Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

SK 5208

Download as pdf or txt
Download as pdf or txt
You are on page 1of 118

MODEL SK-5208

Fire Control/
Communicator

Installation and
Operations Manual Part Number 151204 Rev L

Downloaded from www.Manualslib.com manuals search engine


Downloaded from www.Manualslib.com manuals search engine
Installation Procedure

Adherence to the following will aid in problem-free installation with long-term reliability:

Installation Precautions - Adherence to the following will aid in problem-free installation


with long-term reliability: WARNING - Several different sources of power can be connected
to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit
and associated equipment may be damaged by removing and/or inserting cards, modules, or
interconnecting cables while the unit is energized. Do not attempt to install, service, or operate
this unit until manuals are read and understood. CAUTION - System Re-acceptance Test after
Software Changes: To ensure proper system operation, this product must be tested in
accordance with NFPA 72 after any programming operation or change in site-specific
software. Re-acceptance testing is required after any change, addition or deletion of system
components, or after any modification, repair or adjustment to system hardware or wiring. All
components, circuits, system operations, or software functions known to be affected by a
change must be 100% tested. In addition, to ensure that other operations are not inadvertently
affected, at least 10% of initiating devices that are not directly affected by the change, up to a
maximum of 50 devices, must also be tested and proper system operation verified. This
system meets NFPA requirements for operation within the range of 0°C-49°C (32°F-120°F) or
humidity within the range of 10%-93% at 30°C (86°F) noncondensing. However, the useful
life of the system's standby batteries and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore, it is recommended that this system
and its peripherals be installed in an environment with a normal room temperature of 15-27º
C/60-80º F. Verify that wire sizes are adequate for all initiating and indicating device loops.
Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged
when subjected to lightning induced transients. Although no system is completely immune
from lightning transients and interference, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to
nearby lightning strikes. Consult with the Technical Services Department if any problems are
anticipated or encountered. Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits. Remove all electronic
assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible,
make all cable entries from the sides or rear. Before making modifications, verify that they
will not interfere with battery, transformer, or printed circuit board location. Do not tighten
screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in
reduced terminal contact pressure and difficulty with screw terminal removal. Silent Knight
fire alarm control panels contain static-sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are removed from the
body. Use static suppressive packaging to protect electronic assemblies removed from the
unit.
Follow the instructions in the installation, operating, and programming manuals. These
instructions must be followed to avoid damage to the control panel and associated equipment.

151286 -1

Downloaded from www.Manualslib.com manuals search engine


VIP-Series Voice Integration Package Installation/Operation Manual

FACP operation and reliability depend upon proper installation.


While installing a fire alarm system may make lower insurance rates possible, it is not a
substitute for fire insurance! An automatic fire alarm system - typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm
control with remote notification capability - can provide early warning of a developing fire.
Such a system, however, does not assure protection against property damage or loss of life
resulting from a fire. Any fire alarm system may fail for a variety of reasons: Smoke
detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in
walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire
on another level or floor of a building. A second floor detector, for example, may not sense a
first floor or basement fire. Furthermore, all types of smoke detectors, including ionization
and photoelectric types, have sensing limitations. No type of smoke detector can sense every
kind of fire caused by carelessness and safety hazards like smoking in bed, violent explosions,
escaping gas, improper storage of flammable materials, overloaded electrical circuits, children
playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and
in rooms used by the system for the connection of alarm transmission wiring,
communications, signaling, and/or power. If detectors are not so located, a developing fire
may damage the alarm system, crippling its ability to report a fire. Audible warning devices
such as bells may not alert people if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building. A fire alarm system will not
operate without any electrical power. If AC power fails, the system will operate from standby
batteries only for a specified time. Rate-of-Rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested
at least once per year by a qualified fire protection specialist. Equipment used in the system
may not be technically compatible with the control. It is essential to use only equipment listed
for service with your control panel. Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service or temporarily disabled. The
most common cause of fire alarm malfunctions, however, is inadequate maintenance. All
devices and system wiring should be tested and maintained by professional fire alarm
installers following written procedures supplied with each device. System inspection and
testing should be scheduled monthly or as required by National and/or local fire codes.
Adequate written records of all inspections should be kept.

-2 151286

Downloaded from www.Manualslib.com manuals search engine


Contents

Contents

Section 1
Introduction .............................................................................................................................................. 1-1
1.1 Model SK-5208 Features ......................................................................................................................... 1-1
1.2 About This Manual .................................................................................................................................. 1-2
1.2.1 Optional Accessories ...................................................................................................................... 1-2
Limitations of Fire Alarm Systems ........................................................................................ 1-3

Section 2
Agency Listings and Requirements ........................................................................ 2-1

2.1 Federal Communications Commission (FCC) ......................................................................................... 2-1


2.2 Underwriters Laboratories (UL) .............................................................................................................. 2-2
2.2.1 Requirements for All Installations .................................................................................................... 2-2
Restricted Options: ................................................................................................................. 2-2
2.2.2 Requirements for Central Station Fire Alarm Systems .................................................................... 2-2
2.2.3 Requirements for Auxiliary Protected Fire Alarm Systems for Fire Alarm Service ........................ 2-2
2.2.4 Requirements for Remote Station Protected Fire Alarm Systems, for Digital Communication or
Polarity Reversal 2-2

Section 3
Control Panel Installation ...................................................................................................... 3-1

3.1 Electrical Specifications ........................................................................................................................... 3-1


3.2 Environmental Specifications .................................................................................................................. 3-1
3.3 Wiring Specifications ............................................................................................................................... 3-2
3.4 Control Board Components ..................................................................................................................... 3-3
3.5 Mounting the SK-5208 ............................................................................................................................. 3-5
3.5.1 Preventing Water Damage ................................................................................................................ 3-5
3.6 Current Draw Calculations ....................................................................................................................... 3-6
3.6.1 Worksheet Requirements .................................................................................................................. 3-6
Filling in the Current Draw Worksheet, Table 3-2 (Section 3.6.2) ....................................... 3-6
3.6.2 Current Draw Worksheet .................................................................................................................. 3-6
3.6.3 Maximum Battery Standby Load ...................................................................................................... 3-8
3.7 AC Wiring ................................................................................................................................................ 3-9
3.8 Backup Batteries .................................................................................................................................... 3-10
3.9 Terminal Strip Description ..................................................................................................................... 3-11
3.10 Telephone Line Connection .................................................................................................................. 3-13
3.11 Detector Installation ............................................................................................................................... 3-14
3.11.1 Class A (Style D) Zones ................................................................................................................. 3-14
3.11.2 Class B (Style B) Zones ................................................................................................................. 3-15
3.11.3 Four-Wire Smoke Detector Connection ......................................................................................... 3-16
3.11.4 Two-Wire Smoke Detector Connection ......................................................................................... 3-17
3.12 Supervised Notification Appliance Outputs ......................................................................................... 3-18
3.13 Auxiliary Relays .................................................................................................................................... 3-19

Downloaded from www.Manualslib.com manuals search engine


Contents

3.14 Accessory Devices ................................................................................................................................. 3-20


3.14.1 Setting ID Codes ............................................................................................................................. 3-20
3.14.2 Model SK-5235 Remote Annunciator ............................................................................................ 3-21
3.14.2.1 Mounting the SK-5235 Remote Annunciator ...................................................................... 3-21
3.14.2.2 Wiring the SK-5235 ............................................................................................................. 3-22
3.14.3 Model SK-5280 Status Display Module ......................................................................................... 3-23
3.14.3.1 Mounting the SK-5280 ......................................................................................................... 3-25
Mounting the SK-5280 into SK-5208 Cabinet .................................................................... 3-25
Mounting the SK-5280 into the SK-2190 Accessory Cabinet. ............................................ 3-26
3.14.3.2 Wiring Relays ...................................................................................................................... 3-27
3.14.3.3 Wiring LEDs to Outputs ...................................................................................................... 3-27
3.14.4 Model SK-5217 Zone Expander Installation .................................................................................. 3-28
3.14.4.1 Zone Inputs .......................................................................................................................... 3-29
3.14.4.2 Mounting Instructions .......................................................................................................... 3-30
Mounting the SK-5217 into SK-5208 Cabinet .................................................................... 3-30
Mounting the SK-5217 into the SK-2190 Accessory Cabinet. ............................................ 3-31
3.14.5 Model 5824 Installation Instructions .............................................................................................. 3-32
3.14.5.1 Mounting the 5824 Module .................................................................................................. 3-32
3.14.5.2 5824 SBUS Connections ...................................................................................................... 3-33
3.15 Special Applications .............................................................................................................................. 3-34
3.15.1 Model 5220 Direct Connect Module .............................................................................................. 3-34
3.15.1.1 City Box Connection ............................................................................................................ 3-34
3.15.1.2 NFPA 72 Polarity Reversal .................................................................................................. 3-35
3.15.2 Keltron 95M3158 Tones Transmitter Module ................................................................................ 3-36
3.15.3 Using a MR-201/T Control Relay From Air Products ................................................................... 3-37

Section 4
Programming ......................................................................................................................................... 4-1

4.1 Keypad Operation During Programming ................................................................................................. 4-1


4.1.1 Special Characters ............................................................................................................................. 4-2
4.1.2 Enabling Extended Programming List .............................................................................................. 4-2
4.2 Programming Flow .................................................................................................................................. 4-3
4.2.1 Zone Options ..................................................................................................................................... 4-4
4.2.2 Misc System Option .......................................................................................................................... 4-5
4.2.3 NAC Cadence ................................................................................................................................... 4-6
4.2.3.1 Cadence Patterns .................................................................................................................... 4-6
4.2.4 NAC Options .................................................................................................................................... 4-7
4.2.5 Relay Options ................................................................................................................................... 4-8
4.2.6 User Code ......................................................................................................................................... 4-9
4.2.7 Account ........................................................................................................................................... 4-10
4.2.8 Computer Options ........................................................................................................................... 4-11
4.2.8.1 Computer Code .................................................................................................................... 4-11
4.2.9 Line Options ................................................................................................................................... 4-12
4.2.10 Misc Reporting ............................................................................................................................... 4-13
4.2.11 5280 Outputs ................................................................................................................................... 4-14
4.2.12 5824 Expander Options .................................................................................................................. 4-15
4.2.13 DST/Clk Options ............................................................................................................................ 4-16
4.3 Programming Options ............................................................................................................................ 4-17

ii

Downloaded from www.Manualslib.com manuals search engine


Contents

Section 5
Operation ..................................................................................................................................................... 5-1

5.1 Installer & User Keys ............................................................................................................................... 5-1


5.2 On-board Touchpad and SK-5235 Operation .......................................................................................... 5-2
5.2.1 View Control Panel Firmware Number and Revision ...................................................................... 5-3
5.3 Acknowledge Operation .......................................................................................................................... 5-3
5.4 LED Indicators ......................................................................................................................................... 5-4
5.5 Releasing Operation ................................................................................................................................. 5-5
5.5.1 Cross Alarm Operation ..................................................................................................................... 5-5
5.5.1.1 Default NAC Settings for Releasing ...................................................................................... 5-5
5.5.2 Double Interlock Releasing Operation ............................................................................................. 5-7
5.6 Smoke Alarm Verification ....................................................................................................................... 5-8
5.7 System Testing ......................................................................................................................................... 5-9
5.7.1 Fire Drills .......................................................................................................................................... 5-9
5.7.2 Walk Test .......................................................................................................................................... 5-9
5.7.3 Automatic Self Test .......................................................................................................................... 5-9
5.7.4 Watchdog Circuit .............................................................................................................................. 5-9
5.8 Communicating with a Programming Computer ................................................................................... 5-10
5.8.1 Programming From a Remote Computer Location ........................................................................ 5-10
5.8.1.1 Having the Control Panel Call the Remote Computer ......................................................... 5-10
5.8.1.2 Having Remote Computer Call the Control Panel ............................................................... 5-11
5.8.2 Directly Connecting to a Programming Computer ......................................................................... 5-12

Section 6
Reporting ..................................................................................................................................................... 6-1

6.1 Reporting Formats .................................................................................................................................... 6-1


6.2 Reporting Codes ....................................................................................................................................... 6-2
6.2.1 Default Settings for 3/1 Format ........................................................................................................ 6-4

Section 7
Troubleshooting ................................................................................................................................ 7-1

7.1 System Error Messages ............................................................................................................................ 7-1


7.2 Earth Ground Fault Troubleshooting ....................................................................................................... 7-3
7.3 Earth Fault Resistance .............................................................................................................................. 7-4

Appendix A
Compatible Devices ..................................................................................................................... A-1

A.1 Notification Appliances .......................................................................................................................... A-1


A.2 Two-Wire Smoke Detectors .................................................................................................................. A-11
A.3 Four Wire Smoke Detectors .................................................................................................................. A-13

Silent Knight Fire Product Warranty and Return Policy


SK-5208 Plus Basic Operating Instructions P/N 151214 Rev. A

iii

Downloaded from www.Manualslib.com manuals search engine


Installation Manual

iv

Downloaded from www.Manualslib.com manuals search engine


Section 1
Introduction

The Model SK-5208 is an 24-volt 10-zone fire alarm control panel (expandable up to 30 zones
using SK-5217 Zone Expanders) with a digital communicator that meets NFPA 72
requirements. The SK-5208 cabinet can be surface mounted or semi-flush mounted.

1.1 Model SK-5208 Features


• Built-in two-line (16 Character each line) LCD display provides easy to read english
language readouts
• 10 Initiation inputs, 8 Class B (Style B) and 2 zones that can be configured as Class B
(Style B) or Class A (Style D), expandable to 30 zones
• Supervised zone expanders and I/O modules can be mounted remotely from the main
control panel
• UL Listed
• Event History Buffer (approximately 150 events) with Date/Time stamp
• All zones are compatible with 2- and 4-wire detectors
• 8 selectable/programmable output pattern for notification appliance circuits (Including
ANSI 3.41)
• Built-in Digital Alarm Communicator Transmitter (DACT)
• 4 Notification appliance circuits
• 4 programmable general purpose relays
• Programmable smoke verification, pre-alarm delay, cross zoning and enhanced
verification mode features that can help minimize false alarms
• Capable of single or dual operation for water releasing services.

• Programmable from the built-in control panel touchpad, remote annunciator or Window®
downloading software
• Built-in walk test

P/N 151204 1-1

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

1.2 About This Manual


The Model SK-5208 Fire Control/Communicator Installation Manual (P/N 151204) is
intended for those persons involved with the installation and maintenance of the SK-5208
panel. It is a comprehensive guide, providing detailed instructions, and should be kept for
reference. As much as possible, we have tried to organize the manual chronologically by the
tasks that need to be performed.
Table 1-1: Standards Used in this Manual

1 A same graphic replicating the key that you press on a touchpad.

LCD DISPLAY MESSAGE The font shown to the left represents messages that you see on a liquid crystal
display (LCD) on the control panel and the remote annunciator.
1-1, 2-3, etc. This manual is organized into sections. Section numbers are part of the page
numbers. For example, 1-1 means Page 1 of Section 1.

1.2.1 Optional Accessories


Table 1-2: Compatible Modules Manufactured by Silent Knight

Model What It Does


SK-5217 Zone Expander Adds 10 zones to the SK-5208 for a total expansion of the system to 30 zones.
SK-2190 Accessory Cabinet Used for remote mounting of the SK-5217 Zone Expander.
Dimensions: 10-3/8”W x 10-3/16”H x 3”D (26.35 cm W x 25.88 cm H x 7.62 cm D)
5220 Direct Connect Module For direct alarming and trouble transmission from the SK-5208 to a supervising
station.
SK-5235 Remote Annunciator For remote annunciation, operation, and on-site programming.
SK-5280 The Model SK-5280 Status Display module provides outputs and control functions for
remote annunciation of alarm, trouble, and supervisories for each zone.
5824 Provides connectivity to a Serial or Parallel printer. (See Section 4.2.12 for
programming.)
SK-5499 Signal Power Expander Notification circuit power for additional notification appliances. Provides additional
9A of 24 VDC, supervised.
SK-5495 Signal Power Expander Notification circuit power for additional notification appliances. Provides additional
6A of 24 VDC, supervised.
SKSS Downloading Software For remote programming of the SK-5208 using a personal computer.
Model 5660
PLEX-2 Optional door accessory for single button operation. (See Section 4.3 for
programming.)

1-2 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Introduction
Limitations of Fire Alarm Systems
Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the
recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer’s
recommendations, State and local codes, and the recommendations contained in Guide for the Proper Use of System Smoke
Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emergency Management
Agency (an agency of the United States government) indicated that smoke detectors may not go off or give early warning in as
many as 35% of all fires. While fire alarm systems are designed to provide warning against fire, they do not guarantee warning
or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a
variety of reasons. For example:
• Particles of combustion or smoke from a developing fire may not reach the sensing chambers of smoke detectors because:
- Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
- Smoke particles may become cold, stratify, and not reach the ceiling or upper walls where detectors are located.
- Smoke particles may be blown away from detectors by air outlets
- Smoke particles may be drawn into air returns before reaching the detector.
In general, smoke detectors on one level of a structure cannot be expected to sense fires developing on another level.
• The amount of smoke present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the
detectors will not go into alarm.
• Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have
ionizing-type sensing chambers tend to detect fast flaming fires better than smoldering fires. Because fires develop in
different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of
detector may not provide adequate warning of a fire.
• Smoke detectors are subject to false alarms and nuisance alarms and may have been disconnected by users. For example,
a smoke detector located in or near a kitchen may go into nuisance alarm during normal operation of kitchen appliances.
In addition, dusty or steamy environments may cause a smoke detector to falsely alarm. If the location of a smoke
detector causes an abundance of false alarms or nuisance alarms, do not disconnect the smoke detector; call a professional
to analyze the situation and recommend a solution.
• Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches
(especially within bedrooms), smoking in bed, violent explosions (caused by escaping gas, improper storage of flammable
materials, etc.).
• Heat detectors do not sense particles of combustion and are designed to alarm only when heat on their sensors increases at
a predetermined rate or reaches a predetermined level. Heat detectors are designed to protect property, not life.
• Warning devices (including horns, sirens, and bells) may not alert people or wake up sleepers who are located on the other
side of closed or partially open doors. A warning device that activates on a different floor or level of a dwelling or
structure is less likely to awaken or alert people. Even persons who are awake may not notice the warning if the alarm is
muffled by noise from a stereo, radio, air conditioner or other appliance, or by passing traffic. Audible warning devices
may not alert the hearing-impaired (strobes or other devices should be provided to warn these people). Any warning
device may fail to alert people with a disability, deep sleepers, people who have recently used alcohol or drugs, or people
on medication or sleeping pills.
- Please note that:
i) Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
ii) Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend
the meaning of the signal. It is the property owner’s responsibility to conduct fire drills and other training exer-
cises to make people aware of fire alarm signals and instruct on the proper reaction to alarm signals.
iii) In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
• Telephone lines needed to transmit alarm signals from a premises to a central station may be out of service or temporarily
out of service. For added protection against telephone line failure, backup radio transmission systems are recommended.
• System components, though designed to last many years, can fail at any time. As a precautionary measure, it is
recommended that smoke detectors be checked, maintained, and replaced per manufacturer's recommendations.
• System components will not work without electrical power. If system batteries are not serviced or replaced regularly, they
may not provide battery backup when AC power fails.
• Environments with high air velocity or that are dusty or dirty require more frequent maintenance.

P/N 151204 1-3

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

In general, fire alarm systems and devices will not work without power and will not function properly unless they
are maintained and tested regularly.
While installing a fire alarm system may make the owner eligible for a lower insurance rate, an alarm system is
not a substitute for insurance. Property owners should continue to act prudently in protecting the premises and
the people in their premises and should properly insure life and property and buy sufficient amounts of liability
insurance to meet their needs.

1-4 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Section 2
Agency Listings and Requirements

Install and maintain in accordance with NFPA 72. Detector spacing shall be in accordance to
NFPA 72. End-of -line relays and resistors shall be placed within the electrical box located
and the end of the initiating circuit. Testing and maintenance should be performed according
to NFPA 72.

2.1 Federal Communications Commission (FCC)

1. If requested by the telephone company, the following information must be provided before
the SK-5208 can be connected to the phone lines:
A. Manufacturer: Silent Knight
A. Model Number: SK-5208
B. FCC registration number: AC6USA-34758-AL-E
Ringer equivalence: 0.5B
C. Type of jack (to be installed by the telephone company): RJ31X

4. This device may not be directly connected to coin telephone or party line services.
5. This device cannot be adjusted or repaired in the field. In case of trouble with the device,
notify the installing company or return to:
Silent Knight
12 Clintonville Road
Northford, CT 06472-1610
203-484-7161
800-328-0103
6. If the SK-5208 causes harm to the telephone network, the telephone company will notify
the user in advance that temporary discontinuance of service may be required. When
advance notice is not practical, the telephone company will notify the user as soon as
possible. Users have the right to file complaints, if necessary, with the Federal
Communications Commission.
7. The telephone company may make changes in its facilities, equipment, operations, or
procedures that could affect the operation of the equipment. If this happens, the telephone
company will provide advance notice to allow you to make the necessary modifications to
maintain uninterrupted service.

Warning
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the two following
conditions: (1) This device may not cause radio interference; and (2) This device must accept any
interference received including interference that may cause undesired operation.

P/N 151204 2-1

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

2.2 Underwriters Laboratories (UL)

The SK-5208 is UL Listed as a control unit for use in Central Station Protected Premises,
Local Protected Fire Alarm Systems, Auxiliary Protected Fire Alarm Systems for Fire Alarm
Service (City Box), Remote Station Protected Fire Alarm Systems and water releasing
service. If the SK-5208 and its accessories are to be used as part of a UL installation, carefully
read the UL requirements in this section.

2.2.1 Requirements for All Installations


General requirements are described below. The sections that follow describe additional
requirements for the type of installation (for example, Central Station Fire Alarm systems,
Local Protected Fire Alarm systems, and so on).
1. Use UL listed smoke detectors compatible with the SK-5208. Refer to Appendix A.
2. Use UL listed compatible notification devices. Refer to Appendix A.

Restricted Options:
• The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 -
30 hours. For UL certified installations this number must be set from 1 to 3 hours.
• Call forwarding shall not be used.
• When cross zoning is used detector spacing shall be cut in half, you shall not use the alarm
verification feature, and no delay shall be used.

2.2.2 Requirements for Central Station Fire Alarm


Systems
1. The Phone Line “Line Dial Type” must be selected for anything other than “Not Used”.
(See programming Section 4.2.9).
2. On class A (style D) zones, the number of waterflow devices is limited to five.
3. Auxiliary relays may not be programmed to activate for Pre-Alarm. See programming
Section 4.2.5.

2.2.3 Requirements for Auxiliary Protected Fire Alarm


Systems for Fire Alarm Service
1. Follow the current load restrictions shown in Section 3.6.
2. The Model 5220 Direct Connect module must be installed (see Section 3.15.1 for wiring).

2.2.4 Requirements for Remote Station Protected Fire


Alarm Systems, for Digital Communication or
Polarity Reversal
1. Follow the current load restrictions shown in Section 3.6.
2. Use the SK-5208’s built-in dialer or install the Model 5220 Direct Connect Module (see
Section 3.15.1).

2-2 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Section 3
Control Panel Installation

3.1 Electrical Specifications

Table 3-1: Electrical Specifications


Primary AC 120 Vrms at 60 Hz, 3A
Total DC Load 6A
Accessory Power 27.4 VDC, 1A
Smoke Power 27.4 VDC, 1A
Battery Charging Voltage 27.4
Battery Charging Current .75 A max.
Class B (Style B) Circuit Current 95 mA max.
Telephone Minimum Input Sensitivity 35 dB
Good Phone Line Voltage 3V
Maximum Low Battery Detect 20.4
Minimum Low AC Detect 98
Notification Power 3A max. per output (6A total)

3.2 Environmental Specifications

It is important to protect the SK-5208 control panel from water. To prevent water damage, the
following conditions should be AVOIDED when mounting the units:
• Do not mount directly on exterior walls, especially masonry walls (condensation).
• Do not mount directly on exterior walls below grade (condensation).
• Protect from plumbing leaks.
• Protect from splash caused by sprinkler system inspection ports.
• Do not mount in areas with humidity-generating equipment (such as dryers, production
machinery).
When selecting a location to mount the SK-5208 control panel, the unit should be mounted
where it will NOT be exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or
humidity equal to or greater than 93% at 30°C (89°F) noncondensing.
See also the mounting recommendations in Section 3.5 for additional environmental
specifications.

P/N 151204 3-1

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

3.3 Wiring Specifications

To avoid induced noise (transfer of electrical energy from one wire to another), keep input
wiring isolated from high current output and power wiring. Induced noise can interfere with
telephone communication or even cause false alarms. Avoid pulling one multiconductor cable
for the entire panel. Instead, separate the wiring as follows:

Input/Output Type Wiring


1/4" spacing must be maintained High Voltage: AC power
between each of these circuit types;
Low Voltage: Annunciator, zone circuit wiring, and notification devices
as well as between power limited
and non-power limited circuits. Audio: Speaker
Telco Separated

DO NOT pull wires from different groups through the same conduit. If you must run them
together, do so for as short a distance as possible or use shielded cable. Connect the shield to
earth ground at the panel only.
For the same reasons, wiring within the cabinet should be routed around the perimeter of the
cabinet. It should not cross the printed circuit board where it could induce noise into the
sensitive microelectronics or pick up unwanted RF noise from the high speed circuits.
High frequency noise, such as that produced by the inductive reactance of a speaker or bell,
can also be reduced by running the wire through ferrite shield beads or by wrapping it around

3-2 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Control Panel Installation

a ferrite toroid. Figure 3-1 provides an example.

Tel. Line

To Zone Aux Relays

NACs

To AC

SBUS devices
or
Annunciator

Figure 3-1 Wire Routing Example

3.4 Control Board Components

Figure 3-2 is a wiring diagram for wiring the Model SK-5208 panel.
Figure 3-2 Model SK-5208 Board Layout

Refer to Section 3.9 for complete description of control panel terminal connections.

P/N 151204 3-3

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

Phone Line 1 Phone Line 2 RS232


Connections Connections Programming Connector

Class A
or
Class B Programmable
Zone Output Relays
Inputs

Class B
Zone
Inputs NAC
Circuit

Remote
Annunciator
Connections

SBUS
Connections

AC
Input
Backup
Battery
Connector

3-4 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Control Panel Installation

3.5 Mounting the SK-5208

Read the environmental specifications in section 3.2 on page 1 before mounting the SK-5208
panel.
The SK-5208 cabinet dimensions are:
16" W x 26.4" H x 4" D (40.64 cm W x 67.06 cm H x 10.16 cm D).
The SK-5208 panel should be located within a secured area, where it is accessible to main
drop wiring runs and where it can be easily tested and serviced. End-users responsible for
maintaining the panel should be able to hear alarms and troubles. When selecting a location,
keep in mind that the panel itself is the main source of alarm and trouble annunciation.
When mounting on interior walls, use appropriate screw anchors in plaster. When mounting
on concrete, especially when moisture can accumulate, the enclosure shall be placed or
equipped so as to prevent moisture or water from entering and accumulating within the
cabinet, and shall be mounted so there is a least 1/4” space between the enclosure and the
concrete wall surface. A piece of plywood, standoffs, or other equivalent material can be used
to space the cabinet from the concrete surface and then attach the SK-5208 to that spacing
surface. Also mount any other desired components to the 1/4” spacing surface.
DO NOT flush-mount the SK-5208 cabinet in a wall designated as a fire break.

3.5.1 Preventing Water Damage


Water damage to the fire system can be caused by moisture entering the cabinet through the
conduits. Conduits that are installed to enter the top of the cabinet are most likely to cause
water problems. Installers should take reasonable precautions to prevent water from entering
the cabinet. Water damage is not covered under warranty.

P/N 151204 3-5

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

3.6 Current Draw Calculations

3.6.1 Worksheet Requirements


The following steps must be taken when determining SK-5208 current draw and standby
battery requirements.

Filling in the Current Draw Worksheet, Table 3-2 (Section 3.6.2)


1. For the SK-5208, the worst case current draw is listed for the panel and panel accessories.
Fill in the number of devices that will be used in the system and compute the current draw
requirements for alarm and standby. Record this information in Table 3-2 at Line A.
2. Add up the current draw for all smoke detectors and record in the table at Line B.
3. Add up all notification appliance loads and record in the table at Line C.
4. For notification appliances and auxiliary devices not mentioned in the manual, refer to the
device manual for the current ratings.
5. Make sure that the total alarm current you calculated, including current for the panel itself,
does not exceed 6.0 A. This is the maximum alarm current for the SK-5208 control panel.
If the current is above 6.0 A you will need to use a notification power expander(s) such as
the 5495 to distribute the power loads so that the SK-5208 or the power expanders do not
exceed their power rating. Refer to the current draw worksheets provided with the 5495
manuals so you do not exceed their power requirements.
6. Complete the remaining instructions in Table 3-2 for determining battery size
requirements.

3.6.2 Current Draw Worksheet


Use Table 3-2 to determine current requirements during alarm/battery standby operation.
(Copy the page if additional space is required.)

3-6 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Control Panel Installation

Table 3-2: Current Draw Calculations


Standby Alarm
Device # of Devices Current per Device
Current Current
For each device use this formula: This column X This column = Current per number of devices.
SK-5208 Fire Panel (Current draw Standby: 140 mA 140 mA
1
from battery) Alarm: **550 mA 550 mA
Panel Accessories
Standby: 60 mA mA
SK-5217 Zone Expander (2 max.)
Alarm: 150 mA mA
5824 Serial/Parallel Interface Standby: 45 mA mA
(1 max.)
Gateway Module Alarm: 45 mA mA
Standby: 15 mA mA
5220 Direct Connect
Alarm: 15 mA mA
Standby: 30 mA mA
SK-5235 Annunciator (6 max.)
Alarm: 50 mA mA
Relay Standby: 10 mA mA
(max.) Alarm: 80 mA mA
SK-5280 Status Display Module (8 max.)
Per output 100 mA mA
Outputs
Max. 700 mA mA
A Total System Current
Smoke Detectors
Standby: mA mA
Alarm: mA mA
Standby: mA mA
Alarm: mA mA
Standby: mA mA
Alarm: mA mA
Standby: mA mA
Alarm: mA mA
B Smoke Detector Current mA mA
Notification Appliances
Alarm: mA mA
Alarm: mA mA
Alarm: mA mA
Alarm: mA mA
C Notification Appliances Current mA
Additional Devices
Standby: mA
Alarm: mA
Standby: mA
Alarm: mA
D Additional Devices Current mA
E Total current ratings of all devices in system (line A + line B + C +D) mA mA
F Total current ratings converted to amperes (line E x .001): A A
G Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5): H
H Multiply lines F and G. Total standby AH AH
I Alarm sounding period in hours. (For example, 5 minutes = .0833 hours) H
J Multiply lines F and I. Total alarm AH AH
K Total ampere AH
*Add lines H and J.
hours required
* Use next size battery with capacity greater than required.
** The SK-5208 and SK-5217 limits alarm current to 95mA per zone. The SK-5208 alarm current includes
10% of zones in alarm, but in no case less then three zones per UL864

P/N 151204 3-7

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

3.6.3 Maximum Battery Standby Load


Table 3-3 shows the maximum battery standby load for the SK-5208 based on 24 and 60 hours
of standby. The standby load calculations of line D in the Current Draw Calculation
Worksheet (Table 3-2) must be less than the number shown in Table 3-3 for the battery size
used and standby hours required.
Batteries larger then 18 AH will not fit into the SK-5208 cabinet and must be housed in the
RBB remote battery box cabinet. See Section 3.8 for battery installation.
Table 3-3: Maximum Battery Standby Load

Max. Load for 24 hrs. *Max. Load for 60 hrs.


Rechargeable Battery Size
Standby, 5 mins. Alarm Standby, 5 mins. Alarm
7 AH 270 mA 105 mA
12 AH 475 mA 190 mA
18 AH 685 mA 270 mA
35 AH 1.1 A 450 mA

* Required for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box) and Remote
Station Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Communicator/Transmitter
(DACT).

Warning!
Silent Knight does not support the use of batteries smaller than those listed in Table 3-3. If you use a battery too
small for the installation, the system could overload the battery resulting in the installation having less than the
required 24 hours standby power. Use Table 3-2 to calculate the correct battery amperes/hour rating needed for
your installation.

3-8 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Control Panel Installation

3.7 AC Wiring

The Model SK-5208 power supply delivers 24 VDC at 6A for smoke detector power,
notification device power, and accessory power. Figure 3-3 shows the AC connections to the
SK-5208 control panel.

Figure 3-3 AC Wiring

Warning
To reduce the risk of electrical shock, make sure that all power has been turned off or disconnected before attempting
to connect the Model SK-5208 control panel. Do NOT apply power to this panel until all accessories are properly
connected.

Note: Note: All conduit and wiring connected to the SK-5208 must meet the applicable National Electric Code,
NFPA Standards, state, and local building code requirements. In all cases, the authority having
jurisdiction takes precedence.

P/N 151204 3-9

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

3.8 Backup Batteries

The control panel battery charge capacity is 7.0 to 35.0 AH. Use 12V batteries of the same AH
rating. Determine the correct AH rating as per your current load calculation (see 3.6.2).
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase
the AH rating.
Batteries larger than 18 AH (not to exceed 35 AH) use the RBB Remote Battery Box. It is
recommended that you replace the batteries every five years. The following steps and diagram
explain how to connect the batteries.
1. Connect the black wire to the negative (-) side of battery #1.
2. Connect the jumper wire provided (P/N 140694) from the positive (+) side of battery #1 to
the negative side of battery #2.
3. Connect the red wire to the positive (+) side of battery #2

RED

Control Panel
Black

Battery Jumper
(P/N 140694)
Note: Replace batteries Shipped With Panel
every 5 years.

Battery #1 Battery #2

UL Listed 12VDC Battery UL Listed 12VDC Battery


Gell Cell Gell Cell

Caution
Apply AC power before connecting the batteries to the power supply to prevent arcing on battery terminals.

Note: The total current draw on smoke power, accessory power, and notification device outputs must not exceed
6A.

3-10 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Control Panel Installation

3.9 Terminal Strip Description

The terminal strips on the PC board are non-removable. Table 3-4 lists the functions of each
terminal. See Section 3.4 for the board layout.
Table 3-4: Terminal Descriptions

Terminal
Function Terminal Label Comments
Number
1 A Zone 1 input Class A (Style D) or Class B (Style B). See
2 B Section 3.11 for wiring configurations.
Zone 1 input. Z1
3 C
4 D
5 A Zone 2 input Class A (Style D) or Class B (Style B). See
6 B Section 3.11 for wiring configurations.
Zone 2 input Z2
7 C
8 D
Ground 9 GND
Zone 3 input 10 Z3 Zone input Class B (Style B). Refer to Section 3.11.2.
Power (Zone 3 & 4) 11 PWR Power Limited at 100mA. Voltage 27.4 VDC.

Zone 4 input 12 Z4
Zone 5 input 13 Z5
Smoke Power 14 PWR
Zone 6 input 15 Z6
Zone 7 input 16 Z7
Smoke Power 17 PWR
Zone 8 input 18 Z8
Zone9 input 19 Z9
Smoke Power 20 PWR
Zone 10 input 21 Z10
Ground 22 GND
23 B
AC Power Connections 24 Earth
25 W
26 GND Used to connect SK-5217 Zone Expanders and 5280
27 +24DC Status Display Modules to the control panel. Accessory
SBUS Connections Power (terminals 26 and 27) provides 1 Amp total
28 A current.
29 B
30 SKI Used to connect 5235 remote annunciators to the control
31 SKO panel.
Remote Annunciator
Connections 32 PWR
33 GND

P/N 151204 3-11

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

Table 3-4: Terminal Descriptions

Terminal
Function Terminal Label Comments
Number

Notification Appliance 34 + 3 Amp maximum per circuit. Voltage 27.4 VDC, 1.5
NAC4 Ohms Maximum.
Circuit 4 35 _
Note: Total control panel current is 6 Amps.
Notification Appliance 36 +
NAC3
Circuit 3 37 _
Notification Appliance 38 +
NAC2
Circuit 2 39 _
Notification Appliance 40 +
NAC1
Circuit 1 41 _
42 NO Relay contacts are rated at 2.5 A, 24 VDC/24VAC
Auxiliary Relay 4 43 COM (inductive rating). 5A, 24 VDC/24 VAC (resistive).
Connect to power limited source only.
44 NC
45 NO
Auxiliary Relay 3 46 COM
47 NC
48 NO
Auxiliary Relay 2 49 COM
50 NC
51 NO
Auxiliary Relay 1 52 COM
53 NC
54 TIP Telephone line 2 connection terminals (see Section 3.10
P2 for wiring diagram).
55 RING
Telco Line 2
56 TIP
T2
57 RING
58 TIP Telephone line 1 connection terminals (see Section 3.10
P1 for wiring diagram).
59 RING
Telco Line 1
60 TIP
T1
61 RING

3-12 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Control Panel Installation

3.10 Telephone Line Connection

The SK-5208 connects to two separate telephone lines to report data to the central station. An
RJ31X jack should be installed by the telephone company for each line. Figure 3-4 shows how
to wire the telephone line interconnect cords (not provided) to the SK-5208.
Note: To reduce the possibility of false alarms and transient damage, DO NOT bundle telephone wires together
with initiation or notification device wires.

Supervised

Figure 3-4 Telephone Line Connection

The letter designator on the phone input indicates whether it is the Telco or House side of the
phone circuit. For example terminals 60 and 61 are labeled T1, T = Telco side of the phone
circuit and terminals 58 and 59 are labeled P1, P = Premise (House) side of the phone circuit.
The SK-5208 has built-in dual phone line monitors. These circuits will detect any fault in the
phone lines by monitoring the DC voltage present on the lines. If phone line voltage drops
below 3 VDC and is not corrected within approximately 60 seconds, an audible trouble signal
will sound and the panel will report a line fault trouble over the remaining phone line.
A situation could occur where both phone lines appear to be good, but the dialer cannot get
through to the central station on the first line. In this case, the SK-5208 will switch phone lines
and attempt the call again using the second line. Make sure the phone lines are programmed
properly (see Section 4).
Note: To comply with industry standards, this product is equipped with line seizure. Any time the system’s dialer
needs to communicate with the central station, it will not be possible to use any telephones that are on the
same line(s) as the system. Normally, this condition will last approximately one minute, but under adverse
telephone circuit conditions, could last for as long as 15 minutes.

P/N 151204 3-13

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

3.11 Detector Installation

3.11.1 Class A (Style D) Zones


Zones 1 and 2 may be selected through programming as Class A (Style D) zones (see Section
4.2.2 for zone style programming). See Section 3.11.2 for Class B (Style B) configuration.
Each class A zone is a four-wire circuit that allows an alarm to be detected even after a single
open or ground fault occurs. When a single open or ground fault occurs, the audible trouble
signal will sound and the SK-5208 will report the trouble to the central station or remote
station (if programmed to report troubles). If reporting to a remote station troubles may be
transmitted to a secondary location.
Figure 3-5 shows how to wire a Class A (Style D) circuit. No end-of-line (EOL) resistors are
needed for these zones. These zones must be wired using normally open contacts.

Supervised
Power Limited

Figure 3-5 Class A (Style D) Supervised Fire Circuit

Maximum voltage: 17.5 to 28 VDC Full Wave Rectified


Circuit Current: 95 mA
Maximum circuit Resistance: 50 ohms

3-14 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Control Panel Installation

3.11.2 Class B (Style B) Zones


Zones 3 through 10 are Class B (Style B) only fire zones. Zones 1 & 2 may also be
programmed as Class A (Style D) or Class B (Style B), see Section 4.2.2 for zone 1 & 2 zone
programming.
Each Class B zone consists of a two-wire circuit that will detect the occurrence of an open in
the circuit, but may not be able to detect an alarm after such an occurrence. The detection of
an open will cause the audible trouble signal to sound and the SK-5208 will report the trouble
to the central or remote station (if programmed to do so).
Figure 3-6 shows how to wire a Class B (Style B) circuit. One side of each Class B circuit
connects to a zone input terminal and the other side of each circuit connects to Smoke power.
For each circuit, use a 4.7K-ohm EOL resistor wired in parallel with the normally open
contact farthest from the panel.
Note: Zones 1 and 2 can be
configured as either Class A
or Class B. See also Section
3.11.1.

4.7 kΩ EOL
UL Listed
Model 7628
Supervised
Power Limited

Figure 3-6 Model SK-5208 Class B (Style B) Circuits

Maximum circuit Resistance - 50 ohms


Maximum Total alarm current for all Class B (Style B) zones - 1 A
Maximum Standby Current per Zone:3.0 mA
Maximum Alarm Current per Zone:95 mA

P/N 151204 3-15

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

3.11.3 Four-Wire Smoke Detector Connection


Figure 3-7 illustrates how UL listed four-wire smoke detectors must be connected to Class B
(Style B) zones.
When wiring a four-wire smoke detector to the Class B (Style B) zones, you must use a Power
Supervision Unit, such as Silent Knight’s 160150.
Note: Mount the PAM-2 and the end-of-line resistor at the last device on the circuit.

Supervised
Power Limited

Figure 3-7 Four-Wire Smoke Detector Wiring

See Appendix A for a list of four-wire smoke detectors that may be used with the SK-5208.

3-16 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Control Panel Installation

3.11.4 Two-Wire Smoke Detector Connection


Figure 3-8 shows how to connect two-wire smoke detectors to Class B (Style B) zones.

Silent Knight
SLK-24F 2-wire detector
with HSB-224 base

– –
+ +
Supervised
Power Limited
4.7 kΩ
UL Listed EOL
Model 7628

Figure 3-8 Two-Wire Smoke Detector Wiring

See Appendix A for a list of two-wire smoke detectors that may be used with the SK-5208.
Note: Two-wire detectors can be configured for Enhanced Mode. Enhanced mode is smoke verification for zones
with 2-wire detectors and contact type devices, such as pull stations, used on the same circuit. If the alarm
current is greater than 78 mA, the smoke verification cycle will not occur. See Section 4.2.1 Verify Options
under the Zone Options Menu to program initiation circuits for enhanced mode.

P/N 151204 3-17

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

3.12 Supervised Notification Appliance Outputs

Note: To reduce the possibility of false alarms and transient damage, DO NOT bundle telephone wires together
with notification circuit wires.
The SK-5208 provides four Class B (Style Y) supervised notification circuit outputs to
annunciate alarm conditions. For proper operation, you must use polarized sounding devices
with a 4.7k ohm end-of-line resistor on each circuit. Figure 3-9 shows how to connect the
notification circuits to the SK-5208.
3 Amps Max. per circuit full
wave rectified, 27.5 VDC, 1.5
Ohms Maximum.

Supervised
Power Limited

4.7 kΩ
UL Listed EOL
Model 7628

Figure 3-9 Supervised Notification Appliance Wiring

3 Amp maximum current draw from any single NAC output (not to exceed a total current
draw of 6 amps for the control panel). See Appendix A for a list of the UL notification
appliances that can be used with the SK-5208. Contact Silent Knight if you have any
questions about compatible notification circuits.
All circuit are regulated unless used for releasing service in which case they are considered
special applications. See Section 5.5 for details on releasing.

3-18 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Control Panel Installation

3.13 Auxiliary Relays

The SK-5208 provides four programmable auxiliary relay outputs. Relays can be programmed
to activate for the following conditions, either for all zones or by individual zone: pre-alarm
(not acceptable for NFPA 72 Central Station), fire alarm, auxiliary alarm, alarm by zone, and
system or circuit troubles (loss of AC, low battery, failed to communicate, phone line troubles,
fire drills, and notification circuit troubles).
Refer to the SK-5208 programming manual for more information. Figure 3-10 shows the relay
contact connections using a door holder application as an example.
Note: Relays programmed as “Trouble” will be active during normal state and deactivated during a trouble
condition.

Door Holder
ESL DHX 1224

Relay contacts are rated at


2.5 A, 24 VDC/24VAC (inductive rating).
5A, 24 VDC/24 VAC (resistive).

Figure 3-10 Auxiliary Relays

P/N 151204 3-19

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

3.14 Accessory Devices

The section describes how to install the SK-5235 Remote Annunciator, SK-5217 Zone
Expander, the 5824 Serial/Parallel Printer Module, and the SK-5280 Status Display Module.
All circuits are 24 VDC regulated.
All S-Bus devices are Style 1 Class B as per NFPA 72.

3.14.1 Setting ID Codes


Before installing the SK-5235, SK-5217, 5824 or SK-5280, you must first set their
identification codes. Each device must be given its own identification code. For example:
each SK-5235 needs a unique ID code, but a SK-5235 can have the same ID code as a
SK-5217. Each type of device has it’s own device type programmed into it enabling the
control panel to distinguish between the different devices.
On the back of each device is a small 4-position dip switch used to set the ID code. Use the
chart below to determine the dip switch positions for each possible ID code.
Table 3-5: ID Dip Switch Settings

Switches1
ID Number
1 2 3 4

02 Down Down Down Down


1 Up Down Down Down
2 Down Up Down Down
3 Up Up Down Down
4 Down Down Up Down
5 Up Down Up Down
6 Down Up Up Down
7
Not used3
8
1. Switch Settings: Up = On Down = Off
2. Not supervised.
3. ID number 7 and 8 are not valid ID settings.

3-20 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Control Panel Installation

3.14.2 Model SK-5235 Remote Annunciator


The SK-5235 performs all system operation. It also provides trouble and alarm information
and can be used for programming. The control panel can support up to six SK-5235 Remote
Annunciators.
Upon initial power up, the address of each SK-5235 is displayed on the LCD. (Annunciators
with address 0 will not be supervised.)

3.14.2.1 Mounting the SK-5235 Remote Annunciator


The SK-5235 Remote Annunciators must be mounted on a dual gang electrical box.
To mount the annunciator:
1. Remove the rear mounting plate by inserting a #4 flat blade screwdriver into the slots on
the bottom edge of the annunciator. See Figure 3-11. Gently turn the screwdriver until the
mounting plate pulls away from the frame.

Figure 3-11 Rear Mounting Plate Removal

2. Secure it to the wall using #6 or #8 screws. The mounting plate should be oriented so that
the word TOP is toward the top of the plate and facing you. A square hole is provided in
the mounting plate to run the wiring to the annunciator.
3. When all of the wires have been connected to the annunciator, set the top of the
annunciator over the tabs on the top of the mounting plate. Make sure the wires do not get
pinched between the frame and the mounting plate. Press each corner of the bottom side
onto the annunciator mounting plate until you hear it click. You may have to gently
squeeze the annunciator (top to bottom) to align it while snapping the bottom edge into
place.

P/N 151204 3-21

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

3.14.2.2 Wiring the SK-5235


Follow these steps to properly wire the SK-5235 to the control panel.
1. Remove power from the control panel.
2. Wire the SK-5235s as shown in Figure 3-12.
3. Set the ID number. See Table 3-5.
Note: The ID number of 7 is reserved for the built-in touchpad on the SK-5208.
4. Reapply power the the control panel.
When the annunciator powers up, it will display its ID code and current status of the panel.

1
ID DIP switches 2
3
4

Supervised
Power Limited
Class B

Figure 3-12 Model SK-5235 Connection


Note: Each 5235 touchpad can be individually supervised. See Section 4.2.2 for programming touchpads as
supervised.

3-22 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Control Panel Installation

3.14.3 Model SK-5280 Status Display Module


The Model SK-5280 Status Display module provides outputs and control functions for remote
annunciation of alarm, trouble, and supervisories for each zone.The system can supervise up
to eight SK-5280 Status Display Modules.
Note: The driver outputs are non-supervised. Relays must be connected to power limited sources only.
4 On-board Relays

ID Number
DIP Switch

Relay Rating
2.5A @ 30 VDC/120 VAC

Alarm Outputs Trouble Outputs SBUS Connector


1/4” spacing must be maintained between power limited
& non-power limited wiring

Figure 3-13 Model 5280 Board Layout

The SK-5280 has 1 connector which has 10 outputs for alarms and 10 outputs for trouble
annunciation. These outputs are active low. Each output can provide up to 100 mA of current,
with a total limitation of 700 mA.
The module has 4 normally open non-dedicated relays that can be wired to be active with any
of the outputs.
Wire the SK-5280 as shown in Figure 3-14. Maintain a physical separation of one-half inch or
more between field wires and connection points to prevent damage from transients.
Note: SILENCE does not affect SK-5280 outputs. To reset a SK-5280 output, the alarm or
trouble condition must be restored.

P/N 151204 3-23

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

The SK-5280 can be used to interface to LED annunciator.


The SK-5280 can be programmed to indicate alarms and trouble status for; zones 1 - 10, zones
11 - 20, zones 21 - 30, or system status outputs. See Section 4.2.11.
5280

Supervised
Power Limited
Control Class B
Panel

Figure 3-14 Model SK-5280 Connection to the Control Panel

3-24 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Control Panel Installation

3.14.3.1 Mounting the SK-5280


The SK-5280 into a metal bracket and standoffs in the SK-5208 cabinet or into SK-2190
accessory cabinet.

Mounting the SK-5280 into SK-5208 Cabinet


Follow these steps to properly mount the SK-5280 into the SK-5208 cabinet:
1. Remove power from the control panel.
2. Mount the SK-5280 onto the standoffs and bracket located in the cabinet. See Figure 3-15.

Figure 3-15 Installing the 5280 Into the 5208 Cabinet

3. Connect the SK-5280 to the SK-5208 control panel as shown in Figure 3-14.
4. Set the ID number (see Figure 3-13 for ID DIP switch location). See also Section 3.14.1for
information on setting ID numbers.
5. Reconnect power to the control panel.

P/N 151204 3-25

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

Mounting the SK-5280 into the SK-2190 Accessory Cabinet.


Follow these steps to properly mount the SK-5280 into the SK-2190 cabinet:
1. Mount the remote cabinet using the cabinet mounting holes. See Figure 3-16.
Refer to Section 3.5 for proper cabinet mounting procedures.
2. Remove power from the control panel.
3. Mount the SK-5280 onto the standoffs and bracket located in the cabinet. See Figure 3-16.

Mounting
Mounting Holes
Holes

Figure 3-16 Model SK-5280 Remote Installation

4. Connect the SK-5280 to the SK-5208 control panel as shown in Figure 3-14.
5. Set the ID number (see Figure 3-13 for ID DIP switch location). See also Section 3.14.1for
information on setting ID numbers.
6. Reconnect power to the control panel.

3-26 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Control Panel Installation

3.14.3.2 Wiring Relays


The four on-board relays can be triggered by the active low outputs. For example, the alarm
outputs can all be wired to relay 3 and the trouble outputs can be wired to relay 4
(see Figure 3-17).
C1 is the coil for the relay 1, C2 is the coil for relay 2, C3 and C4 are the coils for relays 3 and
4 respectively.

Relay Rating
2.5A @ 30 VDC/120 VAC

Figure 3-17 Relay Wiring on the SK-5280


Note: Figure 3-17 uses A7 and T7 to activate relays 3 and 4 as an example. However, any of the outputs can be
used to trip any of the relays.

3.14.3.3 Wiring LEDs to Outputs


The outputs (A1-A10 and T1-T10) can be used to operate LEDs used in a remote annunciator
(see Figure 3-18). Outputs A1-A10 are alarm outputs for the zones corresponding to those
outputs. For example, if the SK-5280 is programmed to output for zones 11-20, then outputs
A1-A10 will correspond with zones 11 through 20.
Outputs T1-T10 are trouble outputs for the zones corresponding to those outputs. for example,
if the SK-5280 is programmed to output for zones 21-30, then outputs T1-T10 will correspond
with zones 21-30.

Figure 3-18 LED Wiring on the SK-5280

P/N 151204 3-27

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

3.14.4 Model SK-5217 Zone Expander Installation


The Model SK-5217 provides the SK-5208 with ten additional Class B (style B) zones. The
SK-5217 connects to the SK-5208 control panel via the SBUS as shown in Figure 3-19.

SK-5217

Control Panel
Supervised
Power Limited
Class B

Figure 3-19 SBUS Connections

3-28 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Control Panel Installation

3.14.4.1 Zone Inputs


Figure 3-20 and Figure 3-21 shows how to wire detectors to the SK-5217. Use a 4.7k end of
line resistor for each Class B circuit. The EOL must be wired in parallel with the normally
open contact farthest from the panel. See Appendix A for a list of the smoke detectors that can
be used with the SK-5217.
Maximum circuit Resistance - 50 ohms
Maximum Total alarm current for all class B (style A) zones - 1 A
Maximum Standby Current per Zone: 3.0 mA
Maximum Alarm Current per Zone: 95 mA
Voltage: 17.5 to 28 VDC
Device ID Dip Switches

Supervised
Power Limited

4.7kΩ
UL Listed
EOL Resistor
Model 7628

Figure 3-20 Model SK-5217 Two-wire Detectors

Figure 3-21 4-Wire Detector Connections

P/N 151204 3-29

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

3.14.4.2 Mounting Instructions


The SK-5217 into a metal bracket and standoffs in the SK-5208 cabinet or into SK-2190
accessory cabinet.

Mounting the SK-5217 into SK-5208 Cabinet


Follow these steps to properly mount the SK-5217 zone expander into the SK-5208 cabinet:
1. Remove power from the control panel.
2. Mount the SK-5217 onto the standoffs and bracket located in the cabinet. See Figure 3-22.

Figure 3-22 Installing the SK-5217 Into the SK-5208 Cabinet

3. Connect the SK-5217 to the SK-5208 control panel as shown in Figure 3-19.
4. Wire the zone inputs to the zone expander as shown in Figure 3-20.
5. Set the ID code (see Section 3.14.1).
If ID code 1 is selected the SK-5217 will input zones 11 - 20.
If ID code 2 is selected the SK-5217 will input zones 21 - 30.
6. Reconnect power to the control panel.

3-30 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Control Panel Installation

Mounting the SK-5217 into the SK-2190 Accessory Cabinet.


Follow these steps to properly mount the SK-5217 zone expander into the SK-2190 cabinet:
1. Mount the remote cabinet using the cabinet mounting holes. See Figure 3-23.
Refer to Section 3.5 for proper cabinet mounting procedures.
2. Remove power from the control panel.
3. Mount the SK-5217 onto the standoffs and bracket located in the cabinet. See Figure 3-23.

Mounting
Mounting Holes
Holes

Figure 3-23 Model SK-5217 Remote Installation

4. Connect the SK-5217 to the SK-5208 control panel as shown in Figure 3-19.
5. Set the ID code (see Section 3.14.1).
If ID code 1 is selected the SK-5217 will input zones 11 - 20.
If ID code 2 is selected the SK-5217 will input zones 21 - 30.
6. Wire the zone inputs to the zone expander as shown in Figure 3-20.

P/N 151204 3-31

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

3.14.5 Model 5824 Installation Instructions


The Model 5824 provides the 5208 with the ability to communicate to a serial or parallel
printer to print the event log. You can use one 5824 on the 5208. The 5824 is for ancillary use
only.

3.14.5.1 Mounting the 5824 Module


The 5824 comes in a plastic enclosure, follow these steps to mount the 5824’s plastic
enclosure:
1. Remove the 5824’s cover. Use a small screw driver if necessary.
2. Remove the 5824 circuit board from the base by pushing outward on the base snap
retaining tabs and lifting the circuit board out.

Mounting Holes

Snap
Retaining Tabs

Mounting Holes
Base

Figure 1: 5824 Circuit Board And Plastic Base

3. Mount the plastic base.


4. Replace the circuit board in the plastic base.
Note: It may be necessary to connect the wiring to the circuit board before the board is replaced in the base. See
Section 3.14.5.2.
5. Connect the 5824 to the 5208.
6. Set the device ID (see Section 3.14.1). See also Figure 3-25 for ID selector switch
location.

3-32 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Control Panel Installation

3.14.5.2 5824 SBUS Connections


Figure 3-24 illustrates how the 5824 connects to the 5208 control panel.

Control
Panel Supervised
Power Limited

5824

Figure 3-24 5824 Connections

Serial Port

5824

Parallel Port
ID Selector
Switches

Figure 3-25 Model 5824 Serial/Parallel Port, and ID Selector Switch location

P/N 151204 3-33

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

3.15 Special Applications

3.15.1 Model 5220 Direct Connect Module


The 5220 Direct Connect module can be used with the SK-5208 to meet NFPA 72 standards.
The 5220 requires four connections to the SK-5208 and provides outputs for city box and
polarity reversal applications. The 5220 cannot be used for sprinkler supervisory.
The 5220 provides a current that reverses polarity during alarm or removes current during a
trouble condition. Maximum voltage 27.3 VDC.
Note: The 5220 Direct Connect Module will activate for alarm and trouble conditions during a Walk Test. To
disable alarm activation during Walk Test, bypass the NAC programmed for Direct Connect before
entering the Walk Test mode. To bypass the NAC, press; 10 + NAC# + * + Code (repeat to un-bypass
NAC). The Direct Connect relay will indicate trouble until the NAC is un-bypassed.

3.15.1.1 City Box Connection


This section describes how to connect the SK-5208 to a municipal fire alarm box or “city box”
as required by NFPA 72 Auxiliary Protected Fire Alarm systems for fire alarm service. The
city (master) box is an enclosure that contains a manually operated transmitter used to send an
alarm to the municipal communication center which houses the central operating part of the
fire alarm system.
The maximum coil and wire resistance (combined) must not exceed 30 ohms.
To install the 5220 for city box connection:
1. Locate the knockout on the right side of the SK-5208 cabinet to connect the 5220 using a
short piece of conduit (must not exceed 20 feet in length).
2. Wire the 5220 to the SK-5208 as shown in Figure 3-26. This drawing also shows how to
connect the city box coil to terminals 3 and 4 on the 5220.
3. Program NAC #4 to be direct connect from the NAC Options menu. Relay #4 will
automatically be configured to indicate system troubles.
Note: It is not possible to reset the remote indication until you clear the condition and reset the SK-5208.

5220
City Box
Coil Resistance
14.5 Ω

Supervised for
Opens and Ground Faults

Control
Panel

Figure 3-26 City Box Connection

3-34 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Control Panel Installation

3.15.1.2 NFPA 72 Polarity Reversal


When the 5220 is wired and programmed for polarity reversal, it reports alarm and trouble
events to a remote site. Alarms will override trouble conditions and it will not be possible to
reset the remote indicator until the condition is cleared and the SK-5208 panel is reset.
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition.
To install the 5220 for polarity reversal, follow the steps below:
1. Locate the knockout on the right side of the SK-5208 cabinet to connect the 5220 using a
short piece of conduit (must not exceed 20 feet in length).
2. Wire the 5220 to the SK-5208 using the four-wire pigtail provided as shown in Figure 3-
27 (next page). This diagram also shows how to connect the 5220 to the remote indicator.
3. Program one of the notification circuits to be Direct Connect (Figure 3-27 uses NAC 4 and
Relay 4). The relay and NAC circuits are paired when selected as direct connect. For
example, if NAC 4 is programmed as Direct Connect then relay 4 used for the trouble
output. Do not program the NAC for Silence or Supervision (NACs with EOL).
4. If necessary, adjust circuit current using potentiometer R10 on the 5220 board. Normal
circuit current is 4-to-8 mA with a 1k ohm remote station protected premise unit.
Maximum circuit resistance is 3k ohm.
Trouble Contacts Supervised Intended for connection to a polarity
For Opens and Ground Faults reversal circuit of a remote station
receiving unit having compatible ratings.

All Other Wires


Supervised, Power Limited

UL Listed

Figure 3-27 Polarity Reversal Connection

P/N 151204 3-35

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

3.15.2 Keltron 95M3158 Tones Transmitter Module


This section of the manual shows the specific connections you will make when wiring the SK-
5208 to the Keltron 95M3158 Tones Transmitter Module (3158). Refer to the installation
sheet shipped with the 95M3158 for complete information. (Note: The 3158 is not available
from Silent Knight.)
Note: The 3158 Keltron Module must be mounted within 3 feet of the control panel and all wiring must be run in
conduit. The Keltron Module shall be enclosed in the TBX1 enclosure.
1. Wire the 3158 to the SK-5208 as shown in the Figure 3-28.
2. Program NAC 4 for Direct Connect (see Section 4.2.4).
3. Program NAC 3 for Supervisory (see Section 4.2.4).
4. Program NACs 3 and 4 as unsupervised (NACs With EOL). See Section 4.2.4.
5. Program NAC 3 cadence as Steady (see Section 4.2.3).

Trouble Contacts Supervised For


Opens and Ground Faults

See Table 3-4 for electrical


ratings.

All Other Circuits Supervised


Power Limited

Note: The term FACP Term. refers to terminals on the SK-5208

Figure 3-28 Wiring the Keltron 3158 to the SK-5208

3-36 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Control Panel Installation

3.15.3 Using a MR-201/T Control Relay From Air Products


When the MR-201/T control relay is wired for polarity reversal, it reports alarm and trouble
events to a remote site. Alarms will override trouble conditions and it will not be possible to
reset the remote indicator until the condition is cleared and the control panel is reset.
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition.
Current: 15 mA max.
Operating Voltage: 24 VDC nominal
Resistance: 4 KΩ
To install the MR-201/T for polarity reversal, follow the steps below:

1. Wire the MR-201/T as shown in Figure 3-29.


Intended for Connection to a Polarity Reversal
Circuit of a Remote Station Receiving Unit
Having Compatible Rating.

Figure 3-29 Wiring the MR-201/T

2. Program the NAC circuit as a non silence NAC (see Section 4.3).

P/N 151204 3-37

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

3-38 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Section 4
Programming

The SK-5208 control panel can be programmed from either the on-board annunciator or the
SK-5235 remote annunciator. You must be in Programming Mode to program the control
panel.

4.1 Keypad Operation During Programming

This section describes the function of the buttons on the keypad while in program mode.

Operation/Button Operation/Description
Enter Step Programming
mode Press 2 7 , followed by installer level code (the factory programmed code is
123456 or 5208). See Section 4.2.6 for user code programming information.
Moving through When you have entered programming correctly, the display will show Zone 1 Options. Press
programming
to move to next programming option. See Table 4-4 for list of programming options
(column 1) and their menu items (column 2).

When the display shows the option you wish to program press to program items in this
option.
If you receive a trouble beep and the message TRY AGAIN appears you are not
using an installer level code.
Exit Step Programming
Press . You are prompted to save programming changes. The default is No. Press the
up or down arrow to select Yes to save programming changes. Press Enter to complete the
save and return to normal operation mode.
Accepts the entered data and scrolls down to the next menu item.
Down Arrow
Accepts the entered data and scrolls down to the next menu item.
Enter Button
Scrolls backwards through the programmable items list for the currently selected option.
Left Arrow
Scrolls forward through the programmable options list or choices for an the selected item.
Right Arrow
Enables extended programming list so you can scroll through lists of items that have multiple
Silence Button components such as, Zone 1 -30. See Section 4.1.2 for an example.
Accepts the entered data and scrolls up to the next menu item.
Up Arrow
Used as shift key when entering special characters (A, B, C, D, or E characters). See Section
* Button
4.1.1 for more information.

# Clear entry.
# Button

P/N 151204 4-1

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

4.1.1 Special Characters


Special characters are characters used while dialing such as pause, *, #, or 2nd dial tone. Table
4-1 list the Special characters and what they mean.
Table 4-1: Special Characters

To Enter: Press LCD Display


Pause 1 A

* 2 B

# 3 C

2nd Dial Tone 4 D

4.1.2 Enabling Extended Programming List


While programming there are several programming options that have multiple components
that can be programmed within that menu item, such as Zones, NAC Cadence, User Codes,
Accounts, etc. However when you scroll through these options only the first one may be
displayed (see Figure 4-1). In order to view and program subsequent items the Silence button
must be pressed. This enables you to move through the other Zones, NAC Cadence, etc.
Example:
If the Zone 1 Options is displayed (see Figure 4-1) and you want to program zone 2 options,
press the button.

Initial Display Display After Silence Button Pressed

Right Arrow Pressed then


Display Moves to Next Zone Number

Figure 4-1 Extended Programming List Access Example

The display will add brackets around the zone number (see Figure 4-1). To move to the next
zone number press the right arrow to go forward through the zone numbers or the left arrow to
go backward through the zone numbers. Press the Silence button again to remove the bracket
and lock the menu on this Zone number, NAC number, or Relay, etc.
This Feature works for the following programming options: Zone Options, NAC Cadence,
User Codes, Accounts, Line Options, and SK-5280 Options.

4-2 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Programming

4.2 Programming Flow

Figure 4-2 provides an overview of the programming menu flow. Figure 4-3 through Figure 4-
13 illustrate the programming flow within each option. The arrows indicate how to maneuver
through programming.

Figure 4-2 Programming Overview Flow Chart

P/N 151204 4-3

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

4.2.1 Zone Options


Figure 4-3 illustrates, in more detail, the programming flow when in the zone options menu.

Figure 4-3 Zone Options

4-4 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Programming

4.2.2 Misc System Option


Figure 4-4 illustrates, in more detail, the programming flow when in the misc system menu.

Figure 4-4 Miscellaneous System Options

P/N 151204 4-5

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

4.2.3 NAC Cadence


Figure 4-5 illustrates, in more detail, the programming flow when in the NAC cadence menu.

Figure 4-5 NAC Cadence

4.2.3.1 Cadence Patterns


The cadence patterns shown in Table 4-2 can be selected for NAC outputs. Each NAC can
select an output pattern. Special cadence patterns can be selected for fire drill or an auxiliary
input switches used with the system.
Table 4-2: Cadence Patterns

Pattern Description
# Name
(Patterns repeat until condition is cleared)
1 Constant Output Continuous sound
2 March Code Output

3 ANSI S-3.41 Code Output

4 Single Stroke BI

5 California Code

6 System Sensor Sync. Provides Synchronization for visual and audible devices.
7 Wheelock Sync.
8 Gentex Sync.
9 Faraday Sync.
10 Amseco Sync.

4-6 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Programming

4.2.4 NAC Options


Figure 4-6 illustrates, in more detail, the programming flow when in the NAC options menu.

Figure 4-6 NAC Options Programming Menu

P/N 151204 4-7

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

4.2.5 Relay Options


Figure 4-7 illustrates, in more detail, the programming flow when in the relay options menu.

Figure 4-7 Relay Options Programming Menu

4-8 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Programming

4.2.6 User Code


Figure 4-8 illustrates, in more detail, the programming flow when in the user code menu.

Figure 4-8 User Code Programming Menu

P/N 151204 4-9

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

4.2.7 Account
Figure 4-9 illustrates, in more detail, the programming flow when in the account menu.

Figure 4-9 Account Programming Menu

Must The dialer MUST report events in this family to this account.
Selecting Must makes an account a primary reporting account. The dialer will try to report the event to the primary
account until it exceeds the “Account Tries” value. When the dialer has exceeded the Account Tries retry limit, it will
switch to a backup account (a “Can Report” or “Yes” account, see below). If the dialer cannot report the event to any of
the backup accounts, it will return to the primary account and repeat the process until it exceeds the a total of 10 attempts.
When the Account Tries limit is exceeded, an Account Trouble condition is generated and a local trouble will sound.
Yes Can Report. Selecting Y makes this a backup account for this event family. The dialer will report to this account only if it
was previously unable to report the event to a Must account.
No No events in this family will ever be reported to this account.

Note: CIC and Phone number can also use special characters as described in Section 4.1.1.

4-10 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Programming

4.2.8 Computer Options


Figure 4-10 illustrates, in more detail, the programming flow when in the computer options
menu.

Figure 4-10 Computer Options Programming Menu


Note: Computer CIC & Phone can also use special characters as described in Section 4.1.1.

4.2.8.1 Computer Code


In order to remote download to a control, the computer code programmed in the panel, and the
computer code used in the downloading software must match.
! Important!
Remote downloading can only be used for Central Station Signaling Services, if this
system does not meet Central Station Signaling requirements, this feature must be
set to zero.

P/N 151204 4-11

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

4.2.9 Line Options


Figure 4-11 illustrates, in more detail, the programming flow when in the line options menu.

Figure 4-11 Line Options Programming Menu


Note: Line prefix can also use special characters as described in Section 4.1.1.

4-12 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Programming

4.2.10 Misc Reporting


Figure 4-12 illustrates, in more detail, the programming flow when in the miscellaneous
reporting menu.

Figure 4-12 Misc Reporting Programming Menu

P/N 151204 4-13

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

4.2.11 5280 Outputs


Figure 4-13 illustrates, in more detail, the programming flow when in the SK-5280 outputs
menu.

Figure 4-13 5280 Outputs Programming Menu

If Zones 1-10 is selected then the SK-5280 will output when alarms and troubles occur for
zones 1 through 10. If Zones 11-20 is selected then SK-5280 will output when alarms and
troubles occur for zones 11 through 20. If Zones 21-30 is selected then the SK-5280 will
output when alarms and troubles occur for zones 21-30.
If System is selected then the SK-5280 will output as shown in Table 4-3 for the following
system conditions:
Table 4-3: System Outputs

SK-5280 Output
Output For:
Terminal
A1 Fire Alarm
A2 Waterflow Alarm
A3 Supervisory
A4 Aux Alarm
A5 Prealarm
A6 Trouble
A7 Communications Fail
A8 Communicating
A9 Alarm Silenced
A10 Trouble Silenced
T1 Low AC
T2 Low Battery
T3 Relay 1 Active
T4 Relay 2 Active
T5 Relay 3 Active
T6 Relay 4 Active
T7 NAC 1 Active
T8 NAC 2 Active
T9 NAC 3 Active
T10 NAC 4 Active

4-14 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Programming

4.2.12 5824 Expander Options


Figure 4-14 illustrates, in more detail, the programming flow for the 5824 serial/parallel
module.

Figure 4-14 5824 Programming Options Flow Chart

P/N 151204 4-15

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

4.2.13 DST/Clk Options


Figure 4-15 illustrates the programming flow for the Daylight Saving Time (DST) and clock
source options.

Figure 4-15 DST/Clk Options Flow Chart

4-16 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Programming

4.3 Programming Options

Table 4-4 list all the programming options and the items that can be modified within those
programming option menus.
Note: Programming options that have a # in the Programming Options column have multiple programmable
components. See Section 4.1.2 for additional information.

Table 4-4: Programming Options


Programming
Menu Item Choices Default Comments
Option
Programmable through SKSS downloading
software. To program through On-board or remote
annunciator:
1. Press * to activate.
2. Press Up or Down arrow to move through
character set.
Zone # Location
3. Press Left or Right arrow to move cursor to
desired character location.
4. Repeat steps 2 and 3 until location name is
entered.
5. Press Enter when the desired location name is
complete.
Not Used
Fire 
Waterflow
Supervisory
Undefined
Heat
Zone (1-30) # Cold
Options Water
Zone # Type Will generate an AC Trouble for either an open or
shorted input. The report to the receiver will be
AC Delay
delayed until the AC Delay timer expires. (See
Section 4.2.10 for AC Delay Time programming.)
A shorted input will reset active alarms. This type
Ext. Reset of zone is local only. No troubles will be reported
to the central station receiver.
A shorted input will silence alarms and troubles.
Ext. Silence This type of zone is local only. No troubles will be
reported to the central station receiver.
No  Zone will report when activated.
Zone # Local
Yes Local Zone, will not report when activated.
No Zone cannot be bypassed.
Zone # Disable
Yes  Zone can be bypassed.
1 Sec 
4 sec
Zone # Response
16 sec
40 sec

P/N 151204 4-17

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

Table 4-4: Programming Options


Programming
Menu Item Choices Default Comments
Option
Note: Alarm verification feature must not be
None  used if the FACP is being used for releasing.
Smoke verification for zones with 2- or 4-wire
Smoke detectors. Do not use any other type of device on
this circuit if Smoke Verification is selected.
Activated zone will start a prealarm timer that
counts down from a user programmed value (see
Prealarm Section 4.2.2 for prealarm time programming). If
the timer reaches zero before the panel is reset, a
general alarm will then be sounded.
Verify # Options Crossalert A
Crossalert B
See Section 5.5.
Interlock A
Interlock B
Manual Release A
See Section 5.5.
Manual Release B
Zone (1-30) #
Options Smoke verification for zones with 2-wire detectors
and contact type devices, such as pull stations,
Enhanced Smoke used on the same circuit. If the alarm current is
greater than 78 mA, the smoke verification cycle
will not occur.
Alarm sounds for this zone cannot be
No 
automatically silenced.
Zone # Auto Sil
Alarm sounds for this zone can be automatically
Yes
silenced.
Alarm sounds for this zone cannot be manually
No
silenced.
Zone # Man Sil
Alarm sounds for this zone can be manually
Yes 
silenced.
Zone # NAC Select the number of each NAC to operate with
____
this zone in alarm.
Zone # Relay Select the number of each Relay to operate with
____
this zone in alarm.
Enter a value from 0 Enter time duration for prealarm verification.
Prealarm Time 40 seconds
to 60
No on-board or 5235 remote PZT sound for
No
Sound Prealarm prealarms.
Yes  5235 and on-board PZTs will sound for prealarms.
This feature selects the time in minutes in which
Enter a value from 0
Auto Silence 8 minutes the NAC will automatically silence. 0 = no
to 60
automatic silence
Misc System No  Supervisory type zones will self restore.
Latch Supervise Supervisory type zones must be reset after any
Yes
supervisories conditions.
1
Class A Zone Class A.
2
Touchpad numbers that are selected here will be
5235 Keypads ______
supervised.
1 Enables zones 11-20.
5217 Expanders
2 Enables zones 21-30

4-18 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Programming

Table 4-4: Programming Options


Programming
Menu Item Choices Default Comments
Option
No  If Yes is selected you are not required to enter a
Code for operator level functions, such as Reset,
Misc System
Plex Door Silence, and Display Event History.
(cont.) Yes Note: If this option is enabled, the PLEX-2
accessory must be installed on the control panel.
Constant Additional cadence patterns are programmable
March Code only through down loading software. See also
ANSI S-3.41 Code All NACs Section 4.2.3.
Single Stroke BI
California Code
NAC (1-4) # Cadence
System Sensor Sync.
Wheelock Sync.
Gentex Sync.
Faraday Sync.
Amseco Sync.
No NACs If number is selected that NAC may be silenced.
Silence NAC ____
selected
All NACs If number is selected that NAC will activate for
Fire NAC 1234
selected any fire alarm.
No NACs If number is selected that NAC will activate during
Prealarm NAC ____
selected the prealarm timer countdown.
No NACs If number is selected that NAC will activate for
Aux NAC ____
selected undefined, heat, cold, and water alarms.
All NACs If number is selected that NAC will activate for
Waterflow NAC 1234
selected waterflow alarms.
No NACs If number is selected that NAC will activate for
Supervisory NAC ____
selected sprinkler supervisories.
If you have a single zone, that is programmed for
No NACs
Crossalert A NAC _ _ _ _ crossalarm verification, in alarm, all NAC output
selected
select for this option will activate.
Activates during the group “A” releasing action.
No NACs This circuit would be connected to a UL listed
Release A NAC ____
NAC Options selected releasing solenoid. See Table 5-4 for compatible
solenoids.
If you have a single zone, that is programmed for
No NACs
Crossalert B NAC ____ crossalarm verification, in alarm, all NAC output
selected
select for this option will activate.
Activates during the group “B” releasing action.
No NACs This circuit would be connected to a UL listed
Release B ____
selected releasing solenoid. See Table 5-4 for compatible
solenoids.
No NACs If number is selected that NAC will activate for
Trouble NAC ____
selected any trouble condition.
for alarms when using the 5220 module for city
No NACs
Direct Conn NAC ____ box or polarity reversal. Corresponding relay
selected
number will automatically be selected.
All NACs If number is selected that NAC output must be
NACs With EOL 1234
selected supervised with an 4.7 kΩ UL listed EOL.
All NACs If number is selected that NAC will activate during
Fire Drill NAC 1234
selected a fire drill.

P/N 151204 4-19

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

Table 4-4: Programming Options


Programming
Menu Item Choices Default Comments
Option
If a relay is selected, that relay can be silenced for
No Relays
Silence Relay ____ Trouble and Supervisory conditions only. (This
selected
includes relays programmed for AC Trbl.)
Relay 1 If a relay is selected, that relay will activate for fire
Fire Relay 1___
selected alarm conditions.
No Relays If a relay is selected, that relay will activate for
Prealarm Relay ____
selected prealarm conditions.
No Relays If a relay is selected, that relay will activate for
Aux Relay ____
selected Auxiliary conditions.
No Relays If a relay is selected, that relay will activate for
Waterflow Relay ____
selected waterflow conditions.
No Relays If a relay is selected, that relay will activate for
Superv Relay ____
selected supervisory conditions.
No Relays If a relay is selected, that relay will activate for
Relay Options Crossalert A Relay _ _ _ _
selected crossalarm conditions.
No Relays If selected will activate for releasing group “A”.
Release A Relay ____
selected
No Relays If a relay is selected, that relay will activate for
Crossalert B Relay _ _ _ _
selected crossalarm conditions.
No Relays If selected will activate for releasing group “B”.
Release B Relay ____
selected
Relay will be activated when no troubles exist and
Trouble Relay ___4 4
will deactivate when a trouble condition occurs.
Relay 1 If a relay is selected, that relay will activate for fire
Fire Drill Relay 1___
selected drills.
If a relay is selected, that relay will be activated
No Relays
AC Trbl ____ when AC is normal and will deactivate when a
selected
Low AC condition exists.
5208 and
Installers
123456
Code # Type
User (1-10) # Operators 1111
Code Not Used
Enter 3 to 6 digit Enter any value from 001 to 999999.
User # Code
number

4-20 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Programming

Table 4-4: Programming Options


Programming
Menu Item Choices Default Comments
Option
1: 105208 Enter any value from 000001 to 999999. Account
Enter a 6-digits 2: 205208 numbers with less than 6 digits must use leading
Account <#> #
number 3: 305208 zeros. For example, if the code 321 is used, it must
4: 405208 be entered as 000321.
Carrier Identification Code is the prefix that needs
to be dialed before a phone number to access a
particular long distance carrier. Use special
CIC <#> # Enter up to 8 digits
characters to add pauses, #, *, and “2nd dial tone”
characters into the phone number. See Section
4.1.1 for special characters.
Phone <#> # Enter up to 16 digits See Section 4.1.1 for special characters.
SIA8 
SIA20
Contact ID
Account # Format
SK4/2 1400
3/1 1400
3/1 2300
Account # Tries 1 to 5 3
Account (1-4) # No  Do not report alarm events.
Report # Alarm Yes Can report alarm events.
Must Must report alarm events.
No  Do not report alarm restores.
Report # Restore Yes Can report alarm restores.
Must Must report alarm restores.
Do not report sprinkler supervisory, system
No  troubles, zone troubles, zone bypasses, and zone
restores.
Report # Trouble Can report sprinkler supervisory, system troubles,
Yes
zone troubles, zone bypasses, and zone restores.
Must report sprinkler supervisory, system troubles,
Must
zone troubles, zone bypasses, and zone restores.
Do not report manual test, auto test, downloading
No 
pass, downloading fail, data lest, and walk test.
Can report manual test, auto test, downloading
Report # Test Yes
pass, downloading fail, data lest, and walk test.
Must report manual test, auto test, downloading
Must
pass, downloading fail, data lest, and walk test.
Enter any value from 000001 to 999999. Account
numbers with less than 6 digits must use leading
Computer Account Enter 6-digit number 505208
zeros. For example, if the code 321 is used, it must
be entered as 000321.
Carrier Identification Code is the prefix that needs
to be dialed before a phone number to access a
particular long distance carrier. Use special
Computer Computer CIC Up to 8 digits.
characters to add pauses, #, *, and “look for
Options
second dial tone” characters into the phone
number. See Section 4.1.1 for special characters.
Computer Phone up to 16 digits See Section 4.1.1 for special characters.
The computer code must match the computer code
in the remote downloading computer in order to
Computer Code 1 to 6 digits 0
perform a remote download. See also Section
4.2.8.1.

P/N 151204 4-21

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

Table 4-4: Programming Options


Programming
Menu Item Choices Default Comments
Option
Not Used  This disables the phone line.
Attempts 1 through 6 will be DTMF, then the
dialer will alternate between Rotary and DTMF for
DTMF/USA Rotary
attempts 7 through 10, Rotary Make/Break ratio is
40/60.
Attempts 1 through 10 will be Rotary only, with a
USA Rotary Only
Make/Break ratio of 40/60.
Line # Dial Type
DTMF Only Attempts 1 through 10 will be DTMF only.
Attempts 1 through 6 will be DTMF, then the
dialer will alternate between Rotary and DTMF for
DTMF/Euro Rotary
attempts 7 through 10, Rotary Make/Break ratio
33/67.
Attempts 1 through 10 will be Rotary only, with a
Euro Rotary Only
Make/Break ratio of 33/67.
Line (1-2) # No  Yes enables Ground Start phone functions. A
Options Line # GS ground start relay (Model 5211) is required if this
Yes feature is enabled (see Figure 3-2).
Line 1: 2 Number of rings before the panel will answer an
Line # Rings 0 - 15
Line 2: 10 incoming telephone call.
This feature is used in installations where an
answering machine is on the same phone line that
No 
the control panel is on. The answering machine
may interfere with a computer download.
Line # Ans Mach When enabled (Yes) the computer calls the control
panel and the phone line rings twice, hangs up and
calls again (within 10 to 60 seconds). When the
Yes
control panel see two more rings on the phone line
it will answer and acknowledge the calling
computer.
Line # Prefix Up to 8 digits See Section 4.1.1 for special characters.
Selects the time of day the control will send an
Test Time 00:00 - 23:59 12:00
automatic test signal to a central station receiver.
Selects the delay time (in hours) before the control
AC Delay 0-30 Hours 2
will report an AC power loss to the central station.
No zone information will be reported just test
No 
begin and test end.
Report Walk Test
Test begin, test end, and all events in between will
By Zone
be reported to central station.
0-9 Alarms for Fire, Waterflow, Undefined, Heat,
*3/1 Alarm 0
Misc Reporting * Event code for 3/1 Cold, and Water events.
and 4/2 reporting Alarms restores for Fire, Waterflow, Undefined,
*3/1 Alarm Rst formats. 2
Heat, Cold, and Water events.
*3/1 Supervisory 6 Sprinkler supervisories.
Restore reports for Troubles, Supervisories, and
*3/1 Restore 7 unbypasses. The only exceptions are the restores
listed as alarm restores.
All system and zone troubles, and zone/NAC
*3/1 Trouble 8
bypasses, and NACs troubles.
*3/1 Test 9 All test events.

4-22 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Programming

Table 4-4: Programming Options


Programming
Menu Item Choices Default Comments
Option
Not Used 
Zones 1_10
5280 (1 - 8) #
5280 # Zones 11_20
Outputs
Zones 21_30
System
Sets the serial bus address for the 5824. Use a 0 to
5824 ID 0-7 0
disable this feature.
Yes  If yes then all events are sent to the printer.
Event Log
No
Selects the number of seconds the printer can be
Prn Off Line 0 - 30 Seconds 20
off line before a trouble is generated.
Yes  If yes is selected then data is sent to the serial port.
Serial Prn If no is selected then data is sent to the parallel
No
port.
9600  Select the Baud rate at which your printer requires
19.2K to communicate properly. Consult installation
5824 Expander 75 manual for the printer you are using.
110
134.5
150
Baud Rate 300
600
1200
2000
2400
4800
1800
8  Select the number of data bits that your printer
5 requires for proper communication. Consult
Data Bits installation manual for your printer.
6
7
1  Select the number of stop bits that your printer
5824 Expander
Stop Bits 2 requires for proper communication. Consult
0 installation manual for your printer.
None  Select the Parity that your printer requires for
Parity Even proper communication. Consult installation
Odd manual for your printer.

P/N 151204 4-23

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

Table 4-4: Programming Options


Programming
Menu Item Choices Default Comments
Option
The panel’s AC line frequency is selectable for 60,
60 Hz  50 Hz, or Internal. AC Frequency feature dictates
how the control panel will calculate time based on
the AC line frequency used in the installation site.
The “Internal” option can be used in areas where
50 Hz
Clock Source the AC line frequency is not dependable and you
want the panel to calculate time from the internal
crystal. The internal crystal is not as accurate as
the AC power source and either 60 Hz or 50 Hz
Internal
should normally be selected. The panel defaults to
the 60 Hz. selection
No  No automatic clock adjust for Daylight Saving.
Automatically changes system clock between
Daylight Saving Time (DST) and standard time.
Before January 1, 2007, the system clock will
switch to DST on the first Sunday in April at 2:00
a.m. and will revert to standard time on the last
Auto DST Adjust Sunday in October at 2:00 a.m. On January 1,
Yes 2007, the system clock will be adjusted according
to the values set in the DST Start (Wk and Mo) and
DST/Clk
DST End (Wk and Mo) options. Default values for
Options
these fields match federal law: DST begins on the
second Sunday in March at 2:00 a.m. and reverts
to standard time on the first Sunday of November
at 2:00 a.m.
1st Sunday Setting determines the week of the month in which
2nd Sunday  Daylight Saving Time is to start. If you always
3rd Sunday want the change to occur on the last Sunday of the
DST Start (Wk)*
month, select the Last Sunday option regardless of
4th Sunday
whether there are four or five Sundays in the
Last Sunday month.
Setting determines the month in which Daylight
DST Start (Mo)* Jan – Dec Mar
Saving Time is to end.
1st Sunday  Setting determines the week of the month in which
2nd Sunday Daylight Saving Time is to end. If you always
3rd Sunday want the change to occur on the last Sunday of the
DST End (Wk)*
month, select the Last Sunday option regardless of
4th Sunday
whether there are four or five Sundays in the
Last Sunday month.
Setting determines the month in which Daylight
DST End (Mo)* Jan – Dec Nov
Saving Time is to start.
* This option is not recognized by the panel until January 1, 2007. Before January 1, 2007, the panel will recognize the values
described above in the Auto DST Adjust option.

4-24 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Section 5
Operation

To operate the SK-5208 you can use either the on-board touchpad or the Model SK-5235
Remote Annunciator.

Figure 5-1 Model SK-5235 Remote Annunciator

Important! Upon initial power up there is a 45 second delay before the initiation circuits become active.
The system will be ready to receive alarms once the display indicates “System Normal”

5.1 Installer & User Keys


An installer key ships with the panel and an operator’s key ships with the SK-5235
(Figure 5-2). The installer key opens the panel door and can be used to perform user
operations without a user code at the panel and the SK-5235. The operator’s key can be used
to perform user operations without a user code but will not open the panel door. All installer
operations require an installer code. To perform user operations without a user code, insert and
turn the key as shown in Figure 5-2. See Table 5-1 for a list of user and installer operations.

Installer Key: Perform user


operations without a user
Normal Operation
code and open panel door.

User Key: Perform user User Operations


operations without a user Enabled
code.
Note: The key can not be removed
when in the user operations position.

Figure 5-2 Keys & Key Operation


P/N 151204 5-1

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

5.2 On-board Touchpad and SK-5235 Operation


Basic operations for the on-board annunciator (touchpad) and SK-5235 are described in Table
5-1. If you are using an annunciator key or the Flex Door option, you are not required to enter
a code for operator level functions.
If no keys are pressed for 4 minutes while in program mode, the system will time out and
resume normal operation.
Table 5-1: Basic Panel Operations Using the On-Board Annunciator and the SK-5235

Do This
How To Display Comments
Press Press*
Message
System performs a display lamp test, a
System Test
Test the system 0 Enter Code communication test, and displays the firmware
Enter Code
number and revision. See 5.2.1 for an example.
Reset Alarm Resets system.
Reset Alarms Enter Code
1 or Enter Code
Clear History Enter Installer Clears event history of all events.
Clear History
2 Enter Code Code
Reset Dialer Resets the dialer and aborts the call to central
Reset the Dialer Enter Code station.
3 Enter Code
Call Computer to Up/ Call Computer Enter Installer Will dial the programmed phone number for the
Download 4 Enter Code Code computer to initiate an up or download.
Displays panel history, including alarms,
Display History History Events
5 Enter Code supervisories, troubles, reports, time and date
Events Enter Code
changes, etc.
Show Status View existing system status. List Alarms first,
Show Status Enter Code supervisories and then troubles.
6 Enter Code
Silence Troubles or Silence
Enter Code
Alarms 7 or Enter Code
Enter 8 digits for the date. For example, to set
Set Date
Set the Date 8 Enter Code the date 08/31/1999 enter 08311999. Press #
Enter Code
to clear incorrect entries.
Set Time Enter the time in 24 hour increments. For
Set the Time Enter Code example, 1:00 pm = 13:00.
9 Enter Code
Disable/Enable a Disable Zone Repeat the process to enable the zone.
Zone # + Enter Code
Zone Enter Code
1 0 NAC # Disable NAC Repeat the process to enable the NAC.
Disable/Enable NAC Enter Code
Enter Code
Fire Drill
Conduct a Fire Drill Enter Code Enter Code To End the Fire Drill press then code.
2 0
Rst Smk Pwr Resets all smoke detector power.
Reset Detectors Enter Code Enter Code
2 1
Walk Test
Walk Test the System Enter Code To End the Walk Test press .
2 2 Enter Code

Menu of Options Press or to


To exit press or wait 15 seconds.
scroll through list.
* Code = any valid operator or installer code.

5-2 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Operation

5.2.1 View Control Panel Firmware Number and Revision

When 0 and the code is entered The system will perform a display lamp test and a
communication test. Also displays Firmware number and revision as shown in Figure 5-3.
Control Firmware Revision Letter
Number

Dialer Firmware Revision Letter


Number

Figure 5-3 Firmware Numbers and Revisions

5.3 Acknowledge Operation

To display an event, first press the , while the event is displayed the event can be

acknowledged by pressing the button again. No code is required to acknowledge events.


The status LEDs (Alarm, Supervisory and Trouble) will flash when an un-acknowledged
alarm, supervisory, or trouble condition exists.
After each event has been acknowledged its associated LED (Alarm, Supervisory, or Trouble
LED) stop flashing and turn on steady. When viewing system status the LCD displays
“Acked” for each individual event once has been acknowledged. The control panel piezo will
silence after all alarms have been acknowledged.
Note: The control panel piezo will continue to sound for Supervisories and Troubles even after the event has been
acknowledged. Supervisories and troubles will silence once the event is restored.
After the event is acknowledged an event is added to the event history buffer. Acknowledged
events in the history buffer will be preceded with an asterisk “*”.

P/N 151204 5-3

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

5.4 LED Indicators


Five light emitting diodes (LEDs) appear in the SK-5208 built in annunciator and remote
annunciator. The chart below explains the meaning of these LEDs.
Table 5-2

LED Status Condition


Off Normal condition
ALARM (red) On System in alarm and all alarms have been acknowledged.
Flashing LED will flash when a alarm condition exists that has not been acknowledged.
Off Normal condition
SUPERVISORY (yellow) On If a supervisory condition exist on the system.
Flashing LED will flash when a supervisory condition exists that has not been acknowledged.
Off Normal condition
TROUBLE (yellow) On Trouble condition exists
Flashing LED will flash when a trouble condition exists that has not been acknowledged.
Off Normal condition.
SILENCED (yellow)
On Alarm or trouble condition has been silenced but condition still exists.
On Panel is running on AC (normal condition); standby battery fully charged.
AC (green) Off Panel has lost all power.
Flashing Panel is running on battery power only or AC power only.

5-4 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Operation

5.5 Releasing Operation


This system can perform two types of releasing operation, cross alarm releasing, and double
interlock releasing operations. Install in accordance with NFPA 72 paragraphs 3-8.3.2.3.3 and
3-8.3.2.3.3.2.

5.5.1 Cross Alarm Operation


The fire alarm control panel has two cross alert groups to select from, Cross Alert A and Cross
Alert B that accommodate releasing water systems.
When two or more zones are programmed to one of these groups then a single activation of
one zone in the group will cause a cross alert condition at the local annunciator and the pre-
alert signal output for that group. (Note: the local annunciator and the pre-alert signal will
continue to sound until it is silenced or until another cross alarm zone within the same group
activates.) If a second zone in the same group activates then both will become active alarm
zones.
If the second zone is not in the same group as the first zone then the cross alert zone will
remain in the cross alert condition and the system will signal the second by how it is
programmed.
The fire alarm control panel has four NAC and relay options that allow NACs and relays to be
selected to indicate the cross alert condition and assign release circuits for each group.

5.5.1.1 Default NAC Settings for Releasing


When “Cross Alert A” is selected in “Zone Options” the NACs are defaulted to the following
settings:
NAC 1 Releasing Circuit
NAC 3 Pre-Alert Signal Circuit
NAC 4 General Alarm Circuit
When “Cross Alert B” is selected in “Zone Options” the NACs are defaulted to the following
settings:
NAC 2 Releasing Circuit
NAC 3 Pre-Alert Signal Circuit
NAC 4 General Alarm Circuit
Table 5-3: Cross Alarm Operation
Inputs Output Results
Cross Zone 1    
Cross Zone 2    
Pull Station    
General Alarm

General Alarm

General Alarm

General Alarm

General Alarm
Release and

Release and

Release and

Release and

Release and
Pre-Alert

Pre-Alert
Normal

P/N 151204 5-5

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

A Model 7641 EOL resistor/diode assembly is required when connecting the FACP to
releasing solenoids. The 7641 allows the FACP to supervise the wiring between its NACs and
the releasing solenoid.
Table 5-4: Approved Releasing Solenoids

Manufacturer Part Number Rating


T8210A107 24 VDC, 16.8 W
Asco
8210G207 24 VDC, 10.6 W

Figure 5-4 Solenoid Wiring Configuration

Do not mix cross alarming zones with smoke verification zones. There must be at least two
automatic detection devices in each protected space. Spacing must be reduced to 0.7 tines the
linear spacing in accordance with NFPA72. See Section 4.2.1 for zone option programming.
Figure 5-5 is an example of how cross alarming may be programmed.

Figure 5-5 Example Showing Smoke Detector Cross Alarm Application

5-6 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Operation

5.5.2 Double Interlock Releasing Operation


A typical double interlock releasing system would be programmed with a minimum of two
zones selected for “Cross Alert A”, one zone selected as “Man. Release A”, and one selected
as “Interlock A”. Additional zones can be selected as Cross Alert or Manual Release.
This double interlock system requires both cross alert and manual release verification zones.
A single manual release and interlock zone can be used without any cross alert zones. In this
system configuration an active manual release and the interlock zone is required to initiate the
release.
Table 5-5 illustrates what will cause a Pre-alert, General Alarm, and a Release.
Table 5-5: Double Interlock Operation

Inputs Output Results


Cross Zone 1        

Cross Zone 2        

Manual
       
Release A
Interlock        

Release and General Alarm

Release and General Alarm

Release and General Alarm

Release and General Alarm

Release and General Alarm


General Alarm

General Alarm

General Alarm

General Alarm

General Alarm

General Alarm

General Alarm

General Alarm
Pre-Alert

Pre-Alert
Normal

If no zones are selected for “Interlock” verification then the system will operate as a standard
cross alarm releasing system (see Section 5.5.1).
See Section 5.5.1.1 for default NAC settings for releasing systems.

P/N 151204 5-7

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

5.6 Smoke Alarm Verification


Figure 5-6 illustrates how the Smoke Alarm Verification cycle operates.

Figure 5-6 Smoke Verification Cycle

During the Confirmation Period if there is no alarm indication then the system will return to
normal operation.

5-8 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Operation

5.7 System Testing


This section describes operation of fire drills, zone testing, and the 24-hour automatic test.

5.7.1 Fire Drills


Fire drills can be run from either the on-board touchpad or the Model SK-5235 Remote

Annunciator. To initiate a fire drill, press 2 0 + Code. The system will sound an
alarm and report a fire test. To end the fire drill, press + Code.

5.7.2 Walk Test


The walk test is designed to be used for on-site testing only.

To enter walk test mode, press 2 2 + Installer Code.


Select the following test parameters:

Enable or
Test Feature Comments
Disable
Use Verify: Yes or No If Yes is selected then this option will be enabled during
Mapped Rlys: Yes or No walk test. If No is selected this option will be disabled
during walk test.
Mapped NACs: Yes or No

The LCD will indicate that you are in walk test mode. When a zone is tripped, the SK-5208
will activate the bell outputs for approximately six second and will cycle smoke power off and
on for the programmed time interval. When smoke power is restored, there is a two-second
power up delay before the zone will respond to additional test inputs.
The system will time out and resume normal operation in 30 minutes if no keys are pressed or
no zones are tripped during the walk test.

To exit walk test mode, press .

5.7.3 Automatic Self Test


The Model SK-5208 lets you select the time of day that the 24-hour automatic test signal will
be sent to the central station. See Sections 4.2.10 and 4.3 for additional information on
automatic test time.

5.7.4 Watchdog Circuit


During normal operation, the control microprocessor of the SK-5208 is constantly running
programs to check inputs and carry out other routine functions. If the program should ever
stop running, the watchdog circuit will automatically detect this and attempt to resume normal
operation by resetting the microprocessors. Each time the watchdog circuit initiates a reset
signal, it will also sound the audible trouble signal for approximately four seconds.

P/N 151204 5-9

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

5.8 Communicating with a Programming Computer


An installer at the panel site can initiate communications between the panel and a computer
running the Silent Knight Software Suite SKSS. In order for this communication to function
properly both the computer (running the software) and the control panel must have matching
computer account numbers and computer access codes.
Before you program in this location you should know how your control panel will
communicate with the downloading computer, either through direct connect (RS232) or via
the phone lines (Internal Modem).

5.8.1 Programming From a Remote Computer Location


The panel can communicate with a Up/Downloading computer using two methods. The
control panel can call the programming computer or the programming computer can call the
control panel.
The programming information for the control panel will be stored in the queue of the
downloading software SKSS P/N 5660. This data packet will have been pre-configured for the
control panel that you are about to program. For more information see SKSS Installation
Manual P/N 151240.

5.8.1.1 Having the Control Panel Call the Remote Computer


If the panel initiates the call to a downloading computer, a phone number must be
programmed in the computer accounts area (see Section 4.2.8).
To initiate communication:

1. Press the 4 or the up arrow until the display reads Call Computer.
2. Enter the Installer Code.
The control panel will then begin the communication process with the remote computer.

5-10 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Operation

5.8.1.2 Having Remote Computer Call the Control Panel


If the computer initiates the call then answering machine bypass (see Section 4.2.8) may need
to be selected.
To initiate communication:
1. From the SKSS Up/Downloading software File Menu, select the download or upload
menu item you want to schedule.

Download Menu Upload Menu

2. In the appropriate locations in the dialog box, enter your selections for the following
options:
File Name: To download, select the file that you want to download. To upload
assign a name to the file that will be uploaded from the panel. You
can use the Browse option to select from the list of available files. If
you do not select a name for the file, it will be automatically named
with the panel model and the date and time of the download.
For downloads, the latest saved version of the file will be sent. This
means if the file you want to send is currently open and has been
changed, save it before you attempt to download.
Account
Number: Enter the panel account number.
Computer Code: Enter the code that allows access to the panel from a PC.
Phone Number: Enter the panel phone number.
Call Option: Select how often and when the call should be placed.
Answering: Select the preferred options if the phone line used by the control
panel has an answering machine installed. This feature is not used
when connecting directly to a panel.
3. Click OK to begin downloading/uploading or to post the job to the Queue.

P/N 151204 5-11

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

5.8.2 Directly Connecting to a Programming Computer


The control panel can be up or downloaded from a computer that is directly connected to the
control panel.
Note: This connection is to be used as a temporary connection and should be disconnected after programming is
completed.
To initiate communication:
1. Connect a serial cable from the control panel to the computer.

To Computer
Serial Port

2. Make sure SKSS software is running and that the up/download task is in the queue.

3. Press the 4 or the up arrow until the display reads Call Computer.
4. Enter the Installer Code.
The control panel will then begin the communication process with the remote computer.

5-12 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Section 6
Reporting

The SK-5208 can transmit information in four different formats. This section describes the
four basic reporting formats of the SK-5208 and the codes that they send to a central station
receiver. Of these four formats some of the formats offer a more specific selection for that
format. For example, you can select a 3/1 format that requires a 1400 or 2300 Hz handshake,
or SIA format that can handle 8 or 20 events per call. Selecting the correct format depends on
the type of receiver that will receive calls from the SK-5208.
The SK-5208 DACT is compatible with Silent Knight Model 9800 and 9500 Digital
Receivers.

6.1 Reporting Formats


This section gives a description of each of the SK-5208 reporting formats. Refer to Table 6-1.
Table 6-1: Reporting Formats Descriptions

Format Name

Category Programming Description


Name Name
Old format, transmits a 3-digit account number and a 1-digit event
3/1 14
code. Transmissions are acknowledged at 1400 Hz.
3/1
Old format, transmits a 3-digit account number and a 1-digit event
3/1 23
code. Transmissions are acknowledged at 2300 Hz.
Tone burst format, transmits a 4-digit account code and 2-digit
4/2 SK4/2 1400
event code. Transmissions are acknowledged at 1400 Hz.
Security Industry Association standard communication format
SIA8
which send a maximum of 8 events per call.
SIA Security Industry Association standard communication format
SIA20 which send a maximum of 20 events per call. Up to a 6-digit
account number.
Ademco Contact ID format. DTMF (Dual Tone Multiple
Contact ID Contact ID Frequency) format. Send a 4-digit account number. Transmission is
acknowledged at both 1400 and 2300 Hz.

P/N 151204 6-1

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

6.2 Reporting Codes


Table 6-2 list the events sent by the SK-5208 and the code that is sent for that event by the
type of reporting format used.
Note: Codes under in the SK4/2 and 3/1 1400 & 2300 column are the codes programmed for 3/1 reporting
formats in Misc Reporting. See Section 4.2.10 for Misc. Reporting options and Table 6-3 for default 3/1
format reporting values.

Table 6-2: Event and Reporting Code by Format

Event SIA8 & 20 SK4/2 3/1 1400 &2300 Contact ID

AC Trouble AT0 T0 Trouble Code 1 301 000


AC Restore AR0 R0 Restore Code 3 301 000
Annunciator Trouble 1-7 ET17 - ET23 T7 - T3 Trouble Code 1 330 017 - 1 330 023
Annunciator Restore 1-7 ER17 - ER23 R7 - R3 Restore Code 3 330 017 - 3 330 023
Bell Trouble 1-4 ET32-ET35 T2 - T5 Trouble Code 1 330 032 - 1 320 035
Bell Restore 1-4 ER32-ET35 R2 - R5 Restore Code 3 330 032 - 3 320 035
Smoke (Loop) Power Trouble ET36 T6 Trouble Code 1 320 036
Smoke (Loop) Power Restore ET36 R6 Restore Code 3 320 036
Aux Power Trouble ET37 T7 Trouble Code 1 330 037
Aux Power Restore ER37 R7 Restore Code 3 330 037
Earth Ground Trouble ET38 T8 Trouble Code 1 330 038
Earth Ground Restore ER38 R8 Restore Code 3 330 038
Keypad Power Trouble ET40 T0 Trouble Code 1 330 040
Keypad Power Trouble ET40 R0 Restore Code 3 330 040
5217 Expander Trouble ET51-ET52 T1 - T2 Trouble Code 1 330 051 - 1 330 052
5217 Expander Restore ER51-ER52 R1 - R2 Restore Code 3 330 051 - 3 330 052
5280 Expander Trouble ET61-ET68 T1 - T8 Trouble Code 1-330 061 - 1 330 068
5280 Expander Restore ER61-ER68 R1 - R8 Restore Code 3-330 061 - 3 330 068
NAC Bypass ET101-ET104 T1 - T4 Trouble Code 1-330 101 - 1 330 104
NAC Restore ER101-ER104 R1 - R4 Restore Code 3-330 101 - 3 330 104
NAC Supervisory (See Note) SS101-SS104 S1 - S4 Supervisory Code 1 203 101 - 1 203 104
NAC Supervisory Restore (See Note) SR101-SR104 R1 - R4 Restore Code 3 203 101 - 3 203 104
Fire Alarm 1-30 FA1 - FA30 A1 - A0 Alarm Code 1 110 001 - 1 110 030
Fire Bypass FB1-FB30 T1 - T0 Trouble Code 1 571 001 - 1 571 030
Fire Alarm Restore 1-30 FH1 - FH30 AR1 - AR0 Alarm Restore Code 3 110 001 - 3 110 030
Fire Test Begin FI1 - FI10 Test 0 Test Code 1 604 000
Fire Trouble Restore 1-30 FJ1 - FJ30 R1 - R0 Restore Code 3 373 001 - 3 373 030
Fire Test End FK0 Test 0 Test Code 1 604 000
Fire Restore/Clean-Me Restore FR1-FR30 R1 - R0 Restore Code 3 110 001 - 3 110 030

Note: These reports are sent for Notification Appliance Circuits that are programmed for releasing operation.

6-2 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Reporting

Table 6-2: Event and Reporting Code by Format

Event SIA8 & 20 SK4/2 3/1 1400 &2300 Contact ID

Fire Trouble/Clean-Me Trouble 1-30 FT1 - FT30 T1 - T0 Trouble Code 1 373 001 - 1 373 030
Fire Unbypass FU1-FU30 R1 - R9 Restore Code 3 571 011 - 3 571 030
Heat Alarm KA1-KA30 A1 - A9 Alarm Code 1 114 001 - 1 114 030
Heat Bypass KB1-KB30 T1 - T0 Trouble Code 1 570 011 - 1 570 030
Heat Alarm Restore KH1-KH30 AR1 - AR0 Alarm Restore Code 3 114 001 - 3 114 030
Heat Trouble KT1-KT30 T1 - T0 Trouble Code 1 370 001 - 1 370 030
Heat Trouble Restore KJ1-KJ30 R1 - R0 Restore Code 3 370 001 - 3 370 030
Heat Restoral KR1-KR30 R1 - R0 Restore Code 3 370 001 - 3 370 030
Heat Unbypass KU1-KU30 R1 - R0 Restore Code 3 570 001 - 3 570 030
Trouble Phone Line #1 LT1 T1 Trouble Code 1 351 000 01
Restore Phone Line #1 LR1 R1 Restore Code 3 351 000 01
Trouble Phone Line #2 LT2 T2 Trouble Code 1 352 000 02
Restore Phone Line #2 LR2 R2 Restore Code 3 352 000 02
Automatic Test (Normal) RP0 Test 0 Test Code 1 602 000
Automatic Test (Abnormal) RY0 Test 9 Test Code 1 608 000
Power Up RR0 T0 Test Code 1 305 000
Downloading Passed RS0 Test 0 Test Code 1 412 000
Data Lost RT0 Test 0 Trouble Code 1 354 000
Downloading Failed RU0 Test 0 Test Code 1 413 000
Manual Test RX1-RX10 Test 1 - Test 0 Test Code 1 601 001 - 1 601 010
Sprinkler Alarm SA1-SA30 A1 - A0 Alarm code 1 113 001 - 1 113 030
Sprinkler Bypass SB1-SB30 T1 - T0 Trouble Code 1 570 001 - 1 570 030
Sprinkler Alarm Restore SH1-SH30 AR1 - AR0 Alarm Restore Code 3 113 001 - 3 113 030
Sprinkler Trouble Restore 1-30 SJ1 - SJ30 R1 - R0 Restore Code 3 370 001 - 3 370 030
Sprinkler Supervisory Restore 1-30 SR1 - SR30 R1 - R0 Restore Code 3 203 001 - 3 203 030
Sprinkler Supervisory 1-30 SS1 - SS30 S1 - S0 Supervisory Code 1 203 001 - 1 203 030
Sprinkler Trouble 1-30 ST1 - ST30 T1 - T0 Trouble Code 1 370 001 - 1 370 030
Sprinkler Unbypass 1-30 SU1-SU30 R1 - R0 Restore Code 3 570 001 - 3 570 030
Untyped Zone Alarm 1-30 UA1-UA30 A1 - A0 Alarm Code 1 140 001 - 1 140 030
Untyped Bypass 1-30 UB1-UB30 T1 - T0 Trouble Code 1 570 001 - 1 570 030
Untyped Alarm Restore 1-30 UH1-UH30 AR1 - AR9 Alarm Restore Code 3 140 001 - 3 140 030
Untyped Trouble Restore 1-30 UJ1-UJ30 R1 - R0 Restore Code 3 370 001 - 3 370 030
Untyped Zone Trouble 1-30 UT1-UT30 T1 - T0 Trouble Code 1 370 001 - 1 370 030
Untyped Zone Unbypass 1-30 UU1-UU30 R1 - R0 Restore Code 3 570 001 - 3 570 030
Water Alarm 1-30 WA1-WA30 A1 - A0 Alarm Code 1 154 001 - 1 154 030
Water Bypass 1-30 WB1-WB30 T1 - T0 Trouble Code 1 570 001 - 1 570 030

P/N 151204 6-3

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

Table 6-2: Event and Reporting Code by Format

Event SIA8 & 20 SK4/2 3/1 1400 &2300 Contact ID

Water Alarm Restore 1-30 WH1-WH30 AR1 - AR0 Alarm Restore Code 3 154 001 - 3 154 030
Water Trouble Restore 1-30 WJ1-WJ30 R1 - R0 Restore Code 3 370 001 - 3 370 030
Water Trouble 1-30 WT1-WT30 T1 - T0 Trouble Code 1 370 001 - 1 370 030
Water Unbypass 1-30 WU1-WU30 R1 - R0 Restore Code 3 570 001 - 3 570 030
Communications Failure Line #1 YC1 T1 Trouble Code 1 354 001
Communications Restore Line #1 YK1 R1 Restore Code 3 354 001
Communications Failure Line #2 YC2 T2 Trouble Code 1 354 002
Communications Restore Line #2 YK2 R2 Restore Code 3 354 002
System Battery Restore YR0 R0 Restore Code 3 302 000
System Battery Trouble YT0 T0 Trouble Code 1 302 000
Cold Alarm 1-30 ZA1-ZA30 A1 - A0 Alarm Code 1 153 001 - 1 153 030
Cold Bypass 1-30 ZB1-ZB30 T1 - T0 Trouble Code 1 570 001 - 1 570 030
Cold Alarm Restore 1-30 ZH1-ZH30 AR1 - AR0 Alarm Restore Code 3 153 001 - 3 153 030
Cold Trouble Restore 1-30 ZJ1-ZJ30 R1 - R0 Restore Code 2 370 001 - 3 370 030
Cold Trouble 1-30 ZT1-ZT30 T1 - T0 Trouble Code 1 370 001 - 1 370 030
Cold Unbypass 1-30 ZU1-ZU30 R1 - R0 Restore Code 3 570 001 - 3 570 030

6.2.1 Default Settings for 3/1 Format


Table 6-3 displays the default settings which are set in the Misc. Reporting section of
Programming.
Table 6-3: Default Settings for 3/1 Format
Programming
Menu Item Choices Default Comments
Option
Selects the time of day the control will send an
Test Time 00:00 - 23:59 12:00
automatic test signal to a central station receiver.
Selects the delay time (in hours) before the control
AC Delay 0-30 Hours 2
will report an AC power loss to the central station.
No zone information will be reported just test
No 
begin and test end.
Report Walk Test
Test begin, test end, and all events in between will
By Zone
be reported to central station.
0-9 Alarms for Fire, Waterflow, Undefined, Heat,
*3/1 Alarm 0
Misc Reporting * Event code for 3/1 Cold, and Water events.
and 4/2 reporting Alarms restores for Fire, Waterflow, Undefined,
*3/1 Alarm Rst formats. 2
Heat, Cold, and Water events.
*3/1 Supervisory 6 Sprinkler supervisories.
Restore reports for Troubles, Supervisories, and
*3/1 Restore 7 unbypasses. The only exceptions are the restores
listed as alarm restores.
All system and zone troubles, and zone/NAC
*3/1 Trouble 8
bypasses, and NACs troubles.
*3/1 Test 9 All test events.

6-4 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Section 7
Troubleshooting

This section of the manual contains information that can be used to isolate and correct
installation problems encountered in the field.

7.1 System Error Messages

Table 7-1 contains a list of possible error messages along with their meaning and possible
solution.
Table 7-1: Error Messages

Error Message Description Solution


FLASH Defaulted On power up the SK-5208 will check the flash for If an “option record” is not found
an “option record”. during power up, one will be created
and the display will indicate “Flash
Defaulted” for approximately one
second.
Earth Fault Trb The SK-5208 has built-in earth ground fault See Section 7.2 for earth ground
detection that will detect an earth ground fault fault troubleshooting procedure.
connection between earth and any panel terminal.
When an earth ground fault is detected the SK-
5208 display will indicate Earth Fault Trb.
The SK-5208 will also add two events to the
history buffer Expand Trb 38 and Earth ###. The
Earth ### is a debug event number between 0 and
255.
Key BUS Trouble This message will display when communication is Check for a short or an open on
lost between the 5235 and the control panel. either the SKI or SKO terminals.
NAC # Trb This message indicates that a short or an open is Check for a short or an open on the
detected on a Notification Appliance Circuit. The indicated NAC wire run.
# indicates which NAC has the trouble.
Remote # Trb Each 5235 can be programmed to be supervised Check the wire connections between
(see Section 4.2.2). If the SK-5208 is unable to the indicated touchpad and the
communicate with the 5235 it will indicate this control panel.
message. # indicates the ID number of the faulted
touchpad.
5217 Trb # If the SK-5208 is unable to communicate with a Check all wire connections between
5217 expander it will display this message. The # the control panel and the 5217
indicates the ID number of the expander in expander in trouble.
trouble.
5280 Trb # If the control panel is unable to communicate with Check all wire connections between
a SK-5280 Status Display Module this message the control panel and the SK-5280
will be displayed. # indicates the ID number of the in trouble.
SK-5280 in trouble.

P/N 151204 7-1

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

Table 7-1: Error Messages

Error Message Description Solution


Smk Pwr Trb Smoke power terminals 11, 14, 17, and 20 are This may occur when the maximum
supervised. If the voltage between circuit ground current draw for the initiation circuit
(terminals 9, 22, 26, 33) and loop power is less is exceeded. See Section 3.11 for
than 20VDC this message will display. initiation circuit current
requirements.
5235 Pwr Trb The power terminal for the 5235 is supervised and This may occur if the maximum
a trouble indication will occur if the voltage current rating (1Amp) for this circuit
between circuit ground and terminal 32 drops is exceeded.
below 20 VDC.
Aux Pwr Trb The SBUS power terminal (27) is supervised and This may occur if the maximum
will display this message when the voltage current rating (1Amp) for this circuit
between SBUS power and circuit ground drops is exceeded.
below 20 VDC.
AC Trb This message is displayed when the AC voltage Check the AC power connection.
drops below 98 VAC. This report will be sent to the central
station after the AC delay time has
expired. See Section 4.2.10 to
program AC delay time.
Battery Trb This message will be displayed when the battery Check battery connection. Verify
voltage drops below 20.4 VDC under load. The that the control panel has AC power.
control panel performs a load test every minute.
Ph Line # Trb This message is displayed when the phone line
voltage drops below 2 VDC or can not supply a
minimum of 4 mA of current. The # indicates
which phone line is in trouble.
Data Lost This event will be reported to the central station if
the reporting buffer fills. This may occur if more
that 24 events need to be reported. When the
report buffer is full and additional events are
added to the report buffer, the oldest event will be
overwritten and the data lost event will be added.
Com # Trb The SK-5208 must use alternating phone lines The trouble condition will clear after
(according to NFPA) when reporting auto tests the control panel is successful in
and manual tests. If the control panel can not communicating using the phone
communicate using the selected phone line, the line.
Com # Trb message will be displayed. The #
indicates which line had the trouble.

7-2 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Troubleshooting

7.2 Earth Ground Fault Troubleshooting

An Earth Fault Trb indicates that the panel has detected a short between any terminal on
the panel and earth ground. To determine the location of the short, place a DC volt meter with
ground on terminal 22 (circuit ground) and positive on any of the screws that secure the circuit
board to the cabinet (earth ground).
A typical meter reading should alternate between 0 VDC and 11.7 VDC. Any other voltage
will put the panel into Earth Fault Trb (see also Table 7-1). Remove and leave off field
wiring from the panel until the meter alternates between 0 VDC and 11.7 VDC.
When an Earth Fault is indicated at the touchpad two messages will be added to the event
history buffer, Earth Fault 38 and Earth ###. This information can be very helpful to
identify where an earth ground fault exists in an intermittent earth ground situation.
If the Earth ### is lower than 133 this typically would indicate an earth ground short to a
low voltage source (13.1 VDC or less). For example, any circuit ground terminal or zone input
terminal.
If the Earth ### is higher than 134 this typically would indicate an earth ground to a higher
voltage source (13.1 VDC or higher). For example, any circuit power, standby battery, phone
lines, or AC power.

P/N 151204 7-3

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

7.3 Earth Fault Resistance

Table 7-2 list the earth fault resistance values for each applicable terminal on the FACP.
Table 7-2: Earth Fault Resistance Values by Terminal
Terminal Earth Fault Resistance
Function Terminal Label
Number Value (in Ohms)
1 A 0K
2 B 0K
Zone 1 input. Z1
3 C 0K
4 D 0K
5 A 0K
6 B 0K
Zone 2 input Z2
7 C 0K
8 D 0K
Ground 9 GND 0K
Zone 3 input 10 Z3 0K
Power (Zone 3 & 4) 11 PWR 0K
Zone 4 input 12 Z4 0K
Zone 5 input 13 Z5 0K
Smoke Power 14 PWR 0K
Zone 6 input 15 Z6 0K
Zone 7 input 16 Z7 0K
Smoke Power 17 PWR 0K
Zone 8 input 18 Z8 0K
Zone9 input 19 Z9 0K
Smoke Power 20 PWR 0K
Zone 10 input 21 Z10 0K
Ground 22 GND 0K
23 B NA
AC Power Connections 24 Earth NA
25 W NA
26 GND 0K
27 +24DC 0K
SBUS Connections
28 A 0K
29 B 0K
30 SKI 0K
Remote Annunciator 31 SKO 0K
Connections 32 PWR 0K
33 GND 0K
Notification Appliance 34 + 0K
NAC4
Circuit 4 35 _ 0K
Notification Appliance 36 + 0K
NAC3
Circuit 3 37 _ 0K
Notification Appliance 38 + 0K
NAC2
Circuit 2 39 _ 0K
Notification Appliance 40 + 0K
NAC1
Circuit 1 41 _ 0K

7-4 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Appendix A
Compatible Devices
This section of the manual lists devices (smoke detectors and notification appliances) that are
compatible with the SK-5208. Contact Silent Knight if you have a question about whether a
device not listed here is compatible.
A.1 Notification Appliances
For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL
resistor on each loop. All supervised notification appliances used with the control panel must
be polarized. The table below lists notification appliances compatible with the FACP.
Appliances which can be synchronized indicate the type of sync available in the columns
marked Audio and/or Visual.
Note: Not all devices can use the Sync feature, be sure to check table below to ensure the device you have chosen
will work with this feature. Synchronization is UL listed as a single circuit operation.

Manufacturer Model Audio Visual Type


SH24W-153075   Horn/Strobe
SAD24-153075  Strobe
SAD24-75110  Strobe
SL24W-75110  Strobe
SL24C-3075110  Strobe
SLB24-75  Strobe
RSD24-153075  Strobe
RSD24-75110  Strobe
AMSECO SH24W-75110   Horn/Strobe
SH24W-3075110   Horn/Strobe
SHB24-75   Horn/Strobe
SCM24W-153075  Chimes/Strobe
SCM24W-75110  Chimes/Strobe
SCM24C-3075110  Chimes/Strobe
SCM24C-177  Chimes/Strobe
H24W  Horn
H24R  Horn

P/N 151204 A-1

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

Manufacturer Model Audio Visual Type


446 Vibrating Bell
476 Vibrating Bell
477 Single Stroke Bell
2700 -M. -R, -T, -Y, -Z Strobe
2701 Series Strobe
2705 Series Strobe
2820   Snyc Temporal Horn/Strobe
2821   Snyc Temporal Horn/Strobe
2824   Horn Strobe
5333 Multi-Tone Horn)
5336 Multi-Tone Horn/Strobe
5337 Multi-Tone Horn/Strobe
5338 Multi-Tone Horn/Strobe
5343 Single Tone Horn/Strobe
5346 Electronic Horn with Strobe
5347 Electronic Horn with Strobe
5348 Single Tone Horn/Strobe
5373 8-Tone Horn/Strobe
6321 Sync Mini Horn/Strobe
6322 Mini Horn/Sync Strobe
Faraday 6380 8-Tone Electronic Signal/Strobe
5376 8-Tone Horn/Strobe
5377 8-Tone Horn/Strobe
5378 8-Tone Horn/Strobe
5383 8-Tone Horn/Strobe with Sync Strobe
5386 8-Tone Horn/Strobe with Sync Strobe
5387 8-Tone Horn/Strobe with Sync Strobe
5388 8-Tone Horn/Strobe with Sync Strobe
5508 Single Gang Sync Strobe
5509 Strobe
5510 Strobe
5511 Strobe
5512 Strobe
5516 Strobe
5517 Strobe
5518 Strobe
5519 Strobe
5521 4” Square Sync Strobe
5522 4” Square Sync Strobe
6120 Horn
6140 Horn

A-2 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Compatible Devices

Manufacturer Model Audio Visual Type


Faraday 6223 Horn
6226 Horn/Strobe
6227 Horn/Strobe
6228 Horn/Strobe
6243 Electron-Mechanical Horn
6244 Electron-Mechanical Horn
6245 Electron-Mechanical Horn
6246 Electron-Mechanical Horn/Strobe
6247 Electron-Mechanical Horn/Strobe
6248 Electron-Mechanical Horn/Strobe
6300 Mini-Horn
6301 Mini-Horn
6302 Mini-Horn
6310 Mini-Horn/Strobe
6311 Mini-Horn/Strobe
6312 Mini-Horn/Strobe
6314 Series -M, -R, -T, -Y, -Z Strobe
6320 Sync Mini Horn/Strobe
S2415-FC Strobe
S241575-FC Strobe
S2430-FC Strobe
130-3117C Mini Horn
130-3147C Mini Horn
BLV-6 Vibrating Bell
BLV-10 Vibrating Bell
FCI
BLVCH Vibrating Chime
H12/24-FC Horn
H12/24W-FC Horn
H12/24K-FC Horn
HC12/24-FC Horn
HC12/24W-FC Horn
HC12/24K-FC Horn

P/N 151204 A-3

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

Manufacturer Model Audio Visual Type


FCI P2415-FC Horn/Strobe
P2415W-FC Horn/Strobe
P2415K-FC Horn/Strobe
P241575-FC Horn/Strobe
P241575W-FC Horn/Strobe
P241575F-FC Horn/Strobe
P241575K-FC Horn/Strobe
P2430-FC Horn/Strobe
P2430W-FC Horn/Strobe
P2430K-FC Horn/Strobe
P2475-FC Horn/Strobe
P2475W-FC Horn/Strobe
P2475K-FC Horn/Strobe
P24110-FC Horn/Strobe
P24110W-FC Horn/Strobe
P24110K-FC Horn/Strobe
S2430W-FC Strobe
S2430K-FC Strobe
S2475-FC Strobe
S2475W-FC Strobe
S2475K-FC Strobe
S24110-FC Strobe
S24110W-FC Strobe
S24110K-FC Strobe
450 Horn
Federal Signal
VALS Horn/Strobe
Gentex GEC-24-15   Horn/Strobes
GEC-24-30   Horn/Strobes
GEC-24-60   Horn/Strobes
GEC-24-75   Horn/Strobes
GEC-24-177   Horn/Strobes
GEC-24-110   Horn/Strobe
GEC-24-15/75   Horn/Strobe
GX91  MiniHorn Steady Tone
GX93  MiniHorn Temporal Tone

A-4 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Compatible Devices

Manufacturer Model Audio Visual Type


Gentex HG124 Horn
HS24-15   Horn/Strobe
HS24-30   Horn/Strobe
HS24-60   Horn/Strobe
HS24-75   Horn/Strobe
HS24-110   Horn/Strobe
HS24-1575   Horn/Strobe
GCC24   Multi Candella Horn/Strobe Ceiling Mount
GCCR24   Multi Candella Horn/Strobe Ceiling Mount
GCS24  Multi Candella Strobe Ceiling Mount
GCSR24  Multi Candella Strobe Ceiling Mount
GECR-24   Multi Candella Horn/Strobe
GES24-15  Strobes
GES24-30  Strobes
GES24-60  Strobes
GES24-75  Strobes
GES24-110  Strobes
GES24-15/75  Strobes
GES24-177  Strobes
GES3-24  Multi Candella Strobe
GESR-24  Multi Candella Strobe
GEH-24  Horn
ST24-30  Strobe
ST24-60  Strobe
ST24-75  Strobe
ST24-110  Strobe
ST24-1575  Strobe
WGEC24-75W   Weatherproof Horn/Strobe
WGES24-75W  Weatherproof Strobe
WGMS-24-X Horn/Strobe

P/N 151204 A-5

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

Manufacturer Model Audio Visual Type


CHR  Chime
CHW  Chime
CHSR   2-Wire Chime/Strobe
CHSW   2-Wire Chime/Strobe
HR   Horn
HW  Horn
HRK  Horn
P2R   2-Wire Horn/Strobe
P2R-P   2-Wire Horn/Strobe
PC2R   2-Wire Horn/Strobe
PC2R-P   2-Wire Horn/Strobe
P2RH   2-Wire Horn/Strobe High Candela
P2RH-P   2-Wire Horn/Strobe High Candela
PC2RH   2-Wire Horn/Strobe High Candela
PC2RH-P   2-Wire Horn/Strobe High Candela
System Sensor P2W   2-Wire Horn/Strobe
P2W-P   2-Wire Horn/Strobe
PC2W   2-Wire Horn/Strobe
PC2W-P   2-Wire Horn/Strobe
P2WH   2-Wire Horn/Strobe High Candela
P2WH-P   2-Wire Horn/Strobe High Candela
PC2WH   2-Wire Horn/Strobe High Candela
PC2WH-P   2-Wire Horn/Strobe High Candela
P2RK   2-Wire Horn/Strobe
PC2RK   2-Wire Horn/Strobe
P2RHK   2-Wire Horn/Strobe High Candela
PC2RHK   2-Wire Horn/Strobe High Candela
P4R   4-Wire Horn/Strobe
PC4R   4-Wire Horn/Strobe
P4RH   4-Wire Horn/Strobe High Candela
P4W   4-Wire Horn/Strobe

A-6 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Compatible Devices

Manufacturer Model Audio Visual Type


System Sensor PC4W   4-Wire Horn/Strobe
P4WH   4-Wire Horn/Strobe High Candela
PC4WH   4-Wire Horn/Strobe High Candela
P4RK   4-Wire Horn/Strobe
PC4RK   4-Wire Horn/Strobe
P4RHK   4-Wire Horn/Strobe High Candela
PC4RHK   4-Wire Horn/Strobe High Candela
PC4RH   4-Wire Horn/Strobe High Candela
SR  Strobe
SR-P  Strobe
SCR  Strobe
SCR-P  Strobe
SRH  Strobe High Candela
SRH-P  Strobe High Candela
SCRH  Strobe High Candela
SCRH-P  Strobe High Candela
SW  Strobe
SW-P  Strobe
SCW  Strobe
SCW-P  Strobe
SWH  Strobe High Candela
SWH-P  Strobe High Candela
SCWH  Strobe High Candela
SCWH-P  Strobe High Candela
SRK  Strobe
SCRK  Strobe
SRHK  Strobe High Candela
SCRHK  Strobe High Candela

P/N 151204 A-7

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

Manufacturer Model Audio Visual Type


Wheelock AH-12  Horn
AH-24  Horn
AH-12WP  Horn Weatherproof
AH-24WP  Horn Weatherproof
AMT-241575W   Multi-Tone Horn Strobe
AMT-24MCW  Mutli-Tone Horn Strobe
AMT-241575W-NYC   Multi-Tone Horn Strobe
AMT-12/24  Multi-tone Horn
AMT-12/24 NYC  Multi-tone Horn
AS-121575W  Horn/Strobe
NH-12/24  Horn
AS-241575W   Horn/Strobe
AS-24MCC   Horn/Strobe
AS-24MCCH   Horn/Strobe
AS-24MCW   Horn/Strobe
AS-24MCWH   Horn/Strobe
ASWP-2475W   Horn/Strobe Weatherproof
ASWP-2475C   Horn/Strobe Weatherproof
ASWP-24MCWH   Horn/Strobe
ASWP-24MCCH   Horn/Strobe
CH-70  Chime
CH-90  Chime
CH70-241575W  Chime/Strobe
CH70-24MCW  Chime/Strobe
CH70-24MCWH  Chime/Strobe
CH90-24MCC  Chime/Strobe
CH90-24MCCH  Chime/Strobe
HS-24  Horn
HS4-241575W   Horn/Strobe
HS4-24MCW   Horn/Strobe
HS4-24MCWH   Horn/Strobe
HS4-24MCC   Horn/Strobe
MIZ-24S   Mini Horn Strobe
MT-121575W  MultitoneHorn Strobe
MT-241575W   Multitone Horn Strobe
MT-24MCW  Multitone Horn Strobe
MTWP-2475W  Multitone Horn Strobe
MTWP-2475C  Multitone Horn Strobe
MTG-121575W   Multitone Horn Strobe
MTR-121575W   Multitone Horn Strobe

A-8 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Compatible Devices

Manufacturer Model Audio Visual Type


Wheelock MTWPA-2475W   Multitone Horn Strobe
Con’t MTWPB-2475W   Multitone Horn Strobe
MTWPG-2475W   Multitone Horn Strobe
MTWPR-2475W   Multitone Horn Strobe
MTWPA-24MCCH   Multitone Horn Strobe
ZNH  Horn
NS-121575W   Horn/Strobe
NS-241575W   Horn/Strobe
NS-24MCW   Horn/Strobe
NS-24MCC   Horn/Strobe
NS-24MCCH   Horn/Strobe
ZNS-MCW   Horn/Strobe
ZNS-MCWH   Horn/Strobe
ZNS-24MCC   Horn/Strobe
ZNS-24MCCH   Horn/Strobe
RSS-121575W  Strobe
RSS-241575W  Strobe
RSS-24MCC  Strobe
RSS-24MCCR  Strobe
RSS-24MCCH  Strobe
RSS-24MCCHR  Strobe
RSS-24MCW  Strobe
RSS-24MCWH  Strobe
RSSP-121575W  Strobe
RSSP-241575W  Strobe
RSSR-2415W  Strobe
RSSR-2415C  Strobe
RSSR-2475W  Strobe
RSSR-2475C  Strobe
RSSR-24110C  Strobe
RSSA-24110W  Strobe
RSSB-24110W  Strobe
RSSG-24110W  Strobe
RSSR-24110W  Strobe
RSSA-24MCC  Multi-Cd Strobe
RSSB-24MCC  Multi-Cd Strobe
RSSG-24MCC  Multi-Cd Strobe
RSSR-24MCC  Multi-Cd Strobe
RSSWPA-2475W  Strobe Weatherproof

P/N 151204 A-9

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

Manufacturer Model Audio Visual Type


Wheelock RSSWPA-24MCCH  Strobe Weatherproof
Con’t RSSWPG-24MCCH  Strobe Weatherproof
RSSWPR-24MCCH  Strobe Weatherproof
RSSWP-2475W  Strobe Weatherproof
RSSWP-2475C  Strobe Weatherproof
RSSWP-24MCWH  Strobe Weatherproof
ZRS-MCWH  Strobe
ZRS-24MCC  Strobe
ZRS-24MCCH  Strobe
MB-G6-24 Motor Bell
MB-G10-24 Motor Bell
MB-G6-12 Motor Bell
MB-G10-12 Motor Bell
MIZ-24-R Mini-Horn
MT-12/24-R   Multitone Horn
MT4-12/24   Multitone Horn
ZRS-MCW  Strobe
MTWPR-24MCCH   Multitone Horn Strobe
NH-12/24R  Horn
HSR  Horn/Strobe
HSW  Horn/Strobe
STR  Strobe
STW  Strobe
HNR  Horn
HNW  Horn

Smoke Detectors
This section of the manual contains information about smoke detectors that are compatible
with the SK-5208.
SK-5208 SK-5217
Identifier 24J 24J

Maximum Voltage 27.4 VDC 27.4 VDC

Note: The maximum number of smoke detectors per zone is determined by both the current draw and the imped-
ance of the smoke detector. If too many smoke detectors are used on any zone, false alarms could occur.

Do not mix different models of detectors on any zone; false alarms could occur.

Control unit Smoke Reset Time must be programmed for a number greater than or equal to the maximum
reset time of the smoke detector.

A-10 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Compatible Devices

A.2 Two-Wire Smoke Detectors


The table below lists two-wire smoke detectors that are compatible with the SK-5208 and SK-
5217 zone expander. The table is organized by manufacturer. The columns show the number
of detectors per loop that can be used.
Enhanced Model Name or Number Compatibility ID # per Loop
Manufactu
Mode (Base model name or number in
rer Head Base
Compatible parentheses.)
55000-150, 151, 152, 153 55000-150, 45681-200, 220, 230, 40
151, 152, 153 231, 232
 55000-250 55000-350 45681-200, 220, 230, 40
231, 232
 55000-350 55000-250 45681-200, 220, 230, 25
231, 232
55000-380 55000-380 45681-200, 220, 230, 15
Apollo 231, 232
 55000-225 55000-225 45681-255, 256 15 / loop for
 55000-226 55000-226 Ion Detectors
 55000-227 55000-227
45681-200, 220, 230, 15 / loop for
 55000-325 55000-325
232, 251, 252 Photoelectric
 55000-328 55000-328 detectors
 55000-326 55000-326
 55000-327 55000-327
DS200 (MB200-2W) B A 24
DS200HD (MB200-2W) B A 24
Detection
DS250 (MB2W or MB2WL) B A 18
Systems
DS250HD (MB2W or MB2WL) B A 18
DS250TH (MB2W or MB2WL) B A 18
 425 (S10) N/A S00 30
 425C (S10) N/A S00 30
 425CR (S10) N/A S00 30
 425CRT (S10) N/A S00 30
 425CT (S10) N/A S00 30
 429C (S10A) N/A S10A 30
 429CRT (S11A) N/A S11A 30
 429CST (S11A) N/A S11A 30
 429CT (S10A) N/A S10A 30
ESL
 521B N/A S10A/S11A 40
 521BXT N/A S10A/S11A 40
 609U01-11 S10 S00 40
 609U02-11 S10 S00/S03 40
 611U (601U or 602U) S10 S00/S03 40
 611UD (601U or 602U) S10 S00/S03 40
 611UT (601U or 602U) S10 S00/S03 40
 612U (601U or 602U) S10 S00/S03 40
 612UD (601U or 602U) S10 S00/S03 40

P/N 151204 A-11

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

Enhanced Model Name or Number Compatibility ID # per Loop


Manufactu
Mode (Base model name or number in
rer Head Base
Compatible parentheses.)
ESL  711U (701E or 701U) N/A S10A 25
 712U (701E or 701U) N/A S10A 25
 713-5U (702E or 701U) N/A S10A 25
 713-6U (702E or 701U) N/A S10A 25
 721-U (S10A) N/A S10A 30
 721-UT (S10A) N/A S10A 30
301I (301B) A A 20
301IL (301BL/SS B401BH) N/A N/A 20
301P (301B) A N/A 20
301PL (301BL/SS B401BH) A N/A 20
301PT (301B) A N/A 20
301P (301DH-2) A N/A 20
301I-DH (301DH-2) A N/A 20
2100S A N/A 20
2100TS A N/A 20
2100TR A N/A 20
FCI 2100AT A N/A 20
SBS-1101 A N/A 20
SBS-1201 A N/A 20
SBS-1201T N/A N/A 20
PSD-7155 (2WB/2WRLT/2WRB) P55FE1 FE51A 40
PSD-7155 (CPD-001/-002/-003/-005) P56FE1 FE51A 40
PSD-7156 (2WB/2WRLT/2WRB) P55FE1 FE01A 40
PSD-7156 (CPD-001/-002/-003/-005) P56FE1 FE01A 40
CPD-7051 (2WB/2WRLT/2WRB) CPD7051 FE51A 40
CPD-7051 (CPD-001/-002/-003/-005) CPD7051 FE51A 40
DH100P (Duct Housing) N/A N/A 40
612H (4B, 6B, 612/912) 612H 4B, 6B, 612/912 15
612HP (4B, 6B, 612/912) 612HP 4B, 6B, 612/912 15
612I (4B, 6B, 612/912) 612I 4B 4B, 6B, 612/912 15
612P (4B, 6B, 612/912) 612P 4B, 6B, 612/912 15
622HP (4B, 6B, 612/912) 622HP 4B, 6B, 612/912 15
632H(4B, 6B, 612/912) 632H 4B, 6B, 612/912 15
Grinnell
MD612 (4B, 6B, 612/912) MD612 4B, 6B, 612/912 15
Fire
MD622 (4B, 6B, 612/912) MD622 4B, 6B, 612/912 15
Protection
MD632 (4B, 6B, 612/912) MD632 4B, 6B, 612/912 15
MF612 (4B, 6B, 612/912) MF612 4B, 6B, 612/912 15
MR612 (4B, 6B, 612/912) MR612 4B, 6B, 612/912 15
MR612T (4B, 6B, 612/912) MR612T 4B, 6B, 612/912 15
ISC—350I (IBC-350, 351, 353) ISC—350I IBC-350, 351, 353 24
ISC—350P (IBC-350, 351, 353) ISC—350P IBC-350, 351, 353 24
SIH-24F (HS-224D or HSB-224) N/A N/A 25
SLK-12 N/A N/A 25
SLK-24F (HS-224D) N/A N/A 25
Hochiki
SLK-24FH (HS-224D) N/A N/A 25
(HS224L) Heat Detector base N/A N/A 30
SLR-8358B N/A N/A 25

A-12 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Compatible Devices

Enhanced Model Name or Number Compatibility ID # per Loop


Manufactu
Mode (Base model name or number in
rer Head Base
Compatible parentheses.)
PSD-7155 (70-201000-001) P55FE1, FE51A, FE01A 40
P56FE1
Kidde-
PSD-7156 (70-201000-001) P56FE1 FE01A 40
Fenwal
CPD-7051 (70-201000-001) CPD 7051, FE51A, FE01A 40
I51FE1
1100T 20
1151 (B110LP) 20
1400 A N/A 20
1451 (B401B) A A 20
2100 A N/A 20
2100AT A N/A 20
2100D A N/A 20
2100T A N/A 20
2100TR A N/A 20
2100TS A N/A 20
2151 (B401) A N/A 16
2151T (B401) A N/A 16
System
2151 (B110LP) 20
Sensor
2300 A N/A 20
2300T A N/A 20
2300TB A N/A 20
2400 A N/A 20
2400TH 20
2400 (DH400) A N/A 20
2451 (B401B) A N/A 20
2451DH (DH 400) A N/A 20
2451TH (B401B) A N/A 20
2W-B A N/N 25
2WT-B A N/A 25
2WTR-B A N/A 25

A.3 Four Wire Smoke Detectors

Manufacturer Model
Hochiki SLR-835B with HD-6 Base
ESL 445C Series
449C Series
System Sensor 1851B
2851/2851BTH
DH400AC/DC

P/N 151204 A-13

Downloaded from www.Manualslib.com manuals search engine


Model SK-5208 Fire Control/Communicator Installation and Operation Manual

A-14 P/N 151204

Downloaded from www.Manualslib.com manuals search engine


Silent Knight Fire Product Warranty and Return Policy

General Terms and Conditions


• All new fire products manufactured by Silent Knight have a limited warranty period of
36 months from the date of manufacture against defects in materials and workmanship.
See limited warranty statement for details.
• This limited warranty does not apply to those products that are damaged due to misuse,
abuse, negligence, exposer to adverse environmental conditions, or have been modified in
any manner whatsoever.

Repair and RA Procedure


• All products that are returned to Silent Knight for credit or repair require a RMA (Return
Authorization) number. Call Silent Knight Customer Service at 800-328-0103 or
203-484-7161 between 8:00 A.M. and 5:00 P.M. EST, Monday through Friday to obtain a
return authorization number.
• Silent Knight Technical Support is available at 800-446-6444 between 8:00 A.M. and
5:00 P.M. CST, Monday through Friday.
• All returns for credit are subject to inspection and testing at the factory before actual deter-
mination is made to allow credit.
• RMA number must be prominently displayed on the outside of the shipping box. See
return address example under Advanced Replacement Policy.
• Include a packing slip that has the RMA number, a content list, and a detailed description
of the problem should be included with each return.
• All products returned to Silent Knight must be sent freight pre-paid. After product is pro-
cessed, Silent Knight will pay for shipping product back to customer via UPS ground.
• Return the Silent Knight product circuit board only. Products that are returned in cabinets
will be charged an additional $50 to cover the extra shipping and handling costs over
board only returns. Do not return batteries. Silent Knight has the authority to determine
if a product is repairable. Products that are deemed un-repairable will be returned to the
customer.
• Product that is returned that has a board date code more than 36 months from date of man-
ufacture will be repaired and the customer will be assessed the standard Silent Knight
repair charge for that model.

Downloaded from www.Manualslib.com manuals search engine


VIP-Series Voice Integration Package Installation/Operation Manual

Advanced Replacement Policy


• Silent Knight offers an option of advance replacement for fire product printed circuit
boards that fail during the first 6 months of the warranty period. These items must be
returned with transportation charges prepaid and must be accompanied by a return
authorization.
• For advance replacement of a defective board contact your local Silent Knight Distributor
or call Silent Knight at 203-484-7161 to obtain a RMA (Return Authorization) number
and request advanced replacement,
• A new or refurbished board will be shipped to the customer. The customer will initially be
billed for the replacement board but a credit will be issued after the repairable board is
received at Silent Knight. All returned products must comply with the guidelines
described under “General Terms and Conditions”.
• The defective board must be returned within 30 days of shipment of replacement board for
customer to receive credit. No credit will be issued if the returned board was damaged due
to misuse or abuse.
• Repairs and returns should be sent to:
Silent Knight / Honeywell
Attn: Repair Department
12 Clintonville Road
Northford, CT 06472
USA
RMA Number:___________________

-16 151286

Downloaded from www.Manualslib.com manuals search engine


Limited Warranty
SILENT KNIGHT warrants products manufactured by it to be free from defects in materials and
workmanship for thirty-six (36) months from the date of manufacture, under normal use and service.
Products are date stamped at time of manufacture. The sole and exclusive obligation of SILENT
KNIGHT is to repair or replace, at its option, free of charge for parts and labor, any part that is
defective in materials or workmanship under normal use and service. All returns for credit are
subject to inspection and testing at the factory before actual determination is made to allow
credit. SILENT KNIGHT does not warrant products not manufactured by it, but assigns to the
purchaser any warranty extended by the manufacturer of such products. This warranty is void if the
product is altered or repaired by anyone other than SILENT KNIGHT or as expressly authorized by
SILENT KNIGHT in writing, or is serviced by anyone other than SILENT KNIGHT or its authorized
distributors. This warranty is also void if there is a failure to maintain the products and systems in
which they operate in a proper and workable manner. In case of defect, secure a Return Material
Authorization form from our Return Authorization Department.

This writing constitutes the only warranty made by SILENT KNIGHT, with respect to its
products. SILENT KNIGHT, does not represent that its products will prevent any loss by
fire or otherwise, or that its products will in all cases provide the protection for which they
are installed or intended. Buyer acknowledges that SILENT KNIGHT is not an insurer and
assumes no risk for loss or damages or the cost of any inconvenience, transportation
damage, misuse, abuse, accident or similar incident.

SILENT KNIGHT GIVES NO WARRANTY, EXPRESS OR IMPLIED, OF


MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE
WHICH EXTENDS BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO
CIRCUMSTANCES SHALL SILENT KNIGHT BE LIABLE FOR ANY LOSS OF OR
DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING
OUT OF THE USE OF, OR INABILITY TO USE SILENT KNIGHT ALARM’S PRODUCTS.
FURTHERMORE, SILENT KNIGHT SHALL NOT BE LIABLE FOR ANY PERSONAL
INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF,
PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS
This warranty replaces all previous warranties and is the only warranty made by SILENT
KNIGHT. No increase or alteration, written or verbal, of the obligation of this warranty is
authorized.
“SILENT KNIGHT” is a registered trademark.

Downloaded from www.Manualslib.com manuals search engine


VIP-Series Voice Integration Package Installation/Operation Manual

-18 151286

Downloaded from www.Manualslib.com manuals search engine


SK-5208 Plus Basic Operating Instructions P/N 151214 Rev. A
These instructions must be framed and displayed next to the panel in accordance with NFPA 72 fire code
for Local Fire Alarm System.
Do This
How To Comments
Press Display Message Press
System Test The system will perform a display lamp test and a
Test the system Enter Code
0 Enter Code communication test. Displays Firmware Revisions.

Reset Alarms
1 or Reset Alarm
Enter Code Resets system.
Enter Code

Reset Dialer
Reset the Dialer Enter Code Resets the dialer and aborts the call to central station.
3 Enter Code

Display History History Events Displays the panel history, which includes alarms,
Enter Code
Events 5 Enter Code supervisories, troubles, reports, time and date changes, etc.

Show Status View existing system status. List Alarms first, supervisories
Show Status Enter Code
6 Enter Code and then troubles.

Silence Troubles or 7 or Silence


Enter Code
Alarms Enter Code

Disable Zone
Disable/Enable a Zone Zone # + Enter Code Repeat the process to enable the zone.
Enter Code
Repeat the process to enable the NAC.
1 0 NAC # + Disable NAC
Disable/Enable NAC Enter Code
Cut Along the Dotted Line

Enter Code

Fire Drill
Conduct a Fire Drill Enter Code
2 0 Enter Code To End the Fire Drill press then code.

Rst Smk Pwr


Reset Detectors Enter Code Resets all smoke detector power.
2 1 Enter Code

Walk Test
Walk Test the System Enter Code
2 2 Enter Code To End the Walk Test press .

Menu of Options Press or to


To exit press or wait 15 seconds.
scroll through list.

Events can be acknowledged by pressing the button. No code is required to acknowledge events. The status LEDs (Alarm,
Supervisory and Trouble) will flash when an un-acknowledged alarm, supervisory, or trouble condition exists.
After each event has been acknowledged its associated LED (Alarm, Supervisory, or Trouble LED) stop flashing and turn on steady.
Acknowledge Events When viewing system status the LCD displays “Acked” for each individual event once it has been acknowledged. The control panel
piezo will silence after all alarms have been acknowledged.
Note: The control panel piezo will continue to sound for Supervisories and Troubles even after the event has been acknowledged.
Supervisories and troubles will silence once the event is restored.
After the event is acknowledged an event is added to the event history buffer. Acknowledged events in the history buffer will be preceded
with an asterisk “*”.
LEDs Meaning
LED Status Condition
Off Normal condition
ALARM (red) On System in alarm.
Flashing LED will flash when a alarm condition exists that has not been acknowledged.
Off Normal condition
SUPERVISORY (yellow) On If a supervisory condition exist on the system.
Flashing LED will flash when a supervisory condition exists that has not been acknowledged.
Off Normal condition
TROUBLE (yellow) On Trouble condition exists
Flashing LED will flash when a trouble condition exists that has not been acknowledged.
Off Normal condition.
SILENCED (yellow)
On Alarm or trouble condition has been silenced but condition still exists.
On Panel is running on AC (normal condition); standby battery fully charged.
AC (green) Off Panel has lost all power.
Flashing Panel is running on battery power only or AC power only.

For Service Contact:

Downloaded from www.Manualslib.com manuals search engine


Cut Along the Dotted Line

Downloaded from www.Manualslib.com manuals search engine


Downloaded from www.Manualslib.com manuals search engine
Downloaded from www.Manualslib.com manuals search engine

You might also like