Self Contained Emergency Lighting: Section 10
Self Contained Emergency Lighting: Section 10
Self Contained Emergency Lighting: Section 10
by Honeywell
Section 10:
Self Contained
Emergency Lighting
SECTION 10: page 3
by Honeywell
8W Luminaire
Suitable for a wide range
of interior and exterior
applications
Cost effective with an optically
efficient and durable lens
design
Maintained /non-maintained
versions
Weatherproof (fit seal
supplied if an IP65 rating is
required)
Snap-fit construction with
hinged gear tray
Simple to install with screw
terminal block and a BESA
box mounting facility
8W Luminaire
Stylish, slim profile design
with a range of optional
TECHNICAL SPECIFICATION
pictograms
Emergency Duration 3 hours
Emergency Lamp O/P 105 lumens
Maintained Lamp O/P 185 lumens (LUM8/M)
3 part self-extinguishing unit incorporating a polycarbonate lens, ABS/PC alloy
Construction
base and metal geartray. Colour: White
Length 343mm
Dimensions Height 78mm
Depth 101mm
Weight 1.0kg (LUM8/NM) 1.2kg (LUM8/M)
Cable Entry Drill guides on sides and one end. BESA in rear of fitting
Supply Voltage 230Vac +/- 10% 50Hz
Power Consumption 8VA (LUM8/NM) 15VA (LUM8/M)
Recharge Period 24 hours for full 3 hour duration
Battery NiCad 2.4V 4Ah
Light Source 300mm 8 Watt T5 fluorescent
Monitor High intensity red LED monitoring charger output and battery connection
Operating Temperature 0 to +25oC
Ingress Protection IP40 (IP65 when seal fitted)
Warranty 1 year
Certification CE - Ref. BS 4533 / EN 60598-2-22
ORDER CODES
8W Luminaire, IP65, LUM8/NM
Non-maintained
8W Luminaire, IP65, Maintained LUM8/M
Semi-recessing Bezel for LUM8/RB
8W Luminaire, White
Pictogram, Arrow Down LUM8/PAD
Pictogram, Arrow Left LUM8/PAL
Pictogram, Arrow Right LUM8/PAR
SECTION 10: page 4
by Honeywell
Unilux Emergency Luminaire
A flexible high light output
luminaire
A separate mounting bracket
and battery compartment
makes the Unilux easy to
install and maintain
Elegant and functional design
Unilux Luminaire
TECHNICAL SPECIFICATION
Emergency Duration 3 hours
Emergency Lamp O/P 180 lumens
Maintained Lamp O/P 220 lumens (UNIHI8/M and UNIHI8/M/ST)
3 part self-extinguishing unit incorporating a polycarbonate lens, ABS/PC alloy
Construction
base and metal geartray. Colour: White
Length 363mm
Dimensions Height 83mm
Width 149mm
Weight 1.16kg
16/20mm knockouts on side/end of fitting
Cable Entry
Provision for rear BESA box mountings
6VA Non maintained
Power Consumption
26VA Maintained
Recharge Period 24 hours for full 3 hour duration
Battery NiCad 3.6V 4Ah
Light Source 8 Watt T5 fluorescent
Indicators Green LED / Manual Test Switch
Self-test Indicator Green, Amber, Red LED / Auto test
Operating Temperature 0 to +35oC
Ingress Protection IP20
Certification CE
ORDER CODES
High Light Output 8W UNIHI8/NM
Luminaire, IP20, Non-maintained
High Light Output 8W UNIHI8/M
Luminaire, IP20, Maintained
Self-test High Light Output 8W UNIHI8/NM/ST
Luminaire, IP20, Non-maintained
Self-test High Light Output 8W UNIHI8/M/ST
Luminaire, IP20, Maintained
Pictogram, Arrow Down LUM8/PAD
Pictogram, Arrow Left LUM8/PAL
Pictogram, Arrow Right LUM8/PAR
SECTION 10: page 5
by Honeywell
High Light 8W Luminaire
Cost effective lighting solution
for both interior and exterior
applications
Designed to minimise panic
and assist finding the escape
routes
Energy efficient illumination
provided by a 28W 2D
fluorescent lamp
Maintained/non-maintained
versions
Weatherproof (IP65 rating)
Snap-fit construction
Simple to install with 20mm
gland rear entry and drill
points
High Light 8W Luminaire
Strong, neutral coloured
polycarbonate base and
TECHNICAL SPECIFICATION
PMMA diffuser
Emergency Duration 3 hours
Emergency Lamp O/P 180 lumens Clean, simple styling with
Maintained Lamp O/P 220 lumens (LUMHIGH/M and LUMHIGH/M/ST) rugged durability
3 part self-extinguishing unit incorporating a polycarbonate lens, ABS/PC alloy
Construction
base and steel geartray. Colour: White
Length 370mm
Dimensions Height 87mm (with recess bezel 44mm)
Depth 140mm
1.8kg (LUMHIGH/NM) 2.1kg (LUMHIGH/M)
Weight
1.9kg (LUMHIGH/NM/ST) 2.2kg (LUMHIGH/M/ST)
Cable Entry Gland entry points in end walls of base. BESA in rear of fitting
Supply Voltage 230Vac +/- 10% 50Hz
9VA (LUMHIGH/NM) 19VA (LUMHIGH/M)
Power Consumption
10VA (LUMHIGH/NM/ST) 21VA (LUMHIGH/M/ST)
Recharge Period 24 hours for full 3 hour duration
Battery NiCad 3.6V 4Ah
Light Source 300mm 8 Watt T5 fluorescent
Monitor High intensity red LED monitoring charger output and battery connection
Self-test Monitor High intensity red and green LED monitoring luminaire status
Operating Temperature 0 to +25oC
Ingress protection IP65
Warranty 1 year
Certification CE - Ref. BS 4533 / EN 60598-2-22
ORDER CODES
High Light Output 8W LUMHIGH/NM
Luminaire, IP65, Non-maintained
High Light Output 8W LUMHIGH/M
Luminaire, IP65, Maintained
Self-test High Light Output LUMHIGH/NM/ST
8W Luminaire, IP65, Non-maintained
Self-test High Light Output 8W LUMHIGH/M/ST
Luminaire, IP65, Maintained
Pictogram, Arrow Down LUM8/PAD
Pictogram, Arrow Left LUM8/PAL
Pictogram, Arrow Right LUM8/PAR
SECTION 10: page 6
by Honeywell
28W Antipanic Luminaire
Cost effective lighting solution
for both interior and exterior
applications
Designed to minimise panic
and assist finding the escape
routes
Energy efficient illumination
provided by a 28W 2D
fluorescent lamp
Maintained/non-maintained
versions
Weatherproof (IP65 rating)
Snap-fit construction
Simple to install with 20mm
gland rear entry and drill
points
Circular 28W Luminaire
Strong, neutral coloured
polycarbonate base and TECHNICAL SPECIFICATION
PMMA diffuser Emergency Duration 3 hours
Clean, simple styling with Emergency Lamp O/P 380 lumens
rugged durability Maintained Lamp O/P 2000 lumens (LUMCIRC28/M)
Circular unit incorporating a polycarbonate base, PMMA diffuser and removable
Construction
steel geartray. Colour: White
Diameter 360mm
Dimensions
Height 90mm
Weight 2.7kg (LUMCIRC28/NM) 3.3kg (LUMCIRC28/M)
Cable Entry 20mm gland entry points in rear of fitting
Supply Voltage 230Vac +/- 10% 50Hz
Power Consumption 9VA (LUMCIRC28/NM) 63VA (LUMCIRC28/M)
Recharge Period 24 hours for full 3 hour duration
Battery NiCad 4.8V 4Ah
Light Source 28 Watt 2D fluorescent
Monitor High intensity red LED monitoring charger output and battery connection
Operating Temperature 0 to +25oC
Ingress Protection IP65
Warranty 1 year
Certification CE - Ref. BS 4533 / EN 60598-2-22
ORDER CODES
Circular 28W Luminaire, LUMCIRC28/NM
IP65, Non-maintained
Circular 28W Luminaire, LUMCIRC28/M
IP65, Maintained
SECTION 10: page 7
by Honeywell
Rectangular 8W Exit Sign
Cost effective lighting solution
for interior applications
Suitable for mounting on
emergency escape routes as
defined by BS 5266
Maintained/non-maintained
versions
Single-sided low profile unit
with pictogram accessible
from bottom entry
Integral threshold down-
lighter
Robust construction for
simple surface-mounted
installation
Range of self-adhesive
Rectangular Exit Sign
pictogram options
TECHNICAL SPECIFICATION
Emergency Duration 3 hours
Emergency Lamp O/P 105 lumens
Maintained Lamp O/P 185 lumens (LUMRECT/M)
Rectangular sheet steel housing, incorporating self-extinguishing opal exit
Construction
screen and down-lighter. Colour: White
Length 425mm (pictogram 395mm)
Dimensions Height 190mm (pictogram 160mm)
Depth 60mm
Weight 2.3kg (LUMRECT/NM) 2.4kg (LUMRECT/M)
Cable Entry 20mm knockouts in side, top and rear. Rear BESA box mounting provision
Supply Voltage 230Vac +/- 10% 50Hz
Power Consumption 8VA (LUMRECT/NM) 15VA (LUMRECT/M)
Recharge Period 24 hours for full 3 hour duration
Battery NiCad 2.4V 4Ah
Light Source 300mm 8 Watt T5 fluorescent
Monitor High intensity red LED monitoring charger output and battery connection
Operating Temperature 0 to +25oC
Ingress Protection IP20
Warranty 1 year
Certification CE - Ref. BS 4533 / EN 60598-2-22
ORDER CODES
Rectangular 8W Exit Sign, LUMRECT/NM
IP20, Non-maintained
Rectangular 8W Exit Sign, LUMRECT/M
IP20, Maintained
Pictogram for Rectangular LUMRECT/PAD
Exit Sign, Arrow Down
Pictogram for Rectangular LUMRECT/PAL
Exit Sign, Arrow Left
Pictogram for Rectangular LUMRECT/PAR
Exit Sign, Arrow Right
SECTION 10: page 8
by Honeywell
LED Exit Sign
Cost effective lighting solution
for interior applications
Stylish surface - mounted
unit requiring ultra-low
maintenance/running cost
Maintained (or non-
maintained via link)
Housing constructed from
sheet steel and white PC/ABS
Simple to install:
(1) Steel back box can be
“first-fixed” to the wall
(2) Steel gear tray is
then assembled and the
terminal block wired up LED Exit Sign with pictogram
(3) Plastic cover is then
snapped in position over TECHNICAL SPECIFICATION
the whole assembly Emergency Duration 3 hours
Two pre-punched 20mm holes Emergency Lamp O/P N/A
in the rear of the back box Maintained Lamp O/P N/A
PC/ABS cover, sheet steel rear housing and geartray Clear dot-printed LED
20mm conduit entry in the Construction
blade. Colour: White
top of the housing allows for
Length 308.5mm (pictogram 316mm)
surface wiring
Dimensions Height 255mm (pictogram 170.5mm)
Self-test facility option (for Depth 53.5mm
testing to BS 5266) Weight 1.3kg (LUMLED/W) 1.4kg (LUMLED/W/ST)
Supplied with single-sided Cable Entry 20mm in rear or top of fitting Provision for BESA box entry
pictogram already fitted Supply Voltage 230Vac +/- 10% 50Hz
Power Consumption 5VA (LUMLED/W) 6VA (LUMLED/W/ST)
(LUMLED/PAD)
Recharge Period 24 hours for full 3 hour duration
Uniform LED lit surface with a NiCad 2.4V 1.2Ah (LUMLED/W)
range of optional pictograms Battery
Nickel metal hydride 3.6V (LUMLED/W/ST)
Light Source In moulded LED blade
Monitor High intensity red LED monitoring charger output and battery connection
Self-test Monitor High intensity red and green LED monitoring luminaire status
ORDER CODES Operating Temperature 0 to +25oC
Ingress Protection IP20
Exit Sign, IP20, Maintained LUMLED/W
Warranty 1 year
(or non-maintained via link) Certification CE - Ref. BS 4533 / EN 60598-2-22
Self-test LED Exit Sign, LUMLED/W/ST
IP20, Maintained (or non-maintained via link)
Pictogram for LED Exit Sign, LUMLED/PAD
Arrow Down
Pictogram for LED Exit Sign, LUMLED/PAD/DS
Arrow Down, Double Sided
Pictogram for LED Exit Sign, LUMLED/PAL
Arrow Left
Pictogram for LED Exit Sign, LUMLED/PAL/DS
Arrow Left, Double Sided
Pictogram for LED Exit Sign, LUMLED/PAR
Arrow Right
Pictogram for LED Exit Sign, LUMLED/PAR/DS
Arrow Right, Double Sided
SECTION 10: page 9
by Honeywell
Hanging LED Exit Sign – Brass Effect
Effective and flexible design
for high profile interior
applications
Chain mounting system
allows unit to blend in with
decorative lighting
Maintained (or non-
maintained via link)
Attractively styled unit
requiring ultra-low
maintenance/running cost
Housing constructed from
anodised extruded aluminium
Upper steel top box is used
for termination
Unit supplied ready assembled
Hanging LED Exit Sign with Pictogram
with a one metre long supply
cable
TECHNICAL SPECIFICATION
No need to open the
Emergency Duration 3 hours
Emergency Lamp O/P N/A
housing unless an alternative
Maintained Lamp O/P N/A pictogram is required
Aluminium housing with sheet steel top box. Clear dot-printed LED blade. Supplied with single-sided
Construction
Colour: Brass Effect pictogram already fitted
Length 300mm Height top box 32mm (LUMLED/PAD)
Height sign 260mm (pictogram 173mm)
Dimensions Uniform LED lit surface with a
Chain height variable
Depth top box 70mm Depth sign 47mm
range of optional pictograms
Weight 2.0kg
Cable Entry 20mm hole in top box. Provision for BESA box entry
Supply Voltage 230Vac +/- 10% 50Hz
Power Consumption 5VA
Recharge Period 24 hours for full 3 hour duration
Battery NiCad 2.4V 1.2Ah
Light Source In moulded LED blade
Monitor High intensity red LED monitoring charger output and battery connection
Operating Temperature 0 to +25oC
Ingress Protection IP20
Warranty 1 year
Certification CE - Ref. BS 4533 / EN 60598-2-22
ORDER CODES
Hanging LED Exit Sign, LUMEXIT/B
IP20, Brass Effect, Maintained
(or non-maintained via link)
Pictogram for LED Exit Sign, LUMLED/PAD
Arrow Down
Pictogram for LED Exit Sign, LUMLED/PAD/DS
Arrow Down, Double Sided
Pictogram for LED Exit Sign, LUMLED/PAL
Arrow Left
Pictogram for LED Exit Sign, LUMLED/PAL/DS
Arrow Left, Double Sided
Pictogram for LED Exit Sign, LUMLED/PAR
Arrow Right
Pictogram for LED Exit Sign, LUMLED/PAR/DS
Arrow Right, Double Sided
SECTION 10: page 10
by Honeywell
Hanging LED Exit Sign – White
Effective and flexible design
for high profile interior
applications
Chain mounting system
allows unit to blend in with
decorative lighting
Maintained (or non-
maintained via link)
Attractively styled slimline
unit requiring ultra-low
maintenance/running cost
Housing constructed from
powder coated extruded
aluminium
Upper steel top box is used
for termination
Hanging LED Exit Sign with Pictogram
Unit supplied ready assembled
with a one metre long supply
TECHNICAL SPECIFICATION
cable
Emergency Duration 3 hours
Self-test facility option (for Emergency Lamp O/P N/A
testing to BS 5266) Maintained Lamp O/P N/A
No need to open the Aluminium housing with sheet steel top box. Clear dot-printed LED blade.
Construction
housing unless an alternative Colour: White
pictogram is required Length 300mm (pictogram 316mm)
Height top box 46mm Height sign 232mm (pictogram 172mm)
Supplied with single-sided Dimensions
Chain height variable
pictogram already fitted Depth top box 70mm Depth sign 32mm
(LUMLED/PAD) Weight 2.1kg (LUMEXIT/W) 2.2kg (LUMEXIT/W/ST)
Uniform LED lit surface with a Cable Entry 20mm hole in top box. Provision for BESA box entry
range of optional pictograms Supply Voltage 230Vac +/- 10% 50Hz
Power Consumption 5VA (LUMEXIT/W) 6VA (LUMEXIT/W/ST)
Recharge Period 24 hours for full 3 hour duration
NiCad 2.4V 1.2Ah (LUMEXIT/W)
Battery
Nickel metal hybride (LUMEXIT/W/ST)
ORDER CODES Light Source In moulded LED blade
Monitor High intensity red LED monitoring charger output and battery connection
Hanging LED Exit Sign, LUMEXIT/W
Self-test Monitor High intensity red and green LED monitoring luminaire status
IP20, White, Maintained
Operating Temperature 0 to +25oC
(or non- maintained via link) Ingress Protection IP20
Self-test Hanging LED Exit Sign, LUMEXIT/W/ST Warranty 1 year
IP20, White, Maintained Certification CE - Ref. BS 4533 / EN 60598-2-22
(or non-maintained via link)
Pictogram for LED Exit Sign, LUMLED/PAD
Arrow Down
Pictogram for LED Exit Sign, LUMLED/PAD/DS
Arrow Down, Double Sided
Pictogram for LED Exit Sign, LUMLED/PAL
Arrow Left
Pictogram for LED Exit Sign, LUMLED/PAL/DS
Arrow Left, Double Sided
Pictogram for LED Exit Sign, LUMLED/PAR
Arrow Right
Pictogram for LED Exit Sign, LUMLED/PAR/DS
Arrow Right, Double Sided
SECTION 10: page 11
by Honeywell
Recessed LED Exit Sign
Cost effective lighting solution
for interior applications
Slim profile unit requiring
ultra - low maintenance /
running cost
Maintained (or non-
maintained via link)
Ideally suited for areas where
there is a height restriction
with false ceilings
Fully recessable housing
constructed from sheet steel
Main housing supplied with
drill points and BESA box
mounting
Simple to install
Recessed LED Exit Sign with Pictogram
Tabs in one end of the
geartray can be swung open
TECHNICAL SPECIFICATION
for quick wiring
Emergency Duration 3 hours
Emergency Lamp O/P N/A Supplied with single-sided
Maintained Lamp O/P N/A pictogram already fitted
Sheet steel housing, bezel and hinge gear tray. Clear dot-printed LED blade. (LUMLED/PAD)
Construction
Colour: White Uniform LED lit surface with a
Length 395mm (recessed base 358mm, pictogram 316mm)
range of optional pictograms
Dimensions Height 7mm (recessed base 85mm, pictogram 165mm)
Depth 143mm (recessed base 105mm)
Weight 2.7kg
Cable Entry 20mm hole in top on fitting. Provision for BESA box entry
Supply Voltage 230Vac +/- 10% 50Hz
Power Consumption 5VA
Recharge Period 24 hours for full 3 hour duration
Battery NiCad 2.4V 1.2Ah
Light Source In moulded LED blade
Monitor High intensity red LED monitoring charger output and battery connection
Operating Temperature 0 to +25oC
Ingress Protection IP20
Warranty 1 year
Certification CE - Ref. BS 4533 / EN 60598-2-22
ORDER CODES
Recessed LED Exit Sign, LUMRECESS
IP20, Maintained
(or non-maintained via link)
Pictogram for LED Exit Sign, LUMLED/PAD
Arrow Down
Pictogram for LED Exit Sign, LUMLED/PAD/DS
Arrow Down, Double Sided
Pictogram for LED Exit Sign, LUMLED/PAL
Arrow Left
Pictogram for LED Exit Sign, LUMLED/PAL/DS
Arrow Left, Double Sided
Pictogram for LED Exit Sign, LUMLED/PAR
Arrow Right
Pictogram for LED Exit Sign, LUMLED/PAR/DS
Arrow Right, Double Sided
SECTION 10: page 12
by Honeywell
2 x 18W Twinlight
Suitable for interior
applications
Cost-effective solution
for large open areas with
undefined escape routes
Non-maintained
Ideal for illuminating
areas which could become
dangerous if mains power
fails
Stylish design features
adjustable lamps with
polycarbonate lenses
Snap-fit construction
Simple to install
Maintenance-free batteries 18W Twinlight
A high intensity LED on the
unit front indicates healthy TECHNICAL SPECIFICATION
supply Emergency Duration 3 hours
Independent lamp tests give Emergency Lamp O/P 2 x 264 lumens
indications of both left and Maintained Lamp O/P N/A
3 part assembly comprising an ABS housing, steel geartray and two
right lamp integrity Construction
polycarbonate fronted projectors. Colour: Buff
Length 368mm (base housing 325mm)
Dimensions Height 283mm (base housing 155mm)
Depth 115mm
Weight 6.5kg including battery
Cable Entry 20mm knockouts in one end and rear of fitting
Supply Voltage 230Vac +/- 10% 50Hz
Power Consumption 30VA
Recharge Period 24 hours for full 3 hour duration
Battery 2 x sealed Lead Acid 6V 1.2Ah
Light Source 2 x 18 Watt Tungsten
High intensity red LED monitoring charger output and battery connection.
Monitor
Amber LEDs monitoring left and right lamp integrity
Self-test Monitor High intensity red & green LED monitoring luminaire status
Operating Temperature 0 to +30oC
IP Rating IP20
Warranty 1 year
Certification CE - Ref. BS 4533 / EN 60598-2-22
ORDER CODES
Twinlight, 2 x 18W, 3-hour, IP20, LUMTWIN
Non-maintained
Self-test Twinlight, 2 x 18W, LUMTWIN/ST
3-hour, IP20, Non-maintained
SECTION 10: page 13
by Honeywell
2 x 55W Twinlight
Suitable for interior
applications
High light output Tungsten
Halogen projectors
Cost-effective solution
for large open areas with
undefined escape routes
Non-maintained
Ideal for illuminating
areas which could become
dangerous if mains power
fails
Slimline design features
adjustable lamps with glass
lenses
Robust construction
55W Twinlight
Simple to install
TECHNICAL SPECIFICATION Maintenance-free batteries
Emergency Duration 1 hour Mains healthy indicator
Emergency Lamp O/P 2 x 1100 lumens
Maintained Lamp O/P N/A
Rectangular sheet steel enclosure finished in a two-tone durable powder
Construction coating with two polycarbonate, glass-fronted projectors. Colour: Black and
Light Grey
Length 407mm (base enclosure 360mm)
Dimensions Height 385.8mm (base enclosure 265.8mm)
Depth 117mm (base enclosure 112mm)
Weight 13.7kg including battery
Cable Entry 20mm conduit entry at each end of fitting
Supply Voltage 230Vac +/- 10% 50Hz
Power Consumption 30VA
Recharge Period 24 hours for full 1 hour duration
Battery 3 x sealed Lead Acid 12V 7Ah
Light Source 2 x 55 Watt Tungsten Halogen
Monitor High intensity red LED monitoring charger output and battery connection
Operating Temperature 0 to +25oC
Ingress Protection IP20
Warranty 1 year
Certification CE - Ref. BS 4533 / EN 60598-2-22
ORDER CODES
Tungsten Halogen Twinlight, LUMTWIN/TH
2 x 55W, 1-hour, IP20, Non-maintained
SECTION 10: page 14
by Honeywell
Photometric Data
Maximum permitted spacing (in metres) Maximum permitted spacing (in metres) Maximum permitted spacing (in metres)
to achieve 0.2 lux to achieve 0.5 lux to achieve 1 lux
Height (m) Tr-Tr Ax-Ax Tr-Wall Ax-Wall Tr-Tr Ax-Ax Tr-Wall Ax-Wall Tr-Tr Ax-Ax Tr-Wall Ax-Wall
LUM8/NM 2.5 11.8 6.9 4.5 2.7 8.0 4.8 2.8 1.7 5.5 3.2 1.1 0.7
3 12.3 7.3 4.5 2.8 8.0 4.8 2.5 1.5 4.8 2.8
4 12.6 7.6 4.4 2.6 7.3 4.3
6 11.9 7.0 1.1 0.8
8 5.2 3.2
LUM8/M 2.5 10.7 6.4 4.0 2.5 7.1 4.3 2.3 1.4 4.5 2.6
3 11.0 6.6 4.0 2.4 6.9 4.1 1.7 1.1 2.8 1.7
4 11.2 6.8 3.6 2.2 4.8 2.9
6 9.3 5.6
LUMHIGH/NM 2.5 14.3 7.5 5.8 2.8 10.6 5.3 3.9 2.0 7.7 3.9 2.5 1.2
3 15.3 7.9 6.1 2.9 10.8 5.5 3.8 1.9 7.4 3.7 2.0 0.8
4 16.8 8.5 6.1 2.9 10.7 5.4 3.1 1.4 4.4 2.2
6 17.1 8.7 5.2 1.8 4.9 2.3
8 14.4 7.3
10 5.9 2.0
LUMHIGH/M 2.5 13.6 7.1 5.5 2.8 9.9 5.0 3.6 1.8 7.0 3.5 2.1 1.0
3 14.5 7.4 5.6 2.9 10.0 5.1 3.4 1.7 6.6 3.3
4 15.7 8.0 5.6 2.9 9.6 4.8 2.5 0.9 2.9 1.3
6 15.5 7.8 4.3 1.8
8 9.9 5.0
10
Note: All photometric data has been compiled in accordance with BS 5225: Part 3 (Method of Photometric measurement of
battery-operated emergency luminaires).
Key
Tr-Tr Spacing transverse to transverse
Tr-Wall Transverse distance to wall
Ax-Ax Spacing axial to axial
Ax-Wall Axial distance to wall
Information currently not available – contact Gent
Not applicable
SECTION 10: page 15
by Honeywell
Photometric Data
Illuminance perpendicular to beam (lux)
10m 20m
LUMTWIN 0 degrees 90 degrees 0 degrees 90 degrees
0 degrees 2.89 2.89 0.72 0.72
10 degrees 6.31 1.87 1.58 0.47
(data for single lamp) 12V 20 degrees 1.25 0.35 0.31 0.09
18W filament lamp Lamp 30 degrees 0.24 0.25 0.06 0.06
Output (1m):264 40 degrees 0.18 0.23 0.05 0.06
50 degrees 0.16 0.23 0.04 0.06
60 degrees 0.11 0.12 0.03 0.03
Illuminance perpendicular to beam (lux)
10m 20m
LUMTWIN/TH 0 degrees 90 degrees 0 degrees 90 degrees
0 degrees 248.55 248.55 62.14 62.14
10 degrees 3.09 6.85 0.77 1.71
(data for single lamp) 12V 20 degrees 1.74 2.77 0.44 0.69
55W filament lamp Lamp 30 degrees 1.07 0.84 0.27 0.21
Output (1m):1500 40 degrees 1.54 0.84 0.39 0.21
50 degrees 2.20 1.02 0.55 0.26
60 degrees 1.73 0.74 0.43 0.19
by Honeywell
Optilite
Optilite is an 8W general
purpose luminaire
Optilite’s high light output
can reduce the number of
required luminaires to 66% of
previously accepted norms
Suitable for use on escape
routes as defined in BS 5266
Polycarbonate base and
diffuser
Prestige Teletest is fitted as
standard
Optilite
TECHNICAL SPECIFICATION
Special feature Recess kits Order Code P/OP8/NM3 P/OP8/M3
considerably reduce the impression Mode Non-Maintained Maintained
of ceiling clutter. E/L Design Lumens (ELDL) 106 106
Lighting Design Lumens (LDL) N/A 380
Duration 3 Hours 3 Hours
Lamp 8W T5 fluorescent cool white
Mains Input Voltage 230V AC +10% - 6%, 50Hz
Power Consumption 3VA 40VA
Weight 1.1 Kg 1.5 Kg
Battery High temperature sealed Nickel Cadmium
2.4V 4Ah 2.4V 4Ah
Ingress Protection IP20 IP20
Environment Indoor, 0 to 25oC F
Dimensions (mm)
365
396
340
ORDER CODES
106
150
120
by Honeywell
Stormlite
Stormlite is an 8W,
weatherproof emergency
luminaire suitable for general
outdoor use, such as outside
an exit door
The diffuser is screw fixed
to prevent tampering and
vandalism
Polycarbonate base and
diffuser
Suitable for use on escape
routes as defined in BS 5266
Prestige Teletest is fitted as
standard
Stormlite
TECHNICAL SPECIFICATION
Order Code P/SM8/NM3 P/SM8/M3
Mode Non-Maintained Maintained
E/L Design Lumens (ELDL) 106 106
Lighting Design Lumens (LDL) N/A 380
Duration 3 Hours
Lamp 8W T5 fluorescent cool white
Mains Input Voltage 230V AC +10% - 5%, 50Hz
Power Consumption 3VA 40VA
Weight 1.2 Kg 1.6 Kg
Battery High temperature sealed Nickel Cadmium
2.4V 4Ah 2.4V 4Ah
Ingress Protection IP54 IP54
Environment Indoor/Outdoor, 0 to 25oC F
Dimensions (mm)
365
396
340
ORDER CODES
106
150
120
by Honeywell
Twinspot
A double projection
emergency luminaire for
lighting large anti-panic
areas such as factories and
warehouses
Twinspot
TECHNICAL SPECIFICATION
Design tip Assuming the average Order Code PTS220/NM3
eye level is 1.5m, this table gives Mode Non-Maintained
the maximum horizontal distance E/L Design Lumens (ELDL) 2 x 400
of the viewer to the projector. Lighting Design Lumens (LDL) N/A
Twinspot luminaires should be Duration 3 Hours
mounted at least 30o above the Lamp Twin 20W Tungsten Halogen
line of sight to avoid glare. Mains Input Voltage 230V ac +10% - 6%, 50Hz
Power Consumption 35VA
Mounting Max. Weight 11 Kg
Height Distance to Battery Maintenance free sealed Lead Acid 12V 18AH
Projector Ingress Protection IP20
Environment Indoor, 0 to 25oC
4m 4.3m
Cable Entries 2 x 20mm conduit knockout at either end
6m 7.8m
8m 11.3m
10m 14.7m
Dimensions (mm)
178
90
110
294
ORDER CODES
Twinspot PTS220/NM3
472 85
SECTION 10: page 19
by Honeywell
Trimsign
Trimsign is a purpose built
illuminated sign suitable for
extended viewing distances
such as long corridors
TECHNICAL SPECIFICATION
Order Code P/TR8/NM3 P/TR8/M3 Design tip
Mode Non-Maintained Maintained
E/L Design Lumens (ELDL) N/A
Lighting Design Lumens (LDL) N/A
Duration 3 Hours
Lamp 8W T5 fluorescent cool white EXIT
Mains Input Voltage 230V ac +10% - 6%, 50Hz
Power Consumption 3VA 40VA
Weight 1.8 Kg 2.2 Kg
Battery High temperature sealed Nickel Cadmium 2.4V 4Ah
Ingress Protection IP20
Environment Indoor, 0 to 25oC F
Dimensions (mm)
420 90
ORDER CODES
Prestige Trimsign, NM P/TR8/NM3
Prestige Trimsign, M P/TR8/M3
250
Exit TRX/EP
Pictogram, Arrow Down TRX/EAD
Pictogram, Arrow Left TRX/EAL
Pictogram, Arrow Right TRX/EAR
Recess Kit (cut out 282mm x 452mm)
SECTION 10: page 20
by Honeywell
Teletest 8 Channel Controller
Prestige Teletest is a unique facility
to make routine testing easier. The
controller continuously monitors
the system for mains failure,
charger and battery faults and
open circuit faults. The controller
simulates a mains supply failure
for a set duration. Any luminaire
which fails to operate for the
complete duration of the test
indicates its failure locally and
reports back to the controller at
the end of the test.
TECHNICAL SPECIFICATION
Design tip Do not divide Order Code P/TT2008
the luminaires into zones, as Max. Number of Luminaires 100 per channel
in a fire alarm system. Connect Number of Channels 8
the luminaires in such a manner Control Access Via numeric keypad. Password protected.
that by testing one channel at a Test Periods 5 min, 1 hour and 3 hour via keypad operation.
time, the integrity of the overall LED indicators showing channel inhibited, open circuit
Local Indication per Channel
system is maintained eg. for a two system fault and luminaire failed.
channel system connect the odd Local Indication LED indicators showing system on test and test period.
number luminaires to channel 1 Volt free contacts allowing interface with the fire alarm
Remote Indication
and the even number to channel and BMS systems.
2. This is particularly relevant for Power Consumption 50mA
Max. Cable Length per Channel 1,000m
buildings which cannot be closed
Mains Input Voltage 230V + 10% - 6%, 50Hz
e.g. hotels.
Test System Cable 0.5mm twin cable insulated to 250V ac
Dimensions (mm)
395 87
19
197
274
ORDER CODES
Prestige Teletest Eight Channel P/TT2008
For flush mounting, aperture size
Flush Surround 13270-29
89 89 378mm x 245mm x 60mm
SECTION 10: page 21
by Honeywell
Photometric Data
ESCAPE ROUTE SPACING USING SELF CONTAINED LUMINAIRES
All figures are verified by the British
Min. - 1.0 LUX Min. - 0.2 LUX
Standards Institute and registered
Specified Points of Emphasis & Normal Risks Permanently Unobstructed Routes Only
by ICEL.
Ceiling Transverse to Transverse to
Transverse to Transverse to Axial to Axial Axial to Wall Transverse to Transverse to Axial to Axial Axial to Wall
Mounting Transverse Transverse
Wall (m) Axial (m) (m) (m) Wall (m) Axial (m) (m) (m)
Height (m) (m) (m)
2.5 1.3 4.7 4.4 4.0 1.2 4.5 12.4 10.0 7.6 3.0
Optilite / Stormlite
4 - 2.8 2.6 2.3 - 3.7 12.7 10.8 8.8 3.2
Non-Maintained
6 - - - - - 2.5 10.0 9.4 8.9 2.2
2.5 1.1 4.0 3.9 3.7 0.9 4.1 11.6 9.4 7.2 2.9
Optilite / Stormlite
4 - 1.5 1.1 0.8 - 3.2 11.6 10.0 8.3 2.9
Maintained
6 - - - - - 1.8 8.7 8.4 8.0 1.4
Note: Spacing data includes a maintenance factor of 0.8 and a maintained lamp derating factor of 0.85 as defined by BSI and
ICEL.
SECTION 10: page 22
by Honeywell
Notes
SECTION 10: page 23
by Honeywell
Section 10.1:
Central Battery Systems
SECTION 10: page 25
1 0 . 1 : C E N T R A L B AT T E R Y S Y S T E M S
by Honeywell
Central Battery Systems
Central battery systems provide
a solution to power and test an
array of emergency luminaires
all from one central point. The
luminaires are all wired back
to a main cabinet housing
the batteries and charger.
This cabinet can be housed
in a secure location that only
authorised personnel can access.
Due to the life safety importance
of emergency lighting, central
battery systems should always
be wired in fire protected cables.
This reassures the end-user that
in a fire situation the power
to the luminaires would not be
lost.
1 0 . 1 : C E N T R A L B AT T E R Y S Y S T E M S
by Honeywell
Slave Luminaires
LUMHI8 Range
Mains voltage
LUMHI8/240 8W fluorescent, 240Vac
Low voltage centrally supplied versions
LUMHI8/24V, 50V 110Vac/dc input central battery system 8W slave luminaires
Power Consumption Emergency Operating
Order Code Input Voltage Weight
AC DC Lamp output Temperature
LUMHI8/24 24Vac/dc 1.2 Kg 11 VA 10W 275 Lumens 0 - +40oC
LUMHI8/50 50Vac/dc 1.2 Kg 11 VA 10W 275 Lumens 0 - +40oC
LUMHI8/110 110Vac/dc 1.2 Kg 11 VA 10W 275 Lumens 0 - +40oC
LUMHI8/240 240Vac 1.4 Kg 41 VA - 400 Lumens 0 - +40oC
LUMHI8
LUMSTORM
LUMRECT Range
Mains voltage
LUMRECT/240 Exit sign, 8W fluorescent 240Vac.
Low voltage centrally supplied versions
LUMRECT/24V, 50V or 110Vac/dc input central battery system 8W slave luminaires
LUMCIRC Range
Low voltage centrally supplied version
LUMCIRC28/110Vac/dc input IP65 weatherproof central battery system 28W 2D slave luminaires.
LUMCIRC
SECTION 10: page 27
1 0 . 1 : C E N T R A L B AT T E R Y S Y S T E M S
by Honeywell
Slave Luminaires
Maximum permitted spacing (in metres) Maximum permitted spacing (in metres) Maximum permitted spacing (in metres)
to achieve 0.2 lux to achieve 0.5 lux to achieve 1 lux
Height (m) Tr-Tr Ax-Ax Tr-Wall Ax-Wall Tr-Tr Ax-Ax Tr-Wall Ax-Wall Tr-Tr Ax-Ax Tr-Wall Ax-Wall
LUMHI8 2 15.59 10.91 6.32 4.49 11.81 8.42 4.73 3.40 9.46 6.79 3.68 2.67
2.5 17.04 12.05 6.89 4.92 12.82 9.18 5.06 3.65 10.12 7.29 3.80 2.78
3 18.29 13.03 7.34 5.27 13.64 9.80 5.28 3.96 10.56 7.64 3.78 2.80
4 20.35 14.59 8.02 5.78 14.74 10.66 5.38 3.96 10.75 7.93 3.39 2.58
6 23.02 16.63 8.52 6.25 15.12 11.21 4.54 3.50 9.09 6.99
LUMSTORM 2.5 17.30 10.10 6.90 4.00 12.30 7.20 4.10 2.90 8.00 5.70 2.50 2.30
3 18.40 10.60 7.00 4.20 12.20 7.70 3.50 3.10 6.80 6.00 2.50 2.30
4 19.60 11.50 6.40 4.60 10.00 8.40 3.50 3.20 6.80 6.30 2.00 1.90
6 16.70 13.10 5.50 5.10 9.60 9.00 2.40 2.40 4.70 4.60
8 15.20 14.10 5.20 4.80 7.80 7.50
10 15.20 14.20 3.20 3.30 2.40 2.50
10
SECTION 10: page 28
1 0 . 1 : C E N T R A L B AT T E R Y S Y S T E M S
by Honeywell
Notes