EP109206 Horn - 103dB, Explosion Proof, High Output Datasheet
EP109206 Horn - 103dB, Explosion Proof, High Output Datasheet
EP109206 Horn - 103dB, Explosion Proof, High Output Datasheet
Description: Features*:
This range of light weight, flameproof horns has been • UL Listed – Class I, Div 1. Groups C & D
designed with a high weatherproof rating to cope with the • Class I, Zone 1
harsh environmental conditions found offshore and onshore • ATEX approved
in the oil, gas and petrochemical industries. • NEMA 4x, IP66
New electronic circuitry allows the DB1P and DB1HP to be • Certified temperature –13°F to +158°F (–25°C
switched between two selectable tones by either reversing to +70°C)
the supply polarity, or connecting a second voltage supply. • NFPA 72 compliant
• 4 wire diode monitored connection for operation
The higher output DB1 HP is particularly suitable for noisy in supervisory mode
environments.
• Up to 103 dBA output @ 10 feet (DB1 HP)
• Marine grade alloy
• Up to 27 output tones, user selectable
• 12V, 24V & 48 VDC, 110 VAC
• Tones can be selected remotely
• Any two tones may be switched via the external
voltage supply
*Depends on version
Explosion-proof horns shall be UL Listed for Class I, Division 1, Groups C&D, and Class I, Zone 1 hazardous locations. The horns
shall be constructed of marine grade alloy with an epoxy paint finish and shall meet NEMA 4x and IP 66 environmental requirements
over a temperature range of -13°F to 158°F (-25°C to 70°C) in hazardous and harsh environments.
The horns shall have 27 user selectable output tones. Multiple horns shall be able to operate in synchronization. Rated current draw
at 24 vdc shall not exceed 250 mA for rated sound output of 93 dBA at 10 feet or 700 mA for rated sound output of 100 dBA at 10 feet.
The horns shall be capable of direct surface mounting.
Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance
with Cooper Wheelock standard terms and conditions.
ATEX
Specification
Certification: UL Listing: Class I, Div 1, Groups C & D.
Listing No. E187688.
ATEX approved: EExd, IIB T3
Cert No. Baseefa 02ETEX0207 for DB(1P)
Cert No. Baseefa 02ETEX0209 for DBH(P)
Material: LM25 corrosion resistant alloy with stainless steel cover
screws.
ABS flare.
Finish: Epoxy paint finish as standard or to customer's specification.
Max Sound Levels: DB1(P)=93±3dB(A) (86±3dB(A) for 12V DB1).
DB1H(P)=100 ± 3dB(A) @ 10 feet
Note: Sound level is dependent upon the tone selec-
tion.
Weight: DB1P 7.7lb./3.5 Kg approx.
DB1HP 12.3lb./5.6 Kg approx.
Certified Temperature: –13°F to +158°F (–25°C to +70°C)
Ingress Protection: NEMA 4x, IP66.
Tone Selection: 27 User Selectable Tones
1 Alt Tones 800/970 Hz at 1/4 sec. 15 554 Hz for 0.1S/440 Hz for 0.1S
2 Sweeping 800/970 Hz at 7 Hz 16 Int 660 Hz 150 mS on 150 mS off
3 Sweeping 800/970 Hz at 1 Hz 17 Int 660 Hz 1.8 sec. on 1.8 sec. off
4 Continuous at 2850 Hz 18 Int 660 Hz 6.5 sec. on 13 sec. off
5 Sweeping 2400-2850 Hz at 7 Hz 19 Continuous 660 Hz
6 Sweeping 2400-2850 Hz at 1 Hz 20 Alt 554/440 Hz at 1 Hz
7 Slow Whoop 21 Int 660 Hz at 7/8 Hz
8 Sweep 1200-500 Hz at 1 Hz 22 Int 2850 Hz 150 mS on 100 mS off
9 Alt Tones 2400/2850 Hz at 2 Hz 23 Sweep 800-970 Hz at 50 Hz
10 Int Tones of 970 Hz at 1 Hz 24 Sweep 2400-2850 Hz at 50 Hz
11 Alt Tones 800/970 Hz at 7/8 Hz 25 3x970 Hz pulses 0.5 off, 1.5 off
12 Int Tone at 2850 Hz at 1 Hz 26 3x2850z pulses 0.5 on/0.5 off, 1.5 off.
13 970 Hz at 1/4 sec. on 1 sec. off 27 Int 3100 Hz 0.3 sec. on 0.7 sec. off
14 Continuous at 970 Hz
Current
Consumption: DB1(P) DB1H(P)
12V 125mA 900mA
24V 250mA 700mA
48V 250mA –
NOTE:- DB1H(P) DIMENSIONS IN BRACK- 110V 60mA 200mA
Labels: Duty and tag labels optional.
Configuration Options: Entries: Up to 3 x 1/2" or 3/4" NPT
Terminals: up to 8 x 12AWG
The following code is designed to help in the selection of the
correct unit. Build up the reference number by inserting the Single Stage - 4 wire diode monitored connection - on board diode allows unit to be
code for each component into the appropriate box. operated in supervisory mode when monitoring line in reverse polarity
Two Stage - Switchable unit available in DC versions only either by:
(i) Reversing the polarity of the supply, or,
(ii) By a 3 wire common +ve system, switching between the -ve lines
Unit Type Voltage Cable Entries Duty Labels Tag Label Features Finish
DB1P ULA Voltage Code Entries Code
Duty Labels Code Finish Code
DB1HP 12V d.c. 012 1
/2" NPT C
None N Red R
24V d.c. 024 3
/4" NPT D
Required* D Grey G
48V d.c. DB1(P) only 048 LHS 1
*(Please specify) Special S
110V a.c. 110 RHS 2
Bottom 3 Features Code
*Prefix position with entry Tag Label
Not required N
size code None N Yes* Y
e.g. C1C3 = 20mm left and Required T *Please specify
Standard Models bottom entries. *Please specify
Series Model Number Order Code Decription
DB1 DB1PULA024D1D2NNNR 109205-001 Multitone, 93dBA, 24 VDC, Red finish
DB1 DB1HPULA024D1D2NNNR 109205-002 Multitone, 100dBA, 24 VDC, Red finish