HGM6400 V1.0 en PDF
HGM6400 V1.0 en PDF
HGM6400 V1.0 en PDF
CONTENT
1 SUMMARY ................................................................................................................. 4
2 PERFORMANCE AND CHARACTERISTICS...................................................... 4
3 SPECIFICATION ....................................................................................................... 6
4 OPERATION............................................................................................................... 7
4.1 LCD display........................................................................................................ 7
4.2 Key function ....................................................................................................... 9
4.3 Automatic operation ........................................................................................ 10
4.4 Manual operation..............................................................................................11
5 PROTECTION.......................................................................................................... 12
5.1 Warning alarm /Pre-alarm.............................................................................. 12
5.2 Shutdowns......................................................................................................... 13
5.3 Electrical trips .................................................................................................. 15
6 CONFIGURATION .................................................................................................. 16
6.1 Parameter Setting ............................................................................................ 16
6.2 Editing the current data/time ......................................................................... 19
7 DEFINITION OF DIGIT INPUTS AND OUTPUTS ............................................ 20
7.1 Digit input 1-6................................................................................................... 20
7.2 Digit output 1-6 ................................................................................................ 22
8 BACK BOARD ......................................................................................................... 28
9 CONNECTING TERMINAL .................................................................................. 28
10 FAULT FINDING ..................................................................................................... 31
11 TYPICAL WIRING DIAGRAM ............................................................................. 33
11.1 3-phase 4 wires ................................................................................................. 33
11.2 3-phase 3 wires ................................................................................................. 34
11.3 single phase 2 wires .......................................................................................... 34
11.4 2-phase 3 wires ................................................................................................. 34
12 IDMT TRIPPING CURVES (TYPICAL) .............................................................. 35
13 LINK TO PC ............................................................................................................. 36
14 CANBUS CONNECT ............................................................................................... 37
14.1 CUMMINS ISB/ISBE.......................................................................... 37
14.2 CUMMINS QSL9................................................................................ 37
14.3 CUMMINS QSM11 ............................................................................. 38
14.4 DETROIT DIESEL DDEC III / IV ........................................................ 39
14.5 DEUTZ EMR2 .................................................................................... 39
14.6 JOHN DEERE.................................................................................... 40
14.7 MTU MDEC........................................................................................ 40
14.8 PERKINS ........................................................................................... 41
14.9 SCANIA ............................................................................................. 41
14.10 VOLVO EDC3 .................................................................................... 42
14.11 VOLVO EDC4 .................................................................................... 42
14.12 VOLVO-EMS2 .................................................................................... 43
14.13 BOCSH .............................................................................................. 44
15 INSTALLATION ...................................................................................................... 45
1 SUMMARY
HGM6400 Series generator controller integrating digital, intelligent and network
techniques is used for automatic control system of diesel generator. It can carry
out functions including automatic start/stop, data measure and alarming. The
controller uses LCD display, optional Chinese and English display interface with
operation easy and reliable.
HGM6400 Series generator controller have a port of SAE J1939. It can connect
engine that possess J1939 ECU.
◆ Using microprocessor as a core, graphics LCD with big screen and backlight,
display between Chinese and English, key touch for operation.
◆ Parameters setting: Allow user to modify setting and store them inside internal
FLASH memory, the parameters can not be lost even with power down.
◆ Built-in speed/frequency detecting units can accurately judge the states such
as crank success and over speed;
◆ 99 historical records can be stored circularly and inquiring of the records can
be made on site;
◆ Built-in watch dog can never be dead halt, ensuring smooth program
execution;
3 SPECIFICATION
Operating Voltage DC8. 0V to 35. 0V, Continuous Power Supply
Power Consumption <3W
Alternator Input Range
Single phase 2 wire 15V AC - 360 V AC (ph-N)
3-Phase 4 Wire 15V AC - 360 V AC (ph-N)
3-Phase 3 Wire 30V AC - 600 V AC (ph-ph)
2-Phase 3 Wire 30V AC - 600 V AC (ph-ph)
Alternator Input Frequency 50Hz - 60 Hz at rated engine speed
Magnetic Input Range +/- 1. 0 V to 70 V Peak
Magnetic Input Frequency 10,000 Hz (max) at rated engine speed.
Start Relay Output 16 Amp DC at supply voltage.
Fuel Relay Output 16 Amp DC at supply voltage.
Auxiliary Relay Output (1-4) (1-3)16 Amp DC at supply voltage,(4)6A
250VAC
Close Mains Relay 16A 250VAC free voltage contact
Close Generator Relay 16A 250VAC free voltage contact
Dimensions 240mm x 172mm x 57mm
Panel cutout 214mm x 160mm
Charge Fail / Excitation Range 0 V to 35 V
Operating Temperature Range -30 to +70°C
Storage Condition Temperature: (-20 - 80)°C
C. T. Burden 2. 5VA
C. T. Secondary 5A
Weight 0. 90kg
4 OPERATION
Page order:
• Status display
• Instrument display
• Alarms display
• Event log
Mains on load:
Generator on load:
When a Remote Start signal is applied to the remote start input (Hgm6410) or
when mains voltage occur over-voltage, under-voltage, over-frequency, under-
frequency (Hgm6420), the following sequence is initiated:
To allow for false signals the mains abnormal timer is initiated (only Hgm6420),
Then the Start Delay timer is initiated. After this delay, if the pre-heat output
option is selected then the pre-heat timer is initiated, and the corresponding
auxiliary output (if configured) will energize.
NOTE: If the Remote Start signal is removed (Hgm6410) during the Start Delay
timer, or if mains voltage is normal (Hgm6420) during the mains abnormal timer,
the unit will return to a stand-by state.
After the above delays the Fuel Solenoid is energized, then one second later, the
Starter Motor is engaged. The engine is cranked for a pre-set time period. If the
engine fails to fire during this cranking attempt then the starter motor is
disengaged for the pre-set rest period. Should this sequence continue beyond the
set number of attempts, the start sequence will be terminated and Fail to Start
fault will be displayed on the LCD screen.
When the engine fires, the starter motor is disengaged and locked out at a pre-set
frequency from the Alternator output. Alternatively a Magnetic Pickup mounted on
the flywheel housing can be used for speed detection (This is selected by PC
using the HGM6400 series configuration software). Rising oil pressure can also
be used to disconnect the starter motor, however it cannot be used for under
speed or over speed detection.
After the starter motor has disengaged, the Safety On timer is activated, allowing
Oil Pressure, High Engine Temperature, Under-speed, Charge Fail and any
delayed Auxiliary fault inputs to stabilize without triggering the fault.
Once the engine is running, the Warm Up timer, if selected is initiated, allowing
the engine to stabilize before accepting the load.
If an auxiliary output has been selected to give a load transfer signal, this would
then activate.
HGM6410/6420 Auto Start Module ISSUE 2008-8-10 Version 1.0 Page 10 of 45
HGM6410/6420 AUTO START MODULE
NOTE: A load transfer will not be initiated until the Oil Pressure has risen. Thus
preventing excessive wear on the engine.
On removal of the Remote Start signal, the Stop delay timer is initiated, once it
has timed out, the load Transfer signal is de-energized, removing the load. The
Cooling timer is then initiated, allowing the engine a cooling down period off load
before shutting down. Once the Cooling timer expires the Fuel Solenoid is
de-energized, bringing the generator to a stop.
If the pre-heat output option is selected this timer is then initiated, and the
auxiliary output selected is energized.
After the above delay the Fuel Solenoid is energized, then the Starter Motor is
engaged.
The engine is cranked for a pre-set time period. If the engine fails to fire during
this cranking attempt then the starter motor is disengaged for the pre-set rest
period. Should this sequence continue beyond the set number of attempts, the
start sequence will be terminated and Fail to Start fault will be displayed on the
LCD screen
When the engine fires, the starter motor is disengaged and locked out at a pre-set
frequency from the Alternator output. Alternatively a Magnetic Pickup mounted on
the flywheel housing can be used for speed detection (This is selected by PC
using the HGM6400 series configuration software). Rising oil pressure can also
be used to disconnect the starter motor, however it cannot be used for under
speed or over speed detection.
After the starter motor has disengaged, the Safety On timer is activated, allowing
Oil Pressure, High Engine Temperature, Under-speed, Charge Fail and any
delayed Auxiliary fault inputs to stabilize without triggering the fault.
Once the engine is running, the Warm Up timer, if selected is initiated, allowing
the engine to stabilize before it can be loaded.
In manual test mode, generator will take load regardless of mains supply normal
or abnormal.
In above process, when the Warm Up timer has expired, if the remote start signal
is active, generator will take load, if inactive, generator will not take load.
5 PROTECTION
In the event of a warning alarm or pre-alarm, the module will display on the LCD
screen.
HIGH ENGINE TEMPERATURE: if the module detects that the engine coolant
temperature has exceeded the high engine temperature pre-alarm setting level
after the Safety On timer has expired, a warning will occur.
LOW OIL PRESSURE, if the module detects that the engine oil pressure has
fallen below the low oil pressure pre- alarm setting level after the Safety On timer
has expired, a warning will occur.
UNDERSPEED, if the engine speed falls below the pre-set pre-alarm after the
Safety On timer has expired, a warning is initiated.
LOSS OF SPEED SIGNAL, if the speed sensing signal is lost during cranking, a
warning will occur.
FAIL TO STOP, If the module detects the engine is still running when the ‘Fail to
stop timer’ expires, a warning is initiated.
BATTERY HIGH VOLTAGE, if the module detects that the plant DC supply has
risen above the high volts setting level, a warning is initiated.
BATTERY LOW VOLTAGE, if the module detects that the plant DC supply has
fallen below the low volts setting level, a warning is initiated.
ECU WARN, If the module is configured for CAN instruments and receives an
“warn” message from the engine control unit, ‘ECU warn” is shown on the
module’s display and a warning alarm is generated.
5.2 SHUTDOWNS
Shutdowns are latching and stop the Generator. The alarm must be cleared, and
the fault removed to reset the module.
NOTE: The alarm condition must be rectified before a reset will take place. If
HGM6410/6420 Auto Start Module ISSUE 2008-8-10 Version 1.0 Page 13 of 45
HGM6410/6420 AUTO START MODULE
the alarm condition remains it will not be possible to reset the unit (The
exception to this is the Low Oil Pressure alarm, as the oil pressure will be
low with the engine at rest). Any subsequent warnings or shutdowns that
occur will be displayed steady, therefore only the first-up shutdown will
appear displaying.
EMERGENCY STOP, removal of the +ve DC Supply from the Emergency Stop
input initiates the following sequence, firstly it will initiate a controlled shutdown of
the Generator and prevent any attempt to restart the Generator until the
Emergency Stop push-button has been reset. Secondly it removes the +ve DC
supply from both the Fuel Solenoid and Starter Solenoid.
HIGH ENGINE TEMPERATURE if the module detects that the engine coolant
temperature has exceeded the high engine temperature trip setting level after the
Safety On timer has expired, a shutdown will occur.
LOW OIL PRESSURE, if the module detects that the engine oil pressure has
fallen below the low oil pressure trip setting level after the Safety On timer has
expired, a shutdown will occur.
OVERSPEED, if the engine speed exceeds the pre-set trip a shutdown is initiated.
UNDERSPEED, if the engine speed falls below the pre-set trip after the Safety On
timer has expired, a shutdown is initiated.
LOSS OF SPEED SIGNAL, if the speed sensing signal is lost during cranking, a
shutdown is initiated.
For instance the factory default settings for Generator High Current allow for a
loading of the generator to 110% for one hour. That is to say if the generator load
level exceeds the trip point by 10%, a warning alarm will occur while the overload
condition exists. If the load level does not drop to normal levels within one hour,
the engine is stopped, the HGM6400 module displaying either shutdown alarm or
electrical trip alarm depend upon module configuration.
NOTE: Higher overload levels will result in a faster acting shutdown condition. For
instance with the factory default configuration, an overload level twice that of the
trip level ( typically 200%) will result in a Generator High Current shutdown
condition after 36 seconds. For details of the relationship between the overload
and the shutdown time, please see the Appendix section of this manual.
FAIL TO START, if the engine does not fire after the pre-set number of attempts
has been made a shutdown will be initiated.
OIL PRESSURE SENDER OPEN CIRCUIT, if the module detects a loss of signal
from the oil pressure sender (open circuit) a shutdown is initiated.
ECU SHUTDOWN, If the module is configured for CAN instruments and receives
an “error” message from the engine control unit, ‘ECU shutdown” is shown on the
module’s display and a warning alarm is generated.
CAN DATA FAIL ,If the module is configured for CAN operation and does not
detect data on the engine Can datalink, a shutdown will occur and ‘Can data fail’
is shown on the module’s display.
If this over current condition continues for an excess period of time, then the alarm
is escalated to either a shutdown or electrical trip condition (depending upon
HGM6410/6420 Auto Start Module ISSUE 2008-8-10 Version 1.0 Page 15 of 45
HGM6410/6420 AUTO START MODULE
module configuration). For further details of the over current alarm, please see
Over Current Shutdown Alarm.
6 CONFIGURATION
Although full configuration of the module is possible using the HGM6400 series
configuration software, selected parameters that may require adjustment in the
field are able to be adjusted via the module’s fascia.
NOTE: Care should be taken to ensure that changes made via the front panel
editor are carefully recorded and fed back to the generator supplier if applicable.
This is to safeguard against using the HGM6400 series configuration software to
configure the module at a later date, possibly overwriting the changes made using
the front panel editor. When using the HGM6400 series configuration software to
make configuration changes, the first operation should be to “read configuration
from controller” to ensure that any changes made to the controller’s configuration
by the front panel editor are ‘loaded’ into the PC before any changes are made.
Full details of this procedure can be found in the HGM6400 series configuration
software manual.
Pressing down both and keys will show the interface to enter
password. The default password is “1234” when it leaves factory. When setting
each item, after selecting this item, press the key ‘enter’ to enter the setting
interface, then press the key ‘-‘ or ‘+’ to adjust the numerical value, press the key
‘enter’ to move the cursor, finally press the key ‘enter’ to confirm the set
parameter.
In setting process, pressing key will quit and return main LCD screen.
Pressing down both the key and key will show the setting data/time
interface. The setting sequence is year -month -date (week) hour :minute :second.
Note: Setting must be in stop mode.
8 BACK BOARD
The back board of hgm6410 and hgm6420 Controller is shown as follows:
9 CONNECTING TERMINAL
Pin Function Dim Description
DC Plant Supply Input System DC negative input.
1 2. 5mm
(-ve) (Battery Negative).
System DC positive input.
DC Plant Supply Input (Battery Positive).
2 2. 5mm
(+ve) (Recommended Maximum Fuse
20A)
Plant Supply +ve. Also supplies
fuel & start outputs.
3 Emergency Stop Input 2. 5mm
(Recommended Maximum Fuse
32A)
Plant Supply +ve from pin 3.
4 Fuel relay Output 2. 5mm
16 Amp rated.
Plant Supply +ve from pin 3.
5 Start relay Output 2. 5mm
16 Amp rated.
Plant Supply +ve.
6 Auxiliary Output relay 1 2. 5mm
16 Amp rated.
Plant Supply +ve.
7 Auxiliary Output relay 2 2. 5mm
16 Amp rated.
8 Auxiliary Output relay 3 2. 5mm Plant Supply +ve.
HGM6410/6420 Auto Start Module ISSUE 2008-8-10 Version 1.0 Page 28 of 45
HGM6410/6420 AUTO START MODULE
Pin Function Dim Description
16 Amp rated.
Do not connect to ground (battery
9 Charge fail / excite 1. 0mm
–ve)
10 Auxiliary input 1 1. 0mm Switch to -ve
11 Auxiliary input 2 1. 0mm Switch to -ve
12 Auxiliary input 3 1. 0mm Switch to -ve
13 Auxiliary input 4 1. 0mm Switch to -ve
14 Auxiliary input 5 1. 0mm Switch to -ve
15 Auxiliary input 6 1. 0mm Switch to -ve
Connect to a good clean earth
16 Functional Earth 1. 0mm
point
17 Magnetic pickup +ve 1. 0mm Connect to Magnetic Pickup
18 Magnetic pickup -ve 1. 0mm device
19 Oil Pressure Input2 1. 0mm Connect to Oil pressure sender
20 Free voltage contacts. 16 Amp
21 Auxiliary Output relay 4 2. 5mm rated.
22
23 Not connected -
24 RS485 port Common 0. 5mm
Use only 120Ω RS485 approved
25 RS485 port A(+) 0. 5mm
cable
26 RS485 port B(-) 0. 5mm
27 Auxiliary Output relay 6 Free voltage contacts, N/C, 16
2. 5mm
28 (close mains output) Amp rated.
Note:
1. These terminals of 31, 32, 33, 34 is not used for HGM6410 module.
2. The RS232/485 serial port is used for monitoring the module by connecting
with PC.
10 FAULT FINDING
Symptom Possible Remedy
Check the battery and wiring to the unit. Check the
Unit is inoperative
DC supply. Check the DC fuse.
Check DC supply voltage is not above 35 Volts or
Unit shuts down below 8 Volts. Check the operating temperature is
not above 70 °C. Check the DC fuse.
If an Emergency Stop Switch is not fitted, ensure
Unit locks out on Emergency that a positive is connected to the Emergency Stop
Stop input. Check emergency stop switch is functioning
correctly. Check Wiring is not open circuit.
Ensure that Magnetic pick-up screen is only
Intermittent Magnetic Pick- up connected at one end, if connected at both ends,
sensor fault this enables the screen to act as an aerial and will
pick up random voltages.
Check engine oil pressure. Check oil pressure
switch/ sender and wiring. Check configured
Low oil Pressure fault
polarity (if applicable) is correct (i.e. Normally Open
operates after engine has
or Normally Closed) or that sender is compatible
fired
with the HGM6400 Module and is correctly
configured.
Check engine temperature. Check switch/sender
High engine temperature fault and wiring. Check configured polarity (if applicable)
operates after engine has is correct (i.e. Normally Open or Normally Closed)
fired. or that sender is compatible with the HGM6400
Module.
Check relevant switch and wiring of fault indicated
Shutdown fault operates
on LCD display. Check configuration of input.
Check relevant switch and wiring of fault indicated
Warning fault operates
on LCD display. Check configuration of input.
Check wiring of fuel solenoid. Check fuel. Check
Fail to Start is activated after battery supply. Check battery supply is present on
pre-set number of attempts to the Fuel output of the module. Check the speed
start sensing signal is present on the HGM6400 inputs.
Refer to engine manual.
Continuous starting of Check that there is no signal present on the
generator when in AUTO “Remote Start” input. Check configured polarity is
correct.
Check Start Delay timer has timed out. If remote
Generator fails to start on
start fault, check signal is on “Remote Start” input.
receipt of Remote Start
Confirm input is configured to be used as “Remote
signal.
Start”.
Check wiring to engine heater plugs. Check battery
Pre-heat inoperative supply. Check battery supply is present on the
Pre-heat output of module. Check pre-heat has
HGM6410/6420 Auto Start Module ISSUE 2008-8-10 Version 1.0 Page 31 of 45
HGM6410/6420 AUTO START MODULE
Symptom Possible Remedy
been selected in your configuration.
Check wiring to starter solenoid. Check battery
supply. Check battery supply is present on the
Starter motor inoperative
Starter output of module. Ensure that the
Emergency Stop input is at +Ve.
Check Warm up timer has timed out. Ensure
Engine runs but generator will
generator load inhibit signal is not present on the
not take load
module inputs.
Check engine is operating correctly. Check sender
and wiring paying particular attention to the wiring
Incorrect reading on Engine
to terminal 47. Check that sender is compatible
gauges
with the HGM6400 Module and is correctly
configured.
13 LINK TO PC
The module has a RS485 and a RS232 communication port on the rear. The
HGM6400 configuration software allows the modules to be connected to a PC via
a RS485-RS232 transducer or direct connected to a PC. Once connected the
various operating parameters within the module can be viewed or edited as
required by the engineer. This software allows easy controlled access to these
values and also has diagnostic monitoring facilities.
Communication parameters
Item Default
Module address 1 (range: 1-254)
Baud rate 9600bps
Data bits 8bit
Parity bit None
Stop bit 1bit
Please download the HGM6400 configuration software from the below web site.
http://www.smartgen.com.cn/
14 CANBUS CONNECT
14.1 CUMMINS ISB/ISBE
Cummins ISB
HGM6400
OEM Harness NOTES
TERMINAL
connector B
Fuel relay output 39 Key switch input.
Connects directly to engine
Start relay output -
starter solenoid.
Use to control
a 30A external Using PC configuration
slave relay to software select the relevant
Aux output 1
supply DC engine and configure “aux
battery power output 1” to be “ECU Power”
to 01,07,12,13
Cummins ISB 9
HGM6400
pin Deutsch NOTES
TERMINAL
Connector
Screen for the J1939 cable.
SAE J1939
Connect at Cummins ECU end
shield
only.
J1939 + Use only screened
SAE J1939 120 impedance cable
CAN(H)
signal approved specifically for use in
CANbus applications.
J1939 - Use only screened
SAE J1939 120 impedance cable approved
CAN(L)
return specifically for use in CANbus
applications.
The HGM6400 mode must be configured engine ECU :Cummins ISB
Cummins
HGM6400 CM570 3 pin
NOTES
TERMINAL data link
connector
Screen for the J1939 cable.
C Connect at Cummins ECU end
only.
J1939 + Use only screened
120 impedance cable
CAN(H) A
approved specifically for use in
CANbus applications.
HGM6410/6420 Auto Start Module ISSUE 2008-8-10 Version 1.0 Page 38 of 45
HGM6410/6420 AUTO START MODULE
J1939 - Use only screened
120 impedance cable
CAN(L) B
approved specifically for use in
CANbus applications.
The HGM6400 mode must be configured engine ECU :Cummins ISB
14.8 PERKINS
Engines in the Perkins range are fitted with the ADEM3 or ADEM4 Engine
control module. This system allows engine control and diagnostics via the
J1939 link.
Perkins engines fitted with the ADEM3 / ADEM4: 2306 2506 1106 2806
(This list is not exhaustive, contact Perkins for further details)
Perkins
HGM6400 Customer
NOTES
TERMINAL interface
connector
Powers up ECU and enables
Fuel relay output 1,10,15,33,34
the injectors.
Connects directly to engine
Start relay output -
starter solenoid.
Screen for the J1939 cable.
CAN GND -
Connect at one end only.
J1939 + Use only screened
120 impedance cable
CAN(H) 31
approved specifically for use in
CANbus applications.
J1939 - Use only screened
120 impedance cable
CAN(L) 32
approved specifically for use in
CANbus applications.
The HGM6400 mode must be configured engine ECU :Perkins
14.9 SCANIA
Scania engines fitted with the S6 ECU: DC9 DC 12 DC 16
This list is not exhaustive, contact Scania for further details
The functions of the S6 coordinator are built within the DSE controller
negating the need to fit this device to the engine controller.
HGM6400 Scania EMS
NOTES
TERMINAL B1 connector
Fuel relay output 3 Ignition U15
Connects directly to engine
Start relay output -
starter solenoid.
Screen for the J1939 cable.
CAN GND -
Connect at one end only.
CAN(H) 9 J1939 + Use only screened
HGM6410/6420 Auto Start Module ISSUE 2008-8-10 Version 1.0 Page 41 of 45
HGM6410/6420 AUTO START MODULE
120 impedance cable
approved specifically for use in
CANbus applications.
J1939 - Use only screened
120 impedance cable
CAN(L) 10
approved specifically for use in
CANbus applications.
The HGM6400 mode must be configured engine ECU :Scania
Volvo TAD12
HGM6400 Data bus
NOTES
TERMINAL Connector
terminal
Screen for the J1939 cable.
CAN GND -
Connect at one end only.
J1939 + Use only screened
120 impedance cable
CAN(H) 1
approved specifically for use in
CANbus applications.
J1939 - Use only screened
120 impedance cable
CAN(L) 2
approved specifically for use in
CANbus applications.
The HGM6400 mode must be configured engine ECU :Volvo
14.12 VOLVO-EMS2
Fitted to Volvo Penta engine types : TAD734, TAD940, TAD941, TAD1640,
TAD1641, TAD1642 (This list is not exhaustive, contact Volvo Penta for
further details)
Volvo EMS2
HGM6400
connector NOTES
TERMINAL
terminal
Using PC software select the
relevant engine and configure
aux output 1 6
“aux output 1”to be “ECU
STOP”
Using PC software select the
relevant engine and configure
aux output 2 5
“aux output 2”to be “ECU
POWER”
3 DC Supply negative
4 DC Supply positive
Screen for the J1939 cable.
CAN GND -
Connect at one end only.
HGM6410/6420 Auto Start Module ISSUE 2008-8-10 Version 1.0 Page 43 of 45
HGM6410/6420 AUTO START MODULE
J1939 + Use only screened
120 impedance cable approved
CAN(H) 1(Hi)
specifically for use in CANbus
applications.
J1939 - Use only screened
120 impedance cable approved
CAN(L) 2(Lo)
specifically for use in CANbus
applications.
The HGM6400 mode must be configured engine ECU :Volvo-EMS2
14.13 BOCSH
Fitted to Yuchai BOCSH engine.
HGM6400 42-pin NOTES
TERMINAL connector
Fuel relay output 1.40 Ignition U15
- Connects directly to engine
Start relay output
starter solenoid.
CAN GND - Screen for the J1939 cable.
Connect at one end only.
CAN(H) 1.35 J1939 + Use only screened
120 impedance cable
approved specifically for use in
CANbus applications.
CAN(L) 1.34 J1939 - Use only screened
120 impedance cable
approved specifically for use in
CANbus applications.
15 INSTALLATION
The controller is designed to panel installation mode, and it is fixed by clamps
when it is installed. The overall dimension and panel tapping dimension are given
as follows: