EasyPact EZC
EasyPact EZC
EasyPact EZC
EasyPact EZC
Moulded-case circuit breakers
from 15 to 630 A
Catalogue
2013
EasyPact EZC
General contents
Presentation
Functions
and characteristics
A-1
Busbars
B-1
Installation guide
C-1
Catalogue numbers
D-1
So easy, so simple
With just three sizes of circuit breakers,
Schneider Electrics EasyPactTM EZC system is the
simple, universal solution to fit all low-voltage
protection needs.
> The fixed version is particularly adapted
to the OEM and Building markets, offering
optimum performance at a competitive price.
Buildings
CPB100607-001
Marine
IEC 60947-2
EN 60947-2
JISC8201-2-1/C8201-2-2 (annex 1 and 2)
GB 14048.2
NEMA-AB1
UL508 (1)
CSA22-2 (2)
IACS for Merchant Marine
(International Association of Classification Societies:
ABS, BV, CCS, DNV, GL, KRS, LR, NK, RINA)**
(1) Only for the 250A and 400A models
(2) Only for the 100A and 250A models
DB402689_01
Easy to choose
Breaking capacity
Icu kA at 400/415 V AC
50
36
30
25
18
15
10
7.5
EZC250H
EZCV250H
EZC250N
EZCV250N
EZC400H
EZC630H
EZC400N
EZC630N
EZC100H
EZC100N
EZC250F
EZC100F
EZC100B
15 A
60 A 100 A
250 A
400 A
630 A
Easy to install
> Fixed front mounting
> Plug-in mounting
> Front connexions
> Bare cables connected through cable lugs,
screwed inside the breaker
> Field-installable auxiliaries and accessories
> Built-in earth-leakage protection
> Interchangeable MCCB and ELCB
Easy to use
TM
C 250 ELCB
EasyPact EZ th-Leakage Circuit
ted Ear
Built-in Integra
) function
Breaker (ECLB
MCCB
ngeable with
fully intercha
d
B foot print an
same MCC
panel cut
EasyPactTM EZC:
Build your complete
solution with
Schneider Electric
Timely
delivery,
wherever
you are
Schneider Electric
offers a worldrenowned logistics
network capable of
getting EasyPactTM
EZC products to you
fast, wherever you
are.
PB104903
Accessories
CPB100610
CPB100609
EasyPact EZC
Presentation
II
General characteristics
A-2
Selection table
A-6
EasyPact EZC100
EasyPact EZC250
EasyPact EZCV250
EasyPact EZC400-630
A-10
A-10
A-11
A-12
A-13
A-14
A-16
A-18
A-19
Plug-in
100 A
Insulation of live parts
250 A
Insulation of live parts
A-20
A-21
A-22
A-23
A-24
A-26
A-28
A-30
A-31
A-32
A-33
A-34
B-1
C-1
D-1
A-1
CDB500612
CDB500611
Functions
and characteristics
Ui=690Va 50/60Hz
IEC 60947-2
JIS C8201-2-1
Ue (V)
230/240a
400/415a
440
a
550
a
250
c
U (V)
240
a
277/480a
NEMA - AB1
Icu/Ics (kA)
85 / 43
36 / 18
25 / 13
10 / 5
30 / 15
HIC (kAmps)
85
25
DL 06253
CDB500613
General characteristics
EasyPact EZC circuit breakers and auxiliaries comply with the following international
standards:
b IEC 60947-1 - general rules
b IEC 60947-2 - low-voltage switchgear and controlgear, part 2 (circuit breakers)
b European (EN 60947-1 and EN 60947-2) and the corresponding national
standards
b GB 14048.2
b JIS C8201-2-1 Annex 1 and Annex 2, for molded case circuit breakers
b JIS C8201-2-2 Annex 1 and Annex 2, for earth-leakage circuit breakers
b NEMA-AB1 (High Interrupting Capacity): American standard
b UL508/CSA 22-2 no. 14.
marking
Pollution degree
EasyPact EZC circuit breakers are certified for operation in pollution-degree III
environments as defined by IEC standard 60947 (industrial environments).
Tropicalisation
EasyPact EZC circuit breakers have successfully passed the tests prescribed by the
following standards for extreme atmospheric conditions:
b IEC 60068-2-1 - dry cold (-55 C)
b IEC 60068-2-2 - dry heat (+85 C)
b IEC 60068-2-30 - damp heat (95 % relative humidity at 55 C)
b IEC 60068-2-52 - salt mist (severity level 2).
All EasyPact EZC circuit breakers are suitable for isolation as defined in IEC
standard 60947-2:
b the isolation position corresponds to the O (OFF) position
b the operating handle cannot indicate the O (OFF) position (green colour visible)
unless the contacts are effectively open
b padlocks may not be installed unless the contacts are open
b installation of a rotary handle does not alter the reliability of the position-indication
system.
The isolation function is certified by tests guaranteeing:
b the mechanical reliability of the position indication system
b the absence of leakage currents
b overvoltage withstand capacity between upstream and downstream connections.
EasyPact EZC circuit breakers take into account important concerns for
environmental protection. Most components are recyclable and the parts are marked
as specified in applicable standards.
A-2
Ambient temperature
b EasyPact EZC circuit breakers has been particularly designed to hold 100 % In at
50 C without tripping in normal condition (except for earth-leakage circuit breakers).
b EasyPact EZC circuit breakers may be used between -25 C and +70 C.
b The permissible storage-temperature range for EasyPact EZC circuit breakers in
the original packing is -35 C to +85 C.
DB116374
Installation
EasyPact EZC circuit breakers are designed for easy installation in the various types
of switchboards. They may be mounted vertically, horizontally or flat on their back
without any derating of characteristics.
Installation positions.
DB116375
Power supply
EasyPact EZC circuit breaker can be supplied from either the top or the bottom
(reverse feeding) without any reduction in performance. For earth-leakage circuit
breakers, reverse feeding is possible only up to 240 V AC.
This capability facilitates connection when installed in a switchboard.
Degree of protection
Reverse feeding.
With toggle
DB116377
IP20
IK07
IP40
IK07
IP40
IK07
IP54
IK07
IP54
IK08
DB116380
DB116379
DB116378
DB116381
With toggle
A-3
Functions
and characteristics
CPB100611
Earth-leakage protection
EasyPact EZC earth-leakage circuit breakers comply with all the international
standards listed page A-2:
b IEC 60947-1
b IEC 60947-2
b EN 60947-1
b EN 60947-2
b GB 14048.2
b JIS C8201-2-2 Annex 1 and Annex 2
b NEMA-AB1 (High Interrupting Capacity)
b UL508/CSA 22-2 no. 14.
DB125803
Power supply
Reverse feeding
EasyPact EZC earth-leakage circuit breakers can be supplied from either the top or
the bottom for voltages up to 300 V AC. For voltages over 300 V AC, only supply
from the top is possible (Line-Load indication on the cover of the breaker).
Power supply of the electronics
EasyPact EZC earth-leakage circuit breakers are self-supplied by the distributionsystem voltage and therefore do not require any external source. They fully comply
with new IEC requirements (Annex B): they are powered from the three phases and
continue to function even if one phase is missing.
Dielectric tests
Tripping features
1
2
3
4
5
6
Tripping indications:
b EasyPact EZC earth-leakage circuit breakers have a yellow mechanical indicator
to locally signal tripping due to an earth fault.
b EasyPact EZC earth-leakage circuit breakers may be equipped with an earthleakage alarm switch (ALV) to remotely signal tripping due to an earth fault.
Resetting
EasyPact EZC earth-leakage circuit breakers are fully reset by the operating handle.
After resetting, tripping indicators (mechanical and ALV) come to normal position.
A-4
adjustable
adjustable
DB125805
EasyPact
TM
A-5
Functions
and characteristics
Selection table
CPB100600
EZC100-1P.
Fixed version
Plug-in version
Number of poles
Rated current (A)
In
Ui
Uimp
Ue
at 40 C
AC 50/60 Hz
DC
Ics
CPB100601
CPB100602
EZC100-2P.
AC 50/60 Hz 110/130 V
220/230/240 V
380 V
400/415 V
440 V
550 V
DC
125 V (1P)
250 V
(2P in series)
% Icu
110-400 V
415-550 V
Mechanical
Electrical
In/415 V
HIC
AC 50/60 Hz 240 V
277/480 V
Protection
Overload protection
Instantaneous protection
Bimetal
Magnetic
Fixed (20 %)
Auxiliary switch
Alarm switch
Combined AX + AL
Shunt trip release
Undervoltage release
AX
AL
AXAL
SHT
UVR
Auxiliaries
Indication contacts
EZC100-3P.
Voltage releases
CPB100603
Installation
Connection
Accessories
Crimp lugs/bars
Box lugs for bare cables
Rotary handles
Terminal extensions
Spreaders
Phase barriers
Terminal shields
Padlocking system
DIN rail adaptor
EZC100-4P.
Dimensions (mm)
Weight (kg)
EZC250-3P.
A-6
DxH
W
Direct
Extended
EZC100B
EZC100F
EZC100N
b
EZC250F
EZC250N
EZC250H
690
6
550
-
3
15, 16, 20, 25,
30, 32, 40, 45,
50, 60, 63, 75,
80, 100
690
6
550
250
1
15, 16, 20, 25,
30, 32, 40, 45,
50, 60, 63, 75,
80, 100
690
6
415
125
3
100, 125, 150,
160, 175, 200,
225, 250
3
100, 125, 150,
160, 175, 200,
225, 250
2-3
100, 125, 150,
160, 175, 200,
225, 250
690
6
550
250
690
6
550
250
690
6
550
250
10
10
7.5
7.5
5
2.5
-
25
25
10
10
7.5
5
5
5
100
100 (1)
30
30
20
10
10
10
25
25
18
18
15
5
5
5
50
50
25
25
20
8
20
20
25 %
25 %
b
50 %
50 %
b
50 %
25 %
b
50 %
50 %
b
50 %
50 %
b
50 %
50 %
b
A
3
8 500
1 500
A
3
8 500
1 500
A
3
8 500
1 500
A
3
10 000
5 000
A
3
10 000
5 000
A
3
10 000
5 000
10
10 (2)
25
10
18
18 (2)
100
18 (3)
25
15
fixed
fixed
fixed
fixed
fixed
fixed
fixed
fixed
fixed
fixed
fixed
10 In
fixed
10 In
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b (3)
b (3)
b
b
b
b
b
b
b (3)
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
60 x 130
75
60 x 130
75
60 x 130
25
60 x 130
75 (3P)
100 (4P)
60 x 130
25
0.78
0.78
0.28
0.78 (3P)
1.0 (4P)
0.28
60 x 130
50 (2P)
75 (3P)
100 (4P)
0.6 (2P)
0.78 (3P)
1.0 (4P)
b
b
EZC100H
b
b (4)
3-4
15, 16, 20, 25,
30, 32, 40, 45,
50, 60, 63, 75,
80, 100
690
6
550
250
1
15, 16, 20, 25,
30, 32, 40, 45,
50, 60, 63, 75,
80, 100
690
6
415
125
b (4)
2-3-4
15, 16, 20, 25,
30, 32, 40, 45,
50, 60, 63, 75,
80, 100
690
6
550
250
25
18
2.5
2.5
5
-
25
25
18
15
10
5
5
5
50
25
5
5
10
-
50 %
50 %
b
50 %
50 %
b
50 %
50 %
b
A
3
8 500
1 500
A
3
8 500
1 500
A
3
8 500
1 500
fixed
fixed
3
15, 16, 20, 25,
30, 32, 40, 45,
50, 60
b
b
b
b
b
b
b
b
b
b
b
50
18
b
b
85
85
36
36
25
10
30
30
85
25 (3)
fixed
10 In
60 x 165
105
60 x 165
105
60 x 165
105
1.3
1.3
1.1 (2P)
1.3 (3P)
A-7
Functions
and characteristics
CPB100605
In
at 40 C
AC 50/60 Hz
DC
Icu
Ics
AC 50/60 Hz 220/230 V
380 V
400/415 V
440 V
550 V
DC
125 V (1P)
250 V
(2P in series)
% Icu
Mechanical
Electrical
In/415 V
CPB100606
EZC250-4P.
HIC
Protection
CPB100607
Overload protection
Instantaneous protection
Bimetal
Magnetic
Earth-leakage protection
Sensitivity (A)
Time-delay (ms)
Max. breaking time (s)
Voltage releases
Connection
Accessories
A-8
adjustable
adjustable
OF/AX
SD/AL
AXAL
ALV
MX/SHT
MN/UVR
Extended
Terminal extensions
Spreaders
Phase barriers
Terminal shields
Padlocking system
fixed ( 20 %)
Auxiliary switch
Alarm switch
Combined AX + AL
Earth-alarm switch
Shunt trip release
Undervoltage release
Installation
EZC400-3P.
In
t
at 2 In
Auxiliaries
Indication contacts
AC 50/60 Hz 240 V
277/480 V
Dimensions (mm)
DxH
W
Weight (kg)
EZC250N
EZC250H
EZCV250N EZCV250H
b
b
b
b
b
b
b
b
4
63, 80, 100, 125,
150, 160, 175,
200, 225, 250
690
6
550
250
4
63, 80, 100, 125,
150, 160, 175,
200, 225, 250
690
6
550
250
3-4
63, 80, 100, 125,
150, 160, 175,
200, 225, 250
440
6
440
3-4
63, 80, 100, 125,
150, 160, 175, 200,
225, 250
440
6
440
-
50
25
25
20
8
20
20
85
36
36
25
10
30
30
85
25
25
20
-
50 %
50 %
50 %
EZC400N
EZC400H
EZC630N
3-4
320, 350, 400
3-4
320, 350, 400
3-4
400, 500, 600
3-4
400, 500, 600
690
6
440
250
690
6
440
250
690
6
440
250
690
6
440
250
100
36
36
25
-
40
36
36
36
-
70
50
50
50
-
40
36
36
36
-
70
50
50
50
-
50 %
50 %
50 %
100% (220-415V)
50% (440V)
b
A
3
10 000
3 000
100% (220-415V)
50% (440V)
b
A
3
10 000
5 000
A
3
10 000
5 000
A
3
10 000
5 000
A
3
10 000
5 000
A
3
10 000
4 000
A
3
10 000
4 000
A
3
10 000
3 000
50
18
85
25
50
85
-
50
25
85
35
50
25
fixed
10 In
fixed
10 In
fixed
10 In
fixed
10 In
fixed
10 In
fixed
10 In
b
b
b
b
b
b
b
b
b
b
0.1/0.3/0.5/1
0/200/500/1000
0.15/0.4/1/2
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
68 x 165
140
68 x 165
140
1.8
1.8
68 x 165
105 (3P)
140 (4P)
1.6 (3P)
2.1 (4P)
EZC630H
0.1/0.3/0.5/1
0/200/500/1000
0.15/0.4/1/2
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
68 x 165
105 (3P)
140 (4P)
1.6 (3P)
2.1 (4P)
fixed
10 In (400/500A)
5000A (600A)
fixed
10 In (400/500A)
5000A (600A)
b
b
85
35
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
140 x 255
140 (3P)
185 (4P)
4.8 (3P)
6.4 (4P)
140 x 255
140 (3P)
185 (4P)
4.8 (3P)
6.4 (4P)
140 x 255
140 (3P)
185 (4P)
4.8 (3P)
6.4 (4P)
140 x 255
140 (3P)
185 (4P)
4.8 (3P)
6.4 (4P)
A-9
Functions
and characteristics
EasyPact EZC100
PB104909
EasyPact EZC circuit breaker EZC100 comes with a full range of accessories to
fulfill different application requirements and make it easy for the end-user.
Phase
barriers
Terminal shield
Short terminal
shield
Din rail
adaptor
Sealing screws
Cable lugs
> 50 A
Spreaders
Cable lugs
> 50 A
Plug-in
connectors
Short terminal
shield
Padlocking system
Fishbone
connectors
Cable lugs
> 50 A
Spreaders
Cable lugs
> 50 A
A-10
Terminal shield
Sealing screws
EasyPact EZC250
PB106410_176
EasyPact EZC circuit breaker EZC250 comes with a full range of accessories to
fulfill different application requirements and make it easy for the end-user.
Short terminal
shield
Phase
barriers
Terminal shield
Plug-in
connectors
Terminal
extensions
Spreaders
Cable lugs
Plug-in
Short terminal
shield
TM
EasyPact
Padlocking
system
Terminal
extensions
Extended rotary handles
Terminal shield
Phase
barriers
A-11
Functions
and characteristics
EasyPact EZCV250
PB106411_176
EasyPact EZC circuit breaker EZCV250 comes with a full range of accessories to
fulfill different application requirements and make it easy for the end-user.
Short terminal
shield
Phase
barriers
Terminal shield
Plug-in
connectors
Spreaders
Terminal
extensions
Cable lugs
Plug-in
Plug-in
connectors
Earth-leakage
alarm switch (ALV)
Short terminal
shield
Auxiliary
switch (AX)
Alarm
switch (AL)
Auxiliary/
Alarm switch
(AX + AL)
Shunt trip
(SHT)
Under
voltage
release
(UVR)
Padlocking
system
Direct rotary handles
Cable lugs
Spreaders
Terminal
extensions
Extended rotary handles
Terminal shield
Phase
barriers
A-12
EasyPact EZC400-630
DB400001_1
EasyPact EZC circuit breaker EZC400-630 comes with a full range of accessories to
fulfill different application requirements and make it easy for the end-user.
Insulation accessories
Connection
Cable connectors
Interphase barriers
Sealable terminal
shields
Rear connectors
Terminal
extensions
Cable connectors
Electrical auxiliaries
Indication contact
Voltage release
Control accessories
A-13
Electrical auxiliaries
100-250AF
Functions
and characteristics
AX - AL - AXAL - ALV
CPB100612
DB116832
EZC100
EZC100-2P. EZC100-3P.
EZC100-4P.
DB116834
EZC250
CDB500603
EZC100.
EZC250-3P. EZC250-4P.
DB116835
EZCV250
AL or
AX or
AXAL
AL or
AX or
AXAL
EZCV250-3P. EZCV250-4P.
Indication contacts
CDB500604
AL or
AX or
AXAL
Characteristics
CDB500605
Contacts
AL or
AX or
AXAL
AL or
AX or
AXAL
AL or
AX or
AXAL
A-14
5
10 mA at 24 V
AC12
AC15
5
5
5
5
5
3
3
2
DC12
4
2.5
0.4
0.2
Connections
Connection wire length
Cross-section
450 mm
EZC100: 1 mm2,
EZC250/EZCV250: 1.5 mm2
DC14
3
1
0.4
0.2
DB116386
PB101876-21
PB101862-21
PB101893-28
A-15
Electrical auxiliaries
100-250AF
Functions
and characteristics
CPB100616
DB116836
EZC100
EZC100-2P.
EZC100-3P.
EZC100-4P.
DB116838
EZC250
CDB500606
EZC250.
EZC250-3P.
EZC250-4P.
SHT or
UVR
DB116839
EZCV250
SHT or
UVR
EZCV250-3P.
EZCV250-4P.
Remote tripping
CDB500608
UVR
Characteristics
SHT or
UVRN
Mechanical
Mechanical endurance
Electrical
SHT
UVR
UVRN
UVRN release on EZCV250.
Connections
SHT
UVR
UVRN
A-16
pick-up consumption
response time
seal-in consumption
response time
seal-in consumption
response time
EZC100
EZC250/EZCV250
AC/DC
< 30 VA
< 50 ms
< 5 VA
< 50 ms
< 5 VA
< 50 ms
AC
< 30 VA
< 50 ms
< 5 VA
< 50 ms
< 5 VA
< 50 ms
DC
< 35 W
< 100 ms
< 10 W
< 100 ms
< 10 W
< 100 ms
EZC100
EZC250/EZCV250
pre-wired (1 mm2)
pre-wired (1 mm2)
pre-wired (1 mm2)
PB101879-18
PB101865-16
Installation
b EZC100 SHT and UVR: internal mounting
b EZC250/EZCV250:
v SHT: internal mounting
v UVR: external mounting
v UVRN: internal mounting
PB101894-27
PB101866-18
PB101880-15
A-17
Functions
and characteristics
PB101867-31
PB102159-30
DB116387
IP40 or IP54
DB116388
PB101881-33
EZC100.
EZC100.
Designation
Direct rotary handle (red/yellow) for EZC250/EZCV250.
Direct rotary handle (black)
Direct rotary handle (red/yellow)
A-18
DB116390
DB116389
PB102157-33
Padlocking
EZC250/EZCV250.
Cat. no.
EZC100
EZAROTDS
EZAROTDSRY
EZC250/EZCV250
EZEROTDS
EZEROTDSRY
PB101868-46
PB102158-46
DB116391
IP40 or IP54
PB101882-42
DB116392
EZC100.
EZC250/EZCV250.
EZC100.
Extended rotary handle (red/yellow) for EZC250/EZCV250.
Designation
Extended rotary handle (black)
Extended rotary handle (red/yellow)
DB116390
DB116389
PB102156-42
Padlocking
EZC250/EZCV250.
Cat. no.
EZC100
EZAROTE
EZAROTERY
EZC250/EZCV250
EZEROTE
EZEROTERY
A-19
Plug-in
Plug-in
100 A
DB127457
DB127456
The plug-in base is equipped with terminals which, depending on their orientation,
serve for front and rear connection. Degree of protection IP20.
DB127455
CPB100620
Functions
and characteristics
BFN
BF
EZC
NH
EZC
100
100
BFN
EZC
Front connection.
100
DB127458
Connection accessories
All accessories for fixed devices (bars, lugs) may be used with the plug-in base.
y7
y8.5
y9
y17
y17
Tightening torque
y7
y9
EZAPLUG3L
EZAPLUG3H
EZAFSHB3 - set of 3
EZAPCON1L
-y17
set of 2
y17
EZAPCON1H
y8.5
100 A
EZAPCON1H
PB106397-27
EZAPCON1L
PB106398-33
PB106398-30
ReferencesPlug-in
EZAFSHB3
CPB100609
Fishbone
The fishbone, designed for vertical installation, saves space and reduces
cabling time.
Fishbone.
A-20
Terminal shields
CPB100621
Insulating accessories used for protection against direct contact with power circuits.
They provide IP40 degree of protection and IK07 mechanical impact protection.
Terminal-shield types
Easypact EZC 100 to 250:
b short terminal shields
Short terminal shields
They are used with:
b plug-in in all connection configurations
b fixed versions with rear connection.
DB127460
DB111356
Pitch (mm)
100/160/250
35
Interphase barriers
A-21
Functions
and characteristics
Plug-in
Plug-in
250 A
Front connection.
DB127463
DB127462
DB127461
The plug-in base is equipped with terminals which, depending on their orientation,
serve for front and rear connection. Degree of protection IP20.
DB127464-1
Connection accessories
All accessories for fixed devices (bars, lugs).
DB127464-4
LV429241
y6
y10
= =
= =
y25
y25
PB106402-43
Tightening torque
References Plug-in
EZEPCON1
A-22
EZEPLUG3L - 60 mm breaker
EZEPLUG3H - 68 mm breaker
EZEPLUG4 - 68 mm breaker
EZEPCON1 - set of 2
250 A
Kit, plug-in base 3P 100 A - 250 A
Kit, plug-in base 3P 100 A - 250 A
Kit, plug-in base 4P 100 A - 250 A
Kit, plug-in connectors 100 A - 250 A
Terminal shields
CPB100622
Insulating accessories used for protection against direct contact with power circuits.
They provide IP40 degree of protection and IK07 mechanical impact protection.
Terminal-shield types
Easypact EZC 100 to 250:
b short terminal shields.
Short terminal shields
They are used with:
b plug-in in all connection configurations
b fixed versions with rear connection.
Terminal shields and pitch
Combination possibilities are shown below.
Circuit breaker Easypact
100/160/250
35
Pitch (mm)
DB111356
Interphase barriers
Interphase barriers.
DB127466
W x H x thickness (mm)
W x H x thickness (mm)
140 x 105 x 1
175 x 105 x 1
A-23
Functions
and characteristics
DB116395
EZC100 60 to 100 A
Screw M8
EZC250/EZCV250 63 to 250 A
Screw M8
DB112345
E88222
E88221
All EasyPact EZC circuit breakers are supplied with terminal screws
EZC100 15 to 50 A
DB116396
DB112346
Bars
(mm)
Crimp lugs
y 50 A
> 50 A
L (mm)
d (mm)
(mm)
Tightening torque
y 50 A
> 50 A
y 50 A
> 50 A
y 17
d + 10
y7
y6
5.5
8.5
EZC250/
EZCV250
y 25
d + 10
y8
y6
9
y 17
y9
5.5
8.5
2 N.m
5.5 N.m
y 25
y8
9
13 N.m
DB116397
Cable lugs
Cable lugs directly screwed on standard circuit breaker terminals.
u 100 A (EZC250/EZCV250)
DB115938
> 50 A (EZC100)
E88189
E88190
y 50 A (EZC100)
Designation
Cable lug up to 50 A (set of 2)
Cable lug up to 50 A (set of 3)
Cable lug from 60 A up to 100 A (set of 2)
Cable lug from 60 A up to 100 A (set of 3)
Cable lug from 100 A up to 250 A (set of 3)
Cable lug from 100 A up to 250 A (set of 4)
Cat. no.
EZC100
EZALUG0502 (1)
EZALUG0503 (1)
EZALUG1002 (2)
EZALUG1003 (2)
-
EZC250/EZCV250
EZELUG2503
EZELUG2504
Important:
(1) EZALUG0502 and EZALUG0503 can be use with maximum rating of 50 A.
(2) EZALUG1002 and EZALUG1003 can be use with maximum rating of 100 A.
A-24
Spreaders
Spreader.
Terminal extensions
DB116399
PB101873-25
DB116398
Terminal extensions.
Designation
Cat. no.
PB101861-23
EZC100
EZASPDR3P
EZASPDR4P
-
EZC250/EZCV250
EZESPDR3P
EZESPDR4P
EZETEX
EZETEX4P
Phase barriers
PB101875-15
DB116401
DB116400
Designation
Phase barriers for EZC250/
EZCV250.
EZC100
EZAFASB2
-
EZC250/EZCV250
EZEFASB2
EZEFASB3N
Terminal shields
PB101874-25
PB104906
Cat. no.
DB402709
b Insulating accessory used for protection against direct contacts with power circuit
connections. It provides a degree of protection of IP20 and a mechanical resistance
of IK07.
b The long terminal shield is used with front cable or isolated busbar connections.
b Designed for 3-pole EZC100, 3, 4-pole EZC250/EZCV250.
Terminal shield
for EZC250/EZCV250.
Designation
Terminal shield 3P, 60 mm depth (set of 2)
Terminal shield 3P, 68 mm depth (set of 2)
Terminal shield 4P, 60 mm depth (set of 2)
Terminal shield 4P, 68 mm depth (set of 2)
Cat. no.
EZC100
EZATSHD3P
EZATSHD4P
-
EZC250/EZCV250
EZETSHD3P
EZETSHD3PN
EZETSHD4PN
A-25
Functions
and characteristics
PB101870-10
PB101917-15
DB116403
Breaker mounting on a DIN rail is possible by using special adaptator (EZC100 only).
Number of adaptators:
b one for two 1P, or one 2P or one 3P
b two for one 4P.
Designation
Cat. no.
EZC100
EZADINR
EZC250/EZCV250
-
Padlocking system
DB116405
DB116404
PB101920-20
PB101869-22
Designation
Padlocking system
Padlocking system for EZC250-3P
Padlocking system for EZC250-4P and
EZCV250-3/4P
A-26
for EZC250/EZCV250
Cat. no.
EZC100
EZALOCK
-
EZC250/EZCV250
EZELOCK
EZELOCKN
DB116406
PB101860-30
Sealing screws
Designation
Sealing screws (set of 2)
Cat. no.
EZC100
EZASSCR
EZC250/EZCV250
-
A-27
Functions
and characteristics
Connection of devices
CDB500620
DB112169
Front connection
Bars or cables with lugs
Standard terminals
EasyPact EZC400 to 630 come with terminals comprising snap-in nuts with screws:
b EasyPact EZC400/630: M10 nuts and screws.
These terminals may be used for:
b direct connection of insulated bars or cables with lugs
b terminal extensions.
Interphase barriers or terminal shields are recommended. They are mandatory for
certain connection accessories (in which case the interphase barriers are provided).
Bars
When the switchboard configuration has not been tested, insulated bars are mandatory.
Maximum size of bars
Insulated bar.
DB112170
Without spreaders
With spreaders
DB112171
Straight terminal
extensions.
Right-angle
terminal extensions
400/630
45
32 x 8
52.5
40 x 6
Crimp lugs
There are two modules of lugs, for aluminium and copper cables.
Interphase barriers or long terminal shields must be used with narrow lugs. The lugs
are supplied with interphase barriers.
EasyPact EZC circuit breaker
Copper cables
size (mm)
crimping
Aluminium cables
size (mm)
crimping
400/630
240, 300
hexagonal barrels or punching
240, 300
hexagonal barrels
Terminal extensions
Extensions with anti-rotation ribs can be attached to the standard terminals to provide
numerous connection possibilities in little space:
b straight terminal extensions
b right-angle terminal extensions
DB112177
DB112173
DB112172
pitch (mm)
maximum bar size (mm)
pitch (mm)
maximum bar size (mm)
Spreaders.
Spreaders
Spreaders may be used to increase the pitch:
b EZC400/630: the 45 mm pitch can be increased to 52 or 70 mm.
Bars, cable lugs or cable connectors can be attached to the ends.
Pitch (mm) depending on the type of spreader
EasyPact EZC circuit breaker
Without spreaders
With spreaders
A-28
EZC400 to 630
45
52.5 or 70
DB112314
CDB500621
Connection of devices
Bare-cable connectors may be used for both copper and aluminium cables.
1-cable connectors for EasyPact EZC400 to 630
The connectors are screwed directly to the device terminals.
Bare cable.
630
35 to 300 mm
Four positions.
2-cable
connector for
EZC400/630.
DB111330
1-cable
connector for
EZC400/630.
CDB500622
400
2 cables 35 to 240 mm
DB111326
DB112316
Aluminium connectors
Two lengths.
Rear connection
Rear connections for bars or cables with lugs are available in two lengths. Bars may
be positioned flat, on edge or at 45 angles depending on how the rear connections
are positioned.
The rear connections are simply fitted to the device connection terminals. All
combinations of rear connection lengths and positions are possible on a given
device.
A-29
Functions
and characteristics
DB400184-00
Rotary handle
OF1
OF2
OF3
Reserved
MN /
MX
Standard
SD
SDE
All EasyPact EZC400/630 circuit breakers and switch-disconnectors have slots for the
electrical auxiliaries listed below.
5 indication contacts
b 3 ON/OFF (OF3)
b 1 trip indication (SD)
b 1 fault-trip indication (SDE)
1 remote-tripping release
b either 1 MN undervoltage release
b or 1 MX shunt release.
All these auxiliaries can be installed with a rotary handle.
A-30
DB125549
Functions
Indication contacts.
Installation
b OF, SD, SDE functions: a single type of contact provides all these different indication
functions, depending on where it is inserted in the device. The contacts clip into slots
behind the front cover of the circuit breaker.
Standard
Types of contacts
All
Minimum load
100 mA at 24 V DC
1 mA at 4 V DC
Operational24 V
current (A)
48 V
110 V
Low level
AC/DC 6
AC/DC 6
2.5
0.2
2.5
0.2
AC/DC 6
0.6
0.05
2.5
0.6
0.05
220/240 V AC
250 V
DC
0.3
0.03
0.3
0.03
380/440 V AC
1.5
A-31
Functions
and characteristics
DB125550
MN undervoltage release
b This release trips the circuit breaker when the control voltage drops below a tripping
threshold
b The tripping threshold is between 0.35 and 0.7 times the rated voltage
b Circuit breaker closing is possible only if the voltage exceeds 0.85 times the rated
voltage.
Characteristics
DB115605
MX or MN voltage release.
V AC
Operating threshold
V DC
Opening
Closing
0.35
0.7
1.1 Un
Power supply
Failsafe closing
0
0.85
1.1 Un
PB103752-32
DB115607
Delayed
trip order
10
12
Time-delay
unit
Instantaneous
trip order
Corresponding MN release
48 V DC
250 V DC
48 V DC
125 V DC
250 V DC
MX shunt release
The MX release opens the circuit breaker via an impulse-type (u 20 ms) or maintained
order.
D2
Opening conditions
When the MX release is supplied, it automatically opens the circuit breaker. Opening
is ensured for a voltage U u 0.7 x Un.
MN
Characteristics
D1
MN release with a time-delay
unit.
Operating range
Consumption (VA or W)
Response time (ms)
Power supply
Wiring
diagram
for
emergency-off function with
MN + time-delay unit.
V AC
V DC
Operating range
Consumption (VA or W)
Response time (ms)
DB115608
Failsafe opening
0
0.7
Opening conditions of the MX release.
1.1
Un
A-32
When the circuit breaker has been tripped by an MN or MX release, it must be reset
before it can be reclosed.
MN or MX tripping takes priority over manual closing.
In the presence of a standing trip order, closing of the contacts, even temporary, is not
possible.
Connection using wires up to 1.5mm2 to integrated terminal blocks.
CPB100628
CPB100629
CPB100630
An additional accessory interlocks two devices with rotary handles to create a sourcechangeover system. Closing of one device is possible only if the second is open.
This function is compatible with direct or extended rotary handles.
Up to three padlocks can be used to lock in the OFF or ON position.
A-33
Functions
and characteristics
DB400026
DB400025
Locking in the OFF position guarantees isolation as per IEC 60947-2. Padlocking
systems can receive up to three padlocks with shackle diameters ranging from 5 to
8 mm (padlocks not supplied). Certain locking systems require an additional accessory.
Control device
Function
Toggle
Direct
handle
rotaryStandard Lock in
OFF position
OFF or ON position (1)
DB400027
Removable device
CDB500624
CDB500623
Sealing accessories
DB115033
CDB500625
Toggle control
Rotary handle
CDB500626
Sealing accessories.
A-34
Padlock Lock in
OFF position
(1)
OFF or ON position
with
door
opening
prevented (2)
Padlock -
EasyPact EZC
Busbars
Presentation
Functions and characteristics
II
A-1
Introduction B-2
Busbars characteristics
B-4
B-5
Accessories B-6
Dimensions
Busbar EZB250
Busbars EZB400/630
EasyPact EZC or Compact NSX branch extensions layout
B-7
B-8
B-9
Installation guide
Catalogue numbers
C-1
D-1
B-1
DB116419.eps
Busbars
B-2
Introduction
CPB100623
B-3
Busbars characteristics
Busbars
The EasyPact EZC Busbar System is designed and certified to meet all international
requirements specified in IEC 60439-1 relating to construction of Low Voltage
switchgear and controlgear assemblies, including:
b verification of temperature - rise limits
b verification of dielectric properties
b verification of short-circuit withstand strength
b verification of clearances and creepage distances.
In addition, the system has been type-tested in ASTA labs to confirm the short-circuit
and short-time withstand ratings.
EZB250
1P
2P
3P
4
6
8
12
18
24
6
8
12
4
6
8
No extension
EZB400
10
30
14
10
12
36
18
12
4
6
8
12
18
24
6
8
12
4
6
8
Yes (2 or 4 Ways)
EZB630
10
30
14
10
12
36
18
12
4
6
8
12
18
24
6
8
12
4
6
8
Yes (2 or 4 Ways)
250
400
550
550
690
690
Refer to cascading tablespage C-18
30
40
630
550
690
Dimensions H x W x D (mm)
B-4
4 Ways
6 Ways
8 Ways
10 Ways
12 Ways
40
10
30
14
10
12
36
18
12
EZ149P-60.eps
Main busbar
The core of the EasyPact EZC Busbar System includes the main busbars and
outgoing connectors for EasyPact EZC MCCBs.
Cat. no.
EZB 400
400 A
EZB630
630 A
EZB250W04
EZB250W06
EZB250W08
EZB250W10
EZB250W12
EZB400W04
EZB400W06
EZB400W08
EZB400W10
EZB400W12
EZB630W04
EZB630W06
EZB630W08
EZB630W10
EZB630W12
DB116421.eps
DB116420.eps
EZB250
250 A
DB116422.eps
Type
Main busbar current rating
Number of ways
4 ways
6 ways
8 ways
10 ways
12 ways
E88637-60_SE
DB116426.eps
DB116425.eps
DB116424.eps
DB116423.eps
Designation
For applications calling for larger than 100 A outgoing MCCBs, EasyPact EZC
Busbar rated 400 A and 630 A can accept the 2 ways or 4 ways EasyPact EZC and
Compact NSX branch extension for up to four additional 250 A max. outgoing circuits.
EasyPact EZC and Compact NSX branch extensions simply connect directly to the
terminals provided on the EZB400 and EZB630 EasyPact EZC Busbar.
Designation
Cat. no.
EZBNS2
EZBNS4
B-5
Accessories
Busbars
E88301-50.eps
EZ117P-60_SE
DB116427.eps
Incoming cables with crimped lugs can connect directly to the terminals provided.
Main connectors
For installing a main disconnect device (EasyPact EZC or Compact NSX MCCB or
INS switch) ahead of EasyPact EZC Busbar, use the tin-plated copper connector kits
below.
Designation
Cat. no.
400 A
EZB400MCNS
630 A
EZB630MCNS
Mechanical lugs
CDB500620_00
For incoming cables without crimped lugs, use the mechanical lug kits below. Each
kit contains three aluminium lugs suitable for copper or aluminium cables.
Designation
Cat. no.
250 A
16-150 mm2
400 A
35-300mm2
Lug kit
EZB250MLUG
EZB400MLUG
DB116428.eps
Connector caps
E88310-54_SE
630 A
25-240 mm2
2 cables per phase
EZB630MLUG
DB116429.eps
Connector caps are available to isolate the ends of connectors in positions where
branch breakers are not installed.
Mounting screws are provided for an insulating barrier (locally provided) to cover the
branch connectors when IP2X finger safety is specified.
Designation
DB116430.eps
B-6
Cat. no.
EZB100CAP
EZB250CAP
Dimensions
Busbar EZB250
DB116432.eps
DB116431.eps
Panel layout using the EasyPact EZC Busbar is simple using the guides below. In
addition to the mounting locations for the busbar and main disconnect components
(if required), make note of the minimum clearances required to the top, bottom and
sides of the enclosure.
DB116433.eps
Trim cut-out
EZ250
incomer
NS incomer
4 ways
6 ways
8 ways
10 ways
12 ways
187.4
52
92.7
24
109.5
126
268.5
343.5
418.5
493.5
568.5
225
300
375
450
525
147
222
297
372
447
182.4
-
76
-
90.2
-
29
-
108
-
125
-
B-7
Dimensions
Busbars
Busbars EZB400/630
DB116435.eps
DB116434.eps
Trim cut-out
4 ways
6 ways
8 ways
10 ways
12 ways
290
365
440
515
590
225
300
375
450
525
147
222
297
372
447
Note: to avoid excess temperature rise on incoming MCCB terminals, panels using 630 A main
breaker with these minimum enclosure dimensions require a 7000 mm2 ventilation opening (after
subtracting effects of screening) at each of the 4 corners of the enclosure.
B-8
Dimensions
DB116437.eps
DB116438.eps
EZBNS2
EZBNS4
EZC250
NSX250
270
384
-
175
275
-
NA
85.5
90.5
85.5
57.5
78.5
24
29
61
45.5
52
76
249
232
DB116439.eps
Trim cut-out
DB106569
B-9
B-10
EasyPact EZC
Installation guide
Presentation
Functions and characteristics
Busbars
Dimensions
II
A-1
B-1
C-2
C-4
C-6
C-8
C-10
C-12
C-13
C-14
C-15
Temperature derating
C-17
Tripping curves
C-18
Current-limiting curves
C-20
Cascading C-21
Cascading tables
C-22
Motor protection
C-24
Capacitor protection
C-26
Catalogue numbers
D-1
C-1
Dimensions
Installation guide
Dimensions
4P
DB125751
3P
DB125750
2P
Y
Y
DB125749
DB116443
DB125748
1P
Mounting on plate
2P
DB116449
DB116448
1P
or
4P
DB116451
DB116450
3P
YY
xX
or
xX
C-2
DB116453
DB116452
DB116454
xX
xX
DB116458
4P
DB116457
DB116457
2P
Y
Y
YY
DB116455
1P, 3P
DB116461
DB116460
YY
DB116459
1P
xX
xX
xX
YY
xX
4P
DB116463
DB116462
3P
YY
X
x
C-3
Dimensions
Installation guide
Mounting
DB127537
DB127541
25
12.5
BF
NH
00
1
EZC
X
83.5
5
78
DB127540
DB127542
On rail
25
12.5
BFN
EZC
100
26
y32
C-4
X 52
167
160
DB127539
DB127538
DB127536
Dimensions
Y
DB127544
DB127543
On backplate
25
12.5
BFN
EZC
100
140
70
3.65
or M4
DB127546
DB127545
Dimensions - combination
6.4
239
61
365.8
20
61
6.4
C-5
Dimensions
Installation guide
DB116466
??
52.5
35
35
50
4P
YY
DB116465
DB116464
2P, 3P
YY
144
X
102
19.5
25
22
100
105
44
Dimensions (EZCV250)
Mounting on plate
4P
DB116472
DB116471
2P, 3P
X
x
C-6
Y
Y
xX
3P, 4P ELCB
YY
DB116469
DB116468
DB116467
4P
YY
DB116470
3P
Y
Y
4P
Y
Y
DB116475
DB116473
DB116474
YY
xX
xX
4P
YY
DB116478
DB116476
DB116477
YY
X
x
X
x
X
x
Dimensions (mm)
EZC 2/3P
EZC 4P
EZCV 3P
EZCV 4P
A
60
68
B
65
73
C
85.5
95
D
45.5
80.5
E
67
75
F
61
69
C-7
Dimensions
Installation guide
Dimensions
DB127587
DB127586
??
52.5
35
35
DB127550
YY
50
X
102
19.5
25
22
100
105
44
Mounting
DB127557
DB127556
DB127554
3P
35
17.5
70
178
194
89
97
54.5
144
109
On rail
4P
70
y32
35
C-8
DB127559
DB127558
DB127555
3P
105
35
75
37.5
On backplate
DB127581
DB127560
3P
4P
70
35
17.5
17.5
159
79.5
C-9
Dimensions
Installation guide
Dimensions
CDB500629
4P
CDB500628
CDB500627
3P
A
A1
B
C1
C2
Z
B2
B1
C3
Mounting on plate
3P
4P
F1
F1
CDB500631
CDB500630
On backplate
F2
F1
F1
F1 F1
F2
F3
4 6
A
127.5
C-10
A1
255
B
70
B1
140
B2
185
F1
45
F2
22.5
F3
90
4 6
CDB500632
For toggle
116
41.5
Y
31.5
112
63
CDB500635
CDB500634
184
92.5
107
Z
71.5
143(3P)
188(4P)
Y
C-11
Dimensions
Installation guide
3P
4P
Y
Y
DB116492
YY
DB116491
DB116490
Terminal shields
xX
xX
3P
YY
xX
4P
YY
YY
DB116496
DB116494
DB116493
2P
DB116495
Phase barriers
xX
X
x
xX
Z
YY
4P
3P, 4P
YY
DB116500
3P
DB116499
DB116498
DB116497
X
x
X
xX
xX
DB116501
xX
C-12
3P, 4P
YY
DB116503
3P, 4P
xX
xX
Dimensions
Phase barriers
3P, 4P
xX
DB116507
YY
DB116505
DB116504
3P, 4P
DB116506
Terminal shields
Xx
X
x
Xx
Z
Z
3P, 4P
Y
Y
4P
YY
DB116511
DB116509
DB116508
3P
DB116510
Xx
xX
Y
Y
3P, 4P
Y
DB116514
DB116513
DB116512
3P, 4P
xX
Xx
Dimensions (mm)
EZC 2/3P
EZC 4P
EZCV 3P/4P
A
58.5
66.5
B
55
63
C
93 to 97
101 to 105
D
145
153
E
137 to 414
145 to 422
C-13
Dimensions
Installation guide
4P
CDB500637
CDB500636
3P
A4
A3
A2
A
A1
A2
A3
A4
C1
C2
B
B2
B1
C3
Y
Y
Long terminal shields also available for EZC400/630 spreaders with 52.5 mm pitch:
B1 = 157.5 mm, B2 = 210 mm).
Interphase barriers.
Short terminal shields.
4P
CDB500641
B10
CDB500640
CDB500639
A15
60
A14
60
O
A18
B8
B8
B9
B9
C7
B
B
C8/C9
B2
B1
Z
CDB500644
CDB500643
CDB500642
60
50
A18
45
A18
75
37.5
10
X
60
2 4.2
36
72
B10
B10
37.5
75
R1
47
A
127.5
A14
40
C-14
A1
255
A2
142.5
A15
123
A3
200
A4
237
A18
24.6
B
70
B1
140
B8
61.5
B2
185
B9
123
C1
95.5
C2
110
B10
5
C3
168
F1
45
C7
145
R1
min. 195
max. 600
F2
22.5
F3
90
C8
179
C9
188
A18
24.6
B10
5
CPB500600
Dimensions (mm)
CPB500601
C-15
Installation guide
E44458
Installation in an enclosure
EasyPact EZC circuit breakers can be installed in a metal enclosure together with other devices
(contactors, motor-protection circuit breakers, LEDs, etc.).
Installation in an enclosure.
C-16
Circuit breakers
EZC100B/F/N
EZC100H
EZC250F/N-EZCV250N
EZC250H-EZCV250H
EZC400N
EZC400H
EZC630N
EZC630H
(1) With front door.
Height (mm)
200
215
270
290
480
500
480
500
Width (mm)
155
155
205
205
240
300
240
300
Temperature derating
Ambient temperature
EasyPact EZC devices are equipped with fixed thermal-magnetic trip units.
b EasyPact EZC has been particularly designed to hold 100 % In at 50 C without
tripping in normal condition (except for earth-leakage circuit breakers).
b EasyPact EZC circuit breakers may be used between -25 C and +70 C.
b EasyPact EZC circuit breakers should be put into service under normal ambient
operating temperature conditions. Exceptionally, the circuit breaker may be put into
service when the ambient temperature is between -35 C and -25 C.
b the permissible storage-temperature range for EasyPact EZC circuit breakers in
the original packing is -35 C to +85 C.
To determine tripping times using time/current curves, use Ir values corresponding to
the thermal setting on the device, corrected as indicated in the tables below.
Rated current 25 C
(A)
EZC100
15
16
20
25
30
32
40
45
50
60
63
75
80
100
EZC250
63
80
100
125
150
160
175
200
225
250
EZCV250
63
80
100
125
150
160
175
200
225
250
EZC400/630
250
320
400
500
600
40 C
45 C
50 C
55 C
60 C
65 C
70 C
17.0
18.1
21.8
26.9
34.5
36.8
42.8
48.8
54.2
64.4
67.6
78.6
84.4
109
15.7
16.7
20.4
25.7
31.4
33.5
40.9
46.9
52.1
61.8
64.9
76.8
82.2
103
15.3
16.3
20.2
25.3
30.7
32.7
40.4
45.9
51.0
60.9
63.9
75.9
81.1
101
15.0
16.0
20.0
25.0
30.0
32.0
40.0
45.0
50.0
60.0
63.0
75.0
80.0
100
14.7
15.7
19.7
24.7
29.4
31.4
39.5
44.4
49.3
59.0
62.0
73.5
78.6
99
14.6
15.6
19.2
24.5
29.1
31.0
38.0
43.3
48.1
57.5
60.4
70.4
77.3
94
14.2
15.1
18.9
24.3
28.5
30.4
37.6
42.6
47.3
56.6
59.4
69.8
76.7
94
13.8
14.7
18.5
24.0
28.0
29.9
37.1
41.9
46.6
55.7
58.5
69.1
76.1
93
77
93
115
148
174
186
207
236
268
297
69
86
106
135
160
171
188
215
244
270
66
83
103
130
155
166
182
208
235
260
63
80
100
125
150
160
175
200
225
250
60
77
96
120
145
154
168
192
215
239
56
74
93
114
139
148
161
184
205
228
53
71
89
109
134
142
153
175
194
215
49
68
85
103
128
136
145
166
182
203
72
89
113
140
163
177
194
223
245
277
63
80
100
125
150
160
175
200
225
250
60
77
95
120
145
154
168
192
218
240
56
73
91
114
141
148
161
183
211
230
53
70
86
108
136
141
154
175
203
220
49
66
80
102
131
135
146
165
196
209
44
62
74
95
125
127
138
155
180
198
39
58
68
88
120
120
126
144
162
180
269
343
429
530
637
250
320
400
500
600
244
312
390
489.6
587
238
303.6
379.3
479
574
231
295
368.5
468
560.6
225
286
357.3
457
547
219
277
345.8
445.4
532.7
213
267.7
334
433.6
518
C-17
Tripping curves
Installation guide
25 A
DB115732
20 A
DB115731
DB115730
15-16 A
10 000
5 000
2 000
1 000
500
1 000
500
200
100
50
200
100
50
200
100
50
20
10
5
20
10
5
20
10
5
t(s)
2
1
t(s)
2
1
2
1
.5
.5
.5
.2
.1
.2
.1
.2
.1
.05
.05
.05
.02
.02
.02
.01
.005
.01
.005
.01
.005
.002
.001
.5 .7 1
3 4 5 .7 10
.002
.001
.5 .7 1
20 30 50 70 100 200300
I / Ir
3 4 5 .7 10
.002
.001
.5 .7 1
20 30 50 70 100 200300
10 000
5 000
2 000
10 000
5 000
2 000
1 000
500
1 000
500
1 000
500
200
100
50
200
100
50
200
100
50
20
10
5
20
10
5
20
10
5
t(s)
2
1
t(s)
2
1
2
1
.5
.5
.5
.2
.1
.2
.1
.2
.1
.05
.05
.05
.02
.02
.02
.01
.005
.01
.005
.01
.005
.002
.001
.5 .7 1
.002
.001
.5 .7 1
3 4 5 .7 10
20 30 50 70 100 200300
3 4 5 .7 10
.002
.001
.5 .7 1
20 30 50 70 100 200300
10 000
5 000
2 000
10 000
5 000
2 000
1 000
500
1 000
500
1 000
500
200
100
50
200
100
50
200
100
50
20
10
5
20
10
5
20
10
5
t(s)
2
1
t(s)
2
1
2
1
.5
.5
.5
.2
.1
.2
.1
.2
.1
.05
.05
.05
.02
.02
.02
.01
.005
.01
.005
.01
.005
.002
.001
.5 .7 1
3 4 5 .7 10
I / Ir
C-18
20 30 50 70 100 200300
.002
.001
.5 .7 1
20 30 50 70 100 200300
80 A
DB115738
DB115737
2 000
3 4 5 .7 10
I / Ir
75 A
10 000
5 000
t(s)
I / Ir
I / Ir
60-63 A
20 30 50 70 100 200300
45-50 A
DB115735
DB115734
2 000
3 4 5 .7 10
I / Ir
40 A
10 000
5 000
t(s)
I / Ir
30-32 A
DB115733
2 000
1 000
500
t(s)
DB115736
10 000
5 000
3 4 5 .7 10
I / Ir
20 30 50 70 100 200300
.002
.001
.5 .7 1
3 4 5 .7 10
I / Ir
20 30 50 70 100 200300
100 A
10 000
5 000
2 000
1 000
500
200
100
50
20
10
5
t(s)
2
1
.5
.2
.1
.05
.02
.01
.005
.002
.001
.5 .7 1
3 4 5 .7 10
20 30 50 70 100 200300
I / Ir
10 000
5 000
2 000
10 000
5 000
2 000
1 000
500
1 000
500
1 000
500
200
100
50
200
100
50
200
100
50
20
10
5
20
10
5
20
10
5
t(s)
t(s)
2
1
t(s)
2
1
2
1
.5
.5
.2
.1
.2
.1
.2
.1
.05
.05
.05
.5
.02
.02
.02
.01
.005
.01
.005
.01
.005
.002
.001
.002
.001
.5 .7 1
3 4 5 .7 10
20 30 50 70 100 200300
.5 .7 1
I / Ir
3 4 5 .7 10
.002
.001
.5 .7 1
20 30 50 70 100 200300
2 000
10 000
5 000
2 000
10 000
5 000
2 000
1 000
1 000
1 000
500
500
500
200
200
200
100
100
100
50
50
50
20
20
20
10
10
t(s)
10
5
t(s)
t(s)
2
.5
.5
.5
.2
.2
.2
.1
.05
.1
.05
.1
.05
.02
.01
t < 10 ms
.005
.002
.001
.5 .7 1
.02
.01
t < 10 ms
.005
3 4 5 7 10
I / Ir
20 30
50 70 100
200 300
20 30 50 70 100 200300
TM600D
CDB500647
TM500D
CDB500646
10 000
5 000
3 4 5 .7 10
I / Ir
320-350-400 A
.02
.01
I / Ir
225-250 A
DB115742
150-160-175-200 A
DB115741
DB115740
63-80-100-125 A
.002
.001
.5 .7 1
t < 10 ms
.005
3 4 5 7 10
I / Ir
20 30
50 70 100
200 300
.002
.001
.5 .7 1
3 4 5 7 10
20 30
50 70 100
200 300
I / Ir
C-19
Current-limiting curves
The exceptional limiting capacity of the EasyPact EZC range greatly reduces the
forces created by fault currents in devices.
The result is a major increase in breaking performance.
DB116528
Installation guide
The Ics value, defined by IEC standard 60947-2, is guaranteed by tests comprising
the following operations:
b break three times consecutively a fault current equal from 25% to 100% of Icu
b check that the device continues to function normally:
v it conducts the rated current without abnormal temperature rises
v protection functions perform within the limits specified by the standard
v suitability for isolation is not impaired.
Cascading is a technique directly derived from current limiting. Circuit breakers with
breaking capacities less than the prospective shortcircuit current may be installed
downstream of a limiting circuit breaker. The breaking capacity is reinforced by the
limiting capacity of the upstream device.
It follows that substantial savings can be made on downstream equipment and
enclosures.
Current-limiting curves
DB115744
3
2
60
50
10
40
5
30
2
As
3
2
20
kA peak
10
5
10
8
7
6
2
10
5
5
4
2
10
20
kA rms
C-20
30
40
60
100
10
20
kA rms
30 40
60
100
Cascading
What is cascading?
Cascading is the use of the current limiting capacity of circuit breakers at a given
point to permit installation of lower-rated and therefore lower-cost circuit breakers
downstream.
The upstream compact circuit breakers acts as a barrier against short-circuit
currents. In this way, downstream circuit breakers with lower breaking capacities
than the prospective short-circuit (at their point of installation) operate under their
normal breaking conditions.
Since the current is limited throughout the circuit controlled by the limiting circuit
breaker, cascading applies to all switchgear downstream. It is not restricted to two
consecutive devices.
DB116529
The use of a protective device possessing a breaking capacity less than the
prospective short-circuit current at its installation point is permitted as long as
another device is installed upstream with at least the necessary breaking capacity.
In this case, the characteristics of the two devices must be coordinated in such a way
that the energy let through by the upstream device is not more than that which can
be withstood by the downstream device and the cables protected by these devices
without damage.
Cascading can only be checked by laboratory tests and the possible combinations
can be specified only by the circuit breaker manufacturer.
Thanks to cascading, circuit breakers with breaking capacities less than the
prospective short-circuit current may be installed downstream from a current limiting
circuit breaker.
It follows that substantial savings can be made on downstream switchgear and
enclosures.
Cascading tables
C-21
Installation guide
Cascading tables
DB127584
Network 220/240 V
Upstream
Upstream
Breaking capacity kA rms
Downstream
EZC100B
10
EZC100F
25
EZC100N
25
EZC100H
100
Upstream
Breaking capacity kA rms
Downstream
EZC100B
10
EZC100F
25
EZC100N
25
EZC100H
100
EZC250F
25
EZC/EZCV250N
50
EZC/EZCV250H
85
EZC100F EZC100N
25
50
85
Enhanced breaking capacity
15
30
30
30
36
-
100
EZC400N EZC400H
NSX400N NSX400H
NSX630N NSX630H
DB127585
Upstream
Breaking capacity kA rms
Downstream
EZC100B
7.5
EZC100F
10
EZC100N
15
EZC100H
30
Upstream
Breaking capacity kA rms
Downstream
EZC100B
7.5
EZC100F
10
EZC100N
15
EZC100H
30
EZC250F
18
EZC/EZCV250N
25
EZC/EZCV250H
36
C-22
NB400
NB630
40
70
85
Enhanced breaking capacity
20
20
20
40
40
50
40
40
50
40
40
50
70
85
100
-
Network 380/415 V
Upstream
EZC100H
25
25
100
Enhanced breaking capacity
25
25
50
25
25
65
65
EZC100F EZC100N
20
50
50
-
85
100
20
50
50
50
85
-
20
50
50
50
85
100
EZC100H
10
15
30
Enhanced breaking capacity
10
15
15
15
15
15
18
25
36
Enhanced breaking capacity
15
15
20
25
36
70
EZC400N EZC400H
NSX400N NSX400H
NSX630N NSX630H
NB400
NB630
36
50
30
Enhanced breaking capacity
20
20
20
36
36
20
20
20
36
36
30
-
15
30
50
70
50
70
20
45
20
36
45
30
50
20
40
50
Network 440 V
Upstream
Breaking capacity kA rms
Downstream
EZC100B
5
EZC100F
7.5
EZC100N
10
EZC100H
20
Upstream
Breaking capacity kA rms
Downstream
EZC100B
5
EZC100F
7.5
EZC100N
10
EZC100H
25
EZC250F
15
EZC/EZCV250N
20
EZC/EZCV250H
25
EZC400N EZC400H
NB400
NB630
36
50
30
Enhanced breaking capacity
15
15
15
30
30
20
20
25
25
30
30
NSX400N NSX400H
NSX630N NSX630H
42
65
15
30
25
30
25
30
30
30
C-23
DB116533
DB116532
Installation guide
Motor protection
A circuit supplying a motor may include one, two, three or four switchgear or
controlgear devices fulfilling one or more functions.
When a number of devices are used, they must be coordinated to ensure
optimum operation of the motor.
Protection of a motor circuit involves a number of parameters that depend on:
b the application (type of machine driven, operating safety, starting frequency, etc.)
b the level of service continuity imposed by the load or the application
b the applicable standards to ensure protection of life and property.
The necessary electrical functions are of very different natures:
b short circuit protection
b overload protection dedicated for motor
b control (generally with high endurance levels)
b isolation.
Protection functions
Disconnection functions:
Isolate a motor circuit prior to maintenance operations.
Short-circuit protection:
Protect the starter and the cables against major overcurrents (> 10 In).
This type of protection is provided by a circuit breaker.
DB116534
Control:
Start and stop the motor and, if applicable:
b gradual acceleration
b speed control.
Overload protection:
Protect the starter and the cables against minor overcurrents (< 10 In).
Thermal relays provide protection against this type of fault. They may be:
b integrated in the short-circuit protective device
b separate.
Additional specific protection:
b limitative fault protection (while the motor is running)
b preventive fault protection (monitoring of motor insulation with motor off).
Overloads (I < 10 In)
An overload may be caused by:
b an electrical problem, for instance on the mains (loss of a phase, voltage outside
tolerances, etc.)
b a mechanical problem, for instance excessive torque due to abnormally high
demands by the process or motor damage (bearing vibrations, etc.).
A further consequence of these two origins is excessively long starting.
Impedance short-circuit (10 < I < 50 In)
Deterioration of motor-winding insulation is the primary cause.
Short-circuit (I > 50 In)
This type of fault is relatively rare. A possible cause may be a connection error during
maintenance.
Protection against insulation faults
This type of protection may be provided by:
b a residual current device (RCD)
b an insulation monitoring device (IMD).
C-24
Motors
P (kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
30
37
45
220/230 V 240 V
I (A)
I (A)
Circuit breakers
Type
Rating
In (A)
380/400 V 415 V
I (A)
I (A)
Circuit breakers
Type
Rating
In (A)
440 V
I (A)
Circuit breakers
Type
Rating
In (A)
2
2.8
3.5
5
6.5
9
12
15
21
28
36
39
52
63
75
100
125
150
EZC100
1.2
1.6
2
2.8
3.7
5.3
7
9
12
16
21
23
30
37
43
59
72
85
EZC100
EZC250
1
1.4
1.7
2.4
3.1
4.5
5.8
8
10.5
13.7
19
20
26.5
33
39
52
63
76
EZC100
EZC250
1.8
2.6
3.2
4.5
6
8
11
14
19
25
33
36
48
59
70
95
115
140
EZC250
20
20
20
20
20
20
20
20
40
60
60
80
80
80
125
160
250
250
1.1
1.5
1.8
2.6
3.4
4.8
6.5
8.2
11
14
19
21
28
34
40
55
66
80
20
20
20
20
20
20
20
20
20
20
40
40
60
60
80
125
150
160
20
20
20
20
20
20
20
20
20
20
40
40
60
60
60
80
125
150
C-25
Capacitor protection
Installation guide
CPB100602
CPB100604
EZC250.
DB115748
EZC100.
Circuit Breaker
Example:
Capacitor
C-26
Reactive power
(kVAR)
7.5
10
15
20
30
40
50
60
75
100
Inc
(A)
11
14
22
29
43
58
72
87
108
144
Inb
(A)
15
20
30
40
60
80
100
118
147
196
EasyPact EZC
Catalogue numbers
Presentation
Functions and characteristics
Busbars
Installation guide
EZC100N/H 1P/2P
Circuit breaker
EZC100B/F/N/H 3P
Circuit breaker
EZC100N/H 4P
Circuit breaker
II
A-1
B-1
C-1
D-2
D-3
D-4
EZC100N/H/B/F
Accessories D-5
EZC250F/N/H 2P/3P
Circuit breaker
EZC250N/H 4P
Circuit breaker
EZCV250N/H 3P/4P
D-7
D-8
D-9
EZC250F/N/H, EZCV250N/H
Accessories D-10
EZC400N/H 3P/4P
Circuit breaker
EZC630N/H 3P/4P
Circuit breaker
D-12
D-13
EZC400/630N/H
Accessories D-14
D-17
D-1
Catalogue numbers
EZC100N/H 1P/2P
Circuit breaker
Rating
15 A
16 A
20 A
25 A
30 A
32 A
40 A
45 A
50 A
60 A
63 A
75 A
80 A
100 A
1P 1t
EZC100N1015
EZC100N1016
EZC100N1020
EZC100N1025
EZC100N1030
EZC100N1032
EZC100N1040
EZC100N1045
EZC100N1050
EZC100N1060
EZC100N1063
EZC100N1075
EZC100N1080
EZC100N1100
Rating
15 A
16 A
20 A
25 A
30 A
32 A
40 A
45 A
50 A
60 A
63 A
75 A
80 A
100 A
1P 1t
EZC100H1015
EZC100H1016
EZC100H1020
EZC100H1025
EZC100H1030
EZC100H1032
EZC100H1040
EZC100H1045
EZC100H1050
EZC100H1060
EZC100H1063
EZC100H1075
EZC100H1080
EZC100H1100
DB116441.eps
1P
2P
D-2
2P 2t
EZC100H2015
EZC100H2016
EZC100H2020
EZC100H2025
EZC100H2030
EZC100H2032
EZC100H2040
EZC100H2045
EZC100H2050
EZC100H2060
EZC100H2063
EZC100H2075
EZC100H2080
EZC100H2100
EZC100B/F/N/H 3P
Circuit breaker
Rating
15 A
16 A
20 A
25 A
30 A
32 A
40 A
45 A
50 A
60 A
3P 3t
EZC100B3015
EZC100B3016
EZC100B3020
EZC100B3025
EZC100B3030
EZC100B3032
EZC100B3040
EZC100B3045
EZC100B3050
EZC100B3060
Rating
15 A
16 A
20 A
25 A
30 A
32 A
40 A
45 A
50 A
60 A
63 A
75 A
80 A
100 A
3P 3t
EZC100F3015
EZC100F3016
EZC100F3020
EZC100F3025
EZC100F3030
EZC100F3032
EZC100F3040
EZC100F3045
EZC100F3050
EZC100F3060
EZC100F3063
EZC100F3075
EZC100F3080
EZC100F3100
Rating
15 A
16 A
20 A
25 A
30 A
32 A
40 A
45 A
50 A
60 A
63 A
75 A
80 A
100 A
3P 3t
EZC100N3015
EZC100N3016
EZC100N3020
EZC100N3025
EZC100N3030
EZC100N3032
EZC100N3040
EZC100N3045
EZC100N3050
EZC100N3060
EZC100N3063
EZC100N3075
EZC100N3080
EZC100N3100
Rating
15 A
16 A
20 A
25 A
30 A
32 A
40 A
45 A
50 A
60 A
63 A
75 A
80 A
100 A
3P 3t
EZC100H3015
EZC100H3016
EZC100H3020
EZC100H3025
EZC100H3030
EZC100H3032
EZC100H3040
EZC100H3045
EZC100H3050
EZC100H3060
EZC100H3063
EZC100H3075
EZC100H3080
EZC100H3100
DB116442.eps
D-3
Catalogue numbers
EZC100N/H 4P
Circuit breaker
Rating
15 A
16 A
20 A
25 A
30 A
32 A
40 A
45 A
50 A
60 A
63 A
75 A
80 A
100 A
4P 3t
EZC100N4015
EZC100N4016
EZC100N4020
EZC100N4025
EZC100N4030
EZC100N4032
EZC100N4040
EZC100N4045
EZC100N4050
EZC100N4060
EZC100N4063
EZC100N4075
EZC100N4080
EZC100N4100
Rating
15 A
16 A
20 A
25 A
30 A
32 A
40 A
45 A
50 A
60 A
63 A
75 A
80 A
100 A
4P 3t
EZC100H4015
EZC100H4016
EZC100H4020
EZC100H4025
EZC100H4030
EZC100H4032
EZC100H4040
EZC100H4045
EZC100H4050
EZC100H4060
EZC100H4063
EZC100H4075
EZC100H4080
EZC100H4100
DB114620.eps
D-4
EZC100N/H/B/F
Accessories
Connection accessories
DB100822.eps
DB100821.eps
Cable lugs
y 50 A
Set of 2
Set of 3
EZALUG0502
EZALUG0503
> 50 A
Set of 2
Set of 3
EZALUG1002
EZALUG1003
Set of 3
Set of 4
EZASPDR3P
EZASPDR4P
Set of 2
Set of 2
EZATSHD3P
EZATSHD4P
Sealing screws
Set of 2
EZASSCR
Phase barriers
Set of 2
EZAFASB2
DB111674.eps
Spreaders
DB100824.eps
Terminal shields
DB100825.eps
Sealing screws
DB100826.eps
Phase barriers
Electrical auxiliaries
DB111669.eps
DB111663.eps
DB111662.eps
Indication contacts
EZAUX10
EZAUX01
EZAUX11
D-5
EZC100N/H/B/F (cont.)
Catalogue numbers
Accessories (cont.)
Voltage releases
AC
DC
Voltage
100-130 V
200-277 V
380-480 V
24 V
48 V
MX/SHT
EZASHT100AC
EZASHT200AC
EZASHT380AC
EZASHT024DC
EZASHT048DC
Voltage
110-130 V
200-240 V
277 V
380-415 V
440-480 V
24 V
48 V
MN/UVR
EZAUVR110AC
EZAUVR200AC
EZAUVR277AC
EZAUVR380AC
EZAUVR440AC
EZAUVR024DC
EZAUVR048DC
125 V
EZAUVR125DC
Db100831.eps
AC
DC
Rotary handles
EZAROTDS
EZAROTDSRY
Db100833.eps
EZAROTE
EZAROTERY
Padlocking system
EZALOCK
Locks
Db100834.eps
Padlocking system
Installation accessory
Db100835.eps
For 2 x 1P or 1 x 2P or 1 x 3P breaker
Note: for 4P breaker, use 2 adaptors
EZADINR
EZAPLUG3L
EZAPLUG3H
EZAFSHB3
EZAPCON1L
EZAPCON1H
Plug-in
DB127582.eps
Plug-in 100 A
D-6
EZC250F/N/H 2P/3P
Circuit breaker
Rating
100 A
125 A
150 A
160 A
175 A
200 A
225 A
250 A
3P 3t
EZC250F3100
EZC250F3125
EZC250F3150
EZC250F3160
EZC250F3175
EZC250F3200
EZC250F3225
EZC250F3250
Rating
100 A
125 A
150 A
160 A
175 A
200 A
225 A
250 A
3P 3t
EZC250N3100
EZC250N3125
EZC250N3150
EZC250N3160
EZC250N3175
EZC250N3200
EZC250N3225
EZC250N3250
DB111751.eps
Rating
100 A
125 A
150 A
160 A
175 A
200 A
225 A
250 A
2P 2t
EZC250H2100
EZC250H2125
EZC250H2150
EZC250H2160
EZC250H2175
EZC250H2200
EZC250H2225
EZC250H2250
3P 3t
EZC250H3100
EZC250H3125
EZC250H3150
EZC250H3160
EZC250H3175
EZC250H3200
EZC250H3225
EZC250H3250
D-7
Catalogue numbers
EZC250N/H 4P
Circuit breaker
Rating
63 A
80 A
100 A
125 A
150 A
160 A
175 A
200 A
225 A
250 A
4P 3t
EZC250N4063
EZC250N4080
EZC250N4100
EZC250N4125
EZC250N4150
EZC250N4160
EZC250N4175
EZC250N4200
EZC250N4225
EZC250N4250
4P 4t
EZC250N44063
EZC250N44080
EZC250N44100
EZC250N44125
EZC250N44150
EZC250N44160
EZC250N44175
EZC250N44200
EZC250N44225
EZC250N44250
Rating
63 A
80 A
100 A
125 A
150 A
160 A
175 A
200 A
225 A
250 A
4P 3t
EZC250H4063
EZC250H4080
EZC250H4100
EZC250H4125
EZC250H4150
EZC250H4160
EZC250H4175
EZC250H4200
EZC250H4225
EZC250H4250
4P 4t
EZC250H44063
EZC250H44080
EZC250H44100
EZC250H44125
EZC250H44150
EZC250H44160
EZC250H44175
EZC250H44200
EZC250H44225
EZC250H44250
DB111666.eps
D-8
EZCV250N/H 3P/4P
Rating
63 A
80 A
100 A
125 A
150 A
160 A
175 A
200 A
225 A
250 A
3P 3t
EZCV250N3063
EZCV250N3080
EZCV250N3100
EZCV250N3125
EZCV250N3150
EZCV250N3160
EZCV250N3175
EZCV250N3200
EZCV250N3225
EZCV250N3250
DB111504.eps
Rating
63 A
80 A
100 A
125 A
150 A
160 A
175 A
200 A
225 A
250 A
3P 3t
EZCV250H3063
EZCV250H3080
EZCV250H3100
EZCV250H3125
EZCV250H3150
EZCV250H3160
EZCV250H3175
EZCV250H3200
EZCV250H3225
EZCV250H3250
DB111505.eps
Rating
63 A
80 A
100 A
125 A
150 A
160 A
175 A
200 A
225 A
250 A
4P 3t
EZCV250N4063
EZCV250N4080
EZCV250N4100
EZCV250N4125
EZCV250N4150
EZCV250N4160
EZCV250N4175
EZCV250N4200
EZCV250N4225
EZCV250N4250
4P 4t
EZCV250N44063
EZCV250N44080
EZCV250N44100
EZCV250N44125
EZCV250N44150
EZCV250N44160
EZCV250N44175
EZCV250N44200
EZCV250N44225
-
4P 3t
EZCV250H4063
EZCV250H4080
EZCV250H4100
EZCV250H4125
EZCV250H4150
EZCV250H4160
EZCV250H4175
EZCV250H4200
EZCV250H4225
EZCV250H4250
4P 4t
EZCV250H44063
EZCV250H44080
EZCV250H44100
EZCV250H44125
EZCV250H44150
EZCV250H44160
EZCV250H44175
EZCV250H44200
EZCV250H44225
-
DB111505.eps
D-9
EZC250F/N/H, EZCV250N/H
Catalogue numbers
Accessories
Connection accessories
Cable lugs
Set of 3
Set of 4
EZELUG2503
EZELUG2504
Set of 3
Set of 4
EZETEX
EZETEX4P
Set of 3
Set of 4
EZESPDR3P
EZESPDR4P
Set of 2
Set of 2
Set of 2
EZETSHD3P
EZETSHD3PN
EZETSHD4PN
Set of 2
Set of 3
EZEFASB2
EZEFASB3N
DB105209.eps
250 A
DB111752.eps
Terminal extensions
DB111674.eps
Spreaders
DB105210.eps
Terminal shields
DB105211.eps
Phase barriers
Electrical auxiliaries
DB111667.eps
DB105214.eps
DB105213.eps
DB105212.eps
Indication contacts
D-10
EZEAX
EZEAL
EZEAXAL
EZEALV
Voltage releases
AC
AC
DB111632.eps
DB111506.eps
DC
(UVR)
(UVRN)
DC
Voltage
MX/SHT
100-120 V
EZESHT100AC
120-130 V
EZESHT120AC
200-240 V
EZESHT200AC
277 V
EZESHT277AC
380-440 V
EZESHT400AC
440-480 V
EZESHT440AC
24 V
EZESHT024DC
48 V
EZESHT048DC
Voltage
MN/UVR
110-130 V
EZEUVR110AC
200-240 V
EZEUVR200AC
277 V
EZEUVR277AC
380-415 V
EZEUVR400AC
440-480 V
EZEUVR440AC
24 V
EZEUVR024DC
48 V
EZEUVR048DC
125 V
EZEUVR125DC
(1) Only EZC250-4P and EZCV250-3/4P
MN/UVR (1)
EZEUVRN110AC
EZEUVRN200AC
EZEUVRN277AC
EZEUVRN400AC
EZEUVRN440AC
EZEUVRN024DC
EZEUVRN048DC
EZEUVRN125DC
Rotary handles
DB105216.eps
EZEROTDS
EZEROTDSRY
EZEROTE
EZEROTERY
EZELOCK
EZELOCKN
EZEPLUG3L
EZEPLUG3H
EZEPLUG4
EZEPCON1
DB105217.eps
Locks
DB105218.eps
Padlocking system
Plug-in
DB127583.eps
Plug-in 250 A
D-11
Catalogue numbers
EZC400N/H 3P/4P
Circuit breaker
DB400023
Rating
320 A
350 A
400 A
3P 3t
EZC400N3320N
EZC400N3350N
EZC400N3400N
Rating
320 A
350 A
400 A
3P 3t
EZC400H3320N
EZC400H3350N
EZC400H3400N
Rating
320 A
350 A
400 A
4P 3t
EZC400N4320N
EZC400N4350N
EZC400N4400N
4P 4t
EZC400N44320N
EZC400N44350N
EZC400N44400N
Rating
320 A
350 A
400 A
4P 3t
EZC400H4320N
EZC400H4350N
EZC400H4400N
4P 4t
EZC400H44320N
EZC400H44350N
EZC400H44400N
DB400023
DB400023
D-12
EZC630N/H 3P/4P
Circuit breaker
DB400023
Rating
400 A
500 A
600 A
3P 3t
EZC630N3400N
EZC630N3500N
EZC630N3600N
Rating
400 A
500 A
600 A
3P 3t
EZC630H3400N
EZC630H3500N
EZC630H3600N
Rating
400 A
500 A
600 A
4P 3t
EZC630N4400N
EZC630N4500N
EZC630N4600N
4P 4t
EZC630N44400N
EZC630N44500N
EZC630N44600N
Rating
400 A
500 A
600 A
4P 3t
EZC630H4400N
EZC630H4500N
EZC630H4600N
4P 4t
EZC630H44400N
EZC630H44500N
EZC630H44600N
DB400023
DB400023
D-13
Catalogue numbers
EZC400/630N/H
Accessories
Rear connections
Set of 3
Set of 4
LV432479
LV432480
Set of 3
Set of 4
LV432481
LV432482
Set of 10
LV429348
Set of 3
Set of 4
LV432484
LV432485
Set of 3
Set of 4
LV432486
LV432487
3P
4P
3P
4P
LV432490
LV432491
LV432492
LV432493
Set of 3
Set of 4
Set of 3
Set of 4
LV432500
LV432501
LV432502
LV432503
Set of 3
Set of 4
Set of 3
Set of 4
LV432504
LV432505
LV432506
LV432507
3P
4P
Long terminal shield, 45 mm (1 piece)
3P
4P
Interphase barriers
Set of 6
Long terminal shiled for spreaders, 52,5mm (1 piece) (supplied with insulating plate) 3P
4P
2 insulating screens (70 mm pitch)
3P
4P
LV432591
LV432592
LV432593
LV432594
LV432570
LV432595
LV432596
LV432578
LV432579
E22041
E22040
LV432475
LV432476
2 short
2 long
E21276
E21012
Spreaders
52.5 mm
70 mm
(1)
E18602
Insulation accessories
E18606
E18618
D-14
EZC400/630N/H (cont.)
Accessories(cont.)
Electrical auxiliaries
Auxiliary contacts (changeover)
E18608
Voltage releases
E18609
29450
29452
LV540050
OF or SD or SDE or SDV
OF or SD or SDE or SDV low level
SDE adaptor mandatory for trip unit TM
Voltage
24 V 50/60 Hz
48 V 50/60 Hz
110-130 V 50/60 Hz
220-240 V 50/60 Hz and 208-277 V 60 Hz
380-415 V 50 Hz and 440-480 V 60 Hz
DC
Voltage
12 V
24 V
30 V
48 V
60 V
125 V
250 V
MN 48 V 50/60 Hz with fixed time delay
Composed of:
MN 48 V DC
Delay unit 48 V 50/60 Hz
MN 220-240 V 50/60 Hz with fixed time delay
Composed of:
MN 250 V DC
Delay unit 220-240 V 50/60 Hz
MN 48 V DC/AC 50/60 Hz with adjustable time delay
Composed of:
MN 48 V DC
Delay unit 48 V 50/60 Hz
MN110-130 V DC/AC 50/60 Hz with adjustable time delay
Composed of:
MN 125 V DC
Delay unit 110-130 V 50/60 Hz
MN 220-250 V 50/60 Hz with adjustable time delay
Composed of:
MN 250 V DC
Delay unit 220-250 V 50/60 Hz
AC
MX
LV429384
LV429385
LV429386
LV429387
LV429388
MN
LV429404
LV429405
LV429406
LV429407
LV429408
LV429382
LV429390
LV429391
LV429392
LV429383
LV429393
LV429394
LV429402
LV429410
LV429411
LV429412
LV429403
LV429413
LV429414
LV429412
LV429426
LV429414
LV429427
LV429412
33680
LV429413
33681
LV429414
33682
D-15
Catalogue numbers
EZC400/630N/H (cont.)
Accessories (cont.)
Rotary handle
LV432597
E18611
LV432598
E18612
Locks
29370
By fixed device
32631
E18613
E18621
By removable device
D-16
Ronis 1351B.500
Profalux KS5 B24 D4Z
LV432604
41940
42888
Main Busbar
4 ways
6 ways
8 ways
10 ways
12 ways
250 A
EZB250W04
EZB250W06
EZB250W08
EZB250W10
EZB250W12
400 A
EZB400W04
EZB400W06
EZB400W08
EZB400W10
EZB400W12
630 A
EZB630W04
EZB630W06
EZB630W08
EZB630W10
EZB630W12
Db100837.eps
4 ways (3P)
8 ways (3P)
Db100838.eps
2 ways
4 ways
4 ways (3P)
250 A
400 A
630 A
Db100839.eps
Main connectors
EZB250MCNS
EZB400MCNS
EZB630MCNS
To connect the main incomer to EasyPact EZC busbar (EasyPact EZC/Compact NSX/NB or INS switch)
Mechanical lugs
Db100840.eps
250 A
400 A
630 A
16-150 mm2
35-300 mm2
25-240 mm2
2 cables per phase
EZB630MLUG
EZB400MLUG
Db100841.eps
Connector caps
Connector caps for 100 A out goings
Connector caps for 250 A out goings
To isolate connections when branch breaker not installed
Set of 3
Set of 3
EZB100CAP
EZB250CAP
D-17
Notes
D-18
As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this publication.
This document has been printed on ecological paper
Design: Schneider Electric
Photos: Schneider Electric
Printed:
04-2013