Presostato Potter
Presostato Potter
Presostato Potter
WATERFLOW SWITCHES
PRESSURE SWITCHES
SUPERVISORY DEVICES
EXPLOSION-PROOF DEVICES
VSR-F
VANE TYPE WATERFLOW
ALARM SWITCH WITH RETARD
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • P.O. Box 28480 55 Glen Cameron Road
St.Louis, MO 63146-4161 Thornhill, Ontario, Canada L3T 1P2
(314) 878-4321 • (800) 325-3936 (905) 882-1833
UL, ULC and CSFM Listed, FM and LPC Approved, NYMEA Accepted
Service Pressure: Up to 450 PSI
Minimum Flow Rate for Alarm: 10 GPM
Maximum Surge: 18 FPS
Contact Ratings: Two sets of SPDT (Form C)
15.0 Amps at 125/250VAC
2.0 Amps at 30VDC Resistive
Conduit Entrances: Two knockouts provided for 1/2" conduit
Environmental Specifications:
• Suitable for indoor or outdoor use with factory installed gasket
and die-cast housing.
• NEMA 4/IP54 Rated Enclosure - use with appropriate conduit
fitting
• Temperature Range: 40°F/120°F, 4.5°C/49°C
• Non-corrosive sleeve factory installed in saddle
Caution: This device is not intended for applications in explosive
environments
Sizes Available: Pipe schedules 10 thru 40, sizes 2" thru 8"
BS 1387 pipe 50mm thru 200mm
Service Use:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
Residential occupancy up to four stories NFPA-13R
U.S. PAT. NO. 3921989 National Fire Alarm Code NFPA-72
CANADIAN PAT. NO. 1009680
OTHERS PATENTS PENDING Optional: Cover Tamper Switch Kit, Stock No. 0090018
POTTER ELECTRIC, Rd., 1990
NOTES:
1. The Model VSR-F has two switches, one can be used to operate a central station, proprietary or remote signaling unit, while the
other contact is used to operate a local audible or visual annunciator.
2. A condition of LPC Approval of this product is that the electrical entry must be sealed to exclude moisture.
TESTING
The frequency of inspection and testing for the model VSR-F and its associated protective monitoring system should be in
accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends
quarterly or more frequently).
If provided, the inspector’s test valve, that is usually located at the end of the most remote branch line, should always be used for
test purposes. If there are no provisions for testing the operation of the flow detection device on the system, application of the
VSR-F is not recommended or advisable.
IMPORTANT NOTICE: Please advise the person responsible for testing of the fire protection system that this system must be
tested in accordance with the testing instructions.
Retard Adjustment:
To change time, turn knob (either
direction) for desired time delay.
Use the minimum amount of retard
necessary to prevent false alarms.
A “B” setting is usually adequate for
this. Factory set at “B”.
Screw the device into the TEE fitting as shown. Care must be taken
to properly orient the device for the direction of the waterflow.
On sweat TEE's no threaded bushings, inserts or adapters are
permitted unless they comply with the dimensions listed in the chart
Important:
There are 10 paddles below.
furnished with each unit. One Important - The depth to the inside bottom of the TEE should
for each size of threaded,
sweat or plastic TEE as CAUTION:
described in Fig. 2. These TO PREVENT LEAKAGE APPLY TEFLON TAPE
SEALANT TO MALE THREADS ONLY. DO NOT USE ANY APPROXIMATE DEPTH REQUIREMENT
paddles have raised lettering OTHER TYPE OF LUBRICANT OR SEALANT.
that shows the pipe size and TEE SIZE THREADED SWEAT CTS, POLYBUTYLENE CPVC
type of TEE that they are to be
used with. The proper paddle APPROX. RETARD SETTINGS (IN SEC.) 1" x 1" x 1" 2 1/16" 1 3/4" N/A 2 7/16"
must be used. The paddle 0 A B C D E 1 1/4" x 1 1/4" x 1" 2 7/16" 2 7/16" N/A N/A
must be properly attached (see 0 10-25 20-40 35-55 50-70 60-90 1 1/2" x 1 1/2" x 1" 2 11/16" 2 1/4" 2 1/2" N/A
drawing) and the screw that 2" x 2" x1" 3 3/16" 2 3/4" N/A N/A
holds the paddle must be
securely tightened.
SWITCH TERMINAL CONNECTIONS
CLAMPING PLATE TERMINAL
FIG. 3 CAUTION:
An uninsulated section of a single conductor should not be looped around the
terminal and serve as two separate connections. The wire must be severed,
thereby providing supervision of the connection in the event that the wire
becomes dislodged from under the terminal.
NOTE: The Model VSR-SF has two switches, one can be used to operate a central station, proprietary or remote signaling unit,
while the other is used to operate a local audible or visual annunciator.
TESTING: The frequency of inspection and testing for the model VSR-SF and its associated protective monitoring system should
be in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends
quarterly or more frequently).
The Model VS-SP is a vane type waterflow switch for use on installation. Screw the device into the TEE fitting as shown in
wet sprinkler systems. These devices may be used as Fig. 2. Care must be taken to properly orient the device for the
sectional flow indicators on large sprinkler systems and on direction of waterflow.
smaller sprinkler systems such as mobile homes and
The vane must not rub the inside of the TEE or bind in any
residential dwellings.
way. The stem should move freely when operated by hand.
INSTALLATION: These devices may be mounted in horizontal
TESTING: Check the operation of the unit by opening the
or vertical pipe. On horizontal pipe they should be installed on
inspector’s test valve at the end of the sprinkler line, or the
the top side of the pipe where they will be accessible. The units
drain and test connection if a test valve is not provided.
should not be installed within 6" of a valve, drain or fitting which
changes the direction of the water flow. If there are no provisions for testing the operation of the flow
detection device on the system, application of the VS–SP is
The unit has a 1" NPT bushing for threading into a non-
not recommended or advisable.
corrosive TEE. See Fig. 2 for proper TEE size, type and
FIG. 1 FIG. 2
Screw the device into the TEE fitting as shown. Care must be taken
to properly orient the device for the direction of the waterflow.
On sweat TEE's no threaded bushings, inserts or adapters are
Important: permitted unless they comply with the dimensions listed in the chart
There are 10 paddles furnished below.
with each unit. One for each
Important - The depth to the inside bottom of the TEE should have
size of threaded, sweat or
plastic TEE as described in Fig. the following dimensions:
2. These paddles have raised
lettering that shows the pipe APPROXIMATE DEPTH REQUIREMENT
size and type of TEE that they
are to be used with. The TEE SIZE THREADED SWEAT CTS, POLYBUTYLENE CPVC
proper paddle must be used.
The paddle must be properly 1" x 1" x 1" 2 1/16" 1 3/4" N/A 2 7/16"
attached (see drawing) and the 1 1/4" x 1 1/4" x 1" 2 7/16" 2 7/16" N/A N/A
screw that holds the paddle 1 1/2" x 1 1/2" x 1" 2 11/16" 2 1/4" 2 1/2" N/A
must be securely tightened. 2" x 2" x1" 3 3/16" 2 3/4" N/A N/A
CAUTION:
An uninsulated section of a single conductor should
not be looped around the terminal and serve as two
separate connections. The wire must be severed,
thereby providing supervision of the connection in
the event that the wire becomes dislodged from
under the terminal
NOTE: The Model VS-SP has one SPDT switch. An optional second switch is available if required. For example, one switch would
connect to an annunciator panel, and the optional switch could be used to operate a local bell. Order Switch Kit No. 0090013.
TESTING
The frequency of inspection and testing for the Model VS-SP and its associated protective monitoring system should be in accordance with
applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).
FIG. 1 FIG. 2
SWITCH TERMINAL CONNECTIONS
CLAMPING PLATE TERMINAL
CAUTION:
An uninsulated section of a single
conductor should not be looped around
the terminal and serve as two separate
connections. The wire must be severed,
thereby providing supervision of the
connection in the event that the wire
becomes dislodged from under the
terminal.
NOTE: The Model VSR-CF has two switches, one can be used to operate a central station, proprietary or remote
signaling unit, while the other contact is used to operate a local audible or visual annunciator.
TESTING
The frequency of inspection and testing for the model If there are no provisions for testing the operation of the
VSR-CF and its associated protective monitoring system flow detection device on the system, application of the
should be in accordance with applicable NFPA Codes VSR-CF is not recommended or advisable.
and Standards and/or the authority having jurisdiction
(manufacturer recommends quarterly or more frequent- A minimum flow of 10 gpm is required to activate this
ly). device.
If provided, the inspector’s test valve, that is usually IMPORTANT NOTICE: Please advise the person
located at the end of the most remote branch line, responsible for testing of the fire protection system that
should always be used for test purposes. this system must be tested in accordance with the
testing instructions.
UL Listed
Service Pressure: Up to 300 PSI
Minimum Flow Rate for Alarm: 10 GPM
Maximum Surge: 18 FPS
Contact Ratings: Two sets of SPDT (Form C)
15.00 Amps at 125/250VAC
2.00 Amps at 30VDC Resistive
Conduit Entrances: Two knockouts provided for 1/2" conduit
Environmental Specifications:
• Suitable for indoor or outdoor use with factory installed
gasket and die-cast housing.
• NEMA 4 Rated Enclosure - use with appropriate conduit
fitting
• Temperature Range: 40°F/120°F, 4.5°C/49°C
Pipe Schedules: 10 thru 40
Caution: This device is not intended for applications in
explosive environments.
Service Use:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
U.S. PAT. NO. 3921989 Residential occupancies up to four stories NFPA-13R
CANADIAN PAT. NO. 1009680 National Fire Alarm Code NFPA-72
OTHER PATENTS PENDING Optional: Cover tamper switch kit, Order Stock No. 0090018
POTTER ELECTRIC, Rd., 1990
GENERAL INFORMATION
The Model VSR-F 10" is a vane type waterflow switch for use INSTALLATION (See Fig. 2)
on wet sprinkler systems These devices may be mounted on horizontal or vertical pipe.
On horizontal pipe they should be installed on the top side of
The unit contains two single pole, double throw, snap action the pipe where they will be accessible. The units should not
switches and an adjustable, instantly recycling pneumatic be installed within 6" of a fitting which changes the direction
retard. The switches are actuated when a flow of 10 gallons of the waterflow or within 24" of a valve or drain.
per minute or more occurs downstream of the device. The
flow condition must exist for a period of time necessary to Drain the system and drill a hole with a diameter of 2" ± 1/8"
overcome the selected retard period. in the pipe using a circular saw in a slow speed drill.
ENCLOSURE Clean the inside pipe of all growth or other material for a
The unit is enclosed in a general purpose, die-cast housing. distance equal to the pipe diameter on either side of the hole.
The cover is held in place with two tamper resistant screws
which require a special key for removal. A field installable Roll the vane so that it may be inserted into the hole; do not
cover tamper switch is available as an option which may be bend or crease it. Insert the vane so that the arrow on the
used to indicate unauthorized removal of the cover. See saddle points in the direction of the waterflow. Install the
Bulletin No. 5400775 for installation instructions of this saddle strap and tighten nuts alternately to an eventual 50 ft-
switch. lbs. of torque (see Fig. 2). The vane must not rub the inside
of the pipe or bind in any way.
FIG. 1 FIG. 2
SWITCH TERMINAL CONNECTIONS
CLAMPING PLATE TERMINAL
CAUTION:
An uninsulated section of
a single conductor should
not be looped around the
terminal and serve as two
separate connections.
The wire must be severed,
thereby providing supervi-
sion of the connection in
the event that the wire
becomes dislodged from
under the terminal.
NOTE:
The Model VSR-F 10" has two switches, one can be used to operate a central station, proprietary or remote signaling unit, while the
other contact is used to operate a local audible or visual annunciator.
TESTING
The frequency of inspection and testing for the model VSR-F 10" and its associated protective monitoring system should be in
accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends
quarterly or more frequently).
If provided, the inspectors test valve, that is usually located at the end of the most remote branch line, should always be used for
test purposes.
If there are no provisions for testing the operation of the flow detection device on the system, application of the VSR-F 10" is not
recommended or advisable.
A minimum flow of 10 gpm is required to activate this device.
IMPORTANT NOTICE: Please advise the person responsible for testing of the Fire Protection System that this system must be
tested in accordance with the Testing Instructions.
GENERAL INFORMATION: The Model VSR-FE-2 is a vane INSTALLATION: See Fig. 1. These devices may be mounted
type waterflow switch for use on wet sprinkler systems. It is on horizontal or vertical pipe. On horizontal pipe they should
UL Listed and FM Approved for use on steel pipe; schedules be installed on the top side of the pipe where they will be
10 thru 40, sizes 2" thru 8". accessible. The units should not be installed within 6" of a
fitting which changes the direction of the waterflow or within
The unit may also be used as a sectional waterflow detector 24" of a valve or drain.
on large systems.
Drain the system and drill a hole in the pipe using a circular
The unit contains an output relay and an adjustable electronic saw in a slow speed drill. The 2" and 2 1/2" devices require a
retard. The relay is actuated when a flow of 10 gallons per hole with a diameter of 1 1/4" +1/8" -1/16". All other sizes
minute or more occurs downstream of the device. The flow require a hole with a diameter of 2" ± 1/8".
condition must exist for a period of time necessary to over-
come the selected retard period. Clean the inside of the pipe of all growth or other material for a
distance equal to the pipe diameter on either side of the hole.
ENCLOSURE: The unit is enclosed in a general purpose, die-
cast housing. The cover is held in place with two tamper Roll the vane so that it may be inserted into the hole; do not
resistant screws which require a special key for removal. A bend or crease it. Insert the vane so that the arrow on the
field installable cover tamper switch is available as an option saddle points in the direction of the waterflow. Install the
which may be used to indicate unauthorized removal of the saddle strap and tighten nuts alternately to an eventual 50 ft.-
cover. See bulletin no. 5400775 for installation instructions of lbs. of torque (see Fig. 1). The vane must not rub the inside of
this switch. the pipe or bind in any way.
1&2 30
1, 2, & 3 45
1, 2, 3, & 4 60
1, 2, 3, 4, & 5 75
1, 2, 3, 4, 5, & 6 90
7 not used
8 not used
TESTING: The operation of the waterflow switch should be If there are no provisions for testing the operation of the
tested upon completion of installation and periodically there- flow detection device on the system, application of the
after in accordance with the applicable NFPA codes and VSR-FE-2 is not recommended or advisable.
standards and/or the authority having jurisdiction (manufac-
A flow of 10 GPM is required to activate this device.
turer recommends quarterly or more frequently).
IMPORTANT NOTICE: Please advise the person
If provided, the inspector’s test valve, that is usually
responsible for testing of the fire protection system that
located at the end of the most remote branch line, should
this system must be tested in accordance with the
always be used for test purposes.
preceding section.
GENERAL INFORMATION: The Model VSG is a flexible INSTALLATION: See Fig. 1. These devices may be mounted
vane type of waterflow switch for use in wet pipe water mist on a horizontal or vertical pipe. On horizontal pipe they
systems where a low flow for alarm is required. It is designed should be installed on the top side of the pipe where they will
for installation in sections of 2 to 4 inch stainless steel or be accessible. The units should not be installed within 6" of a
brass pipe with wall thickness in accordance with the above fitting which changes the direction of the waterflow or within
specifications (see “Nominal OD and Wall Thickness”). 24" of a valve or drain.
The unit may also be used as a sectional waterflow detector Drain the system and drill a hole in the pipe using a circular
on large systems. saw in a slow speed drill. The 2" and 2 1/2" devices require a
The unit contains an output relay and an adjustable electronic hole with a of 1 1/4" +1/8" -1/16". The 3" and 4" devices
retard. The relay is actuated when a flow of 3 gallons per require a hole with a diameter of 2" ± 1/8".
minute or more occurs downstream of the device. The flow Clean the inside of the pipe of all growth or other material for
condition must exist for a period of time necessary to a distance equal to the pipe diameter on either side of the
overcome the selected retard period. hole.
ENCLOSURE: The unit is enclosed in a general purpose, Roll the vane so that it may be inserted into the hole; do not
die-cast housing. The cover is held in place with two tamper bend or crease it. Insert the vane so that the arrow on the
resistant screws which require a special key for removal. A saddle points in the direction of the waterflow. Install the
field installable cover tamper switch is available as an option saddle strap and tighten nuts alternately to an eventual 50 ft-
which may be used to indicate unauthorized removal of the lbs. of torque. See Fig. 1. The vane must not rub the inside
cover. See bulletin no. 5400775 for installation instructions of of the pipe or bind in any way.
this switch.
CAUTION:
When supervised circuits are used the following must be observed: An uninsulated
section of a single conductor should not be looped around the terminal and serve as two
separate connections. The wire must be severed, thereby providing supervision of the
connection in the event that the wire becomes dislodged from under the terminal.
TESTING: The operation of the waterflow switch and the associated alarms is to be tested upon completion of the
installation and periodically thereafter in accordance with the applicable NFPA standards and/or the authority having
jurisdiction (manufacturer recommends quarterly or more frequently).
INSTALLATION AND TEST PROCEDURES TESTING: Accomplished by opening the inspector's end-of-line test
The Potter PS10A Series Pressure Actuated Switches are designed valve. Allow time to compensate for system or control retard.
for the detection of a waterflow condition in automatic fire sprinkler CAUTION: Method 2 is not applicable for remote station service use,
systems of particular designs such as wet systems with alarm check if there is an unsupervised shut-off valve between the alarm check
valves or dry pipe systems. They may also be used to provide a low valve and the PS10A.
pressure supervisory signal. They may be adjusted to operate on
pressure between 4 and 20 PSI. WET SYSTEM WITH EXCESS PRESSURE:
Connect PS10A into alarm port piping extending from alarm check
MOUNTING: Device should be mounted in upright position (threaded valve. Retard provisions are not required. Insure that no unsupervised
connection down). Requires NEMA type 4 conduit hub for outdoor shut-off valves are present between the alarm check valve and the
installations. PS10A.
TESTING: The operation of the pressure alarm switch should be TESTING: Accomplished by opening the water by-pass test valve or
tested upon completion of installation and periodically thereafter in the inspector's end-of-line test valve. When using end-of-line test,
accordance with the applicable NFPA codes and standards and/or the allow time for excess pressure to bleed off.
authority having jurisdiction (manufacturer recommends quarterly or
more frequently). DRY SYSTEM:
Connect PS10A into alarm port piping that extends from the intermedi-
WET SYSTEM: ate chamber of the alarm check valve. Install on the outlet side of the
METHOD 1: When using PS10A and control unit with retard - connect in-line check valve of the alarm port piping. Insure that no unsuper-
PS10A into alarm port piping on the input side of retard chamber and vised shut-off valves are present between the alarm check valve and
electrically connect PS10A to control unit that provides a retard to the PS10A.
compensate for surges. Insure that no unsupervised shut-off valves
are present between the alarm check valve and PS10A. TESTING: Accomplished by opening the water by-pass test valve.
METHOD 2: When using the PS10A for local bell application or with a CAUTION: The above tests may also activate any other circuit closer
control that does not provide a retard feature - the PS10A must be or water motor gongs that are present on the system.
installed on the alarm outlet side of the retard chamber of the sprinkler
system.
CAUTION:
An uninsulated section of a single conductor
should not be looped around the terminal and
serve as two separate connections. The wire
must be severed, thereby providing supervision of
the connection in the event that the wire becomes
dislodged from under the terminal.
CAUTION: Closing of any shutoff valves between the alarm check valve and the PS10A will render the PS10A inoperative. To comply with
NFPA-72 any such valve shall be electrically supervised with a supervisory switch such as Potter Model BVS.
ORDERING INFORMATION
Model Description Stock No.
PS10-1A Pressure switch with one set SPDT contacts 1340101
PS10-2A Pressure switch with two sets SPDT contacts 1340102
Hex Key 5250062
Cover Tamper Switch Kit 0090134
BVS 1/2" Ball Valve with tamper switch 1010150
ENGINEER/ARCHITECT SPECIFICATIONS
Pressure type waterflow switches shall be a Model PS10A as manufactured by Potter Electric Signal Co. of St. Louis, Mo. and
shall be installed on the sprinkler systems as shown on the drawings and/or specified herein.
Switches shall be provided with a 1/2" NPT male pressure connection to be connected into the alarm check valve of a “wet”
sprinkler system or into the intermediate chamber of a “dry” pipe system and shall be actuated by any flow of water to or in excess
of the discharge from one sprinkler head.
Switches shall have a maximum service pressure rating of 250 PSI and shall be factory adjusted to operate on pressure increase
at 6 ±1 PSI. There shall be one (1) or two (2) SPDT contacts rated at 15.0 Amps at 125/250VAC and 2.5 Amps at 30VDC.
The switch housing shall be weather proof and oil resistant. The cover shall incorporate tamper resistant screws.
The unit shall be UL and CSFM Listed, FM and LPC Approved, and NYMEA Accepted.
MODEL PS40A PRESSURE SWITCH FOR MONITORING HIGH UL and CSFM LISTED, FM and LPC APPROVED, NYMEA
AND/OR LOW PRESSURE VARIATIONS ACCEPTED
Dimensions: 4 3/4"W x 2 1/4"D x 4 3/8"H
Enclosure: Cover - Die-cast with textured red powdercoat
finish
Base - Plated Steel
Pressure Connection: 1/2" NPT Male
Factory Adjustment:
PS40-1A: Operates on decrease at 30 PSI
PS40-2A: Operates on increase at 50 PSI, and on
decrease at 30 PSI
Pressure Range: 10 - 175 PSI
Maximum Differential: Approx. 2 lbs. at 20 PSI
5 lbs. at 175 PSI
Maximum System Pressure: 250 PSI
Switch Contacts: SPDT (Form C)
15.0 Amps at 125/250VAC, 2.5 Amps at 30VDC
One set in PS40-1A, Two sets in PS40-2A
Environmental Specifications:
Indoor or outdoor use
NEMA 4/IP55 Rated Enclosure
Temperature range: -40°F to 140°F (-40°C to 60°C)
(Not for use in hazardous locations)
Service Use:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72
Tamper: Cover incorporates tamper resistant fasteners that
require a special key for removal. One key is supplied with
PS40-1A Single Switch - Stk. No.1340401 each device. For optional cover tamper switch kit, order Stock
PS40-2A Double Switch - Stk. No.1340402 No. 0090134.
The Potter PS40A Series are pressure actuated switches Dry System: Connect PS40A in air supply line on the system
designed primarily to detect a 10 PSI increase and/or decrease side of any shutoff or check valve.
from normal system pressure in automatic fire sprinkler
systems. Provision for testing the unit can be accomplished with the
installation of a Potter Bleeder Valve (Model BVL) in the line to
Typical applications are air pressure supervision in dry pipe the PS40A.
systems and pressure supervision of pressure tanks, air supply
or water supply. Testing: The operation of the pressure supervisory switch
should be tested upon completion of installation and periodi-
INSTALLATION AND TEST PROCEDURES cally thereafter in accordance with the applicable NFPA codes
and standards and/or the authority having jurisdiction (manu-
Mounting: Device should be mounted in upright position facturer recommends quarterly or more frequently).
(threaded connection down).
CAUTION: Testing the PS40A may activate other system
Requires NEMA type 4 conduit hub for outdoor installations. connected devices.
Engineer/Architect Specifications
Air pressure supervisory switch shall be a Model PS40A as manufactured by Potter Electric Signal Co. of St. Louis, Mo. and shall be installed on
the sprinkler systems as shown on the drawings and/or as specified herein.
Switches shall be provided with a 1/2" NPT male pressure connection to be connected into the air supply line on the system side of any shut-off
valve. A Model BVL bleeder valve as supplied by Potter Electric Signal Co. of St. Louis, Mo. or equivalent shall be connected in line with the
PS40A to provide a means of testing the operation of the supervisory switch. (See DWG. #924-1)
The switch unit shall contain SPDT (Form C) switch(es). One switch shall operate at a pressure decrease of 10 PSI from normal. If two
switches are provided, the second switch shall operate at a pressure increase of 10 PSI from normal. Switch contacts shall be rated at 15.0
Amps at 125/250VAC and 2.5 Amps at 30VDC. The units shall have a maximum pressure rating of 250 PSI and shall be adjustable from 10 to
175 PSI.
The switch housing shall be weatherproof and oil resistant. The cover shall incorporate tamper resistant screws.
The unit shall be UL and CSFM Listed, FM and LPC Approved, and NYMEA Accepted.
PRESSURE SWITCH FOR MONITORING WET SYSTEMS UL and CSFM LISTED, FM and LPC APPROVED,
WITH EXCESS PRESSURE NYMEA ACCEPTED
Dimensions: 4 3/4"W x 2 1/4"D x 4 3/8"H
Enclosure:
Cover - Die-cast with textured red powdercoat finish
Base - Plated Steel
Pressure Connection: 1/2" NPT Male
Factory Adjustment: Operates on decrease at 90 PSI
Pressure Range: 10 - 175 PSI
Maximum Differential: Approx. 2 lbs. at 20 PSI
5 lbs. at 175 PSI
Maximum System Pressure: 250 PSI
Switch Contacts: Two sets of SPDT (Form C)
15.0 Amps at 125/250VAC
2.5 Amps at 30VDC
Environmental Specifications:
Indoor or Outdoor Use
NEMA 4/IP55 Rated Enclosure
Temperature range: -40°F to 140°F (-40°C to 60°C)
(Not for use in hazardous locations)
Service Use:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72
Tamper: Cover incorporates tamper resistant fasteners that
require a special key for removal. One key is supplied with
PS100-2A Double Switch - Stock No. 1341002 each device. For optional cover tamper switch kit, order Stock
No. 0090134.
The Potter PS100-2A is a pressure actuated switch designed Provision for testing the unit can be accomplished with the
primarily to detect a 10 PSI decrease from normal system installation of a Potter Bleeder Valve (Model BVL) in the line to
pressure in automatic fire sprinkler systems. the PS100-2A.
TYPICAL APPLICATION: Alarm device on systems with Testing: The operation of the pressure supervisory switch
excess pressure should be tested upon completion of installation and periodical-
ly thereafter in accordance with the applicable NFPA codes
INSTALLATION AND TEST PROCEDURES: Device should and standards and/or the authority having jurisdiction (manu-
be mounted in upright position (threaded connection down). facturer recommends quarterly or more frequently).
Requires NEMA type 4 conduit hub for outdoor installations. CAUTION: Testing the PS100-2A may activate other system
connected devices.
WET SYSTEM: (With excess pressure) Connect PS100-2A in
the constant pressure line on the system side of any shut-off
or check valve.
DIMENSIONS
NOTE:
TO PREVENT LEAKAGE, APPLY TEFLON TAPE
SEALANT TO MALE THREADS ONLY.
WARNING:
USE OF PIPE JOINT CEMENT MAY RESULT IN
OBSTRUCTION OF APERTURE AND LOSS OF
SIGNAL.
FIELD ADJUSTMENTS: The operating point of the switch
(or switches on the PS100-2A) can be adjusted to any
point between 10 and 175 PSI by turning the adjustment
knob(s) clockwise to raise the actuation point, and
counter-clockwise to lower the actuation point. In the case
of the PS100-2A, the two switches operate completely
independently of one another, and each switch may be
adjusted to actuate at any point the system requires. Final
adjustment should be made with a pressure gauge.
Engineer/Architect Specifications
Pressure type waterflow switch shall be a Model PS100-2A as manufactured by Potter Electric Signal Co. of St. Louis, Mo. and shall be installed
on the sprinkler systems as shown on the drawings and/or as specified herein.
Switches shall be provided with a 1/2" NPT male pressure connection to be connected into the excess pressure supply line on the system side
of any shut-off valve. A Model BVL Bleeder Valve as supplied by Potter Electric Signal Co. of St. Louis, MO or equivalent shall be connected in
line with the PS100A to provide a means of testing the operation of the pressure type switch.
The switch unit shall contain two SPDT (Form C) switches. Both switches shall operate when the pressure decreases to 90 PSI. The switch
contacts shall be rated at 15.0 Amps at 125/250VAC and 2.5 Amps at 30VDC. The unit shall have a maximum pressure rating of 250 PSI and
shall be adjustable from 10 to 175 PSI.
The switch housing shall be weatherproof and oil resistant. The cover shall incorporate tamper resistant screws.
The unit shall be UL and CSFM Listed, FM and LPC Approved, and NYMEA Accepted.
PRESSURE SWITCH FOR MONITORING HIGH AND/OR UL and CSFM LISTED, FM and LPC APPROVED,
LOW PRESSURE VARIATIONS NYMEA ACCEPTED
Dimensions: 4 3/4"W x 2 1/4"D x 4 3/8"H
Enclosure:
Cover - Die-cast with textured red powdercoat finish
Base - Plated Steel
Pressure Connection: 1/2" NPT Male
Factory Adjustment:
PS120-1A: Operates on decrease at 110 PSI
PS120-2A: Operates on increase at 130 PSI, and on
decrease at 110 PSI
Pressure Range: 10 - 175 PSI
Maximum Differential: Approx. 2 lbs. at 20 PSI
5 lbs. at 175 PSI
Maximum System Pressure: 250 PSI
Switch Contacts: SPDT (Form C)
15.0 Amps at 125/250VAC, 2.5 Amps at 30VDC
One set in PS120-1A, Two sets in PS120-2A
Environmental Specifications:
Indoor or outdoor use
NEMA 4/IP55 Rated Enclosure
Temperature Range: -40°F to 140°F (-40°C to 60°C)
(Not for use in hazardous locations)
Service Use:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72
Tamper: Cover incorporates tamper resistant fasteners that
PS120-1A Single Switch - Stock No. 1341201 require a special key for removal. One key is supplied with
PS120-2A Double Switch - Stock No. 1341202 each device. For optional cover tamper switch kit, order
Stock No. 0090134.
The Potter PS120A Series are pressure actuated switches excess pressure line on the system side of any shut-off or
designed primarily to detect a 10 PSI increase and/or check valve.
decrease from normal system pressure in automatic fire
sprinkler systems. Provision for testing the unit can be accomplished with the
installation of a Potter Bleeder Valve (Model BVL) in the line to
Typical applications are pressure supervision in systems the PS120A.
with excess pressure.
Testing: The operation of the pressure supervisory switch
INSTALLATION AND TEST PROCEDURES should be tested upon completion of installation and periodi-
Mounting: Device should be mounted in upright position cally thereafter in accordance with the applicable NFPA codes
(threaded connection down). and standards and/or the authority having jurisdiction
(manufacturer recommends quarterly or more frequently).
Requires NEMA type 4 conduit hub for outdoor installations.
CAUTION: Testing the PS120A may activate other system
Wet System (with excess pressure): Connect PS120A in the connected devices.
Engineer/Architect Specifications
Pressure supervisory switch shall be a Model PS120A as manufactured by Potter Electric Signal Co. of St. Louis, MO and shall be installed on the
sprinkler systems as shown on the drawings and/or as specified herein.
Switches shall be provided with a 1/2" NPT male pressure connection and shall be connected into the excess pressure supply line on the system
side of any shut off valve. A Model BVL Bleeder Valve as supplied by Potter Electric Signal Co. of St. Louis, MO or equivalent shall be connected
in line with the PS120A to provide a means of testing the operation of the supervisory switch.
The switch unit shall contain SPDT (Form C) switch(es). One switch shall operate at a pressure decrease of 10 PSI from normal. If two switches
are provided, the second switch shall operate at a pressure increase of 10 PSI from normal. Switch contacts shall be rated at 15.0 Amps at 125/
250VAC and 2.5 Amps at 30VDC. The unit shall have a maximum pressure rating of 250 PSI and shall be adjustable from 10 to 175 PSI.
The switch housing shall be weatherproof and oil resistant. The cover shall incorporate tamper resistant screws.
The unit shall be UL and CSFM Listed, FM and LPC Approved, and NYMEA Accepted.
FIG. 3 FIG. 4
SWITCH TERMINAL CONNECTIONS
Retard Adjustment: CLAMPING PLATE TERMINAL
To change time turn
knob (either direction)
for desired time delay.
Use the minimum
amount of retard neces-
sary to prevent false
alarms, a “B” setting is
usually adequate for CAUTION:
this. Factory set at “B”. An uninsulated section of a single conductor
should not be looped around the terminal and
serve as two separate connections. The wire
must be severed, thereby providing supervision
APPROX. RETARD SETTINGS (IN SEC.)
of the connection in the event that the wire
0 A B C D E becomes dislodged from under the terminal.
0 10-25 20-40 35-55 50-70 60-90
WARNING
Use teflon tape sealant
only. Apply only to male
threads of connectors.
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • P.O. Box 28480 55 Glen Cameron Road
St. Louis, MO 63146-4161 Thornhill, Ontario, Canada L3T 1P2
(314) 878-4321 • (800) 325-3936 (905) 882-1833
The Model PCVS is a weather proof and tamper resistant nished with each device and should be left with the
switch for monitoring the open position of fire sprinkler building owner or responsible party. Replacement or
control valves of the post indicator, butterfly and other additional cover screws and hex keys are available. See
types. Depending on the model, one or two SPDT (Form ordering information on page 6.
C) contacts are provided which will operate when the
OPTIONAL COVER TAMPER SWITCH: A field instal-
valve position is altered from an open state.
lable cover tamper switch is available as an option which
The unit mounts in a 1/2" NPT tapped hole in the post may be used to indicate removal of the cover. See
indicator or butterfly valve housing. The device is en- ordering information on page 6.
gaged by the indicating assembly of the post indicator or
TESTING: The PCVS and its associated protective
the operating mechanism of the butterfly valve, actuating
monitoring system should be tested in accordance with
switch(es) when the valve is fully open. The unit should
applicable NFPA codes and standards and/or the authori-
be installed where it is accessible for service.
ty having jurisdiction (manufacturer recommends quarter-
The cover is held in place by two tamper resistant screws ly or more frequently).
that require a special tool to remove. The tool is fur-
NOTE: If the sprinkler system is in service the owner or If the target moved down as the valve was closed, mea-
authorized representative should be notified, before any work is sure the distance from the bottom of the head to the upper
done on the system, that the valve controlling the water supply portion of the target assembly that will contact the trip rod
to the system may be closed for periods of time during the of the PCVS (see Fig. 4). Add 1/8" to this measurement.
installation and testing of this device, resulting in all or portions
of the system being inoperative during these periods. 4. Mark the housing at the proper location. Using a 23/32"
drill bit, drill and then tap a 1/2" NPT in the housing on the
If the system is not in service and valve is closed, be sure that side that coincides with the portion of the target assembly
opening the valve will not allow any unwanted water flow due to that will engage the trip rod of the PCVS.
openings in the system, such as heads off, broken or incom-
plete piping, etc. (Continued on page 3.)
PBK - PRATT IBV BUTTERFLY VALVE KIT PVK (STOCK NO. 1000060) - PRATT PIVA POST
FIG. 10 FIG. 11 INDICATOR VALVE KIT
FIG. 12
CAUTION:
An uninsulated section of a single conductor should not be
looped around the terminal and serve as two separate
connections. The wire must be severed, thereby providing
supervision of the connection in the event that the wire
becomes dislodged from under the terminal.
ORDERING INFORMATION
MODEL DESCRIPTION STOCK NO.
PCVS-1 Potter Control Valve Switch (single switch) 1010107
PCVS-2 Potter Control Valve Switch (double switch) 1010207
-- Cover Screw 5490293
-- Hex Key for Cover Screws and Installation Adjustments 5250062
PBK-S Pratt Butterfly Valve Kit (Up to 12") 0090133
PBK-L Pratt Butterfly Valve Kit (14" and Up) 0090132
PVK Pratt Valve Kit 1000060
-- Optional Cover Tamper Switch Kit 0090131
For pressure reducer type valve installation kits (if required) contact valve manufacturer.
GENERAL INFORMATION additional cover screws and hex keys are available. See
The OSYSU is used to monitor the open position of an ordering information on page 4.
OS & Y (outside screw and yoke) type gate valve. This
device is available in two models; the OSYSU-1, contain- OPTIONAL COVER TAMPER SWITCH
ing one set of SPDT (Form C) contacts and the OSYSU- A field installable cover tamper switch is available as an
2, containing two sets of SPDT (Form C) contacts. option which may be used to indicate removal of the
These switches mount conveniently to most OS & Y cover. See ordering information on page 4.
valves ranging in size from 2" to 12". They will mount on
some valves as small as 1/2". TESTING
The OSYSU and its associated protective monitoring
The cover is held in place by two tamper resistant system should be inspected and tested in accordance
screws that require a special tool to remove. The tool is with applicable NFPA codes and standards and/or the
furnished with each device and should be left with the authority having jurisdiction (manufacturer recommends
building owner or responsible party. Replacement or quarterly or more frequently).
CAUTION:
An uninsulated section of a single conductor Contacts shown in normal (valve open) condition.
should not be looped around the terminal and
serve as two separate connections. The wire
must be severed, thereby providing supervision TYPICAL SWITCH ACTION
of the connection in the event that the wire
becomes dislodged from under the terminal.
ORDERING INFORMATION
MODEL DESCRIPTION STOCK NO.
OSYSU-1 Outside Screw & Yoke-Supervisory Switch (Single switch) 1010106
OSYSU-2 Outside Screw & Yoke-Supervisory Switch (Double switch) 1010206
-- Cover Screw 5490293
-- Hex Key for Cover Screws and Installation Adjustments 5250062
-- Optional Cover Tamper Switch Kit 0090131
For pressure reducer type valve installation kits (if required) contact valve manufacturer.
UL Listed
GENERAL INFORMATION
INSTALLATION
CAUTION:
An uninsulated section of a single conductor should not be looped around the terminal and
serve as two separate connections. The wire must be severed, thereby providing supervision
of the connection in the event that the wire becomes dislodged from under the terminal.
TESTING
The BVS-1/2" and its associated protective monitoring system should be inspected and tested in accordance with the
applicable NFPA codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly
or more frequently).
GENERAL INSTALLATION
The Model PTS-B is designed to supervise sprinkler system The receptacle housing is mounted near the valve. With the
control valves. This unit is particularly useful for unusual valve in the full OPEN position, the approximate 8' of water-
conditions, such as non-rising stem valves. proof wire provided, can be cut to the desired length and
looped through the valve wheel and terminated in the plug.
Turning the valve wheel will pull the plug out of the receptacle.
The plug cannot be reinserted after operation until the cover is
This forms a normally closed single circuit loop when the plug
removed with special key provided. Cover tamper is provided.
is inserted into the receptacle.
CONTACTS: SPST normally closed when plug is in recep-
tacle. Contacts rated 250 mA 28 VDC/VAC. The cover tamper switch can be series wired into this loop or
can be wired into a separate normally closed protection circuit
The PTS-B is NOT available with normally open contacts. (see wiring diagrams).
WARNING
As stipulated by FACTORY MUTUAL and UNDERWRITER'S LABORATORIES
This unit is not intended or designed for ordinary use. It is a special application device to be used for unusual conditions such as non-rising
stem gate valves where no other approved or listed method of protection is available or practical. As this unit does not meet NFPA codes and
standards, requiring restoration signal when the valve is positioned to normal, special attention should be given by the responsible parties to
assure that the proper operation of this device is maintained. This device should only be restored to normal when the valve is in the normal
condition.
COVER TAMPER IN SERIES WITH PROTECTIVE CIRCUIT SEPARATE COVER TAMPER CIRCUIT
The Model PMS magnetic plug switch is designed to supervise sprinkler system control valves. This unit is particularly
useful on non-rising stem valves.
The unit consists of a glass magnetic reed switch sealed in a stainless steel tube, a condulet fitting for connection of
the external circuit to the cable that is connected to the switch, and a condulet fitting that houses the magnet and
serves as a receptacle for the stainless steel tube.
INSTALLATION: OPERATION:
The bracket holding the two condulet fittings is mounted When the valve wheel is turned, the encased switch will
on the wall near the valve, in such a manner that when pull out of its receptacle, and away from the magnet, and
the cable is fed thru the valve wheel and the tube is the switch contacts will transfer. A key that is provided
inserted into its receptacle, turning the wheel will cause must be inserted in the keyhole in the receptacle cover
the tube to pull straight out of its receptacle. and turned before the tube can be re-inserted.
FIG. 1 CONTACT CONDITIONS FIG. 2 TYPICAL ELECTRICAL CONNECTIONS
WARNING
As stipulated by FACTORY MUTUAL and UNDERWRITERS LABORATORIES
This unit is not intended or designed for ordinary use. It is a special application device to be used for unusual conditions such as non-rising
stem gate valves where no other approved method of protection is available or practical. As this unit does not meet NFPA standards,
requiring restoration signal when the valve is positioned to normal, special attention should be given by the responsible parties to assure that
the proper operation of this device is maintained. This device should only be restored to normal when the valve is in the normal condition.
UL Listed
Dimensions:Housing - 5.56"H x 3.50"W x 2.56"D
14.1cm H x 8.9cm W x 6.5cm D
Weight: 11.0 lb / 4.95 kg
Enclosure: Cast aluminum with red enamel finish
Applications: Steel or wood tanks
(With the optional wood bushing adapter,
Stock No. 5180199)
Contacts: Two sets SPDT (Form C)
One set for high / One set for low
Rated - 15.00 Amps at 125/250VAC
0.50 Amp at 125VDC
0.25 Amp at 250VDC
Detection Range: Before 3" Rise /Before 3" Fall
Environmental Specifications:
• Suitable for indoor or outdoor use
STOCK NO. 1010117 • Temperature range: 40°F to 140°F (4.5°C to 60°C)
• NEMA 4 rated enclosure
Maximum Pressure: 175 PSI
The Model WLS Water Level Switch is a float operated existing 2" steel flanges. An optional bushing adapter
device for supervising water level in a sprinkler supply with a buttress thread is available for mounting in wooden
gravity or pressure tank. tanks.
The Model WLS has a bushing with 1 1/2" American The unit is capable of detecting the level of water before a
Standard Pipe Threads for mounting in steel tanks. A 1 1/ 3" rise and/or a 3" fall in the water level in a pressure tank,
2" x 2" adapter bushing is available for mounting in as required.
FIG. 1
INSTALLATION INSTRUCTIONS
A buttress thread nut and gasket are available for use with into the adapter (see Fig. 4).
devices on installations where the inside of the tank is NOTE: The high signal is not required for gravity tanks
accessible and it is not convenient to weld a flange on the and the WLS can be wired so that either High or Low or
tank. The nut and gasket can also be used in a wood both switches may be used (see Fig. 5).
tank that is not sound enough to hold a thread (see Fig.
2). For pressure tanks, weld the 1 1/2" NPT threaded flange
(#6660225) into the tank at the desired water level and
For installation in steel gravity tanks, weld a 1 1/2" NPT use both high and low signals.
threaded flange (#6660225) 9" below the required water
level to receive the 1 1/2" bushing (see Fig. 3). To replace an existing Potter WLS in a steel tank with a
welded flange a 1 1/2" x 2"NPT bushing adapter
For wood gravity tanks, bore a 2 3/8" hole in the center of (#5020126) is available. Thread the bushing adapter into
a stave 9" below the required water level and screw the the 2" welded flange securely then install the WLS into
buttress bushing adapter (#5180199) in place, allowing the adapter.
the bushing to cut its own thread, then install the WLS
CAUTION: Do not lift or hold device by float or float rod as
bending may occur.
FIG. 2 Wood or Steel Tank FIG. 3 Steel Tank Installa- FIG. 4 Wood Tank Installation
Installation tion
TTS-W
TTS-S
The Model TTS-S is a water tank temperature superviso- A buttress thread nut and gasket are available for use
ry switch preset to give a low temperature signal at 40°F/ with the TTS-W for installations where the inside of the
4.5°C and a high temperature signal at 140°F/60°C tank is accessible and it is not convenient to weld a
(±3°F/2°C). It is UL Listed and FM Approved. flange on the tank.
A glass mercury thermostat is used for low temperature The nut and gasket can also be used on a wood tank,
sensing and a bi-metal thermostat for high temperature which is not sound enough to hold a thread (see Fig. 1).
sensing. A diode is used in this unit as a testing aid. Locate the switch at a point 24 inches below the required
When the polarity of DC current is reversed at the feed water level of the tank.
wires to a TTS, the diode in the circuit prevents the flow
For steel tanks, weld in a No. 282-1 pipe flange or drill a
of current, proving the absense of a short circuit fault in
tap tank to receive the one inch pipe thread of the
the wiring or the device itself.
bushing (see Fig. 2).
CONTACTS: .15 Amp at 115 VDC
For wood tanks, drill a 1 3/16" hole in the center of a
The TTS, tank temperature switch is supplied with a one stave and thread the bushing into the tank allowing the
inch pipe thread for steel tanks (Model TTS-S) or with a butress bushing to cut its own thread (see Fig. 3).
buttress thread for wood tanks (Model TTS-W).
INSTALLATION
ACCESSORIES
Flange 1" 5020010
Buttress Nut 5020105
Gasket 5330035
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • P.O. Box 28480 55 Glen Cameron Road
St. Louis, MO 63146-4161 Thornhill, Ontario, Canada L3T 1P2
(314) 878-4321 • (800) 325-3936 (905) 882-1833
Mounting: Surface
RTS-O STK. #1010108
RTS-C STK. #1010109
Environmental Specifications:
• For use in hazardous locations, Classified as:
Class I: Groups C, D, Div. 1
Class II: Groups E, F, G, Div. 1
Class III: Div. 1
• Suitable for indoor or outdoor use with factory installed gasket
and cast aluminum housing.
• NEMA 4 Rated Enclosure - use with appropriate conduit fitting
• Temperature: 40°F/120°F, 4.5°C/49°C
• Non-corrosive sleeve factory installed in saddle.
Sizes Available: Pipe schedules 10 thru 40, sizes 2" thru 8"
FIG. 1 FIG. 2
SWITCH TERMINAL
CONNECTIONS
CLAMPING PLATE
TERMINAL
CAUTION:
An uninsulated section
of a single conductor
should not be looped
around the terminal and
serve as two separate
connections. The wire
must be severed,
thereby providing
supervision of the
connection in the event
that the wire becomes
CAUTION: When this device is to be installed in an area that is classified as “Hazardous”, the
dislodged from under the
person responsible for safety in the area should be contacted to determine if the tools and opera-
terminal.
tions required for the installation of the device and associated components are permitted in the
area. To reduce the risk of ignition of hazardous atmospheres, disconnect supply circuits before
opening enclosure. Keep cover tightly closed when in operation. cover screws must be torqued to a
minimum of 20 in. lbs.
NOTE: The Model VSR-FEX has two switches, one can be used to operate a central station, proprietary or remote signaling unit,
while the other contact is used to operate a local audible or visual annunciator.
TESTING: The frequency of testing for the model VSR-FEX for test purposes. If there are no provisions for testing the
and its associated protective monitoring system should be in operation of the flow detection device on the system,
accordance with applicable NFPA Standards and/or the application of the VSR-FEX is not recommended or advisable.
authority having jurisdiction (manufacturer recommends
A minimum flow of 10 gpm is required to activate this device.
quarterly or more frequently).
IMPORTANT NOTICE: Please advise the person responsible
If provided, the inspector’s test valve, that is usually located at
for testing of the fire protection system that this system must be
the end of the most remote branch line, should always be used
tested in accordance with the testing instructions.
INSTALLATION AND TEST PROCEDURE: The Potter PS10- METHOD 2: When using the PS10-EX for local bell application
EX Pressure Actuated Switch is designed for the detection of a or with a control that does not provide a retard feature, the
waterflow condition in automatic fire sprinkler systems located PS10-EX must be installed on the alarm outlet side of the
in hazardous locations classified as shown above, of particular retard chamber of the sprinkler system.
designs such as wet systems with alarm check valves or dry TESTING: Accomplished by opening the inspector's end-of-line
pipe systems. It may also be used to provide a low pressure test valve. Allow time to compensate for system or control retard.
supervisory signal. It can be adjusted to operate on pressure CAUTION: Method 2 is not applicable for remote station
between 4 and 20 PSI. service use.
MOUNTING: Device should be mounted in upright position WET SYSTEM WITH EXCESS PRESSURE: Connect the
(threaded connection down). Requires NEMA Type 4 conduit PS10-EX into alarm port piping extending from alarm check
hub for outdoor installations. valve. Retard provisions are not required. Insure that no shut
off valves are present between the alarm check valve and the
TESTING: The operation of the pressure alarm switch should
PS10-EX.
be tested upon completion of installation and periodically
TESTING: Accomplished by opening the water by-pass test
thereafter in accordance with the applicable NFPA codes and
valve or the inspector's end-of-line test valve. When using end-
standards and/or the authority having jurisdiction (manufacturer
of-line test, allow time for excess pressure to bleed off.
recommends quarterly or more frequently).
DRY SYSTEM: Connect the PS10-EX into alarm port piping
WET SYSTEM:
that extends from the intermediate chamber of the alarm check
METHOD 1: When using PS10–EX and control unit with
valve. Install on the outlet side of the in-line check valve of the
retard, connect the PS10–EX into alarm port piping on the input
alarm port piping. Insure that no shut off valves are present
side of retard chamber and electrically connect PS10–EX to
between the alarm check valve and the PS10-EX.
control unit that provides a retard to compensate for surges.
TESTING: Accomplished by opening the water by-pass test valve.
Insure that no shut off valves are present between the alarm
check valve and the PS10–EX. CAUTION: The above tests may also activate any other circuit
closer or water motor gongs that are present on the system.
ORDERING INFORMATION
Model Description Stock No.
PS10-EX Pressure switch with two sets SPDT contacts 1350102
Hex Key 5250073
CAUTION: Closing of any shutoff valves between the alarm check valve and the PS10-EX will render the PS10-EX
inoperative. To comply with NFPA-72 any such valve shall be electrically supervised with a supervisory switch
such as Potter Model BVS.
CAUTION:
An uninsulated section of a single conductor should not be
looped around the terminal and serve as two separate
connections. The wire must be severed, thereby providing
supervision of the connection in the event that the wire
becomes dislodged from under the terminal.
PRESSURE SWITCH
TERMINATION
CAUTION: When this device is to be installed in an area that is classified as “HAZARDOUS”, the person
responsible for safety in the area should be contacted to determine if the tools and operations required for the
installation of the device and associated components are permitted in the area. To reduce the risk of ignition of
hazardous atmospheres, disconnect supply circuits before opening cover. Keep cover tight while circuits are live.
Cover screws must be torqued to 45-50 in. lbs.
ENGINEER/ARCHITECT SPECIFICATIONS
Pressure type waterflow switches shall be a Model PS10-EX as manufactured by Potter Electric Signal Co. of St. Louis, Mo. and
shall be installed on the sprinkler systems as shown on the drawings and/or specified herein.
Switches shall be provided with a 1/2" NPT male pressure connection to be connected into the alarm check valve of a “wet”
sprinkler system or into the intermediate chamber of a “dry” pipe system and shall be actuated by any flow of water to or in excess
of the discharge from one sprinkler head.
Switches shall have a maximum service pressure rating of 250 PSI and shall be factory adjusted to operate on pressure increase
at 6 ±1 PSI. There shall be two (2) SPDT contacts rated at 15.0 Amps at 125/250VAC and 2.5 Amps at 30VDC.
The switch housing shall be weather proof and oil resistant with a NEMA 4 rating. The cover shall incorporate tamper resistant
screws.
The unit shall be listed by Underwriters Laboratories, Inc. and CSFM and approved by Factory Mutual. It shall be rated for use in
hazardous locations classified as Class I, Groups B, C, D, Div. 1; Class II, Groups E, F, G, Div. 1; Class III, Div. 1.
The Potter PS40-EX is a pressure actuated switch Dry System: Connect PS40-EX in air supply line on the
designed primarily to detect a 10 PSI increase and/or system side of any shutoff or check valve.
decrease from normal system pressure in automatic fire
sprinkler systems located in hazardous locations classi- Provision for testing the unit can be accomplished with
fied as shown above. the installation of a Potter Bleeder Valve (Model BVL) in
the line to the PS40-EX.
Typical applications are air pressure supervision in dry
pipe systems and pressure supervision of pressure Testing: The operation of the pressure supervisory
tanks, air supply or water supply. switch should be tested upon completion of installation
and periodically thereafter in accordance with the
INSTALLATION AND TEST PROCEDURE applicable NFPA codes and standards and/or the
authority having jurisdiction (manufacturer recommends
Mounting: Device should be mounted in upright position quarterly or more frequently).
(threaded connection down).
CAUTION: Testing the PS40-EX may activate other
Requires NEMA Type 4 conduit hub for outdoor installations. system connected devices.
Ordering Information
Model Description Stock No.
PS40-EX Pressure switch with two sets SPDT contacts 1350402
BVL Bleeder Valve 1000018
Hex Key 5250073
CAUTION:
An uninsulated section of a single conductor should not be
looped around the terminal and serve as two separate
connections. The wire must be severed, thereby providing
supervision of the connection in the event that the wire
becomes dislodged from under the terminal.
FIELD ADJUSTMENTS
The operating point of the switches on the
PS40-EX can be adjusted to any point between
10 and 175 PSI by turning the adjustment
knob(s) clockwise to raise the actuation point,
and counter-clockwise to lower the actuation
point. The two switches operate completely
independently of one another, and each switch
may be adjusted to actuate at any point the
system requires. Final adjustment should be
made with a pressure gauge.
CAUTION: When this device is to be installed in an area that is classified as “HAZARDOUS”, the person
responsible for safety in the area should be contacted to determine if the tools and operations required for the
installation of the device and associated components are permitted in the area. To reduce the risk of ignition of
hazardous atmospheres, disconnect supply circuits before opening cover. Keep cover tight while circuits are live.
Cover screws must be torqued to 45-50 in. lbs.
ENGINEER/ARCHITECT SPECIFICATIONS
Air pressure supervisory switch shall be a Model PS40-EX as manufactured by Potter Electric Signal Co. of St. Louis, Mo. and
shall be installed on the sprinkler systems as shown on the drawings and/or as specified herein.
Switches shall be provided with a 1/2" NPT male pressure connection to be connected into the air supply line on the system side
of any shut-off valve. A Model BVL bleeder valve as supplied by Potter Electric Signal Co. of St. Louis, Mo. or equivalent shall be
connected between the air line to provide a means of testing the operation of the supervisory switch.
The switch unit shall contain SPDT (Form C) switches. One switch shall operate at a pressure decrease of 10 PSI from normal.
The second switch shall operate at a pressure increase of 10 PSI from normal. Switch contacts shall be rated at 15.0 Amps at
125/250 VAC and 2.5 Amps at 30 VDC. The units shall have a maximum pressure rating of 250 PSI and shall be adjusted from
10 to 175 PSI.
The switch housing shall be weatherproof and oil resistant with a NEMA 4 rating. The cover shall incorporate tamper resistant
screws.
The unit shall be listed by Underwriters Laboratories, Inc. and CSFM and approved by Factory Mutual. It shall be rated for use in
hazardous locations classified as Class I, Groups B, C, D, Div. 1; Class II, Groups E, F, G, Div. 1; Class III, Div. 1.
Environmental Limitations:
-40° to 140°F (-40°C to 60°C).
For use in hazardous locations.
Service Uses:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72
The PIVS-U-EX is designed to mount in a 1/2" tapped hole in Drill and tap the post at the location selected to receive the 1/2"
the post indicator housing. The PIVS-U-EX should be located NPT nipple on the switch.
so that the stem of the switch is held against the stem return
In some cases it may be necessary to attach an angle bracket
spring by the indicator assembly when the valve is open.
to the target assembly to engage the switch stem. Any excess
SWITCH ENCLOSURE: UL listed explosion proof switch length of the stem should be cut off with a hack saw.
enclosure. For hazardous locations. Class I, Group C & D;
Close the valve carefully and see that the switch stem is free to
Class II, Groups E, F, & G.
move and that no excess pressure is placed on the stem at the
INSTALLATION: See Figures 1, 2, 3, 4, and 5. Operate the end of its travel.
valve to determine whether the target moves up or down as the
Small adjustments of the target position may be made if
valve is closed.
necessary.
Open the valve fully and see that target indicates “OPEN”.
The contacts of the switch should operate when the valve is
Remove the head from the indicator post and remove target
closed 1 or 2 turns. The switch can be tested with a buzzer or
assembly.
ohmeter.
Select a location for the switch, so that the stem of the switch
Replace the head on the indicator post.
will be depressed by some part of the target assembly when
valve is fully open. The switch location should be accessible An alternate method of installation is shown in Figure 3. In this
for service. method one of the glass windows is replaced with a 1/4" thick
steel plate cut to fit in place of the glass and drilled and tapped
If the target assembly moves up when the valve is closed
to receive the 1/2" pipe nipple on the switch.
locate the switch below the target with the long part of the case
pointing down. A 1/2" or 3/4" square block of steel is attached to the target
assembly, in place of the cast letter plate, to actuate the switch
If the target assembly moves down when the valve is closed
stem.
locate the switch above the target with the long part of the case
pointing up. Figure 4 shows the switch mounted on a butterfly valve.
VALVE SIZES 1/2" THRU 2 1/2" VALVE SIZES 3" THRU 12"
FIG.1 FIG.2