Vuqua - Uv SHF 140
Vuqua - Uv SHF 140
Vuqua - Uv SHF 140
• Equipped to inactivate harmful microorganisms in water • Separate control panel with power isolation.
flows up to 290 GPM (65 m3/hr).
• Visual display of lamp life remaining and audible/visual
• Specially designed and tested Sterilume-HO lamps lamp change reminder.
provide consistent and reliable UV output over the entire
life of the lamp (9000 hours) to ensure continuous • Specialised 254nm UV intensity sensor available
purification. (SHFM models) with output to enable solenoid valve or
remote alarm.
• Superior quality 316 stainless steel chamber.
Replacement Parts
S740RL-4C UV Lamp – – – –
S950RL-4C UV Lamp – –
254NM-HF UV Sensor – – – –
BA-ICE-HF Controller
BA-ICE-M-HF Controller – – –
Specifications
MODEL
N. America SHF-140 SHF-180 SHF-290 SHFM-140 SHFM-180 SHFM-290
170 GPM (640 lpm) 210 GPM (790 lpm) 290 GPM (1098 lpm) 170 GPM (640 lpm) 210 GPM (790 lpm) 290 GPM (1098 lpm)
VIQUA Standard (30 mJ/cm2)
(38 m3/hr) (47 m3/hr) (65 m3/hr) (38 m3/hr) (47 m3/hr) (65 m3/hr)
125 GPM (470 lpm) 160 GPM (600 lpm) 215 GPM (813 lpm) 125 GPM (470 lpm) 160 GPM (600 lpm) 215 GPM (813 lpm)
NSF/EPA (40 mJ/cm2)
(28 m3/hr) (36 m3/hr) (48 m3/hr) (28 m3/hr) (36 m3/hr) (48 m3/hr)
DIMENSIONS
34” x 6” x 14” 42.5” x 6” x 14” 42.5” x 8” x 17” 34” x 6” x 14” 42.5” x 6” x 14” 42.5” x 8” x 17”
Chamber (86.4 cm x 15.2 cm x (107.3 cm x 15.2 cm (108 cm x 20.3 cm x (86.4 cm x 15.2 cm x (107.3 cm x 15.2 cm (108 cm x 20.3 cm x
35.6 cm) x 35.6 cm) 43.5 cm) 35.6 cm) x 35.6 cm) 43.5 cm)
17.5” x 19.5” x 8.2” 17.5” x 19.5” x 8.2” 17.5” x 19.5” x 8.2” 17.5” x 19.5” x 8.2” 17.5” x 19.5” x 8.2” 17.5” x 19.5” x 8.2”
Controller (44.5 cm x 50 cm x (44.5 cm x 50 cm x (44.5 cm x 50 cm x (44.5 cm x 50 cm x (44.5 cm x 50 cm x (44.5 cm x 50 cm x
21 cm) 21 cm) 21 cm) 21 cm) 21 cm) 21 cm)
Inlet/Outlet Port Size 3” FLANGE 3” FLANGE 4” FLANGE 3” FLANGE 3” FLANGE 4” FLANGE
Shipping Weight 96 lbs (43.5 kg) 99 lbs (45 kg) 286.5 lbs (129.7 kg) 96.5 lbs (43.7 kg) 99.5 lbs (45.1 kg) 287 lbs (130.1 kg)
ELECTRICAL
Voltage 100-240V / 50-60 Hz 100-240V / 50-60 Hz 100-240V / 50-60 Hz 100-240V / 50-60 Hz 100-240V / 50-60 Hz 100-240V / 50-60 Hz
Maximum Operating Pressure 125 psi (8.62 bar) 125 psi (8.62 bar) 125 psi (8.62 bar) 125 psi (8.62 bar) 125 psi (8.62 bar) 125 psi (8.62 bar)
Influent Water Temperature 2-40°C (36-104°F) 2-40°C (36-104°F) 2-40°C (36-104°F) 2-40°C (36-104°F) 2-40°C (36-104°F) 2-40°C (36-104°F)
Number of Lamps 4 4 5 4 4 5
FEATURES
Visual “Power On” YES YES YES YES YES YES
Visual Lamp Life Remaining YES YES YES YES YES YES
Sensor Reading Output (4-20mA) -- -- -- Optional with 260134 Optional with 260134 Optional with 260134
500
Hardness Iron Tannins
FLOW RATE (U.S. gpm)
< 7 grains (120 mg/L) < 0.3 mg/L < 0.1 mg/L 400
HI-FLO 290 Series
300 HI-FLO 180 Series
Cryptosporidium &Giardia HI-FLO 140 Series
eradicated at <10mJ/cm2
200
E. Coli eradicated
100 at 6.6mJ/cm2 1966
US Public Manufacturers NSF/EPA
Health Standard Standard
0
0 5 10 15 20 25 30 35 40 45