NFS2-3030
Programming Manual
G1
ECN 11-336
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly. Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended. The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
Limit-C1-2-2007
The amount of smoke present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm. Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire. Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood. CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for operation at 0-49 C/32-120 F and at a relative humidity 93% 2% RH (noncondensing) at 32C 2C (90F 3F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27 C/60-80 F. Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Overtightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit. Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his or her own expense. Canadian Requirements This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications. Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
HARSH, NIS, and NOTIFIRENET are all trademarks; and Acclimate Plus, FlashScan, NION, NOTIFIER, ONYX, ONYXWorks, UniNet, VeriFire, and VIEW are all registered trademarks of Honeywell International Inc. Echelon is a registered trademark and LonWorks is a trademark of Echelon Corporation. ARCNET is a registered trademark of Datapoint Corporation. Microsoft and Windows are registered trademarks of the Microsoft Corporation. 2011 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us. Please include the following information: Product name and version number (if applicable) Printed manual or online Help Topic Title (for online Help) Page number (for printed manual) Brief description of content you think should be improved or corrected Your suggestion for how to correct/improve documentation Send email messages to: FireSystems.TechPubs@honeywell.com Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
Table of Contents
Table of Contents
Section 1: General Information................................................................................................ 8
1.1: About This Manual ........................................................................................................................................8 1.2: UL 864 Compliance.......................................................................................................................................8 1.2.1: Products Subject to AHJ Approval......................................................................................................8 1.2.2: Programming Features Subject to AHJ Approval ...............................................................................8 1.3: Related Documents ........................................................................................................................................9 1.4: Introduction to the Control Panel ................................................................................................................10 1.4.1: Features..............................................................................................................................................11 1.5: Navigating Menu and Programming Screens ..............................................................................................11 1.6: Basic Procedure ...........................................................................................................................................12 1.7: Getting Started .............................................................................................................................................12 1.7.1: Password Change...............................................................................................................................12
Table of Contents
Table of Contents
D.2.3: Self-Optimizing Pre-Alarm ............................................................................................................120 D.2.4: Detector Sensitivity ........................................................................................................................120 D.2.5: Cooperative Multi-Detector Sensing ..............................................................................................121 D.3: Pre-Alarm..................................................................................................................................................121 D.3.1: Definition........................................................................................................................................121 D.3.2: Alert Level ......................................................................................................................................121 D.3.3: Action Level ...................................................................................................................................122 D.4: Detector Sensitivity Settings.....................................................................................................................122 D.4.1: How to Select Pre-Alarm and Alarm Sensitivity............................................................................122 D.4.2: To Test Detectors Set Below 0.50% Obscuration per Foot............................................................124 D.5: Detector Status Display.............................................................................................................................124 D.5.1: Detector Maintenance Display .......................................................................................................124 D.5.2: Print a Detector Maintenance Report .............................................................................................125 D.5.3: To Interpret a Detector Status Display or Maintenance Report .....................................................126
NOTE: Information that highlights an important part of the preceding or subsequent text or illustration.
Possible Settings
Yes No Timed NYC AHJ ULI IRI SUP L(DUCTI) SUP T(DUCTI) SUP T(DUCTP) SUP L(DUCTP) SUP L(ION) SUP T(ION) SUP L(PHOTO) SUP T(PHOTO) SUP L(LASER) SUP T(LASER) P/CO (P SUP) No
Yes
ULI IRI
Yes
Related Documents
General Information
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below. Program Feature or Option
AC Fail Delay Timer Regional Settings Yes Yes
Possible Settings
None, or 1-12 hours Singapore Chicago Australia China No Event Trouble Fire Supervisory Security Nonfire Critical Process
Yes
General Information Networking NotiFireNet Manual, Network Version 4.0 & Higher *Note: Also documents some retrofit equipment manufactured under UL 8th edition High Speed NotiFireNet Manual NCM-W/F Installation Document HS-NCM High Speed Network Communications Module Installation Document NCS ONYX Network Control Station, Network Version 4.0 & Higher Manual NCA-2 Network Control Annunciator Manual NCA Network Control Annunciator Manual System Components Annunciator Control System Manual Annunciator Fixed Module Manual ACM-8R Annunciator Control Module Manual LCD-80 Manual LCD2-80 Liquid Crystal Display LCD-160 Manual LDM Series Lamp Driver Annunciator Manual SCS Smoke Control Manual (Smoke and HVAC Control Station) Manual RPT-485W/RPT-485WF EIA-485 Annunciator Loop Repeater DPI-232 Manual TM-4 Installation Document (Reverse Polarity Transmitter) UDACT Manual (Universal Digital Alarm Communicator/Transmitter) ACT-1 Installation Document ACT-2 Installation Document ACT-4 Installation Document ACT-25 Installation Document ACT-70 Installation Document FireVoice 25/50 Series RM-1 Series Remote Microphone Installation Document RA100Z Remote LED Annunciator Document RFX Wireless Interface Manual UZC-256 Universal Zone Coder Manual UZC-256 Programming Manual XP Transponder Manual XP10-M Ten Input Monitor Module Installation Document XP5 Series Manual XP6-C Supervised Control Module Installation Document XP6-MA Six Zone Interface Module Installation Document XP6-R Six Relay Control Module Installation Document XPIQ Audio Transponder Manual
Introduction to the Control Panel Document Number 51584 54013 51533 54014 51658 52482 51482 Document Number 15842 15048 15342 15037 53242 51850 15885 15712 15640 51499 51490 50050 52527 51118 53431 53432 53240 52290 51138 I56-0508 51012 15216 15976 15888 I56-1803 50786 I56-1805 I56-1806 I56-1804 51013
10
General Information
There are two basic configuration options for the NFS2-3030. It can be ordered with: a front display/keypad, which allows programming and viewing options at the panel, or no display/keypad.
This manual gives programming instructions using the front display/keypad. Displayless Mode When there is no keypad/display at the panel, it is controlled by remote annunciators. VeriFire Tools programming is required. The displayless panel has four buttons on its circuit board that are service-level switches for local operation should it become necessary. They are the only buttons, and are clearly marked with ACK for Acknowledge, SIGSIL for Signal Silence, SYSRST for System Reset, and LAMP TEST. These buttons are mainly for installer use: the operator should utilize a remote annunciator for these functions, if possible. The status indicator LEDs on the circuit board are the same as on the display/keypad; refer to the NFS2-3030 Operating Manual for LED descriptions. Refer to VeriFire Tools for information on programming without an NFS2-3030 display/keypad. A PC is required when using VeriFire Tools. Canadian applications must conform to ULC requirements for displays and network control. Refer to the Canadian Applications appendix in this panels installation manual.
1.4.1 Features
Programming features include the following: Ease of use - Field program the control panel without special software skills. Local programming - program directly from the control panel keypad to reduce installation time. PC programming - input long data entry programming information on a PC; transfer programming data between a PC and the control panel. Autoprogram option - automatically detect newly installed, addressable devices, allowing quicker installation. Security - use passwords to control access to the control panel and protect programming. Large display option - 640 character screen, 16 lines x 40 characters
11
General Information
Basic Procedure
When the FACP can not read an address (that is, if the point entered on the screen for processing does not exist) it will display an error screen for several seconds, then return to the screen where the address was entered. The user must check his input and investigate the state of the point.
12
Getting Started
General Information
CHANGE PASSWORD
BACK
Figure 1.1 Change Password Screen Soft Keys MASTER PASSWORD - Press to change the master password USER PASSWORD - Press to change the user password.
NOTE: Only a master can change another password.
Master Password
Press the MASTER PASSWORD Soft Key to display the following screen. Enter a new password that will replace the factory default password: there can be up to eight alphanumeric characters. Press the enter key on the keyboard. RE-ENTER PASSWORD will appear. Reenter the password for verification. Press enter to save the new password.
******** ********
BACK
User Password
Press the USER PASSWORD soft key to display the following screen.
13
General Information
Getting Started
CHANGE USER PASSWORD USER:1 REFERENCE:JOHN ENTER PASSWORD RE-ENTER PASSWORD ******** ********
ACCEPT BACK
Figure 1.3 Change User Password Screen Soft Keys USER: Press this soft key to scroll through the nine user password numbers. When this key is pressed, the rest of the display will update to reflect information for each new record. Stop at the password number that requires entering. MODE: Press this soft key to select the users level of access. Levels are as follows: PROGRAM/ALTER STATUS Gives access to the Program Change Menu and Alter Status Menu. ALTER STATUS Gives access to the Alter Status Menu NONE Gives no access. REFERENCE: Press this key to enter a maximum 20-character alphanumeric label that identifies the user. Press the enter key on the display/keyboard to enter the information. ENTER PASSWORD - Press to enter a new password. Enter up to eight alphanumeric characters, then press enter. RE-ENTER PASSWORD will appear. Retype the password for verification. ACCEPT: After entering all password information and retyping the password at the prompt, press this soft key to save all the password information. Incorrect or Forgotten Password If a password is entered incorrectly, the panel will respond by displaying an INVALID PASSWORD message and a code. The programmer may hit the escape key and re-enter the password correctly. However, if the password has been forgotten, record the code and contact NOTIFIER. After proper authentication, the master password can be determined by deciphering the code. An example of the message that would appear on the display follows: INVALID PASSWORD: 9066-21FS-7D78-5FA4-6163
Code
14
LAKEVIEW GENERAL HOSPITAL SYSTEM NORMAL 11:58:45A TUE JAN 25, 2011 READ STATUS PROGRAM/ALTER STATUS MULTIPLE EVENT LIST HISTORY DISPLAY PRINTER FUNCTIONS BACK
Figure 2.1 Main Menu Screen Soft Keys Pressing the soft keys brings the user to the screens described below.
15
Main Menu
Read Status
16
Section 3: Program
3.1 General Information
The NFS2-3030 operates with two levels of programming: Program, and Alter Status. Program level allows change to the essential control panel functions such as point functions, system functions, and passwords. Program level change requires the master password, or a user password that allows access to the Program level. All password information can be changed with a master password only. Alter Status level allows change to operating parameters, such as detector sensitivity, or time/date, or Walk Test. The master password, or a user password that allows access to the Alter Status level, is required.
NOTE: All events except troubles are annunciated during programming. When an annunciated event occurs, the panel will automatically exit the programming screen and the Event Counts menu screen will appear.
To access the Program level, press the Program/Alter Status soft key on the Main Menu and at the prompt enter a master password, or a user password that allows access to the Program level. The following screen will display.
NOTE: No program menus will display if a user password is entered that has access to Alter Status level only: the Alter Status menu will be the sole menu choice.
LAKEVIEW GENERAL HOSPITAL SYSTEM NORMAL 10:22:34A TUE JAN 25, 2011 PROGRAM/ALTER STATUS DELETE PROGRAM MENU AUTOPROGRAM MENU PANEL PROGRAM MENU POINT PROGRAM MENU BACK
Figure 3.1 Program/Alter Status Screen Press a soft key with the word program in its menu to bring up the associated program menu. When programming the panel for the first time, press the DELETE PROGRAM MENU soft key, which brings up the Delete Program Menu screen (Refer to Figure 3.53). Press the CLEAR ALL PROGRAMMING button, then ACCEPT, to ensure that the panel is set to defaults and clear of programs.
NOTE: Clearing all programs is not necessary when initial programming with a database downloaded from VeriFire Tools.
17
Program
Panel Program
The logical sequence for initial programming is to program the panel parameters first, then to program the individual points through autoprogramming and/or point programming.
PANEL PROGRAM MENU NETWORK PARAMETERS NETWORK MAPPING PANEL SETTINGS PANEL TIMERS LCD DISPLAY ACS PROGRAMMING SUPERVISION MORE BACK
NETWORK PROGRAMMING NODE NUMBER: 000 NODE LABEL: LAKEVIEW GENERAL HOSPITAL STYLE: STYLE 7 CH A. THRESHOLD: HIGH CH B. THRESHOLD: LOW IP ACCESS ACCEPT BACK
18
Panel Program
Program
Soft Keys NODE NUMBER: Enter the network node number of this panel. For standalone NFS2-3030, the network node number will be 000. A valid network node number range is 1-240. Once the soft key has been pressed, the number may be typed in from the keypad, or the Next/Previous Selection special function key on the keypad may be used to toggle through online node numbers. The network node number may be viewed by pressing the Lamp Test special function key longer than five seconds. (Refer to Section 5.1, Version Information, on page 84.) Default: 000 NODE LABEL: Enter the network node label for this panel. This is the label that appears in the System Normal message. Default: <blank> STYLE: Select the wiring style as 4 or 7. Default: style 4 CHANNEL A THRESHOLD, CHANNEL B THRESHOLD: Enter HIGH or LOW, for high or low threshold setting for channel A or B on the network communications module. Default: HIGH IP ACCESS: Press this soft key to bring up the IP ACCESS screen. ACCEPT: Press this soft key to save the information entered on this screen.
IP ACCESS Screen
NOTE: Use of the IP ACCESS feature is subject to the approval of the local AHJ.
This screen allows the programmer to set the IP Access. This setting allows the disabling/enabling of commands, downloads and programming from the Wide Area Network (WAN).
IP ACCESS IP ACCESS: ON
ACCEPT BACK
Figure 3.4 IP Access Screen Soft Keys IP ACCESS: Press the soft key to scroll through the choices. Press ACCEPT at the desired setting. Settings are: ON - IP commands, downloads and programming are allowed. OFF - IP commands, downloads and programming are NOT allowed. (default) TIMED - IP commands, downloads and programming are allowed for a two-hour period, after which the setting will revert to OFF.
NOTE: Enabling IP ACCESS allows downloads over a local area network (LAN) or the internet (Wide Area Network - WAN) using VeriFire Tools through the NotiFireNet Web Server (NWS), or a wide-area enabled NCS through a PC version of NotiFireNet Gateway. Always verify system operation after programming changes are made in this manner.
19
Program
Panel Program
NOTE: The NFS2-3030 can be programmed to monitor events and initiate drill on one (1) additional fire panel and up to four (4) DVCs.
NEXT navigates to the next screen in the sequence. The last screen will not have a NEXT key. BACK will go to the preceding screen in the sequence or to the Node Programming menu if the current screen is the first one in the 15-screen sequence. ACCEPT implements any changes that have been made up to this point and returns the user to the Node Programming menu. AUTO PROGRAM will consult the internal map of which nodes are on the network and automatically set all 240 Nodes according to the map, regardless of which screen is being shown. The results will not be saved to flash until the ACCEPT key is pressed.
Main menu Program/alter status menu Panel program menu Network mapping
001:OFFLINE 003:ONLINE 005:OFFLINE 007:OFFLINE 009:ONLINE 011:OFFLINE 013:OFFLINE 015:OFFLINE AUTO PROGRAM NEXT
NETWORK MAPPING SCREEN 01 OF 15 / 002:OFFLINE /MAPPED 004:OFFLINE / 006:OFFLINE / 008:OFFLINE /MAPPED 010:OFFLINE / 012:OFFLINE / 014:OFFLINE / 016:OFFLINE
/ / / / / / / / ACCEPT BACK
20
Panel Program
Program
PANEL SETTINGS LOCAL CONTROL: YES PIEZO: ON PROPRIETARY SUPERVISING STATION: NO EVENT ORDERING: USA DISPLAY ADDRESS: YES ACCEPT BACK REMINDER MENU MORE
Figure 3.6 Panel Settings (1) Screen Soft Keys LOCAL CONTROL: Press this soft key to toggle between YES and NO. This option disables (NO) or enables (YES) local panel control of the Signal Silence, System Reset, and Drill Fixed Function keys, as well as SIGNAL SILENCE, SYSTEM RESET, and ACKNOWLEDGE soft keys. A setting of NO (disable) turns the panel piezo sounder off, overriding the next field if PIEZO is set to ON. Default: YES
NOTE: A setting of NO (disable) will disable key switch operation.
NOTE: ACS devices programmed for acknowledge, signal silence, system reset and drill are not affected by this setting: these commands will still function at the devices if LOCAL CONTROL is set to NO.
PIEZO:Press this soft key to toggle between OFF and ON. This option enables (ON) or disables (OFF) the panel piezo from sounding when alarms or troubles occur. A setting of ON is overridden if LOCAL CONTROL is set to NO. Default: ON PROPRIETARY SUPERVISING STATION:Press this soft key to enable (YES) or disable (NO) Local Receive mode. When enabled, events and the clearing of events must be handled one at a time: each must be acknowledged. Latching events require a system reset. The panel will override a setting of YES if the Node Number is greater than zero. Default: NO
NOTE: Proprietary Supervising Station does not support standalone mode (direct connect) with a Digital Voice Command.
EVENT ORDERING: Press this soft key to toggle between USA and CANADA ordering priorities. This order is applied to events shown in the Multiple Events List screen. Default: USA
USA Event Order
Fire Security Supervisory Trouble
21
Table 3.1 Event Ordering (2 of 2) DISPLAY ADDRESS: Press this soft key to toggle between YES and NO. Choose YES to display all point address information at the top of event screens and in printouts. Choose NO to suppress address information display and printing. Default: YES REMINDER MENU: Press this soft key to bring up the Reminder Menu screen. ACCEPT: Press this soft key to save the information entered on this screen. MORE: Press this key to progress to the second Panel Settings screen.
POWER MANAGEMENT MODE:OFF DCC PARTICIPATION: NO RAPID ALL CALL: NO DEFAULT SETTINGS MORE ACCEPT BACK
Figure 3.7 Panel Settings (2) Screen Soft Keys LCM LOCAL MODE: Press this soft key to toggle between YES and NO. Enter YES to enable all SLCs to participate in local mode. When enabled, all LCMs will operate together in a limited fashion when communication is lost with the NFS2-3030 CPU. Inputs on LCM loops (and associated LEM loops, if installed) will activate outputs on all loops for those inputs and outputs that have been set with point programming to participate in local mode, and when type codes are the same point type: that is, an input with a fire type code will activate an output with a fire type code. (Refer to Appendix G, Type Codes, on page 138 for point types). Default: NO POWER MANAGEMENT MODE: Select ON to invoke the power management mode to conserve power consumption. In this mode, the number of LEDs that can be turned ON on a particular loop will be limited. A maximum of 30 input device (monitor modules and detectors) LEDs will be allowed ON at a time. No output module LEDs will turn ON. When the limit of 30 LEDs is reached, every time a new LED is turned ON, the oldest LED activation will turn OFF and will poll in red rather than the usual green. Default:OFF
22
Panel Program
Program
DCC PARTICIPATION: Press this key to program the panel for DCC (Display and Control Center) participation. This network function ensures that one location at a time is in command of the Acknowledge, System Reset, Signal Silence and Drill functions. Default: NO
CAUTION: ON SYSTEMS UTILIZING THE DCC FUNCTION, ALL LOCATIONS THAT CAN PARTICIPATE IN DCC SHOULD BE SET TO YES.
RAPID ALL CALL: Set YES to invoke Rapid All Call for XP Series transponder modules. For use when retrofitting an AM-2020/AFP-1010 system that has XPP modules used for audio operation. This setting causes these modules to activate more quickly. Rapid All Call is used with the Speaker type code. Default:NO DEFAULT SETTINGS: Press this soft key to activate default settings for the following:
Program Setting for:
Local Control Piezo Proprietary Supervising Station Event Ordering Display Address LCM Local Mode DCC Participation Power Management Rapid All Call
Default:
YES ON NO USA YES NO NO OFF NO
Table 3.2 Default Settings REGIONAL SETTINGS: Press this soft key to proceed to the Regional Settings screen. Press the soft key to scroll through the selections. The default is that there are no special regional settings. Other settings are explained in Appendix I, Regional Settings. MORE: Press this key to progress to the third Panel Settings screen.
PANEL SETTINGS
SOUNDER BASE SETUP NETWORK DISPLAY MODE:ON DRILL MODE:CUSTOM ACCEPT BACK
23
Program
Panel Program S O U N D E R B A S E S E T U P : Press this soft key to proceed to the SOUNDER BASE SETUP
screen.
N E T W O R K D I S P L A Y M O D E : Press this softkey to enable Network Display Mode for the fire panel. Network Display Mode allows the NFS2-3030 to display network events for up to five mapped network nodes. Refer to Network Display Mode on page 152. D R I L L M O D E : Press this soft key to select between the STANDARD and CUSTOM drill mode
options. CUSTOM drill mode can be used to activate specific output devices when a drill occurs. When using CUSTOM drill mode, Special Function Zone 16 must be programmed into the zone mapping of the devices to be activated during a drill. For more information on Special Zones, refer to Zones on page 130. For more information about DRILL MODE, refer to Appendix C.2, Drill Mode, on page 117.
BACK
CUSTOM TONE SETUP PULSE ON TIME:0.5 PERIOD:1.0 NUMBER OF PULSES:03 TONE OFF PERIOD:1.5 ACCEPT BACK
24
Panel Program
Program
Pulse On Time
Period. Press this softkey to enter the amount of time in second and fraction of a second increments.
P E R I O D : A Period is the length of time designated for a pulse, including Pulse On time and Pulse Off time. The pulse off time is designated by the amount of time left in a Period after the Pulse On time has expired. Press this softkey to enter the amount of time in second and fraction of a second increments. N U M B E R O F P U L S E S : Press this softkey to enter the number of pulses that will occur before
For more information on programming the Intelligent Sounder Base, refer to Detector Point on page 44.
Reminder Menu
Press the Reminder Menu soft key on the Panel Program Menu 1 screen to set the trouble reminder.
ACCEPT BACK
25
Program
Panel Program
Soft Keys TROUBLE REMINDER: Press this soft key to toggle between the two possibilities: YES: Choose this to initiate a daily 11:00AM reminder that there are uncleared troubles in the system. The reminder will appear on the screen and will sound a piezo (if the piezo is enabled). NO: Choose this if no reminder is desired. Default: YES ACCEPT: Press this soft key to save the information entered on this screen.
2 HOURS
Figure 3.13 Panel Timers (Menu 1) Screen Soft Keys VERIFY TIME: Press this soft key to set the Alarm Verification timer. Type in a value of 0-60 (seconds), which will delay initiating devices set for Alarm Verification from signaling for the amount of time entered. If a second alarm occurs while the alarm verification timer is counting, the timer will stop and the alarm will signal immediately. Default: 30
NOTE: This value may not exceed 30 seconds for ULC installations.
MAXIMUM VERIFICATION COUNT: Press and enter a value from 0-20 for a maximum verification count threshold value that applies to detectors set to participate in Alarm Verification. A value of zero produces no verification trouble. When the counter exceeds the threshold value entered, a trouble is generated to the panel. Default: 20 AC FAIL DELAY: Press this soft key to set the timing for the time delay from AC failure to when the trouble is reported. Type in a value of 1-12 (hours), or select NONE. A value of NONE will cause immediate notification. Default: 8
NOTE: AC FAIL DELAY settings other than 1-3 hours for off-premises notification require the approval of the local Authority Having Jurisdiction.
The onboard trouble relay (TB3 on the CPU2-3030) will activate and TM-4s will report according to this setting.
26
Panel Program
Program
UDACTs are notified immediately of AC failure by the panel, regardless of the panels delay setting. Once the UDACT receives notification, it operates according to its own programmed AC Fail Delay reporting schedule. Example: AC Failure occurs at 1:00 p.m. on a panel with an AC FAIL DELAY setting of 8 hours. The UDACT is set for notification after 6 hours
Time
1:00 p.m. 7:00 p.m. 9:00 p.m.
Event
AC Failure. Panel notifies UDACT. Panel and UDACT timers begin countdown to report time. UDACT reports. TM-4 reports, TB3 trouble relay activates.
Table 3.3 AC Fail Delay Example The AMPS-24, ACPS-610, and ACPS-2406 power supplies must be set to an AC FAIL DELAY value of 0 (zero) when used with this panel. SILENCE INHIBIT: Press to enter a value from 0 (disabled) to 5 minutes. This software timer disables the SIGNAL SILENCE key function for the time entered when a fire alarm occurs. The timer starts at the first alarm only; it does not restart with each new alarm. Default: 0 AUTO SILENCE: Press to enter a value of OFF (no Auto Silence Timer), or a value of 10, 15 or 20 minutes. This global software timer functions like pressing the SIGNAL SILENCE key. For example, if a value of 10 is entered, the control panel will silence all active outputs programmed as silenceable after ten minutes. Default: 0FF
NOTE: This value must be 20 minutes for ULC installations.
VERIFY=PREALARM: Press this soft key to enter Yes or No for displaying Prealarm during alarm verification. Default: NO
PANEL TIMERS PAS: OFF PRESIGNAL DELAY: MM:SS DEFAULT TIMERS ACCEPT BACK
Figure 3.14 Panel Timers (Menu 2) Screen Soft Keys PAS: Press to toggle between the choices of OFF or ON for PAS (Positive Alarm Sequence). Refer to Appendix C, Special Zone Outputs for an explanation of this option. Default: OFF
27
Program
Panel Program
PRESIGNAL DELAY: Press to enter a value of 00:00 (OFF) or a value of 1:00 to 3:00 minutes (in the format MM:SS, where MM= minutes, SS=seconds). This feature initially causes alarm signals to sound only in specific areas, monitored by qualified personnel. This allows delay of the alarm for up to 3 minutes after the start of alarm processing. Refer to Appendix C, Special Zone Outputs for further explanation of this option. Default: 3:00 DEFAULT TIMERS: Press this soft key to activate default settings for the following:
Program setting for: Verify Time Max. Verify AC Fail Delay Silence Inhibit Auto Silence Verify=Prealarm PAS Presignal Delay 20 8 hours 0 (disabled) Off No OFF 3 minutes Default: 30 seconds
Table 3.4 Default Timers ACCEPT: Press this soft key to save the information entered on this screen and return to the previous screen.
LCD PROGRAMMING LCD INTENSITY: 50% BRIGHTER DARKER LANGUAGE: ENGLISH BACKLIGHT ON EXCEPT AC FAIL DEFAULT CURRENT ACCEPT BACK
Figure 3.15 LCD Display Screen Soft Keys BRIGHTER: Press this soft key to increase contrast. The intensity will increase by approximately 5% with each press of the key. DARKER: Press this soft key to decrease contrast. The intensity will decrease by approximately 5% with each press of the key. LANGUAGE: Press this soft to choose the language that will display on the LCD. Menu choices are ENGLISH, HEBREW, PORTUGUESE and SPANISH.
28
Panel Program
Program
To change the language display on an LCD-160, refer to Section 5.3.1, LCD-160 Download Menu, on page 86. BACKLIGHT: Press this soft key to select one of the following backlighting options: ON EXCEPT AC FAIL, OFF, or ON. When ON EXCEPT AC FAIL is selected, the backlight will turn off when the power supply experiences AC failure. Default: ON DEFAULT: Press to select the factory default setting (40%). CURRENT:Press to select the intensity that was in effect when the screen was accessed. ACCEPT: Line 5 (which displays LCD INTENSITY: 50% in the figure above) will change value when the INTENSITY soft keys are pressed. Press ACCEPT to save the desired setting.
UDACT and TM-4 communicators, as well as the UZC Zone Coder, are installed on the same EIA-485 ACS circuit as annunciators, and so are included with annunciator programming. The TM-4 occupies one of the 32 annunciator addresses, and the UDACT can occupy one or more of these addresses. The UZC can occupy up to four annunciator addresses, each with 64 points. When the UDACT or UZC expand beyond one annunciator address, 64PT should be used for the subsequent address types, and the annunciator addresses should be sequential. Other than address assignment, there is no ACS point programming for these devices. Refer to the specific device manual for more information.
29
Program
Panel Program
Press the ACS Programming soft key at the Panel Program screen to invoke the following screen. Press the up and down arrow keys on the keypad to navigate through the annunciator addresses. There will be a cursor highlighted at the current annunciator address position.
ACS PROGRAMMING A01:64PT A05:UDACT A09: NO A13: NO A17: NO A21: NO A25: NO A29: NO A02:64SYS A06:96SYS A10: NO A14: NO A18: NO A22: NO A26: NO A30: NO A03:96PT A07:FSCS A11: NO A15: NO A19: NO A23: NO A27: NO A31: NO A04:TM4 A08:UZC A12: NO A16: NO A20: NO A24: NO A28: NO A32:AMG ACCEPT BACK
Figure 3.16 ACS Programming Screen Soft Keys ANNUNCIATOR TYPE: When the cursor is placed at the desired address, press this soft key to scroll through the following list of types. Stop at the appropriate type.
Type 64PT 64SYS 64SVC* 96PT 96SYS 96SVC* 96DCC UDACT TM4 AMG FSCS HVAC UZC 64 point annunciation 64 point annunciation, with first 8 points reserved 64-point service mode for Two Level Bypass 96 point annunciation 96 point annunciation, with first 8 points reserved 96-point service mode for Two Level Bypass 96 point annunciation to be used with multiple Command Centers UDACT, first address. Any additional UDACT annunciator addresses should be programmed as 64PT and be sequential. TM-4 AMG Smoke control modules set for FSCS mode Smoke control modules set for HVAC mode Universal Zone Coder, first address. Any additional UZC annunciator addresses should be programmed as 64PT and be sequential. Used for
*Two Level Bypass: When an ACS board is programmed as a 64SVC or 96SVC type, the operator must enter the Program/Alter Status mode of operation before pressing any push buttons to control points on these boards. If a push button is pressed while not in the Program/Alter Status screen, and no unacknowledged events exist, the password screen will automatically be displayed so the operator can enter the Program/Alter Status mode. AMG Addressing: When using an AMG, the address it occupies (an address of 25 through 32, typically address 32) must be set to annunciator type AMG, and address one must be set to annunciator type 64PT.
POINT PROGRAMMING: Press this soft key to proceed to the ACS Point Programming screen. ACCEPT: Press this soft key to save all the changes made and return to the previous screen (Panel Program).
30
Panel Program
Program
NOTE: The NFS2-3030 supports ACM-24AT/ACM-48A annunciators and their expanders with either 64 or 96 points at an address, as well as ACM-16AT/ACM-32A/LDM-32 annunciators with 64 points at an address.
ACS POINT PROGRAMMING POINT: MODE: SOURCE: NEXT PREVIOUS A27P04 MONITOR N23L01M037 (MODULE) ACCEPT BACK
Figure 3.17 Sample ACS Point Programming Screen Soft Keys POINT: Press this soft key to enter the ACS point number. The format is AxxPyy, where A is the twodigit device address, P is the two-digit point number. Enter a leading zero for one-digit numbers. MODE: Press this soft key to enter the ACS mapping mode. Table 3.5 shows the possible mode choices and descriptions of their functions.
ACS Point Mode NONE CONTROL Function: The point is not programmed. Explanation No messages are sent from or received at this point. LEDs at this point do not light.
will change the state of up to eight control modules The Point Active LED is lit if a corresponding mapped OR (for NFS2-3030 only) up to eight general zones to off point is active. The Status (trouble) LED is on when a or on when its button is pushed. point or zone is in trouble. Selecting this point mode will bring up the Control Point Select screen (refer to Figure 3.18). will show the current status of a specified point or zone. The Point Active LED is lit if the corresponding mapped point or zone is active. The Status (trouble) LED is on if that point or zone is in trouble. If the point has a button, it has no effect when pushed.
MONITOR
31
Program
Panel Program
Explanation
supports telephone functionality when mapped to a Both the Point Active LED and the Status (trouble) LED will telephone point. Press the button to connect the mapped flash if a telephone has been placed in the jack at the mapped point with the telephone station. telephone point. Otherwise, the Point Active LED is lit if the corresponding point or zone is active. The Status (trouble) LED is lit if that point or zone is in trouble. will change the state of a point, zone, or DAA speaker circuit(s) specified through mapping from enabled to disabled, or from disabled to enabled, when its button is pushed. See Caution below this table. The Point Active LED is lit if the corresponding mapped point or zone is active. The Status (trouble) LED is lit only if that point or zone is disabled.
DISABLE
ACKNOWLEDGE will act like an Acknowledge soft key or button on the panel, acknowledging an event when its button is pushed. SILENCE will act like the Signal Silence button on the panel, silencing all silenceable outputs when its button is pushed. will act like the System Reset button on the panel, resetting the panel when its button is pushed.
The Point Active LED is lit when there are any fire alarms in the system. The Status (trouble) LED is lit when there are troubles in the system. The Point Active LED is lit if all silenceable outputs have been silenced. The Status (trouble) LED is lit if not all silenceable outputs have been silenced after the button is pushed. No LED will ever light at this point.
RESET DRILL
will act like the Drill button on the panel, initiating a fire The Point Active LED lights when the button is pushed drill when its button is pushed. and the system has entered the drill state. The Status (trouble) LED will never light.
ENABLE ...will cause the associated input to become an active The Point Active LED is lit if a corresponding mapped PAGING FROM audio source on NotiFireNet. The user may then point is active. The Status (trouble) LED is on when a choose to activate specific PAM points on remote Digital point or zone is in trouble. ___ Voice Commands to use this network input, or to perform a paging function such as ALL CALL from this input. ALL CALL This point will activate ALL CALL. (Speaker Circuits will The Point Active LED is lit if a corresponding mapped turn on according to programming) to a DVC only. point is active. The Status (trouble) LED is on when a Mapping must be to a DVC node. point or zone is in trouble. If an AMG is connected to this panel, ALL CALL can be activated ONLY by the ALL CALL switch on the AMG. Do not program any other annunciators for ALL CALL. ...will, when pressed after a Page Enable, allow PAGE INACTIVE paging from that source. The Special Paging Function map programming at the DVC will receive the page function. ...will, when pressed after a Page Enable, allow Page Evac paging from that source. The Special Paging Function map programming at the DVC will receive the page function. ...will, when pressed after a Page Enable, allow Page Alert paging from that source. The Special Paging Function map programming at the DVC will receive the page function. ....will, when pressed: Notify a DVC in the map format Nxxx,Nxxx,NxxxLyyMzzz or Nxxx,Nxxx,NxxxAyyT to open the FFT-NFN link and turn on the mapped FFT point or riser. A second press will notify the DVC to turn off that FFT point or riser and determine whether the FFT-NFN link should be closed or remain open. Notify a DVC in the map format Nxxx,Nxxx to close or open the FFT-NFN link between two DVCs. The Point Active LED is lit if a corresponding mapped point is active. The Status (trouble) LED is on when a point or zone is in trouble. The Point Active LED is lit if a corresponding mapped point is active. The Status (trouble) LED is on when a point or zone is in trouble. The Point Active LED is lit if a corresponding mapped point is active. The Status (trouble) LED is on when a point or zone is in trouble. The Point Active LED is lit if a corresponding mapped point is active. The Status (trouble) LED is on when a point or zone is in trouble.
PAGE INACTIVE
PAGE EVAC
PAGE ALERT
FFT-NFN
32
Panel Program
Program
Function: The point will show the current state of the CO element for the specified point entered.
Explanation The Point Active LED is lit if a corresponding mapped point is active. The Status (trouble) LED is on when a point is in trouble. This point is specifically used to annunciate the PHOTO/CO detector.
SOURCE: Pressing this soft key will select the SOURCE field and also toggle between display formats if a point value is allowed. Enter a point or zone, or the panels node number if the mode type is a system function such as acknowledge or reset. Up to eight sources are allowed when CONTROL mode is chosen. For ALL CALL, PAGE INACTIVE, PAGE EVAC, and PAGE ALERT modes, enter the node number of the DVC where the source is connected. For TELEPHONE mode, enter the address of the telephone module point using the format NxxXLyyMzzz. Use the format NxxxAyyT (where xxx=the node number and yy = the digital audio amplifier address) for FFTs on risers that have no FTM modules installed. FFT-NFN mode sources: format Nxxx,Nxxx,NxxxLyyMzzz: Telephone control module (NxxxLyyMzzz) preceded by the node numbers of the two DVCs (Nxxx,Nxxx) that will communicate over the FFT-NFN link. format Nxxx, Nxxx: numbers of the two DVCs that will communicate over the FFT-NFN link. format NxxxAyyT: Use this address (N = the DVC node number and A = the DAL device address on the digital audio loop) when no telephone control modules are installed on a DAL devices FFT riser. Refer to the FFT-NFN section of the DVC manual for programming and application examples. ACCEPT: Press this soft key to save the changes to the point displayed. BACK: Press this soft key to exit the screen without saving, and return to the ACS Programming Screen.
33
Program
Panel Program
XXX
XXX
XXX
XXX
XXX
POINT SELECT
ACCEPT
Figure 3.18 Control Point Select Screen Control source field entries may be: SLC modules in the format NxxxLyyMzzz. xxx = FACP node number, yy - the SLC loop number, zzz - module loop address. General zones in the format NxxxZyyy. xxx = FACP node number, yyy = General zone number (Z001 - Z999, not Z000. Zone 0 is not valid).
NOTE: A zone with a node number of zero (0) will be a local zone.
Panel circuit modules in the format NxxxPyy.z. xxx = FACP node number, yy = panel circuit module number, z = panel circuit push button number. Prioritized Audio Matrix (PAM) speaker points, in the format NxxxIyyyyAzzSn. xxx = the DVC node number, yyyy = the input number in the PAM, zz = the DAA address on the Digital Audio Loop (01 through 32), and n = the DAA speaker circuit (1 through 4).
CAUTION: DO NOT MIX GENERAL ZONES WITH OTHER SOURCE TYPES FOR AN ACS CONTROL POINT. PROGRAM UP TO EIGHT GENERAL ZONES OR UP TO EIGHT OTHER CONTROL POINT TYPES.
Soft Keys All soft keys function like they do on the ACS Point Programming Screen.
34
Panel Program
Program
3.2.9 Supervision
From the Panel Program Menu (1), select SUPERVISION to display the following screen.
SUPERVISION MAIN PS AC FAIL ADDRESS: LXXMXXX PRINTER: 80-COLUMN CRT BAUD RATE: 57600 AUXILIARY TROUBLE REPORTING:NO TAMPER INPUT: NO MORE ACCEPT BACK
Figure 3.19 Supervision Screen Soft Keys MAIN POWER SUPPLY AC FAIL ADDRESS: Press to enter the Monitor AC Fail (base plus one) address of the main power supply. Refer to the main power supply manual for complete addressing information. Enter the power supply address and press ACCEPT. The LCD backlight will turn off when this power supply experiences AC failure (see BACKLIGHT in Section 3.2.7, LCD Programming, on page 28). PRINTER: Press to scroll through the types of printer supervision: NONE, 40-COLUMN, 40-COLUMN SUPERVISED, 80-COLUMN, 80-COLUMN SUPERVISED, 40 GRAPHIC, 80 GRAPHIC, 80 GRAPHIC SUPERVISED. The printer will not be active if NONE is selected. If a SUPERVISED selection is made, the printer will be supervised. Default: NONE
NOTE: When changing from an 80-column or 80-column supervised to an 80 graphic or 80 graphic supervised printer (or vice-versa), settings must be changed at the printer. Refer to this panels installation manual for the settings.
CRT BAUD RATE: Press to scroll through CRT baud rates. SUP after the rate indicates supervised. Select from: 4800, 4800 SUP, 9600, 9600 SUP, 19200, 19200 SUP, 38400, 38400 SUP, 57600, 57600 SUP. Default: NONE
NOTE: When LCD-80 Terminal Supervision is on (LCD-80 is selected at the MORE Supervision screen, see Figure 3.20 on page 36), CRT baud rate selections of 19200 and 57600 are disallowed.
AUXILIARY TROUBLE REPORTING: Press to toggle between Yes and No. Choose Yes if a trouble bus cable has been attached at J5 of the CPU2-3030. Default: NO TAMPER INPUT: Press the soft key to toggle between YES, NO, and AKS-1. YES/NO reports (YES) or does not report (NO) a tamper situation at the panel cabinet door (as determined by an STS-1 tamper switch connected as shown in this panels installation manual).
35
Program
Panel Program
AKS-1 should be selected when there is an AKS-1 key switch connected to the panel cabinet door (which allows the operator to use Signal Silence, Reset, Drill and Acknowledge functions when a key turns the lock to Enable). Default: NO MORE: Press to bring up the second supervision screen. ACCEPT: Press to save changes and return to previous menu.
SUPERVISION
TERMINAL:LCD-80
ACCEPT BACK
Figure 3.20 MORE Supervision Screen TERMINAL: Select NONE or LCD-80. (Default: NONE.) When LCD-80 is selected, LCD-160 programming is not allowed.
NOTE: When LCD-80 Terminal Supervision is on, CRT baud rate selections of 19200 and 57600 are disallowed.
36
Program
PANEL PROGRAM MENU PASSWORD CHANGE WEEKLY OCCUPANCY SCHEDULES REMOTE DISPLAY MENU LOOP CONFIGURATION CUSTOM ACTION MESSAGE BACK EVENT LOGGING HOLIDAY MENU
Figure 3.21 Panel Program Menu 2 Screen Soft Keys Press a soft key to bring up the associated menu.
WEEKLY OCCUPANCY SCHEDULE WEEKLY OCCUPANCY SCHEDULE: SUNDAY , MONDAY 08:00-12:00, TUESDAY 08:00-12:00, WEDNESDAY 08:00-12:00, THURSDAY 08:00-12:00, FRIDAY 08:00-12:00, SATURDAY 08:00-12:00, HOLIDAY , 10 13:00-18:00 13:00-18:00 13:00-18:00 13:00-18:00 13:00-18:00 ACCEPT BACK
Figure 3.22 Weekly Occupancy Schedule Screen Use the arrow keys on the keyboard to navigate between occupancy time fields: use the keypad to type in the time values.
NFS2-3030 Programming Manual P/N 52545:G1 06/16/2011 37
Program
Soft Keys WEEKLY OCCUPANCY SCHEDULE: Press this soft key to toggle between schedules 1 - 10. A value of zero indicates no schedule. ACCEPT: Press this to save changes made on the screen.
D01:YES D02:NO D03:NO D05:NO D06:NO D07:NO D09:NO D10:NO D11:NO D13:NO D14:NO D15:NO D17:NO D18:NO D19:NO D21:NO D22:NO D23:NO D25:NO D26:NO D27:NO D29:NO D30:NO D31:NO INSTALL REMOTE DISPLAY POINT PROGRAMMING
BACK
Figure 3.23 Remote Display Menu Screen Soft Keys INSTALL REMOTE DISPLAY: To install a remote display, press the arrow keys to place the cursor on the line next to the remote display address to be installed. Press this soft key until YES displays. Default:NO POINT PROGRAMMING: Once a display has been installed, press this soft key to program the display point.
38
Program
POINT LABEL EAST WING HALLWAY LOCAL CONTROL:YES NEXT SELECTION PREVIOUS SELECTION ACCEPT BACK
Figure 3.24 Remote Display Point Programming Screen Soft Keys DISPLAY POINT: Press this soft key to bring the cursor to the underlined field. Use the keypad to type in the desired display address. POINT LABEL: Press this soft key to bring the cursor to the underlined label field. Type in a label of up to 40 characters that will appear in trouble messages. LOCAL CONTROL: Press to toggle between YES and NO. A setting of YES enables local control at the remote display.
ACCEPT BACK
39
Program
Soft Keys LOOP SELECTION: Pressing this soft key will invoke the cursor at the underlined field. Enter the loop number desired (01 through 10) in the yy of the Lyy format. NEXT/PREVIOUS SELECTION: Press either key to go forward or back through the loop selections. ACCEPT: Press to proceed to the Loop Point Programming screen.
Loop Programming
LOOP CONFIGURATION INSTALLED: YES DETECTOR POLL: CLIP MODULE POLL: CLIP RAPID POLL: ENABLED WIRING STYLE: 6 ACCEPT BACK BLINK MODE: _ON
Figure 3.26 Loop Programming Screen Soft Keys INSTALLED: Press this soft key to choose YES or NO, depending on whether an SLC is installed at this address. DETECTOR POLL: Press to select loop-polling mode. (See note below.) MODULE POLL: Press to select loop-polling mode. (See note below.)
NOTE: FlashScan and CLIP Mode Most FlashScan devices can be programmed to run in either CLIP or FlashScan mode. The types cannot be mixed on a loop: for example, if Loop 1 is programmed with a FlashScan module poll, CLIP modules may not be used on that loop. A detectors LEDs will light a steady green for several seconds while it is subjected to a detector test during FlashScan polling. Each detector is tested this way on a regular basis. During the short time the LEDs are on steady, the detector is not providing fire protection.
RAPID POLL: For CLIP mode only - enable or disable Rapid Poll for CLIP. This feature will poll the first 20 modules more often to speed response on manual pull stations. WIRING STYLE: Press to select the NFPA wiring style (4 or 6) of the loop. If Style 6 is entered when the wiring is Style 4, a trouble message will be generated at the panel. BLINK MODE: Press to enable (ON) or disable (OFF) detector LED blinking for this loop. If the Loop is configured in FlashScan mode with Blink Mode enabled, all detector and module LEDs will remain OFF. If the loop is configured in CLIP mode with Blink Mode enabled, the LEDs for detectors and monitor modules will remain OFF while the control modules operate normally.
40
Program
CUSTOM ACTION MESSAGE CUSTOM ACTION MESSAGE: 001 MESSAGE Edit Custom
VIEW
BACK
Figure 3.27 Custom Action Message Screen CUSTOM ACTION MESSAGE:Enter a number with a value of 001 to 100 to display the corresponding Custom Action Message, or to add or edit a message. MESSAGE: This soft key appears after VIEW is pressed.Press to enter/edit a custom message in the four lines indicated. The message may be up to 160 characters. VIEW: Press this soft key to view the message that corresponds to the number entered in the underlined field. ACCEPT: Press to save any change made to the message and return to the previous screen.
NOTE: A printout of all the messages may be obtained by entering the PRINT PROGRAMMING MENU (2) and pressing the CUSTOM ACTION MESSAGES soft key.
41
Program
ACCEPT BACK
Figure 3.28 Event Logging Screen Press the appropriate softkey to choose event logging (YES) and no event logging (NO). When YES is chosen, the activations are logged into history and printed.
HOLIDAY MENU MM/DD/YY 01 02 03 04 05 01/01/** 05/28/08 07/04/** 12/03/08 12/25/** ACCEPT BACK
ANY YEAR
42
Point Program
Program
The cursor will appear in the date fields, and may be moved using the keyboard arrow keys. Type to add/edit any holiday dates. Soft Keys ANY YEAR: Press to place asterisks in the YY section of the field. An asterisk denotes any year. NEXT/PREVIOUS SELECTION: Press to view the next or previous group of five holidays. ACCEPT: Press to save changes to the date fields and to return to the Panel Program Menu.
ACCEPT BACK
Figure 3.30 Point Program Menu Soft Keys POINT SELECT: Press until the desired point type appears. The types - DETECTOR, MODULE, GENERAL ZONE, LOGIC ZONE, TROUBLE ZONE, ACS BOARD, or DAA or DVC - appear in the parenthesis after the point formats. Enter the desired point address in the format field. Formats are illustrated in Table 3.6.
Type DETECTOR MODULE LyyDzzz LyyMzzz Address Format L=Loop, yy=Loop number (1-10) D=Detector, zzz=Detector address (1-159) L=Loop, yy=Loop number (1-10) M=Module, zzz=Module address (1-159) Z=Zone, yyy=Zone number (0-999) ZL=Logic Zone, yyyy=Logic Zone number(1-1000) A=Annunciator, Custom label R=Releasing Zone, yy=Releasing Zone number (00-09) ZT=Trouble Zone, yyy=Trouble Zone number (1-100) N = Node, xxx=DVC or DVC-EM Node number, AA = DAA Audio Amplifier, yy=DAA address (01 through 32). Note: When yy=00, the address format is the DVC or DVC-EM address.
GENERAL ZONE Zyyy LOGIC ZONE ANNUNCIATOR ZLyyyy Axx + Custom Label
43
Program
Point Program
ACCEPT: Press to progress to the appropriate screen, based on the type of point selected. NEXT/PREVIOUS SELECTION: Press to scroll backward or forward to the next or previously installed point.
ZONE MAP: Z003, Z104, Z105, Z106, Z107, Z110, Z114, Z115, Z116, Z117
Figure 3.31 Detector Point Programming Screen The point address is displayed in line 3 of this screen. Existing point information is displayed in the fields. Soft Keys TYPE: Press this soft key to scroll through the point type choices: stop at the appropriate selection. If a new point is being added, no other field will be displayed until TYPE: is entered and the ACCEPT soft key is pressed. At this point, the rest of the fields will appear. FLASHSCAN CODE LABEL: Press to scroll through a list of FlashScan Codes. Stop when the appropriate label appears (Table G.4 on page 142 for codes and descriptions). If the detector is not a FlashScan type, choose NONE. POINT LABEL: Press this soft key to place the cursor at this field. Type in a 20-character maximum point label that will appear in message formats. If no entry is made, the field will default to the point address. EXTENDED LABEL: Press to place the cursor at this field. Type in a 12-character maximum extended label to further define the location or nature of the point. ZONE MAP: Displays the zones mapped to this point. During initial programming, zone map position one for each detector is set to Z0YY, where YY represents the loop number where the detector resides. In Figure 3.31 above, zone position one has a value of Z003 (YY = 03). The detector in the example resides on loop 3. To add or delete zones for this point, press this soft key to progress to the Detector Zone Map screen. MORE: Press this soft key to progress to the next detector point programming screen.
44
Point Program
Program
ACCEPT: Press to accept changes. If the user is adding a point, pressing this soft key after entering the TYPE field will display all the other fields.
Zone Map
The Detector Zone Map screen will display when the ZONE MAP soft key is pressed at the Detector Point Programming screen.
Zone Map Position 1 2 3 4 5 6 7 8 9 10
ZONE Z003, Z187, Z234, ZXXX ZXXX ZXXX ZXXX ZXXX ZXXX ZXXX
DETECTOR ZONE MAP L03D123 SELECTION (ZONE) (ZONE) (ZONE) (UNMAPPED) (UNMAPPED) (UNMAPPED) (UNMAPPED) (UNMAPPED) (UNMAPPED) (UNMAPPED)
UP DOWN
ACCEPT BACK
Figure 3.32 Zone Map (Detector Point) Screen When programming Zone Map for detectors, certain zone map positions are used for specific functions:
Zone Position: 1 3 4 Specific Function: Use to link zone label to detector and for group zone disable. For Photo/CO detector only-Activates when the photo element of the Photo/CO detector activates. For Photo/CO detector only-Activates when the CO element of the Photo/CO detector activates. (Map the zone in this location to one of the Aux Controls of the intelligent sounder bases in order to play the Temp-4 tone for CO Alarms.) For Photo/CO detectors only-Activates when the Photo/CO detector reports a CO Pre-Alarm. Use to activate sounder/relay bases of FlashScan detectors. Use for detectors set to Prealarm, Action
5 9 10
Table 3.7 Zone Position Special Functions The point address will appear in line 3 of the screen. Refer to Appendix E, CBE: Zones and Equations, on page 130, and Appendix C, Special Zone Outputs, on page 116 in this manual for more information about zones and how they apply to Control-By-Event.
45
Program
Point Program
Soft Keys ZONE MAP: A detector may be mapped to up to ten general, releasing, or special zones. There are ten positions available for mapping; positions 1, 9 and 10 have additional functionality. (Refer to Figure 3.32) Position 1 - Use this position to link the 20-character zone label to the detector. The zone label will appear after the 20-character label and 12-character extended label, providing a total of 52 characters to describe an event. This position is checked when a group zone disable command is issued. If the zone number in the group zone disable command matches the zone number in the first position of the zone map, the detector point will be disabled. Position 9 Use this position to activate the sounder/relay base of a detector. When this position is mapped to the same zone as Position 10, the sounder or relay base will be activated when the detector goes into prealarm (Action). Use this position to activate the sounder base of a detector using a general or a logic zone. When a general or logic zone activates, the panel is searched for any detector with the same zone mapped in its 9th position. The sounder base of any FlashScan detector that matches the search will activate. Position 10 - Use this position to map detectors with an Action Prealarm setting. The zone in the tenth position will activate when the detector reaches its Prealarm threshold; no other zones in this detectors zone map will activate. Move the cursor with the keyboard arrow keys to the appropriate zone map position, then select the type of zone by pressing the NEXT SELECTION (+) key until the desired zone type appears. Type in a zone number to map the detector to it. ACCEPT: Press to save entries made on this screen and return to the Detector Point Programming screen.
DETECTOR POINT PROGRAMMING L03D123 CUSTOM ACTION MESSAGE:010 ALARM VERIFICATION: OFF LOCAL MODE: OFF WEEKLY OCCUPANCY SCHEDULE:10 MULTI-DETECTOR: D100, D105 SENSITIVITY MORE ACCEPT BACK
46
Point Program
Program
Soft Keys CUSTOM ACTION MESSAGE: Displays the custom action message number (a value of one through 100). The default value is 0 (no message). Press this soft key to progress to the Custom Action Message screen (Figure 3.34) to view the message or to choose a different message for viewing when this point activates. (To create a new custom action message, refer to Section 3.3.5, Custom Action Message, on page 41.) ALARM VERIFICATION: Press this key to determine the devices participation in Alarm Verification. Choosing Yes will set the device participation to the values entered at the Panel Timers screen (Figure 3.13). LOCAL MODE: Press to toggle between Local Mode (ON) or no Local Mode (OFF). When there is a communication loss between the panel and its LCM/LEMs, SLC devices that have been selected for Local Mode participation (ON) will continue to function across all the panels SLCs in a limited manner as follows: input points will activate output points of the same Type Code point type designations. For example, SLC inputs with fire point types will activate SLC outputs with fire point types. Refer to Appendix G, Type Codes, on page 138 for type code point types. All SLC detector types can participate in local mode.
NOTE: The panel setting LCM LOCAL MODE must be set to YES for local mode to work at the device level.
SENSITIVITY: Press to proceed to the Detector Sensitivity screen. WEEKLY OCCUPANCY SCHEDULE: To choose an existing weekly occupancy schedule, press this soft key to proceed to the Detector Occupancy Schedule screen. Refer to Section 3.3.2, Weekly Occupancy Schedule, on page 37 for information on how to set up a schedule. MULTI-DETECTOR: This detector can be linked with up to two detectors at other addresses on the same loop in cooperative multi-detector sensing if entries are made in these fields. The detectors need not be sequential in their addresses. Refer to the section on Cooperative MultiDetector Sensing in Appendix D, Intelligent Sensing Applications for a description of this function. MORE: Press this soft key to progress to the next detector point programming screen.
CUSTOM ACTION MESSAGE: 001 Custom Action Message Displayed here. ACCEPT VIEW BACK
47
Program
Point Program
Soft Keys CUSTOM ACTION MESSAGE: Enter the number of the Custom Action Message to be displayed during alarm conditions for this point (refer to Figure 3.27 on page 41 for an example). VIEW: Press this soft key to view the message associated with the number entered. ACCEPT: Press to save the entries made on this screen.
Sensitivity
Detector sensitivity levels for alarm and prealarm are set at this screen, which displays when the SENSITIVITY soft key is pressed at the Detector Point Programming (2) screen.
DETECTOR SENSITIVITY L03D123 OCCUPIED SENSITIVITY ALARM - 7 OCCUPIED SENSITIVITY PREALARM - 5 UNOCCUPIED SENSITIVITY ALARM = 3 UNOCCUPIED SENSITIVITY PREALARM = 3 ACCEPT BACK
ALARM SENSITIVITY TABLE 1= 0.50% 4= 1.19% 7= 1.89% 2= 0.73% 5= 1.43% 8= 2.12% 3= 0.96% 6= 1.66% 9= 2.35%
Figure 3.35 Detector Sensitivity Screen The control panel provides nine levels of Prealarm and Alarm in percent per foot obscuration, with the following two exceptions: for heat detectors, the settings are in degrees Centigrade. for beam detectors, there are only six levels of Alarm. There is no Prealarm for beam detectors in CLIP mode. for Intelliquad FSC-851 detectors, there are only six levels of Alarm and Prealarm for FlashScan mode, The sixth level is a fixed 135oF, and it is not available in CLIP mode.
Alarm sensitivity settings range from one to nine, with one representing the most sensitive alarm level and nine the least sensitive. Prealarm sensitivity settings range from zero to nine. Zero indicates no prealarm. A value of one can be a self-optimizing setting where the control panel selects a suitable prealarm level for the detector. Values one or two through nine represent decreasing sensitivity, with nine being the least sensitive. Refer to the section Detector Sensitivity Settings in Appendix D, Intelligent Sensing Applications for a full description and a table of the nine sensitivity levels by detector type. Soft Keys OCCUPIED SENSITIVITY ALARM: OCCUPIED SENSITIVITY PREALARM: UNOCCUPIED SENSITIVITY ALARM: UNOCCUPIED SENSITIVITY PREALARM: Press the soft key next to these setting categories to enter values as described above.
48
Point Program
Program
ALARM SENSITIVITY TABLE: This table will toggle from ALARM to PREALARM based on which sensitivity value is being entered. The table will display the values for this type of detector.
Detector Occupancy Schedule
DETECTOR OCCUPANCY SCHEDULE WEEKLY OCCUPANCY SCHEDULE: SUNDAY MONDAY 08:00-12:00, TUESDAY 08:00-12:00, WEDNESDAY 08:00-12:00, THURSDAY 08:00-12:00, FRIDAY 08:00-12:00, SATURDAY 08:00-12:00, HOLIDAY UNOCCUPIED 10 13:00-18:00 13:00-18:00 13:00-18:00 13:00-18:00 13:00-18:00 ACCEPT BACK
Figure 3.36 Detector Occupancy Schedule Screen Soft Keys WEEKLY OCCUPANCY SCHEDULE: Press this soft key to place the cursor at the underlined field. There can be up to ten Weekly Occupancy Schedules. Enter a value of zero through ten. Zero indicates no schedule is applied, and occupied detector sensitivity values are used. ACCEPT: Press this key to accept the change made and return to the previous screen.
DETECTOR POINT PROGRAMMING L03D123 LOW TEMP ENABLE: YES PREALARM:ALERT SILENCEABLE:NO INTELLIGENT SOUNDER:YES SOUNDER BASE SETUP ACCEPT BACK CO PRE-ALARM: YES
Figure 3.37 More Detector Point Programming (3) Screen Soft Keys LOW TEMP ENABLE: Press this softkey to select YES or NO to enable the Low Temperature Warning for the PHOTO/CO detector. This field is only available when programming a PHOTO/CO smoke detector.
49
Program
Point Program
PREALARM: Press this softkey to select ALERT or ACTION for the Prealarm function. Refer to the section on Prealarm in Appendix D, Intelligent Sensing Applications for a description of Alert and Action. SILENCEABLE: This field determines whether the user can manually silence a detectors activated sounder/relay base. Values are as follows:
NO YES - RESOUND FIRE YES - RESOUND SUPERV YES - NO RESOUND Not manually silenceable Silenceable, resound on fire alarm events Network and Local Resound
Silenceable, resound on supervisory events Network and Local Resound Silenceable, does not resound
NOTE: In network applications, specific nodes can be excluded from having the ability to initiate a resound on the local fire alarm panel. This is programmable via VeriFire Tools. Refer to the VeriFire Tools help file.
INTELLIGENT SOUNDER: Press this softkey to select YES if an Intelligent Sounder Base is installed for this detector. SOUNDER BASE SETUP: Press this softkey to proceed to the Sounder Base Setup screen. This option will only be available if the INTELLIGENT SOUNDER is set to YES. CO PRE-ALARM: Press this softkey to select YES or NO to enable the CO Prealarm function for the PHOTO/CO smoke detector. This field is only available when programming the PHOTO/CO smoke detector.
Sounder Base Setup
SOUNDER BASE SETUP L03D123 AUX TONE 1:TEMP-3 AUX TONE 1 CONTROL:ZL0040 AUX TONE 2:TEMP-4 AUX TONE 2 CONTROL:ZLOO41 VOLUME:HIGH ACCEPT BACK
50
Point Program
Program V O L U M E : Press this softkey to select L O W or H I G H for the intelligent sounder base volume level.
For CUSTOM TONE SETUP, refer to Custom Tone Setup Screen on page 24.
MODULE POINT PROGRAMMING L03M123 MODULE TYPE: MONITOR TYPE CODE LABEL:HEAT DETECT FLASHSCAN CODE LABEL: MONITOR POINT LABEL: MONITOR L03M123 EXTENDED LABEL: MORE ACCEPT BACK
Figure 3.39 Module Point Programming (1) Screen Soft Keys MODULE TYPE: Press the soft key to toggle between CONTROL and MONITOR. TYPE CODE LABEL: Press this soft key to scroll through the point type choices: stop at the appropriate selection. FLASHSCAN CODE LABEL: Press this soft key to scroll through the point type choices: stop at the appropriate selection (Table G.4 on page 142 for codes and descriptions). Choose NONE if the point type is not FlashScan.
NOTE: If the point is not installed, MODULE TYPE:, TYPE CODE LABEL:, and FLASHSCAN CODE LABEL: must be entered before any entries can be saved using the ACCEPT key.
POINT LABEL: Press this soft key to place the cursor at this field. Type in a 20-character maximum point label that will appear in message formats. If no entry is made, the field will default to the point address. EXTENDED LABEL: Press to place the cursor at this field. Type in a 12-character maximum extended label to further define the location or nature of the point. MORE: Press to proceed to the next screen for more point programming. ACCEPT: Press to save entries made on this screen.
51
Program
Point Program
MODULE POINT PROGRAMMING L03M123 CUSTOM ACTION MESSAGE:020 ZONE MAP: Z003 , Z104 Z110 , Z114 , Z105 , Z115 , Z106 , Z116 , Z107 , Z117
ALARM VERIFICATION: OFF LOCAL MODE: OFF 4-20 DEVICE SETUP ACCEPT BACK
This menu selection will appear when 4-20MA has been entered as the modules Type Code Label. Zone Map Position 1 - Use for group zone disable participation.
Figure 3.40 Module Point Programming Screen 2 (Monitor) Soft Keys CUSTOM ACTION MESSAGE: Displays the custom action message number (a value of one through 100). The default value is 0 (no message). Press this soft key to progress to the Custom Action Message screen (shown in Figure 3.34) to view the message or to choose a different message for viewing when this point activates. To create a new custom action message, refer to Section 3.3.5, Custom Action Message, on page 41. ZONE MAP: Displays the zones mapped to this point. During initial programming, zone map position one for each monitor module is set to Z0YY, where YY represents the loop number where the module resides. In Figure 3.40 above, zone position one has a value of Z003 (YY = 03). The module in the example resides on loop 3. To add or delete zones, press this soft key to proceed to the Module Zone Map screen. Refer to Zone Map on page 45 for an illustration and explanation of the Detector Zone Map screen. The Module Zone Map screen is the same except that Module replaces Detector in the title and the module address appears instead of the detector address. Up to ten general, releasing or special zones may be mapped to a monitor module: none of the zone map positions are fixed. Positions 1 and 3 - 7 have additional functionality. Position 1 - This position is checked when a group zone disable command is issued. If the zone number in the group zone disable command matches the zone number in the first position of the zone map, the module point will be disabled. Positions 3 - 7 - For the FMM-4-20 module only. These positions are assigned to FMM-4-20 threshold levels 1 - 5 respectively. (Threshold levels are user-programmed. Refer to FMM-420 Monitor Module Programming on page 53.) Each will activate only if the device is currently at that threshold level. Once the device leaves that threshold level, the zone in its corresponding CBE position will remain active or deactivate according to whether its threshold is programmed for latching or tracking. ALARM VERIFICATION: Press this key to determine participation in Alarm Verification. Choosing Yes will set the device participation to the value entered at the Panel Timers screen (Figure 3.13). The only module type that can participate in alarm verification is the FZM-1.
52
Point Program
Program
LOCAL MODE: Press to toggle between Local Mode (ON) or no Local Mode (OFF). When there is a communication loss between the panel and its LCM/LEMs, SLC devices that have been selected for Local Mode participation (ON) will continue to function across all the panels SLCs in a limited manner as follows: input points will activate output points of the same Type Code point type designations. For example, SLC inputs with fire point types will activate SLC outputs with fire point types. Refer to Appendix G.3, Type Codes for Input Devices, on page 138 for Type Code point types. This setting is fixed at OFF for the FMM-4-20 module. Default: OFF
NOTE: The panel setting LCM LOCAL MODE must be set to YES for local mode to work at the device level.
4-20 DEVICE SETUP: Press to go to FMM-4-20 programming. (Refer to FMM-4-20 Monitor Module Programming on page 53FMM-4-20 Monitor Module Programming on page 53) This field appears only when FMM-420 appears as the modules Type Code label. ACCEPT: Press to save entries made on this screen and to return to the previous screen.
FMM-4-20 Monitor Module Programming
Pressing the 4-20 DEVICE SETUP soft key at the Module Point Programming screen will display this screen.
MODULE POINT PROGRAMMING L03M150 4MA SCALE VALUE: 0.00 20MA SCALE VALUE: 2000.00 UNITS: PPM HYSTERESIS: 02.0% THRESHOLD SETUP ACCEPT BACK
Default: 0
T H R E S H O L D S E T U P : Press to continue to the T H R E S H O L D S E T U P screen. (Refer to Figure 3.42
on page 54)
A C C E P T : Press to save entries made on this screen.
53
Program
Point Program
Pressing the THRESHOLD SETUP soft key at the Module Point Programming screen will display this screen.
MODULE POINT PROGRAMMING L03M150 THRESHOLD NUMBER 1 THRESHOLD VALUE: 500.25 PPM EVENT TROUBLE TROUBLE TYPE: TROUBLE1 EVENT TRIGGER: LOWER LEVEL LATCHING ACCEPT BACK
SAME LEVEL.
T R A C K I N G / L A T C H I N G : Select TRACKING or LATCHING for the threshold trouble. If more than one threshold has been programmed as latching, the first threshold reached will be the one that is latched. A C C E P T : Press to save screen entries.
54
Point Program
Program
MODULE POINT PROGRAMMING L03M150 LOCAL MODE:ON ZONE MAP: Z000 , Z104 Z110 , Z114 WALK TEST: OFF SWITCH INHIBIT: YES SILENCEABLE:NO ACCEPT BACK , Z105 , Z115 , Z106 , Z116 , Z107 , Z117
Figure 3.43 Module Point Programming Screen 2 (Control) Soft Keys LOCAL MODE: Press to toggle between Local Mode (ON) or no Local Mode (OFF). When there is a communication loss between the panel and its LCM/LEMs, SLC devices that have been selected for Local Mode participation (ON) will continue to function across all the panels SLCs in a limited manner as follows: input points will activate output points of the same Type Code point type designations. For example, SLC inputs with fire point types will activate SLC outputs with fire point types. Refer to Appendix G.3, Type Codes for Input Devices, on page 138 for Type Code point types. Default: OFF
NOTE: The panel setting LCM LOCAL MODE must be set to Yes for local mode to work at the device level.
ZONE MAP: Displays the zones mapped to this point. The default value assigned to control modules during initial programming is Z000 at Position 1 (refer to Figure 3.43), with the exception of control modules with the following Type IDs: TELEPHONE, GEN ALARM, GEN SUPERVIS, GEN TROUBLE, and TROUBLE PEND. To add or delete zones, press this soft key to proceed to the Module Zone Map screen. Refer to Zone Map on page 45 for an illustration and explanation of the Detector Zone Map screen. The Module Zone Map screen is the same except that Module replaces Detector in the title and the module address appears instead of the detector address. Up to ten general, logic, release, special or trouble zones may be mapped to a control module. Position 1 has additional functionality. Position 1 - This position is checked when a group zone disable command is issued. If the zone number in the group zone disable command matches the zone number in the first position of the zone map, the module point will be disabled. Note that the group zone disable command has no effect on general alarm zone Z000.
55
Program
Point Program
WALK TEST: This field determines if the output will activate during Walk Test. Values are ON (the output will activate) and OFF (the output will not activate). Default: OFF.
NOTE: The following Type ID codes do not participate in Walk Test, and the WALK TEST soft key will not appear when the screen displays: REL END BELL, RELEASE CKT, REL CKT ULC, REL. FORM C, REL AUDIBLE, INST RELEASE, NONRESET CTL, TELEPHONE, and FORM-C RESET. The FMM-1 module with SMOKE CONV, HEAT DETECT, or SMOKE DETECT does not participate in Walk Test.
SWITCH INHIBIT: This field determines whether a user can manually activate an output. Values are YES (can not be activated manually) or NO (can be activated manually). Default: NO SILENCEABLE: This field determines whether the user can manually silence an activated output. Values are as follows:
NO YES - RESOUND FIRE YES - RESOUND SUPERV YES - RESOUND SECURITY YES - RESOUND TROUBLE YES - NO RESOUND Not manually silenceable Silenceable, resound on fire alarm events Network and Local Resound
Silenceable, resound on supervisory events Network and Local Resound Silenceable, resound on security events Silenceable, resound for trouble Silenceable, does not resound Network and Local Resound Local Resound
NOTE: This soft key will not appear for modules with Type ID codes where silence is not optional.
NOTE: In network applications, specific nodes can be excluded from having the ability to initiate a resound on the local fire alarm panel. This is programmable via VeriFire Tools. Refer to the VeriFire Tools help file.
ZONE POINT PROGRAMMING Zyyyy ZONE LABEL: NON-RESETTABLE CONTROL:YES SILENCEABLE ZONE: YES ACCEPT BACK
56
Point Program
Program
Soft Keys ZONE LABEL: Press to type in a 20-character maximum zone description that will appear in the zones display messages. NON-RESETTABLE CONTROL: Select YES to designate the zone as non-resettable (not affected by System Reset), or NO to designate the zone as resettable (zone will turn off when System Reset occurs.). Default: NO ACCEPT: Press to save the message and return to the previous screen. SILENCEABLE ZONE: This option will designate the general zone as silenceable. When a general zone is programmed as silenceable, a signal silence local to the panel or over the network will deactivate the zone and any devices mapped to it, unless those devices are programmed with another active zone that is not silenceable. Default:NO
DELAY TIME: 00 ABORT SWITCH: ULI CROSS ZONE: NO SOAK TIME: 0000 ACCEPT BACK
Figure 3.45 Releasing Zone Programming Menu Screen Refer to Appendix B, Releasing Applications for a full explanation of the fields below. Soft Keys DELAY TIME: Press this soft key to type a value from 0 to 60 (seconds). Default 00
NOTE: The FCM-1-REL has an inherent two second delay, which must be factored into the DELAY TIME entry.
ABORT SWITCH: Press this soft key to scroll through the selection list of ULI, IRI, NYC, or AHJ. Default:ULI CROSS ZONE: Press to scroll through the selection list of YES, NO, ZONE, HEAT. Default: NO.
57
Program
Point Program
SOAK TIME: Press to type a value from 0 to 9999 (seconds). Default: 0000
NOTE: The FCM-1-REL has an inherent two second delay, which must be factored into the SOAK TIME entry.
LOGIC ZONE PROGRAMMING MENU LOGIC ZONE ZLxxxx AUTOMATIC OFF AND(Z20,OR(L2D159,L2D14))
Figure 3.46 Logic Zone Programming Menu Screen Soft Keys EDIT EQUATION: Press to proceed to the edit screen to add or edit a logic equation. NEXT/PREVIOUS EQUATION: Press to view the next or previous logic equation.
58
Point Program
Program
LOGIC ZONE PROGRAMMING MENU LOGIC ZONE ZLxxxx AUTOMATIC OFF INS/OVR AND(Z20,OR(L2D159,L2D14)) INSERT ADD POINT/ZONE ADD LOGIC FUNCTION ADD TIME/DATE DELETE EQUATION ACCEPT BACK
Figure 3.47 Edit Logic Equation Screen The cursor will be present in the equation, and can be moved by pressing the left/right arrow keys on the keyboard. To add or delete information, use the INS/OVR soft key function described below. Use the keypad to type in an equation. The ADD POINT/ZONE and ADD LOGIC FUNCTION soft keys may be used to facilitate creating a logic equation; however, commas must be added by using the keypad. Soft Keys INS/OVR: Press to toggle between insert and overwrite. Stop at the appropriate mode, which displays in line 8 of the screen. Insert will add information to the equation, overwrite will write over information already in the equation. ADD POINT/ZONE: Press to proceed to the Add Point/Zone screen. This screen is an alternative to typing in the information at this screen; it provides point and zone formats that make it less likely for typographical errors to occur. ADD LOGIC FUNCTION: Press to proceed to the Add Logic Function screen. This screen is an alternative to typing in the information at this screen; it provides logic function formats that make it less likely for typographical errors to occur. ADD TIME/DATE: Press to proceed to the Add Time/Date screen. DELETE EQUATION: Press to delete the entire equation. ACCEPT: Press to save changes made on this screen and return to the previous screen.
NOTE: When the ACCEPT soft key is pressed to save an equation, the panel checks the equation for errors. If there is an error in the equation, the previous screen will not appear, and the cursor will appear at the error point. Correct the equation, and re-press the ACCEPT soft key.
59
Program
Point Program
LOGIC ZONE PROGRAMMING MENU LOGIC ZONE ZLxxxx AUTOMATIC OFF AND(Z20,OR(L2D159,L2D14))
Figure 3.48 Add Logic Point/Zone Screen The cursor will be present in the logic equation. Place it, using the arrow keys on the keyboard, at the place where the additional point should be inserted. Soft Keys POINT SELECT: Press to scroll through the list of possible formats (detector, module, etc.). Stop at the desired format. Type in the address for the additional point. ACCEPT: Press to insert the point into the equation where the cursor is blinking, and to return to the previous screen. NEXT/PREVIOUS POINT: Press these soft keys to scroll forward or backward from the displayed point to the next installed point.
LOGIC ZONE PROGRAMMING MENU LOGIC ZONE ZLxxxx AUTOMATIC OFF AND(Z20,OR(L2D159,L2D14))
LOGIC FUNCTION:
AND
ACCEPT BACK
Figure 3.49 Add Logic Function Screen The cursor will be present in the logic equation. Place it, using the arrow keys on the keyboard, at the place where the logic function should be inserted.
60 NFS2-3030 Programming Manual P/N 52545:G1 06/16/2011
Point Program
Program
Soft Keys LOGIC FUNCTION: Press to scroll through the list of possible logic functions. ACCEPT: Press to insert the logic function into the equation where the cursor is blinking, and to return to the previous screen.
Add Time/Date
This screen appears when the ADD TIME/DATE soft key is pressed at the Logic Zone Programming Menu screen
LOGIC ZONE PROGRAMMING MENU LOGIC ZONE ZLxxxx AUTOMATIC OFF DEL OVERWRITE
ENTER TIME:22:30:00
ACCEPT BACK
Figure 3.50 Add Time/Date to Logic Zone Screen Soft Keys ENTER TIME: _ _:_ _:_ _ Press this soft key to toggle between the time/date formats. Choose one based on the type of time-based function used.
Time-based function Screen Field Time/date format HH:MM:SS, entered as military time (22:30:00 = 10:30 P.M.) (MM-DD-YY) (Use the TOGGLE DAY soft key that appears to scroll through and choose a day of the week.
DEL, SDEL, TIM ENTER TIME:_ _:_ _:_ _ TIM TIM ENTER DATE:_ _-_ _-_ _ ENTER DAY: MO
61
Program
Point Program
ACCEPT BACK
AUDIO VOLUME CONTROL POINT: N078AA00 MASTER VOLUME: 9 AUXILIARY VOLUME:12 ACCEPT BACK
Figure 3.52 Audio Point Programming Menu Screen Soft Keys MASTER VOLUME: - This field can set the volume for all audio outputs at the DVC node. When the audio amplifier point is set to 00, as it is in Figure 3.52, the setting affects all audio outputs on the DVC node (this includes all outputs on its DAAs). When a specific DAA point is entered at the point program menu (for example, N078AA01) the MASTER VOLUME setting will apply to the audio outputs at that DAA (the DAA with its address set to 01). Set this field to any volume setting from 0 (off) to 15 (high). Default: 15
62
Delete Program
Program
AUXILIARY VOLUME: - This field sets the volume for DVC inputs AUXA (background music from various sources or a telephone paging source) and AUXB (AMG-1 input). The field does not appear if a specific DAA address has been entered. The DAAs have onboard volume control for AUX A and AUXB inputs. Set this field to any volume setting from 0 (off) to 15 (high). Default: 15. ACCEPT - Press to program the displayed volume.
CLEAR: PANEL
ACCEPT BACK
Figure 3.53 Delete Program Menu Screen Soft Keys CLEAR ALL PROGRAMMING: Press to remove all panel, loop, point and ACS programming information, as well as logic and trouble zone equations. Pressing this key removes everything except passwords. A confirmation screen will display asking the user to confirm the deletion command. Pressing this key causes a reboot. CLEAR:PANEL Press to remove all programmed panel setting information from control panel memory. This does not remove ACS programming. A confirmation screen will display asking the user to confirm the deletion command. Pressing this key causes a reboot. CLEAR LOOPS Press to scroll through the options: ALL, LOOP 1, LOOP 2, , LOOP 10. Stop at the desired option. Press ACCEPT to delete all loop programming for the selected option. Pressing this key causes a reboot. DELETE POINT To delete a point, press this soft key to display the Delete Point screen. CLEAR ACS: Press to remove all ACS programming from panel memory. A confirmation screen will display asking the user to confirm the deletion command. Pressing this key causes a reboot. ACCEPT: Press to clear all programming for the selected loop option for CLEAR LOOPS. A confirmation screen will display asking the user to confirm the deletion command.
63
Program
Autoprogram Menu
DELETE BACK
Figure 3.54 Delete Point Screen POINT SELECT: Press to scroll through the options: detector or module. Stop at the desired option. Press the DELETE soft key to delete the point from programming. A confirmation screen will display asking the user to confirm the deletion command.
NOTE: Deleting points that are active or in trouble will cause a reboot.
2. 3. 4.
64
Autoprogram Menu
Program
2. 3.
Physically install/uninstall the SLC devices. Press the A U T O P R O G R A M L O O P S soft key to run the Autoprogram. Existing information will not be changed.
Autoprogram will find the devices/modules on the selected installed SLCs. It will compare the information it finds during autoprogramming against any point information that may already be in the database, and it will look for any addressing errors, such as two detectors with the same address. If it finds a discrepancy or error, a screen will be displayed with the discrepant or incorrect information and the programmer will be given the option of changing it.
ACCEPT BACK
9+10. Stop at the desired option to select it. ACCEPT: Press to autoprogram the selection. A confirmation screen will display asking the programmer to confirm the autoprogram choice made (press the YES soft key to confirm). A screen with the message AUTOPROGRAM IN PROGRESS will display until autoprogramming is complete.
65
Program
Autoprogram Menu
AUTOPROGRAM CONFIRMATION LOOP 1 2 3 4 5 6 7 8 9 10 REVIEW DETECTORS MODULES 011 087 030 129 NOT INSTALLED NOT INSTALLED NOT INSTALLED NOT INSTALLED NOT INSTALLED NOT INSTALLED NOT INSTALLED NOT INSTALLED
Figure 3.56 Autoprogram Confirmation Screen (SLCs) Soft Keys REVIEW: Press this soft key to review the new devices found (with the option of adding them to the program one by one), devices that are in the database that the autoprogram did not find, devices that have data base and autoprogram information that differs, and devices that are incorrectly doubled up on a single address. Devices will display in the following order: L01M001 through L01M159 L01D001 through L01D159 L02M001 through L02M159, etc. Depending on what information was found, different screens may appear for different points. Refer to Figure 3.57 through Figure 3.60 for examples of the screens. ACCEPT ALL: Press to accept all the new devices that have been found by the autoprogram. Errors and discrepancies will still be displayed the same as if the REVIEW soft key had been pressed: however, new devices will not individually display for review and acceptance.
YES EDIT
NO BACK
66
Autoprogram Menu
Program
Soft Keys YES: Press this soft key to install the new point into the panels database. EDIT: Press this soft key to advance to the point programming menu for the new point. NO: Press if the point will not be installed.
YES
NO BACK
Figure 3.58 Autoprogram Confirmation Screen (Missing Point) Display This screen will display the SLC device address when a previously installed/programmed point does not respond during a subsequent Autoprogram. Soft Keys YES: Press to delete the point information from the panels database. NO: Press to leave the point information in the panels database.
AUTOPROGRAM CONFIRMATION MISMATCHED MODULE FOUND AT L01M123 OLD:CONTROL NEW:MONITOR ACCEPT CHANGES?
YES EDIT
NO BACK
67
Program
Autoprogram Menu
Display The O L D field contains the information currently in the panels programming database. The N E W field contains the information found during autoprogramming. The fields contain the FlashScan Type ID codes if the device is FlashScan, or they will contain the device type if CLIP. Soft Keys YES: Press this soft key to accept the new device type. EDIT: This soft key will appear only when SLC devices are mismatched. Press it to advance to the point programming screen for this point. NO: Press if the new information should not be installed over the existing information in the database.
ACCEPT BACK
Figure 3.60 Autoprogram Confirmation Screen (Double Address) Display The SLC loop number and device address are displayed where the Autoprogram has found more than one detector or module with the same address. Soft Keys ACCEPT: Pressing this soft key acknowledges that the programmer has been informed of the double address. Autoprogram will not make a modification to the database for this point. The installer must correct this problem.
68
LAKEVIEW GENERAL HOSPITAL SYSTEM NORMAL 10:22:34A TUE JAN 25, 2011 ALTER STATUS WALK TEST CHANGE TIME/DATE CONTROL ON/OFF BACK
Figure 4.1 Alter Status Screen Soft Keys All soft key selections (except BACK) are menu selections. Press to display the desired menu.
LAKEVIEW GENERAL HOSPITAL SYSTEM NORMAL 10:22:34A TUE JAN 25, 2011 POINT SELECT
ACCEPT BACK
Figure 4.2 Point Select for Disable/Enable Screen Soft Keys POINT: Press this soft key to identify the type of point to disable/enable: the choices that will appear in parentheses next to the point format are DETECTOR, MODULE, LOGIC ZONE, GENERAL ZONE, or DAA SPEAKER CIRCUIT. Enter the address of the point using the keyboard. If there is an event in the display area, that address will be the default. If no event is present, the default format will be that of a detector.
NFS2-3030 Programming Manual P/N 52545:G1 06/16/2011 69
Alter Status
Disable/Enable
4.2 Disable/Enable
A point can be disabled or enabled using this screen. Press the DISABLE/ENABLE soft key at the Alter Status screen to display the following.
LAKEVIEW GENERAL HOSPITAL SYSTEM NORMAL 10:22:34A TUE JAN 25, 2011 DISABLE/ENABLE: N114L03D052 AUTOMATIC INACTIVE ELEVATOR LOBBY EAST WING FIFTH FLOOR Z005 SMOKE(PHOTO) VALUES: 011% OF ALARM, 045% OF PREALARM
DISABLE
BACK
Figure 4.3 Disable/Enable Screen Soft Keys DISABLE/ENABLE Only the applicable command will display. Press to disable an installed, programmed point, or to enable a disabled one.
CAUTION: WHEN A DISABLED OUTPUT IS ENABLED, IT WILL BE AFFECTED BY CONDITIONS EXISTING IN THE SYSTEM THAT WOULD NORMALLY AFFECT IT. THAT IS, IF A CONDITION EXISTS THAT WOULD HAVE TURNED THE OUTPUT ON WERE IT ENABLED, IT WILL TURN ON WHEN IT IS ENABLED.
NOTE: When an input or output point associated with releasing functions is disabled, a single supervisory trouble will be generated.
Group Zone Disable - This term refers to the disabling (or enabling) of a general zone. If the first position in a devices zone map matches the general zone number entered at this screen, that device will be disabled (or enabled).
WARNING: DO NOT RELY ON DISABLE TO DISABLE RELEASING POINTS DURING TESTING. RELEASING POINTS MUST BE PHYSICALLY DISCONNECTED.
70
Detector Sensitivity
Alter Status
ACCEPT BACK
Figure 4.4 Sensitivity Select Point Screen Soft Keys POINT: Press to place the cursor in the format field. Type the address using the keyboard. NEXT/PREVIOUS SELECTION: Press these soft keys to scroll sequentially through the detector addresses on the loop. The screen will display the next loop when the last device on this loop is passed. ACCEPT: Press to proceed to the Detector Sensitivity screen.
71
Alter Status
Detector Sensitivity
The current sensitivity values displayed are described in Detector Point Programming (Refer to the paragraph Sensitivity on page 48) and in Appendix D, Intelligent Sensing Applications.
LAKEVIEW GENERAL HOSPITAL SYSTEM NORMAL 10:22:34A TUE JAN 25, 2011 ADDRESS: L03D052 AUTOMATIC INACTIVE ELEVATOR LOBBY EAST WING FIFTH FLOOR Z003 SMOKE(PHOTO) OCCUPIED ALARM SENSITIVITY = 7 OCCUPIED PREALARM SENSITIVITY = 5 UNOCCUPIED ALARM SENSITIVITY = 5 UNOCCUPIED PREALARM SENSITIVITY = 3 BACK
Figure 4.5 Detector Sensitivity Select Screen Soft Keys OCCUPIED ALARM SENSITIVITY: OCCUPIED PREALARM SENSITIVITY: UNOCCUPIED ALARM SENSITIVITY: UNOCCUPIED PREALARM SENSITIVITY: Press the soft key next to one of these setting categories to proceed to the next screen, where the setting value may be changed.
LAKEVIEW GENERAL HOSPITAL SYSTEM NORMAL 10:22:34A TUE JAN 25, 2011 ADDRESS: L03D052 AUTOMATIC INACTIVE ELEVATOR LOBBY EAST WING FIFTH FLOOR Z003 SMOKE(PHOTO) OCCUPIED ALARM =6, 1= 0.50%, 6= 1.66% 2= 0.73%, 7= 1.89% 3= 0.96%, 8= 2.12% 4= 1.19%, 9= 2.35% 5= 1.43%,
ACCEPT BACK
72
Alter Status
Soft Keys OCCUPIED ALARM: The type of alarm/prealarm will display based on which soft key was pressed in the previous screen. For example, in the screen above, OCCUPIED ALARM displays because the OCCUPIED ALARM SENSITIVITY: soft key was pressed. The detector sensitivity values display below the soft key. Select a value by pressing the soft key until the desired value appears in the underlined field. ACCEPT: Press to accept the change made on this screen, and to return to the previous screen.
LAKEVIEW GENERAL HOSPITAL SYSTEM NORMAL 10:22:34A TUE JAN 25, 2011 ALTER STATUS MENU
LAKEVIEW GENERAL HOSPITAL THIS WILL CLEAR ALL VERIFY COUNTERS CLEAR COUNTERS BACK
Figure 4.7 Clear Verify Counters Screen Soft Keys CLEAR COUNTERS: Press this soft key to clear all verification counters.
73
Alter Status
Walk Test
LAKEVIEW GENERAL HOSPITAL SYSTEM NORMAL 10:22:34A TUE JAN 25, 2011 CLEAR HISTORY
Figure 4.8 Clear History Screen Soft Keys ALARM HISTORY: Press to clear Alarm history. EVENT HISTORY: Press to clear Event history. ALL HISTORY: Press to clear both Alarm and Event history.
WARNING: WALK TEST MODE CAN DEACTIVATE FIRE PROTECTION. OBSERVE THE FOLLOWING IMPORTANT PRECAUTIONS.
IMPORTANT! Prior to Walk Test, secure all protected buildings, and notify the building owner/operator, fire department, and other pertinent personnel that testing is in progress. Immediately after Walk Test is completed, notify the same people that testing is complete and the system is restored to normal operation. Reconnect releasing devices. Walk Test will time out and return to normal operation after one hour when no Walk Test activations have occurred during that time.
74
Walk Test
Alter Status
Walk Test may be exited at any time by pressing the ABORT soft key on the screen
NOTE: Walk Test will not start if any devices are active (i.e., fire alarms, security, supervisories or pre-alarms). To perform a walk test while a device is active, disable the device and press the System Reset button.
NOTE: In network applications, specific nodes can be excluded from having the ability to force the fire panel out of Walk Test due to an alarm condition. This is programmable via VeriFire Tools. Refer to the VeriFire Tools help file.
Basic Walk Test - The basic test allows a single operator to run audible tests on the panel. All logic equation automation is suspended during the test. All ACS devices will default to Disable. They may be enabled by selecting NO at the DISABLE ACS BOARDS soft key on the Walk Test Menu screen (Figure 4.9). Advanced Walk Test - The advanced test allows field-supplied output point programming that will react to input stimuli such as CBE and logic equations. When points are activated in advanced testing, each initiating event will latch the input. Release of the latch and subsequent activation of the next point is controlled through use of the NEXT TEST soft key. All ACS devices default to disable. They may be enabled by selecting NO at the DISABLE ACS BOARDS soft key on the Walk Test Menu screen (Figure 4.9). An advanced test is audible. An audible test is intended for pull station verification, magnet-activated tests on input devices, input and output device and wiring operation/verification. Only devices previously configured to participate and designated as part of the test through the following screens will make sound.
Walk Test Activation Indications
FlashScan poll mode - Once the START TEST soft key has been pressed: Each intelligent addressable input device will blink its address in red, and each intelligent addressable output device will blink its address in green. Pattern examples are given below.
Address 8 37 152 Blink Pattern 8 blinks, long stop, 8 blinks, long stop, 3 blinks, stop, 7 blinks, long stop, 3 blinks, stop, 7 blinks, long stop, 15 blinks, stop, 2 blinks, long stop, 15 blinks, stop, 2 blinks, long stop,
An input device activated in Walk Test latches on steady green for the duration of the test. If the device is put in trouble (for instance, the detector head is removed, then replaced), the LED will be latched on for the duration of the test. An output device activated in Basic Walk Test will remain active and the LED will glow steady green for
4 seconds for alarms 8 seconds for troubles.
An output device activated in Advanced Walk Test will remain active and the LED will glow steady green until the NEXT TEST soft key is pressed.
CLIP poll mode - Once the START TEST soft key has been pressed: Intelligent addressable input and output devices continue to blink red as usual until activated. An input device activated in Walk Test latches on steady red during activation. If the device is put in trouble (for instance, the detector head is removed, then replaced), the LED will be latched on for the duration of the test. An output device activated during Basic Walk Test will remain active and the LED will glow steady green (if a FlashScan module) or steady red (if a CLIP module) for
4 seconds for alarms
75
Walk Test
An output device activated in Advanced Walk Test will remain active and the LED will glow steady green (if a FlashScan module) or steady red (if a CLIP module) until the NEXT TEST soft key is pressed.
Conventional Devices - Monitor modules with the Type Codes SMOKE CONV, HEAT DETECT, and SMOKE DETECT, and outputs with the Type Code FORM C RESET do not participate in Walk Test other than blinking their addresses if they are polled in FlashScan mode unless they are used with a FlashScan zone module. To prevent the occurrence of false alarms for conventional devices, 24 volt power will be interrupted for up to a minute after Walk Test has been exited.
BASIC/ADVANCED: BASIC SILENT/AUDIBLE: AUDIBLE PARAMETER: ZONE DISABLE ACS BOARDS: YES ACCEPT BACK
Figure 4.9 Walk Test Menu Screen Soft Keys BASIC/ADVANCED: Press to toggle between the two choices. Stop at the desired test. SILENT/AUDIBLE: This soft key is for future use. Walk test is audible. PARAMETER: Press to scroll through the choices. Stop at the desired parameter. Choosing the loops parameter will bring up the Walk Test loops programming screen. (Refer to Figure 4.10.) Choosing the Zone parameter will bring up the Zone Walk Test screen. (Refer to Figure 4.13.) Choosing the Devices parameter will bring up the Devices Walk Test screen (Refer to Figure 4.11.
76
Walk Test
Alter Status
The participating devices/points in Basic Test will be All devices/points on all the FACP SLCs that are set to participate in Walk Test with the exception of logic equations, whose activation is suspended. When an input test is initiated, only the outputs on the corresponding loop will activate. The entire panel - all devices/points set to participate in Walk Test - will participate with the exception of logic equations, whose activation is suspended. When an input test is initiated, only the outputs on the corresponding loop will activate. Individual detectors tested one at a time.
The participating devices/points in Advanced Test will be All devices/points on all the FACP SLCs that are set to participate in Walk Test. When an input test is initiated, outputs mapped on all loops will activate.
PANEL
The entire panel - all devices/points set to participate in Walk Test - will participate. When an input test is initiated, outputs mapped on all loops will activate. Detectors only.
DEVICES ZONE
For BASIC Walktest only. When the zone n/a entered in the parameter field is present in a devices first (primary) CBE location, that device will go into Walk Test when the parameter zone is put into Walk Test. When an input test is initiated, outputs mapped to the corresponding zone on all loops will activate.
Table 4.1 Walk Test Parameters DISABLE ACS BOARDS: This soft key allows the operator to disable ACS devices during Walk Test. Press to toggle between the two choices, YES (disable) and NO (enable). Default: YES
LAKEVIEW GENERAL HOSPITAL SYSTEM NORMAL 10:22:34A TUE JAN 25, 2011 WALK TEST SETTINGS: BASIC, AUDIBLE, LOOPS L1:NO L4:NO L7:NO L10:NO START TEST BACK L2:NO L5:NO L8:NO L3:YES L6:YES L9:YES
Once the START TEST soft key has been pressed and the test begun, this message changes to ABORT
Figure 4.10 Walk Test Loops Programming Screen The chosen settings are displayed (BASIC, AUDIBLE in Figure 4.10), and installed loops will display with a participation field. The up and down arrow keys on the keypad navigate through the fields. Choose YES for participation, NO for no participation, using the NEXT SELECTION(+)/PREVIOUS SELECTION(-) keys on the keypad.
77
Alter Status
Walk Test
Soft Keys START TEST: Press to begin Walk Test using the chosen parameters. Once Walk Test has begun, this soft key becomes ABORT, and can be pressed at any time to exit Walk Test. NEXT TEST: This key appears for Advanced Walk Tests when the panel parameter is chosen at the Walk Test Menu Screen. Refer to Figure 4.14 for the location of this key. Press it to progress from one activation to the next, latching the new point and releasing the latch on the previous point.
LAKEVIEW GENERAL HOSPITAL SYSTEM NORMAL 10:22:34A TUE JAN 25, 2011 WALK TEST SELECT SETTINGS: BASIC,AUDIBLE,DEVICES
Figure 4.11 Walk Test Devices Programming Screen This screen appears when DEVICES is chosen as a parameter at the Walk Test Menu. The chosen settings are displayed (BASIC, AUDIBLE in Figure 4.11). Soft Keys DEVICE:Press this key to type the desired detector address into the underlined field. NEXT POINT: Press this key to bring up the next installed address for an addressable detector into the DEVICE field. PREVIOUS POINT: Press this key to bring up the previous installed address of an addressable detector into the DEVICE field. ACCEPT: Press this key to begin Walk Test, and to proceed to the Devices Test Selection screen (Figure 4.12).
78
Walk Test
Alter Status
START TROUBLE TEST START ALARM TEST START OBSCURATION TEST ABORT
This field will appear only for a beam detector with an integral sensitivity test feature.
Figure 4.12 Devices Test Selection Screen Soft Keys START TROUBLE TEST:Press this key to generate a Trouble on the selected detector. START ALARM TEST: Press to generate an Alarm on the selected detector. START OBSCURATION TEST: Press to perform an Obscuration Test on the selected Beam detector. (Beam detectors only.) ABORT: Press to stop the Walk Test.
NOTE: The Trouble, Alarm and Obscuration tests described above are additional tools provided to ascertain the functionality of a detector. They are not a substitute for periodic maintenance and sensitivity verification per NFPA 72.
79
Alter Status
Walk Test
TROUBLE PROG MODE ACTIVATED LAKEVIEW GENERAL HOSPITAL 10:22:34A TUE JAN 25, 2011 WALK TEST SETTINGS:BASIC,AUDIBLE,ZONES
Figure 4.13 Zone Walk Test Selection Screen POINT SELECT: Press to enter a zone number that will be put into Walk Test. When the panel finds that zone in the first position of a devices CBE map, that device will be put in Walk Test mode. START TEST: Press to begin Walk Test using the chosen parameters. Once Walk Test has begun, this soft key becomes ABORT, and can be pressed at any time to exit Walk Test. Walk Test In Progress Screen
TROUBLE PROG MODE ACTIVATED LAKEVIEW GENERAL HOSPITAL 10:22:34A TUE JAN 25, 2011 WALK TEST IN PROGRESS SETTINGS: ADVANCED, AUDIBLE, PANEL
Settings will indicate whether it is a Basic or Advanced walk test.
NEXT TEST
ABORT
Once the START TEST soft key has been pressed, this soft key appears. Appears in Advanced walk test only.
Once the START TEST soft key has been pressed and the test begun, the message changes to ABORT
80
Program Time/Date
Alter Status
TIME/DATE: 08:22A TUE 01/15/08 TIME FORMAT: H:MM AM/PM DATE FORMAT: MM/DD/YY TIME ZONE: USA EASTERN ACCEPT BACK
Figure 4.15 Program Time and Date Screen Soft Keys TIME/DATE: Press to bring the cursor to the time/date field. The current time and date will be displayed using the current format. Change the values using the keypad. TIME FORMAT: Press to scroll through a list of formats as follows; HH:MM AM/PM; H:MM AM/PM; HH:MM; and H:MM. Stop at the desired format. DATE FORMAT: Press to toggle between MM/DD/YY and DD/MM/YY formats. Stop at the desired format. TIME ZONE: Press to scroll through a list of 34 time zone selections. Stop at the appropriate zone. ACCEPT: Press to save changes made on this screen and to return to the previous screen.
LAKEVIEW GENERAL HOSPITAL SYSTEM NORMAL 10:22:34A TUE JAN 25, 2011 POINT SELECT
ACCEPT BACK
81
Alter Status
Soft Keys POINT: Press this soft key to enter the point address or general zone number (except Z000) to be forced on or off.
NOTE: A module with a releasing Type ID can not be forced.
NEXT/PREVIOUS SELECTION: Press to progress to the next or previous point on the loop, or the next or previous general zone. ACCEPT: Press to continue to the Control On or Control Off screen.
LAKEVIEW GENERAL HOSPITAL SYSTEM NORMAL 10:22:34A TUE JAN 25, 2011 CONTROL ON/OFF: N114L03M052 AUTOMATIC ACTIVE ELEVATOR RECALL EAST WING FIFTH FLOOR Z000 CONTROL
FORCE OFF
BACK
Figure 4.17 Control Off Screen Soft Keys FORCE OFF: Press this soft key to change the state of the control module or general zone from A U T O M A T I C A C T I V E to A U T O M A T I C I N A C T I V E .
NOTE: A module with a releasing Type ID cannot be forced.
82
Alter Status
4.8.2 Control On
If the selected point or zone is inactive, the Control On screen will appear:
LAKEVIEW GENERAL HOSPITAL SYSTEM NORMAL 10:22:34A TUE JAN 25, 2011 CONTROL ON/OFF: N114L03M052 AUTOMATIC INACTIVE ELEVATOR RECALL EAST WING FIFTH FLOOR Z000 CONTROL
FORCE ON BACK
Figure 4.18 Control On Screen Soft Keys FORCE ON: Press this soft key to change the state of the control module or zone from A U T O M A T I C I N A C T I V E to A U T O M A T I C A C T I V E .
83
LCM IMAGE: BOOT: APP: 002.004.003 JUN 28 2011 002.008.001 JUN 30 2011
LCD 160 IMAGE: 001.000.024 NOV 17 2011 002.000.001 MAY 19 2011 NCM: (NODE:134) APP: 003.000.004 MAY 25 2011
DATABASE: 010.000 08:54 WED JAN 19 2011 LAST CHANGED: SYSTEM DATA FROM: FRONT PANEL
SERIAL NUMBER:
84
Power-up Screen
Service Screens
LCM SOFTWARE VERSION 1 2 3 4 5 BOOT: 002.005.001 APP: BOOT: 002.005.001 APP: NOT INSTALLED NOT INSTALLED NOT INSTALLED 003.000.018 003.000.018
BOOT: 010.000.025
APP:
010.000.041
SELF TEST RAM TEST: NVRAM TEST: RTC TEST: KEYPAD : COMM 1 : COMM 2 : COMM 3 : PASS PASS PASS PASS PASS PASS PASS BOOT APP DBASE LCM LCD-160 LANG CRC: CRC: CRC: CRC: CRC: CRC: PASS PASS PASS PASS PASS PASS
NOTE: LCM refers to the code resident in the CPU2-3030, not the code that is programmed into the LCM-320.
NOTE: LCD-160 refers to the code resident in the CPU2-3030, not the code that is programmed into the LCD-160.
85
Service Screens
Bootloader Screen
Figure 5.5 Bootloader Menu Screen LCD-160 DOWNLOAD:Press this soft key to display the LCD-160 Download menu screen. REBOOT:Press this soft key to reboot the panel, and exit the bootloader screen. LOOP DOWNLOAD:Press this soft key to display the Loop Download Menu screen.
TROUBLE LOADING..NO SERVICE LAKEVIEW GENERAL HOSPITAL BOOTLOADER LCD-160 DOWNLOAD MENU 11:58:45A TUE JAN 25, 2011
N001
Figure 5.6 LCD-160 Download Menu Screen ADDRESS: Press this soft key to scroll through to the desired LCD-160 address. All means all addresses. Default: ADDRESS 001. Shortcut: Type 1 on the keyboard, which jumps to address 10, or type 2 for twenty, 3 for thirty, 0 to reset back to 1. Type an asterisk (*) to select all addresses.
86
Bootloader Screen
Service Screens
DOWNLOAD TYPE: Press this soft key to scroll through the languages (LANGUAGE-ENGLISH, LANGUAGE-HEBREW, LANGUAGE-PORTUGUESE, LANGUAGE-SPANISH), BANNER, APP and BOOT. Stop at the desired selection. Choose a language to change LCD-160s selected at the ADDRESS field to display in that language. Choose BANNER to add the panel banner to those LCD-160 displays selected at the ADDRESS field. Select APP to download an application file to the selected LCD-160(s). Select BOOT to download a boot file to the selected LCD-160(s). AUTO:Press this soft key to automatically download to the LCD-160 the most up-to-date language, bootloader, and application from the panel. START:Press this soft key to begin the download.
TROUBLE LOADING..NO SERVICE LAKEVIEW GENERAL HOSPITAL BOOTLOADER LOOP DOWNLOAD MENU 11:58:45A TUE JAN 25, 2011 AUTO START BACK
Figure 5.7 Loop Download Menu Screen LOOP ADDRESS: Press this soft key to scroll through the Loops. Stop at the appropriate pair, or select ALL. DOWNLOAD TYPE: Press this soft key to scroll through the download types. Stop at the appropriate type. Selections are: APP, BOOT, or APP/BOOT. Select APP to download an application file to the selected loops. Select BOOT to download a boot file to the selected loops. Select APP/BOOT to select both for downloading. AUTO:Press this soft key to automatically download to the selected loop(s) the most up-to-date applications or boot programming from the panel. START:Press this soft key to begin the download.
87
Service Screens
Download Screen
TROUBLE LOADING..NO SERVICE LAKEVIEW GENERAL HOSPITAL BOOTLOADER PERFORM DOWNLOAD 11:58:45A TUE JAN 25, 2011
PERFORM DOWNLOAD
88
89
Menu Hierarchy Rapid All Call Default Settings More (Panel Settings (3) Screen Sounder Base Setup Custom Tone Setup Screen Pulse On Time Period Number Of Pulses Tone Off Period Network Display Mode Drill Mode Panel Timers Verify Time Maximum Verification Count AC Fail delay Silence Inhibit Auto Silence Verify=Prealarm More PAS Presignal Delay Default Timers LCD Programming Brighter Darker Language Backlight Default Current ACS Programming Annunciator Type Point Programming Point Mode Source Supervision Main PS AC Fail Address Printer CRT Baud rate Auxiliary Trouble Reporting Tamper Input More Terminal More Password Change Master Password User Password Weekly Occupancy Schedule Remote Display Menu Point Programming Display Point Point Label Local control Loop Configuration Loop Point Programming Loop Selection Installed 90
Screens Overview
Screens Overview Detector Poll Module Poll Rapid Poll Wiring Style Blink Mode Custom Action Message Custom Action Message Message Event Logging Non-Fire Activations Output Activations Holiday Menu Point Program Detector Point Programming (1) Type FlashScan Type Point Label Extended Label Zone Map More (Detector Point Programming (2)) Custom Action Message Alarm Verification Local Mode Weekly Occupancy Schedule Multi-Detector Sensitivity Occupied Sensitivity Alarm Occupied Sensitivity Prealarm Unoccupied Sensitivity Alarm Unoccupied Sensitivity Prealarm More (Detector Point Programming (3)) Low Temp Enable Prealarm Silenceable Intelligent Sounder Sounder Base Setup AUX Tone 1 AUX Tone 1 Control AUX Tone 2 AUX Tone 2 Control Volume CO Pre-Alarm Module Point Programming Module Type Type Code Label FlashScan Code Label Point label Extended Label More (for a Monitor Type) Custom Action Message Zone Map Alarm Verification Local Mode 4-20 Device Setup 4mA Scale Value 20mA Scale Value Units NFS2-3030 Programming Manual P/N 52545:G1 06/16/2011
Menu Hierarchy
91
Menu Hierarchy Hysteresis Threshold Setup Threshold Number Threshold Value Event Trouble type Event trigger Latching More (for a Control Type) Local Mode Zone Map Walk Test Switch Inhibit Silenceable General Zone Point Programming Zone Label Non-Resettable Control Releasing Zone Programming Delay Time Abort Switch Cross Zone Soak Time Logic Zone Programming Edit Logic Equation Add Point/Zone Add Logic Function Add Time/Date Delete Equation Trouble Zone Programming Edit Logic Equation Add Point/Zone Add Logic Function Add Time/Date Delete Equation Annunciator Board Label ACS Label Audio Point Programming Master Volume Auxiliary Volume Delete Program Menu Clear Panel Clear Loops Delete Point Point Select Clear All Programming Clear ACS Autoprogram Menu Confirmation Screens Alter Status Disable/Enable Point Select Detector Sensitivity Sensitivity Select Change Alarm/Prealarm Sensitivity Clear Verify Counters 92
Screens Overview
Screens Overview Clear Counters Clear History Alarm History Event History All History Walk Test Basic/Advanced Silent/Audible Parameter Disable ACS Boards Change Time/Date Time Format Date format Time Zone Control On/Off Point Select Point Force On/Off
Menu Hierarchy
Printer Functions Programming Print Programming Menu Print Programming Menu (2) Active Points Active Points Menu Walk Test Detector Maintenance Report Installed Points Installed Points Menu Installed Points Menu (Range)
93
Cross Zone
94
Releasing Applications
Figure B.1 UL-listed Abort Station This section contains information on each type of abort switch. Example of an Abort Switch Application The figure below contains an illustration for an abort switch application configuration using releasing zone ZR05 as an example. The configuration includes:
95
Releasing Applications
Abort Switches
A monitor module wired to an abort station and programmed with the Type Code ABORT
SWITCH
All initiating devices and outputs with a common releasing zone in their zone maps - ZR05 in the example shown A fully programmed releasing zone - releasing zone ZR05 in the example shown. (Refer to Section 3.4.4, Releasing Zone, on page 57 for programming information.) In the following example, when an initiating device activates (one of the two detectors or the pull station), pressing and holding the abort switch while the delay time is in effect will prevent the control panel from sending the command to dump releasing agents when the delay time expires. The abort switch selection (ULI, IRI, NYC, or AHJ) determines the function of the abort switch.
SYSTEM NORMAL SYSTEM ACT IVATED
Detector
Detector
Type Code Abort station with Abort Switch and Manual Release lever
ZR05
Output Module
Output Module
Output Module
Output Module
Type Code
RELEASE CKT
Type Code
REL CKT ULC
Type Code
REL AUDIBLE
Type Code
REL END BELL
Example: If you program these three output modules as shown, these outputs activate at release.
Example: If you program a fourth module as shown, this output activates when the release is finished.
96
Abort Switches
Releasing Applications
5 sec Alarm
15 sec 10 sec
Release the Abort Switch; the 10-second ULI timer begins When the 10-seconds ULI timer expires, the control panel activates Releasing Zone outputs
97
Releasing Applications
Abort Switches
Program selections for this releasing zone Delay Time: 15 seconds Abort Switch: IRI Cross Zone: Z Soak Time: 0 0 sec 5 sec Alarm 1
5 sec
10 sec
20 sec
30 sec
5 sec 10 sec
Press and hold the Abort Switch for 15 seconds Alarm 2 (Cross-zone conditions met)
10 sec Release the abort switch; a 10-second IRI timer begins At the end of the 10 seconds, the control panel activates releasing zone outputs
Total time from when Abort Switch is pressed to output activation: 15 + 10 = 25 seconds Total time from when Abort Switch is released to output activation: 10 seconds
98
Abort Switches
Releasing Applications
When an alarm initiates in the programmed releasing zone, pressing and holding the abort switch stops the delay timer countdown. The delay timer restarts at the beginning of its countdown when the abort switch is released. When the Delay Time expires, the 90-second NYC timer starts counting down. When both timers expire, the control panel activates releasing zone outputs.
NOTE: 120 seconds is the maximum delay after the abort switch is released. If the Delay Time plus the NYC delay time of 90 seconds exceeds 120 seconds, the releasing zone outputs will still be activated at 120 seconds after the abort switch is released.
0 sec.
10 sec. 30 sec.
Alarm Press and hold the Abort Switch Release Abort Switch--At this point, the delay time becomes the programmed delay (15 sec.) plus 90 seconds (105 sec.) OR 120 seconds, whichever is smaller When all timers are expired (in this example, 145 seconds after alarm initiation, 105 seconds after the Abort switch has been released) the control panel activates Releasing Zone outputs
99
Releasing Applications
Abort Switches
expire at 150 seconds: however, this time exceeds the maximum of 120 seconds, so the releasing zone outputs will begin releasing at 120 seconds, not at 150. Following is a graphic example of an NYC Abort Switch and a delay timer programmed to a releasing zone.
Program selections for this releasing zone Delay Time: 60 seconds Abort Switch: NYC Cross Zone: N Soak Time: 0
Delay Time =60 sec. Pressing and releasing abort switch restarts Delay Time = 60 countdown after 40 seconds have elapsed.
Release Abort Switch--At this point, the delay becomes the programmed Delay Time (60 seconds) plus the NYC Delay (90 seconds), which is 150 seconds, OR 120 seconds, whichever is smaller.
The control panel activates releasing zone outputs after 120 seconds have elapsed. The NYC timer has not expired, but it is overridden by the control panel.
100
Abort Switches
Releasing Applications
When an alarm initiates in the programmed releasing zone, the programmed Delay Time starts. Pressing and holding the abort switch suspends the delay timer. When the abort switch is released, the control panel restores the value of the programmed Delay Time and the delay timer counts down. When the Delay Time expires, the control panel activates releasing zone outputs.
Program selections for this releasing zone Delay Time: 60 seconds Abort Switch: AHJ Cross Zone: N Soak Time: 0
0 sec.
45 sec. 30 sec.
60 sec.
Release the abort switch and the control panel restores the programmed value Delay Time (60 sec.) and counts down When the Delay Time expires, the control panel activates releasing zone outputs
101
Releasing Applications
Abort Switches
CAUTION: MAPPING OF ANY INPUTS THAT ARE NOT ASSOCIATED WITH A PRIMARY ZONE COULD CAUSE IMPROPER OPERATION OF CROSS ZONE TYPE ZONE.
A summary of the types of Cross Zones and the conditions for activating a releasing zone:
Type No Yes Zone Activates when A Cross Zone has not been selected. An alarm from any initiating device mapped to the releasing zone activates it. Two or more initiating devices are in alarm that are mapped to the same releasing zone. Two or more initiating devices are in alarm that are mapped to two different Primary Zones and that are also mapped to the same releasing zone. Note that the FACP considers only Primary Zones to determine whether releasing zone activation should occur. At least one smoke detector mapped to a releasing zone is in alarm and at least one heat detector mapped to the same releasing zone is in alarm.
Heat
* *
* indicates a
Primary Zone
REL L02M107 Zone Map = ZR01
Abort Switches
Releasing Applications
Each Cross Zone option and the conditions required to activate releasing zone ZR01 are shown in the table below, according to the example in Figure B.8.
Cross Zone Selection (Cross=) Cross=No Cross=Yes Cross=Zone For example: Condition(s) Required to Activate the Releasing zone An alarm from any initiating device activates the releasing zone. An alarm from any two initiating devices activates the releasing zone. An alarm from two initiating devices mapped to different primary general zones, but mapped to the same releasing zone. An alarm from L02D101 and L02D103 An alarm from L02D102 and L02D104 An alarm from L02D101 and L02D104 An alarm from L02D102 and L02D103 The two detectors listed in each set above are each mapped to different primary general zones, but both list ZR01 in their zone maps. Activation of heat detector L02D104 and one smoke detector (L02D101, L02D102, or L02D103).
Cross=Heat
What the Type Code does Provides an abort function through a monitor module (connected to a UL-listed abort station) for a releasing zone. Provides a manual release through a monitor module (connected to a UL-listed pull station) for a releasing zone. Provides a manual release with a 10-second delay through a monitor module (connected to a UL-listed pull station) for a releasing zone. Provides a second manual release through a monitor module (connected to a UL-listed pull station) for a releasing zone.
Refer to How to Program an Abort Switch on page 104 How to Program a Manual Release Switch on page 105 How to Program a Manual Release Delay Switch on page 106
(tracking)
MAN. RELEASE
(latching)
(latching)
SECOND SHOT
(latching)
Type Codes designed for releasing zone outputs (SLC control modules).
Type Code
REL END BELL
What the Type Code does Activates an NAC audio or visual device when releasing circuits shut off. Directs outputs to perform a release function as required by ULC. Directs outputs to perform a releasing function. Directs relay outputs to perform a releasing function. Activates audio or visual devices steady when releasing starts. Activates non-releasing output (SLC modules) with no delay time.
Refer to How to Program a Release End Bell Circuit on page 108 How to Program a ULC Release Circuit on page 109 How to Program a Release Circuit on page 110 How to Program a Release Form-C Circuit on page 111 How to Program a Release Audible Circuit on page 112 How to Program an Instant Release Circuit on page 113
RELEASE CKT
REL. FORM C
REL AUDIBLE
INST RELEASE
103
Releasing Applications
Abort Switches
Example A programming example of a monitor module programmed as an Abort Switch for Releasing Zone ZR05.
SYSTEM NORMAL SYSTEM ACT IVATED
Detector
R05
104
Abort Switches
Releasing Applications
Example A programming example of a monitor module programmed as an manual release switch for releasing zone ZR05.
SYSTEM NORMAL SYSTEM ACT IVATED
Detector
ZR05
105
Releasing Applications
Abort Switches
Example A programming example of a Monitor module programmed for MAN REL DELAY switch for Releasing Zone ZR05.
SYSTEM NORMAL SYSTEM ACT IVATED
Monitor Module Type Code MAN REL DELAY ZR05 NBG-12LRA station with Manual Release Lever
Detector
Figure B.11 Monitor Module Configured as a Manual Release Delay Switch For example, program releasing zone ZR05 with a Manual Release Delay switch for the following releasing selections: Delay Time = 15, Abort Switch = ULI, Cross Zone = NO, Soak Time = 30. When the Manual Release Delay Switch activates, the control panel replaces the remainder of the 15-second Delay Time, if running, with a 10-second timer. Examples: 1. The FACP programmed Delay Time begins its 15 second countdown. The Manual Release Delay switch is pulled when the FACP delay timer has counted down to 12 seconds. The 12 seconds remaining in the countdown are overridden by the 10-second delay initiated by the Manual Delay switch. In this example, the total time elapsing from FACP countdown initiation to agent release is 13 seconds, less than the original 15 second FACP Delay Timer countdown. 2. The FACP programmed Delay Time begins its 15 second countdown. The Manual Release Delay switch is pulled when the FACP Delay Timer has counted down to 8 seconds. The 8 seconds remaining in the countdown are overridden by the 10-second delay initiated by the Manual Delay switch. In this example, the total time elapsing from FACP countdown initiation to agent release is 17 seconds, more than the original 15 second FACP Delay Timer countdown. The FACP programmed Delay Time is not running (as would happen if the releasing station were pulled before an alarm registered). The Manual Release Delay Switch is activated by the pull station. Agent release will occur in 10 seconds.
3.
106
Abort Switches
Releasing Applications
The following contains information needed to program a Second Shot switch for a monitor module Description A monitor moduleconnected to a UL-listed manual station (such as the NBG-12LRA)used as for a second release of agents. A Second Shot switch overrides a Delay Timer programmed to the same Releasing Zone. Program Select a monitor module for the manual release function. While programming the module (refer to Section 3.4.2, Module Point, on page 51 for instructions) 1. 2. Select the SECOND SHOT Type Code. Enter the number of the desired releasing zone into the modules zone map. The releasing zone must be fully programmed (refer to Section 3.4.4, Releasing Zone, on page 57).
Example A programming example of a monitor module programmed as a MAN REL DELAY switch for the first shot and a SECOND SHOT switch for the second shot.
SYSTEM N ORMAL SYSTEM ACT IVATED
Type Code
MAN REL DELAY
ZR05
Type Code
SECOND SHOT
Figure B.12 Monitor Module Configured as a Second Shot Switch With two monitor modules configured as shown above, program releasing zone ZR05 for the following releasing selections: Delay Time = 15, Abort Switch = ULI, Cross Zone = Y, Soak Time = 30 ZR05 can be activated in one of two ways, as described in the examples given below. Example 1: If the detector initiates the alarm, ZR05 activates. Releasing begins after the delay timer has expired (15 seconds). Releasing will continue for the soak timer duration (30 seconds). The Second Shot switch can then be activated, and will remain activated for the soak timer duration. Once the soak timer expires, the Second Shot switch can then be activated to initiate an additional soak cycle. Example 2: If the NBG-12LRA (Type Code MAN REL DELAY) lever is pulled, the manual release delay timer begins its 10 second countdown. Releasing will begin after the manual release delay timer has expired, and will continue for the soak timer duration (30 seconds). The Second Shot switch can then be activated, and will remain activated for the soak timer duration. Once the soak timer expires, the Second Shot switch can then be activated to initiate an additional soak cycle.
107
Releasing Applications
Abort Switches
The following contains information needed to program a Release End Bell circuit for an SLC output module. Description An SLC output module to activate an audible or visual device when releasing devices shut off when soak time is complete. Multiple outputs with the REL END BELL Type Code can be mapped to the same Releasing Zone. When the soak timer has expired, all outputs with the REL END BELL Type Code activate at the same time. A REL END BELL circuit remains on until the system is reset. Program Select an SLC output module to use as a Release End Bell circuit. While programming the point (refer to the Point Programming section of this manual for instructions), 1. 2. Select the REL END BELL Type Code, Enter the number of the desired releasing zone into the modules zone map. The releasing zone must be fully programmed (refer to Section 3.4.2, Module Point, on page 51).
Example A programming example of a control module programmed as a Release End Bell for Releasing Zone ZR05.
Monitor Module Detector Detector Detector
ZR05
For example, a module programmed with the REL END BELL Type Code activates when the ZR05 soak timer expires.
108
Abort Switches
Releasing Applications
The following contains information needed to program a ULC Release Circuit for an SLC output module. Description An SLC output module used to activate a releasing solenoid or other releasing device. Multiple outputs with the REL CKT ULC Type Code can also be mapped to the same Releasing Zone. When the Releasing Zone activates, all outputs with the REL CKT ULC Type Code also activate at the same time. A ULC Release Circuit activates when: An initiating device programmed to the same Releasing Zone activates (two devices if using the Cross Zone option) The Delay Timer for the Releasing Zone (if used) expires No Abort Switch for the Releasing Zone (if used) is active
A ULC Release Circuit and all wiring to the release deviceis fully supervised and usable with power-limited energy cable. Program Select an SLC output module to use for a ULC Release Circuit. While programming the point (refer to the Point Programming section of this manual for instructions), 1. 2. Select the REL CKT ULC Type Code, Enter the number of the desired Releasing Zone into the modules zone map. The releasing zone must be fully programmed (refer to Section 3.4.4, Releasing Zone, on page 57).
Example A programming example of a control module programmed as a ULC Release Circuit for Releasing Zone ZR05.
Monitor Module Detector Detector Detector
ZR05
Type Code
REL CKT ULC
Type Code
REL CKT ULC
109
Releasing Applications
Abort Switches
NOTE: Do not use a Release Circuit for the following: An application requiring ULC Listing; An application requiring power-limited energy cable.
The following contains information needed to program a Release Circuit for an SLC output circuit module. Description An SLC output module used to activate a releasing solenoid or other releasing device. Multiple outputs with the RELEASE CKT Type Code can be mapped to the same Releasing Zone. When the Releasing Zone activates, all outputs associated with the releasing zone and with the RELEASE CKT Type Code also activate at the same time. A Release Circuit activates when: An initiating device programmed to the same Releasing Zone activates (two devices if using the Cross Zone option) The Delay Timer for the releasing zone (if used) expires The Abort Switch for the releasing zone (if used) is not active
Program Select an SLC output module to use as a Release Circuit. While programming the point (refer to the Point Programming section of this manual for instructions), 1. 2. Select the RELEASE CKT Type Code Enter the number of the desired Releasing Zone into the modules zone map. The releasing zone must be fully programmed (refer to Section 3.4.4, Releasing Zone, on page 57).
Example A programming example of a control module programmed as a Release Circuit for Releasing Zone ZR05.
Monitor Module Detector Detector Detector
ZR05
Type Code
RELEASE CKT
Type Code
RELEASE CKT
For example, all modules programmed with the RELEASE CKT Type Code activate when the delay timer expires for ZR05. Other outputs (modules A & B) will activate according to their programming.
110
Abort Switches
Releasing Applications
The following contains information needed to program a Release Form-C circuit for an SLC Form-C relay output module. Description An SLC output module, configured as a relay, programmed to activate an output by opening or closing a switch. Typical applications include closing doors and air handlers. Program Select an SLC output module to use as a Releasing Form-C Circuit. While programming the point (refer to the Point Programming section of this manual for instructions), 1. 2. Select the REL. FORM C Type Code, Enter the number of the desired Releasing Zone into the modules zone map. The releasing zone must be fully programmed (refer to Section 3.4.4, Releasing Zone, on page 57).
Example A programming example of a control module programmed as a Release Form-C circuit for Releasing Zone ZR05.
Monitor Module Detector Detector Detector
ZR05
For example, an output module, configured as a Form-C relay, activates simultaneously with other outputs (modules A, B & C) programmed for ZR05.
111
Releasing Applications
Abort Switches
The following contains information needed to program a Release Audible circuit for an SLC output module. Description An output module programmed to activate an audio or visual device when all releasing outputs, programmed to the same Releasing Zone, turn on. Multiple outputs with the REL AUDIBLE Type Code can be mapped to the same Releasing Zone. When the Releasing Zone activates, all outputs with the REL AUDIBLE Type Code activate at the same time. Program Select a control module to use as a releasing circuit. While programming the point (refer to the Point Programming section of this manual for instructions), 1. 2. Select the REL AUDIBLE Type Code, Enter the number of the desired Releasing Zone into the modules zone map. The releasing zone must be fully programmed (refer to Section 3.4.4, Releasing Zone, on page 57).
Example A programming example of a control module programmed as a Release Audible circuit for Releasing ZoneZR05.
Monitor Module Detector Detector Detector
ZR05
For example, an output module programmed with the REL AUDIBLE Type Code activates simultaneously with other outputs (modules A & B) programmed for ZR05.
112
Abort Switches
Releasing Applications
The following contains information needed to program an Instant Release circuit for an SLC output module. Description An SLC output circuit module programmed to activate non-releasing devices, such as door openers or warning sounders, without counting down delay timers. A device programmed with the INST RELEASE Type Code device is supervised for open circuits and ground faults. Program Select an SLC output module to use with a releasing circuit. While programming the point (refer to the Point Programming section of this manual for instructions), 1. 2. Select the INST RELEASE Type Code, Enter the number of the desired Releasing Zone into the modules zone map. The releasing zone must be fully programmed (refer to Section 3.4.4, Releasing Zone, on page 57).
Example A programming example of a control module programmed as an Instant Release circuit for Releasing Zone ZR05.
Monitor Module Detector Detector Detector
ZR05
Type Code
INST RELEASE
Type Code
INST RELEASE
For example, a module programmed with the INST RELEASE Type Code activates simultaneously with other outputs (modules A & B) programmed for ZR05.
113
Releasing Applications
Miscellaneous
The outputs are each set to a code appropriate for one of the three releasing phases: for example, one code for the first alarm, a faster code when the Delay Timer activates, and a continuous tone during releasing. Program Program releasing zone ZR1 as follows: ZR1 = Delay Time:15, Abort Switch:ULI, Cross Zone:YES, Soak Time:120 Map ZR1 to all inputs and outputs shown in this example. Program logic zones as follows: ZL1 = AND(OR(L1D1,L1D2,L1D3,L1D4,L1D5,L1D6),NOT(L1M30)) When conditions are met for ZL1, a first alarm has occurred in the releasing zone, but the Delay Timer has not yet started. Map ZL1 to an output set to the code chosen for a first alarm (L1M31 in this example). ZL2 = AND(L1M30,NOT(L1M20)) When conditions are met for ZL2, the Delay Timer has started, but releasing has not begun. Map ZL2 to the output set to the code chosen for when the Delay Timer activates (L1M32 in this example). ZL3 = OR(L1M20) When conditions are met for ZL3, the 120 second releasing operation has begun. Map ZL3 to the output that produces a continuous tone (L1M33 in this example). Program output Type Codes as follows:
L1M20 = RELEASE CKT, L1M30 = INST RELEASE, L1M31 = CONTROL, L1M32 = CONTROL, L1M33 = CONTROL
Illustration
L1D1 L1D2 L1D3 L1D4 L1D5 L1D6
ZR01
L1M20
L1M30
L1M31
L1M32
L1M33
Type Code
RELEASE CKT
Type Code
INST RELEASE
B.4 Miscellaneous
B.4.1 Initiating Devices
Releasing zone initiating devices include the following: FST-851/751 intelligent heat detectors FSI-851/751, FSP-851/751, FAPT-851/751, FSL-751 intelligent smoke detectors Conventional detection UL-listed devices connected to monitor modules
114
Miscellaneous
Releasing Applications
Multiple zone initiating devices can be used for the same releasing hazard. Map zone initiating devices to the same Releasing Zone. Factory Mutual and certain Local Authorities Having Jurisdiction require using redundant wiring (NFPA 72 Style 6 or Style D) for initiating devices in releasing applications.
115
If PAS=Y, alarm activates outputs if not acknowledged Initial alarm annunciation Alarm activates outputs, if the control panel is not reset
Figure C.1 Presignal and PAS Time The control panel delays activation of outputs containing ZF0 in their zone maps for all alarm initiating devices that contain ZF0 in their CBE list. A subsequent alarm will abort the Presignal Delay Timer and execute CBE lists.
Drill Mode
TM-4 polarity reversal alarm output TM-4 municipal box output UDACT
117
118
A graphic representation of a detector analog reading using drift compensation and smoothing:
Alarm Level
without compensation
Analog Reading
Time
MAINTENANCE REQ Dust accumulation that is near but below the allowed limit. The Maintenance Required is an alert level that indicates the need for maintenance before the performance of the detector is compromised. MAINT.URGENT Dust accumulation above the allowed limit.
100
100
100
Table D.1 Definitions of Intelligent Sensing Maintenance Levels A graphic representation of the maintenance levels:
MAINT.URGENT DIRTY
LOW THRESHOLD
Low Value
Awacs1a.cdr
Time (days)
Figure D.4 Sample Sensitivity Levels for a FlashScan View Laser Detector
120
Awacs4a.cdr
Pre-Alarm
D.3 Pre-Alarm
D.3.1 Definition
The Pre-Alarm function is a programmable option which determines the systems response to realtime detector sensing values above the programmed setting. Use the Pre-Alarm function to get an early warning of incipient or potential fire conditions. There are two levels of Pre-Alarm: Alert (Refer to Alert Level below) Action (Refer to Appendix D.3.3, Action Level, on page 122) Alert and Action Pre-Alarm settings are set with point programming. Unique Pre-Alarm sensitivity levels (PA) for individual detectors are listed in Appendix D.4, Detector Sensitivity Settings, on page 122. The LEDs on detectors polled in FlashScan mode will light steady green when in pre-alarm.
The Pre-Alarm indication for this detector will restore automatically to normal if its obscuration reading drops below pre-alarm level. A subsequent alarm for this detector also clears the Pre-Alarm indication.
Alarm (FlashScan)
AL:1=0.50 % AL:2=0.73 % AL:3=0.96 % AL:4=1.19 % AL:5=1.43 % AL:6=1.66 % AL:7=1.89 % AL:8=2.12 %~ AL:9=2.35 %
Pre-Alarm
PA:1=Auto PA:2=0.30 % PA:3=0.47 % PA:4=0.64 % PA:5=0.81 % PA:6=0.99 % PA:7=1.16 % PA:8=1.33 %~ PA:9=1.50 %
122
Pre-Alarm
PA:1=Auto PA:2=0.40 % PA:3=0.50 % PA:4=0.75 % PA:5=1.00 % PA:6=1.25 %~ PA:7=1.50 % PA:8=1.75 % PA:9=2.00 % PA:1=Auto PA:2=0.02 % PA:3=0.05 % PA:4=0.10 % PA:5=0.20 % PA:6=0.50 %~ PA:7=0.70 % PA:8=1.00 % PA:9=1.50 % PA:1=0.50 % PA:2=1.00 % PA:3=1.00 % PA:4=1.00 to 2.00 % PA:5=1.00 to 2.00 %~ PA:6=2.00 % PA:7=2.00 % PA:8=2.00 to 3.00 % PA:9=2.00 to 3.00 % PA:1=40C PA:2=43C PA:3=57C~ PA:4=65C PA:5=70C PA:6=75C PA:7=75C PA:8=75C PA:9=75C PA:1=50% PA:2=55% PA:3=60% PA:4=65% PA:5=70% PA:6=75% PA:7=80% PA:8=85% PA:9=90% PA:1= 1% PA:2= 2% PA:3= 3% PA:4= 3% w/ 10 minute confirmation period PA:5= 4% w/ 10 minute confirmation period PA:6= Thermal 135F PA:1=1% PA:2=2% PA:3=3% PA:4=3% with a 10 minute confirmation period PA:5=4% with a 10 minute confirmation period PA:6=Thermal 135F
~Signifies
Beam
(See Note )
AL:1= 1% AL:2= 2% AL:3= 3% AL:4= 3% w/ 10 minute confirmation period**** AL:5= 4% w/ 10 minute confirmation period AL:6= Thermal 135F AL:1=1% AL:2=2% AL:3=3% AL:4=3% with a 10 minute confirmation period**** AL:5=4% with a 10 minute confirmation period AL:6=Thermal 135F
Photo/CO
123
Detectors are suitable for open area protection within the listed air velocity range. Typically, this range is 0 - 4,000 ft/min for photoelectric detectors and 0 - 1,200 ft/min for ionization detectors. Be sure to confirm this range before installing the detector by referring to the manufacturers installation instructions. For ION detectors installed in Canada: Use only an alarm sensitivity setting of AL=1, AL=2 or AL=3. 1% max. on CLIP. Larger figures may display. ** The use of alarm sensitivities below 0.50% obscuration per foot requires a 90 day test to ensure that the environment for the detectors is suitable for the higher sensitivity setting. (Refer to To Test Detectors Set Below 0.50% Obscuration per Foot on page 124.) For Acclimate detectors installed in Canada: Use only the alarm settings of AL:1 or AL:2. Refer to the beam detector manual to determine the alarm settings: they are a function of the distance between the detector and its reflector. There is no Prealarm for beam detectors in CLIP mode. *** AL:6 and PA:6 are not available in CLIP mode. ****Within the 10 minute signature confirmation delay period, if there is a detection of another fire signature (Carbon Monoxide, Infrared or Thermal) it overrides the 10 minute confirmation time.
2.
Operate detectors continuously for 90 days with all environmental factors (such as, temperature, humidity, air flow, occupancy, and so on) similar to the intended application for the detectors. Record all events for each tested detector with an electronic History buffer or a printout. At the end of the 90-day test: An authorized Notifier representative, or an end user trained by an authorized Notifier representative must inspect the results of the test. If the test results show no alarms or pre-alarms for the tested detectors, reprogram the fire alarm system to set the Alarm sensitivity to the more sensitive Pre-Alarm level of the test.
3.
124
Press ACCEPT
LAKEVIEW GENERAL HOSPITAL SYSTEM NORMAL 10:22:34A WED DEC 19, 2007 READ ADDRESS: L03D052 AUTOMATIC INACTIVE ELEVATOR LOBBY EAST WING FIFTH FLOOR Z003 SMOKE(PHOTO) Z005, Z027, Z066, , , , , , , , VALUES: 011% OF ALARM, 045% OF PREALARM ALARM: 6= 1.66%, PREALARM: 3= 0.47% ACTION/STATUS: NONE/VERY CLEAN PEAKS:56% VERIFY COUNT:02 CO-OP:D100,158 10:22:34A WED DEC 19, 2007 BACK
Field Identification Long term average of raw analog value in microseconds Current reading of raw analog value in microseconds Extended Label L01D001 000330us 000340us Compensation percentage Detector peak Comp:000% Pk: 002%
State
Label
Alarm:
L01D001 Address
Programmed prealarm sensitivity setting in effect when the report was generated Programmed alarm sensitivity setting in effect when the report was generated.
125
The first field displays the point control. There are three designations that could appear in this field
Point Control Designation Description The point is being controlled automatically by the panel. The point has been forced into a disabled state by an outside source. The point is in a trouble state and is no longer functioning automatically.
The second field displays the point status. There are two designations that could appear in this field.
Point Status Designation Description The point is currently reporting no events. The point is currently in an off-normal status. The point is currently in a prealarm status.
The device is a detector (an input device) so by referring to the descriptions below, it can be determined that the point is in a normal state. Inputs: (detectors, monitor modules, zones) If the point is not in trouble or disabled, and the point is automatically controlled by the panel, the display will be one of the following: AUTOMATIC AUTOMATIC AUTOMATIC INACTIVE ACTIVE PREALARM
If the point is disabled, the display will be one of the following. The Trouble Status field will appear if the point is in trouble. DISABLED DISABLED DISABLED INACTIVE ACTIVE PREALARM <Trouble Status>* <Trouble Status>* <Trouble Status>*
If the point is in trouble, the display will read: TROUBLE TROUBLE INACTIVE ACTIVE <Trouble Status>* <Trouble Status>*
126
TROUBLE
PREALARM
<Trouble Status>*
*The field <Trouble Status> will contain a device trouble message. Refer to this panels Operations manual for information on these messages. Line 7 - The custom label for this point Line 8 - Continuation of the points custom label, first zone, and device type Lines 9, 10 - A display of all the zones that contain the current point being read. Lines 11through 14 -These lines will have values in them only if the device is a detector. They will not display for wireless detectors. Line 11 VALUES: The screen displays the Alarm and Prealarm values that are in effect when read status is requested. For example, if occupied settings are in effect, occupied values will display 121% OF ALARM - This field gives the detector reading as it relates to its preprogrammed alarm level value (indicated in the next line on the screen). The example above shows the detector exceeding the alarm level by 21%. 145% OF PREALARM - This field gives the detector reading as it relates to its preprogrammed prealarm level value (indicated in the next line on the screen). The example above shows the detector exceeding the prealarm level by 45%. If the detector is an Alert heat detector, the value is indicated by a temperature reading (example: 148 DEGREES F). Line 12 The screen displays the Alarm and Prealarm levels that are in effect when read status is requested. For example, if unoccupied settings are in effect, they will display. ALARM: 6=1.66% - Six is the preprogrammed alarm level value for this detector: its value is 1.66%, indicating the percent per foot obscuration value assigned to level 6. PREALARM: 3=0.47% - Three is the preprogrammed alarm level value for this detector: its value is 0.47%, indicating the percent per foot obscuration value assigned to level 3. Line 13 ACTION/STATUS: NONE/VERY CLEAN - This displays the maintenance status of the device. The message that appears in this field depends on the drift compensation value. A detector will automatically compensate for environmental contaminants and other factors over time, until the tolerance value has been exceeded. The FACP will signal a trouble condition when this level has been reached. Refer to the following table for messages and required action.
Message None/Very Clean None/Fairly Clean Needs Cleaning Drift Compensation % Less than 50 50 - 69 70 - 79 Description No action necessary. The detector readings are near ideal. No action necessary. The detector will activate at the selected sensitivity level. Clean the detector soon. The detector may cause a false alarm because it has reached the drift compensation tolerance value. Clean immediately! The detector is a false alarm risk. The drift compensation tolerance value has been exceeded.
80 - 100
Table D.3 Drift Compensation Messages/Actions Line 13 will not display for Acclimate detectors.
NFS2-3030 Programming Manual P/N 52545:G1 06/16/2011 127
Line 14 PEAKS: 56% - This value represents the highest percent per foot obscuration reading taken by this detector. It can be a historical figure, and does not necessarily represent the highest reading for this particular alarm. Re-initializing the detector would reset this value to zero. VERIFY COUNT: 02 - This displays the number of times the detector has gone into alarm. This count aids in differentiating false alarms from actual alarms by showing repeated alarm events that have come into the device. In this example, the detector has gone into alarm two times since the verification count was begun. The FACP will signal a trouble condition when the verify count exceeds 20. CO-OP: D100,158 - Indicates the address(es) of any detector(s) linked with the detector thats in alarm for Co-operative Multi-Alarm Sensing. This field will not display for Acclimate detectors. Line 15 - The current time and date are displayed in this line.
128
Notes
129
E.1 Zones
There are four types of zones that may be listed to a point for CBE purposes.
Zone Type General Zone Description/Function A general zone is used to link input and output devices. When an input device activates, any general zone in its zone map will be active, and any output device that has an active general zone in its map will be active. General zones can be used as arguments in logic equations. Zone Z000 is a general alarm zone: those points listing Z000 in their zone map participate in a general alarm. The panel will support up to 1000 general zones, designated as Z0 through Z999. General zones can be used in CCBE applications when a node number is entered before the zone number. A logic zone consists of a logic equation. Whenever the logic equation becomes true, all output points mapped to the logic zone will activate. The panel will support up to 1000 logic zones, designated as ZL1 through ZL1000. Logic zones can be used in CCBE applications when a node number is entered before the zone number. A trouble zone consists of a trouble equation. Whenever the trouble equation becomes true, all output points mapped to the trouble zone will activate. The panel will support up to one hundred trouble zones, designated as ZT001 through ZT100. Trouble zones can be used in CCBE applications when a node number is entered before the zone number. NOTE: Trouble zones can be used only in CCBE applications between NFS2-3030, NFS-3030 and NFS-640 FACPs. Trouble zones will not activate with other combinations. Releasing Zone A releasing zone is used to control a releasing operation. The panel will support up to ten releasing zones, designated as ZR00 through ZR09.
Logic Zone
Trouble Zone
130
Equations
Special Zone
ZF0 An output participates in Presignal with this special zone in its zone map. ZF1 (Trouble less AC) An output programmed to turn on/off if a system trouble - other than an AC power loss occurs. ZF2 (AC Trouble) An output programmed to turn on/off if an AC power loss or a brownout condition occurs. ZF3 (Security) An output programmed to turn on/off if a Security input activates. ZF4 (Supervisory) An output programmed to turn on/off if a Supervisory input activates. ZF5 Alternate An input programmed to switch from the active detector alarm sensitivities to the Sensitivity Activation alternate alarm sensitivities when a non-fire point with ZF5 in its CBE activates. ZF6 Plant Isolate special zone for Australian Mode. When the Plant Isolate button is pressed, ZF6 will toggle between Normal and Active. ZF7 Drill for Australian Mode. In the event of a drill activation, ZF7 will activate and will remain active until a reset is performed on the fire panel. ZF9 An output programmed to turn on/off if a PreAlarm is active (ALERT, ACTION). ZF10 Any detector or module in alarm verification will activate this zone. ZF11 When the drill key is pushed or drill is performed, ZF11 will go active. When the system reset key is pushed or system reset performed, ZF11 will go to normal. ZF12 When the acknowledge key is pushed, or a block or event acknowledge is performed, ZF12 will go active. After a two-second delay, ZF12 will go to normal. ZF13 When the signal silence key is pushed or a signal silence is performed, ZF13 will go active. After a two-second delay, ZF13 will go to normal. ZF14 When the system reset key is pushed or a system reset is performed, ZF14 will go active. After a ten-second delay, ZF14 will go to normal. ZF15 When there are disabled events present in the system, ZF15 will be set to active. When all disabled events have cleared, the state of ZF15 will go to normal. ZF16 Drill Zone. This zone used when Drill Mode is set to Custom. When a drill is performed on the fire panel, ZF16 will be set to active. ZF16 will return to normal following a system reset. ZF17 Signal Silence for Australian Mode operations. When a signal silence is performed, ZF17 will go active and will remain active until a System Reset is performed. The special zone will only function when Australian Mode is enabled. ZF18 CO Alarm. When a CO Alarm is present, ZF18 will activate. ZF19 CO Pre-Alarm. When a CO Pre-Alarm is present, ZF19 will activate.
Time, date and holiday functions, which were formerly determined through special zones, are now defined in the panel programming section of this manual.
E.2 Equations
Logic and Trouble Equations can define complex relationships between input and output devices. The FACP supports up to 1000 Logic Equations, each designated with a Logic Zone number of ZL1 through ZL1000. It also supports up to 100 Trouble Zones, each designated with a Trouble Zone number of ZT001 through ZT100. Once created, these equations can be included in input/output zone mapping. 1. 2. 3. 4. 5. Equations will always begin with a logic function. The function set is listed below. Equations will be a maximum of 80 characters long, including parentheses and commas. Logic and Trouble Equations can have a maximum of 10 logic functions unless a time delay function is used: a time delay function must be the only function in its equation. Equations are evaluated after all other devices have been evaluated. One logic equation can be used as an argument in another logic equation, or one trouble equation can be used in another trouble equation, only if the equation used has previously been evaluated; that is, only zones with a lower number than the zone currently being edited can be used as arguments. A logic function can have a maximum of 20 arguments (inclusive start and stop address). Maximum for the delay timer is 23 hours, 59 minutes, 59 seconds (23:59:59).
6. 7.
Equations are entered using Point Programming for logic or trouble zones. Refer to these sections in this manual for instruction. The panel will check for errors after the user has entered the complete equation. Possible errors are too many or two few parentheses, too many or two few arguments inside the parentheses, unknown function and unknown device type.
NFS2-3030 Programming Manual P/N 52545:G1 06/16/2011 131
Equations
Equations are made up of two basic components: functions (either logic or time delay) and arguments.
E.2.1 Arguments
Arguments are discrete parts of a logic or time delay function used in a logic or trouble equation. They can consist of another function, another equation, or any of the devices listed below.
LxxD1 - LxxD159 LxxM1 - LxxM159 (Nxxx)Z0 - (Nxxx)Z999* ZF1 - ZF7, ZF9 - ZF19 T0 - T510 (Nxxx)ZT001 - (Nxxx)ZT100 (Nxxx)ZL1 - (Nxxx)ZL1000 detectors loop xx modules loop xx general zones special zones system troubles (trouble equations only) trouble zones logic zones (159 per loop) (159 per loop) (1000) (18) (511) (100) (1000)
xx = loop number (01 through 10) (Nxxx) = Node number, necessary for CCBE programming. The node number identifies what node the panel will watch for a particular zone activation.
132
Equations
Example: XZONE(Z02) If any combination of two or more initiating devices that have been mapped to this software zone come into alarm, then outputs mapped to this zone will activate. The RANGE Operator Each argument within the range must conform to the requirements of the governing function. The range limit is 20 consecutive arguments. Example: AND(RANGE(Z1,Z20)) Zone 1 through Zone 20 must all be active to activate the logic zone. The DIS(point argument) Operator Requires that the point argument be disabled for the operator to go active. The PRE(point argument) Operator Requires that the point argument be in prealarm for the operator to go active. Example: AND(L1D1,PRE(L1D2)) The detector at address L1D1 must be active and the detector at L1D2 must be in prealarm for this equation to go active. The SUP(point argument) Operator Requires that the point argument be in an active supervisory state for the operator to go active. Example: OR(L1D1,SUP(L1M1)) The detector at address L1D1 must be active, or the module at L1M1 must be in an active supervisory state, for the equation to go active. The FIRE(point argument) Operator Requires that the point argument be in an active fire alarm state for the operator to go active. Example: AND(L1D1,FIRE(L1M1),FIRE(L1M2)) The detector at address L1D1 must be active, and the modules at L1M1 and L1M2 must be in an active fire alarm state, for the equation to go active. The NON(point argument) Operator Requires that the point argument be in an active non-alarm state for the operator to go active. Example: AND(L1D1,NON(L1M1)) The detector at address L1D1 must be active, and the module at address L1M1 must be in an active non-fire alarm state, for the equation to go active. The SEC(point argument) Operator Requires that the point argument be in an active security alarm state for the operator to go active. Example: AND(L1M1,SEC(L1M2)) The module at address L1M1 must be active, and the module at address L1M2 must be in an active security alarm state, for the equation to go active.
Time-based Functions
The panel supports three time-based functions: DEL, SDEL, and TIM. Special rules apply to an equation containing a time-based function: Only one time-based function may be used in an equation. The time-based function must appear only once, as the first entry of the equation. It may not be nested within parentheses in the equation. Logic functions may be used in an equation that begins with a DEL or SDEL time-based function: however, they must appear within parentheses following the time-based function. Delay and duration times are in 24-hour format (HHMMSS); the allowable range is 00:00:00 to 23:59:59. The DEL Function
NFS2-3030 Programming Manual P/N 52545:G1 06/16/2011 133
Equations
Used for delayed operation. Example: DEL(HH.MM.SS, HH.MM.SS,AND(L1M1,L1M140)) The first HH.MM.SS is the delay time, the second HH.MM.SS is the duration time. If the argument - AND(L1M1,L1M140) - in the example above activates, the function becomes true after the argument has been active for the delay time, and continues to be true for the duration time as long as the argument stays active. If the argument goes inactive during the delay time or the duration time, the function reverts to false and the timing would begin all over again if reactivated. If duration time of zero is entered (00.00.00), the equation will evaluate true when the delay time expires if the argument remains active throughout the delay time period. If no duration or delay is specified, then the function will follow the input argument, indicating true while it is active and false when it is inactive. DEL assumes a value of false on reset. The SDEL Function A latched version of the DEL function. Example: SDEL(HH.MM.SS, HH.MM.SS,L1M140) The first HH.MM.SS is the delay time, the second HH.MM.SS is the duration time. If the argument (L1M140 in the example above) activates, the function becomes true after the delay time, and will remain active for the duration even if the argument becomes inactive during either the delay or duration time. If delay time of zero is entered (00.00.00), the equation will evaluate true as soon as the argument (L1M140) activates and will remain that way for the specified duration, even if the argument becomes inactive during that time. If no duration or delay time is specified, then the argument will not deactivate until reset, even if the argument becomes inactive. The TIM Operator The TIM function is used to specify activation on specific days of the week or year. Examples: TIM(7-11-06) will evaluate as true for 24 hours starting at midnight (00:00:00) on July 11, 2006. TIM(MO,TU,WE,TH,FR,08:00:00,23:00:00) will evaluate as true at 8:00 AM and remain true until 11:00 PM (23:00) for the list of days supplied. TIM(MO,TU,WE,TH,FR,08:00:00) will evaluate as true at 8:00 AM and remain true until 23:59:59 of the current day for the list of days supplied. TIM(TU,07:45:00,18:30:00) will evaluate as true every Tuesday between 7:45 AM until 6:30 PM. TIM(MO,TU,WE,TH,FR) will evaluate as true from Monday morning at 12:01 AM until Friday evening at 11:59:00 PM. Logic Equation Syntax Example OR(AND(L1D1,L1D4),AND(L2D6,L2M3,NOT(L2M4)),ANYX(2,L1M13,L1M14,L1M15)) Equation begins with a logic function - OR 67 Characters (maximum of 80) - includes parentheses and commas. 5 Logic Functions (maximum of 10) - OR, AND, AND, NOT and ANYX. 8 Arguments (maximum of 20 per logic function) - L1D1,L1D4,L2D6,L2M3,L2M4 The equation contains no spaces. Evaluating an Equation To evaluate an equation, start from the innermost part of the equation and work outwards. For this equation to evaluate TRUE and thus turn on any output mapped to it, the following conditions must be met:
134 NFS2-3030 Programming Manual P/N 52545:G1 06/16/2011
Equations
OR(AND(L1D1,L1D4),AND(L2D6,L2M3,NOT(L2M4)),ANYX(2,L1M13,L1M14,L1M15))
OR
OR
Then all outputs programmed with this equation will be turned ON.
Examples: AND(L1M149,L2M110) will evaluate as true when both arguments go into trouble. OR(ZT049,ZT050) will evaluate as true when either argument goes into trouble.
135
Notes
136
WARNING: IF ANY DETECTOR IS REPLACED WITH A DIFFERENT TYPE OF DETECTOR (FOR EXAMPLE, A LASER DETECTOR IS REPLACED WITH A PHOTOELECTRIC DETECTOR), THE CONTROL PANEL MUST BE PROGRAMMED IMMEDIATELY WITH THE NEW DETECTOR TYPE CODE. FAILURE TO DO SO CAN CAUSE INCORRECT CONTROL PANEL OPERATION, INCLUDING FALSE ALARMS.
137
Point Type
fire supervisory supervisory fire supervisory supervisory fire supervisory supervisory Y Y N Y Y N Y Y N
Activates CBE Y Y Y Y Y Y Y Y Y
Device/Point Function
Ionization smoke detector Ionization smoke detector Ionization smoke detector Duct Ionization smoke detector Duct ionization smoke detector Ionization smoke detector used as a duct detector to report supervisory condition rather than alarm. Photoelectric smoke detector Photoelectric smoke detector Photoelectric smoke detector
SUP L(ION)* SUP T(ION)* SMOKE(DUCTI) SUP L(DUCTI) SUP T(DUCTI) SMOKE(PHOTO) SUP L(PHOTO)* SUP T(PHOTO)*
138
Type Codes
Duct Photoelectric smoke detector Photoelectric smoke detector used as a duct detector to report supervisory condition rather than alarm Photoelectric smoke detector used as a duct detector to report supervisory condition rather than alarm. Wireless Photoelectric smoke detector HARSH smoke detector Laser smoke detector Laser Smoke Detector Laser Smoke Detector Duct Laser smoke detector Laser smoke detector used as a duct detector to report supervisory condition rather than alarm. Laser smoke detector used as a duct detector to report supervisory condition rather than alarm. Combination Photoelectric/CO detector Combination Photoelectric/CO detector. Photo element activation generates a supervisory condition. Combination Photoelectric/CO detector. CO element activation generates a supervisory condition. Assign to one or more FSL-751 detectors used to monitor the quality of air entering the protected area. The air quality measurement allows the VIEW system to compensate for vehicle fumes, fog, or other particles brought into the protected area through the ventilation system. Poor air quality will lower the sensitivity of all FSL-751 detectors on the SLC. The detector sensitivity, however, remains within approved limits (always less than 1% obscuration per foot).
Note: A reference detector still functions as a smoke detector, but the detector sensitivity level should be set to the least sensitive levelAL:9 and PA:9 Alarm and Pre-Alarm sensitivity. Refer to Detector Sensitivity Settings on page 122 for a complete list of detector sensitivity settings.
Y Y Y Y Y Y
Y Y Y Y Y Y
190oF heat detector 190oF heat detector with low temperature warning 135oF intelligent thermal sensor 15oF per minute rate-of-rise detector Combination Photoelectric/heat detector Combination Photoelectric/heat detector with low temperature warning, or Intelliquad FSC-851 Photoelectric Multi-Criteria Smoke Sensor. Multisensor smoke detector Beam Smoke Detector
SMOKE(MULTI) SMOKE(BEAM)
fire fire
Y Y
Y Y
Activates CBE
Y Y Y
Device Function
Alarm-monitoring device Alarm monitoring device, where an open circuit=active. Manual fire-alarm-activating device
Type Codes
Point Characteristics Type Code Point Type Latching (Y=yes N=no)
Y Y Y Y N Y N N Y Y Y Y N N Y Y Y N N Y Y N N N N N N N N N
Activates CBE
Y Y Y Y Y Y N Y Y Y Y Y Y Y Y Y Y N Y N N Y Y Y N N N N Y N
Device Function
Indicates activation of a conventional smoke detector. An FZM-1 must be used for alarm verification of a two-wire conventional detector. Indicates activation of a conventional smoke detector. An FZM-1 must be used for alarm verification of a two-wire conventional detector Monitor for waterflow alarm switch Indicates supervisory condition for activated waterflow switch Used for monitoring building access Monitors building access Used for monitoring audio equipment (use trouble zones for activations) Used for monitoring equipment Monitors 4-20 mA industrial sensors. Indicates activation of security alarm Indicates latching supervisory condition Indicates latching supervisory condition, where an open circuit=active. Monitors for waterflow tamper switches for alarm points Indicates tracking supervisory condition, where an open circuit=active. Monitors a waterflow device Monitors equipment security Indicates activation of tamper switch Performs Acknowledge function Performs function AMG-1 All-call and telephone page Performs Drill function Performs Drill function, activates silenceable fire outputs Monitors non-fire activations Monitors non-fire activations Monitors non-fire activations, where an open circuit=active. Inhibits Positive Alarm Sequence Monitors main and auxiliary power supplies (use trouble zones for activations) Performs Reset function Performs Signal Silence function Performs function of page button on FFT-7. Allows remote paging to a fire area When this point activates it will create a disable on the panel for that point. No CBE generated. Modules can not be disabled via ACS, Alter Status, or over the network. Monitors trouble inputs (use trouble zones for activations) Monitors for a device with no description Monitors for conventional heat detector Wireless alarm-monitoring device Wireless manual fire-alarm-activating device Wireless supervisory-monitoring device Provides an abort function through a monitor module (connected to a UL-listed abort station) for a releasing zone. Provides a manual release through a monitor module (connected to a UL-listed pull station) for a releasing zone Provides a manual release with a 10-second delay through a monitor module (connected to a UL-listed pull station) for a releasing zone Provides a second manual release through a monitor module (connected to a UL-listed pull station) for a releasing zone Monitors for a hazard alert Monitors for a weather alert Monitors for a critical process Monitors for a critical process
SMOKE CONVEN SMOKE DETECT WATERFLOW WATERFLOW S ACCESS MONTR AREA MONITOR AUDIO SYSTEM EQUIP MONITR FMM-420 SECURITY L LATCH SUPERV NC SUP L TRACK SUPERV NC SUP T SPRINKLR SYS SYS MONITOR TAMPER ACK SWITCH ALLCALL PAGE DRILL SWITCH EVACUATE SWITCH FIRE CONTROL NON FIRE NC NON FIRE PAS INHIBIT POWER MONITR RESET SWITCH SIL SWITCH TELE PAGE DISABLE MON
fire alarm fire alarm fire alarm supervisory non-alarm security security trouble non-alarm security userprogrammable security supervisory supervisory supervisory supervisory supervisory security supervisory non-alarm non-alarm
non-alarm*
non-alarm* non-alarm non-alarm non-alarm non-alarm trouble non-alarm non alarm non-alarm disable
TROUBLE MON Blank HEAT DETECT RF MON MODUL RF PULL STA RF SUPERVSRY ABORT SWITCH MAN RELEASE MAN REL DELAY SECOND SHOT HAZARD ALRT WEATHER ALRT PROCESS MON PROCESS AUTO
trouble fire alarm fire alarm fire alarm fire alarm supervisory non-alarm fire alarm fire alarm fire alarm non-fire non-fire critical process critical process
N Y Y Y Y N N Y Y Y N N Y N
N Y Y Y Y Y Y Y Y Y Y Y Y Y
Type Codes
Activates CBE
Y
Device Function
Monitors conventional CO detectors for a CO alarm condition.
CO MONITOR
CO alarm
Type Code
Device Function
CONTROL RELAY BELL CIRCUIT STROBE CKT HORN CIRCUIT AUDIBLE CKT SPEAKER blank NONRESET CTL TELEPHONE CONTROL NAC ISOLATED NAC
Y Y Y Y Y Y Y Y N N Y Y
N N N N N N N N N N N N
Y Y Y Y Y Y Y Y N N Y Y
NAC Relay NAC NAC NAC NAC NAC NAC Relay or NAC Relay NAC NAC
n/a n/a fire fire fire fire fire n/a n/a fire fire fire
ISOLATED SPK
NAC
fire
GEN ALARM
NAC
fire
GEN SUPERVIS
NAC
supervisory
GEN TROUBLE
NAC
trouble
GENERAL PEND
NAC
trouble
TROUBLE PEND
NAC
trouble
ALARMS PEND
NAC
fire
N N
Y Y
N N
fire n/a
Supervised NAC Relay output Supervised NAC Supervised NAC Supervised NAC Supervised NAC Supervised NAC for speaker circuits Supervised NAC for undefined device Supervised output, unaffected by System Reset command Supervised Telephone circuit Supervised NAC Supervised NAC for notification appliance, used with audio isolators. Activates even if there is a short on its NAC circuit. For ULC installations only. Supervised NAC for speaker circuits, used with audio isolators. Activates even if there is a short on its audio circuit. For ULC installations only. Control Module, XPC-8, or an XP5-C (in NAC mode) configured as a Municipal Box Transmitter for NFPA 72 Auxiliary Fire Alarm Systems applications (MBT1 required). This Type ID can also be used for general alarm activation. Control Module, XPC-8, or an XP5-C (in NAC mode) activated under any Supervisory condition (includes sprinkler type). Control Module, XPC-8, or an XP5-C (in NAC mode) activated under any System Trouble condition.This device will not turn ON when it is in trouble (short or open). Control Module XPC-8 circuit, or an XP5-C (in NAC mode) that will activate upon receipt of an alarm and/or trouble condition, and remain in the ON state until all events have been ACKNOWLEDGED. This device will not turn ON when it is in trouble (short or open) Control Module or an XP5-C (in NAC mode) that will activate upon receipt of a trouble condition, and remain in the ON state until all troubles have been ACKNOWLEDGED. This device will not turn ON when it is in trouble (short or open). Control module or NAC for output that will activate upon receipt of an alarm condition, and remain in the alarm state until all alarms have been acknowledged. Supervised for open circuits and ground faults. Short = normal Directs relay outputs to perform a releasing function.
141
Type Codes
RELEASE CKT, REL CKT ULC, REL END BELL REL AUDIBLE FORM C RESET N Y N NAC (SLC only) n/a
FlashScan Codes
Directs outputs to perform a releasing function.Supervised for open circuits and ground faults. Short = normal Directs outputs to perform a release function as required by ULC. Activates NAC audio or visual device when releasing circuits shut off. Activates audio or visual devices steady when releasing starts. Relay module used to interrupt 24V power to fourwire conventional detectors for 30 seconds upon reset. Used in conjunction with a monitor module with a conventional detector Type ID
N N Y N
Y Y Y Y
N N N N
FlashScan Codes
Type Codes
143
System Troubles
System Trouble Index 539 540 541 542 543 544 545 546 547 548 549 550 551 552 553 554 555 556 557 558 559 560 561 562 563 564 565 566 567 568 569 570 571 572 573 574 575 576 577 578 579 580 581 582 583 584
System Trouble Name RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED GROUND FAULT PORT A GROUND FAULT PORT B AMPLIFIER TROUBLE AUXIN TROUBLE DIGIN TROUBLE FFT TROUBLE REMOTE MIC TROUBLE DAP PORT A FAILURE DAP PORT B FAILURE DAA NO ANSWER LOCAL MIC TROUBLE LOCAL PHONE TROUBLE ANALOG OUTPUT A TROUBLE
System Trouble Index 585 586 587 588 589 590 591 592 593 594 603 604 605 606 607 608 609 610 611 612 613 614 615 616 617 618 619 620 621 622 623 624 625 626 627 628 629 630 631 632 633 634 635 636 637 638 639
System Trouble Name ANALOG OUTPUT B TROUBLE ANALOG OUTPUT C TROUBLE ANALOG OUTPUT D TROUBLE FLASH IMAGE ERROR POWER SUPPLY TROUBLE AMPLIFIER LIMIT AMPLIFIER SUPERVISION DAA ADDRESS CONFLICT Reserved Reserved DATABASE CORRUPTED AUDIO LIBRARY CORRUPTED DATABASE INCOMPATIBLE AUDIO LIBRARY INCOMPATIBLE DAA DOWNLOAD IN PROGRESS RESERVED RESERVED PHONE CHANNEL LIMIT EXCEEDED NCM SNIFFER MODE ACTIVE NCM CONNECTION LIMIT EXCEEDED HARDWARE MISMATCH DAL DEVICE NO ANSWER PRIMARY AMP 1 HARDWARE FAILURE PRIMARY AMP 2 HARDWARE FAILURE PRIMARY AMP 3 HARDWARE FAILURE PRIMARY AMP 4 HARDWARE FAILURE BACKUP AMP 1 HARDWARE FAILURE BACKUP AMP 2 HARDWARE FAILURE BACKUP AMP 3 HARDWARE FAILURE BACKUP AMP 4 HARDWARE FAILURE DSBUS 1 COMMFAIL DSBUS 2 COMMFAIL DSBUS 3 COMMFAIL DSBUS 4 COMMFAIL AA TROUBLE BUS FAIL NFN PAGING CHANNEL LIMIT EXCEEDED BACKUP AMP LIMIT PRIMARY AMP 1 LIMIT PRIMARY AMP 2 LIMIT PRIMARY AMP 3 LIMIT PRIMARY AMP 4 LIMIT BACKUP AMP 1 LIMIT BACKUP AMP 2 LIMIT BACKUP AMP 3 LIMIT BACKUP AMP 4 LIMIT PRIMARY AMP 1 OVERCURRENT
System Trouble Index 640 641 642 643 644 645 646 647 648 649 650 651 652 653 654 655 656 657 658 659 660 661 662 663 664 665 666 667 668 669 670 671 672 673 674 675 676 677 678 679 680 681 682 683
System Trouble Name PRIMARY AMP 2 OVERCURRENT PRIMARY AMP 3 OVERCURRENT PRIMARY AMP 4 OVERCURRENT BACKUP AMP 1 OVERCURRENT BACKUP AMP 2 OVERCURRENT BACKUP AMP 3 OVERCURRENT BACKUP AMP 4 OVERCURRENT RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED DSBUS 1 AC FAIL DSBUS 2 AC FAIL DSBUS 3 AC FAIL DSBUS 4 AC FAIL DSBUS 1 HIGH BATT DSBUS 2 HIGH BATT DSBUS 3 HIGH BATT DSBUS 4 HIGH BATT DSBUS 1 LOW BATT DSBUS 2 LOW BATT DSBUS 3 LOW BATT DSBUS 4 LOW BATT DSBUS 1 SELF TEST FAIL DSBUS 2 SELF TEST FAIL DSBUS 3 SELF TEST FAIL DSBUS 4 SELF TEST FAIL PRIMARY AMP 1 FAIL PRIMARY AMP 2 FAIL PRIMARY AMP 3 FAIL PRIMARY AMP 4 FAIL BACKUP AMP 1 FAIL BACKUP AMP 2 FAIL BACKUP AMP 3 FAIL BACKUP AMP 4 FAIL BACKUP AMP NOT INSTALLED BACKUP AMP 1 NOT INSTALLED BACKUP AMP 2 NOT INSTALLED BACKUP AMP 3 NOT INSTALLED BACKUP AMP 4 NOT INSTALLED
REMOTE DISPLAY 29 TROUBLE 441 REMOTE DISPLAY 29 NO ANSWER 442 REMOTE DISPLAY 30 TROUBLE 443 REMOTE DISPLAY 30 NO ANSWER 444 REMOTE DISPLAY 31 TROUBLE 445 REMOTE DISPLAY 31 NO ANSWER 446 REMOTE DISPLAY 32 TROUBLE 447 REMOTE DISPLAY 32 NO ANSWER 448 SYSTEM INITIALIZATION 449-502 RESERVED 503 504 505 506 507 508 509 510 511 512 513 514 515 516 517 518 519 520 521 522 523 524 525 526 527 528 529 530 531 532 533 534 535 536 537 538 SOFTWARE MISMATCH NO POWER SUPPLY INST LOOP 1-2 COMM FAILURE LOOP 3-4 COMM FAILURE LOOP 5-6 COMM FAILURE LOOP 7-8 COMM FAILURE LOOP 9-10 COMM FAILURE TEST PROGRAM UPDATE RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED
145
System Troubles
BASIC WALK TEST BATTERY BUZZER OFF-LINE CHARGER FAIL CORRUPT LOGIC EQUAT DAA ADDRESS CONFLICT DAA DOWNLOAD IN PROGRESS DAA NO ANSWER DAL DEVICE NO ANSWER DAP PORT x FAILURE
DISPLAY NODE LIMIT EXCEEDED The number of display nodes on the network has been exceeded. This trouble will only be displayed if at least one of the NFS2-3030s on the network are in Network Display Mode and the total number of display nodes has exceeded 25. Remove one or more display nodes to correct this trouble. (Display nodes include NCA, NCA-2, a Gateway node, or an NFS2-3030 in Network Display Mode.) DRILL INITIATED Drill has been initiated locally. DRILL RECEIVED Drill has been initiated remotely. DSBUS x AC FAIL The DSBUS at address x has lost AC power. Check wiring and source. DSBUS x COMMFAIL The DSBUS at address x is not communicating with the fire panel. Check wiring and source.
System Troubles
SYSTEM TROUBLES TROUBLE MESSAGE TYPE DSBUS x HIGH BATT TROUBLE DESCRIPTION The battery voltage for the DSBUS at address x has exceeded 28 V. If the batteries are shared, ensure that only one power supply is charging the batteries. Remove the batteries and measure the charging voltage from the supply to ensure it is not exceeding 27.6 V. Call Technical Services. The battery voltage for the DSBUS at address x has fallen below 20.4 V. Charge or replace batteries. A device on the DSBUS at address X has failed self test. Reboot the device. If this does not repair it, update the software of the device. If the self test fail trouble continues to be displayed, call Technical Services. The application and/or boot code is corrupt. Service required. The external RAM test failed. Service required. The software is corrupt. Re-download the panel code software from VeriFire Tools. If the trouble does not clear, call Technical Services. There is a short or open on an FFT riser on a Digital Audio Loop. Check that the DVCs 4-wire switch is set properly and that there is an end-of-line resistor in place for 2-wire operation. A ground fault has occurred within the panel. There is a ground fault on loop x. A ground fault has occurred on DAP x (A or B). The device installed does not match what was previously installed. Install the correct device. The internal RAM test failed. Service required. An invalid node type has been mapped to the NFS2-3030 for Network Display Mode. Check network mapping and correct. Refer to Limitations on page 152 for valid network types. The internal RAM test failed. Service required. Communication has been lost with an LCD-80. A program or database download is in progress. The panel is NOT providing fire protection during the download. Proper authorities should be notified while a download is in progress so that other means of fire protection can be supplied. The DVCs local microphone is in trouble. There is no communication, or paging has been enabled for over 28 seconds and no signal has been received. Investigate whether the mic is plugged into the DVC, or whether there is a problem with the local mic. The DVCs local FFT handset is in trouble. There is no communication, or paging has been enabled for over 28 seconds and no signal has been received. Investigate whether the handset is plugged into the DVC, or whether there is a problem with the handset. Loops x and x are not responding. The LCM and LEM for those loops must be serviced. Local initiation of DRILL Network initiation of DRILL An annunciator has been placed in manual mode. Communication lost between CPU2-3030 or DVC and network communications module. More than two panels have been connected to a high-speed network communications module. The network is in a diagnostic state. Communication lost between NCM Port x and corresponding node. The brand of this panel is incompatible with this network. More than 1 fire panel or more than 4 DVCs has been mapped to the NFS2-3030 for Network Display Mode. Check network mapping and correct. Multiple paging sources are attempting to page over the NFN, exceeding the limit of one (1). reduce the number of paging sources to clear this trouble. This message occurs every day at 11 am if any troubles exist. Battery backup and/or clock backup is low. Replace battery. No devices are installed on the system. The address of the main power supply has not been entered. The panel door is open. The DVC has allocated all its phone channels, and there are still phones ringing in requesting more channels. There is a communication failure with the DAA onboard power supply. Call Technical Services. The Primary Amp at address x has failed. Call Technical Services. The Primary Amp at address x has had a hardware failure. Call Technical Services.
EPROM ERROR EXTERNAL RAM ERROR FLASH IMAGE ERROR FFT TROUBLE GROUND FAULT GROUND FAULT LOOP x GROUND FAULT PORT x HARDWARE MISMATCH INTERNAL RAM ERROR INVALID NODE TYPE MAPPED INTERNAL RAM ERROR LCD80 SUPERVISORY LOADING...NO SERVICE
LOOP x- x COMM FAILURE MAN EVAC INITIATED MAN EVAC RECEIVED MANUAL MODE ENTERED NCM COMM LOSS NCM CONNECTION LIMIT EXCEEDED NCM SNIFFER MODE ACTIVE NETWORK FAIL PORT x NETWORK INCOMPATIBILITY NETWORK MAPPING LIMIT EXCEEDED NFN PAGING CHANNEL LIMIT EXCEEDED NFPA 24HR REMINDER NVRAM BATT TROUBLE NO DEV. INST ON L1 NO POWER SUPPLY INST PANEL DOOR OPEN PHONE CHANNEL LIMIT EXCEEDED POWER SUPPLY TROUBLE PRIMARY AMP x FAIL PRIMARY AMP x HARDWARE FAIL
147
System Troubles
SYSTEM TROUBLES TROUBLE MESSAGE TYPE PRIMARY AMP x LIMIT TROUBLE DESCRIPTION The Audio Circuit of the Primary Amplifier at address x has been overloaded or shorted so the Audio Signal has been attenuated. Check wiring and source and ensure that there are no shorts. The Primary Amplifier at address x has overloaded and shut down. Check the total Load calculations fir the DS-AMP and/or DS-BDA and ensure the total values do not exceed 120 watts.
Communication loss with printer. Restore power and/or printers online status. Add paper. The database that houses the panels programming is corrupt. It must be re-downloaded, or all programming must be cleared and re-entered. Service required. PROG MODE ACTIVATED A user is currently using the panels programming menus. REMOTE DISPLAY x NO ANSWER The remote display at address x is not responding. REMOTE DISPLAY x TROUBLE The remote display at address x is in trouble. REMOTE MIC TROUBLE The DVCs remote microphone is in trouble. It is installed and supervised, but no signal is coming from it. Investigate and fix. SELF TEST FAILED SOFTWARE MISMATCH Diagnostic test failed. Service required. Call Technical Services. One or more LCM or DAA software revisions do not match other LCMs or DAAs, and/or the network communications module is not network version 5.0, or LCD-160 software is incompatible. Update the software as necessary. Service required. Call Technical Services. There is an open circuit on the positive side of loop x. Style 6 and Style 7 are supervised methods of communicating with addressable devices. If the control panel detects a trouble (open only), it will drive both ends of the loop, maintaining communication in an unsupervised method. The latching trouble will display on the panel as a Style 6 trouble until you correct the condition and press reset. Style 7 configuration of the SLC requires the use of ISO-X modules. There is an open circuit on the negative side of loop x. Style 6 and Style 7 are supervised methods of communicating with addressable devices. If the control panel detects a trouble (open only), it will drive both ends of the loop, maintaining communication in an unsupervised method. The latching trouble will display on the panel as a Style 6 trouble until you correct the condition and press reset. Style 7 configuration of the SLC requires the use of ISO-X modules. Style 6 and Style 7 are supervised methods of communicating with addressable devices. If the control panel detects a trouble (open or short), it will drive both ends of the loop, maintaining communication in an unsupervised method. The latching trouble will display on the panel as a Style 6 trouble until you correct the condition and press reset. Style 7 configuration of the SLC requires the use of ISO-X modules. One or more devices (detectors or modules) can not report activation. This can occur following system startup, when exiting Walk Test, or following a device trouble of No Response.
SYSTEM INITIALIZATION
148
I.1 Singapore
The REGIONAL SETTING choice of SINGAPORE activates the following features: Does not allow the disabling of a bell circuit either locally or via the network. A BELL CIRCUIT Type Code will allow power monitoring. The panel will sound the piezo when local control is set to OFF. Does not turn ON the System Trouble LED or the System Trouble relay for disabled points. Does not turn ON the System Trouble LED, the System Trouble relay, or the piezo when Drill is initiated. Turns ON keypad LEDs, PCB LEDs, and all ACM-24/48 LEDs during Lamp Test. Requires the user to initiate the start of the application when the panel boots/reboots. The CPU Failure LED will be ON until the user initiates startup. (Refer to Figure I.2.)
TROUBLE LOADING..NO SERVICE LAKEVIEW GENERAL HOSPITAL BOOTLOADER
N083
CONTINUE
ABORT
Regional Settings
Chicago
I.2 Chicago
The REGIONAL SETTING choice of CHICAGO disallows local drill or signal silence. The DRILL and SIGNAL SILENCE keys at the panel will not function. Annunciator Control Modules and SLC modules given a drill or signal silence Mode or Type Code will not allow local drill or signal silence initiation. Events must be acknowledged prior to system reset.
I.3 Australia
The REGIONAL SETTING choice of AUSTRALIA activates the following features: allows use of the Australian smoke control module SCS-8AU. Brigade Act LED is controlled by ZL1000. Test LED is lit during walktest. Ability to manually corrupt memory to test memory corruption detection. Special passwords for testing memory corruption detection. corrupta will temporarily corrupt a location in the application. corruptb will temporarily corrupt a location in the boot. corruptd will temporarily corrupt a location in the database. reset will uncorrupt the panel and reboot. Plant Isolate button will disable/enable ZL999. Use special function zone ZF6 with ZL999. No softkeys on the panel will function while there is an unacknowledged alarm EXCEPT scroll, silence, reset and disable. Silence Buzzer key acknowledges everything before silencing. Special Function Zone ZF17 may be used with Signal Silence. When a Signal Silence is performed, ZF17 will go active and remain active until a System Reset is performed. Disable key disables the current event on the screen. Special Function Zone ZF7 may be used for Drill. When the drill key is pushed or a drill performed, ZF7 will go to active. When the system reset key is pushed or a system reset is performed, ZF7 will go normal. Fan control function per AS/NZS 1668:1:1998, section 4.13.2. First zone in alarm displayed at top of display. Additional zones in alarm also displayed, until panel reset. Alarm zones not currently on display may be viewed using the scroll button. Security events will light the supervisory LED. The supervisory scroll key will scroll through security events. Display acknowledged and unacknowledged alarms at the same priority. Pre-alarm events will be displayed after alarms. The Main Menu includes an Other events menu key to scroll through other events. Password Bypass Timer enabled. After entering a valid password, the user does not need to enter a password again until no key is pressed for ten minutes. Active Output events are displayed if Output Activations are enabled in the Event Logging menu. Disable/Enable button will disable or enable the currently-displayed event. AMPS-24 supervision disabled. When the primary supply is not an AMPS-24, selecting AUX trouble supervisory setting will generate a general power supply fault.
150
China
Regional Settings
I.4 China
The REGIONAL SETTING choice of CHINA activates the following features: POM-8A support. Active output events displayed. A counter is displayed for active outputs. Municipal Communication panel settings. New special function zone for alarm verification. Prealarm automatically cleared after five minutes. Co-op detectors alarm functions Dual alarm window. Points in trouble will not activate. Ten minute limit for DEL and SDEL delay functions. Disable events do not light LED or trip the trouble relay. No system trouble generated upon entering program mode. Low AC operation of FACP. Power supply troubles. Ability to manually corrupt memory to test memory corruption detection.
151
J.1 Limitations
When in Network Display Mode: 1. Only the following network node types can be mapped to the NFS2-3030: NFS2-3030 NFS2-640 NFS-320 DVC NFS-640 NFS-3030
2. 3.
Read Status, Control On/Off, Disable/Enable, and Network Control-By-Event will only function for the nodes that are mapped to the NFS2-3030. The number of display type nodes for the entire network is limited to a total of 25. Display nodes include NCA, NCA-2, a Gateway node, or an NFS2-3030 in Network Display Mode.
Auto Silence
In Network Display Mode, the Auto Silence feature also applies to any network nodes mapped to the NFS2-3030.
NOTE: Initiating an Acknowledge, System Reset, Signal Silence or Drill on a network node mapped to the NFS2-3030 may affect nodes that are not participating in Network Display Mode through Logic Zone Programming.
152
Glossary
0.1 Glossary
This section contains descriptions of terms essential to know when programming the control panel. Alarm History See History buffer. Alarm Verification Timer A user-defined global software timer function that can reduce the number of nuisance alarms. When you select Alarm Verification for a detector, the control panel delays an alarm signal for a user-specified time period. (The control panel ignores the Alarm Verification Timer if it detects another alarm during the verification period.) Argument An argument is a discrete part of a logic function used in a CBE logic or trouble equation. It can consist of panel/SLC addresses for detectors, modules, zones, special function zones, logic or trouble equations. Auto Silence Timer A user-defined global software timer that functions like pressing the signal silence key. The control panel silences all active outputs programmed as silenceable once the timer has reached the selected time. For example, if 20 minutes is selected, when the timer reaches 20 minutes the control panel turns off all active outputs programmed as silenceable. Autoprogram A software routine that directs the control panel to identify and automatically load SLCconnected devices into the program with default values for all parameters. The Autoprogram Finds and displays all new or missing intelligent detectors and modules-while ignoring devices already installed in memory--so you can edit default option selections. Typically, you Autoprogram the control panel as a first step in a new installation, or to add devices. Control module An addressable module that a) switches power to a Style Y or Style Z NAC; or b) functions as a Form-C control relay. CBE (Control-by-Event) A programming method that lets you map inputs and outputs to provide a variety of output responses based on various initiating conditions (events). CLIP poll - Classic Loop Interface Protocol - CLIP - is standard polling of each intelligent device (as differentiated from FlashScan poll, a method of group polling described below). DCC (Display and Control Center) - Term for a display location, programmed to participate in DCC, when it has control of Acknowledge, Signal Silence, System Reset and Drill functions.
Drift Compensation An algorithm which permits the maintenance of a constant smoke detector sensitivity by accounting for environmental contaminants and other factors. Download A function for loading a system program from a file on a personal computer and storing the program in system memory of the control panel. Also see VeriFire. FlashScan poll - a patented system (US Patent Number 5,539,389) that enhances the speed of communication between analog intelligent devices. Communication is in a grouped fashion. When one of the devices within the group has new information, the panel CPU stops the group poll and concentrates on single points. History buffer The control panel maintains a history buffer of the last 4000 events, each with a time and date stamp. History events include all alarms, troubles, operator actions, and programming entries. The control panel also maintains a 1000-event Alarm History buffer, which consists of the 1000 most recent alarm events from the 4000-event history buffer. latching An attribute of a device that keeps it in an active state until the condition causing the activation is corrected and the panel is reset. Missing device A device that exists in a program, but is not found by the control panel during Autoprogram, typically because the device is disconnected. NAC (Notification Appliance Circuit) A circuit or path directly connected to a notification appliance device (a fire alarm system component--such as a bell, speaker, strobe, and so on--that produces an audible output, a visual output, or both). On this panel, NACs can be transponder points or control modules. New device A device connected to the control panel, but not in program memory. Non-latching An attribute of a device that follows the state of the fire alarm system. That is, if a device is non-latching, it returns to its normal state automatically when the condition clears. Notification Appliance Circuit see NAC. Obscuration A reduction in the atmospheric transparency caused by smoke, usually expressed in percent per foot. Output circuit A control module connected to the SLC.
153
Glossary
Point A system memory address occupied by an addressable SLC device, Software Zone, or annunciator. For example, the control panel considers L01M102, a module on loop 1 at address 102, as a point. Panel sounder The piezo sounder on control panel, that pulses when troubles and alarms occur. Primary zone The zone in the first position of a points zone map. The FACP looks at this zone for certain functions, such as some Cross Zone activations or Walk Test participation. Silence Inhibit Timer A user-defined timer that disables the signal silence key function for the programmed time (0-300 seconds) when a fire alarm occurs. All subsequent alarms can be silenced immediately. SLC (Signaling Line Circuit) A physical wire loop used to connect addressable detectors and modules to the control panel. General Zone A label, internal to the fire alarm system, assigned to a group of addressable devices. Switch Inhibit A software function that allows the programming of control modules and NACs so an operator cannot manually activate NACs. With Switch Inhibit enabled, an operator cannot manually activate the NACs from the control panel. System Normal message A message that displays on the second line of the LCD display during normal operation of the control panel. System Reset Pressing the System Reset fixed function key will clear all latched alarms and other events if the initiating condition is gone. LEDs associated with these events will turn off. Unacknowledged events will not prevent reset from functioning. If alarms or other offnormal events exist after reset, they will resound the system. The System Reset key will not function if the programmable Silence Inhibit timer is running. The System Reset key will not immediately silence active outputs. If the Control-by-event programming for the output evaluates false after reset, the output will deactivate. (Typically this is 30 seconds local, 60 seconds network.) Terminal Interface EIA-232 bidirectional serial port used for upload and download functions. Tracking An attribute of a device that allows it to enter an active state when a condition causes its activation, then to return from an active to an inactive state when the condition causing its activation is corrected. Type Code A Type Code is a software function that specifies the function of a detector, control module, monitor module, transponder point, or NAC. (You can select a Type Code while programming a point). The
154
Type Code specifies what action the control panel takes when the point activates. For example, when a monitor module with evacuate as a Type Code activates, the control panel activates all outputs, as if someone pressed the drill key. Upload A function for making a copy of a system program and storing the program as a file on a personal computer. Also see VeriFire Tools Programming Utility. View (Very Intelligent Early Warning) System A smoke detection system, consisting of the NFS2-3030 control panel and intelligent laser detectors, that provides very early warning of smoldering fires. VeriFire Tools Program Utility A software utility for uploading and downloading a system program between a personal computer and the control panel through the EIA-232 port. Walk Test A feature that lets a single (qualified) maintenance person test a fire alarm control panel and initiating devices without causing the control panel to enter into an alarm state. Zone Map SLC inputs (detectors and monitor modules) and outputs (control modules) provide for up to ten zone selections for CBE.
Glossary
155
Index
A
Abort Switch 95 AHJ 101 Basic configuration example 96 Configuration example with monitor module 104 IRI 98 NYC 99 To program 104 Type Code (ULI, IRI, NYC, AHJ) 57, 94 ULI 97 AC Fail Delay 26 ACCEPT soft key, about 11 Acclimate, detector sensitivity settings 123 Acknowledge AKS-1 36 Local control 21 ACPS-2406 27 ACPS-610 27 ACS Annunciation, releasing applications 115 Number of annunciator devices per circuit 29 Point Programming 31 Programming Mode 31 Point 31 Source 33 Smoke control devices 29 TM-4 29 Type 30 UDACT 29 UZC Zone Coder 29 Action level, prealarm 122 Address To display 22 Advanced Warning Addressable Combustion Sensing see Intelligent Sensing Applications AHJ Abort Switch 101 AKS-1 keyswitch, functions 36 Alarm Sensitivity Levels 120 Alarm, to set 48 Prealarm, to set 48 Table, displayed on screen 48 To select 72, 122 Alarm Verification 26, 47, 52, 153 Alert Level, pre-alarm 121 ALL CALL 32 Alter Status 6983 Clear History 73 Alarm, Event or All History 74 Clear Verify Counters 73
156
Control On/Off 81 Force On/Off 82 Point select 82 Detector Alarm Sensitivity 71 Occupied & Unoccupied Alarm & Prealarm Sensitivity 72 Point Select 71 Disable/Enable 70 Point selection for disable/enable 69 Program Time/Date 81 Walk Test Advanced 75 Audible 75 Disable ACS Boards 77 Panel test screen 80 Parameter 76 AMG 12, 30 AMPS-24 27 Annunciator Address format 43 Annunciator, See ACS 30 Application Corrupt Screen 88 Argument 132, 153 Arrow keys 11 Audio Volume Control 62 auto program 20 Auto Silence 27, 153 Autoprogram 6468, 153 Auxiliary Control Functions, releasing applications 115 Auxiliary trouble reporting 35 AWACS see Intelligent Sensing Applications
B
BACK soft key, about 11 Beam detector sensitivity settings 48, 123 Blink Mode 40 Bootloader Screen 86
C
Canada Auto Silence Value 27 Event ordering 21 ULC installation Alarm Verification timer value 26 CAUTION Do not mix general zones with other sources... 34 Mapping of inputs not associated with Primary Zones 102 On systems utilizing the DCC function 23
Index
DF
CBE (Control-by-Event) 130, 153 CCBE (Cooperative Control-By-Event) 130 Channel A,B thresholds 19 Clear ACS programming 63 All programming 63 History 73 Loop programming 63 Panel programming 63 Verify Counters 73 CLIP Mode 40 Communication loss, panel & SLC 47 Control Module 153 See Module, SLC Control On/Off 81 Cooperative Multi-Detector Sensing 47, 121 CPU2-3030 35 Cross Zone 94 Programming example 102 To activate a Releasing Zone 102 Types 102, 103 CRT Supervision 35 Custom Action message Detector 47, 48 Module 52 To create 41 To view 41 To view, point 48 Custom Drill Mode 117 Custom Tone Setup 24
D
DAA-5025/DAA-5070 62 Address format 43 DCC Participation 23 Default settings soft key 23 Default Timers soft key 28 Delay Time 94 Delete point 63 Delete Program 63 Clear ACS programming 63 All programming 63 Loop programming 63 Panel 63 Delete point 63 Delete Program Menu, when programming panel the first time 17 Detector Address format 43 Alarm Sensitivity Levels 48, 71, 120 Alarm Verification 47 Custom action message 47 Drift Compensation 118 Extended label 44 FlashScan code label 44
Label 44 Local Mode 47 Maintenance Level messages 119 Maintenance Warning 119 Multi-Detector (Coop) 47 Occupancy Schedule 49 Point programming 44 Poll 40 Pre-Alarm Sensitivity Level 120 Print a Detector Maintenance Report 125 Sensitivity 47 To replace 137 To test detectors set below 0.50% obscuration per foot 124 Type Codes 44 Weekly Occupancy Schedule 49 Zone map 44, 45 Disable/Enable Point Selection 69 Displayless Mode Service-level switches, ACK, SIG-SIL, SYSRST, LAMP 11 Do not assign Releasing Type Codes to Panel Circuits 141 Download 153 Download screen 88 Drift Compensation 118, 153 Graphic representation 119 Drill AKS-1 36 Local control 21 Drill Mode 24, 117 Drill Zone 117 DVC/DAA Address format 43 DVC/DVC-EM 62
E
Equations Arguments 132 Editing 58 Logic 131 Functions 132 Time-based functions 133 Trouble 135 Event Counts Display 15 Event logging 42 Event ordering Canada Event Order 21 USA Event Order 21 Extended label 44, 51
F
Factory default settings Password 12 FCM-1-REL releasing module 57 Field information, how to enter 11
157
GM
Index
Fixed position, detector zone map 46 FlashScan code label 44, 51 Force On/Off (point) 82 FSC-851 detector sensitivity settings 123 FST-751 120 FZM-1 & alarm verification 52
G
General Zone 56, 154 Address format 43 Group Zone Disable 70
H
Heat (Adjustable Threshold), detector sensitivity settings 123 History buffer 153 History Display 15 Holiday menu 42
I
Initial programming Basic procedure 12 Initiating Devices for releasing zones 114 Insert (Logic equation screen) 59 Instant Release Circuit Control module configuration example 113 To program 113 Intelligent Sensing Applications 118128 Cooperative Multi-Detector Sensing 121 Detector Sensitivity 120 Drift Compensation 118 Features 118 Maintenance Warnings, 3 levels 119 Self-Optimizing Prealarm 120 Smoothing 118 Intelliquad detector sensitivity settings 123 Ion detector sensitivity settings 123 IP Access 19 IRI Abort Switch 98 ISO-X module 148
Intensity up 28 Language 28 LCD-160 Download Menu Address 86 Language 87 LCD-80 36 LCM Download Menu 87 LCM Local Mode, See Local mode 22 Local control 21 Local mode 22, 47, 53, 55 Local Receive mode 21 Logic equations, editing 58 Logic Zone 58, 130 Address format 43 Loop Download Menu Download Type 87 Loop Address 87 Loop programming 40 CLIP 40 Configuration 39 Detector poll 40 FlashScan 40 Module poll 40 Rapid poll 40 Wiring style 40
M
Main Menu 11, 15 Main Power Supply Address 35 Maintenance Warnings 119 Major changes and additions Basic procedure 12 Manual Release Delay Switch Monitor module configuration example 106 To program 106 Manual Release Switch Monitor module configuration example 105 To program 105 Master password, see Password 13 Maximum verification count 26 Menu Hierarchy 89 Module Address format 43 Module poll 40 Module, SLC Control 55 Custom action message 52 Local mode 55 Silenceable 56 Switch inhibit 56 Walk test 56 Zone map 55 Extended label 51 FlashScan Code label 51
L
Label, point 44, 51 Language selection 28 LCD-160 87 latching 153 LCD Programming 28 LCD programming Backlight 29 Current setting 29 Factory default setting 29 Intensity down 28
158
Index
NP
Label 51 Module Type (Control/Monitor) 51 Monitor 52 Alarm verification 52 FMM-4-20 53 Local control 53 Zone map 52 Type Codes 51 Monitor Module, see Module, SLC Multiple Event List 15 Multiple Events List screen order of events 21
N
NAC (Notification Appliance Circuit) 153 Navigating Menu and Programming Screens 11 NBG-12LRA 95, 104, 105, 106, 107 Network Display Mode 152 network mapping 20 Network Parameters 18 Channel threshold 19 Node Label 19 Number, range 19 Standalone 19 To view 19 Wiring style 19 NFPA Standards for Releasing Applications 95 NFS2-3030 Displayless Mode 11 Two basic configurations 11 Node label 19 Node number 19 For standalone panel 19 Range 19 To view 19 Non-fire activations Event logging 42 Non-latching 153 Note Clearing all programs is not necessary when (VeriFire) 17 NYC Abort Switch 99
O
Obscuration 153 Occupancy Schedule 37, 49 Holidays 42 Output activations Event logging 42 Output circuit 153 Overwrite (logic equation screen) 59
P
Panel programming, see Programming, Panel setNFS2-3030 Programming Manual P/N 52545:G1 06/16/2011
tings Panel settings 21 AC Fail Delay 26 Alarm Verification timer 26 Auto Silence 27 Auxiliary trouble reporting 35 Custom Action message 41 Default Settings 23 Default Timers 28 Display Address 22 Event logging 42 Event Ordering 21 Holiday menu 42 Local Control 21 Local mode 22 Local Receive mode 21 Loop configuration 39 Loop programming 40 Maximum verification count 26 PAS 27 Password 37 Piezo 21 Poll types 40 Presignal delay 28 Proprietary Supervising Station 21 Reminder Menu 22, 25 Remote Display Menu 38 Silence Inhibit 27 Supervision 35 CRT 35 Main power supply address 35 Printer 35 Tamper input 35 Timers 26 Trouble reminder 26 Verify-Prealarm 27 Weekly occupancy schedule 37 Panel sounder 154 Panel Timers 26 PAS (Positive Alarm Sequence) 116 Inhibit switch 116 Setting 27 Password 12, 37 Factory default settings 12 Incorrect or forgotten 14 Master 12, 13 User 12, 13 Level of access 14 Piezo 21 Point 154 Selection for programming 43 Point Program 43 Autoprogram 64 Delete Point 63 Detector point 44 See also Detector Disable/Enable Point 69
159
RS
Index
Module Point, SLC 51 See also Module, SLC Point select 43 Zones 5661 Poll types 40 Position 10 in zone map 46 Position 9 in zone map 46 Position one in zone map 44, 52, 55 Power Management Mode 22 Power-up Screen 85 Pre-Alarm 121 Action Level 122 Alert Level 121 See also Alarm Sensitivity 120 Self-optimizing 120 Sensitivity Levels 120 To select sensitivity 122 Prealarm (Action), fixed position zone 46 Presignal delay 28 Presignal Delay Timer/PAS 116 Primary zone 44, 102, 154 Printer Functions 16 Printer supervision 35 Program Time/Date 81 Program/Alter Status 16 Programming ACS 29 Alter Status 6983 Autoprogram 64 Delete program 63 Detector point 4449 First time, Delete Program Menu 17 LCD screen 28 Module point 5156 Control 55 Monitor 52 See also Module Panel 1843 See also Panel settings Point 4368 See also Point Program Presence of unacknowledged alarm 12 See also Point Program, Panel settings Two levels Alter Status 17 Program 17 Zones 5661 programming 57 Proprietary Supervising Station 21
Regional Settings 23, 149 Release Audible Circuit Output module configuration example 112 To program 112 Release Circuit Output module configuration example 110 To program 110 Release Code Bell Circuit Configuration example 114 To program 113 Release End Bell Circuit Output module configuration example 108 To program 108 Release Form-C Circuit Output module configuration example 111 To program 111 Releasing Applications 94115 Abort Switch 94 ACS Annunciation 115 Auxiliary Control Functions 115 Cross Zones 94 Types 102 Delay Time 94 Initiating Devices 114 Soak Time 94 Switches & Circuits, programming & configuration 104114 Warning sounders 115 Releasing Zone Address Format 43 Releasing Zones (R0-R9) 130 Type codes for inputs/outputs 103 Reminder Menu Screen 25 Remote Display Menu 38 Reset 154 AKS-1 36 Local control 21
S
screen navigation 20 Scrolling 11 Second Shot Switch Monitor module configuration example 107 To program 107 selecting a field 20 Self Test 85 Self-Optimizing Pre-Alarm 120 Sensitivity, see Alarm Sensitivity Levels, Detector Service Screens 84 Application Corrupt Screen 88 Download screen 88 LCM Download Menu 87 Power-up screen 85 Version Information 84
R
Rapid All Call 23 Rapid poll 40 Read Status 16 Receiving Station, see this panels installation manual. 21
160
Index
TZ
Signal Silence AKS-1 36 Disabling with Silence Inhibit timer 27 Local control 21 Silence Inhibit Timer 27, 154 Silenceable 56 Silenceable Zone 57 SLC (Signaling Line Circuit) 154 SLC loop programming, see Loop programming Smoke Control devices 29 Smoothing 118 Soak Time 94 Sounder Base Setup 24 Special Zone F0, notes and restrictions 116 Special Zone Outputs 116 Special Zones 131 Standard Drill Mode 117 STS-1 tamper switch 35 Supervision 35 Supplemental Documentation 9 Switch Inhibit 56, 154 Switches, service level, displayless mode 11 System Troubles 144
ULC, auto silence value 27 ULI Abort Switch 97 User password, see Password 13 UZC Zone Coder 29
V
VeriFire Tools Program Utility 154 Use with displayless mode 11 Verify-Prealarm 27 Version Information 84 Volume Control 62
W
Walk Test 56, 7480, 154 Advanced Audible 75 Basic 75 See also Alter Status 74 Type IDs, modules, that do not participate 56 Warning Do not rely on Disable to disable releasing points during 70, 94 If you replace any detector with a different type 137 The IRI abort switch will only work if it is pushed before 98 Warning Sounders, releasing applications 115 Weekly occupancy schedules 37, 47, 49 Wiring Style 40 wiring style, network 19
T
Tamper input 35 Threshold, Channel A & B 19 Time control, special zones 116 Time zone 81 Time-based functions 61 Equations 133 Timers 26 TM-4 26, 29, 117 Trouble bus cable, for auxiliary trouble reporting 35 Trouble Equations 135 Trouble Zone 61, 130 Address format 43 Trouble, Point - see this panels Operations manual Trouble, System 144 Type Codes 51, 154 Explanation 138 For Intelligent Detectors 138 For Monitor Modules 139 For releasing zone inputs/outputs 103 For SLC output modules 141 See also Point Program 44 To select 138
Z
Z000 general alarm 121 Zone map Control module 55 Detector 44, 45 Monitor module 52 Zones CBE 130 Fixed positions in map Detectors, position one 46 Detectors, position ten 46 primary zone 44, 102 Sounder/relay bases, position nine 46 General Zone 56 Non-resettable control 57 Zone label 57 Logic 58 Add logic function 59 Add point 59 Add Time/Date 59 Delete equation 59 Edit Equation 58 Enter time 61
161
U
UDACT 27, 29 UL Standard 864 97, 98, 99, 101 ULC Release Circuit Output module configuration example 109 To program 109
NFS2-3030 Programming Manual P/N 52545:G1 06/16/2011
ZZ
Index