WEG CFW300 Programming Manual 10007849716 en
WEG CFW300 Programming Manual 10007849716 en
WEG CFW300 Programming Manual 10007849716 en
Frequency Inverter
CFW300 V3.1X
Programming Manual
Programming Manual
Series: CFW300
Language: English
Document: 10007849716 / 03
Build: 940
5 HMI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.1 ACCESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.2 INDICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
9 I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
9.1 ANALOG INPUTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
9.2 EXTERNAL TEMP. SENSOR INPUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-5
9.3 SIGNAL POTENTIOMETER INPUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-5
9.4 ANALOG OUTPUTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-6
9.5 FREQUENCY INPUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-10
9.6 DIGITAL INPUTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-12
9.7 INPUT FOR INFRARED RECEIVER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-20
9.8 ENCODER INPUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-20
9.9 DIGITAL OUTPUTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-22
11 READ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-1
12 COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-1
12.1 COMMANDS AND COMMUNICATION STATUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-1
12.2 SERIAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-2
12.3 BLUETOOTH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-3
12.4 BACNET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-4
12.5 CANOPEN AND DEVICENET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-5
12.6 PROFIBUS DP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-8
12.7 ETHERNET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-9
13 SOFTPLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1
13.1 COMMAND AND STATUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1
13.2 USER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-2
14 APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-1
14.1 PID CONTROLLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-1
14.1.1 Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-3
14.1.2 Academic PID Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-5
14.1.3 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-5
14.1.4 Sleep Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14-14
CFW300 | 0-1
QUICK REFERENCE OF PARAMETERS
0-2 | CFW300
QUICK REFERENCE OF PARAMETERS
CFW300 | 0-3
QUICK REFERENCE OF PARAMETERS
0-4 | CFW300
QUICK REFERENCE OF PARAMETERS
CFW300 | 0-5
QUICK REFERENCE OF PARAMETERS
0-6 | CFW300
QUICK REFERENCE OF PARAMETERS
CFW300 | 0-7
QUICK REFERENCE OF PARAMETERS
0-8 | CFW300
QUICK REFERENCE OF PARAMETERS
CFW300 | 0-9
QUICK REFERENCE OF PARAMETERS
0-10 | CFW300
QUICK REFERENCE OF PARAMETERS
CFW300 | 0-11
QUICK REFERENCE OF PARAMETERS
0-12 | CFW300
QUICK REFERENCE OF PARAMETERS
CFW300 | 0-13
QUICK REFERENCE OF PARAMETERS
0-14 | CFW300
QUICK REFERENCE OF PARAMETERS
CFW300 | 0-15
QUICK REFERENCE OF PARAMETERS
0-16 | CFW300
QUICK REFERENCE OF PARAMETERS
CFW300 | 0-17
QUICK REFERENCE OF PARAMETERS
0-18 | CFW300
QUICK REFERENCE OF PARAMETERS
Notes:
(*) Only available when IO or communication expansion accessory is present (connected). For further information,
refer to the respective accessory guide.
ro = Read only parameter
cfg = Configuration parameter, value can be programmed only with motor stopped
V/f = Available when V/f control mode is chosen
VVW = Available when VVW control mode is chosen
CFW300 | 0-19
QUICK REFERENCE OF PARAMETERS
0-20 | CFW300
QUICK REFERENCE OF ALARMS AND FAULTS
F033 Stator resistance setting fault P409. Stator resistance value in P409 does not comply with the
VVW Self-tuning Fault inverter power.
Motor connection error; turn off the power supply and
check the motor terminal box and the connections with the
motor terminals.
Motor power too low or too high in relation to the inverter.
A046 Motor overload alarm. Settings of P156 is too low for the used motor.
Motor Overload Overload on the motor shaft.
A050 Overtemperature alarm from the power High temperature at IGBTs. P030 > Level A050, according
IGBTs Overtemperatures module temperature sensor (NTC). to Table 11.2 on page 11-4.
High ambient temperature around the inverter and high
output current. For further information, refer to of the
user’s manual available for download on the website:
www.weg.net.
Blocked or defective fan.
Heatsink is too dirty, preventing the air flow.
F051 Overtemperature fault measured on High temperature at IGBTs. P030 > Level F051, according
IGBTs Overtemperatures the temperature sensor of the power to Table 11.2 on page 11-4.
pack. High ambient temperature around the inverter and high
output current. For further information, refer to of the
user’s manual available for download on the website:
www.weg.net.
Blocked or defective fan.
Heatsink is too dirty, preventing the air flow.
F067 Fault related to the phase relation of the Output motor cables U, V, W are inverted.
Incorrect Encoder/ Motor encoder signals. Encoder channels A and B are inverted.
Wiring Encoder was not properly mounted.
F070 Overcurrent or short-circuit on the Short-circuit between two motor phases.
Overcurrent/Shortcircuit output, DC Link or braking resistor. IGBTs module in short-circuit or damaged.
Start with too short acceleration ramp.
Start with motor spinning without the Flying Start function.
F072 Motor overload fault. P156, P157 or P158 setting is too low in relation to the
Motor Overload motor operating current.
Overload on the motor shaft.
F078 Overtemperature fault measured on Overload on the motor shaft.
Motor Overtemperature the motor temperature sensor (Triple Load cycle is too high (high number of starts and stops per
PTC) via analog input AIx minute).
High ambient temperature around the motor.
Poor contact or short-circuit (3k9 < RPTC < 0k1).
Motor thermistor not installed.
Motor shaft is stuck.
F079 Fault of encoder signals absent. Wiring between encoder and interface accessory to
Encoder Signal Fault encoder broken.
Encoder defective.
F080 Fault related to the supervision Electric noise.
CPU Fault (Watchdog) algorithm of the inverter main CPU. Inverter firmware fault.
CFW300 | 1-1
QUICK REFERENCE OF ALARMS AND FAULTS
F091 External fault via DIx (“no external fault” Wiring on DI1 to DI8 inputs are open or have poor contact.
External Fault in P263 to P270).
A128 It indicates that the device stopped Check network installation, broken cable or fault/poor
Telegram Reception Timeout receiving valid telegrams for a period contact on the connections with the network, grounding.
longer than the setting in P314. Ensure the master always sends telegrams to the
The time counting starts as soon as it equipment in a time shorter than the setting in P314.
receives the first valid telegram, with Disable this function in P314.
correct address and error-checking
field.
A133 It indicates that the CAN interface has Measure if there is voltage within the allowed range between
No Power Supply on the CAN no power supply between pins 25 and pins 25 and 29 of the CAN interface connector.
Interface 29 of the connector. Check if the power supply cables are not misconnected or
inverted.
Check for contact problems on the cable or connector of
the CAN interface.
A134 Bus off error detected on the CAN Check for short circuit on the CAN circuit transmission
Bus Off interface. cable.
Check if the cables are not misconnected or inverted.
Check if all the network devices use the same baud rate.
Check if the termination resistors with the right specification
were installed only at the end of the main bus.
Check if the CAN network was properly installed.
A135 CANopen communication error control Check the times set on the master and on the slave for
Node Guarding/ Heartbeat detected communication error using message exchange. In order to prevent problems due to
the guarding mechanism. transmission delays and time counting, it is recommended
that the values set for error detection by the slave be
multiples of the times set for message exchange on the
master.
Check if the master is sending the guarding telegrams in
the time set.
Check problems in the communication that may cause
missing telegrams or transmission delays.
A136 Alarm indicates that the DeviceNet Set the switch that controls the master operation of the
Idle Master network master is in Idle mode. master for Run or the corresponding bit on the configuration
word of the master software. If further information is
needed, refer to the documentation of the master used.
A137 Alarm that indicates that one or more Check the network master status.
DeviceNet Connection Timeout DeviceNet connections timed out. Check network installation, broken cable or fault/poor
contact on the connections with the network.
A138 It indicates that the inverter received Check the network master status, ensuring it is in the run
Profibus DP Interface in Clear the command from the Profibus DP mode.
Mode network master to go into clear mode.
A139 It indicates interruption in the Check if the network master is correctly configured and
Offline Profibus DP Interface communication between the Profibus operating properly.
DP network master and the inverter. Check for short-circuit or poor contact on the
The Profibus DP communication communication cables.
interface went into offline status. Check if the cables are not misconnected or inverted.
Check if the termination resistors with the right value were
installed only at the end of the main bus.
Check the network installation in general - cabling,
grounding.
A140 It indicates error in the access to the Check if the Profibus DP module is correctly fitted.
Profibus DP Module Access Profibus DP communication module Hardware errors due to improper handling or installation
Error data. of the accessory, for instance, may cause this error. If
possible, carry out tests by replacing the communication
accessory.
1-2 | CFW300
QUICK REFERENCE OF ALARMS AND FAULTS
A149 It indicates that the device stopped Check network installation, broken cable or fault/poor
Timeout Modbus TCP receiving valid telegrams for a period contact on the connections with the network, grounding.
longer than the setting in P868. Ensure the Modbus TCP client always sends telegrams to
The time counting starts as soon as it the equipment in a time shorter than the setting in P868.
receives the first valid telegram. Disable this function in P868.
A163 Analog input signal AI1 at 4 to 20 mA Current signal on the analog input AI1 interrupted or null.
Signal Fault AI1 4...20 mA or 20 to 4 mA is below 2 mA. Parameterization error on analog input AI1.
A164 .Analog input signal AI2 at 4 to 20 mA Current signal on the analog input AI2 interrupted or null.
Signal Fault AI2 4...20 mA or 20 to 4 mA is below 2 mA. Parameterization error on analog input AI2.
A177 Alarm to replace the fan (P045 > 50000 Maximum number of operation hours of the heatsink fan
Replace Fan hours). exceeded.
F182 Pulse feedback circuit fault of the Hardware identification fault; compare P295 and P296 to
Pulse Feedback Failure output voltage. the inverter identification label.
Note: it may be turned off in P397. Inverter internal pulse feedback circuit fault.
A211 Indicates that the drive is in Fire Mode. The digital input programmed for activating the Fire Mode
Drive in Fire Mode is active.
F228 It indicates that the device stopped Check network installation, broken cable or fault/poor
Timeout in Receipt of receiving valid telegrams for a period contact on the connections with the network, grounding.
Telegrams longer than the setting in P314. Ensure the master always sends telegrams to the
The time counting starts as soon as it equipment in a time shorter than the setting in P314.
receives the first valid telegram, with Disable this function in P314.
correct address and error-checking
field.
F233 It indicates that the CAN interface has Measure if there is voltage within the allowed range between
No Power Supply on the CAN no power supply between pins V(-) and pins V(-) and V(+) of the CAN interface connector.
Interface V(+) of the connector. Check if the power supply cables are not misconnected or
inverted.
Check for contact problems on the cable or connector of
the CAN interface.
F234 Bus off error detected on the CAN Check for short circuit on the CAN circuit transmission
Bus Off interface. cable.
Check if the cables are not misconnected or inverted.
Check if all the network devices use the same baud rate.
Check if the termination resistors with the right specification
were installed only at the end of the main bus.
Check if the CAN network was properly installed.
F235 CANopen communication error control Check the times set on the master and on the slave for
Node Guarding/ Heartbeat detected communication error using message exchange. In order to prevent problems due to
the guarding mechanism. transmission delays and time counting, it is recommended
that the values set for error detection by the slave be
multiples of the times set for message exchange on the
master.
Check if the master is sending the guarding telegrams in
the time set.
Check problems in the communication that may cause
missing telegrams or transmission delays.
F236 Fault indicates that the DeviceNet Set the switch that controls the master operation for Run
Idle Master network master is in Idle mode. or the corresponding bit on the configuration word of the
master software. If further information is needed, refer to
the documentation of the master used.
F237 Fault that indicates that one or more Check the network master status.
DeviceNet Connection Timeout DeviceNet connections timed out. Check network installation, broken cable or fault/poor
contact on the connections with the network.
F238 It indicates that the inverter received Verify the network master status, making sure it is in the
Profibus DP Interface in Clear a command from the Profibus DP execution mode (Run).
Mode network master to enter the clear
mode.
CFW300 | 1-3
QUICK REFERENCE OF ALARMS AND FAULTS
F249 It indicates that the device stopped Check network installation, broken cable or fault/poor
Timeout Modbus TCP receiving valid telegrams for a period contact on the connections with the network, grounding.
longer than the setting in P868. Ensure the Modbus TCP client always sends telegrams to
The time counting starts as soon as it the equipment in a time shorter than the setting in P868.
receives the first valid telegram. Disable this function in P868.
A700 No communication with remote HMI, Check if the communication interface with the HMI is
Remote HMI Communication but there is no frequency command or properly configured in parameter P312.
reference for this source. HMI cable disconnected.
F701 No communication with the remote Check that the HMI communication interface is properly
Remote HMI Communication HMI; however, there is command or configured in parameter P312.
Fault frequency reference for this source. HMI cable disconnected.
A702 This failure occurs when there is a Check if the drive General Enable command is active.
Inverter Disabled SoftPLC movement block active and
the “General Enable” command is
disabled.
A704 It occurs when 2 or more SoftPLC Check the user’s program logic.
Two Movem. Enabled movement blocks are enabled at the
same time.
A706 This failure occurs when a SoftPLC Check the programming of the references in the Local
Refer. Not Progr. SPLC movement block is enabled and the and/or Remote mode (P221 and P222).
speed reference is not programmed for
the SoftPLC.
A708 SoftPLC Application not running. SoftPLC Application is stopped (P901 = 0 and P900 = 3).
SoftPLC Application Stopped SoftPLC state presents application incompatible with the
firmware version of the frequency inverter.
F709 SoftPLC application not running. SoftPLC application stopped (P901 = 0 and P900 = 3).
SPLC Application Stopped SoftPLC state presents incompatible application with the
firmware version of the frequency inverter.
F710 The size of the SoftPLC user’s The logic implemented on the SoftPLC is too large. Check
Size of the SoftPLC Application program exceeded the maximum project size.
memory capacity.
F711 Fault found in SoftPLC user’s SoftPLC user’s program stored on flash memory is
Fault on SoftPLC Application program. corrupted.
Timeout during execution of SoftPLC scan cycle.
A712 It occurs when there is an attempt Attempt to copy SoftPLC application protected against
SPLC Protected Against Copy to copy the SoftPLC application copies (“never permit copies”).
protected against copies. Attempt to copy SoftPLC from a copy protected against
copies (“no permission to copy from a copy”).
F750/A750 to Fault/Alarm range intended for the Defined by the user’s application developed in the SoftPLC
F799/A799 user’s application developed in the function.
User’s Faults/Alarms for SoftPLC function.
SoftPLC
1-4 | CFW300
QUICK REFERENCE OF ALARMS AND FAULTS
A762 It indicates that the level of the control The control process variable (P916) remained above the
High Level of the Control process variable (P916) is high. value programmed in P926 for 150 ms.
Process Variable
F763 It indicates the motor was switched The control process variable (P916) remained above the
High Level of the Control off due to the high level of the control value programmed in P926 for a certain time (P927).
Process Variable process variable.
A790 It indicates that parameters of the The PID Controller was enabled, the Run/Stop command
Speed reference source not speed reference sources in local is active, and neither of the two parameters of the speed
programmed for the SoftPLC mode (P221) and in remote mode reference source was programmed in 12 (SoftPLC).
(P222) were not programmed for the
SoftPLC.
Faults operate by indicating their occurrence on the HMI, in the frequency inverter status word (P006), in the
present fault parameter (P049) and disabling the motor. They can only be reset with a reset command or de-
energizing the frequency inverter.
Alarms operate by indicating their occurrence on the HMI and in the present alarm parameter (P048). They are
automatically reset when the alarm condition ceases existing.
CFW300 | 1-5
QUICK REFERENCE OF ALARMS AND FAULTS
1-6 | CFW300
SAFETY NOTICES
2 SAFETY NOTICES
This manual contains the information necessary for the correct frequency inverter programming.
It was developed to be used by people with proper technical training or qualification to operate this kind of
equipment. These people must follow the safety instructions defined by local standards. The noncompliance with
the safety instructions may result in death risk and/or equipment damage.
2
2.1 SAFETY NOTICES IN THIS MANUAL
DANGER!
! The procedures recommended in this warning have the purpose of protecting the user against death,
serious injuries and considerable material damage.
WARNING!
! The procedures recommended in this warning have the purpose of avoiding material damage.
✓
NOTE!
The information mentioned in this warning is important for the proper understanding and good
operation of the product.
The following symbols are attached to the product, serving as safety notices:
CFW300 | 2-1
SAFETY NOTICES
DANGER!
! Only qualified personnel familiar with the frequency inverter and associated equipment should plan or
implement the installation, start-up and subsequent maintenance of this equipment.
These personnel must follow all the safety instructions included in this manual and/or defined by local
regulations.
2 Failure to comply with these instructions may result in life threatening and/or equipment damage.
✓
NOTE!
For the purposes of this manual, qualified personnel are those trained to be able to:
1. Install, ground, energize and operate the frequency inverter according to this manual and the
effective legal safety procedures.
2. Use protective equipment according to the established standards.
3. Give first aid services.
DANGER!
! Always disconnect the input power before touching any electrical component associated to the
frequency inverter.
Many components may remain loaded with high voltages and/or moving (fans), even after the AC
power supply input is disconnected or turned off.
Wait for at least ten minutes in order to guarantee the full discharge of the capacitors. Always connect
the frame size of the equipment to the protective earth (PE) at the proper point for that.
WARNING!
! Electronic boards have components sensitive to electrostatic discharge. Do not touch directly the
component parts or connectors.
If necessary, first touch the grounded metallic frame size or use proper grounding strap.
✓
NOTE!
Frequency inverters may interfere in other electronic equipments. Observe the recommendations
of chapter 3 Installation and Connection of the user’s manual in order to minimize these effects.
Read the user’s manual completely before installing or operating this inverter.
2-2 | CFW300
GENERAL INFORMATION
3 GENERAL INFORMATION
This manual presents information necessary for the configuration of all the functions and parameters of the frequency
inverter. This manual must be used together with the user’s manual.
The text provides additional information so as simplify the use and programming of the frequency inverter in certain
applications.
It is prohibited the reproduction of the contents of this manual, in whole or in part, without the written permission
of the manufacturer.
Amp, A: Ampère.
AIP: analog input via potenciometer.
AIx: analog input “x”.
AOx: analog output “x”.
◦
C: Celsius degrees.
CA: alternate current.
CC: direct current.
Pre-Charge Circuit: charges the capacitors of the DC link with limited current, avoiding current peaks in the
inverter power-up.
CO/DN/PB/ETH: Interface CANopen, DeviceNet, ProfibusDP or Ethernet. Check for the interface availability at
product user’s manual.
CV: cavalo-vapor = 736 Watts (Brazilian unit of measurement of power, normally used to indicate mechanical power
of electric motors).
Heatsink: metal part designed to dissipate the heat produced by power semiconductors.
DIx: digital input “x”.
DOx: digital output “x”.
Switching Frequency: switching frequency of the IGBTs of the inverter bridge, normally expressed in kHz.
Run/Stop: inverter function which, when activated (run), accelerates the motor by acceleration ramp up to the
reference frequency and, when deactivated (stop), decelerates the motor by deceleration ramp. It may be controlled
by digital input set for this function, via serial or via SoftPLC.
h: hour; time unit.
General Enable: when activated, it accelerates the motor by acceleration ramp and Run/Stop = Run. When
disabled, the PWM pulses will be immediately blocked. It may be controlled by digital input set for this function, via
serial or via SoftPLC.
HMI: human-machine interface; device which allows controlling the motor, viewing and changing the inverter
parameters. It features keys to control the motor, navigation keys and graphic LCD display.
hp: horse power = 746 Watts (power unit, normally used to indicate mechanical power of electric motors).
Hz: hertz; frequency unit.
IGBT: insulated gate bipolar transistor - basic component part of the output inverter bridge. It works as an electronic
switch in the saturated (closed switch) and cut-off (open switch) modes.
Inom : inverter rated current by P295.
kHz: quilohertz = 1000 Hertz; frequency unit.
CFW300 | 3-1
GENERAL INFORMATION
DC Link: intermediary circuit of the inverter; voltage in direct current obtained by rectifying the power supply
alternate voltage or external supply; it supplies the output inverter bridge with IGBTs.
mA: miliampère = 0.001 Ampère.
min: minute; time unit.
ms: milisecond = 0.001 second.
Nm: Newton meter; torque unit.
NTC: resistor whose resistance value in ohms decreases proportionally to the increase of the temperature; it is
used as a temperature sensor in power packs.
Throughout the manual, parameter values with suffix “hexa” represent hexadecimal numbers. The decimal numbers
are represented by means of digits without suffix.
3-2 | CFW300
ABOUT THE HMI
Using the HMI, it is possible to command the inverter, view and adjust all of its parameters. The HMI presents the
following functions:
Inverter status
Direction of rotation
Unit of measurement
(it refers to the value
of the main display)
When inverter is powered-up, the initial state of the HMI remains in the start-up mode as long as no faults, alarms,
undervoltages occur or no keys are pressed.
The setting mode is composed of two levels: Level 1 allows browsing the parameters. Level 2 allows the
modification of the parameter selected in level 1. At the end of this level, the modified value is saved when the
key is pressed.
A Figure 4.2 on page 4-1 illustrates the basic browsing of the operating modes of the HMI.
✓
NOTE!
When the inverter is in the fault state, the main display indicates the number of the fault in the format
Fxxx.The browsing is allowed after pressing the key.
CFW300 | 4-1
ABOUT THE HMI
4 Press the key to confirm the modification (save the new value). After the
change is confirmed, the HMI returns to level 1 of the setting mode. Setting
Locked Parametrization level 2
This state is displayed when the or keys are pressed while viewing the
parameter value with the following characteristics:
The displayed parameter is read-only.
The parameter has CFG property (change only with stopped motor) and the
motor is running. Locked
The inverter has a defined password (except if it is a SoftPLC user parameter Parameter
and has the unprotected property checked).
The parameter value is automatically displayed again when the keys are
released.
✓
NOTE!
When the inverter is in the alarm state, the main display indicates the number of the alarm in the format
Axxx.The browsing is allowed after pressing the key, and then the indication “A” is displayed on
the unit of measurement display, flashing until the situation causing the alarm is solved.
4-2 | CFW300
HMI
5 HMI
✓
NOTE!
The inverter comes from the factory with the frequency (V/f 50/60 Hz mode) and voltage adjusted
according to the market.
The reset to factory default may change the content of the parameters related to frequency.
5.1 ACCESS
Whenever the inverter is powered up, the HMI display goes to the start-up mode if no faults, alarms or undervoltages
are present. In order to simplify the reading of the inverter parameters, the display was designed to show two
parameters simultaneously, at the user’s discretion. One of those parameters (main display) is shown in the numeric
form and the other parameter as a bar graph. The parameter monitored by the bar graph is selected via P207, as
indicated in Figure 5.1 on page 5-1.
Inverter status
5
Direction of rotation
Unit of measurement
(it refers to the value
of the main display)
✓
NOTE!
The view of parameter P000 on the HMI will only be available when the password is active (P200 =
1).
To release the access to the parameters, it is necessary to set P000 after each inverter energization,
as such information is not retained.
P200 - Password
(1) It only allows changing the content of the parameters when P000 is equal to the value of the password.
(2) It is allowed to change the content of the parameters and P000 is inaccessible.
5
P204 - Load/Save Parameters
In order to load the parameters of user for operating area of the inverter (P204 = 7) it is necessary that this area be
previously saved.
The operation of uploading this memory (P204 = 7), can also be done via digital inputs (DIx). For further details
referring to this programming, refer to Section 9.6 DIGITAL INPUTS on page 9-12.
✓
NOTE!
When P204 = 5 or 6, parameters P295 (Inv. Rated Current), P296 (Line Rated Voltage) and P308
(Serial Address) are not changed.
5-2 | CFW300
HMI
✓
NOTE!
In order to upload the user parameters (P204 = 7), the factory default must be uploaded first (P204
= 5 or 6).
5.2 INDICATIONS
5
Adjustable 0 to 999 Factory 3
Range: Setting:
Description:
Defines which parameter will be shown on the HMI bar graph.
5-4 | CFW300
FREQUENCY INVERTER IDENTIFICATION
In order to check the inverter model, see the code on the product nameplate on the side of the inverter.
Once verified the identification code of the model of the inverter, refer to Chapter 2 General Information of the user’s
manual of the frequency inverter.
The parameters related to the inverter model are shown below. They are modified according to the model and
version of the inverter and must comply with the data read on the product nameplate.
CFW300 | 6-1
FREQUENCY INVERTER IDENTIFICATION
✓
NOTE!
The models of the 400 V line have rated currents specified according to the supply voltage:
Voltage range 1: power supplies of 380-400-415 Vac, or 513-540-560 Vdc (P296 = 4 or 5).
Voltage range 2: power supplies of 440-460-480 Vac, or 594-621-650 Vdc (P296 = 6 or 7).
For these models, P296 must be adjusted in accordance with the mains voltage used, and the
parameter P295 will be changed automatically by the inverter. For more information, refer to the
user manual, available for download on www.weg.net.
6-2 | CFW300
FREQUENCY INVERTER IDENTIFICATION
✓
NOTE!
200 V Line: P296 is read-only parameter (ro).
400 V Line: P296 is configuration parameter (cfg).
For further information, refer to the user’s manual, available for download on: www.weg.net.
6
P613 - Main SW Revision
6.2 ACCESSORIES
CFW300 | 6-3
FREQUENCY INVERTER IDENTIFICATION
Adjustable 0 to 10 Factory
Range: Setting:
Properties: ro
Description:
It indicates accessories that are connected according to the quick reference of each product.
6-4 | CFW300
COMMAND AND REFERENCES
The drive of the electric motor connected to the inverter depends on the logical command and on the reference
defined by one of the several possible sources, such as: HMI keys, digital inputs (DIx), analog inputs (AIx), Serial/
USB interface, CANopen/DeviceNet interface, SoftPLC, etc.
The command via HMI is limited to a set of functions pre-defined for the keys according to Chapter 5 HMI on page
5-1, similarly to the digital inputs (DIx), with the functions implemented in parameter P263 to P266. On the other
hand, the command via digital interfaces, such as communication network and SoftPLC, act directly on the inverter
control word by means of control parameters and system markers of the SoftPLC, respectively.
The frequency reference, in turn, is processed inside the frequency inverter in 16 bits with signal (-32768 to +32767)
for a range of -400.0 Hz to +400.0 Hz. On the other hand, the unit factor, range and resolution of the reference
depend on the used source, as described in Section 7.2 SPEED REFERENCE on page 7-6.
The inverter command and reference source is defined by the inverter parameters for two different situations: Local
and Remote, which can be switched dynamically during the inverter operation. Thus, for a certain parameterization,
the inverter has two sets for command and reference, according to block diagram of Figure 7.1 on page 7-2.
Parameter P220 determines the source of commands for Local and Remote situations.
Parameters P223, P224 and P225 define the commands in the Local situation; parameters P226, P227 and P228
define the commands in the Remote situation, and parameter P105 determines the source for selection between
1st and 2nd Ramp. This structure for the selection of the command source is shown in Figure 7.1 on page 7-2.
Parameters P221 and P222 define the frequency reference in the Local and Remote situations. This structure for
the selection of the reference source is shown in Figure 7.2 on page 7-3.
7
CFW300 | 7-1
COMMAND AND REFERENCES
Direction of
rotation
P223
Run/
Stop
P224
Control
LOC
P225
JOG
word
Control word
Direction of
REM
rotation Control
P226
word
Run/
P227
Stop
P228
JOG
LOC/REM
7
P220
2nd Ramp
P105
Reference
P221
LOC
frequency
Reference frequency
Reference
REM
P222
frequency
7-2 | CFW300
COMMAND AND REFERENCES
Command
selection
frequency
HMI P221 or P222
Reference
HMIR key (P121) 0 - HMI
CRS485
Accessory
FI
via
7 - EP
DI1 to DI4 P247
P249
Accel.
DIx
Decel. 4 - FI
DIx
17 - FI > 0
Electronic potentiometer Frequency
reference of
P124 to P131 the inverter
DIx
DIx
8 - Multispeed
DIx
Multispeed
AI1
1 - AI1
P232 14 - AI1 > 0
P234
5 - AI1 + AI2 > 0
7
6 - AI1 + AI2
AI2
2 - AI2
P237 15 - AI2 > 0
P239
Potentiometer
P242 3 - Potentiometer
P244 16 - Potentiometer > 0
CRS232
PC Accessory
9 - Serial/USB
CUSB
Accessory
Bluetooth CBLT
adapter Accessory
CANopen / DeviceNet
CCAN / CPDP / CETH-IP
Profibus DP
Accessory
ModbusTCP / Ethernet-IP 11 - CO/DN/DP/ETH
SoftPLC
12 - SoftPLC
CFW300 | 7-3
COMMAND AND REFERENCES
AIx: it refers to the analog input signal according to Section 9.1 ANALOG INPUTS on page 9-1.
HMI: the reference value set by the keys and are contained in parameter P121.
7-4 | CFW300
COMMAND AND REFERENCES
E.P.: electronic potentiometer, refer to Section 9.6 DIGITAL INPUTS on page 9-12.
AIx > 0: the negative values of the AIx reference are zeroed.
H: means Forward.
CFW300 | 7-5
COMMAND AND REFERENCES
✓
NOTE!
When the Coast Stop mode is programmed and the Flying Start function is disabled, only activate
the motor if it is stopped.
✓
NOTE!
This parameter is applied to all the inverter command sources, but it was created aiming at allowing
the command via HMI to be able to disable the motor by inertia instead of deceleration ramp. In this
way, when P229 = 1, Bit 0 of the control word (Ramp Enable) has a function similar to Bit 1 (General
Enable). The same way, the digital input functions such as: Run/Stop, Forward/Reverse Run stop
the motor by inertia in this condition of P229.
The frequency reference is the value applied to the input of the acceleration ramp module (P001) to control the
frequency applied to the inverter output (P002) and consequently the motor shaft speed.
Inside the CPU, the inverter uses signed 16 bit variables to treat the frequency references. Besides, the full scale of
the reference, output frequency and related variables are defined in 400.0 Hz. On the other hand, depending on the
source, this scale is conveniently modified considering the interface with the user by standardization or application
requirements.
In general, the digital references defined by parameters such as: HMI keys (P121), Multispeed (P124 to P131) and
7-6 | CFW300
COMMAND AND REFERENCES
E.P. have a scale from 0.0 to 400.0 Hz with resolution of 0.1 Hz.
In digital inputs (DIx), on the other hand, the reference is defined according to the function predefined for P263 to
P266.
The frequency reference applied to the inverter output via frequency input follows the behavior of the parameters
related to it (P230 to P250).
The full scale of the reference is always by P134, that is, maximum value in AIx is equivalent to the frequency
reference equal to P134.
The digital references Serial/USB, CANopen/DeviceNet, Profibus DP, Ethernet and SoftPLC act on a standardized
scale called “13-bit speed”, where the value 8192 (213 ) is equivalent to the motor rated frequency (P403).
Those references are accessed by parameters P683 and P685.
The digital references, though, have a different scale and the frequency reference parameters with their range from
0.0 to 400.0 Hz, according to previous descriptions, the frequency value on the ramp input (P001) is always limited
by P133 and P134.
For example, the JOG reference is given by P122, this parameter may be set in up to 400.0 Hz, but the value
applied to the ramp input as reference will be limited by P134 when the function is executed.
Table 7.2: Summary of the scales and resolutions of the frequency references
Reference Full Scale Resolution
Analog input (AIx) -P134 to P134 10 bits or (P134/1024)
Communication Networks and SoftPLC -400.0 Hz to 400.0 Hz 13-Bit Speed (P403/8192)
HMI Parameter -400.0 Hz to 400.0 Hz 0.1 Hz
If P120 = Inactive, the inverter will not save the speed reference value when it is disabled. Thus, when the inverter
is enabled again, the speed reference value will become the frequency minimum limit value (P133).
If P120 = Active, the value set in the reference is not lost when the inverter is disabled or powered down.
If P120 = Backup by P121, the reference initial value is fixed by P121 at the enabling or power-up of the inverter.
in the monitoring mode, the value of P121 is increased and shown on the HMI main display. Besides, the P121 is
used as input for the reference backup function.
✓
NOTE!
The minimum and maximum values of parameter setting are limited by P134 and P133, respectively.
7-8 | CFW300
COMMAND AND REFERENCES
Output
P131
frequency
P130
P129
P128
Acceleration
P127 ramp
7
P126
P125
P124
Time
Active
DI1 or DI2
Inactive
DI5 or DI6
Active
Active
of “13-bit speed”.
7-10 | CFW300
MOTOR CONTROL
8 MOTOR CONTROL
The inverter feeds the motor with variable voltage, current and frequency, providing control of the motor speed.
The values applied to the motor follow a control strategy, which depends on the selected type of motor control and
on the inverter parameter settings.
The selection of the proper control type for the application depends on the static and dynamic requirements of torque
and speed of the driven load, that is, the control type is directly connected to the required performance. Additionally,
proper configuration of the selected control mode parameters is essential to reach maximum performance.
The inverter is equipped with three control modes for the three-phase induction motor, that is:
V/f Scalar Control: for basic applications without output speed control.
Quadratic V/f Scalar Control: for applications that reduce motor and inverter losses without regulation of the
output speed.
VVW Control: for applications that need high performance in the control of the output speed.
Section 8.2 CONTROLE ESCALAR V/f on page 8-19 and Section 8.3 CONTROLE VVW on page 8-27, each of
these kinds of control, related parameters and directions regarding the use of each of these modes are described
in details.
This chapter describes the functions common to all inverter control modes V/f and VVW and that interfere in the
drive performance.
8.1.1 Ramps
The inverter ramp functions allow the motor to accelerate or decelerate faster or slower. They are adjusted by
parameters that define the linear acceleration time between zero and the maximum frequency (P134) and the time
for a linear deceleration from the maximum frequency zero.
In the inverter, three ramps with different functions were implemented:
2nd Ramp - it may be activated by the user, according to the drive requirement, by means of the inverter command
word or by a digital input.
emergency ramp - it is used for the inverter internal protection functions, such as: current limitation, DC link
regulation, etc. The Emergency Ramp has priority over the other ramps.
✓
NOTE!
The setting with too short ramp time may cause overcurrent in the output (F070), undervoltage (F021)
or overvoltage (F022) of the DC link.
CFW300 | 8-1
MOTOR CONTROL
P104 - Ramp S
Output
frequency
Linear ramp
Ramp S t(s)
8-2 | CFW300
MOTOR CONTROL
8.1.2 Regulation
The DC link voltage and output current limitation are protection functions of the inverter which act on the ramp
control, aiming at containing the rise of voltage on the DC link and of the output current. In this way, the following
of the reference by the ramp is blocked and the output frequency follows the emergency ramp for a preset safety
value.
When the DC link voltage is too high, the inverter may freeze the deceleration ramp. On the other hand, when
the output current is too high, the inverter may decelerate or freeze the acceleration ramp in order to reduce this
current. Those actions prevent the occurrence of faults F022 and F070, respectively.
Both protections normally occur at different moments of the inverter operation, but in case of occurrence at the
same time, by definition, the DC link limitation has higher priority than the output current limitation.
The voltage limitation on the DC link during braking actuates limiting the braking power and torque, so as to prevent
the shutting down of the inverter for overvoltage (F022). This situation often occurs when a load with high moment 8
of inertia is decelerated or when short deceleration time is programmed.
Use recommended in the drive of loads with high moment of inertia referred to the motor shaft or loads that
require short deceleration ramps.
Actuation: when the DC link voltage reaches the level set in P151, a command is sent to the ramp block to
accelerate the motor.
Use recommended for the drive of loads that require braking torques at constant frequency in the inverter output.
For example, the drive of loads with eccentric shaft as in sucker rod pumps; another application is the handling
of loads with balance like in the translation in overhead cranes.
Another condition that prevents the output voltage from reaching its maximum value is internal losses of the inverter.
Such losses are associated to the dead time of the switching and losses in the components, being aggravated by
the increase of the switching frequency.
8-4 | CFW300
MOTOR CONTROL
Such conditions, variations in the DC Link voltage and internal losses can be compensated with variations in the
modulation index; however, with specific characteristics as presented in each of the options below:
P149 = 0 (Disabled): The DC link compensation is disabled. The DC link voltage oscillations will reflected in the
output voltage.
P149 = 1 (Standard): In this mode, the output voltage will be generated according to the ideal V/f profile,
parameterized in P142, P143, P145 and P146, but not reaching the maximum available voltage at the output
and also not generating distortions in the output voltage.
P149 = 2 (Overmodulation): When selecting this option the output voltage will also be generated according to
the ideal V/f profile, parameterized in P142, P143, P145 and P146, but the maximum available voltage can be
generated. On the other hand, distortions in the output voltage may occur.
P149 = 3 (Extended): This option works similarly to option 2 (overmodulation). However, in the event of a DC
link voltage drop of approximately 20 % of the rated voltage, the function may take two different actions:
1. If the torque demand is low, it reduces the voltage applied to the motor, also reducing the motor current,
allowing to maintain the application, or;
2. If the torque demand is high, it reduces the output frequency until it is possible to generate a voltage according
to the V/f profile.
Both cases have restrictions of use according to the final application, and the user is responsible for validating the
application.
✓
NOTE!
It is recommended to use extended DC link voltage compensation mode (P149 = 3) for quadratic
torque applications (blowers, fans, pumps and compressors).
WARNING! 8
! The use of the DC link voltage compensation options does not compensates for all internal losses of
the inverter, and it is not intended to increase the performance in installations that do not observe the
recommendations in the product user’s manual.
CFW300 | 8-5
MOTOR CONTROL
Figure 8.3 on page 8-6 shows the block diagram of the actuation of the limitation. Figure 8.4 on page 8-6 and
Figure 8.5 on page 8-7 show the example chart.
Ramp
P100-P104
Reference Output frequency
P101 P002
Hold
P004 + ≥0
-
P151
F022 - overvoltage
P151 DC Link
Ud rated regulation
8 Time
Output
frequency
Time
Figure 8.4: Example graph of DC Link voltage limitation - Ramp Hold (P150 = 2 or 3)
8-6 | CFW300
MOTOR CONTROL
F022 - overvoltage
P151 DC Link
Ud rated regulation
Time
Output
frequency
Time
Figure 8.5: Example graph of the DC Link voltage limitation - Accelerate Ramp (P150 = 0 or 1)
Like in the DC Link voltage regulation, the output current regulation also has two operating modes: “Ramp Holding”
(P150 = 2 or 3) and “Decelerate Ramp” (P150 = 0 or 1). Both actuate limiting the torque and power delivered to the
motor, so as to prevent the shutting down of the inverter by overcurrent (F070). This situation often occurs when a
load with high moment of inertia is accelerated or when short acceleration time is programmed.
Actuation: if the motor current exceeds the value set in P135 during acceleration or deceleration, the frequency
will not be incremented (acceleration) or decremented (deceleration). When the motor current reaches a value
below P135 the motor accelerates or decelerates again. Refer to Figure 8.6 on page 8-8.
Actuation: if the motor current exceeds the value set in P135, a null value is forced for the frequency ramp input
forcing the motor deceleration. When the motor current reaches a value below P135 the motor accelerates again.
Refer to Figure 8.6 on page 8-8.
CFW300 | 8-7
MOTOR CONTROL
Figure 8.6 on page 8-8 (a) and (b), respectively. In order to disable the current limitation, you must set parameter
P135 > 1.9 x Inom .
P135 P135
Time Time
Output Output
frequency frequency
Ramp
deceleration
Ramp (P101)
acceleration
(P100) Time Time
During Acceleration During Deceleration
Motor current
P135
Time
Output
frequency
8 It decelerates
by emergency
ramp
Time
8-8 | CFW300
MOTOR CONTROL
✓
NOTE!
Both the function related to P219 and the function controlled by P397 (bit 3) act by reducing the
switching frequency. As the function related to P219 is intended to improve the reading of the inverter
current, that function has priority of action over the function controlled by P397 (bit 3).
The Flying Start function allows driving a motor that is in free running, accelerating it from the rotation in which it is.
The Ride-Through function allows recovering the inverter, with no locking by undervoltage, when there is an instant
drop in the power supply.
Both functions assume the special case in which the motor is running in the same direction and at a frequency close
to the frequency reference, thus, by immediately applying the frequency reference to the output and increasing the
output voltage in ramp, the slip and the starting torque are minimized.
Flying Start Function (FS): In order to activate this function, just program P320 in 1 or 2; thus the inverter will
impose a fixed frequency at the start, defined by the frequency reference, and apply the voltage ramp defined in
parameter P331. In this way, the start current is reduced. On the other hand, if the motor is at rest, the frequency
reference and the real frequency of the motor are very different or the direction of rotation is inverted; the result in
such cases may be worse than the conventional start without Flying Start.
The Flying Start function is applied on loads with high inertia or systems that require start with the motor spinning.
Besides, the function may be deactivated dynamically by a digital input P263 to P266 programmed for “24
= Disable Flying Start”. In this way, the user may activate the function in a convenient way according to the
application.
Ride-Through Function (RT): The Ride-Through function will disable the inverter output pulses (IGBT) as soon
as the supply voltage reaches a value below the undervoltage value. A fault due to undervoltage (F021) does not
occur and the DC link voltage will slowly drop until the supply voltage returns. In case it takes the supply voltage
too long to return (over 2 seconds), the inverter may indicate F021 (undervoltage on the DC link). If the supply
voltage returns before, the inverter will enable the pulses again, imposing the frequency reference instantly (like
in the Flying Start function) and making a voltage ramp with time defined by parameter P331. Refer to Figure 8.7
on page 8-10.
Return line
DC Link
voltage
Level F021
P331
Output voltage
8
Disabled
0V
Output
frequency (P002)
0 Hz
The Ride-Through function allows recovering the inverter without locking by undervoltage F021 for momentary
power supply drops. The time interval accepted during a fault is at most two seconds.
8-10 | CFW300
MOTOR CONTROL
It defines the minimum time the frequency inverter will wait until driving the motor again with the Ride Through
function, which is necessary to demagnetize the motor.
8.1.4 DC Braking
The DC Braking allows stopping the motor by applying direct current to it. The current applied at the DC Braking is
proportional to the braking torque and may be set in P302. It is set in percentage (%) of the inverter rated current
considering the motor of power compatible with the inverter.
Output frequency
Time
Direct current
injection at start
P299
P302
DC braking
Time
8
Run
Stop
CFW300 | 8-11
MOTOR CONTROL
Injection of
DC current
Output P300
frequency
P301
Time
Active
DIx - Run/Stop
Inactive
During the braking process, if the inverter is enabled, the braking is interrupted and the inverter will start operating
normally.
WARNING!
! The DC Braking can continue acting even if the motor has already stopped. Be careful with the
thermal dimensioning of the motor for short-period cyclic braking.
✓
NOTE!
A value too high in P302 may cause overcurrent faults on the inverter and even damages to the
connected motor by overcurrent on the windings.
8-12 | CFW300
MOTOR CONTROL
The braking torque that can be obtained through the application of frequency inverters without dynamic braking
resistors varies from 10 % to 35 % of the motor rated torque.
In order to obtain higher braking torques, resistors for dynamic braking are used. In this case the regenerated
energy is dissipated on the resistor mounted externally to the inverter.
This type of braking is used in the cases when short deceleration times are wished or when high inertia loads are
driven.
✓
NOTE!
The Dynamic Braking function can only be used if a braking resistor has been connected to the
inverter, and if the parameters related to it have been adjusted properly.
Figure 8.10 on page 8-14 shows an example of typical dynamic braking actuation, where the hypothetical wave
shapes of the voltage on the braking resistor and the DC link voltage can be observed. Thus, when the braking
IGBT connects the link to the external resistor, the DC link voltage drops below the value set by P153, keeping the
level below fault F022.
CFW300 | 8-13
MOTOR CONTROL
Time
Ud Ud
Braking resistor
voltage (DB) Time
With the inverter powered down, connect the braking resistor (Refer to the user’s manual of the Inverter).
Set P151 at the maximum value: (According to inverter model) to prevent the activation of the DC voltage
regulation before the dynamic braking.
DANGER!
! Be sure the inverter is OFF and disconnected before handling the electric connections and read
carefully the installation instructions of the user’s manual.
8
8.1.6 Skip Frequency
This inverter function prevents the motor from operating permanently at frequency values in which, for example,
the mechanical system goes into resonance (causing excessive vibration or noises).
8-15 below. The passage by the skip frequency band (2 x P306) is done through acceleration/deceleration ramp.
The function does not operate correctly if two bands of “Skip Frequency” overlap.
2 x P306
Output
frequency
P304 2 x P306
P303
Reference
P303
P304
Figure 8.11: Actuation of the skip frequency
The “Fire Mode” function is intended to make the frequency inverter continue to drive the motor even under adverse
conditions, inhibiting most faults generated by the frequency inverter. The “Fire Mode” is activated by driving a digital
input previously set to “Fire Mode” with logic level “0” at the input terminals. When the drive enters the “Fire Mode”,
the alarm “A211” will be generated on the HMI (keypad) and the status of the operation mode will be updated in
parameter P006.
CFW300 | 8-15
MOTOR CONTROL
DANGER!
✓
NOTE!
When activating the “Fire Mode” function, the user acknowledges that the protection functions of
the frequency inverter are disabled, which may result in damages to the frequency inverter, to the
components connected to it, to the environment in which it is installed and to the people present in
such environment. Therefore, the user takes full liability for the resulting risks. The operation of the
inverter with the “Fire Mode” function enabled voids the warranty of the product. The operation under
such condition is internally registered by the frequency inverter and must be validated by an engineer
and occupational safety professional duly qualified. If the user presses the key, the message will
disappear from the display (A211), but the operation mode will continue to be shown in parameter
P006. It is also possible to indicate this condition in a digital output (DOx) previously programmed for
“Fire Mode”. During the operation in “Fire Mode”, all the stop commands are ignored (even General
Enable). Some Faults (considered critical) that may damage the inverter will not be disabled, but they
can be infinitely reset automatically (define this condition in parameter P582): Overvoltage on the DC
Link (F022), Overcurrent/Short Circuit (F070).
8-16 | CFW300
MOTOR CONTROL
CFW300 | 8-17
MOTOR CONTROL
✓
NOTE!
Both the function related to P219 and the function controlled by P397 (bit 3) act by reducing the
switching frequency. As the function related to P219 is intended to improve the reading of the inverter
current, that function has priority of action over the function controlled by P397 (bit 3).
8 WARNING!
! The default setting of P397 meets most application needs of the inverter. Therefore, avoid modifying
its content without knowing the related consequences. If you are not sure, contact WEG Technical
Assistance before changing P397.
8-18 | CFW300
MOTOR CONTROL
8.2 V/F
This is the classical control method for three-phase induction motors, based on a curve that relates output frequency
and voltage. The inverter works as a variable frequency and voltage source, generating a combination of voltage
and frequency according to the configured curve. It is possible to adjust this curve for standard 50 Hz, 60 Hz or
special motors.
According to the block diagram of Figure 8.12 on page 8-20, the frequency reference f* is limited by P133 and
P134 and applied to the input of “V/f Curve” block, where the output voltage amplitude and frequency imposed to
the motor are obtained. For further details on the frequency reference, refer to Section 7.2 SPEED REFERENCE
on page 7-6.
By monitoring the total and active output current, and the DC link voltage, compensators and regulators are
implanted so as to help in the protection and performance of the V/f control. The operation and parameterization
of those blocks are detailed in Section 8.1 COMMON FUNCTIONS on page 8-1.
The advantage of the V/f control is its simplicity and the need of few settings. The start-up is quick and simple
and the factory default, in general, requires little or no modification. In cases whose objective is to reduce losses
on the motor and inverter, the “Quadratic V/f” may be used, where the flow in the motor air-gap is proportional to
the output frequency up to the field weakening point (also defined by P142 and P145). Thus, the result is a torque
capacity as a quadratic function of the frequency. The great advantage of such control is the capacity to save
energy when driving loads with variable resistant torque, due to the reduction of motor losses (especially losses in
the air-gar, magnetic losses).
The V/f or scalar control is recommended for the following cases:
Motor rated current lower than 1/3 of the inverter rated current.
For test purposes, the inverter is turned on without motor or with a small motor with no load.
Applications where the load connected to the inverter is not a three-phase induction motor. 8
Applications that aim at reducing losses on the motor and inverter (Quadratic V/f).
CFW300 | 8-19
8
Power Supply
8-20 | CFW300
MOTOR CONTROL
Ud Curve V/f
P202 = 0 (V/f)
P151 P142
P143
P151 P137 Direction of rotation
P136
P146 P145 f
P135 Io P138
Ia
Io P003 Iv ,Iw
Calculation of Io
MOTOR CONTROL
The V/f curve is completely adjustable in four different points as according to Figure 8.13 on page 8-21, although
the factory default set a curve pre-adjusted for motors 50 Hz or 60 Hz, as options for P204. This format, point P0
defines the amplitude applied at 0 Hz, while P2 defines the rated amplitude and frequency and beginning of field
weakening. Intermediate points P1 allow the setting of the curve for a non-linear relationship between torque and
frequency, for instance, in fans where the load torque is quadratic in relation to the frequency. The field weakening
region is determined between P2 and P3 , where the amplitude is maintained in 100 %.
Output
voltage (%)
P142
P2 P3
P143
P1
P136
P0
P146 P145 P134 Output
frequency (Hz)
Figure 8.13: Curve V/f
The factory default setting of the frequency inverter defines a linear relation of the torque with the frequency by
means of three points (P0 , P1 and P2 ).
The points P0 [P136, 0 Hz], P1 [P143, P146], P2 [P142, P145] and P3 [100 %, P134] can be set so that the voltage
and frequency relation imposed to the output approximates the ideal curve for the load. Therefore, for loads in
which the torque behavior is quadratic in relation to the frequency, such as in centrifugal pumps and fans, the
points of the curve can be set or the Quadratic V/f control mode can be used so as to save energy. This Quadratic
V/f curve is presented in Figure 8.14 on page 8-21. 8
Output
voltage (%)
P142
P136
✓
NOTE!
In frequencies below 0.1 Hz, the output PWM pulses are cut, except when the inverter is in DC Braking
mode.
CFW300 | 8-21
MOTOR CONTROL
✓
NOTE!
Read chapter 3 Installation and Connection of the frequency inverter user’s manual before installing,
energizing or operating the inverter.
1. Install the inverter: according to chapter 3 Installation and Connection of the user’s manual, making all the
power and control connections.
2. Prepare and power up the inverter according to Section 3.2 Electrical Installation of the user’s manual of the
frequency inverter.
3. Load the factory default with P204 = 5 (60 Hz) or P204 = 6 (50 Hz), according to the input rated frequency
(power supply) of the inverter used.
4. Set the value of P296 according to the rated supply voltage (only for the 400 V Line).
5. In order to set a V/f curve different from the default, set the V/f curve using parameters P136 to P146.
6. Setting of specific parameters and functions for the application: program the digital and analog inputs and
outputs, HMI keys, etc., according to the application requirements.
Output
voltage (%)
P142
P2 P3
P143
P1
P136
P0
P146 P145 P134 Output
frequency (Hz)
Figure 8.15: Torque boost region for quadratic V/f control mode
8-22 | CFW300
MOTOR CONTROL
Output
voltage (%)
P142
P136
P007
IxR Voltage
Frequency reference applied on
P136
the motor
IxR
Output automatic
active current P137
P139
Figure 8.17: Block diagram of the automatic torque boost
CFW300 | 8-23
MOTOR CONTROL
Description:
Defines the percentage of compensation of the speed drop due to the application of the load on the shaft and,
consequently, the slip. Parameter P138 is used in the motor slip compensation function, when set for positive
values. In this case, it compensates the speed drop due to the application of load on the shaft and, consequently,
the slip. Thus, it increments the output frequency (Δf) considering the increase of the motor active current, as shown
in Figure 8.18 on page 8-24. In Figure 8.12 on page 8-20 this compensation is represented in the variable fSlip .
The setting in P138 allows regulating with good accuracy the slip compensation by moving the operation point on
the V/f curve, as shown in Figure 8.18 on page 8-24. Once P138 is set, the inverter is able to keep the frequency
constant even with load variations.
Negative values are used in special applications where you wish to reduce the output frequency considering the
increase of the motor current.
Eg.: load distribution in motors driven in parallel.
Output
voltage (%)
P142
P143
P136 ∆f
8
P142 - Maximum Output Voltage
The adjustment of the V/f curve is necessary when the motor has a frequency different from 50 Hz or 60 Hz, or when
a quadratic approximation is desired for energy saving in centrifugal pumps and fans, or in special applications:
when a transformer is used between the inverter and the motor or the inverter is used as a power supply.
The efficiency of a machine is defined as being the ratio between the output mechanical power and the input
electrical power. Remember that the mechanical power is the product between torque and rotor speed, and that
the input electric power is the sum of the output mechanical power and the motor losses.
In the case of the three-phase induction motor, the optimized efficiency is achieved with ¾ of the rated load. In the
region below this point, the Energy Saving function has its best performance.
The Energy Saving function acts directly on the voltage applied on the inverter output; thus, the flux relationship
delivered to the motor is changed so as to reduce the motor losses and enhance the efficiency, consequently
reducing consumption and noise.
Output
voltage (%)
P142
P589
P142
P589
8
The function will be active when the motor load is below the maximum value (P588) and the frequency is above
the minimum value (P590). In addition, in order to prevent the stalling of the motor, the applied voltage is limited to
a minimum acceptable value (P589). The parameter group presented in the sequence defines the characteristics
necessary for the energy saving function.
✓
NOTE!
The use of the energy saving function is recommended in quadratic torque applications (blowers,
fans, pumps and compressors).
Description:
It indicates the power factor, that is, the relationship between the real power and the total power absorbed by the
motor.
Adjustable 0 to 85 % Factory 0%
Range: Setting:
Properties: cfg
Description:
8
It defines the torque value to activate the operation of the energy saving function.
Setting this parameter to 0 % disables the function.
It is recommended to set this parameter to 60 %, but it has to be set according the application requirements.
Adjustable 40 to 80 % Factory 40 %
Range: Setting:
Properties: cfg
Description:
It defines the minimum voltage value that will be applied to the motor when the energy saving function is active.
This minimum value is relative to the voltage imposed by the V/f curve for a certain speed.
8-26 | CFW300
MOTOR CONTROL
Adjustable 0 to 30 % Factory 10 %
Range: Setting:
Properties: cfg
Description:
It defines the hysteresis used to activate and deactivate the energy saving function.
If the function is active and the output current oscillates, it is necessary to increase the hysteresis value.
✓
NOTE!
It is not possible to set those parameters, while the motor is spinning.
8.3 VVW
The VVW vector control mode (Voltage Vector WEG) uses a control method with a much higher performance than
the V/f control because of the load torque estimation and of the control of the magnetic flux in the air gap, as per
scheme of Figure 8.20 on page 8-28. In this control strategy, losses, efficiency, rated slip and power factor of the
motor are considered in order to improve the control performance.
The main advantage compared to the V/f control is the best frequency regulation with greater torque capacity
at low speeds (frequencies below 5 Hz), allowing a relevant improvement in the drive performance in permanent
duty. Besides, the VVW control has a quick and simple setting and it is suitable for most medium-performance
applications in the control of three-phase induction motor.
By just measuring the output current, the VVW control instantly obtains the motor torque and slip. Thus, the VVW
actuates in the output voltage compensation and slip compensation. Therefore, the VVW controller action replaces
the classical V/f functions in P137 and P138, but with a calculation model much more sophisticated and accurate,
meeting several load conditions or operation points of the application.
8
In order to achieve a good frequency regulation in permanent duty with a good operation of the VVW control, the
parameter setting in the range P399 to P407, and the stator resistance in P409 are essential for the good operation
of the VVW control. These parameters can be easily obtained on the motor nameplate.
CFW300 | 8-27
8
Power supply
8-28 | CFW300
P202 = 5 (VVW Control)
MOTOR CONTROL
m MI
Current limitation Calculation of Ia Ish 3ϕ
controller
P135 fo
P403 Calculation of fslip
Ia
P295
TL /TR , SR
404, P399, fo
P401,P409, Ia
Torque Iv ,Iw
P402, P403 Io Calculation of Io
estimation
Ud m
Io P003
MOTOR CONTROL
Opposite to the V/f scalar control, the VVW control requires a series of data from the motor nameplate and a self-
tuning for its proper operation. Besides, it is recommended that the driven motor match the inverter, that is, the
motor and inverter power be as close as possible.
Below are described the parameters to configure the VVW vector control setting. This data is easily obtained on
WEG standard motor nameplates, however in older motors or motors made by other manufacturers, the data may
not be readily available.
In those cases, it is recommended first contact the motor manufacturer, measure or calculate the desired parameter.
As a last resort, the user always can make a relationship with Table 8.6 on page 8-30 and use the equivalent or
approximate WEG standard motor parameter.
✓
NOTE!
The correct setting of the parameters directly contributes to the VVW control performance.
CFW300 | 8-29
MOTOR CONTROL
✓
NOTE!
Read chapter 3 Installation and Connection of the frequency inverter user’s manual before installing,
energizing or operating the inverter.
1. Install the inverter: according to chapter 3 Installation and Connection of the user’s manual, making all the
power and control connections.
8-30 | CFW300
MOTOR CONTROL
2. Prepare and power up the inverter: according to Section 3.2 Electrical Installation of the user’s manual.
3. Load the correct factory default in P204: based on the motor rated frequency (set P204 = 5 for 60 Hz
motors and P204 = 6 for 50 Hz motors.
4. Setting of specific parameters and functions for the application: program the digital and analog inputs
and outputs, HMI keys, etc., according to the application requirements.
5. Activation of the VVW control: set P202 = 5 and parameters P399, P400, P401, P402, P403, P404 and
P407 according to the motor nameplate. Also set the value of P409. If some of those data are not available,
enter the approximate value by calculation or by similarity with WEG standard motor, see the Table 8.6 on
page 8-30.
6. Self-Tuning of the VVW control: the self-tuning is activated by setting P408 = 1. In this process, the inverter
applies DC to the motor to measure the stator resistance, while the HMI bar graph shows the progress of the
self-tuning. The self-tuning process can be interrupted at any time by pressing the key.
7. End of the Self-Tuning: at end of the self-tuning, the HMI returns to the browsing menu, the bar displays
the parameter programmed by P207 again and the stator resistance measured is stored in P409. On the
other hand, if the self-tuning fails, the inverter will indicate a fault. The most common fault in this case is F033,
which indicates error in the estimated stator resistance. Refer to Chapter 10 FAULTS AND ALARMS on page
10-1.
For better visualization of the start-up in the VVW mode, check Table 8.7 on page 8-32.
CFW300 | 8-31
MOTOR CONTROL
Seq Indication on the Display / Action Seq Indication on the Display / Action
Initialization mode
Press this key to enter the first level of the setting Press the or keys until selecting parameter P296
mode
If necessary, change the content of “P296 - Line Rated Press the key to change the content of “P202 -
Voltage” (only for 400 V line) Control Type” to P202 = 5 (VVW)
Press the key until selecting parameter P202 Use the key
Press the key to save the change of P202 If necessary, change the content of “P399 - Motor
Use the key until selecting parameter P399 Rated Efficiency” according to data on the nameplate
Press the key for the next parameter
If necessary, change the content of “P400 - Motor If necessary, change the content of “P401 - Motor
Rated Voltage” Rated Current”
Press the key for the next parameter Press the key for the next parameter
If necessary, change the content of “P402 - Motor If necessary, change the content of “P403 - Motor
Rated Speed” Rated Frequency”
Press the key for the next parameter Press the key for the next parameter
8
If necessary, change the content of “P404 - Motor If necessary, change the content of “P407 - Motor
Rated Output” Rated Power Factor”
Press the key for the next parameter Press the key for the next parameter
If necessary to make the self-tuning, change the value of During the self-tuning, the HMI will show “Auto” and the
P408 to “1” bar will indicate the operation progress
When the self-tuning is completed, it will return to the If necessary, change the content of “P409 - Stator
Initialization Mode Resistance”
8-32 | CFW300
MOTOR CONTROL
Table 8.8: Default setting of P400 according to the identified inverter model
P296 P145 (Hz) P400 (V)
0 Reserved Reserved
50.0 230
1
60.0 220
50.0 230
2
60.0 220
3 Reserved Reserved
4 50/60 380
5 50/60 415
6 50/60 440
7 50/60 480
For further information on model identification, refer to Table 6.1 on page 6-2 of Chapter 6 FREQUENCY INVERTER
IDENTIFICATION on page 6-1.
Description:
It defines the rated motor current. Parameter P401 must be set according to the information on the motor
nameplate, taking into account the motor voltage.
✓
NOTE!
It is not recommended setting the motor rated current greater than inverter rated current (P295).
8-34 | CFW300
MOTOR CONTROL
Adjustable 0 = No Factory 0
Range: 1 = Yes Setting:
Properties: cfg, VVW
Description:
It allows the self-tuning of the VVW mode, where the motor stator resistance is measured. The self-tuning can only
be activated via HMI, and it can be interrupted at any time with the key.
During the self-tuning, the bar graph shows the progress of the operation and the motor remains still, because a
DC signal is sent to measure the stator resistance.
If the estimated value of the motor stator resistance is too high for the inverter used (for example: motor not
connected or motor too small for the inverter) the inverter indicates fault F033.
At the end of the self-tuning process, the measured motor stator resistance is saved in P409.
✓
NOTE!
The self-tuning will not run if the inverter is in Alarm or Fault.
CFW300 | 8-35
MOTOR CONTROL
8-36 | CFW300
I/O
9 I/O
This chapter contains the parameters for setting the inverter inputs and outputs. This setting depends on the
accessory connected to the product.
✓
NOTE!
The inverter HMI only displays the parameters related to the resources available in the accessory
connected to the product.
For example, the use of an external frequency reference is possible via the analogue inputs. The details for this
configuration are described in the following parameters.
Each analog input of the inverter is defined by the steps of calculation of Signal, Offset, Gain, Filter, Function and
Value AIx, as shown in Figure 9.1 on page 9-1.
Input
AI1 AI1 - P018
AI2(*) AI2 - P019
Filter
Signal Gain Function
AI1 - P233 AI1 - P232 AI1 - P231
AI2 - P238 AI2 - P237 AI2 - P236
AI1 - P235
Offset AI2 - P240 Value AIx
AI1 - P234 (internal)
AI2 - P239
9
P018 - AI1 Value
CFW300 | 9-1
I/O
If the parameter is configured as Inactive (P230 = 0), the signal in the analog inputs will actuate on the frequency
reference from the minimum point (0 V / 0 mA / 4 mA or 10 V / 20 mA), and it will be directly related to the minimum
frequency set in P133. Check Figure 9.2 on page 9-2.
If the parameter is set as Active (P230 = 1), the signal in the analog inputs will have a dead zone, where the frequency
reference remains at the Minimum frequency value (P133), even with the variation of the input signal. Check Figure
9.2 on page 9-2.
Reference Reference
P134 P134
P133 P133
Figure 9.2: (a) and (b) Actuation of the analog inputs with dead zone
is also necessary to configure parameters P221 and/or P222 by selecting the analog input. For further details, see
the description of those parameters in Chapter 7 COMMAND AND REFERENCES on page 7-1.
Option 4 (PTC) configures the input to monitor the motor temperature. For further details on this function, refer to
Section 10.3 PROTECTIONS on page 10-3.
Option 7 (PLC Use), as well as options 8 to 15, configures the input to be used by the programming done in the
memory area reserved for the SoftPLC function. For further details, refer to the help menu of the WPS software.
Options 16 and 17 configure the input for the use of the PID Controller application (P903 = 1). For further details,
see Chapter 14 APPLICATIONS on page 14-1.
Adjustable 0 = 0 to 10 V / 20 mA Factory 0
Range: 1 = 4 to 20 mA Setting:
2 = 10 V / 20 mA to 0
3 = 20 to 4 mA
9
Description:
It configures the signal type (if current or voltage) that will be read in each analog input, as well as its variation range.
In options 2 and 3 of the parameters, the reference is inverse, that is, the maximum frequency is obtained with the
minimum reference.
Pay attention to the connections of the analog input with voltage or current signal according to the inverter used.
For analog inputs on expansion accessories, refer to the installation, configuration, and operation guide of the I/O
expansion accessory used.
CFW300 | 9-3
I/O
( )
AIx(mA)
0 to 20 mA 0 AIx(%) = x (100.0 %) + offset x gain
20 mA
( )
AIx(mA) - 4 mA
4 to 20 mA 1 AIx(%) = x (100.0 %) + offset x gain
16 mA
( )
AIx(V)
10 to 0 V 2 AIx(%) = 100 % - x (100.0 %) + offset x gain
10 V
( )
AIx(mA)
20 to 0 mA 2 AIx(%) = 100 % - x (100.0 %) + offset x gain
20 mA
( )
AIx(mA) - 4 mA
20 to 4 mA 3 AIx(%) = 100 % - x (100.0 %) + offset x gain
16 mA
For example: AIx = 5 V, offset = -70.0 %, gain = 1.000, with signal of 0 to 10 V, that is, AIxini = 0 and AIxFE = 10.
( )
5
AIx(%) = x (100.0 %) + (-70 %) x 1.000 = -20.0 %
10
Another example: AIx = 12 mA, offset = -80.0 %, gain = 1.000, with signal of 4 to 20 mA, that is, AIxini = 4 and
AIxFE = 16.
( )
12 - 4
AIx(%) = x (100.0 %) + (-80 %) x 1.000 = -30.0 %
16
9 AIx = -30.0 % means that the motor will spin forward with a reference in module equal to 30.0 % of P134, if the
signal AIx function is “Frequency Reference”.
In the case of filter parameters (P235), the value set corresponds to the time constant used to filter the input signal
read. Therefore, the filter response time is around three times the value of this time constant.
9-4 | CFW300
I/O
Depending on the inverter (see the user’s manual), there is an exclusive input to connecting an external temperature
sensor, in some cases it is an I/O of the inverter itself, in others, the sensor connection is via an expansion module.
The parameter to read the temperature is described below.
✓
NOTE!
When the external sensor is NTC, which is disconnected from the accessory, the frequency inverter will
display 999 °C (1830 °F) in parameter P375. If the connection pins of the NTC (accessory connector)
are shorted, the value indicated on P375 will be 0 °C (32 °F).
The IOP accessory provides the potentiometer signal value for the frequency inverter. The steps to calculate this
value are indicated in the block diagram of the Figure 9.3 on page 9-5. 9
Value
P020
Filter
Input Gain Function
IOP P242 P245 P241
The AIP value can be used as a frequency reference or accessed by the WPS software. The details for the possible
configurations are described in the following parameters.
Description:
It indicates the analog signal value of the AIP potentiometer as a percentage of the full scale. The indicated values
are obtained after the offset action and the multiplication by the gain.
9
P244 - Potentiometer Signal Offset
The analog output (AOx) is configured by means of three types of parameters: Function, Gain and Signal, according
to the block diagram in Figure 9.4 on page 9-7.
9-6 | CFW300
I/O
The quantity of analog outputs depends on the expansion accessory IO’s. For further details, refer to the installation,
configuration and operation guide of the IO’s expansion accessory used.
AO1 - P014
AO2 - P015
Function Signal
Gain
AO1 - P251 AO1 - P253
AO1 - P252
AO2 - P254 AO2 - P256
AO2 - P255
Value
AO1(*)
AO2(*)
(*) Control terminals available on the accessory.
CFW300 | 9-7
I/O
(*) For further details refer the Chapter 14 APPLICATIONS on page 14-1.
9-8 | CFW300
I/O
Description:
It defines the analog output gain according to the equations of Table 9.3 on page 9-9.
Adjustable 0 = 0 to 10 V Factory 0
Range: 1 = 0 to 20 mA Setting:
2 = 4 to 20 mA
3 = 10 to 0 V
4 = 20 to 0 mA
5 = 20 to 4 mA
Description:
It configures if the analog outputs signal will be in current or voltage, with direct or reverse reference.
Table 9.3 on page 9-9 below summarizes the configuration and equation of the analog output, where the relationship
between the analog output function and the full scale is defined by P251 (AO1) or P256 (AO2), as per Table 9.2 on
page 9-8.
( )
function
0 to 20 mA 1 AOx(%) = x gain x 20 mA
scale
( )
function
4 to 20 mA 2 AOx(%) = x gain x 16 mA + 4 mA
scale
( ) 9
function
10 to 0 V 3 AOx(%) = 10 V - x gain x 10 V
scale
( )
function
20 to 0 mA 4 AOx(%) = 20 mA - x gain x 20 mA
scale
( )
function
20 to 4 mA 5 AOx(%) = 20 mA - x gain x 16 mA
scale
CFW300 | 9-9
I/O
description, refer to the communication manual (User) according to the interface used. These manuals are they are
available for download on the website: www.weg.net.
A frequency input consists of a fast digital input able to convert the frequency of the pulses in the input into a
proportional signal with 15-bit resolution. After the conversion, this signal is used as an analog signal for frequency
reference, process variable, for example.
According to the block diagram of Figure 9.5 on page 9-10, the signal in frequency is converted into a digital
quantity in 15 bits by means of the block “Calc. Hz / %”, where parameters P248 and P250 define the input signal
frequency band, while parameter P022 shows the frequency of the pulses in Hz.
Signal FI
(via DIx)
FI(Hz) - P022
FI (Hz)
Calc. Hz / %
(Hz)
Filter
P248
100 (%)
Offset
FI - P249 Value FIx Function
(internal) FI - P246
Digital input DIx is pre-defined for frequency input via parameter P246, with operating capacity in a wide band from
1 to 3000 Hz.
Parameters P248 and P250 determine the operation range of the frequency input (FI), while parameters P249 and
9 P247 determine the offset and gain, respectively, according to with the equation:
(( ) )
FI (Hz) - P248
FI = x (100 %) + P249 x P247
P250 - P248
For example, FI = 2000 Hz, P248 = 1000 Hz, P250 = 3000 Hz, P249 = -70.0 % and P247 = 1.000, thus:
(( ) )
2000 - 1000
FI = x (100 %) - 70 % x 1.000 = -20.0 %
3000 - 1000
The value FI = -20.0 % means that the motor will run in the opposite direction with a reference in module equal
20.0 % of P134, with the function of the FI signal for “Frequency Reference” (P221 = 4).
When P246 = 3, the digital input DI3 is defined for frequency input, regardless the value of P265, with operating
capacity in the band from 0 to 3000 Hz in 10 Vpp.
The time constant of the digital filter for the frequency input is defined by means of parameter P245.
P022 - FI Value in Hz
9-10 | CFW300
I/O
✓
NOTE!
The operation of parameters P022 as well as of the frequency input, depends on the configuration of
the parameter P246.
9
Adjustable 1 to 3000 Hz Factory 100 Hz
Range: Setting:
Description:
It defines the minimum value of the frequency input.
CFW300 | 9-11
I/O
✓
NOTE!
Parameter P012 requires the user to know the conversion between binary and hexadecimal numerical
system.
9-12 | CFW300
I/O
CFW300 | 9-13
I/O
(*) For further details refer the Chapter 14 APPLICATIONS on page 14-1.
9-14 | CFW300
I/O
a) RUN/STOP
It enables or disables the motor rotation through the acceleration and deceleration ramp (Figure 9.6 on page
9-15).
Acceleration Deceleration
ramp ramp
Output
frequency
Time
Active
DIx Inactive
Time
Figure 9.6: Example of the Run/Stop function
b) GENERAL ENABLE
It enables the motor rotation through the acceleration ramp and disables it by cutting off the pulses
immediately; the motor stops by inertia (Figure 9.7 on page 9-15).
Output 9
frequency
Time
Active
DIx Inactive
Time
Figure 9.7: Example of the General Enable function
c) QUICK STOP
When inactive, it disables the inverter by the emergency deceleration (P107) (Figure 9.8 on page 9-15).
Acceleration
P107 - Deceleration
ramp
ramp
Output
frequency
Time
Active
DIx Inactive
Time
Figure 9.8: Example of the Quick Stop function
CFW300 | 9-15
I/O
d) FORWARD/REVERSE COMMAND
This function is the combination of two DIS: one programmed for forward run and the other for reverse run
(Figure 9.9 on page 9-16).
Active
DIx - Forward Active
Time
Active
DIx - Reverse Active
Time
Output
Forward
frequency
Reverse Time
e) START/STOP
This function tries to reproduce the activation of a three-wire direct start with retention contact, where a pulse
in the DIx-Start enables the motor spin while the Dlx-Stop is active (Figure 9.10 on page 9-16).
Active
Output
frequency
Time
Figure 9.10: Example of the Start/Stop
✓
NOTE!
All the digital inputs set for General Enable, Fast Stop, Forward Run/Reverse Run and Start/Stop
must be in the “Active” state so that the inverter can enable the motor run.
f) DIRECTION OF ROTATION
If the DIx is Inactive, the Direction of Rotation is Forward, otherwise, the direction of rotation will be reverse
(Figure 9.11 on page 9-17).
9-16 | CFW300
I/O
Forward
Output
frequency
Time
Reverse
Active
DIx Inactive
Time
Figure 9.11: Example of the Direction of Rotation function
g) LOCAL/REMOTE
If DIx is inactive, the Local command is selected, reverse the Remote command is selected.
h) JOG
The JOG command is the combination of the Run/Stop command with a speed reference via parameter P122
(Figure 9.12 on page 9-17).
JOG frequency
Acceleration
(P122)
ramp
Output Deceleration
frequency ramp
Time
DIx - Active
Run/Stop Inactive
Time
Active
DIx - JOG Inactive 9
Time
DIx - Active
General Enable Inactive
Time
Figure 9.12: Example of the JOG function
i) ELECTRONIC POTENTIOMETER
The E.P. function enables the setting of the speed via digital inputs programmed for Accelerate E.P. and
Decelerate E.P. (Figure 9.13 on page 9-18). The basic principle of this function is similar to the sound volume
and intensity control of electronic appliances.
The operation of the E.P. function is also affected by the behavior of parameter P120, that is, if P120 = 0 the
E.P. reference initial value will be P133; if P120 = 1 the initial value will be the last reference value before the
disabling of the inverter, and if P120 = 2, the initial value will be the reference via P121 keys.
CFW300 | 9-17
I/O
DIx - Accelerate
RAMP Reference
DIx - Decelerate
P133
Output
frequency
Active Time
DIx - Accelerate
Inactive
Reset Time
Active
DIx - Decelerate
Inactive
Active Time
j) MULTISPEED
The Multispeed reference, as described in Section 7.2 SPEED REFERENCE on page 7-6, enables, by means
of the combination of up to three digital inputs, the selection of one from eight reference levels predefined in
parameters P124 to P131.
For further details, refer to Chapter 7 COMMAND AND REFERENCES on page 7-1.
k) 2nd RAMPA
If DIx is inactive, the inverter uses the default ramp by P100 and P101, otherwise, it will use the 2nd Ramp by
P102 and P103 (Figure 9.14 on page 9-18).
9
Active
Active
P100 P101
Output
frequency
Time
Figure 9.14: Example of the 2nd Ramp function
l) NO EXTERNAL ALARM
If DIx is inactive, the inverter will activate the external alarm A090.
m) NO EXTERNAL FAULT
If DIx is inactive, the inverter will activate the external fault F091. In this case, the PWM pulses are disabled
immediately.
9-18 | CFW300
I/O
n) FAULT RESET
Once the inverter is with the fault state active, and the fault origin condition is no longer active. The reset of
the fault state will occur when the DIx set for this function is active.
p) LOCK PROG
When the DIx input is active, parameters cannot be changed, no matter the values set in P000 and P200.
When the DIx input is Inactive, the modification of parameters will depend on the values set in P000 and
P200.
P134
(Fmax)
P133 P133
(Fmin) (Fmin)
Output
frequency
Time
Active
Pulse
DIx - Accelerate/ Turn ON
Turn ON Inactive
Time
Active
Pulse
DIx - Decelerate/ Turn OFF
Turn OFF Inactive
Time 9
Figure 9.15: Example of the Accelerate Turn ON / Decelerate Turn OFF
r) STOP
Only on pulse in the DIx disables the inverter (Figure 9.16 on page 9-19).
Deceleration
ramp
Output
frequency
Time
Active
s) SAFETY SWITCH
Only one inactive pulse in the DIx disables the inverter (Figure 9.17 on page 9-20).
CFW300 | 9-19
I/O
Deceleration
Output ramp
frequency
Time
Active
DIx - Safety
switch Inactive
Time
The IOADR accessory uses an infrared remote control to control the inverter. The RC-5 protocol (Philips) was used
for the communication of the control with the accessory. The information on the control/selection of remote control
is available in the parameters below.
The IOAENC expansion module makes it possible to connect an incremental encoder to the frequency inverter.
The speed (RPM) and pulse count are available to user by parameters.
Below is a detailed description of the parameters for the encoder input.
Adjustable 0 = No Factory 0
Range: 1 = Yes Setting:
Properties: cfg
Description:
It allows to reset the pulse counter to synchronize the counter aiming to synchronize the minimum or maximum
count at the parameter P039 - Encoder Pulse Counter, with the application limits (limit switches).
This parameter starts with zero value at the frequency inverter power-on. When adjusted to one (P191 = 1) the
function is activated. After the function turn on, the parameter P039 is cleared or setted up with maximum count
value (9999), according with the direction of rotation.
At the end of P039 clearing, the value of parameter, P191, returns to zero, allowing perform the process again, if
necessary.
CFW300 | 9-21
I/O
✓
NOTE!
The encoder input is not used to motor vector control, and must be applied when there is no
requirement to high performance.
The frequency inverter can activate relay digital outputs available at product and/or accessory. The parameter
configuration of the digital outputs behaves as described in detail below.
✓
NOTE!
Parameter P013 requires the user to know the conversion between binary and hexadecimal numerical
system.
9-22 | CFW300
I/O
CFW300 | 9-23
I/O
(*) For further details refer the Chapter 13 SOFTPLC on page 13-1.
P281 - Fx Frequency
9-24 | CFW300
I/O
P282 - Fx Hysteresis
P290 - Ix Current
P293 - Tx Torque
CFW300 | 9-25
I/O
9-26 | CFW300
FAULTS AND ALARMS
The problem detection structure in the inverter is based on the fault and alarm indication.
In case of fault, the locking the IGBTs and motor stop by inertia will occur.
The alarm works as a warning for the user of critical operating conditions and that may cause a fault if the situation
is not corrected.
The inverter is able to store a set of data on the last three faults occurred, such as: fault number, current (P003),
DC link voltage (P004), output frequency (P005), power module temperature (P030).
CFW300 | 10-1
FAULTS AND ALARMS
Description:
It indicates the DC link voltage at the moment of the last occurred fault.
The parameters related to the control of the motor protections of operation and the inverter are in this group.
✓
NOTE!
The function auto-reset is locked if the same fault occurs three times in a row within 30 seconds after
the reset.
10-2 | CFW300
FAULTS AND ALARMS
10.3 PROTECTIONS
This section contains information on the internal protections of the inverters and the motors. Refer to the user’s
manual for further information.
10.3.1 Inverter
The inverter has several levels of internal protection. Among them, we can point out:
The DC link voltage is constantly compared to the maximum and minimum values according to the inverter power
supply, as shown in Table 10.1 on page 10-3.
The temperature of the power module is read via internal temperature sensor and displayed in parameter P030
(more information on Chapter 11 READ on page 11-1. The temperature controlled by a fan according to parameter
P352.
10.3.2 Motor
The inverter has a function to protect the motor from overtemperature by indicating fault F078. The motor must
have a triple PTC type temperature sensor. The sensor can be read through the analog inputs.
For the reading of the PTC, it is necessary to configure it for current input and select the option “4 = PTC” in P231
or P236. Connect the PTC between the supply +10 Vdc and the analog input.
The analog input reads the PTC resistance and compares it to the limits for the fault. When those values are
exceeded, fault F078 is indicated. As shown in Table 10.3 on page 10-4.
CFW300 | 10-3
FAULTS AND ALARMS
WARNING!
! The PTC must have reinforced insulation of the live parts of the motor and other installations.
✓
NOTE!
For this function to work properly, it is important to keep the gain(s) and offset(s) of the analog inputs
at the factory setting values.
Figure 10.1 on page 10-4 shows the connection of the PTC to the inverter terminals via analog input.
+ 10 V
PTC
AIx (0 .. 4 to 20 mA)
10-4 | CFW300
FAULTS AND ALARMS
2,5
2 Region of overload
Overload current
Output current
1,5
0,5
0
0 60 120 180 240 300
Time (s)
✓
NOTE!
In order to ensure greater protection in case of de-energization of the inverter, this function keeps the
information regarding the motor thermal image in a non-volatile memory area of the inverter. Thus,
after the inverter energization, the function will use the saved value of the thermal image to execute a
new overload assessment.
CFW300 | 10-5
FAULTS AND ALARMS
10
10-6 | CFW300
READ
11 READ
It is important to point out that all the parameters of this group can only be viewed on the HMI display, and cannot
be changed by the user.
11
Adjustable 0 to 828 V Factory
Range: Setting:
Properties: ro
Description:
It indicates the DC link direct current voltage in (V).
CFW300 | 11-1
READ
It indicates the real frequency instantly applied to the motor in Hertz (Hz).
11
11-2 | CFW300
READ
7 Reserved - -
11
CFW300 | 11-3
READ
In addition to the indication of alarm A050, the overtemperature protection gradually reduces the switching
frequency to 2.5 kHz. This overtemperature protection characteristic can be disabled in the control configuration
parameter P397.
✓
NOTE!
The default setting of P397 meets most application needs of the inverter. Therefore, avoid modifying
its content without knowing the related consequences. If you are not sure, contact WEG Technical
Assistance before changing P397.
11
Adjustable 0 to FFFF (hexa) Factory
Range: Setting:
Properties: ro
Description:
It indicates the total number of hours that the heatsink fan remained connected. This value is kept even when the
inverter is disconnected.
Adjustable 0 to 33 Factory
Range: Setting:
Properties: ro
Description:
11-4 | CFW300
READ
It indicates the source situation of the CONFIG mode. The Table 11.3 on page 11-5 describes the CONFIG status.
11
CFW300 | 11-5
READ
11-6 | CFW300
READ
CFW300 | 11-7
READ
11
11-8 | CFW300
COMMUNICATION
12 COMMUNICATION
In order to exchange information via communication network, the frequency inverter features several standardized
communication protocols, such as Modbus (RTU and TCP), CANopen, DeviceNet, Profibus DP and Ethernet IP.
For further details referring to the inverter configuration to operate in those protocols, refer to the inverter user’s
manual for communication with the desired network.
See below the parameters related to the states and commands through the communication networks available for
the frequency inverter.
CFW300 | 12-1
COMMUNICATION
12.2 SERIAL
See below the frequency inverter parameters that are directly related to the Modbus RTU communication.
12
P308 - Serial Address
12-2 | CFW300
COMMUNICATION
12.3 BLUETOOTH
See below the parameters to configure and operate the Bluetooth interface. For the correct configuration of this
interface, it is necessary to configure properly the parameters of the Section 12.2 SERIAL on page 12-2.
CFW300 | 12-3
COMMUNICATION
✓
NOTE!
Parameter P770 is only available with the bluetooth accessory connected.
✓
NOTE!
Parameter P771 is only available with the bluetooth accessory connected.
12.4 BACNET
See below the parameters to configure and operate the BACnet communication.
12-4 | CFW300
COMMUNICATION
See below the parameters to configure and operate the CAN interface.
CFW300 | 12-5
COMMUNICATION
12-6 | CFW300
COMMUNICATION
CFW300 | 12-7
COMMUNICATION
12.6 PROFIBUS DP
See below the parameters to configure and operate the Profibus interface.
12-8 | CFW300
COMMUNICATION
12.7 ETHERNET
See below the parameters to configure and operate the Ethernet interface.
P851 - IP Address 1
P852 - IP Address 2
P853 - IP Address 3
CFW300 | 12-9
COMMUNICATION
P854 - IP Address 4
12
P856 - Gateway 1
P857 - Gateway 2
P858 - Gateway 3
12-10 | CFW300
COMMUNICATION
P859 - Gateway 4
Adjustable 0 to 4 Factory
Range: Setting:
Properties: ro
12
P870 - EIP: Communication Status
CFW300 | 12-11
COMMUNICATION
12-12 | CFW300
COMMUNICATION
12
CFW300 | 12-13
COMMUNICATION
12
12-14 | CFW300
SOFTPLC
13 SOFTPLC
The SoftPLC function allows the inverter to assume PLC (Programmable Logical Controller). For further details
regarding the programming of those functions in the inverter, refer to the “Help” menu of the WPS software.
See below the parameters related to the SoftPLC commands and states.
CFW300 | 13-1
SOFTPLC
WARNING!
! It is recommended to load the factory setting (P204 = 5 or 6) after alternating between user’s
application and PID controller application.
13.2 USER
13-2 | CFW300
SOFTPLC
CFW300 | 13-3
SOFTPLC
✓
NOTE!
Parameters P910 to P959 can only be viewed when there are application installed.
13
13-4 | CFW300
APPLICATIONS
14 APPLICATIONS
Using the SoftPLC function of the inverter, it is possible to develop an application (or functionality) in ladder language
and include it in the inverter software.
Parameter P903 allows selecting the application and uploading it to the SoftPLC execution area of the inverter.
The frequency inverter has the following application already implanted:
PID Controller.
The PID controller application can be used to control a process in closed loop. This application adds a proportional,
integral and derivative controller superimposed to the regular speed control of the frequency inverter having selection
options:
Basically, the PID controller application compares the control setpoint to the process variable and controls the
motor speed to try to eliminate any errors so as to keep the process variable equal to the control setpoint required
by the user. The setting of the gains P, I and D determine the speed at which the inverter will respond to eliminate
that error. See the PID controller block diagram below.
Process variable
AI1
P916
AI2
AI1 - AI2
Selection
via P921 P922, P923
The example below defines the terms used by the PID controller application.
CFW300 | 14-1
APPLICATIONS
An electric pump used in a water pumping system in which the pressure must be controlled at the pump output pipe.
A pressure transducer is installed on the pipe and provides an analog feedback signal to the inverter proportional to
the water pressure. That signal is called process variable and can be viewed in parameter P916. A control setpoint
is programmed in the inverter via HMI (P911), or via analog input (AI1 or AI2), or via electronic potentiometer
function (DI3 and DI4), or via logical combination of digital inputs DI3 and DI4 according to the control setpoint
source defined in P920. The control setpoint is the water pressure which the pump must produce regardless of
the demand variations in the pump output at any moment.
In order to enable the operation of the PID controller application, it is necessary to program the speed reference
for the SoftPLC function, that is, parameter P221 or P222 in 12 = SoftPLC, and select the PID controller control
action in P928 for direct action (=1) or reverse action (=2), thus enabling the PID operation. Otherwise, the alarm
message “A790: Speed reference source (P221 or P222) not programmed for the SoftPLC (12)” will be generated.
The functionalities that can be programmed in the analog and digital inputs and outputs are shown in the Table
14.1 on page 14-2.
Table 14.1: Functionalities and programming of the analog and digital inputs and outputs
Analog Inputs AI1 (P231) and AI2 (P236)
Control Setpoint = 16
Process Variable = 17
Analog Outputs AO1 (P251) and AO2 (P254)
Control Setpoint = 29
Process Variable = 30
Digital Inputs DI2 (P264) to DI4 (P266)
Manual / Automatic PID (DI2) = 51
Increase Setpoint Command (PE) (DI3) = 52
Decrease Setpoint Command (PE) (DI4) = 53
1st DI of the Control Setpoint (DI3) = 54
2nd DI of the Control Setpoint (DI4) = 55
Digital Outputs DO1 (P275) to DO4 (P278)
Process Variable Low Level (A760/F761) = 46
Process Variable High Level (A762/F763) = 47
The control setpoint source of the PID controller is defined in parameter P920, and it may be: via parameter P911,
which can be changed via HMI (or communication networks); via analog input AI1 or AI2, being parameter P231
(AI1) or P236 (AI2) previously programmed to 16 = Control Setpoint so that it is enabled for operation; via Electronic
Potentiometer (EP) through increase and decrease commands in digital inputs DI3 and DI4, being parameter P265
(DI3) previously programmed to 51 = Increase Setpoint Command (EP) and P266 (DI4) to 52 = Decrease Setpoint
Command (EP); via logical combination of digital inputs, with the selection of up to four control setpoints, being
parameter P265 (DI3) previously programmed to 53 = 1st DI for Control Setpoint and P266 (DI4) to 54 = 2nd DI for
Control Setpoint.
The value of the present control setpoint of the PID controller (P911) can be indicated via analog output AO1 or
AO2, being necessary to program P251 (AO1) or P254 (AO2) to 29 = Control Setpoint. The variable full scale is
100.0 % and corresponds to 10 V or 20 mA.
The source of the PID controller process variable is defined in parameter P921, and it can be via analog input AI1
and/or AI2, being then parameter P231 (AI1) and/or P236 (AI2) previously programmed to 17 = Process Variable.
The value of the PID controller process variable (P916) can be indicated via analog output AO1 or AO2, being
necessary to program P251 (AO1) or P254 (AO2) to 30 = Process Variable. The variable full scale is 100.0 % and
corresponds to 10 V or 20 mA.
The PID controller operation mode is defined in parameter P929, which can be manual, always automatic or via a
Manual/Automatic command through digital input DI2, being then parameter P264 (DI2) previously programmed
to 50 = Man/Auto PID Selection. Digital input DI2 programmed to PID in Manual/Automatic is active while it is at
logical level “1”, indicating automatic command, and inactive at logical level “0”, indicating manual command.
14
Digital outputs DO1 to DO4 can be programmed to indicated alarm/fault conditions for low level or high level of the
process variable (PV), seeing that one of the respective parameters (P275 to P278) must be programmed to 46 =
Process Variable Low Level (equivalent to PV<PVy) or 47 = Process Variable High Level (equivalent to PV>PVx).
14-2 | CFW300
APPLICATIONS
14.1.1 Start-Up
See below the required steps to put the PID controller application into operation.
✓
NOTE!
For the PID controller application to work properly, it essential to check if the inverter is configured
properly to drive the motor at the desired speed. In order to do so, check the following settings:
Acceleration and deceleration ramps (P100 to P101).
Current limit (P135) for V/f and VVW control modes.
Torque boost (P136 and P137) and slip compensation (P138) if in the V/f control mode.
Configuring the PID Controller Application The PID controller application will be configured according to the
example shown below, where:
Digital input DI1 will be used for the Run/Stop command in local mode.
The PID controller process variable (PV) will be connected to analog input AI1 in the scale of 4-20 mA, where 4
mA is equal to 0 bar and 20 mA is equal to 4.0 bar.
The PID controller control setpoint (SP) will be via HMI (keys).
Pressure
Fuses Transducer
Line
Frequency
inverter
Process
Shield
14
CFW300 | 14-3
APPLICATIONS
Parameters P931, P932, P933 and P934 must be set according to the response of the process to be controlled.
See below suggestions for initial values of sampling time and gain setting for the PID controller according to the
process to be controlled.
Putting into Operation Check the state of the PID controller application in parameter P900. Value equal to 4
indicates the application is already in operation. Value equal to 3 indicates the application is stopped; therefore, it
14-4 | CFW300
APPLICATIONS
is necessary to change the command value for the SoftPLC in parameter P901 to 1 (execute application). Value
different from 3 or 4 indicates the application cannot go into operation. For further details, refer to the inverter
SoftPLC manual.
1. Manual Operation (DI2 open): keeping DI2 open (Manual), check the indication of the process variable on the
HMI (P916) based on an external measurement of the sensor signal (transducer) in analog input AI1.
Then, changes the manual setpoint value of the PID controller (P918) until reaching the desired process
variable value. Check if the control setpoint value (P911) is set to this value, and then put the PID controller
into the automatic mode.
✓
NOTE!
The PID controller only begins the speed regulation when the motor reaches the minimum speed
programmed in P133, as it was configured to operate from 0.0 to 100.0 %, where 0.0 %
corresponds to the minimum speed programmed in P133, and 100.0 % corresponds to the
maximum speed programmed in P134.
2. Automatic Operation (DI2 closed): close DI2 and make the dynamic adjustment of the PID controller, that
is, of the proportional (P931), integral (P932) and derivative (P933) gains, checking if the regulation is being
done correctly. In order to do so, just compare the control setpoint and the process variable and check if the
values are close. Also check how fast the motor responds to the oscillations of the process variable.
It is important to point out that the setting of the PID controller gains is a step that requires some attempt
and error procedure to reach the desired response time. If the system responds quickly and oscillates close
to the control setpoint, then the proportional gain is too high. If the system responds slowly and it takes a
long time to reach the control setpoint, the proportional gain is too low and must be increased. In case the
process variable does not reach the required value (control setpoint), the integral gain must be set then.
The PID controller implemented on the inverter is academic. See below the equations that characterize the
Academic PID controller, which is the base of this function algorithm.
The transfer function in the frequency domain of the Academic PID controller is:
[ ]
1
y(s) = Kp x e(s) x 1 + + sTd
sTi
Replacing the integrator by a sum and the derivative by the incremental quotient, we obtain the approximation for
the discrete (recursive) transfer equation presented below:
[ ]
y(k) = i(k − 1) + Kp (1 + Ki Ta + Kd /Ta )e(k) − (Kd /T a)E(k − 1) x 10
Where:
y(k): present output of the PID controller; it may vary from 0.0 to 100.0 %.
i(k-1): integral value in the previous state of the PID controller.
Kp : Proportional gain = P931.
Ki : Integral gain = P932 = [1 / Ti (s)].
Kd : Differential gain = P933 = [Td (s)].
Ta : sampling period of the PID controller = P934.
e(k): present error, being [SP(k) - PV(k)] for direct action, and [PV(k)] - SP(k)] for reverse action.
e(k-1): previous error, being [SP(k-1) - PV(k-1)] for direct action, and [PV(k-1)] - SP(k-1)] for reverse action.
SP: present control setpoint of the PID controller.
PV: process variable of the PID controller, read through the analog inputs (AI1 and AI2).
14
14.1.3 Parameters
See below the description of the parameters related to the PID controller application.
CFW300 | 14-5
APPLICATIONS
✓
NOTE!
This parameter will be viewed according to the selection of the parameters for the SoftPLC engineering
unit (P510 and P511).
✓
NOTE!
These parameters will be viewed according to the selection of the parameters for the SoftPLC
engineering unit (P510 and P511).
14-6 | CFW300
APPLICATIONS
Description:
It indicates the value of the PID controller process variable according to the source defined in P921 and scale
defined in P922 and P923.
✓
NOTE!
This parameter will be viewed according to the selection of the parameters for the SoftPLC engineering
unit (P510 and P511).
The conversion of the value read by the analog input in percentage into the value of the process variable shown in
P916 according to the scale is done through the following formula:
P916 = [ValorAI(%) x (P923 - P922)] + [P922]
Table 14.4: Description of the logical status of the PID controller application
Bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Process Process Process Process PID controller
Function Reserved
Variable High Variable High Variable Low Variable Low in Manual Sleep Mode 14
Level Level Level Level or Active (A750)
(F763) (A762) (F761) (A760) Automatic
CFW300 | 14-7
APPLICATIONS
Bits Values
Bit 0 0: Inverter is not in the alarm condition
Sleep Mode Active (A750) 1: It indicates that the PID controller is in the sleep mode (A750)
Bit 1 0: PID controller operating in Manual mode
PID Controller in Manual or Automatic 1: PID controller operating in Automatic mode
Bit 2 0: Inverter is not in the alarm condition
Control Process Variable Low (A760) 1: It indicates that the control process variable (P916) is in low level (A760)
0: Inverter is not in the fault condition
Bit 3
1: It indicates that the inverter switched the motor off due to the control variable low
Fault for Control Process Variable Low Level (F761)
level (F761)
Bit 4 0: Inverter is not in the alarm condition
Control Process Variable High Level (A762) 1: It indicates that the control process variable (P916) is in high level (A762)
0: Inverter is not in the fault condition
Bit 5
1: It indicates that the inverter switched the motor off due to the control process
Fault for Control Process Variable High Level (F763)
variable high level (F763)
Bit 6
Reserved
Reserved
Bit 7
Reserved
Reserved
Bit 8
Reserved
Reserved
Bit 9
Reserved
Reserved
Bit 10
Reserved
Reserved
Bit 11
Reserved
Reserved
Bit 12
Reserved
Reserved
Bit 13
Reserved
Reserved
Bit 14
Reserved
Reserved
Bit 15
Reserved
Reserved
14
14-8 | CFW300
APPLICATIONS
When the control setpoint is via Electronic Potentiometer (EP) function (P920 = 3), the control setpoint of the PID
controller is adjusted by means of digital inputs DI3 and DI4, being DI3 to increase it and DI4 to decrease it.
Figure 14.3 on page 14-9 shows the operation of the EP function: when digital input DI3 is activated, the control
setpoint value (P911) is incremented, and when digital input DI4 is activated, the control setpoint value (P911) is
decremented. In case both digital inputs are activated at the same time, the value remains the same.
DI3 - increase SP
Ramp for
P911 - (control setpoint)
setpoint
DI4 - decrease SP
Active Time
Active Time
Sleep
Motor running (RUN) (A750)
Time
Figure 14.3: PID controller block diagram
When the control setpoint is via logical combination of digital inputs DI3 and DI4 (P920 = 4, 5 or 6), the following
truth table must be used so as to obtain the control setpoint of the PID controller in automatic mode.
Table 14.6: Truth table for the control setpoint via logical combination of digital inputs DI3 and DI4
P912 - Control P913 - Control P914 - Control P915 - Control
Setpoint 1 Setpoint 2 Setpoint 3 Setpoint 4
Digital input DI3 0 1 0 1
Digital input DI4 0 0 1 1
14
CFW300 | 14-9
APPLICATIONS
Table 14.7: Description of the source of the PID controller process variable
P921 Description
1 It defines that the control variable source will be the value read by AI1 and viewed in parameter P916
2 It defines that the control variable source will be the value read by AI2 and viewed in parameter
It defines that the control variable source will be the value read by AI1 minus the value read by AI2
3
that is, the difference between AI1 and AI2, and viewed in parameter P916
✓
NOTE!
This parameter will be viewed according to the selection of the parameters for the SoftPLC engineering
unit (P510 and P511).
✓
NOTE!
This parameter will be viewed according to the selection of the parameters for the SoftPLC engineering
unit (P510 and P511).
P924 - Value for Low Level Alarm for the Control Process Variable
14-10 | CFW300
APPLICATIONS
✓
NOTE!
Setting it to “0” disables the low level alarm and fault for the control process variable.
✓
NOTE!
This parameter will be viewed according to the selection of the parameters for the SoftPLC engineering
unit (P510 and P511).
P925 - Time for Low Level Fault for the Control Process Variable
✓
NOTE!
Setting it to “0.0 s” disables the low level fault for the control process variable.
P926 - Value for High Level Alarm for the Control Process Variable
✓
NOTE!
Setting it to “0” disables the high level alarm and fault for the control process variable.
✓
NOTE!
This parameter will be viewed according to the selection of the parameters for the SoftPLC engineering
unit (P510 and P511).
P927 - Time for High Level Fault for the Control Process Variable
14
✓
NOTE!
Setting it to “0.0 s” disables the high level fault for the control process variable.
CFW300 | 14-11
APPLICATIONS
✓
NOTE!
When enabling the PID controller, that is, changing the content of parameter P928 from 0 to 1 or
2 (with application running), the following parameters related to the PID controller application will be
loaded: P100, P101, P133, P134, P205, P207, P208, P209, P210, P213, P220, P221, P224, P231,
P232, P233, P234, P235, P263, P264, P510, P511, P911, P912, P913, P914, P915, P918, P920,
P921, P922, P923, P924, P925, P926, P927, P929, P930, P931, P932, P933, P934, P935, P936,
P937, P938, P939.
✓
NOTE!
The control action of the PID controller must be selected for direct mode when it is necessary to
increase the PID controller output in order to increase the process variable value. E.g.: Pump driven
by an inverter and filling a tank. For the level of the tank (process variable) to increase, it is necessary
that the flow increase, which is accomplished by increasing the speed of the motor.
The control action of the PID controller must be selected for reverse mode when it is necessary to
decrease the PID controller output in order to increase the process variable value. E.g.: Fan driven by
inverter cooling a refrigeration tower. When an increase in temperature is desired (process variable),
it is necessary to reduce the ventilation by reducing the motor speed.
14
14-12 | CFW300
APPLICATIONS
✓
NOTE!
The change from an operation mode to another with the motor running may cause disturbances
on the system control. That can be optimized according to the automatic adjustment mode of the
PID controller setpoint defined in parameter P930 together with the bumpless transfer characteristic
from the manual mode to the automatic mode of the PID block of the SoftPLC function. Bumpless
transfer is merely making the transfer from the manual mode to the automatic mode without causing
variation in the PID controller output. In other words, when the transition from the manual mode to the
automatic mode occurs, the PID controller output value in manual mode is used to start the integral
part of the PID controller in automatic mode. That ensures that the output will start from this value.
✓
NOTE!
The adjustment of the control setpoint in automatic mode is only valid when the control setpoint
source is HMI or communication networks (P920 = 0) or via the Electronic Potentiometer Function 14
(P920 = 3). For other control setpoint sources, the automatic adjustment is not executed.
CFW300 | 14-13
APPLICATIONS
✓
NOTE!
Table 14.3 on page 14-4 suggests setting values for the gains according to the process to be
controlled by the PID controller.
✓
NOTE!
Table 14.3 on page 14-4 suggests setting values for the sampling time according to the process to
be controlled by the PID controller.
This parameter group allows the user to set the operation conditions of the sleep mode.
Sleep Mode is a controlled system state in which the control demand is zero or almost zero, and, at this moment,
the motor driven by the frequency inverter may be switched off. That prevents the motor from running at a low
speed, doing little or nothing for the controlled system. Even if the motor is apparently OFF, the process variable
continues to be monitored so that, when necessary, the controlled system can start the motor again according to
the conditions of the wake up mode.
14
Wake Up Mode switches on the motor when the difference between the control process variable and the control
setpoint is greater than a certain programmed value.
14-14 | CFW300
APPLICATIONS
✓
NOTE!
The sleep mode only actuates if the PID controller is enabled and in the automatic mode.
DANGER!
! When the inverter is in the sleep mode, the motor may spin at any moment because of the process
conditions. If you wish to handle the motor or execute any kind of maintenance, power down the
inverter.
✓
NOTE!
This parameter will be viewed according to the selection of the parameters for the SoftPLC engineering
unit (P510 and P511).
✓
NOTE!
If, in the energization of the inverter, the “Run/Stop” command is active and the condition to Wake
Up is active, the time programmed in P937 will not be waited for, and thus the motor will be started
instantly.
CFW300 | 14-15
APPLICATIONS
✓
NOTE!
Setting it to “0.0 Hz” disables the sleep mode; that means the motor will be switched on or off
according to the state of the “Run/Stop” command.
✓
NOTE!
The alarm message “A750: Sleep Mode Active” will be shown on the HMI of the frequency inverter
warning that the motor is in the sleep mode.
Figure 14.4 on page 14-16 shows an analysis of the PID controller operation programmed with control action in
direct mode and configured for the Sleep Mode.
PROCESS VARIABLE
Figure 14.4: Operation of the PID controller with the sleep mode enabled
1. The Run/Stop command via digital input DI1 enables the starting of the motor. As the wake up condition was
not detected, it remains in sleep mode, and the motor remains stopped.
14 2. The process variable starts to decrease and becomes smaller than the deviation of the process variable
programmed to wake up (P936); at this moment, the time count to wake up (P937) begins.
3. The process variable remains smaller than the process variable deviation to wake up (P936), and the time to
wake up (P937) elapses; at this moment, the command to start the motor and control the system with its
speed variation is executed.
14-16 | CFW300
APPLICATIONS
4. The inverter accelerates the motor up to the minimum speed (P133). After that, the PID controller is enabled
and starts controlling the motor speed.
5. Then it is possible to control the process variable so that it reaches the control setpoint required by the user.
To that end, the PID controller output is incremented, making the motor speed increase until reaching the
control stabilization.
6. The value of the process variable remains above the required control setpoint due to a decrease in demand,
and the motor speed starts slowing down.
7. The value of the motor speed falls below the value to sleep (P938); the time count to activate the sleep mode
(P939) begins.
8. The motor speed remains below the value to sleep (P938), and the time to activate the sleep mode (P939)
elapses; at this moment, the command to switch off the motor is executed.
9. The motor is decelerated down to 0 Hz and remains stopped; at this moment the PID controller goes into the
sleep mode.
14
CFW300 | 14-17
APPLICATIONS
14
14-18 | CFW300
APPLICATION EXAMPLES
15 APPLICATION EXAMPLES
In this section some applications that use analog inputs are shown. Figure 15.1 on page 15-1 presents some
possible connections. The applications described here require load factory settings (P204 = 5 or 6) for correct
execution.
AIx (V)
or
AIx (mA) GND 10 V AIx (V) GND
Transducer Extern
Voltage or Current potentiometer
Electronic Potentiometer
plugin
Figure 15.1: Connections for analog inputs
The results for the equations presented in Section 9.1 ANALOG INPUTS in page 9-1 are shown on P018 or P020
according to the availability of analog inputs from the inverter. This readings can be used for options given by P231
or P236 or P241.
In case of speed reference function is selected by P231 or P236 or P241 = 0 this reference is going to be a
percentage of the maximum frequency(P134).
15
CFW300 | 15-1
APPLICATION EXAMPLES
This example describes an application where the analogic input signal corresponds to a frequency reference. The
total excursion of analogic signal represents to command the motor to run from its minimum to maximum frequency
as presented on Figure 15.2 on page 15-2. Table 15.1 on page 15-2 show parameters related to the correct setting.
Requirements:
Motor: 1 HP, 220 V, 2.9 A, 1725 rpm, 60 Hz
Min. Frequency = 0 Hz
Max. Frequency = 60 Hz
Programming:
Example:
Output
frequency
15
15-2 | CFW300
APPLICATION EXAMPLES
This example describes an application where the analogic input signal corresponds to a frequency reference. The
total excursion of analogic signal represents to command the motor to run from its minimum to maximum frequency
as presented on Figure 15.3 on page 15-3. In this example, maximum speed is over the nominal speed (or field
weakeaning speed). Table 15.2 on page 15-3 show parameters related to the correct setting.
Requirements:
Motor: 1 HP, 220 V, 2.9 A, 1725 rpm, 60 Hz
Min. Frequency = 0 Hz
Max. Frequency = 80 Hz
Programming:
Table 15.2: Parameters for application 2
Analog Input AI1 AI2 Potenciometer Value
Min. Frequency P133 0.0 Hz
Max. Frequency P134 80.0 Hz
Max. Output Voltage P142 100.0 %
Interm. Output Voltage P143 50.0 %
Field Weak. Freq. P145 60.0 Hz
Intermediate Freq. P146 30.0 Hz
Selection source P220 0
Reference source P221 = 1 P221 = 2 P221 = 3 According application*
Rotation sel. P223 0
Signal function P231 P236 P241 0
Gain P232 P237 P242 1.000
Input signal P233 P238 - According application**
Offset P234 P239 P244 0%
15
CFW300 | 15-3
APPLICATION EXAMPLES
This example describes an application where the analogic input signal corresponds to a frequency reference. The
total excursion of analogic signal represents to command the motor to run from its minimum to maximum frequency,
reversing the direction of rotation, as presented on Figure 15.4 on page 15-4. Table 15.3 on page 15-4 show
parameters related to the correct setting.
Requirements:
Motor: 1 HP, 220 V, 2.9 A, 1725 rpm, 60 Hz
Min. Frequency = -60 Hz (Reverse)
Max. Frequency = 60 Hz
Programming:
Table 15.3: Parameters for application 3
Analog Input AI1 AI2 Potenciometer Value
Min. Frequency P133 0.0 Hz
Max. Frequency P134 60.0 Hz
Max. Output Voltage P142 100.0 %
Interm. Output Voltage P143 50.0 %
Field Weak. Freq. P145 60.0 Hz
Intermediate Freq. P146 30.0 Hz
Selection source P220 0
Reference source P221 = 1 P221 = 2 P221 = 3 According application*
Rotation sel. P223 0
Signal function P231 P236 P241 0
Gain P232 P237 P242 2.000
Input signal P233 P238 - According application**
Offset P234 P239 P244 -50.0 %
15
15-4 | CFW300
APPLICATION EXAMPLES
In this example, the output stay in 0Hz through the first 2.5V of analogic signal. The rotation of the motor (reverse)
only happens if the Dead Zone parameter is disable (P230 = 0), as presented on Figure 15.5 on page 15-5. Table
15.4 on page 15-5 show parameters related to the correct setting.
Requirements:
Motor: 1 HP, 220 V, 2.9 A, 1725 rpm, 60 Hz
Min. Frequency = 0 Hz
Max. Frequency = 45 Hz
Programming:
Table 15.4: Parameters for application 4
Analog Input AI1 AI2 Potenciometer Value
Min. Frequency P133 0.0 Hz
Max. Frequency P134 60.0 Hz
Max. Output Voltage P142 100.0 %
Interm. Output Voltage P143 50.0 %
Field Weak. Freq. P145 60.0 Hz
Intermediate Freq. P146 30.0 Hz
Selection source P220 0
Reference source P221 = 1 P221 = 2 P221 = 3 According application*
Rotation sel. P223 0
Signal function P231 P236 P241 0
Gain P232 P237 P242 1.000
Input signal P233 P238 - According application**
Offset P234 P239 P244 -25.0 %
Dead Zone** P230 1
15
CFW300 | 15-5
APPLICATION EXAMPLES
This example describes an application where the analogic input signal corresponds to a frequency reference. The
total excursion of analogic signal represents to command the motor to run from its minimum to maximum frequency
as presented on Figure 15.6 on page 15-6. Here the analog input is inverted when compared to Application 1.
Table 15.5 on page 15-6 show parameters related to the correct setting.
Requirements:
Motor: 1 HP, 220 V, 2.9 A, 1725 rpm, 60 Hz
Min. Frequency = 0 Hz
Max. Frequency = 60 Hz
Programming:
Table 15.5: Parameters for application 5
Analog Input AI1 AI2 Potenciometer Value
Min. Frequency P133 0.0 Hz
Max. Frequency P134 60.0 Hz
Max. Output Voltage P142 100.0 %
Interm. Output Voltage P143 50.0 %
Field Weak. Freq. P145 60.0 Hz
Intermediate Freq. P146 30.0 Hz
Selection source P220 0
Reference source P221 = 1 P221 = 2 P221 = 3 According application*
Rotation sel. P223 = 0 P223 = 0 P223 = 1 According application
Signal function P231 P236 P241 0
Gain P232 P237 P242 1.000
Input signal P233 P238 - 2
Offset P234 = 0 % P239 = 0 % P244 = -100.0 % According application**
P133 (0 Hz) AIx Signal Output Freq. = P018 x P134 = -25.0% x 60.0 Hz = -15.0 Hz
0 ....................................... 10 V
0 ....................................... 20 mA
4 ....................................... 20 mA
10 V .................................... 0
20 mA ................................. 0
20 mA ............................... 4 mA
15
15-6 | CFW300
APPLICATION EXAMPLES
This example describes an application controlling a process in closed loop (PID Controller), as presented in Figure
15.7 on page 15-7. Table 15.6 on page 15-7 show parameters related to the correct setting.
Requirements:
The frequency inverter will be configured to operate in the local mode.
Digital input DI1 will be used for the Run/Stop command in local mode.
Digital input DI2 will be used to select the PID to Manual/Automatic.
The PID controller process variable (PV) will be connected to analog input AI1 in the scale of 4-20 mA, where
4 mA is equal to 0 bar (P922) and 20 mA is equal to 4.0 bar (P923).
The PID controller control setpoint (SP) will be via HMI (keys).
Example:
Pressure
Fuses Transducer
Line
Frequency
inverter
Process
Shield
Programming:
Table 15.6: Programming sequence of the PID controller application
Sequence Setting Action / Result
P903 1 = PID Controller It selects the PID controller application in the SoftPLC function of the inverter
P901 1 = Run Application It enables the execution of the PID controller application
P928 1 = Direct It selects the PID controller control action, thus enabling its operation and uploading, at this moment
the application default setting*
P133 40.0 Hz Minimum frequency
P134 60.0 Hz Maximum frequency
P233 1 = 4 to 20 mA Selection of the AI1 Signal Function
P911 2.00 Setting of the control Setpoint via HMI
P931 1.00 Proportional Gain of the PID controller
P932 5.00 Integral Gain of the PID controller
P933 0.00 Derivative Gain of the PID controller
15
CFW300 | 15-7
WEG Drives & Controls - Automation LTDA.
Jaraguá do Sul - SC - Brazil
Phone 55 (47) 3276-4000 - Fax 55 (47) 3276-4020
São Paulo - SP - Brazil
Phone 55 (11) 5053-2300 - Fax 55 (11) 5052-4212
automacao@weg.net
www.weg.net