Oil, Gas and Dual Fuel Burners

Burner series 130...150


250, 280

Group

3
Capacity
390-3,500 kW
Table of contents

General 1

How to choose a burner 2

Light oil burners

Technical data and dimensions 3-4


Light oil burners 3-6
PI-diagrams 4

Capacity/back pressure graphs 5

Scope of delivery 6

Heavy oil burners

Technical data and dimensions 7-8

PI-diagrams 8

Capacity/back pressure graphs 9

Scope of delivery 10

Gas burners
Heavy oil burners 7 - 10
Technical data and dimensions 11-12

PI-diagrams 12

Capacity/back pressure graphs 13

Scope of delivery 14

Dual fuel burners, light fuel oil/gas

Technical data and dimensions 15-16

PI-diagrams 16

Capacity/back pressure graphs 17

Scope of delivery 18

Dual fuel burners, heavy fuel oil/gas Gas burners 11 - 14

Technical data and dimensions 19

PI-diagram 20

Capacity/back pressure graphs 20

Scope of delivery 21

Gas valve selection table 22

Gas elbow 22

Burner preheater 23

Silencer 24

WiseDrive – an electronic regulator for Dual fuel burners, light fuel oil/gas 15 - 18
controlling the fuel/air ratio 24

Low NOx gas burner 25

Masonry figure 26

Flame dimensions 26

Servomotor 26

Oil supply diagram for heavy fuel oil 27

Gas pressure control assembly 27

Dual fuel burners, heavy fuel oil/gas 19 - 21


Oil, Gas and Dual Fuel Burners
Burner series 130...150
250, 280

Oilon oil, gas, and dual fuel burners are fully automatic, safe, and Capacity regulation methods
reliable. The design and manufacturing of the burners is based Depending on the model, options to choose from are:
on economy, safety, and service as well as environmental friendli- Two-stage, H
ness. Our gas burners comply with the EN 676 standard, oil burn- Three-stage, T
ers with the EN 230 and EN 267 standards, and dual fuel burners Modulating, M
with all of these standards. All burners are EU type tested. We also The two- and three-stage burners are equipped with an air damp-
supply burners complying with various marine classification society er servomotor, run time of which is 5 seconds between capacity
requirements, such as ABS, BV, CCS, DNV, GL, KR, LR, NKK, RINA stages. The burners automatically operate as one-, two-, or three-
and RS. stage according to the load. Modulating burners are equipped
with a servomotor with a transition time of 30 sec/90°. The servo-
Construction motor is connected to the oil regulator and compound regulator
All burner components are mounted directly on the burner hous- via an axle. A modulating burner operates regardless of the firing
ing. The aluminium alloy cast housing incorporates a three-phase rate, on the basis of the load. The burners are controlled on the
motor that runs the fan and the oil pump. In dual fuel burners, basis of combustion gas analysis.
the oil pump has its own three-phase motor. The contactors and
thermal relays of the motors and the contactors of the preheater Oilon preheater guarantees accurate oil temperature con-
are pre-mounted on the burner. The surface of the housing is fin- trol
ished with durable high-gloss paint. The housing is equipped with RP and GRP models are equipped with oil shut-off valves and a
a hinged burner flange with a safety interlock switch, enabling the filter, and with an electric mass preheater. The preheater is con-
burner to be swung open to the left or right. Due to the burner trolled via an electronic regulator that keeps the oil temperature
flange, it is possible to service the combustion head, nozzles, and stable. Stable oil temperature makes it easier to obtain optimal
ignition electrodes without removing the burner. The stainless combustion conditions. In the heavy oil burners, the oil heated
during the pre-purge phase flows to the nozzle through the pre-
steel alloy combustion head and the diffuser disc can withstand
heater to ensure that the oil temperature is high enough during
temperatures up to 1,200 °C. The combustion head is adjustable,
the ignition phase.
to optimise the mixing of fuel regardless of the firing rate. The
burner contains a sight glass for flame observation. On the suction Gas equipment
side of the fan there is an air damper that, together with the ser- The gas-related components of the gas and dual fuel burners
vomotor, automatically controls the amount of fuel and air on the comply with the standard EN 676: two shut-off valves, pressure
basis of the firing rate required. A removable upper cover makes switches (min./max.), and an automatic valve leak tester. Other
Electrical installations and burner servicing easier. piping related equipment is available on request.

1 Installation and suitable applications Oil piping


The burners are suitable for warm and hot water boilers, steam Mounted on the burner, three-stage burners with four solenoid
boilers, hot air generators, and various types of process heating. valves (one main valve and one valve for each nozzle). Modulating
They are also designed to suit furnaces with high back pressure. burners have three solenoid valves. The oil regulator for the mod-
The burners can be mounted in horizontal, vertical and upward- ulating burner is located on the oil line returning from the nozzle.
facing, or vertical and downward-facing orientation. Our burners The oil filter is located on the suction side of the pump. The two
are designed for operation in covered areas, max. +50 °C. Normal oil hoses enable the burner to be hinged.
operation altitude is 500 metres above sea level (other altitudes
Flame monitoring
on request). The enclosure class of the burner is IP 20. All models are equipped with automatic flame monitoring. In KP
Fuels and RP models, flame monitoring is taken care of via photocell; in
Different fuels can be used depending on the burner model: GP, GKP, and GRP models, it is performed via UV cell.
KP models: Control devices
- light fuel oil, viscosity 4 to 12 mm2/s, +20 °C The control automatics (control unit) are integrated with the
RP models: burner. The control unit handles all burner operation phases auto-
- heavy fuel oil, viscosity max. 250 mm2/s, +50 °C matically. In the event of a burner failure, the automatics stop the
- heavy fuel oil, viscosity max. 450 mm2/s, +50 °C burner automatically. The modulating burners also incorporate a
heating cartridge for pump and nozzle pre-mounted capacity controller.
- heavy fuel oil, viscosity max. 650 mm2/s, +50 °C
heating cartridges as above + trace heating for the oil piping Silencer
GP models: The sound level of the burners is low, but, if desired, they can be
- natural gas, gases of 2nd family, groups H and E (equipment equipped with a separate silencer to make them even quieter.
category I2R) Optimising combustion head pressure loss
GKP and GRP dual fuel burners: At an additional charge, the modulating burners can be equipped
- fuel properties as above, natural gas/light fuel oil with a system that optimises the combustion head pressure loss.
- fuel properties as above, natural gas/heavy fuel oil The system reduces the amount of excess air and also improves
Burners using other fuels are available on request. combustion figures for partial burner loads.

We reserve the right to make technical alterations.


How to choose a burner

A. Procedure B. Equations and rules of thumb


1 Establish relevant boiler and application information 1. Burner capacity = boiler capacity / 0.9 (when boiler efficiency is 90 %)
• boiler capacity and efficiency, or required burner capacity 2. Steam boilers: 1 ton/h steam ≈ 700 kW boiler capacity
• back pressure of the furnace 3. Light oil: 1 kg/h ≈ 11.86 kW burner capacity
• fuel/fuels to be used with calorific value 42.7 MJ/kg
• fuel inlet pressure to the burner 4. Heavy oil: 1 kg/h ≈ 11.22 kW burner capacity
• capacity regulation method of the burner with calorific value 40.5 MJ/kg
2 Calculate the burner capacity. Burner capacity = 5. Natural gas: 1 m3n/h ≈ 10 kW burner capacity
with calorific value 35.84 MJ/m3n
boiler capacity / efficiency
6. The amount of combustion air:
Example: boiler capacity of 2,500 kW, efficiency of 90 % → • Gas burners: required amount of combustion air for
burner capacity = 2,500 kW / 0.9 = 2,780 kW each 10 kW of burner capacity is 12 to 13 m3/h.
3 Gas burners: Required gas flow [m3n/h] = (burner capacity • Oil burners: required amount of combustion air for
[kW] x 3.6) / gas’s calorific value [MJ/m3n]. each kilo of oil burned [kg/h] is 13.5 m3/h.
Example: required burner capacity = 2,780 kW → required 7. Oil pumping, filtering, and preheating unit (Oilon HotBox) is
gas flow = (2,780 kW x 3.6) / 35.8 MJ/m3n = 280 m3n/h, required with heavy fuel oil. The required minimum pump
where 35.8 MJ/m3n is the calorific value of natural gas. output [kg/h] can be calculated as follows:
Oil burners: Calculate the required oil flow [kg/h]. Required Required minimum output [kg/h] = (oil flow to be burned in kg/h
oil flow [kg/h] = (burner capacity [kW] x 3.6) / the oil’s calorific + 150 to 200 kg/h)* 1.25 to 1.3, where the expression inside
value [MJ/kg]. Example: required burner capacity = 2,780 kW the parentheses indicates the preheated oil flow to each burner.
→ required oil flow = (2,780 kW x 3.6) / 42.7 MJ/kg = 234 kg/h,
where 42.7 MJ/kg is the calorific value of light oil.
4. See the brochure for burner capacity/back pressure graphs:
The graphs indicate the operating range of the burner. For
example, the back pressure of a boiler with a burner capacity
of 2,780 kW is 12 mbar. When you look at the point at the
coordinates for 2,780 kW and 12 mbar on the graph at the
bottom of the page, you can see that the point is located
within the capacity/back pressure area for the GP-280 M
burner. When the point representing the required back pres-
sure and capacity is located within the indicated area, the
burner capacity is a dequate. The best size of burner can be
selected by choosing a burner for which the point is located
as near the right-hand edge as possible. Note that different
2
fuels and capacity regulation methods have separate graphs.
An example of burner selection
The calorific value of the fuel is indicated in conjunction with
the graphs.
5. Choosing a valve for gas and dual fuel burners: Choose a GP-250 M GP-280 M
large enough valve, using the gas valve selection table. Note
that the values in the selection table apply when the furnace
20
back pressure is 0 mbar. Therefore, you must subtract the
furnace back pressure from the actual gas inlet pressure and 18
choose the valve on the basis of the value thus obtained. The 16
14
mbar (x100 Pa)

ratings shown in the table apply to natural gas.


For example, when the gas inlet pressure of the burner is 70 12
mbar, boiler back pressure is 12 mbar, and required burner 10
capacity is 2,780 kW, the effective pressure is 70 mbar - 12
8
mbar = 58 mbar. For the GP-280 M burner, for example, you
should choose a valve allowing a minimum burner capacity 6
of 2,780 kW with 58 mbar gas inlet pressure → in this case, 4
valve DN 65. 2
6. Check that the outer dimensions of the burner, especially 0
those of the combustion head, are suitable for the appli- 500 1000 1500 2000 2500 3000 3500
cation; the length of the combustion head should be such kW
that, when mounted, the combustion head is even with the Boiler pressure loss graph as
a function of burner capacity
furnace wall or about 10 to 20 mm inside the furnace (see
‘Masonry’ figure).
7. Check the flame dimensions in the flame dimension table. The max. capacity of a hot water boiler is 2,500 kW, efficiency 0.9, and
the corresponding burner capacity 2,500 kW / 0.9 = 2,780 kW. The graph
Please note that the flame must not touch the walls of the
indicates that a suitable gas burner for this capacity is the GP-280 M, as the
furnace. pressure loss value for the boiler is located inside the area for the GP-280
8. Remember the accessories: gas pressure regulator, oil pump- M burner on the capacity/back pressure graph. The GP-250 M can also
ing unit, boiler thermostats/pressostats. be used for this application, provided that the full boiler capacity is not
required. Remember to take efficiency into account when relating the boiler
pressure loss information to the burner capacity/back pressure graph.
Light oil burners

KP-140 H... -150 H KP-130 M... -150 M


1000 L2
1030 L2

¯D1
¯D1

620
620

420

50
420

B2 450
470 450

R1
275
R1

275 45
45 4 x M16
00

4 x M16
0

210
¯D
210

360

275
¯D
4
360

275

415
0
00
R1
0

250
10
R1

BURNER L2 B2 Ø D1 Ø D4 R1
KP-140 H 220 470 240 270 1000
KP-150 H 230 470 270 300 1000
BURNER L2 B2 Ø D1 Ø D4 R1
KP-130 M 200 430 200 230 980
KP-140 M 220 470 240 270 1000
KP-150 M 230 470 270 300 1000

KP-250 T, -280 T KP-250 M, -280 M


1000 L2 970 L2
¯D1
¯D1

680
680

450
450

50

470 470 470 470


R1
R1

365 45 365
02

45
02

4 x M16
0

4 x M16
0

250
250

¯D ¯D
4
420

365

4 Ê
420

365

430
0
04
0
10

R1

240
R1

BURNER L2 Ø D1 Ø D4
KP-250 T 300 270 300
KP-280 T 312 300 330

BURNER L2 Ø D1 Ø D4
KP-250 M 300 270 300
KP-280 M 312 300 330
Light oil burners

TECHNICAL DATA

BURNER KP-130 M KP-140 H KP-140 M KP-150 H KP-150 M


Capacity kg/h 32 -126 47 - 200 47 - 200 85 - 210 56 - 240
kW 390 - 1500 550 - 2350 550 - 2350 1000 - 2490 660 - 2850
Burner motor
3~ 400 V 50 Hz
Output kW 3,0 4,0 4,0 5,5 5,5
Current A 6,2 8,7 8,7 11,1 11,1
Speed rpm 2880 2900 2900 2910 2910
Control unit LAL1.25 LAL1.25 LAL1.25 LAL1.25 LAL1.25
Oil hose
connection
- suction R½” R½” R½” R½” R½”
- return R½” R½” R½” R½” R½”
Oil pump TA2 J7 TA2 TA2 TA2
Weight kg 114 107 118 113 128

BURNER KP-250 T KP-250 M KP-280 T KP-280 M


Capacity kg/h 55 - 270 55 - 270 76 - 295 76 - 295
kW 650 - 3200 650 - 3200 900 - 3500 900 - 3500
Burner motor
3~ 400 V 50Hz
Output kW 7,5 7,5 7,5 7,5
Current A 14,7 14,7 14,7 14,7
Speed rpm 2855 2855 2855 2855
Control unit LAL1.25 LAL1.25 LAL1.25 LAL1.25
Oil hose
connection
- suction R¾” R¾” R¾” R¾”
- return R½” R½” R½” R½”
Oil pump TA2 TA3 TA2 TA3
Weight kg 144 146 147 150

4
PI-diagrams
KP-140 H, -150 H
5
1 Oil filter 5 Solenoid valve, NC
B 2 Oil pump, plugged
3 Solenoid valve, NC A Oil, inlet
4 Solenoid valve, NC B Oil, return

A-473M
A
3 4
KP-130 M...-150 M , -250 M, -280 M
1 2
6

9 8 7 PI
KP-250 T, -280 T
PS M
6 B

3
B 5
PI

A-467T
A A-466T 4 5
3 4
1 2 1 2

1 Oil filter A Oil, inlet 1 Oil filter 8 Non-return valve


2 Oil pump, plugged B Oil, return 2 Oil pump, plugged 9 Pressure switch, max.
3 Solenoid valve, NC 3 Pressure gauge, gauge valve
4 Solenoid valve, NC 4 Solenoid valve, NC A Oil, inlet
5 Solenoid valve, NC 5 Solenoid valve, NC B Oil, return
6 Solenoid valve, NC 6 Pressure gauge, gauge valve
7 Oil regulator/servomotor
Light oil burners

Capacity/back pressure graphs

KP-130 M KP-140 H KP-140 M


20 200-152x50
20 240-165x60
20 240-165x60
A-583E
18
A-591E A-589E
18 18
16 16 16

mbar ( x100 Pa )
mbar ( x100 Pa )

mbar ( x100 Pa )
14 14 14
12 12 12
10 10 10
8 8 8
6 6 6
4 4 4
2 2 2

30 60 90 120 150 180 210 240 30 60 90 120 150 180 210 240 30 60 90 120 150 180 210 240
kg/h kg/h kg/h

KP-150 H KP-150 M KP-250 T


20 270-195x75
20 270-195x75
20
A-588A A-450T
18
A-576E
18 18
16 16 16

mbar ( x100 Pa )
mbar ( x100 Pa )
mbar ( x100 Pa )

14 14 14
12 12 12
10 10 10
8 8 8
6 6 6
4 4 4
2 2 2

30 60 90 120 150 180 210 240 30 60 90 120 150 180 210 240 50 100 150 200 250 300 350
kg/h kg/h kg/h

5
KP-250 M KP-280 T KP-280 M
20 20 20
A-450T A-450T
18 18
A-450T
18
16 16 16
mbar ( x100 Pa )

mbar ( x100 Pa )
mbar ( x100 Pa )

14 14 14
12 12 12
10 10 10
8 8 8
6 6 6
4 4 4
2 2 2

50 100 150 200 250 300 350 50 100 150 200 250 300 350 50 100 150 200 250 300 350
kg/h kg/h kg/h

Light fuel oil: 1 kg/h = 11.86 kW


Light oil burners

Scope of delivery
Burners include following equipment:

KP-140,150 H KP-130…150 M KP-250, 280 T KP- 250, 280 M


Hinge flange with limit switch • • • •
Burner flange gasket • • • •
Oil nozzle/nozzles • • • •
Solenoid valves for oil • • • •
Oil pump with pressure regulating valve • • • •
Non-return valve • •
2 pressure gauges for oil • •
Pressure switch for return oil • •
Deaerator o o
2 oil hoses, length 2000 mm • • • •
Oil filter • • • •
Pressure gauge for o o o o
control of inlet oil
Pressure switch for o o o o
control of inlet oil
Compound regulator for regulation of • •
air/oil ratio incl.:
- oil regulator
- servomotor
Potentiometer fitted in servomotor o o o o
Differential air pressure switch o o o o
6
Ignition transformer • • • •
Ignition cables and electrodes • • • •
Flame sensor • • • •
Inbuilt combustion air fan with • • • •
direct-driven electric motor
Air dampers • • • •
Separate servomotor • •
for air dampers
Pressure gauge for o o o o
fan pressure
Control unit • • • •
Capacity controller o • o •
Motor contactors and • • • •
thermal relays
Operating switches • • • •
Manual • • • •

• standard delivery
o option
Heavy oil burners

RP-130 H... -150 H RP-130 M... -150 M

1030 L2 1000 L2

¯D1
¯D1

H1
H1

H2
H2

50
B2 450 B2 490
300 300

R1
R1

45 275 45 275
4 x M16 4 x M16

355
355

210
210

¯D ¯D
4 4

360
360

275
275

415
0
0

15
15

250

R1
R1

BURNER L2 H1 H2 B2 Ø D1 Ø D4 R1
RP-130 H 200 620 420 430 200 230 980
RP-140 H 220 620 420 470 240 270 1000
RP-150 H 230 750 500 470 270 300 1000

BURNER L2 H1 H2 B2 Ø D1 Ø D4 R1
RP-130 M 200 620 420 430 200 230 980
RP-140 M 220 620 420 470 240 270 1000
7 RP-150 M 230 750 500 470 270 300 1000

RP-250 T, -280 T RP-250 M, -280 M

1000 970 L2
¯D1
¯D1

680
680

450
450

50

470 470 470 490


290 290
R1
R1

45 365 45 365
02
02

4 x M16 4 x M16
0
0

355
355

250
250

¯D ¯D
4 4
420
420

365
365

430
0

0
09

13

240
R1
R1

BURNER L2 Ø D1 Ø D4
RP-250 T 300 270 300
RP-280 T 312 300 330

BURNER L2 Ø D1 Ø D4
RP-250 M 300 270 300
RP-280 M 312 300 330
Heavy oil burners

TECHNICAL DATA
BURNER RP-130 H RP-130 M RP-140 H RP-140 M RP-150 H RP-150 M
Capacity kg/h 44 - 121 34 - 121 60 - 180 50 - 180 86 - 210 60 - 240
kW 500 - 1370 390 - 1370 680 - 2040 560 - 2040 975 - 2400 680 - 2700
Burner motor
3~ 400 V 50 Hz
Output kW 3,0 3,0 4,0 4,0 5,5 5,5
Current A 6,2 6,2 8,7 8,7 11,1 11,1
Speed rpm 2880 2880 2900 2900 2910 2910
Control unit LAL1.25 LAL1.25 LAL1.25 LAL1.25 LAL1.25 LAL1.25
Oil hose
connection
- suction R½” R½” R½” R½” R½” R½”
- return R½” R½” R½” R½” R½” R½”
Oil pump E7 TA2 E7 TA2 TA2 TA2
Preheater
3~ 400 V 50 Hz
Capacity kW 6 6 6 6 12 12
Weight kg 115 140 121 139 150 167

BURNER RP-250 T RP-250 M RP-280 T RP-280 M


Capacity kg/h 58 - 282 58 - 282 80 - 308 80 - 308
PI-diagrams
kW 650 - 3200 650 - 3200 900 - 3500 900 - 3500
RP-130 H...-150 H
Burner motor
B 12 8 10
3~ 400 V 50 Hz
Output kW 7,5 7,5 7,5 7,5 6 4
Current A 14,7 14,7 14,7 14,7
PI
Speed rpm 2855 2855 2855 2855 TC TS 7 11

Control unit LAL1.25 LAL1.25 LAL1.25 LAL1.25 TI

Oil hose A 5
connection
- suction R¾” R¾” R¾” R¾” 1 2 9 3 TZA A-475M1

- return R½” R½” R½” R½”


1 Oil filter 9 Solenoid valve, NC
Oil pump TA2 TA3 TA2 TA3
2 Oil pump, without plug 10 Solenoid valve, NO
Preheater 3 Preheater 11 Solenoid valve, NC
8
3~ 400 V 50 Hz 4 Temperature regulation/ 12 Drilled ball valve
Capacity kW 12 12 12 12 lower limit
Weight kg 181 195 182 196
5 Limit thermostat A Oil, inlet
6 Pressure gauge, gauge valve B Oil, return
7 Thermometer
8 Non-return valve,
throttle plug ø 1.2 mm

RP-250 T, -280 T RP-130 M...-150 M, -250 M, -280 M


13

PI
14 12
B 13 8 10
PS M
6 4
PI
TC TS 7 11 6 8 10

TI 15 4
16 PI
B TC TS 7 11
A 5 TI

1 2 9 3 TZA 12 A-468T
A 5 A-469T

1 2 15 9 3 TZA

1 Oil filter 9 Solenoid valve, NC 1 Oil filter 10 Solenoid valve, NO


2 Oil pump, without plug 10 Solenoid valve, NO 2 Oil pump, with plug 11 Solenoid valve, NC
3 Preheater 11 Solenoid valve, NC 3 Preheater 12 Oil regulator/servomotor
4 Temperature regulation/ 12 Solenoid valve, NC 4 Temperature regulation/ 13 Pressure gauge, gauge valve
lower limit 13 Drilled ball valve lower limit 14 Pressure switch, max.
5 Limit thermostat 5 Limit thermostat 15 Deaerator
6 Pressure gauge, gauge valve A Oil, inlet 6 Pressure gauge, gauge valve 16 Drilled ball valve
7 Thermometer B Oil, return 7 Thermometer
8 Non-return valve 8 Non-return valve A Oil, inlet
throttle plug ø 1.2 mm 9 Solenoid valve, NC B Oil, return
Heavy oil burners

Capacity/back pressure graphs


RP-130 H RP-140 H RP-150 H
20 200-152x50 20 240-165x60
20 270-195x75

18
A-584E
18 A-592A
18 A-594A

mbar ( x100 Pa )
16 16 16

mbar ( x100 Pa )
mbar ( x100 Pa )

14 14 14
12 12 12
10 10 10
8 8 8
6 6 6
4 4 4
2 2 2

30 60 90 120 150 180 210 240 30 60 90 120 150 180 210 240 30 60 90 120 150 180 210 240
kg/h kg/h kg/h

RP-130 M 20
RP-140 M 240-165x60
20
RP-150 M 270-195x75
20 200-152x50
A-593A A-579E
A-592E 18 18
18
16 16

mbar ( x100 Pa )
16
mbar ( x100 Pa )

14 14
mbar ( x100 Pa )

14
12 12
12
10 10
10
8 8
8
6 6
6
4 4
4
2 2
2
30 60 90 120 150 180 210 240 30 60 90 120 150 180 210 240
30 60 90 120 150 180 210 240
kg/h kg/h
kg/h

9
20
RP-250 T 20
RP-250 M 20 RP-280 T
A-451T A-451T
18
A-451T
18 18
16 16 16
mbar ( x100 Pa )

mbar ( x100 Pa )
mbar ( x100 Pa )

14 14 14
12 12 12
10 10 10
8 8 8
6 6 6
4 4 4
2 2 2

50 100 150 200 250 300 350 50 100 150 200 250 300 350 50 100 150 200 250 300 350
kg/h kg/h kg/h

20
RP-280 M Heavy fuel oil: 1 kg/h = 11.22 kW
A-451T
18
16
mbar ( x100 Pa )

14
12
10
8
6
4
2

50 100 150 200 250 300 350


kg/h
Heavy oil burners

Scope of delivery
Burners include following equipment:

RP-130 H...150 H RP-130…150 M RP-250, 280 T RP- 250, 280 M

Hinge flange with limit switch • • • •


Burner flange gasket • • • •
Oil nozzle/nozzles • • • •
Heating cartridge for oil nozzle o o o o
Solenoid valves for oil • • • •
Heating cartridge for solenoid valves • • • •
Oil pump with pressure regulating valve • • • •
Heating cartridge for oil pump o o o o
Non-return valve • •
2 oil pressure gauges • •
Thermometer • • • •
Pressure switch for return oil • •
Deaerator • •
Electric preheater incl.: • • • •
- limit thermostat
- electronic temperature controller
- temperature sensor
2 oil hoses, length 2000 mm • • • •
Electric tracing cables for burner oil pipes o o o o
Electric tracing cables for oil hoses o o o •
Oil filter • • • •
Pressure gauge for control of inlet oil o o o o
Pressure switch for control of inlet oil o o o o 10
Compound regulator for regulation of • •
air/oil ratio incl.:
- oil regulator
- servomotor
Potentiometer fitted in servomotor o o o o
Differential air pressure switch o o o o
Ignition transformer • • • •
Ignition cables and electrodes • • • •
Flame sensor • • • •
Inbuilt combustion air fan with • • • •
direct-driven electric motor
Air dampers • • • •
Separate servomotor for air dampers • •
Pressure gauge for o o o o
fan pressure
Control unit • • • •
Capacity controller o • o •
Motor contactors and thermal relays • • • •
Preheater contactors • • • •
Operating switches • • • •
Manual • • • •

• standard delivery
o option
Gas burners

GP-140 H... -150 H GP-130 M... -150 M


1230 L2 1200 L2
¯D1

¯D1
620

620
420

420

50
129 129

470 350 B2 350


10

R1
260 275 260 275
00

4 x M16 4 x M16
210

210
¯D ¯D
4
360

4
275

360

275
415
0
0

00
10
R1

R1 465

BURNER L2 Ø D1 Ø D4 R1
GP-140 H 220 240 270 1000
GP-150 H 230 270 300 1000

BURNER L2 B2 Ø D1 Ø D4 R1

11 GP-130 M 200 430 200 230 980


GP-140 M 220 470 240 270 1000
GP-150 M 230 470 270 300 1000

GP-250 T/M, -280 T/M


1200 L2
¯D1
680
450

50

130

470 380
R1

260 365
02

4 x M16
0

250

¯D
4
440

365
430
0
04
R1

455

BURNER L2 Ø D1 Ø D4
GP-250 T/M 295 270 300
GP-280 T/M 307 300 330
Gas burners

TECHNICAL DATA
BURNER GP-130 M GP-140 H GP-140 M GP-150 H GP-150 M
Capacity kW 390 - 1500 410 - 2350 410 - 2350 450 - 2700 450 - 2700
Burner motor
3~ 400 V 50 Hz
Output kW 3,0 4,0 4,0 5,5 5,5
Current A 6,2 8,7 8,7 11,1 11,1
Speed rpm 2880 2900 2900 2910 2910
Control unit LFL1.322 LFL1.322 LFL1.322 LFL1.322 LFL1.322
Weight kg 115 110 121 125 130

BURNER GP-250 T GP-250 M GP-280 T GP-280 M


Capacity kW 370 - 2600 370 - 2600 500 - 3500 500 - 3500
Burner motor
3~ 400 V 50 Hz
Output kW 5,5 5,5 7,5 7,5
Current A 10,9 10,9 14,7 14,7
Speed rpm 2855 2855 2855 2855
Control unit LFL1.322 LFL1.322 LFL1.322 LFL1.322
Weight kg 160 160 210 210

PI-diagrams

12
GP-140 H, -150 H GP-130 M...-150 M,
GP-250 T/M, -280 T/M

6 8

5 PS PS
2.5
1 2.2 2.3 2.4 1 6
5
4 2

PS PS PS PS

C C
7
2 2.1 A-493N 3 A-470T

3 4

1 Ball valve, blow-off 1 Ball valve, blow-off


2 Gas valve 2 Pressure switch, min.
2.1 Gas filter 3 Double solenoid valve
2.2 Pressure switch, min. 4 Valve leak tester
2.3 Gas valve 1 5 Pressure switch, max.
2.4 Pressure regulator 6 Solenoid valve, NC, ignition gas *)
2.5 Gas valve 2, two-stage 7 Gas butterfly valve
3 Valve leak tester 8 Differential air pressure switch
4 Pressure switch, max.
5 Solenoid valve, NC, ignition gas *) *) on 130…150 burners only on request
6 Differential air pressure switch on 250, 280 burners as standard

*) only on request
Gas burners

Capacity/back pressure graphs

20
GP-130 M 200-152x50 20
GP-140 H 240-165x60
20
GP-140 M 240-165x60
A-588E A-582E
18 A-597A
18 18
16 16 16

mbar ( x100 Pa )
mbar ( x100 Pa )
mbar ( x100 Pa )

14 14 14
12 12 12
10 10 10
8 8 8
6 6 6
4 4 4
2 2 2

300 600 900 1200 1500 1800 2100 2400 2700 300 600 900 1200 1500 1800 2100 2400 2700 300 600 900 1200 1500 1800 2100 2400 2700
kW kW kW

20
GP-150 H 270-195x75 20
GP-150 M 270-195x75
20
GP-250 T
A-575E A-452T
18 18
A-587E
18
16 16 16
mbar ( x100 Pa )

mbar ( x100 Pa )
mbar ( x100 Pa )

14 14 14
12 12 12
10 10 10
8 8 8
6 6 6
4 4 4
2 2 2

300 600 900 1200 1500 1800 2100 2400 2700 300 600 900 1200 1500 1800 2100 2400 2700 500 1000 1500 2000 2500 3000 3500
kW kW kW

13

20
GP-250 M 20
GP-280 T 20
GP-280 M
A-452T A-452T A-452T
18 18 18
16 16 16
mbar ( x100 Pa )

mbar ( x100 Pa )
mbar ( x100 Pa )

14 14 14
12 12 12
10 10 10
8 8 8
6 6 6
4 4 4
2 2 2

500 1000 1500 2000 2500 3000 3500 500 1000 1500 2000 2500 3000 3500 500 1000 1500 2000 2500 3000 3500
kW kW kW

Natural gas: gases of 2nd family, groups H and E


(equipment category I2R)
Gas burners

Scope of delivery
Burners include following equipment:

GP-140 H,150 H GP-130 M…150 M GP-250 T, 280 T GP-250 M, 280 M


Hinge flange with limit switch • • • •
Burner flange gasket • • • •
Compound regulator for regulation • • •
of air/gas ratio incl.:
- servomotor
Potentiometer fitted in servomotor o o o o
Gas nozzle • • • •
Pressure gauge for measuring o o o o
the pressure in gas nozzle
Gas butterfly valve • • •
Max. gas pressure switch • • • •
Differential air pressure switch • • • •
Ignition transformer • • • •
Ignition cables and electrodes • • • •
Flame sensor • • • •
Inbuilt combustion air fan with • • • •
direct-driven electric motor
Air dampers • • • •
Separate servomotor for air dampers •
Pressure gauge for fan o o o o
pressure
Control unit • • • • 14
Capacity controller o • o •
Motor contactors and • • • •
thermal relays
Operating switches • • • •
Elbow 90° • • • •
Double solenoid valve for gas • • •
incl.:
- gas pressure switch, min.
- 2 gas valves
- automatic valve proving system
- ball valve, blow-off (loose)
Gas train •
incl.:
- gas pressure switch, min.
- main gas valve
- gas valve, two-stage
- pressure regulator
- automatic valve proving system
- filter
- ball valve, blow-off (loose)
Solenoid valve for ignition gas • •
Manual • • • •

• standard delivery
o option
Dual fuel burners, light fuel oil/gas

GKP-130 H... -150 H GKP-130 M... -150 M

1230 L2 1200 L2

¯D1
¯D1

620
620

420
420

50
129 129

B2 580 B2 580

R1
R1

260 275 260 275


4 x M16 4 x M16

210
210

¯D ¯D
4

360
4

275
360

275

415
465
00
00

R 12
R 12

BURNER L2 B2 Ø D1 Ø D4 R1
GKP-130 H 200 430 200 230 980
GKP-140 H 220 470 240 270 1000
GKP-150 H 230 470 270 300 1000
15
BURNER L2 B2 ØD1 ØD4 R1
GKP-130 M 200 430 200 230 980
GKP-140 M 220 470 240 270 1000
GKP-150 M 230 470 270 300 1000

GKP-250 M, -280 M 1200 L2


¯D1
680
450

50

129

470 600
R1

260 365
02

4 x M16
0

250

¯D
4
440

365
430

455
00
R 12

BURNER L2 Ø D1 Ø D4
GKP-250 M 295 270 300
GKP-280 M 307 300 330
Dual fuel burners, light fuel oil/gas
TECHNICAL DATA
BURNER GKP-130 H GKP-130 M GKP-140 H GKP-140 M GKP-150 H GKP-150 M
Capacity oil, kg/h 32 -126 32 - 126 47 - 200 47 - 200 85 - 210 56 - 227
oil, kW 390 - 1500 390 - 1500 550 - 2350 550 - 2350 1000 - 2490 660 - 2700
gas, kW 390 - 1500 390 - 1500 550 - 2350 410 - 2350 1000 - 2490 450 - 2700
Fan motor
3~ 400 V 50 Hz
Output kW 3,0 3,0 4,0 4,0 5,5 5,5
Current A 6,2 6,2 8,7 8,7 11,1 11,1
Speed rpm 2880 2880 2900 2900 2910 2910
Control unit LFL1.322 LFL1.322 LFL1.322 LFL1.322 LFL1.322 LFL1.322
Oil hose
connection
- suction R½” R½” R½” R½” R½” R½”
- return R½” R½” R½” R½” R½” R½”
Oil pump J7 TA2 J7 TA2 TA2 TA2
- Motor
3~ 400 V 50 Hz
Output kW 1,5 1,5 1,5 1,5 1,5 1,5
Current A 3,3 3,3 3,3 3,3 3,3 3,3
Speed rpm 2870 2870 2870 2870 2870 2870
Weight kg 121 144 129 162 147 164

BURNER GKP-250 M GKP-280 M


Capacity oil, kg/h
oil, kW
55 - 220
650 - 2600
76 - 295
900 - 3500 PI-diagrams
gas, kW 370 - 2600 500 - 3500
Fan motor
3~ 400 V 50 Hz GKP-130 H...-150 H
Output kW 5,5 7,5
Current A 10,9 14,7 1 Ball valve, blow-off 6 Differential air
Speed rpm 2855 2855 2 Gas valve pressure switch
Control unit LFL1.322 LFL1.322
2.1 Gas filter 7 Oil filter
2.2 Pressure switch, min. 8 Oil pump, with plug
Oil hose 2.3 Gas valve 1 9 Solenoid valve, NC
connection
2.4 Pressure regulator 10 Solenoid valve, NC
- suction R¾” R¾”
- return R½” R½”
2.5 Gas valve 2, two-stage 11 Solenoid valve, NC
3 Valve leak tester
Oil pump TA3 TA3 4 Pressure switch for gas, max. A Oil, inlet
- Motor
5 Solenoid valve, NC, B Oil, return
16
3~ 400 V 50 Hz
ignition gas *) C Gas
Output kW 1,5 1,5
Current A 3,3 3,3 *) only on request
B
Speed rpm 2870 2870 6
9 10
Weight kg 270 278 PS

11
A
7
GKP-130 M...-150 M, 8

-250 M, -280 M 2.5 5


1 2.2 2.3 2.4

13 4
A-491N
14 PS PS
PI
16 15

PS M 17 C
B
PS 2 2.1
10
PI
3
A
8
9 1 Ball valve, blow-off 12 Solenoid valve, NC
11 12
2 Pressure switch, min. 13 Pressure gauge, gauge valve
3 Double solenoid valve 14 Oil regulator/servomotor
6 A-472T
4 Valve leak tester 15 Non-return valve
2
PS 5 Pressure switch, gas, max. 16 Pressure switch for oil, max.
1 5
PS
7
6 Solenoid valve, NC, 17 Differential air pressure switch
C ignition gas *)
3 7 Gas butterfly valve A Oil, inlet
8 Oil filter B Oil, return
4
9 Oil pump, with plug C Gas
10 Pressure gauge,
gauge valve *) on 130…150 burners only on request
11 Solenoid valve, NC on 250, 280 burners as standard
Dual fuel burners, light fuel oil/gas

Capacity/back pressure graphs

20
GKP-130 H 200-152x50
20
GKP-130 M 200-152x50 20 GKP-140 H 240-165x60
A-503B A-504B
18
A-505B
18 18
16 16 16

mbar ( x100 Pa )
mbar ( x100 Pa )

mbar ( x100 Pa )
14 14 14
12 12 12
10 10 10
8 8 8
6 6 6
4 4 4
2 2 2

300 600 900 1200 1500 1800 2100 2400 2700 300 600 900 1200 1500 1800 2100 2400 2700 300 600 900 1200 1500 1800 2100 2400 2700
kW kW kW

20 GKP-140 M 240-165x60 20 GKP-150 H 270-195x75 20


GKP-150 M 270-195x75
A-580E A-586E A-575E
18 18 18
16 16 16
mbar ( x100 Pa )

mbar ( x100 Pa )

mbar ( x100 Pa )
14 14 14
12 12 12
10 10 10
8 8 8
6 6 6
4 4 4
2 2 2

300 600 900 1200 1500 1800 2100 2400 2700 300 600 900 1200 1500 1800 2100 2400 2700 300 600 900 1200 1500 1800 2100 2400 2700
kW kW kW

17
20
GKP-250 M 20
GKP-280 M
A-453T A-453T
18 18
16 16
mbar ( x100 Pa )

mbar ( x100 Pa )

14 14
12 12
10 10
8 8
6 6
4 4
2 2

500 1000 1500 2000 2500 3000 3500 500 1000 1500 2000 2500 3000 3500
kW kW

Natural gas: gases of 2nd family, groups H and E


(equipment category I2R)
Light fuel oil: 1 kg/h = 11.86 kW
Dual fuel burners, light fuel oil/gas
Scope of delivery
Burners include following equipment:

GKP-130 H...150 H GKP-130 M...150 M GKP-250 M, -280 M


Hinge flange with limit switch • • •
Burner flange gasket • • •
Oil nozzle/nozzles • • •
Solenoid valves for oil • • •
Oil pump with pressure
regulating valve • • •
Separate motor for oil pump • • •
Non-return valve • •
2 pressure gauges for oil • •
Pressure switch for return oil • •
Deaerator o o
2 oil hoses, length 2000 mm • • •
Oil filter • • •
Pressure gauge for control
of inlet oil o o o
Pressure switch for control
of inlet oil o o o
Compound regulator for regulation of • •
air/gas/oil ratio incl.:
- oil regulator
- servomotor
Potentiometer fitted in servomotor o o o
Gas nozzle • • •
Pressure gauge for measuring o o o
the pressure in gas nozzle
Gas butterfly valve • •
Gas pressure switch, max. • • •
Differential air pressure switch • • •
Ignition transformer • • • 18
Ignition cables and electrodes • • •
Flame sensor • • •
Inbuilt combustion air fan with • • •
direct-driven electric motor
Air dampers • • •
Separate servomotor for air dampers •
Pressure gauge for
fan pressure o o o
Capacity controller o • •
Motor contactors and thermal relays • • •
Preheater contactors
Operating switches • • •
Elbow 90° • • •
Double solenoid valve for
gas incl.: • •
- pressure switch for gas, min.
- 2 gas valves
- automatic valve proving system
- ball valve, blow-off (loose)
Gas train incl.: •
- gas pressure switch, min.
- main gas valve
- gas valve, two-stage
- pressure regulator
- automatic valve proving system
- filter
- ball valve, blow-off (loose)
Solenoid valve for ignition gas •
Manual • • •

• standard delivery o option


Dual fuel burners, heavy fuel oil/gas

GRP-130 M... -150 M GRP-250 M, -280 M

1200 L2 1200 L2

¯D1
¯D1

680
H1

450
H2

50
50

129 130

B2 640 470 670


515 500

R1
R1

260 275 260 365

02
4 x M16 4 x M16

355
355

250
210

¯D ¯D
4 4

440
360

365
275

430
415

465 455
00
00

490 505
R 12
R 12

BURNER L2 L4 H1 H2 B2 Ø D1 Ø D4 R1
GRP-130 M 200 450 610 420 430 200 230 980
GRP-140 M 220 450 610 420 470 240 270 1000
GRP-150 M 230 450 750 560 470 270 300 1000

BURNER L2 Ø D1 Ø D4
19 GRP-250 M 295 270 300
GRP-280 M 307 300 330

TECHNICAL DATA

BURNER GRP-130 M GRP-140 M GRP-150 M BURNER GRP-250 M GRP-280 M


Capacity oil, kg/h 34 - 132 50 - 180 60 - 240 Capacity oil, kg/h 58 - 230 80 - 308
oil, kW 390 - 1500 560 - 2040 680 - 2700 oil, kW 650 - 2600 900 - 3500
gas, kW 390 - 1500 410 - 2040 450 - 2700 gas, kW 370 - 2600 500 - 3500
Fan motor Fan motor
3~ 400 V 50 Hz 3~ 400 V 50 Hz
Output kW 3,0 4,0 5,5 Output kW 5,5 7,5
Current A 6,2 8,7 11,1 Current A 10,9 14,7
Speed rpm 2880 2900 2910 Speed rpm 2855 2855
Control unit LFL1.322 LFL1.322 LFL1.322 Control unit LFL1.322 LFL1.322
Oil hose Oil hose
connection connection
- suction R½” R½” R½” - suction R¾” R¾”
- return R½” R½” R½” - return R½” R½”
Oil pump TA2 TA2 TA2 Oil pump TA3 TA3
- Motor - Motor
3~ 400 V 50 Hz 3~ 400 V 50 Hz
Output kW 1,5 1,5 1,5 Output kW 1,5 1,5
Current A 3,3 3,3 3,3 Current A 3,3 3,3
Speed rpm 2870 2870 2870 Speed rpm 2870 2870
Preheater Preheater
3~ 400 V 50 Hz 3~ 400 V 50 Hz
Capacity kW 6 6 12 Capacity kW 12 12
Weight kg 167 174 198 Weight kg 233 238
Dual fuel burners, heavy fuel oil/gas

PI-diagram

GRP-130 M...-150 M, -250 M, -280 M 1 Ball valve, blow-off


2 Pressure switch, min.
3 Double solenoid valve
4 Valve leak tester
5 Pressure switch for gas, max.
6 Solenoid valve, NC, ignition gas *)
7 Gas butterfly valve
21 20
8 Oil filter
PS M 16 PI
9 Oil pump, with plug
10 Preheater
15 19 22 11 Temperature regulation/lower limit
23 12 Limit thermostat
24 11 PS
B PI TC TS 14 13 Pressure gauge, gauge valve
13 14 Thermometer
TI 17
15 Non-return valve
16 Oil regulator/servomotor
A
8 18 17 Solenoid valve, NC
10
9 TZA 18 Solenoid valve, NC
12 6 19 Solenoid valve, NO
20 Pressure gauge, gauge valve
1 PS
PS 21 Pressure switch for oil, max.
2 5
22 Differential air pressure switch
7
C A-474T 23 Deaerator
3
24 Drilled ball valve
4
A Oil, inlet
B Oil, return
C Gas
*) only on request

20

Capacity/back pressure graphs

20
GRP-130 M 200-152x50
20
GRP-140 M 240-165x60
20
GRP-150 M 270-195x75
A-510B A-585E A-578E
18 18 18
16 16 16
mbar ( x100 Pa )

mbar ( x100 Pa )

mbar ( x100 Pa )

14 14 14
12 12 12
10 10 10
8 8 8
6 6 6
4 4 4
2 2 2

300 600 900 1200 1500 1800 2100 2400 2700 300 600 900 1200 1500 1800 2100 2400 2700 300 600 900 1200 1500 1800 2100 2400 2700
kW kW kW

20
GRP-250 M 20
GRP-280 M Natural gas: gases of 2nd family, groups
18
A-454T
18
A-454T
H and E (equipment category l2R)
16 16 Heavy fuel oil: 1 kg/h = 11.22 kW
mbar ( x100 Pa )
mbar ( x100 Pa )

14 14
12 12
10 10
8 8
6 6
4 4
2 2

500 1000 1500 2000 2500 3000 3500 500 1000 1500 2000 2500 3000 3500
kW kW
Dual fuel burners, heavy fuel oil/gas
Scope of delivery
Burners include following equipment:

GRP-130 M...-150 M GRP-250 M, -280 M


Hinge flange with limit switch • •
Burner flange gasket • •
Oil nozzle/nozzles • •
Heating cartridge for oil nozzle o o
Solenoid valves for oil • •
Heating cartridge for solenoid valves • •
Oil pump with pressure regulating valve • •
Heating cartridge for oil pump o o
Separate motor for oil pump • •
Non-return valve • •
2 pressure gauges for oil • •
Thermometer • •
Pressure switch for return oil • •
Deaerator for oil • •
Electric preheater incl.: • •
- limit thermostat
- electronic temperature controller
- temperature sensor
2 oil hoses, length 2000 mm • •
Electric tracing cables for burner oil pipes o o
Electric tracing cables for oil hoses o o
Oil filter • •
Pressure gauge for control of inlet oil o o
Pressure switch for control of inlet oil o o
Compound regulator for regulation of • •
air/gas/oil ratio incl.:
- oil regulator
- servomotor
21 Potentiometer fitted in servomotor o o
Gas nozzle • •
Pressure gauge for measuring o o
the pressure in gas nozzle
Gas butterfly valve • •
Gas pressure switch, max. • •
Differential air pressure switch • •
Ignition transformer • •
Ignition cables and electrodes • •
Flame sensor • •
Inbuilt combustion air fan with • •
direct-driven electric motor
Air dampers • •
Pressure gauge for fan pressure o o
Control unit • •
Capacity controller • •
Motor contactors and thermal relays • •
Preheater contactors • •
Operating switches • •
Elbow 90° • •
Double solenoid valve
incl.: • •
- gas pressure switch, min.
- 2 gas valves
- automatic valve proving system
- ball valve, blow-off (loose)
Solenoid valve for ignition gas •
Manual • •

• standard delivery o option


Gas valve selection table

BURNER SERIES 130...150


BURNER GAS VALVE BURNER MAX. CAPACITY kW *) COMBUSTION
GAS INLET PRESSURE HEAD
SIZE TYPE **) 20 mbar 30 mbar 50 mbar 100 mbar
GKP-130 H R2” MB-ZRDLE 940 1150 1480 1500 200-152x50
GP/GKP/GRP-130 M DN 50 DMV-DLE 990 1210 1500 1500 200-152x50
DN 65 DMV-D 1140 1400 1500 1500 200-152x50
DN 80 DMV-D 1230 1500 1500 1500 200-152x50
GP/GKP-140 H R2” MB-ZRDLE 1110 1360 1760 2350 240-165x60
GP/GKP/GRP-140 M DN 50 DMV-DLE 1190 1460 1890 2350 240-165x60
DN 65 DMV-D 1590 1950 2350 2350 240-165x60
DN 80 DMV-D 1870 2290 2350 2350 240-165x60
GP/GKP-150 H R2” MB-ZRDLE 1120 1370 1770 2500 270-195x75
GP/GKP/GRP-150 M DN 50 DMV-DLE 1240 1520 1970 2700 270-195x75
DN 65 DMV-D 1610 1980 2520 2700 270-195x75
DN 80 DMV-D 1910 2340 2700 2700 270-195x75

BURNER SERIES 250, 280


GP/GKP/GRP-250 T/M DN 50 DMV-D 1200 1500 2000 2600 270-195x75
DN 65 DMV-D 1800 2200 2600 2600 270-195x75
DN 80 DMV-D 2300 2600 2600 2600 270-195x75
DN 100 DMV-D 2600 2600 2600 2600 270-195x75
GP/GKP/GRP-280 T/M DN 50 DMV-D 1300 1600 2100 3000 300-215x75
DN 65 DMV-D 1900 2400 3100 3500 300-215x75
DN 80 DMV-D 2700 3300 3500 3500 300-215x75
DN 100 DMV-D 3200 3500 3500 3500 300-215x75
DN 125 DMV-D 3500 3500 3500 3500 300-215x75
22

NOTE! If the gas inlet pressure is less than 20 mbar or if the gas used is not Gas inlet pressure (Pmax) at burner
among those mentioned, evaluation must be made case-specifically. - max. 500 mbar when using DMV-D valve
*) The max. capacities shown in the table are achieved when the boiler - max. 360 mbar when using MB valve
back pressure is 0.
Natural gas 1 m3n/h ≅ 10 kW
**) or corresponding type

Gas elbow
H

GAS ELBOW DIMENSIONS WITH DIFFERENT VALVES


R2” DN50 DN65 DN80 DN100 DN125
H L L L L L L
GP/GKP/GRP-130…150 440 435 465 505 530 580 750
GP/GKP/GRP-250…280 450 - 510 560 615 665 745

Other dimensions available on special request


Burner preheater

Accurate temperature control


guarantees good combustion
In burning heavy fuel oil, the right atomising viscosity of the
oil is essential for good combustion and low combustion gas
emissions. A prerequisite for stable atomising viscosity is that
the oil temperature stays stable throughout the firing rate.

Control based
on Oilon technology

Control based
on traditional technology

23

. . . . . .

Oilon ML mass preheater keeps the oil temperature


stable even if the incoming temperature fluctuates.
On account of the construction and the electronic
regulator, the temperature of the oil flowing to the
nozzle remains stable. The burner may, depending on
the capacity and model, have one or more 6-kW heater
equipped with a safety device to guard against
overheating. The electronic regulator has an integrated
minimum temperature limiter as well; this prevents
the burner from starting if the oil is too cold.
Silencer

Intake silencer, type MV 1 Silencer, type MV 3


Construction Construction
The MV 1 silencer is made of steel plate lined with fireproof The MV 3 silencer is made of steel plate lined with fireproof
dampening wool. The silencer is connected to the burner’s dampening wool. This wheel-equipped silencer isolates the
suction side via a screw connection. The silencer reduces the burner from four sides. The MV 3 silencer reduces the sounds
high-pitched sound produced by the air flow. produced when the burner operates.

WiseDrive (WD100), an electronic regulator for 24


controlling the fuel/air ratio
Air flow control
Control room

Service
computer
Combustion
manager

CAN-BUS

Indication and
operating unit
Oil flow control Gas flow control
Low NOx technology for lower
combustion gas emissions

The development of the Low NOx burners increased the Oilon The high efficiency typical of Oilon burners applies to the
burner selection considerably. The greatest improvement Low NOx burners, too. With respect to the setting dimensions,
took place at the burner combustion head, where changes the outer dimensions of the burner combustion head are the
to the flow of the combustion gases enable lower NOx same as those of standard burners, so Low NOx burners are
emissions. Various tests and practical experience prove that easy to install in place of traditional Oilon burners, without
the Low NOx burners can achieve 40 to 60 % lower emission even electrical modifications. The burners are designed for
levels than traditional burners do. The carbon monoxide gases of 2nd family, groups H and E.
emissions of the Low NOx burners are also very low.

25
Masonry figure

2
1
60
..
.9 0
°

1 Gasket
2 Mounting panel
3 Ceramic wool or equivalent
ØD1
ØD4

4 Masonry
ØD1, ØD4, L2 See burner dimension diagram

3
4

L2

26

Flame dimensions Servomotor

7
x 1000 mm

6
Flame length
max.

5
Flame length
min.
4

3
Flame diameter
max.
2

1
Flame diameter
min.
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
x 1000 kW
kW

The dimensions apply for light oil and gas. For heavy oil, the The new, advanced servomotor of the modulating burners
dimensions used must be larger. makes it possible to determine the minimum capacity of
the burner more quickly than before.
Oil supply diagram for heavy fuel oil
RP-...M

Example

 

RP-...H

 

   

27

Gas pressure control assembly


Example
EN3/2.00/022012
Oilon invests in product development and
research. A modern product development
centre meeting all European standards
enables us to perform a wide range of
burning tests and accurate oil and gas
measurements.

We supply burners for ships according to


classification societies, such as ABS, BV,
CCS, DNV, GL, KR, LR, NKK, RINA, and RS
classifications.

We participate in trade shows around the


world every year.

OILON OY
Metsä-Pietilänkatu 1