Weishaupt Product Info Gas and Dual Fuel Burners Sizes 1-3
Weishaupt Product Info Gas and Dual Fuel Burners Sizes 1-3
Weishaupt Product Info Gas and Dual Fuel Burners Sizes 1-3
The Weishaupt Research and automatically or manually without further quantity can be matched to the oil quan-
Development Institute was established adjustments to the burner. Dual gas tity throughout the firing range and
in 1962 with the aim to develop excep- burners are available on special request. improved turn down figures.
tional products in terms of quality and
performance. This commitment was Electro-Magnetic Clutch Controlled shut down
made at a time when the concepts of The coupling between the oil pump and The control system is designed to
“energy savings” and “environmental the motor shaft is automatically discon- ensure a controlled shut down of the
protection” were not yet considered nected when operating on gas, protect- burner at the low fire position. After a
issues of social and political importance. ing the oil pump from unnecessary wear. controlled shut down the air damper dri-
ves automatically closed.
The Weishaupt company and its pro- Gas Trains
ducts are founded on the principles of Weishaupt Gas and Combination Ignition position
quality design and performance. Gas/Oil burners are always supplied Burner models “G” and “GL” provide an
with two (2) safety shut off valves in independent ignition position, in addition
● Certified to international quality stan- both the pilot and main gas trains. to the low fire position, when operating
dard ISO 9001 on gas.
● Listed by ETL (UL795/296) and CGA Burner Version and Capacity
● Annual sales in excess of 150,000 Regulation Burner model “RGL” provides a sepa-
burners Gas models “G” rate ignition position and separate low
– Low/High/Low version ZD controlled fire positions for both gas and oil.
Burner Design by a servomotor with a running time of
● Forced draft automatic burner 8 seconds This feature permits the burner to be
● Cast aluminum, hinged monobloc – Modulating version ZMD controlled by tuned to the appliance, allowing only a
design a servomotor with a running time of very small quantity of gas (or oil) to be
● Burner swings open to the left or right 42 seconds released for light off.
● Stainless steel flame tube capable of
withstanding temperatures up to Combination Gas/Oil models “GL” Flame supervision
1450° F – Low/High/Low gas/oil version ZD Standard methods of flame monitoring
● Precision cam arrangement controls controlled by a servomotor with a are:
the fuel and combustion air running time of 8 seconds ● a flame rod for Gas
● Single servomotor drives the cam – Modulating gas, Low/High/Low oil ● a UV scanner for Combination
arrangement and controls the indivi- version ZMD controlled by a servo- Gas/Oil
dual set point for: motor with a running time of
– High fire position gas/oil 20 seconds Flame Monitoring Systems
– Air damper closed The burner flame monitor sequences
– Ignition position gas Combination Gas/Oil models “RGL” and controls the operation of the burner
– Ignition position oil (RGL) – Modulating gas/Modulating oil version automatically. The flame monitor can be
– Low fire position gas ZMD controlled by a servomotor with located in either the burner control panel
– Low fire position oil (RGL) a running time of 42 seconds or mounted directly on the burner. The
– Stage 2 oil solenoid (GL) standard flame monitoring system used
– Low fire position gas/oil (GL) Air/Fuel Regulation is manufactured by Landis & Staefa.
Low/High/Low and Modulating gas
Fuels The adjustable cam arrangement on the Alternative flame monitoring systems
Following fuels can be burned with the burner results in a simultaneous move- utilizing configurations of the Honeywell
burner models G, GL, RGL ment of the air damper and gas butterfly. 7800 series and Fireye E 110 are
● Gas The air quantity can be matched to the available upon request.
– Natural gas gas quantity throughout the firing range.
– Liquid gas (Propane) This precise regulation results in an opti- Site of Installation
– Manufactured gas mum fuel/air ratio and improved turn The standard version of Weishaupt burn-
– Special gases on request down figures. ers is designed for operation in enclosed
e.g. digester / sewer gas areas with ambient temperatures from
Low/High/Low oil 15°F to 100°F (-10°C to +40°C)
● Oil The low fire (stage 1) and high fire
– No.2 Oil (model GL and RGL) (stage 2) oil solenoid valves are con-
trolled by micro switch set points on the
Oil Viscosities servomotor, which permit precise
No.2 Oil adjustment of fuel and air.
Maximum viscosity 3.5 cSt at 100°F
Modulating oil
Combination Gas/Oil burners are The adjustable cam arrangement results
designed so that the operation can be in a simultaneous movement of the air
swithed from one fuel to the other, either damper and oil flow regulator. The air
2
Gas burner G, sliding two stage ZM and modulating
Pressure side air regulating damper Gas burner G, sliding two stage Z
Electro magnetic clutch Dual fuel burner GL, sliding two stage ZM and modulating
Gas burner G with integrated switch gear Servomotor on Dual fuel burner RGL: Gas- and Oil part sliding two stage ZM
3
Model designation
Scope of supply
Dual fuel
Gas burner Gas burner Dual fuel burner
burner
sliding- Gas: slid.twostage sliding- modulating Gas: slid.twostage Gas: modulating Gas and Oil: Gas and Oil:
twostage Oil: twostage twostage Oil: twostage Oil: twostage slid.twostage modulating
Servomotor with
Servomotor with Servomotor with Servomotor with 42 sec. running time Servomotor Servomotor with Servomotor with Servomotor with
8 sec. running time 8 sec. running time 20 sec. running time (20 sec only with with 20 sec. 8 sec. running 8 sec. running 42 sec. running
heat exchanger with running time time time time
quick load changes)
Burner nomenclature
Gas burner Dual fuel burner
Model G 1 / 1 – E , version Z E Model G L 3/1 – E , version Z E
ZM D ZM D
Scope of supply
Burner model G1-G3Z G1-G3ZM GL1-GL3Z GL1-GL3ZM RGL3
Burner casing with integral air intake guide, hinged flange, ● ● ● ● ●
casing cover with sight glass, Weishaupt burner motor,
pressure side air regulation, blower wheel, air pressure switch,
Servomotor, Gas/air-compound regulation with regulating cam(s),
Combustion head, ignition transformer, ignition cable, ignition electrodes,
terminal strip, flange gasket, mounting bolts
Flange interlock switch ● ● ● ● ●
Flame safeguard with flame sensor (ionization electrode) ● ●
loose for installation in a remote panel or mounted on the burner
Flame safeguard with flame sensor (UV cell) ● ● ●
loose for installation in a remote panel
Double gas valves ● ● ● ● ●
Gas butterfly valve ● ● ● ● ●
Pressure switch(es) for Gas ● ● ● ● ●
Oil pump , solenoid valve, nozzle head, nozzles, oil hoses, ● ● ●
Oil/Air-compound regulation with regulating cam(s)
Pressure switch(es) für Oil ●
Electro-Magnetic clutch (on GL1-GL3 as an option available) ●
4
Burner selection gas and dual fuel burners
Burner capacity/combustion chamber
pressure
2.0 2.0
1.5 1.5
1.0 1.0
Nat gas/ Propane
0.5 0.5
#2 oil
-0.5 -0.5
-1.0 -1.0
[MBH] 0 200 400 600 800 1,000 1,200 1,400 [MBH] 0 200 400 600 800 1,000 1,200 1,400
[“WC ] Burner model G3/1-E [“WC ] Burner model GL3/1-E and RGL3/1-E
Combustion head G3/1a- 133 - 100K Combustion head G3/1a- 133 - 100K
MBH Natural gas/ Propane 310 – 2,150 MBH Natural gas/ Propane 310 – 2,150
GPH #2 Oil 4.6 – 15.3
3.0 3.0
2.5 2.5
2.0 2.0
1.5 1.5
1.0 1.0
Nat gas/ Propane
0.5 0.5
0 0 Nat gas/
Propane
#2 oil
#2 oil
-0.5 -0.5
-1.0 -1.0
[MBH] 0 200 400 600 800 1,000 1,200 1,400 1,600 1,800 2,000 2,200 [MBH] 0 200 400 600 800 1,000 1,200 1,400 1,600 1,800 2,000 2,200
The capacity graphs are representa- Gas burner version LN The capacity graphs show the burner
tive of tests performed under condi- Using the especially low emission gas rating at:
tions as stated below. burners G1 and G3, version LN, the Flame tube “open”
most stringent regulation and limits of Flame tube “closed”
The minimum firing rate may vary various emission regulating standards
from application to application. In cer- can be achieved.
tain cases, a greater turn down ratio
is possible.
Test Criteria:
All figures relate to an ambient tem-
perature of 70ºF (20ºC) and a site ele-
vation of 1,650 ft (500m) above sea
level.
5
Accessories
Description G1 G3
GL1 GL3
RGL3
1 Interlock switch on burner flange standard standard
G, version ZME ● ●
G, version ZMD ● ●
GL, version ZE ● ●
GL, version ZD ● ●
6
Technical Data
Servomotor
– one stage, sliding-twostage Z (Running time 8 sec.) Model -w- 1055/80 -w- 1055/80
– sliding-twostage ZM (Running time 20 sec.) Model SQM 10.15561 SQM 10.15561
– modulating (Running time 42 sec.) Model SQM 10.16561 SQM 10.16561
Oil solenoid valve 110V 1/8” GL (qty: 3) Model 121 C 2323 121 C 2323
55V 1/4” RGL (qty: 2) Model – 121 K 6220
55V 1/8” RGL (qty: 2) Model – 121 K 2423
Weight
Gas burners without gas train approx. lbs/ kg 86/ 39 95/ 43
Dual fuel burners without gas train approx. lbs/ kg 93/ 42 104/ 47
P P
2 3 4 1 5 8
Legend
1 Isolating valve 11 Oil solenoid valve, normally closed
2 Main gas pressure regulator 12 Oil pressure switch
3 Low gas pressure switch 13 Oil regulator
4 Double main gas valves 14 Oil nozzles
5 High gas pressure switch
8 Integrated gas butterfly valve Note
9 Burner The actual gas train arrangement may differ
10 Oil pump depending on applicable code and regulation
7
Dimensions Weishaupt Corporation
6280 Danville Road
Mississauga, ON L5T 2H7
Ph.: (905) 564 0946, Fax.: (905) 564 0949
www.weishaupt-corp.com
Flange connection
1 27.0 6.6 4.4 6.6 1.4 3.5 0.3 12.3 13.5 4.3 4.7 25.8 19.6 10.8 9.8 21.4
(685) (168) (112) (168) (35) (88) (8) (312) (342) (110) (120) (655) (497) (275) (248) (543)
3 31.7 7.4 6.0 7.4 1.1 3.9 0.3 15.4 15.0 4.3 4.7 28.9 20.7 11.6 11.0 22.4
(805) (188) (153) (188) (28) (98) (8) (392) (382) (110) (120) (735) (525) (295) (280) (570)
b5➁ b5➂ h1 h2 h3 h4 h5 d1 d2 d3 d4 d5 d6 d7 r1 r2
1 25.7 – 15.3 11.4 5.9 6.9 5.1 7.7 5.1 5.1 6.3-6.7 5.3 21.7 24.8
DN25 M8
(653) – (388) (290) (150) (175) (130) (195) (129) (130) (160-170) (135) (550) (630)
3 26.8 29.5 16.9 12.8 6.7 6.9 5.5 8.7 6.1 6.3 7.3 6.5 25.6 27.6
DN40 M10
(680) (750) (430) (325) (170) (175) (140) (220) (154) (160) (186) (165) (650) (700)