Protection www.schneider-electric.

com

Circuit protection
iK60N circuit breakers (curve C)

IEC/EN 60898-1
DB406121

Country approval pictogram

iK60N circuit breakers are circuit breakers which combine the following functions:
- circuit protection against short-circuit currents,
- circuit protection against overload currents,
- disconnection, opening and closing.

iK60N circuit breaker 50/60 Hz


Breaking capacity in short circuit (Icn) as per Service breaking
IEC/EN 60898-1 capacity (Ics)
Ph/Ph 400 V 100 % of Icn
Ph/N 230 V
Rating (In) 6 to 63 A 6000 A

Catalogue numbers
iK60N circuit breakers
Type 1P 2P 3P 4P
1 1 3 1 3 5 1 3 5 7

2 2 4 2 4 6 2 4 6 8

Auxiliaries Without auxiliaries


Vigi iC60 Without Vigi iC60
Rating (In) Curve Curve Curve Curve
C C C C
1A A9K24101 - - -
2A A9K24102 - - -
3A A9K24103 - - -
4A A9K24104 - - -
6A A9K27106 A9K27206 A9K24306 A9K24406
10 A A9K27110 A9K27210 A9K24310 A9K24410
16 A A9K27116 A9K27216 A9K24316 A9K24416
20 A A9K27120 A9K27220 A9K24320 A9K24420
25 A A9K27125 A9K27225 A9K24325 A9K24425
32 A A9K27132 A9K27232 A9K24332 A9K24432
40 A A9K24140 A9K24240 A9K24340 A9K24440
Operating frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Width in 9-mm modules 2 4 6 8
Accessories Padlocking device cat. no. A9A26970

4
Protection www.schneider-electric.com

Circuit protection
iK60N circuit breakers (curve C) (cont.)

bb Double clip for


dismounting with comb
busbar in place

bb Large circuit
labelling area

bb Padlocking device

bb Top or bottom electrical feeding.

Connection
Type Rating Tightening Copper cables
DB123060

torque Rigid Flexible or with


14 mm ferrule
6.5 mm
PZ2

C curve 1 to 32 A 2 N.m 1 to 25 mm2 1 to 16 mm2


40 to 63 A 3.5 N.m 1 to 35 mm2 1 to 25 mm2

5
Protection www.schneider-electric.com

Circuit protection
iK60N circuit breakers (curve C) (cont.)

Technical data
Main characteristics
According to IEC/EN 60898-1
Insulation voltage (Ui) 440 V AC
Pollution degree 2
Rated impulse withstand voltage (Uimp) 4 kV
Clip on DIN rail 35 mm. Thermal tripping Reference temperature 30°C
Temperature derating See module CA908007
Magnetic tripping C curve 5 to 10 In
Limitation class 3
Rated making and breaking capacity of an Icn1 = Icn
individual pole (Icn1)
Additional characteristics
Degree of protection Device in modular IP40
(IEC 60529) enclosure Insulation class II
Position d’installation indifférente. Endurance (O-C) Electrical 10,000 cycles
Mechanical 20,000 cycles
Overvoltage category (IEC 60364) III
IP40 Operating temperature -25°C to +60°C
Storage temperature -40°C to +85°C

Weight (g)
Circuit-breaker
Type iK60N
1P 100
2P (1P+N) 200
3P 300
4P (3P+N) 400

Dimensions (mm)
78.5
72
DB123392

3P+N / 4P
69.5
3P 54
50
1P+N / 2P 36
5.5
1P 18

4.4

94 85 45

64
4.6