Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Presostato Potter

Download as pdf or txt
Download as pdf or txt
You are on page 1of 57

SPRINKLER DIVISION

WATERFLOW SWITCHES

PRESSURE SWITCHES

SUPERVISORY DEVICES

EXPLOSION-PROOF DEVICES
VSR-F
VANE TYPE WATERFLOW
ALARM SWITCH WITH RETARD
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • P.O. Box 28480 55 Glen Cameron Road
St.Louis, MO 63146-4161 Thornhill, Ontario, Canada L3T 1P2
(314) 878-4321 • (800) 325-3936 (905) 882-1833

UL, ULC and CSFM Listed, FM and LPC Approved, NYMEA Accepted
Service Pressure: Up to 450 PSI
Minimum Flow Rate for Alarm: 10 GPM
Maximum Surge: 18 FPS
Contact Ratings: Two sets of SPDT (Form C)
15.0 Amps at 125/250VAC
2.0 Amps at 30VDC Resistive
Conduit Entrances: Two knockouts provided for 1/2" conduit
Environmental Specifications:
• Suitable for indoor or outdoor use with factory installed gasket
and die-cast housing.
• NEMA 4/IP54 Rated Enclosure - use with appropriate conduit
fitting
• Temperature Range: 40°F/120°F, 4.5°C/49°C
• Non-corrosive sleeve factory installed in saddle
Caution: This device is not intended for applications in explosive
environments
Sizes Available: Pipe schedules 10 thru 40, sizes 2" thru 8"
BS 1387 pipe 50mm thru 200mm
Service Use:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
Residential occupancy up to four stories NFPA-13R
U.S. PAT. NO. 3921989 National Fire Alarm Code NFPA-72
CANADIAN PAT. NO. 1009680
OTHERS PATENTS PENDING Optional: Cover Tamper Switch Kit, Stock No. 0090018
POTTER ELECTRIC, Rd., 1990

GENERAL INFORMATION INSTALLATION: See Fig.2


The Model VSR-F is a vane type waterflow switch for use on wet These devices may be mounted on horizontal or vertical pipe. On
sprinkler systems. It is UL Listed and FM Approved for use on horizontal pipe they should be installed on the top side of the pipe
steel pipe; schedules 10 through 40, sizes 2" thru 8". where they will be accessible. The units should not be installed
within 6" of a fitting which changes the direction of the waterflow or
LPC approved sizes are 2" thru 8" (50mm thru 200mm).
within 24" of a valve or drain.
The unit may also be used as a sectional waterflow detector on
Drain the system and drill a hole in the pipe using a circular saw in
large systems.
a slow speed drill. The 2" (50mm) and 2 1/2" (65mm) devices
The unit contains two single pole, double throw, snap action require a hole with a diameter of 1 1/4" + 1/8" - 1/16" (33mm
switches and an adjustable, instantly recycling pneumatic retard. ±2mm). All other sizes require a hole with a diameter of 2" ±1/8"
The switches are actuated when a flow of 10 gallons per minute (50mm ±2mm).
or more occurs downstream of the device. The flow condition
Clean the inside pipe of all growth or other material for a distance
must exist for a period of time necessary to overcome the
equal to the pipe diameter on either side of the hole.
selected retard period.
Roll the vane so that it may be inserted into the hole; do not bend or
ENCLOSURE: The unit is enclosed in a general purpose, die-
crease it. Insert the vane so that the arrow on the saddle points in
cast housing. The cover is held in place with two tamper
the direction of the waterflow. Install the saddle strap and tighten
resistant screws which require a special key for removal. A field
nuts alternately to an eventual 50 ft-lbs. of torque (see Fig. 2). The
installable cover tamper switch is available as an option which
vane must not rub the inside of the pipe or bind in any way.
may be used to indicate unauthorized removal of the cover. See
bulletin no. 5400775 for installation instructions of this switch. Specifications subject to change without notice.

PRINTED IN USA MKT. #8800001 - REV L PAGE 1 OF 2


MFG. #5400761 - 11/95
VSR-F
VANE TYPE WATERFLOW
SWITCH WITH RETARD
FIG. 1 FIG. 2
SWITCH TERMINAL CONNECTIONS
CLAMPING PLATE TERMINAL

CAUTION: TO INSTALL, DRILL A HOLE AS INDICATED:


An uninsulated section of
a single conductor should PIPE SIZE HOLE SIZE
not be looped around the
2" to 2 1/2" 1 1/4" +1/8" -1/16"
terminal and serve as two (50mm to 65mm) (33mm ±2mm)
separate connections.
3" to 8" 2" ±1/8"
The wire must be severed, (80mm to 200mm) (50mm ±2mm)
thereby providing supervi-
sion of the connection in
the event that the wire
becomes dislodged from
under the terminal.

FIG. 3 TYPICAL ELECTRICAL CONNECTIONS

Note: For supervised circuits see


“Switch Terminal Connections”
drawing and caution note (Fig. 1).

NOTES:
1. The Model VSR-F has two switches, one can be used to operate a central station, proprietary or remote signaling unit, while the
other contact is used to operate a local audible or visual annunciator.
2. A condition of LPC Approval of this product is that the electrical entry must be sealed to exclude moisture.

TESTING
The frequency of inspection and testing for the model VSR-F and its associated protective monitoring system should be in
accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends
quarterly or more frequently).

If provided, the inspector’s test valve, that is usually located at the end of the most remote branch line, should always be used for
test purposes. If there are no provisions for testing the operation of the flow detection device on the system, application of the
VSR-F is not recommended or advisable.

A minimum flow of 10 gpm is required to activate this device.

IMPORTANT NOTICE: Please advise the person responsible for testing of the fire protection system that this system must be
tested in accordance with the testing instructions.

PRINTED IN USA MKT. #8800001 - REV L PAGE 2 OF 2


MFG. #5400761 - 11/95
VSR-SF
VANE TYPE WATERFLOW
FOR SMALL PIPE
ALARM SWITCH WITH RETARD
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • St. Louis, MO 63146-4161 55 Glen Cameron Road
(314) 878-4321 • (800) 325-3936 Thornhill, Ontario, Canada L3T 1P2
www.pottersignal.com (905) 882-1833

UL, ULC, CSFM LISTED and NYMEA ACCEPTED


Service Pressure: Up to 250 PSI
Minimum Flow Rate for Alarm: 10 GPM
Maximum Surge: 18 FPS
Enclosure: Die-cast, red enamel finish
Cover held in place with tamper resistant screws
Contact Ratings: Two sets of SPDT (Form C)
15.0 Amps at 125/250 VAC
2.0 Amps at 30 VDC
Conduit Entrances: Two knockouts provided for 1/2" conduit.
Usage: Listed plastic, copper and schedule 40 iron pipe.
Fits pipe sizes - 1", 1 1/4", 1 1/2" and 2"
Note: 10 paddles are furnished with each unit, one for
each pipe size of threaded and sweat TEE, one for 1"
CPVC and one for 1 1/2" polybutylene.
(CTS-Copper tubing size)
Environmental Specifications:
• Suitable for indoor or outdoor use with factory installed gasket
and die-cast housing.
• NEMA 4/IP55 rated enclosure - use with appropriate conduit
fitting.
• Temperature range: 40° F to 120° F (4.5° C to 49° C)
Caution: This device is not intended for applications in
explosive environments.
Service Use:
Automatic Sprinkler NFPA-13
Stock No. 1113000 One or two family dwelling NFPA-13D
U.S. PAT. NO. 3921989, CANADIAN PAT. NO. 1009680 Residential occupancy up to four stories NFPA-13R
OTHER PATENTS PENDING. National Fire Alarm Code NFPA-72
Optional: Cover Tamper Switch Kit, order Stock No. 0090018
The Model VSR-SF is a vane type waterflow switch for use on waterflow.
wet sprinkler systems that use 1", 1 1/4", 1 1/2" or 2" pipe size.
The vane must not rub the inside of the TEE or bind in any
The unit may also be used as a sectional waterflow detector
way. The stem should move freely when operated by hand.
on large systems.
The device can also be used in copper or plastic pipe installa-
The unit contains two single pole double throw snap action
tions with the proper adapters so that the specified TEE fitting
switches and an adjustable, instantly recycling pneumatic
may be installed on the pipe run.
retard. The switches are actuated when a flow of 10 gallons
per minute or more occurs downstream of the device. The flow INSPECTION AND TESTING: Check the operation of the unit
condition must exist for a period of time necessary to over- by opening the inspector’s test valve at the end of the sprin-
come the selected retard period. kler line or the drain and test connection, if an inspector’s test
valve is not provided.
INSTALLATION: These devices may be mounted in horizon-
tal or vertical pipe. On horizontal pipe they should be installed If there are no provisions for testing the operation of the flow
on the top side of the pipe where they will be accessible. The detection device on the system, application of the VSR-SF is
units should not be installed within 6" of a valve, drain or fitting not recommended or advisable
which changes the direction of the waterflow. The unit has a
1" NPT bushing for threading into a non-corrosive TEE. See The frequency of the inspection and testing and its associated
Fig. 2 for proper TEE size, type and installation. protective monitoring system should be in accordance with the
applicable NFPA Codes and Standards and/or authority
Screw the device into the TEE fitting as shown in Fig. 2. Care having jurisdiction (manufacturer recommends quarterly or
must be taken to properly orient the device for the direction of more frequently).

PRINTED IN USA MKT. #8800003 - REV N PAGE 1 OF 2


MFG. #5400802 - 7/97
VSR-SF
FOR SMALL PIPE VANE TYPE WATERFLOW
ALARM SWITCH WITH RETARD
FIG. 1 FIG. 2

Retard Adjustment:
To change time, turn knob (either
direction) for desired time delay.
Use the minimum amount of retard
necessary to prevent false alarms.
A “B” setting is usually adequate for
this. Factory set at “B”.

Screw the device into the TEE fitting as shown. Care must be taken
to properly orient the device for the direction of the waterflow.
On sweat TEE's no threaded bushings, inserts or adapters are
permitted unless they comply with the dimensions listed in the chart
Important:
There are 10 paddles below.
furnished with each unit. One Important - The depth to the inside bottom of the TEE should
for each size of threaded,
sweat or plastic TEE as CAUTION:
described in Fig. 2. These TO PREVENT LEAKAGE APPLY TEFLON TAPE
SEALANT TO MALE THREADS ONLY. DO NOT USE ANY APPROXIMATE DEPTH REQUIREMENT
paddles have raised lettering OTHER TYPE OF LUBRICANT OR SEALANT.
that shows the pipe size and TEE SIZE THREADED SWEAT CTS, POLYBUTYLENE CPVC
type of TEE that they are to be
used with. The proper paddle APPROX. RETARD SETTINGS (IN SEC.) 1" x 1" x 1" 2 1/16" 1 3/4" N/A 2 7/16"
must be used. The paddle 0 A B C D E 1 1/4" x 1 1/4" x 1" 2 7/16" 2 7/16" N/A N/A
must be properly attached (see 0 10-25 20-40 35-55 50-70 60-90 1 1/2" x 1 1/2" x 1" 2 11/16" 2 1/4" 2 1/2" N/A
drawing) and the screw that 2" x 2" x1" 3 3/16" 2 3/4" N/A N/A
holds the paddle must be
securely tightened.
SWITCH TERMINAL CONNECTIONS
CLAMPING PLATE TERMINAL
FIG. 3 CAUTION:
An uninsulated section of a single conductor should not be looped around the
terminal and serve as two separate connections. The wire must be severed,
thereby providing supervision of the connection in the event that the wire
becomes dislodged from under the terminal.

FIG. 4 TYPICAL ELECTRICAL CONNECTIONS

NOTE: FOR SUPERVISED CIRCUITS SEE


“SWITCH TERMINAL CONNECTIONS” DRAWING
AND CAUTION NOTE (FIG. 3).

NOTE: The Model VSR-SF has two switches, one can be used to operate a central station, proprietary or remote signaling unit,
while the other is used to operate a local audible or visual annunciator.
TESTING: The frequency of inspection and testing for the model VSR-SF and its associated protective monitoring system should
be in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends
quarterly or more frequently).

PRINTED IN USA MKT. #8800003 - REV N PAGE 2 OF 2


MFG. #5400802 - 7/97
VS-SP
VANE TYPE WATERFLOW
ALARM SWITCH - SMALL PIPE
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • St. Louis, MO 63146-4161 55 Glen Cameron Road
(314) 878-4321 • (800) 325-3936 Thornhill, Ontario, Canada L3T 1P2
www.pottersignal.com (905) 882-1833

UL, ULC, CSFM and NYBSA Listed


Service Pressure: Up to 250 PSI
Minumum Flow Rate for Alarm: 10 GPM
Maximum Surge: 18 FPS
Enclosure: Die-cast, red enamel finish
Cover held in place with tamper resistant screws
Contacts: One set of SPDT (Form C), standard
Second set optional, see below:
15 Amps at 125/250VAC
0.5 Amps at 125VDC
0.25 Amps at 250VDC
2.5 Amps at 30 VDC resistive
Conduit Entrance: One opening for 1/2" conduit
Usage: Listed plastic, copper and schedule 40 iron pipe
For pipe sizes - 1", 1-1/4", 1-1/2", and 2"
Note: 10 paddles are furnished with each unit, one
for each pipe size of threaded and sweat TEE's, one
for 1" CPVC, and one for 1-1/2" polybutylene.
(CTS-Copper Tubing Size).
Environmental Specifications:
• Suitable for indoor or outdoor use with factory installed
gasket and die-cast housing.
• NEMA 4/IP55 rated enclosure - use with appropriate conduit
fitting.
• Temperature range: 40°F to 120°F (4.5°C to 49°C)
Caution: This device is not intended for applications in
explosive environments.
Service Use:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
STOCK NO. 1111100 Residential occupancy up to four stories NFPA-13R
U.S. Patent No. 3921989, Canadian Patent No. 1009680 National Fire Alarm Code NFPA-72
Other Patents Pending Optional : Extra Contacts Switch Kit, Stock No. 0090013
Cover Tamper Switch Kit, Stock No. 5420220

The Model VS-SP is a vane type waterflow switch for use on installation. Screw the device into the TEE fitting as shown in
wet sprinkler systems. These devices may be used as Fig. 2. Care must be taken to properly orient the device for the
sectional flow indicators on large sprinkler systems and on direction of waterflow.
smaller sprinkler systems such as mobile homes and
The vane must not rub the inside of the TEE or bind in any
residential dwellings.
way. The stem should move freely when operated by hand.
INSTALLATION: These devices may be mounted in horizontal
TESTING: Check the operation of the unit by opening the
or vertical pipe. On horizontal pipe they should be installed on
inspector’s test valve at the end of the sprinkler line, or the
the top side of the pipe where they will be accessible. The units
drain and test connection if a test valve is not provided.
should not be installed within 6" of a valve, drain or fitting which
changes the direction of the water flow. If there are no provisions for testing the operation of the flow
detection device on the system, application of the VS–SP is
The unit has a 1" NPT bushing for threading into a non-
not recommended or advisable.
corrosive TEE. See Fig. 2 for proper TEE size, type and

PRINTED IN USA MKT. #8800004 - REV K PAGE 1 OF 2


MFG. #5400769 - 7/97
VS-SP
VANE TYPE WATERFLOW
ALARM SWITCH - SMALL PIPE

FIG. 1 FIG. 2

Screw the device into the TEE fitting as shown. Care must be taken
to properly orient the device for the direction of the waterflow.
On sweat TEE's no threaded bushings, inserts or adapters are
Important: permitted unless they comply with the dimensions listed in the chart
There are 10 paddles furnished below.
with each unit. One for each
Important - The depth to the inside bottom of the TEE should have
size of threaded, sweat or
plastic TEE as described in Fig. the following dimensions:
2. These paddles have raised
lettering that shows the pipe APPROXIMATE DEPTH REQUIREMENT
size and type of TEE that they
are to be used with. The TEE SIZE THREADED SWEAT CTS, POLYBUTYLENE CPVC
proper paddle must be used.
The paddle must be properly 1" x 1" x 1" 2 1/16" 1 3/4" N/A 2 7/16"
attached (see drawing) and the 1 1/4" x 1 1/4" x 1" 2 7/16" 2 7/16" N/A N/A
screw that holds the paddle 1 1/2" x 1 1/2" x 1" 2 11/16" 2 1/4" 2 1/2" N/A
must be securely tightened. 2" x 2" x1" 3 3/16" 2 3/4" N/A N/A

SWITCH INFORMATION TYPICAL CONTROL PANEL SWITCH TERMINAL CONNECTIONS


CONNECTIONS CLAMPING PLATE TERMINAL

CAUTION:
An uninsulated section of a single conductor should
not be looped around the terminal and serve as two
separate connections. The wire must be severed,
thereby providing supervision of the connection in
the event that the wire becomes dislodged from
under the terminal

NOTE: The Model VS-SP has one SPDT switch. An optional second switch is available if required. For example, one switch would
connect to an annunciator panel, and the optional switch could be used to operate a local bell. Order Switch Kit No. 0090013.

TESTING
The frequency of inspection and testing for the Model VS-SP and its associated protective monitoring system should be in accordance with
applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).

PRINTED IN USA MKT. #8800004 - REV K PAGE 2 OF 2


MFG. #5400769 - 7/97
VSR-CF
VANE TYPE WATERFLOW
SWITCH WITH RETARD
FOR COPPER OR PLASTIC PIPE
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • St. Louis, MO 63146-4161 55 Glen Cameron Road
(314) 878-4321 • (800) 325-3936 Thornhill, Ontario, Canada L3T 1P2
www.pottersignal.com (905) 882-1833

UL, CSFM and NYBSA LISTED


Service Pressure : Up to 175 PSI
Minimum Flow Rate for Alarm: 10 GPM
Maximum Surge: 18 FPS
Contact Ratings: Two sets of SPDT (Form C)
15.0 Amps at 125/250 VAC
2.0 Amps at 30 VDC resistive
Environmental Specifications:
• Suitable for indoor or outdoor use with factory installed
gasket and die-cast housing.
• NEMA 4/IP55 rated enclosure - use with appropriate conduit
fitting
• Temperature range: 40° F to 120° F (4.5° C to 49° C)
• Non-corrosive sleeve factory installed in saddle
Conduit Entrances: Two knockouts provided for 1/2" conduit
Caution: This device is not intended for applications in
explosive environments.
Sizes Available:
2", 2 1/2", 3" and 4" for type K, L and M copper pipe
2", 2 1/2" and 3" for listed CPVC pipe, SDR 13.5
PIPE SECTION SHOWN
(Standard Dimensional Ratio)
FOR ILLUSTRATION
PURPOSES ONLY Service Use:
Automatic Sprinkler NFPA-13
U.S. Patent No. 3921989, Canadian Patent No. 1009680 One or two family dwelling NFPA-13D
Other Patents Pending, Residential occupancy up to four stories NFPA-13R
Potter Electric, Rd., 1990 National Fire Alarm Code NFPA-72
Optional: Cover Tamper Switch Kit, Stock No. 0090018

GENERAL INFORMATION INSTALLATION: See Fig. 2.


The Model VSR-CF is a vane type waterflow switch for use on These devices may be mounted on horizontal or vertical pipe.
wet sprinkler systems. It is UL Listed for use on type K, L On horizontal pipe they should be installed on the top side of
and M copper pipe, sizes 2" thru 4" and listed CPVC pipe, the pipe where they will be accessible. The units should not
SDR 13.5 (standard dimensional ratio), sizes 2" thru 3". be installed within 6" of a fitting which changes the direction
of the water flow or within 24" of a valve or drain.
The unit may also be used as a sectional waterflow detector
on large systems. Drain the system and drill a hole in the pipe using a circular
saw in a slow speed drill. The 2" and 2 1/2" devices require a
The unit contains two single pole, double throw, snap action
hole with a diameter of 1 1/4" ±1/16". All other sizes require
switches and an adjustable pneumatic retard. The switches
a hole with a diameter of 2" +1/16", -1/8".
are actuated when a flow of 10 gallons per minute or more
occurs downstream of the device. The flow condition must Clean the inside of the pipe of all growth or other material for
exist for a period of time necessary to overcome the selected a distance equal to the pipe diameter on either side of the
retard period. hole.
ENCLOSURE: The unit is enclosed in a general purpose, Roll the vane so that it may be inserted into the hole; do not
die-cast housing. The cover is held in place with two tamper bend or crease it. Insert the vanes so that the arrow on the
resistant screws which require a special key for removal. A saddle points in the direction of the water flow. Install the
field installable cover tamper switch is available as an option saddle strap and tighten nuts alternately to an eventual
which may be used to indicate unauthorized removal of the 100 in-lbs. of torque, see Fig. 2. The vane must not rub the
cover. See bulletin no. 5400775 for installation instructions of inside of the pipe or bind in any way.
this switch.

PRINTED IN USA MKT #8800002 - REV M PAGE 1 OF 2


MFG. #5400771 - 2/97
VSR-CF
VANE TYPE WATERFLOW
SWITCH WITH RETARD
FOR COPPER OR PLASTIC PIPE

FIG. 1 FIG. 2
SWITCH TERMINAL CONNECTIONS
CLAMPING PLATE TERMINAL

CAUTION:
An uninsulated section of a single
conductor should not be looped around
the terminal and serve as two separate
connections. The wire must be severed,
thereby providing supervision of the
connection in the event that the wire
becomes dislodged from under the
terminal.

FIG. 3 TYPICAL ELECTRICAL CONNECTIONS

Note: For supervised circuits see


“Switch Terminal Connections”
drawing and caution note (Fig. 1).

NOTE: The Model VSR-CF has two switches, one can be used to operate a central station, proprietary or remote
signaling unit, while the other contact is used to operate a local audible or visual annunciator.

TESTING
The frequency of inspection and testing for the model If there are no provisions for testing the operation of the
VSR-CF and its associated protective monitoring system flow detection device on the system, application of the
should be in accordance with applicable NFPA Codes VSR-CF is not recommended or advisable.
and Standards and/or the authority having jurisdiction
(manufacturer recommends quarterly or more frequent- A minimum flow of 10 gpm is required to activate this
ly). device.

If provided, the inspector’s test valve, that is usually IMPORTANT NOTICE: Please advise the person
located at the end of the most remote branch line, responsible for testing of the fire protection system that
should always be used for test purposes. this system must be tested in accordance with the
testing instructions.

PRINTED IN USA MKT #8800002 - REV M PAGE 2 OF 2


MFG. #5400771 - 2/97
VSR-F 10"
VANE TYPE WATERFLOW
ALARM SWITCH WITH RETARD
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • P.O. Box 28480 55 Glen Cameron Road
St. Louis, MO 63146-4161 Thornhill, Ontario, Canada L3T 1P2
(314) 878-4321 • (800) 325-3936 (905) 882-1833

UL Listed
Service Pressure: Up to 300 PSI
Minimum Flow Rate for Alarm: 10 GPM
Maximum Surge: 18 FPS
Contact Ratings: Two sets of SPDT (Form C)
15.00 Amps at 125/250VAC
2.00 Amps at 30VDC Resistive
Conduit Entrances: Two knockouts provided for 1/2" conduit
Environmental Specifications:
• Suitable for indoor or outdoor use with factory installed
gasket and die-cast housing.
• NEMA 4 Rated Enclosure - use with appropriate conduit
fitting
• Temperature Range: 40°F/120°F, 4.5°C/49°C
Pipe Schedules: 10 thru 40
Caution: This device is not intended for applications in
explosive environments.
Service Use:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
U.S. PAT. NO. 3921989 Residential occupancies up to four stories NFPA-13R
CANADIAN PAT. NO. 1009680 National Fire Alarm Code NFPA-72
OTHER PATENTS PENDING Optional: Cover tamper switch kit, Order Stock No. 0090018
POTTER ELECTRIC, Rd., 1990

GENERAL INFORMATION
The Model VSR-F 10" is a vane type waterflow switch for use INSTALLATION (See Fig. 2)
on wet sprinkler systems These devices may be mounted on horizontal or vertical pipe.
On horizontal pipe they should be installed on the top side of
The unit contains two single pole, double throw, snap action the pipe where they will be accessible. The units should not
switches and an adjustable, instantly recycling pneumatic be installed within 6" of a fitting which changes the direction
retard. The switches are actuated when a flow of 10 gallons of the waterflow or within 24" of a valve or drain.
per minute or more occurs downstream of the device. The
flow condition must exist for a period of time necessary to Drain the system and drill a hole with a diameter of 2" ± 1/8"
overcome the selected retard period. in the pipe using a circular saw in a slow speed drill.

ENCLOSURE Clean the inside pipe of all growth or other material for a
The unit is enclosed in a general purpose, die-cast housing. distance equal to the pipe diameter on either side of the hole.
The cover is held in place with two tamper resistant screws
which require a special key for removal. A field installable Roll the vane so that it may be inserted into the hole; do not
cover tamper switch is available as an option which may be bend or crease it. Insert the vane so that the arrow on the
used to indicate unauthorized removal of the cover. See saddle points in the direction of the waterflow. Install the
Bulletin No. 5400775 for installation instructions of this saddle strap and tighten nuts alternately to an eventual 50 ft-
switch. lbs. of torque (see Fig. 2). The vane must not rub the inside
of the pipe or bind in any way.

PRINTED IN USA MKT. #8800007 - REV B PAGE 1 OF 2


MFG. #5401023 - 12/95
VSR-F 10"
VANE TYPE WATERFLOW
ALARM SWITCH WITH RETARD

FIG. 1 FIG. 2
SWITCH TERMINAL CONNECTIONS
CLAMPING PLATE TERMINAL

CAUTION:
An uninsulated section of
a single conductor should
not be looped around the
terminal and serve as two
separate connections.
The wire must be severed,
thereby providing supervi-
sion of the connection in
the event that the wire
becomes dislodged from
under the terminal.

FIG. 3 TYPICAL ELECTRICAL CONNECTIONS

Note: For supervised circuits see


“Switch Terminal Connections”
drawing and caution note (Fig. 1).

NOTE:
The Model VSR-F 10" has two switches, one can be used to operate a central station, proprietary or remote signaling unit, while the
other contact is used to operate a local audible or visual annunciator.

TESTING
The frequency of inspection and testing for the model VSR-F 10" and its associated protective monitoring system should be in
accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends
quarterly or more frequently).
If provided, the inspectors test valve, that is usually located at the end of the most remote branch line, should always be used for
test purposes.
If there are no provisions for testing the operation of the flow detection device on the system, application of the VSR-F 10" is not
recommended or advisable.
A minimum flow of 10 gpm is required to activate this device.
IMPORTANT NOTICE: Please advise the person responsible for testing of the Fire Protection System that this system must be
tested in accordance with the Testing Instructions.

PRINTED IN USA MKT. #8800007 - REV B PAGE 2 OF 2


MFG. #5401023 - 12/95
VSR-FE-2
VANE TYPE WATERFLOW
SWITCH WITH ELECTRONIC RETARD
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • P.O. Box 28480 55 Glen Cameron Road
St. Louis, MO 63146-4161 Thornhill, Ontario, Canada L3T 1P2
(314) 878-4321 • (800) 325-3936 (905) 882-1833
UL LISTED and FM APPROVED
Service Pressure: Up to 450 PSI
Minimum Flow for Alarm: 10 GPM
Maximum Surge: 18 FPS
Power Requirements:
STANDBY: 10 mA at 120VAC or 1.5 mA at 24VAC/DC
ALARM: 40 mA at 120VAC or 35 mA at 24VAC/DC
Contact Ratings:
DPDT (Form C) 2 Amps at 30VDC or 125VAC resistive
Conduit Entrances: Two knockouts provided for 1/2"
conduit
Environmental Specifications:
• Suitable for indoor or outdoor use with factory installed
gasket and die-cast housing.
• NEMA 4 Rated Enclosure - use with appropriate conduit
fitting
• Temperature range: 40°F / 120°F, 4.5°C/49°C
• Non-corrosive sleeve factory installed in saddle.
Caution: This device is not intended for applications in
explosive environments.
Sizes Available: Schedules 10 thru 40, sizes 2" thru 8"
Service Use:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
U.S. PAT. NO. 3921989, CANADIAN PAT. NO. 1009680 Residential occupancy up to four stories NFPA-13R
OTHER PATENTS PENDING, National Fire Alarm Code NFPA-72
POTTER ELECTRIC, Rd., 1990
Optional: Cover Tamper Switch Kit, Stk. No. 0090018

GENERAL INFORMATION: The Model VSR-FE-2 is a vane INSTALLATION: See Fig. 1. These devices may be mounted
type waterflow switch for use on wet sprinkler systems. It is on horizontal or vertical pipe. On horizontal pipe they should
UL Listed and FM Approved for use on steel pipe; schedules be installed on the top side of the pipe where they will be
10 thru 40, sizes 2" thru 8". accessible. The units should not be installed within 6" of a
fitting which changes the direction of the waterflow or within
The unit may also be used as a sectional waterflow detector 24" of a valve or drain.
on large systems.
Drain the system and drill a hole in the pipe using a circular
The unit contains an output relay and an adjustable electronic saw in a slow speed drill. The 2" and 2 1/2" devices require a
retard. The relay is actuated when a flow of 10 gallons per hole with a diameter of 1 1/4" +1/8" -1/16". All other sizes
minute or more occurs downstream of the device. The flow require a hole with a diameter of 2" ± 1/8".
condition must exist for a period of time necessary to over-
come the selected retard period. Clean the inside of the pipe of all growth or other material for a
distance equal to the pipe diameter on either side of the hole.
ENCLOSURE: The unit is enclosed in a general purpose, die-
cast housing. The cover is held in place with two tamper Roll the vane so that it may be inserted into the hole; do not
resistant screws which require a special key for removal. A bend or crease it. Insert the vane so that the arrow on the
field installable cover tamper switch is available as an option saddle points in the direction of the waterflow. Install the
which may be used to indicate unauthorized removal of the saddle strap and tighten nuts alternately to an eventual 50 ft.-
cover. See bulletin no. 5400775 for installation instructions of lbs. of torque (see Fig. 1). The vane must not rub the inside of
this switch. the pipe or bind in any way.

PRINTED IN USA MKT. #8800006 - REV I PAGE 1 OF 2


MFG. #5400985 - 12/95
VSR-FE-2
VANE TYPE WATERFLOW
SWITCH WITH ELECTRONIC RETARD
RETARD ADJUSTMENT FIG. 1
The retard time is selected by turning the
appropriate switches to the off position.
Example: For 45 seconds turn switches 1,
2 and 3 to the off position. TO INSTALL, DRILL A HOLE AS
INDICATED:
Approximate time is as follows:
PIPE SIZE HOLE SIZE
Switch Off Time in Sec.
2" TO 2 1/2" 1 1/4" +1/8" -1/16"
1 thru 8 On 0
1 15 3" TO 8" 2" ± 1/8"

1&2 30
1, 2, & 3 45
1, 2, 3, & 4 60
1, 2, 3, 4, & 5 75
1, 2, 3, 4, 5, & 6 90
7 not used
8 not used

FIG. 2 TYPICAL ELECTRICAL CONNECTIONS

SWITCH TERMINAL CONNECTIONS


CLAMPING PLATE TERMINAL
CAUTION: When supervised circuits are used the following must be ob-
served: An uninsulated section of a single conductor should not be looped
around the terminal and serve as two separate connections. The wire must
be severed, thereby providing supervision of the connection in the event that
the wire becomes dislodged from under the terminal. See drawing at right.

TESTING: The operation of the waterflow switch should be If there are no provisions for testing the operation of the
tested upon completion of installation and periodically there- flow detection device on the system, application of the
after in accordance with the applicable NFPA codes and VSR-FE-2 is not recommended or advisable.
standards and/or the authority having jurisdiction (manufac-
A flow of 10 GPM is required to activate this device.
turer recommends quarterly or more frequently).
IMPORTANT NOTICE: Please advise the person
If provided, the inspector’s test valve, that is usually
responsible for testing of the fire protection system that
located at the end of the most remote branch line, should
this system must be tested in accordance with the
always be used for test purposes.
preceding section.

PRINTED IN USA MKT. #8800006-REV I PAGE 2 OF 2


MFG. #5400985 - 12/95
VSG
LOW FLOW RATE VANE TYPE WATERFLOW
SWITCH WITH ELECTRONIC RETARD
Potter Electric Signal Company Potter Electric Signal & Mfg. LTD.
2081 Craig Road • St. Louis, MO 63146-4161 55 Glen Cameron Road
(314) 878-4321 • (800) 325-3936 Thornhill, Ontario, Canada L3T 1P2
www.pottersignal.com (905) 882-1833
UL LISTED
Germanisher Lloyd Approved No. 97 778-95HH
Service Pressure: Up to 450 PSI
Flow Required for Alarm: 3.0 GPM
Maximum Surge: 18 FPS
Power Requirements:
STANDBY: 10ma at 120V AC or 1.5ma at 24V AC/DC
ALARM: 40ma at 120V AC or 35ma at 24V AC/DC
Contact Ratings: DPDT (Form C)
2 Amps at 0-30VDC or 0-125VAC resistive
Conduit Entrances: 2 knockouts provided for 1/2" conduit
Environmental Specifications:
• Suitable for indoor or outdoor use with factory
installed gasket and die-cast housing.
• NEMA 4 Rated Enclosure - use with appropriate
conduit fitting.
• Temperature Range: 40°F/120°F, 4.5°C/49°C
• Non-corrosive sleeve factory installed in saddle.
Caution: This device is not intended for applications in
explosive environments.
Nominal OD and Wall Thickness:
2" (60.3mm OD), 3.9mm to 4.5mm wall
2 1/2" (73.0mm OD), 4.8mm to 5.2mm wall
2 1/2" (76.1mm OD), 4.3mm to 4.7mm wall
3" (88.9mm OD), 5.0mm to 5.6mm wall
4" (114.3mm OD), 5.4mm to 6.4mm wall
U.S. PAT. NO. 3921989, CANADIAN PAT. NO. 1009680 Service use: Water mist systems where low flow for alarm is
OTHER PATENTS PENDING, required.
POTTER ELECTRIC, Rd., 1990 Optional: Cover Tamper Switch Kit, Stock No. 0090018

GENERAL INFORMATION: The Model VSG is a flexible INSTALLATION: See Fig. 1. These devices may be mounted
vane type of waterflow switch for use in wet pipe water mist on a horizontal or vertical pipe. On horizontal pipe they
systems where a low flow for alarm is required. It is designed should be installed on the top side of the pipe where they will
for installation in sections of 2 to 4 inch stainless steel or be accessible. The units should not be installed within 6" of a
brass pipe with wall thickness in accordance with the above fitting which changes the direction of the waterflow or within
specifications (see “Nominal OD and Wall Thickness”). 24" of a valve or drain.
The unit may also be used as a sectional waterflow detector Drain the system and drill a hole in the pipe using a circular
on large systems. saw in a slow speed drill. The 2" and 2 1/2" devices require a
The unit contains an output relay and an adjustable electronic hole with a of 1 1/4" +1/8" -1/16". The 3" and 4" devices
retard. The relay is actuated when a flow of 3 gallons per require a hole with a diameter of 2" ± 1/8".
minute or more occurs downstream of the device. The flow Clean the inside of the pipe of all growth or other material for
condition must exist for a period of time necessary to a distance equal to the pipe diameter on either side of the
overcome the selected retard period. hole.
ENCLOSURE: The unit is enclosed in a general purpose, Roll the vane so that it may be inserted into the hole; do not
die-cast housing. The cover is held in place with two tamper bend or crease it. Insert the vane so that the arrow on the
resistant screws which require a special key for removal. A saddle points in the direction of the waterflow. Install the
field installable cover tamper switch is available as an option saddle strap and tighten nuts alternately to an eventual 50 ft-
which may be used to indicate unauthorized removal of the lbs. of torque. See Fig. 1. The vane must not rub the inside
cover. See bulletin no. 5400775 for installation instructions of of the pipe or bind in any way.
this switch.

PRINTED IN USA MKT. #8800008 - REV D PAGE 1 OF 2


MFG. #5400999 - 1/98
VSG
LOW FLOW RATE VANE TYPE
WATERFLOW SWITCH WITH ELECTRONIC
RETARD

RETARD ADJUSTMENT FIG. 1


The retard time is selected by
turning the appropriate switches to
the off position. Example: For 45
seconds turn switches 1, 2 and 3
to the off position.
TO INSTALL, DRILL A HOLE AS
Approximate time is as follows: INDICATED:

Switch Off Time in Sec. PIPE SIZE HOLE SIZE


1 thru 8 On 0 2" TO 2 1/2" 1 1/4" +1/8" -1/16"
1 15
3" TO 4" 2" ± 1/8"
1&2 30
1, 2, & 3 45
1, 2, 3, & 4 60
1, 2, 3, 4, & 5 75 DIRECTION OF
WATERFLOW
1, 2, 3, 4, 5, & 6 90
7 not used
8 not used

FIG. 2 TYPICAL ELECTRICAL CONNECTIONS

FIG. 3 SWITCH TERMINAL CONNECTIONS


CLAMPING PLATE TERMINAL

CAUTION:
When supervised circuits are used the following must be observed: An uninsulated
section of a single conductor should not be looped around the terminal and serve as two
separate connections. The wire must be severed, thereby providing supervision of the
connection in the event that the wire becomes dislodged from under the terminal.

TESTING: The operation of the waterflow switch and the associated alarms is to be tested upon completion of the
installation and periodically thereafter in accordance with the applicable NFPA standards and/or the authority having
jurisdiction (manufacturer recommends quarterly or more frequently).

A minimum flow of 3 GPM is required to activate this device.

PRINTED IN USA MKT. #8800008 - REV D PAGE 2 OF 2


MFG. #5400999 - 1/98
MODEL PS10A
PRESSURE SWITCH
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • St. Louis, MO 63146-4161 55 Glen Cameron Road
(314) 878-4321 • (800) 325-3936 Thornhill, Ontario, Canada L3T 1P2
www.pottersignal.com (905) 882-1833

UL and CFSM LISTED, FM and LPC APPROVED,NYMEA ACCEPTED


Dimensions: 4 3/4"W x 2 1/4"D x 4 3/8"H
Enclosure: Cover - Die-cast with textured red powdercoat finish
Base - Plated Steel
Pressure Connection: 1/2" NPT Male
Factory Adjustment: Operates on Pressure increase at 6 ±1 PSI
Operates on Pressure decrease at 5 ±1 PSI
Maximum Differential: 1 PSI
Maximum System Pressure: 250 PSI
Switch Contacts: SPDT (Form C)
15.0 Amps at 125/250VAC, 2.5 Amps at 30VDC
One set in PS10-1A, Two sets in PS10-2A
Environmental Specifications:
Indoor or outdoor use
NEMA 4/IP55 Rated Enclosure
Temperature range: -40°F to 140°F (-40°C to 60°C)
(Not for use in hazardous locations)
Service Use: Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
Residential Occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72
Tamper: Cover incorporates tamper resistant fasteners that require a
special key for removal. One key is supplied with each device. For
PS10-1A Single Switch - Stk. No. 1340101
optional cover tamper switch kit, order Stock No. 0090134.
PS10-2A Double Switch - Stk. No. 1340102

INSTALLATION AND TEST PROCEDURES TESTING: Accomplished by opening the inspector's end-of-line test
The Potter PS10A Series Pressure Actuated Switches are designed valve. Allow time to compensate for system or control retard.
for the detection of a waterflow condition in automatic fire sprinkler CAUTION: Method 2 is not applicable for remote station service use,
systems of particular designs such as wet systems with alarm check if there is an unsupervised shut-off valve between the alarm check
valves or dry pipe systems. They may also be used to provide a low valve and the PS10A.
pressure supervisory signal. They may be adjusted to operate on
pressure between 4 and 20 PSI. WET SYSTEM WITH EXCESS PRESSURE:
Connect PS10A into alarm port piping extending from alarm check
MOUNTING: Device should be mounted in upright position (threaded valve. Retard provisions are not required. Insure that no unsupervised
connection down). Requires NEMA type 4 conduit hub for outdoor shut-off valves are present between the alarm check valve and the
installations. PS10A.
TESTING: The operation of the pressure alarm switch should be TESTING: Accomplished by opening the water by-pass test valve or
tested upon completion of installation and periodically thereafter in the inspector's end-of-line test valve. When using end-of-line test,
accordance with the applicable NFPA codes and standards and/or the allow time for excess pressure to bleed off.
authority having jurisdiction (manufacturer recommends quarterly or
more frequently). DRY SYSTEM:
Connect PS10A into alarm port piping that extends from the intermedi-
WET SYSTEM: ate chamber of the alarm check valve. Install on the outlet side of the
METHOD 1: When using PS10A and control unit with retard - connect in-line check valve of the alarm port piping. Insure that no unsuper-
PS10A into alarm port piping on the input side of retard chamber and vised shut-off valves are present between the alarm check valve and
electrically connect PS10A to control unit that provides a retard to the PS10A.
compensate for surges. Insure that no unsupervised shut-off valves
are present between the alarm check valve and PS10A. TESTING: Accomplished by opening the water by-pass test valve.
METHOD 2: When using the PS10A for local bell application or with a CAUTION: The above tests may also activate any other circuit closer
control that does not provide a retard feature - the PS10A must be or water motor gongs that are present on the system.
installed on the alarm outlet side of the retard chamber of the sprinkler
system.

PRINTED IN USA MKT. #8810001 - REV N PAGE 1 OF 2


MFG. #5400923 - 12/97
MODEL PS10A
PRESSURE SWITCH

DIMENSIONS SWITCH TERMINAL CONNECTIONS


CLAMPING PLATE TERMINAL

CAUTION:
An uninsulated section of a single conductor
should not be looped around the terminal and
serve as two separate connections. The wire
must be severed, thereby providing supervision of
the connection in the event that the wire becomes
dislodged from under the terminal.

TYPICAL SPRINKLER APPLICATIONS

CAUTION: Closing of any shutoff valves between the alarm check valve and the PS10A will render the PS10A inoperative. To comply with
NFPA-72 any such valve shall be electrically supervised with a supervisory switch such as Potter Model BVS.

TYPICAL ELECTRICAL CONNECTIONS PRESSURE SWITCH


TERMINATION

ORDERING INFORMATION
Model Description Stock No.
PS10-1A Pressure switch with one set SPDT contacts 1340101
PS10-2A Pressure switch with two sets SPDT contacts 1340102
Hex Key 5250062
Cover Tamper Switch Kit 0090134
BVS 1/2" Ball Valve with tamper switch 1010150

ENGINEER/ARCHITECT SPECIFICATIONS
Pressure type waterflow switches shall be a Model PS10A as manufactured by Potter Electric Signal Co. of St. Louis, Mo. and
shall be installed on the sprinkler systems as shown on the drawings and/or specified herein.
Switches shall be provided with a 1/2" NPT male pressure connection to be connected into the alarm check valve of a “wet”
sprinkler system or into the intermediate chamber of a “dry” pipe system and shall be actuated by any flow of water to or in excess
of the discharge from one sprinkler head.
Switches shall have a maximum service pressure rating of 250 PSI and shall be factory adjusted to operate on pressure increase
at 6 ±1 PSI. There shall be one (1) or two (2) SPDT contacts rated at 15.0 Amps at 125/250VAC and 2.5 Amps at 30VDC.
The switch housing shall be weather proof and oil resistant. The cover shall incorporate tamper resistant screws.
The unit shall be UL and CSFM Listed, FM and LPC Approved, and NYMEA Accepted.

PRINTED IN USA MKT. #8810001 - REV N PAGE 2 OF 2


MFG. #5400923 - 12/97
MODEL PS40A
HIGH/LOW
PRESSURE SWITCHES
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • St. Louis, MO 63146-4161 55 Glen Cameron Road
(314) 878-4321 • (800) 325-3936 Thornhill, Ontario, Canada L3T 1P2
www.pottersignal.com (905) 882-1833

MODEL PS40A PRESSURE SWITCH FOR MONITORING HIGH UL and CSFM LISTED, FM and LPC APPROVED, NYMEA
AND/OR LOW PRESSURE VARIATIONS ACCEPTED
Dimensions: 4 3/4"W x 2 1/4"D x 4 3/8"H
Enclosure: Cover - Die-cast with textured red powdercoat
finish
Base - Plated Steel
Pressure Connection: 1/2" NPT Male
Factory Adjustment:
PS40-1A: Operates on decrease at 30 PSI
PS40-2A: Operates on increase at 50 PSI, and on
decrease at 30 PSI
Pressure Range: 10 - 175 PSI
Maximum Differential: Approx. 2 lbs. at 20 PSI
5 lbs. at 175 PSI
Maximum System Pressure: 250 PSI
Switch Contacts: SPDT (Form C)
15.0 Amps at 125/250VAC, 2.5 Amps at 30VDC
One set in PS40-1A, Two sets in PS40-2A
Environmental Specifications:
Indoor or outdoor use
NEMA 4/IP55 Rated Enclosure
Temperature range: -40°F to 140°F (-40°C to 60°C)
(Not for use in hazardous locations)
Service Use:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72
Tamper: Cover incorporates tamper resistant fasteners that
require a special key for removal. One key is supplied with
PS40-1A Single Switch - Stk. No.1340401 each device. For optional cover tamper switch kit, order Stock
PS40-2A Double Switch - Stk. No.1340402 No. 0090134.

The Potter PS40A Series are pressure actuated switches Dry System: Connect PS40A in air supply line on the system
designed primarily to detect a 10 PSI increase and/or decrease side of any shutoff or check valve.
from normal system pressure in automatic fire sprinkler
systems. Provision for testing the unit can be accomplished with the
installation of a Potter Bleeder Valve (Model BVL) in the line to
Typical applications are air pressure supervision in dry pipe the PS40A.
systems and pressure supervision of pressure tanks, air supply
or water supply. Testing: The operation of the pressure supervisory switch
should be tested upon completion of installation and periodi-
INSTALLATION AND TEST PROCEDURES cally thereafter in accordance with the applicable NFPA codes
and standards and/or the authority having jurisdiction (manu-
Mounting: Device should be mounted in upright position facturer recommends quarterly or more frequently).
(threaded connection down).
CAUTION: Testing the PS40A may activate other system
Requires NEMA type 4 conduit hub for outdoor installations. connected devices.

PRINTED IN USA MKT. #8810002 - REV M PAGE 1 OF 2


MFG. #5400924 - 12/97
MODEL PS40A
HIGH/LOW
PRESSURE SWITCHES
DIMENSIONS
NOTE:
TO PREVENT LEAKAGE, APPLY TEFLON TAPE SEAL-
ANT TO MALE THREADS ONLY.
WARNING:
USE OF PIPE JOINT CEMENT MAY RESULT IN OBSTRUC-
TION OF APERTURE AND LOSS OF SIGNAL.
FIELD ADJUSTMENTS: The operating point of the switch
(or switches on the PS40-2A) can be adjusted to any
point between 10 and 175 PSI by turning the adjustment
knob(s) clockwise to raise the actuation point, and
counter-clockwise to lower the actuation point. In the
case of the PS40-2A, the two switches operate com-
pletely independently of one another, and each switch
may be adjusted to actuate at any point the system
requires. Final adjustment should be made with a
pressure gauge.

Typical Sprinkler Application - Dry System Pressure Switch Terminations

Typical Electrical Connections

NOTE: Switches are shown in standby condition with “normal”


pressure applied. Switch #1 (high) changes with pressure increase.
Switch #2 (low) changes with pressure decrease.

Ordering Information Switch Terminal Connections Clamping Plate Terminal


Model Description Stk. No. CAUTION:
An uninsulated section of a single
PS40-1A Pressure switch with one set SPDT contacts 1340401 conductor should not be looped
PS40-2A Pressure switch with two sets SPDT contacts 1340402 around the terminal and serve as
BVL Bleeder Valve 1000018 two separate connections. The wire
Hex Key 5250062 must be severed, thereby providing
Cover Tamper Switch 0090134 supervision of the connection in the
event that the wire becomes
BVS 1/2" Ball Valve with tamper switch 1010150
dislodged from under the terminal.

Engineer/Architect Specifications
Air pressure supervisory switch shall be a Model PS40A as manufactured by Potter Electric Signal Co. of St. Louis, Mo. and shall be installed on
the sprinkler systems as shown on the drawings and/or as specified herein.
Switches shall be provided with a 1/2" NPT male pressure connection to be connected into the air supply line on the system side of any shut-off
valve. A Model BVL bleeder valve as supplied by Potter Electric Signal Co. of St. Louis, Mo. or equivalent shall be connected in line with the
PS40A to provide a means of testing the operation of the supervisory switch. (See DWG. #924-1)
The switch unit shall contain SPDT (Form C) switch(es). One switch shall operate at a pressure decrease of 10 PSI from normal. If two
switches are provided, the second switch shall operate at a pressure increase of 10 PSI from normal. Switch contacts shall be rated at 15.0
Amps at 125/250VAC and 2.5 Amps at 30VDC. The units shall have a maximum pressure rating of 250 PSI and shall be adjustable from 10 to
175 PSI.
The switch housing shall be weatherproof and oil resistant. The cover shall incorporate tamper resistant screws.
The unit shall be UL and CSFM Listed, FM and LPC Approved, and NYMEA Accepted.

PRINTED IN USA MKT. #8810002 - REV M PAGE 2 OF 2


MFG. #5400924 - 12/97
MODEL PS100-2A
PRESSURE TYPE FLOW
SWITCHES
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • St. Louis, MO 63146-4161 55 Glen Cameron Road
(314) 878-4321 • (800) 325-3936 Thornhill, Ontario, Canada L3T 1P2
www.pottersignal.com (905) 882-1833

PRESSURE SWITCH FOR MONITORING WET SYSTEMS UL and CSFM LISTED, FM and LPC APPROVED,
WITH EXCESS PRESSURE NYMEA ACCEPTED
Dimensions: 4 3/4"W x 2 1/4"D x 4 3/8"H
Enclosure:
Cover - Die-cast with textured red powdercoat finish
Base - Plated Steel
Pressure Connection: 1/2" NPT Male
Factory Adjustment: Operates on decrease at 90 PSI
Pressure Range: 10 - 175 PSI
Maximum Differential: Approx. 2 lbs. at 20 PSI
5 lbs. at 175 PSI
Maximum System Pressure: 250 PSI
Switch Contacts: Two sets of SPDT (Form C)
15.0 Amps at 125/250VAC
2.5 Amps at 30VDC
Environmental Specifications:
Indoor or Outdoor Use
NEMA 4/IP55 Rated Enclosure
Temperature range: -40°F to 140°F (-40°C to 60°C)
(Not for use in hazardous locations)
Service Use:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72
Tamper: Cover incorporates tamper resistant fasteners that
require a special key for removal. One key is supplied with
PS100-2A Double Switch - Stock No. 1341002 each device. For optional cover tamper switch kit, order Stock
No. 0090134.

The Potter PS100-2A is a pressure actuated switch designed Provision for testing the unit can be accomplished with the
primarily to detect a 10 PSI decrease from normal system installation of a Potter Bleeder Valve (Model BVL) in the line to
pressure in automatic fire sprinkler systems. the PS100-2A.

TYPICAL APPLICATION: Alarm device on systems with Testing: The operation of the pressure supervisory switch
excess pressure should be tested upon completion of installation and periodical-
ly thereafter in accordance with the applicable NFPA codes
INSTALLATION AND TEST PROCEDURES: Device should and standards and/or the authority having jurisdiction (manu-
be mounted in upright position (threaded connection down). facturer recommends quarterly or more frequently).

Requires NEMA type 4 conduit hub for outdoor installations. CAUTION: Testing the PS100-2A may activate other system
connected devices.
WET SYSTEM: (With excess pressure) Connect PS100-2A in
the constant pressure line on the system side of any shut-off
or check valve.

PRINTED IN USA MKT. #8810003 - REV L PAGE 1 OF 2


MFG. #5400925 - 12/97
MODEL PS100-2A
PRESSURE TYPE FLOW
SWITCHES

DIMENSIONS
NOTE:
TO PREVENT LEAKAGE, APPLY TEFLON TAPE
SEALANT TO MALE THREADS ONLY.
WARNING:
USE OF PIPE JOINT CEMENT MAY RESULT IN
OBSTRUCTION OF APERTURE AND LOSS OF
SIGNAL.
FIELD ADJUSTMENTS: The operating point of the switch
(or switches on the PS100-2A) can be adjusted to any
point between 10 and 175 PSI by turning the adjustment
knob(s) clockwise to raise the actuation point, and
counter-clockwise to lower the actuation point. In the case
of the PS100-2A, the two switches operate completely
independently of one another, and each switch may be
adjusted to actuate at any point the system requires. Final
adjustment should be made with a pressure gauge.

Typical Sprinkler Applications Pressure Switch Terminations


Wet System with Excess Pressure

Typical Electrical Connections - Decreasing Pressure

Ordering Information Switch Terminal Connections Clamping Plate Terminal


CAUTION:
Model Description Stock No.
An uninsulated section of a single
PS100-2A Pressure switch 1341002 conductor should not be looped
BVL Bleeder Valve 1000018 around the terminal and serve as two
separate connections. The wire must
Hex Key 5250062 be severed, thereby providing super-
Cover Tamper Switch 0090134 vision of the connection in the event
BVS 1/2" Ball Valve with tamper switch 1010150 that the wire becomes dislodged from
under the terminal.

Engineer/Architect Specifications
Pressure type waterflow switch shall be a Model PS100-2A as manufactured by Potter Electric Signal Co. of St. Louis, Mo. and shall be installed
on the sprinkler systems as shown on the drawings and/or as specified herein.
Switches shall be provided with a 1/2" NPT male pressure connection to be connected into the excess pressure supply line on the system side
of any shut-off valve. A Model BVL Bleeder Valve as supplied by Potter Electric Signal Co. of St. Louis, MO or equivalent shall be connected in
line with the PS100A to provide a means of testing the operation of the pressure type switch.
The switch unit shall contain two SPDT (Form C) switches. Both switches shall operate when the pressure decreases to 90 PSI. The switch
contacts shall be rated at 15.0 Amps at 125/250VAC and 2.5 Amps at 30VDC. The unit shall have a maximum pressure rating of 250 PSI and
shall be adjustable from 10 to 175 PSI.
The switch housing shall be weatherproof and oil resistant. The cover shall incorporate tamper resistant screws.
The unit shall be UL and CSFM Listed, FM and LPC Approved, and NYMEA Accepted.

PRINTED IN USA MKT. #8810003 - REV L PAGE 2 OF 2


MFG. #5400925 - 12/97
MODEL PS120A
HIGH/LOW
PRESSURE SWITCHES
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • St. Louis, MO 63146-4161 55 Glen Cameron Road
(314) 878-4321 • (800) 325-3936 Thornhill, Ontario, Canada L3T 1P2
www.pottersignal.com (905) 882-1833

PRESSURE SWITCH FOR MONITORING HIGH AND/OR UL and CSFM LISTED, FM and LPC APPROVED,
LOW PRESSURE VARIATIONS NYMEA ACCEPTED
Dimensions: 4 3/4"W x 2 1/4"D x 4 3/8"H
Enclosure:
Cover - Die-cast with textured red powdercoat finish
Base - Plated Steel
Pressure Connection: 1/2" NPT Male
Factory Adjustment:
PS120-1A: Operates on decrease at 110 PSI
PS120-2A: Operates on increase at 130 PSI, and on
decrease at 110 PSI
Pressure Range: 10 - 175 PSI
Maximum Differential: Approx. 2 lbs. at 20 PSI
5 lbs. at 175 PSI
Maximum System Pressure: 250 PSI
Switch Contacts: SPDT (Form C)
15.0 Amps at 125/250VAC, 2.5 Amps at 30VDC
One set in PS120-1A, Two sets in PS120-2A
Environmental Specifications:
Indoor or outdoor use
NEMA 4/IP55 Rated Enclosure
Temperature Range: -40°F to 140°F (-40°C to 60°C)
(Not for use in hazardous locations)
Service Use:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72
Tamper: Cover incorporates tamper resistant fasteners that
PS120-1A Single Switch - Stock No. 1341201 require a special key for removal. One key is supplied with
PS120-2A Double Switch - Stock No. 1341202 each device. For optional cover tamper switch kit, order
Stock No. 0090134.

The Potter PS120A Series are pressure actuated switches excess pressure line on the system side of any shut-off or
designed primarily to detect a 10 PSI increase and/or check valve.
decrease from normal system pressure in automatic fire
sprinkler systems. Provision for testing the unit can be accomplished with the
installation of a Potter Bleeder Valve (Model BVL) in the line to
Typical applications are pressure supervision in systems the PS120A.
with excess pressure.
Testing: The operation of the pressure supervisory switch
INSTALLATION AND TEST PROCEDURES should be tested upon completion of installation and periodi-
Mounting: Device should be mounted in upright position cally thereafter in accordance with the applicable NFPA codes
(threaded connection down). and standards and/or the authority having jurisdiction
(manufacturer recommends quarterly or more frequently).
Requires NEMA type 4 conduit hub for outdoor installations.
CAUTION: Testing the PS120A may activate other system
Wet System (with excess pressure): Connect PS120A in the connected devices.

PRINTED IN USA MKT. #8810004 - REV N PAGE 1 OF 2


MFG. #5400926 - 12/97
MODEL PS120A
HIGH/LOW
PRESSURE SWITCHES
DIMENSIONS
NOTE:
TO PREVENT LEAKAGE, APPLY TEFLON TAPE
SEALANT TO MALE THREADS ONLY.
WARNING:
USE OF PIPE JOINT CEMENT MAY RESULT IN
OBSTRUCTION OF APERTURE AND LOSS OF
SIGNAL.
FIELD ADJUSTMENTS: The operating point of the switch
(or switches on the PS120-2A) can be adjusted to any
point between 10 and 175 PSI by turning the adjustment
knob(s) clockwise to raise the actuation point, and
counter-clockwise to lower the actuation point. In the case
of the PS120-2A, the two switches operate completely
independently of one another, and each switch may be
adjusted to actuate at any point the system requires. Final
adjustment should be made with a pressure gauge.

Typical Sprinkler Application Pressure Switch Terminations

Typical Electrical Connections

NOTE: Switches are shown in standby condition with “normal”


pressure applied. Switch #1 (high) changes with pressure
increase. Switch #2 (low) changes with pressure decrease.

Switch Terminal Connections Clamping Plate Terminal


Ordering Information
CAUTION:
Model Description Stock No. An uninsulated section of a single conduc-
PS120-1A Pressure switch with one set SPDT contacts 1341201 tor should not be looped around the termi-
PS120-2A Pressure switch with two sets SPDT contacts 1341202 nal and serve as two separate connec-
BVL Bleeder Valve 1000018 tions. The wire must be severed, thereby
Hex Key 5250062 providing supervision of the connection in
Cover Tamper Switch 0090134 the event that the wire becomes dislodged
BVS 1/2" Ball Valve with tamper switch 1010150 from under the terminal.

Engineer/Architect Specifications
Pressure supervisory switch shall be a Model PS120A as manufactured by Potter Electric Signal Co. of St. Louis, MO and shall be installed on the
sprinkler systems as shown on the drawings and/or as specified herein.
Switches shall be provided with a 1/2" NPT male pressure connection and shall be connected into the excess pressure supply line on the system
side of any shut off valve. A Model BVL Bleeder Valve as supplied by Potter Electric Signal Co. of St. Louis, MO or equivalent shall be connected
in line with the PS120A to provide a means of testing the operation of the supervisory switch.
The switch unit shall contain SPDT (Form C) switch(es). One switch shall operate at a pressure decrease of 10 PSI from normal. If two switches
are provided, the second switch shall operate at a pressure increase of 10 PSI from normal. Switch contacts shall be rated at 15.0 Amps at 125/
250VAC and 2.5 Amps at 30VDC. The unit shall have a maximum pressure rating of 250 PSI and shall be adjustable from 10 to 175 PSI.
The switch housing shall be weatherproof and oil resistant. The cover shall incorporate tamper resistant screws.
The unit shall be UL and CSFM Listed, FM and LPC Approved, and NYMEA Accepted.

PRINTED IN USA MKT. #8810004 - REV N PAGE 2 OF 2


MFG. #5400926 - 12/97
WFSR-F
WATERFLOW ALARM SWITCH
WITH RETARD
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • St. Louis, MO 63146-4161 55 Glen Cameron Road
(314) 878-4321 • (800) 325-3936 Thornhill, Ontario, Canada L3T 1P2
www.pottersignal.com (905) 882-1833

UL and CSFM LISTED, FM APPROVED and NYMEA ACCEPTED


Dimensions: 5 9/16"H x 3 1/2"W x 5 7/8"D
(14.1cm H x 8.9cm W x 14.9cm D)
Weight: 1.5 lbs. (3.3 kg.)
Enclosure: Cover - Die-cast with textured red powdercoat finish
Base - Die-cast aluminum
Pressure Connection: 1/2" Male NPT
Pressure Adjustments: Factory adjusted to operate between 4
and 8 PSI on rising pressure
Maximum system pressure: 175 PSI
Contact Ratings: Two Sets of SPDT (Form C)
15.0 Amps at 125/250VAC
2.0 Amps at 30VDC Resistive
Conduit Entrances: Two knockouts provided for 1/2" conduit
Environmental Specifications: 40°F to 120°F (4.5°C to 49°C)
NEMA 4 Enclosure
Caution: This device is not intended for applications in explosive
environments.
Service Use: Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72
Tamper: Cover incorporates tamper resistant fasteners that require
a special key for removal. One key is supplied with each device.
STOCK NO. 1010080 For optional cover tamper switch kit, order Stock No. 0090018.

WATERFLOW ALARM SWITCH WITH RETARD FOR SUPERVISION


OF WET ALARM CHECK VALVE: The Model WFSR-F is a pressure
FIG. 1 WFSR-F
operated switch with an adjustable, instantly recycling pneumatic retard
to prevent false alarms due to water pressure variation. The WFSR-F
is connected into the alarm port of a wet sprinkler system alarm check
valve (see " WARNING", page 2).
INSTALLATION: A male 1/2" NPT pipe fitting is provided for connec-
tion to the alarm port of the alarm check valve. No additional mounting
or support is required. Allow 5 inches to the front of the unit for
removal of the cover.
TESTING: Operation of the unit is checked by opening the by-pass test
valve or inspector's test valve. The frequency of the inspection and
testing for the Model WFSR-F and its associated protective monitoring
system should be in accordance with applicable NFPA Codes and
Standards and/or authority having jurisdiction (manufacturer recom-
mends quarterly or more frequently).

FIG. 2 TYPICAL ELECTRICAL CONNECTIONS

PRINTED IN USA MKT. #8810009 - REV G PAGE 1 OF 2


MFG. #5400987 - 5/97
WFSR-F
WATERFLOW ALARM SWITCH
WITH RETARD

FIG. 3 FIG. 4
SWITCH TERMINAL CONNECTIONS
Retard Adjustment: CLAMPING PLATE TERMINAL
To change time turn
knob (either direction)
for desired time delay.
Use the minimum
amount of retard neces-
sary to prevent false
alarms, a “B” setting is
usually adequate for CAUTION:
this. Factory set at “B”. An uninsulated section of a single conductor
should not be looped around the terminal and
serve as two separate connections. The wire
must be severed, thereby providing supervision
APPROX. RETARD SETTINGS (IN SEC.)
of the connection in the event that the wire
0 A B C D E becomes dislodged from under the terminal.
0 10-25 20-40 35-55 50-70 60-90

FIG. 5 TYPICAL WET SYSTEM

WARNING
Use teflon tape sealant
only. Apply only to male
threads of connectors.

Use of pipe cement voids


warranty as this material
may obstruct pressure
aperture resulting in loss
of alarm signal.

Device must be installed


before any shut off valve
on alarm port line unless it
is supervised by a
supervisory switch such
as POTTER Model BVS.

The system should be


tested on a quarterly basis
or more frequently to
insure proper operation.

PRINTED IN USA MKT. #8810009 - REV G PAGE 2 OF 2


MFG. #5400987 - 5/97
BVL
LEVER TYPE BLEEDER VALVE

Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • P.O. Box 28480 55 Glen Cameron Road
St. Louis, MO 63146-4161 Thornhill, Ontario, Canada L3T 1P2
(314) 878-4321 • (800) 325-3936 (905) 882-1833

Valve Body: Bronze

Handle: Zinc plated steel

Maximum Pressure: 175 PSI

Connections: 1/2" NPT

Exhaust Orifice: .125"

STOCK NO. 1000018

GENERAL INFORMATION sure actuation of the pressure device, testing


The Model BVL, lever type bleeder valve, is for its operation.
use as a test valve for pressure operated
devices on wet pipe sprinkler systems that INSTALLATION
have excess pressure, or dry pipe sprinkler The BVL should be installed in-line to the
systems. alarm or supervisory device with the “PD”
(Potter Device) stamp, or with the arrow point-
The BVL should be installed in-line with the ing toward the alarm or supervisory device that
pressure device. It provides a convenient is to be tested.
means for removal or testing the pressure
actuated device without affecting the pressure Caution: The BVL should be installed so the
in the system. Closing the valve (moving the exhaust orifice is pointed in a safe direction.
valve handle perpendicular to the 1/2" pipe-
line) shuts off the water or air from the supply
and opens a small orifice (pin-hole) to exhaust
the pressure between the valve and the pres-
sure device. This should provide a low pres-

PRINTED IN USA MKT. #8900067 - REV D PAGE 1 OF 1


MFG. #5400799 - 12/95
PCVS-1, -2
CONTROL VALVE
SUPERVISORY SWITCH
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • St. Louis, MO 63146-4161 55 Glen Cameron Road
(314) 878-4321 • (800) 325-3936 Thornhill, Ontario, Canada L3T 1P2
www.pottersignal.com (905) 882-1833

UL and CSFM LISTED, FM APPROVED, NYMEA ACCEPTED


Dimensions: 4.75"L x 2.25"W x 7.2"H (stem extended)
12.1cm L x 5.7cm W x 18.3cm H

Weight: 1.35 lb. / .61 kg


Enclosure: Cover - Die-cast
Finish - Red Spatter Enamel
Base - Die Cast Zinc
All parts have corrosion resistant finishes

Cover Tamper: Tamper Resistant Screws,


Optional cover tamper kit available

Mounting: 1/2" NPT


Contact Rating: PCVS-1: One set of SPDT (Form C)
PCVS-2: Two sets of SPDT (Form C)
15.00 Amps at 125/250VAC
2.50 Amps at 30VDC resistive

Environmental Limitations: -40°F / +140°F (-40°C to 60°C)


NEMA 4 and NEMA 6P Enclosure (IP67)
Indoor or Outdoor Use (Not for use in hazardous loca-
tions.)
See Bulletin No. 5400694 PIVS-U-EX for hazardous locations.

Conduit Entrances: Two knockouts for 1/2" conduit provided


Service Use:
Automatic Sprinkler NFPA-13
PCVS-1 STOCK NO. 1010107 One or two family dwelling NFPA-13D
PCVS-2 STOCK NO. 1010207 Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72

The Model PCVS is a weather proof and tamper resistant nished with each device and should be left with the
switch for monitoring the open position of fire sprinkler building owner or responsible party. Replacement or
control valves of the post indicator, butterfly and other additional cover screws and hex keys are available. See
types. Depending on the model, one or two SPDT (Form ordering information on page 6.
C) contacts are provided which will operate when the
OPTIONAL COVER TAMPER SWITCH: A field instal-
valve position is altered from an open state.
lable cover tamper switch is available as an option which
The unit mounts in a 1/2" NPT tapped hole in the post may be used to indicate removal of the cover. See
indicator or butterfly valve housing. The device is en- ordering information on page 6.
gaged by the indicating assembly of the post indicator or
TESTING: The PCVS and its associated protective
the operating mechanism of the butterfly valve, actuating
monitoring system should be tested in accordance with
switch(es) when the valve is fully open. The unit should
applicable NFPA codes and standards and/or the authori-
be installed where it is accessible for service.
ty having jurisdiction (manufacturer recommends quarter-
The cover is held in place by two tamper resistant screws ly or more frequently).
that require a special tool to remove. The tool is fur-

PRINTED IN USA MKT. #8820001 - REV K PAGE 1 OF 6


MFG. #5400980 - 2/97
PCVS-1, -2
CONTROL VALVE
SUPERVISORY SWITCH

FIG. 1 DIMENSIONS FIG. 2 PARTS

TYPICAL INSTALLATIONS ON POST INDICATOR VALVE HOUSINGS (SEE FIGS. 3 THRU 6)


Refer to Fig. 2 for the location of parts described in the follow- on the target assembly, on a side adjacent to the “OPEN/
ing instructions. SHUT” plates. Subtract 1/8" from the measurement.

NOTE: If the sprinkler system is in service the owner or If the target moved down as the valve was closed, mea-
authorized representative should be notified, before any work is sure the distance from the bottom of the head to the upper
done on the system, that the valve controlling the water supply portion of the target assembly that will contact the trip rod
to the system may be closed for periods of time during the of the PCVS (see Fig. 4). Add 1/8" to this measurement.
installation and testing of this device, resulting in all or portions
of the system being inoperative during these periods. 4. Mark the housing at the proper location. Using a 23/32"
drill bit, drill and then tap a 1/2" NPT in the housing on the
If the system is not in service and valve is closed, be sure that side that coincides with the portion of the target assembly
opening the valve will not allow any unwanted water flow due to that will engage the trip rod of the PCVS.
openings in the system, such as heads off, broken or incom-
plete piping, etc. (Continued on page 3.)

1. Position the valve to fully open (“OPEN” should appear in


the window of the housing). Partially close the valve while FIG. 3 FIG. 4
observing the direction that the target assembly moves.
Reopen the valve.

If the valve housing is predrilled with a 1/2" NPT for


installation of a monitoring switch, remove the 1/2" plug
and fully open the valve. Make sure that “OPEN” appears
in the window of the housing. GO TO STEP NO. 6.

2. Remove the head and target assembly (consultation with


valve manufacturer is recommended).

3. If the target assembly moved up as the valve was closed,


measure the distance from the bottom of the head to the
lower part of the target assembly that will contact the trip
rod of the PCVS (see Fig. 3). This is usually a plate or bar

PRINTED IN USA MKT. #8820001 - REV K PAGE 2 OF 6


MFG. #5400980 - 2/97
PCVS-1, -2
CONTROL VALVE
SUPERVISORY SWITCH

POST INDICATOR VALVE INSTALLATIONS (CONT.)


5. Replace the head and target assembly. observing which direction the rod will move when the valve
is closed. Orient the device to actuate the switches when
6. Loosen the socket head screw that holds the nipple in the the valve is open. Tighten the socket head screw in the
PCVS and remove the nipple. collar.
7. Screw the locknut that is provided onto the nipple. 14. Carefully open the valve to the fully open position. As the
8. Screw the nipple into the 1/2" NPT hole in the valve target moves to the open position it should engage the trip
housing - hand tighten. Tighten the locknut against the rod and actuate the switch(es). There should be a mini-
valve housing to secure the nipple firmly in place. mum overtravel of 1/2 revolution of the handle/hand wheel
after the switch(es) actuate (a continuity meter connected
9. Insert a scale or probe thru the nipple to measure the to each set of contacts is one method that could be used to
distance from the open end of the nipple to the target determine this).
assembly. Subtract 1/2" from this measurement.
15. Slowly close the valve. The switch must operate during the
NOTE: In some cases, it may be necessary to attach an first two revolutions of the handle/hand wheel or during 1/5
angle bracket to the target assembly to engage the PCVS of the travel distance of the valve control apparatus from its
trip rod. normal condition.
10. Using the special tool provided, loosen the two cover NOTE: Small adjustments of the target position may be
screws and remove the cover from the PCVS. necessary (consultation with valve manufacturer is recom-
mended).
11. Loosen the locking screw that holds the trip rod in place
and adjust the rod length, from the end of the collar to the 16. Complete the required electrical wiring, connections and
end of the rod, using the dimension determined in Step 9. tests. The valve should be operated through the entire
Tighten the locking screw to hold the rod in place. cycle of fully closed and fully open to determine the
integrity of the PCVS installation and the signaling system.
NOTE: If trip rod length is excessive, loosen the locking Check that all electrical and mechanical connections are
screw and remove the trip rod from the trip lever. Using secure.
pliers, break off the one (1) inch long notched section (see
Fig. 7). Reinstall trip rod and repeat Step 11 procedure. 17. When the installation and testing are complete, return
valve to its proper position.
12. Partially close the valve (3 to 4 revolutions of the handle/
hand wheel). 18. Alternative installation for other post indicator valve
housing shown in Fig. 5 and 6.
13. Slide the PCVS unit as far as possible onto the nipple,

FIG. 5 WINDOW INSTALLATION FIG. 6 CLOW VALVE INSTALLATION


Note A - See Fig. 5
Subject to the approval of the “authority having
jurisdiction” the alternate method of installation
shown in Fig. 5 may be used. In this method, one
of the glass windows of the housing is replaced
with a 1/4" thick metal plate that is cut to fit in
place of the glass and drilled and tapped to
receive the 1/2" NPT pipe nipple. In some cases
it may be necessary to attach an angle bracket to
the target assembly to engage the PCVS trip rod.
Note B - See Fig. 6
If the target is stationary and a hood arrangement
is used, such as is shown in Fig. 6, the hood must
be drilled with a 23/32" drill and tapped with a 1/2"
NPT. The center line of this hole should be 1/8"
below the portion of target assembly that strikes
the PCVS trip rod. The 11 3/8" dimension shown
is for a Clow Valve. Flexible conduit must be used
for this type of installation.

PRINTED IN USA MKT. #8820001 - REV K PAGE 3 OF 6


MFG. #5400980 - 2/97
PCVS-1, -2
CONTROL VALVE
SUPERVISORY SWITCH

TYPICAL INSTALLATION ON A BUTTERFLY VALVE (SEE FIGS. 8 AND 9)


B1. Remove the 1/2" NPT plug from the gear operator case. to hold the rod in place. Re-install the device on the
nipple. Tighten the screw in the collar against the nipple.
Refer to Fig. 2 for location of parts described in the
following instructions: NOTE: In some cases it may be necessary to remove the
gear box cover to ensure correct operation (consultation
B2. Loosen the set screw that holds the nipple in the PCVS
with the valve manufacturer is recommended).
and remove the nipple.
B9. Carefully open the valve to its full open position, as the
B3. Screw the locknut that is provided onto the nipple.
boss on the gear hub moves to the open position it must
B4. Screw the nipple into the 1/2" NPT hole in the gear engage the PCVS trip rod and actuate the switch(es).
operator - hand tighten. Tighten the locknut against the There should be a minimum overtravel or revolution of the
case, to secure the nipple firmly in place. crank or hand wheel after the switch(es) actuate (a
continuity meter connected to each set of contacts is one
B5. Partially close the valve (3 or 4 revolutions of the hand method that could be used to determine this).
wheel or crank).
NOTE: Slight adjustment of gear stops may be necessary
B6. Using the special tool provided, loosen the two cover to prevent overtravel of the trip rod (consultation with
screws and remove the cover from the PCVS. valve manufacture is recommended).
B7. Loosen the locking screw that holds the trip rod in place. B10. Carefully close the valve. The switch(es) must operate
Estimate trip rod length required and extend slightly past during the first two revolutions of the crank or hand wheel
that point. Slide the PCVS unit as far as possible onto or during 1/5 of the travel distance of the valve control
the nipple, observing which direction the rod will move apparatus from its normal condition.
when the valve is closed. Orient the device to actuate
switches when valve is open. B11. Complete the required electrical wiring, connections and
tests. The valve should be operated through the entire
NOTE: If trip rod length is excessive, loosen the locking cycle of fully closed and fully open to determine the
screw and remove the trip rod from the trip lever. Using integrity of the PCVS installation and signaling system.
pliers, break off the one (1) inch long notched section
(see Fig. 7). Reinstall trip rod and repeat Step B7 Check that all electrical and mechanical connections are
procedure. secure.
B8. Remove device from nipple and withdraw trip rod 1/32" B12. When the installation and testing are complete, return
(this dimension is important). Tighten the locking screw valve to its proper position.

FIG. 7 BREAKING EXCESSIVE ROD LENGTH

PRINTED IN USA MKT. #8820001 - REV K PAGE 4 OF 6


MFG. #5400980 - 2/97
PCVS-1, -2
CONTROL VALVE
SUPERVISORY SWITCH
ITT GRINNELL/KENNEDY INDICATING BUTTERFLY VALVE DRESSER INDICATING BUTTERFLY VALVE
FIG. 8
FIG. 9

OTHER SELECTED INSTALLATIONS


NOTE: THE APPLICATIONS IN FIGURES 10, 11 AND 12 ARE SUBJECT TO THE APPROVAL OF THE AUTHORITY HAVING JURISDICTION

PBK - PRATT IBV BUTTERFLY VALVE KIT PVK (STOCK NO. 1000060) - PRATT PIVA POST
FIG. 10 FIG. 11 INDICATOR VALVE KIT

MODEL PBK-L MODEL PBK-S


Stock No. 0090132 Stock No. 0090133
(14" and Up) (Up to 12")
Pratt Butterfly Valve Kit as used to mount a PCVS on a Pratt Pratt Valve Kit as used to mount a PCVS on a Pratt Model
Model IBV Valve. PIVA Valve.
Kits contains: Bracket, nuts and instructions Kit contains: Instructions, template, screw and nut.

PRINTED IN USA MKT. #8820001 - REV K PAGE 5 OF 6


MFG. #5400980 - 2/97
PCVS-1, -2
CONTROL VALVE
SUPERVISORY SWITCH

TYPICAL PRESSURE REDUCER TYPE VALVE SWITCH TERMINAL CONNECTIONS


INSTALLATION CLAMPING PLATE TERMINAL
This figure shows the Model PCVS mounted on the valve
FIG. 13
yoke, with a bracket supplied by the valve manufacturer, to
supervise a pressure reducer type valve.

FIG. 12

CAUTION:
An uninsulated section of a single conductor should not be
looped around the terminal and serve as two separate
connections. The wire must be severed, thereby providing
supervision of the connection in the event that the wire
becomes dislodged from under the terminal.

FIG. 14 TYPICAL ELECTRICAL CONNECTIONS (Switches Shown in Valve Open Position)


Please Note: This device should be wired in accordance with the applicable parts of the National Electrical Code, all state and
local codes, applicable NFPA Standards and the requirements of the authority having jurisdiction.

TYPICAL SWITCH ACTION TYPICAL ELECTRICAL CONNECTIONS

Contacts shown in normal (valve open) condition.

ORDERING INFORMATION
MODEL DESCRIPTION STOCK NO.
PCVS-1 Potter Control Valve Switch (single switch) 1010107
PCVS-2 Potter Control Valve Switch (double switch) 1010207
-- Cover Screw 5490293
-- Hex Key for Cover Screws and Installation Adjustments 5250062
PBK-S Pratt Butterfly Valve Kit (Up to 12") 0090133
PBK-L Pratt Butterfly Valve Kit (14" and Up) 0090132
PVK Pratt Valve Kit 1000060
-- Optional Cover Tamper Switch Kit 0090131

For pressure reducer type valve installation kits (if required) contact valve manufacturer.

PRINTED IN USA MKT. #8820001 - REV K PAGE 6 OF 6


MFG. #5400980 - 2/97
OSYSU-1, -2
OUTSIDE SCREW AND YOKE VALVE
SUPERVISORY SWITCH
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • St. Louis, MO 63146-4161 55 Glen Cameron Road
(314) 878-4321 • (800) 325-3936 Thornhill, Ontario, Canada L3T 1P2
www.pottersignal.com (905) 882-1833

UL and CSFM LISTED, FM APPROVED and NYMEA


ACCEPTED
Dimensions: 6.19"L X 2.25"W X 5.88"H
15.7cm L X 5.7cm W X 14.6cm H
Weight: 2 lbs (.9 kg)
Enclosure: Cover - Die-Cast
Finish - Red Spatter Enamel
Base - Die Cast Zinc
All parts have corrosion resistant finishes
Cover Tamper: Tamper resistant screws,
Optional cover tamper kit available.
Contact Ratings:
OSYSU-1: One set of SPDT (Form C)
OSYSU-2: Two sets of SPDT (Form C)
15.00 Amps at 125/250VAC
2.50 Amps at 30VDC resistive
Environmental Limitations:
-40°F to 140°F (-40°C to 60°C)
NEMA 4 and NEMA 6P Enclosure (IP67)
Indoor or outdoor use (Not for use in hazardous
locations.See Bulletin No. 5400705 OSYS-U-EX
for hazardous locations).
Conduit Entrances:
2 knockouts for 1/2" conduit provided
Service Use:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
OSYSU-1 Stock No. 1010106 Residential occupancy up to four stories NFPA-13R
OSYSU-2 Stock No. 1010206 National Fire Alarm Code NFPA-72

GENERAL INFORMATION additional cover screws and hex keys are available. See
The OSYSU is used to monitor the open position of an ordering information on page 4.
OS & Y (outside screw and yoke) type gate valve. This
device is available in two models; the OSYSU-1, contain- OPTIONAL COVER TAMPER SWITCH
ing one set of SPDT (Form C) contacts and the OSYSU- A field installable cover tamper switch is available as an
2, containing two sets of SPDT (Form C) contacts. option which may be used to indicate removal of the
These switches mount conveniently to most OS & Y cover. See ordering information on page 4.
valves ranging in size from 2" to 12". They will mount on
some valves as small as 1/2". TESTING
The OSYSU and its associated protective monitoring
The cover is held in place by two tamper resistant system should be inspected and tested in accordance
screws that require a special tool to remove. The tool is with applicable NFPA codes and standards and/or the
furnished with each device and should be left with the authority having jurisdiction (manufacturer recommends
building owner or responsible party. Replacement or quarterly or more frequently).

PRINTED IN USA MKT. #8820004 - REV J PAGE 1 OF 4


MFG. #5400979 - 2/97
OSYSU-1, -2
OUTSIDE SCREW AND YOKE VALVE
SUPERVISORY SWITCH

FIG. 1 SMALL VALVE INSTALLATION - 1/2" THRU 2 1/2" SIZES


THESE SWITCHES MOUNT CONVENIENTLY TO MOST 2" TO 12" OS & Y VALVES. THEY WILL MOUNT ON SOME
VALVES AS SMALL AS 1/2". J-HOOKS MAY BE REQUIRED ON VALVES WITH LIMITED CLEARANCE.

SMALL VALVE INSTALLATION


1. Remove and discard "C" washer and roller from the trip 6. Remove the OSYSU. File a 1/8" deep groove centered on
rod. the mark on the valve stem utilizing a 3/16" diameter
straight file. Round and smooth the edges of the groove to
2. With the valve in the FULL OPEN position, locate the prevent damage to the valve packing and to allow the trip
OSYSU across the valve yoke as far as possible from the rod to move easily in and out of the groove as the valve is
valve gland, so that the trip rod lays against the non- operated.
threaded portion of the valve stem.
7. Mount the OSYSU with the trip rod centered in groove.
3. Loosen the locking screw that holds the trip rod in place
and adjust the rod length (see Fig. 4). When adjusted 8. Final adjustment is made by loosening 2 screws (see Fig.
properly, the rod should extend past the valve screw, but 1) and sliding the OSYSU on the bracket. Adjustment is
not so far that it contacts the clamp bar. Tighten the correct when switches are not activated with the trip rod
locking screw to hold the trip rod in place. seated in the valve stem groove and that the switches
activate when the trip rod moves out of the groove.
NOTE: If trip rod length is excessive, loosen the locking
screw and remove the trip rod from the trip lever. Using 9. Tighten the adjustment screws and all mounting hardware.
pliers, break off the one (1) inch long notched section (see Check to insure that the rod moves out of the groove easily
Fig. 5). Reinstall trip rod and repeat Step 3 procedure. and that the switches activate within one turn when the
valve is operated from the FULL OPEN towards the
4. Mount the OSYSU loosely with the carriage bolts and CLOSED position.
clamp bar supplied. On valves with limited clearance use
J-hooks supplied instead of the carriage bolts and clamp NOTE: CLOSE THE VALVE FULLY TO DETERMINE THAT
bar to mount the OSYSU. THE STEM THREADS DO NOT ACTIVATE THE SWITCH.
THE SWITCH BEING ACTIVATED BY THE STEM THREADS
5. Mark the valve stem at the center of the trip rod. COULD RESULT IN A FALSE VALVE OPEN INDICATION.

PRINTED IN USA MKT. #8820004 - REV J PAGE 2 OF 4


MFG. #5400979 - 2/97
OSYSU-1, -2
OUTSIDE SCREW AND YOKE VALVE
SUPERVISORY SWITCH

FIG. 2 LARGE VALVE INSTALLATION - 3" THRU 12" SIZES

LARGE VALVE INSTALLATION


1. With the valve in the FULL OPEN position, locate the damage to the valve packing and to allow the trip rod to
OSYSU across the valve yoke as far as possible from the move easily in and out of the groove as the valve is
valve gland, so that the trip rod lays against the non- operated.
threaded portion of the valve stem.
6. Mount the OSYSU loosely with the trip rod centered in
2. Mount the OSYSU loosely with the carriage bolts and groove.
clamp bar supplied.
7. Final adjustment is made by loosening 2 screws (see Fig. 2)
3. Loosen the locking screw that holds the trip rod in place and sliding the OSYSU on the bracket. Adjustment is
and adjust the rod length (see Fig. 4). When adjusted correct when switches are not activated with the trip rod
properly, the rod should extend past the valve screw, but seated in the valve stem groove and that the switches
not so far that it contacts the clamp bar. Tighten the activate within one turn when the valve is operated from the
locking screw to hold the trip rod in place. FULL OPEN towards the CLOSED position.
NOTE: If trip rod length is excessive, loosen the locking 8. Tighten the adjustment screws and mounting hardware.
screw and remove the trip rod from the trip lever. Using Check to insure that the rod moves out of the groove easily
pliers, break off the one (1) inch long notched section (see and that the switches activate within one turn when the
Fig. 5). Reinstall trip rod and repeat Step 3 procedure. valve is operated from the FULL OPEN towards the
CLOSED position.
4. Mark the valve stem at the center of the trip rod.
NOTE: CLOSE THE VALVE FULLY TO DETERMINE THAT
5. Remove the OSYSU. File a 1/8" deep groove centered on THE STEM THREADS DO NOT ACTIVATE THE SWITCH.
the mark of the valve stem utilizing a 3/8" diameter straight THE SWITCH BEING ACTIVATED BY THE STEM THREADS
file. Round and smooth the edges of the groove to prevent COULD RESULT IN A FALSE VALVE OPEN INDICATION.

PRINTED IN USA MKT. #8820004 - REV J PAGE 3 OF 4


MFG. #5400979 - 2/97
OSYSU-1, -2
OUTSIDE SCREW AND YOKE VALVE
SUPERVISORY SWITCH

FIG. 3 DIMENSIONS FIG. 4 PARTS

BREAKING EXCESSIVE ROD SWITCH TERMINAL TYPICAL ELECTRICAL CONNECTIONS


LENGTH CONNECTIONS
CLAMPING PLATE
FIG. 5 TERMINAL

CAUTION:
An uninsulated section of a single conductor Contacts shown in normal (valve open) condition.
should not be looped around the terminal and
serve as two separate connections. The wire
must be severed, thereby providing supervision TYPICAL SWITCH ACTION
of the connection in the event that the wire
becomes dislodged from under the terminal.

ORDERING INFORMATION
MODEL DESCRIPTION STOCK NO.
OSYSU-1 Outside Screw & Yoke-Supervisory Switch (Single switch) 1010106
OSYSU-2 Outside Screw & Yoke-Supervisory Switch (Double switch) 1010206
-- Cover Screw 5490293
-- Hex Key for Cover Screws and Installation Adjustments 5250062
-- Optional Cover Tamper Switch Kit 0090131
For pressure reducer type valve installation kits (if required) contact valve manufacturer.

PRINTED IN USA MKT. #8820004 - REV J PAGE 4 OF 4


MFG. #5400979 - 2/97
BVS-1/2"
BALL VALVE WITH
SUPERVISORY SWITCH
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • St. Louis, MO 63146-4161 55 Glen Cameron Road
(314) 878-4321 • (800) 325-3936 Thornhill, Ontario, Canada L3T 1P2
www.pottersignal.com (905) 882-1833

UL Listed

Dimensions: 4.8"L x 2.6"W x 5.5"H


12.0cm L x 6.6cm W x 14.0cm H
Weight: 2.25lbs (1.0kg)
Enclosure: Die-cast zinc, red enamel finish
(All parts plated to resist corrosion)
Conduit Entrance: One opening for non-threaded
1/2" conduit provided
Contact Ratings:Two sets of SPDT (Form C)
15.0 Amps at 125/250VAC
2.50 Amps at 30VDC resistive
Environmental Specifications:
• Indoor or outdoor use
• Temperature range: 40°F/140°F (4.5°C/60°C)
• NEMA 4 rated enclosure
• Not for use in hazardous locations
Maximum Pressure: 175 PSI
BVS-1/2" Stock No. 1010150 Pipe Connection: 1/2" Female NPT
Service Use:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72
Cover Tamper:
Tamper resistant screws standard. For optional
cover tamper switch kit, order Stock No. 0090140

GENERAL INFORMATION

The BVS utilizes a 1/2" ball valve in conjunction with a state.


switch assembly. The switch assembly is enclosed in a The cover is held in place by two tamper resistant
tamper resistant NEMA 4 enclosure. The switch screws that require a special tool to remove. The tool is
assembly monitors the fully open position of the valve. furnished with each device and should be left with the
Two sets of SPDT contacts are provided which will building owner or responsible party. Replacement or
operate when the valve position is altered from an open additional cover screws and hex keys are available.

PRINTED IN USA MKT. #8820014 - REV C PAGE 1 OF 2


MFG. #5401021 - 6/97
BVS-1/2"
BALL VALVE WITH
SUPERVISORY SWITCH

INSTALLATION

The BVS-1/2" is intended to be installed in the 1/2" alarm trim


line of a wet or dry fire sprinkler system. (It serves as an
electrically supervised shut-off valve to allow for maintenance
or service on alarm attachments, without closing the sprinkler
supply valve.)

For retrofit installations, it is necessary to remove the existing


shut-off valve and replace it with the BVS-1/2".

SWITCH TERMINAL CONNECTIONS


CLAMPING PLATE TERMINAL

CAUTION:
An uninsulated section of a single conductor should not be looped around the terminal and
serve as two separate connections. The wire must be severed, thereby providing supervision
of the connection in the event that the wire becomes dislodged from under the terminal.

TYPICAL SPRINKLER APPLICATIONS

TYPICAL ELECTRICAL CONNECTIONS

TESTING
The BVS-1/2" and its associated protective monitoring system should be inspected and tested in accordance with the
applicable NFPA codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly
or more frequently).

PRINTED IN USA MKT. #8820014 - REV C PAGE 2 OF 2


MFG. #5401021 - 6/97
PTS-B
PLUG TYPE
SUPERVISORY SWITCH
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • P.O. Box 28480 55 Glen Cameron Road
St. Louis, MO 63146-4161 Thornhill, Ontario, Canada L3T 1P2
(314) 878-4321 • (800) 325-3936 (905) 882-1833

UL AND ULC LISTED AND FM APPROVED


Dimensions: 5.25"L x 2.63"W x 2"D
13.3cm L x 6.7cm W x 5.1cm D
with Bracket 8" L (20.3cm)
Weight: 2 lbs. (.91 kg.)
Enclosure: Cast Aluminum
Finish: Red Wrinkle Enamel
Tamper: Activated by Cover Removal
Electrical Ratings: 250 mA at 28VDC/AC
Stk. No. 1010095
U.S. Patent No. 4234879 Cable: 2-wire, 18 Ga. Waterproof - Approx. 8' long

GENERAL INSTALLATION
The Model PTS-B is designed to supervise sprinkler system The receptacle housing is mounted near the valve. With the
control valves. This unit is particularly useful for unusual valve in the full OPEN position, the approximate 8' of water-
conditions, such as non-rising stem valves. proof wire provided, can be cut to the desired length and
looped through the valve wheel and terminated in the plug.
Turning the valve wheel will pull the plug out of the receptacle.
The plug cannot be reinserted after operation until the cover is
This forms a normally closed single circuit loop when the plug
removed with special key provided. Cover tamper is provided.
is inserted into the receptacle.
CONTACTS: SPST normally closed when plug is in recep-
tacle. Contacts rated 250 mA 28 VDC/VAC. The cover tamper switch can be series wired into this loop or
can be wired into a separate normally closed protection circuit
The PTS-B is NOT available with normally open contacts. (see wiring diagrams).

WARNING
As stipulated by FACTORY MUTUAL and UNDERWRITER'S LABORATORIES
This unit is not intended or designed for ordinary use. It is a special application device to be used for unusual conditions such as non-rising
stem gate valves where no other approved or listed method of protection is available or practical. As this unit does not meet NFPA codes and
standards, requiring restoration signal when the valve is positioned to normal, special attention should be given by the responsible parties to
assure that the proper operation of this device is maintained. This device should only be restored to normal when the valve is in the normal
condition.

COVER TAMPER IN SERIES WITH PROTECTIVE CIRCUIT SEPARATE COVER TAMPER CIRCUIT

PRINTED IN USA MKT. #8820007 - REV D PAGE 1 OF 1


MFG. #5400701 - 12/95
PMS
MAGNETIC PLUG TYPE
SUPERVISORY SWITCH
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • P.O. Box 28480 55 Glen Cameron Road
St. Louis, MO 63146-4161 Thornhill, Ontario, Canada L3T 1P2
(314) 878-4321 • (800) 325-3936 (905) 882-1833

UL and ULC LISTED and FM APPROVED


Dimensions: 9"L x 4"W x 2"D
22.9cm L x 10.2cm W x 5.1cm D
Weight: 3 lbs. (1.35 kg.)
Enclosure: Cover - Stainless Steel and Aluminum
Base - Die Cast Aluminum
Finish - Red Spatter Enamel
Contact Rating: One set (form C) SPDT contacts
STK. NO. 1010007
0.1 Amp at 120VDC

The Model PMS magnetic plug switch is designed to supervise sprinkler system control valves. This unit is particularly
useful on non-rising stem valves.
The unit consists of a glass magnetic reed switch sealed in a stainless steel tube, a condulet fitting for connection of
the external circuit to the cable that is connected to the switch, and a condulet fitting that houses the magnet and
serves as a receptacle for the stainless steel tube.

INSTALLATION: OPERATION:
The bracket holding the two condulet fittings is mounted When the valve wheel is turned, the encased switch will
on the wall near the valve, in such a manner that when pull out of its receptacle, and away from the magnet, and
the cable is fed thru the valve wheel and the tube is the switch contacts will transfer. A key that is provided
inserted into its receptacle, turning the wheel will cause must be inserted in the keyhole in the receptacle cover
the tube to pull straight out of its receptacle. and turned before the tube can be re-inserted.
FIG. 1 CONTACT CONDITIONS FIG. 2 TYPICAL ELECTRICAL CONNECTIONS

WARNING
As stipulated by FACTORY MUTUAL and UNDERWRITERS LABORATORIES
This unit is not intended or designed for ordinary use. It is a special application device to be used for unusual conditions such as non-rising
stem gate valves where no other approved method of protection is available or practical. As this unit does not meet NFPA standards,
requiring restoration signal when the valve is positioned to normal, special attention should be given by the responsible parties to assure that
the proper operation of this device is maintained. This device should only be restored to normal when the valve is in the normal condition.

PRINTED IN USA MKT. #8820010 - REV F PAGE 1 OF 1


MFG. #5400614 - 1/96
WLS
TANK WATER LEVEL SWITCH
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • St. Louis, MO 63146-4161 55 Glen Cameron Road
(314) 878-4321 • (800) 325-3936 Thornhill, Ontario, Canada L3T 1P2
www.pottersignal.com (905) 882-1833

UL Listed
Dimensions:Housing - 5.56"H x 3.50"W x 2.56"D
14.1cm H x 8.9cm W x 6.5cm D
Weight: 11.0 lb / 4.95 kg
Enclosure: Cast aluminum with red enamel finish
Applications: Steel or wood tanks
(With the optional wood bushing adapter,
Stock No. 5180199)
Contacts: Two sets SPDT (Form C)
One set for high / One set for low
Rated - 15.00 Amps at 125/250VAC
0.50 Amp at 125VDC
0.25 Amp at 250VDC
Detection Range: Before 3" Rise /Before 3" Fall
Environmental Specifications:
• Suitable for indoor or outdoor use
STOCK NO. 1010117 • Temperature range: 40°F to 140°F (4.5°C to 60°C)
• NEMA 4 rated enclosure
Maximum Pressure: 175 PSI

The Model WLS Water Level Switch is a float operated existing 2" steel flanges. An optional bushing adapter
device for supervising water level in a sprinkler supply with a buttress thread is available for mounting in wooden
gravity or pressure tank. tanks.

The Model WLS has a bushing with 1 1/2" American The unit is capable of detecting the level of water before a
Standard Pipe Threads for mounting in steel tanks. A 1 1/ 3" rise and/or a 3" fall in the water level in a pressure tank,
2" x 2" adapter bushing is available for mounting in as required.

FIG. 1

PRINTED IN USA MKT. #8820016 - REV A PAGE 1 OF 2


MFG. #5401040 - 2/97
WLS
TANK WATER LEVEL SWITCH

INSTALLATION INSTRUCTIONS
A buttress thread nut and gasket are available for use with into the adapter (see Fig. 4).
devices on installations where the inside of the tank is NOTE: The high signal is not required for gravity tanks
accessible and it is not convenient to weld a flange on the and the WLS can be wired so that either High or Low or
tank. The nut and gasket can also be used in a wood both switches may be used (see Fig. 5).
tank that is not sound enough to hold a thread (see Fig.
2). For pressure tanks, weld the 1 1/2" NPT threaded flange
(#6660225) into the tank at the desired water level and
For installation in steel gravity tanks, weld a 1 1/2" NPT use both high and low signals.
threaded flange (#6660225) 9" below the required water
level to receive the 1 1/2" bushing (see Fig. 3). To replace an existing Potter WLS in a steel tank with a
welded flange a 1 1/2" x 2"NPT bushing adapter
For wood gravity tanks, bore a 2 3/8" hole in the center of (#5020126) is available. Thread the bushing adapter into
a stave 9" below the required water level and screw the the 2" welded flange securely then install the WLS into
buttress bushing adapter (#5180199) in place, allowing the adapter.
the bushing to cut its own thread, then install the WLS
CAUTION: Do not lift or hold device by float or float rod as
bending may occur.
FIG. 2 Wood or Steel Tank FIG. 3 Steel Tank Installa- FIG. 4 Wood Tank Installation
Installation tion

FIG. 5 SWITCH TERMINAL CONNECTIONS ORDERING INFORMATION


CLAMPING PLATE TERMINAL
Device Stock No.
WLS 1010117
Accessories
Flange 1 1/2" 6660225
Buttress Nut 6660083
CAUTION:
Gasket 5330025
An uninsulated section of a single Buttress Adapter 5180199
conductor should not be looped 1 1/2" NPT x 2 1/2"
around the terminal and serve as two Bushing Adapter 5020126
separate connections. The wire must 1 1/2" NPT x 2" NPT
be severed, thereby providing supervi-
sion of the connection in the event that
the wire becomes dislodged from
under the terminal.

PRINTED IN USA MKT. #8820016 - REV A PAGE 2 OF 2


MFG. #5401040 - 2/97
TTS
TANK TEMPERATURE
SUPERVISORY SWITCH
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • P.O. Box 28480 55 Glen Cameron Road
St. Louis, MO 63146-4161 Thornhill, Ontario, Canada L3T 1P2
(314) 878-4321 • (800) 325-3936 (905) 882-1833

UL, CSFM LISTED, FM APPROVED and


NYMEA ACCEPTED

TTS-W

TTS-S

2 1/2" DIA x 17 1/2"L

The Model TTS-S is a water tank temperature superviso- A buttress thread nut and gasket are available for use
ry switch preset to give a low temperature signal at 40°F/ with the TTS-W for installations where the inside of the
4.5°C and a high temperature signal at 140°F/60°C tank is accessible and it is not convenient to weld a
(±3°F/2°C). It is UL Listed and FM Approved. flange on the tank.
A glass mercury thermostat is used for low temperature The nut and gasket can also be used on a wood tank,
sensing and a bi-metal thermostat for high temperature which is not sound enough to hold a thread (see Fig. 1).
sensing. A diode is used in this unit as a testing aid. Locate the switch at a point 24 inches below the required
When the polarity of DC current is reversed at the feed water level of the tank.
wires to a TTS, the diode in the circuit prevents the flow
For steel tanks, weld in a No. 282-1 pipe flange or drill a
of current, proving the absense of a short circuit fault in
tap tank to receive the one inch pipe thread of the
the wiring or the device itself.
bushing (see Fig. 2).
CONTACTS: .15 Amp at 115 VDC
For wood tanks, drill a 1 3/16" hole in the center of a
The TTS, tank temperature switch is supplied with a one stave and thread the bushing into the tank allowing the
inch pipe thread for steel tanks (Model TTS-S) or with a butress bushing to cut its own thread (see Fig. 3).
buttress thread for wood tanks (Model TTS-W).

PRINTED IN USA MKT. #8820011 - REV D PAGE 1 OF 2


MFG. #5400674 - 12/95
TTS
TANK TEMPERATURE
SUPERVISORY SWITCH

INSTALLATION

FIG. 1 TTS-W (WOOD OR STEEL) FIG. 2 TTS-S (STEEL)

FIG. 3 TTS-W (WOOD) FIG. 4 TTS-S SIMPLIFIED SCHEMATIC

TTS ORDERING INFORMATION


DEVICE STOCK NO.
TTS-S (Steel) 1010040
TTS-W (Wood) 1010041

ACCESSORIES
Flange 1" 5020010
Buttress Nut 5020105
Gasket 5330035

PRINTED IN USA MKT. #8820011 - REV D PAGE 2 OF 2


MFG. #5400674 -12/95
RTS-O / RTS-C
ROOM TEMPERATURE SWITCH

Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • P.O. Box 28480 55 Glen Cameron Road
St. Louis, MO 63146-4161 Thornhill, Ontario, Canada L3T 1P2
(314) 878-4321 • (800) 325-3936 (905) 882-1833

Enclosure: White ABS

Dimensions: 2 1/16"W x 3 7/16"L x 1 1/4"H

Sensor: Epoxy sealed stainless steel case, bi-


metallic operating mechanism.

Contacts: Silver clad, available normally open or


normally closed.

Electrical Rating: 1Amp at 24VDC

Temperature Setting: 40°±5°F, 5°±3°C

Terminals: Screw Terminals

Mounting: Surface
RTS-O STK. #1010108
RTS-C STK. #1010109

The RTS Series Room Temperature Sensors are FEATURES:


precision engineered, designed and manufactured
for commercial or residential use. • Easily installed
• Completely sealed sensor, moisture and vapor
Available at factory preset temperature rating of 40° F. resistant
Designed to warn of potential sprinkler pipe freezing • Highly resistant to vibration and corrosion
or other cold detection applications. • Highly sensitive to temperature changes
• No sensitivity loss due to aging
Each unit consists of a bi-metal operating mecha- • Repetitive operation without the need to replace
nism, featuring hermetically sealed precious metal sensing elements
contacts, N.O. or N.C., which automatically reset for • Small compact design
repetitive operation, eliminating the need for sens- • Precision and quality at low cost
ing element replacement.
OPERATION
Small compact design, highly resistant to vibration
The normally open detector, RTS-O, will close the
and corrosion. Easily installed using the enclosed
contact when the temperature drops below 40°F.
hardware or adhesive mounting pad.
The normally closed detector, RTS-C, will open the
contact when the temperature drops below 40°F.
Screw terminals permit easy installation in single or
The detector will automatically reset to the normal
multiple detector circuits.
state when the temperature rises above 40°F.

PRINTED IN USA MKT. #8820013 - REV C PAGE 1 OF 1


MFG. #5401019 - 12/95
VSR-FEX
EXPLOSION PROOF VANE TYPE
WATERFLOW ALARM SWITCH WITH RETARD
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • P.O. Box 28480 55 Glen Cameron Road
St. Louis, MO 63146-4161 Thornhill, Ontario, Canada L3T 1P2
(314) 878-4321 • (800) 325-3936 (905) 882-1833

UL, CSFM and NYMEA Listed and FM Approved

Service Pressure: Up to 450 PSI

Minimum Flow Rate for Alarm: 10 GPM

Maximum Surge: 18 FPS

Contact Ratings: Two sets of SPDT (Form C)


15.0 Amps at 125/250 VAC
2.5 Amps at 30 VDC Resistive

Conduit Entrances: Two conduit entrances provided for 1/2" con-


duit

Environmental Specifications:
• For use in hazardous locations, Classified as:
Class I: Groups C, D, Div. 1
Class II: Groups E, F, G, Div. 1
Class III: Div. 1
• Suitable for indoor or outdoor use with factory installed gasket
and cast aluminum housing.
• NEMA 4 Rated Enclosure - use with appropriate conduit fitting
• Temperature: 40°F/120°F, 4.5°C/49°C
• Non-corrosive sleeve factory installed in saddle.

Sizes Available: Pipe schedules 10 thru 40, sizes 2" thru 8"

Service Use: Automatic Sprinkler NFPA-13


National Fire Alarm Code NFPA-72

GENERAL INFORMATION INSTALLATION (See Fig.2)


The Model VSR-FEX is a vane type waterflow switch for use These devices may be mounted on horizontal or vertical pipe.
on wet sprinkler systems located in hazardous locations as On horizontal pipe they should be installed on the top side of
shown above. the pipe where they will be accessible. The units should not
be installed within 6" of a fitting which changes the direction of
The unit may also be used as a sectional waterflow detector
the waterflow or within 24" of a valve or drain.
on large systems.
Drain the system and drill a hole in the pipe using a circular
The unit contains two single pole, double throw, snap action
saw in a slow speed drill. The 2" and 2 1/2" devices require a
switches and an adjustable, instantly recycling pneumatic
hole with a diameter of 1 1/4" + 1/8" - 1/16". All other sizes
retard. The switches are actuated when a flow of 10 gallons
require a hole with a diameter of 2" ± 1/8".
per minute or more occurs downstream of the device. The
flow condition must exist for a period of time necessary to Clean the inside pipe of all growth or other material for a
overcome the selected retard period. distance equal to the pipe diameter on either side of the hole.
ENCLOSURE Roll the vane so that it may be inserted into the hole, do not
bend or crease it. Insert the vane so that the arrow on the
The unit is enclosed in a cast aluminum housing. The cover
saddle points in the direction of the waterflow. Install the
is held in place with tamper resistant screws which require a
saddle strap and tighten nuts alternately to an eventual 50 ft-
special key for removal.
lbs. of torque. See Fig. 2. The vane must not rub the inside
of the pipe or bind in any way.

PRINTED IN USA MKT. #8880009 - REV D PAGE 1 OF 2


MFG. #5400805 - 5/96
VSR-FEX
EXPLOSION PROOF VANE TYPE
WATERFLOW ALARM SWITCH WITH RETARD

FIG. 1 FIG. 2
SWITCH TERMINAL
CONNECTIONS
CLAMPING PLATE
TERMINAL

CAUTION:
An uninsulated section
of a single conductor
should not be looped
around the terminal and
serve as two separate
connections. The wire
must be severed,
thereby providing
supervision of the
connection in the event
that the wire becomes
CAUTION: When this device is to be installed in an area that is classified as “Hazardous”, the
dislodged from under the
person responsible for safety in the area should be contacted to determine if the tools and opera-
terminal.
tions required for the installation of the device and associated components are permitted in the
area. To reduce the risk of ignition of hazardous atmospheres, disconnect supply circuits before
opening enclosure. Keep cover tightly closed when in operation. cover screws must be torqued to a
minimum of 20 in. lbs.

FIG. 3 TYPICAL ELECTRICAL CONNECTIONS

Note: for supervised circuits see “Switch


Terminal Connections” drawing and
caution note (Fig. 1).

NOTE: The Model VSR-FEX has two switches, one can be used to operate a central station, proprietary or remote signaling unit,
while the other contact is used to operate a local audible or visual annunciator.

TESTING: The frequency of testing for the model VSR-FEX for test purposes. If there are no provisions for testing the
and its associated protective monitoring system should be in operation of the flow detection device on the system,
accordance with applicable NFPA Standards and/or the application of the VSR-FEX is not recommended or advisable.
authority having jurisdiction (manufacturer recommends
A minimum flow of 10 gpm is required to activate this device.
quarterly or more frequently).
IMPORTANT NOTICE: Please advise the person responsible
If provided, the inspector’s test valve, that is usually located at
for testing of the fire protection system that this system must be
the end of the most remote branch line, should always be used
tested in accordance with the testing instructions.

PRINTED IN USA MKT. #8880009 - REV D PAGE 2 OF 2


MFG. #5400805 - 5/96
MODEL PS10-EX
EXPLOSION PROOF PRESSURE SWITCH
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • St. Louis, MO 63146-4161 55 Glen Cameron Road
(314) 878-4321 • (800) 325-3936 Thornhill, Ontario, Canada L3T 1P2
www.pottersignal.com (905) 882-1833

UL and CSFM Listed, FM Approved and NYMEA Accepted


Dimensions: 6"Dia. x 7"H
Enclosure: Cast aluminum
Pressure Connection: 1/2" NPT Male Brass Fitting
Factory Adjustment:
Both switches operate on Pressure Increase at 6 ±1 PSI
Both switches operate on Pressure Decrease at 5 ±1 PSI
Maximum Differential: 1 PSI
Maximum System Pressure: 250 PSI
Switch Contacts: Two Sets of SPDT (Form C)
15.0 Amps at 125/250 VAC
2.5 Amps at 30 VDC
Environmental Specifications:
For use in hazardous locations classified as:
Class I: Groups B, C, D, Div. 1
Class II: Groups E, F, G, Div. 1
Class III: Div. 1
NEMA 4 Rated Enclosure
Temperature range: -40°F to 140°F (-40°C to 60°C)
Service Use:
Automatic Sprinkler NFPA-13
PS10-EX No.1350102 National Fire Alarm Code NFPA-72

INSTALLATION AND TEST PROCEDURE: The Potter PS10- METHOD 2: When using the PS10-EX for local bell application
EX Pressure Actuated Switch is designed for the detection of a or with a control that does not provide a retard feature, the
waterflow condition in automatic fire sprinkler systems located PS10-EX must be installed on the alarm outlet side of the
in hazardous locations classified as shown above, of particular retard chamber of the sprinkler system.
designs such as wet systems with alarm check valves or dry TESTING: Accomplished by opening the inspector's end-of-line
pipe systems. It may also be used to provide a low pressure test valve. Allow time to compensate for system or control retard.
supervisory signal. It can be adjusted to operate on pressure CAUTION: Method 2 is not applicable for remote station
between 4 and 20 PSI. service use.
MOUNTING: Device should be mounted in upright position WET SYSTEM WITH EXCESS PRESSURE: Connect the
(threaded connection down). Requires NEMA Type 4 conduit PS10-EX into alarm port piping extending from alarm check
hub for outdoor installations. valve. Retard provisions are not required. Insure that no shut
off valves are present between the alarm check valve and the
TESTING: The operation of the pressure alarm switch should
PS10-EX.
be tested upon completion of installation and periodically
TESTING: Accomplished by opening the water by-pass test
thereafter in accordance with the applicable NFPA codes and
valve or the inspector's end-of-line test valve. When using end-
standards and/or the authority having jurisdiction (manufacturer
of-line test, allow time for excess pressure to bleed off.
recommends quarterly or more frequently).
DRY SYSTEM: Connect the PS10-EX into alarm port piping
WET SYSTEM:
that extends from the intermediate chamber of the alarm check
METHOD 1: When using PS10–EX and control unit with
valve. Install on the outlet side of the in-line check valve of the
retard, connect the PS10–EX into alarm port piping on the input
alarm port piping. Insure that no shut off valves are present
side of retard chamber and electrically connect PS10–EX to
between the alarm check valve and the PS10-EX.
control unit that provides a retard to compensate for surges.
TESTING: Accomplished by opening the water by-pass test valve.
Insure that no shut off valves are present between the alarm
check valve and the PS10–EX. CAUTION: The above tests may also activate any other circuit
closer or water motor gongs that are present on the system.

PRINTED IN USA MKT. #8880010 - REV G PAGE 1 OF 3


MFG. #5400982 - 5/97
MODEL PS10-EX
EXPLOSION PROOF PRESSURE SWITCH

ORDERING INFORMATION
Model Description Stock No.
PS10-EX Pressure switch with two sets SPDT contacts 1350102
Hex Key 5250073

TYPICAL SPRINKLER APPLICATIONS

CAUTION: Closing of any shutoff valves between the alarm check valve and the PS10-EX will render the PS10-EX
inoperative. To comply with NFPA-72 any such valve shall be electrically supervised with a supervisory switch
such as Potter Model BVS.

TYPICAL ELECTRICAL CONNECTIONS

SWITCH TERMINAL CONNECTIONS


CLAMPING PLATE TERMINAL

CAUTION:
An uninsulated section of a single conductor should not be
looped around the terminal and serve as two separate
connections. The wire must be severed, thereby providing
supervision of the connection in the event that the wire
becomes dislodged from under the terminal.

PRINTED IN USA MKT. #8880010 - REV G PAGE 2 OF 3


MFG. #5400982 - 5/97
MODEL PS10-EX
EXPLOSION PROOF PRESSURE SWITCH

PRESSURE SWITCH
TERMINATION

NOTE: To prevent leakage, apply teflon tape


sealant to male threads only.

WARNING: Use of pipe joint cement may result


in obstruction of aperture and loss of signal.

CAUTION: When this device is to be installed in an area that is classified as “HAZARDOUS”, the person
responsible for safety in the area should be contacted to determine if the tools and operations required for the
installation of the device and associated components are permitted in the area. To reduce the risk of ignition of
hazardous atmospheres, disconnect supply circuits before opening cover. Keep cover tight while circuits are live.
Cover screws must be torqued to 45-50 in. lbs.

ENGINEER/ARCHITECT SPECIFICATIONS
Pressure type waterflow switches shall be a Model PS10-EX as manufactured by Potter Electric Signal Co. of St. Louis, Mo. and
shall be installed on the sprinkler systems as shown on the drawings and/or specified herein.
Switches shall be provided with a 1/2" NPT male pressure connection to be connected into the alarm check valve of a “wet”
sprinkler system or into the intermediate chamber of a “dry” pipe system and shall be actuated by any flow of water to or in excess
of the discharge from one sprinkler head.
Switches shall have a maximum service pressure rating of 250 PSI and shall be factory adjusted to operate on pressure increase
at 6 ±1 PSI. There shall be two (2) SPDT contacts rated at 15.0 Amps at 125/250VAC and 2.5 Amps at 30VDC.
The switch housing shall be weather proof and oil resistant with a NEMA 4 rating. The cover shall incorporate tamper resistant
screws.
The unit shall be listed by Underwriters Laboratories, Inc. and CSFM and approved by Factory Mutual. It shall be rated for use in
hazardous locations classified as Class I, Groups B, C, D, Div. 1; Class II, Groups E, F, G, Div. 1; Class III, Div. 1.

PRINTED IN USA MKT. #8880010 - REV G PAGE 3 OF 3


MFG. #5400982 - 5/97
MODEL PS40-EX
EXPLOSION PROOF HIGH/LOW
PRESSURE SWITCH
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • St. Louis, MO 63146-4161 55 Glen Cameron Road
(314) 878-4321 • (800) 325-3936 Thornhill, Ontario, Canada L3T 1P2
www.pottersignal.com (905) 882-1833

UL and CSFM Listed, FM Approved and NYMEA Accept-


e d
Dimensions: 6"Dia. x 7"H
Enclosure: Cast Aluminum
Pressure Connection: 1/2" NPT Male Brass Fitting
Factory Adjustment:
One switch operates on decrease at 30 PSI and one
switch operates on increase at 50 PSI.
Pressure Range: 10 - 175 PSI
Maximum Differential: Approx. 2 lbs. at 20 PSI
5 lbs. at 175 PSI
Maximum System Pressure: 250 PSI
Switch Contacts: Two sets of SPDT (Form C)
15.0 Amps at 125/250 VAC
2.5 Amps at 30 VDC
Environmental Specifications:
For use in hazardous locations classified as:
Class I: Groups B, C, D, Div. 1
Class II: Groups E, F, G, Div. 1
Class III: Div. 1
NEMA 4 Rated Enclosure
Temperature range: -40°F to 140°F (-40°C to 60°C)
Service Use:
PS40-EX No. 1350402 Automatic Sprinkler NFPA-13
National Fire Alarm Code NFPA-72

The Potter PS40-EX is a pressure actuated switch Dry System: Connect PS40-EX in air supply line on the
designed primarily to detect a 10 PSI increase and/or system side of any shutoff or check valve.
decrease from normal system pressure in automatic fire
sprinkler systems located in hazardous locations classi- Provision for testing the unit can be accomplished with
fied as shown above. the installation of a Potter Bleeder Valve (Model BVL) in
the line to the PS40-EX.
Typical applications are air pressure supervision in dry
pipe systems and pressure supervision of pressure Testing: The operation of the pressure supervisory
tanks, air supply or water supply. switch should be tested upon completion of installation
and periodically thereafter in accordance with the
INSTALLATION AND TEST PROCEDURE applicable NFPA codes and standards and/or the
authority having jurisdiction (manufacturer recommends
Mounting: Device should be mounted in upright position quarterly or more frequently).
(threaded connection down).
CAUTION: Testing the PS40-EX may activate other
Requires NEMA Type 4 conduit hub for outdoor installations. system connected devices.

PRINTED IN USA MKT. #8880011 - REV H PAGE 1 OF 3


MFG. #5400983 - 5/97
MODEL PS40-EX
EXPLOSION PROOF HIGH/LOW
PRESSURE SWITCH

Ordering Information
Model Description Stock No.
PS40-EX Pressure switch with two sets SPDT contacts 1350402
BVL Bleeder Valve 1000018
Hex Key 5250073

TYPICAL SPRINKLER APPLICATION - DRY SYSTEM

TYPICAL ELECTRICAL CONNECTIONS

SWITCH TERMINAL CONNECTIONS


CLAMPING PLATE TERMINAL

CAUTION:
An uninsulated section of a single conductor should not be
looped around the terminal and serve as two separate
connections. The wire must be severed, thereby providing
supervision of the connection in the event that the wire
becomes dislodged from under the terminal.

PRINTED IN USA MKT. #8880011 - REV H PAGE 2 OF 3


MFG. #5400983 - 5/97
MODEL PS40-EX
EXPLOSION PROOF HIGH/LOW
PRESSURE SWITCH

PRESSURE SWITCH TERMINATION

NOTE: Switches are shown in standby condition with “normal”


pressure applied. Switch #1 (high) changes with pressure
increase. Switch #2 (low) changes with pressure decrease.

FIELD ADJUSTMENTS
The operating point of the switches on the
PS40-EX can be adjusted to any point between
10 and 175 PSI by turning the adjustment
knob(s) clockwise to raise the actuation point,
and counter-clockwise to lower the actuation
point. The two switches operate completely
independently of one another, and each switch
may be adjusted to actuate at any point the
system requires. Final adjustment should be
made with a pressure gauge.

NOTE: To prevent leakage, apply teflon tape


sealant to male threads only.

WARNING: Use of pipe joint cement may result


in obstruction of aperture and loss of signal.

CAUTION: When this device is to be installed in an area that is classified as “HAZARDOUS”, the person
responsible for safety in the area should be contacted to determine if the tools and operations required for the
installation of the device and associated components are permitted in the area. To reduce the risk of ignition of
hazardous atmospheres, disconnect supply circuits before opening cover. Keep cover tight while circuits are live.
Cover screws must be torqued to 45-50 in. lbs.

ENGINEER/ARCHITECT SPECIFICATIONS
Air pressure supervisory switch shall be a Model PS40-EX as manufactured by Potter Electric Signal Co. of St. Louis, Mo. and
shall be installed on the sprinkler systems as shown on the drawings and/or as specified herein.
Switches shall be provided with a 1/2" NPT male pressure connection to be connected into the air supply line on the system side
of any shut-off valve. A Model BVL bleeder valve as supplied by Potter Electric Signal Co. of St. Louis, Mo. or equivalent shall be
connected between the air line to provide a means of testing the operation of the supervisory switch.
The switch unit shall contain SPDT (Form C) switches. One switch shall operate at a pressure decrease of 10 PSI from normal.
The second switch shall operate at a pressure increase of 10 PSI from normal. Switch contacts shall be rated at 15.0 Amps at
125/250 VAC and 2.5 Amps at 30 VDC. The units shall have a maximum pressure rating of 250 PSI and shall be adjusted from
10 to 175 PSI.
The switch housing shall be weatherproof and oil resistant with a NEMA 4 rating. The cover shall incorporate tamper resistant
screws.
The unit shall be listed by Underwriters Laboratories, Inc. and CSFM and approved by Factory Mutual. It shall be rated for use in
hazardous locations classified as Class I, Groups B, C, D, Div. 1; Class II, Groups E, F, G, Div. 1; Class III, Div. 1.

PRINTED IN USA MKT. #8880011 - REV H PAGE 3 OF 3


MFG. #5400983 - 5/97
PIVS-U-EX
POST INDICATOR VALVE SWITCH
EXPLOSION PROOF
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • P.O. Box 28480 55 Glen Cameron Road
St. Louis, MO 63146-4161 Thornhill, Ontario, Canada L3T 1P2
(314) 878-4321 • (800) 325-3936 (905) 882-1833

Enclosure: Explosion Proof Switch Enclosure

Environmental Limitations:
-40° to 140°F (-40°C to 60°C).
For use in hazardous locations.

Mounting: 1/2" tapped hole in post indicator housing

Contact Rating: 10 AMPS at 125VAC


1/2 AMP at 125VDC

Service Uses:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72

STOCK NO. 1010092

The PIVS-U-EX is designed to mount in a 1/2" tapped hole in Drill and tap the post at the location selected to receive the 1/2"
the post indicator housing. The PIVS-U-EX should be located NPT nipple on the switch.
so that the stem of the switch is held against the stem return
In some cases it may be necessary to attach an angle bracket
spring by the indicator assembly when the valve is open.
to the target assembly to engage the switch stem. Any excess
SWITCH ENCLOSURE: UL listed explosion proof switch length of the stem should be cut off with a hack saw.
enclosure. For hazardous locations. Class I, Group C & D;
Close the valve carefully and see that the switch stem is free to
Class II, Groups E, F, & G.
move and that no excess pressure is placed on the stem at the
INSTALLATION: See Figures 1, 2, 3, 4, and 5. Operate the end of its travel.
valve to determine whether the target moves up or down as the
Small adjustments of the target position may be made if
valve is closed.
necessary.
Open the valve fully and see that target indicates “OPEN”.
The contacts of the switch should operate when the valve is
Remove the head from the indicator post and remove target
closed 1 or 2 turns. The switch can be tested with a buzzer or
assembly.
ohmeter.
Select a location for the switch, so that the stem of the switch
Replace the head on the indicator post.
will be depressed by some part of the target assembly when
valve is fully open. The switch location should be accessible An alternate method of installation is shown in Figure 3. In this
for service. method one of the glass windows is replaced with a 1/4" thick
steel plate cut to fit in place of the glass and drilled and tapped
If the target assembly moves up when the valve is closed
to receive the 1/2" pipe nipple on the switch.
locate the switch below the target with the long part of the case
pointing down. A 1/2" or 3/4" square block of steel is attached to the target
assembly, in place of the cast letter plate, to actuate the switch
If the target assembly moves down when the valve is closed
stem.
locate the switch above the target with the long part of the case
pointing up. Figure 4 shows the switch mounted on a butterfly valve.

PRINTED IN USA MKT. #8880005 - REV D PAGE 1 OF 2


MFG. #5400694 - 12/95
PIVS-U-EX
POST INDICATOR VALVE SWITCH
EXPLOSION PROOF
FIG. 1 TYPICAL VALVE INSTALLATION FIG. 2 TYPICAL VALVE INSTALLATION FIG. 3 VALVE WINDOW INSTALLATION

FIG. 4 BUTTERFLY VALVE INSTALLATION

FIG. 5 TYPICAL ELECTRICAL CONNECTIONS

PRINTED IN USA MKT. #8880005 - REV D PAGE 2 OF 2


MFG. #5400694 - 12/95
OSYS-U-EX
O S & Y SWITCH - UNIVERSAL
EXPLOSION PROOF
Potter Electric Signal Company Potter Electric Signal & Mfg., LTD.
2081 Craig Road • St. Louis, MO 63146-4161 55 Glen Cameron Road
(314) 878-4321 • (800) 325-3936 Thornhill, Ontario, Canada L3T 1P2
www.pottersignal.com (905) 882-1833

GATE VALVE SWITCH FOR SUPERVISION OF


O S & Y VALVES: The Model OSYS-U-EX is
designed to supervise the open condition of an
O S & Y type gate valve in hazardous locations.

CONTACTS: One set of SPDT (Form C)


Contacts rated 15 Amps,125/250/480VAC;
1/2 Amp, 125VDC; 1/4 Amp, 250VDC

SWITCH ENCLOSURE: UL listed explosion proof


switch enclosure. For hazardous locations.
Class I, Groups C & D; Class II, Groups E, F & G

TYPICAL ELECTRICAL CONNECTIONS

PRINTED IN USA MKT. #8880006 - REV D PAGE 1 OF 2


MFG. #5400705 - 11/97
OSYS-U-EX
O S & Y SWITCH - UNIVERSAL
EXPLOSION PROOF

VALVE SIZES 1/2" THRU 2 1/2" VALVE SIZES 3" THRU 12"
FIG.1 FIG.2

SMALL VALVE INSTALLATION LARGE VALVE INSTALLATION


1. Remove and discard "C" washer and roller from the trip rod. 1. With the valve in the FULL OPEN position, locate the OSYS-U-EX
across the valve yoke as far as possible from the valve gland, so
2. With the valve in the FULL OPEN position, locate the OSYS-U-EX that the trip rod lays against the non-threaded portion of the valve
across the valve yoke as far as possible from the valve gland, so stem.
that the trip rod lays against the non-threaded portion of the valve
stem. 2. Mount the OSYS-U-EX loosely with the carriage bolts and clamp
bar supplied.
3. Excess trip rod length extending beyond the valve stem must be
cut off. 3. If the trip stem extends below the valve yoke, the clamp bar must
be discarded and the large J hooks must be used to mount the
4. Mount the OSYS-U-EX loosely with the carriage bolts and clamp OSYS-U-EX to the valve.
bar supplied. On valves with limited clearance use J-hooks
supplied instead of the carriage bolts and clamp bar to mount the 4. Mark the valve stem at the center of the trip rod.
OSYS-U-EX.
5. Remove the OSYS-U-EX. File a 1/8" deep groove centered on the
5. Mark the valve stem at the center of the trip rod. mark of the valve stem utilizing a 3/8" diameter straight file.
Round and smooth the edges of the groove to prevent damage to
6. Remove the OSYS-U-EX. File a 3/32" deep groove centered on the valve packing and to allow the trip rod to move easily in and
the mark on the valve stem utilizing a 1/4" diameter straight file. out of the groove as the valve is operated.
Round and smooth the edges of the groove to prevent damage to
the valve packing and to allow the trip rod to move easily in and 6. Mount the OSYS-U-EX loosely with the trip rod centered in groove.
out of the groove as the valve is operated.
7. Final adjustment is made by loosening 2 screws (see Fig. 2) and
7. Mount the OSYS-U-EX with the trip rod centered in groove. sliding the OSYS-U-EX on the bracket. Adjustment is correct
when switches are not activated with the trip rod seated in the
8. Final adjustment is made by loosening 2 screws (see Fig. 1) and valve stem groove and that the switches activate within one turn
sliding the OSYS-U-EX on the bracket. Adjustment is correct when the valve is operated from the FULL OPEN towards the
when switches are not activated with the trip rod seated in the CLOSED position.
valve stem groove and that the switches activate when the trip rod
moves out of the groove. 8. Tighten the adjustment screws and mounting hardware. Check to
insure that the rod moves out of the groove easily and that the
9. Tighten the adjustment screws and all mounting hardware. switches activate within one turn when the valve is operated from
Check to insure that the rod moves out of the groove easily and the FULL OPEN towards the CLOSED position.
that the switches activate within one turn when the valve is
operated from the FULL OPEN towards the CLOSED position. NOTE: CLOSE THE VALVE FULLY TO DETERMINE THAT THE
STEM THREADS DO NOT ACTIVATE THE SWITCH. THE SWITCH
NOTE: CLOSE THE VALVE FULLY TO DETERMINE THAT THE BEING ACTIVATED BY THE STEM THREADS COULD RESULT IN A
STEM THREADS DO NOT ACTIVATE THE SWITCH. THE SWITCH FALSE VALVE OPEN INDICATION.
BEING ACTIVATED BY THE STEM THREADS COULD RESULT IN A
FALSE VALVE OPEN INDICATION.

PRINTED IN USA MKT. #8880006 - REV D PAGE 2 OF 2


MFG. #5400705 - 11/97

You might also like