Rac Module 4
Rac Module 4
Rac Module 4
Contents
1. Application Of Refrigeration
• Domestic Refrigerators
• Water Coolers
• Ice Plants
• Cold Storages
5. Charging Of Refrigerant
6. System
. Controls
APPLICATIONS OF REFRIGERATION
1.DOMESTIC REFRIGERATOR
• Today’s refrigerators use much less energy as a result of using smaller and
higher- efficiency motors and compressors, better insulation materials,
larger coil surface areas, and better door seals.
• Despite the improvements made in several areas during the past 100 years
in household refrigerators, the basic vapor-compression refrigeration cycle
has remained unchanged. The alternative absorption refrigeration and
thermoelectric refrigeration systems are currently more expensive and less
efficient.
• Compressor used in domestic refrigerator is of reciprocating type and is
of hermetically sealed means compressor and electric motor are a single
unit enclosed in a container.
Parts of the Domestic Refrigerator
(1) Refrigerant (2) Compressor (3) Condenser (4) Expansive valve or the capillary tube (5)
Evaporator or chiller or freezer
(6)Drier(Crisper) : Kept between receiver and the evaporator to eliminate traces of moisture and
keeps vegetables and fruits fresh for longer time.
(7)Temperature control device or thermostat: To control the temperature inside the refrigerator
there is thermostat, whose sensor is connected to the evaporator. The thermostat setting can be
done by the round knob inside the refrigerator compartment. When the set temperature is
reached inside the refrigerator the thermostat stops the electric supply to the compressor and
compressor stops and when the temperature falls below certain level it restarts the supply
to the compressor.
(8)Defrost system: The defrost system of the refrigerator helps removing the excess ice from the
surface of the evaporator. The frost acts as insulation that impedes the HT to the evaporator. The
defrost system can be operated manually by the thermostat button or there is automatic defrost
system comprising of the electric heater and the timer.
(9)Starting Relay: Used to provide the necessary starting torque required to start the motor.
(10)Overload protector : To protect the compressor motor winding from damage due to excessive
current.
• Primary function of refrigerator is to provide food storage space maintained at low temperature for the
preservation of food.
• They are usually specified by the internal gross volume and the deep freezer’s volume.
• For specified external dimensions, a refrigerator is desired to have maximum food storage volume,
minimum energy consumption, and the lowest possible cost to the consumer.
• Freezer provided bottom portion is more energy efficient (Since warm air rises, the top freezer
refrigerator uses more power to keep the temperature cooler) and time to cool products will be less.
• Different temperatures for the storage of specific foods can be maintained in the refrigerator section by
• Household refrigerators consume from about 90 to 600 W of electrical energy when running and are designed to
• Refrigerator body is provided with good quality insulation (thick glass loos fill fibre or glass role)
• The size of the compressor and the other components of a refrigeration system are determined on the basis of the
anticipated heat load (or refrigeration load), which is the rate of heat flow into the refrigerator.
TEMPERATURE
SENSOR
cold refrigerant
to expansion valve Hot refrigerant
From compressor
2. WATER COOLERS
• To make water available at a constant temperature irrespective of ambient temperature.
• To produce cold water at about 70C to 130C.
• All coolers consists of basic parts that are the same as that of a refrigeration system such as compressor, condenser
(usually air cooled), expansion device (thermostatic expansion valve or capillary tube), provisions are provided for
water inlet and outlet.
condenser), expansion device, and an evaporator (the space where water is to be cooled).
• The refrigerant flows from the compressor to the condenser where the high pressure refrigerant vapor is converted
into high pressure liquid refrigerant.
• From the condenser, the liquid refrigerant flows through the expansion device where the high pressure refrigerant is
• The liquid refrigerant absorbs the latent heat from the water in the evaporator and gets converted into vapor refrigerant
and flows to the compressor suction which completes one cycle.
Working Principle
• In this type of cooler, the evaporator coils are soldered on
to the outer surface of the walls of the storage tank. Water storage tank where
water is cooled. The
• The water level of the storage tank may be maintained evaporator coils are
soldered in between the
by a float valve. walls
• In this type of cooler, the disadvantage is that the time Cold water outlet
taken to bring the temperature down to the set value is
more ( i.e., the cooler will have to work for a long time
since the mass of water in the tank is more). Waste water tray
• The thermostat senses the temperature of water and
This area contains the
stops the machine when the set temperature has been compressor, condenser,
and cut out and cut in
achieved. switches (thermostat)
• When water is drawn from the cooler for drinking, an
equal amount of water is being admitted in to the tank.
• When the temperature of the water increases more than
the set point, the machine starts its cycle automatically.
• This type of cooler finds a variety of applications such as
in colleges, schools, hotels, etc.
2.2 Instantaneous type water coolers
• In general the instantaneous type of water coolers consists of two separate cylindrically wound coils.
• One coil is for the refrigerant and the other for water.
• They may be made of copper or stainless steel tubes. Usually both the coils are entwined together and bonded
together by soldering.
Three types
• Bottle type,
• Pressure type, and
• Self-contained remote type.
BOTTLE TYPE:
• The water that is to be cooled will be stored in a bottle or
reservoir.
• A faucet (push type water taps) is used to minimize the
wastage of water.
• The drip receptor receives water that is not used and sends it
to the drainage.
• When we operate the faucet, the water flows from bottle to
the water coil through flow regulator.
• Now as the water travels through the coil, it loses its latent
heat to the refrigerant in the evaporator coil there by
reduction in water temperature is achieved.
• A thermostat is placed at the end of the water coil to start and
stop the compressor according to the water temperature.
17
• It consists an ice box having heavy insulation.
• The size depends on the capacity of ice plant.
• Should contain sufficient no. of cans for ice harvest.
• The ice cans are usually tapered around 10 to 20 mm per meter depth.
• Water level in the can should be around 20 to 30 mm below the brine level.
• Provided piping for air blowing into ice cans for air agitation. It helps form
ice in the whole of can otherwise a small amount of water remains at the
center.
• Heat transfer between water and brine is either by free convection or forced
convection(caused by suitable no. of agitators).
• The brine solution is maintained by refrigeration plants at -100C to -
110C
• Ammonia gas is used as refrigerant because of (i) Excellent thermal
properties (ii) High refrigeration effect per kg of refrigerant (iii) Low
specific volume.
• The high temperature, high pressure ammonia vapors are condensed in a
condenser (shell and tube type).
• The condensed liquid ammonia is collected in the receiver and then expanded
through the expansion valve.
• It then passes through the evaporator coils surrounding a brine tank in which
brine solution is filled.
• The low pressure ammonia absorbs heat from the brine solution, equivalent to
its latent heat of vaporization, gets converted to vapor state and is once again
fed to compressor to complete cycle.
• Note : Brine solution circulates itself from brine tank to evaporator and cools the
water kept in ice-can below zero degree centigrade to make it in ice form. Here,
brine solution is also a refrigerant but as it does change the phase during heat
transfer between water and evaporator, it is called secondary refrigerant. On the
other hand, Ammonia is primary refrigerant as it undergoes phase change during
cooling process.
4. COLD STORAGES
• Cold storages are meant to preserve the perishable commodities of food items for a longer period with retention of
the original color, flavor and taste. (it doesn't improve the quality of food products but slows down its deterioration)
• They are specially designed and built of concrete, stone or brick in order to prevent the leakage or cold leakage. Its floors
ceilings, walls and doors are properly insulated with special insulating materials with low thermal conductivity.
• Vegetable require 00C to 50C with
RH 80 - 90%
• For milk processing - 250C to - 300C
• For fish -200C to - 450C
Working of cold storage plant:
• Works on the 'Vapor Compression Refrigeration' cycle.
• The compressor compresses vaporized refrigerant (Ammonia) to high pressure and high temperature to raise
the boiling point of refrigerant.
• The condenser then liquefies the vaporized refrigerant to high pressure and high temperature state. Thus,
heat rejection takes place.
• The condensate from the condenser is collected in reservoir and allow to pass through expansion valve where
its pressure and temperature decrease from earlier state.
• The low pressure liquid refrigerant then allow to pass through refrigerated space where by heat of hot air of
refrigerated space starts evaporating the liquid refrigerant hence, heat in the atmosphere decrease and
cooling is produced.
• Blowers circulates the chilled air to stored fruits and vegetables.
• For most product, a high but not saturated, relative humidity is required (85% - 95%)
• Pre - cooling of product prior to refrigerated storage is strongly recommended since rapid removal of field heat
and cooling the product to the storage temperature before placing it in the refrigerated storage will
substantially increase the storage life.
Food Preservation Methods
Plate Freezing &Quick-freezing
ice crystals will be inhibited. Damage to food cells is prevented, reducing the dripping during defrosting.
• A quick-frozen food is commonly defined as one that has been cooled from a temperature of 0°C to −5°C or lower, in
a period of not more than 2 hours, and then cooled to −18 °C.
Air-cooled condensers can be further classified into Natural convection type or Forced convection type.
1.1 Natural Convection Condenser
• Air movement over the surface of condenser tubes is by natural convection. As air comes in contact with the warm-
condenser tubes, it absorbs heat from the refrigerant and thus the temperature of the air increases. Warm air rise up
and in its place, cooler air from below rises to take away the heat from the condenser. This cycle goes on.
• Not capable of rejecting heat rapidly, Since air moves very slowly by natural convection. A relatively large surface area of
the condenser is required.
• Use of this type of condenser limited to very small units such as domestic refrigerators, freezers, water coolers, room air
AC.
• In the small units, the condenser is fixed at the rear of the refrigerator cabinets. Generally, steel tubes are used. To
increase the heat-transfer area, wires are welded to the condenser tubes. In certain designs, widely-spaced fins are
used.
• Another design is the plate-type. The condenser coil is fastened to a plate. The plate being in contact with the condenser
tubes, the surface area of the condenser is increased. The plate-type condenser is mounted on the back of the
refrigerator cabinet with a small gap between the cabinet and the plate. This gap facilitates better natural convection air
currents.
Fig.1 Natural convection
thin wires are welded
to the condenser tube coil
• A fusible plug or safety pressure relief valve is fixed on the shell of the condenser to protect the high side of
the refrigeration system against excessive pressures.
Care should be taken not to overcharge the system with the refrigerant. This is because an excessive
accumulation of liquid in the condenser tends to cover too much of the water tubes and reduce the heat-
transfer surface available for condensing the high-pressure gas. This result in increasing the head pressure
and condensing temperature, also excessive overcharge can create hydraulicpressures.
Air cooled Condenser Water Cooled Condenser
Simple construction, less initial and maintenance Complicated construction, more initial and
cost maintenance cost
No handling problems Difficult to handle
Doesn’t require piping arrangement for carrying Pipes are required to take water to and from the
air condenser
Problem in disposing used air unless a
No problem in disposing of used air
recirculation system is provided
No corrosion – Low fouling effect Corrosion occurs – Fouling effects are high
Low heat transfer capacity due to low “K” High heat transfer capacity due to high “K”
Used for low capacity plants (< 5 TR) Used for large plants
Non uniform distribution of air on condenser Even distribution of water on the condenser surface
• Scale also forms a hard layer if hard water is used. Once these hard layers are allowed to form, it is never
possible to effectively clean the coil.
• So the capacity of the condenser gets substantially affected, because of this maintenance problem.
• Evaporative condensers are not much in favor.
INTRODUCTION
• Also known as throttling device, metering device.
• Expansion device used with dry expansion evaporators – expansion valves
• Expansion device used with flooded evaporators – float valves
• The basic functions of an expansion device used in refrigeration systems are to:
1. Reduce pressure from condenser pressure to evaporator pressure, and
2. It maintains the desired pressure difference between the high and low pressure sides of the system, so
that the liquid refrigerant vaporizes at the designed pressure in the evaporator.
1. The spring pressure and atmospheric pressure acting on the top of the diaphragm, and
2. The evaporator pressure and spring pressure acting below the diaphragm.
• When the compressor is running, the valve maintains an evaporator pressure in equilibrium with the spring
pressure and the atmospheric pressure.
• The spring pressure can be varied by adjusting the tension of the spring with the help of spring adjusting
screw.
• Once the spring is adjusted for a desired evaporator pressure, then the valve operates automatically to
maintain constant evaporator pressure by controlling the flow of refrigerant to the evaporator.
• When the evaporator pressure falls down, the diaphragm moves downwards to open the valve and allows
more liquid refrigerant to enter into the evaporator, thus ensuring the desired evaporator pressure.
• When the evaporator pressure rises, the diaphragm moves upwards to reduce the opening of the valve and
decreases the flow of liquid refrigerant into the evaporator, thus ensuring the desired evaporator pressure.
• When compressor stops, the refrigerant continues to flow into the evaporator and increases the pressure in
evaporator, which causes the diaphragm to move upward and the valve is closed. It remains closed until
compressor starts again and reduces the pressure in the evaporator.
3.Float valves
• Normally used with flooded evaporators in large capacity refrigeration systems.
• It opens or closes depending upon the liquid level as sensed a float(a hollow metal or plastic ball)
• The float valve always maintains a constant liquid level in a chamber called as float chamber.
• Depending upon the location of the float chamber, two types are:
a) Low-side float valve b) High-side float valve.
3.1 Low-side float valve
• The low-side float valve is located at the low pressure side of the system ie., connected to the
evaporator.
• It maintains a constant liquid level in a flooded evaporator or a float chamber attached to the
evaporator.
• The float of the low side float valve is placed in the evaporator.
• The valve assembly comprises of the hollow ball, a float arm, needle valve and the seat.
• The movement of the float ball (rise or fall) is transmitted to the needle valve by the float arm which
closes or opens the flow of liquid refrigerant.
• The hollow ball is connected to the needle and valve seat via the float arm.
• The needle valve being located at the inlet of the float chamber.
• When the load increases, more amount of refrigerant evaporates from the evaporator.
• As a result, the refrigerant liquid level in the evaporator or the low-side float chamber drops.
• The float then moves such that the valve opening is increased and more amount of refrigerant flows
into the evaporator and the liquid level is restored.
• When the load falls, the float reduces the opening of the valve and less amount of refrigerant flows
into the evaporator.
3.2. High Side Float Valve
• Maintains the liquid level constant in a float chamber
connected to the condenser on the high pressure side.
• The liquid condensed in the condenser flows down to the float
chamber.
• The needle and seat of the valve are at the outlet of the
float chamber.
• As the liquid level rises in the chamber, the float ball also rises,
thereby opening the needle valve.
• As the liquid level falls in the chamber, thereby closing the
needle valve.
• It is noted that refrigerant vapor is condensed in the
condenser at the same rate at which the liquid vaporizes in the
• evaporator; the float chamber receives and feeds liquid to the
evaporator at the same rate.
• Since the rate of vaporization of the liquid in the evaporator is
according to the load, the high-side float obviously works as
per the load.
• When the load increases, more amount of refrigerant evaporates and condenses.
• As a result, the liquid level in the float chamber rises momentarily. The float then opens the valve more to
allow a higher amount of refrigerant flow so the liquid level drops back to the original level.
• It allows only a fixed amount of refrigerant on the high pressure side(condenser), the bulk of the
refrigerant is stored in the low-pressure side (evaporator).
• The refrigerant liquid level in a high float valve is critical. Too much liquid refrigerant causes flooding
of the suction line followed by compressor slugging and too little liquid refrigerant causes a low
evaporator level resulting in low capacity of the refrigerating system.
• A high-side float valve can be used with both flooded as well as direct expansion type evaporators.
• Refrigerant feed/throttling devices for flooded chillers are usually the low- side or high-side float
valve. For example, in centrifugal plants, the chiller is of the flooded type and generally high-side
float valves are used as throttling devices. In a flooded chiller working in conjunction with a
reciprocating compressor, a low-side float valve is used as the throttling and refrigerant liquid flow
control.
Refrigeration system with Low Side Float Valve Refrigeration system with High Side Float Valve
4. Thermostatic expansion valve
• Most commonly used device in both commercial and
industrial refrigeration system.
• Also known as constant superheat valve – it maintains
a constant superheat of the vapor refrigerant at the
end of evaporator coil - prevent the slugging of the
compressors.
• It consist of a needle valve, seat, metallic diaphragm, spring, an adjusting screw, a feeler or thermal bulb (mounted
on suction line near the outlet of the evaporator coil).
• The feeler bulb is connected to the top of the bellows by a capillary tube. The feeler bulb and the capillary tube contain
some fluid called power fluid.
• The power fluid is the same as the refrigerant or it may be different fluid(TEV is called TEV with cross charge).
• The opening and closing of the valve depends on the following forces acting on the diaphragm
1. The spring force (PS) acting on the bottom of the diaphragm
2. The evaporator pressure (PE) acting on the bottom of the diaphragm
3. The feeler bulb pressure (PB) acting on the top of the diaphragm
• Feeler bulb will be at same temperature as the refrigerant at the exit of evaporator. Any change in temperature of
the refrigerant will cause a change in pressure in the feeler bulb which will be transmitted to the top of the
diaphragm.
• At normal operating condition feeler bulb pressure acting at the top of diaphragm is balanced by the evaporator
and spring force pressure.
• The force tending to open the valve depends upon spring pressure and evaporator pressure
which in turn depends upon the saturation temperature of the refrigerant in the evaporator coil.
• The force tending to close the valve depends upon feeler bulb pressure which in turn depends
upon the temperature of the power fluid in the bulb.
• Operation of valve is controlled by the difference between the two temperatures (saturation
temperature and feeler bulb temperature)
• If the load on the evaporator increases, it causes liquid refrigerant to boil off faster in the evaporator
coil, thus the feeler bulb temperature and pressure increases which is transmitted through the
capillary tube to the diaphragm.
• At this stage Diaphragm moves downward – Opens the valve – Admitting more quantity of
refrigerant to evaporator - Continues till the pressure equilibrium on the diaphragm is reached.
• If the load on the evaporator decreases, it causes less liquid refrigerant to evaporate, the excess
refrigerant flows towards the evaporator outlet which cools the feeler bulb – pressure reduces
due to decrease in its temperature – low feeler bulb pressure is transmitted through the capillary
tube to the diaphragm.
• Diaphragm moves upward – reduces the opening of the valve, and thus the flow of the refrigerant to
evaporator. Evaporator pressure reduces and continues till the evaporator and spring force pressure
maintain equilibrium with the feeler bulb pressure.
• Thus the TEV maintains the flow of the
refrigerant inside the evaporator as per the
refrigeration or air conditioning load.
• The TEV constantly modulates the flow to
maintain the superheat for which it has been
adjusted by the spring.
• Most TEV are set for 50C of superheat.
• This leads to highly efficient working of the
compressor and the whole refrigeration and the
air conditioning plant.
• It is commonly used in the industrial refrigeration
plants, high capacity split air conditioners,
packaged air conditioners, central air
conditioners and many other systems.
Advantages of the Thermostatic Expansion Valve
• The TEV maintains the flow of the refrigerant to the evaporator as per the load inside. Thus
the refrigeration or the air conditioning plant can run to the optimum capacity as per the
requirements.
• The TEV keeps the evaporator fully active and helps getting the optimum cooling effect from it.
• Since the entire refrigerant in the evaporator gets vaporized the chances of the liquid refrigerant
particles going to the compressor are reduced. This reduces the chances of the breakdown of
the compressor due to compression of the liquid.
• The compressor can also work at the optimum capacity as per the refrigeration load on the
system. If the load is lesser it has to compress refrigerant and work on lesser capacity thus
absorbing lesser electric power. If the load is higher it can work at higher capacities.
Disadvantages of the Thermostatic Expansion Valve
• TEV is more expensive and proper precautions should be taken at the installation.
• The use of TEV depends upon degree of superheat. Hence, in applications where a close
approach between the fluid to be cooled and evaporator temperature is desired, TEV cannot be
used since very small extent of superheating is available for operation.
5.Electronic Type Expansion Valve
• The needle moves up and down in response to magnitude of current in the heating
element.
• A small resistance allows more current to the heater, hence the valve opens wider.
• A thermistor is placed in series with the heater.
• The heater current depends upon the thermistor resistance that depends upon the
refrigerant condition.
• Superheated vapour lowering the thermistor resistance and increasing the heater
current.
• This opens the valve wider and increases the mass flow rate.
• This continues until the vapour becomes saturated and some liquid refrigerant droplets
appear.
• The liquid refrigerant cool the thermistor and increase its resistance, so it allows a small
current to flow through the heater making the valve opening narrower.
• The control of this valve is independent of refrigerant and refrigerant pressure; hence it
works in reverse flow direction also.
• It is convenient to use it in year-round-air-conditioning systems, which serve as heat
pumps in winter with reverse flow.
6. Solenoid valve
• A solenoid valve is an electromechanical valve frequently used to control the flow of liquid or gas.
• Solenoid valves are found in many applications and are commonly used in refrigeration and air
conditioning systems.
• Their function is simply to turn refrigerant flow on and off.
• Solenoid valves offer fast and safe switching, reliability, long life and compact design.
• The valve is commonly used to replace a manual valve or where remote control is desirable.
• A solenoid is operated by opening and closing an orifice in a valve body that permits or prevents flow
through the valve.
• The orifice is opened or closed through the use of a plunger that is raised or lowered within a sleeve tube by
energizing the coil.
• The bottom of the plunger contains a compatible sealing material, which closes off the orifice in the body,
stopping flow through the valve.
Diagram of solenoid valve
Operation
The solenoid assembly consists of a coil, plunger, and sleeve assembly. In a normally closed valve, a plunger
return spring holds the plunger against the orifice, preventing flow through the valve. When the coil is
energized, a magnetic field is produced, raising the plunger and allowing flow through the valve. In a
normally open valve, when the coil is energized, the plunger seals off the orifice, stopping flow through the
valve.
• In an evaporator, the refrigerant boils or evaporates and in doing so absorbs heat from the surrounding location
or medium which is to be cooled.
• The temperature of the boiling refrigerant in the evaporator must always be less than that of surrounding
medium.
• It is also called a cooling coil, chilling coil, freezing coil.
• Point 5 – Entry of liquid refrigerant into expansion valve. Liquid refrigerant is sub-cooled
ensuring that expansion valve receives pure liquid refrigerant with no vapors.
• Point 6 – Low pressure liquid refrigerant passes through the evaporator coil, and
continually absorbs heat through the coil walls, from the medium being cooled.
• Point 1’ – All liquid refrigerant has evaporated and only vapor refrigerant remains in the
evaporator coil.
• Since at point 1’ vapor refrigerant is still colder than the medium being cooled, therefore
the vapor refrigerant continues to absorb heat. This heat absorption causes an increase
in the sensible heat(or temperature) of the vapor refrigerant.
• The vapor temperature continues to rise until the vapor leaves the evaporator to the
suction line at point 1.
• At this point, the temperature of the vapor is above the saturation temperature and the
vapor refrigeration is superheated.
Classification of evaporators
1. According to the type of construction
• Bare tube coil evaporator
• Finned tube evaporator
• Plate evaporator
• Shell and tube evaporator
• Shell and coil evaporator
• Tube in tube evaporator
2. According to the manner in which liquid refrigerant is fed
• Flooded type evaporator
• Dry expansion evaporator
3. According to the mode of heat transfer
• Natural convection evaporator
• Forced convection evaporator
4. According to the operating conditions
• Frosting, Non frosting, Defrosting evaporator
• The process of heat removal from the substance to be cooled or refrigerated is done in the evaporator.
The liquid refrigerant is vaporized inside the evaporator (coil or shell) in order to remove heat from a
fluid such as air, water etc.
• Evaporators are manufactured in different shapes, types and designs to suit a diverse nature of cooling requirements.
• The terms dry expansion and flooded indicate the manner in which the liquid refrigerant is fed into the
evaporator and circulated, the terms natural convection and forced convection describe the way in which
the fluid (air or liquid) is cooled/circulated around the evaporator.
• Sufficient space should be provided between evaporator and ceiling to permit the air circulation over the top of the
coil.
• Baffles are also provided to separate the warm air and cold air plumes to ensure good air circulation.
• For rooms with larger width more evaporator coils are used.
• The refrigerant tubes are made of steel or copper. Steel tubes are used for ammonia and in large capacity systems.
• The advantages are that the coil takes no floor space and it also requires low maintenance cost.
• It can operate for long periods without defrosting the ice formed on it and it does not require special skills to fabricate
it.
• Defrosting can be done easily (e.g. by scraping) even when the plant is running.
• Disadvantage is that natural convection heat transfer coefficient is very small hence very long length are required,
which in turn requires larger quantity of refrigerants.
2.Flooded evaporators
• Used in the chemical and food processing industries.
• Used in comfort and process air cooling installations.
• Used in cold storage boxes and freezers
• In a flooded-type evaporator a constant refrigerant liquid level is maintained.
• A float valve is used as the expansion device which maintains a constant liquid level in the evaporator.
• The liquid refrigerant from the receiver passes through a low side float control valve and accumulator before
entering the evaporator coil.
• The accumulator (surge drum or surge tank) serves as a storage tank for the liquid refrigerant and It maintains
a constant liquid level in the evaporator and helps to separate the liquid refrigerant from the vapor returning
to the compressor.
• Due to the heat supplied by the substance to be cooled, the liquid refrigerant in the evaporator coil vaporizes
and thus the liquid level falls down.
• The accumulator supplies more liquid to the evaporator in order to keep the liquid refrigerant in the
• The refrigerant, by the time it reaches the end of the evaporator, is purely in the vapor state and that too
superheated. It may be noted that in this type, the refrigerant doesn't recirculate within the evaporator as in
flooded evaporator.
• Thus the evaporator in its length is filled with a varying proportion of liquid and vapor. The inside of the
evaporator is far from ‘dry’ but wetted with liquid.
• Refrigerant supply to the evaporator is through a thermostatic expansion valve, which maintain automatically
a moderate level of superheating of the vapour drawn off.
• Mostly used in producing refrigeration and having capacity below 150 tonnes of refrigeration. The direct
expansion coil is preferred for air conditioning purposes.
• They are simpler in design, more compact and require less refrigerant and have less problems with oil return,
and are cheaper than flooded or refrigerant circulates evaporators.
When the cooling load is light, quantity of liquid When the cooling load is heavy, it allows a larger quantity of
refrigerant in the evaporator is small. When liquid liquid refrigerant into the evaporator coil. In this case the
refrigerant passes through the expansion valve, some liquid and vapor separates. The liquid refrigerant flows along
vapor (flash gas) is formed. The flash gas causes bubbles in the bottom of the coil and vapor rises towards the top. Thus
the evaporator. If the coil diameter is small, the bubbles evaporator efficiency increases. This efficiency depends upon
can cause dry areas on the interior walls of the coil which the diameter of evaporator tubes, quantity in the evaporator
reduce the rate of heat transfer. Thus evaporator and quantity in the evaporator and the velocity of the liquid
efficiency decreases as dry area increase. refrigerant within the evaporator coil.
INTRODUCTION
• A compressor is the most important and often the costliest component (typically 30 to 40 percent of total cost) of any
vapor compression refrigeration system (VCRS).
• The function of a compressor in a VCRS is to continuously draw the refrigerant vapor from the evaporator, so that a low
pressure and low temperature can be maintained in the evaporator at which the refrigerant can boil, extracting heat
from the refrigerated space.
• The compressor then has to raise the pressure of the refrigerant to a level at which it can condense by rejecting heat to
the cooling medium in the condenser.
• Compressors used in refrigeration systems based on the working principle can be classified in several ways:
Positive displacement machines
• Reciprocating Compressors
• Rotary Compressors
• Scroll Compressors
• Screw Compressors
Non positive machines
• Centrifugal Compressors
• In positive displacement type compressors, compression is achieved by trapping a refrigerant vapor into an enclosed space
and , its pressure rises and then reducing its volume.
• When the pressure rises to a level that is slightly higher than the condensing pressure, then it is expelled from the
enclosed space and a fresh charge of low-pressure refrigerant is drawn in and the cycle continues.
• Since the flow of refrigerant to the compressor is not steady, the positive displacement type compressor is a pulsating flow
device and are prone to high wear, vibration and noise level.
• In non positive displacement compressors, the pressure rise of refrigerant is achieved by imparting kinetic energy to a
steadily flowing stream of refrigerant by a rotating mechanical element and then converting into pressure as the
refrigerant flows through a diverging passage.
• These compressors are steady flow devices, hence are subjected to less wear and vibration.
• The reciprocating and screw compressors used with refrigerants which require a relatively small displacement and
condense at relatively high pressure, such as R-12, R-22, Ammonia, etc.
• The centrifugal compressors are suitable for handling refrigerants that require large displacement and operate at low
condensing pressure, such as R-11, R-113, etc.
• The rotary compressor is most suited for pumping refrigerants having moderate or low condensing pressures, such as R-
21 and R-114; this is mainly used in domestic refrigerators.
1. Reciprocating compressor
• Vapor refrigerant is compressed by the reciprocating (i.e. back and forth) motion of the piston.
• These compressors are used for refrigerants which have comparatively low volume per kg and a large differential pressure,
• Types: Single acting vertical compressors and double acting horizontal compressors.
• Modern day reciprocating compressors are high speed (≈ 3000 to 3600 rpm), single acting, single or multi-cylinder (Upto 16
cylinders) type.
Operating principle
• Reciprocating compressors consist of a piston moving back and forth in a cylinder, with suction and discharge valves to
achieve suction and compression of the refrigerant vapor.
• Its construction and working are somewhat similar to a two-stroke engine, as suction and compression of the refrigerant
vapor are completed in one revolution of the crank.
• The suction side of the compressor is connected to the exit of the evaporator, while the discharge side of the compressor is
connected to the condenser inlet.
1.2 Multi stage reciprocating compressor
• To deliver vapor refrigerant at a very pressure as in the case of low temperature refrigerating systems.
• Vapor refrigerant is compressed in two or more cylinders in series with intercooling between them
Drawbacks in single stage compression
• Size of the cylinder is too large
• Difficult to reject heat from the refrigerant in the small time available for the compression due to high temperature.
• Sometimes heats up the cylinder head or burn the lubricating oil due to high temperature.
• The friction losses and running cost is high
• Volumetric efficiency is low
Fig 1
• The vapor refrigerant from the evaporator at pressure p1 and temperature T1 sucked by the LPC at point 1 during its suction
stroke.
• The machine consists of two helically- grooved rotors which rotate in a housing.
• The male rotor consists of lobes and is normally the driving rotor. The female rotor has gullies and is normally the driven rotor.
A four-lobe male rotor will drive a six-gully female rotor at two-thirds of its speed.
• At 3600 rpm the number of compressed gas discharges of a four-lobe rotor will he 4 x 3600 = 14,400 per minute.
• In a positive displacement machines, there are three basic phases – suction, compression and discharge.
• When the male rotor turns clockwise, an inter-lobe space between a pair and housing nearest to the suction end, opens
and is filled with the gas. There are four such pairs to be filled during one revolution in a four-lobe rotor and the suction
• On completion of the discharge phase, there is no residual gas remaining in the rotors. As a result, there is no expansion of
clearance gases. The compressor has no suction and discharge valves.
• There are leakage paths in a screw compressor mainly across the line of mesh between the rotors and across the clearance
between the rotors and the housing.
• To eliminate leakage, oil is injected in a number of small jets directed towards the mesh. Oil injection also serves the
purpose of cooling and lubricating along with that of sealing the leakage paths.
• A slide valve, closely following the shape of the rotors is used for capacity control. At full load the valve is closed. At part
load, the valve opens enabling a return flow passage to be formed so that a part of the gas drawn into the inter-lobe spaces
• A blade is set into the slot of a cylinder in such a manner that it maintains contact with the roller by means of spring.
• The blades separates suction and discharge ports and moves in and out of the slot to follow the rotor when it rotates
• The theoretical piston displacement is
Where A and B are respectively the diameters of the cylinder and rolling piston and H the length of the cylinder.
• When the roller rotates, the vapor refrigerant ahead of the the roller is being compressed and the new intake from the
• In this way low pressure and temperature vapor refrigerant is compressed gradually to a high pressure and temperature
• In the rotating vane type, its having four vanes, the rotor is concentric with the shaft. The vanes slide within the
rotor but keep contact with the cylinder.
• The center of the rotor is eccentric with the center of the cylinder.
• The blades are forced against the cylinder wall by the centrifugal action during the rotation of the motor.
• The low pressure and temperature vapor refrigerant from the evaporator is drawn through the suction port (In)
• As the rotor turns, the suction vapor refrigerant entrapped between the two adjacent blades is compressed.
• Compressed refrigerant at high pressure & temperature is discharged through the discharge port (Out) to the
condenser
• In both designs, the whole assembly is enclosed in a housing (not shown in the figures), filled with oil and
remains submerged in oil. When the compressor is working, oil film forms the seal between the high-pressure and
the low- pressure sides. When the compressor stops, this seal is lost and high pressure vapor refrigerant flow into
low pressure side
• Rotary compressors have high volumetric efficiencies due to negligible clearance. They are normally used in a
single stage up to a capacity of 5 TR with R-114. Large rotary compressors are used in low-temperature fields,
such as in chemical and industrial processing, cold storages and freezing, as high displacement. low- stage or
booster compressors at -90 to -l00°C evaporator temperature with R-12, R-22 and ammonia.
• They are available in 10 to 600 hp sizes with 2 to 120 cubic metres per minute displacement in one unit.
Based on arrangement of compressor motor or external drive, the different type of
reciprocating compressors are;
etc.
Hermetic compressor
• Used in household refrigerators, deep freezers, window air conditioners, split air conditioners, most of the packaged air
conditioners.
• The hermetically sealed reciprocating compressor is very easy to handle, and requires low maintenance. They are used with
motor power requirements from 1/20 to 7.5 hp.
• In hermetically sealed compressor, the compressor and the motor are enclosed in the welded steel casing and the two are
connected by a common shaft. This makes the whole compressor and the motor a single compact and portable unit that can
be handled easily and prevent refrigerant leakage.(eliminate the use of crankshaft seal)
• The housing has welded connections for refrigerant inlet and outlet and for power input socket.
• All motors reject a part of the power supplied to it due to eddy currents and friction, that is, inefficiencies. Similarly the
compressor also gets heated-up due to friction and also due to temperature rise of the vapor during compression.
• In Open type, both the compressor and the motor normally reject heat to the surrounding air for efficient operation. In
hermetic compressors heat cannot be rejected to the surrounding air since both are enclosed in a shell.
• Hence, the cold suction gas is made to flow over the motor and the compressor before entering the compressor. This keeps
the motor cool.
• The motor winding is in direct contact with the refrigerant hence only those refrigerants, which have high dielectric strength,
can be used in hermetic compressors.
• The hermetically sealed compressor is very different from the traditional open type of compressors in which the
compressor and the motor are different entities and the compressor is connected to the motor by coupling or belt.
• The cooling rate depends upon the flow rate of the refrigerant, its temperature and the thermal properties of the
refrigerant.
• If flow rate is not sufficient and/or if the temperature is not low enough the insulation on the winding of the motor can burn
out and short-circuiting may occur.
• Hence, hermetically sealed compressors give satisfactory and safe performance over a very narrow range of design
compressor from the motor and no coupling, belt and pulley arrangement is involved.
2) Since no coupling, belt or pulley is involved, the maintenance is lesser.
3) The lubrication system of the hermetically sealed compressor is inherent and no external lubrication is required, unless the
fresh gas charging is done.
4) The installation of the hermetically sealed compressor is very easy. The suction and discharge connections and the electrical
connections are available externally.
5) Have very long life, the companies offer warranty period of up to seven years for these compressors.
Disadvantages:
1) Maintenance is not easy because the moving parts are inaccessible.
2) A separate pump is reqd. for evacuation and charging of refrigerant.
3) Burnout winding can contaminate entire system.
4) Only electric power sources can run this unit.
Semi hermetic
• In some (usually larger) hermetic units, the cylinder head is usually removable so that the valves and the piston can be serviced.
This type of unit is called a semi-hermetic (or semi-sealed) compressor.
Advantages
• Due to the semi-hermetic design such compressors are very compact and occupy less space compared to open type machines
thus saving expensive building and plant room costs.
• The foot print and weight of a semi-hermetic machine is 70% of that of the corresponding open type machine. These
compressors are hence easier to handle and do not require heavy foundations like open type machines.
• The common problem of refrigerant leakage through the shaft seal is not facing with the semi-hermetic compressor because
the motor is directly mounted on the compressor crankshaft.
• Semi-hermetic compressors do not require any pulleys and belts and have no alignment problems and no wear and tear
problem of the d rive elements.
• Such compressors are also quieter and produce less vibration compared to the open type. This reason alone makes them the
The hot water is usually caused by air conditioning condensers or other industrial processes. That water is pumped through pipes
directly into the cooling tower. Cooling tower nozzles are used to spray the water onto to the “fill media”, which slows the water
flow down and exposes the maximum amount of water surface area possible for the best air-water contact. The water is exposed
to air as it flows throughout the cooling tower. The air is being pulled by an motor-driven electric “cooling tower fan”.
When the air and water come together, a small volume of water evaporates, creating an action of cooling. The colder water gets
pumped back to the process/equipment that absorbs heat or the condenser. It repeats the loop over and over again to constantly
cool down the heated equipment or condensers.
power plants.
• Hyperbolic towers operate through a chimney, or stack, effect; when
the air outside the cooling tower is cooler than the air inside the
tower, the air outside forces the humid, inside air to travel upwards.
• Fill is placed around the lower portion of the tower, water is sprayed
over it, and the water is cooled by the natural draft of the air moving
• There will be less liquid and more flash gas, which has negative effect on several components of the system.
• If the suction pressure due to refrigerant leakage falls below atmospheric pressure, then there is a possibility of air leaking
into the system. This will bring moisture into the system and the presence of moisture affects the system
adversely.
Leak detection:
• Bubble Solutions. The oldest method of leak detection is the bubble solution. Soap solution is applied at suspected leak
points, usually with a squeeze bottle, brush, or dauber. Theoretically, the escaping refrigerant will produce bubbles at the
leak sites. However, very small leaks or windy conditions may make this method ineffective.
• Halide Torches. Halide torches are more sophisticated than bubble solutions. This method is based on the fact that the
torch’s flame will turn green when exposed to refrigerants containing chlorine atoms (CFCs and HCFCs). However, not all
refrigerants contain chlorine atoms.
Electronic leak detector
• All electronic leak detectors use an element that is sensitive to halogenated gases.
• An audible and/or visual alarm signals when a leak has been detected.
• HFCs, CFCs, HCFCs and HCFC-based refrigerant blends can be detected easily
• Most commonly used due to accuracy and ease of use.
• This detector has a filter that prevent contaminants and water from entering it.
the leak.
• A microphone and earphones are used as input and output of the system.
Detecting Ammonia
• Ammonia can be detected by the use of phenolphthalein paper where the moistened paper will turn pink (small amount)
or scarlet (bigger amount) when in contact with this gas.
• The other method is by using a lighted sulfur candle which will give a thick white smoke when it encounters the ammonia
gas.
CHARGING OF REFRIGERANT
• The schematic arrangement for the charging of a refrigerant unit shownbelow.
• The refrigerant charging tube is flexible, the main refrigerant pipe is rigid and these are joined by a connector.
• The quantity of the refrigerant charged in the system is observed by noting the difference in weight of the refrigerant
cylinder. The amount of the refrigerant to be charged is dependent on the size and type of insulation.
• For small installation like water cooler, room cooler the exact quantity is prescribed by the manufacturer. if the
recommended weight of the refrigerant is not known, the refrigerant is charged in the system till no flashing or
bubbles are visible in the sight glass in the liquid line.
• The proper charging of the refrigerant is essential for smooth functioning of the system.
• Overcharging results in high temperature and pressure in the system and may lead to damage in compressor.
• Undercharging results in insufficient cooling and frequent tripping of the compressor motor.
REFRIGERATION CONTROLS SYSTEM
These are devices used to control the flow of refrigerant at various points throughout the refrigerant cycle. There are six basics
types of refrigerant flow controls.
1. Automatic Expansion Valve (Study)
2. Thermostatic Expansion valve (Study)
3. Capillary Tube (Study)
4. Low side Float (Study)
5. High Side Float (Study)
There are also secondary controls which, in some systems, ensure that other important activities are carried out
properly. Examples are defrost control and head pressure control.
Control Systems Offer Many Advantages
• Energy efficiency
• Reduced maintenance costs and extended equipment life
• Operator convenience
• Equipment redundancies
• Ice quality
• Reduced downtime and Reduced liability
1. THE THERMOSTAT - THERMOSTATIC EXPANSION VALVE (TXV)
• Thermostats allow refrigeration systems to bring product down to a predetermined temperature, but no lower than that
temperature.
• Thermostats typically are located inside the fridge behind the interior walls, with a sensor extending into the cooling
compartment.
• Refrigeration thermostats are similar to room thermostats in that they use a bimetallic strip to sense temperature Thermostats
don’t often fail completely, but their internal calibration sometimes changes, and other factors can affect their accuracy.
• Thus, it is not safe to assume that the temperature indicated on the thermostat dial is the actual temperature in the
refrigerated space. An accurate thermometer should be used to monitor spacetemperature.
2. DEFROST CONTROL
• Where cooling (not freezing) is the refrigeration goal, special defrosting equipment and controls may not be needed.
• Because the refrigerated space temperature is above freezing, allowing the evaporator fans to run when the compressor is
off may be all that is needed to remove the frost.
• Where freezing is the goal, however, heat from some source must be periodically applied to the evaporator coil to melt the
accumulated frost.
• Defrost cycles are often initiated by timers. This is appropriate. But using a timer to establish the duration of the defrost
period tends to waste energy. Evaporator temperature is a better indicator of when to stopdefrosting.
3. HEAD PRESSURE CONTROL
• Head pressure refers to the pressure in the high pressure side of a refrigeration system – the condenser.
• It may also be referred to as the discharge or condensing pressure. The temperature at which refrigerant condenses in the
refrigeration system.
• By minimising the head pressure, we can maximise system’s cooling capacity and minimise energy costs.
• When head pressure is higher than necessary, the compressor has to do more work. It will therefore
use more power and its efficiency and cooling capacity will decrease.
• The compressor has to run for longer to provide the required cooling and, in extreme cases, won’t be able to provide
enough cooling to achieve the required process or storage temperature.
• So minimising head pressure saves energy, and also maximises the cooling capacity of the refrigeration system, often