Accuflow Series Low Flow Rate Waterflow Detectors: Sprinkler Systems Monitoring
Accuflow Series Low Flow Rate Waterflow Detectors: Sprinkler Systems Monitoring
Accuflow Series Low Flow Rate Waterflow Detectors: Sprinkler Systems Monitoring
Accuflow™ Series
Low Flow Rate
Waterflow Detectors
Models Available
LFD30-2
LFD20
LFD25-73MM
LFD25-76MM
LFD30-2 LFD30-2 (cover removed)
LFD40
Replacement Par ts
WFDW Cover wrench
546-9000 Cover tamper
switch kit
WFDN4 Gasket kit
Product Overview
For use in wet pipe water mist systems System Sensor’s Accuflow™ Low Flow Rate detectors are a new line of solid state
waterflow detectors designed for use in wet pipe water mist systems where low
Compatible with 2 to 4 inch stainless flow detection is required.
steel and brass pipe
Robust Construction. Accuflow low flow detectors consist of a rugged enclosure for
Solid state retard assures precise indoor and outdoor use. Like all System Sensor waterflow detectors, low flow models
timing accuracy operate across a wide temperature range, from 32ºF to 120ºF (0°C to 49°C).
Dipswitch selections simplify Reliable Performance. Accuflow low flow detectors are intended for applications
retard settings where flow detection of 3 GPM or greater is required. By incorporating a solid state
retard, proper sensitivity, timing accuracy and switch resetting is assured.
Non-polarized, two-wire design
allows connection to a local bell and False Alarm Immunity. The solid state circuitry of Accuflow low flow detectors pro-
conventional or addressable systems vides greater timing accuracy over traditional mechanical retard designs. This accura-
cy minimizes the risk of false alarms created by pressure surges or air trapped within
NEMA 4 rated the sprinkler system.
Synchronized switches activate Simplified Operation. Accuflow low flow detectors are designed to simplify instal-
both the alarm panel and local lation. Wired like traditional waterflow detectors, these models do not require the
bell simultaneously installer to run an additional third wire. Two conduit openings permit easy attach-
ment to the local alarm system.
Engineering Specification
Low flow rate vane-type waterflow detector with solid state retard shall be an Accuflow model number ____________________
manufactured by System Sensor, and shall be installed on system piping as designated on the drawing and/or as specified
herein. Detectors shall mount on a stainless steel clear pipe span of the appropriate nominal size, either on a ver tical upflow
of horizontal run, at least 6” from any fittings which may change water direction, flow rate, or pipe diameter, or no closer
than 24” from a valve or drain. Detectors shall be compatible with 2” through 4” diameter stainless steel and brass pipe.
Detectors shall have a sensitivity of 3 gallons (11.35 liters) per minute minimum and a static pressure of 450 psi for 2”
– 4” diameter pipes. The detector shall respond to water flow in the specified direction after a preset time delay. The delay
mechanism shall be a solid state unit which is field-adjustable via a dipswitch. The detector’s actuation mechanism shall
include a polyethylene vane inser ted through a hole in the pipe and connected by a mechanical linkage to the delay mecha-
nism. Outputs shall consist of one SPDT switch (Form C contact) and one SPST switch (normally open contact) for wiring to
an alarm panel or addressable control module and local bell and/or notification device. Two conduit entrances (one knockout
type) for standard fittings of commonly used electrical conduit shall be provided on the detectors. A grounding provision shall
be provided. Unless noted, enclosures shall be NEMA 4 listed by Under writers Laboratories, Inc. for indoor or outdoor use.
Standard Specifications
Static Pressure Rating Contact Ratings Cover Tamper Switch
450 PSI One SPDT (Form C) Optional, par t no. 546-9000
One SPST (normally open) Shipping Weight
Triggering Threshold Bandwidth (Flow Rate) 0.6 A @ 125 VAC
3 GPM (11.35 liters/minute) LFD20: 4.1 lbs. (1.8 kg)
2.0 A @ 30 VDC
Maximum Surge Voltage Range LFD25-73MM: 4.2 lbs. (1.9 kg)
18 Feet Per Second (FPS) 8.4-35V (DC-FWR)
108-132 VAC AFD25-76MM: 4.2 lbs. (2.0 kg)
Compatible Pipe
Stainless steel and brass water pipe, Current Draw LFD30-2: 4.4 lbs. (2.1 kg)
2” through 4” (refer to Ordering Information 300 microamps @ 12/24 V(DC-FWR) LFD40: 5.1 lbs. (2.3 kg)
below) 400 microamps @ 120 VAC
Ser vice Use
Overall Dimensions Installed
Conduit Entrances Water mist systems where low flow detection
3.75″ Two openings for 1/2” conduit, one open, one is required.
knock-out type
Warranty
3.0″
Operating Temperature Range 3 years
32°F - 120°F (0°C to 49°C)
U.S. Patent No.
Enclosure Rating 6,084,521
U bolt nut 1.6″
NEMA 4 - suitable for indoor/outdoor use
Pipe saddle
Pipe
Plastic vane
Ordering Information
Model Numbers Nominal Pipe O.D. and Wall Thickness Hole Size Replacement Part Number Description
LFD20 2” (60.3 mm OD), 3.9 mm to 4.5 mm 1-1/4” 546-9000 Cover tamper switch kit
LFD25-73MM 2-1/2” (73.0 mm OD), 4.8 mm to 5.2 mm 1-1/4” WFDW Tamper proof wrench for cover
LFD25-76MM 2-1/2” (76.1 mm OD), 4.3 mm to 4.7 mm 1-1/4” WFDN4 Gasket kit
LFD30-2 3” (88.9 mm OD), 5.0 mm to 5.6 mm 2”
LFD40 4” (114.3 mm OD), 5.4 mm to 6.4 mm 2”