Easypact CVS: Catalogue
Easypact CVS: Catalogue
Easypact CVS: Catalogue
EasyPact CVS
Moulded-case circuit breakers and switch-disconnectors
from 100 to 630 A
Catalogue
2011
Safe
Reliable
Simple
The easy choice for
quality and value
EasyPact CVS
LV circuit breakers from 100 to 630A
Do you strain to find a high
quality circuit breaker that
is simple, flexible, and safe?
Buildings Industry
Gain peace of mind
and optimized cost
for every installation
EasyPact CVS General contents
Presentation 1
Functions
A-1
and characteristics
Installation
B-1
recommendations
Dimensions
C-1
and connection
A-7
Functions and characteristics
A-2
EasyPact CVS Functions and characteristics
Introduction
General characteristics A-2
Characteristics and performance A-4
Motor protection
MA instantaneous trip units A-9
Switch-disconnectors A-10
A-1
Functions Introduction
and characteristics General characteristics
2
EasyPact CVS circuit breakers and auxiliaries comply with the following international
7 recommendations:
8 bb IEC 60947-1: general rules
bb IEC 60947-2: circuit breakers
3 bb IEC 60947-3: switch-disconnectors
4
5 Pollution degree
EasyPact CVS circuit breakers are certified for operation in pollution-degree III
6
environments as defined by IEC standards 60947-1 and 60664-1 (industrial
environments).
cat.A
9
Climatic withstand
EasyPact CVS circuit breakers have successfully passed the tests defined by the
following standards for extreme atmospheric conditions:
bb IEC 60068-2-1: dry cold (-55°C)
bb IEC 60068-2-2: dry heat (+85°C)
bb IEC 60068-2-30: damp heat (95 % relative humidity at 55°C)
bb IEC 60068-2-52 severity level 2: salt mist.
Standardised characteristics indicated on the rating plate:
1 Type of device: frame size and breaking capacity class
2 Ui: rated insulation voltage.
Environment
3 Uimp: rated impulse withstand voltage. EasyPact CVS respects the European environment directive EC/2002/95 concerning
4 Ics: service breaking capacity. the restriction of hazardous substances (RoHS).
5 Icu: ultimate breaking capacity for various values of the All EasyPact CVS production sites have set up an ISO 14001 certified environmental
rated operational voltage Ue management system.
6 Ue: operational voltage.
7 Colour label indicating the breaking capacity class.
Ambient temperature
bb EasyPact CVS circuit breakers can be used between -25°C and +70°C. For
CVS CVS CVS CVS CVS temperatures higher than 40°C (65°C for circuit breakers used to protect motor
feeders), devices must be derated (see page B-2).
bb Circuit breakers should be put into service under normal ambient, operating-
temperature conditions. Exceptionally, the circuit breaker can be put into service
when the ambient temperature is between -35°C and -25°C.
bb The permissible storage-temperature range for EasyPact CVS circuit breakers in
8 Suitable for Isolation symbol.
the original packing is -50°C and +85°C.
9 Reference standard.
Note: when the circuit breaker is equipped with an extended
rotary handle, the door must be opened to access the rating
plate.
A-2
Suitable for isolation with positive contact
indication
All EasyPact CVS circuit breakers are suitable for isolation as defined in IEC
standard 60947-2:
bb The isolation position corresponds to the O (OFF) position.
bb The operating handle cannot indicate the OFF position unless the contacts are
effectively open.
bb Padlocks cannot be installed unless the contacts are open.
Installation of a rotary handle does not alter the reliability of the position-indication
system.
The isolation function is certified by tests guaranteeing:
bb The mechanical reliability of the position-indication system
bb The absence of leakage currents
bb Over voltage withstand capacity between upstream and downstream connections.
The tripped position does not ensure isolation with positive contact indication.
Only the OFF position guarantees isolation.
Degree of protection
The following indications are in accordance with standards IEC 60529 (IP degree of
protection) and IEC 62262 (IK protection against external mechanical impacts).
Bare circuit breaker:
bb with toggle: IP40, IK07 front face
bb with extended rotary handle: IP 55, IK08
Circuit breaker installed in a switchboard:
bb with toggle: IP40, IK07 front face
bb with extended rotary handle: IP 55, IK08
A-3
Functions Introduction
and characteristics Characteristics and performance
Common characteristics
PB106447
Rated voltages
Insulation voltage (V) Ui 690
Impulse withstand voltage (kV) Uimp 8
Operational voltage (V) Ue AC 50/60 Hz 440
Suitability for isolation IEC/EN 60947-2 yes
Utilisation category A
Pollution degree IEC 60664-1 3
Circuit breakers
Performance
Electrical characteristics as per IEC 60947-2
Rated current (A) In 40 °C
Number of poles
Breaking capacity levels
EasyPact CVS100/160/250 Breaking capacity (kA rms)
lcu AC 50/60 Hz 220/240 V
380/415 V
440 V
PB106448
Protection
Short-circuit protection Magnetic only
Overload/short-circuit protection Thermal magnetic
Electronic
with neutral protection (Off-0.5-1)
Earth-leakage protection By Vigi module
Installation/connections
Dimensions and weights
Dimensions (mm) Fixed, front connections 3P
WxHxD 4P
Weight (kg) Fixed, front connections 3P
EasyPact CVS400/630 4P
Connections
Connection terminals Pitch Without/With spreaders
A-4
CVS100 CVS160 CVS250 CVS400 CVS630
40 70 40 70 40 70 40 70 40 70
25 36 25 36 25 36 36 50 36 50
20 36 20 36 20 36 30 42 30 42
40 70 40 70 40 70 40 70 40 70
25 36 25 36 25 36 36 50 36 50
15 18 15 18 15 18 23 32 23 32
30000 25000 20000 15000 15000
30000 25000 20000 12000 8000
12000 12000 10000 6000 4000
b b b b b
b b b b b
- - - b b
- - - b b
b b b b b
105 x 161 x 86 105 x 161 x 86 105 x 161 x 86 140 x 255 x 110 140 x 255 x 110
140 x 161 x 86 140 x 161 x 86 140 x 161 x 86 185 x 255 x 110 185 x 255 x 110
1.8 1.8 2.0 4.7 5.2
2.2 2.3 2.6 6.3 7.1
A-5
Functions Protection of distribution systems
and characteristics TM-D thermal-magnetic trip units
TM-D thermal-magnetic trip units can be used on TM-D thermal-magnetic trip units
EasyPact CVS100-630 circuit breakers with
DB400003
performance levels B/F/N.
Protection...............................................................................
TM-D trip units are used mainly in electrical distribution applications for
protection of cables supplied by transformers.
Protection versions
bb 3-pole:
vv 3P 3D: 3-pole frame (3P) with detection on all 3 poles (3D)
bb 4-pole:
vv 4P 3D: 4-pole frame (4P) with detection on 3 poles (3D).
vv 4P 4D: 4-pole frame (4P) with detection on all 4 poles (same threshold for phases
and neutral).
Magnetic protection
Pick-up (A) Im fixed adjustable
accuracy ±20 % CVS100 190 300 400 500 500 500 640 800
CVS160/250 800 1250 1250 2000 2500
CVS400 1600 to 3200 (320A), 2000 to 4000 (400A)
CVS630 2500 to 5000
Thermal protection
Pick-up (A) Ir = In x ... adjustable in amps from 0.7 to 1 x In
tripping between
1.05 and 1.30 Ir
Neutral protection
Unprotected neutral 4P 3D no detection
Fully protected neutral 4P 4D 1 x Ir
(1) For temperatures not equal to 40°C, the thermal protection characteristics are modified. See the temperature derating table on page B-2.
Note: All the trip units have a transparent lead-sealable cover that protects access to the adjustment dials.
A-6
Protection of distribution systems
ETS 2.3 electronic trip unit and accessories
DB400166
505 565 5 6
440 630 4 7
370 3 8
315 2 10
Protection...............................................................................
The protection functions can be set using the adjustment dials.
Overload protection
Long-time protection with an adjustable threshold and fixed tripping delay:
bb Ir base setting (6-position dial from 0.5 to 1)
Short-circuit protection
Short-time and instantaneous protection:
bb short-time protection with an adjustable pick-up and fixed tripping delay
bb instantaneous protection with fixed pick-up.
A-7
Functions Earth-leakage protection
and characteristics Add-on protection against insulation faults using
a Vigi module
A Vigi module can be added to any three or four-pole Circuit breaker with add-on Vigi module (Vigi CVS)
CVS100 to 630 circuit breaker to form a Vigi CVS.
bb For general characteristics of circuit breakers, see pages A-2 and A-3.
bb Add-on Vigi modules: Earth-leakage protection is achieved by installing a Vigi
module (characteristics and selection criteria on next page) directly on the circuit
breaker terminals. It directly actuates the trip unit (magnetic, thermal-magnetic or
ETS).
PB106449
CVS100 b -
CVS160 b -
CVS250 b -
1 Sensitivity setting CVS400 - b
2 Time-delay setting (for selective earth-leakage protection).
3 Lead-seal fixture for controlled access to settings. CVS630 - b
4 Test button simulating an earth-fault for regular checks on Protection characteristics
the tripping function
5 Reset button (reset required after earth-fault tripping). Sensitivity adjustable adjustable
6 Rating plate I△n (A) 0.03 - 0.3 - 1 - 3 - 10 0.3 - 1 - 3 - 10 - 30
Time delay adjustable adjustable
Intentional delay (ms) 0 - 60 (2) - 150 (2) - 310 (2) 0 - 60 - 150 - 310
Max. break time (ms) < 40 < 140 < 300 < 800 < 40 < 140 < 300 < 800
Rated voltage 200... 440 200...440
V AC 50/60 Hz
(1) Vigi 3P modules may also be used on 3P circuit breakers used for two-phase protection.
(2) If the sensitivity is set to 30 mA, there is no time delay, whatever the time-delay setting.
Operating safety
The Vigi module is a user safety device. It must be tested at regular intervals (every 6
months) via the test button.
A-8
Motor protection
MA instantaneous trip units
3100
2000
2900
MA 220
2700 2200 220A/65
2450
DB400006
Circuit breakers with an MA trip unit are combined with a thermal relay and a
contactor or a starter.
Protection………………………………………………
E26988
MA trip units
Ratings (A) In at 65 °C 2.5 6.3 12.5 25 50 100 150 220 320 500
CVS100 b b b b b b - - - -
Circuit breaker CVS160 - - - - - b b - - -
CVS250 - - - - - - b b - -
CVS400 - - - - - - - - b -
CVS630 - - - - - - - - - b
Short-circuit protection (magnetic)
Pick-up (A) Im = In x ... setting setting setting
CVS100 6...14 x ln - -
CVS160/250 - 9...14 x ln -
CVS400/630 - - 6...13 x ln
A-9
Functions Switch-disconnectors
and characteristics Characteristics and performance
Switch-disconnectors
PB106451
A-10
CVS100NA CVS160NA CVS250NA CVS400NA CVS630NA
b b
b b
b b
b b
A-11
Functions Accessories and auxiliaries
and characteristics Overview
Connection A-14
Cable connectors
Interphase barriers
Sealable terminal
shields Rear connectors
Indication contact
cat.A
Voltage release
A-12
Accessories and auxiliaries
Device installation
DB400009
DB400010
DB400011
Mounting on a backplate. Mounting on rails. Mounting on DIN rail (with
adaptor).
DB400012
Mounting on a Prisma
mounting plate.
A-13
Functions Accessories and auxiliaries
and characteristics Connection of devices
Fixed circuit breakers are designed for standard front Front connection
connection using bars or cables with lugs.
Cable connectors are available for bare cables. Rear Bars or cables with lugs
connection is also possible. Standard terminals
EasyPact CVS100 to 630 come with terminals comprising snap-in nuts with screws:
bb EasyPact CVS100: M6 nuts and screws.
bb EasyPact CVS160/250: M8 nuts and screws
bb EasyPact CVS400/630: M10 nuts and screws.
These terminals may be used for:
bb direct connection of insulated bars or cables with lugs
DB400013
DB112169
bb terminal extensions.
Interphase barriers or terminal shields are recommended. They are mandatory for
certain connection accessories (in which case the interphase barriers are provided).
Bars
Insulated bar. When the switchboard configuration has not been tested, insulated bars are
mandatory.
Maximum size of bars
DB112170
Terminal extensions
Extensions with anti-rotation ribs can be attached to the standard terminals to
DB112172
DB112173
DB112177
A-14
Accessories and auxiliaries
Connection of devices
Bare cables
DB400014
DB112314 Bare-cable connectors may be used for both copper and aluminium cables.
1-cable connectors for EasyPact CVS100 to 250
The connectors snap directly on to the device terminals or are secured by clips to
right-angle and straight terminal extensions as well as spreaders.
Bare cable.
1-cable connectors for EasyPact CVS400 to 630
The connectors are screwed directly to the device terminals.
2-cable connectors for EasyPact CVS100 to 250 and 400/630
The connectors are screwed to device terminals or right-angle terminal extensions.
DB112316
DB112317
DB111326
1-cable 2-cable
connector for connector for
CVS100 to 250 CVS400/630. CVS100 to 250 CVS400/630.
DB111330
A-15
Functions Accessories and auxiliaries
and characteristics Selection of auxiliaries
EasyPact CVS100/160/250
Standard
DB115583
Rotary handle All EasyPact CVS100/160/250 circuit breakers and switch-disconnectors have slots
for the electrical auxiliaries listed below.
5 indication contacts (see page A-17)
OF1 OF2
bb 2 ON/OFF (OF1 and OF2)
SDE bb 1 trip indication (SD)
MN /
bb 1 fault-trip indication (SDE)
MX bb 1 earth-fault indication (SDV), when the device is equipped with a Vigi module.
1 remote-tripping release (see page A-18)
bb either 1 MN undervoltage release
bb or 1 MX shunt release.
EasyPact CVS400/630
Standard
DB115590
Rotary handle
All EasyPact CVS400/630 circuit breakers and switch-disconnectors have slots for
the electrical auxiliaries listed below.
6 indication contacts (see page A-17)
OF1 SD bb 3 ON/OFF (OF3)
OF2 bb 1 trip indication (SD)
OF3 SDE bb 1 fault-trip indication (SDE)
Reserved bb 1 earth-fault indication (SDV), when the device is equipped with a Vigi module.
MN / 1 remote-tripping release (see page A-18)
MX
bb either 1 MN undervoltage release
bb or 1 MX shunt release.
A-16
Accessories and auxiliaries
Indication contacts
One contact model provides circuit-breaker status These common-point changeover contacts provide remote circuit-breaker status
indications (OF - SD - SDE - SDV). information.
They can be used for indications, electrical locking, relaying, etc.
They comply with the IEC 60947-5 international recommendation.
Functions
Breaker-status indications, during normal operation or after a fault
A single type of contact provides all the different indication functions:
bb OF (ON/OFF) indicates the position of the circuit breaker contacts
bb SD (trip indication) indicates that the circuit breaker has tripped due to:
vv an overload
vv a short-circuit
vv an earth fault (Vigi)
DB125549
Installation
bb OF, SD, SDE and SDV functions: a single type of contact provides all these
different indication functions, depending on where it is inserted in the device. The
contacts clip into slots behind the front cover of the circuit breaker (or the Vigi module
for the SDV function).
The SDE function on a CVS100 - 630 A equipped with a magnetic, thermal-magnetic
or ETS2.3 trip unit requires the SDE adaptor.
A-17
Functions Accessories and auxiliaries
and characteristics Remote tripping
MN undervoltage release
DB125550
bb This release trips the circuit breaker when the control voltage drops below a
tripping threshold
bb The tripping threshold is between 0.35 and 0.7 times the rated voltage
bb Circuit breaker closing is possible only if the voltage exceeds 0.85 times the rated
voltage.
Characteristics
MX or MN voltage release. Power supply V AC 50/60 Hz: 24 - 48 - 100/130 - 200/240
50 Hz: 380/415 60 Hz: 208/277
V DC 12 - 24 - 30 - 48 - 60 - 125 -250
Operating threshold Opening 0.35 to 0.7 Un
Failsafe opening Possible opening Closing 0.85 Un
DB115605
A time delay unit for the MN release eliminates the risk of nuisance tripping due to
0
a transient voltage dip lasting y 200 ms. For shorter micro-outages, a system of
0.85 1.1 Un capacitors provides temporary supply to the MN at U > 0.7 to ensure non tripping.
Closing conditions of the MN release. The correspondence between MN releases and time-delay units is shown below.
Power supply Corresponding MN release
Unit with fixed delay 200 ms
48 V AC 48 V DC
Delayed 220 / 240 V AC 250 V DC
PB103752-32
DB115607
A-18
Accessories and auxiliaries
Rotary handles
A-19
Functions Accessories and auxiliaries
and characteristics Locks and sealing accessories
Locks
DB400025
DB400026 Locking in the OFF position guarantees isolation as per IEC 60947-2. Padlocking
systems can receive up to three padlocks with shackle diameters ranging from 5 to
8 mm (padlocks not supplied). Certain locking systems require an additional
accessory.
DB400029
Rotary handle
DB400018
Sealing accessories.
Access to Vigi-module
DB400019
settings
A-20
Accessories and auxiliaries
Escutcheons and protection collars
Escutcheons are an optional feature mounted on the IP40 escutcheons for fixed devices
switchboard door. They increase the degree of
protection to IP40, IK07. Protection collars maintain the There are three types of escutcheon with a gasket which are screwed to the door
degree of protection, whatever the position of the cut-out:
device (connected, disconnected). bb three escutcheons for all control types (toggle, handle or motor mechanism)
bb a wide model for Vigi modules that can be combined with the above.
DB400031
DB400030
Escutcheon for toggle without and with access to the trip unit.
DB400032
A-21
Installation
recommendations
B-2
EasyPact CVS Installation recommendations
Contents
Installation in switchboards
Power supply and weights B-3
Safety clearances and minimum distances B-4
Installation example B-5
B-1
Installation Operating conditions and temprature
recommendations derating
2000
Vibrations
CVS devices resist electromagnetic or mechanical vibrations.
Tests are carried out in compliance with standard IEC 60068-2-6 for the levels
required by merchant-marine inspection organisations (Veritas, Lloyds, etc.):
bb 2 to 13.2 Hz: amplitude ±1 mm
bb 13.2 to 100 Hz: constant acceleration 0.7 g.
Excessive vibration may cause tripping, breaks in connections or damage to
mechanical parts.
Degree of protection
CVS circuit breakers have been tested for degree of protection (IP) and mechanical
impact protection (IK). See page A-3.
Electronic trip units are not affected by variations in
temperature. If the trip units are used in high- The overload protection is calibrated at 40 °C in the lab. This means that when the
temperature environments, the ETS setting must ambient temperature is less than or greater than 40 °C, the Ir protection pick-up is
nevertheless take into account the temperature limits slightly modified.
of the circuit breaker. To obtain the tripping time for a given temperature:
bb see the tripping curves for 40 °C (see pages D-2 and D-3)
bb determine tripping times corresponding to the Ir value (thermal setting on the
device), corrected for the ambient temperature as indicated in the tables below.
DB115053
(A)
110
Settings of CVS100 to 630 equipped with TM-D trip units as a
100 function of the temperature
The table indicates the real Ir (A) value for a given rating and temperature.
90
Rat. Temperature (°C)
80
(A) 10 15 20 25 30 35 40 45 50 55 60 65 70
16 18.4 18 18 18 17 16.6 16 15.6 15.2 14.8 14.5 14 13.8
10 20 30 40 50 60 70 (°C) 25 28.8 28 27.5 27 26.3 25.6 25 24.5 24 23.5 23 22 21
Temperature derating curve for CVS100. 32 36.8 36 35.2 34.4 33.6 32.8 32 31.3 30.5 30 29.5 29 28.5
40 46 45 44 43 42 41 40 39 38 37 36 35 33.5
50 57.5 56 55 54 53 51 50 49 47 46 44 43 41
10 000
63 73 72 70 68 67 65 63 61 59 57 55 53 50
DB400102
DB400102
5 000
80 92 90 88 86 84 82 80 78 75.5 73 70.7 68 65
2 000
1 000 100 114 112 110 107 105 102.5 100 97 95 92.0 89 86 83
500
125 144 141 138 134 131 128 125 122 119 116 113 109 106
200
100
160 184 180 176 172 168 164 160 156 152 148 144 140 136
50 200 230 225 220 215 210 205 200 195 190 185 180 175 170
20
250 288 281 277 269 263 256 250 244 238 231 225 219 213
10
5 320 365 358 350.5 343 335.6 328 320 312 303.6 295 286 277 267.7
t(s)
2
TM80D : Im = 10 x In 400 456.6 447.7 438.6 429 419.7 410 400 390 379.3 368.5 357.3 345.8 334
1
.5 500 558.6 549 539.7 530 520.3 510.2 500 489.6 479 468 457 445.4 433.6
TM100D : Im = 10 x In
.2 600 672 660.5 649 637 625 612.6 600 587 574 560.6 547 532.7 518
.1
.05
.02
.01 t < 10 ms
.005
.002 CVS400 and 630 (equipped with ETS2.3 electronic trip unit)
.001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
The table below indicates the maximum long-time (LT) protection setting Ir (A)
I / Ir depending on the ambient temperature.
Type of Rating (A) Temperature (°C)
device 40 45 50 55 60 65 70
CVS400
Fixed 400 400 400 400 390 380 370 360
Thermal-protection curve with minimum and maximum
CVS630
values.
Fixed 630 630 615 600 585 570 550 535
B-2
Installation in switchboards
Power supply and weights
CVS circuit breakers can be supplied from either the top or the bottom, even when
equipped with a Vigi earth-leakage protection module, without any reduction in
performance. This capability facilitates connection when installed in a switchboard.
All connection and insulation accessories can be used on circuit breakers supplied
either from the top or bottom.
Weight
The table below presents the weights (in kg) of the circuit breakers and Vigi module.
B-3
Installation Installation in switchboards
recommendations Safety clearances and minimum distances
General rules
When installing a circuit breaker, minimum distances (safety clearances) must
be maintained between the device and panels, bars and other protection devices
installed nearby. These distances, which depend on the ultimate breaking capacity,
are defined by tests carried out in accordance with standard IEC 60947-2.
If installation conformity is not checked by type tests, it is also necessary to:
bb use insulated bars for circuit-breaker connections
bb segregate the busbars using insulating screens.
For CVS100 to 630 devices, terminal shields and interphase barriers are
recommended and may be mandatory depending on the operating voltage of the
device and type of installation (fixed, withdrawable, etc.).
Power connections
The table below indicates the rules to be respected for CVS100 to 630 devices to
ensure insulation of live parts for fixed devices.
DB400040
Possible, recommended or mandatory accessories: No insulating Interphase Long terminal Short terminal
accessory barriers shields (1) shields
DB115059
DB115060
DB115061
With:
Extension terminals
Possible
Cables + crimp lugs Mandatory
No (instead of ph. Recommended
(supplied)
barriers)
(1) Long terminal shields provide a degree of protection of IP40 (ingress) and IK07 (mechanical
impact).
B-4
Installation in switchboards
Installation example
Safety clearance
Minimum distance between two Minimum distance between circuit
adjacent circuit breakers breaker and front or rear panels
Front F
DB400046
DB400047
panel
A1
B=0 F
Bare or painted sheet metal Note: if F < 8 mm: an insulating screen or long
terminal shield is mandatory.
Minimum distance between circuit breaker and top, bottom or side panels
DB400048
DB400049
DB400050
D1 D1 D1
D2 C1
Devices without accessories. Devices with interphase barriers or long terminal shields.
Bars
Bars
Live busbars.
B-5
Dimensions and connection
C-2
EasyPact CVS Dimensions and connection
Contents
C-1
Dimensions and Dimensions and mounting
connection EasyPact CVS100 to 630
Dimensions 3P 4P
DB400055
DB400056
DB400057
DB400058
A4
A3
A A2
A1
X X X
A A2
A3
A4
C1 B B
C2 B1 B2
C3
Z Y Y
Interphase barriers. Long terminal shields (also available for CVS400/630 spreaders with 52.5 mm pitch:
Short terminal shields. B1 = 157.5 mm, B2 = 210 mm).
DB111411
DB112066
DB112067
F1 F1 F1 F1 F1
F2 F2 F2
F1 F1 F3
E4
X X X
E2
E1 E3
2 Ø6 ØT(1) Y 4 Ø6 4 Ø6
Y Y
On rails 3P 3P 4P
F1 F1 F3
DB400063
DB111412
DB112069
DB112070
F2 F2 F2
X X X
E2
E1
2 Ø6 Y Y 4 Ø6 Y 4 Ø6
DB400169
G4
G5
G3 X
G2
G1
C-2
Dimensions and mounting
Vigi CVS100 to 630
DB400068
DB400069
DB400070
A4
A3
A A2
X X
X
A6 A8
A5 A7 A9
C1
C2 B B
C3 B1 B1
B2 B2
Z
Y Y
F1 F1 F1
DB112079
DB112078
F2
F2 F2
F1
F1 F3
X
X X
E6 E1
E8
E5
E7
6 Ø6
Y 6 Ø6
ØT(1) 3 Ø6 Y
Y
(1) The ØT holes are required for rear connection only.
On rails 3P 3P 4P
F1 F1 F3
DB111421
DB400075
DB112081
DB112082
F2 F2 F2
X X X
E6 E1
E5
Y 6 Ø6 Y 6 Ø6
Y 3 Ø6
Type A A1 A2 A3 A4 A5 A6 A7 A8 A9 B B1 B2 C1 C2 C3 E1
CVS100/160/250 80.5 161 94 145 178.5 155.5 236 169 220 253.5 52.5 105 140 81 86 126 62.5
CVS400/630 127.5 255 142.5 200 237 227.5 355 242.5 300 337 70 140 185 95.5 110 168 100
Type E2 E3 E4 E5 E6 E7 E8 F1 F2 F3 G1 G2 G3 G4 G5 ØT U
CVS100/160/250 125 70 140 137.5 200 145 215 35 17.5 70 95 75 13.5 23 17.5 24 y 32
CVS400/630 200 113.5 227 200 300 213.5 327 45 22.5 90 - - - - - 32 y 35
C-3
Dimensions and Front-panel accessories
connection EasyPact CVS100 to 630
E21641
E21642
E21643
M2 M3
A1 D1 D2
DB115010
DB115011
DB115012
A2 X X
A3
B1 3.5 6.5
Y
For Vigi
DB400097
DB115018
DB115019
DB115020
X
79 X 64
69 3.5 6.5
Y
Type A1 A2 A3 B1 M2 M3
CVS100/160/250 91 114 101 157 115 102
CVS400/630 123 164 151 189 155 142
C-4
Front-panel cutouts
EasyPact CVS100 to 630
DB400115
DB400116
DB400117
76 116
X X X
29 41.5
Y Y
P3 R R
R1 R1
Z
DB400119
DB400120
DB400121
X X X
102 175
54.5
90
P3 47.5 63.5
95 127
Z Y Y
Type P3 R R1
CVS100/160/250 88 14.5 29
CVS400/630 112 31.5 63
C-5
Dimensions and Front-panel cutouts
connection Vigi CVS100 to 630
DB400123
DB400124
DB400125
X X X
85.5
148
38
38
P3 14.5
29
Z Y 29
32
Y
DB400127
DB400128
DB400129
X X X
85.5
148
38
38
P3 14.5
29
Z Y 29
32
Y
C-6
Power connections
EasyPact and Vigi CVS100 to 630
Connection locations
C1 B1 B1 B1
DB400134
DB400135
A1
X X
A2
A3
C2 Y
Z
Type A1 A2 B1 C1 C2 Type A1 A3 B1 C1 C2
CVS100/160 70 140 35 19.5 19.5 CVS100/160 + Vigi 70 215 35 19.5 21.5
CVS250 70 140 35 21.5 19.5 CVS250 + Vigi 70 215 35 21.5 21.5
CVS400/630 113.5 227 45 26 26 CVS400/630 + Vigi 113.5 327 45 26 26
DB400137
DB400138
10.5 14
70 113.5
X X
Cables with lugs/bars Bars/cables with lugs
43 for short RC
88 for long RC
10 ∅8.6
DB400137
13
18
70
6 ∅20
X
CVS400/630
Z
DB116108
50 for short RC
115 for long RC
15 ∅13 ∅23.2
14
30
113.5
8
X
C-7
Dimensions and Power connections
connection EasyPact and Vigi CVS100 to 630
DB115452
DB400138
DB115451
Z Z 63
22
70 70
X X
DB400139
CVS400/630
DB115455
DB115454
Z Z
46.5
14
113.5 113.5
X X
70
41
DB115459
DB115460
Z
37.5 61 8
39.5 (b) 4
20.5 34
70 113.5
(b) CVS250.
X X
41
30
70
C-8
Power connections
EasyPact and Vigi CVS100 to 630
DB400143
DB400144
DB400145
E2 E2 F2 E2 E2 E2 C3
F1
X
X X
Z
CVS400/630
C4
Y Y
Type C3 C4 E1 E2 E3 F1 F2
CVS100/160 23.5 - 114 45 159 100 11
CVS250 25.5 - 114 45 159 100 11
X
CVS400/630 - 44 135 52.5 187.5 152.5 15
170 70 240 166 15
Z
C-9
Dimensions and Power connections
connection Connection of insulated bars or cables with lugs
to EasyPact and Vigi CVS100 to 630
DB115655
l (mm) 20 y I y 25 20 y I y 25
d (mm) y 10 y 10
Ø Ø
Tinned copper 400 e (mm) y6 y6
d Ø (mm) 6.5 8.5
I
Lugs L (mm) y 25 y 25
Spreaders: L L Ø (mm) 6.5 8.5
separate parts e Torque (Nm) (1) 10 15
(1) Tightening torque on the circuit breaker for spreaders or terminal extensions.
DB112177
Spreaders and straight, right-angle, 45°, double-L and edgewise terminal extensions
are supplied with flexible interphase barriers.
Tinned copper
l (mm) d + 15 30 y I y 34
d (mm) y 20 y 15
Tinned copper Ø
400 Ø e (mm) 3 y e y 10 3 y e y 10
d Ø (mm) 12.5 10.5
I
Accessories for CVS100 to 630 L
Lugs L (mm) y 40 y 32
L
Right-angle terminal extensions Ø (mm) 12.5 10.5
e
DB112173
side.
C-10
Power connections
Connection of bare cables to EasyPact and
Vigi CVS100 to 630
DB112317
DB112315
1-cable 2-cable
connector connector
DB111326
C-11
Additional characteristics
D-2
EasyPact CVS Additional characteristics
Contents
Tripping curves
EasyPact CVS100 to 630 Protection of distribution systems D-2
EasyPact CVS100 to 250 Motor protection D-5
Current and energy limiting curves D-6
D-1
Additional characteristics Tripping curves
EasyPact CVS100 to 630
Protection of distribution systems
10 000 10 000
DB400094
DB400095
5 000 5 000
2 000 2 000
1 000 1 000
500 500
200 200
100 100
50 50
20 20
10 10
5 5
t(s) t(s)
2 2
TM16D/25D : Im = 12 x In TM32D : Im = 12.5 x In
1 1
.5 .5
.2 .2
.1 .1
.05 .05
.02 .02
.01 t < 10 ms .01 t < 10 ms
.005 .005
.002 .002
.001 .001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir I / Ir
TM40D/50D TM63D
10 000 10 000
DB400096
DB400101
5 000 5 000
2 000 2 000
1 000 1 000
500 500
200 200
100 100
50 50
20 20
10 10
5 5
t(s) t(s)
2 2
TM40D : Im = 12.5 x In TM63D : Im = 8 x In
1 1
.5 .5
.2 TM50D : Im = 10 x In .2
.1 .1
.05 .05
.02 .02
.01 t < 10 ms .01 t < 10 ms
.005 .005
.002 .002
.001 .001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir I / Ir
D-2
Tripping curves
EasyPact CVS100 to 630
Protection of distribution systems
10 000 10 000
DB400102
DB400103
5 000 5 000
2 000 2 000
1 000 1 000
500 500
200 200
100 100
50 50
20 20
10 10
5 5
t(s) t(s)
2 2
TM80D/100D : Im = 8 x In TM125D : Im = 10 x In
1 1
.5 .5
.2 TM160D : Im = 8 x In
.2
.1 .1
.05 .05
.02 .02
.01 t < 10 ms .01 t < 10 ms
.005 .005
.002 .002
.001 .001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir I / Ir
TM200D/250D TM320D/400D
10 000 10 000
DB400104
DB400106
5 000 5 000
2 000 2 000
1 000 1 000
500 500
200 200
100 100
50 50
20 20
10 10
5 5
t(s) t(s)
2 2
TM200D/250D : TM320D/400D :
1 1
Im = 10 x In Im = 5...10 x In
.5 .5
.2 .2
.1 .1
.05 .05
.02 .02
.01 t < 10 ms .01 t < 10 ms
.005 .005
.002 .002
.001 .001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir I / Ir
D-3
Additional characteristics Tripping curves
EasyPact CVS400 to 630
Protection of distribution systems
TM500D TM600D
10 000 10 000
DB400107
DB400108
5 000 5 000
2 000 2 000
1 000 1 000
500 500
200 200
100 100
50 50
20 20
10 10
5 5
t(s) t(s)
2 2
TM500D : TM600D :
1 1
Im = 5...10 x In Im = 4.2...8.3 x In
.5 .5
.2 .2
.1 .1
.05 .05
.02 .02
.01 t < 10 ms .01 t < 10 ms
.005 .005
.002 .002
.001 .001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir I / Ir
10 000
DB400105
DB400105
5 000
2 000
Ir = 0.5...1 x In
1 000
500
200
100
50
20
10
5
t(s)
2
Isd = 2...10 x Ir
1
.5
.2
.1
.05
.02
.01 Reflex tripping :
t < 10 ms
.005
.002 I = 11 x In
.001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir
D-4
Tripping curves
EasyPact CVS100 to 250
Motor protection
10 000 10 000
DB118546
DB115716
5 000 5 000
2 000 2 000
1 000 1 000
500 500 Thermal withstand
.2 .2
.1 .1
.05 .05
.02 .02
.01 t < 10 ms .01 t < 10 ms
.005 .005
.002 .002
.001 .001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir I / Ir
Reflex tripping.
MA320 MA500
10 000 10 000
DB400110
DB400111
5 000 5 000
2 000 2 000
1 000 1 000
500 500
200 200
100 Thermal withstand 100 Thermal withstand
50 50
20 20
10 10
5 5
t(s) t(s)
2 2
1 1
.5 .5
.2 Im = 6 ...13 x In .2 Im = 6 ...13 x In
.1 .1
.05 .05
.02 .02
.01 t < 10 ms .01 t < 10 ms
.005 .005
.002 .002
.001 .001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / In I / In
D-5
Additional characteristics Tripping curves
Current and energy limiting curves
The limiting capacity of a circuit breaker is its aptitude Ics = 100 % Icu
to let through a current, during a short-circuit, that is The exceptional limiting capacity of the EasyPact CVS range greatly reduces the
less than the prospective short-circuit current. forces created by fault currents in devices.
The result is a major increase in breaking performance.
In particular, the service breaking capacity Ics is equal to 100 % of Icu.
The Ics value, defined by IEC standard 60947-2, is guaranteed by tests comprising
the following steps:
bb break three times consecutively a fault current equal to 100% of Icu
(Isc)
DB115719
Prospective
bb check that the device continues to function normally, that is:
Isc peak vv it conducts the rated current without abnormal temperature rise
vv protection functions perform within the limits specified by the standard
Prospective
current vv suitability for isolation is not impaired.
Prospective
Longer service life of electrical installations
Isc Current-limiting circuit breakers greatly reduce the negative effects of short-circuits
on installations.
Limited Isc
peak Thermal effects
Actual Less temperature rise in conductors, therefore longer service life for cables.
current
Mechanical effects
Limited
Isc Reduced electrodynamic forces, therefore less risk of electrical contacts or busbars
being deformed or broken.
(t)
Electromagnetic effects
The exceptional limiting capacity of the EasyPact CVS range is Fewer disturbances for measuring devices located near electrical circuits.
due to the rotating double-break technique (very rapid natural
repulsion of contacts and the appearance of two arc voltages Current and energy limiting curves
in-series with a very steep wave front). The limiting capacity of a circuit breaker is expressed by two curves which are a
function of the prospective short-circuit current (the current which would flow if no
protection devices were installed):
bb the actual peak current (limited current)
bb thermal stress (A2s), i.e. the energy dissipated by the short-circuit in a conductor
with a resistance of 1 Ω.
D-6
Tripping curves
Current and energy limiting curves
Current-limiting curves
DB116369
300
DB116369
200
146
100
80
70
60
50
40 N CVS630
k F
30 CVS400
20 F CVS250
B CVS100
CVS160
10
8
7
6
5
4
2 3 4 6 10 20 30 40 50 70 100 200 300
kA rms
Energy-limiting curves
DB116371
9
10
DB116371
5
3
2
1.41
8
10
5
3
2
7
10
2
As 5
F N
3 CVS630
CVS400
2
6
10 B F
CVS250
5 CVS100
CVS160
3
2
5
10
5
3
2
2 3 4 6 10 20 30 40 50 70 100 150 200 300
kA rms
D-7
Catalogue numbers
E-2
EasyPact CVS Catalogue numbers
Contents
E-1
E-2
EasyPact CVS EasyPact CVS100 to 250
Contents
Accessories E-11
EasyPact and Vigi CVS100/160/250 E-11
E-3
Catalogue numbers CVS100/160/250B:
complete fixed/FC device
EasyPact and Vigi CVS100/160/250B
(25 kA 380/415 V)
EasyPact CVS100/160/250B
With TM-D thermal-magnetic trip unit
EasyPact CVS100B (25 kA at 380/415 V)
DB400150
Rating 3P 3d 4P 3d 4P 4d
TM16D LV510300 LV510310 LV510320
TM25D LV510301 LV510311 LV510321
TM32D LV510302 LV510312 LV510322
TM40D LV510303 LV510313 LV510323
TM50D LV510304 LV510314 LV510324
TM63D LV510305 LV510315 LV510325
TM80D LV510306 LV510316 LV510326
TM100D LV510307 LV510317 LV510327
EasyPact CVS160B (25 kA at 380/415 V)
Rating 3P 3d 4P 3d 4P 4d
TM100D LV516301 LV516311 LV516321
TM125D LV516302 LV516312 LV516322
TM160D LV516303 LV516313 LV516323
EasyPact CVS250B (25 kA at 380/415 V)
Rating 3P 3d 4P 3d 4P 4d
TM160D LV525301 LV525311 LV525321
TM200D LV525302 LV525312 LV525322
TM250D LV525303 LV525313 LV525323
EasyPact CVS100/160/250B
With Magnetic trip unit MA
EasyPact CVS100B (25 kA at 380/415 V)
DB400153
Rating 3P 3d
MA2,5 LV510430
MA6,3 LV510431
MA12,5 LV510432
MA25 LV510433
MA50 LV510434
MA100 LV510435
EasyPact CVS160B (25 kA at 380/415 V)
Rating 3P 3d
MA100 LV516430
MA150 LV516431
EasyPact CVS250B (25 kA at 380/415 V)
Rating 3P 3d
MA150 LV525435
MA220 LV525436
Vigi CVS100/160/250B
With TM-D thermal-magnetic trip unit
Vigi CVS100B (25 kA at 380/415 V) equipped with MH Vigi module (200 to 440 V)
DB400153
Rating 3P 3d 4P 3d 4P 4d
TM16D LV510360 LV510370 LV510380
TM25D LV510361 LV510371 LV510381
TM32D LV510362 LV510372 LV510382
TM40D LV510363 LV510373 LV510383
TM50D LV510364 LV510374 LV510384
TM63D LV510365 LV510375 LV510385
TM80D LV510366 LV510376 LV510386
TM100D LV510367 LV510377 LV510387
Vigi CVS160B (25 kA at 380/415 V) equipped with MH Vigi module (200 to 440 V)
Rating 3P 3d 4P 3d 4P 4d
TM100D LV516361 LV516371 LV516381
TM125D LV516362 LV516372 LV516382
TM160D LV516363 LV516373 LV516383
Vigi CVS250B (25 kA at 380/415 V) equipped with MH Vigi module (200 to 440 V)
Rating 3P 3d 4P 3d 4P 4d
TM160D LV525361 LV525371 LV525381
TM200D LV525362 LV525372 LV525382
TM250D LV525363 LV525373 LV525383
E-4
CVS100/160/250F:
complete fixed/FC device
EasyPact and Vigi CVS100/160/250F
(36 kA 380/415 V)
EasyPact CVS100/160/250F
With TM-D thermal-magnetic trip unit
EasyPact CVS100F (36 kA at 380/415 V)
DB400150
Rating 3P 3d 4P 3d 4P 4d
TM16D LV510330 LV510340 LV510350
TM25D LV510331 LV510341 LV510351
TM32D LV510332 LV510342 LV510352
TM40D LV510333 LV510343 LV510353
TM50D LV510334 LV510344 LV510354
TM63D LV510335 LV510345 LV510355
TM80D LV510336 LV510346 LV510356
TM100D LV510337 LV510347 LV510357
EasyPact CVS160F (36 kA at 380/415 V)
Rating 3P 3d 4P 3d 4P 4d
TM100D LV516331 LV516341 LV516351
TM125D LV516332 LV516342 LV516352
TM160D LV516333 LV516343 LV516353
EasyPact CVS250F (36 kA at 380/415 V)
Rating 3P 3d 4P 3d 4P 4d
TM160D LV525331 LV525341 LV525351
TM200D LV525332 LV525342 LV525352
TM250D LV525333 LV525343 LV525353
EasyPact CVS100/160/250F
With MA magnetic trip unit
EasyPact CVS100F (36 kA at 380/415 V)
DB400155
Rating 3P 3d
MA2.5 LV510440
MA6.3 LV510441
MA12.5 LV510442
MA25 LV510443
MA50 LV510444
MA100 LV510445
EasyPact CVS160F (36 kA at 380/415 V)
Rating 3P 3d
MA100 LV516439
MA150 LV516440
EasyPact CVS250F (36 kA at 380/415 V)
Rating 3P 3d
MA150 LV525438
MA220 LV525439
E-5
Catalogue numbers CVS100/160/250F:
complete fixed/FC device (cont.)
Vigi CVS100/160/250F
(36 kA 380/415 V)
Vigi CVS100/160/250F
With TM-D thermal-magnetic trip unit
Vigi CVS100F (36 kA at 380/415 V) equipped with MH Vigi module (200 to 440 V)
DB400153
Rating 3P 3d 4P 3d 4P 4d
TM16D LV510390 LV510400 LV510410
TM25D LV510391 LV510401 LV510411
TM32D LV510392 LV510402 LV510412
TM40D LV510393 LV510403 LV510413
TM50D LV510394 LV510404 LV510414
TM63D LV510395 LV510405 LV510415
TM80D LV510396 LV510406 LV510416
TM100D LV510397 LV510407 LV510417
Vigi CVS160F (36 kA at 380/415 V) equipped with MH Vigi module (200 to 440 V)
Rating 3P 3d 4P 3d 4P 4d
TM100D LV516391 LV516401 LV516411
TM125D LV516392 LV516402 LV516412
TM160D LV516393 LV516403 LV516413
Vigi CVS250F (36 kA at 380/415 V) equipped with MH Vigi module (200 to 440 V)
Rating 3P 3d 4P 3d 4P 4d
TM160D LV525391 LV525401 LV525411
TM200D LV525392 LV525402 LV525412
TM250D LV525393 LV525403 LV525413
E-6
CVS100/160/250NA:
complete fixed/FC device
EasyPact CVS100/160/250NA
Rating 3P 4P
100 LV510425 LV510426
EasyPact CVS160NA
Rating 3P 4P
160 LV516425 LV516426
EasyPact CVS250NA
Rating 3P 4P
250 LV525425 LV525426
Rating 3P 4P
100 LV510427 LV510428
EasyPact CVS160NA
Rating 3P 4P
160 LV516427 LV516428
EasyPact CVS250NA
Rating 3P 4P
250 LV525427 LV525428
E-7
Catalogue numbers Add-on Vigi module
EasyPact and Vigi CVS100/160/250
E-8
Catalogue numbers Accessories
EasyPact and Vigi
CVS100/160/250
2 long LV429236
Set of 4 LV429243
Set of 4 LV429228
1 x (120 to 185 mm²) ; y 250 A Set of 3 LV429259
Set of 4 LV429260
Clips for connectors Set of 10 LV429241
DB112726
Aluminium connectors for 2 cables (1) 2 x (50 to 120 mm²) ; y 250 A Set of 3 LV429218
DB112227
Set of 4 LV429219
Terminal extensions
Edgewise terminal extensions (1) Set of 3 LV429308
DB112231
Set of 4 LV429308
Set of 4 LV429262
Set of 4 LV429264
4P LV431564
E-9
Accessories
EasyPact and Vigi
CVS100/160/250
Set of 4 LV429256
For cable 150 mm² Set of 3 LV429253
Set of 4 LV429257
For cable 185 mm² Set of 3 LV429254
Set of 4 LV429258
Crimp lugs for aluminium cable (1)
For cable 150 mm² Set of 3 LV429504
DB112238
Set of 4 LV429505
For cable 185 mm² Set of 3 LV429506
Set of 4 LV429507
Insulation accessories
1 short terminal shield for breaker 3P LV429515
DB400161
4P LV429516
4P LV429518
4P LV429331
E-10
Catalogue numbers Accessories
EasyPact and Vigi
CVS100/160/250
Electrical auxiliaries
Auxiliary contacts (changeover)
OF or SD or SDE or SDV 29450
DB112254
Voltage releases
Voltage MX MN
DB111454
E-11
Accessories
EasyPact and Vigi
CVS100/160/250
Rotary handles
Direct rotary handle
With black handle LV429337
DB112259
Locks
Toggle locking device for 1 to 3 padlocks
By removable device 29370
DB400164
E-12
Catalogue numbers Accessories
EasyPact and Vigi
CVS100/160/250
Interlocking
Mechanical interlocking for circuit breakers
With toggles 29354
DB111486
Installation accessories
Front-panel escutcheons
IP40 toogle escutcheon (small cut-out) 29315
E21641
E21641
IP40
Lead-sealing accessories
Bag of accessories LV429375
DB115615
Spare parts
10 toggle extensions LV429313
E18624
E-13
E-14
EasyPact CVS EasyPact CVS400 to 630
Contents
Accessories E-21
EasyPact and Vigi CVS400/630 E-21
E-15
Catalogue numbers CVS400/630:
complete fixed/FC device
EasyPact and Vigi
CVS400/630F/N
EasyPact CVS400/630F
With TM-D thermal-magnetic trip unit
EasyPact CVS400F (36 kA at 380/415 V)
DB400008
Rating 3P 3d 4P 3d 4P 4d
TM320D LV540305 LV540308 LV540311
TM400D LV540306 LV540309 LV540312
EasyPact CVS630N (36 kA at 380/415 V)
Rating 3P 3d 4P 3d 4P 4d
TM500D LV563305 LV563308 LV563311
TM600D LV563306 LV563309 LV563312
EasyPact CVS400/630N
With TM-D thermal-magnetic trip unit
EasyPact CVS400F (50 kA at 380/415 V)
DB400008
Rating 3P 3d 4P 3d 4P 4d
TM320D LV540315 LV540318 LV540321
TM400D LV540316 LV540319 LV540322
EasyPact CVS630F (50 kA at 380/415 V)
Rating 3P 3d 4P 3d 4P 4d
TM500D LV563315 LV563318 LV563321
TM600D LV563316 LV563319 LV563322
E-16
CVS400/630:
complete fixed/FC device
EasyPact and Vigi
CVS400/630F/N
EasyPact CVS400/630F
With MA magnetic trip unit
EasyPact CVS400F (36 kA at 380/415 V)
Rating 3P 3D
MA320 LV540550
DB400020
5500 4000
5000 4500
Rating
MA500 LV563550
EasyPact CVS630N (50 kA at 380/415 V)
Rating
MA500 LV563552
E-17
Catalogue numbers CVS400/630:
complete fixed/FC device
EasyPact CVS400/630N
(36 kA 380/415 V)
EasyPact CVS400/630F
ETS 2.3 electronic trip unit (LS0I protection)
3P 3d 4P 3d, 4d, 3d + N/2
DB400021
6
5 7
4 8
3 10
565 2
505 630
440
370
315
EasyPact CVS400/630N
ETS 2.3 electronic trip unit (LS0I protection)
3P 3d 4P 3d, 4d, 3d + N/2
DB400021
6
5 7
4 8
3 10
565 2
505 630
440
370
315
6
5 7
4 8
3 10
2
565
505 630
440
370
315
6
5 7
4 8
3 10
2
565
505 630
440
370
315
E-18
CVS400/630:
complete fixed/FC device
EasyPact CVS400/630NA
3P 4P
DB400023
3P 4P
DB400024
E-19
Catalogue numbers Add-on Vigi module
EasyPact and Vigi CVS400/630
E-20
Accessories
EasyPact and Vigi CVS400/630
2 long LV432476
Set of 4 LV432480
Set of 4 LV432482
Set of 4 LV432487
4P LV432491
70 mm 3P LV432492
4P LV432493
Crimp lugs for copper cable (1)
For cable 240 mm2 Set of 3 LV432500
E18602
Set of 4 LV432501
For cable 300 mm² Set of 3 LV432502
Set of 4 LV432503
Supplied with 2 (or 3) interphase barriers
Crimp lugs for aluminium cable (1)
For cable 240 mm² Set of 3 LV432504
E30908
Set of 4 LV432505
For cable 300 mm² Set of 3 LV432506
Set of 4 LV432507
Supplied with 2 (or 3) interphase barriers
Insulation accessories
Short terminal shield, 45 mm (1 piece) 3P LV432591
E18618
4P LV432592
Long terminal shield, 45 mm (1 piece) 3P LV432593
4P LV432594
Interphase barriers Set of 6 LV432570
2 insulating screens (70 mm pitch) 52,5 mm 3P LV432595
E18606
4P LV432596
70 mm 3P LV432578
4P LV432579
(1) supplied with 2 or 3 interphase barriers
E-21
Catalogue numbers Accessories
EasyPact and Vigi
CVS400/630
Electrical auxiliaries
Auxiliary contacts (changeover)
OF or SD or SDE or SDV 29450
E18608
Voltage releases
Voltage MX MN
E18609
E-22
Accessories
EasyPact and Vigi
CVS400/630
Rotary handle
Direct rotary handle
Standard black handle LV432597
E18611
Locks
Toggle locking device for 1 to 3 padlocks
By removable device 29370
E18621
E-23
Catalogue numbers Accessories
EasyPact and Vigi
CVS400/630
Interlocking
Mechanical interlocking for circuit breakers
With toggles 32614
E21288
1 set of 2 keylocks (1 key only, keylock kit not included) Ronis 1351B.500 41950
Profalux KS5 B24 D4Z 42878
(1) for only 1 device
Installation accessories
Front-panel escutcheons
IP40 Toggle escutcheon (small cut-out) 32556
E21641
Lead-sealing accessories
LV429375
Spare parts
Front-panel escutcheons
Toggle extension LV432553
Bag of screws LV432552
Test
Test kits
Mini test kit for STR trip units 43362
E21290
E-24
Notes
E-25
Notes
E-26
© 2011 - Schneider Electric - All rights reserved.
Schneider Electric Industries SAS As standards, specifications and designs change from time to time, please ask for confirmation
35, rue Joseph Monier of the information given in this publication.
CS 30323
F- 92506 Rueil Malmaison Cedex This document has been printed on ecological paper
LVED210011EN 09-2011