NFS-3030-E Operations Manual
NFS-3030-E Operations Manual
NFS-3030-E Operations Manual
NFS-3030
Programming Manual
Document 51345
1/22/2007
P/N 51345:D1
Rev: D1
ECN 06-481
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of Heat detectors do not sense particles of combustion and
smoke detectors, heat detectors, manual pull stations, audible alarm only when heat on their sensors increases at a predeter-
warning devices, and a fire alarm control panel with remote mined rate or reaches a predetermined level. Rate-of-rise
notification capability—can provide early warning of a develop- heat detectors may be subject to reduced sensitivity over time.
ing fire. Such a system, however, does not assure protection For this reason, the rate-of-rise feature of each detector
against property damage or loss of life resulting from a fire. should be tested at least once per year by a qualified fire pro-
The Manufacturer recommends that smoke and/or heat detec- tection specialist. Heat detectors are designed to protect
tors be located throughout a protected premise following the property, not life.
recommendations of the current edition of the National Fire IMPORTANT! Smoke detectors must be installed in the
Protection Association Standard 72 (NFPA 72), manufacturer's same room as the control panel and in rooms used by the sys-
recommendations, State and local codes, and the recommen- tem for the connection of alarm transmission wiring, communi-
dations contained in the Guide for Proper Use of System cations, signaling, and/or power. If detectors are not so
Smoke Detectors, which is made available at no charge to all located, a developing fire may damage the alarm system, crip-
installing dealers. A study by the Federal Emergency Man- pling its ability to report a fire.
agement Agency (an agency of the United States government) Audible warning devices such as bells may not alert people
indicated that smoke detectors may not go off in as many as if these devices are located on the other side of closed or
35% of all fires. While fire alarm systems are designed to pro- partly open doors or are located on another floor of a building.
vide early warning against fire, they do not guarantee warning Any warning device may fail to alert people with a disability or
or protection against fire. A fire alarm system may not provide those who have recently consumed drugs, alcohol or medica-
timely or adequate warning, or simply may not function, for a tion. Please note that:
variety of reasons:
• Strobes can, under certain circumstances, cause seizures
Smoke detectors may not sense fire where smoke cannot in people with conditions such as epilepsy.
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors • Studies have shown that certain people, even when they
also may not sense a fire on another level or floor of a building. hear a fire alarm signal, do not respond or comprehend the
A second-floor detector, for example, may not sense a first- meaning of the signal. It is the property owner's responsi-
floor or basement fire. bility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
Particles of combustion or “smoke” from a developing fire on the proper reaction to alarm signals.
may not reach the sensing chambers of smoke detectors
because: • In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow. A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
• Smoke particles may become “cold,” stratify, and not reach batteries only for a specified time and only if the batteries have
the ceiling or upper walls where detectors are located. been properly maintained and replaced regularly.
• Smoke particles may be blown away from detectors by air Equipment used in the system may not be technically com-
outlets. patible with the control panel. It is essential to use only equip-
• Smoke particles may be drawn into air returns before ment listed for service with your control panel.
reaching the detector. Telephone lines needed to transmit alarm signals from a
The amount of “smoke” present may be insufficient to alarm premise to a central monitoring station may be out of service
smoke detectors. Smoke detectors are designed to alarm at or temporarily disabled. For added protection against tele-
various levels of smoke density. If such density levels are not phone line failure, backup radio transmission systems are rec-
created by a developing fire at the location of detectors, the ommended.
detectors will not go into alarm. The most common cause of fire alarm malfunction is inade-
Smoke detectors, even when working properly, have sensing quate maintenance. To keep the entire fire alarm system in
limitations. Detectors that have photoelectronic sensing excellent working order, ongoing maintenance is required per
chambers tend to detect smoldering fires better than flaming the manufacturer's recommendations, and UL and NFPA stan-
fires, which have little visible smoke. Detectors that have ion- dards. At a minimum, the requirements of NFPA 72 shall be
izing-type sensing chambers tend to detect fast-flaming fires followed. Environments with large amounts of dust, dirt or
better than smoldering fires. Because fires develop in different high air velocity require more frequent maintenance. A main-
ways and are often unpredictable in their growth, neither type tenance agreement should be arranged through the local man-
of detector is necessarily best and a given type of detector ufacturer's representative. Maintenance should be scheduled
may not provide adequate warning of a fire. monthly or as required by National and/or local fire codes and
Smoke detectors cannot be expected to provide adequate should be performed by authorized professional fire alarm
warning of fires caused by arson, children playing with installers only. Adequate written records of all inspections
matches (especially in bedrooms), smoking in bed, and violent should be kept.
explosions (caused by escaping gas, improper storage of
flammable materials, etc.). Limit-C-9-2005
This system meets NFPA requirements for operation at 0-49º This system contains static-sensitive components.
C/32-120º F and at a relative humidity (non condensing) of Always ground yourself with a proper wrist strap before han-
85% at 30°C (86°F) per NFPA, and 93% ± 2% at 32°C ± 2°C dling any circuits so that static charges are removed from the
(89.6°F ± 1.1°F) per ULC. However, the useful life of the sys- body. Use static suppressive packaging to protect electronic
tem's standby batteries and the electronic components may be assemblies removed from the unit.
adversely affected by extreme temperature ranges and humid- Follow the instructions in the installation, operating, and pro-
ity. Therefore, it is recommended that this system and its gramming manuals. These instructions must be followed to
peripherals be installed in an environment with a normal room avoid damage to the control panel and associated equipment.
temperature of 15-27º C/60-80º F. FACP operation and reliability depend upon proper installation.
Verify that wire sizes are adequate for all initiating and indi- Precau-D1-9-2005
cating device loops. Most devices cannot tolerate more than a
10% I.R. drop from the specified device voltage.
FCC Warning
WARNING: This equipment generates, uses, and can Canadian Requirements
radiate radio frequency energy and if not installed and This digital apparatus does not exceed the Class A limits
used in accordance with the instruction manual may for radiation noise emissions from digital apparatus set
cause interference to radio communications. It has been out in the Radio Interference Regulations of the Cana-
tested and found to comply with the limits for class A dian Department of Communications.
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable Le present appareil numerique n'emet pas de bruits radi-
protection against such interference when devices are oelectriques depassant les limites applicables aux appa-
operated in a commercial environment. Operation of this reils numeriques de la classe A prescrites dans le
equipment in a residential area is likely to cause interfer- Reglement sur le brouillage radioelectrique edicte par le
ence, in which case the user will be required to correct ministere des Communications du Canada.
the interference at his or her own expense.
Acclimate Plus™, HARSH™, NIS™, Notifier Integrated Systems™, NOTI•FIRE•NET™, and ONYXWorks™ are all trademarks; and FlashScan®, NION®,
NOTIFIER®, ONYX®, UniNet®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. Echelon® is a registered trademark and
LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are
registered trademarks of the Microsoft Corporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary of General Electric Company.
©Thursday, January 25, 2007 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
WARNING: Information about procedures that could cause irreversible damage to the
! control panel, irreversible loss of programming data or personal injury.
CAUTION: Information about procedures that could cause programming errors, runtime
! errors, or equipment damage.
NOTE: Information that highlights an important part of the preceding or subsequent text or
illustration.
1.3.1 Features
Programming features include the following:
• Ease of use - Field program the control panel without special software skills.
• Local programming - program directly from the control panel keypad to reduce installation
time.
• PC programming - input long data entry programming information on a PC; transfer
programming data between a PC and the control panel.
• Autoprogram option - automatically detect newly installed, addressable devices, allowing
quicker installation.
• Security - use passwords to control access to the control panel and protect programming.
• Large display option - 640 character screen, 16 lines x 40 characters
CHANGE PASSWORD
MASTER PASSWORD
USER PASSWORD
BACK
Soft Keys
MASTER PASSWORD - Press to change the master password
USER PASSWORD - Press to change the user password.
Master Password
Press the MASTER PASSWORD Soft Key to display the following screen. Type in the new password
that will replace the factory default password: there can be up to eight alphanumeric characters.
Press the enter key on the keyboard. RE-ENTER PASSWORD will appear. Retype the password for
verification. Press enter to save the new password.
BACK
User Password
Press the USER PASSWORD soft key to display the following screen.
USER:1 REFERENCE:JOHN
BACK
Soft Keys
USER: Press this soft key to scroll through the nine user password numbers. When this key is
pressed, the rest of the display will update to reflect information for each new record. Stop at the
password number that requires entering.
MODE: Press this soft key to select the user’s level of access. Levels are as follows:
• PROGRAM/ALTER STATUS Gives access to the Program Change Menu and Alter Status
Menu.
• ALTER STATUS Gives access to the Alter Status Menu
• NONE Gives no access.
REFERENCE: Press this key to enter a maximum 20-character alphanumeric label that identifies the
user. Press the enter key on the display/keyboard to enter the information.
ENTER PASSWORD - Press to enter a new password. Type in up to eight alphanumerics on the
keyboard, then press enter. RE-ENTER PASSWORD will appear. Retype the password for
verification.
ACCEPT: After entering all password information and retyping the password at the prompt, press this
soft key to save all the password information.
Incorrect or Forgotten Password
If a password is entered incorrectly, the panel will respond by displaying an INVALID
PASSWORD message and a code. The programmer may hit the escape key and re-enter the
password correctly. However, if the password has been forgotten, record the code and contact
NOTIFIER. After proper authentication, the master password can be determined by deciphering the
code. An example of the message that would appear on the display follows:
INVALID PASSWORD:
9066-21FS-7D78-5FA4-6163
Code
PROGRAM/ALTER STATUS
Soft Keys
Pressing the soft keys brings the user to the screens described below.
NOTE: All events except troubles are annunciated during programming. When an annunciated
event occurs, the panel will automatically exit the programming screen and the Event Counts
menu screen will appear.
To access the Program level, press the Program/Alter Status soft key on the Main Menu and at the
prompt enter a master password, or a user password that allows access to the Program level. The
following screen will display.
NOTE: No program menus will display if a user password is entered that has access to Alter
Status level only: the Alter Status menu will be the sole menu choice
AUTOPROGRAM MENU
Press a soft key with the word “program” in its menu to bring up the associated program menu.
When programming the panel for the first time, press the DELETE PROGRAM MENU soft key,
which brings up the Delete Program Menu screen (Refer to Figure 3.46). Press the CLEAR ALL
PROGRAMMING button, then ACCEPT, to ensure that the panel is set to defaults and clear of
programs.
NOTE: Clearing all programs is not necessary when initial programming with a database
downloaded from VeriFire™.
The logical sequence for initial programming is to program the panel parameters first, then to
program the individual points through autoprogramming and/or point programming.
ACS PROGRAMMING
BACK
NETWORK PROGRAMMING
NODE LABEL:
LAKEVIEW GENERAL HOSPITAL
Soft Keys
NODE NUMBER: Enter the network node number of this panel. For standalone NFS-3030, the
network node number will be 000. A valid network node number range is 1-240. Once the soft key
has been pressed, the number may be typed in from the keypad, or the Next/Previous Selection
special function key on the keypad may be used to toggle through online node numbers. The
network node number may be viewed by pressing the Lamp Test special function key longer than
five seconds. (Refer to “Version Information” on page 79 ). Default: 000
NODE LABEL: Enter the network node label for this panel. This is the label that appears in the
System Normal message. Default: <blank>
STYLE: Select the wiring style as 4 or 7. Default: style 4
CHANNEL A THRESHOLD, CHANNEL B THRESHOLD: Enter HIGH or LOW, for high or low
threshold setting for channel A or B on the NCM module. Default: HIGH
IP ACCESS: Press this soft key to bring up the IP ACCESS screen.
ACCEPT: Press this soft key to save the information entered on this screen.
IP ACCESS Screen
NOTE: Use of the IP ACCESS feature is subject to the approval of the local AHJ.
This screen allows the programmer to set the IP Access. This setting allows the disabling/enabling
of commands, downloads and programming from the Wide Area Network (WAN).
IP ACCESS
IP ACCESS: ON
ACCEPT
BACK
NOTE: Enabling IP ACCESS allows downloads over a local area network (LAN) or the internet
(Wide Area Network - WAN) using VeriFire Tools through a Noti•Fire•Net™ Web Server (NWS),
or a wide-area enabled NCS through a PC version of Noti•Fire•Net™ Gateway.
Always verify system operation after programming changes are made in this manner.
PANEL SETTINGS
PIEZO: ON MORE
Soft Keys
LOCAL CONTROL: Press this soft key to toggle between Yes and No. This option disables (No) or
enables (Yes) local panel control of the Signal Silence, System Reset, and Drill Fixed Function
keys, as well as SIGNAL SILENCE, SYSTEM RESET, and ACKNOWLEDGE soft keys. A setting of
No (disable) turns the panel piezo sounder off, overriding the next field if PIEZO is set to ON.
Default: Yes
NOTE: ACS devices programmed for acknowledge, signal silence, system reset and drill are not
affectted by this setting: these commands will still function at the devices if LOCAL CONTROL is set to
No.
PIEZO:Press this soft key to toggle between Off and On. This option enables (On) or disables
(Off) the panel piezo from sounding when alarms or troubles occur. A setting of On is overridden if
LOCAL CONTROL is set to No. Default: On
PROPRIETARY SUPERVISING STATION:Press this soft key to enable (Yes) or disable (No)
Local Receive mode. When enabled, events and the clearing of events must be handled one at a
time: each must be acknowledged. Latching events require a system reset. The panel will override a
setting of Yes if the Node Number is greater than zero. Default: No
EVENT ORDERING: Press this soft key to toggle between USA and Canada ordering priorities.
This order is applied to events shown in the Multiple Events List screen. Default: USA
USA Event Order Canada Event Order
Fire Fire
Security Supervisory
Supervisory Trouble
Trouble Prealarm
Prealarm Disabled
Disabled
DISPLAY ADDRESS: Press this soft key to toggle between Yes and No. Choose Yes to display all
point address information at the top of event screens and in printouts. Choose No to suppress
address information display and printing. Default: Yes
REMINDER MENU: Press this soft key to bring up the Reminder Menu screen.
ACCEPT: Press this soft key to save the information entered on this screen.
MORE: Press this key to progress to the second Panel Settings screen.
PANEL SETTINGS
DCC PARTICIPATION: NO
Soft Keys
LCM LOCAL MODE: Press this soft key to toggle between Yes and No. Enter Yes to enable all SLCs
to participate in local mode. When enabled, all LCMs will operate together in a limited fashion
when communication is lost with the NFS-3030 CPU. Inputs on LCM loops (and associated LEM
loops, if installed) will activate outputs on all loops
• for those inputs and outputs that have been set with point programming to participate in local
mode, and
• when type codes are the same point type: that is, an input with a fire type code will activate
an output with a fire type code.(Refer to Appendix G, “Type Codes”, on page 133 for point
types).
Default: NO
PANEL CIRCUIT BELL CODING: Press to toggle between MARCH and TEMPORAL. This is a
global setting: ZF8 must be entered in the zone map of any panel circuit point that will participate
in this coding. Refer to “Coding Functions for Panel Circuit Outputs” on page 114 for more
information. Default: MARCH
DCC PARTICIPATION: Press this key to program the panel for DCC (Display and Control Center)
participation. This network function ensures that one location at a time is in command of the
Acknowledge, System Reset, Signal Silence and Drill functions. Default: NO
CAUTION:
! On systems utilizing the DCC function, all locations that can participate in DCC should be set to
YES.
LOCAL SETTINGS:Press this soft key to proceed to the Local Settings screen. Press the soft key
to scroll through the selections. The default is that there are no special local settings. Other settings
are explained in Appendix I, “Local Settings”.
DEFAULT SETTINGS: Press this soft key to activate default settings for the following:
Program setting for: Default:
Local Control Yes
Piezo On
Proprietary Supervising No
Station
Event Ordering USA
Display Address Yes
LCM Local Mode No
Panel Circuit Bell Coding March
DCC Participation No
Reminder Menu
Press the Reminder Menu soft key on the Panel Program Menu 1 screen to set the trouble reminder.
REMINDER MENU
ACCEPT
BACK
Soft Keys
TROUBLE REMINDER: Press this soft key to toggle between the two possibilities:
YES: Choose this to initiate a daily 11:00AM reminder that there are uncleared troubles in the
system. The reminder will appear on the screen and will sound a piezo (if the piezo is enabled).
NO: Choose this if no reminder is desired. Default: YES
ACCEPT: Press this soft key to save the information entered on this screen.
PANEL TIMERS
Soft Keys
VERIFY TIME: Press this soft key to set the Alarm Verification timer. Type in a value of 0-60
(seconds), which will delay initiating devices set for Alarm Verification from signaling for the
amount of time entered. If a second alarm occurs while the alarm verification timer is counting, the
timer will stop and the alarm will signal immediately. Default: 30
NOTE: This value may not exceed 30 seconds for ULC installations.
MAXIMUM VERIFICATION COUNT: Press and enter a value from 0-20 for a maximum
verification count threshold value that applies to detectors set to participate in Alarm Verification.
A value of zero produces no verification trouble. When the counter exceeds the threshold value
entered, a trouble is generated to the panel. Default: 20
AC FAIL DELAY: Press this soft key to set the timing for the time delay from AC Failure to when
the trouble is reported. Type in a value of 6-12 (hours), or 0 (zero). A value of zero will cause
immediate notification. Default: 8
The onboard trouble relay ( TB3 on the CPU-3030 ) will activate and TM-4s will report according
to this setting.
UDACTs are notified immediately of AC failure by the panel, regardless of the panel’s delay
setting. Once the UDACT receives notification, it operates according to its own programmed AC
Fail Delay reporting schedule.
Example: AC Failure occurs at 1:00 p.m. on a panel with an AC FAIL DELAY setting of 8
hours. The UDACT is set for notification after 6 hours.
Time Event
1:00 p.m. AC Failure. Panel notifies UDACT. Panel and UDACT timers begin countdown to
report time.
7:00 p.m. UDACT reports.
9:00 p.m. TM-4 reports, TB3 trouble relay activates.
The AMPS-24, ACPS-2406, and XPIQ power supplies must be set to an AC Delay value of 0
(zero) when used with this panel.
SILENCE INHIBIT: Press to enter a value from 0 (disabled) to 5 minutes. This software timer
disables the SIGNAL SILENCE key function for the time entered when a fire alarm occurs. The
timer starts at the first alarm only; it does not restart with each new alarm. Default: 0
AUTO SILENCE: Press to enter a value of OFF (no Auto Silence Timer), or a value of 10, 15 or 20
minutes. This global software timer functions like pressing the SIGNAL SILENCE key. For
example, if a value of 10 is entered, the control panel will silence all active outputs programmed as
silenceable after ten minutes. Default: 0FF
VERIFY=PREALARM: Press this soft key to enter Yes or No for displaying Prealarm during alarm
verification. Default: NO
PANEL TIMERS
PAS: OFF
DEFAULT TIMERS
ACCEPT
BACK
Soft Keys
PAS: Press to toggle between the choices of OFF or ON for PAS (Positive Alarm Sequence). Refer
to Appendix C, “Special Zone Outputs” for an explanation of this option. Default: OFF
PRESIGNAL DELAY: Press to enter a value of 00:00 (OFF) or a value of 1:00 to 3:00 minutes (in
the format MM:SS, where MM= minutes, SS=seconds). This feature initially causes alarm signals
to sound only in specific areas, monitored by qualified personnel. This allows delay of the alarm for
up to 3 minutes after the start of alarm processing. Refer to Appendix C, “Special Zone Outputs”
for further explanation of this option. Default: 3:00
DEFAULT TIMERS: Press this soft key to activate default settings for the following:
Program setting for: Default:
Verify Time 30 seconds
Max. Verify 20
AC Fail Delay 8 hours
SIlence Inhibit 0 (disabled)
Auto Silence Off
Verify=Prealarm No
PAS OFF
Presignal Delay 3 minutes
ACCEPT: Press this soft key to save the information entered on this screen and return to the
previous screen.
LCD PROGRAMMING
BRIGHTER DEFAULT
DARKER CURRENT
Soft Keys
BRIGHTER: Press this soft key to increase contrast. The intensity will increase by approximately
5% with each press of the key.
DARKER: Press this soft key to decrease contrast. The intensity will decrease by approximately
5% with each press of the key.
LANGUAGE: Press this soft to choose the language that will display on the LCD. Menu choices are
ENGLISH, HEBREW, PORTUGUESE and SPANISH.
To change the language display on an LCD-160, refer to “LCD-160 Download Menu” on page 81.
BACKLIGHT: Press this soft key to select one of the following backlighting options: ON EXCEPT
AC FAIL, OFF, or ON. When ON EXCEPT AC FAIL is selected, the backlight will turn off when
the power supply designated as the main power supply experiences AC failure. (The designation is
made at the Supervision screen using the MAIN POWER SUPPLY AC FAIL ADDRESS field. Refer
to “Supervision” on page 30.)
Default: ON
DEFAULT: Press to select the factory default setting (60%).
CURRENT:Press to select the intensity that was in effect when the screen was accessed..
ACCEPT: Line 5 (which displays LCD INTENSITY: 50% in the figure above) will change
value when the INTENSITY soft keys are pressed. Press ACCEPT to save the desired setting.
NOTE: Smoke Control devices must be set as FSCS or HVAC annunciator types. In addition to
its 64 smoke control points, when an SCS device is operating in FSCS (Firefighters Smoke
Control Station) mode, there are 32 additional points which function as alarm points. They can be
mapped to a zone or point to send the SCS device into a fire alarm state when any of the
additional 32 points is activated. Any of the 32 alarm points that are used must be set to
MONITOR mode from the panel. Any of these points that are not used can be set to NONE. Refer
to the SCS manual for further information on Smoke Control devices.
NOTE: When using an AMG, the address it occupies (an address of 25 through 32, typically
address 32 ) must be set to annunciator type AMG, and address one must be set to annunciator
type 64PT.
UDACT and TM-4 communicators, as well as the UZC Zone Coder, are installed on the same
EIA-485 ACS circuit as annunciators, and so are included with annunciator programming. The
TM-4 occupies one of the 32 annunciator addresses, and the UDACT can occupy one or more of
these addresses. The UZC can occupy up to four annunciator addresses, each with 64 points. When
the UDACT or UZC expand beyond one annunciator address, 64PT should be used for the
subsequent address types, and the annunciator addresses should be sequential. Other than address
assignment, there is no ACS point programming for these devices. Refer to the specific device
manual for more information.
Press the ACS Programming soft key at the Panel Program screen to invoke the following screen.
Press the up and down arrow keys on the keypad to navigate through the annunciator addresses.
There will be a cursor highlighted at the current annunciator address position.
ACS PROGRAMMING
Soft Keys
ANNUNCIATOR TYPE: When the cursor is placed at the desired address, press this soft key to
scroll through the following list of types. Stop at the appropriate type.
TM4 TM-4
AMG AMG
FSCS Smoke control modules set for FSCS mode
HVAC Smoke control modules set for HVAC mode
UZC Universal Zone Coder, first address. Any additional
UZC annunciator addresses should be programmed
as 64PT and be sequential.
POINT PROGRAMMING: Press this soft key to proceed to the ACS Point Programming screen.
ACCEPT: Press this soft key to save all the changes made and return to the previous screen (Panel
Program).
ACS Point Programming
ACS Point Programming can be reached by pressing POINT PROGRAMMING at the ACS
Programming screen. This screen allows the programmer to assign a mode and sources to each
annunciator point at the annunciator address. One ACS input may be used to control multiple panel
circuit or SLC output modules by listing the output points in the SOURCE fields. This feature
applies to the following Types: 64PT, 64SYS, 96PT, and 96SYS.
NOTE: Panel circuit or SLC output modules with releasing Type IDs may not be listed in the
annunciator source fields.
NOTE: This FACP supports ACM-24AT/ACM-48A annunciators and their expanders with either
64 or 96 points at an address, as well as ACM-16AT/ACM-32A/LDM-32 annunciators with 64
points at an address.
POINT: A27P04
MODE: CONTROL
NEXT ACCEPT
PREVIOUS BACK
Soft Keys
POINT: Press this soft key to enter the ACS point number. The format is AxxPyy, where A is the
two-digit device address, P is the two-digit point number. Enter a leading zero for one-digit
numbers.
MODE: Press this soft key to enter the ACS mapping mode. Refer to the following chart for
possible mode choices and descriptions of their functions.
None is not programmed. No messages are sent from or received at this point. LEDs at this
point do not light.
Control will change the state of up to eight panel The Point Active LED is lit if a corresponding mapped point is
circuits or control modules to off or on active. The Status (trouble) LED is on when a point or zone is
when its button is pushed. disabled or in trouble.
This mode is not for use with an ACS point with no switch, or with
a TM-4 or UDACT.
Monitor will show the current status of a specified The Point Active LED is lit if the corresponding mapped point or
point or zone. zone is active. The Status (trouble) LED is on if that point or zone
is disabled or in trouble. If the point has a button, it has no effect
when pushed.
Telephone supports telephone functionality when Both the Point Active LED and the Status (trouble) LED will flash
mapped to a telephone point. Press the if a telephone has been placed in the jack at the mapped
button to connect the mapped point with telephone point. Otherwise, the Point Active LED is lit if the
the telephone station. corresponding point or zone is active. The Status (trouble) LED is
lit if that point or zone is in trouble or disabled.
This mode is for use with ACS Series annunciator points
configured for telephone operation.
Disable will change the state of a point or zone The Point Active LED is lit if the corresponding mapped point or
specified through mapping from enabled zone is active. The Status (trouble) LED is lit if that point or zone
to disabled, or from disabled to enabled, is disabled or in trouble.
when its button is pushed. This mode is not for use with an ACS point with no switch, or with
See Caution below this table. a TM-4, UDACT, or smoke control device.
Acknowledge will act like an Acknowledge soft key or The Point Active LED is lit when there are any fire alarms in the
button on the panel, acknowledging an system. The Status (trouble) LED is lit when there are troubles in
event when its button is pushed. the system.
Silence will act like the Signal Silence button on The Point Active LED is lit if all silenceable outputs have been
the panel, silencing all silenceable silenced. The Status (trouble) LED is lit if not all silenceable
outputs when its button is pushed. outputs have been silenced after the button is pushed.
Reset will act like the System Reset button on No LED will ever light at this point.
the panel, resetting the panel when its This mode is not for use with an ACS point with no switch, or with
button is pushed. a TM-4, UDACT, or smoke control device.
Drill will act like the Drill button on the panel, The Point Active LED lights when the button is pushed and the
initiating a fire drill when its button is system has entered the drill state. The Status (trouble) LED will
pushed. never light.
This mode is not for use with an ACS point with no switch, or with
a TM-4, UDACT, or smoke control device.
CAUTION: When a disabled output is enabled, it will be affected by conditions existing in the
! system that would normally affect it. For example, when a condition exists in the system that would
normally turn the output on, the output will turn on when it is enabled.
SOURCE: Pressing this soft key will select the Source field and also toggle between display
formats if a point value is allowed. Enter a point or zone, or the panel’s node number if the mode
type is a system function such as acknowledge or reset.
Up to eight sources are allowed when CONTROL mode is chosen.
ACCEPT: Press this soft key to save the changes to the point displayed. The next point address will
appear.
BACK: Press this soft key to exit the screen without saving, and return to the ACS Programming
Screen.
3.2.8 Supervision
From the Panel Program Menu (1), select SUPERVISION to display the following screen.
SUPERVISION
PRINTER: 80-COLUMN
Soft Keys
MAIN POWER SUPPLY AC FAIL ADDRESS: Press to enter the “Monitor AC Fail” (base plus
one) address of the main power supply. Refer to the main power supply manual for complete
addressing information. Type in the address using the keypad.
The LCD backlight will turn off when this power supply experiences AC failure (see BACKLIGHT
in “LCD Programming” on page 26).
PRINTER: Press to scroll through the types of printer supervision: NONE, 40-COLUMN,
40-COLUMN SUPERVISED, 80-COLUMN, 80-COLUMN SUPERVISED, 40 GRAPHIC, 80
GRAPHIC, 80 GRAPHIC SUPERVISED. The printer will not be active if NONE is selected. If a
SUPERVISED selection is made, the printer will be supervised. Default: NONE
AUXILIARY TROUBLE REPORTING: Press to toggle between Yes and No. Choose Yes if a
trouble bus cable has been attached at J5 of the CPU-3030. Default: NO
TAMPER INPUT: Press the soft key to toggle between Yes, No, and AKS-1.
Yes/No reports (YES) or does not report (NO) a tamper situation at the panel cabinet door (as
determined by an STS-1 tamper switch connected as shown in this panel’s installation
manual).
AKS-1 should be selected when there is an AKS-1 key switch connected to the panel cabinet
door (which allows the operator to use Signal Silence, Reset, Drill and Acknowledge functions
when a key turns the lock to “Enable”). Default: NO
ACCEPT: Press to save changes and return to previous menu.
LOOP CONFIGURATION
Soft Keys
Press a soft key to bring up the associated menu.
BACK
Use the arrow keys on the keyboard to navigate between occupancy time fields: use the keypad to
type in the time values.
SOFT KEYS
WEEKLY OCCUPANCY SCHEDULE: Press this soft key to toggle between schedules 1 - 10. A
value of zero indicates no schedule.
ACCEPT: Press this to save changes made on the screen.
NOTE: To change the language of the remote display, or to program the panel banner to appear
in the remote display, refer to“LCD-160 Download Menu” on page 81.
Soft Keys
INSTALL REMOTE DISPLAY: To install a remote display, press the arrow keys to place the
cursor on the line next to the remote display address to be installed. Press this soft key until YES
displays. Default:No
POINT PROGRAMMING: Once a display has been installed, press this soft key to program the
display point.
DISPLAY POINT
D01
POINT LABEL
EAST WING HALLWAY
LOCAL CONTROL:YES
Soft Keys
DISPLAY POINT: Press this soft key to bring the cursor to the underlined field. Use the keypad to
type in the desired display address.
POINT LABEL: Press this soft key to bring the cursor to the underlined label field. Type in a label
of up to 40 characters that will appear in trouble messages.
LOCAL CONTROL: Press to toggle between YES and NO. A setting of YES enables local control at
the remote display.
LOOP CONFIGURATION
LOOP SELECTION
Lyy (LOOP)
Soft Keys
POINT SELECT: Pressing this soft key will invoke the cursor at the underlined field. Enter the
loop number desired (01 through 10) in the yy of the Lyy format.
NEXT/PREVIOUS SELECTION: Press either key to go forward or back through the loop
selections.
ACCEPT: Press to proceed to the Loop Point Programming screen.
Loop Point Programming
Soft Keys
INSTALLED: Press this soft key to choose YES or NO, depending on whether an SLC is installed
at this address.
FlashScan and CLIP Mode
FlashScan devices can be programmed to run in either CLIP or FlashScan mode. The types can not
be mixed on a loop: for example, if Loop 1 is programmed with a FlashScan module poll, CLIP
modules may not be used on that loop.
A detector’s LEDs will light a steady green for several seconds while it is subjected to a detector
test during FlashScan polling. Each detector is tested this way on a regular basis. During the short
time the LEDs are on steady, the detector is not providing fire protection.
DETECTOR POLL: Press to select FLASHSCAN or CLIP loop polling.
MODULE POLL: Press to select FLASHSCAN or CLIP loop polling.
RAPID POLL: For CLIP mode only - enable or disable Rapid Poll for CLIP. This feature will poll
the first 20 modules more often to speed response on manual pull stations.
WIRING STYLE: Press to select the NFPA wiring style (4 or 6) of the loop. If Style 6 is entered
when the wiring is Style 4, a trouble message will be generated at the panel.
BLINK MODE: Press to enable (ON) or disable (OFF) detector LED blinking for this loop.
MESSAGE
Edit
Custom
Action
Message here.
ACCEPT
VIEW BACK
CUSTOM ACTION MESSAGE:Enter a number with a value of 001 to 100 to display the
corresponding Custom Action Message, or to add or edit a message.
MESSAGE: Enter/edit a custom message in the four lines indicated. The message may be up to 160
characters.
VIEW: Press this soft key to view the message that corresponds to the number entered in the
underlined field.
ACCEPT: Press to save any change made to the message and return to the previous screen.
NOTE: A printout of all the messages may be obtained by entering the Print Programming Menu
(2) and pressing the CUSTOM ACTION MESSAGES soft key.
EVENT LOGGING
ACCEPT
BACK
Press the appropriate softkey to choose event logging (Yes) and no event logging (No). When Yes
is chosen, the activations are logged into history and printed.
HOLIDAY MENU
MM/DD/YY
01 01/01/**
02 05/30/04
03 07/04/**
04 09/06/04
ANY YEAR 05 12/25/**
The cursor will appear in the date fields, and may be moved using the keyboard arrow keys. Type to
add/edit any holiday dates.
SOFT KEYS
ANY YEAR: Press to place asterisks in the YY section of the field. An asterisk denotes any year.
NEXT/PREVIOUS SELECTION: Press to view the next or previous group of five holidays.
ACCEPT: Press to save changes to the date fields and to return to the Panel Program Menu.
POINT SELECT:
LyyDzzz (DETECTOR)
Soft Keys
POINT SELECT: Press until the desired point type appears. The types - detector, module, panel
circuit module, general zone, logic zone, trouble zone, or ACS Board - appear in the parenthesis
after the point formats. Enter the desired point address in the format field.
ACCEPT: Press to progress to the appropriate screen, based on the type of point selected.
NEXT/PREVIOUS SELECTION: Press to scroll backward or forward to the next or previously
installed point.
POINT LABEL:
MORE
EXTENDED LABEL:
ACCEPT
ZONE MAP:
Z003, Z104, Z105, Z106, Z107,
Z110, Z114, Z115, Z116, Z117 BACK
The point address is displayed in line 3 of this screen. Existing point information is displayed in the
fields.
Soft Keys
TYPE: Press this soft key to scroll through the point type choices: stop at the appropriate selection.
If a new point is being added, no other field will be displayed until TYPE: is entered and the
ACCEPT soft key is pressed . At this point, the rest of the fields will appear.
FLASHSCAN CODE LABEL: Press to scroll through a list of FlashScan Codes. Stop when the
appropriate label appears (Table G.4 on page 137 for codes and descriptions). If the detector is not a
FlashScan type, choose NONE.
POINT LABEL: Press this soft key to place the cursor at this field. Type in a 20-character
maximum point label that will appear in message formats. If no entry is made, the field will default
to the point address.
EXTENDED LABEL: Press to place the cursor at this field. Type in a 12-character maximum
extended label to further define the location or nature of the point.
ZONE MAP: Displays the zones mapped to this point. During initial programming, zone map
position one for each detector is set to Z0YY, where YY represents the loop number where the
detector resides. In Figure 3.24 above, zone position one has a value of Z003 (YY = 03). The
detector in the example resides on loop 3.
To add or delete zones for this point, press this soft key to progress to the Detector Zone Map
screen.
MORE: Press this soft key to progress to the next detector point programming screen.
ACCEPT: Press to accept changes. If the user is adding a point, pressing this soft key after entering
the TYPE field will display all the other fields.
Zone Map
The Detector Zone Map screen will display when the ZONE MAP soft key is pressed at the Detector
Point Programming screen.
Zone Map
Zone Map Position
Position 1 -
Use to link DETECTOR ZONE MAP
zone label 2 L03D123
to detector, ZONE SELECTION
and for 3 Z003, (ZONE)
group zone Z187, (ZONE)
disable. 4 Z234, (ZONE)
ZXXX (UNMAPPED)
5 ZXXX (UNMAPPED)
ZXXX (UNMAPPED)
6 ZXXX (UNMAPPED)
ZXXX (UNMAPPED)
7 ZXXX (UNMAPPED) ACCEPT
ZXXX (UNMAPPED)
8
Zone Map BACK
Position 9 - Use
to activate
FlashScan
sounder/relay-
bases. Zone Map Position 10 - Use for
detectors set to Prealarm, Action.
ACCEPT: Press to save entries made on this screen and return to the Detector Point Programming
screen.
Detector Point Programming (2)
Press the MORE soft key on the Detector Point Programming screen to display this screen.
Soft Keys
CUSTOM ACTION MESSAGE: Displays the custom action message number (a value of one
through 100). The default value is 0 (no message). Press this soft key to progress to the Custom
Action Message screen (Figure 3.27) to view the message or to choose a different message for
viewing when this point activates. (To create a new custom action message, refer to “Custom
Action Message” on page 35.)
ALARM VERIFICATION: Press this key to determine the device’s participation in Alarm
Verification. Choosing Yes will set the device participation to the values entered at the Panel
Timers screen (Figure 3.8).
LOCAL MODE: Press to toggle between Local Mode (ON) or no Local Mode (OFF). When there is
a communication loss between the panel and its LCM/LEMs, SLC devices that have been selected
for Local Mode participation (ON) will continue to function across all the panel’s SLCs in a limited
manner as follows: input points will activate output points of the same Type Code point type
designations. For example, SLC inputs with“fire” point types will activate SLC outputs with“fire”
point types. Refer to Appendix G, “Type Codes”, on page 133 for type code point types. All SLC
detector types can participate in local mode.
NOTE: The panel setting LCM LOCAL MODE must be set to Yes for local mode to work at the
device level.
ACCEPT
VIEW BACK
Soft Keys
CUSTOM ACTION MESSAGE: Enter the number of the Custom Action Message to be displayed
during alarm conditions for this point (refer to Figure 3.20 for an example).
VIEW: Press this soft key to view the message associated with the number entered.
ACCEPT: Press to save the entries made on this screen.
Sensitivity
Detector sensitivity levels for alarm and prealarm are set at this screen, which displays when the
SENSITIVITY soft key is pressed at the Detector Point Programming (2) screen.
DETECTOR SENSITIVITY
L03D123
OCCUPIED UNOCCUPIED
SENSITIVITY SENSITIVITY
ALARM - 7 ALARM = 3
OCCUPIED UNOCCUPIED
SENSITIVITY SENSITIVITY
PREALARM - 5 PREALARM = 3
The control panel provides nine levels of Prealarm and Alarm in percent per foot obscuration, with
the following two exceptions:
BACK
Soft Keys
WEEKLY OCCUPANCY SCHEDULE: Press this soft key to place the cursor at the underlined
field. There can be up to ten Weekly Occupancy Schedules. Enter a value of zero through ten. Zero
indicates no schedule is applied, and occupied detector sensitivity values are used.
ACCEPT: Press this key to accept the change made and return to the previous screen.
PREALARM:ALERT
SILENCEABLE:NO
ACCEPT
BACK
Soft Keys
PREALARM: Press to select ALERT or ACTION for the Prealarm function. Refer to the section on
Prealarm in Appendix D, “AWACS™ Applications” for a description of Alert and Action.
SILENCEABLE: This field determines whether the user can manually silence a detector’s
activated sounder/relay base. Values are as follows:
YES - RESOUND FIRE Silenceable, resound on fire alarm events Network and Local Resound
YES - RESOUND SUPERV Silenceable, resound on supervisory events Network and Local Resound
POINT LABEL:
MONITOR L03M123 ACCEPT
EXTENDED LABEL:
BACK
Soft Keys
MODULE TYPE: Press the soft key to toggle between CONTROL and MONITOR.
TYPE CODE LABEL: Press this soft key to scroll through the point type choices: stop at the
appropriate selection.
FLASHSCAN CODE LABEL: Press this soft key to scroll through the point type choices: stop at
the appropriate selection (Table G.4 on page 137 for codes and descriptions). Choose NONE if the
point type is not FlashScan.
NOTE: If the point is not installed, MODULE TYPE: , TYPE CODE LABEL:, and FLASHSCAN
CODE LABEL: must be entered before any entries can be saved using the ACCEPT key.
POINT LABEL: Press this soft key to place the cursor at this field. Type in a 20-character
maximum point label that will appear in message formats. If no entry is made, the field will default
to the point address.
EXTENDED LABEL: Press to place the cursor at this field. Type in a 12-character maximum
extended label to further define the location or nature of the point.
MORE: Press to proceed to the next screen for more point programming.
ACCEPT: Press to save entries made on this screen.
Module Point Programming (Monitor Module)
Pressing the MORE soft key at the Module Point Programming screen will display this screen if the
module type was monitor.
ZONE MAP:
Z003 , Z104 , Z105 , Z106 , Z107
Z110 , Z114 , Z115 , Z116 , Z117
BACK
Soft Keys
CUSTOM ACTION MESSAGE: Displays the custom action message number (a value of one
through 100). The default value is 0 (no message). Press this soft key to progress to the Custom
Action Message screen (shown in Figure 3.27) to view the message or to choose a different
message for viewing when this point activates. (To create a new custom action message, refer to
“Custom Action Message” on page 35.)
ZONE MAP: Displays the zones mapped to this point. During initial programming, zone map
position one for each monitor module is set to Z0YY, where YY represents the loop number where
the module resides. In Figure 3.32 above, zone position one has a value of Z003 (YY = 03). The
module in the example resides on loop 3.
To add or delete zones, press this soft key to proceed to the Module Zone Map screen. Refer to
“Zone Map” on page 39 for an illustration and explanation of the Detector Zone Map screen. The
Module Zone Map screen is the same except that Module replaces Detector in the title and the
module address appears instead of the detector address. Up to ten general, releasing or special
zones may be mapped to a monitor module: none of the zone map positions are fixed. Position 1
has additional functionality.
Position 1 - This position is checked when a group zone disable command is issued. If the zone
number in the group zone disable command matches the zone number in the first position of
the zone map, the module point will be disabled.
ALARM VERIFICATION: Press this key to determine participation in Alarm Verification.
Choosing Yes will set the device participation to the value entered at the Panel Timers screen
(Figure 3.8). The only module type that can participate in alarm verification is the FZM-1.
LOCAL MODE: Press to toggle between Local Mode (ON) or no Local Mode (OFF). When there is
a communication loss between the panel and its LCM/LEMs, SLC devices that have been selected
for Local Mode participation (ON) will continue to function across all the panel’s SLCs in a limited
manner as follows: input points will activate output points of the same Type Code point type
designations. For example, SLC inputs with“fire” point types will activate SLC outputs with“fire”
point types. Refer to “Type Codes for Input Devices” on page 134 for Type Code point types.
Default: OFF
NOTE: The panel setting LCM LOCAL MODE must be set to Yes for local mode to work at the
device level.
ACCEPT: Press to save entries made on this screen and to return to the previous screen.
ZONE MAP:
Z000 , Z104 , Z105 , Z106 , Z107
Z110 , Z114 , Z115 , Z116 , Z117
SILENCEABLE:NO BACK
Soft Keys
ZONE MAP: Displays the zones mapped to this point. The default value assigned to control modules
during initial programming is Z000 at Position 1 (refer to Figure 3.33), with the exception of control modules
with the following Type IDs: Telephone, Gen Alarm, Gen Supervis, Gen Trouble, and Trouble Pend.
To add or delete zones, press this soft key to proceed to the Module Zone Map screen. Refer to
“Zone Map” on page 39 for an illustration and explanation of the Detector Zone Map screen. The
Module Zone Map screen is the same except that Module replaces Detector in the title and the
module address appears instead of the detector address. Up to ten general, logic, release, special or
trouble zones may be mapped to a control module. Position 1 has additional functionality.
Position 1 - This position is checked when a group zone disable command is issued. If the zone
number in the group zone disable command matches the zone number in the first position of
the zone map, the module point will be disabled.
Note that the group zone disable command has no effect on general alarm zone Z000.
WALK TEST: This field determines if the output will activate during Walk Test. Values are ON
(the output will activate) and OFF (the output will not activate). Default: OFF.
NOTE: The following Type ID codes do not participate in Walk Test, and the WALK TEST soft key will
not appear when the screen displays: REL END BELL, RELEASE CKT, REL CKT ULC, REL. FORM
C, REL AUDIBLE, INST RELEASE, NONRESET CTL, TELEPHONE, and FORM-C RESET. The
FMM-1module with SMOKE CONV, HEAT DETECT, or SMOKE DETECT does not participate in Walk
Test.
SWITCH INHIBIT: This field determines whether a user can manually activate an output.
Values are YES (can not be activated manually) or NO (can be activated manually). Default: NO
SILENCEABLE: This field determines whether the user can manually silence an activated output.
Values are as follows:
YES - RESOUND FIRE Silenceable, resound on fire alarm events Network and Local Resound
YES - RESOUND SUPERV Silenceable, resound on supervisory events Network and Local Resound
YES - RESOUND SECURITY Silenceable, resound on security events Network and Local Resound
NOTE: This soft key will not appear for modules with Type ID codes where silence is not optional.
LOCAL MODE: Press to toggle between Local Mode (ON) or no Local Mode (OFF). When there is
a communication loss between the panel and its LCM/LEMs, SLC devices that have been selected
for Local Mode participation (ON) will continue to function across all the panel’s SLCs in a limited
manner as follows: input points will activate output points of the same Type Code point type
designations. For example, SLC inputs with“fire” point types will activate SLC outputs with“fire”
point types. Refer to “Type Codes for Input Devices” on page 134 for Type Code point types.
Default: OFF
NOTE: The panel setting LCM LOCAL MODE must be set to Yes for local mode to work at the
device level.
WARNING: When using alarm verification, do not mix fire alarm points with non-fire alarm
! points on the same IZM-8RK/IZE-A Initiation Zone Module.
The point information is displayed onscreen in the format Pyy.z, where P means panel circuit point,
yy is the panel circuit module number (1 through 12), and z is the module push-button number (1-
8). Each panel circuit point is assigned an address by the panel depending on its location. Refer to
Figure 3.34 below for an illustration of how the panel assigns addresses.
.
CPU-3030 Panel 1st position* 2nd position 3rd position 4th position
Circuit Connection module module module module
addresses addresses addresses addresses
Panel Circuit #1 (J10) P1.1 - P1.8 P2.1 - P2.8 P3.1 - P3.8 P4.1 - P4.8
Pyy.1 Pyy.5
Panel Circuit #2 (J11) P5.1 - P5.8 P6.1 - P6.8 P7.1 - P7.8 P8.1 - P8.8
Pyy.2 Pyy.6 Panel Circuit #3 (J12) P9.1 - P9.8 P10.1 - P10.8 P11.1 - P11.8 P12.1 - P12.8
Pyy.3 Pyy.7 * The first position is the position closest to the CPU-3030 connection, the fourth
position is the furthest from this connection. These address assignments are fixed; if a
Pyy.4 Pyy.8 panel module is not installed in position 3 of panel circuit #1, the fourth position
module still has an address of P4.yy.
Panel Circuit Module
MORE
EXTENDED LABEL:
BACK
Soft Keys
PANEL MODULE TYPE: Press the soft key to toggle between MONITOR, CONTROL-CRM,
CONTROL-ICM. Select MONITOR for IZM-8RK/IZE-A modules, CONTROL-CRM for
CRM-4RK/CRE4 modules, and CONTROL-ICM for ICM-4RK/ICE-4 modules.
TYPE CODE LABEL: Press this soft key to scroll through the point Type Code choices: stop at
the appropriate selection.
POINT LABEL: Press this soft key to place the cursor at this field. Type in a 20-character
maximum point label that will appear in message formats. If no entry is made, the field will default
to the point address.
EXTENDED LABEL: Press to place the cursor at this field. Type in a 12-character maximum
extended label to further define the location or nature of the point.
MORE: Press to proceed to the next screen for more point programming.
ACCEPT: Press to save entries made on this screen.
ZONE MAP:
Z011 , Z104 , Z105 , Z106 , Z107
Z110 , Z114 , Z115 , Z116 , Z117
ACCEPT
BACK
Soft Keys
CUSTOM ACTION MESSAGE: Displays the custom action message number (a value of one
through 100). The default value is 0 (no message). Press this soft key to progress to the Custom
Action Message screen (shown in Figure 3.27) to view the message or to choose a different
message for viewing when this point activates. (To create a new custom action message, refer to
“Custom Action Message” on page 35.).
ZONE MAP: Displays the zones mapped to this point. The default value assigned to panel circuit
input modules during initial programming is Z011 in the first zone map position.
To add or delete zones, press this soft key to proceed to the Panel Module Zone Map screen. Refer
to “Zone Map” on page 39 for an illustration and explanation of the Detector Zone Map screen. The
Panel Module Zone Map screen is the same except that Panel Module replaces Detector in the title
and the module address appears instead of the detector address. Up to ten general, releasing or
special zones may be mapped to a panel monitor module. Position 1 has additional functionality.
Position 1 - This position is checked when a group zone disable command is issued. If the zone
number in the group zone disable command matches the zone number in the first position of
the zone map, the module point will be disabled.
ALARM VERIFICATION: Press this key to determine participation in Alarm Verification.
Choosing Yes will set the device participation to the value entered at the Panel Timers screen
(Figure 3.8).
ACCEPT: Press to save entries made on the screen and return to the previous screen.
ZONE MAP:
Z000 , Z104 , Z105 , Z106 , Z107
Z110 , Z114 , Z115 , Z116 , Z117
Soft Keys
ZONE MAP: Displays the zones mapped to this point. The default value assigned to panel circuit
output modules during initial programming is Z000, with the exception of control modules with the
following Type IDs: Telephone, Gen Alarm, Gen Supervis, Gen Trouble, and Trouble Pend. . To
add or delete zones, press this soft key to proceed to the Panel Module Zone Map screen. Refer to
“Zone Map” on page 39 for an illustration and explanation of the Detector Zone Map screen. The
Panel Module Zone Map screen is the same except that Panel Module replaces Detector in the title
and the module address appears instead of the detector address. Up to ten general, logic, release,
special or trouble zones may be mapped to a panel control module.Position 1 has additional
functionality.
Position 1 - This position is checked when a group zone disable command is issued. If the zone
number in the group zone disable command matches the zone number in the first position of
the zone map, the module point will be disabled.
Note that the group zone disable command has no effect on general alarm zone Z000.
WALK TEST: This field determines if the output will activate during Walk Test. Values are ON
(the output will activate) and OFF (the output will not activate). The default is OFF.
NOTE: The IZM-8RK module does not participate in Walk Test. Also, the following Type ID
codes do not participate in Walk Test, and the WALK TEST soft key will not appear when the
screen displays: REL END BELL, RELEASE CKT, REL CKT ULC, RELEA.FORM C, REL
AUDIBLE, INSTANT RELE, NONRESET CTL, and TELEPHONE.
SILENCEABLE: This field determines whether the user can manually silence an activated output.
Values are YES - RESOUND FIRE (manually silenceable, resounds on fire alarm) and NO (not
manually silenceable). The default is YES.
NOTE: This soft key will not appear for modules with Type ID codes where silence is not
optional.
SWITCH INHIBIT: This field determines whether a user can manually activate an output.
Values are YES (can not be activated manually) or NO (can be activated manually). The default is
NO.
ACCEPT
BACK
Soft Keys
ZONE LABEL: Press to type in a 20-character maximum zone description that will appear in the
zone’s display messages.
ACCEPT: Press to save the message and return to the previous screen.
DELAY TIME: 00
Refer to Appendix B, “Releasing Applications” for a full explanation of the fields below.
Soft Keys
DELAY TIME: Press this soft key to type a value from 0 to 60 (seconds). Default 00
ABORT SWITCH: Press this soft key to scroll through the selection list of ULI, IRI, NYC, or AHJ.
Default:ULI
CROSS ZONE: Press to scroll through the selection list of YES, NO, ZONE, HEAT. Default: NO.
SOAK TIME: Press to type a value from 0 to 9999 (seconds). Default: 0000
AND(Z20,OR(L2D159,L2D14))
EDIT EQUATION
Soft Keys
EDIT EQUATION: Press to proceed to the edit screen to add or edit a logic equation.
NEXT/PREVIOUS EQUATION: Press to view the next or previous logic equation.
AND(Z20,OR(L2D159,L2D14))
INSERT
The cursor will be present in the equation, and can be moved by pressing the left/right arrow keys
on the keyboard. To add or delete information, use the INS/OVR soft key function described
below. Use the keypad to type in an equation. The ADD POINT/ZONE and ADD LOGIC
FUNCTION soft keys may be used to facilitate creating a logic equation; however, commas must be
added by using the keypad.
Soft Keys
INS/OVR: Press to toggle between insert and overwrite. Stop at the appropriate mode, which
displays in line 8 of the screen. Insert will add information to the equation, overwrite will write
over information already in the equation.
ADD POINT/ZONE: Press to proceed to the Add Point/Zone screen. This screen is an alternative
to typing in the information at this screen; it provides point and zone formats that make it less likely
for typographical errors to occur.
ADD LOGIC FUNCTION: Press to proceed to the Add Logic Function screen. This screen is an
alternative to typing in the information at this screen; it provides logic function formats that make it
less likely for typographical errors to occur.
ADD TIME/DATE: Press to proceed to the Add Time/Date screen.
DELETE EQUATION: Press to delete the entire equation.
ACCEPT: Press to save changes made on this screen and return to the previous screen.
NOTE: When the ACCEPT soft key is pressed to save an equation, the panel checks the
equation for errors. If there is an error in the equation, the previous screen will not appear, and the
cursor will appear at the error point. Correct the equation, and re-press the ACCEPT: soft key.
AND(Z20,OR(L2D159,L2D14))
POINT SELECT:
L01D043 (DETECTOR)
The cursor will be present in the logic equation. Place it, using the arrow keys on the keyboard, at
the place where the additional point should be inserted.
Soft Keys
POINT SELECT: Press to scroll through the list of possible formats (detector, module, etc.). Stop
at the desired format. Type in the address for the additional point.
ACCEPT: Press to insert the point into the equation where the cursor is blinking, and to return to
the previous screen.
NEXT/PREVIOUS POINT: Press these soft keys to scroll forward or backward from the
displayed point to the next installed point.
Add Logic Function
This screen appears when the ADD LOGIC FUNCTION soft key is pressed at the Logic Zone
Programming Menu screen.
.
AND(Z20,OR(L2D159,L2D14))
BACK
The cursor will be present in the logic equation. Place it, using the arrow keys on the keyboard, at
the place where the logic function should be inserted.
Soft Keys
LOGIC FUNCTION: Press to scroll through the list of possible logic functions.
ACCEPT: Press to insert the logic function into the equation where the cursor is blinking, and to
return to the previous screen.
Add Time/Date
This screen appears when the ADD TIME/DATE soft key is pressed at the Logic Zone
Programming Menu screen
DEL
OVERWRITE
BACK
Soft Keys
ENTER TIME: _ _:_ _:_ _ Press this soft key to toggle between the time/date formats. Choose one
based on the type of time-based function used.
Table 3.1
Time-based Screen Field Time/date format
function
DEL, SDEL, TIM ENTER TIME:_ _:_ _:_ _ HH:MM:SS, entered as military time (22:30:00 = 10:30 P.M.)
TIM ENTER DAY: MO (Use the TOGGLE DAY soft key that appears to scroll through
and choose a day of the week.
Refer to Appendix E, “CBE: Zones and Equations” for information on how to create a trouble
equation, and how they operate.
ACCEPT
BACK
Soft Keys
A C S L A B E L : Type a label for the selected annunciator. The label can have up to 40 characters.
Soft Keys
CLEAR ALL PROGRAMMING: Press to remove all panel, panel module, loop, point and ACS
programming information, as well as logic and trouble zone equations. Pressing this key removes
everything except passwords. A confirmation screen will display asking the user to confirm the
deletion command. Pressing this key causes a reboot.
CLEAR:PANEL Press to remove all programmed panel setting information from control panel
memory. This does not remove ACS programming. A confirmation screen will display asking the
user to confirm the deletion command. Pressing this key causes a reboot.
CLEAR:PANEL MODULES Press to remove all panel module programming information. A
confirmation screen will display asking the user to confirm the deletion command. Pressing this
key causes a reboot.
CLEAR LOOPS Press to scroll through the options: ALL, LOOP 1, LOOP 2,...., LOOP 10. Stop at
the desired option. Press ACCEPT to delete all loop programming for the selected option. Pressing
this key causes a reboot.
DELETE POINT To delete a point, press this soft key to display the Delete Point screen. Pressing
this key may cause a reboot.
CLEAR ACS: Press to remove all ACS programming from panel memory. A confirmation screen
will display asking the user to confirm the deletion command. Pressing this key causes a reboot.
ACCEPT: Press to clear all programming for the selected loop option for CLEAR LOOPS. A
confirmation screen will display asking the user to confirm the deletion command.
DELETE POINT
POINT SELECT:
LyyDzzz (DETECTOR)
POINT SELECT: Press to scroll through the options: detector, module, or panel module. Stop at
the desired option. Press the DELETE soft key to delete the point from programming. A
confirmation screen will display asking the user to confirm the deletion command.
NOTE: Deleting points that are active or in trouble will cause a reboot.
AUTOPROGRAM MENU
ACCEPT
BACK
Soft Keys
AUTOPROGRAM LOOPS: Press to scroll through the options: ALL, 1+2, 3+4, 5+6, 7+8, 9+10.
Stop at the desired option to select it.
AUTOPROGRAM PANEL MODULES: Press to select panel modules for autoprogramming.
ACCEPT: Press to autoprogram the selection. A confirmation screen will display asking the
programmer to confirm the autoprogram choice made (press the YES soft key to confirm). A screen
with the message AUTOPROGRAM IN PROGRESS will display until autoprogramming is complete.
AUTOPROGRAM CONFIRMATION
REVIEW BACK
Soft Keys
REVIEW: Press this soft key to review the new devices found (with the option of adding them to
the program one by one), devices that are in the database that the autoprogram did not find, devices
that have data base and autoprogram information that differs, and devices that are incorrectly
doubled up on a single address. Devices will display in the following order:
• L01M001 through L01M159
• L01D001 through L01D159
• L02M001 through L02M159, etc.
Depending on what information was found, different screens may appear for different points. Refer
to Figure 3.51 through Figure 3.54 for examples of the screens.
ACCEPT ALL: Press to accept all the new devices that have been found by the autoprogram.
Errors and discrepancies will still be displayed the same as if the REVIEW soft key had been
pressed: however, new devices will not individually display for review and acceptance.
AUTOPROGRAM CONFIRMATION
ACCEPT
ALL
REVIEW BACK
Soft Keys
REVIEW: Press this soft key to review the new panel modules found (with the option of adding
them to the program one by one), modules that are in the database that the autoprogram did not
find, and modules that have data base and autoprogram information that differs. Devices will
display in the following order: P01 through P12.
Depending on what information was found, different screens may appear for different points. Refer
to Figure 3.51 through Figure 3.53 for examples of the screens.
NOTE: If panel circuit points have been added, Autoprogram will add them. Pressing the
REVIEW soft key does not give the option to review panel circuit points.
ACCEPT ALL: Press to accept all the new modules and devices that have been found by the
Autoprogram. Discrepancies will still be displayed the same as if the REVIEW soft key had been
pressed: however, new devices will not individually display for review and acceptance.
AUTOPROGRAM CONFIRMATION
ADD POINT?
YES NO
EDIT BACK
Soft Keys
YES: Press this soft key to install the new point into the panel’s database.
EDIT: Press this soft key to advance to the point programming menu for the new point. (This
option is available for SLC points only, not for panel points. The E D I T soft key will not appear for
panel modules).
NO: Press if the point will not be installed.
Error and Discrepancy Resolution
Pressing the REVIEW soft key will bring up screens that provide the means to resolve any errors or
discrepancies found during autoprogram.
AUTOPROGRAM CONFIRMATION
DELETE POINT?
YES NO
BACK
Display
This screen will display either the SLC device address or the panel circuit module address when a
previously installed/programmed point does not respond during a subsequent Autoprogram.
Soft Keys
YES: Press to delete the point information from the panel’s database.
NO: Press to leave the point information in the panel’s database.
AUTOPROGRAM CONFIRMATION
OLD:CONTROL-ICM
NEW:CONTROL-CRM
ACCEPT CHANGES?
YES NO
BACK
Display
The O L D field contains the information currently in the panel’s programming database. The N E W
field contains the information found during autoprogramming. The fields contain the FlashScan
Type ID codes if the device is FlashScan, or they will contain the device type if CLIP.
Soft Keys
YES: Press this soft key to accept the new device type.
EDIT: This soft key will appear only when SLC devices are mismatched. It will not appear for
panel modules. Press it to advance to the point programming screen for this point.
NO: Press if the new information should not be installed over the existing information in the
database.
AUTOPROGRAM CONFIRMATION
ACCEPT
BACK
Display
The SLC loop number and device address are displayed where the Autoprogram has found more
than one detector or module with the same address.
Soft Keys
ACCEPT: Pressing this soft key acknowledges that the programmer has been informed of the
double address. Autoprogram will not make a modification to the database for this point. The
installer must correct this problem.
Soft Keys
All soft key selections (except BACK) are menu selections. Press to display the desired menu.
POINT SELECT:
LyyDzzz (DETECTOR)
Soft Keys
POINT: Press this soft key to identify the type of point to disable/enable: the choices that will
appear in parentheses next to the point format are DETECTOR, MODULE, PANEL CKT, or
GENERAL ZONE. Enter the address of the point using the keyboard. If there is an event in the
display area, that address will be the default. If no event is present, the default format will be that of
a detector.
4.2 Disable/Enable
A point can be disabled or enabled using this screen. Press the DISABLE/ENABLE soft key at the
Alter Status screen to display the following.
DISABLE BACK
Soft Keys
DISABLE/ENABLE Only the applicable command will display. Press to disable an installed,
programmed point, or to enable a disabled one.
CAUTION: When a disabled output is enabled, it will be affected by conditions existing in the
! system that would normally affect it. That is, if a condition exists that would have turned the output on
were it enabled, it will turn on when it is enabled.
Group Zone Disable - This term refers to the disabling (or enabling) of a general zone. If the
first position in a device’s zone map matches the general zone number entered at this screen,
that device will be disabled (or enabled).
WARNING: Do not rely on Disable to disable releasing points during testing. Releasing
! points must be physically disconnected.
Soft Keys
POINT: Press to place the cursor in the format field. Type the address using the keyboard.
NEXT/PREVIOUS SELECTION: Press these soft keys to scroll sequentially through the detector
addresses on the loop. The screen will display the next loop when the last device on this loop is
passed.
ACCEPT: Press to proceed to the Detector Sensitivity screen.
The current sensitivity values displayed are described in Detector Point Programming (Refer to the
paragraph “Sensitivity” on page 41 ) and in Appendix D, “AWACS™ Applications”
BACK
Soft Keys
OCCUPIED ALARM SENSITIVITY:
Press the soft key next to one of
OCCUPIED PREALARM SENSITIVITY: these setting categories to proceed
to the next screen, where the
UNOCCUPIED ALARM SENSITIVITY:
setting value may be changed.
UNOCCUPIED PREALARM SENSITIVITY:
Change Alarm/Prealarm Sensitivity
This screen displays when any of the soft keys is pressed on the Detector Sensitivity Select screen.
The user can change detector sensitivity values using this screen.
The settings (1-9) displayed below the soft key are unique to the type of detector.
Soft Keys
OCCUPIED ALARM: The type of alarm/prealarm will display based on which soft key was
pressed in the previous screen. For example, in the screen above, OCCUPIED ALARM displays
because the OCCUPIED ALARM SENSITIVITY: soft key was pressed.
The detector sensitivity values display below the soft key. Select a value by pressing the soft key
until the desired value appears in the underlined field.
ACCEPT: Press to accept the change made on this screen, and to return to the previous screen.
CLEAR COUNTERS
BACK
Soft Keys
CLEAR COUNTERS: Press this soft key to clear all verification counters.
ALARM HISTORY
EVENT HISTORY
ALL HISTORY
BACK
Soft Keys
ALARM HISTORY: Press to clear Alarm history.
EVENT HISTORY: Press to clear Event history.
ALL HISTORY: Press to clear both Alarm and Event history.
WARNING: Physically disconnect all releasing devices before starting Walk Test. It is not
! sufficient to disable in any other manner.
WARNING: Walk Test mode can deactivate fire protection. Observe the following important
! precautions.
IMPORTANT!
• Prior to Walk Test, secure all protected buildings, and notify the building owner/operator,
fire department, and other pertinent personnel that testing is in progress.
• Immediately after Walk Test is completed, notify the same people that testing is complete
and the system is restored to normal operation. Reconnect releasing devices.
• Walk Test will “time out” and return to normal operation after one hour when no Walk Test
activations have occurred during that time.
• Walk Test may be exited at any time by pressing the ABORT soft key on the screen
NOTE: Walk Test will not start if any devices are active (i.e., fire alarms, security, supervisories
or pre-alarms.) To perform a walk test while a device is active, disable the device and press the
System Reset button.
Basic Walk Test - The basic test allows a single operator to run audible tests on the panel. All logic
equation automation is suspended during the test. All ACS devices will default to Disable. They
may be enabled by selecting NO at the DISABLE ACS BOARDS soft key on the Walk Test Menu
screen (Figure 4.9 ).
Advanced Walk Test - The advanced test allows field-supplied output point programming that will
react to input stimuli such as CBE and logic equations. When points are activated in advanced
testing, each initiating event will latch the input. Release of the latch and subsequent activation of
the next point is controlled through use of the NEXT TEST soft key. All ACS devices default to
disable. They may be enabled by selecting NO at the DISABLE ACS BOARDS soft key on the
Walk Test Menu screen (Figure 4.9 ).
An advanced test is audible. An audible test is intended for pull station verification, magnet-
activated tests on input devices, input and output device and wiring operation/verification. Only
devices previously configured to participate and designated as part of the test through the following
screens will make sound.
152 15 blinks, stop, 2 blinks, long stop, 15 blinks, stop, 2 blinks, long stop....
• an input device activated in Walk Test latches on steady green for the duration of the test. If
the device is put in trouble (for instance, the detector head is removed, then replaced), the
LED will be latched on for the duration of the test.
• an output device activated in Basic Walk Test will remain active and the LED will glow
steady green for
- 4 seconds for alarms
- 8 seconds for troubles.
• an output device activated in Advanced Walk Test will remain active and the LED will glow
steady green until the NEXT TEST soft key is pressed.
CLIP poll mode - Once the START TEST soft key has been pressed:
• intelligent addressable input and output devices continue to blink red as usual until
activated.
• an input device activated in Walk Test latches on steady red during activation. If the device
is put in trouble (for instance, the detector head is removed, then replaced), the LED wil be
latched on for the duration of the test.
• an output device activated during Basic Walk Test will remain active and the LED will glow
steady green (if a FlashScan module) or steady red (if a CLIP module) for
- 4 seconds for alarms
- 8 seconds for troubles.
• an output device activated in Advanced Walk Test will remain active and the LED will glow
steady green (if a FlashScan module) or steady red (if a CLIP module) until the NEXT TEST
soft key is pressed.
Conventional Devices - Monitor modules with the Type Codes SMOKE CONV, HEAT DETECT,
and SMOKE DETECT, and outputs with the Type Code FORM C RESET do not participate in Walk
Test other than blinking their addresses if they are polled in FlashScan mode. To prevent the
occurrence of false alarms for conventional devices, 24 volt power will be interrupted for up to
a minute after Walk Test has been exited.
BASIC/ADVANCED: ADVANCED
SILENT/AUDIBLE: AUDIBLE
Soft Keys
BASIC/ADVANCED: Press to toggle between the two choices. Stop at the desired test.
SILENT/AUDIBLE: This soft key is for future use. Walk test is audible.
PARAMETER: Press to scroll through the choices. Stop at the desired parameter. Choosing the
loops parameter will bring up the Walk Test loops programming screen (Refer to Figure 4.10 )
Choosing the panel parameter will bring up the panel Walk Test screen (Refer to Figure 4.13)
Choosing the Devices parameter will bring up the Devices Walk Test screen (Refer to Figure 4.11.
LOOPS All devices/points on all the FACP SLCs All devices/points on all the FACP
that are set to participate in Walk Test with SLCs, as well as panel circuit outputs
the exception of logic equations, whose that are set to participate in Walk Test.
activation is suspended.
PANEL The entire panel - all devices/points set to The entire panel - all devices/points set
participate in Walk Test - will participate with to participate in Walk Test including
the exception of logic equations, whose panel circuit outputs - will participate.
activation is suspended.
START TEST
BACK
The chosen settings are displayed (BASIC, AUDIBLE in Figure 4.10), and installed loops will
display with a participation field. The up and down arrow keys on the keypad navigate through the
fields. Choose YES for participation, NO for no participation, using the
NEXT SELECTION(+)/PREVIOUS SELECTION(-) keys on the keypad.
Soft Keys
START TEST: Press to begin Walk Test using the chosen parameters. Once Walk Test has begun,
this soft key becomes ABORT, and can be pressed at any time to exit Walk Test.
NEXT TEST: This key appears for Advanced Walk Tests when the panel parameter is chosen at the
Walk Test Menu Screen. Refer to Figure 4.13 for the location of this key. Press it to progress from
one activation to the next, latching the new point and releasing the latch on the previous point.
DEVICE:L01D005
This screen appears when DEVICES is chosen as a parameter at the Walk Test Menu. The chosen
settings are displayed (BASIC, AUDIBLE in Figure 4.11).
Soft Keys
DEVICE:Press this key to type the desired detector address into the underlined field.
NEXT POINT: Press this key to bring up the next installed address for an addressable detector into
the DEVICE field.
PREVIOUS POINT: Press this key to bring up the previous installed address of an addressable
detector into the DEVICE field.
ACCEPT: Press this key to begin Walk Test, and to proceed to the Devices Test Selection screen
(Figure 4.12).
TROUBLE
PROG MODE ACTIVATED
NFS-3030
10:22:34A FRI SEP 24, 2004
WALK TEST IN PROGRESS
SETTINGS:BASIC, AUDIBLE, PANEL
This field will appear only for a beam detector with an integral sensitivity test feature.
Soft Keys
START TROUBLE TEST:Press this key to generate a Trouble on the selected detector.
START ALARM TEST: Press to generate an Alarm on the selected detector.
START OBSCURATION TEST: Press to perform an Obscuration Test on the selected Beam
detector. (Beam detectors only.)
ABORT: Press to stop the Walk Test.
NOTE: The Trouble, Alarm and Obscuration tests described above are additional tools provided to
ascertain the functionality of a detector. They are not a substitute for periodic maintenance and
sensitivity verification per NFPA 72.
TROUBLE
PROG MODE ACTIVATED
NFS-3030
10:22:34A FRI SEP 24, 2004
WALK TEST IN PROGRESS
SETTINGS: ADVANCED, AUDIBLE, PANEL
Once the START TEST soft key has Once the START TEST soft key has
been pressed, this soft key appears. been pressed and the test begun,
the message changes to ABORT
Soft Keys
TIME/DATE: Press to bring the cursor to the time/date field. The current time and date will be
displayed using the current format. Change the values using the keypad.
TIME FORMAT: Press to scroll through a list of formats as follows; HH:MM AM/PM; H:MM
AM/PM; HH:MM; and H:MM. Stop at the desired format.
DATE FORMAT: Press to toggle between MM/DD/YY and DD/MM/YY formats. Stop at the
desired format.
TIME ZONE: Press to scroll through a list of 34 time zone selections. Stop at the appropriate zone.
ACCEPT: Press to save changes made on this screen and to return to the previous screen.
Soft Keys
POINT: Press this soft key to enter the point address to be forced on or off.
NEXT/PREVIOUS SELECTION: Press to progress to the next or previous point on the loop.
ACCEPT: Press to continue to the Control On or Control Off screen.
Soft Keys
FORCE OFF: Press this soft key to change the state of the control module from A U T O M A T I C
A C T I V E to A U T O M A T I C I N A C T I V E .
4.8.2 Control On
If the selected point is inactive, the Control On screen will appear
FORCE ON
BACK
Soft Keys
FORCE ON: Press this soft key to change the state of the control module from A U T O M A T I C
I N A C T I V E to A U T O M A T I C A C T I V E .
PANEL:
LCM IMAGE:
NCM: (NODE:134)
APP: 002.003.014 AUG 30 2004
DATABASE:
LAST CHANGED:
SYSTEM DATA
FROM:
FRONT PANEL
SERIAL NUMBER:
SELF TEST
NOTE: “LCM” refers to the code resident in the CPU-3030, not the code that is programmed into
the LCM.
NOTE: “LCD-160” refers to the code resident in the CPU-3030, not the code that is programmed
into the LCD-160.
TROUBLE
LOADING..NO SERVICE
LAKEVIEW GENERAL HOSPITAL
BOOTLOADER
REBOOT
LCD-160 DOWNLOAD:Press this soft key to display the LCD-160 Download menu screen.
REBOOT:Press this soft key to reboot the panel, and exit the bootloader screen.
LOOP DOWNLOAD:Press this soft key to display the Loop Download Menu screen.
TROUBLE
LOADING..NO SERVICE
LAKEVIEW GENERAL HOSPITAL
N001
BOOTLOADER
ADDRESS: Press this soft key to scroll through to the desired LCD-160 address. “All” means all
addresses. Default: ADDRESS 001.
Shortcut: Type 1 on the keyboard, which jumps to address 10, or type 2 for twenty, 3 for thirty,
0 to reset back to 1. Type an asterisk (*) to select all addresses.
DOWNLOAD TYPE: Press this soft key to scroll through the languages (LANGUAGE-ENGLISH,
LANGUAGE-HEBREW, LANGUAGE-PORTUGUESE, LANGUAGE-SPANISH), BANNER, APP
and BOOT. Stop at the desired selection.
Choose a language to change LCD-160s selected at the ADDRESS field to display in that
language.
Choose BANNER to add the panel banner to those LCD-160 displays selected at the ADDRESS
field.
Select APP to download an application file to the selected LCD-160(s).
Select BOOT to download a boot file to the selected LCD-160(s).
AUTO:Press this soft key to automatically download to the LCD-160 the most up-to-date language,
bootloader, and application from the panel.
START:Press this soft key to begin the download.
TROUBLE
LOADING..NO SERVICE
LAKEVIEW GENERAL HOSPITAL
BOOTLOADER
LOOP ADDRESS: Press this soft key to scroll through the Loops. Stop at the appropriate pair, or
select ALL.
DOWNLOAD TYPE: Press this soft key to scroll through the download types. Stop at the
appropriate type. Selections are: APP, BOOT, or APP/BOOT.
Select APP to download an application file to the selected loops.
Select BOOT to download a boot file to the selected loops.
Select APP/BOOT to select both for downloading.
AUTO:Press this soft key to automatically download to the selected loop(s) the most up-to-date
applications or boot programming from the panel.
START:Press this soft key to begin the download.
TROUBLE
LOADING..NO SERVICE
LAKEVIEW GENERAL HOSPITAL
BOOTLOADER
PERFORM DOWNLOAD
76%
TROUBLE
EPROM ERROR
LAKEVIEW GENERAL HOSPITAL
BOOTLOADER
PERFORM DOWNLOAD
MAIN MENU
Event Counts Display
More Information
Multiple Event List
History Select
All Events
Alarms Only
Troubles Only
Supervisory Only
Security/Other
Time/Date Interval
Time & Date Range Select
Point Range
Point Range Select
Read Status
Smoke Detector
Heat Detector
Monitor Module
Control Module
General Zone
Releasing Zone
Logic Zone
Trouble Zone
Panel Input
Panel Output
Annunciator
Program/Alter Status
Panel Program
Network Parameters
IP Access
Panel Settings (Panel Settings (1) Screen
Reminder Menu
More (Panel Settings (2) Screen
Panel Timers
More
LCD Programming
ACS Programming
ACS Point Programming
Supervision
More
Password Change
Master Password
User Password
Weekly Occupancy Schedule
Remote Display Menu
Remote Display Point Programming
Loop Configuration
Loop Point Programming
Custom Action Message
Event Logging
Holiday Menu
Point Program
Detector Point Programming (1)
Zone Map
More (Detector Point Programming (2))
Custom Action Message
Weekly Occupancy Schedule
Sensitivity
More (Detector Point Programming (3))
Module Point Programming
More
Zone Map
Custom Action Message
Panel Module Point Programming
More
Zone Map
Custom Action Message
General Zone Point Programming
Releasing Zone Programming
Logic Zone Programming
Edit Logic Equation
Add Point/Zone
Add Logic Function
Add Time/Date
Trouble Zone Programming
Annunciator Board Label
Delete Program Menu
Delete Point
Autoprogram Menu
Confirmation Screens
Alter Status
Disable/Enable
Detector Sensitivity
Sensitivity Select
Change Alarm/Prealarm Sensitivity
Clear Verify Counters
Clear History
Walk Test Menu
Walk Test Loop Parameters
Advanced Walk Activation
Device Test Selection
Walk Test in Progress
Program Time/Date
Control On/Off Point Select
Control Off
Control On
Printer Functions
Programming
Print Programming Menu
Print Programming Menu (2)
Active Points
Active Points Menu
Walk Test
Detector Maintenance Report
Installed Points
Installed Points Menu
Installed Points Menu (Range)
Function/Field Explanation
Delay Time Delay Time is the time that elapses between activation of an initiating device and
activation of all outputs mapped to the initiating device through a releasing zone.
Delay Time can have a value of 0 to 60 (seconds). A value of 0 will result in immediate
output activation upon activation of the initiating device.
Following is a graphic representation of what happens when a delay timer is set to 15
seconds for releasing zone ZR02.
Initiating device with Delay Time = 15 (seconds) All outputs with
releasing zone ZR02 in their zone
ZR02 in its zone 15 maps activate at
0 sec. 15 seconds
map activates sec.
NOTE: If cross-zoning is in effect, the delay time will not begin until the
cross-zoning conditions are met. Refer to “Cross Zones” on page 97 for
more information.
Abort Switch Selection of a 3-letter abort switch type code (ULI, IRI, NYC, or AHJ) defines the
operation of an Abort Switch in that releasing zone. Refer to the specific abort switch
type code heading in this appendix for details on how each functions.
Cross Zone Select one of three Cross Zone types (Yes, Zone, or Heat), or No (not used). A Cross
Zone requires tripping two or more initiating devices to activate the outputs mapped to a
releasing zone. Refer to the Section B.3.5 on page 97 section of this appendix for details
and examples.
Soak Time Soak Time specifies the length of time to dump releasing agents when a releasing zone
(NFPA 16 activates. When the Soak Time expires, the control panel automatically shuts the
Applications releasing solenoids for the active releasing zone. Soak Time can have a value of 0 to
only) 9999 seconds. If Soak Time is set to 0, the releasing solenoids will remain active until
system reset.
Following is a graphic representation of what happens when soak time is set to 300
seconds for releasing zone ZR02.
Initiating device At 300
with releasing Soak Time = 300 (seconds) seconds, the
zone ZR02 in its control panel
zone map shuts releasing
activates. All 0 300 sec.
solenoids for
outputs with ZR02 sec.
outputs with
in their zone maps ZR02 in their
activate. zone maps.
SYSTEM SYSTEM
Abort Switch NORMAL ACTIVATED
Manual Agent
Release lever
• A monitor module wired to an abort station and programmed with the Type Code ABORT
SWITCH
• All initiating devices and outputs with a common releasing zone in their zone maps - ZR05
in the example shown
• A fully programmed releasing zone - releasing zone ZR05 in the example shown. (Refer to
“Releasing Zone” on page 51 for programming information.)
In the following example, when an initiating device activates (one of the two detectors or the pull
station), pressing and holding the abort switch while the delay time is in effect will prevent the
control panel from sending the command to dump releasing agents when the delay time expires.
The abort switch selection (ULI, IRI, NYC, or AHJ) determines the function of the abort switch.
SYSTEM SYSTEM
NORMAL ACT IVATED
Monitor
Module with
Detector Detector
ABORT SWITCH
Type Code
Abort station with Abort Switch
and Manual Release lever
ZR05
Example: If you program these three output modules Example: If you program a
as shown, these outputs activate at release. fourth module as shown,
this output activates when
the release is finished.
When an alarm initiates in the programmed releasing zone, the abort switch can be pressed while
the delay timer continues to count down, and held for as long as necessary. (If the abort switch is
pressed after the delay timer has expired, the abort switch has no effect.) Releasing the abort switch
starts a countdown by a 10-second ULI timer. When the 10-second ULI timer expires, the control
panel activates the releasing zone outputs.
Program selections for this releasing zone
Delay Time: 15 seconds
Abort Switch: ULI
Cross Zone: N Total time from alarm initiation to
Soak Time: 0 release:
Delay Time=15 sec. 5 + 15 + 10 = 30 seconds
5 sec 15 sec
Alarm
10 sec
Press and hold the
Abort Switch for 15
seconds Release the Abort
Switch; the 10-second
ULI timer begins
When the
10-seconds ULI
timer expires, the
WARNING:
! The IRI abort switch will only work if it is pushed before the second alarm occurs. If it is pushed after
the second alarm, the releasing zone will already have been activated, and the switch will have no
effect.
5 sec.
5 sec.
Alarm 1
10 sec.
When an alarm initiates in the programmed releasing zone, pressing and holding the abort switch
stops the delay timer countdown. The delay timer restarts at the beginning of its countdown when
the abort switch is released. When the Delay Time expires, the 90-second NYC timer starts
counting down. When both timers expire, the control panel activates releasing zone outputs.
NOTE: 120 seconds is the maximum delay after the abort switch is released. If the Delay Time
plus the NYC delay time of 90 seconds exceeds 120 seconds, the releasing zone outputs will still
be activated at 120 seconds after the abort switch is released.
0 sec.
105 sec. (15 + 90). Does not exceed 120 seconds.
10 sec.
30 sec.
Alarm
Press and hold
the Abort Switch
Release Abort Switch---
At this point, the delay time When all timers are expired (in this
becomes the programmed example, 145 seconds after alarm
delay (15 sec.) plus 90 initiation, 105 seconds after the
seconds (105 sec.) OR 120 Abort switch has been released)
seconds, whichever is smaller the control panel activates
Releasing Zone outputs
expire at 150 seconds: however, this time exceeds the maximum of 120 seconds, so the releasing
zone outputs will begin releasing at 120 seconds, not at 150. Following is a graphic example of an
NYC Abort Switch and a delay timer programmed to a releasing zone.
Program selections for this releasing zone
Delay Time: 60 seconds
Abort Switch: NYC
Cross Zone: N
Soak Time: 0
10 sec.
30 sec.
Alarm
Press and hold
the Abort Switch
120 sec. to release
When an alarm initiates in the programmed releasing zone, the programmed Delay Time starts.
Pressing and holding the abort switch suspends the delay timer. When the abort switch is released,
the control panel restores the value of the programmed Delay Time and the delay timer counts
down. When the Delay Time expires, the control panel activates releasing zone outputs.
Program selections for this releasing zone
Delay Time: 60 seconds
Abort Switch: AHJ
Cross Zone: N
Soak Time: 0 Total time from alarm initiation to
Delay=60 sec.
release:
0 sec. 45 sec 60 sec. 75 sec. 135 sec.
45 sec.
30 sec.
Alarm
60 sec.
NOTE: The FACP considers only the primary zone (the first zone in a point’s zone map) to
determine whether conditions have been met for Cross Zone type Z.
A summary of the types of Cross Zones and the conditions for activating a releasing zone:
Table 3:
Type Activates when
No A Cross Zone has not been selected. An alarm from any detector mapped to the
releasing zone activates it.
Yes Two or more initiating devices are in alarm that are mapped to the same releasing
zone.
Zone Two or more initiating devices are in alarm that are mapped to two different primary
zones and that are also mapped to the same releasing zone. Note that the FACP
considers only primary zones to determine whether releasing zone activation should
occur.
Heat At least one smoke detector mapped to a releasing zone is in alarm and at least one
heat detector mapped to the same releasing zone is in alarm.
General
Zone Z001
Releasing
Zone ZR01
* indicates a
primary zone
Each Cross Zone option and the conditions required to activate releasing zone ZR01 are shown in
the table below, according to the example in Figure B.8.
Table 4
Cross Zone Selection
Condition(s) Required to Activate the Releasing zone
(Cross=)
Cross=No An alarm from any initiating device activates the releasing zone.
Cross=Yes An alarm from any two initiating devices activates the releasing zone.
Cross=Zone An alarm from two initiating devices mapped to different primary general
zones, but mapped to the same releasing zone.
For example: • An alarm from L02D101 and L02D103
• An alarm from L02D102 and L02D104
• An alarm from L02D101 and L02D104
• An alarm from L02D102 and L02D103
The two detectors listed in each set above are each mapped to different
primary general zones, but both list ZR01 in their zone maps.
NOTE: Panel circuit modules are not suitable for the release of agents.
Type Codes designed for releasing zone inputs (SLC monitor modules).
Table 5:
Type Code What the Type Code does Refer to
ABORT SWITCH Provides an abort function through “How to Program an Abort Switch”
(tracking) a monitor module (connected to a on page 100
UL-listed abort station) for a
releasing zone.
MAN REL DELAY Provides a manual release with a “How to Program a Manual
(latching) 10-second delay through a monitor Release Delay Switch” on
module (connected to a UL-listed page 102
pull station) for a releasing zone.
SECOND SHOT Provides a second manual release “How to Program a Second Shot
(latching) through a monitor module Switch” on page 104
(connected to a UL-listed pull
station) for a releasing zone.
Type Codes designed for releasing zone outputs (SLC control modules).
Table 6:
Type Code What the Type Code does Refer to
REL END BELL Activates an NAC audio or visual “How to Program a Release End
device when releasing circuits shut Bell Circuit” on page 105
off.
REL CKT ULC Directs outputs to perform a release “How to Program a ULC Release
function as required by ULC. Circuit” on page 106
REL. FORM C Directs relay outputs to perform a “How to Program a Release Form-
releasing function. C Circuit” on page 108
REL AUDIBLE Activates audio or visual devices “How to Program a Release Audible
steady when releasing starts. Circuit” on page 109
Description A monitor module, connected to a UL-listed abort station (such as the Notifier
NBG-12LRA), used to monitor an abort switch for a releasing zone. Multiple
monitor modules can be programmed with the ABORT SWITCH Type Code. They
will work like multiple conventional abort switches on a conventional zone.
Program Select a monitor module for use as an Abort Switch. While programming this
module (refer to “Module Point” on page 43 for instructions),
1. Select the ABORT SWITCH Type Code.
2. Enter the number of the desired releasing zone into the module’s zone map.
The releasing zone must be fully programmed, with the Abort Switch type
code included (refer to “Releasing Zone” on page 51).
Example A programming example of a monitor module programmed as an Abort Switch for Releasing
Zone ZR05.
SYSTEM SYSTEM
NORMAL ACT IVATED
Monitor
Detector
Module
Type Code
ABORT SWITCH
NBG-12LRA
station with
Abort Switch
R05
SLC SLC
output output
module module
Description A monitor module—connected to a UL-listed manual station (such as the Notifier NBG-
12LRA)—used to monitor a pull station for the manual release of agents. A Manual Release
switch overrides all timers, such as Delay Time or a Soak Time. Multiple monitor modules
can be programmed with a MAN. RELEASE type code. They work like multiple conventional
manual release switches on a conventional zone.
Program Select a monitor module for the manual release function. While programming this module
(refer to “Module Point” on page 43 for instructions),
1. Select the MAN. RELEASE type code.
2. Enter the number of the desired releasing zone into the module’s zone map. The releasing
zone must be fully programmed (refer to “Releasing Zone” on page 51).
Example A programming example of a monitor module programmed as an manual release switch for releasing zone
ZR05.
SYSTEM SYSTEM
NORMAL ACT IVATED
Monitor
Detector
Module
Type Code
MAN. RELEASE
ZR05
SLC SLC
output output
module module
SYSTEM SYSTEM
NORMAL ACT IVATED
Monitor
Detector
Module
Type Code
MAN REL DELAY
NBG-12LRA
station with
Manual Release ZR05
Lever
SLC SLC
output output
module module
For example, program releasing zone ZR05 with a Manual Release Delay switch for the following
releasing selections: Delay Time = 15, Abort Switch = ULI, Cross Zone = NO, Soak Time = 30.
When the Manual Release Delay Switch activates, the control panel replaces the remainder of the
15-second Delay Time, if running, with a 10-second timer.
Examples:
1. The FACP programmed Delay Time begins its 15 second countdown. The Manual Release
Delay switch is pulled when the FACP delay timer has counted down to 12 seconds. The 12
seconds remaining in the countdown are overridden by the 10-second delay initiated by the
Manual Delay switch. In this example, the total time elapsing from FACP countdown initiation
to agent release is 13 seconds, less than the original 15 second FACP Delay Timer countdown.
2. The FACP programmed Delay Time begins its 15 second countdown. The Manual Release
Delay switch is pulled when the FACP Delay Timer has counted down to 8 seconds. The 8
seconds remaining in the countdown are overridden by the 10-second delay initiated by the
Manual Delay switch. In this example, the total time elapsing from FACP countdown initiation
to agent release is 17 seconds, more than the original 15 second FACP Delay Timer
countdown.
3. The FACP programmed Delay Time is not running (as would happen if the releasing station
were pulled before an alarm registered). The Manual Release Delay Switch is activated by the
pull station. Agent release will occur in 10 seconds.
NOTE: The Second Shot switch can only be used with the MAN REL DELAY Type Code
The following contains information needed to program a Second Shot switch for a monitor module.
SLC SLC
output output
module module
With two monitor modules configured as shown above, program releasing zone ZR05 for the
following releasing selections: Delay Time = 15, Abort Switch = ULI, Cross Zone = Y, Soak Time
= 30
ZR05 can be activated in one of two ways, as described in the examples given below.
Example 1: If the detector initiates the alarm, ZR05 activates. Releasing begins after the delay
timer has expired (15 seconds). Releasing will continue for the soak timer duration (30 seconds).
The Second Shot switch can then be activated, and will remain activated for the soak timer
duration. Once the Soak Timer expires, the Second Shot switch can then be activated to initiate an
additional soak cycle.
Example 2: If the NBG-12LRA (Type Code MAN REL DELAY) lever is pulled, the delay timer
begins its 15 second countdown. Releasing will begin after the delay timer has expired, and will
continue for the soak timer duration (30 seconds). The Second Shot switch can then be activated,
and will remain activated for the soak timer duration. Once the Soak Timer expires, the Second
Shot switch can then be activated to initiate an additional soak cycle.
NOTE: A releasing circuit with this Type Code requires the following selections: a Releasing
Zone; an output circuit mapped to the same Releasing Zone; Switch Inhibit; Non-Silenceable; No
Walk Test.
The following contains information needed to program a Release End Bell circuit for an SLC or
Panel Circuit output module.
Description An SLC or panel circuit output module to activate an audible or visual device
when releasing devices shut off. Multiple outputs with the REL END BELL Type
Code can also be mapped to the same Releasing Zone. When all the Releasing
Zone functions are complete, all outputs with the REL END BELL Type Code
activate at the same time. A REL END BELL circuit remains on until the system is
reset.
Program Select an SLC or panel circuit output module to use as a Release End Bell circuit.
While programming the point (refer to the Point Programming section of this
manual for instructions),
1. Select the REL END BELL Type Code,
2. Enter the number of the desired releasing zone into the module’s zone map.
The releasing zone must be fully programmed (refer to “Releasing Zone” on
page 51).
Example A programming example of a control module programmed as a Release End Bell for
Releasing Zone ZR05.
Monitor
Module Detector Detector Detector
ZR05
SLC SLC
Output output output Output
module module module module
NOTE: A ULC Release Circuit with this Type Code requires the following selections: a Releasing
Zone; an output circuit mapped to the same Releasing Zone; Switch Inhibit ; Non-Silenceable; No
Walk Test.
The following contains information needed to program a ULC Release Circuit for an SLC output
module.
Description An SLC output module used to activate a releasing solenoid or other releasing device. Multiple
outputs with the REL CKT ULC Type Code can also be mapped to the same Releasing Zone. When
the Releasing Zone activates, all outputs with the REL CKT ULC Type Code also activate at the
same time. A ULC Release Circuit activates when:
• An initiating device programmed to the same Releasing Zone activates (two devices if
using the Cross Zone option)
• The Delay Timer for the Releasing Zone (if used) expires
• No Abort Switch for the Releasing Zone (if used) is active
A ULC Release Circuit —and all wiring to the release device—is fully supervised and usable with
power-limited energy cable.
Program Select an SLC output module to use for a ULC Release Circuit. While programming the point
(refer to the Point Programming section of this manual for instructions),
1. Select the REL CKT ULC Type Code,
2. Enter the number of the desired Releasing Zone into the module’s zone map. The releasing
zone must be fully programmed (refer to “Releasing Zone” on page 51).
Example A programming example of a control module programmed as a ULC Release Circuit for Releasing Zone ZR05.
Monitor
Module Detector Detector Detector
ZR05
NOTE: A Release Circuit with this Type Code requires the following selections: a Releasing
Zone; an output circuit mapped to the same Releasing Zone; Switch Inhibit; Non-Silenceable; No
Walk Test.
NOTE: Do not use a Release Circuit for the following: An application requiring ULC Listing; An
application requiring power-limited energy cable.
The following contains information needed to program a Release Circuit for an SLC output circuit
module.
Description An SLC output module used to activate a releasing solenoid or other releasing device. Multiple
outputs with the RELEASE CKT Type Code can be mapped to the same Releasing Zone. When the
Releasing Zone activates, all outputs associated with the releasing zone and with the RELEASE
CKT Type Code also activate at the same time. A Release Circuit activates when:
• An initiating device programmed to the same Releasing Zone activates (two devices if
using the Cross Zone option)
• The Delay Timer for the releasing zone (if used) expires
• The Abort Switch for the releasing zone (if used) is not active
Program Select an SLC output module to use as a Release Circuit. While programming the point (refer to
the Point Programming section of this manual for instructions),
1. Select the RELEASE CKT Type Code
2. Enter the number of the desired Releasing Zone into the module’s zone map. The releasing
zone must be fully programmed (refer to “Releasing Zone” on page 51).
Example A programming example of a control module programmed as a Release Circuit for Releasing Zone ZR05.
Monitor
Module Detector Detector Detector
ZR05
NOTE: An output with a REL. FORM C Type Code requires the following selections: a Releasing
Zone; an output circuit mapped to the same Releasing Zone; Switch Inhibit; Non-Silenceable; No
Walk Test.
The following contains information needed to program a Release Form-C circuit for an SLC
Form-C relay output module.
Description An SLC output module, configured as a relay, programmed to activate an output by opening or
closing a switch. Typical applications include closing doors and air handlers.
Program Select an SLC output module to use as a Releasing Form-C Circuit. While programming the
point (refer to the Point Programming section of this manual for instructions),
1. Select the REL. FORM C Type Code,
2. Enter the number of the desired Releasing Zone into the module’s zone map. The releasing
zone must be fully programmed (refer to “Releasing Zone” on page 51).
Example A programming example of a control module programmed as a Release Form-C circuit for Releasing Zone
ZR05.
Monitor
Module Detector Detector Detector
ZR05
NOTE: An output with a REL AUDIBLE Type Code requires the following selections: a Releasing
Zone; an output circuit mapped to the same Releasing Zone; Switch Inhibit.
The following contains information needed to program a Release Audible circuit for an SLC or
Panel Circuit output module.
Description An output module programmed to activate an audio or visual device when all releasing outputs,
programmed to the same Releasing Zone, turn on. Multiple outputs with the REL AUDIBLE Type
Code can be mapped to the same Releasing Zone. When the Releasing Zone activates, all
outputs with the REL AUDIBLE Type Code activate at the same time.
Program Select a control module or panel circuit module to use as a releasing circuit. While
programming the point (refer to the Point Programming section of this manual for instructions),
1. Select the REL AUDIBLE Type Code,
2. Enter the number of the desired Releasing Zone into the module’s zone map. The releasing
zone must be fully programmed (refer to “Releasing Zone” on page 51).
Example A programming example of a control module programmed as a Release Audible circuit for Releasing
ZoneZR05.
Monitor
Module Detector Detector Detector
ZR05
SLC SLC
Output output output Output
module module module module
A B
Type Code Type Code Type Code Type Code
REL AUDIBLE RELEASE CKT RELEASE CKT REL AUDIBLE
NOTE: An output with an INST RELEASE Type Code requires the following selections: a zone
selection (a releasing zone may be used, but is not required); an output circuit mapped to the
same zone; Switch Inhibit; Non-Silenceable; No Walk Test.
The following contains information needed to program an Instant Release circuit for an SLC output
module.
Description An SLC output circuit module programmed to activate non-releasing devices, such as door
openers or warning sounders, without counting down delay timers. A device programmed with
the INST RELEASE Type Code device is supervised for open circuits and ground faults.
Program Select an SLC output module to use with a releasing circuit. While programming the point (refer
to the Point Programming section of this manual for instructions),
1. Select the INST RELEASE Type Code,
2. Enter the number of the desired Releasing Zone into the module’s zone map. The releasing
zone must be fully programmed (refer to “Releasing Zone” on page 51).
Example A programming example of a control module programmed as an Instant Release circuit for Releasing Zone
ZR05.
Monitor
Module Detector Detector Detector
ZR05
SLC SLC
SLC SLC
output output
output output
module module
module module
A B
Illustration
ZR01
Type Code Type Code Type Code Type Code Type Code
RELEASE CKT INST RELEASE control control control
ZL1 ZL2 ZL3
B.4 Miscellaneous
B.4.1 Initiating Devices
Releasing zone initiating devices include the following:
• FST-851/751 intelligent heat detectors
• FSI-851/751, FSP-851/751, FAPT-851/751, FSL-751 intelligent smoke detectors
• Conventional detection UL-listed devices connected to monitor modules
Multiple zone initiating devices can be used for the same releasing hazard. Map zone initiating
devices to the same Releasing Zone. Factory Mutual and certain Local Authorities Having
Jurisdiction require using redundant wiring (NFPA 72 Style 6 or Style D) for initiating devices in
releasing applications.
When the Delay Timer starts, when the Map the SLC or Panel Circuit to a releasing hazard
releasing device activates, or both zone (R0-R9).
Immediately when one of the initiating Map the SLC or Panel Circuit output to a separate
devices activate zone (not R0-R9) that is also mapped to all initiating
devices of the hazard.
Function Do this
A releasing application Use control modules set for dry contact operation. Program the
requires control relays control relays for different functions by following the
instructions in “To activate a sounder” above.
Providing control functions Use an ACM-8R remote relay module mapped to the software
zones of the control panel.
PAS (15 s)
The control panel delays activation of outputs containing ZF0 in their zone maps for all alarm
initiating devices that contain ZF0 in their CBE list. A subsequent alarm will abort the Presignal
Delay Timer and execute CBE lists.
Notes on using ZF0
• NFPA 72 requires installation of a PAS Inhibit switch, that can be used to turn off the PAS
delay timer when the control panel is unattended. Do so by programming a monitor module
with the Type Code, PAS INHIBIT.
• The Presignal Delay timer countdown can be stopped by pressing the SYSTEM RESET key
before the timer expires.
• Program zone ZF0 to participating inputs and outputs.
Restrictions on using ZF0
• Do not include ZF0 in the CBE list for a releasing device.
• Do not include ZF0 in the CBE list for any monitor module that connects to a device other
than an automatic fire detector.
NOTE: Do not include ZF8 in the zone map of Panel Circuits used for releasing or zone coding
applications.
Select Coding Functions on a global basis by setting the Panel Circuit Bell Coding field to March
or Temporal. (Refer to “Panel Settings (2) Screen” on page 22). Select individual panel circuit
output points for coding participation by entering ZF8 in the point’s zone map. All Panel Circuit
outputs with ZF8 in their zone maps will sound the same code when activated. The table below
contains descriptions of each Coding Function selection:
Coding Function
Signal
Selection
Temporal 0.5s on, 0.5s off, 0.5s on, 0.5s off, 0.5s on, 1.5s off, repeats
Topic Page
A graphic representation of a detector analog reading using drift compensation and smoothing:
Alarm Level
without compensation
Awacs1a.cdr
Analog with compensation and
Reading smoothing
Time
MAINTENANCE REQ
Acceptable
Range
LOW THRESHOLD
Low Value
Prealarm Threshold
Analog
Awacs4a.cdr
Reading
Time (days)
2.1%
2.0% 2.0% Alarm Selection 9
1.5% 1.5% Alarm Selection 8 1.5% Pre-Alarm 9
1.0% 1.0% Alarm Selection 7 1.00% Pre-Alarm 8
0.7% 0.7% Pre-Alarm 7
0.5% 0.5% Alarm Selection 6 0.5% Pre-Alarm 6
0.2% 0.2% Alarm Selection 5 0.2% Pre-Alarm 5
0.1% 0.1% Alarm Selection 4 0.1% Pre-Alarm 4
0.05% 0.05% Alarm Selection 3 0.05% Pre-Alarm 3
0.03% Alarm Selection 2
SAMPLE 0.02% Alarm Selection 1 0.02% Pre-Alarm 2
SENSITIVITY
Self Adjust 1
WINDOW, laser detector
Figure D.4 Sample Sensitivity Levels for a FlashScan View Laser Detector
Combined
Alarm
SMOKE OBSCURATION
3 Sensors
Awacs5a.cdr
Time (minutes)
D.3 Pre-Alarm
D.3.1 Definition
The Pre-Alarm function is a programmable option which determines the system’s response to real-
time detector sensing values above the programmed setting. Use the Pre-Alarm function to get an
early warning of incipient or potential fire conditions. There are two levels of Pre-Alarm:
• Alert (Refer to “Alert Level” below)
• Action (Refer to “Action Level” on page 119)
Alert and Action Pre-Alarm settings are set with point programming. Unique Pre-Alarm sensitivity
levels (PA) for individual detectors are listed in “Detector Sensitivity Settings” on page 119.
The LEDs on detectors polled in FlashScan mode will light steady green when in pre-alarm.
• The Pre-Alarm indication for this detector will restore automatically to normal if its
sensitivity, programmable to one of nine settings, drops below pre-alarm level.
• A subsequent alarm for this detector also clears the Pre-Alarm indication.
* Detectors are suitable for open area protection within the listed air velocity range. Typically, this range is 0 - 4,000 ft/min for
photoelectric detectors and 0 - 1,200 ft/min for ionization detectors. Be sure to confirm this range before installing the detector
by referring to the manufacturer’s installation instructions.
† Use only alarm sensitivity setting of AL=1, AL=2 or AL=3 for ION detectors installed in Canada.
‡ The use of alarm sensitivities below 0.50% obscuration per foot requires a 90 day test to ensure that the environment
for the detectors is suitable for the higher sensitivity setting. (Refer to “To Test Detectors Set Below 0.50%
Obscuration per Foot” on page 121.)
** 1% max. on CLIP. Larger figures may display.
†† Refer to the beam detector manual to determine the alarm settings: they are a function of the distance between the detector and
its reflector. There is no Prealarm for beam detectors in CLIP mode.
Table D.2 Detector Sensitivity Settings
Step Action
1 Initially set to the 0.50% obscuration per foot Alarm level.
2 Set the Pre-Alarm level to the desired final Alarm sensitivity.
3 Set the Pre-Alarm to Alert mode (non-latching).
2. Operate detectors continuously for 90 days with all environmental factors (such as,
temperature, humidity, air flow, occupancy, and so on) similar to the intended application for
the detectors. Record all events for each tested detector with an electronic History buffer or a
printout.
3. At the end of the 90-day test: An authorized Notifier representative, or an end user trained by
an authorized Notifier representative must inspect the results of the test. If the test results show
no alarms or pre-alarms for the tested detectors, reprogram the fire alarm system to set the
Alarm sensitivity to the more sensitive Pre-Alarm level of the test.
******DETECTOR MAINTENANCE******************************************************
NORMAL SMOKE(LASER) Detector L01D001 000330us 000340us Comp:000% Pk: 002%
Alarm: 000% PreAlarm: 000% A6P6 V000 L01D001
NORMAL SMOKE ACCLIM Detector L01D002 000030us 000000us Comp:000% Pk: 000%
Alarm: 000% PreAlarm: 000% A8P8 V000 L01D002
Field Identification
Long term average of
raw analog value in
microseconds
Current reading of raw analog
value in microseconds Compensation
percentage
Extended
Label Label Detector peak
State
The first field displays the point control. There are three designations that could appear in this field
Point Control Description
Designation
DISABLED The point has been forced into a disabled state by an outside source.
The second field displays the point status. There are two designations that could appear in this field.
Point Status Description
Designation
The device is a detector (an input device) so by referring to the descriptions below, it can be
determined that the point is in a normal state.
Inputs: (detectors, monitor modules, zones)
If the point is not in trouble or disabled, and the point is automatically controlled by the panel, the
display will be one of the following:
AUTOMATIC INACTIVE
AUTOMATIC ACTIVE
AUTOMATIC PREALARM
If the point is disabled, the display will be one of the following. The Trouble Status field will
appear if the point is in trouble.
DISABLED INACTIVE <Trouble Status>*
DISABLED ACTIVE <Trouble Status>*
DISABLED PREALARM <Trouble Status>*
If the point is in trouble, the display will read:
TROUBLE INACTIVE <Trouble Status>*
TROUBLE ACTIVE <Trouble Status>*
TROUBLE PREALARM <Trouble Status>*
*The field <Trouble Status> will contain a device trouble message. Refer to this panel’s Operations
manual for information on these messages.
Line 7 - The custom label for this point
Line 8 - Continuation of the point’s custom label, first zone, and device type
Lines 9,10 - a display of all the zones that contain the current point being read.
Lines 11through 14 -These lines will have values in them only if the device is a detector. They will
not display for wireless detectors.
Line 11
VALUES:
The screen displays the Alarm and Prealarm values that are in effect when read status is
requested. For example, if occupied settings are in effect, occupied values will display
121% OF ALARM - This field gives the detector reading as it relates to its preprogrammed
alarm level value (indicated in the next line on the screen). The example above shows the
detector exceeding the alarm level by 21%.
145% OF PREALARM - This field gives the detector reading as it relates to its
preprogrammed prealarm level value (indicated in the next line on the screen). The example
above shows the detector exceeding the prealarm level by 45%.
If the detector is an Alert heat detector, the value is indicated by a temperature reading
(example: 148 DEGREES F).
Line 12
The screen displays the Alarm and Prealarm levels that are in effect when read status is
requested. For example, if unoccupied settings are in effect, they will display.
ALARM: 6=1.66% - Six is the preprogrammed alarm level value for this detector: its value is
1.66%, indicating the percent per foot obscuration value assigned to level 6.
PREALARM: 3=0.47% - Three is the preprogrammed alarm level value for this detector: its
value is 0.47%, indicating the percent per foot obscuration value assigned to level 3.
Line 13
ACTION/STATUS: NONE/VERY CLEAN - This displays the maintenance status of the
device. The message that appears in this field depends on the drift compensation value. A
detector will automatically compensate for environmental contaminants and other factors over
time, until the tolerance value has been exceeded. The FACP will signal a trouble condition
when this level has been reached. Refer to the following table for messages and required
action.
Message Description
None/Very Clean No action necessary. The detector readings are near ideal.
Needs Cleaning Clean the detector soon. The detector may cause a false
alarm because it has reached the drift compensation
tolerance value.
Needs Immediate Cleaning Clean immediately! The detector is a false alarm risk. The
drift compensation tolerance value has been exceeded.
E.1 Zones
There are five types of zones that may be listed to a point for CBE purposes.
General Zone A general zone is used to link input and output devices. When an input device activates, any general zone
in its zone map will be active, and any output device that has an active general zone in its map will be
active. General zones can be used as arguments in logic equations.
Zone Z000 is a general alarm zone: those points listing Z000 in their zone map participate in a general
alarm.
The panel will support up to 1000 general zones, designated as Z0 through Z999. General zones can be
used in CCBE applications when a node number is entered before the zone number.
Logic Zone A logic zone consists of a logic equation. Whenever the logic equation becomes true, all output points
mapped to the logic zone will activate.
The panel will support up to 1000 logic zones, designated as ZL1 through ZL1000. Logic zones can be
used in CCBE applications when a node number is entered before the zone number.
Trouble Zone A trouble zone consists of a trouble equation. Whenever the trouble equation becomes true, all output
points mapped to the trouble zone will activate.
The panel will support up to one hundred trouble zones, designated as ZT001 through ZT100. Trouble
zones can be used in CCBE applications when a node number is entered before the zone number.
Special Zone ZF0 An output participates in Presignal with this special zone in its zone map.
ZF1 (Trouble less AC) An ouput programmed to turn on/off if a system trouble - other than an AC
power loss - occurs.
ZF2 (AC Trouble) An output programmed to turn on/off if an AC power loss or a brownout
condition occurs.
ZF3 (Security) An output programmed to turn on/off if a Security input activates.
ZF4 (Supervisory) An output programmed to turn on/off if a Supervisory input activates.
ZF5 Alternate An input programmed to switch from the active detector alarm sensitivities to the
Sensitivity Activation alternate alarm sensitivities when a non-fire point with ZF5 in its CBE activates.
ZF8 A panel output participates in March or Temporal time coding (depending on the
global setting) with this special zone in its zone map.
ZF9 An output programmed to turn on/off if a PreAlarm is active (ALERT, ACTION).
Time, date and holiday functions, which were formerly determined through special zones, are now defined in the panel
programming section of this manual.
E.2 Equations
Logic and Trouble Equations can define complex relationships between input and output devices.
The FACP supports up to 1000 Logic Equations, each designated with a Logic Zone number of
ZL1 through ZL1000. It also supports up to ten Trouble Equations, each designated with a Trouble
Zone number of ZT001 through ZT100. Once created, these equations can be included in
input/output zone mapping.
1. Equations will always begin with a logic function. The function set is listed below.
2. Equations will be a maximum of 80 characters long, including parentheses and commas.
3. Logic and Trouble Equations can have a maximum of 10 logic functions unless a time delay
function is used: a time delay function must be the only function in its equation.
4. Equations are evaluated after all other devices have been evaluated.
5. One logic equation can be used as an argument in another logic equation, or one trouble
equation can be used in another trouble equation, only if the equation used has previously been
evaluated; that is, only zones with a lower number than the zone currently being edited can be
used as arguments.
6. A logic function can have a maximum of 20 arguments (inclusive start and stop address).
7. Maximum for the delay timer is 23 hours, 59 minutes, 59 seconds (23:59:59).
Equations are entered using Point Programming for logic or trouble zones. Refer to these sections
in this manual for instruction. The panel will check for errors after the user has entered the
complete equation. Possible errors are too many or two few parentheses, too many or two few
arguments inside the parentheses, unknown function and unknown device type.
Equations are made up of two basic components: functions (either logic or time delay) and
arguments.
E.2.1 Arguments
Arguments are discrete parts of a logic or time delay function used in a logic or trouble equation.
They can consist of another function, another equation, or any of the the devices listed below.
• If duration time of zero is entered (00.00.00), the equation will evaluate true when the delay
time expires if the argument remains active throughout the delay time period.
• If no duration or delay is specified, then the function will follow the input argument,
indicating true while it is active and false when it is inactive. DEL assumes a value of false
on reset.
The “SDEL” Function
A latched version of the DEL function.
Example: SDEL(HH.MM.SS, HH.MM.SS,L1M140)
• The first HH.MM.SS is the delay time, the second HH.MM.SS is the duration time. If the
argument (L1M140 in the example above) activates, the function becomes true after the
delay time, and will remain active for the duration even if the argument becomes inactive
during either the delay or duration time.
• If delay time of zero is entered (00.00.00), the equation will evaluate true as soon as the
argument (L1M140) activates and will remain that way for the specified duration, even if
the argument becomes inacative during that time.
• If no duration or delay time is specified, then the argument will not deactivate until reset,
even if the argument becomes inactive.
The “TIM” Operator
The TIM function is used to specify activation on specific days of the week or year.
Examples:
TIM(7-11-04) will evaluate as true for 24 hours starting at midnight (00:00:00) on July 11,
2004.
TIM(MO,TU,WE,TH,FR,08:00:00,23:00:00) will evaluate as true at 8:00 AM and remain true
until 11:00 PM (23:00) for the list of days supplied.
TIM(MO,TU,WE,TH,FR,08:00:00) will evaluate as true at 8:00 AM and remain true until
23:59:59 of the current day for the list of days supplied.
TIM(TU,07:45:00,18:30:00) will evaluate as true every Tuesday between 7:45 AM until 6:30
PM.
TIM(MO,TU,WE,TH,FR) will evaluate as true from Monday morning at 12:01 AM until
Friday evening at 11:59:00 PM.
Logic Equation Syntax Example
OR(AND(L1D1,L1D4),AND(L2D6,L2M3,NOT(L2M4)),ANY2(L1M13,L1M14,L1M15))
Equation begins with a logic function - OR
67 Characters (maximum of 80) - includes parentheses and commas.
5 Logic Functions (maximum of 10) - OR, AND, AND, NOT and ANY2.
8 Arguments (maximum of 20 per logic function) - L1D1,L1D4,L2D6,L2M3,L2M4....
The equation contains no spaces.
Evaluating an Equation
To evaluate an equation, start from the innermostpart of the equation and work outwards. For this
equation to evaluate TRUE and thus turn on any output mapped to it, the following conditions must
be met:
OR(AND(L1D1,L1D4),AND(L2D6,L2M3,NOT(L2M4)),ANY2(L1M13,L1M14,L1M15))
for this part to be TRUE for this part to be TRUE for this part to be TRUE
Then all outputs programmed with this equation will be turned ON.
F.1 Overview
The control panel automatically performs a detector initialization routine when a detector is added
or changed.
The detector initialization routine takes approximately 2.5 minutes. During this time, the detector
being initialized does not perform fire protection functions. The LEDs of detectors polled in
FlashScan mode will latch a steady green while initializing, and return to blinking green when
initialization is over.
While initializing a detector, follow these guidelines:
• Make sure the detector is free of residual smoke during detector initialization.
• Do not test a detector during detector initialization.
NOTE: The control panel only performs detector initialization if it senses that a detector was
removed for at least 15 seconds.
WARNING:
If any detector is replaced with a different type of detector (for example, a laser detector is replaced
with a photoelectric detector), the control panel must be programmed immediately with the new
detector Type Code. Failure to do so can cause incorrect control panel operation, including false
alarms.
Step Action
1 Delete the old detector point from FACP programming using the “Delete Point” screen on
page page 57.
3 Enter point programming for this point and change the Type and FlashScan Code Label to
the values appropriate for the new detector. (Refer to “Detector Point” on page 38 for
programming instructions).
NOTE: Do not assign Releasing Type Codes to Panel Circuit module points.
Point Characteristics
Type Code Point Type Latching Activates Device Function
(Y=yes CBE
N=no)
MONITOR fire alarm Y Y Alarm-monitoring device
NC MONITOR fire alarm Y Y Alarm monitoring device, where an open circuit=active. SLC only.
PULL STATION fire alarm Y Y Manual fire-alarm-activating device
SMOKE CONVEN fire alarm Y Y Indicates activation of a conventional smoke detector. An FZM-1 must be used for
alarm verification of a two-wire conventional detector.
SMOKE DETECT fire alarm Y Y Indicates activation of a conventional smoke detector. An FZM-1 must be used for
alarm verification of a two-wire conventional detector
WATERFLOW fire alarm Y Y Monitor for waterflow alarm switch
WATERFLOW S supervisory Y Y Indicates supervisory condition for activated waterflow switch
ACCESS MONTR non-alarm security N Y Used for monitoring building access
AREA MONITOR security Y Y Monitors building access
AUDIO SYSTEM trouble N N Used for monitoring audio equipment (use trouble zones for activations)
EQUIP MONITR non-alarm security N Y Used for monitoring equipment
SECURITY L security Y Y Indicates activation of security alarm
LATCH SUPERV supervisory Y Y Indicates latching supervisory condition
NC SUP L supervisory Y Y Indicates latching supervisory conditon, where an open circuit=active. SLC only.
TRACK SUPERV supervisory N Y Monitors for waterflow tamper switches for alarm points
NC SUP T supervisory N Y Indicates tracking supervisory conditon, where an open circuit=active. SLC only.
SPRINKLR SYS supervisory Y Y Monitors a waterflow device
SYS MONITOR security Y Y Monitors equipment security
TAMPER supervisory Y Y Indicates activation of tamper switch
ACK SWITCH non-alarm N N Performs Acknowledge function
ALLCALL PAGE non-alarm N Y Performs AMG-1 All-call and telephone page functions
DRILL SWITCH non-alarm* N N Performs Drill function, activates silenceable fire outputs
EVACUATE SWITCH non-alarm* N N Performs Drill function, activates silenceable fire outputs
FIRE CONTROL non-alarm N Y Monitors non-fire activations
NON FIRE non-alarm N Y Monitors non-fire activations
NC NON FIRE non-alarm N Y Monitors non-fire activations, where an open circuit=active. SLC only.
PAS INHIBIT non-alarm N N Inhibits Positive Alarm Sequence
POWER MONITR trouble† N N Monitors main and auxiliary power supplies (use trouble zones for activations)
RESET SWITCH non-alarm N N Performs Reset function
SIL SWITCH non alarm N N Performs Signal Silence function
TELE PAGE non-alarm N Y Performs function of Page Button on FFT-7. Allows remote paging to a fire area
TROUBLE MON trouble N N Monitors trouble inputs (use trouble zones for activations)
Blank fire alarm Y Y Monitors for a device with no description
HEAT DETECT fire alarm Y Y Monitors for conventional heat detector
RF MON MODUL fire alarm Y Y Wireless alarm-monitoring device
RF PULL STA fire alarm Y Y Wireless manual fire-alarm-activating device
RF SUPERVSRY supervisory N Y Wireless supervisory-monitoring device
ABORT SWITCH non-alarm N Y Provides an abort function through a monitor module (connected to a UL-listed
abort station) for a releasing zone.
MAN RELEASE fire alarm‡ Y Y Provides a manual release through a monitor module (connected to a UL-listed
pull station) for a releasing zone
MAN REL DELAY fire alarm† Y Y Provides a manual release with a 10-second delay through a monitor module
(connected to a UL-listed pull station) for a releasing zone
SECOND SHOT fire alarm† Y Y Provides a second manual release through a monitor module (connected to a UL-
listed pull station) for a releasing zone
NOTE: Do not assign Releasing Type Codes to Panel Circuit module points.
Label Device/Point
HEAT FST-751/R, FST-851/R
ION FSI-751, FSI-851
PHOTO FSP-751,FSD-751P/RP, FSP-851, FSD-751PL/RPL, FSH-
751
BEAM FSB-200,FSB-200S
RFX SMOKE SDRF-751
LASER FSL-751
PHOTO/HEAT FSP-751T, FSP-851T
ACCLIMATE FAPT-751, FAPT-851
HIGH HEAT FST-851H
MONITOR FMM-1
MINI/DUAL FMM-101,FDM-1
MONITOR
MANUAL STATION FSM-101 (NBG-12LX Series)
ZONE MONITOR FZM-1
CONTROL FCM-1
RELAY FRM-1
TELEPHONE FTM-1
XPIQ BATTERY XPIQ BAT MON
XPIQ GND FLT XPIQ EF MON
XPIQ AC XPIQ AC MON
XPIQ TROUBLE XPIQ GEN MON
XPIQ STROBE XPIQ STROBE
XPIQ SPEAKER XPIQ SPEAKER
XPIQ TELEPHONE XPIQ TELEPHONE
XPIQ MUSIC XPIQ MUSIC
PS MON PS MON
PS CONTROL ACPS CONTROL
PS RELAY ACPS RELAY
RFX MON RFX MON
RFX SUP RFX SUP
LOCAL SETTINGS
LOCAL SETTINGS:SINGAPORE
TROUBLE
LOADING..NO SERVICE
LAKEVIEW GENERAL HOSPITAL
N083
BOOTLOADER
CONTINUE ABORT
I.2 Chicago
The LOCAL SETTING choice of CHICAGO disallows local drill or signal silence.
• The DRILL and SIGNAL SILENCE keys at the panel will not function.
• Annunciator Control Modules, SLC modules, and panel circuits given a drill or signal
silence Mode or Type Code will not allow local drill or signal silence initiation.
• Events must be acknowledged prior to system reset.
This section contains descriptions of terms essential to know when programming the control panel.
Alarm History See History buffer.
Alarm Verification Timer A user-defined global software timer function that can reduce the
number of nuisance alarms. When you select Alarm Verification for a detector, the control panel
delays an alarm signal for a user-specified time period. (The control panel ignores the Alarm
Verification Timer if it detects another alarm during the verification period.)
Argument An argument is a discrete part of a logic function used in a CBE logic or trouble
equation. It can consist of panel/SLC addresses for detectors, modules, panel modules, zones,
special function zones, logic or trouble equations.
Auto Silence Timer A user-defined global software timer that functions like pressing the signal
silence key. The control panel silences all active outputs programmed as silenceable once the timer
has reached the selected time. For example, if 20 minutes is selected, when the timer reaches 20
minutes the control panel turns off all active outputs programmed as silenceable.
Autoprogram A software routine that directs the control panel to identify and automatically load
SLC-connected devices into the program with default values for all parameters. The Autoprogram
Finds and displays all new or missing intelligent detectors and modules--while ignoring devices
already installed in memory--so you can edit default option selections. Typically, you Autoprogram
the control panel as a first step in a new installation, or to add devices.
Control module An addressable module that a) switches power to a Style Y or Style Z NAC; or b)
functions as a Form-C control relay.
CBE (Control-by-Event) A programming method that lets you map inputs and outputs to provide a
variety of output responses based on various initiating conditions (events).
CLIP poll - Classic Loop Interface Protocol - CLIP - is standard polling of each intelligent device
(as differentiated from FlashScan poll, a method of group polling described below).
DCC (Display and Control Center) - Term for a display location, programmed to participate in
DCC, when it has control of Acknowledge, Signal Silence, System Reset and Drill functions.
Drift Compensation An algorithm which permits the maintenance of a constant smoke detector
sensitivity by accounting for environmental contaminants and other factors.
Download A function for loading a system program from a file on a personal computer and storing
the program in system memory of the control panel. Also see Veri•Fire.
FlashScan poll - a patented system (US Patent Number 5,539,389) that enhances the speed of
communication between analog intelligent devices. Communication is in a grouped fashion. When
one of the devices within the group has new information, the panel CPU stops the group poll and
concentrates on single points.
History buffer The control panel maintains a history buffer of the last 4000 events, each with a
time and date stamp. History events include all alarms, troubles, operator actions, and
programming entries. The control panel also maintains a 1000-event Alarm History buffer, which
consists of the 1000 most recent alarm events from the 4000-event history buffer.
latching An attribute of a device that keeps it in an active state until the condition causing the
activation is corrected and the panel is reset.
Missing device A device that exists in a program, but is not found by the control panel during
Autoprogram, typically because the device is disconnected.
Type Code A Type Code is a software function that specifies the function of a detector, control
module, monitor module, transponder point, NAC, or Panel Circuit point. (You can select a Type
Code while programming a point). The Type Code specifies what action the control panel takes
when the point activates. For example, when a monitor module with evacuate as a Type Code
activates, the control panel activates all outputs, as if someone pressed the drill key.
Upload A function for making a copy of a system program and storing the program as a file on a
personal computer. Also see VeriFire™ Tools Programming Utility.
View (Very Intelligent Early Warning) System A smoke detection system, consisting of the
NFS-3030 control panel and LPX-751 laser detectors, that provides very early warning of
smoldering fires.
VeriFire™ Tools Program Utility A software utility for uploading and downloading a system
program between a personal computer and the control panel through the EIA-232 port.
Walk Test A feature that lets a single (qualified) maintenance person to test a fire alarm control
panel and initiating devices without causing the control panel to enter into an alarm state.
Zone Map SLC and panel circuit inputs (detectors and monitor modules) and outputs (control
modules) provide for up to ten zone selections for CBE.
I M
ICM-4RK/ICE-4 48 Main Menu 11, 15
Initial programming Main Power Supply Address 30
Basic procedure 11 Maintenance Warnings 116
Initiating Devices for releasing zones 112 Major changes and additions
Insert (Logic equation screen) 53 Basic procedure 11
Instant Release Circuit Manual Release Delay Switch
Control module configuration example Monitor module configuration example
110 102
To program 110 To program 102
Ion FSI-751, detector sensitivity settings 120 Manual Release Switch
IP Access 20 Monitor module configuration example
IRI Abort Switch 93 101
ISO-X module 140 To program 101
IZM-8RK/IZE-A 47, 48, 50 March Time coding 22, 114
Master password, see Password 12
J Maximum verification count 24
Menu Hierarchy 85
J5 of CPU-3030 30
Module poll 34
Module, Panel Circuit
L Coding 22
Label, point 38, 44, 48 Control 50
Language selection 26 Silenceable 50
LCD-160 82 Switch Inhibit 50
latching 143 Walk Test 50
LCD Programming 26 Zone map 50
LCD programming Extended label 48
Backlight 26 Label 48
Current setting 26 Module Type (Control/Monitor) 48
Factory default setting 26 Monitor 49
Intensity down 26 Alarm Verification 49
Intensity up 26 Custom Action message 49
Language 26 Zone map 49
LCD-160 Download Menu Point addresses 47
Address 81 Type Codes 48
Language 82 Module, SLC
LCM Download Menu 82 Control 46
LCM Local Mode, See Local mode 22 Custom action message 45
Local control 21 Local mode 47
Local mode 22, 40, 45, 47 Silenceable 46
Local Receive mode 21 Switch inhibit 46
Local Settings 23 Walk test 46
Logic equations, editing 52 Zone map 46
Logic Zone 52, 125 Extended label 44
W Delay Time 52
Soak Time 52
Walk Test 46, 50, 70–75, 145
Special Zones 125
Advanced
Audible 71 Trouble 55
Z000 general alarm 46, 50, 119, 125
Basic 71
See also Alter Status 70
Type IDs, modules, that do not participate
46
Warning
Do not rely on Disable to disable releasing
points during.... 66, 89
If you replace any detector with a different
type... 131
The IRI abort switch will only work if it is
pushed before.... 93
When using alarm verification, do not mix
....(IZM-8RK) 47
Warning Sounders, releasing applications 112
Weekly occupancy schedules 31, 40, 42
Wiring Style 34
wiring style, network 19
X
XPIQ power supply 24
Z
Z000 general alarm 118
Zone map
Control module 46, 50
Detector 38, 39
Monitor module 45, 49
Zones
CBE 125
Fixed positions in map
Detectors, position one 39
Detectors, position ten 39
primary zone 38, 97
Sounder/relay bases, position nine 39
General Zone 51
Zone label 51
Logic 52
Add logic function 53
Add point 53
Add Time/Date 53
Delete equation 53
Edit Equation 52
Enter time 55
Logic function 55
Point select 54
Position layout 38, 39
Position one, initial programming 38, 45,
46
Releasing 51, 89–112
Abort Switch 52
Cross Zone 52
www.notifier.com