hz
Power Consumption 5VA (LUMEXIT/W) 6VA (LUMEXIT/W/ST)
Recharge Period 24 hours for full 3 hour duration
NiCad 2.4V 1.2Ah (LUMEXIT/W)
Battery
Nickel metal hybride (LUMEXIT/W/ST)
ORDER CODES Light Source In moulded LED blade
Monitor High intensity red LED monitoring charger output and battery connection
Hanging LED Exit Sign, LUMEXIT/W
Self-test Monitor High intensity red and green LED monitoring luminaire status
IP20, White, Maintained
Operating Temperature 0 to +25oC
(or non- maintained via link) Ingress Protection IP20
Self-test Hanging LED Exit Sign, LUMEXIT/W/ST Warranty 1 year
IP20, White, Maintained Certification CE - Ref. BS 4533 / EN 60598-2-22
(or non-maintained via link)
Pictogram for LED Exit Sign, LUMLED/PAD
Arrow Down
Pictogram for LED Exit Sign, LUMLED/PAD/DS
Arrow Down, Double Sided
Pictogram for LED Exit Sign, LUMLED/PAL
Arrow Left
Pictogram for LED Exit Sign, LUMLED/PAL/DS
Arrow Left, Double Sided
Pictogram for LED Exit Sign, LUMLED/PAR
Arrow Right
Pictogram for LED Exit Sign, LUMLED/PAR/DS
Arrow Right, Double Sided
SECTION 10: page 11

10: LUMENEX EMERGENCY LIGHTING

by Honeywell
Recessed LED Exit Sign
 Cost effective lighting solution
for interior applications
 Slim profile unit requiring
ultra - low maintenance /
running cost
 Maintained (or non-
maintained via link)
 Ideally suited for areas where
there is a height restriction
with false ceilings
 Fully recessable housing
constructed from sheet steel
 Main housing supplied with
drill points and BESA box
mounting
 Simple to install
Recessed LED Exit Sign with Pictogram
 Tabs in one end of the
geartray can be swung open
TECHNICAL SPECIFICATION
for quick wiring
Emergency Duration 3 hours
Emergency Lamp O/P N/A  Supplied with single-sided
Maintained Lamp O/P N/A pictogram already fitted
Sheet steel housing, bezel and hinge gear tray. Clear dot-printed LED blade. (LUMLED/PAD)
Construction
Colour: White  Uniform LED lit surface with a
Length 395mm (recessed base 358mm, pictogram 316mm)
range of optional pictograms
Dimensions Height 7mm (recessed base 85mm, pictogram 165mm)
Depth 143mm (recessed base 105mm)
Weight 2.7kg
Cable Entry 20mm hole in top on fitting. Provision for BESA box entry
Supply Voltage 230Vac +/- 10% 50Hz
Power Consumption 5VA
Recharge Period 24 hours for full 3 hour duration
Battery NiCad 2.4V 1.2Ah
Light Source In moulded LED blade
Monitor High intensity red LED monitoring charger output and battery connection
Operating Temperature 0 to +25oC
Ingress Protection IP20
Warranty 1 year
Certification CE - Ref. BS 4533 / EN 60598-2-22
ORDER CODES
Recessed LED Exit Sign, LUMRECESS
IP20, Maintained
(or non-maintained via link)
Pictogram for LED Exit Sign, LUMLED/PAD
Arrow Down
Pictogram for LED Exit Sign, LUMLED/PAD/DS
Arrow Down, Double Sided
Pictogram for LED Exit Sign, LUMLED/PAL
Arrow Left
Pictogram for LED Exit Sign, LUMLED/PAL/DS
Arrow Left, Double Sided
Pictogram for LED Exit Sign, LUMLED/PAR
Arrow Right
Pictogram for LED Exit Sign, LUMLED/PAR/DS
Arrow Right, Double Sided
SECTION 10: page 12

10: LUMENEX EMERGENCY LIGHTING

by Honeywell
2 x 18W Twinlight
 Suitable for interior
applications
 Cost-effective solution
for large open areas with
undefined escape routes
 Non-maintained
 Ideal for illuminating
areas which could become
dangerous if mains power
fails
 Stylish design features
adjustable lamps with
polycarbonate lenses
 Snap-fit construction
 Simple to install
 Maintenance-free batteries 18W Twinlight
 A high intensity LED on the
unit front indicates healthy TECHNICAL SPECIFICATION
supply Emergency Duration 3 hours
 Independent lamp tests give Emergency Lamp O/P 2 x 264 lumens
indications of both left and Maintained Lamp O/P N/A
3 part assembly comprising an ABS housing, steel geartray and two
right lamp integrity Construction
polycarbonate fronted projectors. Colour: Buff
Length 368mm (base housing 325mm)
Dimensions Height 283mm (base housing 155mm)
Depth 115mm
Weight 6.5kg including battery
Cable Entry 20mm knockouts in one end and rear of fitting
Supply Voltage 230Vac +/- 10% 50Hz
Power Consumption 30VA
Recharge Period 24 hours for full 3 hour duration
Battery 2 x sealed Lead Acid 6V 1.2Ah
Light Source 2 x 18 Watt Tungsten
High intensity red LED monitoring charger output and battery connection.
Monitor
Amber LEDs monitoring left and right lamp integrity
Self-test Monitor High intensity red & green LED monitoring luminaire status
Operating Temperature 0 to +30oC
IP Rating IP20
Warranty 1 year
Certification CE - Ref. BS 4533 / EN 60598-2-22

ORDER CODES
Twinlight, 2 x 18W, 3-hour, IP20, LUMTWIN
Non-maintained
Self-test Twinlight, 2 x 18W, LUMTWIN/ST
3-hour, IP20, Non-maintained
SECTION 10: page 13

10: LUMENEX EMERGENCY LIGHTING

by Honeywell
2 x 55W Twinlight
 Suitable for interior
applications
 High light output Tungsten
Halogen projectors
 Cost-effective solution
for large open areas with
undefined escape routes
 Non-maintained
 Ideal for illuminating
areas which could become
dangerous if mains power
fails
 Slimline design features
adjustable lamps with glass
lenses
 Robust construction
55W Twinlight
 Simple to install
TECHNICAL SPECIFICATION  Maintenance-free batteries
Emergency Duration 1 hour  Mains healthy indicator
Emergency Lamp O/P 2 x 1100 lumens
Maintained Lamp O/P N/A
Rectangular sheet steel enclosure finished in a two-tone durable powder
Construction coating with two polycarbonate, glass-fronted projectors. Colour: Black and
Light Grey
Length 407mm (base enclosure 360mm)
Dimensions Height 385.8mm (base enclosure 265.8mm)
Depth 117mm (base enclosure 112mm)
Weight 13.7kg including battery
Cable Entry 20mm conduit entry at each end of fitting
Supply Voltage 230Vac +/- 10% 50Hz
Power Consumption 30VA
Recharge Period 24 hours for full 1 hour duration
Battery 3 x sealed Lead Acid 12V 7Ah
Light Source 2 x 55 Watt Tungsten Halogen
Monitor High intensity red LED monitoring charger output and battery connection
Operating Temperature 0 to +25oC
Ingress Protection IP20
Warranty 1 year
Certification CE - Ref. BS 4533 / EN 60598-2-22

ORDER CODES
Tungsten Halogen Twinlight, LUMTWIN/TH
2 x 55W, 1-hour, IP20, Non-maintained
SECTION 10: page 14

10: LUMENEX EMERGENCY LIGHTING

by Honeywell
Photometric Data
Maximum permitted spacing (in metres) Maximum permitted spacing (in metres) Maximum permitted spacing (in metres)
to achieve 0.2 lux to achieve 0.5 lux to achieve 1 lux
Height (m) Tr-Tr Ax-Ax Tr-Wall Ax-Wall Tr-Tr Ax-Ax Tr-Wall Ax-Wall Tr-Tr Ax-Ax Tr-Wall Ax-Wall
LUM8/NM 2.5 11.8 6.9 4.5 2.7 8.0 4.8 2.8 1.7 5.5 3.2 1.1 0.7
3 12.3 7.3 4.5 2.8 8.0 4.8 2.5 1.5 4.8 2.8
4 12.6 7.6 4.4 2.6 7.3 4.3
6 11.9 7.0 1.1 0.8
8 5.2 3.2

LUM8/M 2.5 10.7 6.4 4.0 2.5 7.1 4.3 2.3 1.4 4.5 2.6
3 11.0 6.6 4.0 2.4 6.9 4.1 1.7 1.1 2.8 1.7
4 11.2 6.8 3.6 2.2 4.8 2.9
6 9.3 5.6

UNIHI8/NM 2.5 12 6 5 2.5


3 12.5 6 4.8 2.5
4 12.4 6 3.6 2

UNIHI8/M 2.5 12 6 5 2.5


3 12.5 6 4.8 2.5
4 12.4 6 3.6 2

LUMHIGH/NM 2.5 14.3 7.5 5.8 2.8 10.6 5.3 3.9 2.0 7.7 3.9 2.5 1.2
3 15.3 7.9 6.1 2.9 10.8 5.5 3.8 1.9 7.4 3.7 2.0 0.8
4 16.8 8.5 6.1 2.9 10.7 5.4 3.1 1.4 4.4 2.2
6 17.1 8.7 5.2 1.8 4.9 2.3
8 14.4 7.3
10 5.9 2.0

LUMHIGH/M 2.5 13.6 7.1 5.5 2.8 9.9 5.0 3.6 1.8 7.0 3.5 2.1 1.0
3 14.5 7.4 5.6 2.9 10.0 5.1 3.4 1.7 6.6 3.3
4 15.7 8.0 5.6 2.9 9.6 4.8 2.5 0.9 2.9 1.3
6 15.5 7.8 4.3 1.8
8 9.9 5.0
10

Note: All photometric data has been compiled in accordance with BS 5225: Part 3 (Method of Photometric measurement of
battery-operated emergency luminaires).

Key
Tr-Tr Spacing transverse to transverse
Tr-Wall Transverse distance to wall
Ax-Ax Spacing axial to axial
Ax-Wall Axial distance to wall
 Information currently not available – contact Gent
 Not applicable
SECTION 10: page 15

10: LUMENEX EMERGENCY LIGHTING

by Honeywell
Photometric Data
Illuminance perpendicular to beam (lux)
10m 20m
LUMTWIN 0 degrees 90 degrees 0 degrees 90 degrees
0 degrees 2.89 2.89 0.72 0.72
10 degrees 6.31 1.87 1.58 0.47
(data for single lamp) 12V 20 degrees 1.25 0.35 0.31 0.09
18W filament lamp Lamp 30 degrees 0.24 0.25 0.06 0.06
Output (1m):264 40 degrees 0.18 0.23 0.05 0.06
50 degrees 0.16 0.23 0.04 0.06
60 degrees 0.11 0.12 0.03 0.03
Illuminance perpendicular to beam (lux)
10m 20m
LUMTWIN/TH 0 degrees 90 degrees 0 degrees 90 degrees
0 degrees 248.55 248.55 62.14 62.14
10 degrees 3.09 6.85 0.77 1.71
(data for single lamp) 12V 20 degrees 1.74 2.77 0.44 0.69
55W filament lamp Lamp 30 degrees 1.07 0.84 0.27 0.21
Output (1m):1500 40 degrees 1.54 0.84 0.39 0.21
50 degrees 2.20 1.02 0.55 0.26
60 degrees 1.73 0.74 0.43 0.19

LUMINAIRE UTILISATION FACTOR DATA (self-contained luminaires at zero reflectance)


Room Index (RI)
0.75 1.00 1.25 1.50 2.00 2.50 3.00 4.00 5.00
LUM8 - 0.25 0.28 0.31 0.37 0.40 0.43 0.47 0.50
LUMHIGH - 0.29 0.33 0.37 0.44 0.48 0.52 0.56 0.59
Note: All photometric data has been compiled in accordance with BS 5225: Part 3 (Method of Photometric measurement of
battery-operated emergency lighting luminaires).
SECTION 10: page 16

10: NOVA EMERGENCY LIGHTING

by Honeywell
Optilite
 Optilite is an 8W general
purpose luminaire
 Optilite’s high light output
can reduce the number of
required luminaires to 66% of
previously accepted norms
 Suitable for use on escape
routes as defined in BS 5266
 Polycarbonate base and
diffuser
 Prestige Teletest is fitted as
standard

Optilite

TECHNICAL SPECIFICATION
Special feature Recess kits Order Code P/OP8/NM3 P/OP8/M3
considerably reduce the impression Mode Non-Maintained Maintained
of ceiling clutter. E/L Design Lumens (ELDL) 106 106
Lighting Design Lumens (LDL) N/A 380
Duration 3 Hours 3 Hours
Lamp 8W T5 fluorescent cool white
Mains Input Voltage 230V AC +10% - 6%, 50Hz
Power Consumption 3VA 40VA
Weight 1.1 Kg 1.5 Kg
Battery High temperature sealed Nickel Cadmium
2.4V 4Ah 2.4V 4Ah
Ingress Protection IP20 IP20
Environment Indoor, 0 to 25oC F

Cable Entries 1 Rear BESA and 2 side entries ( 1 per side )

Dimensions (mm)

365

396
340

ORDER CODES
106

150
120

Prestige Optilite, NM P/OP8/NM3


Prestige Optilite, M P/OP8/M3
Recess Kit OP/R
Euro Exit OPX/P
Pictogram, Arrow Down OPX/AD/P
90

Pictogram, Arrow Left OPX/AL/P


Pictogram, Arrow Right OPX/AR/P
Recess Kit (cut out 120mm x 365mm)
SECTION 10: page 17

10: NOVA EMERGENCY LIGHTING

by Honeywell
Stormlite
 Stormlite is an 8W,
weatherproof emergency
luminaire suitable for general
outdoor use, such as outside
an exit door
 The diffuser is screw fixed
to prevent tampering and
vandalism
 Polycarbonate base and
diffuser
 Suitable for use on escape
routes as defined in BS 5266
 Prestige Teletest is fitted as
standard

Stormlite

TECHNICAL SPECIFICATION
Order Code P/SM8/NM3 P/SM8/M3
Mode Non-Maintained Maintained
E/L Design Lumens (ELDL) 106 106
Lighting Design Lumens (LDL) N/A 380
Duration 3 Hours
Lamp 8W T5 fluorescent cool white
Mains Input Voltage 230V AC +10% - 5%, 50Hz
Power Consumption 3VA 40VA
Weight 1.2 Kg 1.6 Kg
Battery High temperature sealed Nickel Cadmium
2.4V 4Ah 2.4V 4Ah
Ingress Protection IP54 IP54
Environment Indoor/Outdoor, 0 to 25oC F

Cable Entries 1 Rear BESA and 2 side entries ( 1 per side )

Dimensions (mm)

365

396
340

ORDER CODES
106

150

120

Prestige Stormlite, NM P/SM8/NM3


Prestige Stormlite, M P/SM8/M3
Recess Kit OP/R
Euro Exit OPX/P
Pictogram, Arrow Down OPX/AD/P
90

Pictogram, Arrow Left OPX/AL/P


Pictogram, Arrow Right OPX/AR/P
Recess Kit (cut out 120mm x 365mm)
SECTION 10: page 18

10: NOVA EMERGENCY LIGHTING

by Honeywell
Twinspot
 A double projection
emergency luminaire for
lighting large anti-panic
areas such as factories and
warehouses

Twinspot

TECHNICAL SPECIFICATION
Design tip Assuming the average Order Code PTS220/NM3
eye level is 1.5m, this table gives Mode Non-Maintained
the maximum horizontal distance E/L Design Lumens (ELDL) 2 x 400
of the viewer to the projector. Lighting Design Lumens (LDL) N/A
Twinspot luminaires should be Duration 3 Hours
mounted at least 30o above the Lamp Twin 20W Tungsten Halogen
line of sight to avoid glare. Mains Input Voltage 230V ac +10% - 6%, 50Hz
Power Consumption 35VA
Mounting Max. Weight 11 Kg
Height Distance to Battery Maintenance free sealed Lead Acid 12V 18AH
Projector Ingress Protection IP20
Environment Indoor, 0 to 25oC
4m 4.3m
Cable Entries 2 x 20mm conduit knockout at either end
6m 7.8m
8m 11.3m
10m 14.7m

Dimensions (mm)

178
90
110
294

ORDER CODES
Twinspot PTS220/NM3
472 85
SECTION 10: page 19

10: NOVA EMERGENCY LIGHTING

by Honeywell
Trimsign
 Trimsign is a purpose built
illuminated sign suitable for
extended viewing distances
such as long corridors

Trimsign with Arrow Left Pictogram

TECHNICAL SPECIFICATION
Order Code P/TR8/NM3 P/TR8/M3 Design tip
Mode Non-Maintained Maintained
E/L Design Lumens (ELDL) N/A
Lighting Design Lumens (LDL) N/A
Duration 3 Hours
Lamp 8W T5 fluorescent cool white EXIT
Mains Input Voltage 230V ac +10% - 6%, 50Hz
Power Consumption 3VA 40VA
Weight 1.8 Kg 2.2 Kg
Battery High temperature sealed Nickel Cadmium 2.4V 4Ah
Ingress Protection IP20
Environment Indoor, 0 to 25oC F

Cable Entries 1 Rear BESA and 2 side entries (1 per side)

Dimensions (mm)

420 90

ORDER CODES
Prestige Trimsign, NM P/TR8/NM3
Prestige Trimsign, M P/TR8/M3
250

Exit TRX/EP
Pictogram, Arrow Down TRX/EAD
Pictogram, Arrow Left TRX/EAL
Pictogram, Arrow Right TRX/EAR
Recess Kit (cut out 282mm x 452mm)
SECTION 10: page 20

10: NOVA EMERGENCY LIGHTING

by Honeywell
Teletest 8 Channel Controller
Prestige Teletest is a unique facility
to make routine testing easier. The
controller continuously monitors
the system for mains failure,
charger and battery faults and
open circuit faults. The controller
simulates a mains supply failure
for a set duration. Any luminaire
which fails to operate for the
complete duration of the test
indicates its failure locally and
reports back to the controller at
the end of the test.

Prestige Teletest Eight Channel

TECHNICAL SPECIFICATION
Design tip Do not divide Order Code P/TT2008
the luminaires into zones, as Max. Number of Luminaires 100 per channel
in a fire alarm system. Connect Number of Channels 8
the luminaires in such a manner Control Access Via numeric keypad. Password protected.
that by testing one channel at a Test Periods 5 min, 1 hour and 3 hour via keypad operation.
time, the integrity of the overall LED indicators showing channel inhibited, open circuit
Local Indication per Channel
system is maintained eg. for a two system fault and luminaire failed.
channel system connect the odd Local Indication LED indicators showing system on test and test period.
number luminaires to channel 1 Volt free contacts allowing interface with the fire alarm
Remote Indication
and the even number to channel and BMS systems.
2. This is particularly relevant for Power Consumption 50mA
Max. Cable Length per Channel 1,000m
buildings which cannot be closed
Mains Input Voltage 230V + 10% - 6%, 50Hz
e.g. hotels.
Test System Cable 0.5mm twin cable insulated to 250V ac

Dimensions (mm)
395 87
19
197

274

ORDER CODES
Prestige Teletest Eight Channel P/TT2008
For flush mounting, aperture size
Flush Surround 13270-29
89 89 378mm x 245mm x 60mm
SECTION 10: page 21

10: NOVA EMERGENCY LIGHTING

by Honeywell
Photometric Data
ESCAPE ROUTE SPACING USING SELF CONTAINED LUMINAIRES
All figures are verified by the British
Min. - 1.0 LUX Min. - 0.2 LUX
Standards Institute and registered
Specified Points of Emphasis & Normal Risks Permanently Unobstructed Routes Only
by ICEL.
Ceiling Transverse to Transverse to
Transverse to Transverse to Axial to Axial Axial to Wall Transverse to Transverse to Axial to Axial Axial to Wall
Mounting Transverse Transverse
Wall (m) Axial (m) (m) (m) Wall (m) Axial (m) (m) (m)
Height (m) (m) (m)
2.5 1.3 4.7 4.4 4.0 1.2 4.5 12.4 10.0 7.6 3.0
Optilite / Stormlite
4 - 2.8 2.6 2.3 - 3.7 12.7 10.8 8.8 3.2
Non-Maintained
6 - - - - - 2.5 10.0 9.4 8.9 2.2
2.5 1.1 4.0 3.9 3.7 0.9 4.1 11.6 9.4 7.2 2.9
Optilite / Stormlite
4 - 1.5 1.1 0.8 - 3.2 11.6 10.0 8.3 2.9
Maintained
6 - - - - - 1.8 8.7 8.4 8.0 1.4

Min - 1.0 LUX Min - 0.2 LUX


Mounting Height Spacing to Wall Twinspot to Twinspot Spacing to Wall Twinspot to Twinspot
(m) (m) (m) (m) (m)
4 5.0 12.0 13.0 30.0
6 3.0 9.0 12.0 33.0
Twinspot
8 3.0 7.0 9.0 25.0
10 3.0 8.0 6.0 21.0

Note: Spacing data includes a maintenance factor of 0.8 and a maintained lamp derating factor of 0.85 as defined by BSI and
ICEL.
SECTION 10: page 22

10: NOVA EMERGENCY LIGHTING

by Honeywell
Notes
SECTION 10: page 23

by Honeywell
Section 10.1:
Central Battery Systems
SECTION 10: page 25

1 0 . 1 : C E N T R A L B AT T E R Y S Y S T E M S

by Honeywell
Central Battery Systems
Central battery systems provide
a solution to power and test an
array of emergency luminaires
all from one central point. The
luminaires are all wired back
to a main cabinet housing
the batteries and charger.
This cabinet can be housed
in a secure location that only
authorised personnel can access.
Due to the life safety importance
of emergency lighting, central
battery systems should always
be wired in fire protected cables.
This reassures the end-user that
in a fire situation the power
to the luminaires would not be
lost.

Testing and maintenance


Either AC or DC systems can be provided with a comprehensive range of slave luminaires to suit. An end user should always
ensure that regular testing and
AC Battery System Features
maintenance is carried out for
 High efficiency
all emergency lighting products
 Low operating cost
in accordance with BS5266. This
 Wide range of standard ratings available, with batteries to suit all applications
is much easier with a central
 High light levels available
battery system because testing
 Designed to comply with BS EN 50171:2001
can be controlled at one central
DC Battery System Features point. A competent engineer
 Wide range of standard ratings available should always be used to carry
 Extensive choice of battery types out maintenance.
 Extensive range of compatible luminaires
 Comprehensive instrumentation and monitoring
Cost of ownership
 Long battery life of 5 to 25 years On-going costs are also reduced
 Designed to comply with BS EN 50171:2001 because with a central battery
system the batteries can have
a design life of up to 25 years
where self-contained fittings
need changing every 4 years.
SECTION 10: page 26

1 0 . 1 : C E N T R A L B AT T E R Y S Y S T E M S

by Honeywell
Slave Luminaires
LUMHI8 Range
Mains voltage
LUMHI8/240 8W fluorescent, 240Vac
Low voltage centrally supplied versions
LUMHI8/24V, 50V 110Vac/dc input central battery system 8W slave luminaires
Power Consumption Emergency Operating
Order Code Input Voltage Weight
AC DC Lamp output Temperature
LUMHI8/24 24Vac/dc 1.2 Kg 11 VA 10W 275 Lumens 0 - +40oC
LUMHI8/50 50Vac/dc 1.2 Kg 11 VA 10W 275 Lumens 0 - +40oC
LUMHI8/110 110Vac/dc 1.2 Kg 11 VA 10W 275 Lumens 0 - +40oC
LUMHI8/240 240Vac 1.4 Kg 41 VA - 400 Lumens 0 - +40oC
LUMHI8

LUMSTORM Weatherproof Range


Low voltage centrally supplied versions
LUMSTORM/24V, 50V or 110Vac/dc input weatherproof central battery system 8W slave luminaire

Power Consumption Emergency Operating


Order Code Input Voltage Weight
Lamp Output Temperature
AC DC
LUMSTORM/24 24Vac/dc 1.2 Kg 11 VA 10W 275 Lumens 0 - +40oC
LUMSTORM/50 50Vac/dc 1.2 Kg 11 VA 10W 275 Lumens 0 - +40oC
LUMSTORM/110 110Vac/dc 1.2 Kg 11 VA 10W 275 Lumens 0 - +40oC

LUMSTORM

LUMRECT Range
Mains voltage
LUMRECT/240 Exit sign, 8W fluorescent 240Vac.
Low voltage centrally supplied versions
LUMRECT/24V, 50V or 110Vac/dc input central battery system 8W slave luminaires

Power Consumption Emergency Operating


Order Code Input Voltage Weight
Lamp Output Temperature
AC DC
LUMRECT/24 24Vac/dc 1.9 Kg 11 VA 10W 275 Lumens 0 - +40oC
LUMRECT/50 50Vac/dc 1.9 Kg 11 VA 10W 275 Lumens 0 - +40oC
LUMRECT/110 110Vac/dc 1.9 Kg 11 VA 10W 275 Lumens 0 - +40oC
LUMRECT LUMRECT/110 240Vac/dc 2.0 Kg 41 VA - 400 Lumens 0 - +40oC

LUMCIRC Range
Low voltage centrally supplied version
LUMCIRC28/110Vac/dc input IP65 weatherproof central battery system 28W 2D slave luminaires.

Power Consumption Emergency Operating


Order Code Input Voltage Weight
Lamp Output Temperature
AC DC
LUMCIRC 28/110 110Vac/dc 1.7 Kg 17 VA 21W 760 Lumens 0 - +40oC

LUMCIRC
SECTION 10: page 27

1 0 . 1 : C E N T R A L B AT T E R Y S Y S T E M S

by Honeywell
Slave Luminaires

PICTOGRAM LUMRECT LUMHI8 LUMSTORM

Down LUMRECT/PAD LUM8/PAD

Left LUMRECT/PAL LUM8/PAL

Right LUMRECT/PAR LUM8/PAR

Maximum permitted spacing (in metres) Maximum permitted spacing (in metres) Maximum permitted spacing (in metres)
to achieve 0.2 lux to achieve 0.5 lux to achieve 1 lux
Height (m) Tr-Tr Ax-Ax Tr-Wall Ax-Wall Tr-Tr Ax-Ax Tr-Wall Ax-Wall Tr-Tr Ax-Ax Tr-Wall Ax-Wall
LUMHI8 2 15.59 10.91 6.32 4.49 11.81 8.42 4.73 3.40 9.46 6.79 3.68 2.67
2.5 17.04 12.05 6.89 4.92 12.82 9.18 5.06 3.65 10.12 7.29 3.80 2.78
3 18.29 13.03 7.34 5.27 13.64 9.80 5.28 3.96 10.56 7.64 3.78 2.80
4 20.35 14.59 8.02 5.78 14.74 10.66 5.38 3.96 10.75 7.93 3.39 2.58
6 23.02 16.63 8.52 6.25 15.12 11.21 4.54 3.50 9.09 6.99

LUMSTORM 2.5 17.30 10.10 6.90 4.00 12.30 7.20 4.10 2.90 8.00 5.70 2.50 2.30
3 18.40 10.60 7.00 4.20 12.20 7.70 3.50 3.10 6.80 6.00 2.50 2.30
4 19.60 11.50 6.40 4.60 10.00 8.40 3.50 3.20 6.80 6.30 2.00 1.90
6 16.70 13.10 5.50 5.10 9.60 9.00 2.40 2.40 4.70 4.60
8 15.20 14.10 5.20 4.80 7.80 7.50
10 15.20 14.20 3.20 3.30 2.40 2.50

10
SECTION 10: page 28

1 0 . 1 : C E N T R A L B AT T E R Y S Y S T E M S

by Honeywell