Spec of 11 KV Series Trip Metering Panel With VCB
Spec of 11 KV Series Trip Metering Panel With VCB
1.01 This Specification covers the design, manufacture, assembly of components, testing at
Manufacturer‟s Works, supply and delivery of 12KV, 400A,18.4 KA FLOOR MOUNTED INDOOR
TYPE TOTALLY ENCLOSED SESRIES TRIP METERING SWITCHGEAR WITH VACUUM CIRCUIT
BREAKER including all accessories by Road Transport to different sites, for Indoor Installation
in switch room measuring 5M x 4M x 3.5M (height) with door of size 2.75M (height) x 1.8M
(width)
2.01 The offered equipment including all accessories shall conform to latest versions of following
standards.
4. Painting IS 5
3.01 For the purpose of designing, following climatic conditions shall be considered.
5. Relative Humidity 95 %
4.00 APPLICATION :
4.01 The equipment shall be installed on floor in indoor locations towards the following applications :
1 To protect WBSEDCL‟s Distribution System for Fault in Consumer‟s Installation.
2 To protect and isolate 11KV Bulk Power Supply Feeder for Fault in Outgoing System.
5.01 For the purpose of designing, following technical parameters shall be considered :
1 Nominal voltage 11 KV
2 Rated Voltage 12 KV
3 Phase 3
4 Frequency 50 Hz
9 Insulation Level :
6.01 General :
6.011 The equipment shall be indoor type, metal enclosed, floor mounted Series Trip, Triple Pole,
Metering Switchgear with Vacuum Circuit Breaker, suitable isolation and horizontal draw out
facility.
6.012 The equipment shall be totally enclosed metal clad for indoor application.
6.013 Vacuum Interrupter shall be rated for 100 nos. operation at interrupting capacity of 26.3 KA.
6.014 Before despatching equipment all external holes shall be blocked suitably so that no foreign
element may enter into it.
6.015 The equipment furnished under this specification shall be suitably packed for transportation
maintaining space and weight limitations.
6.02 Construction :
6.080 C.T. shall be provided with terminal marking, wiring diagram and rating plate as per provision
in I.S.
6.08 POTENTIAL TRANSFORMER :
6.081 The equipment shall be provided with (3) three phase Potential Transformer(P.T.) having
following particulars :
1. No. of Phase Three
2. Ratio 11000/110 Volts
√3 √3
3. Vector Group Star / Star
4. Accuracy Class 0.5
5. VA Burden 50 VA/Phase
6. Protection of H.V. & L.V. H.R.C. Fuse
6.082 P.T. should be 3 phase, 5 Limb or 3 single phase with Star Connection made to form 3 phase
PT having Star point Earthed for both type of PT in HV & LV side.
6.083 P.T. shall be dry or resin-cast type.
6.084 P.T. shall be connected at Incoming side.
6.085 P.T. shall be non-draw out fixed type.
6.086 P.T. shall be mounted on top of the Unit.
6.087 Over Voltage factor of P.T. : 1.2 for continuous & 1.9 for 8 Hrs.
6.088 P.T. shall be provided with suitable H.R.C. Fuses both at H.V. & L.V. sides which shall be easily
accessible without dismantling.
6.092 Test Terminal Block : Standard Test Terminal Block with cover having Sealing Arrangement
shall be provided in metering circuit of equipment panel for connection to 3 phase 4 wire
Energy Meter. TTB to be placed beneath the Energy Meter.
6.093 Space & Wiring for Energy Meter : Necessary space shall be provided in man height position
of the equipment panel for housing projected type Energy Meter. Space is to be provided for
fixing of Energy Meter of dimension 250 mm(W) x 300 mm(H). Necessary wiring shall be
drawn from Test Terminal Block for connection of Energy Meter.
6.172 H.T. Power Cable of Outgoing Side shall enter the rear bottom portion of the Switchgear
through rear Entry Cable End Box. Normally no rear Entry Cable End Box shall be supplied
with the Switchgear unless otherwise required for design consideration. But provision shall be
made for housing, fixing and covering user‟s Cable and Cable End Box for termination of H.T.
XLPE Power Cable of size upto 3C x 300 sq.mm. (Outgoing Power Cable)
3. The front door of Switchgear Panel where meters to be installed shall be provided with
sealing arrangement with similar extension pieces welded at appropriate placed one at
the upper side and another at lower side of the cubicle and door.
11.02 Six copies of above mentioned drawings, data and manuals of offered equipment shall have to
be submitted for approval and final distribution afterwards.
11.03 In addition to above, each crate containing mentioned equipment shall also accompany in
water proof folder and set of approved drawings, data and manuals as mentioned above.
11.04 Before starting manufacture of the equipment, the manufacturer shall have to take approval
of the design drawings from the WBSEDCL.
12.00 PRICE :
12.01 The price (quoted price) should include the price of equipment including all accessories as per
schedule of requirement.
14.00 DEVIATION :
14.01 All deviations from the specification shall be recorded in the „Deviation Sheet‟ with reference
to respective Clauses of the Specification by drawing specification for the same. Unless
deviations are recorded in the Deviation Sheet and submitted with the offer it will be taken for
granted that the offer is made in conformity with the specification.
15.00 VALIDITY PERIOD :
15.01 The Offer against Tender should remain valid for a minimum period of 120 days from the next
day of opening of the Tender. However, WBSEDCL may, on the merit of case, request
extension of validity of the Offer for a further suitable period without any change in Terms &
Conditions of the Offer.
16.00 TYPE TESTS (after issuance of order) :
Besides submission of Type Test Report, carried out within five years as per Tender
Specification, Type Test at the discretion of WBSEDCL, shall have to be arranged by the
successful Manufacturer from any lot offered for inspection, sample chosen at random after
successful Routine Test by our Inspection Team, as per relevant ISS from CPRI/NABL
accredited/Government recognized Test House or Laboratory in presence of WBSEDCL‟S
representative.
However the However the necessary cost of the Type Test charges will be reimbursed to the
party on production of necessary supporting documents.
The following documents to be submitted by the Vendors to the Consignee Stores at the time
of physical delivery :-
a) Copy of Purchase Order.
b) Copy of Despatch Instruction.
c) Inspection Test Certificate.
d) Guarantee Certificate.
e) Proforma Invoice.
f) Calculation Sheet for price Variation on the basis of IEEMA or CACMAI as applicable
with base date of order.
g) Challan in triplicate.
h) Way bill, if applicable.
Sl No
A. General :
BILL OF MATERIALS
A. General : .
1. Maker‟s Name.
2. Company Addresses :
a) Office
b) Factory.
3. Applicable Standard.
4. Type & Designation.
5. Rated Voltage.
6. Phase.
7. Frequency.
8. Rated Normal Current.
9. Rated Short Circuit withstand capability for 3
Seconds.
10. Rated Making Current.
11. Insulation Level :
a) Power Frequency Withstand Voltage
b) Impulse withstand Voltage 1.2x50
micro seconds wave crest
12. Temperature Category.
B. Buses :
1. Bus Conductor :
a) Manufacture.
b) Material.
c) Reference Standard.
d) Size
e) Shape
f) Cross Sectional Area Sq .mm.
g) Minimum Clearance of Bare Bus and
Connections.
i) Phase to Phase mm.
ii) Phase to Ground mm.
h) Busbars provided with
i) Insulating Sleeve.
ii) Insulating Barriers.
i) Current Rating :
i) Rated Current-Amps(r.m.s.)
ii) Derated Current due to site
condition and 50 deg. C ambient
iii) 3 Sec-KA (r.m.s.)
C. Circuit Breaker :
1. Make
2. Type & Service
3. Reference Standard
4. Rated Voltage (Nominal/Highest)
5. Frequency
6. Poles
7. Current Rating.
a) Rated Current Amps.(r.m.s.)
b) Derated current due to site
conditions and 50 degree C
ambient Amps.(r.m.s.)
c) 3 Sec. Thermal rating KA
(r.m.s.)
d) Momentary KA (peak)
8. Temperature rise over 50 Deg. C.
Ambient Deg. C.
9. Interrupting Capacity based on duty
cycle
I) Duty Cycle :
a) Symmetrical KA (rms)
b) Symmetrical MVA at rated voltage
c) Asymmetrical (KA if any)
II) Rated Breaking Capacity :
a) Single Phase Capacitor Breaking
Capacity (Amps.)
b) Three Phase Capacitor Breaking
Capacity (Amps.)
c) Line Charging Breaking Capacity
(Amps.)
d) Cable Charging Breaking Capacity
(Amps.)
a) Type of Plating.
b) Thickness of Plating.
c) Contact Pressure.
E. Potential Transformers :
1. Make
2. Type
3. Reference Standard
4. Frequency
5. a) Rated Primary Voltage.
b) Rated Secondary Voltage.
c) Winding Connection.
6. a) Rated VA Burden per Phase.
b) VA Burden Thermal Limit.
7. Accuracy Class :
8. a) Class of Insulation.
b) Temperature Rise above 50 Deg.C
H. Toggle Switches :
1. Make.
2. Type.
3. Catalogue No.
4. Contract Rating.
I. Lamps :
1. Make
2. Type
3. Wattage
4. Resistance.
L. Operation Counter :
1. Make.
2. Type.
3. Ranges.
M. Breaker Assembly :
1. Type of Breaker.
2. Type of enclosure.
3. Thickness of sheet metal /plate.
4. Type of Indicators provided for Breaker position.
5. Insulation Level :
a) Impulse withstand in earth and between Phase
KV
b) 1 Min. Power Frequency withstand Voltage KV
RMS.
6. TL Fuse of Trip Circuit :
TECHNICAL SPEC SERIES TRIP METERING SWITCHGEAR
a) Type
b) Rating.
c) Continuous Current
d) Fusing Current
7. O/C & E/F Trip Coils :
a) Amps Rating :
b) Burden.
O. Approximate Weight :
a) Net Weight of the equipment
P. Painting Details :
R. Applicable Standards :
S. Shipping Dimensions :
a) Length mm.
b) Depth mm.
c) Height mm.
Date : Signature :
Name :
Designation :
Company Seal :
Place :