Introduction To Power System Simulator For Engineering
Introduction To Power System Simulator For Engineering
USERS MANUAL
Microsoft Windows 2000, Windows XP, Windows Vista and Visual C++ are registered trademarks of Microsoft
Corporation.
Table of Contents
CONTENTS
Siemens Power Transmission & Distribution, Inc., Power Technologies International iii
PSS™E-31.0
Table of Contents Users Manual
Siemens Power Transmission & Distribution, Inc., Power Technologies International vii
PSS™E-31.0
Table of Contents Users Manual
viii Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0
Users Manual Table of Contents
xii Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0
Users Manual Table of Contents
Siemens Power Transmission & Distribution, Inc., Power Technologies International xiii
PSS™E-31.0
Table of Contents Users Manual
xiv Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0
Users Manual Table of Contents
xvi Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0
Users Manual Table of Contents
Siemens Power Transmission & Distribution, Inc., Power Technologies International xvii
PSS™E-31.0
Table of Contents Users Manual
xviii Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0
Users Manual Table of Contents
Siemens Power Transmission & Distribution, Inc., Power Technologies International xix
PSS™E-31.0
Table of Contents Users Manual
Chapter 18 - Scenarios
18.1 Overview: Scenarios .................................................................................................18-1
18.1.1 General Workflow using Scenarios ..............................................................18-2
18.2 Scenario Menu Bar Entries .......................................................................................18-3
18.2.1 Creating a New Scenario File .......................................................................18-3
18.2.2 Opening an Existing Scenario File ...............................................................18-3
18.2.3 Saving a Scenario File .................................................................................18-3
18.2.4 Closing a Scenario File ................................................................................18-3
18.2.5 Editing a Scenario File .................................................................................18-3
Siemens Power Transmission & Distribution, Inc., Power Technologies International xxi
PSS™E-31.0
Table of Contents Users Manual
xxii Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0
Users Manual List of Figures
LIST OF FIGURES
Siemens Power Transmission & Distribution, Inc., Power Technologies International xxiii
PSS™E-31.0
List of Figures Users Manual
xxiv Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0
Users Manual List of Figures
Siemens Power Transmission & Distribution, Inc., Power Technologies International xxv
PSS™E-31.0
List of Figures Users Manual
xxvi Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0
Users Manual List of Figures
Siemens Power Transmission & Distribution, Inc., Power Technologies International xxvii
PSS™E-31.0
List of Figures Users Manual
xxviii Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0
Users Manual List of Figures
Siemens Power Transmission & Distribution, Inc., Power Technologies International xxix
PSS™E-31.0
List of Figures Users Manual
4-103 Diagram View of Deleted Buses and the Diagram Properties Options . . . . . . . . 4-138
4-104 Selection of Non-transformer branches Data Category for Deletion and Output View .
4-139
4-105 Join Buses Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-140
4-106 Buses 154 and 3008 to be Joined . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-142
4-107 Selecting Buses for Joining . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-142
4-108 Join Buses Dialog and Summary Report on Relocation of Load . . . . . . . . . . . . 4-143
4-109 Original Topology at Bus 203 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-144
4-110 Revised Topology with Joined Buses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-145
4-111 Initiating the Split Bus Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-146
4-112 Reassign Branches and Equipment Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-147
4-113 Bus 3003 to be Split . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-148
4-114 Bus Select, Reassign and Output Report Summary for Bus Split . . . . . . . . . . . . 4-149
4-115 Diagram View of New Topology following Bus Split . . . . . . . . . . . . . . . . . . . . . . 4-150
4-116 Tap Line Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-151
4-117 Line Selected to be Tapped . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-152
4-118 Selection of Branch for the Tap Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-153
4-119 Final Stage in Tap Line and Output View Summary . . . . . . . . . . . . . . . . . . . . . . 4-154
4-120 New Topology on Tapped Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-155
4-121 Move Network Elements Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-155
4-122 Original Topology before Moving Branch 151 - 201 . . . . . . . . . . . . . . . . . . . . . . 4-157
4-123 Selecting From and To Branch Information for Moving the To Bus . . . . . . . . . . 4-158
4-124 Branch Selection Dialog with Available Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-159
4-125 New Topology Following Branch Move and Output Report . . . . . . . . . . . . . . . . 4-160
4-126 GEXM/GOUT Toolbar Button and Bus Selection for Bus 153 MID230 . . . . . . . . 4-161
4-127 Diagram View for Selected Bus 153 MID230 from Savnw.sav case . . . . . . . . . . 4-162
4-128 GOUT/GEXM View Displaying Impedance Data . . . . . . . . . . . . . . . . . . . . . . . . 4-163
4-129 Disconnecting Bus from GOUT/GEXM Diagram View . . . . . . . . . . . . . . . . . . . . 4-165
4-130 Right-Clicking on Load on Bus 154 to Open Item Pop-up Menu . . . . . . . . . . . . 4-166
4-131 Scrolling through the Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-167
4-132 Initiating Bus Renumbering Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-168
4-133 Renumber Buses Dialogs for Bus Name and Bus Number . . . . . . . . . . . . . . . . 4-170
4-134 Dialogs for Selection by Number or Name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-171
4-135 Renumber Buses By Bus Packing Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-172
4-136 Packing Bus Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-172
4-137 Output Bar Indicating Number of Buses Modified . . . . . . . . . . . . . . . . . . . . . . . . 4-173
4-138 Renumbering Buses by Subsystem Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-173
4-139 Renumber Buses by Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-174
4-140 Result of Block Renumbering by Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-174
4-141 Alternative Methods of Renumbering Buses by Selected Subsystems . . . . . . . 4-175
4-142 Menu for Renumbering Auxiliary Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-176
4-143 Renumber Buses in Auxiliary Files Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-177
4-144 Available Auxiliary Files used by PSS™E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-177
4-145 Renumbering Area/Owner/Zone Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-179
4-146 Area and Inter-Area Interchange Information . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-180
xxx Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0
Users Manual List of Figures
Siemens Power Transmission & Distribution, Inc., Power Technologies International xxxi
PSS™E-31.0
List of Figures Users Manual
xxxii Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0
Users Manual List of Figures
Siemens Power Transmission & Distribution, Inc., Power Technologies International xxxiii
PSS™E-31.0
List of Figures Users Manual
7-43 Initial Condition Load Flow Solution for Two-Phase Sample System . . . . . . . . . . 7-66
7-44 Output from Short-Circuit Solution Reporting Corresponding to Figure 7-42 . . . . 7-67
7-45 Simple L-G Fault at Bus 300 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-69
7-46 Simple Ground Connection at Bus 330 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-70
7-47 Secondary System Grounded at Buses 330 and 550 . . . . . . . . . . . . . . . . . . . . . . 7-71
7-48 Current Flows (per unit) from Figure 7-47 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-72
7-49 Home Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-73
7-50 Faults at Home Bus for Each Outgoing Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-74
7-51 Home Bus and Open Line End Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-75
7-52 Clarification of Home Bus and "n" Levels Away . . . . . . . . . . . . . . . . . . . . . . . . . . 7-76
7-53 Output and Reporting Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-77
7-54 Automatic Sequence Fault Calculation Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-78
7-55 Location of Bus 151 and Buses one Level Away in savnw.sav . . . . . . . . . . . . . . 7-82
7-56 Report Output at the Home Bus ( 0 level) for a 3-Phase Fault . . . . . . . . . . . . . . . 7-84
7-57 Current Flows 1 Level Away from Home Bus 151 for Three-Phase Fault . . . . . . 7-85
7-58 Fault Summary Report with 3-Phase Fault on Bus 151 . . . . . . . . . . . . . . . . . . . . 7-86
7-59 Results for Three-Phase and Single Phase fault at bus 151 . . . . . . . . . . . . . . . . 7-87
7-60 Transient Phase Currents in Suddenly Applied Short Circuit . . . . . . . . . . . . . . . . 7-89
7-61 Forms of Expression of Fault Current at Instant of Circuit Breaker Opening . . . . 7-90
7-62 Relationships Between Machine Time Constants in Radial System . . . . . . . . . . . 7-94
7-63 Launching the Circuit Breaker Interrupting Duty Calculation . . . . . . . . . . . . . . . . 7-96
7-64 Relationship of Outputs to Offset Fault Current Wave (amps) . . . . . . . . . . . . . . 7-100
7-65 ANSI Fault Current Calculation Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-102
7-66 Selection of Buses to be Faulted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-103
7-67 Summary and Detailed Report of ANSI Fault Calculation . . . . . . . . . . . . . . . . . . 7-106
7-68 Examples of Unbalanced Network Conditions Requiring a PI Equivalent . . . . . 7-107
7-69 Separate Pole Circuit Breaker Calculation Dialog . . . . . . . . . . . . . . . . . . . . . . . . 7-108
7-70 Output Report for Equivalent PI shown in Figure 7-71 . . . . . . . . . . . . . . . . . . . . 7-110
7-71 Diagram View of Equivalent Pi and the Branch Power Flow Data . . . . . . . . . . . 7-111
8-1 Time Regimes Considered in Power System Simulations . . . . . . . . . . . . . . . . . . . 8-2
8-2 Standard Load-Flow Model and Norton Equivalent Used for Switching and
Dynamic Studies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
8-3 Performing the Generator Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6
8-4 Change of Generator Boundary Condition for Switching . . . . . . . . . . . . . . . . . . . . 8-7
8-5 Ordering the Network Buses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-8
8-6 Switching Analysis – Sequence of Processes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-9
8-7 Launching the Factorization Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-10
8-8 Launching the Triangularized Y Matrix Solution . . . . . . . . . . . . . . . . . . . . . . . . . . 8-11
8-9 Example – Circuits from Bus 151 to Bus 152 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-13
8-10 Opening a Line at One End . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-13
8-11 Using the Split Bus Tool to Produce an Open Line End . . . . . . . . . . . . . . . . . . . . 8-14
8-12 Motor Starting Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-16
8-13 Bus Based Report Following Motor Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-16
8-14 Calculation of Branch Currents Flowing into a Bus Faulted through
Zero-Impedance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-17
xxxiv Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0
Users Manual List of Figures
8-15 Bus Based Output for Three-phase Balanced Fault on Bus 3006 . . . . . . . . . . . . .8-18
9-1 Separation of Complete Network into Study System and External Systems
by Boundaries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-3
9-2 Dialog for Equivalencing and Related Processes . . . . . . . . . . . . . . . . . . . . . . . . . .9-5
9-3 Selection for Netting Generation with Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-6
9-4 Generation and Load in Powerflow Case savnw.sav . . . . . . . . . . . . . . . . . . . . . . . .9-7
9-5 Result of Netting Generation in the LIGHTCO Area . . . . . . . . . . . . . . . . . . . . . . . .9-7
9-6 Dialog for Radial and 2-Point Bus Equivalencing . . . . . . . . . . . . . . . . . . . . . . . . . . .9-9
9-7 Result of Radial Equivalencing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-10
9-8 Dialog for Building Electrical Equivalent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-12
9-9 Components of the WORLD Area in the savnw.sav Powerflow Case . . . . . . . . . .9-15
9-10 Pre-Equivalence Powerflow Diagram for the WORLD Area . . . . . . . . . . . . . . . . .9-16
9-11 Reduced Components of the WORLD Area after Equivalencing . . . . . . . . . . . . . .9-17
9-12 Redrawn One-Line Diagram to Match Topology after Equivalencing . . . . . . . . . .9-18
9-13 Net Boundary Bus Mismatches Dialog and Modification Options . . . . . . . . . . . . .9-20
9-14 Pictorial Image of Powerflow Case with Equivalenced Sequence Networks . . . . .9-21
9-15 Form of Sequence Equivalents Built the Short-Circuit Equivalencing Process . . .9-24
9-16 Dialog for Short-Circuit Equivalent Construction . . . . . . . . . . . . . . . . . . . . . . . . . .9-25
9-17 Pre-Equivalence Power Flow One-Line Diagram Showing the FLAPCO
Area Buses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-28
9-18 Equivalent FLAPCO Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-29
10-1 Opening the Transaction Data Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-3
10-2 Transaction Data Input Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-3
10-3 Menu Selection for Transmission Access Calculations . . . . . . . . . . . . . . . . . . . . .10-6
10-4 Input Dialog for Transaction Impacts Calculation . . . . . . . . . . . . . . . . . . . . . . . . . .10-7
10-5 Results of Impact Calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-8
10-6 Line Loading Relief Calculation Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-10
10-7 Selecting Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-12
10-8 Selecting the Branch Mileage Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-13
11-1 PV Analysis Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-2
11-2 PV Analysis Results Window: Calculations Results . . . . . . . . . . . . . . . . . . . . . . . .11-5
11-3 PV Analysis Results Window: Graph Results . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-6
11-4 Scale Values Dialog for Vertical Axis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-7
11-5 Scale Values Dialog for Horizontal Axis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-8
11-6 Scale Values Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-9
11-7 QV Analysis Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-10
11-8 QV Analysis Results Window: Calculation Results . . . . . . . . . . . . . . . . . . . . . . .11-12
11-9 QV Analysis Results Window: Graph Results . . . . . . . . . . . . . . . . . . . . . . . . . . .11-14
11-10 Scale Values Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-15
11-11 Graph Area Visual Parameters Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-16
11-12 Two Terminals Simple Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-17
11-13 PV Curves Voltage and Incremental Power Transfer Characteristics . . . . . . . . .11-18
11-14 PV Curves Voltage and Incremental Power Transfer Characteristics for
Bus 203 under Different Network Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-20
Siemens Power Transmission & Distribution, Inc., Power Technologies International xxxv
PSS™E-31.0
List of Figures Users Manual
xxxvi Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0
Users Manual List of Figures
Siemens Power Transmission & Distribution, Inc., Power Technologies International xxxvii
PSS™E-31.0
List of Figures Users Manual
xxxviii Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0
Users Manual List of Tables
LIST OF TABLES
Siemens Power Transmission & Distribution, Inc., Power Technologies International xxxix
PSS™E-31.0
List of Tables Users Manual
In addition to steady-state and dynamic analysis, the PSS™E package also provides the user with
a wide range of auxiliary programs for installation, data input, output, manipulation and preparation.
This manual comprehensively covers the operation and application of only the new PSS™E Inter-
face. For comprehensive reference manuals, refer to the PSS™E Program Operation Manual
(POM), Volumes I and II.
Throughout the rest of this manual the user will become familiar with following:
Siemens Power Transmission & Distribution, Inc., Power Technologies International 1-1
PSS™E Overview PSS™E-31.0
Introduction to the Users Manual Users Manual
To help in the transition from the older user interface to the new one, a map between the activity
names and the corresponding menu items is provided in Appendix A, Functional Summaries of
PSS™E Activities. Most of the traditional activity names are also included in the menu functions of
the new interface.
1-2 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 PSS™E Overview
Users Manual Introduction to the Users Manual
The PSS™E OPF Manual comprehensively describes the operational and engineering aspects of
formulating optimal power flow problems, solving them and interpreting the results. It pertains to the
optional OPF module made available from a menu within PSS™E.
Computer platform specific user procedures, as well as PSS™E installation instructions and docu-
mentation on several PSS™E utility programs, are contained in a set of computer dependent
installation manuals (i.e., PSS™E for Windows).
The Guide to Printing and Plotting manual describes the graphics and tabular output devices sup-
ported by the traditional PSS™E interface (i.e., PSS™E dynamics, PSSPLT, etc.). It includes both
program user information as well as system-related instructions required by those responsible for
PSS™E installation.
The PSSPLT Program Manual describes the use of the simulation channel output file processing
program used for plotting dynamics study results.
The IPLAN Program Manual describes the Siemens PTI IPLAN programming language and use of
the IPLAN compiler.
The PSS™E WECC Data Conversion Manual describes the auxiliary programs WECCLF,
WECCDS, and RAWECC. These auxiliary programs convert data between the Western Electricity
Coordinating Council (WECC) power flow and stability program data formats and PSS™E input
data file formats.
The Saved Case Data Extraction Subroutines manual describes the programming interface func-
tions whereby users may develop programs that access power flow data directly from PSS™E
Saved Case Files.
The PSAS User’s Ready Reference and PSEB User’s Ready Reference describe the Command
File structures that allow the PSS™E user to specify many routine power flow and dynamic simu-
lation runs, respectively, in English sentence form. These command files are created by the user
with a text editor before starting up PSS™E. The PSAS and PSEB commands are translated into
a PSS™E Response File for immediate execution or for subsequent processing as a standard
PSS™E Response File.
The PSS™E Application Program Interface (API) manual describes the Psspy Python procedures
and PSS™E Batch Commands ("BAT_") used in the PSS™E automation facility.
The Transmission Line Characteristics (TMLC) Program Manual and the PSS™E LineProp Manual
document the two auxiliary programs available to calculate line impedances from a transmission
corridor definition.
• The PSS™E Grid Editor Users Guide has been replaced by this PSS™E Users
Manual.
• The Programming Manual for Device Independent Plotting (INDEPLOT) is obsolete.
• The Graphic Report Generator GRPG User’s Ready Reference is obsolete.
• The B-Matrix Program Manual is obsolete.
What was titled Guide to PSS™E Batch Commands has been renamed the PSS™E Applica-
tion Program Interface (API) manual.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 1-3
PSS™E Overview PSS™E-31.0
Introduction to the Users Manual Users Manual
Bold italic text denotes a menu option that the user must select, or a button the user must
click. For example:
Choose File>Open from the main menu, or click the Open button on the File toolbar
Italic text is used to emphasize a word or phrase.
Indicates additional information of interest.
The PSS™E manuals and reference guides are located on the installation CD in the "DOCS" folder.
If the option to install documentation with PSS™E is selected during the PSS™E installation, a
shortcut to the PSS™E documentation will be placed on the PSS™E Start menu.
1-4 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 PSS™E Overview
Users Manual Overview: PSS™E Functionality
• High priority is given to issues that cause the program to crash or produce incorrect
results with no published work around.
• Medium priority is given to issues that cause incorrect functionality, however the
problem can be remedied by a published work around.
• Low priority is given to those issues that do not fall into the above categories, or are
purely cosmetic in nature.
Every effort is made to address high and medium issues in a PSS™E point release. Some low pri-
ority items may also be include in a point release although this cannot be guaranteed.
Feature requests are evaluated on the basis of whether it benefits a wide majority of PSS™E users.
If it does, it will likely be considered for implementation in a point release or major release of
PSS™E. If several users have the same feature request, the feature may sit higher in the queue
than others for implementation in PSS™E.
Through the PSS™E interface the following functions and analyses are available:
Siemens Power Transmission & Distribution, Inc., Power Technologies International 1-5
PSS™E Overview PSS™E-31.0
Overview: The PSS™E User Interface Users Manual
1-6 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 PSS™E Overview
Users Manual Overview: The PSS™E User Interface
At program startup the Spreadsheet View is not shown. It will appear when a raw data or saved
case file is opened. The Spreadsheet View is the default view for the interface and remains open
once it is populated. It can be minimized, but if closed will remove the current network from PSS™E.
In Figure 1-2, the Bus tab has been selected and the spreadsheet reflects the bus data records
within the working case. Other data items may be viewed by clicking on the other tabs located at
the bottom of the spreadsheet view.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 1-7
PSS™E Overview PSS™E-31.0
Overview: The PSS™E User Interface Users Manual
The Diagram View is not automatically opened. It is initiated by opening an existing one-line
drawing file, or by starting a new diagram window.
The Diagram View can directly import old PSS™E DRAW files, which can then be saved to the new
diagram Slider (SLD) format.
Note: One-line diagrams from the new interface are not backward compatible with the
DRAW/DRED activities of previous versions of PSS™E.
1-8 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 PSS™E Overview
Users Manual Overview: The PSS™E User Interface
Siemens Power Transmission & Distribution, Inc., Power Technologies International 1-9
PSS™E Overview PSS™E-31.0
Overview: The PSS™E User Interface Users Manual
The Output Bar is also used to display program output in the form of text reports. Reports can
optionally be sent to a single report view or to individual reports, and are activated by clicking on
the Report tab.
Standard Windows® capabilities for selecting and copying text to the clip board or saving it to an
external file are supported in both views. This allows for easy transition between PSS™E and
external applications such as Excel or Word.
1-10 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 PSS™E Overview
Users Manual Using the PSS™E User Interface
For additional convenience, Appendix A of this manual provides a map from the old activity names
to their new locations on the pull-down menus in the new user interface. The analytical functions
are listed in accordance with their common applications in planning and operations studies.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 1-11
PSS™E Overview PSS™E-31.0
Co-existence of Multiple PSS™E Versions Users Manual
Existing Python scripts (.py), Response files (.idv), IPLAN programs and PSAS/PSEB command
files may be executed from within the user interface by selecting I/O Control>Run program Auto-
mation file. PSS™E will open a file selector window and prompt for the appropriate filename to
execute.
1-12 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 PSS™E Overview
Users Manual Starting the PSS™E Application
• -inifile filename
Override the default "ini" file with the one specified by filename.
• -pyfile filename
• -rspfile filename
• -argstring string
When -rspfile filename or -pyfile filename is also specified, use string as the argu-
ment for filename; otherwise the -argstring option is ignored.
• -buses buses
Set the program bus size level. Buses will be rounded to the next multiple of 1000,
up to a maximum of 150000. If zero is specified, the current default size level is
used.
• -embed
When -rspfile or -pyfile is also specified, do not display the user interface until that
file has completed its execution; otherwise the -embed option is ignored.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 1-13
PSS™E Overview PSS™E-31.0
Starting the PSS™E Application Users Manual
The above keywords may be abbreviated to any unique string. The options may be specified in any
order. If the same option is specified more than once, the last one specified is used. The -pyfile and
-rspfile options are mutually exclusive; if both are used, the -rspfile option is ignored.
"String" and "filename" should be quoted if they contain embedded blanks - use the quote character
("). When the "string" value from -argstring is passed to the Python program or Response Rile, the
surrounding quotes will be removed. Also any embedded pairs of quotes will be interpreted as a
single quote character. For example, "abc""def" will appear to be the single 7-character string
abc"def. When used with -rspfile, that resulting string will then be parsed according to the normal
free-format parsing rules to assign the individual response file arguments. When used with -pyfile,
that resulting string will be the value of sys.argv[1].
The above keywords may be appended to the PSS™E startup command by appending the argu-
ment to the psse31.exe path name specified in the Target field of the Properties window associated
with the PSSE shortcut icon or Start>Programs>PSSE 31>PSSE menu item (see Figure 1-8).
1-14 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 PSS™E Overview
Users Manual Starting the PSS™E Application
Figure 1-8. Specifying the -buses Command Line Option in the Properties
Window
The keywords may also be appended to the psse command prompt by initiating the Start>Pro-
grams>PSSE 31>PSSE-31 Command Prompt window and appending the command keyword to
the psse30.exe command (see Figure 1-9).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 1-15
PSS™E Overview PSS™E-31.0
Starting the PSS™E Application Users Manual
Figure 1-9. Specifying the "-buses" Option in the PSSE-31 Command Prompt
Window
At PSS™E startup, the size assumed will be the default bus size level established during program
installation. An alternate size level may be specified by either
• selecting Misc>Change program settings (OPTN)… from within PSS™E, and spec-
ifying the desired size level in the Startup bus dimension field. The new bus size level
will take effect the next time PSS™E is started; or
• specifying the "-buses buses" command line option as described in Section 1.6.1.
If the specified bus size falls in between standard size levels, the dimensional capacities of some
elements are interpolated between the two adjacent standard size dimensions and other elements
take on the dimension of the nearest smaller standard size level. If the specified bus size level is
greater than 50000 buses, the dimensional capacities of those elements not determined by extrap-
olation take on the dimensions of the 150000 bus size level. The "I/E or S" column of Table 1-1
contains "I/E" if interpolation or extrapolation is used or an "S" if the dimension of the nearest
smaller standard size level is taken. For example, if PSS™E is started up at 10000 buses, the max-
imum number of loads, transformers, and switched shunts are determined by interpolating between
the corresponding capacities at the 4000 and 12000 bus size levels, and the maximum number of
areas, dc lines, and zero sequence mutuals are the same as at the 4000 bus size level.
1-16 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 PSS™E Overview
Users Manual Starting the PSS™E Application
Siemens Power Transmission & Distribution, Inc., Power Technologies International 1-17
PSS™E Overview PSS™E-31.0
Starting the PSS™E Application Users Manual
It is perfectly reasonable to set up one directory for running the PSS™E programs (a working direc-
tory) and another for the storage of base case power flow and dynamics data files. Various other
working directories may also be established in which to run PSS™E on a variety of different studies
or investigations, each with its own set of data files.
A simple way of setting up PSS™E to run in a variety of working directories is to create a shortcut
icon for each one and alter the Properties of the shortcut to indicate the directory in which the pro-
gram is to start in. In Figure 1-10 the directory path specified in the Start in: field may be set to an
alternate location.
1-18 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 PSS™E Overview
Users Manual Starting the PSS™E Application
PSS™E requires that certain files reside in any working directory in which PSS™E is to be exe-
cuted. Among these are the files on which PSS™E operates. Files containing input and output data
for PSS™E, saved power flow binary files, and other files generated by PSS™E, may reside in the
working directory or some other directory.
A set of arrays in PSS™E’s address space contains a complete set of power flow data. The content
of these arrays is referred to throughout this manual as the working case. The working case is mod-
ified by the load flow activities and is always a valid working case even though its voltages may not
represent a solution of Kirchhoff’s laws.
The working files are an integral part of the PSS™E package. The user never needs to reference
these files by name but must be aware that processing may be performed on these files every time
PSS™E is used. The names and general functions of the working files are:
FMWORK Used by all activities involving the factorized system admittance matrix.
DSWORK Used by dynamic simulation activities.
SCWORK Used by power flow solution and unbalanced fault analysis activities.
The working files are used as scratch files by many PSS™E activities. Their contents are variable
depending upon the recent sequencing and context of activity executions. The user of PSS™E
does not need to be concerned with the specific contents of these files as long as the prerequisites
listed for each activity are observed.
Before PSS™E can operate upon a power system model, the working files must be established in
the user’s directory. Upon initiation, PSS™E checks for the existence of the working files in the
user’s directory. If they are not present, PSS™E automatically creates them with a small amount of
header information.
Once created, the user need not be concerned with the working files except to note that:
1. The working file filenames FMWORK, SCWORK, and DSWORK (with the appropriate
host dependent suffix) must not be used for any other purpose.
3. Only one user may be executing PSS™E with a given set of working files at a time.
Multiple simultaneous executions of PSS™E are permitted as long as each user uti-
lizes a different set of working files.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 1-19
PSS™E Overview PSS™E-31.0
Starting the PSS™E Application Users Manual
Figure 1-11. Program Settings Dialog
1-20 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 PSS™E Overview
Users Manual Starting the PSS™E Application
Bus Input: Buses are selected in the interactive dialog portions of PSS™E by either bus
number ("Number" option) or extended bus name ("Extended Name" option). Extended bus
names consist of the twelve-character alphanumeric name plus the bus base voltage.
Bus Output: Buses are ordered in PSS™E reports in either ascending bus number order
("Number" option) or alphabetical extended bus name order ("Extended Name" option).
Power Output: Power output may be output in units of either MVA or kVA.
Voltage Output: Voltages are tabulated in either per unit (pu) or kV.
Voltage Input: Voltages are reported and input in either per unit (pu) or kV.
Transmission Line Units: Transmission line (not transformer or generator) impedances
input and/or output in either per unit (pu) or ohms; line capacitances are in either per unit
or microfarads.
Short Circuit Units: Fault analysis results are tabulated in either physical units or per unit
(pu).
Short Circuit Coordinates: Fault analysis results are tabulated in either rectangular (e.g.,
MW, Mvar) or polar coordinates (e.g., MVA, pf).
Short Circuit Phase Modelling: Fault analysis calculations handle either three-phase sys-
tems (3-Phase) modeled by their positive, negative, and zero sequence networks, or two-
phase systems (2-Phase) used in some electric traction systems modeled by their positive
and zero sequence networks.
Default Rating Set: Default branch rating used in power flow output and contingency anal-
yses. Selections can be Rate A, Rate B, or Rate C.
Tap Adjustment: Sets the mode of tap adjustment in the solution process to be either Off,
Step, or Direct.
• The Off mode suppresses transformer adjustments during the power flow solution.
• In the Step mode of tap adjustment each transformer is checked independently
outside of the main power flow iteration. If the controlled voltage is outside of its
specified band the tap ratio is moved at least one user-specified step.
• The Direct mode is a Newton-based method of tap adjustment. If any tap ratios
need to be adjusted, a simultaneous adjustment is made of all voltage controlling
transformers as well as all Mvar controlling transformers and all bus voltage mag-
nitudes. Upon convergence of the main power flow iteration, tap ratios of control-
ling transformers are moved to their nearest step and the solution refined with tap
ratios locked at those positions.
Area Interchange: Sets the mode of area interchange control.
• Disabled indicates to disable area interchange control.
• If Tie lines only is selected, an area’s net interchange is defined as the sum of the
flows on all of its tie lines; a tie line is a branch (ac line, dc line, or series FACTS
device) connected to a bus residing in the area whose other end is connected to a
bus that is not in the area. Tie flows are calculated at the metered end as power
flowing out of the area.
• If Tie lines and loads is selected, a load whose area assignment differs from that
of the bus to which it is connected is considered a tie branch for net interchange
calculation purposes; that is, an area’s net interchange includes tie line flows as
Siemens Power Transmission & Distribution, Inc., Power Technologies International 1-21
PSS™E Overview PSS™E-31.0
Starting the PSS™E Application Users Manual
well as contributions from loads connected to area buses that are assigned to
areas other than the bus’ area, and from loads assigned to the area which are con-
nected to buses assigned to other areas.
File Overwrite Option: If asked to save to a file that already exists, PSS™E may either
automatically overwrite the file or ask the user before doing so.
Transformer percent units: Transformer percent loadings may be either percent MVA
loadings or percent current loadings in the reports of a variety of output and analysis func-
tions and the various AC contingency calculation reporting functions.
Non transformer percent units: Percent loadings on non-transformer branches may be
either percent MVA loadings or percent current loadings in the reports of a variety of output
and analysis functions and the various AC contingency calculation reporting functions.
Startup Bus Dimensions: Shows the current size level of PSS™E in terms of the maxi-
mum number of buses allowed. A new bus size level may be specified and will take effect
when the program is restarted, assuming the Save options to file box is checked. This set-
ting may be overridden by the user at the time PSS™E is initiated by specifying the "-buses"
command line token followed by the desired bus dimension as described in Section 1.6.1.
Newton Solution Tolerance: The Newton Solution convergence tolerance (MW/Mvar) is
set to this value when a Newton-Raphson solution is selected in PSS™E. This is the toler-
ance used to determine when the power flow has established convergence.
Base Frequency: The base or system frequency in Hertz (commonly 50 or 60 Hz).
Matrix Growth Factor: The matrix growth factor used in allocating working arrays by activ-
ities involving the ordering, factorization, or triangularization of network matrices. PSS™E
updates this value as required, so that users do not normally need to be concerned with it.
Check Network Before Solving: The power flow solution activities may be instructed to
perform a network connectivity check before beginning their voltage solution iterations.
This ensures that all type one and two buses are connected back to a swing (type three)
bus by in-service ac branches.
Report Multisection Lines: Multisection line groupings are either recognized or ignored in
a variety of output and analysis functions, in the area interchange control option of the
power flow solution activities and in the interchange subroutines accessible from IPLAN
programs.
Report line shunts: Line shunt powers may optionally be reported in power flow output
activities.
Enable fault analysis warnings: Certain warning messages can be either printed or sup-
pressed in the fault analysis input and solution activities (i.e., missing generator data and
sequence network isolated buses).
Setup fault network before solving with unbalances: Allows or suppresses automatic
set-up of the factored matrix working file prior to running unbalanced fault analysis.
Adjust phase shift: Turns phase shift adjustment ON or OFF during the solution process.
Adjust DC taps: Locks or unlocks dc transformer taps during the solution process.
Switched shunt adjustments: Allows or suppresses the adjustment of switched shunts
during the solution process.
1-22 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 PSS™E Overview
Users Manual Overview: Files Used by PSS™E
Non-divergent Newton solution: Allows the voltage vector of diverging power flow itera-
tions to be captured and the power flow solution to be terminated prior to blowing up when
performing the fixed slope decoupled Newton-Raphson solution (FDNS), fully coupled
Newton-Raphson solution (FNSL) or AC contingency analysis (see Section 4.3.9.6).
Print outaged branches: In the bus output blocks of output activities, out-of-service
branches connected to the bus may optionally be listed.
Print "to" buses of 3 winding transformers: When reporting flows into three-winding
transformer windings, the other two buses connected to the transformer may optionally be
listed.
Save options to file: Checking this box saves the options settings to a binary file psse.opt.
The file is saved in the current working directory, the location where the program was last
invoked. This file must remain in the working directory, otherwise, the options will not be
preserved. There is no default psse.opt file provided with the program installation. This file
is created only when this option is checked.
If this option is not selected (checked), startup bus dimensions and other options will
not be preserved.
The user can instruct PSS™E to read from or write into virtually any existing file at any time and
can have PSS™E create a new file at any time that it is needed. The prerequisite for full use of this
capability is a sound understanding of the distinct classes of files used by PSS™E.
A file class is a distinction imposed by PSS™E, not by the computer’s file management system.
1. Files created by the user – These are data files required for analysis, or batch and pro-
gram control files used for directing the running of the program.
2. Files created by PSS™E – These are files generated when the user’s working case is
saved, or output and results files are requested by the user.
Table 1-2 summarizes all classes of files used and created by the PSS™E Power Flow. With the
exception of the Working Files and the PSS™E and OPF Options files, the user may assign any
name to any file. The maximum filename or pathname length that PSS™E can handle is platform
dependent, with the most restrictive platform able to handle 200-character filenames and path-
names. A file is always identified by this user-assigned name, both within the computer’s file
management system and within PSS™E activities. The following subsections discuss these file
classes in some detail.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 1-23
PSS™E Overview PSS™E-31.0
Overview: Files Used by PSS™E Users Manual
Input data files may be obtained by reading from storage mediums (i.e. CD’s) or e-mail attachments
from external sources (other computer installations), or by the typing and file editing facilities of the
host computer. In the case of power flow and dynamics data input, the input data files may often be
created by reading and reformatting data obtained from other computer installations. While they are
not a part of the PSS™E activity structure, reformatting programs are available for translating sev-
eral widely used power flow and dynamics data formats into the PSS™E input format.
The principal PSS™E input data files are defined below. Their use in performing analysis is dis-
cussed in other chapters, as appropriate.
1-24 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 PSS™E Overview
Users Manual Overview: Files Used by PSS™E
Siemens Power Transmission & Distribution, Inc., Power Technologies International 1-25
PSS™E Overview PSS™E-31.0
Overview: Files Used by PSS™E Users Manual
Reading basic power flow data from input data files should be a relatively infrequent occurrence in
PSS™E. Once an initial working case has been built up, the input data files should be set aside and
all data changes and small additions should be made directly on the working case, specifically using
the Spreadsheet View data editing capability. Attempts to keep a large input data file up to date with
an ongoing power system study are usually both error prone and time consuming. PSS™E Saved
Cases, as described in Section 1.7.2, are far more efficient vehicles for maintaining the power flow
system database of a study. The PSS™E Power Flow has capabilities that allow power flow data,
machine data, sequence data and optimal power flow data to be translated back into input data file
form on those occasions when it is needed. These output processes are described in the appro-
priate sections.
The user may create as many saved cases as desired. Each saved case is a complete power flow
data set including analysis results that may be imported into PSS™E as a new base case at any
time. Similarly, PSS™E Dynamics utilizes a binary snapshot file to store dynamics working memory
(see the PSS™E Program Operation Manual (POM) Vol I and II for descriptions of dynamic activi-
ties and processes).
1-26 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 PSS™E Overview
Users Manual Overview: Files Used by PSS™E
Once written, the output listing file is available to all standard file manipulation functions; it may be
printed, transferred to a backup medium, examined with a text editor, or simply discarded.
Alternatively, the user can have the program record a sequence of operations or calculations which
the user performs manually. That sequence of events is then stored in a file for subsequent use in
automatically repeating the entire process. PSS™E can record the sequence of operations as
"BAT_" commands. Activity names referenced in Response Files are currently supported, but only
if they are entered through a text editor.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 1-27
PSS™E Overview PSS™E-31.0
Data In Non-PSS™E Formats Users Manual
CMDYRE From a PSS™E Dynamics Data File and a Machine Impedance Data File, builds
a file containing card image records in the IEEE format for the exchange of sta-
bility data.
CNV27 From a Power Flow Raw Data File in the format required for PSS™E-24 through
PSS™E-26, builds a Power Flow Raw Data File in the form required by PSS™E-
27 or PSS™E-28, and then provides for the conversion to PSS™E-27 or later of
any corresponding Sequence Data File which is in the form required for
PSS™E-22 through PSS™E-26.
CNV29 From a Power Flow Raw Data File in the format required for PSS™E-27 or
PSS™E-28, builds a Power Flow Raw Data File in the form required by PSS™E-
29.
CNV30 From a Power Flow Raw Data File in the format required for PSS™E-29, builds
a Power Flow Raw Data File in the form required by PSS™E-30.
CNVDRW From a Drawing Coordinate Data File in the format required for PSS™E-15
through PSS™E-23, builds a Drawing Coordinate Data File in the form required
by PSS™E-24 or later.
CNVRAW From a Power Flow Raw Data File in the format required for PSS™E-15 through
PSS™E-23, builds a Power Flow Raw Data File in the form required by PSS™E-
24 through PSS™E-26.
1-28 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 PSS™E Overview
Users Manual Using PSS™E Files
CNVRSQ From a Sequence Data File in the format required for PSS™E-21 or earlier,
builds a Sequence Data File in the form required by PSS™E-22 through
PSS™E-26.
COMDAT From a file containing card image records in the IEEE format for the exchange of
stability date, builds a PSS™E Dynamics Data File and a Machine Impedance
Data File.
COMFOR From a file containing load flow data records in IEEE Common Tape Format,
builds a PSS™E-24 Power Flow Raw Data File.
ConvertRaw Converts Power Flow Raw Data Files from PSS™E-15 format or later to any
more recent Power Flow Raw Data File format, include PSS™E-31.
CreateRaw Creates Power Flow Raw Data Files, back to PSS™E-15 format, given a
PSS™E-31 Saved Case File.
PSAP4 From a file containing card image records in the PJM PSAP Version 4 or 5
power flow program data format, builds a PSS™E-23 Power Flow Raw Data
File.
RAW23 From a PSS™E Saved Case File, builds a PSS™E-23 Power Flow Raw Data
File.
RAW26 From a PSS™E Saved Case File, builds a PSS™E-26 Power Flow Raw Data
File.
RAW28 From a PSS™E Saved Case File, builds a PSS™E-28 Power Flow Raw Data
File.
RAW29 From a PSS™E Saved Case File, builds a PSS™E-29 Power Flow Raw Data
File.
WECCLF From a file containing records in the new Western Electricity Coordinating
Council (WECC) power flow program data format, builds a PSS™E Power Flow
Raw Data File.
RAWECC From a PSS™E Saved Case File, builds a file containing records in the new
WECC power flow program data format.
WECCDS From a file containing records in the WECC stability program data format, builds
a PSS™E Dynamics Data File, a Machine Impedance Data File, and a PSS™E
Response File.
On completion of data collection, the user will have a completed file planning sheet giving the
names of all files to be used in the initial phases of a study. The user will also have written out
(in study notes, in spreadsheets, etc.) the input data that must be placed into the PSS™E input files.
The types of data files used by PSS™E, the activities that use them, and the default extensions or
suffixes used when specifying filenames are summarized in Table 1-3. Except as described below,
Siemens Power Transmission & Distribution, Inc., Power Technologies International 1-29
PSS™E Overview PSS™E-31.0
Deleting PSS™E Files Users Manual
whenever a file type listed in the table is being specified to PSS™E, the extension designated in
the table is automatically appended to the filename if the user specifies a filename without an exten-
sion. For file types not listed in Table 1-3 a platform dependent default extension is used.
PSS™E writes out various types of data in the form of input files for use by other PSS™E activities,
and uses platform dependent default extensions. The data output processes which perform this
function are listed in Table 1-4.
Input files need not be created if the activities that use them are not going to be executed.
If the user does not exercise discipline in this regard, confusion could result even if the user is
careful in noting the significance of each file on a file planning sheet. Furthermore, disk space is
unnecessarily wasted and, although disks have large capacities, they are finite.
Files that are not current, but need to be retained for documentation or archival purposes, should
be kept on some off-line bulk storage medium.
The user is referred to the appropriate computer system documentation for details on the
mechanics of archiving and deleting files.
PSS™E files over which the user has no naming control are generally accessed from the current
directory or from some other system default directory (e.g., the "TEMP" directory on Windows® sys-
tems). This includes files such as the PSS™E working files, temporary files used during graphics-
related activities, and so on. (PSS™E also looks to the user’s "home" directory and to its own
master directories for a PSS™E Options File, for output device parameter files, and for several
other types of files if they are not found in the user’s current directory; see Section 1.6.3).
1-30 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 PSS™E Overview
Users Manual Summary: PSS™E Files
This mode of operation has been found in thousands of man-years of use of PSS™E and its pre-
decessors to be the preferred way of handling files. It simply requires that the user keep effective
records of the files that created. The best form of record is a concise written catalog to which the
user can refer during use of PSS™E, together with a systematic way of assigning filenames. The
catalog may take the form of the PSS™E File Planning Sheet shown at the end of this chapter.
PSS™E is able, at any time, to write over the contents of a file that had previously been created.
PSS™E does not generally append to files; each time that a user specifies a file’s name for saving
and output processes, the writing commences at the start of that file, destroying the previous con-
tents. The Misc>Change program settings (OPTN)… activity does offer a File overwrite option
that can be set to either "Overwrite without asking" or "Ask first"; see Section 1.6.4.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 1-31
PSS™E Overview PSS™E-31.0
Summary: PSS™E Files Users Manual
Table 1-4. PSS™E Output Activities for Creating Data Files for Other PSS™E Applications
File>Save or Show Create a file of power flow data from the working
Select IEEE Format Power Flow Data tab case, in IEEE common format.
File>Save or Show Create a file of power flow data from the working
Select UCTE Data tab case, in UCTE-2 common format
1-32 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 PSS™E Overview
Users Manual Other Auxiliary Programs
The following auxiliary programs are also used outside of the main PSS™E program structure. This
group includes programs to analyze and/or prepare data to be used as input to PSS™E, as well as
programs to process files containing the results of certain PSS™E calculations.
ACCCBrwsGrid This application, provided on the PC platform only, will post-process the AC
Contingency Calculation’s output file and provide spread sheet style reports of
these results.
DBUILD Incorporates information on user-written plant-related models into the data file
used by the dynamics data modification utility.
IMD Induction motor model data verification program.
IPLAN Compiles programs written in the IPLAN programming language in prepara-
tion for their execution in PSS™E as an automation file.
LineProp Transmission line constants calculation program, available on the PC platform
only, with a modern user interface.
LSYSAN Used to perform small disturbance dynamic analysis. This program is supplied
to those whose lease includes the Linear Dynamic Analysis Program section.
PLINC Plots incremental cost curve data as contained in an Economic Dispatch Data
File.
PSSPLT Processes PSS™E dynamic simulation Channel Output Files.
TMLC Calculates the transmission line constant data required by many power
system analysis programs including PSS™E. TMLC is supplied to only those
users licensed for the Transmission Line Characteristics program section.
Users on the PC are also supplied with the LineProp auxiliary program.
VCV Plots generator "V-curves".
Siemens Power Transmission & Distribution, Inc., Power Technologies International 1-33
PSS™E File Planning Sheet
1-34 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Chapter 2
The User Interface
• Tree View: All network items are represented as selectable elements in a hierarchical
list. Items in the list are organized by data type and reside in expandable/collapsible
folders.
• Spreadsheet View: All network data is presented in the Spreadsheet View. Tabs along
the bottom of the Spreadsheet View allow selection and editing of the various data cat-
egories. The Spreadsheet View only appears when a case is opened.
• Output Bar: All progress and report output is directed toward this expandable window.
Tabs along the bottom allow selection of reports and progress output.
• Diagram View: Facilitates the creation and display of one-line diagrams in the new
Slider format. In addition to the display of power flow results, the Diagram View facili-
tates the building of new diagrams and networks bus by bus. Further, for existing power
flow cases, this view enables the "growing" of one-line diagrams by automatically
drawing selected buses and all their equipment and connected buses. The Diagram
View appears only when a diagram is opened or created.
• Toolbars: Allows convenient selection of analytical tools, creation of one-line dia-
grams, generation of reports, selection of subsystems, and view management.
• Main Menu: Provides access to file handling, interface views, analytical functions,
automation tools, I/O formatting, toolbar organization and online help.
• Status Bar: Provides information related to the diagram status and operating mode.
Figure 2-1 shows the main components of the interface. At startup only the Output Bar together
with the Main Menu and toolbars will be shown. The populated Spreadsheet View will appear when
a power flow case file or raw data file is imported.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-1
The User Interface PSS™E-31.0
Components of the User Interface Users Manual
The Tree, Spreadsheet, Output and Diagram Views can be individually re-sized and located
anywhere on the interface between the Status Bar and toolbars.
Although existing PSS™E DRAW files can be imported, diagrams can be saved only in the
Slider format (.sld). The new diagrams are not backward compatible with the PSS™E
DRAW/DRED activities used to display and edit one-line diagrams in earlier versions of PSS™E.
Figure 2-2 shows an example of a one-line diagram display of a power flow solution using the
PSS™E Diagram View.
2-2 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Components of the User Interface
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-3
The User Interface PSS™E-31.0
Managing Views Users Manual
The Spreadsheet View is the default view as cases are opened. It can be minimized and restored
but will remain available until the user exits the program.
An alternative way to hide, or close, the Views is to right-click within the view and select the Hide
option (see Figure 2-4). Use the View menu from the main menu to reopen them.
Output Bar
Right-click Menu
2-4 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Managing Views
The Diagram View and Spreadsheet View can not be undocked but can be controlled using the
standard Windows® controls found in the upper right corner of the window (i.e., Minimize, Maxi-
mize, Move, etc.). This allows the windows to be "layered" and relocated within the PSS™E main
window.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-5
The User Interface PSS™E-31.0
Tree View Users Manual
When a Diagram View is active the data items in the Tree View are updated to reflect whether that
particular item is drawn in the diagram or not. If the item is not drawn, then the symbol to the left of
the item is blank. If the item is drawn, the symbol to the left of the item is filled with the symbol
belonging to the data category (i.e., bus, branch, etc.). Refer to Figure 2-7b where a bus symbol is
drawn.
The symbols in the Tree View are refreshed whenever a Diagram View is made active. A network
item can be drawn in one Diagram View and not another, so the symbols found in the Tree View
give a quick visual cue as to whether the network item is drawn in the active Diagram View. When
the Spreadsheet View is active, all symbols are replaced with blanks.
2-6 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Tree View
(a) There is no active diagram (b) These three buses are drawn in the active
with these buses drawn. diagram where this symbol is used for
buses.
Figure 2-7. Items Drawn in Active Diagram View indicated in the Tree View
As was discussed in Section 2.2.2, a right-click in a blank area of the Tree View (without selecting
a data category) will display the standard pop-up View Menu from which hiding/exposing and
docking/undocking the view can be selected (see Figure 2-4).
Hide: Closes the view. The user must use the View men from the main menu to reopen
them.
Allow Docking: Toggles whether the View is to be docked or a free-floating window.
Right-click on
unexpanded Branches
category
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-7
The User Interface PSS™E-31.0
Tree View Users Manual
The Sort option causes all items in the selected data category to be sorted in ascending alphanu-
meric order.
Right-Click on Expanded
Bus Category Diagram View must be active (on top)
The Assign all items to Layer option displays the Select Layer dialog. If a layer selection is made
from this dialog, all drawn items in the expanded list will have their diagram layers re-assigned and
the Diagram View will be refreshed. This tool can be useful for assigning network items to layers
for existing or imported diagram views.
If elements are assigned to a layer that is not currently visible, assigning them to that layer will
cause them to disappear from the display. Refer to Section 2.5.10 to see the discussion on
managing layers in the Diagram View.
2-8 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Tree View
If the pop-up menu is launched with the Spreadsheet View active, the following menu options are
available:
Switch: Toggles the switch status of the selected network element (i.e., disconnects the
device).
Network Data: Points to the selected network element in the Spreadsheet View on the rel-
evant data tab, and places the focus on the first spreadsheet cell of the selected item.
Delete: Deletes the network element from the model.
If the selected element is a bus, area, zone or owner, the menu offers the user the ability to create
a subsystem based on the selected element.
Create bus subsystem: Create a bus-based subsystem. (i.e., filters the model by a set of
selected buses).
Create area subsystem: Create an area-based subsystem. (i.e., filters the model by a set
of selected areas).
Create zone subsystem: Create a zone-based subsystem. (i.e., filters the model by a set
of selected zones).
Create owner subsystem: Create an owner-based subsystem. (i.e., filters the model by a
set of selected owners).
If the Diagram View is the active view, then the right-click menu for the selected element will offer
some additional options:
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-9
The User Interface PSS™E-31.0
Tree View Users Manual
Assign to Layer: Displays the Select Layer dialog. If a layer selection is made from this
dialog, the network element can be assigned to a Diagram layer and the Diagram View is
refreshed. This tool can be useful for assigning a network item to a layer for existing or
imported diagram views.
Locate: The Locate menu option is available if the selected element is drawn in the dia-
gram. It allows you to easily locate the element on the diagram.
Bind: Bind literally relates the model element to a graphical element on the diagram.
Selecting an "unbound" element on the diagram, then selecting Bind from the right-click
menu forces PSS™E to couple the two together. The Bind option is discussed in more
detail in Section 2.9.8.
If the selected item is a bus and it is not drawn in the active Diagram View, then the Draw menu
option become available:
Draw: Selecting Draw from the pop-up menu draws the bus and all its equipment in the
active Diagram View.
If the selected item is a bus and is drawn in the active Diagram View, then only the Grow option is
available.
Grow: Selecting Grow will draw the bus, all its equipment, all connected buses and their
equipment, and all the lines and transformers between them. Grow differs from Draw in that
Draw only draws the bus and it’s equipment.
Grow N Levels…: Selecting Grow N Levels… will draw the bus, all its equipment, all con-
nected buses and their equipment, and all the lines and transformers between them. Then
this will continue on to draw the next level of connected buses and their equipment until this
procedure has been done N times. This will draw all buses, equipment, and all connections
between buses that are N connections away from the original bus.
2.3.2 Double-Clicking
Double-clicking on a data element (i.e. particular bus) is equivalent to selecting the Network Data
option from the right-click menu. Both actions activate the Spreadsheet View, change to the correct
data tab, and place the focus on the first spreadsheet cell of the selected item (see Figure 2-11).
2-10 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Spreadsheet View
The Zoom Extent, Zoom Window, Zoom Previous, and Pan buttons have no effect on the
Spreadsheet View and are thus greyed out. They are designed to work with the Diagram
View only.
The Zoom Combo Box is used to select a predefined zoom factor to apply to the Spread-
sheet View. Click the arrow to the right of the combo box to drop down a list of predefined
zoom factors from which to choose. A customized zoom factor may be entered directly in
the field if the desired one is not found in the list. The Zoom Combo Box is also updated to
display the current zoom factor which can be changed through the use of the other zoom
tools.
The Zoom In/Zoom Out buttons are used to zoom the center of the Spreadsheet View in
or out.
The Zoom 100% button is used to quickly return the Spreadsheet View to 100% zoom.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-11
The User Interface PSS™E-31.0
Spreadsheet View Users Manual
Selecting Area…, Owner…, or Zone… from the Subsystem menu opens a dialog window from
which available areas, owners or zones can be selected. These tools can be used to select specific
Areas, Owners, or Zones for reports that are specific to one of the three attributes.
Selecting Bus… from the Subsystem menu, or clicking on the Create a bus subsystem button
displays the Bus Subsystem Selector dialog (Figure 2-15). The five tabs shown allow for a bus
subsystem to be built using a combination of Areas, Owners, Zones, Base kV, or individual
Buses.
Clicking on the All Buses button will remove the current subsystem so all buses can be seen in the
tree and spreadsheet view.
Clicking the Toggle bus subsystems is used to toggle between two subsystems. Under normal
operation, only one subsystem is created at a time. However, a second subsystem will be created
when, in the diagram view, information is requested for an element that is not in the current sub-
system. The creation of the second subsystem allows the first subsystem to be preserved.
When a selection has been made within any of the categories, an asterisk (*) appears on the
tab.
2-12 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Spreadsheet View
Once the subsystem selections have been made, click Apply to refresh the Spreadsheet View.
Selecting the OK button closes the Bus Subsystem Selector dialog. The spreadsheet will now dis-
play data corresponding to only the subsystem selected until a new subsystem selection is made.
To return to a complete Spreadsheet View select the All buses check box (see Figure 2-15).
To preserve a specific subsystem for later recollection select the Memorize button following use of
the Apply button. The information will be stored in a specified file of type *.sbs. The file can then be
accessed later by selecting the Recall button. Selecting the Reset button will undo any changes
made during the selection process.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-13
The User Interface PSS™E-31.0
Spreadsheet View Users Manual
Once the buses have been selected and the Create bus subsystem option selected, the spread-
sheet will show only those buses selected (Figure 2-16b).
2-14 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Spreadsheet View
Copy: Context sensitive, standard Windows® Copy. If the column header is selected, the
entire column is copied to the Windows clipboard. If an individual element is selected, then
only that element is copied in the clipboard.
Paste: Pastes the current contents of the clipboard. If the copied area exceeds the number
of rows available, PSS™E will automatically create the extra network elements required
(and generate appropriate bus numbers).
Copy/Paste uses either the standard keystrokes ([Ctrl] +C, [Ctrl]+V) or the Main Menu
(Edit>Copy, Edit>Paste). The copied data can be pasted using either the standard key-
strokes or the Main Menu.
Bus numbers and other identifiers are not copied as this would result in duplicate data items
in the network. Instead, the next available unused identifier is placed in the field.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-15
The User Interface PSS™E-31.0
Spreadsheet View Users Manual
If a column or set of columns is selected, PSS™E offers the Find, Find again and Replace options.
Find: Selecting the Find option displays the Find dialog window. A text string entered in
the "Find what:" field can be searched for within the selected column. The Find window is
the result of right-clicking on the Base kV column in the bus spreadsheet (see Figure 2-19).
The Find Next button may be used to continue searching up or down the column, based
on the Direction toggle selection.
Find again: Use Find again to search within the selected column for the value entered dur-
ing the previous Find operation. It will find only the first match and cannot be used to iterate
through other matching items within the column. To iterate through matching items in the
column, click Find Next in the Find dialog to find successive items.
Replace: The Replace option displays the Replace window from which a particular text
string can be searched for and replaced by an alternate text string.
Filter: The Filter option displays the Filter Grid window (Figure 2-20) within which a subset
of the spreadsheet data can be displayed based on a Boolean selection criteria applied to
each individual cell in the column. The filtered spreadsheet will have the filtered columns
appear with red headers. Any number of columns may be filtered in the spreadsheet to fur-
ther reduce the amount of data. Selecting a previously filtered column will populate the Fil-
ter Grid dialog with the previous values used to filter the column. A range of values to filter
a cell by may be selected by choosing either the AND or OR radio button. Doing so will
enable the fields at the bottom of the dialog to allow the specification of the additional Bool-
ean check.
2-16 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Spreadsheet View
Any data edits performed within the filtered spreadsheet will automatically be reflected in the
original unfiltered sheet. This allows the use of a reduced data set on which to perform edits.
Figure 2-21 shows the filter set up to reduce the records shown in the bus spreadsheet to only those
records whose bus voltage levels fall below 500 kV and above 22 kV.
Using the Copy and Paste options allow the entire row can be copied and pasted to another appli-
cation or within the spreadsheet. This capability assists in adding equipment or lines to an existing
case. The Copy and Paste options are available for all data category tabs.
The right-click menu for bus data records additionally contains Create bus subsystem and Create
bus display (GOUT/GEXM) options. The Create bus subsystem is discussed in Section 2.4.2.2.
The Create bus display (GOUT/GEXM) option displays a pictorial view of the selected bus and all
its associated data and equipment in a new Diagram View. The graphical bus display for bus 152
selected in Figure 2-23a is shown in Figure 2-23b.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-17
The User Interface PSS™E-31.0
Spreadsheet View Users Manual
If copying data from another application, such as Microsoft® Excel, to the PSS™E spreadsheet,
copy the data from the application to the clipboard, select the insertion point within the desired
PSS™E spreadsheet and select Edit>Paste.
2-18 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Spreadsheet View
For data fields that must contain values from a predefined list of items, double-clicking within the
white area of data field will bring up a window from which a list of valid entries may be chosen. This
is predominately the case for fields requesting an area, owner, or zone number. The new data value
is recorded in the PSS™E case when the cursor is moved to another row.
Data fields that contain check boxes (Figure 2-24a) may be toggled on or off by clicking on the box
to display or remove a checkmark. Data fields that require a selection from a list of valid entries con-
tain a pull-down menu. Clicking on the field produces an arrow in the right side of the field that, when
clicked, displays a drop down list from which one value may be selected (Figure 2-24b).
When one or more cells in a row have been modified, a pencil symbol is placed in column 1 of the
row (Figure 2-25). The data changed is not recorded in the PSS™E case until the cursor is moved
to another row. At that point, all data changes made to the row are recorded and the pencil symbol
is removed.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-19
The User Interface PSS™E-31.0
Spreadsheet View Users Manual
2-20 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Spreadsheet View
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-21
The User Interface PSS™E-31.0
Diagram View Users Manual
The Diagram View is also linked to the Tree View (Section 2.3) where right-click menus facilitate
interaction with the Diagram View (Section 2.3.1.3), including:
• Locating buses
• Adding buses in automatic Draw and Grow
• Binding network items
• Assignment of network items to layers
2-22 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram View
It is also possible to link from the Diagram View directly to the Spreadsheet View where data han-
dling options are available (Section 2.4).
Network components drawn in a Diagram View that do not correspond to existing items in the net-
work will be displayed in an unbound item color. Network components drawn in a Diagram View
that do correspond to existing items in the network will be displayed in bound item colors unless
over-ridden by range checking coloration.
Both the bound and unbound colors can be set by the user in the Diagram Properties sheet dis-
cussed in Section 2.9.1.
Each type of result or information shown in the Diagram view has its own annotation options. The
annotation options can be modified by choosing Diagram>Annotation from the Diagram Menu,
(see Section 2.9). The title of this dialog and the annotation options will change to reflect the current
results setting for the active Diagram View.
The diagram can be expanded, reduced and panned using the Zoom Toolbar buttons. Additionally
the view can be panned horizontally and vertically using the mouse. These manipulations are dis-
cussed in Section 2.5.4.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-23
The User Interface PSS™E-31.0
Diagram View Users Manual
2-24 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram View
With the new Diagram View open, select File>Import>DRAW file… from the Main Menu to import
a DRAW file (Figure 2-29). A list of available *.drw files will be provided from which to select. The
diagram will appear in the previously opened Diagram View.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-25
The User Interface PSS™E-31.0
Diagram View Users Manual
2-26 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram View
CARTESIAN | GEOPHYSICAL
The first record in the file describes the format of all bus position records. CARTESIAN
specifies that bus positions are provided as x/y locations on the diagram. GEOPHYSICAL
specifies that bus positions are provided in GIS form as two pairs of hour, minute, seconds
inputs.
The next N lines specify the bus positions. The Bus Location file does not require an entry for every
bus in the case. If a bus position record is not found in the file when positioning a bus on the dia-
gram, default bus positioning is used.
Degrees are specified as a set of 1 to 3 real numbers (degrees, minutes, seconds) followed by a
direction (E, W, N, S) (the direction can be omitted if all three numbers are specified). Positive
values are interpreted as E or N, negative values as W or S. The degree parts can be separated by
spaces, commas, apostrophes, or by the specific unit markers for degree, minutes, or seconds (in
which case they must be used in order). For example, the following all represent the same value:
79°30’36"W
-79 -30 -36
79.51W
-79.51,,,
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-27
The User Interface PSS™E-31.0
Diagram View Users Manual
The Bus Location file can also contain location entries for branches and two winding transformers
found in the network.
Branch and two winding transformers records are indicated by the BRANCH record appearing in
the file.
BRANCH
FromBusId Either a bus number or a "quoted" extended bus name of the "From" bus.
ToBusId Either a bus number or a "quoted" extended bus name of the "To" bus.
CircuitId Circuit Id of branch.
X From loc The "From" bus X location, in inches, on the diagram.
Y From loc The "From" bus Y location, in inches, on the diagram.
X KP1 loc The first knee point X location, in inches, on the diagram.
Y KP1 loc The first knee point Y location, in inches, on the diagram.
X KPn loc The nth knee point X location, in inches, on the diagram.
Y KPn loc The nth knee point Y location, in inches, on the diagram.
X To loc The "To" bus X location, in inches, on the diagram.
Y To loc The "To" bus Y location, in inches, on the diagram.
FromBusId Either a bus number or a "quoted" extended bus name of the "From" bus.
ToBusId Either a bus number or a "quoted" extended bus name of the "To" bus.
CircuitId Circuit Id of branch.
X From loc The "From" bus X location, in degrees latitude (see format, above).
Y From loc The "From" bus Y location, in degrees latitude (see format, above).
X KP1 loc The first knee point X location, in degrees latitude (see format, above).
Y KP1 loc The first knee point Y location, in degrees latitude (see format, above).
X KPn loc The nth knee point X location, in degrees latitude (see format, above).
Y KPn loc The nth knee point Y location, in degrees latitude (see format, above).
X To loc The "To" bus X location, in degrees latitude (see format, above).
Y To loc The "To" bus Y location, in degrees latitude (see format, above).
If there are no kneepoints associated with the branch, there will be no X & Y KPn entries in the
record.
FromBusId Either a bus number or a "quoted" extended bus name of the "From" bus.
ToBusId Either a bus number or a "quoted" extended bus name of the "To" bus.
2-28 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram View
FromBusId Either a bus number or a "quoted" extended bus name of the "From" bus.
ToBusId Either a bus number or a "quoted" extended bus name of the "To" bus.
CircuitId Circuit Id of two winding transformer.
X From loc The "From" bus X location, in degrees latitude (see format, above).
Y From loc The "From" bus Y location, in degrees latitude (see format, above).
X Sym loc The two winding transformer symbol X location, in degrees latitude (see format,
above).
Y Sym loc The two winding transformer symbol Y location, in degrees latitude (see format,
above).
X KP1 loc The first knee point X location, in degrees latitude (see format, above).
Y KP1 loc The first knee point Y location, in degrees latitude (see format, above).
X KPn loc The nth knee point X location, in degrees latitude (see format, above).
Y KPn loc The nth knee point Y location, in degrees latitude (see format, above).
X To loc The "To" bus X location, in degrees latitude (see format, above).
Y To loc The "To" bus Y location, in degrees latitude (see format, above).
If there are no kneepoints associated with the two winding transformer, there will be no X & Y KPn
entries in the record.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-29
The User Interface PSS™E-31.0
Diagram View Users Manual
The Zoom Combo Box is used to select a pre-defined zoom factor to apply to the Diagram
View. Click the arrow to the right of the combo box to drop down a list of pre-defined zoom
factors from which to choose from.
A custom zoom factor can be entered directly in the box if the one desired is not found in
the list. The value shown in the Zoom Combo Box always reflects the current zoom factor
setting which may change through the use of the other zoom tools.
The Zoom In/Zoom Out buttons are used to zoom the center of the Diagram View in or
out, typically by 10%.
The Zoom Extent button is used to zoom the Diagram View out so as to encompass all the
items within the borders.
The Zoom 100% button is used to quickly return the Diagram View zooming factor to
100%.
The Zoom Window button is used to zoom in on a selected portion of the Diagram View.
Clicking on the button will cause a dashed square to appear along side the mouse pointer.
Click the mouse on one corner of the portion of the diagram and, while holding the mouse
button down, drag the mouse pointer out to create a box around the portion of the diagram
to be zoomed into. The selected part of the Diagram View is then zoomed to fit in the extent
of the Diagram View.
The Zoom Previous button is used to return the zooming factor of the Diagram View to its
previous setting.
The Pan button is used to scroll around the Diagram View in any direction. Upon selecting
this item, the cursor in the Diagram View changes to a hand. The Diagram View is then
panned by holding down the left mouse button and dragging the hand around the window.
For users who have computers equipped with a mouse-wheel, the Diagram View may also be
manipulated with the mouse wheel. Moving the mouse-wheel with the Diagram View active will pan
the Diagram View vertically. Holding down the [Shift] key while moving the mouse-wheel will pan
the Diagram View horizontally. Holding down the [Ctrl] key while moving the mouse-wheel will
zoom the Diagram View.
The keyboard cursor keys may also be used to pan the image.
2-30 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram View
Using the Auto Draw function will place a selected bus on the diagram graphically, and automati-
cally draw adjacent equipment, including adjacent buses. The Auto Draw feature also allows the
specification of the number of bus levels to extend out of the first bus. Auto Draw will draw and con-
nect these buses and neighboring facilities of all of these buses.
The initiation of the creation of a one-line diagram is done using the Auto Draw button found in the
Diagram Toolbar.
The user has two options to quickly draw a diagram. The first approach involves the following steps:
2. Select the Auto Draw button and click on the Diagram View to set the bus
position.
3. A Bus Selector window will appear in which to select or specify the bus to grow and
the number of levels to grow out from this bus. For example, using the savnw.sav
power flow case, bus 101 has been selected and "grown" two levels (see Figure 2-32).
The bus, all it’s equipment, all lines, transformers, and attached buses are then laid out in the
Diagram View. Figure 2-32 shows the result of selecting to grow bus 101. The bus along and its
one neighboring bus is drawn, along with their attached equipment and connecting transformer
branch.
If a Bus Location file has been opened (see Section 2.5.3), and the Use Bus Location file to
"Grow" items option is enabled on the diagram Preferences dialog (see Section 2.7.6), then the
buses will be placed at the locations specified in the Bus Location file. If the bus location data for
the bus does not exist or the option is disabled, then the bus will be placed at the default location.
The process could be continued by selecting locations on the diagram and bus numbers from the
Select Bus dialog. If, in this example, bus 152 were the next one selected and one level was grown
out of this bus, the diagram would grow to include the other attached buses to bus 152, which are
buses 153, 202, and 3004, their connected equipment, and the branches from these buses back to
bus 152.
You can experiment with this method using the savnw.sav power flow case.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-31
The User Interface PSS™E-31.0
Diagram View Users Manual
Figure 2-32. Drawing Bus 101 and Buses Two Levels Out, using the Auto
Draw Toolbar Button
The second approach to start drawing a diagram is to reverse the order of selections, namely:
2. Click on the Auto Draw button from the Diagram Toolbar and click on the Diagram
View to place the bus.
If the first bus selected in the Tree View were bus 101, the result would be bus 101 and 151 plus all
equipment attached to either bus. The process could be continued by selecting other buses from
the Tree View.
If there is a bus or buses already drawn on the one-line diagram it is possible to use the Grow option
from the Tree View (Section 2.3.1.3) to add more one more level of buses. Also, the Grow N
Levels… option can be used to add multiple levels of buses to the diagram. The Grow N Levels…
option is accessed by right-clicking on a bus in the expanded bus list in the Tree View or right-
clicking on a bus in the Diagram View (see Figure 2-33).
2-32 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram View
Right-Click on Bus in
Equipment List View
Right-Click on Bus
in Diagram View
Selecting Grow N Levels… on either of these menus will initiate the drawing of all buses attached
to the bus selected, along with the connected equipment and the branches back to the selected bus
N levels out from the bus. This method assists in rapidly creating a one-line diagram of the open
power flow case.
If a connecting bus or branch already exists on the diagram when a Grow is performed, any new
connections will be made to the existing equipment.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-33
The User Interface PSS™E-31.0
Diagram View Users Manual
To move or resize a bus first to select the bus in the diagram with a mouse click, (see Figure 2-34a).
To move the bus to a different location, select the desired bus and position the mouse over the
center of the bus. The mouse pointer will change to a four arrow cursor. Click on the bus and, while
holding the mouse button down drag (move) the bus to the new position (Figure 2-34b).
To make the bus longer or shorter, select the desired bus and position the mouse over one end of
the bus. The pointer will change to a double sided arrow. Click on the bus end handle and move it
in desired direction (Figure 2-34c).
(a) Select Bus to Move (b) New Position (c) Grab Bus End to Re-size
1. Click on the end of the diagram item you wish to move. The diagram item will be
selected and the bus end(s) connection illuminated with gray or green circles (Figure 2-
35a).
2. Move the desired end by selecting and dragging the end to the new attachment point.
Valid attachment points will be illuminated with gray circles as the mouse passes over
them (Figure 2-35b).
3. When the end illuminates the desired attachment point, release the mouse to attach
the diagram item to the selected attachment point, (Figure 2-35c).
2-34 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram View
The direction in which the capacitor symbol points away from the bus is decided by the edge
on which the grey circle is located. Either the left or right edge of the bus diagram element can
be selected.
Not only can equipment and lines can be moved to another location on their bus but they can
also can be moved to another bus, using the same technique. If Bind Items is selected, (see
Section 2.5.8) moving equipment and lines to another bus in the Diagram View will also move the
equipment and lines in the Tree View. The change will also be reflected in the Spreadsheet View.
Consequently, this is another form of modifying not only the power flow topology but also the loca-
tion of equipment.
To copy diagrams between applications, such as copying a diagram from PSS™E to Microsoft®
Word, the system clipboard is utilized. A Diagram View can be copied to the system clipboard by
selecting Edit>Copy to clipboard from the Main Menu. This action copies everything visible in the
Diagram View to the clipboard; the user is not required to select any elements before initiating this
type of Copy.
Another way to use a Diagram View in other applications is to export the Diagram View into either
a JPEG (*.jpg) or Bitmap (*.bmp) image file. To export a Diagram View into an image file, select
File>Export Diagram Image… from the Main Menu. A File dialog will appear prompting for a name
to save the image file under. Select the image file format, either JPEG or Bitmap, by using the Save
as type: drop-down box at the bottom of the dialog. Click Save to export the visible area of the Dia-
gram View to the specified file.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-35
The User Interface PSS™E-31.0
Diagram View Users Manual
When saving as a JPEG file, a JPEG Quality dialog will appear where the user can control the
quality level of the saved file (see Figure 2-36).
Figure 2-36. JPEG Quality Dialog for Diagram Export to JPEG File
The behavior of Cut/Copy/Paste in the Diagram View is dependent on the setting of the Bind Items
option (Figure 2-37) when the diagram items are cut, copied or pasted. When Bind Items is
selected, changes to diagram items are synchronized with the associated network items. Cutting
items from the Diagram View in this mode will delete the items from the network as well as the dia-
gram. Pasting items into the Diagram View will add the items to the network as well as the diagram.
When Bind Items is not selected, changes to the diagram items are not synchronized with the net-
work. Cutting and pasting in the Diagram View will have no effect on the underlying network.
Consequently there will be no apparent data changes in the Spreadsheet View.
Cutting diagram items from the Diagram View places a copy of the diagram items and associated
network items in the PSS™E diagram clipboard and deletes the diagram items from the Diagram
View. Network items are also deleted if the Bind Items is active.
Copying diagram items from the Diagram View places a copy of the diagram items and associated
network items in the PSS™E diagram clipboard.
Pasting diagram items from the PSS™E diagram clipboard places copies of the diagram items in
the Diagram View. New network items are created in the network if Bind Items is selected.
2-36 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram View
Currently, the Diagram View provides undo support for the last 30 actions in the Diagram View.
The Edit>Undo option provides support for undoing both Diagram View and network changes. If
a bus is deleted from the Diagram View with Bind Items enabled, both the diagram item and the
associated network bus is deleted. The Undo option will restore both the diagram item and the net-
work bus.
To Cut or Copy from the Diagram View, first select the items to be cut or copied and then click the
Edit menu to select Cut or Copy. The Undo and Paste options are also on the same menu. Right-
clicking on the Diagram View displays a menu containing the same items (see Figure 2-38).
Edit Menu
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-37
The User Interface PSS™E-31.0
Diagram View Users Manual
Right-clicking in a Diagram View without a diagram item selected brings up the following menu (see
Figure 2-39.)
Selecting a network item in the Diagram View and then right-clicking in the view, or right-clicking
directly on the network item brings up a menu for that item. The bottom part of the menu displays
menu items specific to the type of network element selected:
Cut: Context sensitive, standard Windows® Cut menu option. In the case of a selected dia-
gram element, the system will either cut the graphic representation or cut the representa-
tion and the corresponding model information into the System Clipboard, depending on
whether the Bind option is set or not.
Copy: Context sensitive, standard Windows Copy menu option. In the case of a selected
diagram element, the system will either take a copy of the graphic representation or a copy
of the representation and the corresponding model information into the System Clipboard,
depending on whether the Bind option is set or not.
2-38 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram View
Paste: Pastes the current contents of the clipboard. If the Bind option is on, and the copied
area exceeds the number of existing elements, PSS™E will automatically create the extra
network elements required (and generate appropriate bus numbers).
The Copy/Paste functions relate to the type of window involved. Specifically, when you copy
or cut from the Diagram View, you can only paste back into the Diagram View. When working
from the Spreadsheet View, when you copy a cell or group of cells, you can paste the results into
the Spreadsheet view or an outside application like Microsoft® Excel. Further, you can copy a piece
of your network from a diagram into PSS™E’s clipboard, you are allowed to copy a collection of
cells from a Spreadsheet view into PSS™E clipboard at the same time; PSS™E will keep track of
both copies. After, when you paste back onto the spreadsheet or an external application like
Notepad, the software will know to paste the copied data from the spreadsheet. If you paste on the
diagram, the software will paste the copied data from the diagram.
The Undo/Cut/Copy/Paste options are discussed in some detail in Section 2.5.7. Some of this
menu’s other options are active only when a diagram item has been selected. The items active in
this menu are discussed below.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-39
The User Interface PSS™E-31.0
Diagram View Users Manual
gram items are drawn in the order they appear in the display list. In some cases, it might be
desirable to have a particular item drawn after or before another. This would be the case where two
diagram items occupy the same general area in the Diagram View and one needs to be drawn over
the other.
Diagram items may be "grouped" together to form logical units. These units can then be modified
as a single entity. Diagram items can belong to only one group at a time. If a diagram item already
belongs to group and is added to a new group, it is removed from the existing group before being
added to the new group. Grouping items together is particularly helpful when wanting to move a
collection of diagram elements as a group.
Grouping>Group: Before selecting the Group option first define a group by either holding
down and dragging the left mouse button on a portion of the diagram to block select the
items to be grouped, or use [Ctrl]+ left-mouse-click to selectively add items to the group.
After doing so select Grouping>Group to build a group out of all the selected diagram
items. Figure 2-41shows a group of items selected for grouping. Selecting only one item
and clicking Group has no effect.
Grouping>Ungroup: To ungroup a previously grouped set of items, select the group in the
diagram and select Grouping>Ungroup to explode the group back into individual items.
Ungrouping a selected item which is not part of a group has no effect on the selected item.
2-40 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram View
To include any item in the group, it must be totally selected. The figure shows the selection of
buses 3001 and 3002 and the branch between them. Once the items are grouped, the partic-
ular group can be selected by clicking on any one of its elements.
The system manages annotations (labels) associated with a given device as if it were
"grouped" with the device. If the device is deleted, the related annotation is also deleted. If the
selected device is moved, the related annotation is also moved. Therefore, adding a device to a
larger group, in effect, adds all the related annotation to the larger group as well. This grouping
behavior automatically moves annotations when the device is moved (called autopositioning), but
can be disabled by selecting Properties>Auto Position. When autopositioning is disabled, the
annotation must be explicitly selected to be added to the group during the grouping operation.
Manage Layers: This tool provides a way to easily hide and show different groups of dia-
gram items. Multiple diagram items can be assigned to a layer. Each layer has its own vis-
ibility options, as well as an option to turn selectability on and off.
Manage Views: This option provides a way to store and retrieve a variety of one-line dia-
gram presentations at different zoom levels and with data presentations. At times this may
be desirable for establishing unique views of the data in different one-line diagrams such
as for displaying different results or other information and zooming or panning to different
levels to examine different parts of the network. If these specific views are needed on a reg-
ular basis, then those views can be stored for rapid retrieval. Selecting the Manage Views
option opens the Saved Views dialog (see Figure 2-42).
• To save the current view, click on the New (insert) icon, type in a name for the view
and click Save. With several views saved, the desired view can be selected from
the available list.
• To restore a view, select the view from the list and click Restore. The image will
be repositioned and zoomed to the settings specified for the view.
• To delete a view, select the view to delete from the list and click the Delete icon.
• To reposition a view within the list, use the Move Up and Move Down arrow but-
tons.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-41
The User Interface PSS™E-31.0
Diagram View Users Manual
Network Data: With a diagram element selected, selecting the Network Data option acti-
vates the spreadsheet, changes to the correct data tab, and places the focus on the first
spreadsheet cell of the selected data item. The data can then be examined and manipu-
lated as desired. If more then one diagram item is selected or no items are selected, then
the Network Data option is disabled.
Create bus subsystem: Defines a bus subsystem consisting of all elements selected on
the diagram. Both the Spreadsheet View and the Tree View will be updated to reflect the
new subsystem selection.
Diagram Annotation: Opens the Powerflow Data Annotation window. From here diagram
annotations (i.e. Branch, bus, equipment annotation and diagram title) and diagram range
checking options can be set. These are described in Section 2.9.2.
Item Properties>Auto Position: Without a network item selected in the diagram, the Auto
Position option setting will indicate the auto-positioning setting for the entire diagram.
If an equipment item or annotation is selected (i.e. machine, load, capacitor), then the Auto
Position option can be toggled ON or OFF for only the selected element. With auto-posi-
tioning enabled, the selected equipment or annotation connected to a bus will orient itself
perpendicular to the bus. Toggling this property OFF allows the diagram item to be posi-
tioned in any orientation (see Figure 2-44).
Auto Position ON
2-42 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram View
Item Properties>Auto Relink: Without a bus selected in the diagram, the Auto Relink
option setting will indicate the auto-relinking setting for all buses in the diagram.
If a busbar/bus node is selected, then the Auto Relink option can be toggled ON or OFF
for only the selected busbar/bus node. With auto-relinking enabled, moving or re-sizing a
busbar causes the attached branches and transformers to re-attach themselves for a per-
ceived optimal representation. Toggling this property OFF allows the busbar to be moved
or re-sized without affecting the attachment of branches and transformers.
Item Properties>Auto Rotate: Indicates whether equipment connected to a bus should
rotate when the bus is rotated. Toggling this property off (no checkmark) retains the position
of the equipment when the bus is rotated. This menu option is only available when a
non-bus item is selected.
Item Properties>Font: Displays the Font Selection dialog from which a new text font,
style, and point size for the selected item and its result labels can be applied. This item is
only available when a label (annotation) is selected.
Item Properties>Line Style / Color: Displays the Line Style dialog for changing the color
and style of lines, annotation or primitive shapes. Primitive shapes include straight lines,
arcs, circles, polygons, etc that may be placed in any location on the Diagram View. The
button icons for accessing them are located on the Diagram Toolbar along with the other
network diagram elements.
Item Properties>Visible: Toggles whether the selected item is to be made visible or invis-
ible on the diagram. When the Visible option is toggled off the item is still selectable, as
denoted by the selection handles that appear when the location of the item is clicked on,
however it is not visible. This option is only available when an item, or items, are selected
(whether visible or invisible!).
Item Properties>Unbind: Selecting the Unbind option overrides the binding of the
selected diagram item from the associated network model. Unbinding an item causes the
diagram element to be disassociated with the network item. The network model item in the
Tree View and the diagram element must be reselected and the Bind option from the Tree
View right-click menu must be invoked to bind the items again. This item is only available
when a network item (or items) on the diagram is selected.
Item Annotation: Launches an Item-specific Annotation Properties dialog box that pro-
vides control over the annotation displayed with the selected item. For example, when the
selected item is a bus, selecting Item Annotation brings up the Bus Annotation Proper-
ties sheet for the bus shown in Figure 2-45.
The Item Annotation Properties dialog will depend on what diagram item was previously
selected. The Item Annotation option is only available when a network element is
selected.
A variety of options for selecting and positioning the annotation are available. The standard
positions for bus information, which include numbers, names and voltages are to have
name and/or number at the top right of vertical buses and the voltage at bottom right.
For horizontal buses, the positions are top left for names and numbers and bottom right for
voltages. In addition, the annotation changes can be applied to all diagram items of the
selected type, in this case buses, by checking the Apply the selected option to all buses
checkbox at the bottom of the properties sheet. Similar selection boxes appear on other
equipment annotation properties windows.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-43
The User Interface PSS™E-31.0
Diagram View Users Manual
As mentioned at the start of this section, the items shown at the bottom of the right-click Diagram
View menu are customized to the element(s) selected on the diagram. Figure 2-46 shows the lower
portion of the right-click menu when a bus is selected. There may be other options when another
type of equipment is selected on the diagram (i.e., load, machine, etc). Below are inclusive descrip-
tions of all possible options that may appear.
Toggle bus symbol: If a bus was the selected item, the Toggle bus symbol option appears
on the menu. Selecting Toggle bus symbol toggles the selected bus between the busbar
and busnode representations (see Figure 2-47).
2-44 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram View
Grow N Levels…: Selecting Grow N Levels… draws any undrawn elements connected
to the bus using the method described in Section 2.5.5.
Split bus: If a single bus is selected on the diagram, then the Split bus option appears on
the menu. Selecting Split bus displays a dialog prompting for a new bus number, name
and base kV. Pressing OK will split the bus into two bus, preserving the existing one and
adding a new one. Equipment and lines can then be moved between the buses by holding
the [Ctrl] key and clicking on the end of the equipment/line and dragging to the new bus.
See Section 4.6.5 for a detailed description.
Join buses: If two buses are selected on the diagram, then the Join buses option appears
on the menu. Selecting Join buses displays a dialog prompting how to handle line shunts
of deleted in-service branches. Pressing OK will join the two buses into a single retained
bus. See Section 4.6.4 for a detailed description.
Switch: Selecting Switch toggles the status of the selected item(s) to either in-service or
out-of-service. The graphical representation of the diagram item is changed accordingly.
Combine/Split Machines: If a single bus with at least one connected machine diagram
item is selected, then the Combine/Split Machines option appears on the menu. Selecting
Combine/Split Machines combines multiple machine diagram items at the bus into a sin-
gle summing machine symbol, where results are summed for total generation at the bus. A
summing machine symbol has no machine ID in the center of the symbol whereas a
machine diagram item representing a single machine has a machine ID in the center of the
symbol.
If only a summing machine symbol exists on the bus, selecting the bus and then the Com-
bine/Split Machines option will remove the summing machine symbol and replace it with
one or more machine diagram items representing the individual machines at the bus.
Combine/Split Loads: This operation does the same operation as Combine/Split
Machines but for Loads.
Combine/Split Fixed Shunts: This operation does the same operation as Combine/Split
Machines but for Fixed Shunts.
Collapse buses towards high voltage bus: When two buses are selected and the Col-
lapse buses towards high voltage bus is used, all elements on the lower voltage bus will
now appear to be connected to the high voltage bus, and the lower voltage bus will be
removed, as well as any elements that were connecting the two buses. These elements will
be removed from the diagram, but they will not been removed from the actual network.
When any analysis is done, these elements are still included in the calculations. This func-
tion is used to visually change the layout in the diagram view, and has no effect on the
actual network.
Collapse buses towards low voltage bus: When two buses are selected and the Col-
lapse buses towards low voltage bus is used, all elements on the higher voltage bus will
now appear to be connected to the low voltage bus, and the higher voltage bus will be
removed, as well as any elements that were connecting the two buses. These elements will
be removed from the diagram, but they will not been removed from the actual network.
When any analysis is done, these elements are still included in the calculations. This func-
tion is used to visually change the layout in the diagram view, and has no effect on the
actual network.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-45
The User Interface PSS™E-31.0
Diagram View Users Manual
The right-click menu obtained from selecting a line element is similar to that for a bus selec-
tion but the bus related options will not exist. The bottom portion of the menu list may now
include the Switch and Tap line option (see Figure 2-48).
The Switch option toggles the status of the equipment to either in-service or out-of-service and
changes the visual properties of the line.
The Tap Line option allows for the introduction of a new bus into the working file at a designated
location along a selected AC branch. Any nontransformer branch may be tapped. The Tap Line
option is discussed in detail in Section 4.6.6.
If the selection is a transformer, the Tap line option will be absent but the Switch option will remain.
For bus connected capacitors and reactors the Switch option will not be available. To switch the
status of capacitors and reactors, double-click on the network item (or right-click and select Net-
work data…) to edit the status field of the corresponding data record in the Spreadsheet View.
2-46 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram View
Even if all layers are visible, only one is considered the "active" layer. The active layer and its
name is always displayed in the Status Bar at the bottom of the Spreadsheet View. The
active layer is the layer selected when the Layers dialog is closed.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-47
The User Interface PSS™E-31.0
Diagram View Users Manual
The Visibility of the layers may be made either Fixed or Zoom-dependent, depending on the option
selected. If a layer is Fixed, it is in the Diagram View but can additionally be made either visible or
invisible by checking or unchecking the Visible checkbox. If a layer is Zoom-dependent, its visi-
bility in the Diagram View is determined by the current zooming factor. If the current zooming factor
is within the minimum and maximum zooming factors specified, then the layer is visible. If the
zooming factor is outside of the range, then the layer is invisible.
It is not necessary to close the dialog to save the changes to a layer. Changes are saved whenever
a different layer is selected from the list. All items on a selected layer may be made unselectable
by unchecking the Items are selectable checkbox. This can be handy if you want to avoid the inad-
vertent selection or manipulation of certain diagram items. Simply place those items of concern on
a layer that it made unselectable.
The layer’s description may be changed by selecting the layer from the list and entering a new
description in the Layer description field.
Layers are added by clicking the Add button. The attributes of this new layer may then be modified
as described above. Layers are removed by selecting the layer from the list and clicking the
Remove the last button.
The Diagram>Set Active Layer option from the Main Menu, as shown in Figure 2-50, invokes a
Select Layer dialog for assigning selected items to a specific layer (see Figure 2-51).
Diagram items may be assigned to a given layer by selecting Display>Assign to Layer… on the
right-click menu. The desired layer for the selected item is specified via the Select Layer dialog
(see Figure 2-51).
This method can be used to assign diagram items to a layer one at a time, or a group of items can
be selected and all be assigned to a layer. As an example, all diagram items from Area 1 of the
savnw.sav power flow case can be selected and assigned to a layer with the name Area 1. To add
the new layer, open the open the Layers dialog, as shown in Figure 2-50, click Add, and enter the
desired information. After adding the additional layer, the Layers dialog will appear (see Figure 2-
53).
2-48 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram View
To see the entire one-line diagram, select all layers to be "visible" (see Figure 2-54). If the Area 1
layer is selected to be not visible, the one-line diagram will show only the diagram items belonging
to Default (see Figure 2-55).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-49
The User Interface PSS™E-31.0
Diagram View Users Manual
2-50 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram View
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-51
The User Interface PSS™E-31.0
Diagram View Users Manual
The default information shown for buses includes the number, name and the voltage expressed as
magnitude (pu) and angle. Flows are shown at both ends of each branch in MW and Mvar units. A
positive number indicates the flow is away from the bus, (56 MW is flowing from bus 3002 towards
bus 3004).
Generator information includes power in MW and reactive power in Mvar. On bus 3011 the "R" indi-
cates that the machine is within its reactive limits.
Separately shown are a Load of 200 MW + j100 Mvar and a shunt capacitor providing 46.7 Mvar.
The results presentation shown may be modified globally for the diagram by selecting Dia-
gram>Annotation. The details of this option is described in Section 2.9. Using the right-click menu
applied to a specific diagram item opens an annotation dialog for that specific network item.
Bus Annotation
Right-clicking on a bus in the Diagram View opens the Bus Annotation Properties sheet (see
Figure 2-58). The information displayed, as well as its positioning, can be selected. Further, you can
select to suppress all annotation at the selected bus or choose to apply the annotation properties
selected to all buses by checkmarking the Apply the selection option to all buses box.
2-52 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram View
Equipment Annotation
Right-clicking on a load or a shunt capacitor/reactor opens the appropriate annotation properties
dialog (see Figure 2-59). You can choose the type of display, whether to suppress the display, and
optionally whether to apply the properties to all shunt or load items.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-53
The User Interface PSS™E-31.0
Diagram View Users Manual
2-54 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram View
By default the diagram displays the generator scheduled power and the reactive power limits. Bus
information includes the bus number, name and base kV. Line and transformer information shows
the R, X and B values, as appropriate and the transformer tap information is included. The presen-
tation can be modified using the annotation properties tools discussed in the previous section for
the power flow results.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-55
The User Interface PSS™E-31.0
Diagram View Users Manual
Within the Graphical case comparison window enter or select the saved case file to be compared
against the currently open power flow case.
In the Bus comparison based on section select the identification method to be used for comparing
the buses within the two sets of cases. This selection establishes how buses in each case are deter-
mined to be the "same" bus. Choices include comparison by bus number, bus name or both. If
buses in the two cases are matched using only their extended bus names, then the extended bus
names of the bus in each case must match and no other bus in either case can have the same
extended bus name. Alarms are printed in the Output View or the selected reporting device if any
problems occur.
The Bus annotation option allows for either bus names, bus numbers or both to be displayed on
the diagram.
The results in the one-line diagram show the differences in solution results and bus boundary con-
ditions between the current power flow case and the selected saved case. Differences are always
calculated as comparison case values minus power flow case values. At each bus in the bus com-
parison list, voltage differences in per unit and phase angle differences in degrees are shown. All
other difference values are shown in MW and Mvar. An example diagram is shown in Figure 2-63.
2-56 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram View
The difference fields are left blank for equipment items present in the power flow case, but not in
the comparison case. Those items present in the comparison case that are not included in the
power flow case are omitted from the diagram.
Differences in flow into a converter bus of DC line "n" are shown if all of the following conditions
apply:
Differences in the sending end bus’ shunt element of FACTS device "n" are shown if all of the fol-
lowing conditions apply:
Differences in series flow at the terminal end bus are shown if all of the following conditions apply:
• FACTS device "n" is present and has a series element in both cases.
• The terminal end bus is in the bus compare list.
• The same terminal end bus is specified in both cases.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-57
The User Interface PSS™E-31.0
Diagram View Users Manual
To initiate the calculation process select the Diagram>Results>Short circuit data option from the
Main Menu or the associated toolbar button. The resulting dialogue and fault calculation procedure
is covered in detail in Chapter 7 and more specifically Section 7.6.3.2.
The Animate flows button is used to animate branch flows on the active Diagram
View. The branch flows are animated using the flows from the last load flow solution
(see Figure 2-64a).
The Current loadings button is used to display line loading graphs. The graph values
are set using values from the last load flow solution. See Figure 2-64b
The Multisection line reporting button is used to expose or hide the dummy buses
that constitute the terminals of multiple sections that make up a single line between
buses (see Figure 2-65).
2-58 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram View
The partial one-line diagrams in Figure 2-65 show the presentation with and without multisection
line reporting. There is a multisection (2 section) line between bus 3008 and bus 3005 which is
shown as a single section with the reporting OFF. With reporting ON the "dummy" bus (bus 3007)
is shown. The diagram automatically draws the two line sections and the dummy bus when the mul-
tisection line reporting is ON although the diagram might need to be adjusted.
(b) Reporting On
2.5.11.9 Contouring
Contours can be drawn on the Diagram View.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-59
The User Interface PSS™E-31.0
File Menu Users Manual
Figure 2-66. Alternative File Menus for Active Spreadsheet and Diagram
Views
Within the Main Menu the Diagram Menu appears only when the Diagram View is active. Addition-
ally, there are two other Menus on the Main Menu that change depending on whether the Diagram
View or the Spreadsheet View is open.
2-60 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual File Menu
(a)
(b)
Figure 2-67. Opening the New and Build New Case Dialogs
The system stores the Heading lines as comments within the exported case. They are used
to document the case.
The DRAW coordinate data files cannot be opened in this menu. Refer to Section 2.5.2.1 for
importing a DRAW file.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-61
The User Interface PSS™E-31.0
File Menu Users Manual
Or
When Save or Show option is selected, the Save/Show Network Data dialog will open (see
Figure 2-69). Data that can be saved includes:
• Case Data
• Power Flow Raw Data
• Optimal Power Flow Data
• Machine Impedance Data
• Sequence Data
• Transaction Data
• Power flow data in IEEE format
• UCTE Data
2-62 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual File Menu
Each data type has its own tab. When a tab is selected options on how to handle the data and a
subsystem selector option is available. The choice of a destination; either a file or Output Bar (for
raw data files), is available.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-63
The User Interface PSS™E-31.0
File Menu Users Manual
Two file type options are available for saving the file to. The Slider Binary File (*.sld) is the standard
Slider format in which to save diagrams. An alternative Slider XML File (*.sldxml) selection will save
the diagram to an XML text file.
2-64 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual File Menu
• Case Totals
• Power Flow Cases
• Tie Lines
A typical report produced by the comparison is shown in Figure 2-73. The report compares the total
generation, load, losses and solution mismatches. Differences in the totals for each case as also
presented (under the DELTA columns).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-65
The User Interface PSS™E-31.0
File Menu Users Manual
2-66 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual File Menu
(a)
(b)
Figure 2-74. Accessing the Select Power Flow Comparison Options Dialog
Clicking on the Compare field produces the drop-down list for all the data and results categories
available for comparison (see Figure 2-75).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-67
The User Interface PSS™E-31.0
File Menu Users Manual
When a category is selected, the options shown in Figure 2-74b will change to those appropriate to
the category.
The Comparison threshold type may be set to either percent or engineering units whenever
appropriate.
The comparison results are output to a Report tab in the Output Bar or to a report file designated
by the user through I/O Control>Direct Report output (OPEN)….
The results displayed show all differences between the case that are greater than the defined
threshold values.
2-68 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual File Menu
When selections are complete, clicking Go opens the Select Tie Line Comparison Options dialog
(see Figure 2-76a). Clicking on the Compare field produces the drop-down list shown in Figure 2-
76b from which a comparison value may be selected. Units for the comparison threshold, the level
of threshold, and, where applicable, the ratings to be compared are also specified. Clicking the
Compare button performs the comparison and outputs the results to either a Report tab in the
Output Bar or to a file designated by the user.
The results displayed will show all differences which are greater than the selected thresholds.
(a)
(b)
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-69
The User Interface PSS™E-31.0
File Menu Users Manual
The information requested may be written to a Report tab in the Output Bar or to a file designated
by the user through the I/O Control Menu. Below is a description of each available option on the
File Information dialog.
2-70 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual File Menu
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-71
The User Interface PSS™E-31.0
File Menu Users Manual
Selecting the Import long title (RETI) option opens a file selector dialog from which an existing text
file containing the long title text may be imported.
Selecting the Import ECDI File option opens a file selector dialog from which an existing ASCII file
containing economic dispatch data may be read in. The data populates the Optimal Power Flow
(OPF) generator cost curve data records for use in the OPF solution.
2-72 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual File Menu
Selecting File>Import>DRAW file… displays the file selector dialog from which a DRAW file may
be selected for import into the one-line diagram. The DRAW file is the coordinate data file con-
structed and used in previous versions of PSS™E.
Once imported the diagram can be saved (using Save or Save As…) in the new Slider format file
(*.sld). When the diagram is imported, all diagram items are placed on one layer. The user is then
free to move diagram items to other layers.
Selecting File>Import>Image file… displays the Import Image File dialog (see Figure 2-81).
From here a variety of image file types may be imported including bitmaps (*.bmp), JPEG files
(*.jpg), GIF files (*.gif) and PNG files (*.png). The image is imported into the active Diagram View
and is placed in the background layer. From there it can be move if required.
When a JPEG file type is selected, the export process facilitates the selection of the JPEG quality
level on a scale of 1 to 100 (see Figure 2-36). Some experimentation may be necessary to find the
desired level of quality.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-73
The User Interface PSS™E-31.0
File Menu Users Manual
2-74 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual File Menu
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-75
The User Interface PSS™E-31.0
File Menu Users Manual
Figure 2-83. Setting Up Header and Footer for Printed Spreadsheet Tab
The Header/Footer dialog presents a full facility for setting the header and footer spacing, the align-
ment, page numbering and the style, size and other font characteristics. If the Save settings to
profile option is checkmarked, then the next time PSS™E is used, the saved profile will be
assumed and activated.
2-76 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual File Menu
Selecting File>Print… opens the Print dialog (see Figure 2-85b). The common print setup facilities
are available including the printer or network selection, the printer properties, the page range and
number of copies.
The print activity can also be used to save to a file designated by the user.
The File>Print Preview option show a facsimile of the page as it will be printed.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-77
The User Interface PSS™E-31.0
File Menu Users Manual
(a)
(b)
(c)
2-78 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Edit Menu
Figure 2-86. Alternative Edit Menus for Active Spreadsheet and Diagram
Views
If a bus is deleted from the Diagram View with Bind Items selected, both the diagram item and the
underlying network bus is deleted. If Edit>Undo is then executed, both the diagram item and the
network bus are restored.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-79
The User Interface PSS™E-31.0
Edit Menu Users Manual
application keeps notify the user of the problem. At this point, Edit>Undo Record operation will
reset the application back to the state before the Add operation was begun. The missing data can
then be added in other spreadsheets and the item added again. Once the data has been entered,
however, the Undo Record operation will not do anything.
Between Cells
Data can be copied and pasted between cells using the standard [Ctrl]+C, [Ctrl]+V keystrokes, or
by selecting Edit>Copy and Edit>Paste from the Main Menu.
Between Rows
All or some of the cells in a row can be copied to another row on the same spreadsheet tab. To do
this, select the row(s) to copy by clicking in the row header column(s). The [Shift]+left-mouse-click
and [Ctrl]+left-mouse-click can be used to select multiple rows. Once the row(s) are highlighted
copy the data using either the standard keystrokes [Ctrl]+C or the Edit>Copy function. Click on the
row(s) where the data is to be placed and use either the standard [Ctrl]+V keystroke or the
Edit>Paste function.
Bus numbers and other identifiers are not copied as this would result in duplicate data items
in the network. These identifiers will automatically adjust to the next available value when
pasted.
Select the diagram items to be copied before selecting Edit>Copy to clipboard. To paste the clip-
board contents to another application, use the paste function in that application. To paste the
clipboard contents to a Diagram View, select Edit>Paste or right-click on the Diagram View and
select Paste.
Select Edit>Find Again to search a selected column for the value entered during the last Find oper-
ation. It will only find the first match. It cannot be used to iterate through matching items in the
2-80 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Edit Menu
column. To iterate through matching items in the column, click the Find Next button in the Find
dialog to find successive items.
The Find and Find Again dialogs can also be opened by selecting a column and right-clicking
on the column header. See Section 2.4.3.1 and Figure 2-19.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-81
The User Interface PSS™E-31.0
Edit Menu Users Manual
Output options: Allows you to choose whether to create a new tab for each output report,
and to specify the maximum number of lines to display.
Auto-Save option: Allows for the automatic saving of the currently open power flow case
and how often the case is to be saved. The option to save the case under its current name
or to save it to a temporary file named PsseTempSave.sav is also provided.
Auto bus and equipment numbering: When creating a one-line diagram from scratch,
with the Bind option on (see Section 2.9.8), the addition of network items into the Diagram
View will populate the Spreadsheet View with data as you build a new network (see
Section 3.7). Without the Bind option selected, the network items added will belong to only
the Diagram View. In either case, if the option to Automatically number buses, lines,
and equipment is enabled, the program will automatically number the buses as they are
added. The initial bus number and the increments by which subsequent buses are num-
bered may be specified in the fields provided.
2-82 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Edit Menu
Diagram interactions:
If the Upon changing IDs, update all open diagrams option is enabled, then when
IDs in the spreadsheet are changed, the IDs in the Diagram View will automatically be
updated.
If the Allow "single click" deletion of a bus and all its equipment option is enabled,
then a selected bus on the diagram may be deleted, along with all its equipment, by
either using the [Delete] key or selecting Delete from the right-click menu. Otherwise
these options are not available.
If the Allow drag panning of the diagram option is enabled, then the "select" mouse
pointer will turn to Pan mode when the left-mouse-button is clicked on the diagram,
held down and dragged. Otherwise, the default behavior of holding down and dragging
the "select" pointer is to form a selection box around a portion of the diagram.
If the Zoom GOUT/GEXM to extents option is enabled, then a bus is displayed in the
diagram via the GOUT/GEXM command will fill the entire diagram viewing area.
If the Only "Grow" in-service items option is enabled, then only those items currently
in-service will be drawn during a Grow operation.
If the Only "Grow" items in current bus subsystem option is enabled, then only
those items in the current bus subsystem will be drawn during a Grow operation.
If the Use Bus Location file to "Grow" items option is enabled and a Bus Location
file has been opened, then any Grow or Auto-Draw operations will use the Bus Location
file when placing buses on the diagram.
If the Display Circuit ID’s on all lines with ID’s/Names option is enabled, then circuit
ID’s will be displayed for every line that is drawn that is bound to line in the network.
If the Allow "Grow" from GOUT/GEXM option is enabled, then the user will be able
to grow a diagram generated from GOUT/GEXM. This grow method does not work the
same as the grow method for auto draw. When an element is told to grow it will draw
all lines connected to it along with all buses connected to those lines regardless of
whether or not the bus is already drawn. In other words, grow in GOUT does not avoid
redrawing the same bus.
The Default Bind mode setting indicates the default setting for whether diagram items
are to be bound to network items or not bound.
The Default GOUT/GEXM font is used to select a font for the labels created when
using GOUT/GEXM diagrams.
The Default Bus Height is the default length of the bus, in inches, that is drawn when
either Auto-Draw or Grow operations take place in a one-line Diagram.
The Default "Grow" Spacing is the default distance between buses, in inches, when
either Auto-Draw or Grow operations take place in a one-line Diagram.
General Options:
If the Delete working files option is enabled, then the working files are deleted when
the program is closed.
The mode selection box is used to select a mode used to read in raw files.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-83
The User Interface PSS™E-31.0
View Menu Users Manual
If the Always prompt to "Save" modified files is enabled then the user will be
prompted to save any modified files when attempting to close the file or the program.
Configuration file text editor: This field is used to select a text editor that can be launched
wherever an input configuration text file is specified. The file selector can be used to browse
for a *.exe file that is capable of editing a text file.
2-84 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram Menu
• Labels
• Grid
• Printing
• Colors
• Zoom and Pan
• Display
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-85
The User Interface PSS™E-31.0
Diagram Menu Users Manual
Labels: Select from a variety of font styles, sizes and colors to apply to the labels on the
diagram. Options for hiding or showing all labels and hiding results labels are also avail-
able.
Grid: The Diagram View contains an underlying grid pattern that may or not be visible. The
line style and width, as well as the spacing and snap distance, of the grid may be specified.
For very dense diagrams the snap distance must be sufficiently small to better ensure that
items snap to the desired grid point instead of one further away.
Printing: Three options are available for printing a diagram:
• As seen on the screen (WYSIWYG): "What you see is what you get" (WYSI-
WYG). Prints only that part of the one-line diagram which can be seen in the Dia-
gram View. This might be only part of the diagram if you have zoomed in to see
more detail. This can be checked by selecting File>Print Preview.
• Fit the whole diagram to page: The entire one-line diagram is printed on one
page independent of whether or not the entire diagram is shown in the Diagram
View.
• Multi-page: Allows the user to print the entire diagram over multiple pages, inde-
pendent of whether or not the entire diagram is visible in the Diagram View. This is
useful when the one-line diagram is large.
High Quality printing: If the diagram is zoomed out, labels and text can appear blurry
when printed. Enabling High Quality printing will smooth out all text and labels. The use
of this option will result in larger print files and longer print times. Some experimentation
may be necessary to determine the effectiveness of this option.
General Colors: Defines the colors for the Background, Grid and Port. The ports are
symbolized by small circles that appear at the locations where lines and equipment connect
to buses. Ports appear when lines and equipment are selected and along the bus as con-
nection points when a network item is moved to a new bus location.
Network Item Colors: Defines the colors for bound and unbound diagram items. All net-
work items in the Diagram View that represent actual data in the network are drawn in the
bound color, unless over-ridden by range checking coloration. All network items in the Dia-
gram View that do not represent data in the network are drawn in the unbound color. The
range checking colorations are discussed in Section 2.9.2.
The power flow results can be animated to show flow directions for real and reactive power
(see Figure 2-90). The "P" flow arrow and the "Q" flow arrow palettes allow for selection of
a color for these arrows.
Zoom/Pan: Values for the maximum and minimum zoom multipliers, and value in which to
increment/decrement the zoom factor by each time the diagram is zoomed in or out, may
be entered directly in the fields provided. In addition, it is possible to hide some diagram
items when the zoom factor is small and the diagram becomes more crowded. These
include such things as the "handles" which appear at each end of a bus when it is selected.
Image File Directory: Images may be imported to the background layer of the Diagram
View. Specifying an Image file directory identifies the default path for commonly used
images.
Display Options: Located in the lower right hand corner of the Diagram Properties sheet,
are several self-evident display options. If the Display Tooltips option is checkmarked,
then when the mouse cursor is held over a diagram item such as a bus, a pop-up note will
2-86 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram Menu
be displayed that gives basic information about the bus such as number, name and base
kV.
Power Flow results precision: Defines the number of decimal places used in represent-
ing Power Flow results.
Diagram annotations can easily be adjusted by changing options in the Diagram Annotation tab.
Choices include the type of results annotation information to be displayed for Branches, Buses and
Equipment. Additionally, the user can elect to represent flows on the branches with either signs or
arrows (see Figure 2-91). The real power, in each case is shown above the branch.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-87
The User Interface PSS™E-31.0
Diagram Menu Users Manual
The Diagram Range Checking tab is a very useful tool for the user (see Figure 2-92). Not only can
the Diagram View show numerical results for bus voltage, line flow and equipment loading, but
color coding can be set up to provide rapid identification of problems. In addition, the user can
choose to over-ride the color selected for bound items and select colors for each voltage level in
the network. This makes it easy to identify networks at different voltage levels.
The Use voltage level thresholds option, when checkmarked, visually identifies equip-
ment and lines based on their voltage level. Voltage levels may be specified by entering a
value directly in the input field or using the scroll buttons. Color and style specification may
be modified by clicking on the sample image shown under the corresponding voltage value.
2-88 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram Menu
The Use line ratings option, when checkmarked, visually identifies lines that are loaded
above the specified percent loading value. The color and style of the line may be modified
by clicking on the sample image to the right of the % loading field. To identify the branch
rating to which the % loading value is to be applied, click on the Branch Rating Set drop-
down menu and select from one of the options. Rate A is typically used for normal power
flow conditions while Rate B or C would be used to examine contingency conditions where
loadings are often allowed to be higher.
The Use bus voltage limits option, when checkmarked, visually identifies buses with volt-
ages above or below specific levels. The maximum and minimum voltage levels may be set
by entering values directly in the fields or using the scroll buttons. The color and style of
buses that go above the maximum voltage setting or below the minimum setting may be
modified by clicking on the sample image to the right of the corresponding voltage value.
The Out-of-service equipment setting identifies how equipment whose status has been
switched to out-of-service should be visually represented on the diagram. To specify the
appearance of out-of-service equipment, such as a branch or bus, click on the sample
image.
The Loading percentages for loading bar charts input fields are used to control the per-
centage at which overload colors are applied to the loading bar charts. Overload colors
progress from purple to red to deeper shades of red.
Only the bus, branch, and equipment annotations, as well as voltage level thresholds are available
in the impedance data annotation.
Only the bus annotation, and voltage thresholds are available in the case comparison annotation.
Only the voltage thresholds are available in the fault analysis annotation.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-89
The User Interface PSS™E-31.0
Diagram Menu Users Manual
2-90 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram Menu
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-91
The User Interface PSS™E-31.0
Diagram Menu Users Manual
2.9.6 Contouring
• Every item added to a Diagram View will create a corresponding piece of data in the
power flow case (e.g., adding a bus to the Diagram View will automatically add a new
bus to the power flow case); or
• Items that are added in the Diagram View are not added to the power flow case. These
items exist in the Diagram View only as annotation and do not represent real data in
the network.
If the Diagram>Bind Items option is checkmarked (see Figure 2-88) then an element in the power
flow case will be created for every element added to the Diagram View. If no checkmark appears
next to the Bind Items option, then the elements created in the Diagram View will not be added to
the power flow case.
2-92 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram Menu
An example of each option, as it would appear for a bus, is shown in Figure 2-98.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-93
The User Interface PSS™E-31.0
Diagram Menu Users Manual
(a) ID Only
2.9.12 Set Active Layer and Manage Layers Diagram Menu Option
The Diagram>Set Active Layer and Diagram>Manage Layers… options handle the managing
and setting of active layers. These options are covered in Section 2.5.10.
Selecting Diagram>Manage Views… opens the Saved Views dialog from which new views can be
added or a specific view can be selected for presentation (see Figure 2-99).
To preserve the current diagram view for later retrieval, click on the New icon, type in a name for
the view and click Save (Figure 2-99a). With several views saved, you can retrieve the desired view
by selecting it from the Saved Views list and clicking Restore (Figure 2-99b).
2-94 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Diagram Menu
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-95
The User Interface PSS™E-31.0
Power Flow Menu Users Manual
1. Makes sure any name extension is separated by a ’ ’ from the end of the internally gen-
erated name.
4. Fixes any bad annotation tags found on branches and two winding transformers.
The analyses methods not contained in the Power Flow Menu are short-circuit analysis
(Section 2.11), the Optimal Power Flow (Section 2.12), Transmission Access analysis
(Section 2.13) and Dynamics and Disturbances (Chapter 16). These solution methods are available
on their own menus.
The functionality of the applications available from the Power Flow Menu are discussed extensively
in other chapters. The Power Flow Menu is described below in this subsection.
2-96 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Power Flow Menu
References for the Power Flow Menu options are shown in Table 2-1 below.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-97
The User Interface PSS™E-31.0
Fault Menu Users Manual
References for the Fault Menu options are shown in Table 2-2 below.
2-98 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual OPF Menu
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-99
The User Interface PSS™E-31.0
Subsystem Menu Users Manual
2-100 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Miscellaneous (Misc) Menu
The timing process is not sensitive to any interrupt control code options.
At any time during a work session in PSS™E, if the Misc>Reset timing statistics to zero
(TIME,INIT) is selected, the timers are initialized and the same initialization message is printed to
the progress output device.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-101
The User Interface PSS™E-31.0
I/O Control Menu Users Manual
The I/O Control Menu options are shown in Figure 2-109. The first four items involve directing
output to a device of the users’ choice. The next item deals with providing a short cut path to the
users’s files.
The bottom items in the menu are related to recording and re-playing control commands issued by
the user during interactive sessions with the program running under control of automation files and
initializing command line interface sessions.
2-102 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual I/O Control Menu
If the Printer option is selected, the Printer group of the dialog is enabled for selection of the printer
and printing options.
The Report output destination file field is for specifying a filename if file output is selected.
Fortran forms control can be enabled if either file or printer output is specified.
The Append to file, if file exists option may be selected if file output is selected. If enabled, then
any new report output will be appended to the specified file instead of overwriting it.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-103
The User Interface PSS™E-31.0
I/O Control Menu Users Manual
2-104 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual I/O Control Menu
2.16.4 Setting the Path for Use with "&" Filenames (PATH)
The I/O Control>Set path for use with "&" filenames (PATH)… option allows you to specify a
directory path name that can later be represented by an ampersand (e.g., &myfile). This short hand
method for specifying a path name can be used by PSS™E file accessing activities. A filename pre-
fixed by this ampersand will be obtained from the directory specified in the path setting.
When invoking this option, a dialog box is opened in which the directory path to be accessed by the
& short-hand method is selected by clicking on any file in the desired directory (see Figure 2-113).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-105
The User Interface PSS™E-31.0
Tools Menu Users Manual
When selecting the Tools>Customize… option, the Customize dialog is displayed. This gives
access to both a Toolbars tab and a Commands tab (see Figure 2-116).
2-106 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Tools Menu
The Toolbars tab facilitates the selection of those toolbars that are to be active and displayed on
the interface. It also allows you to choose whether to show tooltip messages when the mouse
pointer is held over the toolbar button. The tooltips identify the function of each toolbar button.
In the above figure all toolbars are selected to be visible on the interface except for the Custom
Toolbar. The Custom Toolbar can be made active by checkmarking the Custom option. The
resulting toolbar contains all the user definable buttons. Customization of these buttons is covered
below (Section 2.17.2).
Toolbars can be rearranged in any position on the interface. They can also be dragged off the
toolbar location and converted into floating windows.
The Commands tab displays the individual toolbar categories and shows the buttons currently
assigned to each bar. An example showing the File Toolbar and its associated buttons is shown in
Figure 2-117. Clicking on one of the toolbar buttons will provide a description of its command func-
tion. In this case it is the "Show or hide the output bar". A button can be removed from an active
toolbar by clicking and dragging it from the toolbar to the Buttons area of the toolbar on the Com-
mands tab. Likewise, a button in a particular toolbar category may be added to an active toolbar by
dragging the icon of the button from the Commands tab to the desired location on the toolbar.
Many of the toolbar buttons (or toolbar commands) are duplicates of menu options and will
open the same dialog.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-107
The User Interface PSS™E-31.0
Tools Menu Users Manual
There are 30 buttons which may be defined to invoke a user specified command. Each button
requires a file type, a file name. An optional tooltip to display can also be provided.
File Type - specifies the type of Automation file to be run when the button is clicked.
Options include:
• PYTHON - A Python script file (*.py) (default)
• RESPONSE - A Response file (*.idv)
• IPLAN - An IPLAN program (*.irf)
File Name - the name of the Automation file to be executed when clicking the correspond-
ing custom toolbar button. The filename will contain the full pathname of the file.
Text To Display - an optional description (tooltip) of the operation to be performed when
the corresponding custom toolbar button is clicked. If specified, the description will popup
when the mouse cursor is held over the custom toolbar button. If it is not specified, the
name of the file, as specified by filename, will be displayed as the tooltip.
To define a toolbar button, select one of the buttons from either the available or active button list.
Initially, all buttons will appear in the available button list with a default file type of PYTHON. You
can change the File Type by selecting from the dropdown list of types. Select the pathname of the
file (file must exist), and then type in the tooltip text that you wish to have displayed. Click on the
Update button to apply the changes that you’ve made.
The arrows in the center of the dialog move buttons from being available to being active. Figure
Figure 2-119 shows the results of several buttons having been defined and two being moved to the
active list.
2-108 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Tools Menu
Only those buttons which are in the “Active Button” list will be highlighted when the custom toolbar
is displayed. The others will be grayed out (see Figure 2-119).
Only those buttons which are in the “Active Button” list will be highlighted when the custom toolbar
is displayed. The others will be grayed out (see Figure 2-120).
When the application exits, these custom toolbar button definitions will be preserved in a file named
“Toolbar.prm” found in the "Document and Settings" directory for the active user.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-109
The User Interface PSS™E-31.0
Tools Menu Users Manual
To add command buttons to the new toolbar, click on the Commands tab and drag the desired
toolbar buttons to the new toolbar window. The new toolbar window can be docked to the toolbar
area by dragging the window to the desired location on the toolbar and releasing the mouse.
To remove a user defined toolbar from the list of toolbars on the Toolbars tab, highlight the desired
toolbar to be deleted and click Delete. The standard toolbars can only be reset to their default
settings.
The initial default directory is the current directory (.\). Click on the New (Insert) button to add a new
directory to the search list. A blank line will be displayed (see Figure 2-122).
2-110 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Tools Menu
Click the button at the end of the blank line to bring up the File Directory dialog (see Figure 2-123).
Select a file directory to be searched and press OK. The new filepath will be added to the search
list, as seen in Figure 2-124.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-111
The User Interface PSS™E-31.0
Tools Menu Users Manual
Additional directories may be added, deleted or moved up and down in the search list by using the
buttons at the top of the dialog.When the application exits, the defined paths will be saved in a file
named “DynModelPaths.prm” found in the "Document and Settings" directory for the active user.
Directories are searched for GMB models in the order in which they appear in the dialog shown in
Figure 2-124. To change the search order, select an item file item in the dialog and move it up or
down in the search order by use of the "arrow" icons found on the dialog.
A total of five model search paths may be defined at any given time.
2-112 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Window Menu
2.19 Toolbars
Print preview.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-113
The User Interface PSS™E-31.0
Toolbars Users Manual
The Zoom Combo Box is used to select a predefined zoom factor to apply to the Diagram
View. Click the arrow to the right of the combo box for a drop down a list of predefined
zoom factors from which to choose from. You can also type in a desired zoom factor if it is
not found in the list. The Zoom Combo Box is automatically reflects the current zoom
factor, which can be changed through the use of the other zoom tools.
The Zoom in/Zoom out buttons are used to zoom the center of the diagram in or out.
The Zoom Extent button is used to zoom the diagram out to encompass all items drawn.
The Zoom 100% button is used to quickly return the Diagram View zooming factor to
100%.
The Zoom Window button is used to zoom in on a selected portion of the Diagram View.
The user selects this item and then drags a rectangle over the Diagram View to encom-
pass the part of the Diagram View they want zoomed. The selected part of the Diagram
View is then zoomed to fit in the extent of the Diagram View window.
The Zoom Previous button is used to return the zooming factor of the Diagram View to its
previous setting.
The Pan button is used to scroll around the Diagram View. Upon selecting this item, the
cursor in the Diagram View changes to a hand. The Diagram View is then panned by
holding down the left mouse button and dragging the hand around the window.
2-114 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Toolbars
Delete buses/equipment/lines.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-115
The User Interface PSS™E-31.0
Toolbars Users Manual
Animate Flows.
The "creation" term implies that diagram items, network items or simple annotation items, are
selected from the Diagram Toolbar for construction of a new network diagram. This can imply the
construction of a new power flow case if the diagram items are "bound" to network items. The cre-
ation of a power flow case using the Diagram View and Diagram Toolbar is discussed in
Section 3.8.
2-116 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Toolbars
The Select button is used to select diagram items in a Diagram View. Items can be selected
using common selection techniques (e.g., dragging a rectangle around several objects,
clicking on an item and then holding down the [Ctrl] key to add more selections to the selec-
tion list). The selected items can then be manipulated in many ways.
The Rotation button is used to rotate diagram items. If the rotation item is selected, and then
a diagram item is selected, the cursor changes to a circular arrow. Holding down the left
mouse button while dragging the cursor will rotate the selected item around its center.
The +90 button is used to rotate a selected item positive 90 degrees.
The Show Grid button is used to toggle on or off the display of a grid in the Diagram View.
The Grid Snap button is used to toggle on or off the feature that causes the location of any
newly created diagram item to snap to the nearest grid point in the Diagram View.
The Toggle Labels button is used to toggle on or off the display of labels in the Diagram.
The Kneepoint button is used to put bends, or kneepoints, in a link that connects two diagram
items. Links are used to represent lines, the connections between two- and three-winding
transformer symbols and buses, and the connections between equipment and buses. When
the kneepoint item is selected the cursor changes to a crosshair. Clicking on a link will place a
red square on the link. This red square can later be dragged with the select item to achieve the
desired shape. Kneepoints can be deleted by selecting the kneepoint and pressing the
[Delete] key.
The Bus button is the basic building block of a PSS™E case and a Diagram View. Buses
need to exist in a Diagram View before any lines or equipment can be drawn. Buses have a
number of discrete "ports" arranged along both sides of the busbar. When connecting lines
and equipment to a bus, the connection point will snap to the nearest port.
The Horizontal Bus is the same as a regular bus, except that when drawn on the Diagram
View it is placed horizontally across the screen instead of vertically placed.
The Bus Node button is used when busbar representation of the bus is not desired. The bus
node has a number of "ports" "stacked" in the center of the node. When connecting lines or
equipment to a bus node, the connection point will snap to the center.
The Branch button is used to create a line between two buses. When the branch item is
selected, the cursor changes to a crosshair. The branch is started by placing the cross-hair on
the FROM bus and clicking. Any number of intermediate kneepoints may then be created by
clicking on the way to the TO bus. Clicking on the TO bus will complete the creation of the
branch. At any point during the creation of the branch, the branch may be canceled and
removed by pressing the [Esc] key. The attachment point of a branch on a bus may be
changed by [Ctrl] clicking on the attachment point of the link and then moving it to another
port on the bus.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-117
The User Interface PSS™E-31.0
Toolbars Users Manual
The Load button is used to create a load on a bus. When the load item is selected, the cursor
changes to a crosshair. The load is started by placing the crosshair on the bus and pressing
the left mouse button. The mouse is then dragged to where the load symbol is to appear and
released.
The Generator button is used to create a generator on a bus. When the generator item is
selected, the cursor changes to a crosshair. The generator is started by placing the crosshair
on the bus and pressing the left mouse button. The mouse is then dragged to where the gen-
erator symbol is to appear and released.
The Switched Shunt button is used to create a switched shunt on a bus. When the switched
shunt item is selected, the cursor changes to a crosshair. The switched shunt is started by
placing the crosshair on the bus and pressing the left mouse button. The mouse is then
dragged to where the switched shunt symbol is to appear and released.
The Fixed Shunt button is used to create a fixed shunt on a bus. When the fixed shunt item is
selected, the cursor changes to a crosshair. The fixed shunt is started by placing the crosshair
on the bus and pressing the left mouse button. The mouse is then dragged to where the fixed
shunt symbol is to appear and released.
The FACTS Device button is used to create a FACTS device between two buses. The FACTS
device is started by selecting one or two buses. One bus is selected to create a shunt element
FACTS device. Two buses are selected to create a series element FACTS device. When the
FACTS device item is selected, the cursor changes to a crosshair. If a single bus was
selected, the FACTS device is started by placing the crosshair on the selected bus and
pressing the left mouse button. The mouse is then dragged to where the FACTS device is to
appear and released. If two buses were selected, the FACTS device is started by placing the
crosshair on the "sending bus" and clicking. Any number of intermediate kneepoints may then
be created by clicking on the way to the "terminal bus". Clicking on the "terminal bus" will com-
plete the creation of the FACTS device. At any point during the creation of the FACTS device,
the FACTS device may be canceled and removed by pressing the [Esc] key.
The Two-winding Transformer button is used to create a two-winding transformer between
two buses. The two-winding transformer is started by placing the crosshair on the FROM bus
and clicking. Any number of intermediate kneepoints may then be created by clicking on the
way to the TO bus. Clicking on the TO bus will complete the creation of the two-winding trans-
former. At any point during the creation of the two-winding transformer, the two-winding
transformer may be canceled and removed by pressing the [Esc] key. The attachment point of
a two-winding transformer on a bus may be changed by [Ctrl] clicking on the attachment point
of the two-winding transformer and then moving it to another port on the bus.
The Three-winding Transformer button is used to create a three-winding transformer
between three buses. The three-winding transformer is created by first selecting three buses.
The three buses will be regarded as the FROM, TO, and last bus in the order they were ini-
tially selected. The three-winding transformer item is then selected, the cursor placed in the
Diagram View at the desired location for the symbol to be placed, and the left mouse button
clicked. Any number of intermediate kneepoints may be added to the links between the
symbol and the three buses, or the attachment points modified in the manner described
above.
2-118 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Toolbars
The Two-terminal dc Line button is used to create a two-terminal dc line between two buses.
When the dc line item is selected, the cursor changes to a crosshair. The dc line is started by
placing the crosshair on the FROM bus and clicking. Any number of intermediate kneepoints
may then be created by clicking on the way to the TO bus. Clicking on the TO bus will com-
plete creation of the dc line. At any point during the creation of the dc line, the dc line may be
canceled and removed by pressing the [Esc] key. The attachment point of a link on a bus may
be changed by [Ctrl] clicking on the attachment point of the link and then moving it to another
port on the bus.
The VSC dc Line button is used to create a VSC dc line between two buses. When the VSC
dc line item is selected, the cursor changes to a crosshair. The VSC dc line is started by
placing the crosshair on the FROM bus and clicking. Any number of intermediate kneepoints
may then be created by clicking on the way to the TO bus. Clicking on the TO bus will com-
plete creation of the VSC dc line. At any point during the creation of the VSC dc line, the VSC
dc line may be canceled and removed by pressing the [Esc] key. The attachment point of a
link on a bus may be changed by [Ctrl] clicking on the attachment point of the link and then
moving it to another port on the bus.
2.19.8.3 Diagram Toolbar Buttons for Adding Annotation to the Diagram View
The Annotation Text button is used to place annotation text anywhere on the Diagram View.
The annotation text item is selected and text can then be placed anywhere in the Diagram
View by clicking at the location to display the text annotation.
The Title button is used to place a title on the Diagram View. The title item displays the two-
line diagram title as well as the time and date of the last diagram update on the third line. The
time and date is updated on the title item whenever a solution is run and the diagram is open
in the application. The title item is selected and titles can then be placed anywhere in the Dia-
gram View by clicking on the location where the title is to be placed.
The Legend button is used to place a legend on the Diagram View. The legend item displays
the two-line diagram legend. The legend item is selected and legends can then be placed any-
where in the Diagram View by clicking at the location where the legend is to be displayed.
The Files button is used to place a Diagram File Block on the Diagram View. The Diagram File
Block contains the current case filename and the current Diagram filename. The files item is
selected and file blocks can then be placed anywhere in the Diagram View by clicking the
location where the file block is to be displayed.
The Summation button is used to place a summation record on the Diagram View. The sum-
mation item is selected and summations can then be placed anywhere in the Diagram View by
clicking. As each summation is placed, the Edit Summation dialog is displayed that allows the
setting of the summation records (see Section 2.19.8.4).
The Summation button shown above in Section 2.19.8.3 is used to open the dialog shown in
Figure 2-126. The user can supply a title line for the summation, as shown, and then select a variety
of system results to sum. These can be generator output and line flows for example. The example
show in Figure 2-126 sums the difference between generator output at bus 101 and the flow on cir-
cuit 1 of the line from bus 151 to 201.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-119
The User Interface PSS™E-31.0
Toolbars Users Manual
The "Title" and the value of the summation will be placed in the Diagram View at the point selected
by the user. Subsequently, it can be edited and/or moved to a different location.
• Initializing a summing variable; usually, the initial value of the summing variable is zero,
but a nonzero value may be specified.
• Specifying individual ac branches, generator buses, and/or load buses whose active
power components of line flow, generation, and load, respectively, are added to or sub-
tracted from the summing variable.
• Specifying a character string to be printed in front of the calculated value of the sum-
ming variable anywhere on the one-line diagram.
2-120 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Toolbars
O Is a valid option (blank, or "1" through "8"; blank and "1" are equivalent); see
below.
text Is the character string to be displayed in front of the summing variable's value. It
must be enclosed in single quotes and is limited to 40 characters.
X,Y Is the (x,y) coordinate of the first character of the text string, specified in inches.
TSIZ Is the character height specified in inches. TSIZ must be between 0.05 and
1.5 in.
TANG Is the angle of rotation of the character string, specified in degrees between 0
and 360; 0 degrees is the angle at which the title lines are written on the
diagram.
CNST Is the initial value to be assigned to the summing variable. The default value is
zero.
The option field is used to designate a line width, pen number, or color for the drawing of the text.
It is the user's responsibility to ensure that the designated number is appropriate for the graphics
output device being used (e.g., "6" would be invalid for a pen plotter with only four pens). If the
numeric option is invalid, a device dependent default is used.
The summation record in the summation block structure may be followed by summation participa-
tion records. These define the generator buses, load buses, and ac branches whose active power
components are to be included in the summation. The summation participation records may be
entered in any order and are of the following forms:
O Is a valid option (blank, "+" or "-"). Blank or "+" indicates that the active power of
the corresponding network element is to be added to the summing variable; "-"
indicates that it is to be subtracted from the summing variable.
IB Is a bus identifier.
IFR Is the "from bus" identifier.
ITO Is the "to bus" identifier.
ICKT Is the circuit or multisection line grouping identifier; default value is '1'.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-121
The User Interface PSS™E-31.0
Toolbars Users Manual
DIR Is either ’F’ or ’T’ and indicates flow direction. Line flow is always calculated at the
bus IFR end of the line; if DIR is ’F’, flow is in the bus IFR "to bus" ITO direction,
and if it is ’T’, flow is in the bus ITO "to bus" IFR direction. DIR is ’F’ by default.
Solve.
Perform a PV analysis.
Perform a QV analysis.
2-122 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Toolbars
Solve OPF.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-123
The User Interface PSS™E-31.0
Toolbars Users Manual
Refresh contours.
Remove contours.
2-124 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Toolbars
Clear a fault.
Trip a line.
Close a line.
Disconnect a bus.
Disconnect a machine.
The line primitive button is used to place annotation lines anywhere on the Diagram View.
The line primitive item is selected and lines can then be placed anywhere in the Diagram View
by clicking. Be aware, they are not branches!
The arc primitive button is used to place annotation arcs anywhere on the Diagram View. The
arc primitive item is selected and arcs can then be placed anywhere in the Diagram View by
clicking.
The circle primitive button is used to place annotation circles anywhere on the Diagram
View. The circle primitive item is selected and circles can then be placed anywhere in the Dia-
gram View by clicking.
The ellipse primitive item is used to place annotation ellipses anywhere on the Diagram
View. The ellipse primitive item is selected and ellipses can then be placed anywhere in the
Diagram View by clicking.
The rectangle primitive button is used to place annotation rectangles anywhere on the Dia-
gram View. The rectangle primitive item is selected and rectangles can then be placed
anywhere in the Diagram View by clicking.
The region primitive button is used to place annotation regions anywhere on the Diagram
View. The region primitive item is selected and multi-segment polygon regions can then be
placed anywhere in the Diagram View by clicking the end point for each edge of the polygon.
The region is complete when the last point clicked is on the first point.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-125
The User Interface PSS™E-31.0
Status Bar Users Manual
2-126 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Program Automation
More sophisticated control is available through operation of programs created with the IPLAN or
Python programming language. Such programs control operation of PSS™E in a manner which
enables not only basic program operations but also examination of data and results which can lead
to subsequent operation of PSS™E based on looping through repetitive processes or boolean/log-
ical decisions. Custom made reporting formats can be established. An IPLAN file has the extension
"irf". A Python file has the extension "py".
For details on the IPLAN programming language, the IPLAN language interface to the PSS™E
working case and dynamics data, and the IPLAN compiler, refer to the IPLAN Program Manual.
For details on the Python programming language, refer to one of the widely available resource
books or on the web at http://www.python.org.
Figure 2-127. Menu and Toolbar Button for Running Automation Files
Selecting from the I/O Control>Run program Automation file… option or the Run Automation
File toolbar button will open the Select Program Automation File dialog (see Figure 2-128). The
drop-down menu provides access to a Response file, an IPLAN or a Python file. When the selected
file is opened, the processes packaged in the Response file or programmed into the IPLAN or
Python file will be initiated.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-127
The User Interface PSS™E-31.0
Program Automation Users Manual
Selecting the Start recording… option displays the Select Program Automation File dialog where
the user selects a file in which the response file elements will be recorded (see Figure 2-130).
2-128 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Program Automation
Having selected the file, the user now executes the required sequence of activities or operations
using the menu and toolbar facilities in the interface. The resulting response file will contain, in
Response File form, a series of commands reflecting the user’s sequence of activities. This file can
be opened when using the Run program Automation file… option described in Section 2.21.1.
The user can to tailor this basic Response File for subsequent runs by editing the created response
file by changing some of the filenames and bus numbers specifying faulted nodes, switched
branches, and so on.
As an example it can be assumed that, using the savnw.sav power flow case, the user wishes to
open one circuit between buses 151 and 152, solve the case and then output the power flow results
for bus 151.
• Right-click on the branch in the Diagram View and select Switch from the pop-up
menu.
• Employ the Power Flow>Solution>Solve option or the Solve toolbar button.
• Select the Bus Based Output toolbar button and, subsequently, bus number 151.
If this series of operations were recorded, a response file would be constructed (see Figure 2-131).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-129
The User Interface PSS™E-31.0
Program Automation Users Manual
It can be seen that the Response file contains PSS™E batch (BAT_) commands. Consequently,
the manual creation of a Response File, which could be done with the text editor, requires an inti-
mate familiarity with the PSS™E batch commands. These commands are covered in the PSS™E
API Manual.
Alternatively the user can create a Python file using the Python programming language. This will
facilitate a more sophisticated control of PSS™E by enabling looping and decision making based
on results of analyses. Standard concepts such as looping and subroutine calling are available. For
details on the Python programming language refer to a Python reference book or
http://www.python.org.
It is not possible to construct an IPLAN file using the PSS™E recording facility. The file must be
created manually and compiled. It is very beneficial to be familiar with at least one programming
language and the standard programming concepts such as assignment statements, looping and
subroutine calls.
For details on the IPLAN programming language, the IPLAN language interface to the PSS™E
working case and dynamics data, and the IPLAN compiler, refer to the IPLAN Program Manual.
2-130 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 The User Interface
Users Manual Running Command Line Interactive Sessions
Selection of the command line processor will open the Command Line Input dialog (see Figure 2-
133). The user input can be either by use of conventional activity names or by Python language
commands. Set the Command language drop-down menu in the upper right corner of the dialog to
the desired entry method.
An interactive session can be run by typing in activity names and responding to program responses
in the traditional manner. The user input must be in the Enter commands field. The program
responses will be seen in the Progress View area of the Command Line Input dialog.
The example shows that the commands are recorded and accessible in the Previous commands
drop-down menu. Selection of a previous command will result in its execution.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 2-131
The User Interface PSS™E-31.0
Running Command Line Interactive Sessions Users Manual
Closing this dialog will take the user back to the newly reactivated menus and toolbars.
2-132 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Chapter 3
Managing Power Flow Data
In addition to the basic data set describing the network elements, PSS™E requires other data and
control element files for specific applications. Those files and their data requirements will be
described in the subsections of Chapters 4 through 10, where they are appropriate.
Objectives of this chapter are to describe several aspects of data preparation, including:
• Specific network data required and their format for importation into PSS™E.
• Methods of importing data.
• Means by which data can be listed and examined.
• Methods to check data for errors and conflicts.
• Data editing.
• Data exportation.
• Building a network using the Diagram View.
• Building a network using the Spreadsheet View.
The user should be aware that not all the data described in this chapter are needed for all applica-
tions and that some data can be defaulted. The following subsection will indicate which data fall into
those categories.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-1
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
Case Identification
Bus Data
Load Data
Generator Data
Transformer Data
Zone Data
Owner Data
3-2 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
The bulk power flow data input facility, File>Open… (Section 2.6.2) imports hand-typed power flow
source data from a correctly formatted Power Flow Raw Data File (.raw) and enters it into the load
flow working case, rearranging it from its original format into a computationally oriented data struc-
ture in the process.
All data is read in "free format" with data items separated by a comma or one or more blanks.
Tabbed delimited data items are not recommended. The File>Open… command may also import
binary saved case files (*.sav) containing power flow data as well as solution values and related
options (see Section 1.7.2).
The following sections identify the power flow data categories in the order of presentation expected
in the Power Flow Raw Data File.
IC, SBASE
where:
IC Change code:
0 - base case (i.e., clear the working case before adding data to it)
1 - add data to the working case
IC = 0 by default.
SBASE System base MVA. SBASE = 100.0 by default.
The next two records each contain a line of heading to be associated with the case. Each line may
contain up to 60 characters.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-3
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
I, 'NAME', BASKV, IDE, GL, BL, AREA, ZONE, VM, VA, OWNER
where:
VM and VA could be set to values obtained from a previously solved case if they were available.
Normally, however, they can be set to default value.
When entering bus data in the Power Flow Raw Data File, bus data input is terminated with a record
specifying a bus number of zero.
3-4 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
When the "Extended Name" bus input option is enabled in the Misc>Change Program Settings
(OPTN)… dialog, data fields designating buses on load, generator, branch, transformer, area, two-
terminal dc line, VSC dc line, switched shunt, multi-terminal dc line, multisection line, and FACTS
device data records may be specified as either extended bus names enclosed in single quotes or
as bus numbers.
As for data output, reports developed by PSS™E functions can be ordered in ascending bus
number or by the buses extended bus name, in alphabetical order. The setting of bus output to
either bus number or extended name is made using the Misc>Change Program Settings
(OPTN)… option (see Section 1.6.4).
2. The twelve-character bus name, including any trailing blanks, must be the first twelve
characters.
3. The bus base voltage in kV must immediately follow the bus name. Up to six characters
may be used.
4. For those data fields whose sign is used to indicate a modeling attribute, a minus sign
may be specified between the leading single quote and the first character of the twelve-
character bus name.
As an example, consider a 345 kV bus with the name FRONT-STREET. Its extended bus name
would be:
’FRONT-STREET 345’
99,,345, 1,,,,3
If, in addition, you name the bus ERIE BLVD and it has a 200 Mvar shunt reactor, the minimum data
line would be:
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-5
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
I, ID, STATUS, AREA, ZONE, PL, QL, IP, IQ, YP, YQ, OWNER
where:
3-6 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
OWNER Owner to which the load is assigned (1 through the maximum number of owners
at the current size level, see Table 1-1). By default, OWNER is the owner to
which bus "I" is assigned (see Section 3.2.2).
As for buses, it is possible to enter only the data items which apply to the analyses to be undertaken.
An example entry in the Power Flow Raw Data File for a constant MVA load of 100 MW and 50
Mvar, at bus 123, with no assigned area, zone or owner, would be:
123, ’1’,,,,100,50
Within the Raw Data File, load data input is terminated by a record specifying a bus number of zero.
Voltage
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-7
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
The constant current characteristic holds the load current constant as long as the bus voltage
exceeds 0.5 pu, and assumes an elliptical current-voltage characteristic as shown in Figure 3-3 for
voltages below 0.5 pu.
Further details on load characteristic and modeling requirements are given in Section 4.5.
1.1
Current
1.0
Power
0.5
0.0
In particular, each bus specified in the bus data input with a type code of two (2) or three (3) must
have a generator data record entered for it.
3-8 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
Each generator has a single line data record with the following format:
I, ID, PG, QG, QT, QB, VS, IREG, MBASE, ZR, ZX, RT, XT, GTAP, STAT,
RMPCT, PT, PB, O1, F1, ....O4, F4
where:
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-9
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
RMPCT Percent of the total Mvar required to hold the voltage at the bus controlled by this
bus "I" that are to be contributed by the generation at bus "I"; RMPCT must be
positive. RMPCT is needed if IREG specifies a valid remote bus and there is
more than one local or remote voltage controlling device (plant, switched shunt,
FACTS device shunt element, or VSC dc line converter) controlling the voltage
at bus IREG to a setpoint. RMPCT is needed also if bus "I" itself is being con-
trolled locally or remotely by one or more other setpoint mode voltage controlling
devices. RMPCT = 100.0 by default.
PT Maximum generator active power output; entered in MW. PT = 9999.0 by
default.
PB Minimum generator active power output; entered in MW. PB = -9999.0 by
default.
Oi Owner number; (1 through the maximum number of owners at the current size
level: see Table 1-1). Each machine may have up to four owners. By default, O1
is the owner to which bus "I" is assigned and O2, O3, and O4 are zero.
Fi Fraction of total ownership assigned to owner Oi; each Fi must be positive. The
Fi values are normalized such that they sum to 1.0 before they are placed in the
working case. By default, each Fi is 1.0.
In specifying reactive power limits for voltage controlling plants (i.e., those with unequal reactive
power limits), the use of very narrow var limit bands is discouraged. The Newton-Raphson solutions
require that the difference between the controlling equipment’s high and low reactive power limits
be greater than 0.002 pu for all setpoint mode voltage controlling equipment (0.2 Mvar on a 100
MVA system base). It is recommended that voltage controlling plants have Mvar ranges substan-
tially wider than this minimum permissible range.
As with other data sets, some of the generator data have default values and, further, it is not nec-
essary to specify all the data for basic power flow studies.
If an implicit transformer model is used, the minimum data set needed is:
3-10 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
In Figure 3-5, there is an additional bus to represent the generator terminal. This is the Type 2 bus
where the generator will regulate/control voltage unless the user specifies otherwise.
Multiple Generators
If a generating plant has several units, they can be represented separately even if they are con-
nected to the same Type 2 bus.
Figure 3-6 shows three Type 2 buses, each having two connected units. For generators 1 through
4, the GSU is explicitly represented while for generators 5 and 6 the GSU is implicitly represented.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-11
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
To clarify the data requirements, Figure 3-7 shows a properly formatted listing for the generators in
Figure 3-6.
The separate transformer branches from Buses 1238 and 1239 to Bus 1237 are not included
in this generator list.
Figure 3-7. Data Set for the Multiple Generators in Figure 3-6
Generator data input from a Power Flow Raw Data File is terminated with a record specifying
a bus number of zero.
3-12 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
To represent shunts connected to buses, that shunt data should be entered in the bus data
record.
I,J,CKT,R,X,B,RATEA,RATEB,RATEC,GI,BI,GJ,BJ,ST,LEN,O1,F1,...,O4,F4
where:
I Branch "from bus" number, or extended bus name enclosed in single quotes
(see Section 3.2.2.1).
J Branch "to bus" number, or extended bus name enclosed in single quotes (see
Section 3.2.2.1). "J" is entered as a negative number, or with a minus sign
before the first character of the extended bus name, to designate it as the
metered end; otherwise, bus "I" is assumed to be the metered end.
CKT One- or two-character uppercase nonblank alphanumeric branch circuit identi-
fier; the first character of CKT must not be an ampersand "&" (see
Section 3.4.4.12 for a discussion on use of the ampersand in designation of mul-
tisection transmission lines). It is recommended that single circuit branches be
designated as having the circuit identifier ’1’. CKT = ’1’ by default.
R Branch resistance; entered in pu. A value of R must be entered for each branch.
X Branch reactance; entered in pu. A nonzero value of X must be entered for each
branch. See Section 3.2.5.1 for a discussion of the treatment of branches as
zero impedance lines.
B Total branch charging susceptance; entered in pu. B = 0.0 by default.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-13
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
RATEA First loading rating; entered in MVA. If RATEA is set to 0.0, the default value, this
branch will not be included in any examination of circuit loading (see
Section 4.4.5.1.1).
RATEB Second loading rating; entered in MVA. RATEB = 0.0 by default.
RATEC Third loading rating; entered in MVA. RATEC = 0.0 by default.
Ratings are entered as:
When specifying a nontransformer branch between buses "I" and "J" with circuit identifier CKT, if a
two-winding transformer between buses "I" and "J" with a circuit identifier of CKT is already present
in the working case, it is replaced (i.e., the transformer is deleted from the working case and the
newly specified branch is then added to the working case).
Branches to be modeled as transformers are not specified in this data category; rather, they
are specified in the transformer data category described in the following Section 3.2.6.
Nontransformer branch data input to the Power Flow Raw Data File is terminated with a record
specifying a "from bus" number of zero.
3-14 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
During network solutions, buses connected by such lines are treated as the same bus, thus having
identical bus voltages. At the completion of each solution, the loadings on zero impedance lines are
determined.
When obtaining power flow solutions, zero impedance line flows, as calculated at the end of the
solution, are preserved with the power flow case and are available to the power flow solution pro-
cedures. Similarly, in unbalanced fault calculations, the positive, negative, and zero sequence
branch currents on zero impedance lines are determined and preserved, and are subsequently
available to be reported. In other applications such automatic contingency analysis, short-circuit
scanning and in linearized network analyses, zero impedance line results are calculated and
reported as needed.
The zero impedance line threshold tolerance, THRSHZ, may be changed by launching the Solution
Parameters dialog (see Figure 4-22) from the Power Flow>Solution>Parameters option under
the General tab. Setting THRSHZ to zero disables zero impedance line modeling, and all branches
are represented with their specified impedances.
A zero impedance line may not have a transformer in parallel with it. Although not required, it is
recommended that no other in-service lines exist in parallel with a zero impedance line.
A zero impedance line may have nonzero values of line charging and/or line connected shunts. This
allows, for example, a low impedance cable to be modeled as a zero impedance line.
While more than two buses may be connected together by zero impedance lines, buses may not
be connected in a loop arrangement by zero impedance lines. For example, connecting bus 1 to
bus 2 and bus 2 to bus 3 by zero impedance lines is allowed; adding a third zero impedance line
connecting buses 1 and 3 would form a zero impedance line connected loop and is not allowed.
It is important to note that buses connected together by zero impedance lines are treated as a single
bus by the power flow solution activities. Hence, equipment controlling the voltages of multiple
buses within a zero impedance connected group of buses must have coordinated voltage
schedules.
With large databases it is important to have the ability to easily identify which bus voltages are being
regulated and which equipment is controlling the regulation. This helps to avoid situations in which
there are potential regulation conflicts. Clicking the Regulated buses tab in the Power
Flow>Reports>Limit checking reports… dialog, will facilitate generation of a report that tabulates
those buses whose voltages are controlled by generation, switched shunts, voltage controlling
transformers, FACTS devices, and/or VSC dc line converters.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-15
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
Similarly, if multiple voltage controlling devices are present within a group of buses connected
together by zero impedance lines, the power flow solution activities handle the boundary condition
as if they are all connected to the same bus.
In the fault analysis activities, a branch treated as a zero impedance line in the positive sequence
is treated in the same manner in the zero sequence, regardless of its zero sequence branch imped-
ance. Zero sequence mutual couplings involving a zero impedance line are ignored in the fault
analysis solution activities.
That exception is a set of ancillary data, comprising transformer impedance correction tables, which
define the manner in which transformer impedance changes as off-nominal turns ratio or phase shift
angle is adjusted. Those data records are described in Section 3.2.12.
Both two-winding and three-winding transformers are specified in transformer data record blocks.
Two-winding transformers require a block of four data records. Three-winding transformers require
five data records.
The data records for the two-winding transformer are common to the three-winding transformer.
Figure 3-9 shows the transformer winding configurations.
3-16 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
The five record transformer data block for three-winding transformers has the following format:
I,J,K,CKT,CW,CZ,CM,MAG1,MAG2,NMETR,’NAME’,STAT,O1,F1,...,O4,F4
R1-2,X1-2,SBASE1-2,R2-3,X2-3,SBASE2-3,R3-1,X3-1,SBASE3-1,VMSTAR,ANSTAR
WINDV1,NOMV1,ANG1,RATA1,RATB1,RATC1,COD1,CONT1,RMA1,RMI1,VMA1,VMI1,NTP1,TAB1,CR1,CX1
WINDV2,NOMV2,ANG2,RATA2,RATB2,RATC2,COD2,CONT2,RMA2,RMI2,VMA2,VMI2,NTP2,TAB2,CR2,CX2
WINDV3,NOMV3,ANG3,RATA3,RATB3,RATC3,COD3,CONT3,RMA3,RMI3,VMA3,VMI3,NTP3,TAB3,CR3,CX3
The four-record transformer data block for two-winding transformers is a subset of the data required
for three-winding transformers and has the following format:
I,J,K,CKT,CW,CZ,CM,MAG1,MAG2,NMETR,’NAME’,STAT,O1,F1,...,O4,F4
R1-2,X1-2,SBASE1-2
WINDV1,NOMV1,ANG1,RATA1,RATB1,RATC1,COD1,CONT1,RMA1,RMI1,VMA1,VMI1,NTP1,TAB1,CR1,CX1
WINDV2,NOMV2
The three-winding transformer model in PSS™E is in fact a grouping of three two-winding trans-
formers models where each of these two-winding transformers models one of the windings. While
most of the three-winding transformer data is stored in the two-winding transformer data arrays, it
is accessible for reporting and modification only as three-winding transformer data.
Record 1
I,J,K,CKT,CW,CZ,CM,MAG1,MAG2,NMETR,’NAME’,STAT,O1,F1,...,O4,F4
I The bus number, or extended bus name enclosed in single quotes, of the bus to
which the first winding is connected. The transformer’s magnetizing admittance
is modeled on winding one. The first winding is the only winding of a two-winding
transformer whose tap ratio or phase shift angle may be adjusted by the power
flow solution activities; any winding(s) of a three-winding transformer may be
adjusted. No default is allowed.
J The bus number, or extended bus name enclosed in single quotes, of the bus to
which the second winding is connected. No default is allowed for "J".
K The bus number, or extended bus name enclosed in single quotes, of the bus to
which the third winding is connected. Zero is used to indicate that no third
winding is present (i.e., that a two-winding rather than a three-winding trans-
former is being specified). This winding may have a fixed, off-nominal tap ratio
assigned to it. K = 0 by default.
CKT One- or two-character uppercase nonblank alphanumeric transformer circuit
identifier; the first character of CKT must not be an ampersand ("&") (see
Section 3.4.4.12). CKT = ’1’ by default.
CW The winding data I/O code which defines the units in which the turns ratios
WINDV1, WINDV2 and WINDV3 are specified (the units of RMAi and RMIi are
also governed by CW when |CODi| is 1 or 2): 1 for off-nominal turns ratio in pu of
winding bus base voltage; 2 for winding voltage in kV; 3 for off-nominal turns
ratio in pu of nominal winding voltage, NOMV1, NOMV2 and NOMV3. CW = 1 by
default.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-17
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
CZ The impedance data I/O code that defines the units in which the winding imped-
ances R1-2, X1-2, R2-3, X2-3, R3-1 and X3-1 are specified: 1 for resistance and
reactance in pu on system base quantities; 2 for resistance and reactance in pu
on a specified base MVA and winding bus base voltage; 3 for transformer three
phase load loss in watts and impedance magnitude in pu on a specified base
MVA and winding bus base voltage. CZ = 1 by default.
CM The magnetizing admittance I/O code that defines the units in which MAG1 and
MAG2 are specified: 1 for complex admittance in pu on system base quantities;
2 for three phase no-load loss in watts and exciting current in pu on winding one
to two base MVA and nominal voltage. CM = 1 by default.
MAG1, MAG2 The magnetizing conductance and susceptance, respectively, in pu on system
base quantities when CM is 1; MAG1 is the three phase no-load loss in watts
and MAG2 is the exciting current in pu on winding one to two base MVA
(SBASE1-2) and nominal voltage (NOMV1) when CM is 2. MAG1 = 0.0 and
MAG2 = 0.0 by default.
NMETR The nonmetered end code of either 1 (for the winding one bus) or 2 (for the
winding two bus). In addition, for a three-winding transformer, 3 (for the winding
three bus) is a valid specification of NMETR. NMETR = 2 by default.
NAME An alphanumeric identifier assigned to the transformer. The name may be up to
twelve characters and must be enclosed in single quotes. NAME may contain
any combination of blanks, uppercase letters, numbers and special characters.
NAME is twelve blanks by default.
STAT The initial transformer status, where 1 designates in-service and 0 designates
out-of-service. In addition, for a three-winding transformer, 2 designates that
only winding two is out-of-service, 3 indicates that only winding three is out-of-
service, and 4 indicates that only winding one is out-of-service, with the
remaining windings in-service. STAT = 1 by default.
Oi An owner number; (1 through the maximum number of owners at the current
size level: see Table 1-1). Each transformer may have up to four owners. By
default, O1 is the owner to which bus "I" is assigned and O2, O3, and O4 are
zero.
Fi The fraction of total ownership assigned to owner Oi; each Fi must be positive.
The Fi values are normalized such that they sum to 1.0 before they are placed in
the working case. By default, each Fi is 1.0.
3-18 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
Record 2
The first three data items described on the second record are used for both two- and three-winding
transformers; the remaining data items are used only for three-winding transformers:
R1-2,X1-2,SBASE1-2,R2-3,X2-3,SBASE2-3,R3-1,X3-1,SBASE3-1,VMSTAR,
ANSTAR
R1-2, X1-2 The measured impedance of the transformer between the buses to which its first
and second windings are connected. When CZ is 1, they are the resistance and
reactance, respectively, in pu on system base MVA and winding voltage base;
when CZ is 2, they are the resistance and reactance, respectively, in pu on
winding one to two base MVA (SBASE1-2) and winding voltage base; when CZ
is 3, R1-2 is the three phase load loss in watts, and X1-2 is the impedance mag-
nitude in pu on winding one to two base MVA (SBASE1-2) and winding voltage
base. R1-2 = 0.0 by default, but no default is allowed for X1-2.
SBASE1-2 The winding one to two base MVA of the transformer. SBASE1-2 = SBASE (the
system base MVA) by default.
R2-3, X2-3 The measured impedance of a three-winding transformer between the buses to
which its second and third windings are connected; ignored for a two-winding
transformer. When CZ is 1, they are the resistance and reactance, respectively,
in pu on system base MVA and winding voltage base; when CZ is 2, they are the
resistance and reactance, respectively, in pu on winding two to three base MVA
(SBASE2-3) and winding voltage base; when CZ is 3, R2-3 is the three phase
load loss in watts, and X2-3 is the impedance magnitude in pu on winding two to
three base MVA (SBASE2-3) and winding voltage base. R2-3 = 0.0 by default,
but no default is allowed for X2-3.
SBASE2-3 The winding two to three base MVA of a three-winding transformer; ignored for a
two-winding transformer. SBASE2-3 = SBASE (the system base MVA) by
default.
R3-1, X3-1 The measured impedance of a three-winding transformer between the buses to
which its third and first windings are connected; ignored for a two-winding trans-
former. When CZ is 1, they are the resistance and reactance, respectively, in pu
on system base MVA and winding voltage base; when CZ is 2, they are the
resistance and reactance, respectively, in pu on winding three to one base MVA
(SBASE3-1) and winding voltage base; when CZ is 3, R3-1 is the three phase
load loss in watts, and X3-1 is the impedance magnitude in pu on winding three
to one base MVA (SBASE3-1) and winding voltage base. R3-1 = 0.0 by default,
but no default is allowed for X3-1.
SBASE3-1 The winding three to one base MVA of a three-winding transformer; ignored for a
two-winding transformer. SBASE3-1 = SBASE (the system base MVA) by
default.
VMSTAR The voltage magnitude at the hidden star point bus; entered in pu.
VMSTAR = 1.0 by default.
ANSTAR The bus voltage phase angle at the hidden star point bus; entered in degrees.
ANSTAR = 0.0 by default.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-19
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
Record 3
All data items on the third record are processed for both two- and three-winding transformers.
WINDV1,NOMV1,ANG1,RATA1,RATB1,RATC1,COD1,CONT1,RMA1,RMI1,VMA1,
VMI1,NTP1,TAB1,CR1,CX1
WINDV1 The winding one off-nominal turns ratio in pu of winding one bus base voltage
when CW is 1; WINDV1 = 1.0 by default. WINDV1 is the actual winding one
voltage in kV when CW is 2; WINDV1 is equal to the base voltage of bus "I" by
default. WINDV is the winding one off-nominal turns ratio in pu of nominal
winding one voltage, NOMV1 when CW is 3; WINDV1 = 1.0 by default.
NOMV1 The nominal (rated) winding one voltage in kV, or zero to indicate that nominal
winding one voltage is to be taken as the base voltage of bus "I". NOMV1 is used
in converting magnetizing data between per unit admittance values and physical
units when CM is 2. NOMV1 is used in converting tap ratio data between values
in per unit of nominal winding one voltage and values in per unit of winding one
bus base voltage when CW is 3. NOMV1 = 0.0 by default.
ANG1 The winding one phase shift angle in degrees. ANG1 is positive when winding
two leads the winding one side (for a two-winding transformer), or when the "T"
(or star) point bus leads the winding one side (for a three-winding transformer).
ANG1 must be greater than -180.0 and less than or equal to +180.0. ANG1 = 0.0
by default.
RATA1, The first winding’s three ratings entered in MVA (not current expressed in MVA).
RATB1, RATA1 = 0.0, RATB1 = 0.0 and RATC1 = 0.0 (bypass flow limit check for this
RATC1 transformer winding) by default.
COD1 The transformer control mode for automatic adjustments of the winding one tap
or phase shift angle during power flow solutions: 0 for no control (fixed tap and
phase shift); ±1 for voltage control; ±2 for reactive power flow control; ±3 for
active power flow control; ±4 for control of a dc line quantity (+4 is valid only for
two-winding transformers). If the control mode is entered as a positive number,
automatic adjustment of this transformer winding is enabled when the corre-
sponding adjustment is activated during power flow solutions; a negative control
mode suppresses the automatic adjustment of this transformer winding. COD1 =
0 by default.
CONT1 The bus number, or extended bus name enclosed in single quotes, of the bus
whose voltage is to be controlled by the transformer turns ratio adjustment
option of the power flow solution activities when COD1 is 1. CONT1 should be
nonzero only for voltage controlling transformer windings.
CONT1 may specify a bus other than "I", "J", or "K"; in this case, the sign of
CONT1 defines the location of the controlled bus relative to the transformer
winding. If CONT1 is entered as a positive number, or a quoted extended bus
name, the ratio is adjusted as if bus CONT1 is on the winding two or winding
three side of the transformer; if CONT1 is entered as a negative number, or a
quoted extended bus name with a minus sign preceding the first character, the
ratio is adjusted as if bus |CONT1| is on the winding one side of the transformer.
CONT1 = 0 by default.
3-20 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
Record 4
The first two data items on the fourth record are read for both two- and three-winding transformers;
the remaining data items are used only for three-winding transformers.
WINDV2,NOMV2,ANG2,RATA2,RATB2,RATC2,COD2,CONT2,RMA2,RMI2,VMA2,
VMI2,NTP2,TAB2,CR2,CX2
WINDV2 The winding two off-nominal turns ratio in pu of winding two bus base voltage
when CW is 1; WINDV2 = 1.0 by default. WINDV2 is the actual winding two
voltage in kV when CW is 2; WINDV2 is equal to the base voltage of bus "J" by
default. WINDV2 is the winding two off-nominal turns ratio in pu of nominal
winding two voltage, NOMV2 when CW is 3; WINDV2 = 1.0 by default.
NOMV2 The nominal (rated) winding two voltage in kV, or zero to indicate that nominal
winding two voltage is to be taken as the base voltage of bus "J". NOMV2 is
used in converting tap ratio data between values in per unit of nominal winding
two voltage and values in per unit of winding two bus base voltage when CW is
3. NOMV2 = 0.0 by default.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-21
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
ANG2 The winding two phase shift angle in degrees; ignored for a two-winding trans-
former. ANG2 is positive when the "T" (or star) point bus leads the winding two
side. ANG2 must be greater than -180.0 and less than or equal to +180.0. ANG2
= 0.0 by default.
RATA2, The second winding’s three ratings entered in MVA (not current expressed in
RATB2, MVA); ignored for a two-winding transformer. RATA2 = 0.0, RATB2 = 0.0 and
RATC2 RATC2 = 0.0 (bypass flow limit check for this transformer winding) by default.
COD2 The transformer control mode for automatic adjustments of the winding two tap
or phase shift angle during power flow solutions: 0 for no control (fixed tap and
phase shift); ±1 for voltage control; ±2 for reactive power flow control; ±3 for
active power flow control. If the control mode is entered as a positive number,
automatic adjustment of this transformer winding is enabled when the corre-
sponding adjustment is activated during power flow solutions; a negative control
mode suppresses the automatic adjustment of this transformer winding. COD2 =
0 by default.
CONT2 The bus number, or extended bus name enclosed in single quotes, of the bus
whose voltage is to be controlled by the transformer turns ratio adjustment
option of the power flow solution activities when COD2 is 1. CONT2 should be
nonzero only for voltage controlling transformer windings.
CONT2 may specify a bus other than "I", "J", or "K"; in this case, the sign of
CONT2 defines the location of the controlled bus relative to the transformer
winding. If CONT2 is entered as a positive number, or a quoted extended bus
name, the ratio is adjusted as if bus CONT2 is on the winding one or winding
three side of the transformer; if CONT2 is entered as a negative number, or a
quoted extended bus name with a minus sign preceding the first character, the
ratio is adjusted as if bus |CONT2| is on the winding two side of the transformer.
CONT2 = 0 by default.
RMA2, RMI2 The upper and lower limits, respectively, of either:
• Off-nominal turns ratio in pu of winding two bus base voltage when |COD2|
is 1 or 2 and CW is 1; RMA2 = 1.1 and RMI2 = 0.9 by default.
• Actual winding two voltage in kV when |COD2| is 1 or 2 and CW is 2. No
default is allowed.
• Off-nominal turns ratio in pu of nominal winding two voltage (NOMV2) when
|COD2| is 1 or 2 and CW is 3; RMA2 = 1.1 and RMI2 = 0.9 by default.
• Phase shift angle in degrees when |COD2| is 3. No default is allowed.
• Not used when |COD2| is 0; RMA2 = 1.1 and RMI2 = 0.9 by default.
VMA2, VMI2 The upper and lower limits, respectively, of either:
• Voltage at the controlled bus (bus |CONT2|) in pu when |COD2| is 1.
VMA2 = 1.1 and VMI2 = 0.9 by default.
• Reactive power flow into the transformer at the winding two bus end in Mvar
when |COD2| is 2. No default is allowed.
• Active power flow into the transformer at the winding two bus end in MW
when |COD2| is 3. No default is allowed.
• Not used when |COD2| is 0; VMA2 = 1.1 and VMI2 = 0.9 by default.
NTP2 The number of tap positions available; used when COD2 is 1 or 2. NTP2 must
be between 2 and 9999. NTP2 = 33 by default.
3-22 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
Record 5
The fifth data record is specified only for three-winding transformers.
WINDV3,NOMV3,ANG3,RATA3,RATB3,RATC3,COD3,CONT3,RMA3,RMI3,VMA3,
VMI3,NTP3,TAB3,CR3,CX3
WINDV3 The winding three off-nominal turns ratio in pu of winding three bus base voltage
when CW is 1; WINDV3 = 1.0 by default. WINDV3 is the actual winding three
voltage in kV when CW is 2; WINDV3 is equal to the base voltage of bus K by
default.
NOMV3 The nominal (rated) winding three voltage in kV, or zero to indicate that nominal
winding three voltage is to be taken as the base voltage of bus K. NOMV3 is
used in converting tap ratio data between values in per unit of nominal winding
three voltage and values in per unit of winding three bus base voltage when CW
is 3. NOMV3 = 0.0 by default.
ANG3 The winding three phase shift angle in degrees. ANG3 is positive when the "T"
(or star) point bus leads the winding three side. ANG3 must be greater than -
180.0 and less than or equal to +180.0. ANG3 = 0.0 by default.
RATA3, The third winding’s three ratings entered in MVA (not current expressed in MVA).
RATB3, RATA3 = 0.0, RATB3 = 0.0 and RATC3 = 0.0 (bypass flow limit check for this
RATC3 transformer winding) by default.
COD3 The transformer control mode for automatic adjustments of the winding three tap
or phase shift angle during power flow solutions: 0 for no control (fixed tap and
phase shift); ±1 for voltage control; ±2 for reactive power flow control; ±3 for
active power flow control. If the control mode is entered as a positive number,
automatic adjustment of this transformer winding is enabled when the corre-
sponding adjustment is activated during power flow solutions; a negative control
mode suppresses the automatic adjustment of this transformer winding. COD3 =
0 by default.
CONT3 The bus number, or extended bus name enclosed in single quotes, of the bus
whose voltage is to be controlled by the transformer turns ratio adjustment
option of the power flow solution activities when COD3 is 1. CONT3 should be
nonzero only for voltage controlling transformer windings.
CONT3 may specify a bus other than "I", "J", or "K"; in this case, the sign of
CONT3 defines the location of the controlled bus relative to the transformer
winding. If CONT3 is entered as a positive number, or a quoted extended bus
name, the ratio is adjusted as if bus CONT3 is on the winding one or winding two
side of the transformer; if CONT3 is entered as a negative number, or a quoted
extended bus name with a minus sign preceding the first character, the ratio is
adjusted as if bus |CONT3| is on the winding three side of the transformer.
CONT3 = 0 by default.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-23
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
Transformer input in Raw Data File format is terminated with a record specifying a winding
one bus number of zero.
Notes
• When specifying a two-winding transformer between buses I and J with circuit identifier
CKT, if a nontransformer branch between buses I and J with a circuit identifier of CKT
is already present in the working case, it is replaced (i.e., the nontransformer branch is
deleted from the working case and the newly specified two-winding transformer is then
added to the working case).
• In deriving winding impedances, for three-winding transformers, from the measured
impedance data input values, one winding with a small or negative impedance may
result. It is possible to specify a set of measured impedances which themselves do not
individually appear to challenge the precision limits of typical power system calcula-
tions, but which result in one winding impedance of nearly (or identically) 0.0. Such
data could result in precision difficulties, and hence inaccurate results, when pro-
cessing the system matrices in power flow and short circuit calculations.
• Whenever a set of measured impedance results in a winding reactance which is iden-
tically 0.0, a warning message is printed by the three-winding transformer data input or
data changing function, and the winding’s reactance is set to the zero impedance line
3-24 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
threshold tolerance (or to 0.0001 pu if the zero impedance line threshold tolerance itself
is 0.0). Whenever a set of measured impedances results in a winding impedance
whose magnitude is less than 0.00001 pu, a warning message is printed. As with all
warning and error messages produced during data input and data modification phases
of PSS™E, the user should resolve the cause of the message (e.g., was correct input
data specified?) and use engineering judgement to resolve modeling issues (e.g., is
this the best way to model this transformer or would some other modeling be more
appropriate?).
Figure 3-11 shows the data records for a 300 MVA, 345/138/13.8 kV three-winding transformer
connected to system buses with nominal voltages of 345 kV, 138 kV and 13.8 kV, respectively, and
sample data on 100 MVA system base and winding base voltages of 345 kV, 138 kV and 13.8 kV.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-25
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
Adjustable tap
on winding 2
Adjustable tap
on winding 3
Designating buses to specific zones allows additional subdivision of the network to facilitate anal-
yses and documentation but PSS™E provides no analytical facility to schedule interchange
between zones.
Although areas cannot overlap other areas and zones cannot overlap other zones, areas and zones
can overlap each other.
3-26 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
Figure 3-12 shows a system subdivided into three areas and three zones, each with a unique name.
Notice the following:
• An area does not have to be contiguous. Area #1 covers two separate parts of the
network.
• Zone #1 lies entirely in Area #1.
• Zone #2 lies partly in Area #1 and partly in Area #4.
• Zone #3 lies partly in Area 4 and Area 2.
Each bus in the PSS™E working case may be designated as residing in an interchange area, for
purposes of both interchange control and selective output and other processing. When the inter-
change control option is enabled during a power flow solution, each interchange area for which an
area slack bus is specified has the active power output of its area slack bus modified such that the
desired net interchange for the area falls within a desired band.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-27
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
Area identifiers and interchange control parameters are specified in area interchange data records
which have the following format:
I Area number, (1 through the maximum number of areas at the current size level:
see Table 1-1).
ISW Bus number, or extended bus name enclosed in single quotes, of the area slack
bus for area interchange control. The bus must be a generator (type two) bus in
the specified area. Any area containing a system swing bus (type three) must
have either that swing bus or a bus number of zero specified for its area slack
bus number. Any area with an area slack bus number of zero is considered a
"floating area" by the area interchange control option of the power flow solution
activities. ISW = 0 by default.
PDES Desired net interchange leaving the area (export); entered in MW. In the power
flow solution process there are two options for handling the interchange. One
assumes that the interchange is exported only on tie lines out of the area. The
other assumes that the interchange is a combination of flow on the tie lines plus
any loads whose area assignment is different from the bus to which it is con-
nected. Thus the PDES must be specified such that is consistent with these two
options either of which will be selected at initiation of the power flow solution.
PDES = 0.0 by default.
PTOL Interchange tolerance bandwidth; entered in MW. PTOL = 10.0 by default.
ARNAME Alphanumeric identifier assigned to area I. The name may contain up to twelve
characters and must be enclosed in single quotes. ARNAME may be any combi-
nation of blanks, uppercase letters, numbers, and special characters. ARNAME
is set to twelve blanks by default.
Area interchange data input from the Power Flow Raw Data File is terminated with a record
specifying an area number of zero.
3-28 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
Data for each two-terminal dc transmission line are specified on three consecutive data records.
The three data records have the following formats.
Record 1
The first of the three dc line data records defines the following line quantities and control
parameters:
I,MDC,RDC,SETVL,VSCHD,VCMOD,RCOMP,DELTI,METER,DCVMIN,CCCITMX,
CCCACC
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-29
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
DELTI Margin entered in per unit of desired dc power or current. This is the fraction by
which the order is reduced when ALPHA is at its minimum and the inverter is
controlling the line current. DELTI = 0.0 by default.
METER Metered end code of either ’R’ (for rectifier) or ’I’ (for inverter). METER = ’I’ by
default.
DCVMIN Minimum compounded dc voltage; entered in kV. Only used in constant gamma
operation (i.e., when GAMMX = GAMMN) when TAPI is held constant and an ac
transformer tap is adjusted to control dc voltage (i.e., when IFI, ITI, and IDI
specify a two-winding transformer). DCVMIN = 0.0 by default.
CCCITMX Iteration limit for capacitor commutated two-terminal dc line Newton solution pro-
cedure. CCCITMX = 20 by default.
CCCACC Acceleration factor for capacitor commutated two-terminal dc line Newton solu-
tion procedure. CCCACC = 1.0 by default.
Record 2
The second of the three dc line data records defines rectifier end data quantities and control
parameters:
IPR,NBR,ALFMX,ALFMN,RCR,XCR,EBASR,TRR,TAPR,TMXR,TMNR,STPR,ICR,IFR,
ITR,IDR,XCAPR
IPR Rectifier converter bus number, or extended bus name enclosed in single
quotes. No default allowed.
NBR Number of bridges in series (rectifier). No default allowed.
ALFMX Nominal maximum rectifier firing angle; entered in degrees. No default allowed.
ALFMN Minimum steady-state rectifier firing angle; entered in degrees. No default
allowed.
RCR Rectifier commutating transformer resistance per bridge; entered in ohms. No
default allowed.
XCR Rectifier commutating transformer reactance per bridge; entered in ohms. No
default allowed.
EBASR Rectifier primary base ac voltage; entered in kV. No default allowed.
TRR Rectifier transformer ratio. TRR = 1.0 by default.
TAPR Rectifier tap setting. TAPR = 1.0 by default.
TMXR Maximum rectifier tap setting. TMXR = 1.5 by default.
TMNR Minimum rectifier tap setting. TMNR = 0.51 by default.
STPR Rectifier tap step; must be positive. STPR = 0.00625 by default.
ICR Rectifier firing angle measuring bus number, or extended bus name enclosed in
single quotes. The firing angle and angle limits used inside the dc model are
adjusted by the difference between the phase angles at this bus and the ac/dc
interface (i.e., the converter bus, IPR). ICR = 0 by default.
IFR Winding one side “from bus” number, or extended bus name enclosed in single
quotes, of a two-winding transformer. IFR = 0 by default.
ITR Winding two side “to bus" number, or extended bus name enclosed in single
quotes, of a two-winding transformer. ITR = 0 by default.
3-30 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
IDR Circuit identifier; the branch described by IFR, ITR, and IDR must have been
entered as a two-winding transformer; an ac transformer may control at most
only one dc converter. IDR = '1' by default.
If no branch is specified, TAPR is adjusted to keep alpha within limits; otherwise, TAPR is
held fixed and this transformer’s tap ratio is adjusted. The adjustment logic assumes that
the rectifier converter bus is on the winding two side of the transformer. The limits TMXR
and TMNR specified here are used; except for the transformer control mode flag (COD of
Section 3.2.6), the ac tap adjustment data is ignored.
XCAPR Commutating capacitor reactance magnitude per bridge; entered in ohms.
XCAPR = 0.0 by default.
Record 3
Data on the third of the three dc line data records contains the inverter quantities corresponding to
the rectifier quantities specified on the second record described above.
The significant difference is that the control angle ALFA for the rectifier is replaced by the control
angle GAMMA for the inverter.
IPI,NBI,GAMMX,GAMMN,RCI,XCI,EBASI,TRI,TAPI,TMXI,TMNI,STPI,ICI,IFI,
ITI,IDI,XCAPI
Dc line converter buses, IPR and IPI, may be type one, two, or three buses. Generators, loads, fixed
and switched shunt elements, other dc line converters, and FACTS device sending ends are per-
mitted at converter buses.
When either XCAPR > 0.0 or XCAPI > 0.0, the two-terminal dc line is treated as capacitor commu-
tated. Capacitor commutated two-terminal dc lines preclude the use of a remote ac transformer as
commutation transformer tap and remote commutation angle buses at either converter. Any data
provided in these fields are ignored for capacitor commutated two-terminal dc lines.
Further details on dc line modeling in power flow solutions are given in Section 4.3.5.
The dc line data input from a Power Flow Raw Data File is terminated with a record specifying
a dc line number of zero.
The first of the three VSC dc line data records defines line quantities and control parameters.
Record 1
'NAME', MDC, RDC, O1, F1, ... O4, F4
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-31
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
NAME The non-blank alphanumeric identifier assigned to this VSC dc line. Each VSC
dc line must have a unique NAME. The name may be up to twelve characters
and must be enclosed in single quotes. NAME may contain any combination of
blanks, uppercase letters, numbers and special characters. No default allowed.
MDC Control mode: 0 for out-of-service, 1 for in-service. MDC = 1 by default.
RDC The dc line resistance entered in ohms. RDC must be positive. No default
allowed.
Oi An owner number; (1 through the maximum number of owners at the current
size level: see Table 1-1). Each VSC dc line may have up to four owners. By
default, O1 is 1, and O2, O3 and O4 are zero.
Fi The fraction of total ownership assigned to owner Oi; each Fi must be positive.
The Fi values are normalized such that they sum to 1.0 before they are placed in
the working case. By default, each Fi is 1.0.
Records 2 and 3
The remaining two data records define the converter buses (converter 1 and converter 2), along
with their data quantities and control parameters.
IBUS,TYPE,MODE,DOCET,ACSET,ALOSS,BLOSS,MINOSS,SMAX,IMAX,PWF,MAXQ,
MINQ,
REMOT,RMPCT
IBUS Converter bus number, or extended bus name enclosed in single quotes. No
default allowed.
TYPE Code for the type of converter dc control: 0 for converter out-of-service, 1 for dc
voltage control, or 2 for MW control. When both converters are in-service,
exactly one converter of each VSC dc line must be TYPE 1. No default allowed.
MODE Converter ac control mode: 1 for ac voltage control or 2 for fixed ac power factor.
MODE = 1 by default.
DCSET Converter dc setpoint. For TYPE = 1, DCSET is the scheduled dc voltage on the
dc side of the converter bus; entered in kV. For TYPE = 2, DCSET is the power
demand, where a positive value specifies that the converter is feeding active
power into the ac network at bus IBUS, and a negative value specifies that the
converter is withdrawing active power from the ac network at bus IBUS; entered
in MW. No default allowed.
ACSET Converter ac setpoint. For MODE = 1, ACSET is the regulated ac voltage set-
point; entered in pu. For MODE = 2, ACSET is the power factor setpoint. ACSET
= 1.0 by default.
Aloss, Bloss Coefficients of the linear equation used to calculate converter losses:
KWconv loss = Aloss + Idc*Bloss
Aloss is entered in kW. Bloss is entered in kW/amp. Aloss = Bloss = 0.0 by default.
MINloss Minimum converter losses; entered in kW. MINloss = 0.0 by default.
SMAX Converter MVA rating; entered in MVA. SMAX = 0.0 to allow unlimited converter
MVA loading. SMAX = 0.0 by default.
3-32 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
IMAX Converter ac current rating; entered in amps. IMAX = 0.0 to allow unlimited con-
verter current loading. If a positive IMAX is specified, the base voltage assigned
to bus IBUS must be positive. IMAX = 0.0 by default.
PWF Power weighting factor fraction (0.0 < PWF < 1.0) used in reducing the active
power order and either the reactive power order (when MODE is 2) or the reac-
tive power limits (when MODE is 1) when the converter MVA or current rating is
violated. When PWF is 0.0, only the active power is reduced; when PWF is 1.0,
only the reactive power is reduced; otherwise, a weighted reduction of both
active and reactive power is applied. PWF = 1.0 by default.
MAXQ Reactive power upper limit; entered in Mvar. A positive value of reactive power
indicates reactive power flowing into the ac network from the converter; a nega-
tive value of reactive power indicates reactive power withdrawn from the ac
network. Not used if MODE = 2. MAXQ = 9999.0 by default.
MINQ Reactive power lower limit; entered in Mvar. A positive value of reactive power
indicates reactive power flowing into the ac network from the converter; a nega-
tive value of reactive power indicates reactive power withdrawn from the ac
network. Not used if MODE = 2. MINQ = -9999.0 by default.
REMOT Bus number, or extended bus name enclosed in single quotes, of a remote type
1 or 2 bus whose voltage is to be regulated by this converter to the value speci-
fied by ACSET. If bus REMOT is other than a type 1 or 2 bus, bus IBUS
regulates its own voltage to the value specified by ACSET. REMOT is entered
as zero if the converter is to regulate its own voltage. Not used if MODE = 2.
REMOT = 0 by default.
RMPCT Percent of the total Mvar required to hold the voltage at the bus controlled by bus
IBUS that are to be contributed by this VSC; RMPCT must be positive. RMPCT
is needed only if REMOT specifies a valid remote bus and there is more than
one local or remote voltage controlling device (plant, switched shunt, FACTS
device shunt element, or VSC dc line converter) controlling the voltage at bus
REMOT to a setpoint, or REMOT is zero but bus IBUS is the controlled bus,
local or remote, of one or more other setpoint mode voltage controlling devices.
Not used if MODE = 2. RMPCT = 100.0 by default.
VSC dc line data input within a Power Flow Raw Data File is terminated with a record speci-
fying a blank dc line name (’ ’) or a dc line name of ’0’ or zero.
• must be a type one or two bus. Generators, loads, fixed and switched shunt elements,
other dc line converters, and FACTS device sending ends are permitted at converter
buses.
• must not have the terminal end of a FACTS device connected to the same bus.
• must not be connected by a zero impedance line to another bus which violates any of
the above restrictions.
In specifying reactive power limits for converters which control ac voltage (i.e., those with unequal
reactive power limits whose MODE is 1), the use of very narrow var limit bands is discouraged. The
Newton-Raphson based power flow solutions require that the difference between the controlling
equipment's high and low reactive power limits be greater than 0.002 pu for all setpoint mode
voltage controlling equipment (0.2 Mvar on a 100 MVA system base). It is recommended that
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-33
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
voltage controlling VSC converters have Mvar ranges substantially wider than this minimum per-
missible range.
For interchange and loss assignment purposes, the dc voltage controlling converter is assumed to
be the non-metered end of each VSC dc line. As with other network branches, losses are assigned
to the subsystem of the non-metered end, and flows at the metered ends are used in interchange
calculations.
Further details on dc line modeling in power flow solutions are given in Section 4.3.5.
The switched shunt elements at a bus may consist entirely of blocks of shunt reactors (each Bi is a
negative quantity) or entirely of blocks of capacitor banks (each Bi is a positive quantity). Any bus
can have both switched capacitors and reactors.
Each network bus to be represented in PSS™E with switched shunt admittance devices must have
a switched shunt data record specified for it. The switched shunts are represented with up to eight
blocks of admittance, each one of which consists of up to nine steps of the specified block
admittance.
I, MODSW, VSWHI, VSWLO, SWREM, RMPCT, ’RMIDNT’, BINIT, N1, B1, N2,
B2, ... N8, B8
where:
3-34 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-35
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
BINIT Initial switched shunt admittance; entered in Mvar at unity voltage. BINIT = 0.0
by default.
Ni Number of steps for block i. The first zero value of Ni or Bi is interpreted as the
end of the switched shunt blocks for bus I. Ni = 0 by default.
Bi Admittance increment for each of Ni steps in block i; entered in Mvar at unity
voltage. Bi = 0.0 by default.
Switched shunt data input from a Power Flow Raw Data File is terminated with a record spec-
ifying a bus number of zero.
• BINIT needs to be set to its actual solved case value only when the network, as entered
into the working case, is to be considered solved as read in, or when the device is to
be treated as fixed (i.e., MODSW is set to zero or switched shunts are to be locked
during power flow solutions).
• The switched shunt elements at a bus may consist entirely of reactors (each Bi is a neg-
ative quantity) or entirely of capacitor banks (each Bi is a positive quantity). In these
cases, the shunt blocks are specified in the order in which they are switched on the bus.
• If the switched shunt devices at a bus are a mixture of reactors and capacitors, the
reactor blocks are specified first in the order in which they are switched on, followed by
the capacitor blocks in the order in which they are switched on.
• In specifying reactive power limits for setpoint mode voltage controlling switched
shunts (i.e., those with MODSW of 1 or 2), the use of a very narrow admittance range
is discouraged. The Newton-Raphson based power flow solutions require that the dif-
ference between the controlling equipment's high and low reactive power limits be
greater than 0.002 pu for all setpoint mode voltage controlling equipment (0.2 Mvar on
a 100 MVA system base). It is recommended that voltage controlling switched shunts
have admittance ranges substantially wider than this minimum permissible range.
• When MODSW is 3, 4 or 5, VSWLO and VSWHI define a restricted band of the con-
trolled device’s reactive power range. They are specified in pu of the total reactive
power range of the controlled device (i.e., the plant QMAX - QMIN when MODSW is 3,
MAXQ - MINQ of a VSC dc line converter when MODSW is 4, and ΣNiBi − ΣNjBj when
MODSW is 5, where "i" are those switched shunt blocks for which Bi is positive and "j"
are those for which Bi is negative). VSWLO must be greater than 0.0 and less than
VSWHI, and VSWHI must be less than 1.0. That is, the following relationship must be
honored:
0.0 < VSWLO < VSWHI < 1.0
• The reactive power band for switched shunt control is calculated by applying VSWLO
and VSWHI to the reactive power band extremes of the controlled plant or VSC con-
verter. For example, with MINQ of -50.0 and MAXQ of +50.0, if VSWLO is 0.2 and
VSWHI is 0.75, then the reactive power band defined by VSWLO and VSWHI is:
-50.0 + 0.2*(50.0 - (-50.0)) = -50.0 + 0.2*100.0 = -50.0 + 20.0 = -30.0 MVAr
through:
-50.0 + 0.75*(50.0 - (-50.0)) = -50.0 + 0.75*100.0 = -50.0 + 75.0 = +25.0 MVAr
3-36 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
• The switched shunt admittance is kept in the working case and reported in output tab-
ulations separately from the fixed bus shunts, which are input on the bus data record
(see Section 3.2.2).
• Details on the handling of switched shunts during power flow solutions are discussed
in Section 4.3.3.
• It is recommended that data records for switched shunts whose control mode is 5 (i.e.,
they control the setting of other switched shunts) be grouped together following all
other switched shunt data records. This practice will eliminate any warnings of no
switched shunt at the specified remote bus simply because the remote bus’ switched
shunt record has not as yet been read.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-37
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
The Ti values on a transformer impedance correction table record must all be either tap ratios or
phase shift angles. They must be entered in strictly ascending order; i.e., for each "i", Ti+1>Ti. Each
Fi entered must be greater than zero. On each record, at least 2 pairs of values must be specified
and up to 11 may be entered. For a graphical view of a correction table, see Figure 3-14.
The Ti values for tables that are a function of tap ratio (rather than phase shift angle) are in units of
the controlling winding’s off-nominal turns ratio in pu of the controlling winding’s bus base voltage.
Although a transformer winding is assigned to an impedance correction table, each table may be
shared among many transformer windings. If the first "T" in a table is less than 0.5 or the last "T"
entered is greater than 1.5, "T" is assumed to be the phase shift angle and the impedance of each
transformer winding assigned to the table is treated as a function of phase shift angle. Otherwise,
the impedances of the transformer windings assigned to the table are made sensitive to off-nominal
turns ratio.
The power flow case stores both a nominal and actual impedance for each transformer winding
impedance. The value of transformer impedance entered by the user is taken as the nominal value
of impedance. Each time the complex tap ratio of a transformer is changed, either automatically by
the power flow solution activities or manually by the user, and the transformer winding has been
assigned to an impedance correction table, actual transformer winding impedance is redetermined
if appropriate. First, the scaling factor is established from the appropriate table by linear interpola-
tion; then nominal impedance is multiplied by the scaling factor to determine actual impedance. An
appropriate message is printed any time the actual impedance is modified.
Transformer impedance correction data input from a Power Flow Raw Data File is terminated
with a record specifying a table number of zero.
3-38 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
• each converter
• each dc bus
• each dc link
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-39
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
Data Record 1
I, NCONV, NDCBS, NDCLN, MDC, VCONV, VCMOD, VCONVN
where:
Data Record 2
Data record 1 is followed by NCONV converter records of the following format:
IB,N,ANGMX,ANGMN,RC,XC,EBAS,TR,TAP,TPMX,TPMN,TSTP,SETVL,DCPF,MARG,
CNVCOD
where:
3-40 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
Data Record 3
Following are NDCBS records, one for each dc bus, with the following format:
IDC Dc bus number (1 to NDCBS). The dc buses are used internally within each
multi-terminal dc line and must be numbered 1 through NDCBS. No default
allowed.
IB Ac converter bus number, or extended bus name enclosed in single quotes, or
zero. Each converter station bus specified in a converter record must be speci-
fied as IB in exactly one dc bus record. Dc buses that are connected only to
other dc buses by dc links and not to any ac converter buses must have a zero
specified for IB. A dc bus specified as IDC2 on one or more other dc bus records
must have a zero specified for IB on its own dc bus record. IB = 0 by default.
IA Area number, (1 through the maximum number of areas at the current size level:
see Table 1-1). IA = 1 by default.
ZONE Zone number, (1 through the maximum number of zones at the current size
level: see Table 1-1). ZONE = 1 by default.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-41
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
NAME Alphanumeric identifier assigned to dc bus IDC. The name may be up to twelve
characters and must be enclosed in single quotes. NAME may contain any com-
bination of blanks, uppercase letters, numbers, and special characters. NAME is
twelve blanks by default.
IDC2 Second dc bus to which converter IB is connected, or zero if the converter is
connected directly to ground. For voltage controlling converters, this is the dc
bus with the lower dc voltage magnitude and SETVL specifies the voltage differ-
ence between buses IDC and IDC2. For rectifiers, dc buses should be specified
such that power flows from bus IDC2 to bus IDC. For inverters, dc buses should
be specified such that power flows from bus IDC to bus IDC2. IDC2 is ignored on
those dc bus records that have IB specified as zero. IDC2 = 0 by default.
RGRND Resistance to ground at dc bus "IDC"; entered in ohms. During solutions
RGRND is used only for those dc buses specified as IDC2 on other dc bus
records. RGRND = 0.0 by default.
OWNER Owner number, (1 through the maximum number of owners at the current size
level: see Table 1-1). OWNER = 1 by default.
Data Record 4
Following the above records are NDCLN records, one for each dc link, with the following format:
Multi-terminal dc line data input from a Power Flow Raw Data File is terminated with a record
specifying a dc line number of zero.
A multi-terminal layout is shown in Figure 3-15. There are 4 convertors, 5 dc buses and 4 dc links.
3-42 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-43
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
• All dc buses within a multi-terminal dc line must be reachable from any other point
within the subnetwork.
• The area number assigned to dc buses and the metered end designation of dc links
are used in calculating area interchange and assigning losses as well as in the inter-
change control option of the power flow solution activities. Similarly, the zone
assignment and metered end specification are used in Zonal reporting activities.
• Further details on dc line modeling in power flow solutions are given in Section 4.3.5.
A transmission line with several distinct sections can be represented as one multisection line group.
The DUMi values on each record define the branches connecting bus "I" to bus "J", and are entered
so as to trace the path from bus "I" to bus "J". Specifically, for a multisection line grouping consisting
of three line sections (and hence two dummy buses):
I D1 D2 J
C1 C2 C3
3-44 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
From To Circuit
I D1 C1
D1 D2 C2
D2 J C3
If this multisection line grouping is to be assigned the line identifier "&1", the corresponding multi-
section line grouping data record is given by:
I J &1 D1 D2
Multisection line grouping data input from a Power Flow Raw Data File is terminated with a
record specifying a "from bus" number of zero.
• Up to 10 line sections (and hence 9 dummy buses) may be defined in each multisection
line grouping. A branch may be a line section of at most one multisection line grouping.
• Each dummy bus must have exactly two branches connected to it, both of which must
be members of the same multisection line grouping. A multisection line dummy bus
may not be a converter bus of a dc transmission line. A FACTS control device may not
be connected to a multisection line dummy bus.
• The status of line sections and type codes of dummy buses are set such that the mul-
tisection line is treated as a single entity with regards to its service status.
• When the multisection line reporting option is enabled, several power flow reporting
activities, specifically bus related reports, do not tabulate conditions at multisection line
dummy buses. Accordingly, care must be taken in interpreting power flow output
reports when dummy buses are other than passive nodes (e.g., if load or generation is
present at a dummy bus).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-45
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
Zone identifiers are specified in zone data records with the following format:
I, 'ZONAME'
where:
I Zone number, (1 through the maximum number of zones at the current size
level: see Table 1-1).
ZONAME Alphanumeric identifier assigned to zone I. The name may contain up to twelve
characters and must be enclosed in single quotes. ZONAME may be any combi-
nation of blanks, uppercase letters, numbers, and special characters. ZONAME
is set to twelve blanks by default.
Zone data input from a Power Flow Raw Data File is terminated with a record specifying a
zone number of zero.
Scheduled active power transfers between pairs of areas are specified in interarea transfer data
records each of which has the following format:
ARFROM "From area" number (1 through the maximum number of areas at the current
size level: see Table 1-1).
ARTO "To area" number (1 through the maximum number of areas at the current size
level: see Table 1-1).
TRID Single-character (0 through 9 or A through Z) upper case interarea transfer iden-
tifier used to distinguish among multiple transfers between areas ARFROM and
ARTO. TRID = ’1’ by default.
PTRAN MW comprising this transfer. A positive PTRAN indicates that area ARFROM is
selling to area ARTO. PTRAN = 0.0 by default.
Following the completion of interarea transfer data input, PSS™E alarms any area for which at least
one interarea transfer is present and whose sum of transfers differs from its desired net inter-
change, PDES (see Section 3.2.8 for the definition of PDES).
Interarea transfer data input from a Power Flow Raw Data File is terminated with a record
specifying a "from area" number of zero.
3-46 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
Owner identifiers are specified in owner data records with the following format:
I, 'OWNAME'
where:
I Owner number, (1 through the maximum number of owners at the current size
level: see Table 1-1).
OWNAME Alphanumeric identifier assigned to owner I. The name may contain up to twelve
characters and must be enclosed in single quotes. OWNAME may be any com-
bination of blanks, uppercase letters, numbers, and special characters.
OWNAME is set to twelve blanks by default.
Owner data input from a Power Flow Raw Data File is terminated with a record specifying an
owner number of zero.
PSS™E facilitates these devices with one generic set of data records.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-47
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
N,I,J,MODE,PDES,QDES,VSET,SHMX,TRMX,VTMN,VTMX,VSMX,IMX,LINX,RMPCT,
OWNER,SET1,SET2,VSREF
where:
3-48 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Power Flow Data Categories
IMX Maximum series current, or zero for no series current limit; entered in MVA at
unity voltage. IMX = 0.0 by default.
LINX Reactance of the dummy series element used during model solution; entered in
pu. LINX = 0.05 by default.
RMPCT Percent of the total Mvar required to hold the voltage at bus I that are to be con-
tributed by the shunt element of this FACTS device; RMPCT must be positive.
RMPCT is needed only if there is more than one local or remote voltage control-
ling device (plant, switched shunt, FACTS device shunt element, or VSC dc line
converter) controlling the voltage at bus I to a setpoint. RMPCT = 100.0 by
default.
OWNER Owner number, (1 through the maximum number of owners at the current size
level: see Table 1-1). OWNER = 1 by default.
SET1,SET2 If MODE is 3, resistance and reactance respectively of the constant impedance,
entered in pu; if MODE is 4, the magnitude (in pu) and angle (in degrees) of the
constant series voltage with respect to the quantity indicated by VSREF; if
MODE is 7 or 8, the real (Vd) and imaginary (Vq) components (in pu) of the con-
stant series voltage with respect to the quantity indicated by VSREF; for other
values of MODE, SET1 and SET2 are read, but not saved or used during power
flow solutions. SET1 = 0.0 and SET2 = 0.0 by default.
VSREF Series voltage reference code to indicate the series voltage reference of SET1
and SET2 when MODE is 4, 7 or 8: 0 for sending end voltage, 1 for series cur-
rent. VSREF = 0 by default.
FACTS device data input from a Power Flow Raw Data File is terminated with a record spec-
ifying a FACTS device number of zero.
PSS™E’s FACTS device model contains a shunt element that is connected between the sending
end bus and ground, and a series element connected between the sending and terminal end buses.
A unified power flow controller (UPFC) has both the series and shunt elements active, and allows
for the exchange of active power between the two elements (i.e., TRMX is positive). A static syn-
chronous series compensator (SSSC) is modeled by setting both the maximum shunt current limit
(SHMX) and the maximum bridge active power transfer limit (TRMX) to zero (i.e., the shunt element
is disabled).
An Interline Power Flow Controller (IPFC) is modeled by using two consecutively numbered series
FACTS devices. The first of this pair must be assigned as the IPFC master device by setting its con-
trol mode to 5 or 7, and the second must be assigned as its companion IPFC slave device by setting
its control mode to 6 or 8. In an IPFC, both devices have a series element but no shunt element.
Therefore, both devices typically have SHMX set to zero, and VSET of both devices is ignored.
Conditions at the master device define the active power exchange between the two devices.
Figure 3-16 shows the PSS™E FACTS control device model with its various setpoints and limits.
Each FACTS sending end bus must be a type 1 or 2 bus, and each terminal end bus must be a type
1 bus. Refer to Section 4.3.4 for other topological restrictions and for details on the handling of
FACTS devices during the power flow solution activities.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-49
Managing Power Flow Data PSS™E-31.0
Power Flow Data Categories Users Manual
Bus I Bus J
VSMX
IMX
PDES
QDES
VSET VTMX
SHMX
VTMN
TRMX
3-50 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Importing Power Flow Data
This option will give access to the Open dialog where the available .raw files will be listed in the
user’s directory (see Figure 3-17). Clicking the Open button will initiate data import once the
required file has been selected. Prior to data import, the user will be given the option of using the
NAMES or NUMBERS option for importing data records. This selection will override the selection
made (see Section 1.7.10).
Figure 3-17. Open Dialog Showing Available Raw Data Files for Selection
During the processing of data records, the Output Bar will show a message each time a category
of data is imported. Additionally, the view of the populated spreadsheet will open to show the data
in the working case.
Generally, specifying a data record within the Power Flow Raw Data File with a ’Q’ in column one
is used to indicate that the end of all data records in the raw data file. This end of data input
indicator:
1. Is not permitted during the input of the case identification data records.
2. Is allowed when the first record of the four or five record block for a two- or three-
winding transformer are being processed but not on the subsequent records of such a
block.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-51
Managing Power Flow Data PSS™E-31.0
Importing Power Flow Data Users Manual
3. Is allowed when the first record of the three record block for a two-terminal dc transmis-
sion line is being processed but not on the second or third records of such a block.
4. Is allowed when the first record of the three record block for a VSC dc transmission line
is being processed but not on the second or third records of such a block.
5. Is permitted when the first of the series of data records defining a multi-terminal dc
transmission line is being processed but not on the remaining records of such a block.
The data processing may be terminated by entering the AB interrupt control code.
As each bus data record is read (i.e., a bus not previously read), it is assigned to a bus sequence
number which defines the location of data for the bus in the various bus data arrays. Bus sequence
numbers are assigned sequentially starting with 1 in the order in which bus data records are read.
Each bus for which a generator data record is read is assigned a plant sequence number, which
defines the location of its plant-related generator data in the plant data arrays. Within each plant’s
data, for each machine for which a generator data record is read, a machine sequence number is
assigned defining the location of its machine-specific data in the machine data arrays. Plant and
machine sequence numbers are assigned sequentially starting with 1 in the order in which
generator data records are read. It is permissible to enter a generator data record for a bus that was
assigned a type code of 1 or 4 during bus data input.
Each load introduced into PSS™E is assigned a load sequence number, which defines the location
of its data in the load data arrays. Load sequence numbers are assigned sequentially starting with
1 in the order in which load data records are read.
Each ac branch introduced into PSS™E is assigned a branch sequence number, which defines the
location of its data in the branch data arrays. Branch sequence numbers are assigned sequentially
starting with 1 in the order in which branch data and transformer data records are read.
New buses, loads, generators, branches, and transformers are treated in the same manner as in
base case data input. Bus sequence numbers, machine sequence numbers, and so on are
assigned starting with the next available location in the respective data arrays.
3-52 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Importing Power Flow Data
When entering data for an existing piece of equipment, complete data records must be
entered. If not, omitted data items will take on their default values rather than retaining their
previous values.
1. All buses and their connected equipment within a specified subsystem contained in the
Power Flow Raw Data File may be appended to the working case.
2. All branches in the Power Flow Raw Data File for which both buses are in the working
case and only one bus is within a specified subsystem (ties) may be appended to the
working case.
3. Any bus that is within a specified subsystem and connected to a bus that is not in the
working case may be identified as a boundary bus; the type code of each boundary bus
is changed to 5, 6, or 7 as appropriate. For more information see Chapter 9, where the
process of making network equivalents, along with the topic of boundary, buses is
discussed.
The process of adding complete subsystems to an existing working case is facilitated with the
File>Open menu when selecting the Power Flow Raw Data File, Options file type is selected (see
Figure 3-18).
When the file is opened another dialog will pop up with several options for reading the raw power
flow data (see Figure 3-19). Selecting the Subsystem option will read in the raw data as a complete
subsystem to the working case.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-53
Managing Power Flow Data PSS™E-31.0
Importing Power Flow Data Users Manual
Figure 3-19. Add Subsystem File Type in the Read Power Flow Raw Data
Dialog
3-54 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Importing Power Flow Data
For all record types, except the multisection line grouping data, when reading a data record corre-
sponding to an existing component, data items that are specified replace those contained in the
working case while data items omitted on the data record have their values unchanged in the
working case.
Data entry is performed as for a new case using the File>Open. The objective of changing data
rather than reading in new data, is signaled by selection of a Power Flow Data File, Options in the
Open dialog, followed by selecting the Change option in the Read Power Flow Raw Data dialog,
(see Figure 3-20).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-55
Managing Power Flow Data PSS™E-31.0
Importing Power Flow Data Users Manual
3-56 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Importing Power Flow Data
2. Enter the machine quantities MBASE, ZSORCE, XTRAN, and GENTAP into the
working case.
3. Apportion the total plant output and power limits, as contained in the working case,
among the machines at the plant.
The Machine Impedance Data File will comprise a series of records in the following format:
I, ID, FP, FQ, MBASE, ZR, ZX, RT, XT, GENTAP, STAT
where:
I Bus number. Bus I must reside in the working case with a generator table entry
assigned to it. No default is allowed.
ID One- or two-character machine identifier used to distinguish among multiple
machines at a plant (i.e., at a generator bus). ID = ’1’ by default.
FP,FQ Fractions of total plant active and reactive power output, respectively, to be
assigned to this machine. FP and FQ are 1.0 by default.
MBASE Total MVA base of the units represented by this machine; entered in MVA. This
quantity is not needed in normal power flow and equivalent construction work,
but is required for switching studies, fault analysis, and dynamic simulation.
MBASE = system base MVA by default.
ZR,ZX Complex machine impedance, ZSORCE; entered in pu on MBASE base. This
data is not needed in normal power flow and equivalent construction work, but is
required for switching studies, fault analysis, and dynamic simulation. For
dynamic simulation, this impedance must be set equal to the unsaturated sub-
transient impedance for those generators to be modeled by subtransient level
machine models, and to unsaturated transient impedance for those to be mod-
eled by classical or transient level models. ZR = 0.0 and ZX = 1.0 by default.
RT,XT Step-up transformer impedance, XTRAN; entered in pu on MBASE base.
XTRAN should be entered as zero if the step-up transformer is explicitly mod-
eled as a network branch and bus I is the terminal bus. RT+jXT = 0.0 by default.
GENTAP Step-up transformer off-nominal turns ratio; entered in pu. GENTAP is used only
if XTRAN is nonzero. GENTAP = 1.0 by default.
STAT Machine status; 1 for in-service and zero for out-of-service. STAT = 1 by default.
Data records may be input in any order. Input is terminated with a record specifying an "I"
value of zero.
Data entry uses the File>Open option. In the Open dialog, a Machine Impedance Data File will be
selected, (see Figure 3-21).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-57
Managing Power Flow Data PSS™E-31.0
Importing Power Flow Data Users Manual
• If, on any input record, bus I is not in the working case, if it does not have a generator
(i.e., plant) slot assigned to it, or if an invalid machine identifier is specified, an appro-
priate message is printed, the record is ignored, and processing continues.
• If, in attempting to add a machine to the machine data arrays, the maximum number of
machines or machine ownership specifications for which PSS™E is dimensioned is
exceeded, an error message is printed and the record is ignored.
• When entering data records for machines already contained in the working case, com-
plete data records must be entered. Omitted data items take on their default values
rather than retaining their previous values.
• If sequence data is contained in the working case, for all machines being added to the
working case their three sequence machine impedances used in the fault analysis
activities are set to the impedance ZSORCE specified on the data input record.
• PSS™E cycles through all plants for which at least one machine data record had been
successfully read from the Machine Impedance Data File. The sums of the active and
reactive power split fractions of all the plant’s machines for which a data record was
read with a status flag of one are calculated. Then the plant totals of machine powers
and power limits for those machines with a status flag of one which were initially in the
case are calculated. (If any of the above sums are zero, the corresponding quantities
of the out-of-service machines are used.) Finally, the machine power outputs and limits
of all machines at the bus for which a data record was read are set to the product of the
corresponding plant quantity and the ratio of the machine fraction to the plant’s sum of
machine fractions. Plant totals are then updated as the sum of the corresponding
machine quantities
• In processing each plant, if any machine is encountered that existed at the plant prior
to reading the Machine Impedance Data File, and for which no data was read, such
machine is alarmed and either placed out-of-service with its data items in the working
case unchanged or deleted from the working case, as appropriate. Further, any
machine whose status flag is changed is tabulated. In either of these cases, the plant
totals could be changed and the plant configuration should be examined to verify that
it is as intended.
• This data input activity is not sensitive to any interrupt control code options.
3-58 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Importing Power Flow Data
PSS™E is able to access Saved Case Files written on other computer platforms. Refer to the host-
specific PSS™E usage manual for further information on reading foreign files.
If the file to be used is not in a Saved Case File format recognized by this release of PSS™E, the
following error message is generated and the importing process is terminated:
Generally, saved Case Files created by the current and previous releases of PSS™E can be
accessed. However, a Saved Case File written by the current version of PSS™E is normally not
able to be read by earlier releases of the program.
PSS™E can access only Saved Case Files written by PSS™E. It cannot read files written by any
other programs.
To import a Saved Case file, the File>Open option is used. In the Open dialog, selection is made
from the Save Case File (*.sav) file list (see Figure 3-22).
When picking up Saved Case Files created prior to PSS™E-27, transformers with nonzero values
of charging and winding 2 side (previously referred to as untapped side) line shunt in the positive
sequence are logged in the Output Bar (see Section 1.3.4); charging is set to zero, and the winding
2 side line shunt is added to the winding 1 side line shunt and then the winding 2 side line shunt set
to zero. In the zero sequence, nonzero transformer charging and line shunts are alarmed and set
to zero. Nonzero values of line length for transformers are set to zero but are not logged.
When picking up Saved Case Files created prior to PSS™E-20, zone assignments are checked and
any bus assigned to zone zero is reassigned to the zone with the largest permissible zone number.
The number of buses whose zone assignments are so changed is tabulated at the progress output
device.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-59
Managing Power Flow Data PSS™E-31.0
Importing Power Flow Data Users Manual
When picking up Saved Case Files created prior to PSS™E-18, branch circuit identifiers are exam-
ined to check that none contain an ampersand ("&") as their first character. If any such branches
are detected, they are tabulated and the user is asked to designate a character to which these
ampersands are to be changed. A check is made to ensure that this substitution does not result in
two or more branches with the same circuit identifiers connecting a pair of buses; if it does the user
is asked to specify another character to be used.
Very old Saved Case Files created prior to PSS™E-7 cannot be opened directly. Such files must
be converted to PSS™E-7 Saved Case File format by the auxiliary program CASCNV, which was
supplied with PSS™E-7 through PSS™E-10.
Following the successful restoration of the Saved Case into the working case, the two-line case title
is printed, in the Output Bar, followed by the time and date at which the case was last saved. In
addition, whenever any of the PSS™E run-time option settings as contained in the Saved Case File
differ from those set in PSS™E’s working memory, the settings from the Saved Case are estab-
lished and an appropriate message is printed.
This import activity is not sensitive to any interrupt control code options.
PSS™E allows the use of a long title containing up to 16 lines of alphanumeric data, each of which
may contain up to 72 characters. This data is placed into an array that is carried along with the case
as it is saved and retrieved. The user may utilize the long title to enter more detailed case descrip-
tive information than the two 60-character title lines, which are printed by each output reporting
activity, can accommodate.
Long title records are placed into the long title arrays in the exact format in which they are entered.
If any input record contains more than 72 characters, those beyond column 72 are ignored. If a
record contains fewer than 72 characters, the corresponding title line is blank filled.
The long title can be entered manually or read from a file. If input is taken from a data file and it
contains more than 16 lines, only the first 16 are recognized. If the data file contains fewer than 16
lines, the following message is printed, those title lines for which no data was read are blank filled,
and the input activity is terminated.:
Import of a long title is not sensitive to any interrupt control code options.
To import data comprising the long title, the File>Import>Import long title (RETI)… option is used
(see Figure 3-23).
3-60 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Importing Power Flow Data
Subsequent to selecting the Import long title (RETI) option, a Select file containing long case
title dialog will be opened where the appropriate file can be selected and the Open button clicked
to initiate the import of the long title data, (see Figure 3-24).
• Enter the entire long title manually without prior preparation of a Long Title File.
• Continue adding long title lines if there were less than 16 lines of data in the Long Title
File selected by the File>Import option.
• Enter and/or edit the short two-line title lines.
To initiate editing or addition of short and long title line data, use the File>Case titles, short & long
(CHTI)… option (see Figure 3-25).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-61
Managing Power Flow Data PSS™E-31.0
Importing Power Flow Data Users Manual
Selecting this option will open the Case Titles dialog where both long and short titles can be edited
or appended (see Figure 3-26).
3-62 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Viewing Power Flow Data
The data listing is initiated from the Power Flow>List Data… option, the selection of which
will open the List Data dialog (see Figure 3-27). Alternatively, the user can use the List Data
toolbar button which appears on the Reporting toolbar.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-63
Managing Power Flow Data PSS™E-31.0
Viewing Power Flow Data Users Manual
Since the lists can be lengthy, the user has the option to direct the lists to alternative devices using
the I/O Control option (see Figure 3-28). The figure is an abbreviated view of the complete set of
I/O functions but shows the menu items relevant here for directing Report and Progress output.
To re-direct a list it is necessary to select the Direct Report output (OPEN)… option at which point
the Report Output Destination Selector dialog is open (see Figure 3-29).
3-64 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Viewing Power Flow Data
• A file, for which is specified in the Report output destination file input field.
• A printer, for which the available printers will be made available with options on output,
copies and lines per page plus it is possible to print immediately or queue the output.
• Current progress device.
• Current report device.
In addition:
If the Sequence data option is checked, only the sequence data is listed on the same basis.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-65
Managing Power Flow Data PSS™E-31.0
Viewing Power Flow Data Users Manual
• Output voltage: The user can select to output voltage information by kV or by pu.
• Use double entry branch method: This allows selection of nontransformer branch
listing in either single or double entry format. In single entry format, each nontrans-
former ac series branch appears once in the listing: with the lower ordered bus (number
or name) listed as the "from bus". In double entry format, each branch is listed in both
directions.
The drop-down list for the Power flow data is shown in Figure 3-31 where, in addition to having all
the power flow data categories available for listing, there is the option to see a case summary.
The first case summary page tabulates various system totals and solution parameters. The BUSES
summary items are interpreted as follows:
TOTAL Total number of buses in the case, including star point buses of three-winding
transformers.
PQ<>0. Total number of type one buses with nonzero load.
3-66 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Viewing Power Flow Data
PQ=0. Total number of type one buses with no load, including star point buses of in-ser-
vice three-winding transformers.
PE/E Total number of type two buses that are regulating voltage (i.e., not at a var
limit).
PE/Q Total number of type two buses that are at a reactive power limit (these buses
have their type code set to -2 by the power flow solution activities).
SWING Total number of type three buses.
OTHER Total number of buses having other type codes, including star point buses of
out-of-service three-winding transformers (these are usually type four (i.e., dis-
connected) buses and/or those buses identified as boundary buses).
The BRANCHES summary tabulates ac branches. Its data items are interpreted as follows:
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-67
Managing Power Flow Data PSS™E-31.0
Viewing Power Flow Data Users Manual
The number of multisection line groupings and the number of ac branches that are members of mul-
tisection line groupings are tabulated separately. The total numbers of three-winding transformers,
dc transmission lines, and FACTS devices are tabulated separately. The service status of three-
winding transformers, multisection line groupings, dc lines, and FACTS devices is not tabulated.
System totals of generation, load, and so on are tabulated. The quantity shown as SHUNTS is the
sum of bus shunts, switched shunts, line connected shunts, magnetizing admittance of trans-
formers, and the shunt elements of FACTS devices. Losses are the sum of I2R and I2X losses for
in-service lines plus dc line and FACTS device losses, and do not include charging and line shunt
contributions. The loss and swing bus power totals are meaningful only if the working case repre-
sents a solved system condition. The highest and lowest pu bus voltages are listed along with the
largest individual bus and total system mismatch. Up to two swing buses are identified and if more
than two type three buses exist in the case, only two of these are listed.
The second page of the case summary tabulates those buses in the working case with the largest
mismatches. Up to 25 buses are listed, but not more than the number that can fit on one page.
If an area has an area slack bus designated for it, its number, name, base voltage, and active power
output are tabulated in the listing. This is followed by the plant active power limits, which are taken
as the sums of these limits for the in-service machines at the plant. If the total power output is out-
side of these limits, an asterisk ("∗") is printed following the generator power. The number of buses,
loads, and dc buses residing in each area is also tabulated.
The final line tabulates the summation of the listed desired interchanges.
The number of loads independently modeled at the bus is tabulated in the column labeled LOADS.
Shunt data tabulated are at nominal values (i.e., at 1.0 pu voltage), and do not include any constant
admittance load modeled at the bus.
Branches are ordered in ascending numerical or alphabetical order by "from bus", and, for each
"from bus", in ascending order by "to bus". Parallel circuits between any pair of buses are tabulated
in ascending circuit identifier order. An asterisk ("∗") follows the number, name and base voltage of
the bus designated as the metered end.
3-68 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Viewing Power Flow Data
The column labeled "ZI" contains a "Z" if the branch is treated as a zero impedance line; for other
branches, the "ZI" column is blank. The column labeled "ST" is the status flag of the branch, with 0
indicating out-of-service, and 1 indicating in-service. The remaining data items in this report cate-
gory correspond to data items specified in branch data input records.
For each two-terminal line, the dc line current (DCAMPS) and the compounded dc line voltage
(VCOMP) are printed on the first line of the output block, and the dc voltage at each end of the line
is printed with the converter data. The winding one tap ratio (RATIO) of an ac transformer that is
controlling a dc line quantity is shown following the ac transformer identifiers in the output block of
the appropriate dc line.
For each multi-terminal line, the voltage at each dc bus and the current on the dc side of each con-
verter transformer is printed. For each dc link in the line, the metered end dc bus is listed in the
column labeled MET.
For each VSC dc line, the dc line current (DCAMPS) is printed. For each converter, the apparent
ac system complex generation, the ac current in amps (ACAMPS), and the voltage on the dc side
of the converter are listed.
The line reporting the last transfer for each "from area" includes the algebraic sum of all transfers
involving the "from area", as well as the area’s desired net interchange.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-69
Managing Power Flow Data PSS™E-31.0
Viewing Power Flow Data Users Manual
Loads tabulated are at nominal values (i.e., at 1.0 pu voltage). The nominal constant MVA load
component may be adjusted by a load multiplier associated with an Optimal Power Flow adjustable
bus load table; the load multiplier is tabulated in the column labeled "PSI". Constant admittance
loads do not include any shunt elements modeled at the bus.
For each machine, the bus type code, machine identifier and machine status flag are listed in the
columns labelled CD, ID, and ST, respectively. Recall that the actual status of a machine is deter-
mined both by its status flag and the bus type code.
The branches comprising each grouping are listed in series order starting at the bus listed as the
"from bus".
Any plant that regulates the voltage at a remote bus has the remote bus listed at the right-hand side
of the report. Any plant regulating its own terminal voltage has no entry in this field.
3-70 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Viewing Power Flow Data
Any switched shunt that regulates the voltage at a remote bus or the reactive power output of a
voltage controlling device at a remote bus has the remote bus listed at the right-hand side of the
report; those regulating their own terminal voltage have no entry in this field.
In the transformer impedance and control data listings, the column labeled "W1" contains an "F" if
the bus listed as the "from bus" is the bus to which the transformer’s first winding is connected, or
a "T" if the "to bus" is the bus to which the first winding is connected.
In the transformer impedance data listing, the column labeled "ST" is the status flag of the trans-
former, with 0 indicating out-of-service, and 1 indicating in-service. The column labeled "MT"
contains an "F" if the bus listed as the "from bus" is the metered end, or a "T" if the "to bus" is the
metered end.
In the transformer control data listing, the controlled bus number is preceded by a minus sign if it is
on the winding one side of the transformer.
In the general and impedance data listings, the column labeled "ST" is the status flag of the three-
winding transformer.
The winding data and the tap and control data listings are comprised of three lines of data for each
three-winding transformer: one for each of the two-winding transformers in the star model used to
model a three-winding transformer.
In the winding data listing, the winding bus identifiers of the two metered windings are followed by
an asterisk ("*"). The column labeled "ST" is the status flag of the two-winding transformer, as
derived from the status flag of the three-winding transformer, with 0 indicating out-of-service, and 1
indicating in-service. The winding impedances are derived from the values entered as measured
impedances, and are listed in the units indicated by CZ; the measured impedances are listed in the
three-winding transformer impedance data listing.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-71
Managing Power Flow Data PSS™E-31.0
Viewing Power Flow Data Users Manual
In the control data listing, the controlled bus number is preceded by a minus sign if it is on the same
side of the transformer as the bus connected to the controlling winding.
• Out-of-service Branches
• Isolated Buses
• Out-of-service Plants
• Out-of-service Machines at In-service Plants
• Out-of-service Loads at In-service Buses
• Blocked two-terminal dc Lines
• Blocked Multi-terminal dc Lines
• Blocked VSC dc Lines
• Out-of-service Converters at In-service VSC dc Lines
• Blocked FACTS Control Devices.
The information provided shows the nominal shunt ratings (i.e., at nominal voltage) as well as the
actual voltage at the bus. See Figure 3-34 for a listing from the savnw.sav power flow case.
3-72 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Validating Power Flow Data
Figure 3-34. Shunt Data Listing from the savnw.sav Working File
These are not checks on the state of the power flow solution for which PSS™E provides other
reporting capabilities (see Section 4.1.4).
The data checking option is launched from the Power Flow>Check Data menu option which makes
available four data checking activities (see Figure 3-35).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-73
Managing Power Flow Data PSS™E-31.0
Validating Power Flow Data Users Manual
When the Power Flow>Check Data>Branch parameters (BRCH)… option is selected, the Check
Branch Parameters dialog is opened (see Figure 3-36). There are seven threshold values for
checking branch parameters.
In performing the checks, the user is free to change the threshold values to values which might be
more appropriate for the working case under examination.
The Select facility is available to limit the output based on area, zone, owner, voltage, bus or
any combination of these.
The figure shows the default threshold levels against which checks are made for parameters which
could be considered suspect. At the right of the threshold level selectors are shown the incremental
steps by which changes in the threshold values can be changed.
3-74 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Validating Power Flow Data
• Very small impedance branches not being treated as zero impedance lines may result
in a slowing of the rate of convergence of the power flow solution activities, and their
inability to reach the default convergence tolerances.
• Large impedance branches in themselves do not cause problems with the power flow
solution methods. However, when relatively small impedance branches are also con-
nected to these buses, convergence may be slowed and the solution activities may not
be able to reach the default convergence tolerances. In addition, very large imped-
ances are often present in inefficient network equivalents with some buses having an
unusually large number of branches connected to them. This will generally result in the
loss of the beneficial sparsity characteristics present with real system when the system
matrices are processed, with a corresponding increase in solution times.
• High R/X Ratio. The Newton-Raphson decoupled solution, NSOL, will diverge if there
are any branches whose resistance is greater than reactance. The other solution
methods are not particularly sensitive to this ratio.
• High Xmax/Xmin ratio. In determining the largest and smallest connected reactance;
zero impedances are neglected in determining the smallest reactance. The presence
of a bus with a wide range of reactances connected to it may slow the rate of conver-
gence of the power flow solution activities and result in failure to reach the default
convergence tolerances.
• High values of line charging do not necessarily cause problems with the power flow
solution methods except in cases of data entry errors (for example, all charging values
entered in Mvar rather than per unit resulting in abnormally high voltages). Negative
values of line charging are data errors.
• High and Low transformer tap ratios for which the default thresholds are 1.1 and 0.9,
respectively. Any transformer branch for which either the winding one tap ratio or
winding two tap ratio is beyond the specified limit is tabulated.
• The parallel transformer check scans parallel branches between pairs of buses and
alarms:
- Nontransformer and transformer branches in parallel.
- Parallel two-winding transformers with different first winding complex tap ratios.
- Parallel two-winding transformers with different second winding tap ratios.
- Parallel two-winding transformers with their winding one/winding two side relation-
ship reversed.
• The negative reactance check tabulates all negative reactance branches. If either of
the buses for such a branch is a generator bus (i.e., type two or three), an asterisk ("*")
is printed before the branch circuit identifier. The Gauss-Seidel solution method usually
diverges if the working case contains any in-service negative reactance branches. The
Modified Gauss-Seidel method, however, is able to handle negative reactance
branches between type one buses, but negative reactances connected to type two or
three buses usually result in divergence.
• For the missing zero sequence data check, the branch check procedure alarms any
branch with a zero sequence impedance of zero. This test is bypassed if sequence
data is not contained in the working case.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-75
Managing Power Flow Data PSS™E-31.0
Validating Power Flow Data Users Manual
If only in-service elements are to be processed, any bus which is designated as the controlled bus
of some voltage controlling equipment item but whose type code is greater than three is not consid-
ered a voltage controlled bus. In addition, the following voltage controlling equipment is ignored.
3-76 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Validating Power Flow Data
of equipment whose control parameter data is such that it is controlling the voltage at the bus being
processed. Such equipment includes:
• Generation at the bus itself, if it is not remotely controlling the voltage at some other
bus. The type code of the generator bus is printed in the STATUS column.
• Generation at a remote bus, which is controlling the voltage at this bus. The type code
of the remote generator bus is printed in the STATUS column.
• A switched shunt at the bus itself, if it is not remotely controlling the voltage at some
other bus or the reactive power output of some other voltage controlling device. The
control mode of the switched shunt is printed in the STATUS column.
• A switched shunt at a remote bus, which is controlling the voltage at this bus. The type
code of the bus to which the switched shunt is connected and the control mode of the
switched shunt are printed in the STATUS column.
• A FACTS device connected to the bus. The device’s control mode is printed in the
STATUS column.
• A converter of a VSC dc line connected to the bus itself, if the converter is in ac voltage
control mode and is not remotely controlling the voltage at some other bus. The VSC
dc line’s control mode (MDC) and the converter’s dc control code (TYPE) are printed
in the STATUS column.
• A converter of a VSC dc line connected to a remote bus, if the converter is in ac voltage
control mode and is remotely controlling the voltage at this bus. The VSC dc line’s con-
trol mode (MDC) and the converter’s dc control code (TYPE) are printed in the STATUS
column.
• A voltage controlling transformer without load drop compensation. For two-winding
transformers, transformer status is printed; for three-winding transformers, winding
status is printed in the STATUS column.
For each such equipment, the desired voltage setpoint or voltage band, as appropriate, is tabulated.
A list is then generated of any suspect voltage control specifications. If the Allow voltage schedule
changes option was selected, the user has the option of specifying a new scheduled voltage.
If a new value is entered, the control parameters are modified accordingly. For those devices con-
trolling to a voltage band, the band retains its previous voltage spread with the designated voltage
as the midpoint.
Each voltage controlling transformer with load drop compensation, whose controlled bus is being
processed is then listed, along with the compensated voltage it would sense and its voltage limits.
If the Allow voltage schedule changes option was selected, the user then has the option of spec-
ifying a new voltage band:
Buses connected together by zero impedance lines are treated as the same bus. Controlling equip-
ment, along with any error and warning messages, apply to the combined bus. In the interactive
mode, each group of buses connected together by zero impedance lines, which has at least one of
the buses in the specified subsystem, is tabulated once, even if more than one of its buses is in the
specified subsystem. In the reporting mode, each such bus is reported in its usual position in the
bus collating sequence.
The process of voltage schedule processing may be terminated by entering the AB interrupt
control code.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-77
Managing Power Flow Data PSS™E-31.0
Validating Power Flow Data Users Manual
If any transformers fail the check, the user has the option of modifying the data of all transformers
tabulated. The user may then designate the next check to be performed. Prior to performing the
check, the user can select transformers to be checked on the basis of areas, zone, owners, voltage,
buses or any combination.
As an example use of this function, assume we need to check the controlling Flow band for all MW
controlling transformers in the savnw.sav working file. Use a threshold Flow band of 5.0 MW.
Figure 3-39 shows the Check/Change Transformer Adjustment Data dialog for this check.
3-78 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Validating Power Flow Data
The result of this example check shows one power controlling transformer with a Flow band of 10
MW compared to the threshold check of 5.0 MW (see Figure 3-40).
The failure to pass the test prompts an option to change the transformer Flow band to the threshold
level or to any other required level as necessary (see Figure 3-41).
The Report produced first lists any type four bus with one or more in-service branches connected
to it. Such error conditions usually result from manually isolating a bus by changing its bus type
code and the branch status flags to the appropriate values but overlooking one or more branches.
The Report then tabulates all type three buses in the working case, followed by a listing of buses
that do not have a type code of four and are not looped back to a swing bus. These buses are
grouped by island, and, within each island, in ascending bus number (under the numbers output
option) or alphabetical (under the names output option) order. The tabulation of each island is fol-
lowed by a summary of the number of buses and plants in the island along with total island load,
shunt, generation, and var limits.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-79
Managing Power Flow Data PSS™E-31.0
Editing Data Users Manual
The Report will appear in the Progress or Report tab of the Output Bar or at the report output device
selected by the user. Following the tabulation of each island, the user is given the option of discon-
necting it or continuing the check, see Figure 3-42.
If the user elects to disconnect the island, PSS™E performs the required bus type code and branch
status flag changes to disconnect all buses that were listed as not tied back to a swing bus. Any in-
service dc lines connected to such buses are blocked. Any in-service series FACTS devices con-
nected to such buses are placed out-of-service. This process is repeated for each island.
This checking activity does not allow subsystem selection. It always scans the entire working case.
The island output listing may be terminated by entering the AB interrupt control code.
Data changes are made in the Spreadsheet View which can be accessed merely by bringing the
view to the top (over any diagram views which might be open). With the spreadsheet active, the
user can select the data category tab of interest and scroll to the particular cell of interest. From
here data can be modified or deleted using the usual spreadsheet editing techniques.
3-80 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Editing Data
Double-click here
Double-click here
Figure 3-43. Moving to a Spreadsheet Item from the Tree or Diagram View
Data in a cell is edited using standard techniques. When one or more cells in a row have been mod-
ified, a pencil symbol is placed in column 1 of the row (Figure 3-44). The data changed is not
recorded in the PSS™E working case until the cursor is moved to another row. At that point, all data
changes made to the row are recorded and the pencil symbol is removed.
Some cells of a record contain check boxes (Figure 3-45a) for the user to select an option. Other
cells contain combo boxes (Figure 3-45b) in which a user can choose a value from a drop-down list.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-81
Managing Power Flow Data PSS™E-31.0
Editing Data Users Manual
If a single row is selected, the options shown in Figure 3-46a are available. If multiple rows are
selected, the options shown in Figure 3-46b are available.
Use of the Create a bus subsystem option is discussed in Section 2.4.2.2. This is available
when either a single row or multiple rows are selected.
Use of the Create bus display (GOUT/GEXM) option is discussed in Section 2.4.3.3. This is
only available when a single row is selected.
3-82 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Editing Data
Figure 3-46. Selecting Rows for Copy and Paste Operations in the
Spreadsheet
New or additional data can be introduced by pasting data copied from an external application (for
example Excel). This facility accommodates the addition or editing of data on a specific data cate-
gory tab. This is the reverse of the File>Export option (Section 2.4.6) used for copying a data tab
in PSS™E for exporting to another application.
When working in the Diagram View, right-clicking an element will open the pop-up menu that
includes the Delete option. Deleting the item in the diagram will delete that item data from the
spreadsheet; meaning that the element is deleted from the data base. See Section 2.9.8 for more
details on this operation and the Bind Items requirement for deleting via the Diagram View.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-83
Managing Power Flow Data PSS™E-31.0
Creating a New Power Flow Case Users Manual
To initiate creation of the new data base the user should use the File>New option. The New dialog
will give the option of creating a new case, a new case and new diagram, a new diagram or a new
plot sheet. (Figure 3-47).
Having selected the Network case option, the user will be presented with the Build New Case
dialog where the Base MVA and a two line title can be supplied (Figure 3-48).
Figure 3-48. Initial Data Requirement for Creation of a New Data Base
Once this information is provided, a blank Spreadsheet View will be made available. The user can
now type in data elements or paste information copied from another application on to each tab.
3-84 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Creating a Power Flow Case using the Diagram View
An alternative is to open a blank Diagram View after initiating the new case and creating the blank
Spreadsheet View. Then network elements can be added graphically, in the newly opened Diagram
View instead of typing data into the spreadsheet.
The new Diagram View is opened as using the File>New option but this time selecting Diagram
instead of Network case (see Figure 3-47).
First, however, the user should choose to number the buses automatically or not. Selecting
Edit>Preferences will display the Program Preferences dialog partially shown in Figure 3-50. For
the purposes of this example, the buses will be numbered starting from 1 at increments of 100.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-85
Managing Power Flow Data PSS™E-31.0
Creating a Power Flow Case using the Diagram View Users Manual
2. Click on the Diagram View in those locations where the buses are to be placed
(remember, they can be moved and otherwise adjusted later).
If three buses are added, they will be numbered, 1, 101 and 201. As they are added to the diagram,
they will also be added to the spreadsheet with default values. Default values can be modified sub-
sequently by editing in the Spreadsheet View (Figure 3-51).
3-86 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Creating a Power Flow Case using the Diagram View
Figure 3-51. Adding Buses to the Data Base via the Diagram View
With the buses positioned, the following steps are required to add the equipment:
1. Select the Branch toolbar button and drag branches with the mouse between buses 1
and 101 and between buses 101 and 102.
• Select the Generator toolbar button and draw the symbol by dragging the mouse from
bus 1 and bus 201.
• Select the Load toolbar button and draw the symbol by dragging the mouse from bus
101.
• Because default values will be assumed for each data type, now edit the data in the
spreadsheet.
The result are displayed in Figure 3-52.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-87
Managing Power Flow Data PSS™E-31.0
Creating a Power Flow Case using the Diagram View Users Manual
Adding a Branch
Adding a Generator
Adding a Load
3-88 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Exporting and Merging Power Flow Data
This section describes specifically how raw data can be exported for later use in establishing a new
power flow case or modifying an existing case.
Figure 3-53. Save/Show Network Data Dialog – Power Flow Raw Data
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-89
Managing Power Flow Data PSS™E-31.0
Exporting and Merging Power Flow Data Users Manual
When exporting raw data there are three alternative methods. In Figure 3-55, the data file can be
formatted to:
• Initialize a working case (the IC code in the file will be zero; see Section 3.2.1).
• Add data to a working case (the IC code in the file will be 1; see Section 3.2.1).
• Provide change data ("use with RDCH" option) (no case identification information; see
Section 3.3.4).
3-90 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Exporting and Merging Power Flow Data
To merge two power flow cases, designated Case A and Case B, first open Case A and then input
the raw data for Case B. The raw data file must be formatted to add data rather than initialize the
case; independent of its origins, and must be free of bus and other numbering problems. The import
can be initialized by opening the raw data file for Case B by using the File>Open and selecting the
*.raw type file category (see Figure 3-56).
When the file is opened as shown in the figure, the user will be given the option to save or not the
file which is currently open before the raw data is added. The new data, from Case B will appear in
the spreadsheet together with the existing data of Case A.
As described in Section 3.3.3, it is possible to add data by subsystem. Figure 3-56 shows that
option in the file type list as Power Flow Data File, Option(*.raw). After initiating the action to append
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-91
Managing Power Flow Data PSS™E-31.0
Exporting and Merging Power Flow Data Users Manual
the raw data, by clicking the Open button, and having elected to Save or not the current case, the
Read Power Flow Raw Data dialog appears (see Figure 3-57).
When appending data by subsystem, the user can elect to use the name option for input and to ini-
tialize the case. Further, the user can change the "boundary buses". Any bus that is within a
specified subsystem and connected to a bus that is not in the working case may be identified as a
"boundary bus"; the type code of each boundary bus is changed to 5, 6, or 7 as appropriate. For
3-92 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Managing Power Flow Data
Users Manual Exporting and Merging Power Flow Data
more information see Chapter 9, where the process of making network equivalents along with the
topic of "boundary buses", is discussed.
Additional flexibility is available for data input. It can be seen that data can be appended not only
by selected subsystems but also limited to either data within a subsystem or only ties from the
subsystem.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 3-93
Managing Power Flow Data PSS™E-31.0
Exporting and Merging Power Flow Data Users Manual
3-94 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Chapter 4
Power Flow
Having started the PSS™E application the user will see a blank page with only the menu and tool-
bars visible. If, however, the Tree View, Output Bar or Status Bar were open when the program was
previously closed, these will be open.
To import data, use the File>Open option or the Open toolbar button as shown in Figure 4-1 and
select either a Save Case file or a Raw Data file. Selecting either type will provide a list of available
files from which to select.
PSS™E uses a wide variety of files including three type of raw data files. The file of interest, at this
time, is the basic Power Flow Raw Data file, as indicated, or the Save Case file.
In the PSS™E EXAMPLE directory there are many files for the user’s use. To perform some basic
tests, as described here, select either the savnw.sav or savnw.raw files. Selection of either will open
a populated Spreadsheet View containing the savnw power flow base case; a partial view is shown
in Figure 4-2.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-1
Power Flow PSS™E-31.0
Overview: Power Flow Users Manual
4-2 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Overview: Power Flow
To run a power flow case, use the Power Flow>Solution>Solve… option (see Figure 4-3)
or the Solve button.
The initiation of the power flow solution will open the Loadflow solutions dialog (Figure 4-4) where
the user can select the type of power flow solution to use and the control parameters. If this is not
the first power flow solution used in the work session, then clicking the Powerflow toolbar button will
not open the dialog but will assume the previous power flow solution and control selection.
As shown in Figure 4-4 there are two tabs in the dialog; one for Newton solutions and one for
Gauss-Seidel solutions.
There are three Newton solutions and two Gauss solutions. The user should select the appropriate
solution as a function of the network conditions and solution starting point (Section 4.3).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-3
Power Flow PSS™E-31.0
Overview: Power Flow Users Manual
Other controls are available for use during the iteration process. These include, depending on the
type of solution selected:
A quick note of value is that the Gauss-Seidel solution cannot handle negative series reactances
(series capacitors) but the Newton and Modified Gauss-Seidel can.
When the solution type and control options have been selected, the user needs to click the Solve
button. The solution will proceed and a printout of the convergence monitor and power flow condi-
tions will appear in the Output Bar. It will be clear whether of not the solution has converged and
what the mismatch conditions are (Section 4.3.9.4).
If the case has not converged, the user can modify the solution parameters (Sections 4.3.7.1 and
4.3.9.2) and solution type, if warranted, and re-run the solution. If the solution had diverged (blown
up), the Flat start control option should be used to establish a feasible starting point for the next
solution.
4-4 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Overview: Power Flow
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-5
Power Flow PSS™E-31.0
Overview: Power Flow Users Manual
To examine only the power flow results, the bus based report is most appropriate. This will list the
flow and bus conditions in tabular format (as did the activity POUT available in previous versions of
PSS™E). Selecting the Bus based report… option will open the Bus Based Reports dialog where
buses or subsystems of buses can be selected for output; see Figure 4-6 where bus 152 has been
selected.
4-6 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Overview: Power Flow
A partial view of the bus based report for bus #152 is shown in Figure 4-7. The report will be printed
on a Report tab or to an alternative location (file, printer) of the user’s choice, (see Section 2.16).
Reference should be made to Section 4.4 for a more detailed discussion of the output reports.
Figure 4-7. Partial Bus Based Report for Bus #152 in the savnw.sav Power
Flow Case
Figure 4-8. Graphical Output for Power Flow savnw.sav - Bus 152
The user can switch a network element out of service or modify element ratings (loads, shunts, ele-
ment ratings, element impedances etc) by editing data cells in the spreadsheet. Specifically, to take
an element out of service, its status will be changed from "1" to "0" (see Figure 4-9).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-7
Power Flow PSS™E-31.0
Overview: Power Flow Users Manual
When operating in the Diagram View, the user should merely double-click on the element to be
taken out of service or have its data modified. The program will switch the view to the spreadsheet
directly to the data tab and appropriate row for the data item to be changed.
If data is changed in the spreadsheet by editing a specific cell, the user must point to a dif-
ferent row before the data change is recorded by the program.
Once the data change is made (status or value), the user can click on the Solve button to obtain a
revised power flow.
First, double-click on line 152 - 3004 to highlight the line’s data row on
the Branch tab in the spreadsheet.
This section is only an introduction to running power flow cases. The following sections and chap-
ters provide a significant amount of detail on using PSS™E as the simulator for sophisticated and
complex power system analyses.
4-8 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Calculations
"Given the load power consumption at all buses of the electric power system and
the generator power production at each power plant, what is the power flow in each
line and transformer of the interconnecting network?"
Calculated answers to this question are the basic means by which the power system is engineered
to serve its load. The power system must operate without overloading transmission lines or trans-
formers, stay within acceptable voltage limits at all buses, and maintain generator reactive power
outputs between acceptable limits.
The power flow problem pertains to balanced steady-state operation of the power system. Because
it considers balanced operation in which all negative- and zero-sequence voltages are zero, the
power flow calculation deals with the positive-sequence model of all system components.
The following are the basic known input data for power flow calculations:
• The magnitude of the voltage at every bus where this is not specified in the input data.
• The phase of the voltage at every bus, except swing buses.
• The reactive power output of each plant for which it is not specified.
• The real power, reactive power, and current flow in each transmission line and
transformer.
The power flow calculation is a network solution problem. The network of transmission lines and
transformers is described by the linear algebraic equation:
I n = Y nn V n (4.1)
where:
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-9
Power Flow PSS™E-31.0
About Power Flow Calculations Users Manual
If either In or Vn is known, the power flow calculation is straightforward. In practice, neither In nor
Vn is known and the task of the power flow program is to devise successive trials of both In and Vn
such that they satisfy both (4.1) and all the load and generation conditions specified in the problem
data. Once Vn has been determined, all individual transmission line and transformer flows can be
obtained directly from their individual component equations.
Bus i is connected only to buses j, k, m, and n. Also note the designation of the tap-changing
side of each transformer.
n •
Transmission Line •j
Tap
Changer
i Transmission Line
• • k
•
m
•
Transformer
Tap Changer
Shunt Reactor and Capacitors
Each line and transformer may be represented by a per-unit equivalent circuit, with per-unit param-
eters being calculated from spacing, length, and nameplate data with respect to a common system
MVA base. The resulting equivalent circuit surrounding network node, i, which represents bus i in
the equivalent circuit of the whole system, is shown in Figure 4-11.
4-10 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Calculations
n• tin : 1
•j
Zij
•
Zin B ij
2
•
B ij
i
• 2
•
• Zik
Zi m Ysi
1: tim
B ik
•
B lik 2
m• B ik • k
2
The total current, ii, flowing into node i when voltages, vi, vj, vk, vm, and vn are applied to the net-
work are determined by adding up the flow into each leg of Figure 4-11 at its connection to node i.
In the case shown above, the total current, ii, is zero since there is no source or load connected
there. Hence:
i i = v i Y si
v i B ij
+ ( v i – v j )/z ij + -----------
2
v i B ik
+ ( v i – v k )/z ik + ------------- + v i B lik
2
(4.2)
⎛ vi ⎞
+ ⎜ ------- – v m⎟ / ( z im t im )
⎝ t im ⎠
⎛ v n⎞
+ ⎜ v i – ------⎟ /z in
⎝ t in⎠
Expansion of (4.2) for the i-th element of In, which is ii, gives:
n
ii = ∑ y ih v h (4.3)
n=1
where
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-11
Power Flow PSS™E-31.0
About Power Flow Calculations Users Manual
The expressions for the elements, yih, in terms of transmission line and transformer parameters can
be found by collecting terms in (4.2) and comparing the result with (4.3). The construction of the
individual elements, yii, of the network admittance matrix from the line and transformer data is a key
section of all power flow solution procedures of PSS™E.
Examination of (4.2) shows that only the diagonal element, yii, and four off-diagonal elements, yih,
of the i-th row of the admittance matrix are nonzero. That is, a line or transformer from bus i to bus
j contributes nonzero elements only to the i-th and j-th rows of Ynn. Realistic power systems have
between 1.5 and 2 transmission lines or transformers for each node. A transmission network of
2000 buses might, therefore, be expected to have approximately 4000 branches and, correspond-
ingly, 8000 nonzero off-diagonal elements in its admittance matrix. This typical bus-to-branch ratio
results in very sparse admittance matrices. In the above example only 8000 out of (2000) (2000-1),
or 0.2% of the off-diagonal elements of Ynn are nonzero.
The great majority of modern power flow calculation programs, including those of PSS™E, take
advantage of this sparsity in their management of computer storage. They also take advantage of
procedures that allow the admittance matrix to be manipulated into triangular factor and partial
inverse forms which have similar sparsity properties, but whose number of nonzero off-diagonal ele-
ments is typically two to three times the number of such elements in the original Ynn matrix.
Presenting a power flow program with a power system network model, whose original Ynn matrix
(or derivatives therefrom), has a number of nonzero elements that exceed the program’s allocated
capacity, results in an error condition that prevents the use of some, but not all, of the available
power flow iteration algorithms.
4-12 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Calculations
The Select area allows the user to select the portion of the admittance matrix to be output. The fol-
lowing selections are available:
In the Destination and data type area, the user elects to direct the output to either a named file or
to the Output Bar of the PSS™E window.
The admittance matrix terms produced are extracted from the admittance constructed by, and used
during, the PSS™E power flow solution functions. As such, they include constant admittance loads,
off-nominal tap ratios, and phase shifts, but exclude constant MVA load, constant current load, gen-
erator, switched shunt, dc line, and FACTS device contributions. Further, the admittance matrix
used during the power flow solutions excludes rows and columns for swing (i.e., type 3) buses; this
function also excludes terms from these rows and columns unless generators are "converted" (i.e.,
activity CONG is executed) prior to initiating this function.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-13
Power Flow PSS™E-31.0
About Power Flow Calculations Users Manual
Since the admittance matrix is extremely sparse, its terms are output as a set of matrix terms, using
external bus numbers, as in the following example:
2. Build up an estimated current inflow vector, In, at each bus from a boundary condition
such as:
P k + jQ k = v k i k* (4.4)
where:
3. Pk + jQk= Net load and generation demand at bus k.
5. Return to Step 2 and repeat the cycle until it converges on an unchanging estimate of
vn.
While this scheme is useful in some specific situations (to be discussed later), it does not work well
for the general power flow calculation where the terminal voltage magnitude, rather than reactive
power output, is specified for many generators.
The network condition (4.1) is linear and can be solved without iteration if either the voltage vector,
vn, or the current vector, In, is specified. The solution is a direct calculation if vn is specified, and
requires a standard computer procedure for solving linear simultaneous equations if In is given.
The boundary conditions may be specified quite arbitrarily, depending upon the loads that electricity
users choose to connect to the network, and are usually nonlinear. It is the nonlinearity of the
boundary conditions that forces the use of an iterative procedure for power flow solution. It must be
4-14 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Calculations
noted though, that while the network condition can be handled in a non iterative, closed-form
manner, it is often advantageous to use an iterative method to solve both the network condition and
the boundary conditions.
Real (v k i k* ) = – P k (4.5)
Imag (v k i k* ) = – Q k (4.6)
This characteristic is not realistic for voltages below approximately 0.8 per unit. All PSS™E power
flow voltage solutions, in both power flow and dynamic simulation, therefore, modify (4.5) and (4.6)
to make Pk and Qk functions of the magnitude of the bus voltage as shown in Figure 4-13.
Figure 4-13. Constant MVA Load Characteristic (Top) and Resultant Form of
Current/Voltage Curve (Bottom)
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-15
Power Flow PSS™E-31.0
About Power Flow Calculations Users Manual
The constant power characteristic holds the load power constant as long as the bus voltage
exceeds the value specified by the solution parameter PQBRAK, and assumes an elliptical current-
voltage characteristic of the corresponding load current for voltages below this threshold.
Figure 4-15 depicts this characteristic for PQBRAK values of 0.6, 0.7, and 0.8 pu. The user may
modify the value of PQBRAK via the Power Flow>Solution>Parameters… option. This will open
the Solution Parameters dialog where the value of PBRAK can be edited (see Figure 4-14).
4-16 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Calculations
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-17
Power Flow PSS™E-31.0
About Power Flow Calculations Users Manual
Real (v k i k* )
------------------------------ = – I pk (4.7)
vk
Imag ( v k i k* )
------------------------------- = – I qk (4.8)
vk
Again, because this characteristic is unrealistic for voltages below about 0.5 per unit, all PSS™E
power flow solutions modify (4.7) and (4.8) to make Ipk and Iqk functions of the magnitude of vk, as
shown in Figure 4-16.
Figure 4-16. Constant Current Load Characteristic (Top) and Resultant Form
of Load MVA/Voltage Curve (Bottom)
4-18 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Calculations
ik P k – jQ k P k – jQ k Pk Qk
----- = G k + jB k = ---------------------- = ---------------------- = ------------ – j ------------ (4.9)
vk v k v k* 2 2 2
vk vk vk
Note that (4.9) is not treated as a boundary condition in the solution process; it can be more conve-
nient to incorporate this type of load as a bus shunt branch unless there is a need, at some time, to
convert this load to another type.
The normal practice is to specify the load at each bus initially as a compendium of constant MVA
and constant admittance loads. Subsequently the data can be adjusted to comprise the required
amounts of each characteristic. This course gives compatibility with external power flow data for-
mats such as the IEEE Common Format.
Conversion and construction of load data is facilitated by the Power Flow>Convert Loads and
Generators… which launches the Convert/Reconstruct Loads and Generators dialog (see
Figure 4-17). The operation is described in detail in Section 4.5.2.
The net real and reactive power inflow to a swing bus are free variables and follow from the power
flow solution, rather than being boundary conditions imposed upon it.
Power flow solution cases must have at least one swing bus in every separate section (island) of
the network. An AC island is defined as the set of all in-service buses such that each bus in the
island may be reached from every other bus in the island through the in-service AC network. If a
working case contains more than one island, any island is either electrically disjoint from all other
islands, or connected to one or more other islands by one or more asynchronous ties (e.g., DC
lines).
To be a valid power flow case, each AC island in the working case must contain at least one type
3 (swing) bus. Further, the buses connected by each in-service branch must be in-service (i.e.,
none of them may be type 4 buses). No swing bus is needed in fault analysis, switching, and
dynamic simulation calculations, although swing buses may be used in these simulations.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-19
Power Flow PSS™E-31.0
About Power Flow Calculations Users Manual
When enabled, the solution connectivity checking option checks for the presence of swingless
islands at the start of each power flow solution (see Section 1.6.4).
The user can check that every subsystem of a power system power flow case includes a swing bus
via the Power Flow>Check Data>Buses not in swing bus tree (TREE) option (see Figure 4-18).
4-20 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Calculations
Bus k
•
t g :1 Zt
The standard generator boundary condition is a specification of real power output at the high
voltage bus, bus k, and of voltage magnitude at some designated bus, not necessarily bus k.
Real (v k i k* ) = P k (4.11)
V 1 = V sched (4.12)
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-21
Power Flow PSS™E-31.0
About Power Flow Calculations Users Manual
Q mn k ≤ Imag ( v k i k* ) ≤ Q mx k (4.13)
It is important to recognize that the maximum and minimum reactive power limits assigned to bus k
apply to generator reactive power output measured at the high-voltage bus and not at the generator
terminals. Determination of Qmin k and Qmax k must, therefore, recognize the reactive power loss
in the step-up transformer reactance. A reasonable assumption for assigning reactive power limits
to bus k, in this situation, is to subtract a reactive loss corresponding to full load current (1.0 pu)
from the generator terminal reactive power limits.
Since Zt has a per-unit value with respect to generator MVA base and Qmin k, Qmax k are in
megavars,
Unit 1 R MVA
t :1 Zt
Unit 2 R MVA
t :1 Zt
Unit n R MVA
t :1 Zt
nR MVA
t :1 Zt
4-22 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Calculations
Lumping several identical generators may, for example, be used where startup and shutdown of
individual units within a plant are scheduled to meet increasing and decreasing plant loading. This
is achieved by adjusting Pgen, Qmax k, Qmin k, and MBASEk. No adjustment of Zt or of the network
Use of this lump approach to handle multiple units implies that real and reactive power output are
distributed uniformly between them. If loadings of multiple units are not identical, they must be
treated as different generators even though their impedances and other characteristics are iden-
tical. This offers the advantage of having to change only unit status flags to account for a change in
the number of operating units at the plant.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-23
Power Flow PSS™E-31.0
About Power Flow Solution Methods Users Manual
Because their convergence properties are dependent upon network and load attributes, each of the
five power flow iteration methods of PSS™E has its own strengths and weaknesses. The most sig-
nificant strengths and weaknesses are summarized in Table 4-2.
Any of these five methods can fail to converge on the solution of some problems. It is rare, however,
to find a problem whose correct voltage solution vector cannot be found by the application of one
or more of the five methods. There are many problems that are difficult or impossible to solve with
a single iterative method but which can be solved readily by the successive application of more than
one method.
• The Gauss-Seidel methods are generally tolerant of power system operating condi-
tions involving poor voltage distributions and difficulties with generator reactive power
allocation, but do not converge well in situations where real power transfers are close
to the limits of the system.
• The Newton-Raphson methods are generally tolerant of power system situations in
which there are difficulties in transferring real power, but are prone to failure if there are
difficulties in the allocation of generator reactive power output or if the solution has a
particularly bad voltage magnitude profile.
• The Gauss-Seidel methods are quite tolerant of poor starting voltage estimates, but
converge slowly as the voltage estimate gets close to the true solution.
• The Newton-Raphson methods are prone to failure if given a poor starting voltage esti-
mate, but are usually superior to the Gauss-Seidel methods once the voltage solution
has been brought close to the true solution.
Experimentation is needed to determine the optimum combination of iterative methods for each par-
ticular power system model.
Experience suggests the following as the most advantageous approach to new power flow cases
whose specific characteristics have yet to be learned:
4-24 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Solution Methods
• Initialize all voltages to either unity amplitude, or to scheduled amplitude if given, and
initialize all phase angles to zero. (This step is referred to as a flat start.)
• Execute Gauss-Seidel iterations until the adjustments to the voltage estimates
decrease to, say, 0.01 or 0.005 per unit in both real and imaginary parts.
• Switch to Newton-Raphson iterations until either the problem is converged, or the reac-
tive power output estimates for generators show signs of failure to converge.
• Switch back to Gauss-Seidel iterations if the Newton-Raphson method does not settle
down to a smooth convergence within 8 to 10 iterations.
Experience with each specific problem will suggest modifications to this procedure. In particular, the
initial Gauss-Seidel iterations and flat-start steps will be bypassed when the result of a previous
solution is known to be a close estimate of the expected new solution.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-25
About Power Flow Solution Methods
Power Flow
4-26
Iteration (SOLV) errors, insoluble reactances. estimates are poor. capacitors or very number of bus and return directly to
conditions in local Acceleration factor must be tuned Network has reactive low impedance having largest ∆V activity selector.
areas of network. to match system for optimum power problem. branches. each iteration NC to suppress
Fails gently, performance. together with /∆V/ convergence
NSOL or FNSL has
indicates areas of and rectangular monitor listing.
Number of iterations increases as failed to converge.
network causing components of
system size increases. Data is suspect. DC to print DC line
problem. ∆V. /∆V/ is printed
operating
as multiple of
parameters at each
solution
iteration.
tolerance.
NM to suppress
adjustment
monitors.
Modified Gauss- Has most Convergence is very sensitive to As for Gauss-Seidel. Network has very As for Gauss- As for Gauss-Seidel.
Seidel Iteration advantages of tuning of acceleration factor, low impedance Seidel.
(MSLV) Gauss-Seidel and ACCM. branches, series
is able to handle Slight deviation of ACCM from compensation
series capacitors optimum. Value gives poor exceeding about
between Type 1 convergence. 80%, or series
buses. capacitors
connected directly to
generator buses.
Users Manual
PSS™E-31.0
Table 4-2. Power Flow Solution Activities—Selection Guide (Cont.)
Users Manual
PSS™E-31.0
Siemens Power Transmission & Distribution, Inc., Power Technologies International
Power Flow
cases where reactive power
limits are restrictive.
4-27
Power Flow PSS™E-31.0
About Power Flow Solution Methods Users Manual
4-28 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Solution Methods
1. Those generators that regulate their own voltage hold their scheduled voltage as long
as their reactive power limits are not violated.
2. Those generators that regulate the voltage of a remote type 1 or 2 bus have their own
voltage adjusted as required to hold the desired voltage at the remote bus as long as
their reactive power limits are not violated.
3. Those generators that are swing buses (i.e., with a type code of three) are held at
constant voltage and phase angle. Their active and reactive power outputs are set as
required prior to leaving the solution process. For such buses with both generators and
synchronous condensers, only the generators share the swing bus’ active power
output.
4. At the end of the solution process, generator plant reactive powers (and active powers
for type three buses) are apportioned among the machines at the plant; var values are
split so as to achieve identical power factor at all machines in a plant, except that
machine reactive power limits are honored.
1. Automatically switched shunts are permitted only at type 1 and 2 buses. At type 3
(swing) buses, switched shunts are treated as fixed at the value initially specified as
BINIT or as subsequently modified by editing the working case.
2. For those switched shunts designated as fixed (i.e., MODSW = 0 or the bus is a type 3
bus), the specified admittance is held constant during the solution.
3. Those switched shunts controlling local or remote bus voltage to a voltage setpoint
(i.e., VSWHI = VSWLO) are handled as follows:
4. Switched shunts controlling local or remote bus voltage to a voltage band (i.e.,
VSWHI > VSWLO) must be designated as operating in discrete mode. Such devices
are moved in single steps between network solution iterations.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-29
Power Flow PSS™E-31.0
About Power Flow Solution Methods Users Manual
5. Continuous mode control to a voltage band is not allowed. Such devices are alarmed
and treated as controlling to a voltage setpoint (taken as the midpoint of the specified
voltage band) in continuous mode as described in (3a) above.
6. Those switched shunts controlling other voltage controlling devices check the reactive
power output of the controlled device against the more restrictive limits described in
Section 3.2.11 which describes the data records and control modes for switched shunt
devices. If the reactive power is outside of those limits, one step of switched shunt
admittance is switched on or off so as to bring the reactive output of the controlled
device toward the nearest of the more restrictive limits. In the example in
Section 3.2.11, if the output of the controlled voltage controlling device exceeds 25
Mvar, the reactive output of the switched shunt will be increased: if the switched shunt
has inductors switched on, one step of inductors will be switched off; otherwise one
step of capacitors will be switched on.
An adjustment monitor is printed at the progress output device any time a step wise adjustment as
in (4) and (6) above, or the setting to the nearest discrete step as in (3b) above, occurs.
When an iterative solution process is initiated on a system which has previously been solved, the
presence of discretely operating switched shunts as described in (3b) above may result in more
than one network solution iteration being required. Although the network should have been in bal-
ance, significant voltage changes may initially be imposed as these devices are (temporarily)
switched to the continuous mode. This may be overcome by locking the switched shunts at their
present settings (see Section 4.3.12).
2. The sending end bus must not be connected by a zero impedance line to type 3 bus.
3. If it is specified, the terminal end bus must be a type one bus with exactly one in-service
AC branch connected to it; this branch must not be a zero impedance line and it must
not be in parallel with the FACTS device.
4. If it is specified, the terminal end bus must not have a switched shunt connected to it.
5. If it is specified, the terminal end bus must not be a converter bus of a DC line.
6. A bus which is specified as the terminal end bus of an in-service FACTS device may
have no other in-service FACTS device connected to it. However, multiple FACTS
device sending ends on the same bus are permitted.
7. A bus which is specified as the terminal end bus of an in-service FACTS device may
not have its voltage controlled by any remote generating plant, switched shunt, or VSC
DC line converter.
The FACTS device model is called at the start of each iteration to set the boundary conditions to be
imposed upon the AC network at the sending and terminal end buses during that iteration.
4-30 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Solution Methods
The shunt element at the sending end bus is used to hold the sending end bus voltage magnitude
to VSET subject to the sending end shunt current limit SHMX. This is handled in power flow solu-
tions in a manner similar to that of locally controlling synchronous condensers and continuous
switched shunts. In terms of the boundary conditions they impose at the buses to which they are
connected, these three devices differ only in their representation of limits: synchronous condensers
have Mvar limits; switched shunts have admittance limits; and the shunt elements of FACTS
devices have current limits. Current in the shunt-connected bridge is determined by both the shunt
Mvar output and the amount of active power transferred between the shunt and the series elements.
If the current limit is violated, sending end voltage control is abandoned and the magnitude of the
shunt Mvar output is reduced.
The series element may be set to operate in one of eight modes as described in the following
sections.
Limits on three quantities may prohibit the series element from maintaining power flow at the estab-
lished active and/or reactive power setpoints: the series voltage magnitude (maximum of VSMX);
the receiving end bus voltage magnitude (maximum of VTMX and minimum of VTMN); and the
magnitude of the active power transfer between the shunt and series-connected bridges (maximum
of TRMX). These limits result in seven possible states of the model:
1. Series voltage, receiving bus voltage, and bridge active power transfer are all treated
as dependent variables. Active and reactive power flows meet their established
setpoints.
2. Series voltage is held at VSMX; terminal bus voltage and bridge active power transfer
are both dependent variables. If possible, active power flow is maintained at its estab-
lished setpoint and reactive power flow control is abandoned; otherwise, active power
flow control is abandoned and the model attempts to hold reactive power flow at its
established setpoint.
3. Terminal bus voltage magnitude is held at either VTMX or VTMN; series voltage and
bridge active power transfer are both dependent variables. Reactive power flow control
is abandoned and active power flow is maintained at its established setpoint.
4. Bridge active power transfer is held at either TRMX or -TRMX; series voltage and
receiving bus voltage are both dependent variables. Reactive power flow control is
abandoned and active power flow is maintained at its established setpoint.
5. Series voltage is held at VSMX and receiving bus voltage magnitude is held at either
VTMX or VTMN; bridge active power transfer is a dependent variable. Both active and
reactive power flow control are abandoned.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-31
Power Flow PSS™E-31.0
About Power Flow Solution Methods Users Manual
6. Series voltage is held at VSMX and bridge active power transfer is held at either TRMX
or -TRMX; receiving bus voltage is a dependent variable. Both active and reactive
power flow control are abandoned.
7. Terminal bus voltage magnitude is held at either VTMX or VTMN and bridge active
power transfer is held at either TRMX or -TRMX; series voltage is a dependent variable.
Both active and reactive power flow control are abandoned.
Generally, the model remains in its current state until network convergence is achieved. Then
model quantities are checked to determine if a change in model state is required (i.e., if a limited
quantity can be made a dependent variable, or if a dependent variable violates its limit). If a change
of model state is applied, the power flow solution continues until convergence is again achieved,
and then the model is again tested for a change of state.
The PSS™E FACTS model will not attempt to solve for the state in which all three of the above
quantities are simultaneously held at a limit. Such a state defines an over constrained problem. In
such a system condition, the FACTS model will usually cycle among model states (5) through (7)
above. Observing the FACTS device conditions monitor via the FD interrupt control code (see
Section 4.3.1) reveals such a situation. It is the user’s responsibility to decide which of the three
limits is to be relaxed, and then make the appropriate data change.
In the IPFC model, both devices have a series element but no shunt element. The "master" device
is solved in the same manner as a series device in normal mode when the control mode is 5 or in
constant series voltage mode when the control mode is 7, except that the active power transfer is
exchanged with the series element of the "slave" device. The "slave" device is always solved with
its bridge active power transfer fixed as dictated by the "master" device; that is, when its control
4-32 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Solution Methods
mode is 6, it is always in one of solution states 4, 6, or 7. When its control mode is 8, the specified
value of series voltage is modified to reflect the active power exchange dictated by the "master".
In control mode 8 when VSREF is 1 (i.e., desired series voltage is specified relative to series cur-
rent), the specified Vd is replaced with that calculated from the active power exchange determined
by the "master" and the series current of the "slave". In control mode 8 when VSREF is 0 (i.e.,
desired series voltage is specified relative to sending end bus voltage), the specified Vd and Vq are
first transformed to the series current axis, and the resulting Vd is then replaced with that calculated
from the active power exchange determined by the "master" and the series current of the "slave".
Therefore, both devices typically have SHMX set to zero, and VSET of both devices is ignored.
TRMX of the "master" device is the maximum active power exchange between the two devices, and
TRMX of the "slave" device is set to zero. QDES of the "slave" device is ignored.
The solution of the series FACTS device in all of the above model states except the constant series
impedance mode includes the temporary insertion into the network of AC series and shunt elements
and a corresponding Norton current injection at the sending and receiving end buses of the FACTS
device. This technique can improve the convergence properties of the power flow solution. The
insertion of these dummy elements is handled automatically by the FACTS model using the reac-
tance specified as LINX. If the convergence monitor indicates an under accelerated convergence,
increasing LINX (which decreases its effect) may be helpful. When the shunt element is at a current
limit, and therefore the sending end voltage magnitude is changing from one iteration to the next,
slow network convergence may be observed with several of the model states described above.
Manually adjusting LINX can improve the convergence characteristics.
1. Convert the current limit IMAX to MVA using the present AC voltage and the base
voltage of the converter bus. If IMAX is positive, but the base voltage at the converter
bus is zero, unlimited current loading is permitted.
2. Use IMAX converted to MVA or SMAX, whichever is smaller, as the converter limit.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-33
Power Flow PSS™E-31.0
About Power Flow Solution Methods Users Manual
3. If in power factor mode, limits are checked during each power flow iteration as follows:
b. If |P + jQ| exceeds the limit from 2, reduce the magnitude of P and/or Q using PWF.
4. If in AC voltage control mode, limits are checked whenever convergence of the power
flow iteration is achieved as follows:
b. If |P + jQ| exceeds the limit from 2, reduce the magnitude of P and/or the appro-
priate Q limit using PWF.
c. If, on any iteration during which limits are checked, both converters are controlling
voltage and both are loaded beyond a limit, only the converter with the larger over-
load has its loading reduced so that it is at its limit.
d. Whenever a limit violation is detected and relieved are described above, the con-
vergence flag is reset and the power flow solution continues.
5. Whenever a converter has its active power order reduced due to a limit violation, the
active power order at the other converter is reduced accordingly.
Power orders and/or reactive power limits are reduced such that the following two equations are
simultaneously satisfied:
2 2 2
( P i + ∆P ) + ( Q i + ∆Q ) = SMAX
Thus, if PWF is 0.0, only active power is reduced; if PWF is 1.0, only reactive power is reduced;
otherwise, the above equations are applied.
One of two solution strategies is used for solving the conditions at a VSC DC line at each iteration.
The following approach is used when the following three conditions are satisfied: both converters
are in AC voltage control mode; limits are being checked on this iteration; and both converters are
overloaded.
2. Solve for the DC current using the specified DC voltage at the voltage controlling con-
verter, the active power order and the converter loss coefficients at the converter
whose overloading was relieved, and the DC line resistance.
2. Solve for the DC current using the specified DC voltage at the voltage controlling con-
verter, the active power order and the converter loss coefficients at the power
controlling converter, and the DC line resistance.
4-34 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Solution Methods
5. If a limit is violated at the voltage controlling converter, calculate a new power order for
the power controlling converter and repeat steps 1 and 2.
When an iterative solution process is invoked on a system which had previously been solved by one
of the PSS™E network solution methods, the presence of VSC converters which control AC voltage
and which are at an MVA or current limit usually results in more than one network solution iteration
being required. Although the network should have been in balance, significant voltage changes may
initially be imposed as these devices are solved with limits ignored until convergence is achieved.
1. Swing bus.
While more than one type 3 bus may be present in an island, this is generally not recommended. It
is the user’s responsibility to coordinate their phase angle settings when multiple swing buses are
present in an island. Further, care must be taken in the use of the "flat start" option of the power
flow solution activities, which always sets the phase angles of all buses, including type 3 buses, to
zero degrees.
The following setpoint mode voltage controlling devices may be modeled in PSS™E:
• An in-service generating plant at a type 2 bus may control either local bus voltage or
the voltage at a remote bus.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-35
Power Flow PSS™E-31.0
About Power Flow Solution Methods Users Manual
• A switched shunt for which MODSW is 1 or 2 at a type 1 or 2 bus may control either
local bus voltage or the voltage at a remote bus to a voltage setpoint. Such switched
shunts for which MODSW = 1 (i.e., discrete control) are initially treated as continuous,
then moved to the nearest step and locked.
• A voltage controlling converter of a VSC DC line at a type 1 or 2 bus may control either
local bus voltage or the voltage at a remote bus. To be a voltage controlling converter,
the VSC DC line must be in-service (MDC = 1), the converter must be in-service
(TYPE = 1 or 2), and the AC control mode must be set for voltage control (MODE = 1).
• The shunt element at the sending end of an in-service FACTS device at a type 1 or 2
bus may control local bus voltage.
When multiple voltage controlling devices control the same bus voltage, the reactive power require-
ments are shared among the controlling devices in proportion to their RMPCTs, subject to each
device’s reactive power, current or admittance limits, as appropriate. The Mvar output of each device
controlling the voltage at bus "I" is set to the product of the total Mvar required at all devices controlling
the voltage at bus "I" times a fraction; the numerator of this fraction is RMPCT of the device and the
denominator is the sum of the RMPCTs of all the devices controlling the voltage at bus "I". It is the
responsibility of the user to ensure that voltage control specifications for all the setpoint mode
devices controlling the same bus voltage are identical, and that the RMPCT values are such that
the desired reactive power sharing is obtained.
When multiple setpoint mode voltage controlling devices are present at a bus, they should normally
all be specified with the same voltage control objective. Similarly, when multiple setpoint mode
voltage controlling devices are present among a group of buses connected together by zero imped-
ance lines, the same voltage control objective should be specified for all of them. (Recall that buses
connected together by zero impedance lines are treated as the same bus during power flow solu-
tions; see Section 3.2.5.1)
When one or more devices are controlling the voltage at a remote bus, any setpoint mode voltage
controlling devices at the controlled bus should be specified so as to control local bus voltage.
Other than generation at the bus itself, setpoint mode voltage controlling devices at type 3 buses
and at buses connected to type 3 buses through zero impedance lines may not be used for voltage
control purposes. Such devices are handled as follows by the power flow solution activities:
• A zero impedance line connected generating plant is held at its present active and
reactive power output.
• A local or zero impedance line connected switched shunt controlling to a voltage set-
point is locked at its present admittance.
• A local or zero impedance line connected VSC DC line is blocked.
• A local or zero impedance line connected FACTS device is blocked.
Section 4.4.5.6 describes how to check for suspect or erroneous voltage control specifications.
4-36 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Solution Methods
The following band mode voltage controlling devices may be modeled in PSS™E:
• A switched shunt for which MODSW is 1 at a type 1 or 2 bus may control either local
bus voltage or the voltage at a remote bus to a voltage band.
• A switched shunt for which MODSW is 3 at a type 1 or 2 bus may control the reactive
power output of a generating plant to fall within a reduced reactive power limit band.
• A switched shunt for which MODSW is 4 at a type 1 or 2 bus may control the reactive
power output of a voltage controlling VSC DC line converter to fall within a reduced
reactive power limit band.
• A switched shunt for which MODSW is 5 at a type 1 or 2 bus may control the admittance
setting of a remote switched shunt to fall within a reduced reactive admittance limit
band.
• A transformer may have its winding one turns ratio adjusted to hold the voltage at a
designated bus within a specified band.
• The terminal end of an in-service FACTS device at a type 1 or 2 bus may deviate from
its desired power setpoints to keep the voltage at the terminal end bus within a speci-
fied band.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-37
Power Flow PSS™E-31.0
About Power Flow Solution Methods Users Manual
4-38 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Solution Methods
Alternatively, the solution can be launched using the Solve button. This will open the same
dialog shown in Figure 4-21, or will automatically invoke the previously used solution method
without offering the selection dialog.
Following selection of any or all Solution Options and/or Area Interchange Control options (see
Section 4.3.12), the solution is initiated by clicking the Solve button in the dialog.
If the load flow solution network connectivity checking option is enabled (see Section 1.6.4), a check
is made to confirm that each non type four bus is connected back to a type three (swing) bus
through the in-service AC network. If any violations are detected, an appropriate message is printed
and the solution is terminated.
At the completion of each iteration, a convergence monitor is shown in the Output Bar. The monitor
tabulates:
3. The number, name and base voltage of the bus experiencing the largest voltage
change; alternatively, if the bus is the star point bus of a three-winding transformer, the
transformer name followed by "* BUS" is printed.
At completion of the solution or exhaustion of the allowable number of iterations, the largest bus
mismatch is tabulated, along with the system total MVA mismatch and a summary of swing (type
three) bus power outputs. An asterisk ("∗") following a machine’s active or reactive power output in
the swing bus summary indicates that the power output is beyond its limits.
The Gauss-Seidel solution method has five available solution control parameters:
• ACCP - Acceleration factor for the real part of the voltage adjustment.
• ACCQ - Acceleration factor for the imaginary part of the voltage adjustment.
• TOL - Convergence tolerance in pu.
• ITMX - Default limit on number of iterations. (= 100)
• BLOWUP - Largest voltage change threshold.
Both acceleration factors have default values of 1.6, but ACCP need not be equal to ACCQ. The
guide to the tuning of the acceleration factors should be:
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-39
Power Flow PSS™E-31.0
About Power Flow Solution Methods Users Manual
The acceleration factors should never be set greater than two, and the optimum seldom exceeds
about 1.8. Although the acceleration must be tuned to the system for optimum performance, devi-
ations from the optimum values do not have a dramatic effect on the number of iterations required.
At the completion of each iteration, the largest voltage change is checked against the "blowup" tol-
erance, BLOWUP, which has a default value of 5.0 pu. If the largest change exceeds this tolerance,
an appropriate message is printed and the solution is terminated.
The voltage convergence tolerance default is 0.0001 pu. This tolerance applies to the largest
voltage change each iteration, and convergence is assumed when the magnitude of the largest bus
voltage change is less than this tolerance. Reducing the tolerance as low as 0.00001 pu is permis-
sible to achieve reduced node mismatches, but such a small tolerance is not recommended since
the convergence of the Gauss-Seidel method becomes very slow as the voltage changes fall below
about 0.0001 pu.
The user may modify any of these solution parameters by launching the Solution Parameters dialog
(see Figure 4-22) from the Power Flow>Solution>Parameters… option. On the Gauss tab,
changes can be made to the acceleration factors, ACCP/ACCQ, and the TOL and ITMX parame-
ters. The BLOWUP parameter is available on the General tab (see Figure 4-22).
4-40 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Solution Methods
The acceleration factor ACCM is used only for the Modified Gauss-Seidel method.
The General solution parameters are independent of the type of iterative solution. In addition to the
BLOWUP parameter, previously described, they are:
• PQBRAK – This is the voltage level below which the load characteristic will change
from constant MVA to an elliptical current-voltage characteristic. (see Section 4.2.4.1).
• THRSHZ – This is the threshold reactance for branches below which they will be
treated as zero impedance lines. (see Section 3.2.5.1)
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-41
Power Flow PSS™E-31.0
About Power Flow Solution Methods Users Manual
• ADJTHR – When tap adjustment is enabled for the Gauss-Seidel and the Full Newton-
Raphson solutions, those transformers controlling voltage are checked for adjustment
whenever the largest voltage magnitude change in per unit on the previous iteration is
less than the automatic adjustment threshold tolerance, ADJTHR. When using the
decoupled and fixed slope decoupled Newton-Raphson solutions, this adjustment
check occurs following any "P-angle half iteration" in which the largest voltage phase
angle change in radians is less than ADJTHR.
• ACCTAP – This is a tap movement deceleration factor. The voltage error, for a voltage
controlling transformer is multiplied by ACCTAP. If ACCTAP is set less than its default
value of 1.0, the apparent voltage error is reduced and the number of tap changes
occurring during the iterative process is reduced.
• TAPLIM – The solution parameter TAPLIM, which has a default value of 0.05, defines
the maximum ratio change that may be applied to a transformer during any adjustment
calculation. If the tap STEP of a transformer exceeds TAPLIM and the controlled
voltage is outside of its voltage band, the ratio is changed by one tap STEP.
Reducing ACCTAP and/or TAPLIM below their default values may be beneficial on systems
with a high concentration of Load Tap Changers or whose voltage profile is extremely sensi-
tive to tap settings.
2. The presence of very low impedance branches (e.g., jumpers with an impedance of
j0.0001 pu) which are not being treated as zero impedance lines often results in slow
convergence as the voltage adjustments get small, and in mismatches at the buses
involved.
3. The number of iterations required to reach the convergence tolerance increases as the
system size increases.
6. Is tolerant of data errors and insoluble conditions in local areas of the network. It is gen-
erally well converged everywhere except in the problem areas.
4-42 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Solution Methods
Although the Modified method uses the same acceleration factors, ACCP and ACCQ, at type two
buses as does the standard Gauss method, at type one buses, it uses a separate acceleration
factor, ACCM, which has a default value of unity. The principles for setting ACCM are the same as
outlined in Section 4.3.7.1 for setting ACCP and ACCQ. The convergence of activity MSLV is, how-
ever, very much more sensitive to the value of ACCM than the standard Gauss solution is to the
values of ACCP and ACCQ. Changing ACCP and ACCQ by 0.05 has very little effect on the con-
vergence of either Gauss-Seidel solution but the same change in ACCM may cause a major change
in the convergence properties of the Modified solution. Typical values for ACCM range from about
1.2 for well-behaved systems without series capacitors down to slightly below unity in difficult cases
with series capacitors.
The solution parameters designating the maximum number of iterations, the convergence toler-
ance, the acceleration factors (including ACCM), and the blowup threshold can be changed using
the same menu facility used for the standard Gauss solution method. (see Section 4.3.7.1).
1. The presence of negative reactance branches connected to type two or three buses
usually causes divergence.
2. Series capacitors may be represented between type one buses, as long as the level of
compensation does not exceed about 80%.
3. The presence of very low impedance branches (e.g., jumpers with an impedance of
j0.0001 pu) which are not being treated as zero impedance lines often results in slow
convergence as the voltage adjustments get small, and in mismatches at the buses
involved.
4. The number of iterations required to reach the convergence tolerance increases as the
system size increases.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-43
Power Flow PSS™E-31.0
About Power Flow Solution Methods Users Manual
7. Is tolerant of data errors and insoluble conditions in local areas of the network. It is gen-
erally well converged everywhere except in the problem areas.
8. The rate of convergence is very sensitive to the tuning of the acceleration factor ACCM.
Modest deviation from the optimum value may result in poor convergence
characteristics.
9. The Modified solution takes somewhat more time per iteration than does the standard
Gauss-Seidel solution but generally requires fewer iterations.
4-44 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Solution Methods
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-45
Power Flow PSS™E-31.0
About Power Flow Solution Methods Users Manual
Alternatively, the solution can be launched using the Solve button. This will open the same
selector dialog as shown in Figure 4-23, or it will automatically invoke the previously used
solution method without offering the selector dialog.
For the Newton solution options, differences from the Gauss method are shown in Figure 4-23.
They are:
The Newton-Raphson solutions handle the network connectivity checking option, flat start solution,
and load, generator, switched shunt, FACTS device, and DC line boundary conditions in the same
way as do the Gauss-Seidel solutions. In addition to the interrupt control codes recognized by the
Gauss-Seidel solution methods, however, the NC interrupt control code may be used to suppress
the incorrect var limit tabulation printed at the termination of a Newton-Raphson solution (see
Section 4.3.1).
The FACTS device monitor, DC transmission line monitors, largest mismatch tabulation, and swing
bus summary are identical to those provided by the Gauss-Seidel solution method.
4-46 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Solution Methods
• Apply automatically: Reactive power limits are to be ignored until the largest reactive
power mismatch has been reduced to a preset multiple of the convergence tolerance.
• Apply immediately: Reactive power limits are to be recognized on the first mismatch
calculation, preceding the first iteration.
• Ignore: Reactive power limits are to be ignored at all type two buses except those for
which the upper and lower limits are equal.
• Apply at: Reactive power limits are to be applied either on iteration number "n" or when
the largest reactive power mismatch is within a preset multiple of the tolerance, which-
ever occurs first.
The var limit logic of this solution method contains code to prevent the phenomenon of a setpoint
mode voltage controlling device oscillating on and off a limit from one iteration to the next, or
between high and low limits from one iteration to the next. This is accomplished by "looking back"
to check the reactive power requirement and voltage magnitude on the previous iteration. Conse-
quently, since the logic presumes the existence of a previous iteration for the conditions in the
working case, the immediate application of generator reactive power limits should be specified only
when continuing the solution of the system in the working case from a previous Gauss-Seidel or
Newton-Raphson solution.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-47
Power Flow PSS™E-31.0
About Power Flow Solution Methods Users Manual
The application of generator reactive power limits on the first iteration following a network change
may cause setpoint mode voltage controlling devices to be spuriously placed on a limit (e.g., a gen-
erator’s reactive power set at the low limit but voltage magnitude less than scheduled voltage).
Activity FNSL prints a summary of any such voltage controlling devices at the progress output
device prior to returning control back to the activity selector.
The reactive power component limits of voltage controlling switched shunts, VSC converters, and
shunt elements of FACTS devices are always recognized.
The user may modify any of these solution parameters by launching the Solution Parameters dialog
(see Figure 4-26) from the Power Flow>Solution>Parameters… option. The available solution
parameters are:
4-48 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Solution Methods
The Newton-Raphson solution methods apply an acceleration factor, ACCN, to the voltage adjust-
ments made at setpoint mode voltage controlled buses. This is done to overcome the stability
problems that can arise when the Newton method encounters reactive power limits. The normal
value of this acceleration factor is unity, but in cases exhibiting oscillatory convergence, it may occa-
sionally be advantageous to decrease the acceleration factor. It will rarely, if ever, be advantageous
to set this acceleration factor greater than unity.
The Newton-Raphson solutions scale down the voltage magnitude and voltage angle change vec-
tors if the most negative element of the "∆vmag / vmag" vector is less than or equal to -1.0. A more
restrictive limit on the size of the largest voltage magnitude change which may be applied on any
single iteration is provided by the solution parameter DVLIM; the element of the "∆vmag / vmag"
vector with the largest magnitude is checked against DVLIM, and, if it exceeds DVLIM, the change
vectors are scaled down such that the largest voltage magnitude change applied is of magnitude
DVLIM. The default value of DVLIM is 0.99; reducing it to as low as 0.05 may improve convergence
properties in difficult cases.
At the completion of the first iteration, the largest "∆vmag / vmag" change is checked against a
"blowup" tolerance, BLOWUP, which has a default value of 5.0 pu; on subsequent iterations, the
largest phase angle change as well as the largest voltage magnitude change are checked. The
unscaled change vectors are used in the "blowup" check; i.e., the "blown up" condition is deter-
mined before any scaling down of the change vectors, as described in the preceding paragraph, is
applied. If the largest change exceeds the "blowup" tolerance, an appropriate message is printed
and the solution process is terminated. The "blowup" check is bypassed in the non-divergent
Newton power flow solution (see Section 4.3.9.7).
The Newton-Raphson solutions have a default limit of 20 iterations (ITMXN). The tolerance, TOLN,
applies to the largest bus mismatch during each iteration. Convergence is assumed when no active
or reactive component of bus mismatch exceeds the tolerance. The default tolerance is 0.1 MW and
Mvar, (0.001 pu on 100 MVA base) but a tolerance as large as 1 MW and Mvar can give acceptable
power flow solutions for many purposes.
1. No active or reactive component of bus mismatch exceeds the bus power mismatch
convergence tolerance and all FACTS devices are satisfactorily solved.
3. The non-divergent solution option is disabled and the "blown up" condition is detected.
4. The non-divergent solution option is enabled and applying the current iteration’s
change vectors does not significantly reduce the system mismatch level.
6. A diagonal element of the Jacobian matrix is near zero, indicating a singular matrix.
The following rules and convergence characteristics apply to Newton-Raphson solution methods
but consideration should be given to the non-divergent solution (see Section 4.3.9.7):
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-49
Power Flow PSS™E-31.0
About Power Flow Solution Methods Users Manual
3. The presence of very low impedance branches (e.g., jumpers with an impedance of
j0.0001) which are not being treated as zero impedance lines (seeSection 3.2.5.1) may
result in the inability of the Newton-Raphson to reach the default convergence toler-
ance. Even with such a network, the solution is usually capable of reducing the largest
bus power mismatch to less than 0.2 MVA.
7. Applying generator reactive power limits "too soon" may cause the solution to diverge.
8. The solution is intolerant of data errors and insoluble conditions in local areas of the
network.
9. When the solution diverges, it often fails catastrophically, giving no indication of where
the problems are.
10. The Newton-Raphson solutions require the optimal ordering of network nodes. If a new
ordering requirement is detected, a message is printed, and the ordering process is
automatically executed at which point the solution continues.
11. The time per iteration of the solution is longer than that required for other power flow
solution activities, but few iterations are usually needed.
The solution convergence monitor is similar to that of the fully coupled solution. Each iteration is
identified in the ITER column with its main iteration number, followed by a decimal point, followed
by either a zero (for the angle correction calculation) or a five (for the voltage magnitude correction
calculation), see Figure 4-27.
4-50 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Solution Methods
The rules and characteristics governing the use of the decoupled solution are similar to those of the
fully coupled solution. In addition to those rules, the following apply:
1. The decoupled solution converges well if fairly uniform X/R ratios are present
throughout the network.
2. When the network contains branches with resistance close to or greater than the reac-
tance, the iteration usually reaches some mismatch level and then begins to diverge,
usually slowly.
4. The time per "half iteration" in the decoupled solution is roughly 1/4 of the time per fully
coupled iteration.
The method employs an approximation of the Jacobian matrix which is insensitive to bus voltages.
Thus the matrix used in the active power-angle solution remains fixed throughout the solution, while
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-51
Power Flow PSS™E-31.0
About Power Flow Solution Methods Users Manual
the matrix used for the reactive power-voltage calculation changes only as voltage controlled buses
switch between voltage regulating and reactive power limited boundary conditions.
The solution convergence monitor is similar to that of the decoupled solution. Each iteration is iden-
tified in the ITER column with its main iteration number, followed by a decimal point, followed by
either a zero (for the angle correction calculation) or a five (for the voltage magnitude correction
calculation).
In addition to those rules enumerated for the fully coupled solution, in Section 4.3.9.3), the following
apply:
1. The fixed slope decoupled solution is much less sensitive to a poor initial voltage esti-
mate than is the fully coupled solution.
2. As the mismatches are reduced, the rate of improvement on successive iterations may
be slowed.
3. The time per "half iteration" with the fixed slope solution is roughly 1/5 of the time per
fully coupled iteration. The "start-up" time is longer as the fixed matrices are calculated.
• Bus power mismatches for all buses are within tolerance ("convergence").
• Increasing bus power mismatches, and usually increasing voltage and angle changes,
are observed on successive iterations ("divergence"). A divergent solution is often
characterized by unrealistically small or large voltage magnitudes and by very large
bus power mismatches; it may be characterized by a Jacobian matrix that is singular
or nearly so.
• Mismatch tolerances are not met, but the solution is neither converging nor diverging
("non-convergence"). This condition could be caused by a convergence tolerance
which is beyond the precision limits of the combination of host computer and network
impedances; it could also result from control ranges which are too narrow relative to
the adjustment step (e.g., desired voltage range used by a voltage controlling trans-
former relative to the tap step) which results in oscillation of the controlling parameter
from one adjustment cycle to the next (e.g., tap ratio increasing, then decreasing, then
increasing, and so on), or by multiple controlling devices "fighting" each other.
The non-divergent Newton power flow solution option attempts to terminate the iterative procedure
before divergent iterations have driven the voltage vector to a state where large power mismatches
and unrealistic voltages are present. The resulting voltage vector, although not sufficiently accurate
to provide a "converged" power flow solution, often provides a relatively good indication of the state
of the network. In particular, voltage collapse situations can be identified by localized areas of bus
power mismatches and low voltages, with the remainder of the network "converged".
The Non-divergent Solution option may be applied in the Fully Coupled and the Fixed Slope Decou-
pled Newton solutions. It also finds use in Automatic AC Contingency analysis (see Chapter 5). The
Non-divergent solution option is selected in the Loadflow solutions dialog on the Newton tab (see
Figure 4-28).
4-52 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Solution Methods
The application of the Newton method to the power flow problem calculates a pair of change vec-
tors: ∆θ for voltage phase angles, and ∆vmag / vmagold for bus voltage magnitudes. In its usual
application, the bus voltages are updated using equations which may be written in the form:
In the non-divergent solution scheme, ACCFAC is set to 1.0 at the start of each Newton iteration. If
the mismatches that result from the new voltage and angle vectors indicate divergence, the value
of ACCFAC is halved, θnew and vmagnew recalculated, and mismatches recalculated. This process
is repeated until either:
• the indication of divergence is eliminated. In this case, the solution advances to its next
iteration.
• ACCFAC has been reduced to a near zero value without eliminating the indication of
divergence. In this case, the solution is terminated.
The divergence metric used in this "inner loop" voltage correction is the sum of squares of the MVA
mismatches, expressed in per unit, at all in-service buses in the working case (SUMSQM). The non-
divergent algorithm infers the elimination of divergence when the SUMSQM resulting from the appli-
cation of a set of voltage magnitude and phase angle corrections is less than the SUMSQM at the
start of the iteration multiplied by the improvement factor NDVFCT. That is, a new set of voltages
is accepted if:
Up to ten "inner loop" mismatch calculations are performed, and if SUMSQM has not improved suf-
ficiently by the last attempt (with ACCFAC approximately 0.00195), the solution is terminated. The
voltage vector is set to either its value at the completion of the prior Newton iteration, or to the value
corresponding to the last "inner loop" mismatch calculation, whichever has the smaller value of
SUMSQM.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-53
Power Flow PSS™E-31.0
About Power Flow Solution Methods Users Manual
LARGEST MISMATCH: 495.60 MW 1025.72 MVAR 1139.18 MVA AT BUS 205 [SUB230 230.00]
SYSTEM TOTAL ABSOLUTE MISMATCH: 7280.85 MVA
LARGEST MISMATCH: 23.16 MW 5.59 MVAR 23.83 MVA AT BUS 205 [SUB230 230.00]
SYSTEM TOTAL ABSOLUTE MISMATCH: 93.62 MVA
4-54 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Solution Methods
A simple approach is to allow a Gauss-Seidel solution to complete its maximum iterations and then
select a Newton method and continue the solution from the same convergence point. (The starting
voltage estimate for the Newton solution would be the last voltage vector estimated in the preceding
execution of the Gauss solution.) At any time the solution can be changed back to a Gauss-Seidel
solution or a different Newton method.
If the iterations are slow, it is possible to use the AB interrupt to cancel whichever solution method
is in progress and, subsequently, select a different solution method to continue.
The four acceleration factors listed in Table 4-3 are saved and retrieved with the power flow case.
The power flow working case contains two tolerance values for use in convergence checking: a
voltage change threshold for the Gauss-Seidel solutions, and a bus power mismatch tolerance for
the Newton-Raphson solutions. These tolerances are set to default values of 0.0001 per unit and
0.001 per unit, (or 0.1 MW and Mvar on a 100 MVA system base) respectively, when PSS™E is
started up.
The convergence and tolerance data can be changed via the Power Flow>Solution>Parame-
ters… option which opens up the Solution Parameters dialog. Figures 4-30 and 4-31 show the
dialog open at the Newton and Gauss tabs respectively.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-55
Power Flow PSS™E-31.0
About Power Flow Solution Methods Users Manual
ACCP and ACCQ values less than unity are perfectly permissible and will be required to
achieve convergence in some difficult cases. The acceleration factor should never be set
greater than 2, and the optimum value seldom exceeds about 1.8.
The normal tolerance value for the Gauss-Seidel solution is 0.0001 per unit. This tolerance is
applied to the largest voltage change in each iteration and convergence is assumed when |∆V| is
less than this tolerance. The tolerance may be increased as far as 0.0005 per unit if only approxi-
mate power flows are needed. Reducing the tolerance as low as 0.00001 per unit is permissible to
achieve reduced node mismatches, but such a small tolerance is not recommended because the
convergence of the Gauss-Seidel method becomes very slow as the voltage changes fall below
about 0.0001 per unit.
4-56 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Solution Methods
Largest
|DV|
Under accelerated
ACCN Factor Should
be Increased
Over accelerated
ACCN Factor Should
be Decreased
Optimum
Acceleration
Iteration Number
The Modified solution uses the Gauss-Seidel acceleration factors ACCP and ACCQ at Type 2
buses and a separate acceleration factor, ACCM at Type 1 buses. The principles for setting ACCM
are the same as outlined above for setting ACCP, ACCQ. The convergence of the Modified solution
is, however, very much more sensitive to the value of ACCM than is the standard Gauss-Seidel
solution to the values of ACCP and ACCQ. Changing ACCP, ACCQ by 0.01 has very little effect on
the convergence of either Gauss solution but the same change in ACCM may cause a major
change in the convergence properties of the Modified version. Typical values for ACCM range from
about 1.2 for well-behaved systems without series capacitors down to slightly below unity in difficult
cases with series capacitors.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-57
Power Flow PSS™E-31.0
About Power Flow Solution Methods Users Manual
Convergence is assumed when no real or reactive component of bus power mismatch exceeds the
tolerance. The typical tolerance value for Newton methods is 0.001 per unit (0.1 MW on 100-MVA
base), but a tolerance as large as 0.01 per unit will give very acceptable power flow solutions for
many purposes.
The Newton solutions might not be able to reduce mismatch to the 0.001 per-unit value because of
the inherent computer precision limit.
Consider a branch with impedance of 0.0001 per unit and voltages close to unity at both ends. The
maximum imprecision in calculation of power flow through the branch is approximately:
∆V
∆P = 2 -------- = 0.0025 per unit
Z
Since the bus mismatch imprecision is the sum of the imprecisions in flows into connected
branches, a power flow case including such low-impedance branches is unlikely to reach the default
tolerance of 0.001 per unit.
Branch impedances as low as 0.0001 per unit do not occur frequently, but can arise in star-equiv-
alents of three-winding transformers and are sometimes used to represent jumpers between bus
sections. When these low-impedance branches exist in a power flow case, it is often advisable to
raise the zero-impedance branch threshold to represent these branches as zero-impedance lines
and then remove the low-impedance branches by "joining" the terminal buses of the branch
together. (This topological manipulation is described in Section 4.6.4). An alternative is to increase
the tolerance to 0.0025 or 0.005 per unit.
A tolerance of 0.005 per unit on a 100-MVA system base represents a power flow solution impreci-
sion of 0.5 MW, which is more than acceptable for the great majority of power flow cases.
Alternatively the same adjustments can be enabled or disabled (to override the program run-time
options), in the Loadflow Solutions dialog which is opened from the Power Flow>Solution>Solve
option, (see Figure 4-21, for the Gauss solutions and Figure 4-23 for the Newton solutions). The
Loadflow Solution dialog for the Newton solution is replicated in Figure 4-33.
4-58 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Solution Methods
Figure 4-33. Solution Options and Adjustments for the Newton Solutions
The automatic adjustments available are specified in Table 4-4. In addition to the options listed in
the table, the user has the option to start the power flow solution from a flat-start, as seen in
Figure 4-33.
When enabled, an adjustment option is applied throughout the entire power flow case. However, it
is important to recognize that the adjustment of any individual tap-changing transformer, phase
shifter, or area net interchange can be suppressed by editing its adjustment parameters in such a
way that no adjustment can occur. Those parameters are accessible in the spreadsheet.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-59
Power Flow PSS™E-31.0
About Power Flow Solution Methods Users Manual
With all solution activities, the request to adjust taps ratio automatically will not be honored until the
voltage change is less than the adjustment threshold (ADJTR), a solution parameter with a default
value of 0.005 per unit. With discrete tap adjustment, tap ratio will then be adjusted to a maximum
of value of tap limit (TAPLIM), a solution parameter with a default value of 0.05 per unit, until toler-
ance is reached. With direct tap adjustment controlling voltage, tap ratio will be adjusted, as if the
taps are continuous, from the iteration when tolerance is first reached through subsequent iterations
until the tolerance is again reached. At that time, unless the tap ratio is zero, all taps will be set to
the nearest step, locked, and additional iterations made to bring mismatch down to tolerance once
again. Similarly, with direct tap adjustment controlling Mvar, adjustment will not be made until toler-
ance is reached and controlling logic is identical thereafter to that of direct tap adjustment controlling
voltage.
The solution parameters ADJTR and TAPLIM can be changed in the Solution Parameters
dialog, on the General tab, as previously shown in Figure 4-14.
4-60 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Solution Methods
where:
The tap-step ratio should be properly coordinated with the acceptable voltage band (VMAX-VMIN)
because the discrete steps of available tap ratio are recognized. The default tap-step ratio is
0.00625 per unit (0.625%). The band between VMAX and VMIN should normally be twice the
transformer tap-step. A band of 2% is recommended for the normal case of 0.625% tap ratio steps.
A value of 0 for tap-step should only be used to indicate continuously adjustable taps to the direct
tap adjustment algorithm.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-61
Power Flow PSS™E-31.0
About Power Flow Solution Methods Users Manual
Phase-shift adjustment is continuous and all adjustable phase shifters are adjusted simultaneously
whenever the regulated real power flow of at least one of them falls outside its scheduled band. An
unduly narrow band can cause non convergence of the power flow solution. A reasonable band is
± 5 MW of the target flow.
Converter taps are adjusted only until the corresponding bridge firing angles are between their
specified maximum and minimum values; taps are not adjusted to minimize firing angles once they
fall between their corresponding maxima and minima. Accordingly, the ranges of the bridge firing
should be treated as the optimum bands for the various converters, with recognition that operation
at a firing angle above the specified maximum value may be necessary for some combinations of
scheduled DC power, DC voltage, and AC system conditions.
The AC solution options can be modified such that the adjustment of converter transformer ratios
are disabled. This disabling applies to all DC transmission lines. Selective locking of DC converter
transformer taps requires that their adjustment not be disabled via the AC solution options. The tap
ratio of any individual converter transformer can be locked by using the program’s data editing func-
tions to set the DC converter tap limits and tap ratio equal to the desired value.
The net interchange tolerance should be related to system interchange capability and system
impedances. A typical tolerance for a large electric utility with capability for a 500 MW net inter-
change might be 10 MW, while an industrial plant with a maximum net interchange capability of 15
MW might be assigned a tolerance of 0.5 MW. The tolerance should be set in relation to interchange
capability and remain fixed as the interchange schedule is varied.
4-62 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual About Power Flow Solution Methods
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-63
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
Table 4-6 summarizes the available power flow reports and subsystems by which they can be
limited.
Power flow results can be provided either in a tabular format or in a graphical format using the one-
line slider format.
In the tabular format, power flow output reports may be organized either numerically by ascending
bus number, or alphabetically by bus name. Selection of ordering by numbers or names is made in
the Program Settings (see Section 1.6.4.) where either the Number output option, or the Extended
Name output option may be chosen. Changing between the Number and Extended Name input
options has no effect on the ordering of power flow reports.
4-64 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
All reports, except those selected by the AREA, ZONE and OWNER criteria, are made with buses
appearing in pure numeric or alphabetic order. Power flow results reports selected by these criteria
order the buses numerically or alphabetically within groupings. As an example, if output is selected
by AREA, with areas 2 and 6 selected, the report will list all buses in area 2 first and then all buses
in area 6.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-65
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
The Bus Based Reports dialog shows options for selection of the "standard" output or a "Wide
Format" output with or without the inclusion of branch and equipment currents (amperes) in the tab-
ulation. The lower half of the dialog allows selection of output by Area, Zone, Owner, Base kV, Bus
or any combination of those selection criteria.
The second line contains the bus voltage in kV if a base voltage was specified for the bus, followed
by the MW and Mvar headings for the losses column. In addition, if the bus is a generator bus, the
line contains the identifier GENERATION at the beginning and the plant active power, reactive
power, and MVA output under the appropriate headings. This is followed by the percent MVA
loading of the plant based on total plant MBASE. The plant reactive power output is followed by a
single character flag, where "H" indicates that the plant reactive power output is at or beyond the
total plant upper reactive power limit, "L" indicates that it is at or below the total plant lower reactive
power limit, and "R" indicates that it is within limits.
Only plant conditions are tabulated. If more than one machine is modeled at the plant, indi-
vidual machine conditions may be examined using the range checking facilities described in
Section 4.4.5.
4-66 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
The first two lines for each tabulated bus are followed in turn by:
In Figure 4-36, on Bus 152, it can be seen that there are three connected loads, of different char-
acteristics, and an 800 Mvar shunt capacitor. The capacitor is injecting 930 Mvar into the bus
because of the elevated voltage at the bus (1.0782 pu).
For each FACTS device for which the bus being reported is the sending end bus of an IPFC
"master" or "slave" device, the following data pertaining to the device’s active power transfer to its
companion IPFC device is printed:
1. An identifier indicating the type of the companion IPFC device ("IPFC MASTER" or
"IPFC SLAVE").
2. The FACTS device number; this is printed in the circuit identifier column.
3. The active power flowing to the companion IPFC device. If the bus being reported is
the IPFC "master" and the active power transfer is being held at its limit, its value is
followed by the tag "HI".
Except for IPFC devices for which SHMX is 0.0, for each FACTS device for which the bus being
reported is the sending end bus, the following data pertaining to the device’s shunt element are
printed:
1. An identifier indicating the type of FACTS device shunt element and/or active power
transfer being reported ("STATCON", "SSSC SHUNT", "UPFC SHUNT", or "IPFC
SHUNT").
2. The FACTS device number; this is printed in the circuit identifier column.
3. Unless the device being reported is an IPFC, the active power being exchanged
between the shunt and series element. If the active power is being held at its limit, its
value is followed by the tag "HI".
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-67
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
5. The MVA corresponding to the active and reactive powers in (3) and (4) above, and the
percent loading on the shunt element.
If the FACTS device contains a series element, the following data pertaining to it is printed in the
output blocks of its sending and terminal end buses:
1. The number, name, and base voltage of the other endpoint bus ("to bus").
2. The FACTS device number; this is printed in the circuit identifier column.
3. The power flowing into the series element along with its percent loading at the "from
bus" end.
4. The magnitude and phase of the series voltage. If the series voltage magnitude is being
held at its limit (control modes 1, 5 and 6) or if the series voltage magnitude exceeds
VSMX (control modes 2, 3, 4, 7 or 8), its value is followed by the tag "HI". Otherwise,
the tag "RG" is printed.
5. The FACTS device losses calculated as the algebraic sum of the reactive power
flowing into the series device from its endpoint buses.
6. The numbers and names of the area and zone in which the other endpoint bus ("to
bus") resides.
7. An identifier indicating the type of FACTS device being reported ("SSSC", "UPFC", or
"IPFC").
In Figure 4-36, it can be seen that on Bus 153, listed immediately after the 200 MW constant imped-
ance load, there is a STATCON (identified as FACTS Device #1) absorbing 50 Mvar.
The following data is printed in the output block of each two-terminal and multi-terminal DC line con-
verter bus:
1. For two-terminal lines, the number, name, and base voltage of the other converter ter-
minal bus ("to bus"). For multi-terminal lines, the identifier "MULTI-TERMINAL DC".
4. The converter transformer off-nominal turns ratio, TAPR (or TAPI), followed by a two-
character tag, which is either "HI" or "LO" if the ratio is at its high or low limit, respec-
tively; "LK" if DC taps were locked during the last power flow solution activity, or if an
4-68 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
5. The value of converter angle followed by one of the tags "RG", "HI" or "LO" if the angle
is within its limits, at or above its nominal high limit, or at or below its steady-state low
limit, respectively.
6. DC line losses calculated as the algebraic sum of the powers flowing into the line from
its converter buses.
7. For two-terminal lines, the numbers and names of the area and zone in which the other
converter bus ("to bus") resides. For multi-terminal lines, the numbers and names of
the area and zone in which the "DC bus" to which the AC converter bus is connected
resides.
8. The identifier "RECTIFIER" (or "INVERTER"), which refers to the "from bus".
Figure 4-37 shows the output listing at a 765 kV Bus (1600) where there is a Generator (3,000 MW)
feeding the rectifiers on the two DC lines to the 18 kV Buses 1403 and 1404. Each line is transmit-
ting 1,500 MW. (Note that the LOSSES, AREA and ZONE columns are not shown.)
The converter transformer tap on DC line #1 is at its high limit (HI) and the firing angle, alpha is at
9.33o, within its range (RG). On line #2, both the converter transformer and the firing angle are
within regulating range (RG).
In Figure 4-38 output for the inverter at Bus 1404 can be seen. It shows only 1435.9 MW arriving
from the rectifier at Bus 1600, the converter transformer taps are locked (LK) and the firing angle,
gamma, is at or above its high limit (HI) of 20o.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-69
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
For a bus with a VSC DC line connected to it, the following data is printed in the output block:
1. If the other converter terminal is in-service, the number, name, and base voltage of the
other converter terminal bus ("to bus"), followed by the tag "VSC" in the circuit identifier
column. If the other converter terminal is out-of-service, "VSC CONVERTER" is printed
in these columns.
3. The percent of MVA rating, where the rating is taken as the more restrictive of IMAX
converted to MVA and SMAX.
4. DC line losses calculated as the algebraic sum of the powers flowing into the line from
its converter buses.
5. The numbers and names of the area and zone in which the other converter bus resides
if the other converter terminal is in-service; if it is out-of-service, these columns are left
blank.
For three-winding transformers, the output line contains the string "3WNDTR" in the bus number
column, the transformer name in the bus name column, and the winding number in the base voltage
column, followed by the transformer circuit identifier.
The active and reactive power flow on the branch is printed as power leaving the "from bus" (i.e.,
positive for outgoing and negative for incoming); MVA flow is also printed. The percent current
loading, based on the rating set established as the default rating in the run time options is then
printed (see Sections 1.6.4, 3.2.5 and 3.2.6).
Branch losses which are printed are taken as I2R and I2X losses and exclude the line charging, line
connected shunt, and magnetizing admittance components. For three-winding transformers, total
losses on all three windings are printed.
The number and name of the area and zone in which the "to bus" resides are printed for non trans-
former branches and for two-winding transformers.
For transformers, the turns ratio of the winding connected to the "from bus" is printed following the
percent loading. A two-character tag is printed adjacent to the ratio, which has the following
significance:
HI The "from bus" is connected to the winding one side of a regulating two-winding
transformer or to a regulating winding of this three-winding transformer, and the
off-nominal turns ratio is at or beyond its high limit.
LO The "from bus" is connected to the winding one side of a regulating two-winding
transformer or to a regulating winding of this three-winding transformer, and the
off-nominal turns ratio is at or below its low limit.
4-70 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
RG The "from bus" is connected to the winding one side of this regulating two-
winding transformer or to a regulating winding of this three-winding transformer,
its adjustment control mode is set to +1 or +2, the automatic tap ratio adjustment
was enabled during the last power flow solution activity, and the off-nominal
turns ratio is within its limits.
DC The "from bus" is the winding one side of this two-winding transformer which is
regulating alpha, gamma, or DC voltage of a DC line; its adjustment control
mode is set to +4; DC tap adjustment was enabled during the last power flow
solution activity; and the off-nominal turns ratio is within its limits.
LK The "from bus" is connected to the winding one side of this two-winding trans-
former or to any winding of this three-winding transformer, and either this
transformer winding is not a tap changing transformer winding, its adjustment
control mode is to zero or negative, or the automatic tap ratio adjustment was
disabled during the previous power flow solution activity.
UN The "from bus" is not the winding one side of this two-winding transformer.
Except for the tags "DC" and "UN", phase shifters are handled in a similar manner. For single sec-
tion two-winding transformers with non-zero phase shift angle on the winding one side, no indication
of phase shift is printed in the output block of the winding two side bus.
When the multisection line reporting option is enabled (see Section 1.6.4), the far end "to bus"
(rather than the closest "dummy" bus) of each multisection line connected to the "from bus" is
shown as its "to bus". Multisection lines are identified with an ampersand ("&") as the first character
of their branch identifiers in the circuit identifier column (e.g., "&1"). The sum of the losses on all of
the line sections comprising the multisection line is shown as losses on the multisection line.
Finally, transformer information is shown only if the line section adjacent to the "from bus" is a trans-
former branch, and the data applies to the winding adjacent to the "from bus".
If any of the non transformer branches reported have a nonzero line shunt at the "from bus" end, or
if any first winding of a transformer branch connected to the "from bus" has non-zero magnetizing
admittance, and the line shunt reporting option is enabled (see Section 1.6.4), the branch output
lines are followed by lines reporting powers corresponding to each of these admittances. Note that,
regardless of the setting of this option, the branch flows reported always include these components.
Figure 4-39 shows a sample of the tabular output. It covers Buses 152 and 153 which are con-
nected by a 500/230 kV transformer. It can be seen that the tap, at the Bus 152 side is at its high
limit (HI) of 1.05 pu. At bus 153 it can be seen that this is not the winding one side of this two-winding
transformer (UN).
The figure also shows three non transformer branches from Bus 153. They include circuits #1 and
#2 to Bus 154 (DOWNTN), which are overloaded (at 180% and 150% of rating) and a single circuit
to Bus 3006 (UPTOWN).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-71
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
The layout of the information is different from the standard layout. Figure 4-40 shows the wide
format output for the buses shown in Figure 4-36 for the standard output format.
4-72 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
Figure 4-40. Wide Format Power Flow Output including Branch Currents
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-73
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
The main difference between the standard and wide format is that, in the former, the data categories
are listed in vertical order while in the wide format they are printed from left to right. Those data cat-
egories are:
• Bus data
• Generators
• Load
• Shunts
• FACTS devices
• DC Lines
• Branches
The wide data format output is initiated in the same manner as the standard format. Selecting Wide
format output provides the option to include currents in the tabulation (see Figure 4-41).
4-74 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
The user can choose to show all this information for all buses, branches and equipment, including
generation, or to globally prevent showing of particular types of information (e.g., no branch flows
on all branches) or to select particular buses, lines and equipment to have their annotation sup-
pressed. Selecting the Diagram>Annotation… option will open the Powerflow Data Annotation
dialog where selections can be made of which information to show. Right-clicking on the diagram
or a network element in the diagram will give access to the same dialog (Figure 4-44). Right-clicking
on a network element will make the Item Annotation… and Diagram Annotation… options avail-
able (Figure 4-43).
In the right hand diagram of Figure 4-43, the number of the bus (151) is shown. This is the
item on which the right-click was performed. Note further that the Diagram Annotation toolbar
button is indicated in the pop-up menu.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-75
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
Figure 4-43. Selecting the Power Flow Data Annotation Dialog from the
Diagram Right-click Pop-up Menu
The Powerflow Data Annotation dialog is shown in Figure 4-44. It can be seen that the annotations
on the one-line diagram in Figure 4-42 are in accord with the selections shown for branch, bus,
voltage, equipment and flow directions.
4-76 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
Figure 4-44. Power Flow Data Annotation Dialog: Diagram Annotations Tab
For each item (or network element) including generation, branch, equipment and bus, an Annota-
tion Properties dialog will open particular to the item selected. Figure 4-45 shows the selections for
a LOAD. More details on item annotation are discussed in Section 2.5.11.1.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-77
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
Figure 4-46 displays the Diagram Range Checking tab. Under Line Ratings, Use line ratings is
selected to highlight lines loaded at 55% of the Rate A. In addition, the Bus Voltage Limits are
selected to highlight buses with voltages higher than 1.01 pu or lower than 0.95 put
4-78 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
Figure 4-46. Selecting Line Ratings in the Diagram Range Checking Tab
With these Diagram Range Checking options selected, the power flow output shown in Figure 4-43
will change to show the buses and lines with voltages and loadings outside the ranges selected (see
Figure 4-47).
It can be seen that buses 206 and 3018 (and others) are highlighted for having voltages in excess
of the high limit, 1.02 pu. Bus 203 and 205 are highlighted for having voltages below the low limit,
0.97 pu.
The circuit one between buses 153 and 154 (and others) are highlighted to show their loading is in
excess of 90% of their Rate A.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-79
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
4-80 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
Another way to use a Diagram View in other applications is to export the Diagram View into either
a JPEG (*.jpg) or Bitmap (*.bmp) image file. To export a Diagram View into an image file, select
File>Export Diagram Image… from the Main Menu. A File dialog will appear prompting for a name
to save the image file under. Select the image file format, either JPEG or Bitmap, by using the Save
as type: field at the bottom of the dialog.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-81
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
Area, zone and owner subsystem totals are selected in the Area/Owner/Zone Totals dialog (see
Figure 4-51). The reports are generated, as specified, for all subsystems or for selected sub-
systems. The figure shows that Area totals have been indicated and that specific Areas will be
selected. When the Select button is clicked, the Area Subsystem Selector dialog will be opened.
Clicking Go generates the report.
4-82 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-83
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
• The FLAPCO area is transmitting power to the other two areas although it is exporting
more (278.7 MW) than scheduled (250 MW). This is because the Area Interchange
control was not enabled in the Loadflow Solutions window.
• LIGHTCO area is receiving 130.8 MW compared to a desired interchange of 100 MW.
• The FLAPCO area is receiving 684.6 Mvar from the other two areas.
• Total Real Power losses are 58.7 MW
• Zone 1 (FIRST) has zero generation but a demand level of 1200 MW. It can be seen
that its net interchange is 1218 MW which serves the load demand and the zone’s
losses of 18 MW. Note that there is no Zone interchange flow control available.
• Similarly, Zone 2 (SECOND) has 1400 MW of generation but 1500 MW of load. Its net
interchange therefore is seen to be 130 MW which serves the deficit between genera-
tion and demand and the zone’s real power losses of 30.8 MW.
4-84 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
• The seven Owners have ownership of all the generators in this network (3258 MW).
This can be compared with the Area totals.
• All the shunts in the network, whether they be FACTS devices, switched shunts or bus
shunts are assigned to three Owners (TRAN 1, TRAN 2 and GEN 2).
• Three Owners (GEN 1, GEN 2 and GEN 5) supply a total of 19,196 MW of generation
but have no ownership of demand.
• Note that there is no Owner interchange control available.
Table 4-8. Information Provided in Interchange Reports for Areas and Zones
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-85
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
The dialog for interchange reports are opened from the Power Flow>Reports>Area / zone
based reports… or by clicking the Area/Zone button. The Area/Zone Base Reports dialog
will be displayed (Figure 4-55).
There are two types of summary reports: Inter area/zone flow, which provides total flows between
Areas or Zones and Tie line, which provides detailed flows on the tie lines (branches) between the
Areas or Zones.
The output is organized by Area or Zone such that all Areas or all Zones are reported or the Select…
facility may be used to limit the output to selected Areas or Zones.
It is useful to note that the inter Area / Zone flow report can be compared to the Totals report
described in Section 4.4.4.1.
4-86 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
This simple summary on inter-area flow can be compared with the Area Total report (see Figure 4-
52). This report confirms the previously documented results which show that Area 1 is exporting
131 MW to Area 2 and exporting 148 MW to Area 5. Note that these numbers are rounded in com-
parison to results shown in Figure 4-52.
The Inter-zone summary report for the savnw.sav case is seen in Figure 4-57.
This simple summary on inter-zone flow can be compared with the Zone Total report (see Figure 4-
53). This report confirms the previously documented results which show that Zone 1 is importing a
total of 1218 MW from the other three zones.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-87
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
A portion of the inter-zone tie-line report for the savnw.sav case is seen in Figure 4-59. The report
presents information in order of Zone. The figure shows the tie-line flows from Zone 1 to Zones 2,
5 and 77. The total flows can be compared with the interchange totals shown in Figure 4-57 (inter-
zone flows) and Figure 4-53 (zone totals report).
4-88 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-89
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
The seven available reports are accessed from the seven tabs shown in the Limit Checking Reports
dialog. Note that each report can be selected by AREA, ZONE, OWNER, BASE KV and BUS, using
the Select area of the dialog.
Figure 4-62 shows the available reporting selections and the ratings selections on the Branches
tab.
4-90 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-91
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
where:
Ebase Is the base voltage in volts of the bus to which the terminal of the branch is
connected.
Irated Is the rated phase current in amps.
Any checked branch whose current loading, including line charging, line connected shunt, and
transformer magnetizing admittance components, exceeds the specified percentage of rating is
reported. The default limit is 100%.
If the user specified a subsystem for reporting (for example, AREA, ZONE, etc.), the output is gen-
erated, with all branches having at least one endpoint bus in the specified subsystem being
checked. It should be noted, however, that when subsystem selection is by OWNER, it is branch
ownership rather than bus ownership which is used in determining which branches are contained
in the specified subsystem. Any other selection criteria apply to the branch’s endpoint buses.
Any branch whose corresponding rating is zero is not checked for overloading. Any branch whose
current loading exceeds the designated percentage of rating is alarmed. The current is calculated
at each end of the line and the number of the bus at which the current is higher is followed by an
asterisk ("∗"). The branch current loading, rating, and percentage loading are tabulated.
For three-winding transformers, each winding is checked and reported separately. Only those wind-
ings connected to buses in the specified subsystems are processed. For each winding reported, the
bus to which the winding is connected is shown as the "from bus", and the winding number and
transformer name are listed as the "to bus".
The process of generating the report can be terminated with the AB interrupt control code.
Figure 4-63 shows a sample output from the savnw.sav case with a branch overload check per-
formed on the basis of 80% of RATE A
The overload report lists branches in single entry list format ordered by "from bus". It can be seen
that branches are also listed by AREA so that all branches overloaded in AREA 1 are listed first
followed by branches in AREA 2 and AREA 5. Branches would also be listed by circuit number if
appropriate.
In the table, the right most column shows the percentage loading on 100% of the RATE A level.
Only one branch loading exceeds the 100% limit; the 230/18 kV transformer branch from Bus 205
to Bus 206. Four other branches are listed which have loadings less than 100% of RATE A but have
loadings exceeding 80%.
4-92 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
Figure 4-63. Output Format for Branch Overloads Based on 80% of Rate A
If the user specified a subsystem for reporting (for example, AREA, ZONE, etc.), the output is gen-
erated with all transformer branches having at least one endpoint bus in the specified subsystem
being checked. It should be noted, however, that when subsystem selection is by OWNER, it is
transformer branch ownership rather than bus ownership which is used in determining which trans-
former branches are contained in the specified subsystem. Any other selection criteria apply to the
branch’s endpoint buses.
Any transformer whose corresponding rating is zero is not checked for overloading. Any trans-
former branch whose MVA loading exceeds the designated percentage of rating is alarmed. The
loading is calculated at each end of the line and the number of the bus at which the loading is higher
is followed by an asterisk ("∗"). The branch MVA loading, rating, and percentage loading are
tabulated.
For three-winding transformers, each winding is checked and reported separately. Only those wind-
ings connected to buses in the specified subsystem are processed. For each winding reported, the
bus to which the winding is connected is shown as the "from bus", and the winding number and
transformer name are listed as the "to bus".
The process of generating the report can be terminated with the AB interrupt control code.
Figure 4-64 shows a sample output from the savnw.sav case with the transformer overload check
performed on the basis of 80% of RATE A.
The overload report lists transformer branches in single entry list format ordered by "from bus".
Transformers are also listed by AREA so that all transformers overloaded in AREA 1 are listed first
followed by transformers in AREA 2 and AREA 5. Transformers would also be listed by circuit
number if appropriate. This report shows overloads only in AREAS 2 and 5.
In the table, the right most column shows the percentage loading on 100% of the RATE A level.
Only one transformer loading exceeds the 100% limit. It is the 230/18 kV transformer branch from
Bus 205 to Bus 206.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-93
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
Two other branches are listed which have loadings less than 100% of RATE A but have loadings
exceeding 80%.
Each non-transformer branch current loading is checked against designated branch ratings. Rat-
ings are assumed to have been entered as:
where:
Ebase Is the base voltage in volts of the bus to which the terminal of the branch is
connected.
Irated Is the rated phase current in amps.
Any checked branch whose current loading, including line charging and line connected shunt com-
ponents, exceeds the specified percentage of rating is reported.
If the user specified a subsystem for reporting (for example, AREA, ZONE, etc.), the output is gen-
erated with all non-transformer branches having at least one endpoint bus in the specified
subsystem being checked. It should be noted, however, that when subsystem selection is by
OWNER, it is branch ownership rather than bus ownership which is used in determining which
branches are contained in the specified subsystem. Any other selection criteria apply to the
branch’s endpoint buses.
Any branch whose corresponding rating is zero is not checked for overloading. Any non transformer
branch whose current loading exceeds the designated percentage of rating is alarmed. The current
is calculated at each end of the line and the number of the bus at which the current is higher is fol-
lowed by an asterisk ("∗"). The branch current loading, rating, and percentage loading are tabulated.
The process of generating the report can be terminated with the AB interrupt control code.
Figure 4-65 shows a sample output from the savnw.sav case with the transmission line (non-trans-
former branch) overload check performed on the basis of 75% of RATE A.
4-94 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
The overload report lists branches in single entry list format ordered by "from bus". As for Branch
and Transformer overloads, branches are also listed by AREA so that all branches overloaded in
AREA 1 are listed first followed by branches in AREA 2 and AREA 5. Branches would also be listed
by circuit number if appropriate. This report shows overloads only in AREA 1.
In the table, the right most column shows the percentage loading on 100% of the RATE A level. It
can be seen that no transmission lines have a loading in excess of 100% of RATE A. Three trans-
mission lines are shown to have loadings in excess of 75% of RATE A. One line from Bus 153 to
Bus 154 has two circuits listed in order of circuit number.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-95
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
Figure 4-65. Report on Transmission Line Overloads
4-96 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
When the Branch currents, all ratings report is selected, branch loadings are reported for all of
the Rating sets, A, B and C.
where:
Ebase Is the base voltage in volts of the bus to which the terminal of the branch is
connected.
Irated Is the rated phase current in amps.
Any checked branch whose current loading, including line charging, line connected shunt, and
transformer magnetizing admittance components, exceeds the specified percentage of rating is
reported.
If the user specified a subsystem for reporting (for example, AREA, ZONE, etc.), the output is gen-
erated with all branches having at least one endpoint bus in the specified subsystem being checked.
It should be noted, however, that when subsystem selection is by OWNER, it is branch ownership
rather than bus ownership which is used in determining which branches are contained in the spec-
ified subsystem. Any other selection criteria apply to the branch’s endpoint buses.
Any branch whose corresponding rating is zero is not checked for overloading. Any branch whose
current loading exceeds the designated percentage of rating is alarmed. The current is calculated
at each end of the line and the number of the bus at which the current is higher is followed by an
asterisk ("∗").
The branch current loading, rating, and percentage loading are tabulated for each Rating Set.
Figure 4-66 shows a subset of the report for the savnw.sav power flow case. It demonstrates the
manner in which the branches are listed in bus number, circuit and Area sequence.
The report shows only one branch is overloaded. It is the 230/18 kV transformer branch from Bus
205 to Bus 206 the loading of which is 108.5% of the RATE A level.
Note that a value for RATE C has been entered with a fictitious value of 1.0 MVA for most branches.
The table therefore shows very high percentage loadings for that RATE.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-97
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
Figure 4-66. Report for Branch Loadings, All Ratings
4-98 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
Figure 4-67. Limit Checking Reports Dialog: Out-of-limit Bus Voltage Tab
The voltage band is specified by selection of the Min and Max levels in pu. In Figure 4-67, the range
is from 0.95 pu to 1.05 pu (the default level). Both limits can be adjusted in 0.01 pu increments in
either direction. The Select facility is available for customizing the report to a particular subsystem.
The report generated by clicking the Go button produces a listing of those buses whose voltage
magnitude is greater than VMAX, followed by a listing of buses whose voltage is less than VMIN.
Both listings are in ascending numerical (under the "numbers" output option) or alphabetical (under
the "names" output option) order. All buses except those whose type code is four are checked. The
"star point" buses of three-winding transformers are neither checked nor reported.
The process of generating the report may be terminated with the AB interrupt control code.
Figure 4-68 shows the report generated for the savnw.sav case using a voltage range from 0.97 pu
to 1.01 pu. It can be seen that the bus base voltage is listed together with the actual bus voltages
in pu and kV. There are 13 buses with voltages greater than 1.01 pu and 5 buses with voltages less
than 0.97 pu.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-99
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
Figure 4-68. Report for Voltages Out-of-limit
4-100 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
As shown, there is a facility for specifying a Machine Capability Curve Data File and an option for
updating Var limits in the power flow. The Select facility is also available for customizing the report
to a particular subsystem.
I, ID, P1, QT1, QB1, P2, QT2, QB2, ... P10, QT10, QB10
where:
I Bus number. Bus I must reside in the working case with a generator table entry
assigned to it. No default is allowed.
ID One- or two character machine identifier used to distinguish among multiple
machines at a plant (i.e., at a generator bus). ID = ’1’ by default.
Pi Generator active power output along the "MW" axis of the machine’s capability
curve, entered in MW; no default allowed.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-101
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
QTi Maximum (i.e., overexcited) reactive power limit at Pi MW, entered in Mvar.
QTi = 0.0 by default.
QBi Minimum (i.e., underexcited) reactive power limit at Pi MW, entered in Mvar.
QBi = 0.0 by default.
Up to 10 sets of points on the capability curve may be entered. When the machine is a generator,
the Pi values must be in ascending order with P1 greater than or equal to zero. When the machine
is a motor, the Pi values must be in descending order with P1 less than or equal to zero.
If P1 is nonzero, an additional point is assumed at P = 0.0 with its QT and QB set equal to QT1 and
QB1, respectively.
In the PSS™E EXAMPLE directory, there is an example capability curve established for the
machines in the savnw.sav power flow case. The data file is savnw.gcp, and the contents of the file
are listed in Figure 4-70. A generic plot of the reactive limits for the machine at bus 206 is shown.
4-102 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
The report generated can be limited by employing the Select facility to include only machines in
specific areas, owners, zones, base kV or at specific buses.
If selection is by OWNER, each machine wholly or partly owned by any of the owners specified and
for which a data record was successfully read is processed. The owner assignment of the bus to
which the machine is connected is not considered.
1. Machine active and reactive power loading from the power flow case.
2. The Mvar limit settings on the capability curve corresponding to the machine’s active
power loading from (1).
3. The maximum active power loading from the capability curve (i.e., Pi from the last point
entered for this machine).
4. The active and reactive power limits as contained in the working case.
If the machines’ reactive power output in (1) is beyond the limits shown in (2), it is followed by an
asterisk ("∗").
If the Update VAR limits in working case option is enabled, the update takes place after all
reporting is complete or after interruption of the process via the AB interrupt control code for all
machines that were reported.
It is important to note that the updating of reactive power limits is not reversible. It is recommended
that, prior to generating the report with the option to update var limits enabled, the working file be
preserved in a Saved Case File and that the new reactive power limit data be examined before per-
manently overwriting the original data.
Figure 4-71 shows the report generated for the savnw.sav working file. It clearly indicates that the
machine at bus 206 has a reactive power output of 600 MW and a real power output of 800 MW.
Based on its capability curve, the reactive power limit should be 160 Mvar based on the real power
output of 800 MW. This is much less than the assumed limit of 600 Mvar. Examination of the capa-
bility curve plotted in Figure 4-70 confirms a reactive power limit of 160 Mvar with 800 MW
generated.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-103
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
Figure 4-71. Report Output for Reactive Power Checking with Capability Curve
4-104 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
From the Generator bus tab, the following reports can be selected:
The Output with voltage reversed option allows the user to change the option to tabulate the
results with voltage shown in pu or kV, depending on what the program option setting is
(Section 1.6.4).
The report generated can be limited by the Select facility to include only machines in specific areas,
owners, zones, base kV or at specific buses.
The report includes the bus number, name, base voltage, and type code, along with the number of
machines modeled at the plant whose status flags are one, the number of machines whose status
flags are zero, the total plant power outputs and reactive power limits, and scheduled and actual
voltages.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-105
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
If a plant regulates the voltage of a remote bus, the remote bus identifiers are printed and the actual
voltage printed is that at the remote bus; if a plant regulates its own terminal voltage, the remote
bus fields are blank. Total plant MBASE of machines at the bus whose status flags are one, along
with the numbers of the zone and area in which the bus resides, are also printed.
Any plant that is either a system or area swing is identified with an appropriate tag at the end of the
output line.
As the last line of each report, subsystem totals of plant power outputs, var limits, and MBASE are
tabulated.
The generation of the report may be terminated by entering the AB interrupt control code.
Figure 4-73 shows a report for "All plants" from the savnw.sav working file.
• Generators at buses 206, 211 and 3018 are regulating voltage at remote buses.
• Generator at buses 206 and 3018 are failing to meet scheduled voltages (VSCHED) at
their remote buses. Their actual voltages (VACTUAL) at the remote buses are below
scheduled because the machines have reached maximum reactive power limits. Under
the TYP column, the machines at buses 206 and 3018 are indicated to be "-2"; the neg-
ative sign indicates that the machines are at a reactive power limit.
• The system swing bus is 3011 while the swing buses for Areas 1 and 2 are Buses 101
and 206 respectively.
4-106 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
Figure 4-73. Generator Bus Report
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-107
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
The user can select to report on all on-line machines or only those which are overloaded (see
Figure 4-74).
Figure 4-74. Limit Checking Reports Dialog: Machine Terminal Report Tab
When the step-up transformer is modeled with the generator data (i.e., XTRAN is nonzero), the gen-
erator bus is the high side bus (refer to Section 3.2.4.1). In this case, the overload check calculates
back through the step-up transformer impedance to determine the conditions that exist at the gen-
erator terminals.
The overload check assumes a machine capability curve as shown in Figure 4-75. The radius of
the semicircle in the upper half plane, centered at the origin, is taken as:
MBASE
----------------------
Et
4-108 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
P
-------
2
Et
1.6*MBASE
Q
-------
2
Et
When XTRAN is nonzero, the reactive power limits are modified to reflect these limits at the termi-
nals by taking into account losses through the step-up transformer.
The assumed operating region in the capability curve of Figure 4-75 is bounded as follows:
3. On the left, by the straight line connecting the point QMIN on the "Q" axis and the point
on the upper half plane circle corresponding to an abscissa of -0.3∗MBASE. When
QMIN is greater than -0.3∗MBASE, this bound is a line parallel to the "P" axis through
the point QMIN on the "Q" axis.
4. On the right, by a circle of radius 1.6∗MBASE, with center at (0,Qmin) and passing
through the point QMAX on the "Q" axis and the point on the upper half plane circle
corresponding to an abscissa of 0.55∗MBASE. When QMAX is less than 0.55∗MBASE,
this bound is a line parallel to the "P" axis through the point QMAX on the "Q" axis.
P gen + jQ gen
------------------------------------
( Et )2
is outside this region is considered overloaded. Any machine absorbing active power is checked as
if its active power is in the upper half plane.
For determining overloaded conditions, the value specified as MBASE for each machine must be
the actual MVA base of the generator. The overload check is invalid for any machine for which the
base is something other than this quantity, even if the base conversion has properly been taken into
account in specifying ZSORCE and XTRAN.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-109
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
When the Overloaded machines only option is enabled, only those machines considered over-
loaded under the criteria described above are reported. When the All on-line machines option is
enabled (all machines in the case or only those within a specified subsystem), then those whose
loading is outside the assumed capability curve have an asterisk ("*") printed following their current
loading.
The report generated can be limited by the Select facility to include only machines in specific areas,
owners, zones, base kV values or at specific buses.
If selection is by OWNER, each machine wholly or partly owned by any of the owners specified and
for which a data record was successfully read is processed. The owner assignment of the bus to
which the machine is connected is not considered.
Data presented includes the bus number, name, and base voltage, along with the machine identifier
and the machine terminal conditions of power output, voltage, current, and power factor. Reactive
power limits and the generator base, MBASE, are also printed, along with the step-up transformer
impedance and off-nominal turns ratio if the transformer is represented as part of the generator
model. The numbers of zone and area in which the bus resides are also printed, and machines at
any plant which is either a system or area swing are identified with an appropriate tag at the end of
the output line. Generators whose loading is outside the assumed capability curve have an asterisk
("∗") printed following their current loading.
As the last line of each report, subsystem totals of machine power outputs, reactive power limits,
and MBASE are tabulated.
The generation of the report may be terminated by entering the "AB" interrupt control code.
Figure 4-76 shows the Machine Terminal report selected for "All on-line machines" in the savnw.sav
power flow case.
It can be seen that machines at buses 206 and 3018 are overloaded based on the calculations con-
forming to the assumed capability curve in Figure 4-75.
It should be noted that the terminal voltages for those two machines, and the machine at bus 211,
are higher than their scheduled voltages (VSCHED) because these machines are attempting to
control voltage at remote buses rather than at the machine terminals. The Generator Bus report
shows the scheduled voltages and the remote buses (see Figure 4-73).
4-110 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
Figure 4-76. Report Tabulation for Machine Terminal Conditions in savnw.sav File
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-111
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
Clicking the Regulated buses tab in the Limit Checking Reports dialog will facilitate generation of
a report which tabulates those buses whose voltages are controlled by generation, switched shunts,
voltage controlling transformers, FACTS devices, and/or VSC DC line converters (see Figure 4-77).
Figure 4-77. Limit Checking Reports Dialog: Regulated Buses Report Tab
Only in-service voltage controlled buses (i.e., buses whose type codes are less than four) are
reported. The following lists the conditions under which the various voltage controlling equipment
items are reported:
Generation Bus type code is two or three, and at least one in-service machine is present.
Switched shunt Bus type code is less than four and the control mode is 1 or 2.
Transformer Branch is in-service and its adjustment control mode is set to +1.
FACTS device Control mode is nonzero for sending bus end; control mode is one, five or seven for
terminal bus end.
VSC DC converter VSC DC line’s control mode (MDC) is one, the VSC converter’s AC control mode
(MODE) is one, and the VSC converter’s DC control code (TYPE) is not zero.
The report always displays voltage at the controlled bus. For any voltage controlling transformer
whose load drop compensation impedance is nonzero, the controlled bus voltage (or, equivalently,
the voltage limits) are compensated. Therefore, limits printed for such transformers are the com-
4-112 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
pensated limits and the lower limit is preceded by an asterisk ("∗"). Note that the calculation of these
limits requires transformer current; hence, they are valid only if the report is generated from a solved
system condition.
The generation of the report may be terminated by entering the AB interrupt control code.
The report generated can be limited by the Select facility to include only machines in specific areas,
owners, zones, base kV or at specific buses.
Data presented includes the bus number, name, and base voltage of each regulated bus along with
its present voltage magnitude. For each controlling equipment item, the desired voltage setpoint or
voltage band, as appropriate, is listed along with any deviation between actual and scheduled
voltages.
A Regulated Bus report from the savnw.sav power flow case is shown in Figure 4-78.
• Regulated buses 101, 102 and 3011 are generator terminal buses.
• Bus 154 is a type 1 bus whose voltage is regulated by the transformer in the branch
from bus 152 to bus 153. Further the voltage control range of the transformer’s tap
changer is 0.98 to 1.0 pu but the controlled bus voltage is only 0.93892 pu. Conse-
quently, a violation (or error) of -0.04108 pu is indicated.
• Bus 201 is a type 1 bus whose voltage is regulated by the remote generator at bus 211.
The scheduled voltage of 1.04 pu has been met.
• Bus 205 is a type 1 bus whose voltage is regulated by the remote generator at bus 206
and the transformer tap changer in the transformer branch from the 500 kV bus 204 to
the 230 kV bus 205. The generator is scheduled to control voltage at bus 205 to a level
of 0.98 pu. The transformer tap changer has a voltage range between 0.98 pu and 1.0
pu and is controlling bus 205. The actual voltage on bus 205 is only 0.949 pu. Conse-
quently, there is a violation indicated of 0.03098 pu.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-113
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
Figure 4-78. Regulated Bus Report from the Savnw.sav Power Flow Case
4-114 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
The user has the option of listing all adjustable transformers or of restricting the report to those
whose controlled quantity is outside of its specified band. Further, the user can choose to reverse
the voltage reporting from pu to kV, or vice versa, depending on the current program option setting
(Section 1.6.4).
The report generated can be limited by the Select facility to include only transformers in specific
areas, owners, zones, base kV or at specific buses. When subsystem selection by owner is in
effect, branch ownership rather than bus ownership is used in determining which transformers are
contained in the specified subsystem; any other selection criteria apply to the transformer’s end-
point buses.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-115
Power Flow PSS™E-31.0
Analyzing Power Flow Solution Results Users Manual
Two-winding transformers are listed in the report with their winding one side bus first and with their
winding two side bus as the "to bus". Three-winding transformer windings are listed in the report
with their controlling winding side bus first and with their transformer name and winding number as
the "to bus"; a three-winding transformer winding is processed if it is an adjustable winding and if
the bus to which it is connected is in the specified subsystem.
Transformers are ordered in ascending numerical (under the "numbers" output option) or alphabet-
ical (under the "names" option) order by controlling winding side bus, and, for each such bus, in
ascending order by "to bus" field and circuit identifier.
The output report for each subsystem grouping is printed in up to four sections.
1. Those transformer windings whose tap ratio may be adjusted to control the voltage at
a designated controlled bus are printed. The present controlled voltage and the desired
voltage band are listed, along with the controlled bus, the tap ratio, the ratio limits, and
the tap step. When the load drop compensating impedance is nonzero, the compen-
sated voltage is printed preceded by an asterisk ("∗"); otherwise, the voltage at the
controlled bus is reported.
2. A list of any transformer windings whose phase shift angle may be adjusted to control
the active power flow through itself. The data tabulated for these includes the present
active power flow through the phase shifter and the desired flow band, the phase shift
angle, and the angle limits.
3. A list of any transformer windings whose ratio may be adjusted to control the reactive
power flow through itself. The present reactive power flow and the desired flow band,
the present tap ratio and its limits, and the tap step are tabulated.
4. A list of those two-winding transformers whose ratio may be adjusted to control the
firing angle, extinction angle, or voltage of a DC line. Shown are the DC line number,
type of quantity controlled, its present value and desired band, present tap ratio and its
limits, and the tap step.
Any controlled quantity outside of its desired band is followed by the tag "HI" or "LO" as appropriate.
Similarly, if the ratio or phase shift angle of a transformer is at or beyond one of its limits, the appro-
priate identifier is printed.
The generation of the report may be terminated by entering the AB interrupt control code.
See Figure 4-80 for an example of a Controlling Transformers report from the savnw.sav power flow
case. Controlled buses at 154 and 205 show voltages below their transformers’ control range (indi-
cated by "LO") and the Phase Shifting transformer controlling power flow shows a flow level above
its control range (indicated by "HI").
4-116 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Analyzing Power Flow Solution Results
Figure 4-80. Controlling Transformers Report for savnw.sav Power Flow Case
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-117
Power Flow PSS™E-31.0
Modifying Load Characteristics Users Manual
This is particularly true of conventional planning studies where demand level is a given quantity
which must be maintained under a variety of system normal and abnormal conditions. The Plan-
ners’ job is to identify the lines and equipment required to sustain the defined demand levels; it is
axiomatic that the demand level is a given (constant MVA).
In steady-state and quasi steady-state operation studies, it is reasonable to recognize the loads’
dependence on voltage. Such studies include balanced switching (Chapter 8), short-circuit analysis
(Chapter 7) and examination of potential voltage collapse or voltage instability. These are condi-
tions under which voltage excursions can be significant.
Similarly, under dynamic conditions, which would be simulated with the PSS™E dynamic simulator,
treating loads as purely constant MVA at the reference load value is not acceptable because time
delays in distribution voltage-regulating devices prevent them from adjusting customer voltages in
the period of interest. Further, loads have a frequency dependence. For dynamic studies, therefore,
a variety of load models of varying complexity are available. These models recognize, in more
detail, the specific characteristics of loads such as lighting, heating and motor loads. The PSS™E
models available for dynamic simulations are discussed in detail in the PSS™E Program Operation
Manual.
The input functions of PSS™E (see Section 3.3) identify the load at each bus and allow the user to
indicate the following components of each load.
All of these components are specified in MW and Mvar. The MW and Mvar values for the constant
current and constant admittance components are the values that would be consumed by these
loads when the bus voltage is unity per unit. The values of these components can be changed,
using the editing facility in the Spreadsheet View or the load can be taken out of service by changing
its status in the Spreadsheet View.
While it is possible to enter bus loads as combinations of constant MVA, constant current and con-
stant admittance, it is preferable to enter the total load as constant MVA mainly because the
majority of steady-state analysis will be performed at or close to nominal voltage and the total
4-118 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying Load Characteristics
demand level is critical to the study at hand. It is a simple exercise to convert system loads from the
constant MVA characteristic to either of the voltage dependent characteristics or a combination of
all three depending on the type of analysis being carried out. It is equally simple to reconvert the
loads to have their original characteristic or any other combination.
aS p
S I = S i + ----------
v
bS p
S Y = S y + ----------
v2
SP = Sp × ( 1 – a – b )
where:
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-119
Power Flow PSS™E-31.0
Modifying Load Characteristics Users Manual
2. Load converted to constant current and constant admittance is added to any existing
load represented by those characteristics.
3. The load is converted on the basis of the actual voltage at the network buses. Prior to
conversion the working case should be solved to an acceptable mismatch level. Fol-
lowing conversion, the network is still in balance.
4. The split of load among the three characteristics may be different for the active and
reactive components of load.
Further, following conversion, only the new components are accessible for editing.
Load conversion is facilitated via the Power Flow>Convert Loads and Generators… option. This
selection will display the Convert/Reconstruct Loads and Generators dialog where selections can
be made on reallocations of constant MVA loads (see Figure 4-82).
4-120 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying Load Characteristics
Figure 4-82 shows an example in which 30% of the Real part of the Constant MVA load is to be
converted to constant current and 20% to constant admittance. For the imaginary component, the
conversion is to 20% constant current and 10% constant admittance.
It can be seen further that the loads to be converted can be selected by the Area, Zone or Owner
number to which the loads are assigned (NOT to the bus assignment to which the loads are con-
nected). When selected by kV, all loads connected to buses with the selected voltage(s) will be
converted in the loads’ selected Areas, Zones and/or Owners.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-121
Power Flow PSS™E-31.0
Modifying Load Characteristics Users Manual
Figure 4-83 shows the MVA loads in the savnw.sav power flow case, as initially defined. If the con-
version selections shown in Figure 4-82 were chosen, the result would be to re-allocate the loads
as shown in Figure 4-84. The conversion has been done, as can be seen, on all loads.
Note that conversion is done on the basis of the current load bus voltages in the power flow case.
The user should be sure to solve the case to an acceptable tolerance before converting the loads.
4-122 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying Load Characteristics
This process first collects all load into the constant MVA component by
2
ST = S p + vS i + v S y
where ST is the total of the three load components and then reallocates it by the formula
aST
S I = -----------
v
bST
S Y = -----------
v2
S P = ST ( 1 – a – b )
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-123
Power Flow PSS™E-31.0
Modifying Load Characteristics Users Manual
When reconstructing loads based on unity voltage, the three load components are summed
assuming one per unit voltage, (v = 1.0) and this total load is split among the three load character-
istics as specified. The network will normally not be in balance following this process with this load
reconstruction option.
Load reconstruction is facilitated via the Power Flow>Convert Loads and Generators… option
which displays the Convert/Reconstruct Loads and Generators dialog. To perform the load recon-
struction, select the Convert / Reconstruct Loads option and select one of the "Reconstruct" options
from the Operation menu.
In the this example the option to reconstruct using present voltage has been selected and the re-
allocation is to 10% of total load for both real and reactive power for constant current and constant
impedance loads (see Figure 4-86).
As for the conversion process, loads to be converted can be selected by the Area, Zone or Owner
number to which the loads are assigned (NOT to the bus assignment to which the loads are con-
nected) (see Figure 4-82). When selected by kV, all loads connected to buses with the selected
voltage(s) will be converted in the loads’ selected Areas, Zones and/or Owners.
Section 4.5.2 shows an example conversion process in which Figure 4-83 shows the MVA loads in
the savnw.sav power flow case, as initially defined. That conversion example re-allocates the loads
with the result shown in Figure 4-84. The conversion was done on all loads.
With that converted load as a starting point, the reconstruction can be done based on the realloca-
tions shown in Figure 4-86 above. The result is shown in Figure 4-87.
4-124 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying Load Characteristics
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-125
Power Flow PSS™E-31.0
Modifying Load Characteristics Users Manual
The first requirement is to select loads and generators to be scaled. Selection is by Area, Zone,
Owner, Base kV, combinations of these criteria, or by specific buses (see Figure 4-89).
Clicking the Go button in the Scale Powerflow Data dialog (see Figure 4-89) gives access to a
second dialog where specific scaling selections can be made to loads and generation (see Figure 4-
90).
Scaling Loads
It should be noted that selection by Area, Zone or Owner relates to the loads and not to the Area,
Zone and Owner assignments of the buses to which the loads are connected.
In the scaling process, load totals include voltage dependency effects. The constant power charac-
teristic holds the load power constant as long as the bus voltage exceeds the value specified by the
solution parameter PQBRAK which is discussed in Section 4.2.4.1).
4-126 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying Load Characteristics
Further, the load totals are the sums of any constant power, current, and admittance components
of those loads being scaled; all of these load components are scaled by the same factor.
Scaling Generators
For scaling purposes, machines with positive active power generation are included in the generator
totals, and those with negative active power generation are included in the motor totals. The dis-
cussion below is in terms of generator totals, but the same approach is used for motor totals.
All in-service machines whose type code is two or three are included in the generation totals and
subsequent scaling unless selection criteria limit the machines to be considered on the basis of
Base kV, Area, Zone, Owner, a combination of those or by selection of specific buses. When the
Owner criterion is employed, each machine wholly or partly owned by any of the owners specified
is included. The owner assignments of buses are not considered.
1. The scaling process is not a dispatch activity; it merely scales the existing active power
output of online machines such that the ratio of machine to total power is retained.
Machine power limits are recognized only if the user selects to enable the Enforce
machine power limits option.
2. If a system swing (type three) bus is in the subsystem being scaled, the working case
should be solved so that the swing power, which is included in the total generation, is
reasonable.
If the total generation is being changed by a large amount, the new generator outputs, as set by the
scaling process, should be examined to verify that machines are set at realistic operating points.
(For these situations, the economic dispatch activity facility, as described in Section 4.8, might be
more appropriate.)
Example data for the savnw.sav power flow case is presented in the Scale Powerflow Data dialog
(see Figure 4-90). That data includes the total real load (3,200 MW), the total generation real power
(3,258.7 MW) and the total reactive power for bus connected reactors and capacitor (600 Mvar and
950 Mvar, respectively). In addition the total reactive component of load is indicated to be 1,950
Mvar.
For scaling purposes, the real load and generation power can be changed by an absolute amount
in 10 MW increments or by a percentage. Similarly, the bus connected reactive equipment can be
scaled in the same manner.
For the reactive component of load, the scaling process provides three options:
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-127
Power Flow PSS™E-31.0
Modifying Load Characteristics Users Manual
Figure 4-90. Dialog for Selecting Scaling Factors of Loads and Generation
Using the savnw.sav power flow case, an example can be shown of scaling all real load by + 2%
while maintaining a constant P/Q ratio. No scaling will be imposed on real generation. Conse-
quently, the swing bus will need to generate the extra power as well any additional system losses.
Figure 4-91 shows the total loads, the swing bus power and the system losses in the savnw.sav
power flow case prior to scaling. Figure 4-92 shows the same data after scaling and resolving the
case.
4-128 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying Load Characteristics
Figure 4-91. Pre-Scaling Load, Generation, Losses and Swing Bus Output
Figure 4-92. Post-Scaling Load, Generation, Losses and Swing Bus Output
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-129
Power Flow PSS™E-31.0
Modifying the Network Users Manual
This section will address a variety of procedures for modifying and manipulating network files,
including:
Figure 4-93. Toolbar Buttons for Changing Network Content and Topology
Figure 4-94. Accessing the Procedures for Changing Network Content and
Topology
4-130 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying the Network
If the bus being processed is the endpoint bus of a multisection line grouping, the entire multisection
line grouping is removed from service. If the bus being processed is a dummy bus of a multi- section
line grouping, the multisection line is removed from service.
If a three-winding transformer is connected to the bus being processed, all three windings of the
transformer are removed from service.
The user has the choice of typing in a bus number or using the Select… button to display the Bus
Selection dialog. The bus 154 DOWNTN in the savnw.sav power flow case has been selected (see
Figure 4-96).
Clicking the OK button will revert back to the Disconnect / Reconnect Bus dialog (see Figure 4-95).
Clicking the Go button will initiate the disconnection.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-131
Power Flow PSS™E-31.0
Modifying the Network Users Manual
This disconnection procedure will result in the printing of a summary of branch status changes in
the Output Bar (see Figure 4-97).
The output results shows that five circuits have been taken out of service. This summary, however,
does not list the bus connected equipment which is taken out of service.
The filter allows the selection of a range of buses, selected by type, bus number range, Base kV
range and by name mask range. Following selection of the buses to be connected, clicking the OK
button will revert back to the Bus Selection dialog.
4-132 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying the Network
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-133
Power Flow PSS™E-31.0
Modifying the Network Users Manual
When disconnecting in the Diagram View, the buses, lines and equipment notation will change to
indicate their out of service condition. The line colors, width and style for out-of-service equipment
is selected in the Diagram Range Checking tab in the Powerflow Data Annotation dialog (see
Section 2.9.2). Further, the Output Bar will show a summary of the disconnected branches as
shown in Figure 4-97.
In the example shown in Figure 4-100, a dashed black line has been selected for visually identifying
out-of-service equipment. Using the savnw.sav power flow case, Bus 154 has been disconnected
and it can be see that the diagram indicates all the branches and bus connected equipment are out
of service.
4-134 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying the Network
For each bus processed, if its type code is four, it is set to two if there is a plant table entry assigned
to the bus or to one if no generator data is associated with the bus. Then, all branches connected
to the bus for which the "to bus" is not a type four bus are set to in-service. All two-terminal and
multi-terminal DC lines returned to service are placed in power control mode. All series FACTS
devices returned to service have their control modes set to a positive value as described below. A
summary of branch status changes is printed at the Output Bar.
If the bus being processed is the endpoint bus of a multisection line grouping, the entire multisection
line grouping is returned to service as long as the type code of the other endpoint bus is not four;
i.e., each line section is set to in-service and each dummy bus has its type code set to one (if there
is no generator data for the dummy bus) or two (if there is a generator slot for the dummy bus).
If the bus being processed is a dummy bus of a multisection line grouping, the multisection line is
set to in-service as long as the type codes of neither of the two end point buses is four.
If a three-winding transformer is connected to the bus being processed, all three windings of the
transformer are set to in-service as long as the type codes of neither of the other two buses con-
nected to the transformer is four.
Any series FACTS device returned to service has its control mode set as follows:
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-135
Power Flow PSS™E-31.0
Modifying the Network Users Manual
• To 3 if it was previously holding constant series impedance and then was disconnected
as described in the previous section.
• To 4 if it was previously holding constant series voltage and then was disconnected as
described in the previous section.
• To 5 through 8, as appropriate, if it was previously a series element of an IPFC and
then was disconnected as described in the previous section.
• To 1 in all other cases.
Use of the menu options, toolbar buttons and the diagram view for selection and reconnection of
buses are the same as for disconnecting buses as described in the previous section. The only dif-
ference is in selection of the Connect option rather than the Disconnect option (see Figure 4-101).
It is important to understand the difference between "deleting" network items and changing their
service status. Network elements which are "flagged" as out of service are merely to be ignored
during PSS™E network solution and reporting activities. The act of "deleting" permanently removes
the equipment item and all its data from the power flow working file.
If all loads at a bus are removed, a message indicating that is printed to the Output Bar. Similarly,
in deleting machines from the working case, if all machines at a bus (plant) are removed, an appro-
priate message is printed in the Output Bar and the plant data at the bus is also deleted.
If the plant entry of any area swing bus is deleted, an appropriate message is printed in the Output
Bar and the area swing bus number is set to zero.
This deleting process does not check that the power flow data is in the form required by the power
flow solution activities after deleting has taken place. The user should check for islands, system
swing bus specification and area interchange control parameters before proceeding.
4-136 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying the Network
When deleting buses, the user has the option to Remove generator entries for out-of-service
plants, (i.e., type one buses at which a plant is currently off-line). The proper selection for this
option is dependent upon the application at hand. If the user is setting up the working file to build
an equivalent of a subsystem contained within it, the usual procedure is to enable this option. For
other applications, it is often desirable to retain these generator table allocations if the machines
may subsequently be returned to service.
The other option available when deleting buses is to Change codes of boundary buses. This
option will add four to the bus type codes of "boundary buses", which are retained in the working
file following the deletion process. A "boundary bus" is defined as a bus to be retained in the working
file which is connected to a bus to be deleted. The normal procedure is to disable this option unless
some advanced equivalencing operation is to be performed with the retained data. See Chapter 9
for a description of these procedures.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-137
Power Flow PSS™E-31.0
Modifying the Network Users Manual
As the deletion process proceeds, a summary of the number of buses deleted is shown in the
Output Bar.
In the Diagram View, it is possible to see the buses and their associated lines and equipment which
have been deleted (see Figure 4-103). The "unbound" items (items that exist in the diagram but not
in the network data because of the deletion) are shown in the designated color selected in the Dia-
gram Properties dialog, as described in Section 2.9.1. The diagram shows a partial view of the
buses deleted from the FLAPCO area of the savnw.sav power flow case.
Figure 4-103. Diagram View of Deleted Buses and the Diagram Properties
Options
The deletion process operates on subsystem equipment items according to the following
conditions:
4-138 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying the Network
In addition, the user can elect to Remove out-of-service ties to other subsystems when
removing outages of AC branches, DC lines, FACTS devices, three-winding transformers and VSC
DC lines. When making this election, any outaged branch with at least one bus in the specified sub-
system is deleted. Otherwise, all buses connected by the branch must be in the specified
subsystem. In the case of multi-terminal DC lines, only the AC converter buses are considered in
determining if all buses are in the specified subsystem; specifically, the Area, Zone, and Owner
assignments of the DC buses are not considered.
The data categories which can be processed for deletion are shown in the drop-down menu in
Figure 4-104. In addition, the figure shows an example report following deletion of three AC lines in
the savnw.sav case. These branches were taken out-of-service before attempting to delete them.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-139
Power Flow PSS™E-31.0
Modifying the Network Users Manual
Selecting the Power Flow>Changing>Join buses (JOIN)… option or clicking the Join
Buses button on the toolbar opens the Join Buses dialog (see Figure 4-105). Within the
dialog the user will identify the two buses to be joined. One of the buses will be retained and
the other discarded. Additionally the user must decide how to treat the line shunts which are con-
nected to any branch currently joining the two buses; either discard them or add them to the bus
which is to be retained.
4-140 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying the Network
All other branches originally emanating from the bus being removed are rerouted to the retained
bus. If there are branches from the two specified buses to a common third bus with identical circuit
identifiers, branches originally connected to the retained bus keep their original circuit identifiers
and new identifiers are assigned to the rerouted circuits.
All loads at the bus being removed are transferred to the retained bus. In the case of conflicting load
identifiers, those loads originally at the retained bus keep their original identifiers and new identifiers
are assigned to the transferred loads.
If the retained bus is not a generator bus but the deleted one is, the plant and machine data of the
removed bus is transferred to the retained bus. If both buses are generator buses, machines from
the removed bus are transferred to the retained bus and plant totals are updated. In the case of
conflicting machine identifiers, those machines originally at the retained bus keep their original
machine identifiers and new identifiers are assigned to the transferred machines.
All changes to branch, load, and machine identifiers are reported in the Output Bar. The user has
the option, however, of changing identifier settings in the spreadsheet before executing the Join
Buses process.
If the retained bus does not have a switched shunt and the deleted one does, the switched shunt
of the removed bus is transferred to the retained bus.
If both buses have switched shunts, the switched shunts are merged, with blocks being assigned
in the following order:
Control parameters from the retained bus are kept unless the switched shunt at the retained bus
controls the admittance setting of the switched shunt at the removed bus. In this case, the control
parameter data items (MODSW, VSWHI, VSWLO, SWREM, RMPCT and RMIDNT) of the removed
bus are transferred to the retained bus.
If either the retained bus or removed bus is involved in multisection line groupings, each such
grouping is either:
The Join Buses process is not sensitive to any interrupt control code options.
As an example, using the savnw.sav power flow case, the buses ’154 DOWNTN’ and ’3008
CATDOG’ will be joined. In Figure 4-106 it can be seen that bus 154 has two loads (600+j450 MVA
and 400+j350 MVA) and bus 3008 has one load (200 + j75 MVA) at nominal voltage. The buses are
joined by one 230 kV line without line shunts.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-141
Power Flow PSS™E-31.0
Modifying the Network Users Manual
If bus 154 is the retained bus, the Join Buses process should move the load from bus 3008 to bus
154 and its identifier changed to ’3’.
In the Join Buses dialog, shown in Figure 4-105, clicking the Select… button will display the Bus
Selection dialog (see Figure 4-107). The bus can be selected from the bus listing or the number can
be typed in directly. For large cases, the filter can be used to limit the bus listing to a selected
subsystem.
The result of the selection process will revert to the Join Buses dialog where the selected buses are
indicated along with the choice of method of dealing with line shunts. Clicking the Go button shown
in Figure 4-108 will complete the joining process and, for this example, result in a summary report
in the Output Bar (the text of which is shown in the lower portion of Figure 4-108).
4-142 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying the Network
Figure 4-108. Join Buses Dialog and Summary Report on Relocation of Load
The summary report indicates that the load on Bus 3008, with identifier 1, was moved to bus 154
and its identifier changed to 3 so as to avoid conflict with two existing loads on that bus. Figure 4-
110 shows the Diagram View of the retained bus #154. In the diagram it can be seen that there are
now three bus loads on bus 154 and that the bus is now joined to buses 3005, 3007 and 3018, each
of which were previously connected to bus 3008 (see Figure 4-109).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-143
Power Flow PSS™E-31.0
Modifying the Network Users Manual
Figure 4-109. Original Topology at Bus 203
4-144 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying the Network
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-145
Power Flow PSS™E-31.0
Modifying the Network Users Manual
In the Split Buses dialog, the user enters the bus to be split directly in the Original bus input field,
or alternatively can click the Select… button which opens up the Bus Selection dialog. Having
selected the bus, the user should provide a bus number, name and Base kV for the new bus.
Clicking the Go button in the Split Buses dialog (Figure 4-111) will initiate the splitting process.
The user is now required to identify which network elements will be moved from the split bus and
connected to the new bus. This selection is made in the Reassign Branches and Equipment dialog
which opens when the splitting process is underway. Figure 4-112 shows a sample Reassign
Branches and Equipment dialog which would display if bus 154 were selected to be split in the
savnw.sav power flow case. Reassignment can be made for loads, switched shunts, machines and
branches.
Finally, when the split is made, a new jumper branch is created to join the original and new buses
together. See the notes in the next section.
4-146 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying the Network
The new bus is set up with no fixed shunt element, and is given the same area, zone, and owner
assignments as the original bus. When generation is moved from the original bus to the new bus,
the new bus is assigned the bus type code of the original bus; if all machines are moved to the new
bus, the original bus is given a type code of one; if no machines are moved to the new bus, the
original bus has its type code unchanged and the new bus becomes a type one bus with no gener-
ator entry.
If the zero impedance line threshold tolerance, THRSHZ, is greater than zero, the branch con-
necting the original and new buses is entered as a zero impedance line. Otherwise, a jumper branch
with an impedance of j0.0001 is introduced between the original and new buses. The new branch
is given the same owner as the original bus.
If the original bus is an endpoint bus of one or more multisection line groupings and the adjacent
line section of a multisection line grouping is rerouted to the new bus, the new bus becomes the
endpoint bus of the multisection line. If the original bus is a dummy bus of a multisection line
grouping, the multisection line grouping is either:
• Redefined if exactly one of the two branches connected to the original bus is rerouted
to the new bus.
• Deleted if neither or both are rerouted to the new bus.
The new bus is given a type code of one (or two or three if generation is moved to it) and the jumper
branch between the original bus and the new bus is set to in-service unless the new bus becomes
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-147
Power Flow PSS™E-31.0
Modifying the Network Users Manual
a dummy bus of an out-of-service multisection line grouping; in this case, the bus type code is set
to four and the jumper branch is set to out-of-service.
If sequence data is contained in the working case (see Section 7.2), it is handled appropriately,
including the rerouting of zero sequence mutuals. Branches introduced by the splitting process
have their zero sequence impedances set to j0.0001.
Once the new bus has been created, the data associated with the new bus and branch may be mod-
ified just as any other bus and branch in the working case.
This splitting process is not sensitive to any interrupt control code options.
Using the savnw.sav power flow case, (see Figure 4-113) bus 3003 can be split and circuit 2 from
bus 3005 reassigned to the new bus 3020.
Selection of the bus to be split, its number, name and Base kV is done in the Split Buses dialog (see
Figure 4-114). After clicking the Go button, the Reassign Branches and Equipment dialog displays
the elements which can be selected to be moved to the new bus 3020. In the example, the option
to move circuit 2 from bus 3005 to the new bus has been selected. Clicking the OK button in the
Reassign Branches and Equipment dialog will complete the process. A summary of the changes is
shown in the Output Bar (see the lower portion of Figure 4-114).
4-148 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying the Network
Figure 4-114. Bus Select, Reassign and Output Report Summary for Bus
Split
The result of the splitting process can be seen in the Diagram View (see Figure 4-115). The diagram
shows the new bus, 3020, the new branch from the new bus to the original bus and the new routing
of circuit 2 from bus 3005 to the new bus.
A one-line Slider file conforming to the original topology will now show circuit 2 out-of-service. A
modified Slider file will have to be generated to show the new topology.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-149
Power Flow PSS™E-31.0
Modifying the Network Users Manual
4-150 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying the Network
The process is initiated by either selecting the Power Flow>Changing>Tap line (LTAP)…
option or by clicking the Tap Line button. The Tap Line dialog is displayed (see Figure 4-
116).
When the new bus is then introduced into the working file it is assigned to the area, zone, and owner
of the nearer bus. The new bus is given a bus type code of one if the branch being tapped is in-
service, or a type code of four if the branch is out-of-service. It is made a passive node with no load,
generation, or shunt elements.
The original branch is split into two branches: one from the original "from bus" to the new bus, and
one from the new bus to the original "to bus", both with appropriate fractions of the original branch
impedance and charging. Line connected shunts on the new branches are set such that the line
connected shunts from the original branch remain at the original "from" and "to buses". Circuit iden-
tifiers, ratings, status, metered ends, and ownership follow from the original branch.
If the original branch was a member of a multisection line grouping, the grouping’s definition is mod-
ified to include the two new branches in place of the original branch.
If the working file contains sequence data (see Section 7.2), zero sequence branch parameters are
handled in the same manner as their positive sequence counterparts. If the original branch is
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-151
Power Flow PSS™E-31.0
Modifying the Network Users Manual
involved in a zero sequence mutual coupling, the mutual data arrays are modified and extended as
appropriate. All mutual data changes are tabulated in the Output Bar.
The line tapping process is not sensitive to any interrupt control code options.
As an example, the branch from bus 3003 to 3005 circuit 1, in the savnw.sav power flow case, will
be tapped at a point 40% of the distance from bus 3003. A new bus will be created with the number
3020, a name NEWBUS and a base voltage of 230 kV. Figure 4-117 shows the original topology in
the Diagram View.
In the Tap Line dialog, shown in Figure 4-116, clicking the Select… button will display the Branch
Selection dialog (see Figure 4-118). Selecting a bus in the From bus list will create a list of the To
Buses having branches from that bus. The selection is completed by selecting a bus in the To bus
list. If required, the filter can be used to reduce the listed buses to those in a specified subsystem.
In Figure 4-118, the branch from bus 3003 to bus 3005, circuit 1, has been selected. Clicking the
OK button will revert the process to the Tap Line dialog.
4-152 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying the Network
In the Tap Line dialog, the tap position, 40% of the distance from bus 3003 and the new bus name,
number and Base kV are identified as shown in Figure 4-119. Clicking the OK button will complete
the process and generate a summary report of the action in the output window (see Figure 4-119).
The Output Bar summary report registers the tapping process and also indicates that the mutual
coupling has been modified to take into account that the original line now comprises two lines.
At this point, any Slider diagram established for the original network topology will indicate that the
tapped line is out-of-service. The one-line Slider diagram will need to be modified to show the new
topology with the new bus. Figure 4-120 shows a modified Diagram View of the new topology
around the new bus.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-153
Power Flow PSS™E-31.0
Modifying the Network Users Manual
Figure 4-119. Final Stage in Tap Line and Output View Summary
4-154 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying the Network
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-155
Power Flow PSS™E-31.0
Modifying the Network Users Manual
After selecting the equipment category by clicking on the corresponding tab, the user designates
the individual equipment to be moved and the bus to which the equipment item is to be transferred.
Finally, the Apply button is clicked to complete the transfer. A summary of the action taken is
printed in the Output Bar.
In rerouting branches and three-winding transformers, if the new "to bus" is a dummy bus of a multi-
section line grouping, that line grouping is deleted since the new "to bus" will have three branches
connected to it following the rerouting.
If the branch being rerouted is a member of a multisection line grouping and the original "to bus" is
a dummy bus, the multisection line grouping is deleted; if the original "to bus" is an endpoint bus of
the multisection line grouping, either the grouping is deleted if the new "to bus" is the other endpoint
bus, or the grouping is redefined.
In rerouting a branch that is involved in zero sequence mutual couplings, the mutual arrays are
updated under the assumption that the rerouted branch retains the same couplings as the original
branch.
Control parameters from the destination bus are kept unless the switched shunt at the destination
bus controls the admittance setting of the switched shunt at the original bus. In this case, the control
parameter data items (MODSW, VSWHI, VSWLO, SWREM, RMPCT and RMIDNT) of the original
bus are transferred to the destination bus.
In moving plants, the destination bus must not be a generator bus; all machines at a plant may be
moved to another plant only by moving each individual machine.
4-156 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying the Network
In moving machines and plants, bus type codes are updated appropriately. If any moves result in
the plant entry of an area swing being deleted, an appropriate message is printed. If the current
destination bus is in the same area as the former area swing bus, it becomes the new area swing.
Otherwise, the area swing bus number is set to zero.
Using the savnw.sav power flow case, the 500 kV line from bus 151, which terminates at bus 201
will be moved to terminate at bus 202. The original topology is shown in Figure 4-122.
On the Branch tab, in the Move network elements dialog, the original FROM and TO buses and the
new TO bus are entered directly or by using the Select… button (see Figure 4-123).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-157
Power Flow PSS™E-31.0
Modifying the Network Users Manual
Figure 4-123. Selecting From and To Branch Information for Moving the To
Bus
When using the Select facility, the Branch Selector dialog will display (see Figure 4-124). The
selection of a From bus provides a list of available branches and circuits from which a To bus can
be selected. A Filter facility is available to limit the available bus listings based on subsystem selec-
tion. Clicking the OK button takes the user back to the Move network elements dialog where the
new To bus can be selected.
The terms "From" and "To" in this network element moving process are not related to the
transformer and non-transformer data attributes which relate to windings and taps. Here the
"From" and "To" are used merely to select branches, recognizing that the "To" end is the end which
will be relocated. For three-winding transformers there are three buses to be selected; the From,
To and Last bus. It is the Last bus which can be moved.
4-158 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying the Network
When the moving process is complete, the original one-line Slider file will not be able to display the
new topology. The branch which was moved (in the case of this example, the line from bus 151 to
bus 201) will be indicated as out-of-service. The Slider file will need to be modified to display the
new line termination. Figure 4-125 shows the new display with the new line location and the indi-
cated "line out-of-service" from the original topology. That now non-existent branch can be deleted
from the Slider file. It will no longer be in the network data and will not appear in the Spreadsheet
View or Tree View.
The figure also show the summary of the moving action as printed in the Output Bar.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-159
Power Flow PSS™E-31.0
Modifying the Network Users Manual
Figure 4-125. New Topology Following Branch Move and Output Report
4-160 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying the Network
Click GEXM/GOUT
Click Select...
Figure 4-126. GEXM/GOUT Toolbar Button and Bus Selection for Bus 153
MID230
After bus selection a Diagram View will be generated for the selected bus showing associated lines
and equipment and distant "to buses". The default symbol for "to buses" is the node (see Figure 4-
127 where one of the bus’ symbols has been toggled to a scalable vertical type node). The user is
able to perform the switching actions, data changes and examinations, as listed above, directly from
this Diagram View.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-161
Power Flow PSS™E-31.0
Modifying the Network Users Manual
Figure 4-127. Diagram View for Selected Bus 153 MID230 from Savnw.sav case
4-162 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying the Network
Once the GEXM/GOUT bus is in the Diagram View, subsequently clicking on the "Display
Powerflow results" LF toolbar button, will display powerflow results data on the diagram,
including:
Clicking on the "Display Impedance data" DAT toolbar button, will display impedance and
equipment rating data on the diagram instead of powerflow data (see Figure 4-128).
The view will return to the power flow view by clicking the LF button. It is useful to note, however,
the user can perform switching and data changing operations from the diagram independent of the
view.
4.6.8.1 Using the Data (GEXM) and Load Flow (GOUT) Views
For these notes, reference should be made to Figure 4-127 for the LF view and to Figure 4-128 for
the DAT view.
If the selected bus is a generator bus controlling the voltage at a remote bus, the remote bus
number, name, and base voltage will be tabulated with the other selected bus information. Further,
if the active and reactive power mismatch at the bus exceed 0.5 MVA or kVA, according to the
power output option in effect, the mismatch information will be listed.
Each machine at a selected bus is separately displayed with the machine identifier printed inside of
the generator symbol. In the LF view, the machine loading is shown along with one of the "H", "L"
and "R" flags indicating the current reactive loading condition (see Section 4.4.1.1). In the DAT
view, the machine’s defined power setting and reactive limits are shown.
Load and shunt elements are represented with actual loadings when shown in the LF view and rat-
ings when shown in the DAT view. Load identifiers are shown within the symbol.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-163
Power Flow PSS™E-31.0
Modifying the Network Users Manual
Branches are drawn from the top of the page in ascending "to bus" order (numeric or alphabetic
according to the bus output option in effect). The "to bus" number and name are drawn on the
extreme right of the branch line adjacent to the "to bus" busbar. Placing the cursor on the branch
will pop up the line from bus and to bus numbers/names and the circuit identifier. In the LF view
flows are shown as active and reactive power leaving the "from bus" (the selected bus) and as
active and reactive power arriving at the to bus end. In the DAT view, the R, X and B data quantities
are shown.
For two-winding transformer branches, two transformer symbols are drawn between the flow and
the "to bus". Off-nominal turns ratio and any nonzero phase shift angle are displayed between the
flow and the first transformer symbol and between transformer symbols.
Any three-winding transformer connected to the bus is drawn similar to the two-winding transformer
except one more branch and bus are displayed, and off-nominal turns ratio and any nonzero phase
shift angle are shown only for the winding connected to the bus box.
When the multisection line reporting option is enabled (see Section 1.6.4), the far end "to bus"
(rather than the closest "dummy" bus) of each multisection line connected to the bus being dis-
played is shown as its "to bus".
An asterisk ("∗") is drawn at the metered end of each branch. If a branch is a member of a multisec-
tion line grouping and the multisection line reporting option is enabled, the asterisk indicates the
metered end of the line section adjacent to the bus being displayed and a plus sign ("+") designates
the metered end of the multisection line grouping.
Any DC lines connected to the bus are drawn before any AC branches in ascending DC line number
order, with two-terminal lines listed first, followed by any multi-terminal lines. Power flow conven-
tions for DC lines are as in the Bus based report output format (see Section 4.2.3). Alpha, gamma,
and the converter transformer off-nominal turns ratios are displayed and tagged as in the Bus base
reports. For multi-terminal lines, no "to bus" end conditions are listed.
Any FACTS device with no series element which is connected to the selected bus is drawn to the
left of the bus. It is illustrated with a straight line drawn from the displayed bus and connects to a
rectangular box, which is attached to a shunt symbol. The rectangular box contains a power flow
direction arrow pointing in the direction of the shunt. The FACTS device number is displayed above
the device.
Any series FACTS device connected to the selected bus is drawn to the right of the bus with a line
connecting that bus and its associated terminal/send bus. The series element is illustrated by a
circle containing an embedded arrow and is located midway on the connecting line. The arrow indi-
cates the power flow direction (sending end bus to terminal end bus direction). The FACTS device
number is displayed to the right of the connected bus.
For series FACTS devices with non-zero shunt current and/or bridge active power transfer limits,
when the selected bus is the sending end bus, two additional lines are drawn to represent the shunt
and bridge element connections. The first line is drawn to the right of the sending end bus under-
neath the series element connecting line and stops at a point midway between the sending end bus
and the terminal end bus. Another line is drawn from that point upward to the series element circle.
4-164 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying the Network
The bus along with its network elements can be disconnected directly from the diagram. This oper-
ation is initiated by right-clicking the bus to open the Bus Item pop-up menu and selecting the
Switch option.
When disconnecting items in diagram views, the buses, lines and equipment notation will change
to indicate their out-of-service condition. The line colors, width and style for out of service equipment
are selected in the Diagram Range Checking tab in the Power Flow Data Annotation dialog (right-
click on the diagram item and select Diagram Annotation…; see Section 2.9.2).
If the switch operation is performed on bus 153, the diagram produced will indicate that the bus and
its associated elements are out-of-service (see Figure 4-129). To reconnect the bus, perform the
switch operation again.
Item status can be changed from in-service to out-of-service, or vice versa, by selecting the Switch
option.
If the Network data option is selected, the user is taken directly to that item in the Spreadsheet View
where the data changes can be made. Note also that changes in status can be made in the Spread-
sheet View.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-165
Power Flow PSS™E-31.0
Modifying the Network Users Manual
Figure 4-130. Right-Clicking on Load on Bus 154 to Open Item Pop-up Menu
4-166 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Modifying the Network
To move from the initially selected bus to one of its to buses, all that is necessary is to double click
the to bus node. That node/bus will become the "selected" bus. Figure 4-131 shows the result of
double-clicking on to bus #154 from the diagram shown in Figure 4-127 where the selected bus was
# 153.
Double-click on
bus 154
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-167
Power Flow PSS™E-31.0
Renumbering Buses Users Manual
When the renumbering procedure is initiated, the user is asked to specify the output destination,
which can be the Output Bar or a file. The output tabulation consists of a series of records docu-
menting those buses that have been assigned new numbers. The records are in the format:
old bus number new bus number / bus name and base voltage
When directed to a file, denoted as a Bus Translation File, the output tabulation is useful for the
situation where several power flow power flow Saved Cases of identical network topology but, for
example, different loading levels are to be renumbered. The Bus Translation File may then be used
as input in subsequent executions of the renumbering procedure for the other Saved Cases.
The process is initiated via the Power Flow>Renumber Buses option (see Figure 4-132).
Bus numbers can be renumbered by Number, Name, Packing and by Subsystem. These options
are covered in more detail in the following sections.
4-168 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Renumbering Buses
Within the dialog a Bus Translation File can be specified that defines mappings from a series of old
bus numbers/names to new bus numbers/names, or individual bus numbers/names can be entered
directly in the input fields provided.
When specifying buses in the Old bus number/name and New bus number/name fields a single bus
or a series of buses can be selected individually. Once the renumbering procedure is initiated the
old and associated new bus numbers are output either to the Output Bar or a file selected by the
user. Clicking the Go button will cause the bus numbers to be changed in the power flow working
file. Clicking the Close button will close the dialog.
When specifying a Bus Translation File of type *.trn that file will have the same format as the Data
file created by this bus renumbering process. Consequently, the user can create the "translation"
file when renumbering buses and retain that information to repeat the process on other power flow
data files having the same bus numbering. Specifying the translation file name will avoid having to
repeat the bus selection process.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-169
Power Flow PSS™E-31.0
Renumbering Buses Users Manual
Figure 4-133. Renumber Buses Dialogs for Bus Name and Bus Number
The difference in selecting by number or name will be seen when the Select… button is clicked.
That action will open up an additional dialog in which individual buses can be selected for the
renumbering process. The buses will be listed in ascending order of bus number or alphabetical
order of bus name. As is common with the PSS™E dialog, a filter is provided to reduce the range
of buses from which to make the selection. This is particularly useful for very large data files.
Figure 4-134 shows the different Bus Selection dialogs.
4-170 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Renumbering Buses
It can be seen that the user can enter the starting and ending bus numbers of a selected series of
buses to be packed. In Figure 4-135, buses from 101 to 160 have been selected for packing. There
is no translation file facility. Again the output of the selection process can be sent to the Output Bar
or a file.
If the ending bus number is less than the starting bus number or greater than 999997, an error mes-
sage is generated and the input request remains open. If both the starting and ending numbers are
valid, the bus numbers falling within the specified range are packed sequentially beginning with the
starting bus number.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-171
Power Flow PSS™E-31.0
Renumbering Buses Users Manual
Suppose for example, that bus packing is performed on the range shown in Figure 4-135, for the
savnw.sav case. The original and resulting new bus numbers are shown in Figure 4-136. It can be
seen that the original bus range from 101 to 154 has been packed to a range from 101 to 106.
In the Output Bar the following message is printed indicating how many buses have been modified,
along with a list of the old and new bus numbers. That list could have been sent to a specified output
file.
4-172 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Renumbering Buses
If the user enables the Block bus numbers by area option, when Go is clicked the Block Numbers
by Area dialog will open to facilitate the input of a new bus number range for each interchange area
in the working file (see Figure 4-139).
No bus number changes are implemented until the new number range for each area in the working
case is specified. Consequently, unless non-zero bus numbers are entered to indicate the bus
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-173
Power Flow PSS™E-31.0
Renumbering Buses Users Manual
number ranges for each area in the working file, the renumbering process will be terminated with
the original numbering intact.
Within each area, the new bus number sequence corresponds to either the original bus number
sequence or the bus name sequence, depending on the bus output option in force.
Figure 4-140 shows the result of selecting this renumbering process using the savnw.sav power
flow working file. Each of the three areas in the file will require a new bus number range.
In this example, the three area bus ranges are made consecutive. When the OK button is clicked
in the Block Numbers by Area dialog the renumbering process will be completed and the original
and new bus numbers will be listed in the Output Bar or the user’s designated output file. Figure 4-
140 shows the result of this renumbering example as shown in the Output Bar.
4-174 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Renumbering Buses
In Figure 4-141 it can be seen that when buses within a selected subsystem are to be renumbered,
the user has two options:
As with other renumbering procedures, the result of renumbering can be shown in the Output Bar
or output to a user designated file.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-175
Power Flow PSS™E-31.0
Renumbering Buses Users Manual
The advantage of directing the output of the bus renumbering processes to a file, as described in
the previous subsections, is that a record is available of which bus numbers were changed and what
the new numbers are. The file can provide this information to the process for renumbering buses in
the auxiliary file. Such a file is designated as a Bus Number Translation file and will have a "trn"
extension.
Alternatively, a user-created Bus Number Translation File, containing data records of the following
form, may also be used as the input to the process.
Selection of this option will display the Renumber Buses in Auxiliary Files dialog where the user will
provide information on the type of auxiliary file to be processed, the Bus Number Translation File
name, the specific auxiliary file to be processed and, if required, an output data file (see Figure 4-
143).
4-176 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Renumbering Buses
There is a wide variety of auxiliary files used by PSS™E (see Figure 4-144). Each of these is dis-
cussed in detail in the appropriate sections in the PSS™E manuals.
The output data file is the final piece of information to be supplied by the user. While this is optional,
it is most useful to identify an output file. This file will contain a copy of the processed auxiliary data
file reconstructed with the new numbering. Consequently it will be immediately available for use with
the renumbered Power Flow Data File. The alternative is to allow the reconstructed file to be printed
in the Output Bar.
Note that this renumbering process is not sensitive to any interrupt control code options.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-177
Power Flow PSS™E-31.0
Renumbering Buses Users Manual
• Machines
• Branches
• FACTS devices
• VS DC lines
It should be noted that buses, loads and the elements listed above will be assigned by the user or
will take on a default assignment when the power flow case is first set up. This means that there is
always an existing assignment and that this renumbering process is one of changing assignments
rather than providing an initial one.
In this dialog, tabs may be selected for Area, Owner and Zone assignments. Within each of the tabs
options are available for reassigning buses and loads, a listing of the Areas/Owners/Zones and their
names which are already in use as well as the Areas/Owners/Zones which are not currently in use
but available, and a subsystem selection utility. WIth this dialog it is possible to reassign to Areas,
Owners or Zones which are already in use or those which are not.
4-178 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Renumbering Buses
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-179
Power Flow PSS™E-31.0
Renumbering Buses Users Manual
An example of area renumbering would best explain the process. Suppose that all buses in Area 5
(WORLD) in the savnw.sav power flow case needed to be reassigned to Area 2 (LIGHTCO). Before
the reassignment it is useful to examine the Area information. Figure 4-146 shows via the Spread-
sheet View that there are three Areas with a zero net interchange comprising four inter-area
transactions from Area 1 (FLAPCO).
The Select facility shown in Figure 4-145 allows selection of Area 5 as a subsystem or by identifi-
cation of all buses in the Area to be re-numbered. In this example, let’s select the ten buses residing
in Area 5. Specify the bus number range in the "The following buses" field as "3001 -3018". Then
highlight, in either the Used areas or Unused areas listing, the Area to which the buses will be reas-
signed. For this example, Area 2 was selected and OK was clicked. The results of this process is
recorded in the Output Bar, at a printer or to a file of the user’s choice (see Figure 4-147).
4-180 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Renumbering Buses
As shown in the output displayed in Figure 4-147, because Area 5 no longer has any buses
assigned to it, the inter-area assignments have to be changed. It also indicates that Area 2 now has
17 buses and 4 loads, and that the system swing bus, 3011, now resides in Area 2 where that Area’s
slack bus, 206 already resides.
The modifications to network information will be indicated in the Spreadsheet View (see Figure 4-
148). The inter-area transactions, which previously were identified for Area 5, as transactions A and
B, have now been assigned to Area 2 as transactions 1 and 2 to avoid the conflict. This change was
indicated in the Output Bar shown in Figure 4-147. The total transactions remain the same.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-181
Power Flow PSS™E-31.0
Renumbering Buses Users Manual
When one or more of the branch devices (Branch, FACTS or VSC DC lines) is selected, the Branch
reassignment options field is active and a selection may be made (see Figure 4-150). The following
branch reassignment options are available:
4-182 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Renumbering Buses
• The destination owner has a blank name and the reassignment process assigns to it
the owner name from an owner which has a nonblank name and which is emptied
during the owner reassignment process.
• An owner no longer has any equipment assigned to it.
The owner reassignment process then lists the number of buses, loads, machines, branches,
FACTS devices, and/or VSC DC lines transferred to the destination owner, and the total number of
buses, loads, machines, branches, DC buses, FACTS devices, and VSC DC lines now assigned to
the owner, or, if no changes were made outputs:
When reassigning ownership for machines, branches, and VSC DC lines previously designated as
having multiple owners, each ownership block is assigned to the new owner unless subsystem
specification by owner is enabled. Under subsystem specification by owner, only those ownership
blocks previously assigned to the specified owners are reassigned.
When reassigning ownership for FACTS devices, FACTS devices with no terminal bus specified
(e.g., a STATCON) are not candidates for processing under the "subsystem ties only" series ele-
ment renumbering option. Series FACTS devices are processed using the same criteria as AC
branches and VSC DC lines (subsystem branches only, subsystem ties only, or subsystem
branches and ties).
The owner reassignment process does not change the owner assignments of DC buses internal to
multi-terminal DC lines.
The reassignment process is not sensitive to any interrupt control code options.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-183
Power Flow PSS™E-31.0
Economic Dispatch Users Manual
The Economic dispatch process requires minimum and maximum outputs, incremental heat rates,
fuel costs, and start-up priority rankings for all machines to be scheduled. This data should reside
in source file form in an Economic Dispatch Data File (*.ecd), which is read at initiation of the
procedure.
I,ID,PRIOR,FUELCO,PMAX,PMIN,HEMIN,X1,Y1,X2,Y2,X3,Y3,X4,Y4,X5,Y5,X6,Y6
where:
I Bus number; bus I must be present in the working case and have a nonzero gen-
erator number assigned to it.
ID One- or two-character machine identifier of the machine at bus I whose data is
specified by this record. ID = ’1’ by default.
PRIOR Priority ranking code (> 0). Machines with a priority ranking of zero do not have
their status changed during the unit commitment portion of the process.
Machines with lowest positive priority ranking codes are switched in-service first
even though machines with higher priority rankings may be more economical to
run. Machines with highest priority ranking codes are switched out-of-service
first even though machines with lower priority rankings may be more expensive
to run. PRIOR = 0 by default.
FUELCO Fuel cost for the machine in dollars per MBtu. No default is allowed.
PMAX Maximum machine active power output; entered in MW. If this machine is the
"principal" unit of a dispatch group, this is the sum of the maximum outputs of all
machines in the dispatch group. If defaulted, PMAX and PMIN for this machine
are set to the power limits currently in the power flow case (see Section 3.2.4).
PMIN Minimum machine active power output; entered in MW. If this machine is the
"principal" unit of a dispatch group, this is the sum of the minimum outputs of all
machines in the dispatch group. If PMAX is defaulted, the value specified for
PMIN is ignored and the one currently in the power flow working case is used;
otherwise, no default is allowed.
4-184 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Economic Dispatch
HEMIN Minimum heat input required by the machine when on-line; entered in MBtu/hr. If
X1 (see below) is greater than zero, HEMIN should be specified as the heat input
required at "X1" MW. No default is allowed.
Xi,Yi Points on the incremental heat rate curve; Xi values are entered in MW and Yi
values are entered in Btu/kWh. At least two points, and up to six points, may be
entered. Both X and Y must be in ascending order, with X1 > PMIN and Xn <
PMAX. If this machine is the "principal" unit of a dispatch group, this curve is the
combined curve of all machines in the dispatch group.
For the user’s reference, the PSS™E EXAMPLE directory contains an economic dispatch file,
savnw.ecd, which can be used in conjunction with the power flow case savnw.sav. A plot of those
incremental heat rate curves is shown in Figure 4-151.
The auxiliary program PLINC may be used to plot the incremental heat rate curves of selected
machines. Refer to PSS™E Program Operation Manual, Section 10.5 for details on its use.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-185
Power Flow PSS™E-31.0
Economic Dispatch Users Manual
I,ID,PRIOR,FRACT,PRNBUS,PRNMAC,CODFRC
where:
I Bus number; bus I must be present in the working case with a nonzero generator
number assigned to it.
ID One- or two-character machine identifier of the machine at bus I whose data is
specified by this record. ID = ’1’ by default.
PRIOR Priority ranking code (< 0). A negative priority ranking code signifies that this
machine is a "supplementary" unit of a dispatch group. No default is allowed.
FRACT When CODFRC is zero or negative, the fraction of the total power dispatched for
the dispatch group to be assigned to the "principal" unit. When CODFRC is pos-
itive, the fraction of the total power dispatched for the dispatch group to be
assigned to this "supplementary" unit. FRACT must be greater than zero and
less than one. No default is allowed.
PRNBUS Bus number of the "principal" machine associated with the dispatch group of
which this "supplementary" unit is a member. No default is allowed.
PRNMAC One- or two-character machine identifier of the "principal" machine at bus
PRNBUS associated with the dispatch group of which this "supplementary" unit
is a member. PRNMAC = ’1’ by default.
CODFRC Defines the interpretation of FRACT on this record by the economic dispatch
process. When CODFRC is zero or negative, FRACT is the fraction of the total
power dispatched for the dispatch group to be assigned to the "principal" unit.
When CODFRC is positive, FRACT is the fraction of the total power dispatched
for the dispatch group to be assigned to this "supplementary" unit. CODFRC = 0
by default.
A Standard economic dispatch data record (see Section 4.8.1.1) must be included in the data input
file for machine PRNMAC at bus PRNBUS. Its power output limits and incremental heat rate curve
must be that corresponding to the combination of all machines in the dispatch group.
To specify a dispatch group, any one (and only one) of the machines in the dispatch group must be
designated on a standard Economic Dispatch Data File record (see Section 4.8.1.1); this machine
is referred to as the "principal" unit of the dispatch group. The dispatch data specified on this data
record must be that for the combination of all machines which are members of the dispatch group.
Each of the remaining units in the dispatch, must be specified on a supplementary Economic Dis-
patch Data File record (see Section 4.8.1.2); these machines are referred to as the "supplementary"
units of the dispatch group.
4-186 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Economic Dispatch
The sum of the FRACT values on all of the "supplementary" data records of a dispatch group must
be less than one. When a dispatch group contains more than two machines, the data record for
each of its "supplementary" machines must have CODFRC specified as a positive number, and
FRACT as the fraction of total group power assigned to the "supplementary" machine. When a dis-
patch group contains exactly two machines, CODFRC for the "supplementary" machine may be
specified as a positive or negative number or zero, and FRACT must be specified accordingly (see
Figure 4-152).
The initial service status of each machine in a dispatch group, as determined by the combination of
the type code of the bus to which it is connected and its machine status flag, must be the same:
either all in-service or all out-of-service. If the status of a dispatch group is switched during the unit
commitment calculation, the status of each machine in the dispatch group is changed.
For a dispatch group, at the completion of the dispatch calculation, the dispatch group’s total power
output is split among the machines in the group according to the split fractions FRACT specified on
the data records of the "supplementary" machines in the group (see Section 4.8.1.2).
When PMAX (and hence PMIN) are defaulted in the Economic Dispatch Data File, the machine
limits contained in the working case are used as the dispatch limits (see Section 4.8.1.1). For a dis-
patch group, the sums of the limits of all machines in the group are used as the dispatch limits. In
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-187
Power Flow PSS™E-31.0
Economic Dispatch Users Manual
this case, it is possible to violate the individual machine limits as contained in the working case if
FRACT is not coordinated with the individual machine limits.
When a subsystem of the power flow working case is being processed, the subsystem assignment
of the "principal" unit of a dispatch group is taken as the subsystem assignment of the group. If the
"principal" unit is in the subsystem being processed, its dispatch group is processed even if one or
more of its "supplementary" units is not in the subsystem. Conversely, if the "principal" unit is not in
the subsystem being processed, the dispatch group is not processed even if some or all of its "sup-
plementary" units are in the subsystem.
When the subsystem to be processed is specified by owner, the owners to which machines (rather
than buses) are assigned are used in defining the subsystem of machines to be processed. If a
machine has multiple owners (see Section 3.2.4), the owner specified in the owner/fraction pair with
the largest ownership fraction is assumed to have dispatch responsibility. If this largest ownership
fraction is identical for two or more owners of a machine, the first one in the tables, as shown in the
machine data listings is used.
The iterative dispatch calculation in the economic dispatch process is a binary search technique
with an upper limit of 40 iterations. Convergence is assumed when the difference between dis-
patched power and desired power is less than 0.00001 times the desired power. Convergence
failure, which is usually the result of precision limitations, is alarmed and the economic dispatch pro-
cess continues as if convergence had been achieved.
The subsystem selector is available for the user to identify which specific subsystems of the power
flow case ("Area", "Zone", "Owner", "base kV") or which specific buses are to be processed. The
dispatch is performed on only those machines in the specified subsystem for which valid dispatch
data had been read. Other machines retain their initial status and power outputs.
The user is provided with the facility to identify the Economic Dispatch Data File (type *.ecd) to be
processed and to decide whether of not to base the subsequent dispatch on an existing unit com-
mitment of a new one. If a new unit commitment is selected, all machines in the specified subsystem
with a nonzero priority ranking for which dispatch data had been read are placed out-of-service prior
to commencing the unit commitment calculation. Otherwise, the current unit commitment status
profile is used as the starting point.
4-188 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Economic Dispatch
After defining the subsystem to be processed and identifying the data file, clicking the Go button
will invoke the process and output a summary of the predispatch condition to the Output Bar or
output device of the user’s choice.
This is the result obtained using the savnw.sav power flow case and savnw.ecd file.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-189
Power Flow PSS™E-31.0
Economic Dispatch Users Manual
The first four quantities in the above summary are totals based upon the present power outputs and
dispatch data specified in the data input file for those machines initially in-service in the subsystem
to be processed. The final total is the sum of the present power outputs of those machines to be
processed, and those machines in the specified subsystem for which no dispatch data was provided
and whose outputs will not be changed by the economic dispatching process.
Following the summary of predispatch conditions, the process will prompt the user for additional
information including the Desired load and Desired minimum capacity of units being dispatched
(see Figure 4-154). The values specified for these two quantities should be entered as those
applying to the machines to be dispatched. Specifically, they must not include the power outputs
assigned to those machines within the specified subsystem for which dispatch data was not read.
In Figure 4-154, a new load level has been selected for the savnw.sav power case prior to per-
forming the economic dispatch.
After clicking the OK button, the process commences the unit commitment portion of its calculation.
Note again that the status of any machine with a priority ranking of zero is not changed during the
unit commitment portion of the process but such machines are included in the economic dispatch
calculation. Neither the status nor power outputs of machines for which either no dispatch data was
provided or whose data was alarmed, and of machines outside of the specified subsystem, is
changed during this process.
If the specified desired minimum capacity is greater than the sum of the maximum power outputs
of the machines currently on-line, the unit commitment process places additional units on-line.
Machines with lowest priority rankings are connected first, and, within a given priority ranking, units
with the lowest full load average cost per MW are placed in-service first.
If the specified desired load is less than the sum of the minimum power outputs of the machines
currently on-line, units are taken off-line. Machines with highest priority rankings are disconnected
first, and, within a given priority ranking, units with the highest full load average cost per MW are
placed out-of-service first.
Any time a machine status is changed, a message is printed at the Output Bar. Any processing
errors encountered are alarmed and the user is asked to respecify the desired load and minimum
capacity.
Once a commitment profile satisfying the desired load and capacity constraints has been success-
fully determined, the power outputs of the machines to be dispatched are calculated. Power outputs
are set on the basis of equal incremental costs subject to the machine power output limits.
4-190 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Power Flow
Users Manual Economic Dispatch
The dispatch calculation uses an iterative approach and, at the end of each iteration a convergence
monitor is printed which tabulates:
Results are summarized in the Output Bar or output device selected by the user. For the example
shown in Figure 4-154, using the savnw.sav power flow case, the results summary and conver-
gence monitor are shown in Figure 4-155.
The dispatch data as read from the Economic Dispatch Data File is not retained with the working
case file following termination of the process. A data input file is required for each new execution.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 4-191
Power Flow PSS™E-31.0
Economic Dispatch Users Manual
Figure 4-156. Before and After Machine Terminal Conditions for Economic
Dispatch Example
4-192 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Chapter 5
Contingency Analysis
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-1
Contingency Analysis PSS™E-31.0
Overview: Contingency Analysis Users Manual
• Less probable contingences and/or extreme contingencies can include loss of entire
substations or multiple generators.
Typical dynamic testing will include the same family of contingencies and are augmented by repre-
sentation of the severity of the initiating disturbance which results in the loss of system elements
(three-phase and single-phase faults with normal or delayed clearing times for example).
Acceptable system conditions prior to and subsequent to the contingencies depend on the severity
of the contingency and include:
5-2 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Users Manual
PSS™E-31.0
Siemens Power Transmission & Distribution, Inc., Power Technologies International
Generally, for the normal condition (base case with all elements in service) the user is establishing
acceptable normal conditions of voltage and loading of lines, transformers and generators. Under
these conditions the user will normally solve the power flow with control options activated for trans-
former taps, switched shunts and other devices. Under contingency conditions, depending on the
criteria in use, the user will often block control actions as a function of how equipment in the user’s
system operates.
A limited system analysis can be performed merely by manually performing the steps outlined in
the ’basic process’. A more detailed analysis, specifically of a large system can involve the simula-
tion and examination of thousands of contingencies. For this, PSS™E provides procedures for
automatic testing and reporting. These procedures are described in this chapter.
As power transfers are increased across a network, limits will be reached when the thermal loading
of network elements is exceeded or when voltages fall outside acceptable levels; usually during
contingencies. The procedures for identifying transfer limits, available in PSS™E, are described in
Chapters 6 and 11.
• Power - Voltage curves (P-V) which identify voltage levels within a system as power
transfers increase.
• Reactive - Voltage curves (Q-V) which identify reactive margins versus system voltage
levels.
Both P-V and Q-V curves show limiting operating conditions within a network for both normal and
contingency conditions. The procedures for analyzing these conditions with PSS™E are described
in Chapter 11.
5-4 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
• perform a contingency analysis following the procedure for contingency analysis dis-
cussed in the above section
• prepare outage statistic data
• perform probabilistic reliability assessment
One role of the AC contingency calculation is that of a screening tool whose purpose is to focus
attention on those contingency cases which deserve closer study.
A useful feature is the ability to produce reports in a format appropriate for import to a spread sheet
program.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-5
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
Solution Engine: Select the desired load flow solution engine to be used in obtaining post-contin-
gency states (see Chapter 4).
Dispatch Mode: Dispatch codes for generation dispatch calculations in ACCC analysis.
5-6 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
PT is set equal to the PG. If PB of a machine had been defaulted, it is set to zero; if PB
of a machine is less than its PG, the PB is set equal to the PG.
• Subsystem machines (Pmax): Participating machines are connected to dispatch
subsystem buses and have positive active power generation. Each machine's partici-
pation factor is its maximum active power generation with positive values. If a Unit
Inertia and Governor Data File is specified, maximum machine active power limits are
taken from it; otherwise, the maximum machine active power limits in the working case
are used. PT is adjusted by the rules discussed in Dispatch Mode of Machine Reserve.
• Subsystem machines (Inertia): Participating machines are connected to dispatch
subsystem buses and have positive active power generation. Each machine's partici-
pation factor is its inertia constant. For machines for which no data record is
successfully read, an inertia constant of 4.0 on machine base is used.
• Subsystem machines (Governor droop): Participating machines are connected to
dispatch subsystem buses and have positive active power generation. Each machine's
participation factor is its governor permanent droop. For machines for which no data
record is successfully read, a droop constant of 0.05 on machine base is used.
Dispatch system: Select the subsystem for the generation dispatch. The subsystem is predefined
in a subsystem description file. All subsystem buses with one or more in-service machines whose
active power generation is positive are participating in the generation dispatch. If several islands
exist in the system, participating machines for each island are connected to dispatch subsystem
buses within the island.
Mismatch tolerance: Specify mismatch tolerance. This tolerance will be used to check for the
largest initial active or reactive power mismatch. If exceeded, the process is terminated. This value
is also used as the convergence tolerance in the power flow solution of each contingency case (see
Chapter 4)
To provide a more realistic model of the post-contingency states, one of four dispatch modes and
a proper dispatch subsystem should be selected. Imbalances are then apportioned among
machines within the dispatch subsystem in specified participation factors. For islands without the
swing bus, the bus with largest generation capacity is designated as the island swing bus. When
there is insufficient capacity available from the reserves, load is shed. Reactive power loads are
shed in proportion to real power loads to retain the power factor at affected buses. The following
describes the computation procedures.
1. Identify all islands within the network using a tree searching technique.
2. For each island, assure that a swing bus exists. If there is no existing swing bus, the
bus with the largest generation capacity within the island is chosen as the swing bus.
If no such bus can be found, the entire island is shut down and all load shed.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-7
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
3. Sum the present generator output and generation requirement to find if there is a MW
imbalance. The generation requirement in the island is given by the total of all bus
loads, active power bus shunts, and active power losses, including dc lines.
where:
0
PGEN i is the present dispatch of unit i,
1
PGEN i is the new dispatch of unit i, and
0
1 0 PLOAD i
PLOADi = PLOAD i + -------------------------------------- × DEF
0
∑
( PLOAD i )
where:
0
PLOADi is the present load at bus i,
1
PLOADi is the new load at bus i.
1 0
PGEN i = PGEN i + p i × EXC
5-8 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
• Distribution Factor Data: This must be created using the Build facility found in the
Power Flow>Linear Network option (see Section 5.2.3.2).
• Contingency Output: This is a required file designated by the user as the destination
for the results of the contingency calculations.
• Load throwover Data: This is an optional file, created by the user, that contains data
records of the following form:
IBUS, JBUS
where IBUS and JBUS are bus numbers. If branch outage contingency events isolate
bus IBUS, the user can elect to move the load to bus JBUS. Bus IBUS and/or JBUS
may be a dummy bus of a multi section line grouping. Data records may be input in any
order. Input is terminated with a record specifying an "IBUS" value of zero.
• Unit Inertia and Governor Data File: This is an optional file, created by the user, that
contains generator inertia and governor response data (see Section 5.6.1).
Input for the process of creating the Distribution Factor file is contained in three data files:
• Subsystem Description Data file; relevant subsystems of the working case are speci-
fied in this *.sub file.
• Monitored Element Data file; network elements to be monitored for problems are
specified in this *.mon file.
• Contingency Description Data file; contingencies to be tested are specified in this
*.con file.
CAPITALS Keyword that must be specified exactly as shown. No keyword abbreviations are
allowed.
[…] Items enclosed in square brackets are optional keywords and/or values.
|A| or A|B Specify one from the list separated by, or enclosed in, the vertical bars.
|B|
bsid Bus identifier; this data value must be a bus number when the numbers input
option is in effect, and an extended bus name (twelve character name plus bus
base voltage) when the names input option is in effect. If an extended bus name
contains blanks or special characters, it must be enclosed in single quotes.
ckid One- or two-character circuit identifier.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-9
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
TRACE Enables or disables input tracing. When enabled, each line read from the input
file is written to the dialog output device (normally the user’s terminal) and is ini-
tially disabled.
ECHO file Outputs each input line to a designated file of the user’s choice. If the filename
specification contains any blanks or slashes ("/"), it must be enclosed in single
quotes. This writing of input records is useful when they are being input interac-
tively and the same set of input records will be used in subsequent construction
of a Distribution Factor file.
COM Designates a comment line which is ignored during input processing. Any mean-
ingful comments may be placed on a comment line following the COM keyword.
END End of block structure or end of data input, as appropriate.
In addition, blank lines may be included anywhere in the file. These are ignored during the input file
processing.
The portion of the working case to be contained in each subsystem being defined is specified in the
following SUBSYSTEM block structure:
SUBSYSTEM|SYSTEM [label]
(subsystem specification data record)
.
.
(subsystem specification data record)
END
5-10 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
The optional subsystem labels are used on several record types in the Monitored Element and Con-
tingency Description Data Files. If no label is specified on a SUBSYSTEM record, the label
"UNNAMED n" is assigned to the subsystem, where "n" is a unique integer. Up to one hundred
subsystems may be specified in a Subsystem Description Data File, and each subsystem must be
defined within a single SUBSYSTEM block structure.
BUS bsid
BUSES bsid bsid
The BUSES record is valid only when the numbers input option is in effect and assigns the desig-
nated buses, as well as all buses whose bus numbers fall between the two bus numbers specified,
to the subsystem being defined. For example, the data record "BUSES 15 77" may be used to
select all buses with numbers from 16 to 76, inclusive.
AREA i
AREAS i i
where "i" is an area number. The AREAS record type assigns all buses in a range of area numbers
to the subsystem being defined. For example, the data record "AREAS 5 7" may be used to assign
all buses in areas five, six, and seven to the subsystem.
Similarly, all buses in selected zones and owners may be assigned to a subsystem with data
records of the following form:
ZONE i
ZONES i i
OWNERS i
OWNERS i i
Buses at designated voltage levels may be assigned to a subsystem with records of the following
form, where, as above, the KVRANGE record defines a range of voltage levels:
KV r
KVRANGE r r
Note that, in specifying ranges of bus numbers, areas, zones, owners, and voltage levels, the
second value specified must not be preceded with a minus sign. The second number specified
must be greater than the first.
In addition, a "join group" block structure provides for the specification of a group of buses through
the logical "anding" of two or more of the five selection criteria described above. A "join group" has
the following block structure:
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-11
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
JOIN [label]
(subsystem specification data record)
.
.
(subsystem specification data record)
END
where each subsystem specification data record is one of the simple record types (BUS, AREA,
ZONE, OWNER, KV, or the corresponding "range of" records) described above. The optional JOIN
group label is for the user’s convenience and is neither used in the distribution factor calculations
nor preserved in the Distribution Factor Data File.
Each join group block structure must appear within the subsystem block structure described above.
Both JOIN group block structures and the simple record types may be included within a SUB-
SYSTEM block structure.
The following example defines the subsystem "MY COMPANY", which consists of all buses in area
five, along with all buses in area six which are in zones eight through ten:
PARTICIPATE
BUS bsid r
.
.
BUS bsid r
END
The "r" values are nonzero participation factors which are normally expressed in percent or per unit
of the total SUBSYSTEM generation shift. While individual "r" values may be negative, the sum of
the "r" values within a participate block structure must be positive.
Each participation block structure must appear within the SUBSYSTEM block structure described
above, and must follow the simple record types and/or join group block structures defining the
SUBSYSTEM; that is, it must be the last data record block in the SUBSYSTEM specification.
Each bus specified must reside in the subsystem being processed. Any bus which violates this
requirement or which is disconnected (i.e., its type code is four or greater) is alarmed and ignored.
5-12 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
Up to 1,000 interfaces are allowed, and the total of single branches plus branches contained in all
interfaces may not exceed the number of branches for which PSS™E is dimensioned. Only in-ser-
vice branches are added to the monitored element list.
To specify a single branch for monitoring, the following data record may be used:
[MONITOR] |BRANCH| FROM BUS bsid TO BUS bsid TO BUS bsid ⎡|CIRCUIT| ckid⎤
|LINE | ⎣|CKT | ⎦
If the optional circuit identifier keyword and data value are omitted, a circuit identifier of '1' is
assumed.
As a convenience to save typing, the following block structure may be used to designate a series
of single branches for monitoring where, as above, the default circuit identifier is '1'. Three-winding
transformers cannot be specified using this block structure.
[MONITOR] |BRANCHES|
|LINES |
bsid bsid [ckid]
.
.
bsid bsid [ckid]
END
In specifying a branch with the above records, if it is already in the monitored element list in the
specified direction, an appropriate message is printed and the record is ignored. If a branch is
included in the monitored element list in both directions, the same results are shown in both
directions.
When the Multi Section Line Reporting option is enabled, in-service multi section line groupings
may be specified with the above records. If an in-service member of a multi section line grouping is
specified, the multi section line (rather than the specified member) is added to the monitored ele-
ment list in the same direction as the specified member. When the Multi Section Line Reporting
option is disabled, multi section line groupings may not be specified in the above records; in-service
members of multi section line groupings may be designated and are added as specified to the mon-
itored element list.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-13
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
The following four record types provide for the addition of a group of branches to the monitored ele-
ment list with a single record. Any branch that is included in the subset specified by the following
records, but which is already included in the monitored element list in either direction, is skipped.
For these record types, when the Multi Section Line Reporting option is enabled, multi section
line groupings within the specified subset, but not the individual members of such groupings, are
added to the monitored line list. When the Multi Section Line Reporting option is disabled,
members of multi section line groupings within the specified subset, but not the multi section line
groupings, are added to the monitored line list.
To place all branches in the monitored element list, the following data record may be used:
The following data record may be used to select for monitoring all branches connected to a speci-
fied bus:
Finally, the following record provides for the monitoring of all ties from a specified subsystem, or all
ties between a pair of subsystems:
5-14 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
For a tie branch between a pair of subsystems to be added to the monitored element list, both of
the following must be satisfied:
2. Another bus is in the "to subsystem", and it is not in the "from subsystem".
For the case of disjoint subsystems (e.g., TIES FROM AREA 1 TO AREA 2), the selection of tie
branches is clear and unambiguous. However, in the case of overlapping subsystems (e.g., TIES
FROM AREA 1 TO ZONE 5), the user must be aware of the above rules in specifying "TIES"
records. The possibility exists that, in applying the above criteria, the set of branches included as
ties may not be the same if the "from" and "to subsystems" are interchanged. Consider, for example,
the following area and zone assignments:
Further, assume that a branch exists between each pair of buses. The record "TIES FROM AREA 1
TO ZONE 5" would include the branches 1-3, 2-3, and 4-3, but not 1-2, 1-4, or 2-4. Conversely, the
record "TIES FROM ZONE 5 TO AREA 1" would include the branches 2-1, 3-1, and 4-1, but not
2-3, 2-4, or 3-4.
When the Multi Section Line Reporting option is enabled, the subsystem assignments of the
"dummy buses" of each multi section line grouping are ignored; a multi section line grouping is
treated as a tie branch if and only if its endpoint buses satisfy items (1) and (2) above. When the
Multi Section Line Reporting option is disabled, the multi section line grouping definitions are
ignored and any member of a multi section line grouping satisfying items (1) and (2) above is con-
sidered a tie branch.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-15
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
For specifying sets of tie lines the following data specification record is used:
[MONITOR] |BRANCH| FROM BUS bsid TO BUS bsid TO BUS bsid ⎡|CIRCUIT| ckid⎤
|LINE | ⎣|CKT | ⎦
For specifying individual branches, the following data specification record is used:
When the second form of the INTERFACE record is used (i.e., the token RATINGS and three
values are specified), the designated values are used as the interface’s A, B, and C ratings, respec-
tively. Interface ratings, which are entered as zero, are based on the default rating set indicated by
the program run-time options.
If the optional specification of ratings is omitted, the sum of the appropriate rating set values of each
of the interface members is taken as the interface rating. It is important to note that an interface
rating is usually specified as something other than a thermal limit; for example, contractual or sta-
bility considerations may determine the interface rating to be used.
The following data record defines a voltage band along with a set of buses whose voltages are to
be checked against the band.
5-16 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
where the first "r" value is the lower bound of the per unit voltage band and the optional second "r"
value is the upper bound. If the upper bound is omitted, the upper end of the band is not checked.
The following data record defines voltage drop and voltage rise deviation thresholds along with a
set of buses whose voltage changes in contingency cases from their base case values are to be
checked.
The Contingency Description Data File provides two means by which contingency cases may be
specified. First, individual contingency cases consisting of single or multiple events involving bus
boundary condition and/or branch status changes may be specified in a contingency case block
structure.
Second, the selection of a group of single or double line outage contingency cases may be specified
with a single data record.
CONTINGENCY label [f d]
(contingency event specification record; see below)
.
.
(contingency event specification record; see below)
END
The 12-character contingency label is printed in output reports to identify each contingency. ’f’ and
’d’ are frequency and duration of user specified outages respectively for probabilistic reliability
assessment.
There is a variety of supported contingency event specifications record formats available. They are
described in the remainder of this section.
The outaging of an in-service non transformer branch or two-winding transformer is specified with
the following record where the default circuit identifier is '1'.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-17
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
When the Multi Section Line Reporting option is enabled, multi section line groupings may be
specified with the above records. If a member of a multi section line grouping is specified, switching
the entire multi section line (rather than the specified member) is treated as the contingency
event.When the Multi Section Line Reporting option is disabled, multi section line groupings may
not be specified in the above records. In this situation; members of multi section line groupings may
be designated on OPEN and CLOSE records but only the specified member is switched.
The outaging of an in-service three-winding transformer is specified with the following record where
the default circuit identifier is '1' if this specification is omitted:
|DISCONNECT| |BRANCH| FROM BUS bsid TO BUS bsid TO BUS bsid ⎡|CIRCUIT| ckid⎤
|OPEN | |LINE | ⎣|CKT | ⎦
|TRIP |
Similarly, all windings of an out-of-service three-winding transformer may be placed in-service with
a record of the form:
CLOSE |BRANCH| FROM BUS bsid TO BUS bsid TO BUS bsid ⎡|CIRCUIT| ckid⎤
|LINE | ⎣|CKT | ⎦
The outaging of one winding of a three-winding transformer is specified with the following record
where the default circuit identifier is ’1’ if this specification is omitted:
|DISCONNECT| |THREEWINDING| AT BUS bsid TO BUS bsid TO BUS bsid ⎡|CIRCUIT| ckid⎤
|OPEN | ⎣|CKT | ⎦
|TRIP |
Similarly, one winding of a three-winding transformer my be placed in-service with a record of the
form:
|CLOSE| |THREEWINDING| AT BUS bsid TO BUS bsid TO BUS bsid ⎡|CIRCUIT| ckid⎤
⎣|CKT | ⎦
The winding to be opened or closed is the one connected to ’AT BUS’ end. When opening one
winding of a three-winding transformer, all three windings of the three-winding transformer must be
in-service; when closing one winding of a three-winding transformer, the other two windings of the
three-winding transformer must be in-service.
5-18 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
The outaging of all in-service branches connected to a bus may be specified with a record of the
form:
|DISCONNECT|BUS bsid
|OPEN |
|TRIP |
This command is converted to as many OPEN BRANCH commands as are required before it is
passed to the Distribution Factor Data File.
When the Multi Section Line Reporting option is enabled, each in-service multi section line con-
nected to the specified bus is switched out as a unit. If the specified bus is a dummy bus of a multi
section line, this command is converted to a single OPEN BRANCH command that outages the cor-
responding multi section line. When the Multi Section Line Reporting option is disabled, only the
line section adjacent to the specified bus is outaged for each multi section line connected to the bus.
The next four record types allow the user to specify contingency events in which the load and gen-
eration boundary conditions may be changed at a selected bus. Load and shunt are synonymous
in the linearized network model, and specifying either results in identical contingency events. When
changing generation, the bus must have in-service generation connected to it and it may not be a
swing bus.
The first data record of this type uses the following data record to set the load or generation at a
bus either to a designated value or to a specified percentage of its initial value:
When the optional keyword DISPATCH is included at the end of the SET record, the user may des-
ignate how the change in the bus boundary condition is to be apportioned among selected network
buses rather than having it all assigned to the system swing bus(es). In this case, the SET data
record must be followed by records of the form:
BUS bsid r
.
.
BUS bsid r
END
The "r" values are positive participation factors which are normally expressed in percent or per unit
of the total MW change specified by the contingency event specification record.
The second data record of this type uses the following data record to change the load or generation
at a bus either by a designated amount or by a specified percentage of its initial value:
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-19
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
When the PERCENT keyword is specified, the magnitude of the initial value of the quantity to be
modified is used to determine the amount of the change; i.e.,
r × P orig
P new = P orig + -------------------------
100.
In changing either by PERCENT or MW, when the quantity to be modified is initially positive and
the change is a reduction (i.e., "r" is negative), a negative result is treated as an error condition.
The presence of the optional keyword DISPATCH is handled as described above for the SET data
record.
The third and fourth data records of this type are similar to the CHANGE record, except the direction
of the change is defined by the first keyword, and "r" must be a positive number:
To transfer load or generation from one bus to another, the following data record is used:
r × P orig
P sh = -------------------------
100.
where Porig is initial load or generation, as appropriate, at the "from bus". The power shift is then
subtracted from the original power at the "from bus" and added to the original power at the "to bus".
When the quantity to be modified at the "from bus" is initially positive, a negative post-shift power
at the "from bus" is treated as an error condition.
When generation is being transferred, the "from bus" must have in-service generation. If the
"to bus" is not a generator bus, an appropriate message is printed and the power shift is treated as
negative load at the "to bus". Either of the two buses may be a swing bus.
An in-service machine may be removed from service using the following data record:
5-20 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
Similarly, an out-of-service machine may be placed in-service with a record of the form:
In-service DC lines and FACTs devices can be blocked using the following data record:
where the four tokens in the selection list allow access to two-terminal dc lines, multi-terminal dc
lines, VSC dc lines, and FACTS devices, respectively.
A series of double line outage contingency cases are designated with the following data record.
All branches within a specified subsystem, can be outaged, either singly or in pairs, by using the
following data record.
The BUSDOUBLE record is more restrictive than the DOUBLE record. For each bus in the specified
subsystem, it generates all combinations of double line outage contingencies for all branches
between that bus and other subsystem buses. BUSDOUBLE may be viewed as considering single
events in substations which affect pairs of branches connected to a substation.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-21
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
The PARALLEL record is more restrictive than the BUSDOUBLE record. It generates double line
outage contingencies only for parallel branches (i.e., for each contingency case, the two branches
being outaged connect the same pair of subsystem buses). Three-winding transformer contingen-
cies are not generated by the PARALLEL record. PARALLEL may be viewed as considering single
events on rights-of-way which affect pairs of branches on a right-of-way.
In using the SYSTEM or SUBSYSTEM keywords, the "label" must correspond to a subsystem label
specified in a previously accessed Subsystem Description Data File (see Section 5.2.2.3).
Finally, the following data record provides for the outaging, either singly or in pairs, of all ties from
a specified subsystem or all ties between a pair of subsystems:
For these record types, when the Multi Section Line Reporting option is enabled, the outaging of
a multi section line grouping within the specified subset is treated as a contingency event; the entire
multi section line is outaged. When the Multi Section Line Reporting option is disabled, individual
members of multi section line groupings within the specified subset (rather than entire multi section
line groupings) are outaged.
The SKIP block structure is used to specify individual branches which are to be excluded from out-
aging in contingencies generated as a result of subsequent SINGLE, DOUBLE, BUSDOUBLE, and
PARALLEL contingency specification records. Each SKIP block structure is specified as follows:
SKIP
(branch specification record; see below)
.
.
(branch specification record; see below)
END
Non-transformer branches and two-winding transformers are specified on branch specification
records using the following record format:
Branches specified in a SKIP block structure apply only to SINGLE, DOUBLE, BUSDOUBLE, and
PARALLEL contingency specification records which are below it in the Contingency Description
5-22 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
Data File. Multiple SKIP block structures are allowed, and each SKIP block structure appends to
the list of branches to be omitted from outaging as a result of subsequent automatic contingency
specification records.
When the multi-section line reporting option is enabled and a branch which is a member of a multi-
section line is specified, the multi-section line is excluded from outaging. When the multi-section line
reporting option is disabled and a multi-section line is specified, an error message is printed and the
record is ignored.
In the dialog (Figure 5-3), the data files available in the PSS™E EXAMPLE directory have been
selected. They can be used for testing the process. The other file required is the user’s destination
file for the output. This can be a new file or a previously built file which can be written over. It will be
a *.dfx type file.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-23
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
The building process reads the Contingency Description Data File, updating internal arrays and
transferring the contingency definitions into the Distribution Factor Data File. Any contingency case
specifications in which errors are detected are alarmed and skipped.
The first check box gives the user the option of having the branches in the monitored element list
sorted in the contingency analysis report. If the box is checked, branches are sorted in ascending
numerical or alphabetical order according to the bus output option currently in effect. Branches are
sorted by "from bus", and, for each "from bus", by "to bus" and circuit identifier. If the box is not
checked, monitored branches remain in the same order in which they were specified in the Moni-
tored Element Data File. In either case, interfaces are reported after all monitored branches in the
order in which they were specified in the Monitored Element Data File.
For AC Contingency analysis, the second check box should remain unchecked and the process ter-
minated with the OK button. Such a Distribution Factor Data File is specified not only for AC
contingency analysis but also in transmission access analyses described in Chapter 10.
The second check box should be checked to build a distribution factor file suitable for DC contin-
gency testing (Section 5.5.2) and linearized transfer limit analyses discussed in Chapter 6.
Since the information stored in the Distribution Factor Data File are a function of data organization
and network topology in the working case, it follows that it must be re-executed before performing
the AC contingency analysis any time one or more of the following occurs:
5-24 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
The distribution factor file building process is sensitive to the Bus Input option. That option setting
is, at the time of building governs the manner in which buses must be identified (i.e., either bus
numbers or extended bus names) in the Linear Network Analysis Data Files which are used in the
building process. The setting of the Bus Input option in subsequent executions of the AC contin-
gency analysis must be identical to that which existed when the distribution factor file was built.
A Distribution Factor Data File, and therefore the corresponding Monitored Element Data File, must
specify at least one monitored branch. This applies even if one or more interfaces are specified or
if the Distribution Factor Data File is to be used only for AC contingency calculations and only
voltage violations are of interest.
Care should be taken not to include unnecessary END statements in the Linear Network Analysis
Data Files. END statements are used to indicate the termination of block structures as well as the
termination of the data input stream. Improperly placed END statements are often interpreted by
activity DFAX as an end of input data signal. Symptoms of these conditions can occur during the
execution of activities that use such a Distribution Factor Data File; they include monitored elements
that are omitted from output reports and contingency cases that are skipped.
2. For each criterion established in (1), define a scalar mathematical function which has
a large value for contingencies which stress the system relative to that criteria, and a
small value for those which do not; this function is called a "performance index". The
performance index should be such that contingencies resulting in system conditions
yielding large valued performance indices are considered more severe than system
conditions with smaller performance indices.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-25
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
3. Derive an efficient and accurate procedure for calculating these performance indices
for a large number of possible contingencies.
The ranking process in PSS™E is able to calculate contingency rankings based on either or both
of the following criteria:
The set of monitored branches in the overload ranker is as defined in a Monitored Element Data
File. This is normally the same set of monitored elements which are specified in the building of a
Distribution Factor Data File, as described previously in Section 5.2.2.1.
where:
The set of monitored branches in the voltage ranker is normally all branches in the working case.
The user may elect to omit those branches for which no rating is specified in a selected rating set.
The performance indices are calculated in PSS™E using the ranking algorithm described in An
Advanced Contingency Selection Algorithm by T.A. Mikolinnas and B.F. Wollenberg, IEEE Trans-
actions on Power Apparatus and Systems, Vol. PAS-100, No. 2, February, 1981, pp. 608-617. This
5-26 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
algorithm provides for the evaluation of the performance indices described above without requiring
post-contingency branch flows.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-27
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
MW mismatch tolerance: If the largest initial active power mismatch exceeds the specified MW
mismatch tolerance, the user is given the opportunity to terminate the ranking process.
Small reactance threshold: The "performance index" calculation used in ranking is inaccurate for
the outaging of branches with "small" reactances. All branches from the list of contingencies created
by the ranking process whose magnitude of reactance is less than or equal to this threshold have
their performance indices explicitly calculated. The contingency list is created based on the user’s
subsystem selection, (see below).
Allow ties from subsystem as contingency: The group of branches which may be outaged are
defined according to the subsystem selected by the user in the Select facility of the dialog. The box,
if checked, will allow the inclusion in the contingency list, of both the selected subsystem branches
5-28 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
and ties from the subsystem to other buses in the network. If the box is not checked, only branches
from within the designated subsystem will be included.
Number of contingencies in file: This defines the number "n" of line outages from the overload
ranking to be included in the output of the ranking process. A value of zero for this solution param-
eter causes the process to bypass the overload ranking calculation.
Number of mach. contingencies in file: This defines the number "m" of machine outages from
the overload ranking to be included in the output of the ranking process. The overload ranker is
applied to generating machine outages by assuming that the generation deficiency is redispatched
among remaining machines and that the new dispatches cause changes in branch loading. The dis-
patch is always based on reserve. A value of zero for this solution parameter causes the process
to bypass the machine overload ranking calculation.
Contingency case rating and percent of rating: These define the loading limits to be used in cal-
culating overload performance indices. The default rating set is the one established as the default
rating set program option setting.
Convert ratings to estimate MW ratings: If this is checked, ratings of monitored branches are
converted to estimated MW ratings based upon each monitored line's Mvar loading at the metered
end in the base case AC solution.
Number of (voltage) contingencies in file: This defines the number "k" of voltage contingencies
to be included in the output of the ranking process. A value of zero for this solution parameter
causes the process to bypass the voltage ranking calculation.
Lines used in voltage ranker PI: This defines the network branches which are to contribute to the
voltage ranker performance index. Either all network branches are used or only those branches
having a nonzero value in the designated case rating set.
• The number of overload and voltage contingencies are both zero and contingencies
resulting in islands are not included.
• Generators have been converted.
• Any non type four bus is not connected to a type three bus through an in-service branch
• largest active power mismatch corresponding to the present AC solution voltage vector
in the working case is greater than the MW mismatch tolerance solution parameter
specified above.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-29
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
The user has the option of limiting the contingency list by Area, Owner, Zone, BasekV and Buses
or including all branches. The ranking process will assume the user’s designated subsystem as a
basis for construction of the contingency list to be ranked.
In Figure 5-6, the user can supply Subsystem and Monitored Element Description Data Files. That
facility is available, however, only if overload ranking is enabled.
The ranking process establishes subsystem definitions and constructs a monitored branch list from
these two files, respectively. It should be noted, however, that the ranking process excludes from
the monitored branch list any branch with a zero (or negative) rating in the rating set specified. It
also ignores any interface definitions.
The contingency ranking algorithm is unable to handle zero impedance lines as contingent or mon-
itored branches. Consequently, if any zero impedance lines are present in the contingency list, the
monitored element list for the overload ranker (if overload ranking is enabled) or the monitored ele-
ment list for the voltage ranker (if voltage ranking is enabled), zero impedance line modeling is
temporarily disabled and a new ordering of network buses is determined automatically. The optimal
ordering process in PSS™E is used to determine an ordering of the network buses such that
sparsity is maintained as the Jacobian matrix is triangularized for AC network solutions or the
system admittance matrix is decomposed into its triangular factors in activities for linearized net-
work analyses.
5-30 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
If overload ranking is enabled, the "n" contingencies with the largest performance indices are output
in the form of Contingency Description Data File records. Similarly, if voltage depression ranking is
enabled, the "m" contingencies with the largest performance indices are output in the form of Con-
tingency Description Data File records. Finally, if islanding contingency output is enabled, any
contingency which results in the formation of a swingless island and whose base case DC power
flow loading exceeds the threshold specified is output in the form of Contingency Description Data
File records.
Figure 5-7 shows a subset of the Contingency Description Data file produced by the ranking pro-
cess using the savnw.sav power flow case. It can be seen that each contingency included in the
ranked set is identified with either an overload or a voltage label and independently numbered.
The use of a single number to characterize a system condition is convenient for ranking purposes.
It does, however, have its limitations. For example, it is possible for a contingency which results in
a number of heavily loaded lines but no overloaded lines to be ranked equally with a contingency
which produces one or two overloaded lines with other lines being relatively lightly loaded. This is
not necessarily a deficiency; it is quite appropriate to conclude that both of these system conditions
deserve further study.
The performance indices defined above, and hence the severity rankings which are based on them,
are dependent both on (1) network topological and parametric data and (2) the system operating
point. New ranking should be performed if any of the following network changes are made:
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-31
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
Figure 5-7. Typical Contingency Description File from the Contingency Ranking Process
5-32 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
Further, boundary condition changes (e.g., changes to loads, machine loadings, etc.), while not
invalidating a Distribution Factor Data File, may affect the contingency rankings. Boundary condi-
tion changes which have only a minor impact on line loadings are not likely to significantly affect the
rankings; changes such as increasing an area's load by ten percent or tripping a large unit and dis-
patching its previous power output among other machines in the system are likely to have a
significant effect on line flows which in turn could significantly alter the contingency rankings.
The contingency ranking algorithm is not able to accurately calculate performance indices for
branches with "small" reactances. For any branch in the contingency list whose reactance magni-
tude is less than or equal to the reactance threshold (see Figure 5-5 where the default value of
0.0005 is shown), the standard calculation is bypassed and its performance indices are explicitly
calculated. The small reactance threshold value should always be at least as large as the zero
impedance line threshold tolerance (see Section 3.2.5.1). Experience to date indicates that the
default value is conservative and for most systems it could safely be reduced. For systems with
small impedance lines, one could test the adequacy of this threshold by calculating two sets of over-
load rankings using different threshold values. If the performance indices for the outaging of small
reactance branches are essentially the same, the smaller threshold value may be used.
When the Multi Section Reporting option is enabled, the subsystem assignments of the two end-
point buses of each multi section line are considered (rather than those of any of its dummy buses)
in adding the branch to the contingency list. If a multi section line is added to the contingency list,
the line section at the metered end of the multi section line is considered to be the outaged element.
The performance indices which result are correct unless there is any load or generation present at
any of the dummy buses of the multi section line.
For each three-winding transformer in the contingency list, performance indices are calculated for
the outaging of each in-service winding in turn, and the largest of these is taken as the performance
index for the entire transformer.
In constructing the contingency list, parallel lines between the same pair of buses which have iden-
tical impedances, loss estimates, and line shunt and phase shift active power injections (i.e., they
are identical in the linear network model used by the ranking process) are not all included in the
contingency list. Only one from among such a group of lines is needed. The ranking process does
not check for identical three-winding transformers connecting the same three buses.
If both overload and voltage depression rankings are being determined in the same execution of
the ranking process, the overload rankings are calculated first and any branch which is output by
the overload ranker is removed from the contingency list prior to calculating the voltage rankings.
The Contingency Description Data File constructed by the ranking process is a standard source file
which may be edited by the user prior to its being used in the building of a Distribution Factor file.
Bus identifiers are written as bus numbers when the Numbers Input option is in effect, and as
extended bus names when the Names Input option is in effect. That is, when the Contingency
Description Data File produced by the ranking process is submitted for building the Distribution
Factor File along with the same Subsystem Description and Monitored Element Data Files which
were used for ranking, the files are compatible with each other.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-33
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
As shown in Section 5.2.1, in order to launch the contingency calculation solution process select
the Power Flow>Solution>AC contingency solution (ACCC) option. This will open the AC
Contingency Solution dialog shown in Figure 5-1 which is reproduced here for reference.
When selected this process will alarm and terminate if generators are converted. It then checks that
each non type four bus is connected back to a type three (swing) bus through the in-service AC
network. If any violations are detected, an appropriate message is printed and the process is
terminated.
As noted, the dialog prompts the user for various inputs, including: a mismatch tolerance, Newton
solution parameters, a choice between two Newton type solutions, and the names of three files.
Selecting the Close button terminates the process.
The user is required to enter the name of the Distribution Factor file which is build using the process
described previously in Section 5.2.1 and select a Contingency Output file to which the results of
the contingency analyses will be written. The Load Throwover Data file (Section 5.2.2) is optional.
5-34 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
Once the control and solution options together with the required filenames have been specified,
select the Solve button to initiate the calculations.
The AC contingency solution process then sets up PSS™E working memory, the working files and
temporary scratch files in preparation for the contingency case power flow solutions. This process
uses either the fixed slope decoupled Newton-Raphson iterative power flow solution algorithm or
the full Newton-Raphson method.
The contingency label and contingency events of each contingency case are logged at the progress
output device as the solution process encounters it. A message identifies any network conditions
that fail to converge or which are skipped.
The AC contingency solution process responds to the following interrupt control codes:
• The AC Contingency Single Run Report function (see Section 5.2.6.1) may be used to
produce a variety of tabular and spreadsheet output reports of results from a single AC
Contingency Solution Output File.
• The AC Contingency Multiple Run Report function (see Section 5.2.6.2) may be used
to produce a variety of tabular reports of results from up to nine AC Contingency Solu-
tion Output Files.
• The auxiliary program AcccBrwsGrid (see Section 5.2.6.3) may be used to perform
spreadsheet-like manipulations of the results from a single AC Contingency Solution
Output File.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-35
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
5-36 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
The contingency analysis report options can be specified on the AC Contingency Reports Dialog.
The options are described as follows:
Base Case Rating and Contingency Case Rating: Base case and contingency case rat-
ing and the Percent of flow rating define the line loading limits used in determining over-
loads in base case and contingency cases respectively. Defaults are the default rating set
program option (see Section 1.6.4).
Report format: The available options list allow the user to select from among:
• An overload report having a format appropriate for import to a spread sheet
program.
• A loading table having a format appropriate for import to a spread sheet program.
• An available capacity table formatted for import to a spread sheet program.
• An overload report having a format appropriate for visual inspection (non-spread
sheet).
• A loading table having a format appropriate for visual inspection (non-spread
sheet).
• A report of the non-converged network conditions in a format appropriate for import
to a spread sheet program.
• A report of overloads and voltage violations in each network condition which cor-
rective actions are specified to alleviate the violations, overloads and voltage vio-
lations in corresponding post-corrective action network condition, as well as
specified corrective actions, having a format appropriate for visual inspection (see
Section 5.3.8 for corrective action analysis).
Exclude interfaces from report: Interface loadings may be excluded from all reports by
checking this box.
Perform voltage limit check: Voltage limit checking may be enabled by checking this box.
The user selects those subsystems whose bus voltages are to be monitored, the types of
voltage check (voltage band or deviation from base case values), and threshold values by
specifying records in the Monitored Element Data File (see Section 5.2.3). In the dialog,
however, is the facility to specify the Minimum contingency case voltage change for range
violations. If voltage checking is enabled, buses whose out-of-limits voltages in contingency
cases differ from their base case voltages by less than this minimum change parameter are
omitted from any voltage range checking reports.
Exclude elements with base case loading violations from contingency reports: To
include or exclude monitored branches and interfaces which experience loading violations
in the base case from being checked and reported in overload reports of contingency
cases.
Exclude elements with base case voltage violations from contingency reports: To
include or exclude monitored buses which experience voltage range violations in the base
case from the corresponding check in contingency case reports. This flag applies only to
the voltage range violation checks of the overload reports.
Exclude cases with no overloads from non-spreadsheet overload: This box can be
checked to limit the number of records appearing in the non-spread sheet overload report.
If the box is not checked, the report will identify all network conditions and it may indicate
that some network conditions have no overloaded monitored elements.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-37
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
Report post-tripping simulation solutions: By checking the box, each post-tripping network
condition which satisfies the filter criteria is included in reports from 1 to 6, otherwise post-
tripping network conditions are excluded from reports from 1 to 6 (see Section 5.3.6 for trip-
ping simulation).
Filter Criteria: The converged network conditions included in a report may be limited by
filter criteria. Only those contingencies that satisfy the filter criteria are reported. The follow-
ing filter criteria are user assigned:
• Number of low voltage range violations
• Number of high voltage range violations
• Number of voltage deviation violations
• Number of buses in largest disconnected island
When voltage limit checking is enabled, a network condition is included in the report if the
following conditions are satisfied:
• The number of buses in the largest disconnected island is greater than or equal to
the threshold.
• The number of violations of all three voltage violation categories is greater than or
equal to each respective threshold.
When voltage limit checking is disabled a network condition is included in the report if the
number of buses in the largest disconnected island is greater than or equal to the threshold.
Maximum elements in available capacity table: This limits the total number of records
(monitored elements) which may appear in the table, and the Cutoff threshold for available
capacity table parameter excludes any monitored element whose available capacity
exceeds this threshold.
Minimum contingency case flow change for overload report: Overloaded branches in
contingency cases whose contingency case flows differ from their base case flows by less
than this parameter are omitted from the overload report.
The Non-converged networks selection from the Report format field will identify the network con-
ditions that fail the convergence criteria. The convergence criteria conditions include:
• an AC contingency solution process termination for the network condition of: "MET
CONVERGENCE TOLERANCE", or "ITERATION LIMIT EXCEEDED", or "TERMI-
NATED BY NON-DIVERGENT OPTION",
• a largest bus mismatch magnitude that is less than the Bus mismatch tolerance,
• and a system mismatch magnitude that is less than the System mismatch tolerance.
The AC contingency report process responds to the following interrupt control codes:
5-38 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
Details on the significance of the input parameters to the AC Contingency Multiple Run Report func-
tion and on the operation of the AC Contingency Multiple Run Report function are given in Section
Section 4.114.5 of the PSS™E Program Operation Manual. Details on the content of the reports
which can be produced by the AC Contingency Multiple Run Report function are given in
Section 4.114.6 of the PSS™E Program Operation Manual.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-39
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
The process and file path are shown in Figure 5-11. Remember that the *.con file can be partially
constructed using the Ranking process in Section 5.2.4.
5-40 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
end of the branch with the larger current loading. An asterisk ("∗") is printed between the bus
number and name of the bus at the end of the branch with the larger current loading.
For monitored transformers, the percent loading is either the percent current or the percent MVA
loading, according to the transformer percent loading units program option setting. For monitored
three-winding transformer windings, both the MVA loading and percent loading are calculated at the
winding bus. For monitored two-winding transformers, both the MVA loading and percent loading
are taken from the end of the branch with the larger MVA loading. An asterisk ("∗") is printed
between the bus number and name of the bus at the end of the transformer with the larger MVA
loading.
During the construction of the Distribution Factor Data File, when the Multi Section Line Reporting
option is enabled, all members of each monitored multi section line are checked for overloading.
For each such line section reported, both the branch itself and the multi section line of which it is a
member are identified in the overload report.
The flow across an interface is taken as the sum of the MW flows of its members. For three-winding
transformer windings, the MW loading is calculated at the winding bus as power flowing into the
transformer. For other members, the MW flow is calculated at its metered end in the "from bus" to
"to bus" direction. The percent loading for each interface is its percent MW loading based on its MW
loading and its interface MW rating from the selected rating set.
The percent of flow rating does not affect the values printed as monitored element ratings in all
report formats.
If a line outage contingency forms an island with no type three (swing) bus, a singular sub matrix is
formed. In the overload report, any monitored branch which resides in the swingless island, as well
as any interface which includes such a branch as a member, is omitted. In the loading table, such
monitored elements have zero reported as their flows. Any bus in a swingless island is omitted from
the voltage report.
When the Perform voltage limit check is enabled, the overloaded monitored element report for
each system condition is followed by the voltage violation report. The voltage violations report is
presented in groups corresponding to the voltage monitoring data records specified in the Moni-
tored Element Data File.
Each "voltage range" record results in a tabulation of those buses from the set of buses defined on
the data record whose voltage is below the low voltage threshold (i.e., the first "r" value on the data
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-41
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
record), followed by the list of buses whose voltage is above the high voltage threshold (i.e., the
second "r" value on the data record). For contingency cases, if the voltage change at a bus from its
value in the base case is less than the minimum contingency case voltage change for range viola-
tions parameter, the bus is omitted from the report.
Each "voltage deviation" record results in a tabulation of those buses from the set of buses specified
on the data record whose voltage drop from their base case values exceeds the voltage drop
threshold (i.e., the first "r" value on the data record), followed by the list of buses whose voltage rise
exceeds the voltage rise threshold (i.e., the second "r" value on the data record).
For each bus printed, both its contingency case and base case values are printed. Report blocks
are printed in the order in which the Monitor Voltage data records are contained in the Monitored
Element Data File. Any report block for which no violations are detected is omitted from the report.
An example spreadsheet overload report is shown, partially in Figure 5-13a and 5-13b overleaf.
The report shows initially the rating set and percentage used for checking overloads, followed by
the files used to perform the contingency analysis.
The overload report lists the monitored elements which suffer overloads and the name of the con-
tingency causing the overload. To the right of that listing is the branch Rating, the post-contingency
Flow and the post-contingency flow’s percentage of rating. It should be noted that the first branch
listed, which is from bus 153 to bus 154 has a rating of 350 MVA, an post-contingency flow of 343.2
MVA and a percentage loading of 117%. While the MVA flow is apparently less than the branch
rating, it must be remembered that the rating is based on branch current capacity and 100%
voltage.
where:
Ebase = the base voltage in volts of the bus to which the terminal of the branch
is connected.
Irated = the rated phase current in amps.
For this contingency, the MVA flow shown is concurrent with a voltage of 0.832 pu. This corre-
sponding level of current is 17% higher than the branches current capacity.
The monitored interface listed as suffering an overload is identified in the jdmsavnw.mon file, indi-
cating that the interface comprises the three branches shown (see Figure 5-12).
5-42 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
Figure 5-13. Overload Report from AC Contingency Analysis
b.)
a.)
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-43
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
Following the overloaded element list, the report shows buses where voltage falls outside the spec-
ified range which has an upper threshold of 1.50 pu (a value of 1.05 is more adequate) and a lower
threshold of 0.93 pu. The contingency initiating the voltage reduction is indicated by the bus
number. Note that the list of buses outside the range is limited for only two in Figure 5-13.
Finally, following the listing of the overloaded elements and buses outside Range, the report pre-
sents a legend indicating for each contingency name, the details of the disturbance.
In the non-spread sheet overload report, for each monitored element printed, the pre-contingency
and post-contingency loadings, the rating and the post-contingency percent loading are listed.
In the non-spread sheet format, results are reported in tabular form with four contingency cases per
table. Each group of contingency cases contains a page summarizing the contingency cases per-
formed. For each contingency, the contingency label and the events defining the contingency are
listed.
The summary page is followed by the loading table. For each monitored element, this table lists its
rating, loading, and percentage loading in the base case network solution, and the loading and per-
centage loading for each of the contingency cases reported. MVA loadings are printed for branches
and MW loadings reported for interfaces. Percentage loadings are calculated as described above.
Any percentage loading above the specified percentage threshold is followed by an asterisk ("∗").
When the Multi Section Line Reporting option is enabled, all members of each monitored multi
section line are reported.
In the spread sheet format, the monitored flow results are reported in a table that include the fol-
lowing fields: the monitored element description, the network condition label, the element’s rating,
the element’s flow, and the element’s percent loading. A subsequent table identifies event descrip-
tions for each network condition label.
Single branches are listed first, either in the order in which they were specified in the Monitored Ele-
ment Data File, or in ascending numerical or alphabetical order, according to the option selected
during the building process of the distribution factor file. Unless excluded, interfaces are listed in the
order in which they were specified.
If Perform voltage limit check is enabled, the loading table is followed by voltage violation report
blocks corresponding to the voltage monitoring data records specified in the Monitored Element
Data File. In the non-spread sheet format, the report is limited to only those buses with voltage vio-
lations. In the spread sheet format, the report includes all buses identified by the monitoring data
records.
Figure 5-14 shows a partial sample of a loading report obtained using the savnw.sav power flow
case.
5-44 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
Figure 5-14. Sample Loading Report
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-45
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
It can be seen in the report that there are eleven monitored elements two of which are defined inter-
faces. Their ratings, flow and percentage loadings are listed for the base case and subsequently for
each contingency for which a converged case was obtained.
The two parameters which may be assigned to control the contents of the available capacity table
are the:
Base case (the column headed BASE) and worst case (MAXIMUM) loadings are MVA loadings for
branches and MW loadings for interfaces,. Worst case percentage loadings are calculated as
described above for the overload report. For non transformer branches, current loadings, calculated
as in Section 4.4.5.1.3, are listed in the column headed "IMPACT". For transformer branches the
IMPACT is MVA loading and for interfaces the IMPACT is MW loading. An "available capacity"
index (the column labeled AVAILABLE) is listed for each tabulated monitored element. The "avail-
able capacity" index is the difference between the RATING and the IMPACT.
In the available capacity report, monitored elements are printed in order of increasing "available
capacity" index. Clearly, elements with negative indices are overloaded in the "worst case" system
condition.
This report is terminated with descriptions of those contingency cases which were identified as
"worst case" system conditions for one or more monitored elements. This contingency case sum-
mary lists contingency cases in the order in which they were calculated.
Figure 5-15 shows the capacity report for the savnw.sav power flow case. It can be seen that the
Interface West suffers the greatest capacity deficiency, followed by the branches from bus 154 to
buses 153 and 203. Other listed branches and interface show, for the contingencies tested (and
converged) an available capacity for increased flow.
5-46 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
Figure 5-15. Sample Capacity Report from the savnw.sav Power Flow Case
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-47
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
The user selected values of Bus mismatch tolerance and System mismatch tolerance are iden-
tified following the report title. A table of non-converged networks is presented that identifies: the
network condition label, the largest bus mismatch magnitude, the system mismatch magnitude and
the termination condition from the AC contingency solution process. A subsequent table identifies
event descriptions for each network condition label.
For the savnw.sav power flow case, Figure 5-16 shows the Report. It can be seen that five contin-
gencies have failed to converge. The user, at this point has the option of re-testing the AC
contingencies using the non-divergent power flow solution with this automated approach or to
examine each contingency heuristically using a variety of solution methods and solution controls.
Often the problem is a lack of voltage support.
5-48 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
Figure 5-16. Non-Converged Network Report Example
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-49
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
Each network condition that satisfies two conditions is included in the non-spread sheet corrective
action report. One is that a network condition causes violations, and corrective actions are specified
for the network condition to relieve the violations. After each network condition is solved, flow over-
loads and bus voltage violations are identified by the operating limits specified prior to multiple level
contingency analysis. Flow limits are Contingency case rating and percent of rating specified in
Multiple Contingency Analysis Tab prior to multiple level contingency analysis; 100.0 percent of
rating set program settings by default. Voltage limits are taken from Monitored Element Data File.
Another condition is that network conditions must satisfy the filter criteria.
The corrective actions results also depend on running mode specified prior to multiple contingency
analysis. The running mode is specified according to selections of three options in contingency
analysis: perform multiple contingency analysis, perform tripping simulation (see Section 5.3.6) and
perform corrective actions (Section 5.3.8). When contingency analysis is initiated with perform trip-
ping simulation, flows and voltages in post-tripping network conditions are checked against limits,
corrective actions are then specified to alleviate flows and voltages violations if any.
To reproduce the complete sequences that had been simulated, and present corrective actions and
violations that had been identified and activated corrective actions during contingency analysis,
some options in AC Contingency Single Run report are not allowed to select, but set by programs
when the report option is corrective action report. Exclude interfaces from report is not checked,
and the box of Perform voltage limit check is checked. Boxes of Exclude elements with base
case loading violations from contingency reports, Exclude elements with base case voltage
range violations from contingency reports and Exclude cases with no overloads from non-
spreadsheet overload report are unchecked. Report post-tripping simulation solutions is
checked. Base case rating and Contingency rating and percent of flow rating are taken from
the rating set specified prior to contingency analysis.
In the summary page, input files and options used in contingency analysis are presented. For each
network condition that satisfies conditions, post-contingency solution is reported first, then followed
by post-tripping solution and post-corrective action solution. Each solution is presented in the
format similar to non-spread sheet overload report format. For each monitored element printed, the
pre-contingency loading, one of post-contingency, post-tripping and post-corrective action loading,
the rating and the corresponding percent loading are listed. For each bus printed, voltage in one of
post-contingency, post-tripping and post-corrective action solutions, base case voltage are printed.
Violations in solutions are followed by correctives actions specified for the network condition. Cor-
rective actions are grouped into three groups: generation dispatch, load shedding and phase shift
angle adjustment. For generator dispatch, active power outputs prior to corrective action analysis
and changes in active power outputs in MW are reported. For load shedding, active power loads
prior to corrective actions and load curtailments in MW are reported. For phase shifter angle adjust-
ments, phase shifter angles prior to corrective actions and angle adjustments in degrees are
reported.
Figure 5-17 shows a partial sample of a corrective action report. In the sample, contingency ’1_5’
causes an interface flow overloading and two bus voltage violations. In post-corrective action solu-
tion, the loading of the interface is decreased to 100.2 percent of rating A and two bus voltage
violations still exist. The corrective actions involved are generation re-dispatch of five generators,
load shedding at four buses and one phase shift angle adjustment.
5-50 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
Figure 5-17. Sample Corrective Action Report
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-51
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
The Append ACCC function is initiated by selecting the Power Flow>Report>Append to AC Con-
tingency solution output file menu entry, which brings up the Append to AC Contingency Solution
Output File dialog (see Figure 5-18). This dialog is used to specify:
5-52 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
Details on the significance of the input parameters to the Append ACCC function and on the oper-
ation of the Append ACCC function are given in Section 4.114.7 of the PSS™E Program Operation
Manual.
Select Power flow >Solution>Implement Generation Dispatch to launch the Implement Gener-
ation Dispatch dialog (see Figure 5-19).
Study case: Select to impose a contingency from the contingency list specified in Contingency
Description Data File or to use working case
Dispatch Mode and Dispatch system: Specify generation dispatch mode and dispatch sub-
system. If Dispatch mode is disabled, buses that are not connected to a swing bus will be
disconnected and imbalances are absorbed by the swing bus within the island.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-53
Contingency Analysis PSS™E-31.0
Performing AC Contingency Analysis Users Manual
Distribution Factor Data File: it is a required file, that contains contingency descriptions and sub-
system specifications.
Load Throwover Data File: It is an optional file, that contains load throwover data.
Unit Inertia and Governor Data File: it is an optional file, that contains generator inertia and gov-
ernor response data.
If any line outage contingency cases form one or more swingless islands, any DC line having at
least one converter station bus in such an island is blocked for that contingency case solution. Sim-
ilarly, any FACTS device having at least one of its buses in such an island removed from service
for that contingency case solution. Any such DC line or FACTS device which is a tie branch between
a swingless island and the remaining system is alarmed.
When the SET, CHANGE, INCREASE, DECREASE or MOVE contingency records operate on
LOAD, the specified buses must have one or more in-service connected loads. For the MOVE
event, in-service connected load must exist at both the FROM and TO buses. When these events
employ the PERCENT keyword, the connected bus load MVA magnitudes are adjusted. The reac-
tive power to active power ratio remains constant, and the relative proportions of constant MVA,
constant current and constant admittance load components remain constant. When these events
employ the MW keyword and the bus demand includes a non-zero active power component, the
bus load MVA is adjusted by the ratio of the specified MW value to the initial active power bus load
(or this ratio plus 1.0 if the specified value is incremental load). This initial active power bus load is
computed using nominal (i.e., not voltage adjusted) values for constant current and constant admit-
tance load components, and recognizing the affect of any load multiplier associated with an Optimal
Power Flow (see the PSS™E OPF Manual) adjustable bus load table. When these events employ
the MW keyword and the initial bus active power load is zero, the specified MW value is assigned
to the bus as a constant MVA component active power load and the reactive power bus load is
unaltered.
When the SET, CHANGE, INCREASE, DECREASE or MOVE contingency records operate on
SHUNT and employ the PERCENT keyword, the bus SHUNT MVA magnitude is adjusted. When
these events employ the MW keyword and the initial active power component of shunt admittance
is non-zero, the bus shunt MVA is adjusted by the ratio of the specified MW value to the initial active
power component of shunt admittance (or this ratio plus 1.0 if the specified value is incremental
load). When these events employ the MW keyword and the initial active power component of shunt
admittance is zero, the specified MW value is assigned to the active power component of shunt
admittance and the reactive power component of shunt admittance is unaltered.
When the SET, CHANGE, INCREASE, DECREASE or MOVE contingency records operate on
GENERATION, the specified buses must have one or more in-service connected machines. For the
MOVE event, an in-service connected machine must exist at both the FROM and TO buses. The
value specified, whether PERCENT or MW, affects the magnitude of the bus active power genera-
tion only.
5-54 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing AC Contingency Analysis
The AC contingency calculation detects the specification of duplicate single- and double-line outage
contingencies and calculates the contingency case solution only for the first specification of such a
contingency. Any contingency cases involving bus boundary condition contingency events or more
than two-line outage contingency events are not checked for duplication.
It is required that the working case be solved to an acceptable mismatch tolerance prior to executing
the AC contingency calculation solution process.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-55
Contingency Analysis PSS™E-31.0
Performing Multiple Level AC Contingency Analysis Users Manual
Multiple level AC contingency analysis calculates full AC power flow solutions for the user specified
and automatically selected single or multiple contingencies, monitors voltage and loading condi-
tions and stores the results in a binary file. It will accept a user-specified list of contingencies to be
included in a contingency study as defined in a Contingency Description Data File (see
Section 5.2.3.1). Each of these specified contingencies may consist of a combination of generation
and transmission outages. In addition, contingencies may be selected by built-in automatic contin-
gency rankers. Two such rankers, for branch overload and voltage collapse contingencies (see
Section 5.2.4), are integrated within multiple level contingency analysis. There is full flexibility in
defining contingency subsystem; i.e., you can define in which portion of the system you will allow
5-56 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing Multiple Level AC Contingency Analysis
The multiple contingency solution function performs deterministic reliability assessment for up to
three levels, namely N-1, N-2 and N-3 criterion. User specified and automatically selected contin-
gencies are evaluated individually and in combination with each other as overlapping outages up
to the specified evaluation level. When used in conjunction with the automatic contingency ranker,
a stopping criterion (non-failure cutoff) is applied at each level. This provides the opportunity for
enormous savings in computational evaluation of contingencies. Furthermore, PSS™E has built-in
logic that identifies if a given set of outages has already been evaluated as a contingency, thus
ensuring that an automatic contingency analysis run is comprised only of unique contingencies.
Multiple level AC contingency analysis models special relay actuation schemes designed to trip or
reconnect a generator or a circuit, and shed or transfer load in response to specified low voltage,
line flow, interface flow, generator output, or line and generator service status. During contingency
analysis, switching will be automatically performed and new load flow solutions obtained whenever
trip/reconnect relaying sequences are triggered. The tripping simulation can simulate cascading
outages from contingencies.
Multiple Level Ac contingency analysis performs corrective action analysis to eliminate flow over-
loads and voltage violations caused by a contingency with the objective of minimizing control
adjustments including: re-dispatch of generations, curtailment of loads and adjustment of phase-
shifting transformers. This can help translate system related reliability measures, such as the loca-
tion and magnitude of branch overloads and bus voltage violations, to customer-impact indices in
terms of the potential amount of service interruptions, which are critical indices in probabilistic reli-
ability assessment.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-57
Contingency Analysis PSS™E-31.0
Performing Multiple Level AC Contingency Analysis Users Manual
Solution options: Select the desired solution options to be applied during load flow calculations
(see Chapter 4).
Solution Engine: Select the desired load flow solution engine to be used (see Chapter 4).
Dispatch mode: Dispatch codes for generation dispatch calculations in contingency analysis (see
Section 5.2.1.1).
Dispatch system: Select the subsystem for the generation dispatch (see Section 5.2.1.1).
Mismatch tolerance: Specify mismatch tolerance. This tolerance will be used to check for the
largest initial active or reactive power mismatch. If exceeded, the process is terminated. This value
is also used as the convergence tolerance in power flow solution (see Chapter 4).
5-58 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing Multiple Level AC Contingency Analysis
• Distribution Factor Data: This must be created using the Build facility found in the
Power Flow>Linear Network option (see following Section 5.2.3.2).
• Contingency Output: This is a required file designated by the user as the destination
for the results of the contingency calculations.
• Load throwover Data: This is an optional file that contains load throwover data (see
Section 5.2.2).
• Unit Inertia and Governor Data: This is an optional file, created by the user, that con-
tains generator inertia and governor response data (see following Section 5.6.1).
• Tripping data: if multiple level contingency analysis is initiated with tripping simulation,
this file is required, created by the user, that contains tripping data (see following
Section 5.3.7.2). The tripping Data File is specified in tripping simulation tab.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-59
Contingency Analysis PSS™E-31.0
Performing Multiple Level AC Contingency Analysis Users Manual
Perform multiple contingency analysis: When perform multiple contingency analysis is disabled,
all other options in this dialog are disabled; when perform multiple contingency analysis is enabled,
the next-level contingencies (e.g. secondary contingencies of a primary contingency) of each non-
failure contingency (see Section 5.3.3) are to be evaluated; when perform multiple contingency
analysis is enabled with failure cutoff disabled, the next-level contingencies of each failure and non-
failure contingency will be evaluated.
Max level of contingency analysis: Select the level of multiple contingency analysis up to three.
This option enables the contingency combination selections at less or equal levels.
First level analysis: Select the contingency groups included in the primary contingency list (see
Section 5.3.4). There are three groups of contingencies to choose, namely S, U and B. S represents
user specified outages, U and B are machine outages and branch outages respectively. When the
ranked contingencies are included in the primary list, the ranking solution is performed on the base
power flow case using a linearized network model. The number of ranked contingencies of each
group included in the list is determined by the min, max, cutoff values of the ranker.
Second level analysis: Select the contingency groups included in the secondary contingency list
for each primary contingency. Nine N-2 contingency combinations are represented with a matrix.
Each row represents one type of first-level contingencies which the secondary contingency list is
generated based on existing system condition after solving. The name of contingency type is dic-
tated by the letter at the beginning of each row; three elements of a row represent the same
categories (S, U, B) in secondary contingency list. When an element is selected, the corresponding
N-2 contingency will be evaluated. If one group of contingencies is not specified in primary contin-
gency list, its secondary list is empty and the corresponding row will be disabled.
Third level analysis: Select the contingency groups included in the tertiary contingency list for
each first-level and second-level contingency. There are 27 N-3 contingency combinations for the
tertiary contingency; each combination is comprised of one of each of three contingency event
types for each level. These combinations are represented with three matrices; each of them has
nine elements. Each matrix represents one group of first-level contingency cases and is dictated by
the letter at the first column; each row of a matrix represents one type of second-level contingencies
and is indicated by the letter at the second column. Three elements of a row of a matrix represent
categories S, U and B in tertiary contingency list. The tertiary contingency list is built based on
existing system condition after solving first and second level contingencies. Similarly, tertiary con-
tingency list may exist if and only if its corresponding first and second level contingencies have been
tested. That is if one group of contingency is not included in primary list, all following lists are empty
and the corresponding matrix is disabled; if one group of contingency is not tested at level 2, the
corresponding row is disabled and the tertiary list is empty.
Ranking options: Select contingency rankers and specify the number of each group of contingen-
cies to be included in the list (for contingency ranking, see Section 5.2.4).
• Enable: Include single machine outages from branch overload ranking in the contin-
gency list.
• Min.: The minimum of single machine outages from the overload ranking to be tested
in the list.
• Max.: The maximum of single machine outages from the overload ranking to be tested
in the list.
5-60 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing Multiple Level AC Contingency Analysis
• Cutoff: The number of consecutive single machine outages from the overload ranking
that are non-failure.
Line overload: has four control parameters.
• Enable: Include single branch outage that causes overloading in the contingency list.
• Min.: The minimum of single branch outages from the overload ranking to be tested in
the list.
• Max.: The maximum of single branch outages from the overload ranking to be tested
in the list.
• Cutoff: The number of consecutive single branch outages from the overload ranking
that are non-failure.
Voltage depression: has four control parameters.
• Enable: Include single branch outage that causes voltage collapse in the contingency
list.
• Min.: The minimum of single branch outages from the voltage collapse ranking to be
tested in the list.
• Max.: The maximum of single branch outages from the voltage collapse ranking to be
tested in the list.
• Cutoff: The number of consecutive single branch outages from the voltage collapse
ranking that are non-failure.
Islanding ranking: has two control parameters.
• Enable: Include single branch Contingencies which result in the formation of an island
of one or more buses, without a swing bus, in the contingency list.
• MW threshold: The minimum of active power flow on such branches.
Contingency case rating and percent of rating: These define the loading limits to be used in cal-
culating overload performance indices. By default, contingency case rating is rating set program
option setting and percent of rating is 100 percent. They are also used to determine flow overloads
in post-contingency solutions and classify the post-contingency solutions into either failure or non-
failure groups, and if Perform corrective actions option is enabled, then corrective actions are spec-
ified to remove the flow overloads.
See Section 5.2.4 for options of Convert ratings to estimate MW ratings, Small reactance threshold,
and Allow ties from subsystem as contingency.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-61
Contingency Analysis PSS™E-31.0
Performing Multiple Level AC Contingency Analysis Users Manual
Contingency element: A major component in the network whose operation status or set-
points can be changed, e.g., one transmission circuit outage, one machine out-of-service,
one transmission circuit reclosing, a change in load or generation at a bus.
Contingency event: The contingency of one or more elements originating from a single
cause, e.g., each contingency case defined with a block structure in a contingency descrip-
tion file is considered as one contingency event.
Contingency: A contingency condition simulated by PSS™E made up of one or more con-
tingency events.
Level: The number of contingency events within a contingency studied by PSS™E. "Level"
may also be viewed as the number of independent causes studied in a contingency; e.g.,
N-1, N-2 and N-3.
Contingency events include:
• Single contingency elements, e.g., one transmission circuit outage, and
• Multiple contingency elements, e.g., a combination of circuits and, or machines
out-of-service at the same time.
Examples of the latter include outages of multiple circuits terminating at the same bus caused by
bus failures and outages of two circuits on the same right-of-way caused by ROW failure.
When multiple events are combined within a contingency, they are assumed to be occurring simul-
taneously but originating from independent causes, i.e., one event does not trigger the others.
Multiple level contingency analysis is deigned to model up to three events per contingency.
The failure cutoff is enabled by selecting ’Enable’ for multiple contingency analysis option, the next-
level contingencies of a failure contingency that results in operating limit violations will be skipped.
It is most likely that under a failure contingency condition any next-level contingencies will result in
operating limit violations too, so there is no need to apply more contingencies to failure cases.
Enabling failure cutoff can reduce the set of tested contingencies and concentrate studies on more
probable contingencies. To evaluate complete multiple event contingencies for the specified level,
the failure cutoff must be disabled by selecting ’Enable with failure cutoff disabled’ for Perform mul-
tiple contingency analysis option. After completion of a contingency analysis, only non-failure
cases could be used as base cases for next-level contingency analysis. The failure cutoff is applied
to both user specified contingencies and ranked contingencies. For example, multiple level contin-
gency analysis is initiated with level 2 and failure cutoff enabled, user specified contingencies for
N-1 and combinations SS and SB for N-2 (SS consists of two different user specified contingencies
in the user specified contingency list, and SB consists of a user specified contingency and a ranked
single branch outage), if all user specified contingencies are failure cases based on the failure cri-
teria in Table 5-3, namely all N-1 cases are failure cases, all N-2 contingencies are skipped.
5-62 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing Multiple Level AC Contingency Analysis
The non-failure cutoff is specified by cutoff numbers within each ranker. If the number of consecu-
tive non-failure contingencies from the ranker is more than the cutoff, it is assumed that the rest
contingencies from the same ranker will not lead to violations and be skipped. This section dis-
cusses internal the failure criteria to classify a contingency solution.
At the completion of a contingency evaluation, the contingency may be classified according to solu-
tion characteristics of the last power flow solution performed on the contingency. This classification
is shown in Table 5-2.
Category I contingencies are those whose power flow solutions have a maximum bus mismatch
less than the mismatch tolerance. Category I contingencies are further classified into: failures and
non-failures. A Category I contingency is classified as a failure if the contingency results in problems
listed in Table 5-3 or if specific events occur during the contingency. The classifications are applied
only to internal programs. The failure status of the contingency is used only as stopping criteria for
failure and non-failure cutoff algorithms. You can make your failure criteria more stringent in order
to obtain a reduced set of tested contingencies; however only monitored flows and voltages speci-
fied in monitored element data file of tested contingencies are saved in results files and can be post-
processed to generate the different reports. In order to test more contingencies, you have to repeat
contingency analysis with new selections of failure criteria (see Section 5.3.5). The failure status of
a contingency is not stored in result files.
Table 5-3. Types of problem that would Qualify a Category I Contingency as a Failure
Problem Description Default Criteria
OVERLOAD Circuit or interface loading above a Specified rating multiplied by a percent
specified multiplier of a specified rating factor from GUI, by default, 100 percent
(A, B or C). of rating set program option setting is
used.
HIGH VOLTAGE Bus voltage above the high voltage limit. Upper limit defined in monitored ele-
ment file.
LOW VOLTAGE Bus voltage below the low voltage limit. Lower limit defined in monitored ele-
ment file.
VOLTAGE DEVIATION Bus voltage change (absolute value) Variation defined in monitored element
between pre- and post-contingency con- file
ditions exceeds the Deviation criterion
The detected overloaded branches are different with those in post-processed report files
where the different ratings of loading may be applied.
An islanding event occurs when a contingency causes a physical separation of a bus or group of
buses from the base case network. The outage of a radial branch will automatically result in
islanding of a radial bus. If the contingency is a multiple element outage, it may cause multiple
islands. When dispatch mode and dispatch subsystem are specified, contingency analysis will pro-
cess islanding events via generation redispatch (see Section 5.2.1.2), otherwise those islands
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-63
Contingency Analysis PSS™E-31.0
Performing Multiple Level AC Contingency Analysis Users Manual
without a swing bus will be shut down. The islanding problem has been removed from the failure
criteria since PSS™E-30.3.
The types of events (as differentiated from troubles) occurring during contingency evaluation that
would qualify a contingency as a failure, include:
It is useful to think of the contingency list as further divided into contingency groups. Contingency
groups are shown in Table 5-4. The graphic equivalent of this table is shown in Figure 5-23.
In group S, the contingencies are taken directly from a dfax file which is generated with a Contin-
gency Description File (see Section 5.2.3.1). These can be viewed as must-test contingencies; i.e.,
no matter how system conditions change, it is important to the reliability assessment to consider
these contingencies. The Contingency Description File may be:
• Created by the user based on previous operating or planning experience with a system,
reliability criteria guidelines or some other arbitrary method. The file is thus one that is
created outside of PSS™E, with a text editor.
• Produced by pre-screening contingencies using activity RANK (refer to Section 5.2.4).
Groups U, B1, B2 and B3 are comprised of ranked contingencies from the contingency subsystem,
each group is based on different methods of ranking.
• Within each ranked group, there is internal ordering from most severe to least severe
contingencies.
• Contingencies are evaluated according to the sequence of groups.
5-64 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing Multiple Level AC Contingency Analysis
• If a contingency has been evaluated in an earlier group, the same contingency in a later
group will be skipped.
Each contingency evaluation constitutes a Power Flow solution resulting in a post-contingency
system state. Conditions in the post-contingency state are then checked against the specified
failure criteria.
Ranked contingencies are tested one by one in sequence until an unbroken series of N non-failure
contingencies. The stopping criterion (non-failure cutoff) of "N contingencies in a row" is applied
here. The evaluation of a ranked contingency group is complete when all contingencies are
exhausted or the stopping criterion is met.
Groups B1, B2 and B3 may be comprised of the same contingencies, albeit with different ranking.
Some of these contingencies may also be included in group S.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-65
Contingency Analysis PSS™E-31.0
Performing Multiple Level AC Contingency Analysis Users Manual
stopping criterion has been met, the branch outage events causing system separations (group B1)
are evaluated. A simple screening algorithm that searches for continuity can also automatically
select these events. The final two groups of events in the list are the ranked branch outages from
overload (group B2) and voltage collapse ranking (group B3). These are tested in a similar fashion
as the ranked machine outages, in which the individual branch outages are tested one by one and
the list is truncated after the corresponding stopping criterion is met. Groups B1, B2 and B3 may be
comprised of the same contingencies, albeit with different ranking. Some of these contingencies
may also be included in group S.
The multiple contingency solution procedure is given by the example of a two-level contingency
analysis. If a two-level contingency analysis is to be performed, a newly ordered event list is built
after solving each first-level contingency Power Flow. These secondary ordered event lists may
contain the same categories of outage events as those in the first-level list, with the exclusion of the
initial outage event. New rankings are determined based on the system conditions existing after
each first-level contingency using a linearized network model. This approach is called Wind Chime
approach.
Figure 5-24 illustrates the Wind Chime approach for a two-level contingency run using a contin-
gency level of 2; some other options specified for this run are ’Enabled with failure cutoff disabled’
for Perform multiple contingency analysis option, B for the first level and BB for the second level
analysis, as well as only single branch outages from overload ranking with non-failure cutoff of 2.
5-66 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing Multiple Level AC Contingency Analysis
In Figure 5-24, the initial first-level contingency is a non-failure. That is, it does not have any criteria
violations in Table 5-3 and trigger any failure events. A number of second-level contingencies are
then run until two consecutive second-level contingencies are non-failures. The next first-level con-
tingency is evaluated and is classified as a failure case; because failure cutoff is disabled, it is
followed by second-level contingencies until two consecutive second-level contingencies are non-
failures. This procedure continues until the top two second-level contingencies are non-failures for
two consecutive first level contingencies.
This process can be duplicated for any level of automatic contingency analysis. If third-level contin-
gencies are requested, a ranking is done for each second-level contingency and the tertiary
contingencies are run until the maximum is reached or the cutoff criterion is satisfied.
The contingency evaluation functions contain logic to efficiently check whether a contingency con-
sisting of a combination of branchess and machines has already been tested. In this way, any
particular branch or machine outage combination, whether it originates from one multiple element
event or from two or more single element events, will be tested only once. Also, elements that are
ranked higher in the primary event list than the present primary contingency will not be included in
the present and subsequent secondary ranking lists. This assumes that all two level events asso-
ciated with those primary events would have been evaluated, either explicitly by power flow
solutions or implicitly by ranking list truncation. The ranking algorithm also takes into account the
outages of identical machines located at the same bus. Since the impact of these outages on the
system will be identical, it is necessary to test only one of such machine outages per contingency
level.
The program can still test multiple levels of machines of the same size.
Number of trip events per load flow: After a contingency power flow solution, tripping conditions
that trigger tripping sequences are checked in the order in which tripping events are specified in
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-67
Contingency Analysis PSS™E-31.0
Performing Multiple Level AC Contingency Analysis Users Manual
Tripping Element Data File (Section 5.3.7.2). There may be more than one instance of tripping
sequences that are activated. The number of trip events that are activated prior to the next power
flow solution is set by number of trip events per load flow.
Number of load flows per contingency: When a new power flow solution is performed following
activation of one or more tripping sequences, the trip triggers are reset and all the remaining trip
sequences are checked for the new power flow solution. If one or more remaining tipping
sequences satisfy conditions, a new power flow is performed with activation of these tripping
sequences up to Number of trip events per load flow. This process continues till the number of load
flows following a contingency power flow reaches the number of load flows per contingency.
5-68 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing Multiple Level AC Contingency Analysis
Tripping Label
(monitor element)...
(trip element)
End
where the first "r" value is the lower bound of the per unit voltage band and the optional second "r"
value is the upper bound. If the upper bound is omitted, the upper end of the band is not checked.
Token TR is key word for trip rating.
To specify one winding of a three-winding transformer for monitoring, the bus to which the winding
is connected must be the first bus specified in the following data record:
[MONITOR]|BRANCH| FROM BUS bsid TO BUS bsid TO BUS bsid [|CIRCUIT |] ckid TR r|MW |
|LINE | |CKT | |MVA |
|MVAR |
|AMPS |
|PERCENT| OF |A|
|B|
|C|
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-69
Contingency Analysis PSS™E-31.0
Performing Multiple Level AC Contingency Analysis Users Manual
When flow monitoring records employ keyword ’PERCENT’, one of rating sets ’A/B/C’ must be
specified. Percent loadings of monitored elements based on ratings are specified as either Current
or MVA percent loadings by percent units program settings (see Section 1.6.4).
where r is trip rating for the monitored interface, if the sum of MW/MVA/ MVAR/AMPS flows at the
’From bus’ end of specified branches is greater than r, trip actions occur. A rating of zero will disable
the monitored interface flow condition. The branch specification record may specify individual two-
winding or non-transformer branches or individual three-winding transformers.
For specifying a two-winding or non-transformer branch the following data specification record is
used:
For specifying a three-winding transformer the following data specification record is used:
|BRANCH| FROM BUS bsid TO BUS bsid TO BUS bsid |CIRCUIT| ckid
|LINE | |CKT |
5-70 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing Multiple Level AC Contingency Analysis
|DISCONNECT||BRANCH| FROM BUS bsid TO BUS bsid TO BUS bsid [|CIRCUIT| ] ckid
|OPEN ||LINE | |CKT |
|TRIP |
An out-of-service three-winding transformer may be placed in-service with a record of the form:
CLOSE |BRANCH| FROM BUS bsid TO BUS bsid TO BUS bsid [|CIRCUIT| ] ckid
|LINE | |CKT |
The next four record types allow the user to specify contingency events in which the load and gen-
eration boundary conditions may be changed at a selected bus. When changing generation, the bus
must have in-service generation connected to it and it may not be a swing bus.
The first data record of this type uses the following data record to set the load or generation at a
bus either to a designated value or to a specified percentage of its initial value:
The number "r" specified must not be a negative number when the PERCENT keyword is used.
The second data record of this type uses the following data record to change the load or generation
at a bus either by a designated amount or by a specified percentage of its initial value:
The third and fourth data records of this type are similar to the CHANGE record, except the direction
of the change is defined by the first keyword, and "r" must be a positive number:
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-71
Contingency Analysis PSS™E-31.0
Performing Multiple Level AC Contingency Analysis Users Manual
To transfer load or generation from one bus to another, the following data record is used:
An in-service machine may be removed from service using the following data record:
Similarly, an out-of-service machine may be placed in-service with a record of the form:
In each tripping event, a single branch within a given subsystem is monitored. For non-transformer
branches and two-winding transformers, a branch is tripped when flow at either one of its two bus
ends exceeds the tripping rating. For three-winding transformers, a three-winding transformer is
outaged when the flow at any one of its three winding buses exceeds the tripping rating.
5-72 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing Multiple Level AC Contingency Analysis
Number of AC load flows: Select the desired number of iterations between execution of the linear
programming engine to identify corrective actions and subsequent AC load flow solution to verify
the feasibility of those actions. The specified number of iterations can be between 1 and 10. Note
that, even if a feasible solution appears to have been found, i.e., the identified corrective actions
appear to have been successful, the iteration between linear programming computation and AC
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-73
Contingency Analysis PSS™E-31.0
Performing Multiple Level AC Contingency Analysis Users Manual
power flow solution may continue in an attempt to further optimize the solution if not exceeding the
iteration limit.
Branch overload violation tolerance: The percent of flow rating used in linear programming
engine can be adjusted by specifying a branch overload violation tolerance. e.g., if branch overload
violation tolerance is specified as 0.1% and percent of flow rating is 100%, percent of rating of
100.1% is used in determination of overload violations in linear programming algorithm.
Bus voltage violation tolerance: The limits of bus voltages used in linear programming engine
can be adjusted by specifying bus voltage violation tolerance. The voltage violation tolerance is
applied to both upper and lower voltage limits, if applicable. e.g., if bus voltage violation tolerance
is specified as 0.1%, lower and upper limits of bus voltages are 0.95 and 1.05 in pu respectively.
The adjusted voltage limits are 0.949 and 1.051 respectively.
Control options: Select types of control adjustments and specify weighting factors for each type.
Enable generator controls: Real power generation dispatch controls can be included by checking
this box. The adjustable range is from PT to PB of each participating machine. Generator active
power limits are taken from a Generator Inertia and Governor Response Data File (see
Section 5.6.1) if the file is specified, otherwise the values in base case are used. In corrective action
analysis, generator active power limits are adjusted by the following rules. If PT had been defaulted,
the larger value of PG (its existing MW output) and machine power base (MVA base) will be used
as PT; If PT of a machine is less than its PG, the PT is set equal to the PG. If PB of a machine had
been defaulted, it is set equal to 0; if PB of a machine is less than its PG, the PB is set equal to the
PG. A machine will be excluded from the controls if its PT is equal to its PB.
Generator weighting factors: Weighting factors of generation dispatch adjustments are used to
adjust cost factors in the objective function. The internal cost factors for real power generation dis-
patch control specified in the programs are shown in Table 5-5; the actual cost factors are equal to
internal factors multiplied by the user defined generator weighting factors. e.g., if weighting factor
of generation dispatch control is set as 1.0, the cost for generation dispatch of 100 MW will be 1.0.
Generator control subsystem: Select the subsystem in which all in-service generators with valid
range of adjustments will participate in corrective action analysis.
Enable load controls: Load shedding controls can be included by checking this box. The loads
with negative MW values will be excluded from the controls. While performing load curtailment, the
algorithm maintains a constant power factor at the buses where load curtailment occurs.
Load weighting factors: Weighting factors of load curtailments are used to adjust cost factors in
the objective function. The internal cost factors for load curtailments defined in the programs are
shown in Table 5-5; the actual cost factors are equal to internal factors multiplied by the user-
defined weighting factors. e.g., if weighting factor of load curtailments is set as 1.0, the cost for load
shedding of 100 MW will be 100.0.
Load control subsystem: Select the subsystem in which all in-service loads will participate in cor-
rective action analysis. Loads with negative real power will not be included as candidates for load
curtailments.
Enable phase shifter controls: Phase shifter controls can be included by checking this box. To be
adjustable as a phase shifter, transformers must be operated under MW control mode. The adjust-
able range of a participating phase shifter is from Rmax to Rmin.
5-74 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Performing Multiple Level AC Contingency Analysis
Phase shifter weighting factors: Weighting factors of phase shifter angle adjustments to be used
to adjust cost factors in the objective function. The internal cost factors for phase shifter angle
adjustments defined in the programs are shown in Table 5-5; the actual cost factors are equal to
internal factors multiplied by the user-defined weighting factors. e.g., if weighting factor of phase
shifter angle adjustment is 1.0, the cost of phase shifter angle adjust em nt of 100 degrees is 3.5.
Phase shifter subsystem: Select the subsystem in which all in-service phase shifters will partici-
pate in corrective actions.
When options of perform multiple contingency analysis, perform tripping simulation and perform
corrective actions are disabled, the user will perform single AC contingency analysis (see
Section 5.2) by pressing Solve button after options together with required filenames in the tab for
power flow control have been specified. Only user specified contingencies defined in contingency
description file are tested.
When perform multiple contingency analysis option is disable while perform tripping simulation
enabled, after options with required filenames in tabs for power flow control and tripping simulation
have been specified, AC contingency analysis will be performed to all user specified contingencies
with tripping simulations. All converged post-contingency states will be checked against the tripping
conditions. If tripping actions are activated, the post-tripping condition at the last stage of tripping
simulation will be saved in the output file.
When perform multiple contingency analysis is enabled while perform tripping simulation disabled,
multiple level contingency analysis is performed using wind chime algorithm after options together
with filenames in tabs for power flow control and multiple contingency analysis have been specified.
When both perform multiple contingency analysis and perform tripping simulation are enabled, mul-
tiple level contingency analysis with tripping simulation is performed after options together with
filenames in all three tabs have been specified. Each post-contingency condition will be checked
against the tripping conditions. If tripping actions are activated, post-tripping condition at the last
stage of tripping simulation will be saved in the output file. Tripping events activated following a con-
tingency will qualify the case as failure, so that its next-level contingencies are skipped if failure
cutoff is enabled.
Corrective action analysis can be enabled or disabled for any above running mode.
The contingency label and contingency events of each contingency case are logged at the progress
output device as the solution process encounters it. A message identifies any network conditions
that fail to converge or which are skipped. The duplicate contingencies at secondary and tertiary
levels will not be presented in the progress windows.
The AC contingency solution process responds to the following interrupt control codes:
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-75
Contingency Analysis PSS™E-31.0
AC Corrective Action Analysis Users Manual
NM – Suppress any automatic adjustment monitors (only used with CM interrupt control
code).
DC – Tabulate conditions for each DC line after each iteration.
FD – Tabulate conditions for each FACTS device after each iteration.
Post-tripping solutions at the last stage of tripping simulation for each contingency that triggers trip-
ping events are saved into output files in the same format as contingency cases. The label of a post-
tripping solution is generated by the programs, and is comprised of the first ten letters of the label
of the contingency activating tripping actions and ended with a "/T" which identifies the case as a
post-tripping case. Normally contingency legends for a tripping solution will include tripping labels,
description of the monitored element which trigger the tripping activities and description of tripping
activities, due to limited space to save the legends, when the number of tripping activities and mon-
itored elements in a tripping solution is more than 16, only tripping labels are saved as contingency
legends.
The post-corrective action solution and activated corrective actions are stored into output files if
Perform corrective action analysis is enabled.
The maximum number of contingencies that can be tested in a multiple level contingency analysis
is 100,000.
5-76 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual AC Corrective Action Analysis
Recognizing that thermal ratings and voltage limits in a power system may sometimes be treated
as soft limits, the algorithm relaxes the hard limits on the constraints in case of infeasibility, and
returns a solution with some minor violations. Hence, incorporation of the soft limits reduces the
likelihood of infeasible solutions, which is particularly useful during contingency analysis when a
large number of corrective action solutions may need to be performed automatically.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-77
Contingency Analysis PSS™E-31.0
AC Corrective Action Analysis Users Manual
Solution options: Select the desired solution options to be applied during load flow calculations
within corrective actions (see Chapter 4).
Number of AC load flows: Select the desired number of iterations between execution of the linear
programming engine to identify corrective actions and subsequent AC load flow solution to verify
the feasibility of those actions. The specified number of iterations can be between 1 and 10. Note
that, even if a feasible solution appears to have been found, i.e., the identified corrective actions
appear to have been successful, the iteration between linear programming computation and AC
power flow solution may continue in an attempt to further optimize the solution if not exceeding the
iteration limit. The user needs to select this parameter carefully, based on experience. On the other
hand, if a solution fails at the nth iteration because the AC load flow diverges, the user may obtain
an approximate solution by specifying the number of AC load flows as n-1 and repeating the
calculations.
Mismatch tolerance: This tolerance will be used to check for the largest active or reactive power
mismatch in the power flow case prior to the start of the AC corrective actions computation. If this
tolerance is exceeded, the process is terminated. This value is also used as the convergence tol-
erance for the AC load flow solution embedded in AC corrective action analysis.
Constraint options: Select branch flow rating set, and limit tolerances for monitored elements.
Rating and percent of flow rating: Specify rating and percent of rating to be used in determination
of branch and interface flow overloads.
Branch overload violation tolerance: The percent of flow rating used in linear programming
engine can be adjusted by specifying a branch overload violation tolerance. e.g., if branch overload
violation tolerance is specified as 0.1% and percent of flow rating is 100%, percent of rating of
100.1% is used in determination of overload violations in linear programming algorithm.
Bus voltage violation tolerance: The limits of bus voltages used in linear programming engine
can be adjusted by specifying bus voltage violation tolerance. The voltage violation tolerance is
applied to both upper and lower voltage limits, if applicable. e.g., if bus voltage violation tolerance
is specified as 0.1%, lower and upper limits of bus voltages are 0.95 and 1.05 in pu respectively.
The adjusted voltage limits are 0.949 and 1.051 respectively.
Control options: Select types of control adjustments and specify weighting factors for each type.
Enable generator controls: Real power generation dispatch controls can be included by checking
this box. The adjustable range is from PT to PB of each participating machine. Generator active
power limits are taken from a Generator Inertia and Governor Response Data File (see
Section 5.6.1) if the file is specified, otherwise the values in base case are used. In corrective action
analysis, generator active power limits are adjusted by the following rules. If PT had been defaulted,
the larger value of PG (its existing MW output) and machine power base (MVA base) will be used
as PT; If PT of a machine is less than its PG, the PT is set equal to the PG. If PB of a machine had
been defaulted, it is set equal to 0; if PB of a machine is less than its PG, the PB is set equal to the
PG. A machine will be excluded from the controls if its PT is equal to its PB.
Generator weighting factors: Weighting factors of generation dispatch adjustments are used to
adjust cost factors in the objective function. The internal cost factors for real power generation dis-
patch control defined in the programs are shown in Table 5-5; the actual cost factors are equal to
5-78 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual AC Corrective Action Analysis
internal factors multiplied by the user defined generator weighting factors. e.g., if weighting factor
of generation dispatch control is set as 1.0, the cost for generation dispatch of 100 MW will be 1.0.
Generator control subsystem: Select the subsystem in which all in-service generators with valid
range of adjustments will participate in corrective action analysis.
Enable load controls: Load shedding controls can be included by checking this box. The loads
with negative MW values will be excluded from the controls. While performing load curtailment, the
algorithm maintains a constant power factor at the buses where load curtailment occurs.
Load weighting factors: Weighting factors of load curtailments are used to adjust cost factors in
the objective function. The internal cost factors for load curtailments defined in the programs are
shown in Table 5-5; the actual cost factors are equal to internal factors multiplied by the user-
defined weighting factors. e.g., if weighting factor of load curtailments is set as 1.0, the cost for load
shedding of 100 MW will be 100.0.
Load control subsystem: Select the subsystem in which all in-service loads will participate in cor-
rective action analysis. Loads with negative real power will not be included as candidates for load
curtailments.
Enable phase shifter controls: Phase shifter controls can be included by checking this box. To be
adjustable as a phase shifter, transformers must be operated under MW control mode. The adjust-
able range of a participating phase shifter is from Rmax to Rmin.
Phase shifter weighting factors: Weighting factors of phase shifter angle adjustments to be used
to adjust cost factors in the objective function. The internal cost factors for phase shifter angle
adjustments defined in the programs are shown in Table 5-5; the actual cost factors are equal to
internal factors multiplied by the user-defined weighting factors. e.g., if weighting factor of phase
shifter angle adjustment is 1.0, the cost of phase shifter angle adjust em nt of 100 degrees is 3.5.
Phase shifter subsystem: Select the subsystem in which all in-service phase shifters will partici-
pate in corrective actions.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-79
Contingency Analysis PSS™E-31.0
AC Corrective Action Analysis Users Manual
Constraints are the power system operating limits that need to be observed. The corrective action
algorithm allows three types of constraints that are defined in the Distribution Factor Data File:
• Branch flows: Branch flow limits are obtained from the designated rating set, adjusted
by a specified multiplying factor. Percent loadings of monitored elements based on rat-
ings are specified as either Current or MVA percent loadings by percent units program
settings (see Section 1.6.4), and used in determination of overloading. Any branch
whose rating in the designated rating set is zero is excluded from the set of constraint;
zero impedance lines are also excluded from the set of constraints in the correction
actions solution.
• Interface MW flows: Interface flow is defined as the sum of MW flow of its members.
Each interface is specified in terms of the "from" bus, "to" bus and circuit identifier of
each of its members. Flow is computed at the "from" bus end of each circuit in the inter-
face. If an interface consists of one or more zero impedance branches, or its rating in
the designated rating set is zero, it will be excluded from constraints.
• Bus voltages: High and low voltage limits for each bus are defined in per unit. Voltage
limits can be specified on a system-wide basis, for the study area only, or for individual
areas, zones and buses. If a bus voltage is monitored by several sets of upper and
lower limits, the maximum of upper limits of all sets is selected as the upper limit and
the minimum of lower limits of all sets is selected as the lower limit for the bus voltage
respectively. Note that voltage deviation limits are not checked in corrective action cal-
culations. For a generator bus, if the generator has sufficient reactive power generation
to maintain its scheduled voltage, the generator bus is excluded from the constraint set.
Controls are the actions that can be taken to correct branch loading, bus voltage and interface flow
limit violations in a power system. There are three categories of controls modeled in the corrective
actions computation:
• Generator real power output: Generators located at buses with zero impedance lines
are excluded from the control set.
• Phase shifter angle: The desired MW flow values in the power flow database for indi-
vidual phase shifters are ignored in the corrective action analysis.
• Load shedding: Bus real power load can be curtailed as needed to correct system
problems. The reactive power load is adjusted accordingly to maintain a constant
power factor of load at the bus. Loads located at buses with zero impedance lines are
excluded from the control set.
5-80 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual AC Corrective Action Analysis
Two types of weighting functions for controls are used: V-curves for MW generation and phase
shifter angle; and a linear function for load shedding, as shown in Figure 5-28, Figure 5-29 and
Figure 5-30.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-81
Contingency Analysis PSS™E-31.0
AC Corrective Action Analysis Users Manual
Load shedding should be assigned a much higher weight than generator real power dispatch to pre-
vent unnecessary load shedding when generation rescheduling is adequate in relieving the system
problems. Moderate changes of the weights from the default values generally have little influence
on the corrective actions since the sensitivities expressing the effectiveness of individual actions
tend to dominate. A large weighting factor discourages the control from being adjusted. Therefore,
you can favor certain controls over others by specifying smaller external weights. However, please
note that extremely large or small weights may cause solution problems. For this reason, it is rec-
ommended that weights be limited to the range from 0.1 to 10.
If the limit violations in the power system cannot all be eliminated using the basic control actions, it
may be preferable sometimes to accept certain degree of limit violations instead of applying
extreme and ineffective control adjustments. This strategy can be represented by applying soft pen-
alties to the constraints.
The penalties for constraint violations are represented by multi-segment linear functions. The
internal penalties for the first two segments for branch loading and bus voltage constraints are 1000
and 10000, respectively, as shown in Figure 5-31 and Figure 5-32. These penalties cannot be
adjusted.
5-82 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual AC Corrective Action Analysis
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-83
Contingency Analysis PSS™E-31.0
AC Corrective Action Analysis Users Manual
5-84 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual AC Corrective Action Analysis
Operating limit violations caused by incorrect limit settings may have a significant impact on the
optimal solution found. Hence, suspicious limits should be verified and corrected, if necessary, or
even removed from the solution.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-85
Contingency Analysis PSS™E-31.0
DC Linearized Network Solutions Users Manual
Two methods can be used to excluded controls from the corrective actions solution. One is to set
the upper and lower limits of a control identical; another is by specifying a control subsystem that
does not include controls that are not desired in a particular application
Since the optimization engine is based on a linear power flow, the result from the linear program-
ming solution is iterated with a standard AC power flow solution until one of following conditions
occurs:
The DC power flow model is useful for rapid calculation of real power flow. It ignores reactive power
flow and changes in voltage magnitudes, and assumes that, for most circuits, Xij > > rij and the
angle between two buses is small. These assumptions result in the power flow from bus i to bus k
simplifying to
θi – θj
P ij = --------------- (5.1)
X ij
5-86 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual DC Linearized Network Solutions
where:
θi = Angle at bus i.
θj = Angle at bus j.
Xij = Reactance between bus i and bus j.
The power injected into a single bus i is just the sum of the power on all circuits into the bus or
n n
θi – θj
Pi = ∑ P ij = ∑ ---------------
X ij
(5.2)
j=1 j=1
The DC network solution provides only approximate power flow solutions. The simplified branch
flow equations on which its algorithm is based inherently result in phase angles and branch flows
that are different from the AC power flow solution, even when the starting point is a fully solved
power flow case. Further, they lead to the assumption that bus voltage magnitudes and line losses
remain constant as a branch is placed in- or out-of-service. It has the advantage, though, that it is
substantially faster than a full AC power flow solution. Thus, its proper role is that of a screening
tool to indicate which cases deserve further attention.
The "linearized" or "DC" power flow model used by the DC network solution process approximates
the nonlinear AC power flow with a simplified non iterative calculation. In this method, the matrix
equation,
P = B θ
expresses net bus power injections as linear functions of bus phase angles.
The DC network solution is launched with the Power Flow>Linear Network>DC network solution
and report (DCLF) option as seen in Figure 5-34. This selection will display the DC Network
Solution and Report dialog (Figure 5-35)
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-87
Contingency Analysis PSS™E-31.0
DC Linearized Network Solutions Users Manual
The user can select, which of the three ratings are to be used in tabulating line loading percentages
in the output report. The default will be the rating set established as the default rating set program
options, a change case involving outage of a non-transformer branch or two-winding transformer,
or a change case involving outage of a three-winding transformer.
5-88 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual DC Linearized Network Solutions
Following the solution, the user has the option of modifying the voltage vector to incorporate the
phase angle vector calculated for either the base case or change case DC power flow solution. As
shown in Figure 5-35, the choices are:
• Original voltages
• Base Case DC load flow voltages
• Change case DC load flow voltages
If Original is selected, the voltage vector remains the same as it was prior to launching the DC net-
work solution process and the following message is printed in the Output Bar:
Finally, the user can, with the Select facility in the dialog choose the buses to be included in the
output report with the usual selection by Area, Owner, Zone BasekV and Bus options.
With the selection shown in Figure 5-35, the process, when the Go button is selected, will show the
following information in the Output Bar.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-89
Contingency Analysis PSS™E-31.0
DC Linearized Network Solutions Users Manual
grouping is switched. If the specified multi section line grouping or member is initially
out-of-service, the DC network solution process does not allow it to be switched. In out-
aging a multi section line grouping, the type codes of the interior "dummy" buses are
automatically changed as required. When the multi section line reporting option is dis-
abled, neither multi section line groupings nor members thereof may be switched.
• If an out-of-service three-winding transformer is specified as the branch whose status
is to be changed, it is not allowed to be switched.
The bus information presented includes the number of the area in which the bus resides, the bus
voltage phase angles for the base case and change case DC power flow solutions, generator MW,
and load MW. The value printed as load includes the active power components of the bus shunt
and all in-service loads connected to the bus on the basis of the voltage magnitude at the bus at
the DC network solution is initiated.
The load also includes the power entering or leaving the bus through any DC lines, VSC DC lines
or FACTS devices connected to the bus. If the DC line, VSC DC line or FACTS device power arrays
are zero (e.g., if a power flow network raw data file had just been opened and no AC power flow
solution attempted), an estimate of the DC or VSC DC line and FACTS device powers is used
based upon the scheduled power or current. Otherwise, regardless of the quality of the AC solution
upon entry to the DC network solution process, the powers contained in the working case are used.
In any case, DC lines, VSC DC lines and FACTS devices are not separately reported here.
For non transformer branches and for two-winding transformers listed, the number, name, base
voltage, and area of the "to bus" is printed, along with the circuit identifier; for three-winding trans-
formers, the output line contains the string "3WNDTR" in the bus number column, the transformer
name in the bus name column, and the winding number in the base voltage column, followed by the
transformer circuit identifier. The active power flowing into the line at the "from bus" and the corre-
sponding percentage of the selected rating are printed for both the base and change case DC
solutions. The selected line rating and the difference in line flow between the base case and change
case solutions are also tabulated.
If the current execution of the DC network solution includes only a base case DC solution, the
change case columns of the report are blank. If a change case solution was calculated, a descrip-
tion of the change case is included in the banner at the top of each page of output. In addition, in
the bus output block for the "from" and "to buses" of the branch whose status was changed, the
branch output line for this branch is preceded by the character string "--->".
If the change case is a line outage which results in the creation of an island without a swing bus,
change case phase angles and line flows from within the swingless island are not tabulated; dashes
are printed in the output report where these values would normally be shown.
5-90 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual DC Linearized Network Solutions
Figure 5-36. Sample Output Listing for the DC Network Solution Including Change Case
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-91
Contingency Analysis PSS™E-31.0
DC Linearized Network Solutions Users Manual
When the multi section line reporting option is enabled, the interior "dummy" buses of multi section
line groupings are not reported. In reporting branches, the far end "to bus" (rather than the closest
"dummy" bus) of each multi section line connected to the "from bus" is shown as its "to bus". Mid-
section lines are identified with an ampersand ("&") as the first character of their line identifiers in
the branch circuit identifier column (e.g., "&1").
The active power components of any line connected shunts in the working case are treated in the
same manner that bus shunts are as far is the DC network solution is concerned. Here, they are
reported as part of the line flow rather than as load at the bus; that is, they are reported in the same
manner as for AC solutions. If the change case is a branch outage, its line shunts are removed from
the solution along with the branch. If the change case places a branch in-service, its line shunt com-
ponents are not added with the branch.
The mathematics of a standard DC analogy network solution neglects line losses. That is, in
applying such a method, generation and load exactly balance. The DC network solution employed
by PSS™E, on the other hand, approximates the effect of line losses on its DC analogy solutions
with the following approach for each branch: From the voltage vector in the working case, it calcu-
lates the losses on the branch. Then, during the network solutions, the line losses at the "sending
end" of the branch, as determined from the initial voltage vector, are injected as load.
In the output report, these loss injections are not included in the bus loads tabulated. Rather, their
effect is included in the line flows printed for each branch. Thus, instead of having equal flows with
opposite signs at the two ends of a branch, the flows as tabulated here differ by the line loss
estimate.
The same loss estimate vector is used in both the base case and change case DC analogy solu-
tions. If the change case is a branch outage, its loss estimate is not removed from the solution along
with the branch; it remains as an "invisible" load at the "sending end" bus described above. If the
change case places a branch in-service, no loss estimate is added with the branch.
If the multi section line reporting option is enabled, the losses from the members of each in-service
multi section line are equivalenced to its endpoint buses. Thus, if the change case calculation is the
outaging of a multi section line, all of its losses remain as "invisible" load.
Similarly, any loss estimate that would normally be injected at the "star point" bus of a three-winding
transformer are equivalenced to its endpoint buses, and remain as "invisible" load if the change
case calculation is the outaging of a three-winding transformer.
From the foregoing discussion, then, it is strongly recommended that when using the DC network
solution, to check branch outage cases, the network be solved to an acceptable mismatch tolerance
with a full AC solution prior to launching the DC solution. While it does not require a solved system
condition, the only time an unsolved starting point should be provided is when using the DC solution
as a "bootstrap" to obtain an estimate of phase angles for a full AC power flow solution.
5-92 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual DC Linearized Network Solutions
The DC contingency analysis process is launched by selecting the Power Flow>Linear Network>
DC contingency checking (DCCC) option. This option will open the DC Contingency Checking
dialog (see Figure 5-37). This figure shows drop-down menus for the Output code, the Line flow
code and the Contingency case rating selections.
5.5.2.1 Setting Initial Condition Mismatch for the Linear Network DC Contingency
Checking
If the largest initial active power mismatch exceeds the specified MW mismatch tolerance, the user
is given the opportunity to terminate the contingency checking process. Note that the user can
modify the tolerance in steps of 0.1.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-93
Contingency Analysis PSS™E-31.0
DC Linearized Network Solutions Users Manual
5.5.2.2 Setting Solution Options for the Linear Network DC Contingency Checking
Contingency case rating: This set and the percentage thereof, define the line loading limits used
in determining overloads. The default rating set is the one established as the default rating set pro-
gram option.
Convert ratings code: If the convert ratings code box is checked, ratings of monitored branches
are converted to estimated MW ratings based upon each monitored line’s Mvar loading at the
metered end in the base case AC solution.
Line flow code: Defines the base flow to be used in deriving contingency case flow estimates. The
user can select the AC or the DC base case conditions.
Minimum flow change: Overloaded branches in contingency cases whose contingency case flows
differ from their base case flows by less than the minimum contingency case flow change parameter
are omitted from the summary overload report.
Exclude cases: If this box is checked, those cases for which no overloads are detected are omitted
from the summary overload report.
5.5.2.4 Using the Distribution Factor Data File in Linear Network DC Solutions
In Figure 5-37, that the user must supply the name of a distribution factor data file which corre-
sponds to the current network condition and to the desired Linear Network Analysis Data Files. The
process of building a distribution factor file for AC contingency analysis was discussed in
Section 5.2.7. The building process for building a file suitable for linearized network analyses (such
as this DC contingency calculation process) is initially the same but requires the "base case" sus-
ceptance matrix to be constructed and the calculation of the line outage distribution factors
corresponding to line outage contingency events contained in the Contingency Description Data
File.
Note that, whenever a line outage contingency results in the presence of a swingless island, an
appropriate message is printed prior to calculating the corresponding distribution factor vector.
As described in Section 5.2.7, to launch the building process, use the Power Flow>Linear
Network>Build Distribution Factor data file (DFAX) option, to open the dialog. As seen in
Figure 5-38, it is necessary to check the Calculate Distribution Factors box to build the distribu-
tion factor file suitable for linear analyses as opposed to AC analysis.
5-94 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual DC Linearized Network Solutions
Figure 5-38. Build Distribution Factor Data File for Linear Analyses
Returning to Figure 5-37, the user, once having made the selections for Solutions and Output and
having identified the appropriate distribution factor file will select the OK button in the dialog.
The DC contingency checking process checks that generators are not "converted" and that each
non type four bus is connected back to a type three (swing) bus through the in-service AC network.
If any violations are detected, an appropriate message is printed and the process is terminated.
The Distribution Factor Data File is read, and, if the convert ratings option was enabled at the start
of the process, ratings from the selected rating set of those monitored branches having a nonzero
rating are modified. For each such branch, the Mvar loading is calculated and a MW rating is deter-
mined under the assumption that the Mvar loading is unchanged under contingency conditions.
Finally, the "base case" DC load flow solution is calculated followed by the processing of the des-
ignated contingency cases. If a line outage contingency forms an island with no type three (swing)
bus, a singular submatrix is formed. Such islands are omitted from the contingency checking
process.
This DC contingency checking process may be terminated by entering the AB interrupt control
code.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-95
Contingency Analysis PSS™E-31.0
DC Linearized Network Solutions Users Manual
1. The contingency case flow estimates are initialized to either the flows given by the base
case DC network solution or the base case AC flows, according to the line flow code
solution parameter selected.
2. If any bus boundary condition contingency events have been specified as part of the
contingency case, the incremental form of the DC power flow equation:
∆P = B ∆θ
is solved for the corresponding phase angle changes, and the resulting incremental line
flows are calculated and added to the contingency case flow estimate vector initialized
in (1).
3. If one (or two) line outage contingency events have been specified as part of the con-
tingency case, the corresponding vector(s) of line outage distribution factors is (are)
retrieved from the Distribution Factor Data File. The contingency case flow estimate
vector is updated to reflect the first (or only) line outage.
4. If two line outage contingency events have been specified as part of the contingency
case, the vector of distribution factors for the second outage is updated to reflect the
prior outage of the branch processed in (3). The contingency case flow estimate vector
is again updated to reflect the second line outage.
For contingency cases involving either line closure contingency event(s), three-winding transformer
outages, or more than two line outage contingency events, full DC network solutions are calculated.
If the line flow code selection is for the DC base case, contingency case flows are taken as those
from the contingency case DC network solution; if the line flow code selection was for the AC base
case, the changes in flows between the base case and contingency case DC network solutions are
added to the base case AC flows to establish the contingency case flow estimates.
In applying the first method described above (the "distribution factor method") for contingency cases
involving two line outages, if the simultaneous outages create a swingless island which neither of
the two outages individually creates, the distribution factor method is abandoned and the second
method described above, the full DC network solution, is used.
In either of the two calculation methods, whenever a line outage contingency results in the presence
of a swingless island, an appropriate message is printed prior to calculating the contingency case
flow estimates.
5-96 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual DC Linearized Network Solutions
For three-winding transformer windings, flow estimates are calculated at the winding bus end as
power flowing into the transformer. For other AC branches, flow estimates are calculated at the
metered end in the "from bus" to "to bus" direction. The flow across an interface is taken as the sum
of the flows of its members. For three-winding transformer windings, the flow is calculated at the
winding bus as power flowing into the transformer. For other members, the flow is calculated at its
metered end in the "from bus" (i.e., the first bus specified in entering the branch) to "to bus"
direction.
Single branches are listed first, either in the order in which they were specified in the Monitored
Element Data File, or in ascending numerical or alphabetical order, according to the option selected
during the building of the distribution factor file. These are followed by the interfaces in the order in
which they were specified.
If the convert ratings option was selected at the start of this DC contingency checking process, the
values printed as line ratings are the estimated MW ratings; otherwise, the ratings as contained in
the power flow case are printed. In either case, the values printed are not modified by any per-
centage of rating parameter specified at the start of this contingency checking process.
An example DC contingency check run using the savnw.sav, savnw.sub, savnw.mon and
savnw.con files will produce the Overload/ Summary Report (see Figure 5-38).
It can be seen that four contingencies result in overload conditions. The description of the contin-
gencies are listed at the left hand side of the report. Centered are shown the lines and interfaces
which are subjected to overload conditions during each listed contingency. At the right of the table
are listed, under the "Name" of the contingency condition, the:
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-97
Contingency Analysis PSS™E-31.0
DC Linearized Network Solutions Users Manual
Figure 5-39. Summary Contingency Report from the DC Contingency Checking Process
5-98 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual DC Linearized Network Solutions
An example DC contingency check run using the savnw.sav, savnw.sub, savnw.mon and
savnw.con files will produce the Loading Report partially shown in Figure 5-40.
It should be noted that the cases marked with an asterisk, are summarized on the overload report
typical of which is that shown in Figure 5-39.
Any monitored branch which resides in a swingless island, as well as any interface which includes
such a branch as a member, has dashes printed in place of its flow in the loading table.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-99
Contingency Analysis PSS™E-31.0
DC Linearized Network Solutions Users Manual
Figure 5-40. Loading Report from the DC Contingency Checking Process
5-100 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual DC Linearized Network Solutions
Modify network data with corrective action solution: select to modify generation, load and
phase shifter angle to incorporate adjustments of control components involved in corrective actions
and modify bus voltages to incorporate bus voltage phase angle vectors calculated from corrective
actions.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-101
Contingency Analysis PSS™E-31.0
DC Linearized Network Solutions Users Manual
Constraint options: Select branch flow rating set and limit tolerance for monitored branches and
interfaces.
Rating and percent of flow rating: Define branch rating set and percent of rating. The limits are
equal to the specified rating multiplied by percent of flow rating.
Convert ratings to estimated MW ratings: If the convert ratings code box is checked, ratings of
monitored branches are converted to estimated MW ratings based upon each monitored line's
MVAR loading at the metered end in the base case AC solution.
Branch overload violation tolerance: Specify branch loading limit tolerance for adjustment of
load limits to be used in linear programming engine. For example, if the tolerance is 0.1% and the
selected flow rating is 100% of Rate A, the linear programming algorithm will consider the solution
feasible if the loading of a branch has been reduced within 100.1% of the rating.
Control options: Select types of control adjustments and specify weighting factors for each type
(see Section 5.4.1.1).
5-102 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual DC Linearized Network Solutions
Operating limit violations caused by incorrect limit settings may have a significant impact on the
optimal solution found. Hence, suspicious limits should be verified and corrected, if necessary, or
even removed from the solution.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-103
Contingency Analysis PSS™E-31.0
Generator Contingency Analysis Users Manual
Two methods can be used to excluded controls from the corrective actions solution. One way is to
set the upper and lower limits of a control equal; another is to carefully define the control subsystem
to exclude those controls that are not desired in a particular application.
• Sudden loss of load, which would be redistributed in the transient period immediately
following the disturbance among generators
• Sudden loss of generation which would be redistributed among all other generators
• System break-up into islands each with its own frequency deviation.
An "Inertial" power flow represents the effects of governor action and other effects which might
stress the system. Following the loss of generation, addition of significant demand or the splitting
of a network, conditions can be such that there is a demand resource unbalance. The result is a
change in frequency and an adjustment of generator output. Generator output will be controlled ini-
tially by machine inertia and fast acting controls, such as excitation and voltage regulators. As time
extends beyond the disturbance, the generator governors will have more influence.
PSS™E provides two power flow solutions with inertia/governor re-dispatch to enable the user to
examine system conditions and to obtain a revised generator dispatch for the conditions under
which machine inertia plays the major role in modifying generator output and under which governors
play a more significant role.
The Inertial Power Flow solution gives a quick approximation to system effects in the first 0.5 sec-
onds following a disturbance, during which governor effects are minimal. Generator powers are
principally influenced by machine inertias
The Governor Response solution represents the system several seconds after an event when
governors and exciters have brought the system back to steady-state. The new generator powers
are determined by governor droop and load damping characteristics.
The inertial and governor response power flow solutions both use a Newton-Raphson iterative algo-
rithm to solve for the bus voltages needed to satisfy the bus boundary conditions contained in the
working case. The power flow case is assumed to have appropriate data changes corresponding
to some event imposed upon the solved pre-event power flow case.
Data required for the generation dispatch are specified in an Inertia and Governor Response Data
File. Island average frequencies are estimated and network parameters are made frequency
sensitive.
5-104 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Generator Contingency Analysis
5.6.1 Creating the Generator Inertia and Governor Response Data File
The input data stream consists of a series of records in the following format:
I Bus number. Bus I must reside in the working case with a generator table entry
assigned to it. No default is allowed.
ID One- or two-character machine identifier used to distinguish among multiple
machines at a plant (i.e., at a generator bus). ID = ’1’ by default.
H Machine inertia; entered in pu on MBASE base. H = 4.0 by default.
PMAX Maximum machine active power output; entered in pu on MBASE base. If
defaulted, PMAX and PMIN for this machine are set to the active power limits
contained in the power flow case for any machine for which a data file record
was successfully read but PMAX was defaulted.
PMIN Minimum machine active power output; entered in pu on MBASE base. If PMAX
is defaulted, the value specified for PMIN is set to the active power limit con-
tained in the power flow case; otherwise, PMIN = 0.0 by default.
R Governor permanent droop; entered in pu on MBASE base. R = 0.05 by default.
D Turbine damping factor; entered in pu on MBASE base. D = 0.0 by default.
Data records may be input in any machine order. Input is terminated with a record specifying an "I"
value of zero.
Any machine for which PMAX = PMIN in the Inertia and Governor Response Data File is treated as
non dispatchable. Its active power remains at its initial value from the working case when its island’s
swing bus generation change is dispatched among the in-service machines in the island.
In the inertial power flow, except for the use of "PMAX" and "PMIN" to categorize machines as either
dispatchable or non dispatchable, only "H" is used. In the governor response power flow, "R", "D",
"PMAX", and "PMIN" are used.
In this solution, generator scheduled voltages at those generator buses which are initially at a reac-
tive power limit are set to their predisturbance (i.e., initial working case) voltages. The default
response to the var limits selection is to ignore reactive power limits. By default, tap adjustment and
phase shift angle adjustment are disabled, DC converter taps are locked, and switched shunts are
active. Area interchange control and the non-divergent solution option are always disabled.
For machines for which no data record is successfully read (e.g., if no data file is specified, or if it
does not contain data records for all in-service machines), a machine inertia constant of 4.0 on
machine base (i.e., on MBASE base), is used. Clearly, the proper specification of MBASE for any
machine using default data is essential.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-105
Contingency Analysis PSS™E-31.0
Generator Contingency Analysis Users Manual
Speed deviation and frequency of each machine are estimated according to the equations:
Pt – Pe dn
------------------ = 2H ------- (5.3)
1+n dt
dn
n = 0.5 ------- (5.4)
dt
f = 1+n (5.5)
where:
In this solution, generator scheduled voltages are unchanged except as described below, and the
default response to the var limit selection is to honor generator reactive power limits. By default, tap
adjustment by the stepping method and phase shift angle adjustment are enabled, DC taps are
unlocked, and switched shunts are active. These settings may be overridden by the user when ini-
tiating the solution. Area interchange control and the non-divergent solution option are always
disabled.
A generator bus that is selected as an island swing by the solution process and that was initially at
a reactive power limit is alarmed and its scheduled voltage is set to its predisturbance (i.e., initial
power flow case) voltage.
Speed deviation and frequency of each machine are estimated according to the equations:
Pt – Pe
n = --------------------------- (5.6)
D + (1 ⁄ R)
f = 1+n (5.7)
where D and R are as defined in Section 5.6.1, and Pt, Pe, n, and f are as defined in Section 5.6.2.
5-106 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Generator Contingency Analysis
If, during the solution, the total generation requirement in an island drives all generators in the island
to their high or low power output limits, an appropriate message is printed and the solution process
is terminated.
In the dialog shown in Figure 5-43, the user’s minimum requirements are to supply the Unit Inertia
and governor data file and to select the Inertial Solution type. Note that the figure shows default
values for Solution options, Tap adjustments and Var limits. Remember that Area interchange con-
trol and the non-divergent solution option are always disabled in this solution.
In reading the input file, gross data errors (e.g., H = 0.0) are alarmed and the corresponding record
is ignored. Data inconsistencies (e.g., PMAX less than initial machine power) are alarmed, "fixed",
and used.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-107
Contingency Analysis PSS™E-31.0
Generator Contingency Analysis Users Manual
The power flow process, when initiated, checks each island for a swing bus. One (and only one)
swing bus must be specified in each island, and, if no swing bus exists in an island, the program
assigns the self-regulating generator bus with the largest inertial or governor response, as appro-
priate, as the island swing. The process will alarm and terminate if:
The solution parameters designating the maximum number of iterations, acceleration, convergence
tolerance, and maximum voltage magnitude change are shared with fully coupled Newton-Raphson
solution and the blowup threshold and constant power voltage breakpoint are shared among all
power flow solutions. The user may modify any of these solution parameters.
The inertial power flow solution objective is to provide for the redispatch of generator powers to
allow proper load sharing in a power unbalance condition. This occurs whenever the largest angle
change in radians during an iteration is less than the automatic adjustment threshold tolerance,
ADJTHR, and any island swing bus power has changed by more than the convergence tolerance
since the last dispatch. The largest swing bus power change is tabulated prior to each dispatch
calculation.
Island average frequency estimates are updated during the dispatch calculation; they are set to the
average of the dispatchable machine frequencies. All bus and line shunts, admittance loads, line
charging capacitances and line impedances are modified to reflect their dependency on frequency.
Prior to terminating, the solution process tabulates the frequency estimate and swing bus of each
island.
5-108 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Generator Contingency Analysis
The test will be to trip the machine at bus 101 in the power flow. That unit is generating 750 MW.
The inertial data file to be used assumes the following information contained in Table 5-6.
I ID H PMAX PMIN R D
101 1 4 0.9 0 0.05 0
102 1 4 0.9 0 0.05 0
206 1 4 0.9 0 0.05 0
211 1 5 0.85 0 0.05 0
3011 1 4 0.9 0 0.05 0
3018 1 4 0.9 0 0.05 0
Running the Inertial and Governor power flow solutions will result in a summary of network condi-
tions and a convergence monitor in the Output Bar (see Figure 5-44).
Inertial Response
Governor Response
Figure 5-44. Progress Reports for Inertial and Governor Power Flow
Solutions
It can be seen in Figure 5-44 that the frequency in the inertial response, shortly after the disturbance
has fallen to 59.287 Hz while following governor action it has recovered to 59.478 Hz. Further, fol-
lowing governor action the swing bus has an increased power generation at 809 MW.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-109
Contingency Analysis PSS™E-31.0
Generator Contingency Analysis Users Manual
To further examine the solution it is useful to look at the redispatches. In Figure 5-45 the dispatches
are shown for the Base case, the situation subject to inertial redispatch and the situation subject to
governor action.
Inertial redispatch is not controlled by governor action. The amount of power from each unit is a
function of its inertia and it can be seen that some units are outputting power above PMAX. This will
slow down the units. Following governor action, machine powers have been reduced to levels at or
within their maximum capabilities.
Base Case
Inertial
Governor
Figure 5-45. Initial Dispatch Compared to Inertial and Governor Power Flow
Redispatch Levels
All frequency-sensitive data items are modified in the power flow case at the completion of this
redispatch process. Therefore, standard power flow reporting activities such as the Bus based,
Area based and Subsystem based implicitly calculate results at off-nominal frequencies, even
though island frequencies are not preserved. As a result of this, and the possible modification of
generator scheduled voltages described above, it is strongly recommended that care be taken in
saving the new power flow condition. In particular, the user should not overwrite the Saved Case
File containing the pre-event network solution, or any milestone Saved Case File preserved prior to
running the inertial or governor response power flow solutions.
5-110 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Calculating Distribution Factors
These power flow solutions might require more iterations than the Newton-Raphson solutions
activity, particularly when the system, or an island thereof, is under severe stress. The iteration limit
ITMXN may be increased via the solution parameters data editor window.
Should the inertial or governor response power flow solutions fail to converge in an islanding situ-
ation, inspection of solution results may indicate that all islands except one are "solved." Such a
solution may be adequate for the application at hand. Note that in an islanding case, those islands
that are not of particular interest may be disconnected. This should be done after implementing the
data changes required to model the event being studied, and before running the power flow
solutions.
Just as in a conventional power flow solution, selection of a swing bus for each island can have an
effect on the solution convergence properties for that island. Proper selection of island swing buses
requires a "feel" for the system. The user may find it helpful to make several attempts at solution for
a particularly troublesome island, each with a different island swing bus.
It is good practice to save the working case in a Saved Case File before running either the inertial
or governor response power flow solution. This is useful for the situation in which either of them fails
to converge. The Saved Case may be restored, changes made (e.g., different load characteristics,
different island swing buses, or other techniques described above) and a new solution attempted
without having to re-specify the data changes required to model the event under study.
Note again that the data items described earlier in Section 5.6.1 are specified on machine base.
Because the linearized network model is the basis of the calculation of distribution factors, it is nec-
essary to recognize that their use provides approximate results useful for estimating conditions
during contingencies.
Each distribution factor is a sensitivity coefficient describing the effect of the corresponding contin-
gency on the set of monitored elements. A distribution factor is defined as the ratio of the change
in flow on the monitored element in the pre-contingency and post-contingency DC power flow solu-
tions to the DC power change on the element involved in the contingency:
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-111
Contingency Analysis PSS™E-31.0
Calculating Distribution Factors Users Manual
Figure 5-46 is an example that shows the outage of a line carrying 100 MW in the base case. If the
distribution factor for that specific outage is denoted as "FIJ" for the line from Bus I to Bus L and its
value is equal to 0.05, then the line from Bus I to Bus L will have an increased loading equal to the
100 MW lost from the outaged line multiplied by "FIJ", that is 5 MW.
For bus boundary condition contingencies, the distribution factors are expressed relative to a
change in power withdrawn at the bus. Thus, they are identical for increases in generation,
decreases in generation, increases in load and decreases in load. A load increase and a generation
decrease both have a positive "∆P", while a load decrease and a generation increase both have a
negative "∆P" in deriving post-contingency monitored line flows with the above formula.
5-112 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Calculating Distribution Factors
The program will check that generators are not "converted" and that each non type four bus is con-
nected back to a type three (swing) bus through the in-service AC network. If any violations are
detected, an appropriate message is printed and the process terminated. Next the largest active
power mismatch corresponding to the present AC solution voltage vector in the working case is cal-
culated and printed.
The Distribution Factor Data File is read, and the "base case" DC load flow solution is calculated
followed by the processing of the designated contingency cases. Only single event contingencies
are allowed. Changing the status of a three-winding transformer is considered a multiple event con-
tingency; disconnecting a bus is often a multiple event contingency. Any multiple event
contingencies are alarmed and ignored.
The calculation and printing process may be terminated by entering the AB interrupt control code.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-113
Contingency Analysis PSS™E-31.0
Calculating Distribution Factors Users Manual
The summary page is followed by the distribution factor table. For each monitored element, this
table lists its active power loading in the base case AC network solution; its loading in the base case
DC analogy network solution, along with the distribution factor for each of the contingency cases
reported.
Single branches are listed first, either in the order in which they were specified in the Monitored Ele-
ment Data File or in ascending numerical or alphabetical order, according to the option selected
during the building of the distribution factor file. These are followed by the interfaces in the order in
which they were specified.
If a line outage contingency forms an island with no type three (swing) bus, a singular submatrix is
formed. Any monitored branch which resides in the swingless island has dashes printed in place of
its distribution factor. Similarly, any interface which includes such a member has its distribution
factor printed as dashes.
Because the distribution factor output process uses the same linearized network model as is used
in the DC analogy network solution method for the DC load flow, only approximate power flow solu-
tions are obtained. The simplified branch flow equations inherently result in phase angles and
branch flows that are different from the AC power flow solution, even when the starting point is a
fully solved power flow case. Further, they lead to the assumption that bus voltage magnitudes and
line losses remain constant as a branch is placed in- or out-of-service. It has the advantage, though,
that it is substantially faster than a full AC power flow solution. Thus, its proper role is that of a
screening tool to indicate which cases deserve further attention.
The process described here will detect the specification of duplicate single line outage contingen-
cies and prints the distribution factor vector only for the first specification of such a contingency. Any
contingency cases involving bus boundary contingency events or line closure contingency events
are not checked for duplication.
In using distribution factors, the flow directions of "Pbase" and "∆P" used in the above equation must
be consistent with those assumed when the distribution factors were calculated.
A line outage distribution factor reflects the outage of the series reactance element only and not the
removal of the branch’s loss estimate and line shunt components. Further, neither line outage nor
line closure distribution factors for a multi section line reflect the removal of any generation or load
that may be present at its dummy buses.
A partial report is shown in Section 5-48 which is curtailed to show only three of the first six contin-
gencies. Note that the reports shows the data files uses and lists each single contingency
considered prior to listing the distribution factors for each of the lines and interfaces monitored, for
5-114 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Calculating Distribution Factors
each contingency. The files used are the savnw.con/mon/sub files from the PSS™E EXAMPLE
directory.
As an example, it can be seen the if the nuclear plant at bus 101 is tripped, the SHIFT will be 750
MW, (the units output), and the line from Bus 201 to 151 will experience a power flow reduction of
310 MW (which is equal to 750 MW x 0.41339). The base case flow is shown as negative value of
564.8 MW at the Bus 201 end. This is the receiving end of the line. Consequently, the 750 MW shift
coupled with a positive distribution factor will result in a reduce flow towards Bus 201. An AC solu-
tion shows the flow reduces to 255.9 MW. The calculation (-564.8 + 310) gives -254.8 MW (error
less than 0.43%).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-115
Contingency Analysis PSS™E-31.0
Calculating Distribution Factors Users Manual
Figure 5-48. Example Report Listing Distribution Factors
5-116 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Perform Probabilistic Reliability Assessment
The results are referred to as "probabilistic indices". They are composite probabilities of problems
given in terms of frequency and duration indices, and determined by probabilities of transitions from
'success' operating conditions to 'failure' operating conditions. Generally, outage statistics are given
in terms of frequencies and duration to reflect the probability that a transmission element will be
forced out-of-service, and to calculate transition probabilities.
Perform contingency
analysis
Outage statistic data *.acc
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-117
Contingency Analysis PSS™E-31.0
Perform Probabilistic Reliability Assessment Users Manual
5-118 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Perform Probabilistic Reliability Assessment
When no probabilistic data is available or the studies are limited in deterministic reliability area, the
users can produce the first six reports for deterministic reliability analysis, and each contingency will
have identical statistic data.
Output mode: Probabilistic reliability analysis can be performed in one of three modes, they are
post-contingency, post-tripping and post-corrective action, subject to the corresponding running
mode is specified during contingency analysis.
Subsystem: Define the study subsystem where the probability indices are calculated. There is a
'Entire system' subsystem set by the programs, when selected, analysis is performed within entire
system. Probabilistic Indices can also be obtained for a specific subsystem predefined in Sub-
system Description Data File (see Section 5.2.2.3). When a subsystem is designated, only
monitored elements in the subsystem are checked against failure criteria to determine whether a
contingency solution has problems. For bus voltages being checked, buses must belong to the sub-
system; for line flows being checked, both of ends of a line must be in the subsystem.
Include interfaces: Interfaces do not belong to any subsystems. if the box of including interfaces
is checked, then the impacts of interfaces on probability indices of the specified subsystem will be
accumulated.
Include ties: Check the box to include the impacts of tie lines on probability indices of the specified
subsystem.
Probability and frequency cutoffs: A contingency may be of low probability or frequency that the
risk to the system is low, and evaluation is superfluous. Probability and frequency cutoffs are used
to exclude contingencies from probabilistic reliability analysis whose probability and frequency are
less than these threshold values.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-119
Contingency Analysis PSS™E-31.0
Perform Probabilistic Reliability Assessment Users Manual
Distribution Factor Data File: It is a required file, and is the one used when performing contin-
gency analysis (see Section 5.2.3.2).
Contingency Solution Output File: it is a required file, and is created with the current base case
and above Distribution Factor Data File. It is recommended that the file been generated by multiple
level contingency analysis function (see Section 5.3), When the file is generated by plain ACCC,
analysis is limited to deterministic reliability assessment.
Outage Statistic Data File: It contains outage statistics of user specified contingencies and indi-
vidual components (see Section 5.8.1.3), it is required when performing probabilistic reliability
assessment.
Output Outage Statistic Data File: It is required when output statistic data file option is selected.
The file is used to convert generic statistics to specific statistics for individual components, then the
resulting file can be edited and modified for future use. It has the same format as Outage Statistic
Data File.
Example 1: There is no need to specify outage statistics of contingencies created by global com-
mand 'DOUBLE', each double branch contingency is treated as a multiple independent outage and
its outage statistics are calculated from frequency and duration of two branches within it.
Example 2: Contingency A has branch B outage. Statistics for contingency A can be specified in
the Outage Statistic Data File or in the Contingency Description Data File. Otherwise its statistics
are equal to the statistics for the outage of branch B. If no invalid outage statistic data record is read
for branch B in Outage Statistic Data File, outage statistics of contingency A are zero.
Example 3: Contingency A has branches B and C outages. Statistics for contingency A can be
specified in the Outage Statistic Data File or in the Contingency Description Data File. If no statistics
are specified for contingency A, its statistics are equal to frequency and duration of the multiple
independent outaging of branches A and B. If no invalid outage statistic data records are read for
either branch B or C, outage statistics of contingency A are zero.
5-120 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Perform Probabilistic Reliability Assessment
Example 4: Contingency A has branch B and FACTs device C outages. Statistics for contingency
A can be specified in the Outage Statistic Data File or in the Contingency Description Data File. If
no statistics are specified for contingency A, its statistics are zeros.
There are two types of data records in the Outage Statistic Data File: one is generic outage statistic
data and the other is specific outage data. The following data record defines a set of non-trans-
former branches that have the same outage statistics:
Where: "xm" is branch reactance (ohm/mile), "bm" is branch charging susceptance (mh./mile), "ft"
is outage frequency for terminal caused single circuit outages (occurrences/year), "dt" is repair time
for terminal caused single circuit outages (hours), "fmt" is outage frequency for single circuit out-
ages (occurrences/year-mile), and "dmt" is outage durations for single circuit outages (hours). In
using "system" or "subsystem" keywords, the "label" must correspond to a subsystem label speci-
fied in a previously accessed Subsystem Description Data File. In using "in" keyword, both bus ends
of a non-transformer branch must belong to a specified subsystem to be included. In using "From"
keyword, either end of a non-transformer branch belongs to a specified subsystem to be included.
The frequency and duration of a single line outage is calculated as:
F=len*fmt+ft
D=(mft*dmt*len+ft*dt)/F
Where len is the length of the branch. When length of the branch is not specified in working case,
it is estimated by its reactance X: len=X/xm. For example, if the branch from bus i to bus j is 10 miles
and statistics of the branch are ft=0.01, dt=10, fmt=0.02, dmt=20, then F and D of this single branch
outage is:
F=(10*0.02+0.01)=0.21 (Occurrences/year)
D=(0.02*20*10+10*0.01)/0.21=19.5 (hour)
The following data record defines a set of transformers that have the same statistic data.
Where: ftr is outage frequency for transformer on site outages (occurrences/year), dtr is outage
duration for transformer on site outages (hours). In using 'in' keyword, for a three winding trans-
former to be included, all of its in-service windings must be connected to subsystem buses. In using
'from' keyword, for a three winding transformer to be included, one of its in-serve winding must be
connected to a subsystem bus.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-121
Contingency Analysis PSS™E-31.0
Perform Probabilistic Reliability Assessment Users Manual
The following data record defines generic statistic data for a set of machines.
Where: min_size and max_size are minimum and maximum size of generators in the set, the
MBASE of generators are checked against the limits. Fmt is frequency of unit outage (occur-
rences/year), dmt is duration of unit outage (hours)
The following records define statistic data for a specific user specified contingency:
CONTINGENCY 'LABEL' f d
Where: ’f’ and ’d’ are frequency and duration of user specified outages respectively. As discussed
before, statistics of user specified contingencies can be specified in .con file or in statistic data file
in above format, if both files have statistics for the same user specified contingencies, the values in
outage statistic data file will be applied.
The following data record defines statistic data for a non-transformer branch or two winding
transformer.
Similarly the following data record defines statistic data for a three-winding transformer:
When the multi-section reporting option is enabled, the frequency and probability of a multi section
line is equal to the sum of frequencies and probabilities of all its members.
5-122 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Perform Probabilistic Reliability Assessment
• Perform contingency analysis. The contingency screening results (.acc output files) are
required to computed reliability indices.
• select the Power flow > Reliability > probabilistic reliability assessment option,
after setting up options and specifying input files, perform reliability assessment. If
deterministic reliability indices are computed, Outage Statistic data File is not required.
• Analyzing the results
Three output modes are available when reporting results: post-contingency, post-tripping simula-
tion, and post-corrective actions. Each output mode corresponds to one stage in the evaluation of
a contingency. When performing multiple level contingency analysis (see Section 5.3), a running
mode is specified according to selections of options of perform multiple contingency analysis, per-
form tripping simulations and perform corrective actions. The running mode determines how many
stages in a contingency analysis are involved. e.g. if all three options are selected, a contingency
and its following sequences: tripping events and corrective actions are simulated and then each
contingency may have one load flow solution with respect to each option stored in the Contingency
Analysis Output File, the solution after a contingency being imposed, the one after simulating trip-
ping events triggered by the contingency, and the last one is after applying corrective actions that
are specified to relieve violations in the second solution. In other words, a contingency analysis con-
sists of three stages. By specifying output mode option, users have access to power flow solutions
at each stage. If power flow solutions for an output mode do not exist in the output files, load flow
solutions at previous stage will be used for the output mode. e.g., tripping simulation option is dis-
abled prior to contingency analysis, therefore there are no post-tripping solutions in result files. If
output mode is set as post-tripping, reliability results under post-tripping mode are identical to those
under post-contingency mode.
When calculating probabilistic load curtailment indices, results may be quite different under different
output mode, since load curtailments may be caused by contingencies, tripping events, generation
dispatch and corrective actions.
In order to better understand the output, several examples are developed with the savnw.sav power
flow case. The .sub, .mon, and .con files for contingency analysis and an example outage statistic
data file .prb for reliability assessment are provided in the example directory. Contingency analysis
is performed by multiple level contingency analysis function with simulations of tripping and correc-
tive actions sequences.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-123
Contingency Analysis PSS™E-31.0
Perform Probabilistic Reliability Assessment Users Manual
5-124 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Users Manual
PSS™E-31.0
Siemens Power Transmission & Distribution, Inc., Power Technologies International
Figure 5-52. System Reliability Indices Summary Under Post-Corrective Action Mode
Contingency Analysis
5-125
Contingency Analysis PSS™E-31.0
Perform Probabilistic Reliability Assessment Users Manual
Figure 5-53 shows system loss of load report under post-corrective actions mode. System load cur-
tailments results are dependent on the options used in the multiple level contingency analysis. The
sum of frequency, average duration and probability causing the corresponding amount of load cur-
tailments are reported. The interrupted power I.P. and Expected Unserved Energy E.U.E. are
provided. Note for E.U.E, the duration is one year (8760 hours). The study subsystem is specified
as 'ENTIRE SYSTEM'
<-- LOAD CURTAILMENTS --> FREQ. DURATION PROB. I.P. E.U.E NO. OF WORST CONT.
<----- (MW) -----> (OC/Y) (HOUR) (H/Y) (MW/Y) (MWH/Y) CONT.
80.0 -- 90.0 3.6272 10.0 36.4 290.17 2911.76 2 OVRLOD 14
160.0 -- 170.0 6.8657 10.0 68.9 1098.51 11029.22 2 OVRLOD 17
ENTIRE SYSTEM 10.4928 10.0 105.3 1388.68 13940.98 4
Figure 5-55 shows overload probabilistic indices for each circuit and for the study subsystem. Spe-
cifically, the sum of frequency, average duration and probability of all contingencies resulting in a
circuit overload are reported. The system overload impact index is equal to the sum of overload
impact indices of all circuits. As we can see, the total number of contingencies that result in overload
problem in Figure 5-54 is much bigger than that in Figure 5-55; this is because some contingencies
with overload problems had zero statistics or statistics less than cutoff values.
5-126 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Users Manual
PSS™E-31.0
Siemens Power Transmission & Distribution, Inc., Power Technologies International
<------ O V E R L O A D E D L I N E S -------> FREQ. DURATION PROB. IMPACT MAX VIO. NO. OF WORST CONT.
<------ F R O M ------> <------ T O ---- -->CKT (OC/Y) (HOUR) (H/Y) (PU) (%) CONT.
ENTIRE SYSTEM 0.4113 9.1 3.7 3.68 0.00 6
203 EAST230 230.00 154 DOWNTN 230.00 0.3518 9.8 3.4 3.62 211.90 3 14_20
205 SUB230 230.00 154 DOWNTN 230.00 0.0744 5.0 0.4 0.06 120.68 4 15_22
With reliability diagram annotation, one of three data categories can be displayed one a time on the
reliability diagram; they are contingency solution, deterministic reliability results, and probabilistic
reliability results. Under each data category, several data quantities are available. When a data cat-
egory does not exist in the reliability assessment analysis, the corresponding option is disabled.
Note to display bus voltage violations, a voltage limit record and either its lower or upper limit must
be specified. On the diagram voltage violations for one monitored voltage limit record are shown at
a time.
5-128 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Perform Probabilistic Reliability Assessment
Figure 5-57. Reliability Diagram Annotation
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-129
Contingency Analysis PSS™E-31.0
Perform Probabilistic Reliability Assessment Users Manual
Figure 5-58 shows branch flow overloads. Only monitored branches have values and are shown in
the diagram. Overloaded circuits are branches from bus 154 to bus 203 and from bus 154 to bus
205. Note that the results shown in the diagram are calculated on the basis of contingency analysis
results and specified options in reliability assessment. (e.g rating set, percent loading, cutoff values
of frequency and probability). In this example, branch flow overloading probabilistic indices are on
the basis of 100% of rating A. If users want to change the results in the diagram by changing the
rating set, then a reliability assessment analysis has to be redone. Following are parameters whose
change requires redoing reliability assessment to refresh the diagram view.
Figure 5-59 shows bus load curtailment probabilistic results. Expected Unserved Energy at buses
153 and 154 are 5546.6 MWH/Y and 8480.8MWH/Y respectively.
5-130 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Contingency Analysis
Users Manual Perform Probabilistic Reliability Assessment
The Contingency Solution Output File must be created by the multiple level contingency analysis
function in PSS™E-31 or later to compute probabilistic reliability indices.
Contingencies with frequencies and probabilities of zeros have no impact on probability indices.
When a user specified contingency does not have statistics specified, it is treated as a multiple inde-
pendent outage and its statistic data is determined on the basis of the individual outages of which
it consists. In case any one among them has unknown or zero frequency or duration, its statistics
will be zeros. For contingencies consisting of closing outages, FACTs device outages and boundary
condition changes (specified by keywords SET/CHANGE/INCREASE/ DECREASE /MOVE), since
statistics of these outages can not be defined in outage statistic data file, statistics of such contin-
Siemens Power Transmission & Distribution, Inc., Power Technologies International 5-131
Contingency Analysis PSS™E-31.0
Perform Probabilistic Reliability Assessment Users Manual
gencies then can not be calculated must be given explicitly in outage statistics data file or in
Contingency Description Data File, otherwise their statistics are zeros.
The multiple level contingency analysis function can simulate a contingency and event sequences
following the contingency. For a contingency, there may be three solutions: post-contingency, post-
tripping, and post-corrective actions solutions. It is important to properly select the stage at which
the reliability assessment will be performed. When analysis is performed on solutions at the stage
which does not exist in Contingency Analysis Output File, the solutions at previous stage will be
used.
Reliability measures can be obtained as a function of the severity of problems without repeating the
contingency analysis. For example, PSS™E can be used to compute failure indices for 10%, 20%,
and more severe levels of overloads. Such computations can be done entirely within activity
RELIND by adjusting the overload failure criterion and obtaining the reliability index output corre-
sponding to each overload rating. The procedure to change voltage limits is to edit voltage monitor
records in Monitored Element Data File (only the values of limits can be changed), and then rec-
reate the Distribution Factor Data File. The reliability assessment can then be performed with newly
created DFAX file without redoing contingency analysis. However, when other changes are made
to Monitored Element Data File and Contingency Description Data File, the whole procedure must
be gone through to perform probabilistic reliability assessment.
Reliability calculations can be obtained for different outage statistics without repeating the contin-
gency analysis. This can be done by preparing two or more sets of outage statistics, and simply
repeating the reliability calculations in RELIND after each set of outage data has been read into the
program. This feature is useful for studying the impact of severe weather conditions and to deter-
mine the sensitivity of results to specific outages and to uncertainties in outage statistics.
If there are violations in the base case with specified failure criteria, all other states will result in
system problems on the basis of the second assumption of the algorithm in PSS™E, and then the
probability of system problems should be equal to 1; in other words, system problems always exist.
In this case, PSS™E will neglect the probability of the base case, and add up probabilities of all
outages with system problems to calculate probabilistic indices. However, the double counting
problem is more prominent because it is most likely that tested outages have system problems if
the base case has problems.
When probabilistic indices are used to compare the relative performance of the system under dif-
ferent operating conditions or with different system configurations, a contingency analysis must be
performed for each initial system condition (base case). The different operating conditions can be
simulated by means of load or dispatch adjustments, or by outages of specific network elements in
the pre-disturbance condition. Different system configurations can be represented using appro-
priate system adjustment activities within PSS™E, such as CHNG activity.
5-132 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Chapter 6
Transmission Transfer Limit
Analysis
As shown in Section 5.5 a DC technique gives a quick solution. A common approach used to find
a limiting solution is to start with a base case and calculate the sensitivity of flow in monitored ele-
ments or groups of elements to a variation in interchange. This technique is often referred to as a
distribution factor technique. Once the sensitivity of elements is known, linear projections can be
used to estimate permissible interchanges based on thermal limits. P1, P2 and P3 represents linear
line flow functions of the net import. The horizontal line rating intersects P1 impassing a limit or net
import restriction. Figure 6-1 graphically shows this technique.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 6-1
Transmission Transfer Limit Analysis PSS™E-31.0
Calculating Transmission Transfer Limits Users Manual
Power transfer distribution factors relating changes in branch and interface flows to a change in
study system interchange are determined. The maximum study system export or import is then
derived by extrapolation subject to the constraint that no monitored elements exceed a specified
percentage of a selected rating. This process may be repeated for a designated set of user speci-
fied contingency cases.
The process will perform all the contingencies identified in the contingency description file pro-
cessed when building the distribution factor file. Further, the process uses the monitored list file,
which allows the lines to be monitored and interfaced. This feature is important because these inter-
faces often define stability limits.
Note that any two subsystems identified in the *.sub file can be used for the transfer analysis. Fur-
ther, however, it should be noted that the limits will be found based on only those elements (lines
and interfaces) which are monitored, i.e., included in the *.mon file.
In Figure 6-2 it can be seen that Areas A and C form the "study" and "opposing" system, respec-
tively. Transfers take place directly and via Area B. It is important therefore to monitor lines within
Area B or interfaces between Area B and the other two areas to ensure that the correct limits are
identified.
Figure 6-2. Study System (A) and Opposing System (C). Area B Potentially
Limiting
The interchange limits calculation is launched using the Power Flow>Linear network>Transmis-
sion interchange limits calculation (TLTG) option. This option will display the Transmission
interchange limits calculation dialog, shown in Figure 6-3 with default values.
6-2 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Transmission Transfer Limit Analysis
Users Manual Calculating Transmission Transfer Limits
The first requirement is for the user to identify the linearized network model Distribution Factor file
built as described in Section 5.2.1.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 6-3
Transmission Transfer Limit Analysis PSS™E-31.0
Calculating Transmission Transfer Limits Users Manual
Convert ratings code: If the convert ratings code box is checked, ratings of monitored branches
are converted to estimated MW ratings based upon each monitored line’s Mvar loading at the
metered end in the base case AC solution.
Line flow code: This defines the base flow to be used in deriving branch flow estimates. The user
can select the AC or the DC base case conditions.
Phase shifter in base case: This can be set to "Lock" or "Regulate" If set to regulate any regulating
phase shifter whose adjustment control mode COD n is set to +3 holds its base case flow in all base
case shift solutions. Otherwise, all phase shift angles are locked at their base case settings.
Base case constraints in contingency cases: The user can choose to recognize, "include", both
the base case and contingency case flow constraints in calculating the pre-contingency interchange
limits for each contingency case. Otherwise, "ignore" the base case constraints and consider only
the contingency case loadings (see Section 6.2.3.3).
Add study system ties to monitored lines: The user can check this box to have study system tie
lines included as monitored elements.
Minimum contingency case pre-shift flow change and Minimum contingency case distribu-
tion factor change: These provides a means of ignoring those monitored elements which, in a
contingency case, are not significantly affected by the contingency. If the magnitude change in pre-
shift flow from the base case value is less than this minimum flow change threshold and the mag-
nitude change in the power transfer distribution factor from the base case value is less than the
distribution factor change threshold, the monitored element is ignored.
Study system generation shift: This is the value of change in total generation in the study system.
If the value entered is positive, export limits are to be determined; otherwise, import limits are to be
calculated. The "generation shift" is apportioned among generator and load buses in the "study" and
"opposing" systems in proportion to the participation factors specified in the "participation block
structure" of the Subsystem Description Data file. Alternatively the "shift" is shared among gener-
ator buses in proportion to their plant MBASEs (i.e., the sum of the MBASEs of in-service machines
with positive active power output at the bus). In this case, there must be at least one in-service
machine with a positive MBASE in the subsystem.
6-4 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Transmission Transfer Limit Analysis
Users Manual Calculating Transmission Transfer Limits
Opposing System: This is the network subsystem in which an opposite change, from that in the
"Study" system, is made.
Minimum distribution factor: This is the second of three "cutoff" thresholds for including moni-
tored elements in the summary report. For small distribution factors, with levels below this
threshold, there will be no reporting for the related element.
Maximum time report samet: This is the third of three "cutoff" thresholds for including monitored
elements in the summary report. This will limit the number of times an element is reported in the
same report.
Contingency descriptions: The user can select the manner in which contingency cases are iden-
tified in the summary report. The options are to use the 12-character contingency case label or the
events comprising the contingency case or both the contingency label and the contingency events
description.
List opposing system buses: The user can check this box to provide for a listing of "opposing"
system buses, in the output report.
List study system tie lines: The user can check this box to provide for a listing of study system tie
lines in the output report.
Output code: This provides for a selection of either a "Summary" report of all cases considered or
a "Full" report which will comprise a monitored element flow table for each case considered followed
by a summary report of all cases considered
Interchange limit output: This output code provides for selection of either "incremental transfer
capability" or "total transfer capability" as the desired output quantity.
Elements in flow tables: This is the number of elements to include in flow tables allowing the user
to limit the flow table for each case reported to the "n" most restrictive monitored elements.
Apply summary minimum distribution factor to report: If checked, this will cause the limitation of
reported output to only those elements whose distribution factors are greater than the "Minimum
distribution factor magnitude" referred to in Section 6.2.1.4.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 6-5
Transmission Transfer Limit Analysis PSS™E-31.0
Calculating Transmission Transfer Limits Users Manual
The program will check to ensure that there are no buses which are members of both of the selected
subsystems. If any such buses are found, they are alarmed and the process is terminated.
The largest active power mismatch corresponding to the present AC solution voltage vector in the
working case is calculated and printed.
If the convert ratings option was enabled, ratings from the selected rating set(s) of those monitored
branches having nonzero rating(s) are modified. For each such branch, the Mvar loading is calcu-
lated and MW rating(s) are determined under the assumption that the Mvar loading is unchanged
under power transfer and contingency conditions.
Using the incremental form of the DC power flow equation (see Section 5.5) and the power shift
vector, phase angle changes are calculated, followed by incremental line flows for all monitored
lines and interfaces. These are transformed into a vector of base case power transfer distribution
factors, and the interchange limit is determined by extrapolation such that all monitored elements
satisfy their rating constraints.
The "base case" DC network solution is calculated and the solution summarized as in the following
example:
In listing study system buses, opposing system buses, and study system tie lines, the tabulation
may be terminated by entering the AB interrupt control code. In this case, the interrupt is cleared
and processing continues. Once the interchange limit calculations have started, the process may
be terminated by entering the AB interrupt control code.
6-6 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Transmission Transfer Limit Analysis
Users Manual Calculating Transmission Transfer Limits
Figure 6-4. Subsystem file and Power Flow Condition for Transfer Analysis
6.2.3.1 Viewing the Transfer Limit Analysis Base Case Conditions Report
Base case conditions are reported first. The report lists the study system generation, the opposing
system generation, and the study system net interchange corresponding to the network solution
before and after applying the generation shift. This is followed by a tabulation of the pre-shift and
post-shift generation at those study system and opposing system buses participating in the gener-
ation shift. Loadings on monitored elements are then reported, sorted such that the most restrictive
elements are listed first. Either incremental or total pre-contingency transfer limits, as appropriate,
are listed.
Flow estimates are listed for each of three interchange schedules: with the original generation pro-
file, with the specified generation shift, and at the generation shift corresponding to the transfer level
limit required for the most restrictive monitored element (i.e., the one listed first). Any flow at or
above the selected percentage of the appropriate rating is followed by an asterisk ("∗"). The power
transfer distribution factor relating the change in flow on the monitored element to a change in study
system net interchange is also tabulated, along with the rating of the monitored element; for
branches, this is not the percentage of the rating used in determining the interchange limit, but
either the value of rating entered as raw data and the data editor windows, or, if the convert ratings
option was selected at the start of this transfer analysis calculation, the estimated MW ratings.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 6-7
Transmission Transfer Limit Analysis PSS™E-31.0
Calculating Transmission Transfer Limits Users Manual
Figure 6-5 shows the report obtained using the example files (savnw.*) from which was built the dc-
contingency.dfx distribution factor file. The file names are listed in the report as shown.
The pre- and post-shift generation levels and the net interchange are listed for the "Study" and
"Opposing" systems. In this example, a shift of 100 MW is assumed. The generators which partic-
ipate in both systems to make the + 100 MW shift are listed. They are the nuclear plants at buses
101 and 102 in the "Study" system and the generators at buses 206 and 211 in the "Opposing"
system.
6-8 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Transmission Transfer Limit Analysis
Users Manual Calculating Transmission Transfer Limits
Figure 6-5. Base Case Results for Two Area Transfer Limit Calculation
Siemens Power Transmission & Distribution, Inc., Power Technologies International 6-9
Transmission Transfer Limit Analysis PSS™E-31.0
Calculating Transmission Transfer Limits Users Manual
For the base case condition, it can be seen that the element which is most restrictive for transfers
is the "INTERFACE EAST". This interface comprises 4 branches which tie the Study and Opposing
systems. Consequently, all transfer takes place across these branches. This is why the Distribution
factor has a value of 1.0. This means that 100% of any generation shift will flow on this interface.
The flow in the PRE-SHIFT condition is 130.8 MW on the interface. If a 100 MW shift is imposed,
the POST-SHIFT flow on the interface will increase by 100 MW to 230 MW as shown. The shift can
be increased until the flow on the interface is 350 MW, its thermal limit. this is the "LIMIT" case.
It can be seen that the flow on the limiting interface can increase by 220 MW (350-131) before
reaching its thermal limit. Consequently, the "TOTAL" transfer limit will be the pre-shift flow of 278.7
MW plus the possible 220 MW increase. As the report shows, therefore, the transfer limit for the
base case condition is 497.9 MW and is caused by the thermal limit on the "INTERFACE EAST".
As the listing shows, the next most restrictive element is the branch from Bus 201 to Bus 151. The
results are showing that, if the "INTERFACE EAST" thermal limit were removed (by upgrading or
other means), this branch would create the limit; in this case it is 1,330 MW.
Similar calculations can be done to check the other, less restrictive limits shown in the report listing.
Note that the limit imposed by the branch from Bus 205 to Bus 154 is marginally more complicated
to check because the generation shift actually decreases flow on this branch. It is necessary to con-
sider the flow direction on the branches (to and from) and the sign of the distribution factors.
Three-Winding Transformers
For monitored three-winding transformer windings, flow estimates are calculated at the winding bus
end as power flowing into the transformer. For other monitored branches, flow estimates are calcu-
lated at the metered end in the "from bus" to "to bus" direction. The flow across an interface is taken
as the sum of the flows of its members. For three-winding transformer windings, the flow is calcu-
lated at the winding bus as power flowing into the transformer. For other members, the flow is
calculated at its metered end in the "from bus" (the first bus specified in entering the branch) to
"to bus" direction.
An curtailed example of the report listing for the contingency cases is shown in Figure 6-6.
6-10 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Transmission Transfer Limit Analysis
Users Manual Calculating Transmission Transfer Limits
A summary report tabulates the number of system condition solutions attempted and the number
for which there exists no interchange schedule at which the rating constraint can be satisfied for all
monitored elements.
This is followed by a tabulation of monitored elements for all system conditions which were calcu-
lated, in order of increasing incremental or total transfer capability, as appropriate. The limiting
element is listed along with its power transfer distribution factor, its pre-shift contingency case flow,
its rating, and a description of the system condition.
Only those monitored elements satisfying the "cutoff" threshold solution parameters set by the user
are included in the summary. Once an element has been listed the maximum number of times "n",
its "nth" occurrence includes an asterisk ("∗") before its description, and further reporting of the ele-
ment is suppressed.
This summary report is reprinted for each selected interface with interface transfer limits and distri-
bution factors rather than study system interchange limits and distribution factors tabulated. All
distribution factors on the interface transfer limits summary report describe changes in monitored
element flow relative to a change in interface flow. The branches which form the interface are listed
on the first page of an interface’s transfer limit summary report.
The final page of the summary report lists those elements which were reported "n" times, sorted by
the number of times they would have been reported.
If a line outage contingency forms an island with no type three (swing) bus, a singular submatrix is
formed. Any monitored branch which resides in the swingless island, as well as any interface which
includes such a branch as a member, has dashes printed where its contingency case results would
normally be printed.
The distribution factor is 0.07566. Consequently the transfer has to be reduced by 335 MW ( that is
25.4 MW divided by 0.07566) from its current level of 278.7 MW. This, rounding off, is 57 MW less
than the base case (pre-shift) transfer.
The process detects the specification of duplicate single and double line outage contingencies and
calculates the contingency case solution only for the first specification of such a contingency. Any
contingency cases involving bus boundary contingency events, line closure contingency events, or
more than two line outage contingency events are not checked for duplication.
The values shown as monitored element flows are set as described in Section 5.5.2.5. The user
selects the base flow value to be used by setting the line flow code solution parameter at the start
of the process.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 6-11
Calculating Transmission Transfer Limits
Transmission Transfer Limit Analysis
6-12
Siemens Power Transmission & Distribution, Inc., Power Technologies International
Typical output for Contingency case. Most restrictive transfer limit is negative due to overload prior to shift during contingency.
Partial Summary Listing showing Contingency Testing results in order of Increasing Transfer Capability
Users Manual
PSS™E-31.0
Figure 6-6. Partial Listing of Report for Two Area Transfer Limits for Contingency Cases
PSS™E-31.0 Transmission Transfer Limit Analysis
Users Manual Calculating Transmission Transfer Limits
In the contingency case monitored flow tables, transfer limits may be calculated using either of the
following approaches:
1. Both pre-contingency and post-contingency flows must satisfy their appropriate rating
constraints (i.e., both the base case and the contingency case must have no
overloads).
The user selects the method to be used by selecting or not to ignore the base case constraints. This
selection has no effect on the summary report. For contingency cases, the transfer capability shown
is always that at which the monitored element is at its limit in the contingency case. Thus, the selec-
tion is meaningful only if the full output option is selected.
When the Apply summary minimum distribution factor to Report box is checked and the
Minimum distribution factor Magnitude is set to greater than zero, monitored elements with dis-
tribution factor magnitudes below the threshold are ignored in calculating the corresponding
monitored element flow table as well as being omitted from the summary report.
If the Convert ratings to estimated MW Ratings box is checked, any percentage of rating param-
eter is applied after the conversion to estimated MW ratings. Interface ratings are not affected by
the convert ratings solution parameter.
Line loss estimates and line shunts of outaged lines are handled as in the DC Load Flow solution
process.
It is required that the working case be solved to an acceptable mismatch tolerance prior to initiating
this transfer limit analysis.
It is entirely possible that, for a given system condition, there is no interchange schedule at which
the linearized network model results in all monitored elements satisfying their rating constraints.
This could occur, for example, if the pre-shift solution had two overloaded branches, and one
required an increase in interchange to relieve its overload while the other required a decrease in
interchange.
The settings of the Minimum contingency case pre-shift flow Change and the Minimum
contingency case distribution factor Change solution options may be used to exclude from con-
sideration in a contingency case those monitored elements which are not greatly affected by the
contingency. This could result in a situation in which none of the remaining monitored elements
have nonzero ratings. Such insoluble conditions are described in the output block for that condition
when full output is selected; when the summary report is chosen, such cases are identified.
When specifying a rating percentage of other than one hundred percent, note that interface ratings
are also scaled by the specified percentage in checking their flows to determine maximum
interchange.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 6-13
Transmission Transfer Limit Analysis PSS™E-31.0
Factoring Generation Participation in Transfer Limit Analysis Users Manual
It is clear that this analysis is similar to that described in Section 6.2, the difference here being that
the shifts in export or import are defined on the basis of specific participating elements in the "study"
and "opposing" systems.
The process described here accesses a Distribution Factor Data File to pick up subsystem, moni-
tored element and contingency definitions. In addition, however, it accesses a Subsystem
Participation Data File in which alternative participation data may be provided for the study and/or
opposing systems.
Power transfer distribution factors relating changes in branch and interface flows to a change in
study system interchange are determined. The maximum study system export or import is then
derived by extrapolation subject to the constraint that no monitored elements exceed a specified
percentage of a selected rating. This process may is then repeated for a designated set of user
specified contingency cases.
The process will perform all the contingencies identified in the contingency description file pro-
cessed when building the distribution factor file. Further, the process uses the monitored list file,
which allows the lines to be monitored and interfaced. This feature is important because these inter-
faces often define stability limits.
Note that any two subsystems identified in the *.sub file can be used for the transfer analysis. Fur-
ther, however, it should be noted that the limits will be found based on only those elements (lines
and interfaces) which are monitored, i.e. included in the *.mon file.
6-14 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Transmission Transfer Limit Analysis
Users Manual Factoring Generation Participation in Transfer Limit Analysis
.
.
.
Each set of data for a subsystem contains the subsystem label enclosed in single quotes (see
Section 5.2.2.3), followed by data for up to five participation blocks, followed by line containing a
zero:
'label'
.
.
.
BLOCKF
IBUS PF
.
.
.
IBUS PF
0 End of participation block
Siemens Power Transmission & Distribution, Inc., Power Technologies International 6-15
Transmission Transfer Limit Analysis PSS™E-31.0
Factoring Generation Participation in Transfer Limit Analysis Users Manual
where:
BLOCKF Is a positive value defining the block participation factor. BLOCKF is typically
expressed in percent or per unit of the maximum permissible power shift which is
to be assigned to the participation block.
IBUS Is the bus number of a bus assigned to subsystem "label". A subsystem bus may
be a member of no more than one participation block.
PF Is a nonzero value defining the bus participation factor. PF is typically expressed
in percent or per unit of the power shift assigned to this participation block. While
individual PF value may be negative, the sum of PF factors within each participa-
tion block must be positive.
The first requirement is for the user to identify the linearized network model Distribution Factor file
built as described in Section 5.2.3.2 and the Subsystem participation data file.
The second requirement is to make the necessary and appropriate selections for the subsystems
to be tested and the solution and output options discussed below.
6-16 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Transmission Transfer Limit Analysis
Users Manual Factoring Generation Participation in Transfer Limit Analysis
Convert ratings code: If the convert ratings code box is checked, ratings of monitored branches
are converted to estimated MW ratings based upon each monitored line’s Mvar loading at the
metered end in the base case AC solution.
Line flow code: This defines the base flow to be used in deriving branch flow estimates. The user
can select the AC or the DC base case conditions.
Phase shifter in base case: This can be set to "Lock" or "Regulate" If set to regulate any regulating
phase shifter whose adjustment control mode COD n is set to +3 holds its base case flow in all base
case shift solutions. Otherwise, all phase shift angles are locked at their base case settings.
Add study system ties to monitored lines: The user can check this box to have study system tie
lines included as monitored elements is checked.
Minimum contingency case pre-shift flow change and Minimum contingency case distribu-
tion factor change: These provides a means of ignoring those monitored elements which, in a
contingency case, are not significantly affected by the contingency. If the magnitude change in pre-
shift flow from the base case value is less than this minimum flow change threshold and the mag-
nitude change in the power transfer distribution factor from the base case value is less than the
distribution factor change threshold, the monitored element is ignored.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 6-17
Transmission Transfer Limit Analysis PSS™E-31.0
Factoring Generation Participation in Transfer Limit Analysis Users Manual
Study system generation shift: This is the value of change in total generation in the study system.
If the value entered is positive, export limits are to be determined; otherwise, import limits are to be
calculated. The "generation shift" is apportioned among generator and load buses in the study
system in proportion to the participation factors specified in the "participation block structure" of the
Subsystem Description Data file (see Section 6.3.1) or in a series of sequential shifts as defined in
the Subsystem Participation Data file described above. If no participation block was entered for the
study system in either file, the generation shift is shared among generator buses in proportion to
their plant MBASEs (i.e., the sum of the MBASEs of in-service machines with positive active power
output at the bus). In this case, there must be at least one in-service machine with a positive MBASE
in the subsystem. Similar opposite "generation shifts" are applied to buses in the opposing system,
again according to their participation factors or MBASEs.
6-18 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Transmission Transfer Limit Analysis
Users Manual Factoring Generation Participation in Transfer Limit Analysis
Using the incremental form of the DC power flow equation (see Section 5.5) and the generation shift
vectors, phase angle changes are calculated, followed by incremental line flows for all monitored
lines and interfaces. These are transformed into vectors of base case power transfer distribution
factors, and the interchange limit is determined by extrapolation such that all monitored elements
satisfy their rating constraints.
Opposing System: This is the network subsystem in which an opposite change, from that in the
"Study" system, is made.
Minimum distribution factor: This the second of three "cutoff" thresholds for including monitored
elements in the summary report. For small distribution factors, with levels below this threshold,
there will be no reporting for the related element.
Maximum time report same element: This the third of three "cutoff" thresholds for including mon-
itored elements in the summary report. This will limit the number of times an element is reported in
the same report.
Contingency descriptions: The user can select the manner in which contingency cases are iden-
tified in the summary report. The options are to use the 12-character contingency case label or the
events comprising the contingency case or both the contingency label and the contingency events
description.
List opposing system buses: The user can check this box to provide for a listing of "opposing"
system buses, in the output report.
List study system tie lines: The user can check this box to provide for a listing of study system tie
lines in the output report.
Output code: This provides for a selection of either a "Summary" report of all cases considered or
a "Full" report which will comprise a monitored element flow table for each case considered followed
by a summary report of all cases considered
Interchange limit output: This output code provides for selection of either "incremental transfer
capability" or "total transfer capability" as the desired output quantity.
Elements in flow tables: This is the number of monitored elements to include in flow tables
allowing the user to limit the flow table for each case reported to the "n" most restrictive monitored
elements.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 6-19
Transmission Transfer Limit Analysis PSS™E-31.0
Factoring Generation Participation in Transfer Limit Analysis Users Manual
Apply summary minimum distribution factor to report: If checked this will cause the limitation
of reported output to only those elements whose distribution factors are greater than the "Minimum
distribution factor magnitude" referred to in Section 6.3.2.4.
The program will check to ensure that there are no buses which are members of both of the selected
subsystems. If any such buses are found, they are alarmed and the process is terminated.
The largest active power mismatch corresponding to the present AC solution voltage vector in the
working case is calculated and printed.
If no subsystems are defined an appropriate error message is printed and the interchange calcula-
tion process is terminated. If only one subsystem is defined, a second subsystem ("WORLD") is
assumed containing those buses in the power flow case which are not assigned to the specified
subsystem.
If the convert ratings option was enabled, ratings from the selected rating set(s) of those monitored
branches having nonzero rating(s) are modified. For each such branch, the Mvar loading is calcu-
lated and MW rating(s) are determined under the assumption that the Mvar loading is unchanged
under power transfer and contingency conditions.
Using the incremental form of the DC power flow equation (see Section 5.5) and the power shift
vector, phase angle changes are calculated, followed by incremental line flows for all monitored
lines and interfaces. These are transformed into a vector of base case power transfer distribution
factors, and the interchange limit is determined by extrapolation such that all monitored elements
satisfy their rating constraints.
The "base case" DC network solution is calculated and the solution summarized as in the following
example:
6-20 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Transmission Transfer Limit Analysis
Users Manual Factoring Generation Participation in Transfer Limit Analysis
The "generation shift" is apportioned among generator and load buses in the study system in a
series of sequential shifts as defined in the Subsystem Participation Data File described above.
The "base case" solution is then reported, followed by processing of the designated contingency
cases with contingency case flow estimates. Prior to terminating, an ordered summary report from
among all the cases calculated is tabulated.
The user is given the option of having the summary report repeated with interface transfer limits and
distribution factors for a selected interface (as indicated in Section 6.3.2.6) mentioned in Listed
rather than study system transfer limits and distribution factors. The "interface" distribution factors
listed on the "interface" summary report are measures of the changes in monitored element flows
to a change in base case interface flow.
In listing study system buses, opposing system buses, and study system tie lines, the tabulation
may be terminated by entering the AB interrupt control code. In this case, the interrupt is cleared
and processing continues. Once the interchange limit calculations have started, the interchange
calculation process may be terminated by entering the AB interrupt control code.
When multiple participation blocks are specified in the Subsystem Participation Data File for the
study and/or opposing systems, the study system generation shift and the block participation fac-
tors specified in the Subsystem Participation Data File are used to allocate portions of the specified
shift sequentially among the participation blocks. Within each participation block, its allocation is
assigned to the block's participating buses in proportion to their bus participation factors. Thus, the
sensitivity of each monitored element's flow to an incremental change in study system interchange
is defined by a set of power transfer distribution factors which vary according to the current level of
study system interchange.
Flow estimates are listed for each of three interchange schedules: with the original generation pro-
file, with the specified generation shift, and at the generation shift corresponding to the transfer level
limit required for the most restrictive monitored element (i.e., the one listed first). Any flow at or
above the selected percentage of the appropriate rating is followed by an asterisk ("∗"). The power
transfer distribution factor relating the change in flow on the monitored element to a change in study
system net interchange is also tabulated. When multiple participation blocks were specified for
either the study or opposing system, the power transfer distribution factors printed are those that
apply at the transfer level required for the most restrictive monitored element.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 6-21
Transmission Transfer Limit Analysis PSS™E-31.0
Factoring Generation Participation in Transfer Limit Analysis Users Manual
For each monitored element reported, its rating is listed; for branches, this is not the percentage of
the rating used in determining the interchange limit, but either the value of rating entered as raw
data and the data editor windows, or, if the convert ratings option was selected at the start of this
transfer analysis calculation, the estimated MW ratings.
Figure 6-9 shows the report obtained using the example files (savnw.*) from which was built the dc-
contingency.dfx distribution factor file. The example data files used (*.sub, *.mon, *.con) can be
seen listed at the top of the report listing. They are available in the PSS™E EXAMPLE directory.
As an example, a Subsystem Participation Data file was prepared for the two study areas "STUDY"
and "EAST" identified in the savnw.sub file. The file is shown in Figure 6-8 where it can be seen that
generators at Buses 101 and 102, in the "STUDY" subsystem are identified as participating at 20%
and 80% respectively. In the "EAST" subsystem, the "opposing" system, there are two participation
blocks, one of which has a participation of 30% and the other which participation of 70%. Each block
has a participating generator and load bus.
For the purposes of running and example case, a total shift of 100 MW is assumed. In the Report
listing, Figure 6-9, it can be seen that this shifts in the "study" and "opposing systems are appor-
tioned as defined by the participation block ratios as identified in Figure 6-8.
6-22 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Transmission Transfer Limit Analysis
Users Manual Factoring Generation Participation in Transfer Limit Analysis
Figure 6-9. Sequential Participation Interchange Limit Output for Base Case
Siemens Power Transmission & Distribution, Inc., Power Technologies International 6-23
Transmission Transfer Limit Analysis PSS™E-31.0
Factoring Generation Participation in Transfer Limit Analysis Users Manual
It can be seen that the transfer capabilities and participation factors are different from those shown
in Figure 6-5 where sequential participation factors were not used. There, the power shift is appor-
tioned relative to the MBASE value for the machines in the two participating systems.
Three-Winding Transformers
For monitored three-winding transformer windings, flow estimates are calculated at the winding bus
end as power flowing into the transformer. For other monitored branches, flow estimates are calcu-
lated at the metered end in the "from bus" to "to bus" direction. The flow across an interface is taken
as the sum of the flows of its members. For three-winding transformer windings, the flow is calcu-
lated at the winding bus as power flowing into the transformer. For other members, the flow is
calculated at its metered end in the "from bus" (the first bus specified in entering the branch) to
"to bus" direction.
A summary report tabulates the number of system condition solutions attempted and the number
for which there exists no interchange schedule at which the rating constraint can be satisfied for all
monitored elements. This is followed by a tabulation of monitored elements for all system conditions
which were calculated, in order of increasing incremental or total transfer capability, as appropriate.
The limiting element is listed along with its power transfer distribution factor, its pre-shift contin-
gency case flow, its rating, and a description of the system condition.
Only those monitored elements satisfying the "cutoff" threshold solution parameters set by the user
when launching the calculation process are included in the summary. Once an element has been
listed the maximum number of times "n", its "nth" occurrence includes an asterisk ("∗") before its
description, and further reporting of the element is suppressed.
This summary report is reprinted for each selected interface with interface transfer limits and distri-
bution factors rather than study system interchange limits and distribution factors tabulated. All
distribution factors on the interface transfer limits summary report describe changes in monitored
element flow relative to a change in interface flow. The branches which form the interface are listed
on the first page of an interface’s transfer limit summary report.
The final page of the summary report lists those elements which were reported "n" times, sorted by
the number of times they would have been reported.
If a line outage contingency forms an island with no type three (swing) bus, a singular submatrix is
formed. Any monitored branch which resides in the swingless island, as well as any interface which
includes such a branch as a member, has dashes printed where its contingency case results would
normally be printed.
Reference can be made to Figure 6-6 which shows the report listing for the two-area Transmission
Interchange Limit calculation. The format for this two area calculation, using sequential participation
factors, is the same. The results, however, will show different interchange limits and distribution
factors.
6-24 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Transmission Transfer Limit Analysis
Users Manual Factoring Generation Participation in Transfer Limit Analysis
Since this transfer limit calculation process uses the linearized network model, note should be taken
of the approximate nature of the solution. The proper role of this analysis, therefore, should be to
focus attention on those system conditions which deserve more detailed study.
The process detects the specification of duplicate single and double line outage contingencies and
calculates the contingency case solution only for the first specification of such a contingency. Any
contingency cases involving bus boundary contingency events, line closure contingency events, or
more than two line outage contingency events are not checked for duplication.
The values shown as monitored element flows are set as described in Section 6.3.1. The user
selects the base flow value to be used by setting the line flow code solution parameter at the start
of the process; see above.
In the contingency case monitored flow tables, transfer limits are calculated such that only post-con-
tingency constraints need be satisfied.
When the Apply summary minimum distribution factor to Report box is checked and the Min-
imum distribution factor Magnitude is set to greater than zero, monitored elements with
distribution factor magnitudes below the threshold are ignored in calculating the corresponding
monitored element flow table as well as being omitted from the summary report.
If the Convert ratings to estimated MW Ratings box is checked, any percentage of rating param-
eter is applied after the conversion to estimated MW ratings. Interface ratings are not affected by
the convert ratings solution parameter.
Line loss estimates and line shunts of outaged lines are handled as in the DC Load Flow solution
process.
It is required that the working case be solved to an acceptable mismatch tolerance prior to initiating
this transfer limit analysis.
It is entirely possible that, for a given system condition, there is no interchange schedule at which
the linearized network model results in all monitored elements satisfying their rating constraints.
This could occur, for example, if the pre-shift solution had two overloaded branches, and one
required an increase in interchange to relieve its overload while the other required a decrease in
interchange.
The settings of the Minimum contingency case pre-shift flow Change and the Minimum contingency
case distribution factor Change solution options may be used to exclude from consideration in a
contingency case those monitored elements which are not greatly affected by the contingency. This
could result in a situation in which none of the remaining monitored elements have nonzero ratings.
Such insoluble conditions are described in the output block for that condition when full output is
selected; when the summary report is chosen, such cases are identified.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 6-25
Transmission Transfer Limit Analysis PSS™E-31.0
Calculating Transfer Limits with Three Participating Areas Users Manual
When specifying a rating percentage of other than one hundred percent, note that interface ratings
are also scaled by the specified percentage in checking their flows to determine maximum
interchange.
This interchange analysis differs from the two-area calculation, however, in that it considers simul-
taneous power injection shifts in two "opposing systems" in maximizing "study system" import or
export.
Two sets of base case power transfer distribution factors are determined: one set relating changes
in branch and interface flows to a change in study system interchange against the first opposing
system, and another relating changes in flows to a change in study system interchange against the
second opposing system. The maximum study system export or import is then derived by a linear
program subject to the constraint that no monitored elements exceed a specified percentage of a
selected rating. This process may then be repeated for a designated set of user specified contin-
gency cases.
The data used here is the same at that used for the two-area calculation, i.e a distribution factor
data file is required to be constructed as described in Section 5.2.2.
The user is required to identify the Distribution factor data file and to identify the name of an output
file to which the information will be written for current or later plotting of the graphical display of
results. The file is of type *.pol.
The remaining task is to make the selections for solution options, output options and graphical
output parameters.
6-26 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Transmission Transfer Limit Analysis
Users Manual Calculating Transfer Limits with Three Participating Areas
Siemens Power Transmission & Distribution, Inc., Power Technologies International 6-27
Transmission Transfer Limit Analysis PSS™E-31.0
Calculating Transfer Limits with Three Participating Areas Users Manual
Convert ratings code: If the convert ratings code box is checked, ratings of monitored branches
are converted to estimated MW ratings based upon each monitored line’s Mvar loading at the
metered end in the base case AC solution.
Line flow code: This defines the base flow to be used in deriving branch flow estimates. The user
can select the AC or the DC base case conditions.
Phase shifter in base case: This can be set to "Lock" or "Regulate" If set to regulate any regulating
phase shifter whose adjustment control mode COD n is set to +3 holds its base case flow in all base
case shift solutions. Otherwise, all phase shift angles are locked at their base case settings.
Base case constraints in contingency cases: The user can choose to recognize, "include", both
the base case and contingency case flow constraints in calculating the pre-contingency interchange
limits for each contingency case. Otherwise, "ignore" the base case constraints and consider only
the contingency case loadings.
Add study system ties to monitored lines: The user can check this box to have study system tie
lines included as monitored elements is checked
Maximum allowed opposing system generation shift: Places a bound on the permissible gen-
eration shift for each of the opposing systems.
Minimum distribution factor magnitude: This defines the minimum distribution factor magnitude
threshold for including monitored elements in the transfer limit calculation and report. Any moni-
tored element for which both of its power transfer distribution factor magnitudes are below this
threshold is ignored during the processing and reporting of the corresponding system condition.
Study system generation shift: The "generation shift" is apportioned among generator and load
buses in the study system in proportion to the participation factors specified in the "participation
block structure" of the Subsystem Description Data File. If no participation block was entered for the
study system, the generation shift is shared among generator buses in proportion to their plant
MBASEs (i.e., the sum of the MBASEs of in-service machines with positive active power output at
the bus). In this case, there must be at least one in-service machine with a positive MBASE in the
subsystem. The opposite "generation shift" is applied to buses in the first opposing system, again
according to their participation factors or MBASEs.
Opposing System 1 and Opposing System 2: These are the network subystems in which an
opposite change, from that in the "Study" system, is made.
List opposing system buses: The user can check this box to provide for a listing of "opposing"
system buses, in the output report.
List study system tie lines: The user can check this box to provide for a listing of study system tie
lines in the output report.
6-28 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Transmission Transfer Limit Analysis
Users Manual Calculating Transfer Limits with Three Participating Areas
Output code: The output code allows the user to select either a summary report of all cases con-
sidered, or a monitored element flow table for each case considered followed by a summary report
of all cases considered.
Plot Code: The user can select to produce graphical output only for the combined case or for all
cases.
Constraint plot code: The user can select to include on each plot for which a transfer limit exists
either all constraint lines or only those which form the boundary of the polygon which encloses the
feasible region.
Graphic output: This allows the user to include both the graph and the letter code key on the same
plot or on separate plots.
Place: The user can select to place the graphic results on the monitor or send to a printer.
Prior to calculation, the program will check that generators are not "converted" and that each non
type four bus is connected back to a type three (swing) bus through the in-service AC network. If
any violations are detected, an appropriate message is printed and the process is terminated.
Next, the largest active power mismatch corresponding to the present AC solution voltage vector in
the working case is calculated. If this largest mismatch is greater than the MW mismatch tolerance,
the user is given the option of continuing or terminating: the process.
The program will check to ensure that there are no buses which are members of two or all three of
the selected subsystems. If any such buses are found, they are alarmed and the process is
terminated.
If the convert ratings option was enabled at the start of the process ratings from the selected rating
set(s) of those metered branches having nonzero rating(s) are modified. For each such branch, the
Mvar loading is calculated and MW rating(s) are determined under the assumption that the Mvar
loading is unchanged under power transfer and contingency conditions.
The "base case" DC network solution is then calculated summarized as in the following example:
Siemens Power Transmission & Distribution, Inc., Power Technologies International 6-29
Transmission Transfer Limit Analysis PSS™E-31.0
Calculating Transfer Limits with Three Participating Areas Users Manual
Using the incremental form of the DC power flow equation (see Section 5.5) and the power shift
vector, phase angle changes are calculated, followed by incremental line flows for all monitored
lines and interfaces. These are transformed into a vector of base case power transfer distribution
factors. A second set of power transfer distribution factors describing the effect on the monitored
elements of an interchange shift between the study system and the second opposing system is
calculated.
Based on the two sets of power transfer distribution factors, the "study" system interchange limit is
determined by a linear programming technique such that all monitored elements satisfy their rating
constraint. The "base case" solution is reported, followed by processing of the designated contin-
gency cases.
One final optimal solution is calculated for a "combined case". This solution calculation includes
constraints for all system conditions (i.e., the base case and all contingency cases) for which an
individual optimum solution was found. This calculation therefore determines the maximum study
system export (or import, as appropriate) schedule such that no monitored element is overloaded
in the base case or under contingency conditions.
The "combined case" solution is then reported and, prior to the process terminating, the calculated
interchange limits for the base case, for all contingency cases, and for the combined case are
summarized.
In listing study system buses, opposing system buses, and study system tie lines, the tabulation
may be terminated by entering the AB interrupt control code. In this case, the interrupt is cleared
and processing continues. Once the interchange limit calculations have started, the process may
be terminated by entering the AB interrupt control code.
The "generation shifts" required to achieve the interchange limit (import or export, as appropriate)
are then listed, along with the limiting lines and/or interfaces and their ratings (see Figure 6-11).
For monitored three-winding transformer windings, flow estimates are calculated at the winding bus
end as power flowing into the transformer. For other monitored branches, flow estimates are calcu-
lated at the metered end in the "from bus" to "to bus" direction. The flow across an interface is taken
as the sum of the flows of its members. For three-winding transformer windings, the flow is calcu-
lated at the winding bus as power flowing into the transformer. For other members, the flow is
calculated at its metered end in the "from bus" (i.e., the first bus specified in entering the branch; to
"to bus" direction.
Loadings on monitored elements are then reported. The flow estimates are listed for each of four
interchange schedules: with the original generation profile; with the specified generation shift in the
study system and the opposite shift in the first opposing system; with the specified generation shift
in the study system and the opposite shift in the second opposing system; and in the case with max-
imum import or export, as appropriate, in which no monitored elements exceed the specified
percentage of the selected rating. Any flow at or above the selected percentage of the appropriate
6-30 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Transmission Transfer Limit Analysis
Users Manual Calculating Transfer Limits with Three Participating Areas
rating is followed by an asterisk ("∗"). The power transfer distribution factors relating the change in
flow on the monitored element to a change in study system net interchange with the opposite
change in the two opposing systems in turn are also tabulated, along with the rating of the moni-
tored element; for branches, this is not the percentage of the rating used in determining the
interchange limit, but either the value of rating as entered with the raw data or as modified with the
program editor or, if the convert ratings option was selected at the start of this interchange calcula-
tion, the estimated MW ratings (see Figure 6-11).
When reporting results for contingency cases, the events comprising the contingency are listed, fol-
lowed by the "generation shifts" required to achieve the transfer limit for the contingency case being
reported, along with the limiting elements. The flow table includes both the contingency case flows
in the same form as the base case report described above, as well as the base case flows at the
transfer limit. Note that if the user has so selected, only the contingency case constraints are con-
sidered in calculating the transfer limit; in this case, base case flows at the transfer limit may be
shown as overloaded since the corresponding constraints were ignored in the transfer limit
calculation.
When reporting results for the "combined case", the program tabulates the "generation shifts"
required to achieve the interchange schedule which results in maximum import (or export, as appro-
priate) while simultaneously avoiding overloading in all system conditions for which individual
optima were found. The limiting elements are listed along with the system condition in which they
are limiting. The combined case flow table includes only those elements which are part of the border
of the feasible region of a successfully solved system condition. Flows are reported in the same
form as the base case report described above, and the system condition to which they apply is
shown at the right side of each output line.
A summary page tabulates the number of optimal solutions attempted, and the number for which
there exists no interchange schedule at which the rating constraint can be satisfied for all monitored
elements. Then, for each case processed, the interchange limit is listed along with the corre-
sponding generation shifts required in the two opposing systems.
If a line outage contingency forms an island with no type three (swing) bus, a singular submatrix is
formed. Any monitored branch which resides in the swingless island, as well as any interface which
includes such a branch as a member, has dashes printed where its contingency case results would
normally be printed.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 6-31
Transmission Transfer Limit Analysis PSS™E-31.0
Calculating Transfer Limits with Three Participating Areas Users Manual
Figure 6-11. Typical Output from Interchange Calculation for Two Opposing System
6-32 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Transmission Transfer Limit Analysis
Users Manual Calculating Transfer Limits with Three Participating Areas
For each monitored element, a pair of straight lines is plotted indicating the set of interchange
schedule changes for which that element is exactly at its rating constraint. Moving to any point on
one side of any "limit line" brings the loading on the element below its limit; points on the other side
result in a limit violation. On the "violation" side of the "limit line," the background is shaded blue
(see Figure 6-13).
When all monitored elements are so plotted, the region of interchange schedule changes at which
no monitored element violates its rating constraint is shown as the "clean" portion of the graph. If
the point of maximum transfer (export or import, as appropriate) exists for a given system condition,
it occurs at the intersection of a pair of "limit lines," and is enclosed in a square. In Figure 6-13 this
is where the interchange with the EAST system is 434 MW and -226 MW with the WEST.
A single-letter code is printed at each end of any limit line which is part of the border of the polygon
forming the "clean" portion of the graph; a key is printed with the graph indicating the elements rep-
resented by each such annotated constraint line. The two lines whose intersection occurs at the
transfer limit are assigned the letter codes "A" and "B"; continuing along the border of the polygon,
successively encountered constraint lines are assigned letter codes in alphabetical order.
If the user elects to "Place" the graph in the program window, the graph will appear at completion
of the calculation. The output, however, is saved in the *.pol type file indicated by the user. That file
c a n b e p r o c e s s e d w i t h a g r a p h ic f a c i l i t y la u n c h e d w i t h t h e P o w e r F l o w > L i n e a r
networks>Interchange limits calculations (POLY) - previous results… option (see Figure 6-
12).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 6-33
Transmission Transfer Limit Analysis PSS™E-31.0
Calculating Transfer Limits with Three Participating Areas Users Manual
Figure 6-12. Processing the Graphics file for Reporting Interchange Results
for Two Opposing Systems
6-34 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Transmission Transfer Limit Analysis
Users Manual Calculating Transfer Limits with Three Participating Areas
Siemens Power Transmission & Distribution, Inc., Power Technologies International 6-35
Transmission Transfer Limit Analysis PSS™E-31.0
Calculating Transfer Limits with Three Participating Areas Users Manual
6-36 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Chapter 7
Short-Circuit Fault Analysis
The system under study is modeled by three symmetrical component sequence networks based on
the positive-, negative-, and zero-sequence parameters of the three-phase power system elements.
The topology of the system, the positive-sequence parameters of all components (except genera-
tors in some cases), and the pre disturbance system conditions, are all taken from the load flow
saved case. Fault analyses may be made with the same level of system modeling as used in a load
flow study. Specifically, fault analyses may do the following:
• Recognize both reactance and resistance and include all actual shunt branches and
line charging in the three sequence networks.
• Recognize both the magnitude ratio and phase shift of all transformers, including the
inherent shift of delta-wye transformers if it is entered in the load flow data.
• Recognize the actual spread of internal voltage magnitude and phase angle of gener-
ators as initialized from a solved load flow case.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-1
Short-Circuit Fault Analysis PSS™E-31.0
Preparing Short Circuit Sequence Data Users Manual
The overriding principle of fault analysis data management in PSS™E is that the modeling detail
and component status information is dictated by the positive-sequence model. Negative- and zero-
sequence data values are held in the power flow file only where their values are different from the
corresponding positive-sequence values. In setting up the negative and zero-sequence networks,
PSS™E assumes the following:
1. All transmission branches (lines and transformers) have the same impedance,
charging, and line-connected shunt characteristics in the negative-sequence as in the
positive-sequence.
2. All transformers have phase shift in the negative-sequence equal and opposite to that
in the positive-sequence.
4. All constant MVA and constant current load specified in the positive-sequence data are
converted automatically to constant shunt admittance in the positive-sequence
network.
5. All loads are automatically represented by the same shunt admittance in the negative-
sequence as in the positive-sequence unless a different negative-sequence shunt
admittance is specified.
6. Loads are open circuits in the zero-sequence unless represented specifically by entry
of a value of shunt admittance.
7-2 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Preparing Short Circuit Sequence Data
Sequence data may be listed for examination and modified in a manner similar to that of standard
(positive sequence) power flow data. The sequence data appear together with the positive
sequence data in the spreadsheet view.
As for positive sequence data, the "raw" sequence data file is read in "free format" with data items
separated by a comma or one or more blanks. Each category of data except the change code is
terminated by a record specifying an "I" value of zero. Termination of all data is indicated by a value
of "Q".
The Sequence Data File contains 10 groups of records (see Figure 7-1) with each group specifying
a particular type of sequence data required for fault analysis work. Any piece of equipment for which
sequence data is to be entered must be represented as power flow data in the powerflow case. If
not, the data will not be accepted.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-3
Short-Circuit Fault Analysis PSS™E-31.0
Preparing Short Circuit Sequence Data Users Manual
IC = 0 Indicates the initial input of sequence data for the network contained in the
power flow case. All buses, generators, branches, and switched shunts for which
no data record is input in a given category of data have the default values
assigned for those data items.
IC = 1 Indicates change case input of sequence data for the network contained in the
power flow case. All buses, generators, branches, and switched shunts for which
no data record is input in a given category of data have those data items
unchanged. (Specifically, they are not set to the default values.)
The use of the change case mode for the appending sequence data is identical to its use in reading
the positive sequence power flow data; that is for the addition of equipment to the power flow case
(e.g., to add a zero sequence mutual coupling parameters). It is not valid to set IC to one for the
initial appending of sequence data. In such a situation, an appropriate message is printed and the
process continues its execution as if IC had been specified as zero.
I Bus number; bus I must be present in the working case as a generator bus.
ID One- or two-character machine identifier of the machine at bus I whose data is
specified by this record. ID = ’1’ by default.
ZRPOS Generator positive sequence resistance; entered in pu on machine base (i.e., on
MBASE base). No default is allowed.
ZXPOS Generator positive sequence reactance; entered in pu on machine base (i.e., on
MBASE base). No default is allowed.
During the initial input of sequence data (i.e., IC = 0 on the first data record), any machine for which
no data record of this category is entered has its positive sequence generator impedance, ZPOS
(i.e., ZRPOS + j ZXPOS), set equal to ZSORCE. This is the generator impedance which would be
entered into the power flow case for use in switching studies and dynamic simulation.
In subsequent appending of sequence data (i.e., IC = 1 on the first data record), any machine for
which no data record of this category is entered has its positive sequence generator impedance
unchanged. Note that the generator positive sequence impedance appended for fault analysis pur-
poses (ZPOS) is not necessarily the same as the generator impedance (ZSORCE) used in
dynamics, and that it does not overwrite ZSORCE. That is, the two different positive sequence
impedances reside in the power flow file simultaneously at different locations.
7-4 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Preparing Short Circuit Sequence Data
Positive sequence generator impedance data input is terminated with a record specifying a bus
number of zero.
I Bus number; bus I must be present in the working case as a generator bus.
ID One- or two-character machine identifier of the machine at bus I whose data is
specified by this record. ID = ’1’ by default.
ZRNEG Generator negative sequence resistance; entered in pu on machine base (i.e.,
on MBASE base). No default is allowed.
ZXNEG Generator negative sequence reactance; entered in pu on machine base (i.e.,
on MBASE base). No default is allowed.
During the initial input of sequence data (i.e., IC = 0 on the first data record), any machine for which
no data record of this category is entered has its negative sequence generator impedance, ZNEG
(i.e., ZRNEG + j ZXNEG), set equal to ZPOS, the positive sequence generator impedance.
In subsequent input of sequence data (i.e., IC = 1 on the first data record), any machine for which
no data record of this category is entered has its negative sequence generator impedance
unchanged.
Negative sequence generator impedance data input is terminated with a record specifying a bus
number of zero.
I Bus number; bus I must be present in the working case as a generator bus.
ID One- or two-character machine identifier of the machine at bus I whose data is
specified by this record. ID = ’1’ by default.
RZERO Generator zero sequence resistance; entered in pu on machine base (i.e., on
MBASE base). No default is allowed.
XZERO Generator zero sequence reactance; entered in pu on machine base (i.e., on
MBASE base). No default is allowed.
For those machines at which the step-up transformer is represented as part of the generator data
(i.e., XTRAN is nonzero), ZZERO (i.e., RZERO + j XZERO) is not used and, in the fault analysis
activities, the step-up transformer is assumed to be a delta wye transformer.
Any machine with a zero sequence impedance of zero is treated as an open circuit in the zero
sequence.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-5
Short-Circuit Fault Analysis PSS™E-31.0
Preparing Short Circuit Sequence Data Users Manual
During the initial input of sequence data (i.e., IC = 0 on the first data record), any machine for which
no data record of this category is entered has its zero sequence generator impedance, ZZERO, set
equal to ZPOS, the positive sequence generator impedance.
In subsequent input of sequence data RESQ (i.e., IC = 1 on the first data record), any machine for
which no data record of this category is entered has its zero sequence generator impedance
unchanged.
Zero sequence generator impedance data input is terminated with a record specifying a bus number
of zero.
I, GNEG, BNEG
where:
For any bus where no such data record is specified, or GNEG and BNEG are both specified as zero,
the load and shunt elements are assumed to be equal in the positive and negative sequence
networks.
The user is advised to exercise caution in applying exceptional negative sequence shunt loads. It
is the user’s responsibility to ensure that the positive sequence loading and shunt data, as con-
tained in the power flow case, is coordinated with the specified negative sequence shunt load.
Negative sequence shunt load data input is terminated with a record specifying a bus number of
zero.
I, GZERO, BZERO
where:
7-6 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Preparing Short Circuit Sequence Data
For any bus where no such data record is specified, no shunt load component is represented in the
zero sequence. The zero sequence ground tie created by a grounded transformer winding is
automatically added to whatever zero sequence shunt load is specified at the bus when the trans-
former winding connection code data for the transformer is specified (see Section 7.2.9).
Zero sequence shunt load data input is terminated with a record specifying a bus number of zero.
The zero sequence network is assumed to be a topological subset of the positive sequence net-
work. That is, it may have a branch in every location where the positive sequence network has a
branch, and may not have a branch where the positive sequence network does not have a branch.
The zero sequence network does not need to have a branch in every location where the positive
sequence network has a branch.
A branch treated as a zero impedance line in the positive sequence is treated in the same manner
in the zero sequence, regardless of its specified zero sequence impedance.
During the initial input of sequence data (i.e., IC = 0 on the first data record), any branch for which
no data record of this category is entered is treated as open in the zero sequence network
(i.e., the zero sequence impedance is set to zero). In subsequent input of sequence data
(i.e., IC = 1 on the first data record), any branch for which no data record of this category is entered
has its zero sequence branch data unchanged.
Zero sequence branch data input is terminated with a record specifying a "from bus" number of
zero.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-7
Short-Circuit Fault Analysis PSS™E-31.0
Preparing Short Circuit Sequence Data Users Manual
1. The maximum number of zero sequence mutual couplings that may be entered at the
standard size levels of PSS™E is given in Table 1-1 of Chapter 1.
2. The polarity of a mutual coupling is determined by the ordering of the bus numbers
(I,J,K,L) in the data record. The "dot" convention applies, with the "from buses" (I and
K) specifying the two "dot" ends of the coupled branches.
3. RM+jXM specifies the circuit-to-circuit mutual impedance, given the polarity implied by
I and K.
4. The geographical "B" factors are required only if one or both of the two mutually cou-
pled lines is to be involved in an unbalance part way down the line, and only part of the
length of one or both of the lines is involved in the coupling.
5. The values of the "B" factors must be between zero and one inclusive; they define the
portion of the line involved in the coupling.
7-8 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Preparing Short Circuit Sequence Data
6. BIJ1 must be less than BIJ2, and BKL1 must be less than BKL2.
7. Mutuals involving transformers or zero impedance lines are ignored by the fault anal-
ysis solution activities.
Figure 7-2 schematically illustrates a mutual coupling with BIJ1 = 0.0, BIJ2 = 0.4, BKL1 = 0.0 and
BKL2 = 1.0 (the first 40% of the first line coupled with the entire second line).
As a second example, BIJ1 = 0.6, BIJ2 = 1.0, BKL1 = 0.0 and BKL2 = 0.6 (last 40% of the first line
coupled with the first 60% of the second line) might be depicted as follows in Figure 7-3.
Zero sequence mutual impedance data input is terminated with a record specifying a "from bus"
number of zero.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-9
Short-Circuit Fault Analysis PSS™E-31.0
Preparing Short Circuit Sequence Data Users Manual
7-10 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Preparing Short Circuit Sequence Data
In specifying zero sequence impedances for three-winding transformers, note that winding imped-
ances are required, and that the zero sequence impedances default to the positive sequence
winding impedances. Recall that, in specifying positive sequence data for three-winding trans-
formers, measured impedances between pairs of buses to which the transformer is connected, not
winding impedances, are required. PSS™E converts the measured bus-to-bus impedances to
winding impedances which are subsequently used in building the network matrices.
Specification of the transformer connection code along with the impedances entered here enables
the fault analysis activities to correctly model the zero sequence transformer connections, including
the ground ties and open series branch created by certain grounded transformer windings. If no
connection code is entered for a transformer, all windings are assumed to be open. Zero sequence
transformer default data is such that the transformer appears as an open circuit in the zero
sequence network. Therefore, zero sequence data must be entered for all grounded transformers.
Connection codes do not indicate the inherent phase shift due to the relative connection of delta
and wye windings. This phase shift is specified in the positive sequence power flow data.
Zero sequence transformer data input is terminated with a record specifying a "from bus" number
of zero.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-11
Short-Circuit Fault Analysis PSS™E-31.0
Preparing Short Circuit Sequence Data Users Manual
Winding 1 Winding 2
ti – q + tj
Zt
Winding 1 Winding 2
ti Z0
t
tj
1
ti Z0
t
2
3.*Zg
Z0t tj
3
3.*Zg
7-12 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Preparing Short Circuit Sequence Data
Winding 1 Winding 2
ti Z 0t tj
5
3.*Z g
ti
6
Z 0t Zg
tj
7
Zg Zt
ti Z0t tj
Zg Z g2
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-13
Short-Circuit Fault Analysis PSS™E-31.0
Preparing Short Circuit Sequence Data Users Manual
First-Winding Second-Winding
t1 – q1 t2 – q2
+ +
Z1 Z2
+
Z3
t3 – q3
Third-Winding
a. Positive Sequence
where:
+
Z 10 = Z 1 + 3Z 1 – G
t1 t2 +
Z 20 = Z 2 + 3Z 2 – G
+
Z 30 = Z 3 + 3Z 3 – G
3Zg +
Z 10 = Z 1
t3 +
Z 20 = Z 2
+
Z 30 = Z 3
Zg = 0
7-14 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Preparing Short Circuit Sequence Data
t1 t2
Z 10 Z 20
Z 30
3Zg
Z 30 = ∞
Zg = ∞
t2
Z 10 Z 20
Z 30
+
Z 20 = Z 2 + 3Z g
Zg = 0
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-15
Short-Circuit Fault Analysis PSS™E-31.0
Preparing Short Circuit Sequence Data Users Manual
Z 10 Z 20
Z 30
t1 t2
Z 10 Z 20
Z 30 3Zg
t3
7-16 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Preparing Short Circuit Sequence Data
The winding type codes do not distinguish between an ungrounded wye-winding and a delta-
winding. This distinction is conveyed by the specification of transformer phase shift in the positive-
sequence data. A delta-wye transformer, has an inherent 30° phase shift, which must be specified
as a positive-sequence phase shift of either +30 or –30° in the load flow data if the behavior of the
delta-wye transformer is to be represented completely. If the 30° phase shift is not specified, it is
implied that the transformer is either wye-wye or delta-delta connected.
The significance of transformer phase shift, and the effect of ignoring it, is illustrated by Figures 7-
6 and 7-7. Consider the radially connected wye-delta transformer as shown in Figure 7-6. It is rep-
resented as a two-winding transformer with a connection code of 2. The remaining details are
specified via the phase-shift and impedance values. The correct representation is as shown in
Figure 7-6, with a 30° phase shift in the turns-ratio of the positive-sequence model. An incorrect,
but often used representation, would be to ignore the phase shift, also shown in Figure 7-6.
The fault analysis results, for a single phase-to-ground fault on the wye-connected winding, are
shown in Figure 7-7a. The correct result obtained when transformer phase shift is represented
properly are shown in Figure 7-7b.
I 0 = I 1 = I 2 = If ⁄ 3
The sequence currents flowing in the leads to the delta-winding are given by
I0 = 0
I 1 = If ÷ 3 at 30°
I 2 = If ÷ 3 at -30°
The phase currents corresponding to these delta-winding sequence currents are shown in the fol-
lowing figure. One leg of the delta connection carries a current of If ÷ 3 , which flows in two of the
leads on this side of the transformer. This data is correct with respect to magnitude and phase of
the sequence currents, and to magnitude and phase of the transformer phase currents.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-17
Short-Circuit Fault Analysis PSS™E-31.0
Preparing Short Circuit Sequence Data Users Manual
System
L-G
Fault
I ∠30:1
System
Z
t
Winding Winding
Type 1 Type 2
I ∠0:1
System
Zt
Figure 7-7b shows the results obtained when the phase shift of the transformer is ignored. The
sequence and phase currents on the fault side of the transformer are identical in amplitude to those
calculated with phase shift present. (They are all shifted in phase by 30°, however.) The sequence
and phase currents calculated for the delta-connected winding in the absence of transformer phase
shift are significantly different from those shown in Figure 7-7a.
While Figure 7-7a shows correct results with the positive- and negative-sequence leading and lag-
ging the fault current by 30°, respectively, the results shown in Figure 7-7b have positive- and
negative-sequence current in phase with the fault current. The lead currents corresponding to these
sequence currents are as shown, with a current 2If ÷ 3 in one phase and currents of If ÷ 3 in the
other two. The corresponding currents in the delta-connected transformer windings are inconsistent
with the currents in the wye-connected winding.
7-18 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Preparing Short Circuit Sequence Data
I0 = 0
If
I 1 = --- ∠30
3
If If
I 0 = I 1 = I 2 = --- I 2 = --- ∠– 30
3 3
a
If
A -------
3
If System
If If ------- b
3
c
If B
C If
-------
3
a. 30° Phase Shift Wye-Delta
I0 = 0
If
I 0 = I 1 = I 2 = --- If
3 I 1 = I 2 = ---
3
A
a
2I f
If -------
--- 3
If 3
If System
---
If 3 b
If
---
If B 3
C
c
If
---
3
Figure 7-7. Effect of Including and Neglecting 30° Phase Shift in Transformer
with One Grounded and One Ungrounded Winding
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-19
Short-Circuit Fault Analysis PSS™E-31.0
Preparing Short Circuit Sequence Data Users Manual
It is evident, then, that neglect of the inherent 30° phase shift of wye-delta transformers results in
the following:
• Calculated sequence and phase currents that are correct in all branches on the fault
side of the transformer.
• Calculated sequence currents that are correct in amplitude but erroneous in phase in
all branches that are removed from the fault by a transformer.
• Erroneous values of phase current in all branches separated from the fault by a wye-
delta transformer.
ZSORCE should always be set to the value, normally the subtransient impedance, Z ′′, required for
representation of the generator in dynamic simulations. ZPOS may be set equal to ZSORCE or any
other value, such as the transient impedance, Z ′, which may represent the generator in fault anal-
ysis studies. While the ZSORCE values assigned to the generators may be a mixture of
subtransient and transient values, depending upon the modeling levels chosen for the individual
generators, the ZPOS values should be consistently transient or subtransient values for all gener-
ators. The use of subtransient impedances as the values of ZPOS for all generators leads to fault
calculations giving the conditions at an instant immediately after the unbalancing event. The use of
transient values results in fault calculations giving conditions a short time, say 0.1 seconds, after
the event when the subtransient components of the generator flux transients have died out and the
generator can be regarded as a voltage source behind transient impedance.
7-20 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Preparing Short Circuit Sequence Data
Generators are modeled in the negative-sequence by the impedance, ZNEG, connected in series
with the generator transformer reactance, ZTRAN, and thence to ground. The normal value for
ZNEG is the subtransient impedance of the generator, regardless of the choice of values for
ZSORCE and ZPOS. The generator zero-sequence model is the impedance, ZZERO, connected
to ground. ZZERO should be assigned the value (3Rg + jXo), where:
Rg = the generator grounding resistance in per unit with respect to generator base
voltage and generator base, MVA.
Xo = the generator zero-sequence impedance, per unit, with respect to generator
base, MVA.
When the generator step-up transformer is modeled as a part of the generator it is always treated
as a two-winding unit:
The unbalanced solutions of PSS™E calculate and display generator conditions only at the bus to
which the generator is connected. Hence, inclusion of the step-up transformer precludes display of
generator terminal conditions in the fault analysis results; all generator currents shown in fault
analysis reports are as observed at the bus-side of the step-up transformer. Generator unbalanced
terminal conditions can be observed only when the step-up transformer is represented as a trans-
mission system branch, the generator zero-sequence impedance is specified, and the generator
terminals are a bus in the system model.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-21
Short-Circuit Fault Analysis PSS™E-31.0
Preparing Short Circuit Sequence Data Users Manual
1:GTAP
~ ~
ZSORCE ZTRAN ZSORCE
or or
ZPOS ZPOS
1:GTAP
ZTRAN ZNEG
ZNEG
1:GTAP
ZZERO
ZZERO ZTRAN
7-22 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Preparing Short Circuit Sequence Data
I Bus number; bus I must be present in the working case with positive sequence
switched shunt data.
BZi Zero sequence admittance increment for each of the steps in block i; entered in
pu. BZi = 0.0 by default.
Data specified on zero sequence switched shunt data records must be coordinated with the corre-
sponding positive sequence data. The number of blocks and the number of steps in each block are
taken from the positive sequence data.
The input process will alarm any block for which any of the following applies:
• The positive sequence admittance is positive and the zero sequence admittance is
negative.
• The positive sequence admittance is negative and the zero sequence admittance is
positive.
• The positive sequence admittance is zero and the zero sequence admittance is
nonzero.
The zero sequence admittance switched on at a bus is determined from the bus’ positive sequence
value, with the same number of blocks and steps in each block switched on.
Zero sequence switched shunt data input is terminated with a record specifying a bus number of
zero.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-23
Short-Circuit Fault Analysis PSS™E-31.0
Appending Sequence Data to the Power Flow Case Users Manual
To append the sequence data to the power flow case, the File>Open option is selected. This, in
turn, will open the file dialog where files of the type *.seq can be accessed (see Figure 7-9).
Selecting and opening the file will initiate appending the data. Progress in importing of each data
category will show in the Output Bar (see Figure 7-10).
7-24 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Appending Sequence Data to the Power Flow Case
If the change code parameter IC in the first record of the Sequence Data File is set to one and
sequence data had not previously been read for the system in the working case, an alarm is printed
and the data is processed as if IC was set to zero. Remember that a code of zero indicates that the
data is being appended for the first time.
As for positive sequence data, the "raw" sequence data file is read in "free format" with data items
separated by a comma or one or more blanks. Each category of data except the change code is
terminated by a record specifying an "I" value of zero. Specifying a data record with a "Q" in column
one is used to indicate that no more data records are to be supplied.
In Section 1.6.4 the run-time "Options" were described. One of the options available to the user is
to enable warnings to be issued when there are "apparent" problems with the sequence data being
appended to the power flow case. When the fault analysis warning option is enabled, the following
tabulations are produced:
1. When IC is zero, a listing of all online machines at type two and three buses for which
no negative sequence generator impedance is entered. The negative sequence gen-
erator impedance, ZNEG, is set to the positive sequence value, ZPOS.
2. When IC is zero, a listing of all online machines at type two and three buses for which
no zero sequence generator impedance is entered. The zero sequence generator
impedance, ZZERO, is set to the positive sequence value, ZPOS.
Each of these tabulations may be individually suppressed by entering the AB interrupt control code.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-25
Short-Circuit Fault Analysis PSS™E-31.0
Appending Sequence Data to the Power Flow Case Users Manual
Figure 7-11. Machine Sequence Data from Power Flow Case savnw.sav
Section 2.4 describes the means by which the data in the spreadsheet can be edited, filtered,
sorted, exported and otherwise manipulated. Those functions apply equally to the sequence data.
Data can be changed or additional data can be imported by using the File>Open option to open a
subsequent Sequence Data file with a change case mode (IC = 1). All buses, generators, branches,
and switched shunts for which no data record is input in a given category of data have those data
items unchanged. (Specifically, they are not set to the default values.)
Selecting the Power Flow>List data option will open the List Data dialog (see Figure 7-12). There
it can be seen that the user can simply list all data; select by category and select by subsystems.
The output listing can be directed to a file or to a Report tab.
7-26 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Appending Sequence Data to the Power Flow Case
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-27
Short-Circuit Fault Analysis PSS™E-31.0
Fault Calculation Modeling Assumptions Users Manual
• Recognize both reactance and resistance and include all actual shunt branches and
line charging in the three sequence networks.
• Recognize both the magnitude ratio and phase shift of all transformers, including the
inherent shift of delta-wye transformers if it is entered in the load flow data.
• Recognize the actual spread of internal voltage magnitude and phase angle of gener-
ators as initialized from a solved load flow case.
• Recognize loads by converting them to equivalent constant shunt admittance.
The level of system modeling detail used in a fault analysis calculation is controlled by manipulating
the positive-sequence (or load flow) data in the working file into the required form before com-
mencing fault analysis work. The detailed, unbalanced fault analyses activities, described in
Section 7.5, usually operate on the assumption that the system is modeled in the highest level of
detail. In these activities, although results corresponding to a simplified modeling basis are obtained
if appropriate elements of data have null values, simplified calculating algorithms are not used.
Therefore, no computing time advantage is gained by simplifying the system model. One advantage
to simplifying the model, as described in Section 7.4.3 is to allow comparison of PSS™E results
with those obtained from other software packages which usually use a more simple or "classical"
model.
7.4.1.1 Detailed Fault Calculation Models for DC Lines and FACTS Devices
If any unblocked DC lines or in-service FACTS devices are present in the working case, the user
can specify their treatment in the fault analysis solution. The options are to:
• Block the device: Lines and FACTS devices are treated as open circuits (i.e., fully
blocked bridges) in all three sequences, regardless of their actual prefault loadings as
given by the initial condition load flow.
• Represent as load: the apparent AC system complex loads are converted to positive
sequence constant admittance load at the buses at which these quantities are injected
into the AC system during normal power flow work. In the negative and zero sequence
networks, DC lines and series FACTS devices are represented as open circuits. The
equivalent positive-sequence shunt admittance is derived from the values of PAC and
QAC given by the initial condition load flow at each converter AC bus.
Neither of these two representations should be regarded as exact. The first may be regarded as
reasonable for the calculation of fault-current duty on circuit breakers since converter controls are
usually designed to limit their fault currents to values equal to or less than normal load current.
Only one of these options may be selected in any execution of the unbalanced network solutions.
The selected option applies to all DC lines and FACTS devices in the working case. The default
handling of these devices is to block.
7-28 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Fault Calculation Modeling Assumptions
Use of the simplified model is more usually applicable in the automatic sequencing calculations
described in Section 7.8, where the model is referred to as one using "Flat conditions", although
those calculations can use the prefault network condition are as specified in the power flow case
when the calculations are initiated.
For the automatic sequencing calculations, similar simplifications can be made to the model but the
decision for the user can be made during initiation of the calculations.
All of these modelling options are accessible via the Fault>Setup for special fault calculations
(FLAT) option. Figure 7-13 shows the menu, the Setup for Special Fault Calculations dialog and
the three special options available.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-29
Short-Circuit Fault Analysis PSS™E-31.0
Fault Calculation Modeling Assumptions Users Manual
1. All bus voltages are set to one per unit at zero phase angle modified as described in
Section.
5. Transformer phase shift angles are set to zero. Any transformer impedance, which is a
function of phase shift angle is set to its nominal value.
7-30 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Fault Calculation Modeling Assumptions
6. Optionally, all transformer turns ratios are set to one. This includes generator step-up
transformers, which are modeled as part of the machine representation (i.e., the
GENTAP). Any transformer impedance, which is a function of turns ratio, is set to its
nominal value.
1. Voltage magnitudes are either left at their present values or are all set to a specified
magnitude; phase angles are all set to zero.
3. Any machine whose active power is zero or negative has its active and reactive power
outputs set to zero. All machines whose active power outputs are positive have their
reactive power outputs either left unchanged or set such that a specified power factor
is maintained.
5. Transformer phase shift angles are set to zero. Any transformer impedance, which is a
function of phase shift angle, is set to its nominal value.
6. Optionally, all transformer turns ratios are set to one. This includes generator step-up
transformers, which are modeled as part of the machine representation (i.e., the
GENTAP). Any transformer impedance, which is a function of turns ratio, is set to its
nominal value.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-31
Short-Circuit Fault Analysis PSS™E-31.0
About Detailed Unbalanced Fault Types Users Manual
9. Optionally select a voltage magnitude or leave voltages as in the power flow case.
10. Optionally select a generator power factor or leave generator Mvar unchanged.
When this IEC setup is selected activity, short circuit currents in conformance with IEC standard
909 can be calculated for examination of circuit-breaker duties (see Section 7.9).
7-32 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual About Detailed Unbalanced Fault Types
single-line-to-ground fault and the "second" double-line-to-ground fault with all fault impedances set
to 0.0+j0.0. Figure 7-16 shows the fault combinations together with the impedances available for
selection. It shows how a double-line-to-ground fault can be converted to a line-to-line fault by
assuming an "infinite" impedance for the impedance to ground ZG.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-33
Short-Circuit Fault Analysis PSS™E-31.0
About Detailed Unbalanced Fault Types Users Manual
It should be noted that phase impedances will be placed in parallel with any branch which already
exists, in the power flow case, between the selected buses. If the user wishes to use these models
to represent an unbalance in an existing branch, then that branch must be switched out of services
to avoid duplication (see Section 7.6.1.4).
The simulation of a fault at any point on a line is designated as the "fault slider". The line may be
represented with both ends closed or with one end opened. In either of these two topologies, one
of the following may be applied at any point along the line:
3. A three phase fault utilizing both the second L-G fault and the second L-L-G fault.
The dummy bus, introduced at the fault point is automatically numbered 999999. If one end of the
faulted line is opened and the fault point is not at the line end position, a second dummy bus, num-
bered 999998, is introduced at the opened end (see Figure 7-18).
7-34 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Performing Fault Analysis in PSS™E
The dialog is divided into three main areas. The first is a series of tabs; one for each type of unbal-
ance. Selection of a tab will open the appropriate data selection menus for the type of fault selected
and provide a Select check box for the user to confirm selection of the unbalance.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-35
Short-Circuit Fault Analysis PSS™E-31.0
Performing Fault Analysis in PSS™E Users Manual
Legend
Indicates unbalances selected and
The second area is at the right hand end of the dialog where the status of selections is shown. This
enables the user to see which unbalances have been selected, which have been disabled by pre-
vious selections and which selections remain available.
The third area, in the lower let of the dialog (see Figure 7-21), facilitates the selection of treatment
for DC lines and FACTS devices and of the transformer impedance correction in the zero sequence
(see Section 7.4.1.1).
The first selection (a) is a line-to-ground fault on Bus 153. The fault impedance is 0.0 + j0.0 pu of
base impedance. The faulted phase has been selected to be the "B" phase.
The second selection (b) is a line-to-line-ground fault on Bus 154. The impedance between phases
and to ground are both 0.0 + j0.0. Note that, in this case the phase selected is the one excluded
from the fault. Consequently, the fault is between phases "C" and "B".
The third selection shown (c) is for a three phase fault on Bus 205. This is modelled by applying the
second line-to-ground and the second line-to-line-to-ground fault on Bus 205. Further, the assump-
tion is that the fault impedance is zero.
Note that the fault selected could be a line-to-line-to-ground or a three-phase fault type.
To utilize the line faults, the number of buses in the working case must be at least one less (two less
for an in-line fault with one end opened) than the maximum number for which PSS™E is dimen-
sioned. In addition, except for the case of a line end fault at the opened end of a line, the following
conditions must be met:
• The number of branches in the working case must be less than the maximum number
for which PSS™E is dimensioned.
• The geographical "B" factors, BIJ1, BIJ2, BKL1, and BKL2, must have been properly
specified for any zero sequence mutual couplings involving the branch (see
Section 7.2.8).
Only one line fault may be imposed on the network in any given execution of the unbalanced fault
calculation, but other bus faults and the phase closed unbalances may be simultaneously applied.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-37
Short-Circuit Fault Analysis PSS™E-31.0
Performing Fault Analysis in PSS™E Users Manual
For this in-line slider fault, with both ends closed, the faulted line may not be a transformer, and it
may not be open in the zero sequence (i.e., its zero sequence impedance must be nonzero).
In output reports, the faulted dummy bus is listed as bus 999999 with the name "DUMMYBUS". For
the one end opened case, the base voltage of the dummy bus is taken to be the same as the
opened end bus. For the case of both ends closed, the base voltage of the dummy bus will be that
of one of the two buses involved.
7-38 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Performing Fault Analysis in PSS™E
With one end of the branch opened, the user designates the opened end and, except for a three-
winding transformer, the fault location on the "branch". For a non-transformer branch, the fault loca-
tion is specified by specifying the fraction of the line between the closed end and the fault point, as
for the "slider". The proper designation is a number greater than zero and less than or equal to one
(one would indicate a "line end" fault). For a two-winding transformer, the value of one must be
specified. For a three-winding transformer, the user can select the open point at any of the three
buses to which the transformer is connected.
In the case of one end opened with the fault location other than at the opened end, the opened end
dummy bus is listed as bus 999998 with the name "STUB END" and the base voltage of the original
bus at the opened end of the line.
Figure 7-24 shows the appearance of the unbalance dialog for the selection of a single-line-to-
ground fault, on Phase A, at the open 500 kV bus of a three-winding transformer. The fault imped-
ance is 0.0 + j0.0 pu.
Note that the fault type can be a line-to-ground, a line-to-line-to ground or a 3-phase fault.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-39
Short-Circuit Fault Analysis PSS™E-31.0
Performing Fault Analysis in PSS™E Users Manual
Figure 7-24. Selection of a L-G Fault on the 500 kV Bus Side of a Three-
Winding Transformer
Following the unbalance specification process, a warning message is printed if there are already
any in-service branches between the designated buses. In this case the new series branch, of
which only one or two phases are closed, is placed in parallel with those branches that are already
present. It is the user’s responsibility to ensure that the working case is in a state such that the appli-
cation of the phase closed unbalance produces the desired overall condition.
If it is intended to open one or two phases of a branch which already exists, that branch must be
taken out of service in order to be replaced by the unbalance model.
Figure 7-25 shows the appearance of the dialog for selection of a two-phases closed branch
between Bus 152 and Bus 153. The two phases closed are "B" and "C" and the phase impedance
is equal to - 0.02 pu; indicating series capacitance.
Note that the dialog for single-phase closed looks the same. The difference being that the user
would identify the closed Phase rather than the open Phase.
7-40 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Performing Fault Analysis in PSS™E
2. Append the required sequence data to the power flow case (Section 7.2).
When the calculation is initiated, the first step in the process is the setting up of the sequence net-
works. This involves the preparation of the power flow case for the unbalanced network solution (as
well as for the Separate Pole Circuit Breaker simulation discussed in Section 7.11.1)
This process involves taking the positive sequence network (i.e., the power flow case) and the var-
ious sequence data arrays defining the negative and zero sequence networks, and setting up the
factored matrix working file (FMWORK) and the short circuit working file (SCWORK) in the neces-
sary form. The following computations are performed:
• All positive sequence loads are converted to fixed shunt admittances on the basis of
the voltage at each load bus in the working case.
• All negative sequence loads, except those for which the user has specified a nonzero
negative sequence shunt load are set equal to the positive sequence values calculated
in the previous step.
• All generator positive sequence sources are initialized and fixed to correspond to their
generator terminal bus conditions in the working case. This is a temporary "conversion"
of the power flow generator model to a Norton equivalent for the fault calculations (see
Figure 7-26).
• An ordering for the positive and negative sequence networks is determined and
summarized in the Output Bar or alternative device selected by the user (see Figure 7-
27).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-41
Short-Circuit Fault Analysis PSS™E-31.0
Performing Fault Analysis in PSS™E Users Manual
• The positive and negative sequence admittance matrices are constructed and
factorized.
• The zero sequence network is ordered and summarized in the Output Bar or alternative
device selected by the user (see Figure 7-27).
• The zero sequence network admittance matrix is constructed and factorized.
ZSORCE or ZPOS
Z tran
Positive Sequence
1:GTAP
P+ jQ t:1 t ∠-θ:1
~
E source
Z neg
Negative Sequence
Z tran
1:GTAP
t ∠-θ:1
1:GTAP
Unbalanced Fault
Load Flow Setup
Augment Positive Sequence model Analysis Setup
and Append Sequence Data
7-42 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Performing Fault Analysis in PSS™E
With respect to the summary shown in Figure 7-27, it is quite common, and perfectly valid, to have
the generator terminal bus isolated in the zero sequence network. This is, in fact, the usual case
since the majority of generator step-up transformers are delta connected on the generator side and
wye connected on the high side. This is the assumption inherent in the generator modeling when
the step-up transformer is represented as part of the generator data (i.e., XTRAN is nonzero). An
alarm message will be printed for any generator with nonzero values of both XTRAN and ZZERO.
In this case, the value of only XTRAN is used in setting up the zero sequence ground tie at the type
two (high side) bus.
An example is shown in Figure 7-28 for a case in which two line-to-ground faults were applied in
the savnw.sav power flow case, with a zero fault impedance, on Buses 151 and 3002.
The calculation process interconnects the three sequence networks to represent the unbalanced
condition and solves for the sequence voltages. Following solution, a summary report is printed for
each unbalance applied. The user is then given the opportunity to get complete output for any bus
in the working case.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-43
Short-Circuit Fault Analysis PSS™E-31.0
Performing Fault Analysis in PSS™E Users Manual
The summary report is printed at the selected output device for each unbalance that is in effect.
Each individual unbalance report consists of a tabulation of bus voltages and branch currents in
terms of both symmetrical component (sequence) and phase quantities. Voltages and currents are
printed in either physical units (kV L-G and amps) or per unit, and in either rectangular or polar coor-
dinates, according to the fault analysis output options currently in effect (refer to Section 1.6.4). If
the physical units option is enabled and a bus has no base voltage specified for it, its output is
printed in per unit.
2. Bus voltages for the bus at which the unbalance is applied. The first line of each bus
voltage block gives the bus zero, positive and negative sequence voltages as well as
three times the zero sequence voltage, and the second line gives the bus phase volt-
ages. When the per unit option is enabled, values are in per unit of rated line to ground
voltage. The phase voltages are line to neutral values. For the phase closed unbal-
ances, the bus voltage block is printed for both of the buses involved.
3. For the L-G and L-L-G faults, series branch currents flowing in each branch (including
any generator contributions) connected to the faulted node. All currents are tabulated
as flowing into the faulted node and include the effects of line charging capacitance and
line connected shunt admittances. When the per unit option is enabled, currents are
expressed in per unit of base phase current. The first line gives sequence components
of current as well as three times the zero sequence current, and the second line gives
the phase currents. For non transformer branches and for two-winding transformers,
the number and name of the "to bus" is printed, along with the circuit identifier; for
three-winding transformers, the output line contains the winding number, the trans-
former circuit identifier and the transformer name. For the phase closed unbalances,
the only branch series currents tabulated are those represented by the unbalance.
4. For the L-G and L-L-G faults, the algebraic "sum of contributions" of all elements tabu-
lated in (3). The format of these currents is the same as for the series branch currents.
This is the total current apparently flowing to ground at the bus, and it includes any load
connected to the bus, fault current, and the AC side current of any unblocked DC line
or FACTS device.
5. For the L-G and L-L-G faults, a value of "contributions equivalent positive sequence
admittance" is expressed in per unit, rectangular form, relative to system base values.
This quantity is computed from the sum of contributions in (4) and thus includes any
load and unblocked DC line and FACTS device elements connected to the bus. Fur-
thermore, this equivalent admittance is valid only in the case of single ground faults. In
the case where there are no DC line or FACTS device effects included in this admit-
tance, and only this single unbalance was applied, this shunt admittance, multiplied by
system base MVA, may be entered as a shunt replacing the load and shunt elements
at the bus, to give the correct positive sequence equivalent representation of this fault
in the dynamic simulation activities.
6. For the L-G and L-L-G faults, the current flowing to ground at the bus exclusive of any
fault current. The format of these currents is the same as in (3) and (4) above, and they
include any load and shunt current at the bus as well as the AC side current of any
unblocked DC line or FACTS device. In the zero sequence, only the shunt load is
output here; specifically, the zero sequence ground ties created by grounded trans-
7-44 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Performing Fault Analysis in PSS™E
former windings are not shown here but are included in the branch contribution output
of (3) above. Load and shunt current output is suppressed if the three sequence shunt
and load admittances are all zero.
7. For the L-G and L-L-G faults, when no phase closed unbalances are applied and only
one bus is involved in the ground faults, "fault current" is calculated and tabulated in a
format similar to (4) above, and "positive sequence equivalent fault admittance" is listed
in a format similar to (5) above. This admittance, multiplied by system base MVA, would
be added to any shunt at the bus to represent this fault in the dynamic simulation
activities.
Whenever a single ground fault unbalance is solved an entry is appended to a summary file, named
"SMRYSC", in the user’s directory. This file contains fault descriptive information along with the
"sum of contributions" entry described in (4) above. This file is cumulative, and if it does not exist it
is created automatically when the unbalanced fault calculations are performed. It is never automat-
ically deleted; results are always appends to it. The user may delete this file at any time when it is
no longer of use.
Figure 7-29 shows the summary report for a single-line-to-ground fault at Bus 151 in the savnw.sav
power flow case, with zero fault impedance.
Note that the output options are polar coordinates and physical quantities; i.e., the voltages are in
kV and the current is in amperes.
Since there is a 600 Mvar shunt connected to bus 151, the "Total Contributions" include the current
in this shunt.
The total A Phase current is 8371.6 / -67.76 amps. The zero sequence current is 2756.0 /-67.73
amps, These include contributions from the 600 MVAr shunt.
Since the A Phase current in the 600 Mvar shunt is 103.7 /- 69.48, the actual A Phase fault current
at the bus is less and is 8267.9 /-67.73 amps.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-45
Short-Circuit Fault Analysis PSS™E-31.0
Performing Fault Analysis in PSS™E Users Manual
Figure 7-29. Summary Output at Bus 151 with L-G Faults at Buses 151 in Power Flow Case savnw.sav
Sum of Contributions without the 600 Mvar Shunt
600 Mvar Shunt at bus 151
7-46 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Performing Fault Analysis in PSS™E
For that same fault condition, conditions at other buses in the system can be reported. This is
achieved using the Solution Output tab in the unbalance dialog as shown in Figure 7-20. That tab
provides access to selection of buses for which reporting is required and, further, allows the selec-
tion of output to be in terms of current, apparent impedances or apparent admittances of the
branches (see Figure 7-30).
This reporting facility recognizes the same fault analysis output options, with quantities printed in
either physical units or per unit, and in either rectangular or polar coordinates as does the summary
report.
The data printed for any selected bus or buses has the same format as for the summary report and
consists of:
2. Series branch quantity for each branch and machine connected to the bus, consisting
of either:
a. Branch series currents leaving the bus, in either per unit or amps. These are in the
reverse direction of the currents shown in the summary report.
b. Branch apparent impedances looking down each branch from the bus, expressed
in either per unit or ohms. These apparent impedances are defined as:
V seq i V phase i
Z seq ij = --------------- Z phase ij = ---------------------
I seq ij I phase ij
c. where the sequence and phase currents are the total currents flowing into the line
at the bus, including line charging capacitance and line connected shunt current.
Infinite impedance is printed as 9999 per unit or 999999 ohms.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-47
Short-Circuit Fault Analysis PSS™E-31.0
Performing Fault Analysis in PSS™E Users Manual
d. Branch apparent admittances looking down each branch from the bus, expressed
in either per unit or mmhos. Apparent admittances are defined as the reciprocal of
apparent impedances. Infinite admittance is printed as 9999 per unit or
99999 mmhos.
3. Sum of branch contributions. When branch currents are being tabulated, the sum of all
contributions flowing into the bus is the total current apparently flowing to ground at the
bus and will be zero unless there is a load or a shunt connected (see Section 7.6.3).
4. When branch currents are being tabulated, the sum of load and shunt current at the
bus. Load and shunt current output is suppressed if the three sequence shunt and load
contributions are all zero.
Note that the direction of current flow in the series branch output is the reverse of that in the sum-
mary output. Rather, it follows the power flow output convention of current leaving the bus.
When output is directed to the user’s terminal, a summary description of each active unbalance is
printed at the top of the first page of output. Otherwise, the unbalance summary is printed on each
page of output.
Production of the detailed report may be terminated by entering the AB interrupt control code.
The dialog for launching the calculation is shown in Figure 7-31b. The selections include the option
to select either a three-phase or single-phase fault, the option to output Phase A current or three
times zero sequence current and the ability to select a single bus to be faulted or all the buses.
The solution options are similar to the detailed unbalance calculation method.
7-48 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Performing Fault Analysis in PSS™E
(a.)
(b.)
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-49
Short-Circuit Fault Analysis PSS™E-31.0
Performing Fault Analysis in PSS™E Users Manual
Note that, in this figure, Bus 151 has been selected for calculation of a single-line-to-ground fault
with output of Phase A current. The coordinate (rectangular or polar) output will be as selected in
the run time options as for the detailed unbalance analysis.
The graphical output shows the results of applying a single-line-to-ground fault on Bus 151 (see
Figure 7-32). Output was selected to be in polar coordinates for Phase A.
An examination of the figure will demonstrate that the results are equal to those tabulated in
Figure 7-29 where polar coordinates were selected. The diagram shows more clearly, however, the
bus connected shunt contribution and the total fault current (at the bottom of the bus) without the
shunt contribution, i.e. in the diagram they are recolonized separately.
As an extension of this example, the calculation was run for a fault at all buses. The results for the
fault on Bus 152 can be seen. While the results are shown simultaneously, the faults are not simul-
taneous. The results are independent.
7-50 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Performing Fault Analysis in PSS™E
positive sequence parameters of every system component. This data may be introduced into the
working case at any time and, once introduced, it is saved and retrieved.
Each fault calculation is a complete solution for the full sequence and phase specification of condi-
tions at every bus. The user may obtain output of voltage at any bus, or current, apparent
impedance or apparent admittance at the entry to any branch. Multiple unbalanced conditions may
be applied simultaneously.
• Set up the power flow case for the pre switching system condition. When a solved case
is to be the initial condition, the working case must be a solved case. Otherwise, the
bus boundary conditions must correspond to the prefault condition. This provides the
basis for the initialization of all generators and the conversion of all loads to constant
admittance.
• Change branch and generator status as required, or adjust loads and shunts, to pro-
duce the desired posts witching system conditions excluding unbalances. An example
would be the application of a two-phase unbalance between two buses where a branch
already exists and the unbalance is to be applied to that branch. It is necessary to
remove the branch and to apply the unbalance (see Figure 7-25).
• Apply the unbalances that are to exist in the post switching condition and solve the
resulting interconnected sequence networks for the complete set of system voltages.
The unbalance fault calculation process will re-establish the network admittance
matrices for the posts switching condition prior to performing the calculations.
In applying unbalances, the following points should be noted:
1. Both resistance and reactance must be specified for each impedance shown. Imped-
ances are specified in per unit relative to base impedance.
2. It is not necessary to multiply ground fault impedances by three; this is done automat-
ically as part of the fault calculation by.
4. Only one in-line unbalance may be applied. The location of this unbalance is automat-
ically assigned the bus number 999999.
5. For in-line unbalances, the user is cautioned against the applying faults very close to
the sending or receiving end of the branch. Since this can give very low impedances
between the dummy bus and the closer real bus.
6. The single and double phase closed unbalances place new phase branches in parallel
with those that are already present in the working case.
7. The single and double phase closed unbalances are applicable to discrete components
such as series capacitors and jumpers, but are not applicable to transmission lines.
The user may create unbalanced conditions, other than those that are automated by the unbal-
anced fault calculation process, by judicious use of dummy buses and low impedance branches.
The fault analysis is normally able to handle a branch impedance as low as j0.0001 per unit without
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-51
Short-Circuit Fault Analysis PSS™E-31.0
Performing Fault Analysis in PSS™E Users Manual
difficulty. However, when introducing "jumper" branches which are not being treated as zero imped-
ance lines, the user should examine the impedances of other branches connected to these buses
to check for an extremely wide range of impedances, which could result in numerical precision
problems.
Consider the currents flowing in the leads of a wye-delta transformer as shown in Figure 7-33. The
wye-connected winding allows zero-sequence current to flow into the transformer leads and thence
to ground via the neutral grounding strap. While the wye-connected winding is certainly a path to
ground, observations at the leads that feed this winding see the zero-sequence current just as if it
were a series current flowing to the bus at the other side. This zero-sequence current in the trans-
former leads must be recognized in calculations of the phase values of the lead currents.
I p1 Primary
Leads
I p2 Secondary
I p0 Leads I s1
I s2
Tank
3I p0
– Neutral Lead
3I p0
Grounding Strap
Figure 7-33. Lead Current Flowing Into and Out of a Wye-Delta Transformer
Consider the calculation of conditions at a bus where the following are connected:
• Transmission lines.
• A grounded wye-winding of a wye-delta transformer.
• A grounded wye-connected shunt reactor.
• A phase-to-ground fault somewhere on the bus side of all circuit breakers.
7-52 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Performing Fault Analysis in PSS™E
The bus arrangement is shown in Figure 7-34a. There are three components of zero-sequence cur-
rent flowing from the bus to ground: fault current, reactor zero-sequence current, and transformer
zero-sequence current. A conventional way of representing the bus is shown in Figure 7-34b. Here,
the transformer is represented as a ground tie at the bus in the zero-sequence. The bus is assigned
a shunt admittance equal to the sum of the reactor and transformer admittances. Use of this repre-
sentation in system network solutions leads to correct results for bus positive-, negative-, and zero-
sequence voltages. The subsequent calculation of transformer lead currents is erroneous, though,
because the zero-sequence lead current appears to be zero when it should not be.
The alternative and recommended approach is to represent the transformer via the winding type
code option of PSS™E. When the winding type code approach is used, the implied bus represen-
tation is as shown in Figure 7-34c.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-53
Short-Circuit Fault Analysis PSS™E-31.0
Performing Fault Analysis in PSS™E Users Manual
Ir
Line A
Shunt Reactor
Line B
If
It
1:t
Transformer
I fo
I ro
Z
I fo
I to B = Br
I ro + I to
1:t
1 Z to
B = B r + --------------
2
Z to t
b. Bus Setup with Transformer Treated as c. Bus Setup with Transformer Modeled
Bus Ground Path via Winding Type Codes
This results in the same system solution as obtained with the prior approach, but recognizes the
zero-sequence current in the transformer leads. Calculations of transformer lead phase currents
are correct, provided that the 30° phase shift of the transformer is handled properly.
7-54 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Performing Fault Analysis in PSS™E
While the winding type codes are normally used in the handling of the majority of transformers, use
of manually determined shunt paths at buses may still be needed in special situations. When the
winding type codes are not used, the following points must be noted:
t:1 t:1
Positive
Sequence
Z Z
∆ ∆
Zero
Sequence
1 1
y = --------- y = ---
2 Z
Zt
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-55
Short-Circuit Fault Analysis PSS™E-31.0
Working with a Two-Wire System Users Manual
132 kV 12 kV
Secondary of
Generator Step-Up Load
Transformer Transformer
The two-phase system modelling assumption is established with the Short circuit phase
modeling run-time option (Section 1.6.4). This option allows the selection of two-phase instead of
the conventional three-phase mode. Selecting the two-phase option has the following effects:
• The symmetrical component "a" operator becomes (–1+j0), and the negative sequence
is ignored, giving
i0 i
= 1⁄2 1 1 a
i1 1 –1 ib
• The base voltage is taken to be the line-to-line voltage at base conditions, and the base
current is taken to be the corresponding line current so that
MVA base
I L base = --------------------------
V LL base
V 2 LL base
Z LG base = ------------------------------
2MVA base
I p = I L base × I pu
where vpu and Ipu are the per-unit bus voltage and branch current, respectively.
7-56 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Working with a Two-Wire System
Use of PSS™E under the two-phase option is identical to its use in conventional three-phase mode
except for the following:
• Negative-sequence data may be entered for generators, branches, and loads but it is
ignored in the fault calculations.
• Unbalanced faults may involve only phases 1 and 3. (The excluded phase in an L-L-G
fault must be phase 2.) The three-phase fault selection must not be used.
• The two-phases-closed unbalance should not be used.
Z1 = Zp – Zm
Z0 = Zp + Zm
where
Z1 = Positive-sequence impedance.
Z0 = Zero-sequence impedance.
Zp = Self impedance of one phase conductor.
Zm = Mutual impedance between the phase conductors.
Similar expressions hold for the charging capacitances in the positive- and zero-sequences.
7.7.2 Transformers
The positive and zero-sequence characteristics of transformers must be determined from their
internal connections. As an example, consider the transformer connection shown in Figure 7-36.
The behavior of the transformer when positive and zero-sequence currents, respectively, flow in its
primary windings are shown in Figure 7-37. When positive-sequence current flows in the primary
side, the two secondary windings are effectively in parallel and a positive-sequence current flows
in the secondary leads. When a zero-sequence current flows in the primary leads, the direction of
current is reversed in one primary and secondary winding. The two secondary windings now form
a short-circuited loop; a current corresponding to the primary zero-sequence current flows around
this loop, but no zero-sequence current flows in the secondary leads. The behavior of the primary
and secondary currents in this transformer is not affected by the grounding of one secondary lead;
no zero-sequence current can flow into the transformer because the ground is external to it.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-57
Short-Circuit Fault Analysis PSS™E-31.0
Working with a Two-Wire System Users Manual
i 1s
i 1p
i 1s
--------
2
i 1p
i 1s
-------- i 1s
2
a. Positive-Sequence Behavior
0.0
i 0p
i 0s
i 0s
2i 0p i 0p
b. Zero-Sequence Behavior
The modeling of the load transformer in PSS™E can be handled in a completely standard manner
by the use of grounding codes. The positive- and zero-sequence connections, corresponding to
Figures 7-37 and 7-36, are shown in Figure 7-38. They may be specified to PSS™E by grounding
codes of 2.
7-58 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Working with a Two-Wire System
a. Winding Connections
Winding 1 Winding 2
b. Positive-Sequence Connection
Winding 1 Winding 2
c. Zero-Sequence Connection
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-59
Short-Circuit Fault Analysis PSS™E-31.0
Working with a Two-Wire System Users Manual
Sequence Circuits
Load Circuit Positive Zero
ZL
ZL ZL
ZL
ZL ZL
-------
2
ZL
ZL -------
2
Zp Z1 = Zp – Zm Z 0 =Z p +Zm
Zm
B c1 B c1 B c0 B c0
---------- ---------- ---------- ----------
2 2 2 2
d. Mutual Coupling
7-60 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Working with a Two-Wire System
30 MVA
100
j0.333
200
400
j0.15
j0.15
330
0.05 + j0.5 j4
(5 + j2) MVA 440
550
0.05 + j0.5
(5 + j2) MVA
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-61
Working with a Two-Wire System
Short-Circuit Fault Analysis
7-62
Users Manual
PSS™E-31.0
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Working with a Two-Wire System
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-63
Working with a Two-Wire System
Short-Circuit Fault Analysis
7-64
BUS# X-- NAME --X BASKV CODE LOADS VOLT ANGLE S H U N T AREA ZONE OWNER
100 ’GEN-1’ 10.000 3 0 1.0000 0.0 0.0 0.0 1 1 1
200 ’HYDRO’ 132.00 1 0 0.9828 -4.8 0.0 0.0 1 1 1
300 ’WEST’ 132.00 1 0 0.9747 -6.0 0.0 0.0 1 1 1
330 ’EAST-LO 12.000 1 1 0.9672 -7.2 0.0 0.0 1 1 1
Siemens Power Transmission & Distribution, Inc., Power Technologies International
BUS# X-- NAME --X BASKV ID CD ST PSI MVA-LOAD CUR-LOAD Y - LOAD AREA ZONE OWNER
330 ’EAST-LO 12.000 1 1 1 1.000 5.0 2.0 0.0 0.0 0.0 0.0 1 1 1
440 ’WEST-LO 12.000 1 1 1 1.000 5.0 2.0 0.0 0.0 0.0 0.0 1 1 1
550 ’MAIN-LO 12.000 1 1 1 1.000 15.0 8.0 0.0 0.0 0.0 0.0 1 1 1
X----- REMOTE BUS ------X
BUS# X-- NAME --X BASKV COD MCNS PGEN QGEN QMAX QMIN VSCHED VACT. PCT Q BUS# X-- NAME --X BASKV
100 ’GEN-1’ 10.000 3 1 25.1 6.3 20.0 0.0 1.0000 0.9828 1.0 200 ’HYDRO’ 132.00
BUS# X-- NAME --X BASKV CD ID ST PGEN QGEN QMAX QMIN PMAX PMIN OWN FRACT OWN FRACT MBASE Z S O R C E X T R A N GENTAP
100 ’GEN-1’ 10.000 3 3 1 25.1 6.3 20.0 0.0 9999.0-9999.0 1 1.000 30.0 0.0000 0.2000
X------ FROM BUS -------X X------- TO BUS --------X W C X---- CONTROLLED BUS ----X
BUS# X-- NAME --X BASKV BUS# X-- NAME --X BASKV CKT 1 W CN RMAX RMIN VMAX VMIN NTPS BUS# X-- NAME --X BASKV CR CX
100 ’GEN-1’ 10.000 200 ’HYDRO’ 132.00 1 T 1 1 1.15000 0.85000 1.03000 1.01000 49 -200 ’HYDRO’ 132.00
300 ’WEST’ 132.00 330 ’EAST-LO 12.000 1 T 1 1 1.15000 0.85000 1.00000 0.98000 49 -330 ’EAST-LO 12.000
400 ’EAST’ 132.00 440 ’WEST-LO 12.000 1 T 1 1 1.15000 0.85000 1.00000 0.98000 49 -440 ’WEST-LO 12.000
Users Manual
PSS™E-31.0
Users Manual
PSS™E-31.0
Siemens Power Transmission & Distribution, Inc., Power Technologies International
BUS# X-- NAME --X BASKV CODE ZERO SEQ SHUNT NEG SEQ SHUNT POS SEQ SHUNT MVA-LOAD CURRENT-LOAD ADMITTANCE-LOAD
100 ’GEN-1’ 10.000 3 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
200 ’HYDRO’ 132.00 1 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
300 ’WEST’ 132.00 1 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
330 ’EAST-LO 12.000 1 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0500 0.0200 0.0000 0.0000 0.0000 0.0000
400 ’EAST’ 132.00 1 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
440 ’WEST-LO 12.000 1 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0500 0.0200 0.0000 0.0000 0.0000 0.0000 Capacitor
550 ’MAIN-LO 12.000 1 0.0000 0.0000 0.0000 0.0000 0.0000 0.0400 0.1500 0.0800 0.0000 0.0000 0.0000 0.0000 bank not
BUS# X-- NAME --X BASKV ID CODE ST ZGEN (ZERO) ZGEN (POSITIVE) ZGEN (NEGATIVE) MBASE X T R A N GENTAP
grounded
100 ’GEN-1’ 10.000 3 3 1 0.00000 0.00000 0.00000 0.20000 0.00000 0.20000 30.0 0.00000 0.00000 1.0000 internally
X------ FROM BUS -------X X------- TO BUS --------X X- POS AND NEG SEQUENCE -X X---- ZERO SEQUENCE -----X
BUS# X-- NAME --X BASKV BUS# X-- NAME --X BASKV CKT ST ZI LINE R LINE X CHARGING LINE R LINE X CHARGING
200 ’HYDRO’ 132.00 300 ’WEST’ 132.00 1 1 0.01500 0.15000 0.02500 0.02000 0.30000 0.04000
200 ’HYDRO’ 132.00 400 ’EAST’ 132.00 1 1 0.02500 0.25000 0.04000 0.04000 0.45000 0.06500
330 ’EAST-LO 12.000 550 ’MAIN-LO 12.000 1 1 0.05000 0.50000 0.00000 0.04000 0.80000 0.00000
440 ’WEST-LO 12.000 550 ’MAIN-LO 12.000 1 1 0.05000 0.50000 0.00000 0.04000 0.80000 0.00000
X------ FROM BUS -------X X------- TO BUS --------X S W C X-- POS & NEG --X X-------- ZERO SEQUENCE --------X X- WINDING1 -X WINDNG2 MAGNETIZING Y
BUS# X-- NAME --X BASKV BUS# X-- NAME --X BASKV CK T 1 C R X R X RGROUND XGROUND RATIO ANGLE RATIO G B
100 ’GEN-1’ 10.000 200 ’HYDRO’ 132.00 1 1 T 2 0.00000 0.33000 0.00000 0.33000 0.0000 0.0000 1.00000 0.0 1.00000 0.0000 0.0000
300 ’WEST’ 132.00 330 ’EAST-LO 12.000 1 1 T 3 0.00000 0.15000 0.00000 0.15000 0.0000 0.0000 1.00000 0.0 1.00000 0.0000 0.0000
400 ’EAST’ 132.00 440 ’WEST-LO 12.000 1 1 T 3 0.00000 0.15000 0.00000 0.15000 0.0000 0.0000 1.00000 0.0 1.00000 0.0000 0.0000
The initial condition load flow solution is shown in Figure 7-43; this is exactly the same as for a
three-phase system solution since it involves only balanced operation and the positive sequence.
The bus voltages in kilovolts are line-to-line values. This solution was made with the following
PSS™E option settings:
• 50 Hz base frequency.
• Two-phase solution mode.
• Polar output of fault analysis results.
BUS 100 GEN-1 10.0 AREA CKT MW MVAR MVA %I 1.0000PU 0.00 100
GENERATION 1 25.1 5.5R 25.7 86 10.000KV
TO 200 HYDRO 132 1 1 25.1 5.5 25.7 73 1.0313UN
BUS 200 HYDRO 132 AREA CKT MW MVAR MVA %I 1.0162PU -4.83 200
1 134.13KV
TO 100 GEN-1 10.0 1 1 -25.1 -3.3 25.3 71 1.0313LK
TO 300 WEST 132 1 1 13.3 2.5 13.5 33
TO 400 EAST 132 1 1 11.8 0.8 11.9 29
BUS 300 WEST 132 AREA CKT MW MVAR MVA %I 1.0087PU -5.91 300
1 133.15KV
TO 200 HYDRO 132 1 1 -13.3 -4.8 14.1 35
TO 330 EAST-LOD12.0 1 1 13.3 4.8 14.1 70 0.9937UN
BUS 330 EAST-LOD12.0 AREA CKT MW MVAR MVA %I 0.9955PU -7.04 330
1 11.946KV
TO LOAD-PQ 5.0 2.0 5.4
TO 300 WEST 132 1 1 -13.3 -4.5 14.0 70 0.9937LK
TO 550 MAIN-LOD12.0 1 1 8.3 2.5 8.6 58
BUS 400 EAST 132 AREA CKT MW MVAR MVA %I 1.0066PU -6.45 400
1 132.88KV
TO 200 HYDRO 132 1 1 -11.8 -4.5 12.6 31
TO 440 WEST-LOD12.0 1 1 11.8 4.5 12.6 63 0.9937UN
BUS 440 WEST-LOD12.0 AREA CKT MW MVAR MVA %I 0.9938PU -7.45 440
1 11.926KV
TO LOAD-PQ 5.0 2.0 5.4
TO 400 EAST 132 1 1 -11.8 -4.3 12.6 63 0.9937LK
TO 550 MAIN-LOD12.0 1 1 6.8 2.3 7.2 48
BUS 550 MAIN-LOD12.0 AREA CKT MW MVAR MVA %I 0.9795PU -9.39 550
1 11.754KV
TO LOAD-PQ 15.0 8.0 17.0
TO SHUNT 0.0 -3.8 3.8
TO 330 EAST-LOD12.0 1 1 -8.2 -2.1 8.5 58
TO 440 WEST-LOD12.0 1 1 -6.8 -2.0 7.1 48
Figure 7-43. Initial Condition Load Flow Solution for Two-Phase Sample
System
Figure 7-43 shows output from activity SCOP corresponding directly to Figure 7-42, with no fault
applied. In this report the negative sequence and "b-phase" fields have no significance. The "a" and
"c" phase voltage fields show sequence and phase voltages on a line-to-ground basis. The current
values are in terms of per unit line current.
7-66 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Working with a Two-Wire System
Comparison of the flow into bus 550 from bus 330 in Figures 7-42 and 7-43 and shows:
MVA 8.5E6
• Phase current, I p , from Figure 7-42, = ------------- = -------------------------- = 723.2 A
V LL 11.754E3
723.2
• Per-unit phase current, from Figure 7-42, = ------------------ = 0.08605 per unit
8333.3
8.4965E6
-------------------------------------------------
- = 0.08674 per unit
11.754E3 × 8333.3
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-67
Short-Circuit Fault Analysis PSS™E-31.0
Working with a Two-Wire System Users Manual
All transformers in the system are connected as shown in Figure 7-36 with two low-voltage windings
in parallel. This is reflected in the grounding code data in Figures 7-41 and 7-42. The shunt capac-
itor bank at bus 550 is connected line-to-line and is not grounded internally. Figure 7-45 shows the
output from the unbalance fault calculation for a single L-G fault applied at bus 300.
As expected, the a-phase bus voltage at the fault is zero, and a current of 1.6417 per unit flows into
the fault, and at the fault I 0 = I 1 = V oc ⁄ ( Z 0 + Z 1 ) .
1.009
I 0 = I 1 = ---------------------------------------------------------------------------------------------------------------------------------------------------------------
0.00127 + j0.11696 + 0.28804 + j1.07742 (from Figure 7-45)
Figure 7-46 shows the result for an L-G fault at bus 330. Here, because no zero-sequence ground
path exists in the secondary system except for the fault, there is no fault current, and no unbalance
appears in the 132 kV primary system.
The ground connection at one point in the system does not affect the balanced load current at bus
330, and the fault current is zero. The a-phase voltage at bus 330 is zero, as expected. The c-phase
voltage at bus 330 is listed by SCMU as 1.991 per unit. The phase voltages listed by SCMU are
per-unit of phase-to-ground base voltage, and correspond to an a-phase-to-ground voltage of kV.
7-68 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Working with a Two-Wire System
FROM 200 1 0.1810 -80.09 0.7558 -80.88 0.0000 0.00 Load currents
HYDRO 132 0.9368 -80.73 0.0000 0.00 0.5749 98.87 flowing in
FROM 330 1 0.6400 -82.91 0.0679 -98.25 0.0000 0.00
c-phase
EAST-LOD12.0 0.7057 -84.37 0.0000 0.00 0.5749 -81.13
I0 = I1 for a-phase
FAULT CURRENT AT BUS 300 [WEST 132]:
fault current
300 0.8208 -82.29 0.8208 -82.29 0.0000 0.00
WEST 132 1.6417 -82.29 0.0000 0.00 0.0000 0.00
Fault current
POSITIVE SEQUENCE EQUIVALENT FAULT ADMITTANCE 0.0927 -8.5492
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-69
Short-Circuit Fault Analysis PSS™E-31.0
Working with a Two-Wire System Users Manual
UNBALANCES APPLIED:
Figure 7-47 shows the results when the a-phase of the 12-kV system is grounded (by an L-G fault)
at both bus 330 and bus 550. In some cases, the ungrounded zero-sequence network cannot be
handled by PSS™E because its admittance matrix is singular. This problem is rectified by con-
necting a low admittance branch to ground in the zero sequence at an appropriate bus; this small
shunt admittance is insignificant in relation to the admittances of the system branches, but is ade-
quate to avoid the numerical problems stemming from the singular matrix.
Figure 7-48 shows the phase currents from Figure 7-47 on the 2-line diagram of the secondary
system. Note the following:
• The SUM OF CONTRIBUTIONS shown by the unbalance fault calculation for the a-
phase includes both load and ground current.
Current does flow on the a-phase conductor from bus 330 to 550 even though it is solidly grounded
at both ends, as a result of the mutual coupling between the two phases of the line. No current would
flow in the a-phase conductor if the two phases were of isolated-phase construction and had no
phase-to-phase mutual impedance.
7-70 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Working with a Two-Wire System
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-71
Short-Circuit Fault Analysis PSS™E-31.0
Performing Automatic Sequencing Fault Analysis Users Manual
0.147-j0.0674
0.069-j0.035 0.069-j0.035
1. A prefault network condition either as specified in the working case or, optionally, cor-
responding to classical "flat" fault analysis assumptions.
3. The application of only three phase faults or both three phase and single-line-to-ground
faults at each fault location.
4. The application of the faults selected in (3) at each "home bus" selected in (2).
5. Optionally, (4) again with each branch connected to the "home bus" in turn removed
from service.
6. Optionally, (4) again with the far end of each branch connected to the "home bus" in
turn opened, and the faults applied at the line end position.
7. Optionally, (4) again with specified branches in turn removed from service.
8. A selection of output options for each fault applied, ranging from a tabulation of fault
currents through detailed output of conditions at the "home bus" along with detailed
output for all buses up to "n" levels away from the "home bus".
7-72 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Performing Automatic Sequencing Fault Analysis
Bus I is the "home" bus and if faults are to be selected only at home buses there will be a maximum
of 2 faults applied at Bus I, if both a three phase and a single-line-to-ground fault are applied. With
only a 3-phase fault applied the number of faults will be limited to one.
Figure 7-50 shows the option where a fault is to be applied at the home bus with all circuits in ser-
vice and with each outgoing line out of service in turn. In this situation, for this "home" bus, there
will be 4 faults if only one fault type is selected. If line outages are performed on a selective basis
instead of selecting "all" outgoing branches, the number of faults applied will clearly be reduced.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-73
Short-Circuit Fault Analysis PSS™E-31.0
Performing Automatic Sequencing Fault Analysis Users Manual
Figure 7-51 shows the option where a fault is to be applied at the home bus with all circuits in ser-
vice and faults applied at the open end of each outgoing line. In this situation, for this "home" bus,
there will be 4 faults if only one fault type is selected.
7-74 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Performing Automatic Sequencing Fault Analysis
Figure 7-52 clarifies the concept of "n" levels away. It can be seen that, given the possibility of a
large combination of home buses, line out cases and line open end cases, coupled with a value of
"n" greater than "1", the possibility arises for a very large output listing or file.
In the diagram, for the home bus shown, there are 3 buses which are 1 level away and 2 buses
which are 2 levels away.
The user should take care in selection of the number of fault and output options.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-75
Short-Circuit Fault Analysis PSS™E-31.0
Performing Automatic Sequencing Fault Analysis Users Manual
Type of faults to be applied: The available faults and topological locations are described
in the previous section
Starting power flow conditions: The user selects either the full detailed solution or a Flat
or "classical" condition for the network in the power flow case. If the Flat condition is
selected, Generator power outputs are assumed to be zero; loads and fixed bus shunts are
neglected in the positive and negative sequence networks; switched shunts are neglected
in all three sequences; zero sequence shunt loads and the zero sequence ground ties cre-
ated by grounded transformer windings are represented. Line charging capacitances and
line connected shunt elements are neglected in all three sequence networks. All transform-
ers, including generator step-ups, are assumed to be at nominal ratio, zero phase shift
angle, and a uniform voltage profile of unity magnitude at zero phase angle is assumed; DC
lines and FACTS devices are ignored. The original values of all data items in the power flow
case are not modified; i.e. at the termination of the fault calculation, the power flow case is
identical in content to what it was prior to initiating the fault calculation process.
If the flat conditions option is not enabled, the level of network modeling and the bus bound-
ary conditions used as the prefault network condition are as specified in the power flow prior
to initiating the fault calculation process.
DC Lines and FACTS Devices: DC lines and FACTS devices can be blocked or be rep-
resented as load. If represented as load, the apparent AC system complex loads are con-
verted to positive sequence constant admittance load at the buses at which these quantities
are injected into the AC system during normal power flow work. In the negative and zero
7-76 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Performing Automatic Sequencing Fault Analysis
sequence networks, DC lines and FACTS devices are represented as open circuits. The
selected option applies to all DC lines and FACTS devices in the working case.
Transformer impedance: The zero sequence impedance of each such transformer is
scaled by the same factor as is its positive sequence impedance. Otherwise, all zero
sequence transformer impedances are left at their nominal values
Output options and number of levels "n": These define the level of output required. Out-
put can be at only the home bus or at both the home bus and "n" levels away in full or sum-
mary form or as a fault current summary table (see Figure 7-53a).
Line-to-ground reporting: This defines the form of output for cases involving L-G faults.
If the L-G faults option is selected the user can select to output the results in the form of A
Phase currents and apparent impedances or 3 x zero sequence currents and zero
sequence apparent impedances or both (see Figure 7-53b).
(a)
(b)
Subsystem: Identifies the subsystem to be tested including Areas, Owners, Zones, Based
and individual buses.
As can be seen in the dialog, the user can identify two file names one of which is the Fault control
input file. This file provides the user with more flexibility in selection of faults to be simulated and in
the manner in which output is limited or extended (see Section 7.8.3.1).
The Relay file is generated as a user option (see Section 7.8.3.2). This file summarizes the faults
performed and the short-circuit current levels in pu. The file is generated as a *.re type in ASCII
format; readily portable to an Excel type.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-77
Short-Circuit Fault Analysis PSS™E-31.0
Performing Automatic Sequencing Fault Analysis Users Manual
7-78 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Performing Automatic Sequencing Fault Analysis
where:
IBUS Bus number. Bus IBUS must reside in the working case. No default is allowed.
FCODE Fault code of either zero (suppress faulting of bus IBUS) or one (allow bus IBUS
to be faulted). FCODE = 1 by default.
PCODE Print control code for conditions at bus IBUS when some other bus is faulted.
PCODE may be specified as either zero (no reporting, and not counted in the
"levels away" calculation), one (no reporting, but counted in the "levels away"
calculation), or two (reported and counted). PCODE = 2 by default.
Data records may be input in any order. This group of records is terminated with a record specifying
an IBUS value of zero.
The hidden "star point" buses of three-winding transformers are always assumed to have FCODE
and PCODE values of zero. Any other bus for which no data record is read is assigned the default
values given above.
With the second group of records, for any bus to be faulted, the following may be specified:
1. Up to 20 buses whose conditions are to be tabulated for all fault cases calculated for
this home bus. These buses are in addition to those printed as a result of the "levels
away" selection.
2. Up to eight additional branches to be outaged in turn with the home bus faulted. These
fault cases are calculated only if the line out option was selected, and are in addition to
the automatic outaging of the branches connected to the home bus. Only non trans-
former branches and two-winding transformers may be specified.
Data for each home bus specified here is entered on three consecutive data records as follows:
IBUS
JBUS1, JBUS2, ... JBUS20
I1, J1, CKT1, ... I8, J8, CKT8
where:
IBUS Bus number. Bus IBUS must reside in the working case. No default is allowed.
JBUSi Bus number of a bus to be reported for home bus IBUS fault calculations. The
first zero value of JBUSi is interpreted as the end of JBUS values for bus IBUS.
JBUSi = 0 by default.
Ii, Ji, CKTi The "from bus" number, "to bus" number and branch circuit identifier respec-
tively of a branch to be outaged with bus IBUS faulted. The first zero value of Ii is
interpreted as the end of branch specifications for bus IBUS. Ii = 0 and CKTi = ’1’
by default; no default is allowed for Ji.
If any of the data records in the block for bus IBUS contains an error (e.g., bus not found), an appro-
priate message is printed and the entire block for bus IBUS is ignored.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-79
Short-Circuit Fault Analysis PSS™E-31.0
Performing Automatic Sequencing Fault Analysis Users Manual
All three records must be entered for each bus block specified. If, for example, one or more output
buses are to be specified for bus IBUS but no additional branches for outage calculations are
required, the third record must still be specified; it may either have a zero as its first bus number or
simply be a blank line.
The buses and branches in the block for bus IBUS are used only if bus IBUS is among the buses
selected for processing as home buses, and an FCODE value of zero was not specified for bus
IBUS.
Bus JBUSi is not reported if it was assigned a PCODE value of zero or one, or if it is not connected
back to the home bus via in-service AC branches.
Outage fault cases are calculated only if the Line outage cases option box is checked in the dialog.
The following quantities are tabulated in the indicated column positions of each record:
7-80 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Performing Automatic Sequencing Fault Analysis
Once the output destination has been selected and the user has completed the process of selecting
fault, solution and output options and of identifying the required files in the dialog (Figure 7-54) all
that is required is to select the Go button to initiate the calculations. The fault calculation process
may be terminated by entering the AB interrupt control code.
If sequence data has not been appended to the power flow case, an appropriate error message is
printed and calculation process is terminated.
At initiation of the calculation process, PSS™E builds and factorizes the sequence admittance
matrices, reporting its progress to the Output Bar or to an alternative destination selected by the
user.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-81
Short-Circuit Fault Analysis PSS™E-31.0
Performing Automatic Sequencing Fault Analysis Users Manual
Figure 7-55. Location of Bus 151 and Buses one Level Away in savnw.sav
Each page of the detailed bus output report contains a heading block, which tabulates the current
date and time, the two-line case heading, and the home bus number and name. If the flat conditions
option was selected, this is noted; if the line outage or line end condition is being reported, this is
also flagged. If subsystems are being specified by area, zone, and/or owner, the area, zone, and/or
owner, as appropriate, currently being processed are also identified.
The home bus, the level number, relative to the home bus, of buses whose output is printed on the
page, and, if appropriate, a line out or line end identifier are printed on the right side of the banner
block. If line-to-ground faults are being calculated and subsystem selection by area, zone, and/or
owner is enabled, the current area, zone, and/or owner is also printed here.
Voltages, currents and apparent impedances are printed in either physical units (kV L-G, amps and
ohms) or per unit, and in either rectangular or polar coordinates, according to the fault analysis
output options currently in effect. If the physical units option is enabled and the bus whose base
voltage is required for the calculation of a quantity has no base voltage specified for it, the quantity
is printed in per unit.
For each bus at which conditions are reported (i.e., for each "at bus"), the following quantities are
tabulated:
1. The bus number, name, base voltage, and area number in which it resides. This is fol-
lowed by the positive sequence bus voltage for the three phase fault case. If single line
7-82 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Performing Automatic Sequencing Fault Analysis
to ground faults are being calculated, the A phase voltage and the three sequence volt-
ages for the L-G case are printed.
2. If the bus is the home bus, the sequence Thevenin impedances at the fault point in per
unit, rectangular coordinates. If only three phase faults are being calculated, only the
positive sequence Thevenin impedance is printed.
3. The machine identifier and currents arriving at the bus from all online machines at the
bus. For the L-G fault, either zero sequence, A phase, or both quantities are printed,
according to the user’s selection.
4. The "from bus" number, name, base voltage, area number, and circuit identifier of each
non transformer branch and two-winding transformer connected to the "at bus". The
branch quantities tabulated include the current arriving at the "at bus" from the
"from bus", the apparent impedance as seen at the "from bus" looking down the line
toward the "at bus" (i.e., the V/I ratio at the "from bus"), and the ratio of apparent X/R.
For the L-G fault, either zero sequence, A phase, or both quantities are printed,
according to the user’s selection. Branches are printed in ascending "from bus" numer-
ical or alphabetical order according to the bus output option in effect.
5. The winding number, transformer name and circuit identifier of each three-winding
transformer connected to the "at bus". The current arriving at the "at bus" from the
transformer is tabulated. For the L-G fault, either zero sequence, A phase, or both cur-
rents are printed, according to the user’s selection. Three-winding transformers are
printed in ascending transformer name order.
6. The current flowing to ground at the bus exclusive of any fault current. These currents,
annotated "TO SHUNT", include any load and shunt current at the bus as well as the
AC side current of any unblocked DC line or in-service FACTS device. In the zero
sequence, only the shunt load plus switched shunt is output here; specifically, the zero
sequence ground ties created by grounded transformer windings are not shown here
but are included in the branch contribution output of (4) and (5) above. For the L-G fault,
either zero sequence, A phase, or both quantities are printed, according to the user’s
selection. Load and shunt current output is suppressed if the corresponding sequence
load and shunt admittances are all zero.
If the user selected to obtain a full report for home buses and all buses "n" levels away, the reports
will be printed as described above for all the buses.
If the user selected to obtain a full report for home buses but only a summary report for "n" levels
away, the home bus report will be printed as described above. For the remote buses, however, only
machine and branch quantities are tabulated in a form similar to (3), (4) and (5) above. A branch is
only reported once: at the end which is "closer to" (i.e., fewer levels away from) the "home bus."
Under both of the output options, the printing of remote contributions at buses for which a PCODE
value of zero or one was specified in the Fault Control Data File is suppressed. In addition, upon
encountering a remote bus with a PCODE value of zero, those buses connected to the bus that
would normally be at the next "level away" are promoted to the current level.
The third output option is the Fault current summary. Here, one output line is printed for each fault
giving the fault currents. Fault currents are printed in either amps or per unit, and in either rectan-
gular or polar coordinates, according to the fault analysis output options currently in effect. If the
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-83
Short-Circuit Fault Analysis PSS™E-31.0
Performing Automatic Sequencing Fault Analysis Users Manual
physical units option is enabled and the faulted bus has no base voltage specified for it, fault current
is printed in per unit. If line out and/or line end faults are being calculated, for a given home bus, the
bus fault is reported first. Then the line out and/or line end faults involving each branch connected
to the home bus in turn are processed.
In Figure 7-56, overleaf, the results for the home bus are listed. It can be seen that although there
is a 600 Mvar shunt connected at bus 151, the total shunt current is zero. This is clearly because
the voltage at this bus (the faulted home but is zero).
Note that the listing has been compressed slightly from the original output listing for the portrait
view.
In Figure 7-57, the results are listed for the "1 Level" away. It can be seen that there is a listing for
the four immediate neighbors of bus 151, the home bus. The information on branch flows has the
same format as that of the home bus, at the 0 Level since the "full" report options was selected for
these buses.
- PSS/E SHORT CIRCUIT OUTPUT THU, FEB 26 2004 11:35 .HOME BUS IS 151.
- PSS/E PROGRAM APPLICATION GUIDE EXAMPLE .NUCPANT 500.0.
- BASE CASE INCLUDING SEQUENCE DATA .
- *** FAULTED BUS IS: 151 [NUCPANT 500.0] *** 0 LEVELS AWAY
T H R E E P H A S E F A U L T
X--------- FROM --------X AREA CKT I/Z RE(I+) IM(I+) RE(Z+) IM(Z+) APP X/R
101 [NUC-A 21.600] 1 1 PU/PU 9.8734 -11.0030 0.0003 0.0136 45.333
102 [NUC-B 21.600] 1 1 PU/PU 9.8734 -11.0030 0.0003 0.0136 45.333
152 [MID500 500.00] 1 1 PU/PU -0.2319 -6.2545 0.0031 0.0500 16.264
152 [MID500 500.00] 1 2 PU/PU -0.2319 -6.2545 0.0031 0.0500 16.264
201 [HYDRO 500.00] 2 1 PU/PU 3.3729 -16.5469 0.0010 0.0151 14.864
TO SHUNT (P.U.) 0.0000 0.0000
TOTAL FAULT CURRENT (P.U.) 22.6560 -51.0619
Figure 7-56. Report Output at the Home Bus ( 0 level) for a 3-Phase Fault
In Figure 7-57 it can be seen that the immediate neighbors to bus 151 are the buses 101, 102, 152
and 201. Those buses, at 1 level away, are now the "AT" buses. The flows shown in the tabulation
are from the "FROM" buses towards the respective "AT" buses.
As an example, it can be seen that the flow shown for bus 101 is the flow from bus 151 to bus 101.
The flow is(-9.8734 11.003). This has the opposite sign from that shown in Figure 7-56 where the
home bus 151 is the "AT" bus.
7-84 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Performing Automatic Sequencing Fault Analysis
Figure 7-58 shows the Fault Current Summary report from the calculation which applies a three
phase fault. It shows the fault current for a fault at Bus 151 with all lines in. It can be seen that the
result is the same as that shown in Figure 7-56. The report then lists the results for a fault at Bus
151 each outgoing line OUT of service and with the fault at the open END.
- PSS/E SHORT CIRCUIT OUTPUT THU, FEB 26 2004 11:35 .HOME BUS IS 151.
- PSS/E PROGRAM APPLICATION GUIDE EXAMPLE .NUCPANT 500.0.
- BASE CASE INCLUDING SEQUENCE DATA .
- *** FAULTED BUS IS: 151 [NUCPANT 500.0] *** 1 LEVELS AWAY
T H R E E P H A S E F A U L T
X--------- FROM --------X AREA CKT I/Z RE(I+) IM(I+) RE(Z+) IM(Z+) APP X/R
MACHINE 1 PU/ 9.8734 -11.0030
151 [NUCPANT 500.00] 1 1 PU/PU -9.8734 11.0030 0.0000 0.0000 0.000
T H R E E P H A S E F A U L T
X--------- FROM --------X AREA CKT I/Z RE(I+) IM(I+) RE(Z+) IM(Z+) APP X/R
MACHINE 1 PU/ 9.8734 -11.0030
151 [NUCPANT 500.00] 1 1 PU/PU -9.8734 11.0030 0.0000 0.0000 0.000
T H R E E P H A S E F A U L T
X--------- FROM --------X AREA CKT I/Z RE(I+) IM(I+) RE(Z+) IM(Z+) APP X/R
151 [NUCPANT 500.00] 1 1 PU/PU 0.1847 5.7520 0.0000 0.0000 0.000
151 [NUCPANT 500.00] 1 2 PU/PU 0.1847 5.7520 0.0000 0.0000 0.000
153 [MID230 230.00] 1 1 PU/PU -1.2158 -5.5759 -0.0060 0.0542 9.048
151 [EAST500 500.00] 2 1 PU/PU 0.5901 -1.5481 0.1073 0.1860 1.733
3004 [WEST 500.00] 5 1 PU/PU 0.2561 -4.3801 0.0193 0.1146 5.929
300 Mvar shunt at Bus 201 Current flow from Bus 211 to Bus 201
Figure 7-57. Current Flows 1 Level Away from Home Bus 151 for Three-
Phase Fault
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-85
Short-Circuit Fault Analysis PSS™E-31.0
Performing Automatic Sequencing Fault Analysis Users Manual
Figure 7-58. Fault Summary Report with 3-Phase Fault on Bus 151
In Figure 7-59, it can be seen that with the single-line-to-ground faults included, the report format is
the same as for only 3-phase faults. The results now append the zero sequence fault current flows
in the branches connected to the home bus. In addition the negative and zero sequence Thevenin
impedances are shown, together with the A phase and sequence voltages at the faulted bus.
With polar coordinates used, it can be seen that the total fault current is 55.8625 / -66.07 pu, com-
pared to the rectangular coordinate output which, in Figure 7-56, is 22.656 -51.0619 pu. The listing
for "n" levels away will use the same format shown in Figure 7-57 with, in this case, the zero
sequence (L-G) results appended in the right hand columns.
7-86 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Users Manual
PSS™E-31.0
Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS/E SHORT CIRCUIT OUTPUT MON, MAR 01 2004 14:53 HOME BUS IS :
PSS/E PROGRAM APPLICATION GUIDE EXAMPLE 151 [NUCPANT 500.00]
BASE CASE INCLUDING SEQUENCE DATA
*** FAULTED BUS IS : 151 [NUCPANT 500.00] *** 0 LEVELS AWAY
RT BUS 151 [NUCPANT 500.00] AREA 1 (PU) V+: / 0.0000/ 0.00 (PU) VA: / 0.0000/ 0.00 V0: / 0.1497/ -159.48
V+: / 0.5799/ 12.13 V-: / 0.4323/ -170.77
THEV. R, X, X/R: POSITIVE 0.00409 0.01765 4.318 NEGATIVE 0.00409 0.01765 4.138 ZERO 0.00019 0.00627 32.847
T H R E E P H A S E F A U L T O N E P H A S E F A U L T
X--------- FROM -------X AREA CKT I/Z /I+/ AN(I+) /Z+/ AN(Z+) APP X/R /3I0/ AN(3I0) /Z0/ AN(Z0) APP X/R
101 [NUC-A 21.600 1 1 PU/PU 14.7835 -48.10 0.0136 88.74 45.333 33.0137 -68.21 0.0000 0.00 0.000
102 [NUC-B 21.600 1 1 PU/PU 14.7835 -48.10 0.0136 88.74 45.333 33.0137 -68.21 0.0000 0.00 0.000
152 [MID500 500.00 1 1 PU/PU 6.2588 -92.12 0.0501 86.48 16.264 0.1865 53.87 0.1044 -95.14 11.121
152 [MID500 500.00 1 2 PU/PU 6.2588 -92.12 0.0501 86.48 16.264 0.1865 53.87 0.1044 -95.14 11.121
201 [HYDRO 500.00 2 1 PU/PU 16.8872 -78.48 0.0512 86.15 14.864 5.7775 -65.40 0.0222 -93.00 19.081
TO SHUNT (P.U.) 0.0000 0.00 0.0000 0.00
TOTAL FAULT CURRENT (P.U.) 55.8625 -66.07 71.6023 -68.21
Instead of imposing flat conditions for the calculations, it is possible to set up a "converted" power
flow case with a classical representation. Having the "converted" case would allow launching the
automatic sequencing calculation process without having to select impose flat conditions in the
selector window (Figure 7-54).
The automatic sequencing process is sensitive to the fault analysis modeling option setting. Under
the two phase option, negative sequence Thevenin impedances are shown in the output report as
zero.
As with all user specified output files used in PSS™E, the relay output summary file designated
when launching these fault calculations does not have data appended to it if the file already exists.
If the contents of a relay output file are to be appended to a previously existing file, a new filename
should be specified. The two files may be subsequently merged with a text editor following comple-
tion of the calculations.
Depending upon the standard (e.g., ANSI Standard C37.5 – 1975 or the International Electrotech-
nical Commission standards) the determination of circuit breaker duty requires the calculation of
either of these values:
• The maximum instantaneous value of current in any phase at the instant, a few milli-
seconds after fault initiation, when the circuit breaker contacts separate
• The root-mean-square (rms) value of current wave consisting of sinusoidal component
of constant amplitude equal to the instantaneous amplitude of the decaying alternating
component at an instant, superimposed on a constant unidirectional component of
amplitude equal to that of the decaying unidirectional component at the same instant.
Figure 7-61 illustrates the two current values of interest. The maximum instantaneous value, as
shown in Figure 7-61a is of interest in connection with the IEC Circuit Breaker standards, while the
rms value shown in Figure 7-61b is used by ANSI C37 standards. In this section, we describe the
calculations made in PSS™E.
7-88 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Calculating Circuit Breaker Interrupting Duty
DC
Component
φA
Current
φB
DC
Component
φC
DC
Component
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-89
Short-Circuit Fault Analysis PSS™E-31.0
Calculating Circuit Breaker Interrupting Duty Users Manual
• The alternating current component results from decaying machine internal flux linkages
behind constant subtransient impedances of the machines.
• The unidirectional component is, at the instant of fault application, determined by the
value of the alternating component.
7-90 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Calculating Circuit Breaker Interrupting Duty
The alternating components can be approximated, with acceptable accuracy for several cycles after
fault application, by expressing the generator flux as:
1 1 1 – t ⁄ T′ dz
ψ″ d = ψ″ do ( L″ d + L e ) ⎛ -------------------⎞ + ⎛ --------------------- – -------------------⎞ e
⎝ L + L ⎠ ⎝ L′ + L L + L ⎠
d e d e d e
1 1 – t ⁄ T″ dz
+ ⎛ ---------------------- – ---------------------⎞ e
⎝ L″ + L L′ + L ⎠
d e d e
⎛ L d – L″ d – t ⁄ T′ dz ⎞
+ i do ( L″ d + L e ) ⎜ --------------------- ( 1 – e )⎟
⎝ dL + L e ⎠
L′ d – L″ d – t ⁄ T′ – t ⁄ T″ dz
+ ----------------------- ⎛ e dz + e ⎞
L′ d + L e ⎝ ⎠
and the equivalent for the q-axis. For induction motors (Ld = Lq or L'd or L'q), the Ld terms are not
in the above equations.
The calculations for initial fluxes, ψ′′do and ψ′′qo, and initial currents, ido and iqo, are based on the
initial conditions in the load flow before fault application. The value of Le at each generator is cal-
culated by dividing the voltage at each terminal by the current flowing at the terminals at fault
initiation. Because an initial loading on the machine, Le, will never be infinity, this approximation will
result in flux decaying even for very remote machines. The user is responsible for not including data
for machines where flux decay is not wanted.
The initial value of the unidirectional component of fault current is, in the worst case, equal to the
initial amplitude of the alternating component; this corresponds to a fully offset current wave as
shown for Phase A in Figure 7-60. Using full offset is, of course, conservative. The actual maximum
offset depends on the fault point X/R and the point on the wave where the fault occurs. Thus, the
peak is reached after some DC decay has occurred. The decay of the unidirectional component of
fault current is given by:
where a1 + a2 + … + an = 1
and
• The coefficients ki, characterize the decay of the initial unidirectional components
throughout the network.
• The coefficients, ai, express the contribution of each decaying unidirectional current
component to the unidirectional fault current.
In general, an exact expression of the unidirectional fault current would involve a number of k and
a coefficients equal to the number of branches in the network. Their determination would require a
calculation of the eigenvalues and eigenvectors of the differential equations:
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-91
Short-Circuit Fault Analysis PSS™E-31.0
Calculating Circuit Breaker Interrupting Duty Users Manual
where [Rnet + sLnet] is the operational impedance matrix of the complete network. This calculation
is impractical for normal system analysis work, and it is usual to approximate the unidirectional fault
current by:
–t ⁄ Ts
i dc = I ac ( 0 )e
where
T s = L thev ⁄ R thev
where Lthev and Rthev are the Thevenin impedance (inductance, resistance) at the point of the fault.
• The maximum instantaneous current that could flow in any phase at the specified time
after fault application, assuming that the fault was initiated at such a time, in relation to
the voltage wave that the specified time after application corresponds to a current peak
(Figure 7-61).
• The rms value of the current at the specified time after fault application (Figure 7-61).
The maximum instantaneous current, Itotal peak, and rms currents, Itotal rms, are determined by
I total peak = I dc + I ac
I total rms = 2 + I2
I dc rms
where:
I ac
I rms = -------
2
enabling the total rms current to be written as
I total rms = 2 + I2
I dc rms
7-92 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Calculating Circuit Breaker Interrupting Duty
The breaker duty calculation starts with a load-flow case corresponding to system conditions just
before the application of the fault. The values of the initial internal fluxes, ψ′′do, ψ′′qo, and initial cur-
rents, ido and iqo, are calculated from the prefault machine currents, terminal voltages, and the
characteristic machine impedances, ZSORCE.
The calculation recognizes that the time constants T′dz, T′′dz, T′qz, T′′qz governing the decay of
machine internal fluxes and currents are dependent on the relative values of the machine imped-
ances and the impedances of the network between the machines and the fault. The relationships
used to calculate these time constants are shown in Figure 7-62. The Le term is calculated at each
machine in the network by dividing terminal voltage by terminal current at the instant the fault is
applied.
If the fault location is close to major machines, it will present these machines with conditions approx-
imating a short circuit at their terminals, Le = 0. In this case the short-circuit time constants result.
If the fault location is remote from key generators or fault impedances are high, open-circuit time
constants result. The calculation process reads the machine reactances, open-circuit time con-
stants, and short-circuit time constants, from a Breaker Duty File. The subtransient reactances
specified in this file must correspond to the reactive parts of the impedances, ZSORCE, in the load-
flow case.
For method one, the instantaneous DC offset for each branch is set equal to the magnitude of the
difference between the prefault current on the branch and the instantaneous AC current after the
fault. The total DC offset current is the magnitude of the sum of these differences. Decremented DC
currents and hence total rms and total peak currents for each path are calculated by decaying each
path’s initial DC offset current by the Thevenin impedance at the point of the fault looking out each
path.
Again the total DC offset current is the magnitude of the sum of the decayed currents, which have
been stored and decayed as complex values. The values are listed in the output report on the line
headed with FAULT CURRENT.
For method two, the total instantaneous DC offset current is assumed to be equal to the total instan-
taneous AC current. This instantaneous DC offset current is decremented by the equivalent
Thevenin impedance of all paths from the fault location. The total DC offset, total rms, and total peak
current are listed following the Thevenin impedance and initial voltage on the row beginning with
the word THEVENIN.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-93
Short-Circuit Fault Analysis PSS™E-31.0
Calculating Circuit Breaker Interrupting Duty Users Manual
Fault
Ze
Ld Ld
L′ d L′ q
L″ d L″ q
T′ do T′ do
T″ qo T″ qo
L′ + L L′ + L
d e q e
T′ dz = ---------------------- T′ do T′ qz = ---------------------- T′ qo
Ld + Le Lq + Le
L″ d + L e L″ q + L e
T″ dz = ----------------------- T″ do T″ qz = ----------------------- T″
L′ d + L e L′ q + L e qo
I, ID, T'do, T"do, T'qo, T"qo, Xd, Xq, X'd, X'q, X"
where:
I Bus number. Bus I must reside in the working case with a generator table entry
assigned to it. No default is allowed.
ID One- or two-character machine identifier used to distinguish among multiple
machines at a plant (i.e., at a generator bus). ID = ’1’ by default.
T'do d axis transient open circuit time constant. No default is allowed.
T" do d axis subtransient open circuit time constant. No default is allowed.
T'qo q axis transient open circuit time constant. T'qo = 0. by default.
T"qo q axis subtransient open circuit time constant. No default is allowed.
Xd d axis synchronous reactance, entered in pu on MBASE base. No default is
allowed.
Xq q axis synchronous reactance, entered in pu on MBASE base. No default is
allowed.
X'd d axis transient reactance, entered in pu on MBASE base. No default is allowed.
X'q q axis transient reactance, entered in pu on MBASE base. X'q = 0. by default.
X" Subtransient reactance, entered in pu on MBASE base. No default is allowed.
7-94 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Calculating Circuit Breaker Interrupting Duty
Data records may be input in any order. Input is terminated with a record specifying an "I" value of
zero.
If a nonzero value is specified for JBUS, the branch designated by IBUS, JBUS and CKT must
reside in the working case as an in-service branch or multi section line grouping. The specification
of a branch is used solely for output identification purposes if several fault calculations are per-
formed at the same bus, each with a different fault duty time.
Data records may be input in any order; fault cases are calculated and reported in the same order
in which data records are read. Input is terminated with a record specifying an "IBUS" value of zero.
The calculation is launched with selection of the Fault>Circuit Breaker Interrupting Duty (BKDY)
option which displays the dialog shown in Figure 7-63.
Default fault duty time: The user specifies the time after fault application at which the decre-
mented fault current is to be calculated.
Number of levels back for contributions output: The user should specify the number of levels
away from the faulted bus for which contributions will be output. A level of zero will output contribu-
tions at only the faulted bus.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-95
Short-Circuit Fault Analysis PSS™E-31.0
Calculating Circuit Breaker Interrupting Duty Users Manual
Breaker duty data file: This file contains the machine parametric data required for the calculation
(see Section 7.9.2).
Fault specification data input file: Identifies fault locations and fault duty times required to be
investigated (see Section 7.9.3). Without this file, the user can use the usually available Select
facility shown in the figure to identify fault locations by Area, Owner, Zone, BasekV or Bus.
Once the selections have been made, the calculations will be initiated by clicking Go button. Prior
to that the user can elect to have the output printed to a Report in the Output Bar or to an identified
file selected using the I/O Control option.
• All generator buses are converted from their power flow representation to a constant
Norton current source representation (see Section 7.6.2).
• Load boundary conditions are converted from the conventional constant MVA charac-
teristic used in power flow calculations to a representation suitable for network
conditions involving abnormally low voltages.
7-96 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Calculating Circuit Breaker Interrupting Duty
The user has the option to perform a bus ordering. If not, PSS™E will do a new bus ordering of the
admittance matrix such that its sparsity characteristics are preserved. A new ordering is required
since the generator conversion process introduces a row and column into the admittance matrix for
each former type three (swing) bus.
The short-circuit current calculations employ a triangularized Y matrix network solution which is
designed for those situations where the internal flux linkages of generators are assumed to remain
unchanged as a load or fault is switched onto the system, as a line is opened or closed, or as a load
is removed.This activity is used for balanced short circuit, motor starting, voltage dip, and initial load
rejection over voltage studies; this class of studies is termed "switching studies" (see Chapter 8).
The Y matrix solution handles load boundary conditions and the "blowup" check in the same way
as the Gauss-Seidel solution method. The solution convergence monitor, the DC transmission line
monitors for two-terminal and multi-terminal DC lines, and the mismatch summary also are identical
to those of the Gauss-Seidel method.
No automatic adjustments are allowed, and switched shunt devices and DC converter transformer
tap settings are locked at their pre switching settings. A two-terminal or multi-terminal DC transmis-
sion line is blocked during the remainder of the current execution of this breaker duty calculation if,
on any iteration, the AC voltage at a rectifier converter station bus falls below 50% or is insufficient
to make margin order. Shunt elements of FACTS devices hold their pre switching reactive currents,
and series elements are held at their pre switching series voltages.
For each in-service VSC DC line, the solution starts with each converter holding the active and reac-
tive power at the time the generators were converted to the Norton equivalent. If, on any iteration,
the corresponding current exceeds the converter’s IMAX, the injection is reduced using the power
weighting factor fraction (PWF) just as in the conventional power flow solution activities. Each con-
verter is treated independently, so that any reduction at one converter does not affect the injection
at the other end of the VSC DC line. The DC transmission line monitor for VSC DC lines includes
the DC line name, followed by the AC power injection at each converter bus.
In reading the Breaker Duty Data File, a machine is treated as a salient pole machine if either T'qo
or X'q are specified as zero; a machine is treated as an induction machine if Xd = Xq and X'd = X'q;
otherwise, a round rotor machine is assumed. For any online machine in the working case for which
no data record is read, the same d and q axis currents are used in the two network solutions per-
formed for each fault case.
Note that the user can convert the generators prior to entering the circuit breaker duty calculation.
The power flow case with converted generators can be saved under a different filename for subse-
quent or frequent calculation of circuit breaker duties. The conversion is initiated using the Power
Flow>Convert>Generators (CONG) option (see Section 8.3.2). When performing the conversion,
the user can elect to use the imaginary part of the ZSOURCE (used in stability analyses) or the
ZPOS (used in unbalanced fault calculations) machine impedance.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-97
Short-Circuit Fault Analysis PSS™E-31.0
Calculating Circuit Breaker Interrupting Duty Users Manual
Regardless of the method of designating buses to be faulted, those buses which are "dummy"
buses of multi section lines are skipped as the calculation sequences through fault cases when the
multi section line reporting option is enabled.
2. Decremented complex alternating current at the specified fault duty time, again
assuming no DC offset.
The branch decremented peak DC currents in (3) above are calculated assuming that the initial DC
offset current follows from the prefault to post fault instantaneous change in current, and that the
DC offset current decays at a rate dependent upon the X/R ratio of the Thevenin equivalent of the
branch assuming "flat" conditions. Machine currents are similarly calculated, except that the
machine (plus step-up transformer if XTRAN is nonzero) impedance is used in setting the X/R ratio.
The value printed as "FAULT CURRENT" is the magnitude of the sum of the decayed change in
current of each of the above components. For reference, the final line for each faulted bus’ output
block shows as peak DC current the total instantaneous fault current decayed according to the
faulted bus’ Thevenin impedance as determined from the "flat" conditions impedance matrix. This
line also shows the Thevenin impedance (in per unit, rectangular coordinates) and prefault bus
voltage (in per unit, polar coordinates).
All currents are printed in either amps or per unit, and the complex currents in (1) and (2) above in
either rectangular or polar coordinates, according to the fault analysis output options currently in
effect (refer to Section 1.6.4). If the physical units option is enabled and the bus whose base voltage
is required for the calculation of the current has no base voltage specified for it, the current is printed
in per unit.
The output report may be extended to provide contributions up to "n" levels away from the faulted
bus. Generalizing, the selection of a positive number "n" results in output for the faulted bus, fol-
lowed by output for all buses connected to it, followed by output for all buses two buses away from
it, and so on up to "n" levels removed from the faulted bus. In reporting these remote contributions,
only the currents described in (1) and (2) above are tabulated, and a branch is only reported once:
at the end which is "closer to" (i.e., fewer levels away from) the faulted bus.
Whenever output is requested for buses more than two levels away from the faulted bus, the pro-
gram will ask the user to verify the value entered as "n":
7-98 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Calculating Circuit Breaker Interrupting Duty
the first character of their line identifiers in the branch circuit identifier column. When reporting
remote contributions, the "dummy" buses of multi section lines are neither reported nor counted in
the "levels away" calculation; i.e., the far end bus is one level removed from the "at bus".
Contributions from a three-winding transformer are identified by the winding number, the trans-
former name and the circuit identifier.
The center block of output specifies the situation at 25 milliseconds after fault initiation. Here the
AC component of current has decayed to 16239.1 A, while the DC component has decayed more
rapidly to 13996.6 A. The final output block, corresponding to 0.5 seconds with the DC component
having decayed to essentially zero, shows the expected 1.414 relationship between rms and peak
fault current, when expressed in amperes.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-99
Short-Circuit Fault Analysis PSS™E-31.0
Calculating Circuit Breaker Interrupting Duty Users Manual
( 22965.6 ) 2
( 15918.6 ) 2 + ------------------------------
FAULT DUTY TIME IS 0.025 SECONDS - ALL BREAKERS
2
Decaying
total Decaying
each path
independently
22965.6 + 15918.6 = 38884.2
7-100 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Calculating Fault Currents to ANSI Standards
Data records may be input in any order; fault cases are calculated and reported in the same order
in which data records are read. Input is terminated with a record specifying an "IBUS" value of zero.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-101
Short-Circuit Fault Analysis PSS™E-31.0
Calculating Fault Currents to ANSI Standards Users Manual
In the dialog, the user specifies the following solution and reporting options:
Transformer zero sequence impedance: If this box is checked, the zero sequence impedance of
all transformers whose actual positive sequence impedance differs from its nominal value are
scaled by the same factor as is its positive sequence impedance. If the box is not checked, all zero
sequence transformer impedances are left at their nominal values (i.e., the original values used to
establish the sequence network data). The same treatment applies to all transformers in the system
that are not at nominal impedance.
7-102 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Calculating Fault Currents to ANSI Standards
Decay factors to be applied: The user can select to include the effects of both AC and DC decay,
or only the effects of DC decay.
Resistance scaling factors (the Divisors): For branches and machines with a zero value of resis-
tance, activity ANSI assigns a non-zero resistance equal to its reactance divided by a scaling factor.
Four such factors (for positive sequence branch impedance, positive sequence machine imped-
ance, zero sequence branch impedance, and zero sequence machine impedance) are specified.
Fault specifications: Faulted buses, along with their highest operating voltages and contact
parting times, may be specified either interactively using the selector window or in an ANSI Fault
Specification Data file (see Section 7.10.1). When using the interactive approach, buses are added
to the "buses to fault" list. During the bus selection process, the Add Bus dialog allow selection of
the bus maximum operating voltage and the contact parting time (see Figure 7-66).
• Summary output in report format using only the ANSI X matrices (output fields are sep-
arated by blanks).
• Summary output in spreadsheet input format using only the ANSI X matrices (output
fields are comma delimited).
• Detailed output in report format using only the ANSI X matrices.
• Detailed output in report format using both the ANSI R and ANSI X matrices.
• Summary output in report format using both the ANSI R and X matrices (output fields
are separated by blanks).
• Summary output in spreadsheet input format using both the ANSI R and X matrices
(output fields are comma delimited).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-103
Short-Circuit Fault Analysis PSS™E-31.0
Calculating Fault Currents to ANSI Standards Users Manual
If sequence data is not contained in the working case, an appropriate error message is printed and
the calculation process is terminated.
1. An ordering for the positive sequence network is determined and the standard sum-
mary printed at the progress report output device.
2. The positive sequence decoupled admittance matrices are constructed and factorized.
3. The zero sequence network is ordered and the standard summary is printed.
4. The zero sequence decoupled admittance matrices are constructed and factorized.
If, in the process of building the sequence network admittance matrices, isolated buses are
detected, they are alarmed. The presence of isolated buses in the positive sequence network indi-
cates an improperly specified power flow case. Isolated buses in the zero sequence network,
though alarmed, are permitted and require no special treatment. The isolated bus summaries may
be terminated by entering the AB interrupt control code. When the fault analysis warning option is
disabled (see Section 1.6.4), the isolated bus tabulations are suppressed. In either case, the total
number of isolated buses in the sequence networks is tabulated.
As each fault case is calculated, its results are tabulated. The processing and reporting of the ANSI
fault current calculation process may be terminated by entering the AB interrupt control code.
• The bus number, name and base voltage of the faulted bus, along with the maximum
operating voltage and contact parting time input values.
• Three phase fault results, including symmetrical fault MVA, symmetrical fault current in
kA, asymmetrical fault current in kA, the ANSI X/R ratio, and the multiplying factor.
• Line-to-ground fault results, including symmetrical fault current in kA, asymmetrical
fault current in kA, the ANSI X/R ratio, and the multiplying factor.
• Line-to-line-to-ground fault results, including symmetrical phase current in kA, and
three times the zero sequence symmetrical fault current in kA.
• The positive sequence Thevenin impedance as obtained from the decoupled positive
sequence admittance matrices.
• The zero sequence Thevenin impedance as obtained from the decoupled zero
sequence admittance matrices.
An example of a summary report, obtained using the savnw.sav power flow case, with a fault on
Bus 151 (see Figure 7-67a).
7-104 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Calculating Fault Currents to ANSI Standards
In the detailed output, an output block for each faulted bus is printed. Voltages, currents and
apparent impedances are printed in either physical units (kV L-G, amps and ohms) or per unit, and
in either rectangular or polar coordinates, according to the fault analysis output options currently in
effect (refer to Section 1.6.4). If the physical units option is enabled and the bus whose base voltage
is required for the calculation of a quantity has no base voltage specified for it, the quantity is printed
in per unit.
For each faulted bus (i.e., at each "at bus"), the following quantities are tabulated:
1. The bus number, name, base voltage, and area number in which it resides, with the
specified maximum operating voltage listed below the bus identifiers. This is followed
by the positive sequence bus voltage for the three phase fault case, and the A phase
voltage and the three sequence voltages for the L-G case.
2. The positive and zero sequence ANSI Thevenin impedances at the fault point in per
unit, rectangular coordinates (the positive and negative sequences are identical under
the ANSI fault calculation standard).
3. The machine identifier and currents arriving at the bus from all online machines at the
bus. For the L-G fault, three times the zero sequence current (3I0) is printed.
4. The "from bus" number, name, base voltage, area number, and circuit identifier of each
non transformer branch and two-winding transformer connected to the "at bus". The
branch quantities tabulated include the current arriving at the "at bus" from the
"from bus", the apparent impedance as seen at the "from bus" looking down the line
toward the "at bus" (i.e., the V/I ratio at the "from bus"), and the ratio of apparent X/R.
For the L-G fault, zero sequence quantities are printed. Branches are printed in
ascending "from bus" numerical or alphabetical order according to the bus output
option in effect.
5. The winding number, transformer name and circuit identifier of each three-winding
transformer connected to the "at bus". The current arriving at the "at bus" from the
transformer is tabulated. For the L-G fault, zero sequence quantities are printed. Three-
winding transformers are printed in ascending transformer name order.
6. The sum of the currents output in (3), (4) and (5) above. These currents are annotated
"SUM OF CONTRIBUTIONS".
7. The fault current as calculated from the maximum operating voltage and the ANSI
Thevenin reactance or impedance, as appropriate.
The quantity shown as the sum of contributions will be essentially identical to the quantity shown
as fault current for both three phase and line-to-ground faults when fault currents and contributions
are calculated using only the ANSI X matrices. However, these quantities will normally differ when
the output is calculated using both the ANSI "R" and ANSI "X" matrices. This is due to the error intro-
duced by decoupling the complex sequence admittance matrices into pairs of real matrices, using
the real matrices to derive columns of "R" and "X" matrices (i.e., the decoupled impedance
matrices), and then coupling the columns back together to get approximations of the complex
impedance matrix columns.
Figure 7-67b shows an example of a detailed report obtained for faults on Bus 151 in the savnw.sav
power flow case.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-105
Short-Circuit Fault Analysis PSS™E-31.0
Calculating Fault Currents to ANSI Standards Users Manual
Figure 7-67. Summary and Detailed Report of ANSI Fault Calculation
7-106 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Calculating PI Equivalent for Unbalanced Switching
A series of situations where this activity would be used is shown in Figure 7-68. In this series, a line-
ground fault occurs 40% of the way down the line from bus 151 to bus 152. This is the first unbal-
ance condition. Next, the single-pole breaker at one end of the line opens the faulted phase while
the breaker at the other end of the line remains closed (stuck) for a period of time. This is the second
unbalanced condition. Finally, the second breaker opens to leave an unbalanced condition which
is with two phases closed on the line section. The user, in a stability study, may then want to simu-
late the results of such a sequence of events.
In order to be able to simulate the three unbalanced conditions, in a stability case, the user would
have to replace the positive sequence branch, in the power flow case, with a positive sequence PI
equivalent for each of the three conditions, in sequence.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-107
Short-Circuit Fault Analysis PSS™E-31.0
Calculating PI Equivalent for Unbalanced Switching Users Manual
Using the facility of the dialog the user can identify the topologies, fault locations and type and
grounding impedances to be simulated.
First the user selects the circuit on which the unbalance will be placed. In Figure 7-69 circuit #1 of
the branch from bus 151 to bus 152 has been selected.
7-108 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Calculating PI Equivalent for Unbalanced Switching
Next the user selects the type of unbalance of which there are four options:
• One phase open at both ends of the branch. With this option a "path to ground" can be
selected to be placed at any point on the line with a specified impedance.
• Two phases open. this option has no fault applications.
• In-line fault. This assumes both circuit breakers are closed. The fault can be located at
any point on the line and can be a single-line-to-ground fault, a line-to-line fault or a 3-
phase fault; with selectable fault impedance where appropriate.
• One breaker. This allows opening the branch at one end (selected by the user) and fur-
ther facilitates the application of an in-line line-to-ground fault at any point on the
branch with a selectable fault impedance.
Having made the selections, the user selects the Go button to initiate the calculation.
3. Ensure that the fault analysis modeling option setting is placed in the normal three
phase mode.
Having selected the output device and made the fault and unbalance type selections, the user
selects the Go button to initiate the calculation.
PSS™E will then prepare the power flow case for the unbalanced network solution in a manner sim-
ilar to that used at the initiation of the detailed unbalanced fault analysis described in Section 7.6.2.
Next calculates the columns of the three sequence impedance matrices corresponding to the spec-
ified buses are calculated in submatrix form.
Finally the positive sequence pi-equivalent of the branch unbalance is calculated and the results
printed in the Report window or to a file designated by the user.
1. The admittance matrix terms corresponding to the branch with the selected unbalance
present.
3. The positive sequence pi-equivalent. This is presented in the form of a branch imped-
ance (R + jX) and the equivalent line connected shunts at each end of the branch.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-109
Short-Circuit Fault Analysis PSS™E-31.0
Calculating PI Equivalent for Unbalanced Switching Users Manual
The pi-equivalent calculated may be used in dynamic simulations to model the branch unbalance.
It should replace the branch parameters used in modeling the branch without the presence of the
unbalance.
Figure 7-70 shows the output for a single-line-to-ground fault applied on the branch from bus 151
to bus 152 at a point 40% along the line from bus 151. The fault impedance is zero. Figures 7-71a
and 7-71b show diagrammatic view of the equivalent PI.
7-110 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Short-Circuit Fault Analysis
Users Manual Calculating PI Equivalent for Unbalanced Switching
151 152
0.0026 0.0460
B=1.75 B=1.75
Y=0,0 Y=0,0
151 152
0.00249 0.05390
B=0.0 B=0.0
b) Pi Equivalent for Line-Ground Fault 40% Down Line From Bus 151
Figure 7-71. Diagram View of Equivalent Pi and the Branch Power Flow Data
Siemens Power Transmission & Distribution, Inc., Power Technologies International 7-111
This page intentionally left blank.
7-112 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Chapter 8
Balanced Switching
All power system simulations assume that the system is in the steady state for an extended period
prior to the time, t. It is assumed that the first incident of interest, such as a switching operation,
fault, load change, or control setpoint change, occurs at, t. Power flow calculations apply to the
instant, t– (t minus). The power flow generator boundary conditions, therefore, assume that the
system is in the steady state, or more practically, experiencing the gentle motions of normal undis-
turbed operation. Every power flow calculation establishes the condition of the entire transmission
network, outward from generator terminals to load terminals, for an instant, t–.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 8-1
Balanced Switching PSS™E-31.0
Overview: Balanced Switching Users Manual
Generator
Internal
Flux
Linkage
t Time
Network
Variable,
(Voltage
or Current)
t Time
t– t+ Post Disturbance
Conditions Conditions Conditions
(Steady State) (Switching) (Dynamics of
System)
Any switching operation, fault, significant load change or change of control inputs (governor or exci-
tation system reference) starts the system moving. PSS™E simulations assume that high
frequency switching transients in the electric network die away very rapidly in relation to the time
durations of the transients that are of interest. The power frequency phasors representing currents
and voltages throughout the network are assumed to change instantaneously at time t.
The transients of the flux linkages in the rotors of electrical machines are of prime interest and must
be accurately accounted for. Simulations of conditions at, t+ (t plus), and later must, therefore, use
boundary conditions that recognize dynamic, rather than steady state, behavior of equipment. Both
generator and load characteristics applicable to t+ are different from those applying at t–. Loads are
commonly assumed to have a constant MVA steady-state characteristic in steady-state power flow
solutions applying to t–, but to be better modeled by a mixture of constant current and constant
impedance characteristics at t+ and later.
The instantaneous change caused by a switching is followed by a period when all generator flux
linkages, rotor angular positions, and other power plant quantities vary, as dictated by the differen-
tial equations governing their dynamic behavior.
The power flow database of PSS™E allows the entry of generator and load data pertaining to pre-
disturbance conditions at t–, to switching conditions at t+, and to system dynamic behavior over an
arbitrarily long period after the initiation of the disturbance. The user of PSS™E may then obtain a
8-2 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Balanced Switching
Users Manual Overview: Balanced Switching
solution for any of the three time regimes, steady state, switching, or dynamic behavior, by exe-
cuting appropriately selected sequences of PSS™E analytical processes.
Switching, or t+, solutions and dynamic simulations require the generator boundary conditions to be
set in accordance with the electromagnetic laws governing rotor flux linkages. Therefore, the power
flow boundary condition in which power output and bus voltage are specified, must be replaced by
a specification of a Thevenin or Norton source whose instantaneous value is determined by instan-
taneous values of flux linkages. The generator boundary conditions applying at instants, t– and t+,
are illustrated by Figure 8-2. The t+ boundary condition recognizes that generator rotor flux linkages
must obey Lenz’s and Maxwell’s laws.
Bus k
P k + jQ k
ek
~ ISORCE
t g:1 Zt
1 E int –δ
y = --------------
Z dyn -----------------
ek Z dyn
Figure 8-2. Standard Load-Flow Model and Norton Equivalent Used for
Switching and Dynamic Studies
Siemens Power Transmission & Distribution, Inc., Power Technologies International 8-3
Balanced Switching PSS™E-31.0
Objectives of a Balanced Switching Study Users Manual
3. To show the immediate change of flow that will be seen on each tie-line into an area
(before the inertial swing of rotor angles) when one such tie or a generator within the
area is tripped.
4. To show the voltage rise which occurs when a line is opened at one end. This could
separate a generation plant from the network and result in what is commonly known as
"load rejection".
A switching study is a calculation of conditions at time, t+. A switching study is, in effect, the calcu-
lation of the transmission system conditions at the first instant, t = t+, of a dynamic simulation,
separated from the subsequent calculation of conditions at later instants, t > t+. Switching study
results are presented and examined with the same output and limit checking activities as are used
in power flow work studies.
• Ensure the power flow case is solved and contains the required generator dynamic
data
• Convert the generators to a Norton Equivalent (generator boundary condition)
• Convert the loads to a voltage dependent model (load boundary condition)
These operations result in a converted power flow case which can be saved in its converted form
for subsequent switching analyses. Note that this converted case should be saved under a different
name because the conversion process is not reversible.
The generator dynamic impedance and step-up transformer parameters are not needed during load
flow solutions; they may be added to the power flow but a solved load flow case need not be
resolved after any item of generator dynamic impedance or step-up transformer is added or
changed since the dynamic impedance and step-up transformer parameters affect only the Norton
equivalent current sources, ISORCE, that will represent the generators in the post switching
calculation.
8-4 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Balanced Switching
Users Manual Preparing a Powerflow Case for Balanced Switching
The initialization of the Norton sources and changeover of boundary conditions is illustrated in
Figure 8-4. The conversion process, which initializes all source currents to correspond to the flux
linkages behind the dynamic impedance (ZSORCE or ZPOS), sets flags to cause ISORCE to be
held constant in all subsequent solutions, and changes all Type 3 buses to Type 2. The choice of
dynamic impedance is controlled during the conversion process and selected by the user.
To initiate the conversion process, the user selects the Powerflow>Convert>Generators (CONG).
This will open a dialog for electing to use ZSORCE or ZPOS (see Figure 8-3).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 8-5
Balanced Switching PSS™E-31.0
Preparing a Powerflow Case for Balanced Switching Users Manual
When the conversion process is complete, it will print a notification in the Output Bar so indicating.
8-6 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Balanced Switching
Users Manual Preparing a Powerflow Case for Balanced Switching
To launch the ordering process, the user should select the Powerflow>Solution>Order network
for matrix operations (ORDR). This, in turn will display the dialog where the user can elect to
Ignore out of service branches, (recognizes the status of network branches and ignores out-of-ser-
vice branches in determining the bus ordering), or to Assume all branches are in-service, (ignores
Siemens Power Transmission & Distribution, Inc., Power Technologies International 8-7
Balanced Switching PSS™E-31.0
Preparing a Powerflow Case for Balanced Switching Users Manual
the service status of all branches and assumes all branches connected to type one, two, or three
buses are in-service) (see Figure 8-5).
If the user elects to ignore out of service branches, when a branch previously out-of-service is
returned to service, the network has to be ordered again. Consequently, the advantage of assuming
that all branches are in service is to avoid having to re-order. However, when a large number of
branches are out-of-service, the "ignore" option might result in a more efficient matrix storage,
thereby decreasing both the time and memory required to perform calculations using the network
matrices.
8-8 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Balanced Switching
Users Manual Preparing a Powerflow Case for Balanced Switching
There are, however, two functions highlighted in Figure 8-6 which have not yet been discussed.
These are the Factorization (FACT) process and the triangularized Y matrix network solution.
These are discussed in Sections 8.3.4.1 and 8.3.4.2.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 8-9
Balanced Switching PSS™E-31.0
Preparing a Powerflow Case for Balanced Switching Users Manual
Since the process performs a computation involving the admittance matrix, it follows that it must be
re-executed any time this matrix changes and switching studies or dynamic simulations are to be
run. Thus, in these applications, the factorization process must be rerun any time one or more of
the following occurs:
Following factorization, the number of nonzero diagonal and off-diagonal terms in each factor of the
matrix are tabulated in the Output Bar.
Finally, if the factorization process detects that the network requires to be re-ordered, this is auto-
matically executed prior to the factorization.
8-10 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Balanced Switching
Users Manual Preparing a Powerflow Case for Balanced Switching
During the solution, generator buses are not treated as they are in the other PSS™E network solu-
tion methods. Rather, the type two bus voltages become "free variables" just as the voltages at type
one buses, and a fixed source current is injected into the network at each generator bus.
The load boundary conditions and the "blowup" check are handled in the same way as in the Gauss-
Seidel solution method. Further, the solution convergence monitor, the DC transmission line mon-
itors for two-terminal and multi-terminal DC lines, and the mismatch summary are identical too.
No automatic adjustments are allowed, and switched shunt devices and DC converter transformer
tap settings are locked at their pre switching settings. A two-terminal or multi-terminal DC transmis-
sion line is blocked for the remainder of the current execution of the network solution if, on any
iteration, the AC voltage at a rectifier converter station bus falls below 50% or is insufficient to make
margin order. Shunt elements of FACTS devices hold their pre switching reactive currents, and
series elements are held at their pre switching series voltages.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 8-11
Balanced Switching PSS™E-31.0
Examples of Balanced Switching Studies Users Manual
For each in-service VSC DC line, the solution starts with each converter holding the active and reac-
tive power at their values at the time the generators are converted. If, on any iteration, the
corresponding current exceeds the converter’s IMAX, the injection is reduced using the power
weighting factor fraction (PWF) just as in the conventional power flow solution activities. Each con-
verter is treated independently, so that any reduction at one converter does not affect the injection
at the other end of the VSC DC line. The DC transmission line monitor for VSC DC lines includes
the DC line name, followed by the AC power injection at each converter bus.
By default, this Y matrix solution has a convergence tolerance of 0.00001 on voltage change and a
limit of 20 iterations. A deceleration factor, which has a default value of unity, is applied to the
voltage change at each bus. For optimum convergence characteristics, it may be advantageous to
reduce the deceleration factor, especially when a large fraction of the reactive load is represented
by the constant MVA and/or current characteristics. The presence of DC lines may also require
some deceleration of the solution. The user may modify any of these solution parameters with the
data in the solution parameters data editor window.
The user should remember, as described in Figure 8-6, the Y matrix solution requires that the fac-
tors of the network admittance matrix reside in the factored matrix working file (i.e., it requires prior
factorization.
Note that the Y admittance solution method is not a power flow solution; it is unable to handle the
power flow style representation of generator buses (i.e., fixed power and voltage). But, for networks
in which generators are represented by constant internal flux linkages (i.e., following conversion),
it is capable of producing very small mismatches in only a few iterations. (Note that its default
convergence tolerance is an order of magnitude smaller than that used by the Gauss-Seidel and
Newton-Raphson solutions). It is much less sensitive to the values of branch impedances than the
other network solution activities.
8-12 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Balanced Switching
Users Manual Examples of Balanced Switching Studies
This example will open the line from bus 151 to bus 152, circuit 1, at the end terminating on bus
152, in the savnw.sav power flow case. Figure 8-9 shows the power flow diagram for these buses.
One way of performing the breaker operation, is to establish a dummy bus on the circuit from bus
151 to bus 152 which is connected to Bus 152 via a zero impedance line. To "open the breaker" it
would require taking the zero impedance line out of service (see Figure 8-10). The circuit from bus
151 to the dummy bus 999 will have the same line parameters as the actual circuit from bus 151 to
bus 152 circuit 1. When the zero impedance line between bus 999 and bus 152 is opened, circuit 1
from bus 151 will be connected at bus 151 and "hanging" open. The post-switching voltage at bus
999 is the line-end voltage of interest together with the voltage at bus 152.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 8-13
Balanced Switching PSS™E-31.0
Examples of Balanced Switching Studies Users Manual
To avoid having to pre-view the need for dummy buses, the "split bus" tool can be used. Here the
user would split bus 152 and move circuit 1 to bus 151 to a new bus automatically created by the
program and provided with its own new number by the user. The process is shown below in
Figure 8-11.
Figure 8-11. Using the Split Bus Tool to Produce an Open Line End
8-14 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Balanced Switching
Users Manual Examples of Balanced Switching Studies
The bus split will introduce a new zero impedance branch between bus 999 and bus 152. The
user will open this zero impedance line to perform the line opening. Further, the new bus; the
new line to bus 151 and the zero impedance branch will be seen in the Tree View and the Spread-
sheet View.
• First convert the power flow case and order the network buses
• Do the bus split and open the new zero impedance line to create an open ended line
• Factorize the matrix and perform the Y matrix solution
Now the voltages can be examined with a bus based report or by examining the solution shown in
the diagram.
It can be seen that immediately after switching the voltage at bus 152 drops because of the sudden
loss of incoming power and the need for greater voltage support. The voltage at bus 151 rises
slightly because, in part, of unconsumed reactive power from the open line. The line end voltage
has increased from its original level of 1.017 pu to 1.112 pu (see Table 8-1).
Following voltage regulator action, the voltage at all buses has been reduced to a new steady-state
level. The voltage at the open end is elevated but reasonable for sustained operation.
The example will assume a load at bus 3006, in the savnw.sav power flow case, to consist of two
large motors which, at full load and unity voltage, draw (7.5 + j3.95) MVA each. The starting current
for one motor is given in specification data as 2.72 times rated current at 0.275 power factor. The
calculation in Figure 8-12 shows that this starting duty corresponds to an initial shunt admittance of
(0.0625 j0.218) per unit, relative to a 100-MVA base (I = YV), and nominal voltage.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 8-15
Balanced Switching PSS™E-31.0
Examples of Balanced Switching Studies Users Manual
G + jB = 0.0625 - j0.218
The switching operation comprises the connection of the starting admittance to the case. As previ-
ously discussed, the user will convert and order the power flow case; then connect the admittance
to bus 3006 then factorize and perform the Y matrix solution. Note that the starting admittance is on
a 100 MVA base. This means that the user should add a shunt of 6.25 -j21.8 MVA which is the MVA
at 1.0 pu voltage. Figure 8-13 shows the bus based report for bus 3006.
It can be seen that the inrush is 85.6 MVA at 0.987 pu voltage. The initial voltage was 0.993 pu,
indicating a voltage dip of only less than 1.0%.
It can be seen too that the load on the bus (the other motor) was converted to 100% constant current
for real power and 100% constant admittance for reactive power.
8-16 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Balanced Switching
Users Manual Examples of Balanced Switching Studies
In the case of a three-phase fault, the switching operation which is performed before factorization
and solution is the connection of a very large reactive admittance to ground at the fault point. A
value of -j1E9 is adequate. Once a solution has been obtained for the instant, t+ output of results is
handled by the standard load flow output formats such as the bus based reports. Such a bus based
report will provide the fault point and branch information (see Figure 8-14).
i v i ∠θ i per unit
MVA ij P ij + jQ ij = MVA ij
I ij = ------------------------------- per unit
SBASE × V i
P ij + jQ ji = (0. + j0.)
MVA ji = 0.
j
v=0 MVA jk = 0.
Z f = (0. + j0.)
MVA kj = P k + Q kj
V k ∠θ k
MVA kj
I kj = --------------------------------- per unit
SBASE × V k
The format of the bus based report will be unchanged except that it will display the net current
flowing to ground at any bus whose voltage is below 0.1 per unit. This current value is expressed
in terms of fault MVA where
Siemens Power Transmission & Distribution, Inc., Power Technologies International 8-17
Because the output reports display load flow results, the current flowing in faults and branches must
be calculated from the displays of voltage and complex power or MVA flow. Current in amperes is
obtained from
MVA flow
Current = ----------------------------------------------------------------------------------- A
3 × ( Voltage, kV ) × ( 1 × 10 – 3 )
Per-unit current is obtained from
MVA flow
Current = ------------------------------------------------------------------------------------------------------------- per unit
( System Base MVA ) × ( Voltage, per unit )
The calculation of currents flowing into a bus faulted through a zero impedance is illustrated by
Figure 8-14. Because the voltage at the faulted bus is zero, the MVA flows into it are zero even
though the currents are nonzero. The currents in the branches feeding the fault must be determined
from the MVA flows and voltages at the ends that are away from the fault.
Figure 8-15 shows the output report for a fault on bus 3006, in the savnw.sav power flow case.
Output is for the faulted and two adjacent buses.
Figure 8-15. Bus Based Output for Three-phase Balanced Fault on Bus 3006
8-18 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Chapter 9
Equivalent (Reduced)
Networks
Study System A group of buses under detailed study; all components are represented explicitly.
External System A group of buses and branches that connect to and influence a study system, but do
not need to be represented in detail.
Boundary Buses Buses from which branches run into either a study system and one or more external
systems, or into more than one external system.
Source System A power system representation which contains all components of an external system
as a subset of its own components. It is used to solve for the base conditions within the
external system. The source system does not need to include the study system, but
must recognize flows between the external and study system.
Electrical An artificial group of branches and buses which represents the behavior of the external
Equivalent system as seen from its boundary buses.
Retained Bus A bus of the external system which is also a bus of the electrical equivalent. A retained
bus is not necessarily a boundary bus, but all boundary buses are retained buses.
Deleted Bus A bus of the external system which is not a bus of the electrical equivalent, but whose
effect is represented by the equivalent.
Tie Branch A branch with one end in one system (study or external) and the other end in a different
system.
Area A group of buses designated in load flow input data for interchange control purposes.
An area may, but does not necessarily, coincide with a study or external system.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 9-1
Equivalent (Reduced) Networks PSS™E-31.0
Methodology of the Electrical Equivalent Users Manual
I1 Y1 Y2 V1
= (9.1)
I2 Y3 Y4 V2
where I1 and V1 are node current and voltage at the nodes to be retained and I2 and V2 are node
current and voltage at the nodes to be deleted.
The desired form of an equivalent is an equation involving only I1 and V1 explicitly, with the I2 and
V2 variables assumed to be linearly dependent upon I1 and V1, and recognized implicitly. The
equivalent is obtained by rearranging the second row of (9.1) as
–1
V2 = Y4 ( I2 – Y3 V1 ) (9.2)
–1 –1
I1 = ( Y1 – Y2 Y4 Y3 )V 1 + Y 2 Y 4 I2 (9.3)
The first term of (9.3) specifies a set of equivalent branches and static shunt elements connecting
the retained nodes, while the second term specifies a set of equivalent currents which must be
impressed on the retained nodes to reproduce the effect of load currents at the deleted nodes.
These equivalent currents may be translated into equivalent constant real and reactive power loads
at the retained buses. The equivalent obtained by translating the two terms of (9.3) into equivalent
branches, shunts, and loads is exact in the base case for which the current vector, I2, was calcu-
lated. When voltage conditions at the boundary buses are changed, the equivalent gives an
approximation to the change in power flow into the external system. This approximation is good as
long as the changes are small, but may become unreliable when boundary bus voltages and power
flows into the external system (or its equivalent) deviate from the base values by large amounts.
An electrical equivalent is, therefore, correctly applied when it represents an external system in
which the disturbances or switching operations under study produce only minor effects; but equiv-
alents should not be applied to network segments in the close vicinity of the disturbances or
switchings.
9-2 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Equivalent (Reduced) Networks
Users Manual Defining Boundaries and Boundary Buses
An equivalent makes more efficient use of storage when the ratio of branches to buses in the equiv-
alent is reduced. The relative efficiency of different equivalents of a given system is best determined
by trial and error. As a general rule, however, reducing a system into a number of small equivalents
is more efficient than reducing of a large system in one step to produce a single equivalent.
Study Boundary
System
B 550
198 B
T 553 R
302
552 R
13 78 B T 551
B
External
77 B System
T
T Boundary
T
911 B 914 B
Boundary
D R
912 917
External
System
B = Boundary Bus D = Deleted Bus
R = Retained Bus T = Tie Branch
Figure 9-1. Separation of Complete Network into Study System and External
Systems by Boundaries
Siemens Power Transmission & Distribution, Inc., Power Technologies International 9-3
Equivalent (Reduced) Networks PSS™E-31.0
Handling DC Lines Users Manual
Three special bus type codes are used to designate boundary buses at various stages of the equiv-
alent construction processes:
Type 5 As for Type 1 (load bus); boundary bus or a bus that is not to be deleted by
equivalencing, retained bus.
Type 6 As for Type 2 (generator bus); boundary bus.
Type 7 As for Type 3 (swing bus); boundary bus.
It can be seen in Figure 9-1 that the area designated as the "Study System" there are three buses
(buses 198,78 and 77) which are the terminals of lines incoming from the other two areas and there
are four boundary buses in the external systems. If the external systems bus were to be reduced to
an equivalent network, it is possible that boundary 914 could be eliminated. But it would probably
be important for the user to retain this bus because of its strategic position in the network. Conse-
quently, it would be important to change the code of this bus, or to retain area boundary buses in
the dialog (see Figure 9-2), to represent it as a "boundary" bus to avoid having it deleted.
Several analytical processes of PSS™E change the type codes of boundary buses back and forth
between 1, 2, 3 and 5, 6, 7, respectively. The user may also change type codes manually by editing
the data in the spreadsheet view.
It is important to note that type codes 5, 6, 7 are valid only during equivalent construction and
system data processing operations. Type codes 5, 6, or 7 must be returned to 1, 2, or 3, respec-
tively, before invoking any optimal ordering, factorization, generator or load conversion, or solution
processing.
Additionally, PSS™E provides a process for the construction of network equivalents of the positive
and zero sequence networks, and calculates source impedances at equivalent source nodes for all
three sequences in preparation for the unbalanced fault analysis activities of PSS™E.
Further, PSS™E provides a boundary bus balance process which converts the mismatch at
boundary buses to equivalent load and/or generation. It is intended to be used following the removal
of a subsystem from a solved power flow case, with the flows to the deleted subsystem replaced by
load and/or generation at those retained buses which were directly connected to the removed
subsystem.
All these related processes are accessed by selection of the Powerflow>Equivalence networks
option which will display the Equivalence Networks dialog (see Figure 9-2).
9-4 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Equivalent (Reduced) Networks
Users Manual Approaching the Network Equivalent Process
As seen in the figure, there are several tabs each of which is used to initiate the various processes
cited above. The following sections will discuss these in turn.
• Buses that are designated by the user at the start of the activity.
• Buses which are indicated by type codes 6 or 7 to be boundary or retained buses.
When replacing generation with an equivalent load, the power flow solution will remain the same,
i.e. re-solving the case after the netting process will not produce a different solution.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 9-5
Equivalent (Reduced) Networks PSS™E-31.0
Approaching the Network Equivalent Process Users Manual
The user specifies the manner of selecting buses using the dialog shown in Figure 9-2 with the Net
generation with load tab selected (see Figure 9-3).
Not shown in Figure 9-3 is the usual subsystem selector where the user can select generators by
Area, Owner, Zone, BasekV or individually. What is different from most of the other subsystem
selections is that, for netting generation, the user can choose to identify those generators which will
be netted (see the "inside the selected subsystem" in the figure) or choose to identify those gener-
ators which will not be netted (see the "outside" option).
Following the specification of those buses to be netted, the program processes all type two and
three buses specified as follows:
In the savnw.sav power flow case there are three areas each of which has two generation buses.
Figure 9-4 shows the machine and load data from the spreadsheet. Note that the Load tab data has
been compressed to show the Load P and Q.
If the LIGHTCO Area is selected as the subsystem inside of which all generators will be netted, the
two generators there, on bus 206 and bus 211 will be netted. In the listing of loads, there will be two
new loads each assigned the identifier "99". If a load with the identifier "99" already exists at the
bus, an unused two-digit identifier is assigned. The two new loads are shown in the spreadsheet
view in Figure 9-5.
Prior to terminating the netting process, PSS™E prints a message in the Output Bar, or destination
of the user’s choice, stating:
9-6 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Equivalent (Reduced) Networks
Users Manual Approaching the Network Equivalent Process
Generation
Loads
Siemens Power Transmission & Distribution, Inc., Power Technologies International 9-7
Equivalent (Reduced) Networks PSS™E-31.0
Approaching the Network Equivalent Process Users Manual
If sequence data is contained in the working case, the zero sequence network is equivalenced
along with the positive sequence.
The radial equivalent process determines the buses to be equivalenced based upon their current
electrical connections. Suppose, for example, that bus "I" is a type one bus connected to two other
buses by in-service branches and that there is an out-of-service branch from bus "I" to a third bus.
Assuming that bus "I" is not in the subsystem to be exempted from equivalencing and that the "two
point" bus equivalencing option was enabled, bus "I" will be equivalenced.
It is neither necessary nor helpful to perform equivalencing of radial or "two-point" buses prior to
performing a global equivalence of a network or subsystem.
Buses which are always retained by this radial/two-point option are those:
Whenever a two-point bus and its connected branches are equivalenced, the length assigned to the
equivalent branch is the sum of the lengths of the equivalent paths. If parallel branches existed
between a retained bus and the equivalenced bus, the length of that path is assumed to be the
length of the longest of the parallel branches.
Equivalent branches, introduced by the radial equivalencing process, are assigned the circuit iden-
tifier "99". Equivalent branches between the same pair of buses have descending circuit identifiers
assigned starting at "99".
Equivalent loads introduced by the radial equivalencing process, are assigned the load identifier
"99". If a load with the identifier "99" already exists at a retained bus, the process adds any equiv-
alent load to the load already modeled as load "99". If such a load is associated with an adjustable
bus load table for which the load multiplier is zero, a mismatch is introduced at the corresponding
retained bus.
The user specifies the requirements for performing the radial equivalent using the dialog shown in
Figure 9-2 with the Equivalence radial / 2-point buses tab selected (see Figure 9-6).
9-8 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Equivalent (Reduced) Networks
Users Manual Approaching the Network Equivalent Process
Not shown in Figure 9-6 is the usual subsystem selector where the user can select buses by Area,
Owner, Zone, BasekV or individually. As in netting generation, the user can choose to identify those
buses which will be equivalenced (see the "inside the selected subsystem" in the figure) or choose
to identify those buses which will not be equivalenced (see the "outside" option).
Following the selection of equivalencing "inside" or "outside" the selected subsystem, the user has
other options.
Equivalence radial buses only: The user will check this to limit equivalencing to only
radial buses, otherwise both radial buses and those buses connected to only two other
buses are to be eliminated.
Suppress equivalence of transformers: The user will check this to exclude transformer
branches from the equivalencing process.
Suppress equivalence of zero impedance lines: If the working case contains any
branches that are treated as zero impedance lines, this can be checked to exempt from
equivalencing buses connected by such lines.
Suppress equivalence of controlled buses: This would be checked to suppress the
equivalencing of buses whose voltage or reactive power output is controlled by remote gen-
eration, switched shunts, and/or VSC DC line converters.
Suppress equivalence of mutually coupled branches: If sequence data is contained in
the working case and zero sequence mutual couplings have been specified, the user can
check this to exempt from equivalencing any branch (and the buses it connects) involved
in such a coupling.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 9-9
Equivalent (Reduced) Networks PSS™E-31.0
Approaching the Network Equivalent Process Users Manual
Suppress equivalence of area or zone boundary buses: Checking these will keep area
and zone boundaries intact.
Apply transformer impedance correction to zero sequence: If the actual positive
sequence impedance of any transformer being equivalenced differs from its nominal value,
the user can elect to specify the treatment of the zero sequence impedance of all such
transformers: If this option is checked, all zero sequence transformer impedances are left
at their nominal values (i.e., the values input to the power flow case). Alternatively, the zero
sequence impedance of each such transformer is scaled by the same factor as is its posi-
tive sequence impedance. The same treatment applies to all transformers to be equiva-
lenced.
Once the user has selected the output device, and completed the selections, all that is required is
to click the Go button in the dialog to initiate the equivalencing process.
Using the savnw.sav power flow case, and selecting to equivalence only radial buses, with all other
options suppressed, will result in the removal of one radial bus (bus 3007). The load on that bus is
moved to the neighboring buses 3005 and 3008 (see Figure 9-7).
9-10 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Equivalent (Reduced) Networks
Users Manual Creating a Network Equivalent
The equivalent constructed by PSS™E is exact in the base case from which it was calculated. It
gives an exact reproduction of the self and transfer impedances of the external system as seen from
its boundary buses. The net total of load, generation, and losses in the equivalent matches this total
in the complete external system if the bus voltages in the working case were a valid power flow solu-
tion. However, the load, generation, and loss totals in the equivalent may not individually match
those of the complete external system.
When voltage conditions at the boundary buses of the study system are changed, the equivalent
gives an approximation to the change in power flow into the external system. This approximation is
good as long as the changes are small, but may become unreliable when boundary bus voltages
and power flows into the external system (or its equivalent) deviate from the base values by large
amounts.
An electrical equivalent is, therefore, correctly applied when it represents an external system in
which disturbances or switching operations under study produce only minor effects. Equivalents
should not be applied to network segments in the close vicinity of the disturbances or switchings.
Following the selection of equivalencing "inside" or "outside" the selected subsystem, the user
specifies the following options and parameters:
Retain area boundary buses: Checking this box will keep area boundaries intact.
Retain zone boundary buses: Checking this box will keep zone boundaries intact.
Suppress equivalencing of phase shifters: Checking this box will suppress the equiva-
lencing of any two-winding transformers with a nonzero phase shift angle which are present
in the subsystem to be equivalenced.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 9-11
Equivalent (Reduced) Networks PSS™E-31.0
Creating a Network Equivalent Users Manual
If the user elects to retain two-winding transformer phase shifters, the retention of the buses
involved is forced by changing their type codes from one, two, or three to five, six, or seven, respec-
tively. Thus, the phase shifter and the buses it connects are all explicitly retained in the equivalent.
If the user chooses to equivalence two-winding transformer phase shifters, the phase shift angle is
reset to zero degrees. Additionally, an equivalent MVA load at the buses connected by the phase
shifter is introduced such that an electrical balance is retained. The phase shifter is then treated like
any other transformer.
Retain controlled buses: Checking this box will suppress the equivalencing of buses
whose voltage or reactive power output is controlled by remote generation, switched
shunts, and/or VSC DC line converters.
Retain existing branches: Checking this box will force the retention of the identity of all
non transformer branches and two-winding transformers in the power flow case connecting
buses to be retained in the equivalent. If this option is selected, the equivalent may contain
9-12 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Equivalent (Reduced) Networks
Users Manual Creating a Network Equivalent
an additional equivalent branch in parallel with any real branches between any such pair of
buses; if this option is not selected, the equivalent branch between any such pair of buses
represents the single circuit equivalent of all real branches between the buses and (possi-
bly) an equivalent branch.
Net load and shunt: Checking this box will result in netting the total equivalent load and
shunt at retained buses such that occurrences of load and shunt which "cancel out" at a
bus (e.g., positive load and negative shunts) are eliminated. The component of smaller
magnitude is set to zero with the other component set to the netted quantity. Active and
reactive components at each retained bus are processed independently. If this option is not
selected, the equivalent load and shunt components at retained buses remain as calcu-
lated by the equivalent construction matrix reduction process
Minimum generation for retaining generator buses: The user sets the positive threshold
below which type two buses will have their generation netted with the bus load and its type
code changed to one. This does not apply to boundary type two buses or area swing buses.
Both active and reactive power generation magnitudes must be below the threshold. If the
threshold specified is zero, all type two generator buses in the subsystem being equiva-
lenced are retained.
Branch threshold tolerance: The user selects this impedance tolerance above which any
equivalent branch, which is created by the equivalencing process, whose magnitude of
impedance is greater than this tolerance is not retained in the equivalent. The default value
is 10 per unit.
Once the selections are made, the user clicks the Go button and the equivalent is constructed. This
process is not sensitive to any interrupt control code options.
1. Isolating an external system in the working case. The process temporarily discards
from the open power flow case all other subsystems (study and external) contained in
the source system except the one to be equivalenced. Boundary and retained buses
are identified and, if desired, selected generators are replaced by negative load.
2. Constructing the electrical equivalent by performing the required matrix reduction oper-
ation on the external system remaining in the working case.
3. Combining system sections together to form a valid system model in the working case.
In this step, detailed representations of selected external systems are replaced with
their electrical equivalents.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 9-13
Equivalent (Reduced) Networks PSS™E-31.0
Creating a Network Equivalent Users Manual
That is, it constructs an equivalent of a subsystem of the working case with its interior type one
buses eliminated. The equivalent construction process automates many of the data handling tasks
required in preparation for, and following the execution of, the equivalent construction calculation.
It may be used whenever the entire solved source system is able to be opened in PSS™E.
The equivalent constructed resides along with the unequivalenced portions of the system in the
same form as an unequivalenced power flow case. There are normally no operations required to
combine system sections.
Only the positive sequence network is processed. If sequence data is included in the working case,
the following message is printed when initiating the process and processing continues:
In constructing the equivalent, all nonboundary type one buses in the designated external system
are eliminated, and all type five, six, and seven buses are retained as type one, two, and three
buses, respectively. Normally, the boundary buses from within the subsystem being equivalenced
are those connected to buses outside of the specified subsystem. However, when the subsystem
to be equivalenced is specified by bus only, type one and netted type two buses specified are equiv-
alenced, with the boundary buses being those buses to which they are connected and that are not
among those specified.
When three or more buses are all connected together by zero impedance lines, either all may be
equivalenced, all may be retained, or one may be retained. If the bus type codes are such that more
than one but not all the buses in such a group of buses are to be retained, an appropriate message
is printed and all buses in the group are retained.
For any bus whose voltage is being controlled by a remote generator, switched shunt, or VSC DC
line converter, an alarm is printed if the controlled bus is equivalenced while the voltage controlling
equipment is retained. The controlling equipment is then set to control local bus voltage and the
scheduled voltage setpoint or band is not changed.
For any bus with voltage controlling equipment which is being controlled by a remote switched
shunt, an alarm is printed if the controlled bus is equivalenced while the controlling switched shunt
bus is retained. The switched shunt’s control mode is not changed.
Equivalent branches created by the equivalencing process are assigned the circuit identifier "99".
Equivalent loads are assigned the load identifier "99". If a load with the identifier "99" already exists
at a retained bus, the process adds any equivalent load to the load already modeled as load "99".
9-14 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Equivalent (Reduced) Networks
Users Manual Creating a Network Equivalent
If such a load is associated with an adjustable bus load table for which the load multiplier is zero, a
mismatch is introduced at the corresponding retained bus.
There are also several two-winding transformers in the WORLD area along with generators at
buses 3011 and 3018. A plot of the area is shown in Figure 9-10.
It is to be expected that the result of creating an equivalent of the WORLD area would be to leave
the two generator buses intact, (unless the threshold for retaining generation is chosen to be greater
that their generation) and leave the boundary buses 3004, 3006 and 3008 intact. This will result in
the removal of 5 of the 10 buses. In this example, area boundary buses are retained and the gen-
eration threshold is 0.00.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 9-15
Equivalent (Reduced) Networks PSS™E-31.0
Creating a Network Equivalent Users Manual
Following the equivalencing of the WORLD area, the raw data will now appear as shown in
Figure 9-11.
It can be seen that the total load of 500 MW in the WORLD area has been retained but allocated to
the retained buses 3004, 3006, 3008 and 3011 with an identifier of "99". Note that bus 3008 already
had a load of 200 MW with an identifier of "1".
The buses at the boundaries have been maintained but now the number of buses is reduced to five.
There are now 6 new branches with in the WORLD area each with a circuit identifier of "99".
9-16 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Equivalent (Reduced) Networks
Users Manual Creating a Network Equivalent
It should be noted that the slider file (savnw.sld) which was used to create the plotted results in
Figure 9-10 will not suffice for the new power flow with the WORLD area equivalenced. Five of the
buses have been removed and new branches have been created. The user’s selected color coding
for the diagram properties will indicate that the buses and branches are "unbound", i.e., do not exist
in the power flow case. This is because the slider file no longer matches the network. A new or mod-
ified slider file will have to be produced.
Figure 9-12 shows the redrawn slider file presentation with the new branches and loads indicated.
Comparing this diagram with that of Figure 9-10 will clarify the changes in topology due to the
changes brought about by the equivalencing process.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 9-17
Equivalent (Reduced) Networks PSS™E-31.0
Creating a Network Equivalent Users Manual
Boundary buses
9-18 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Equivalent (Reduced) Networks
Users Manual Working with Boundary Bus Mismatches
It is not advisable to net all generation in an external system when constructing an equivalent in
which more than a very few buses are to be retained. Type two buses have a generally beneficial
effect on the convergence of power flow iterations and excessive netting of generation removes this
effect from the composite power flow case when the equivalent is finally put to use. It is generally
advisable to retain some major generator and synchronous condenser buses and to net the small
generators that do not contribute strongly to the regulation of system voltage.
When generator netting has taken place in constructing equivalents, it is advisable to check for the
existence of a swing (type three) bus in the working case at the completion of the equivalencing
calculation. Use the Powerflow>Check data>Buses not in swing bus tree (TREE) option.
Bus type codes of five, six, and seven are valid only during equivalent construction. All such type
codes are returned to one, two, and three, respectively, when the equivalencing process is
complete.
The values of load and shunt admittance at each retained bus in the equivalent represent both
actual and equivalent quantities at these buses. Changing these values invalidates the equivalent.
Similarly, changing the status of any branches in the equivalent invalidates it.
A power flow case containing elements introduced via an equivalent is identical in form to a power
flow case containing only real system elements and may be operated on by all PSS™E analytical
processes. It is permissible to construct an equivalent of an external system which contains an
equivalent.
The user specifies the requirements for performing the mismatch netting using the dialog shown in
Figure 9-2 with the Net boundary bus mismatches tab selected (see Figure 9-13). Note that the
subsystem selector is not shown in the figure. There, the user starts by identifying the buses to have
their mismatch netted by Area, Owner, Zone, BasekV or individually.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 9-19
Equivalent (Reduced) Networks PSS™E-31.0
Working with Boundary Bus Mismatches Users Manual
Figure 9-13. Net Boundary Bus Mismatches Dialog and Modification Options
All load and generator additions, implemented by the netting process, are tabulated at the selected
output device. The user should first select the destination; preferably a file.
In Figure 9-13, there are three options for the type of boundary condition modifications to be used:
• Model the inflow of power to the retained area as a generator and the outflow of power
as a load. A a new machine is introduced at any boundary bus at which there was a net
inflow of active power from the removed subsystem into the retained subsystem; at
boundary buses where there was a net outflow of active power, a new load is
introduced.
• Independent of the power flow at the boundary a new machine is introduced at each
boundary bus.
• Independent of the power flow at the boundary a new load is introduced at each
boundary bus.
When the user has selected the modification method and the subsystem to be treated, all that is
necessary is to click the Go button.
The selected buses are checked in ascending order of Area, Owner or Zone and in ascending order
of buses (numeric or alphabetical, depending on the current option) specified by user input. When
a bus has a mismatch in excess of 0.5 MVA, it is assumed to be a boundary bus and a new load or
machine, as selected above, is introduced.
Boundary buses are reported in ascending bus number order (under the "numbers" output option)
or alphabetical order (under the "names" output option).
When the netting process is complete, the user has given the opportunity to specify an additional
group of buses.
When a new machine is introduced at a bus, it is assigned the machine identifier "99". If a machine
"99" already exists at the bus, an unused two-digit identifier is used.
When a new load is introduced at a bus, the load is assigned the identifier "99". If a load with the
identifier "99" already exists at the bus, an unused two-digit identifier is assigned.
9-20 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Equivalent (Reduced) Networks
Users Manual Creating Short Circuit Equivalents
This process applies all of its operations to all three sequences in parallel, using the same topolog-
ical boundary definitions for each, as shown in Figure 9-14. This process handles all steps of the
equivalencing process automatically so that its single execution, in effect, accomplishes the fol-
lowing tasks:
External System
Positive Study
Sequence System
Negative
Sequence
Zero
Sequence
The short-circuit equivalencing process performs a simple network reduction without regard to
loads, transformer phase shift, or pre-event voltages. All generators in the external system are rep-
resented by simple Norton equivalents so that their effective impedances (i.e., Norton shunt
admittances) and positive-sequence source currents can be transferred to the boundary buses by
standard network mathematics. The process operates on a standard fault analysis model set up in
accordance with Section 7.2, but with FLAT pre-event voltages.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 9-21
Equivalent (Reduced) Networks PSS™E-31.0
Creating Short Circuit Equivalents Users Manual
The network reduction is performed by setting up the partitioned admittance matrix of the external
system:
Ib Y bb Y bn V b
= (9.4)
In Y nb Y nn V n
where:
The generator internal impedances, Zpos, Zneg, Zzero, where appropriate, are included in the net-
work as shunt elements and are accounted for by the diagonal terms of the admittance matrix. The
positive-sequence source currents are taken as ISORCE = (1./Zpos). The admittance matrix and
equivalent source currents of reduced network are then obtained from the elimination formula:
– 1 I ) = ( Y – Y Y – 1 Y )V
( I b – Y bn Y nn (9.5)
n bb bn nn nb b
After calculating these matrix equivalent of the reduced network, the short-circuit equivalencing pro-
cess automatically deletes the true data for the external system from the working case and replaces
it with data for the equivalent network. This equivalent network comprises:
• Branches with series impedance but no charging capacitance or shunts, and with cir-
cuit number 99.
• Equivalent generators with rating equal to system MVA base and a nonzero positive-
sequence source impedance.
• Negative- and zero-sequence source impedance for each equivalent generator.
• Positive-, negative-, and zero-sequence equivalent shunts.
This equivalent can have an equivalent generator at every boundary bus. As indicated by the left-
hand side of (9.5) the source currents of these generators are the compendium of source current
of any real generators at the boundary bus plus equivalent source currents representing the effect
of generators at deleted buses. The short-circuit equivalencing process replaces all real generators
at each boundary bus with a single equivalent generator and identifies it as such by assigning it
machine number 9. It also assigns the circuit number 99 to all equivalent branches.
All shunt admittances (charging, reactors, capacitors, etc.) arising in the equivalent, except the gen-
erator Norton admittances, are collected together and included in the equivalent as a single shunt
admittance at each boundary bus. These shunts and the generator Norton admittances are always
connected as shunts to ground when the equivalent is used within PSS™E.
The form of the equivalent is illustrated in Figure 9-15. Each sequence equivalent is contained in
the working case as fault analysis data for equivalent branches and generators. Each equivalent is
joined by real tie branches to the study system, which remains in the working case, completely
unaltered.
9-22 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Equivalent (Reduced) Networks
Users Manual Creating Short Circuit Equivalents
The generator positive- and negative-sequence source impedances in the power flow case need
not be identical. If they are different, the positive-sequence and negative-sequence reduced admit-
tance matrices will be different. The standard PSS™E negative-sequence model format recognizes
differences between positive and negative sequence only in the generator source impedances,
Zpos and Zneg.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 9-23
Equivalent (Reduced) Networks PSS™E-31.0
Creating Short Circuit Equivalents Users Manual
Real Branches
to Study
System
ISORCE ISORCE
1 1
-------------- --------------
Z pos Z pos
Real Branches
to Study System
Sequence Networks
Prior to Equivalencing
1 1 1 1
-------------- , ---------------- -------------- , ----------------
Z neg Z zero Z neg Z zero
ISORCE
Real
Branches
to Study
System
ISORCE
Equivalent Sequence
Equivalent Networks After
Source Circuits Equivalencing
1 ⁄ Z seq
Equivalent Generator
Source Impedances
9-24 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Equivalent (Reduced) Networks
Users Manual Creating Short Circuit Equivalents
The user’s first task is to select the subsystem of buses to be equivalenced. This can be done by
Area, Owner, Zone, BasekV or by individual buses using the normal Select facility. Following the
specification of the subsystem to be equivalenced, the equivalencing process alarms and termi-
nates if either none or all buses are to be retained.
In Figure 9-16, it can be seen that the user is required to complete some selections:
Apply impedance correction to zero sequence: If the actual positive sequence imped-
ance of any transformer in the subsystem to be equivalenced differs from its nominal value,
the user is free to specify the treatment of the zero sequence impedance of all such trans-
formers. If this box is checked, the zero sequence impedance of each such transformer is
scaled by the same factor as is its positive sequence impedance. Otherwise, all zero
sequence transformers are left at their nominal values (i.e., the raw data values entered to
populate the power flow case). The same treatment applies to all transformers in the sub-
system to be equivalenced which are not at nominal impedance.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 9-25
Equivalent (Reduced) Networks PSS™E-31.0
Creating Short Circuit Equivalents Users Manual
Branch threshold tolerance: The user can select this tolerance. Any equivalent branch
whose magnitude of impedance is greater than this tolerance is not retained in the equiva-
lent. The default value is 10 per unit.
Raw data output file: The user is given the option of saving the equivalents in the form of
a Power Flow Raw Data File.
Sequence data output file: The user is given the option of saving the equivalents in the
form of a Sequence Data File.
Create FLAT condition: The network must reflect classical fault analysis assumptions.
That is, a uniform voltage profile must be specified, loads must be zero, and all transform-
ers must be at zero phase shift angle. The set up of these conditions is discussed in
Section 7.4.3. The FLAT profile setup is accessible via the Fault>Setup for special fault
calculations (FLAT) option.
Convert generators: The generator source currents must be determined on the basis of
the positive sequence generator impedances and the flat generator conditions described in
(1) above. The conversion of generators is discussed in Section 8.3.2. To initiate the con-
version process, the user selects the Powerflow>Convert>Generators (CONG) option.
If these conditions are not satisfied when initiating the equivalencing process, an appropriate alarm
message is printed and the process terminated.
Identify the subsystem: The short-circuit equivalencing process works on the basis of
classical fault analysis assumptions. External systems, following the terminology of
Table 9-1, are defined when identifying the subsystem to be equivalenced. Subsequently
the process handles the data processing tasks automatically.
If sequence data is not contained in the working case, an appropriate message is printed, the equiv-
alent is constructed in the normal manner, but only the positive sequence equivalent is valid.
The equivalencing process begins by temporarily removing the portion of the power flow network
which is exempted from equivalencing. All radial and two point type one buses are equivalenced.
Next, the processing of the positive and negative sequence networks is then completed and the
zero sequence calculation commenced. A summary output of the optimal ordering function is
printed and the zero sequence network equivalent is constructed. Finally, the process is completed
by combining the equivalent and detailed system sections.
When three or more buses are all connected together by zero impedance lines, either all may be
equivalenced, all may be retained, or one may be retained. If the bus type codes are such that more
9-26 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Equivalent (Reduced) Networks
Users Manual Analyzing the Results of a Short Circuit Equivalent
than one but not all the buses in such a group of buses are to be retained, an appropriate message
is printed and all buses in the group are retained.
In constructing the equivalent, all nonboundary type one and two buses in the designated external
system are eliminated, and all type five and six buses are retained as type one or two buses,
respectively. Normally, the boundary buses from within the subsystem being equivalenced are
those which are connected to buses outside of the specified subsystem. However, when the sub-
system to be equivalenced is specified by bus only, type one and two buses specified are
equivalenced, with the boundary buses being those buses to which they are connected and which
are not among those specified.
All boundary buses that represent equivalent sources are set to type two buses with appropriate
Norton source currents and source impedances. Boundary buses with no equivalent source are set
to type one. Ground paths other than those resulting from equivalent generator impedances are
included as positive (and hence, negative) sequence shunts and zero sequence shunts.
The topology of the equivalent network is determined from the positive sequence network. As is the
case with "real system," there may be branches in the positive (and negative) sequence network
for which the zero sequence path is open.
If, in the original data, positive and negative sequence generator impedances are equal, the corre-
sponding sequence source and branch impedances in the equivalent will be identical. For
generators initially characterized by different positive and negative sequence impedances, the cor-
responding sequence source and branch impedances will differ in the equivalent. Since the fault
analysis activities of PSS™E assume that the branch impedances are identical in the positive and
negative sequence networks, the equivalent construction process gives an approximation of the
negative sequence branch impedances by using those of the equivalent positive sequence
network.
A warning message is printed any time the calculated negative sequence branch impedance differs
from the positive sequence impedance by more than 5% of the positive sequence value.
This equivalencing process is not capable of handling the case in which zero sequence mutual cou-
plings span the boundary of the external system to be equivalenced and the portion of the system
to be retained in detail. Any such mutual is alarmed, the mutual is ignored, and processing
continues.
Further, the process is not able to build an equivalent of a subsystem in which a DC line or FACTS
device is present. If any DC lines or FACTS devices are encountered, an alarm message is printed
but the process continues. Upon completion of the equivalencing process, the user should ensure
that any such DC lines and FACTS devices are blocked before using the case in any fault analysis
calculation.
An appropriate error message is printed if the number of equivalent source nodes (i.e., generators)
or branches exceeds the capacity limits of PSS™E.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 9-27
Equivalent (Reduced) Networks PSS™E-31.0
Short Circuit Equivalencing of a Power Flow Case Users Manual
The short-circuit equivalencing removes the two generator buses and original area branches. An
equivalent generator is attached to bus 151. Three new equivalent branches are created linking
buses 151, 152 and 153 (see Figure 9-18). Branch impedances are shown.
9-28 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Equivalent (Reduced) Networks
Users Manual Short Circuit Equivalencing of a Power Flow Case
Siemens Power Transmission & Distribution, Inc., Power Technologies International 9-29
Equivalent (Reduced) Networks PSS™E-31.0
Short Circuit Equivalencing of a Power Flow Case Users Manual
9-30 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Chapter 10
Open Access and Pricing
OPA requires a load flow model, which can be employed to produce a valid DC load-flow solution,
be imported into PSS™E. This model is then augmented with transaction data. Transaction data
includes transaction event definitions.
• A unique number used for reporting, for defining sequence order, and for referring to
transactions in program dialog.
• An alpha numeric label.
• Service status.
• Priority for grouping and ranking.
• A magnitude value in MW.
• A curtailment value in MW.
• A list of participating network buses.
Buses participate in a transaction as points of power injection into or demand from the power
system network. An in-service transaction of nonzero magnitude will result in power flows on trans-
mission branch elements. Load and generation input values are associated with each participating
bus. A bus participates as a power injection point when its generation value is greater than zero or
its load value is less than zero. A bus participates as a power demand point when its load value is
greater than zero or its generation value is less than zero. The injection or demand magnitude is a
function of the transaction magnitude, the load and generation values, and for some functions, the
transaction curtailment value.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 10-1
Open Access and Pricing PSS™E-31.0
Managing Transaction Data Users Manual
Transmission cost and loss allocation methods are concerned with branch ownership and control
area, respectively. The flow or loss impact of a branch is computed and accumulated by owner or
control area.
For each transaction event the user identifies which will be the participating buses. For each partic-
ipating bus, the following information is required:
Table 10-1 shows an example transaction data consisting of two transaction events.
10-2 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Open Access and Pricing
Users Manual Managing Transaction Data
Data is facilitated by selection of the Trans Access>Data… option (see Figure 10-1). This in turn
opens the Transaction Data dialog (see Figure 10-2). Note that the data is neither saved nor
retrieved with the power flow case. It is only temporarily available for the Access analyses.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 10-3
Open Access and Pricing PSS™E-31.0
Overview of Transmission Allocation Reports Users Manual
In Figure 10-2 the data from Table 10-1 has been entered. To enter, the user first "Adds" the
attribute data which is entered in the lower left dialogue area and then, with the transaction high-
lighted, enters the information on participating buses. Both attribute and bus data can be modified.
The user should remember that this data is not saved and retrieved with the power flow case.
A Vector Absolute MW-Mile (VAMM) method is used to produce the transmission embedded cost
allocation. MW-mile methods are techniques for ascribing the use of the electric power transmission
system among the various beneficiaries. These are accounting practices which rely on engineering
analysis to determine the basis. This basic accounting unit is the product of branch MW flow with
branch length.
The VAMM method determines the impact for each individual transaction event by perturbing each
bus generation associated with the event against the associated event load. For each perturbation,
the absolute value of change in branch flow (i.e., change from the initial condition power flow model)
is multiplied by the branch length in miles, and this result is accumulated in the event’s MW-Mile
vector, one entry for each branch owner of the load flow model (i.e., each facility owner) as illus-
trated in equation (10.1).
NAG j NAL i
MWM ij = ∑ ∑ ∆P l L l (10.1)
k l
where:
MWMij = MW-Mile impact for the ith owner and jth transaction event.
The aggregate MW-Mile allocation matrix may be constructed directly by using a procedure which
repeatedly perturbs the participating generation buses for each of the various transaction events,
computing the flow impact and accumulating the impacts into the appropriate matrix positions. The
aggregate matrix may also be constructed as the union of impact vectors, one for each transaction,
where these impact vectors are computed by a transaction event worksheet.
10-4 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Open Access and Pricing
Users Manual Overview of Transmission Allocation Reports
Transaction event worksheets compute an impact vector as a product of generation vector with a
coefficient matrix; a generation on MW-Mile shift factor matrix. An element of this coefficient matrix
is the sensitivity of the MW-mile impact on a facility owner to the generation output of a participating
bus. The matrix elements have units of MW-Mile per MW. The inner summation of equation (10.1)
is used to compute the elements of the generation on MW-Mile shift factor matrix, where the gen-
eration perturbation magnitude is 1.0 MW. Computing the aggregate MW-Mile allocation matrix in
this manner while more involved, provides for analyzing the impact of various generation dispatch
scenarios with the spreadsheet program. A generation vector can be selected which satisfies the
demand and minimizes the transmission cost.
The reports generated can produce information for allocating control area transmission losses
among the various transaction events. Two loss allocation methods are available, the Vector Abso-
lute MW-Ohm (VAMO) and the Vector Sum MW-Ohm (VSMO). As with the MW-Mile methods,
these MW-Ohm methods are accounting practices which rely on engineering analysis to determine
the basis. This basic accounting unit is the product of branch MW flow with branch per unit
resistance.
The computation required to produce both the VAMO and the VSMO aggregate allocation matrices
is that described in equation (10.1) modified as follows:
Siemens Power Transmission & Distribution, Inc., Power Technologies International 10-5
Open Access and Pricing PSS™E-31.0
Available Calculators Users Manual
The impact calculator produces a report which illustrates the incremental MW flow impacts on each
of the monitored elements, along with the initial available transfer capability (ATC) for the element
and a final ATC which is adjusted for the flow impact due to the transaction. For monitored inter-
faces, a value is provided which illustrates the maximum transaction magnitude that can be
supported by the element’s ATC.
10-6 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Open Access and Pricing
Users Manual Available Calculators
The user may provide the name of the Available Transmission Capacity (ATC) update file. Providing
a filename is optional. When provided, this file may modify the monitored interface ratings employed
in the report as available transfer capability (ATC). The ATC update file consists of one or more
records. Each record consists of two fields, a text field which identifies an interface by twelve char-
acter label and a numeric value field which identifies the interface ATC in MW.
Having provided the required information, the user selects Go. This will initiate the calculation the
result of which is a report of results.
The calculation uses the same linearized network model as is used in DC power flow analyses (see
Section 5.5). Thus, the comments given in that section apply here as well. Regulating in-service
phase shifting transformers hold constant MW flow.
The remainder of the report is divided into two sections. The first section reports impacts for all
monitored branches contained in the Distribution Factor Data File. The second section reports
impacts for all monitored interfaces. The selected transaction event is identified and followed by a
table of monitored elements. The transaction event identification includes: transaction event
number, transaction event label and transaction magnitude. Each record of the monitored element
table includes: a monitored element description, an initial ATC value in MW, the incremental MW
flow impact on the monitored element due to the transaction event, and a final (adjusted for incre-
mental flow) ATC value in MW. Branch RATEA values are employed as ATC values for monitored
branches. Monitored interface ATC values default to the interface RATEA and may be adjusted by
entries in the "ATC update file" if such a file was requested by the user.
For monitored branches the monitored element description consists of: "from bus" number and
name, "to bus" number and name, and circuit id. For monitored interfaces the twelve character mon-
itored element label is employed as the monitored element description.
The monitored interface table includes an additional column of numeric values. These values
illustrate the transaction magnitude, in MW, which would result in a final ATC value of zero for that
Siemens Power Transmission & Distribution, Inc., Power Technologies International 10-7
Open Access and Pricing PSS™E-31.0
Available Calculators Users Manual
element. This maximum transaction field will take a value only when the initial ATC and incremental
flow values are of the same sign and when the incremental flow value magnitude significantly
exceeds zero.
Using the savnw.sav power flow case and the associated data files (savnw.sub/.mon/.con), all of
which are available in the PSSE/EXAMPLE directory in the user’s installation, an example case is
run using Transaction #6 described in Figure 10-2. The report generated by the impact calculation
is shown in Figure 10-5.
The user may specify the desired MW flow increment on a monitored element. This incremental flow
value may, for example, represent the amount by which the element is overloaded. The line loading
relief calculator will report adjustments to transaction magnitudes required to satisfy this incre-
mental flow. These transaction adjustments may be limited to transaction curtailment (i.e.,
increases in transaction curtailment value magnitude not to exceed the transaction magnitude
value) or transaction restoration (i.e., decreases in transaction curtailment value magnitude).
Transactions participate in adjustment as a function of their transaction priority and the applied
adjustment method. Four adjustment methods are available: first in last out, decreasing order by
distribution factor magnitude, pro rata by distribution factor magnitude, and pro rata by the product
of distribution factor with transaction schedule (transaction magnitude less curtailment). Transac-
tions are excluded from adjustment when their distribution factor magnitude is less than a user-
specified tolerance. Individual events are grouped by priority. The curtail transactions function pro-
ceeds to investigate the priorities from lowest to highest priority number until the incremental flow
target is satisfied or all transaction priority groups are exhausted. The restore transactions function
10-8 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Open Access and Pricing
Users Manual Available Calculators
proceeds to investigate the priorities from highest to lowest priority number until the incremental
flow target is satisfied or all transaction priority groups are exhausted.
The user’s first requirement is to Identify the name of a Distribution Factor Data file constructed as
described in Section 5.2.2.1 or to initiate the construction of such a file. The file should correspond
to the network condition contained in the power flow case and to the desired Linear Network Anal-
ysis Data Files. The bus input option must have the same setting that was in effect when the data
file was constructed.
When the distribution factor file is identified, the monitored element list (from the savnw.mon file) is
tabulated in the window.
The user is next presented with a menu prompting for a selection among three functions: curtail
transactions, report distribution factor matrix and restore transactions.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 10-9
Open Access and Pricing PSS™E-31.0
Available Calculators Users Manual
After selecting a target element and defining the incremental flow target the user needs to select an
adjustment method association. Four transaction event adjustment methods are available:
Individual events, whose distribution factors exceed a tolerance, are grouped by priority. The curtail
transactions function investigates the priorities from lowest to highest priority number until the incre-
mental flow target is satisfied or all transaction priority groups are exhausted. The restore
transactions function investigates the priorities from highest to lowest priority number until the incre-
mental flow target is satisfied or all transaction priority groups are exhausted.
10-10 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Open Access and Pricing
Users Manual Available Calculators
The calculation produces a report of transaction adjustments and the effect of each on the target
monitored element. The transaction event curtailment values are updated by the reported
adjustments.
The line loading relief calculation uses the same linearized network model as is used in DC power
flow analyses (see Section 5.5). Thus, the comments given in that section apply here as well. Reg-
ulating in-service phase shifting transformers hold constant MW flow.
Transaction events may be adjusted by the curtailment or restoration functions when their distribu-
tion factor magnitudes exceed the distribution factor tolerance and are of the correct sign with
respect to the sign of the adjustment MW value (e.g., having opposite sign for curtailment and the
same sign for restoration).
When performing curtailment, the adjustment magnitude limit for each transaction event is equal to
the transaction event magnitude less the initial curtailment magnitude. When performing restoration
the adjustment magnitude limit for each transaction event is equal to the initial transaction event
curtailment magnitude. Adjustments resulting from the curtailment and restoration functions update
the transaction event curtailment magnitude.
The distribution factor values of the matrix represent the sensitivity of monitored element MW flow
to transaction event magnitude. A positive value indicates that the monitored element flow will
increase with increasing transaction event magnitude.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 10-11
Open Access and Pricing PSS™E-31.0
Making Allocations Users Manual
• Determine the MW-mile impacts of all transaction events on all transmission facility
owners.
• Determine the active power generation on MW-mile shift factors of an individual event
on all transmission facility owners.
• Determine the MW-ohm impacts of all transaction events on all control areas.
• Determine the active power generation on MW-ohm shift factors of a individual event
on all control areas.
• Report the total branch mileage of each transmission facility owner.
The Vector Absolute MW-Mile method is employed as required by the Public Utility Commission of
Texas for computing the "impact fee" (see PUCT Substantive Rule 23.67, Open-Access Compa-
rable Transmission Service, and PUCT Substantive Rule 23.70, Terms and Conditions of Open-
Access Comparable Transmission Service).
10-12 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Open Access and Pricing
Users Manual Making Allocations
The user is presented with a menu prompting for a selection among five reports, including:
When selecting Vector Absolute MW-mile, Vector Absolute MW-ohm or Vector MW-ohm, the user
has only to select the output device.
For import to a spreadsheet program, the reports include an initial record of text fields for use as
column headings in a spreadsheet table. The first field of each subsequent record provides a row
label. All other fields are numeric data.
The report can be printed on a Report tab on the interface or to a file of the user’s choice. The report
contains only the branch mileage summary by owner.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 10-13
This page intentionally left blank.
10-14 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Chapter 11
Performing PV/QV Analyses
11.1 Overview
The PV/QV analyses that are described in this chapter are designed for studies of slow voltage sta-
bility, which could be analyzed as a steady-state problem. They are load flow based analyses used
to assess voltage variations with active and reactive power change. Two methods are used to deter-
mine the loading limits imposed by voltage stability under the steady-state conditions.
The PV/QV analyses do not provide solutions to specific problem but function as tools that can be
directed by the user to perform analyses in the solution of problems associated with the steady-
state voltage stability of power systems.
1. Open an existing data file containing network data (*.raw, *.sav) by selecting
File>Open from the Main Menu.
3. Enter and select the PV analysis options you want for your calculation:
Solution options: Select solution options for the series of load flow calculations per-
formed to obtain the PV curves. The contingency-case solution options allow for a dif-
ferent set of automatic adjustments of the contingency cases than those used in the
base case solutions. For more information, please refer to Chapter 4 of the Program
Operation Manual, Volume I.
Solution Engine: Select the solution engines for the series of load flow calculations
and contingency studies to obtain the PV curves please refer to Chapter 4 of the
Program Operation Manual, Volume I.
Var Limit Code: Select the var control options limit code for contingency case initial
power flow solution and subsequent transfer increment cases. The var limit control can
be set to apply immediately to limit the var output of all generators, or to ignore var limit
at initial iterations and then apply automatically afterwards.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 11-1
Performing PV/QV Analyses PSS™E-31.0
How to Perform PV and QV Analysis in PSS™E Users Manual
Figure 11-1. PV Analysis Dialog
11-2 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Performing PV/QV Analyses
Users Manual How to Perform PV and QV Analysis in PSS™E
4. Transfer Dispatch Methods: Dispatch codes for study and opposing dispatch calcu-
lations in PV analysis.
- Dfax generation: Participating buses and their participation factors are taken from
the DFAX file for buses in the subsystem with one or more in-service machines
whose active power generation is positive.
- Dfax load: Participating buses and their participation factors are taken from the
DFAX file for buses in the subsystem with one or more in-service loads whose con-
stant MVA load active power is positive.
- Dfax generation or load: Participating buses and their participation factors are
taken from the DFAX file for buses in the subsystem with either one or more in-ser-
vice machines whose active power generation is positive, or one or more in-service
loads whose constant MVA load active power is positive. If both generation and
load meeting the above criteria are present at a bus, the generation is dispatched
if the bus is in the study subsystem, and the load is dispatched, if the bus is in the
opposing subsystem.
- Subsystem load: Participating buses are subsystem buses with one or more in-
service loads whose constant MVA load active power is positive; each bus' partic-
ipation factor is the total of its positive active power constant MVA load.
- Subsystem machines (MW): Participating buses are subsystem buses with one
or more in-service machines whose active power generation is positive; each bus'
participation factor is the total of the active power generation of its machines with
positive active power generation.
- Subsystem machines (MBASE): Participating buses are subsystem buses with
one or more in-service machines whose active power generation is positive; each
bus' participation factor is the total of the MBASEs of its machines with positive
active power generation.
- Subsystem machines (Reserve): Participating buses are subsystem buses with
one or more in-service machines whose active power generation is positive; each
bus' participation factor is the total of the reserve (PT-PG) of its machines with pos-
itive values of both active power generation and reserve.
- Subsystem machines (ECDI): Participating buses are subsystem buses with one
or more in-service machines specified in the Economic Dispatch Data File;
machines participate in the transfer based on an equal incremental cost dispatch
as implemented by activity ECDI.
Mismatch tolerance (MW and Mvar): Specify mismatch tolerance. This tolerance will
be used to check for largest initial active or reactive power mismatch. If exceeded the
process is terminated. This value is also used as the convergence tolerance in the
power flow solution of each contingency and transfer increment case; please refer to
Chapter 4 of the Program Operation Manual, Volume I.
Initial transfer increment (MW): Specify the starting transfer increment value. This
value will be the initial transfer increment step size in MW between the two defined sub-
systems.
Transfer increment tolerance (MW): Specify the largest acceptable difference in
transfer level between a transfer level for which a solution is found and a higher transfer
level which fails to achieve convergence.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 11-3
Performing PV/QV Analyses PSS™E-31.0
How to Perform PV and QV Analysis in PSS™E Users Manual
1. The distribution factor input data file (*.dfx). For more information on the distribution
factor input data file, please refer to Chapter 4 of the Program Operation Manual,
Volume I.
2. The output file (results)(*.pv). The results of the PV calculation will be stored in the file
specified in this field. The results file is provided so that you may view the PV calcula-
tion results at a later time by simply selecting the output results file rather than re-
running the PV calculations.
Enter and select the parameters that apply and click the Go button to start the PV calculations.
Select Cancel to close the window and return. The results window for PV analysis will be displayed
(see Figure 11-2).
11-4 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Performing PV/QV Analyses
Users Manual How to Perform PV and QV Analysis in PSS™E
Select the type of graph you wish to plot and select the items of interest in the list provided:
Bus voltages: Plots bus voltages against incremental power transfer of selected base
case or contingencies.
Generator MW: Plots generator MW output against incremental power transfer of selected
base case or contingencies.
Branch MVA Flow: Plots branch MVA against incremental power transfer of selected base
case or contingencies.
Interface MW Flow: Plots interface MW against incremental power transfer of selected
base case or contingencies.
Bus voltage against interface flow: Plots the selected bus voltage against interface flow.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 11-5
Performing PV/QV Analyses PSS™E-31.0
How to Perform PV and QV Analysis in PSS™E Users Manual
Items in the list may be selected individually or as a continuous set. To select individual items, left-
click on the item you want to select. Hold the [Ctrl] key down while clicking the left mouse button to
select the additional items. To select continuous items, hold the [Shift] key down while clicking the
left mouse button.
Select the Graph button to plot the graphs. The graphs will be displayed as shown in Figure 11-3.
Graph axis's parameters are fully adjustable. To adjust parameters such as decimal places and axis
labels, left-click on the axis of interest. The Scale Values dialog is displayed in Figure 11-4 and
Figure 11-5 for both vertical and horizontal axes:
Values: Specify a top value and bottom values of the axes. These values can be adjusted
based in grid step size if Adjust to grid step is checked. Select the start point of the grid
step. If undefined then grid step will start from bottom. Select grid step method either by
step value or defined the number of values required on the axes.
11-6 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Performing PV/QV Analyses
Users Manual How to Perform PV and QV Analysis in PSS™E
View (not real values): Select the graphs display options in this section. The changes will
be reflected on the sample display on the left.
The Scale Values dialogs are displayed in Figure 11-4 and Figure 11-5 for both vertical and hori-
zontal axes.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 11-7
Performing PV/QV Analyses PSS™E-31.0
How to Perform PV and QV Analysis in PSS™E Users Manual
To change the visual parameters of the graph area, left-click on the graph area. The Graph Area
Visual Parameters dialog will be displayed (see Figure 11-6).
11-8 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Performing PV/QV Analyses
Users Manual How to Perform PV and QV Analysis in PSS™E
Select the color and line style for the axes, the grid lines, the border and background area. When
finished, select the OK button. The graph view will be displayed with your updated selections.
• Place a check mark in the box labeled Use different line styles to print each selected
item plot in a different line style. This will ensure line clarity on non-color printers.
• Place a check mark in the box labeled Numbers on the lines to label each selected
item plot for identification.
• Select the Print button to send the graph to a standard Windows® default printer. The
Printer Selection dialog will be displayed to allow selection of an appropriate printer.
To retrieve results from a previous PV analysis, select Solution>PV previous results. The PV
Analysis – Parameters window is displayed. Select a PV analysis output file by clicking the Select…
button. Choose the output file of interest and select Open. Parameters used for the select PV anal-
ysis will be shown. These values are for reference only and are not editable. Select Show
Results… to display the results window (see Figure 11-2).
1. Open an existing data file containing network data (*.raw, *.sav) by selecting
File>Open from the Main Menu.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 11-9
Performing PV/QV Analyses PSS™E-31.0
How to Perform PV and QV Analysis in PSS™E Users Manual
Figure 11-7. QV Analysis Dialog
11-10 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Performing PV/QV Analyses
Users Manual How to Perform PV and QV Analysis in PSS™E
3. Enter and select the QV analysis options you want for your calculation:
Tap adjustment: Select transformer tap adjustment options for the series of load flow
calculations performed to obtain the QV curves, please refer to Chapter 4 of the
Program Operation Manual, Volume I.
Area Interchange control: Select area interchange control options for the series of
load flow calculations performed to obtain the QV curves, please refer to Chapter 4 of
the Program Operation Manual, Volume I.
Solution options: Select solution options for the series of load flow calculations per-
formed to obtain the QV curves, please refer to Chapter 4 of the Program Operation
Manual, Volume I.
Solution engine: Select the solution engines for the series of load flow calculations
and contingency studies to obtain the QV curves, please refer to Chapter 4 of the
Program Operation Manual, Volume I.
VAR Limit Code: Select the var control options limit code for contingency case initial
power flow solution and subsequent transfer increment cases. The var limit control can
be set to apply immediately to limit the var output of all generators, or to ignore var limit
at initial iterations and then apply automatically afterwards.
Mismatch tolerance (MW and Mvar): Specify mismatch tolerance. This tolerance will
be used to check for largest initial active or reactive power mismatch. If exceeded the
process is terminated. This value is also used as the convergence tolerance in the
power flow solution of each contingency case; please refer to Chapter 4 of the Program
Operation Manual, Volume I.
Initial (maximum) per unit voltage setpoint at study bus (VHI): Specify the maxi-
mum voltage of study bus.
Minimum per unit voltage setpoint at study bus (VLO): Specify the minimum volt-
age of the study bus.
Per unit voltage setpoint decrement (positive) at study bus (DLTAV): Specify the
voltage increment size from VLO to VHI.
In order to begin calculations, the bus number and two data files are required:
1. The distribution factor input data file (*.dfx). For more information on the distribution
factor input data file, please refer to Chapter 4 of the Program Operation Manual,
Volume I.
2. The output file (results)(*.qv). The results of the QV calculation will be stored in the file
specified in this field. The results file is provided so that you may view the QV calcula-
tion results at a later time by simply selecting the output results file rather than re-
running the QV calculations.
Enter and select the parameters that apply and click the Go button to start the QV calculations.
Select Cancel to close the window and return. The results window for QV analysis will be displayed
(see Figure 11-8).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 11-11
Performing PV/QV Analyses PSS™E-31.0
How to Perform PV and QV Analysis in PSS™E Users Manual
Figure 11-8. QV Analysis Results Window: Calculation Results
11-12 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Performing PV/QV Analyses
Users Manual How to Perform PV and QV Analysis in PSS™E
Select the base case and/or contingencies. Items in the list may be selected individually or as a con-
tinuous set. To select individual items, left-click on the item you want to select. Hold the [Ctrl] key
down while clicking the left mouse button to select the additional items. To select continuous items,
hold the [Shift] key down while clicking the left mouse button.
Select the Show Graphs button to plot the graphs. The graphs will be displayed as shown in
Figure 11-9.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 11-13
Performing PV/QV Analyses PSS™E-31.0
How to Perform PV and QV Analysis in PSS™E Users Manual
Figure 11-9. QV Analysis Results Window: Graph Results
11-14 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Performing PV/QV Analyses
Users Manual How to Perform PV and QV Analysis in PSS™E
Graph axes parameters are fully adjustable. To adjust parameters such as decimal places and axis
labels, left-click on the axis of interest. The Scale Values dialog is displayed as in Figure 11-10.
To change the visual parameters of the graph area, left-click on the graph area. The Graph Area
Visual Parameters dialog will be displayed (see Figure 11-11).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 11-15
Performing PV/QV Analyses PSS™E-31.0
How to Perform PV and QV Analysis in PSS™E Users Manual
Select the color and line style for the axes, the grid lines, the border and background area. When
finished, select the OK button. The graph view will be displayed with your updated selections.
• Place a check mark in the box labeled Use different line styles to print each selected
item plot in a different line style. This will ensure line clarity on non-color printers.
• Place a check mark in the box labeled Numbers on the lines to label each selected
item plot for identification.
• Select the Print button to send the graph to a standard Windows® default printer. The
Printer Selection dialog will be displayed to allow selection of an appropriate printer.
To retrieve results from a previous QV analysis, select Solution>QV previous results. The QV
Analysis – Parameters window is displayed. Select a QV analysis output file by clicking the
Select… button. Choose the output file of interest and select Open. Parameters used for the select
QV analysis will be shown. These values are for reference only and are not editable. Select Show
Results… to display the results window (see Figure 11-8).
11-16 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Performing PV/QV Analyses
Users Manual Basic Engineering Guide to PV and QV Curves Applications
11.3.1 Objective
The objective of a PV and QV curves is to determine the ability of a power system to maintain
voltage stability at all the buses in the system under normal and abnormal steady state operating
conditions. They are useful, for example:
• To show the voltage collapse point of the buses in the power system network.
• To study the maximum transfer of power between buses before voltage collapse point.
• To size the reactive power compensation devices required at relevant buses to prevent
voltage collapse.
• To study the influence of generator, loads and reactive power compensation devices
on the network.
The PV and QV curves are obtained through a series of AC load flow solutions. The PV curve is a
representation of voltage change as a result of increased power transfer between two systems, and
the QV curve is a representation of reactive power demand by a bus or buses as voltage level
changes.
This can be demonstrated using a simple two terminals network as in Figure 11-12. From reference
P. Kundur, Power System Stability and Control, McGraw-Hill 1994, the power flow relationship
between the source and the load can be summarized by equations (11.1) and 11.2).
Z LD ⎛ E s ⎞ 2
P R = V R I cos φ = ----------- ⎜ -----------⎟ cos φ (11.1)
F ⎝ Z LN⎠
Siemens Power Transmission & Distribution, Inc., Power Technologies International 11-17
Performing PV/QV Analyses PSS™E-31.0
Basic Engineering Guide to PV and QV Curves Applications Users Manual
1 Z LD
V R = -------- ----------- E S (11.2)
F' Z LN
where:
⎛ Z LD⎞ 2 ⎛ Z LD⎞
F = 1 + ⎜ -----------⎟ + 2 ⎜ -----------⎟ cos ( θ – φ )
⎝ Z LN⎠ ⎝ Z LN⎠
The loading of the network can be increased by decreasing the value if ZLD. This is done with Es,
load power factor and line parameters fixed. From equation (11.1), as ZLD is decreased gradually
the load power, PR, increases, hence the power transmitted will increase. As the value of ZLD
approaches ZLN the value of PR starts to decrease gradually due to F. However, from equation
(11.2) as ZLD decreases the receiving voltage VR decreases gradually.
The plot of the relationship between voltage at the receiving end, VR, and the load power, PR, as
the power transfer is increased due to increase loading, gives the PV curves similar in characteristic
to the curve shown in Figure 11-13.
PV curves are typically used for the "knee curve analysis". It is as named because of its distinctive
shape at the point of voltage collapse as the power transfer increases, as shown in Figure 11-13.
Depending on the transfer path, different buses have different knee point. The buses closer to the
transfer path will normally exhibit a more discernible knee point.
Voltage instability occurs at the "knee point" of the PV curve where the voltage drops rapidly with
an increase in the transfer power flow. Load flow solution will not converge beyond this limit, indi-
cating voltage instability. Operation at or near the stability limit is impractical and a satisfactory
operating condition must be ensured to prevent voltage collapse.
In PSS™E, the PV curves are generated by selecting two subsystems where the power transfer
between the subsystems is incremented in a defined step size for a series of AC load flow calcula-
tions while the bus voltages, generator outputs and the branch flows of the system are monitored.
When the bus voltages are plotted as a function of the incremental power transfer the PV curves
are obtained. One of the subsystems in the study must be defined as the study (source) system and
11-18 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Performing PV/QV Analyses
Users Manual Basic Engineering Guide to PV and QV Curves Applications
another as the opposing (sink) system. The power flows from the study subsystem to the opposing
subsystem.
Figure 11-14 shows the PV curves of a bus 203 in an example network under normal and various
contingency conditions. The maximum transfer limit for this bus in base case is approximately 750
MW. The maximum transfer limit decreases under contingency conditions. The response shown is
expected since under network contingencies the loading of the line will increase. These curves can
be used to set transfers or local generation dispatch so that the system will not fall below the knee
point following a disturbance (i.e., loss of lines).
The PV curves for different buses under the same network conditions (base case or contingency)
can also be plotted in the results window as shown in Figure 11-15. The plots of three different
buses in base case indicate that the "knee point" is below the 90% of the nominal voltage and the
transfer limit is approximately 750 MW. However, this transfer limit is not reasonable as voltages
below 90% will cause motors in the system to stall. The transfer limit should be set for voltages in
the vicinity of 95% of the nominal voltage.
The distribution of generations between the generators in the system as a result of the power
transfer can be observed by analyzing their relationship as shown in Figure 11-16.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 11-19
Performing PV/QV Analyses PSS™E-31.0
Basic Engineering Guide to PV and QV Curves Applications Users Manual
11-20 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Performing PV/QV Analyses
Users Manual Basic Engineering Guide to PV and QV Curves Applications
Siemens Power Transmission & Distribution, Inc., Power Technologies International 11-21
Performing PV/QV Analyses PSS™E-31.0
Basic Engineering Guide to PV and QV Curves Applications Users Manual
QV curves are used to determine the reactive power injection required at a bus in order to vary the
bus voltage to the required value. The curve is obtained through a series of AC load flow calcula-
tions. Starting with the existing reactive loading at a bus, the voltage at the bus can be computed
for a series of power flows as the reactive load is increased in steps, until the power flow experi-
ences convergence difficulties as the system approaches the voltage collapse point.
Figure 11-17 is a typical of the QV curves that will be generated for a system that is stable at mod-
erate loading and unstable at higher loadings.
11-22 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Performing PV/QV Analyses
Users Manual Basic Engineering Guide to PV and QV Curves Applications
The bottom of the QV curve, where the change of reactive power, Q, with respect to voltage, V (or
derivative dQ/dV) is equal to zero, represents the voltage stability limit. Since all reactive power
compensator devices are designed to operate satisfactorily when an increase in Q is accompanied
by an increase in V, the operation on the right side of the QV curve is stable, whereas the operation
on the left side is unstable. Also, voltage on the left side may be so low that the protective devices
may be activated.
The bottom of the QV curves, in addition to identifying the stability limit, defines the minimum reac-
tive power requirement for the stable operation. Hence, the QV curve can be used to examine the
type and size of compensation needed to provide voltage stability. This can be performed by super-
imposing the QV characteristic curves of the compensator devices on that of the system. For
instance the capacitor characteristic can be drawn over the system's QV curves as shown in
Figure 11-18.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 11-23
Performing PV/QV Analyses PSS™E-31.0
Basic Engineering Guide to PV and QV Curves Applications Users Manual
Figure 11-19 shows the QV curves for a range of capacitor banks with different rating super-
imposed on the system's QV curves under different loading conditions. From the plot we can deter-
mine that capacitor rating of 300 Mvar is required to maintain 1 pu voltage at loading of 1300 MW,
450 Mvar at 1500 MW and so on.
For the case of very high loading at 1900 MW, even though the capacitor bank rating of 950 Mvar
can maintain a voltage of 1 pu, point B is not a stable operating point. If there is a drop in voltage
from point B to B', the ability of the capacitor to supply reactive power is decreased more than the
drop in requirement of the system. This will result in continuous drop in voltage. Alternatively, if the
voltage is increased above point B, the capacitor will supply more reactive power than the increase
in requirement of the system. This will result in continuous rise in voltage.
Hence, the criterion for stable operating point when using a reactive power compensator is as
follow:
dQ/dV is the change of the system's reactive power, Q, with respect to voltage, V.
dQcomp/dV is the change of the compensator's reactive power output, Qcomp,
with respect to voltage, V.
For the case of light loading at 1300 MW with capacitor rating of 300 Mvar, point A is a stable oper-
ating point. If the voltage is increased from point A to A', the capacitor will supply less reactive power
than the increase in system's demand, hence reducing the voltage to 1 pu. Alternatively, if the
voltage is decreased from point A towards the bottom of the QV curve, the capacitor will supply
more reactive power than the system's demand, hence returning the voltage to 1 pu.
11-24 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Performing PV/QV Analyses
Users Manual Basic Engineering Guide to PV and QV Curves Applications
In PSS™E, the QV curves are generated by artificially introducing a synchronous condenser, with
high reactive power limits, at a bus to make this a PV bus. As the scheduled voltage set point (bus
voltage) of the PV bus is varied in steps for a series of AC load flow calculations, the reactive power
output from the condenser is monitored. When the reactive power is plotted as a function of the bus
voltage a QV curves are obtained.
QV curves are commonly used to identify voltage stability issues and reactive power margin for spe-
cific locations in the power system under various loading and contingency conditions. The QV
curves are also used as a method to size shunt reactive compensation at any particular bus to main-
tain the required scheduled voltage.
Figure 11-20 shows QV curves for bus 203 in an example network. From the curves we can deter-
mine the reactive power required to hold the desired scheduled voltage in the base case and under
various contingencies. In this example, the reactive power required is approximately 110 Mvar to
hold the scheduled voltage at bus 203 at 1.0 pu in the base case.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 11-25
Performing PV/QV Analyses PSS™E-31.0
Basic Engineering Guide to PV and QV Curves Applications Users Manual
Figure 11-20. QV Curves under Various Contingencies for Bus 103
11-26 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Performing PV/QV Analyses
Users Manual Basic Engineering Guide to PV and QV Curves Applications
Figure 11-21 show the QV curves of bus 103 in base case under higher loading conditions. It is
observed that the demand for reactive power to hold the scheduled voltage at 1.0 pu increases with
loading.
There are no functions in PSS™E QV Analysis that allow super-imposing of compensator QV char-
acteristics over that of the system. However, this can be performed using IPLAN or Python
programming tools.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 11-27
Performing PV/QV Analyses PSS™E-31.0
Basic Engineering Guide to PV and QV Curves Applications Users Manual
Figure 11-21. QV Curve in Base Case with Increase in Load on Bus 103
11-28 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Performing PV/QV Analyses
Users Manual Basic Engineering Guide to PV and QV Curves Applications
The shape of the QV curves can also be used to determine the load characteristic, and study the
effect of load tap changer (LTC) transformer on the system. Figure 11-22 shows the QV curve on
bus 108 of the example system. The load on the bus 108 is of constant current type controlled by
a LTC transformer. It is observed that the QV curves are slightly shaped like an 'S'. The S-shape
characteristics are due to the load type in the system and the action of the LTC transformer as illus-
trated in Figure 11-23.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 11-29
Performing PV/QV Analyses PSS™E-31.0
Basic Engineering Guide to PV and QV Curves Applications Users Manual
Figure 11-22. S-Shaped QV Curve on Bus 108
11-30 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Performing PV/QV Analyses
Users Manual How to Implement a Specific PV Transfer
Figure 11-23. QV Curves for Different Load Type with Consideration of LTC
1. Open the Saved Case File containing the power flow case on which the transfer is to
be imposed by selecting the File>Open menu entry. Normally, the same Saved Case
File on which an earlier PV analysis calculation had been performed is specified.
3. Specify the same Distribution Factor Data File, "source" and "sink" systems, and
transfer dispatch method data as was specified in the earlier PV analysis calculation.
The implement PV transfer function then changes the generation or load, as appropriate, at those
subsystem buses participating in the transfer.
Details on the transfer may be examined using the Powerflow Cases tab of the File>Compare…
menu entry.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 11-31
Performing PV/QV Analyses PSS™E-31.0
How to Implement a Specific PV Transfer Users Manual
Figure 11-24. Implement PV Transfer Dialog
11-32 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Chapter 12
Program Automation
• As a program extension. In this case the user, in the course of using the program inter-
actively, can decide to select an existing Automation File as the next instruction to the
program.
• For un-attended execution. This is commonly called batch execution. In this case the
entirety of the user’s interaction would be the specification of the source of the instruc-
tions for it to execute (although there may be other options specified at the same time).
Although there are a few minor exceptions, for the most part the specification of the instructions, i.e.
the contents of the Automation File, is the same in both cases.
The following sections will concentrate on the first alternative. Near the end of the chapter is a sec-
tion on batch execution. There is also a section on entering single commands; while not a program
automation method it uses the commands defined here and is best understood in this context.
In most cases the API manual will also describe the syntax for calling an equivalent Fortran
subroutine.
Siemens PTI will support users who make use of the API through the automation methods
described here, such as batch commands and Python programs, only. No support is provided
for Fortran or, say, C applications developed by users of PSS™E.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 12-1
Program Automation PSS™E-31.0
Automation Methods in PSS™E Users Manual
Only five file types are shown. This is because Line Mode commands and Batch commands can be
intermingled in the same file, so the Response File file type (*.idv) is used for either (or both).
12-2 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Program Automation
Users Manual Python Programs
• Python and IPLAN are both programming languages, i.e. they can be used to write any
kind of a program, not just control PSS™E (although IPLAN’s features are fairly limited,
relatively speaking).
• IPLAN programs must be compiled (they do not need to be linked). The compiler
(called IPLAN) is a Siemens PTI product and supplied with PSS™E. The source files
are of file type *.ipl. The result (*.irf) are not object code files in the normal sense, but
a unique format.
• Python programs are interpreted (one command at a time is executed - no compilation
is necessary); although Python does support optional byte-compilation.
• PSEB and PSAS commands can also be embedded in Response Files, albeit in a par-
ticular context.
• Python programs can use existing IPLAN programs and Response Files. The other
automation methods can all interact with each other.
• Response Files, PSAS, and PSEB Command Files are free-format data files.
A Python installer is included in the PSS™E program installation package for your convenience.
The language can also be downloaded from the official Python site at http://www.wxpython.org/.
Python language documentation, extension modules, book recommendations, and user forums are
also available directly from this site. Siemens PTI recommends the following textbooks for
reference:
Siemens Power Transmission & Distribution, Inc., Power Technologies International 12-3
Program Automation PSS™E-31.0
Python Programs Users Manual
The PSS™E installation package will also install the following freely available third-party extension
modules:
• wxPython (http://www.wxpython.org//)
• win32all (Python Extensions for Windows) (http://sourceforge.net/projects/pywin32/)
Python files can be in source form (*.py, *.pyw) or byte-compiled (*.pyc). Python Files can be used
in PSS™E in any of the following ways:
Many extension modules are currently available on the Internet for download including: numeric
processing and optimization, graphic and data visualization (plotting), database connectivity, graph-
ical user interface programming, XML and text processing, network programming and connections
to Microsoft® Excel and Microsoft® Access.
Your PSS™E installation will include the following Python extension modules, which are docu-
mented in the PSS™E Application Program Interface Manual, and which can be imported into user
programs inside or outside of the PSS™E GUI:
• excelpy - provides Python functions to interface with Excel; these functions can be
used to create, populate and format Excel workbooks from Python.
• pssarrays - provides Python functions to retrieve PSS™E solution results
• pssexcel - provides Python functions to export PSS™E data or solution results to
Microsoft® Excel spreadsheets.
• pssplot - provides access to the PSS™Plot API
• psspy - provides access to the PSS™E API
Your PSS™E installation will also include the following Python extension modules which can also
be imported into user programs inside or outside of the PSS™E GUI:
12-4 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Program Automation
Users Manual Python Programs
Each of the modules above provides built-in documentation which can be accessed via the Python
help command. In the case of psspy, however, the result will be too voluminous to be useful. A sum-
mary is available by entering:
help(psspy.psspyc)
Help is also available for individual API routines, e.g:
help(psspy.pout)
Some features of the psspy module that are not part of the API itself are documented in the doc
string for psspy. Enter:
print psspy.__doc__
import os,sys
sys.path.append(pathname)
import psspy
_i,_f=psspy.getbatdefaults()
import pssplot,redirect
redirect.py2psse()
(where pathname is a variable containing a value retrieved from the registry; you will generally not
need to be concerned with this)
The os and sys modules are supplied with Python and contain commonly used functions for
accessing operating system features. The psspy, pssplot, and redirect modules are defined above.
The use of the _i and _f variables is explained in the section about Default Values in Python Files,
below, and in the PSS™E Application Program Interface (API). The redirect.py2psse() function
causes Python’s stdin (standard input) to use the function userin from the psspy module
(psspy.userin) and Python’s stdout (standard output) and stderr (standard error) to be redirected to
PSS™E’s progress device.
Note in particular that none of the modules are imported into the local name space. That means, for
example, that to use a PSS™E API routine defined in the API manual as, say:
ierr = abc()
You would need to reference it as:
ierr = psspy.abc()
This is in keeping with standard practice for the Python community.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 12-5
Program Automation PSS™E-31.0
Python Programs Users Manual
psspy.case('savnw.sav')
psspy.fnsl((0,0,0,1,1,0,99,0))
psspy.inibus(0)
while 1:
ierr,busnum,busname = psspy.nxtbus()
if ierr!=0: break
ierr,busarea = psspy.busint(busnum,'AREA')
psspy.report('%s %s' % (busnum,busarea))
One current idiosyncrasy of the embedded interpreter is that results are not automatically echoed
to the terminal as they are in the stand-alone Python interpreter. To see the values of expressions
you must use the print command.
In order to use the PSS™E supplied extension modules in this way, you must first make sure that
the Python import path can find all the modules by name, and that the windows load path can find
any required DLL’s. The following example replicates the environment in the embedded interpreter
explained in the preceding section:
This example assumes the standard PSS™E installation location, and a starting bus size of 80000.
Other values could have been chosen. Other techniques could be used as well. For example, if the
PYTHONPATH and PATH variables already contained the PSSBIN directory, then they would not
need to be set here. If the current directory was to be the working directory then that statement
would not be necessary, either. The only absolutely critical statements are the import psspy and
the call to psseinit.
The import of pssplot is omitted in the example above because its functions depend on the PSS™E
GUI and cannot be used in this mode. There are some graphics functions in psspy for which this is
true as well.
12-6 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Program Automation
Users Manual Batch Commands
Let’s say there is a PSS™E API routine called abcd. It takes an integer argument (IVAL), a two-
element integer array (IDATA) and returns a floating-point value and an integer return code. The
batch command syntax for this hypothetical API routine would be:
The format of the Batch Commands is the same as the standard free-format rules used for all
PSS™E data files. The following additional rules apply to Batch Commands, though:
• The command name itself is case insensitive, i.e. it doesn’t matter whether you use
upper case or lower case letters, or mix them (the documentation will always define
them as all upper case).
• The commands may be continued on multiple lines. The interpreter keeps reading data
until all the arguments that it needs for a given API routine are satisfied.
• There is a special token, a semi-colon, that can be used to tell the interpreter that it
should default all remaining inputs for that particular API routine. It must be a separate
token, not part of the previous value. In our example above,
BAT_ABCD 1 34 ;
will default the third value, but
BAT_ABCD 1 34;
will return a syntax error because "34;" is not a valid integer.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 12-7
Program Automation PSS™E-31.0
Line Mode Users Manual
Activity?
The appropriate response to this question was any of about 170-180 (in the last few releases)
"activities" which comprised the primary functions that PSS™E could perform. Each activity name
was four characters long; most could be abbreviated. Some activities could accept optional "suf-
fixes" which modified their behavior somewhat. Almost all would then ask a series of questions,
unique to each activity, to which the user would respond to operate the program. Many of those
activity names are preserved today in API routines that perform similar functions.
Line Mode commands can be used to automate PSS™E through Response Files (*.idv), so called
because they contain responses to the questions that the Line Mode of PSS™E asks.
The modern GUI has replaced this previously common method of operation, but there is a wealth
of existing Response Files containing Line Mode commands used to automate PSS™E. Therefore
PSS™E currently contains a feature called the Line Mode Interpreter (LMI) - a new program written
to imitate the traditional line mode of PSS™E, but that actually uses the PSS™E API. In a way it is
a translator from Line Mode to Batch Commands. It is not a perfect imitation, and those differences
are captured in Appendix D. The Line Mode itself is documented in the PSS™E Program Operation
Manual (POM).
It is worth noting that, although the Line Mode now comprises a subset of the full functionality of
PSS™E, for those functions it can perform, and for those users who are thoroughly familiar with the
Line Mode (and are good typists), that the program can still be operated more quickly from the key-
board than is physically possible with a point-and-click interface (i.e. a mouse). So while Line Mode
capabilities are not likely to be enhanced in the future, it’s current operation is considered to be an
important feature of the program.
The format of the Line Mode also conforms to the PSS™E standard free-format rules
12-8 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Program Automation
Users Manual IPLAN Programs
12.6.3 Version
The LMI provides one additional feature that the Line Mode does not - the ability to change versions.
As releases of PSS™E come out sometimes changes are necessary in the sequence of Line Mode
commands. The creates maintenance work for existing Response Files. The LMI provides a com-
mand, "VERSION", which displays or sets the version of the Line Mode "language" being
processed. Introduced at rev 31 of PSS™E, it recognizes versions from rev 30 and afterwards, e.g.:
Siemens Power Transmission & Distribution, Inc., Power Technologies International 12-9
Program Automation PSS™E-31.0
PSS™E PSEB Macro Language Users Manual
Compiled IPLAN Files can be used in PSS™E in any of the following ways:
IPLAN cannot modify PSS™E directly, or call other routines in the PSS™E API directly. However,
via the PUSH (and PUSHX, QPUSH, QPUSHX) command(s) it can do anything that can be done
in a Response File. That includes, say, @input, which will open a Response File; in that case, the
commands in that response file will not take effect immediately unless other steps are taken. This
is explained in detail in the IPLAN Program Manual.
One of the commands in the Line Mode is EXEC, which is used to load an IPLAN program. If an
IPLAN program invokes EXEC through a PUSH statement or by causing a Response File con-
taining EXEC to run, that program will replace the current one in the IPLAN simulator. IPLAN
programs do not nest.
12-10 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Program Automation
Users Manual PSS™E PSAS Macro Language
only the translation is performed, even if the CHECK option is not specified. When using the PSEB
API routine only the translation is performed.
12.10 Recording
The PSS™E interface is capable of recording PSS™E API commands. Recorded API commands
can be in the form of either Python statements or Batch Commands (Response File) depending on
a specified user option. The easiest way to record a Python script (*.py, for Python statements) or
a Response File (*.idv, for Batch Commands) for later execution is to use the I/O Control>Start
Recording… option. Selecting this option will start the recorder. The entry of subsequent selections
of PSS™E commands will record the API routines used to an automation file for later use until the
I/O Control>Stop Recording option is selected.
As an example, suppose you wanted to print power flow results to the Report View for buses 101,
201, 205, 154, and 3001. To record these interactions:
1. Select I/O Control>Start Recording… and select the type of file you wish to record:
Python File (*.py) or Response File (*.idv).
2. Specify, say, busout.idv or busout.py as the file name depending on your selection of
file type in Step 1, and select Open.
5. Select Power Flow>Reports>Bus based reports…. The bus based reports dialog is
displayed. Select the radio button for The following buses and enter 101, 201, 205,
143, 3001 in the text box provided. Select Go. Select Close.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 12-11
Program Automation PSS™E-31.0
Recording Users Manual
Using a text editor, open the file busout.idv (Figure 12-2) or busout.py (Figure 12-3) and you will
see the following
12.10.1 ECHO
Users of PSS™E’s traditional Line Mode will be familiar with the activity ECHO. It performs a func-
tion similar in effect to the recording function in the current program. It is a very different thing,
however, and a remnant of it remains.
ECHO copied all terminal input to a file. Since all PSS™E input at that time either came from a ter-
minal or a device that imitated the terminal, that meant all (interactive) input.
The current recording function is a feature of the API routines. When they are called, if recording is
enabled, they record a copy of their input in the designated format in the designated file; it doesn’t
matter how the call occurred - by menu selection, through the CLI, from an automation file, etc.
The ECHO function still exists, and it still does the same thing, i.e. copies all terminal input to a file.
The difference is that there is very little terminal input. The API routine userin, the IPLAN function
INPUT (and INPUTLN), and the @pause immediate command all attempt to read from the terminal,
which is handled in via a pop-up window. So data entered there will show up in an ECHO file.
Related to this is the traditional Line Mode activity IDEV, meaning Input DEVice. IDEV was used to
replace the terminal with a file so that subsequent READ’s from the terminal would find the
responses in the file (hence the name "Response File"). IDEV never "executed" the commands in
a Response File, but it appeared that way to most people. The implementation of IDEV in the LMI
does what most people would expect, therefore; it causes the commands in the Response File to
be interpreted by the LMI. This means, however, that IDEV no longer does what it used to do, i.e.
replace terminal input with a file. This function is now performed by the API routine
SET_INPUT_DEV. The effect of that API is open a file to respond to input requests from the ter-
minal (except @pause which will still force an actual terminal read, handled via a pop-up window).
12-12 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Program Automation
Users Manual Argument Passing
1. Select I/O Control Run Program Automation File…. The Select Program Automation
File dialog displays (Figure 12-4).
2. Select the type of file you wish to execute from the Files of Type drop-down list.
4. Select the Arguments button, enter the argument string in the box provided, and select
OK (Figure 12-5).
5. Select Open. The file will be executed within the PSS™E user interface with results
being displayed appropriately to the spreadsheet, report, and progress views.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 12-13
Program Automation PSS™E-31.0
Argument Passing Users Manual
• Python files
• Response files
• IPLAN files
but how they are handled by each varies. Note that the dialog permits specifying arguments for
PSAS and PSEB files, but those languages have no facility for retrieving the argument values.
import sys
print sys.argv
When run using the Python interpreter from a Command Prompt the input is assumed to be space
delimited and is parsed into separate values, e.g.:
Enter:
12-14 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Program Automation
Users Manual Default Values
Response File arguments are documented in Section 3.7.3 of the PSS™E Program Operation
Manual (POM). An example of an argument would be %1%, which could appear anywhere in the
file. In this case %1% would be replaced by the first value parsed from the argument string. Likewise
%5% would be replaced by the fifth value parsed from the argument string.
Response Files require that all arguments receive values. A useful technique is to document all
arguments referenced in a Response File using the TEXT command at the beginning of the
Response File. This approach will help detect missing argument errors before any lengthy compu-
tations specified in the Response File are performed.
While it is possible in some programming languages for a value to be "not there", the general case
is that in order to indicate this situation a special value is used. When input values are omitted in
automation files such special values are substituted for them. The various API routines check for
the special values and take appropriate default actions when they are encountered.
Currently spaces and false are used for string and logical values when they are omitted. The special
values for integers and reals (floats) are returned from the API routine GETBATDEFAULTS. No
assumptions should be made that these precise values will be identical from one release of the
PSS™E to another. If it is necessary to acquire these values, always run the API routine to get the
current values.
Default values can be specified in references to API routines in Python Files. Data items can be
omitted in Response Files. The concept of default values does not apply to IPLAN programs in gen-
eral, but there are some functions that take optional arguments, and since PUSH statements can
contain anything that could be in a Response File, any comments about Response Files will apply
there. All data values are required in PSEB and PSAS files
Siemens Power Transmission & Distribution, Inc., Power Technologies International 12-15
Program Automation PSS™E-31.0
Default Values Users Manual
In addition psspy contains a unique feature for specifying values for specific elements in an input
list. This is best illustrated by example. Let’s say a function mysub takes a single argument, opt,
which is a 2-element list of integers, then the following are equivalent:
mysub([_i,1])
mysub(opt=[_i,1])
mysub(opt2=1)
mysub(opt=None,opt2=1)
mysub(opt=[_i,42],opt2=1)
mysub(opt2=1,opt=[_i,352])
mysub(opt1=_i,opt2=1)
where _i is a variable equal to the default integer value.
What this means is that all the functions in psspy recognize special keywords formed by concate-
nating any input list name and the string representation all the possible index values (starting at 1)
and will use them to override just that specific element of the list.
_i,_f=psspy.getbatdefaults()
is recommended in Section 12.4.3.
For Batch Commands there is a special token, a semi-colon, that can be used to tell the interpreter
that it should default all remaining inputs (see Section 12.5).
Files containing recorded Batch Commands will use consecutive commas for default values spec-
ified to the API routine.
12-16 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Program Automation
Users Manual Unattended Execution of PSS™E
The -embed option has the effect of suppressing the display of the PSS™E GUI. If the Automation
File terminates without stopping the execution of PSS™E the GUI will be displayed at that time.
The following are a few points to be aware of when preparing to run PSS™E in an unattended
mode:
• PSS™E does not read input from stdin or write to stdout, so pipes cannot be used for
batch execution of PSS™E.
• Be aware of the nature of the operating system tool you are using to start PSS™E. In
Microsoft® Windows, for example, non-console application programs, such as
PSS™E, are executed asynchronously. This means that should you have a batch file
that starts PSS™E it will not wait for the program to stop before continuing on the next
statement in the batch file.
• PSS™E needs exclusive access to a set of working files that it will find or create in its
initial working directory. This means that an attempt to start a second execution of
PSS™E in the same working directory will fail.
• When running in batch mode (i.e. with a startup automation file specified that stops the
program) the progress view and report view output should be re-directed to a printer or
file, otherwise output will be sent to the windows that will be closed when the program
stops.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 12-17
Program Automation PSS™E-31.0
Using the Command Line Interface Users Manual
1. Select I/O Control>Begin command line input session…. The command line input
dialog displays (Figure 12-6, Figure 12-7, Figure 12-8). The command line input dialog
has a tabbed format, presenting an Input tab and Report tabs. The Input tab is where
commands are typed and prompts and Progress view information are displayed. The
Report tab(s) function(s) similarly to the main GUI.
2. Select the Command Language you wish to use from the available list containing
Python and PSS™E Response. If the Python language is chosen (default), the inter-
face will expect entry of Python commands in the Input tab. If PSS™E Response is
chosen, you can enter Line Mode or Batch Commands. Place your mouse cursor in the
Input tab and begin typing commands. Press the [Return] key to allow PSS™E to inter-
pret and process your command. Once the command is processing, output messages
and prompts will be directed to the Input tab.
3. Previously executed commands may be recalled by either selecting the command from
the drop-down list labeled Command History or hitting the [Scroll Up] and [Scroll
Down] keys.
4. If you wish to execute an automation file, select the Run Auto… button and select the
desired file name using the file selector. Once the automation file has completed its
execution, the Run Again… button will be activated. Select Run Again… to repeat the
execution of the automation file, eliminating the need to re-specify the automation file
name and associated path.
12-18 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Program Automation
Users Manual Using the Command Line Interface
Line Mode commands entered in the CLI are handled by the LMI; Batch Commands are handled
by the Batch Command interpreter, and Python Commands are passed to the embedded Python
interpreter. When using the Line Mode, prompts are provided that resemble the traditional Line
Mode prompts; when an activity is completed the "Activity?" prompt is presented. When an incom-
plete Batch Command is entered, a prompt of the form "API-name:" is presented.
Every time the CLI is started, the various processors are set to receive new commands. If the CLI
is closed without completing a command, the uncompleted information is discarded. However,
there are some API routines that are designed to be called in a series with different options. If a Line
Mode activity is interrupted that used such an API routine, and some of the API calls in the series
have taken place, it will be difficult to return that API routine to a state where is can be used again
(this same situation can be created by a Batch Command or Python statement invoking the API,
but it is more apparent there).
The CLI is a modal dialog; i.e. while it is running the remainder of the PSS™E GUI is unavailable.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 12-19
Program Automation PSS™E-31.0
Using the Command Line Interface Users Manual
12-20 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Program Automation
Users Manual Using the Command Line Interface
Siemens Power Transmission & Distribution, Inc., Power Technologies International 12-21
Program Automation PSS™E-31.0
Using the Command Line Interface Users Manual
12-22 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Chapter 13
Result Retrieval APIs
This will open the Excel Export dialog where PSS™E solution/analysis results file, excel
output file and the quantities to export can be identified (see Figure 13.1).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 13-1
Result Retrieval APIs PSS™E-31.0
Exporting PSS™E results to Excel using Excel Export GUI Users Manual
Data/Results to Export - Options button: The solution type to export (contingency, tripping or cor-
rective action) can be specified as part of options data, in this example, ACCC.
Data/Result File: The default excel file name is the name of the results file with an xls extension, if
no name is specified for Excel Workbook File.
Excel Workbook File: One worksheet for each selected item from Quantities to Export is created
in a specified workbook. The name of the worksheet is the name of the quantity to export. This work-
sheet name will be prefixed by the text specified in Excel Sheet Prefix.
13-2 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Result Retrieval APIs
Users Manual Python Lists
• Show Workbook flag: Select to open and display workbook as it is being written to.
Deselect to populate workbook without displaying it.
• Split Extended Bus Names flag: Select to split extended bus names into three columns
- Bus Number, Bus Name and Bus Voltage.
• PSSARRAYS module returns data and results from PSS™E activities to Python lists.
• PSSEXCEL module creates and populates Excel spreadsheets with data and results
from PSS™E activities. This module is an example of how to use Python lists returned
by PSSARRAYS for further processing. This modules uses the PSSARRAYS module
to retrieve PSS™E activity data and results and the EXCELPY module to write the data
and results to Excel spreadsheets.
• EXCELPY is an auxiliary module that provides Python functions to create and populate
Excel spreadsheets.
Following sections describe just few functions and give sample Python commands/code to illustrate
how to use Python functions available in these modules. These Python commands can be executed
from either PSS™E program automation files or the PSS™E CLI.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 13-3
Result Retrieval APIs PSS™E-31.0
pssarrays.accc_summary Users Manual
13.3 pssarrays.accc_summary
13.3.1 CLI
import pssarrays 1
2
smry = pssarrays.accc_summary(r"savnw.acc")
or
smry = pssarrays.accc_summary(accfile=r"savnw.acc")
or
smry = pssarrays.accc_summary(accfile=r"c:\filepath\savnw.acc")
print smry.ierr 3
0
print smry.acccsize.nmline
11
print smry.file.acc
C:\Program Files\PTI\PSSE31 Alpha 2\EXAMPLE\savnw.acc
print smry.melement
(' 201 HYDRO 500.00 151 NUCPANT 500.00 1', ' 202
EAST500 500.00 152 MID500 500.00 1', ' 203 EAST230
230.00 154 DOWNTN 230.00 1', ' 205 SUB230 230.00 15
DOWNTN 230.00 1', ' 3001 MINE 230.00 3002 E. MINE
500.00 1', ' 3004 WEST 500.00 152 MID500 500.00 1', '
3004 WEST 500.00 3005 WEST 230.00 1', ' 3005 WEST
230.00 3008 CATDOG 230.00 1', ' 3006 UPTOWN 230.00 15
MID230 230.00 1', ' 3008 CATDOG 230.00 154 DOWNTN
230.00 1', ' 3008 CATDOG 230.00 3018 CATDOG_G 13.800 1', '
INTERFACE WEST', ' INTERFACE EAST')
print smry.mvbuslabel
(' 3001 MINE 230.00', ' 201 HYDRO 500.00', ' 202
EAST500 500.00', ' 203 EAST230 230.00', ' 204 SUB500
500.00', ' 205 SUB230 230.00', ' 206 URBGEN 18.000', '
211 HYDRO_G 20.000', ' 3001 MINE 230.00', ' 3002 E. MINE
500.00', ' 3003 S. MINE 230.00', ' 3004 WEST 500.00', '
3005 WEST 230.00', ' 3006 UPTOWN 230.00', ' 3007 RURAL
230.00', ' 3008 CATDOG 230.00', ' 3011 MINE_G 13.800', '
3018 CATDOG_G 13.800')
By importing the pssarrays module, the functions defined inside this module are made avail-
1 able outside of the module.
13-4 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Result Retrieval APIs
Users Manual pssarrays.accc_summary
• ACCC solution output file is available in the working folder, accc_summary function
called with keyword argument ’accfile’.
smry = pssarrays.accc_summary(accfile=r"savnw.acc")
• ACCC solution output file is not available in the working folder, then its location needs
to be specified.
smry = pssarrays.accc_summary(accfile=r"c:\filepath\savnw.acc")
Note: The accfile name is specified in r"…" format, to make the file name a Python raw
string. It suppresses escapes sequences, viz., \n for newline character, \t for tab etc.
ACCC summary results are returned in the Python list “smry”. The various values available
3 in this list are accessed by their names as an attribute of the returned list. The API docu-
mentation provide the list of values available in the returned list.
import pssarrays
smry = pssarrays.accc_summary(r"savnw.acc")
print smry.ierr
print smry.acccsize.nmline
print smry.file.acc
print smry.melement
print smry.mvbuslabel
Siemens Power Transmission & Distribution, Inc., Power Technologies International 13-5
Result Retrieval APIs PSS™E-31.0
pssarrays.accc_solution Users Manual
13.4 pssarrays.accc_solution
The following Python code example shows how to get ACCC analysis results and write them to a
report.
import pssarrays
reptfile = 'accc_output.txt'
reptnam = open(reptfile,'w')
smry = pssarrays.accc_summary(accfile=r'savnw.acc')
rate = smry.rating.a
stype = 'con'
13-6 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Result Retrieval APIs
Users Manual pssarrays.accc_solution
if not cnvflag:
reptnam.write("\n================================\n")
continue # consider solution for converged cases only
# (2) flows
txtstr = ''
for jj in range(smry.acccsize.nmline+smry.acccsize.ninter):
mvaflow = "%9.2f" % soln.mvaflow[jj]
if jj < smry.acccsize.nmline:
ampflow = "%9.2f" % soln.ampflow[jj]
pctflow = abs( soln.ampflow[jj])
else:
ampflow = 9*' '
pctflow = abs( soln.mvaflow[jj])
if rate[jj]:
pctflow = "%6.2f" % (pctflow*100.0/rate[jj])
else:
pctflow = 6*' '
# (3) voltages
if smry.acccsize.nmvbus:
reptnam.write("\nMONITORED BUS VOLTAGES\n")
txtstr = ''
for eachv in soln.volts:
txtstr += " %8.5f" % eachv
if txtstr:
reptnam.write("%(lbl)-12s%(txtstr)s\n" % vars())
Siemens Power Transmission & Distribution, Inc., Power Technologies International 13-7
Result Retrieval APIs PSS™E-31.0
pssarrays.accc_solution Users Manual
reptnam.write("\n================================\n")
reptnam.close()
print "ACCC Solution saved in file %s." % reptfile
13-8 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Result Retrieval APIs
Users Manual pssarrays.accc_violations_report
13.5 pssarrays.accc_violations_report
This function creates the following reports:
• monitored element flow violations (percent flow greater than flow limit). The flow limit is
specified as an argument of this function.
• monitored bus voltage violations (bus voltage <minimum voltage bound or >maximum
voltage bound). The voltage bound values are taken from monitored element data file
(.mon).
• loads shed
• generator dispatch
• phase shifter angle adjustments
The following command, executed from either the CLI or a Python automation file, produces ACCC
violations reports for corrective action solution and reports on monitored branches whose loading
is above 95%.
13.6 pssexcel.accc
Using the “pssarrays” module, ACCC analysis results are retrieved from an *.acc input file and then,
using the “excelpy” module, these results are written to Excel Spreadsheets.
The Python commands below create a ’savnw_acc.xls’ file and the following worksheets populated
with “ACCC Corrective Action” solution data from the ’savnw.acc’ file for contingencies ’base case’
and ’trip1nuclear’. If a ’colabel’ value is not provided, all contingencies are considered. Also the
extended bus names of monitored branches and buses are split into three Excel spread columns
(namesplit=True). The argument show=True displays the workbook when it is being populated.
• test Summary
• test Contingency Events
• test Branch Flow
• test Interface Flow
• test Bus Voltage
• Test Load Shed
• test Generator Dispatch
• test Phase Shifter Angle
import pssexcel
pssexcel.accc(accfile = r"savnw.acc",
string = ['b','e','g','i','l','p','s','v'],
colabel = ['base case', 'trip1nuclear'],
Siemens Power Transmission & Distribution, Inc., Power Technologies International 13-9
Result Retrieval APIs PSS™E-31.0
pssexcel.accc Users Manual
stype = 'cor',
busmsm = 0.5,
sysmsm = 5.0,
rating = 'a',
namesplit = True,
xlsfile = r'savnw_acc.xls',
sheet = 'test',
overwritesheet = True,
show = True
)
In the command above, ’accfile’ and ’string’ are the only mandatory arguments. The worksheets to
create are defined by the ’string’ argument.
13-10 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Result Retrieval APIs
Users Manual pssexcel.pv
13.7 pssexcel.pv
Using the “pssarrays” module, PV solution results are retrieved from a *.pv input file and then, using
the “excelpy” module, these results are written to Excel Spreadsheets.
The Python commands below create a ’savnw_pv.xls’ file and the following worksheets populated
with PV solution results from the ’savnw.pv’ file for contingencies ’base case’ and ’trip1nuclear’. If
a ’colabel’ value is not provided, all contingencies are considered. Also the extended bus names of
monitored branches and buses are split into three Excel spread columns (namesplit=True). The
argument show=True displays the workbook when it is being populated.
• testpv Summary
• testpv Bus Voltage
• testpv Mismatch
• testpv Generator Dispatch
• testpv Bus Load
• testpv Branch Flow
• testpv Interface Flow
import pssexcel
pssexcel.pv(pvfile = r"savnw.pv",
string = ['s','m','v','g','l','b','i'],
colabel = ['base case', 'trip1nuclear'],
namesplit = True,
xlsfile = r'savnw_pv.xls',
sheet = 'testpv',
overwritesheet = True,
show = True
)
In the command above, ’pvfile’ and ’string’ are the only mandatory arguments. The worksheets to
create are defined by the ’string’ argument.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 13-11
Result Retrieval APIs PSS™E-31.0
excelpy Examples Users Manual
import excelpy
import pssarrays
qvfile = r"savnw.qv"
colabel = ['base case', 'trip1nuclear']
xlsfile = 'testqv.xls'
13-12 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Result Retrieval APIs
Users Manual excelpy Examples
tmplst=[
smry.casetitle.line1,
smry.casetitle.line2,
'QV output file = %s' % smry.file.qv,
'Saved Case file = %s' % smry.file.sav,
'DFAX file = %s' % smry.file.dfx,
'Subsystem file = %s' % smry.file.sub,
'Monitored Element file = %s' % smry.file.mon,
'Contingency Description file = %s' % smry.file.con,
' ', # blank row
'Number of Contingencies+Base Case = %d' % smry.qvsize.ncase,
'Number of Monitored Generators(Plants)= %d' % smry.qvsize.nmgn-
bus,
'Number of Voltage Monitored Buses = %d' % smry.qvsize.nmvbus,
'Number of Voltage Monitored Records = %d' % smry.qvsize.nmvrec,
'Number of max.volt. setpoint changes = %d' % smry.qvsize.nmx-
vstp,
]
if smry.file.thr:
tmplst.insert(4,'Load throwover file = %s' % smry.file.thr)
row += 2
Siemens Power Transmission & Distribution, Inc., Power Technologies International 13-13
Result Retrieval APIs PSS™E-31.0
excelpy Examples Users Manual
bottomRow,rightCol = qvxls.set_range(row,col,tmplst,trans-
pose=True)
qvxls.font_color((row,col,row+1,col),'brown')
row = bottomRow+2
qvxls.set_cell((row,col),"QV Contingencies",fontStyle="Bold",
fontSize=12, fontColor="red")
row += 1
bottomRow,rightCol = qvxls.set_range(row,col,conlst)
qvxls.font_color((row,col,row,rightCol), "dgreen")
qvxls.font((row,col+2,bottomRow,col+3),numberFormat='0.00')
qvxls.font((row,col+4,bottomRow,col+6),numberFormat='0.000')
13-14 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Result Retrieval APIs
Users Manual excelpy Examples
qvxls.align((row,col),'right')
qvxls.font((row,col,row,rightCol),fontStyle=('Bold',))
qvxls.autofit_columns((row,col+1,row,rightCol))
# done qvsummary worksheet
qvxls.set_active_sheet('qvvolts')
row, col = 1, 1
col = 1
qvxls.set_cell((row,col+1),contitle,fontStyle='bold',
fontSize=12,fontColor="dgreen")
row += 1
bottomRow,rightCol = qvxls.set_range(row,col,tmplst,trans-
pose=True)
qvxls.font((row,col,row,rightCol),fontColor="red",font-
Style='bold')
qvxls.font((row,col+1,bottomRow,rightCol),numberFormat="0.000")
Siemens Power Transmission & Distribution, Inc., Power Technologies International 13-15
Result Retrieval APIs PSS™E-31.0
excelpy Examples Users Manual
qvxls.align((row,col,row,rightCol),'h_center')
qvxls.align((row,col),'right')
qvxls.font((row+1,col,bottomRow,col),fontColor="blue",
fontStyle='bold')
row = bottomRow + 2 # one blank row
13-16 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Result Retrieval APIs
Users Manual excelpy Examples
import excelpy
testxls = excelpy.workbook(r"test.xls","TestExcelPy")
testxls.show()
testxls.font_sheet()
testdata=[
['CON#', 'LABEL', 'Max MW', 'DESCRIPTION'],
[' ', 'BASE CASE', 756.25, 'BASE CASE '],
['1', 'TRIP1NUCLEAR', 1000.0, 'REMOVE UNIT 1'],
['2', 'TRIP2NUCLEAR', 0.0, 'REMOVE UNIT 1'],
['', '', '', 'REMOVE UNIT 2'],
['3', 'ADDLARGELOAD', 0.0, 'INCREASE LOAD'],
['4', 'LOSEWESTGEN', 625.0, 'REMOVE UNIT 3'],
['5', 'LOSEWESTBIGT', 312.5, 'TRIP LINE 1 '],
]
row=1
col=1
testxls.set_cell(value="How to use EXCELPY module?",
address=(row,col),fontName="Arial",fontSize=12,
fontColor='red',fontStyle=('Bold','italic'))
Siemens Power Transmission & Distribution, Inc., Power Technologies International 13-17
Result Retrieval APIs PSS™E-31.0
excelpy Examples Users Manual
xlsfile = testxls.save(xlsfile)
print "Excel workbook saved to ’%s’ file.\n"% xlsfile
13-18 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Chapter 14
Dynamic Simulation
Interface
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-1
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
All network elements that have Dynamics models attached to them will have an entry in the appro-
priate folder in the Dynamics tab.
Double-clicking on a data element (i.e. particular bus) activates the Dynamics Spreadsheet View,
changes to the correct data tab, and places the focus on the first spreadsheet cell of the selected
item (see Figure 14-2).
14-2 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
The Dynamics Tree View only displays network elements for which Dynamics models have been
defined, either through the opening of a Snapshot or DYRE file or through the Dynamics
Spreadsheet.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-3
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
Figure 14-3. Dynamics Spreadsheet
14-4 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
If the Dynamics spreadsheet has been opened, it can be brought to the foreground, i.e. made the
active view, by selecting Window>Dynamics Spreadsheet or the Dynamics Spreadsheet toolbar
Icon found on the Spreadsheets toolbar (see Figure 14-4).
Once the network element has been specified, models can be added by moving to the desired
model location on the spreadsheet line and right-clicking. From the popup menu, select
“Add/Replace Model” (see Figure 14-5).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-5
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
Figure 14-5. Dynamic Models Spreadsheet
14-6 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
Selecting “Add/Replace Model” will display a model selector that displays all the currently loaded
models appropriate for the type of network element being modified (see Figure 14-6).
Once all Dynamics models for the network element have been selected, move off the record to store
the data. If you create a new entry for a network element in one of the spreadsheets without spec-
ifying any Dynamics models, the following message will appear (see Figure 14-7). Dynamics
models must then be specified or the entry removed through the use of Edit>Undo record.
To remove an existing Dynamics model from a network element, select the Dynamics model in the
spreadsheet, right-click and select “Remove Model” from the popup menu and move off the record
to store the data.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-7
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
To edit the parameters for a particular Dynamics model, select the Dynamics model in the spread-
sheet, right-click, and select “Edit Model” from the popup menu. Selecting “Edit Model” will display
a dialog which can be used to modify any of the parameters (CONs/ICONs) associated with that
particular instance of the model at that particular network element (see Figure 14-8).
To change the status of an existing Dynamics model, toggle the status check box located to the
right of the Dynamics model of interest and move off the record to store the data (see Figure 14-9).
14-8 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
If channels have been defined to collect the output of simulation results, they will appear in the
spreadsheet for editing. Channels are defined for output through the dialogs available at
Dynamics>Define simulation output (CHAN)… and Dynamics>Define simulation output by
subsystem (CHSB)….
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-9
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
14-10 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
The Models tab is organized by Dynamics model types e.g. Generators, Stabilizers etc. Each model
type contains a list of all models of that type present in the current network. Figure 14-12 shows that
there are three types of exciter models present in the current network, SEXS, SCRX and IEEET1.
Double-clicking on a Dynamics model activates the Model Spreadsheet View and loads the spread-
sheet with all network instances of that selected model (see Figure 14-13).
The columns containing a particular CON or ICON can be sorted by double-clicking the column
header, just as in the Network spreadsheet. Copy/Paste operations work the same as described for
the Network spreadsheet.
If the Model spreadsheet has been opened, it can be brought to the foreground, i.e., made the
active view, by selecting Window>Model Spreadsheet or the Model Spreadsheet toolbar Icon
found on the Spreadsheets toolbar (see Figure 14-14).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-11
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
Further details on using the integrated plot package can be found in Chapter 16.
14-12 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-13
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
Note that, in Figure 14-17, the last two entries, namely the ’Calculate and apply unbalanced bus
fault’ and the ’Calculate and apply branch unbalance’ involve the calculation of the positive
sequence equivalent of an unbalanced condition. For the unbalanced bus fault, activity SCMU (see
Program Operation Manual Volume I, Section 4.99) is used; for the branch unbalance, activity
SPCB (see Program Operation Manual Volume I Section 4.101) is used. The requirements and
restrictions applicable to those activities must be recognized. Further, the use of these two fault cal-
culations is applicable only to the application of a single unbalance. It would not be valid to apply a
fault using any of the methods described in this section, and then, with that fault is still applied, cal-
culate the positive sequence equivalent of another unbalanced condition.
The list of currently applied faults is not preserved in Snapshot Files or Saved Case Files. This list
is initialized to "empty" when PSS™E is started up at its dynamic simulation entry point, and also
during the simulation initialization activities STRT, MSTR, ASTR, ESTR and GSTR
14-14 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-15
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
Once the DYRE file has been selected, the following dialog appears (see Figure 14-21). From this
dialog CONEC and CONET files can be specified, as well as starting values for CONs, ICONs,
STATEs and VARs. Clicking on OK will read the specified DYRE file and update the Dynamics Tree
View and Spreadsheet with the Dynamics data contained in the file.
14-16 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-17
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
Once the DYRE file has been selected, the following dialog appears (see Figure 14-23). From this
dialog CONEC and CONET files can be specified, as well as starting values for the CONs, ICONs,
STATEs and VARs contained within the DYRE file. Clicking on OK will read the specified DYRE file
and update the Dynamics Tree View and Spreadsheet with the Dynamics data contained in the file.
Commonly, a Dynamics simulation is run to a certain time, solution parameters are modified, and
the run continued with the new parameters.
Select the OK button to use the new solution parameter settings. Select the Cancel button to dis-
miss the dialog without making any changes.
14-18 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
The network frequency dependence option results in both network parameters and the flux calcu-
lations of generator models made dependent on local frequency. The out-of-step relay scanning
model checks every circuit in both directions for out-of-step conditions. The two generator scanning
functions trip machines instantaneously if the specified threshold is violated. The voltage scanning
model reports bus voltages outside of the specified band. The generic apparent impedance relay
scanning model checks every circuit in both directions against generic relay characteristics. If
machine angles are "relativized", reports which list machine angles, as well as any output channels
containing machine angles, express them relative to the specified value rather than as absolute
angles. For additional information, see the Program Application Guide.
Select the OK button to use the new simulation option settings. Select the Cancel button to dismiss
the dialog without making any changes.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-19
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
14-20 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
The channel output file, used to capture the output of the Dynamics simulation, is specified in the
“Channel output file” field. The channel output file can be selected by entering it directly in the field
or by selecting the “browse” button to the right of the field and using a standard file selector dialog
to select the file.
The "Run to" field defines the value of simulated TIME at which the simulation activity is to be ter-
minated. When the dialog is brought up, this field contains the present value of simulated TIME.
The values of the "Print every", "Write every" and "Plot every" data items are integer values defining
the interval, in units of the number of simulation time steps, between the recording of output channel
values. Any changes to these settings are remembered and become their initial values the next time
the dialog is brought up.
The "Print every" data item defines the interval to be used in tabulating the values of the output
channels. This tabulation is directed to the defined progress output device.
The "Write every" data item defines the interval to be used in writing the values of the output chan-
nels to the current channel output file. This value is meaningful only if a channel output file had been
specified when the Initialize button was selected.
The "Plot every" data item defines the interval to be used in plotting the values of the CRT plot chan-
nels at the user's CRT workstation. This value is meaningful only if: a channel output file had been
specified when the Initialize button was selected and at least one of the six CRT plot channels
listed in the Dynamics Plotting Channels tab of the Dynamics Spreadsheet has been selected.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-21
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
When the dialog first appears, if the simulation has not been initialized, the Run button will be dis-
abled. The simulation will first need to be initialized by selecting the Initialize button. Note that the
file specified in the Channel output file field is used during the initialization process. Once the sim-
ulation has been initialized the Run button will be enabled.
Selecting the Run button will run the simulation out to the time specified in the “Run to” field. Once
the simulation has been run out to the specified time, disturbances and faults can be applied and
the simulation run again out to a new specified time.
The Perform Dynamic Simulation dialog is a modeless dialog. This means that it doesn’t have to be
dismissed in order to access other program functions.
If a bus is specified in the “Bus to be tested” field, the excitation system response of all machines
connected to the specified bus having connected excitation system models is tested. If no bus is
specified, all machines with connected exciter models are tested. The bus can be specified by
entering it directly in the Bus to be tested field or by selecting the Select button to the right of the
field and using the standard bus selector dialog to select the bus.
The “VREF P.U. step change” field is used to specify the step to be applied to all voltage regulator
setpoints, typically 0.02 to 0.1. The step magnitude should not exceed about ten percent (0.1) since
the object of this test is to reveal small disturbance behavior.
14-22 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
The channel output file, used to capture the output of the Dynamics simulation, is specified in the
“Channel output file” field. The channel output file can be selected by entering it directly in the field
or by selecting the “browse” button to the right of the field and using a standard file selector dialog
to select the file.
The "Run to" field defines the value of simulated TIME at which the simulation activity is to be ter-
minated. When the dialog is brought up, this field contains the present value of simulated TIME.
The values of the "Print every", "Write every" and "Plot every" data items are integer values defining
the interval, in units of the number of simulation time steps, between the recording of output channel
values. Any changes to these settings are remembered and become their initial values the next time
the dialog is brought up.
The "Print every" data item defines the interval to be used in tabulating the values of the output
channels. This tabulation is directed to the defined progress output device.
The "Write every" data item defines the interval to be used in writing the values of the output chan-
nels to the current channel output file. This value is meaningful only if a channel output file had been
specified when the Initialize button was selected.
The "Plot every" data item defines the interval to be used in plotting the values of the CRT plot chan-
nels at the user's CRT workstation. This value is meaningful only if: a channel output file had been
specified when the Initialize button was selected and at least one of the six CRT plot channels
listed in the Dynamics Plotting Channels tab of the Dynamics Spreadsheet has been selected.
When the dialog first appears, if the simulation has not been initialized, the Run button will be dis-
abled. The simulation will first need to be initialized by selecting the Initialize button. Note that the
file specified in the Channel output file field is used during the initialization process. Once the sim-
ulation has been initialized the Run button will be enabled. Selecting the Run button will run the
simulation out to the time specified in the “Run to” field.
The Perform Exciter Simulation Test dialog is a modeless dialog. This means that it doesn’t have
to be dismissed in order to access other program functions.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-23
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
If a bus is specified in the “Bus to be tested” field, the excitation system response of all machines
connected to the specified bus having connected excitation system models are tested. If no bus is
specified, all machines with connected exciter models are tested. The bus can be specified by
entering it directly in the Bus to be tested field or by selecting the Select button to the right of the
field and using the standard bus selector dialog to select the bus.
14-24 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
The “Default power factor” field is used to specify the value used to initialize each generator to rated
MVA (i.e., to MBASE as contained in the power flow generator data) at the specified power factor.
The channel output file, used to capture the output of the Dynamics simulation, is specified in the
“Channel output file” field. The channel output file can be selected by entering it directly in the field
or by selecting the “browse” button to the right of the field and using a standard file selector dialog
to select the file.
Machines can be selected to be initialized with a power factor other than the “Default power factor”
by adding them to the list of “Machines initialized with own power factor”. This is done by specifying
the individual machine and its power factor in the fields in the middle of the dialog. The machine can
be specified by entering it directly in the “Bus” and “Machine ID fields or by selecting the Select
button to the right of the field and using the standard machine selector dialog to select the machine.
When the machine is specified, change the “Power factor” field to specify the power factor at which
to initialize the specified machine. Select the Add button to add it to the list of machines with unique
initializations. To remove a machine from the list, select it in the list and press the [Delete] key.
The "Run to" field defines the value of simulated TIME at which the simulation activity is to be ter-
minated. When the dialog is brought up, this field contains the present value of simulated TIME.
The values of the "Print every", "Write every" and "Plot every" data items are integer values defining
the interval, in units of the number of simulation time steps, between the recording of output channel
values. Any changes to these settings are remembered and become their initial values the next time
the dialog is brought up.
The "Print every" data item defines the interval to be used in tabulating the values of the output
channels. This tabulation is directed to the defined progress output device.
The "Write every" data item defines the interval to be used in writing the values of the output chan-
nels to the current channel output file. This value is meaningful only if a channel output file had been
specified when the Initialize button was selected.
The "Plot every" data item defines the interval to be used in plotting the values of the CRT plot chan-
nels at the user's CRT workstation. This value is meaningful only if: a channel output file had been
specified when the Initialize button was selected and at least one of the six CRT plot channels
listed in the Dynamics Plotting Channels tab of the Dynamics Spreadsheet has been selected.
When the dialog first appears, if the simulation has not been initialized, the Run button will be dis-
abled. The simulation will first need to be initialized by selecting the Initialize button. Note that the
file specified in the Channel output file field is used during the initialization process. Once the sim-
ulation has been initialized the Run button will be enabled. Selecting the Run button will run the
simulation out to the time specified in the “Run to” field.
The Perform Exciter Response Ratio Simulation Test dialog is a modeless dialog. This means that
it doesn’t have to be dismissed in order to access other program functions.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-25
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
If a bus is specified in the “Bus to be tested” field, the governor response of all machines connected
to the specified bus having connected governor models is tested. If no bus is specified, all machines
with connected governor models are tested. The bus can be specified by entering it directly in the
Bus to be tested field or by selecting the Select button to the right of the field and using the standard
bus selector dialog to select the bus.
The “Initial P.U. loading” field is used to specify the initial machine loading in per unit of machine
base, MBASE. The “P.U. loading step” field is used to specify the load step change to be applied
at TIME equals zero during the simulation. Here again, since the machine initialization to a specified
fraction of rated MVA is based on the value specified as MBASE for each machine, this test
assumes that generator and governor model parameters are entered on actual machine base.
The channel output file, used to capture the output of the Dynamics simulation, is specified in the
“Channel output file” field. The channel output file can be selected by entering it directly in the field
or by selecting the “browse” button to the right of the field and using a standard file selector dialog
to select the file.
The "Run to" field defines the value of simulated TIME at which the simulation activity is to be ter-
minated. When the dialog is brought up, this field contains the present value of simulated TIME.
14-26 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
The values of the "Print every", "Write every" and "Plot every" data items are integer values defining
the interval, in units of the number of simulation time steps, between the recording of output channel
values. Any changes to these settings are remembered and become their initial values the next time
the dialog is brought up.
The "Print every" data item defines the interval to be used in tabulating the values of the output
channels. This tabulation is directed to the defined progress output device.
The "Write every" data item defines the interval to be used in writing the values of the output chan-
nels to the current channel output file. This value is meaningful only if a channel output file had been
specified when the Initialize button was selected.
The "Plot every" data item defines the interval to be used in plotting the values of the CRT plot chan-
nels at the user's CRT workstation. This value is meaningful only if: a channel output file had been
specified when the Initialize button was selected and at least one of the six CRT plot channels
listed in the Dynamics Plotting Channels tab of the Dynamics Spreadsheet has been selected.
When the dialog first appears, if the simulation has not been initialized, the Run button will be dis-
abled. The simulation will first need to be initialized by selecting the Initialize button. Note that the
file specified in the Channel output file field is used during the initialization process. Once the sim-
ulation has been initialized the Run button will be enabled. Selecting the Run button will run the
simulation out to the time specified in the “Run to” field.
The Perform Governor Response Simulation dialog is a modeless dialog. This means that it doesn’t
have to be dismissed in order to access other program functions.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-27
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
The channel output file, used to capture the output of the Dynamics simulation, is specified in the
“Channel output file” field. The channel output file can be selected by entering it directly in the field
or by selecting the “browse” button to the right of the field and using a standard file selector dialog
to select the file.
The "Run to" field defines the value of simulated TIME at which the simulation activity is to be ter-
minated. When the dialog is brought up, this field contains the present value of simulated TIME.
The values of the "Print every", "Write every" and "Plot every" data items are integer values defining
the interval, in units of the number of simulation time steps, between the recording of output channel
values. Any changes to these settings are remembered and become their initial values the next time
the dialog is brought up.
The "Print every" data item defines the interval to be used in tabulating the values of the output
channels. This tabulation is directed to the defined progress output device.
The "Write every" data item defines the interval to be used in writing the values of the output chan-
nels to the current channel output file. This value is meaningful only if a channel output file had been
specified when the Initialize button was selected.
The "Plot every" data item defines the interval to be used in plotting the values of the CRT plot chan-
nels at the user's CRT workstation. This value is meaningful only if: a channel output file had been
14-28 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
specified when the Initialize button was selected and at least one of the six CRT plot channels
listed in the Dynamics Plotting Channels tab of the Dynamics Spreadsheet has been selected.
When the dialog first appears, if the simulation has not been initialized, the Run button will be dis-
abled. The simulation will first need to be initialized by selecting the Initialize button. Note that the
file specified in the Channel output file field is used during the initialization process. Once the sim-
ulation has been initialized the Run button will be enabled.
Selecting the Run button will run the simulation out to the time specified in the “Run to” field. Once
the simulation has been run out to the specified time, disturbances and faults can be applied as well
as changed to solution parameters and options, and the simulation run again out to a new specified
time.
The Perform Extended Term Dynamic Simulation dialog is a modeless dialog. This means that it
doesn’t have to be dismissed in order to access other program functions.
The bus to assign the bus quantity is specified in the “Bus” field. The bus can be specified by
entering it directly in the “Bus” field or by selecting the Select button to the right of the field and using
the standard bus selector dialog to select the bus.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-29
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
The bus quantity to record in the output channel is selected by the “Bus quantity” combo box.
Clicking on this combo box will reveal a list of defined quantities to select from.
The “Starting VAR”, “Starting ICON” and “Output channel” fields are used to describe identifiable
storage locations in the channel output file. These locations are used in other parts of PSS™E to
access this data. The storage locations available for definition depend on the bus quantity selected.
Channel identifiers (two in case of the "Voltage and Angle" bus quantity) to be assigned to the
output channel(s) can be specified by entering them in the appropriate fields. If an identifier field is
blank, PSS™E generates an appropriate identifier.
Selecting the Go button will define the channel as specified in the input fields and then allow another
channel definition. Selecting the Close button will close the dialog without defining any further
channels.
Quantities can be defined for either branches, 2 winding transformers or 3 winding transformers.
Branches and 2 winding transformers are specified by selecting the “Assign channels for branches”
toggle button. The branch or 2 winding transformer is then specified by entering the identifiers
directly in the “From bus”, “To bus” and “Circuit ID” fields or by selecting the Select button to the
right of the field and using the standard line selector dialog to select the line. 3 winding transformers
14-30 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
are specified by selecting the “Assign channels for 3 winding transformers” toggle button. The 3
winding transformer is then specified by entering the identifiers directly in the “From bus”, “To bus”,
“Last bus” and “Circuit ID” fields or by selecting the Select button to the right of the field and using
the standard 3 winding transformer selector dialog to select the 3 winding transformer.
The line quantity to record in the output channel is selected by the “Line quantity” combo box.
Clicking on this combo box will reveal a list of defined quantities to select from.
The “Starting VAR”, “Starting ICON” and “Output channel” fields are used to describe identifiable
storage locations in the channel output file. These locations are used in other parts of PSS™E to
access this data.
Channel identifiers (two in case of the "Flow (PQ)" and “Relay2 (R & X) line quantities) to be
assigned to the output channel(s) can be specified by entering them in the appropriate fields. If an
identifier field is blank, PSS™E generates an appropriate identifier.
Selecting the Go button will define the channel as specified in the input fields and then allow another
channel definition. Selecting the Close button will close the dialog without defining any further
channels.
The load to assign the load quantity is specified in the “Bus” and “Load ID” fields. The load can be
specified by entering it directly in the “Bus” and “Load ID” fields or by selecting the Select button to
the right of the field and using the standard load selector dialog to select the load.
The load quantity to record in the output channel is selected by the “Load quantity” combo box.
Clicking on this combo box will reveal a list of defined quantities to select from.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-31
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
The “Output channel” field is used to describe identifiable channel storage location in the channel
output file. This location is used in other parts of PSS™E to access this data.
The channel identifier can be specified by entering it in the appropriate fields. If the identifier field is
blank, PSS™E generates an appropriate identifier.
Selecting the Go button will define the channel as specified in the input fields and then allow another
channel definition. Selecting the Close button will close the dialog without defining any further
channels.
The machine to assign the machine quantity is specified in the “Bus” and “Machine ID” fields. The
machine can be specified by entering it directly in the “Bus” and “Machine ID” fields or by selecting
the Select button to the right of the field and using the standard machine selector dialog to select
the machine.
The machine quantity to record in the output channel is selected by the “Machine quantity” combo
box. Clicking on this combo box will reveal a list of defined quantities to select from.
The “Output channel” field is used to describe identifiable channel storage location in the channel
output file. This location is used in other parts of PSS™E to access this data.
The channel identifier can be specified by entering it in the appropriate fields. If the identifier field is
blank, PSS™E generates an appropriate identifier.
Selecting the Go button will define the channel as specified in the input fields and then allow another
channel definition. Selecting the Close button will close the dialog without defining any further
channels.
14-32 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
The miscellaneous quantity to record in the output channel is selected by the “Miscellaneous quan-
tity” combo box. Clicking on this combo box will reveal a list of defined quantities to select from.
The “VAR”, “STATE” and “Output channel” fields are used to describe identifiable storage locations
in the channel output file. These locations are used in other parts of PSS™E to access this data.
The storage locations available for definition depend on the bus quantity selected.
The channel identifier can be specified by entering it in the appropriate fields. If the identifier field is
blank, PSS™E generates an appropriate identifier.
Selecting the Go button will define the channel as specified in the input fields and then allow another
channel definition. Selecting the Close button will close the dialog without defining any further
channels.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-33
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
The category to define quantities for is determined by selecting the desired quantity tab at the top
of the dialog which exposes and activates the appropriate controls.
When the "Machine, Bus, Load and Branch Quantities" tab is active, the bus subsystem to be pro-
cessed may be specified as follows:
1. If the "All buses" toggle button is "depressed", all buses from the working case are
selected.
2. If the "Selected bus subsystem" toggle button is "depressed", all buses in the current
bus subsystem are selected. The current bus subsystem may be specified or changed
either by "pressing" the "Select…" button to the right of the "Selected bus subsystem"
toggle button, or by selecting the "Bus subsystem" entry from the "Subsystem" menu
of the menu bar.
14-34 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
3. If "The following buses" toggle button is "depressed", buses may be specified in the
input field to the right of the toggle button. Conventions for specifying buses follow
those of the line mode method of bus selection described in Section 3.10.1.1 of the
PSS™E Program Operation Manual.
When the "Tie Line Quantities" tab is active, the user may select area or zone ties by "depressing"
the appropriate toggle button in the middle of the dialog. The appropriate pair of toggle buttons at
the bottom of the window is enabled and the set of areas or zones to be processed may be specified
as described in the following example. While this description is in terms of areas, the same
approach applies to zones.
1. If the "All areas" toggle button is "depressed", all areas from the working case are
selected.
2. If the "Selected areas" toggle button is "depressed", all areas in the current area sub-
system are selected. The current area subsystem may be specified or changed either
by "pressing" the "Select…" button to the right of the "Selected areas" toggle button, or
by selecting the "Area subsystem" entry from the "Subsystem" menu of the menu bar.
With the "Machine, Bus, Load and Branch Quantities" and the "Tie Line Quantities" tabs, the user
selects the simulation quantity for which data values are to be assigned to output channels by
selecting it from the appropriate "…quantities" combo box. Clicking on this combo box will reveal a
list of defined quantities to select from.
Data for out-of-service equipment may be included in the set of channels generated for a selected
output category by "depressing" the “Include out-of-service equipment” toggle button.
When the "Subsystem Power Totals" is active, the user may select power totals by area, owner or
zone, or power totals for all buses, by "depressing" the appropriate toggle button in the middle of
the window. If the "Areas", "Zones" or "Owners" toggle button is "depressed" the appropriate pair
of toggle is enabled and the set of areas, owners, or zones to be processed may be specified as
described in the previous example. While the previous example is in terms of areas, the same
approach applies to owners and zones. If the “All buses" toggle is "depressed", none of the sub-
system selection toggle buttons at the bottom of the window are enabled. Five channels,
containing totals of mechanical power, electrical power, accelerating power, load active power, and
electrical power - load active power, are added for each area, owner, or zone selected, or for the
entire network, as appropriate.
Assigning channels for "Subsystem Power Totals" requires no simulation quantity or out-of-service
option selection.
When the "Machine angle statistics" tab is active, six channels summarizing machine angles are
assigned. No simulation quantity, out-of-service option, or subsystem selection is required.
The "next available" channel number, VAR index and ICON index are displayed in fields in the
"Starting Indices" group. The starting indices to be used may be specified by editing their values in
the fields.
Selecting the Go button will define the channels as specified in the input fields and then allow
another channel definition. Selecting the Close button will close the dialog without defining any fur-
ther channels.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-35
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
From the “Select model type” combo box, the Dynamics model type to be operated on is selected.
All operations invoked from the buttons in the center of the dialog will be performed on the model
type selected in the combo box.
Selecting “List unconnected models” will list all models of the selected type that are not connected
to any network elements. The listing is printed at the progress report output device.
Selecting “Remove unconnected models” will remove all models of the selected type that are not
connected to any network elements. They will no longer appear in any saved Snapshot or DYRE
files. Each model reference removed from the model tables is reported at the progress report output
device.
Selecting “Pack models” will pack the internal storage tables and removes "holes" (i.e., entries
which are marked as unused) from the model connection table and the array allocation table for all
models of the selected type. If these tables are packed, messages are printed at the progress report
output device.
Selecting “List user models” will list all user models of the selected type found in the active User
Dynamics Dll.
Selecting “Remove unused user models” will delete from the user model definition table any model
definitions of the selected type that are not referenced from the array allocation table. Vacated slots
are available for new model definitions.
14-36 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
Selecting “Consistency check” will perform an internal consistency check for all Plant and Wind
model types. This button is only enabled when Plant or Wind is the selected model type. This check
loops through all machines in the working case and alarms any invalid model combinations at the
progress report output device. This report is in ascending bus number order when the "numbers"
output option is in effect, and in alphabetical bus name order under the "names" option.
Section 5.7.2 details the conditions which are alarmed by the consistency checking function for the
Plant model type.
The top set of toggle buttons allows the user to indicate whether the dynamics model data reporting
function is to be executed in a "reporting mode" or a "data checking mode".
The "List" combo box allows the user to select output for either "All subroutine CONEC models",
"All subroutine CONET models", "All CHAN models", or "Models by subsystem".
If the "Models by subsystem" category is selected, the "Model type to be processed" option menu
and the three subsystem selection toggle buttons are enabled.
The model type to be processed is selected from the “Process” combo box.
1. If the "All buses" radio button is selected, all buses from the working case are selected.
2. If the "Selected bus subsystem" radio button is selected, all buses in the current bus
subsystem are selected. When subsystem selection by owner is enabled, the owner
assignments of each load, machine and branch, rather than the bus(es) to which they
are connected, govern which elements are in the subsystem; for dc lines, FACTS
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-37
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
devices, and auxiliary signal models that are connected to dc lines and FACTS
devices, the buses to which they are connected govern which elements are in the sub-
system. The current bus subsystem may be specified or changed either by "pressing"
the "Select…" button to the right of the "Selected bus subsystem" toggle button, or by
selecting the "Bus subsystem" entry from the "Subsystem" menu of the menu bar.
3. If "The following buses" radio button is selected, buses may be specified in the input
field to the right of the toggle button. Conventions for specifying buses follow those of
the line mode method of bus selection described in Section 3.10.1.1 of the PSS™E
Program Operation Manual.
Selecting the Go button will produce the selected report. When "The following buses" radio button
is selected, selecting the [Return] or [Enter] key on the keyboard while the cursor is positioned in
the input field is equivalent to selecting the Go button.
A data category is selected for reporting by "selecting" the toggle button to the left of its description;
any data category whose toggle button is not “selected” is omitted from the report.
"From" and "To" data items may be specified by editing their values in the corresponding input text
fields. If the "To" index is greater than the "From” index, all entries in the corresponding data cate-
gory between the "From" and "To" entries inclusive are reported; otherwise, only the "From" entry
is printed.
Selecting the "OK" button will generate the report and dismiss the dialog. If no items are “selected”
for reporting, selecting the OK button will have no effect.
14-38 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
Selecting the Reset button restores the "From" and "To" input text fields to values reflecting the
number of elements being used in the current simulation setup.
The model category to list storage locations for is determined by selecting the desired model cate-
gory tab at the top of the dialog which exposes and activates the appropriate controls.
3. Line relay models connected to branches whose "from bus" is in a specified subsystem
of the working case when the "Relay" tab is active.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-39
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
4. Auxiliary signal models connected to dc lines or FACTS devices which have at least
one of their buses in the specified subsystem of the working case when the "Aux. Sig."
tab is active.
5. FACTS device models whose sending end bus is in the specified subsystem of the
working case when the "FACTS dev" tab is active.
6. DC line models which have at least one of their ac buses in the specified subsystem of
the working case when the "DC Line" tab is active.
7. Switched Shunt device models in a specified subsystem of the working case when the
"Switched Shunt" tab is active.
8. Wind machine models in a specified subsystem of the working case when the "Wind
Machines" tab is active.
For each of these model categories, the "Model status" combo box is used to restrict the tabulation
to active models, bypassed models, or both. Bypassed models are identified either with an asterisk
("*") preceding the model name.
When the "Load” tab is active, the radio buttons under "Report On" allow the user to select a report
organized by either models ("Loads connected to model") or loads ("Models connected to loads").
Selecting the Loads connected to model toggle results in a report organized by model, with load-
characteristic models reported first followed by load-relay models. Within these two categories,
models applied by bus are listed first, followed by those applied by subsystem other than bus in
model precedence order (see Program Operation Manual, Volume I, Section 5.1.4). For each
model reported, the loads to which the model is applied are listed. If a load model is not applied at
any loads, it is omitted from the report.
Selecting the Models connected to loads toggle results in a report organized by load. For each
load reported, the model(s) connected to it are listed. Any load with no load-related model con-
nected to it is omitted from the report.
For either presentation, buses are tabulated in ascending numerical or alphabetical order,
according to the bus output option currently in effect. Multiple loads at the same bus are tabulated
in ascending load identifier order.
The "Model status" combo box functions as described above. However, in the case of load models,
bypassed load models are identified either with an asterisk ("*") preceding the model name, or by
following the load element description with the word BYPASSED. The latter format is employed for
bypassed element instances of a subsystem model when the presentation hierarchy is Loads con-
nected to model.
When the "Machines" tab is active, the "Model status" combo box functions as described above,
and the "Model type" combo box is used to select the type(s) of machine-related models to be
reported.
When the "Relay", "Aux. Sig." or "FACTS dev" tab is active, the "Model status" combo box functions
as described above.
When the "DC Line" tab is active, the "Model type" combo box allows the user to indicate the type
of dc lines to be reported: two-terminal dc lines, multi-terminal dc lines, or VSC dc lines. The "Model
status" combo box functions as described above.
14-40 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
When the "Switched Shunts" tab is active, the "Model status" combo box provides for listing all such
models, only those which are active, or only those which are bypassed.
When the "WInd Machines" tab is active, the "Model status" combo box functions as described
above., and the "Model type" combo box is used to select the type(s) of wind machine-related
models to be reported.
The set of network elements whose models are to be reported may be specified as follows:
1. If the "All buses" radio button is selected, models at all buses in the working case are
selected.
2. If the "Selected bus subsystem" radio button is selected, all loads, machines, branches,
dc lines, FACTS devices, switched shunt, and/or wind machines as appropriate, in the
current bus subsystem are selected. When owners are part of the selection criteria, the
owner assignments of each load, machine, and branch, (rather than the bus(es) to
which it is connected) govern which elements are in the subsystem; for dc lines, FACTS
devices, and their auxiliary signals, the owner assignments of the buses to which they
are connected govern which elements are in the subsystem. The current bus sub-
system may be specified or changed either by "pressing" the "Select…" button to the
right of the "Selected bus subsystem" toggle button, or by selecting the "Bus sub-
system" entry from the "Subsystem" menu of the menu bar.
3. If "The following buses" radio button is selected, buses may be specified in the input
field to the right of the toggle, and all loads, machines, branches, dc lines, FACTS
devices, switched shunt, and/or wind machines as appropriate, at the designated
buses are processed. Conventions for specifying buses follow those of the line mode
method of bus selection described in Section 3.10.1.1 of the PSS™E Program Opera-
tion Manual.
Selecting the Go button will generate the selected report. When "The following buses" radio button
is selected, selecting the [Return] or [Enter] key on the keyboard while the cursor is positioned in
the input field is equivalent to selecting the Go button
The tabulation for each model includes a listing of the locations in the various dynamics data arrays
used by the model, and a flag for models which are bypassed. Models which are connected to ele-
ments which are not contained in the working case are excluded from the report.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-41
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
14-42 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
The "Largest derivative…" and "Perturbation amount…" data items may be specified by editing their
values in the edit fields in the appropriate field.
The file into which the results for use by the auxiliary program LSYSAN is specified in the "Matrix
output file" field. Alternatively, the "Select…" button to the right of the edit field may be selected to
allow the specification of the file via a file selector window.
The state variables to be included in the system matrices are specified using a pair of input fields
("From…" and "…To") with increment/decrement arrows and an "Add" button. These are used to
construct a list of STATE numbers and/or ranges of STATE numbers. The user may either edit the
values in the edit fields or "press" the increment/decrement arrows to the right of the edit fields;
selecting the Add button then adds the specified STATEs to the "Selected States" list. All STATEs
between the "From…" and "…To" STATE numbers inclusive are added to the scrolled list if the
"…To" STATE number exceeds the "From…” STATE number. Otherwise, the "From…" STATE is
added to the list. Selecting a list entry so that it is highlighted and selecting the Remove button is
used to remove an entry from the list.
The output channels to be used as system outputs are specified using a similar approach.
The “Buses” section at the bottom of the dialog allows the specification of a system input variable
whose value is to be perturbed. The resulting calculation is used to construct columns of the "B"
and "F" system matrices. Up to 20 items may be specified.
The "Input quantity" combo box allows the selection of the quantity to be perturbed. Either “EFD”,
“Pmech”, “Vothsg”, “Vref” or “Var” may be selected.
The perturbation data value may be modified by editing the value in the “Perturbation” edit field.
If a machine quantity is selected (any “Input quantity other than “Var”), the user must designate the
machine whose selected quantity is to be perturbed. The machine to apply the perturbation to is
specified in the “Bus” and “Machine ID” fields. The machine can be specified by entering it directly
in the “Bus” and “Machine ID” fields or by selecting the Select button to the right of the field and
using the standard machine selector dialog to select the machine.
If “Var” is selected in the “Input quantity” combo box, the user must designate its index in the "Var
number" edit field.
An identifier can be assigned to the input quantity in the "Identifier" edit field. If this field is blank,
PSS™E generates an appropriate identifier.
Selecting the OK button processes the selected items and creates the Matrix output file for use in
the LSYSAN program. Selecting the OK button with no file specified in the "Matrix output file" field
is invalid. If no entries are in the "Selected States" scrolled list at the time the OK button is
"pressed", activity ASTR includes all STATEs in the system matrices. If no entries are in the
"Selected Channels" list at the time the OK button is selected, all channels (or the first fifty if the
system model contains more than fifty output channels) are included as system outputs.
Selecting the Cancel button closes the dialog without performing any processing.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-43
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
The bus to fault is specified in the “Apply fault at bus” field. The bus can be specified by entering it
directly in the “Apply fault at bus” field or by selecting the Select button to the right of the field and
using the standard bus selector dialog to select the bus.
The "Base kV" field is set to the base voltage of the specified bus as contained in the current
network.
The value of fault admittance is calculated based the settings of the "Units" radio button, the imped-
ance or admittance edit fields, and, except for faults specified in MVA, the "Base kV" edit field. The
"MHO's" and "OHM's" radio buttons are enabled only if the "Base KV" field contains a positive value.
When the dialog is opened, these fields are set such that a three phase fault is applied. The spec-
ification of these data items is identical to that used in the APPLY FAULT BUS command of activity
PSAS.
Selecting the OK button replaces the fixed shunt at the designated bus with the MVA admittance
equivalent to the values entered in the fault specification edit fields. The bus faulting dialog is then
dismissed.
Selecting the Cancel button dismisses the dialog without faulting any bus.
14-44 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
The branch or 2 winding transformer to fault is specified in the “Apply fault on branch” fields. These
fields are enabled by selecting the “Apply fault on branch” radio button. The branch or 2 winding
transformer can be specified by entering it directly in the ”From bus”, “To bus” and ”Circuit ID” fields
or by selecting the Select button to the right of the fields and using the standard branch/2 winding
transformer selector dialog to select the branch or 2 winding transformer.
The 3 winding transformer to fault is specified in the “Apply fault on 3 winding transformer” fields.
These fields are enabled by selecting the “Apply fault on 3 winding transformer” radio button. The
3 winding transformer can be specified by entering it directly in the ”From bus”, “To bus”, “Last bus”
and ”Circuit ID” fields or by selecting the Select button to the right of the fields and using the stan-
dard 3 winding transformer selector dialog to select the 3 winding transformer.
The "Base kV" field is set to the base voltage of the specified "From" bus as contained in the working
case.
The value of fault admittance is calculated based the settings of the "Units" toggle switches, the
impedance or admittance input fields, and, except for faults specified in MVA, the "Base kV" input
field. The "MHO’s" and "OHM's" toggle buttons are enabled only if the "Base KV" field contains a
positive value. When the window is brought up, these fields are set such that a three phase fault is
applied. The specification of these data items is identical to that used in the APPLY FAULT
BRANCH command of activity PSAS.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-45
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
Selecting the OK button replaces the line shunt at the "from" bus end of the designated branch with
the p.u. admittance equivalent to the values entered in the fault specification edit fields. The branch
faulting dialog is then dismissed.
Selecting the Cancel button dismisses the dialog without faulting any line.
The scrolled list in the window lists those buses and/or branches which have been faulted in the
current execution of PSS™E but which have not as yet been cleared. When the dialog is opened,
the last entry in the list is automatically selected (i.e., it is highlighted). The user may select another
fault for clearing by "single clicking" on its description.
Selecting the Go button clears the selected fault by returning the data items of the faulted bus or
branch to the values that were present at the time the fault was applied and leaves the dialog active
for another selection. Selecting the Go button with no fault selected from the scrolled list is invalid.
Selecting the Close button dismisses the dialog without clearing any faults.
14-46 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
The branch or 2 winding transformer to trip is specified in the “Trip a branch” fields. These fields are
enabled by selecting the “Trip a branch” radio button. The branch or 2 winding transformer can be
specified by entering it directly in the ”From bus”, “To bus” and ”Circuit ID” fields or by selecting the
Select button to the right of the fields and using the standard branch/2 winding transformer selector
dialog to select the branch or 2 winding transformer.
The 3 winding transformer to trip is specified in the “Trip a 3 winding transformer” fields. These fields
are enabled by selecting the “Trip a 3 winding transformer” radio button. The 3 winding transformer
can be specified by entering it directly in the ”From bus”, “To bus”, “Last bus” and ”Circuit ID” fields
or by selecting the Select button to the right of the fields and using the standard 3 winding trans-
former selector dialog to select the 3 winding transformer.
Selecting the OK button sets the status of the designated branch to zero (out-of-service) and dis-
misses the dialog.
Selecting the Cancel button dismisses the dialog without tripping any branch.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-47
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
The branch or 2 winding transformer to close is specified in the “Close a tripped branch” fields.
These fields are enabled by selecting the “Close a tripped branch” radio button. The branch or 2
winding transformer can be specified by entering it directly in the ”From bus”, “To bus” and ”Circuit
ID” fields or by selecting the Select button to the right of the fields and using the standard branch/2
winding transformer selector dialog to select the branch or 2 winding transformer.
The 3 winding transformer to close is specified in the “Close a tripped 3 winding transformer” fields.
These fields are enabled by selecting the “Close a tripped 3 winding transformer” radio button. The
3 winding transformer can be specified by entering it directly in the ”From bus”, “To bus”, “Last bus”
and ”Circuit ID” fields or by selecting the Select button to the right of the fields and using the stan-
dard 3 winding transformer selector dialog to select the 3 winding transformer.
Selecting the OK button sets the status of the designated branch to one (in-service) and dismisses
the dialog.
Selecting the Cancel button dismisses the dialog without closing any branch.
14-48 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
The bus to disconnect is specified in the “Select bus” field. The bus can be specified by entering it
directly in the “Select bus” field or by selecting the Select button to the right of the field and using
the standard bus selector dialog to select the bus.
Selecting the OK button electrically disconnects the specified bus and dismisses the dialog.
Selecting the Cancel button dismisses the dialog without disconnecting any bus.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-49
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
The machine to change the Vref for is specified in the “Bus” and “Machine ID” fields. The machine
can be specified by entering it directly in the “Bus” and “Machine ID” fields or by selecting the Select
button to the right of the field and using the standard machine selector dialog to select the machine.
The existing Vref value for the specified machine can either be incremented/decremented or a
totally new value specified. If the “Increment/Decrement” radio button is selected, the edit field to
the right of the radio button contains the value to increment/decrement the existing Vref value by.
A positive value will increment the existing Vref, a negative value will decrement the existing Vref.
If the “New value” radio button is selected, the edit field to the right of the radio button contains the
new Vref value to use for the specified machine.
Selecting the OK button will set the specified machines Vref value as indicated and dismisses the
dialog.
Selecting the Cancel button dismisses the dialog without changing any Vref values.
14-50 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
The bus to fault is specified in the “Apply fault at bus” field. The bus can be specified by entering it
directly in the “Apply fault at bus” field or by selecting the Select button to the right of the field and
using the standard bus selector dialog to select the bus.
The type of unbalance to be applied is selected with the "Unbalance type" combo box.
Fault impedances are displayed in edit fields which may be edited using standard windows
techniques.
If the single line-to-ground fault is specified in the "Unbalance type" combo box, the complex fault
impedance (Rl-g + jXl-g) is specified in the two "L-G fault impedance" edit fields.
If the double line-to-ground fault is specified in the "Unbalance type" combo box, the line-to-ground
impedance (Rl-g + jXl-g) is specified in the two "L-G fault impedance" input fields, and the line-to-
line impedance (Rl-l + jXl-l) is specified in the two "L-L fault impedance" edit fields.
If DC lines and/or FACTS devices are present in the network, the “DC line and FACTS devices
option” combo box is enabled. The user has the option of block loading unblocked DC lines and in-
service FACTS devices or converting constant admittance load on them by selecting the appro-
priate element from the combo box.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-51
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
If the actual positive sequence impedance of any transformer in the working case differs from its
nominal value, the user has the option of applying the same correction factor to the zero sequence
impedances of all such transformers by selecting the "Apply transformer impedance to zero correc-
tion" toggle button; if this button is not selected the zero sequence impedances of all such
transformers are left at their nominal values.
Selecting the OK button initiates the fault calculation. The calculated equivalent positive sequence
fault admittance is added to the fixed shunt at the designated bus and the dialog is dismissed.
Selecting the Cancel button dismisses the dialog without faulting any bus.
14-52 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
The non-transformer branch to be subjected to the unbalance can be specified by entering it directly
in the ”From bus”, “To bus” and ”Circuit ID” fields or by selecting the Select button to the right of the
fields and using the standard non- transformer branch selector dialog to select the non-transformer
branch.
The type of unbalance to be applied is selected with the "Unbalance type" combo box.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-53
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
If the user elects to ground the open phase, the grounding impedance (Rl-g+ jXl-g) is specified in
the two "Line to ground impedance" edit fields. The location of the fault is defined in per unit of total
line length from the specified "from" bus. The "slider bar" is used to define the fault location.
"Clicking” on either side of the slider bar handle increments or decrements the slider bar position by
about one tenth of its total range.
In-Line Fault
For the in-line fault unbalance, either a line-to-ground, a double line-to-ground, or a three phase
fault may be applied. The user selects the type of fault by the use of the "Type of in-line fault" combo
box.
If the user selects the single line-to-ground fault, the complex fault impedance (Rl-g + jXl-g) is spec-
ified in the two "Line to ground impedance" input fields.
If the user selects the double line-to-ground fault, the line-to-ground impedance (Rl-g + jXl-g) is
specified in the two "Line to ground impedance" input fields, and the line-to-line impedance (Rl-l +
jXl-l) is specified in the two "Line to line impedance" input fields.
If the user selects the three phase fault, no fault impedance input is required.
The location of the fault is defined in per unit of total line length from the specified "from" bus. The
"slider bar" near the center of the window is used to define the fault location. "Clicking" on either
side of the slider bar handle increments or decrements the slider bar position by about one tenth of
its total range.
If the user elects to ground the open phase, the grounding impedance (Rl-g + jXl-g) is specified in
the two "Line to ground impedance" edit fields. The location of the fault is defined in per unit of total
line length from the specified "from" bus. The "slider bar" near the center of the window is used to
define the fault location. "Clicking” on either side of the slider bar handle increments or decrements
the slider bar position by about one tenth of its total range.
The "Select open end" radio button is used to designate the end of the line at which the breaker is
open: either the "from" bus or "to" bus as specified in the edit fields at the top of the dialog.
14-54 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Dynamic Simulation Interface
Users Manual Overview: Dynamics Interface
If the actual positive sequence impedance of any transformer in the working case differs from its
nominal value, the user has the option of applying the same correction factor to the zero sequence
impedances of all such transformers by selecting the "Apply impedance correction table to zero
sequence transformers" toggle button; if this button is not selected, the zero sequence impedances
of all such transformers are left at their nominal values.
Selecting the OK button initiates the fault calculation. The calculated positive sequence pi-equiva-
lent replaces the branch parameters of the branch subjected to the unbalance and the dialog is
dismissed.
Selecting the Cancel button dismisses the dialog without calculating any branch unbalance.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 14-55
Dynamic Simulation Interface PSS™E-31.0
Overview: Dynamics Interface Users Manual
14-56 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Chapter 15
Compiling and Creating
User DLL
Siemens Power Transmission & Distribution, Inc., Power Technologies International 15-1
Compiling and Creating User DLL PSS™E-31.0
Using createusrdll Users Manual
When the application is launched, the dialog that appears will be as shown in Figure 15-1.
15-2 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Compiling and Creating User DLL
Users Manual Using createusrdll
Siemens Power Transmission & Distribution, Inc., Power Technologies International 15-3
Compiling and Creating User DLL PSS™E-31.0
Using createusrdll Users Manual
15.2.5 Move Up
The ’Move Up’ is used to move one or more source file up the ’List of Model Source Files’.
When a fortran source file is a fortran module file, this file needs to compiled first, so that
the “.mod” created by compiler is available for other fortran source files during their compi-
lation.
To move a file up, select the appropriate source file in “List of Model Source Files” and use
‘Move Up’ button to bring the selected file ahead of other fortran file.
15.2.6 Compile
Compiles all the files in “List of Model Source Files”, and adds the resulting objects to “List
of Model Object/Lib Files”.
15-4 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Compiling and Creating User DLL
Users Manual Application Notes
# File: mymodelfiles.txt
# Input to "createusrdll" program.
# Any text on a line after "#" is treated as comment.
# The file has three sets data records, with each record title as:
# [dll name], [source file names] and [object/lib file names].
# Provide only one dll name in [dll name] record.
# Provide each source file name (.flx, .for, .f90, .f) on a separate
line in [source file names]
# record.
# Provide each object (.obj) or library (.lib) on a separate line
in [source file names] record.
[dll name]
c:\work_dir\myusrmodel.dll
Siemens Power Transmission & Distribution, Inc., Power Technologies International 15-5
Compiling and Creating User DLL PSS™E-31.0
Application Notes Users Manual
15-6 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Chapter 16
Creating and Viewing the Results
of Dynamic Simulations
In order to view the plots, a Plot Book has to be created. The Plot Book is configured like an Excel
Worksheet with multiple Plot Pages each capable of displaying several Plots. A Plot in turn can con-
tain several channels/curves/traces. A Plot Book by default will contain on Page with one Plot on
that Page.
After a Plot Book is created, a channel output file has to be opened. The channel output file will
appear in the Tree View, which, when expanded, will display all the channel outputs that were
selected prior to the Dynamic Simulation run.
Any channel output quantity can be viewed by dragging and dropping into the Plot Page.
16.1.2 Recording
Many of the interactions involved in creating and customizing the Plot Book are recordable and can
be played back through the use of Automation files. In future releases, most of the Plot Book inter-
actions will be recordable and available for playback.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 16-1
Creating and Viewing the Results of Dynamic Simulations PSS™E-31.0
Dynamics Results Interface Elements Users Manual
16-2 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Creating and Viewing the Results of Dynamic Simulations
Users Manual Dynamics Results Interface Elements
Figure 16-2. Plot Book
Siemens Power Transmission & Distribution, Inc., Power Technologies International 16-3
Creating and Viewing the Results of Dynamic Simulations PSS™E-31.0
Dynamics Results Interface Elements Users Manual
The active Plot on the Plot Page is indicated by the red-border that surrounds the plot. All interactive
actions, such as adding channels or changing the Plot appearance take place in the active Plot.
16-4 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Creating and Viewing the Results of Dynamic Simulations
Users Manual Dynamics Results Interface Elements
Figure 16-4. Accessing the Plot Editor through the Context Menu
The Plot Editor allows the configuration of various properties of the Plot, such as Axis, Titles,
Legend, colors etc. (Figure 16-5).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 16-5
Creating and Viewing the Results of Dynamic Simulations PSS™E-31.0
Dynamics Results Interface Elements Users Manual
16-6 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Creating and Viewing the Results of Dynamic Simulations
Users Manual Dynamics Results Interface Elements
Siemens Power Transmission & Distribution, Inc., Power Technologies International 16-7
Creating and Viewing the Results of Dynamic Simulations PSS™E-31.0
Dynamics Results Interface Elements Users Manual
16-8 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Chapter 17
Event Studies
When the Event Study is run as a Dynamics Event Study, Event Items are implemented as Distur-
bance APIs when a match is available, and as general Network APIs when no defined disturbance
API exists e.g. Load connect/disconnect events. Event Items in a Dynamics Event Study have a
time element associated with them and are performed in ascending time sequence.
When the Event Study is run as a Power Flow Study, Fault Event Items are mapped to SCMU APIs
and network Event Items are mapped to Network APIs. Currently, simultaneous Fault Events are
not supported and so any simultaneous Events in the Event Study are de-activated and only the
first encountered Fault Event is performed.
Dynamics and Power Flow event studies can be accessed in several different ways. Event studies
can be added and viewed by accessing the Dynamics tab in the Tree View. Individual event items
can be added to the active study from the tree view, from the diagram, and from the event spread-
sheet. The event spreadsheet enables the user to edit the events belonging to the active study.
Event Studies are preserved in an external file with an *.evs suffix. Through the use of the Event
Study file, defined Event Studies maybe used with more than one set of files.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 17-1
Event Studies PSS™E-31.0
Overview: Event Studies Users Manual
17-2 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Event Studies
Users Manual Dynamics Tab Tree View
If an event studies file has not been opened, or if no studies are listed, a right-click will bring up a
popup menu (see Figure 17-2). If "Add Event Study" is selected, the user will be prompted to select
an existing event studies file, or to create a new file.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 17-3
Event Studies PSS™E-31.0
Dynamics Tab Tree View Users Manual
Once an existing file has been selected or a new file has been named, the Event Studies Properties
dialog will be displayed (see Figure 17-4).
17-4 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Event Studies
Users Manual Dynamics Tab Tree View
The following fields are used only if the Event Study is run as a Dynamics Event Study. The values
in these fields have no significance if the Event Study is run as a Power Flow Event Study. The
"Study length" field specifies, in seconds, the total duration of the event study. The "Integration step"
is the time interval, in seconds, between steps. The "Tolerance" field specifies the PSS™E dynamic
simulation convergence tolerance, and the "Iteration limit" field specifies the PSS™E dynamic sim-
ulation iteration limit. The "Print interval", "Graph interval" and "Plot interval" fields specify the
number of steps between text outputs, channel file outputs, and plot results output. Click the OK
button and the defined study will be added to the event study tree. The new study just added
becomes the active study. The active study is the only study to which event items can be added
from the diagram and from the network tree.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 17-5
Event Studies PSS™E-31.0
Dynamics Tab Tree View Users Manual
When "Add Event Item" is selected from the popup menu, the Event Item Properties Dialog is dis-
played (see Figure 17-6).
17-6 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Event Studies
Users Manual Dynamics Tab Tree View
Figure 17-6. Event Item Properties Dialog
Siemens Power Transmission & Distribution, Inc., Power Technologies International 17-7
Event Studies PSS™E-31.0
Dynamics Tab Tree View Users Manual
The Event Item Properties dialog allows the user to specify the Event Items which will be part of the
selected study. The "Name" field can be edited to suit the user. The "Time" field contains the time
at which this event item occurs. As mentioned previously, the "Time" field is only used if the Event
Study is run as a Dynamics Event Study (ensure that this value is less than the total time duration
of the entire event study.) A drop-down list of available "Event Types" is available (see Figure 17-6).
When an "Event type" is selected, the appropriate "Network Item" lines will become enabled for
selection. For example, if the "Event Type", Disconnect Machine is selected from the list, all of the
Machine fields will become enabled. Click on the Select button to bring up the standard machine
selector dialog (see Figure 17-7).
Select a machine, click the OK button, and the Machine "Bus (number)" and "Machine ID" fields will
be filled in on the Event Item Properties dialog (see Figure 17-8).
17-8 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Event Studies
Users Manual Dynamics Tab Tree View
Click the Add button to save the event and to configure another event item. If an "Event Type" that
pertains to a line is selected, both the "Branch" and the "3WTrans" fields will be enabled. When the
selected "Event Type" requires Fault data, the "Resistance" and "Reactance" fields will be enabled.
When finished, click the Close button. The configured event items are displayed on the Event
Studies tree (see Figure 17-9).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 17-9
Event Studies PSS™E-31.0
Dynamics Tab Tree View Users Manual
Selecting the "Edit" option brings up an Event Spreadsheet (see Figure 17-11).
17-10 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Event Studies
Users Manual Dynamics Tab Tree View
Figure 17-11. Event Spreadsheet
Siemens Power Transmission & Distribution, Inc., Power Technologies International 17-11
Event Studies PSS™E-31.0
Dynamics Tab Tree View Users Manual
The Event Spreadsheet displays the parameters for those event items which belong to the active
study. All data items which are not grayed out can be modified. The values will be saved when the
cursor moves to another line of data. If more than one event study exists in a file, only those items
belonging to the active study will appear in the spreadsheet (see Figure 17-12).
17-12 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Event Studies
Users Manual Dynamics Tab Tree View
If there is more than one study available, selecting either the "Run Dynamic Study" or the "Run
Power Flow Study" option will bring up the Select Event Study dialog from which you can select the
desired study (see Figure 17-15).
Siemens Power Transmission & Distribution, Inc., Power Technologies International 17-13
Event Studies PSS™E-31.0
Dynamics Tab Tree View Users Manual
When the desired study has been selected, click the OK button, and execution of the chosen study
type will begin. Note that in order to run a Dynamic Study, dynamics data must be present.
17-14 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Event Studies
Users Manual Network Tab Tree View
Select one of the available Events to be created. A dialog for data input will be activated (see
Figure 17-18). Modify the default values and click on the OK button to add the event to the active
study. The title of the dialog and the data values available will depend on the type of Event being
added.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 17-15
Event Studies PSS™E-31.0
Network Tab Tree View Users Manual
17-16 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Event Studies
Users Manual One-line Diagrams
Siemens Power Transmission & Distribution, Inc., Power Technologies International 17-17
Event Studies PSS™E-31.0
One-line Diagrams Users Manual
Selection of an available event type will bring up an event data dialog (see Figure 17-22).
17-18 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Event Studies
Users Manual One-line Diagrams
When finished editing values, click the OK button to add the event to the active study.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 17-19
This page intentionally left blank.
17-20 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Chapter 18
Scenarios
Siemens Power Transmission & Distribution, Inc., Power Technologies International 18-1
Scenarios PSS™E-31.0
Overview: Scenarios Users Manual
If a Scenario file already exists, it can be opened through a file selection dialog and all the files con-
tained within will be opened/loaded automatically.
18-2 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Scenarios
Users Manual Scenario Menu Bar Entries
Once a Scenario file has been opened, opening and referencing files in PSS™E will automatically
add them to the Scenario.
The Scenario file can be saved at any time, either to the same name or to a different name.
Closing an open Scenario file will close/unload all files contained in the Scenario.
Files may also be added or removed from an open Scenario through the use of the Scenario Editor.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 18-3
Scenarios PSS™E-31.0
Scenario Menu Bar Entries Users Manual
Figure 18-2. Scenario File Editor
18-4 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Scenarios
Users Manual Scenario Menu Bar Entries
The fields at the top of the dialog list the creation and modification dates of the Scenario as well as
the version of PSS™E for which the Scenario was originally created. They also show the login ID
of the user who created and last updated the Scenario. The RootPath field shows the file path which
is used to complete the files listed in the Scenario. The RootPath is changed by selecting the
“browse” button to the right of the field and using a standard file directory selector dialog to select
the new RootPath. If a file was added to the Scenario in a directory other than that described by the
RootPath, the full path will be described for this file.
Files can be added to the Scenario by selecting the Add button. The File Add dialog (see Figure 18-
3) can then be used to select the individual files to add to the Scenario. The file type combo box is
used to specify the type of file to add to the scenario. Certain file types, such as RAW, SAV, DYR
and SNP can only have one instance in a Scenario file. If one already exists, adding a new one will
replace the existing file. Other files types, such as SLD file, can have multiple instances in the Sce-
nario File.
Files are removed from the Scenario by selecting the file (see Figure 18-4) and selecting the
Remove button.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 18-5
Scenarios PSS™E-31.0
Scenario Menu Bar Entries Users Manual
Figure 18-4. File Selected for Removal from Scenario
18-6 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Scenarios
Users Manual Scenario Menu Bar Entries
Changes made to the Scenario can be saved directly from the Scenario Editor dialog by selecting
the Apply button. If the changes are not saved in this dialog, they can be saved from the Menu Bar
as previously described.
Siemens Power Transmission & Distribution, Inc., Power Technologies International 18-7
Scenarios PSS™E-31.0
Scenario Menu Bar Entries Users Manual
18-8 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Appendix A
Activity Map
Users of previous versions of PSS™E will be familiar with the four letter activity name interface. The
"Activities" which comprise all analytical functions, I/O control and program automation can be ini-
tiated via the pull-down menus or by typing in the four letter activity name in the command line.
The Activity Selector has been replaced with a Microsoft® Windows-based graphical user interface
for all analysis. In future versions of PSS™E there will be diminished use of four letter names.
In order to assist users of previous versions of the program to navigate the user interface, Activity
names are mapped to the appropriate menu item and/or toolbar button as shown in the following
tables.
File>Open…
MCRE
Select files of type "Machine Impedance Data file (*.rwm)"
RETI File>Import>Long title (RETI)… n.a.*
* Not applicable.
Siemens Power Transmission & Distribution, Inc., Power Technologies International A-1
Activity Map PSS™E-31.0
Load Flow Data Changes Users Manual
Toolbar
Activity Menu Item
Button
CHTI File>Case titles, short & long (CHTI)… n.a.
DSCN
Power Flow>Changing>Disconnect / Reconnect Bus (DSCN/RECN)…
RECN
A-2 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Activity Map
Users Manual Load Flow Solution Activities
INLF Power Flow>Solution>N-R solution with inertial / governer dispatch (INLF)… n.a.
Siemens Power Transmission & Distribution, Inc., Power Technologies International A-3
Activity Map PSS™E-31.0
Matrix Handling Activities Users Manual
Toolbar
Activity Menu Item
Button
Power Flow>Reports>Limit checking reports…
GENS
Select tab "Generator bus"
Power Flow>Reports>Limit checking reports…
GEOL
Select tab "Machine terminal"
Power Flow>Reports>Limit checking reports…
GCAP
Select tab "Reactive capability"
Power Flow>List data…
SHNT
Select "Bus shunts"
DIFF File>Compare…
DFTI Select tab "Power Flow Cases" for DIFF, "Tie Lines" for DFTI, and "Case Totals" n.a.
CMPR for CMPR
AREA Power Flow>Reports>Area / owner / zone totals…
OWNR
ZONE Select desired report and subsystem
TIES
TIEZ Power Flow>Reports>Area / zone based reports…
INTA Select desired report and subsystem
INTZ
File>File information (SIZE/SHOW/BUSN)…
SIZE n.a.
Select "List the number of system components"
Power Flow>List data…
OUTS
Select "Outaged equipment"
BRCH Power Flow>Check data>Branch parameters (BRCH)… n.a.
TREE Power Flow>Check data> Buses not in swing bus tree (TREE)
A-4 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Activity Map
Users Manual Switching Studies
Siemens Power Transmission & Distribution, Inc., Power Technologies International A-5
Activity Map PSS™E-31.0
Dynamics Data Users Manual
Toolbar
Activity Menu Item
Button
Power Flow>List Data…
SQEX
Select "Examine Power Flow / sequence data" and "Sequence data"
SQCH Obsolete (replaced with Spreadsheet View) OBSOLETE
File>Save or Show…
RWSQ
Select tab "Sequence Data"
Fault>Setup network for unbalanced solution (SEQD)…
SEQD
May also be performed from the SCMU and SPCB dialogs
A-6 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Activity Map
Users Manual Dynamics Simulation
Toolbar
Activity Menu Item
Button
Dynamics spreadsheet
ALTR n.a.
Select tab "Dynamics Data"
Dynamics>Define simulation output…
CHAN
For Bus channels, select "Bus quantity"
Dynamics>Define simulation output…
CHAN
For Line channels, select "Line quantity"
Dynamics>Define simulation output…
CHAN
For Load channels, select "Load quantity"
Dynamics>Define simulation output…
CHAN
For Machine channels, select "Machine quantity"
Dynamics>Define simulation output…
CHAN n.a.
For Miscellaneous channels, select "Misc quantity"
All data editing functions are available in the Dynamics and Network
Edit n.a.
spreadsheets.
MSTR,
Dynamics>Simulation>Perform extended term simulation…
MRUN
GSTR,
Dynamics>Simulation>Perform governor response simulation…
GRUN
ASTR Dynamics>Build matrices for LSYSAN program… n.a.
Siemens Power Transmission & Distribution, Inc., Power Technologies International A-7
Activity Map PSS™E-31.0
External Interfaces Users Manual
A-8 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Activity Map
Users Manual Load Flow User-Tailored Execution
Toolbar
Activity Menu Item
Button
Power Flow>Linear Network>Interchange limits with two opposing systems
POLY n.a.
(POLY)…
MWMI Power Flow>Linear Network>Midwest MW-mile calculation (MWMI)… n.a.
NOPF OPF>Solve…
File>Save or Show…
RWOP
Select tab "Optimal Power Flow Data"
Siemens Power Transmission & Distribution, Inc., Power Technologies International A-9
Activity Map PSS™E-31.0
I/O Control Users Manual
A.21 Miscellaneous
Toolbar
Activity Menu Item
Button
A-10 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Appendix B
Compatibility Issues
As PSS™E continues to evolve, one of our primary concerns is to ensure backward compatibility
so that current studies can be transferred to the latest program release with minimum disruption.
With each new release of PSS™E, users are usually required to generate a new set of working files.
In addition, dynamic simulation users need to recompile their connection subroutines and user-
written models, and relink them into the main body of PSS™E.
While the vast majority of program dialog remains unchanged, the introduction of new program fea-
tures can affect the dialog. Accordingly, it is recommended that the first use in a new program
release of any existing Response File or IPLAN program be monitored closely to ensure that it per-
forms as intended.
The following sections discuss compatibility issues pertaining to the previous releases of PSS™E.
Users upgrading from a release earlier than the one immediately preceding the current release are
strongly encouraged to review the notes below pertaining to all intervening program releases.
B.1 PSS™E-30.0
B.1.1 General
With the exception of the Power Flow Raw Data File format and a few data input files in which buses
may be specified using their extended bus names (see Chapter 3), there is complete compatibility
between PSS™E-29 and PSS™E-30 at the data input file level. That is, any other binary or source
data file which could be successfully accessed by PSS™E-29 should also be able to be read by
PSS™E-30.
At PSS™E-30, provision is made for "calling" new sets of auxiliary-signal, dc line and FACTS
device models from internal PSS™E tables; that is, the use of these models requires no calls in
subroutines CONEC and/or CONET. Further, additional statements that were needed in CONEC
to place the auxiliary-signal "VAR" into the dc line and FACTS device "other signal VAR", are no
longer required. Nonetheless, a dynamics setup used in PSS™E-29 is able to be used in PSS™E-
30 almost without any change. Dynamic simulation snapshot files from PSS™E-20 through
PSS™E-29 can be read by PSS™E-30.
Other than the addition of the "USRAUX", "USRDCL", and "USRFCT" routines (see Section B.1.3),
a dynamics setup used in PSS™E-29, PSS™E-28 or PSS™E-27 is able to be used in PSS™E-30
without change. The connection routines (CONEC, CONET, USRXXX, USRLOD and USRREL)
and user-written models used in PSS™E-29, PSS™E-28 or PSS™E-27, along with the new
USRAUX, USRDCL, and USRFCT routines, need only be recompiled.
Siemens Power Transmission & Distribution, Inc., Power Technologies International B-1
Compatibility Issues PSS™E-31.0
PSS™E-30.0 Users Manual
The connection routines and user-written models used in PSS™E-26 also require the addition of
the USRREL routine (see Program Operation Manual, Section D.5.4); the connection routines and
user-written models used in PSS™E-25 also require the addition of the USRLOD routine (see
Program Operation Manual, Section D.6.2); those used in PSS™E-20 through PSS™E-24 may
require additional minor modifications (see Program Operation Manual, Section D.7.2). To access
simulation setups from PSS™E-19 or earlier, see the PSS™E-20 update notes below. While a mid-
run Snapshot File written by PSS™E-22 or earlier may be accessed with activity RSTR of PSS™E-
30, it may not be used for the purpose of continuing the interrupted run; the entire simulation must
be executed.
The majority of PSS™E-30 activities and functions are identical in dialog to PSS™E-29. Dialog
changes that have occurred as a result of new program features are described below (new program
features are summarized in Section B.1.6 and chapters in this Users Manual). Any Response Files
and IPLAN programs used with PSS™E-29 that contain any of these line mode dialog streams
and/or "BAT_" commands need to be modified before they can be used in PSS™E-30.
• In activities READ, RDCH and TREA, the switched shunt and FACTS device data
record formats have been changed. Refer to Section B.1.2.
• In activities READ,NAME, RDCH,NAME and TREA,NAME, any extended bus names
in the input stream must be converted so as to recognize the widening of bus names
from 8 to 12 characters. Refer to Section B.1.2.
• In specifying buses with the bus input program option setting in its names mode,
extended bus names must be converted so as to recognize the widening of bus names
from 8 to 12 characters. Refer to Section B.1.2.
• In the BAT_SWITCHED_SHUNT_DATA command, the dimension of the REALAR
array is increased from 11 to 12 in order to accommodate the new RMPCT data item.
Refer to Section B.1.2, Chapter 3, and the manual PSS™E Application Program Inter-
face (API).
• In the BAT_FACTS_DATA command, the dimension of the REALAR array is increased
from 12 to 13 in order to accommodate the new RMPCT data item. Refer to
Section B.1.2, Chapter 3, and the manual PSS™E Application Program Interface
(API).
• In changing switched shunt data in activity CHNG, the new RMPCT data item is
inserted between the controlled bus number and the VSC dc line name data items in
numbers input mode, and between the present switched shunt admittance and the
VSC dc line name data items in names input mode.
• In changing three-winding transformer data in activity CHNG, two additional groups of
data, adjustment data for windings two and three, are presented for possible modifica-
tion by the user. These appear before the final group of data, the ownership data.
• In executing activity DIFF in line mode, an additional prompt to specify the transformer
ratio and angle thresholds is issued when the transformer difference check is selected.
In the BAT_DIFF command, THRESH(2) and THRESH(3) are the ratio and angle
thresholds, respectively, when APIOPT is 2 and STATUS(2) is 22. Refer to the manual
PSS™E Application Program Interface (API).
B-2 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Compatibility Issues
Users Manual PSS™E-30.0
• In the BAT_ECDI command, new APIOPT values are introduced. While the format of
the command is unchanged, the number of consecutive references required is
changed. Refer to the manual PSS™E Application Program Interface (API).
• In the BAT_DCLF command, the dimension of the STATUS array is increased from 3
to 4 in order to accommodate the user’s specification of a continue/abort selection
when the initial active power mismatch exceeds 0.5 MW. Refer to the manual PSS™E
Application Program Interface (API).
• The graphical output of activity POLY is now available only in the new interface. In the
BAT_POLY command, an additional data item to specify a Results output file is
required. Refer to the manual PSS™E Application Program Interface (API).
• In the BAT_SEQ_TWO_WINDING_DATA command, the dimension of the REALAR
array is increased from 4 to 6 in order to accommodate the new winding two side
grounding impedance when the connection code is 8. Refer to Chapter 3 and the
manual PSS™E Application Program Interface (API).
• In the BAT_SEQD command, the dimension of the OPTIONS array is reduced from 3
to 2; the old usage of the OPTIONS(1) entry is removed since there is no longer a
double precision option (see Section B.1.6). Refer to PSS™E Application Program
Interface (API).
• Similarly, in the BAT_SCMU command when APIOPT is 1, the first 2 rather than the
first 3 elements of the OPTIONS array are used; the old usage of the OPTIONS(1)
entry is removed since there is no longer a double precision option (see Section B.1.6).
Refer to PSS™E Application Program Interface (API).
• The format of the ASCC Relay Output File has been modified as a result of the wider
bus number and name fields. Results for winding faults of three-winding transformer
windings are now included.
• In activities DOCU and DYDA, the numeric response codes in the model type selection
prompt for CONEC models and CONET models (and CHAN models in activity DOCU)
have each been increased by five. Corresponding changes have been made in the
values used in the STATUS(3) value passed to the BAT_DOCU command and in the
STATUS(2) value passed to the BAT_DYDA command.
• Four PSS™E option setting commands introduced at PSS™E-29 have had their
names changed as follows: BAT_AREA_INTERCHANGE_CONTROL to
BAT_CONTROL_AREA_INTERCHANGE; BAT_SIZE_LEVEL to
BAT_BUS_SIZE_LEVEL; BAT_SAVE_OPTION_SETTINGS to
BAT_WRITE_OPTIONS_FILE; and BAT_MULTISECTION_LINE_REPORTING to
BAT_MULTISECTION_REPORTING.
• The following load flow data changing commands have had their names changed as
follows: BAT_TWO_TERMINAL_DC_CONVERTER_DATA to
BAT_TWO_TERM_DC_CONVR_DATA;
BAT_VSC_DC_LINE_CONVERTER_DATA to
BAT_VSC_DC_CONVERTER_DATA;
BAT_MULTI_TERMINAL_DC_BUS_DATA to
BAT_MULTI_TERM_DC_BUS_DATA;
BAT_MULTI_TERMINAL_DC_CONVERTER_DATA to
BAT_MULTI_TERM_DC_CONVR_DATA;
BAT_MULTI_TERMINAL_DC_LINE_DATA to
BAT_MULTI_TERM_DC_LINE_DATA;
Siemens Power Transmission & Distribution, Inc., Power Technologies International B-3
Compatibility Issues PSS™E-31.0
PSS™E-30.0 Users Manual
and BAT_MULTI_TERMINAL_DC_LINK_DATA to
BAT_MULTI_TERM_DC_LINK_DATA.
B.1.2 Power Flow Raw Data File and Other Input Files
The following are the changes to the Power Flow Raw Data File format:
• The switched shunt data record contains an additional data item. An RMPCT field is
inserted between the SWREM and RMIDNT fields (see Chapter 3).
• The FACTS device data record contains an additional data item. An RMPCT field is
inserted between the LINX and OWNER fields (see Chapter 3).
• The fourth and fifth records of the three-winding transformer data input block have been
extended to accommodate adjustment data for the windings two and three (see
Chapter 3). Their formats are identical to that of the third record which contains data
that applies to winding one.
In addition, any Power Flow Raw Data File or any Response File containing power flow raw data
input records in which extended bus names are specified (i.e., they require the "names" input option
of activity READ, TREA or RDCH) need to have each extended bus name modified to reflect the
increase in bus name width from 8 to 12 characters. That is, old extended bus names consisted of
the 8 character bus name followed by up to 6 characters containing the bus base voltage; new
extended bus names consist of the 12 character bus name followed by up to 6 characters con-
taining the bus base voltage. Thus, old extended bus names are converted to new extended bus
names by inserting four blanks between the old 8 character name and the base voltage field.
A format conversion program, CNV30, is supplied with PSS™E-30. It converts Power Flow Raw
Data Files from the format required in PSS™E-29 to that required in PSS™E-30. CNV30 includes
provision for expanding extended bus names to the form required by PSS™E-30.
Similarly, in using Response Files, IPLAN programs, and several data input files when the PSS™E
bus input option is at its "names" setting, bus identifiers are either allowed or required to be specified
as extended bus names. Data input files to which this applies include Dynamics Data Files used by
activity DYRE, Linear Network Analysis Data File used by activities DFAX and RANK, Drawing
Coordinate Data Files used by activities DRED, GDIF and SCGR, PSEB and PSAS Command Files
used by activities PSEB and PSAS respectively, and Graphical Report Definition Files used by
activity GRPG. Such input files may be brought up to the form required by PSS™E-30 by manually
editing them to insert four blanks between the name and base voltage portions of any extended bus
names.
Alternatively, PSS™E-30 includes provision for temporarily instructing the extended bus name
search routine to accept as input the extended bus name form used at PSS™E-29 and earlier
releases (eight character alphanumeric bus name plus up to six characters containing the bus base
voltage), and then convert it to the PSS™E-30 form by inserting four blanks between the name and
base voltage portions of the PSS™E-29 extended bus name. The extended bus name form flag
may be placed in either the PSS™E-29 or PSS™E-30 setting by using:
B-4 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Compatibility Issues
Users Manual PSS™E-30.0
• Place the extended bus name form flag in its PSS™E-29 setting by using the batch
command or menu entry listed above.
• Execute the Response File, IPLAN program, or data input activity.
• Place the extended bus name form flag back in its PSS™E-30 setting by using the
batch command or menu entry listed above. Do not omit this step.
This approach should always be successful for the processing of data input files. However, the exe-
cution of Response Files and IPLAN programs should be checked to verify that they behaved as
intended.
Each Dynamics Data Input File model data record referencing one of the old dc line, and FACTS
device models is converted internally by activity DYRE to one of the corresponding new table-driven
dc line and FACTS device models respectively. Activity DYRE notifies the user of each conversion
that takes place. The new versions of these models do not require calls in CONEC and CONET;
rather they are called from internal tables in the same manner that the other "table-ized" plant-
related models are called.
CDC1 CDC1T
CDC4 CDC4T
CDC6 CDC6T
CDC6A CDC6TA
CDCAB1 CDCABT
CEELR2 CEEL2T
CEEL CEELT
Siemens Power Transmission & Distribution, Inc., Power Technologies International B-5
Compatibility Issues PSS™E-31.0
PSS™E-30.0 Users Manual
MTDC01 MTDC1T
MTDC03 MTDC3T
CSTCON CSTCNT
In all cases, there is a one-to-one correspondence between the CON data list for the old model and
the new model to which it is converted. In all, except in the FACTS device model CSTCNT, the
ICON list between the old model and the new model to which it is converted is modified. The old
model set for CDC1, CDC4, CDC6, CDC6A, CDCAB1, CEELR2, CEEL, MTDC01, and MTDC03
contained ICON space for PSS™E internal memory. In the table-ized model, this has been
removed from the ICON data list. Hence while using the corresponding new models CDC1T,
CDC4T, CDC6T, CDC6TA, CDCABT, CEEL2T, CEELT, MTDC1T, and MTDC3T, the user need
not input ICON data for memory.
Unlike in the case of dc lines and FACTS devices, each Dynamics Data Input File model data record
referencing one of the old auxiliary-signal models is not converted internally by activity DYRE to the
corresponding new table-driven model. The reason for this is that the auxiliary-signal models in the
table-driven form require additional data to be input in the Dynamics Data Input File. Activity DYRE
notifies the user to convert the old auxiliary-signal model name to the corresponding new model.
The following table lists the correspondence between the old and new auxiliary-signal model
names.
CPPAUX CPPAUT
DCVREF DCVRFT
PAUX1 PAUX1T
PAUX2 PAUX2T
SQBAUX SQBAUT
CHAAUX CHAAUT
DCCAUX DCCAUT
HVDCAU HVDCAT
RBKELR RBKELT
In all cases, there is a one-to-one correspondence between the CON data list for the old model and
the new model to which it is converted. In all cases, except in RBKELR model, there is a one-to-
one correspondence between the ICON data list for the old model and the new model to which it is
converted. Model RBKELR contained ICON space for PSS™E internal memory. In the table-ized
model, this has been removed from the ICON data list. Hence while using the corresponding new
model RBKELT, the user need not input ICON data for memory.
At PSS™E-30, two options for handling dynamic simulation setups from PSS™E-29 which include
calls in CONEC and/or CONET to any of the old dc line, FACTS device, or auxiliary-signal models
listed above are available:
B-6 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Compatibility Issues
Users Manual PSS™E-30.0
1. The old setup may be used. The only change required is the addition of the following
codes to the bottom of the file containing the FLECS code of subroutine CONEC:
Then the modified CONEC file, the original CONET file, and any user-written models
used in the simulation need to be recompiled, and PSS™E relinked. Using this
approach, dynamic simulations are executed using the old auxiliary-signal, dc line and
FACTS device models called from subroutines CONEC and CONET.
The file conec.flx in the PSS™E "Example" subdirectory contains the default version of
the USRAUX, USRDCL, and USRFCT subroutines as well as those of USRXXX, USR-
LOD and USRREL subroutines.
2. Proceed as if the old setup is to be used as above. Pick up the old Snapshot File and
use activity DYDA to produce a Dynamics Data Input File, which will include data
records for the models. There are two possible cases:
• If the case does not have any old auxiliary-signal models, use activity DYRE to
read the Dynamics Data Input File. If there are old dc line and FACTS device mod-
els, activity DYRE internally converts the old model data records to models from
the new set.
• If the case has old auxiliary-signal models, the auxiliary-signal model records in the
Dynamics Data Input File created as a result of activity DYDA needs to be edited.
If the old auxiliary-signal model is any one of the following: CPPAUX, DCVREF,
PAUX1, PAUX2, CHAAUX, DCCAUX, or HVDCAU, the Dynamics Data Input File
created as a result of activity DYDA would have the corresponding new model
names, and would look as follows:
**DevId ' New Model Name' **DevType **AuxIndex data
items /
Siemens Power Transmission & Distribution, Inc., Power Technologies International B-7
Compatibility Issues PSS™E-31.0
PSS™E-30.0 Users Manual
This has to be edited to specify the device index in place of "**DevId", the device
type in place of "**DevType", and the auxiliary signal index (or the signal injection
point) in place of "**AuxIndex".
If the old auxiliary-signal model is any one of the following: SQBAUX or RBKELR
(these can be used only with two-terminal dc line models), the Dynamics Data Input
File created as a result of activity DYDA would already have the device index, the
device type (which is "1" for two-terminal dc lines), and the corresponding new
model name. The only editing that would be needed is to specify the auxiliary signal
index (or the signal injection point) in place of "**AuxIndex".
Dynamics memory should then be preserved with activity SNAP, the new CONEC
and CONET files recompiled, any user-written models used in the simulation
recompiled, and PSS™E re-linked.
Siemens PTI recommends that the second procedure, or an equivalent variant thereof, eventually
be employed. The old models are considered obsolete and will be removed from PSS™E at a future
program release.
Multi-terminal dc line model "MTDC02" in pre-PSS™E-30 versions was not recognized by activity
DYRE, and the call to this model had to be introduced manually in CONEC and CONET. At
PSS™E-30, this model is called MTDC2T, and is a standard model that is recognized by activity
DYRE. The new model does not require calls in CONEC and CONET; rather it is called from internal
PSS™E tables.
K1=IBITS(MACNUM(ISLOT),0,16)
and the machine index of the low pressure (or second) machine is obtained via a statement such as:
K2=IBITS(MACNUM(ISLOT),16,16)
where IBITS is the FORTRAN intrinsic function for extracting consecutive bits from an integer vari-
able, and ISLOT is the second argument of the model’s SUBROUTINE statement (refer to the
Program Operation Manual, Sections 9.4 and 9.6).
B-8 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Compatibility Issues
Users Manual PSS™E-30.0
BAT_OPF_ADJBRX_INDV, BAT_OPF_ADJBRX_SUBSYS
BAT_OPF_ADJVAR_INDV, BAT_OPF_ADJVAR_SUBSYS
BAT_APDSP_TBL
BAT_BRFLW_3WT_INDV, BAT_BRFLW_BRN_INDV
BAT_BRFLW_SUBSYS
BAT_BUS_INDV, BAT_BUS_SUBSYS
BAT_GEN_RCAP_INDV, BAT_GEN_RCAP_SUBSYS
BAT_GENDSP_INDV, BAT_GENDSP_SUBSYS
BAT_INTFLW_MAIN
• PSS™E now allows six digit bus numbers (through 999997). In addition, bus, area,
zone, owner, transformer, dc bus, and VSC dc line names have been increased from
eight to twelve characters. As a result, all report formats have been modified, some
drastically (for example, activities LIST and SQLI have additional data categories).
• Two additional control strategies for switched shunts have been implemented. Remote
voltage control to a setpoint by switched shunts is now allowed. A switched shunt may
be used to control the reactive power setting of another switched shunt (see Chapter
3.)
• Multiple setpoint mode voltage controlling devices (generation, switched shunts, VSC
dc line converters, and the shunt elements at the sending end of FACTS devices) are
allowed on the same bus and on buses connected by zero impedance lines. Similarly,
different types of setpoint mode voltage controlling devices connected to the same or
different buses may be controlling the same bus voltage.
• An RMPCT data item is now associated with switched shunts and FACTS devices.
• Any or all windings of three-winding transformers may be specified as being automati-
cally adjusted during power flow solutions. In the area interchange control monitor of
the power flow solution activities, slack bus active power limits are now listed. Further,
if an old or new active power setting is outside of its active power limits, the active
power is followed by an asterisk ("*").
• The AC Contingency Calculation solution (ACCC) now processes the SET, CHANGE,
INCREASE, DECREASE, MOVE and ADD contingency events.
Siemens Power Transmission & Distribution, Inc., Power Technologies International B-9
Compatibility Issues PSS™E-31.0
PSS™E-30.0 Users Manual
• In looking for non-converged contingency cases which are "close to" convergence, the
AC Contingency Report function now applies the "Bus mismatch tolerance" and the
"System mismatch tolerance" only to those contingency cases which were terminated
by the non-divergent solution option or due to reaching the iteration limit. Those system
conditions which converged in the AC Contingency Calculation function are always
considered converged by the reporting function.
• In reporting two-winding transformers in activities POUT, LOUT and LAMP, the winding
two tap ratio, rather than the winding one tap ratio and phase shift angle, is printed in
the output block of the winding two bus (i.e., when the winding two bus is the "from
bus"). That is, the tap settings reported are always those adjacent to the bus being
reported.
• In activity DIFF, windings of three-winding transformers are included in the branch
related checks. In the transformer check, the user may now specify difference thresh-
olds for reporting ratio and angle differences.
• In activity BRCH, ratings are included in the output of the parallel transformer report.
• In the new interface, the Optimal Power Flow (OPF) is able to import an Economic Dis-
patch Data File, as used by activity ECDI, into the OPF cost curve data structure.
• The fault analysis activities SEQD, SCMU, ASCC, SCGR and SPCB now use double
precision arithmetic for their fault calculations. These calculations are much faster than
the old double precision option of activities ASCC, SCGR and SEQD,DP.
• The "flat" option of activities ASCC and SCGR no longer uses a matrix modification
technique, which would occasionally fail, for calculating line out and line end faults.
• The Disturbance>Calculate and Apply Branch Unbalance option of the dynamic simu-
lation activity selector calculates and applies a single branch unbalance. The
unbalance calculation is identical to that of activity SPCB.
• The maximum bus dimensional capacity has been increased to 150,000 buses. The
maximum number of areas, owners, and zones which may be represented has been
increased to 1,200, 1,200, and 2,000, respectively (see Table 1-1).
• Two new auxiliary programs have been added: CNV30 converts a PSS™E-29 Raw
Data File to a Raw Data File in the form required by PSS™E-30; RAW29 outputs a
PSS™E Saved Case in PSS™E-29 Raw Data File form.
• The PSS™E interface routines for use in IPLAN programs include several new subrou-
tines. The SWSDT1 subroutine returns floating point data of switched shunts.
SC3WND may be used to access short circuit currents on three-winding transformer
windings following a fault calculation by activity SCMU. AREUSE, ZONUSE and
OWNUSE indicate if any equipment is assigned to a specified area, zone or owner,
respectively. Further, several new STRING values are recognized by subroutines
XFRDAT, DC2DAT, DCNDAT and FCDDAT. See the IPLAN Program Manual.
• New sets of models for dc line, FACTS device, and auxiliary-signal models have been
developed which are called from internal PSS™E tables. This is similar to the approach
used for plant-related, load related, and line relay models in that the use of these
models do not require calls in subroutine CONEC and/or CONET. The new set of
models supersedes the pre-PSS™E-30 set of CONEC and CONET models.
• Three new DYRE data record categories called "USRAUX", "USRDCL", and
"USRFCT" have been introduced for user written models of auxiliary-signal models, dc
line models and FACTS device models respectively.
B-10 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Compatibility Issues
Users Manual PSS™E-30.0
• The following new models are added to the simulation model library:
• Updates and new features of the Optimal Power Flow are described in the PSS™E
Optimal Power Flow (OPF) Manual.
In moving a single machine (via the Edit>Changing>Move>Machine to another bus option or the
BAT_MOVEMAC command) or load (via the Edit>Changing>Move>Load to another bus option
or the BAT_MOVELOAD command) to another bus with a new identifier specified, the new identifier
was ignored unless there already existed at least one machine (or load, as appropriate) at the des-
tination bus.
Siemens Power Transmission & Distribution, Inc., Power Technologies International B-11
This page intentionally left blank.
B-12 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Appendix C
Start-up Commands
The following arguments can be specified on the command line when starting the program:
Siemens Power Transmission & Distribution, Inc., Power Technologies International C-1
This page intentionally left blank.
C-2 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Appendix D
Line Mode Interpreter
The historic command line interface to PSS™E has been replaced with a modern, event-driven
GUI. There exist many response files, representing many man-hours of development effort that use
the command line "language", as well as IPLAN programs that also utilize it via the PUSH set of
commands. An interpreter (LMI) has been developed to support these usages that read in
sequences of the command line "language" and calls the appropriate PSS™E API routine - the
same API routines that are called by the PSS™E GUI. This is desirable for recording and translation
purposes, consistency of behavior, and quality of maintenance. Given this mode of operation the
imitation cannot be perfect. This document attempts to capture and summarize the differences.
D.1.1 General
1. Activities that are not permitted (i.e., optional purchase, activity selector, required data,
etc.) will absorb all inputs, and produce errors only afterwards.
3. Many warning or informative messages that would have appeared during the dialog will
no longer be displayed, or will be displayed at the end of the dialog. In general, if a mes-
sage presented information needed to respond to a prompt it was maintained; if it was
strictly informational, it was not (although many are later produced by the API routines).
4. Many data errors that depended on values from the case that could short-circuit the
activity dialog will no longer occur (the errors will still occur, but later in the dialog) (see
some omitted activity data checks, below). In general, if data values could generate
additional prompts, or modify the sequence of prompts, those checks are maintained;
if the data values produced errors that simply aborted the activity, they were not (for
exceptions, see differences in behavior: by activity, below).
5. Bus subsystems with multiple base kV ranges not supported (actually, this is a limita-
tion of the entire interface).
6. Activities that output data files will have report or printer selections directed to progress
window instead (actually, this is a limitation of the API design). Only file and terminal
choices are presented. The LMI dialog will still absorb printer/copies/etc. inputs, even
though those choices will not be presented in the initial menu.
Siemens Power Transmission & Distribution, Inc., Power Technologies International D-1
Line Mode Interpreter PSS™E-31.0
Differences in Behavior Users Manual
7. Device selection menus no longer present the with or without page breaks alternative;
use lines-per-page to control.
8. Next page dialog for report output is ignored. It compares to running the old interface
with the CRT lines per page (OPTN option 23) set to the maximum.
9. Terminal input of data will not verify any values until all data is entered. Some prompts
may then be repeated (as progress information).
10. Inputs that could accept certain characters or numeric input will not produce data type
errors for other character inputs, but will be treated as zero (e.g., CHNG allows 'Q' for
data change lines. Entering, say, 'x' will be treated as zero.)
11. Names input is allowed, but all APIs are called with bus numbers (means that if you
record your input, you will see bus numbers, not names) (this is true of the entire inter-
face). Quoted strings are allowed for bus names, which is a new feature, but within that
string the length of the "name" portion of the extended name is still fixed.
12. Names input mode would generate extra input lines (i.e., the bus names would always
be requested on a separate line from everything else). The interpreter simply accepts
bus names instead of bus numbers when in names input mode.
D.1.2 By Activity
Other than the general differences cited in Section D.1.1.
1. MENU, HELP, DRED, and GRED will be ignored, except for HELP, NEW.
2. IDEV, EXEC will be recognized in response files and IPLAN programs only.
3. Immediate (@) commands will be recognized in response files and IPLAN programs
only.
4. ECHO works as always, but this is misleading. What ECHO does and always did was
to make a copy of all inputs received from the terminal, or standard input device. In the
LMI implementation, the only such inputs are responses to prompts generated from
IPLAN INPUT and INPUTLN calls, and the equivalent Python API calls.
5. PSAS and PSEB run only in CHECK mode when entered interactively; when used from
a response file or an IPLAN program they can automatically invoke the created
response file.
6. PSAS and PSEB HELP commands will not process until command input is terminated.
10. SIZE and CATA output to the report device, not the progress device.
D-2 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Line Mode Interpreter
Users Manual Differences in Behavior
13. Entering * for CASE only works in old interface if entered on same line as CASE. In the
LMI it can also be entered later; similarly for SAVE, SNAP, RSTR.
14. GOUT/GEXM will use line mode dialog for CRT display.
16. DRAW options to plot by page (or Cycle Through All Pages option) or by bus are not
supported (dialog will be absorbed).
17. All DRAW dialog subsequent to plot, other than device and options selections, are
ignored (but absorbed). Line mode commands generated from the diagram are not
recognized.
18. DRAW options are ignored, except for CHECK. However, the one-line drawing func-
tions are philosophically different. In DRAW, drawing elements were required to match
network elements, unless DRAW was run in ACCEPT mode, in which case the entire
drawing was simply considered a picture, with no correspondence to the network case.
The new one-line diagram allows for bound and unbound items on the diagram, and
the coordinate data file input process attempts to bind what it can, and draws all
remaining items as unbound.
22. TLTG/SPIL will ask for the study and opposing systems by label rather than by number;
also it will always ask for these labels, even if the DFAX file has only 1 or 2 subsystems
specified.
24. EEQV will ask whether to ’SUPPRESS EQUIVALENCING OF PHASE SHIFTER’ if any
appropriate transformer exists in case, and prior to the subsystem selection dialog (line
mode asked only after the first such transformer was selected for the subsystem).
27. SPLT presents loads, machines, and branches at a bus in ID order rather than in load
order.
Siemens Power Transmission & Distribution, Inc., Power Technologies International D-3
28. Block data records in terminal input mode will always generate prompts.
29. STRT always asks for an OUTPUT file, and skips asking for a snapshot file if errors are
returned from the STRT API.
30. DYRE will not check whether the CONEC and CONET filenames are the same.
D-4 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Appendix E
Sample Data Files
Siemens Power Transmission & Distribution, Inc., Power Technologies International E-1
Sample Data Files PSS™E-31.0
SAVNW Case Data Input Files Users Manual
E-2 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Users Manual
PSS™E-31.0
Siemens Power Transmission & Distribution, Inc., Power Technologies International
Figure E-1. SAVNW Load Flow Raw Data File savnw.raw (1 of 2 Sheets)
Sample Data Files PSS™E-31.0
SAVNW Case Data Input Files Users Manual
Figure E-1 (Cont). SAVNW Load Flow Raw Data File savnw.raw (2 of 2 Sheets)
E-4 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Sample Data Files
Users Manual SAVNW Case Data Input Files
Siemens Power Transmission & Distribution, Inc., Power Technologies International E-5
Sample Data Files PSS™E-31.0
SAVNW Case Data Input Files Users Manual
Figure E-3. SAVNW Slider Diagram File savnw.sld
E-6 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Sample Data Files
Users Manual SAVNW Case Data Input Files
101 1 6.5 0.06 0.20 0.050 1.80 1.75 0.60 0.80 0.30 /GENROU
102 1 6.5 0.06 0.20 0.050 1.80 1.75 0.60 0.80 0.30 /GENROU
206 1 4.5 0.07 0.15 0.050 1.40 1.35 0.50 0.70 0.25 /GENROU
211 1 5.0 0.05 0.0 0.200 1.00 0.75 0.40 0.00 0.26 /GENSAL
3011 1 5.0 0.06 0.20 0.060 1.60 1.55 0.70 0.85 0.35 /GENROU
3018 1 5.0 0.06 0.20 0.060 1.60 1.55 0.70 0.85 0.35 /GENROU
0
Siemens Power Transmission & Distribution, Inc., Power Technologies International E-7
Sample Data Files PSS™E-31.0
SAMPLE Case Data Input Files Users Manual
Figure E-6. SAMPLE Load Flow Raw Data File sample.raw (1 of 4 Sheets)
E-8 Siemens Power Transmission & Distribution, Inc., Power Technologies International
Users Manual
PSS™E-31.0
Siemens Power Transmission & Distribution, Inc., Power Technologies International
101,'1 ', 750.000, 104.978, 400.000, -100.000,1.01000, 0, 900.000, 0.01000, 0.30000, 0.00000, 0.00000,1.00000,1, 100.0, 800.000, 50.000, 1,0.1289, 2,0.2524, 3,0.1031, 4,0.5156
102,'1 ', 650.000, 112.745, 410.000, -110.000,1.01000, 0, 950.000, 0.01050, 0.32000, 0.00000, 0.00000,1.00000,1, 100.0, 700.000, 33.000, 1,0.3647, 2,0.1838, 3,0.0751, 4,0.3764
206,'1 ', 800.000, 283.913, 500.000, -400.000,1.00000, 0, 1000.000, 0.01060, 0.25100, 0.00000, 0.00000,1.00000,1, 100.0, 850.000, 50.000, 1,0.1034, 2,0.4006, 3,0.0825, 4,0.4135
211,'1 ', 600.000, 87.292, 510.000, -100.000,1.00000, 0, 725.000, 0.01080, 0.26200, 0.00000, 0.00000,1.00000,1, 100.0, 616.000, 30.000, 1,0.1423, 2,0.2210, 3,0.1842, 4,0.4525
301,'1 ', 996.883, 299.543, 700.000, -650.000,1.00000, 0, 1067.000, 0.01090, 0.23000, 0.01400, 0.12600,1.02500,1, 98.0, 1010.000, 320.000, 1,0.1118, 2,0.2184, 3,0.0893, 4,0.5805
301,'2 ', 996.883, 299.543, 710.000, -600.000,1.00000, 0, 1070.000, 0.01100, 0.24000, 0.01100, 0.12700,1.02600,1, 98.0, 1011.000, 321.000, 1,0.1173, 2,0.3200, 3,0.0936, 4,0.4691
301,'3 ', 996.883, 299.543, 720.000, -600.000,1.00000, 0, 1075.000, 0.00800, 0.25000, 0.01200, 0.12800,1.02700,1, 98.0, 1012.000, 322.000, 1,0.1260, 2,0.2268, 3,0.1827, 4,0.4644
401,'1 ', 321.000, 142.325, 600.000, -100.000,1.00000, 0, 600.000, 0.01230, 0.22230, 0.00000, 0.00000,1.00000,1, 90.0, 350.000, 25.000, 1,0.1625, 2,0.2423, 3,0.0990, 4,0.4962
402,'1 ', 321.000, 142.325, 610.000, -110.000,1.00000, 0, 610.000, 0.00450, 0.24320, 0.00000, 0.00000,1.00000,1, 91.0, 351.000, 26.000, 1,0.1588, 2,0.2117, 3,0.1959, 4,0.4335
3011,'1 ', 1316.962, 148.216, 620.000, -120.000,1.00000, 0, 1050.000, 0.00760, 0.35430, 0.00000, 0.00000,1.00000,1, 92.0, 1400.000, 100.000, 1,0.1452, 2,0.1926, 3,0.2677, 4,0.3945
3018,'1 ', 400.000, -0.628, 300.000, -150.000,0.99000, 0, 530.000, 0.08700, 0.35630, 0.00000, 0.00000,1.00000,1, 92.5, 500.000, 50.000, 1,0.1043, 2,0.2037, 3,0.2749, 4,0.4171
3018,'2 ', 100.000, -0.157, 75.000, -75.000,0.99000, 0, 120.000, 0.02400, 0.35530, 0.00000, 0.00000,1.00000,1, 92.5, 110.000, 20.000, 1,0.3003, 2,0.1358, 3,0.2857, 4,0.2782
0 / END OF GENERATOR DATA, BEGIN BRANCH DATA
151, -152,'1 ', 0.00260, 0.04600, 3.50000, 1200.00, 1100.00, 1000.00, 0.01000, -0.25000, 0.01100, -0.15000,1, 150.00, 1,0.2000, 2,0.3000, 3,0.4000, 4,0.1000
151, -152,'2 ', 0.00261, 0.04610, 3.51000, 1205.00, 1105.00, 1005.00, 0.01300, -0.25100, 0.01200, -0.02000,1, 149.00, 5,0.2315, 1,0.3056, 2,0.3704, 3,0.0926
151, -201,'1 ', 0.00100, 0.01500, 1.20000, 1206.00, 1106.00, 1006.00, 0.00000, 0.00000, 0.00000, -1.00000,1, 100.00, 2,0.3600, 3,0.2400, 4,0.3200, 5,0.0800
152, 202,'1 ', 0.00080, 0.01000, 0.95000, 1207.00, 1107.00, 1007.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 200.00, 1,0.3939, 2,0.2273, 3,0.3030, 4,0.0758
152, -3004,'1 ', 0.00300, 0.03000, 2.50000, 0.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 201.00, 5,0.2379, 1,0.3033, 2,0.3667, 3,0.0922
153, -154,'2 ', 0.00600, 0.05400, 0.15000, 350.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 80.00, 2,0.2727, 3,0.2727, 4,0.3636, 5,0.0909
153, -3006,'1 ', 0.00000, 0.00010, 0.00000, 0.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 0.00, 1,0.3443, 2,0.2459, 3,0.3279, 4,0.0820
154, 155,'1 ', 0.00500, 0.04500, 0.10000, 400.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 81.00, 5,0.1914, 1,0.2535, 2,0.3065, 3,0.2486
154, -203,'1 ', 0.00400, 0.04000, 0.10000, 400.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 100.00, 2,0.2000, 3,0.3000, 4,0.4000, 5,0.1000
154, -205,'1 ', 0.00033, 0.00333, 0.09000, 600.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 120.00, 1,0.1667, 2,0.2500, 3,0.3333, 4,0.2500
154, -3008,'1 ', 0.00270, 0.02200, 0.30000, 800.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 119.00, 5,0.1925, 1,0.2550, 2,0.3083, 3,0.2442
201, -202,'1 ', 0.00200, 0.02500, 2.00000, 1200.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 300.00, 2,0.1905, 3,0.2857, 4,0.3810, 5,0.1429
201, -207,'C1', 0.00150, 0.01500, 1.25000, 1200.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 250.00, 1,0.2500, 2,0.3750, 3,0.2500, 4,0.1250
203, 205,'1 ', 0.00500, 0.04500, 0.08000, 200.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 70.00, 5,0.1925, 1,0.2550, 2,0.3083, 3,0.2442
204, -207,'C2', 0.00150, 0.01500, 1.25000, 1200.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 300.00, 2,0.2000, 3,0.3000, 4,0.4000, 5,0.1000
205, 212,'1 ', 0.00000, 0.01000, 0.00000, 1250.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 71.00, 1,0.2000, 2,0.3000, 3,0.4000, 4,0.1000
205, -214,'2 ', 0.00200, 0.02500, 2.00000, 1200.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 100.00, 5,0.2100, 1,0.2782, 2,0.3364, 3,0.1755
205, -216,'3 ', 0.00500, 0.04500, 0.08000, 200.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 81.00, 2,0.1818, 3,0.2727, 4,0.3636, 5,0.1818
205, -217,'4 ', 0.00500, 0.04500, 0.08000, 200.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 80.00, 1,0.1667, 2,0.2500, 3,0.3333, 4,0.2500
205, -218,'5 ', 0.00500, 0.04500, 0.08000, 200.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 59.00, 5,0.1650, 1,0.2186, 2,0.2643, 3,0.3521
213, -214,'1 ', 0.00000, 0.01000, 0.00000, 1250.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 0.50, 2,0.1429, 3,0.2143, 4,0.2857, 5,0.3571
3001, -3003,'1 ', 0.00000, 0.00800, 0.00000, 0.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 70.00, 1,0.1639, 2,0.2459, 3,0.3279, 4,0.2623
3002, -3004,'1 ', 0.00600, 0.05400, 0.09000, 0.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 200.00, 5,0.1925, 1,0.2550, 2,0.3083, 3,0.2442
3003, -3005,'1 ', 0.00600, 0.05400, 0.09000, 0.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 90.00, 2,0.2000, 3,0.3000, 4,0.4000, 5,0.1000
3003, -3005,'2 ', 0.00600, 0.05400, 0.09000, 0.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 90.00, 1,0.1333, 2,0.2000, 3,0.2667, 4,0.4000
3005, -3006,'1 ', 0.00350, 0.03000, 0.07000, 0.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 70.00, 5,0.1650, 1,0.2186, 2,0.2643, 3,0.3521
3005, -3007,'1 ', 0.00300, 0.02500, 0.06000, 0.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 80.00, 2,0.1527, 3,0.2290, 4,0.3053, 5,0.3130
3005, -3008,'1 ', 0.00600, 0.05000, 0.12000, 0.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,0, 60.00, 1,0.1802, 2,0.2703, 3,0.3604, 4,0.1892
3007, -3008,'1 ', 0.00300, 0.02500, 0.06000, 0.00, 0.00, 0.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 60.00, 5,0.1858, 1,0.2462, 2,0.4023, 3,0.1657
3008, -3009,'1 ', 0.00300, 0.02500, 0.06000, 25.00, 22.00, 18.00, 0.00000, 0.00000, 0.00000, 0.00000,1, 60.00, 1,0.1797, 2,0.2695, 3,0.3594, 4,0.1914
0 / END OF BRANCH DATA, BEGIN TRANSFORMER DATA
101, 151, 0,'T1',2,2,1, 0.17147, 0.10288,2,'NUCA GSU ',1, 1,0.3200, 2,0.3900, 3,0.1400, 4,0.1500
0.00110, 0.09100, 1200.00
21.6000, 21.600, 0.000, 1200.00, 1100.00, 1000.00, 1, 101,22.68000,20.52000, 1.05000, 0.95000, 25, 0, 0.00021, 0.00051
Figure E-6 (Cont). SAMPLE Load Flow Raw Data File sample.raw (2 of 4 Sheets)
E-9
SAMPLE Case Data Input Files
Sample Data Files
E-10
201, 211, 0,'T6',2,1,2, 262500, 0.00300,2,'HYDRO_G XMER',1, 1,0.1400, 2,0.1500, 3,0.3200, 4,0.3900
0.00026, 0.01343, 700.00
500.000, 500.000, 0.000, 700.00, 650.00, 611.00, 0, 0, 1.10000, 0.90000, 1.10000, 0.90000, 5, 0, 0.00000, 0.00000
20.0000, 20.000
203, 202, 0,'T7',1,2,1, 0.00095, 0.00046,1,'EAST PS ',1, 1,0.2754, 2,0.3261, 3,0.2899, 4,0.1087
0.00210, 0.05400, 750.00
0.99000, 230.000, 0.143, 750.00, 700.00, 657.00, 3, 0,12.00000,-11.0000,-900.000,-950.000, 33, 1, 0.00000, 0.00000
1.00000, 500.000
204, 205, 0,'T8',1,2,1, 0.00113, 0.00052,2,'SUB LTC ',1, 1,0.3019, 2,0.4245, 3,0.1321, 4,0.1415
Siemens Power Transmission & Distribution, Inc., Power Technologies International
Users Manual
3005,2,2, -209.00, 0.95000, 100.000, 0.100, 50.000, 400.00, 1200.00,0.10000, 100.00, -110.00, 0, 100.0
PSS™E-31.0
3008,1,1, 100.00, 0.99000, 90.000, 0.150, 40.000, 350.00, 1200.00,0.15000, 150.00, -140.00, 0, 100.0
'VDCLINE2 ',1, 0.3500, 1,0.3705, 2,0.3597, 3,0.1799, 4,0.0899
203,2,1, -100.00, 1.00000, 100.000, 0.150, 123.000, 200.00, 1200.00,1.00000, 200.00, -150.00, 0, 100.0
205,1,1, 100.00, 1.00000, 93.000, 0.120, 98.000, 250.00, 1250.00,1.00000, 225.00, -250.00, 0, 99.0
0 / END OF VSC DC LINE DATA, BEGIN SWITCHED SHUNT DATA
Figure E-6 (Cont). SAMPLE Load Flow Raw Data File sample.raw (3 of 4 Sheets)
Users Manual
PSS™E-31.0
Siemens Power Transmission & Distribution, Inc., Power Technologies International
152,1,1.04500,0.95500, 0, 100.0,' ', -233.00, 1, -15.00, 2, -5.00, 3, -10.00, 4, -8.00, 5, -7.00, 6, -5.00, 7, -7.00, 8, -4.00
154,1,1.04480,0.96500, 0, 100.0,' ', 124.00, 1, 25.00, 2, 10.00, 2, 15.00, 1, 15.00, 2, 5.00, 3, 3.00, 2, 4.00, 1, 7.00
3005,4,0.98000,0.64000, 3005, 100.0,'VDCLINE1 ', 0.00, 1, 33.35
3021,2,1.00000,1.00000, 0, 100.0,' ', 499.66, 2, 200.00, 1, 100.00, 2, 50.00, 4, 25.00
3022,2,1.00000,1.00000, 0, 100.0,' ', 599.58, 4, 100.00, 2, 50.00, 4, 25.00, 3, 20.00, 2, 20.00
0 / END OF SWITCHED SHUNT DATA, BEGIN IMPEDANCE CORRECTION DATA
1, -30.00, 1.10000, -24.00, 1.09100, -18.00, 1.08400, -12.00, 1.06300, -6.00, 1.03200, 0.00, 1.00000, 6.00, 1.03000, 12.00, 1.06000, 18.00, 1.08000, 24.00, 1.09000, 30.00, 1.11000
2,0.60000, 1.06000,0.70000, 1.05000,0.80000, 1.04000,0.90000, 1.03000,0.95000, 1.02000,1.00000, 1.01000,1.05000, 0.99000,1.10000, 0.98000,1.20000, 0.97000,1.30000, 0.96000,1.40000, 0.95000
0 / END OF IMPEDANCE CORRECTION DATA, BEGIN MULTI-TERMINAL DC DATA
1, 4, 5, 4, 1, 212, 400.00, 0
402, 4,10.00, 8.00, 0.0000,19.0000, 500.0,0.22000,1.01000,1.10000,0.97000,0.01000, 321.00, 1.0000, 0.15000, 3
401, 4,10.00, 8.00, 0.0000,19.0000, 500.0,0.22000,1.01000,1.10000,0.97000,0.01000, 321.00, 1.0000, 0.15000, 3
212, 4,20.00,18.00, 0.0000,10.0000, 230.0,0.45200,1.04000,1.10000,0.90000,0.01000, 500.00, 1.0000, 0.00000, 1
213, 4,20.00,18.00, 0.0000,10.0000, 230.0,0.45200,1.10000,1.10000,0.90000,0.01000, -303.80, 1.0000, 0.00000, 4
1, 401, 4, 4,'DC1 ', 0, 0.0000, 4
2, 212, 2, 2,'DC2 ', 0, 0.0000, 2
3, 402, 4, 4,'DC3 ', 0, 0.0000, 4
4, 213, 2, 2,'DC4 ', 0, 0.0000, 2
5, 0, 4, 4,'DC5 ', 0, 0.0000, 4
1, 5,'1', 29.0000, 0.00
2, 5,'1', 29.0000, 0.00
3, 5,'1', 29.0000, 0.00
4, 5,'1', 29.0000, 0.00
0 / END OF MULTI-TERMINAL DC DATA, BEGIN MULTI-SECTION LINE DATA
201, -204,'&1', 207
0 / END OF MULTI-SECTION LINE DATA, BEGIN ZONE DATA
1,'NORTH_A1 '
2,'MID_A1_A2_A5'
3,'DISCNT_IN_A1'
4,'SOUTH_A1_A5 '
5,'ALL_A3 '
6,'NORTH_A5 '
7,'NORTH_A2 '
8,'SOUTH_A2 '
9,'ALL_A4_A6 '
0 / END OF ZONE DATA, BEGIN INTER-AREA TRANSFER DATA
1, 2,'A', 1000.00
1, 5,'B', -3800.00
2, 4,'C', -300.00
2, 6,'E', -300.00
3, 5,'D', 2900.00
0 / END OF INTER-AREA TRANSFER DATA, BEGIN OWNER DATA
1,'OWNER 1 '
2,'OWNER 2 '
3,'OWNER 3 '
4,'OWNER 4 '
5,'OWNER 5 '
Figure E-6 (Cont). SAMPLE Load Flow Raw Data File sample.raw (4 of 4 Sheets)
E-12 Siemens Power Transmission & Distribution, Inc., Power Technologies International
PSS™E-31.0 Sample Data Files
Users Manual SAMPLE Case Data Input Files
Figure E-8. SAMPLE Slider File sample.sld
Siemens Power Transmission & Distribution, Inc., Power Technologies International E-13
This page intentionally left blank.
E-14 Siemens Power Transmission & Distribution, Inc., Power Technologies International