Ed71-440b (Vkm50-100ga (M) V1) PDF
Ed71-440b (Vkm50-100ga (M) V1) PDF
Ed71-440b (Vkm50-100ga (M) V1) PDF
VKM-GA(M) series
ED71-440B
Table of Contents i
ED71-440B
ii Table of Contents
ED71-440B Selection Flowchart
1. Selection Flowchart
&
(
&
' '
,
+ -.
VKM-GA(M) series 1
External Appearance ED71-440B
2. External Appearance
VKM50GAMV1
VKM50GAV1
VKM80GAMV1
VKM100GAMV1
VKM80GAV1
VKM100GAV1
3. Model Series
Type 500 800 1000
DX-Coil and Humidifier VKM50GAMV1 VKM80GAMV1 VKM100GAMV1
DX-Coil VKM50GAV1 VKM80GAV1 VKM100GAV1
These units are applied only for CE regulation.
2 VKM-GA(M) series
ED71-440B Nomenclature
4. Nomenclature
V K M 50 GA M V1
Ventilation
Mounted Type
Power Supply
V1: 1 phase, 220-240V, 50Hz
5. Structures
Heat Exchanger
Exhaust Fan Elements Damper
EA Motor
(Exhaust air to outdoors) Damper
DX-coil
OA
(Direct expansion coil)
(Fresh air from
outdoors) RA
(Return air
from room)
Humidifier element
Float switch
Utilizing the principle of capillary action,
Solenoid
water is permeated throughout the
valve
humidifier element. The heated air from the
DX-coil goes through the humidifier and
absorbs the moisture. water
AIRFLOW SA
VKM-GA(M) series 3
Features ED71-440B
6. Features
6.1 General
• Interlocked operation with VRV
(Controls of interlocked operation for energy saving: The remote controller for air conditioner can be
used, so special remote controller for Heat Reclaim Ventilator is unnecessary.)
• Mounted for direct expansion coil unit for outdoor air treatment
• Changeover function for ventilation mode to Auto/Manual
• Fresh-up operation (Selectable: Supply air rich mode or exhaust air rich mode; initial setting)
• Mounted for water flow type natural evaporating humidifier
• Possible to attach the high efficiency filter
• Attaching the power supply terminal for easy connection
• Quiet operation
• Changeover function for air flow rate to High/Low (Ultra-high setting is possible.)
• The power supply of Heat Reclaim Ventilator is commonly used with the air-conditioner (1 phase, 220-
240V, 50Hz)
• Filter sign display and reset
• Timer setting
Features of direct expansion coil
• Draftless ventilation in heating
• High humidifying function
How to use this unit
• This unit should be used with air conditioners.
Air conditioning is impossible only by this unit, because this unit does not have temperature control
function. (Its capacity is too small in order to control the room temperature to the whole.)
And should be operated in combination with standard indoor units. (Interlocked operation)
• Independent operation without taking an interlock with indoor units is possible, however, temperature
setting by remote controller is impossible.
In this ON/OFF operation by thermostat depends on factory setting, however, this value is changeable by
setting mode on site.
• Model selection should be done not by cooling capacity but by ventilating air flow rate.
4 VKM-GA(M) series
ED71-440B Features
Heat Release
Heat
Reserve
Generation of heat with a PC etc. and The load of air conditioner is large and
its heat are reserved to a wall, ceiling. temperature does not fall easily.
Automatic heat
Cold Air
purge control
The heat which accumulated
indoors is discharged at night. Heat Release
Air conditioning load of the next
day is reduced, and efficiency is
increased. Heat
Reserve
Mechanism
<Operation>
1. Interlocking operation is carried
out with the air-conditioning Temp.
machine, and the time of 2 hours 40
passing after an operation stop is Outdoor Temp.
judged to be night.
(The same judgment as the 30
Setting Temp.
present preparatory operation)
2. After 2-hour progress, when Indoor Temp.
20
indoor temperature is higher than
Auto Start
the preset temperature of an air- Heat ON 2 hours
conditioning machine and higher Reclaim OFF
Ventilator
than outdoor temperature, ON
operation is started. Air Start
OFF
Conditioner
3. Operation will be stopped if indoor
temperature falls to air-
conditioning machine preset temperature.
Effect (Field Setting by remote controller)
It is reduction of about 5% of air-conditioning load at the time of cooling operation.
Air conditioning operation carries out April to October, and air-conditioning load is calculated only with
sensible heat load.
VKM-GA(M) series 5
Features ED71-440B
Nighttime Free Cooling Operating Condition Nighttime Free Cooling Precedent Condition
Air-conditioner Operation
<STOP> Air-conditioner Operation Yes
<RUN>
No
No
Nighttime free cooling Operation
<ON>
Yes
Temp. monitor operation time Yes
Standard mode
Lapsed time setup <Lapsed time> > 60hr
<2hr, 4hr, 6hr, 8hr>
No Standby mode
<60 Min>
( Fan ON time is included )
Yes
<Indoor temp.> < <Preset temp.> Yes
=
Fan operation & Temperature monitor
<5Min>
No
Yes
Yes
<Indoor temp.> < <Outdoor temp.>
No =
<Indoor temp.> > <Preset temp.+2˚C>
No
Yes
Yes
Fan operation Lapsed time Fan operation
No <Lapsed time> > 60Min <STOP>
<Indoor temp.> > <Outdoor temp.>
No
Yes
Fan operation
<ON (H)or(U-H)tap>
EA RA EA RA EA RA
Automatic Automatic
changeover changeover
OA SA OA SA OA SA
6 VKM-GA(M) series
ED71-440B Features
6.3.3 Efficient Outdoor Air Introduction with Heat Exchanger and Cooling / Heating Operation
Indoor unit with outdoor air treatment
Using outdoor air, the temperature can 100 80
be brought near room temperature with 60
minimal cooling capacity through the
use of outdoor air. Outdoor air temperature
Heating and cooling in summer
Effect of full heat exchange
–5 0 5 10 15 20 25 30 35 40
Dry bulb temperature (˚CDB)
6.3.4 Operations, Such as Cleaning, Ventilation, Cooling / Heating and Humidifying, are Possible
with One Remote Controller
Four air conditioner functions can be managed using a single remote control. This makes it easy to obtain
high-quality and energy-efficient outdoor air treatment.
The VRVIII
outdoor unit
Heat Reclaim
Link connection Ventilator (VKM)
VKM-GA(M) series 7
Features ED71-440B
Note: 4-6 can be set at the initial setting only. (When using the remote controller BRC1C62)
Indoor Heat
unit Reclaim
Structure Ventilator
(VKM)
Remote
Controller
(HC0228)
Dust does not fall off from the air filter because the If conventional Heat Reclaim Ventilator, with
air supply fan of the interlocked indoor unit exclusive remote controller, is directly connected
remains activated even when the Heat Reclaim to indoor unit of air conditioner, dust may fall off
Ventilator is operated independently. from air filter when air conditioner is OFF.
Notes: 1. In case of the direct duct connection system, operate interlocking with indoor units.
2. Do not connect the duct with discharge air side of indoor units.
8 VKM-GA(M) series
ED71-440B Features
Installation Examples
Direct duct connection system Independent duct system
(HC0007) (HC0008)
Outdoor Supply
Air Air
Heat Exchanger Element
(Heat Recovery) (HC0230)
By setting to automatic Proper use of Heat recovery ventilation and normal ventilation saves
ventilation mode energy.
When the cooling operation is required in winter, use of heat recovery
ventilation is not efficient because the outdoor air temperature is
Approx. 6% reduction
normally lower than that of the indoor.
of heating / cooling load
Thus, the proper use of ventilation mode enhances the heating / cooling
efficiency.
Automatic Ventilation mode changeover
Operation Sensor of ventilation Decision of mode
Difference between (Which is more
indoor / outdoor temp. energy efficient?)
Indoor temp. > Outdoor temp. Normal ventilation (Bypass)
Cooling
Indoor temp. < Outdoor temp. Heat recovery ventilation
Indoor temp. > Outdoor temp. Heat recovery ventilation
Heating
Indoor temp. < Outdoor temp. Normal ventilation (Bypass)
Outdoor Supply
Air Air
Heat Exchanger Element
(Heat Recovery) (HC0231) Automatic
Changeover
Normal (Bypass) mode
Exhaust Return
Air Air
Outdoor Supply
Air Air
Heat Exchanger Element
(Heat Recovery) (HC0232)
Reduction of
Total heating / cooling 26%
26% reduction load (%)
of heating / cooling
20%
0%
load
Normal Heat Reclaim Ventilator Interlocked
operation independent operation operation (HC0233)
Note: The total heating / cooling load may vary depending on the climate or the other environmental conditions.
VKM-GA(M) series 9
Features ED71-440B
Supply air volume can be set at a higher level Exhaust air volume can be set at a higher level
Detail
than the exhaust air by the remote controller. than the supply air by the remote controller.
30.6˚C SA
62% RH 27.4˚C
63% RH
SA
Temperature Integrally-
and humidity formed liner
RA
26˚C RA
50% RH
32˚C (HC0013)
70% RH Integrally-formed liner
HEP anti-molding
Features
• High air shielding
Even in the conventional less humidity conditions, maintaining the features of the material that can get
excellent moisture permeability, we have achieved high air shielding, by special processing in the step of
milling paper.
Moisture release
Less humid air
Moisture absorbing liquid
• Polymer material that inhibits air permeability that treated on the surface of the heat exchanger
element restrains air permeability.
10 VKM-GA(M) series
ED71-440B Features
Parallel air flow system (Daikin) Cross air flow system (Others)
This system prevents misconnection and
simplifies the installation work.
SA OA SA EA
RA EA RA OA
(HC0234) (HC0235)
6.7.6 The Operation is Available When the Outdoor Air Temperature is Down to -15°C
(Operation when the outdoor air temperature becomes lower than -10°C)
When the outdoor air suction temperature becomes lower than -10°C, the unit is changed to intermittent
operation to prevent freezing of the heat exchanger element and dew condensation within the unit.
Intermittent operation
The outdoor air thermistor (standard equipment) within the unit detects the temperature. According to
the detected temperature, the following operation determines.
<Step 1>
• The air supply fan is changed to intermittent operation, when the temperature is lower than -10°C.
• The intermittent operation of the air supply fan is changed to an operation of each cycle for 45
minutes’ operation after stopping operation for 15 minutes.
• The exhaust fan operates continuously according to setup.
<Step 2>
• When the temperature becomes lower than -15°C, the unit stops operation to prevent any defect,
such as dew condensation and freezing. The unit does not ventilate.
But, to detect the elevation of the outdoor air temperature, the unit operates for 5 minutes per hour.
6.7.7 The High Efficiency Filter (that has 65% of Average Dust Collecting Efficiency) is Suitable
High efficiency filter Maintenance cover
Name plate
Control box AIR
FLOW High efficiency
Install the high efficiency The side of heat
filter to meet the direction exchanger element
filter
of the arrow of the name plate.
Rail
VKM-GA(M) series 11
Features ED71-440B
= 20 × A
Required ventilating
air flow rate (m3 / h) B
Notes: 1. 20 (in the above equation) means “20(m3 / h · person)”, which is the required ventilating air flow rate
based on the CO2 exhausted by an adult sitting still in a room. If smoking is allowed, other calculation
method should be used.
2. Use 10 (m2) if the area occupied per person exceeds 10 (m2).
<Table 1>
Area occupied per
Type of building Remarks
person (N)
Floor space of a part used for business
Dining houses, restaurants, coffee-shops 3 m2 purposes
Notes: 1. Table indicates the required ventilating air flow rate calculated as 20 m3 / h.
2. The area occupied per person by type of business is calculated in reference to Application Standards
for building administration in compliance with Building Standards Act in Japan.
Required ventilating
= C×D×E
air flow rate (m3 / h)
(Selection example)
Place: Living room of common household
Required ventilation: 6 times / h (See Table 2)
Area of room: Approx. 30 (m2)
Height of ceiling: 2.4 m
.
Required ventilating air flow rate = 6 × 30 × 2.4 =. 432 (m3 / h)
Required ventilating air flow rate 500 is almost equivalent to the unit type 50.
So select the close size of the unit.
In this case, select VKM50GAMV1.
12 VKM-GA(M) series
ED71-440B Features
<Table 2>
Groups Type of room Ventilation Groups Type of room Ventilation
required required
Living room 6 Audience room 6
Bathroom 6 Corridor 6
Common Playhouses
Drawing room 6 and movie Smoking room 12
household theaters
Toilet 10 Toilet 12
Kitchen 15 Projector room 20
Restaurant 6 Office room 6
Sushi restaurant 6 General work room 6
Dining
places Banquet hall 10 Telephone room 6
Tempura restaurant 20 Spinning plant 10
Cooking room 20 Printing plant 10
Guest room 5 Battery room 10
Corridor 5 Machinery plant 10
Dance hall 8 Plants Generator room 15
Large dining hall 8 Substation room, 15
Inns and
Washroom, Toilet 10 Painting shop, 15
hotels
Cooking room 15 Welding plant 15
Laundry room 15 Chemical plant 15
Engine room 20 Food plant 20
Boiler room 20 Wood working plant 20
Casting plant 50
Office room 6
General Waiting room 10
buildings Show room, Toilet 10
Consultation office 6
Conference room 12
Comfort 20
stations
Dark rooms Dark rooms for photo 16
Guest
Sick room 6 rooms of 6
ship
VKM-GA(M) series 13
Specifications ED71-440B
7. Specifications
7.1 With DX-Coil
Type VKM50GAV1 VKM80GAV1 VKM100GAV1
Refrigerant R-410A
Power Supply 1 phase, 220-240V, 50Hz
Air flow rate (m3/h) 500 750 950
Ultra-high
Static pressure (Pa) 180 170 150
Air Flow Rate & Air flow rate (m3/h) 500 750 950
Static Pressure High
(Note 6) Static pressure (Pa) 150 120 100
Air flow rate (m3/h) 440 640 820
Low
Static pressure (Pa) 110 80 70
Ultra-high A 3.0 3.0 3.0
Normal Amp.
(Note 7) High A 2.5 2.6 2.5
Low A 2.1 2.1 2.1
Ultra-high W 560 620 670
Normal Input
High W 490 560 570
(Note 7)
Low W 420 470 480
Fan Type Sirocco Fan
Motor Output kW 0.280×2 0.280×2 0.280×2
Ultra-high (dB) 38/38.5/39 40/41/41.5 40/40.5/41
Sound Level
(Note 4, 5) High (dB) 36/36.5/37 37.5/38/39 38/38.5/39
220/230/240V
Low (dB) 33.5/34.5/35.5 34.5/36/37 35/36/36.5
Ultra-high (%) 76 78 74
Temp. Exchange
Efficiency High (%) 76 78 74
(Note 7, 10, 11)
Low (%) 77.5 79 76.5
Ultra-high (%) 64 66 62
Enthalpy Exchange
Efficiency (Cooling) High (%) 64 66 62
(Note 7)
Low (%) 67 68 66
Ultra-high (%) 67 71 65
Enthalpy Exchange
Efficiency (Heating) High (%) 67 71 65
(Note 7)
Low (%) 69 73 69
Casing Galvanized Steel Plate
Insulating Material Self-Extinguishable Urethane Foam
Heat Exchanging System Air to Air Cross Flow Total Heat (Sensible + Latent Heat) Exchange
Heat Exchanger Element Specially Processed Nonflammable Paper
Air Filter Multidirectional Fibrous Fleeces
Rows × Stages × Fin Pitch (mm) 2 × 12 × 2.2
Coil (Cross Fin Coil)
Face Area (m2) 0.078 0.118 0.165
Cooling Capacity (Note 2) (kW) 4.71 (1.91) 7.46 (2.96) 9.12 (3.52)
Heating Capacity (Note 3) (kW) 5.58 (2.38) 8.79 (3.79) 10.69 (4.39)
Dimensions Height × Width × Depth (mm) 387 × 1,764 × 832 387 × 1,764 × 1,214 387 × 1,764 × 1,214
Connection Duct Diameter (mm) φ200 φ250
Liquid (mm) φ6.4 C1220T (Flare Connection)
Piping Connection Gas (mm) φ12.7 C1220T (Flare Connection)
Drain PT3/4 External Thread
Refrigerant Control Electronic Expansion Valve
Connectable Outdoor Unit R-410A P(A) series
Weight Net (kg) 96 109 114
Around Unit 0°C~40°C DB 80%RH or Less
Unit Ambient
OA (Note 8) -15°C~40°C DB 80%RH or Less
Condition
RA (Note 8) 0°C~40°C DB 80%RH or Less
Operation Mode Heat Exchange Mode, Bypass Mode, Freshup Mode
Operation Manual, Installation Manual, Duct Connecting Flange, M4 Tapping Screw (for
Accessories
Connecting Duct), Refrigerant Piping Insulation Cover, Clamp
Drawing Number C: 4D051281 C: 4D051283 C: 4D051284
Notes:
1. Cooling and heating capacities are based on the following conditions. Fan is based on High and Ultra-high.
The figures in the parenthesis indicate the heat reclaimed from the heat recovery ventilator.
When calculating the capacity as indoor units, use the following figures: VKM50GAV1: 3.5kW VKM80GAV1: 5.6kW VKM100GAV1: 7.0kW
2. Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB
3. Indoor temperature: 20°C DB, Outdoor temperature: 7°C DB, 6°C WB
4. The operating sound measured at the point 1.5 m below the center of the unit is converted to that measured at an anechoic chamber built in accordance with the JIS C
1502 condition. The actual operating sound varies depending on the surrounding conditions (near running unit’s sound, reflected sound and so on) and is normally higher
than this value.
For operation in a quiet room, it is required to take measures to lower the sound. In details, refer to Engineering Data.
5. The noise level at the air discharge port is about 8-11 dB higher than the unit’s operating sound.
For operation in a quiet room, it is required to take measures to lower the sound for example install more than 2m soft duct near the air discharge grille.
6. Air flow rate can be changed over to Low mode or High mode.
7. Normal Amp., input, efficiency depend on the above air flow rate value.
8. OA: Fresh air from outdoor, RA: Return air from room
9. The specifications, designs and information here are subject to change without notice.
10. Temperature exchange efficiency is a mean value in cooling and heating.
11. Efficiency is measured under the following conditions. Ratio of rated external static pressure has been kept as follows. Outdoor side to indoor side is equal to 7 to 1.
12. In heating operation, freezing of the outdoor unit's coil increases. Heating capability decreases and the system goes into defrost operation.
During defrost operation, the fans of the unit continues driving (factory setting). The purpose of this is to maintain the amount of ventilation and humidifying.
13. When connecting with a VRV heat recovery type outdoor unit and bringing the RA (exhaust gas intake) of this unit directly in from the ceiling, connect to a BS unit identical
to the VRV indoor unit (master unit), and use group-linked operation. See the Engineering Data for details.
14. When connecting the indoor unit directly to the duct, always use the same system on the indoor unit as with the outdoor unit, perform group-linked operation, and make the
direct duct connection settings from the remote controller. (Mode No. “17 (27)” – First code No. “5” – Second code No. “6”.) Also, do not connect to the outlet side of the
indoor unit. Depending on the fan strength and static pressure, the unit might back up.
14 VKM-GA(M) series
ED71-440B Specifications
VKM-GA(M) series 15
Specifications ED71-440B
14. In heating operation, freezing of the outdoor unit’s coil increases. Heating capability decreases and the system goes into defrost operation.
During defrost operation, the fans of the unit continues driving (factory setting). The purpose of this is to maintain the amount of ventilation and humidifying.
15. When connecting with a VRV heat recovery type outdoor unit and bringing the RA (exhaust gas intake) of this unit directly in from the ceiling, connect to a BS unit identical
to the VRV indoor unit (master unit), and use group-linked operation. See the Engineering Data for details.
16. When connecting the indoor unit directly to the duct, always use the same system on the indoor unit as with the outdoor unit, perform group-linked operation, and make the
direct duct connection settings from the remote controller. (Mode No. “17 (27)” – First code No. “5” – Second code No. “6”.) Also, do not connect to the outlet side of the
indoor unit. Depending on the fan strength and static pressure, the unit might back up.
7.3 Humidifier
VKM50GAMV1 VKM80GAMV1 VKM100GAMV1
Humidifier type Natural evaporating type humidifier
Porosity plate 120 pcs.
Wetted element Porosity plate 60 pcs. Porosity plate 90 pcs.
(60×2 pcs.)
Water inlet port φ6.4 C1220T (Flare Connection)
Water outlet port PT3/4
2
Supply water pressure kg/cm 0.2 (Min.) ~ 5.0 (Max.)
Notes: 1. Feed clean water (city water, tap water or equivalent). Dirty water may clog the valve or cause dirt
deposits in the water container, resulting in poor humidifier performance. (Never use any cooling tower
water and heating - purpose water.)
Also, if the supply water is hard water, use a water softener because of short life.
∗Life of humidifying element is about 3 years (4,000 hours), under the supply water conditions of
hardness: 150 mg/l. (Life of humidifying element is about 1 year (1,500 hours) under the supply water
conditions of hardness: 400 mg/l.)
Annual operating hours: 10 hours / day × 26 days / month × 5 month = 1,300 hours
2. Maintain the supply water temperature at 5 ~ 50°C and its pressure at 20 ~ 490 kPa (0.2 ~ 5.0 kg/cm2).
If the water pressure is above 490 kPa (5.0 kg/cm2), add pressure reducing valve in between the kit
and the supply water shut - off valve.
3. The supply water line cannot be directly connected with a utility water tap. To unavoidably take water
from such line, employ a CISTERN (gotten configuration authorization).
4. Be sure to provide thermal insulation around the indoor piping as well as the shut - off valves.
5. In order to prevent harmful bacteria from generating, do maintenance on humidifying unit portion at the
beginning and the end of the heating season according to the operation manual.
16 VKM-GA(M) series
ED71-440B Dimensions
8. Dimensions
VKM50GAMV1
Unit (mm)
3D051285
VKM-GA(M) series 17
Dimensions ED71-440B
VKM80GAMV1
Unit (mm)
3D051286
18 VKM-GA(M) series
ED71-440B Dimensions
VKM100GAMV1
Unit (mm)
3D051287
VKM-GA(M) series 19
Dimensions ED71-440B
VKM50GAV1
Unit (mm)
3D051288
20 VKM-GA(M) series
ED71-440B Dimensions
VKM80GAV1
Unit (mm)
3D051289
VKM-GA(M) series 21
Dimensions ED71-440B
VKM100GAV1
Unit (mm)
3D051290
22 VKM-GA(M) series
ED71-440B Wiring Diagram
9. Wiring Diagram
VKM50GAMV1
VKM80GAMV1
VKM100GAMV1
C: 3D051310
VKM-GA(M) series 23
Wiring Diagram ED71-440B
VKM50GAV1
VKM80GAV1
VKM100GAV1
C: 3D051311
24 VKM-GA(M) series
ED71-440B Fan Performance
4D051312 4D051313
VKM100GAMV1
4D051314
VKM-GA(M) series 25
Fan Performance ED71-440B
VKM50GAV1 VKM80GAV1
4D051315 4D051316
VKM100GAV1
4D051317
26 VKM-GA(M) series
ED71-440B Fan Performance
90
reading off the chart [%]
Exchange Efficiency
80
70
60
50
40 50 60 70 80 90 100
Corrected Exchange Efficiency [%]
<Example of correction>
VKM-GA(M) series 27
Capacity Tables ED71-440B
28 VKM-GA(M) series
ED71-440B Capacity Tables
11.2 Heating
Capacity Outdoor Coil inlet air temp. °CDB
MODEL DX-Coil
°CDB °CWB 16.0 18.0 20.0 21.0 22.0 24.0
Only
-14.7 -15.0 2.2 2.2 — — — —
-12.6 -13.0 2.3 2.3 — — — —
-10.5 -11.0 2.4 2.4 — — — —
-9.5 -10.0 2.5 2.4 — — — —
-8.5 -9.1 2.5 2.5 — — — —
-7.0 -7.6 2.6 2.6 2.7 — — —
-5.0 -5.6 2.7 2.7 2.7 — — —
VKM50 -3.0 -3.7 2.8 2.8 3.0 3.0 — —
GA(M)V1 2.8kW
0.0 -0.7 3.0 3.0 3.1 3.1 — —
3.0 2.2 3.1 3.1 3.2 3.1 3.0 —
5.0 4.1 3.3 3.2 3.2 3.1 3.0 —
7.0 6.0 3.4 3.4 3.2 3.1 3.0 —
9.0 7.9 3.5 3.4 3.2 3.1 3.0 —
11.0 9.8 3.6 3.4 3.2 3.1 3.0 2.8
13.0 11.8 3.6 3.4 3.2 3.1 3.0 2.8
15.0 13.7 3.6 3.4 3.2 3.1 3.0 2.8
-14.7 -15.0 3.4 3.4 — — — —
-12.6 -13.0 3.6 3.6 — — — —
-10.5 -11.0 3.7 3.7 — — — —
-9.5 -10.0 3.9 3.7 — — — —
-8.5 -9.1 3.9 3.9 — — — —
-7.0 -7.6 4.1 4.1 4.2 — — —
-5.0 -5.6 4.2 4.2 4.2 — — —
VKM80 -3.0 -3.7 4.4 4.4 4.7 4.6 — —
4.5kW
GA(M)V1 0.0 -0.7 4.7 4.7 4.9 4.9 — —
3.0 2.2 4.9 4.9 5.0 4.9 4.7 —
5.0 4.1 5.2 5.0 5.0 4.9 4.7 —
7.0 6.0 5.3 5.3 5.0 4.9 4.7 —
9.0 7.9 5.5 5.3 5.0 4.9 4.7 —
11.0 9.8 5.7 5.3 5.0 4.9 4.7 4.4
13.0 11.8 5.7 5.3 5.0 4.9 4.7 4.4
15.0 13.7 5.7 5.3 5.0 4.9 4.7 4.4
-14.7 -15.0 4.4 4.4 — — — —
-12.6 -13.0 4.6 4.6 — — — —
-10.5 -11.0 4.8 4.8 — — — —
-9.5 -10.0 5.0 4.8 — — — —
-8.5 -9.1 5.0 5.0 — — — —
-7.0 -7.6 5.2 5.3 — — — —
-5.0 -5.6 5.4 5.4 5.4 — — —
VKM100 -3.0 -3.7 5.6 5.6 6.0 — — —
GA(M)V1 5.6kW
0.0 -0.7 6.0 6.0 6.2 6.2 — —
3.0 2.2 6.2 6.2 6.4 6.2 6.0 —
5.0 4.1 6.6 6.4 6.4 6.2 6.0 —
7.0 6.0 6.8 6.8 6.4 6.2 6.0 —
9.0 7.9 7.0 6.8 6.4 6.2 6.0 —
11.0 9.8 7.2 6.8 6.4 6.2 6.0 5.6
13.0 11.8 7.2 6.8 6.4 6.2 6.0 5.6
15.0 13.7 7.2 6.8 6.4 6.2 6.0 5.6
Note: Cooling and heating capacities are based on the following conditions. Fan is based on High and Ultra-high. The figures in the
parenthesis indicate the heat reclaimed from the heat recovery ventilator. When calculating the capacity as indoor units, use
the following figures: VKM50GAMV1: 3.5kW VKM80GAMV1: 5.6kW VKM100GAMV1: 7.0kW
VKM-GA(M) series 29
Sound Level ED71-440B
Location of microphone
4D051291
30 VKM-GA(M) series
ED71-440B Sound Level
230V, 50Hz
VKM50GAMV1 VKM80GAMV1 VKM100GAMV1
240V, 50Hz
VKM50GAMV1 VKM80GAMV1 VKM100GAMV1
VKM-GA(M) series 31
Sound Level ED71-440B
220V, 50Hz
VKM50GAV1 VKM80GAV1 VKM100GAV1
230V, 50Hz
VKM50GAV1 VKM80GAV1 VKM100GAV1
240V, 50Hz
VKM50GAV1 VKM80GAV1 VKM100GAV1
32 VKM-GA(M) series
ED71-440B Sound Level
OA SA
Flexible duct
Apply sound-insulating
material to the SA duct.
(HC0054)
2. Operating sound can be reduced more effectively by applying sound-insulating material to a portion of
the SA duct near the unit body than that near the air suction / discharge grille.
Heat Reclaim Ventilator Air supply
and exhaust
EA RA grille
OA SA
Flexible duct
Apply sound-insulating
material here for effective
operating sound reduction. (HC0055)
12.3.2 Taking Measures to Reduce Operating Sound Heard from Attic-installed Equipment and Air
Ducts
1. When installing large air volume models (650 m3 / h or more), avoid the following wherever possible if it
is expected to be necessary to apply sound-insulating material to them. (Fig.1)
(HC0056)
(1)Making the duct diameter extremely small (Example: φ 250 → φ 150, φ 200 → φ 100)
(2)Making the duct extremely bent using bellows (in particular, connecting bellows to the air discharge
outlet of the unit body)
(3)Making opening holes on the ceiling
(4)Hanging the unit on a material which does not have enough hanging strength
(HC0057)
Note: Some sound-insulating ceilings are not very effective in reducing low-frequency element of the operating
sound.
Note: When using a sound-insulating sheet, it is necessary to have the entire body of the unit covered with it.
Note, however, that some models do not allow the use of a sound-insulating sheet because it may badly
affect the ventilation of their radiation heat.
VKM-GA(M) series 33
Sound Level ED71-440B
12.3.3 Reducing Operating Sound Heard from the Air Discharge Outlet (Suction Inlet)
1. Use the following recommended optional accessories to reduce operating sound heard from attic-
installed duct type models. (Fig.3)
(HC0058)
2. If the above accessories do not give satisfactory effect or when an attic-installed cassette type model is
used, take the following measure.
Fig. 4
(1)
(HC0059)
3. To reduce the air flow sound heard from the air discharge outlet (suction inlet) of an attic-installed duct
type model, use a small diameter flexible duct, which excels in sound absorptivity, for greater sound
reduction effect.
(1) Branched duct (for letting air flow through two ducts to slow down its speed before it reaches the air
discharge outlets (suction inlets))
(HC0060)
4. Installation of the unit with the source of its operating sound located at a corner of a room will be a
partially effective sound reduction measure; it will keep persons in the center of the room free from the
annoying operating sound, with those in the corner of the room kept annoyed by the operating sound.
To avoid this, try to find the best installation place from which the operating sound is least heard by
everyone in the room.
34 VKM-GA(M) series
ED71-440B Sound Level
12.3.5 General Comparison of the Effect ((1) → (6) in more Effective Order)
(1) Mounting a silencer + flexible duct 2 m long (2) Mounting a flexible duct (3) Mounting a flexible duct
Mounting a silencer + flexible duct 6 m long 6 m long 2 m long to the main body
Silencer Silencer
Flexible duct 2 m
(4) Mounting a flexible duct (5) Mounting a silencer (6) Spiral duct 6 m
2 m long to an air suction No measures taken (1) (2) (3) (4) (5) (6)
discharge grille
(dB)
+ 10
Main body Main body Main body
Silencer +5
Spiral duct 4 m
Spiral duct 6 m
Suction /
discharge grille –5
(HC0061)
Note: Measure the noise at 1.5 m below the air supply grille. Operating noise conforms to JIS standard and the
value is converted in terms of the anechoic chamber.
VKM-GA(M) series 35
Optional Accessories ED71-440B
Flexible duct
(Option)
RA
High efficiency filter
(Option)
SA
Round hood
Branch duct (Field supply)
(Field supply)
SA Silencer (Option)
Duct
(Field supply)
Type FXLQ-MA
For wiring (indoor unit of VRV) FXFQ-P FXZQ-M FXCQ-M FXKQ-MA FXDQ-PB FXMQ-P FXMQ-MA FXHQ-MA FXAQ-MA FXNQ-MA FXUQ-MA
FXDQ-NB
KRP1C63 KRP1BA57 KRP1B61 KRP1B61 KRP1B56 KRP1C64 KRP1B61 KRP1BA54 — KRP1B61 —
Installation box for adaptor PCB Notes 2, 3 Notes 4, 6 Notes 2, 3 — Notes 4, 6 Note 2, 3 — Note 3 Notes 2, 3 — KRP1BA97
KRP1H98 KRP1BA101 KRP1B96 KRP1BA101 KRP4A96 KRP1CA93 KRP4AA93
Notes:1. Installation box is necessary for each adaptor marked . 6. Installation box is necessary for each adaptor.
2. Up to 2 adaptors can be fixed for each installation box. 7. *1 Necessary when operating a Heat Reclaim Ventilator (VKM) independently. When operating interlocked
3. Only one installation box can be installed for each indoor unit. with other air conditioners, use the remote controllers of the air conditioners.
4. Up to 2 installation boxes can be installed for each indoor unit. *2 For residential use only. When connected with a Heat Reclaim Ventilator (VKM), you can only switch the
5. Installation box is necessary for second adaptor. power ON/OFF. Cannot be used with other centralised control equipment.
Silencer
Nominal pipe diameter mm — 250 mm
Air suction/ White K-DGL200B K-DGL250B
discharge grille Nominal pipe diameter mm 200 250
High efficiency filter KAF242H80M KAF242H100M
Air filter for replacement KAF241G80M KAF241G100M
Flexible duct (1 m) K-FDS201D K-FDS251D
Flexible duct (2 m) K-FDS202D K-FDS252D
Drawing No. C: 3D051318B
Remote controller Central remote controller Unified ON/OFF controller Schedule timer
36 VKM-GA(M) series
ED71-440B Standard Drawing for Installation
3D051319A
VKM-GA(M) series 37
Standard Drawing for Installation ED71-440B
VKM80GAMV1
Unit (mm)
3D051320A
38 VKM-GA(M) series
ED71-440B Standard Drawing for Installation
VKM100GAMV1
Unit (mm)
3D051321A
VKM-GA(M) series 39
Standard Drawing for Installation ED71-440B
VKM50GAV1
Unit (mm)
3D051322
40 VKM-GA(M) series
ED71-440B Standard Drawing for Installation
VKM80GAV1
Unit (mm)
3D051323
VKM-GA(M) series 41
Standard Drawing for Installation ED71-440B
VKM100GAV1
Unit (mm)
3D051324
42 VKM-GA(M) series
ED71-440B Operation
15. Operation
(5) Damper
Important
Sometimes when first using the unit, the
smell of the heat exchanging element may
be noticeable, but it is not harmful. The smell
will gradually go away as the unit is used.
(23) RA
(21) EA Return air
Exhaust air from room
to outdoors
(24) SA
Supply air
(22) OA to room
Fresh air
from outdoors
(outdoor air)
(18) Solenoid valve
<VKM-GAMV1 series only>
1
[1]
3P130767-3G
VKM-GA(M) series 43
Operation ED71-440B
Remote controller
for indoor unit
Outdoor unit
• Independent system
Heat Reclaim Ventilator
-With DX Coil-
Outdoor unit
2 3
4 3
4 4
UNIT No.
GROUP
1 1
2
3
Remote controller for VRV BRC1A62 Remote controller for VKM BRC1D527 (EU only)
5 5
[2]
C: 3P130767-3G
44 VKM-GA(M) series
ED71-440B Operation
UNIT No.
GROUP
1,2,3 1,2,3
Remote controller for VRV BRC1A62 Remote controller for VKM BRC1D527 (EU only)
6 6
UNIT No.
GROUP
1,2,4
1 7,8
3 3,5 6
2
Remote controller for VRV BRC1A62 Remote controller for VKM BRC1D527 (EU only)
7 7
8-1 8-2
9 10
(2) Handle
(3) Rail
11 12
[3]
3P130767-3G
VKM-GA(M) series 45
Operation ED71-440B
1 English
C: 3P130767-3G
46 VKM-GA(M) series
ED71-440B Operation
• Do not place objects in direct proximity of the outdoor • For refrigerant leakage, consult your dealer.
unit and do not let leaves and other debris accumulate When the Heat Reclaim Ventilator is to be installed in a
around the unit. small room, it is necessary to take proper measures so that
Leaves are a hotbed for small animals which can enter the the amount of any leaked refrigerant does not exceed the
unit. Once in the unit, such animals can cause malfunctions, limiting concentration even when it leaks. If the refrigerant
smoke or fire when making contact with electrical parts. leaks exceeding the level of limiting concentration, an oxy-
• Watch your steps at the time of air filter cleaning or gen deficiency accident may happen.
inspection. • Do not install the Heat Reclaim Ventilator at any place
High-place work is required, to which utmost attention must where flammable gas may leak out.
be paid. If the gas leaks out and stays around the unit, a fire may
If the scaffold is unstable, you may fall or topple down, thus break out.
causing injury. • Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in elec-
WARNING (For installation) tric shocks, or fire.
English 2
C: 3P130767-3G
VKM-GA(M) series 47
Operation ED71-440B
• Use electric insulation between the duct and the wall • Are any obstructions near the outlet vent of the outdoor
when using metal ducts to pass metal or wire laths or unit?
metal plating into wooden buildings. They may reduce the function and increase the operating
This may cause electric shock and fire. noise.
• Arrange the drain hose to ensure smooth drainage. • If any abnormal noise is heard during the operation, con-
Incomplete drainage may cause wetting of the building, fur- tact your dealer.
niture etc. CHECK LIST ABOUT DRAIN PIPING AND WATER
• Avoid placing the controller in a spot splashed with SUPPLY WORK
water. • Make sure the drain works properly.
Water coming inside the controller may cause an electric During cooling operation, no drainage from the outdoor drain
leak or may damage the internal electronic parts. piping may clog the drain piping with dirt or dust, causing
water leakage from the indoor unit.
(For moving and reinstalling/ Stop the unit operation, and contact your dealer.
WARNING repairing)
• Do not modify the unit. 2 WHAT TO DO BEFORE OPERATION
This may cause electric shock or fire.
This operation manual is for the following systems with stan-
• Ask your dealer to move and reinstall the unit. dard control. Before initiating operation, contact your Daikin
Incomplete installation may result in a water leakage, elec- dealer for the operation that corresponds to your system type
tric shock, and fire. and mark.
• Do not disassemble or repair the unit yourself. If your installation has a customized control system, ask your
This may cause electric shock or fire. dealer for the operation that corresponds to your system.
Contact your dealer to have such work done. 2.1 NAMES OF PARTS (Refer to figure 1)
• When removing the unit, be sure not to tip it. (1) Hanger bracket
The water inside the unit may drip or leak out, and get on (2) Duct connecting flange
furniture, etc.
(3) Exhaust fan
• Do not move or attempt to re-install the remote control- (4) Air filter (Long life filter)
ler yourself. (5) Damper
Incorrect installation, may cause electric shock or fire. Con- (6) Electric parts box
tact your dealer to have such work done.
(7) Maintenance cover
¢CHECK LIST EXCEPT SAFETY CAUTION² (8) Heat exchanger elements
The items described below should be checked and ask your (9) Name plate
dealer when you feel uncertain or you can’t check by yourself. (10) Air supply fan
CHECK LIST ABOUT SELECTING INSTALLATION (11) Direct expansion coil
SITE (12) Gas pipe
• Is the outdoor unit installed in a well-ventilated location (13) Liquid pipe
with no obstructions in its vicinity? (14) Drain outlet
• Do not use in the locations described below. (15) Humidifier (Natural evaporating type)
a. Locations with mineral oil such as cutting oil in the atmo- <VKM-GAMV1 series only>
sphere. (16) Strainer (included) <VKM-GAMV1 series only>
b. Locations with salt in the air, such as coastal areas. (17) Feed water tank <VKM-GAMV1 series only>
c. Locations with sulfide gas in the air, such as hot springs. (18) Solenoid valve <VKM-GAMV1 series only>
d. Locations where voltage fluctuates, such as factory. (19) Remote controller (Optional accessory)
e. In automobiles or marine vessels. (20) Damper motor
f. Locations containing steam in the atmosphere or splat- (21) EA Exhaust air to outdoors
tered oil, such as kitchen.
(22) OA Fresh air from outdoors
g. Locations with mechanical equipment generating electro-
(23) RA Return air from room
magnetic wave.
h. Locations enveloped in acidic or alkaline steam. (24) SA Supply air to room
• Has any action for snow protection been taken?
Contact your Daikin dealer for details.
2.2 REMOTE CONTROLLER AND CHANGEOVER
SWITCH: NAME AND FUNCTION OF EACH
CHECK LIST ABOUT ELECTRIC WIRING WORK SWITCH AND DISPLAY
• All wiring must be performed by an authorized electrician. (Refer to figure 3 and 4)
Do not conduct the work yourself. Contact your dealer.
• Only the items marked with an asterisk (
mark) are expla-
• Electrical wiring must be done according to the local nation relating to the functions and display of the unit.
standards. Unmarked items are functions of the combined air condition-
• Is the circuit specific to air conditioner? ers. When using buttons for functions which are not avail-
CHECK LIST CORRESPONDING TO OPERATING able (buttons which are not described in the text) will cause
NOISE “NOT AVAILABLE” to be displayed.
• Is the unit installed at the following locations? Contact your dealer for more detailed descriptions of those
a. Location strong enough to support the weight of the unit, functions (buttons).
and which will not amplify noise or vibration.
1 On/off button
b. Location where the warm air and the noise from the outlet Press the button and the system will start. Press the button
vent of the outdoor unit will not bother neighbors. again and the system will stop.
3 English
3P130767-3G
48 VKM-GA(M) series
ED71-440B Operation
English 4
C: 3P130767-3G
VKM-GA(M) series 49
Operation ED71-440B
5 English
C: 3P130767-3G
50 VKM-GA(M) series
ED71-440B Operation
Example 1: Example 2:
In case of the remote controller “BRC1D527” and as equiva- In case of the remote controller “BRC1A62”
lent. Display changes as below.
Display changes as below.
When air conditioner and
When air conditioner and Heat Reclaim Ventilator
Heat Reclaim Ventilator are not connected via duct
are not connected via duct
<Operation mode>
<Operation mode>
VRV:
VRV: Cooling mode
Cooling mode Heat Reclaim Ventilator:
Heat Reclaim Ventilator: Heat exchange mode
Heat exchange mode
VRV:
VRV: Fan mode
Fan mode Heat Reclaim Ventilator:
Heat Reclaim Ventilator: Heat exchange mode
Heat exchange mode
VRV:
VRV: Stopping
Stopping Heat Reclaim Ventilator:
Heat Reclaim Ventilator: Heat exchange mode
Heat exchange mode
<Operation mode>
<Operation mode>
VRV:
VRV: Cooling mode
Cooling mode Heat Reclaim Ventilator:
Heat Reclaim Ventilator: Heat exchange mode
Heat exchange mode
VRV:
VRV: Fan mode
Fan mode Heat Reclaim Ventilator:
Heat Reclaim Ventilator: Heat exchange mode
Heat exchange mode
English 6
C: 3P130767-3G
VKM-GA(M) series 51
Operation ED71-440B
40
(a) 2 Press ventilation mode selector button if you wish to
change the mode.
30 The display rotates through the following selections
every time the button is pressed.
(c)
20 (b)
OFF ON OFF
Nighttime free cooling operation
(e)
OFF
(d)
7 English
3P130767-3G
52 VKM-GA(M) series
ED71-440B Operation
English 8
C: 3P130767-3G
VKM-GA(M) series 53
Operation ED71-440B
“ ” “ ”
2 Press the programming time button and set the time for
stopping or starting the system.
Each time this button is pressed, the time
advances or goes backward by 1 hour.
9 English
C: 3P130767-3G
54 VKM-GA(M) series
ED71-440B Operation
When you want to start operation after a desired time has 6 Press the “ ” button. “ ” icon displays.
elapsed This icon means the unit will stop at the set time.
Example: When all data for the schedule timer actions for Monday
Set the time to “8”. are entered, you must confirm the programmed actions.
p Make sure the last schedule timer action you want to
8hr keep is selected (schedule timer actions with a higher
“ ” will display.
number will be deleted).
Starts operation 8 hours after the reservation is complete. Now you must choose between 2 options:
The reservation is cancelled after operation starts.
• Set the start time while the unit is stopped. 1. CONFIRM AND COPY TO NEXT DAY
• The remaining time will count at the same time after reser- 7 The schedule timer action programmed for the current
vation is complete. day are also valid for the next day: use the “confirm last
action and copy actions to next day” function by pressing
the “ ” and “ ” buttons simultaneously for 5 sec-
See the example below if you want to reserve “off after time”
onds. “DAY OF THE WEEK INDICATOR” will change
and “on after time” at the same time.
blinking from “ ” to “ ”.
For example: (Refer to figure below)
When the timer is programmed to stop the system after 3 hours 2. CONFIRM ONLY
and start the system after 4 hours, the system will stop after 8 The schedule timer action programmed for the current
3 hours and start 1 hour later. day are only valid for the selected day: use the “confirm
Example: last action and go to next day” function by pressing the
“ ” button for 5 seconds.
Program mode is quit and depending on the choice
made, the programmed actions are saved for Monday
(and possibly Tuesday).
English 10
C: 3P130767-3G
VKM-GA(M) series 55
Operation ED71-440B
• Use city water or clean water and take steps to prevent • If the dirt becomes impossible to clean, change the air filter
condensation from forming. (VKM-GAMV1 series only) (Air filter for exchange is optional).
• The life of humidifier become shorter when the supply (1) Detach the maintenance cover.
water is hard water. (VKM-GAMV1 series only) Go into ceiling through the inspection hatch, remove binding
Use a water softener. metal of maintenance cover and take it off.
(Refer to figure 8-1)
• Do not install the remote controller where the indoor (2) Detach the air filter.
temperature and humidity, respectively, are out of the Take out from the heat exchange elements.
range of 0-35°C and RH 40-80%. (Refer to figure 8-2)
This may cause malfunction. (3) Clean the air filter. (Refer to figure 9)
• Do not install the remote controller where direct sun- Use vacuum cleaner A) or wash the air filter with water B).
light may fall on it. A) Using a vacuum cleaner
This may cause discoloration or deformation. B) Washing with water
NOTE When the air filter is very dirty, use soft brush and neau-
tral detergent.
• When the fan motor fails, the remote controller does not dis- After cleaning, remove water and dry in the shade.
play any error code.
Usage under that status will lead to insufficient ventilation. NOTE
The air supply and exhaust fans should be checked once • Do not wash the air filter with hot water of more than 50°C,
every one or two months. as doing so may result in discoloration and/or deformation.
You can make a simple check such as below way. • Do not expose the air filter to fire, as doing so may result in
To check the wind flow, hold a bar of which the end has a burning.
string or other similar lightweight item over the supply grille • Do not use gasoline, thinner, or other organic solvents.
and exhaust grille. This may cause discoloration or deformation.
• When the solenoid valve fails, the remote controller does not (4) Fix the air filter.
display any error code. If the air filter is washed, remove water completely and allow
Usage under that status will lead to insufficient humidification to dry for 20 to 30 minutes in the shade. When dried com-
and increased tap water consumption. pletely, install the air filter back in place.
The solenoid valve should be checked at the beginning of the (Refer to figure 10)
heating season. <VKM-GAMV1 series only>
NOTE
• Be sure to install the air filter after servicing.
4 MAINTENANCE (Missing air filter causes clogged heat exchange element.)
(for a qualified service person only) The air filter is an optional item and the replacement is
available.
ONLY A QUALIFIED SERVICE PERSON IS ALLOWED TO
(5) Install the maintenance cover.
PERFORM MAINTENANCE
Refer to page 11 (4.1, (1)).
DO NOT CHECK OPENING INSIDE THE UNIT BY YOURSELF.
For remote controllers which display the filter sign, turn on the
WARNING power after maintenance, and press the filter sign reset button.
• BEFORE OBTAINING ACCESS TO TERMINAL DEVICES,
Consult your dealer if you want to change the time setting
ALL POWER SUPPLY CIRCUITS MUST BE INTERRUPTED. for when the filter sign goes on.
• To clean the Heat Reclaim Ventilator, or maintenance be
sure to stop operation, and turn the power switch off. It may CAUTION
cause electrical shock and it is very dangerous to touch the • Always use the air filter.
rotating part. If the air filter is not used, heat exchange elements will be clogged,
• Do not wash the Heat Reclaim Ventilator with water. possibly causing poor performance and subsequent failure.
Doing so may result in an electric shock.
4.2 HOW TO CLEAN THE HEAT EXCHANGE ELEMENT
CAUTION AT LEAST ONCE EVERY TWO YEARS
• Use gloves when cleaning. (FOR GENERAL OFFICE USE)
Cleaning without gloves may cause injury. (CLEAN THE ELEMENT MORE FREQUENTLY IF NECES-
SARY.)
• Watch your step.
Use caution, as this requires working in high places. WARNING
• Do not use benzene or thinner to clean the outside surfaces • Please exchange the heat exchange element if you find
of the air conditioner. that the knob of the heat exchange element is damaged
This may cause cracks, discoloration, or machine trouble. or is deteriorated when cleaning it.
There is falling danger.
4.1 HOW TO CLEAN THE AIR FILTER
Clean the air filter when the display shows “ ” (TIME TO (1) Detach the maintenance cover.
CLEAN AIR FILTER). Refer to page 11 (4.1, (1)).
It will display that it will operate for a set amount of time. (2) Detach the air filter.
Refer to page 11 (4.1, (2)).
AT LEAST ONCE EVERY YEARS (FOR GENERAL OFFICE USE)
(3) Take out the heat exchange elements.
(CLEAN THE MORE FREQUENTLY IF NECESSARY.)
Pull out the air filter and then pull out the two heat
• Increase the frequency of cleaning if the unit is installed in a exchanger elements. (Refer to figure 11)
room where the air is etermely contaminated.
11 English
C: 3P130767-3G
56 VKM-GA(M) series
ED71-440B Operation
(4) Use a vacuum cleaner to remove dust and foreign objects For dealers
on the surface of the heat exchange element. Content of maintenance Problems if
(Refer to figure 12) Inspected maintenance
• Use the vacuum cleaner equipped with a brush on the part Items to be is not carried
Solution
tip of the suction nozzle. inspected out
• Lightly contact the brush on the surface of the heat
exchange element when cleaning. Check for Clean if Insufficient
(Do not crush the heat exchange element while cleaning.) Strainer clogging clogged. humidifying.
(80-mesh) Check o-ring Replace if
CAUTION Leaking.
for cracks cracked.
• Do not clean touching strongly with a vacuum cleaner. This
Clean if it Insufficient
may crush the mesh of the heat exchange elements.
Check for does not humidifying.
• Never wash the heat exchange element with water.
operation of work properly Overflowed
• Have your dealer professionally clean the filter if it is very
float switch due to build- feed water
dirty.
Feed water up. tank.
(5) Put the heat exchange element on the rail and insert it tank Weak fan
securely in place. strength.
(6) Install the air filter securely in place. Clean if very
Check for dirt Reduced
(Refer to page 11 (4.1, (4))) dirty.
humidifying
(7) Install the maintenance cover securely in place. capacity.
(Refer to page 11 (4.1, (5)))
Check for
Insufficient
4.3 SEASONAL MAINTENANCE shutting and
humidifying.
<VKM-GAMV1 series only> opening.
Overflowed
4.3.1 AT THE BEGINNING OF THE SEASON Check in a
Solenoid Replace if it feed water
(1) Check below similar fash-
valve doesn’t work. tank.
• Are the indoor and outdoor unit intake and outlet vents ion when
(Increased
blocked? checking the
tap water
Remove anything that might be blocking them. float switch
consumption)
(2) Turn the power on operation.
• When the power comes on, the characters in the remote 4.5 INSPECTION OF THE FAN MOTER
controller display appear.
(To protect the unit, turn the power on at least 6 hours NOTE
before operating it. This makes operation smoother.) • When the fan motor fails, the remote controller does not dis-
(3) Supply water (Start of heating season) play any error code.
4.3.2 AT THE END OF THE SEASON Usage under that status will lead to insufficient ventilation.
(1) On a clear day, use fan only operation for around half a The air supply and exhaust fans should be checked once
day to thoroughly dry out the interior of the unit. every one or two months.
• Refer to page 7 for details on fan operation. You can make a simple check such as below way.
(2) Turn off the power To check the wind flow, hold a bar of which the end has a
• When the power is shut off, the characters in the remote string or other similar lightweight item over the supply grille
controller display disappear. and exhaust grille.
• When the power is on, the unit consumes up to several 4.6 REPLACING THE HUMIDIFIER ELEMENT
dozen Watts of power. <VKM-GAMV1 series only>
Turn off the power to conserve energy.
(3) Stop water supply (End of heating season) • The humidifier element needs to be replaced regularly.
The humidifier element should in general be replaced once
every three years when supply water is soft water, but out-
4.4 INSPECTION AND MAINTENANCE OF THE side factors (If the water quality is hard water, etc.) as well
HUMIDIFIER <VKM-GAMV1 series only> as operating conditions (24-hour-a-day air conditioning, etc.)
• Have your dealer do the following inspections in order may shorten its productive life.
to get the longest use.
• In order to prevent harmful bacteria from generating, ask • Contact your dealer if you have any questions.
your dealer to do maintenance on humidifying unit portion at
the beginning or the end of the heating season. 5 TROUBLE SHOOTING
NOTE
5.1 THE FOLLOWING SITUATIONS ARE NOT MAL-
• When the solenoid valve fails, the remote controller does not
display any error code. FUNCTIONS
Usage under that status will lead to insufficient humidification • Operation does not start.
and increased tap water consumption. <Symptom>
The solenoid valve should be checked at the beginning of the The icon “ ” (under centralized control) is dis-
heating season. played on the remote controller and pressing the on/off but-
ton causes the display to blink for a few seconds.
<Cause>
This indicates that the central device is controlling the unit.
The blinking display indicates that the remote controller can-
not be used.
English 12
3P130767-3G
VKM-GA(M) series 57
Operation ED71-440B
• The remote control buttons do not work well. Blink- Blink- Incorrect combination with
Off UA
ing ing indoor unit and remote controller.
Measure: Turn off the main power switch.
Blink- Central control address over
On On UC
ing lapping
Transmission error between
Blink- Blink- Blink-
UE the unit and centralized con-
ing ing ing
troller
13 English
C: 3P130767-3G
58 VKM-GA(M) series
ED71-440B Operation
In case of the malfunction with the code in white letters After-sales service and warranty
on the black background in the unit still operates.
However, be sure to have it inspected and repaired After-sales service:
and as soon as possible.
If other than the above error codes are displayed, WARNING
there is a possibility that the problem in question has • Do not modify the unit.
occurred with a combined air conditioner or outdoor This may cause electric shock or fire.
unit. See the operation manuals included with the air
• Do not disassemble or repair the unit.
conditioners or outdoor units for details.
This may cause electric shock or fire.
5.3 IF THE SYSTEM DOES NOT PROPERLY OPERATE Contact your dealer.
EXCEPT FOR THE ABOVE MENTIONED CASE, AND • If the refrigerant leaks, keep out of fire.
NONE OF THE ABOVE MENTIONED MALFUNC- The refrigerant used in this unit is safe.
TIONS IS EVIDENT, CONTACT YOUR DEALER, AND Although the refrigerant does not usually leak, if the refriger-
REQUEST FOR INVESTIGATION THE SYSTEM ant leaks out into a room and comes in contact with the com-
ACCORDING TO THE FOLLOWING PROCEDURES bustible air in the equipment such as fan heater, stove, oil
BY A QUALIFIED SERVICE PERSON (gas) cooker, etc., it will cause toxic gas to be generated.
The following malfunctions must be cheched by a qualified When a refrigerant leakage failure has been repaired, con-
service person. Do not check by yourself. firm a service person that the leakage point has been cor-
rected surely before restarting operation.
• The unit does not operate at all.
a. Check if there is a power failure. • Do not remove or reinstall the unit by yourself.
After power has been restored, start operation again. Incomplete installation may cause a water leakage electric
b. Check if the fuse has blown. shock and fire.
Change the fuse. Contact your dealer.
c. Check if breaker has worked.
Contact your dealer. When asking your dealer to repair, inform related
d. Are there any problems with the power or wiring? staff of the details as follows:
Inspect the power and wiring. • Shipping date and installation date:
e. Are there any problems with the fan unit? • Malfunction:
Inspect the fan motor and fan. Inform the staff of the defective details.
(Malfunction code being displayed on
• Amount of discharged air is small and the discharging
the remote controller.)
sound is high.
• Name, address, telephone number
a. Check if the air filter and heat exchange element are
clogged. (Check both SA and RA air filter. Check both Repair where the warranty term is expired
sides of elements.) Contact your dealer. If necessary to repair, pay service is
Clean the air filter and heat exchange element. available.
• Amount of discharged air is large and so is the sound. Minimum storage period of important parts
a. Check if the air filter and heat exchange element are not Even after a certain type of air conditioner is discontinued,
installed. we have the related important parts in stock for 6 years at
Install the air filter and heat exchange element. least.
• It dries usually in winter. <VKM-GAMV1 series only> The important parts indicate parts essential to operate the air
a. Is the water supply service valve open? conditioner.
Open the water supply service valve.
Recommendations for maintenance and inspec-
b. Have you lowered setting on the humidistat (locally pro-
tion
cured) too far?
Correct the setting. Since dust collects after using the unit for several years, the
performance will be deteriorated to some extent.
• Humidifies very little or not at all. <VKM-GAMV1 series only> Taking apart and cleaning inside require technical expertise,
a. Is there water in the water supply tank? so we recommend entering a maintenance and inspection
b. Is water being supplied? contract (at a cost) separate from normal maintenance.
Inspect the water supply pipes and supply the water.
c. Is the strainer clogged? Recommended inspection and maintenance
Clean the strainer. cycles
d. Is the solenoid valve broken (i.e. won’t open)? [Note: The maintenance cycle is not the same as
Replace the solenoid valve. the warranty period.]
e. Is the humidifier element torn? Table 1 assumes the following usage conditions.
Replace. • Normal use without frequent starting and stopping of the
f. Has the water resistance of the humidifier element dropped? machine.
Replace the humidifier element. (Although it varies with the model, we recommend not start-
g. Are the control circuits broken? ing and stopping the machine more than 6 times/hour for
Replace the printed circuit board and other electric parts. normal use.)
h. Is the float switch broken? • Operation of the product is assumed to be 10 hours/day,
Replace the float switch. 2500 hours/year.
i. Is the water supply pressure sufficient?
Re-set it so that there is sufficient pressure.
j. Is there foreign matter in the feed water tank?
Clean the feed water tank.
English 14
3P130767-3G
VKM-GA(M) series 59
Operation ED71-440B
• Table 1 “Inspection Cycle” and “Maintenance Cycle” Lists Recommended replacement cycle of wear-out parts
Maintenance Cycle
[The cycle is not the same as the warranty period.]
Inspection
Name of Main Part [replacements and/ • Table 2 “Replacement Cycle” Lists
Cycle
or repairs]
Inspection
1~2 months Name of Main Part Replacement Cycle
Electric motor (fan, Cycle
recom- 20,000 hours
damper, etc.) Air filter 3 years
mended *1
High efficiency filter 1 year
PC boards 25,000 hours 1 year
(Optional accessory)
Heat exchanger Heat exchanger ele-
10 years 2 years 10 years
element ment
Heat exchanger 5 years Humidifier element 1 year 3 years (Note 3)
1 year
Sensor (thermistor) 5 years
Note 1
Remote controller and This table indicates main parts.
25,000 hours
switches See the maintenance and inspection contract for details.
Drain pan 8 years Note 2
Expansion valve 1 year *2 20,000 hours This maintenance cycle indicates recommended lengths of
time until the need arises for maintenance work, in order to
Electromagnetic valve 1 year 20,000 hours
ensure the product is operational as long as possible.
*1: Use for appropriate maintenance design (budgeting mainte-
• When the fan motor fails, the remote controller does not dis- nance and inspection fees, etc.).
play any error code. Note 3
Usage under that status will lead to insufficient ventilation. Life of humidifying element is about 3 years (4,000 hours),
The air supply and exhaust fans should be checked once under the supply water conditions of hardness: 150mg/l.
every one or two months. (Life of humidifying element is about 1 year (1,500 hours),
• You can make a simple check such as below way. under the supply water conditions of hardness: 400mg/l.)
To check the wind flow, hold a bar of which the end has a Annual operating hours: 10 hours/day × 26 days/
string or other similar lightweight item over the supply grille month × 5 month = 1,300 hours.
and exhaust grille.
*2: Contact your dealer for details.
• When the solenoid valve fails, the remote controller does not Note: Breakage due to taking apart or cleaning inside by any-
display any error code. one other than our authorized dealers may not be included in
Usage under that status will lead to insufficient humidification the warranty.
and increased tap water consumption.
The solenoid valve should be checked at the biginning of the Moving and discarding the unit
heating season.
• Contact your dealer for removing and reinstalling the total
Note 1
enthalpy heat exchanger when moving house since they
This table indicates main parts.
require technical expertise.
See the maintenance and inspection contract for details.
Note 2 • This unit contains chlorofluorocarbon in the refrigent.
This maintenance cycle indicates recommended lengths of When discarding, removing linstalling and maintaining the
time until the need arises for maintenance work, in order to unit, collect the refrigent in accordance with the local law for
ensure the product is operational as long as possible. the global environmental destruction prevention.
Use for appropriate maintenance design (budgeting mainte- In detail contact your dealer.
nance and inspection fees, etc.). Where to call
Depending on the content of the maintenance and inspection For after-sales service, etc., consult with your dealer.
contract, the inspection and maintenance cycles may in reality
be shorter than those listed here. Warranty period:
Shortening of “maintenance cycle” and “replacement Warranty period: Within one year after
cycle” needs to be considered in the following cases. installation.
• When used in hot, humid locations or locations where tem- • If it is necessary to repair the air conditioner within the war-
perature and humidity fluctuate greatly. ranty period, contact your dealer.
• When used in locations where power fluctuation (voltage, fre-
quency, wave distortion, etc.) is high.
(Cannot be used if it is outside the allowable range.)
• When installed and used in locations where bumps and
vibrations are frequent.
• When used in bad locations where dust, salt, harmful gas or
oil mist such as sulfurous acid and hydrogen sulfide may be
present in the air.
• When used in locations where the machine is started and
stopped frequently or operation time is long. (Example:
24 hour air-conditioning)
• When the supply water is hard water the humidifier’s life
become shorter.
15 English
3P130767-3G
60 VKM-GA(M) series
ED71-440B Installation
16. Installation
English 1
C: 3P130768-2H
VKM-GA(M) series 61
Installation ED71-440B
2 BEFORE INSTALLATION
The accessories needed for installation must be retained in 2. 3 OPTIONAL ACCESSORIES
your custody until the installation work is completed. Do • This unit can be made a part of two different systems: as part
not discard them! of the combined operation system used together with VRVII
After carrying in the unit, protect it with packing materials to pre- SYSTEM Air Conditioners, and as the independent system
vent it from scratching until installation work is done. using only the Heat Reclaim Ventilator. An operating remote
controller is required for this unit when using the unit as an
[1] Decide upon a line of transport. independent system.
[2] Leave the unit inside its packaging while moving, until reach- Select a suitable remote controller from below table accord-
ing the installation site. Where unpacking is unavoidable, ing to customer request and technical materials.
use a sling of soft material or protective plates together with
a rope when lifting, to avoid damage or scratches to the unit. Table
Hold the unit by the hanger brackets (4) when opening the Remote controller type BRC1A62, BRC1D527
crate and moving it, and do not lift it holding on to any other
part (especially the refrigerant piping, the drain piping, the NOTE) 1
water supply piping, and the duct connecting flange). If you use the remote controller which is not listed in above
• Be sure to check the type of R410A refrigerant to be used table, please consult your dealer.
before installing the unit. (Using an incorrect refrigerant will NOTE) 2
prevent normal operation of the unit.)
We recommend the remote controller “BRC1D527” espe-
• For the installation of an outdoor unit, refer to the installa-
tion manual attached to the outdoor unit. cially when the unit is used as independent system. Because
it displays the ventilation mode and can be selected ventila-
2. 1 PRECAUTIONS tion fan mode with the button.
• Be sure to instruct customers how to properly operate the • When installing the unit, have ready the round shape hood,
unit (especially maintenance of air filter, and operation proce- the air discharge grille and the air suction grille, and other
dure) by having them carry out operations themselves while parts needed for the installation.
looking at the manual. Consult your Daikin dealer when selecting optional accesso-
• Where the air contains high levels of salt such as that near ries.
the ocean and where voltage fluctuates greatly such as that
in factories. Also in vehicles or vessels.
2 English
C: 3P130768-2H
62 VKM-GA(M) series
ED71-440B Installation
FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE 3 SELECTING INSTALLATION SITE
DURING CONSTRUCTION AND CHECK AFTER
INSTALLATION IS FINISHED. CAUTION
a. Items to be checked after completion of work • When moving the unit during or after unpacking, make sure
to lift it by holding its hanger brackets. Do not exert any pres-
If not properly done, sure on other parts, especially the refrigerant piping, drain
Items to be checked Check
what is likely to occur piping, water supply piping and duct connecting flange.
Are the indoor and • If you think the humidity inside the ceiling might exceed 30°C
The units may drop, and RH80%, reinforce the insulation on the inter-unit piping.
outdoor unit fixed
vibrate or make noise. Use glass wool or polyethylene foam as insulation so that it is
firmly?
no thicker than 10mm and fits inside the ceiling opening.
Is the outdoor duct
installed to outside Condensate water • Use glass wool or polyethylene form of 10mm or more thick
with down slope? may drip. which fit into ceiling opening as insulation material.
(Refer to page 8 Fig. 16)
(1) Select an installation site where the following conditions
Is the gas leak test It may result in insuffi- are fulfilled and that meets with your customer’s approval.
finished? cient cooling. • Install in a place which has sufficient strength and stabil-
Is the unit fully insu- Condensate water ity. (Beams, ceiling, and other locations capable of fully
lated? may drip. supporting the weight of the unit.)
Insufficient strength is dangerous. It may also cause
Does drainage flow Condensate water vibration and unusual operating noise.
smoothly? may drip. • Where piping between indoor and outdoor units is possi-
Does the power sup- ble within the allowable limit. (Refer to the installation
The unit may malfunc-
ply voltage corre- manual for the outdoor unit.)
tion or the compo-
spond to that shown • Where nothing blocks air passage.
nents burn out.
on the name plate? • Where condensate can be properly drained.
The unit may malfunc- • Install in a location where the air around the unit or taken
Are wiring and piping into the humidifier will not drop below 0°C.
tion or the compo-
correct? • Do not install the unit directly against a ceiling or wall.
nents burn out.
(If the unit is in contact with the ceiling or wall, it can
Is the unit safely Dangerous at electric cause vibration.)
grounded? leakage. • Where sufficient clearance for maintenance and service
The unit may malfunc- can be ensured. (Refer to Fig. 1)
Is wiring size accord-
tion or the compo-
ing to specifications? Unit (mm)
nents burn out.
Is something blocking
the air outlet or inlet of It may result in insuffi-
either the indoor or cient cooling.
outdoor units?
600
Are refrigerant piping or more
The refrigerant Electric parts box
length and additional
charge in the system Maintenance
refrigerant charge space
is not clear.
noted down?
Is water supplied with
the water supply pip- Not humidified. minimum hight
ing connected? ∗H
20 or more
Please check all items listed in the “SAFETY PRECAUTIONS”
above once again.
• Select the ∗H dimension such that a downward slope Fig. 1
b. Items to be checked at time of delivery of at least 1/100 is ensured as indicated in “6 DRAIN
Items to be checked Check PIPING AND WATER SUPPLY WORK”.
Did you explain about operations while showing [PRECAUTION]
the operation manual to your customer? • Install the indoor and outdoor units, power supply wiring and
Did you hand the operation manual and warranty connecting wires at least 1 meter away from televisions or
over to your customer? radios in order to prevent image interference or noise.
Depending on the radio waves, a distance of 1 meter may
c. Points for explanation about operations
not be sufficient enough to eliminate the electric noise.
The items with WARNING and CAUTION marks in • The bellows may not be able to be used in some disc-
the operation manual are the items pertaining to tricts, so exercise caution. (Contact your local govern-
possibilities for bodily injury and material damage in ment office or fire department for details.)
addition to the general usage of the product. Accordingly, it • When discharging exhaust air to a common duct, the
is necessary that you make a full explanation about the Building Standard Law requires the use of fire-proof
described contents and also ask your customers to read the materials, so attach a 2 m copper plate standing duct or
operation manual. smoke back flow prevention damper.
English 3
3P130768-2H
VKM-GA(M) series 63
Installation ED71-440B
(2) Use suspension bolts for installation. Check whether 5 THE METHOD OF INSTALLATION
the ceiling is strong enough to support the weight of
the unit or not. If there is a risk, reinforce the ceiling CAUTION
before installing the unit. ¢¢Hold underside of the unit or hanger bracket without
(Installation pitch is mentioned as follow. Refer to it to check putting force on other parts when unpacking or moving
for points requiring reinforcing.) the unit.²²
¢¢As for the parts to be used for installation work, be sure to
4 PREPARATIONS BEFORE INSTALLATION use the provided accessories and specified parts desig-
(1) Confirm the positional relationship between the unit nated by our company.²²
and suspension bolts. (Refer to Fig. 2)
(1) Install the unit temporarily.
Leave space for servicing the unit and include inspection • Attach the hanger bracket to the suspension bolt. Be sure
hatches. (Always open a hole on the side of the electric parts to fix it securely by using nuts (M10, M12) and washers
box so that the air filters, heat exchange elements, fans, and (M10 with external dia. 30 to 34 mm, M12 with external
humidifier elements can easily be inspected and serviced.) dia. 36 to 38 mm) (locally procured) from the upper and
1764 Unit (mm) lower sides of the hanger bracket. (Refer to Fig. 4)
1688
Hanger bracket
(Suspension Duct layout precaution label
4 English
3P130768-2H
64 VKM-GA(M) series
ED71-440B Installation
or more
100mm
Horizontal line
Fig. 5 CAUTION
(5) Tighten the upper nut. Water accumulating in the drain piping can cause the
drain to clog.
(6) Attach the accessory duct connecting flanges using
the included screws to the outlet and intake holes
• The diameter of the drain pipe should be greater than or
(a total of four).
equal to the diameter of the connecting pipe.
When attaching, make sure the alignment markings on the
(pipe size: PT3/4B)
unit match up with the triangle on the each duct connecting
• When piping passes indoors, always insulate it all the
flange. (Refer to Fig. 6)
way to the base of the drain socket.
Screws (accessory) • In areas where freezing may occur, always take steps to
(6pcs.×4, total 24pcs.) prevent the pipes from freezing.
• Make sure water doesn’t leak from the drain pipes.
Duct connecting flange marking • Avoid bends and curves in the pipes to prevent them
getting clogged.
• If you are using central drain piping, follow the procedure
Unit alignment outlined in the figure 7-2.
Duct connecting • Select central drain pipes of proper size according to the
(RA is a φ3 indentation)
flange capacity of the connected unit.
Duct connecting flange • Make sure the tip of the drain pipes opens out into a loca-
Fig. 6 tion where the drainage can be safely processed.
(2) After piping work is finished, check drainage flows
6 DRAIN PIPING AND WATER SUPPLY smoothly.
WORK • Test the drainage by pouring around 1000cc of water into
the drain pan through the inspection hole by removing the
(1) Install the drain piping. maintenance cover (10 screws) or through the outlet duct
• Make sure the drain works properly. joint of supply air to room (SA). (Refer to Fig. 8)
• In case of the direct duct connection system,
there is negative pressure inside the unit relative to atmo- Supply air to room (SA)
spheric pressure when the unit is running, so be sure to Duct connecting flange
provide drain frap on the drain outlet. (See Fig. 7-1) (accessory)
Maintenance cover
Attached drain hose Portable pump
(Locally procured)
Bottom of unit
Drain outlet
or more or more
Bucket
50 mm 50 mm
Drain piping
(Locally procured)
(Locally procured)
Fig. 8 (Figure shows VKM-GAMV1)
English 5
3P130768-2H
VKM-GA(M) series 65
Installation ED71-440B
(4) Install the water supply piping. ¢VKM-GAMV1 series only² • Also, if the supply water is hard water, use a water soft-
ener because of short life.
CAUTION
Life of humidifying element is about 3 years (4,000
When installing the water supply piping, wash the pipes with hours), under the supply water conditions of hardness:
tap water so that all dirt is removed from them or install a 150mg/l.
drain valve somewhere along the piping and drain the pipes (Life of humidifying element is about 1 year (1,500
thoroughly until the water flowing through them is clear. hours), under the supply water conditions of hardness:
Make sure no cutting oils or detergents get into the pipes. 400mg/l.)
Annual operating hours: 10 hours / day × 26 days /
month × 5 month = 1,300 hours
• Connect the water supply piping with strainer (acces-
sory), other pipings and valves (locally procured) to the (5) Insulate all piping that passes indoors.
indoor unit as shown in the figure at below. After checking that the water supply piping connections do no
leak, insulate them using the included insulation as shown in
Fig. 10. (Tighten both edges with clamping material.)
(Refer to Fig. 10)
Clamp
Water supply piping (accessory)
with strainer
(accessory)
Insulation
Water supply shut-off Cap (for water supply piping)
valve (Locally procured)
(Locally procured) (accessory) Fig. 10
Water supply pipe Drain valve • Wrap the water supply piping with insulation to prevent con-
densation from forming.
(Locally procured) (Locally procured)
• In areas where freezing may occur, always take steps to pre-
vent the pipes from freezing.
[PRECAUTION]
• When installing the water supply piping, do not pass pip-
ing in front of the maintenance cover, as this will make it 7 REFRIGERANT PIPING WORK
impossible to remove the humidifier element. ¢For refrigerant piping of outdoor units, see the installation
• Include the water supply piping with strainer (included), a manual attached to the outdoor unit.²
water supply shut-off valve, and a drain valve (both locally ¢Execute heat insulation work completely on both sides of
procured) somewhere along the water supply piping that the gas piping and the liquid piping. Otherwise, a water
can be reached from the inspection hole. leakage can result sometimes.
• It is impossible to connect the water supply piping directly Use insulation that can withstand temperatures of at least
to public piping. Use a cistern tank (of the approved type)
120°C. Improve insulation of refrigerant piping according
if you need to get your water supply from public piping.
• When using copper piping for the water supply connec- to the installation environment.
tions, replace the included half-union joints. Refer to the following information as a guide.
(Refer to Fig. 9) • The ambient temperature is 30°C and humidity is 75% to
80%: 15 mm min. in thickness.
Replacement of joints when using copper connections • The ambient temperature exceeds 30°C and the humidity
Flare nut Half-union joint exceeds 80%: 20 mm min. in thickness.
(accessory) (accessory) Without reinforcement, condensation may form on the sur-
Water face of the insulation. ²
supply Unit
piping ¢Before refrigerant piping work, check the type of R410A
side side refrigerant is used. (Proper operation is not possible if the
Copper piping types of refrigerant are not the same.)²
Y-shaped CAUTION
strainer
Remove This product must use a new refrigerant (R410A).
Fig. 9 Exchange the included half-union joint Obey the following items.
• Use a pipe cutter and flare suitable for the type of
• Use two spanners when attaching or removing pipes to refrigerant (R410A).
the half-union joints. • Apply ester oil or ether oil around the flare portions
• Secure the water supply piping without applying pressure before connectioning.
[PRECAUTIONS] • Only use the flare nuts included with the unit. Using
• Use pure water (city water, tap water or equivalent) that different flare nuts may cause the refrigerant to leak.
satisfies the standard regulated by the law of each coun- • To prevent dust, moisuture or other foreign matter
try for water supply to the humidifier when performing from infiltrating the tube, either pinch the end or
anti-sweat work. cover it with tape.
• Dirty water may cause valves to clog, dirt to accumulate • Do not allow anything other than the designated refrig-
in water tanks, and resulting in poor humidifier perfor- erant to get mixed into the refrigerant circuit, such as
mance. (Never use water from a cooling tower or warm air, etc. If any refrigerant gas leaks while working on
water for heating.) the unit, ventilate the room thoroughly right away.
• Make sure the supply water is between 5°C and 40°C in
2
temperature and 0.02MPa to 0.49MPa (0.2kg/cm to • The outdoor unit is charged with refrigerant.
2
5kg/cm ) in pressure. Include a pressure release valve • Be sure to use both a spanner and torque wrench together,
between the humidifier and the strainer if the water pres- as shown in the drawing, when connecting or disconnecting
sure will be higher than this range. pipes to the unit. (Refer to Fig. 11)
• Use city water or clean water and take steps to prevent • Refer to the “Table 1” for the dimensions of flare nut spaces.
condensation from forming.
6 English
3P130768-2H
66 VKM-GA(M) series
ED71-440B Installation
0
the edges of the piping insulation material.
45 Ⳳ2
R0.4-0.8
0
90 Ⳳ2
0
(2) Do not tighten the clamp excessively so as to maintain the
A
I12.7 49.5–60.3N·m 16.2 – 16.6 appropriate thickness of the insulator.
(3) Wrap the sealing material around the upper
part of the flare nut connection. Seams up
• When connecting the flare nut, coat the flare section (inside)
with ester oil or ether oil, rotate three or four times first, then (4) Turn the seams up (see the figure on the right-
screw in. (Refer to Fig. 12) hand side).
English 7
C: 3P130768-2H
VKM-GA(M) series 67
Installation ED71-440B
8 DUCT CONNECTION • When connecting the indoor unit directly to the duct, always
¢Perform duct work keeping the following things in mind² use the same system on the indoor unit as with the outdoor
unit, perform group-linked operation, and make the direct
• Do not connect the ducts as shown in Fig. 15. duct connection settings from the remote controller (Mode
(a) Exterme bend (b) Multi bend (c) Reduce the (d) a bend right No. “17 (27)” – FIRST CODE NO. “5” – SECOND CODE NO.
(Do not bend the diameter of the next to the “06”) Also, do not connect to the outlet side of the indoor unit.
duct over 90˚) duct to be outlet Depending on the fan strength and static pressure, the unit
might back up.
connected.
• In the case of suburban buildings where windows and road
lighting equipment are close to the air supply opening and
insects tends to swarm around the light, minute insects may
intrude indoors through the air supply opening and air filter.
(Do not reduce the duct In such cases, the use of a high-performance filter (sold sep-
Fig. 15 diameter halfway.) arately) is recommended. However, it may be still difficult to
prevent the intrusion of very minute insects. In that case, con-
• The minimal radius of bends for flexible ducts are as follows. sider ultimate countermeasures, such as a filter box
200-mm duct : 300mm diameter (arranged on site).
250-mm duct : 375mm diameter
• To prevent air leakage, wind aluminum tape round the sec- 9 ELECTRIC WIRING WORK
tion after the duct connecting flange and the duct are con- • Shut off the power before doing any work.
nected. (Refer to Fig. 16) • All field supplied parts and materials, electric works must
conform to local codes.
• To prevent short circuit, install the opening of the indoor air • Use copper wire only.
intake as far as from the opening of the exhaust suction. • All wiring must be performed by an authorized electrician.
• See also the “Electrical Wiring Diagram label” attached to the
• Use the duct applicable to the model of unit used (Refer to electric parts box lid when laying electrical wiring.
the installation drawing.) • Wire the outdoor unit and remote controller as shown in the
• Install the two outdoor ducts with down slope (slope of 1/30 electric wiring diagram label. See the “Remote Controller
or more) to prevent entry of rain water. Also, provide insula- Installation Manual” for details on how to install and lay the
tion for three ducts (Outdoor ducts and Indoor supply air wiring for the remote controller.
duct) to prevent dew condensation. • This system consists of multiple indoor units. Mark each
(Material : Glass wool of 25mm thick) (Refer to Fig. 16) indoor unit as unit A, unit B..., and be sure the terminal board
• If the level of temperature and humidity inside the ceiling wiring to the outdoor unit and BS unit are properly matched.
is always high, install a ventilation equipment inside the If wiring and piping between the outdoor unit and an indoor
ceiling. unit are mismatched, the system may cause a malfunction.
• Install a wiring interrupter or ground-fault circuit interrupter
• Insulate the duct and the wall electrically when a metal duct for the power wiring.
is to be penetrated through the metal lattice and wire lattice • Make sure the ground resistance is no greater than 100:.
or metal lining of a wooden structure wall.
This value can be as high as 500: when using a ground fault
• Using flexible or silent ducts can be effective in reducing the circuit interrupter since the protective ground resistance can
air discharge sound of the supply air to room (SA). Select
materials keeping in mind the fan strength and operating be applied.
sound of the unit. Consult your Daikin dealer for selection. • Do not let the ground wire should come in contact with gas
• Set the pitch between the exhaust air outlet (EA) and the out- pipes, water pipes, lighting rods, or telephone ground wires.
side air intake (OA) to 3 times the duct diameter. • Gas pipes: gas leaks can cause explosions and fire.
• Do not use a bent cap or a round hood as the outdoor hood • Water pipes: cannot be grounded if hard vinyl pipes are used.
if they might get rained on directly. (We recommend using a • Telephone ground and lightning rods: the ground poten-
deep hood (optional accessory).) tial when struck by lightning gets extremely high.
• When using a deep hood, make sure the duct from the deep • Do not turn on the power supply (switch, wiring interrupter or
hood (outer wall) to the unit is at least 1m long. ground fault circuit interrupter) until all other works are done.
VKM50GAMV1,
VKM50GAV1
Follow Sheathed 0.75-1.25
VKM80GAMV1, H05VV-
Duct connecting 15A local wire 2
VKM80GAV1 U3G mm
flange standards (2 wire)
VKM100GAMV1,
Aluminum tape VKM100GAV1
(Locally procured)
Fig. 16
• The change of air discharge grill's location should be exam-
ined when the cold draft from air discharge grill is feared.
The fan is driving while defrost operation, and the cold air is
often blowing.
8 English
3P130768-2H
68 VKM-GA(M) series
ED71-440B Installation
NOTE CAUTION
• If the wiring is in a place where people it can be easily
• See “Electrical Wiring Diagram label” on the backside of the
touched by people, install a leak interrupter to prevent
lid of the electric parts box for electric wiring work.
electric shock. • Be sure to attach the sealing material or putty (locally pro-
• When using a ground-fault circuit interrupter, make sure cured) to hole of wiring to prevent the infiltration of water as
to select one useful also to protection against overcurrent well as any insects and other small creatures from outside.
and short-circuit. Otherwise a short-circuit may occur inside the electric parts
If you use a leak interrupter which is designed for protect- box.
ing again ground faults, be sure to combine it with a wir- • When clamping the wires, be sure no pressure is applied to
ing interrupter or an load switch that has a fuse. the wire connections by using the included clamping material
• The length of the transmission wiring and remote control- to make appropriate clamps. Also, when wiring, make sure
ler wiring are as follows. the lid on the electric parts box fits snugly by arranging the
wires neatly and attaching the electric parts box lid firmly.
Length of outdoor-indoor transmission
When attaching the electric parts box lid, make sure no wires
wiring … max 1000m (total wiring length 2000m)
get caught in the edges. Pass wiring through the wiring
Length of remote controller wiring between indoor through holes to prevent damage to them.
unit and remote controller … max 500m • Make sure the remote controller wiring, the wiring between
the units, and other electrical wiring do not pass through the
ELECTRICAL CHARACTERISTICS same locations outside of the unit, separating them by at least
Units Power supply Fan motor
50mm, otherwise electrical noise (external static) could
cause mistaken operation or breakage.
Model Voltage
Hz Volts MCA MFA kW FLA
range
10. 2 Connecting power supply wiring and ground
VKM50GAMV1,
4.3 15 0.28×2 1.9×2 wiring
VKM50GAV1
Max. • Pass the power supply wiring and the ground wiring through
VKM80GAMV1, 220- 264V
50 4.3 15 0.28×2 1.9×2 the wiring through-hole into the electrical parts box and
VKM80GAV1 240V Min.
198V secure with the included clamping material after connecting
VKM100GAMV1, the wires to terminal blocks. (Refer to Fig. 17-1, 17-2)
4.3 15 0.28×2 1.9×2
VKM100GAV1
〈 VKM-GAMV1 series 〉
MCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A)
Terminal block (X1M) details
kW: Fan Motor Rated Output (kW); FLA: Full Load Amps (A) Grounging terminal
(M4 screws, spring
10 WIRING EXAMPLE AND HOW TO SET washers, cup washers)
THE REMOTE CONTROLLER
1 2 L N
10. 1 OPENING AND SHUTTING THE ELECTRIC Short-circuit wire Resin Clamp parts
PARTS BOX AND CONNECTING THE WIRING Remove when installing
the humidistat Power supply wiring
CAUTION (locally procured). Clamp Ground wiring
Be sure to power off before opening the electric parts box. (accessory) Wiring for the
Fig. 17-1 humidistat
• Remove the electric parts box lid and wire as shown in the
figure below.
〈 VKM-GAV1 series 〉
SS1 is the switch for setting Terminal block (X1M) details
Do not change the switch settings. Grounging terminal
the remote controller.
The unit will not run if the settings (M4 screws, spring
Factroy setting washers, cup washers)
are changed. Space for installation of
NOR.
adapter PC board (KRP2A1) H L N
SS1
M
Space for Resin Clamp parts
A2P installation of
A3P Power supply wiring
adapter PC board
(KRP50-2) Clamp Ground wiring
A1P Fig. 17-2 (accessory)
X3M
Clamp
X1M
(accessory) ¢Precautions when laying power supply wiring²
Resin Clamp parts
[PRECAUTIONS]
Transmission wiring [1] A circuit breaker capable of shutting down power supply to
Electric parts Power supply wiring through-hole the entire system must be installed.
box lid and Ground wiring Power wiring through-hole [2] A single switch can be used to supply power to units on the
same system.
NOTE) A3P: VKM-GAMV1 series only However branch switches, branch overload circuit interrupter
must be selected carefully.
[3] Fit the power supply wiring of each unit with a switch and
fuse as shown in the drawing.
English 9
3P130768-2H
VKM-GA(M) series 69
Installation ED71-440B
COMPLETE SYSTEM EXAMPLE 10. 3 Remote power supply wiring, transmission wir-
ing, computerised control wire
Power supply wiring
Sheathed cable • Pass the remote control wiring, the transmission wiring,
VRV (H05VV-03G) and the computerised control wire into the electric
Power supply Outdoor unit Transmission wiring parts box through the through-hole and connect to the
Sheathed cable terminals on the X3M terminal block. After connection,
secure with the included cramping material.
Switch
(Refer to Fig. 18)
Fuse
Detail of terminal block (X3M)
VRV P1 P2 F1 F2 T1 T2
Indoor unit Heat Reclaim Clamp
REMOTE TRANSMISSION FORCED
Ventilator CONTRL WIRING OFF
(VKM) (accessory)
VRV
Indoor unit Remote controller wiring
Heat Reclaim
Ventilator Transmission wiring
(VKM) Fig. 18
Remote controller
10 English
C: 3P130768-2H
70 VKM-GA(M) series
ED71-440B Installation
¢Combined operation system with VRVII system (connected with Heat Reclaim Ventilators and standard indoor units in a single
refrigerant circuit)²
Outdoor unit
Electric parts box
IN/D OUT/D
F1 F2 F1 F2
Power supply Power supply
220-240V 220-240V
~ ~
50 Hz 50 Hz
Switch Switch Switch
Fuse Fuse Fuse
Transmission wiring
Remote controller
Remote controller wiring
Remote controller
R S P1 P2 F1 F2 T1 T2
Standard indoor
R S P1 P2 F1 F2 T1 T2
Standard indoor L N P1 P2 F1 F2 T1 T2 Heat Reclaim
unit A unit B Ventilator A
(outside air
Earth processing type)
Earth Earth
¢Independent system (connected only with a Heat Reclaim Ventilator in a single refrigerant circuit)²
Outdoor unit
Electric parts box
IN/D OUT/D
F1 F2 F1 F2
Remote controller
R S P1 P2 F1 F2 T1 T2 R S P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2
Heat Reclaim
Standard indoor Standard indoor Ventilator A
Earth unit A unit B (Outside air
processing or
Earth Earth standard type)
NOTE) Standard type ........ VAM series NOTE)
Switch Switch F1 F2 F1 F2
Remote controller F1 F2 F1 F2
wiring
R S N P F1 F2 T1 T2 L N N P F1 F2 T1 T2
Heat Reclaim Ventilator A
Earth Earth
Standard indoor
unit A
English 11
C: 3P130768-2H
VKM-GA(M) series 71
Installation ED71-440B
[PRECAUTIONS] (2) Add remote controller 2 (slave) to the terminal block for
There is not need to set the indoor unit address when using remote controller (P1, P2) in the electric parts box.
group control. (It is automatically set when the power is turned (There is no polarity.)
on. ) However, since the Heat Reclaim Ventilator (outside air P1 P2 F1 F2 T1 T2
processing type) uses two remote control addresses per unit, REMOTE
CONTRL
TRANSMISSION
WIRING
FORCED
OFF
F2 T1 T2
FORCED
OFF
Input A
Insert the screwdriver here and gently work Wire specification Sheathed wire (2 wire)
off the upper part of remote controller. Gauge
2
0.75 - 1.25mm
(2) Turn the MAIN/SUB changeover switch on one of the Length Max. 100m
two remote controller PC boards to “S”. Contact that can ensure the minimum
(Leave the switch of the other remote controller set to “M”.) External terminal
applicable load of 15V DC, 1mA.
• Actuation
S The following table explains FORCED OFF and ON/OFF
(Factory setting) M
OPERATIONS in response to Input A.
Remote controller FORCED OFF ON/OFF OPERATION
PC board
Only one remote controller Input “ON” stops operation (impos- Input OFF oON turns
S
needs to be changed M
sible by remote controllers.) ON unit.
if factory settings have
remained untouched. Input OFF enables control by Input ON oOFF turns
remote controller. OFF unit.
12 English
C: 3P130768-2H
72 VKM-GA(M) series
ED71-440B Installation
P1 P2
Remote controller
• Local wiring
Operation of Heat Terminal for local Capacity of con-
Reclaim Ventilator connection necting terminal (3) UNIT No.
SECOND
CODE NO. Mode No. (3)
FIRST
CODE (6)
NO. SETTING
FIELD
SET MODE (7) (1)
62
English 13
C: 3P130768-2H
VKM-GA(M) series 73
Installation ED71-440B
¢Example² NOTE)
When adjusting the ventilation air flow to low setting in the 1. The inside the frame indicates the second code no.
group setting mode, enter the Mode No., “19” FIRST CODE set when shipped from factory.
NO., “0” and SECOND CODE NO., “01”. 2. The settings are applied to the entire group, but if the mode
no. inside the parentheses is selected, the settings can be
■Settings and setting numbers applied to individual indoor units.
However, it is only possible to check any changes made to
Mode FIRST SECOND CODE NO. the settings inside the parentheses in individual mode. (For
Description of setting No. CODE group batch operation, the changes are made but the dis-
1 NO. 01 02 03 04 05 06 07
play remains as it was when shipped from the factory.)
App- App- 3. Do not set anything not shown above. If the applicable func-
Filter cleaning time No
rox. rox. tions are not available, they will not be displayed.
setting 0 coun- – – – –
2500 1250 4. When returning to normal mode, the remote controller is ini-
NOTE) 5 ting
hours hours tialized, so the display might show “88.”
Nighttime free cooling 5. When “Filter cleaning time setting” or “Nighttime free cooling
operation setting 2 4 6 8 operation setting” is changed, explain set contents to the
(Time after air condi- 1 OFF hours hours hours hours – – customer.
tioning is stopped.) later later later later 6. See below for details on the settings for cold areas.
NOTE) 5 – : operate at the set fan strength
Fan speed initial Nor- Ultra Air conditioner fan 01 02 04 06
4 – – – – –
setting 17 mal high
Heating thermo off Operation – – L L
(27) Not Not
Defrost Stop – Stop Stop Stop
direct With direct With
Direct duct connec- duct direct duct direct Oil return Stop – Stop Stop Stop
tion with VRV 5 (Air duct – (Air – duct – In case of Independent operation
setting flow (fan flow (fan
set- off) set- off) Air conditioner fan 01 02 04 06
ting) ting) Heating thermo off Operation – – L L
Setting for cold areas Air Air Defrost Stop – – Stop Stop
(Fan operation selec- flow flow Fan Fan
5 – – – Oil return Stop – – Stop Stop
tion for heater thermo set- set- L L
OFF) NOTE) 6 ting ting – : operate at the set fan strength
Ventilation air flow L : operate at the weak fan strength
Ult-
setting when 17 S : Stop
6 High ra- – – – – –
Nighttime free cooling (27)
High Defrost operation
setting
• In heating operation, freezing of the outdoor unit’s coil
ON/OFF input from increases.
ON/
Outside For- Heating capability decreases and the system goes into
12 OFF
(Set when ON/OFF is 1 ced – – – – – defrost operation.
(22) con-
to be controlled from off • The remote controller will read “ ” until the hot air starts
trol
outside) blowing.
No • It returns to the heating operation again after 6 to 8 minutes
Power faillure Equ- (10 at the longest).
12 equ-
automatic reset 5 ipp- – – – – – • During defrost operation, the fans of the unit continues driv-
(22) ipp-
(Auto Restart) ed ing (factory setting).
ed
Humidification on/off The purpose of this is to maintain the amount of ventilation
15 and humidifying.
when heating thermo 1 No Yes – – – – –
(25) • The change of air discharge grill’s location should be exam-
is off
ined when the cold draft from air discharge grill is feared.
No • Though the fan can be stopped by the setting of remote
Indication of Indi-
Indi- controller.
ventilation mode/Not 4 cat- – – – – –
cat- Do not stop the fan in the place where no ventilation by stop-
indication ion
ion ping the fan may cause the influence of diffusion of air which
No it is dirty and moisture into another room, or the inflow from
Fresh up air supply/ Indication
7 Indication – – – outside the room.
exhaust setting (outflow such as viruses from the sickroom, or smell leakage
18 Supply Exhaust Supply Exhaust
from the rest room, etc.)
External input termi- (28)
Air flow 7. See below for details on the external input terminal function.
nal function selection Fresh- Overall
8 – – – incre- –
(between J1 and JC) up alarm SECOND
ase Input Fan Operation
NOTE) 7 CODE
KRP50-2 output contact operation lamp
Fan Abno- NO.
switching selection 9 – – – – – 01 a Operation On Fresh-up operation
on/off rmal
(between 1 and 3)
Malfunction code “60”
Ventilation air flow 02 a Operation On
0 Low Low Low Low High High is displayed
setting 19
(29) Fan strength up (Low to High,
Ventilation mode Auto- Ex- By- 06 a Operation On
2 High to Ultra-High)
setting matic change pass
Fresh-up operation 1A Off On – – – – –
SECOND CODE NO. “04” does not function when in air condi-
tioner linked mode.
Forced fan on 43
Unit no. allocation 45
14 English
3P130768-2H
74 VKM-GA(M) series
ED71-440B Installation
English 15
C: 3P130768-2H
VKM-GA(M) series 75
Outdoor Air Processing of Ceiling Mounted Duct Connection Type ED71-440B
Switching of
Ventilation mode operation mode
Ventilation
amount
Ceiling mounted Corresponding Ability to process outdoor air (kW) Ability to calculate Diameter of
connectable
duct connection type HP Cooling Heating capacity (kW) connection pipe
RXYQ10PAY1
[Features of VKM-GA(M)]
Because VKM-GA(M) model is equipped with a heat exchanger unit, a PCB (corresponding VRV PCB) for
controlling the heat exchanger has been built-in in addition to a PCB for ventilation. These two PCBs are
connected via remote controller line (P1, P2) to perform an interlocked control. Its control system provides
the same condition when 1 ventilation and 1 VRV have been remotely controlled. No air-conditioning
(temperature controlling) function has been equipped. Therefore, it is necessary to prepare separately an
indoor unit for air-conditioning purpose.
Element of Heat
total heat exchanger
exchanger unit
Corresponding
PCB for ventilation VRV PCB Equivalent
P1, P2 P1, P2
BRC1C62
remote controller An image sketch of VKM-GA(M) A group of 1 ventilation/1 VRV indoor unit
for air-conditioner
76 VKM-GA(M) series
ED71-440B Outdoor Air Processing of Ceiling Mounted Duct Connection Type
Note: 1. JC/J2 of ventilation PCB cannot be used. (Because only the ventilation PCB makes a start/stop, no
synchronized movement with the corresponding VRV PCB is assured.)
Connection to central P1
line is prohibited. P2
Remote controller
for air-conditioner
• In case of a central control, operation ON/OFF can be done separately by each zone. (In this case, zone
interlocked setting must be kept as the factory setting (17. 08. 01).)
VKM-GA(M) series 77
Outdoor Air Processing of Ceiling Mounted Duct Connection Type ED71-440B
• Structure without a remote controller cannot be accepted because the remote controller group is
controlled within a VKM-GA(M) model. (intelligent Touch Controller, central control controller)
Zone interlock setting: None Group interlock zone setting: None Without a remote controller
* Alteration of set temperature and independent ventilation operation cannot be performed from a central device.
17.4.2 Caution When Connecting with a VRVIII System, Heat Recovery Type
When bringing the RA (exhaust gas intake) of this unit directly in from the ceiling, connect to a BS unit
identical to the VRV indoor unit (master unit), and use group-linked operation.
SA
• The system must be operated interlocking
with the air conditioner.
CAUTION
If above setting is not made, the detection of correct temperature is not available and automatic judgment
on proper cooling or heating cannot be made when the temperature in the ceiling gets higher than indoor
temperature.
Poor heating or shortage of the amount of humidification may result.
If the indoor unit and this unit are installed with different BS system inevitably, always take following
remedies (1) and (2).
(1) RA (Exhaust and suction) of this unit is not taken directly from inside of the ceiling, connect the suction
duct and suction grille to the fitting port of RA duct to suck the indoor air.
SA Suction
grille
RA
(2) Do not make the selection of heating or cooling in automatic mode and it shall be made by manual
selection from remote controller or centralized controller.
78 VKM-GA(M) series
ED71-440B Outdoor Air Processing of Ceiling Mounted Duct Connection Type
17.4.3 Caution when Connecting the Indoor Unit Directly to the Duct
Follow the indications described below
a) When connecting the indoor unit directly to the duct, always use the same system on the indoor unit as
with the outdoor unit, perform group-linked operation, and make the direct duct connection settings from
the remote controller. (Mode No. “17 (27)” – First code No. “5” – Second code No. “6”.) Refer to
“16. Installation” concerning setting method.
EA
OA
SA Suction
grille
RA
b) Do not connect to the outlet side of the indoor unit. Depending on the fan strength and static pressure,
the unit might back up.
c) When it is connected to the suction side of indoor unit as a direct duct connection system, etc., since
there is a possibility that the body thermo of the indoor unit detects erroneously SA discharge from this
unit as indoor air, use the remote sensor (Optional).
Divert the module of indoor unit Divert the module of total heat exchanger
RA OA
DX-Coil R2T
Thermistor for
R3T outdoor air
SA EA
VKM-GA(M) series 79
Appendix ED71-440B
18. Appendix
18.1 Purpose of Ventilation
Living environment, and working environment as well, can be polluted for various reasons, which in turn will
lead to hygienic problems and/or lower productivity. To avoid this, the polluted air must be replaced with
fresh air. This operation is called ventilation.
To apply ventilation for removing pollution, it is necessary to identify the causes of air pollution before
studying corrective measures.
18.1.1 Air Pollution
Dust
There are about 7,500 ~ 22,000 dust particles in the air of one liter. However, if you feel dusty, the number
may have reached as many as 100 ~ 200 thousand. We are unknowingly inhaling such polluted air, which
enters into our trachea and lungs, leading to coughs and difficulty in breathing, some malignant disease
and/or nausea, and in worse cases, other serious chronic diseases such as bronchitis and
pneumoconiosis.
Table 1 Suspended Dust in the Air
Type of dust Content (weight %)
Smoke, pollen, fly ash 0~20%
Ore chips, cinders 10~90%
Rotten plant 0~10%
Vegetable fiber 5~40%
Carbon, fume 0 ~ 40%
Bacteria
Suspended particles of bacteria of 0.2~5μ in diameter are likely being adhered with dust in the air, not
independently suspended. According to NASA (the National Aeronautics and Space Administration), the
more number of dust particles may allow the more number of bacteria to exist, which may justify the
abovementioned theory of bacteria's presence in the form of adherence to dust. Therefore, it is possible to
remove bacteria using an electrostatic precipitator, though the result of cleaning cannot be easily
measured. It takes time to demonstrate how effectively bacteria could be removed. According to our
experiments that measured the number of bacteria using the settle plate microbe count method, the
number of bacteria in the space above the dust collector electrode is smaller than that collected on a plate
of the same area being left in the air. This indicates that electrostatic precipitators can, to some extent, kill
bacteria collected on the electrode.
Table 2 Particle diameter of dust
Atmospheric dust
Fume Dust
Fog Rain
Virus/protein Road sand
Bacteria and dust
Particle soil
Pollen
#8 powder
Prefilter
Medium-/high-performance filter
HEP filter
80 VKM-GA(M) series
ED71-440B Appendix
Tobacco
Only one cigarette can soon pollute the air in the enclosed room. And both the smoker and other non-
smokers staying here are affected. Especially the “secondhand” smoke from the tip of cigarette contains
2~3 times larger amount of harmful substances (nicotine and tar) than the “main smoke” exhaled by the
smoker, so that the non-smokers around the smoker can be affected by tobacco smoke.
So, tobacco smoke is one of the serious causes of interior air pollution. Tobacco smoke consists mainly of
mists such as tar and nicotine, gases such as carbon monoxide (CO), carbon dioxide (CO2), hydrogen and
various hydrocarbons including methane, and traces of hydrogen cyanide, formaldehyde, acrolein,
ammonia and nitrogen oxides (NOx), so that various human health problems including lung cancer, chronic
CO toxication and bronchitis can occur.
New ceilings, walls, furniture and decorations in white will turn into yellow in one or two years. This is due to
the nicotine and tar contained in tobacco smoke, and/or dust in the air.
To allow smoking, proper ventilation is inevitable. A ventilation system consisting of an air cleaner and
ventilator that operates automatically detecting the level of pollution is recommendable. This system can be
associated with an air conditioning system, so that power consumption for these systems can be reduced,
and so that they can enjoy comfortable smoking without feeling hot or cold.
Table 3 Sensation for Tobacco Smoke
Smoke concentration
(mg/m3) Status of the air in the room Sensation
Table 4 Air Pollutants per Cigarette (when smoking) Fig 1 Three-Year-Old Child Asthmatic
Type NOx (cc) CO (cc) DUST (mg) Bronchitis Due to Passive Smoking
0.90 72 12.6 5
Asthmatic Bronchitis (%)
VKM-GA(M) series 81
Appendix ED71-440B
0.020
0.015
0.010
Smaller
combustion rate
0.005
Larger
combustion rate
18 19 20 21
Oxygen concentration (%)
<CO safety limit is 10 ppm with max. 5 ppm recommended>
82 VKM-GA(M) series
ED71-440B Appendix
8 10-minute breathing will result in serious difficulty in breathing, hectic cheeks and
headache; O2 starvation will enhance the possibility of this disorder
18 and larger Lethal
Nitrogen oxides
Nitrogen oxides (NOx) include NO, NO2, NO3, N2O, N2O3 and N2O4. Of these, NO and NO2 are harmful
and account for large portions of NOx compounds. NO2 (nitrogen dioxide) can easily reach the deepest
part of the lung, and adversely affect it and other organs. In terms of long-term adverse effect, NOx is
stronger than sulfurous acid gases. Dusts can enhance the adverse effect of NOx gases.
NO (nitrogen monoxide) is also harmful, though its chronic effect is yet to be clarified.
Oxygen starvation
About 21% of O2 concentration is normal for human body. Lower O2 concentration will cause difficulty in
breathing with other various symptoms. O2 concentration of 8% or lower will have a fatal effect. Higher O2
concentration will cause our pulse rate to increase, which leads to larger burdens on the heart. Abnormally
higher O2 concentrations invite another danger: higher ignition possibilities. Therefore, artificial oxygen
supplies should be avoided. The most effective way for avoiding oxygen starvation is to supply natural air
that contains oxygen concentrations appropriate for human life.
VKM-GA(M) series 83
Appendix ED71-440B
Humidity
Humidity has a close relationship with our living environment. Humidity is an additional parameter to be
controlled by air conditioning systems. It may give persons a feel of mild air, if the temperature is relevant
for the humidity. Imbalance between the temperature and humidity (especially higher humidity) leads to
discomfort. A term that is frequently used in summer, “discomfort index,” indicates this imbalance between
temperature and humidity. Higher humidity causes buildings and furniture to rot. Lower humidity causes our
skins to dry and buildings and furniture to crack or warp. Another point for controlling humidity is to avoid
mold, ticks and termites. To satisfy all of these requirements, two types of ventilation must be used in a well
controlled, combined manner. One is to maintain the humidity for our living comfort, and the other one is to
remove humidity where dryness is required to prevent such mold and small animals.
<Relative humidity recommended = 30~70%>
Positive Negative
pressure
pressure
Exhaust opening Room
Room Ventilation fan Room Ventilation fan
84 VKM-GA(M) series
ED71-440B Appendix
<Mechanical ventilation>
Whole ventilation
This is to replace all air in the room with fresh air. This
Exhaust
system is effective for rooms in which there is a source of
smoke, steam or odor.
Dirty air
Supply
Local ventilation
This is to replace air in a limited area where the air is polluted. This is
effective for cases where the source of pollution is stationary and
Supply
concentrated. Combined use with a hood is effective for removing Cooking range
highly contaminated air. hood fan
Cooking range
<Important supply flow>
To ensure effective ventilation, sufficient air intakes should be provided.
To ensure stable ventilation, the same amount of fresh air as exhausted should be supplied.
Size and location of air intakes
1. Size
Mechanical ventilation fan rated capacities indicated on a catalogue can be used on condition that the
same amount of air is fed into the room through the air intakes. Smaller air intakes will reduce the
capability of the ventilation fan. Generally, the air intakes should be larger than the ventilation fan
opening. Larger air intakes can reduce the air velocity from the intake, so that persons, when standing
near the intake, do not feel discomfort.
Air intake
Good example
Dispersed location of
ventilation fans Air intake
Good example
VKM-GA(M) series 85
Appendix ED71-440B
Quantity
Air flow is the amount of air that a ventilation fan exhausts (or supplies) per unit time, generally expressed
in m3/h or m3/min.
Pressure
This is a wind pressure expressed in the unit of Pa. Three types of wind pressure are used.
• Dynamic pressure
This is a pressure produced by wind velocity, also called “velocity pressure.” Deflection of a window
glass by strong wind during typhoon is due to this dynamic pressure.
• Static pressure
When a balloon has been inflated, there is a pressure in the balloon that presses against the
membrane of the balloon. Static pressure is produced also when the air is still.
• Total pressure
This is the sum of wind’s dynamic pressure and static pressure.
Stream
Fan
Ps Pv Pt
Water column
manometer
(Static pressure) (Dynamic pressure) (Total pressure)
“Static pressure (Ps)” is a pressure needed for overcoming the resistance of the duct when conveying air.
“Dynamic pressure (Pv)”, on the contrary, is a pressure due to air stream. To determine air velocity,
measure the dynamic pressure of the air.
The “total pressure (Pt)” is the sum of static pressure and dynamic pressure.
2
V γ
Pt = Ps + Pv = Ps +
2 V: velocity (m/sec)
γ: Air density (kg/m3)
86 VKM-GA(M) series
ED71-440B Appendix
Impeller
Axial direction
Impeller
Motor
<Features> <Features>
• Air flow is larger than sirocco or turbo fans, but • Static pressure is higher but the air flow is
the static pressure is lower. smaller than propeller fans.
<Installation> <Installation>
• Residential housing, external wall mount • Housing complex
<Applications> • Ducted ventilation system
• General ventilator <Applications>
• Window-mount ventilator • Air conditioning system ventilator
• Living room ventilator • Cooking range hood, deep
• Intermediate ventilator, ducted system
• Sirocco fan
Impeller characteristics as an essential parameter for type selection
Propeller fans have a smaller pressure rating, which means that the air flow is reduced significantly by
adverse wind. The next table shows the airflow vs. pressure characteristics that differ between propeller
and sirocco fans. Depending on the topography, altitude and/or other conditions, as a general guide,
propeller fans can be used at a height corresponding to the second floor of the building, and other types of
fans having a higher pressure rating should be used at higher locations.
* Even for independent houses, to ventilate a room that does not share any external walls, or if the house
is located in a windy place, use a pressure type fan.
Wind velocity vs. wind pressure, and ventilator capacity reduction due to wind pressures
(air flow: for 50 Hz only)
External Change in fan capacity due to
Wind pressure
air velocity (Pa) Propeller fan Sirocco fan wind pressures
(Vm/sec)
0 0 924m3/h 432m3/h
3 3.9 810 420 Sirocco
fan
Wind
5 10.8 612 408 velocity
Propeller
7 20.6 294 Reverse flow 390 fan
10 43.1 Reverse flow 360
15 96.0 Reverse flow 264
VKM-GA(M) series 87
Appendix ED71-440B
Other noise
• Echoes
Depending on the type or material of the wall and ceilings of the room, and in small room, echoes occur.
• Vibration
Vibrating objects produce vibrating sound by moving their surrounding air. 20Hz or higher frequency
sounds are audible.
• Noise due to duct’s resistance
Higher static pressures acting on the fan will produce larger sounds.
88 VKM-GA(M) series
ED71-440B Appendix
Calculate air flow based on the room capacity (number of persons to be admitted)
Required air flow (m3/h) = Required air flow per person (m3/h) × Number of persons
VKM-GA(M) series 89
Appendix ED71-440B
Calculate air flow based on the required air flow per floor area
Required air flow (m3/h)
= Required air flow per floor area (m3/m2 · h) × Floor area (m2)
Positive Negative
pressure
pressure
Kinds of ventilation Exhaust opening
Room Ventilation fan Room Room Ventilation fan
<Example>
100 × 0.030
Q= = 25m3/h · person
0.15 – 0.03
90 VKM-GA(M) series
ED71-440B Appendix
For example, to keep the odor level not greater than 2, the contamination concentration (tobacco
combustion amount (mg)/ventilation amount (m3)) should be reduced to 35.3 mg/m3 or smaller. To keep
the odor level not greater than 1, the contamination concentration should be reduced to 17.7 mg/m3 or
smaller. To calculate required air flow based on smoking concentration, use the following equation.
<Example>
Assumptions: Combustion per cigarette 1,000 mg
Combustion rate 70%
Number of cigarettes per person 4/h · person
Odor intensity level 2 (=35.5 mg/m3)
1,000 × 0.7 × 4
Q= = 79.3m3/h · person
35.3
Therefore, under the conditions given above, in the case of cleaning air using ventilation only, about 80 m3/
h · person of air flow is required. By using air cleaners and/or deodorizers in conjunction with the ventilation
system, its capacity can be reduced significantly.
Required air flow depending on the degree of smoking (estimated)
Required air flow (m3/h · person), Smoking amount (number
Degree of smoking Locations
minimum to recommended value of cigarettes/hour/person)
Dealer office, newspaper 3~5.1
Very high editing room, meeting room 51~85 (1.5~2.5)
VKM-GA(M) series 91
Appendix ED71-440B
18.3.1 Procedure for Calculating Pressure Drops and Finally Determining the Type of Ventilators
Calculation of required air flow
P = 0.01 ×
1.2
2
×
L
d
Q
× 2 ×
d
4
3,600π
{ }
Friction coefficient of major duct types
Duct material λ
Aluminum flexible duct 0.03~0.04
Vinyl chloride pipe 0.01~0.02
Galvanized steel pipe 0.016~0.025
92 VKM-GA(M) series
ED71-440B Appendix
v=
12
50
0
Air flow Q [m3/h]
.0m
10 0
40
20000 9
/s
.0
80
30
70
.0
20
10000 60 m
0c
.0
8000
15
r5
ete
.0
6000
Ve
i am 45
D
loc
4000 40
ity
=(m
35 25
/s)
30
2000
9.0
8.0
7.0
6.0
20
5.0
1000
800 4.0 18
600 16
3.0
14
400
2.0 8
12
1.
1.6
1.4
10
1.2
200 9
1.0
6
8
5
7 d=
100
0.9
6
0.8
80
0.7
5
0.6
60
4.5
40 4
3
0.5
3.5
20
2.5
2
10
0.04 0.1 0.2 0.4 1.0 2.0 6.0 10 20 40 60 80
]
m
[c
Ve
15
loc
d=
ity
ν
[m
/s
]
A
300
B
0 2.2 Friction loss factor γ [Pa/m]
1. Find the intersection
of the duct diameter d (15 cm) and air flow Q (300
m3/h) => Point A
2. Draw a vertical line through Point A until it intersects
with the abscissa => Point B
3. Read the Point B (2.2 Pa/m for this case). Multiply
the value by the duct length. The answer is 11 Pa.
VKM-GA(M) series 93
Appendix ED71-440B
Long side
E
di qui
am va
et len
er t
Short side
90
De
40
Short side
V2
ΔP (Pa) = ζ · γ = ζ · Pv
2
Where ζ: Local loss coefficient
v: Air velocity...................................[m/s]
* This is the velocity measured at the upstream side of the feature except junctions.
Pv: Dynamic pressure.....................[Pa]
R
[Conditions] = 1.5 v = 5.0 [m/s]
d
ζ = 0.24
V2 25
Pv = γ = × 1.2
2 2
Pv = 15 [Pa]
94 VKM-GA(M) series
ED71-440B Appendix
d
2 Straight bend, round duct – – 1.30
0.5 1.25
0.75 0.60
0.25 1.0 0.37
1.5 0.19
0.5 1.10
0.75 0.50
0.5 1.0 0.28
W 1.5 0.13
3 R bend, rectangular duct
R
0.5 1.00
H
0.75 0.41
1.0
1.0 0.22
1.5 0.09
0.5 0.96
0.75 0.37
4.0
1.0 0.19
1.5 0.07
0.25 1.25
W 0.5 1.47
4 Straight bend, rectangular duct –
H 1.0 1.50
4.0 1.38
20° 0.02
40° 0.03
5 Pipe inlet (with round hood) θ V θ 60° 0.05
90° 0.11
120° 0.20
20° 0.13
40° 0.08
6 Pipe inlet θ V θ 60° 0.12
(with rectangular hood)
90° 0.19
120° 0.27
(Example)
V VI
IV
III
Ventilating fan intended for 5m External hood
use with a ducted system 0.5m 0.5m (equivalent straight pipe length 9m)
Duct diameter φ100
Material: galvanized
steel pipe
I II
(For galvanized steel pipe with λ = 0.02, approximate value)
VKM-GA(M) series 95
Appendix ED71-440B
50Hz
60Hz
19m
Pipe resistance curve
25 20
100
15m
(Pa)
10m
50
A
5m
0
50 100 B 150 200
Air flow (m3/h)
Inspection port
(450 x 450 or larger)
Auxiliary grille
Inspection port
96 VKM-GA(M) series
ED71-440B Appendix
Fan Bellows
Fan
Avoid deformation
Deformed flexible duct may not permit the shutter to open completely.
• Depending on the room structure, the noise may increase by 8 to 10 phons due to echoes and/or other
factors.
• To avoid entry of rainwater, exhaust ducts extending outside should be inclined down by 1/100 or larger.
• To use a two-room ventilating fan for a bathroom and other room, install the fan in the bathroom. Two-
room ventilating fans are designed so that the air flow through the main opening on the fan is about twice
larger than that through the sub opening (for cases where the distance between the main and sub
openings is about 1 m). However, this air flow proportion can be adjusted by moving the air flow
adjusting plate located on the grille of the main unit.
• Components that constitute the ceiling should be strong enough to prevent vibration and sympathetic
sounds.
Recommended material: gypsum board, cement excelsior board, fiber board
• Exhaust duct ends should be fitted with a vent cap or weather cover to prevent rainwater entry and bird
nesting.
• In cold weather areas, the ducts should be thermal-insulated.
• Local rules and regulations may have special requirements for fire dampers and bellows. For details,
consult the authorities.
• For bathrooms, use ventilating fans specially designed for bathroom use. Never fail to earth the fan.
• Electric wiring should be done by a qualified electrician (electric engineering firm). High-voltage
connections are dangerous.
VKM-GA(M) series 97
Appendix ED71-440B
Velocity
Area
Weight
98 VKM-GA(M) series
ED71-440B Appendix
Length
Flow rate
Note: 0.041=0.00001
VKM-GA(M) series 99
Appendix ED71-440B
m in ft km
dm
Length m 1 39.37 3.281 cm
0.0254 1 0.0833 mm
0.3048 12.00 1 m
m2 in2 ft2 km2
dm2
Area m2 1 1550.0 10.76 cm
2
2
0.000652 1 0.006944 mm
0.09290 144.0 1
m
3
in3 ft3 dm3
cm3 =m3
3 1 61020 35.31 3 =10–3m3
Volume m mm
1.639×10–5 1 5.787×10–4 =10–4m3
–5 3
0.02832 1728 1 =10 m
kg lb Mg
g
Mass kg 1 2.205 mg
0.4536 1
K ºF
K (ºC)
Temperature (Kelvin) 1 0.5555
(Celsius) 1.8 1
N kgf lb MN
Force N kN
1 0.102 0.245 mN IN=1kg×1m/s2
(weight) (Newton) 9.807 1 2.205 N
4.448 0.4536 1
Pa kgf/cm2 lb/in2 (psi) GPa MPa
kPa hPa 2
Pa 1 1.02×10 –5
1.45×10–4 mPA Pa Pa=N/m
Pressure hPa=mmbar
(Pascal) 9.807×104 1 14.22
3
6.895×10 0.07031 1
J kcal BTU
J TJ
Work 1 2.39×10–4 9.478×10–4 GJ
(Joule) 4186.05 1 3.968 MJ
1055.1 0.252 1 kJ
18.6 Refrigerant
Fluorocarbon and global environment
Influence of refrigerant given on global environment
Intrusion of harmful
ultraviolet rays
Fluorocarbon Troposphere
Earth's surface
Chlorine is discharged.
2. Global warming
(Principle)
Due to the results of human activities such as a large
quantity of consumption of petrochemical fuels (e.g.
petroleum, coal, and natural gas) and forest
destruction, carbon dioxide, chlorofluorocarbon,
methane, and others in the atmosphere have been
increasing beyond the limit that natural force can
remove them.
As a result, the dissipation of heat from Earth's surface
is interrupted (greenhouse effect), thus resulting in
global warming.
Infrared rays
Earth
Atmosphere
Temperature (˚C)
–51.58 101.32 101.17 1354.0 4.153 1.386 0.745 126.3 401.1 0.769 2.009
–50 109.69 109.51 1349.0 4.474 1.388 0.750 128.5 402.0 0.779 2.004
–48 121.07 120.85 1342.7 4.909 1.391 0.756 131.2 403.1 0.791 1.998
–46 133.36 133.11 1336.3 5.377 1.394 0.763 134.0 404.1 0.803 1.992
–44 146.61 146.32 1330.0 5.880 1.397 0.770 136.8 405.2 0.816 1.987
–42 160.89 160.55 1323.5 6.419 1.401 0.777 139.6 406.2 0.828 1.981
–40 176.24 175.85 1317.0 6.996 1.405 0.785 142.4 407.3 0.840 1.976
–38 192.71 192.27 1310.5 7.614 1.409 0.792 145.3 408.3 0.852 1.970
–36 210.37 209.86 1304.0 8.275 1.414 0.800 148.1 409.3 0.864 1.965
–34 229.26 228.69 1297.3 8.980 1.419 0.809 150.9 410.2 0.875 1.960
–32 249.46 248.81 1290.6 9.732 1.424 0.817 153.8 411.2 0.887 1.955
–30 271.01 270.28 1283.9 10.53 1.430 0.826 156.6 412.1 0.899 1.950
–28 293.99 293.16 1277.1 11.39 1.436 0.835 159.5 413.1 0.911 1.946
–26 318.44 317.52 1270.2 12.29 1.442 0.844 162.4 414.0 0.922 1.941
–24 344.44 343.41 1263.3 13.26 1.448 0.854 165.3 414.9 0.934 1.936
–22 372.05 370.90 1256.3 14.28 1.455 0.864 168.2 415.7 0.945 1.932
–20 401.34 400.06 1249.2 15.37 1.461 0.875 171.1 416.6 0.957 1.927
–18 432.36 430.95 1242.0 16.52 1.468 0.886 174.1 417.4 0.968 1.923
–16 465.20 463.64 1234.8 17.74 1.476 0.897 177.0 418.2 0.980 1.919
–14 499.91 498.20 1227.5 19.04 1.483 0.909 180.0 419.0 0.991 1.914
–12 536.58 534.69 1220.0 20.41 1.491 0.921 182.9 419.8 1.003 1.910
–10 575.26 573.20 1212.5 21.86 1.499 0.933 185.9 420.5 1.014 1.906
–8 616.03 613.78 1204.9 23.39 1.507 0.947 189.0 421.2 1.025 1.902
–6 658.97 656.52 1197.2 25.01 1.516 0.960 192.0 421.9 1.036 1.898
–4 704.15 701.49 1189.4 26.72 1.524 0.975 195.0 422.6 1.048 1.894
–2 751.64 748.76 1181.4 28.53 1.533 0.990 198.1 423.2 1.059 1.890
0 801.52 798.41 1173.4 30.44 1.543 1.005 201.2 423.8 1.070 1.886
2 853.87 850.52 1165.3 32.46 1.552 1.022 204.3 424.4 1.081 1.882
4 908.77 905.16 1157.0 34.59 1.563 1.039 207.4 424.9 1.092 1.878
6 966.29 962.42 1148.6 36.83 1.573 1.057 210.5 425.5 1.103 1.874
8 1026.5 1022.4 1140.0 39.21 1.584 1.076 213.7 425.9 1.114 1.870
10 1089.5 1085.1 1131.3 41.71 1.596 1.096 216.8 426.4 1.125 1.866
12 1155.4 1150.7 1122.5 44.35 1.608 1.117 220.0 426.8 1.136 1.862
14 1224.3 1219.2 1113.5 47.14 1.621 1.139 223.2 427.2 1.147 1.859
16 1296.2 1290.8 1104.4 50.09 1.635 1.163 226.5 427.5 1.158 1.855
18 1371.2 1365.5 1095.1 53.20 1.650 1.188 229.7 427.8 1.169 1.851
20 1449.4 1443.4 1085.6 56.48 1.666 1.215 233.0 428.1 1.180 1.847
22 1530.9 1524.6 1075.9 59.96 1.683 1.243 236.4 428.3 1.191 1.843
24 1615.8 1609.2 1066.0 63.63 1.701 1.273 239.7 428.4 1.202 1.839
26 1704.2 1697.2 1055.9 67.51 1.721 1.306 243.1 428.6 1.214 1.834
28 1796.2 1788.9 1045.5 71.62 1.743 1.341 246.5 428.6 1.225 1.830
30 1891.9 1884.2 1034.9 75.97 1.767 1.379 249.9 428.6 1.236 1.826
32 1991.3 1983.2 1024.1 80.58 1.793 1.420 253.4 428.6 1.247 1.822
34 2094.5 2086.2 1012.9 85.48 1.822 1.465 256.9 428.4 1.258 1.817
36 2201.7 2193.1 1001.4 90.68 1.855 1.514 260.5 428.3 1.269 1.813
38 2313.0 2304.0 989.5 96.22 1.891 1.569 264.1 428.0 1.281 1.808
40 2428.4 2419.2 977.3 102.1 1.932 1.629 267.8 427.7 1.292 1.803
42 2548.1 2538.6 964.6 108.4 1.979 1.696 271.5 427.2 1.303 1.798
44 2672.2 2662.4 951.4 115.2 2.033 1.771 275.3 426.7 1.315 1.793
46 2800.7 2790.7 937.7 122.4 2.095 1.857 279.2 426.1 1.327 1.788
48 2933.7 2923.6 923.3 130.2 2.168 1.955 283.2 425.4 1.339 1.782
50 3071.5 3061.2 908.2 138.6 2.256 2.069 287.3 424.5 1.351 1.776
52 3214.0 3203.6 892.2 147.7 2.362 2.203 291.5 423.5 1.363 1.770
54 3361.4 3351.0 875.1 157.6 2.493 2.363 295.8 422.4 1.376 1.764
56 3513.8 3503.5 856.8 168.4 2.661 2.557 300.3 421.0 1.389 1.757
58 3671.3 3661.2 836.9 180.4 2.883 2.799 305.0 419.4 1.403 1.749
60 3834.1 3824.2 814.9 193.7 3.191 3.106 310.0 417.6 1.417 1.741
62 4002.1 3992.7 790.1 208.6 3.650 3.511 315.3 415.5 1.433 1.732
64 4175.7 4166.8 761.0 225.6 4.415 4.064 321.2 413.0 1.450 1.722
(Z0169)
Pressure-enthalpy curves of HFC32/125 ( 50 / 50 wt% )
VKM-GA(M) series
ED71-440B
18.7
ED71-440B
VKM-GA(M) series
Moist Air h-x Chart [SI]
Pressure: 101.325kPa,
En
Temperature: -10 to +50˚C
t
u = halpy
dh/ -hum
dx
Psychrometric Chart
[kJ idity r
/kg atio ]
] )
( DA
g
/k
kJ
h[
lpy
ha
nt
]
e
c
ϕ[%
ifi
ty
ec
m idi
Sp
hu
t ive
Rela
Sensible heat factor
Wet
-bul
b tem
pera
ture
t' [˚C
]
Water
Ice
109
Daikin products are manufactured for export to numerous countries throughout the world. Prior to
purchase, please confirm with your local authorised importer, distributor and/or retailer whether this
product conforms to the applicable standards, and is suitable for use, in the region where the product
will be used. This statement does not purport to exclude, restrict or modify the application of any local
legislation.
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global_ac/
c All rights reserved
Specifications, designs and other content appearing in this brochure are current as of March 2012 but subject to change without notice.
ED71-440B
03/12 FS.K