Earth Potential Rise

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Earth potential rise - Wikipedia https://en.wikipedia.

org/wiki/Earth_potential_rise

In electrical engineering, earth potential rise (EPR) also called ground potential rise
(GPR) occurs when a large current flows to earth through an earth grid impedance. The potential
relative to a distant point on the Earth is highest at the point where current enters the ground, and
declines with distance from the source. Ground potential rise is a concern in the design of electrical
substations because the high potential may be a hazard to people or equipment.

The change of voltage over distance (potential gradient) may be so high that a person could be
injured due to the voltage developed between two feet, or between the ground on which the person
is standing and a metal object. Any conducting object connected to the substation earth ground,
such as telephone wires, rails, fences, or metallic piping, may also be energized at the ground
potential in the substation. This transferred potential is a hazard to people and equipment outside
the substation.

Causes
Step, touch, and mesh voltages
Mitigation
Calculations
Standards and regulations A computer calculation of the
High-voltage protection of telecommunication circuits voltage gradient around a small
substation. Where the voltage
See also
gradient is steep, a hazard of
References electric shock is present for
passers-by.
External links

Earth Potential Rise (EPR) is caused by electrical faults that occur at electrical substations, power
plants, or high-voltage transmission lines. Short-circuit current flows through the plant structure
and equipment and into the grounding electrode. The resistance of the Earth is non-zero, so
current injected into the earth at the grounding electrode produces a potential rise with respect to a
distant reference point. The resulting potential rise can cause hazardous voltage, many hundreds of
metres away from the actual fault location. Many factors determine the level of hazard, including:
available fault current, soil type, soil moisture, temperature, underlying rock layers, and clearing
time to interrupt a fault.

Earth potential rise is a safety issue in the coordination of power and telecommunications services.
An EPR event at a site such as an electrical distribution substation may expose personnel, users or
structures to hazardous voltages.

1 of 6 12/02/2020, 16:24
Earth potential rise - Wikipedia https://en.wikipedia.org/wiki/Earth_potential_rise

"Step voltage" is the voltage between the feet of a person standing near an energized grounded
object. It is equal to the difference in voltage, given by the voltage distribution curve, between two
points at different distances from the "electrode". A person could be at risk of injury during a fault
simply by standing near the grounding point.

"Touch voltage" is the voltage between the energized object and the feet of a person in contact with
the object. It is equal to the difference in voltage between the object and a point some distance
away. The touch voltage could be nearly the full voltage across the grounded object if that object is
grounded at a point remote from the place where the person is in contact with it. For example, a
crane that was grounded to the system neutral and that contacted an energized line would expose
any person in contact with the crane or its uninsulated load line to a touch voltage nearly equal to
the full fault voltage.

"Mesh voltage" is a factor calculated when a grid of grounding conductors is installed. Mesh voltage
is the potential difference between the metallic object connected to the grid, and the potential of
the soil within the grid. It is significant because a person may be standing inside the grid at a point
with a large voltage relative to the grid itself.

An engineering analysis of the power system under fault conditions can be used to determine
whether or not hazardous step and touch voltages will develop. The result of this analysis can show
the need for protective measures and can guide the selection of appropriate precautions.

Several methods may be used to protect employees from hazardous ground-potential gradients,
including equipotential zones, insulating equipment, and restricted work areas.

The creation of an equipotential zone will protect a worker standing within it from hazardous step
and touch voltages. Such a zone can be produced through the use of a metal mat connected to the
grounded object. Usually this metal mat (or ground mesh) is connected to buried ground rods to
increase contact with the earth and effectively reduce grid impedance.[1] In some cases, a
grounding grid can be used to equalize the voltage within the grid. Equipotential zones will not,
however, protect employees who are either wholly or partially outside the protected area. Bonding
conductive objects in the immediate work area can also be used to minimize the voltage between
the objects and between each object and ground. (Bonding an object outside the work area can
increase the touch voltage to that object in some cases, however.)

The use of insulating personal protective equipment, such as rubber gloves, can protect employees
handling grounded equipment and conductors from hazardous touch voltages. The insulating
equipment must be rated for the highest voltage that can be impressed on the grounded objects
under fault conditions (rather than for the full system voltage).

Workers may be protected from hazardous step or touch voltages by prohibiting access to areas
where dangerous voltages may occur, such as within substation boundaries or areas near

2 of 6 12/02/2020, 16:24
Earth potential rise - Wikipedia https://en.wikipedia.org/wiki/Earth_potential_rise

transmission towers. Workers required to handle conductors or equipment connected to a


grounding system may require protective gloves or other measures to protect them from
accidentally energized conductors.

In electrical substations, the surface may be covered with a high-resistivity layer of crushed stone
or asphalt. The surface layer provides a high resistance between feet and the ground grid, and is an
effective method to reduce the step and touch voltage hazard.

In principle, the potential of the earth grid Vgrid can be calculated using Ohm's Law if the fault
current (If) and resistance of the grid (Zgrid) are known.

While the fault current from a distribution or transmission system can usually be calculated or
estimated with precision, calculation of the earth grid resistance is more complicated. Difficulties
in calculation arise from the extended and irregular shape of practical ground grids, and the
varying resistivity of soil at different depths.

At points outside the earth grid, the potential rise decreases. The simplest case of the potential at a
distance is the analysis of a driven rod electrode in homogeneous earth. The voltage profile is given
by the following equation.

where

is a point from the center of the earth grid (in meters).


is the voltage at distance from the earth grid, in volts.
is the resistivity of the earth, in Ωꞏm.
is the earth fault current, in amperes.

This case is a simplified system; practical earthing systems are more complex than a single rod,
and the soil will have varying resistivity. It can, however, reliably be said that the resistance of a
ground grid is inversely proportional to the area it covers; this rule can be used to quickly assess
the degree of difficulty for a particular site. Programs running on desktop personal computers can
model ground resistance effects and produce detailed calculations of ground potential rise, using
various techniques including the finite element method.

The US Occupational Safety and Health Administration (OSHA) has designated EPR as a "known
hazard" and has issued regulations governing the elimination of this hazard in the work place.[2]

Protection and isolation equipment is made to national and international standards described by

3 of 6 12/02/2020, 16:24
Earth potential rise - Wikipedia https://en.wikipedia.org/wiki/Earth_potential_rise

IEEE, National Electrical Codes (UL/CSA),FCC, and Telcordia.

IEEE Std. 80-2000 is a standard that addresses the calculation and mitigation of step and touch
voltages to acceptable levels around electrical substations.

In itself, a ground potential rise is not harmful to any equipment or person bonded to the same
ground potential. However, where a conductor (such as a metallic telecommunication line) bonded
to a remote ground potential (such as the Central Office/Exchange) enters the area subject to GPR,
the conflicting difference of potentials can create significant risks. High voltage can damage
equipment and present a danger to personnel. To protect wired communication and control
circuits in sub stations, protective devices must be applied. Isolation devices prevent the transfer of
potential into or out of the GPR area. This protects equipment and personnel who might otherwise
be exposed simultaneously to both ground potentials, and also prevents high voltages and currents
propagating towards the telephone company's central office or other users connected to the same
network. Circuits may be isolated by transformers or by non-conductive fiber optic couplings.
(Surge arresting devices such as carbon blocks or gas-tube shunts to ground do not isolate the
circuit but divert high voltage currents from the protected circuit to the local ground. This type of
protection will not fully protect against the hazards of GPR where the danger is from a remote
ground on the same circuit.)

Telecommunication standards define a "zone of influence" around a substation, inside of which,


equipment and circuits must be protected from the effect of ground potential rise. In North
American practice, the zone of influence is considered to be bounded by the "300 volt point", which
is the point along a telecommunications circuit at which the GPR reaches 300 volts with respect to
distant earth.[3] The 300 volt point defining a zone of influence around a sub station is dependent
on the ground resistivity and the amount of fault current. It will define a boundary a certain
distance from the ground grid of the sub station. Each sub station has its own zone of influence
since the variables explained above are different for each location.[4]

In the UK, any site subject to a Rise-of-Earth-Potential (ROEP) is referred to as a 'Hot-Site'. The
Zone-of-Influence was historically measured as anywhere within 100m of the boundary of the
high-voltage compound at a Hot-Site. Depending on the size of the overall site this may mean that
parts of a larger site may not need to be classed as 'Hot', or (conversely) the influence of small sites
may extend into areas outside of the land owner's control. Since 2007, it is allowable to use the
Energy-Networks-Association (ENA) Recommendation S34 [5] ('A Guide for Assessing the Rise of
Earth Potential at Substation Sites') to calculate the Hot-Zone. This is now defined as a contour-
line marking where the ROEP exceeds 430V for normal-reliability power lines, or 650V for high-
reliability lines. The 'Zone' extends in a radius from any bonded metalwork, such as the site earth
electrode system or boundary fence. This may effectively reduce the overall size of the Hot-Zone
compared to the previous definition. However, strip earth electrodes, and any non-effectively
insulated metallic-sheath/armouring of power cables which extend out of this zone would continue
to be considered as 'hot' for a distance of 100m from the boundary, encompassing a width of two
meters on either side of the conductor. It is the responsibility of the owning Electrical-Supply-

4 of 6 12/02/2020, 16:24
Earth potential rise - Wikipedia https://en.wikipedia.org/wiki/Earth_potential_rise

Industry (ESI) to calculate the Hot-Zone.

Openreach (a BT Group company tasked with installing and maintaining a significant majority of
the physical telephone network in the UK) maintains a Hot-Site Register, updated every 12 months
by voluntarily supplied information from the ESI companies in the UK. Any Openreach engineer
visiting a site on the register must be Hot-Site trained. Certain working practices and planning
considerations must be followed, such as not using armoured telephone cables, fully sealing cable
joints to prevent access, over-sleeving of individual pairs of wires beyond the end of the cable
sheath, and isolating (outside the Hot-Zone) any line to be worked on. It is assumed to be the
responsibility of the party ordering the initial installation of a service to cover the cost of providing
isolation links, service isolating devices, and clearly marked trunking for running cables, and all
should be part of the planning process.

In some circumstances (such as when a 'cold' site is upgraded to 'hot' status), the Zone of Influence
may encompass residential or commercial property which is not within the property of the
Electrical Supply Industry. In these cases the cost of retroactively protecting each telephone circuit
may be prohibitively high, so a drainage electrode may be supplied to effectively bring the local
Earth Potential back to safe levels.

Single-wire earth return


Stray voltage

1. "IEEE SA - 80-2013 - IEEE Guide for Safety in AC Substation Grounding" (http://standards.iee


e.org/findstds/standard/80-2013.html). standards.ieee.org. Retrieved 2016-12-15.
2. "Standard Number 1910.269 - Electric Power Generation, Transmission, and Distribution" (http
s://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.269). United States
Department of Labor: Occupational Safety and Health Administration. 29 CFR 1910.269, with
additional information in Appendix C.
3. Steven W. Blume High Voltage Protection for Telecommunications John Wiley & Sons, 2011
ISBN 1-118-12710-2, chapter 3
4. "Archived copy" (https://web.archive.org/web/20120218141554/http://fiberopticlink.com/Tech_In
fo/pdf/Establishing_GPR_and_ZOI.pdf) (PDF). Archived from the original (http://fiberopticlink.c
om/Tech_Info/pdf/Establishing_GPR_and_ZOI.pdf) (PDF) on 2012-02-18. Retrieved
2012-04-20.
5. "Archived copy" (https://web.archive.org/web/20150402111430/http://www.energynetworks.org/
modx/assets/files/electricity/engineering/telecoms/eitc/restricted/Specification_edits/S34/S34.p
df) (PDF). Archived from the original (http://www.energynetworks.org/modx/assets/files/electrici
ty/engineering/telecoms/eitc/restricted/Specification_edits/S34/S34.pdf) (PDF) on 2015-04-02.
Retrieved 2012-06-28.
[1] ACIF Working Committee CECRP/WC18, AS/ACIF S009:2006 Installation Requirements for
Customer Cabling (Wiring Rules), Australian Communications Industry Forum, North Sydney,
Australia (2006) ISBN 1-74000-354-3

5 of 6 12/02/2020, 16:24
Earth potential rise - Wikipedia https://en.wikipedia.org/wiki/Earth_potential_rise

https://web.archive.org/web/20061010124312/http://www.acif.org.au/__data/page/15836
/S009_2006r.pdf AS/ACIF S009:2006 Installation Requirements for Customer Cabling (Wiring
Rules).
http://esgroundingsolutions.com/ Information about Ground Potential Rise Studies
https://www.osha.gov/pls/oshaweb/owadisp.show_document?p_table=STANDARDS&
p_id=9868 OSHA 29 CFR 1910.269
http://www.davas.co.nz

Retrieved from "https://en.wikipedia.org/w/index.php?title=Earth_potential_rise&oldid=918495460"

This page was last edited on 28 September 2019, at 23:29 (UTC).

Text is available under the Creative Commons Attribution-ShareAlike License; additional terms may apply. By using
this site, you agree to the Terms of Use and Privacy Policy. Wikipedia® is a registered trademark of the Wikimedia
Foundation, Inc., a non-profit organization.

6 of 6 12/02/2020, 16:24

You might also like