Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Ed71-440b (Vkm50-100ga (M) V1) PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 116

ED71-440B

Heat Reclaim Ventilator-With DX Coil-

VKM-GA(M) series
ED71-440B

Heat Reclaim Ventilator-With DX Coil-


VKM-GA(M) series
1. Selection Flowchart.................................................................................1
2. External Appearance...............................................................................2
3. Model Series ...........................................................................................2
4. Nomenclature..........................................................................................3
5. Structures................................................................................................3
6. Features ..................................................................................................4
6.1 General.....................................................................................................4
6.2 Design Flexibility ......................................................................................4
6.3 Energy Saving ..........................................................................................5
6.4 Unique Control System ............................................................................7
6.5 Quiet Operation ........................................................................................7
6.6 Easy Installation .......................................................................................8
6.7 Other Features .........................................................................................8
7. Specifications ........................................................................................14
7.1 With DX-Coil ..........................................................................................14
7.2 With DX-Coil & Humidifier ......................................................................15
7.3 Humidifier ...............................................................................................16
8. Dimensions ...........................................................................................17
9. Wiring Diagram .....................................................................................23
10.Fan Performance ..................................................................................25
10.1 Fan Performance....................................................................................25
10.2 The Correction Ratio of Exchange Efficiency.........................................27
11.Capacity Tables ....................................................................................28
11.1 Cooling ...................................................................................................28
11.2 Heating ...................................................................................................29
12.Sound Level ..........................................................................................30
12.1 Overall Sound Level ...............................................................................30
12.2 Octave Band Level .................................................................................31
12.3 Reducing Operating Sound ....................................................................33
13.Optional Accessories ............................................................................36
13.1 Installation of Optional Accessories (For VKM50GA (M) V1,
VKM80GA (M) V1, VKM100GA (M) V1).................................................36
13.2 Optional Accessories..............................................................................36
14.Standard Drawing for Installation ..........................................................37
15.Operation ..............................................................................................43
16.Installation .............................................................................................61
17.Outdoor Air Processing of Ceiling Mounted Duct Connection Type .....76
17.1 Stand-alone Operation is Possible as an Independent System .............76
17.2 Ability to Calculate Connectable Capacity..............................................76
17.3 Central Control System ..........................................................................77
17.4 Restrictions to Control System ...............................................................78
17.5 About the Basic Control of VKM.............................................................79
18.Appendix ...............................................................................................80
18.1 Purpose of Ventilation ............................................................................80
18.2 Kinds of Ventilation.................................................................................84
18.3 Calculation of Duct Pressure Loss .........................................................92
18.4 Notes for Ducted Systems......................................................................96

Table of Contents i
ED71-440B

18.5 Unit Conversion Tables ..........................................................................98


18.6 Refrigerant............................................................................................103
18.7 Psychrometric Chart.............................................................................109

ii Table of Contents
ED71-440B Selection Flowchart

1. Selection Flowchart
 &
   

  


        
/&

        

 #*" +  %

       
    



        !"#$  % 

"#$ => $   )



    => 

(

&
    ' ' 
            

 
       

'      


    + %
 %+   %  
/0&.1

,      
    + -.

/0&.1& 2      


    + % 

3 +    /0&.1&  

VKM-GA(M) series 1
External Appearance ED71-440B

2. External Appearance
VKM50GAMV1
VKM50GAV1

VKM80GAMV1
VKM100GAMV1
VKM80GAV1
VKM100GAV1

3. Model Series
Type 500 800 1000
DX-Coil and Humidifier VKM50GAMV1 VKM80GAMV1 VKM100GAMV1
DX-Coil VKM50GAV1 VKM80GAV1 VKM100GAV1
These units are applied only for CE regulation.

2 VKM-GA(M) series
ED71-440B Nomenclature

4. Nomenclature
V K M 50 GA M V1

Ventilation

Outdoor Air Treatment Type

Mounted Type

Nominal Air Flow Rate


50: 500m3/h, 80: 750m3/h, 100: 950m3/h

Major Design Category

Moisture (M: With Humidifier Elements, nothing: without Humidifier Elements)

Power Supply
V1: 1 phase, 220-240V, 50Hz

5. Structures

Heat Exchanger
Exhaust Fan Elements Damper
EA Motor
(Exhaust air to outdoors) Damper
DX-coil
OA
(Direct expansion coil)
(Fresh air from
outdoors) RA
(Return air
from room)

Air Supply Fan SA


(Supply air to room)
Electronic Parts Box
(Control box)

Humidifier element
Float switch
Utilizing the principle of capillary action,
Solenoid
water is permeated throughout the
valve
humidifier element. The heated air from the
DX-coil goes through the humidifier and
absorbs the moisture. water

AIRFLOW SA

Drain pan Drain

VKM-GA(M) series 3
Features ED71-440B

6. Features
6.1 General
• Interlocked operation with VRV
(Controls of interlocked operation for energy saving: The remote controller for air conditioner can be
used, so special remote controller for Heat Reclaim Ventilator is unnecessary.)
• Mounted for direct expansion coil unit for outdoor air treatment
• Changeover function for ventilation mode to Auto/Manual
• Fresh-up operation (Selectable: Supply air rich mode or exhaust air rich mode; initial setting)
• Mounted for water flow type natural evaporating humidifier
• Possible to attach the high efficiency filter
• Attaching the power supply terminal for easy connection
• Quiet operation
• Changeover function for air flow rate to High/Low (Ultra-high setting is possible.)
• The power supply of Heat Reclaim Ventilator is commonly used with the air-conditioner (1 phase, 220-
240V, 50Hz)
• Filter sign display and reset
• Timer setting
„ Features of direct expansion coil
• Draftless ventilation in heating
• High humidifying function
„ How to use this unit
• This unit should be used with air conditioners.
Air conditioning is impossible only by this unit, because this unit does not have temperature control
function. (Its capacity is too small in order to control the room temperature to the whole.)
And should be operated in combination with standard indoor units. (Interlocked operation)
• Independent operation without taking an interlock with indoor units is possible, however, temperature
setting by remote controller is impossible.
In this ON/OFF operation by thermostat depends on factory setting, however, this value is changeable by
setting mode on site.
• Model selection should be done not by cooling capacity but by ventilating air flow rate.

6.2 Design Flexibility


6.2.1 Efficient Fan Performance Produces a High Static Pressure
Improvements to the fan, including the use of multi- Dramatically higher static pressure is achieved due
arc blades, a thinner scroll and optimized fan scroll to improved fan performance. This reduces
angle, help to boost efficiency. limitations on unit placement and allows more
flexibility in duct design.
Higher static pressure
and reduced noise
Multi-arc blades
The use of multiple,
overlapping arc-shaped
fan blades makes it
possible to optimize the
chord length and blade-
outlet angle. This results
in higher static pressure
and quieter operation over
the entire usage range.
Rotating currents
for reduced loss
Resin scroll
The use of a thinner
scroll makes it possible
to rectify the rotating
currents within the scroll.
Higher static pressure
Higher static and reduced pressure loss
pressure
Fan scroll angle
Double suction In addition to increasing
The fan diameter the scroll wrap angle θ
has been α and boosting the static
increased and the pressure, the outflow
blade width angle α has been
optimized to suit, θ optimized to reduce
resulting in higher pressure loss in the
static pressure. outflow area.

6.2.2 Operable Outdoor Temperature Down to –15°C


If the outdoor air temperature falls below –10° C, the unit changes to intermittent operation to prevent
freezing of the heat exchanger element and dew condensation within the unit.
Intermittent operation
A thermistor (standard equipment) within the unit detects the outdoor air temperature. Unit operation varies
according to the detected temperature.

4 VKM-GA(M) series
ED71-440B Features

6.2.3 Indoor Unit Connectable to up to 130% of the Capacity

6.2.4 Slim Design


The slim design of only 387 mm in height enables
installation inside ceilings with less than 400 mm of
clearance.

6.3 Energy Saving


6.3.1 Automatic Heat Purge Function at Night
Not operation Night Morning
Stop

Heat Release

Heat
Reserve

Generation of heat with a PC etc. and The load of air conditioner is large and
its heat are reserved to a wall, ceiling. temperature does not fall easily.

Automatic heat
Cold Air
purge control
The heat which accumulated
indoors is discharged at night. Heat Release
Air conditioning load of the next
day is reduced, and efficiency is
increased. Heat
Reserve

Heat is discharged There is little load and it is to comfortable


temp. immediately
In case of interlocking operation with an air conditioner

„ Mechanism
<Operation>
1. Interlocking operation is carried
out with the air-conditioning Temp.
machine, and the time of 2 hours 40
passing after an operation stop is Outdoor Temp.
judged to be night.
(The same judgment as the 30
Setting Temp.
present preparatory operation)
2. After 2-hour progress, when Indoor Temp.
20
indoor temperature is higher than
Auto Start
the preset temperature of an air- Heat ON 2 hours
conditioning machine and higher Reclaim OFF
Ventilator
than outdoor temperature, ON
operation is started. Air Start
OFF
Conditioner
3. Operation will be stopped if indoor
temperature falls to air-
conditioning machine preset temperature.
„ Effect (Field Setting by remote controller)
It is reduction of about 5% of air-conditioning load at the time of cooling operation.
Air conditioning operation carries out April to October, and air-conditioning load is calculated only with
sensible heat load.

VKM-GA(M) series 5
Features ED71-440B

Nighttime Free Cooling Operation


<Flow Chart>

Nighttime Free Cooling Operating Condition Nighttime Free Cooling Precedent Condition

Air-conditioner Operation
<STOP> Air-conditioner Operation Yes
<RUN>

No
No
Nighttime free cooling Operation
<ON>

Yes
Temp. monitor operation time Yes
Standard mode
Lapsed time setup <Lapsed time> > 60hr
<2hr, 4hr, 6hr, 8hr>
No Standby mode
<60 Min>
( Fan ON time is included )

No From air-conditioner stop time


<Lapsed time> > <Setup time>

Yes
<Indoor temp.> < <Preset temp.> Yes
=
Fan operation & Temperature monitor
<5Min>
No
Yes
Yes
<Indoor temp.> < <Outdoor temp.>
No =
<Indoor temp.> > <Preset temp.+2˚C>

No
Yes
Yes
Fan operation Lapsed time Fan operation
No <Lapsed time> > 60Min <STOP>
<Indoor temp.> > <Outdoor temp.>
No
Yes

Fan operation
<ON (H)or(U-H)tap>

6.3.2 Automatic Changeover to Efficient Operation Patterns


Operation automatically changes to the optimum pattern to suit conditions.
Cooling In between (bypass ventilation) Heating
Heat exchanger element Heat exchanger element
Exhaust fan Damper (heat recovery) (heat recovery)

EA RA EA RA EA RA
Automatic Automatic
changeover changeover
OA SA OA SA OA SA

Air supply fan DX-coil (cooling) DX-coil (heating) Humidifying

6 VKM-GA(M) series
ED71-440B Features

6.3.3 Efficient Outdoor Air Introduction with Heat Exchanger and Cooling / Heating Operation
Indoor unit with outdoor air treatment
Using outdoor air, the temperature can 100 80
be brought near room temperature with 60
minimal cooling capacity through the
use of outdoor air. Outdoor air temperature
Heating and cooling in summer
Effect of full heat exchange

Relative humidity (%)


+ Effect of cooling 40
heat recovery
+
humidifying Indoor temperature during cooling Effect of
Indoor temperature during heating humidification
20

Outdoor air temperature


in winter Effect of heating
Effect of full heat exchange

–5 0 5 10 15 20 25 30 35 40
Dry bulb temperature (˚CDB)

6.3.4 Operations, Such as Cleaning, Ventilation, Cooling / Heating and Humidifying, are Possible
with One Remote Controller
Four air conditioner functions can be managed using a single remote control. This makes it easy to obtain
high-quality and energy-efficient outdoor air treatment.

The VRVIII
outdoor unit

Heat Reclaim
Link connection Ventilator (VKM)

During group control operation, the unit has a capacity


Indoor unit equivalent to two standard indoor units. Up to 16 standard
remote control indoor units can be connected at once.

Control of the Heat Reclaim Ventilator (VKM) type indoor unit


is managed using the remote control of the standard indoor
units connected.

6.4 Unique Control System


6.4.1 Independent Control Possible
Individual outdoor air treatment operation is
possible by connecting an optional remote
controller.
The VRVIII
outdoor unit

Heat Reclaim Heat Reclaim Heat Reclaim


Ventilator Ventilator Ventilator
(VKM) (VKM) (VKM)
Indoor unit
remote control

6.5 Quiet Operation


Reduced pressure loss and quieter operation internally lowers the noise output of the 1,000m3/h type
system to 38dB (VKM100GAMV1 at 240V 50Hz, High mode).

VKM-GA(M) series 7
Features ED71-440B

6.6 Easy Installation


6.6.1 Integrated System Includes Ventilation, Air Conditioning and Humidifying Operations
Rather than using separate ventilation, air conditioning, and humidifying components, the system
incorporating Heat Reclaim Ventilator (VKM) integrates all functions, reducing the total number of indoor
units and facilitating a far simpler system. The installation space becomes smaller and the labor required
for installation and maintenance is reduced significantly.

● Conventional Heat Humidifier


system Outdoor Reclaim
P56 P56 P56 P56 P56 unit Ventilator
(1,000 CMH)
Standard indoor unit

Ventilation, air conditioning,


and humidifying in a single system
● New system
The VRVIII
P56 P56 P56 P56 outdoor unit
Standard indoor unit VKM100GAMV1
One fewer
unit!

6.7 Other Features


6.7.1 Interlocked Operation with VRV
1. Simultaneous ON/OFF with the indoor unit by the indoor unit remote controller.
2. Heat Reclaim Ventilator independent operation during air conditioning off season by the indoor unit
remote controller.
3. Automatic ventilation mode changeover: Auto / Heat Recovery / Bypass
4. Fan speed changeover by the indoor unit remote controller: High / Low, Ultra-high / High
5. Fresh-up operation setting
6. Filter sign display notifies the time for cleaning the filter.
7. No need to purchase or install the Heat Reclaim Ventilator exclusive remote controller
8. Advantage to IAQ (Internal Air Quality)

Note: 4-6 can be set at the initial setting only. (When using the remote controller BRC1C62)

Type Interlocked operation with air conditioner

Indoor Heat
unit Reclaim
Structure Ventilator
(VKM)
Remote
Controller
(HC0228)

• Simultaneous operation by air conditioner’s remote controller is available.


Features
• Fan speed can be set at the initial setting.
Connectable Indoor unit VRV (all indoor unit)

Daikin’s Heat Reclaim Ventilator Other types

FAN mode No falling of dust OFF Dust


(HC0006) (HC0005)

Dust does not fall off from the air filter because the If conventional Heat Reclaim Ventilator, with
air supply fan of the interlocked indoor unit exclusive remote controller, is directly connected
remains activated even when the Heat Reclaim to indoor unit of air conditioner, dust may fall off
Ventilator is operated independently. from air filter when air conditioner is OFF.
Notes: 1. In case of the direct duct connection system, operate interlocking with indoor units.
2. Do not connect the duct with discharge air side of indoor units.

8 VKM-GA(M) series
ED71-440B Features

Installation Examples
Direct duct connection system Independent duct system

(HC0007) (HC0008)

6.7.2 Mechanism of Energy Saving


Heat Reclaim Ventilator recovers the thermal energy during cooling /
By heat recovery operation heating operation of air conditioner. Heat Reclaim Ventilator reduces the
cooling / heating load drastically and enhances the heating / cooling
efficiency.
Approx. 20% reduction
of heating / cooling load Exhaust Return
Air Air

Outdoor Supply
Air Air
Heat Exchanger Element
(Heat Recovery) (HC0230)

By setting to automatic Proper use of Heat recovery ventilation and normal ventilation saves
ventilation mode energy.
When the cooling operation is required in winter, use of heat recovery
ventilation is not efficient because the outdoor air temperature is
Approx. 6% reduction
normally lower than that of the indoor.
of heating / cooling load
Thus, the proper use of ventilation mode enhances the heating / cooling
efficiency.
Automatic Ventilation mode changeover
Operation Sensor of ventilation Decision of mode
Difference between (Which is more
indoor / outdoor temp. energy efficient?)
Indoor temp. > Outdoor temp. Normal ventilation (Bypass)
Cooling
Indoor temp. < Outdoor temp. Heat recovery ventilation
Indoor temp. > Outdoor temp. Heat recovery ventilation
Heating
Indoor temp. < Outdoor temp. Normal ventilation (Bypass)

Refer to the CONTROL for the mode changeover.


Heat Recovery mode
Exhaust Return
Air Air

Outdoor Supply
Air Air
Heat Exchanger Element
(Heat Recovery) (HC0231) Automatic
Changeover
Normal (Bypass) mode
Exhaust Return
Air Air

Outdoor Supply
Air Air
Heat Exchanger Element
(Heat Recovery) (HC0232)

Reduction of
Total heating / cooling 26%
26% reduction load (%)
of heating / cooling
20%
0%
load
Normal Heat Reclaim Ventilator Interlocked
operation independent operation operation (HC0233)

Note: The total heating / cooling load may vary depending on the climate or the other environmental conditions.

VKM-GA(M) series 9
Features ED71-440B

6.7.3 Fresh-up Operation


Both the excessive supply mode and the excessive exhaust mode are selectable.
This function creates a more comfortable air environment.
Supply Fresh-up Exhaust Fresh-up
(Excessive outdoor air supply) (Excessive exhaust air supply)

Supply air volume can be set at a higher level Exhaust air volume can be set at a higher level
Detail
than the exhaust air by the remote controller. than the supply air by the remote controller.

• Prevents inflow of toilet odor • Prevents outflow of airborne bacteria from


Major • Prevents inflow of outdoor air in winter rooms in a hospital
effects • Prevents outflow of odors from rooms in a
nursing home

Application Offices, etc. Hospitals, Nursing homes, etc.

Portion of fresh-up Heat Reclaim Air exhaust Heat Reclaim Ventilator


operation Ventilator Normal (VKM)
(VKM) ventilation fan Air supply
Air exhaust

Example Sick room Floor area

Air supply Portion of


exhaust
operation

6.7.4 Proprietary Developed HEP Element


The heat exchanger element uses a High Efficiency Paper (HEP) that has superior moisture-absorption
and humidifying properties and doubles the current efficiency of moisture absorption. The heat exchanger
unit speedily recovers heat contained as latent heat (vapor). The element is made of a material with
superior flame-resistant properties and is treated with an anti-molding agent.

Operation of the heat exchanger element


Outdoor Indoor

30.6˚C SA
62% RH 27.4˚C
63% RH

SA
Temperature Integrally-
and humidity formed liner
RA
26˚C RA
50% RH

32˚C (HC0013)
70% RH Integrally-formed liner
HEP anti-molding
Features
• High air shielding
Even in the conventional less humidity conditions, maintaining the features of the material that can get
excellent moisture permeability, we have achieved high air shielding, by special processing in the step of
milling paper.

Polymer material Air component


that inhibits air
permeability
Moisture permeability mechanism
Highly humid air
Moisture absorption
Water vapor

Move through capillary

Moisture release
Less humid air
Moisture absorbing liquid

• Polymer material that inhibits air permeability that treated on the surface of the heat exchanger
element restrains air permeability.

10 VKM-GA(M) series
ED71-440B Features

6.7.5 Easy Installation and Service Maintenance


Downsized
Model name Height (mm)
VKM50GAMV1
VKM50GAV1
VKM80GAMV1
387
VKM80GAV1
VKM100GAMV1
VKM100GAV1

Parallel air flow system (Daikin) Cross air flow system (Others)
This system prevents misconnection and
simplifies the installation work.

SA OA SA EA

RA EA RA OA
(HC0234) (HC0235)

6.7.6 The Operation is Available When the Outdoor Air Temperature is Down to -15°C
(Operation when the outdoor air temperature becomes lower than -10°C)
When the outdoor air suction temperature becomes lower than -10°C, the unit is changed to intermittent
operation to prevent freezing of the heat exchanger element and dew condensation within the unit.
Intermittent operation
The outdoor air thermistor (standard equipment) within the unit detects the temperature. According to
the detected temperature, the following operation determines.
<Step 1>
• The air supply fan is changed to intermittent operation, when the temperature is lower than -10°C.
• The intermittent operation of the air supply fan is changed to an operation of each cycle for 45
minutes’ operation after stopping operation for 15 minutes.
• The exhaust fan operates continuously according to setup.
<Step 2>
• When the temperature becomes lower than -15°C, the unit stops operation to prevent any defect,
such as dew condensation and freezing. The unit does not ventilate.
But, to detect the elevation of the outdoor air temperature, the unit operates for 5 minutes per hour.

6.7.7 The High Efficiency Filter (that has 65% of Average Dust Collecting Efficiency) is Suitable
High efficiency filter Maintenance cover
Name plate
Control box AIR
FLOW High efficiency
Install the high efficiency The side of heat
filter to meet the direction exchanger element
filter
of the arrow of the name plate.
Rail

Air filter Heat exchanger element Rail

Install the high efficiency filter


along the inside of the rail.

High efficiency filter

6.7.8 Additional Optional Accessories


Built-in optional high efficiency filter
It greatly reduces the installation space.
The installation of access doors and the unit can be reduced.

VKM-GA(M) series 11
Features ED71-440B

„ Selection Procedures (in Japan)


Various methods are used to calculate the required ventilating air flow rate according to CO2 generated by
inhabitants in a room, waste gas generated by use of fire, and other conditions of a room.
Here are 2 patterns of calculating methods.
Based on inhabitants

= 20 × A
Required ventilating
air flow rate (m3 / h) B

A: 20 × Living room floor space (m2)


B: Area occupied per person (m2)
The above equation conforms to article 20, 2
No.2 of the Building Standards Act in Japan.

Notes: 1. 20 (in the above equation) means “20(m3 / h · person)”, which is the required ventilating air flow rate
based on the CO2 exhausted by an adult sitting still in a room. If smoking is allowed, other calculation
method should be used.
2. Use 10 (m2) if the area occupied per person exceeds 10 (m2).
<Table 1>
Area occupied per
Type of building Remarks
person (N)
Floor space of a part used for business
Dining houses, restaurants, coffee-shops 3 m2 purposes

Cabarets, beer halls 2 m2 Floor space of a part used for business


purposes
Floor space of a part used for business
Japanese-style restaurants, hall for hire 3 m2
purposes
Floor space of a part used for business
Store market 3 m2 purposes
Pool rooms, Ping-pong rooms, dance 2 m2 Floor space of a part used for business
halls, bowling alleys purposes
Pin-ball parlors, Go club houses, Floor space of a part used for business
2 m2
mahjong parlors purposes
Floor space of a part used for business
Inns, hotels, and motels 10 m2 purposes

Massage parlors 5 m2 Floor space of a part used for business


purposes
Persons accommodated simultaneously with
Meeting places, public halls 0.5 – 1 m2
the number of persons calculated per unit
Offices 5 m2 Floor space of an office

* : Values set by the Metropolitan Maintenance Bureau in Japan.

Notes: 1. Table indicates the required ventilating air flow rate calculated as 20 m3 / h.
2. The area occupied per person by type of business is calculated in reference to Application Standards
for building administration in compliance with Building Standards Act in Japan.

Based on Room size

Required ventilating
= C×D×E
air flow rate (m3 / h)

C: Number of ventilation required per hour (ventilation / h)


D: Area of room (m2)
E: Height of Ceiling (m)
Calculation is based on the experiences of hygienic laboratory, etc. to find out the number of hourly
ventilation of the room air.

(Selection example)
Place: Living room of common household
Required ventilation: 6 times / h (See Table 2)
Area of room: Approx. 30 (m2)
Height of ceiling: 2.4 m
.
Required ventilating air flow rate = 6 × 30 × 2.4 =. 432 (m3 / h)

Required ventilating air flow rate 500 is almost equivalent to the unit type 50.
So select the close size of the unit.
In this case, select VKM50GAMV1.

12 VKM-GA(M) series
ED71-440B Features

<Table 2>
Groups Type of room Ventilation Groups Type of room Ventilation
required required
Living room 6 Audience room 6
Bathroom 6 Corridor 6
Common Playhouses
Drawing room 6 and movie Smoking room 12
household theaters
Toilet 10 Toilet 12
Kitchen 15 Projector room 20
Restaurant 6 Office room 6
Sushi restaurant 6 General work room 6
Dining
places Banquet hall 10 Telephone room 6
Tempura restaurant 20 Spinning plant 10
Cooking room 20 Printing plant 10
Guest room 5 Battery room 10
Corridor 5 Machinery plant 10
Dance hall 8 Plants Generator room 15
Large dining hall 8 Substation room, 15
Inns and
Washroom, Toilet 10 Painting shop, 15
hotels
Cooking room 15 Welding plant 15
Laundry room 15 Chemical plant 15
Engine room 20 Food plant 20
Boiler room 20 Wood working plant 20
Casting plant 50
Office room 6
General Waiting room 10
buildings Show room, Toilet 10
Consultation office 6
Conference room 12
Comfort 20
stations
Dark rooms Dark rooms for photo 16
Guest
Sick room 6 rooms of 6
ship

Office room 6 Room of potential noxious gas or 20 or


Hospitals combustible gas more
Corridor 10
Waiting room 10
Bathroom 10
Dining room, Toilet 10
Respiratory disease room 10
Laundry room 15
Cooking room 15
Surgery room 15
Sterilizing room 15
Engine room 20
Boiler room 20
Class room, library 6
Auditorium 6
Experimental chemistry 6
Schools room
Gymnasium 8
Toilet 12
Cooking room 15

VKM-GA(M) series 13
Specifications ED71-440B

7. Specifications
7.1 With DX-Coil
Type VKM50GAV1 VKM80GAV1 VKM100GAV1
Refrigerant R-410A
Power Supply 1 phase, 220-240V, 50Hz
Air flow rate (m3/h) 500 750 950
Ultra-high
Static pressure (Pa) 180 170 150
Air Flow Rate & Air flow rate (m3/h) 500 750 950
Static Pressure High
(Note 6) Static pressure (Pa) 150 120 100
Air flow rate (m3/h) 440 640 820
Low
Static pressure (Pa) 110 80 70
Ultra-high A 3.0 3.0 3.0
Normal Amp.
(Note 7) High A 2.5 2.6 2.5
Low A 2.1 2.1 2.1
Ultra-high W 560 620 670
Normal Input
High W 490 560 570
(Note 7)
Low W 420 470 480
Fan Type Sirocco Fan
Motor Output kW 0.280×2 0.280×2 0.280×2
Ultra-high (dB) 38/38.5/39 40/41/41.5 40/40.5/41
Sound Level
(Note 4, 5) High (dB) 36/36.5/37 37.5/38/39 38/38.5/39
220/230/240V
Low (dB) 33.5/34.5/35.5 34.5/36/37 35/36/36.5
Ultra-high (%) 76 78 74
Temp. Exchange
Efficiency High (%) 76 78 74
(Note 7, 10, 11)
Low (%) 77.5 79 76.5
Ultra-high (%) 64 66 62
Enthalpy Exchange
Efficiency (Cooling) High (%) 64 66 62
(Note 7)
Low (%) 67 68 66
Ultra-high (%) 67 71 65
Enthalpy Exchange
Efficiency (Heating) High (%) 67 71 65
(Note 7)
Low (%) 69 73 69
Casing Galvanized Steel Plate
Insulating Material Self-Extinguishable Urethane Foam
Heat Exchanging System Air to Air Cross Flow Total Heat (Sensible + Latent Heat) Exchange
Heat Exchanger Element Specially Processed Nonflammable Paper
Air Filter Multidirectional Fibrous Fleeces
Rows × Stages × Fin Pitch (mm) 2 × 12 × 2.2
Coil (Cross Fin Coil)
Face Area (m2) 0.078 0.118 0.165
Cooling Capacity (Note 2) (kW) 4.71 (1.91) 7.46 (2.96) 9.12 (3.52)
Heating Capacity (Note 3) (kW) 5.58 (2.38) 8.79 (3.79) 10.69 (4.39)
Dimensions Height × Width × Depth (mm) 387 × 1,764 × 832 387 × 1,764 × 1,214 387 × 1,764 × 1,214
Connection Duct Diameter (mm) φ200 φ250
Liquid (mm) φ6.4 C1220T (Flare Connection)
Piping Connection Gas (mm) φ12.7 C1220T (Flare Connection)
Drain PT3/4 External Thread
Refrigerant Control Electronic Expansion Valve
Connectable Outdoor Unit R-410A P(A) series
Weight Net (kg) 96 109 114
Around Unit 0°C~40°C DB 80%RH or Less
Unit Ambient
OA (Note 8) -15°C~40°C DB 80%RH or Less
Condition
RA (Note 8) 0°C~40°C DB 80%RH or Less
Operation Mode Heat Exchange Mode, Bypass Mode, Freshup Mode
Operation Manual, Installation Manual, Duct Connecting Flange, M4 Tapping Screw (for
Accessories
Connecting Duct), Refrigerant Piping Insulation Cover, Clamp
Drawing Number C: 4D051281 C: 4D051283 C: 4D051284
Notes:
1. Cooling and heating capacities are based on the following conditions. Fan is based on High and Ultra-high.
The figures in the parenthesis indicate the heat reclaimed from the heat recovery ventilator.
When calculating the capacity as indoor units, use the following figures: VKM50GAV1: 3.5kW VKM80GAV1: 5.6kW VKM100GAV1: 7.0kW
2. Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB
3. Indoor temperature: 20°C DB, Outdoor temperature: 7°C DB, 6°C WB
4. The operating sound measured at the point 1.5 m below the center of the unit is converted to that measured at an anechoic chamber built in accordance with the JIS C
1502 condition. The actual operating sound varies depending on the surrounding conditions (near running unit’s sound, reflected sound and so on) and is normally higher
than this value.
For operation in a quiet room, it is required to take measures to lower the sound. In details, refer to Engineering Data.
5. The noise level at the air discharge port is about 8-11 dB higher than the unit’s operating sound.
For operation in a quiet room, it is required to take measures to lower the sound for example install more than 2m soft duct near the air discharge grille.
6. Air flow rate can be changed over to Low mode or High mode.
7. Normal Amp., input, efficiency depend on the above air flow rate value.
8. OA: Fresh air from outdoor, RA: Return air from room
9. The specifications, designs and information here are subject to change without notice.
10. Temperature exchange efficiency is a mean value in cooling and heating.
11. Efficiency is measured under the following conditions. Ratio of rated external static pressure has been kept as follows. Outdoor side to indoor side is equal to 7 to 1.
12. In heating operation, freezing of the outdoor unit's coil increases. Heating capability decreases and the system goes into defrost operation.
During defrost operation, the fans of the unit continues driving (factory setting). The purpose of this is to maintain the amount of ventilation and humidifying.
13. When connecting with a VRV heat recovery type outdoor unit and bringing the RA (exhaust gas intake) of this unit directly in from the ceiling, connect to a BS unit identical
to the VRV indoor unit (master unit), and use group-linked operation. See the Engineering Data for details.
14. When connecting the indoor unit directly to the duct, always use the same system on the indoor unit as with the outdoor unit, perform group-linked operation, and make the
direct duct connection settings from the remote controller. (Mode No. “17 (27)” – First code No. “5” – Second code No. “6”.) Also, do not connect to the outlet side of the
indoor unit. Depending on the fan strength and static pressure, the unit might back up.

14 VKM-GA(M) series
ED71-440B Specifications

7.2 With DX-Coil & Humidifier


Type VKM50GAMV1 VKM80GAMV1 VKM100GAMV1
Refrigerant R-410A
Power Supply 1 phase, 220-240V, 50Hz
Air flow rate (m3/h) 500 750 950
Ultra-high
Static pressure (Pa) 160 140 110
Air Flow Rate & Air flow rate (m3/h) 500 750 950
Static Pressure High
(Note 7) Static pressure (Pa) 120 90 70
Air flow rate (m3/h) 440 640 820
Low
Static pressure (Pa) 100 70 60
Ultra-high A 3.0 3.0 3.0
Normal Amp.
(Note 8) High A 2.5 2.6 2.5
Low A 2.1 2.1 2.1
Ultra-high W 560 620 670
Normal Input
High W 490 560 570
(Note 8)
Low W 420 470 480
Fan Type Sirocco Fan
Motor Output kW 0.280×2 0.280×2 0.280×2
Ultra-high (dB) 37/37.5/38 38.5/39/40 39/39.5/40
Sound Level
(Note 5, 6) High (dB) 35/35.5/36 36/37/37.5 37/37.5/38
220/230/240V
Low (dB) 32/33/34 33/34/35.5 34/34.5/35.5
System Natural Evaporating Type
Elements quantity 1 2
Humidifier
Amount (Note 4) (kg/h) 2.7 4.0 5.4
Pressure Feed Water (MPa) 0.02-0.49
Ultra-high (%) 76 78 74
Temp. Exchange
Efficiency High (%) 76 78 74
(Note 8, 12, 13)
Low (%) 77.5 79 76.5
Ultra-high (%) 64 66 62
Enthalpy Exchange
Efficiency (Cooling) High (%) 64 66 62
(Note 8, 13)
Low (%) 67 68 66
Ultra-high (%) 67 71 65
Enthalpy Exchange
Efficiency (Heating) High (%) 67 71 65
(Note 8, 13)
Low (%) 69 73 69
Casing Galvanized Steel Plate
Insulating Material Self-Extinguishable Urethane Foam
Heat Exchanging System Air to Air Cross Flow Total Heat (Sensible + Latent Heat) Exchange
Heat Exchanger Element Specially Processed Nonflammable Paper
Air Filter Multidirectional Fibrous Fleeces
Rows × Stages × Fin Pitch (mm) 2 × 12 × 2.2
Coil (Cross Fin Coil)
Face Area (m2) 0.078 0.118 0.165
Cooling Capacity (Note 2) (kW) 4.71 (1.91) 7.46 (2.96) 9.12 (3.52)
Heating Capacity (Note 3) (kW) 5.58 (2.38) 8.79 (3.79) 10.69 (4.39)
Dimensions Height × Width × Depth (mm) 387 × 1,764 × 832 387 × 1,764 × 1,214 387 × 1,764 × 1,214
Connection Duct Diameter (mm) φ200 φ250
Liquid (mm) φ6.4 C1220T (Flare Connection)
Gas (mm) φ12.7 C1220T (Flare Connection)
Piping Connection
Water Supply (mm) φ6.4 C1220T
Drain PT3/4 External Thread
Refrigerant Control Electronic Expansion Valve
Connectable Outdoor Unit R-410A P(A) series
Net (kg) 102 120 125
Weight
Gross (Note 9) (kg) 107 129 134
Around Unit 0°C~40°C DB 80%RH or Less
Unit Ambient
OA (Note 10) -15°C~40°C DB 80%RH or Less
Condition
RA (Note 10) 0°C~40°C DB 80%RH or Less
Operation Mode Heat Exchange Mode, Bypass Mode, Freshup Mode
Operation Manual, Installation Manual, Duct Connecting Flange, M4 Tapping Screw (for Connecting Duct),
Accessories Water Supply Piping with Strainer, Half-Union Joint (Copper Piping Joint), Flare Nut (Copper Piping Joint),
Refrigerant Piping Insulation Cover, Water Supply Piping Insulation Cover, Sealing Material, Clamp
Drawing Number C: 4D051276A C: 4D051278 C: 4D051280
Notes:
1. Cooling and heating capacities are based on the following conditions. Fan is based on High and Ultra-high. The figures in the parenthesis indicate the heat reclaimed from the
heat recovery ventilator. When calculating the capacity as indoor units, use the following figures: VKM50GAMV1: 3.5kW VKM80GAMV1: 5.6kW VKM100GAMV1: 7.0kW
2. Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB
3. Indoor temperature: 20°C DB, Outdoor temperature: 7°C DB, 6°C WB
4. Humidifying capacity is based on the following conditions:
Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB
5. The operating sound measured at the point 1.5 m below the center of the unit is converted to that measured at an anechoic chamber built in accordance with the JIS C
1502 condition. The actual operating sound varies depending on the surrounding conditions (near running unit’s sound, reflected sound and so on) and is normally higher
than this value. For operation in a quiet room, it is required to take measures to lower the sound. In details, refer to Engineering Data.
6. The noise level at the air discharge port is about 8-11 dB higher than the unit’s operating sound.
For operation in a quiet room, it is required to take measures to lower the sound for example install more than 2m soft duct near the air discharge grille.
7. Air flow rate can be changed over to Low mode or High mode.
8. Normal Amp., input, efficiency depend on the above air flow rate value.
9. In case of holding full water in humidifier.
10. OA: Fresh air from outdoor, RA: Return air from room
11. The specifications, designs and information here are subject to change without notice.
12. Temperature exchange efficiency is a mean value in cooling and heating.
13. Efficiency is measured under the following conditions. Ratio of rated external static pressure has been kept as follows. Outdoor side to indoor side is equal to 7 to 1.

VKM-GA(M) series 15
Specifications ED71-440B

14. In heating operation, freezing of the outdoor unit’s coil increases. Heating capability decreases and the system goes into defrost operation.
During defrost operation, the fans of the unit continues driving (factory setting). The purpose of this is to maintain the amount of ventilation and humidifying.
15. When connecting with a VRV heat recovery type outdoor unit and bringing the RA (exhaust gas intake) of this unit directly in from the ceiling, connect to a BS unit identical
to the VRV indoor unit (master unit), and use group-linked operation. See the Engineering Data for details.
16. When connecting the indoor unit directly to the duct, always use the same system on the indoor unit as with the outdoor unit, perform group-linked operation, and make the
direct duct connection settings from the remote controller. (Mode No. “17 (27)” – First code No. “5” – Second code No. “6”.) Also, do not connect to the outlet side of the
indoor unit. Depending on the fan strength and static pressure, the unit might back up.

7.3 Humidifier
VKM50GAMV1 VKM80GAMV1 VKM100GAMV1
Humidifier type Natural evaporating type humidifier
Porosity plate 120 pcs.
Wetted element Porosity plate 60 pcs. Porosity plate 90 pcs.
(60×2 pcs.)
Water inlet port φ6.4 C1220T (Flare Connection)
Water outlet port PT3/4
2
Supply water pressure kg/cm 0.2 (Min.) ~ 5.0 (Max.)
Notes: 1. Feed clean water (city water, tap water or equivalent). Dirty water may clog the valve or cause dirt
deposits in the water container, resulting in poor humidifier performance. (Never use any cooling tower
water and heating - purpose water.)
Also, if the supply water is hard water, use a water softener because of short life.
∗Life of humidifying element is about 3 years (4,000 hours), under the supply water conditions of
hardness: 150 mg/l. (Life of humidifying element is about 1 year (1,500 hours) under the supply water
conditions of hardness: 400 mg/l.)
Annual operating hours: 10 hours / day × 26 days / month × 5 month = 1,300 hours
2. Maintain the supply water temperature at 5 ~ 50°C and its pressure at 20 ~ 490 kPa (0.2 ~ 5.0 kg/cm2).
If the water pressure is above 490 kPa (5.0 kg/cm2), add pressure reducing valve in between the kit
and the supply water shut - off valve.
3. The supply water line cannot be directly connected with a utility water tap. To unavoidably take water
from such line, employ a CISTERN (gotten configuration authorization).
4. Be sure to provide thermal insulation around the indoor piping as well as the shut - off valves.
5. In order to prevent harmful bacteria from generating, do maintenance on humidifying unit portion at the
beginning and the end of the heating season according to the operation manual.

16 VKM-GA(M) series
ED71-440B Dimensions

8. Dimensions
VKM50GAMV1
Unit (mm)

3D051285

VKM-GA(M) series 17
Dimensions ED71-440B

VKM80GAMV1
Unit (mm)

3D051286

18 VKM-GA(M) series
ED71-440B Dimensions

VKM100GAMV1
Unit (mm)

3D051287

VKM-GA(M) series 19
Dimensions ED71-440B

VKM50GAV1
Unit (mm)

3D051288

20 VKM-GA(M) series
ED71-440B Dimensions

VKM80GAV1
Unit (mm)

3D051289

VKM-GA(M) series 21
Dimensions ED71-440B

VKM100GAV1
Unit (mm)

3D051290

22 VKM-GA(M) series
ED71-440B Wiring Diagram

9. Wiring Diagram
VKM50GAMV1
VKM80GAMV1
VKM100GAMV1

C: 3D051310

VKM-GA(M) series 23
Wiring Diagram ED71-440B

VKM50GAV1
VKM80GAV1
VKM100GAV1

C: 3D051311

24 VKM-GA(M) series
ED71-440B Fan Performance

10. Fan Performance


10.1 Fan Performance
VKM50GAMV1 VKM80GAMV1

4D051312 4D051313

VKM100GAMV1

4D051314

VKM-GA(M) series 25
Fan Performance ED71-440B

VKM50GAV1 VKM80GAV1

4D051315 4D051316

VKM100GAV1

4D051317

26 VKM-GA(M) series
ED71-440B Fan Performance

10.2 The Correction Ratio of Exchange Efficiency

Air Flow Ratio = EA / OA 1.1 1.2 1.3

0.5 0.6 0.7 0.8 0.9 1.0 1.4

90
reading off the chart [%]
Exchange Efficiency

80

70

60

50

40 50 60 70 80 90 100
Corrected Exchange Efficiency [%]

<Example of correction>

VKM50 (High mode): Air flow rate at strong notch 500 m3 / h


(Cooling) Enthalpy exchanging efficiency
64%
Supply air and exhaust air flow rate for fresh-up mode:
Supply air flow rate / Exhaust air flow rate = 540 / 500 = 1.08
(Cooling) Enthalpy exchange efficiency from above Table
64 × 0.97 = 62.1%
Correction ratio

VKM-GA(M) series 27
Capacity Tables ED71-440B

11. Capacity Tables


11.1 Cooling
Coil inlet air temp.
Capacity
Outdoor 14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
MODEL
°CDB 20.0°CDB 23.0°CDB 26.0°CDB 27.0°CDB 28.0°CDB 30.0°CDB 32.0°CDB
DX-Coil
Only TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
10.0 1.9 1.5 2.3 1.8 2.6 2.0 2.8 2.0 — — — — — —
12.0 1.9 1.5 2.3 1.8 2.6 2.0 2.8 2.0 — — — — — —
14.0 1.9 1.5 2.3 1.8 2.6 2.0 2.8 2.0 3.0 2.0 — — — —
16.0 1.9 1.5 2.3 1.8 2.6 2.0 2.8 2.0 3.0 2.0 — — — —
18.0 1.9 1.5 2.3 1.8 2.6 2.0 2.8 2.0 3.0 2.0 — — — —
20.0 1.9 1.5 2.3 1.8 2.6 2.0 2.8 2.0 3.0 2.0 — — — —
21.0 — — 2.3 1.8 2.6 2.0 2.8 2.0 3.0 2.0 — — — —
VKM50 23.0 — — 2.3 1.8 2.6 2.0 2.8 2.0 3.0 2.0 3.3 2.1 — —
2.8kW
GA(M)V1 25.0 — — 2.3 1.8 2.6 2.0 2.8 2.0 3.0 2.0 3.3 2.0 — —
27.0 — — 2.3 1.8 2.6 2.0 2.8 2.0 3.0 2.0 3.2 2.0 — —
29.0 — — 2.3 1.8 2.6 2.0 2.8 2.0 3.0 2.0 3.2 2.0 — —
31.0 — — 2.3 1.8 2.6 2.0 2.8 2.0 3.0 2.0 3.1 2.0 — —
33.0 — — 2.3 1.8 2.6 2.0 2.8 2.0 3.0 2.0 3.1 2.0 3.1 1.8
35.0 — — — — 2.6 2.0 2.8 2.0 3.0 2.0 3.0 1.9 3.1 1.8
37.0 — — — — 2.6 2.0 2.8 2.0 2.9 2.0 3.0 1.9 3.0 1.8
39.0 — — — — 2.6 2.0 2.8 2.0 2.9 2.0 2.9 1.9 3.0 1.8
10.0 3.0 2.7 3.6 3.0 4.2 3.2 4.5 3.2 — — — — — —
12.0 3.0 2.7 3.6 3.0 4.2 3.2 4.5 3.2 — — — — — —
14.0 3.0 2.7 3.6 3.0 4.2 3.2 4.5 3.2 4.8 3.3 — — — —
16.0 3.0 2.7 3.6 3.0 4.2 3.2 4.5 3.2 4.8 3.2 — — — —
18.0 3.0 2.7 3.6 3.0 4.2 3.2 4.5 3.2 4.8 3.2 — — — —
20.0 3.0 2.7 3.6 3.0 4.2 3.2 4.5 3.2 4.8 3.2 — — — —
21.0 — — 3.6 3.0 4.2 3.2 4.5 3.2 4.8 3.2 — — — —
VKM80 23.0 — — 3.6 3.0 4.2 3.2 4.5 3.2 4.8 3.2 5.3 3.2 — —
GA(M)V1 4.5kW
25.0 — — 3.6 3.0 4.2 3.2 4.5 3.2 4.8 3.2 5.2 3.2 — —
27.0 — — 3.6 3.0 4.2 3.2 4.5 3.2 4.8 3.2 5.1 3.1 — —
29.0 — — 3.6 3.0 4.2 3.2 4.5 3.2 4.8 3.2 5.1 3.1 — —
31.0 — — 3.6 3.0 4.2 3.2 4.5 3.2 4.8 3.2 5.0 3.1 — —
33.0 — — 3.6 3.0 4.2 3.2 4.5 3.2 4.8 3.2 4.9 3.0 5.0 2.8
35.0 — — — — 4.2 3.2 4.5 3.2 4.7 3.2 4.8 3.0 4.9 2.8
37.0 — — — — 4.2 3.2 4.5 3.2 4.6 3.2 4.8 3.0 4.9 2.8
39.0 — — — — 4.2 3.2 4.5 3.2 4.6 3.2 4.7 2.9 4.9 2.7
10.0 3.9 3.2 4.5 3.6 5.2 4.0 5.6 4.0 — — — — — —
12.0 3.9 3.2 4.5 3.6 5.2 4.0 5.6 4.0 — — — — — —
14.0 3.9 3.2 4.5 3.6 5.2 4.0 5.6 4.0 6.0 4.0 — — — —
16.0 3.9 3.2 4.5 3.6 5.2 4.0 5.6 4.0 6.0 4.0 — — — —
18.0 3.9 3.2 4.5 3.6 5.2 4.0 5.6 4.0 6.0 4.0 — — — —
20.0 3.9 3.2 4.5 3.6 5.2 4.0 5.6 4.0 6.0 4.0 — — — —
21.0 — — 4.5 3.6 5.2 4.0 5.6 4.0 6.0 4.0 — — — —
VKM100 23.0 — — 4.5 3.6 5.2 4.0 5.6 4.0 6.0 4.0 — — — —
5.6kW
GA(M)V1 25.0 — — 4.5 3.6 5.2 4.0 5.6 4.0 6.0 4.0 6.5 4.0 — —
27.0 — — 4.5 3.6 5.2 4.0 5.6 4.0 6.0 4.0 6.4 4.0 — —
29.0 — — 4.5 3.6 5.2 4.0 5.6 4.0 6.0 4.0 6.3 3.9 — —
31.0 — — 4.5 3.6 5.2 4.0 5.6 4.0 6.0 4.0 6.2 3.9 — —
33.0 — — 4.5 3.6 5.2 4.0 5.6 4.0 6.0 4.0 6.1 3.8 6.3 3.6
35.0 — — — — 5.2 4.0 5.6 4.0 5.9 3.9 6.0 3.8 6.2 3.6
37.0 — — — — 5.2 4.0 5.6 4.0 5.8 3.9 5.9 3.7 6.1 3.5
39.0 — — — — 5.2 4.0 5.6 4.0 5.7 3.9 5.8 3.7 6.0 3.5
TC: Total capacity; kW
SHC: Sensible heat capacity; kW
Note: Cooling and heating capacities are based on the following conditions. Fan is based on High and Ultra-high. The figures in the
parenthesis indicate the heat reclaimed from the heat recovery ventilator. When calculating the capacity as indoor units, use
the following figures: VKM50GAMV1: 3.5kW VKM80GAMV1: 5.6kW VKM100GAMV1: 7.0kW

28 VKM-GA(M) series
ED71-440B Capacity Tables

11.2 Heating
Capacity Outdoor Coil inlet air temp. °CDB
MODEL DX-Coil
°CDB °CWB 16.0 18.0 20.0 21.0 22.0 24.0
Only
-14.7 -15.0 2.2 2.2 — — — —
-12.6 -13.0 2.3 2.3 — — — —
-10.5 -11.0 2.4 2.4 — — — —
-9.5 -10.0 2.5 2.4 — — — —
-8.5 -9.1 2.5 2.5 — — — —
-7.0 -7.6 2.6 2.6 2.7 — — —
-5.0 -5.6 2.7 2.7 2.7 — — —
VKM50 -3.0 -3.7 2.8 2.8 3.0 3.0 — —
GA(M)V1 2.8kW
0.0 -0.7 3.0 3.0 3.1 3.1 — —
3.0 2.2 3.1 3.1 3.2 3.1 3.0 —
5.0 4.1 3.3 3.2 3.2 3.1 3.0 —
7.0 6.0 3.4 3.4 3.2 3.1 3.0 —
9.0 7.9 3.5 3.4 3.2 3.1 3.0 —
11.0 9.8 3.6 3.4 3.2 3.1 3.0 2.8
13.0 11.8 3.6 3.4 3.2 3.1 3.0 2.8
15.0 13.7 3.6 3.4 3.2 3.1 3.0 2.8
-14.7 -15.0 3.4 3.4 — — — —
-12.6 -13.0 3.6 3.6 — — — —
-10.5 -11.0 3.7 3.7 — — — —
-9.5 -10.0 3.9 3.7 — — — —
-8.5 -9.1 3.9 3.9 — — — —
-7.0 -7.6 4.1 4.1 4.2 — — —
-5.0 -5.6 4.2 4.2 4.2 — — —
VKM80 -3.0 -3.7 4.4 4.4 4.7 4.6 — —
4.5kW
GA(M)V1 0.0 -0.7 4.7 4.7 4.9 4.9 — —
3.0 2.2 4.9 4.9 5.0 4.9 4.7 —
5.0 4.1 5.2 5.0 5.0 4.9 4.7 —
7.0 6.0 5.3 5.3 5.0 4.9 4.7 —
9.0 7.9 5.5 5.3 5.0 4.9 4.7 —
11.0 9.8 5.7 5.3 5.0 4.9 4.7 4.4
13.0 11.8 5.7 5.3 5.0 4.9 4.7 4.4
15.0 13.7 5.7 5.3 5.0 4.9 4.7 4.4
-14.7 -15.0 4.4 4.4 — — — —
-12.6 -13.0 4.6 4.6 — — — —
-10.5 -11.0 4.8 4.8 — — — —
-9.5 -10.0 5.0 4.8 — — — —
-8.5 -9.1 5.0 5.0 — — — —
-7.0 -7.6 5.2 5.3 — — — —
-5.0 -5.6 5.4 5.4 5.4 — — —
VKM100 -3.0 -3.7 5.6 5.6 6.0 — — —
GA(M)V1 5.6kW
0.0 -0.7 6.0 6.0 6.2 6.2 — —
3.0 2.2 6.2 6.2 6.4 6.2 6.0 —
5.0 4.1 6.6 6.4 6.4 6.2 6.0 —
7.0 6.0 6.8 6.8 6.4 6.2 6.0 —
9.0 7.9 7.0 6.8 6.4 6.2 6.0 —
11.0 9.8 7.2 6.8 6.4 6.2 6.0 5.6
13.0 11.8 7.2 6.8 6.4 6.2 6.0 5.6
15.0 13.7 7.2 6.8 6.4 6.2 6.0 5.6
Note: Cooling and heating capacities are based on the following conditions. Fan is based on High and Ultra-high. The figures in the
parenthesis indicate the heat reclaimed from the heat recovery ventilator. When calculating the capacity as indoor units, use
the following figures: VKM50GAMV1: 3.5kW VKM80GAMV1: 5.6kW VKM100GAMV1: 7.0kW

VKM-GA(M) series 29
Sound Level ED71-440B

12. Sound Level


12.1 Overall Sound Level
dB(A)
Ventilation Mode 220V/50Hz 230V/50Hz 240V/50Hz
Fan Speed U-H H L U-H H L U-H H L
VKM50GAMV1 37 35 32 37.5 35.5 33 38 36 34
VKM80GAMV1 38.5 36 33 39 37 34 40 37.5 35.5
VKM100GAMV1 39 37 34 39.5 37.5 34.5 40 38 35.5
Model
VKM50GAV1 38 36 33.5 38.5 36.5 34.5 39 37 35.5
VKM80GAV1 40 37.5 34.5 41 38 36 41.5 39 37
VKM100GAV1 40 38 35 40.5 38.5 36 41 39 36.5
4D051291 4D051297 4D051304
4D051292 4D051299 4D051305
4D051293 4D051300 4D051306
4D051294 4D051301 4D051307
4D051295 4D051302 4D051308
4D051296 4D051303 4D051309

1. Operation noise is measured in an anechoic chamber.


2. The operation noise level become greater than this value depending on the operation conditions,
reflected sound, and peripheral noise.
3. Operation noise differs with operation and ambient conditions.
4. U-H: Ultra-High, H: High, L: Low

Location of microphone

4D051291

30 VKM-GA(M) series
ED71-440B Sound Level

12.2 Octave Band Level


220V, 50Hz
VKM50GAMV1 VKM80GAMV1 VKM100GAMV1

4D051291 4D051292 4D051293

230V, 50Hz
VKM50GAMV1 VKM80GAMV1 VKM100GAMV1

4D051297 4D051299 4D051300

240V, 50Hz
VKM50GAMV1 VKM80GAMV1 VKM100GAMV1

4D051304 4D051305 4D051306

VKM-GA(M) series 31
Sound Level ED71-440B

220V, 50Hz
VKM50GAV1 VKM80GAV1 VKM100GAV1

4D051294 4D051295 4D051296

230V, 50Hz
VKM50GAV1 VKM80GAV1 VKM100GAV1

4D051301 4D051302 4D051303

240V, 50Hz
VKM50GAV1 VKM80GAV1 VKM100GAV1

4D051307 4D051308 4D051309

32 VKM-GA(M) series
ED71-440B Sound Level

12.3 Reducing Operating Sound


The air suction and discharge grille may give out operating sound higher by 8 to 11 phons than of the Heat Reclaim Ventilators
body.
When installing this unit in a quiet place, take measures to reduce operating sound.

12.3.1 Points for Reducing Operating Sound


1. Operating sound heard from the air discharge outlet can be reduced just by applying sound-insulating
material to the SA (indoor air supply) duct.
Heat Reclaim Ventilator Air suction /
discharge
EA RA grille

OA SA
Flexible duct
Apply sound-insulating
material to the SA duct.
(HC0054)

2. Operating sound can be reduced more effectively by applying sound-insulating material to a portion of
the SA duct near the unit body than that near the air suction / discharge grille.
Heat Reclaim Ventilator Air supply
and exhaust
EA RA grille

OA SA
Flexible duct
Apply sound-insulating
material here for effective
operating sound reduction. (HC0055)

12.3.2 Taking Measures to Reduce Operating Sound Heard from Attic-installed Equipment and Air
Ducts
1. When installing large air volume models (650 m3 / h or more), avoid the following wherever possible if it
is expected to be necessary to apply sound-insulating material to them. (Fig.1)

Fig. 1 (1) (4) (3) (2)

(HC0056)

(1)Making the duct diameter extremely small (Example: φ 250 → φ 150, φ 200 → φ 100)
(2)Making the duct extremely bent using bellows (in particular, connecting bellows to the air discharge
outlet of the unit body)
(3)Making opening holes on the ceiling
(4)Hanging the unit on a material which does not have enough hanging strength

2. Take the following sound reduction measures. (Fig.2)

Fig. 2 (1) (2)

(HC0057)

(1)Use a sound-insulating (low-permeability-to-sound) ceiling.

Note: Some sound-insulating ceilings are not very effective in reducing low-frequency element of the operating
sound.

(2)Place a sound-reducing material under the source of the operating sound.

Note: When using a sound-insulating sheet, it is necessary to have the entire body of the unit covered with it.
Note, however, that some models do not allow the use of a sound-insulating sheet because it may badly
affect the ventilation of their radiation heat.

VKM-GA(M) series 33
Sound Level ED71-440B

12.3.3 Reducing Operating Sound Heard from the Air Discharge Outlet (Suction Inlet)
1. Use the following recommended optional accessories to reduce operating sound heard from attic-
installed duct type models. (Fig.3)

Fig. 3 (1) (2) (3)

(HC0058)

(1) Sound-eliminating box (Silencer)


(2) Flexible duct
(3) Sound-eliminating air suction / discharge grille

2. If the above accessories do not give satisfactory effect or when an attic-installed cassette type model is
used, take the following measure.

Fig. 4

(1)
(HC0059)

(1) Apply a sound-absorbing material to the interior of the room.

3. To reduce the air flow sound heard from the air discharge outlet (suction inlet) of an attic-installed duct
type model, use a small diameter flexible duct, which excels in sound absorptivity, for greater sound
reduction effect.
(1) Branched duct (for letting air flow through two ducts to slow down its speed before it reaches the air
discharge outlets (suction inlets))

Fig. 5 (1) (2)

(HC0060)

(2) Flexible duct

4. Installation of the unit with the source of its operating sound located at a corner of a room will be a
partially effective sound reduction measure; it will keep persons in the center of the room free from the
annoying operating sound, with those in the corner of the room kept annoyed by the operating sound.
To avoid this, try to find the best installation place from which the operating sound is least heard by
everyone in the room.

12.3.4 Effect of Remedy for Sound


Caution
1. Be sure to connect a flexible duct (2 m) to an outlet of the main body in the indoor air supply side.
2. Do not connect a spiral duct and an aluminium bellows directly to the outlet of the main body.
* A silencer is effective especially when using the flexible duct at the same time.

34 VKM-GA(M) series
ED71-440B Sound Level

12.3.5 General Comparison of the Effect ((1) → (6) in more Effective Order)
(1) Mounting a silencer + flexible duct 2 m long (2) Mounting a flexible duct (3) Mounting a flexible duct
Mounting a silencer + flexible duct 6 m long 6 m long 2 m long to the main body

Main body Main body Main body Main body

Silencer Silencer
Flexible duct 2 m

Flexible duct 2 m Flexible duct 6 m


Flexible duct 6 m
Spiral duct 4 m Spiral duct 4 m

Effect of a remedy for noise does not change


even for over 2 m long duct

(4) Mounting a flexible duct (5) Mounting a silencer (6) Spiral duct 6 m
2 m long to an air suction No measures taken (1) (2) (3) (4) (5) (6)
discharge grille
(dB)

+ 10
Main body Main body Main body

Silencer +5
Spiral duct 4 m

Spiral duct 6 m

Spiral duct 6 m Catalog


value
Flexible duct 2 m

Suction /
discharge grille –5

(HC0061)

Note: Measure the noise at 1.5 m below the air supply grille. Operating noise conforms to JIS standard and the
value is converted in terms of the anechoic chamber.

12.3.6 Nameplate for Note


“Notes for duct work” is written on the Heat Reclaim Ventilators as indicated below.
• When connecting a spiral duct or an aluminum bellows, sound at the air discharge outlet is higher by
8~11 phon than the main body operating sound.
• When using this unit in a quiet place, take a remedy for sound by connecting an optional flexible duct at
the outlet of the indoor air suction side of the main body.

VKM-GA(M) series 35
Optional Accessories ED71-440B

13. Optional Accessories


13.1 Installation of Optional Accessories (For VKM50GA (M) V1, VKM80GA (M) V1,
VKM100GA (M) V1)
Air suction/discharge grille (Option)

Flexible duct
(Option)
RA
High efficiency filter
(Option)
SA

Round hood
Branch duct (Field supply)
(Field supply)

SA Silencer (Option)
Duct
(Field supply)

Thermal insulation material (Field supply)


EA
OA

13.2 Optional Accessories


Applicable model VKM50/80/100GA(M)V1
Item
Remote controller BRC1E61/BRC1C62//BRC1D61 *1
Residential central remote controller DCS303A51 *2
Centralized Central remote controller DCS302CA61
control
equipment Unified ON/OFF controller DCS301BA61
Schedule timer DST301BA61
Controlling device

Wiring adaptor for electrical KRP2A61


appendices
For humidifier running ON signal output KRP50-2
PC Board Adaptor

For heater control kit BRP4A50

Type FXLQ-MA
For wiring (indoor unit of VRV) FXFQ-P FXZQ-M FXCQ-M FXKQ-MA FXDQ-PB FXMQ-P FXMQ-MA FXHQ-MA FXAQ-MA FXNQ-MA FXUQ-MA
FXDQ-NB
KRP1C63 KRP1BA57 KRP1B61 KRP1B61 KRP1B56 KRP1C64 KRP1B61 KRP1BA54 — KRP1B61 —
Installation box for adaptor PCB Notes 2, 3 Notes 4, 6 Notes 2, 3 — Notes 4, 6 Note 2, 3 — Note 3 Notes 2, 3 — KRP1BA97
KRP1H98 KRP1BA101 KRP1B96 KRP1BA101 KRP4A96 KRP1CA93 KRP4AA93
Notes:1. Installation box is necessary for each adaptor marked . 6. Installation box is necessary for each adaptor.
2. Up to 2 adaptors can be fixed for each installation box. 7. *1 Necessary when operating a Heat Reclaim Ventilator (VKM) independently. When operating interlocked
3. Only one installation box can be installed for each indoor unit. with other air conditioners, use the remote controllers of the air conditioners.
4. Up to 2 installation boxes can be installed for each indoor unit. *2 For residential use only. When connected with a Heat Reclaim Ventilator (VKM), you can only switch the
5. Installation box is necessary for second adaptor. power ON/OFF. Cannot be used with other centralised control equipment.

Applicable model VKM50GA(M)V1 VKM80GA(M)V1 VKM100GA(M)V1


Item
— KDDM24B100
Additional function

Silencer
Nominal pipe diameter mm — 250 mm
Air suction/ White K-DGL200B K-DGL250B
discharge grille Nominal pipe diameter mm 200 250
High efficiency filter KAF242H80M KAF242H100M
Air filter for replacement KAF241G80M KAF241G100M
Flexible duct (1 m) K-FDS201D K-FDS251D
Flexible duct (2 m) K-FDS202D K-FDS252D
Drawing No. C: 3D051318B

Remote controller Central remote controller Unified ON/OFF controller Schedule timer

Air suction/discharge grille Flexible duct


Silencer (Noise suppression type) (Noise suppression type)

36 VKM-GA(M) series
ED71-440B Standard Drawing for Installation

14. Standard Drawing for Installation


VKM50GAMV1
Unit (mm)

3D051319A

VKM-GA(M) series 37
Standard Drawing for Installation ED71-440B

VKM80GAMV1
Unit (mm)

3D051320A

38 VKM-GA(M) series
ED71-440B Standard Drawing for Installation

VKM100GAMV1
Unit (mm)

3D051321A

VKM-GA(M) series 39
Standard Drawing for Installation ED71-440B

VKM50GAV1
Unit (mm)

3D051322

40 VKM-GA(M) series
ED71-440B Standard Drawing for Installation

VKM80GAV1
Unit (mm)

3D051323

VKM-GA(M) series 41
Standard Drawing for Installation ED71-440B

VKM100GAV1
Unit (mm)

3D051324

42 VKM-GA(M) series
ED71-440B Operation

15. Operation

MODELS VKM50GAMV1 VKM80GAMV1 VKM100GAMV1


VKM50GAV1 VKM80GAV1 VKM100GAV1

(1) Hanger bracket

(7) Maintenance cover

(8) Heat exchanger elements


(3) Exhaust fan
It exchanges the heat (temperature and humidity)
(2) Duct connecting flange from indoors with the air taken in from outdoors,
changes the outside air to the same condition as
indoors and then brings it indoors.

(6) Electric parts box

(12) Gas pipe

(13) Liquid pipe

(5) Damper

(4) Air filter (Long life filter) (16) Strainer (included)


<VKM-GAMV1 series only>
(14) Drain outlet
(10) Air supply fan
(19) Remote controller (Optional accessory)

(9) Name plate


(15) Humidifier (Natural evaporating type)
<VKM-GAMV1 series only>
(11) Direct expansion coil

Important
Sometimes when first using the unit, the
smell of the heat exchanging element may
be noticeable, but it is not harmful. The smell
will gradually go away as the unit is used.

(11) Direct expansion coil


(17) Feed water tank
(20) Damper motor <VKM-GAMV1 series only>

(23) RA
(21) EA Return air
Exhaust air from room
to outdoors

(24) SA
Supply air
(22) OA to room
Fresh air
from outdoors
(outdoor air)
(18) Solenoid valve
<VKM-GAMV1 series only>

(15) Humidifier (Natural evaporating type)


<VKM-GAMV1 series only>

1
[1]

3P130767-3G

VKM-GA(M) series 43
Operation ED71-440B

• Combined operation system


with VRV systems
Heat Reclaim Ventilator
Indoor unit -With DX Coil-

Remote controller
for indoor unit

Outdoor unit
• Independent system
Heat Reclaim Ventilator
-With DX Coil-

Outdoor unit

Remote controller Remote controller for VRV BRC1A62


for indoor unit

2 3

Remote controller for VKM BRC1D527 (EU only)

4 3

4 4

UNIT No.

GROUP

1 1

2
3

Remote controller for VRV BRC1A62 Remote controller for VKM BRC1D527 (EU only)

5 5
[2]

C: 3P130767-3G

44 VKM-GA(M) series
ED71-440B Operation

UNIT No.

GROUP

1,2,3 1,2,3

Remote controller for VRV BRC1A62 Remote controller for VKM BRC1D527 (EU only)

6 6

UNIT No.

GROUP

1,2,4

1 7,8
3 3,5 6
2

Remote controller for VRV BRC1A62 Remote controller for VKM BRC1D527 (EU only)

7 7

(1) Air filter

8-1 8-2

9 10

(1) Heat exchanger


element (×2)

(2) Handle

(3) Rail

11 12

[3]

3P130767-3G

VKM-GA(M) series 45
Operation ED71-440B

With DX coil & Humidifier With DX coil


VKM50GAMV1 VKM50GAV1 Operation
VKM80GAMV1 VKM80GAV1 Heat Reclaim Ventilator-with DX Coil-
manual
VKM100GAMV1 VKM100GAV1

• Do not wash the Heat Reclaim Ventilator with water.


CONTENTS Electric shock or fire may result. (Not including air filters,
ILLUSTRATIONS................................................... [1][2][3] etc.)
1 SAFETY CAUTIONS ....................................................... 1 • Be sure to stop the unit and turn off the power when
2 WHAT TO DO BEFORE OPERATION............................. 3 cleaning or inspecting it.
3 OPERATION PROCEDURE............................................ 7 As the fan is rotating at high speed, it will cause injury.
4 MAINTENANCE (for a qualified service person only) ... 11 • Never inspect or service the unit by yourself.
5 TROUBLE SHOOTING.................................................. 12 Ask a qualified service person to perform this work. (The
qualified service person)
Important information regarding the refrig-
• Keep all flames away if the refrigerant leaks.
erant used The refrigerant in the air conditioner is safe and normally
This product contains fluorinated greenhouse gases covered by does not leak. If the refrigerant leaks inside the room, the
the Kyoto Protocol. contact with a fire of a burner, a heater or a cooker may
result in a harmful gas. Extinguish all flames from burning
Refrigerant type: R410A
(1)
appliances (such as stoves, heaters, etc.) ventilate the
GWP value: 1975 room, and contact your dealer. Do not use the air condi-
(1)
GWP = global warming potential tioner until when a service person confirms to finish repair-
ing the portion where the refrigerant leaks.
Periodical inspections for refrigerant leaks may be required
depending on European or local legislation. Please contact your • Consult the dealer if the air conditioner submerges
local dealer for more information. owing to a natural disaster, such as a flood or typhoon.
Do not operate the air conditioner in that case, or otherwise
1 SAFETY CAUTIONS a malfunction, electric shock, or fire may result.

Read the following cautions carefully and use your equipment


properly. CAUTION (During Operation)
This unit comes under the term “appliances not accessible to • Do not use the Heat Reclaim Ventilator for other pur-
the genetic public.” poses.
There are two kinds of safety cautions and tips listed here as fol- In order to avoid any quality deterioration, do not use the
lows: unit for cooling precision instruments, food, plants, animals
or works of art.
WARNING............... Improper handling can lead to such
• Do not use burning appliances directly in the path of the
serious consequences as death or
air from the unit.
severe injury.
Incomplete combustion of the burning appliances may
CAUTION................ Improper handling can lead to injury or occur.
damage. It could also have serious • Never expose little children, plants or animals directly
consequences under certain condi- to the air flow.
tions. Adverse influence to little children, animals and plants may
result.
NOTE
• Neither place a flammable spray bottle near the Heat
• These instructions will ensure proper use of the equipment.
Reclaim Ventilator or indoor intake and outlet grills nor
Be sure to follow these important safety cautions.
perform spraying.
Keep these warning sheets handy so that you can refer to
Doing so may result in a fire.
them if needed.
Also, if this equipment is transferred to a new user, make sure • Turn off the power when the unit is not to be used for
to hand over this user’s manual to the new user. long periods of time.
Otherwise, the unit may get hot or catch on fire due to dust
WARNING (During Operation) accumulation.
• When the unit is in abnormal conditions (smell of some- • Do not block the intake or outlet grills.
thing burning, etc.), cut off the power, and contact your If the fan does not blow air throughout the entire room, it
dealer. may cause oxygen deficiency leading to bad health condi-
Continued operation under such circumstances may result tion or long-term health problems.
in a failure, electric shock, and fire. • Use gloves when cleaning.
• It is not good for your health to expose your body to the Cleaning without gloves may cause injury.
air flow for a long time. • Do not operate the remote controller with wet hands.
• Do not operate the unit with a wet hand. This may cause electric shock.
An electric shock may result. • Never touch the internal parts of the controller.
• Open the windows and ventilate the room if flammable An electric shock or a machine trouble may happen. For
gas is leaked. checking and adjusting the internal parts, contact your
Insufficient ventilation when the unit is turned on or off may dealer.
cause an explosion from sparks at the electrical connection.

1 English

C: 3P130767-3G

46 VKM-GA(M) series
ED71-440B Operation

• Do not place objects in direct proximity of the outdoor • For refrigerant leakage, consult your dealer.
unit and do not let leaves and other debris accumulate When the Heat Reclaim Ventilator is to be installed in a
around the unit. small room, it is necessary to take proper measures so that
Leaves are a hotbed for small animals which can enter the the amount of any leaked refrigerant does not exceed the
unit. Once in the unit, such animals can cause malfunctions, limiting concentration even when it leaks. If the refrigerant
smoke or fire when making contact with electrical parts. leaks exceeding the level of limiting concentration, an oxy-
• Watch your steps at the time of air filter cleaning or gen deficiency accident may happen.
inspection. • Do not install the Heat Reclaim Ventilator at any place
High-place work is required, to which utmost attention must where flammable gas may leak out.
be paid. If the gas leaks out and stays around the unit, a fire may
If the scaffold is unstable, you may fall or topple down, thus break out.
causing injury. • Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in elec-
WARNING (For installation) tric shocks, or fire.

• Do not attempt to install the unit yourself.


Ask your dealer for installation of the unit. CAUTION (For installation)
Incomplete installation performed by yourself may result in a • Do not use the Heat Reclaim Ventilator or an air suction/
water leakage, electric shock, and fire. discharge grille in the following places.
• Installation should be done following the installation a. Place subjected to high temperature or direct flame.
manual. Avoid a place where the temperature near the Heat
Incorrect installation may cause leaking, electric shock, or Reclaim Ventilator and the air suction/discharge air grille
fire. Injuries may result if the unit falls. exceeds 40°C. If the unit is used at high temperature,
deformed air filter and heat exchange element or burned
• Do not install the unit in locations where the tempera- motor result.
ture in the areas around the unit or indoor intake and b. Place such as kitchens or other places where oil
outlet grills may fall below freezing. fumes are present.
<VKM-GAMV1 series only>
This may cause fire.
The water of the water pipes, humidifier element, solenoid c. Place such as machinery plant and chemical plant
valves, and other components may freeze, causing break- where gas, which contains noxius gas or corrosive
age and leaks. components of materials such as acid, alkali, organic
• Do not allow exhaust air to enter the outside air intake solvent and paint, is generated.
vent. Place where combustible gas leakage is likely.
This may cause the interior of the room to become contami- This may cause gas poisoning or fires.
nated and harming the health. d. Place such as bathroom subjected to moisture.
• Locate the outside air intake vent so that it does not Electric leak or electric shock and other failure can be caused.
take in exhaust air which contains combustion air, etc. e. Locations below freezing point.
Incorrect installation may cause a loss of oxygen in the <VKM-GAMV1 series only>
room, leading to serious accidents. Using the unit at temperatures below 0°C may cause the
drain pan the supply and discharge piping, the humidifying
• All wiring must be performed by an authorized electri- element, the solenoid valves, and other parts to freeze,
cian. which can cause accidents.
To do wiring, ask your dealer. Never do it yourself. f. Near machinery emitting electromagnetic waves.
• Make sure that a separate power supply circuit is pro- Electromagnetic waves may disturb the operation of the
vided for this unit and that all electrical work is carried control system and result in a malfunction of the equip-
out by qualified personnel according to local lows and ment.
regulations. g. Place subjected to much carbon black.
Insufficient power circuit capacity or incorrect work may Carbon black attaches to air filter and heat exchange ele-
cause electric shock or fires. ment, marking them unable to use.
• Be sure to establish an earth. • Is a snow protection measure taken?
Do not earth the unit to a utility pipe, arrester, or tele- For detail, consult your dealer.
phone earth. • Make sure the temperature and the humidity of the
Incomplete earth may cause electrical shock, or fire. installation location is within the usage range, not
A high surge current from lightning or other sources may exceed the limit.
cause damage to the air conditioner. Do not install in cold storage or other locations with low tem-
• Install the unit on a foundation strong enough to with- peratures or near heated pools. This may cause electrical
stand the weight of the unit. shock and fire.
A foundation of in sufficient strongth may result in the unit • Install the two outdoor ducts with down slope to pre-
falling and causing injuries. vent rainwater from entering the unit.
• Connect the remote controller to the correct model. If this is not done completely, water may enter the building,
This may cause electric shock or fire. damaging furniture, and cause electric shock and fire.
• Do not connect additional electric wirings. • Insulate the two outdoor ducts to prevent dew conden-
This may cause fire. sation (and the indoor duct as well if needed).
If this is not done completely, water may enter the building,
damaging furniture, etc.

English 2

C: 3P130767-3G

VKM-GA(M) series 47
Operation ED71-440B

• Use electric insulation between the duct and the wall • Are any obstructions near the outlet vent of the outdoor
when using metal ducts to pass metal or wire laths or unit?
metal plating into wooden buildings. They may reduce the function and increase the operating
This may cause electric shock and fire. noise.
• Arrange the drain hose to ensure smooth drainage. • If any abnormal noise is heard during the operation, con-
Incomplete drainage may cause wetting of the building, fur- tact your dealer.
niture etc. „ CHECK LIST ABOUT DRAIN PIPING AND WATER
• Avoid placing the controller in a spot splashed with SUPPLY WORK
water. • Make sure the drain works properly.
Water coming inside the controller may cause an electric During cooling operation, no drainage from the outdoor drain
leak or may damage the internal electronic parts. piping may clog the drain piping with dirt or dust, causing
water leakage from the indoor unit.
(For moving and reinstalling/ Stop the unit operation, and contact your dealer.
WARNING repairing)
• Do not modify the unit. 2 WHAT TO DO BEFORE OPERATION
This may cause electric shock or fire.
This operation manual is for the following systems with stan-
• Ask your dealer to move and reinstall the unit. dard control. Before initiating operation, contact your Daikin
Incomplete installation may result in a water leakage, elec- dealer for the operation that corresponds to your system type
tric shock, and fire. and mark.
• Do not disassemble or repair the unit yourself. If your installation has a customized control system, ask your
This may cause electric shock or fire. dealer for the operation that corresponds to your system.
Contact your dealer to have such work done. 2.1 NAMES OF PARTS (Refer to figure 1)
• When removing the unit, be sure not to tip it. (1) Hanger bracket
The water inside the unit may drip or leak out, and get on (2) Duct connecting flange
furniture, etc.
(3) Exhaust fan
• Do not move or attempt to re-install the remote control- (4) Air filter (Long life filter)
ler yourself. (5) Damper
Incorrect installation, may cause electric shock or fire. Con- (6) Electric parts box
tact your dealer to have such work done.
(7) Maintenance cover
¢CHECK LIST EXCEPT SAFETY CAUTION² (8) Heat exchanger elements
The items described below should be checked and ask your (9) Name plate
dealer when you feel uncertain or you can’t check by yourself. (10) Air supply fan
„ CHECK LIST ABOUT SELECTING INSTALLATION (11) Direct expansion coil
SITE (12) Gas pipe
• Is the outdoor unit installed in a well-ventilated location (13) Liquid pipe
with no obstructions in its vicinity? (14) Drain outlet
• Do not use in the locations described below. (15) Humidifier (Natural evaporating type)
a. Locations with mineral oil such as cutting oil in the atmo- <VKM-GAMV1 series only>
sphere. (16) Strainer (included) <VKM-GAMV1 series only>
b. Locations with salt in the air, such as coastal areas. (17) Feed water tank <VKM-GAMV1 series only>
c. Locations with sulfide gas in the air, such as hot springs. (18) Solenoid valve <VKM-GAMV1 series only>
d. Locations where voltage fluctuates, such as factory. (19) Remote controller (Optional accessory)
e. In automobiles or marine vessels. (20) Damper motor
f. Locations containing steam in the atmosphere or splat- (21) EA Exhaust air to outdoors
tered oil, such as kitchen.
(22) OA Fresh air from outdoors
g. Locations with mechanical equipment generating electro-
(23) RA Return air from room
magnetic wave.
h. Locations enveloped in acidic or alkaline steam. (24) SA Supply air to room
• Has any action for snow protection been taken?
Contact your Daikin dealer for details.
2.2 REMOTE CONTROLLER AND CHANGEOVER
SWITCH: NAME AND FUNCTION OF EACH
„ CHECK LIST ABOUT ELECTRIC WIRING WORK SWITCH AND DISPLAY
• All wiring must be performed by an authorized electrician. (Refer to figure 3 and 4)
Do not conduct the work yourself. Contact your dealer.
• Only the items marked with an asterisk ( mark) are expla-
• Electrical wiring must be done according to the local nation relating to the functions and display of the unit.
standards. Unmarked items are functions of the combined air condition-
• Is the circuit specific to air conditioner? ers. When using buttons for functions which are not avail-
„ CHECK LIST CORRESPONDING TO OPERATING able (buttons which are not described in the text) will cause
NOISE “NOT AVAILABLE” to be displayed.
• Is the unit installed at the following locations? Contact your dealer for more detailed descriptions of those
a. Location strong enough to support the weight of the unit, functions (buttons).
and which will not amplify noise or vibration. 1 On/off button
b. Location where the warm air and the noise from the outlet Press the button and the system will start. Press the button
vent of the outdoor unit will not bother neighbors. again and the system will stop.

3 English

3P130767-3G

48 VKM-GA(M) series
ED71-440B Operation

2 Operation lamp (red) 18 Temperature setting button


The lamp lights up during operation or blinks if a malfunc- Use this button for setting the desired temperature of air
tion occurs. conditioner combined with this unit.
3 Display “ ” (changeover under control) This button can’t use for this unit.
May be displayed when combined with a VRV-system air This unit can’t change temperature setting.
conditioner. 19 Filter sign reset button
It is impossible to changeover heat/cool with the remote Refer to “4.1 HOW TO CLEAN THE AIR FILTER”.
controller when this icon is displayed. 20 Fan speed control button
4 Display “ ” (air flow flap) Press this button to select the fan speed of air conditioner
This displays the direction and mode of the air flow flap of combined with this unit.
the combined air conditioner. 21 Operation mode selector button
5 Display “ ” (ventilation/air cleaning) Press this button to select the operation mode of air condi-
This display shows that the total heat exchange and the air tioner combined with this unit.
cleaning unit are in operation. (these are optional accessories) 22 Air flow direction adjust button
6 Display “ C ” (set temperature) Press this button to select the air flow direction of air con-
This displays the set temperature of the combined air con- ditioner combined with this unit.
ditioner. 23 Fan only/air conditioning selector switch
It is not displayed when the unit is used as an independent Set the switch to “ ” for fan only operation or to “ ”
system. for heating or cooling operation.
7 Display “ ”“ ”“ ”“ ”“ ” (operation 24 Cool/heat changeover switch
mode: “FAN, DRY, AUTOMATIC, COOLING, HEATING”) Set the switch to “ ” for cooling or to “ ” for heating
This displays the operating status of the combined air con- operation.
ditioner.
• There is no “heating” for the VRVII system (Cooling only 25 Remote controller thermo
type). This detects the temperature around the remote controller.
• “ ” is only available for systems operating in cooling This is not the same as the temperature of return air from
and heating at the same time. room (RA) by heat exchanger unit.
8 Display “ ” (programmed time) 26 Display “NOT AVAILABLE”
This display shows the programmed time of the system • “NOT AVAILABLE” may be displayed for a few seconds if
start or stop. the function for the button pressed is not available for the
unit or the air conditioner.
9 Display “ TEST ” (inspection/test operation) • “NOT AVAILABLE” is only displayed when none of the
When the inspection/test operation button is pressed, the indoor units is equipped with the function in question when
display shows the mode in which the system actually is. running several units simultaneously. It is not displayed if
• Do not use under usual use (service person/installer only). the function is available on even one of the units.
10 Display “ ” (under centralized control) 27 Display “ ”“ ”“ ”
When this display shows, the system is under centralized This displays the ventilation mode. (BRC1D527 and so
control. (This is not a standard specification.) on.) (This is not displayed on the controller BRC1A62)
11 Display “ ” (fan speed) 28 Ventilation mode selector button (available only con-
This display shows the fan speed you have selected. necting the Heat Reclaim Ventilator)
This is only displayed when the fan speed selection but- This is pressed to switch the ventilation mode of the Heat
ton is pressed. It normally displays the set fan strength of Reclaim Ventilator.
the combined air conditioner. 29 Ventilation fan speed control button (available only
12 Display “ ” (time to clean air filter) connecting the Heat Reclaim Ventilator)
Refer to “4.1 HOW TO CLEAN THE AIR FILTER”. This is pressed to control the fan speed of the Heat
Reclaim Ventilator.
13 Display “ ” (defrost/hot start) (Refer to item 11)
It may be displayed when freezing of outdoor unit’s coil
30 LEAVE HOME ICON “ ”
increases in heating mode.
The leave home icon shows the status of the leave home
14 Timer mode start/stop button function.
Refer to the chapter “Operation procedure -
Programming start and stop of the system with timer.” ON Leave home is enabled
(Refer to page 9 (3.3)) FLASHING Leave home is active
15 Timer on/off button OFF Leave home is disabled
Refer to the chapter “Operation procedure -
Programming start and stop of the system with timer.” 31 DAY OF THE WEEK INDICATOR “ ”
(Refer to page 9 (3.3)) The day of the week indicator shows the current week day
(or the set day when reading or programming the schedule
16 Inspection/test operation button timer).
Pressed during inspection or “test run.”
32 CLOCK DISPLAY “ ”
• Do not use under usual use. (service person/installer only) The clock display indicates the current time (or the action
17 Programming time button time when reading or programming the schedule timer).
Use this button for programming start and/or stop time. 33 MAXIMUM SET TEMPERATURE “ ”
The maximum set temperature indicates the maximum set
temperature when in limit operation.

English 4

C: 3P130767-3G

VKM-GA(M) series 49
Operation ED71-440B

34 MINIMUM SET TEMPERATURE “ ” Refer to “3 OPERATION PROCEDURE”.


The minimum set temperature indicates the minimum set During intermediate periods when only the Heat Reclaim Venti-
temperature when in limit operation. lator is used without the air conditioner, select “ventilation” with
35 SCHEDULE TIMER ICON “ ” the operation selection button.(Refer to 2.4)
This icon indicates that the schedule timer is enabled. Sample system (Refer to figure 2)
Independent system
36 ACTION ICONS “ ” [Operation]
These icons indicate the actions for each day of the sched- The Heat Reclaim Ventilator can be started and stopped using the
ule timer. remote controller.
37 OFF ICON “ ” You can also select the ventilation amount and the ventilation mode.
This icon indicates that the OFF action is selected when Refer to “3 OPERATION PROCEDURE”.
programming the schedule timer.
NOTE
38 ELEMENT CLEANING TIME ICON “ ”
This icon indicates the element must be cleaned • This unit cannot control room temperature. If this is needed,
( “Heat Reclaim Ventilator” only). do not install the Heat Reclaim Ventilator alone, but rather
install another indoor unit.
39 PROGRAMMING BUTTON “ ”
This button is a multi-purpose button.
Depending on the previous manipulations of the user, the 2.4 ABOUT DIRECT DUCT CONNECTION SYSTEM
programming button can have various functions. Installation Examples
40 SCHEDULE TIMER BUTTON “ ” Direct duct connection system
This button enables or disables the schedule timer.
41 OPERATION CHANGE/ BUTTON “ ”
This button is a multi-purpose button. Depending on the
previous manipulations of the user, it can have following
functions:
1 select the operation mode of the installation (FAN, (HC0007)
DRY, AUTOMATIC, COOLING, HEATING) NOTE) • The system must be operated interlocking
2 toggle between minimum temperature and maximum with the air conditioner.
temperature when in limit operation • Do not connect to the outlet side of the indoor unit.
Independent duct system
42 SETPOINT/LIMIT BUTTON “ ”
This button toggles between setpoint, limit operation or
(programming mode only).
NOTE
• In contradistinction to actual operating situations, the display
on figure 3 shows all possible indications. (HC0008)
• If the filter sign lamp lights up, clean the air filter as explained in
the chapter “MAINTENANCE”. After cleaning and reinstalling The Heat Reclaim Ventilator cannot be operated indepen-
the air filter: press the filter sign reset button on the remote con- dently when the air conditioner is connected to the Heat
troller. The filter sign lamp on the display will go out. Reclaim Ventilator via a duct. When using the Heat
• Item 27~ Item 42 can be used with BRC1D527. Reclaim Ventilator, set the air conditioner to “fan” mode
In detail, refer to operation manual of the remote controller. on weak fan strength.
• Only the items marked with an asterisk ( mark) are explanation Operation mode display
relating to the functions and display of the unit. “Ventilation” is displayed.
Unmarked items are functions of the combined air conditioners.
2.3 EXPLANATION FOR SYSTEMS
Operation mode
This unit can be made a part of two different systems: as selector button
part of the combined operation system used together with
VRVII SYSTEM Air Conditioners and as the independent
system using only the Heat Reclaim Ventilator. An operat-
ing remote controller is required when using the unit as an
independent system.
Ask your dealer what kind of system your system is set up
for before operation.
For the operation of the remote controller for indoor unit
and centralized controller, refer to the instruction manual
provided with each unit. Remote controller
for indoor unit
See the included operating manuals for details on how to
operate each remote control. • Each time you press the operation selection button, the
„ OPERATION for EACH SYSTEM operation mode display will change as shown in the figure
Sample system (Refer to figure 2) below.
Combined operation system with VRVII systems
[Operation]
The air conditioner remote controller starts and stops the air
conditioner and the Heat Reclaim Ventilator.
You can also select the ventilation amount and the ventilation mode.

5 English

C: 3P130767-3G

50 VKM-GA(M) series
ED71-440B Operation

Example 1: Example 2:
In case of the remote controller “BRC1D527” and as equiva- In case of the remote controller “BRC1A62”
lent. Display changes as below.
Display changes as below.
When air conditioner and
When air conditioner and Heat Reclaim Ventilator
Heat Reclaim Ventilator are not connected via duct
are not connected via duct

<Operation mode>
<Operation mode>
VRV:
VRV: Cooling mode
Cooling mode Heat Reclaim Ventilator:
Heat Reclaim Ventilator: Heat exchange mode
Heat exchange mode

VRV:
VRV: Fan mode
Fan mode Heat Reclaim Ventilator:
Heat Reclaim Ventilator: Heat exchange mode
Heat exchange mode

VRV:
VRV: Stopping
Stopping Heat Reclaim Ventilator:
Heat Reclaim Ventilator: Heat exchange mode
Heat exchange mode

When air conditioner and


When air conditioner and Heat Reclaim Ventilator
Heat Reclaim Ventilator are connected via duct
are connected via duct

<Operation mode>
<Operation mode>
VRV:
VRV: Cooling mode
Cooling mode Heat Reclaim Ventilator:
Heat Reclaim Ventilator: Heat exchange mode
Heat exchange mode

VRV:
VRV: Fan mode
Fan mode Heat Reclaim Ventilator:
Heat Reclaim Ventilator: Heat exchange mode
Heat exchange mode

NOTE) Current Ventilation mode doesn’t be displayed.


NOTE) Current Ventilation mode can be visible and
selected on the remote controller. • When the display shows “ ” (time to clean air filter), ask a
qualified service person to clean the filters (Refer to the
chapter “MAINTENANCE”).

English 6

C: 3P130767-3G

VKM-GA(M) series 51
Operation ED71-440B

2.5 NIGHTTIME FREE COOLING OPERATION NOTE


¢AUTOMATIC HEAT PORGE FUNCTION AT NIGHT²
• “ ” can only be set for systems operating in cooling and
The nighttime free cooling is an energy-conserving function
which works at night when the air conditioners is off, reducing heating at the same time.
the cooling load in the morning when the air conditioner is “ ” is displayed on all remote controllers when
turned on by ventilating rooms which contain office equipment using the VRV,, system cooling only type, but only “ ” and
which raises the room temperature.
“ ” can be set.
• Nighttime free cooling only works during cooling and when
• Select the operating mode on a remote controller on which
connected to Building Multi or VRV systems.
• Nighttime free cooling is set to “off” in the factory settings; so “ ” is not displayed.
request your dealer to turn it on if you intend to use it. “ ”“ ” and “ ” (only for simultaneous cooling/heat-
ing systems) cannot be selected on remote controllers on
Operation image which it is displayed.
See 3.2 if “ ” is displayed.
Operating state Temperature (˚C)

40
(a) 2 Press ventilation mode selector button if you wish to
change the mode.
30 The display rotates through the following selections
every time the button is pressed.
(c)
20 (b)

OFF ON OFF
Nighttime free cooling operation
(e)

Automatic mode Heat exchange mode Bypass mode

OFF
(d)

22:00 24:00 (time)


NOTE
Following morning
• Above is available only if the remote controller BRC1D527 is
(a) Outside temperature connected with this unit.
It is unnecessary to change ventilation mode because the
(b) Indoor temperature mode is already set to “automatic mode”.
(c) Set temperature • If you change this mode with BRC1A62, consult your dealer.
(d) Operating state of Air conditioner 3 Press ventilation fan speed button if you wish to change
(e) Operating state of Total heat exchanger the fan speed.
The display rotates through the following selections
every time the button is pressed.
„ EXPLANATION OF NIGHTTIME FREE COOLING
OPERATION IMAGE Low High
The unit compares the indoor and outdoor temperatures after L H
the air conditioning operation stops for the night. If the following
After the selection, the ventilation fan speed display dis-
conditions are satisfied, the operation starts, and when the
appears.
indoor temperature reaches the air conditioning setting, the
And the fan speed of the combined air conditioner regu-
operation stops.
larly displays.
<Conditions>
[1] the indoor temperature is higher than the air conditioning NOTE
setting and • Above is available only if the remote controller BRC1D527 is
[2] the outdoor temperature is lower than the indoor tempera- connected with this unit.
ture, • It is unnecessary to change four speed mode because the
If the above conditions are not satisfied, reevaluation is made mode is already set to “Low” or “High” mode by the installer.
every 60 minutes.
• If you want to know or change this mode with BRC1A62 con-
sult your dealer.
3 OPERATION PROCEDURE
4 Press the on/off button.
3.1 COOLING, HEATING, AND FAN ONLY OPERA- The operation lamp lights up and the system starts oper-
TION (Refer to figure 5) ation.
[PREPARATIONS] Stopping the system
• To protect the unit, turn on the main power switch 6 hours Press start/stop one more time. The operation lamp will go off.
before operation. The unit will stop.
Do not turn off the power during the heating or cooling sea- • After stopping operation, the fan may continue operating for
son. This is to ensure smooth start-up. up to a minute.
1 Press the operation mode selector button several times • The fan may stop, but this is not a malfunction.
and select the operation mode of your choice;
“ ” Cooling operation
“ ” Heating operation
“ ” Fan only operation

7 English

3P130767-3G

52 VKM-GA(M) series
ED71-440B Operation

NOTE „ EXPLANATION OF HEATING OPERATION


• Do not turn off the power immediately after operation stops. Defrost operation
Wait at least 5 minutes. • In heating operation, freezing of the outdoor unit’s coil
Not waiting may cause leaking or malfunction. increases.
• Do not change operations suddenly. Heating capability decreases and the system goes into defrost
It can result not only in malfunction but also failure of operation.
switches or relays in the remote controller. • The remote controller will read “ ” until the hot air
starts blowing.
• Never press the button of the remote controller with a hard, • It returns to the heating operation again after 6 to 8 minutes
pointed object. (10 at the longest).
The remote controller may be damaged. • During defrost operation, the fans of the unit continues driv-
ing (factory setting).
„ EXPLANATION OF OPERATION MODE The purpose of this is to maintain the amount of ventilation
and humidifying.
Cooling mode Heating mode Automatic mode
• The change of the layout in the room should be examined
It automatically
when the cold draft from air supplying opening is feared.
selects “ ” or • Though the fan can be stopped by the setting of remote con-
“ .” troller.
Fan mode Do not stop the fan in the place where no ventilation by stop-
While operating in ventilation mode, the ping the fan may cause the influence of diffusion of air which
It only operates in
unit adjusts the outside air to the indoor it is dirty and moisture into another room, or the inflow from
ventilation mode.
temperature and then brings it into the outside the room.
The unit pro-
room. (outflow such as viruses from the sickroom, or smell leakage
cesses outside air
from the rest room, etc.)
using the heat
Contact your dealer for details.
exchanger ele-
ment, but not the Hot start
DX expantion coil. • The remote controller will read “ ” until the hot air
starts blowing, e.g. at the start of heating operation.
NOTE
• This unit cannot control room temperature. If this is needed, 3.2 SETTING THE MASTER REMOTE CONTROL-
do not install the Heat Reclaim Ventilator alone, but rather LER (Refer to figure 6)
install another indoor unit. • When the system is installed as shown bellow it is neces-
„ EXPLANATION OF VENTILATION MODE sary to designate one of the remote controllers as the mas-
ter remote controller.
NOTE
• Only the master remote controller can select cooling, heat-
• These icons below are displayed on the remote controller ing, or automatic operation (the last only on simultaneous
BRC1D527. cooling/heating systems).
Automatic mode : When combined with a VRV,,-system • The displays of slave remote controllers show “ ”
air conditioner (changeover under control) and they automatically follow the
The unit automatically switches operation mode directed by the master remote controller.
between “ ” and “ ” based on
information from the VRV,, system air However, it is possible to changeover to program dry with slave
conditioner (heating, cooling, fan, and remote controllers if the system is in cooling operation set by the
set temperature) and information from master remote controller.
the Heat Reclaim Ventilator (indoor and (Cooling/heating selection operation systems)
outdoor temperatures).
The unit automatically switches between When multiple indoor units
“ ” and “ ” when it is combined or this unit are connected to
with an air conditioner (Not producted a single outdoor unit.
by Daikin) and based on only the infor-
mation from the Heat Reclaim Ventilator
(indoor and outdoor temperatures)
when the Heat Reclaim Ventilator is
operating alone.
Indoor unit Heat Reclaim Ventilator
Total heat exchange mode : Outdoor air passes through -with DX coil-
the heat exchange element
and heat exchanged air is One of these remote controllers can be
sent into the room. designated as the master remote
Bypass mode : In this mode outdoor air does not through controller.
the heat exchange element, but rather
sent into the room as is.

English 8

C: 3P130767-3G

VKM-GA(M) series 53
Operation ED71-440B

3.3 PROGRAMMING START AND STOP OF THE


(Simultaneous cooling/heating systems)
SYSTEM WITH TIMER
If multiple indoor units or many 3.3.1 HOW TO PROGRAM AND SET THE TIMER WITH THE
of this unit are connected to REMOTE CONTROLLER “BRC1A62” (Refer to figure 7)
outdoor unit via BS unit. • The timer is operated in the following two ways.
BS unit:
This is the unit which Programming the stop time “ ”. The system stops
selects cooling and operating after the set time has elapsed.
BS unit heating.
Programming the start time “ ”. The system starts
operating after the set time has elapsed.
Heat Reclaim
• The start and the stop time can be simultaneously pro-
Indoor unit
Ventilator grammed.
-with DX coil-
One of these remote controllers can be 1 Press the timer mode start/stop button “ ” several
designated as the master remote times and select the mode on the display.
controller.
• For setting the timer stop “ ”
HOW TO DESIGNATE THE MASTER REMOTE CONTROLLER
• For setting the timer start “ ”
1 Press the operation mode selector button of the current Each time the button is pushed, the indication changes
master remote controller for 4 seconds. as shown below.
The display showing“ ” (changeover under
“No indication”
controll) of all slave remote controllers connected to the
same outdoor unit or BS unit flashes on.

“ ” “ ”

2 Press the programming time button and set the time for
stopping or starting the system.
Each time this button is pressed, the time
advances or goes backward by 1 hour.

• “ ” flashes when the power is first turned on.


• The ventilation mode can be changed regardless of the set- • The timer can be programmed for a maximum of 72 hours.
ting (main or slave). • Each time when “ ” is pushed, the time advances one hour.
NOTE Each time when “ ” is pushed, the time goes back one hour.
3 Press the timer on/off button.
• This unit cannot control room temperature. If the unit is con- The timer setting procedure ends. The display
nected to the same system with other indoor units, set the “ ” or “ ” changes from flashing light to
master remote controller on the other indoor units. constant light.
2 Press the operation mode selector button of the controller that • After the timer is programmed, the display shows the
you wish to designate as the master remote controller. Then remaining time.
designation is completed. This remote controller is designated For cancelling the timer operation, push the timer on/off
as the master remote controller and the display showing button “ ” once again.
“ ” (changeover under control) vanishes. The indication disappears.
The displays of other remote controller show
“ ” (changeover under control). NOTE
3 Press the operation mode selector button on the master • When setting the timer off and on at the same time,
remote controller (i.e. a remote controller which does not repeat the above procedure (from “ 1 ” to “ 3 ”)
display “ ”) to scroll through the modes.The once again.
display will scroll through “ ” – “ ” (only for simulta- „ DETAIL EXPLANATION
neous cooling/heating systems) – “ ” – “ ”.
When you want to stop operation after a desired time,
The display on slave remote controllers will also change
Example:
automatically.
Set the time to “8”.
„ Details and activity of operation p
• Setting the master remote controller (without the 8hr
“ ” will display.
“ ” display) to cooling/heating mode will make
slave remote controllers (with the “ ” display) to Stops operation 8 hours after the reservation is complete.
follow to the mode of the master remote controller. The program will be cleared after the operation stops.
Selection of fan mode is possible, however. • Set the stop time during operation.
• Setting the master remote controller (without the
“ ” display) to fan mode will make slave remote
controllers (with the “ ” display) any setting other
than fan mode impossible.

9 English

C: 3P130767-3G

54 VKM-GA(M) series
ED71-440B Operation

When you want to start operation after a desired time has 6 Press the “ ” button. “ ” icon displays.
elapsed This icon means the unit will stop at the set time.
Example: When all data for the schedule timer actions for Monday
Set the time to “8”. are entered, you must confirm the programmed actions.
p Make sure the last schedule timer action you want to
8hr keep is selected (schedule timer actions with a higher
“ ” will display.
number will be deleted).
Starts operation 8 hours after the reservation is complete. Now you must choose between 2 options:
The reservation is cancelled after operation starts.
• Set the start time while the unit is stopped. 1. CONFIRM AND COPY TO NEXT DAY
• The remaining time will count at the same time after reser- 7 The schedule timer action programmed for the current
vation is complete. day are also valid for the next day: use the “confirm last
action and copy actions to next day” function by pressing
the “ ” and “ ” buttons simultaneously for 5 sec-
See the example below if you want to reserve “off after time”
onds. “DAY OF THE WEEK INDICATOR” will change
and “on after time” at the same time.
blinking from “ ” to “ ”.
For example: (Refer to figure below)
When the timer is programmed to stop the system after 3 hours 2. CONFIRM ONLY
and start the system after 4 hours, the system will stop after 8 The schedule timer action programmed for the current
3 hours and start 1 hour later. day are only valid for the selected day: use the “confirm
Example: last action and go to next day” function by pressing the
“ ” button for 5 seconds.
Program mode is quit and depending on the choice
made, the programmed actions are saved for Monday
(and possibly Tuesday).

PROGRAMMING THE OTHER DAYS OF THE WEEK


• Setting “off after 3 hours” and “on after 4 hours” will Programming the other days of the week is identical to program-
p ming the first day of the week. “ ” is blinking to indicate the
• Operation will stop after 3 hours. selected day, “ ” and “ ” are steady if actions were copied
Operation will then start in 1 hour from the time it stopped. from Monday to Tuesday, only “ ” is displayed if no actions
3.3.2 HOW TO PROGRAM AND SET THE TIMER WITH THE were copied from Monday to Tuesday.
REMOTE CONTROLLER “BRC1D527” (Refer to figure 7)
• The controller is equipped with a schedule timer that NOTE) The schedule timer will not:
enables the user to operate the installation automatically; • control fan speed,
setting the clock and day of the week is required to be able • control air flow direction,
to use the schedule timer. • control ventilation mode,
• control ventilation amount,
• To set up clock, refer to the operation manual of the remote • change the operation mode for a scheduled setpoint.
controller.
1 Browse to Monday by pressing the “ ” button. The parameters listed above can be set manually, without inter-
The “ ” icon appears, “ ” will blink and one of the fering with the schedule timer.
“ ” icons, one of the “ ”
icons might be displayed but all other fields remain blank, 3.4 OPTIMUM OPERATION
indicating that no actions are programmed for Monday. Observe the following precautions to ensure the system oper-
ates.
2 Enter the program mode by holding down the “ ” but-
ton for 5 seconds, the “ ” icon will now blink too. • When the display shows “ ”, ask a qualified service
3 Press the “ ” button to activate the first programmed person to clean the filters (Refer to MAINTENANCE).
action. • Do not operate the Heat Reclaim Ventilator in Bypass
A blinking “ ” is displayed indicating that the first pro- mode when the room air is under heating in winter or
grammed action for Monday is being programmed; The when the outside temperature is 30°C or higher.
set temperature and clock display are blinking. This may cause condensation to form on the main unit or on
Enter the time when the action must start using the discharge grill, or around air supply opening.
3
“ ”&“ ” buttons (min. step = 10 minutes). • Keep the indoor unit and the remote controller at least
1 m away from televisions, radios, stereos, and other
4 Press the “ ” button to display the next programmed
similar equipments.
action. If a second action is programmed for Monday,
This may cause distorted picture or noise.
“ ” will still be blinking and “ ” will appear.
Assuming that 5 actions were programmed for Monday, a • Turn off the main power supply switch when it is not
total of 5 presses will be required to display all pro- used for long periods of time. When the main power
grammed actions. switch is turned on, some watts of electricity is being
Enter the time when the action must stop using the used even if the system is not operating.
5
Turn off the main power supply switch for saving energy.
“ ”&“ ” buttons (min. step = 10 minutes).
When reoperating, turn on the main power supply switch
6 hours before operation for smooth running.

English 10

C: 3P130767-3G

VKM-GA(M) series 55
Operation ED71-440B

• Use city water or clean water and take steps to prevent • If the dirt becomes impossible to clean, change the air filter
condensation from forming. (VKM-GAMV1 series only) (Air filter for exchange is optional).
• The life of humidifier become shorter when the supply (1) Detach the maintenance cover.
water is hard water. (VKM-GAMV1 series only) Go into ceiling through the inspection hatch, remove binding
Use a water softener. metal of maintenance cover and take it off.
(Refer to figure 8-1)
• Do not install the remote controller where the indoor (2) Detach the air filter.
temperature and humidity, respectively, are out of the Take out from the heat exchange elements.
range of 0-35°C and RH 40-80%. (Refer to figure 8-2)
This may cause malfunction. (3) Clean the air filter. (Refer to figure 9)
• Do not install the remote controller where direct sun- Use vacuum cleaner A) or wash the air filter with water B).
light may fall on it. A) Using a vacuum cleaner
This may cause discoloration or deformation. B) Washing with water
NOTE When the air filter is very dirty, use soft brush and neau-
tral detergent.
• When the fan motor fails, the remote controller does not dis- After cleaning, remove water and dry in the shade.
play any error code.
Usage under that status will lead to insufficient ventilation. NOTE
The air supply and exhaust fans should be checked once • Do not wash the air filter with hot water of more than 50°C,
every one or two months. as doing so may result in discoloration and/or deformation.
You can make a simple check such as below way. • Do not expose the air filter to fire, as doing so may result in
To check the wind flow, hold a bar of which the end has a burning.
string or other similar lightweight item over the supply grille • Do not use gasoline, thinner, or other organic solvents.
and exhaust grille. This may cause discoloration or deformation.
• When the solenoid valve fails, the remote controller does not (4) Fix the air filter.
display any error code. If the air filter is washed, remove water completely and allow
Usage under that status will lead to insufficient humidification to dry for 20 to 30 minutes in the shade. When dried com-
and increased tap water consumption. pletely, install the air filter back in place.
The solenoid valve should be checked at the beginning of the (Refer to figure 10)
heating season. <VKM-GAMV1 series only>
NOTE
• Be sure to install the air filter after servicing.
4 MAINTENANCE (Missing air filter causes clogged heat exchange element.)
(for a qualified service person only) The air filter is an optional item and the replacement is
available.
ONLY A QUALIFIED SERVICE PERSON IS ALLOWED TO
(5) Install the maintenance cover.
PERFORM MAINTENANCE
Refer to page 11 (4.1, (1)).
DO NOT CHECK OPENING INSIDE THE UNIT BY YOURSELF.
For remote controllers which display the filter sign, turn on the
WARNING power after maintenance, and press the filter sign reset button.
• BEFORE OBTAINING ACCESS TO TERMINAL DEVICES, Consult your dealer if you want to change the time setting
ALL POWER SUPPLY CIRCUITS MUST BE INTERRUPTED. for when the filter sign goes on.
• To clean the Heat Reclaim Ventilator, or maintenance be
sure to stop operation, and turn the power switch off. It may CAUTION
cause electrical shock and it is very dangerous to touch the • Always use the air filter.
rotating part. If the air filter is not used, heat exchange elements will be clogged,
• Do not wash the Heat Reclaim Ventilator with water. possibly causing poor performance and subsequent failure.
Doing so may result in an electric shock.
4.2 HOW TO CLEAN THE HEAT EXCHANGE ELEMENT
CAUTION AT LEAST ONCE EVERY TWO YEARS
• Use gloves when cleaning. (FOR GENERAL OFFICE USE)
Cleaning without gloves may cause injury. (CLEAN THE ELEMENT MORE FREQUENTLY IF NECES-
SARY.)
• Watch your step.
Use caution, as this requires working in high places. WARNING
• Do not use benzene or thinner to clean the outside surfaces • Please exchange the heat exchange element if you find
of the air conditioner. that the knob of the heat exchange element is damaged
This may cause cracks, discoloration, or machine trouble. or is deteriorated when cleaning it.
There is falling danger.
4.1 HOW TO CLEAN THE AIR FILTER
Clean the air filter when the display shows “ ” (TIME TO (1) Detach the maintenance cover.
CLEAN AIR FILTER). Refer to page 11 (4.1, (1)).
It will display that it will operate for a set amount of time. (2) Detach the air filter.
Refer to page 11 (4.1, (2)).
AT LEAST ONCE EVERY YEARS (FOR GENERAL OFFICE USE)
(3) Take out the heat exchange elements.
(CLEAN THE MORE FREQUENTLY IF NECESSARY.)
Pull out the air filter and then pull out the two heat
• Increase the frequency of cleaning if the unit is installed in a exchanger elements. (Refer to figure 11)
room where the air is etermely contaminated.

11 English

C: 3P130767-3G

56 VKM-GA(M) series
ED71-440B Operation

(4) Use a vacuum cleaner to remove dust and foreign objects For dealers
on the surface of the heat exchange element. Content of maintenance Problems if
(Refer to figure 12) Inspected maintenance
• Use the vacuum cleaner equipped with a brush on the part Items to be is not carried
Solution
tip of the suction nozzle. inspected out
• Lightly contact the brush on the surface of the heat
exchange element when cleaning. Check for Clean if Insufficient
(Do not crush the heat exchange element while cleaning.) Strainer clogging clogged. humidifying.
(80-mesh) Check o-ring Replace if
CAUTION Leaking.
for cracks cracked.
• Do not clean touching strongly with a vacuum cleaner. This
Clean if it Insufficient
may crush the mesh of the heat exchange elements.
Check for does not humidifying.
• Never wash the heat exchange element with water.
operation of work properly Overflowed
• Have your dealer professionally clean the filter if it is very
float switch due to build- feed water
dirty.
Feed water up. tank.
(5) Put the heat exchange element on the rail and insert it tank Weak fan
securely in place. strength.
(6) Install the air filter securely in place. Clean if very
Check for dirt Reduced
(Refer to page 11 (4.1, (4))) dirty.
humidifying
(7) Install the maintenance cover securely in place. capacity.
(Refer to page 11 (4.1, (5)))
Check for
Insufficient
4.3 SEASONAL MAINTENANCE shutting and
humidifying.
<VKM-GAMV1 series only> opening.
Overflowed
4.3.1 AT THE BEGINNING OF THE SEASON Check in a
Solenoid Replace if it feed water
(1) Check below similar fash-
valve doesn’t work. tank.
• Are the indoor and outdoor unit intake and outlet vents ion when
(Increased
blocked? checking the
tap water
Remove anything that might be blocking them. float switch
consumption)
(2) Turn the power on operation.
• When the power comes on, the characters in the remote 4.5 INSPECTION OF THE FAN MOTER
controller display appear.
(To protect the unit, turn the power on at least 6 hours NOTE
before operating it. This makes operation smoother.) • When the fan motor fails, the remote controller does not dis-
(3) Supply water (Start of heating season) play any error code.
4.3.2 AT THE END OF THE SEASON Usage under that status will lead to insufficient ventilation.
(1) On a clear day, use fan only operation for around half a The air supply and exhaust fans should be checked once
day to thoroughly dry out the interior of the unit. every one or two months.
• Refer to page 7 for details on fan operation. You can make a simple check such as below way.
(2) Turn off the power To check the wind flow, hold a bar of which the end has a
• When the power is shut off, the characters in the remote string or other similar lightweight item over the supply grille
controller display disappear. and exhaust grille.
• When the power is on, the unit consumes up to several 4.6 REPLACING THE HUMIDIFIER ELEMENT
dozen Watts of power. <VKM-GAMV1 series only>
Turn off the power to conserve energy.
(3) Stop water supply (End of heating season) • The humidifier element needs to be replaced regularly.
The humidifier element should in general be replaced once
every three years when supply water is soft water, but out-
4.4 INSPECTION AND MAINTENANCE OF THE side factors (If the water quality is hard water, etc.) as well
HUMIDIFIER <VKM-GAMV1 series only> as operating conditions (24-hour-a-day air conditioning, etc.)
• Have your dealer do the following inspections in order may shorten its productive life.
to get the longest use.
• In order to prevent harmful bacteria from generating, ask • Contact your dealer if you have any questions.
your dealer to do maintenance on humidifying unit portion at
the beginning or the end of the heating season. 5 TROUBLE SHOOTING
NOTE
5.1 THE FOLLOWING SITUATIONS ARE NOT MAL-
• When the solenoid valve fails, the remote controller does not
display any error code. FUNCTIONS
Usage under that status will lead to insufficient humidification • Operation does not start.
and increased tap water consumption. <Symptom>
The solenoid valve should be checked at the beginning of the The icon “ ” (under centralized control) is dis-
heating season. played on the remote controller and pressing the on/off but-
ton causes the display to blink for a few seconds.
<Cause>
This indicates that the central device is controlling the unit.
The blinking display indicates that the remote controller can-
not be used.

English 12

3P130767-3G

VKM-GA(M) series 57
Operation ED71-440B

<Symptom> • If the display “ ” (INSPECTION), “UNIT No.” and the


The fans rotates after 1 minutes when pressing on on/off but- OPERATION lamp flash and the “MALFUNCTION
ton. CODE” appears.
<Cause>
OPERATION lamp
This indicates that the operation is in preparation.
Wait for about 1 minute.
• Operation stops sometimes.
<Symptom>
“U5” is displayed on the remote controller and the operation
stops but then restarts after a few minutes.
<Cause>
This indicates that the remote controller is intercepting noise
from electrical appliances other than the Heat Reclaim Ven- INSPECTION INDOOR UNIT No. in which
tilator, and this prevents communication between the units, display a malfunction occurs
causing them to stop. MALFUNCTION CODE
Operation automatically restarts when the noise goes away.
• “88” is displayed on the remote controller. Measure: Notify and inform the model name and what the
malfunction code indicates to your Daikin dealer.
<Symptom>
It displays immediately after the power is turned on, and dis- • There are other malfunctions.
appears after several seconds. Measure: Stop the unit.
<Cause> List of malfunction codes of Remote controller of the Heat
This indicates that the unit is checking whether or not the Reclaim Ventilator-system
remote controller is normal.
It is only displayed temporarily. Inspec Mal-
Opera-
tion Unit func-
tion Description
5.2 IF ONE OF THE FOLLOWING MALFUNCTIONS indica- No. tion
lamp
OCCURS, TAKE THE MEASURES SHOWN tor code
BELOW AND CONTACT YOUR DAIKIN DEALER On Off
Blink-
64
Indoor air thermistor mal-
The system must be repaired by a qualified service person. ing function
DO NOT CHECK AND REPAIR OPENING INSIDE THE UNIT On Off
Blink-
65
Outdoor air thermistor mal-
BY YOURSELF. ing function
Blink- Dumper-related malfunction
On Off 6A
WARNING ing
Blink- Blink- Blink- Dumper-related malfunction
When the Heat Reclaim Ventilator is in abnormal condi- 6A
ing ing ing + thermistor malfunction
tions (smell of something burning, etc), cut off the power,
and contact your dealer. Blink- Blink- Blink- Printed circuit board fault
A1
ing ing ing
Continued operation under such circumstances may result in a
failure, electric shock, and fire. Blink- Printed circuit board fault
On Off A1
ing
• The unit does not operate at all. Blink- Blink- Blink-
A9
Electric expansion valve
a. Check if there is a power failure. ing ing ing drive error
Measure: After power has been restored, start operation Liquid piping thermistor error
Blink- Blink- Blink-
again. ing ing ing
C4 (faulty connection, discon-
nection short circuit, fault)
b. Check if the fuse has blown.
Measure: Turn the power off. Gas piping thermistor error
Blink- Blink- Blink-
C5 (faulty connection, cut wire,
c. Check if breaker has worked. ing ing ing
short circuit, fault)
Measure: Intake air into coil thermistor error
ON Blink- Blink- Blink-
Turn the power on with the Switch C9 (faulty connection, disconnection,
ing ing ing
breaker switch in the off short circuit, fault)
position. Trip position Blink- Blink- Blink- Test run not performed
Breaker U3
Do not turn the power on OFF ing ing ing
with the breaker switch in Blink- Blink- Blink- Transmission error between
the trip position. U5
ing ing ing the unit and remote controller
(Contact your dealer.) Blink- Setting error of remote con-
Off Off U5
• If a safety device such as a fuse, a breaker, or an earth ing troller
leakage breaker frequency actuates, or ON/OFF switch Transmission error between
Blink-
does not properly work. Off
ing
Off U8 main remote controller and
Measure: Do not turn the power on. sub remote controller

• The remote control buttons do not work well. Blink- Blink- Incorrect combination with
Off UA
ing ing indoor unit and remote controller.
Measure: Turn off the main power switch.
Blink- Central control address over
On On UC
ing lapping
Transmission error between
Blink- Blink- Blink-
UE the unit and centralized con-
ing ing ing
troller

13 English

C: 3P130767-3G

58 VKM-GA(M) series
ED71-440B Operation

In case of the malfunction with the code in white letters After-sales service and warranty
on the black background in the unit still operates.
However, be sure to have it inspected and repaired After-sales service:
and as soon as possible.
If other than the above error codes are displayed, WARNING
there is a possibility that the problem in question has • Do not modify the unit.
occurred with a combined air conditioner or outdoor This may cause electric shock or fire.
unit. See the operation manuals included with the air
• Do not disassemble or repair the unit.
conditioners or outdoor units for details.
This may cause electric shock or fire.
5.3 IF THE SYSTEM DOES NOT PROPERLY OPERATE Contact your dealer.
EXCEPT FOR THE ABOVE MENTIONED CASE, AND • If the refrigerant leaks, keep out of fire.
NONE OF THE ABOVE MENTIONED MALFUNC- The refrigerant used in this unit is safe.
TIONS IS EVIDENT, CONTACT YOUR DEALER, AND Although the refrigerant does not usually leak, if the refriger-
REQUEST FOR INVESTIGATION THE SYSTEM ant leaks out into a room and comes in contact with the com-
ACCORDING TO THE FOLLOWING PROCEDURES bustible air in the equipment such as fan heater, stove, oil
BY A QUALIFIED SERVICE PERSON (gas) cooker, etc., it will cause toxic gas to be generated.
The following malfunctions must be cheched by a qualified When a refrigerant leakage failure has been repaired, con-
service person. Do not check by yourself. firm a service person that the leakage point has been cor-
rected surely before restarting operation.
• The unit does not operate at all.
a. Check if there is a power failure. • Do not remove or reinstall the unit by yourself.
After power has been restored, start operation again. Incomplete installation may cause a water leakage electric
b. Check if the fuse has blown. shock and fire.
Change the fuse. Contact your dealer.
c. Check if breaker has worked.
Contact your dealer. „ When asking your dealer to repair, inform related
d. Are there any problems with the power or wiring? staff of the details as follows:
Inspect the power and wiring. • Shipping date and installation date:
e. Are there any problems with the fan unit? • Malfunction:
Inspect the fan motor and fan. Inform the staff of the defective details.
(Malfunction code being displayed on
• Amount of discharged air is small and the discharging
the remote controller.)
sound is high.
• Name, address, telephone number
a. Check if the air filter and heat exchange element are
clogged. (Check both SA and RA air filter. Check both „ Repair where the warranty term is expired
sides of elements.) Contact your dealer. If necessary to repair, pay service is
Clean the air filter and heat exchange element. available.
• Amount of discharged air is large and so is the sound. „ Minimum storage period of important parts
a. Check if the air filter and heat exchange element are not Even after a certain type of air conditioner is discontinued,
installed. we have the related important parts in stock for 6 years at
Install the air filter and heat exchange element. least.
• It dries usually in winter. <VKM-GAMV1 series only> The important parts indicate parts essential to operate the air
a. Is the water supply service valve open? conditioner.
Open the water supply service valve.
„ Recommendations for maintenance and inspec-
b. Have you lowered setting on the humidistat (locally pro-
tion
cured) too far?
Correct the setting. Since dust collects after using the unit for several years, the
performance will be deteriorated to some extent.
• Humidifies very little or not at all. <VKM-GAMV1 series only> Taking apart and cleaning inside require technical expertise,
a. Is there water in the water supply tank? so we recommend entering a maintenance and inspection
b. Is water being supplied? contract (at a cost) separate from normal maintenance.
Inspect the water supply pipes and supply the water.
c. Is the strainer clogged? „ Recommended inspection and maintenance
Clean the strainer. cycles
d. Is the solenoid valve broken (i.e. won’t open)? [Note: The maintenance cycle is not the same as
Replace the solenoid valve. the warranty period.]
e. Is the humidifier element torn? Table 1 assumes the following usage conditions.
Replace. • Normal use without frequent starting and stopping of the
f. Has the water resistance of the humidifier element dropped? machine.
Replace the humidifier element. (Although it varies with the model, we recommend not start-
g. Are the control circuits broken? ing and stopping the machine more than 6 times/hour for
Replace the printed circuit board and other electric parts. normal use.)
h. Is the float switch broken? • Operation of the product is assumed to be 10 hours/day,
Replace the float switch. 2500 hours/year.
i. Is the water supply pressure sufficient?
Re-set it so that there is sufficient pressure.
j. Is there foreign matter in the feed water tank?
Clean the feed water tank.

English 14

3P130767-3G

VKM-GA(M) series 59
Operation ED71-440B

• Table 1 “Inspection Cycle” and “Maintenance Cycle” Lists „ Recommended replacement cycle of wear-out parts
Maintenance Cycle
[The cycle is not the same as the warranty period.]
Inspection
Name of Main Part [replacements and/ • Table 2 “Replacement Cycle” Lists
Cycle
or repairs]
Inspection
1~2 months Name of Main Part Replacement Cycle
Electric motor (fan, Cycle
recom- 20,000 hours
damper, etc.) Air filter 3 years
mended *1
High efficiency filter 1 year
PC boards 25,000 hours 1 year
(Optional accessory)
Heat exchanger Heat exchanger ele-
10 years 2 years 10 years
element ment
Heat exchanger 5 years Humidifier element 1 year 3 years (Note 3)
1 year
Sensor (thermistor) 5 years
Note 1
Remote controller and This table indicates main parts.
25,000 hours
switches See the maintenance and inspection contract for details.
Drain pan 8 years Note 2
Expansion valve 1 year *2 20,000 hours This maintenance cycle indicates recommended lengths of
time until the need arises for maintenance work, in order to
Electromagnetic valve 1 year 20,000 hours
ensure the product is operational as long as possible.
*1: Use for appropriate maintenance design (budgeting mainte-
• When the fan motor fails, the remote controller does not dis- nance and inspection fees, etc.).
play any error code. Note 3
Usage under that status will lead to insufficient ventilation. Life of humidifying element is about 3 years (4,000 hours),
The air supply and exhaust fans should be checked once under the supply water conditions of hardness: 150mg/l.
every one or two months. (Life of humidifying element is about 1 year (1,500 hours),
• You can make a simple check such as below way. under the supply water conditions of hardness: 400mg/l.)
To check the wind flow, hold a bar of which the end has a Annual operating hours: 10 hours/day × 26 days/
string or other similar lightweight item over the supply grille month × 5 month = 1,300 hours.
and exhaust grille.
*2: Contact your dealer for details.
• When the solenoid valve fails, the remote controller does not Note: Breakage due to taking apart or cleaning inside by any-
display any error code. one other than our authorized dealers may not be included in
Usage under that status will lead to insufficient humidification the warranty.
and increased tap water consumption.
The solenoid valve should be checked at the biginning of the „ Moving and discarding the unit
heating season.
• Contact your dealer for removing and reinstalling the total
Note 1
enthalpy heat exchanger when moving house since they
This table indicates main parts.
require technical expertise.
See the maintenance and inspection contract for details.
Note 2 • This unit contains chlorofluorocarbon in the refrigent.
This maintenance cycle indicates recommended lengths of When discarding, removing linstalling and maintaining the
time until the need arises for maintenance work, in order to unit, collect the refrigent in accordance with the local law for
ensure the product is operational as long as possible. the global environmental destruction prevention.
Use for appropriate maintenance design (budgeting mainte- In detail contact your dealer.
nance and inspection fees, etc.). „ Where to call
Depending on the content of the maintenance and inspection For after-sales service, etc., consult with your dealer.
contract, the inspection and maintenance cycles may in reality
be shorter than those listed here. „ Warranty period:
Shortening of “maintenance cycle” and “replacement Warranty period: Within one year after
cycle” needs to be considered in the following cases. installation.
• When used in hot, humid locations or locations where tem- • If it is necessary to repair the air conditioner within the war-
perature and humidity fluctuate greatly. ranty period, contact your dealer.
• When used in locations where power fluctuation (voltage, fre-
quency, wave distortion, etc.) is high.
(Cannot be used if it is outside the allowable range.)
• When installed and used in locations where bumps and
vibrations are frequent.
• When used in bad locations where dust, salt, harmful gas or
oil mist such as sulfurous acid and hydrogen sulfide may be
present in the air.
• When used in locations where the machine is started and
stopped frequently or operation time is long. (Example:
24 hour air-conditioning)
• When the supply water is hard water the humidifier’s life
become shorter.

15 English

3P130767-3G

60 VKM-GA(M) series
ED71-440B Installation

16. Installation

With DX coil &Humidifier VKM50GAMV1 With DX coil VKM50GAV1


VKM80GAMV1 VKM80GAV1
Installation
Heat Reclaim Ventilator-with DX Coil-
VKM100GAMV1 VKM100GAV1 manual

• Carry out the specified installation work after taking into


CONTENTS account strong winds, typhoons or earthquakes.
Failure to do so during installation work may result in the unit
1 SAFETY PRECAUTIONS............................................... 1 falling and causing accidents.
2 BEFORE INSTALLATION ............................................... 2 • Make sure that all wiring is secured, the specified wires are used,
and that there is no strain on the terminal connections or wires.
3 SELECTING INSTALLATION SITE ................................ 3
Improper connections or securing of wires may result in
4 PREPARATIONS BEFORE INSTALLATION................... 4 abnormal heat build-up or fire.
5 THE METHOD OF INSTALLATION ................................ 4 • When wiring the power supply and connecting the remote
6 DRAIN PIPING AND WATER SUPPLY WORK .............. 5 controller wiring and transmission wiring, position the wires
7 REFRIGERANT PIPING WORK .................................... 6 so that the electric parts box lid can be securely fastened.
Improper positioning of the electric parts box lid may result in
8 DUCT CONNECTION .................................................... 8
electric shocks, fire or the terminals overheating.
9 ELECTRIC WIRING WORK ........................................... 8 • When installing the unit in a small room, take measures
10 WIRING EXAMPLE AND HOW TO SET against to keep refrigerant concentration from exceeding
THE REMOTE CONTROLLER ...................................... 9 allowable safety limits in the event of refrigerant leakage.
11 FIELD SETTING AND TEST RUN ............................... 13 Contact the place of purchase for more information.
Excessive refrigerant in a closed ambient can lead to oxygen deficiency.
12 WIRING DIAGRAM ...................................................... 16
• If the refrigerant gas leaks during installation, ventilate the
area immediately.
1 SAFETY PRECAUTIONS Toxic gas may be produced if the refrigerant gas comes into
Please read these “SAFETY PRECAUTIONS” carefully before contact with fire.
installing Heat Reclaim Ventilator and be sure to install it correctly. • After completing the installation work, check that the refriger-
After completing installation, conduct a trial operation to check ant gas does not leak.
for faults and explain to the customer how to operate the Heat Toxic gas may be produced if the refrigerant gas leaks into
Reclaim Ventilator and take care of it with the aid of the opera- the room and comes into contact with a source of fire, such
tion manual. Ask the customer to store the installation manual as a fan heater, stove or cooker.
along with the operation manual for future reference. • Be sure to switch off the unit before touching any electrical parts.
• Do not directly touch any refrigerant which has leaked out of
This Heat Reclaim Ventilator comes under the term “appli- refrigerant piping connections, etc.
ances not accessible to the general public”. This may cause frostbite.
Meaning of WARNING and CAUTION notices • Be sure to earth the Heat Reclaim Ventilator.
Do not earth the unit to a utility pipe, lightning conductor or telephone
WARNING ...............Failure to follow these instructions properly earth lead. Imperfect earthing may result in electric shocks or fire.
may result in personal injury or loss of life. A high surge current from lightning or other sources may
CAUTION ............... Failure to observe these instructions cause damage to the air conditioner.
properly may result in property damage • Be sure to install an earth leakage breaker.
or personal injury, which may be serious Failure to install an earth leakage breaker may result in
depending on the circumstances. electric shocks or fire.
WARNING
CAUTION
• Ask your dealer or qualified personnel to carry out installation work.
Do not attempt to install the Heat Reclaim Ventilator your- • While following the instructions in this installation manual,
self. Improper installation may result in water leakage, install drain piping to ensure proper drainage and insulate
electric shocks or fire. piping to prevent condensation.
• Installation should be done following the installation manual and Improper drain piping may result in indoor water leakage and
no changes should be made to the unit. property damage.
Improper installation may result in water leakage, electric shocks • Install the indoor and outdoor units, power cord and connect-
or fire. Injuries may result if the Heat Reclaim Ventilator falls. ing wires at least 1 meter away from televisions or radios to
• Install the unit on a foundation strong enough to withstand prevent picture interference and noise.
the weight of the unit. (Depending on the incoming signal strength, a distance of
A foundation of insufficient strength may result in the equip- 1 meter may not be sufficient to eliminate noise.)
ment falling and causing injuries. • Install the two outdoor ducts with down slope to prevent rain-
• Do not allow exhaust air to enter the outside air intake vent. water from entering the unit.
This may cause the air of the room to become contaminated, If this is not done completely, water may enter the building,
harming the health. may damage furniture, and cause electric shocks and fire.
• Locate the outside air intake vent so that it does not take in • Insulate the two outdoor ducts and the supply air duct to pre-
exhaust air which contains combustion air, etc. vent condensation.
Incorrect installation may cause a loss of oxygen in the room, If this is not done completely, water may enter the building,
leading to serious accidents. may damage furniture, etc.
• Make sure that a separate power supply circuit is provided for this • Insulate the duct and the wall electrically when a metal duct
unit and that all electrical work is carried out by qualified personnel is to be penetrated through the metal lattice and wire lattice
according to local laws and regulations and this installation manual. or metal lining of a wooden structure wall.
An insufficient power supply capacity or improper electrical Inproper duct work may cause electric shocks or fire.
construction may lead to electric shocks or fire.
• Do not install the unit in the following locations:
Insufficient power supply capacity or incorrect wiring may
cause electrical shocks or fire. 1. Place subjected to high temperature or direct flame.
• Be sure to use only the specified accessories and parts for May result in fire or overheating.
installation work. 2. Where there is a high concentration of mineral oil spray or
Failure to use the specified parts may result in the unit falling, vapour (e.g. a kitchen).
water leakage, electric shocks or fire. This may cause fire.

English 1

C: 3P130768-2H

VKM-GA(M) series 61
Installation ED71-440B

3. Place such as machinery plant and chemical plant where 2. 2 ACCESSORIES


gas, which contains noxious gas or corrosive components Check the following accessories are included with your unit.
of materials such as acid, alkali organic solvent and paint, is
generated. Place where combustible gas leakage is likely. M4 tapping
Duct con-
Copper piping and brazed joints may corrode, causing screw (For Water supply piping
Name necting
refrigerant to leak or poisoning and fire due to leaked gas. connecting with strainer
flange
4. Locations below freezing point. duct)
Using the unit at temperatures below 0°C may cause the VKM-GAMV1: 1 pc.
drain pan the supply and discharge piping, the humidifying Quantity 4 pcs. 24 pcs.
VKM-GAV1: 0 pc.
element, the solenoid valves, and other parts to freeze,
which can cause accidents.
5. Near machinery emitting electromagnetic radiation.
Shape
Electromagnetic radiation may disturb the operation of the 50 type M4×12
control system and result in a malfunction of the unit. 80, 100 type M4×16
6. Where flammable gas may leak, where there is carbon fibre
or ignitable dust suspensions in the air, or where volatile flam-
mables such as paint thinner or gasoline are handled. Oper- Half-union
Flare nut
ating the unit in such conditions may result in fire. joint Refrigerant piping
Name (Copper
• The Heat Reclaim Ventilator is not intended for use in a (Copper insulation cover
piping joint)
potentially explosive atmosphere. piping joint)
• Make sure the temperature and humidity near the unit and VKM-GAMV1:1 pc. VKM-GAMV1:1 pc.
Quantity 1 set
the air suction/discharge air grille is within limit dictated by VKM-GAV1: 0 pc. VKM-GAV1: 0 pc.
the usage conditions.
1. Refrigerated truck or other locations with low temperatures.
2. Place such as bathroom or heated pools subjected to moisture. Shape
This may cause fires or electric leak or electric shocks. I.D.: φ35 I.D.: φ26
• Make sure that a snow protection measure is taken. If no pro-
tection snow may enter through the outdoor ducts, and cause
damaging furniture and electric shock and fire. Water sup-
• In areas where insects are easily attracted to a light, such as ply piping Sealing
where there is a window or light near a ventilation opening, Name Clamp
insulation material
extremely small insects can sometimes infiltrate the room by cover
passing through the ventilation opening. VKM-GAMV1: VKM-GAMV1: (Other)
Since totally preventing against infiltration by extremely small 1 pc. 8 pcs.
Quantity 1 pc. • Installation
insects is difficult, it is important to consider a serious solu- VKM-GAV1: VKM-GAV1: manual
tion like a filter box (field supply) during the design process to 0 pc. 6 pcs. • Operation
protect against insect infiltration. manual
• The Heat Reclaim Ventilator is not intended for use in a
potentially explosive atmosphere. Shape
I.D.: φ15

2 BEFORE INSTALLATION
The accessories needed for installation must be retained in 2. 3 OPTIONAL ACCESSORIES
your custody until the installation work is completed. Do • This unit can be made a part of two different systems: as part
not discard them! of the combined operation system used together with VRVII
After carrying in the unit, protect it with packing materials to pre- SYSTEM Air Conditioners, and as the independent system
vent it from scratching until installation work is done. using only the Heat Reclaim Ventilator. An operating remote
controller is required for this unit when using the unit as an
[1] Decide upon a line of transport. independent system.
[2] Leave the unit inside its packaging while moving, until reach- Select a suitable remote controller from below table accord-
ing the installation site. Where unpacking is unavoidable, ing to customer request and technical materials.
use a sling of soft material or protective plates together with
a rope when lifting, to avoid damage or scratches to the unit. Table
Hold the unit by the hanger brackets (4) when opening the Remote controller type BRC1A62, BRC1D527
crate and moving it, and do not lift it holding on to any other
part (especially the refrigerant piping, the drain piping, the NOTE) 1
water supply piping, and the duct connecting flange). If you use the remote controller which is not listed in above
• Be sure to check the type of R410A refrigerant to be used table, please consult your dealer.
before installing the unit. (Using an incorrect refrigerant will NOTE) 2
prevent normal operation of the unit.)
We recommend the remote controller “BRC1D527” espe-
• For the installation of an outdoor unit, refer to the installa-
tion manual attached to the outdoor unit. cially when the unit is used as independent system. Because
it displays the ventilation mode and can be selected ventila-
2. 1 PRECAUTIONS tion fan mode with the button.
• Be sure to instruct customers how to properly operate the • When installing the unit, have ready the round shape hood,
unit (especially maintenance of air filter, and operation proce- the air discharge grille and the air suction grille, and other
dure) by having them carry out operations themselves while parts needed for the installation.
looking at the manual. Consult your Daikin dealer when selecting optional accesso-
• Where the air contains high levels of salt such as that near ries.
the ocean and where voltage fluctuates greatly such as that
in factories. Also in vehicles or vessels.

2 English

C: 3P130768-2H

62 VKM-GA(M) series
ED71-440B Installation

FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE 3 SELECTING INSTALLATION SITE
DURING CONSTRUCTION AND CHECK AFTER
INSTALLATION IS FINISHED. CAUTION
a. Items to be checked after completion of work • When moving the unit during or after unpacking, make sure
to lift it by holding its hanger brackets. Do not exert any pres-
If not properly done, sure on other parts, especially the refrigerant piping, drain
Items to be checked Check
what is likely to occur piping, water supply piping and duct connecting flange.
Are the indoor and • If you think the humidity inside the ceiling might exceed 30°C
The units may drop, and RH80%, reinforce the insulation on the inter-unit piping.
outdoor unit fixed
vibrate or make noise. Use glass wool or polyethylene foam as insulation so that it is
firmly?
no thicker than 10mm and fits inside the ceiling opening.
Is the outdoor duct
installed to outside Condensate water • Use glass wool or polyethylene form of 10mm or more thick
with down slope? may drip. which fit into ceiling opening as insulation material.
(Refer to page 8 Fig. 16)
(1) Select an installation site where the following conditions
Is the gas leak test It may result in insuffi- are fulfilled and that meets with your customer’s approval.
finished? cient cooling. • Install in a place which has sufficient strength and stabil-
Is the unit fully insu- Condensate water ity. (Beams, ceiling, and other locations capable of fully
lated? may drip. supporting the weight of the unit.)
Insufficient strength is dangerous. It may also cause
Does drainage flow Condensate water vibration and unusual operating noise.
smoothly? may drip. • Where piping between indoor and outdoor units is possi-
Does the power sup- ble within the allowable limit. (Refer to the installation
The unit may malfunc-
ply voltage corre- manual for the outdoor unit.)
tion or the compo-
spond to that shown • Where nothing blocks air passage.
nents burn out.
on the name plate? • Where condensate can be properly drained.
The unit may malfunc- • Install in a location where the air around the unit or taken
Are wiring and piping into the humidifier will not drop below 0°C.
tion or the compo-
correct? • Do not install the unit directly against a ceiling or wall.
nents burn out.
(If the unit is in contact with the ceiling or wall, it can
Is the unit safely Dangerous at electric cause vibration.)
grounded? leakage. • Where sufficient clearance for maintenance and service
The unit may malfunc- can be ensured. (Refer to Fig. 1)
Is wiring size accord-
tion or the compo-
ing to specifications? Unit (mm)
nents burn out.
Is something blocking
the air outlet or inlet of It may result in insuffi-
either the indoor or cient cooling.
outdoor units?
600
Are refrigerant piping or more
The refrigerant Electric parts box
length and additional
charge in the system Maintenance
refrigerant charge space
is not clear.
noted down?
Is water supplied with
the water supply pip- Not humidified. minimum hight
ing connected? ∗H
20 or more
Please check all items listed in the “SAFETY PRECAUTIONS”
above once again.
• Select the ∗H dimension such that a downward slope Fig. 1
b. Items to be checked at time of delivery of at least 1/100 is ensured as indicated in “6 DRAIN
Items to be checked Check PIPING AND WATER SUPPLY WORK”.
Did you explain about operations while showing [PRECAUTION]
the operation manual to your customer? • Install the indoor and outdoor units, power supply wiring and
Did you hand the operation manual and warranty connecting wires at least 1 meter away from televisions or
over to your customer? radios in order to prevent image interference or noise.
Depending on the radio waves, a distance of 1 meter may
c. Points for explanation about operations
not be sufficient enough to eliminate the electric noise.
The items with WARNING and CAUTION marks in • The bellows may not be able to be used in some disc-
the operation manual are the items pertaining to tricts, so exercise caution. (Contact your local govern-
possibilities for bodily injury and material damage in ment office or fire department for details.)
addition to the general usage of the product. Accordingly, it • When discharging exhaust air to a common duct, the
is necessary that you make a full explanation about the Building Standard Law requires the use of fire-proof
described contents and also ask your customers to read the materials, so attach a 2 m copper plate standing duct or
operation manual. smoke back flow prevention damper.

English 3

3P130768-2H

VKM-GA(M) series 63
Installation ED71-440B

(2) Use suspension bolts for installation. Check whether 5 THE METHOD OF INSTALLATION
the ceiling is strong enough to support the weight of
the unit or not. If there is a risk, reinforce the ceiling CAUTION
before installing the unit. ¢¢Hold underside of the unit or hanger bracket without
(Installation pitch is mentioned as follow. Refer to it to check putting force on other parts when unpacking or moving
for points requiring reinforcing.) the unit.²²
¢¢As for the parts to be used for installation work, be sure to
4 PREPARATIONS BEFORE INSTALLATION use the provided accessories and specified parts desig-
(1) Confirm the positional relationship between the unit nated by our company.²²
and suspension bolts. (Refer to Fig. 2)
(1) Install the unit temporarily.
Leave space for servicing the unit and include inspection • Attach the hanger bracket to the suspension bolt. Be sure
hatches. (Always open a hole on the side of the electric parts to fix it securely by using nuts (M10, M12) and washers
box so that the air filters, heat exchange elements, fans, and (M10 with external dia. 30 to 34 mm, M12 with external
humidifier elements can easily be inspected and serviced.) dia. 36 to 38 mm) (locally procured) from the upper and
1764 Unit (mm) lower sides of the hanger bracket. (Refer to Fig. 4)
1688
Hanger bracket
(Suspension Duct layout precaution label

(Suspension bolt pitch )


bolt pitch)
Exhaust air to Return air from Nut
outdoors (EA) room (RA) Washer
A
B

Fresh air from Supply air to Transportation


outdoors (OA) room (SA) anchors Double nut
Screw
360(If the inspection Electric parts box
hatch is 450)
140(If the inspection Fig. 4
hatch is 600) Inspection hatches Fig. 2
(2) If unnecessary, remove the four transportation
(mm) anchors.
• Loosen the screws.
Model A B
• Slide upward and remove the transportation anchors.
VKM50GAMV1, VKM50GAV1 832 878 • Securely tighten the screws as before.
VKM80GAMV1, VKM80GAV1
1214 1262 CAUTION
VKM100GAMV1, VKM100GAV1
• The screws shouldn’t be removed from the unit and should
(2) Make sure the range of the unit’s external static pres-
be tightened in order to prevent air from escaping.
sure is not exceeded.
• Check that foreign objects such as plastic or paper are not
(See the fan-strength and static performance characteristic
contained in the unit when installing.
drawings as well as the general catalog for the range of the
external static pressure setting.) • Install the unit after checking the indoor (SA/RA) and out-
(3) Open the installation hole. (Pre-set ceilings) door (EA/OA) in accordance with the figure duct layout
• Once the installation hole is opened in the ceiling where precaution label.
the unit is to be installed, pass refrigerant, drain piping, • Do not turn the unit upside down.
transmission wiring, and remote controller wiring to the (3) Adjust the height of the unit.
unit’s piping and wiring holes. (Tighten the double nuts securely.)
See “6 DRAIN PIPING AND SUPPLY WATER WORK”,
“7 REFRIGERANT PIPING WORK”, and
“10 WIRING EXAMPLE AND HOW TO SET THE
REMOTE CONTROLLER”.
• After opening the ceiling hole, make sure ceiling is level if
needed. It might be necessary to reinforce the ceiling
frame to prevent shaking.
Consult an architect or carpenter for details.
(4) Install the suspension bolts.
(Use M10 to M12 suspension bolts.)
Use a hole-in-anchor, sunken insert, sunken anchor for
existing ceilings, or other part to be procured in the field to
reinforce the ceiling to bearing the weight of the unit.
(Refer to Fig. 3)
Ceiling slab
Anchor bolt
Antivibration lifting
lug or turn buckle
Suspension bolt
Indoor unit
Note: All the above parts are locally procured.
Fig. 3

4 English

3P130768-2H

64 VKM-GA(M) series
ED71-440B Installation

(4) Check the unit is horizontally level.


CAUTION
CAUTION Do not connect the drain piping directly to sewage pipes
Use a level to make sure that the unit is level and that that smell of ammonia. The ammonia in the sewage might
the tilt (downward slope) to the drain piping connection enter the indoor unit through the drain pipes and corrode
is within 1°. (Refer to Fig. 5) the heat exchanger (Direct expantion coil).
(One thing to watch out for in particular is if it is installed so
• Keep the drain pipe short and sloping downwards at a
that the slope is not in the direction of the drain piping, as
gradient of at least 1/100 to prevent air pockets from
this might cause leaking.)
forming. (Refer to Fig. 7-2)
• If converging multiple drain pipes, install according to the
Level 10 or less 10 or less Level procedure shown below. (Install a drain trap for each
indoor unit.)

Central drain piping


Drain hole Dact connecting
Drain hole flange

or more
100mm
Horizontal line

(Install with a downward slope of at least 1/100)


Fig. 7-2

Fig. 5 CAUTION
(5) Tighten the upper nut. Water accumulating in the drain piping can cause the
drain to clog.
(6) Attach the accessory duct connecting flanges using
the included screws to the outlet and intake holes
• The diameter of the drain pipe should be greater than or
(a total of four).
equal to the diameter of the connecting pipe.
When attaching, make sure the alignment markings on the
(pipe size: PT3/4B)
unit match up with the triangle on the each duct connecting
• When piping passes indoors, always insulate it all the
flange. (Refer to Fig. 6)
way to the base of the drain socket.
Screws (accessory) • In areas where freezing may occur, always take steps to
(6pcs.×4, total 24pcs.) prevent the pipes from freezing.
• Make sure water doesn’t leak from the drain pipes.
Duct connecting flange marking • Avoid bends and curves in the pipes to prevent them
getting clogged.
• If you are using central drain piping, follow the procedure
Unit alignment outlined in the figure 7-2.
Duct connecting • Select central drain pipes of proper size according to the
(RA is a φ3 indentation)
flange capacity of the connected unit.
Duct connecting flange • Make sure the tip of the drain pipes opens out into a loca-
Fig. 6 tion where the drainage can be safely processed.
(2) After piping work is finished, check drainage flows
6 DRAIN PIPING AND WATER SUPPLY smoothly.
WORK • Test the drainage by pouring around 1000cc of water into
the drain pan through the inspection hole by removing the
(1) Install the drain piping. maintenance cover (10 screws) or through the outlet duct
• Make sure the drain works properly. joint of supply air to room (SA). (Refer to Fig. 8)
• In case of the direct duct connection system,
there is negative pressure inside the unit relative to atmo- Supply air to room (SA)
spheric pressure when the unit is running, so be sure to Duct connecting flange
provide drain frap on the drain outlet. (See Fig. 7-1) (accessory)
Maintenance cover
Attached drain hose Portable pump
(Locally procured)
Bottom of unit

Drain outlet
or more or more

Bucket
50 mm 50 mm

Drain piping
(Locally procured)
(Locally procured)
Fig. 8 (Figure shows VKM-GAMV1)

(3) Make sure that heat insulation work is executed on the


following 2 spots to prevent any possibility water leak-
age due to dew condensation.
Fig. 7-1 • Indoor drain piping
• Drain outlet

English 5

3P130768-2H

VKM-GA(M) series 65
Installation ED71-440B

(4) Install the water supply piping. ¢VKM-GAMV1 series only² • Also, if the supply water is hard water, use a water soft-
ener because of short life.
CAUTION Life of humidifying element is about 3 years (4,000
When installing the water supply piping, wash the pipes with hours), under the supply water conditions of hardness:
tap water so that all dirt is removed from them or install a 150mg/l.
drain valve somewhere along the piping and drain the pipes (Life of humidifying element is about 1 year (1,500
thoroughly until the water flowing through them is clear. hours), under the supply water conditions of hardness:
Make sure no cutting oils or detergents get into the pipes. 400mg/l.)
Annual operating hours: 10 hours / day × 26 days /
month × 5 month = 1,300 hours
• Connect the water supply piping with strainer (acces-
sory), other pipings and valves (locally procured) to the (5) Insulate all piping that passes indoors.
indoor unit as shown in the figure at below. After checking that the water supply piping connections do no
leak, insulate them using the included insulation as shown in
Fig. 10. (Tighten both edges with clamping material.)
(Refer to Fig. 10)
Clamp
Water supply piping (accessory)
with strainer
(accessory)
Insulation
Water supply shut-off Cap (for water supply piping)
valve (Locally procured)
(Locally procured) (accessory) Fig. 10
Water supply pipe Drain valve • Wrap the water supply piping with insulation to prevent con-
densation from forming.
(Locally procured) (Locally procured)
• In areas where freezing may occur, always take steps to pre-
vent the pipes from freezing.
[PRECAUTION]
• When installing the water supply piping, do not pass pip-
ing in front of the maintenance cover, as this will make it 7 REFRIGERANT PIPING WORK
impossible to remove the humidifier element. ¢For refrigerant piping of outdoor units, see the installation
• Include the water supply piping with strainer (included), a manual attached to the outdoor unit.²
water supply shut-off valve, and a drain valve (both locally ¢Execute heat insulation work completely on both sides of
procured) somewhere along the water supply piping that the gas piping and the liquid piping. Otherwise, a water
can be reached from the inspection hole. leakage can result sometimes.
• It is impossible to connect the water supply piping directly Use insulation that can withstand temperatures of at least
to public piping. Use a cistern tank (of the approved type)
120°C. Improve insulation of refrigerant piping according
if you need to get your water supply from public piping.
• When using copper piping for the water supply connec- to the installation environment.
tions, replace the included half-union joints. Refer to the following information as a guide.
(Refer to Fig. 9) • The ambient temperature is 30°C and humidity is 75% to
80%: 15 mm min. in thickness.
Replacement of joints when using copper connections • The ambient temperature exceeds 30°C and the humidity
Flare nut Half-union joint exceeds 80%: 20 mm min. in thickness.
(accessory) (accessory) Without reinforcement, condensation may form on the sur-
Water face of the insulation. ²
supply Unit
piping ¢Before refrigerant piping work, check the type of R410A
side side refrigerant is used. (Proper operation is not possible if the
Copper piping types of refrigerant are not the same.)²

Y-shaped CAUTION
strainer
Remove This product must use a new refrigerant (R410A).
Fig. 9 Exchange the included half-union joint Obey the following items.
• Use a pipe cutter and flare suitable for the type of
• Use two spanners when attaching or removing pipes to refrigerant (R410A).
the half-union joints. • Apply ester oil or ether oil around the flare portions
• Secure the water supply piping without applying pressure before connectioning.
[PRECAUTIONS] • Only use the flare nuts included with the unit. Using
• Use pure water (city water, tap water or equivalent) that different flare nuts may cause the refrigerant to leak.
satisfies the standard regulated by the law of each coun- • To prevent dust, moisuture or other foreign matter
try for water supply to the humidifier when performing from infiltrating the tube, either pinch the end or
anti-sweat work. cover it with tape.
• Dirty water may cause valves to clog, dirt to accumulate • Do not allow anything other than the designated refrig-
in water tanks, and resulting in poor humidifier perfor- erant to get mixed into the refrigerant circuit, such as
mance. (Never use water from a cooling tower or warm air, etc. If any refrigerant gas leaks while working on
water for heating.) the unit, ventilate the room thoroughly right away.
• Make sure the supply water is between 5°C and 40°C in
2
temperature and 0.02MPa to 0.49MPa (0.2kg/cm to • The outdoor unit is charged with refrigerant.
2
5kg/cm ) in pressure. Include a pressure release valve • Be sure to use both a spanner and torque wrench together,
between the humidifier and the strainer if the water pres- as shown in the drawing, when connecting or disconnecting
sure will be higher than this range. pipes to the unit. (Refer to Fig. 11)
• Use city water or clean water and take steps to prevent • Refer to the “Table 1” for the dimensions of flare nut spaces.
condensation from forming.

6 English

3P130768-2H

66 VKM-GA(M) series
ED71-440B Installation

Table 1 Precautions for insulation material installation on flare nut


Pipe Flare dimen- connection
Tightening torque Flare shape
gauge sion A (mm) (1) Make sure that the piping insulation material comes in close
 contact with the base so that there will be no air passage at
I 6.4 14.2–17.2N·m 8.7 – 9.1

0
the edges of the piping insulation material.

45 Ⳳ2
R0.4-0.8

0
90 Ⳳ2
0
(2) Do not tighten the clamp excessively so as to maintain the

A
I12.7 49.5–60.3N·m 16.2 – 16.6 appropriate thickness of the insulator.
(3) Wrap the sealing material around the upper
part of the flare nut connection. Seams up
• When connecting the flare nut, coat the flare section (inside)
with ester oil or ether oil, rotate three or four times first, then (4) Turn the seams up (see the figure on the right-
screw in. (Refer to Fig. 12) hand side).

Torque wrench CAUTION


Be sure to insulate any field piping all the way to the piping
Ester oil or ether oil
connection inside the unit. Any exposed piping may cause
condensation or burns if touched.
Spanner
Flare nut • Connect refrigerant piping and branching according to the
Piping union attached installation manuals that come with the outdoor unit.
Fig. 11 Fig. 12 Gas piping Liquid piping
Model
• Refer to the “Table 1” for tightening torque. diameter diameter
CAUTION VKM50GAMV1, VKM50GAV1
VKM80GAMV1, VKM80GAV1 I 12.7 I 6.4
Over-tightening may damage the flare and cause a VKM100GAMV1, VKM100GAV1
refrigerant leakage.
• When brazing the refrigerant piping, perform nitrogen
• If a torque wrench is not available, tighten the nut in the fol- replacement first, or perform the brazing (note 2) while
lowing manner. Once work is complete, make sure there is feeding nitrogen into the refrigerant piping (note 1), and
no gas leaking. As the flare nut is tightened with the wrench, finally connect the indoor unit using the flare connections.
the torque will suddenly increase. From that position, tighten (Refer to Fig. 14)
the nut to the angle shown on “ Table 2 ”.
Pressure-
Table 2 reducing valve
Recommended arm Part to be
Pipe size Further tightening angle brazed Taping
length of tool
I6.4 (1/4”) 60 to 90 degrees Approx. 150mm
Nitrogen
I12.7 (1/2”) 30 to 60 degrees Approx. 250mm hands
Refrigerant piping valve Nitrogen
• After the work is finished, make sure to check that there is no Fig. 14
gas leak.
• After checking the pipe-connection for gas leakage, be sure CAUTION
to insulate the liquid and gas piping. (Refer to Fig. 13) • When brazing a pipe while feeding nitrogen inside the pipe,
make sure to set the nitrogen pressure to 0.02MPa
2
(0.2kg/cm ) or less using the pressure reducing valve.
Gas Piping Insulation Procedure
(This pressure is such that breeze is blown to your cheek.)
• Do not use a flux when brazing the refrigerant pipe joints.
Piping insulation Insulation for fitting (accessory) Use phosphor copper brazer (BCuP-2: JIS Z 3264/B-
material (main unit) Cu93P-710/795: ISO 3677) which does not require flux.
Flare nut Mid sealing pad
(1) Attach to base connection (4) Turn seams up (Using a flux containing chlorine may cause the piping to
(accessory)
corrode. Using a welding flux containing fluorine may
Main unit
cause the refrigerant lubricant to deteriorate, and affect
adversely the refrigerant piping system.)
(2) Clamp (3) Wrap over the
(accessory) Piping insulation material • Do not use anti-oxidants or other similar agent when braz-
top of the flare
(locally procured) nut connection. ing the pipe joints.
Residue can clog the pipes and may cause breakdown of
parts.
Liquid Piping Insulation Procedure

Insulation for fitting


Piping insulation (accessory)
material (main unit)
Gas pipe (1) Attach to base Flare nut connection
(4) Turn seams up
Liquid Main unit
pipe
(2) Clamp
(accessory) Piping insulation material
Fig. 13 (Locally procured)

English 7

C: 3P130768-2H

VKM-GA(M) series 67
Installation ED71-440B

8 DUCT CONNECTION • When connecting the indoor unit directly to the duct, always
¢Perform duct work keeping the following things in mind² use the same system on the indoor unit as with the outdoor
unit, perform group-linked operation, and make the direct
• Do not connect the ducts as shown in Fig. 15. duct connection settings from the remote controller (Mode
(a) Exterme bend (b) Multi bend (c) Reduce the (d) a bend right No. “17 (27)” – FIRST CODE NO. “5” – SECOND CODE NO.
(Do not bend the diameter of the next to the “06”) Also, do not connect to the outlet side of the indoor unit.
duct over 90˚) duct to be outlet Depending on the fan strength and static pressure, the unit
might back up.
connected.
• In the case of suburban buildings where windows and road
lighting equipment are close to the air supply opening and
insects tends to swarm around the light, minute insects may
intrude indoors through the air supply opening and air filter.
(Do not reduce the duct In such cases, the use of a high-performance filter (sold sep-
Fig. 15 diameter halfway.) arately) is recommended. However, it may be still difficult to
prevent the intrusion of very minute insects. In that case, con-
• The minimal radius of bends for flexible ducts are as follows. sider ultimate countermeasures, such as a filter box
200-mm duct : 300mm diameter (arranged on site).
250-mm duct : 375mm diameter
• To prevent air leakage, wind aluminum tape round the sec- 9 ELECTRIC WIRING WORK
tion after the duct connecting flange and the duct are con- • Shut off the power before doing any work.
nected. (Refer to Fig. 16) • All field supplied parts and materials, electric works must
conform to local codes.
• To prevent short circuit, install the opening of the indoor air • Use copper wire only.
intake as far as from the opening of the exhaust suction. • All wiring must be performed by an authorized electrician.
• See also the “Electrical Wiring Diagram label” attached to the
• Use the duct applicable to the model of unit used (Refer to electric parts box lid when laying electrical wiring.
the installation drawing.) • Wire the outdoor unit and remote controller as shown in the
• Install the two outdoor ducts with down slope (slope of 1/30 electric wiring diagram label. See the “Remote Controller
or more) to prevent entry of rain water. Also, provide insula- Installation Manual” for details on how to install and lay the
tion for three ducts (Outdoor ducts and Indoor supply air wiring for the remote controller.
duct) to prevent dew condensation. • This system consists of multiple indoor units. Mark each
(Material : Glass wool of 25mm thick) (Refer to Fig. 16) indoor unit as unit A, unit B..., and be sure the terminal board
• If the level of temperature and humidity inside the ceiling wiring to the outdoor unit and BS unit are properly matched.
is always high, install a ventilation equipment inside the If wiring and piping between the outdoor unit and an indoor
ceiling. unit are mismatched, the system may cause a malfunction.
• Install a wiring interrupter or ground-fault circuit interrupter
• Insulate the duct and the wall electrically when a metal duct for the power wiring.
is to be penetrated through the metal lattice and wire lattice • Make sure the ground resistance is no greater than 100:.
or metal lining of a wooden structure wall.
This value can be as high as 500: when using a ground fault
• Using flexible or silent ducts can be effective in reducing the circuit interrupter since the protective ground resistance can
air discharge sound of the supply air to room (SA). Select
materials keeping in mind the fan strength and operating be applied.
sound of the unit. Consult your Daikin dealer for selection. • Do not let the ground wire should come in contact with gas
• Set the pitch between the exhaust air outlet (EA) and the out- pipes, water pipes, lighting rods, or telephone ground wires.
side air intake (OA) to 3 times the duct diameter. • Gas pipes: gas leaks can cause explosions and fire.
• Do not use a bent cap or a round hood as the outdoor hood • Water pipes: cannot be grounded if hard vinyl pipes are used.
if they might get rained on directly. (We recommend using a • Telephone ground and lightning rods: the ground poten-
deep hood (optional accessory).) tial when struck by lightning gets extremely high.
• When using a deep hood, make sure the duct from the deep • Do not turn on the power supply (switch, wiring interrupter or
hood (outer wall) to the unit is at least 1m long. ground fault circuit interrupter) until all other works are done.

SPECIFICATIONS FOR FIELD SUPPLIED FUSES


Outdoor duct
AND WIRE
Remote controller wiring
Power supply wiring
Slope: Transmission wiring
Aluminum tape Over 1/30 Insulation material Model Field
(Locally procured) Make sure there (Locally procured) fuses Wire Size Wire Size
is no slack in the duct.

VKM50GAMV1,
VKM50GAV1
Follow Sheathed 0.75-1.25
VKM80GAMV1, H05VV-
Duct connecting 15A local wire 2
VKM80GAV1 U3G mm
flange standards (2 wire)
VKM100GAMV1,
Aluminum tape VKM100GAV1
(Locally procured)
Fig. 16
• The change of air discharge grill's location should be exam-
ined when the cold draft from air discharge grill is feared.
The fan is driving while defrost operation, and the cold air is
often blowing.

8 English

3P130768-2H

68 VKM-GA(M) series
ED71-440B Installation

NOTE CAUTION
• If the wiring is in a place where people it can be easily
• See “Electrical Wiring Diagram label” on the backside of the
touched by people, install a leak interrupter to prevent
lid of the electric parts box for electric wiring work.
electric shock. • Be sure to attach the sealing material or putty (locally pro-
• When using a ground-fault circuit interrupter, make sure cured) to hole of wiring to prevent the infiltration of water as
to select one useful also to protection against overcurrent well as any insects and other small creatures from outside.
and short-circuit. Otherwise a short-circuit may occur inside the electric parts
If you use a leak interrupter which is designed for protect- box.
ing again ground faults, be sure to combine it with a wir- • When clamping the wires, be sure no pressure is applied to
ing interrupter or an load switch that has a fuse. the wire connections by using the included clamping material
• The length of the transmission wiring and remote control- to make appropriate clamps. Also, when wiring, make sure
ler wiring are as follows. the lid on the electric parts box fits snugly by arranging the
wires neatly and attaching the electric parts box lid firmly.
Length of outdoor-indoor transmission
When attaching the electric parts box lid, make sure no wires
wiring … max 1000m (total wiring length 2000m)
get caught in the edges. Pass wiring through the wiring
Length of remote controller wiring between indoor through holes to prevent damage to them.
unit and remote controller … max 500m • Make sure the remote controller wiring, the wiring between
the units, and other electrical wiring do not pass through the
ELECTRICAL CHARACTERISTICS same locations outside of the unit, separating them by at least
Units Power supply Fan motor
50mm, otherwise electrical noise (external static) could
cause mistaken operation or breakage.
Model Voltage
Hz Volts MCA MFA kW FLA
range
10. 2 Connecting power supply wiring and ground
VKM50GAMV1,
4.3 15 0.28×2 1.9×2 wiring
VKM50GAV1
Max. • Pass the power supply wiring and the ground wiring through
VKM80GAMV1, 220- 264V
50 4.3 15 0.28×2 1.9×2 the wiring through-hole into the electrical parts box and
VKM80GAV1 240V Min.
198V secure with the included clamping material after connecting
VKM100GAMV1, the wires to terminal blocks. (Refer to Fig. 17-1, 17-2)
4.3 15 0.28×2 1.9×2
VKM100GAV1
〈 VKM-GAMV1 series 〉
MCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A)
Terminal block (X1M) details
kW: Fan Motor Rated Output (kW); FLA: Full Load Amps (A) Grounging terminal
(M4 screws, spring
10 WIRING EXAMPLE AND HOW TO SET washers, cup washers)
THE REMOTE CONTROLLER
1 2 L N
10. 1 OPENING AND SHUTTING THE ELECTRIC Short-circuit wire Resin Clamp parts
PARTS BOX AND CONNECTING THE WIRING Remove when installing
the humidistat Power supply wiring
CAUTION (locally procured). Clamp Ground wiring
Be sure to power off before opening the electric parts box. (accessory) Wiring for the
Fig. 17-1 humidistat
• Remove the electric parts box lid and wire as shown in the
figure below.
〈 VKM-GAV1 series 〉
SS1 is the switch for setting Terminal block (X1M) details
Do not change the switch settings. Grounging terminal
the remote controller.
The unit will not run if the settings (M4 screws, spring
Factroy setting washers, cup washers)
are changed. Space for installation of
NOR.
adapter PC board (KRP2A1) H L N
SS1

M
Space for Resin Clamp parts
A2P installation of
A3P Power supply wiring
adapter PC board
(KRP50-2) Clamp Ground wiring
A1P Fig. 17-2 (accessory)
X3M
Clamp
X1M
(accessory) ¢Precautions when laying power supply wiring²
Resin Clamp parts
[PRECAUTIONS]
Transmission wiring [1] A circuit breaker capable of shutting down power supply to
Electric parts Power supply wiring through-hole the entire system must be installed.
box lid and Ground wiring Power wiring through-hole [2] A single switch can be used to supply power to units on the
same system.
NOTE) A3P: VKM-GAMV1 series only However branch switches, branch overload circuit interrupter
must be selected carefully.
[3] Fit the power supply wiring of each unit with a switch and
fuse as shown in the drawing.

English 9

3P130768-2H

VKM-GA(M) series 69
Installation ED71-440B

COMPLETE SYSTEM EXAMPLE 10. 3 Remote power supply wiring, transmission wir-
ing, computerised control wire
Power supply wiring
Sheathed cable • Pass the remote control wiring, the transmission wiring,
VRV (H05VV-03G) and the computerised control wire into the electric
Power supply Outdoor unit Transmission wiring parts box through the through-hole and connect to the
Sheathed cable terminals on the X3M terminal block. After connection,
secure with the included cramping material.
Switch
(Refer to Fig. 18)
Fuse
Detail of terminal block (X3M)

VRV P1 P2 F1 F2 T1 T2
Indoor unit Heat Reclaim Clamp
REMOTE TRANSMISSION FORCED
Ventilator CONTRL WIRING OFF
(VKM) (accessory)

VRV
Indoor unit Remote controller wiring
Heat Reclaim
Ventilator Transmission wiring
(VKM) Fig. 18
Remote controller

[4] Use round crimp-style terminals for connecting wires to the


power supply terminal block. [PRECAUTIONS]
If unavailable, observe the following points when wiring. • Refer to the “Remote Controller Installation Manual” on how
• Do not connect wires of different gauge to the same to install and lay the wiring for the remote controller.
power supply terminal. • Do not, under any circumstances, connect the power wiring
(Looseness in the connection may cause overheating.) to the remote controller or transmission wiring terminal block.
• Use the specified electric wire. Connect the wire securely Doing so can destroy the entire system.
to the terminal. Lock the wire down without applying • Connect the remote controller and transmission wiring their
respective terminal blocks.
excessive force to the terminal. (Tightening torque:
131N·cm ±10%) 10. 4 Wiring for the humidity regulator
Attach insulation sleeve (locally procured)¢VKM-GAMV1 series only²
• Pass into the electric parts box together with the power
wire through the power wiring through-hole.
• Remove the short-circuit wires (1 and 2) on the X1M
terminal block and connect the wiring for the humidity
Round crimp-style terminal regulator.
Electric wire • Secure with cramping material together with the power
wire. (Refer to Fig. 17-1)
[5] Tightening torque for the terminal screws.
• Use the correct screwdriver for tightening the terminal Wiring specifications Sheathed wire (2 wire)
screws. If the blade of screwdriver is too small, the head
of the screw might be damaged, and the screw will not be Size 0.75 - 1.25mm2
properly tightened. Length MAX. 100m
• If the terminal screws are tightened too hard, screws
External contact Normally closed contact
might be damaged.
specifications (Current tolerance 10mA – 0.5A)
• Refer to the table below for the tightening torque of the
terminal screws.
CAUTION
Tightening torque (N·m)
¢VKM-GAMV1 series only²
Treminal block for remote controller/
0.79 – 0.97 • If using humidistat, install one per Heat Reclaim Ventilator.
Transmission wiring (X3M)
Controlling more than one Heat Reclaim Ventilator with a sin-
Power supply terminal block (X1M) 1.18 – 1.44 gle humidity controller may prevent normal humidity opera-
Ground terminal (M4) 1.44 – 1.94 tion and cause water leakage, etc.
¢Precautions when connecting the ground²
When pulling the ground wire out, wire it so that it comes 10. 5 WIRING EXAMPLE
through the cut out section of the cup washer. • This unit can be used as part of the combined operation sys-
(An improper ground connection may prevent a good ground tem used together with indoor units (VRVII system air condi-
from being achieved.) tioners), or as a independent system for processing outside
air.
Round crimp-style terminal • When connecting with a cooling free building multi type and
Cup washer
bringing the RA (exhaust gas intake) of this unit directly in
Spring washer, flat washer
from the ceiling, connect to a BS unit identical to the building
multi indoor unit (master unit), and use group-linked opera-
tion. (See the Engineering Data for details.)

Ground screw Cut out section

10 English

C: 3P130768-2H

70 VKM-GA(M) series
ED71-440B Installation

¢Combined operation system with VRVII system (connected with Heat Reclaim Ventilators and standard indoor units in a single
refrigerant circuit)²

Outdoor unit
Electric parts box
IN/D OUT/D
F1 F2 F1 F2

 
Power supply Power supply
   220-240V 220-240V
 ~ ~
  50 Hz 50 Hz
Switch Switch Switch
Fuse Fuse Fuse

Transmission wiring
Remote controller
Remote controller wiring

Remote controller
R S P1 P2 F1 F2 T1 T2
Standard indoor
R S P1 P2 F1 F2 T1 T2
Standard indoor L N P1 P2 F1 F2 T1 T2 Heat Reclaim
unit A unit B Ventilator A
(outside air
Earth processing type)
Earth Earth

¢Independent system (connected only with a Heat Reclaim Ventilator in a single refrigerant circuit)²

Outdoor unit
Electric parts box
IN/D OUT/D
F1 F2 F1 F2

Power supply Power supply Power supply


220-240V 220-240V 220-240V
~ ~ ~
50 Hz 50 Hz 50 Hz
Switch Switch Switch
Fuse Fuse Fuse

Transmission wiring Remote controller Remote controller

Remote controller
R S P1 P2 F1 F2 T1 T2 R S P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2
Heat Reclaim
Standard indoor Standard indoor Ventilator A
Earth unit A unit B (Outside air
processing or
Earth Earth standard type)
NOTE) Standard type ........ VAM series NOTE)

¢When including a BS unit²


Power supply Power supply
220-240V 220-240V
~ ~ Outdoor unit
50 Hz 50 Hz Electric parts box
IN/D OUT/D

Switch Switch F1 F2 F1 F2

Fuse Fuse Transmission wiring (No polarity)


Remote BS unit
Electric parts box
controller OUT/D IN/D

Remote controller F1 F2 F1 F2

wiring

R S N P F1 F2 T1 T2 L N N P F1 F2 T1 T2
Heat Reclaim Ventilator A
Earth Earth
Standard indoor
unit A

English 11

C: 3P130768-2H

VKM-GA(M) series 71
Installation ED71-440B

[PRECAUTIONS] (2) Add remote controller 2 (slave) to the terminal block for
There is not need to set the indoor unit address when using remote controller (P1, P2) in the electric parts box.
group control. (It is automatically set when the power is turned (There is no polarity.)
on. ) However, since the Heat Reclaim Ventilator (outside air P1 P2 F1 F2 T1 T2
processing type) uses two remote control addresses per unit, REMOTE
CONTRL
TRANSMISSION
WIRING
FORCED
OFF

the number of units which can be group controlled is as follows.


No. of indoor air Remote controller wiring
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 terminal block
conditioner units
No. of
Heat Reclaim 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 Remote Remote
Ventilators controller 1 controller 2
Note: (MAIN) (SUB)
If a simultaneous cooling system is used, a single BS unit
[PRECAUTIONS]
should connect to Heat Reclaim Ventilator (outdoor air-pro-
• Crossover wiring is needed when using group control and
cessing type) and indoor units under group control. If a single
2 remote controllers at the same time.
BS unit connects to the Heat Reclaim Ventilator only, fix the
• Connect the indoor unit at the end of the crossover wire
operating mode of the Heat Reclaim Ventilator to cooling, (P1, P2) to remote controller 2 (slave).
heating, or ventilation.
Max. No. of
10. 6 CONTROL BY 2 REMOTE CONTROLLERS Indoor unit 1 Indoor unit 2 indoor units
(Controlling 1 indoor unit by 2 remote control-
lers)
• When using 2 remote controllers, one must be set to “MAIN”
and the other to “SUB”. Crossover wire (P1.P2)
MAIN / SUB CHANGEOVER Remote controller 1 Remote controller 2
(1) Insert a screw driver into the recess between the (MAIN) (SUB)
upper and lower part of remote controller and, working
from the 2 positions, pry off the upper part. 10. 7 COMPUTERISED CONTROL
(The remote controller PC board is attached to the upper (FORCED OFF AND ON/OFF OPERATION)
part of remote controller.) • Wire specifications and how to perform wiring
Upper part of remote Connect the input from outside to terminals T1 and T2 of the
controller terminal block for remote controller.

F2 T1 T2
FORCED
OFF

Input A

Lower part of The equipment in Nighttime free cooling operation cannot be


remote controller stopped forcibly with T1 or T2.

Insert the screwdriver here and gently work Wire specification Sheathed wire (2 wire)
off the upper part of remote controller. Gauge
2
0.75 - 1.25mm
(2) Turn the MAIN/SUB changeover switch on one of the Length Max. 100m
two remote controller PC boards to “S”. Contact that can ensure the minimum
(Leave the switch of the other remote controller set to “M”.) External terminal
applicable load of 15V DC, 1mA.
• Actuation
S The following table explains FORCED OFF and ON/OFF
(Factory setting) M
OPERATIONS in response to Input A.
Remote controller FORCED OFF ON/OFF OPERATION
PC board
Only one remote controller Input “ON” stops operation (impos- Input OFF oON turns
S
needs to be changed M
sible by remote controllers.) ON unit.
if factory settings have
remained untouched. Input OFF enables control by Input ON oOFF turns
remote controller. OFF unit.

• How to select FORCED OFF and ON/OFF OPERATION


¢Wiring Method²(See “9 ELECTRIC WIRING WORK”.) Enter the FORCED OFF and ON/OFF OPERATION selection
(1) Remove the electric parts box lid. using the local “external start/stop input” settings based on
“11 FIELD SETTING AND TEST RUN”.

10. 8 Central control


If control is performed with a central device (central management
controller, etc.), group number needs to be set with the remote
controller. See the manual of each central device for detail.

12 English

C: 3P130768-2H

72 VKM-GA(M) series
ED71-440B Installation

10. 9 FRESH-UP OPERATION BY EXTERNAL INPUT ¢Operating procedure²


(Heat Reclaim Ventilator) The following describes the operating procedure and
settings.
PURPOSES AND FUNCTIONS
(1) Press the INSPECTION/TRIAL button for more than four
When the operation is interlocked with the local ventilating seconds with the unit in the normal mode to enter the local
fan(such as the one for toilet or kitchen), the Heat Reclaim Ven- setting mode.
tilator performs the over-supply operation to prevent inflow of
the odor from outside. (2) Use the TEMPERATURE ADJUSTMENT button to select
The flow rate of supply air becomes higher than that of exhaust air. the desired “Mode No.” (The code display will blink.)
Both the excessive supply mode(Supply Fresh-up)and the (3) To make settings for individual units under group control
excessive exhaust mode (Exhaust Fresh-up) are selectable. (when mode No. 27, 28 or 29 is selected), press the TIMER
In details, contact your dealer. SETTING ON/OFF button to select the “unit No.” for which
the settings are to be made. (This process is not necessary
EXAMPLE OF CONTROL WIRING when settings are made for the entire group.)
Connecting line can be extended up to 50m maximum.
(4) Press the top section of the TIMER button to select the
“FIRST CODE NO.”
(5) Press the lower section of the TIMER button to select
J1 J2 JC F1 F2 “SECOND CODE NO.”
(6) Press the PROGRAM/CANCEL button once to enter the
settings. (The code display will stop blinking and light up.)
P1 P2 (Terminal for local connection) (7) Press the INSPECTION/TRIAL button to return to normal
mode.
Heat Reclaim
Ventilator

P1 P2

Remote controller

• Local wiring
Operation of Heat Terminal for local Capacity of con-
Reclaim Ventilator connection necting terminal (3) UNIT No.

Fresh-up Short-circuit No-voltage nor- (4) (5) GROUP

mally open contact


for micro-current
Normal Open circuit 12V, 1mA
(3)
Note:
The connecting wiring between Heat Reclaim Ventilator and
the terminal for local connection can be extended up to 50m
maximum.

11 FIELD SETTING AND TEST RUN


11. 1 Perform field settings with the remote
(1) (7) (6) (4) (5) (2)
controller.
(1) Make sure the electric parts box lids are closed on the
indoor and outdoor units.
(2) Depending on the type of installation, make the field
settings from the remote controller after the power is
turned on, following the “Field Settings” manual which
came with the remote controller. (3)
Lastly, make sure the customer keeps the “Field Settings”
(4) (5)
manual, along with the operating manual, in a safe place.

SECOND
CODE NO. Mode No. (3)
FIRST
CODE (6)
NO. SETTING
FIELD
SET MODE (7) (1)
62

11. 1. 1 Field setting


Using the remote controller of the VRV-system air
conditioner to make Heat Reclaim Ventilator settings
¢Initial setting² (4) (5) (2)
• “Mode No.” 17,18 and 19: Group control of Heat Reclaim
Ventilators.
• “Mode No.” 27, 28 and 29: individual control

English 13

C: 3P130768-2H

VKM-GA(M) series 73
Installation ED71-440B

¢Example² NOTE)
When adjusting the ventilation air flow to low setting in the 1. The inside the frame indicates the second code no.
group setting mode, enter the Mode No., “19” FIRST CODE set when shipped from factory.
NO., “0” and SECOND CODE NO., “01”. 2. The settings are applied to the entire group, but if the mode
no. inside the parentheses is selected, the settings can be
■Settings and setting numbers applied to individual indoor units.
However, it is only possible to check any changes made to
Mode FIRST SECOND CODE NO. the settings inside the parentheses in individual mode. (For
Description of setting No. CODE group batch operation, the changes are made but the dis-
1 NO. 01 02 03 04 05 06 07
play remains as it was when shipped from the factory.)
App- App- 3. Do not set anything not shown above. If the applicable func-
Filter cleaning time No
rox. rox. tions are not available, they will not be displayed.
setting 0 coun- – – – –
2500 1250 4. When returning to normal mode, the remote controller is ini-
NOTE) 5 ting
hours hours tialized, so the display might show “88.”
Nighttime free cooling 5. When “Filter cleaning time setting” or “Nighttime free cooling
operation setting 2 4 6 8 operation setting” is changed, explain set contents to the
(Time after air condi- 1 OFF hours hours hours hours – – customer.
tioning is stopped.) later later later later 6. See below for details on the settings for cold areas.
NOTE) 5 – : operate at the set fan strength
Fan speed initial Nor- Ultra Air conditioner fan 01 02 04 06
4 – – – – –
setting 17 mal high
Heating thermo off Operation – – L L
(27) Not Not
Defrost Stop – Stop Stop Stop
direct With direct With
Direct duct connec- duct direct duct direct Oil return Stop – Stop Stop Stop
tion with VRV 5 (Air duct – (Air – duct – In case of Independent operation
setting flow (fan flow (fan
set- off) set- off) Air conditioner fan 01 02 04 06
ting) ting) Heating thermo off Operation – – L L
Setting for cold areas Air Air Defrost Stop – – Stop Stop
(Fan operation selec- flow flow Fan Fan
5 – – – Oil return Stop – – Stop Stop
tion for heater thermo set- set- L L
OFF) NOTE) 6 ting ting – : operate at the set fan strength
Ventilation air flow L : operate at the weak fan strength
Ult-
setting when 17 S : Stop
6 High ra- – – – – –
Nighttime free cooling (27)
High Defrost operation
setting
• In heating operation, freezing of the outdoor unit’s coil
ON/OFF input from increases.
ON/
Outside For- Heating capability decreases and the system goes into
12 OFF
(Set when ON/OFF is 1 ced – – – – – defrost operation.
(22) con-
to be controlled from off • The remote controller will read “ ” until the hot air starts
trol
outside) blowing.
No • It returns to the heating operation again after 6 to 8 minutes
Power faillure Equ- (10 at the longest).
12 equ-
automatic reset 5 ipp- – – – – – • During defrost operation, the fans of the unit continues driv-
(22) ipp-
(Auto Restart) ed ing (factory setting).
ed
Humidification on/off The purpose of this is to maintain the amount of ventilation
15 and humidifying.
when heating thermo 1 No Yes – – – – –
(25) • The change of air discharge grill’s location should be exam-
is off
ined when the cold draft from air discharge grill is feared.
No • Though the fan can be stopped by the setting of remote
Indication of Indi-
Indi- controller.
ventilation mode/Not 4 cat- – – – – –
cat- Do not stop the fan in the place where no ventilation by stop-
indication ion
ion ping the fan may cause the influence of diffusion of air which
No it is dirty and moisture into another room, or the inflow from
Fresh up air supply/ Indication
7 Indication – – – outside the room.
exhaust setting (outflow such as viruses from the sickroom, or smell leakage
18 Supply Exhaust Supply Exhaust
from the rest room, etc.)
External input termi- (28)
Air flow 7. See below for details on the external input terminal function.
nal function selection Fresh- Overall
8 – – – incre- –
(between J1 and JC) up alarm SECOND
ase Input Fan Operation
NOTE) 7 CODE
KRP50-2 output contact operation lamp
Fan Abno- NO.
switching selection 9 – – – – – 01 a Operation On Fresh-up operation
on/off rmal
(between 1 and 3)
Malfunction code “60”
Ventilation air flow 02 a Operation On
0 Low Low Low Low High High is displayed
setting 19
(29) Fan strength up (Low to High,
Ventilation mode Auto- Ex- By- 06 a Operation On
2 High to Ultra-High)
setting matic change pass
Fresh-up operation 1A Off On – – – – – SECOND CODE NO. “04” does not function when in air condi-
tioner linked mode.
Forced fan on 43
Unit no. allocation 45

14 English

3P130768-2H

74 VKM-GA(M) series
ED71-440B Installation

11. 2 Perform a test run according to the outdoor


unit’s installation manual.
(1) Make sure the electric parts box of the unit is closed
before turning on power.
(2) Make a test run following the operation manual of the
outdoor unit.
• The operation lamp of the remote controller will flash
when an malfunction occurs. Check the malfunction code
on the liquid crystal display to identify the point of trouble.
An explanation of malfunction codes and the correspond-
ing trouble is provided in “CAUTION FOR SERVICING” of
the outdoor unit.
If the display shows any of the following, there is a possi-
bility that the wiring was done incorrectly or that the
power is not on, so check again.
Remote controller display Content
• There is a short circuit at the FORCED
“ ” is display
OFF terminals (T1, T2)
“ ” is display • The test-run has not be performed.
• The power on the outdoor unit is off.
• The outdoor unit has not been wired for
power supply.
“ ” is display
• Incorrect wiring for the transmission
“ ” is display wiring and the wiring ¢the remote con-
troller wiring or FORCED OFF wiring.²
• The transmission wiring is cut.
• “MAIN/SUB” setting of the remote
“ ” is display controller is wrong.
• The power on the indoor unit and Heat
Reclaim Ventilator is off.
• The indoor unit and Heat Reclaim Ven-
tilator has not been wired for power
supply.
No display
• Incorrect wiring for the remote control-
ler wiring and the wiring ¢the transmis-
sion wiring or the FORCED OFF
wiring.²
• The remote controller wiring is cut.

11. 3 Next, run the humidifier.


¢VKM-GAMV1 series only²
(1) Check that the water supply piping is connected securely.
(2) Open the water supply shut-off valve. (No water will be
supplied at this time.)
(3) Run the Heat Reclaim Ventilator in heating mode.
(See the operating manual included with the indoor unit
for details on how to run the unit in heating mode.)
The water supply will start and the humidifier will begin
operation.
(4) After starting heating (humidifying), the sound of the
water supply solenoid valve will be heard every
3 or 4 minutes (a clicking sound), so listening for that
clicking sound let the unit run for 30 minutes to make
sure that humidifying operation is normal.
CAUTION
• If carpentry work is not completed when a test run is fin-
ished, tell the customer not to run the humidifier for the pro-
tection of indoor unit and Heat Reclaim Ventilator until it is
completed.
• If the humidifier is run, paint, particles generated from
adhesive and other materials used for carpentry work may
cause Heat Reclaim Ventilator to get dirty, causing splash
or leakage of water.

English 15

C: 3P130768-2H

VKM-GA(M) series 75
Outdoor Air Processing of Ceiling Mounted Duct Connection Type ED71-440B

17. Outdoor Air Processing of Ceiling Mounted Duct


Connection Type
The structure of VKM-GAMV1 model is different from other ventilation models. Points you need to note are
summarized below, which please use for your reference when selecting the model.

17.1 Stand-alone Operation is Possible as an Independent System


Because no function to control the room temperature is equipped, only the operation mode (cooling,
heating, automatic, ventilation) is displayed on the remote controller. Set temperature is not displayed.
(Automatic mode is displayed only when connected with outdoor unit of Heat recovery type.)
In addition, you cannot change the set temperature or set direction of air flow.
Even if you attempt to operate by changing the temperature or air flow direction, only [This function is not
available] will be displayed.
You can select the ventilation mode, ventilation amount and operation switching (if a function to select
either cooling or heating has been provided) only.
Independent system
Switching of ventilation Heating
mode and ventilation Total heat ventilation
amount Ventilation
amount
Strong

Switching of
Ventilation mode operation mode

Ventilation
amount

BRC1C62 Operation switching

17.2 Ability to Calculate Connectable Capacity


Because of an outdoor air processor, the load may increase depending on the outdoor air condition. So,
use the values in the table below when calculating the connectable capacity to an outdoor unit.

Ceiling mounted Corresponding Ability to process outdoor air (kW) Ability to calculate Diameter of
connectable
duct connection type HP Cooling Heating capacity (kW) connection pipe

VKM50GA(M)V1 1.0 4.71 (1.91) 5.58 (2.38) 3.5


φ6.4 for liquid
VKM80GA(M)V1 1.6 7.46 (2.96) 8.79 (3.79) 5.6
φ12.7 for gas
VKM100GA(M)V1 2.0 9.12 (3.52) 10.69 (4.39) 7.0
( ) indicates a heat amount recovered by a total heat exchanger.

Example of a system Connectable capacity of RXYQ10PAY1: 14.0 - 36.4 (kW)


Total calculated capacity of indoor unit: 7.0 + 7.0 × 4 = 35.0 (kW)
Therefore, no more capacity than this is connectable.

RXYQ10PAY1

P71 × 4 units Indoor unit


VKM100GAMV1 × 1 unit

[Features of VKM-GA(M)]
Because VKM-GA(M) model is equipped with a heat exchanger unit, a PCB (corresponding VRV PCB) for
controlling the heat exchanger has been built-in in addition to a PCB for ventilation. These two PCBs are
connected via remote controller line (P1, P2) to perform an interlocked control. Its control system provides
the same condition when 1 ventilation and 1 VRV have been remotely controlled. No air-conditioning
(temperature controlling) function has been equipped. Therefore, it is necessary to prepare separately an
indoor unit for air-conditioning purpose.

Element of Heat
total heat exchanger
exchanger unit

Corresponding
PCB for ventilation VRV PCB Equivalent
P1, P2 P1, P2

BRC1C62
remote controller An image sketch of VKM-GA(M) A group of 1 ventilation/1 VRV indoor unit
for air-conditioner

76 VKM-GA(M) series
ED71-440B Outdoor Air Processing of Ceiling Mounted Duct Connection Type

[Points to be noted for VKM-GA(M)]


There are following restrictions with VKM-GA(M) model due to its own controlling structure.
1. Stand alone system: No address setting is required because of its automatic addressing function
(corresponding VRV PCB: Master).
Because it is under a group control, it is always required to connect to a remote controller. The structure
does not permit if no remote controller is connected. A direct connection to a duct is also prohibited.
2. Interlock system: No address setting is required because of its automatic addressing function (Indoor
unit: Master).
• Basically, the interlocking with an air-conditioner is only made via connection to a remote controller
line (P1, P2).
The display and operation of a
remote controller is the same as
Interlocking of a remote controller group a standard indoor unit.

• Number of units connectable in case of a remote controller group


Because 2 pieces of controlling PCB have been built in a VKM-GAM model, count the remote
controller group as: 1 set = 2 units. The maximum number of units connectable to a remote controller
group is 16.
<Example>
How many units of VKM-GAM model can be connected within a single group?
In case of a group composed of (10 × indoor units + VKM-GAM), the maximum number of VKM-GAM is 3.
10 + 3 × 2 = 16 units OK
In case of 4 units;
10 + 4 × 2 = 18 units NG (2 units are in excess)

• External contact point


If you want to start/stop through an external contact point, use external input terminals (T1 and T2).
* If you start/stop using T1 and T2 terminals, the entire remote controller group makes a start/stop.

Note: 1. JC/J2 of ventilation PCB cannot be used. (Because only the ventilation PCB makes a start/stop, no
synchronized movement with the corresponding VRV PCB is assured.)

17.3 Central Control System


• When carrying out a central connection, connect the central line to F1 and F2 only on the corresponding
VRV PCB. Do not connect to F1 and F2 on the ventilation side. ( = Connect to the terminal block X3M.)
An image sketch of internal wiring on the ventilation side

A1P A2P Terminal block X3M


Note: 1 JC T1
J2 T2
F1 F1
F1
Ventilation PCB Corresponding
F2 VRV PCB F2 F2 Centralized units
P1, P2 P1, P2

Connection to central P1
line is prohibited. P2

Remote controller
for air-conditioner
• In case of a central control, operation ON/OFF can be done separately by each zone. (In this case, zone
interlocked setting must be kept as the factory setting (17. 08. 01).)

VKM-GA(M) series 77
Outdoor Air Processing of Ceiling Mounted Duct Connection Type ED71-440B

• Structure without a remote controller cannot be accepted because the remote controller group is
controlled within a VKM-GA(M) model. (intelligent Touch Controller, central control controller)

Zone interlock setting: None Group interlock zone setting: None Without a remote controller

* Alteration of set temperature and independent ventilation operation cannot be performed from a central device.

17.4 Restrictions to Control System


17.4.1 Do not Give VKM-GA(M) Model a Function to Select Cooling/Heating
(This is because the operation mode switches automatically depending on the outdoor
conditions regardless of the indoor temperature when set to "Automatic")

Give a function to select cooling/heating to either one of these.

17.4.2 Caution When Connecting with a VRVIII System, Heat Recovery Type
When bringing the RA (exhaust gas intake) of this unit directly in from the ceiling, connect to a BS unit
identical to the VRV indoor unit (master unit), and use group-linked operation.

Outdoor unit for heat recovery


EA
OA BS Unit BS Unit
RA

SA
• The system must be operated interlocking
with the air conditioner.

Give a function to select cooling/heating to either one of these.

CAUTION
If above setting is not made, the detection of correct temperature is not available and automatic judgment
on proper cooling or heating cannot be made when the temperature in the ceiling gets higher than indoor
temperature.
Poor heating or shortage of the amount of humidification may result.
If the indoor unit and this unit are installed with different BS system inevitably, always take following
remedies (1) and (2).
(1) RA (Exhaust and suction) of this unit is not taken directly from inside of the ceiling, connect the suction
duct and suction grille to the fitting port of RA duct to suck the indoor air.

Outdoor unit for heat recovery


EA
OA BS Unit BS Unit

SA Suction
grille
RA

Give a function to select cooling/heating to either one of these.

(2) Do not make the selection of heating or cooling in automatic mode and it shall be made by manual
selection from remote controller or centralized controller.

78 VKM-GA(M) series
ED71-440B Outdoor Air Processing of Ceiling Mounted Duct Connection Type

17.4.3 Caution when Connecting the Indoor Unit Directly to the Duct
Follow the indications described below
a) When connecting the indoor unit directly to the duct, always use the same system on the indoor unit as
with the outdoor unit, perform group-linked operation, and make the direct duct connection settings from
the remote controller. (Mode No. “17 (27)” – First code No. “5” – Second code No. “6”.) Refer to
“16. Installation” concerning setting method.

EA
OA

SA Suction
grille
RA

b) Do not connect to the outlet side of the indoor unit. Depending on the fan strength and static pressure,
the unit might back up.
c) When it is connected to the suction side of indoor unit as a direct duct connection system, etc., since
there is a possibility that the body thermo of the indoor unit detects erroneously SA discharge from this
unit as indoor air, use the remote sensor (Optional).

17.5 About the Basic Control of VKM


17.5.1 Basic Control of VKM
VKM sucks the air after OA has subjected to total heat exchange with RA, detects the air temperature by
means of the thermistor for inlet air into DX-coil (R3T) to make a judgment on operation mode, cooling or
heating and exercises the control on the capacity of air heat exchanger.
„ Sensor position and its function
VKM consists of indoor unit + total heat exchanger portion.
Dissimilarities with normal indoor unit are:
- Position of thermostat in the normal indoor unit: Position to detect RA temperature
- Position of thermostat in VKM: Position to detect the air subjected to total heat
exchange between OA and RA.
Therefore, the temperature detected by VKM gets lower than that of the indoor unit thermostat.
Doing so allows VKM to perform treatment of outside air with stability even as the indoor unit stays thermo-
OFF state because of big difference between the set temperature and suction temperature even though the
set temperature of VKM and indoor unit are the same.

Divert the module of indoor unit Divert the module of total heat exchanger

R1T R4T Total heat


Thermistor for exchanger
Thermistor for element
indoor air liquid line
temperature

RA OA

DX-Coil R2T
Thermistor for
R3T outdoor air

SA EA

Humidifier Thermistor or inlet air into DX-coil (R3T)


- This thermistor exercises the control on the capacity of
Electronic heat exchanger by means of electronic expantion valve
expantion in accordance with the difference between detected
valve temperature and set temperature.
- In the case of automatic mode, judgment on operation
R5T mode, cooling or heating is made based on the detected
Thermistor for temperature.
gas line temperature

VKM-GA(M) series 79
Appendix ED71-440B

18. Appendix
18.1 Purpose of Ventilation
Living environment, and working environment as well, can be polluted for various reasons, which in turn will
lead to hygienic problems and/or lower productivity. To avoid this, the polluted air must be replaced with
fresh air. This operation is called ventilation.
To apply ventilation for removing pollution, it is necessary to identify the causes of air pollution before
studying corrective measures.
18.1.1 Air Pollution
„ Dust
There are about 7,500 ~ 22,000 dust particles in the air of one liter. However, if you feel dusty, the number
may have reached as many as 100 ~ 200 thousand. We are unknowingly inhaling such polluted air, which
enters into our trachea and lungs, leading to coughs and difficulty in breathing, some malignant disease
and/or nausea, and in worse cases, other serious chronic diseases such as bronchitis and
pneumoconiosis.
Table 1 Suspended Dust in the Air
Type of dust Content (weight %)
Smoke, pollen, fly ash 0~20%
Ore chips, cinders 10~90%
Rotten plant 0~10%
Vegetable fiber 5~40%
Carbon, fume 0 ~ 40%

„ Bacteria
Suspended particles of bacteria of 0.2~5μ in diameter are likely being adhered with dust in the air, not
independently suspended. According to NASA (the National Aeronautics and Space Administration), the
more number of dust particles may allow the more number of bacteria to exist, which may justify the
abovementioned theory of bacteria's presence in the form of adherence to dust. Therefore, it is possible to
remove bacteria using an electrostatic precipitator, though the result of cleaning cannot be easily
measured. It takes time to demonstrate how effectively bacteria could be removed. According to our
experiments that measured the number of bacteria using the settle plate microbe count method, the
number of bacteria in the space above the dust collector electrode is smaller than that collected on a plate
of the same area being left in the air. This indicates that electrostatic precipitators can, to some extent, kill
bacteria collected on the electrode.
Table 2 Particle diameter of dust

Ultra/electronic microscope Optical microscope Naked eye

Atmospheric dust

Fume Dust

Mist Liquid drop

Fog Rain
Virus/protein Road sand
Bacteria and dust

Milk powder Dense fog milk


Molecule Tobacco smoke
Kaolin Flour

Particle soil

Pollen

#8 powder

Prefilter

Medium-/high-performance filter

HEP filter

10-3 10-2 10-1 1 10 102 103 (μm)


Particle diameter

80 VKM-GA(M) series
ED71-440B Appendix

„ Tobacco
Only one cigarette can soon pollute the air in the enclosed room. And both the smoker and other non-
smokers staying here are affected. Especially the “secondhand” smoke from the tip of cigarette contains
2~3 times larger amount of harmful substances (nicotine and tar) than the “main smoke” exhaled by the
smoker, so that the non-smokers around the smoker can be affected by tobacco smoke.
So, tobacco smoke is one of the serious causes of interior air pollution. Tobacco smoke consists mainly of
mists such as tar and nicotine, gases such as carbon monoxide (CO), carbon dioxide (CO2), hydrogen and
various hydrocarbons including methane, and traces of hydrogen cyanide, formaldehyde, acrolein,
ammonia and nitrogen oxides (NOx), so that various human health problems including lung cancer, chronic
CO toxication and bronchitis can occur.
New ceilings, walls, furniture and decorations in white will turn into yellow in one or two years. This is due to
the nicotine and tar contained in tobacco smoke, and/or dust in the air.
To allow smoking, proper ventilation is inevitable. A ventilation system consisting of an air cleaner and
ventilator that operates automatically detecting the level of pollution is recommendable. This system can be
associated with an air conditioning system, so that power consumption for these systems can be reduced,
and so that they can enjoy comfortable smoking without feeling hot or cold.
Table 3 Sensation for Tobacco Smoke
Smoke concentration
(mg/m3) Status of the air in the room Sensation

0.15 Smoke diffuses in 6 to 30 seconds. Slight odor


0.44 Slightly smoky Odor
0.78 Slightly smoky Feel strange in the nose and/or throat
0.95 Blurred sight Strong odor
1.13 Blurred sight Slight eye irritation
1.26 Heavily smoky Nose and throat irritation
1.48 Heavily smoky Slight pain of eyes
1.73 Heavily smoky Pain of nose and throat
1.95 Heavily smoky Slight tears

Table 4 Air Pollutants per Cigarette (when smoking) Fig 1 Three-Year-Old Child Asthmatic
Type NOx (cc) CO (cc) DUST (mg) Bronchitis Due to Passive Smoking
0.90 72 12.6 5
Asthmatic Bronchitis (%)

Seven Stars 0.57 38 7.7


4
0.77 68 11.3 3.4%
3 2.8%
Table 5 Air Pollutants per Cigarette (when a lit cigarette is left)
2 1.7%
Type NOx (cc) CO (cc) DUST (mg)
1
Seven Stars 1.26 45 6.3
0
0 1 to 20 More than 20
cigarettes cigarettes
per day per day

„ Carbon monoxide (CO)


Carbon monoxide is colorless, odorless and very toxic gas. Imperfect combustion of briquette, charcoal or
oil produces CO gases. Tobacco smoke and automobile exhaust gases also contain CO gases.
CO gases inhaled into the lung join together with hemoglobin in the blood, which result in preventing the
bonding between oxygen and hemoglobin, leading to inability to convey oxygen to the tissues of the human
body. The bonding force between CO and hemoglobin is 200 ~ 300 times larger than that between oxygen
and hemoglobin.
A typical symptom is headache. The motor of their limbs is anaesthetized before losing consciousness, so
that they cannot escape away from the place, which may, in the worst case, lead to fatal accident. Inhaling
CO gases repeatedly may lead to chronic poisoning, with short memory, or in the worst case, he (she) is
crippled for life.
The normal atmosphere contains about 21% of oxygen. Combusting the air will reduce the oxygen
concentration. When it reduces to 19%, CO concentration starts to increase quickly. This quick increase in
CO concentration occurs earlier with the lower combustion rate. This is a reason for larger number of CO
poisoning accidents due to imperfect combustion. During combustion, using both exhaust ventilation and
supply of fresh air is preferable.

VKM-GA(M) series 81
Appendix ED71-440B

Table 6 Effect of Carbon Monoxide (CO)


Concentration (ppm) Effect of change in concentration
0.01~0.2 Standard atmosphere
5 Long-term based allowable value
Building Standard Act and Building Control Act
10 use this value as the 24-hour average
environmental standard.
About 5 ppm in annual average
20 Short-term based allowable value: 8-hour for urban roads; over 100 ppm
average environmental standard
possible for motor highways,
Vocational environment allowable concentration tunnels and parking areas
50
(Japan Industrial Safety and Health Association)
No effect up to 3 hours, effect after 5 hours,
100 headache after 8 hours, malignant disease, long-
term harmful, non-lethal
200 Slight pain in the forehead within 2~3 hours
400 Pain in the forehead within 1~2 hours, and occipital part within 2~3 hours
800 Headache, giddiness, nausea and convulsion in 45 minutes, and swoon in 2 hours
1,600 Headache and giddiness in 20 minutes, and death in 2 hours
3,200 Headache and giddiness in 5~10 minutes, and death in 30 minutes
6,400 Death in 10~15 minutes
11,800 Death in 1~3 minutes
Scores of thousands ppm Possible for automobile exhaust emissions
(several %)
Source: Facility Check List published by Eikoku-Sha
Fig 2 Relationship in Concentration between Oxygen and CO
CO production rate
(m3/kg)

0.020

0.015

0.010

Smaller
combustion rate

0.005

Larger
combustion rate
18 19 20 21
Oxygen concentration (%)
<CO safety limit is 10 ppm with max. 5 ppm recommended>

„ Carbon Dioxide (CO2)


Carbon dioxide gas is a normal component of the air, normal concentration of about 0.04%.
Physiologically, CO2 gas is requisite for human life: the gas stimulates the respiratory center for
unconscious, automatic breathing. CO2 gases dissolve into blood to maintain the oxygen concentration at
the proper level for the purpose of sustaining normal functions of human body. Hygienically, CO2 gases are
used as an indicator of the atmospheric condition in the room, not treated as a toxic gas.
Higher concentration of CO2 gas will adversely affect the human body, though the effect closely depends
on the oxygen concentration.

82 VKM-GA(M) series
ED71-440B Appendix

Table 7 Effect of Carbon Dioxide (CO2)


Concentration (%) Effect of change in concentration
0.03 (0.04) Standard atmosphere
0.04~0.06 Urban atmosphere

0.07 Allowable concentration for many persons


staying in a room These concentration limits are
Allowable concentration for general cases: defined as a pollution indicator
0.10 adopted by the Building Standard Act and within a hypothesis that the
Building Control Act physical and scientific
properties of the air will
Allowable concentration for ventilation become worse with the
0.15
calculation increase in the concentration
of CO2, not based on its own
0.2~0.5 Worse result harmfulness.
0.5 or larger Worst result
0.5 Long-term safety limit (US Labor Health) ACGIH, Labor Office Rule
2 30% increase in breathing depth and air amount inhaled
Lower working performance, change in physiological functions, and twice larger
3
number of breaths
4 Concentration for normal breathing
Stimulates the respiratory center for taking a deeper breath and increasing the
4~5 number of breaths; longer breathing time is a sign of danger; O2 starvation will
raise the possibility of physical disorder outbreak earlier than usual

8 10-minute breathing will result in serious difficulty in breathing, hectic cheeks and
headache; O2 starvation will enhance the possibility of this disorder
18 and larger Lethal

„ Sulfurous acid gas


Volcano exhaust, automobile exhaust or oil fuel-combusted gas and mist contain sulfurous acid gases in
the form of being adhered or absorbed onto suspended dust particles. These gases are a possible cause of
chronic bronchitis or other respiratory diseases.

„ Nitrogen oxides
Nitrogen oxides (NOx) include NO, NO2, NO3, N2O, N2O3 and N2O4. Of these, NO and NO2 are harmful
and account for large portions of NOx compounds. NO2 (nitrogen dioxide) can easily reach the deepest
part of the lung, and adversely affect it and other organs. In terms of long-term adverse effect, NOx is
stronger than sulfurous acid gases. Dusts can enhance the adverse effect of NOx gases.
NO (nitrogen monoxide) is also harmful, though its chronic effect is yet to be clarified.

• NO2 produced by other than combustion


Oil heaters and gas ovens for oxygen-based combustion produce a large amount of NO2 gases. Electric
ovens also produce NO2 gases though their amount is smaller, and this is not well-known. That is, high
temperatures, regardless of combustion, facilitate bonding between N and O atoms in the air, which results
in the increase in the amount of NO2. Continual generation of high temperatures in an enclosed space thus
requires ventilation.
<NO2 safety limit = 0.04 ppm~0.06 ppm>
Table 8 Effect of SO2 on Human Body
Concentration (%) Effect of change in concentration
1 Feel of slight oppression in the chest
3~5 Feel odor
7~12 Stimulant odor
20~40 Significant stimulation, eye irritation and coughing
100~200 Bronchitis and significant stimulation in the chest; and lung disorder
300 Impossible to breath
400 Difficulty in breathing
500 Impossible to breath

„ Oxygen starvation
About 21% of O2 concentration is normal for human body. Lower O2 concentration will cause difficulty in
breathing with other various symptoms. O2 concentration of 8% or lower will have a fatal effect. Higher O2
concentration will cause our pulse rate to increase, which leads to larger burdens on the heart. Abnormally
higher O2 concentrations invite another danger: higher ignition possibilities. Therefore, artificial oxygen
supplies should be avoided. The most effective way for avoiding oxygen starvation is to supply natural air
that contains oxygen concentrations appropriate for human life.

VKM-GA(M) series 83
Appendix ED71-440B

• Yawning is a sign of insufficient oxygen


You may think that persons who frequently yawn have no concentration. However, this is not the case
depending on the situation. Yawning is a physiological phenomenon that can occur when the brain is
suffering from the shortage of oxygen. Concentration can be reduced by the shortage of oxygen. Yawning
is an action to try to keep himself (herself) concentrated. Fresh air required for human body is min. 30 mg
per hour. This corresponds to the oxygen amount contained in a room of normal size (about 10 m2), which
suggests that four persons of a family cannot stay for more than one hour in an enclosed, non-ventilated
living room about four times larger than a normal size bed room or private room. Yawning should be
considered a sign of oxygen shortage. In such cases, immediately take fresh air into the room.
Table 9 Effect of Oxygen (O2) Concentration
Concentration (%) Standard, and effect of change in concentration
About 21 Standard air
Ventilation shall have a target of not decreasing the O2 concentration by 0.5% or larger
20.5 from the normal value (Building Standard Act)
In the normal atmospheric pressure, this small reduction in O2 concentration unlikely
20~19 affects our lives, though in the case of using a combustion apparatus, possible imperfect
combustion may cause the CO concentration to increase quickly.
18 Standard of Labor Safety and Health Law (Oxygen Starvation Preventive Regulation)
16 Concentration during breathing in normal cases
16~12 Increase number of pulses and breaths, giddiness, and headache
15 Combustion apparatuses will be put off
12 Possibility of death within a short time
7 Death

„ Humidity
Humidity has a close relationship with our living environment. Humidity is an additional parameter to be
controlled by air conditioning systems. It may give persons a feel of mild air, if the temperature is relevant
for the humidity. Imbalance between the temperature and humidity (especially higher humidity) leads to
discomfort. A term that is frequently used in summer, “discomfort index,” indicates this imbalance between
temperature and humidity. Higher humidity causes buildings and furniture to rot. Lower humidity causes our
skins to dry and buildings and furniture to crack or warp. Another point for controlling humidity is to avoid
mold, ticks and termites. To satisfy all of these requirements, two types of ventilation must be used in a well
controlled, combined manner. One is to maintain the humidity for our living comfort, and the other one is to
remove humidity where dryness is required to prevent such mold and small animals.
<Relative humidity recommended = 30~70%>

18.2 Kinds of Ventilation


18.2.1 Methods of Ventilation
Natural ventilation based on the natural conditions and mechanical ventilation using mechanical power
„ Natural ventilation
Uses external wind pressures and/or buoyancy force
Exhaust Natural ventilation
produced by the difference in temperature between Supply Natural ventilation
the inside and outside of the room: subject to natural
conditions, so the benefits are unforeseeable, or
smaller than expected.

Warehouse, gymnasium, and plants


where heat is used or produced
„ Mechanical ventilation
Forced ventilation using a power-driven fan or blower produces larger flow in a more stable and timely
manner than natural ventilation.
* To ventilate a more heavily polluted room, it is necessary to keep the room air pressure lower than the
surroundings to avoid the dirty air flowing into the adjacent rooms or passages; for clean rooms, it is
necessary to keep the room air pressure higher than the surroundings to avoid the dirty air coming into
the room.

Exhaust Mechanical ventilation Exhaust Natural ventilation Exhaust Mechanical ventilation


Supply Mechanical ventilation Supply Mechanical ventilation Supply Natural ventilation

Positive Negative
pressure
pressure
Exhaust opening Room
Room Ventilation fan Room Ventilation fan

Ventilation fan Ventilation fan Clean room, machine Intake


Building, parking area in a building, boiler room, cooling, etc. Kitchen, toilet, pantry, etc. in residential
electric room, machine room, galley, warehouse, etc. housing, and copy room, etc.

84 VKM-GA(M) series
ED71-440B Appendix

<Mechanical ventilation>
„ Whole ventilation
This is to replace all air in the room with fresh air. This
Exhaust
system is effective for rooms in which there is a source of
smoke, steam or odor.

Dirty air

Supply

„ Local ventilation
This is to replace air in a limited area where the air is polluted. This is
effective for cases where the source of pollution is stationary and
Supply
concentrated. Combined use with a hood is effective for removing Cooking range
highly contaminated air. hood fan

Ventilation coverage Exhaust

Cooking range
<Important supply flow>
To ensure effective ventilation, sufficient air intakes should be provided.
To ensure stable ventilation, the same amount of fresh air as exhausted should be supplied.
„ Size and location of air intakes
1. Size
Mechanical ventilation fan rated capacities indicated on a catalogue can be used on condition that the
same amount of air is fed into the room through the air intakes. Smaller air intakes will reduce the
capability of the ventilation fan. Generally, the air intakes should be larger than the ventilation fan
opening. Larger air intakes can reduce the air velocity from the intake, so that persons, when standing
near the intake, do not feel discomfort.

Discomfort Noisy Exhaust Smooth air flow Exhaust


due to higher Smaller Smaller velocity
velocity flow

Air intake Air intake

2. Location of exhaust (fans) and intakes


For whole ventilation, air intakes should be located as far from the fans as possible. For local ventilation
intended for narrower, limited space, air intake(s) should be located as close to the fan as possible so
that the surrounding areas can be less affected.

For large rooms, multiple air


intakes should be located
dispersedly and as far from
the exhaust as possible to
ensure uniform ventilation
throughout the room.

Air intake Larger ill-ventilated areas


Bad example

Smaller ill-ventilated areas

Air intake
Good example
Dispersed location of
ventilation fans Air intake
Good example

3. For confined rooms


Ventilating a bathroom with the door tightly closed may
cause the water trap of the drainage to break, which results
in the backflow of odor into the bathroom. In cold weather
areas, ventilating a confined room using a stove with a
natural exhaust ventilation duct may invite backflow of air
into the stove through the exhaust duct, leading to
dangerous combustion condition.

Backflow of air through


the drain piping: cold and smelly

VKM-GA(M) series 85
Appendix ED71-440B

18.2.2 Air Flow (Quantity), and Dynamic and Static Pressure


Ventilation fan performance parameters include air flow (quantity) and static pressure. These two
parameters relate closely to each other. Ventilation cannot be designed without these two parameters. The
first step of “designing a ventilation system” is to understand these two parameters.

„ Quantity
Air flow is the amount of air that a ventilation fan exhausts (or supplies) per unit time, generally expressed
in m3/h or m3/min.

„ Pressure
This is a wind pressure expressed in the unit of Pa. Three types of wind pressure are used.
• Dynamic pressure
This is a pressure produced by wind velocity, also called “velocity pressure.” Deflection of a window
glass by strong wind during typhoon is due to this dynamic pressure.
• Static pressure
When a balloon has been inflated, there is a pressure in the balloon that presses against the
membrane of the balloon. Static pressure is produced also when the air is still.
• Total pressure
This is the sum of wind’s dynamic pressure and static pressure.

„ Relationship between pressure types

Stream

Fan
Ps Pv Pt
Water column
manometer
(Static pressure) (Dynamic pressure) (Total pressure)

“Static pressure (Ps)” is a pressure needed for overcoming the resistance of the duct when conveying air.
“Dynamic pressure (Pv)”, on the contrary, is a pressure due to air stream. To determine air velocity,
measure the dynamic pressure of the air.
The “total pressure (Pt)” is the sum of static pressure and dynamic pressure.
2
V γ
Pt = Ps + Pv = Ps +
2 V: velocity (m/sec)
γ: Air density (kg/m3)

„ P-Q Curve (static pressure - flow characteristic curve)


“P-Q Curve” shows the performance of a ventilation fan by indicating the relationship between air flow and
static pressure.
Fig. a shows a case with a wall-mount supply opening that is so small that the internal pressure becomes
slightly lower than the atmospheric pressure. The static pressure is B mm.
Fig. b shows a case with a wall-mount supply opening that is so large that the internal pressure becomes
almost equal to the atmospheric pressure. The static pressure is 0 Pa.

Fig. a Small Fig. b Large


supply supply
port Slightly lower port Almost equal
than the to the
atmospheric atmospheric
pressure pressure
No difference

Static pressure = point B Static pressure = 0


Static Air flow = point B’ Static Air flow = point C’
pressure pressure

Air flow (m3/h) Air flow (m3/h)

86 VKM-GA(M) series
ED71-440B Appendix

18.2.3 Mechanical Fan Types and their Characteristics


„ Axial fan and centrifugal fan
Ventilation fan are roughly classified into two types: axial fans and centrifugal fans. These two types of
ventilation fans are selected depending on the operating conditions and/or application. Axial fan is normally
a propeller fan available for applications for larger flow but at smaller pressure rating ranging between 0
and 30 Pa. Centrifugal fan is either a sirocco or turbo fan available for applications that need large
pressure, and available for ducted ventilation systems.
<Propeller fan> <Sirocco fan>
• The simplest axial flow fan available for small • Uses the same theory as water wheel; the
capacity applications; larger air flow can be impeller consists of many small fins facing
obtained but at small pressure up to about 30 Pa, forward as shown in the figure below; higher
so that large reduction in flow can occur due to static pressure can be obtained; available for
resistance (e.g. frictional resistance) when various applications.
flowing in a ducted system.

Impeller

Axial direction
Impeller
Motor

<Features> <Features>
• Air flow is larger than sirocco or turbo fans, but • Static pressure is higher but the air flow is
the static pressure is lower. smaller than propeller fans.
<Installation> <Installation>
• Residential housing, external wall mount • Housing complex
<Applications> • Ducted ventilation system
• General ventilator <Applications>
• Window-mount ventilator • Air conditioning system ventilator
• Living room ventilator • Cooking range hood, deep
• Intermediate ventilator, ducted system
• Sirocco fan
„ Impeller characteristics as an essential parameter for type selection
Propeller fans have a smaller pressure rating, which means that the air flow is reduced significantly by
adverse wind. The next table shows the airflow vs. pressure characteristics that differ between propeller
and sirocco fans. Depending on the topography, altitude and/or other conditions, as a general guide,
propeller fans can be used at a height corresponding to the second floor of the building, and other types of
fans having a higher pressure rating should be used at higher locations.
* Even for independent houses, to ventilate a room that does not share any external walls, or if the house
is located in a windy place, use a pressure type fan.

Wind velocity vs. wind pressure, and ventilator capacity reduction due to wind pressures
(air flow: for 50 Hz only)
External Change in fan capacity due to
Wind pressure
air velocity (Pa) Propeller fan Sirocco fan wind pressures
(Vm/sec)
0 0 924m3/h 432m3/h
3 3.9 810 420 Sirocco
fan
Wind
5 10.8 612 408 velocity
Propeller
7 20.6 294 Reverse flow 390 fan
10 43.1 Reverse flow 360
15 96.0 Reverse flow 264

20 171.5 Reverse flow 210 Air flow

VKM-GA(M) series 87
Appendix ED71-440B

18.2.4 Operating Sound


As well as the required airflow and static pressure, the operating sound (noise level) is an important factor
for determining the type of ventilating fans. The noise level allowable limit may have been defined
depending on the use of the room to be ventilated. Select an appropriate type of ventilating fans according
to the noise requirements.

„ Operating sound unit: dB


A-weighted sound pressure level measured using a sound level meter is the measure of sound produced
by an operating ventilator fan. There has been many units used: phon(A), phon, dB(A) and dB. This
catalogue uses the internationally unified unit “dB.” Note that the sound pressure level in “phon” can be
directly converted into “dB” without changing the numerical value. Use sound level meters in the A-
weighted mode.

„ Allowable noise level


Building codes specify the allowable noise level for each type of room. See Table 1 for selecting.
Table 1 Allowable noise level depending on the type of room
Use of room dB Use of room dB
Broadcasting studio 25 Cinema 40
Music hall 30 Hospital 35
Theater (about 500 seats) 35 Library 40
School room 40 Small office room 45
Meeting room 40 Restaurant 50
Apartment 40 Gymnasium 55
Hotel 40 Large office room 50
Residential housing (living room, etc.) 40 Factory 70

„ Notes for noise level


The noise ratings shown on the nameplate of a product are those measured in an anechoic room per the
relevant JIS standard that specifies measuring procedures including the distance between the noise source
under test and the sound level meter. To select types of ventilating fans, observe the following three notes.
1. The environment affects the noise level.
The nameplate values are those measured in an anechoic room. Actual buildings have echoes from the
walls, floors and ceilings, so that the noise level depends on the building materials used and how wide
the room is. Use appropriate echo coefficients to determine the actual noise level and available fan
types.
2. Vibration
Motor driven fans, a type of rotating machine, inevitably produce vibration, though our largest efforts to
reduce such vibration have been made. To minimize vibration (propagation and resonance), the
product should be firmly mounted on the wall.
3. Synthesis of sounds
When using two or more ventilating fans in a room, consider the synthesized effect of sounds.

„ Other noise
• Echoes
Depending on the type or material of the wall and ceilings of the room, and in small room, echoes occur.
• Vibration
Vibrating objects produce vibrating sound by moving their surrounding air. 20Hz or higher frequency
sounds are audible.
• Noise due to duct’s resistance
Higher static pressures acting on the fan will produce larger sounds.

88 VKM-GA(M) series
ED71-440B Appendix

18.2.5 Required Air Flow


When calculating the required air flow (ventilating capacity), various factors, including CO2 production by
the persons staying therein and production of combustion gases, should be considered. Calculations
should consider all of the requirements that the room should meet.
„ Calculate air flow based on the occupied area per person

20 × room floor area (m2)


Required air flow (m3/h) =
Occupied area per person (m2)
Notes: 1. The number 20 contained in the above equation means 20 m3/h · person. This value (required fresh air)
has been determined based on the CO2 production of a male adult when he is sitting quietly. If he is
smoking, additional air flow is required.
2. In the case that the actual occupied area per person exceeds 10 m2, use 10 as the value of the
denominator of the equation.
Occupied area per person for ventilation requirements for commercial facilities
Occupied area
Building type Remarks
per person (N)
2
Restaurant, coffee shop 3m Floor area for business use
Cabaret, beer hall 2m2 Floor area for business use
Japanese restaurant, assembly room on hire 3m2 Floor area for business use
Shop, supermarket 3m2 Floor area for business use
Billiard room, table tennis room, dance hall, bowling alley 2m2 Floor area for business use
Pachinko parlor, go club, mah-jongg saloon 2m2 Floor area for business use
Japanese style hotel, Hotel, motel 10m2 Floor area for business use
2
Special bath house 5m Floor area for business use
Meeting room, city hall 0.5~1m2 Per area number of person
Office 5m2 Floor area of the office room

Calculate air flow based on the required number of air changes


Required air flow (m3/h)
= Required number of air changes (times/h) × Room volume (m3)
• The required number of air changes shown below has been determined based on the prior knowledge
and experiments by sanitary testing laboratories etc.
(Example) Place: ordinary living room
Required number of air changes: 6 (times/h) (see the table below)
Area of the room: about 9.9 m2
Ceiling height: 2.4 m
Required air flow = 6 × 9.9 × 2.4 = 143 (m3/h)
Select ventilating fans that can satisfy the above mentioned airflow requirement.
Guideline for the number of air changes
Room Number of air changes (times/h)
Toilet, washroom 5~15
Locker room, changing room 5
Library, warehouse, store 5
Darkroom 10
Copy room, print room 10
Projection room 10
Pantry 8
Shower room 5
Bathroom 5
Changing room 5
Food locker 5
Garbage locker 15

„ Calculate air flow based on the room capacity (number of persons to be admitted)
Required air flow (m3/h) = Required air flow per person (m3/h) × Number of persons

Required air flow per person


Required air flow
Room
Recommendation Minimum
Bar, cabaret 51m3/person · h 42.5m3/person · h
Office, restaurant 25.5m3/person · h 17~20m3/person · h
3
Shop, department store 25.5m /person · h 17m3/person · h

VKM-GA(M) series 89
Appendix ED71-440B

„ Calculate air flow based on the required air flow per floor area
Required air flow (m3/h)
= Required air flow per floor area (m3/m2 · h) × Floor area (m2)

Required air flow per floor area (1m2)


Room Air flow rate
Office 10m3/h 10m3/h
3
Shop 15m /h 15m3/h
3
Beauty salon 12m /h 12m3/h
Amusement room 15m3/h 15m3/h
3
Smoking room 20m /h 20m3/h
3
Small meeting room 25m /h 25m3/h
3
Dining room (commercial) 25m /h 25m3/h

Exhaust Mechanical ventilation Exhaust Natural ventilation Exhaust Mechanical ventilation


Supply Mechanical ventilation Supply Mechanical ventilation Supply Natural ventilation

Positive Negative
pressure
pressure
Kinds of ventilation Exhaust opening
Room Ventilation fan Room Room Ventilation fan

Ventilation fan Ventilation fan Clean room, machine Intake


Building, parking area in a building, boiler room, cooling, etc. Kitchen, toilet, pantry, etc. in residential
electric room, machine room, galley, warehouse, etc. housing, and copy room, etc.

„ Required air flow based on CO2 production


CO2 is produced by human being’s breathing, which means that the required air flow depends on the
number of persons staying therein and/or labor loads. To calculate air flow based on CO2 production, use
the following equation.
100M
Q=
K-Ko
Q: Required air flow [m3/h · person]
M: CO2 production [m3/h · person] → see Table A
K: CO2 concentration limit in normal status [%] see Table B
Ko: CO2 concentration in the atmosphere [%] (normally 0.03%)
Table A CO2 Production Depending on Labor Burdens
Energy metabolic rate: CO2 production CO2 production for calculation
Labor burden
RMR (m3/h · person) (m3/h · person)
0 Sitting quietly 0.0132 0.013
0~1 Very light work 0.0132~0.0242 0.022
1~2 Light work 0.0242~0.0352 0.030
2~4 Medium work 0.0352~0.0572 0.046
4~7 Heavy work 0.0572~0.0902 0.074

Table B Required Air Flow Based on Labor Burdens


CO2 production Energy Required air flow (m3/h · person)
for calculation metabolic rate Labor burden
(m3/h · person) for calculation CO2 limit = 0.10% CO2 limit = 0.15% CO2 limit = 0.20%
0.013 0 Sitting quietly 18.6 10.8 7.6
0.022 0.8 Very light work 31.4 18.3 12.9
0.030 1.5 Light work 43.0 25.0 17.6
0.046 3.0 Medium work 65.7 38.3 27.1
0.076 0.8 Heavy work 106.0 61.7 43.7

<Example>

Assumptions: CO2 production 0.03 m3/h · person (light work)


CO2 concentration limit 0.15 vol%

100 × 0.030
Q= = 25m3/h · person
0.15 – 0.03

Therefore, air flow of 25 m3/h · person is required.

90 VKM-GA(M) series
ED71-440B Appendix

„ Required air flow based on tobacco smoking and odor


6-class odor level presentation (this classification is linked with an approximate, intuitive
estimation of gas concentration)
Odor intensity Description
0 Odorless
1 Manages to detect the presence of odor (threshold concentration)
2 Manages to detect what is producing the odor (threshold concentration)
3 Easily detects the odor
4 Strong odor
5 Very strong odor

For example, to keep the odor level not greater than 2, the contamination concentration (tobacco
combustion amount (mg)/ventilation amount (m3)) should be reduced to 35.3 mg/m3 or smaller. To keep
the odor level not greater than 1, the contamination concentration should be reduced to 17.7 mg/m3 or
smaller. To calculate required air flow based on smoking concentration, use the following equation.

Tobacco combustion (mg/h · person)


Q= (m3/h)
Allowable contamination (mg/m3)

<Example>
Assumptions: Combustion per cigarette 1,000 mg
Combustion rate 70%
Number of cigarettes per person 4/h · person
Odor intensity level 2 (=35.5 mg/m3)
1,000 × 0.7 × 4
Q= = 79.3m3/h · person
35.3
Therefore, under the conditions given above, in the case of cleaning air using ventilation only, about 80 m3/
h · person of air flow is required. By using air cleaners and/or deodorizers in conjunction with the ventilation
system, its capacity can be reduced significantly.
Required air flow depending on the degree of smoking (estimated)
Required air flow (m3/h · person), Smoking amount (number
Degree of smoking Locations
minimum to recommended value of cigarettes/hour/person)
Dealer office, newspaper 3~5.1
Very high editing room, meeting room 51~85 (1.5~2.5)

High Bar, office, hotel 42~51 2.5~3


(guest room) (1.3~1.5)
1.2~1.6
Medium (to high) Restaurant, office 20~26
(0.6~0.8)
Sales room in a bank, 0.8~1.0
Low (sometimes) office, shop 13~17 (0.4~0.5)

VKM-GA(M) series 91
Appendix ED71-440B

18.3 Calculation of Duct Pressure Loss


Some types of ventilating fans, including those (pressure types) installed in a cooking range hood, are
installed in a ducted system. The air flow depends on the pressure losses determined according to the
length of the ducted system and the number of bends, and other accessories contained in the system. Air
flow calculations should consider these pressure drops to estimate the air flow as accurately as possible.

18.3.1 Procedure for Calculating Pressure Drops and Finally Determining the Type of Ventilators
Calculation of required air flow

Ducting design (duct diameter, type, routing, length and bends)

Method using the duct's friction resistance diagram


Calculate the Using the equivalent

Simplified method using "the equivalent


straight piping length" conversion table
pressure losses of straight piping length
the straight sections conversion table,
using "the friction calculate "the equivalent
resistance diagram". straight pipe length" of
the entire duct system.
Calculate the
pressure losses of
the local features Plot "the loss-resistance
using "the relevant curve" on "the static
local feature loss pressure vs. air flow
coefficients". characteristics curve
chart" to find the
Calculate the overall intersection of these two
losses throughout the curves.
entire duct system.

Add 10 ~ 20% safety margins to the calculated pressure


losses to determine the required static pressure.

Referring to "the static pressure vs. air flow characteristics


curves" of various types of ventilating fans, select a type
that can satisfy the abovementioned pressure requirement.

18.3.2 Pressure Loss Calculation for Straight Duct


„ For round ducts
1. The resistance of a duct can be calculated using the following equation.
Pressure drop ΔP due to the frictional resistance of a straight duct can be calculated using the following
equation.
γ L
Resistance of duct Δ P (Pa) = λ × × × V2
2 d

λ: Duct friction coefficient (0.01~0.25)


γ: Air specific gravity (kg/m3) = 1.20 kg/m3
L: Duct length (m)
d: Duct diameter (m)
V: Duct air velocity (m/sec)
Q 4
V= ×
d2 3,600π
Q: Air flow (m3/h)

Where, λ = 0.01 (very smooth pipe), and γ = 1.2


2

P = 0.01 ×
1.2
2
×
L
d
Q
× 2 ×
d
4
3,600π
{ }
Friction coefficient of major duct types
Duct material λ
Aluminum flexible duct 0.03~0.04
Vinyl chloride pipe 0.01~0.02
Galvanized steel pipe 0.016~0.025

92 VKM-GA(M) series
ED71-440B Appendix

2. Using the duct's friction resistance diagram


Friction resistance diagram for round duct (galvanized steel pipe)
0.04 0.1 0.2 0.4 1.0 2.0 6.0 10 20 40 60 80
1000000
800000 0 cm
50
600000 d=
400000 0
40
0
35
0
200000 30
0
25
0
100000 20
80000 0
18
0
60000 16
0
14
40000 0

v=
12

50
0
Air flow Q [m3/h]

.0m
10 0

40
20000 9

/s
.0
80

30
70

.0
20
10000 60 m
0c

.0
8000

15
r5
ete

.0
6000

Ve
i am 45
D

loc
4000 40

ity
=(m
35 25

/s)
30
2000

9.0
8.0
7.0
6.0
20

5.0
1000
800 4.0 18
600 16
3.0

14
400
2.0 8

12
1.
1.6
1.4

10
1.2

200 9
1.0

6
8
5
7 d=
100
0.9

6
0.8

80
0.7

5
0.6

60
4.5
40 4
3
0.5

3.5
20
2.5
2
10
0.04 0.1 0.2 0.4 1.0 2.0 6.0 10 20 40 60 80

Friction loss factor γ [Pa/m]


Friction Resistance Diagram for Duct

<How to use the diagram>


(Conditions)
• A ventilating fan intended for use with a ducted system should be chosen.
• Required air flow: 300 m3/h
• Duct diameter: φ15 cm
• Duct length: 5 m
Air flow Q [m3/h]

]
m
[c
Ve

15
loc

d=
ity
ν
[m
/s
]

A
300

B
0 2.2 Friction loss factor γ [Pa/m]
1. Find the intersection
of the duct diameter d (15 cm) and air flow Q (300
m3/h) => Point A
2. Draw a vertical line through Point A until it intersects
with the abscissa => Point B
3. Read the Point B (2.2 Pa/m for this case). Multiply
the value by the duct length. The answer is 11 Pa.

VKM-GA(M) series 93
Appendix ED71-440B

„ Conversion from rectangular to round duct

Long side

E
di qui
am va
et len
er t

Short side

<How to use the chart>


(Example) A rectangular duct of 40×200 is equivalent to a round duct of 90 in diameter.
I) Find the intersection of the short side 40 and long side 200: Point A.
A II) Draw the line B passing through Point A until it intersects with the slant
200
line C: Point D.
B D This is the equivalent diameter. In this case, the diameter is 90.
Long side

90
De

40
Short side

18.3.3 Pressure Loss Due to Local Features


1. Local feature loss coefficient (local feature resistance coefficient)
Bends, and sections where the sectional area is suddenly changed, have, unlike straight sections,
particular types of pressure losses due to eddy current and other factors. The pressure loss of these
non-straight parts is given by the following equation.

V2
ΔP (Pa) = ζ · γ = ζ · Pv
2
Where ζ: Local loss coefficient
v: Air velocity...................................[m/s]
* This is the velocity measured at the upstream side of the feature except junctions.
Pv: Dynamic pressure.....................[Pa]

2. Calculation of pressure loss due to local features


(Example) Bend as shown in the figure.

R bend, round duct

R
[Conditions] = 1.5 v = 5.0 [m/s]
d

ζ = 0.24
V2 25
Pv = γ = × 1.2
2 2
Pv = 15 [Pa]

ΔP = ζ (Local loss coefficient) × Pv (Dynamic pressure)


= 0.24 × 15 = 3.6 [Pa]

94 VKM-GA(M) series
ED71-440B Appendix

The right column of Table A shows


le: equivalent straight pipe length of partial resistance...[m]
the duct diameter equivalent to this ζ
pressure loss of the local feature. le = d d: straight pipe diameter................................................[m]
λ ζ: Local loss coefficient
Note that the values shown in the
table are for λ = 0.018. For other
values of the friction resistance coefficient (λ) to be used, use the following equation to find appropriate
conversion.
Table A
Status Loss
No. Name Sketch
H/W R/dR/W coefficient ζ
0.5 0.90
0.75 0.45
d
1 R bend, round duct R – 1.0 0.33
1.5 0.24
2.0 0.19

d
2 Straight bend, round duct – – 1.30

0.5 1.25
0.75 0.60
0.25 1.0 0.37
1.5 0.19
0.5 1.10
0.75 0.50
0.5 1.0 0.28
W 1.5 0.13
3 R bend, rectangular duct
R
0.5 1.00
H
0.75 0.41
1.0
1.0 0.22
1.5 0.09
0.5 0.96
0.75 0.37
4.0
1.0 0.19
1.5 0.07
0.25 1.25
W 0.5 1.47
4 Straight bend, rectangular duct –
H 1.0 1.50
4.0 1.38
20° 0.02
40° 0.03
5 Pipe inlet (with round hood) θ V θ 60° 0.05
90° 0.11
120° 0.20
20° 0.13
40° 0.08
6 Pipe inlet θ V θ 60° 0.12
(with rectangular hood)
90° 0.19
120° 0.27

(Example)

V VI
IV

III
Ventilating fan intended for 5m External hood
use with a ducted system 0.5m 0.5m (equivalent straight pipe length 9m)
Duct diameter φ100
Material: galvanized
steel pipe
I II
(For galvanized steel pipe with λ = 0.02, approximate value)

VKM-GA(M) series 95
Appendix ED71-440B

• To convert a local resistance to the Piping part


Equivalent straight pipe length
equivalent straight pipe length, use the Table (pipe diameter 100)
A shown in the previous page. I 0.5m
• For this example, the equivalent length can II 2m
be calculated as follows. III 0.5m
IV 2m
V 5m
VI 9m
Total 19m
<Calculate from the equivalent straight pipe length (le) and air flow (Q)>
(Example)
Equivalent straight pipe length: 19 m, Air flow: 120 [m3/h]
To find a ventilating fan that can satisfy these requirements, find the intersection of the pipe resistance
curve for le: 19 [m] and the static pressure / air flow characteristics curve, and then draw a vertical line
through the intersection A until it each the abscissa. The intersection B of the vertical line and abscissa
shows the required air flow capacity of the fan. In this case, the fan rating capacity should be greater than
120 m3/h.
Static pressure - air flow characteristics curve

50Hz
60Hz

19m
Pipe resistance curve
25 20
100
15m
(Pa)

10m
50
A
5m

0
50 100 B 150 200
Air flow (m3/h)

18.4 Notes for Ducted Systems


• To connect the ventilation duct to a common (multipurpose)
duct, use a 2 m-long steel leading duct or smoke reverse flow Smoke reverse flow
prevention damper
prevention damper per the regulations for the Building Exhaust duct
Standard Act. In the latter case, an inspection port should be
installed on the ceiling so that the damper can be accessed Ventilating
fan
through the port. Common
duct

Inspection port
(450 x 450 or larger)

• If an intermediate fan is installed midway in the


duct, an inspection port should be installed on the
ceiling so that the fan can be accessed through
the port.

Auxiliary grille
Inspection port

• The ducting examples shown in figures


should be avoided. These invite larger Deep bend Unnecessarily many bends
noise and smaller air flow, and adversely
affect the motor.

Reduced size Inclined connection


Ventilating fan
Duct

96 VKM-GA(M) series
ED71-440B Appendix

Bend located too close to the fan


Duct
Bending the duct near the shutter frame
may not permit the shutter to open
completely. To avoid this, there should be
Fan a distance of minimum 150 mm between
the bend and shutter.

To install a bellows, it should not be expanded near the connection

Fan Bellows

Each local rule or regulation may have different requirements for


bellows. For details, consult the authorities.
Connection to an aluminum flexible duct.

Bend located too close to the fan

Fan
Avoid deformation

Deformed flexible duct may not permit the shutter to open completely.

• Depending on the room structure, the noise may increase by 8 to 10 phons due to echoes and/or other
factors.
• To avoid entry of rainwater, exhaust ducts extending outside should be inclined down by 1/100 or larger.
• To use a two-room ventilating fan for a bathroom and other room, install the fan in the bathroom. Two-
room ventilating fans are designed so that the air flow through the main opening on the fan is about twice
larger than that through the sub opening (for cases where the distance between the main and sub
openings is about 1 m). However, this air flow proportion can be adjusted by moving the air flow
adjusting plate located on the grille of the main unit.

Sub opening Sub opening Main unit


<Toilet> (bathroom) (toilet) (bathroom)

• Components that constitute the ceiling should be strong enough to prevent vibration and sympathetic
sounds.
Recommended material: gypsum board, cement excelsior board, fiber board
• Exhaust duct ends should be fitted with a vent cap or weather cover to prevent rainwater entry and bird
nesting.
• In cold weather areas, the ducts should be thermal-insulated.

In cold weather areas, or in winter, condensation may occur due to the


difference in temperature between the duct surroundings and living room. To
avoid condensation, the ducting and their connections should be thermal-
insulated. Insulation

• Local rules and regulations may have special requirements for fire dampers and bellows. For details,
consult the authorities.
• For bathrooms, use ventilating fans specially designed for bathroom use. Never fail to earth the fan.
• Electric wiring should be done by a qualified electrician (electric engineering firm). High-voltage
connections are dangerous.

VKM-GA(M) series 97
Appendix ED71-440B

18.5 Unit Conversion Tables

„ General conversion tables


Pressure

Velocity

Area

Weight

98 VKM-GA(M) series
ED71-440B Appendix

Length

Flow rate

Note: 0.041=0.00001

VKM-GA(M) series 99
Appendix ED71-440B

„ SI unit used for refrigeration / air conditioning and conversion table


Units mainly Units mainly used in
JIS unit used in integral integral multiple of 10 of
Amount SI unit multiple of 10 of
unit used in combination Remarks
Other units SI unit
with SI unit or of unit
allowed use in combination

m in ft km
dm
Length m 1 39.37 3.281 cm
0.0254 1 0.0833 mm
0.3048 12.00 1 m
m2 in2 ft2 km2
dm2
Area m2 1 1550.0 10.76 cm
2

2
0.000652 1 0.006944 mm
0.09290 144.0 1
m
3
in3 ft3 dm3
cm3 =m3
3 1 61020 35.31 3 =10–3m3
Volume m mm
1.639×10–5 1 5.787×10–4 =10–4m3
–5 3
0.02832 1728 1 =10 m

kg lb Mg
g
Mass kg 1 2.205 mg
0.4536 1

kg/m3 g/cm3 lb/ft3


Density kg/m 3
1000 1 62.43
1 0.001 0.06243
16.02 0.01602 1
m/s ft/s
km/h
Speed m/s 1 3.281 1
1km/h= m/s
0.3048 1 3.6

K ºF
K (ºC)
Temperature (Kelvin) 1 0.5555
(Celsius) 1.8 1

N kgf lb MN
Force N kN
1 0.102 0.245 mN IN=1kg×1m/s2
(weight) (Newton) 9.807 1 2.205 N
4.448 0.4536 1
Pa kgf/cm2 lb/in2 (psi) GPa MPa
kPa hPa 2
Pa 1 1.02×10 –5
1.45×10–4 mPA Pa Pa=N/m
Pressure hPa=mmbar
(Pascal) 9.807×104 1 14.22
3
6.895×10 0.07031 1
J kcal BTU
J TJ
Work 1 2.39×10–4 9.478×10–4 GJ
(Joule) 4186.05 1 3.968 MJ
1055.1 0.252 1 kJ

100 VKM-GA(M) series


ED71-440B Appendix

„ Pressure conversion table


kgf/cm2G MPaG p.s.i.G kgf/cm2G MPaG p.s.i.G p.s.i.G MPaG kgf/cm2G p.s.i.G MpaG kgf/cm2G
0.0 0.00 0.0 12.0 1.18 170.6 0 0.00 0.0 350 2.41 24.6
0.2 0.02 2.8 12.2 1.20 173.5 5 0.03 0.4 355 2.45 25.0
0.4 0.04 5.7 12.4 1.22 176.3 10 0.07 0.7 360 2.48 25.3
0.6 0.06 8.5 12.6 1.23 179.2 15 0.10 1.1 365 2.52 25.7
0.8 0.08 11.4 12.8 1.25 182.0 20 0.14 1.4 370 2.55 26.0
1.0 0.10 14.2 13.0 1.27 184.9 25 0.17 1.8 375 2.58 26.4
1.2 0.12 17.1 13.2 1.29 187.7 30 0.21 2.1 380 2.62 26.7
1.4 0.14 19.9 13.4 1.31 190.5 35 0.24 2.5 385 2.65 27.1
1.6 0.16 22.8 13.6 1.33 193.4 40 0.27 2.8 390 2.68 27.4
1.8 0.18 25.6 13.8 1.35 196.2 45 0.31 3.2 395 2.72 27.8
2.0 0.20 28.4 14.0 1.37 199.1 50 0.34 3.5 400 2.76 28.1
2.2 0.22 31.3 14.2 1.39 201.9 55 0.38 3.9 405 2.79 28.5
2.4 0.23 34.1 14.4 1.41 204.8 60 0.41 4.2 410 2.83 28.8
2.6 0.25 37.0 14.6 1.43 207.6 65 0.45 4.6 415 2.86 29.2
2.8 0.27 39.8 14.8 1.45 210.5 70 0.48 4.9 420 2.90 29.5
3.0 0.29 42.7 15.0 1.47 213.3 75 0.51 5.3 425 2.93 30.0
3.2 0.31 45.5 15.2 1.49 216.1 80 0.55 5.6 430 2.97 30.2
3.4 0.33 48.3 15.4 1.50 219.0 85 0.59 6.0 435 3.00 30.6
3.6 0.35 51.2 15.6 1.53 221.8 90 0.62 6.3 440 3.03 30.9
3.8 0.37 54.0 15.8 1.55 224.7 95 0.66 6.7 445 3.07 31.3
4.0 0.39 56.9 16.0 1.57 227.5 100 0.69 7.0 450 3.10 31.6
4.2 0.41 59.7 16.2 1.58 230.4 105 0.72 7.4 455 3.14 32.0
4.4 0.43 62.6 16.4 1.61 233.2 110 0.76 7.7 460 3.17 32.3
4.6 0.45 65.4 16.6 1.63 236.1 115 0.79 8.1 465 3.20 32.7
4.8 0.47 68.3 16.8 1.65 238.9 120 0.83 8.4 470 3.24 33.0
5.0 0.49 71.1 17.0 1.67 241.7 125 0.86 8.8 475 3.28 33.4
5.2 0.51 73.9 17.2 1.69 244.6 130 0.89 9.1 480 3.31 33.7
5.4 0.53 76.8 17.4 1.71 247.4 135 0.93 9.5 485 3.34 34.1
5.6 0.55 79.6 17.6 1.72 250.3 140 0.97 9.8 490 3.38 34.5
5.8 0.57 82.5 17.8 1.74 253.1 145 1.00 10.2 495 3.41 34.8
6.0 0.59 85.3 18.0 1.76 256.0 150 1.03 10.5 500 3.45 35.2
6.2 0.61 88.2 18.2 1.78 258.8 155 1.07 10.9 505 3.48 35.5
6.4 0.63 91.0 18.4 1.80 261.6 160 1.10 11.2 510 3.52 35.9
6.6 0.65 93.9 18.6 1.82 264.5 165 1.13 11.6 515 3.55 36.2
6.8 0.67 96.7 18.8 1.84 267.3 170 1.17 12.0 520 3.59 36.6
7.0 0.69 99.5 19.0 1.86 270.2 175 1.21 12.3 525 3.62 36.9
7.2 0.71 102.4 19.2 1.88 273.0 180 1.25 12.7 530 3.65 37.3
7.4 0.73 105.2 19.4 1.90 275.9 185 1.28 13.0 535 3.69 37.6
7.6 0.74 108.1 19.6 1.92 278.7 190 1.31 13.4 540 3.72 38.0
7.8 0.76 110.9 19.8 1.94 281.6 195 1.34 13.7 545 3.76 38.3
8.0 0.78 113.8 20.0 1.96 284.4 200 1.38 14.1 550 3.79 38.7
8.2 0.80 116.6 20.2 1.98 287.2 205 1.41 14.4 555 3.83 39.0
8.4 0.82 119.4 20.4 2.00 290.1 210 1.45 14.8 560 3.86 39.4
8.6 0.84 122.3 20.6 2.02 292.9 215 1.48 15.1 565 3.90 39.7
8.8 0.86 125.1 20.8 2.04 295.8 220 1.52 15.5 570 3.93 40.0
9.0 0.88 128.0 21.0 2.06 298.6 225 1.55 15.8 575 3.97 40.4
9.2 0.90 130.8 21.2 2.08 301.5 230 1.59 16.2 580 4.00 40.8
9.4 0.92 133.7 21.4 2.10 304.3 235 1.62 16.5 585 4.03 41.1
9.6 0.94 136.5 21.6 2.12 307.2 240 1.66 16.9 590 4.07 41.5
9.8 0.96 139.4 21.8 2.14 310.0 245 1.69 17.2 595 4.10 41.8
10.0 0.98 142.2 22.0 2.16 312.8 250 1.72 17.6 600 4.14 42.2
10.2 1.00 145.0 22.2 2.18 315.7 255 1.76 17.9 605 4.17 42.5
10.4 1.02 147.9 22.4 2.19 318.5 260 1.79 18.3 610 4.21 42.9
10.6 1.04 150.7 22.6 2.21 321.4 265 1.83 18.6 615 4.24 43.2
10.8 1.06 153.6 22.8 2.23 324.2 270 1.86 19.0 620 4.28 43.6
11.0 1.08 156.4 23.0 2.25 327.1 275 1.90 19.3 625 4.31 43.9
11.2 1.09 159.3 23.2 2.27 329.9 280 1.93 19.7 630 4.34 44.3
11.4 1.12 162.1 23.4 2.29 332.7 285 1.96 20.0 635 4.38 44.6
11.6 1.14 165.0 23.6 2.31 335.6 290 2.00 20.4 640 4.41 45.0
11.8 1.16 167.8 23.8 2.33 338.4 295 2.03 20.7 645 4.45 45.3
300 2.07 21.1 650 4.48 45.7
p.s.i.=14.22×kgf/cm2 305 2.10 21.4 655 4.52 46.0
kgf/cm2=10.2×Mpa
310 2.13 21.8 660 4.55 46.4
kgf/cm2=0.0703×p.s.i. 315 2.17 22.1 665 4.58 46.7
MPa=0.098×kgf/cm2 320 2.20 22.5 670 4.62 47.1
325 2.24 22.8 675 4.65 47.5
p.s.i=145.0×MPa
330 2.27 23.2 680 4.68 47.8
MPa=0.006896×p.s.i 335 2.31 23.6 685 4.72 48.2
Note: This conversion system is based on GAUGE pressure. 340 2.34 23.9 690 4.75 48.5
345 2.37 24.3 695 4.79 48.9

VKM-GA(M) series 101


Appendix ED71-440B

„ Temperature conversion table

102 VKM-GA(M) series


ED71-440B Appendix

18.6 Refrigerant
„ Fluorocarbon and global environment
Influence of refrigerant given on global environment

1. Ozone layer destruction

Space beyond the


earth's atmosphere
Ozone layer
destruction due to
chlorine contained in Upper atmosphere
fluorocarbon

Stratosphere (ozone layer)

Intrusion of harmful
ultraviolet rays
Fluorocarbon Troposphere

Earth's surface

Refrigerants discharged reach the stratosphere


without being decomposed.

Refrigerants are decomposed by strong


ultraviolet rays radiated from the sun.

Chlorine is discharged.

Ozone (O3) reaction caused by chlorine


discharged.

Resulting in ozone layer destruction.

The strong ultraviolet rays radiated from the sun


directly reach Earth's surface.

Resulting in the increase of harmful ultraviolet rays.

Cause of skin cancer and others

VKM-GA(M) series 103


Appendix ED71-440B

2. Global warming

(Principle)
Due to the results of human activities such as a large
quantity of consumption of petrochemical fuels (e.g.
petroleum, coal, and natural gas) and forest
destruction, carbon dioxide, chlorofluorocarbon,
methane, and others in the atmosphere have been
increasing beyond the limit that natural force can
remove them.
As a result, the dissipation of heat from Earth's surface
is interrupted (greenhouse effect), thus resulting in
global warming.

*Gases in the atmosphere


absorb the infrared rays.
Solar light beam

Infrared rays
Earth

Atmosphere

Carbon dioxide, fluorocarbon, methane, nitride,


and others are released from Earth's surface.

Infrared rays (heat rays) from Earth's surface are


absorbed.

Heat (temperature) cannot be dissipated from


Earth's surface.

Resulting in temperature rise and sea level rise.

104 VKM-GA(M) series


ED71-440B Appendix

„ Refrigerant R-410A saturation curve

Gauge pressure (MPa G)


Absolute pressure (MPa)

Temperature (˚C)

VKM-GA(M) series 105


Appendix ED71-440B

„ R-410A Saturation pressure (gauge pressure) chart

Press. Temp Press. Temp Press. Temp


MpaG ºC MpaG ºC MpaG ºC
0 -51.58 0.9 7 3.49 57
0.06 -42 0.93 8 3.57 58
0.07 -41 0.97 9 3.65 59
0.08 -40 1 10 3.73 60
0.085 -39 1.03 11 3.82 61
0.09 -38 1.06 12 3.9 62
0.1 -37 1.09 13 3.99 63
0.11 -36 1.12 14 4.08 64
0.12 -35 1.16 15
0.13 -34 1.2 16
0.14 -33 1.24 17
0.15 -32 1.27 18
0.16 -31 1.31 19
0.17 -30 1.35 20
0.18 -29 1.39 21
0.19 -28 1.43 22
0.21 -27 1.48 23
0.22 -26 1.52 24
0.23 -25 1.56 25
0.24 -24 1.6 26
0.26 -23 1.65 27
0.27 -22 1.7 28
0.29 -21 1.75 29
0.3 -20 1.79 30
0.32 -19 1.84 31
0.33 -18 1.89 32
0.35 -17 1.92 33
0.36 -16 1.94 34
0.38 -15 2.02 35
0.4 -14 2.1 36
0.42 -13 2.16 37
0.43 -12 2.21 38
0.45 -11 2.27 39
0.47 -10 2.33 40
0.49 -9 2.39 41
0.51 -8 2.45 42
0.54 -7 2.51 43
0.56 -6 2.57 44
0.58 -5 2.64 45
0.6 -4 2.7 46
0.63 -3 2.77 47
0.65 -2 2.83 48
0.68 -1 2.9 49
0.7 0 2.97 50
0.73 1 3.04 51
0.75 2 3.11 52
0.78 3 3.19 53
0.81 4 3.26 54
0.84 5 3.34 55
0.87 6 3.41 56

106 VKM-GA(M) series


ED71-440B Appendix

„ Thermodynamic characteristics of R-410A


DAIREP ver2.0
Temperature Steam pressure Density Specific heat at constant Specific enthalpy Specific entropy
(°C) (kPa) (kg/m3) pressure (kj/kgK) (kj/kg) (kj/kgK)
Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor
–70 36.13 36.11 1410.7 1.582 1.372 0.695 100.8 390.6 0.649 2.074
–68 40.83 40.80 1404.7 1.774 1.374 0.700 103.6 391.8 0.663 2.066
–66 46.02 45.98 1398.6 1.984 1.375 0.705 106.3 393.0 0.676 2.058
–64 51.73 51.68 1392.5 2.213 1.377 0.710 109.1 394.1 0.689 2.051
–62 58.00 57.94 1386.4 2.463 1.378 0.715 111.9 395.3 0.702 2.044
–60 64.87 64.80 1380.2 2.734 1.379 0.720 114.6 396.4 0.715 2.037
–58 72.38 72.29 1374.0 3.030 1.380 0.726 117.4 397.6 0.728 2.030
–56 80.57 80.46 1367.8 3.350 1.382 0.732 120.1 398.7 0.741 2.023
–54 89.49 89.36 1361.6 3.696 1.384 0.737 122.9 399.8 0.754 2.017
–52 99.18 99.03 1355.3 4.071 1.386 0.744 125.7 400.9 0.766 2.010

–51.58 101.32 101.17 1354.0 4.153 1.386 0.745 126.3 401.1 0.769 2.009

–50 109.69 109.51 1349.0 4.474 1.388 0.750 128.5 402.0 0.779 2.004
–48 121.07 120.85 1342.7 4.909 1.391 0.756 131.2 403.1 0.791 1.998
–46 133.36 133.11 1336.3 5.377 1.394 0.763 134.0 404.1 0.803 1.992
–44 146.61 146.32 1330.0 5.880 1.397 0.770 136.8 405.2 0.816 1.987
–42 160.89 160.55 1323.5 6.419 1.401 0.777 139.6 406.2 0.828 1.981
–40 176.24 175.85 1317.0 6.996 1.405 0.785 142.4 407.3 0.840 1.976
–38 192.71 192.27 1310.5 7.614 1.409 0.792 145.3 408.3 0.852 1.970
–36 210.37 209.86 1304.0 8.275 1.414 0.800 148.1 409.3 0.864 1.965
–34 229.26 228.69 1297.3 8.980 1.419 0.809 150.9 410.2 0.875 1.960
–32 249.46 248.81 1290.6 9.732 1.424 0.817 153.8 411.2 0.887 1.955

–30 271.01 270.28 1283.9 10.53 1.430 0.826 156.6 412.1 0.899 1.950
–28 293.99 293.16 1277.1 11.39 1.436 0.835 159.5 413.1 0.911 1.946
–26 318.44 317.52 1270.2 12.29 1.442 0.844 162.4 414.0 0.922 1.941
–24 344.44 343.41 1263.3 13.26 1.448 0.854 165.3 414.9 0.934 1.936
–22 372.05 370.90 1256.3 14.28 1.455 0.864 168.2 415.7 0.945 1.932
–20 401.34 400.06 1249.2 15.37 1.461 0.875 171.1 416.6 0.957 1.927
–18 432.36 430.95 1242.0 16.52 1.468 0.886 174.1 417.4 0.968 1.923
–16 465.20 463.64 1234.8 17.74 1.476 0.897 177.0 418.2 0.980 1.919
–14 499.91 498.20 1227.5 19.04 1.483 0.909 180.0 419.0 0.991 1.914
–12 536.58 534.69 1220.0 20.41 1.491 0.921 182.9 419.8 1.003 1.910

–10 575.26 573.20 1212.5 21.86 1.499 0.933 185.9 420.5 1.014 1.906
–8 616.03 613.78 1204.9 23.39 1.507 0.947 189.0 421.2 1.025 1.902
–6 658.97 656.52 1197.2 25.01 1.516 0.960 192.0 421.9 1.036 1.898
–4 704.15 701.49 1189.4 26.72 1.524 0.975 195.0 422.6 1.048 1.894
–2 751.64 748.76 1181.4 28.53 1.533 0.990 198.1 423.2 1.059 1.890
0 801.52 798.41 1173.4 30.44 1.543 1.005 201.2 423.8 1.070 1.886
2 853.87 850.52 1165.3 32.46 1.552 1.022 204.3 424.4 1.081 1.882
4 908.77 905.16 1157.0 34.59 1.563 1.039 207.4 424.9 1.092 1.878
6 966.29 962.42 1148.6 36.83 1.573 1.057 210.5 425.5 1.103 1.874
8 1026.5 1022.4 1140.0 39.21 1.584 1.076 213.7 425.9 1.114 1.870

10 1089.5 1085.1 1131.3 41.71 1.596 1.096 216.8 426.4 1.125 1.866
12 1155.4 1150.7 1122.5 44.35 1.608 1.117 220.0 426.8 1.136 1.862
14 1224.3 1219.2 1113.5 47.14 1.621 1.139 223.2 427.2 1.147 1.859
16 1296.2 1290.8 1104.4 50.09 1.635 1.163 226.5 427.5 1.158 1.855
18 1371.2 1365.5 1095.1 53.20 1.650 1.188 229.7 427.8 1.169 1.851
20 1449.4 1443.4 1085.6 56.48 1.666 1.215 233.0 428.1 1.180 1.847
22 1530.9 1524.6 1075.9 59.96 1.683 1.243 236.4 428.3 1.191 1.843
24 1615.8 1609.2 1066.0 63.63 1.701 1.273 239.7 428.4 1.202 1.839
26 1704.2 1697.2 1055.9 67.51 1.721 1.306 243.1 428.6 1.214 1.834
28 1796.2 1788.9 1045.5 71.62 1.743 1.341 246.5 428.6 1.225 1.830

30 1891.9 1884.2 1034.9 75.97 1.767 1.379 249.9 428.6 1.236 1.826
32 1991.3 1983.2 1024.1 80.58 1.793 1.420 253.4 428.6 1.247 1.822
34 2094.5 2086.2 1012.9 85.48 1.822 1.465 256.9 428.4 1.258 1.817
36 2201.7 2193.1 1001.4 90.68 1.855 1.514 260.5 428.3 1.269 1.813
38 2313.0 2304.0 989.5 96.22 1.891 1.569 264.1 428.0 1.281 1.808
40 2428.4 2419.2 977.3 102.1 1.932 1.629 267.8 427.7 1.292 1.803
42 2548.1 2538.6 964.6 108.4 1.979 1.696 271.5 427.2 1.303 1.798
44 2672.2 2662.4 951.4 115.2 2.033 1.771 275.3 426.7 1.315 1.793
46 2800.7 2790.7 937.7 122.4 2.095 1.857 279.2 426.1 1.327 1.788
48 2933.7 2923.6 923.3 130.2 2.168 1.955 283.2 425.4 1.339 1.782

50 3071.5 3061.2 908.2 138.6 2.256 2.069 287.3 424.5 1.351 1.776
52 3214.0 3203.6 892.2 147.7 2.362 2.203 291.5 423.5 1.363 1.770
54 3361.4 3351.0 875.1 157.6 2.493 2.363 295.8 422.4 1.376 1.764
56 3513.8 3503.5 856.8 168.4 2.661 2.557 300.3 421.0 1.389 1.757
58 3671.3 3661.2 836.9 180.4 2.883 2.799 305.0 419.4 1.403 1.749
60 3834.1 3824.2 814.9 193.7 3.191 3.106 310.0 417.6 1.417 1.741
62 4002.1 3992.7 790.1 208.6 3.650 3.511 315.3 415.5 1.433 1.732
64 4175.7 4166.8 761.0 225.6 4.415 4.064 321.2 413.0 1.450 1.722

VKM-GA(M) series 107


108
R-410A
Appendix

(Z0169)
Pressure-enthalpy curves of HFC32/125 ( 50 / 50 wt% )

VKM-GA(M) series
ED71-440B
18.7
ED71-440B

VKM-GA(M) series
Moist Air h-x Chart [SI]
Pressure: 101.325kPa,
En
Temperature: -10 to +50˚C
t
u = halpy
dh/ -hum
dx
Psychrometric Chart

[kJ idity r
/kg atio ]
] )
( DA
g
/k
kJ
h[
lpy
ha
nt
]

e
c
ϕ[%

ifi
ty

ec
m idi

Sp
hu
t ive
Rela
Sensible heat factor

Absolute humidity x [kg/kg(DA)]

Wet
-bul
b tem
pera
ture
t' [˚C
]

Water
Ice

Dry-bulb temperature t [˚C ]

Specific volume v[m3/kg(DA)]


Appendix

109
Daikin products are manufactured for export to numerous countries throughout the world. Prior to
purchase, please confirm with your local authorised importer, distributor and/or retailer whether this
product conforms to the applicable standards, and is suitable for use, in the region where the product
will be used. This statement does not purport to exclude, restrict or modify the application of any local
legislation.
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.

Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global_ac/
c All rights reserved

Specifications, designs and other content appearing in this brochure are current as of March 2012 but subject to change without notice.
ED71-440B
03/12 FS.K

You might also like