51135
51135
51135
PDRP1002.CD
The PDRP-1002/PDRP-1002E
Agent Release Control System
Manual
Document 51135
I56-1358-00
03/11/99 Revision: A
PN 51135:A ECN 99-017
Installation Precautions – Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the Like all solid state electronic devices, this system may operate
fire alarm control panel. Disconnect all sources of power before erratically or can be damaged when subjected to lightning induced
servicing. Control unit and associated equipment may be damaged by transients. Although no system is completely immune from lightning
removing and/or inserting cards, modules, or interconnecting cables transients and interferences, proper grounding will reduce
while the unit is energized. Do not attempt to install, service, or operate susceptibility. Overhead or outside aerial wiring is not recommended
this unit until this manual is read and understood. due to an increased susceptibility to nearby lightning strikes. Consu
with the Technical Services Department if any problems are
CAUTION - System Reacceptance Test after Software Changes: To anticipated or encountered.
ensure proper system operation, this product must be tested in
accordance with NFPA 72-1993 Chapter 7 after any programming Disconnect AC power and batteries prior to removing or inserting
operation or change in site-specific software. Reacceptance testing is circuit boards. Failure to do so can damage circuits.
required after any change, addition or deletion of system components, or
after any modification, repair or adjustment to system hardware or Remove all electronic assemblies prior to any drilling, filing, reamin
wiring. or punching of the enclosure. When possible, make all cable entries
from the sides or rear. Before making modifications, verify that they
All components, circuits, system operations or software functions known will not interfere with battery, transformer and printed circuit board
to be affected by a change must be 100% tested. In addition, to ensure location.
that other operations are not inadvertently affected, at least 10% of
initiating devices that are not directly affected by the change, up to a Do not tighten screw terminals more than 9 in-lbs. Over tightenin
maximum of 50 devices must also be tested and proper system may damage threads, resulting in reduced terminal contact pressure
operation verified. and difficulty with screw terminal removal.
This system contains static-sensitive components Always ground
This system meets NFPA requirements for operation at 0-49O C/ yourself with a proper wrist strap before handling any circuits so that
32-120O F and at a relative humidity of 85% RH (non-condensing) at static charges are removed from the body. Use static suppressive
30O C/86O F. However, the useful life of the system's standby batteries packaging to protect electronic assemblies removed from the unit.
and the electronic components may be adversely affected by extreme Follow the instructions in the installation, operating and
temperature ranges and humidity. Therefore, it is recommended that this programming manuals. These instructions must be followed to avoid
system and its peripherals be installed in an environment with a nominal damage to the control panel and associated equipment. FACP
room temperature of 15-27O C/60-80O F. operation and reliability depend upon proper installation.
Verify that wire sizes are adequate for all initiating device loops. Most
devices cannot tolerate more than a 10% I.R. drop from the specified
device voltage.
Fire Alarm System Limitations While installing a fire alarm system may make lower insurance
rates possible, it is not a substitute for fire insurance!
An automatic fire alarm system - typically made up of smoke Audible warning devices such as bells may not alert people if thes
detectors, heat detectors, manual pull stations, audible warning devices devices are located on the other side of closed or partly open doors o
and a fire alarm control with remote notification capability can provide are located on another floor of a building.
early warning of a developing fire. Such a system, however, does not
assure protection against property damage or loss of life resulting from a A fire alarm system will not operate without any electrical power. I
fire. AC power fails, the system will operate from standby batteries only fo
a specified time.
Any fire alarm system may fail for a variety of reasons:
Rate-of-Rise heat detectors may be subject to reduced sensitivity
Smoke detectors may not sense fire where smoke cannot reach the over time. For this reason, the rate-of-rise feature of each detector
detectors such as in chimneys, in walls, or roofs, or on the other side of should be tested at least once per year by a qualified fire protection
closed doors. Smoke detectors also may not sense a fire on another specialist.
level or floor of a building. A second floor detector, for example, may not
sense a first floor or basement fire. Furthermore, all types of smoke Equipment used in the system may not be technically compatible
detectors - both ionization and photoelectric types, have sensing with the control panel. It is essential to use only equipment listed fo
limitations. No type of smoke detector can sense every kind of fire service with your control panel.
caused by carelessness and safety hazards like smoking in bed, violent Telephone lines needed to transmit alarm signals from a premise to
explosions, escaping gas, improper storage of flammable materials, central monitoring station may be out of service or temporarily
overloaded electrical circuits, children playing with matches, or arson. disabled.
IMPORTANT! Smoke detectors must be installed in the same room as The most common cause of fire alarm malfunctions, however, is
the control panel and in rooms used by the system for the connection of inadequate maintenance. All devices and system wiring should be
alarm transmission wiring, communications, signaling and /or power. If tested and maintained by professional fire alarm installers following
detectors are not so located, a developing fire may damage the alarm written procedures supplied with each device. System inspection an
system, crippling its ability to report a fire. testing should be scheduled monthly or as required by National and/o
local fire codes. Adequate written records of all inspections should b
kept.
FCC Warning
WARNING: This equipment generates, uses and can radiate radio Canadian Requirements
frequency energy and if not installed and used in accordance with the This digital apparatus does not exceed the Class A limits for radiatio
instruction manual, may cause interference to radio communications, It noise emissions from digital apparatus set out in the Radio
has been tested and found to comply with the limits for class A Interference Regulations of the Canadian Department of
computing device pursuant to Subpart B of 15 of FCC Rules, which is Communications.
designed to provide reasonable protection against such interference
when operated in a commercial environment. Operation of this Le present appareil numerique n'emet pas de bruits radioelectriques
equipment in a residential area is likely to cause interference, in which depassant les limites applicables aux appareils numeriques de la
case the user will be required to correct the interference at his own classe A prescrites dans le Reglement sur le brouillage
expense. radioelectrique edicte par le ministere des Communications du
Canada.
Additional Information
Before proceeding, the installer should be familiar with the following documents and
standards:
NFPA Standards:
NFPA 12 CO2 Fire Extinguishing Systems
NFPA 12A Halon 1301 Fire Extinguishing Systems
NFPA 12B Halon 1211 Fire Extinguishing Systems
NFPA 72 Installation, Maintenance and Use of Central Station Signaling Systems
NFPA 72 Local, Auxiliary, Remote Station and Proprietary Fire Alarm Systems
NFPA 72 Automatic Fire Detectors
NFPA 72 Installation, Maintenance and Use of Notification Appliances for Fire Alarm Systems
NFPA 72 Testing Procedures for Signaling Systems
NFPA 2001 Clean Agent Fire Extinguishing Systems
Other:
NEC Article 300 Wiring Methods
NEC Article 760 Fire Alarm Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction
Notifier Device Compatibility Document, 15378
ADA Americans with Disabilities Act
1 The PDRP-1002/PDRP-1002E
Features
• Microprocessor-controlled
• Power-limited on all circuits except Municipal Box output
• Alarm and trouble resound
• Four Class A (Style D)/Class B (Style B) Initiating Device Circuits
• Two Class A (Style Z)/Class B (Style Y) Notification Appliance circuits
• Two Class B (Style Y) Release Circuits
• General alarm and trouble relays
• Optional module for 4 zone/function relays (4XZM)
• Optional transmitter module (4XTM). Complies with NFPA 72 Auxiliary and
Remote Station Fire Alarm systems
• Optional volt/amp meter module (4XMM)
• Optional supervised remote annunciator (RZA-4X)
• Requires LED Interface Module (4XLM)
• Optional digital communicator (NOTI•FIRE 911AC)*
• Complies with NFPA 72 Central Station and Remote Station Fire Alarm Systems
• Supervisory Input Option
• Delay timer (adjustable)
• Three abort function options
• Designed for suppression standards NFPA 12, 12A and 12B
• Disable/enable controls per initiating zone
• Last Event Recall
• Battery/Earth fault supervision
• Fuse protection on all Notification/Release Circuits
• RMS regulated output power, 2.25 amps
• 7 amp/hour to 15 amp/hour battery options, up to 90 hours standby
• Resettable and non-resettable regulated power outputs
• Extensive transient protection
• Watchdog timer to supervise microprocessor
• Output circuits protected against false activations
• Slide-in zone identification labels
• Steel cabinet 14.5 in (368.3 mm) wide by 16 in ( 406.4 mm) high by 5 in (127 mm)
deep
• Dead-front dress panel option (DP-4X)
• Trim ring for flush mount between 16 in (406.4 mm) center studs (TR-4XR)
• Abort and manual release circuits
• Cross-zone option
Circuits
Input Circuits
Detector Zone 1, Class A (Style D)/Class B (Style B)
Detector Zone 2, Class A (Style D)/Class B (Style B)
Abort, Class A (Style D)/Class B (Style B)
Manual Release, Class A (Style D)/Class B (Style B)
NON-RESETTABLE
RMS-REGULATED
Notification Appliance Initiating Device
Releasing
RESETTABLE
Circuits
REGULATED
REGULATED
Circuits Relays
Class A (Style Z) Circuits Class A (Style D) Abort Manual
24 VVU Switch Release
24 VNR
Class B (Style Y) Alarm Trouble Class B (Style B)
24 VR
1 2 3 4 Contacts Contacts 1 2 3 4
+24VU +24VR +24VNR
+ - + - + - B+ A+ A- B- B+ A+ A- B- B+ B- B+ B- NO NC C NO NC C B+ A+ A- B- B+ A+ A- B- B+ A+ A- B- B+ A+ A- B-
TB1 TB4
TB2 TB3
JP 1 NO DACT
DACT
SUPV 2
4XTM
GEN ALM2
or
J1 Transformer
4XLM
AC Circuit Breaker
or
4XZM
Ground TB5
OPT 2*
O1 2 3 4 5 6
N
BATT EARTH SW1
Cross Zone Abort Option
Supervisory Abort Option Micro Fail LED
Battery Fail LED Ground Fault LED Delay Timer Delay Timer
Optional Boards
The PDRP-1002/PDRP-1002E has mounting slots for two option boards. Any two of
the three option modules may be installed.
4XTM.cdr
LED Interface Module (4XLM - NOTIFIER)
The LED Interface Module supports the RZA-4X Remote
Annunciator module. Annunciator wiring is supervised for
open conditions by this module. The Annunciator Driver
Module mounts to the main board, occupying one of the
two option connectors.
4XLM.cdr
Zone Relay Module (4XZM - NOTIFIER)
The Zone Relay module provides Form-C contacts for the
following:
Remote Annunciator
Remote Annunciator (RZA-4X - NOTIFIER)
The Remote Annunciator mounts on a standard single-
gang box, and provides LED indication of the same
functions as the zone relay module. For example with
DIP 1=ON and DIP 2=OFF:
• One Zone in Alarm (red)
• Two Zones in Alarm (red)
• Releasing Circuit 1 (red)
• Releasing Circuit 2 (red)
• System Trouble (yellow)
A Local Trouble Sounder and Silence Switch are also
provided. All LED wiring is supervised for open
RZA4Xfr.cdr
conditions. Any open condition will cause the System
Trouble LED to illuminate.
Note: The Remote Annunciator requires the use of an LED Interface module (4XLM).
Optional Meters
Voltage, Current Meters (4XMM - NOTIFIER)
The Meter Module provides a voltmeter to measure the
10 20
DC AMPERES
voltmter.cdr
Specifications
AC Power
For the PDRP-1002: 120 VAC, 50/60 Hz, 1.2 amps AC Circuit
For the PDRP-1002E: 220/240 VAC, 50 Hz, 0.6 amps Breaker
Wire size: minimum #14 AWG with 600V insulation
Battery (lead acid only)
Maximum Charging Circuit: 27.6V, 1.5 amps
Maximum Battery Capacity: 15 AH. (Batteries larger
Acctbrkr.cdr
than 12 AH require NOTIFIER #BB-17 or other UL
listed external battery cabinet.)
Initiating Device Circuits
Power-limited circuitry
Operation: Class A (Style D)/Class B (Style B)
Normal Operating Voltage: 24 VDC (ripple = 1.0V peak-to-peak)
Alarm current: 15 mA minimum
Short circuit current: 40 mA maximum
Maximum detector current in standby: 2 mA (max) per zone
Maximum loop resistance: 200 ohms
End-of-line resistor: 4.7K, 1/2-Watt (NOTIFIER part # 71252, UL listed)
Detector loop current is sufficient to ensure operation of one alarmed detector per zone.
Supervisory current: 5 mA (including end-of-line resistor)
Notification Appliance and Releasing Circuits
Power-limited circuitry
Maximum allowable voltage drop due to wiring: 2 VDC
Normal Operating Voltage: 24 VDC
Total current available to all external devices: 2.25 amps
Maximum signaling current per circuit: 1.5 amps
End-of-line resistor: 4.7K, 1/2-Watt (NOTIFIER part # 71252, UL listed)
Alarm and Trouble Relays
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC
(resistive). All relays must be connected to a power limited power supply.
Four-wire Smoke Detector Power
Up to 200 mA is available for powering 4-wire smoke detectors.
Maximum ripple voltage: 1.0 V p/p
Non-resettable Power
Total DC current available from this output is up to 200 mA (subtracted from 4-wire
smoke power).
Maximum ripple voltage: 1.0 V p/p
RMS Regulated Power
Total DC current available for powering external devices is 0.5 amp (subtracted from
2.25 amps available to notification appliance circuits).
Maximum ripple voltage: 100 mV p/p
Note: For device compatibility, refer to Device Compatibility Chart.
1.5 in
(38.1 mm)
TR-4XR
RUBY RD
STEEL
16 GA.
16.094 in.
(408.79 mm)
14.594 in.
(370.69 mm)
RPCABDIM.cdr
2 System Operation
WARNING:When used for CO2 releasing applications, observe proper
precautions as stated in NFPA 12. Do not enter the protected space unless physical
! lockout and other safety procedures are fully completed. Do not use software
disable functions in the panel as lockout.
AC POWER
Green LED that illuminates steadily to
indicate presence of AC power.
SYSTEM ALARM
Red LED that flashes when an alarm
occurs.
RELEASE
Red LED that illuminates steadily when
release occurs.
SUPERVISORY
Yellow LED that flashes upon activation of
a supervisory device (such as tamper
switch) on Output 4 if selected (see
“Setting Mode of Operation” in Section 3
4Xoper2.cdr
of this manual).
BATT EARTH MICRO
FAIL
SYSTEM TROUBLE
Yellow LED that flashes for any trouble
condition, including those associated with option boards.
CIRCUIT TROUBLE
Yellow LED that flashes for trouble conditions on output circuits (notification and
releasing circuits).
ALARM SILENCED
Yellow LED that illuminates steadily when the ALARM SILENCE switch has been
pushed after an alarm.
POWER TROUBLE
Yellow LED that flashes for low or disconnected batteries and earth fault conditions.
BATT
Yellow LED that illuminates steadily on motherboard when battery is low or not
detected (not visible through door).
EARTH
Yellow LED that illuminates steadily on motherboard during a ground fault condition
(not visible through door)
MICRO FAIL
Yellow LED that illuminates on motherboard when watchdog timer detects
microprocessor failure (not visible through door)
Control Switches
Tone Silence
Acknowledge alarms, troubles and
supervisories. The panel has alarm and
trouble resound with LED flash of new
conditions. The flashing trouble LED(s)
illuminate steadily on TONE SILENCE and
the piezo sounder silences. A second trouble
will resound the piezo. The piezo has three
sounds for alarm, trouble, and supervisory.
Trouble conditions are self-restoring. Alarms
latch and require RESET to clear.
4XPTL.cdr
Alarm Silence
Acknowledge for alarms and supervisories.
The ALARM SILENCE switch will silence
the local piezo, change any flashing alarm
LEDs to steady, and turn off the notification
circuits (not the releasing circuits). The
“ALARM SILENCED” LED will illuminate.
Alarm silence is a latching function and
requires a RESET to clear.
Alarm Activate
The ALARM ACTIVATE switch may be used
to activate Notification Appliance Circuits.
ALARM ACTIVATE also activates the
System Alarm relay. ALARM Activate is a
latching function. Pressing ALARM
SILENCE silences the notification circuits
and System Alarm Relay and lights the Alarm
Silenced LED. Pressing RESET returns the
system to normal.
System Reset
The RESET switch breaks power to all
initiating circuits, 4-wire smoke power and
option boards and will clear any activated
output circuits. If any alarms or troubles still
exist after reset, they will reactivate the panel.
Holding RESET down will perform a LAMP
TEST function and will activate the piezo sounder.
Supervisory
Output circuit #4 is used as an input for monitoring supervisory devices such as valve
tamper switches (note that SW1 DIP switch #2 must be set “ON” -- see section “Setting
Mode of Operation”) By setting Switch short circuit on this input (activation of a N.O.
contact) will cause the supervisory LED to flash. The piezo sounder will generate a
unique sound. TONE SILENCE will silence the piezo and cause the LED to illuminate
steadily. Supervisory signals latch and require RESET to clear. An open circuit will be
reported as a circuit trouble.
Zone Disable
If a zone has been disabled, an alarm
that occurs on that zone will flash the
red zone LED, but not the piezo or any
output circuit. If both power sources
are removed from the system, all zones
will be re-enabled upon restoration of
power. Disable status will be lost.
The Zone Disable routine makes use of
the four panel switches as follows:
1. Press and hold in the TONE
SILENCE switch.
2. With the TONE SILENCE switch
held in, press (in sequence) the
4XPTL.cdr
ALARM SILENCE switch, the
ALARM ACTIVATE switch, and
then the RESET switch.
3. The Zone 1 Alarm LED will flash.
4. To disable Zone 1, press the RESET switch. The Zone 1 yellow LED will light to
show that the zone is disabled.
Note: The RESET switch toggles disable status for the selected zone.
If any zone has been disabled, the trouble relay will activate and System Trouble LED
will flash.
3 Installation Procedure
General
Carefully unpack the system and check for shipping damage. Mount the cabinet in a
clean dry, vibration-free area in which extreme temperatures are not encountered. The
location should be readily accessible with sufficient room for easy installation and
maintenance. Locate the top of the cabinet approximately five feet above the floor with
the hinge mounting on the left. Determine the number of conductors required for the
devices to be employed. Pull required conductors into the box through the knockout
provided. All wiring should be in accordance with the National and/or Local codes for
fire alarm systems.
Power Limited
Non-Power
Circuits Power Limited
Limited Circuits
Circuits
AC Power
Power Limited
Circuit
4XZM
Non-Power
PC Board Limited Circuit
RP1002PL.cdr
Class B (Style B)
Initiating Device Circuit
4.7K, 1/2-Watt (part # 71252 UL listed)
Class A (Style D)
Initiating Device
Two-wire
+ _ Circuit_
Smoke +
Detector Abort Switch Manual Release
4.7K, 1/2-Watt 4.7K, 1/2-Watt
+ _ _
Manual +
Pull Station
TB4
B+ A+ A- B- B+ A+ A- B- B+ A+ A- B- B+ A+ A- B-
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
AIDEX.cdr
IN #1 IN #2 IN #3 IN #4
- - - -
IDC (-) IDC (-)
UL listed
4.7K, 1/2-Watt
Listed
UL listed 24 VDC ELR
Power
Four-wire Smoke Detectors Supervision
Relay
TB1 TB4
+ - B+ A+ A- B-
1 2 3 4 1 2 3 4
RP4WR.cdr
+24VR IN #1
Class B Initiating Device Circuit
A maximum of 200mA is available from the +24VDC
4-wire smoke detector power circuit on TB1 terminals 3 Initiating Device Circuits 1,2,3, or 4
and 4. Any power that is drawn from the +24VDC Non- can be used. Class A (Style D) wiring
resettable Power on TB2 terminals 1 and 2 must be can also be employed.
subtracted from available 4-wire detector power. (See
“Specifications” and “Power” sections.)
Output Circuits
Notification Appliance Circuits
This control panel can provide two Class A (Style Z)/Class B (Style Y) Notification
Appliance Circuits and two Class B (Style Y) Releasing Circuits (see section “Setting
Mode of Operation” for DIP switch configuration). Each circuit is capable of 1.5 amps
of current. Total current drawn from all four circuits cannot exceed 2.25 amps. Refer
to the Compatibility Chart. Circuits are supervised and power-limited.
Note: Wiring must be configured to maintain a minimum voltage of 20.4V on release circuits. Calculation of
maximum allowable resistance:
RMAX = 20.6V-20.4V
________________________________________________________________________
IS
Where: RMAX = maximum allowable resistance of wiring
IS = solenoid current
Polarized Bell + - + -
Releasing Circuits
Polarized Horn +- +-
No Connection
No Connection
B+ A+ A- B- B+ A+ A- B- NC B+ B- NC B+ B-
TB2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
OUT #1 OUT #2 OUT #3 OUT #4
See note
below
Note: Output #4 can be configured for releasing or supervisory circuit (see Section “Setting Mode of Opera
configured as a releasing circuit, the circuit will be non-power limited. If configured as a supervisory circuit,
will be power limited. All wiring must follow the power limited “General” Section.
Alarm Relay
One Form-C dry alarm contact is provided in the basic panel for controlling
supplementary devices. It is rated 2 amps at 30 VDC and 0.5 amps at 30 VAC
(resistive), and is non-silenceable when an alarm occurs. See below for terminal
location.
Trouble Relay
One Form-C dry trouble contact is provided in the basic panel for controlling
supplementary devices. It is rated 2 amps at 30 VDC and 0.5 amps at 30 VAC
(resistive), and will silence when trouble condition is cleared. See below for terminal
location.
Note: The alarm and trouble Form-C dry contact relays must be power limited relays. They must be wired
from one of the 24V power limited terminals as shown in the figure below or a comparable UL listed power
limited power supply.
Alarm Trouble
NO NC C NO NC C
or or
TB1 TB2 TB3
RPALMTBL.CDR
1 2 3 4 1 2 1 2 3 4 5 6
Alarm Trouble
Schematic representation of
Alarm/Trouble coils and contacts.
Figure 7 Alarm/Trouble Coils and Contacts
Power
CAUTION: Several different sources of power can be connected to this panel.
! Disconnect all sources of power before servicing. The panel and associated equipment
may be damaged by removing and/or inserting cards, modules, or interconnecting
cables while this unit is energized.
This output is not suitable The combined current draws from the Resettable
for powering devices and Non-resettable outputs cannot exceed 200 mA.
requiring filtered DC power.
TB 1 TB 2
1 2 3 4 1 2
AC Power
Primary power required for the PDRP-1002 panel is 120 VAC, 50/60 Hz, 1.2 amps and
primary power for the PDRP-1002E is 220/240 VAC, 50 Hz, 0.6 amps. Overcurrent
protection for this circuit must comply with Article 760 of the National Electrical Code
(NEC) and/or local codes. Use #14 AWG (2.00 mm2)or larger wire with 600 volt rating.
Battery Power
Observe polarity when connecting battery. Connect battery cable to J9 on the main
board using the plug-in connector provided. See Appendix A for calculation of correct
battery rating.
CAUTION: Batteries contain sulfuric acid which can cause severe burns to the skin and
! eyes, and can destroy fabrics. If contact is made with sulfuric acid, immediately flush
skin or eyes with water for 15 minutes and seek immediate medical attention.
Voltmeter/Ammeter
To monitor battery voltage and battery charging current, a 4XMM (NOTIFIER) is
required. To install the power meter module, remove the jumper labeled “AMP” and
connect cable assembly P2 to pin connector J2 and cable assembly P3 to pin connector
J3 on the main board. Secure the 4XMM to the backbox with the two screws provided.
On some models, it will be necessary to install the meter bracket with the nuts and bolts
provided.
P2
J2
J9
P3
J3
10 20
0 30
DC VOLTS
0
5 5
DC AMPERES
RPMBVM.cdr
Optional Modules
The fire control panel has two module connectors - J5 and J8. Three modules are
available for the panel and they can be used in any combination, including duplicate
modules. The corresponding option jumper must be cut before installation of an
optional module.
Transformer
J4
*Jumper “OPT 1”
Ground J5 must be cut if a
Neutral
module is
installed in this
Hot
position
Optional Ammeter
Connection
Batteries
Optional
VoltmeterConnection
*Jumper “OPT 2”
J7 must be cut if a
module is
J8 installed in this
position
4XRP102a.cdr
Cross Zone Abort Option
Supervisory Abort Option Micro Fail LED
Battery Fail LED Ground Fault LED Delay Timer Delay Timer
Note:
• Optional 4XLM module for an RZA-4X Annunciator must be installed on J7 and J8 only.
• 4XTM and 4XZM modules can be installed in either location.
(Part # 42050)
Stand-offs)
Main
Option Board Board
(4XZM shown)
4XSTNOFF.cdr
4XOPTNBD.cdr
1 + } Remote Alarm
2 - Power Limited Circuit
3 + Remote Trouble
4 -}
5 No Connection
6 + Municipal Box*
-}
Non-Power Limited Circui
7
TBL Jumper
* Dummy load terminals
6 and 7 (4.7K, 1/4 W
Disconnect LED resistor) if Municipal
Box is not connected.
4XTBa.cdr
Disconnect Switch
Push the disconnect switch down to prevent unwanted activation of the Municipal Box
and Remote Station Outputs during testing of the control panel. The Disconnect LED
will remain illuminated while the Municipal Box is disconnected. The System Trouble
LED will indicate disconnected and/or Open Circuit conditions on the Municipal box.
Cutting the TBL jumper will allow the alarm reverse polarity circuit to open on trouble,
if no alarm exists.
Note: Remote Alarm, Remote Trouble, and Municipal Box wiring can leave the building.
1 NO
2 NC Relay #1
3 C
4 NO
5 NC Relay #2
6 C
7 NO
8 NC Relay #3
9 C
10 NO
11 NC Relay #4
12 C
13 NO
14 NC Alarm
15 C
16 NO
17 NC Trouble
18 C
4XZMA.cdr
1) Skip a set of dry contacts to maintain the 0.25 in (6.35 mm) required space
between power limited and non-power limited circuits. The wiring of this module must
follow the requirements as specified in the “General” section, “UL Power Limited
Wiring Requirements.”
OR
2) If this module is needed to drive power limited and non-power limited relays that
are next to each other, refer to the figure below showing a typical connection.
NO
Relay #1 NC Power Limited Circuit
C
NO
Relay #2 NC Power Limited Circuit
C
NO No Connection
Relay #3 NC Non-power Limited Circuit
C
NO
Relay #4 NC
4XZMptl.cdr
Note: Refer to the Protected Premises Unit label, located on the door of the control panel, to
indicate if any dry contacts are to be used as non-power limited dry contacts.
1 +24V
2 Out#1
3 Out#2
4 Out#3
5 Out#4
6 System Trouble
7 Sound
8 Resound
4XLMa.cdr
Connect to corresponding terminals
of RZA-4X Remote Annunciator.
RZA4XBX.cdr
RZA4Xfr.cdr
4XRPDIPS.cdr
O1 2 3 4 5 6
N
Battery Fail
Micro Fail LED
LED
Ground Fault LED O 1 2 3 4 5 6
N
DIP Switches
Switch 3: DELAY TIMER
Switch 4: DELAY TIMER
Switch 1: CROSS ZONE
Switch 5: ABORT OPTION
Switch 2: SUPERVISORY
Switch 6: ABORT OPTION
Note: The Reset key must be depressed after any switch configuration has been made.
Cross Zone
Select the desired mode of operation and set SW1 DIP switch 1.
Switch 1 OFF ON
Outputs 3 and 4 will be activated when the timer expires (provided that
Output 4 is functioning as a releasing circuit - set via DIP Switch 2).
The Timer will start whenever an The Timer will start when alarms
alarm occurs on either Zone 1 or occur on both Zone 1 and Zone 2.
Zone 2.
Note: Outputs 1 and 2 refer to Notification Appliance Circuits. Output 3 refers to a releasing circuit. Output
4 is determined by setting switch 2. Zones 1 and 2 refer to Initiating Device Circuits.
Switch 2 OFF ON
Timer
Select the desired Timer setting and set SW1 DIP switches 3 and 4 per the appropriate
column.
Abort Function
Select the desired abort functions and set SW1 DIP switches 5 and 6 per the appropriate
column.
Note: ABORT timer will not operate when timer is set for “NO DELAY”.
Ampere-Hour Calculations
Total amp/
Add Standby and Alarm amp/hours = hours needed
Notes:
1. Alarm amp-hours assumes a maximum system draw of 3 amps in alarm for 5
minutes (0.25 amp/hour) or for 10 minutes (0.5 amp/hour)
2. NFPA 72 Central Station and Local and Proprietary Fire Alarm Systems require 24
hours of standby.
3. NFPA 72 Auxiliary and Remote Station Fire Alarm Systems require 60 hours of
standby.
4. Factory Mutual Systems require 90 hours of standby.
5. The battery charger in this panel will charge a maximum of 15 amp/hours of
batteries within 48 hours (7 amp/hour minimum). Batteries larger than 12 amp/
hour will require a UL listed battery cabinet (e.g. NOTIFIER BB-17).
8 in. orifice.
Solenoid Group [C]
Star Sprinkler Corp. Solenoid P/N 5550, 24 VDC, part of Model D deluge valve.
Kidde-Fenwal Electric Control Head P/N 890181; 24V, 2.0 Amps
Kidde-Fenwal Electric Control Head P/N 899175; 24V, 2.0 Amps
Kidde-Fenwal Electric Control Head Stackable (XP) P/N 48650001; 24V, 0.2 Amps
Kidde-Fenwal Electric and Cable Op Control Head (XP) P/N 897494; 24V, 1.5 Amps,
33 Watts
Refer to the FM approval guide for automatic water control valves which are
compatible with solenoids listed above.
System Sensor MASS24LOLA Electronic Sounder/Strobe with Fuego lens 24VDC 118 71
System Sensor SS2415ADAS Signaling Strobe with Synch. Circuit 24 VDC 125 106
System Sensor SS241575ADAS Signaling Strobe with Synch. Circuit 24 VDC 180 115
System Sensor MASS2415ADAS Sounder/Signaling Strobe w/ Synch. Ckt. 24 VDC 163 121
System Sensor MASS241575ADAS Sounder/Signaling Strobe w/ Synch. Ckt. 24 VDC 193 139
System Sensor SP100W24MC Ceiling Speaker/Strobe, 8" round grille 24VDC 125 75
System Sensor MA12/24EH Multi Alert Horn with Mechanical Tone 12VDC/ 20/64 38/43
24VDC
System Sensor MAEH24LO Multi Alert Horn with Mechanical Tone/Strobe 24VDC 109 68
System Sensor MAEH24LOC Multi Alert Horn with Mechanical Tone/Strobe 24VDC 109 68
System Sensor MAEH24LOLA Multi Alert Horn with Mechanical Tone/Strobe 24VDC 153 96
System Sensor MAEH24M Multi Alert Horn with Mechanical Tone/Strobe 24VDC 189 118
System Sensor MAEH24MC Multi Alert Horn with Mechanical Tone/Strobe 24VDC 189 118
System Sensor MAEH1215ADA Multi Alert Horn with Mechanical Tone/Strobe 12VDC 240 191
System Sensor MAEH121575ADA Multi Alert Horn with Mechanical Tone/Strobe 12VDC 310 246
System Sensor MAEH2415ADA Multi Alert Horn with Mechanical Tone/Strobe 24VDC 278 216
System Sensor MAEH2475ADA Multi Alert Horn with Mechanical Tone/Strobe 24VDC 273 216
System Sensor MAEH241575ADA Multi Alert Horn with Mechanical Tone/Strobe 24VDC 343 271
System Sensor MAEH24110ADA Multi Alert Horn with Mechanical Tone/Strobe 24VDC 318 256
System Sensor MAEH2415ADAS Multi Alert Horn with Mechanical Tone/Strobe 24VDC 198 152
System Sensor MAEH241575ADAS Multi Alert Horn with Mechanical Tone/Strobe 24VDC 253 241
Note:
1) Control panels suppling Special Application (FWR, Filtered) power must use the notification appliances,
relays or door holders listed in this table.
2) All currents are in Millamperes and worst case average.
3) Nominal Operating voltage.
4) Refer to Installation Instructions for more information.
5) Contact manufacturer for currents.
Number of
Detectors Per Zone
Table 7 UL Listed, Compatible Two-Wire Smoke Detectors for Notifier Control Panels
The following additional equipment is needed for compliance with the NFPA standards
listed below.
NFPA 72 Signaling Systems for Central Station Service (Protected Premises Unit)
NOTI•FIRE 911AC DACT* - for connection to a compatible listed Central Station
DACR or Protected Premises Receiving Unit. This unit must be installed as outlined in
Figure 13.
NFPA 72 Auxiliary Fire Alarm System
4XTM Transmitter Module for connection to a compatible listed Local Energy
Municipal Box. This unit must be installed as outlined in Figure 15.
NFPA 72 Remote Station Fire Alarm System
4XTM Transmitter Module for connection to Fire•Lite RS82-9 Remote Station
Receiver. See Figure 16 for installation instructions.
OR
NOTI•FIRE 911AC DACT* - For connection to a compatible listed remote station
DACR. This unit must be installed as outlined in Figure 13.
*Applications which require the NOTI•FIRE 911AC are not FM approved.
of a supervisory signal to 7
8
9
5
6
7
B AT TE RY +
INI T IAT IN G A1 -
INI T IAT IN G A2 -
+
R e c h a rg e ab le
B a tt e ry
8 INI T IAT IN G B1 +
10 A lte rn a te R J3 1 X
the DACT 11
12
9
10
11
12
INI T IAT IN G B2 +
S U PE RV IS OR Y H I
S U PE RV IS OR Y LO
T ROU B L E R EL AY N C
Te l co Ja c k
13 T ROU B L E R EL AY C O M
14 T ROU B L E R EL AY N O
P ri ma r y R J 31 X
15 A LA R M R ELAY N C Te l co Ja c k
16 A LA R M R ELAY C OM
17 A LA R M R ELAY N O
To AC -+
Power PS1270
12Volt
7AH Battery
Alarm
To Central Station
JP-1
STD DACT
Motherboard 911AC
Alarm TB3-1 6 and 7
normally open
contacts
TB3-3 8 and 9
RP911AC.CD
Trouble TB3-4 10
normally open
TB3-6 11
contacts
Secondary
Phone Line
Modular Cable Primary
P/N MCBL-6 Phone Line
MS-5012
Alarm
TB2
J2
J3
Trouble
AC POWER TROUBLE
ALARM SUPERVISORY
1 2 3 F
TB3
4 5 6 E
1st
7 8 9 D EVENT
A O B C ENTER
STORE
Red
Yellow
120 VAC
Black
HOT
Yellow 12VDC
Neutral Battery
Black 2-7AH
Ground White
Green
Motherboard MS-5012
MS5012X2.CDR
TB3-1 TB2-2
Alarm 12 3 4 5 6
TB3-3 TB2-1 TB3
PDRP-1002/PDRP-1002E
TB3-4 TB2-4
Trouble
TB3-6 TB2-3
+ FIRE
Municipal Box Circuit
AUXPROSS.CDR
4XTB
+ - Gamewell
Model M34-56
6 Local Energy
Municipal Box
7
4XTM (NOTIFIER)
Transmitter Module
(activated polarities
shown)
13
BELLS AND
DRY
CONTACTS
5A
125 V
7
6
}50-60 Hz Receiver
RESISTIVE POLE 1
INPUT UL listed
14 5 N/C
BATT +
CONTROL CARD K
CONN
(RSC) -
CIRCUIT SIDE FILTER
BELL
CAP 4 H 10 K
REMOTE STATION or
ELR
MASTER BOARD 3 HORN
(RSM-9) 2
ZONE CARD(RSZ)
CIRCUIT SIDE 1
2
OPTIONAL ZONE CARD
(RSZ) CIRCUIT SIDE 1
ALARM
OPTIONAL ZONE CARD
2
1
} SIGNAL
INPUT 3
(RSZ) CIRCUIT SIDE
ALARM
OPTIONAL ZONE CARD
2
1
} SIGNAL
INPUT 4
(RSZ) CIRCUIT SIDE
ALARM
OPTIONAL ZONE CARD
2
1
} SIGNAL
INPUT 5
(RSZ) CIRCUIT SIDE
1
} ALARM
SIGNAL
(RSZ) CIRCUIT SIDE INPUT 6
ALARM
OPTIONAL ZONE CARD
2
1
} SIGNAL
INPUT 7
+ - + -
(RSZ) CIRCUIT SIDE ALARM
1
} SIGNAL
INPUT 8
(RSZ) CIRCUIT SIDE ALARM
2
1
} SIGNAL
INPUT 9
OPTIONAL ZONE CARD
(RSZ) CIRCUIT SIDE
K | | | | | | | | | | K
Recommended Types:
ELPOWER EP 1250C
+ POWER SONIC PS 1245
Power Transformer POWER SONIC PS 1260
POWER SONIC PS 1265
YUASA NPG-12
or equivalent
- MAXIMUM BATTERY SIZE
6.0 X 2.6 X 4.1 in. (15.24 x 6.6 x10.41
1
Remote Alarm
2
3 Remote Trouble
4
REMPROSS.CDR
4XTM (NOTIFIER)
Transmitter Module
(activated polarities shown)
Troubleshooting Table
Notes
Notes
Limited Warranty
System Sensor® warrants its products to be free from defects in materials and
workmanship for eighteen (18) months from the date of manufacture, under normal
use and service. Products are date stamped at time of manufacture. The sole and
exclusive obligation of System Sensor® is to repair or replace, at is option, free of
charge for parts and labor, any part which is defective in materials or workmanship
under normal use and service. For products not under System Sensor®
manufacturing date-stamp control, the warranty is eighteen (18) months from date of
original purchase by System Sensor® distributor unless the installation instructions
or catalog sets forth a shorter period, in which case the shorter period shall apply.
This warranty is void if the product is altered, repaired or serviced by anyone other
than System Sensor® or its authorized distributors or if there is a failure to maintain
the products and systems in which they operate in proper and workable manner. In
case of defect, phone System Sensor® Repair Department, RA #_____________,
3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the
malfunction and suspected cause of failure.
This writing constitutes the only warranty made by System Sensor® with respect to
its products. System Sensor® does not represent that its products will prevent any
loss by fire or otherwise, or that its products will in all cases provide the protection for
which they are installed or intended. Buyer acknowledges that System Sensor® is
not an insurer and assumes no risk for loss or damages or the cost of any inconve-
nience, transportation, damage, misuse, abuse, accident or similar incident.
This warranty replaces all previous warranties and is the only warranty made by
System Sensor®. No increase or alteration, written or verbal, of the obligation of this
warranty is authorized.
System Sensor
3825 Ohio Avenue, St. Charles, IL 60174
1-800-SENSOR2 Fax: 630-377-6495