Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

IPL144L-IPL244 Eng

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

PROGRAMMABLE NETWORK

CONVERTER ANALYSER IPL244, IPL144L

• High adaptability: direct, alternative, single-phased,


three-phased balanced, unbalanced, with or without neutral,

• 8 output slots: analog, relay, RS485, ...


• Fully insulated 3U, 3I
IPL144L
• High display capacity:
10 simultaneous values (IPL244)
3 simultaneous values (IPL144L)
IPL244
• Universal power supply

IPL144V is universal analyser of electrical network, it has 8 site intended to measure read (analog output,
digital link, relay ...)

Applications: GENERAL CHARACTERISTICS:


- Measure, control, pilot, regulation, protection.
Measures: - DIN panel plastic case, U-link fastening
Thanks to its integrated calculation functions, the IPL244/144L - IPL244: 144 x 144 x 175, cut-off 139 x 136,
allows the measure of all electric measures: - IPL144L: 144 x 72 x 175, cut-off 139 x 66,
- direct voltage and current (700 Vdc, 5 Adc), - Plug-in connector, connection with screw-terminals
- effective alternating voltage and current (500 Vac, 5 Aac), (2.5 mm²) or with threaded rod for current input (optional),
- inverse current, - Tightness IP20 (option IP54, RS232 on back side).
- active (P), reactive (Q), apparent (S), power CONFIGURATION:
(generated-consumed),
- cos (power factor) inductive-capacitive, Thanks to its front-side keyboard, the IPL244/144L allows to reset
- frequency (35 to 400 Hz), the energy meters, to change the pages of visualization, ...
- active, reactive, generated, consumed energy,
with independant addition by channel (saved), reset in The user can visualize and configure all the parameters of the
configuration or with keyboard (lockable in the configuration), IPL244/144L via the RS232 link.
- configurable transformation ratio (current and voltage).
Display: The device can interact via the RS232 serial link
(jack 3.5, or option: DB9 on back side),
IPL244: with any system emulating a terminal.
- 10 values displayed simultaneously, selected by Example: Terminal program in Windows: ---->
3 press-buttons and/or RS232 configuration (Free supply of cable on single request).
- 8 values of 3 digits 1/2 and 2 values of 7 digits
1/2 ( L1, L2, L3 / I1, I2, I3 / ... ) Through the terminal, the user will be able to:
IPL144L: - visualize the measures, the actual configuration,
- 3 values displayed simultaneously, selected by - make a new configuration of the IPL244/144L.
1 press-button
- 3 values of 7 digits The configuration mode allows to choose:
- display of the type and the value - the wiring type (direct, alternative, single-phase, three-phase,
balanced, unbalanced, with or without neutral, 3 independant
- Display with red leds 7.62 mm great luminosity wattmeters, ...),
- Automatic change of the scale factor - the PT and CT ratio,
(V-kV, A-kA, kW-MW) - the working relays mode,
- Automatic positioning of the decimal point. - the RS485 link parameters,
- the type and the scale of the analog ouputs,
Outputs slots: - the display type.

The IPL244/144L is equipped with 8 slots. Each slot can re-


ceive either:
- one insulated analog ouput, assigned to any chosen measure,
- one configurable relay in alarm or energy counting,
- one digital RS485 link with MODBUS/JBUS protocol.
(data in integer 32 bits and floating 32 bits IEEE (optional))

HIGH CURRENT CONVERTERS - INDICATORS E1


90 days accuracy (20 °C +/- 2 °C) DATA SHEET CAN BE DOWNLOADED ON WWW.LOREME.FR TECHNICAL SPECIFICATIONS

INPUTS OUTPUTS
TYPE RANGE ACCURACY TYPE RANGE ACCURACY
Alternative voltage 500 V (direct) +/- 1.5 V Current 0 ... 4 ... 20 mA +/- 10 µA
Direct voltage +/- 700 V (direct) +/- 1.5 V Load: 500 Ohms
And Voltage 0 / 10 V +/- 5 mV
Alternative voltage 125 V (direct) +/- 0.37 V External shunt 500 Ohms (supplied separately)
Direct voltage +/- 175 V (direct) +/- 0.37 V RELAYS
Input impedance 2 M / 500 kOhms Switching power 5 A / 250 V
Overload 3 x UN during 3 s Reverse contact Type RT
Measure threshold 5 V / 1.5 V Impulse rate in counting 2 / s max.
Absorbed power 0.12 W / 0.03 W Impulse width 200 ms
POWER SUPPLY
Alternative current 5 A (direct) +/- 15 mA (to specify at the order)
Direct current +/- 5 A (direct) +/- 15 mA 20 to 70 Vac / Vdc, 7 VA
Input impedance 0.05 Ohms 80 to 265 Vac / Vdc, 7 VA
Overload 6 x IN during 3 s RECOMMENDED OPERATING CONDITIONS
Measure threshold 0.1 A Temperature
Absorbed power 1.25 W Operating -10 to 60 °C
Storage -20 to 85 °C
Other calibers on request, 1A current, 100V voltage Influence (of the full scale) < 0.03 % / °C
Note: use a transformer for an upper range
Relative humidity 85 % (not condensed)
Frequency 35 to 400 Hz +/- 0.2 % Weight ~ 950 g
Tightness IP20 (option IP54,
METROLOGY RS232 on back side)
(accuracy is given in percentage of the full calibrers) Dielectric strength 1500 Veff continuous
Active power +/- 0.6 % (Input/Outputs/Pwr./Contacts)
Reactive power +/- 1 % (in % app. P)
COS  +/- 0.6 % Electromagnetic compatibility
Active energy +/- 0.6 % Generic standards: NFEN50081-2 / NFEN50082-2
Reactive energy +/- 1 %
(conditions: freq. 45/65 Hz, cos  > 0.7 ; peak factor 1.4 ; calibres U/I 10 to 90%)
EN55011 meet group 1 / class A
Sampling rates / response time accordinging of the configura- EN61000-4-2 no influence B ENV50140 < +/- 5 % A
tion: EN61000-4-4 < +/- 5 % B ENV50141 < +/- 10 % A
Sampling rate: 1 to 3 per second EN61000-4-5 < +/- 5 % B ENV50204 no influence A
Response time: from 300 to 900 ms EN61000-4-8 no influence A
EN61000-4-11 < +/- 5 % B DBT 73/23/CEE
WIRING AND OUTLINE DIMENSIONS:
Identical wiring for IPL244 and IPL144L.
Cut-off: 66 x 139 mm - IPL144L, 136 x 139 mm - IPL244
Insertion depth: 175

E2 LOREME 12, rue des Potiers d'Etain - 57071 Metz  03.87.76.32.51 - Fax 03.87.76.32.52 - Email: Commercial@Loreme.fr - Technique@Loreme.fr
On account of the constant technologies and standards evolution, LOREME keeps the possibility to modify the specifications of the included products without notice. REV0A - 07/08/07

You might also like