NFS-320 Installation Manual
NFS-320 Installation Manual
NFS-320 Installation Manual
NFS-320/E/C
Installation Manual
A
Document 52745
01/12/2007 Rev:
P/N 52745:A ECN 06-166
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of Heat detectors do not sense particles of combustion and
smoke detectors, heat detectors, manual pull stations, audible alarm only when heat on their sensors increases at a predeter-
warning devices, and a fire alarm control panel with remote mined rate or reaches a predetermined level. Rate-of-rise
notification capability—can provide early warning of a develop- heat detectors may be subject to reduced sensitivity over time.
ing fire. Such a system, however, does not assure protection For this reason, the rate-of-rise feature of each detector
against property damage or loss of life resulting from a fire. should be tested at least once per year by a qualified fire pro-
The Manufacturer recommends that smoke and/or heat detec- tection specialist. Heat detectors are designed to protect
tors be located throughout a protected premise following the property, not life.
recommendations of the current edition of the National Fire IMPORTANT! Smoke detectors must be installed in the
Protection Association Standard 72 (NFPA 72), manufacturer's same room as the control panel and in rooms used by the sys-
recommendations, State and local codes, and the recommen- tem for the connection of alarm transmission wiring, communi-
dations contained in the Guide for Proper Use of System cations, signaling, and/or power. If detectors are not so
Smoke Detectors, which is made available at no charge to all located, a developing fire may damage the alarm system, crip-
installing dealers. A study by the Federal Emergency Man- pling its ability to report a fire.
agement Agency (an agency of the United States government) Audible warning devices such as bells may not alert people
indicated that smoke detectors may not go off in as many as if these devices are located on the other side of closed or
35% of all fires. While fire alarm systems are designed to pro- partly open doors or are located on another floor of a building.
vide early warning against fire, they do not guarantee warning Any warning device may fail to alert people with a disability or
or protection against fire. A fire alarm system may not provide those who have recently consumed drugs, alcohol or medica-
timely or adequate warning, or simply may not function, for a tion. Please note that:
variety of reasons:
• Strobes can, under certain circumstances, cause seizures
Smoke detectors may not sense fire where smoke cannot in people with conditions such as epilepsy.
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors • Studies have shown that certain people, even when they
also may not sense a fire on another level or floor of a building. hear a fire alarm signal, do not respond or comprehend the
A second-floor detector, for example, may not sense a first- meaning of the signal. It is the property owner's responsi-
floor or basement fire. bility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
Particles of combustion or “smoke” from a developing fire on the proper reaction to alarm signals.
may not reach the sensing chambers of smoke detectors
because: • In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow. A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
• Smoke particles may become “cold,” stratify, and not reach batteries only for a specified time and only if the batteries have
the ceiling or upper walls where detectors are located. been properly maintained and replaced regularly.
• Smoke particles may be blown away from detectors by air Equipment used in the system may not be technically com-
outlets. patible with the control panel. It is essential to use only equip-
• Smoke particles may be drawn into air returns before ment listed for service with your control panel.
reaching the detector. Telephone lines needed to transmit alarm signals from a
The amount of “smoke” present may be insufficient to alarm premise to a central monitoring station may be out of service
smoke detectors. Smoke detectors are designed to alarm at or temporarily disabled. For added protection against tele-
various levels of smoke density. If such density levels are not phone line failure, backup radio transmission systems are rec-
created by a developing fire at the location of detectors, the ommended.
detectors will not go into alarm. The most common cause of fire alarm malfunction is inade-
Smoke detectors, even when working properly, have sensing quate maintenance. To keep the entire fire alarm system in
limitations. Detectors that have photoelectronic sensing excellent working order, ongoing maintenance is required per
chambers tend to detect smoldering fires better than flaming the manufacturer's recommendations, and UL and NFPA stan-
fires, which have little visible smoke. Detectors that have ion- dards. At a minimum, the requirements of NFPA 72 shall be
izing-type sensing chambers tend to detect fast-flaming fires followed. Environments with large amounts of dust, dirt or
better than smoldering fires. Because fires develop in different high air velocity require more frequent maintenance. A main-
ways and are often unpredictable in their growth, neither type tenance agreement should be arranged through the local man-
of detector is necessarily best and a given type of detector ufacturer's representative. Maintenance should be scheduled
may not provide adequate warning of a fire. monthly or as required by National and/or local fire codes and
Smoke detectors cannot be expected to provide adequate should be performed by authorized professional fire alarm
warning of fires caused by arson, children playing with installers only. Adequate written records of all inspections
matches (especially in bedrooms), smoking in bed, and violent should be kept.
explosions (caused by escaping gas, improper storage of
flammable materials, etc.). Limit-C-9-2005
This system meets NFPA requirements for operation at 0-49º This system contains static-sensitive components.
C/32-120º F and at a relative humidity 93% ± 2% RH (non- Always ground yourself with a proper wrist strap before han-
condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful dling any circuits so that static charges are removed from the
life of the system's standby batteries and the electronic com- body. Use static suppressive packaging to protect electronic
ponents may be adversely affected by extreme temperature assemblies removed from the unit.
ranges and humidity. Therefore, it is recommended that this Follow the instructions in the installation, operating, and pro-
system and its peripherals be installed in an environment with gramming manuals. These instructions must be followed to
a normal room temperature of 15-27º C/60-80º F. avoid damage to the control panel and associated equipment.
Verify that wire sizes are adequate for all initiating and indi- FACP operation and reliability depend upon proper installation.
cating device loops. Most devices cannot tolerate more than a Precau-D1-9-2005
10% I.R. drop from the specified device voltage.
FCC Warning
WARNING: This equipment generates, uses, and can Canadian Requirements
radiate radio frequency energy and if not installed and This digital apparatus does not exceed the Class A limits
used in accordance with the instruction manual may for radiation noise emissions from digital apparatus set
cause interference to radio communications. It has been out in the Radio Interference Regulations of the Cana-
tested and found to comply with the limits for class A dian Department of Communications.
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable Le present appareil numerique n'emet pas de bruits radi-
protection against such interference when devices are oelectriques depassant les limites applicables aux appa-
operated in a commercial environment. Operation of this reils numeriques de la classe A prescrites dans le
equipment in a residential area is likely to cause interfer- Reglement sur le brouillage radioelectrique edicte par le
ence, in which case the user will be required to correct ministere des Communications du Canada.
the interference at his or her own expense.
Acclimate Plus™, HARSH™, NIS™, Notifier Integrated Systems™, NOTI•FIRE•NET™, and ONYXWorks™ are all trademarks; and FlashScan®, NION®,
NOTIFIER®, ONYX®, UniNet®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. Echelon® is a registered trademark and
LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are
registered trademarks of the Microsoft Corporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary of General Electric Company.
©Monday, January 15, 2007 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
The installer should be familiar with the following documents and standards:
• NFPA 72 Initiating Devices for Fire Alarm Systems
• NFPA 72 Inspection, Testing and Maintenance for Fire Alarm Systems
• NFPA 72 Notification Appliances for Fire Alarm Systems
Underwriters Laboratories
• UL 38 Manually Actuated Signaling Boxes
• UL 217 Smoke Detectors, Single and Multiple Station
• UL 228 Door Closers - Holders for Fire Protective Signaling Systems
• UL 268 Smoke Detectors for Fire Protective Signaling Systems
• UL 268A Smoke Detectors for Duct Applications
• UL 346 Waterflow Indicators for Fire Protective Signaling Systems
• UL 464 Audible Signaling Appliances
• UL 521 Heat Detectors for Fire Protective Signaling Systems
• UL 864 Standard for Control Units for Fire Protective Signaling Systems
• UL 1481 Power Supplies for Fire Protective Signaling Systems
• UL 1971 Visual Signaling Appliances
• UL 1076 Proprietary Burglar Alarm Systems
• UL 60950 Safety of Information Technology Equipment
Underwriters Laboratories of Canada (ULC)
• Standard CAN/ULC-S527-M99
• CAN/ULC-S524-M91 Standard for the Installation of Fire Alarm Systems
Other
• EIA-485 and EIA-232 Serial Interface Standards
• NEC Article 300 Wiring Methods
• NEC Article 760 Fire Protective Signaling Systems
• Applicable Local and State Building Codes
• Requirements of the Local Authority Having Jurisdiction
• C22.1-98 The Canadian Electrical Code, Part 1
Fire Alarm Control Panel (FACP) and Main Power Supply Installation Document Number
Note: For individual SLC Devices, refer to the SLC Wiring Manual
Power Supplies, Auxiliary Power Supplies & Battery Chargers Document Number
ONYXWorks™ Workstation Hardware & Software Application: Installation and Operation Manual 52342
ONYXWorks™ NFN Gateway (PC Platform) Installation & Operation Manual 52307
ONYXWorks™ NFN Gateway (Embedded Platform) Installation & Operation Manual 52306
NCS ONYX® Network Control Station Manual, Network Version 4.0 & Higher 51658
SCS Smoke Control Manual (Smoke and HVAC Control Station) 15712
CAUTION:
! Information about procedures that could cause programming errors, runtime errors, or equipment
damage.
WARNING:
! Indicates information about procedures that could cause irreversible damage to the control panel,
irreversible loss of programming data or personal injury.
2.1.2 Options
Refer to Section 2.2 “System Components” for descriptions of the various optional modules.
• Optional devices include: NCM-W/F connection to NotiFireNet, UDACT Universal Digital
Alarm Communicator/Transmitter, and ACM-8R remote relay module to increase point
capacity.
• Optional annunciators connected through the EIA-485 interface allow remote system
monitoring.
320door_open.wmf
Figure 2.1 NFS-320/E/C System, Shown with Door Open
(power-limited, supervised)
TB9 - NAC#1
TB6 - NAC#4
details. (Larger images are referenced on these drawings.)
Hot
TB5 - Neutral
TB4 -
CPU320-KAPS.wmf
Alarm Relay
Trouble Relay
shows jumpers, LEDs and switches. See Section 3 “Installation” for larger images and more
13
System Overview
14
JP2 - Cut for 200MA Operation Fault Jumper
NAC
LEDs
System Overview
Additional Options
The NFS-320/E/C control panel provides space for one or two additional option boards to be
installed, as shown in Figure 3.3 on page 21. The NFS-320C fulfills ULC annunciation
requirements; see NFS-320C Canadian Applications Addendum for details. NFS-320/E/C A
variety of compatible annunciators are available with their own backboxes; see Section 2.3,
“Compatible Equipment”.
CAUTION:
! Make sure to install system components in the sequence listed below. Failure to do so can damage
the control panel and other system components.
WARNING:
! This system contains static-sensitive components. Always ground yourself with a proper wrist strap
before handling any circuits. Use static-suppressive packaging to protect electronic assemblies
removed from the unit.
Top two
mounting holes
Location for 1 or 2
option boards
Two lower
mounting holes
are behind
batteries.
CAUTION:
! Unless you are familiar with the placement of components within this backbox, only use the knockout
locations provided for conduit entry.
320_assembly_tech_pubs_5.wmf
reinstalling KDM-R2.
2. Lay the first option board
over the four stand-offs
already installed on the
CPU, so that the holes and
stand-offs align.
3. If attaching a second
option board, use its standoffs to
secure the first option board, then lay
the second option board over the
standoffs. Two sizes of standoffs are
shipped with the option boards; select
standoffs that allow sufficient
320_assembly_tech_pubs_3.wmf
clearance for electronics on the lower
option board.
4. Secure the top option board with four
#4-40 screws (supplied).
5. Re-attach KDM-R2.
CAUTION:
! It is critical that all mounting holes of the NFS-320/E/C are secured with a screw or standoff to insure
continuity of Earth Ground.
NOTE: It may be convenient to field-wire the SLC loop before installing any option boards, and
to make wiring connections on the first option board before installing a second option board in
front of it.
NOTE: See the Noti•Fire•Net Manual and NCM Installation Document for wiring diagrams and
system configuration information. See the BMP-1 Product Installation Drawing if considering
mounting the module behind blank module plate in a dress plate or annunciator backbox.
NOTE: Over-bending fiber-optic cable can damage it. Do not exceed a 3 inch (7.62 cm)
minimum bend radius.
WARNING:
! Several sources of power can be connected to the control panel. Before servicing the control panel,
disconnect all sources of input power including the battery. While energized, the control panel and
associated equipment can be damaged by removing and/or inserting cards, modules, or
interconnecting cables.
3.5.1 Overview
Complete all mounting procedures and check all wiring before applying power. Electrical
connections include the following:
• Primary AC power source – 120 VAC, 50/60 Hz, 5.0 A from line voltage source (with
NFS-320E use 240 VAC, 50/60 Hz, 2.5 A). Overcurrent protection for this circuit must
comply with Article 760 of the National Electrical Code (NEC) and/or local codes. Use 12
AWG (3.31 mm2) wire (maximum) with a 600-volt rating.
• Secondary power source – 24 VDC from batteries, installed in the control panel (or in an
optional battery cabinet). Secondary (battery) power is required to support the system during
loss of primary power.
• External power sources – 24 VDC power for Smoke Detectors (4 wire), NACs, and
Annunciators.
See Appendix B “Electrical Specifications” for details and overall installation guidelines.
KAPS-24-AC.wmf
2. Open the hinged insulating cover on TB1. Ground
(Earth)
3. Connect the service ground to terminal
marked Ground (Earth).
4. Connect the primary neutral line to terminal
marked NEUTRAL and the primary Hot line Figure 3.4 KAPS-24/E:
to terminal marked HOT. AC Power Connections
5. Close the hinged insulating cover over TB1.
CAUTION:
! While checking AC power, make sure batteries are not connected.
Follow the sequence of steps in Section 3.2 “Installation Checklist”, Table 3.1; this is Step 10.
Component Status
Control panel The green AC Power indicator on; the system Trouble indicator on because batteries are not connected.
circuit board
Each option board In an unconfigured system, the yellow Trouble indicator may come on for approximately 10 seconds after
applying AC power.
Each auxiliary power The yellow Trouble indicator comes on because batteries are not connected.
supply
WARNING:
! Battery contains sulfuric acid which can cause severe burns to the skin and eyes, and can destroy
fabrics. If contact is made with sulfuric acid, immediately flush skin or eyes with water for 15 minutes
and seek immediate medical attention.
WARNING:
! Do not connect the Battery Interconnect Cables (P/N 75560 and 75561) at this time. Make this
connection AFTER initial system primary powerup. Follow sequence of steps in Section 3.2
“Installation Checklist”, Table 3.1; this is Step 11.
Batteries are installed in the control panel cabinet TB3 - Battery Connection
or in a separate battery cabinet which can be
mounted below the control panel or up to 20 feet Battery (+) Battery (-)
(6.096 m) away from the control panel, in conduit
in the same room.
Connect the battery as follows (see Figure 3.4
above):
1. Install batteries into bottom of cabinet or into
separate battery cabinet.
2. Connect the red cable from TB3(+) on the Figure 3.5 KAPS-24/E:
KAPS-24/E power supply to the positive (+) DC Power Connections
terminal of one battery.
3. Connect the black cable from TB3(–) on the
KAPS-24/E power supply to the negative (–) terminal of the other battery.
4. Connect the remaining cable between the negative (-) terminal on the first battery to the
positive (+) terminal on the second battery.
24 VDC Resettable Power Circuit (Four-Wire Smoke Detectors). The power supply
provides a single 24 VDC filtered, power-limited, resettable power circuit for devices that require
resettable power (such as four-wire smoke detectors). This circuit is power-limited, but must be
supervised. To provide supervision, install a UL-listed end-of-line power supervision relay (such
as the System Sensor model 1424, or the EOLR-1) after the last device. Connect the power
supervision relay normally open contact in series with an Initiating Device Circuit (IDC). The
four-wire power circuit energizes the power supervision relay. When you reset the system, the
control panel removes power from these terminals for approximately 15 seconds.
Connect external field wires to the power supply terminals TB10 RESET(+) and (–) to provide up
to 1.25 A of current for powering four-wire smoke detectors. See Figure 3.6 above.
24 VDC Non-resettable Power Circuit The power supply provides one 24 VDC filtered,
power-limited, non-resettable power output, capable of up to 1.25 A. Use this circuit to power
devices that require low-noise 24 VDC power (such as Notifier annunciator model ACS-24AT or
the transmitter module TM-4).
Connect external field wires to power supply terminals TB10 NONRESET(+)and(–) to provide up
to 1.25 A of non-resettable current for powering external devices such as annunciators. See
Figure 3.6 above.
CAUTION:
! During system reset, power remains at terminals TB10 NONRESET(+)and(–).
A–
TB9 - NAC#1 A+
B–
UL-listed ELR-2.2K,
B+
1/2 W (supplied)
A–
TB8 - NAC#2 A+
B–
B+
nfs640-nacout.cdr
B+ B– A+ A– B+ B– A+ A– B+ B– A+ A–
A–
TB7 - NAC#3 A+
B–
Unused Circuits Style Y (Class B) Style Z (Class A) B+
Connection Connection
NOTE: Any NAC can be programmed as a releasing circuit, and the releasing circuit must
be supervised; see Figure 4.6–Figure 4.8. For more information, refer to Section 4.5
“Releasing Applications” in this manual and the NFS-320/E/C Programming Manual. Refer to the
Device Compatibility Document for UL-listed compatible releasing devices. Sample connections
for NAC terminals are shown in Figure 3.7. Follow sequence of steps in Section 3.2 “Installation
Checklist”, Table 3.1; this is part of Step 4.
CPU-320-relays.wmf
Security contacts can also be configured as Alarm
contacts. Follow instructions in the VeriFire
Tools online help.
CPU-320-bckalm.wmf
and an alarm is reported by any detector or a monitor
module that has backup reporting enabled, the NAC
will turn on if the corresponding switch was enabled.
The alarm will activate during microcontroller failure
regardless of the settings of switches SW1-SW4.
Figure 3.10 Backup Alarm
• SW1 - NAC#1 Switches
• SW2 - NAC#2
• SW3 - NAC#3
• SW4 - NAC#4
So, for example, if SW1 and SW4 were enabled at the time of an alarm during microcontroller
failure, NAC#1 and NAC#4 would activate. Follow sequence of steps in Section 3.2 “Installation
Checklist”, Table 3.1.
Power-limited Circuits*
Power-
limited
circuits
Maintain vertical
separation where NPL
circuits appear to
“cross”
NPL
Nonpower-
limited
640-2-PWRLMTWIR-ISO2.wmf
circuits
To cabinet-mounted batteries
(nonpower-limited)
NOTE: AC and battery wiring are not power-limited. Maintain at least 0.25 inches (6.35 mm)
between power-limited and non power-limited circuit wiring. Install tie wraps and adhesive squares
to secure the wiring. Use a power-limited source for relay output on terminals
TB5 and TB4.
See Figure 2.2, “CPU-320 and Power-Supply: Wiring Connections” on page 13 to identify
power-limited and non-powerlimited circuits.
NOTE: Drawing is not to scale; proportions and angles are exaggerated to show wire-placement
more clearly.
cpu2-640tb200.wmf
Figure 3.12 EIA-485 Connections
DB-25 Connector
TB12 on Control Panel
(Custom cable kit 90106)
Pin 3 TX
Pin 2 RX
Pin 7 REF
NOTE: You can also use the EIA-232 printer interface with UL-listed information technology
equipment, such as personal computers, to monitor the control panel for supplementary
purposes.
This section contains information on connecting a printer to the control panel and for setting the
printer options.
Connecting a Remote PRN Series Printer
Remote printers require a 120 VAC, 50/60 Hz primary power source. If required for the fire alarm
system configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a
secondary power source (battery backup). Because a secondary power source is not provided, use a
separate Uninterruptable Power Supply (UPS) that is UL-listed for Fire Protective Signaling. You
may use your building emergency power supply, so long as it meets the power continuity
requirements of NFPA 72. Refer to NFPA 72 for further details.
Connect the remote printer to the Control Panel as follows:
1. Connect the three (3) open leads of the custom cable to the TB12 terminal block on the control
panel as shown in Figure 3.13.
2. Plug the DB-25 connector end of the custom cable into the EIA-232 port of the remote printer.
Tighten securely.
CPU-320-prn.wmf
Control Panel
Control
Panel
Table 3.4 shows the standard settings for using the CRT-2 with the NFS-320/E/C; for one instance
where these settings may change slightly see Section 3.11.4 “Connecting Multiple Printers, CRTs,
or CRT/PRN Combination”. The basic settings for using the CRT-2 with NFS-320/E/C are:
• Baud Rate 9600 • Data format 8 1 N • Protocol xon/off.
NOTE: This section covers installation only; for information on how the CRT-2 functions as part
of the fire alarm system, see the NFS-320/E/C Operations Manual.
NOTE: The CRT cannot be connected at the same time as the network.
prncrt-conn.cdr
7 3 2
To EIA-232 port of next
CRT-2 or PRN (female socket shown)
Note: For wire requirements, see Table B.1 in Appendix B “Electrical Specifications”.
Wiring
Maximum wiring distance of an SLC using 12 AWG (3.31 mm2) wire is 12,500 feet (3810 meters)
total twisted-pair for Style 4, Style 6 and Style 7 circuits.
Capacity
The NFS-320/E/C provides one (1) SLC, with a total capacity of 318 intelligent/addressable
devices:
• 01-159 intelligent detectors
• 01-159 monitor and control modules
Units employing multiple detector operation shall include a minimum of two detectors in each
protected space and reduce the detector installation spacing to 0.7 times the linear spacing in
accordance with National Fire Alarm Code, NFPA. For spacing requirements refer to the detector’s
installation instructions.
NOTE: To meet the ten-second response time required by UL 864, 9th edition, when SLC loops
are configured to run in CLIP mode, all input modules must be mapped to address 19 and lower
on both loop one and 2. There are no limits to detectors or output modules.
Installation
This control panel supports one SLC loop, which connects to TB13 on the control panel. For
details on designing, installing and configuring SLC loops, see the SLC Wiring Manual.
SLC B SLC A
nfs640-slcloops.cdr, CPU-320-SLC-TB.wmf
SLC B (output loop)
B+ A+ B- A- TB13 on B+ A+ B- A-
NFS-320/E/C
Style 4 SLC Loops Style 6 SLC Loops
Note: T-Tapping is not allowed on a four-wire SLC.
NOTE: Download operations that change the basic program of the control panel must be
performed by responsible service personnel in attendance at the control panel. After downloading
a program, test the control panel in accordance with NFPA 72.
4.1 Overview
Section 4.2 “NFPA 72 Central or How to install UDACT with the control panel for use as a NFPA Central
Remote Station Fire Alarm System or Remote Station Fire Alarm System (Protected Premises Unit)
(Protected Premises Unit)”
Section 4.3 “NFPA 72 Proprietary How to set up a Protected Premises Unit to communicate with a listed
Fire Alarm Systems” compatible Protected Premises Receiving Unit.
Section 4.4 “Fire/Security How to use the control panel as a combination Fire/Security system,
Applications” including the following:
• Installing a Security Tamper Switch into the cabinet
• Circuit Wiring
NOTE: An NFPA 72 Central Station or Remote Station requires 24 hours of standby power and 5
minutes in alarm.
NOTE: This application can also be done with the TM-4 Transmitter; refer to the TM-4
Transmitter Module installation document for more details.
Ferrite cores
FACP Cabinet P/N 29090
24 VDC EIA-485
Nonresettable power (ACS Mode)
CPU-320-udact.wmf
UDACT in ABS-8RB
(shown with cover removed)
Figure 4.1 Typical Wiring Diagram for a Central Station Fire Alarm System
NOTE: Install a UL-listed 120 ohm End-of-Line resistor (P/N 71244) UDACT TB1 terminals 3
and 4 if this is the last or only device on EIA-485 line.
UDACT
NFS-320/E
Protected Premises Unit
WARNING:
! Damage can result from incorrect wiring connections.
Connect to
J5 “Security Tamper”
320_STS1.wmf
4.4.4 Programming
The control panel can communicate with any number of security devices. To do so, program the
points as follows:
1. Select the address of the module(s) to be used for security.
2. Select the Type Code SECURITY.
NOTE: For detailed instruction on programming Type Codes, refer to the NFS-320/E/C
Programming Manual.
CPU-320-burg.wmf
UL-listed, normally-closed
security switch
FlashScan Monitor Module
WARNING:
! Do not enable the BACKUP option switch for any of the four Notification Appliance Circuits (NACs) if
they are used for releasing functions!
4.5.1 Overview
This control panel can be used for agent release or preaction/deluge control applications. In a
properly configured system with compatible, listed actuating and initiating devices, this control
panel complies with the following NFPA standards for installation in accordance with the
acceptable standard:
Standard Covers
NFPA 12 CO2 Extinguishing Systems
NFPA 12A Halon 1301 Extinguishing Systems
NFPA 13 Sprinkler Systems
NFPA 15 Water Spray Systems
NFPA 16 Foam-Water Deluge and Foam-water Spray Systems
NFPA 17 Dry Chemical Extinguishing Systems
NFPA 17A Wet Chemical Extinguishing Systems
NFPA 2001 Clean Agent Fire Extinguishing Systems
4.5.2 Programming
The control panel supports up to ten releasing software zones. You can map these zones to activate
Control Panel releasing outputs and FCM-1 modules. Program the FCM-1 module for the
appropriate type code according to the chart below:
4.5.3 Wiring
References to wiring diagrams for releasing applications:
To connect Refer to
A releasing device to the control panel. Section 4.5.4 “Connecting a Releasing Device to the Control Panel”.
A releasing device to the FCM-1 Module. Section 4.5.5 “Connecting a Releasing Device to the FCM-1 Module”.
An NBG-12LRA Agent Release-Abort Station. Section 4.5.6 “Connecting an NBG-12LRA Agent Release-Abort Station”.
CPU-320-RELCONN1.wmf
Control
Panel
WARNING:
! Do not enable the BACKUP option switch for any of the four Notification Appliance Circuits (NACs) if
they are used for releasing functions!
IQActuatorsa.wmf
Figure 4.6 Releasing Circuits (Option 1)
IQActuatorsb.wmf
Figure 4.7 Releasing Circuits (Option 2)
IQActuatorsb.wmf
Figure 4.8 Releasing Circuits: Option 3
+
–
– +
Compatible UL-listed
24 VDC releasing device 9 0
6 7 8 9 10
5
8
4
3
11
12 1 Non-resettable
– 7
2
TENS
1 0 1514
13
2 24 VDC Power
6789
Brown Red 6 4
3
5
3 –
+ 5
2
10
4
+
Relconn-fcm.cdr
REL-47K ONES
ADDRESS
LOOP
(Use with Type Code
Rel Ckt ULC, N.C. Supervision
or see Circuit
Relay Contact Power Supervision
Requirement 3.)
Part of EOLR-1 Relay (EOLR-1)
FCM-1
Figure 4.9 Typical Connection of a 24 VDC Releasing Device to the FCM-1 Module
Circuit Requirements When connecting a releasing device to the FCM-1 module, note the
following:
1. Refer to the Releasing Applications appendix in the NFS-320/E/C Programming Manual for
configuration details (such as setting the Soak Timer).
2. For applications using power-limited circuits:
a) Use an in-line supervisory device (P/N REL-47K) with the FCM-1 module. Connect the
in-line supervisory device as shown in Figure 4.9.
b) Program the releasing circuit for Type Code REL CKT ULC.
c) Circuits are supervised against opens and shorts.
3. For applications not requiring power-limited circuits:
a) In-line supervisory devices (P/N REL-47K) are not required; however, the releasing device
circuit is not supervised against shorts.
b) In non-power-limited applications, program the releasing circuit for Type Code
RELEASE CKT.
c) Limited energy cable cannot be used to wire a non-power-limited releasing device circuit.
d) Maintain a 0.25 inch (6.35 mm) spacing between the non-power-limited releasing circuit
device wiring and any power-limited circuit wiring.
WARNING:
! The XP6-C is not listed for releasing applications and cannot be substituted for FCM-1.
Violet Red
+ +
Normal Non-resettable +24 VDC
from main power supply
ELR mode R-47K Release
supervised and
–
NBG640-NBG12LRA.cdr
power-limited 1
FRM-1
6 2 +
C.
5 4
N.C. N.O.
System
Common (–)
24 VDC power
from FACP’s
0
main power supply
24 VDC UL-listed 7-
FCM-1
1 –
releasing device 2
+
6+ 3– –
Brown Red N.C. Supervision 4 +
REL-47K Relay Contact +
(use with Type Code
Rel Ckt ULC)
Power Supervision
Relay (EOLR-1)
NOTE: If using the on-board NACs, see Circuit Requirements for Section 4.5.4 “Connecting a
Releasing Device to the Control Panel” on page 40. If using FCM-1, see Circuit Requirements for
Section 4.5.5 “Connecting a Releasing Device to the FCM-1 Module” on page 42.
WARNING:
! Do not rely on disable/enable software settings to lockout releasing devices.
NOTE: The battery test requires fully charged batteries. If batteries are new or discharged due
to a recent power outage, allow the batteries to charge for 48 hours before testing.
WARNING:
! Batteries contain Sulfuric Acid which can cause severe burns to the skin and eyes and damage to
fabrics.
• If a battery leaks and contact is made with the Sulfuric Acid, immediately flush skin and/or
eyes with water for at least 15 minutes. Water and household baking soda provides a good
neutralizing solution for Sulfuric Acid.
• If Sulfuric Acid gets into eyes, seek immediate medical attention.
• Ensure proper handling of the battery to prevent short circuits.
• Take care to avoid accidental shorting of the leads from uninsulated work benches, tools,
bracelets, rings, and coins.
WARNING:
! Shorting the battery leads can damage the battery, equipment, and could cause injury to personnel.
Quantities List the number of devices powered by the FACP and its power supply. Devices
powered by the Accessories Output (TB9) draw current directly from the panel. Devices powered
by the Panel Output draw current through the fire panel’s connection to the power supply. Use
these quantities to calculate total current draw of each set of devices in calculation columns 1, 2,
and 3.
Calculation Column 1 (Primary, Non-Fire Alarm Current in amps) Add the contents of
calculation column 1 to get the current drawn from the power supply during a non-alarm condition,
with AC power applied. This current draw cannot exceed 3.9 A without an auxiliary power supply.
Calculation Column 2 (Primary, Fire Alarm Current in amps) Calculation column 2 lets
the system designer determine the current load that the power supply must support during a fire
alarm. The total current draw during a fire alarm cannot exceed 7.4 A without an auxiliary power
supply.
Typically, a system should contain capacity to activate all output circuits and relays, and support
fire alarms on no less than 10% of Initiating Device Circuits, subject to the requirements of the
Authority Having Jurisdiction (AHJ).
The Control Panel provides power for Notification Appliance Circuits. Refer to the Device
Compatibility Document for 24 VDC notification appliances that are UL- and ULC-listed for fire
alarm systems.
Calculation Column 3 [Secondary (Battery) Non-Alarm Current] Column 3 lets the
system designer calculate the non-fire alarm current drawn from the secondary source in a non-fire
alarm condition during AC power loss.The non-fire alarm current is required to complete the
standby battery calculations. After summing all current draws, insert the total in Table A.3.
Current
Device Quantity Total Current/Type
(in amps)
Alarm Current, from Table A.2, col 2 =
APS-6R* [ ] X 6 =
Sum Column for Secondary Fire Alarm Load =
NOTE: The Secondary Fire Alarm Load cannot exceed the following:
• 12 A with BAT-12250 batteries (12 V, 26 AH).
• 20 A with BAT-12550 batteries (12 V, 55 AH).
Component Values
Wire size Maximum 12 AWG (3.31 mm2) with 600 VAC insulation
NOTE: If using an auxiliary power supply such as FCPS-24S6/S8 or APS-6R, refer to the
documentation for that equipment.
Batteries
The control panel uses only sealed lead-acid batteries for secondary standby power. Maximum
battery capacity for the KAPS-24/E main power supply is 200 AH. The NFS-320 enclosure
provides space for two 18 AH batteries. Use external battery boxes if the installation requires
larger capacity batteries; see Table A.5, “Selecting Battery and Battery Backbox,” on page 51.
The table below contains battery charger specifications.
Charger Description Specifications
KAPS-24/E An internal battery charger Normal Charge: 27.6 VDC +/- 0.24 VDC
Main Power Supply for 18 AH to 200 AH Charging Current: 2.0 A or 5.7 A (Software selectable)
CHG-120 An external battery charger Dual Rate: High Charge: 28.1 VDC
Battery Charger designed to charge lead-acid Normal Charge: 27.6 VDC
batteries between 26 AH and Charging Current: 4.5 A
120 AH
ACPS-2406 An internal battery charger Normal Charge: 27.6 VDC
Auxiliary for 7AH to 26 AH Charging Current: 1.1 A max (0.750 A typical)
Charger/Power
Supply
NOTE: The Control Panel provides a total of 7.4 A of power in alarm (3.9 A in standby), shared
by all internal circuitry and external provisions (24 V resettable and non-resettable). For power
requirements, refer to the power supply calculation tables in Appendix A.
• Do not power other equipment from the fire alarm branch circuit.
• Run the AC branch circuit wire continuously, without any disconnect devices except for
overcurrent protection, from the power source to the fire alarm control panel.
• Overcurrent protection for the AC branch circuit must comply with Article 760 of the National
Electrical Codes, as well as local codes.
• Use 12 AWG (3.31 mm2) wire with 600 VAC insulation for the AC branch circuit.
Connect the ground terminal (TB1-Earth) to a solid earth ground (a metallic, cold water pipe may
be suitable in some installations). This connection is vital to maintaining the control panel’s
immunity to unwanted transients generated by lightning and electrostatic discharge.
Operating Power: Secondary Power Source (Batteries)
The battery charger is current-limited and can recharge sealed lead-acid type batteries. The battery
charger shuts off when the control panel is in alarm.
NOTE: If running an SLC in conduit with Notification Appliance Circuits, you can reduce
problems by exclusively using electronic sounders (such as the SpectrAlert, SpectrAlert Advanced
or MA/SS-24 Series) instead of more electronically noisy notification appliances (such as
electromechanical bells or horns).
Circuit Distance
Circuit Type
Function
Wire Requirements
(feet/meters) Typical Wire Type*
SLC Connects to Twisted-unshielded pair, 12 to 18 AWG 12,500 ft. (3,810 m) 12 AWG (3.31 mm2)
(power limited) intelligent and (3.31 to 0.82 mm2). 50 ohms maximum per 9,500 ft. (2,895.6 m) 14 AWG (2.08 mm2)
addressable length of Style 6 and 7 loops. 50 ohms per 6,000 ft. (1,828.8 m) 16 AWG (1.31 mm2)
modules. branch maximum for Style 4 loop. 3,700 ft. (1,127.76 m) 18 AWG (0.82 mm2)
or Untwisted, unshielded wire, in conduit or 1,000 ft. (304.8 m) 12 to 18 AWG (3.31 to
outside of conduit. 0.82 mm2)
NOTE: Lightning arresters required on circuits extending between buildings; 999 meter length
maximum to meet UL 60950.
O Supplemental Documentation 8
Switches
Operating Power 53, 54
Backup-alarm 26
Operational Checks 44
switch locations 13, 14
Option boards
Installation steps 20 System
Description of features 10
Output relays
Connections 26, 53 Limitations 11
Options 11
Specifications 53
System current draws 46, 48, 49, 50, 51
P
T
Periodic Testing 44
Power Terminal block locations 13, 14
AC Power Checklist 23 Testing 44
TM-4
AC power connections 23, 24
see TM-4 Transmitter Module Installation
AC specifications 52
Document 21
DC power connections 23, 24
Trouble relays, see Form-C relays 26
Installation steps 22
Power specifications 22, 53
power supervision relay 42, 43 U
power supply 12 UL nonpower-limited wiring requirements 27
Power supply calculations 46, 48, 49, 50, 51 UL Requirements 27
Power-limited Wiring Requirements 27
Printers 31
Installation 28–32
V
PRN series connections 29 VeriFire 33
PRN settings 29
PRN/CRT combination 31 W
Proprietary Security Alarm Applications Wiring
Wiring 38 Proprietary Security Alarm Applications
Protected Premises Unit 34 38
Wire Requirements 54
R
Related Documentation 8
Relays, see Form-C relays 26
Releasing Circuits
Connections 25
Releasing Applications 39–43
Specifications 53
Releasing Device
Connections 40
FCM-1 Connections 42
S
Security relays, see Form-C relays 26
Security Tamper Switch 37, 38
Service 44
SLC
see also SLC Wiring Manual 32
specifications 52
Specifications 52, 53
Standard equipment 11
STS-1, see also Security Tamper Switch 38
Supervisory and Security contacts
configuring as Alarm contacts 26
Supervisory relays, see Form-C relays 26
www.notifier.com