Hiross ICE 090
Hiross ICE 090
Hiross ICE 090
Versions:
• Air cooled with centrifugal • Low ambient temperature (from ambient temperature option
fans (ICE 015-230): ideal ICE007 onwards): additional recommended).
for installation in enclosed condensing control for • Precision control
environments. Can be ducted continuous operation in (ICE 015-ICE230): for precise water
for air venting or heat recovery. cold ambients (negative temperature control (± 0,5 °C)
• Water cooled temperature). Available for air • Non ferrous (from ICE007
(ICE 015-230 alternative to the cooled, axial fan units. onwards): stainless steel
air cooled versions): Shell&tube • Low water temperature tank, pump, and hydraulic
condensers with pressostatic (from ICE007 onwards): for components.
valves. negative water temperature • Bioenergy: epoxy coating
control, down to -10 °C. (Low on all exposed copper as
protection against aggressive
environments.
• Special and multiple pumps:
higher (P50-5bar) or lower (P15-
1,5bar) head pressure available
to suit different hydraulic
circuits. Double stand-by pump
for high reliability.
• Antifreeze heating (from ICE007
onwards): avoids freezing when
the unit is switched off and
glycol is not used.
Options:
• Water fill kits: pressurized, Advanced version for complete
automatic or ambient manual remote unit management.
kits, for water filling in any • Wheels (ICE005 - ICE010):
installation. for ease of transport.
• Remote control kits: base • Water filters for circuit
version for remote ON/OFF cleanliness and machinery
and general alarm monitoring. protection.
Technical data
Model ICE 003 005 007 010 015 022 029 039 046 057 076 090 116 150 183 230 310 360
Cooling capacity1 kW 2,5 5,1 7,0 9,5 14,3 21,8 28,1 38,2 45,2 56,4 76,0 90,2 115,5 149,2 182,3 228 309 360
Compressor abs. power1 kW 0,7 1,4 2,0 2,3 3,4 5,2 5,7 7,7 10,1 12,3 15,4 20,3 24,9 30,8 40,1 51,4 65 82
Cooling capacity2 kW 1,7 3,7 5,0 6,7 10,0 15,9 21,2 27,7 33,0 40,8 55,2 65,8 84,2 108 133 166 231 262
Compressor abs. power2 kW 0,67 1,3 1,9 2,1 3,2 5,5 6 8,2 10,3 13,1 16,4 21,1 26,2 32,5 41,3 54,6 65 85
Power supply V/ph/Hz 230/1/50 400/3/50 no neutral
Protection index 33 44 54
Refrigerant R407C
Compressors
Type ermetic pistons ermetic scroll
Compressors/circuits 1/1 2/2 4/2
Max abs. power - 1 comp. kW 0,7 1,5 1,8 3 5,8 6,9 7,8 11,1 13,7 16,8 11,1 13,7 16,8 11,1 13,7 16,8 23,3 28,7
Axial fans
Quantity n° 1 2 3 2 3 4
Max abs. Power - 1 fan kW 0,12 0,12 0,14 0,14 0,61 0 61 0,78 0,61 0,61 0,61 0,78 0,78 0,78 2 2 2 2 2
Air flow m3/h 2300 2300 4400 4100 7100 6800 9200 12400 12000 17400 25500 25000 26400 47000 46000 66000 88000 88000
Centrifugal fans
Quantity N° 1 2 3 3
Max abs. Power - 1 fan kW 1,1 1,1 1,1 1,1 1,1 1,1 1,5 1,5 1,5 3 3 3
N.A. N.A.
Air flow m3/h 7100 6800 9200 12400 12000 17400 25500 25000 26400 47000 46000 66000
Head pressure Pa 140 130 200 180 160 200 100 100 100 180 180 130
Water cooled version
Condenser water flow m3/h 1,3 1,9 2,4 4,0 5,6 8,0 11,1 11,5 16,6 19,2 31,0 33,0
N.A. N.A.
Condensers connections in 1” 1” 1 ¼” 1 ¼” 1 ¼” 1 ¼” 1 ¼” 1 ¼” 1 ¼” 1 ¼” 1 ¼” 1 1/2”
Pump P30
Max abs.power kW 0,4 0,4 0,5 0,5 1,1 1,3 1,3 1,3 2,3 2,3 2,5 2,7 2,7 4,5 4,5 4,5 8,4 8,4
Water flow (nom/max)1 m3/h 0,43/2,4 0,88/2,4 1,2/3 1,6/3 2,3/6 3,7/9,6 4,8/9,6 6,6/9,6 7,8/18 9,7/18 13/31 15/27 20/27 25/50 30/50 39/50 53/90 62/90
Head pressure (nom/min)1 m H2O 36/5 29/5 36/8 30/8 29/21 28/17 27/17 24/17 28/22 27/22 23/13 28/16 25/16 34/20 32/20 26/20 26/19 23/19
Water flow (nom/max)2 m3/h 0,29/2,4 0,64/2,4 0,86/3 1,2/3 1,6/6 2,7/9,6 3,6/9,6 4,8/9,6 5,7/18 7,0/18 9,5/31 11/27 14/27 18/50 23/50 29/50 40/90 45/90
Head pressure (nom/min)2 m H2O 38/5 33/5 42/8 36/8 30/21 29/17 28/17 27/17 28/22 28/22 23/13 32/16 30/16 36/20 35/20 32/20 37/19 35/19
Dimensions and weight
Width mm 530 530 980 980 1090 1090 1650 1650 1650 2200 2200 2200 2200 3000 3000 3260 4200 4200
Depth mm 750 750 534 534 744 744 744 744 744 744 898 898 898 1287 1287 1287 1500 1500
Height mm 800 800 1228 1228 1358 1358 1358 1358 1358 1358 1984 1984 1984 2298 2298 2298 2240 2240
Connections in/out in 1” 1” 1” 1” 1 ¼” 1 ¼” 1 ½” 1 ½” 1 ½” 1 ½” 2” 2” 2” 2 ½” 2 ½” 2 ½” 4” 4”
Tank capacity l 25 25 45 45 120 120 180 180 250 300 500 500 500 1000 1000 1000 400 400
Weight (axial) kg 105 110 170 180 250 270 380 410 430 520 800 900 1000 1500 1800 2100 2900 3100
Weight (centrif.) kg 280 300 410 450 480 610 950 1050 1150 1700 2000 2300
N.A. N.A.
Weight (water cooled) kg 250 260 380 410 430 520 800 900 1000 1500 1800 2100
Noise level
Sound pressure (axial)3 dB(A) 52 52 53 53 50 50 53 52 52 56 58 58 58 62 62 64 65 65
1) at water in/out temperature = 20/15°C, glycol 0%, either 25°C ambient temperature (air-cooled models) or 25°C condenser water inlet temperature with 35°C condensing tempera-
ture (water-cooled models).
2) at water in/out temperature = 12/7°C, glycol 0%, 32°C ambient temperature (air-cooled models)
3) referred to axial fan version in free field conditions at a distance of 10m from unit, measured on condenser side, 1m from ground.
Correction factors
C) Glycol % 0 10 20 30 40 50
correction factor (f3) 1 0,99 0,98 0,97 0,96 0,94
To obtain the required cooling capacity multiply the value at nominal conditions by the above correction factors (i.e. cooling capacity = Pxf1xf2xf3xf4, where P is the cooling capacity
at conditions (1)). Hyperchill, in its standard configuration, can operate up to ambient temperatures of max 45°C and min. 5°C and water temperatures of max 30°C inlet and min. 0°C
outlet. The above correction factors are approximative: for a precise selection always refer to the software selection program.
Parker Worldwide
GR – Greece, Athens
Tel: +30 210 933 6450 Tel: +44 (0)1926 317 878
parker.greece@parker.com parker.uk@parker.com
HU – Hungary, Budapest ZA – South Africa, Kempton Park
Tel: +36 1 220 4155 Tel: +27 (0)11 961 0700
parker.hungary@parker.com parker.southafrica@parker.com