Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

NFS-3030-E Operations Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 156

Fire Alarm Control Panel

NFS-3030
Programming Manual

Document 51345
1/22/2007
P/N 51345:D1
Rev: D1
ECN 06-481
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of Heat detectors do not sense particles of combustion and
smoke detectors, heat detectors, manual pull stations, audible alarm only when heat on their sensors increases at a predeter-
warning devices, and a fire alarm control panel with remote mined rate or reaches a predetermined level. Rate-of-rise
notification capability—can provide early warning of a develop- heat detectors may be subject to reduced sensitivity over time.
ing fire. Such a system, however, does not assure protection For this reason, the rate-of-rise feature of each detector
against property damage or loss of life resulting from a fire. should be tested at least once per year by a qualified fire pro-
The Manufacturer recommends that smoke and/or heat detec- tection specialist. Heat detectors are designed to protect
tors be located throughout a protected premise following the property, not life.
recommendations of the current edition of the National Fire IMPORTANT! Smoke detectors must be installed in the
Protection Association Standard 72 (NFPA 72), manufacturer's same room as the control panel and in rooms used by the sys-
recommendations, State and local codes, and the recommen- tem for the connection of alarm transmission wiring, communi-
dations contained in the Guide for Proper Use of System cations, signaling, and/or power. If detectors are not so
Smoke Detectors, which is made available at no charge to all located, a developing fire may damage the alarm system, crip-
installing dealers. A study by the Federal Emergency Man- pling its ability to report a fire.
agement Agency (an agency of the United States government) Audible warning devices such as bells may not alert people
indicated that smoke detectors may not go off in as many as if these devices are located on the other side of closed or
35% of all fires. While fire alarm systems are designed to pro- partly open doors or are located on another floor of a building.
vide early warning against fire, they do not guarantee warning Any warning device may fail to alert people with a disability or
or protection against fire. A fire alarm system may not provide those who have recently consumed drugs, alcohol or medica-
timely or adequate warning, or simply may not function, for a tion. Please note that:
variety of reasons:
• Strobes can, under certain circumstances, cause seizures
Smoke detectors may not sense fire where smoke cannot in people with conditions such as epilepsy.
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors • Studies have shown that certain people, even when they
also may not sense a fire on another level or floor of a building. hear a fire alarm signal, do not respond or comprehend the
A second-floor detector, for example, may not sense a first- meaning of the signal. It is the property owner's responsi-
floor or basement fire. bility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
Particles of combustion or “smoke” from a developing fire on the proper reaction to alarm signals.
may not reach the sensing chambers of smoke detectors
because: • In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow. A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
• Smoke particles may become “cold,” stratify, and not reach batteries only for a specified time and only if the batteries have
the ceiling or upper walls where detectors are located. been properly maintained and replaced regularly.
• Smoke particles may be blown away from detectors by air Equipment used in the system may not be technically com-
outlets. patible with the control panel. It is essential to use only equip-
• Smoke particles may be drawn into air returns before ment listed for service with your control panel.
reaching the detector. Telephone lines needed to transmit alarm signals from a
The amount of “smoke” present may be insufficient to alarm premise to a central monitoring station may be out of service
smoke detectors. Smoke detectors are designed to alarm at or temporarily disabled. For added protection against tele-
various levels of smoke density. If such density levels are not phone line failure, backup radio transmission systems are rec-
created by a developing fire at the location of detectors, the ommended.
detectors will not go into alarm. The most common cause of fire alarm malfunction is inade-
Smoke detectors, even when working properly, have sensing quate maintenance. To keep the entire fire alarm system in
limitations. Detectors that have photoelectronic sensing excellent working order, ongoing maintenance is required per
chambers tend to detect smoldering fires better than flaming the manufacturer's recommendations, and UL and NFPA stan-
fires, which have little visible smoke. Detectors that have ion- dards. At a minimum, the requirements of NFPA 72 shall be
izing-type sensing chambers tend to detect fast-flaming fires followed. Environments with large amounts of dust, dirt or
better than smoldering fires. Because fires develop in different high air velocity require more frequent maintenance. A main-
ways and are often unpredictable in their growth, neither type tenance agreement should be arranged through the local man-
of detector is necessarily best and a given type of detector ufacturer's representative. Maintenance should be scheduled
may not provide adequate warning of a fire. monthly or as required by National and/or local fire codes and
Smoke detectors cannot be expected to provide adequate should be performed by authorized professional fire alarm
warning of fires caused by arson, children playing with installers only. Adequate written records of all inspections
matches (especially in bedrooms), smoking in bed, and violent should be kept.
explosions (caused by escaping gas, improper storage of
flammable materials, etc.). Limit-C-9-2005

2 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be Like all solid state electronic devices, this system may
connected to the fire alarm control panel. Disconnect all operate erratically or can be damaged when subjected to light-
sources of power before servicing. Control unit and associ- ning induced transients. Although no system is completely
ated equipment may be damaged by removing and/or insert- immune from lightning transients and interference, proper
ing cards, modules, or interconnecting cables while the unit is grounding will reduce susceptibility. Overhead or outside aerial
energized. Do not attempt to install, service, or operate this wiring is not recommended, due to an increased susceptibility
unit until manuals are read and understood. to nearby lightning strikes. Consult with the Technical Ser-
CAUTION - System Re-acceptance Test after Software vices Department if any problems are anticipated or encoun-
Changes: To ensure proper system operation, this product tered.
must be tested in accordance with NFPA 72 after any pro- Disconnect AC power and batteries prior to removing or
gramming operation or change in site-specific software. Re- inserting circuit boards. Failure to do so can damage circuits.
acceptance testing is required after any change, addition or Remove all electronic assemblies prior to any drilling, filing,
deletion of system components, or after any modification, reaming, or punching of the enclosure. When possible, make
repair or adjustment to system hardware or wiring. All compo- all cable entries from the sides or rear. Before making modifi-
nents, circuits, system operations, or software functions known cations, verify that they will not interfere with battery, trans-
to be affected by a change must be 100% tested. In addition, former, or printed circuit board location.
to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected Do not tighten screw terminals more than 9 in-lbs. Over-
by the change, up to a maximum of 50 devices, must also be tightening may damage threads, resulting in reduced terminal
tested and proper system operation verified. contact pressure and difficulty with screw terminal removal.

This system meets NFPA requirements for operation at 0-49º This system contains static-sensitive components.
C/32-120º F and at a relative humidity (non condensing) of Always ground yourself with a proper wrist strap before han-
85% at 30°C (86°F) per NFPA, and 93% ± 2% at 32°C ± 2°C dling any circuits so that static charges are removed from the
(89.6°F ± 1.1°F) per ULC. However, the useful life of the sys- body. Use static suppressive packaging to protect electronic
tem's standby batteries and the electronic components may be assemblies removed from the unit.
adversely affected by extreme temperature ranges and humid- Follow the instructions in the installation, operating, and pro-
ity. Therefore, it is recommended that this system and its gramming manuals. These instructions must be followed to
peripherals be installed in an environment with a normal room avoid damage to the control panel and associated equipment.
temperature of 15-27º C/60-80º F. FACP operation and reliability depend upon proper installation.
Verify that wire sizes are adequate for all initiating and indi- Precau-D1-9-2005
cating device loops. Most devices cannot tolerate more than a
10% I.R. drop from the specified device voltage.

FCC Warning
WARNING: This equipment generates, uses, and can Canadian Requirements
radiate radio frequency energy and if not installed and This digital apparatus does not exceed the Class A limits
used in accordance with the instruction manual may for radiation noise emissions from digital apparatus set
cause interference to radio communications. It has been out in the Radio Interference Regulations of the Cana-
tested and found to comply with the limits for class A dian Department of Communications.
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable Le present appareil numerique n'emet pas de bruits radi-
protection against such interference when devices are oelectriques depassant les limites applicables aux appa-
operated in a commercial environment. Operation of this reils numeriques de la classe A prescrites dans le
equipment in a residential area is likely to cause interfer- Reglement sur le brouillage radioelectrique edicte par le
ence, in which case the user will be required to correct ministere des Communications du Canada.
the interference at his or her own expense.

Acclimate Plus™, HARSH™, NIS™, Notifier Integrated Systems™, NOTI•FIRE•NET™, and ONYXWorks™ are all trademarks; and FlashScan®, NION®,
NOTIFIER®, ONYX®, UniNet®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. Echelon® is a registered trademark and
LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are
registered trademarks of the Microsoft Corporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary of General Electric Company.
©Thursday, January 25, 2007 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 3


Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about
our online Help or printed manuals, you can email us.
Please include the following information:
• Product name and version number (if applicable)
• Printed manual or online Help
• Topic Title (for online Help)
• Page number (for printed manual)
• Brief description of content you think should be improved or corrected
• Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact
Technical Services.

4 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Table of Contents
Section 1: General Information................................................................................................ 9
1.1: About This Manual ........................................................................................................................................9
1.2: Supplemental Information .............................................................................................................................9
1.3: Introduction to the Control Panel ................................................................................................................10
1.3.1: Features..............................................................................................................................................10
1.4: Navigating Menu and Programming Screens ..............................................................................................11
1.5: Basic Procedure ...........................................................................................................................................11
1.6: Getting Started .............................................................................................................................................11
1.6.1: Password Change...............................................................................................................................12
Section 2: Main Menu ............................................................................................................. 15
2.1: Event Counts Display ..................................................................................................................................15
2.2: Multiple Event List ......................................................................................................................................15
2.3: History Display (History Select Screen)......................................................................................................15
2.4: Read Status ..................................................................................................................................................16
2.5: Program/Alter Status....................................................................................................................................16
2.6: Printer Functions..........................................................................................................................................16
Section 3: Program ................................................................................................................. 17
3.1: General Information.....................................................................................................................................17
3.2: Panel Program..............................................................................................................................................18
3.2.1: Panel Program Menu (1)....................................................................................................................18
3.2.2: Network Parameters ..........................................................................................................................19
3.2.3: Panel Settings ....................................................................................................................................21
3.2.4: Panel Timers (Menu 1) ......................................................................................................................23
3.2.5: Panel Timers (Menu 2) ......................................................................................................................25
3.2.6: LCD Programming ............................................................................................................................26
3.2.7: ACS Programming ............................................................................................................................26
3.2.8: Supervision ........................................................................................................................................30
3.3: Panel Program Menu (2)..............................................................................................................................31
3.3.1: Password Change...............................................................................................................................31
3.3.2: Weekly Occupancy Schedule ............................................................................................................31
3.3.3: Remote Display Menu .......................................................................................................................32
3.3.4: Loop Configuration ...........................................................................................................................33
3.3.5: Custom Action Message....................................................................................................................35
3.3.6: Event Logging ...................................................................................................................................36
3.3.7: Holiday Menu ....................................................................................................................................36
3.4: Point Program ..............................................................................................................................................37
3.4.1: Detector Point ....................................................................................................................................38
3.4.2: Module Point .....................................................................................................................................43
3.4.3: Panel Circuit Module.........................................................................................................................47
3.4.4: General Zone .....................................................................................................................................51
3.4.5: Releasing Zone ..................................................................................................................................51
3.4.6: Logic Zone.........................................................................................................................................52
3.4.7: Trouble Zone .....................................................................................................................................55
3.4.8: Annunciator Board Label ..................................................................................................................56
3.5: Delete Program ............................................................................................................................................56
3.6: Autoprogram Menu .....................................................................................................................................58
3.6.1: To Create a New Program .................................................................................................................58
3.6.2: To Add/Delete Devices from the Program ........................................................................................58
3.6.3: Confirmation Screens ........................................................................................................................59
Section 4: Alter Status............................................................................................................ 65
4.1: Disable/Enable Point Selection....................................................................................................................65
4.2: Disable/Enable .............................................................................................................................................66

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 5


Table of Contents

4.3: Detector Sensitivity......................................................................................................................................67


4.3.1: Sensitivity Select ...............................................................................................................................67
4.4: Clear Verify Counters ..................................................................................................................................69
4.5: Clear History ................................................................................................................................................69
4.6: Walk Test......................................................................................................................................................70
4.6.1: Walk Test Menu ................................................................................................................................72
4.6.2: Walk Test Loops Parameters .............................................................................................................73
4.6.3: Advanced Walk Test Activation........................................................................................................73
4.6.4: Devices Test Selection.......................................................................................................................74
4.7: Program Time/Date......................................................................................................................................75
4.8: Control On/Off Point Select.........................................................................................................................76
4.8.1: Control Off.........................................................................................................................................76
4.8.2: Control On .........................................................................................................................................77
Section 5: Service Screens.................................................................................................... 79
5.1: Version Information .....................................................................................................................................79
5.2: Power-up Screen ..........................................................................................................................................80
5.3: Bootloader Screen ........................................................................................................................................81
5.3.1: LCD-160 Download Menu ................................................................................................................81
5.3.2: Loop Download Menu .......................................................................................................................82
5.4: Download Screen .........................................................................................................................................83
5.5: Application Corrupt Screen .........................................................................................................................83
Appendix A: Menu Hierarchy................................................................................................ 85
A.1: Screens Overview .......................................................................................................................................85
Appendix B: Releasing Applications .................................................................................. 89
B.1: Releasing Zones ..........................................................................................................................................89
B.2: NFPA Releasing Applications.....................................................................................................................90
B.3: Abort Switches ............................................................................................................................................90
B.3.1: ULI Abort Switch..............................................................................................................................92
B.3.2: IRI Abort Switch ...............................................................................................................................93
B.3.3: NYC Abort Switch............................................................................................................................94
B.3.4: AHJ Abort Switch .............................................................................................................................96
B.3.5: Cross Zones.......................................................................................................................................97
B.3.6: Using Type Codes for Releasing Zones............................................................................................98
B.4: Miscellaneous............................................................................................................................................112
B.4.1: Initiating Devices ............................................................................................................................112
B.4.2: Warning Sounders...........................................................................................................................112
B.4.3: Auxiliary Control Functions ...........................................................................................................112
B.4.4: ACS Annunciation ..........................................................................................................................112
Appendix C: Special Zone Outputs..................................................................................... 113
C.1: Presignal and Positive Alarm Sequence (PAS) .........................................................................................113
C.1.1: What is Presignal and PAS?............................................................................................................113
C.1.2: Selecting Presignal and PAS Outputs .............................................................................................113
C.2: Coding Functions for Panel Circuit Outputs .............................................................................................114
Appendix D: AWACS™ Applications................................................................................. 115
D.1: AWACS Overview ....................................................................................................................................115
D.2: AWACS Features ......................................................................................................................................115
D.2.1: Drift Compensation and Smoothing ...............................................................................................115
D.2.2: Maintenance Warnings – Three Levels ..........................................................................................116
D.2.3: Self-Optimizing Pre-Alarm.............................................................................................................117
D.2.4: Detector Sensitivity.........................................................................................................................117
D.2.5: Cooperative Multi-Detector Sensing ..............................................................................................118
D.3: Pre-Alarm..................................................................................................................................................118
D.3.1: Definition ........................................................................................................................................118

6 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Table of Contents

D.3.2: Alert Level ......................................................................................................................................118


D.3.3: Action Level ...................................................................................................................................119
D.4: Detector Sensitivity Settings.....................................................................................................................119
D.4.1: How to Select Pre-Alarm and Alarm Sensitivity............................................................................119
D.4.2: To Test Detectors Set Below 0.50% Obscuration per Foot............................................................121
D.5: Detector Status Display.............................................................................................................................121
D.5.1: Detector Maintenance Display .......................................................................................................121
D.5.2: Print a Detector Maintenance Report .............................................................................................122
D.5.3: To Interpret a Detector Status Display or Maintenance Report .....................................................122
Appendix E: CBE: Zones and Equations............................................................................ 125
E.1: Zones .........................................................................................................................................................125
E.2: Equations ...................................................................................................................................................126
E.2.1: Arguments .......................................................................................................................................126
E.2.2: Logic Equations ..............................................................................................................................126
E.2.3: Trouble Equations ...........................................................................................................................129
Appendix F: Detector Initialization...................................................................................... 131
F.1: Overview....................................................................................................................................................131
F.2: To Replace a Detector with a Different Type of Detector .........................................................................131
Appendix G: Type Codes ..................................................................................................... 133
G.1: What are Type Codes?...............................................................................................................................133
G.2: How to Select a Type Code .......................................................................................................................133
G.3: Type Codes for Input Devices ...................................................................................................................134
G.3.1: Overview.........................................................................................................................................134
G.3.2: Type Codes for Intelligent Detectors..............................................................................................134
G.3.3: Type Codes for Monitor Modules ..................................................................................................135
G.4: Type Codes for Output Devices ................................................................................................................136
G.5: FlashScan Codes........................................................................................................................................137
Appendix H: System Troubles............................................................................................. 139
Appendix I: Local Settings................................................................................................... 141
I.1: Singapore....................................................................................................................................................141
I.2: Chicago.......................................................................................................................................................142
Glossary................................................................................................................................ 143
Index....................................................................................................................................... 147

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 7


Table of Contents

8 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Section 1: General Information

1.1 About This Manual


The following graphics appear in the manual to indicate a caution, a warning, or a note.

WARNING: Information about procedures that could cause irreversible damage to the
! control panel, irreversible loss of programming data or personal injury.

CAUTION: Information about procedures that could cause programming errors, runtime
! errors, or equipment damage.

NOTE: Information that highlights an important part of the preceding or subsequent text or
illustration.

1.2 Supplemental Information


The table below provides a list of document sources (manuals) containing additional information
regarding the NFS-3030 and optional peripherals. The NOTIFIER document (DOC-NOT) chart
provides the current document revision. A copy of this document is included in every NOTIFIER
shipment.

For information on… Refer to… Part No.


Installation NFS-3030 Installation Manual 51330
Operation NFS-3030 Operations Manual 51344
Main Power Supply AMPS-24/E 51907
SLC Wiring Instructions SLC Wiring Manual 51253
Off-line programming utility VeriFire™ Tools CD help file VERIFIRE-TCD
Compatible Devices Device Compatibility Document 15378
Annunciators Annunciator Control System 15842
Annunciator Fixed Module 15048
ACM-8R Annunciator Control Module 15342
LCD-160Manual 51850
LCD-80 Manual 15037
LDM Series Lamp Driver Annunciator 15885
SCS Smoke Control System 15712
NCA Network Control Annunciator Manual 51482
RPT-485W/RPT-485WF EIA-485 Annunciator Loop Repeater 15640
Auxiliary Power Supply,Charger ACPS-2406 Installation Manual 51304
APS-6R Instruction Manual 50702
CHG-120 Battery Charger Manual 50641
FCPS-24 Field Charger/Power Supply Manual 50059
Cabinets & Chassis CAB-3/CAB-4 Series Cabinet Installation Instructions 15330
Transponders & Transmitters DPI-232 Manual 51499
RFX Wireless Transmitter Manual 51012
TM-4 Instructions (Reverse Polarity Transmitter) 51490
UDACT Manual (Universal Digital Alarm 50050
Communicator/Transmitter) 15888
XP Transponders Manual 50786
XP5 Series Manual
Universal Zone Coder UZC-256 Universal Zone Coder 15216
UZC-256 Programming 15976

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 9


General Information Introduction to the Control Panel

For information on… Refer to… Part No.


Voice Alarm Systems & Voice XPIQ Manual 51013
Evacuation VEC 25/50 Manual 50686
Voice Alarm System Manual 51252
RM-1 Series Remote Microphone Instructions 51138
ACT-2 Instructions 51118
Networking Noti•Fire•Net Version 4.0 and Higher Manual 51584
NCM-W/F Instructions 51533
NCS ONYX™ Network Version 4.0 and Higher 51658

Figure 1.1 Supplemental Documentation

1.3 Introduction to the Control Panel


The NFS-3030 is an intelligent Fire Alarm Control Panel (FACP) with features suitable for most
applications.
There are two basic configuration options for the NFS-3030. It can be ordered with:
• a front display/keypad, which allows programming and viewing options at the panel, or
• no display/keypad.
This manual gives programming instructions using the front display/keypad.
Displayless Mode
When there is no keypad/display at the panel, it is controlled by remote annunciators. VeriFire™
Tools programming is required. The displayless panel has four buttons on its circuit board that are
service-level switches for local operation should it become necessary. They are the only buttons,
and are clearly marked with ACK for Acknowledge, SIGSIL for Signal Silence, SYSRST for
System Reset, and LAMP TEST. These buttons are mainly for installer use: the operator should
utilize a remote annunciator for these functions, if possible. The status indicator LEDs on the
circuit board are the same as on the display/keypad (refer to the NFS-3030 Operating Manual for
LED descriptions.
Refer to VeriFire™ Tools for information on programming without an NFS-3030 display/keypad.
A PC is required when using VeriFire™.
Canadian applications must conform to ULC requirements for displays and network control. Refer
to the Canadian Applications appendix in this panel’s installation manual.

1.3.1 Features
Programming features include the following:
• Ease of use - Field program the control panel without special software skills.
• Local programming - program directly from the control panel keypad to reduce installation
time.
• PC programming - input long data entry programming information on a PC; transfer
programming data between a PC and the control panel.
• Autoprogram option - automatically detect newly installed, addressable devices, allowing
quicker installation.
• Security - use passwords to control access to the control panel and protect programming.
• Large display option - 640 character screen, 16 lines x 40 characters

10 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Navigating Menu and Programming Screens General Information

1.4 Navigating Menu and Programming Screens


The Main Menu (refer to Figure 2.1) leads to screens with various menu and programming options.
Choices may be made from the menu screens by pressing the soft key closest to the menu option.
Appendix A, “Menu Hierarchy” gives the programming menu hierarchy: refer to this appendix for
an overall view of the layout of the screens.
Field information may be added/modified using the keyboard and special function keys.
Arrow keys on the keyboard can be used to navigate between fields on a screen if there are no soft
keys to select the fields.
Scrolling through a list of selections in a screen field can be performed either by repeatedly
pressing the associated soft key, or by pressing the Next Selection/Previous Selection special
function keys on the Display/Keypad.
Pressing a BACK soft key on a screen returns the programmer to the previous screen without saving
the information entered.
Pressing an ACCEPT soft key will save the information entered on the screen. It may also return to
the previous screen and/or perform other functions as described in the soft key section for each
screen.
When the FACP can not read an address (that is, if the point entered on the screen for processing
does not exist) it will display an error screen for several seconds, then return to the screen where the
address was entered. The user must check his input and investigate the state of the point.

1.5 Basic Procedure


For initial programming of the panel, or for major changes and additions, the following basic
procedure is recommended to prevent errors resulting in reprogramming and wasted time.
• Use work sheets to record the exact information for every detector, module, annunciator point
and software zone in the system. Pay close attention to the Software Type IDs. For voice
systems, pay close attention to AMG annunciator point commands. The panel program may
also be created using VeriFire™ Tools and downloaded to the panel after assembly and power-
up.
• Assemble and apply power to the control panel as described in this panel’s installation manual.
All system boards must be physically installed.
• Read this manual before programming.
• Enter/change master and user passwords.
• Enter panel and network parameters.
• Program all devices and thoroughly test the entire system. The Walk Test feature can be used to
test devices and their programming.
• Make a hard-copy record of the program on the printer.
• Save the program by uploading it using VeriFire™ Tools.

1.6 Getting Started


Once the system has been physically installed, programming may begin. The user may program at
any time except while there is an unacknowledged alarm present.
To ensure security, passwords should be entered at this time to replace the factory default settings.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 11


General Information Getting Started

1.6.1 Password Change


The NFS-3030 has two password levels; master and user. There is one master password, which
grants access to all system programming. There are nine user passwords, each of which may be
assigned access to the programming change menus, the alter status menus, or both. A user
password does not give access to or allow change to any password parameters, not even its own.
Only the master password will allow access to password change screens.
The panel arrives with factory default settings of 00000000 for the master password, and 11111111
for one user password.
Follow the steps below to change the factory settings:
1. Press PROGRAM/ALTER STATUS at the Main Menu screen.
2. Using the keyboard, enter eight zeroes (00000000) after ENTER PASSWORD .
3. Press the ACCEPT soft key.
4. Press the PANEL PROGRAM MENU soft key.
5. Press the MORE soft key.
6. Press the PASSWORD CHANGE soft key.

CHANGE PASSWORD

MASTER PASSWORD

USER PASSWORD

BACK

Figure 1.2 Change Password Screen

Soft Keys
MASTER PASSWORD - Press to change the master password
USER PASSWORD - Press to change the user password.

NOTE: Only a master can change another password.

Master Password
Press the MASTER PASSWORD Soft Key to display the following screen. Type in the new password
that will replace the factory default password: there can be up to eight alphanumeric characters.
Press the enter key on the keyboard. RE-ENTER PASSWORD will appear. Retype the password for
verification. Press enter to save the new password.

12 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Getting Started General Information

CHANGE MASTER PASSWORD

ENTER PASSWORD ********

RE-ENTER PASSWORD ********

BACK

Figure 1.3 Change Master Password Screen

User Password
Press the USER PASSWORD soft key to display the following screen.

CHANGE USER PASSWORD

USER:1 REFERENCE:JOHN

ENTER PASSWORD ********

RE-ENTER PASSWORD ********

MODE: PROGRAM/ALTER STATUS ACCEPT

BACK

Figure 1.4 Change User Password Screen

Soft Keys
USER: Press this soft key to scroll through the nine user password numbers. When this key is
pressed, the rest of the display will update to reflect information for each new record. Stop at the
password number that requires entering.
MODE: Press this soft key to select the user’s level of access. Levels are as follows:
• PROGRAM/ALTER STATUS Gives access to the Program Change Menu and Alter Status
Menu.
• ALTER STATUS Gives access to the Alter Status Menu
• NONE Gives no access.
REFERENCE: Press this key to enter a maximum 20-character alphanumeric label that identifies the
user. Press the enter key on the display/keyboard to enter the information.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 13


General Information Getting Started

ENTER PASSWORD - Press to enter a new password. Type in up to eight alphanumerics on the
keyboard, then press enter. RE-ENTER PASSWORD will appear. Retype the password for
verification.
ACCEPT: After entering all password information and retyping the password at the prompt, press this
soft key to save all the password information.
Incorrect or Forgotten Password
If a password is entered incorrectly, the panel will respond by displaying an INVALID
PASSWORD message and a code. The programmer may hit the escape key and re-enter the
password correctly. However, if the password has been forgotten, record the code and contact
NOTIFIER. After proper authentication, the master password can be determined by deciphering the
code. An example of the message that would appear on the display follows:
INVALID PASSWORD:
9066-21FS-7D78-5FA4-6163

Code

14 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Section 2: Main Menu
The Main Menu screen is the means by which the programmer can access displays, history
information, printing and programming menus. This screen is accessible from the System Normal
Screen, and from most other screens by pressing the BACK soft key until it displays.

LAKEVIEW GENERAL HOSPITAL


SYSTEM NORMAL

11:58:45A WED AUG 25, 2004

EVENT COUNTS DISPLAY READ STATUS

PROGRAM/ALTER STATUS

MULTIPLE EVENT LIST PRINTER FUNCTIONS

HISTORY DISPLAY BACK

Figure 2.1 Main Menu Screen

Soft Keys
Pressing the soft keys brings the user to the screens described below.

2.1 Event Counts Display


Pressing the EVENT COUNTS DISPLAY soft key on the Main Menu brings up the EVENT
COUNTS screen. This screen will automatically display if an off-normal event requiring
acknowledgement occurs. The display consists of current counts of off-normal events in six
categories: the counts include both acknowledged and unacknowledged events.
Refer to this panel’s operations manual for an illustration and description of the Event Counts
Display.

2.2 Multiple Event List


Pressing the Multiple Event List soft key shows off-normal events simultaneously in groups of
eight. It displays automatically for off-normal events when the Canada event order has been
selected. (Refer to Event Ordering in “Panel Settings” on page 21 for information on display
order.)
Refer to this panel’s operations manual for an illustration and description of the Multiple Event
List.

2.3 History Display (History Select Screen)


The History Select screen allows the user to select a type of history file to view, and to set time/date
or point range viewing parameters.
Refer to this panel’s operations manual for an illustration and description of History Display.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 15


Main Menu Read Status

2.4 Read Status


Pressing the Read Status soft key brings up screens to view the present status of points, zones, and other
system information. Refer to this panel’s operations manual for a full description of Read Status.

2.5 Program/Alter Status


Pressing the Program/Alter Status soft key brings up screens for panel programming, point
programming, autoprogramming, clear programming, altering the status of points, walk test, and
other information. Refer to Sections 3, and 4 for a full description of Program/Alter Status.

2.6 Printer Functions


Pressing the Printer Functions soft key brings up screens to print reports. Refer to this panel’s
operations manual for a description of Printer Functions. This key will appear only if a printer
operation has been selected. Refer to “Supervision” on page 30 for selection information.

16 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Section 3: Program

3.1 General Information


The NFS-3030 operates with two levels of programming: Program, and Alter Status.
Program level allows change to the essential control panel functions such as point functions, system
functions, and passwords. Program level change requires the master password, or a user password
that allows access to the Program level. All password information can be changed with a master
password only.
Alter Status level allows change to operating parameters, such as detector sensitivity, or time/date,
or Walk Test. The master password, or a user password that allows access to the Alter Status level,
is required.

NOTE: All events except troubles are annunciated during programming. When an annunciated
event occurs, the panel will automatically exit the programming screen and the Event Counts
menu screen will appear.

To access the Program level, press the Program/Alter Status soft key on the Main Menu and at the
prompt enter a master password, or a user password that allows access to the Program level. The
following screen will display.

NOTE: No program menus will display if a user password is entered that has access to Alter
Status level only: the Alter Status menu will be the sole menu choice

LAKEVIEW GENERAL HOSPITAL


SYSTEM NORMAL

10:22:34A FRI SEP 24, 2004


PROGRAM/ALTER STATUS

ALTER STATUS MENU DELETE PROGRAM MENU

AUTOPROGRAM MENU

PANEL PROGRAM MENU

POINT PROGRAM MENU BACK

Figure 3.1 Program/Alter Status Screen

Press a soft key with the word “program” in its menu to bring up the associated program menu.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 17


Program Panel Program

When programming the panel for the first time, press the DELETE PROGRAM MENU soft key,
which brings up the Delete Program Menu screen (Refer to Figure 3.46). Press the CLEAR ALL
PROGRAMMING button, then ACCEPT, to ensure that the panel is set to defaults and clear of
programs.

NOTE: Clearing all programs is not necessary when initial programming with a database
downloaded from VeriFire™.

The logical sequence for initial programming is to program the panel parameters first, then to
program the individual points through autoprogramming and/or point programming.

3.2 Panel Program


Panel programming provides the means to change settings for the panel system as a whole, as well
to address and program annunciator points.

3.2.1 Panel Program Menu (1)


Press the Panel Program Menu for the following choices.

PANEL PROGRAM MENU

NETWORK PARAMETERS LCD DISPLAY

ACS PROGRAMMING

PANEL SETTINGS SUPERVISION

PANEL TIMERS MORE

BACK

Figure 3.2 Panel Program Menu 1 Screen

18 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Panel Program Program

3.2.2 Network Parameters


Press the Network Parameters soft key on Panel Program Menu 1 to bring up the following screen.
If the panel will operate as a standalone unit and not part of a network, the node label is the only
field that needs to be entered: it is the label that appears as part of the System Normal message.

NETWORK PROGRAMMING

NODE NUMBER: 000

NODE LABEL:
LAKEVIEW GENERAL HOSPITAL

STYLE: STYLE 7 IP ACCESS

CH A. THRESHOLD: HIGH ACCEPT

CH B. THRESHOLD: LOW BACK

Figure 3.3 Network Programming Screen

Soft Keys
NODE NUMBER: Enter the network node number of this panel. For standalone NFS-3030, the
network node number will be 000. A valid network node number range is 1-240. Once the soft key
has been pressed, the number may be typed in from the keypad, or the Next/Previous Selection
special function key on the keypad may be used to toggle through online node numbers. The
network node number may be viewed by pressing the Lamp Test special function key longer than
five seconds. (Refer to “Version Information” on page 79 ). Default: 000
NODE LABEL: Enter the network node label for this panel. This is the label that appears in the
System Normal message. Default: <blank>
STYLE: Select the wiring style as 4 or 7. Default: style 4
CHANNEL A THRESHOLD, CHANNEL B THRESHOLD: Enter HIGH or LOW, for high or low
threshold setting for channel A or B on the NCM module. Default: HIGH
IP ACCESS: Press this soft key to bring up the IP ACCESS screen.
ACCEPT: Press this soft key to save the information entered on this screen.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 19


Program Panel Program

IP ACCESS Screen

NOTE: Use of the IP ACCESS feature is subject to the approval of the local AHJ.

This screen allows the programmer to set the IP Access. This setting allows the disabling/enabling
of commands, downloads and programming from the Wide Area Network (WAN).

IP ACCESS

IP ACCESS: ON

ACCEPT

BACK

Figure 3.4 IP Access Screen


Soft Keys
IP ACCESS: Press the soft key to scroll through the choices. Press ACCEPT at the desired setting.
Settings are:
ON - IP commands, downloads and programming are allowed.
OFF - IP commands, downloads and programming are NOT allowed. (default)
TIMED - IP commands, downloads and programming are allowed for a two-hour period, after
which the setting will revert to OFF.

NOTE: Enabling IP ACCESS allows downloads over a local area network (LAN) or the internet
(Wide Area Network - WAN) using VeriFire Tools through a Noti•Fire•Net™ Web Server (NWS),
or a wide-area enabled NCS through a PC version of Noti•Fire•Net™ Gateway.

Always verify system operation after programming changes are made in this manner.

20 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Panel Program Program

3.2.3 Panel Settings


Press the Panel Settings soft key on the Panel Program Menu 1 screen to choose panel settings.

PANEL SETTINGS

LOCAL CONTROL: YES REMINDER MENU

PIEZO: ON MORE

PROPRIETARY SUPERVISING STATION: NO

EVENT ORDERING: USA ACCEPT

DISPLAY ADDRESS: YES BACK

Figure 3.5 Panel Settings (1) Screen

Soft Keys
LOCAL CONTROL: Press this soft key to toggle between Yes and No. This option disables (No) or
enables (Yes) local panel control of the Signal Silence, System Reset, and Drill Fixed Function
keys, as well as SIGNAL SILENCE, SYSTEM RESET, and ACKNOWLEDGE soft keys. A setting of
No (disable) turns the panel piezo sounder off, overriding the next field if PIEZO is set to ON.
Default: Yes

NOTE: A setting of NO (disable) will disable key switch operation.

NOTE: ACS devices programmed for acknowledge, signal silence, system reset and drill are not
affectted by this setting: these commands will still function at the devices if LOCAL CONTROL is set to
No.

PIEZO:Press this soft key to toggle between Off and On. This option enables (On) or disables
(Off) the panel piezo from sounding when alarms or troubles occur. A setting of On is overridden if
LOCAL CONTROL is set to No. Default: On
PROPRIETARY SUPERVISING STATION:Press this soft key to enable (Yes) or disable (No)
Local Receive mode. When enabled, events and the clearing of events must be handled one at a
time: each must be acknowledged. Latching events require a system reset. The panel will override a
setting of Yes if the Node Number is greater than zero. Default: No
EVENT ORDERING: Press this soft key to toggle between USA and Canada ordering priorities.
This order is applied to events shown in the Multiple Events List screen. Default: USA
USA Event Order Canada Event Order
Fire Fire
Security Supervisory
Supervisory Trouble
Trouble Prealarm
Prealarm Disabled
Disabled

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 21


Program Panel Program

DISPLAY ADDRESS: Press this soft key to toggle between Yes and No. Choose Yes to display all
point address information at the top of event screens and in printouts. Choose No to suppress
address information display and printing. Default: Yes
REMINDER MENU: Press this soft key to bring up the Reminder Menu screen.
ACCEPT: Press this soft key to save the information entered on this screen.
MORE: Press this key to progress to the second Panel Settings screen.

PANEL SETTINGS

LCM LOCAL MODE: YES

PANEL CIRCUIT BELL CODING: MARCH

DCC PARTICIPATION: NO

LOCAL SETTINGS ACCEPT

DEFAULT SETTINGS BACK

Figure 3.6 Panel Settings (2) Screen

Soft Keys
LCM LOCAL MODE: Press this soft key to toggle between Yes and No. Enter Yes to enable all SLCs
to participate in local mode. When enabled, all LCMs will operate together in a limited fashion
when communication is lost with the NFS-3030 CPU. Inputs on LCM loops (and associated LEM
loops, if installed) will activate outputs on all loops
• for those inputs and outputs that have been set with point programming to participate in local
mode, and
• when type codes are the same point type: that is, an input with a fire type code will activate
an output with a fire type code.(Refer to Appendix G, “Type Codes”, on page 133 for point
types).
Default: NO
PANEL CIRCUIT BELL CODING: Press to toggle between MARCH and TEMPORAL. This is a
global setting: ZF8 must be entered in the zone map of any panel circuit point that will participate
in this coding. Refer to “Coding Functions for Panel Circuit Outputs” on page 114 for more
information. Default: MARCH
DCC PARTICIPATION: Press this key to program the panel for DCC (Display and Control Center)
participation. This network function ensures that one location at a time is in command of the
Acknowledge, System Reset, Signal Silence and Drill functions. Default: NO

CAUTION:
! On systems utilizing the DCC function, all locations that can participate in DCC should be set to
YES.

22 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Panel Program Program

LOCAL SETTINGS:Press this soft key to proceed to the Local Settings screen. Press the soft key
to scroll through the selections. The default is that there are no special local settings. Other settings
are explained in Appendix I, “Local Settings”.
DEFAULT SETTINGS: Press this soft key to activate default settings for the following:
Program setting for: Default:
Local Control Yes
Piezo On
Proprietary Supervising No
Station
Event Ordering USA
Display Address Yes
LCM Local Mode No
Panel Circuit Bell Coding March
DCC Participation No

Reminder Menu
Press the Reminder Menu soft key on the Panel Program Menu 1 screen to set the trouble reminder.

REMINDER MENU

TROUBLE REMINDER: YES

ACCEPT

BACK

Figure 3.7 Reminder Menu Screen

Soft Keys
TROUBLE REMINDER: Press this soft key to toggle between the two possibilities:
YES: Choose this to initiate a daily 11:00AM reminder that there are uncleared troubles in the
system. The reminder will appear on the screen and will sound a piezo (if the piezo is enabled).
NO: Choose this if no reminder is desired. Default: YES
ACCEPT: Press this soft key to save the information entered on this screen.

3.2.4 Panel Timers (Menu 1)


Press the Panel Timers soft key on the Panel Program Menu 1 screen to display the following
screen.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 23


Program Panel Program

PANEL TIMERS

VERIFY TIME: 30 VERIFY=PREALARM: NO

MAXIMUM VERIFICATION COUNT: 00

AC FAIL DELAY: 8 HOURS MORE

SILENCE INHIBIT:00:00 ACCEPT

AUTO SILENCE: OFF BACK

Figure 3.8 Panel Timers (Menu 1) Screen

Soft Keys
VERIFY TIME: Press this soft key to set the Alarm Verification timer. Type in a value of 0-60
(seconds), which will delay initiating devices set for Alarm Verification from signaling for the
amount of time entered. If a second alarm occurs while the alarm verification timer is counting, the
timer will stop and the alarm will signal immediately. Default: 30

NOTE: This value may not exceed 30 seconds for ULC installations.

MAXIMUM VERIFICATION COUNT: Press and enter a value from 0-20 for a maximum
verification count threshold value that applies to detectors set to participate in Alarm Verification.
A value of zero produces no verification trouble. When the counter exceeds the threshold value
entered, a trouble is generated to the panel. Default: 20
AC FAIL DELAY: Press this soft key to set the timing for the time delay from AC Failure to when
the trouble is reported. Type in a value of 6-12 (hours), or 0 (zero). A value of zero will cause
immediate notification. Default: 8
The onboard trouble relay ( TB3 on the CPU-3030 ) will activate and TM-4s will report according
to this setting.
UDACTs are notified immediately of AC failure by the panel, regardless of the panel’s delay
setting. Once the UDACT receives notification, it operates according to its own programmed AC
Fail Delay reporting schedule.
Example: AC Failure occurs at 1:00 p.m. on a panel with an AC FAIL DELAY setting of 8
hours. The UDACT is set for notification after 6 hours.
Time Event
1:00 p.m. AC Failure. Panel notifies UDACT. Panel and UDACT timers begin countdown to
report time.
7:00 p.m. UDACT reports.
9:00 p.m. TM-4 reports, TB3 trouble relay activates.

The AMPS-24, ACPS-2406, and XPIQ power supplies must be set to an AC Delay value of 0
(zero) when used with this panel.
SILENCE INHIBIT: Press to enter a value from 0 (disabled) to 5 minutes. This software timer
disables the SIGNAL SILENCE key function for the time entered when a fire alarm occurs. The
timer starts at the first alarm only; it does not restart with each new alarm. Default: 0

24 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Panel Program Program

AUTO SILENCE: Press to enter a value of OFF (no Auto Silence Timer), or a value of 10, 15 or 20
minutes. This global software timer functions like pressing the SIGNAL SILENCE key. For
example, if a value of 10 is entered, the control panel will silence all active outputs programmed as
silenceable after ten minutes. Default: 0FF

NOTE: This value must be 20 minutes for ULC installations.

VERIFY=PREALARM: Press this soft key to enter Yes or No for displaying Prealarm during alarm
verification. Default: NO

3.2.5 Panel Timers (Menu 2)


Press the MORE soft key on the Panel Timers Menu 1 screen to display the following screen.

PANEL TIMERS

PAS: OFF

PRESIGNAL DELAY: MM:SS

DEFAULT TIMERS

ACCEPT

BACK

Figure 3.9 Panel Timers (Menu 2) Screen

Soft Keys
PAS: Press to toggle between the choices of OFF or ON for PAS (Positive Alarm Sequence). Refer
to Appendix C, “Special Zone Outputs” for an explanation of this option. Default: OFF
PRESIGNAL DELAY: Press to enter a value of 00:00 (OFF) or a value of 1:00 to 3:00 minutes (in
the format MM:SS, where MM= minutes, SS=seconds). This feature initially causes alarm signals
to sound only in specific areas, monitored by qualified personnel. This allows delay of the alarm for
up to 3 minutes after the start of alarm processing. Refer to Appendix C, “Special Zone Outputs”
for further explanation of this option. Default: 3:00
DEFAULT TIMERS: Press this soft key to activate default settings for the following:
Program setting for: Default:
Verify Time 30 seconds
Max. Verify 20
AC Fail Delay 8 hours
SIlence Inhibit 0 (disabled)
Auto Silence Off
Verify=Prealarm No
PAS OFF
Presignal Delay 3 minutes

ACCEPT: Press this soft key to save the information entered on this screen and return to the
previous screen.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 25


Program Panel Program

3.2.6 LCD Programming


The LCD Programming screen allows the user to vary the contrast of the display and turn the
backlight on or off.

LCD PROGRAMMING

LCD INTENSITY: 50%

BRIGHTER DEFAULT

DARKER CURRENT

LANGUAGE: ENGLISH ACCEPT

BACKLIGHT ON EXCEPT AC FAIL BACK

Figure 3.10 LCD Display Screen

Soft Keys
BRIGHTER: Press this soft key to increase contrast. The intensity will increase by approximately
5% with each press of the key.
DARKER: Press this soft key to decrease contrast. The intensity will decrease by approximately
5% with each press of the key.
LANGUAGE: Press this soft to choose the language that will display on the LCD. Menu choices are
ENGLISH, HEBREW, PORTUGUESE and SPANISH.
To change the language display on an LCD-160, refer to “LCD-160 Download Menu” on page 81.
BACKLIGHT: Press this soft key to select one of the following backlighting options: ON EXCEPT
AC FAIL, OFF, or ON. When ON EXCEPT AC FAIL is selected, the backlight will turn off when
the power supply designated as the main power supply experiences AC failure. (The designation is
made at the Supervision screen using the MAIN POWER SUPPLY AC FAIL ADDRESS field. Refer
to “Supervision” on page 30.)
Default: ON
DEFAULT: Press to select the factory default setting (60%).
CURRENT:Press to select the intensity that was in effect when the screen was accessed..
ACCEPT: Line 5 (which displays LCD INTENSITY: 50% in the figure above) will change
value when the INTENSITY soft keys are pressed. Press ACCEPT to save the desired setting.

3.2.7 ACS Programming


An ACS device is a remote device used by the panel to annunciate certain system messages, and/or
to act with limited commands. A total of 32 annunciator devices may be present on the EIA-485
ACS circuit; however, some devices have associated expander devices, and an NFS-3030 ACS
circuit can accomodate up to 3,072 annunciator points. The ACS Programming and ACS Point
Programming screens in this section allow the user to define the mapping and functional mode of
these devices and points. Each annunciator board may be labeled using the ACS Label Menu.
(Refer to “Annunciator Board Label” on page 56).

26 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Panel Program Program

NOTE: Smoke Control devices must be set as FSCS or HVAC annunciator types. In addition to
its 64 smoke control points, when an SCS device is operating in FSCS (Firefighters Smoke
Control Station) mode, there are 32 additional points which function as alarm points. They can be
mapped to a zone or point to send the SCS device into a fire alarm state when any of the
additional 32 points is activated. Any of the 32 alarm points that are used must be set to
MONITOR mode from the panel. Any of these points that are not used can be set to NONE. Refer
to the SCS manual for further information on Smoke Control devices.

NOTE: When using an AMG, the address it occupies (an address of 25 through 32, typically
address 32 ) must be set to annunciator type AMG, and address one must be set to annunciator
type 64PT.

UDACT and TM-4 communicators, as well as the UZC Zone Coder, are installed on the same
EIA-485 ACS circuit as annunciators, and so are included with annunciator programming. The
TM-4 occupies one of the 32 annunciator addresses, and the UDACT can occupy one or more of
these addresses. The UZC can occupy up to four annunciator addresses, each with 64 points. When
the UDACT or UZC expand beyond one annunciator address, 64PT should be used for the
subsequent address types, and the annunciator addresses should be sequential. Other than address
assignment, there is no ACS point programming for these devices. Refer to the specific device
manual for more information.
Press the ACS Programming soft key at the Panel Program screen to invoke the following screen.
Press the up and down arrow keys on the keypad to navigate through the annunciator addresses.
There will be a cursor highlighted at the current annunciator address position.

ACS PROGRAMMING

A01:64PT A02:64SYS A03:96PT A04:TM4


A05:UDACT A06:96SYS A07:FSCS A08:UZC
A09: NO A10: NO A11: NO A12: NO
A13: NO A14: NO A15: NO A16: NO
A17: NO A18: NO A19: NO A20: NO
A21: NO A22: NO A23: NO A24: NO
A25: NO A26: NO A27: NO A28: NO
A29: NO A30: NO A31: NO A32:AMG

ANNUNCIATOR TYPE ACCEPT

POINT PROGRAMMING BACK

Figure 3.11 ACS Programming Screen

Soft Keys
ANNUNCIATOR TYPE: When the cursor is placed at the desired address, press this soft key to
scroll through the following list of types. Stop at the appropriate type.

Type Used for


64 PT 64 point annunciation
64SYS 64 point annunciation, with first 8 points reserved
96PT 96 point annunciation
96SYS 96 point annunciation, with first 8 points reserved
UDACT UDACT, first address. Any additional UDACT
annunciator addresses should be programmed as
64PT and be sequential.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 27


Program Panel Program

TM4 TM-4
AMG AMG
FSCS Smoke control modules set for FSCS mode
HVAC Smoke control modules set for HVAC mode
UZC Universal Zone Coder, first address. Any additional
UZC annunciator addresses should be programmed
as 64PT and be sequential.

POINT PROGRAMMING: Press this soft key to proceed to the ACS Point Programming screen.
ACCEPT: Press this soft key to save all the changes made and return to the previous screen (Panel
Program).
ACS Point Programming
ACS Point Programming can be reached by pressing POINT PROGRAMMING at the ACS
Programming screen. This screen allows the programmer to assign a mode and sources to each
annunciator point at the annunciator address. One ACS input may be used to control multiple panel
circuit or SLC output modules by listing the output points in the SOURCE fields. This feature
applies to the following Types: 64PT, 64SYS, 96PT, and 96SYS.

NOTE: Panel circuit or SLC output modules with releasing Type IDs may not be listed in the
annunciator source fields.

NOTE: This FACP supports ACM-24AT/ACM-48A annunciators and their expanders with either
64 or 96 points at an address, as well as ACM-16AT/ACM-32A/LDM-32 annunciators with 64
points at an address.

ACS POINT PROGRAMMING

POINT: A27P04

MODE: CONTROL

SOURCE: L01M037 L01M038


P10.2

NEXT ACCEPT

PREVIOUS BACK

Figure 3.12 ACS Point Programming Screen

Soft Keys
POINT: Press this soft key to enter the ACS point number. The format is AxxPyy, where A is the
two-digit device address, P is the two-digit point number. Enter a leading zero for one-digit
numbers.

28 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Panel Program Program

MODE: Press this soft key to enter the ACS mapping mode. Refer to the following chart for
possible mode choices and descriptions of their functions.

ACS Point Function Explanation


Mode The point...

None is not programmed. No messages are sent from or received at this point. LEDs at this
point do not light.

Control will change the state of up to eight panel The Point Active LED is lit if a corresponding mapped point is
circuits or control modules to off or on active. The Status (trouble) LED is on when a point or zone is
when its button is pushed. disabled or in trouble.
This mode is not for use with an ACS point with no switch, or with
a TM-4 or UDACT.

Monitor will show the current status of a specified The Point Active LED is lit if the corresponding mapped point or
point or zone. zone is active. The Status (trouble) LED is on if that point or zone
is disabled or in trouble. If the point has a button, it has no effect
when pushed.

Telephone supports telephone functionality when Both the Point Active LED and the Status (trouble) LED will flash
mapped to a telephone point. Press the if a telephone has been placed in the jack at the mapped
button to connect the mapped point with telephone point. Otherwise, the Point Active LED is lit if the
the telephone station. corresponding point or zone is active. The Status (trouble) LED is
lit if that point or zone is in trouble or disabled.
This mode is for use with ACS Series annunciator points
configured for telephone operation.

Disable will change the state of a point or zone The Point Active LED is lit if the corresponding mapped point or
specified through mapping from enabled zone is active. The Status (trouble) LED is lit if that point or zone
to disabled, or from disabled to enabled, is disabled or in trouble.
when its button is pushed. This mode is not for use with an ACS point with no switch, or with
See Caution below this table. a TM-4, UDACT, or smoke control device.

Acknowledge will act like an Acknowledge soft key or The Point Active LED is lit when there are any fire alarms in the
button on the panel, acknowledging an system. The Status (trouble) LED is lit when there are troubles in
event when its button is pushed. the system.

Silence will act like the Signal Silence button on The Point Active LED is lit if all silenceable outputs have been
the panel, silencing all silenceable silenced. The Status (trouble) LED is lit if not all silenceable
outputs when its button is pushed. outputs have been silenced after the button is pushed.

Reset will act like the System Reset button on No LED will ever light at this point.
the panel, resetting the panel when its This mode is not for use with an ACS point with no switch, or with
button is pushed. a TM-4, UDACT, or smoke control device.

Drill will act like the Drill button on the panel, The Point Active LED lights when the button is pushed and the
initiating a fire drill when its button is system has entered the drill state. The Status (trouble) LED will
pushed. never light.
This mode is not for use with an ACS point with no switch, or with
a TM-4, UDACT, or smoke control device.

CAUTION: When a disabled output is enabled, it will be affected by conditions existing in the
! system that would normally affect it. For example, when a condition exists in the system that would
normally turn the output on, the output will turn on when it is enabled.

SOURCE: Pressing this soft key will select the Source field and also toggle between display
formats if a point value is allowed. Enter a point or zone, or the panel’s node number if the mode
type is a system function such as acknowledge or reset.
Up to eight sources are allowed when CONTROL mode is chosen.
ACCEPT: Press this soft key to save the changes to the point displayed. The next point address will
appear.
BACK: Press this soft key to exit the screen without saving, and return to the ACS Programming
Screen.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 29


Program Panel Program

3.2.8 Supervision
From the Panel Program Menu (1), select SUPERVISION to display the following screen.

SUPERVISION

MAIN PS AC FAIL ADDRESS: LXXMXXX

PRINTER: 80-COLUMN

AUXILIARY TROUBLE REPORTING:NO ACCEPT

TAMPER INPUT: NO BACK

Figure 3.13 Supervision Screen

Soft Keys
MAIN POWER SUPPLY AC FAIL ADDRESS: Press to enter the “Monitor AC Fail” (base plus
one) address of the main power supply. Refer to the main power supply manual for complete
addressing information. Type in the address using the keypad.
The LCD backlight will turn off when this power supply experiences AC failure (see BACKLIGHT
in “LCD Programming” on page 26).
PRINTER: Press to scroll through the types of printer supervision: NONE, 40-COLUMN,
40-COLUMN SUPERVISED, 80-COLUMN, 80-COLUMN SUPERVISED, 40 GRAPHIC, 80
GRAPHIC, 80 GRAPHIC SUPERVISED. The printer will not be active if NONE is selected. If a
SUPERVISED selection is made, the printer will be supervised. Default: NONE

NOTE: When changing from an 80-column or 80-column supervised to an 80 graphic or 80


graphic supervised printer (or vice-versa) , settings must be changed at the printer. Refer to this
panel’s installation manual for the settings.

AUXILIARY TROUBLE REPORTING: Press to toggle between Yes and No. Choose Yes if a
trouble bus cable has been attached at J5 of the CPU-3030. Default: NO
TAMPER INPUT: Press the soft key to toggle between Yes, No, and AKS-1.
Yes/No reports (YES) or does not report (NO) a tamper situation at the panel cabinet door (as
determined by an STS-1 tamper switch connected as shown in this panel’s installation
manual).
AKS-1 should be selected when there is an AKS-1 key switch connected to the panel cabinet
door (which allows the operator to use Signal Silence, Reset, Drill and Acknowledge functions
when a key turns the lock to “Enable”). Default: NO
ACCEPT: Press to save changes and return to previous menu.

30 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Panel Program Menu (2) Program

3.3 Panel Program Menu (2)


Pressing the MORE soft key at Panel Program Menu 1 displays the Panel Program Menu 2 screen.

PANEL PROGRAM MENU

PASSWORD CHANGE EVENT LOGGING

WEEKLY OCCUPANCY SCHEDULES HOLIDAY MENU

REMOTE DISPLAY MENU

LOOP CONFIGURATION

CUSTOM ACTION MESSAGE BACK

Figure 3.14 Panel Program Menu 2 Screen

Soft Keys
Press a soft key to bring up the associated menu.

3.3.1 Password Change


Refer to paragraph Figure 1.6.1 on page 12 for information on password change.

3.3.2 Weekly Occupancy Schedule


The user may specify up to ten different schedules; the one displayed when the screen is invoked is
the one that is currently in effect.

WEEKLY OCCUPANCY SCHEDULE

WEEKLY OCCUPANCY SCHEDULE: 10


SUNDAY - , -
MONDAY 08:00-12:00, 13:00-18:00
TUESDAY 08:00-12:00, 13:00-18:00
WEDNESDAY 08:00-12:00, 13:00-18:00
THURSDAY 08:00-12:00, 13:00-18:00
FRIDAY 08:00-12:00, 13:00-18:00
SATURDAY 08:00-12:00, -
HOLIDAY - , -
ACCEPT

BACK

Figure 3.15 Weekly Occupancy Schedule Screen

Use the arrow keys on the keyboard to navigate between occupancy time fields: use the keypad to
type in the time values.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 31


Program Panel Program Menu (2)

SOFT KEYS
WEEKLY OCCUPANCY SCHEDULE: Press this soft key to toggle between schedules 1 - 10. A
value of zero indicates no schedule.
ACCEPT: Press this to save changes made on the screen.

3.3.3 Remote Display Menu


This screen displays when the REMOTE DISPLAY MENU soft key is pressed at the Panel
Programming Menu 2 screen.

NOTE: To change the language of the remote display, or to program the panel banner to appear
in the remote display, refer to“LCD-160 Download Menu” on page 81.

REMOTE DISPLAY MENU

D01:YES D02:NO D03:NO D04:NO


D05:NO D06:NO D07:NO D08:NO
D09:NO D10:NO D11:NO D12:NO
D13:NO D14:NO D15:NO D16:NO
D17:NO D18:NO D19:NO D20:NO
D21:NO D22:NO D23:NO D24:NO
D25:NO D26:NO D27:NO D28:NO
D29:NO D30:NO D31:NO D32:NO
INSTALL REMOTE DISPLAY

POINT PROGRAMMING BACK

Figure 3.16 Remote Display Menu Screen

Soft Keys
INSTALL REMOTE DISPLAY: To install a remote display, press the arrow keys to place the
cursor on the line next to the remote display address to be installed. Press this soft key until YES
displays. Default:No
POINT PROGRAMMING: Once a display has been installed, press this soft key to program the
display point.

32 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Panel Program Menu (2) Program

Remote Display Point Programming

REMOTE DISPLAY MENU

DISPLAY POINT
D01

POINT LABEL
EAST WING HALLWAY

LOCAL CONTROL:YES

NEXT SELECTION ACCEPT

PREVIOUS SELECTION BACK

Figure 3.17 Remote Display Point Programming Screen

Soft Keys
DISPLAY POINT: Press this soft key to bring the cursor to the underlined field. Use the keypad to
type in the desired display address.
POINT LABEL: Press this soft key to bring the cursor to the underlined label field. Type in a label
of up to 40 characters that will appear in trouble messages.
LOCAL CONTROL: Press to toggle between YES and NO. A setting of YES enables local control at
the remote display.

3.3.4 Loop Configuration


This screen displays when the LOOP CONFIGURATION soft key is pressed at the Panel
Programming Menu 2 screen. Here the programmer chooses one of the ten possible SLC loops for
further definition.

LOOP CONFIGURATION

LOOP SELECTION
Lyy (LOOP)

NEXT LOOP ACCEPT

PREVIOUS LOOP BACK

Figure 3.18 Loop Configuration Screen

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 33


Program Panel Program Menu (2)

Soft Keys
POINT SELECT: Pressing this soft key will invoke the cursor at the underlined field. Enter the
loop number desired (01 through 10) in the yy of the Lyy format.
NEXT/PREVIOUS SELECTION: Press either key to go forward or back through the loop
selections.
ACCEPT: Press to proceed to the Loop Point Programming screen.
Loop Point Programming

LOOP POINT PROGRAMMING

INSTALLED: YES BLINK MODE: _ON

DETECTOR POLL: CLIP

MODULE POLL: CLIP

RAPID POLL: ENABLED ACCEPT

WIRING STYLE: 6 BACK

Figure 3.19 Loop Point Programming Screen

Soft Keys
INSTALLED: Press this soft key to choose YES or NO, depending on whether an SLC is installed
at this address.
FlashScan and CLIP Mode
FlashScan devices can be programmed to run in either CLIP or FlashScan mode. The types can not
be mixed on a loop: for example, if Loop 1 is programmed with a FlashScan module poll, CLIP
modules may not be used on that loop.
A detector’s LEDs will light a steady green for several seconds while it is subjected to a detector
test during FlashScan polling. Each detector is tested this way on a regular basis. During the short
time the LEDs are on steady, the detector is not providing fire protection.
DETECTOR POLL: Press to select FLASHSCAN or CLIP loop polling.
MODULE POLL: Press to select FLASHSCAN or CLIP loop polling.
RAPID POLL: For CLIP mode only - enable or disable Rapid Poll for CLIP. This feature will poll
the first 20 modules more often to speed response on manual pull stations.
WIRING STYLE: Press to select the NFPA wiring style (4 or 6) of the loop. If Style 6 is entered
when the wiring is Style 4, a trouble message will be generated at the panel.
BLINK MODE: Press to enable (ON) or disable (OFF) detector LED blinking for this loop.

34 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Panel Program Menu (2) Program

3.3.5 Custom Action Message


A Custom Action Message appears when the MORE INFORMATION soft key is pressed when an
event is displayed on the Event Counts screen. This panel supports up to 100 Custom Action
Messages.

CUSTOM ACTION MESSAGE

CUSTOM ACTION MESSAGE: 001

MESSAGE
Edit
Custom
Action
Message here.

ACCEPT

VIEW BACK

Figure 3.20 Custom Action Message Screen

CUSTOM ACTION MESSAGE:Enter a number with a value of 001 to 100 to display the
corresponding Custom Action Message, or to add or edit a message.
MESSAGE: Enter/edit a custom message in the four lines indicated. The message may be up to 160
characters.
VIEW: Press this soft key to view the message that corresponds to the number entered in the
underlined field.
ACCEPT: Press to save any change made to the message and return to the previous screen.

NOTE: A printout of all the messages may be obtained by entering the Print Programming Menu
(2) and pressing the CUSTOM ACTION MESSAGES soft key.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 35


Program Panel Program Menu (2)

3.3.6 Event Logging


This menu gives the option of logging Non-fire Activations and Output Activations into a history
file.

EVENT LOGGING

NON-FIRE ACTIVATIONS: YES

OUTPUT ACTIVATIONS: YES

ACCEPT

BACK

Figure 3.21 Event Logging Screen

Press the appropriate softkey to choose event logging (Yes) and no event logging (No). When Yes
is chosen, the activations are logged into history and printed.

3.3.7 Holiday Menu


This menu is used to create a list of up to 15 holidays, which are used together with the Occupancy
Schedule to determine holiday occupancy hours. For example, the schedule displayed in Figure
3.15, “Weekly Occupancy Schedule Screen” on page 31, Schedule 10, has blank fields in the
Holiday row. This Occupancy Schedule defines the schedule for the dates on the Holiday Menu
screen below: there will be no occupancy hours on these dates.
The Holiday Menu is displayed when the Holiday Menu soft key is pressed at the Panel
Programming (2) Menu.

HOLIDAY MENU

MM/DD/YY

01 01/01/**
02 05/30/04
03 07/04/**
04 09/06/04
ANY YEAR 05 12/25/**

NEXT SELECTION ACCEPT

PREVIOUS SELECTION BACK

Figure 3.22 Holiday Menu Screen

36 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Point Program Program

The cursor will appear in the date fields, and may be moved using the keyboard arrow keys. Type to
add/edit any holiday dates.
SOFT KEYS
ANY YEAR: Press to place asterisks in the YY section of the field. An asterisk denotes any year.
NEXT/PREVIOUS SELECTION: Press to view the next or previous group of five holidays.
ACCEPT: Press to save changes to the date fields and to return to the Panel Program Menu.

3.4 Point Program


The Point Program allows the programmer to enter/change point information for detectors,
modules, panel circuits, and general, releasing, logic and trouble zones.
Press the Point Programming Menu soft key of the Program/Alter Status Menu to display the
screen below.

POINT PROGRAM MENU

POINT SELECT:
LyyDzzz (DETECTOR)

NEXT POINT ACCEPT

PREVIOUS POINT BACK

Figure 3.23 Point Program Menu

Soft Keys
POINT SELECT: Press until the desired point type appears. The types - detector, module, panel
circuit module, general zone, logic zone, trouble zone, or ACS Board - appear in the parenthesis
after the point formats. Enter the desired point address in the format field.
ACCEPT: Press to progress to the appropriate screen, based on the type of point selected.
NEXT/PREVIOUS SELECTION: Press to scroll backward or forward to the next or previously
installed point.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 37


Program Point Program

3.4.1 Detector Point


This screen displays when a detector is chosen at the Point Program menu (see Figure 3.23 on
page 37 ).

DETECTOR POINT PROGRAMMING


L03D123
TYPE:
SMOKE (PHOTO)

FLASHSCAN TYPE: PHOTO

POINT LABEL:
MORE

EXTENDED LABEL:
ACCEPT
ZONE MAP:
Z003, Z104, Z105, Z106, Z107,
Z110, Z114, Z115, Z116, Z117 BACK

Zone Map Zone Map position 10


position 1 - Zone Map position 6
(primary zone)

Figure 3.24 Detector Point Programming Screen

The point address is displayed in line 3 of this screen. Existing point information is displayed in the
fields.
Soft Keys
TYPE: Press this soft key to scroll through the point type choices: stop at the appropriate selection.
If a new point is being added, no other field will be displayed until TYPE: is entered and the
ACCEPT soft key is pressed . At this point, the rest of the fields will appear.
FLASHSCAN CODE LABEL: Press to scroll through a list of FlashScan Codes. Stop when the
appropriate label appears (Table G.4 on page 137 for codes and descriptions). If the detector is not a
FlashScan type, choose NONE.
POINT LABEL: Press this soft key to place the cursor at this field. Type in a 20-character
maximum point label that will appear in message formats. If no entry is made, the field will default
to the point address.
EXTENDED LABEL: Press to place the cursor at this field. Type in a 12-character maximum
extended label to further define the location or nature of the point.
ZONE MAP: Displays the zones mapped to this point. During initial programming, zone map
position one for each detector is set to Z0YY, where YY represents the loop number where the
detector resides. In Figure 3.24 above, zone position one has a value of Z003 (YY = 03). The
detector in the example resides on loop 3.
To add or delete zones for this point, press this soft key to progress to the Detector Zone Map
screen.
MORE: Press this soft key to progress to the next detector point programming screen.
ACCEPT: Press to accept changes. If the user is adding a point, pressing this soft key after entering
the TYPE field will display all the other fields.

38 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Point Program Program

Zone Map
The Detector Zone Map screen will display when the ZONE MAP soft key is pressed at the Detector
Point Programming screen.

Zone Map
Zone Map Position
Position 1 -
Use to link DETECTOR ZONE MAP
zone label 2 L03D123
to detector, ZONE SELECTION
and for 3 Z003, (ZONE)
group zone Z187, (ZONE)
disable. 4 Z234, (ZONE)
ZXXX (UNMAPPED)
5 ZXXX (UNMAPPED)
ZXXX (UNMAPPED)
6 ZXXX (UNMAPPED)
ZXXX (UNMAPPED)
7 ZXXX (UNMAPPED) ACCEPT
ZXXX (UNMAPPED)
8
Zone Map BACK
Position 9 - Use
to activate
FlashScan
sounder/relay-
bases. Zone Map Position 10 - Use for
detectors set to Prealarm, Action.

Figure 3.25 Zone Map (Detector Point) Screen

The point address will appear in line 3 of the screen.


Refer to “CBE: Zones and Equations” on page 125, and “Special Zone Outputs” on page 113 in this
manual for more information about zones and how they apply to Control-By-Event.
Soft Keys
ZONE MAP: A detector may be mapped to up to ten general, releasing, or special zones. There are
ten positions available for mapping; positions 1, 9 and 10 - refer to Figure 3.25 - have additional
functionality.
Position 1 - Use this position to link the 20-character zone label to the detector. The zone label
will appear after the 20-character label and 12-character extended label, providing a total of 52
characters to describe an event.
This position is checked when a group zone disable command is issued. If the zone number in
the group zone disable command matches the zone number in the first position of the zone
map, the detector point will be disabled.
Position 10 - Use this position to map detectors with an “Action” Prealarm setting. The zone in
the tenth position will activate when the detector reaches its Prealarm threshold; no other zones
in this detector’s zone map will activate.
Position 9 -
• Use this position to activate the sounder/relay base of a detector. When this position is
mapped to the same zone as Position 10, the sounder or relay base will be activated when
the detector goes into prealarm (Action).
• Use this position to activate the sounder base of a detector using a general or a logic zone.
When a general or logic zone activates, the panel is searched for any detector with the same
zone mapped in its 9th position. The sounder base of any FlashScan detector that matches
the search will activate.
Move the cursor with the keyboard arrow keys to the appropriate zone map position, then select the
type of type of zone by pressing the NEXT SELECTION (+) key until the desired zone type appears.
Type in a zone number to map the detector to it.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 39


Program Point Program

ACCEPT: Press to save entries made on this screen and return to the Detector Point Programming
screen.
Detector Point Programming (2)
Press the MORE soft key on the Detector Point Programming screen to display this screen.

DETECTOR POINT PROGRAMMING


L03D123
CUSTOM ACTION MESSAGE:010

ALARM VERIFICATION: OFF SENSITIVITY

LOCAL MODE: OFF MORE

WEEKLY OCCUPANCY SCHEDULE:10 ACCEPT

MULTI-DETECTOR: D100, D105 BACK

Figure 3.26 More Detector Point Programming (2) Screen

Soft Keys
CUSTOM ACTION MESSAGE: Displays the custom action message number (a value of one
through 100). The default value is 0 (no message). Press this soft key to progress to the Custom
Action Message screen (Figure 3.27) to view the message or to choose a different message for
viewing when this point activates. (To create a new custom action message, refer to “Custom
Action Message” on page 35.)
ALARM VERIFICATION: Press this key to determine the device’s participation in Alarm
Verification. Choosing Yes will set the device participation to the values entered at the Panel
Timers screen (Figure 3.8).
LOCAL MODE: Press to toggle between Local Mode (ON) or no Local Mode (OFF). When there is
a communication loss between the panel and its LCM/LEMs, SLC devices that have been selected
for Local Mode participation (ON) will continue to function across all the panel’s SLCs in a limited
manner as follows: input points will activate output points of the same Type Code point type
designations. For example, SLC inputs with“fire” point types will activate SLC outputs with“fire”
point types. Refer to Appendix G, “Type Codes”, on page 133 for type code point types. All SLC
detector types can participate in local mode.

NOTE: The panel setting LCM LOCAL MODE must be set to Yes for local mode to work at the
device level.

SENSITIVITY: Press to proceed to the Detector Sensitivity screen.


WEEKLY OCCUPANCY SCHEDULE: To choose an existing weekly occupancy schedule, press this
soft key to proceed to the Detector Occupancy Schedule screen. Refer to “Weekly Occupancy
Schedule” on page 31 for information on how to set up a schedule.
MULTI-DETECTOR: This detector can be linked with up to two detectors at other addresses on
the same loop in cooperative multi-detector sensing if entries are made in these fields. The
detectors need not be sequential in their addresses. Refer to the section on Cooperative Multi-
Detector Sensing in Appendix D, “AWACS™ Applications” for a description of this function.
MORE: Press this soft key to progress to the next detector point programming screen.

40 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Point Program Program

Custom Action Message


Press the Custom Action Message soft key on the Detector Point Programming screen to display
this screen. The user may choose a Custom Action Message at this screen.

DETECTOR CUSTOM ACTION MESSAGE


L03D123

CUSTOM ACTION MESSAGE: 001


Custom
Action
Message
Displayed here.

ACCEPT

VIEW BACK

Figure 3.27 Custom Action Message Screen

Soft Keys
CUSTOM ACTION MESSAGE: Enter the number of the Custom Action Message to be displayed
during alarm conditions for this point (refer to Figure 3.20 for an example).
VIEW: Press this soft key to view the message associated with the number entered.
ACCEPT: Press to save the entries made on this screen.

„ Sensitivity
Detector sensitivity levels for alarm and prealarm are set at this screen, which displays when the
SENSITIVITY soft key is pressed at the Detector Point Programming (2) screen.

DETECTOR SENSITIVITY
L03D123

OCCUPIED UNOCCUPIED
SENSITIVITY SENSITIVITY
ALARM - 7 ALARM = 3

OCCUPIED UNOCCUPIED
SENSITIVITY SENSITIVITY
PREALARM - 5 PREALARM = 3

ALARM SENSITIVITY TABLE ACCEPT


1= 0.50% 4= 1.19% 7= 1.89%
2= 0.73% 5= 1.43% 8= 2.12%
3= 0.96% 6= 1.66% 9= 2.35% BACK

Figure 3.28 Detector Sensitivity Screen

The control panel provides nine levels of Prealarm and Alarm in percent per foot obscuration, with
the following two exceptions:

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 41


Program Point Program

• for heat detectors, the settings are to degrees Centigrade.


• for beam detectors, there are only six levels of Alarm. There is no Prealarm for beam detectors
in CLIP mode.
Alarm sensitivity settings range from one to nine, with one representing the most sensitive alarm
level and nine the least sensitive.
Prealarm sensitivity settings range from zero to nine. Zero indicates no prealarm. A value of one
can be a self-optimizing setting where the control panel selects a suitable prealarm level for the
detector. Values one or two through nine represent decreasing sensitivity, with nine being the least
sensitive.
Refer to the section “Detector Sensitivity Settings” in Appendix D, “AWACS™ Applications” for a
full description and a table of the nine sensitivity levels by detector type.
Soft Keys
OCCUPIED SENSITIVITY ALARM:
Press the soft key next to
OCCUPIED SENSITIVITY PREALARM: these setting categories to
enter values as described
UNOCCUPIED SENSITIVITY ALARM:
above.
UNOCCUPIED SENSITIVITY PREALARM:
ALARM SENSITIVITY TABLE: This table will toggle from ALARM to PREALARM based on
which sensitivity value is being entered. The table will display the values for this type of detector.

„ Detector Occupancy Schedule

DETECTOR OCCUPANCY SCHEDULE

WEEKLY OCCUPANCY SCHEDULE: 10


SUNDAY - -
MONDAY 08:00-12:00, 13:00-18:00
TUESDAY 08:00-12:00, 13:00-18:00
WEDNESDAY 08:00-12:00, 13:00-18:00
THURSDAY 08:00-12:00, 13:00-18:00
FRIDAY 08:00-12:00, 13:00-18:00
SATURDAY 08:00-12:00, -
HOLIDAY UNOCCUPIED
ACCEPT

BACK

Figure 3.29 Detector Occupancy Schedule Screen

Soft Keys
WEEKLY OCCUPANCY SCHEDULE: Press this soft key to place the cursor at the underlined
field. There can be up to ten Weekly Occupancy Schedules. Enter a value of zero through ten. Zero
indicates no schedule is applied, and occupied detector sensitivity values are used.
ACCEPT: Press this key to accept the change made and return to the previous screen.

42 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Point Program Program

Detector Point Programming (3)


Press the MORE soft key on the Detector Point Programming (2) screen to display this screen.

DETECTOR POINT PROGRAMMING


L03D123

PREALARM:ALERT

SILENCEABLE:NO

ACCEPT

BACK

Figure 3.30 More Detector Point Programming (3) Screen

Soft Keys
PREALARM: Press to select ALERT or ACTION for the Prealarm function. Refer to the section on
Prealarm in Appendix D, “AWACS™ Applications” for a description of Alert and Action.
SILENCEABLE: This field determines whether the user can manually silence a detector’s
activated sounder/relay base. Values are as follows:

NO Not manually silenceable

YES - RESOUND FIRE Silenceable, resound on fire alarm events Network and Local Resound

YES - RESOUND SUPERV Silenceable, resound on supervisory events Network and Local Resound

YES - NO RESOUND Silenceable, does not resound

3.4.2 Module Point


Module point programming screens will display if a module point address is entered at the Point
Programming Menu (see Figure 3.23 on page 37 ).

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 43


Program Point Program

Module Point Programming (1)

MODULE POINT PROGRAMMING


L03M123
MODULE TYPE: MONITOR

TYPE CODE LABEL:HEAT DETECT

FLASHSCAN CODE LABEL: MONITOR MORE

POINT LABEL:
MONITOR L03M123 ACCEPT

EXTENDED LABEL:
BACK

Figure 3.31 Module Point Programming (1) Screen

Soft Keys
MODULE TYPE: Press the soft key to toggle between CONTROL and MONITOR.
TYPE CODE LABEL: Press this soft key to scroll through the point type choices: stop at the
appropriate selection.
FLASHSCAN CODE LABEL: Press this soft key to scroll through the point type choices: stop at
the appropriate selection (Table G.4 on page 137 for codes and descriptions). Choose NONE if the
point type is not FlashScan.

NOTE: If the point is not installed, MODULE TYPE: , TYPE CODE LABEL:, and FLASHSCAN
CODE LABEL: must be entered before any entries can be saved using the ACCEPT key.

POINT LABEL: Press this soft key to place the cursor at this field. Type in a 20-character
maximum point label that will appear in message formats. If no entry is made, the field will default
to the point address.
EXTENDED LABEL: Press to place the cursor at this field. Type in a 12-character maximum
extended label to further define the location or nature of the point.
MORE: Press to proceed to the next screen for more point programming.
ACCEPT: Press to save entries made on this screen.
Module Point Programming (Monitor Module)
Pressing the MORE soft key at the Module Point Programming screen will display this screen if the
module type was monitor.

44 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Point Program Program

MODULE POINT PROGRAMMING


L03M123
CUSTOM ACTION MESSAGE:020

ZONE MAP:
Z003 , Z104 , Z105 , Z106 , Z107
Z110 , Z114 , Z115 , Z116 , Z117

ALARM VERIFICATION: OFF

LOCAL MODE: OFF ACCEPT

BACK

Zone Map Position 1 - Use for group zone


disable participation.

Figure 3.32 Module Point Programming Screen 2 (Monitor)

Soft Keys
CUSTOM ACTION MESSAGE: Displays the custom action message number (a value of one
through 100). The default value is 0 (no message). Press this soft key to progress to the Custom
Action Message screen (shown in Figure 3.27) to view the message or to choose a different
message for viewing when this point activates. (To create a new custom action message, refer to
“Custom Action Message” on page 35.)
ZONE MAP: Displays the zones mapped to this point. During initial programming, zone map
position one for each monitor module is set to Z0YY, where YY represents the loop number where
the module resides. In Figure 3.32 above, zone position one has a value of Z003 (YY = 03). The
module in the example resides on loop 3.
To add or delete zones, press this soft key to proceed to the Module Zone Map screen. Refer to
“Zone Map” on page 39 for an illustration and explanation of the Detector Zone Map screen. The
Module Zone Map screen is the same except that Module replaces Detector in the title and the
module address appears instead of the detector address. Up to ten general, releasing or special
zones may be mapped to a monitor module: none of the zone map positions are fixed. Position 1
has additional functionality.
Position 1 - This position is checked when a group zone disable command is issued. If the zone
number in the group zone disable command matches the zone number in the first position of
the zone map, the module point will be disabled.
ALARM VERIFICATION: Press this key to determine participation in Alarm Verification.
Choosing Yes will set the device participation to the value entered at the Panel Timers screen
(Figure 3.8). The only module type that can participate in alarm verification is the FZM-1.
LOCAL MODE: Press to toggle between Local Mode (ON) or no Local Mode (OFF). When there is
a communication loss between the panel and its LCM/LEMs, SLC devices that have been selected
for Local Mode participation (ON) will continue to function across all the panel’s SLCs in a limited
manner as follows: input points will activate output points of the same Type Code point type
designations. For example, SLC inputs with“fire” point types will activate SLC outputs with“fire”
point types. Refer to “Type Codes for Input Devices” on page 134 for Type Code point types.
Default: OFF

NOTE: The panel setting LCM LOCAL MODE must be set to Yes for local mode to work at the
device level.

ACCEPT: Press to save entries made on this screen and to return to the previous screen.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 45


Program Point Program

Module Point Programming (Control Module)


Pressing the MORE soft key at the Module Point Programming screen will display this screen if the
module type was control.

MODULE POINT PROGRAMMING


L03M150

ZONE MAP:
Z000 , Z104 , Z105 , Z106 , Z107
Z110 , Z114 , Z115 , Z116 , Z117

WALK TEST: OFF LOCAL MODE:ON

SWITCH INHIBIT: YES ACCEPT

SILENCEABLE:NO BACK

Zone Map Position 1 - Use for group zone


disable participation.

Figure 3.33 Module Point Programming Screen 2 (Control)

Soft Keys
ZONE MAP: Displays the zones mapped to this point. The default value assigned to control modules
during initial programming is Z000 at Position 1 (refer to Figure 3.33), with the exception of control modules
with the following Type IDs: Telephone, Gen Alarm, Gen Supervis, Gen Trouble, and Trouble Pend.
To add or delete zones, press this soft key to proceed to the Module Zone Map screen. Refer to
“Zone Map” on page 39 for an illustration and explanation of the Detector Zone Map screen. The
Module Zone Map screen is the same except that Module replaces Detector in the title and the
module address appears instead of the detector address. Up to ten general, logic, release, special or
trouble zones may be mapped to a control module. Position 1 has additional functionality.
Position 1 - This position is checked when a group zone disable command is issued. If the zone
number in the group zone disable command matches the zone number in the first position of
the zone map, the module point will be disabled.
Note that the group zone disable command has no effect on general alarm zone Z000.
WALK TEST: This field determines if the output will activate during Walk Test. Values are ON
(the output will activate) and OFF (the output will not activate). Default: OFF.

NOTE: The following Type ID codes do not participate in Walk Test, and the WALK TEST soft key will
not appear when the screen displays: REL END BELL, RELEASE CKT, REL CKT ULC, REL. FORM
C, REL AUDIBLE, INST RELEASE, NONRESET CTL, TELEPHONE, and FORM-C RESET. The
FMM-1module with SMOKE CONV, HEAT DETECT, or SMOKE DETECT does not participate in Walk
Test.

SWITCH INHIBIT: This field determines whether a user can manually activate an output.
Values are YES (can not be activated manually) or NO (can be activated manually). Default: NO
SILENCEABLE: This field determines whether the user can manually silence an activated output.
Values are as follows:

NO Not manually silenceable

YES - RESOUND FIRE Silenceable, resound on fire alarm events Network and Local Resound

46 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Point Program Program

YES - RESOUND SUPERV Silenceable, resound on supervisory events Network and Local Resound

YES - RESOUND SECURITY Silenceable, resound on security events Network and Local Resound

YES - RESOUND TROUBLE Silenceable, resound for trouble Local Resound


YES - NO RESOUND Silenceable, does not resound

NOTE: This soft key will not appear for modules with Type ID codes where silence is not optional.

LOCAL MODE: Press to toggle between Local Mode (ON) or no Local Mode (OFF). When there is
a communication loss between the panel and its LCM/LEMs, SLC devices that have been selected
for Local Mode participation (ON) will continue to function across all the panel’s SLCs in a limited
manner as follows: input points will activate output points of the same Type Code point type
designations. For example, SLC inputs with“fire” point types will activate SLC outputs with“fire”
point types. Refer to “Type Codes for Input Devices” on page 134 for Type Code point types.
Default: OFF

NOTE: The panel setting LCM LOCAL MODE must be set to Yes for local mode to work at the
device level.

3.4.3 Panel Circuit Module


There are three panel circuits on the FACP, and each circuit can accomodate up to four panel circuit
modules that have eight push-button switches apiece. The switches can be programmed as input or
output points, depending on the module type.

WARNING: When using alarm verification, do not mix fire alarm points with non-fire alarm
! points on the same IZM-8RK/IZE-A Initiation Zone Module.

The point information is displayed onscreen in the format Pyy.z, where P means panel circuit point,
yy is the panel circuit module number (1 through 12), and z is the module push-button number (1-
8). Each panel circuit point is assigned an address by the panel depending on its location. Refer to
Figure 3.34 below for an illustration of how the panel assigns addresses.
.

CPU-3030 Panel 1st position* 2nd position 3rd position 4th position
Circuit Connection module module module module
addresses addresses addresses addresses
Panel Circuit #1 (J10) P1.1 - P1.8 P2.1 - P2.8 P3.1 - P3.8 P4.1 - P4.8
Pyy.1 Pyy.5
Panel Circuit #2 (J11) P5.1 - P5.8 P6.1 - P6.8 P7.1 - P7.8 P8.1 - P8.8
Pyy.2 Pyy.6 Panel Circuit #3 (J12) P9.1 - P9.8 P10.1 - P10.8 P11.1 - P11.8 P12.1 - P12.8
Pyy.3 Pyy.7 * The first position is the position closest to the CPU-3030 connection, the fourth
position is the furthest from this connection. These address assignments are fixed; if a
Pyy.4 Pyy.8 panel module is not installed in position 3 of panel circuit #1, the fourth position
module still has an address of P4.yy.
Panel Circuit Module

Figure 3.34 Panel Circuit Point Addresses

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 47


Program Point Program

Point Programming (1)


The Panel Circuit Point Programming screen will display if a panel circuit point address is entered
at the Point Programming Menu (see Figure 3.23 on page 37 ).

PANEL CKT POINT PROGRAMMING


P11.2
PANEL MODULE TYPE: MONITOR

TYPE CODE LABEL:HEAT DETECT

MORE

POINT LABEL: ACCEPT

EXTENDED LABEL:
BACK

Figure 3.35 Panel Circuit Point Programming (1) Screen

Soft Keys
PANEL MODULE TYPE: Press the soft key to toggle between MONITOR, CONTROL-CRM,
CONTROL-ICM. Select MONITOR for IZM-8RK/IZE-A modules, CONTROL-CRM for
CRM-4RK/CRE4 modules, and CONTROL-ICM for ICM-4RK/ICE-4 modules.
TYPE CODE LABEL: Press this soft key to scroll through the point Type Code choices: stop at
the appropriate selection.
POINT LABEL: Press this soft key to place the cursor at this field. Type in a 20-character
maximum point label that will appear in message formats. If no entry is made, the field will default
to the point address.
EXTENDED LABEL: Press to place the cursor at this field. Type in a 12-character maximum
extended label to further define the location or nature of the point.
MORE: Press to proceed to the next screen for more point programming.
ACCEPT: Press to save entries made on this screen.

48 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Point Program Program

Point Programming (2) - Monitor

PANEL MODULE POINT PROGRAMMING


P10.2
CUSTOM ACTION MESSAGE:020

ZONE MAP:
Z011 , Z104 , Z105 , Z106 , Z107
Z110 , Z114 , Z115 , Z116 , Z117

ALARM VERIFICATION: OFF

ACCEPT

BACK

Position 1 - Use for group zone disable participation.

Figure 3.36 Panel Module Point Programming (2) -Monitor - Screen

Soft Keys
CUSTOM ACTION MESSAGE: Displays the custom action message number (a value of one
through 100). The default value is 0 (no message). Press this soft key to progress to the Custom
Action Message screen (shown in Figure 3.27) to view the message or to choose a different
message for viewing when this point activates. (To create a new custom action message, refer to
“Custom Action Message” on page 35.).
ZONE MAP: Displays the zones mapped to this point. The default value assigned to panel circuit
input modules during initial programming is Z011 in the first zone map position.
To add or delete zones, press this soft key to proceed to the Panel Module Zone Map screen. Refer
to “Zone Map” on page 39 for an illustration and explanation of the Detector Zone Map screen. The
Panel Module Zone Map screen is the same except that Panel Module replaces Detector in the title
and the module address appears instead of the detector address. Up to ten general, releasing or
special zones may be mapped to a panel monitor module. Position 1 has additional functionality.
Position 1 - This position is checked when a group zone disable command is issued. If the zone
number in the group zone disable command matches the zone number in the first position of
the zone map, the module point will be disabled.
ALARM VERIFICATION: Press this key to determine participation in Alarm Verification.
Choosing Yes will set the device participation to the value entered at the Panel Timers screen
(Figure 3.8).
ACCEPT: Press to save entries made on the screen and return to the previous screen.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 49


Program Point Program

Point Programming (2) - Control

PANEL MODULE POINT PROGRAMMING


P11.2

ZONE MAP:
Z000 , Z104 , Z105 , Z106 , Z107
Z110 , Z114 , Z115 , Z116 , Z117

WALK TEST: OFF

SWITCH INHIBIT: YES ACCEPT

SILENCEABLE: YES - RESOUND FIRE BACK

Zone Map Position 1 - Use for group zone


disable participation.

Figure 3.37 Panel Module Point Programming (2) -Control - Screen

Soft Keys
ZONE MAP: Displays the zones mapped to this point. The default value assigned to panel circuit
output modules during initial programming is Z000, with the exception of control modules with the
following Type IDs: Telephone, Gen Alarm, Gen Supervis, Gen Trouble, and Trouble Pend. . To
add or delete zones, press this soft key to proceed to the Panel Module Zone Map screen. Refer to
“Zone Map” on page 39 for an illustration and explanation of the Detector Zone Map screen. The
Panel Module Zone Map screen is the same except that Panel Module replaces Detector in the title
and the module address appears instead of the detector address. Up to ten general, logic, release,
special or trouble zones may be mapped to a panel control module.Position 1 has additional
functionality.
Position 1 - This position is checked when a group zone disable command is issued. If the zone
number in the group zone disable command matches the zone number in the first position of
the zone map, the module point will be disabled.
Note that the group zone disable command has no effect on general alarm zone Z000.
WALK TEST: This field determines if the output will activate during Walk Test. Values are ON
(the output will activate) and OFF (the output will not activate). The default is OFF.

NOTE: The IZM-8RK module does not participate in Walk Test. Also, the following Type ID
codes do not participate in Walk Test, and the WALK TEST soft key will not appear when the
screen displays: REL END BELL, RELEASE CKT, REL CKT ULC, RELEA.FORM C, REL
AUDIBLE, INSTANT RELE, NONRESET CTL, and TELEPHONE.

SILENCEABLE: This field determines whether the user can manually silence an activated output.
Values are YES - RESOUND FIRE (manually silenceable, resounds on fire alarm) and NO (not
manually silenceable). The default is YES.

NOTE: This soft key will not appear for modules with Type ID codes where silence is not
optional.

SWITCH INHIBIT: This field determines whether a user can manually activate an output.
Values are YES (can not be activated manually) or NO (can be activated manually). The default is
NO.

50 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Point Program Program

3.4.4 General Zone


This screen displays when a general zone is chosen at the Point Program menu (see Figure 3.23 on
page 37 ).

ZONE POINT PROGRAMMING


Zyyy
ZONE LABEL:

ACCEPT

BACK

Figure 3.38 Zone Point Programming Screen

Soft Keys
ZONE LABEL: Press to type in a 20-character maximum zone description that will appear in the
zone’s display messages.
ACCEPT: Press to save the message and return to the previous screen.

3.4.5 Releasing Zone


Releasing Zone Programming
This screen displays when a releasing zone is chosen at the Point Program menu (see Figure 3.23
on page 37 ).

RELEASING ZONE PROGRAMMING MENU


ZR08

DELAY TIME: 00

ABORT SWITCH: ULI

CROSS ZONE: NO ACCEPT

SOAK TIME: 0000 BACK

Figure 3.39 Releasing Zone Programming Menu Screen

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 51


Program Point Program

Refer to Appendix B, “Releasing Applications” for a full explanation of the fields below.
Soft Keys
DELAY TIME: Press this soft key to type a value from 0 to 60 (seconds). Default 00
ABORT SWITCH: Press this soft key to scroll through the selection list of ULI, IRI, NYC, or AHJ.
Default:ULI
CROSS ZONE: Press to scroll through the selection list of YES, NO, ZONE, HEAT. Default: NO.
SOAK TIME: Press to type a value from 0 to 9999 (seconds). Default: 0000

3.4.6 Logic Zone

Logic Zone Programming


This screen displays when a logic zone is entered at the Point Programming Menu (see Figure 3.23
on page 37 ).
The logic equation for that zone will display in line 6. Line 4 indicates the current state of the logic
zone (ON or OFF). If there is no equation at the logic zone number entered, nothing will display in
lines 4 and 6, and the user must press the EDIT EQUATION soft key to proceed to the next screen
and enter an equation.
Refer to Appendix E, “CBE: Zones and Equations” for information on how to create a logic
equation, and how logic equations operate.

LOGIC ZONE PROGRAMMING MENU


LOGIC ZONE ZLxxxx
AUTOMATIC OFF

AND(Z20,OR(L2D159,L2D14))

EDIT EQUATION

NEXT EQUATION ACCEPT

PREVIOUS EQUATION BACK

Figure 3.40 Logic Zone Programming Menu Screen

Soft Keys
EDIT EQUATION: Press to proceed to the edit screen to add or edit a logic equation.
NEXT/PREVIOUS EQUATION: Press to view the next or previous logic equation.

52 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Point Program Program

Edit Logic Equation


This screen displays when the EDIT EQUATION soft key is pressed on the Logic Zone.
Programming Menu

LOGIC ZONE PROGRAMMING MENU


LOGIC ZONE ZLxxxx
AUTOMATIC OFF INS/OVR

AND(Z20,OR(L2D159,L2D14))

INSERT

ADD POINT/ZONE DELETE EQUATION

ADD LOGIC FUNCTION ACCEPT

ADD TIME/DATE BACK

INSERT or OVERWRITE displays here.

Figure 3.41 Edit Logic Equation Screen

The cursor will be present in the equation, and can be moved by pressing the left/right arrow keys
on the keyboard. To add or delete information, use the INS/OVR soft key function described
below. Use the keypad to type in an equation. The ADD POINT/ZONE and ADD LOGIC
FUNCTION soft keys may be used to facilitate creating a logic equation; however, commas must be
added by using the keypad.
Soft Keys
INS/OVR: Press to toggle between insert and overwrite. Stop at the appropriate mode, which
displays in line 8 of the screen. Insert will add information to the equation, overwrite will write
over information already in the equation.
ADD POINT/ZONE: Press to proceed to the Add Point/Zone screen. This screen is an alternative
to typing in the information at this screen; it provides point and zone formats that make it less likely
for typographical errors to occur.
ADD LOGIC FUNCTION: Press to proceed to the Add Logic Function screen. This screen is an
alternative to typing in the information at this screen; it provides logic function formats that make it
less likely for typographical errors to occur.
ADD TIME/DATE: Press to proceed to the Add Time/Date screen.
DELETE EQUATION: Press to delete the entire equation.
ACCEPT: Press to save changes made on this screen and return to the previous screen.

NOTE: When the ACCEPT soft key is pressed to save an equation, the panel checks the
equation for errors. If there is an error in the equation, the previous screen will not appear, and the
cursor will appear at the error point. Correct the equation, and re-press the ACCEPT: soft key.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 53


Program Point Program

Add Point/ Zone

LOGIC ZONE PROGRAMMING MENU


LOGIC ZONE ZLxxxx
AUTOMATIC OFF

AND(Z20,OR(L2D159,L2D14))

POINT SELECT:
L01D043 (DETECTOR)

NEXT POINT ACCEPT

PREVIOUS POINT BACK

Figure 3.42 Add Logic Point/Zone Screen

The cursor will be present in the logic equation. Place it, using the arrow keys on the keyboard, at
the place where the additional point should be inserted.
Soft Keys
POINT SELECT: Press to scroll through the list of possible formats (detector, module, etc.). Stop
at the desired format. Type in the address for the additional point.
ACCEPT: Press to insert the point into the equation where the cursor is blinking, and to return to
the previous screen.
NEXT/PREVIOUS POINT: Press these soft keys to scroll forward or backward from the
displayed point to the next installed point.
Add Logic Function
This screen appears when the ADD LOGIC FUNCTION soft key is pressed at the Logic Zone
Programming Menu screen.
.

LOGIC ZONE PROGRAMMING MENU


LOGIC ZONE ZLxxxx
AUTOMATIC OFF

AND(Z20,OR(L2D159,L2D14))

LOGIC FUNCTION: AND ACCEPT

BACK

Figure 3.43 Add Logic Function Screen

54 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Point Program Program

The cursor will be present in the logic equation. Place it, using the arrow keys on the keyboard, at
the place where the logic function should be inserted.
Soft Keys
LOGIC FUNCTION: Press to scroll through the list of possible logic functions.
ACCEPT: Press to insert the logic function into the equation where the cursor is blinking, and to
return to the previous screen.
Add Time/Date
This screen appears when the ADD TIME/DATE soft key is pressed at the Logic Zone
Programming Menu screen

LOGIC ZONE PROGRAMMING MENU


LOGIC ZONE ZLxxxx
AUTOMATIC OFF

DEL

OVERWRITE

ENTER TIME:22:30:00 ACCEPT

BACK

Figure 3.44 Add Time/Date to Logic Zone Screen

Soft Keys
ENTER TIME: _ _:_ _:_ _ Press this soft key to toggle between the time/date formats. Choose one
based on the type of time-based function used.
Table 3.1
Time-based Screen Field Time/date format
function

DEL, SDEL, TIM ENTER TIME:_ _:_ _:_ _ HH:MM:SS, entered as military time (22:30:00 = 10:30 P.M.)

TIM ENTER DATE:_ _-_ _-_ _ (MM-DD-YY)

TIM ENTER DAY: MO (Use the TOGGLE DAY soft key that appears to scroll through
and choose a day of the week.

3.4.7 Trouble Zone


Trouble Zone Programming
Trouble zones provide a means of using a system trouble input to effect an output. For instance, an
annunciator trouble can be used to activate an output device.
The trouble zone format is ZTxxx, where xxx is a number from one through one hundred. When a
trouble zone format is entered at the Point Select screen, the same programming screens and
choices appear as for logic zones, except the zone format is a trouble zone format. (Refer to
paragraphs “Logic Zone Programming” on page 52 and the paragraphs following “Add
Time/Date”).

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 55


Program Delete Program

Refer to Appendix E, “CBE: Zones and Equations” for information on how to create a trouble
equation, and how they operate.

3.4.8 Annunciator Board Label


When A C S B O A R D is selected from the Point Program Menu, the ACS Label Menu appears.

ZONE POINT PROGRAMMING


A01
ACS LABEL:
EAST WING SPEAKERS

ACCEPT

BACK

Figure 3.45 ACS Label Menu Screen

Soft Keys
A C S L A B E L : Type a label for the selected annunciator. The label can have up to 40 characters.

3.5 Delete Program


Press the D E L E T E P R O G R A M M E N U at the P R O G R A M / A L T E R S T A T U S M E N U menu to
display the screen below.

DELETE PROGRAM MENU

CLEAR: PANEL CLEAR ALL PROGRAMMING

CLEAR: PANEL MODULES CLEAR ACS

CLEAR LOOPS: ALL ACCEPT

DELETE POINT BACK

Figure 3.46 Delete Program Menu Screen

56 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Delete Program Program

Soft Keys
CLEAR ALL PROGRAMMING: Press to remove all panel, panel module, loop, point and ACS
programming information, as well as logic and trouble zone equations. Pressing this key removes
everything except passwords. A confirmation screen will display asking the user to confirm the
deletion command. Pressing this key causes a reboot.
CLEAR:PANEL Press to remove all programmed panel setting information from control panel
memory. This does not remove ACS programming. A confirmation screen will display asking the
user to confirm the deletion command. Pressing this key causes a reboot.
CLEAR:PANEL MODULES Press to remove all panel module programming information. A
confirmation screen will display asking the user to confirm the deletion command. Pressing this
key causes a reboot.
CLEAR LOOPS Press to scroll through the options: ALL, LOOP 1, LOOP 2,...., LOOP 10. Stop at
the desired option. Press ACCEPT to delete all loop programming for the selected option. Pressing
this key causes a reboot.
DELETE POINT To delete a point, press this soft key to display the Delete Point screen. Pressing
this key may cause a reboot.
CLEAR ACS: Press to remove all ACS programming from panel memory. A confirmation screen
will display asking the user to confirm the deletion command. Pressing this key causes a reboot.
ACCEPT: Press to clear all programming for the selected loop option for CLEAR LOOPS. A
confirmation screen will display asking the user to confirm the deletion command.

DELETE POINT

POINT SELECT:
LyyDzzz (DETECTOR)

NEXT SELECTION DELETE

PREVIOUS SELECTION BACK

Figure 3.47 Delete Point Screen

POINT SELECT: Press to scroll through the options: detector, module, or panel module. Stop at
the desired option. Press the DELETE soft key to delete the point from programming. A
confirmation screen will display asking the user to confirm the deletion command.

NOTE: Deleting points that are active or in trouble will cause a reboot.

NEXT/PREVIOUS SELECTION Press to scroll sequentially to the next or previous point.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 57


Program Autoprogram Menu

3.6 Autoprogram Menu


The Autoprogram option identifies addressable devices connected to the control panel. Devices
include addressable detectors and modules connected to the panel’s SLCs and Panel Circuits. The
Autoprogram can be used to create a new program, or to add or remove devices from an existing
program. When the points are accepted, they are added to the panel’s database with the defaults
described in the “Point Programming” section of this manual.

3.6.1 To Create a New Program


To successfully create a new program, the FACP must either be new, or have no existing program in
memory for the loops or panel circuits involved.
1. Use the Delete Program Menu screen ( refer to Figure 3.46) to clear any applicable
programming from the panel. For example, if loops one and two are to be autoprogrammed,
clear the programming that exists by entering 1+2 at the Delete Program Menu screen.
2. Install SLCs (loops 1+2 in this example) using the Loop Programming screen (Figure 3.19)
(panel circuits do not require this step).
3. Press the A U T O P R O G R A M L O O P S soft key and enter the desired SLCs (loops 1+2 in this
example), or select A U T O P R O G R A M P A N E L M O D U L E S in the Autoprogram Menu screen
(Figure 3.48)
4. Press the ACCEPT soft key to run the Autoprogram.

3.6.2 To Add/Delete Devices from the Program


When using the Autoprogram option with an existing program, the control panel does not change
program information for installed and programmed devices.
5. If devices are to be added to a new SLC (an SLC that is not in the program), that SLC must be
installed using the Loop Programming screen (Figure 3.19).
6. Physically install/uninstall the SLC devices or panel circuit modules.
7. Press the AUTOPROGRAM LOOPS or the AUTOPROGRAM PANEL CIRCUITS soft key to run
the Autoprogram. Existing information will not be changed.
Autoprogram will find the devices/modules on the selected installed SLCs/panel circuits. It will
compare the information it finds during autoprogramming against any point information that may
already be in the database, and it will look for any addressing errors, such as two detectors with the
same address. If it finds a discrepancy or error, a screen will be displayed with the discrepant or
incorrect information and the programmer will be given the option of changing it.

AUTOPROGRAM MENU

AUTOPROGRAM LOOPS: ALL

AUTOPROGRAM PANEL MODULES

ACCEPT

BACK

Figure 3.48 Autoprogram Menu Screen

58 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Autoprogram Menu Program

Soft Keys
AUTOPROGRAM LOOPS: Press to scroll through the options: ALL, 1+2, 3+4, 5+6, 7+8, 9+10.
Stop at the desired option to select it.
AUTOPROGRAM PANEL MODULES: Press to select panel modules for autoprogramming.
ACCEPT: Press to autoprogram the selection. A confirmation screen will display asking the
programmer to confirm the autoprogram choice made (press the YES soft key to confirm). A screen
with the message AUTOPROGRAM IN PROGRESS will display until autoprogramming is complete.

3.6.3 Confirmation Screens


SLC and Panel Circuit Statistics
When autoprogramming is complete, the panel will display a list of the number of modules and
detectors found on each SLC, or it will display the number of inputs or outputs found on each panel
module. Refer to Figure 3.49 and Figure 3.50 for examples of these screens.

AUTOPROGRAM CONFIRMATION

LOOP DETECTORS MODULES


1 011 087
2 030 129
3 NOT INSTALLED
4 NOT INSTALLED
5 NOT INSTALLED
6 NOT INSTALLED
7 NOT INSTALLED
8 NOT INSTALLED
9 NOT INSTALLED ACCEPT
10 NOT INSTALLED ALL

REVIEW BACK

Figure 3.49 Autoprogram Confirmation Screen (SLCs)

Soft Keys
REVIEW: Press this soft key to review the new devices found (with the option of adding them to
the program one by one), devices that are in the database that the autoprogram did not find, devices
that have data base and autoprogram information that differs, and devices that are incorrectly
doubled up on a single address. Devices will display in the following order:
• L01M001 through L01M159
• L01D001 through L01D159
• L02M001 through L02M159, etc.
Depending on what information was found, different screens may appear for different points. Refer
to Figure 3.51 through Figure 3.54 for examples of the screens.
ACCEPT ALL: Press to accept all the new devices that have been found by the autoprogram.
Errors and discrepancies will still be displayed the same as if the REVIEW soft key had been
pressed: however, new devices will not individually display for review and acceptance.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 59


Program Autoprogram Menu

AUTOPROGRAM CONFIRMATION

PANEL MODULE STATUS

1 INPUT, 8 POINTS 7 OUTPUT, 4 POINTS


2 OUTPUT, 8 POINTS 8 OUTPUT, 4 POINTS
3 OUTPUT, 8 POINTS 9 NO ANSWER
4 OUTPUT, 8 POINTS 10 NO ANSWER
5 OUTPUT, 8 POINTS 11 NO ANSWER
6 OUTPUT, 8 POINTS 12 NO ANSWER

ACCEPT
ALL

REVIEW BACK

Panel Module number Number of points found


during autoprogramming
Panel Module type
(input or output)

Figure 3.50 Autoprogram Confirmation Screen (Panel Circuits)

Soft Keys
REVIEW: Press this soft key to review the new panel modules found (with the option of adding
them to the program one by one), modules that are in the database that the autoprogram did not
find, and modules that have data base and autoprogram information that differs. Devices will
display in the following order: P01 through P12.
Depending on what information was found, different screens may appear for different points. Refer
to Figure 3.51 through Figure 3.53 for examples of the screens.

NOTE: If panel circuit points have been added, Autoprogram will add them. Pressing the
REVIEW soft key does not give the option to review panel circuit points.

ACCEPT ALL: Press to accept all the new modules and devices that have been found by the
Autoprogram. Discrepancies will still be displayed the same as if the REVIEW soft key had been
pressed: however, new devices will not individually display for review and acceptance.

60 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Autoprogram Menu Program

Add New Points


When the REVIEW soft key is pressed, the panel will individually display each new SLC or panel
circuit point found during autoprogramming. The screen below uses an SLC detector point as an
example. A new panel circuit point will display “NEW PANEL MODULE FOUND AT PXX”
instead of the message below.

AUTOPROGRAM CONFIRMATION

NEW DEVICE FOUND AT LXXXDXXX

ADD POINT?

YES NO

EDIT BACK

Figure 3.51 Autoprogram Confirmation Screen (New SLC Point)

Soft Keys
YES: Press this soft key to install the new point into the panel’s database.
EDIT: Press this soft key to advance to the point programming menu for the new point. (This
option is available for SLC points only, not for panel points. The E D I T soft key will not appear for
panel modules).
NO: Press if the point will not be installed.
Error and Discrepancy Resolution
Pressing the REVIEW soft key will bring up screens that provide the means to resolve any errors or
discrepancies found during autoprogram.

AUTOPROGRAM CONFIRMATION

NO DEVICE FOUND AT LXXDXXX

DELETE POINT?

YES NO

BACK

Figure 3.52 Autoprogram Confirmation Screen (Missing Point)

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 61


Program Autoprogram Menu

Display
This screen will display either the SLC device address or the panel circuit module address when a
previously installed/programmed point does not respond during a subsequent Autoprogram.
Soft Keys
YES: Press to delete the point information from the panel’s database.
NO: Press to leave the point information in the panel’s database.

AUTOPROGRAM CONFIRMATION

MISMATCHED MODULE FOUND AT PXX

OLD:CONTROL-ICM
NEW:CONTROL-CRM

ACCEPT CHANGES?

YES NO

BACK

EDIT will appear here when the


mismatched point is an SLC device

Figure 3.53 Autoprogram Confirmation Screen (Mismatched Point)

Display
The O L D field contains the information currently in the panel’s programming database. The N E W
field contains the information found during autoprogramming. The fields contain the FlashScan
Type ID codes if the device is FlashScan, or they will contain the device type if CLIP.
Soft Keys
YES: Press this soft key to accept the new device type.
EDIT: This soft key will appear only when SLC devices are mismatched. It will not appear for
panel modules. Press it to advance to the point programming screen for this point.
NO: Press if the new information should not be installed over the existing information in the
database.

62 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Autoprogram Menu Program

AUTOPROGRAM CONFIRMATION

DOUBLE ADDRESS FOUND AT LXXDXXX

ACCEPT

BACK

Figure 3.54 Autoprogram Confirmation Screen (Double Address)

Display
The SLC loop number and device address are displayed where the Autoprogram has found more
than one detector or module with the same address.
Soft Keys
ACCEPT: Pressing this soft key acknowledges that the programmer has been informed of the
double address. Autoprogram will not make a modification to the database for this point. The
installer must correct this problem.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 63


Program Autoprogram Menu

64 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Section 4: Alter Status
Alter Status provides a programming level for changing operating parameters such as detector
sensitivity, Walk Test, changing system time/date and disabling/enabling points. Alter Status is
accessible with the Master Password and with User Passwords programmed for Alter Status.

LAKEVIEW GENERAL HOSPITAL


SYSTEM NORMAL

10:22:34A FRI SEP 24, 2004


ALTER STATUS

DISABLE/ENABLE WALK TEST

DETECTOR SENSITIVITY CHANGE TIME/DATE

CLEAR VERIFY COUNTS CONTROL ON/OFF

CLEAR HISTORY BACK

Figure 4.1 Alter Status Screen

Soft Keys
All soft key selections (except BACK) are menu selections. Press to display the desired menu.

4.1 Disable/Enable Point Selection


.

LAKEVIEW GENERAL HOSPITAL


SYSTEM NORMAL

10:22:34A TUE AUG 24, 2004


POINT SELECT

POINT SELECT:
LyyDzzz (DETECTOR)

NEXT SELECTION ACCEPT

PREVIOUS SELECTION BACK

Figure 4.2 Point Select for Disable/Enable Screen

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 65


Alter Status Disable/Enable

Soft Keys
POINT: Press this soft key to identify the type of point to disable/enable: the choices that will
appear in parentheses next to the point format are DETECTOR, MODULE, PANEL CKT, or
GENERAL ZONE. Enter the address of the point using the keyboard. If there is an event in the
display area, that address will be the default. If no event is present, the default format will be that of
a detector.

4.2 Disable/Enable
A point can be disabled or enabled using this screen. Press the DISABLE/ENABLE soft key at the
Alter Status screen to display the following.

LAKEVIEW GENERAL HOSPITAL


SYSTEM NORMAL

10:22:34A FRI SEP 24, 2004


DISABLE/ENABLE: L03D052
AUTOMATIC INACTIVE
ELEVATOR LOBBY EAST WING
FIFTH FLOOR Z005 SMOKE(PHOTO)

VALUES: 011% OF ALARM, 045% OF PREALARM

DISABLE BACK

Figure 4.3 Disable/Enable Screen

Soft Keys
DISABLE/ENABLE Only the applicable command will display. Press to disable an installed,
programmed point, or to enable a disabled one.

CAUTION: When a disabled output is enabled, it will be affected by conditions existing in the
! system that would normally affect it. That is, if a condition exists that would have turned the output on
were it enabled, it will turn on when it is enabled.

Group Zone Disable - This term refers to the disabling (or enabling) of a general zone. If the
first position in a device’s zone map matches the general zone number entered at this screen,
that device will be disabled (or enabled).

WARNING: Do not rely on Disable to disable releasing points during testing. Releasing
! points must be physically disconnected.

66 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Detector Sensitivity Alter Status

4.3 Detector Sensitivity


This screen is displayed when the “Detector Sensitivity” soft key is pressed on the Alter Status
Menu screen.

LAKEVIEW GENERAL HOSPITAL


SYSTEM NORMAL

10:22:34A FRI SEP 24, 2004


POINT SELECT

POINT: LyyDzzz (DETECTOR)

NEXT SELECTION ACCEPT

PREVIOUS SELECTION BACK

Figure 4.4 Sensitivity Select Point Screen

Soft Keys
POINT: Press to place the cursor in the format field. Type the address using the keyboard.
NEXT/PREVIOUS SELECTION: Press these soft keys to scroll sequentially through the detector
addresses on the loop. The screen will display the next loop when the last device on this loop is
passed.
ACCEPT: Press to proceed to the Detector Sensitivity screen.

4.3.1 Sensitivity Select


Detector sensitivity levels, set during initial programming, may be changed through accessing the
Detector Sensitivity Select screen and the command screen that follows. The Detector Sensitivity
Select screen is displayed when the ACCEPT: soft key is pressed at the Sensitivity Select Point
screen.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 67


Alter Status Detector Sensitivity

The current sensitivity values displayed are described in Detector Point Programming (Refer to the
paragraph “Sensitivity” on page 41 ) and in Appendix D, “AWACS™ Applications”

LAKEVIEW GENERAL HOSPITAL


SYSTEM NORMAL

10:22:34A FRI SEP 24, 2004


ADDRESS: L03D052
AUTOMATIC INACTIVE
ELEVATOR LOBBY EAST WING
FIFTH FLOOR Z003 SMOKE(PHOTO)

OCCUPIED ALARM UNOCCUPIED ALARM


SENSITIVITY = 7 SENSITIVITY = 5

OCCUPIED PREALARM UNOCCUPIED PREALARM


SENSITIVITY = 5 SENSITIVITY = 3

BACK

Figure 4.5 Detector Sensitivity Select Screen

Soft Keys
OCCUPIED ALARM SENSITIVITY:
Press the soft key next to one of
OCCUPIED PREALARM SENSITIVITY: these setting categories to proceed
to the next screen, where the
UNOCCUPIED ALARM SENSITIVITY:
setting value may be changed.
UNOCCUPIED PREALARM SENSITIVITY:
Change Alarm/Prealarm Sensitivity
This screen displays when any of the soft keys is pressed on the Detector Sensitivity Select screen.
The user can change detector sensitivity values using this screen.
The settings (1-9) displayed below the soft key are unique to the type of detector.

LAKEVIEW GENERAL HOSPITAL


SYSTEM NORMAL

10:22:34A FRI SEP 24, 2004


ADDRESS: L03D052
AUTOMATIC INACTIVE
ELEVATOR LOBBY EAST WING
FIFTH FLOOR Z003 SMOKE(PHOTO)

OCCUPIED ALARM =6,


1= 0.50%, 6= 1.66%
2= 0.73%, 7= 1.89%
3= 0.96%, 8= 2.12% ACCEPT
4= 1.19%, 9= 2.35%
5= 1.43%,
BACK

Figure 4.6 Change Alarm Sensitivity Screen

Soft Keys

68 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Clear Verify Counters Alter Status

OCCUPIED ALARM: The type of alarm/prealarm will display based on which soft key was
pressed in the previous screen. For example, in the screen above, OCCUPIED ALARM displays
because the OCCUPIED ALARM SENSITIVITY: soft key was pressed.
The detector sensitivity values display below the soft key. Select a value by pressing the soft key
until the desired value appears in the underlined field.
ACCEPT: Press to accept the change made on this screen, and to return to the previous screen.

4.4 Clear Verify Counters


The Clear Verify Counters screen lets you clear all counters for detectors selected for Alarm
Verification on the FACP. It displays when the “CLEAR VERIFY COUNTERS” soft key is pressed
on the Alter Status Menu screen.

LAKEVIEW GENERAL HOSPITAL


SYSTEM NORMAL

10:22:34A FRI SEP 24, 2004


ALTER STATUS MENU

LAKEVIEW GENERAL HOSPITAL

THIS WILL CLEAR ALL VERIFY COUNTERS

CLEAR COUNTERS

BACK

Figure 4.7 Clear Verify Counters Screen

Soft Keys
CLEAR COUNTERS: Press this soft key to clear all verification counters.

4.5 Clear History


This screen is displayed when the CLEAR HISTORY soft key is pressed on the Alter Status Menu
screen. It brings the user to a command screen, where the type of history may be selected for
clearing.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 69


Alter Status Walk Test

LAKEVIEW GENERAL HOSPITAL


SYSTEM NORMAL

10:22:34A FRI SEP 24, 2004


CLEAR HISTORY

ALARM HISTORY

EVENT HISTORY

ALL HISTORY

BACK

Figure 4.8 Clear History Screen

Soft Keys
ALARM HISTORY: Press to clear Alarm history.
EVENT HISTORY: Press to clear Event history.
ALL HISTORY: Press to clear both Alarm and Event history.

4.6 Walk Test


Walk Test allows the user to test the entire fire alarm system while away from the control panel.
There are two types of Walk Test - Basic and Advanced - and each type operates in audible mode.
Walk Test results are sent to the printer and to Event History as “Test”.

WARNING: Physically disconnect all releasing devices before starting Walk Test. It is not
! sufficient to disable in any other manner.

WARNING: Walk Test mode can deactivate fire protection. Observe the following important
! precautions.

IMPORTANT!
• Prior to Walk Test, secure all protected buildings, and notify the building owner/operator,
fire department, and other pertinent personnel that testing is in progress.
• Immediately after Walk Test is completed, notify the same people that testing is complete
and the system is restored to normal operation. Reconnect releasing devices.
• Walk Test will “time out” and return to normal operation after one hour when no Walk Test
activations have occurred during that time.
• Walk Test may be exited at any time by pressing the ABORT soft key on the screen

NOTE: Walk Test will not start if any devices are active (i.e., fire alarms, security, supervisories
or pre-alarms.) To perform a walk test while a device is active, disable the device and press the
System Reset button.

70 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Walk Test Alter Status

Basic Walk Test - The basic test allows a single operator to run audible tests on the panel. All logic
equation automation is suspended during the test. All ACS devices will default to Disable. They
may be enabled by selecting NO at the DISABLE ACS BOARDS soft key on the Walk Test Menu
screen (Figure 4.9 ).
Advanced Walk Test - The advanced test allows field-supplied output point programming that will
react to input stimuli such as CBE and logic equations. When points are activated in advanced
testing, each initiating event will latch the input. Release of the latch and subsequent activation of
the next point is controlled through use of the NEXT TEST soft key. All ACS devices default to
disable. They may be enabled by selecting NO at the DISABLE ACS BOARDS soft key on the
Walk Test Menu screen (Figure 4.9 ).
An advanced test is audible. An audible test is intended for pull station verification, magnet-
activated tests on input devices, input and output device and wiring operation/verification. Only
devices previously configured to participate and designated as part of the test through the following
screens will make sound.

Walk Test Activation Indications


FlashScan poll mode - Once the START TEST soft key has been pressed:
• each intelligent addressable input device will blink its address in red, and each intelligent
addressable output device will blink its address in green. Pattern examples are given below.
Table 4.1
Address Blink Pattern

8 8 blinks, long stop, 8 blinks, long stop,....


37 3 blinks, stop, 7 blinks, long stop, 3 blinks, stop, 7 blinks, long stop,....

152 15 blinks, stop, 2 blinks, long stop, 15 blinks, stop, 2 blinks, long stop....

• an input device activated in Walk Test latches on steady green for the duration of the test. If
the device is put in trouble (for instance, the detector head is removed, then replaced), the
LED will be latched on for the duration of the test.
• an output device activated in Basic Walk Test will remain active and the LED will glow
steady green for
- 4 seconds for alarms
- 8 seconds for troubles.
• an output device activated in Advanced Walk Test will remain active and the LED will glow
steady green until the NEXT TEST soft key is pressed.
CLIP poll mode - Once the START TEST soft key has been pressed:
• intelligent addressable input and output devices continue to blink red as usual until
activated.
• an input device activated in Walk Test latches on steady red during activation. If the device
is put in trouble (for instance, the detector head is removed, then replaced), the LED wil be
latched on for the duration of the test.
• an output device activated during Basic Walk Test will remain active and the LED will glow
steady green (if a FlashScan module) or steady red (if a CLIP module) for
- 4 seconds for alarms
- 8 seconds for troubles.
• an output device activated in Advanced Walk Test will remain active and the LED will glow
steady green (if a FlashScan module) or steady red (if a CLIP module) until the NEXT TEST
soft key is pressed.
Conventional Devices - Monitor modules with the Type Codes SMOKE CONV, HEAT DETECT,
and SMOKE DETECT, and outputs with the Type Code FORM C RESET do not participate in Walk

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 71


Alter Status Walk Test

Test other than blinking their addresses if they are polled in FlashScan mode. To prevent the
occurrence of false alarms for conventional devices, 24 volt power will be interrupted for up to
a minute after Walk Test has been exited.

4.6.1 Walk Test Menu

LAKEVIEW GENERAL HOSPITAL


SYSTEM NORMAL

10:22:34A FRI SEP 24, 2004


WALK TEST

BASIC/ADVANCED: ADVANCED

SILENT/AUDIBLE: AUDIBLE

PARAMETER: LOOPS ACCEPT

DISABLE ACS BOARDS: YES BACK

Figure 4.9 Walk Test Menu Screen

Soft Keys
BASIC/ADVANCED: Press to toggle between the two choices. Stop at the desired test.
SILENT/AUDIBLE: This soft key is for future use. Walk test is audible.
PARAMETER: Press to scroll through the choices. Stop at the desired parameter. Choosing the
loops parameter will bring up the Walk Test loops programming screen (Refer to Figure 4.10 )
Choosing the panel parameter will bring up the panel Walk Test screen (Refer to Figure 4.13)
Choosing the Devices parameter will bring up the Devices Walk Test screen (Refer to Figure 4.11.

If this parameter The participating devices/points in Basic The participating devices/points in


is chosen... Test will be... Advanced Test will be...

LOOPS All devices/points on all the FACP SLCs All devices/points on all the FACP
that are set to participate in Walk Test with SLCs, as well as panel circuit outputs
the exception of logic equations, whose that are set to participate in Walk Test.
activation is suspended.

PANEL The entire panel - all devices/points set to The entire panel - all devices/points set
participate in Walk Test - will participate with to participate in Walk Test including
the exception of logic equations, whose panel circuit outputs - will participate.
activation is suspended.

DEVICES Individual detectors tested one at a time. Detectors only.

Table 4.1 Walk Test Parameters


DISABLE ACS BOARDS: This soft key allows the operator to disable ACS devices during Walk
Test. Press to toggle between the two choices, YES (disable) and NO (enable). Default: YES

72 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Walk Test Alter Status

4.6.2 Walk Test Loops Parameters


This screen appears when LOOPS is chosen as a parameter at the Walk Test Menu.

LAKEVIEW GENERAL HOSPITAL


SYSTEM NORMAL

10:22:34A FRI SEP 24, 2004


WALK TEST
SETTINGS: BASIC, AUDIBLE, LOOPS

L1:NO L2:NO L3:YES


L4:NO L5:NO L6:YES
L7:NO L8:NO L9:YES
L10:NO

START TEST

BACK

Once the START TEST soft key has


been pressed and the test begun, this
message changes to ABORT

Figure 4.10 Walk Test Loops Programming Screen

The chosen settings are displayed (BASIC, AUDIBLE in Figure 4.10), and installed loops will
display with a participation field. The up and down arrow keys on the keypad navigate through the
fields. Choose YES for participation, NO for no participation, using the
NEXT SELECTION(+)/PREVIOUS SELECTION(-) keys on the keypad.

Soft Keys
START TEST: Press to begin Walk Test using the chosen parameters. Once Walk Test has begun,
this soft key becomes ABORT, and can be pressed at any time to exit Walk Test.
NEXT TEST: This key appears for Advanced Walk Tests when the panel parameter is chosen at the
Walk Test Menu Screen. Refer to Figure 4.13 for the location of this key. Press it to progress from
one activation to the next, latching the new point and releasing the latch on the previous point.

4.6.3 Advanced Walk Test Activation

LAKEVIEW GENERAL HOSPITAL


SYSTEM NORMAL

10:22:34A FRI SEP 24, 2004


WALK TEST SELECT
SETTINGS: BASIC,AUDIBLE,DEVICES

DEVICE:L01D005

NEXT POINT ACCEPT

PREVIOUS POINT BACK

Figure 4.11 Walk Test Devices Programming Screen

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 73


Alter Status Walk Test

This screen appears when DEVICES is chosen as a parameter at the Walk Test Menu. The chosen
settings are displayed (BASIC, AUDIBLE in Figure 4.11).
Soft Keys
DEVICE:Press this key to type the desired detector address into the underlined field.
NEXT POINT: Press this key to bring up the next installed address for an addressable detector into
the DEVICE field.
PREVIOUS POINT: Press this key to bring up the previous installed address of an addressable
detector into the DEVICE field.
ACCEPT: Press this key to begin Walk Test, and to proceed to the Devices Test Selection screen
(Figure 4.12).

4.6.4 Devices Test Selection

TROUBLE
PROG MODE ACTIVATED
NFS-3030
10:22:34A FRI SEP 24, 2004
WALK TEST IN PROGRESS
SETTINGS:BASIC, AUDIBLE, PANEL

START TROUBLE TEST

START ALARM TEST

START OBSCURATION TEST ABORT

This field will appear only for a beam detector with an integral sensitivity test feature.

Figure 4.12 Devices Test Selection Screen

Soft Keys
START TROUBLE TEST:Press this key to generate a Trouble on the selected detector.
START ALARM TEST: Press to generate an Alarm on the selected detector.
START OBSCURATION TEST: Press to perform an Obscuration Test on the selected Beam
detector. (Beam detectors only.)
ABORT: Press to stop the Walk Test.

NOTE: The Trouble, Alarm and Obscuration tests described above are additional tools provided to
ascertain the functionality of a detector. They are not a substitute for periodic maintenance and
sensitivity verification per NFPA 72.

74 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Program Time/Date Alter Status

Advanced Walk Test In Progress Screen

TROUBLE
PROG MODE ACTIVATED
NFS-3030
10:22:34A FRI SEP 24, 2004
WALK TEST IN PROGRESS
SETTINGS: ADVANCED, AUDIBLE, PANEL

NEXT TEST ABORT

Once the START TEST soft key has Once the START TEST soft key has
been pressed, this soft key appears. been pressed and the test begun,
the message changes to ABORT

Figure 4.13 Advanced Walk Test In Progress Screen.

4.7 Program Time/Date

LAKEVIEW GENERAL HOSPITAL


SYSTEM NORMAL

8:22:39A FRI SEP 24, 2004


PROGRAM TIME AND DATE

TIME/DATE: 08:22A TUE 1/01/03

TIME FORMAT: H:MM AM/PM

DATE FORMAT: MM/DD/YY ACCEPT

TIME ZONE: USA EASTERN BACK

Figure 4.14 Program Time and Date Screen

Soft Keys
TIME/DATE: Press to bring the cursor to the time/date field. The current time and date will be
displayed using the current format. Change the values using the keypad.
TIME FORMAT: Press to scroll through a list of formats as follows; HH:MM AM/PM; H:MM
AM/PM; HH:MM; and H:MM. Stop at the desired format.
DATE FORMAT: Press to toggle between MM/DD/YY and DD/MM/YY formats. Stop at the
desired format.
TIME ZONE: Press to scroll through a list of 34 time zone selections. Stop at the appropriate zone.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 75


Alter Status Control On/Off Point Select

ACCEPT: Press to save changes made on this screen and to return to the previous screen.

4.8 Control On/Off Point Select


This screen may be used to force a control module (SLC or panel circuit) off if it is on, or on if it is
off.

LAKEVIEW GENERAL HOSPITAL


SYSTEM NORMAL

10:22:34A FRI SEP 25, 2004


POINT SELECT

POINT: LyyMzzz (MODULE)

NEXT SELECTION ACCEPT

PREVIOUS SELECTION BACK

Figure 4.15 Control On/Off Point Select Screen

Soft Keys
POINT: Press this soft key to enter the point address to be forced on or off.

NOTE: A module with a releasing Type ID can not be forced.

NEXT/PREVIOUS SELECTION: Press to progress to the next or previous point on the loop.
ACCEPT: Press to continue to the Control On or Control Off screen.

4.8.1 Control Off


One of the following two screens will display when a point is selected and accepted in the previous
screen.
If the selected point is active, the Control Off screen will appear.

76 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Control On/Off Point Select Alter Status

LAKEVIEW GENERAL HOSPITAL


SYSTEM NORMAL

10:22:34A FRI SEP 24, 2004


CONTROL ON/OFF: L03M052
AUTOMATIC ACTIVE
ELEVATOR RECALL EAST WING
FIFTH FLOOR Z000 CONTROL

FORCE OFF BACK

Figure 4.16 Control Off Screen

Soft Keys
FORCE OFF: Press this soft key to change the state of the control module from A U T O M A T I C
A C T I V E to A U T O M A T I C I N A C T I V E .

A module with a releasing Type ID cannot be forced.

4.8.2 Control On
If the selected point is inactive, the Control On screen will appear

LAKEVIEW GENERAL HOSPITAL


SYSTEM NORMAL

10:22:34A FRI SEP 24, 2004


CONTROL ON/OFF: L03M052
AUTOMATIC INACTIVE
ELEVATOR RECALL EAST WING
FIFTH FLOOR Z000 CONTROL

FORCE ON

BACK

Figure 4.17 Control On Screen

Soft Keys
FORCE ON: Press this soft key to change the state of the control module from A U T O M A T I C
I N A C T I V E to A U T O M A T I C A C T I V E .

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 77


Alter Status Control On/Off Point Select

78 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Section 5: Service Screens

5.1 Version Information


Software version information may be displayed by pressing the Lamp Test special function key on
the keyboard for more than 5 seconds. The following three screens will appear in succession while
the Lamp Test key is pressed.

PANEL:

BOOT: 002.003.042 APR 16 2004


APP: 002.003.014 SEP 16 2004

LCM IMAGE:

BOOT: 001.002.002 MAY 07 2003


APP: 002.003.007 JAN 27 2004

LCD 160 IMAGE:


001.000.024 NOV 17 2003
001.003.005 MAY 06 2004

NCM: (NODE:134)
APP: 002.003.014 AUG 30 2004

Figure 5.1 Version Screen 1

DATABASE:

001.000 08:54 WED AUG 25 2004

LAST CHANGED:
SYSTEM DATA

FROM:
FRONT PANEL

SERIAL NUMBER:

Figure 5.2 Version Screen 2

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 79


Service Screens Power-up Screen

LCM SOFTWARE VERSION

1 BOOT: 002.003.002 APP: 002.003.007


2 BOOT: 002.003.002 APP: 002.003.007
3 NOT INSTALLED
4 NOT INSTALLED
5 NOT INSTALLED

Figure 5.3 Version Screen 3

5.2 Power-up Screen


The Power-up screen appears when the panel is powering up. A series of self-tests are performed
internally: the tests and the results of the tests appear on the screen as they are completed.

BOOT: 002.000.036 APP: 002.000.037

SELF TEST

RAM TEST: PASS BOOT CRC: PASS


NVRAM TEST: PASS APP CRC: PASS
RTC TEST: PASS DBASE CRC: PASS
KEYPAD : PASS LCM CRC: PASS
COMM 1 : PASS LCD-160 CRC: PASS
COMM 2 : PASS LANG CRC: PASS
COMM 3 : PASS

Figure 5.4 Self Test Screen

NOTE: “LCM” refers to the code resident in the CPU-3030, not the code that is programmed into
the LCM.

NOTE: “LCD-160” refers to the code resident in the CPU-3030, not the code that is programmed
into the LCD-160.

80 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Bootloader Screen Service Screens

5.3 Bootloader Screen


This screen is used for LCD-160 and Loop downloads. To display this screen, press the RESET key
during the entire power-up self-testing process, then release the key.

TROUBLE
LOADING..NO SERVICE
LAKEVIEW GENERAL HOSPITAL

BOOTLOADER

11:58:45A WED AUG 25, 2004

REBOOT

LCD-160 DOWNLOAD LOOP DOWNLOAD

Figure 5.5 Bootloader Menu Screen

LCD-160 DOWNLOAD:Press this soft key to display the LCD-160 Download menu screen.
REBOOT:Press this soft key to reboot the panel, and exit the bootloader screen.
LOOP DOWNLOAD:Press this soft key to display the Loop Download Menu screen.

5.3.1 LCD-160 Download Menu


The language and banner displayed on LCD-160s can be programmed at this screen.

TROUBLE
LOADING..NO SERVICE
LAKEVIEW GENERAL HOSPITAL
N001
BOOTLOADER

LCD-160 DOWNLOAD MENU

11:58:45A WED AUG 25, 2004


AUTO

ADDRESS: ADDRESS 001 START

DOWNLOAD TYPE: LANGUAGE-SPANISH BACK

Figure 5.6 LCD-160 Download Menu Screen

ADDRESS: Press this soft key to scroll through to the desired LCD-160 address. “All” means all
addresses. Default: ADDRESS 001.
Shortcut: Type 1 on the keyboard, which jumps to address 10, or type 2 for twenty, 3 for thirty,
0 to reset back to 1. Type an asterisk (*) to select all addresses.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 81


Service Screens Bootloader Screen

DOWNLOAD TYPE: Press this soft key to scroll through the languages (LANGUAGE-ENGLISH,
LANGUAGE-HEBREW, LANGUAGE-PORTUGUESE, LANGUAGE-SPANISH), BANNER, APP
and BOOT. Stop at the desired selection.
Choose a language to change LCD-160s selected at the ADDRESS field to display in that
language.
Choose BANNER to add the panel banner to those LCD-160 displays selected at the ADDRESS
field.
Select APP to download an application file to the selected LCD-160(s).
Select BOOT to download a boot file to the selected LCD-160(s).
AUTO:Press this soft key to automatically download to the LCD-160 the most up-to-date language,
bootloader, and application from the panel.
START:Press this soft key to begin the download.

5.3.2 Loop Download Menu


This screen allows the programmer to select loops for downloading applications and/or boot
programming.

TROUBLE
LOADING..NO SERVICE
LAKEVIEW GENERAL HOSPITAL

BOOTLOADER

LOOP DOWNLOAD MENU

11:58:45A WED AUG 25, 2004


AUTO

LOOP ADDRESS: LOOPS 1+2 START

DOWNLOAD TYPE: APP BACK

Figure 5.7 Loop Download Menu Screen

LOOP ADDRESS: Press this soft key to scroll through the Loops. Stop at the appropriate pair, or
select ALL.
DOWNLOAD TYPE: Press this soft key to scroll through the download types. Stop at the
appropriate type. Selections are: APP, BOOT, or APP/BOOT.
Select APP to download an application file to the selected loops.
Select BOOT to download a boot file to the selected loops.
Select APP/BOOT to select both for downloading.
AUTO:Press this soft key to automatically download to the selected loop(s) the most up-to-date
applications or boot programming from the panel.
START:Press this soft key to begin the download.

82 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Download Screen Service Screens

5.4 Download Screen


This screen is displayed during application/database/loop/LCD-160 downloads. The progress meter
shows the current download type and progress.

TROUBLE
LOADING..NO SERVICE
LAKEVIEW GENERAL HOSPITAL

BOOTLOADER

PERFORM DOWNLOAD

11:58:45A WED AUG 25, 2004

RECEIVING LCM IMAGE...

76%

Figure 5.8 Download Screen

5.5 Application Corrupt Screen


During power-up, the panel checks the image integrity of the application code. If the code is
corrupt, the panel cannot proceed, and the following screen is displayed. The user must use VeriFire
to download the application code. Usually this screen results from a power interrupt during a
critical period of application download. The trouble LED will flash and the piezo (if enabled) will
pulse while this screen is in effect.

TROUBLE
EPROM ERROR
LAKEVIEW GENERAL HOSPITAL

BOOTLOADER

11:58:45A WED AUG 25, 2004


ACKNOWLEDGE

PERFORM DOWNLOAD

Figure 5.9 Application Corrupt Screen

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 83


Service Screens Application Corrupt Screen

84 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Appendix A: Menu Hierarchy

A.1 Screens Overview

MAIN MENU
Event Counts Display
More Information
Multiple Event List
History Select
All Events
Alarms Only
Troubles Only
Supervisory Only
Security/Other
Time/Date Interval
Time & Date Range Select
Point Range
Point Range Select
Read Status
Smoke Detector
Heat Detector
Monitor Module
Control Module
General Zone
Releasing Zone
Logic Zone
Trouble Zone
Panel Input
Panel Output
Annunciator
Program/Alter Status
Panel Program
Network Parameters
IP Access
Panel Settings (Panel Settings (1) Screen
Reminder Menu
More (Panel Settings (2) Screen
Panel Timers
More
LCD Programming
ACS Programming
ACS Point Programming
Supervision
More
Password Change
Master Password
User Password
Weekly Occupancy Schedule
Remote Display Menu
Remote Display Point Programming
Loop Configuration
Loop Point Programming
Custom Action Message
Event Logging

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 85


Menu Hierarchy Screens Overview

Holiday Menu
Point Program
Detector Point Programming (1)
Zone Map
More (Detector Point Programming (2))
Custom Action Message
Weekly Occupancy Schedule
Sensitivity
More (Detector Point Programming (3))
Module Point Programming
More
Zone Map
Custom Action Message
Panel Module Point Programming
More
Zone Map
Custom Action Message
General Zone Point Programming
Releasing Zone Programming
Logic Zone Programming
Edit Logic Equation
Add Point/Zone
Add Logic Function
Add Time/Date
Trouble Zone Programming
Annunciator Board Label
Delete Program Menu
Delete Point
Autoprogram Menu
Confirmation Screens
Alter Status
Disable/Enable
Detector Sensitivity
Sensitivity Select
Change Alarm/Prealarm Sensitivity
Clear Verify Counters
Clear History
Walk Test Menu
Walk Test Loop Parameters
Advanced Walk Activation
Device Test Selection
Walk Test in Progress
Program Time/Date
Control On/Off Point Select
Control Off
Control On
Printer Functions
Programming
Print Programming Menu
Print Programming Menu (2)
Active Points
Active Points Menu
Walk Test
Detector Maintenance Report
Installed Points
Installed Points Menu
Installed Points Menu (Range)

86 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Screens Overview Menu Hierarchy

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 87


Menu Hierarchy Screens Overview

88 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Appendix B: Releasing Applications
WARNING: Do not rely on Disable to disable releasing points during testing. Releasing points
! must be physically disconnected.

B.1 Releasing Zones


The control panel includes ten releasing zones (ZR00-ZR09) that can be used to control up to ten
releasing operations. Each zone operates independently, and is fully programmable. To program a
releasing zone, refer to “Releasing Zone” on page 51.
There are four releasing functions, outlined below, that can be defined by entering values in the
associated fields during programming.

Function/Field Explanation

Delay Time Delay Time is the time that elapses between activation of an initiating device and
activation of all outputs mapped to the initiating device through a releasing zone.
Delay Time can have a value of 0 to 60 (seconds). A value of 0 will result in immediate
output activation upon activation of the initiating device.
Following is a graphic representation of what happens when a delay timer is set to 15
seconds for releasing zone ZR02.
Initiating device with Delay Time = 15 (seconds) All outputs with
releasing zone ZR02 in their zone
ZR02 in its zone 15 maps activate at
0 sec. 15 seconds
map activates sec.

NOTE: If cross-zoning is in effect, the delay time will not begin until the
cross-zoning conditions are met. Refer to “Cross Zones” on page 97 for
more information.

Abort Switch Selection of a 3-letter abort switch type code (ULI, IRI, NYC, or AHJ) defines the
operation of an Abort Switch in that releasing zone. Refer to the specific abort switch
type code heading in this appendix for details on how each functions.

Cross Zone Select one of three Cross Zone types (Yes, Zone, or Heat), or No (not used). A Cross
Zone requires tripping two or more initiating devices to activate the outputs mapped to a
releasing zone. Refer to the Section B.3.5 on page 97 section of this appendix for details
and examples.

Soak Time Soak Time specifies the length of time to dump releasing agents when a releasing zone
(NFPA 16 activates. When the Soak Time expires, the control panel automatically shuts the
Applications releasing solenoids for the active releasing zone. Soak Time can have a value of 0 to
only) 9999 seconds. If Soak Time is set to 0, the releasing solenoids will remain active until
system reset.
Following is a graphic representation of what happens when soak time is set to 300
seconds for releasing zone ZR02.
Initiating device At 300
with releasing Soak Time = 300 (seconds) seconds, the
zone ZR02 in its control panel
zone map shuts releasing
activates. All 0 300 sec.
solenoids for
outputs with ZR02 sec.
outputs with
in their zone maps ZR02 in their
activate. zone maps.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 89


Releasing Applications NFPA Releasing Applications

B.2 NFPA Releasing Applications


This control panel can be used for agent release or preaction/deluge control applications. In a
properly configured system with compatible, listed actuating and initiating devices, this control
panel complies with the following NFPA standards for installation in accordance with the
acceptable standard:
Standard Covers

NFPA 13 Sprinkler Systems

NFPA 15 Water Spray Systems

NFPA 16 Foam-water Deluge and Foam-water Spray Systems

NFPA 17 Dry Chemical Extinguishing Systems

NFPA 17A Wet Chemical Extinguishing Systems

NFPA 2001 Clean Agent Fire Extinguishing Systems

Table B.1 NFPA Standards for Releasing Applications

B.3 Abort Switches


The control panel provides for four types of abort switches - ULI, IRI, NYC, and AHJ - each of
which will affect the operation of the delay timer in the releasing zone. For example, an NYC Abort
Switch for releasing zone ZR05 affects only the delay timer in ZR05.
When an initiating device activates, pressing and holding the abort switch will prevent the control
panel from sending the command to dump releasing agents when the Delay Time expires.
Requirements for using an abort switch include the following:
• A monitor module must be connected to a UL-listed abort station, such as the NBG-12LRA
shown below.
• The monitor module must be programmed with the Type Code ABORT SWITCH.
• An abort switch shall not be used with a preaction system.

SYSTEM SYSTEM
Abort Switch NORMAL ACTIVATED

Manual Agent
Release lever

NBG-12LRA station with Abort Switch

Figure B.1 UL-listed Abort Station

This section contains information on each type of abort switch.


Example of an Abort Switch Application
The figure below contains an illustration for an abort switch application configuration using
releasing zone ZR05 as an example. The configuration includes:

90 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Abort Switches Releasing Applications

• A monitor module wired to an abort station and programmed with the Type Code ABORT
SWITCH
• All initiating devices and outputs with a common releasing zone in their zone maps - ZR05
in the example shown
• A fully programmed releasing zone - releasing zone ZR05 in the example shown. (Refer to
“Releasing Zone” on page 51 for programming information.)
In the following example, when an initiating device activates (one of the two detectors or the pull
station), pressing and holding the abort switch while the delay time is in effect will prevent the
control panel from sending the command to dump releasing agents when the delay time expires.
The abort switch selection (ULI, IRI, NYC, or AHJ) determines the function of the abort switch.

SYSTEM SYSTEM
NORMAL ACT IVATED

Monitor
Module with
Detector Detector
ABORT SWITCH
Type Code
Abort station with Abort Switch
and Manual Release lever

ZR05

Output Output Output Output


Module Module Module Module

Type Code Type Code Type Code Type Code


RELEASE CKT REL CKT ULC REL AUDIBLE REL END BELL

Example: If you program these three output modules Example: If you program a
as shown, these outputs activate at release. fourth module as shown,
this output activates when
the release is finished.

Figure B.2 Example of a Basic Configuration for an Abort Switch

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 91


Releasing Applications Abort Switches

B.3.1 ULI Abort Switch


A ULI Abort Switch has a standard UL-type delay timer that complies with UL Standard 864.

When an alarm initiates in the programmed releasing zone, the abort switch can be pressed while
the delay timer continues to count down, and held for as long as necessary. (If the abort switch is
pressed after the delay timer has expired, the abort switch has no effect.) Releasing the abort switch
starts a countdown by a 10-second ULI timer. When the 10-second ULI timer expires, the control
panel activates the releasing zone outputs.
Program selections for this releasing zone
Delay Time: 15 seconds
Abort Switch: ULI
Cross Zone: N Total time from alarm initiation to
Soak Time: 0 release:
Delay Time=15 sec. 5 + 15 + 10 = 30 seconds

0 sec 5 sec 15 sec 20 sec 30 sec

5 sec 15 sec
Alarm
10 sec
Press and hold the
Abort Switch for 15
seconds Release the Abort
Switch; the 10-second
ULI timer begins
When the
10-seconds ULI
timer expires, the

Figure B.3 ULI Abort Switch

92 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Abort Switches Releasing Applications

B.3.2 IRI Abort Switch


An IRI Abort Switch has a standard UL-type delay timer that complies with UL Standard 864,
operating like ULI but with additional functions for Cross Zones. Refer to “How Cross Zones
Work” on page 98 in this appendix for more information on cross zones.
When the first alarm occurs in a releasing zone programmed with a cross-zone code, pressing the
abort switch will prevent activation of the releasing zone should a second alarm occur while the
switch is held.
When the abort switch is released, if a second alarm has occurred while the switch was held, the
ten-second IRI timer activates immediately, and the control panel activates the releasing zone
outputs at the end of the IRI timer countdown.
When the abort switch is released and a second alarm has not occurred while the switch was held,
the panel waits for the cross-zone conditions to be met before activating the releasing zone.

WARNING:
! The IRI abort switch will only work if it is pushed before the second alarm occurs. If it is pushed after
the second alarm, the releasing zone will already have been activated, and the switch will have no
effect.

Program selections for this releasing zone


Delay Time: 15 seconds
Abort Switch: IRI
Cross Zone: Z Abort Switch held 15 sec.
Soak Time: 0
0 sec. 5 sec. 10 sec. 20 sec. 30 sec.

5 sec.

5 sec.
Alarm 1
10 sec.

Press and hold


the Abort
Switch for 15
10 sec
seconds
Alarm 2
(Cross-zone Release the abort
conditions met) switch; a 10-second
Total time from when Abort Switch is IRI timer begins
pressed to output activation: 15 + 10 = At the end of the 10
25 seconds seconds, the
control panel
Total time from when Abort Switch is activates releasing
released to output activation: 10 zone outputs
seconds

Figure B.4 IRI Abort Switch

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 93


Releasing Applications Abort Switches

B.3.3 NYC Abort Switch


An NYC Abort Switch has a standard NYC delay timer that adds 90 seconds to the programmed
Delay Time.

NOTE: An NYC timer does not comply with UL Standard 864.

When an alarm initiates in the programmed releasing zone, pressing and holding the abort switch
stops the delay timer countdown. The delay timer restarts at the beginning of its countdown when
the abort switch is released. When the Delay Time expires, the 90-second NYC timer starts
counting down. When both timers expire, the control panel activates releasing zone outputs.

NOTE: 120 seconds is the maximum delay after the abort switch is released. If the Delay Time
plus the NYC delay time of 90 seconds exceeds 120 seconds, the releasing zone outputs will still
be activated at 120 seconds after the abort switch is released.

Example 1 - Delay Time Does Not Exceed 120 Seconds


Program a Delay Time of 15 seconds and an Abort Switch type of NYC. The releasing zone
activates and the 15-second delay timer starts. Ten seconds into the delay timer countdown, press
and hold the abort switch for 30 seconds, then release the abort switch. The control panel restarts
the delay timer at 15 seconds and adds the NYC delay of 90 seconds. The delay timers will both
expire at 105 seconds, and releasing zone outputs will begin releasing at that time. Following is a
graphic example of a NYC Abort Switch and a delay timer programmed to a releasing zone.

Program selections for this releasing zone


Delay Time: 15 seconds
Abort Switch: NYC
Cross Zone: N Total time from alarm initiation to
Soak Time: 0 release:
10 + 30 + 105 = 145 seconds
Delay=15 sec. Delay=15 sec. NYC Delay=90 sec.

0 sec.
105 sec. (15 + 90). Does not exceed 120 seconds.
10 sec.

30 sec.
Alarm
Press and hold
the Abort Switch
Release Abort Switch---
At this point, the delay time When all timers are expired (in this
becomes the programmed example, 145 seconds after alarm
delay (15 sec.) plus 90 initiation, 105 seconds after the
seconds (105 sec.) OR 120 Abort switch has been released)
seconds, whichever is smaller the control panel activates
Releasing Zone outputs

Figure B.5 NYC Abort Switch -Example 1

Example 2 - Delay Time Exceeds 120 Seconds


Program a Delay Time value of 60 seconds and an Abort Switch type of NYC. The releasing zone
activates and the 60-second delay timer starts. Ten seconds into the Delay Time countdown, press
and hold the abort switch for 30 seconds, then release the abort switch. The control panel restarts
the delay timer at 60 seconds and adds the the NYC delay of 90 seconds. The delay timers will both

94 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Abort Switches Releasing Applications

expire at 150 seconds: however, this time exceeds the maximum of 120 seconds, so the releasing
zone outputs will begin releasing at 120 seconds, not at 150. Following is a graphic example of an
NYC Abort Switch and a delay timer programmed to a releasing zone.
Program selections for this releasing zone
Delay Time: 60 seconds
Abort Switch: NYC
Cross Zone: N
Soak Time: 0

Delay Time=60 sec. Total time from alarm initiation to release:


Pressing and releasing abort switch 10 + 30 + 60 + 60 = 160 seconds
restarts Delay Time=60 countdown after
40 seconds have elapsed.
Delay=60 sec. NYC Delay=90 sec.

0 sec. 150 sec. (60 + 90). Exceeds 120 seconds.

10 sec.
30 sec.
Alarm
Press and hold
the Abort Switch
120 sec. to release

The control panel activates


Release Abort Switch--- releasing zone outputs
At this point, the delay becomes after 120 seconds have
the programmed Delay Time (60 elapsed. The NYC timer
seconds) plus the NYC Delay (90 has not expired, but it is
seconds), which is 150 seconds, overridden by the control
OR 120 seconds, whichever is panel.
smaller.

Figure B.6 NYC Abort Switch -Example 2

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 95


Releasing Applications Abort Switches

B.3.4 AHJ Abort Switch


An AHJ (Authority Having Jurisdiction) Abort Switch has a delay timer that restores the
programmed Delay Time.

NOTE: An AHJ timer does not comply with UL Standard 864.

When an alarm initiates in the programmed releasing zone, the programmed Delay Time starts.
Pressing and holding the abort switch suspends the delay timer. When the abort switch is released,
the control panel restores the value of the programmed Delay Time and the delay timer counts
down. When the Delay Time expires, the control panel activates releasing zone outputs.
Program selections for this releasing zone
Delay Time: 60 seconds
Abort Switch: AHJ
Cross Zone: N
Soak Time: 0 Total time from alarm initiation to
Delay=60 sec.
release:
0 sec. 45 sec 60 sec. 75 sec. 135 sec.

45 sec.

30 sec.
Alarm
60 sec.

Press and hold


the Abort Switch
(30 sec.)

Release the abort switch and the


control panel restores the
programmed value Delay Time (60
sec.) and counts down When the Delay Time
expires, the control
panel activates
releasing zone outputs.

Figure B.7 AHJ Abort Switch

96 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Abort Switches Releasing Applications

B.3.5 Cross Zones


Purpose of Cross Zones
Programming the Cross Zone releasing function can set the control panel to activate a releasing
zone and any output mapped to that releasing zone only after a predetermined sequence of events
occurs.

NOTE: The FACP considers only the primary zone (the first zone in a point’s zone map) to
determine whether conditions have been met for Cross Zone type Z.

A summary of the types of Cross Zones and the conditions for activating a releasing zone:
Table 3:
Type Activates when

No A Cross Zone has not been selected. An alarm from any detector mapped to the
releasing zone activates it.

Yes Two or more initiating devices are in alarm that are mapped to the same releasing
zone.

Zone Two or more initiating devices are in alarm that are mapped to two different primary
zones and that are also mapped to the same releasing zone. Note that the FACP
considers only primary zones to determine whether releasing zone activation should
occur.

Heat At least one smoke detector mapped to a releasing zone is in alarm and at least one
heat detector mapped to the same releasing zone is in alarm.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 97


Releasing Applications Abort Switches

How Cross Zones Work


Below is an illustrated example of how Cross Zones work, using five Cross Zone selections (four
detectors and an SLC output module mapped to Releasing Zone ZR01):

General
Zone Z001

Zone map = Z002*, ZR01

Smoke Heat Smoke Smoke


General
Detector Detector Detector Detector
Zone Z002
L02D102 L02D104 L02D103 L02D101

Zone map = Z001*, ZR01 Zone map = Z001*, ZR01

Releasing
Zone ZR01

* indicates a
primary zone

REL Zone Map = ZR01


L02M107

Figure B.8 Illustrated Example of Cross Zone Programming

Each Cross Zone option and the conditions required to activate releasing zone ZR01 are shown in
the table below, according to the example in Figure B.8.
Table 4
Cross Zone Selection
Condition(s) Required to Activate the Releasing zone
(Cross=)

Cross=No An alarm from any initiating device activates the releasing zone.

Cross=Yes An alarm from any two initiating devices activates the releasing zone.

Cross=Zone An alarm from two initiating devices mapped to different primary general
zones, but mapped to the same releasing zone.
For example: • An alarm from L02D101 and L02D103
• An alarm from L02D102 and L02D104
• An alarm from L02D101 and L02D104
• An alarm from L02D102 and L02D103
The two detectors listed in each set above are each mapped to different
primary general zones, but both list ZR01 in their zone maps.

Cross=Heat Activation of heat detector L02D104 and one smoke detector


(L02D101, L02D102, or L02D103).

B.3.6 Using Type Codes for Releasing Zones


The control panel provides a set of Type Codes designed for releasing applications for inputs and
outputs. This section details how to program each of these Type Codes.

98 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Abort Switches Releasing Applications

NOTE: Panel circuit modules are not suitable for the release of agents.

Type Codes designed for releasing zone inputs (SLC monitor modules).
Table 5:
Type Code What the Type Code does Refer to

ABORT SWITCH Provides an abort function through “How to Program an Abort Switch”
(tracking) a monitor module (connected to a on page 100
UL-listed abort station) for a
releasing zone.

MAN. RELEASE Provides a manual release through “How to Program a Manual


(latching) a monitor module (connected to a Release Switch” on page 101
UL-listed pull station) for a releasing
zone.

MAN REL DELAY Provides a manual release with a “How to Program a Manual
(latching) 10-second delay through a monitor Release Delay Switch” on
module (connected to a UL-listed page 102
pull station) for a releasing zone.

SECOND SHOT Provides a second manual release “How to Program a Second Shot
(latching) through a monitor module Switch” on page 104
(connected to a UL-listed pull
station) for a releasing zone.

Type Codes designed for releasing zone outputs (SLC control modules).
Table 6:
Type Code What the Type Code does Refer to

REL END BELL Activates an NAC audio or visual “How to Program a Release End
device when releasing circuits shut Bell Circuit” on page 105
off.

REL CKT ULC Directs outputs to perform a release “How to Program a ULC Release
function as required by ULC. Circuit” on page 106

RELEASE CKT Directs outputs to perform a “How to Program a Release Circuit”


releasing function. on page 107

REL. FORM C Directs relay outputs to perform a “How to Program a Release Form-
releasing function. C Circuit” on page 108

REL AUDIBLE Activates audio or visual devices “How to Program a Release Audible
steady when releasing starts. Circuit” on page 109

INST RELEASE Activates non-releasing output (SLC “How to Program an Instant


modules) with no delay time. Release Circuit” on page 110

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 99


Releasing Applications Abort Switches

How to Program an Abort Switch


The following contains information needed to program an Abort Switch for a monitor module.

Description A monitor module, connected to a UL-listed abort station (such as the Notifier
NBG-12LRA), used to monitor an abort switch for a releasing zone. Multiple
monitor modules can be programmed with the ABORT SWITCH Type Code. They
will work like multiple conventional abort switches on a conventional zone.

Program Select a monitor module for use as an Abort Switch. While programming this
module (refer to “Module Point” on page 43 for instructions),
1. Select the ABORT SWITCH Type Code.
2. Enter the number of the desired releasing zone into the module’s zone map.
The releasing zone must be fully programmed, with the Abort Switch type
code included (refer to “Releasing Zone” on page 51).

Example A programming example of a monitor module programmed as an Abort Switch for Releasing
Zone ZR05.
SYSTEM SYSTEM
NORMAL ACT IVATED

Monitor
Detector
Module

Type Code
ABORT SWITCH
NBG-12LRA
station with
Abort Switch
R05

SLC SLC
output output
module module

Figure B.9 Monitor Module Configured as an Abort Switch

100 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Abort Switches Releasing Applications

How to Program a Manual Release Switch


The following contains information needed to program a Manual Release switch for a monitor
module.

Description A monitor module—connected to a UL-listed manual station (such as the Notifier NBG-
12LRA)—used to monitor a pull station for the manual release of agents. A Manual Release
switch overrides all timers, such as Delay Time or a Soak Time. Multiple monitor modules
can be programmed with a MAN. RELEASE type code. They work like multiple conventional
manual release switches on a conventional zone.

Program Select a monitor module for the manual release function. While programming this module
(refer to “Module Point” on page 43 for instructions),
1. Select the MAN. RELEASE type code.
2. Enter the number of the desired releasing zone into the module’s zone map. The releasing
zone must be fully programmed (refer to “Releasing Zone” on page 51).

Example A programming example of a monitor module programmed as an manual release switch for releasing zone
ZR05.
SYSTEM SYSTEM
NORMAL ACT IVATED

NBG-12LRA station with Manual Release Lever

Monitor
Detector
Module

Type Code
MAN. RELEASE

ZR05

SLC SLC
output output
module module

Figure B.10 Monitor Module Configured as a Manual Release Switch

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 101


Releasing Applications Abort Switches

How to Program a Manual Release Delay Switch


The following contains information needed to program a Manual Release Delay switch for a
monitor module.
Description
A monitor module—connected to a UL-listed manual station (such as the Notifier
NBG-12LRA)—used to initiate a manual release with 10-second delay time.
A Manual Release Delay switch overrides the FACP programmed Delay Time, but not
Soak Time.
Multiple monitor modules can be programmed with a MAN REL DELAY type code. They
work like multiple conventional manual release switches on a conventional zone.
Program
Select a monitor module for the manual release function. While programming this module
(refer to “Module Point” on page 43 for instructions),
1. Select the MAN REL DELAY type code.
2. Enter the number of the desired releasing zone into the module’s zone map. The releasing
zone must be fully programmed (refer to “Releasing Zone” on page 51).
Example
A programming example of a Monitor module programmed for MAN REL DELAY switch
for Releasing Zone ZR05.

SYSTEM SYSTEM
NORMAL ACT IVATED

Monitor
Detector
Module

Type Code
MAN REL DELAY
NBG-12LRA
station with
Manual Release ZR05
Lever

SLC SLC
output output
module module

Figure B.11 Monitor Module Configured as a Manual Release Delay Switch

For example, program releasing zone ZR05 with a Manual Release Delay switch for the following
releasing selections: Delay Time = 15, Abort Switch = ULI, Cross Zone = NO, Soak Time = 30.
When the Manual Release Delay Switch activates, the control panel replaces the remainder of the
15-second Delay Time, if running, with a 10-second timer.
Examples:
1. The FACP programmed Delay Time begins its 15 second countdown. The Manual Release
Delay switch is pulled when the FACP delay timer has counted down to 12 seconds. The 12
seconds remaining in the countdown are overridden by the 10-second delay initiated by the
Manual Delay switch. In this example, the total time elapsing from FACP countdown initiation
to agent release is 13 seconds, less than the original 15 second FACP Delay Timer countdown.

102 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Abort Switches Releasing Applications

2. The FACP programmed Delay Time begins its 15 second countdown. The Manual Release
Delay switch is pulled when the FACP Delay Timer has counted down to 8 seconds. The 8
seconds remaining in the countdown are overridden by the 10-second delay initiated by the
Manual Delay switch. In this example, the total time elapsing from FACP countdown initiation
to agent release is 17 seconds, more than the original 15 second FACP Delay Timer
countdown.
3. The FACP programmed Delay Time is not running (as would happen if the releasing station
were pulled before an alarm registered). The Manual Release Delay Switch is activated by the
pull station. Agent release will occur in 10 seconds.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 103


Releasing Applications Abort Switches

How to Program a Second Shot Switch

NOTE: The Second Shot switch can only be used with the MAN REL DELAY Type Code

The following contains information needed to program a Second Shot switch for a monitor module.

Description A monitor module—connected to a UL-listed manual station (such as the NBG-12LRA)—used as


for a second release of agents. A Second Shot switch overrides a Delay Timer programmed to the
same Releasing Zone.
Program Select a monitor module for the manual release function. While programming the module (refer to
“Module Point” on page 43 for instructions)
1. Select the SECOND SHOT Type Code.
2. Enter the number of the desired releasing zone into the module’s zone map. The releasing
zone must be fully programmed (refer to “Releasing Zone” on page 51).
Example A programming example of a monitor module programmed as a MAN REL DELAY switch for the first shot and a
SECOND SHOT switch for the second shot.
SYSTEM
N ORMAL
SYSTEM
ACT IVATED
NBG-12LRA station with
Manual Release lever Second
Shot
Switch
Monitor Monitor
Module Detector Module

Type Code ZR05 Type Code


MAN REL DELAY SECOND SHOT

SLC SLC
output output
module module

Figure B.12 Monitor Module Configured as a Second Shot Switch

With two monitor modules configured as shown above, program releasing zone ZR05 for the
following releasing selections: Delay Time = 15, Abort Switch = ULI, Cross Zone = Y, Soak Time
= 30
ZR05 can be activated in one of two ways, as described in the examples given below.
Example 1: If the detector initiates the alarm, ZR05 activates. Releasing begins after the delay
timer has expired (15 seconds). Releasing will continue for the soak timer duration (30 seconds).
The Second Shot switch can then be activated, and will remain activated for the soak timer
duration. Once the Soak Timer expires, the Second Shot switch can then be activated to initiate an
additional soak cycle.
Example 2: If the NBG-12LRA (Type Code MAN REL DELAY) lever is pulled, the delay timer
begins its 15 second countdown. Releasing will begin after the delay timer has expired, and will
continue for the soak timer duration (30 seconds). The Second Shot switch can then be activated,
and will remain activated for the soak timer duration. Once the Soak Timer expires, the Second
Shot switch can then be activated to initiate an additional soak cycle.

104 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Abort Switches Releasing Applications

How to Program a Release End Bell Circuit

NOTE: A releasing circuit with this Type Code requires the following selections: a Releasing
Zone; an output circuit mapped to the same Releasing Zone; Switch Inhibit; Non-Silenceable; No
Walk Test.

The following contains information needed to program a Release End Bell circuit for an SLC or
Panel Circuit output module.

Description An SLC or panel circuit output module to activate an audible or visual device
when releasing devices shut off. Multiple outputs with the REL END BELL Type
Code can also be mapped to the same Releasing Zone. When all the Releasing
Zone functions are complete, all outputs with the REL END BELL Type Code
activate at the same time. A REL END BELL circuit remains on until the system is
reset.

Program Select an SLC or panel circuit output module to use as a Release End Bell circuit.
While programming the point (refer to the Point Programming section of this
manual for instructions),
1. Select the REL END BELL Type Code,
2. Enter the number of the desired releasing zone into the module’s zone map.
The releasing zone must be fully programmed (refer to “Releasing Zone” on
page 51).

Example A programming example of a control module programmed as a Release End Bell for
Releasing Zone ZR05.

Monitor
Module Detector Detector Detector

ZR05

SLC SLC
Output output output Output
module module module module

Type Code Type Code Type Code Type Code


REL END BELL RELEASE CKT RELEASE CKT REL AUDIBLE

For example, a module programmed with the REL END BELL


Type Code activates when all releasing functions, such as the
releasing functions programmed for ZR05, shut off.

Figure B.13 Output Module Configured as a Release End Bell Circuit

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 105


Releasing Applications Abort Switches

How to Program a ULC Release Circuit

NOTE: A ULC Release Circuit with this Type Code requires the following selections: a Releasing
Zone; an output circuit mapped to the same Releasing Zone; Switch Inhibit ; Non-Silenceable; No
Walk Test.

The following contains information needed to program a ULC Release Circuit for an SLC output
module.

Description An SLC output module used to activate a releasing solenoid or other releasing device. Multiple
outputs with the REL CKT ULC Type Code can also be mapped to the same Releasing Zone. When
the Releasing Zone activates, all outputs with the REL CKT ULC Type Code also activate at the
same time. A ULC Release Circuit activates when:
• An initiating device programmed to the same Releasing Zone activates (two devices if
using the Cross Zone option)
• The Delay Timer for the Releasing Zone (if used) expires
• No Abort Switch for the Releasing Zone (if used) is active
A ULC Release Circuit —and all wiring to the release device—is fully supervised and usable with
power-limited energy cable.
Program Select an SLC output module to use for a ULC Release Circuit. While programming the point
(refer to the Point Programming section of this manual for instructions),
1. Select the REL CKT ULC Type Code,
2. Enter the number of the desired Releasing Zone into the module’s zone map. The releasing
zone must be fully programmed (refer to “Releasing Zone” on page 51).
Example A programming example of a control module programmed as a ULC Release Circuit for Releasing Zone ZR05.

Monitor
Module Detector Detector Detector

ZR05

Type Code Type Code


REL CKT ULC REL CKT ULC

SLC SLC SLC SLC


output output output output
module module module module
A B

Figure B.14 Output Module Configured as a ULC Release Circuit

106 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Abort Switches Releasing Applications

How to Program a Release Circuit

NOTE: A Release Circuit with this Type Code requires the following selections: a Releasing
Zone; an output circuit mapped to the same Releasing Zone; Switch Inhibit; Non-Silenceable; No
Walk Test.

NOTE: Do not use a Release Circuit for the following: An application requiring ULC Listing; An
application requiring power-limited energy cable.

The following contains information needed to program a Release Circuit for an SLC output circuit
module.

Description An SLC output module used to activate a releasing solenoid or other releasing device. Multiple
outputs with the RELEASE CKT Type Code can be mapped to the same Releasing Zone. When the
Releasing Zone activates, all outputs associated with the releasing zone and with the RELEASE
CKT Type Code also activate at the same time. A Release Circuit activates when:

• An initiating device programmed to the same Releasing Zone activates (two devices if
using the Cross Zone option)
• The Delay Timer for the releasing zone (if used) expires
• The Abort Switch for the releasing zone (if used) is not active

Program Select an SLC output module to use as a Release Circuit. While programming the point (refer to
the Point Programming section of this manual for instructions),
1. Select the RELEASE CKT Type Code
2. Enter the number of the desired Releasing Zone into the module’s zone map. The releasing
zone must be fully programmed (refer to “Releasing Zone” on page 51).

Example A programming example of a control module programmed as a Release Circuit for Releasing Zone ZR05.

Monitor
Module Detector Detector Detector

ZR05

Type Code Type Code


RELEASE CKT RELEASE CKT

SLC SLC SLC SLC


output output output output
module module module module
A B

For example, all modules programmed with the RELEASE CKT


Type Code activate simultaneously with other outputs (modules A
& B) programmed for ZR05.

Figure B.15 Output Module Configured as a Release Circuit

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 107


Releasing Applications Abort Switches

How to Program a Release Form-C Circuit

NOTE: An output with a REL. FORM C Type Code requires the following selections: a Releasing
Zone; an output circuit mapped to the same Releasing Zone; Switch Inhibit; Non-Silenceable; No
Walk Test.

The following contains information needed to program a Release Form-C circuit for an SLC
Form-C relay output module.

Description An SLC output module, configured as a relay, programmed to activate an output by opening or
closing a switch. Typical applications include closing doors and air handlers.

Program Select an SLC output module to use as a Releasing Form-C Circuit. While programming the
point (refer to the Point Programming section of this manual for instructions),
1. Select the REL. FORM C Type Code,
2. Enter the number of the desired Releasing Zone into the module’s zone map. The releasing
zone must be fully programmed (refer to “Releasing Zone” on page 51).

Example A programming example of a control module programmed as a Release Form-C circuit for Releasing Zone
ZR05.

Monitor
Module Detector Detector Detector

ZR05

SLC SLC SLC Output


output output output module
module module module C
A B
Type Code Type Code Type Code Type Code
REL. FORM C RELEASE CKT RELEASE CKT REL AUDIBLE

For example, an output module, configured as a Form-C relay,


activates simultaneously with other outputs (modules A, B & C)
programmed for ZR05.

Figure B.16 Control Module Configured as a Release Form-C Circuit

108 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Abort Switches Releasing Applications

How to Program a Release Audible Circuit

NOTE: An output with a REL AUDIBLE Type Code requires the following selections: a Releasing
Zone; an output circuit mapped to the same Releasing Zone; Switch Inhibit.

The following contains information needed to program a Release Audible circuit for an SLC or
Panel Circuit output module.

Description An output module programmed to activate an audio or visual device when all releasing outputs,
programmed to the same Releasing Zone, turn on. Multiple outputs with the REL AUDIBLE Type
Code can be mapped to the same Releasing Zone. When the Releasing Zone activates, all
outputs with the REL AUDIBLE Type Code activate at the same time.

Program Select a control module or panel circuit module to use as a releasing circuit. While
programming the point (refer to the Point Programming section of this manual for instructions),
1. Select the REL AUDIBLE Type Code,
2. Enter the number of the desired Releasing Zone into the module’s zone map. The releasing
zone must be fully programmed (refer to “Releasing Zone” on page 51).

Example A programming example of a control module programmed as a Release Audible circuit for Releasing
ZoneZR05.

Monitor
Module Detector Detector Detector

ZR05

SLC SLC
Output output output Output
module module module module
A B
Type Code Type Code Type Code Type Code
REL AUDIBLE RELEASE CKT RELEASE CKT REL AUDIBLE

For example, an output module programmed with the REL


AUDIBLE Type Code activates simultaneously with other
outputs (modules A & B) programmed for ZR05.

Figure B.17 Output Module Configured as a Release Audible Circuit

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 109


Releasing Applications Abort Switches

How to Program an Instant Release Circuit

NOTE: An output with an INST RELEASE Type Code requires the following selections: a zone
selection (a releasing zone may be used, but is not required); an output circuit mapped to the
same zone; Switch Inhibit; Non-Silenceable; No Walk Test.

The following contains information needed to program an Instant Release circuit for an SLC output
module.

Description An SLC output circuit module programmed to activate non-releasing devices, such as door
openers or warning sounders, without counting down delay timers. A device programmed with
the INST RELEASE Type Code device is supervised for open circuits and ground faults.

Program Select an SLC output module to use with a releasing circuit. While programming the point (refer
to the Point Programming section of this manual for instructions),
1. Select the INST RELEASE Type Code,
2. Enter the number of the desired Releasing Zone into the module’s zone map. The releasing
zone must be fully programmed (refer to “Releasing Zone” on page 51).

Example A programming example of a control module programmed as an Instant Release circuit for Releasing Zone
ZR05.

Monitor
Module Detector Detector Detector

ZR05

Type Code Type Code


INST RELEASE INST RELEASE

SLC SLC
SLC SLC
output output
output output
module module
module module
A B

For example, a module programmed with the INST RELEASE


Type Code activates simultaneously with other outputs
(modules A & B) programmed for ZR05.

Figure B.18 Output Module Configured as an Instant Release Circuit

110 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Abort Switches Releasing Applications

How to Program a Release Code Bell Circuit


When coded ouput is desired to indicate different phases of a releasing operation, the panel can be
programmed using Control-By-Event (CBE) to turn on outputs set to provide the chosen codes.

Example In the following example, programming is shown that will


Description
1. Turn on an output when the first alarm activates in a releasing zone, but Cross Zone
conditions are not met. Turn it off when the Delay Timer starts.
2. Turn on a different output when Cross Zone conditions are met and the Delay Timer
activates, and turn it off when releasing starts.
3. Turn on a different output when releasing starts, and turn it off when the system is reset.
The outputs are each set to a code appropriate for one of the three releasing phases: for
example, one code for the first alarm, a faster code when the Delay Timer activates, and a
continuous tone during releasing.

Program Program releasing zone ZR1 as follows:


ZR1 = Delay Time:15, Abort Switch:ULI, Cross Zone:YES, Soak Time:120
Map ZR1 to all inputs and outputs shown in this example.
Program logic zones as follows:
ZL1 = AND(OR(L1D1,L1D2,L1D3,L1D4,L1D5,L1D6),NOT(L1M30)
When conditions are met for ZL1, a first alarm has occurred in the releasing zone, but the
Delay Timer has not yet started. Map ZL1 to an output set to the code chosen for a first
alarm (L1M31 in this example).
ZL2 = AND(L1M30,NOT(L1M20))
When conditions are met for ZL2, the Delay Timer has started, but releasing has not begun.
Map ZL2 to the output set to the code chosen for when the Delay Timer activates (L1M32
in this example).
ZL3 = OR(L1M20)
When conditions are met for ZL3, the 120 second releasing operation has begun. Map ZL3
to the output that produces a continuous tone (L1M33 in this example).
Program output Type Codes as follows:
L1M20 = RELEASE CKT , L1M30 = INST RELEASE , L1M31 = CONTROL, L1M32 = CONTROL,
L1M33 = CONTROL

Illustration

L1D1 L1D2 L1D3 L1D4 L1D5 L1D6

ZR01

L1M20 L1M30 L1M31 L1M32 L1M33

Type Code Type Code Type Code Type Code Type Code
RELEASE CKT INST RELEASE control control control
ZL1 ZL2 ZL3

Figure B.19 A Release Code Bell Circuit Configuration

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 111


Releasing Applications Miscellaneous

B.4 Miscellaneous
B.4.1 Initiating Devices
Releasing zone initiating devices include the following:
• FST-851/751 intelligent heat detectors
• FSI-851/751, FSP-851/751, FAPT-851/751, FSL-751 intelligent smoke detectors
• Conventional detection UL-listed devices connected to monitor modules
Multiple zone initiating devices can be used for the same releasing hazard. Map zone initiating
devices to the same Releasing Zone. Factory Mutual and certain Local Authorities Having
Jurisdiction require using redundant wiring (NFPA 72 Style 6 or Style D) for initiating devices in
releasing applications.

B.4.2 Warning Sounders


Warning sounders connect to SLC or Panel Circuit output module circuits (refer to this panel’s
installation manual). Note the following:
• If selecting Cross Zones, a warning sounder only activates when two zones alarm.
• Warning sounders—unlike release solenoids—do not wait for a Delay Timer.
• If Coding Functions are required for warning sounders, use an SLC output module.
• The same releasing hazard can activate multiple NACs.
Instructions for activating warning sounders:

To activate a sounder Do this

When the Delay Timer starts, when the Map the SLC or Panel Circuit to a releasing hazard
releasing device activates, or both zone (R0-R9).

Immediately when one of the initiating Map the SLC or Panel Circuit output to a separate
devices activate zone (not R0-R9) that is also mapped to all initiating
devices of the hazard.

B.4.3 Auxiliary Control Functions


Instructions for using control functions:

Function Do this

A releasing application Use control modules set for dry contact operation. Program the
requires control relays control relays for different functions by following the
instructions in “To activate a sounder” above.

Providing control functions Use an ACM-8R remote relay module mapped to the software
zones of the control panel.

B.4.4 ACS Annunciation


Releasing points may be mapped to annunciators using annunciator point programming (Refer to
“ACS Point Programming” on page 28).

112 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Appendix C: Special Zone Outputs

C.1 Presignal and Positive Alarm Sequence (PAS)


C.1.1 What is Presignal and PAS?
Purpose
Presignal is a feature that initially causes alarm signals to only sound in specific areas, monitored
by qualified persons. This allows delay of the alarm up to 180 seconds after the start of alarm
processing. The control panel Presignal feature provides two selections:
• A Presignal Delay Timer (1:00 to 3:00 minutes) that delays activation of all outputs with a
CBE that includes Special Zone ZF0.
• A PAS (Positive Alarm Sequence) selection, in addition to the Presignal Delay Timer, that
allows a 15-second time period for acknowledging an alarm signal from a fire
detection/initiating device. If the alarm is not acknowledged within 15 seconds, all local and
remote outputs activate immediately and automatically.
An illustration of Presignal and PAS timing.
Presignal Delay Timer (60-180 s)

PAS (15 s)

If PAS=Y, alarm activates


outputs if not acknowledged
Initial alarm Alarm activates outputs, if the
annunciation control panel is not reset

Figure C.1 Presignal and PAS Time

The control panel delays activation of outputs containing ZF0 in their zone maps for all alarm
initiating devices that contain ZF0 in their CBE list. A subsequent alarm will abort the Presignal
Delay Timer and execute CBE lists.
Notes on using ZF0
• NFPA 72 requires installation of a PAS Inhibit switch, that can be used to turn off the PAS
delay timer when the control panel is unattended. Do so by programming a monitor module
with the Type Code, PAS INHIBIT.
• The Presignal Delay timer countdown can be stopped by pressing the SYSTEM RESET key
before the timer expires.
• Program zone ZF0 to participating inputs and outputs.
Restrictions on using ZF0
• Do not include ZF0 in the CBE list for a releasing device.
• Do not include ZF0 in the CBE list for any monitor module that connects to a device other
than an automatic fire detector.

C.1.2 Selecting Presignal and PAS Outputs


Presignal
The Presignal Delay Timer can be set to a value between 60 and 180 seconds. A Presignal Delay
Timer does not apply to the following:
• System Alarm relay

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 113


Special Zone Outputs Coding Functions for Panel Circuit Outputs

• TM-4 polarity reversal alarm output


• TM-4 municipal box output
• UDACT
Positive Alarm Sequence (PAS)
Outputs selected for PAS delay for 15 seconds. Acknowledgement within the 15-second delay will
set the Presignal Delay Timer to the full programmed value (60-180 seconds, including the PAS
delay of 15 seconds). When an alarm comes from an initiating device with a CBE list that includes
ZF0, the control panel delays the following outputs:
• System Alarm relay
• TM-4 polarity reversal alarm output
• TM-4 municipal box output
• UDACT

C.2 Coding Functions for Panel Circuit Outputs


Coding Functions are selectable pulsed signals that energize Panel Circuit outputs when a fire
alarm occurs.

NOTE: Do not include ZF8 in the zone map of Panel Circuits used for releasing or zone coding
applications.

Select Coding Functions on a global basis by setting the Panel Circuit Bell Coding field to March
or Temporal. (Refer to “Panel Settings (2) Screen” on page 22). Select individual panel circuit
output points for coding participation by entering ZF8 in the point’s zone map. All Panel Circuit
outputs with ZF8 in their zone maps will sound the same code when activated. The table below
contains descriptions of each Coding Function selection:

Coding Function
Signal
Selection

March Time (default) 120 PPM (pulses per minute)

Temporal 0.5s on, 0.5s off, 0.5s on, 0.5s off, 0.5s on, 1.5s off, repeats

Table C.1 Coding Function Selections

114 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Appendix D: AWACS™ Applications

D.1 AWACS Overview


AWACS™ (Advanced Warning Addressable Combustion Sensing) is a set of software algorithms
that provide the NFS-3030 with industry-leading smoke detection capability. The user can program
AWACS functions on a global or on a per-detector basis.
AWACS topics covered in this appendix:

Topic Page

AWACS features – Descriptions of AWACS features, such as Drift 115


Compensation, Sensitivity Adjust, programmable on a per-detector basis.

Pre-Alarm – Alert and Action settings, programming (global settings). 118

Detector Sensitivity Settings – Pre-Alarm and Alarm sensitivity settings 119


for photo, ion, laser, and multisensor detectors programmable on a per-
detector basis.

Detector Maintenance Features – Instructions for viewing and printing 121


detector maintenance information.

D.2 AWACS Features


AWACS features include the following:
• Drift Compensation and Smoothing
• Maintenance Warnings - Three Levels
• Self-optimizing Pre-Alarm
• Detector Sensitivity
• Cooperative Multi-Detector Sensing

D.2.1 Drift Compensation and Smoothing


Drift compensation uses algorithms (U.S. patent pending) that identify and compensate for long-
term changes in the analog readings from each smoke detector. (Typically, dirt and dust
accumulation inside the smoke chamber causes long-term changes in detector readings.) Drift
compensation does the following:
• Allows a detector to retain its original ability to detect actual smoke, and resist false alarms,
even as dirt and dust accumulates.
• Reduces maintenance requirements by allowing the control panel to automatically perform
the periodic sensitivity measurements required by NFPA Standard 72.
The software also provides smoothing filters to remove transient noise signals, usually caused by
electrical interference. Different smoothing algorithms are used, depending on the sensitivity
selection of each detector. Refer to “Detector Sensitivity Settings” on page 119 for more
information on detector sensitivity levels.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 115


AWACS™ Applications AWACS Features

A graphic representation of a detector analog reading using drift compensation and smoothing:

Alarm Level

without compensation

Awacs1a.cdr
Analog with compensation and
Reading smoothing

Time

Figure D.1 Graphic Representation of Drift Compensation

D.2.2 Maintenance Warnings – Three Levels


The software determines when the drift compensation for a detector reaches an unacceptable level
that can compromise detector performance. When a detector reaches an unacceptable level, the
control panel indicates a maintenance warning. The table below summarizes the three levels of
AWACS maintenance warnings:

Detector Compensation Percentage Range


Detector Trouble
Indicates Ion Photo or Laser
Message
Photo with Heat
N/A Compensation is within acceptable range. 6 - 80 6 - 45 3 - 50

LOW THRESHOLD A hardware problem in the detector. 0-5 0-5 0-2


MAINTENANCE REQ Dust accumulation that is near but below 92 - 99 92 - 99 83 - 99
the allowed limit. The Maintenance
Required is an alert level that indicates the
need for maintenance before the
performance of the detector is
compromised.
MAINT.URGENT Dust accumulation above the allowed limit. 100 100 100

Table D.1 Definitions of AWACS Maintenance Levels


A graphic representation of the maintenance levels:
DIRTY
MAINT.URGENT

MAINTENANCE REQ
Acceptable
Range

LOW THRESHOLD
Low Value

Figure D.2 Diagram of Maintenance Levels

116 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


AWACS Features AWACS™ Applications

D.2.3 Self-Optimizing Pre-Alarm


You can set each detector, except FST-851/751 (Heat), for Self-Optimizing Pre-Alarm (PA=1). In
this Self-Optimizing mode, the software measures the normal peak analog readings and sets the
Pre-Alarm level just above these normal peaks. This allows extremely sensitive Pre-Alarm
capability with reasonable protection against non-fire signals. The figure below shows a graphical
representation of the Self-Optimizing Pre-Alarm level:

Prealarm Threshold

Analog

Awacs4a.cdr
Reading

Time (days)

Figure D.3 Self-optimizing Pre-Alarm Level

D.2.4 Detector Sensitivity


The control panel provides nine Sensitivity Levels (Table D.2 on page 120) for alarm detection and
pre-alarm as follows:
• Alarm Sensitivity Levels You can select the sensitivity of a detector from 1-9 (1=highest
sensitivity; 9=lowest sensitivity).
• Pre-Alarm Sensitivity Levels You can select one of nine levels from 1 to 9 (0=no
Pre-Alarm, 1=self-optimizing, 2=highest sensitivity, 9=lowest sensitivity). You can set
Pre-Alarm operation to Action (latching) or Alert (non-latching) and to activate Special
Zones. For instructions on programming, refer to “Pre-Alarm” on page 118.
You can set the sensitivity levels as fixed or programmed for day and night operation. For details,
refer to “Coding Functions for Panel Circuit Outputs” on page 114.
A sample sensitivity window for a laser detector:
OBSCURATION (% PER FOOT)

2.1%
2.0% 2.0% Alarm Selection 9
1.5% 1.5% Alarm Selection 8 1.5% Pre-Alarm 9
1.0% 1.0% Alarm Selection 7 1.00% Pre-Alarm 8
0.7% 0.7% Pre-Alarm 7
0.5% 0.5% Alarm Selection 6 0.5% Pre-Alarm 6
0.2% 0.2% Alarm Selection 5 0.2% Pre-Alarm 5
0.1% 0.1% Alarm Selection 4 0.1% Pre-Alarm 4
0.05% 0.05% Alarm Selection 3 0.05% Pre-Alarm 3
0.03% Alarm Selection 2
SAMPLE 0.02% Alarm Selection 1 0.02% Pre-Alarm 2
SENSITIVITY
Self Adjust 1
WINDOW, laser detector

Figure D.4 Sample Sensitivity Levels for a FlashScan View Laser Detector

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 117


AWACS™ Applications Pre-Alarm

D.2.5 Cooperative Multi-Detector Sensing


Cooperative Multi-Detector Sensing is the ability of a smoke detector to consider readings from
nearby detectors in making alarm or pre-alarm decisions. Each detector can include up to two other
detectors in its decision. Without statistical sacrifice in the ability to resist false alarms, Cooperative
Multi-Detector Sensing allows a detector to increase its sensitivity to actual smoke by a factor of
almost 2 to 1. Ion, photo and laser detector types can participate. Cooperative Multi-Detector
Sensing also allows the combination of ionization with photoelectric technology in reaching an
alarm decision. The figure below shows a graph representing Cooperative Multi-Detector Sensing:

Combined

Alarm
SMOKE OBSCURATION

3 Sensors

Awacs5a.cdr
Time (minutes)

Figure D.5 Cooperative Multi-Detector Sensing

D.3 Pre-Alarm
D.3.1 Definition
The Pre-Alarm function is a programmable option which determines the system’s response to real-
time detector sensing values above the programmed setting. Use the Pre-Alarm function to get an
early warning of incipient or potential fire conditions. There are two levels of Pre-Alarm:
• Alert (Refer to “Alert Level” below)
• Action (Refer to “Action Level” on page 119)
Alert and Action Pre-Alarm settings are set with point programming. Unique Pre-Alarm sensitivity
levels (PA) for individual detectors are listed in “Detector Sensitivity Settings” on page 119.
The LEDs on detectors polled in FlashScan mode will light steady green when in pre-alarm.

D.3.2 Alert Level


Alert Functions
The control panel software, in addition to checking for alarm levels, checks for Pre-Alarm
thresholds for each addressable, intelligent smoke detector programmed for Pre-Alarm. If a
detector’s real-time sensing level exceeds the programmed Alert threshold, the control panel
indicates a Pre-Alarm condition for the detector. The control panel does the following functions
when a detector reaches pre-alarm level:
• The Pre-Alarm message is sent to the History buffer and to installed printers. The message
is sent (and time stamped) at the time that it first occurred. This historical data could provide
valuable information about the progress of a fire.
• The PRE-ALARM LED flashes and the panel sounder pulses until acknowledged.
• Zone Z000 (general alarm) or any other zone and the System Trouble and System Alarm
relays do not activate.

118 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Detector Sensitivity Settings AWACS™ Applications

• The Pre-Alarm indication for this detector will restore automatically to normal if its
sensitivity, programmable to one of nine settings, drops below pre-alarm level.
• A subsequent alarm for this detector also clears the Pre-Alarm indication.

D.3.3 Action Level


Action Functions
If you program a detector for Action Pre-Alarm and the detector reaches a level that exceeds the
programmed Pre-Alarm level, the control panel indicates an Action condition. The control panel
does the following functions when a detector reaches the programmed pre-alarm level:
• The Action message is sent to the History buffer and installed printers. The message is sent
(and time stamped) only at the time that it first occurred. This historical data could provide
valuable information about the progress of a fire.
• The PRE-ALARM LED and panel sounder pulse until acknowledged.
• The zone that is in the tenth position of the zone map for this detector activates. The tenth
zone is the right-most entry on line two of the detector zone map list in the Point
Programming screen. (For more information on detector zone positions, refer to Figure 3.25
and the accompanying text). The tenth zone can be used to control functions of a detector or
group of detectors once the pre-alarm level is reached. Tenth zone activations also allow
ACS annunciation by a detector or group of detectors in Action Pre-Alarm condition.
• Zone Z000 (general alarm) or any other zone and the System Trouble and System Alarm
relays do not activate.
• The Pre-Alarm condition and the zone programmed will latch until system reset, even if the
sensitivity drops below the pre-alarm level.
• A subsequent alarm condition for this detector clears the Action indication from the LCD
display alarm list.

D.4 Detector Sensitivity Settings


D.4.1 How to Select Pre-Alarm and Alarm Sensitivity
Each detector provides a host of selectable intelligent options. The control panel provides nine
levels of Pre-Alarm (PA:1–PA:9) and Alarm (AL:1–AL:9) in percent per foot obscuration:
• PA:0 no Pre-Alarm selection.
• PA:1 the self-optimizing setting where the control panel selects a suitable Pre-Alarm level
for a detector.
• PA:2–PA:9 the detector Pre-Alarm sensitivity level - with PA:2 the most sensitive and PA:9
the least sensitive.
• AL:1–AL:9 the detector Alarm sensitivity level - with AL:1 the most sensitive and AL:9
the least sensitive.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 119


AWACS™ Applications Detector Sensitivity Settings

Detector Type Alarm (FlashScan) Pre-Alarm


Photo Electric AL:1=0.50 % PA:1=Auto
SMOKE (PHOTO) AL:2=0.73 % PA:2=0.30 %
(See note * ) AL:3=0.96 % PA:3=0.47 %
AL:4=1.19 % PA:4=0.64 %
AL:5=1.43 % PA:5=0.81 %
AL:6=1.66 % PA:6=0.99 %
AL:7=1.89 % PA:7=1.16 %
AL:8=2.12 %~ PA:8=1.33 %~
AL:9=2.35 % PA:9=1.50 %
Ion AL:1=0.50 % PA:1=Auto
SMOKE (ION) AL:2=0.75 % PA:2=0.40 %
(See notes * , † and ‡ ) AL:3=1.00 % PA:3=0.50 %
AL:4=1.25 % PA:4=0.75 %
AL:5=1.50 % PA:5=1.00 %
AL:6=1.75 %~ PA:6=1.25 %~
AL:7=2.00 % PA:7=1.50 %
AL:8=2.25 % PA:8=1.75 %
AL:9=2.50 % PA:9=2.00 %
FlashScan View Laser AL:1=0.02 % PA:1=Auto
(See Note ‡ ) AL:2=0.03 % PA:2=0.02 %
AL:3=0.05 % PA:3=0.05 %
AL:4=0.10 % PA:4=0.10 %
AL:5=0.20 % PA:5=0.20 %
AL:6=0.50 %~ PA:6=0.50 %~
AL:7=1.00 % PA:7=0.70 %
AL:8=1.50** % PA:8=1.00 %
AL:9=2.00 % PA:9=1.50 %
Acclimate Alarm (CLIP)
Multi-Sensor AL:1=0.50 % AL:1=1.00 % PA:1=0.50%
AL:2=1.00 % AL:2=1.00 % PA:2=1.00 %
AL:3=1.00 to 2.00 % AL:3=1.00 to 2.00 % PA:3=1.00 %
AL:4=2.00 % AL:4=2.00 % PA:4=1.00 to 2.00%
AL:5=2.00 to 3.00%~ AL:5=2.00 to 4.00%~ PA:5=1.00 to 2.00 %~
AL:6=3.00 % AL:6=2.00 to 4.00% PA:6=2.00 %
AL:7=3.00 to 4.00 % AL:7=2.00 to 4.00% PA:7=2.00 %
AL:8=4.00 % AL:8=4.00 % PA:8=2.00 to 3.00 %
AL:9=thermal 135oF AL:9=4.00% PA:9=2.00 to 3.00 %
Heat (Adjustable Threshold) AL:1=43°C PA:1=40°C
AL:2=57°C PA:2=43°C
AL:3=63°C~ PA:3=57°C~
AL:4=68°C PA:4=65°C
AL:5=74°C PA:5=70°C
AL:6=88°C PA:6=75°C
AL:7=88°C PA:7=75°C
AL:8=88°C PA:8=75°C
AL:9=88°C PA:9=75°C
Beam Detector AL:1=25% PA:1=50%
(See Note †† )
AL:2=30% PA:2=55%
AL:3=40% PA:3=60%
AL:4=50% PA:4=65%
AL:5=30 - 50% PA:5=70%
AL:6=40 - 50% PA:6=75%
PA:7=80%
PA:8=85%
PA:9=90%
~Signifies the factory default setting.

* Detectors are suitable for open area protection within the listed air velocity range. Typically, this range is 0 - 4,000 ft/min for
photoelectric detectors and 0 - 1,200 ft/min for ionization detectors. Be sure to confirm this range before installing the detector
by referring to the manufacturer’s installation instructions.
† Use only alarm sensitivity setting of AL=1, AL=2 or AL=3 for ION detectors installed in Canada.
‡ The use of alarm sensitivities below 0.50% obscuration per foot requires a 90 day test to ensure that the environment
for the detectors is suitable for the higher sensitivity setting. (Refer to “To Test Detectors Set Below 0.50%
Obscuration per Foot” on page 121.)
** 1% max. on CLIP. Larger figures may display.
†† Refer to the beam detector manual to determine the alarm settings: they are a function of the distance between the detector and
its reflector. There is no Prealarm for beam detectors in CLIP mode.
Table D.2 Detector Sensitivity Settings

120 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Detector Status Display AWACS™ Applications

D.4.2 To Test Detectors Set Below 0.50% Obscuration per Foot


Using alarm sensitivities below 0.50% obscuration per foot requires a 90-day test to ensure that the
detector environment is suitable for the higher sensitivity setting. To meet Notifier and
Underwriters Laboratory requirements, test each detector planned to operate below 0.50%/ft
obscuration as follows:
1. Set the detector as follows:

Step Action
1 Initially set to the 0.50% obscuration per foot Alarm level.
2 Set the Pre-Alarm level to the desired final Alarm sensitivity.
3 Set the Pre-Alarm to Alert mode (non-latching).

2. Operate detectors continuously for 90 days with all environmental factors (such as,
temperature, humidity, air flow, occupancy, and so on) similar to the intended application for
the detectors. Record all events for each tested detector with an electronic History buffer or a
printout.
3. At the end of the 90-day test: An authorized Notifier representative, or an end user trained by
an authorized Notifier representative must inspect the results of the test. If the test results show
no alarms or pre-alarms for the tested detectors, reprogram the fire alarm system to set the
Alarm sensitivity to the more sensitive Pre-Alarm level of the test.

D.5 Detector Status Display


D.5.1 Detector Maintenance Display
Should the panel detect a low chamber value or maintenance condition with a detector, it will
generate a point trouble as described in the operations manual for this panel. The following Read
Status screen displays detector information that applies to the state of the smoke detector. It can be
reached with the following commands, starting at the Main Menu screen:
Press MAIN MENU
Press READ STATUS
Press READ STATUS POINT SELECT (enter the detector point address)
Press ACCEPT

LAKEVIEW GENERAL HOSPITAL


SYSTEM NORMAL

10:22:34A FRI SEP 24, 2004


READ ADDRESS: L03D052
AUTOMATIC INACTIVE
ELEVATOR LOBBY EAST WING
FIFTH FLOOR Z003 SMOKE(PHOTO)
Z005, Z027, Z066, , ,
, , , , ,
VALUES: 011% OF ALARM, 045% OF PREALARM
ALARM: 6= 1.66%, PREALARM: 3= 0.47%
ACTION/STATUS: NONE/VERY CLEAN
PEAKS:56% VERIFY COUNT:02 CO-OP:D100,158
10:22:34A FRI SEP 24, 2004
BACK

Figure D.6 Smoke Detector Screen - Read Status

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 121


AWACS™ Applications Detector Status Display

D.5.2 Print a Detector Maintenance Report


A Detector Maintenance Report lists detector maintenance status for each installed addressable
detector [except FDX (an analog heat detector)].
To print this report, press the Printer Function soft key at the Main Menu, then press the Detector
Maintenance Report soft key sends a Detector Maintenance Report (Figure D.7) to the printer
connected to the control panel.

******DETECTOR MAINTENANCE******************************************************
NORMAL SMOKE(LASER) Detector L01D001 000330us 000340us Comp:000% Pk: 002%
Alarm: 000% PreAlarm: 000% A6P6 V000 L01D001

NORMAL SMOKE ACCLIM Detector L01D002 000030us 000000us Comp:000% Pk: 000%
Alarm: 000% PreAlarm: 000% A8P8 V000 L01D002

Field Identification
Long term average of
raw analog value in
microseconds
Current reading of raw analog
value in microseconds Compensation
percentage
Extended
Label Label Detector peak
State

NORMAL SMOKE(LASER) Detector L01D001 000330us 000340us Comp:000% Pk: 002%

Alarm: 000% PreAlarm: 000% A6P6 V000 L01D001


Verification count
Percent of Percent of Address
alarm prealarm Programmed prealarm sensitivity setting in
threshold threshold effect when the report was generated
Programmed alarm sensitivity setting in
effect when the report was generated.

Figure D.7 Sample Detector Maintenance Report

D.5.3 To Interpret a Detector Status Display or Maintenance Report


The Detector Read Status Screen and Detector Maintenance Report provides the same information
(such as Device Status, Peak Value) about a detector. This section contains descriptions of each
item that appears in a Detector Read Status Screen or a Detector Maintenance Report.
Display Information
Lines 1- 4 - This could display any current event message, or, as in this example, the System
Normal message
Line 5 - Screen title and the address of the point being read
The area between the separator lines, lines 6-14, shows all information concerning the selected
point, which is L03D052 in the above example.
Line 6 - Line 6 displays two statistics that display for inputs (detectors and modules) and zones; in
the above example they are:
AUTOMATIC INACTIVE

122 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Detector Status Display AWACS™ Applications

The first field displays the point control. There are three designations that could appear in this field
Point Control Description
Designation

AUTOMATIC The point is being controlled automatically by the panel.

DISABLED The point has been forced into a disabled state by an outside source.

TROUBLE The point is in a trouble state and is no longer functioning automatically.

The second field displays the point status. There are two designations that could appear in this field.
Point Status Description
Designation

INACTIVE The point is currently reporting no events.

ACTIVE The point is currently in an off-normal status.

PREALARM The point is currently in a prealarm status.

The device is a detector (an input device) so by referring to the descriptions below, it can be
determined that the point is in a normal state.
Inputs: (detectors, monitor modules, zones)
If the point is not in trouble or disabled, and the point is automatically controlled by the panel, the
display will be one of the following:
AUTOMATIC INACTIVE
AUTOMATIC ACTIVE
AUTOMATIC PREALARM
If the point is disabled, the display will be one of the following. The Trouble Status field will
appear if the point is in trouble.
DISABLED INACTIVE <Trouble Status>*
DISABLED ACTIVE <Trouble Status>*
DISABLED PREALARM <Trouble Status>*
If the point is in trouble, the display will read:
TROUBLE INACTIVE <Trouble Status>*
TROUBLE ACTIVE <Trouble Status>*
TROUBLE PREALARM <Trouble Status>*
*The field <Trouble Status> will contain a device trouble message. Refer to this panel’s Operations
manual for information on these messages.
Line 7 - The custom label for this point
Line 8 - Continuation of the point’s custom label, first zone, and device type
Lines 9,10 - a display of all the zones that contain the current point being read.
Lines 11through 14 -These lines will have values in them only if the device is a detector. They will
not display for wireless detectors.
Line 11
VALUES:
The screen displays the Alarm and Prealarm values that are in effect when read status is
requested. For example, if occupied settings are in effect, occupied values will display

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 123


AWACS™ Applications Detector Status Display

121% OF ALARM - This field gives the detector reading as it relates to its preprogrammed
alarm level value (indicated in the next line on the screen). The example above shows the
detector exceeding the alarm level by 21%.
145% OF PREALARM - This field gives the detector reading as it relates to its
preprogrammed prealarm level value (indicated in the next line on the screen). The example
above shows the detector exceeding the prealarm level by 45%.
If the detector is an Alert heat detector, the value is indicated by a temperature reading
(example: 148 DEGREES F).
Line 12
The screen displays the Alarm and Prealarm levels that are in effect when read status is
requested. For example, if unoccupied settings are in effect, they will display.
ALARM: 6=1.66% - Six is the preprogrammed alarm level value for this detector: its value is
1.66%, indicating the percent per foot obscuration value assigned to level 6.
PREALARM: 3=0.47% - Three is the preprogrammed alarm level value for this detector: its
value is 0.47%, indicating the percent per foot obscuration value assigned to level 3.
Line 13
ACTION/STATUS: NONE/VERY CLEAN - This displays the maintenance status of the
device. The message that appears in this field depends on the drift compensation value. A
detector will automatically compensate for environmental contaminants and other factors over
time, until the tolerance value has been exceeded. The FACP will signal a trouble condition
when this level has been reached. Refer to the following table for messages and required
action.

Message Description

Replace/Malfunction Replace the defective detector. The detector may not


operate properly.

None/Very Clean No action necessary. The detector readings are near ideal.

None/Clean No action necessary. Although not ideal, the detector will


activate at the selected sensitivity level.

None/Fairly Clean No action necessary. The detector will activate at the


selected sensitivity level.

Needs Cleaning Clean the detector soon. The detector may cause a false
alarm because it has reached the drift compensation
tolerance value.

Needs Immediate Cleaning Clean immediately! The detector is a false alarm risk. The
drift compensation tolerance value has been exceeded.

Line 13 will not display for Acclimate detectors.


Line 14
PEAKS: 56% - This value represents the highest percent per foot obscuration reading taken by
this detector. It can be a historical figure, and does not necessarily represent the highest reading
for this particular alarm. Re-initializing the detector would reset this value to zero.
VERIFY COUNT: 02 - This displays the number of times the detector has gone into alarm.
This count aids in differentiating false alarms from actual alarms by showing repeated alarm
events that have come into the device. In this example, the detector has gone into alarm two
times since the verification count was begun. The FACP will signal a trouble condition when
the verify count exceeds 20.
CO-OP: D100,158 - Indicates the address(es) of any detector(s) linked with the detector that’s in
alarm for Co-operative Multi-Alarm Sensing. This field will not display for Acclimate detectors.
Line 15 - The current time and date are displayed in this line.
124 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007
Appendix E: CBE: Zones and Equations
CBE (Control-By-Event) is a software function that provides a means to program a variety of
output responses based on various initiating events. The control panel operates CBE through lists of
zones. A zone becomes listed when it is added to a point’s zone map through point programming.
• Each input point (detector, monitor module, Panel Circuit module) can list up to ten zones.
Allowable zone types are general zone, releasing zone, and special zone.
• Each output point (control module, Panel Circuit module) can list up to ten zones.
Allowable zone types are general zone, logic zone, releasing zone, special zone, and trouble
zone.
• Output points can list zone Z000 (general alarm). Non-Alarm or Supervisory points do not
activate zone Z000 (general alarm).
Networked CBE, or CCBE (Cooperative Control-By-Event), provides CBE initiating-event/output-
response relationships over the network through general, logic, and/or trouble zones. One of these
zones, programmed into the zone maps of points on this panel and points on other nodes, will
create network cause-and-effect relationships based on the type and content of the zone.

E.1 Zones
There are five types of zones that may be listed to a point for CBE purposes.

Zone Type Description/Function

General Zone A general zone is used to link input and output devices. When an input device activates, any general zone
in its zone map will be active, and any output device that has an active general zone in its map will be
active. General zones can be used as arguments in logic equations.
Zone Z000 is a general alarm zone: those points listing Z000 in their zone map participate in a general
alarm.
The panel will support up to 1000 general zones, designated as Z0 through Z999. General zones can be
used in CCBE applications when a node number is entered before the zone number.
Logic Zone A logic zone consists of a logic equation. Whenever the logic equation becomes true, all output points
mapped to the logic zone will activate.
The panel will support up to 1000 logic zones, designated as ZL1 through ZL1000. Logic zones can be
used in CCBE applications when a node number is entered before the zone number.

Trouble Zone A trouble zone consists of a trouble equation. Whenever the trouble equation becomes true, all output
points mapped to the trouble zone will activate.
The panel will support up to one hundred trouble zones, designated as ZT001 through ZT100. Trouble
zones can be used in CCBE applications when a node number is entered before the zone number.

Releasing Zone A releasing zone is used to control a releasing operation.


The panel will support up to ten releasing zones, designated as ZR00 through ZR09.

Special Zone ZF0 An output participates in Presignal with this special zone in its zone map.
ZF1 (Trouble less AC) An ouput programmed to turn on/off if a system trouble - other than an AC
power loss - occurs.
ZF2 (AC Trouble) An output programmed to turn on/off if an AC power loss or a brownout
condition occurs.
ZF3 (Security) An output programmed to turn on/off if a Security input activates.
ZF4 (Supervisory) An output programmed to turn on/off if a Supervisory input activates.
ZF5 Alternate An input programmed to switch from the active detector alarm sensitivities to the
Sensitivity Activation alternate alarm sensitivities when a non-fire point with ZF5 in its CBE activates.
ZF8 A panel output participates in March or Temporal time coding (depending on the
global setting) with this special zone in its zone map.
ZF9 An output programmed to turn on/off if a PreAlarm is active (ALERT, ACTION).

Time, date and holiday functions, which were formerly determined through special zones, are now defined in the panel
programming section of this manual.

Table E.1 Zone Table

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 125


CBE: Zones and Equations Equations

E.2 Equations
Logic and Trouble Equations can define complex relationships between input and output devices.
The FACP supports up to 1000 Logic Equations, each designated with a Logic Zone number of
ZL1 through ZL1000. It also supports up to ten Trouble Equations, each designated with a Trouble
Zone number of ZT001 through ZT100. Once created, these equations can be included in
input/output zone mapping.
1. Equations will always begin with a logic function. The function set is listed below.
2. Equations will be a maximum of 80 characters long, including parentheses and commas.
3. Logic and Trouble Equations can have a maximum of 10 logic functions unless a time delay
function is used: a time delay function must be the only function in its equation.
4. Equations are evaluated after all other devices have been evaluated.
5. One logic equation can be used as an argument in another logic equation, or one trouble
equation can be used in another trouble equation, only if the equation used has previously been
evaluated; that is, only zones with a lower number than the zone currently being edited can be
used as arguments.
6. A logic function can have a maximum of 20 arguments (inclusive start and stop address).
7. Maximum for the delay timer is 23 hours, 59 minutes, 59 seconds (23:59:59).
Equations are entered using Point Programming for logic or trouble zones. Refer to these sections
in this manual for instruction. The panel will check for errors after the user has entered the
complete equation. Possible errors are too many or two few parentheses, too many or two few
arguments inside the parentheses, unknown function and unknown device type.
Equations are made up of two basic components: functions (either logic or time delay) and
arguments.

E.2.1 Arguments
Arguments are discrete parts of a logic or time delay function used in a logic or trouble equation.
They can consist of another function, another equation, or any of the the devices listed below.

LxxD1 - LxxD159 detectors loop xx (159 per loop)


LxxM1 - LxxM159 modules loop xx (159 per loop)
P(1-12).(1-8) S5000 Modules (96)
(Nxxx)Z0 - (Nxxx)Z999* general zones (1000)
ZF1, ZF2, ZF3, ZF4, ZF5, ZF9 special zones (6)
T0 - T510 system troubles (trouble equations only) (511)
(Nxxx)ZT001 - (Nxxx)ZT100 trouble zones (100)
(Nxxx)ZL1 - (Nxxx)ZL1000 logic zones (1000)
xx = loop number (01 through 10)
(Nxxx) = Node number, necessary for CCBE programming. The node number identifies what
node the panel will watch for a particular zone activation.

Table E.2 Table of Arguments

E.2.2 Logic Equations


Logic Functions
The “AND” Operator
Requires that each argument be active.
Example: AND(Z02,Z05,L2D12)
All three arguments in the equation must be active for the logic zone to be activated.
The “OR” Operator

126 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Equations CBE: Zones and Equations

Requires that any argument be active


Example: OR(Z02,Z05,L2D12)
If any one of the three arguments in the equation is active the logic zone will be activated.
The “NOT” Operator
Inverts the state of the argument (activated to deactivated OR deactivated to activated).
Example: NOT(Z02)
The logic zone will remain activated until the argument activates.
If the argument activates the logic zone will deactivate.
The “ONLY1” Operator
Requires that only one argument be active.
Example: ONLY1(Z02,Z05,Z09)
If only one of the arguments activates the logic zone will be activated.
The “ANYX” Operator
Requires that the amount of arguments specified by the number preceding the arguments be
active.
Example: ANYX(2,Z02,Z05,Z09)
If any two or more of the arguments are in alarm the output point will be activated.
The X amount may be a value from 1 through 9.
The “XZONE” Operator
Requires that any combination of two or more input devices programmed to a zone be active.
Example: XZONE(Z02)
If any combination of two or more initiating devices that have been mapped to this software
zone come into alarm, then outputs mapped to this zone will activate.
The “RANGE” Operator
Each argument within the range must conform to the requirements of the governing function.
The range limit is 20 consecutive arguments.
Example: AND(RANGE(Z1,Z20))
Zone 1 through Zone 20 must all be active to activate the logic zone.
Time-based Functions
The panel supports three time-based functions: DEL, SDEL, and TIM. Special rules apply to an
equation containing a time-based function:
• Only one time-based function may be used in an equation.
• The time-based function must appear only once, as the first entry of the equation.
• It may not be nested within parentheses in the equation.
• Logic functions may be used in an equation that begins with a DEL or SDEL time-based
function: however, they must appear within parentheses following the time-based function.
Delay and duration times are in 24-hour format (HHMMSS); the allowable range is 00:00:00 to
23:59:59.
The “DEL” Function
Used for delayed operation.
Example: DEL(HH.MM.SS, HH.MM.SS,AND(L1M1,L1M140))
• The first HH.MM.SS is the delay time, the second HH.MM.SS is the duration time. If the
argument - AND(L1M1,L1M140) - in the example above activates, the function becomes
true after the argument has been active for the delay time, and continues to be true for the
duration time as long as the argument stays active. If the argument goes inactive during the
delay time or the duration time, the function reverts to false and the timing would begin all
over again if reactivated.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 127


CBE: Zones and Equations Equations

• If duration time of zero is entered (00.00.00), the equation will evaluate true when the delay
time expires if the argument remains active throughout the delay time period.
• If no duration or delay is specified, then the function will follow the input argument,
indicating true while it is active and false when it is inactive. DEL assumes a value of false
on reset.
The “SDEL” Function
A latched version of the DEL function.
Example: SDEL(HH.MM.SS, HH.MM.SS,L1M140)
• The first HH.MM.SS is the delay time, the second HH.MM.SS is the duration time. If the
argument (L1M140 in the example above) activates, the function becomes true after the
delay time, and will remain active for the duration even if the argument becomes inactive
during either the delay or duration time.
• If delay time of zero is entered (00.00.00), the equation will evaluate true as soon as the
argument (L1M140) activates and will remain that way for the specified duration, even if
the argument becomes inacative during that time.
• If no duration or delay time is specified, then the argument will not deactivate until reset,
even if the argument becomes inactive.
The “TIM” Operator
The TIM function is used to specify activation on specific days of the week or year.
Examples:
TIM(7-11-04) will evaluate as true for 24 hours starting at midnight (00:00:00) on July 11,
2004.
TIM(MO,TU,WE,TH,FR,08:00:00,23:00:00) will evaluate as true at 8:00 AM and remain true
until 11:00 PM (23:00) for the list of days supplied.
TIM(MO,TU,WE,TH,FR,08:00:00) will evaluate as true at 8:00 AM and remain true until
23:59:59 of the current day for the list of days supplied.
TIM(TU,07:45:00,18:30:00) will evaluate as true every Tuesday between 7:45 AM until 6:30
PM.
TIM(MO,TU,WE,TH,FR) will evaluate as true from Monday morning at 12:01 AM until
Friday evening at 11:59:00 PM.
Logic Equation Syntax Example
OR(AND(L1D1,L1D4),AND(L2D6,L2M3,NOT(L2M4)),ANY2(L1M13,L1M14,L1M15))
Equation begins with a logic function - OR
67 Characters (maximum of 80) - includes parentheses and commas.
5 Logic Functions (maximum of 10) - OR, AND, AND, NOT and ANY2.
8 Arguments (maximum of 20 per logic function) - L1D1,L1D4,L2D6,L2M3,L2M4....
The equation contains no spaces.
Evaluating an Equation
To evaluate an equation, start from the innermostpart of the equation and work outwards. For this
equation to evaluate TRUE and thus turn on any output mapped to it, the following conditions must
be met:

128 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Equations CBE: Zones and Equations

OR(AND(L1D1,L1D4),AND(L2D6,L2M3,NOT(L2M4)),ANY2(L1M13,L1M14,L1M15))

These These have Any TWO of


have to be to be ON.......and this OFF these have to be
ON ON

for this part to be TRUE for this part to be TRUE for this part to be TRUE

When this is TRUE OR When this is TRUE OR When this is TRUE

Then all outputs programmed with this equation will be turned ON.

E.2.3 Trouble Equations


A trouble equation follows the same syntax rules as the logic equation. The system allows up to a
hundred trouble equations, ZT001 through ZT100. It differs from a logic equation in the following
manner:
• Equations evaluate as true when the arguments go into trouble.
• Argument entries may consist of system trouble codes. Refer to Appendix H, “System
Troubles” for a listing of these codes.
Examples:
AND(L1M149,L2M110) will evaluate as true when both arguments go into trouble.
OR(ZT049,ZT050) will evaluate as true when either argument goes into trouble.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 129


Notes

130 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Appendix F: Detector Initialization

F.1 Overview
The control panel automatically performs a detector initialization routine when a detector is added
or changed.
The detector initialization routine takes approximately 2.5 minutes. During this time, the detector
being initialized does not perform fire protection functions. The LEDs of detectors polled in
FlashScan mode will latch a steady green while initializing, and return to blinking green when
initialization is over.
While initializing a detector, follow these guidelines:
• Make sure the detector is free of residual smoke during detector initialization.
• Do not test a detector during detector initialization.

NOTE: The control panel only performs detector initialization if it senses that a detector was
removed for at least 15 seconds.

WARNING:
If any detector is replaced with a different type of detector (for example, a laser detector is replaced
with a photoelectric detector), the control panel must be programmed immediately with the new
detector Type Code. Failure to do so can cause incorrect control panel operation, including false
alarms.

F.2 To Replace a Detector with a Different Type of Detector


If one type of detector is replaced with a different type of detector, the control panel must
immediately be programmed for the new detector type. To replace a detector, follow these steps:

Step Action

1 Delete the old detector point from FACP programming using the “Delete Point” screen on
page page 57.

2 Physically remove the old detector.

3 Enter point programming for this point and change the Type and FlashScan Code Label to
the values appropriate for the new detector. (Refer to “Detector Point” on page 38 for
programming instructions).

4 Physically install the new detector. Initialization will occur automatically

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 131


Detector Initialization To Replace a Detector with a Different Type of Detector

132 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Appendix G: Type Codes

G.1 What are Type Codes?


Type Codes are software selections for initiating devices (detectors and monitor modules) and
output devices (control modules, NACs, and Panel Circuits). Some Type Codes are self-
explanatory; that is, the Type Code matches the function of the device, such as a “Monitor” for a
monitor module, “Smoke(photo)” for a photoelectric detector, and so on. Type codes also provide
special functions, such as activating switches, solenoids, and control panel functions. FlashScan
devices are assigned a special FlashScan code.

G.2 How to Select a Type Code


Type Codes are selected at the Point Programming screens. Refer to the Point Program section of
this manual for instructions.
This appendix contains detailed descriptions of Type Codes for input and output devices, as listed
below:

Type of Device Refer to page

G.3.2, "Type Codes for Intelligent Detectors"Intelligent page 134


Detectors

Monitor ModulesG.3.3, "Type Codes for Monitor page 135


Modules"

SLC and Panel Circuit Outputs page 136

FlashScan Codes page 137

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 133


Type Codes Type Codes for Input Devices

G.3 Type Codes for Input Devices


G.3.1 Overview
This section provides a list of Type Codes for intelligent detectors and for monitor modules. The
following Point Types light an LED at the panel when activated.
• fire alarm - lights the FIRE ALARM LED
• supervisory - lights the SUPERVISORY LED
• security - lights the SECURITY LED
• trouble - lights the TROUBLE LED
G.3.2 Type Codes for Intelligent Detectors
Following is a list of intelligent detector Type Codes, which specify the type of detector installed at
an SLC address.
Point Characteristics
Type Code Point Type Latching Activates Device/Point Function
(Y=yes CBE
N=no)
SMOKE (ION) fire Y Y Ionization smoke detector
SUP L(ION)* supervisory Y Y Ionization smoke detector
SUP T(ION)*† supervisory N Y Ionization smoke detector
SMOKE(DUCTI) fire Y Y Duct Ionization smoke detector
SUP L(DUCTI) supervisory Y Y Duct ionization smoke detector
SUP T(DUCTI)† supervisory N Y Ionization smoke detector used as a duct detector to report
supervisory condition rather than alarm.
SMOKE(PHOTO) fire Y Y Photoelectric smoke detector
SUP L(PHOTO)* supervisory Y Y Photoelectric smoke detector
SUP T(PHOTO)*† supervisory N Y Photoelectric smoke detector
SMOKE(DUCTP) fire Y Y Duct Photoelectric smoke detector
SUP L(DUCTP) supervisory Y Y Photoelectric smoke detector used as a duct detector to report
supervisory condition rather than alarm
SUP T(DUCTP)† supervisory N Y Photoelectric smoke detector used as a duct detector to report
supervisory condition rather than alarm.
RFSMOKE(PHOTO) fire Y Y Wireless Photoelectric smoke detector
SMOKE(HARSH) fire Y Y HARSH smoke detector
SMOKE(LASER) fire Y Y Laser smoke detector
SUP T (LASER)*† supervisory N Y Laser Smoke Detector
SUP L (LASER)* supervisory Y Y Laser Smoke Detector
AIR REF fire Y Y Assign to one or more FSL-751 detectors used to monitor the quality
of air entering the protected area. The air quality measurement allows
the VIEW system to compensate for vehicle fumes, fog, or other
particles brought into the protected area through the ventilation
system. Poor air quality will lower the sensitivity of all FSL-751
detectors on the SLC. The detector sensitivity, however, remains
within approved limits (always less than 1% obscuration per foot).
Note: A reference detector still functions as a smoke detector, but the detector sensitivity level should be set to the least sensitive level—AL:9 and
PA:9 Alarm and Pre-Alarm sensitivity. Refer to “Detector Sensitivity Settings” on page 119 for a complete list of detector sensitivity settings.
HEAT fire Y Y 190oF heat detector
HEAT+ fire Y Y 190oF heat detector with low temperature warning
HEAT(FIXED) fire Y Y 135oF intelligent thermal sensor
HEAT (ROR) fire Y Y 15oF per minute rate-of-rise detector
SMOKE ACCLIM fire Y Y Combination Photoelectric/heat detector
SMOKE(ACCLI+) fire Y Y Combination Photoelectric/heat detector with low temperature
warning
SMOKE(MULTI)‡ fire Y Y Multisensor smoke detector
SMOKE(BEAM) fire Y Y Beam Smoke Detector

* Use only with approval of AHJ


† Not suitable for Canadian applications
‡ CLIP Mode only
Table G.1 Intelligent Detector Type Codes

134 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Type Codes for Input Devices Type Codes

G.3.3 Type Codes for Monitor Modules


Following is a list of monitor module Type Codes, which can be used to change the function of a
monitor module point.

NOTE: Do not assign Releasing Type Codes to Panel Circuit module points.

Point Characteristics
Type Code Point Type Latching Activates Device Function
(Y=yes CBE
N=no)
MONITOR fire alarm Y Y Alarm-monitoring device
NC MONITOR fire alarm Y Y Alarm monitoring device, where an open circuit=active. SLC only.
PULL STATION fire alarm Y Y Manual fire-alarm-activating device
SMOKE CONVEN fire alarm Y Y Indicates activation of a conventional smoke detector. An FZM-1 must be used for
alarm verification of a two-wire conventional detector.
SMOKE DETECT fire alarm Y Y Indicates activation of a conventional smoke detector. An FZM-1 must be used for
alarm verification of a two-wire conventional detector
WATERFLOW fire alarm Y Y Monitor for waterflow alarm switch
WATERFLOW S supervisory Y Y Indicates supervisory condition for activated waterflow switch
ACCESS MONTR non-alarm security N Y Used for monitoring building access
AREA MONITOR security Y Y Monitors building access
AUDIO SYSTEM trouble N N Used for monitoring audio equipment (use trouble zones for activations)
EQUIP MONITR non-alarm security N Y Used for monitoring equipment
SECURITY L security Y Y Indicates activation of security alarm
LATCH SUPERV supervisory Y Y Indicates latching supervisory condition
NC SUP L supervisory Y Y Indicates latching supervisory conditon, where an open circuit=active. SLC only.
TRACK SUPERV supervisory N Y Monitors for waterflow tamper switches for alarm points
NC SUP T supervisory N Y Indicates tracking supervisory conditon, where an open circuit=active. SLC only.
SPRINKLR SYS supervisory Y Y Monitors a waterflow device
SYS MONITOR security Y Y Monitors equipment security
TAMPER supervisory Y Y Indicates activation of tamper switch
ACK SWITCH non-alarm N N Performs Acknowledge function
ALLCALL PAGE non-alarm N Y Performs AMG-1 All-call and telephone page functions
DRILL SWITCH non-alarm* N N Performs Drill function, activates silenceable fire outputs
EVACUATE SWITCH non-alarm* N N Performs Drill function, activates silenceable fire outputs
FIRE CONTROL non-alarm N Y Monitors non-fire activations
NON FIRE non-alarm N Y Monitors non-fire activations
NC NON FIRE non-alarm N Y Monitors non-fire activations, where an open circuit=active. SLC only.
PAS INHIBIT non-alarm N N Inhibits Positive Alarm Sequence
POWER MONITR trouble† N N Monitors main and auxiliary power supplies (use trouble zones for activations)
RESET SWITCH non-alarm N N Performs Reset function
SIL SWITCH non alarm N N Performs Signal Silence function
TELE PAGE non-alarm N Y Performs function of Page Button on FFT-7. Allows remote paging to a fire area
TROUBLE MON trouble N N Monitors trouble inputs (use trouble zones for activations)
Blank fire alarm Y Y Monitors for a device with no description
HEAT DETECT fire alarm Y Y Monitors for conventional heat detector
RF MON MODUL fire alarm Y Y Wireless alarm-monitoring device
RF PULL STA fire alarm Y Y Wireless manual fire-alarm-activating device
RF SUPERVSRY supervisory N Y Wireless supervisory-monitoring device
ABORT SWITCH non-alarm N Y Provides an abort function through a monitor module (connected to a UL-listed
abort station) for a releasing zone.
MAN RELEASE fire alarm‡ Y Y Provides a manual release through a monitor module (connected to a UL-listed
pull station) for a releasing zone
MAN REL DELAY fire alarm† Y Y Provides a manual release with a 10-second delay through a monitor module
(connected to a UL-listed pull station) for a releasing zone
SECOND SHOT fire alarm† Y Y Provides a second manual release through a monitor module (connected to a UL-
listed pull station) for a releasing zone

* Local Mode treats this point as a fire alarm point.


† Does not participate in Local Mode
‡ Local Mode activation of NACs only. No releasing.
Table G.2 Type Codes for Monitor Modules

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 135


Type Codes Type Codes for Output Devices

G.4 Type Codes for Output Devices


This section provides a list of Type Codes for SLC control module points and panel circuit output
module points. Select from these codes to define the type of point..

NOTE: Do not assign Releasing Type Codes to Panel Circuit module points.

Silenceable Switch Walk Test


(Y=yes Inhibit (Y=yes,
SLC or Panel Local Mode
Type Code N=no)* (Y=yes, N=No)* Circuit Output Group Point Device Function
N=No)* Point Types
CONTROL Y N Y NAC n/a Supervised NAC
RELAY Y N Y Relay n/a Relay output
BELL CIRCUIT Y N Y NAC fire Supervised NAC
STROBE CKT Y N Y NAC fire Supervised NAC
HORN CIRCUIT Y N Y NAC fire Supervised NAC
AUDIBLE CKT Y N Y NAC fire Supervised NAC
SPEAKER Y N Y NAC fire Supervised NAC for speaker circuits
blank Y N Y NAC n/a Supervised NAC for undefined device
NONRESET N N N Relay or NAC n/a Supervised output, unaffected by “System Reset”
CTL command
TELEPHONE N N N Relay fire Supervised Telephone circuit
CONTROL NAC Y N Y NAC fire Supervised NAC
ISOLATED NAC Y N Y NAC fire Supervised NAC for notification appliance, used with
audio isolators. Activates even if there is a short on its
NAC circuit. For ULC installations only.
ISOLATED SPK Y N Y NAC fire Supervised NAC for speaker circuits, used with audio
isolators. Activates even if there is a short on its audio
circuit. For ULC installations only.
GEN ALARM N Y Y NAC fire Control Module, XPC-8, or an XP5-C (in NAC mode)
configured as a Municpal Box Transmitter for NFPA
72 Auxiliary Fire Alarm Systems applications (MBT-1
required). This Type ID can also be used for general
alarm activation.
GEN SUPERVIS N Y Y NAC supervisory Control Module, XPC-8, or an XP5-C (in NAC mode)
activated under any Supervisory condition (includes
sprinkler type).
GEN TROUBLE N Y Y NAC trouble Control Module, XPC-8, or an XP5-C (in NAC mode)
activated under any System Trouble condition.This device
will not turn ON when it is in trouble (short or open).
GENERAL N Y Y NAC trouble Control Module XPC-8 circuit, or an XP5-C (in NAC
PEND mode) that will activate upon receipt of an alarm and/or
trouble condition, and remain in the ON state until all
events have been ACKNOWLEDGED. This device will
not turn ON when it is in trouble (short or open)
TROUBLE N Y Y NAC trouble Control Module or an XP5-C (in NAC mode) that will
PEND activate upon receipt of a trouble condition, and
remain in the ON state until all troubles have been
ACKNOWLEDGED. This device will not turn ON
when it is in trouble (short or open).
ALARMS PEND N Y Y NAC fire Control module/panel circuit or NAC for output that
will activate upon receipt of an alarm condition, and
remain in the alarm state until all alarms have been
acknowledged.
INST RELEASE N Y N NAC (SLC only) fire Supervised for open circuits and ground faults. Short
= normal.
REL. FORM C N Y N Form-C relay n/a Directs relay outputs to perform a releasing function.
(SLC only)
RELEASE CKT N Y N NAC (SLC only) n/a Directs output to perform releasing function.
Supervised for open circuits and ground faults. Short
= normal.
REL CKT ULC N Y N NAC (SLC only) n/a Directs outputs to perform a release function as
required by ULC.
REL END BELL N Y N NAC n/a Activates NAC audio or visual device when releasing
circuits shut off.
REL AUDIBLE Y Y N NAC n/a Activates audio or visual devices steady when
releasing starts.
FORM C N Y N Form-C Relay n/a Control module used to interrupt 24V power to four-
RESET (SLC only) wire conventional detectors for 30 seconds upon
reset. Used in conjunction with a monitor module with
a conventional detector Type ID

* Values represent program defaults


Table G.3 SLC Control Module and Panel Circuit Output Module Type Codes

136 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


FlashScan Codes Type Codes

G.5 FlashScan Codes


This section provides a list of FlashScan Codes for FlashScan SLC devices. Select from these codes
to define the type of point:

Label Device/Point
HEAT FST-751/R, FST-851/R
ION FSI-751, FSI-851
PHOTO FSP-751,FSD-751P/RP, FSP-851, FSD-751PL/RPL, FSH-
751
BEAM FSB-200,FSB-200S
RFX SMOKE SDRF-751
LASER FSL-751
PHOTO/HEAT FSP-751T, FSP-851T
ACCLIMATE FAPT-751, FAPT-851
HIGH HEAT FST-851H
MONITOR FMM-1
MINI/DUAL FMM-101,FDM-1
MONITOR
MANUAL STATION FSM-101 (NBG-12LX Series)
ZONE MONITOR FZM-1
CONTROL FCM-1
RELAY FRM-1
TELEPHONE FTM-1
XPIQ BATTERY XPIQ BAT MON
XPIQ GND FLT XPIQ EF MON
XPIQ AC XPIQ AC MON
XPIQ TROUBLE XPIQ GEN MON
XPIQ STROBE XPIQ STROBE
XPIQ SPEAKER XPIQ SPEAKER
XPIQ TELEPHONE XPIQ TELEPHONE
XPIQ MUSIC XPIQ MUSIC
PS MON PS MON
PS CONTROL ACPS CONTROL
PS RELAY ACPS RELAY
RFX MON RFX MON
RFX SUP RFX SUP

Table G.4 FlashScan Codes

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 137


Type Codes FlashScan Codes

138 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Appendix H: System Troubles
Table H.1 is a list of System Troubles that could occur during the course of FACP operation. The
System Trouble Name column is the text that displays in the system trouble message. The System
Trouble Index is the number associated with the trouble in FACP memory. It is the number that can
be used as an argument in a Trouble Equation.
System System System System
Trouble System Trouble Name Trouble System Trouble Name Trouble System Trouble Name Trouble System Trouble Name
Index Index Index Index
0 GROUND FAULT 61 ANNUN 24 TROUBLE 197 STYLE 6 POS LOOP 8 400 REMOTE DISPLAY 9 TROUBLE
1-2 RESERVED 62 ANNUN 24 NO ANSWER 198 STYLE 6 POS LOOP 9 401 REMOTE DISPLAY 9 NO ANSWER
3 STYLE 6 POS LOOP 1 63 ANNUN 25 TROUBLE 199 STYLE 6 POS LOOP 10 402 REMOTE DISPLAY 10 TROUBLE
4 STYLE 6 POS LOOP 2 64 ANNUN 25 NO ANSWER 200-205 RESERVED 403 REMOTE DISPLAY 10 NO ANSWER
5 CORRUPT LOGIC EQUAT 65 ANNUN 26 TROUBLE 206 PRINTER PAPER OUT 404 REMOTE DISPLAY 11 TROUBLE
6 RESERVED 66 ANNUN 26 NO ANSWER 207 PRINTER OFF LINE 405 REMOTE DISPLAY 11 NO ANSWER
7 EPROM ERROR 67 ANNUN 27 TROUBLE 208-209 RESERVED 406 REMOTE DISPLAY 12 TROUBLE
8 INTERNAL RAM ERROR 68 ANNUN 27 NO ANSWER 210 MANUAL MODE ENTERED 407 REMOTE DISPLAY 12 NO ANSWER
9 EXTERNAL RAM ERROR 69 ANNUN 28 TROUBLE 211 NCM COMM LOSS 408 REMOTE DISPLAY 13 TROUBLE
10 PROGRAM CORRUPTED 70 ANNUN 28 NO ANSWER 212 STYLE 4 SHORT A LOOP 1 409 REMOTE DISPLAY 13 NO ANSWER
11 NO DEV INST ON L1 71 ANNUN 29 TROUBLE 213 STYLE 4 SHORT B LOOP 1 410 REMOTE DISPLAY 14 TROUBLE
12 PANEL DOOR OPEN 72 ANNUN 29 NO ANSWER 214 STYLE 4 SHORT A LOOP 2 411 REMOTE DISPLAY 14 NO ANSWER
13 AUXILIARY TROUBLE 73 ANNUN 30 TROUBLE 215 STYLE 4 SHORT B LOOP 2 412 REMOTE DISPLAY 15 TROUBLE
14 RESERVED 74 ANNUN 30 NO ANSWER 216 STYLE 4 SHORT A LOOP 3 413 REMOTE DISPLAY 15 NO ANSWER
15 ANNUN 1 TROUBLE 75 ANNUN 31 TROUBLE 217 STYLE 4 SHORT B LOOP 3 414 REMOTE DISPLAY 16 TROUBLE
16 ANNUN 1 NO ANSWER 76 ANNUN 31 NO ANSWER 218 STYLE 4 SHORT A LOOP 4 415 REMOTE DISPLAY 16 NO ANSWER
17 ANNUN 2 TROUBLE 77 ANNUN 32 TROUBLE 219 STYLE 4 SHORT B LOOP 4 416 REMOTE DISPLAY 17 TROUBLE
18 ANNUN 2 NO ANSWER 78 ANNUN 32 NO ANSWER 220 STYLE 4 SHORT A LOOP 5 417 REMOTE DISPLAY 17 NO ANSWER
19 ANNUN 3 TROUBLE 79 NETWORK FAIL PORT A 221 STYLE 4 SHORT B LOOP 5 418 REMOTE DISPLAY 18 TROUBLE
20 ANNUN 3 NO ANSWER 80 NETWORK FAIL PORT B 222 STYLE 4 SHORT A LOOP 6 419 REMOTE DISPLAY 18 NO ANSWER
21 ANNUN 4 TROUBLE 81 RESERVED 223 STYLE 4 SHORT B LOOP 6 420 REMOTE DISPLAY 19 TROUBLE
22 ANNUN 4 NO ANSWER 82 ADV WALK TEST 224 STYLE 4 SHORT A LOOP 7 421 REMOTE DISPLAY 19 NO ANSWER
23 ANNUN 5 TROUBLE 83 RESERVED 225 STYLE 4 SHORT B LOOP 7 422 REMOTE DISPLAY 20 TROUBLE
24 ANNUN 5 NO ANSWER 84 GROUND FAULT LOOP 2 226 STYLE 4 SHORT A LOOP 8 423 REMOTE DISPLAY 20 NO ANSWER
25 ANNUN 6 TROUBLE 85 STYLE 6 NEG LOOP 1 227 STYLE 4 SHORT B LOOP 8 424 REMOTE DISPLAY 21 TROUBLE
26 ANNUN 6 NO ANSWER 86 STYLE 6 NEG LOOP 2 228 STYLE 4 SHORT A LOOP 9 425 REMOTE DISPLAY 21 NO ANSWER
27 ANNUN 7 TROUBLE 87 GROUND FAULT LOOP 1 229 STYLE 4 SHORT B LOOP 9 426 REMOTE DISPLAY 22 TROUBLE
28 ANNUN 7 NO ANSWER 88 - 89 RESERVED 230 STYLE 4 SHORT A LOOP 10 427 REMOTE DISPLAY 22 NO ANSWER
29 ANNUN 8 TROUBLE 90 PROG MODE ACTIVATED 231 STYLE 4 SHORT B LOOP 10 428 REMOTE DISPLAY 23 TROUBLE
30 ANNUN 8 NO ANSWER 91 LOADING..NO SERVICE 232 RESERVED 429 REMOTE DISPLAY 23 NO ANSWER
31 ANNUN 9 TROUBLE 92 BASIC WALK TEST 233 STYLE 6 SHORT LOOP 1 430 REMOTE DISPLAY 24 TROUBLE
32 ANNUN 9 NO ANSWER 93 NFPA 24HR REMINDER 234 STYLE 6 SHORT LOOP 2 431 REMOTE DISPLAY 24 NO ANSWER
33 ANNUN 10 TROUBLE 94 NVRAM BATT TROUBLE 235 STYLE 6 SHORT LOOP 3 432 REMOTE DISPLAY 25 TROUBLE
34 ANNUN 10 NO ANSWER 95-104 RESERVED 236 STYLE 6 SHORT LOOP 4 433 REMOTE DISPLAY 25 NO ANSWER
35 ANNUN 11 TROUBLE 105 STYLE 6 ON LOOP 3 237 STYLE 6 SHORT LOOP 5 434 REMOTE DISPLAY 26 TROUBLE
36 ANNUN 11 NO ANSWER 106-107 RESERVED 238 STYLE 6 SHORT LOOP 6 435 REMOTE DISPLAY 26 NO ANSWER
37 ANNUN 12 TROUBLE 108 MAN EVAC INITIATED 239 STYLE 6 SHORT LOOP 7 436 REMOTE DISPLAY 27 TROUBLE
38 ANNUN 12 NO ANSWER 109 MAN EVAC RECEIVED 240 STYLE 6 SHORT LOOP 8 437 REMOTE DISPLAY 27 NO ANSWER
39 ANNUN 13 TROUBLE 110-175 RESERVED 241 STYLE 6 SHORT LOOP 9 438 REMOTE DISPLAY 28 TROUBLE
40 ANNUN 13 NO ANSWER 176 GROUND FAULT LOOP 3 242 STYLE 6 SHORT LOOP 10 439 REMOTE DISPLAY 28 NO ANSWER
41 ANNUN 14 TROUBLE 177 GROUND FAULT LOOP 4 243-249 RESERVED 440 REMOTE DISPLAY 29 TROUBLE
42 ANNUN 14 NO ANSWER 178 GROUND FAULT LOOP 5 250 SELF TEST FAILED 441 REMOTE DISPLAY 29 NO ANSWER
43 ANNUN 15 TROUBLE 179 GROUND FAULT LOOP 6 251 NETWORK INCOMPATIBILITY 442 REMOTE DISPLAY 30 TROUBLE
44 ANNUN 15 NO ANSWER 180 GROUND FAULT LOOP 7 252-383 RESERVED 443 REMOTE DISPLAY 30 NO ANSWER
45 ANNUN 16 TROUBLE 181 GROUND FAULT LOOP 8 384 REMOTE DISPLAY 1 TROUBLE 444 REMOTE DISPLAY 31 TROUBLE
46 ANNUN 16 NO ANSWER 182 GROUND FAULT LOOP 9 385 REMOTE DISPLAY 1 NO ANSWER 445 REMOTE DISPLAY 31 NO ANSWER
47 ANNUN 17 TROUBLE 183 GROUND FAULT LOOP 10 386 REMOTE DISPLAY 2 TROUBLE 446 REMOTE DISPLAY 32 TROUBLE
48 ANNUN 17 NO ANSWER 184 STYLE 6 NEG LOOP 3 387 REMOTE DISPLAY 2 NO ANSWER 447 REMOTE DISPLAY 32 NO ANSWER
49 ANNUN 18 TROUBLE 185 STYLE 6 NEG LOOP 4 388 REMOTE DISPLAY 3 TROUBLE 448 SYSTEM INITIALIZATION
50 ANNUN 18 NO ANSWER 186 STYLE 6 NEG LOOP 5 389 REMOTE DISPLAY 3 NO ANSWER 449-502 RESERVED
51 ANNUN 19 TROUBLE 187 STYLE 6 NEG LOOP 6 390 REMOTE DISPLAY 4 TROUBLE 503 SOFTWARE MISMATCH
52 ANNUN 19 NO ANSWER 188 STYLE 6 NEG LOOP 7 391 REMOTE DISPLAY 4 NO ANSWER 504 NO POWER SUPPLY INST
53 ANNUN 20 TROUBLE 189 STYLE 6 NEG LOOP 8 392 REMOTE DISPLAY 5 TROUBLE 505 LOOP 1-2 COMM FAILURE
54 ANNUN 20 NO ANSWER 190 STYLE 6 NEG LOOP 9 393 REMOTE DISPLAY 5 NO ANSWER 506 LOOP 3-4 COMM FAILURE
55 ANNUN 21 TROUBLE 191 STYLE 6 NEG LOOP 10 394 REMOTE DISPLAY 6 TROUBLE 507 LOOP 5-6 COMM FAILURE
56 ANNUN 21 NO ANSWER 192 STYLE 6 POS LOOP 3 395 REMOTE DISPLAY 6 NO ANSWER 508 LOOP 7-8 COMM FAILURE
57 ANNUN 22 TROUBLE 193 STYLE 6 POS LOOP 4 396 REMOTE DISPLAY 7 TROUBLE 509 LOOP 9-10 COMM FAILURE
58 ANNUN 22 NO ANSWER 194 STYLE 6 POS LOOP 5 397 REMOTE DISPLAY 7 NO ANSWER 510 TEST PROGRAM UPDATE
59 ANNUN 23 TROUBLE 195 STYLE 6 POS LOOP 6 398 REMOTE DISPLAY 8 TROUBLE
60 ANNUN 23 NO ANSWER 196 STYLE 6 POS LOOP 7 399 REMOTE DISPLAY 8 NO ANSWER
Table H.1 System Trouble Names and Codes

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 139


System Troubles

Table H.2 gives a description of each system trouble.


SYSTEM TROUBLES
TROUBLE MESSAGE TYPE TROUBLE DESCRIPTION
ADV WALK TEST There is an Advanced Walk Test in progress.
ANNUN x NO ANSWER The annunciator at address x is not responding.
ANNUN x TROUBLE The annunciator at address x is in trouble.
AUXILIARY TROUBLE Auxiliary device connected to the CPU-3030 at J5 is in trouble or the cable is missing.
BASIC WALK TEST A Basic Walk Test is in progress.
CORRUPT LOGIC EQUAT The database that houses the panel’s logic equations is corrupt. It must be re-downloaded,
or all programming must be cleared and re-entered.
DRILL INITIATED Drill has been initiated locally.
DRILL RECEIVED Drill has been initiated remotely.
EPROM ERROR The application and/or boot code is corrupt. Service required.
EXTERNAL RAM ERROR The external RAM test failed. Service required.
GROUND FAULT A ground fault has occurred within the panel.
GROUND FAULT LOOP x There is a ground fault on loop x.
INTERNAL RAM ERROR The internal RAM test failed. Service required.
LOADING.NO SERVICE A program or database download is in progress. The panel is NOT providing fire protection
during the download. Proper authorities should be notified while a download is in progress
so that other means of fire protection can be supplied.
LOOP x- x COMM FAILURE Loops x and x are not responding. The LCM and LEM for those loops must be serviced.
MAN EVAC INITIATED Local initiation of DRILL
MAN EVAC RECEIVED Network initiation of DRILL
MANUAL MODE ENTERED An annunciator has been placed in manual mode.
NCM COMM LOSS Communication lost between CPU-3030 and NCM
NETWORK FAIL PORT x Communication lost between NCM Port x and corresponding node.
NETWORK INCOMPATIBILITY The brand of this panel is incompatible with this network.
NFPA 24HR REMINDER This message occurs every day at 11 am if any troubles exist.
NVRAM BATT TROUBLE Battery backup and/or clock backup is low. Replace battery.
NO DEV. INST ON L1 No devices are installed on the system.
NO POWER SUPPLY INST The address of the main power supply has not been entered.
PANEL DOOR OPEN The panel door is open.
PRINTER OFF LINE Communication loss with printer. Restore power and/or printer’s online status.
PRINTER PAPER OUT Add paper.
PROGRAM CORRUPTED The database that houses the panel’s programming is corrupt. It must be re-downloaded, or
all programming must be cleared and re-entered. Service required.
PROG MODE ACTIVATED A user is currently using the panel’s programming menus.
REMOTE DISPLAY x NO ANSWER The remote display at address x is not responding.
REMOTE DISPLAY x TROUBLE The remote display at address x is in trouble.
SELF TEST FAILED Diagnostic test failed. Service required.
SOFTWARE MISMATCH One or more LCM software revisions do not match other LCMs, and/or the NCM is not
network version 5.0, or LCD-160 software is incompatible.
STYLE 4 SHORT x LOOP x Service required.
STYLE 6 POS. LOOP x There is an open circuit on the positive side of loop x. Style 6 and Style 7 are supervised
methods of communicating with addressable devices. If the control panel detects a trouble (open
only), it will drive both ends of the loop, maintaining communication in an unsupervised method.
The latching trouble will display on the panel as a Style 6 trouble until you correct the condition
and press reset. Style 7 configuration of the SLC requires the use of ISO-X modules.
STYLE 6 NEG. LOOP x There is an open circuit on the negative side of loop x. Style 6 and Style 7 are supervised
methods of communicating with addressable devices. If the control panel detects a trouble (open
only), it will drive both ends of the loop, maintaining communication in an unsupervised method.
The latching trouble will display on the panel as a Style 6 trouble until you correct the condition
and press reset. Style 7 configuration of the SLC requires the use of ISO-X modules.
STYLE 6 SHORT LOOP x Style 6 and Style 7 are supervised methods of communicating with addressable devices. If
the control panel detects a trouble (open or short), it will drive both ends of the loop,
maintaining communication in an unsupervised method. The latching trouble will display on
the panel as a Style 6 trouble until you correct the condition and press reset. Style 7
configuration of the SLC requires the use of ISO-X modules.
SYSTEM INITIALIZATION One or more devices (detectors or modules) can not report activation. This can occur following
system startup, when exiting Walk Test, or following a device trouble of No Response.
Table H.2 System Trouble Descriptions

140 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Appendix I: Local Settings
The panel programming LOCAL SETTING choices, available through the Panel Settings (2) screen
(refer to page 22) are described below. The Local Settings screen (Refer to Figure I.1) allows
scrolling through the available choices by pressing the soft key. Choices are Chicago, Singapore, or
Default (no special local settings).

LOCAL SETTINGS

LOCAL SETTINGS:SINGAPORE

Figure I.1 Local Settings Screen


I.1 Singapore
The LOCAL SETTING choice of SINGAPORE:
• Does not allow the disabling of a bell circuit either locally or via the network.
• A BELL CIRCUIT Type Code will allow power monitoring.
• The panel will sound the piezo when local control is set to OFF.
• Does not turn ON the System Trouble LED or the System Trouble relay for disabled points.
• Does not turn ON the System Trouble LED, the System Trouble relay, or the piezo when
Drill is initiated.
• Turns ON keypad LEDs, PCB LEDs, Panel Circuit LEDs, and all ACM-24/48 LEDs during
Lamp Test.
• Requires the user to initiate the start of the application when the panel boots/reboots. The
CPU Failure LED will be ON until the user initiates startup. (Refer to Figure I.2.)

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 141


Local Settings Chicago

TROUBLE
LOADING..NO SERVICE
LAKEVIEW GENERAL HOSPITAL
N083
BOOTLOADER

11:58:45A WED AUG 25, 2004

CPU HAS REBOOTED

CONTINUE ABORT

User should select CONTINUE User should select ABORT to


to initiate applications. abort applications.

Figure I.2 Singapore Application Initiation

I.2 Chicago
The LOCAL SETTING choice of CHICAGO disallows local drill or signal silence.
• The DRILL and SIGNAL SILENCE keys at the panel will not function.
• Annunciator Control Modules, SLC modules, and panel circuits given a drill or signal
silence Mode or Type Code will not allow local drill or signal silence initiation.
• Events must be acknowledged prior to system reset.

142 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Glossary
0.1 Glossary

This section contains descriptions of terms essential to know when programming the control panel.
Alarm History See History buffer.
Alarm Verification Timer A user-defined global software timer function that can reduce the
number of nuisance alarms. When you select Alarm Verification for a detector, the control panel
delays an alarm signal for a user-specified time period. (The control panel ignores the Alarm
Verification Timer if it detects another alarm during the verification period.)
Argument An argument is a discrete part of a logic function used in a CBE logic or trouble
equation. It can consist of panel/SLC addresses for detectors, modules, panel modules, zones,
special function zones, logic or trouble equations.
Auto Silence Timer A user-defined global software timer that functions like pressing the signal
silence key. The control panel silences all active outputs programmed as silenceable once the timer
has reached the selected time. For example, if 20 minutes is selected, when the timer reaches 20
minutes the control panel turns off all active outputs programmed as silenceable.
Autoprogram A software routine that directs the control panel to identify and automatically load
SLC-connected devices into the program with default values for all parameters. The Autoprogram
Finds and displays all new or missing intelligent detectors and modules--while ignoring devices
already installed in memory--so you can edit default option selections. Typically, you Autoprogram
the control panel as a first step in a new installation, or to add devices.
Control module An addressable module that a) switches power to a Style Y or Style Z NAC; or b)
functions as a Form-C control relay.
CBE (Control-by-Event) A programming method that lets you map inputs and outputs to provide a
variety of output responses based on various initiating conditions (events).
CLIP poll - Classic Loop Interface Protocol - CLIP - is standard polling of each intelligent device
(as differentiated from FlashScan poll, a method of group polling described below).
DCC (Display and Control Center) - Term for a display location, programmed to participate in
DCC, when it has control of Acknowledge, Signal Silence, System Reset and Drill functions.
Drift Compensation An algorithm which permits the maintenance of a constant smoke detector
sensitivity by accounting for environmental contaminants and other factors.
Download A function for loading a system program from a file on a personal computer and storing
the program in system memory of the control panel. Also see Veri•Fire.
FlashScan poll - a patented system (US Patent Number 5,539,389) that enhances the speed of
communication between analog intelligent devices. Communication is in a grouped fashion. When
one of the devices within the group has new information, the panel CPU stops the group poll and
concentrates on single points.
History buffer The control panel maintains a history buffer of the last 4000 events, each with a
time and date stamp. History events include all alarms, troubles, operator actions, and
programming entries. The control panel also maintains a 1000-event Alarm History buffer, which
consists of the 1000 most recent alarm events from the 4000-event history buffer.
latching An attribute of a device that keeps it in an active state until the condition causing the
activation is corrected and the panel is reset.
Missing device A device that exists in a program, but is not found by the control panel during
Autoprogram, typically because the device is disconnected.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 143


Glossary

NAC (Notification Appliance Circuit) A circuit or path directly connected to a notification


appliance device (a fire alarm system component--such as a bell, speaker, strobe, and so on--that
produces an audible output, a visual output, or both). On this panel, NACs can be panel circuits,
control modules or transponder points.
New device A device connected to the control panel, but not in program memory.
Non-latching An attribute of a device that follows the state of the fire alarm system. That is, if a
device is non-latching, it returns to its normal state automatically when the condition clears.
Notification Appliance Circuit see NAC.
Obscuration A reduction in the atmospheric transparency caused by smoke, usually expressed in
percent per foot.
Output circuit A control module connected to the SLC, a device connected to one of the four
NACs, or a Panel Circuit, such as an ICM-4.
Panel Circuit A circuit on a module connected to the control panel through connectors on the
control panel. The control panel identifies a Panel Circuit with the addressing convention Px.x. For
example P1.4, indicates Panel Circuit 4 on the first-position module connected to the control panel.
Point A system memory address occupied by an addressable SLC device, Software Zone, or
annunciator. For example, the control panel considers “L01M102”, a module on loop 1 at address
102, as a point.
Panel sounder The piezo sounder on control panel, that pulses when troubles and alarms occur.
Primary zone The zone in the first position of a point’s zone map. The FACP looks at this zone for
certain functions, such as some Cross Zone activations or Walk Test participation.
Silence Inhibit Timer A user-defined timer that disables the signal silence key function for the
programmed time (0-300 seconds) when a fire alarm occurs. All subsequent alarms can be silenced
immediately.
SLC (Signaling Line Circuit) A physical wire loop used to connect addressable detectors and
modules to the control panel.
General Zone A label, internal to the fire alarm system, assigned to a group of addressable
devices.
Switch Inhibit A software function that allows the programming of control modules, NACs, and
Panel Circuits so an operator cannot manually activate NACs. With Switch Inhibit enabled, an
operator cannot manually activate the NACs from the control panel.
System Normal message A message that displays on the second line of the LCD display during
normal operation of the control panel.
System Reset Pressing the System Reset fixed function key will clear all latched alarms and other
events if the initiating condition is gone. LEDs associated with these events will turn off.
Unacknowledged events will not prevent reset from functioning. If alarms or other off-normal
events exist after reset, they will resound the system. The System Reset key will not function if the
programmable Silence Inhibit timer is running.
The System Reset key will not immediatedly silence active outputs. If the Control-by-event
programming for the output evaluates false after reset, the output will deactivate. (Typically this is
30 seconds local, 60 seconds network.)
Terminal Interface EIA-232 bidirectional serial port used for upload and download functions.
Tracking An attribute of a device that allows it to enter an active state when a condition causes its
activation, then to return from an active to an inactive state when the condition causing its
activation is corrected.

144 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Glossary

Type Code A Type Code is a software function that specifies the function of a detector, control
module, monitor module, transponder point, NAC, or Panel Circuit point. (You can select a Type
Code while programming a point). The Type Code specifies what action the control panel takes
when the point activates. For example, when a monitor module with evacuate as a Type Code
activates, the control panel activates all outputs, as if someone pressed the drill key.
Upload A function for making a copy of a system program and storing the program as a file on a
personal computer. Also see VeriFire™ Tools Programming Utility.
View (Very Intelligent Early Warning) System A smoke detection system, consisting of the
NFS-3030 control panel and LPX-751 laser detectors, that provides very early warning of
smoldering fires.
VeriFire™ Tools Program Utility A software utility for uploading and downloading a system
program between a personal computer and the control panel through the EIA-232 port.
Walk Test A feature that lets a single (qualified) maintenance person to test a fire alarm control
panel and initiating devices without causing the control panel to enter into an alarm state.
Zone Map SLC and panel circuit inputs (detectors and monitor modules) and outputs (control
modules) provide for up to ten zone selections for CBE.

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 145


Glossary

146 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Index
A Force On/Off 77
Point select 76
Abort Switch 90
Detector Alarm Sensitivity 67
AHJ 96
Occupied & Unoccupied Alarm &
Basic configuration example 91
Prealarm Sensitivity 68
Configuration example with monitor mod-
ule 100 Point Select 67
Disable/Enable 66
IRI 93
Point selection for disable/enable 66
NYC 94
Program Time/Date 75
To program 100
Walk Test
Type Code (ULI, IRI, NYC, AHJ) 52, 89
Advanced 71
ULI 92
Audible 71
AC Fail Delay 24
Disable ACS Boards 72
ACCEPT soft key, about 11
Panel test screen 75
Acclimate, detector sensitivity settings 120
Parameter 72
Acknowledge
AKS-1 30 AMG 11, 27
AMPS-24 24
Local control 21
Annunciator, See ACS 27
ACPS-2406 24
Application Corrupt Screen 83
ACS
Annunciation, releasing applications 112 Argument 126, 143
Arrow keys 11
Number of annunciator devices per circuit
Auto Silence 25, 143
26
Autoprogram 58–63, 143
Point Programming 28
Auxiliary Control Functions, releasing applica-
Programming
tions 112
Mode 29
Auxiliary trouble reporting 30
Point 28
AWACS Applications 115–124
Source 29
Cooperative Multi-Detector Sensing 118
Smoke control devices 27
Detector Sensitivity 117
TM-4 27
Drift Compensation 115
Type 27
Maintenance Warnings, 3 levels 116
UDACT 27
Self-Optimizing Prealarm 117
UZC Zone Coder 27
Smoothing 115
Action level, prealarm 119
Address
To display 22 B
Advanced Warning Addressable Combustion BACK soft key, about 11
Sensing Beam detector sensitivity settings 42, 120
See AWACS Applications 115 Bell coding 22, 114
AHJ Abort Switch 96 Blink Mode 34
AKS-1 keyswitch, functions 30 Bootloader Screen 81
Alarm Sensitivity
Levels 117
Alarm, to set 41
C
Prealarm, to set 41 Canada
Table, displayed on screen 41 Auto Silence Value 25
To select 68, 119 Event ordering 21
Alarm Verification 24, 40, 45, 49, 143 ULC installation Alarm Verification timer
Alert Level, pre-alarm 118 value 24
Alter Status 65–77 Caution
Clear History 69 On systems utilizing the DCC function...
Alarm, Event or All History 70 22
Clear Verify Counters 69 CBE (Control-by-Event) 125, 143
Control On/Off 76 CCBE (Cooperative Control-By-Event) 125

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 147


D–F Index

Channel A,B thresholds 19 Maintenance Warning 116


Clear Multi-Detector (Coop) 40
ACS programming 57 Occupancy Schedule 42
All programming 57 Point programming 38
History 69 Poll 34
Loop programming 57 Pre-Alarm Sensitivity Level 117
Panel modules programming 57 Print a Detector Maintenance Report 122
Panel programming 57 Sensitivity 40
Verify Counters 69 To replace 131
CLIP Mode 34 To test detectors set below 0.50% obscura-
Coding 22, 114 tion per foot 121
Communication loss, panel & SLC 40 Type Codes 38
Control Module 143 Weekly Occupancy Schedule 42
See Module, SLC or Panel Circuit Zone map 38, 39
Control On/Off 76 Disable/Enable Point Selection 65
Cooperative Multi-Detector Sensing 40, 118 Displayless Mode
CPU-3030 30 Service-level switches, ACK, SIG-SIL,
CRM-4RK/ICE-4 48 SYSRST, LAMP 10
Cross Zone 89 Do not assign Releasing Type Codes to Panel...
Programming example 98 135, 136
To activate a Releasing Zone 97 Download 143
Types 97, 98 Download screen 83
Custom Action message Drift Compensation 115, 143
Detector 40, 41 Graphic representation 116
Module 45 Drill
Panel module 49 AKS-1 30
To create 35 Local control 21
To view 35
To view, point 41 E
Equations
D Arguments 126
DCC Participation 22 Editing 52
Default settings soft key 23 Logic 126
Default Timers soft key 25 Functions 126
Delay Time 89 Time-based functions 127
Delete point 57 Trouble 129
Delete Program 56 Event Counts Display 15
Clear Event logging 36
ACS programming 57 Event ordering
All programming 57 Canada Event Order 21
Loop programming 57 USA Event Order 21
Panel 57 Extended label 38, 44, 48
Panel module programming 57
Delete point 57 F
Delete Program Menu, when programming panel
the first time 18 Factory default settings
Password 12
Detector
Alarm Sensitivity Levels 41, 67, 117 Field information, how to enter 11
Alarm Verification 40 Fixed position, detector zone map 39
Custom action message 40 FlashScan code label 38, 44
Force On/Off (point) 77
Drift Compensation 115
FST-751 117
Extended label 38
FZM-1
FlashScan code label 38
& alarm verification 45
Label 38
Local Mode 40
Maintenance Level messages 116

148 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Index G–M

G Loop Download Menu


Download Type 82
General Zone 51, 144
Loop Address 82
Group Zone Disable 66
Loop programming 34
CLIP 34
H Configuration 33
Heat (Adjustable Threshold), detector sensitivity Detector poll 34
settings 120 FlashScan 34
History buffer 143 Module poll 34
History Display 15 Rapid poll 34
Holiday menu 36 Wiring style 34

I M
ICM-4RK/ICE-4 48 Main Menu 11, 15
Initial programming Main Power Supply Address 30
Basic procedure 11 Maintenance Warnings 116
Initiating Devices for releasing zones 112 Major changes and additions
Insert (Logic equation screen) 53 Basic procedure 11
Instant Release Circuit Manual Release Delay Switch
Control module configuration example Monitor module configuration example
110 102
To program 110 To program 102
Ion FSI-751, detector sensitivity settings 120 Manual Release Switch
IP Access 20 Monitor module configuration example
IRI Abort Switch 93 101
ISO-X module 140 To program 101
IZM-8RK/IZE-A 47, 48, 50 March Time coding 22, 114
Master password, see Password 12
J Maximum verification count 24
Menu Hierarchy 85
J5 of CPU-3030 30
Module poll 34
Module, Panel Circuit
L Coding 22
Label, point 38, 44, 48 Control 50
Language selection 26 Silenceable 50
LCD-160 82 Switch Inhibit 50
latching 143 Walk Test 50
LCD Programming 26 Zone map 50
LCD programming Extended label 48
Backlight 26 Label 48
Current setting 26 Module Type (Control/Monitor) 48
Factory default setting 26 Monitor 49
Intensity down 26 Alarm Verification 49
Intensity up 26 Custom Action message 49
Language 26 Zone map 49
LCD-160 Download Menu Point addresses 47
Address 81 Type Codes 48
Language 82 Module, SLC
LCM Download Menu 82 Control 46
LCM Local Mode, See Local mode 22 Custom action message 45
Local control 21 Local mode 47
Local mode 22, 40, 45, 47 Silenceable 46
Local Receive mode 21 Switch inhibit 46
Local Settings 23 Walk test 46
Logic equations, editing 52 Zone map 46
Logic Zone 52, 125 Extended label 44

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 149


N–P Index

FlashScan Code label 44 Standard 864. 94


Label 44 Clearing all programs is not necessary
Module Type (Control/Monitor) 44 when...(VeriFire) 18
Monitor 45 Deleting points that are active or in trou-
Alarm verification 45 ble... 57
Local control 45 Do not include ZF8 in the zone map of Pan-
Zone map 45 el Circuits used for....(releasing,
Type Codes 44 zone coding) 114
Monitor Module, see Module, SLC or Panel Cir- If the point is not installed...(saving entries)
cuit 44
Multiple Event List 15 No program menus will display if a user
Multiple Events List screen password...(Alter status level) 17
order of events 21 The IZM-8RK module does not participate
in Walk Test... 50
N The panel setting LCM LOCAL MODE
must be set to Yes... 40, 45
NAC (Notification Appliance Circuit) 144
The second shot switch can only be
Navigating Menu and Programming Screens 11 used...(MAN REL DELAY) 104
NBG-12LRA 90, 100, 101, 102, 104
This soft key will not appear for modules
Network Parameters 19 with Type ID...(silence option)
Channel threshold 19 50
Node This value may not exceed 30 seconds for
Label 19 ULC... 24
Number, range 19 This value may not exceed 30 seconds for
Standalone 19 ULC.... 24
To view 19 This value must be 20 minutes for ULC...
Wiring style 19 25
NFPA Standards for Releasing Applications 90 To change the language of the remote dis-
NFS-3030 play 32
Displayless Mode 10
When changing from an 80-column or 80-
Two basic configurations 10 column supervised... 30
Node label 19 When the ACCEPT soft key is pressed to
Node number 19 save an equation... 53
For standalone panel 19 NYC Abort Switch 94
Range 19
To view 19
Non-fire activations O
Event logging 36 Obscuration 144
Non-latching 144 Occupancy Schedule 31, 42
Note Holidays 36
120 seconds is the maximum delay af- Output activations
ter...(NYC timer) 94 Event logging 36
A module with a releasing Type ID cannot Output circuit 144
be forced off. 77 Overwrite (logic equation screen) 53
A printout of all the messages.... (Custom
Action messages) 35 P
A releasing circuit with this Type Code re-
quires...(REL END BELL) 105 Panel Circuit 144
A setting of NO (disable) will disable key- See Module, Panel Circuit
switch operation. 21 See Point Program
Panel circuit modules are not suitable for... 99
A ULC Release circuit with this Type Code
requires...(REL CKT ULC) 106 Panel programming, see Programming, Panel set-
tings
All events except troubles are annunciated
Panel settings 21
during programming... 17
AC Fail Delay 24
An AHJ timer does not comply with UL
Standard 864. 96 Alarm Verification timer 24
Auto Silence 25
An NYC timer does not comply with UL
Auxiliary trouble reporting 30
150 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007
Index R–R

Custom Action message 35 Poll types 34


Default Settings 23 Position 10 in zone map 39
Default Timers 25 Position 9 in zone map 39
Display Address 22 Position one in zone map 38, 45, 46
Event logging 36 Power-up Screen 80
Event Ordering 21 Pre-Alarm 118
Holiday menu 36 Action Level 119
Local Control 21 Alert Level 118
Local mode 22 See also Alarm Sensitivity 117
Local Receive mode 21 Self-optimizing 117
Loop configuration 33 Sensitivity Levels 117
Loop programming 34 To select sensitivity 119
Maximum verification count 24 Prealarm (Action), fixed position zone 39
Panel circuit bell coding 22 Presignal delay 25
PAS 25 Presignal Delay Timer/PAS 113
Password 31 Primary zone 38, 97, 144
Piezo 21 Printer Functions 16
Poll types 34 Printer supervision 30
Presignal delay 25 Program Time/Date 75
Proprietary Supervising Station 21 Program/Alter Status 16
Reminder Menu 22, 23 Programming
Remote Display Menu 32 ACS 26
Silence Inhibit 24 Alter Status 65–77
Supervision 30 Autoprogram 58
Main power supply address 30 Delete program 56
Printer 30 Detector point 38–42
Tamper input 30 First time, Delete Program Menu 18
Timers 23 LCD screen 26
Trouble reminder 23 Module point 43–50
Verify-Prealarm 25 Control 46, 50
Weekly occupancy schedule 31 Monitor 44, 49
Panel sounder 144 See also Module
Panel Timers 24 Panel 18–37
PAS (Positive Alarm Sequence) 113 See also Panel settings
Inhibit switch 113 Point 37–63
Setting 25 See also Point Program
Password 12, 31 Presence of unacknowledged alarm 11
Factory default settings 12 See also Point Program, Panel settings
Incorrect or forgotten 14 Two levels
Master 12 Alter Status 17
User 12, 13 Program 17
Level of access 13 Zones 51–56
Piezo 21 Proprietary Supervising Station 21
Point 144
Selection for programming 37 R
Point Program 37
Rapid poll 34
Autoprogram 58
Read Status 16
Delete Point 57
Receiving Station, see this panel’s installation
Detector point 38
manual. 21
See also Detector
Disable/Enable Point 65 Release Audible Circuit
Output module configuration example
Module Point, SLC 43
See also Module, SLC 109
Panel Circuit Module Point 47 To program 109
See also Module, Panel Circuit Release Circuit
Point select 37 Output module configuration example
Zones 51–56 107

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 151


S–V Index

To program 107 Smoothing 115


Release Code Bell Circuit Soak Time 89
Configuration example 111 Special Zone F0, notes and restrictions 113
To program 111 Special Zone Outputs 113–114
Release End Bell Circuit Special Zones 125
Output module configuration example STS-1 tamper switch 30
105 Supervision 30
To program 105 Supplemental Documentation 10
Release Form-C Circuit Switch Inhibit 46, 50, 144
Output module configuration example Switches, service level, displayless mode 10
108 System Troubles 139
To program 108
Releasing Applications 89–112 T
Abort Switch 89
Tamper input 30
ACS Annunciation 112
Temporal coding 22, 114
Auxiliary Control Functions 112
Threshold, Channel A & B 19
Cross Zones 89
Time control, special zones 113
Types 97
Time-based functions 55
Delay Time 89
Initiating Devices 112 Equations 127
Soak Time 89 Timers 24
Switches & Circuits, programming & con- TM-4 24, 27, 114
figuration 100–111 Trouble bus cable, for auxiliary trouble reporting
Warning sounders 112 30
Releasing Zones (R0-R9) 125 Trouble Equations 129
Type codes for inputs/outputs 98 Trouble Zone 55, 125
Reminder Menu Screen 23 Trouble, Point - see this panel’s Operations man-
ual
Remote Display Menu 32
Trouble, System 139
Reset 144
AKS-1 30 Type Codes 44, 48, 145
Local control 21 Explanation 133
For Intelligent Detectors 134
For Monitor Modules 135
S For releasing zone inputs/outputs 98
Scrolling 11 For SLC & panel circuit output modules
Second Shot Switch 136
Monitor module configuration example See also Point Program 38
104 To select 133
To program 104
Self Test 80 U
Self-Optimizing Pre-Alarm 117
Sensitivity, see Alarm Sensitivity Levels, Detec- UDACT 24, 27
tor UL Standard 864 92, 93, 94, 96
Service Screens 79 ULC Release Circuit
Output module configuration example
Application Corrupt Screen 83
Download screen 83 106
LCM Download Menu 82 To program 106
Power-up screen 80 ULC, auto silence value 25
Version Information 79 ULI Abort Switch 92
Signal Silence User password, see Password 13
AKS-1 30 UZC Zone Coder 27
Disabling with Silence Inhibit timer 24
Local control 21 V
Silence Inhibit Timer 24, 144 VeriFire™ Tools Program Utility 145
Silenceable 46, 50 Use with displayless mode 10
SLC (Signaling Line Circuit) 144 Verify-Prealarm 25
Smoke Control devices 27 Version Information 79

152 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Index W–Z

W Delay Time 52
Soak Time 52
Walk Test 46, 50, 70–75, 145
Special Zones 125
Advanced
Audible 71 Trouble 55
Z000 general alarm 46, 50, 119, 125
Basic 71
See also Alter Status 70
Type IDs, modules, that do not participate
46
Warning
Do not rely on Disable to disable releasing
points during.... 66, 89
If you replace any detector with a different
type... 131
The IRI abort switch will only work if it is
pushed before.... 93
When using alarm verification, do not mix
....(IZM-8RK) 47
Warning Sounders, releasing applications 112
Weekly occupancy schedules 31, 40, 42
Wiring Style 34
wiring style, network 19

X
XPIQ power supply 24

Z
Z000 general alarm 118
Zone map
Control module 46, 50
Detector 38, 39
Monitor module 45, 49
Zones
CBE 125
Fixed positions in map
Detectors, position one 39
Detectors, position ten 39
primary zone 38, 97
Sounder/relay bases, position nine 39
General Zone 51
Zone label 51
Logic 52
Add logic function 53
Add point 53
Add Time/Date 53
Delete equation 53
Edit Equation 52
Enter time 55
Logic function 55
Point select 54
Position layout 38, 39
Position one, initial programming 38, 45,
46
Releasing 51, 89–112
Abort Switch 52
Cross Zone 52

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 153


Z–Z Index

154 NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007


Limited Warranty

NOTIFIER® warrants products manufactured by it to be free from


defects in materials and workmanship for eighteen (18) months from
the date of manufacture, under normal use and service. Products are
date stamped at time of manufacture. The sole and exclusive
obligation of NOTIFIER® is to repair or replace, at its option, free of
charge for parts and labor, any part that is defective in materials or
workmanship under normal use and service. All returns for credit are
subject to inspection and testing at the factory before actual
determination is made to allow credit. NOTIFIER® does not warrant
products not manufactured by it, but assigns to the purchaser any
warranty extended by the manufacturer of such products. This
warranty is void if the product is altered or repaired by anyone other
than NOTIFIER® or as expressly authorized by NOTIFIER® in
writing, or is serviced by anyone other than NOTIFIER® or its
authorized distributors. This warranty is also void if there is a failure to
maintain the products and systems in which they operate in a proper
and workable manner. In case of defect, secure a Return Material
Authorization form from our Return Authorization Department.
This writing constitutes the only warranty made by NOTIFIER®, with
respect to its products. NOTIFIER®, does not represent that its
products will prevent any loss by fire or otherwise, or that its products
will in all cases provide the protection for which they are installed or
intended. Buyer acknowledges that NOTIFIER®, is not an insurer
and assumes no risk for loss or damages or the cost of any
inconvenience, transportation damage, misuse, abuse, accident or
similar incident.
NOTIFIER® GIVES NO WARRANTY, EXPRESS OR IMPLIED, OF
MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE,
OR OTHERWISE WHICH EXTENDS BEYOND THE DESCRIPTION
ON THE FACE HEREOF. UNDER NO CIRCUMSTANCES SHALL
NOTIFIER® BE LIABLE FOR ANY LOSS OF OR DAMAGE TO
PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL,
ARISING OUT OF THE USE OF, OR INABILITY TO USE
NOTIFIER®’S PRODUCTS. FURTHERMORE, NOTIFIER® SHALL
NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH
MAY ARISE IN THE COURSE OF, OR AS A RESULT OF,
PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS
PRODUCTS.
This warranty replaces all previous warranties and is the only
warranty made by NOTIFIER®. No increase or alteration, written or
verbal, of the obligation of this warranty is authorized.
"NOTIFIER" is a registered trademark.
Warn-NL-04-2005.fm

NFS-3030 Programming Manual — P/N 51345:D1 1/22/2007 155


World Headquarters
12 Clintonville Road
Northford, CT 06472-1610 USA
203-484-7161
fax 203-484-7118

www.notifier.com

You might also like